Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2024-07-03 12:21:51
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 30649.91 | 661.69 | 661.69 |
Net Site Energy | 30113.41 | 650.11 | 650.11 |
Total Source Energy | 97068.27 | 2095.58 | 2095.58 |
Net Source Energy | 95369.18 | 2058.90 | 2058.90 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6350.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1712.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 263.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1641.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2839.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 910.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1961.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22368.66 |
Humidification | 14.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 279.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30649.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24654.10 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 6350.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1712.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 263.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1582.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2839.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 910.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1961.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22368.66 |
Humidification | General | 14.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 279.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 6350.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1712.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 263.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1641.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2839.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 910.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1961.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22368.66 |
Humidification | Unassigned | 14.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 279.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 266.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Other | 352.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 661.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 266.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Other | 352.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 661.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 559.880 | 1.83 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -23.38 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 536.498 | 1.75 |
Electricity Coming From Utility | 30113.413 | 98.25 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 30113.413 | 98.25 |
Total On-Site and Utility Electric Sources | 30649.911 | 100.00 |
Total Electricity End Uses | 30649.911 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 24654.10 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 24654.10 | 100.00 |
Total Water End Uses | 24654.10 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 3982.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | - | - | - | - | - | - | - | - | - | - | - | 15-JUN-10:00 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 673094.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 154849.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 236204.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 53135.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 84235.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18881.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2144759.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 673094.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3359.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 151268.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 236204.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 53135.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 84235.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 18881.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20112.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5422.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 834.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 5198.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8992.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2882.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6212.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 44.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 886.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 97068.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 434.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 112.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 194.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 62.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 134.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2095.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 434.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 112.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 194.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 62.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 134.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2095.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.27 | 0.401904 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.72 | 0.332625 | 0.283000 | 1.62 | 0.887001 | 0.500000 | 0.001145 |
CORE_MID VAV BOX COMPONENT | 54.40 | 0.349631 | 0.297000 | 16.16 | 0.932350 | 0.500000 | 0.001090 |
CORE_TOP VAV BOX COMPONENT | 5.50 | 0.345571 | 0.294000 | 1.62 | 0.921521 | 0.500000 | 0.001103 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.25 | 0.190819 | 0.162000 | 0.202752 | 0.508849 | 0.500000 | 0.001997 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.06 | 0.145672 | 0.124000 | 0.131008 | 0.388458 | 0.500000 | 0.002615 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.41 | 0.169670 | 0.144000 | 0.202693 | 0.452452 | 0.500000 | 0.002246 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.38 | 0.111280 | 0.095000 | 0.131389 | 0.300000 | 0.500000 | 0.003424 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 12.41 | 0.192382 | 0.164000 | 2.04 | 0.513019 | 0.500000 | 0.001980 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.05 | 0.371554 | 0.500000 | 0.002734 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 13.94 | 0.171350 | 0.146000 | 2.03 | 0.456933 | 0.500000 | 0.002224 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.24 | 0.125769 | 0.107000 | 1.31 | 0.335385 | 0.500000 | 0.003029 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.37 | 0.173709 | 0.148000 | 0.203475 | 0.463223 | 0.500000 | 0.002193 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.13 | 0.135601 | 0.115000 | 0.130524 | 0.361602 | 0.500000 | 0.002810 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.52 | 0.157089 | 0.134000 | 0.203723 | 0.418905 | 0.500000 | 0.002425 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.31 | 0.117490 | 0.100000 | 0.130994 | 0.313306 | 0.500000 | 0.003243 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 54022.96 |
CORE_MID VAV BOX REHEAT COIL | 539377.98 |
CORE_TOP VAV BOX REHEAT COIL | 54020.40 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6768.51 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4373.47 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6766.53 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4386.16 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 101629.06 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 67773.29 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 101496.51 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 56531.46 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 12879.41 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8520.58 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 12858.97 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7458.49 |
VAV_BOT WITH REHEAT HEATING COIL | 8964.73 |
VAV_MID WITH REHEAT HEATING COIL | 0.000000 |
VAV_TOP WITH REHEAT HEATING COIL | 0.000000 |
CAV_BAS HEATING COIL | 236503.08 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 11172.98 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 516.15 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 5161.45 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 516.15 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.467599 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.46 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.450083 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.58 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.41 | 2.29 | 10.82 | 2.29 | 9.82 | 9.82 | 0.300000 | 0.232714 | 9.82 |
VAV_MID WITH REHEAT | 52.02 | 22.84 | 104.04 | 22.84 | 92.20 | 92.20 | 0.300000 | 0.247730 | 92.20 |
VAV_TOP WITH REHEAT | 5.42 | 2.29 | 10.84 | 2.45 | 10.53 | 10.53 | 0.300000 | 0.233185 | 10.53 |
CAV_BAS | 0.000000 | 0.000000 | 5.27 | 1.20 | 5.27 | 5.27 | 1.00 | 0.227745 | 5.27 |
AIRLOOP DATACENTER BASEMENT | 24.58 | 24.58 | 24.58 | 24.58 | 24.58 | 24.58 | 1.00 | 0.999991 | 24.58 |
AIRLOOP DATACENTER BOT | 0.467599 | 0.467599 | 0.467599 | 0.467599 | 0.467599 | 0.467599 | 1.00 | 1.00 | 0.467599 |
AIRLOOP DATACENTER MID | 4.46 | 4.46 | 4.46 | 4.46 | 4.46 | 4.46 | 1.00 | 1.00 | 4.46 |
AIRLOOP DATACENTER TOP | 0.450083 | 0.450083 | 0.450083 | 0.450083 | 0.450083 | 0.450083 | 1.00 | 1.00 | 0.450083 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.82 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 92.20 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.53 | |
CAV_BAS_OA_CONTROLLER | 5.27 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.58 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.467599 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.46 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.450083 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 27.89 | 6.67 | 11.04 | 0.008046 | 0.007000 | 234324.83 | 0.006702 | 9.82 |
VAV_MID WITH REHEAT COOLING COIL | 28.18 | 6.67 | 11.04 | 0.008135 | 0.007000 | 2257743.53 | 0.064571 | 92.20 |
VAV_TOP WITH REHEAT COOLING COIL | 27.64 | 6.67 | 11.05 | 0.008004 | 0.007000 | 246382.93 | 0.007047 | 10.53 |
CAV_BAS COOLING COIL | 28.45 | 6.67 | 11.03 | 0.008346 | 0.007000 | 134260.26 | 0.003840 | 5.27 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.82 |
VAV_MID WITH REHEAT FAN | 92.20 |
VAV_TOP WITH REHEAT FAN | 10.53 |
CAV_BAS FAN | 5.27 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006702 | 0.000071 |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.064571 | 0.000007 |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007047 | 0.000068 |
CAV_BAS_COOLC_CONTROLLER | 0.003840 | 0.000124 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.58 | 515287.16 | 328802.14 | 0.012619 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.467599 | 9866.53 | 6263.65 | 0.000242 |
AIRLOOP DATACENTER MID COOLING COIL | 4.46 | 94171.31 | 59761.23 | 0.002306 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.450083 | 9507.97 | 6032.49 | 0.000233 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.58 | 24.58 | 24.58 | 24.58 | 515287.16 | 515287.16 | 11172.98 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.467599 | 0.467599 | 0.467599 | 0.467599 | 9866.53 | 9866.53 | 516.15 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.46 | 4.46 | 4.46 | 4.46 | 94171.31 | 94171.31 | 5161.45 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.450083 | 0.450083 | 0.450083 | 0.450083 | 9507.97 | 9507.97 | 516.15 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.58 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.467599 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.46 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.450083 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.58 | 515287.16 | 0.012619 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.467599 | 9866.53 | 0.000242 |
AIRLOOP DATACENTER MID HEATING COIL | 4.46 | 94171.31 | 0.002306 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.450083 | 9507.97 | 0.000233 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000026 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.082159 | 13281.27 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.082159 | 9.86 |
COOLSYS1_SUPPLY | 0.082159 | 9.86 |
SINGLE WATER PLANT LOOP | 0.015400 | 1.85 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.082159 | 0.082159 | 344863.33 | 8.33 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.041080 | 4597.54 |
COOLSYS1 CHILLER2 PUMP | 0.041080 | 4597.54 |
PLANT CIRC PUMP | 0.015400 | 3888.90 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.082159 | 0.041432 | 1448688.25 | 1448687.98 | 0.072773 |
COOLSYS1 CHILLER2 | 0.082159 | 0.041432 | 1448688.25 | 1448687.98 | 0.072773 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.015400 | 152911.36 | 77408.04 | 76455.68 | 7004.20 | 46444.83 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 634351.23 | 622083.11 | 0.015400 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.145546 | 17.47 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.145546 | 35677.21 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 53.27 | 1734102.03 | 10.65 | 216762.75 |
TOWERWATERSYS COOLTOWER 2 | 53.27 | 1734102.03 | 10.65 | 216762.75 |
Design Water Flow Rate [m3/s] Equipment # 27 | |
WSHPPLANT OPERATION SCHEME | 0.075125 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
51 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
52 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
53 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
54 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
55 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
56 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
57 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
58 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
59 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
60 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
61 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
62 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
63 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
64 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
65 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
66 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
67 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
68 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
69 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
70 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
71 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
72 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
73 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
74 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
75 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
76 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
77 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
78 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
79 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1309E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1321E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2756E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2766E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5896E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5903E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5426E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5431E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1580E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2332E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2977E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3606E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6066E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6560E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5556E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5883E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6239E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0110E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2576E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1206E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2225E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2224E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7703E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.6101E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1630E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2571E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3030E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3860E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6116E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6751E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5560E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5892E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1308E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1322E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2755E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2767E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5896E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5904E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5426E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5430E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3510E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4698E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1851E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3048E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0297E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0949E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6379E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6605E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7168E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7424E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4614E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5672E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5307E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4151E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8851E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.0771E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3252E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3782E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1533E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1922E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0104E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0266E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6380E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6608E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4920E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4932E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2886E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2896E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1402E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1409E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5426E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5431E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5197E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5879E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3112E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3654E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1575E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1953E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5560E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5893E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2700E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1690E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7659E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.9711E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5501E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.0381E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7703E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.6072E-003 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5177E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5850E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3088E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3605E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1536E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1834E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5557E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5883E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4919E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4931E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2885E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2894E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1401E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1406E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5426E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5431E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9101E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9651E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6550E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6949E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6076E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6224E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6381E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6609E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0075E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4827E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6194E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2600E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8049E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1457E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8851E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0771E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9312E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0285E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6814E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7753E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6258E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6839E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6379E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6604E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.0793E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4954E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5602E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.6640E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.9294E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4364E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.3990E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6803E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4413E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5383E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1569E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3241E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.2109E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1313E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.4843E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6997E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.8655E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8859E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2913E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5116E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0465E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1378E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3990E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6800E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6364E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1762E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2002E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8941E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3942E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7652E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.4843E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6997E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.0903E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.5049E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5734E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.6745E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.9427E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4449E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.4063E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6840E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4457E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5423E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1618E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3279E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.2183E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1358E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.4917E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7034E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.8661E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8880E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2920E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5133E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0498E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1398E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4063E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6837E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6391E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1793E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2031E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8969E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3999E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7687E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.4917E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7034E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 72976.38870 | 72976.38870 | 5.26973 | 5.26973 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 12.70000 | 9.15345E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 79182.66860 | 79182.66860 | 5.71828 | 5.71828 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 753482.98745 | 753482.98745 | 54.40141 | 54.40141 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 156942.65042 | 156942.65042 | 6.56199 | 10.77825 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 76230.33422 | 76230.33422 | 5.50407 | 5.50407 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 28567.50119 | 28567.50119 | 1.20513 | 1.20513 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 17170.61858 | 17170.61858 | 1.25156 | 1.25156 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 42.80000 | 1.07818E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 145.90778 | 145.90778 | 6.24964E-003 | 0.13533 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14494.84143 | 14494.84143 | 1.05652 | 1.05652 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 39.35650 | 1.07759E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 402.14033 | 402.14033 | 1.71544E-002 | 8.72129E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 19311.34137 | 19311.34137 | 1.40759 | 1.40759 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 1893.02937 | 1893.02937 | 7.99421E-002 | 0.13533 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18974.59705 | 18974.59705 | 1.38304 | 1.38304 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
17 | PERIMETER_MID_ZN_3 | Cooling | 170307.14593 | 170307.14593 | 12.41386 | 12.41386 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 71647.88680 | 71647.88680 | 3.04433 | 3.04433 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 151540.04832 | 151540.04832 | 11.04586 | 11.04586 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 47767.81867 | 47767.81867 | 2.03017 | 2.03017 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 191216.09052 | 191216.09052 | 13.93791 | 13.93791 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 71555.06090 | 71555.06090 | 3.04036 | 3.04036 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 167882.76222 | 167882.76222 | 12.23708 | 12.23708 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 41.83000 | 1.07801E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 39903.45493 | 39903.45493 | 1.69342 | 1.69342 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 18861.38510 | 18861.38510 | 1.37483 | 1.37483 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 42.60600 | 1.07815E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 9067.02823 | 9067.02823 | 0.38581 | 0.38581 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15570.96679 | 15570.96679 | 1.13499 | 1.13499 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 39.84150 | 1.07767E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 5997.69293 | 5997.69293 | 0.25524 | 0.25524 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 20857.31515 | 20857.31515 | 1.52032 | 1.52032 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 9052.69641 | 9052.69641 | 0.38519 | 0.38519 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 17971.24321 | 17971.24321 | 1.30994 | 1.30994 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 5253.62340 | 5253.62340 | 0.22342 | 0.22342 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8134.42376 | 8134.42376 | 0.46760 | 0.46760 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 33.16467 | 1.07653E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 77596.06906 | 77596.06906 | 4.46053 | 4.46053 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 33.16467 | 1.07653E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7828.80092 | 7828.80092 | 0.45008 | 0.45008 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 40.63367 | 1.07781E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371748.48154 | 427510.75377 | 21.37157 | 24.57731 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 33.97300 | 1.07667E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 12.70000 | 9.15345E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 179163.83 | 9.82371 | 9.82371 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 184.19 | 1.52292 | 1.52292 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1698386.18 | 92.20026 | 92.20026 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 2450.52 | 20.58651 | 20.58651 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 188321.01 | 10.52721 | 10.52721 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 244.81 | 2.45478 | 2.45478 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 |
7 | CAV_BAS | Cooling | Sensible | 89543.66 | 5.26973 | 5.26973 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 39626.51 | 1.20016 | 1.20016 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 427982.61 | 24.57752 | 24.57752 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 11172.98 | 0.33839 | 0.33839 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8174.53 | 0.46760 | 0.46760 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 516.15 | 1.56323E-002 | 1.56323E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78012.80 | 4.46053 | 4.46053 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 5161.45 | 0.15632 | 0.15632 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8001.75 | 0.45008 | 0.45008 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 516.15 | 1.56323E-002 | 1.56323E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.26973 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.40190 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.71828 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33263 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28300 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61827 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88700 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14543E-003 |
12 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 54022.95732 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 54.40141 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34963 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29700 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.15722 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93235 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08972E-003 |
20 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 539377.97908 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.50407 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34557 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29400 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61820 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92152 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10252E-003 |
28 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 54020.40008 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25156 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19082 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16200 |
32 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20275 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50885 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.99666E-003 |
36 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6768.50617 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05652 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14567 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12400 |
40 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13101 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38846 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.61547E-003 |
44 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4373.46586 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.40759 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16967 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14400 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20269 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45245 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.24554E-003 |
52 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6766.53213 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38304 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11128 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.50000E-002 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13139 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.42379E-003 |
60 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4386.16347 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.41386 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19238 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16400 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03587 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51302 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.98043E-003 |
68 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 101629.05787 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.04586 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37155 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.73446E-003 |
73 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 67773.28597 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.93791 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17135 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14600 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03493 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45693 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.22352E-003 |
81 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 101496.51015 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.23708 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12577 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10700 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30937 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33539 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.02935E-003 |
89 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 56531.45974 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.37483 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17371 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14800 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20348 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46322 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.19333E-003 |
97 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12879.40735 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13499 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13560 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11500 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13052 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36160 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.80972E-003 |
105 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8520.58463 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.52032 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15709 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13400 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20372 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41891 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42537E-003 |
113 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12858.97162 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30994 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11749 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13099 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31331 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.24284E-003 |
121 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7458.48905 |
122 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46760 |
123 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.46053 |
124 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45008 |
125 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.57731 |
126 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.40849 |
127 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28612 |
128 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.81699 |
129 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28612 |
130 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.82371 |
131 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.82371 |
132 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.23271 |
134 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 52.01806 |
135 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.84080 |
136 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 104.03611 |
137 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 22.84080 |
138 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 92.20026 |
139 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 92.20026 |
140 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.24773 |
142 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.42208 |
143 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28691 |
144 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.84415 |
145 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.45478 |
146 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.52721 |
147 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.52721 |
148 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
149 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.23318 |
150 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
151 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
152 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.26973 |
153 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
154 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.26973 |
155 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.26973 |
156 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
157 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.22775 |
158 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.57731 |
159 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.57731 |
160 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.57731 |
161 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.57731 |
162 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.57752 |
163 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.57752 |
164 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
165 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
166 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46760 |
167 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46760 |
168 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46760 |
169 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46760 |
170 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46760 |
171 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46760 |
172 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
173 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
174 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.46053 |
175 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.46053 |
176 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.46053 |
177 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.46053 |
178 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.46053 |
179 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.46053 |
180 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
181 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
182 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45008 |
183 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45008 |
184 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45008 |
185 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45008 |
186 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45008 |
187 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45008 |
188 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
189 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
190 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.82371 |
191 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 92.20026 |
192 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.52721 |
193 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.26973 |
194 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.57752 |
195 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46760 |
196 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.46053 |
197 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45008 |
198 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.82371 |
199 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.88668 |
200 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
201 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.03944 |
202 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.04596E-003 |
203 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
204 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 234324.83090 |
205 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.70166E-003 |
206 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.82371 |
207 | Coil:Heating:Electric | VAV_BOT WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 8964.73263 |
208 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.82371 |
209 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.70166E-003 |
210 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.10556E-005 |
211 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 92.20026 |
212 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.18000 |
213 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
214 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.03973 |
215 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.13536E-003 |
216 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
217 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2257743.53389 |
218 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.45712E-002 |
219 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 92.20026 |
220 | Coil:Heating:Electric | VAV_MID WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
221 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 92.20026 |
222 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.45712E-002 |
223 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.37466E-006 |
224 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.52721 |
225 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.63606 |
226 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
227 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04866 |
228 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00375E-003 |
229 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
230 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 246382.93455 |
231 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.04652E-003 |
232 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.52721 |
233 | Coil:Heating:Electric | VAV_TOP WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
234 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.52721 |
235 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.04652E-003 |
236 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.75781E-005 |
237 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.26973 |
238 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
239 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.44787 |
240 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
241 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02905 |
242 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.34628E-003 |
243 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
244 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 134260.26158 |
245 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.83983E-003 |
246 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.26973 |
247 | Coil:Heating:Electric | CAV_BAS HEATING COIL | Design Size Nominal Capacity [W] | 236503.07582 |
248 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.26973 |
249 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.83983E-003 |
250 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.24014E-004 |
251 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.57752 |
252 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
253 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.57752 |
254 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 515287.16407 |
255 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 328802.13767 |
256 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.26193E-002 |
257 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.57752 |
258 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.57752 |
259 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.57752 |
260 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.57752 |
261 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 515287.16407 |
262 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 515287.16407 |
263 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11172.98038 |
264 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
265 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.57752 |
266 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.57752 |
267 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 515287.16407 |
268 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.26193E-002 |
269 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11172.98038 |
270 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.58707E-005 |
271 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
272 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
273 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
274 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46760 |
275 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
276 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46760 |
277 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9866.53423 |
278 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6263.64517 |
279 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41631E-004 |
280 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46760 |
281 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46760 |
282 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46760 |
283 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46760 |
284 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9866.53423 |
285 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9866.53423 |
286 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 516.14541 |
287 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
288 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46760 |
289 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46760 |
290 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9866.53423 |
291 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41631E-004 |
292 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 516.14541 |
293 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.46053 |
294 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
295 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.46053 |
296 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 94171.30999 |
297 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 59761.22668 |
298 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30625E-003 |
299 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.46053 |
300 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.46053 |
301 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.46053 |
302 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.46053 |
303 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 94171.30999 |
304 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 94171.30999 |
305 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 5161.45407 |
306 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
307 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.46053 |
308 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.46053 |
309 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 94171.30999 |
310 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30625E-003 |
311 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5161.45407 |
312 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45008 |
313 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
314 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45008 |
315 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9507.96720 |
316 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6032.48541 |
317 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32850E-004 |
318 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45008 |
319 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45008 |
320 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45008 |
321 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45008 |
322 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9507.96720 |
323 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9507.96720 |
324 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 516.14541 |
325 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
326 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45008 |
327 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45008 |
328 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9507.96720 |
329 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32850E-004 |
330 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 516.14541 |
331 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.21592E-002 |
332 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 13281.27201 |
333 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.21592E-002 |
334 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.85910 |
335 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.21592E-002 |
336 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.21592E-002 |
337 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 344863.33264 |
338 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
339 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.21592E-002 |
340 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.85910 |
341 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 4.10796E-002 |
342 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4597.53625 |
343 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 4.10796E-002 |
344 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4597.53625 |
345 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.21592E-002 |
346 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.14323E-002 |
347 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1448688.24523 |
348 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1448687.98000 |
349 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.27730E-002 |
350 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.21592E-002 |
351 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.14323E-002 |
352 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1448688.24523 |
353 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1448687.98000 |
354 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.27730E-002 |
355 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.54001E-002 |
356 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.84801 |
357 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.54001E-002 |
358 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3888.90128 |
359 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.54001E-002 |
360 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 152911.36091 |
361 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 77408.04233 |
362 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 76455.68045 |
363 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
364 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 46444.82540 |
365 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 634351.23316 |
366 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 622083.11000 |
367 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.54001E-002 |
368 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
369 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
370 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
371 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
372 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
373 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14555 |
374 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.46553 |
375 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14555 |
376 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 35677.21229 |
377 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 53.26695 |
378 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1734102.02778 |
379 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.65339 |
380 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 216762.75347 |
381 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 53.26695 |
382 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1734102.02778 |
383 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.65339 |
384 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 216762.75347 |
385 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 27 | 7.51250E-002 |
386 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 27 | 7.51250E-002 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 281656.50 | 190505.02 | 91151.47 | 0.68 | 62612.88 | 635.05 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2667459.68 | 1798180.01 | 869279.67 | 0.67 | 580575.13 | 5888.52 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 299786.62 | 203282.06 | 96504.57 | 0.68 | 67707.84 | 686.73 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 154681.59 | 103728.07 | 50953.52 | 0.67 | 32906.70 | 333.76 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 9.21 | 31.42 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 9.21 | 31.42 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2533102267 | 0.2685549975 | Pass | Pass | 0.8037649321 | 2.6551461207 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1264445399 | 0.2094981010 | Pass | Pass | 0.1198045946 | 0.3233361902 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.0411116818E-002 | 8.9439609697E-002 | Pass | Pass | 1.4525287768E-002 | 0.1197160249 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.7676060428E-002 | 1.1151001630E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1088681425 | 0.1486158081 | Pass | Pass | 0.1193852373 | 0.3232850546 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1145063200 | 0.1533480778 | Pass | Pass | 0.1195600901 | 0.3235453312 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1353488065 | 0.1684869308 | Pass | Pass | 0.1379327821 | 0.3910315938 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1199695579 | 0.1697712018 | Pass | Pass | 0.1186446415 | 0.3223823236 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.8645289463E-002 | 6.8839033839E-002 | Pass | Pass | 1.4213456310E-002 | 0.1183895815 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.3586265145E-002 | 7.0223187025E-002 | Pass | Pass | 1.4230730097E-002 | 0.1184631425 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.3641896385E-002 | 0.1088898734 | Pass | Pass | 1.3984798110E-002 | 0.1174290727 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.5980138921E-002 | 8.5854342391E-002 | Pass | Pass | 1.4068864299E-002 | 0.1177814862 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.9339707837E-002 | 2.7125725419E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.2927444795E-002 | 2.5977703044E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.9435965278E-002 | 5.6963654930E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.9649358488E-002 | 4.3243476380E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.7351579900E-002 | 2.7014186891E-002 | Pass | Pass | 0.3495245412 | 1.3971864075 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.0038164032E-003 | 1.4447538063E-002 | Pass | Pass | 7.7917294305E-002 | 0.5252594563 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.0813274941E-002 | 3.5856229107E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1787466425E-004 | 1.4587164311E-004 | Pass | Pass | 2.0225345047E-003 | 1.4862751920E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.7135214762E-005 | 1.1219837409E-004 | Pass | Pass | 5.8376235090E-003 | 2.9233437376E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.6535248662E-005 | 1.0780042249E-004 | Pass | Pass | 1.9054486278E-002 | 8.2045832459E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.2992814811E-004 | 3.7420837456E-004 | Pass | Pass | 6.4442840515E-005 | 1.0867485912E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3638.66 | -62.7 | 0.00 | -7795.0 | 45582.32 | 41363.30 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
North Total or Average | 1390.74 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.865 | 0.220 | 0.242 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 116.04 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 1042.11 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.93 | 0.0000 | Y | 7.45 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.88 | 0.0000 | Y | 4.79 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.74 | 0.0000 | Y | 7.39 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.85 | 0.0000 | Y | 4.79 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.90 | 0.0000 | Y | 74.43 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.86 | 0.0000 | Y | 47.88 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.73 | 0.0000 | Y | 73.85 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.82 | 0.0000 | Y | 47.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.90 | 0.0000 | Y | 7.44 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.86 | 0.0000 | Y | 4.79 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.73 | 0.0000 | Y | 7.38 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.82 | 0.0000 | Y | 4.78 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.66 | 0.0000 | Y | 32.85 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 16.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 539.77 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 41.85 | 41.85 | 101.76 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.85 | 62.85 | 10.85 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.85 | 46.68 | 150.86 | |
Exterior Lighting Total | 31088.59 | 263.47 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2863863.35 | |||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1448687.98 | 6.01 | 1440615.25 | 5.99 | 9.21 | 31.42 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1448687.98 | 6.01 | 1440615.25 | 5.99 | 9.21 | 31.42 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 637258.10 | |||||
CENTRAL BOILER | Boiler:HotWater | 622083.11 | 1.00 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1734102.03 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1734102.03 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 234324.83 | 281656.50 | 190505.02 | 91151.47 | 0.68 | - | 62612.88 | 635.05 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2257743.53 | 2667459.68 | 1798180.01 | 869279.67 | 0.67 | - | 580575.13 | 5888.52 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 246382.93 | 299786.62 | 203282.06 | 96504.57 | 0.68 | - | 67707.84 | 686.73 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 134260.26 | 154681.59 | 103728.07 | 50953.52 | 0.67 | - | 32906.70 | 333.76 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 515287.16 | 328802.14 | 186485.03 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9866.53 | 6263.65 | 3602.89 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 94171.31 | 59761.23 | 34410.08 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9507.97 | 6032.49 | 3475.48 | 0.63 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 54022.96 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 539377.98 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 54020.40 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6768.51 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4373.47 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6766.53 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4386.16 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 101629.06 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 67773.29 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 101496.51 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 56531.46 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12879.41 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8520.58 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12858.97 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7458.49 | 1.00 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | 8964.73 | 1.00 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | 236503.08 | 1.00 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 515287.16 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9866.53 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 94171.31 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9507.97 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 11172.98 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 516.15 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 5161.45 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 516.15 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.82 | 21228.52 | 2160.95 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 92.20 | 199239.85 | 2160.95 | 1.00 | 1.08 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.53 | 22627.86 | 2149.46 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.27 | 11461.07 | 2174.89 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.58 | 40534.41 | 1649.25 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 523.76 | 1120.11 | 1.00 | 1.64 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.46 | 4996.27 | 1120.11 | 1.00 | 1.16 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 504.14 | 1120.11 | 1.00 | 1.66 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.082159 | 13281.27 | 161652.92 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.041080 | 4597.54 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.041080 | 4597.54 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.015400 | 3888.90 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.145546 | 35677.21 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 72976.39 | 72976.39 | 26.26 | 5.270 | 5.270 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00748 | 35.62 | 0.01077 | 1.200 | 0.00 |
CORE_BOTTOM | 79182.67 | 79182.67 | 31.72 | 5.718 | 5.718 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00739 | 35.62 | 0.01077 | 1.078 | 0.00 |
CORE_MID | 753482.99 | 753482.99 | 301.86 | 54.401 | 54.401 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 35.62 | 0.01077 | 10.778 | 0.00 |
CORE_TOP | 76230.33 | 76230.33 | 30.54 | 5.504 | 5.504 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 35.62 | 0.01077 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 17170.62 | 17170.62 | 54.79 | 1.252 | 1.252 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00726 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14494.84 | 14494.84 | 71.77 | 1.057 | 1.057 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00720 | 39.36 | 0.01078 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 19311.34 | 19311.34 | 61.61 | 1.408 | 1.408 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00723 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18974.60 | 18974.60 | 93.95 | 1.383 | 1.383 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00715 | 41.96 | 0.01078 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 170307.15 | 170307.15 | 543.40 | 12.414 | 12.414 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00730 | 42.70 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 151540.05 | 151540.05 | 750.29 | 11.046 | 11.046 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00722 | 39.60 | 0.01078 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 191216.09 | 191216.09 | 610.10 | 13.938 | 13.938 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00727 | 42.80 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 167882.76 | 167882.76 | 831.21 | 12.237 | 12.237 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00720 | 41.83 | 0.01078 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 18861.39 | 18861.39 | 60.18 | 1.375 | 1.375 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00729 | 42.61 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15570.97 | 15570.97 | 77.09 | 1.135 | 1.135 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 24.00 | 24.00 | 0.00723 | 39.84 | 0.01078 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20857.32 | 20857.32 | 66.55 | 1.520 | 1.520 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00726 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17971.24 | 17971.24 | 88.98 | 1.310 | 1.310 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00720 | 41.96 | 0.01078 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8134.42 | 8134.42 | 224.69 | 0.468 | 0.468 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 33.16 | 0.01077 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 77596.07 | 77596.07 | 2143.38 | 4.461 | 4.461 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 33.16 | 0.01077 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7828.80 | 7828.80 | 216.25 | 0.450 | 0.450 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 27.00 | 27.00 | 0.00709 | 40.63 | 0.01078 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371748.48 | 427510.75 | 545.52 | 21.372 | 24.577 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 33.97 | 0.01077 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 26.39 | 0.00915 | 12.70 | 0.00915 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 23.79 | 0.00915 | 12.70 | 0.00915 | 1.078 | 0.00 | |
CORE_MID | 156942.65 | 156942.65 | 62.87 | 6.562 | 10.778 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 10.778 | 0.00 |
CORE_TOP | 28567.50 | 28567.50 | 11.44 | 1.205 | 1.205 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 145.91 | 145.91 | 0.47 | 0.006 | 0.135 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00875 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 402.14 | 402.14 | 1.99 | 0.017 | 0.087 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00841 | 12.70 | 0.00915 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 1893.03 | 1893.03 | 6.04 | 0.080 | 0.135 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00824 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 21.60 | 0.00915 | 12.70 | 0.00915 | 0.087 | 0.00 | |
PERIMETER_MID_ZN_3 | 71647.89 | 71647.89 | 228.61 | 3.044 | 3.044 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 47767.82 | 47767.82 | 236.50 | 2.030 | 2.030 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 71555.06 | 71555.06 | 228.30 | 3.040 | 3.040 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 39903.45 | 39903.45 | 197.57 | 1.693 | 1.693 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00818 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 9067.03 | 9067.03 | 28.93 | 0.386 | 0.386 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00811 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 5997.69 | 5997.69 | 29.70 | 0.255 | 0.255 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00811 | 12.70 | 0.00915 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 9052.70 | 9052.70 | 28.88 | 0.385 | 0.385 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00811 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 5253.62 | 5253.62 | 26.01 | 0.223 | 0.223 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.31 | 0.00701 | 12.70 | 0.00915 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.80 | 0.00825 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.82 | 9.82 | 1.52 | 1.52 | 9.8237 | 2.2861 | 9.8237 | 0.2327 | 0.3000 |
VAV_MID WITH REHEAT | 92.20 | 92.20 | 20.59 | 20.59 | 92.2003 | 22.8408 | 92.2003 | 0.2477 | 0.3000 |
VAV_TOP WITH REHEAT | 10.53 | 10.53 | 2.45 | 2.45 | 10.5272 | 2.4548 | 10.5272 | 0.2332 | 0.3000 |
CAV_BAS | 5.27 | 5.27 | 1.20 | 1.20 | 5.2697 | 1.2002 | 5.2697 | 0.2277 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.58 | 24.58 | 0.34 | 0.34 | 24.5775 | 24.5773 | 24.5775 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4676 | 0.4676 | 0.4676 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.46 | 4.46 | 0.16 | 0.16 | 4.4605 | 4.4605 | 4.4605 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4501 | 0.4501 | 0.4501 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 54022.957 | 54022.957 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 54022.96 | 35981.13 | 1.077825 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 539377.979 | 539377.979 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 539377.98 | 359811.31 | 10.778248 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 156942.65 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 54020.400 | 54020.400 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 54020.40 | 40230.85 | 1.205126 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 28567.50 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6768.506 | 6768.506 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6768.51 | 4517.79 | 0.135332 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00874893 | 56.4648 | 145.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4373.466 | 4373.466 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4373.47 | 2911.44 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00840845 | 54.2965 | 402.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 6766.532 | 6766.532 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6766.53 | 4517.89 | 0.135335 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00824423 | 53.2498 | 1893.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4386.163 | 4386.163 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 4386.16 | 2911.44 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 101629.058 | 101629.058 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 101629.06 | 101629.06 | 3.044327 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00814328 | 52.6056 | 71647.89 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 67773.286 | 67773.286 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 67773.29 | 67773.29 | 2.030168 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00814041 | 52.5872 | 47767.82 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 101496.510 | 101496.510 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 101496.51 | 101496.51 | 3.040356 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00814375 | 52.6086 | 71555.06 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 56531.460 | 56531.460 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 56531.46 | 56531.46 | 1.693416 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00818180 | 52.8510 | 39903.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 12879.407 | 12879.407 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12879.41 | 12879.41 | 0.385806 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00811173 | 52.4044 | 9067.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 8520.585 | 8520.585 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8520.58 | 8520.58 | 0.255236 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00810975 | 52.3918 | 5997.69 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 12858.972 | 12858.972 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12858.97 | 12858.97 | 0.385194 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00811227 | 52.4078 | 9052.70 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7458.489 | 7458.489 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7458.49 | 7458.49 | 0.223421 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00814352 | 52.6070 | 5253.62 | 0.00 | -999.00 | -999.00 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 234324.831 | -999.000 | 9.823711 | 0.00670166 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 234324.83 | 206107.56 | 9.823711 | 27.89 | 17.35 | 0.00804596 | 11.04 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.6694 | 24.00 | 0.00733272 | 39.5301 | 134711.96 | 0.00 | 234637.52 | 218359.82 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_BOT WITH REHEAT | 8964.733 | 8964.733 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8964.73 | 8964.73 | 2.947113 | 10.28 | 10.28 | 0.00909827 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 68.8979 | 21.46 | 0.00869434 | 54.5413 | 0.00 | 0.00 | -999.00 | -999.00 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2257743.534 | -999.000 | 92.200259 | 0.06457118 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2257743.53 | 1969425.29 | 92.200259 | 28.18 | 17.53 | 0.00813536 | 11.04 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 22.0238 | 24.00 | 0.00737846 | 39.7741 | 1252635.46 | 0.00 | 2260681.23 | 2082817.35 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_MID WITH REHEAT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 27.660078 | 14.91 | 13.30 | 0.00886114 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 73.4127 | 21.00 | 0.00807100 | 52.1452 | 359447.17 | 0.00 | -999.00 | -999.00 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 246382.935 | -999.000 | 10.527210 | 0.00704652 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 246382.93 | 217442.12 | 10.527210 | 27.64 | 17.23 | 0.00800375 | 11.05 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 19.2881 | 24.00 | 0.00733736 | 39.5551 | 143987.19 | 0.00 | 246717.45 | 230697.93 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_TOP WITH REHEAT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 3.158163 | 15.66 | 13.49 | 0.00875160 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 64.2937 | 21.00 | 0.00803160 | 51.8942 | 41876.94 | 0.00 | -999.00 | -999.00 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 134260.262 | -999.000 | 5.269728 | 0.00383983 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 134260.26 | 114627.97 | 5.269728 | 28.45 | 17.79 | 0.00834628 | 11.03 | 9.77 | 0.00700000 | 41.54 | 0.01077963 | 23.52 | 22.7745 | 24.00 | 0.00751927 | 40.5239 | 66310.86 | 0.00 | 134432.12 | 120851.73 |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | CAV_BAS | 236503.076 | 236503.076 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 236503.08 | 236503.08 | 5.269728 | 2.89 | 2.89 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 22.7745 | 26.39 | 0.00915345 | 42.6736 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 515287.164 | 328802.138 | 24.577524 | 0.01261935 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 466199.23 | 460750.61 | -999.0 | 28.61 | 16.80 | 0.00709371 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | -999.0000 | 27.00 | 0.00704216 | 31.7851 | 371274.65 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9866.534 | 6263.645 | 0.467599 | 0.00024163 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 8938.31 | 8699.46 | -999.0 | 28.45 | 16.85 | 0.00721580 | 12.80 | 10.55 | 0.00700000 | 41.70 | 0.01077992 | 23.56 | -999.0000 | 27.00 | 0.00709037 | 31.9985 | 7998.68 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94171.310 | 59761.227 | 4.460526 | 0.00230625 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 85319.49 | 82937.03 | -999.0 | 28.43 | 16.85 | 0.00722562 | 12.80 | 10.55 | 0.00700000 | 40.63 | 0.01077808 | 23.27 | -999.0000 | 27.00 | 0.00709454 | 32.0173 | 76410.29 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9507.967 | 6032.485 | 0.450083 | 0.00023285 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 8615.39 | 8380.36 | -999.0 | 28.46 | 16.86 | 0.00722056 | 12.80 | 10.55 | 0.00700000 | 41.70 | 0.01077992 | 23.56 | -999.0000 | 27.00 | 0.00709240 | 32.0076 | 7823.66 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 515287.164 | 515287.164 | 24.577524 | 0.01261935 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 515287.16 | 515287.16 | 24.577524 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 1.3768 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9866.534 | 9866.534 | 0.467599 | 0.00024163 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9866.53 | 9866.53 | 0.467599 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.3431 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94171.310 | 94171.310 | 4.460526 | 0.00230625 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 94171.31 | 94171.31 | 4.460526 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.5046 | 25.31 | 0.00701121 | 34.9605 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9507.967 | 9507.967 | 0.450083 | 0.00023285 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9507.97 | 9507.97 | 0.450083 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4732 | 24.80 | 0.00825142 | 42.3286 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 11172.980 | 11172.980 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11172.98 | 11172.98 | 24.577524 | 0.17 | 0.17 | 0.00702965 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 1.3768 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 516.15 | 516.15 | 0.467599 | 0.42 | 0.42 | 0.00707199 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.3431 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 5161.454 | 5161.454 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 5161.45 | 5161.45 | 4.460526 | 0.45 | 0.45 | 0.00708629 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.5046 | 25.31 | 0.00701121 | 34.9605 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 516.15 | 516.15 | 0.450083 | 0.44 | 0.44 | 0.00828275 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4732 | 24.80 | 0.00825142 | 42.3286 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 54022.957 | 54022.957 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 54022.96 | 35981.13 | 1.0000 | 1.29726454 | 1.077825 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54022.96 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 539377.979 | 539377.979 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 539377.98 | 359811.31 | 1.0000 | 12.97264538 | 10.778248 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 539377.98 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.60 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 156942.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 54020.400 | 54020.400 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 54020.40 | 40230.85 | 1.0000 | 1.45048396 | 1.205126 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54020.40 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 28567.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 6768.506 | 6768.506 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6768.51 | 4517.79 | 1.0000 | 0.16288451 | 0.135332 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6768.51 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.99 | 0.00874893 | 21.00 | 0.00874893 | 56.4648 | 145.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4373.466 | 4373.466 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4373.47 | 2911.44 | 1.0000 | 0.10496897 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4373.47 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.97 | 0.00840845 | 21.00 | 0.00840845 | 54.2965 | 402.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 6766.532 | 6766.532 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6766.53 | 4517.89 | 1.0000 | 0.16288807 | 0.135335 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6766.53 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.90 | 0.00824423 | 21.00 | 0.00824423 | 53.2498 | 1893.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4386.163 | 4386.163 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 4386.16 | 2911.44 | 1.0000 | 0.10496897 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4386.16 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 101629.058 | 101629.058 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 101629.06 | 101629.06 | 1.0000 | 3.66413643 | 3.044327 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 101629.06 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00814328 | 21.00 | 0.00814328 | 52.6056 | 71647.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 67773.286 | 67773.286 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 67773.29 | 67773.29 | 1.0000 | 2.44349964 | 2.030168 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67773.29 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00814041 | 21.00 | 0.00814041 | 52.5872 | 47767.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 101496.510 | 101496.510 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 101496.51 | 101496.51 | 1.0000 | 3.65935755 | 3.040356 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 101496.51 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00814375 | 21.00 | 0.00814375 | 52.6086 | 71555.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 56531.460 | 56531.460 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 56531.46 | 56531.46 | 1.0000 | 2.03818657 | 1.693416 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56531.46 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.92 | 0.00818180 | 21.00 | 0.00818180 | 52.8510 | 39903.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 12879.407 | 12879.407 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12879.41 | 12879.41 | 1.0000 | 0.46435445 | 0.385806 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12879.41 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00811173 | 21.00 | 0.00811173 | 52.4044 | 9067.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8520.585 | 8520.585 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8520.58 | 8520.58 | 1.0000 | 0.30720136 | 0.255236 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8520.58 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00810975 | 21.00 | 0.00810975 | 52.3918 | 5997.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12858.972 | 12858.972 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12858.97 | 12858.97 | 1.0000 | 0.46361766 | 0.385194 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12858.97 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00811227 | 21.00 | 0.00811227 | 52.4078 | 9052.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7458.489 | 7458.489 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7458.49 | 7458.49 | 1.0000 | 0.26890854 | 0.223421 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7458.49 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00814352 | 21.00 | 0.00814352 | 52.6070 | 5253.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 234324.831 | -999.000 | 9.823711 | 0.00670166 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7970 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.823711 | 11.82376867 | 4197.9300 | 999.8980 | 82.15080591 | 15.00 | 6.67 | 8.33 | 2872711.56 | 8.1569 | 8.156922 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 234324.83 | 206107.56 | 1.0000 | 11.82376867 | 9.823711 | 27.89 | 17.35 | 0.00804596 | 48561.2 | 11.04 | 9.78 | 0.00700000 | 28743.1 | 6.70097686 | 6.67 | 15.00 | 8.33 | 21228.515 | 213096.32 | 42.80 | 0.01078182 | 23.86 | 2.03050000 | 20.6694 | 24.00 | 0.00733272 | 24.00 | 0.00733272 | 39.5301 | 134711.96 | 0.00 | 234637.52 | 218359.82 | 11.82376867 | 27.89 | 17.36 | 0.00804596 | 48561.2 | 9.78 | 9.76 | 0.00749947 | 28716.7 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8964.733 | 8964.733 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.823711 | 11.82376867 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8964.73 | 8964.73 | 1.0000 | 3.54713060 | 2.947113 | 10.28 | 10.28 | 0.00909827 | 33262.9 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8964.73 | 12.70 | 0.00915345 | 12.70 | 2.03050000 | 68.8979 | 4.93 | 0.00897605 | 21.46 | 0.00869434 | 54.5413 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2257743.534 | -999.000 | 92.200259 | 0.06457118 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9632 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 92.200259 | 110.97176900 | 4197.9300 | 999.8980 | 82.15080591 | 15.00 | 6.67 | 8.33 | 2872711.56 | 78.5928 | 78.592768 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 2257743.53 | 1969425.29 | 1.0000 | 110.97176900 | 92.200259 | 28.18 | 17.53 | 0.00813536 | 49088.6 | 11.04 | 9.78 | 0.00700000 | 28743.4 | 64.56459234 | 6.67 | 15.00 | 8.33 | 199239.850 | 2058503.68 | 42.80 | 0.01078182 | 23.86 | 20.30600000 | 22.0238 | 24.00 | 0.00737846 | 24.00 | 0.00737846 | 39.7741 | 1252635.46 | 0.00 | 2260681.23 | 2082817.35 | 110.97176900 | 28.18 | 17.53 | 0.00813536 | 49088.6 | 9.78 | 9.76 | 0.00749911 | 28716.9 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 92.200259 | 110.97176900 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 33.29153070 | 27.660078 | 14.91 | 13.30 | 0.00886114 | 37392.9 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 20.30600000 | 73.4127 | 21.03 | 0.00805402 | 21.00 | 0.00807100 | 52.1452 | 359447.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 246382.935 | -999.000 | 10.527210 | 0.00704652 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7186 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.527210 | 12.67049692 | 4197.9300 | 999.8980 | 82.15080591 | 15.00 | 6.67 | 8.33 | 2872711.56 | 8.5767 | 8.576668 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 246382.93 | 217442.12 | 1.0000 | 12.67049692 | 10.527210 | 27.64 | 17.23 | 0.00800375 | 48197.9 | 11.05 | 9.78 | 0.00700000 | 28752.5 | 7.04580192 | 6.67 | 15.00 | 8.33 | 22627.864 | 223755.07 | 42.80 | 0.01078182 | 23.86 | 2.03050000 | 19.2881 | 24.00 | 0.00733736 | 24.00 | 0.00733736 | 39.5551 | 143987.19 | 0.00 | 246717.45 | 230697.93 | 12.67049692 | 27.64 | 17.24 | 0.00800375 | 48197.9 | 9.78 | 9.76 | 0.00750186 | 28726.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.527210 | 12.67049692 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 3.80114908 | 3.158163 | 15.66 | 13.49 | 0.00875160 | 37881.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 2.03050000 | 64.2937 | 21.00 | 0.00802804 | 21.00 | 0.00803160 | 51.8942 | 41876.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 134260.262 | -999.000 | 5.269728 | 0.00383983 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3553 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:VariableVolume | 5.269728 | 6.34261847 | 4197.9300 | 999.8980 | 82.15080591 | 15.00 | 6.67 | 8.33 | 2872711.56 | 4.6736 | 4.673642 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 134260.26 | 114627.97 | 1.0000 | 6.34261847 | 5.269728 | 28.45 | 17.79 | 0.00834628 | 49900.5 | 11.03 | 9.77 | 0.00700000 | 28732.5 | 3.83943478 | 6.67 | 15.00 | 8.33 | 11461.070 | 122799.19 | 41.54 | 0.01077963 | 23.52 | 1.20015641 | 22.7745 | 24.00 | 0.00751927 | 24.00 | 0.00751927 | 40.5239 | 66310.86 | 0.00 | 134432.12 | 120851.73 | 6.34261847 | 28.45 | 17.80 | 0.00834628 | 49900.5 | 9.77 | 9.75 | 0.00749632 | 28705.4 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 236503.076 | 236503.076 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:VariableVolume | 5.269728 | 6.34261847 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 236503.08 | 236503.08 | 1.0000 | 6.34261847 | 5.269728 | 2.89 | 2.89 | 0.00915345 | 25847.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 236503.08 | 12.70 | 0.00915345 | 12.70 | 1.20015641 | 22.7745 | 0.00 | 0.00915345 | 26.39 | 0.00915345 | 42.6736 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 515287.164 | 328802.138 | 24.577524 | 0.01261935 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0269 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 466199.23 | 460750.61 | 0.9047 | -999.0 | -999.0 | 28.61 | 16.80 | 0.00709371 | 46866.8 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 466199.23 | 42.80 | 0.01078182 | 23.86 | 0.33839277 | -999.0000 | 27.00 | 0.00704216 | 27.00 | 0.00704216 | 31.7851 | 371274.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9866.534 | 6263.645 | 0.467599 | 0.00024163 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2538 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 8938.31 | 8699.46 | 0.9059 | -999.0 | -999.0 | 28.45 | 16.85 | 0.00721580 | 47011.9 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8938.31 | 41.70 | 0.01077992 | 23.56 | 0.01563234 | -999.0000 | 27.00 | 0.00709037 | 27.00 | 0.00709037 | 31.9985 | 7998.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 94171.310 | 59761.227 | 4.460526 | 0.00230625 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2721 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 85319.49 | 82937.03 | 0.9060 | -999.0 | -999.0 | 28.43 | 16.85 | 0.00722562 | 47022.0 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85319.49 | 40.63 | 0.01077808 | 23.27 | 0.15632344 | -999.0000 | 27.00 | 0.00709454 | 27.00 | 0.00709454 | 32.0173 | 76410.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9507.967 | 6032.485 | 0.450083 | 0.00023285 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2627 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | Sensible | 8615.39 | 8380.36 | 0.9061 | -999.0 | -999.0 | 28.46 | 16.86 | 0.00722056 | 47035.4 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8615.39 | 41.70 | 0.01077992 | 23.56 | 0.01563234 | -999.0000 | 27.00 | 0.00709240 | 27.00 | 0.00709240 | 32.0076 | 7823.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 515287.164 | 515287.164 | 24.577524 | 0.01261935 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 515287.16 | 515287.16 | 1.0000 | 29.58138415 | 24.577524 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 515287.16 | 12.70 | 0.00915345 | 12.70 | 0.33839277 | 1.3768 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9866.534 | 9866.534 | 0.467599 | 0.00024163 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9866.53 | 9866.53 | 1.0000 | 0.56279928 | 0.467599 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9866.53 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.3431 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 94171.310 | 94171.310 | 4.460526 | 0.00230625 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 94171.31 | 94171.31 | 1.0000 | 5.36866697 | 4.460526 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94171.31 | 12.70 | 0.00915345 | 12.70 | 0.15632344 | 3.5046 | 0.00 | 0.00701121 | 25.31 | 0.00701121 | 34.9605 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9507.967 | 9507.967 | 0.450083 | 0.00023285 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9507.97 | 9507.97 | 1.0000 | 0.54171753 | 0.450083 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9507.97 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.4732 | 0.00 | 0.00825142 | 24.80 | 0.00825142 | 42.3286 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11172.980 | 11172.980 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.577524 | 29.58138415 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11172.98 | 11172.98 | 1.0000 | 29.58138415 | 24.577524 | 0.17 | 0.17 | 0.00702965 | 17758.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11172.98 | 12.70 | 0.00915345 | 12.70 | 0.33839277 | 1.3768 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.467599 | 0.56279928 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 516.15 | 516.15 | 1.0000 | 0.56279928 | 0.467599 | 0.42 | 0.42 | 0.00707199 | 18118.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 516.15 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.3431 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5161.454 | 5161.454 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.460526 | 5.36866697 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 5161.45 | 5161.45 | 1.0000 | 5.36866697 | 4.460526 | 0.45 | 0.45 | 0.00708629 | 18175.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5161.45 | 12.70 | 0.00915345 | 12.70 | 0.15632344 | 3.5046 | 0.00 | 0.00701121 | 25.31 | 0.00701121 | 34.9605 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.450083 | 0.54171753 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 516.15 | 516.15 | 1.0000 | 0.54171753 | 0.450083 | 0.44 | 0.44 | 0.00828275 | 21164.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 516.15 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.4732 | 0.00 | 0.00825142 | 24.80 | 0.00825142 | 42.3286 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5818.83 | 3950.17 | 3950.17 |
CORE_BOTTOM | 5766.17 | 154.67 | 154.67 |
CORE_MID | 5375.33 | 58.00 | 0.00 |
CORE_TOP | 5114.33 | 333.17 | 14.17 |
PERIMETER_BOT_ZN_3 | 5466.83 | 666.50 | 532.17 |
PERIMETER_BOT_ZN_2 | 5554.83 | 744.50 | 635.00 |
PERIMETER_BOT_ZN_1 | 5693.17 | 757.83 | 684.50 |
PERIMETER_BOT_ZN_4 | 5823.17 | 942.17 | 932.50 |
PERIMETER_MID_ZN_3 | 4859.33 | 950.00 | 310.50 |
PERIMETER_MID_ZN_2 | 4403.00 | 781.17 | 489.67 |
PERIMETER_MID_ZN_1 | 5509.00 | 696.33 | 502.67 |
PERIMETER_MID_ZN_4 | 5355.50 | 877.17 | 594.17 |
PERIMETER_TOP_ZN_3 | 4713.50 | 1228.33 | 380.33 |
PERIMETER_TOP_ZN_2 | 5092.50 | 1003.50 | 524.67 |
PERIMETER_TOP_ZN_1 | 5366.33 | 865.33 | 543.17 |
PERIMETER_TOP_ZN_4 | 5185.67 | 1060.83 | 620.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1661.83 | 1661.83 |
DATACENTER_MID_ZN_6 | 5943.00 | 462.83 | 462.83 |
DATACENTER_TOP_ZN_6 | 5943.00 | 624.33 | 624.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 5850.17 | 0.00 | 3932.67 |
CORE_BOTTOM | 0.00 | 88.83 | 0.00 | 7.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 1.17 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 331.83 | 0.00 | 105.83 |
PERIMETER_BOT_ZN_2 | 0.00 | 381.17 | 0.00 | 132.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 370.33 | 0.00 | 140.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 560.00 | 0.00 | 181.00 |
PERIMETER_MID_ZN_3 | 0.00 | 144.17 | 0.00 | 59.33 |
PERIMETER_MID_ZN_2 | 0.00 | 224.00 | 0.00 | 98.50 |
PERIMETER_MID_ZN_1 | 0.00 | 204.50 | 0.00 | 100.00 |
PERIMETER_MID_ZN_4 | 0.00 | 307.00 | 0.00 | 100.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 182.00 | 0.00 | 68.83 |
PERIMETER_TOP_ZN_2 | 0.00 | 251.33 | 0.00 | 101.67 |
PERIMETER_TOP_ZN_1 | 0.00 | 237.00 | 0.00 | 102.33 |
PERIMETER_TOP_ZN_4 | 0.00 | 324.00 | 0.00 | 105.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 658.50 | 0.00 | 439.33 |
DATACENTER_MID_ZN_6 | 0.00 | 508.00 | 0.00 | 389.33 |
DATACENTER_TOP_ZN_6 | 0.00 | 484.17 | 0.00 | 372.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 70.17 | 0.00 | 70.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 5921.00 | 0.00 | 3982.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.180 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.486 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.454 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.449 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.647 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.757 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.785 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.987 | 0.017 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.732 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.903 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.959 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.997 | 0.041 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.707 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.906 | 0.050 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.919 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.947 | 0.050 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.663 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.648 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.01 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.48 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1027.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 7589588.66 | 0.00 | 7589588.66 | 0.00 | 7589588.66 | 37848132.68 | 7007.61 | 1752.39 | 0.00 | 128.06 |
CORE_BOTTOM | 24884381.18 | 0.00 | 24884381.18 | 0.00 | 24884381.18 | 33990283.35 | 7054.37 | 1006.26 | 699.37 | 1575.65 |
CORE_MID | 0.22E+09 | 0.00 | 0.22E+09 | 0.00 | 0.22E+09 | 0.34E+09 | 7136.68 | 1028.79 | 594.53 | 1071.07 |
CORE_TOP | 21511488.72 | 0.00 | 21511488.72 | 0.00 | 21511488.72 | 33990283.35 | 7196.51 | 1156.79 | 406.70 | 1050.10 |
PERIMETER_BOT_ZN_3 | 4057750.87 | 0.00 | 4057750.87 | 144958.23 | 4202709.11 | 4267819.30 | 3781.89 | 956.30 | 4021.82 | 1575.65 |
PERIMETER_BOT_ZN_2 | 2984156.83 | 0.00 | 2984156.83 | 96638.75 | 3080795.58 | 2750345.05 | 3112.92 | 1017.00 | 4630.09 | 1575.65 |
PERIMETER_BOT_ZN_1 | 4744822.10 | 0.00 | 4744822.10 | 144958.23 | 4889780.33 | 4267912.63 | 2805.08 | 872.42 | 5082.50 | 1575.65 |
PERIMETER_BOT_ZN_4 | 3918970.98 | 0.00 | 3918970.98 | 96638.75 | 4015609.73 | 2750345.05 | 2008.81 | 803.46 | 5947.72 | 1575.65 |
PERIMETER_MID_ZN_3 | 41857363.67 | 0.00 | 41857363.67 | 339958.49 | 42197322.16 | 42678193.03 | 3968.70 | 1132.04 | 3659.26 | 1071.07 |
PERIMETER_MID_ZN_2 | 32796285.45 | 0.00 | 32796285.45 | 226638.84 | 33022924.29 | 27503450.52 | 3620.70 | 755.93 | 4383.37 | 1966.15 |
PERIMETER_MID_ZN_1 | 53405395.18 | 0.00 | 53405395.18 | 339958.49 | 53745353.67 | 42679126.28 | 2989.35 | 969.23 | 4801.42 | 1071.07 |
PERIMETER_MID_ZN_4 | 36515066.99 | 0.00 | 36515066.99 | 226638.84 | 36741705.82 | 27503450.52 | 2897.98 | 961.43 | 4900.59 | 1071.07 |
PERIMETER_TOP_ZN_3 | 4076612.17 | 0.00 | 4076612.17 | 422083.30 | 4498695.47 | 4267819.30 | 3922.85 | 1207.52 | 3629.62 | 1050.10 |
PERIMETER_TOP_ZN_2 | 3288577.76 | 0.00 | 3288577.76 | 281388.67 | 3569966.43 | 2750345.05 | 3330.36 | 895.74 | 4533.90 | 1050.10 |
PERIMETER_TOP_ZN_1 | 5157380.10 | 0.00 | 5157380.10 | 422083.30 | 5579463.40 | 4267912.63 | 2926.62 | 1050.02 | 4783.36 | 1050.10 |
PERIMETER_TOP_ZN_4 | 3501644.87 | 0.00 | 3501644.87 | 281388.67 | 3783033.54 | 2750345.05 | 2882.83 | 1070.89 | 4806.27 | 1050.10 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.40E+10 | 0.00 | 0.40E+10 | 13222084.47 | 0.40E+10 | 0.50E+10 | 8757.46 | 8760.00 | 6380.46 | 3712.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.3305 | 0.0000 | 0.3305 | 0.0000 | 0.3305 | 1.2002 | 4307.53 | 1635.47 | 0.00 |
CORE_BOTTOM | 0.8934 | 0.0000 | 0.8934 | 0.0000 | 0.8934 | 1.0778 | 4942.07 | 335.97 | 664.96 |
CORE_MID | 8.3502 | 0.0000 | 8.3502 | 0.0000 | 8.3502 | 10.7782 | 4840.14 | 513.58 | 589.29 |
CORE_TOP | 0.8254 | 0.0000 | 0.8254 | 0.0000 | 0.8254 | 1.0778 | 4859.40 | 679.03 | 404.58 |
PERIMETER_BOT_ZN_3 | 0.1493 | 0.0000 | 0.1493 | 0.0039 | 0.1531 | 0.1353 | 2009.66 | 353.38 | 3579.96 |
PERIMETER_BOT_ZN_2 | 0.1125 | 0.0000 | 0.1125 | 0.0026 | 0.1151 | 0.0872 | 1465.22 | 335.98 | 4141.80 |
PERIMETER_BOT_ZN_1 | 0.1814 | 0.0000 | 0.1814 | 0.0039 | 0.1852 | 0.1353 | 1039.83 | 277.19 | 4625.98 |
PERIMETER_BOT_ZN_4 | 0.1467 | 0.0000 | 0.1467 | 0.0026 | 0.1493 | 0.0872 | 656.03 | 228.55 | 5058.42 |
PERIMETER_MID_ZN_3 | 1.6872 | 0.0000 | 1.6872 | 0.0090 | 1.6962 | 1.3533 | 1956.08 | 494.62 | 3492.30 |
PERIMETER_MID_ZN_2 | 1.3401 | 0.0000 | 1.3401 | 0.0063 | 1.3464 | 0.8721 | 1204.44 | 405.70 | 3423.86 |
PERIMETER_MID_ZN_1 | 2.2135 | 0.0000 | 2.2135 | 0.0090 | 2.2225 | 1.3533 | 1020.28 | 347.31 | 4575.42 |
PERIMETER_MID_ZN_4 | 1.4796 | 0.0000 | 1.4796 | 0.0060 | 1.4856 | 0.8721 | 1078.77 | 415.12 | 4449.11 |
PERIMETER_TOP_ZN_3 | 0.1629 | 0.0000 | 0.1629 | 0.0112 | 0.1741 | 0.1353 | 1874.29 | 658.73 | 3409.98 |
PERIMETER_TOP_ZN_2 | 0.1345 | 0.0000 | 0.1345 | 0.0075 | 0.1420 | 0.0872 | 1137.23 | 576.83 | 4228.94 |
PERIMETER_TOP_ZN_1 | 0.2121 | 0.0000 | 0.2121 | 0.0112 | 0.2233 | 0.1353 | 950.87 | 482.68 | 4509.45 |
PERIMETER_TOP_ZN_4 | 0.1405 | 0.0000 | 0.1405 | 0.0075 | 0.1480 | 0.0872 | 1017.57 | 596.45 | 4328.97 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 155.9281 | 0.0000 | 155.9281 | 0.3543 | 156.2825 | 158.4706 | 5941.12 | 5943.00 | 5279.65 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 58800454.49 | 0.00 | 58800454.49 | 48026705.38 | 1881.57 | 4.26 | 6874.17 | 1575.65 |
VAV_MID WITH REHEAT | 0.55E+09 | 0.00 | 0.55E+09 | 0.48E+09 | 2518.24 | 2.28 | 6239.48 | 1071.07 |
VAV_TOP WITH REHEAT | 54375756.24 | 0.00 | 54375756.24 | 48026705.38 | 2554.11 | 2.47 | 6203.42 | 1050.10 |
CAV_BAS | 10994432.32 | 0.00 | 10994432.32 | 37848132.68 | 7006.24 | 0.06 | 1753.70 | 128.06 |
AIRLOOP DATACENTER BASEMENT | 15459249.82 | 0.00 | 15459249.82 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7141532.97 | 0.00 | 7141532.97 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.1487 | 0.0000 | 2.1487 | 1.5229 | 571.70 | 2.08 | 5369.22 |
VAV_MID WITH REHEAT | 21.8406 | 0.0000 | 21.8406 | 15.2292 | 748.48 | 0.88 | 5193.64 |
VAV_TOP WITH REHEAT | 2.1373 | 0.0000 | 2.1373 | 1.5229 | 760.19 | 1.13 | 5181.68 |
CAV_BAS | 0.4788 | 0.0000 | 0.4788 | 1.2002 | 4307.16 | 0.06 | 1635.79 |
AIRLOOP DATACENTER BASEMENT | 0.4902 | 0.0000 | 0.4902 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2265 | 0.0000 | 0.2265 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 363.61 | 0.00 | 0.00 | 0.00 | 0.00 | 6615.44 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 521.80 | 0.00 | 0.00 | 0.00 | 0.00 | 5769.37 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 260.49 | 0.00 | 0.00 | 0.00 | 0.00 | 5998.75 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1752.34 | 0.00 | 0.00 | 15.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.3672 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.3638 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 26.5194 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 24.7095 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.3452 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4425 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7391 | 0.0000 | 0.0000 | 0.7076 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4902 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1460 |
Defaulted Fields | 1156 |
Fields with Defaults | 3692 |
Autosized Fields | 289 |
Autosizable Fields | 361 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 472 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 30649.91 | 326871.82 | 15-JAN-05:00 | 2144759.08 | 10-AUG-16:00 |
Electricity:Building | 16388.72 | 215366.33 | 21-MAY-17:10 | 940052.87 | 15-DEC-17:00 |
Electricity:Zone:BASEMENT | 540.44 | 14022.76 | 01-JAN-00:10 | 23631.68 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16388.72 | 215366.33 | 21-MAY-17:10 | 940052.87 | 15-DEC-17:00 |
InteriorLights:Electricity | 1712.33 | 8110.17 | 01-JAN-09:30 | 164979.26 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1712.33 | 8110.17 | 01-JAN-09:30 | 164979.26 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity | 1712.33 | 8110.17 | 01-JAN-09:30 | 164979.26 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1712.33 | 8110.17 | 01-JAN-09:30 | 164979.26 | 15-MAR-07:10 |
Electricity:Zone:CORE_BOTTOM | 393.83 | 4960.84 | 01-JAN-00:10 | 26343.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3938.24 | 49608.19 | 01-JAN-00:10 | 263436.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 393.82 | 4960.82 | 01-JAN-00:10 | 26343.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 43.82 | 589.50 | 26-MAR-17:10 | 3191.87 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.45 | 30.32 | 01-JAN-09:30 | 1031.32 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.45 | 30.32 | 01-JAN-09:30 | 1031.32 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.23 | 379.89 | 21-MAY-17:10 | 2047.26 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.79 | 19.54 | 01-JAN-08:00 | 654.92 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.79 | 19.54 | 01-JAN-08:00 | 654.92 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.76 | 589.50 | 12-MAR-17:10 | 3189.58 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.39 | 30.33 | 01-JAN-08:00 | 1029.00 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.39 | 30.33 | 01-JAN-08:00 | 1029.00 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.22 | 379.89 | 12-MAR-17:10 | 2061.19 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.79 | 19.54 | 01-JAN-09:30 | 668.86 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.79 | 19.54 | 01-JAN-09:30 | 668.86 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 438.08 | 5894.96 | 19-MAR-17:10 | 31905.48 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 74.43 | 303.25 | 01-JAN-09:20 | 10299.96 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 74.43 | 303.25 | 01-JAN-09:20 | 10299.96 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 282.24 | 3798.93 | 21-MAY-17:10 | 20453.46 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 47.88 | 195.42 | 01-JAN-08:00 | 6530.04 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 47.88 | 195.42 | 01-JAN-08:00 | 6530.04 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 437.51 | 5895.05 | 12-MAR-17:10 | 31882.50 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 73.85 | 303.26 | 01-JAN-08:00 | 10276.65 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 73.85 | 303.26 | 01-JAN-08:00 | 10276.65 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 282.15 | 3798.91 | 12-MAR-17:10 | 20593.44 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 47.80 | 195.42 | 01-JAN-09:30 | 6670.11 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 47.80 | 195.42 | 01-JAN-09:30 | 6670.11 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 43.81 | 589.50 | 19-MAR-17:10 | 3190.31 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.44 | 30.32 | 01-JAN-09:20 | 1029.75 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.44 | 30.32 | 01-JAN-09:20 | 1029.75 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.22 | 379.89 | 21-MAY-17:10 | 2045.18 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.79 | 19.54 | 01-JAN-08:00 | 652.84 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.79 | 19.54 | 01-JAN-08:00 | 652.84 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.75 | 589.50 | 12-MAR-17:10 | 3188.00 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.38 | 30.33 | 01-JAN-08:00 | 1027.42 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.38 | 30.33 | 01-JAN-08:00 | 1027.42 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.22 | 379.89 | 12-MAR-17:10 | 2059.20 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.78 | 19.54 | 01-JAN-09:30 | 666.86 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.78 | 19.54 | 01-JAN-09:30 | 666.86 | 14-MAR-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7527.71 | 95067.50 | 01-JAN-00:10 | 382501.19 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1555.56 | 19567.35 | 01-JAN-00:10 | 79407.42 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 6311.49 | 8041.93 | 20-JAN-05:50 | 622200.09 | 10-AUG-16:00 |
HeatRejection:Electricity | 1961.63 | 4137.15 | 20-JAN-07:00 | 84235.13 | 30-JAN-13:40 |
General:HeatRejection:Electricity | 1961.63 | 4137.15 | 20-JAN-07:00 | 84235.13 | 30-JAN-13:40 |
ElectricityProduced:Facility | 536.50 | -0.00 | 18-AUG-18:40 | 80415.16 | 21-MAY-12:30 |
ElectricityProduced:Plant | 536.50 | -0.00 | 18-AUG-18:40 | 80415.16 | 21-MAY-12:30 |
Photovoltaic:ElectricityProduced | 559.88 | 0.00 | 01-JAN-00:10 | 83680.20 | 21-MAY-12:30 |
PowerConversion:ElectricityProduced | -23.38 | -3265.05 | 21-MAY-12:30 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 6099.13 | 80927.14 | 10-JAN-03:00 | 456255.01 | 07-AUG-15:40 |
ExteriorEquipment:Electricity | 1641.46 | 10611.42 | 01-JAN-00:10 | 154953.99 | 15-MAR-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.35 | 979.82 | 01-JAN-00:10 | 3369.55 | 15-MAR-07:20 |
ElectricityPurchased:Facility | 30113.41 | 319575.48 | 15-JAN-09:10 | 2108675.93 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 30113.41 | 319575.48 | 15-JAN-09:10 | 2108675.93 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 30113.41 | 319575.48 | 15-JAN-09:10 | 2108675.93 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 30113.41 | 319575.48 | 15-JAN-09:10 | 2108675.93 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 30113.41 | 319575.48 | 15-JAN-09:10 | 2108675.93 | 10-AUG-16:00 |
ElectricityNet:Plant | 30113.41 | 319575.48 | 15-JAN-09:10 | 2108675.93 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 30113.41 | 319575.48 | 15-JAN-09:10 | 2108675.93 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 30113.41 | 319575.48 | 15-JAN-09:10 | 2108675.93 | 10-AUG-16:00 |
Heating:Electricity | 0.04 | 0.00 | 01-JAN-00:10 | 2107.73 | 02-JAN-07:00 |
General:Heating:Electricity | 0.04 | 0.00 | 01-JAN-00:10 | 2107.73 | 02-JAN-07:00 |
Fans:Electricity | 2839.54 | 46558.58 | 01-JAN-12:40 | 252766.45 | 07-AUG-15:40 |
General:Fans:Electricity | 2839.54 | 46558.58 | 01-JAN-12:40 | 252766.45 | 07-AUG-15:40 |
ExteriorLights:Electricity | 263.47 | 0.00 | 01-JAN-07:10 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 263.47 | 0.00 | 01-JAN-07:10 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1582.20 | 9600.00 | 01-JAN-00:10 | 151268.49 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
Cooling:Electricity | 6350.74 | 31664.98 | 21-JAN-05:50 | 673094.08 | 10-AUG-16:00 |
General:Cooling:Electricity | 6350.74 | 31664.98 | 21-JAN-05:50 | 673094.08 | 10-AUG-16:00 |
Humidifier:Electricity | 14.15 | 0.00 | 01-JAN-12:00 | 13583.30 | 18-DEC-06:00 |
General:Humidifier:Electricity | 14.15 | 0.00 | 01-JAN-12:00 | 13583.30 | 18-DEC-06:00 |
Boiler:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 279.95 | 0.00 | 01-JAN-00:10 | 37718.13 | 12-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 279.95 | 0.00 | 01-JAN-00:10 | 37718.13 | 12-JAN-12:30 |
Pumps:Electricity | 910.21 | 3888.90 | 01-JAN-00:10 | 54550.99 | 24-JUL-05:10 |
General:Pumps:Electricity | 910.21 | 3888.90 | 01-JAN-00:10 | 54550.99 | 24-JUL-05:10 |
WIRED_LTG_ELECTRICITY | 48.12 | 0.00 | 01-JAN-00:10 | 4635.92 | 15-MAR-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 39428.99 | 173409.64 | 21-JAN-05:50 | 3582050.35 | 10-AUG-16:00 |
PlantLoopCoolingDemand:HVAC | 39428.99 | 173409.64 | 21-JAN-05:50 | 3582050.35 | 10-AUG-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 39428.99 | 173409.64 | 21-JAN-05:50 | 3582050.35 | 10-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 24654.10 | 0.00 | 09-JAN-00:10 | 0.00 | 15-JUN-11:00 |
Water:HVAC | 5.26 | 0.00 | 01-JAN-12:00 | 0.00 | 18-DEC-06:00 |
Humidifier:Water | 5.26 | 0.00 | 01-JAN-12:00 | 0.00 | 18-DEC-06:00 |
General:Humidifier:Water | 5.26 | 0.00 | 01-JAN-12:00 | 0.00 | 18-DEC-06:00 |
MainsWater:Facility | 24654.10 | 0.00 | 09-JAN-00:10 | 0.00 | 15-JUN-11:00 |
MainsWater:HVAC | 5.26 | 0.00 | 01-JAN-12:00 | 0.00 | 18-DEC-06:00 |
Humidifier:MainsWater | 5.26 | 0.00 | 01-JAN-12:00 | 0.00 | 18-DEC-06:00 |
General:Humidifier:MainsWater | 5.26 | 0.00 | 01-JAN-12:00 | 0.00 | 18-DEC-06:00 |
Water:Plant | 24648.83 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-11:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 24648.83 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-11:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 22368.66 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-11:00 |
General:HeatRejection:Water | 22368.66 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-11:00 |
HeatRejection:MainsWater | 22368.66 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-11:00 |
General:HeatRejection:MainsWater | 22368.66 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-11:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 141207.07 | 242363.45 | 21-JAN-05:50 | 14122057.51 | 10-AUG-16:00 |
EnergyTransfer:Building | 23894.29 | 100618.79 | 21-JAN-05:50 | 1755682.38 | 07-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 288.98 | 0.00 | 01-JAN-00:10 | 98060.42 | 30-OCT-05:50 |
Heating:EnergyTransfer | 6.72 | 0.00 | 01-JAN-00:10 | 24783.68 | 01-JAN-13:50 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 6.72 | 0.00 | 01-JAN-00:10 | 24783.68 | 01-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 23887.58 | 100618.79 | 21-JAN-05:50 | 1755682.38 | 07-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 288.98 | 0.00 | 01-JAN-00:10 | 98060.42 | 30-OCT-05:50 |
General:Cooling:EnergyTransfer | 23887.58 | 100618.79 | 21-JAN-05:50 | 1755682.38 | 07-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 288.98 | 0.00 | 01-JAN-00:10 | 98060.42 | 30-OCT-05:50 |
EnergyTransfer:Zone:CORE_BOTTOM | 938.24 | 0.00 | 01-JAN-00:10 | 79865.21 | 21-AUG-05:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 938.24 | 0.00 | 01-JAN-00:10 | 79865.21 | 21-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 938.24 | 0.00 | 01-JAN-00:10 | 79865.21 | 21-AUG-05:20 |
EnergyTransfer:Zone:CORE_MID | 5696.77 | 0.00 | 01-JAN-00:10 | 427937.58 | 27-NOV-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5696.77 | 0.00 | 01-JAN-00:10 | 427937.58 | 27-NOV-06:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5696.77 | 0.00 | 01-JAN-00:10 | 427937.58 | 27-NOV-06:10 |
EnergyTransfer:Zone:CORE_TOP | 593.74 | 0.00 | 01-JAN-00:10 | 54810.07 | 05-SEP-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 593.74 | 0.00 | 01-JAN-00:10 | 54810.07 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 593.74 | 0.00 | 01-JAN-00:10 | 54810.07 | 05-SEP-05:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 167.41 | 0.00 | 01-JAN-00:10 | 16540.55 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 167.41 | 0.00 | 01-JAN-00:10 | 16540.55 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 167.41 | 0.00 | 01-JAN-00:10 | 16540.55 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 125.06 | 0.00 | 01-JAN-00:10 | 13887.84 | 04-AUG-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 125.06 | 0.00 | 01-JAN-00:10 | 13887.84 | 04-AUG-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 125.06 | 0.00 | 01-JAN-00:10 | 13887.84 | 04-AUG-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 194.20 | 0.00 | 01-JAN-00:10 | 18649.96 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 194.20 | 0.00 | 01-JAN-00:10 | 18649.96 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 194.20 | 0.00 | 01-JAN-00:10 | 18649.96 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 156.14 | 0.00 | 01-JAN-00:10 | 15905.60 | 10-AUG-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 156.14 | 0.00 | 01-JAN-00:10 | 15905.60 | 10-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 156.14 | 0.00 | 01-JAN-00:10 | 15905.60 | 10-AUG-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1225.79 | 0.00 | 01-JAN-00:10 | 140452.32 | 21-JUL-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1225.79 | 0.00 | 01-JAN-00:10 | 140452.32 | 21-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1225.79 | 0.00 | 01-JAN-00:10 | 140452.32 | 21-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 985.10 | 0.00 | 01-JAN-00:10 | 128826.98 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 985.10 | 0.00 | 01-JAN-00:10 | 128826.98 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 985.10 | 0.00 | 01-JAN-00:10 | 128826.98 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1557.43 | 0.00 | 01-JAN-00:10 | 165726.01 | 05-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1557.43 | 0.00 | 01-JAN-00:10 | 165726.01 | 05-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1557.43 | 0.00 | 01-JAN-00:10 | 165726.01 | 05-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1072.64 | 0.00 | 01-JAN-00:10 | 131582.14 | 10-AUG-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1072.64 | 0.00 | 01-JAN-00:10 | 131582.14 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1072.64 | 0.00 | 01-JAN-00:10 | 131582.14 | 10-AUG-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 127.21 | 0.00 | 01-JAN-00:10 | 15176.44 | 21-JUL-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 54.62 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 54.62 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 127.21 | 0.00 | 01-JAN-00:10 | 15176.44 | 21-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 127.21 | 0.00 | 01-JAN-00:10 | 15176.44 | 21-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 104.24 | 0.00 | 01-JAN-00:10 | 12901.72 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 68.89 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 68.89 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 104.24 | 0.00 | 01-JAN-00:10 | 12901.72 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 104.24 | 0.00 | 01-JAN-00:10 | 12901.72 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 159.18 | 0.00 | 01-JAN-00:10 | 17380.32 | 05-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 159.18 | 0.00 | 01-JAN-00:10 | 17380.32 | 05-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 159.18 | 0.00 | 01-JAN-00:10 | 17380.32 | 05-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 109.88 | 0.00 | 01-JAN-00:10 | 13844.40 | 10-AUG-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 109.88 | 0.00 | 01-JAN-00:10 | 13844.40 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 109.88 | 0.00 | 01-JAN-00:10 | 13844.40 | 10-AUG-15:50 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 180.12 | 0.00 | 01-JAN-00:10 | 23220.08 | 07-AUG-05:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.72 | 0.00 | 01-JAN-00:10 | 2959.21 | 16-JAN-10:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.72 | 0.00 | 01-JAN-00:10 | 2959.21 | 16-JAN-10:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 179.41 | 0.00 | 01-JAN-00:10 | 23220.08 | 07-AUG-05:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 179.41 | 0.00 | 01-JAN-00:10 | 23220.08 | 07-AUG-05:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1189.67 | 0.00 | 01-JAN-00:10 | 148362.38 | 07-AUG-05:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.23 | 0.00 | 01-JAN-00:10 | 24783.68 | 01-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.23 | 0.00 | 01-JAN-00:10 | 24783.68 | 01-JAN-13:50 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1185.44 | 0.00 | 01-JAN-00:10 | 148362.38 | 07-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1185.44 | 0.00 | 01-JAN-00:10 | 148362.38 | 07-AUG-05:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 173.79 | 0.00 | 01-JAN-00:10 | 26653.73 | 16-AUG-13:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.77 | 0.00 | 01-JAN-00:10 | 5002.19 | 28-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.77 | 0.00 | 01-JAN-00:10 | 5002.19 | 28-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 172.01 | 0.00 | 01-JAN-00:10 | 26653.73 | 16-AUG-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 172.01 | 0.00 | 01-JAN-00:10 | 26653.73 | 16-AUG-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.84 | 1245.51 | 21-JAN-08:00 | 7850.93 | 23-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.84 | 1245.51 | 21-JAN-08:00 | 7850.93 | 23-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.84 | 1245.51 | 21-JAN-08:00 | 7850.93 | 23-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1340.41 | 8066.38 | 21-JAN-08:00 | 73609.51 | 23-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1340.41 | 8066.38 | 21-JAN-08:00 | 73609.51 | 23-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1340.41 | 8066.38 | 21-JAN-08:00 | 73609.51 | 23-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.71 | 332.10 | 01-JAN-08:30 | 7584.56 | 23-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.71 | 332.10 | 01-JAN-08:30 | 7584.56 | 23-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.71 | 332.10 | 01-JAN-08:30 | 7584.56 | 23-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7229.73 | 89040.79 | 21-JAN-19:10 | 370908.69 | 04-AUG-14:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7229.73 | 89040.79 | 21-JAN-19:10 | 370908.69 | 04-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7229.73 | 89040.79 | 21-JAN-19:10 | 370908.69 | 04-AUG-14:10 |
PlantLoopHeatingDemand:Facility | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
EnergyTransfer:HVAC | 36237.97 | 141725.88 | 16-JAN-04:00 | 3374904.38 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.04 | 0.00 | 01-JAN-00:10 | 2107.73 | 02-JAN-07:00 |
CoolingCoils:EnergyTransfer | 36237.93 | 141725.88 | 16-JAN-04:00 | 3374904.38 | 10-AUG-16:00 |
PlantLoopHeatingDemand:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatingCoils:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Plant | 81074.81 | 0.00 | 01-JAN-00:10 | 9013595.15 | 10-AUG-16:00 |
LoopToLoop:EnergyTransfer | 26054.98 | 0.00 | 01-JAN-00:10 | 2843049.32 | 10-AUG-16:00 |
WaterSystems:EnergyTransfer | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
Chillers:EnergyTransfer | 25792.44 | 0.00 | 01-JAN-00:10 | 2842860.54 | 10-AUG-16:00 |
HeatRejection:EnergyTransfer | 28952.13 | 0.00 | 01-JAN-00:10 | 3308808.64 | 10-AUG-16:00 |
General:HeatRejection:EnergyTransfer | 28952.13 | 0.00 | 01-JAN-00:10 | 3308808.64 | 10-AUG-16:00 |
Boilers:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -288.969 | 0.000 | 0.000 | 64.510 | 116.039 | 424.397 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -315.978 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -938.247 | 0.000 | 0.000 | 83.301 | 104.212 | 289.614 | 0.000 | 0.000 | 0.000 | 461.120 | 0.000 | 0.000 | 0.000 | 0.000 | -0.010 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5696.784 | 0.000 | 0.000 | 835.118 | 1042.115 | 2896.128 | 0.000 | 0.000 | 0.000 | 923.423 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -593.743 | 0.000 | 0.000 | 83.610 | 104.212 | 289.613 | 0.000 | 0.000 | 0.000 | 116.308 | 0.000 | 0.000 | 0.000 | 0.000 | -0.008 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -167.409 | 0.000 | 0.000 | 10.460 | 7.454 | 36.365 | 61.416 | 0.000 | 0.764 | 68.064 | 0.000 | -16.860 | 0.000 | -0.254 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -125.064 | 0.000 | 0.000 | 6.737 | 4.794 | 23.435 | 63.397 | 0.000 | 0.506 | 36.768 | 0.000 | -10.403 | 0.000 | -0.169 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -194.206 | 0.000 | 0.000 | 10.449 | 7.391 | 36.366 | 99.417 | 0.000 | 0.758 | 56.826 | 0.000 | -16.722 | 0.000 | -0.279 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -156.143 | 0.000 | 0.000 | 6.726 | 4.787 | 23.435 | 63.120 | 0.000 | 0.497 | 71.158 | 0.000 | -13.362 | 0.000 | -0.217 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -1225.786 | 0.000 | 0.000 | 105.125 | 74.430 | 363.654 | 646.510 | 0.000 | 18.180 | 170.793 | 0.000 | -147.595 | 0.000 | -5.311 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -985.102 | 0.000 | 0.000 | 49.420 | 47.884 | 234.352 | 644.026 | 0.000 | 11.736 | 98.844 | 0.000 | -97.240 | 0.000 | -3.920 | -0.010 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1557.422 | 0.000 | 0.000 | 104.655 | 73.850 | 363.660 | 1013.169 | 0.000 | 17.770 | 148.989 | 0.000 | -158.117 | 0.000 | -6.553 | -0.005 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -1072.644 | 0.000 | 0.000 | 67.511 | 47.803 | 234.351 | 652.167 | 0.000 | 11.660 | 174.463 | 0.000 | -111.078 | 0.000 | -4.233 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -127.211 | 0.000 | 0.000 | 10.551 | 7.443 | 36.365 | 64.063 | 0.000 | 2.203 | 21.487 | 0.000 | -14.271 | 0.000 | -0.629 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -104.238 | 0.000 | 0.000 | 6.760 | 4.788 | 23.435 | 64.247 | 0.000 | 1.437 | 13.473 | 0.000 | -9.437 | 0.000 | -0.465 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -159.180 | 0.000 | 0.000 | 10.484 | 7.385 | 36.366 | 100.589 | 0.000 | 2.158 | 18.387 | 0.000 | -15.400 | 0.000 | -0.788 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -109.875 | 0.000 | 0.000 | 6.768 | 4.780 | 23.435 | 64.750 | 0.000 | 1.420 | 20.055 | 0.000 | -10.822 | 0.000 | -0.510 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -144.841 | 0.000 | 0.000 | 0.939 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -11.654 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1340.412 | 0.000 | 0.000 | 9.398 | 16.758 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -224.550 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.000 | -133.713 | 0.000 | 0.000 | 0.940 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -22.784 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7229.734 | 0.000 | 0.000 | 20.510 | 32.854 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -318.487 |
GROUNDFLOOR_PLENUM | 0.717 | -179.407 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.371 | 177.901 | 0.000 | 0.000 | 0.000 | -0.582 | 0.000 |
MIDFLOOR_PLENUM | 4.228 | -1185.443 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26.416 | 1164.482 | 0.000 | 0.000 | 0.000 | -9.683 | 0.000 |
TOPFLOOR_PLENUM | 1.771 | -172.015 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.833 | 168.435 | 0.000 | 0.000 | 0.000 | -1.025 | -0.002 |
Total Facility | 6.716 | -1536.865 | 0.000 | -22350.722 | 0.000 | 0.000 | 1493.971 | 1712.328 | 14676.396 | 3536.869 | 0.000 | 99.708 | 3910.978 | 0.000 | -621.307 | 0.000 | -34.618 | -893.495 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-OCT-05:41 | 0.00 | 0.00 | 0.00 | -111076.38 | 0.00 | 0.00 | 553.74 | 1130.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 95934.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 09-FEB-05:13 | 0.00 | 0.00 | 0.00 | -97454.92 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 90979.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 20-OCT-04:13 | 0.00 | 0.00 | 0.00 | -875066.69 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 810316.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-05:04 | 0.00 | 0.00 | 0.00 | -83859.25 | 0.00 | 0.00 | 804.95 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 74869.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 21-MAY-15:43 | 0.00 | 0.00 | 0.00 | -22835.25 | 0.00 | 0.00 | 37.45 | 30.32 | 720.18 | 5413.27 | 0.00 | 234.03 | 16399.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 21-MAY-09:41 | 0.00 | 0.00 | 0.00 | -20217.86 | 0.00 | 0.00 | 20.72 | 19.54 | 464.11 | 10054.14 | 0.00 | 105.43 | 9553.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 29-OCT-13:03 | 0.00 | 0.00 | 0.00 | -27435.60 | 0.00 | 0.00 | 32.40 | 30.33 | 720.19 | 14813.11 | 0.00 | 52.18 | 11787.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 21-MAY-15:41 | 0.00 | 0.00 | 0.00 | -25781.93 | 0.00 | 0.00 | 19.64 | 19.54 | 464.11 | 9508.92 | 0.00 | 125.78 | 15643.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-SEP-16:11 | 0.00 | 0.00 | 0.00 | -230784.32 | 0.00 | 0.00 | 371.59 | 303.25 | 7201.84 | 53393.63 | 0.00 | 4677.38 | 164836.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-SEP-10:11 | 0.00 | 0.00 | 0.00 | -209146.66 | 0.00 | 0.00 | 212.02 | 195.42 | 4641.14 | 82238.50 | 0.00 | 2039.17 | 119820.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-14:11 | 0.00 | 0.00 | 0.00 | -271752.05 | 0.00 | 0.00 | 328.63 | 303.26 | 7201.95 | 101767.27 | 0.00 | 4642.11 | 157508.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-SEP-16:11 | 0.00 | 0.00 | 0.00 | -246477.58 | 0.00 | 0.00 | 184.97 | 195.42 | 4641.11 | 92740.48 | 0.00 | 2794.96 | 145920.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-JUL-15:21 | 0.00 | 0.00 | 0.00 | -26097.78 | 0.00 | 0.00 | 35.00 | 30.32 | 720.18 | 6456.37 | 0.00 | 473.81 | 18382.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-SEP-10:11 | 0.00 | 0.00 | 0.00 | -21846.65 | 0.00 | 0.00 | 20.42 | 19.54 | 464.11 | 8140.03 | 0.00 | 245.14 | 12957.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-14:51 | 0.00 | 0.00 | 0.00 | -29621.28 | 0.00 | 0.00 | 32.47 | 30.33 | 720.19 | 7801.49 | 0.00 | 527.41 | 20509.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-JUL-15:21 | 0.00 | 0.00 | 0.00 | -26114.44 | 0.00 | 0.00 | 18.47 | 19.54 | 464.11 | 9125.59 | 0.00 | 292.59 | 16194.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 23-APR-18:00 | 0.00 | 0.00 | 0.00 | -7850.85 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 48.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 23-APR-17:42 | 0.00 | 0.00 | 0.00 | -73609.26 | 0.00 | 0.00 | 0.00 | 81.29 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4416.25 |
DATACENTER_TOP_ZN_6 | 23-APR-18:03 | 0.00 | 0.00 | 0.00 | -7586.14 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -216.41 |
DATACENTER_BASEMENT_ZN_6 | 10-AUG-21:01 | 0.00 | 0.00 | 0.00 | -374276.04 | 0.00 | 0.00 | 112.76 | 318.73 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5787.98 |
GROUNDFLOOR_PLENUM | 24-JUL-05:20 | 0.00 | -25296.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 | 25286.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 07-AUG-05:12 | 0.00 | -212185.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.17 | 211846.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 04-SEP-15:31 | 0.00 | -28253.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.67 | 27540.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:01 | 0.00 | -144201.55 | 0.00 | -2225097.53 | 0.00 | 0.00 | 14446.55 | 10223.35 | 616289.16 | 30571.64 | 0.00 | 1303.82 | 1696464.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 03-JAN-06:08 | 0.00 | 0.00 | 186.43 | 0.00 | 0.00 | 0.00 | 138.23 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 1444.28 | 0.00 | -2796.65 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JAN-06:07 | 0.00 | 0.00 | 206.66 | 0.00 | 0.00 | 0.00 | 89.50 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 902.71 | 0.00 | -1847.82 | 0.00 | -13.36 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:11 | 10944.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -160.47 | -10783.84 |
MIDFLOOR_PLENUM | 21-FEB-05:11 | 68562.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4190.28 | -64372.49 |
TOPFLOOR_PLENUM | 21-FEB-06:03 | 14987.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -90.42 | -14897.52 |
Total Facility | 21-FEB-05:11 | -1263216.85 | 1341245.85 | 0.00 | -1341245.85 | 0.00 | 0.00 | 0.00 | 10223.35 | 350716.63 | 0.00 | 0.00 | 0.00 | 1029755.12 | 0.00 | -113799.76 | 0.00 | -13678.48 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.8170 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.8237 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 104.0361 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 92.2003 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.8442 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5272 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.2697 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.2697 | 0.2277 | 1.0000 | Not calculated | 1.2002 | 0.2277 | ||
AIRLOOP DATACENTER BASEMENT | 24.5773 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.5775 | 0.0138 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.4676 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4676 | 0.0334 | 1.0000 | Not calculated | 0.0156 | 0.0334 | ||
AIRLOOP DATACENTER MID | 4.4605 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4605 | 0.0350 | 1.0000 | Not calculated | 0.1563 | 0.0350 | ||
AIRLOOP DATACENTER TOP | 0.4501 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4501 | 0.0347 | 1.0000 | Not calculated | 0.0156 | 0.0347 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.4085 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2861 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 52.0181 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8408 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.4221 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2869 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 24.5773 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.5773 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.4676 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4676 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0334 | ||
AIRLOOP DATACENTER MID | 4.4605 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4605 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0350 | ||
AIRLOOP DATACENTER TOP | 0.4501 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4501 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0347 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.2697 | 5.2697 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7183 | 5.7183 | 1.6183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 54.4014 | 54.4014 | 16.1572 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5041 | 5.5041 | 1.6182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2516 | 1.2516 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0565 | 1.0565 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4076 | 1.4076 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3830 | 1.3830 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.4139 | 12.4139 | 2.0359 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.0459 | 11.0459 | 1.3034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.9379 | 13.9379 | 2.0349 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.2371 | 12.2371 | 1.3094 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3748 | 1.3748 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1350 | 1.1350 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5203 | 1.5203 | 0.2037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3099 | 1.3099 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4676 | 0.4676 | 0.4676 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4605 | 4.4605 | 4.4605 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4501 | 0.4501 | 0.4501 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.5773 | 24.5773 | 24.5773 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.8170 | 9.8237 | 10.8170 | 2.2861 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 104.0361 | 92.2003 | 104.0361 | 22.8408 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.8442 | 10.5272 | 10.8442 | 2.2869 | 0.0000 | 1.0000 |
CAV_BAS | 5.2697 | 5.2697 | 5.2697 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.5773 | 24.5775 | 24.5773 | 24.5773 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4676 | 0.4676 | 0.4676 | 0.4676 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4605 | 4.4605 | 4.4605 | 4.4605 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4501 | 0.4501 | 0.4501 | 0.4501 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8591 | 2.8591 | 1.6183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.2007 | 27.2007 | 16.1572 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7520 | 2.7520 | 1.6182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6258 | 0.6258 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5283 | 0.5283 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7038 | 0.7038 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6915 | 0.6915 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.2069 | 6.2069 | 2.0359 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5229 | 5.5229 | 1.3034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.9690 | 6.9690 | 2.0349 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1185 | 6.1185 | 1.3094 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6874 | 0.6874 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5675 | 0.5675 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7602 | 0.7602 | 0.2037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6550 | 0.6550 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4676 | 0.4676 | 0.4676 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4605 | 4.4605 | 4.4605 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4501 | 0.4501 | 0.4501 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.5773 | 24.5773 | 24.5773 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.4085 | 2.2861 | 2.2861 | 2.2861 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 52.0181 | 22.8408 | 22.8408 | 22.8408 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.4221 | 2.2869 | 2.2869 | 2.2869 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.5773 | 24.5773 | 24.5773 | 24.5773 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4676 | 0.4676 | 0.4676 | 0.4676 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4605 | 4.4605 | 4.4605 | 4.4605 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4501 | 0.4501 | 0.4501 | 0.4501 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 3982.17 |
Number of hours not met | 3982.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.04 | 2107.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6350.74 | 673094.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1712.33 | 164979.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 263.47 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.35 | 3369.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1582.20 | 151268.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2839.54 | 252766.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 910.21 | 54550.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1961.63 | 84235.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 14.15 | 13583.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 279.95 | 37718.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 30649.91 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 30649.91 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 559.88 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 36.97 |
Space Heating | 0.00 |
Space Cooling | 137.10 |
Fans (All) | 61.30 |
Service Water Heating | 6.04 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 661.69 |
Subtotal | 661.69 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.59 |
Space Heating | 0.00 |
Space Cooling | 20.72 |
Fans (All) | 9.26 |
Service Water Heating | 0.91 |
Receptacle Equipment | 47.88 |
Miscellaneous | 15.63 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2069. | 8760. |
LTG_SCH_DATACENTER | 1840. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 923. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 2570.17 | 1158.17 | 563.33 | 4468.33 | 0.00 |
CORE_BOTTOM | 8486.33 | 273.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7890.83 | 869.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7744.83 | 1015.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7761.67 | 998.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6746.50 | 2013.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8349.67 | 410.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7965.83 | 794.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7926.00 | 834.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7530.00 | 1230.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8238.33 | 521.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7890.00 | 870.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7855.00 | 905.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7501.17 | 1258.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6213.17 | 2546.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6010.83 | 2749.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6091.00 | 2669.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8043.33 | 716.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7218.00 | 1542.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8619.00 | 141.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7801.67 | 958.33 | 0.00 | 0.00 | 0.00 |
Min | 2570.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2749.17 | 563.33 | 4468.33 | 0.00 |
Average | 7477.07 | 1064.17 | 24.49 | 194.28 | 0.00 |
Sum | 171972.50 | 24475.83 | 563.33 | 4468.33 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 126757.50 | 23960.33 | 23763.33 | 194134.83 | 0.00 |
CORE_BOTTOM | 330325.00 | 488.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330810.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1436.00 | 832.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1388.83 | 879.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1402.33 | 865.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 89044.83 | 14350.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330813.00 | 23960.33 | 23763.33 | 194134.83 | 0.00 |
Average | 69062.02 | 1799.06 | 1033.19 | 8440.64 | 0.00 |
Sum | 1588426.50 | 41378.33 | 23763.33 | 194134.83 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 2043.67 | 1692.67 | 420.83 | 3018.17 | 1584.67 |
CORE_BOTTOM | 5786.33 | 2973.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7402.50 | 1357.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 6987.83 | 1772.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6090.67 | 2669.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6135.00 | 2625.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5794.33 | 2965.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5428.00 | 3332.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6110.67 | 2649.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 5906.17 | 2853.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5747.50 | 3012.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5778.33 | 2981.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6136.00 | 2624.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 5958.00 | 2802.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5811.83 | 2948.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5831.33 | 2928.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7145.83 | 1614.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7055.33 | 1704.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7120.00 | 1640.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8574.17 | 185.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 4792.50 | 3967.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3259.17 | 5500.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3277.17 | 5482.83 | 0.00 | 0.00 | 0.00 |
Min | 2043.67 | 185.83 | 0.00 | 0.00 | 0.00 |
Max | 8574.17 | 5500.83 | 420.83 | 3018.17 | 1584.67 |
Average | 5833.58 | 2708.00 | 18.30 | 131.22 | 68.90 |
Sum | 134172.33 | 62284.00 | 420.83 | 3018.17 | 1584.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 121576.33 | 30357.50 | 17342.00 | 93650.50 | 105689.67 |
CORE_BOTTOM | 325342.00 | 5471.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328570.00 | 2243.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 325369.33 | 5443.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38922.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38850.00 | 75.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24887.83 | 21.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38900.83 | 24.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24902.33 | 6.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1761.50 | 506.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1698.00 | 570.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1717.50 | 550.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 98716.83 | 4678.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 328570.00 | 30357.50 | 17342.00 | 93650.50 | 105689.67 |
Average | 68742.21 | 2171.74 | 754.00 | 4071.76 | 4595.20 |
Sum | 1581070.83 | 49950.00 | 17342.00 | 93650.50 | 105689.67 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.570026E+11 | 106630.97 | 01-JAN-18:32 | 19.57 | 15.21 | 0.567676E+10 | 7499.29 | 12-JAN-10:20 | 20.87 | 17.11 |
February | 0.456791E+11 | 103760.10 | 10-FEB-05:11 | 19.93 | 12.75 | 0.555477E+10 | 11333.82 | 09-FEB-14:00 | 19.93 | 12.75 |
March | 0.452324E+11 | 100021.02 | 06-MAR-05:12 | 16.67 | 12.96 | 0.704044E+10 | 11550.76 | 28-MAR-13:00 | 31.00 | 19.33 |
April | 0.261960E+11 | 90420.03 | 05-APR-04:12 | 17.07 | 15.11 | 0.714678E+10 | 12386.50 | 28-APR-13:00 | 35.00 | 23.22 |
May | 0.414153E+10 | 95798.58 | 01-MAY-05:11 | 20.87 | 20.87 | 0.929744E+10 | 12498.87 | 30-MAY-13:00 | 38.00 | 25.47 |
June | 0.364074E+10 | 85776.03 | 22-JUN-10:05 | 38.00 | 24.19 | 0.955104E+10 | 12693.29 | 13-JUN-13:00 | 38.00 | 24.19 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 | 27.02 | 0.933211E+10 | 13081.05 | 05-JUL-13:00 | 35.00 | 28.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 | 28.28 | 0.107787E+11 | 13452.76 | 07-AUG-13:00 | 37.00 | 29.28 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 | 25.04 | 0.938371E+10 | 13352.93 | 05-SEP-13:00 | 40.00 | 25.05 |
October | 0.844790E+10 | 111092.01 | 30-OCT-05:41 | 22.08 | 17.88 | 0.946941E+10 | 13455.40 | 10-OCT-13:00 | 22.08 | 17.88 |
November | 0.430943E+11 | 100242.58 | 13-NOV-05:41 | 21.00 | 17.65 | 0.709361E+10 | 12698.66 | 03-NOV-13:00 | 21.00 | 17.65 |
December | 0.555468E+11 | 104036.33 | 12-DEC-22:17 | 19.80 | 14.62 | 0.585200E+10 | 11915.73 | 12-DEC-14:00 | 19.80 | 14.62 |
Annual Sum or Average | 0.288981E+12 | 0.961768E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 16.67 | 12.75 | 0.555477E+10 | 7499.29 | 19.80 | 12.75 | ||
Maximum of Months | 0.570026E+11 | 111092.01 | 38.00 | 28.28 | 0.107787E+11 | 13455.40 | 40.00 | 29.28 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.455150E+11 | 96830.23 | 02-JAN-05:11 | 13.67 | 11.10 | 0.507885E+10 | 6734.85 | 09-JAN-10:20 | 16.40 | 15.51 |
February | 0.473251E+11 | 97483.01 | 09-FEB-05:13 | 23.00 | 19.02 | 0.460909E+10 | 6734.92 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.650279E+11 | 94156.73 | 15-MAR-04:13 | 22.00 | 17.33 | 0.549979E+10 | 6735.13 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.739916E+11 | 91809.77 | 24-APR-04:23 | 22.75 | 14.38 | 0.488398E+10 | 6783.00 | 28-APR-13:00 | 35.00 | 23.22 |
May | 0.872412E+11 | 95608.78 | 01-MAY-04:23 | 21.65 | 21.48 | 0.529562E+10 | 6760.62 | 30-MAY-13:39 | 37.43 | 26.20 |
June | 0.918837E+11 | 95270.81 | 05-JUN-03:03 | 29.88 | 24.74 | 0.528068E+10 | 6755.60 | 19-JUN-13:00 | 35.00 | 25.46 |
July | 0.984028E+11 | 96983.02 | 05-JUL-03:03 | 30.02 | 27.78 | 0.491670E+10 | 6761.72 | 17-JUL-13:00 | 37.00 | 29.90 |
August | 0.110018E+12 | 97107.77 | 28-AUG-03:03 | 31.07 | 27.26 | 0.552196E+10 | 6778.97 | 24-AUG-13:00 | 31.07 | 27.26 |
September | 0.921440E+11 | 92486.35 | 11-SEP-04:25 | 29.25 | 27.56 | 0.489615E+10 | 6748.11 | 05-SEP-09:00 | 29.25 | 27.56 |
October | 0.937920E+11 | 97267.49 | 10-OCT-03:04 | 27.00 | 23.99 | 0.508939E+10 | 6736.66 | 19-OCT-09:30 | 31.10 | 21.74 |
November | 0.725285E+11 | 95931.74 | 30-NOV-05:13 | 19.67 | 18.31 | 0.503282E+10 | 6736.15 | 13-NOV-10:09 | 19.67 | 18.31 |
December | 0.603743E+11 | 94418.48 | 18-DEC-05:11 | 13.00 | 10.66 | 0.490198E+10 | 6734.81 | 20-DEC-10:20 | 21.60 | 16.49 |
Annual Sum or Average | 0.938244E+12 | 0.610070E+11 | ||||||||
Minimum of Months | 0.455150E+11 | 91809.77 | 13.00 | 10.66 | 0.460909E+10 | 6734.81 | 16.40 | 15.51 | ||
Maximum of Months | 0.110018E+12 | 97483.01 | 31.07 | 27.78 | 0.552196E+10 | 6783.00 | 37.43 | 29.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341904E+11 | 80230.68 | 02-JAN-05:11 | 13.67 | 11.10 | 0.505849E+10 | 6734.84 | 09-JAN-10:20 | 16.40 | 15.51 |
February | 0.333514E+11 | 82879.74 | 21-FEB-05:11 | 14.67 | 13.69 | 0.459701E+10 | 6734.96 | 15-FEB-14:09 | 14.67 | 13.69 |
March | 0.429180E+11 | 83344.18 | 06-MAR-05:12 | 16.67 | 12.96 | 0.549486E+10 | 6735.16 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.449189E+11 | 82880.90 | 13-APR-04:12 | 19.07 | 15.51 | 0.487721E+10 | 6735.23 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.546016E+11 | 75041.23 | 04-MAY-04:13 | 23.53 | 18.44 | 0.527807E+10 | 6735.06 | 08-MAY-13:30 | 35.75 | 23.54 |
June | 0.557325E+11 | 65555.95 | 12-JUN-05:02 | 29.02 | 24.10 | 0.526089E+10 | 6734.92 | 02-JUN-13:09 | 29.02 | 24.10 |
July | 0.571105E+11 | 67055.50 | 05-JUL-05:03 | 30.00 | 28.44 | 0.488579E+10 | 6735.20 | 03-JUL-09:09 | 30.00 | 28.44 |
August | 0.608091E+11 | 71737.41 | 07-AUG-05:01 | 32.82 | 23.16 | 0.548845E+10 | 6734.72 | 03-AUG-13:20 | 32.82 | 23.16 |
September | 0.537608E+11 | 74236.20 | 05-SEP-05:03 | 30.17 | 24.66 | 0.487327E+10 | 6734.76 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.514011E+11 | 87519.35 | 20-OCT-04:13 | 22.60 | 16.22 | 0.507069E+10 | 6734.73 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.440426E+11 | 83086.62 | 27-NOV-05:12 | 18.00 | 16.14 | 0.502419E+10 | 6734.77 | 22-NOV-10:20 | 18.00 | 16.14 |
December | 0.368402E+11 | 82028.53 | 07-DEC-05:11 | 19.00 | 16.51 | 0.488776E+10 | 6734.81 | 01-DEC-14:20 | 19.00 | 16.51 |
Annual Sum or Average | 0.569677E+12 | 0.607967E+11 | ||||||||
Minimum of Months | 0.333514E+11 | 65555.95 | 13.67 | 11.10 | 0.459701E+10 | 6734.72 | 14.67 | 13.69 | ||
Maximum of Months | 0.608091E+11 | 87519.35 | 32.82 | 28.44 | 0.549486E+10 | 6735.23 | 35.75 | 28.44 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298503E+11 | 78609.29 | 30-JAN-06:02 | 20.03 | 17.43 | 0.500260E+10 | 6734.79 | 17-JAN-10:20 | 20.03 | 17.43 |
February | 0.309179E+11 | 82216.34 | 07-FEB-05:12 | 20.33 | 18.36 | 0.456826E+10 | 6734.93 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.418621E+11 | 82877.21 | 30-MAR-04:11 | 19.67 | 17.92 | 0.548305E+10 | 6735.15 | 28-MAR-09:00 | 19.67 | 17.92 |
April | 0.464654E+11 | 82549.32 | 21-APR-04:12 | 20.40 | 17.89 | 0.487795E+10 | 6735.21 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.601351E+11 | 78441.14 | 03-MAY-04:12 | 23.10 | 18.53 | 0.528346E+10 | 6735.03 | 08-MAY-13:30 | 35.75 | 23.54 |
June | 0.621717E+11 | 81389.91 | 12-JUN-05:03 | 29.02 | 24.10 | 0.526532E+10 | 6734.91 | 02-JUN-13:09 | 29.02 | 24.10 |
July | 0.649891E+11 | 80499.98 | 05-JUL-05:03 | 30.00 | 28.44 | 0.489377E+10 | 6735.19 | 03-JUL-09:09 | 30.00 | 28.44 |
August | 0.686225E+11 | 83878.84 | 07-AUG-05:04 | 32.82 | 23.16 | 0.549440E+10 | 6734.67 | 21-AUG-09:20 | 32.67 | 28.09 |
September | 0.587825E+11 | 81932.55 | 05-SEP-05:03 | 30.17 | 24.66 | 0.487844E+10 | 6734.75 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.536019E+11 | 80372.08 | 21-OCT-04:12 | 22.40 | 15.15 | 0.507339E+10 | 6734.73 | 20-OCT-09:20 | 22.40 | 15.15 |
November | 0.429075E+11 | 83018.49 | 13-NOV-05:12 | 21.00 | 17.39 | 0.502175E+10 | 6734.75 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.334366E+11 | 82846.36 | 11-DEC-05:12 | 22.00 | 18.87 | 0.485564E+10 | 6734.78 | 01-DEC-14:20 | 22.00 | 18.87 |
Annual Sum or Average | 0.593743E+12 | 0.606980E+11 | ||||||||
Minimum of Months | 0.298503E+11 | 78441.14 | 19.67 | 15.15 | 0.456826E+10 | 6734.67 | 19.67 | 15.15 | ||
Maximum of Months | 0.686225E+11 | 83878.84 | 32.82 | 28.44 | 0.549440E+10 | 6735.21 | 35.75 | 28.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.475075E+10 | 14636.59 | 30-JAN-06:02 | 20.03 | 17.43 | 0.631776E+09 | 845.63 | 17-JAN-14:20 | 20.03 | 17.43 |
February | 0.574694E+10 | 16912.73 | 07-FEB-05:12 | 20.33 | 18.36 | 0.576446E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.935137E+10 | 16698.03 | 15-MAR-04:11 | 22.00 | 17.33 | 0.690120E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.123701E+11 | 20655.61 | 30-APR-11:02 | 34.50 | 21.63 | 0.614281E+09 | 854.61 | 28-APR-13:00 | 34.50 | 21.63 |
May | 0.177350E+11 | 22843.20 | 21-MAY-15:43 | 37.42 | 23.35 | 0.666439E+09 | 850.46 | 30-MAY-13:39 | 37.43 | 26.20 |
June | 0.197797E+11 | 21681.46 | 11-JUN-16:22 | 36.70 | 26.39 | 0.664510E+09 | 849.48 | 19-JUN-13:00 | 35.00 | 25.46 |
July | 0.220251E+11 | 22141.91 | 30-JUL-14:22 | 42.50 | 25.87 | 0.619169E+09 | 850.73 | 17-JUL-13:00 | 42.50 | 25.87 |
August | 0.237509E+11 | 21369.34 | 13-AUG-15:02 | 39.80 | 25.70 | 0.695104E+09 | 853.93 | 24-AUG-13:00 | 37.00 | 27.78 |
September | 0.180607E+11 | 21716.10 | 10-SEP-14:23 | 35.00 | 29.49 | 0.615989E+09 | 847.93 | 05-SEP-09:00 | 35.00 | 29.49 |
October | 0.160520E+11 | 22012.58 | 09-OCT-14:23 | 37.00 | 20.55 | 0.639790E+09 | 845.87 | 05-OCT-09:00 | 37.00 | 20.55 |
November | 0.106764E+11 | 16677.38 | 30-NOV-05:12 | 19.67 | 18.31 | 0.632090E+09 | 845.62 | 22-NOV-10:20 | 19.67 | 18.31 |
December | 0.710927E+10 | 16040.66 | 12-DEC-05:12 | 23.00 | 18.27 | 0.613959E+09 | 845.63 | 01-DEC-14:20 | 23.00 | 18.27 |
Annual Sum or Average | 0.167408E+12 | 0.765967E+10 | ||||||||
Minimum of Months | 0.475075E+10 | 14636.59 | 19.67 | 17.33 | 0.576446E+09 | 845.62 | 19.67 | 17.43 | ||
Maximum of Months | 0.237509E+11 | 22843.20 | 42.50 | 29.49 | 0.695104E+09 | 854.61 | 42.50 | 29.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.376583E+10 | 9986.13 | 30-JAN-06:02 | 20.03 | 17.43 | 0.409027E+09 | 544.96 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.436118E+10 | 13858.04 | 09-FEB-05:11 | 23.00 | 19.02 | 0.372052E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.680088E+10 | 11578.29 | 28-MAR-05:02 | 25.67 | 14.74 | 0.444813E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.919316E+10 | 18359.28 | 30-APR-11:02 | 34.50 | 21.63 | 0.396058E+09 | 551.34 | 28-APR-13:00 | 34.50 | 21.63 |
May | 0.139235E+11 | 20217.79 | 21-MAY-09:41 | 37.25 | 19.70 | 0.429719E+09 | 548.37 | 30-MAY-13:39 | 37.43 | 26.20 |
June | 0.146543E+11 | 18432.13 | 11-JUN-10:22 | 38.50 | 26.61 | 0.428367E+09 | 547.64 | 19-JUN-13:00 | 35.00 | 25.46 |
July | 0.159845E+11 | 19249.50 | 30-JUL-09:42 | 41.80 | 21.60 | 0.399200E+09 | 548.48 | 17-JUL-13:00 | 41.80 | 21.60 |
August | 0.173321E+11 | 18401.17 | 13-AUG-10:22 | 38.80 | 25.02 | 0.448168E+09 | 550.65 | 24-AUG-13:00 | 37.00 | 27.78 |
September | 0.140890E+11 | 18718.32 | 10-SEP-09:42 | 34.88 | 28.15 | 0.397214E+09 | 546.92 | 05-SEP-09:00 | 34.88 | 28.15 |
October | 0.123259E+11 | 18426.55 | 01-OCT-09:42 | 31.82 | 26.95 | 0.412549E+09 | 545.16 | 05-OCT-09:00 | 33.30 | 26.11 |
November | 0.782017E+10 | 14541.39 | 05-NOV-10:23 | 30.85 | 19.47 | 0.407611E+09 | 544.95 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.481373E+10 | 8494.54 | 12-DEC-06:03 | 23.03 | 17.89 | 0.395485E+09 | 544.96 | 01-DEC-14:20 | 23.03 | 17.89 |
Annual Sum or Average | 0.125064E+12 | 0.494026E+10 | ||||||||
Minimum of Months | 0.376583E+10 | 8494.54 | 20.03 | 14.74 | 0.372052E+09 | 544.95 | 20.03 | 17.19 | ||
Maximum of Months | 0.173321E+11 | 20217.79 | 41.80 | 28.15 | 0.448168E+09 | 551.34 | 41.80 | 28.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.853459E+10 | 19525.65 | 30-JAN-05:12 | 20.00 | 17.44 | 0.636191E+09 | 845.65 | 17-JAN-14:09 | 20.00 | 17.44 |
February | 0.917131E+10 | 25493.11 | 05-FEB-13:52 | 31.60 | 19.33 | 0.578104E+09 | 845.70 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.122128E+11 | 21055.51 | 26-MAR-14:32 | 32.73 | 18.52 | 0.690860E+09 | 845.92 | 27-MAR-13:00 | 35.00 | 19.40 |
April | 0.136285E+11 | 23670.27 | 30-APR-11:02 | 34.50 | 21.63 | 0.614638E+09 | 855.58 | 28-APR-13:00 | 34.50 | 21.63 |
May | 0.173527E+11 | 24963.93 | 21-MAY-12:22 | 38.00 | 22.80 | 0.666368E+09 | 850.52 | 30-MAY-13:39 | 37.43 | 26.20 |
June | 0.184836E+11 | 23946.47 | 11-JUN-15:02 | 36.90 | 27.61 | 0.664348E+09 | 849.40 | 19-JUN-13:00 | 35.00 | 25.46 |
July | 0.211315E+11 | 24818.89 | 30-JUL-13:42 | 44.08 | 24.34 | 0.619070E+09 | 850.74 | 17-JUL-13:00 | 44.08 | 24.34 |
August | 0.242614E+11 | 23997.50 | 13-AUG-15:02 | 39.80 | 25.70 | 0.695226E+09 | 854.60 | 24-AUG-13:00 | 37.00 | 27.78 |
September | 0.208539E+11 | 26442.91 | 10-SEP-14:23 | 35.00 | 29.49 | 0.616324E+09 | 848.16 | 05-SEP-09:00 | 35.00 | 29.49 |
October | 0.209973E+11 | 27429.85 | 29-OCT-13:03 | 34.92 | 15.89 | 0.640486E+09 | 846.26 | 20-OCT-13:00 | 34.92 | 15.89 |
November | 0.160809E+11 | 25666.51 | 11-NOV-13:02 | 30.50 | 19.15 | 0.633376E+09 | 846.29 | 13-NOV-14:09 | 33.00 | 16.45 |
December | 0.114965E+11 | 26018.24 | 03-DEC-12:42 | 29.50 | 17.81 | 0.615926E+09 | 845.97 | 04-DEC-14:09 | 27.00 | 21.00 |
Annual Sum or Average | 0.194205E+12 | 0.767092E+10 | ||||||||
Minimum of Months | 0.853459E+10 | 19525.65 | 20.00 | 15.89 | 0.578104E+09 | 845.65 | 20.00 | 15.89 | ||
Maximum of Months | 0.242614E+11 | 27429.85 | 44.08 | 29.49 | 0.695226E+09 | 855.58 | 44.08 | 29.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.525112E+10 | 18363.92 | 30-JAN-05:12 | 20.00 | 17.44 | 0.411022E+09 | 544.96 | 17-JAN-14:20 | 20.00 | 17.44 |
February | 0.677402E+10 | 23795.68 | 05-FEB-15:12 | 32.00 | 19.23 | 0.373720E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.109696E+11 | 20684.10 | 13-MAR-04:12 | 17.00 | 15.63 | 0.446331E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.137745E+11 | 23999.69 | 30-APR-16:22 | 31.25 | 25.60 | 0.397108E+09 | 552.71 | 28-APR-13:00 | 31.25 | 25.60 |
May | 0.141753E+11 | 25795.33 | 21-MAY-15:41 | 37.42 | 23.35 | 0.429776E+09 | 548.67 | 30-MAY-13:50 | 37.72 | 25.85 |
June | 0.163720E+11 | 24344.40 | 11-JUN-16:22 | 36.70 | 26.39 | 0.428522E+09 | 548.03 | 19-JUN-13:00 | 35.00 | 25.46 |
July | 0.187372E+11 | 24845.57 | 02-JUL-15:42 | 38.33 | 22.99 | 0.399401E+09 | 549.06 | 17-JUL-13:00 | 37.00 | 29.90 |
August | 0.214792E+11 | 24482.70 | 13-AUG-15:02 | 39.80 | 25.70 | 0.448638E+09 | 551.94 | 24-AUG-13:00 | 37.00 | 27.78 |
September | 0.141186E+11 | 24171.44 | 03-SEP-15:42 | 37.50 | 26.65 | 0.397238E+09 | 546.49 | 05-SEP-09:00 | 37.60 | 24.92 |
October | 0.136570E+11 | 23616.10 | 01-OCT-14:21 | 34.50 | 26.02 | 0.412775E+09 | 545.12 | 05-OCT-09:00 | 33.30 | 26.11 |
November | 0.113316E+11 | 24149.47 | 19-NOV-14:52 | 30.00 | 18.62 | 0.408572E+09 | 544.95 | 06-NOV-14:00 | 30.00 | 18.62 |
December | 0.950205E+10 | 23995.20 | 03-DEC-14:42 | 27.00 | 20.88 | 0.398097E+09 | 544.96 | 01-DEC-14:09 | 27.00 | 20.88 |
Annual Sum or Average | 0.156142E+12 | 0.495120E+10 | ||||||||
Minimum of Months | 0.525112E+10 | 18363.92 | 17.00 | 15.63 | 0.373720E+09 | 544.95 | 20.00 | 17.44 | ||
Maximum of Months | 0.214792E+11 | 25795.33 | 39.80 | 26.65 | 0.448638E+09 | 552.71 | 37.72 | 29.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339630E+10 | 5044.11 | 23-JAN-14:10 | 27.50 | 16.66 | 0.613439E+09 | 845.63 | 17-JAN-14:20 | 27.50 | 16.66 |
February | 0.396706E+10 | 10884.07 | 09-FEB-06:03 | 22.92 | 19.06 | 0.566614E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.647272E+10 | 15153.80 | 27-MAR-04:12 | 22.43 | 13.90 | 0.686024E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.866016E+10 | 15784.45 | 23-APR-15:31 | 32.33 | 18.32 | 0.613262E+09 | 845.71 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.139871E+11 | 22006.29 | 29-MAY-16:51 | 36.00 | 23.95 | 0.665841E+09 | 845.69 | 04-MAY-13:00 | 36.00 | 23.95 |
June | 0.156843E+11 | 21343.92 | 04-JUN-16:01 | 36.83 | 28.89 | 0.663680E+09 | 845.64 | 02-JUN-13:09 | 36.83 | 28.89 |
July | 0.169827E+11 | 21770.07 | 04-JUL-15:31 | 38.93 | 27.62 | 0.617768E+09 | 846.64 | 21-JUL-13:20 | 42.20 | 27.40 |
August | 0.177204E+11 | 21810.98 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692487E+09 | 846.76 | 10-AUG-13:20 | 43.00 | 28.12 |
September | 0.136814E+11 | 23086.16 | 04-SEP-16:11 | 40.47 | 23.66 | 0.614901E+09 | 845.63 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.107925E+11 | 21663.30 | 09-OCT-14:21 | 37.00 | 20.55 | 0.638974E+09 | 845.62 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.704753E+10 | 14039.89 | 20-NOV-06:02 | 25.85 | 18.49 | 0.630559E+09 | 845.62 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.418665E+10 | 10167.78 | 11-DEC-06:03 | 21.90 | 19.23 | 0.603322E+09 | 845.63 | 01-DEC-14:20 | 21.90 | 19.23 |
Annual Sum or Average | 0.122579E+12 | 0.760687E+10 | ||||||||
Minimum of Months | 0.339630E+10 | 5044.11 | 21.90 | 13.90 | 0.566614E+09 | 845.62 | 21.90 | 16.66 | ||
Maximum of Months | 0.177204E+11 | 23086.16 | 40.85 | 28.89 | 0.692487E+09 | 846.76 | 43.00 | 28.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273119E+10 | 6389.60 | 30-JAN-06:02 | 20.03 | 17.43 | 0.298347E+09 | 548.51 | 24-JAN-11:09 | 20.03 | 17.43 |
February | 0.327966E+10 | 9936.34 | 06-FEB-05:11 | 21.93 | 19.24 | 0.272955E+09 | 548.51 | 16-FEB-15:09 | 24.78 | 18.41 |
March | 0.535072E+10 | 13664.90 | 27-MAR-04:12 | 22.43 | 13.90 | 0.327140E+09 | 548.54 | 28-MAR-10:09 | 27.17 | 20.40 |
April | 0.744610E+10 | 19664.42 | 23-APR-10:12 | 32.80 | 16.75 | 0.292795E+09 | 548.53 | 28-APR-14:09 | 35.00 | 23.22 |
May | 0.114319E+11 | 20226.63 | 07-MAY-09:52 | 36.50 | 17.98 | 0.317451E+09 | 548.56 | 11-MAY-12:09 | 35.87 | 23.99 |
June | 0.121311E+11 | 20093.54 | 04-JUN-10:02 | 36.17 | 25.27 | 0.315913E+09 | 548.52 | 02-JUN-12:09 | 36.17 | 25.27 |
July | 0.130456E+11 | 20084.46 | 04-JUL-11:32 | 39.33 | 23.68 | 0.295167E+09 | 548.49 | 03-JUL-10:09 | 39.33 | 23.68 |
August | 0.139591E+11 | 19342.87 | 06-AUG-15:01 | 40.85 | 24.99 | 0.329606E+09 | 548.49 | 24-AUG-12:09 | 37.25 | 26.69 |
September | 0.111006E+11 | 20924.39 | 04-SEP-10:11 | 38.00 | 23.07 | 0.293400E+09 | 548.49 | 26-SEP-14:09 | 39.00 | 24.02 |
October | 0.894612E+10 | 19554.27 | 09-OCT-14:21 | 37.00 | 20.55 | 0.305251E+09 | 548.50 | 20-OCT-10:09 | 30.83 | 18.35 |
November | 0.582619E+10 | 16661.95 | 05-NOV-14:42 | 32.17 | 20.87 | 0.301389E+09 | 548.50 | 06-NOV-15:09 | 31.90 | 21.82 |
December | 0.326201E+10 | 7845.11 | 11-DEC-06:03 | 21.90 | 19.23 | 0.290330E+09 | 548.50 | 01-DEC-13:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.985103E+11 | 0.363975E+10 | ||||||||
Minimum of Months | 0.273119E+10 | 6389.60 | 20.03 | 13.90 | 0.272955E+09 | 548.49 | 20.03 | 17.43 | ||
Maximum of Months | 0.139591E+11 | 20924.39 | 40.85 | 25.27 | 0.329606E+09 | 548.56 | 39.33 | 26.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.752025E+10 | 18330.11 | 30-JAN-06:02 | 20.03 | 17.43 | 0.632766E+09 | 845.66 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.773491E+10 | 24550.05 | 05-FEB-12:43 | 31.08 | 19.52 | 0.575533E+09 | 845.71 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.978486E+10 | 24384.76 | 26-MAR-12:53 | 35.00 | 18.29 | 0.689328E+09 | 846.70 | 27-MAR-13:20 | 35.67 | 19.65 |
April | 0.102556E+11 | 22739.86 | 23-APR-15:31 | 32.33 | 18.32 | 0.614002E+09 | 845.74 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.140465E+11 | 24319.29 | 07-MAY-15:11 | 36.03 | 20.90 | 0.665834E+09 | 845.71 | 04-MAY-13:00 | 36.03 | 20.90 |
June | 0.148879E+11 | 23618.57 | 04-JUN-16:01 | 36.83 | 28.89 | 0.663530E+09 | 845.66 | 02-JUN-13:09 | 36.83 | 28.89 |
July | 0.167187E+11 | 24359.35 | 30-JUL-14:22 | 42.50 | 25.87 | 0.617706E+09 | 845.72 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.189808E+11 | 24529.74 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692645E+09 | 846.85 | 17-AUG-13:20 | 43.33 | 25.24 |
September | 0.171571E+11 | 27185.99 | 04-SEP-14:11 | 41.00 | 24.86 | 0.615466E+09 | 846.80 | 20-SEP-13:20 | 36.80 | 24.08 |
October | 0.165613E+11 | 26833.37 | 09-OCT-13:41 | 37.10 | 20.32 | 0.640327E+09 | 846.75 | 17-OCT-13:20 | 32.20 | 25.79 |
November | 0.131419E+11 | 26263.75 | 05-NOV-12:02 | 33.90 | 17.83 | 0.633260E+09 | 846.76 | 07-NOV-14:20 | 31.00 | 22.83 |
December | 0.895269E+10 | 24532.39 | 03-DEC-15:02 | 26.85 | 20.89 | 0.613870E+09 | 845.66 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.155743E+12 | 0.765427E+10 | ||||||||
Minimum of Months | 0.752025E+10 | 18330.11 | 20.03 | 17.43 | 0.575533E+09 | 845.66 | 20.03 | 17.31 | ||
Maximum of Months | 0.189808E+11 | 27185.99 | 42.50 | 28.89 | 0.692645E+09 | 846.85 | 43.33 | 28.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312867E+10 | 10008.88 | 30-JAN-06:02 | 20.03 | 17.43 | 0.402332E+09 | 544.96 | 17-JAN-14:20 | 20.03 | 17.43 |
February | 0.384818E+10 | 15429.57 | 05-FEB-16:03 | 31.83 | 18.84 | 0.369376E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.630798E+10 | 16925.93 | 26-MAR-17:33 | 31.07 | 18.86 | 0.444596E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.804077E+10 | 21314.53 | 23-APR-16:11 | 32.00 | 18.66 | 0.396250E+09 | 545.01 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.118401E+11 | 23354.18 | 29-MAY-16:51 | 36.00 | 23.95 | 0.429537E+09 | 545.00 | 04-MAY-13:00 | 36.00 | 23.95 |
June | 0.129655E+11 | 21882.64 | 04-JUN-17:21 | 35.00 | 28.83 | 0.428043E+09 | 544.97 | 02-JUN-13:09 | 35.00 | 28.83 |
July | 0.139640E+11 | 22249.09 | 04-JUL-15:31 | 38.93 | 27.62 | 0.398458E+09 | 545.01 | 03-JUL-09:09 | 38.93 | 27.62 |
August | 0.151667E+11 | 22488.44 | 06-AUG-16:21 | 40.05 | 25.93 | 0.446625E+09 | 544.95 | 04-AUG-09:20 | 40.05 | 25.93 |
September | 0.118096E+11 | 24659.76 | 04-SEP-16:11 | 40.47 | 23.66 | 0.396728E+09 | 544.95 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.960536E+10 | 22727.84 | 09-OCT-16:21 | 36.40 | 19.87 | 0.412485E+09 | 544.95 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.656093E+10 | 21548.01 | 05-NOV-15:22 | 31.70 | 21.27 | 0.407557E+09 | 544.95 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.402649E+10 | 10531.68 | 11-DEC-06:03 | 21.90 | 19.23 | 0.393720E+09 | 544.96 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.107264E+12 | 0.492571E+10 | ||||||||
Minimum of Months | 0.312867E+10 | 10008.88 | 20.03 | 17.43 | 0.369376E+09 | 544.95 | 20.03 | 17.19 | ||
Maximum of Months | 0.151667E+11 | 24659.76 | 40.47 | 28.83 | 0.446625E+09 | 545.01 | 40.05 | 28.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309419E+10 | 5257.59 | 23-JAN-14:10 | 27.50 | 16.66 | 0.597573E+09 | 845.63 | 17-JAN-14:20 | 27.50 | 16.66 |
February | 0.379654E+10 | 9976.41 | 06-FEB-06:03 | 21.88 | 19.06 | 0.557796E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.641145E+10 | 17696.01 | 02-MAR-06:02 | 28.80 | 15.43 | 0.681953E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.888560E+10 | 21279.82 | 30-APR-13:31 | 35.03 | 22.43 | 0.612616E+09 | 845.70 | 28-APR-13:09 | 35.03 | 22.43 |
May | 0.148586E+11 | 25632.05 | 21-MAY-15:41 | 37.42 | 23.35 | 0.665972E+09 | 845.68 | 04-MAY-13:00 | 37.42 | 23.35 |
June | 0.166233E+11 | 25591.50 | 04-JUN-16:11 | 36.67 | 28.92 | 0.663799E+09 | 845.65 | 02-JUN-13:09 | 36.67 | 28.92 |
July | 0.182356E+11 | 26107.81 | 04-JUL-15:21 | 39.20 | 27.54 | 0.617942E+09 | 845.70 | 03-JUL-09:09 | 39.20 | 27.54 |
August | 0.189514E+11 | 24605.37 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692632E+09 | 845.71 | 17-AUG-13:50 | 42.33 | 26.20 |
September | 0.144631E+11 | 25728.01 | 03-SEP-14:51 | 38.00 | 27.45 | 0.615052E+09 | 845.63 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.110360E+11 | 19722.45 | 09-OCT-15:12 | 36.93 | 20.06 | 0.639033E+09 | 845.62 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.694653E+10 | 19722.40 | 05-NOV-14:52 | 32.00 | 20.75 | 0.629494E+09 | 845.62 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.390911E+10 | 8708.35 | 11-DEC-06:03 | 21.90 | 19.23 | 0.594473E+09 | 845.63 | 01-DEC-14:20 | 21.90 | 19.23 |
Annual Sum or Average | 0.127211E+12 | 0.756833E+10 | ||||||||
Minimum of Months | 0.309419E+10 | 5257.59 | 21.88 | 15.43 | 0.557796E+09 | 845.62 | 21.90 | 16.66 | ||
Maximum of Months | 0.189514E+11 | 26107.81 | 40.85 | 28.92 | 0.692632E+09 | 845.71 | 42.33 | 28.92 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.266084E+10 | 6347.57 | 30-JAN-06:02 | 20.03 | 17.43 | 0.400453E+09 | 544.97 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.332488E+10 | 11861.39 | 05-FEB-15:12 | 32.00 | 19.23 | 0.367738E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.554348E+10 | 14729.08 | 27-MAR-04:12 | 22.43 | 13.90 | 0.442891E+09 | 545.00 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.781719E+10 | 20188.28 | 30-APR-10:52 | 34.00 | 21.75 | 0.395798E+09 | 545.02 | 25-APR-09:09 | 34.00 | 21.75 |
May | 0.122934E+11 | 21684.88 | 21-MAY-10:21 | 38.15 | 20.67 | 0.429504E+09 | 545.15 | 22-MAY-09:50 | 36.25 | 22.78 |
June | 0.130235E+11 | 21164.65 | 04-JUN-15:31 | 36.67 | 28.71 | 0.427973E+09 | 544.97 | 02-JUN-13:09 | 36.67 | 28.71 |
July | 0.141305E+11 | 21703.40 | 04-JUL-15:21 | 39.20 | 27.54 | 0.398466E+09 | 545.05 | 31-JUL-09:00 | 39.90 | 23.78 |
August | 0.150662E+11 | 20296.36 | 06-AUG-15:01 | 40.85 | 24.99 | 0.446574E+09 | 545.24 | 30-AUG-09:50 | 39.75 | 24.22 |
September | 0.118657E+11 | 21858.93 | 04-SEP-10:11 | 38.00 | 23.07 | 0.396688E+09 | 544.96 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.928973E+10 | 18858.28 | 09-OCT-09:13 | 31.10 | 27.33 | 0.412368E+09 | 544.95 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.598191E+10 | 18993.43 | 05-NOV-14:52 | 32.00 | 20.75 | 0.407192E+09 | 544.95 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.324078E+10 | 6898.96 | 11-DEC-06:03 | 21.90 | 19.23 | 0.390893E+09 | 544.96 | 01-DEC-14:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.104238E+12 | 0.491654E+10 | ||||||||
Minimum of Months | 0.266084E+10 | 6347.57 | 20.03 | 13.90 | 0.367738E+09 | 544.95 | 20.03 | 17.19 | ||
Maximum of Months | 0.150662E+11 | 21858.93 | 40.85 | 28.71 | 0.446574E+09 | 545.24 | 39.90 | 28.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.685973E+10 | 19040.68 | 30-JAN-06:02 | 20.03 | 17.43 | 0.625392E+09 | 845.66 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.740722E+10 | 27735.43 | 05-FEB-13:52 | 31.60 | 19.33 | 0.571099E+09 | 845.71 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.963471E+10 | 23873.79 | 26-MAR-14:32 | 32.73 | 18.52 | 0.686854E+09 | 845.79 | 27-MAR-13:39 | 35.33 | 19.53 |
April | 0.104609E+11 | 25965.35 | 30-APR-11:32 | 36.00 | 21.14 | 0.613404E+09 | 845.73 | 28-APR-13:09 | 36.00 | 21.14 |
May | 0.149154E+11 | 28243.61 | 21-MAY-15:41 | 37.42 | 23.35 | 0.665964E+09 | 845.70 | 04-MAY-13:00 | 37.42 | 23.35 |
June | 0.158196E+11 | 27812.20 | 04-JUN-15:31 | 36.67 | 28.71 | 0.663668E+09 | 845.67 | 02-JUN-13:09 | 36.67 | 28.71 |
July | 0.179683E+11 | 28528.39 | 04-JUL-15:21 | 39.20 | 27.54 | 0.617897E+09 | 845.72 | 03-JUL-09:09 | 39.20 | 27.54 |
August | 0.202208E+11 | 27247.19 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692769E+09 | 846.11 | 17-AUG-13:50 | 42.33 | 26.20 |
September | 0.179344E+11 | 29631.05 | 03-SEP-14:51 | 38.00 | 27.45 | 0.615534E+09 | 845.96 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.166367E+11 | 27035.20 | 09-OCT-13:52 | 37.00 | 20.40 | 0.640295E+09 | 846.10 | 20-OCT-13:00 | 34.00 | 18.77 |
November | 0.129454E+11 | 28673.75 | 05-NOV-12:12 | 33.80 | 18.48 | 0.632822E+09 | 846.10 | 13-NOV-14:09 | 33.00 | 16.45 |
December | 0.837753E+10 | 27769.67 | 03-DEC-12:52 | 29.80 | 17.63 | 0.610454E+09 | 845.66 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.159181E+12 | 0.763615E+10 | ||||||||
Minimum of Months | 0.685973E+10 | 19040.68 | 20.03 | 17.43 | 0.571099E+09 | 845.66 | 20.03 | 16.45 | ||
Maximum of Months | 0.202208E+11 | 29631.05 | 40.85 | 28.71 | 0.692769E+09 | 846.11 | 42.33 | 28.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290867E+10 | 10275.02 | 30-JAN-06:02 | 20.03 | 17.43 | 0.394549E+09 | 544.96 | 17-JAN-14:20 | 20.03 | 17.43 |
February | 0.370817E+10 | 18787.63 | 05-FEB-15:12 | 32.00 | 19.23 | 0.365425E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.622850E+10 | 18163.18 | 27-MAR-04:12 | 22.43 | 13.90 | 0.443229E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.814893E+10 | 22598.74 | 30-APR-16:51 | 31.00 | 25.72 | 0.396052E+09 | 545.01 | 28-APR-13:09 | 31.00 | 25.72 |
May | 0.123955E+11 | 26097.04 | 21-MAY-15:41 | 37.42 | 23.35 | 0.429573E+09 | 544.99 | 04-MAY-13:00 | 37.42 | 23.35 |
June | 0.135629E+11 | 25778.78 | 04-JUN-16:11 | 36.67 | 28.92 | 0.428078E+09 | 544.97 | 02-JUN-13:09 | 36.67 | 28.92 |
July | 0.147395E+11 | 26127.89 | 04-JUL-15:21 | 39.20 | 27.54 | 0.398515E+09 | 545.00 | 03-JUL-09:09 | 39.20 | 27.54 |
August | 0.159592E+11 | 24438.56 | 06-AUG-15:41 | 40.25 | 25.55 | 0.446676E+09 | 544.94 | 04-AUG-13:20 | 40.25 | 25.55 |
September | 0.122902E+11 | 25879.14 | 03-SEP-14:51 | 38.00 | 27.45 | 0.396773E+09 | 544.95 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.967272E+10 | 22467.01 | 09-OCT-15:52 | 36.80 | 18.76 | 0.412477E+09 | 544.95 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.647101E+10 | 23218.07 | 05-NOV-15:32 | 31.60 | 21.44 | 0.407242E+09 | 544.95 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.379035E+10 | 10078.42 | 03-DEC-15:32 | 26.40 | 20.90 | 0.390183E+09 | 544.96 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.109876E+12 | 0.490877E+10 | ||||||||
Minimum of Months | 0.290867E+10 | 10078.42 | 20.03 | 13.90 | 0.365425E+09 | 544.94 | 20.03 | 17.19 | ||
Maximum of Months | 0.159592E+11 | 26127.89 | 40.25 | 28.92 | 0.446676E+09 | 545.01 | 40.25 | 28.92 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.457321E+10 | 9114.20 | 30-JAN-06:15 | 20.07 | 17.42 | 0.00 | 0.00 | 01-JAN-00:10 | 20.07 | 17.42 |
February | 0.580323E+10 | 11165.80 | 07-FEB-06:15 | 20.90 | 18.90 | 0.00 | 0.00 | 01-FEB-00:10 | 20.90 | 18.90 |
March | 0.924145E+10 | 12274.91 | 29-MAR-05:15 | 20.33 | 18.79 | 0.00 | 0.00 | 01-MAR-00:10 | 20.33 | 18.79 |
April | 0.120639E+11 | 15299.95 | 27-APR-05:10 | 22.83 | 13.44 | 0.00 | 0.00 | 01-APR-00:10 | 22.83 | 13.44 |
May | 0.188019E+11 | 22213.93 | 30-MAY-05:13 | 27.00 | 24.83 | 0.00 | 0.00 | 01-MAY-00:10 | 27.00 | 24.83 |
June | 0.209858E+11 | 21468.77 | 12-JUN-05:15 | 29.13 | 24.04 | 0.00 | 0.00 | 01-JUN-00:10 | 29.13 | 24.04 |
July | 0.237912E+11 | 25301.04 | 24-JUL-05:20 | 32.67 | 27.85 | 0.00 | 0.00 | 01-JUL-00:10 | 32.67 | 27.85 |
August | 0.266690E+11 | 25300.79 | 07-AUG-05:30 | 32.45 | 23.07 | 0.00 | 0.00 | 01-AUG-00:10 | 32.45 | 23.07 |
September | 0.203615E+11 | 24737.10 | 05-SEP-05:15 | 30.33 | 24.49 | 0.00 | 0.00 | 01-SEP-00:10 | 30.33 | 24.49 |
October | 0.181543E+11 | 23587.63 | 10-OCT-05:20 | 26.67 | 24.04 | 0.00 | 0.00 | 01-OCT-00:10 | 26.67 | 24.04 |
November | 0.118075E+11 | 16558.02 | 13-NOV-06:08 | 20.92 | 17.72 | 0.00 | 0.00 | 01-NOV-00:10 | 20.92 | 17.72 |
December | 0.715393E+10 | 10959.71 | 04-DEC-06:15 | 17.40 | 16.34 | 0.00 | 0.00 | 01-DEC-00:10 | 17.40 | 16.34 |
Annual Sum or Average | 0.179407E+12 | 0.00 | ||||||||
Minimum of Months | 0.457321E+10 | 9114.20 | 17.40 | 13.44 | 0.00 | 0.00 | 17.40 | 13.44 | ||
Maximum of Months | 0.266690E+11 | 25301.04 | 32.67 | 27.85 | 0.00 | 0.00 | 32.67 | 27.85 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244893E+10 | 4135.29 | 30-JAN-06:15 | 20.07 | 17.42 | 0.00 | 0.00 | 01-JAN-00:10 | 20.07 | 17.42 |
February | 0.334106E+10 | 6200.84 | 06-FEB-15:30 | 31.95 | 17.43 | 0.00 | 0.00 | 01-FEB-00:10 | 31.95 | 17.43 |
March | 0.586021E+10 | 9217.76 | 27-MAR-16:00 | 35.00 | 18.85 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 18.85 |
April | 0.798370E+10 | 10222.12 | 24-APR-05:02 | 21.83 | 13.96 | 0.00 | 0.00 | 01-APR-00:10 | 21.83 | 13.96 |
May | 0.130925E+11 | 14757.77 | 30-MAY-05:03 | 27.00 | 24.83 | 0.00 | 0.00 | 01-MAY-00:10 | 27.00 | 24.83 |
June | 0.145826E+11 | 13762.49 | 05-JUN-05:02 | 29.00 | 23.92 | 0.00 | 0.00 | 01-JUN-00:10 | 29.00 | 23.92 |
July | 0.164705E+11 | 17653.08 | 17-JUL-05:13 | 31.00 | 26.67 | 0.00 | 0.00 | 01-JUL-00:10 | 31.00 | 26.67 |
August | 0.180838E+11 | 21220.42 | 07-AUG-05:12 | 32.63 | 23.12 | 0.00 | 0.00 | 01-AUG-00:10 | 32.63 | 23.12 |
September | 0.138380E+11 | 19942.13 | 05-SEP-05:15 | 30.33 | 24.49 | 0.00 | 0.00 | 01-SEP-00:10 | 30.33 | 24.49 |
October | 0.113990E+11 | 17119.28 | 10-OCT-05:13 | 26.67 | 24.04 | 0.00 | 0.00 | 01-OCT-00:10 | 26.67 | 24.04 |
November | 0.760791E+10 | 10062.27 | 13-NOV-06:15 | 20.83 | 17.71 | 0.00 | 0.00 | 01-NOV-00:10 | 20.83 | 17.71 |
December | 0.383609E+10 | 6576.16 | 11-DEC-06:15 | 21.80 | 19.16 | 0.00 | 0.00 | 01-DEC-00:10 | 21.80 | 19.16 |
Annual Sum or Average | 0.118544E+12 | 0.00 | ||||||||
Minimum of Months | 0.244893E+10 | 4135.29 | 20.07 | 13.96 | 0.00 | 0.00 | 20.07 | 13.96 | ||
Maximum of Months | 0.180838E+11 | 21220.42 | 35.00 | 26.67 | 0.00 | 0.00 | 35.00 | 26.67 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288148E+10 | 7972.90 | 23-JAN-14:10 | 27.50 | 16.66 | 0.00 | 0.00 | 01-JAN-00:10 | 27.50 | 16.66 |
February | 0.442934E+10 | 13014.77 | 06-FEB-15:00 | 32.50 | 17.28 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 17.28 |
March | 0.813017E+10 | 18576.55 | 27-MAR-14:30 | 35.00 | 19.13 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 19.13 |
April | 0.117980E+11 | 20527.21 | 28-APR-12:50 | 37.58 | 22.61 | 0.00 | 0.00 | 01-APR-00:10 | 37.58 | 22.61 |
May | 0.201366E+11 | 23368.54 | 10-MAY-14:40 | 40.00 | 20.07 | 0.00 | 0.00 | 01-MAY-00:10 | 40.00 | 20.07 |
June | 0.225945E+11 | 24146.42 | 09-JUN-14:50 | 41.83 | 25.26 | 0.00 | 0.00 | 01-JUN-00:10 | 41.83 | 25.26 |
July | 0.257918E+11 | 26369.06 | 21-JUL-13:00 | 42.30 | 27.28 | 0.00 | 0.00 | 01-JUL-00:10 | 42.30 | 27.28 |
August | 0.275699E+11 | 26653.73 | 16-AUG-13:50 | 44.03 | 25.58 | 0.00 | 0.00 | 01-AUG-00:10 | 44.03 | 25.58 |
September | 0.202731E+11 | 28255.05 | 04-SEP-15:31 | 40.80 | 24.09 | 0.00 | 0.00 | 01-SEP-00:10 | 40.80 | 24.09 |
October | 0.151766E+11 | 19035.92 | 05-OCT-14:40 | 36.00 | 22.65 | 0.00 | 0.00 | 01-OCT-00:10 | 36.00 | 22.65 |
November | 0.903375E+10 | 15177.23 | 01-NOV-14:20 | 32.67 | 26.20 | 0.00 | 0.00 | 01-NOV-00:10 | 32.67 | 26.20 |
December | 0.419969E+10 | 10343.03 | 04-DEC-14:05 | 27.00 | 21.00 | 0.00 | 0.00 | 01-DEC-00:10 | 27.00 | 21.00 |
Annual Sum or Average | 0.172015E+12 | 0.00 | ||||||||
Minimum of Months | 0.288148E+10 | 7972.90 | 27.00 | 16.66 | 0.00 | 0.00 | 27.00 | 16.66 | ||
Maximum of Months | 0.275699E+11 | 28255.05 | 44.03 | 27.28 | 0.00 | 0.00 | 44.03 | 27.28 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.417639E+10 | 1885.51 | 29-JAN-17:40 | 24.33 | 19.64 | 95236987.99 | 126.85 | 17-JAN-14:00 | 24.33 | 19.64 |
February | 0.851651E+10 | 3831.25 | 05-FEB-17:27 | 31.00 | 18.68 | 86408870.07 | 126.85 | 07-FEB-10:09 | 26.33 | 20.66 |
March | 0.145805E+11 | 7197.86 | 31-MAR-24:00 | 22.30 | 20.22 | 0.103245E+09 | 126.85 | 29-MAR-09:09 | 22.30 | 20.22 |
April | 0.191146E+11 | 7850.93 | 23-APR-18:00 | 30.00 | 19.02 | 92078655.62 | 139.58 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.496325E+10 | 3695.88 | 31-MAY-23:57 | 32.70 | 23.39 | 99239140.11 | 126.85 | 11-MAY-13:09 | 32.70 | 23.39 |
June | 0.975192E+10 | 5545.37 | 30-JUN-23:57 | 31.70 | 26.86 | 98979027.21 | 126.88 | 08-JUN-09:09 | 31.70 | 26.86 |
July | 0.153528E+11 | 7332.62 | 31-JUL-23:57 | 33.30 | 28.31 | 91890447.76 | 126.84 | 26-JUL-09:09 | 33.30 | 28.31 |
August | 0.195354E+11 | 7698.86 | 15-AUG-04:12 | 29.80 | 23.20 | 0.114352E+09 | 152.33 | 10-AUG-13:00 | 29.80 | 23.20 |
September | 0.493502E+10 | 3693.43 | 30-SEP-24:00 | 29.00 | 26.44 | 91606846.16 | 126.85 | 25-SEP-13:39 | 29.00 | 26.44 |
October | 0.100431E+11 | 5452.37 | 31-OCT-24:00 | 27.40 | 21.22 | 95251671.44 | 126.88 | 17-OCT-09:09 | 27.40 | 21.22 |
November | 0.143088E+11 | 6069.10 | 12-NOV-17:17 | 28.67 | 17.77 | 94311560.24 | 126.85 | 01-NOV-09:09 | 28.67 | 17.77 |
December | 0.195623E+11 | 7706.16 | 03-DEC-17:07 | 25.17 | 21.34 | 91884218.90 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.144841E+12 | 0.115448E+10 | ||||||||
Minimum of Months | 0.417639E+10 | 1885.51 | 22.30 | 17.77 | 86408870.07 | 126.83 | 19.67 | 17.77 | ||
Maximum of Months | 0.195623E+11 | 7850.93 | 33.30 | 28.31 | 0.114352E+09 | 152.33 | 37.33 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331459E+10 | 1625.84 | 29-JAN-17:50 | 24.17 | 19.49 | 95233574.32 | 126.84 | 25-JAN-14:00 | 24.17 | 19.49 |
February | 0.767272E+10 | 3507.51 | 05-FEB-17:40 | 31.00 | 18.75 | 86408132.66 | 126.85 | 09-FEB-10:09 | 23.92 | 19.44 |
March | 0.136738E+11 | 6916.43 | 31-MAR-24:00 | 22.30 | 20.22 | 0.103244E+09 | 126.84 | 02-MAR-14:09 | 22.30 | 20.22 |
April | 0.181313E+11 | 7360.95 | 23-APR-17:44 | 30.17 | 19.07 | 92005175.48 | 138.47 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.439609E+10 | 3467.29 | 31-MAY-23:57 | 32.70 | 23.39 | 99237159.87 | 126.85 | 22-MAY-13:00 | 32.70 | 23.39 |
June | 0.899167E+10 | 5214.67 | 30-JUN-23:57 | 31.70 | 26.86 | 98978545.28 | 126.87 | 20-JUN-09:09 | 31.70 | 26.86 |
July | 0.142266E+11 | 6942.77 | 31-JUL-23:57 | 33.30 | 28.31 | 91892366.33 | 126.85 | 05-JUL-09:09 | 33.30 | 28.31 |
August | 0.184603E+11 | 7203.13 | 14-AUG-03:31 | 31.00 | 24.23 | 0.113129E+09 | 150.45 | 10-AUG-13:00 | 31.00 | 24.23 |
September | 0.428745E+10 | 3400.88 | 30-SEP-23:33 | 29.00 | 26.39 | 91605897.63 | 126.85 | 05-SEP-13:39 | 29.00 | 26.39 |
October | 0.920511E+10 | 5214.13 | 31-OCT-24:00 | 27.40 | 21.22 | 95250302.61 | 126.87 | 06-OCT-09:09 | 27.40 | 21.22 |
November | 0.134136E+11 | 5523.76 | 05-NOV-16:54 | 31.00 | 21.45 | 94311232.19 | 126.84 | 01-NOV-09:09 | 31.00 | 21.45 |
December | 0.182679E+11 | 7138.32 | 03-DEC-17:12 | 25.13 | 21.24 | 91884201.50 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.134041E+12 | 0.115318E+10 | ||||||||
Minimum of Months | 0.331459E+10 | 1625.84 | 22.30 | 18.75 | 86408132.66 | 126.83 | 19.67 | 18.50 | ||
Maximum of Months | 0.184603E+11 | 7360.95 | 33.30 | 28.31 | 0.113129E+09 | 150.45 | 37.33 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283319E+10 | 1681.20 | 29-JAN-17:40 | 24.33 | 19.64 | 95233278.83 | 126.84 | 31-JAN-14:09 | 23.00 | 16.33 |
February | 0.740715E+10 | 3648.03 | 05-FEB-17:27 | 31.00 | 18.68 | 86408295.38 | 126.85 | 07-FEB-14:00 | 28.00 | 22.41 |
March | 0.135546E+11 | 6861.06 | 31-MAR-24:00 | 22.30 | 20.22 | 0.103244E+09 | 126.85 | 02-MAR-14:09 | 22.30 | 20.22 |
April | 0.181579E+11 | 7586.16 | 23-APR-18:03 | 29.83 | 19.17 | 91993963.76 | 138.95 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.453734E+10 | 3518.80 | 31-MAY-23:57 | 32.70 | 23.39 | 99237889.03 | 126.85 | 11-MAY-13:09 | 32.70 | 23.39 |
June | 0.913772E+10 | 5237.21 | 30-JUN-23:57 | 31.70 | 26.86 | 98979043.18 | 126.87 | 08-JUN-13:09 | 31.70 | 26.86 |
July | 0.144457E+11 | 7007.42 | 31-JUL-23:57 | 33.30 | 28.31 | 91892391.79 | 126.85 | 05-JUL-09:09 | 33.30 | 28.31 |
August | 0.186496E+11 | 7306.97 | 14-AUG-03:02 | 31.00 | 24.41 | 0.113125E+09 | 151.83 | 10-AUG-13:00 | 31.00 | 24.41 |
September | 0.442314E+10 | 3442.95 | 30-SEP-24:00 | 29.00 | 26.44 | 91606228.65 | 126.85 | 25-SEP-13:09 | 29.00 | 26.44 |
October | 0.926507E+10 | 5209.15 | 31-OCT-24:00 | 27.40 | 21.22 | 95250654.81 | 126.87 | 17-OCT-13:09 | 27.40 | 21.22 |
November | 0.133389E+11 | 5677.06 | 05-NOV-17:05 | 30.83 | 21.62 | 94311523.96 | 126.85 | 01-NOV-13:00 | 30.83 | 21.62 |
December | 0.179621E+11 | 7181.19 | 03-DEC-17:07 | 25.17 | 21.34 | 91884529.00 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.133712E+12 | 0.115317E+10 | ||||||||
Minimum of Months | 0.283319E+10 | 1681.20 | 22.30 | 18.68 | 86408295.38 | 126.83 | 19.67 | 16.33 | ||
Maximum of Months | 0.186496E+11 | 7586.16 | 33.30 | 28.31 | 0.113125E+09 | 151.83 | 37.33 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242353E+12 | 92860.08 | 02-JAN-17:00 | 21.00 | 13.15 | 0.206204E+10 | 2747.82 | 19-JAN-10:09 | 16.17 | 11.29 |
February | 0.439125E+12 | 184387.56 | 09-FEB-16:52 | 21.00 | 18.37 | 0.187074E+10 | 2747.75 | 13-FEB-10:09 | 19.50 | 13.91 |
March | 0.731089E+12 | 359117.38 | 31-MAR-24:00 | 22.30 | 20.22 | 0.223516E+10 | 2746.79 | 16-MAR-09:09 | 22.30 | 20.22 |
April | 0.944408E+12 | 369647.99 | 28-APR-13:05 | 36.42 | 23.03 | 0.198505E+10 | 2911.41 | 28-APR-12:20 | 36.42 | 23.03 |
May | 0.245063E+12 | 177624.39 | 31-MAY-23:57 | 32.70 | 23.39 | 0.214870E+10 | 2747.16 | 30-MAY-09:09 | 32.70 | 23.39 |
June | 0.474633E+12 | 269320.52 | 30-JUN-23:57 | 31.70 | 26.86 | 0.214278E+10 | 2747.00 | 20-JUN-09:09 | 31.70 | 26.86 |
July | 0.738031E+12 | 362207.57 | 31-JUL-23:57 | 33.30 | 28.31 | 0.198935E+10 | 2746.27 | 26-JUL-09:09 | 33.30 | 28.31 |
August | 0.984808E+12 | 374289.71 | 10-AUG-21:01 | 34.93 | 27.53 | 0.228669E+10 | 3169.62 | 16-AUG-13:09 | 44.17 | 25.68 |
September | 0.242028E+12 | 178870.28 | 30-SEP-24:00 | 29.00 | 26.44 | 0.198366E+10 | 2747.21 | 15-SEP-09:09 | 29.00 | 26.44 |
October | 0.494609E+12 | 270261.76 | 31-OCT-24:00 | 27.40 | 21.22 | 0.206206E+10 | 2746.86 | 17-OCT-09:09 | 27.40 | 21.22 |
November | 0.713514E+12 | 278053.65 | 03-NOV-16:00 | 30.20 | 23.81 | 0.204165E+10 | 2746.05 | 01-NOV-09:09 | 30.20 | 23.81 |
December | 0.980063E+12 | 369057.47 | 12-DEC-17:00 | 23.80 | 16.27 | 0.198930E+10 | 2747.74 | 18-DEC-10:09 | 20.42 | 13.70 |
Annual Sum or Average | 0.722973E+13 | 0.247972E+11 | ||||||||
Minimum of Months | 0.242028E+12 | 92860.08 | 21.00 | 13.15 | 0.187074E+10 | 2746.05 | 16.17 | 11.29 | ||
Maximum of Months | 0.984808E+12 | 374289.71 | 36.42 | 28.31 | 0.228669E+10 | 3169.62 | 44.17 | 28.31 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60739.20 | 186.43 | 03-JAN-06:08 | 12.93 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 60739.20 | |||
Minimum of Months | 0.00 | 0.00 | 12.93 | |
Maximum of Months | 60739.20 | 186.43 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41335.09 | 206.68 | 02-JAN-06:07 | 13.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 41335.09 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 41335.09 | 206.68 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76547719.10 | 8228.72 | 17-JAN-05:12 | 16.67 |
February | 80142013.30 | 9466.02 | 21-FEB-05:11 | 14.67 |
March | 77680532.23 | 10213.15 | 06-MAR-05:12 | 16.67 |
April | 57802128.86 | 6994.24 | 02-APR-14:12 | 33.67 |
May | 32608898.82 | 4566.33 | 07-MAY-14:52 | 37.00 |
June | 25460785.91 | 3913.81 | 25-JUN-14:22 | 35.50 |
July | 34936289.81 | 4875.39 | 30-JUL-11:02 | 44.67 |
August | 31652708.44 | 4028.97 | 27-AUG-10:22 | 37.15 |
September | 23353488.46 | 4569.14 | 24-SEP-15:01 | 33.98 |
October | 46846439.19 | 4873.51 | 29-OCT-11:42 | 34.42 |
November | 89117896.53 | 9738.06 | 30-NOV-05:12 | 19.67 |
December | 0.140758E+09 | 10944.56 | 18-DEC-05:11 | 13.00 |
Annual Sum or Average | 0.716907E+09 | |||
Minimum of Months | 23353488.46 | 3913.81 | 13.00 | |
Maximum of Months | 0.140758E+09 | 10944.56 | 44.67 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45284036.86 | 6408.91 | 02-JAN-05:11 | 13.67 |
February | 34976120.71 | 6855.36 | 21-FEB-05:11 | 14.67 |
March | 29993066.52 | 6571.55 | 02-MAR-04:02 | 29.10 |
April | 35009143.24 | 6541.14 | 02-APR-14:32 | 33.33 |
May | 33183855.24 | 6165.97 | 07-MAY-14:31 | 37.00 |
June | 26989840.11 | 5520.31 | 04-JUN-14:01 | 37.67 |
July | 40152630.81 | 6061.61 | 30-JUL-11:02 | 44.67 |
August | 27105713.66 | 5171.32 | 13-AUG-14:22 | 40.00 |
September | 32041787.04 | 6143.58 | 17-SEP-14:01 | 36.00 |
October | 41409899.71 | 6230.17 | 29-OCT-13:41 | 34.18 |
November | 38060032.76 | 5136.13 | 05-NOV-14:42 | 32.17 |
December | 38542754.18 | 5496.27 | 18-DEC-06:02 | 13.17 |
Annual Sum or Average | 0.422749E+09 | |||
Minimum of Months | 26989840.11 | 5136.13 | 13.17 | |
Maximum of Months | 45284036.86 | 6855.36 | 44.67 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.642212E+09 | 13376.66 | 12-JAN-06:02 | 13.93 |
February | 0.367497E+09 | 14984.72 | 21-FEB-06:03 | 13.95 |
March | 0.222462E+09 | 13130.98 | 06-MAR-06:02 | 15.97 |
April | 64354505.94 | 11094.78 | 05-APR-05:03 | 17.00 |
May | 9697449.52 | 8487.30 | 02-MAY-04:11 | 22.87 |
June | 2353503.65 | 3779.20 | 07-JUN-03:02 | 25.83 |
July | 110680.41 | 922.34 | 30-JUL-08:22 | 36.90 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 2854793.45 | 3997.55 | 22-SEP-03:02 | 28.00 |
October | 20609868.82 | 10146.39 | 30-OCT-04:12 | 22.40 |
November | 69361763.38 | 11275.54 | 22-NOV-06:03 | 16.98 |
December | 0.369743E+09 | 12575.95 | 29-DEC-06:03 | 15.87 |
Annual Sum or Average | 0.177126E+10 | |||
Minimum of Months | 0.00 | 0.00 | 13.93 | |
Maximum of Months | 0.642212E+09 | 14984.72 | 36.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968216E+10 | 10174.14 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.878253E+10 | 10174.14 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.104353E+11 | 10174.14 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.932187E+10 | 10174.14 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.100587E+11 | 10174.14 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.100099E+11 | 10174.14 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.937071E+10 | 10174.14 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.104353E+11 | 10174.14 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.932187E+10 | 10174.14 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.968216E+10 | 10174.14 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.956821E+10 | 10174.14 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.937071E+10 | 10174.14 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.116039E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.878253E+10 | 10174.14 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.104353E+11 | 10174.14 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.660438E+09 | 854.72 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.579779E+09 | 880.50 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.671216E+09 | 1031.32 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.586417E+09 | 848.40 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.615151E+09 | 545.86 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.605754E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.577587E+09 | 637.35 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.645153E+09 | 600.46 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.590454E+09 | 616.14 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.629103E+09 | 761.09 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.644693E+09 | 957.43 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.648232E+09 | 983.36 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.745398E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.577587E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.671216E+09 | 1031.32 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.420959E+09 | 579.47 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.371987E+09 | 580.65 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.430908E+09 | 654.92 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.377893E+09 | 496.80 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.398732E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.393067E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.373749E+09 | 395.91 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.416599E+09 | 351.77 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.380264E+09 | 351.77 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.402569E+09 | 381.17 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.413951E+09 | 634.58 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.413020E+09 | 642.41 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.479370E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.371987E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.430908E+09 | 654.92 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.640116E+09 | 754.37 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.569703E+09 | 833.30 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.667275E+09 | 1029.00 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.587600E+09 | 854.35 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.620847E+09 | 582.86 | 23-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.611845E+09 | 593.66 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.582355E+09 | 750.07 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.647834E+09 | 596.39 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.589654E+09 | 613.16 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.622058E+09 | 608.81 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.627209E+09 | 830.74 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.624412E+09 | 919.89 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.739091E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.569703E+09 | 582.86 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.667275E+09 | 1029.00 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.417813E+09 | 548.11 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.369581E+09 | 519.61 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.433246E+09 | 668.86 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.379620E+09 | 573.64 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.399680E+09 | 396.88 | 23-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.393078E+09 | 398.63 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.375326E+09 | 516.87 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.418008E+09 | 410.79 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.381058E+09 | 485.89 | 06-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.405014E+09 | 531.73 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.407195E+09 | 533.33 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.407261E+09 | 612.61 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.478688E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.369581E+09 | 396.88 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.433246E+09 | 668.86 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.658713E+09 | 850.09 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.578462E+09 | 877.19 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.670290E+09 | 1030.00 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.585880E+09 | 844.72 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.614864E+09 | 545.86 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.605052E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.577252E+09 | 633.52 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.644765E+09 | 594.54 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.589828E+09 | 611.10 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.628170E+09 | 754.73 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.643321E+09 | 954.76 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.646435E+09 | 981.28 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.744303E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.577252E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.670290E+09 | 1030.00 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.420084E+09 | 575.48 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.371413E+09 | 576.48 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.430335E+09 | 653.00 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.377598E+09 | 492.27 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.398474E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.392792E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.373512E+09 | 393.23 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.416304E+09 | 351.77 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.379998E+09 | 351.77 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.402239E+09 | 377.22 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.413375E+09 | 631.87 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.412241E+09 | 639.90 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.478837E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.371413E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.430335E+09 | 653.00 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639770E+09 | 750.12 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.569302E+09 | 829.74 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.666645E+09 | 1027.67 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.587084E+09 | 850.71 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.620401E+09 | 545.88 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.611340E+09 | 587.20 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.581787E+09 | 744.62 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.647347E+09 | 590.25 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.589118E+09 | 607.99 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.621256E+09 | 602.83 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.626912E+09 | 826.78 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.624035E+09 | 917.17 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.738500E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.569302E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.666645E+09 | 1027.67 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.417160E+09 | 543.12 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.368990E+09 | 513.79 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.432539E+09 | 667.01 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.378958E+09 | 569.25 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.399198E+09 | 393.62 | 23-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.392610E+09 | 395.48 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.374784E+09 | 510.95 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.417560E+09 | 408.35 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.380691E+09 | 478.80 | 06-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.404553E+09 | 526.96 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.406739E+09 | 528.71 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.406467E+09 | 609.30 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.478025E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.368990E+09 | 393.62 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.432539E+09 | 667.01 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.658632E+09 | 849.64 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.578391E+09 | 876.65 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.670238E+09 | 1029.75 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.585864E+09 | 844.12 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.614855E+09 | 545.86 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.605040E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.577236E+09 | 633.36 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.644742E+09 | 594.31 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.589811E+09 | 610.91 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.628128E+09 | 754.20 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.643287E+09 | 954.43 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.646385E+09 | 980.97 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.744261E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.577236E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.670238E+09 | 1029.75 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.420065E+09 | 575.24 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.371397E+09 | 576.16 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.430319E+09 | 652.84 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.377589E+09 | 491.83 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.398456E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.392783E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.373500E+09 | 393.10 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.416280E+09 | 351.77 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.379990E+09 | 351.77 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.402212E+09 | 377.11 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.413358E+09 | 631.69 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.412185E+09 | 639.71 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.478813E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.371397E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.430319E+09 | 652.84 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639759E+09 | 749.42 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.569284E+09 | 829.14 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.666619E+09 | 1027.42 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.587066E+09 | 850.12 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.620372E+09 | 545.88 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.611313E+09 | 586.96 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.581758E+09 | 743.84 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.647322E+09 | 590.02 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.589096E+09 | 607.78 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.621246E+09 | 602.63 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.626905E+09 | 826.34 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.624023E+09 | 916.80 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.738476E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.569284E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.666619E+09 | 1027.42 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.417130E+09 | 542.75 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.368975E+09 | 513.36 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.432584E+09 | 666.86 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.378945E+09 | 568.90 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.399187E+09 | 393.51 | 23-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.392585E+09 | 395.37 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.374764E+09 | 510.50 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.417535E+09 | 408.26 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.380659E+09 | 478.34 | 06-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.404539E+09 | 526.69 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.406731E+09 | 528.46 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.406418E+09 | 609.04 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.478005E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.368975E+09 | 393.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.432584E+09 | 666.86 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274130E+10 | 2868.67 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.248656E+10 | 2868.67 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.295472E+10 | 2868.67 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.263917E+10 | 2868.67 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.284801E+10 | 2868.67 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.283424E+10 | 2868.67 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.265294E+10 | 2868.67 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.295472E+10 | 2868.67 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.263917E+10 | 2868.67 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.274130E+10 | 2868.67 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.270917E+10 | 2868.67 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.265294E+10 | 2868.67 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.328542E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.248656E+10 | 2868.67 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.295472E+10 | 2868.67 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.100587E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.100099E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.956821E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.116039E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.660438E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 613782.13 | 66789402.36 |
February | 0.136985E+10 | 0.579779E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5870056.31 | 67430537.04 |
March | 0.163685E+10 | 0.671216E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15356148.92 | 35643655.42 |
April | 0.145243E+10 | 0.586417E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35965038.18 | 14215692.25 |
May | 0.157338E+10 | 0.615151E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89347194.57 | 1459948.97 |
June | 0.156900E+10 | 0.605754E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112178E+09 | 103661.80 |
July | 0.145680E+10 | 0.577587E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158098E+09 | 0.00 |
August | 0.163685E+10 | 0.645153E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151137E+09 | 0.00 |
September | 0.145243E+10 | 0.590454E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106944E+09 | 218830.49 |
October | 0.150991E+10 | 0.629103E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60145237.46 | 2405983.74 |
November | 0.149516E+10 | 0.644693E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24642648.63 | 16706311.07 |
December | 0.145680E+10 | 0.648232E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3730057.60 | 48901663.27 |
Annual Sum or Average | 0.181194E+11 | 0.745398E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764028E+09 | 0.253876E+09 |
Minimum of Months | 0.136985E+10 | 0.577587E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 613782.13 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.671216E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158098E+09 | 67430537.04 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.420959E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 261781.05 | 45842693.34 |
February | 0.882782E+09 | 0.371987E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3601675.42 | 45159019.95 |
March | 0.105485E+10 | 0.430908E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10157556.11 | 23353957.51 |
April | 0.936002E+09 | 0.377893E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23583610.44 | 9155632.66 |
May | 0.101394E+10 | 0.398732E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58991866.88 | 1037227.33 |
June | 0.101113E+10 | 0.393067E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74540231.53 | 75904.36 |
July | 0.938820E+09 | 0.373749E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105159E+09 | 0.00 |
August | 0.105485E+10 | 0.416599E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100602E+09 | 0.00 |
September | 0.936002E+09 | 0.380264E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70615486.75 | 159847.49 |
October | 0.973041E+09 | 0.402569E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39564508.77 | 1741765.42 |
November | 0.963541E+09 | 0.413951E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16030634.85 | 11171543.40 |
December | 0.938820E+09 | 0.413020E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2462103.15 | 31177395.63 |
Annual Sum or Average | 0.116768E+11 | 0.479370E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505571E+09 | 0.168875E+09 |
Minimum of Months | 0.882782E+09 | 0.371987E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 261781.05 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.430908E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105159E+09 | 45842693.34 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.640116E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 331646.97 | 74519238.00 |
February | 0.136988E+10 | 0.569703E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5133414.39 | 72872289.09 |
March | 0.163688E+10 | 0.667275E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14734490.06 | 38413853.21 |
April | 0.145246E+10 | 0.587600E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35108862.40 | 14802221.45 |
May | 0.157341E+10 | 0.620847E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89672653.36 | 1386854.51 |
June | 0.156904E+10 | 0.611845E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113031E+09 | 75489.35 |
July | 0.145684E+10 | 0.582355E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158594E+09 | 0.00 |
August | 0.163688E+10 | 0.647834E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151203E+09 | 0.00 |
September | 0.145246E+10 | 0.589654E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106132E+09 | 225409.39 |
October | 0.150994E+10 | 0.622058E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58326853.42 | 2920670.62 |
November | 0.149520E+10 | 0.627209E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22247209.47 | 19421123.92 |
December | 0.145684E+10 | 0.624412E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3051814.94 | 54183891.89 |
Annual Sum or Average | 0.181198E+11 | 0.739091E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757566E+09 | 0.278821E+09 |
Minimum of Months | 0.136988E+10 | 0.569703E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 331646.97 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.667275E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158594E+09 | 74519238.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.417813E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 242551.12 | 52227316.10 |
February | 0.882782E+09 | 0.369581E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3459817.11 | 54759717.32 |
March | 0.105485E+10 | 0.433246E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9480415.21 | 32210018.51 |
April | 0.936002E+09 | 0.379620E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22373929.53 | 14398196.10 |
May | 0.101394E+10 | 0.399680E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58615579.54 | 1250901.40 |
June | 0.101113E+10 | 0.393078E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73604761.57 | 109722.54 |
July | 0.938820E+09 | 0.375326E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104098E+09 | 0.00 |
August | 0.105485E+10 | 0.418008E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99342593.97 | 0.00 |
September | 0.936002E+09 | 0.381058E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70376287.35 | 165085.15 |
October | 0.973041E+09 | 0.405014E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38646154.07 | 2273620.44 |
November | 0.963541E+09 | 0.407195E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14626746.17 | 15877304.61 |
December | 0.938820E+09 | 0.407261E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1978898.03 | 43664087.32 |
Annual Sum or Average | 0.116768E+11 | 0.478688E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496846E+09 | 0.216936E+09 |
Minimum of Months | 0.882782E+09 | 0.369581E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 242551.12 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.433246E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104098E+09 | 54759717.32 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.658713E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2589233.97 | 0.132409E+09 |
February | 0.136985E+10 | 0.578462E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15172103.19 | 0.136911E+09 |
March | 0.163685E+10 | 0.670290E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35247441.21 | 77892056.15 |
April | 0.145243E+10 | 0.585880E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85161871.25 | 37079485.34 |
May | 0.157338E+10 | 0.614864E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210981E+09 | 3480418.79 |
June | 0.156900E+10 | 0.605052E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265655E+09 | 178969.64 |
July | 0.145680E+10 | 0.577252E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373683E+09 | 0.00 |
August | 0.163685E+10 | 0.644765E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357654E+09 | 0.00 |
September | 0.145243E+10 | 0.589828E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255208E+09 | 412667.72 |
October | 0.150991E+10 | 0.628170E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144971E+09 | 5601734.40 |
November | 0.149516E+10 | 0.643321E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61486989.17 | 38093745.65 |
December | 0.145680E+10 | 0.646435E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10171528.53 | 99069055.57 |
Annual Sum or Average | 0.181194E+11 | 0.744303E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181798E+10 | 0.531129E+09 |
Minimum of Months | 0.136985E+10 | 0.577252E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2589233.97 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.670290E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373683E+09 | 0.136911E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.420084E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 621271.79 | 98540107.13 |
February | 0.649041E+09 | 0.371413E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7988365.79 | 99948787.85 |
March | 0.773965E+09 | 0.430335E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21733047.31 | 57232008.78 |
April | 0.688021E+09 | 0.377598E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52773882.37 | 27445893.25 |
May | 0.744847E+09 | 0.398474E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137039E+09 | 2743648.51 |
June | 0.742030E+09 | 0.392792E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174029E+09 | 170933.06 |
July | 0.690839E+09 | 0.373512E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245861E+09 | 0.00 |
August | 0.773965E+09 | 0.416304E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235207E+09 | 0.00 |
September | 0.688021E+09 | 0.379998E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165711E+09 | 341728.77 |
October | 0.715730E+09 | 0.402239E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91887385.13 | 4699310.99 |
November | 0.708685E+09 | 0.413375E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35563659.66 | 28817423.42 |
December | 0.690839E+09 | 0.412241E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5160189.62 | 72101357.86 |
Annual Sum or Average | 0.858171E+10 | 0.478837E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117357E+10 | 0.392041E+09 |
Minimum of Months | 0.649041E+09 | 0.371413E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 621271.79 | 0.00 |
Maximum of Months | 0.773965E+09 | 0.430335E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245861E+09 | 99948787.85 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.639770E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 703071.92 | 0.169414E+09 |
February | 0.136988E+10 | 0.569302E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11618507.63 | 0.164275E+09 |
March | 0.163688E+10 | 0.666645E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32866207.78 | 91515947.80 |
April | 0.145246E+10 | 0.587084E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81541753.11 | 40274215.36 |
May | 0.157341E+10 | 0.620401E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211069E+09 | 3578289.48 |
June | 0.156904E+10 | 0.611340E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267559E+09 | 151081.47 |
July | 0.145684E+10 | 0.581787E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374511E+09 | 0.00 |
August | 0.163688E+10 | 0.647347E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356248E+09 | 0.00 |
September | 0.145246E+10 | 0.589118E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249247E+09 | 537299.11 |
October | 0.150994E+10 | 0.621256E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134976E+09 | 8671010.30 |
November | 0.149520E+10 | 0.626912E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50064443.19 | 50409696.82 |
December | 0.145684E+10 | 0.624035E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6606218.04 | 0.126433E+09 |
Annual Sum or Average | 0.181198E+11 | 0.738500E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177701E+10 | 0.655260E+09 |
Minimum of Months | 0.136988E+10 | 0.569302E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 703071.92 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.666645E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374511E+09 | 0.169414E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.417160E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 908320.49 | 0.102564E+09 |
February | 0.882782E+09 | 0.368990E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8623573.89 | 0.105584E+09 |
March | 0.105485E+10 | 0.432539E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21906313.99 | 63509207.22 |
April | 0.936002E+09 | 0.378958E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52615436.59 | 31222721.24 |
May | 0.101394E+10 | 0.399198E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136311E+09 | 3255611.30 |
June | 0.101113E+10 | 0.392610E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172296E+09 | 222479.16 |
July | 0.938820E+09 | 0.374784E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244606E+09 | 0.00 |
August | 0.105485E+10 | 0.417560E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234140E+09 | 0.00 |
September | 0.936002E+09 | 0.380691E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164033E+09 | 426064.08 |
October | 0.973041E+09 | 0.404553E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90338858.95 | 5767087.37 |
November | 0.963541E+09 | 0.406739E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35119161.11 | 31778308.69 |
December | 0.938820E+09 | 0.406467E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5084045.40 | 78943263.82 |
Annual Sum or Average | 0.116768E+11 | 0.478025E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116598E+10 | 0.423273E+09 |
Minimum of Months | 0.882782E+09 | 0.368990E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 908320.49 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.432539E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244606E+09 | 0.105584E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.658632E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3268888.75 | 0.151086E+09 |
February | 0.136985E+10 | 0.578391E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17635702.30 | 0.161735E+09 |
March | 0.163685E+10 | 0.670238E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41963971.13 | 94981060.36 |
April | 0.145243E+10 | 0.585864E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101141E+09 | 46611158.10 |
May | 0.157338E+10 | 0.614855E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255380E+09 | 4617141.13 |
June | 0.156900E+10 | 0.605040E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322450E+09 | 297373.06 |
July | 0.145680E+10 | 0.577236E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455274E+09 | 0.00 |
August | 0.163685E+10 | 0.644742E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436423E+09 | 0.00 |
September | 0.145243E+10 | 0.589811E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309538E+09 | 574067.07 |
October | 0.150991E+10 | 0.628128E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174826E+09 | 7424528.36 |
November | 0.149516E+10 | 0.643287E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72629060.71 | 46157921.11 |
December | 0.145680E+10 | 0.646385E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12341531.33 | 0.115689E+09 |
Annual Sum or Average | 0.181194E+11 | 0.744261E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220287E+10 | 0.629173E+09 |
Minimum of Months | 0.136985E+10 | 0.577236E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3268888.75 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.670238E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455274E+09 | 0.161735E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.420065E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 848033.52 | 0.113252E+09 |
February | 0.882782E+09 | 0.371397E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9705955.83 | 0.118151E+09 |
March | 0.105485E+10 | 0.430319E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26816745.77 | 69562068.72 |
April | 0.936002E+09 | 0.377589E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64459574.18 | 34306388.92 |
May | 0.101394E+10 | 0.398456E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167457E+09 | 3588523.05 |
June | 0.101113E+10 | 0.392783E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212886E+09 | 266411.49 |
July | 0.938820E+09 | 0.373500E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301117E+09 | 0.00 |
August | 0.105485E+10 | 0.416280E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288702E+09 | 0.00 |
September | 0.936002E+09 | 0.379990E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202543E+09 | 463669.19 |
October | 0.973041E+09 | 0.402212E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112215E+09 | 6129215.30 |
November | 0.963541E+09 | 0.413358E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43346719.70 | 34909502.42 |
December | 0.938820E+09 | 0.412185E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6464938.65 | 84244894.87 |
Annual Sum or Average | 0.116768E+11 | 0.478813E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143656E+10 | 0.464873E+09 |
Minimum of Months | 0.882782E+09 | 0.371397E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 848033.52 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.430319E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301117E+09 | 0.118151E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.639759E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 808818.92 | 0.199149E+09 |
February | 0.136988E+10 | 0.569284E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13895317.22 | 0.196635E+09 |
March | 0.163688E+10 | 0.666619E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39510114.34 | 0.111955E+09 |
April | 0.145246E+10 | 0.587066E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97850241.14 | 50524174.97 |
May | 0.157341E+10 | 0.620372E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255464E+09 | 4729214.09 |
June | 0.156904E+10 | 0.611313E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324353E+09 | 254128.72 |
July | 0.145684E+10 | 0.581758E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456131E+09 | 0.00 |
August | 0.163688E+10 | 0.647322E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435047E+09 | 0.00 |
September | 0.145246E+10 | 0.589096E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303215E+09 | 738067.65 |
October | 0.150994E+10 | 0.621246E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163758E+09 | 11349240.12 |
November | 0.149520E+10 | 0.626905E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60014659.50 | 61361646.81 |
December | 0.145684E+10 | 0.624023E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7698971.76 | 0.150904E+09 |
Annual Sum or Average | 0.181198E+11 | 0.738476E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215775E+10 | 0.787599E+09 |
Minimum of Months | 0.136988E+10 | 0.569284E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 808818.92 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.666619E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456131E+09 | 0.199149E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.417130E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1097648.43 | 0.120770E+09 |
February | 0.882782E+09 | 0.368975E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10238062.20 | 0.126847E+09 |
March | 0.105485E+10 | 0.432584E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26377623.61 | 78012581.56 |
April | 0.936002E+09 | 0.378945E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63454030.64 | 39047435.53 |
May | 0.101394E+10 | 0.399187E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165817E+09 | 4222807.71 |
June | 0.101113E+10 | 0.392585E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210008E+09 | 345562.28 |
July | 0.938820E+09 | 0.374764E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299080E+09 | 0.00 |
August | 0.105485E+10 | 0.417535E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286604E+09 | 0.00 |
September | 0.936002E+09 | 0.380659E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199855E+09 | 572098.31 |
October | 0.973041E+09 | 0.404539E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109665E+09 | 7531403.22 |
November | 0.963541E+09 | 0.406731E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42146597.73 | 38813261.84 |
December | 0.938820E+09 | 0.406418E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5985696.52 | 94322176.77 |
Annual Sum or Average | 0.116768E+11 | 0.478005E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142033E+10 | 0.510484E+09 |
Minimum of Months | 0.882782E+09 | 0.368975E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1097648.43 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.432584E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299080E+09 | 0.126847E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.274130E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.248656E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.295472E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.263917E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.284801E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.283424E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.265294E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.295472E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.263917E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.274130E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.270917E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.265294E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.328542E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.248656E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.295472E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 809116.66 | 0.149317E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10324614.82 | 0.148288E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25554170.94 | 81878550.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64477249.98 | 35628921.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162630E+09 | 4492340.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202424E+09 | 550078.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289364E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274574E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191211E+09 | 726313.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104028E+09 | 8052519.06 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40538605.96 | 41440736.81 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5525389.77 | 0.111946E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137146E+10 | 0.582321E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 809116.66 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289364E+09 | 0.149317E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2396731.69 | 0.246713E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20245439.36 | 0.247780E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47096100.43 | 0.138631E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121023E+09 | 62734824.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311839E+09 | 6060452.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389138E+09 | 510530.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557273E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525323E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371129E+09 | 798667.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205542E+09 | 11058685.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79032657.63 | 69105054.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11556049.90 | 0.184889E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264159E+10 | 0.968281E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2396731.69 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557273E+09 | 0.247780E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1386377.07 | 0.257233E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18492888.71 | 0.266643E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46379260.64 | 0.154884E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113225E+09 | 67757243.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327618E+09 | 6423334.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425204E+09 | 521815.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607299E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581814E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403346E+09 | 855853.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220289E+09 | 11334667.09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78928772.44 | 67493632.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9281411.95 | 0.192003E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283326E+10 | 0.102515E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1386377.07 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607299E+09 | 0.266643E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10174.14 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10174.14 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10174.14 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10174.14 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10174.14 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10174.14 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10174.14 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10174.14 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10174.14 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10174.14 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10174.14 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10174.14 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 854.72 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.22 | 29-JAN-12:00 | 179.88 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 880.50 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 131.29 | 05-FEB-15:00 | 149.67 | 10-FEB-24:00 |
March | 2010.79 | 01-MAR-10:09 | 1031.32 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.32 | 26-MAR-14:00 | 127.55 | 06-MAR-05:53 |
April | 2010.79 | 03-APR-09:09 | 848.40 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.42 | 30-APR-13:04 | 94.71 | 05-APR-01:00 |
May | 2010.79 | 01-MAY-09:09 | 545.86 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 911.15 | 21-MAY-12:51 | 31.17 | 01-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.39 | 11-JUN-13:04 | 21.99 | 07-JUN-04:30 |
July | 2010.79 | 03-JUL-09:09 | 637.35 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.29 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.79 | 01-AUG-09:09 | 600.46 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.48 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 616.14 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.12 | 03-SEP-16:00 | 23.42 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 761.09 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.16 | 09-OCT-15:04 | 55.05 | 20-OCT-04:20 |
November | 2010.79 | 01-NOV-09:09 | 957.43 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.39 | 19-NOV-14:00 | 78.51 | 22-NOV-05:53 |
December | 2010.79 | 01-DEC-10:09 | 983.36 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.36 | 10-DEC-12:10 | 115.05 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 38.22 | 0.00 | |||||
Maximum of Months | 2010.79 | 1031.32 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 911.15 | 179.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 579.47 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.28 | 29-JAN-12:00 | 119.81 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 580.65 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.75 | 05-FEB-15:16 | 98.31 | 13-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 654.92 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.87 | 02-MAR-04:00 | 81.06 | 06-MAR-05:53 |
April | 1295.83 | 03-APR-09:09 | 496.80 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.69 | 30-APR-13:04 | 60.96 | 05-APR-01:00 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 602.64 | 21-MAY-12:51 | 20.74 | 01-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.42 | 11-JUN-13:04 | 14.80 | 07-JUN-04:30 |
July | 1295.83 | 03-JUL-09:09 | 395.91 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.52 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.32 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 351.77 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.05 | 03-SEP-15:43 | 16.03 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 381.17 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.05 | 09-OCT-15:04 | 37.39 | 20-OCT-04:20 |
November | 1295.83 | 01-NOV-09:09 | 634.58 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.01 | 19-NOV-13:53 | 50.44 | 22-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 642.41 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.22 | 10-DEC-12:50 | 71.62 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 13.28 | 0.00 | |||||
Maximum of Months | 1295.83 | 654.92 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 602.64 | 119.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 754.37 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 29-JAN-12:00 | 188.52 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 833.30 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 119.08 | 05-FEB-15:00 | 160.86 | 10-FEB-23:30 |
March | 2010.83 | 01-MAR-10:09 | 1029.00 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.79 | 26-MAR-13:55 | 133.35 | 17-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 854.35 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.52 | 30-APR-13:04 | 96.24 | 05-APR-01:00 |
May | 2010.83 | 01-MAY-09:09 | 582.86 | 23-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 910.16 | 21-MAY-12:51 | 30.73 | 01-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 593.66 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.64 | 11-JUN-13:04 | 20.22 | 07-JUN-04:30 |
July | 2010.83 | 03-JUL-09:09 | 750.07 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.29 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.83 | 01-AUG-09:09 | 596.39 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.48 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 613.16 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.12 | 03-SEP-16:00 | 23.50 | 25-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 608.81 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.42 | 09-OCT-15:04 | 58.31 | 20-OCT-04:20 |
November | 2010.83 | 01-NOV-09:09 | 830.74 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.54 | 19-NOV-14:00 | 78.84 | 22-NOV-05:53 |
December | 2010.83 | 01-DEC-10:09 | 919.89 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.85 | 10-DEC-12:37 | 112.13 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 582.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 0.00 | |||||
Maximum of Months | 2010.83 | 1029.00 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 910.16 | 188.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 548.11 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 | 29-JAN-12:00 | 137.82 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 519.61 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.52 | 05-FEB-14:34 | 122.14 | 10-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 668.86 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.79 | 26-MAR-13:55 | 111.52 | 17-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 573.64 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.52 | 30-APR-13:04 | 83.69 | 05-APR-01:00 |
May | 1295.83 | 01-MAY-09:09 | 396.88 | 23-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 603.59 | 21-MAY-12:51 | 24.67 | 01-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 398.63 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.18 | 11-JUN-13:04 | 17.51 | 07-JUN-04:30 |
July | 1295.83 | 03-JUL-09:09 | 516.87 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.52 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 410.79 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.31 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 485.89 | 06-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.74 | 03-SEP-16:00 | 16.38 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 531.73 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.38 | 09-OCT-15:04 | 42.05 | 20-OCT-04:20 |
November | 1295.83 | 01-NOV-09:09 | 533.33 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.36 | 19-NOV-13:53 | 61.70 | 22-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 612.61 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 | 10-DEC-12:37 | 94.97 | 16-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 396.88 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 | 0.00 | |||||
Maximum of Months | 1295.83 | 668.86 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 603.59 | 137.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 850.09 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 135.11 | 29-JAN-12:00 | 350.21 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 877.19 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.94 | 05-FEB-15:00 | 297.37 | 13-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1030.00 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 274.75 | 26-MAR-14:00 | 290.88 | 05-MAR-15:03 |
April | 2010.79 | 03-APR-09:09 | 844.72 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 375.16 | 30-APR-12:53 | 210.69 | 05-APR-00:55 |
May | 2010.79 | 01-MAY-09:09 | 545.86 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2174.91 | 21-MAY-13:00 | 62.08 | 02-MAY-02:55 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 533.86 | 11-JUN-13:04 | 47.08 | 07-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 633.52 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.45 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.79 | 01-AUG-09:09 | 594.54 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 761.71 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 611.10 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 581.71 | 04-SEP-16:54 | 37.32 | 25-SEP-04:50 |
October | 2010.79 | 02-OCT-09:09 | 754.73 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 504.02 | 09-OCT-15:04 | 114.90 | 20-OCT-04:03 |
November | 2010.79 | 01-NOV-09:09 | 954.76 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.52 | 19-NOV-14:00 | 166.46 | 22-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 981.28 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 146.46 | 10-DEC-11:50 | 228.67 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 135.11 | 0.00 | |||||
Maximum of Months | 2010.79 | 1030.00 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2174.91 | 350.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 575.48 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.98 | 29-JAN-12:00 | 246.02 | 18-JAN-04:00 |
February | 1239.33 | 01-FEB-08:09 | 576.48 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 196.49 | 05-FEB-15:00 | 208.41 | 10-FEB-23:20 |
March | 1239.33 | 01-MAR-08:09 | 653.00 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 178.92 | 02-MAR-04:06 | 202.10 | 05-MAR-15:00 |
April | 1239.33 | 03-APR-07:10 | 492.27 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.11 | 30-APR-12:52 | 146.04 | 05-APR-00:55 |
May | 1239.33 | 01-MAY-07:10 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.94 | 21-MAY-13:00 | 44.57 | 02-MAY-02:55 |
June | 1239.33 | 01-JUN-07:10 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.44 | 11-JUN-13:04 | 33.06 | 07-JUN-05:00 |
July | 1239.33 | 03-JUL-07:10 | 393.23 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 543.63 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1239.33 | 01-AUG-07:10 | 351.77 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 507.80 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1239.33 | 01-SEP-07:10 | 351.77 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.09 | 03-SEP-16:00 | 26.48 | 25-SEP-04:50 |
October | 1239.33 | 02-OCT-07:10 | 377.22 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.80 | 09-OCT-15:04 | 81.01 | 20-OCT-04:03 |
November | 1239.33 | 01-NOV-07:10 | 631.87 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.00 | 05-NOV-14:45 | 112.11 | 22-NOV-06:00 |
December | 1239.33 | 01-DEC-08:09 | 639.90 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.82 | 10-DEC-12:30 | 151.73 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 36.98 | 0.00 | |||||
Maximum of Months | 1239.33 | 653.00 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.94 | 246.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 750.12 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 23-JAN-13:00 | 402.03 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 829.74 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 277.03 | 05-FEB-14:45 | 346.13 | 10-FEB-23:10 |
March | 2010.83 | 01-MAR-10:09 | 1027.67 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 265.54 | 02-MAR-04:06 | 342.79 | 05-MAR-15:00 |
April | 2010.83 | 03-APR-09:09 | 850.71 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 375.16 | 30-APR-12:52 | 218.21 | 05-APR-00:55 |
May | 2010.83 | 01-MAY-09:09 | 545.88 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2174.91 | 21-MAY-13:00 | 63.60 | 02-MAY-02:55 |
June | 2010.83 | 01-JUN-09:09 | 587.20 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 535.62 | 11-JUN-13:04 | 46.07 | 07-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 744.62 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.45 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.83 | 01-AUG-09:09 | 590.25 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 761.71 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 607.99 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 583.37 | 04-SEP-16:54 | 40.45 | 25-SEP-04:50 |
October | 2010.83 | 02-OCT-09:09 | 602.83 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 493.15 | 09-OCT-15:04 | 131.62 | 20-OCT-04:03 |
November | 2010.83 | 01-NOV-09:09 | 826.78 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.38 | 19-NOV-13:55 | 176.65 | 22-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 917.17 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 103.34 | 10-DEC-12:25 | 232.20 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 0.00 | |||||
Maximum of Months | 2010.83 | 1027.67 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2174.91 | 402.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 543.12 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.01 | 29-JAN-12:00 | 256.53 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 513.79 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 186.45 | 05-FEB-15:00 | 225.59 | 10-FEB-23:10 |
March | 1295.83 | 01-MAR-10:09 | 667.01 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.04 | 02-MAR-04:06 | 229.58 | 05-MAR-15:00 |
April | 1295.83 | 03-APR-09:09 | 569.25 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.11 | 30-APR-12:52 | 158.22 | 05-APR-00:55 |
May | 1295.83 | 01-MAY-09:09 | 393.62 | 23-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.94 | 21-MAY-13:00 | 49.30 | 02-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 395.48 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.48 | 11-JUN-13:04 | 36.96 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 510.95 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 543.62 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 408.35 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 507.80 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 478.80 | 06-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 388.91 | 04-SEP-16:54 | 28.51 | 25-SEP-04:50 |
October | 1295.83 | 02-OCT-09:09 | 526.96 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.30 | 09-OCT-15:06 | 89.97 | 20-OCT-04:03 |
November | 1295.83 | 01-NOV-09:09 | 528.71 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.88 | 19-NOV-13:55 | 118.75 | 22-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 609.30 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.63 | 10-DEC-12:00 | 159.32 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 393.62 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 71.01 | 0.00 | |||||
Maximum of Months | 1295.83 | 667.01 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.94 | 256.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 849.64 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 164.09 | 29-JAN-11:35 | 400.46 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 876.65 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 390.06 | 05-FEB-15:00 | 347.42 | 10-FEB-23:10 |
March | 2010.79 | 01-MAR-10:09 | 1029.75 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 327.59 | 26-MAR-14:00 | 357.34 | 05-MAR-15:03 |
April | 2010.79 | 03-APR-09:09 | 844.12 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 477.09 | 30-APR-12:55 | 253.70 | 05-APR-00:55 |
May | 2010.79 | 01-MAY-09:09 | 545.86 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2582.62 | 21-MAY-12:51 | 76.66 | 02-MAY-02:55 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 659.51 | 11-JUN-13:04 | 60.91 | 07-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 633.36 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.92 | 30-JUL-14:40 | 0.00 | 01-JUL-00:05 |
August | 2010.79 | 01-AUG-09:09 | 594.31 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 937.89 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 610.91 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 720.18 | 04-SEP-16:54 | 43.43 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 754.20 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 618.70 | 09-OCT-15:14 | 143.91 | 20-OCT-04:03 |
November | 2010.79 | 01-NOV-09:09 | 954.43 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 376.36 | 19-NOV-14:00 | 196.59 | 22-NOV-05:53 |
December | 2010.79 | 01-DEC-10:09 | 980.97 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 181.76 | 10-DEC-12:10 | 263.20 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 164.09 | 0.00 | |||||
Maximum of Months | 2010.79 | 1029.75 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2582.62 | 400.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 575.24 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.26 | 29-JAN-12:00 | 282.14 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 576.16 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 246.51 | 05-FEB-15:16 | 244.16 | 10-FEB-23:10 |
March | 1295.83 | 01-MAR-10:09 | 652.84 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 219.83 | 26-MAR-13:58 | 248.09 | 05-MAR-15:03 |
April | 1295.83 | 03-APR-09:09 | 491.83 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.64 | 30-APR-12:53 | 175.53 | 05-APR-00:55 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1703.04 | 21-MAY-12:51 | 54.69 | 02-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 442.01 | 11-JUN-13:04 | 42.52 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 393.10 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 669.94 | 30-JUL-14:40 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 625.25 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 351.77 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 477.94 | 04-SEP-16:54 | 28.97 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 377.11 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 413.91 | 09-OCT-15:14 | 100.76 | 20-OCT-04:03 |
November | 1295.83 | 01-NOV-09:09 | 631.69 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.53 | 05-NOV-14:55 | 132.41 | 22-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 639.71 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 103.88 | 10-DEC-12:50 | 174.28 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 38.26 | 0.00 | |||||
Maximum of Months | 1295.83 | 652.84 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1703.04 | 282.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 749.42 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 | 23-JAN-13:00 | 466.12 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 829.14 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 332.48 | 05-FEB-15:00 | 410.09 | 10-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1027.42 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 324.61 | 26-MAR-13:55 | 423.11 | 05-MAR-15:00 |
April | 2010.83 | 03-APR-09:09 | 850.12 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 476.75 | 30-APR-12:53 | 262.62 | 05-APR-00:55 |
May | 2010.83 | 01-MAY-09:09 | 545.88 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2576.95 | 21-MAY-12:51 | 78.45 | 02-MAY-02:55 |
June | 2010.83 | 01-JUN-09:09 | 586.96 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 661.57 | 11-JUN-13:04 | 59.66 | 07-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 743.84 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.92 | 30-JUL-14:40 | 0.00 | 01-JUL-00:05 |
August | 2010.83 | 01-AUG-09:09 | 590.02 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 937.89 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 607.78 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 722.33 | 04-SEP-16:54 | 44.17 | 25-SEP-04:40 |
October | 2010.83 | 02-OCT-09:09 | 602.63 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 601.40 | 09-OCT-15:00 | 163.70 | 20-OCT-04:03 |
November | 2010.83 | 01-NOV-09:09 | 826.34 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.19 | 05-NOV-14:55 | 209.55 | 22-NOV-05:53 |
December | 2010.83 | 01-DEC-10:09 | 916.80 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.04 | 10-DEC-12:37 | 268.04 | 17-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 | 0.00 | |||||
Maximum of Months | 2010.83 | 1027.42 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2576.95 | 466.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 542.75 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.24 | 29-JAN-11:35 | 298.80 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 513.36 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 246.17 | 05-FEB-15:16 | 267.76 | 10-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 666.86 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 222.74 | 02-MAR-04:06 | 284.85 | 05-MAR-15:00 |
April | 1295.83 | 03-APR-09:09 | 568.90 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.41 | 30-APR-12:53 | 190.57 | 05-APR-00:55 |
May | 1295.83 | 01-MAY-09:09 | 393.51 | 23-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1708.58 | 21-MAY-12:51 | 60.46 | 02-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 395.37 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 440.57 | 11-JUN-13:04 | 47.24 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 510.50 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 669.94 | 30-JUL-14:40 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 408.26 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 625.25 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 478.34 | 06-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 479.87 | 04-SEP-16:54 | 31.51 | 24-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 526.69 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 409.68 | 09-OCT-15:14 | 111.95 | 20-OCT-04:03 |
November | 1295.83 | 01-NOV-09:09 | 528.46 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.61 | 19-NOV-13:46 | 141.73 | 22-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 609.04 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.64 | 10-DEC-12:10 | 185.83 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 393.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 82.24 | 0.00 | |||||
Maximum of Months | 1295.83 | 666.86 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1708.58 | 298.80 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2868.67 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2868.67 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2868.67 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2868.67 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2868.67 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2868.67 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2868.67 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2868.67 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2868.67 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2868.67 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2868.67 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2868.67 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.39 | 29-JAN-11:53 | 392.09 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.52 | 05-FEB-15:00 | 322.55 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.95 | 26-MAR-14:00 | 282.19 | 06-MAR-05:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.08 | 30-APR-12:52 | 201.72 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1779.57 | 21-MAY-12:51 | 66.88 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.49 | 11-JUN-12:52 | 48.71 | 07-JUN-04:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.63 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.25 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.17 | 03-SEP-16:00 | 51.51 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.65 | 09-OCT-14:51 | 111.55 | 20-OCT-04:22 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.56 | 19-NOV-14:00 | 176.03 | 22-NOV-05:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.70 | 10-DEC-13:00 | 242.28 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.39 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1779.57 | 392.09 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.09 | 29-JAN-12:00 | 643.61 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.06 | 05-FEB-15:00 | 543.00 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.37 | 26-MAR-14:00 | 489.29 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 610.94 | 30-APR-13:00 | 359.87 | 05-APR-00:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3400.72 | 21-MAY-13:00 | 100.53 | 01-MAY-04:52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 822.30 | 11-JUN-12:52 | 79.08 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1254.16 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1167.48 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 889.32 | 03-SEP-16:00 | 71.38 | 25-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 757.46 | 09-OCT-14:51 | 180.56 | 20-OCT-04:12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.69 | 19-NOV-14:00 | 304.01 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.75 | 10-DEC-12:50 | 413.34 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.09 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3400.72 | 643.61 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.37 | 29-JAN-11:43 | 648.92 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.12 | 05-FEB-15:00 | 530.58 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.79 | 26-MAR-14:00 | 586.64 | 05-MAR-15:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.45 | 30-APR-13:00 | 373.64 | 05-APR-00:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3254.59 | 21-MAY-12:51 | 115.87 | 01-MAY-04:52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 786.04 | 11-JUN-12:52 | 79.12 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1282.06 | 30-JUL-14:10 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1163.65 | 13-AUG-14:10 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 876.81 | 04-SEP-14:00 | 80.16 | 25-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 757.07 | 09-OCT-15:00 | 209.39 | 20-OCT-04:13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.34 | 19-NOV-14:00 | 293.24 | 22-NOV-05:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.29 | 10-DEC-12:13 | 411.88 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.37 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3254.59 | 648.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 106630.97 | 01-JAN-18:32 | 0.00 | 2826.07 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 103760.10 | 10-FEB-05:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 100021.02 | 06-MAR-05:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 90420.03 | 05-APR-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95798.58 | 01-MAY-05:11 | 12566.58 | 7912.99 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85776.03 | 22-JUN-10:05 | 34109.28 | 20348.28 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 1130.43 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 01-AUG-00:03 | 0.00 | 1695.64 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 1130.43 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 111092.01 | 30-OCT-05:41 | 16157.03 | 10173.84 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 100242.58 | 13-NOV-05:41 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 104036.33 | 12-DEC-22:17 | 5385.68 | 6782.56 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 0.00 | 0.00 | 1130.43 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 111092.01 | 34109.28 | 20348.28 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 96830.23 | 02-JAN-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 97483.01 | 09-FEB-05:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94156.73 | 15-MAR-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91809.77 | 24-APR-04:23 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95608.78 | 01-MAY-04:23 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 95270.81 | 05-JUN-03:03 | 0.00 | 3045.61 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 96983.02 | 05-JUL-03:03 | 0.00 | 3045.61 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 97107.77 | 28-AUG-03:03 | 0.00 | 3045.61 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92486.35 | 11-SEP-04:25 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97267.49 | 10-OCT-03:04 | 0.00 | 2538.01 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95931.74 | 30-NOV-05:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 94418.48 | 18-DEC-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91809.77 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97483.01 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 80230.68 | 02-JAN-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82879.74 | 21-FEB-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 83344.18 | 06-MAR-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82880.90 | 13-APR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75041.23 | 04-MAY-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 65555.95 | 12-JUN-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 67055.50 | 05-JUL-05:03 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71737.41 | 07-AUG-05:01 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74236.20 | 05-SEP-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87519.35 | 20-OCT-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 83086.62 | 27-NOV-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82028.53 | 07-DEC-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 65555.95 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87519.35 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 78609.29 | 30-JAN-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82216.34 | 07-FEB-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82877.21 | 30-MAR-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82549.32 | 21-APR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78441.14 | 03-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81389.91 | 12-JUN-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80499.98 | 05-JUL-05:03 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 83878.84 | 07-AUG-05:04 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81932.55 | 05-SEP-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80372.08 | 21-OCT-04:12 | 0.00 | 2538.01 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 83018.49 | 13-NOV-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82846.36 | 11-DEC-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 78441.14 | 0.00 | 2538.01 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83878.84 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14636.59 | 30-JAN-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 |
February | 16912.73 | 07-FEB-05:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.59 |
March | 16698.03 | 15-MAR-04:11 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 |
April | 20655.61 | 30-APR-11:02 | 506.08 | 151.62 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 58.18 | 0.00 |
May | 22843.20 | 21-MAY-15:43 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 234.03 | 0.00 |
June | 21681.46 | 11-JUN-16:22 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.21 | 0.00 |
July | 22141.91 | 30-JUL-14:22 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.95 | 0.00 |
August | 21369.34 | 13-AUG-15:02 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.63 | 0.00 |
September | 21716.10 | 10-SEP-14:23 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 149.96 | 0.00 |
October | 22012.58 | 09-OCT-14:23 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 193.60 | 0.00 |
November | 16677.38 | 30-NOV-05:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 |
December | 16040.66 | 12-DEC-05:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14636.59 | 0.00 | 151.62 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22843.20 | 1012.16 | 472.30 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 331.95 | 52.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9986.13 | 30-JAN-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 |
February | 13858.04 | 09-FEB-05:11 | 0.00 | 304.37 | 3363.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 |
March | 11578.29 | 28-MAR-05:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 | 0.00 |
April | 18359.28 | 30-APR-11:02 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 35.12 | 0.00 |
May | 20217.79 | 21-MAY-09:41 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 105.43 | 0.00 |
June | 18432.13 | 11-JUN-10:22 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 87.71 | 0.00 |
July | 19249.50 | 30-JUL-09:42 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 98.50 | 0.00 |
August | 18401.17 | 13-AUG-10:22 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 165.91 | 0.00 |
September | 18718.32 | 10-SEP-09:42 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 46.63 | 0.00 |
October | 18426.55 | 01-OCT-09:42 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.52 | 0.00 |
November | 14541.39 | 05-NOV-10:23 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 21.26 | 0.00 |
December | 8494.54 | 12-DEC-06:03 | 521.82 | 173.92 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8494.54 | 0.00 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20217.79 | 652.28 | 304.37 | 3363.28 | 0.00 | 0.00 | 0.00 | 0.00 | 165.91 | 19.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19525.65 | 30-JAN-05:12 | 0.00 | 404.83 | 4473.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.39 |
February | 25493.11 | 05-FEB-13:52 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 86.18 | 0.00 |
March | 21055.51 | 26-MAR-14:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 99.53 | 0.00 |
April | 23670.27 | 30-APR-11:02 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 56.22 | 0.00 |
May | 24963.93 | 21-MAY-12:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 526.01 | 0.00 |
June | 23946.47 | 11-JUN-15:02 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 215.06 | 0.00 |
July | 24818.89 | 30-JUL-13:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 311.88 | 0.00 |
August | 23997.50 | 13-AUG-15:02 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 283.10 | 0.00 |
September | 26442.91 | 10-SEP-14:23 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 145.10 | 0.00 |
October | 27429.85 | 29-OCT-13:03 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 52.18 | 0.00 |
November | 25666.51 | 11-NOV-13:02 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 35.12 | 0.00 |
December | 26018.24 | 03-DEC-12:42 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19525.65 | 0.00 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27429.85 | 708.53 | 404.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 526.01 | 19.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18363.92 | 30-JAN-05:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 |
February | 23795.68 | 05-FEB-15:12 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 73.28 | 0.00 |
March | 20684.10 | 13-MAR-04:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 |
April | 23999.69 | 30-APR-16:22 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 0.00 |
May | 25795.33 | 21-MAY-15:41 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 125.78 | 0.00 |
June | 24344.40 | 11-JUN-16:22 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 121.18 | 0.00 |
July | 24845.57 | 02-JUL-15:42 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 124.32 | 0.00 |
August | 24482.70 | 13-AUG-15:02 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 180.66 | 0.00 |
September | 24171.44 | 03-SEP-15:42 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 154.99 | 0.00 |
October | 23616.10 | 01-OCT-14:21 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 65.88 | 0.00 |
November | 24149.47 | 19-NOV-14:52 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 41.49 | 0.00 |
December | 23995.20 | 03-DEC-14:42 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18363.92 | 0.00 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25795.33 | 521.82 | 260.89 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 180.66 | 18.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5044.11 | 23-JAN-14:10 | 4021.58 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.52 | 0.00 |
February | 10884.07 | 09-FEB-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 |
March | 15153.80 | 27-MAR-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.34 |
April | 15784.45 | 23-APR-15:31 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 254.40 | 0.00 |
May | 22006.29 | 29-MAY-16:51 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 213.45 | 0.00 |
June | 21343.92 | 04-JUN-16:01 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 279.85 | 0.00 |
July | 21770.07 | 04-JUL-15:31 | 910.95 | 272.92 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 431.23 | 0.00 |
August | 21810.98 | 06-AUG-15:01 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 471.76 | 0.00 |
September | 23086.16 | 04-SEP-16:11 | 910.95 | 272.92 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 467.74 | 0.00 |
October | 21663.30 | 09-OCT-14:21 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 423.38 | 0.00 |
November | 14039.89 | 20-NOV-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 | 0.00 |
December | 10167.78 | 11-DEC-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5044.11 | 0.00 | 212.27 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23086.16 | 4021.58 | 1091.73 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 471.76 | 25.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6389.60 | 30-JAN-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 |
February | 9936.34 | 06-FEB-05:11 | 0.00 | 304.37 | 3363.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.07 |
March | 13664.90 | 27-MAR-04:12 | 0.00 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.76 |
April | 19664.42 | 23-APR-10:12 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 71.03 | 0.00 |
May | 20226.63 | 07-MAY-09:52 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 84.55 | 0.00 |
June | 20093.54 | 04-JUN-10:02 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 141.09 | 0.00 |
July | 20084.46 | 04-JUL-11:32 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 98.54 | 0.00 |
August | 19342.87 | 06-AUG-15:01 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 315.58 | 0.00 |
September | 20924.39 | 04-SEP-10:11 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 203.92 | 0.00 |
October | 19554.27 | 09-OCT-14:21 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 276.04 | 0.00 |
November | 16661.95 | 05-NOV-14:42 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 166.39 | 0.00 |
December | 7845.11 | 11-DEC-06:03 | 521.82 | 173.92 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6389.60 | 0.00 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20924.39 | 652.28 | 304.37 | 3363.28 | 0.00 | 0.00 | 0.00 | 0.00 | 315.58 | 72.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18330.11 | 30-JAN-06:02 | 1012.19 | 337.36 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 |
February | 24550.05 | 05-FEB-12:43 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 185.38 | 0.00 |
March | 24384.76 | 26-MAR-12:53 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 116.74 | 0.00 |
April | 22739.86 | 23-APR-15:31 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 253.08 | 0.00 |
May | 24319.29 | 07-MAY-15:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 354.11 | 0.00 |
June | 23618.57 | 04-JUN-16:01 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 285.71 | 0.00 |
July | 24359.35 | 30-JUL-14:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 784.35 | 0.00 |
August | 24529.74 | 06-AUG-15:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 470.90 | 0.00 |
September | 27185.99 | 04-SEP-14:11 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 464.21 | 0.00 |
October | 26833.37 | 09-OCT-13:41 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 321.98 | 0.00 |
November | 26263.75 | 05-NOV-12:02 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 100.94 | 0.00 |
December | 24532.39 | 03-DEC-15:02 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18330.11 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27185.99 | 1012.19 | 337.36 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 784.35 | 16.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10008.88 | 30-JAN-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 |
February | 15429.57 | 05-FEB-16:03 | 260.91 | 78.17 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 156.79 | 0.00 |
March | 16925.93 | 26-MAR-17:33 | 0.00 | 78.17 | 1441.39 | 0.00 | 0.00 | 0.00 | 0.00 | 83.71 | 0.00 |
April | 21314.53 | 23-APR-16:11 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 140.51 | 0.00 |
May | 23354.18 | 29-MAY-16:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 123.38 | 0.00 |
June | 21882.64 | 04-JUN-17:21 | 0.00 | 136.80 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 143.15 | 0.00 |
July | 22249.09 | 04-JUL-15:31 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.36 | 0.00 |
August | 22488.44 | 06-AUG-16:21 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 257.30 | 0.00 |
September | 24659.76 | 04-SEP-16:11 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.50 | 0.00 |
October | 22727.84 | 09-OCT-16:21 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 255.01 | 0.00 |
November | 21548.01 | 05-NOV-15:22 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 137.37 | 0.00 |
December | 10531.68 | 11-DEC-06:03 | 521.82 | 173.92 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10008.88 | 0.00 | 78.17 | 1441.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24659.76 | 652.28 | 217.40 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.50 | 18.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5257.59 | 23-JAN-14:10 | 4021.58 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.47 | 0.00 |
February | 9976.41 | 06-FEB-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.59 |
March | 17696.01 | 02-MAR-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 69.25 | 0.00 |
April | 21279.82 | 30-APR-13:31 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 395.88 | 0.00 |
May | 25632.05 | 21-MAY-15:41 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 580.52 | 0.00 |
June | 25591.50 | 04-JUN-16:11 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 298.84 | 0.00 |
July | 26107.81 | 04-JUL-15:21 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 473.81 | 0.00 |
August | 24605.37 | 06-AUG-15:01 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 571.67 | 0.00 |
September | 25728.01 | 03-SEP-14:51 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 564.70 | 0.00 |
October | 19722.45 | 09-OCT-15:12 | 506.08 | 151.62 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 591.54 | 0.00 |
November | 19722.40 | 05-NOV-14:52 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 307.83 | 0.00 |
December | 8708.35 | 11-DEC-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5257.59 | 506.08 | 151.62 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26107.81 | 4021.58 | 1091.73 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 591.54 | 33.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6347.57 | 30-JAN-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 |
February | 11861.39 | 05-FEB-15:12 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 214.55 | 0.00 |
March | 14729.08 | 27-MAR-04:12 | 0.00 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.15 |
April | 20188.28 | 30-APR-10:52 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 100.14 | 0.00 |
May | 21684.88 | 21-MAY-10:21 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 337.49 | 0.00 |
June | 21164.65 | 04-JUN-15:31 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 206.59 | 0.00 |
July | 21703.40 | 04-JUL-15:21 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 312.65 | 0.00 |
August | 20296.36 | 06-AUG-15:01 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 381.43 | 0.00 |
September | 21858.93 | 04-SEP-10:11 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 245.14 | 0.00 |
October | 18858.28 | 09-OCT-09:13 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 28.37 | 0.00 |
November | 18993.43 | 05-NOV-14:52 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 203.11 | 0.00 |
December | 6898.96 | 11-DEC-06:03 | 521.82 | 173.92 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6347.57 | 0.00 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21858.93 | 652.28 | 260.89 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 381.43 | 22.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19040.68 | 30-JAN-06:02 | 1012.19 | 337.36 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.28 |
February | 27735.43 | 05-FEB-13:52 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 234.18 | 0.00 |
March | 23873.79 | 26-MAR-14:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 277.60 | 0.00 |
April | 25965.35 | 30-APR-11:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 179.77 | 0.00 |
May | 28243.61 | 21-MAY-15:41 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 583.98 | 0.00 |
June | 27812.20 | 04-JUN-15:31 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 320.77 | 0.00 |
July | 28528.39 | 04-JUL-15:21 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 482.02 | 0.00 |
August | 27247.19 | 06-AUG-15:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 570.76 | 0.00 |
September | 29631.05 | 03-SEP-14:51 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 527.41 | 0.00 |
October | 27035.20 | 09-OCT-13:52 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 472.38 | 0.00 |
November | 28673.75 | 05-NOV-12:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 139.57 | 0.00 |
December | 27769.67 | 03-DEC-12:52 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19040.68 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29631.05 | 1012.19 | 337.36 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 583.98 | 15.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10275.02 | 30-JAN-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.11 |
February | 18787.63 | 05-FEB-15:12 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 211.76 | 0.00 |
March | 18163.18 | 27-MAR-04:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 |
April | 22598.74 | 30-APR-16:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 114.91 | 0.00 |
May | 26097.04 | 21-MAY-15:41 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 342.39 | 0.00 |
June | 25778.78 | 04-JUN-16:11 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 178.29 | 0.00 |
July | 26127.89 | 04-JUL-15:21 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 292.59 | 0.00 |
August | 24438.56 | 06-AUG-15:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 323.06 | 0.00 |
September | 25879.14 | 03-SEP-14:51 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 343.10 | 0.00 |
October | 22467.01 | 09-OCT-15:52 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 380.42 | 0.00 |
November | 23218.07 | 05-NOV-15:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 158.15 | 0.00 |
December | 10078.42 | 03-DEC-15:32 | 260.91 | 78.17 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10078.42 | 0.00 | 78.17 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26127.89 | 652.28 | 260.89 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 380.42 | 21.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9114.20 | 30-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 |
February | 11165.80 | 07-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.52 |
March | 12274.91 | 29-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 |
April | 15299.95 | 27-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
May | 22213.93 | 30-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 | 0.00 |
June | 21468.77 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 | 0.00 |
July | 25301.04 | 24-JUL-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 | 0.00 |
August | 25300.79 | 07-AUG-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 | 0.00 |
September | 24737.10 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.30 | 0.00 |
October | 23587.63 | 10-OCT-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 | 0.00 |
November | 16558.02 | 13-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 |
December | 10959.71 | 04-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9114.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25301.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 | 25.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4135.29 | 30-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.57 |
February | 6200.84 | 06-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.10 | 0.00 |
March | 9217.76 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.14 | 0.00 |
April | 10222.12 | 24-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 |
May | 14757.77 | 30-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 | 0.00 |
June | 13762.49 | 05-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.38 | 0.00 |
July | 17653.08 | 17-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.57 | 0.00 |
August | 21220.42 | 07-AUG-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.92 | 0.00 |
September | 19942.13 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.54 | 0.00 |
October | 17119.28 | 10-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 | 0.00 |
November | 10062.27 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.70 |
December | 6576.16 | 11-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4135.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21220.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.14 | 52.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7972.90 | 23-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.75 | 0.00 |
February | 13014.77 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.91 | 0.00 |
March | 18576.55 | 27-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.95 | 0.00 |
April | 20527.21 | 28-APR-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.27 | 0.00 |
May | 23368.54 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.63 | 0.00 |
June | 24146.42 | 09-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.44 | 0.00 |
July | 26369.06 | 21-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.80 | 0.00 |
August | 26653.73 | 16-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.13 | 0.00 |
September | 28255.05 | 04-SEP-15:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.67 | 0.00 |
October | 19035.92 | 05-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.13 | 0.00 |
November | 15177.23 | 01-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.80 | 0.00 |
December | 10343.03 | 04-DEC-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7972.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.87 | 0.00 | |
Maximum of Months | 28255.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.67 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1885.51 | 29-JAN-17:40 | 23.38 | 16.26 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3831.25 | 05-FEB-17:27 | 35.07 | 24.39 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7197.86 | 31-MAR-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7850.93 | 23-APR-18:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3695.88 | 31-MAY-23:57 | 0.00 | 24.39 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5545.37 | 30-JUN-23:57 | 0.00 | 24.39 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7332.62 | 31-JUL-23:57 | 0.00 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7698.86 | 15-AUG-04:12 | 0.00 | 97.54 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3693.43 | 30-SEP-24:00 | 0.00 | 16.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5452.37 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6069.10 | 12-NOV-17:17 | 35.07 | 24.39 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7706.16 | 03-DEC-17:07 | 35.07 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1885.51 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7850.93 | 35.07 | 97.54 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1625.84 | 29-JAN-17:50 | 23.38 | 16.26 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3507.51 | 05-FEB-17:40 | 11.69 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6916.43 | 31-MAR-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7360.95 | 23-APR-17:44 | 0.00 | 40.65 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3467.29 | 31-MAY-23:57 | 0.00 | 24.39 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5214.67 | 30-JUN-23:57 | 0.00 | 24.39 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6942.77 | 31-JUL-23:57 | 0.00 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7203.13 | 14-AUG-03:31 | 0.00 | 56.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3400.88 | 30-SEP-23:33 | 0.00 | 24.39 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5214.13 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5523.76 | 05-NOV-16:54 | 58.46 | 40.65 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7138.32 | 03-DEC-17:12 | 46.77 | 32.52 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1625.84 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7360.95 | 58.46 | 56.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1681.20 | 29-JAN-17:40 | 23.38 | 16.26 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3648.03 | 05-FEB-17:27 | 35.07 | 24.39 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6861.06 | 31-MAR-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7586.16 | 23-APR-18:03 | 0.00 | 32.52 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3518.80 | 31-MAY-23:57 | 0.00 | 24.39 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5237.21 | 30-JUN-23:57 | 0.00 | 24.39 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7007.42 | 31-JUL-23:57 | 0.00 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7306.97 | 14-AUG-03:02 | 0.00 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3442.95 | 30-SEP-24:00 | 0.00 | 16.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5209.15 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5677.06 | 05-NOV-17:05 | 0.00 | 32.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7181.19 | 03-DEC-17:07 | 35.07 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1681.20 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7586.16 | 35.07 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92860.08 | 02-JAN-17:00 | 4808.68 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184387.56 | 09-FEB-16:52 | 28852.07 | 17212.03 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359117.38 | 31-MAR-24:00 | 0.00 | 318.73 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369647.99 | 28-APR-13:05 | 10055.84 | 5737.34 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 177624.39 | 31-MAY-23:57 | 0.00 | 478.10 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 269320.52 | 30-JUN-23:57 | 0.00 | 478.10 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 362207.57 | 31-JUL-23:57 | 0.00 | 478.10 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 374289.71 | 10-AUG-21:01 | 2024.71 | 2549.86 | 3037060.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 178870.28 | 30-SEP-24:00 | 0.00 | 318.73 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 270261.76 | 31-OCT-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 278053.65 | 03-NOV-16:00 | 4808.68 | 2868.67 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369057.47 | 12-DEC-17:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92860.08 | 0.00 | 159.37 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 374289.71 | 28852.07 | 17212.03 | 3037060.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.159522E+13 | 1164331.22 | 30-JAN-11:00 | 0.00 | 0.00 |
February | 0.185286E+13 | 1416987.05 | 07-FEB-15:39 | 0.00 | 0.00 |
March | 0.256824E+13 | 1622908.98 | 27-MAR-10:30 | 0.00 | 0.00 |
April | 0.295955E+13 | 1819023.81 | 28-APR-15:09 | 0.00 | 0.00 |
May | 0.207832E+13 | 1494136.76 | 31-MAY-15:00 | 0.00 | 0.00 |
June | 0.259890E+13 | 1681353.90 | 12-JUN-15:09 | 0.00 | 0.00 |
July | 0.318328E+13 | 1948003.23 | 19-JUL-15:09 | 0.00 | 0.00 |
August | 0.373604E+13 | 2144759.08 | 10-AUG-15:00 | 0.00 | 0.00 |
September | 0.218465E+13 | 1581867.07 | 07-SEP-14:09 | 0.00 | 0.00 |
October | 0.246330E+13 | 1598874.04 | 06-OCT-15:50 | 0.00 | 0.00 |
November | 0.258182E+13 | 1682409.39 | 01-NOV-15:09 | 0.00 | 0.00 |
December | 0.284773E+13 | 1715942.29 | 04-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.306499E+14 | 0.00 | 0.00 | ||
Minimum of Months | 0.159522E+13 | 1164331.22 | 0.00 | 0.00 | |
Maximum of Months | 0.373604E+13 | 2144759.08 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.316604E+11 | 53648.50 | 28-JAN-12:30 | 0.00 | 0.00 |
February | 0.341585E+11 | 61428.35 | 23-FEB-13:30 | 0.00 | 0.00 |
March | 0.445117E+11 | 67873.92 | 31-MAR-11:30 | 0.00 | 0.00 |
April | 0.497739E+11 | 74992.41 | 30-APR-11:30 | 0.00 | 0.00 |
May | 0.565893E+11 | 80415.16 | 21-MAY-12:30 | 0.00 | 0.00 |
June | 0.567342E+11 | 73565.29 | 27-JUN-11:30 | 0.00 | 0.00 |
July | 0.562590E+11 | 76566.42 | 20-JUL-13:30 | 0.00 | 0.00 |
August | 0.539527E+11 | 72892.98 | 16-AUG-11:30 | 0.00 | 0.00 |
September | 0.476698E+11 | 64853.47 | 06-SEP-12:30 | 0.00 | 0.00 |
October | 0.422390E+11 | 60230.35 | 19-OCT-12:09 | 0.00 | 0.00 |
November | 0.336438E+11 | 51917.63 | 04-NOV-12:09 | 0.00 | 0.00 |
December | 0.293056E+11 | 51568.47 | 25-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.536498E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.293056E+11 | 51568.47 | 0.00 | 0.00 | |
Maximum of Months | 0.567342E+11 | 80415.16 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.144077E+12 | 0.268047E+11 | 0.766053E+12 | 0.136274E+12 | 0.184288E+12 | 0.470578E+11 | 35751551.53 | 0.165489E+12 | 0.939893E+11 | 0.279082E+10 | 0.00 | 0.283641E+11 | 0.00 |
February | 0.130100E+12 | 0.225596E+11 | 0.978954E+12 | 0.124863E+12 | 0.174924E+12 | 0.442711E+11 | 1257132.59 | 0.244059E+12 | 0.105108E+12 | 0.294343E+10 | 0.00 | 0.250781E+11 | 0.00 |
March | 0.154058E+12 | 0.227874E+11 | 0.141687E+13 | 0.144887E+12 | 0.210369E+12 | 0.589391E+11 | 0.00 | 0.399912E+12 | 0.130615E+12 | 0.232350E+10 | 0.00 | 0.274753E+11 | 0.00 |
April | 0.137193E+12 | 0.197952E+11 | 0.165903E+13 | 0.135268E+12 | 0.217920E+12 | 0.685913E+11 | 0.00 | 0.552519E+12 | 0.146411E+12 | 0.310486E+09 | 0.00 | 0.225160E+11 | 0.00 |
May | 0.147448E+12 | 0.186136E+11 | 0.774844E+12 | 0.140580E+12 | 0.261870E+12 | 0.844633E+11 | 0.00 | 0.445406E+12 | 0.183578E+12 | 7260300.71 | 0.00 | 0.215073E+11 | 0.00 |
June | 0.146477E+12 | 0.172664E+11 | 0.106252E+13 | 0.139647E+12 | 0.271253E+12 | 0.943074E+11 | 0.00 | 0.646011E+12 | 0.201932E+12 | 0.00 | 0.00 | 0.194885E+11 | 0.00 |
July | 0.137524E+12 | 0.181963E+11 | 0.139340E+13 | 0.136200E+12 | 0.287153E+12 | 0.101644E+12 | 0.00 | 0.879137E+12 | 0.212006E+12 | 0.00 | 0.00 | 0.180126E+11 | 0.00 |
August | 0.153171E+12 | 0.197205E+11 | 0.173200E+13 | 0.144887E+12 | 0.310896E+12 | 0.107040E+12 | 0.00 | 0.102959E+13 | 0.218204E+12 | 0.00 | 0.00 | 0.205275E+11 | 0.00 |
September | 0.137314E+12 | 0.209526E+11 | 0.740713E+12 | 0.135267E+12 | 0.262043E+12 | 0.953014E+11 | 0.00 | 0.567258E+12 | 0.205277E+12 | 0.00 | 0.00 | 0.205227E+11 | 0.00 |
October | 0.143121E+12 | 0.239508E+11 | 0.108340E+13 | 0.136274E+12 | 0.247909E+12 | 0.850734E+11 | 0.00 | 0.531421E+12 | 0.188414E+12 | 76274082.32 | 0.00 | 0.236637E+11 | 0.00 |
November | 0.142137E+12 | 0.253648E+11 | 0.135889E+13 | 0.131108E+12 | 0.217237E+12 | 0.677742E+11 | 0.00 | 0.465220E+12 | 0.148094E+12 | 0.378296E+09 | 0.00 | 0.256121E+11 | 0.00 |
December | 0.139708E+12 | 0.274576E+11 | 0.170972E+13 | 0.136200E+12 | 0.193676E+12 | 0.557506E+11 | 76258.51 | 0.424716E+12 | 0.128003E+12 | 0.531770E+10 | 0.00 | 0.271863E+11 | 0.00 |
Annual Sum or Average | 0.171233E+13 | 0.263470E+12 | 0.146764E+14 | 0.164146E+13 | 0.283954E+13 | 0.910213E+12 | 37084942.63 | 0.635074E+13 | 0.196163E+13 | 0.141478E+11 | 0.00 | 0.279954E+12 | 0.00 |
Minimum of Months | 0.130100E+12 | 0.172664E+11 | 0.740713E+12 | 0.124863E+12 | 0.174924E+12 | 0.442711E+11 | 0.00 | 0.165489E+12 | 0.939893E+11 | 0.00 | 0.00 | 0.180126E+11 | 0.00 |
Maximum of Months | 0.154058E+12 | 0.274576E+11 | 0.173200E+13 | 0.144887E+12 | 0.310896E+12 | 0.107040E+12 | 35751551.53 | 0.102959E+13 | 0.218204E+12 | 0.531770E+10 | 0.00 | 0.283641E+11 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 155162.26 | 23-JAN-16:00 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 154947.86 | 09-JAN-08:20 | 124838.77 | 23-JAN-13:30 | 27898.78 | 30-JAN-06:10 | 2107.73 | 02-JAN-06:00 |
February | 157827.72 | 09-FEB-16:00 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 154947.13 | 09-FEB-08:20 | 159662.31 | 07-FEB-13:00 | 50000.38 | 06-FEB-15:39 | 337.01 | 13-FEB-06:49 |
March | 164979.26 | 15-MAR-07:10 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 154953.99 | 15-MAR-07:19 | 199727.39 | 27-MAR-15:20 | 52608.23 | 23-MAR-15:20 | 0.00 | 01-MAR-00:10 |
April | 157541.36 | 18-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 154950.08 | 18-APR-07:19 | 202005.44 | 28-APR-15:20 | 52138.86 | 27-APR-12:39 | 0.00 | 01-APR-00:10 |
May | 146529.51 | 23-MAY-07:10 | 31088.59 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 154944.31 | 23-MAY-07:19 | 223816.31 | 30-MAY-15:30 | 51850.61 | 11-MAY-08:20 | 0.00 | 01-MAY-00:10 |
June | 147016.92 | 08-JUN-07:10 | 31088.59 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 154944.57 | 08-JUN-07:19 | 227455.21 | 01-JUN-15:20 | 51710.31 | 22-JUN-14:09 | 0.00 | 01-JUN-00:10 |
July | 151847.86 | 20-JUL-07:10 | 31088.59 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 154947.10 | 20-JUL-07:19 | 245141.86 | 31-JUL-15:50 | 54550.99 | 24-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 147796.69 | 29-AUG-07:10 | 31088.59 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 154944.97 | 29-AUG-07:19 | 252766.45 | 07-AUG-15:39 | 54499.06 | 21-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 149056.15 | 06-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 154945.63 | 06-SEP-07:19 | 248746.39 | 05-SEP-15:00 | 53337.94 | 05-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 150606.23 | 31-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 154946.45 | 31-OCT-07:19 | 209950.39 | 10-OCT-15:39 | 51109.75 | 20-OCT-13:39 | 0.00 | 01-OCT-00:10 |
November | 159193.86 | 29-NOV-16:00 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 154946.65 | 29-NOV-08:20 | 192253.19 | 06-NOV-15:30 | 50791.64 | 01-NOV-14:09 | 0.00 | 01-NOV-00:10 |
December | 161681.18 | 15-DEC-16:00 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 154951.86 | 15-DEC-08:20 | 152929.17 | 04-DEC-13:00 | 50107.64 | 06-DEC-11:00 | 127.10 | 18-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 146529.51 | 31088.59 | 423497.50 | 154944.31 | 124838.77 | 27898.78 | 0.00 | |||||||
Maximum of Months | 164979.26 | 31088.59 | 778371.69 | 154953.99 | 252766.45 | 54550.99 | 2107.73 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 227013.99 | 30-JAN-13:00 | 84235.13 | 30-JAN-13:39 | 5460.17 | 01-JAN-05:00 | 0.00 | 37718.13 | 12-JAN-12:30 | 0.00 | 01-JAN-00:10 |
February | 303628.23 | 06-FEB-15:00 | 84235.13 | 06-FEB-11:39 | 6787.87 | 15-FEB-05:00 | 0.00 | 37357.19 | 02-FEB-12:30 | 0.00 | 01-FEB-00:10 |
March | 350482.14 | 01-MAR-13:20 | 84235.13 | 01-MAR-13:30 | 9425.63 | 08-MAR-05:00 | 0.00 | 35034.83 | 01-MAR-12:00 | 0.00 | 01-MAR-00:10 |
April | 418134.06 | 26-APR-12:09 | 84235.13 | 03-APR-07:10 | 5189.51 | 05-APR-04:00 | 0.00 | 31636.48 | 03-APR-11:39 | 0.00 | 01-APR-00:10 |
May | 402013.38 | 31-MAY-15:00 | 84235.13 | 01-MAY-07:10 | 1440.50 | 07-MAY-10:00 | 0.00 | 28823.30 | 01-MAY-11:00 | 0.00 | 01-MAY-00:10 |
June | 467122.05 | 12-JUN-14:09 | 84235.13 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 0.00 | 26219.59 | 01-JUN-11:50 | 0.00 | 01-JUN-00:10 |
July | 609153.45 | 19-JUL-14:00 | 84235.13 | 01-JUL-00:30 | 0.00 | 01-JUL-00:10 | 0.00 | 24706.94 | 31-JUL-11:39 | 0.00 | 01-JUL-00:10 |
August | 673094.08 | 10-AUG-15:00 | 84235.13 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 26485.48 | 29-AUG-11:20 | 0.00 | 01-AUG-00:10 |
September | 488954.94 | 07-SEP-14:09 | 84235.13 | 01-SEP-00:30 | 0.00 | 01-SEP-00:10 | 0.00 | 29010.21 | 29-SEP-11:50 | 0.00 | 01-SEP-00:10 |
October | 400547.37 | 06-OCT-15:00 | 84235.13 | 01-OCT-00:10 | 4490.10 | 29-OCT-12:00 | 0.00 | 33136.99 | 31-OCT-11:30 | 0.00 | 01-OCT-00:10 |
November | 404379.65 | 01-NOV-14:09 | 84235.13 | 01-NOV-07:10 | 5700.13 | 22-NOV-06:00 | 0.00 | 35632.97 | 30-NOV-12:00 | 0.00 | 01-NOV-00:10 |
December | 355304.51 | 04-DEC-13:09 | 84235.13 | 04-DEC-09:20 | 13583.30 | 18-DEC-05:00 | 0.00 | 37553.53 | 28-DEC-12:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 227013.99 | 84235.13 | 0.00 | 0.00 | 24706.94 | 0.00 | |||||
Maximum of Months | 673094.08 | 84235.13 | 13583.30 | 0.00 | 37718.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1164331.22 | 30-JAN-11:00 | 145987.23 | 423497.50 | 0.00 | 154722.86 | 113693.07 | 27034.36 | 0.00 | 205022.83 | 64005.69 |
February | 1416987.05 | 07-FEB-15:39 | 145987.23 | 541788.89 | 0.00 | 154722.86 | 154056.96 | 49908.78 | 0.00 | 264747.68 | 84235.13 |
March | 1622908.98 | 27-MAR-10:30 | 145987.23 | 660080.29 | 0.00 | 154722.86 | 172483.01 | 51601.44 | 0.00 | 326932.34 | 84235.13 |
April | 1819023.81 | 28-APR-15:09 | 145987.23 | 778371.69 | 0.00 | 154849.24 | 201368.71 | 50210.08 | 0.00 | 382278.69 | 84235.13 |
May | 1494136.76 | 31-MAY-15:00 | 145987.23 | 423497.50 | 0.00 | 154849.24 | 212314.39 | 51385.70 | 0.00 | 402013.38 | 84235.13 |
June | 1681353.90 | 12-JUN-15:09 | 145987.23 | 541788.89 | 0.00 | 154849.24 | 224441.22 | 51647.74 | 0.00 | 459603.80 | 84235.13 |
July | 1948003.23 | 19-JUL-15:09 | 145987.23 | 660080.29 | 0.00 | 154849.24 | 226014.35 | 52710.45 | 0.00 | 606172.86 | 84235.13 |
August | 2144759.08 | 10-AUG-15:00 | 145987.23 | 778371.69 | 0.00 | 154849.24 | 236204.86 | 53135.41 | 0.00 | 673094.08 | 84235.13 |
September | 1581867.07 | 07-SEP-14:09 | 145987.23 | 423497.50 | 0.00 | 154722.86 | 217034.25 | 52301.29 | 0.00 | 488954.94 | 84235.13 |
October | 1598874.04 | 06-OCT-15:50 | 145987.23 | 541788.89 | 0.00 | 154849.24 | 198193.08 | 51001.18 | 0.00 | 400000.38 | 84235.13 |
November | 1682409.39 | 01-NOV-15:09 | 145987.23 | 660080.29 | 0.00 | 154849.24 | 178347.41 | 50530.62 | 0.00 | 383519.84 | 84235.13 |
December | 1715942.29 | 04-DEC-11:30 | 145987.23 | 778371.69 | 0.00 | 154722.86 | 141715.99 | 49689.05 | 0.00 | 331476.02 | 84235.13 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1164331.22 | 145987.23 | 423497.50 | 0.00 | 154722.86 | 113693.07 | 27034.36 | 0.00 | 205022.83 | 64005.69 | |
Maximum of Months | 2144759.08 | 145987.23 | 778371.69 | 0.00 | 154849.24 | 236204.86 | 53135.41 | 0.00 | 673094.08 | 84235.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 27.46 | 20.17 | 27.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 123.17 | 27.69 | 76.50 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 245.17 | 27.72 | 175.33 | 27.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 442.00 | 28.46 | 302.17 | 28.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 724.50 | 29.56 | 494.00 | 29.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 713.17 | 29.83 | 489.17 | 29.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.43 | 497.00 | 30.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.87 | 514.00 | 30.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 30.57 | 485.00 | 30.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 724.50 | 30.31 | 483.67 | 30.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 469.17 | 28.46 | 299.00 | 28.45 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 157.50 | 27.81 | 96.67 | 27.85 |
Annual Sum or Average | 0.00 | 0.00 | 5850.17 | 29.74 | 3932.67 | 29.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 27.46 | 20.17 | 27.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.87 | 514.00 | 30.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.62 | 0.00 | 25.62 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.58 | 0.00 | 25.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.64 | 0.00 | 25.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.86 | 0.00 | 25.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 25.86 | 0.33 | 25.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 26.09 | 0.00 | 26.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 26.18 | 0.83 | 26.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 26.39 | 3.83 | 26.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 26.11 | 0.17 | 26.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 26.40 | 1.83 | 26.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.79 | 0.00 | 25.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.81 | 0.00 | 25.81 |
Annual Sum or Average | 0.00 | 0.00 | 88.83 | 26.19 | 7.00 | 26.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 26.40 | 3.83 | 26.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.57 | 0.00 | 25.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.61 | 0.00 | 25.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.88 | 0.00 | 25.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 25.67 | 0.00 | 25.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.88 | 0.00 | 25.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.72 | 0.00 | 25.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.01 | 4.00 | 27.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 27.20 | 12.67 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 27.30 | 12.17 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 85.00 | 27.55 | 25.00 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 80.83 | 27.47 | 22.83 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 27.31 | 14.50 | 27.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 | 27.13 | 12.33 | 27.28 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.70 | 2.33 | 26.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 331.83 | 27.36 | 105.83 | 27.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 85.00 | 27.55 | 25.00 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.36 | 0.83 | 27.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.19 | 2.00 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.34 | 11.17 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 27.42 | 15.33 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 27.40 | 14.17 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 86.83 | 27.64 | 26.33 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 80.67 | 27.57 | 22.67 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 | 27.48 | 17.50 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 27.35 | 15.50 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.18 | 7.17 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 381.17 | 27.49 | 132.83 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 86.83 | 27.64 | 26.33 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.40 | 4.67 | 27.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.58 | 4.83 | 27.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.32 | 3.83 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.27 | 8.67 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 27.16 | 11.33 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 27.17 | 10.33 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 76.00 | 27.49 | 22.50 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 79.50 | 27.46 | 22.33 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 | 27.43 | 15.67 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 27.42 | 15.67 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.56 | 12.67 | 27.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.66 | 7.83 | 27.66 |
Annual Sum or Average | 0.00 | 0.00 | 370.33 | 27.41 | 140.33 | 27.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.16 | 3.83 | 27.31 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 79.50 | 27.66 | 22.50 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.48 | 1.33 | 27.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.28 | 4.33 | 27.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.19 | 7.17 | 27.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 27.57 | 17.50 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 54.50 | 27.45 | 16.00 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 76.00 | 27.60 | 20.00 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 88.50 | 27.97 | 26.50 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 82.33 | 28.04 | 24.33 | 28.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 66.33 | 27.50 | 19.17 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 59.67 | 27.44 | 19.00 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 27.39 | 14.17 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.21 | 11.50 | 27.37 |
Annual Sum or Average | 0.00 | 0.00 | 560.00 | 27.63 | 181.00 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.19 | 1.33 | 27.34 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 88.50 | 28.04 | 26.50 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.35 | 1.50 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.23 | 8.83 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 27.00 | 9.00 | 27.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 | 27.26 | 15.33 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 27.11 | 10.00 | 27.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.18 | 9.33 | 27.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.25 | 5.33 | 27.33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 144.17 | 27.17 | 59.33 | 27.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 | 27.35 | 15.33 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.53 | 2.00 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.59 | 10.83 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 27.41 | 13.00 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 27.20 | 10.83 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 53.50 | 27.48 | 17.67 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 44.67 | 27.34 | 12.67 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 27.34 | 12.50 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.45 | 13.50 | 27.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.37 | 5.17 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 224.00 | 27.39 | 98.50 | 27.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 53.50 | 27.59 | 17.67 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.41 | 3.33 | 27.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.63 | 3.50 | 27.64 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.50 | 3.00 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.50 | 6.83 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.25 | 8.67 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 26.93 | 8.17 | 27.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 27.25 | 14.00 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 27.18 | 10.50 | 27.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 27.29 | 11.17 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 27.48 | 12.67 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.81 | 11.67 | 27.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.61 | 6.50 | 27.61 |
Annual Sum or Average | 0.00 | 0.00 | 204.50 | 27.31 | 100.00 | 27.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.93 | 3.00 | 27.14 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 27.81 | 14.00 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.56 | 0.83 | 27.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.23 | 2.33 | 27.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.50 | 7.00 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 34.83 | 27.36 | 11.50 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 27.30 | 10.50 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 72.00 | 27.55 | 21.67 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 | 27.50 | 17.83 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 27.35 | 11.83 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 27.28 | 10.17 | 27.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.51 | 6.00 | 27.57 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
Annual Sum or Average | 0.00 | 0.00 | 307.00 | 27.43 | 100.00 | 27.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 72.00 | 27.56 | 21.67 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.67 | 27.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.47 | 3.50 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.42 | 10.00 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.21 | 9.67 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 27.43 | 16.50 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 27.29 | 11.00 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 27.37 | 10.00 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.40 | 7.33 | 27.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 182.00 | 27.35 | 68.83 | 27.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 27.47 | 16.50 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.31 | 0.67 | 27.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.48 | 2.00 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.68 | 11.00 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 27.60 | 12.83 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 27.35 | 11.00 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 27.62 | 18.67 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 53.83 | 27.45 | 13.83 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 27.50 | 12.67 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.59 | 13.17 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.41 | 5.83 | 27.41 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 251.33 | 27.52 | 101.67 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 27.68 | 18.67 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.41 | 2.33 | 27.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.65 | 3.33 | 27.66 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.49 | 2.83 | 27.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.59 | 7.67 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 27.43 | 9.83 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 27.16 | 8.83 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 27.41 | 15.83 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 | 27.35 | 11.67 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 27.45 | 11.33 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 27.64 | 12.33 | 27.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.85 | 11.00 | 27.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.60 | 5.33 | 27.60 |
Annual Sum or Average | 0.00 | 0.00 | 237.00 | 27.45 | 102.33 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.16 | 2.33 | 27.35 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 27.85 | 15.83 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.66 | 1.00 | 27.66 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.46 | 2.67 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.60 | 7.83 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 27.49 | 12.17 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 27.41 | 11.33 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 75.50 | 27.65 | 22.50 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 70.00 | 27.60 | 18.17 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 | 27.45 | 13.00 | 27.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 27.42 | 10.17 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.63 | 6.17 | 27.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.50 | 27.31 |
Annual Sum or Average | 0.00 | 0.00 | 324.00 | 27.54 | 105.50 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 75.50 | 27.66 | 22.50 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.90 | 17.00 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.70 | 0.00 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 638.50 | 28.27 | 422.33 | 28.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 658.50 | 28.26 | 439.33 | 28.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 638.50 | 28.27 | 422.33 | 28.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.89 | 10.33 | 27.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.61 | 0.00 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 497.00 | 28.21 | 379.00 | 28.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 508.00 | 28.20 | 389.33 | 28.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 497.00 | 28.21 | 379.00 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.81 | 14.00 | 27.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.59 | 0.00 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 468.17 | 28.31 | 358.33 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 484.17 | 28.29 | 372.33 | 28.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 468.17 | 28.31 | 358.33 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.98 | 1.67 | 27.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 27.94 | 68.50 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 70.17 | 27.95 | 70.17 | 27.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 27.98 | 68.50 | 27.98 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.67 | 27.90 | 433.83 | 24.83 | 14.67 | 24.93 |
February | 102.00 | 27.14 | 438.83 | 25.55 | 102.00 | 25.80 |
March | 165.33 | 27.79 | 497.67 | 26.23 | 165.33 | 26.54 |
April | 324.17 | 28.32 | 478.17 | 27.60 | 324.17 | 27.81 |
May | 489.33 | 29.65 | 508.00 | 29.55 | 489.33 | 29.58 |
June | 483.50 | 29.95 | 496.00 | 29.89 | 483.50 | 29.91 |
July | 497.00 | 30.50 | 497.00 | 30.50 | 497.00 | 30.50 |
August | 514.00 | 30.93 | 514.00 | 30.93 | 514.00 | 30.93 |
September | 485.00 | 30.64 | 485.00 | 30.64 | 485.00 | 30.64 |
October | 474.83 | 30.48 | 502.00 | 30.32 | 474.83 | 30.37 |
November | 280.00 | 28.64 | 486.83 | 27.54 | 280.00 | 27.83 |
December | 120.33 | 27.30 | 481.50 | 25.64 | 120.33 | 25.92 |
Annual Sum or Average | 3950.17 | 29.78 | 5818.83 | 28.79 | 3950.17 | 29.08 |
Minimum of Months | 14.67 | 27.14 | 433.83 | 24.83 | 14.67 | 24.93 |
Maximum of Months | 514.00 | 30.93 | 514.00 | 30.93 | 514.00 | 30.93 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 415.00 | 24.44 | 0.00 | 24.44 |
February | 0.00 | 0.00 | 429.83 | 24.41 | 0.00 | 24.41 |
March | 0.00 | 0.00 | 485.83 | 24.30 | 0.00 | 24.30 |
April | 2.50 | 26.69 | 477.67 | 24.31 | 2.50 | 24.33 |
May | 3.67 | 26.62 | 506.00 | 24.42 | 3.67 | 24.43 |
June | 7.17 | 26.59 | 496.00 | 24.41 | 7.17 | 24.44 |
July | 40.67 | 26.58 | 497.00 | 24.69 | 40.67 | 24.82 |
August | 48.50 | 26.60 | 514.00 | 24.64 | 48.50 | 24.80 |
September | 25.33 | 26.61 | 485.00 | 24.58 | 25.33 | 24.68 |
October | 26.83 | 26.70 | 497.33 | 24.63 | 26.83 | 24.73 |
November | 0.00 | 0.00 | 485.33 | 24.43 | 0.00 | 24.43 |
December | 0.00 | 0.00 | 477.17 | 24.40 | 0.00 | 24.40 |
Annual Sum or Average | 154.67 | 26.61 | 5766.17 | 24.48 | 154.67 | 24.53 |
Minimum of Months | 0.00 | 0.00 | 415.00 | 24.30 | 0.00 | 24.30 |
Maximum of Months | 48.50 | 26.70 | 514.00 | 24.69 | 48.50 | 24.82 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.17 | 23.55 | 310.50 | 24.20 | 0.00 | 24.20 |
February | 6.83 | 23.61 | 372.00 | 24.27 | 0.00 | 24.27 |
March | 1.50 | 23.60 | 409.17 | 24.28 | 0.00 | 24.28 |
April | 3.00 | 23.83 | 433.17 | 24.24 | 0.00 | 24.24 |
May | 0.00 | 0.00 | 478.83 | 24.14 | 0.00 | 24.14 |
June | 0.00 | 0.00 | 493.67 | 24.09 | 0.00 | 24.09 |
July | 0.00 | 0.00 | 496.00 | 24.10 | 0.00 | 24.10 |
August | 0.00 | 0.00 | 514.00 | 24.10 | 0.00 | 24.10 |
September | 0.00 | 0.00 | 485.00 | 24.15 | 0.00 | 24.15 |
October | 0.00 | 0.00 | 485.33 | 24.23 | 0.00 | 24.23 |
November | 0.00 | 0.00 | 481.17 | 24.29 | 0.00 | 24.29 |
December | 11.50 | 23.52 | 416.50 | 24.23 | 0.00 | 24.23 |
Annual Sum or Average | 58.00 | 23.57 | 5375.33 | 24.19 | 0.00 | 24.19 |
Minimum of Months | 0.00 | 0.00 | 310.50 | 24.09 | 0.00 | 24.09 |
Maximum of Months | 35.17 | 23.83 | 514.00 | 24.29 | 0.00 | 24.29 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 166.67 | 23.34 | 209.17 | 23.75 | 13.33 | 23.74 |
February | 71.00 | 23.35 | 305.00 | 24.04 | 0.00 | 24.04 |
March | 22.00 | 23.46 | 389.33 | 24.21 | 0.00 | 24.21 |
April | 0.00 | 0.00 | 435.00 | 24.28 | 0.00 | 24.28 |
May | 0.00 | 0.00 | 486.17 | 24.24 | 0.00 | 24.24 |
June | 0.00 | 0.00 | 496.00 | 24.17 | 0.00 | 24.17 |
July | 0.00 | 0.00 | 497.00 | 24.24 | 0.00 | 24.24 |
August | 0.00 | 0.00 | 514.00 | 24.19 | 0.00 | 24.19 |
September | 0.83 | 26.62 | 485.00 | 24.24 | 0.83 | 24.25 |
October | 0.00 | 0.00 | 488.50 | 24.27 | 0.00 | 24.27 |
November | 0.00 | 0.00 | 474.33 | 24.27 | 0.00 | 24.27 |
December | 72.67 | 23.34 | 334.83 | 24.01 | 0.00 | 24.01 |
Annual Sum or Average | 333.17 | 23.36 | 5114.33 | 24.17 | 14.17 | 24.17 |
Minimum of Months | 0.00 | 0.00 | 209.17 | 23.75 | 0.00 | 23.74 |
Maximum of Months | 166.67 | 26.62 | 514.00 | 24.28 | 13.33 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 91.17 | 23.38 | 258.83 | 24.03 | 0.00 | 24.03 |
February | 26.17 | 23.33 | 366.83 | 24.25 | 0.00 | 24.25 |
March | 5.33 | 23.53 | 453.00 | 24.29 | 0.00 | 24.29 |
April | 20.67 | 26.85 | 476.00 | 24.53 | 20.67 | 24.63 |
May | 66.33 | 26.87 | 508.00 | 24.84 | 66.33 | 25.05 |
June | 81.17 | 26.83 | 496.00 | 24.87 | 81.17 | 25.11 |
July | 113.50 | 26.94 | 497.00 | 25.13 | 113.50 | 25.41 |
August | 93.00 | 26.94 | 514.00 | 24.94 | 93.00 | 25.21 |
September | 83.67 | 26.86 | 485.00 | 24.95 | 83.67 | 25.19 |
October | 59.67 | 26.86 | 502.00 | 24.85 | 59.67 | 25.04 |
November | 14.17 | 26.80 | 487.00 | 24.51 | 14.17 | 24.58 |
December | 11.67 | 23.61 | 423.17 | 24.28 | 0.00 | 24.28 |
Annual Sum or Average | 666.50 | 26.18 | 5466.83 | 24.67 | 532.17 | 24.85 |
Minimum of Months | 5.33 | 23.33 | 258.83 | 24.03 | 0.00 | 24.03 |
Maximum of Months | 113.50 | 26.94 | 514.00 | 25.13 | 113.50 | 25.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.00 | 23.41 | 319.17 | 24.21 | 0.67 | 24.21 |
February | 24.17 | 23.77 | 393.33 | 24.33 | 3.17 | 24.35 |
March | 15.00 | 25.00 | 459.00 | 24.34 | 6.67 | 24.38 |
April | 41.83 | 26.90 | 474.83 | 24.67 | 41.83 | 24.84 |
May | 81.50 | 26.95 | 508.00 | 24.93 | 81.50 | 25.18 |
June | 84.67 | 26.89 | 496.00 | 24.90 | 84.67 | 25.16 |
July | 114.50 | 27.00 | 497.00 | 25.15 | 114.50 | 25.45 |
August | 93.67 | 26.99 | 514.00 | 24.96 | 93.67 | 25.23 |
September | 95.83 | 26.94 | 485.00 | 25.03 | 95.83 | 25.30 |
October | 78.67 | 26.93 | 502.00 | 24.96 | 78.67 | 25.19 |
November | 33.83 | 26.82 | 486.83 | 24.65 | 33.83 | 24.78 |
December | 17.83 | 23.34 | 419.67 | 24.26 | 0.00 | 24.26 |
Annual Sum or Average | 744.50 | 26.42 | 5554.83 | 24.75 | 635.00 | 24.95 |
Minimum of Months | 15.00 | 23.34 | 319.17 | 24.21 | 0.00 | 24.21 |
Maximum of Months | 114.50 | 27.00 | 514.00 | 25.15 | 114.50 | 25.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.33 | 24.27 | 377.33 | 24.47 | 15.50 | 24.56 |
February | 38.50 | 25.15 | 405.83 | 24.53 | 19.17 | 24.62 |
March | 21.33 | 26.01 | 472.17 | 24.45 | 15.67 | 24.52 |
April | 35.17 | 26.89 | 478.17 | 24.63 | 35.17 | 24.78 |
May | 58.83 | 26.88 | 508.00 | 24.81 | 58.83 | 25.00 |
June | 64.33 | 26.83 | 496.00 | 24.79 | 64.33 | 25.00 |
July | 109.83 | 26.91 | 497.00 | 25.10 | 109.83 | 25.38 |
August | 93.33 | 26.94 | 514.00 | 24.95 | 93.33 | 25.21 |
September | 94.17 | 26.91 | 485.00 | 25.01 | 94.17 | 25.28 |
October | 85.67 | 26.98 | 502.00 | 25.01 | 85.67 | 25.26 |
November | 56.50 | 26.97 | 489.00 | 24.84 | 56.50 | 25.04 |
December | 41.83 | 26.45 | 468.67 | 24.65 | 36.33 | 24.80 |
Annual Sum or Average | 757.83 | 26.57 | 5693.17 | 24.79 | 684.50 | 24.99 |
Minimum of Months | 21.33 | 24.27 | 377.33 | 24.45 | 15.50 | 24.52 |
Maximum of Months | 109.83 | 26.98 | 514.00 | 25.10 | 109.83 | 25.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.17 | 25.15 | 402.67 | 24.55 | 8.50 | 24.59 |
February | 24.50 | 26.93 | 442.17 | 24.70 | 24.50 | 24.81 |
March | 41.83 | 26.97 | 507.33 | 24.73 | 41.83 | 24.88 |
April | 93.67 | 26.93 | 485.00 | 25.02 | 93.67 | 25.28 |
May | 96.33 | 26.90 | 508.00 | 24.99 | 96.33 | 25.25 |
June | 96.33 | 26.93 | 496.00 | 24.97 | 96.33 | 25.24 |
July | 118.83 | 27.05 | 497.00 | 25.20 | 118.83 | 25.50 |
August | 101.17 | 27.08 | 514.00 | 25.04 | 101.17 | 25.32 |
September | 104.17 | 26.90 | 485.00 | 25.05 | 104.17 | 25.33 |
October | 108.00 | 26.91 | 502.00 | 25.08 | 108.00 | 25.36 |
November | 80.67 | 26.94 | 489.00 | 25.00 | 80.67 | 25.24 |
December | 58.50 | 26.94 | 495.00 | 24.91 | 58.50 | 25.10 |
Annual Sum or Average | 942.17 | 26.92 | 5823.17 | 24.95 | 932.50 | 25.19 |
Minimum of Months | 18.17 | 25.15 | 402.67 | 24.55 | 8.50 | 24.59 |
Maximum of Months | 118.83 | 27.08 | 514.00 | 25.20 | 118.83 | 25.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 291.33 | 23.02 | 115.50 | 23.31 | 0.00 | 23.31 |
February | 124.83 | 23.07 | 219.17 | 23.76 | 0.00 | 23.76 |
March | 61.17 | 23.26 | 358.83 | 24.10 | 0.00 | 24.10 |
April | 13.83 | 25.47 | 449.33 | 24.46 | 10.17 | 24.50 |
May | 40.17 | 26.86 | 506.50 | 24.70 | 40.17 | 24.85 |
June | 43.67 | 26.86 | 496.00 | 24.69 | 43.67 | 24.85 |
July | 75.50 | 26.90 | 497.00 | 24.94 | 75.50 | 25.17 |
August | 57.33 | 26.86 | 514.00 | 24.74 | 57.33 | 24.93 |
September | 49.67 | 26.80 | 485.00 | 24.75 | 49.67 | 24.93 |
October | 34.00 | 26.63 | 495.67 | 24.66 | 34.00 | 24.78 |
November | 4.17 | 23.25 | 460.67 | 24.33 | 0.00 | 24.33 |
December | 154.33 | 23.13 | 261.67 | 23.76 | 0.00 | 23.76 |
Annual Sum or Average | 950.00 | 24.30 | 4859.33 | 24.42 | 310.50 | 24.54 |
Minimum of Months | 4.17 | 23.02 | 115.50 | 23.31 | 0.00 | 23.31 |
Maximum of Months | 291.33 | 26.90 | 514.00 | 24.94 | 75.50 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 136.00 | 23.10 | 171.00 | 23.77 | 0.17 | 23.77 |
February | 55.33 | 23.19 | 269.50 | 24.17 | 1.83 | 24.19 |
March | 38.50 | 24.07 | 340.83 | 24.40 | 8.83 | 24.46 |
April | 52.17 | 26.68 | 393.17 | 24.88 | 50.17 | 25.08 |
May | 61.33 | 26.99 | 430.00 | 24.98 | 61.33 | 25.21 |
June | 52.83 | 26.97 | 418.00 | 24.90 | 52.83 | 25.11 |
July | 92.50 | 26.98 | 422.00 | 25.20 | 92.50 | 25.47 |
August | 75.50 | 26.92 | 433.00 | 24.98 | 75.50 | 25.23 |
September | 63.67 | 26.97 | 410.00 | 25.02 | 63.67 | 25.25 |
October | 59.50 | 26.89 | 426.33 | 24.99 | 59.50 | 25.20 |
November | 24.33 | 26.69 | 408.67 | 24.71 | 23.33 | 24.82 |
December | 69.50 | 23.15 | 280.50 | 24.09 | 0.00 | 24.09 |
Annual Sum or Average | 781.17 | 25.51 | 4403.00 | 24.74 | 489.67 | 24.93 |
Minimum of Months | 24.33 | 23.10 | 171.00 | 23.77 | 0.00 | 23.77 |
Maximum of Months | 136.00 | 26.99 | 433.00 | 25.20 | 92.50 | 25.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 97.33 | 23.70 | 340.33 | 24.31 | 14.50 | 24.39 |
February | 61.50 | 24.12 | 375.00 | 24.38 | 16.67 | 24.47 |
March | 38.00 | 24.48 | 427.33 | 24.40 | 12.83 | 24.47 |
April | 33.33 | 26.54 | 460.17 | 24.63 | 31.83 | 24.76 |
May | 38.17 | 26.88 | 506.50 | 24.69 | 38.17 | 24.83 |
June | 38.83 | 26.84 | 496.00 | 24.65 | 38.83 | 24.79 |
July | 71.33 | 26.89 | 497.00 | 24.92 | 71.33 | 25.14 |
August | 65.17 | 26.86 | 514.00 | 24.78 | 65.17 | 24.99 |
September | 63.50 | 26.93 | 485.00 | 24.87 | 63.50 | 25.09 |
October | 65.50 | 27.00 | 502.00 | 24.93 | 65.50 | 25.15 |
November | 52.67 | 26.93 | 486.67 | 24.82 | 52.00 | 25.01 |
December | 71.00 | 24.88 | 419.00 | 24.55 | 32.33 | 24.69 |
Annual Sum or Average | 696.33 | 25.86 | 5509.00 | 24.68 | 502.67 | 24.85 |
Minimum of Months | 33.33 | 23.70 | 340.33 | 24.31 | 12.83 | 24.39 |
Maximum of Months | 97.33 | 27.00 | 514.00 | 24.93 | 71.33 | 25.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 151.50 | 23.19 | 246.33 | 23.86 | 2.17 | 23.88 |
February | 61.33 | 23.37 | 341.67 | 24.18 | 4.00 | 24.21 |
March | 29.83 | 24.57 | 433.83 | 24.41 | 10.33 | 24.47 |
April | 36.50 | 26.81 | 476.00 | 24.72 | 36.50 | 24.86 |
May | 71.33 | 26.95 | 507.67 | 24.89 | 71.33 | 25.12 |
June | 83.50 | 26.87 | 496.00 | 24.89 | 83.50 | 25.14 |
July | 113.50 | 26.92 | 497.00 | 25.12 | 113.50 | 25.40 |
August | 96.17 | 26.90 | 514.00 | 24.93 | 96.17 | 25.20 |
September | 85.17 | 26.92 | 485.00 | 24.97 | 85.17 | 25.22 |
October | 61.83 | 26.91 | 499.33 | 24.90 | 61.83 | 25.10 |
November | 27.50 | 26.76 | 485.83 | 24.62 | 26.50 | 24.74 |
December | 59.00 | 23.41 | 372.83 | 24.21 | 3.17 | 24.23 |
Annual Sum or Average | 877.17 | 25.70 | 5355.50 | 24.69 | 594.17 | 24.89 |
Minimum of Months | 27.50 | 23.19 | 246.33 | 23.86 | 2.17 | 23.88 |
Maximum of Months | 151.50 | 26.95 | 514.00 | 25.12 | 113.50 | 25.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.17 | 22.65 | 95.50 | 22.95 | 0.00 | 22.95 |
February | 183.33 | 22.84 | 192.33 | 23.51 | 0.33 | 23.51 |
March | 89.50 | 23.09 | 339.33 | 24.00 | 0.67 | 24.00 |
April | 40.83 | 25.20 | 434.83 | 24.51 | 26.83 | 24.61 |
May | 47.67 | 26.90 | 505.83 | 24.75 | 47.67 | 24.92 |
June | 47.83 | 26.90 | 496.00 | 24.72 | 47.83 | 24.89 |
July | 86.00 | 26.91 | 497.00 | 25.00 | 86.00 | 25.24 |
August | 68.83 | 26.86 | 514.00 | 24.80 | 68.83 | 25.02 |
September | 57.00 | 26.80 | 485.00 | 24.79 | 57.00 | 24.98 |
October | 40.33 | 26.63 | 492.50 | 24.69 | 40.33 | 24.83 |
November | 22.00 | 23.69 | 442.00 | 24.31 | 2.83 | 24.32 |
December | 204.83 | 22.81 | 219.17 | 23.48 | 2.00 | 23.48 |
Annual Sum or Average | 1228.33 | 24.03 | 4713.50 | 24.37 | 380.33 | 24.51 |
Minimum of Months | 22.00 | 22.65 | 95.50 | 22.95 | 0.00 | 22.95 |
Maximum of Months | 340.17 | 26.91 | 514.00 | 25.00 | 86.00 | 25.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 204.00 | 22.84 | 178.17 | 23.47 | 0.00 | 23.47 |
February | 92.83 | 22.97 | 282.83 | 23.96 | 3.00 | 23.98 |
March | 63.83 | 23.66 | 395.67 | 24.24 | 9.00 | 24.29 |
April | 60.67 | 26.30 | 462.50 | 24.74 | 52.83 | 24.93 |
May | 62.17 | 27.03 | 508.00 | 24.86 | 62.17 | 25.07 |
June | 56.83 | 26.99 | 496.00 | 24.79 | 56.83 | 25.00 |
July | 98.83 | 27.00 | 497.00 | 25.08 | 98.83 | 25.36 |
August | 81.50 | 26.94 | 514.00 | 24.88 | 81.50 | 25.13 |
September | 69.00 | 26.98 | 485.00 | 24.91 | 69.00 | 25.14 |
October | 62.33 | 26.89 | 501.33 | 24.87 | 62.33 | 25.07 |
November | 32.33 | 26.19 | 469.83 | 24.60 | 26.50 | 24.71 |
December | 119.17 | 23.00 | 302.17 | 23.86 | 2.67 | 23.87 |
Annual Sum or Average | 1003.50 | 25.01 | 5092.50 | 24.59 | 524.67 | 24.78 |
Minimum of Months | 32.33 | 22.84 | 178.17 | 23.47 | 0.00 | 23.47 |
Maximum of Months | 204.00 | 27.03 | 514.00 | 25.08 | 98.83 | 25.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 136.17 | 23.12 | 306.83 | 24.03 | 11.67 | 24.10 |
February | 82.67 | 23.50 | 349.67 | 24.21 | 15.33 | 24.30 |
March | 66.00 | 23.91 | 405.67 | 24.31 | 14.00 | 24.38 |
April | 52.00 | 25.83 | 447.33 | 24.64 | 40.67 | 24.78 |
May | 45.33 | 26.92 | 505.00 | 24.74 | 45.33 | 24.90 |
June | 43.83 | 26.89 | 496.00 | 24.68 | 43.83 | 24.85 |
July | 81.83 | 26.91 | 497.00 | 24.98 | 81.83 | 25.22 |
August | 74.83 | 26.88 | 514.00 | 24.83 | 74.83 | 25.06 |
September | 70.83 | 26.92 | 485.00 | 24.91 | 70.83 | 25.13 |
October | 67.83 | 26.98 | 502.00 | 24.94 | 67.83 | 25.15 |
November | 52.50 | 26.83 | 478.17 | 24.80 | 50.50 | 24.99 |
December | 91.50 | 24.03 | 379.67 | 24.37 | 26.50 | 24.51 |
Annual Sum or Average | 865.33 | 25.39 | 5366.33 | 24.65 | 543.17 | 24.83 |
Minimum of Months | 43.83 | 23.12 | 306.83 | 24.03 | 11.67 | 24.10 |
Maximum of Months | 136.17 | 26.98 | 514.00 | 24.98 | 81.83 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 204.67 | 22.83 | 206.17 | 23.55 | 2.50 | 23.56 |
February | 97.00 | 23.10 | 313.33 | 24.01 | 5.33 | 24.05 |
March | 53.50 | 23.98 | 406.17 | 24.34 | 11.17 | 24.40 |
April | 45.83 | 26.59 | 463.67 | 24.75 | 44.17 | 24.90 |
May | 72.67 | 26.97 | 507.17 | 24.91 | 72.67 | 25.14 |
June | 85.17 | 26.89 | 496.00 | 24.90 | 85.17 | 25.16 |
July | 115.00 | 26.95 | 497.00 | 25.14 | 115.00 | 25.42 |
August | 97.00 | 26.93 | 514.00 | 24.95 | 97.00 | 25.22 |
September | 88.83 | 26.92 | 485.00 | 24.99 | 88.83 | 25.25 |
October | 63.33 | 26.89 | 498.33 | 24.90 | 63.33 | 25.10 |
November | 32.17 | 26.49 | 472.17 | 24.62 | 28.67 | 24.74 |
December | 105.67 | 23.13 | 326.67 | 24.02 | 6.17 | 24.05 |
Annual Sum or Average | 1060.83 | 25.23 | 5185.67 | 24.65 | 620.00 | 24.85 |
Minimum of Months | 32.17 | 22.83 | 206.17 | 23.55 | 2.50 | 23.56 |
Maximum of Months | 204.67 | 26.97 | 514.00 | 25.14 | 115.00 | 25.42 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 10.00 | 27.00 | 514.00 | 27.00 | 10.00 | 27.00 |
April | 160.00 | 27.13 | 485.00 | 27.06 | 160.00 | 27.08 |
May | 44.50 | 27.00 | 508.00 | 27.00 | 44.50 | 27.00 |
June | 179.33 | 27.00 | 496.00 | 27.00 | 179.33 | 27.00 |
July | 428.33 | 27.00 | 497.00 | 27.00 | 428.33 | 27.00 |
August | 514.00 | 28.17 | 514.00 | 28.17 | 514.00 | 28.17 |
September | 129.50 | 27.00 | 485.00 | 27.00 | 129.50 | 27.00 |
October | 88.67 | 27.00 | 502.00 | 27.00 | 88.67 | 27.00 |
November | 64.00 | 27.00 | 489.00 | 27.00 | 64.00 | 27.00 |
December | 43.50 | 27.00 | 497.00 | 27.00 | 43.50 | 27.00 |
Annual Sum or Average | 1661.83 | 27.38 | 5943.00 | 27.16 | 1661.83 | 27.20 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 514.00 | 28.17 | 514.00 | 28.17 | 514.00 | 28.17 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 16.67 | 27.68 | 485.00 | 27.05 | 16.67 | 27.07 |
May | 2.50 | 27.00 | 508.00 | 27.00 | 2.50 | 27.00 |
June | 8.67 | 27.00 | 496.00 | 27.00 | 8.67 | 27.00 |
July | 21.83 | 27.00 | 497.00 | 27.00 | 21.83 | 27.00 |
August | 401.67 | 28.24 | 514.00 | 28.11 | 401.67 | 28.15 |
September | 10.83 | 27.00 | 485.00 | 27.00 | 10.83 | 27.00 |
October | 0.67 | 27.00 | 502.00 | 27.00 | 0.67 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 462.83 | 28.10 | 5943.00 | 27.16 | 462.83 | 27.23 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 401.67 | 28.24 | 514.00 | 28.11 | 401.67 | 28.15 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 1.67 | 27.00 | 514.00 | 27.00 | 1.67 | 27.00 |
April | 33.17 | 27.42 | 485.00 | 27.06 | 33.17 | 27.08 |
May | 20.50 | 27.00 | 508.00 | 27.00 | 20.50 | 27.00 |
June | 25.50 | 27.00 | 496.00 | 27.00 | 25.50 | 27.00 |
July | 87.83 | 27.00 | 497.00 | 27.00 | 87.83 | 27.00 |
August | 400.00 | 28.28 | 514.00 | 28.13 | 400.00 | 28.18 |
September | 31.33 | 27.00 | 485.00 | 27.00 | 31.33 | 27.00 |
October | 19.17 | 27.00 | 502.00 | 27.00 | 19.17 | 27.00 |
November | 5.17 | 27.00 | 489.00 | 27.00 | 5.17 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 624.33 | 27.84 | 5943.00 | 27.16 | 624.33 | 27.22 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 400.00 | 28.28 | 514.00 | 28.13 | 400.00 | 28.18 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.18 | 514.00 | 27.18 | 514.00 | 27.18 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5943.00 | 27.02 | 5943.00 | 27.02 | 5943.00 | 27.02 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.18 | 514.00 | 27.18 | 514.00 | 27.18 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00086 | 31.60861 | 0.88515 | 21.56615 |
February | 454.00000 | 27.00157 | 31.10309 | 0.92606 | 23.13498 |
March | 514.00000 | 27.00091 | 30.91238 | 0.96538 | 24.70501 |
April | 485.00000 | 27.04243 | 31.72062 | 1.02628 | 27.29132 |
May | 508.00000 | 27.00064 | 36.50369 | 0.34223 | 7.49794 |
June | 496.00000 | 27.00257 | 36.68032 | 0.40004 | 8.37987 |
July | 497.00000 | 27.00115 | 36.38758 | 0.46059 | 9.48242 |
August | 514.00000 | 28.17146 | 35.17502 | 0.78071 | 18.53146 |
September | 485.00000 | 27.00019 | 40.11405 | 0.38943 | 8.21758 |
October | 502.00000 | 27.00238 | 34.77414 | 1.01360 | 26.72562 |
November | 489.00000 | 27.00125 | 32.29858 | 0.99724 | 26.02762 |
December | 497.00000 | 27.00041 | 30.37419 | 0.98514 | 25.52022 |
Annual Sum or Average | 5943.00000 | 27.10577 | 33.98378 | 0.76328 | 18.89287 |
Minimum of Months | 454.00000 | 27.00019 | 30.37419 | 0.34223 | 7.49794 |
Maximum of Months | 514.00000 | 28.17146 | 40.11405 | 1.02628 | 27.29132 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00040 | 32.04065 | 0.82782 | 19.49510 |
February | 454.00000 | 27.00148 | 31.26132 | 0.85402 | 20.42015 |
March | 514.00000 | 27.00086 | 30.96013 | 0.88605 | 21.60210 |
April | 485.00000 | 27.02991 | 31.76172 | 0.93522 | 23.51416 |
May | 508.00000 | 27.00044 | 36.87505 | 0.26737 | 6.52974 |
June | 496.00000 | 27.00254 | 36.92382 | 0.29858 | 6.88726 |
July | 497.00000 | 27.00136 | 36.56192 | 0.33203 | 7.32910 |
August | 514.00000 | 28.00766 | 35.38054 | 0.59406 | 13.08362 |
September | 485.00000 | 27.00008 | 40.81985 | 0.30490 | 6.97341 |
October | 502.00000 | 27.00226 | 35.00920 | 0.93734 | 23.57976 |
November | 489.00000 | 27.00121 | 32.38364 | 0.91370 | 22.65370 |
December | 497.00000 | 27.00041 | 30.41180 | 0.87679 | 21.25661 |
Annual Sum or Average | 5943.00000 | 27.09051 | 34.21186 | 0.66760 | 16.07390 |
Minimum of Months | 454.00000 | 27.00008 | 30.41180 | 0.26737 | 6.52974 |
Maximum of Months | 514.00000 | 28.00766 | 40.81985 | 0.93734 | 23.57976 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00034 | 32.32129 | 0.80601 | 18.78229 |
February | 454.00000 | 27.00149 | 31.31087 | 0.84040 | 19.96776 |
March | 514.00000 | 27.00088 | 30.96094 | 0.88238 | 21.49413 |
April | 485.00000 | 27.03298 | 31.75100 | 0.94153 | 23.79871 |
May | 508.00000 | 27.00051 | 36.78743 | 0.28828 | 6.81911 |
June | 496.00000 | 27.00259 | 36.86282 | 0.32215 | 7.23566 |
July | 497.00000 | 27.00136 | 36.51850 | 0.36244 | 7.81806 |
August | 514.00000 | 28.01988 | 35.33854 | 0.62242 | 14.10676 |
September | 485.00000 | 27.00012 | 40.67984 | 0.32427 | 7.27312 |
October | 502.00000 | 27.00229 | 34.98993 | 0.94486 | 23.89742 |
November | 489.00000 | 27.00123 | 32.38679 | 0.91140 | 22.58517 |
December | 497.00000 | 27.00045 | 30.42301 | 0.86005 | 20.67402 |
Annual Sum or Average | 5943.00000 | 27.09183 | 34.20685 | 0.67430 | 16.17314 |
Minimum of Months | 454.00000 | 27.00012 | 30.42301 | 0.28828 | 6.81911 |
Maximum of Months | 514.00000 | 28.01988 | 40.67984 | 0.94486 | 23.89742 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00363 | 30.87444 | 1.10577 | 30.78375 |
February | 454.00000 | 27.00396 | 30.97878 | 1.25213 | 37.83763 |
March | 514.00000 | 27.00245 | 31.32649 | 1.38845 | 44.89941 |
April | 485.00000 | 27.00698 | 32.10248 | 1.52994 | 52.52940 |
May | 508.00000 | 27.00321 | 34.71031 | 0.59310 | 12.40702 |
June | 496.00000 | 27.00360 | 35.34198 | 0.81747 | 19.10474 |
July | 497.00000 | 27.00215 | 35.61915 | 1.03777 | 27.74665 |
August | 514.00000 | 27.18444 | 35.33216 | 1.29604 | 40.14124 |
September | 485.00000 | 27.00364 | 36.67784 | 0.67655 | 14.64965 |
October | 502.00000 | 27.00328 | 33.79809 | 1.34437 | 42.57579 |
November | 489.00000 | 27.00194 | 32.16869 | 1.44448 | 47.89741 |
December | 497.00000 | 27.00271 | 30.90841 | 1.54020 | 53.08763 |
Annual Sum or Average | 5943.00000 | 27.01906 | 33.33470 | 1.16823 | 35.28061 |
Minimum of Months | 454.00000 | 27.00194 | 30.87444 | 0.59310 | 12.40702 |
Maximum of Months | 514.00000 | 27.18444 | 36.67784 | 1.54020 | 53.08763 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.63249 | 48.26318 | 0.58785 | 12.98979 |
February | 454.00000 | 25.14194 | 56.46740 | 0.76497 | 19.94369 |
March | 514.00000 | 25.65638 | 62.06429 | 0.92674 | 27.07611 |
April | 485.00000 | 27.06596 | 73.29154 | 1.34684 | 45.57294 |
May | 508.00000 | 29.46377 | 97.47871 | 1.70996 | 63.63548 |
June | 496.00000 | 29.82133 | 97.55673 | 1.84673 | 69.91070 |
July | 497.00000 | 30.50027 | 99.99290 | 2.11696 | 81.57302 |
August | 514.00000 | 30.93435 | 99.99292 | 2.28689 | 87.71870 |
September | 485.00000 | 30.64293 | 99.99824 | 2.17360 | 83.77814 |
October | 502.00000 | 30.16596 | 91.24766 | 2.30929 | 84.98108 |
November | 489.00000 | 26.88977 | 67.05337 | 1.28829 | 42.69472 |
December | 497.00000 | 25.19333 | 56.23909 | 0.78658 | 20.64007 |
Annual Sum or Average | 5943.00000 | 28.03088 | 79.31303 | 1.51751 | 53.61867 |
Minimum of Months | 454.00000 | 24.63249 | 48.26318 | 0.58785 | 12.98979 |
Maximum of Months | 514.00000 | 30.93435 | 99.99824 | 2.30929 | 87.71870 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.36124 | 50.04934 | 0.53611 | 11.33689 |
February | 454.00000 | 24.39073 | 53.41746 | 0.58230 | 12.46820 |
March | 514.00000 | 24.28403 | 51.05801 | 0.55944 | 11.79426 |
April | 485.00000 | 24.29799 | 52.39296 | 0.59533 | 12.69666 |
May | 508.00000 | 24.40096 | 52.72820 | -0.1790 | 6.43210 |
June | 496.00000 | 24.38258 | 53.88987 | -0.1564 | 6.27228 |
July | 497.00000 | 24.53077 | 52.12789 | -0.0992 | 6.36343 |
August | 514.00000 | 24.45727 | 51.71638 | -0.1033 | 6.32620 |
September | 485.00000 | 24.47680 | 53.41668 | -0.1229 | 6.36937 |
October | 502.00000 | 24.51025 | 52.32227 | 0.68329 | 15.39330 |
November | 489.00000 | 24.42388 | 54.90776 | 0.64157 | 13.98525 |
December | 497.00000 | 24.38230 | 53.65069 | 0.59496 | 12.72818 |
Annual Sum or Average | 5943.00000 | 24.40824 | 52.62038 | 0.29138 | 10.15412 |
Minimum of Months | 454.00000 | 24.28403 | 50.04934 | -0.1790 | 6.27228 |
Maximum of Months | 514.00000 | 24.53077 | 54.90776 | 0.68329 | 15.39330 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.12512 | 51.23460 | 0.45569 | 9.56497 |
February | 454.00000 | 24.20335 | 54.44562 | 0.50492 | 10.53925 |
March | 514.00000 | 24.21415 | 51.93453 | 0.50190 | 10.45965 |
April | 485.00000 | 24.21711 | 53.77979 | 0.52592 | 10.97200 |
May | 508.00000 | 24.13514 | 55.02598 | -0.3543 | 7.74939 |
June | 496.00000 | 24.09380 | 57.27967 | -0.3472 | 7.56841 |
July | 497.00000 | 24.10304 | 56.95926 | -0.3418 | 7.48525 |
August | 514.00000 | 24.09536 | 57.47651 | -0.3346 | 7.37824 |
September | 485.00000 | 24.14851 | 57.46432 | -0.3302 | 7.38033 |
October | 502.00000 | 24.22302 | 55.80071 | 0.54998 | 11.47195 |
November | 489.00000 | 24.28138 | 56.66779 | 0.56166 | 11.77969 |
December | 497.00000 | 24.18272 | 55.06922 | 0.50665 | 10.57249 |
Annual Sum or Average | 5943.00000 | 24.16798 | 55.25717 | 0.15470 | 9.39601 |
Minimum of Months | 454.00000 | 24.09380 | 51.23460 | -0.3543 | 7.37824 |
Maximum of Months | 514.00000 | 24.28138 | 57.47651 | 0.56166 | 11.77969 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.80245 | 53.87981 | 0.37891 | 8.40348 |
February | 454.00000 | 24.01332 | 55.41674 | 0.45628 | 9.63327 |
March | 514.00000 | 24.14718 | 52.45461 | 0.48759 | 10.17335 |
April | 485.00000 | 24.25071 | 53.82929 | 0.54073 | 11.32593 |
May | 508.00000 | 24.22750 | 54.79830 | -0.3018 | 7.21949 |
June | 496.00000 | 24.17099 | 57.04682 | -0.2954 | 7.02346 |
July | 497.00000 | 24.23849 | 56.50452 | -0.2664 | 6.80280 |
August | 514.00000 | 24.19184 | 57.17812 | -0.2729 | 6.80972 |
September | 485.00000 | 24.23946 | 57.29046 | -0.2792 | 6.98973 |
October | 502.00000 | 24.26682 | 55.93658 | 0.56974 | 11.97248 |
November | 489.00000 | 24.25905 | 57.16153 | 0.55702 | 11.63920 |
December | 497.00000 | 23.96268 | 56.16105 | 0.44957 | 9.53346 |
Annual Sum or Average | 5943.00000 | 24.14805 | 55.63030 | 0.16560 | 8.94775 |
Minimum of Months | 454.00000 | 23.80245 | 52.45461 | -0.3018 | 6.80280 |
Maximum of Months | 514.00000 | 24.26682 | 57.29046 | 0.56974 | 11.97248 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.01305 | 50.47089 | 0.42139 | 9.07123 |
February | 454.00000 | 24.21207 | 53.29247 | 0.51623 | 10.90507 |
March | 514.00000 | 24.25232 | 50.46164 | 0.54557 | 11.50278 |
April | 485.00000 | 24.42475 | 51.41033 | 0.64435 | 14.27182 |
May | 508.00000 | 24.57538 | 51.51613 | -0.0328 | 6.66319 |
June | 496.00000 | 24.54922 | 52.75852 | 0.01143 | 6.60655 |
July | 497.00000 | 24.71313 | 51.03926 | 0.08795 | 7.34537 |
August | 514.00000 | 24.58453 | 50.84860 | 0.05889 | 6.90704 |
September | 485.00000 | 24.61690 | 52.48199 | 0.00576 | 6.85415 |
October | 502.00000 | 24.60578 | 51.48780 | 0.73308 | 17.13162 |
November | 489.00000 | 24.44490 | 54.20491 | 0.64420 | 14.14945 |
December | 497.00000 | 24.23733 | 53.64562 | 0.53149 | 11.19396 |
Annual Sum or Average | 5943.00000 | 24.43697 | 51.94553 | 0.34524 | 10.19828 |
Minimum of Months | 454.00000 | 24.01305 | 50.46164 | -0.0328 | 6.60655 |
Maximum of Months | 514.00000 | 24.71313 | 54.20491 | 0.73308 | 17.13162 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.14554 | 49.83040 | 0.46984 | 10.11504 |
February | 454.00000 | 24.27755 | 52.90233 | 0.54926 | 11.79480 |
March | 514.00000 | 24.27539 | 50.27108 | 0.56841 | 12.18790 |
April | 485.00000 | 24.46097 | 51.16216 | 0.67969 | 15.42827 |
May | 508.00000 | 24.60900 | 51.26121 | 0.04309 | 6.96034 |
June | 496.00000 | 24.56441 | 52.60070 | 0.06605 | 6.84213 |
July | 497.00000 | 24.72941 | 50.91159 | 0.13948 | 7.82488 |
August | 514.00000 | 24.59565 | 50.71139 | 0.11289 | 7.19350 |
September | 485.00000 | 24.64984 | 52.23540 | 0.08167 | 7.27675 |
October | 502.00000 | 24.64540 | 51.14970 | 0.77991 | 18.74777 |
November | 489.00000 | 24.49757 | 53.90286 | 0.67798 | 15.25674 |
December | 497.00000 | 24.21513 | 53.66911 | 0.53493 | 11.35002 |
Annual Sum or Average | 5943.00000 | 24.47309 | 51.69581 | 0.38996 | 10.89315 |
Minimum of Months | 454.00000 | 24.14554 | 49.83040 | 0.04309 | 6.84213 |
Maximum of Months | 514.00000 | 24.72941 | 53.90286 | 0.77991 | 18.74777 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.33128 | 48.92291 | 0.55075 | 12.20381 |
February | 454.00000 | 24.38748 | 52.31550 | 0.61172 | 13.52846 |
March | 514.00000 | 24.33792 | 49.96487 | 0.60463 | 13.16058 |
April | 485.00000 | 24.46173 | 51.23043 | 0.67035 | 15.10184 |
May | 508.00000 | 24.56547 | 51.56554 | -0.0435 | 6.62579 |
June | 496.00000 | 24.53051 | 52.85447 | -0.0178 | 6.49899 |
July | 497.00000 | 24.70192 | 51.07960 | 0.06929 | 7.18568 |
August | 514.00000 | 24.58546 | 50.82646 | 0.06783 | 6.92265 |
September | 485.00000 | 24.64276 | 52.31965 | 0.06315 | 7.12933 |
October | 502.00000 | 24.67561 | 51.06771 | 0.80940 | 19.80333 |
November | 489.00000 | 24.59347 | 53.39937 | 0.75354 | 17.77914 |
December | 497.00000 | 24.45351 | 52.51540 | 0.64536 | 14.52109 |
Annual Sum or Average | 5943.00000 | 24.52272 | 51.48665 | 0.39621 | 11.67526 |
Minimum of Months | 454.00000 | 24.33128 | 48.92291 | -0.0435 | 6.49899 |
Maximum of Months | 514.00000 | 24.70192 | 53.39937 | 0.80940 | 19.80333 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.40956 | 48.70899 | 0.56182 | 12.17701 |
February | 454.00000 | 24.55649 | 51.65501 | 0.66899 | 15.11253 |
March | 514.00000 | 24.53460 | 49.16147 | 0.70689 | 16.26228 |
April | 485.00000 | 24.64675 | 50.41131 | 0.80286 | 19.55858 |
May | 508.00000 | 24.62287 | 51.30740 | 0.04807 | 7.06700 |
June | 496.00000 | 24.58756 | 52.54822 | 0.10755 | 7.22161 |
July | 497.00000 | 24.75312 | 50.81157 | 0.19981 | 8.43498 |
August | 514.00000 | 24.63354 | 50.56742 | 0.20487 | 8.16857 |
September | 485.00000 | 24.65327 | 52.28639 | 0.07963 | 7.32271 |
October | 502.00000 | 24.68776 | 51.10618 | 0.80955 | 19.82399 |
November | 489.00000 | 24.67935 | 53.13275 | 0.78626 | 18.89223 |
December | 497.00000 | 24.66237 | 51.69391 | 0.73116 | 17.14279 |
Annual Sum or Average | 5943.00000 | 24.61888 | 51.09925 | 0.47345 | 13.06460 |
Minimum of Months | 454.00000 | 24.40956 | 48.70899 | 0.04807 | 7.06700 |
Maximum of Months | 514.00000 | 24.75312 | 53.13275 | 0.80955 | 19.82399 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.41977 | 52.33496 | 0.26279 | 7.15940 |
February | 454.00000 | 23.78676 | 54.96888 | 0.39023 | 8.71615 |
March | 514.00000 | 24.08033 | 51.36650 | 0.47002 | 10.01501 |
April | 485.00000 | 24.38368 | 52.64381 | 0.59484 | 12.92673 |
May | 508.00000 | 24.52566 | 52.73626 | -0.1104 | 6.64810 |
June | 496.00000 | 24.49397 | 55.16209 | -0.0671 | 6.44907 |
July | 497.00000 | 24.64676 | 54.50036 | -0.0003 | 6.80672 |
August | 514.00000 | 24.50541 | 55.40492 | -0.0377 | 6.45081 |
September | 485.00000 | 24.54168 | 55.68146 | -0.0836 | 6.65844 |
October | 502.00000 | 24.51434 | 54.32793 | 0.66327 | 14.85801 |
November | 489.00000 | 24.30444 | 55.84809 | 0.57321 | 12.16194 |
December | 497.00000 | 23.76479 | 55.91032 | 0.38935 | 8.73094 |
Annual Sum or Average | 5943.00000 | 24.24995 | 54.22399 | 0.25182 | 8.95465 |
Minimum of Months | 454.00000 | 23.41977 | 51.36650 | -0.1104 | 6.44907 |
Maximum of Months | 514.00000 | 24.64676 | 55.91032 | 0.66327 | 14.85801 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.82889 | 50.34449 | 0.36877 | 8.60401 |
February | 385.00000 | 24.11373 | 53.39528 | 0.48102 | 10.51945 |
March | 433.00000 | 24.28688 | 50.22393 | 0.53679 | 11.67497 |
April | 410.00000 | 24.60805 | 51.84355 | 0.68084 | 15.68881 |
May | 430.00000 | 24.69675 | 52.19173 | 0.00185 | 7.10086 |
June | 418.00000 | 24.63289 | 54.73222 | 0.02254 | 6.90682 |
July | 422.00000 | 24.81401 | 53.82534 | 0.09815 | 7.73930 |
August | 433.00000 | 24.64691 | 54.85719 | 0.06064 | 7.04018 |
September | 410.00000 | 24.71868 | 54.97331 | 0.02727 | 7.27179 |
October | 427.00000 | 24.72764 | 53.45419 | 0.74636 | 17.71687 |
November | 417.00000 | 24.57441 | 54.57991 | 0.65782 | 14.76518 |
December | 422.00000 | 24.05500 | 54.45143 | 0.46785 | 10.19795 |
Annual Sum or Average | 5034.00000 | 24.47678 | 53.22753 | 0.34441 | 10.42382 |
Minimum of Months | 385.00000 | 23.82889 | 50.22393 | 0.00185 | 6.90682 |
Maximum of Months | 433.00000 | 24.81401 | 54.97331 | 0.74636 | 17.71687 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.19200 | 49.13512 | 0.50255 | 11.38633 |
February | 454.00000 | 24.25711 | 52.74060 | 0.56057 | 12.44409 |
March | 514.00000 | 24.28337 | 50.30872 | 0.56366 | 12.28198 |
April | 485.00000 | 24.45783 | 52.23782 | 0.63537 | 14.15406 |
May | 508.00000 | 24.52200 | 52.74612 | -0.1108 | 6.65091 |
June | 496.00000 | 24.47371 | 55.28163 | -0.0887 | 6.43809 |
July | 497.00000 | 24.63759 | 54.53547 | -0.0081 | 6.77443 |
August | 514.00000 | 24.52001 | 55.28186 | -0.0117 | 6.52446 |
September | 485.00000 | 24.60331 | 55.23294 | 0.00046 | 6.90058 |
October | 502.00000 | 24.66387 | 53.40179 | 0.77229 | 18.55276 |
November | 489.00000 | 24.59069 | 54.34960 | 0.72678 | 16.98712 |
December | 497.00000 | 24.34430 | 53.19828 | 0.59357 | 13.40657 |
Annual Sum or Average | 5943.00000 | 24.46289 | 53.19704 | 0.34203 | 11.01559 |
Minimum of Months | 454.00000 | 24.19200 | 49.13512 | -0.1108 | 6.43809 |
Maximum of Months | 514.00000 | 24.66387 | 55.28186 | 0.77229 | 18.55276 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.87404 | 50.53792 | 0.38951 | 8.96739 |
February | 454.00000 | 24.13657 | 53.40635 | 0.50379 | 10.93640 |
March | 514.00000 | 24.30936 | 50.27325 | 0.56909 | 12.37779 |
April | 485.00000 | 24.54703 | 51.84224 | 0.68528 | 15.74525 |
May | 508.00000 | 24.60409 | 52.35135 | -0.0123 | 6.98461 |
June | 496.00000 | 24.55731 | 54.78025 | 0.02548 | 6.85763 |
July | 497.00000 | 24.70633 | 54.14369 | 0.09351 | 7.49893 |
August | 514.00000 | 24.56541 | 54.98908 | 0.07224 | 7.03359 |
September | 485.00000 | 24.62863 | 55.12340 | 0.02379 | 7.13200 |
October | 502.00000 | 24.64265 | 53.67169 | 0.74494 | 17.61941 |
November | 489.00000 | 24.49814 | 54.88877 | 0.66355 | 14.86806 |
December | 497.00000 | 24.15729 | 54.15358 | 0.51050 | 11.08678 |
Annual Sum or Average | 5943.00000 | 24.43704 | 53.33547 | 0.35383 | 10.57408 |
Minimum of Months | 454.00000 | 23.87404 | 50.27325 | -0.0123 | 6.85763 |
Maximum of Months | 514.00000 | 24.70633 | 55.12340 | 0.74494 | 17.61941 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.07118 | 53.54682 | 0.17621 | 6.95495 |
February | 454.00000 | 23.56682 | 55.81102 | 0.33666 | 8.35048 |
March | 514.00000 | 23.98435 | 51.89486 | 0.44928 | 9.84800 |
April | 485.00000 | 24.37036 | 52.90998 | 0.59863 | 13.16280 |
May | 508.00000 | 24.54139 | 52.90791 | -0.0859 | 6.79425 |
June | 496.00000 | 24.50664 | 55.35179 | -0.0411 | 6.58661 |
July | 497.00000 | 24.66509 | 54.67959 | 0.03296 | 7.12214 |
August | 514.00000 | 24.52113 | 55.62646 | -0.0076 | 6.65162 |
September | 485.00000 | 24.55764 | 55.96783 | -0.0588 | 6.83559 |
October | 502.00000 | 24.51977 | 54.71418 | 0.67385 | 15.23341 |
November | 489.00000 | 24.26674 | 56.37500 | 0.56540 | 12.09431 |
December | 497.00000 | 23.53084 | 56.91297 | 0.33164 | 8.28823 |
Annual Sum or Average | 5943.00000 | 24.17870 | 54.70596 | 0.24602 | 8.98557 |
Minimum of Months | 454.00000 | 23.07118 | 51.89486 | -0.0859 | 6.58661 |
Maximum of Months | 514.00000 | 24.66509 | 56.91297 | 0.67385 | 15.23341 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.58419 | 51.61854 | 0.31133 | 8.19282 |
February | 454.00000 | 23.92239 | 54.22706 | 0.44167 | 9.97122 |
March | 514.00000 | 24.16572 | 50.96311 | 0.52199 | 11.42737 |
April | 485.00000 | 24.49540 | 52.08530 | 0.67348 | 15.44512 |
May | 508.00000 | 24.59474 | 52.48933 | 0.00596 | 7.02265 |
June | 496.00000 | 24.53867 | 55.02856 | 0.03170 | 6.81627 |
July | 497.00000 | 24.70219 | 54.39442 | 0.10758 | 7.72016 |
August | 514.00000 | 24.55297 | 55.29406 | 0.07407 | 6.99556 |
September | 485.00000 | 24.61448 | 55.47423 | 0.03121 | 7.18420 |
October | 502.00000 | 24.61589 | 53.97244 | 0.74162 | 17.50345 |
November | 489.00000 | 24.45222 | 55.41423 | 0.64260 | 14.30851 |
December | 497.00000 | 23.86487 | 55.48234 | 0.42602 | 9.61695 |
Annual Sum or Average | 5943.00000 | 24.34413 | 53.85720 | 0.33240 | 10.16874 |
Minimum of Months | 454.00000 | 23.58419 | 50.96311 | 0.00596 | 6.81627 |
Maximum of Months | 514.00000 | 24.70219 | 55.48234 | 0.74162 | 17.50345 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.96006 | 49.99692 | 0.43815 | 10.65525 |
February | 454.00000 | 24.10071 | 53.39006 | 0.51879 | 11.86175 |
March | 514.00000 | 24.20456 | 50.80231 | 0.54580 | 12.06595 |
April | 485.00000 | 24.43785 | 52.51761 | 0.63743 | 14.33059 |
May | 508.00000 | 24.53790 | 52.91875 | -0.0864 | 6.80544 |
June | 496.00000 | 24.48878 | 55.46099 | -0.0616 | 6.56294 |
July | 497.00000 | 24.65754 | 54.71180 | 0.02574 | 7.08701 |
August | 514.00000 | 24.53331 | 55.51456 | 0.01730 | 6.75635 |
September | 485.00000 | 24.61176 | 55.54906 | 0.02196 | 7.16112 |
October | 502.00000 | 24.65982 | 53.81580 | 0.77979 | 18.86544 |
November | 489.00000 | 24.55493 | 54.81546 | 0.71847 | 16.79693 |
December | 497.00000 | 24.19976 | 53.88796 | 0.55225 | 12.70001 |
Annual Sum or Average | 5943.00000 | 24.41365 | 53.60634 | 0.33995 | 10.94784 |
Minimum of Months | 454.00000 | 23.96006 | 49.99692 | -0.0864 | 6.56294 |
Maximum of Months | 514.00000 | 24.65982 | 55.54906 | 0.77979 | 18.86544 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.60314 | 51.50315 | 0.32078 | 8.51162 |
February | 454.00000 | 23.97242 | 54.07386 | 0.46243 | 10.46659 |
March | 514.00000 | 24.23903 | 50.73924 | 0.55345 | 12.17682 |
April | 485.00000 | 24.53064 | 52.09948 | 0.68741 | 15.89945 |
May | 508.00000 | 24.61095 | 52.55723 | 0.00732 | 7.20436 |
June | 496.00000 | 24.56161 | 54.99912 | 0.04691 | 7.06428 |
July | 497.00000 | 24.71423 | 54.35045 | 0.12070 | 7.86968 |
August | 514.00000 | 24.57231 | 55.24116 | 0.09690 | 7.32257 |
September | 485.00000 | 24.63386 | 55.44619 | 0.04318 | 7.37794 |
October | 502.00000 | 24.63756 | 54.07937 | 0.75226 | 17.90681 |
November | 489.00000 | 24.46352 | 55.37996 | 0.65644 | 14.73991 |
December | 497.00000 | 23.99117 | 54.93347 | 0.46732 | 10.52514 |
Annual Sum or Average | 5943.00000 | 24.37966 | 53.77067 | 0.34956 | 10.57376 |
Minimum of Months | 454.00000 | 23.60314 | 50.73924 | 0.00732 | 7.06428 |
Maximum of Months | 514.00000 | 24.71423 | 55.44619 | 0.75226 | 17.90681 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.661002E+11 | 182540.58 | 30-JAN-14:00 | 451.75 | 0.657537E+12 | 0.00 | 0.723637E+12 | 6.26 | 10.67 | 19-JAN-08:30 | 0.00 | 0.00 |
February | 0.821714E+11 | 214080.06 | 07-FEB-12:05 | 423.33 | 0.776724E+12 | 0.00 | 0.858896E+12 | 6.32 | 10.66 | 13-FEB-07:10 | 0.00 | 0.00 |
March | 0.124327E+12 | 215196.90 | 29-MAR-12:10 | 565.83 | 0.112406E+13 | 0.00 | 0.124838E+13 | 7.47 | 10.66 | 20-MAR-04:12 | 0.00 | 0.00 |
April | 0.166237E+12 | 216839.00 | 03-APR-13:10 | 650.00 | 0.143220E+13 | 0.00 | 0.159843E+13 | 8.58 | 10.63 | 26-APR-01:30 | 0.00 | 0.00 |
May | 0.224644E+12 | 231238.55 | 30-MAY-03:02 | 691.00 | 0.188738E+13 | 0.00 | 0.211203E+13 | 8.33 | 10.63 | 10-MAY-03:02 | 0.00 | 0.00 |
June | 0.260220E+12 | 242325.92 | 24-JUN-17:07 | 677.31 | 0.209027E+13 | 0.00 | 0.235049E+13 | 7.90 | 10.61 | 02-JUN-03:35 | 0.00 | 0.00 |
July | 0.308212E+12 | 238935.32 | 12-JUL-05:03 | 688.59 | 0.234454E+13 | 0.00 | 0.265275E+13 | 7.36 | 10.61 | 04-JUL-07:34 | 0.00 | 0.00 |
August | 0.327533E+12 | 241557.31 | 12-AUG-17:09 | 710.30 | 0.245855E+13 | 0.00 | 0.278608E+13 | 7.47 | 10.38 | 15-AUG-22:00 | 0.00 | 0.00 |
September | 0.270252E+12 | 242154.63 | 02-SEP-17:10 | 687.54 | 0.212683E+13 | 0.00 | 0.239708E+13 | 7.89 | 10.61 | 26-SEP-04:30 | 0.00 | 0.00 |
October | 0.220842E+12 | 233034.07 | 07-OCT-17:10 | 697.13 | 0.182531E+13 | 0.00 | 0.204615E+13 | 8.35 | 10.62 | 21-OCT-03:10 | 0.00 | 0.00 |
November | 0.154595E+12 | 206907.93 | 01-NOV-17:00 | 607.33 | 0.132665E+13 | 0.00 | 0.148124E+13 | 8.00 | 10.63 | 22-NOV-04:55 | 0.00 | 0.00 |
December | 0.971134E+11 | 206104.53 | 05-DEC-13:20 | 546.54 | 0.910070E+12 | 0.00 | 0.100718E+13 | 7.39 | 10.66 | 18-DEC-06:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230225E+13 | 7396.66 | 0.189601E+14 | 0.00 | 0.212624E+14 | 7.61 | 0.00 | 0.00 | ||||
Minimum of Months | 0.661002E+11 | 182540.58 | 423.33 | 0.657537E+12 | 0.00 | 0.723637E+12 | 6.26 | 10.38 | 0.00 | 0.00 | ||
Maximum of Months | 0.327533E+12 | 242325.92 | 710.30 | 0.245855E+13 | 0.00 | 0.278608E+13 | 8.58 | 10.67 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.131090E+10 | 119300.52 | 07-FEB-13:05 | 4.25 | 0.119776E+11 | 0.00 | 0.132885E+11 | 0.06 | 9.53 | 06-FEB-15:40 | 0.00 | 0.00 |
March | 0.735216E+10 | 116632.45 | 23-MAR-11:05 | 25.79 | 0.685861E+11 | 0.00 | 0.759383E+11 | 0.33 | 11.24 | 13-MAR-15:00 | 0.00 | 0.00 |
April | 0.175251E+11 | 121891.89 | 21-APR-12:05 | 59.63 | 0.161557E+12 | 0.00 | 0.179082E+12 | 0.77 | 11.27 | 24-APR-13:10 | 0.00 | 0.00 |
May | 0.676806E+11 | 187689.58 | 30-MAY-05:05 | 199.79 | 0.585875E+12 | 0.00 | 0.653556E+12 | 2.36 | 11.21 | 08-MAY-08:70 | 0.00 | 0.00 |
June | 0.129001E+12 | 236465.27 | 18-JUN-17:42 | 333.37 | 0.105490E+13 | 0.00 | 0.118390E+13 | 3.86 | 10.91 | 21-JUN-07:50 | 0.00 | 0.00 |
July | 0.182945E+12 | 238935.32 | 12-JUL-05:03 | 396.14 | 0.139024E+13 | 0.00 | 0.157318E+13 | 4.16 | 11.13 | 03-JUL-07:30 | 0.00 | 0.00 |
August | 0.212640E+12 | 238330.39 | 23-AUG-05:03 | 435.49 | 0.158372E+13 | 0.00 | 0.179636E+13 | 4.48 | 10.65 | 15-AUG-20:50 | 0.00 | 0.00 |
September | 0.137401E+12 | 238351.05 | 11-SEP-05:03 | 334.28 | 0.109269E+13 | 0.00 | 0.123010E+13 | 3.78 | 10.70 | 02-SEP-05:03 | 0.00 | 0.00 |
October | 0.704232E+11 | 229897.72 | 02-OCT-05:02 | 202.79 | 0.603892E+12 | 0.00 | 0.674316E+12 | 2.37 | 11.27 | 19-OCT-13:10 | 0.00 | 0.00 |
November | 0.282799E+11 | 135208.11 | 01-NOV-14:05 | 90.16 | 0.252445E+12 | 0.00 | 0.280725E+12 | 1.13 | 11.27 | 13-NOV-14:10 | 0.00 | 0.00 |
December | 0.288052E+10 | 124110.88 | 04-DEC-13:05 | 10.29 | 0.264412E+11 | 0.00 | 0.293218E+11 | 0.13 | 10.91 | 06-DEC-15:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.857440E+12 | 2091.98 | 0.683233E+13 | 0.00 | 0.768977E+13 | 1.96 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.212640E+12 | 238935.32 | 435.49 | 0.158372E+13 | 0.00 | 0.179636E+13 | 4.48 | 11.27 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.912217E+11 | 744.00 | 43776.24 | 01-JAN-09:50 | 270556.07 | 12-JAN-11:10 | 24.52 | 21.11 | 16.40 |
February | 0.985067E+11 | 672.00 | 43776.24 | 01-FEB-00:10 | 391553.53 | 07-FEB-14:05 | 29.02 | 23.05 | 16.40 |
March | 0.116748E+12 | 744.00 | 43776.24 | 01-MAR-00:10 | 636224.08 | 31-MAR-23:25 | 34.73 | 26.17 | 16.40 |
April | 0.113468E+12 | 720.00 | 43776.24 | 01-APR-00:05 | 729605.92 | 28-APR-12:40 | 41.83 | 30.53 | 16.40 |
May | 0.117250E+12 | 744.00 | 43776.24 | 01-MAY-00:05 | 386694.94 | 31-MAY-23:13 | 36.83 | 32.80 | 16.40 |
June | 0.113468E+12 | 720.00 | 43776.24 | 01-JUN-00:03 | 542925.85 | 30-JUN-23:20 | 42.27 | 35.43 | 16.40 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:05 | 708579.36 | 31-JUL-23:23 | 48.26 | 38.59 | 16.40 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:03 | 766846.58 | 04-AUG-13:05 | 52.00 | 39.77 | 16.40 |
September | 0.113468E+12 | 720.00 | 43776.24 | 01-SEP-00:05 | 393960.11 | 30-SEP-23:15 | 38.30 | 34.02 | 16.40 |
October | 0.117250E+12 | 744.00 | 43776.24 | 01-OCT-00:05 | 513859.12 | 31-OCT-23:25 | 38.54 | 31.90 | 16.40 |
November | 0.113468E+12 | 720.00 | 43776.24 | 01-NOV-00:05 | 562670.45 | 01-NOV-14:05 | 37.50 | 28.67 | 16.40 |
December | 0.116846E+12 | 744.00 | 43776.24 | 01-DEC-00:05 | 678807.55 | 03-DEC-13:12 | 35.96 | 25.03 | 16.40 |
Annual Sum or Average | 0.134620E+13 | 8760.00 | 38.37 | 30.63 | 16.40 | ||||
Minimum of Months | 0.912217E+11 | 672.00 | 43776.24 | 270556.07 | 24.52 | 21.11 | 16.40 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 766846.58 | 52.00 | 39.77 | 16.40 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.265844E+10 | 384.74 | 20229.45 | 09-JAN-13:10 | 1369192.48 | 30-JAN-13:30 | 22.32 | 21.39 | 41.84 |
February | 0.614486E+10 | 384.01 | 20229.45 | 01-FEB-16:50 | 1628624.30 | 06-FEB-14:00 | 22.71 | 21.51 | 44.26 |
March | 0.115871E+11 | 495.85 | 20229.45 | 01-MAR-06:04 | 1654699.91 | 22-MAR-15:00 | 23.04 | 21.46 | 51.86 |
April | 0.256432E+11 | 595.93 | 20229.45 | 03-APR-05:04 | 1635596.63 | 06-APR-12:40 | 24.14 | 22.06 | 60.93 |
May | 0.425021E+11 | 686.19 | 20229.45 | 01-MAY-00:05 | 1625461.01 | 08-MAY-08:00 | 26.65 | 24.02 | 60.73 |
June | 0.483300E+11 | 677.31 | 20229.45 | 01-JUN-00:03 | 1631415.94 | 02-JUN-07:50 | 29.47 | 26.44 | 57.17 |
July | 0.491216E+11 | 688.51 | 20229.45 | 01-JUL-00:05 | 1639606.73 | 19-JUL-15:00 | 30.88 | 27.59 | 56.01 |
August | 0.517281E+11 | 710.30 | 20229.45 | 01-AUG-00:03 | 1670344.06 | 10-AUG-16:00 | 31.37 | 27.90 | 57.63 |
September | 0.498155E+11 | 687.54 | 20229.45 | 01-SEP-00:05 | 1551497.26 | 07-SEP-14:05 | 30.05 | 26.96 | 57.04 |
October | 0.449007E+11 | 688.01 | 20229.45 | 01-OCT-00:05 | 1609080.65 | 20-OCT-11:20 | 26.94 | 24.38 | 59.90 |
November | 0.247611E+11 | 540.52 | 20229.45 | 01-NOV-03:02 | 1605830.35 | 20-NOV-13:40 | 24.18 | 22.26 | 56.41 |
December | 0.985169E+10 | 460.75 | 20229.45 | 01-DEC-13:05 | 1482180.73 | 26-DEC-15:00 | 22.70 | 21.42 | 50.21 |
Annual Sum or Average | 0.367044E+12 | 6999.65 | 26.22 | 23.96 | 54.55 | ||||
Minimum of Months | 0.265844E+10 | 384.01 | 20229.45 | 1369192.48 | 22.32 | 21.39 | 41.84 | ||
Maximum of Months | 0.517281E+11 | 710.30 | 20229.45 | 1670344.06 | 31.37 | 27.90 | 60.93 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.109239E+09 | 1.50 | 20229.45 | 30-JAN-13:40 | 730889.79 | 30-JAN-14:00 | 22.32 | 22.31 | 0.07 |
February | 0.455949E+09 | 6.33 | 20229.45 | 06-FEB-11:40 | 1295982.87 | 06-FEB-15:10 | 22.71 | 22.68 | 0.56 |
March | 0.227963E+10 | 32.17 | 20229.45 | 01-MAR-13:05 | 1306321.64 | 23-MAR-14:30 | 23.04 | 22.88 | 2.61 |
April | 0.730023E+10 | 102.96 | 20229.45 | 03-APR-07:10 | 1353253.58 | 27-APR-09:50 | 24.14 | 23.61 | 7.89 |
May | 0.238260E+11 | 327.44 | 20229.45 | 01-MAY-07:10 | 1339269.53 | 31-MAY-16:00 | 26.65 | 25.13 | 25.41 |
June | 0.401338E+11 | 551.09 | 20229.45 | 01-JUN-07:10 | 1585602.21 | 26-JUN-05:03 | 29.47 | 26.82 | 44.46 |
July | 0.456337E+11 | 626.61 | 20229.45 | 01-JUL-00:20 | 1639606.73 | 19-JUL-15:00 | 30.88 | 27.77 | 49.97 |
August | 0.492261E+11 | 675.94 | 20229.45 | 01-AUG-00:03 | 1670344.06 | 10-AUG-16:00 | 31.37 | 28.00 | 54.28 |
September | 0.419936E+11 | 576.63 | 20229.45 | 01-SEP-00:05 | 1551497.26 | 07-SEP-14:05 | 30.05 | 27.25 | 45.87 |
October | 0.262627E+11 | 361.40 | 20229.45 | 01-OCT-00:05 | 1351508.55 | 19-OCT-12:20 | 26.94 | 25.26 | 27.31 |
November | 0.986440E+10 | 136.11 | 20229.45 | 01-NOV-05:07 | 1441407.42 | 13-NOV-14:20 | 24.18 | 23.51 | 11.28 |
December | 0.130480E+10 | 17.92 | 20229.45 | 04-DEC-09:20 | 1092571.78 | 06-DEC-13:05 | 22.70 | 22.61 | 1.37 |
Annual Sum or Average | 0.248390E+12 | 3416.10 | 26.22 | 24.83 | 22.72 | ||||
Minimum of Months | 0.109239E+09 | 1.50 | 20229.45 | 730889.79 | 22.32 | 22.31 | 0.07 | ||
Maximum of Months | 0.492261E+11 | 675.94 | 20229.45 | 1670344.06 | 31.37 | 28.00 | 54.28 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 24.52 | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 29.02 | 29.02 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 34.73 | 34.73 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 41.83 | 41.83 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 36.83 | 36.83 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 42.27 | 42.27 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 48.26 | 48.26 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 52.00 | 52.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 38.30 | 38.30 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 38.54 | 38.54 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 37.50 | 37.50 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 35.96 | 35.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 38.37 | 38.37 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.52 | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.00 | 52.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.659805E+11 | 0.00 | 430.78 | 0.632312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 224274.84 | 30-JAN-05:12 | 156540.21 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.830377E+11 | 0.00 | 408.44 | 0.770555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 249865.19 | 09-FEB-05:11 | 165995.61 | 09-FEB-05:11 | 0.00 | 0.00 | 0.00 |
March | 0.128488E+12 | 0.00 | 550.53 | 0.120165E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 234376.65 | 24-MAR-04:12 | 173979.20 | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.176376E+12 | 0.00 | 620.15 | 0.156271E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 228822.89 | 30-APR-16:22 | 176589.24 | 29-APR-03:12 | 0.00 | 0.00 | 0.00 |
May | 0.257036E+12 | 0.00 | 645.17 | 0.217784E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 302040.70 | 30-MAY-03:02 | 194942.70 | 21-MAY-15:41 | 0.00 | 0.00 | 0.00 |
June | 0.319457E+12 | 0.00 | 638.20 | 0.240362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 310847.51 | 19-JUN-03:02 | 194982.77 | 05-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.378905E+12 | 0.00 | 652.09 | 0.270458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 327522.74 | 24-JUL-03:02 | 208639.27 | 04-JUL-15:42 | 0.00 | 0.00 | 0.00 |
August | 0.420111E+12 | 0.00 | 659.30 | 0.300066E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 326393.62 | 27-AUG-14:21 | 222007.57 | 06-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.329700E+12 | 0.00 | 630.79 | 0.233681E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 331983.13 | 10-SEP-17:42 | 221389.64 | 04-SEP-15:42 | 0.00 | 0.00 | 0.00 |
October | 0.274492E+12 | 0.00 | 643.46 | 0.214577E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 306399.23 | 02-OCT-03:02 | 210099.04 | 09-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.173588E+12 | 0.00 | 575.89 | 0.147232E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 249162.23 | 03-NOV-04:12 | 170548.60 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 |
December | 0.109327E+12 | 0.00 | 524.25 | 0.977051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 228575.82 | 12-DEC-05:12 | 162748.31 | 12-DEC-05:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271650E+13 | 0.00 | 6979.05 | 0.213859E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.659805E+11 | 0.00 | 408.44 | 0.632312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 224274.84 | 156540.21 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.420111E+12 | 0.00 | 659.30 | 0.300066E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 331983.13 | 222007.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.471943E+12 | 0.00 | 409.75 | 0.449866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1830104.22 | 30-JAN-06:02 | 1219923.49 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.576262E+12 | 0.00 | 380.11 | 0.528391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2050625.12 | 06-FEB-05:11 | 1418032.63 | 06-FEB-05:11 | 0.00 | 0.00 | 0.00 |
March | 0.880244E+12 | 0.00 | 461.00 | 0.815358E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2039518.57 | 01-MAR-06:02 | 1605944.57 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.119882E+13 | 0.00 | 486.87 | 0.104775E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2087280.87 | 10-APR-04:12 | 1536269.32 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.196357E+13 | 0.00 | 604.58 | 0.160361E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2721967.57 | 24-MAY-05:02 | 1642761.41 | 11-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.253204E+13 | 0.00 | 622.92 | 0.175605E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2902405.58 | 04-JUN-16:41 | 1723453.21 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.303350E+13 | 0.00 | 646.66 | 0.195813E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3181062.67 | 30-JUL-16:22 | 1759732.86 | 30-JUL-13:42 | 0.00 | 0.00 | 0.00 |
August | 0.328584E+13 | 0.00 | 655.40 | 0.210080E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3021160.18 | 01-AUG-05:01 | 1874818.01 | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.260503E+13 | 0.00 | 601.78 | 0.167269E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3117058.35 | 10-SEP-16:52 | 1782644.94 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.190632E+13 | 0.00 | 551.15 | 0.139415E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2738255.28 | 07-OCT-05:02 | 1629571.30 | 06-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.119330E+13 | 0.00 | 451.24 | 0.977640E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2123095.39 | 04-NOV-04:12 | 1552929.89 | 20-NOV-04:02 | 0.00 | 0.00 | 0.00 |
December | 0.670524E+12 | 0.00 | 419.71 | 0.588465E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1951536.59 | 12-DEC-06:03 | 1335938.19 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203174E+14 | 0.00 | 6291.17 | 0.148929E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.471943E+12 | 0.00 | 380.11 | 0.449866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1830104.22 | 1219923.49 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.328584E+13 | 0.00 | 655.40 | 0.210080E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3181062.67 | 1874818.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.426780E+11 | 0.00 | 401.86 | 0.404979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176024.70 | 30-JAN-06:02 | 115130.25 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.558652E+11 | 0.00 | 374.14 | 0.510935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 207526.91 | 06-FEB-05:11 | 137439.84 | 06-FEB-05:11 | 0.00 | 0.00 | 0.00 |
March | 0.887835E+11 | 0.00 | 451.61 | 0.822861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 201769.68 | 01-MAR-06:02 | 184024.98 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.124808E+12 | 0.00 | 484.19 | 0.109675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 259286.52 | 30-APR-14:51 | 170981.28 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.210207E+12 | 0.00 | 606.16 | 0.173980E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 308381.35 | 30-MAY-04:03 | 190633.64 | 22-MAY-04:23 | 0.00 | 0.00 | 0.00 |
June | 0.268905E+12 | 0.00 | 625.31 | 0.191122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 315219.51 | 04-JUN-16:51 | 195623.80 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.321842E+12 | 0.00 | 647.85 | 0.214569E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 345479.52 | 30-JUL-16:22 | 205050.24 | 24-JUL-04:22 | 0.00 | 0.00 | 0.00 |
August | 0.346954E+12 | 0.00 | 656.01 | 0.229013E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 334623.44 | 01-AUG-05:01 | 211680.16 | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.272762E+12 | 0.00 | 604.70 | 0.179506E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 322409.24 | 11-SEP-05:02 | 232849.37 | 04-SEP-15:31 | 0.00 | 0.00 | 0.00 |
October | 0.195642E+12 | 0.00 | 550.36 | 0.144554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 298918.45 | 07-OCT-05:02 | 179315.39 | 06-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.118315E+12 | 0.00 | 446.53 | 0.969432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 226328.82 | 02-NOV-04:12 | 166648.63 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.631197E+11 | 0.00 | 410.53 | 0.550812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 194603.72 | 11-DEC-06:03 | 127164.33 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210988E+13 | 0.00 | 6259.24 | 0.156832E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.426780E+11 | 0.00 | 374.14 | 0.404979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176024.70 | 115130.25 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.346954E+12 | 0.00 | 656.01 | 0.229013E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 345479.52 | 232849.37 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.647317E+11 | 0.00 | 397.81 | 0.625269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141107.33 | 30-JAN-07:51 | 110422.97 | 01-JAN-18:32 | 0.00 | 0.00 | 0.00 |
February | 0.557204E+11 | 0.00 | 301.79 | 0.528386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 254032.84 | 09-FEB-16:52 | 106777.66 | 10-FEB-05:11 | 0.00 | 0.00 | 0.00 |
March | 0.591253E+11 | 0.00 | 276.49 | 0.532410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 258687.15 | 29-MAR-03:55 | 100423.40 | 03-MAR-06:03 | 0.00 | 0.00 | 0.00 |
April | 0.398288E+11 | 0.00 | 143.76 | 0.328570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 270929.52 | 30-APR-03:03 | 99461.97 | 10-APR-12:10 | 0.00 | 0.00 | 0.00 |
May | 0.673392E+10 | 0.00 | 16.33 | 0.511817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 182171.75 | 01-MAY-04:22 | 105652.39 | 01-MAY-11:00 | 0.00 | 0.00 | 0.00 |
June | 0.673713E+10 | 0.00 | 13.17 | 0.499192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 271847.27 | 22-JUN-07:52 | 117278.62 | 22-JUN-12:00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 |
October | 0.131663E+11 | 0.00 | 29.71 | 0.103149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 276767.61 | 29-OCT-02:25 | 116287.97 | 21-OCT-12:05 | 0.00 | 0.00 | 0.00 |
November | 0.635228E+11 | 0.00 | 191.68 | 0.521656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 269672.82 | 04-NOV-04:33 | 110405.96 | 06-NOV-03:45 | 0.00 | 0.00 | 0.00 |
December | 0.697030E+11 | 0.00 | 341.64 | 0.634370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 249916.40 | 12-DEC-20:31 | 106996.61 | 12-DEC-22:17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379269E+12 | 0.00 | 1712.40 | 0.337491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.697030E+11 | 0.00 | 397.81 | 0.634370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 276767.61 | 117278.62 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.353244E+12 | 0.858870E+11 | 744.00 | 0.342500E+12 | 0.107442E+11 | 0.00 | 0.33 | 23-JAN-14:00 | 0.29 | 21-JAN-05:55 | 142180.98 | 30-JAN-15:00 | 133435.21 | 23-JAN-14:00 | 10935.52 | 30-JAN-15:00 | 41901.02 | 23-JAN-14:00 | 0.00 |
February | 0.544231E+12 | 0.134116E+12 | 672.00 | 0.531136E+12 | 0.130956E+11 | 0.00 | 0.56 | 06-FEB-15:00 | 0.48 | 01-FEB-05:00 | 236714.85 | 07-FEB-16:10 | 227010.12 | 06-FEB-15:00 | 11712.43 | 07-FEB-16:10 | 77937.09 | 06-FEB-15:00 | 0.00 |
March | 0.848318E+12 | 0.221264E+12 | 744.00 | 0.835534E+12 | 0.127838E+11 | 0.00 | 0.87 | 31-MAR-23:15 | 0.66 | 08-MAR-06:00 | 407952.87 | 31-MAR-23:05 | 397758.22 | 31-MAR-24:00 | 12100.31 | 28-MAR-16:00 | 124980.53 | 27-MAR-11:00 | 0.00 |
April | 0.106253E+13 | 0.302331E+12 | 720.00 | 0.104903E+13 | 0.134982E+11 | 0.00 | 1.00 | 26-APR-10:00 | 0.37 | 30-APR-23:15 | 421680.79 | 30-APR-14:53 | 418540.50 | 28-APR-12:40 | 15914.35 | 10-APR-10:00 | 170486.70 | 28-APR-12:00 | 0.00 |
May | 0.376608E+12 | 0.126775E+12 | 744.00 | 0.358667E+12 | 0.179414E+11 | 0.00 | 0.55 | 31-MAY-23:13 | 0.31 | 03-MAY-06:00 | 230993.11 | 31-MAY-23:03 | 220622.68 | 31-MAY-23:57 | 15786.47 | 30-MAY-00:55 | 78567.68 | 31-MAY-23:13 | 0.00 |
June | 0.614262E+12 | 0.210194E+12 | 720.00 | 0.586444E+12 | 0.278188E+11 | 0.00 | 0.75 | 30-JUN-24:00 | 0.52 | 22-JUN-08:00 | 329051.66 | 30-JUN-23:03 | 311981.22 | 30-JUN-23:57 | 18737.67 | 08-JUN-13:00 | 106113.23 | 30-JUN-24:00 | 0.00 |
July | 0.889514E+12 | 0.316387E+12 | 744.00 | 0.856036E+12 | 0.334776E+11 | 0.00 | 0.96 | 31-JUL-23:03 | 0.73 | 03-JUL-06:00 | 425123.79 | 31-JUL-23:03 | 405573.45 | 31-JUL-24:00 | 22563.31 | 20-JUL-11:00 | 151165.64 | 21-JUL-12:00 | 0.00 |
August | 0.113750E+13 | 0.401812E+12 | 744.00 | 0.110298E+13 | 0.345169E+11 | 0.00 | 1.00 | 01-AUG-10:05 | 0.39 | 31-AUG-23:13 | 444636.27 | 04-AUG-14:00 | 420975.72 | 10-AUG-21:01 | 24659.87 | 04-AUG-14:00 | 181702.44 | 16-AUG-12:00 | 0.00 |
September | 0.384015E+12 | 0.131493E+12 | 720.00 | 0.353367E+12 | 0.306474E+11 | 0.00 | 0.56 | 30-SEP-23:05 | 0.33 | 30-SEP-05:20 | 242336.18 | 30-SEP-23:05 | 220389.31 | 30-SEP-24:00 | 22722.63 | 30-SEP-23:05 | 73017.86 | 30-SEP-23:15 | 0.00 |
October | 0.630464E+12 | 0.197503E+12 | 744.00 | 0.606223E+12 | 0.242409E+11 | 0.00 | 0.72 | 31-OCT-23:20 | 0.51 | 29-OCT-07:00 | 319457.14 | 31-OCT-23:05 | 311021.85 | 31-OCT-24:00 | 18948.26 | 07-OCT-10:10 | 93374.10 | 31-OCT-23:20 | 0.00 |
November | 0.834289E+12 | 0.232298E+12 | 720.00 | 0.817148E+12 | 0.171410E+11 | 0.00 | 0.78 | 01-NOV-14:00 | 0.67 | 26-NOV-05:00 | 334774.11 | 01-NOV-15:00 | 320682.57 | 13-NOV-15:00 | 15600.03 | 01-NOV-15:00 | 112243.47 | 01-NOV-14:00 | 0.00 |
December | 0.109985E+13 | 0.267728E+12 | 744.00 | 0.108247E+13 | 0.173728E+11 | 0.00 | 0.92 | 10-DEC-12:20 | 0.84 | 30-DEC-05:55 | 421128.92 | 05-DEC-17:00 | 409291.77 | 11-DEC-16:20 | 13803.87 | 26-DEC-07:40 | 127335.45 | 10-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.877482E+13 | 0.262779E+13 | 8760.00 | 0.852154E+13 | 0.253279E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.353244E+12 | 0.858870E+11 | 672.00 | 0.342500E+12 | 0.107442E+11 | 0.00 | 0.33 | 0.29 | 142180.98 | 133435.21 | 10935.52 | 41901.02 | 0.00 | ||||||
Maximum of Months | 0.113750E+13 | 0.401812E+12 | 744.00 | 0.110298E+13 | 0.345169E+11 | 0.00 | 1.00 | 0.84 | 444636.27 | 420975.72 | 24659.87 | 181702.44 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.552151E+10 | 0.132898E+10 | 744.00 | 0.518336E+10 | 0.338154E+09 | 0.00 | 0.32 | 29-JAN-17:25 | 0.19 | 21-JAN-08:00 | 2623.58 | 29-JAN-17:35 | 2360.29 | 29-JAN-17:40 | 417.40 | 30-JAN-15:05 | 718.58 | 23-JAN-14:00 | 0.00 |
February | 0.994741E+10 | 0.239822E+10 | 672.00 | 0.949677E+10 | 0.450642E+09 | 0.00 | 0.57 | 05-FEB-16:03 | 0.42 | 01-FEB-07:00 | 4744.84 | 07-FEB-16:10 | 4432.43 | 05-FEB-17:27 | 489.79 | 07-FEB-16:10 | 1463.57 | 05-FEB-15:40 | 0.00 |
March | 0.162563E+11 | 0.413339E+10 | 744.00 | 0.157874E+11 | 0.468923E+09 | 0.00 | 0.90 | 31-MAR-23:05 | 0.63 | 08-MAR-07:00 | 8098.75 | 31-MAR-23:05 | 7634.15 | 31-MAR-24:00 | 494.58 | 28-MAR-16:10 | 2367.71 | 27-MAR-11:00 | 0.00 |
April | 0.210560E+11 | 0.579485E+10 | 720.00 | 0.204501E+11 | 0.605932E+09 | 0.00 | 1.00 | 02-APR-13:32 | 0.39 | 30-APR-23:43 | 8849.21 | 30-APR-21:33 | 8453.39 | 23-APR-16:40 | 589.70 | 30-APR-15:00 | 3161.32 | 28-APR-12:00 | 0.00 |
May | 0.733537E+10 | 0.237383E+10 | 744.00 | 0.659858E+10 | 0.736794E+09 | 0.00 | 0.59 | 31-MAY-23:13 | 0.27 | 03-MAY-07:00 | 4736.75 | 31-MAY-23:03 | 4333.34 | 31-MAY-23:57 | 662.11 | 30-MAY-02:00 | 1539.36 | 31-MAY-23:13 | 0.00 |
June | 0.126220E+11 | 0.412295E+10 | 720.00 | 0.114208E+11 | 0.120121E+10 | 0.00 | 0.81 | 30-JUN-23:03 | 0.52 | 03-JUN-06:30 | 6901.31 | 30-JUN-23:03 | 6167.12 | 30-JUN-23:57 | 802.03 | 30-JUN-23:03 | 2105.73 | 30-JUN-23:53 | 0.00 |
July | 0.186869E+11 | 0.632242E+10 | 744.00 | 0.171912E+11 | 0.149577E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.74 | 03-JUL-06:40 | 8654.03 | 31-JUL-24:00 | 7966.64 | 31-JUL-24:00 | 964.29 | 20-JUL-14:00 | 3001.57 | 30-JUL-14:00 | 0.00 |
August | 0.228770E+11 | 0.761807E+10 | 744.00 | 0.213277E+11 | 0.154934E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.39 | 31-AUG-23:05 | 8928.92 | 27-AUG-06:00 | 8290.58 | 06-AUG-05:00 | 963.55 | 30-AUG-20:00 | 3371.49 | 16-AUG-12:00 | 0.00 |
September | 0.786045E+10 | 0.255353E+10 | 720.00 | 0.658139E+10 | 0.127905E+10 | 0.00 | 0.61 | 30-SEP-23:05 | 0.30 | 26-SEP-07:00 | 5219.45 | 30-SEP-23:05 | 4262.38 | 30-SEP-24:00 | 990.39 | 30-SEP-23:05 | 1471.00 | 30-SEP-23:15 | 0.00 |
October | 0.126213E+11 | 0.379794E+10 | 744.00 | 0.115863E+11 | 0.103504E+10 | 0.00 | 0.74 | 31-OCT-24:00 | 0.49 | 21-OCT-07:00 | 6329.84 | 31-OCT-23:05 | 5986.68 | 31-OCT-24:00 | 852.32 | 07-OCT-10:10 | 1844.94 | 09-OCT-15:12 | 0.00 |
November | 0.163326E+11 | 0.440277E+10 | 720.00 | 0.155994E+11 | 0.733161E+09 | 0.00 | 0.82 | 01-NOV-14:05 | 0.66 | 22-NOV-07:00 | 6914.23 | 01-NOV-16:00 | 6625.48 | 12-NOV-17:17 | 673.13 | 01-NOV-15:00 | 2201.47 | 01-NOV-14:00 | 0.00 |
December | 0.212434E+11 | 0.503511E+10 | 744.00 | 0.206675E+11 | 0.575952E+09 | 0.00 | 0.96 | 03-DEC-16:53 | 0.81 | 30-DEC-08:00 | 8571.07 | 05-DEC-17:00 | 8197.99 | 03-DEC-17:07 | 578.34 | 05-DEC-17:00 | 2445.76 | 10-DEC-12:53 | 0.00 |
Annual Sum or Average | 0.172360E+12 | 0.498821E+11 | 8760.00 | 0.161890E+12 | 0.104700E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.552151E+10 | 0.132898E+10 | 672.00 | 0.518336E+10 | 0.338154E+09 | 0.00 | 0.32 | 0.19 | 2623.58 | 2360.29 | 417.40 | 718.58 | 0.00 | ||||||
Maximum of Months | 0.228770E+11 | 0.761807E+10 | 744.00 | 0.213277E+11 | 0.154934E+10 | 0.00 | 1.00 | 0.81 | 8928.92 | 8453.39 | 990.39 | 3371.49 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.458040E+11 | 0.111601E+11 | 744.00 | 0.425667E+11 | 0.323725E+10 | 0.00 | 0.30 | 29-JAN-17:35 | 0.15 | 21-JAN-08:00 | 23497.93 | 30-JAN-15:00 | 20732.09 | 29-JAN-17:40 | 4071.08 | 30-JAN-15:05 | 6486.97 | 23-JAN-14:00 | 0.00 |
February | 0.903951E+11 | 0.219198E+11 | 672.00 | 0.859457E+11 | 0.444943E+10 | 0.00 | 0.56 | 07-FEB-16:10 | 0.39 | 13-FEB-07:00 | 45005.54 | 07-FEB-16:10 | 40908.02 | 06-FEB-15:40 | 4860.62 | 07-FEB-16:10 | 13792.53 | 06-FEB-15:00 | 0.00 |
March | 0.152822E+12 | 0.389542E+11 | 744.00 | 0.148159E+12 | 0.466224E+10 | 0.00 | 0.90 | 31-MAR-23:05 | 0.60 | 08-MAR-07:00 | 77851.67 | 31-MAR-23:05 | 73285.78 | 31-MAR-24:00 | 4914.25 | 28-MAR-16:10 | 22571.57 | 27-MAR-11:00 | 0.00 |
April | 0.200092E+12 | 0.551015E+11 | 720.00 | 0.194046E+12 | 0.604629E+10 | 0.00 | 1.00 | 24-APR-12:00 | 0.33 | 30-APR-23:55 | 83767.97 | 30-APR-17:55 | 79227.71 | 23-APR-17:20 | 5922.98 | 30-APR-15:00 | 30169.12 | 28-APR-12:00 | 0.00 |
May | 0.668883E+11 | 0.217102E+11 | 744.00 | 0.596651E+11 | 0.722322E+10 | 0.00 | 0.58 | 31-MAY-23:03 | 0.26 | 03-MAY-07:00 | 45067.22 | 31-MAY-23:03 | 40805.97 | 31-MAY-23:57 | 6447.53 | 30-MAY-02:00 | 14615.72 | 31-MAY-23:13 | 0.00 |
June | 0.117886E+12 | 0.385624E+11 | 720.00 | 0.105978E+12 | 0.119081E+11 | 0.00 | 0.81 | 30-JUN-23:03 | 0.51 | 03-JUN-06:50 | 65885.16 | 30-JUN-23:03 | 58122.46 | 30-JUN-23:57 | 8093.27 | 30-JUN-23:03 | 19947.87 | 30-JUN-23:15 | 0.00 |
July | 0.174884E+12 | 0.592656E+11 | 744.00 | 0.160002E+12 | 0.148821E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.73 | 03-JUL-06:00 | 82550.59 | 31-JUL-24:00 | 75592.07 | 31-JUL-24:00 | 9594.53 | 20-JUL-14:00 | 27682.54 | 21-JUL-12:00 | 0.00 |
August | 0.217536E+12 | 0.726551E+11 | 744.00 | 0.201993E+12 | 0.155434E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.35 | 31-AUG-23:05 | 84628.21 | 08-AUG-04:53 | 78194.27 | 06-AUG-05:00 | 9609.28 | 30-AUG-20:00 | 32174.25 | 16-AUG-12:00 | 0.00 |
September | 0.712518E+11 | 0.231869E+11 | 720.00 | 0.587087E+11 | 0.125430E+11 | 0.00 | 0.60 | 30-SEP-23:05 | 0.28 | 26-SEP-07:00 | 49428.86 | 30-SEP-23:05 | 39461.35 | 30-SEP-23:33 | 10212.82 | 30-SEP-23:05 | 13870.78 | 30-SEP-23:05 | 0.00 |
October | 0.117081E+12 | 0.352986E+11 | 744.00 | 0.106835E+12 | 0.102465E+11 | 0.00 | 0.75 | 31-OCT-24:00 | 0.47 | 21-OCT-07:00 | 60735.69 | 31-OCT-23:05 | 57242.77 | 31-OCT-24:00 | 8454.26 | 07-OCT-10:10 | 17059.76 | 31-OCT-23:20 | 0.00 |
November | 0.153708E+12 | 0.415016E+11 | 720.00 | 0.146417E+12 | 0.729094E+10 | 0.00 | 0.82 | 01-NOV-14:00 | 0.63 | 22-NOV-07:00 | 66030.29 | 01-NOV-16:00 | 61029.67 | 05-NOV-16:54 | 6698.12 | 01-NOV-15:00 | 21025.53 | 01-NOV-14:00 | 0.00 |
December | 0.198826E+12 | 0.472817E+11 | 744.00 | 0.193085E+12 | 0.574090E+10 | 0.00 | 0.96 | 05-DEC-17:00 | 0.78 | 30-DEC-08:00 | 81846.10 | 05-DEC-17:00 | 76094.36 | 04-DEC-17:00 | 5768.96 | 05-DEC-17:00 | 22961.81 | 10-DEC-12:10 | 0.00 |
Annual Sum or Average | 0.160717E+13 | 0.466598E+12 | 8760.00 | 0.150340E+13 | 0.103773E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.458040E+11 | 0.111601E+11 | 672.00 | 0.425667E+11 | 0.323725E+10 | 0.00 | 0.30 | 0.15 | 23497.93 | 20732.09 | 4071.08 | 6486.97 | 0.00 | ||||||
Maximum of Months | 0.217536E+12 | 0.726551E+11 | 744.00 | 0.201993E+12 | 0.155434E+11 | 0.00 | 1.00 | 0.78 | 84628.21 | 79227.71 | 10212.82 | 32174.25 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.410211E+10 | 0.101284E+10 | 744.00 | 0.378732E+10 | 0.314788E+09 | 0.00 | 0.31 | 29-JAN-17:35 | 0.08 | 01-JAN-08:00 | 2394.78 | 29-JAN-17:35 | 2136.31 | 29-JAN-17:40 | 410.06 | 30-JAN-15:05 | 665.38 | 23-JAN-14:00 | 0.00 |
February | 0.878321E+10 | 0.214220E+10 | 672.00 | 0.833990E+10 | 0.443307E+09 | 0.00 | 0.57 | 07-FEB-16:10 | 0.34 | 13-FEB-08:00 | 4558.53 | 07-FEB-16:10 | 4229.59 | 05-FEB-17:27 | 487.06 | 07-FEB-16:10 | 1399.94 | 06-FEB-15:00 | 0.00 |
March | 0.151749E+11 | 0.388055E+10 | 744.00 | 0.147089E+11 | 0.466066E+09 | 0.00 | 0.89 | 31-MAR-23:05 | 0.57 | 08-MAR-07:20 | 7739.84 | 31-MAR-23:05 | 7277.72 | 31-MAR-24:00 | 491.88 | 28-MAR-16:10 | 2270.09 | 27-MAR-11:00 | 0.00 |
April | 0.200476E+11 | 0.553003E+10 | 720.00 | 0.194428E+11 | 0.604736E+09 | 0.00 | 1.00 | 02-APR-13:23 | 0.34 | 30-APR-23:25 | 8499.36 | 30-APR-17:55 | 8151.77 | 23-APR-18:00 | 587.45 | 30-APR-15:00 | 3046.09 | 28-APR-12:00 | 0.00 |
May | 0.684608E+10 | 0.222340E+10 | 744.00 | 0.611997E+10 | 0.726109E+09 | 0.00 | 0.58 | 31-MAY-23:03 | 0.25 | 03-MAY-07:00 | 4557.89 | 31-MAY-23:03 | 4136.63 | 31-MAY-23:57 | 648.89 | 30-MAY-02:00 | 1478.21 | 31-MAY-23:13 | 0.00 |
June | 0.119489E+11 | 0.391017E+10 | 720.00 | 0.107556E+11 | 0.119327E+10 | 0.00 | 0.80 | 30-JUN-23:03 | 0.50 | 03-JUN-06:50 | 6611.26 | 30-JUN-23:03 | 5839.31 | 30-JUN-23:57 | 808.34 | 30-JUN-23:03 | 2005.01 | 30-JUN-23:53 | 0.00 |
July | 0.177216E+11 | 0.600596E+10 | 744.00 | 0.162315E+11 | 0.149008E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.72 | 03-JUL-06:40 | 8326.19 | 31-JUL-24:00 | 7629.12 | 31-JUL-24:00 | 961.61 | 20-JUL-14:00 | 2873.77 | 30-JUL-14:00 | 0.00 |
August | 0.219540E+11 | 0.733271E+10 | 744.00 | 0.203997E+11 | 0.155434E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.35 | 31-AUG-23:13 | 8532.85 | 20-AUG-21:04 | 7909.37 | 06-AUG-05:00 | 966.05 | 30-AUG-20:00 | 3248.62 | 16-AUG-12:00 | 0.00 |
September | 0.727804E+10 | 0.237025E+10 | 720.00 | 0.601837E+10 | 0.125967E+10 | 0.00 | 0.60 | 30-SEP-23:05 | 0.27 | 26-SEP-07:00 | 4994.42 | 30-SEP-23:05 | 3992.45 | 30-SEP-23:30 | 1010.38 | 30-SEP-23:05 | 1403.09 | 30-SEP-23:05 | 0.00 |
October | 0.117811E+11 | 0.355609E+10 | 744.00 | 0.107555E+11 | 0.102556E+10 | 0.00 | 0.74 | 31-OCT-24:00 | 0.45 | 21-OCT-07:00 | 6069.44 | 31-OCT-23:05 | 5723.82 | 31-OCT-24:00 | 848.07 | 07-OCT-10:10 | 1723.40 | 09-OCT-15:30 | 0.00 |
November | 0.153075E+11 | 0.414333E+10 | 720.00 | 0.145787E+11 | 0.728836E+09 | 0.00 | 0.82 | 01-NOV-14:05 | 0.61 | 22-NOV-07:30 | 6655.10 | 01-NOV-15:00 | 6259.56 | 05-NOV-16:34 | 670.70 | 01-NOV-15:00 | 2118.73 | 01-NOV-14:00 | 0.00 |
December | 0.195883E+11 | 0.467812E+10 | 744.00 | 0.190147E+11 | 0.573552E+09 | 0.00 | 0.96 | 05-DEC-17:00 | 0.73 | 31-DEC-08:00 | 8210.34 | 05-DEC-17:00 | 7653.39 | 03-DEC-17:07 | 576.84 | 05-DEC-17:00 | 2303.99 | 10-DEC-12:53 | 0.00 |
Annual Sum or Average | 0.160533E+12 | 0.467856E+11 | 8760.00 | 0.150153E+12 | 0.103803E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.410211E+10 | 0.101284E+10 | 672.00 | 0.378732E+10 | 0.314788E+09 | 0.00 | 0.31 | 0.08 | 2394.78 | 2136.31 | 410.06 | 665.38 | 0.00 | ||||||
Maximum of Months | 0.219540E+11 | 0.733271E+10 | 744.00 | 0.203997E+11 | 0.155434E+10 | 0.00 | 1.00 | 0.73 | 8532.85 | 8151.77 | 1010.38 | 3248.62 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 120.27 | 277.74 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 168.87 | 235.84 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 247.35 | 178.45 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 358.92 | 113.20 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 542.17 | 32.93 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 623.66 | 11.62 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 687.26 | 0.76 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 671.74 | 0.28 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 508.46 | 14.95 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 363.32 | 58.04 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 231.87 | 133.23 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 134.08 | 233.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 389.50 | 106.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 120.27 | 0.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 687.26 | 277.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 120.27 | 277.74 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 168.87 | 235.84 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 247.35 | 178.45 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 358.92 | 113.20 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 542.17 | 32.93 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 623.66 | 11.62 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 687.26 | 0.76 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 671.74 | 0.28 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 508.46 | 14.95 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 363.32 | 58.04 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 231.87 | 133.23 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 134.08 | 233.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 389.50 | 106.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 120.27 | 0.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 687.26 | 277.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 120.27 | 277.74 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 168.87 | 235.84 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 247.35 | 178.45 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 358.92 | 113.20 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 542.17 | 32.93 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 623.66 | 11.62 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 687.26 | 0.76 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 671.74 | 0.28 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 508.46 | 14.95 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 363.32 | 58.04 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 231.87 | 133.23 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 134.08 | 233.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 389.50 | 106.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 120.27 | 0.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 687.26 | 277.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 120.27 | 277.74 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 168.87 | 235.84 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 247.35 | 178.45 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 358.92 | 113.20 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 542.17 | 32.93 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 623.66 | 11.62 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 687.26 | 0.76 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 671.74 | 0.28 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 508.46 | 14.95 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 363.32 | 58.04 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 231.87 | 133.23 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 134.08 | 233.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 389.50 | 106.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 120.27 | 0.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 687.26 | 277.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 120.27 | 277.73 | 0.00 | 0.00 | 0.00 |
February | 128.46 | 0.00 | 128.46 | 168.86 | 235.83 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 247.34 | 178.44 | 0.00 | 0.00 | 0.00 |
April | 166.25 | 0.34 | 165.91 | 358.90 | 113.19 | 0.00 | 0.00 | 0.00 |
May | 187.13 | 5.49 | 181.64 | 542.15 | 32.93 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.23 | 623.63 | 11.62 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.55 | 687.23 | 0.76 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.73 | 671.71 | 0.28 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.88 | 508.44 | 14.95 | 0.00 | 0.00 | 0.00 |
October | 138.20 | 0.00 | 138.20 | 363.30 | 58.04 | 0.00 | 0.00 | 0.00 |
November | 118.64 | 0.00 | 118.64 | 231.86 | 133.22 | 0.00 | 0.00 | 0.00 |
December | 104.60 | 0.00 | 104.60 | 134.08 | 233.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 389.48 | 106.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.60 | 0.00 | 104.60 | 120.27 | 0.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.23 | 687.23 | 277.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.26 | 68.15 | 157.11 | 300.16 | 286.12 | 0.00 | 0.00 | 0.00 |
February | 245.49 | 66.53 | 178.96 | 366.94 | 243.01 | 0.00 | 0.00 | 0.00 |
March | 271.17 | 66.83 | 204.33 | 472.06 | 183.84 | 0.00 | 0.00 | 0.00 |
April | 330.15 | 96.20 | 233.96 | 675.84 | 117.27 | 0.00 | 0.00 | 0.00 |
May | 368.96 | 117.55 | 251.41 | 903.77 | 36.42 | 0.00 | 0.00 | 0.00 |
June | 361.34 | 110.50 | 250.84 | 950.34 | 12.11 | 0.00 | 0.00 | 0.00 |
July | 337.25 | 97.23 | 240.02 | 1017.21 | 0.65 | 0.00 | 0.00 | 0.00 |
August | 345.34 | 105.99 | 239.35 | 1047.86 | 0.23 | 0.00 | 0.00 | 0.00 |
September | 324.66 | 100.35 | 224.31 | 851.69 | 15.95 | 0.00 | 0.00 | 0.00 |
October | 294.60 | 96.24 | 198.35 | 669.91 | 61.02 | 0.00 | 0.00 | 0.00 |
November | 246.87 | 78.20 | 168.68 | 469.67 | 136.37 | 0.00 | 0.00 | 0.00 |
December | 199.82 | 54.82 | 145.00 | 295.08 | 234.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 296.11 | 88.31 | 207.80 | 670.10 | 109.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.82 | 54.82 | 145.00 | 295.08 | 0.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.96 | 117.55 | 251.41 | 1047.86 | 286.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.26 | 68.15 | 157.11 | 300.16 | 286.12 | 0.00 | 0.00 | 0.00 |
February | 245.49 | 66.53 | 178.96 | 366.94 | 243.01 | 0.00 | 0.00 | 0.00 |
March | 271.17 | 66.83 | 204.33 | 472.06 | 183.84 | 0.00 | 0.00 | 0.00 |
April | 330.15 | 96.20 | 233.96 | 675.84 | 117.27 | 0.00 | 0.00 | 0.00 |
May | 368.96 | 117.55 | 251.41 | 903.77 | 36.42 | 0.00 | 0.00 | 0.00 |
June | 361.34 | 110.50 | 250.84 | 950.34 | 12.11 | 0.00 | 0.00 | 0.00 |
July | 337.25 | 97.23 | 240.02 | 1017.21 | 0.65 | 0.00 | 0.00 | 0.00 |
August | 345.34 | 105.99 | 239.35 | 1047.86 | 0.23 | 0.00 | 0.00 | 0.00 |
September | 324.66 | 100.35 | 224.31 | 851.69 | 15.95 | 0.00 | 0.00 | 0.00 |
October | 294.60 | 96.24 | 198.35 | 669.91 | 61.02 | 0.00 | 0.00 | 0.00 |
November | 246.87 | 78.20 | 168.68 | 469.67 | 136.37 | 0.00 | 0.00 | 0.00 |
December | 199.82 | 54.82 | 145.00 | 295.08 | 234.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 296.11 | 88.31 | 207.80 | 670.10 | 109.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.82 | 54.82 | 145.00 | 295.08 | 0.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.96 | 117.55 | 251.41 | 1047.86 | 286.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.26 | 68.15 | 157.11 | 300.16 | 286.11 | 0.00 | 0.00 | 0.00 |
February | 245.48 | 66.53 | 178.96 | 366.93 | 243.01 | 0.00 | 0.00 | 0.00 |
March | 271.16 | 66.83 | 204.33 | 472.06 | 183.84 | 0.00 | 0.00 | 0.00 |
April | 330.15 | 96.19 | 233.95 | 675.83 | 117.27 | 0.00 | 0.00 | 0.00 |
May | 368.95 | 117.55 | 251.40 | 903.75 | 36.42 | 0.00 | 0.00 | 0.00 |
June | 361.33 | 110.50 | 250.83 | 950.32 | 12.11 | 0.00 | 0.00 | 0.00 |
July | 337.25 | 97.23 | 240.02 | 1017.20 | 0.65 | 0.00 | 0.00 | 0.00 |
August | 345.33 | 105.99 | 239.35 | 1047.84 | 0.23 | 0.00 | 0.00 | 0.00 |
September | 324.65 | 100.35 | 224.31 | 851.67 | 15.95 | 0.00 | 0.00 | 0.00 |
October | 294.59 | 96.24 | 198.35 | 669.89 | 61.02 | 0.00 | 0.00 | 0.00 |
November | 246.87 | 78.20 | 168.67 | 469.66 | 136.37 | 0.00 | 0.00 | 0.00 |
December | 199.82 | 54.82 | 144.99 | 295.08 | 234.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 296.10 | 88.30 | 207.80 | 670.09 | 109.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.82 | 54.82 | 144.99 | 295.08 | 0.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.95 | 117.55 | 251.40 | 1047.84 | 286.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 567.24 | 267.90 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 567.19 | 233.49 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 522.31 | 182.48 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 484.08 | 116.53 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 542.85 | 32.35 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 571.41 | 8.92 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 669.45 | 0.45 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 749.27 | 0.20 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 753.70 | 14.66 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 791.75 | 58.75 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 741.96 | 135.58 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 599.62 | 228.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.55 | 82.51 | 193.03 | 630.50 | 106.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 484.08 | 0.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 791.75 | 267.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 567.24 | 267.90 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 567.19 | 233.49 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 522.31 | 182.48 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 484.08 | 116.53 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 542.85 | 32.35 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 571.41 | 8.92 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 669.45 | 0.45 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 749.27 | 0.20 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 753.70 | 14.66 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 791.75 | 58.75 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 741.96 | 135.58 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 599.61 | 228.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.54 | 82.51 | 193.03 | 630.50 | 106.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 484.08 | 0.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 791.75 | 267.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 567.24 | 267.90 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 567.19 | 233.49 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 522.31 | 182.48 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 484.08 | 116.53 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 542.85 | 32.35 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 571.41 | 8.92 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 669.45 | 0.45 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 749.27 | 0.20 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 753.70 | 14.66 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 791.75 | 58.75 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 741.96 | 135.58 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 599.62 | 228.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.55 | 82.51 | 193.03 | 630.50 | 106.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 484.08 | 0.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 791.75 | 267.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 567.24 | 267.90 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 567.19 | 233.49 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 522.31 | 182.48 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 484.08 | 116.53 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 542.85 | 32.35 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 571.41 | 8.92 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 669.45 | 0.45 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 749.27 | 0.20 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 753.70 | 14.66 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 791.75 | 58.75 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 741.96 | 135.58 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 599.61 | 228.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.54 | 82.51 | 193.03 | 630.50 | 106.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 484.08 | 0.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 791.75 | 267.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.20 | 170.29 | 191.91 | 567.22 | 267.89 | 0.00 | 0.00 | 0.00 |
February | 340.12 | 139.12 | 200.99 | 567.17 | 233.48 | 0.00 | 0.00 | 0.00 |
March | 279.93 | 76.00 | 203.93 | 522.29 | 182.47 | 0.00 | 0.00 | 0.00 |
April | 220.05 | 23.33 | 196.72 | 484.06 | 116.52 | 0.00 | 0.00 | 0.00 |
May | 186.40 | 2.85 | 183.55 | 542.83 | 32.35 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.33 | 571.39 | 8.92 | 0.00 | 0.00 | 0.00 |
July | 175.54 | 1.49 | 174.05 | 669.43 | 0.45 | 0.00 | 0.00 | 0.00 |
August | 203.61 | 14.43 | 189.19 | 749.24 | 0.20 | 0.00 | 0.00 | 0.00 |
September | 268.47 | 61.53 | 206.94 | 753.67 | 14.65 | 0.00 | 0.00 | 0.00 |
October | 351.48 | 139.73 | 211.74 | 791.72 | 58.75 | 0.00 | 0.00 | 0.00 |
November | 387.75 | 186.92 | 200.83 | 741.93 | 135.57 | 0.00 | 0.00 | 0.00 |
December | 359.95 | 177.80 | 182.14 | 599.59 | 228.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.53 | 82.51 | 193.03 | 630.48 | 106.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.54 | 0.22 | 174.05 | 484.06 | 0.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.75 | 186.92 | 211.74 | 791.72 | 267.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.91 | 63.45 | 157.46 | 300.97 | 338.27 | 0.00 | 0.00 | 0.00 |
February | 252.26 | 71.93 | 180.33 | 379.32 | 299.17 | 0.00 | 0.00 | 0.00 |
March | 298.81 | 88.46 | 210.35 | 512.92 | 240.25 | 0.00 | 0.00 | 0.00 |
April | 326.55 | 91.74 | 234.81 | 650.15 | 166.31 | 0.00 | 0.00 | 0.00 |
May | 355.45 | 106.40 | 249.05 | 879.00 | 44.72 | 0.00 | 0.00 | 0.00 |
June | 367.32 | 115.79 | 251.53 | 952.66 | 16.82 | 0.00 | 0.00 | 0.00 |
July | 336.98 | 96.40 | 240.58 | 993.81 | 1.72 | 0.00 | 0.00 | 0.00 |
August | 345.70 | 105.11 | 240.59 | 1013.10 | 1.03 | 0.00 | 0.00 | 0.00 |
September | 328.85 | 103.32 | 225.54 | 858.87 | 19.44 | 0.00 | 0.00 | 0.00 |
October | 292.25 | 94.41 | 197.85 | 663.10 | 76.88 | 0.00 | 0.00 | 0.00 |
November | 251.16 | 82.14 | 169.02 | 474.13 | 184.03 | 0.00 | 0.00 | 0.00 |
December | 210.26 | 63.56 | 146.70 | 308.84 | 315.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.04 | 90.29 | 208.76 | 667.18 | 141.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.26 | 63.45 | 146.70 | 300.97 | 1.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.32 | 115.79 | 251.53 | 1013.10 | 338.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.91 | 63.45 | 157.46 | 300.97 | 338.27 | 0.00 | 0.00 | 0.00 |
February | 252.26 | 71.93 | 180.33 | 379.32 | 299.17 | 0.00 | 0.00 | 0.00 |
March | 298.81 | 88.46 | 210.35 | 512.92 | 240.25 | 0.00 | 0.00 | 0.00 |
April | 326.55 | 91.74 | 234.81 | 650.15 | 166.31 | 0.00 | 0.00 | 0.00 |
May | 355.45 | 106.40 | 249.05 | 879.00 | 44.72 | 0.00 | 0.00 | 0.00 |
June | 367.32 | 115.79 | 251.53 | 952.66 | 16.82 | 0.00 | 0.00 | 0.00 |
July | 336.98 | 96.40 | 240.58 | 993.81 | 1.72 | 0.00 | 0.00 | 0.00 |
August | 345.70 | 105.11 | 240.59 | 1013.10 | 1.03 | 0.00 | 0.00 | 0.00 |
September | 328.85 | 103.32 | 225.54 | 858.87 | 19.44 | 0.00 | 0.00 | 0.00 |
October | 292.25 | 94.41 | 197.85 | 663.10 | 76.88 | 0.00 | 0.00 | 0.00 |
November | 251.16 | 82.14 | 169.02 | 474.13 | 184.03 | 0.00 | 0.00 | 0.00 |
December | 210.26 | 63.56 | 146.70 | 308.84 | 315.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.04 | 90.29 | 208.76 | 667.18 | 141.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.26 | 63.45 | 146.70 | 300.97 | 1.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.32 | 115.79 | 251.53 | 1013.10 | 338.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.91 | 63.45 | 157.46 | 300.96 | 338.26 | 0.00 | 0.00 | 0.00 |
February | 252.26 | 71.93 | 180.32 | 379.32 | 299.16 | 0.00 | 0.00 | 0.00 |
March | 298.80 | 88.46 | 210.34 | 512.91 | 240.25 | 0.00 | 0.00 | 0.00 |
April | 326.54 | 91.74 | 234.80 | 650.14 | 166.30 | 0.00 | 0.00 | 0.00 |
May | 355.44 | 106.40 | 249.04 | 878.98 | 44.72 | 0.00 | 0.00 | 0.00 |
June | 367.32 | 115.79 | 251.53 | 952.64 | 16.82 | 0.00 | 0.00 | 0.00 |
July | 336.97 | 96.40 | 240.57 | 993.79 | 1.72 | 0.00 | 0.00 | 0.00 |
August | 345.70 | 105.11 | 240.59 | 1013.08 | 1.03 | 0.00 | 0.00 | 0.00 |
September | 328.85 | 103.31 | 225.53 | 858.86 | 19.44 | 0.00 | 0.00 | 0.00 |
October | 292.25 | 94.40 | 197.84 | 663.09 | 76.88 | 0.00 | 0.00 | 0.00 |
November | 251.15 | 82.13 | 169.02 | 474.12 | 184.03 | 0.00 | 0.00 | 0.00 |
December | 210.25 | 63.56 | 146.70 | 308.84 | 315.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.04 | 90.29 | 208.75 | 667.16 | 141.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.25 | 63.45 | 146.70 | 300.96 | 1.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.32 | 115.79 | 251.53 | 1013.08 | 338.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 560.36 | 0.00 | 560.36 | 650.76 | 1237.49 | 0.00 | 0.00 | 0.00 |
February | 642.34 | 0.00 | 642.34 | 888.97 | 1051.17 | 0.00 | 0.00 | 0.00 |
March | 737.81 | 0.00 | 737.81 | 1274.27 | 814.27 | 0.00 | 0.00 | 0.00 |
April | 831.27 | 1.71 | 829.56 | 1848.58 | 518.48 | 0.00 | 0.00 | 0.00 |
May | 935.67 | 27.44 | 908.23 | 2815.40 | 128.35 | 0.00 | 0.00 | 0.00 |
June | 1001.81 | 55.62 | 946.19 | 3253.11 | 30.52 | 0.00 | 0.00 | 0.00 |
July | 919.26 | 26.49 | 892.77 | 3627.72 | 0.71 | 0.00 | 0.00 | 0.00 |
August | 855.75 | 7.08 | 848.67 | 3575.52 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 779.51 | 0.09 | 779.42 | 2701.69 | 43.35 | 0.00 | 0.00 | 0.00 |
October | 691.02 | 0.00 | 691.02 | 1932.59 | 212.52 | 0.00 | 0.00 | 0.00 |
November | 593.23 | 0.00 | 593.23 | 1222.46 | 588.62 | 0.00 | 0.00 | 0.00 |
December | 523.03 | 0.00 | 523.03 | 724.04 | 1024.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.36 | 9.90 | 746.46 | 2050.07 | 468.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 523.03 | 0.00 | 523.03 | 650.76 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1001.81 | 55.62 | 946.19 | 3627.72 | 1237.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 675.79 | 204.46 | 471.33 | 908.64 | 803.98 | 0.00 | 0.00 | 0.00 |
February | 736.45 | 199.58 | 536.87 | 1101.56 | 689.18 | 0.00 | 0.00 | 0.00 |
March | 813.49 | 200.49 | 612.99 | 1409.53 | 537.51 | 0.00 | 0.00 | 0.00 |
April | 990.45 | 288.59 | 701.87 | 2021.76 | 351.81 | 0.00 | 0.00 | 0.00 |
May | 1106.86 | 352.65 | 754.21 | 2746.59 | 88.63 | 0.00 | 0.00 | 0.00 |
June | 1084.00 | 331.50 | 752.50 | 2903.74 | 20.36 | 0.00 | 0.00 | 0.00 |
July | 1011.74 | 291.68 | 720.06 | 3134.96 | 0.45 | 0.00 | 0.00 | 0.00 |
August | 1036.01 | 317.97 | 718.04 | 3236.81 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 973.97 | 301.04 | 672.93 | 2625.02 | 29.12 | 0.00 | 0.00 | 0.00 |
October | 883.78 | 288.73 | 595.05 | 2049.18 | 142.70 | 0.00 | 0.00 | 0.00 |
November | 740.61 | 234.59 | 506.02 | 1413.62 | 389.59 | 0.00 | 0.00 | 0.00 |
December | 599.45 | 164.47 | 434.99 | 889.56 | 669.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 888.31 | 264.91 | 623.39 | 2042.19 | 308.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.45 | 164.47 | 434.99 | 889.56 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.86 | 352.65 | 754.21 | 3236.81 | 803.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1811.03 | 851.45 | 959.59 | 2817.31 | 1303.15 | 0.00 | 0.00 | 0.00 |
February | 1700.64 | 695.64 | 1005.00 | 2822.78 | 1120.89 | 0.00 | 0.00 | 0.00 |
March | 1399.70 | 380.01 | 1019.69 | 2611.31 | 876.42 | 0.00 | 0.00 | 0.00 |
April | 1100.27 | 116.65 | 983.62 | 2449.25 | 551.70 | 0.00 | 0.00 | 0.00 |
May | 932.02 | 14.27 | 917.75 | 2805.51 | 130.31 | 0.00 | 0.00 | 0.00 |
June | 877.75 | 1.09 | 876.67 | 2993.45 | 22.64 | 0.00 | 0.00 | 0.00 |
July | 877.73 | 7.46 | 870.27 | 3518.76 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 1018.10 | 72.14 | 945.96 | 3927.55 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 1342.37 | 307.64 | 1034.73 | 3871.05 | 50.17 | 0.00 | 0.00 | 0.00 |
October | 1757.43 | 698.68 | 1058.75 | 4005.49 | 246.90 | 0.00 | 0.00 | 0.00 |
November | 1938.80 | 934.65 | 1004.15 | 3706.82 | 650.65 | 0.00 | 0.00 | 0.00 |
December | 1799.79 | 889.04 | 910.75 | 2991.30 | 1099.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1377.71 | 412.56 | 965.15 | 3212.74 | 501.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 877.73 | 1.09 | 870.27 | 2449.25 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1938.80 | 934.65 | 1058.75 | 4005.49 | 1303.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 662.73 | 190.34 | 472.39 | 937.47 | 890.99 | 0.00 | 0.00 | 0.00 |
February | 756.77 | 215.80 | 540.97 | 1177.81 | 762.72 | 0.00 | 0.00 | 0.00 |
March | 896.42 | 265.39 | 631.03 | 1581.20 | 607.35 | 0.00 | 0.00 | 0.00 |
April | 979.63 | 275.22 | 704.41 | 2006.17 | 411.19 | 0.00 | 0.00 | 0.00 |
May | 1066.33 | 319.19 | 747.13 | 2676.90 | 113.70 | 0.00 | 0.00 | 0.00 |
June | 1101.96 | 347.37 | 754.59 | 2935.51 | 29.32 | 0.00 | 0.00 | 0.00 |
July | 1010.93 | 289.21 | 721.72 | 3105.74 | 1.15 | 0.00 | 0.00 | 0.00 |
August | 1037.10 | 315.32 | 721.78 | 3192.63 | 0.38 | 0.00 | 0.00 | 0.00 |
September | 986.55 | 309.95 | 676.60 | 2635.27 | 42.73 | 0.00 | 0.00 | 0.00 |
October | 876.75 | 283.22 | 593.54 | 2044.52 | 183.48 | 0.00 | 0.00 | 0.00 |
November | 753.46 | 246.41 | 507.05 | 1473.26 | 451.72 | 0.00 | 0.00 | 0.00 |
December | 630.76 | 190.67 | 440.10 | 988.55 | 756.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 897.12 | 270.86 | 626.26 | 2068.01 | 352.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 630.76 | 190.34 | 440.10 | 937.47 | 0.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1101.96 | 347.37 | 754.59 | 3192.63 | 890.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 560.36 | 0.00 | 560.36 | 674.86 | 1160.33 | 0.00 | 0.00 | 0.00 |
February | 642.34 | 0.00 | 642.34 | 898.92 | 1003.68 | 0.00 | 0.00 | 0.00 |
March | 737.81 | 0.00 | 737.81 | 1268.06 | 794.76 | 0.00 | 0.00 | 0.00 |
April | 831.27 | 1.71 | 829.56 | 1827.88 | 521.89 | 0.00 | 0.00 | 0.00 |
May | 935.67 | 27.44 | 908.23 | 2779.02 | 134.76 | 0.00 | 0.00 | 0.00 |
June | 1001.81 | 55.62 | 946.19 | 3212.59 | 34.13 | 0.00 | 0.00 | 0.00 |
July | 919.26 | 26.49 | 892.77 | 3575.00 | 1.18 | 0.00 | 0.00 | 0.00 |
August | 855.75 | 7.08 | 848.67 | 3528.17 | 0.15 | 0.00 | 0.00 | 0.00 |
September | 779.51 | 0.09 | 779.42 | 2664.10 | 45.86 | 0.00 | 0.00 | 0.00 |
October | 691.02 | 0.00 | 691.02 | 1911.34 | 217.87 | 0.00 | 0.00 | 0.00 |
November | 593.23 | 0.00 | 593.23 | 1215.55 | 575.64 | 0.00 | 0.00 | 0.00 |
December | 523.03 | 0.00 | 523.03 | 737.53 | 973.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.36 | 9.90 | 746.46 | 2031.42 | 452.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 523.03 | 0.00 | 523.03 | 674.86 | 0.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1001.81 | 55.62 | 946.19 | 3575.00 | 1160.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 675.79 | 204.46 | 471.33 | 932.04 | 761.31 | 0.00 | 0.00 | 0.00 |
February | 736.45 | 199.58 | 536.87 | 1114.57 | 662.12 | 0.00 | 0.00 | 0.00 |
March | 813.49 | 200.49 | 612.99 | 1412.35 | 525.79 | 0.00 | 0.00 | 0.00 |
April | 990.45 | 288.59 | 701.87 | 2015.46 | 352.74 | 0.00 | 0.00 | 0.00 |
May | 1106.86 | 352.65 | 754.21 | 2730.17 | 91.87 | 0.00 | 0.00 | 0.00 |
June | 1084.00 | 331.50 | 752.50 | 2885.18 | 22.24 | 0.00 | 0.00 | 0.00 |
July | 1011.74 | 291.68 | 720.06 | 3108.43 | 0.69 | 0.00 | 0.00 | 0.00 |
August | 1036.01 | 317.97 | 718.04 | 3214.51 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 973.97 | 301.04 | 672.93 | 2608.00 | 30.26 | 0.00 | 0.00 | 0.00 |
October | 883.78 | 288.73 | 595.05 | 2041.60 | 144.59 | 0.00 | 0.00 | 0.00 |
November | 740.61 | 234.59 | 506.02 | 1415.55 | 381.35 | 0.00 | 0.00 | 0.00 |
December | 599.45 | 164.47 | 434.99 | 904.91 | 639.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 888.31 | 264.91 | 623.39 | 2037.26 | 299.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.45 | 164.47 | 434.99 | 904.91 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.86 | 352.65 | 754.21 | 3214.51 | 761.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1811.03 | 851.45 | 959.59 | 2831.31 | 1241.30 | 0.00 | 0.00 | 0.00 |
February | 1700.64 | 695.64 | 1005.00 | 2822.60 | 1080.12 | 0.00 | 0.00 | 0.00 |
March | 1399.70 | 380.01 | 1019.69 | 2599.37 | 857.65 | 0.00 | 0.00 | 0.00 |
April | 1100.27 | 116.65 | 983.62 | 2427.55 | 553.55 | 0.00 | 0.00 | 0.00 |
May | 932.02 | 14.27 | 917.75 | 2768.77 | 136.07 | 0.00 | 0.00 | 0.00 |
June | 877.75 | 1.09 | 876.67 | 2952.11 | 25.19 | 0.00 | 0.00 | 0.00 |
July | 877.73 | 7.46 | 870.27 | 3464.92 | 0.51 | 0.00 | 0.00 | 0.00 |
August | 1018.10 | 72.14 | 945.96 | 3880.04 | 0.11 | 0.00 | 0.00 | 0.00 |
September | 1342.37 | 307.64 | 1034.73 | 3832.22 | 52.53 | 0.00 | 0.00 | 0.00 |
October | 1757.43 | 698.68 | 1058.75 | 3979.30 | 250.65 | 0.00 | 0.00 | 0.00 |
November | 1938.80 | 934.65 | 1004.15 | 3692.21 | 638.61 | 0.00 | 0.00 | 0.00 |
December | 1799.79 | 889.04 | 910.75 | 2994.59 | 1059.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1377.71 | 412.56 | 965.15 | 3189.65 | 488.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 877.73 | 1.09 | 870.27 | 2427.55 | 0.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1938.80 | 934.65 | 1058.75 | 3979.30 | 1241.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 662.73 | 190.34 | 472.39 | 944.21 | 848.06 | 0.00 | 0.00 | 0.00 |
February | 756.77 | 215.80 | 540.97 | 1176.83 | 735.92 | 0.00 | 0.00 | 0.00 |
March | 896.42 | 265.39 | 631.03 | 1571.22 | 595.22 | 0.00 | 0.00 | 0.00 |
April | 979.63 | 275.22 | 704.41 | 1989.63 | 411.10 | 0.00 | 0.00 | 0.00 |
May | 1066.33 | 319.19 | 747.13 | 2653.19 | 116.93 | 0.00 | 0.00 | 0.00 |
June | 1101.96 | 347.37 | 754.59 | 2910.29 | 31.16 | 0.00 | 0.00 | 0.00 |
July | 1010.93 | 289.21 | 721.72 | 3073.98 | 1.54 | 0.00 | 0.00 | 0.00 |
August | 1037.10 | 315.32 | 721.78 | 3162.82 | 0.49 | 0.00 | 0.00 | 0.00 |
September | 986.55 | 309.95 | 676.60 | 2611.69 | 44.61 | 0.00 | 0.00 | 0.00 |
October | 876.75 | 283.22 | 593.54 | 2029.44 | 185.80 | 0.00 | 0.00 | 0.00 |
November | 753.46 | 246.41 | 507.05 | 1465.15 | 443.16 | 0.00 | 0.00 | 0.00 |
December | 630.76 | 190.67 | 440.10 | 989.81 | 727.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 897.12 | 270.86 | 626.26 | 2053.20 | 343.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 630.76 | 190.34 | 440.10 | 944.21 | 0.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1101.96 | 347.37 | 754.59 | 3162.82 | 848.06 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.322141E+09 | 0.743901E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.408534E+09 | 0.570544E+09 |
March | 0.395235E+09 | 0.00 | 0.395235E+09 | 0.662506E+09 | 0.477958E+09 |
April | 0.430936E+09 | 887921.69 | 0.430048E+09 | 0.930317E+09 | 0.293412E+09 |
May | 0.501225E+09 | 14700635.90 | 0.486525E+09 | 0.145214E+10 | 88195901.92 |
June | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.161653E+10 | 30126098.70 |
July | 0.492435E+09 | 14188242.10 | 0.478247E+09 | 0.184075E+10 | 2045975.36 |
August | 0.458415E+09 | 3791545.17 | 0.454623E+09 | 0.179918E+10 | 757933.50 |
September | 0.404104E+09 | 46306.58 | 0.404057E+09 | 0.131793E+10 | 38746393.05 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.973107E+09 | 0.155455E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.601004E+09 | 0.345330E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.359124E+09 | 0.625529E+09 |
Annual Sum or Average | 0.477055E+10 | 62447133.55 | 0.470810E+10 | 0.122833E+11 | 0.337200E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.322141E+09 | 757933.50 |
Maximum of Months | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.184075E+10 | 0.743901E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.322141E+09 | 0.743901E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.408534E+09 | 0.570543E+09 |
March | 0.395234E+09 | 0.00 | 0.395234E+09 | 0.662506E+09 | 0.477957E+09 |
April | 0.430936E+09 | 887920.63 | 0.430048E+09 | 0.930316E+09 | 0.293412E+09 |
May | 0.501225E+09 | 14700618.26 | 0.486524E+09 | 0.145214E+10 | 88195796.50 |
June | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.161653E+10 | 30126030.58 |
July | 0.492435E+09 | 14188225.07 | 0.478246E+09 | 0.184075E+10 | 2045964.35 |
August | 0.458414E+09 | 3791540.62 | 0.454623E+09 | 0.179918E+10 | 757929.19 |
September | 0.404103E+09 | 46306.53 | 0.404057E+09 | 0.131793E+10 | 38746326.25 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.973107E+09 | 0.155455E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.601004E+09 | 0.345330E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.359124E+09 | 0.625529E+09 |
Annual Sum or Average | 0.477054E+10 | 62447058.62 | 0.470809E+10 | 0.122833E+11 | 0.337200E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.322141E+09 | 757929.19 |
Maximum of Months | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.184075E+10 | 0.743901E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.322141E+09 | 0.743901E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.408534E+09 | 0.570544E+09 |
March | 0.395235E+09 | 0.00 | 0.395235E+09 | 0.662506E+09 | 0.477958E+09 |
April | 0.430936E+09 | 887921.69 | 0.430048E+09 | 0.930317E+09 | 0.293412E+09 |
May | 0.501225E+09 | 14700635.90 | 0.486525E+09 | 0.145214E+10 | 88195901.92 |
June | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.161653E+10 | 30126098.70 |
July | 0.492435E+09 | 14188242.10 | 0.478247E+09 | 0.184075E+10 | 2045975.36 |
August | 0.458415E+09 | 3791545.17 | 0.454623E+09 | 0.179918E+10 | 757933.50 |
September | 0.404104E+09 | 46306.58 | 0.404057E+09 | 0.131793E+10 | 38746393.05 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.973107E+09 | 0.155455E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.601004E+09 | 0.345330E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.359124E+09 | 0.625529E+09 |
Annual Sum or Average | 0.477055E+10 | 62447133.55 | 0.470810E+10 | 0.122833E+11 | 0.337200E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.322141E+09 | 757933.50 |
Maximum of Months | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.184075E+10 | 0.743901E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.322141E+09 | 0.743901E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.408534E+09 | 0.570543E+09 |
March | 0.395234E+09 | 0.00 | 0.395234E+09 | 0.662506E+09 | 0.477957E+09 |
April | 0.430936E+09 | 887920.63 | 0.430048E+09 | 0.930316E+09 | 0.293412E+09 |
May | 0.501225E+09 | 14700618.26 | 0.486524E+09 | 0.145214E+10 | 88195796.50 |
June | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.161653E+10 | 30126030.58 |
July | 0.492435E+09 | 14188225.07 | 0.478246E+09 | 0.184075E+10 | 2045964.35 |
August | 0.458414E+09 | 3791540.62 | 0.454623E+09 | 0.179918E+10 | 757929.19 |
September | 0.404103E+09 | 46306.53 | 0.404057E+09 | 0.131793E+10 | 38746326.25 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.973107E+09 | 0.155455E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.601004E+09 | 0.345330E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.359124E+09 | 0.625529E+09 |
Annual Sum or Average | 0.477054E+10 | 62447058.62 | 0.470809E+10 | 0.122833E+11 | 0.337200E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.322141E+09 | 757929.19 |
Maximum of Months | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.184075E+10 | 0.743901E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300167E+09 | 0.00 | 0.300167E+09 | 0.322128E+09 | 0.743871E+09 |
February | 0.310779E+09 | 0.00 | 0.310779E+09 | 0.408518E+09 | 0.570521E+09 |
March | 0.395219E+09 | 0.00 | 0.395219E+09 | 0.662480E+09 | 0.477938E+09 |
April | 0.430919E+09 | 887885.91 | 0.430031E+09 | 0.930279E+09 | 0.293400E+09 |
May | 0.501205E+09 | 14700043.40 | 0.486505E+09 | 0.145208E+10 | 88192347.24 |
June | 0.519324E+09 | 28831320.03 | 0.490493E+09 | 0.161646E+10 | 30124884.49 |
July | 0.492415E+09 | 14187670.25 | 0.478227E+09 | 0.184068E+10 | 2045892.90 |
August | 0.458396E+09 | 3791392.35 | 0.454605E+09 | 0.179911E+10 | 757902.95 |
September | 0.404087E+09 | 46304.72 | 0.404041E+09 | 0.131788E+10 | 38744831.40 |
October | 0.370155E+09 | 0.00 | 0.370155E+09 | 0.973068E+09 | 0.155449E+09 |
November | 0.307520E+09 | 0.00 | 0.307520E+09 | 0.600980E+09 | 0.345316E+09 |
December | 0.280167E+09 | 0.00 | 0.280167E+09 | 0.359109E+09 | 0.625504E+09 |
Annual Sum or Average | 0.477035E+10 | 62444616.66 | 0.470791E+10 | 0.122828E+11 | 0.337186E+10 |
Minimum of Months | 0.280167E+09 | 0.00 | 0.280167E+09 | 0.322128E+09 | 757902.95 |
Maximum of Months | 0.519324E+09 | 28831320.03 | 0.490493E+09 | 0.184068E+10 | 0.743871E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603349E+09 | 0.182543E+09 | 0.420806E+09 | 0.803955E+09 | 0.766332E+09 |
February | 0.593881E+09 | 0.160945E+09 | 0.432936E+09 | 0.887689E+09 | 0.587898E+09 |
March | 0.726289E+09 | 0.179004E+09 | 0.547285E+09 | 0.126438E+10 | 0.492402E+09 |
April | 0.855761E+09 | 0.249341E+09 | 0.606421E+09 | 0.175178E+10 | 0.303960E+09 |
May | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.242065E+10 | 97542590.41 |
June | 0.936584E+09 | 0.286418E+09 | 0.650166E+09 | 0.246328E+10 | 31380100.08 |
July | 0.903295E+09 | 0.260418E+09 | 0.642877E+09 | 0.272450E+10 | 1750990.96 |
August | 0.924959E+09 | 0.283882E+09 | 0.641076E+09 | 0.280658E+10 | 618413.72 |
September | 0.841518E+09 | 0.260103E+09 | 0.581415E+09 | 0.220757E+10 | 41337900.69 |
October | 0.789047E+09 | 0.257782E+09 | 0.531265E+09 | 0.179428E+10 | 0.163429E+09 |
November | 0.639894E+09 | 0.202686E+09 | 0.437208E+09 | 0.121738E+10 | 0.353479E+09 |
December | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.790349E+09 | 0.627554E+09 |
Annual Sum or Average | 0.933799E+10 | 0.278481E+10 | 0.655318E+10 | 0.211324E+11 | 0.346768E+10 |
Minimum of Months | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.790349E+09 | 618413.72 |
Maximum of Months | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.280658E+10 | 0.766332E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603349E+09 | 0.182543E+09 | 0.420806E+09 | 0.803955E+09 | 0.766332E+09 |
February | 0.593881E+09 | 0.160945E+09 | 0.432936E+09 | 0.887689E+09 | 0.587898E+09 |
March | 0.726289E+09 | 0.179004E+09 | 0.547285E+09 | 0.126438E+10 | 0.492402E+09 |
April | 0.855761E+09 | 0.249341E+09 | 0.606421E+09 | 0.175178E+10 | 0.303960E+09 |
May | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.242065E+10 | 97542590.41 |
June | 0.936584E+09 | 0.286418E+09 | 0.650166E+09 | 0.246328E+10 | 31380100.08 |
July | 0.903295E+09 | 0.260418E+09 | 0.642877E+09 | 0.272450E+10 | 1750990.96 |
August | 0.924959E+09 | 0.283882E+09 | 0.641076E+09 | 0.280658E+10 | 618413.72 |
September | 0.841518E+09 | 0.260103E+09 | 0.581415E+09 | 0.220757E+10 | 41337900.69 |
October | 0.789047E+09 | 0.257782E+09 | 0.531265E+09 | 0.179428E+10 | 0.163429E+09 |
November | 0.639894E+09 | 0.202686E+09 | 0.437208E+09 | 0.121738E+10 | 0.353479E+09 |
December | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.790349E+09 | 0.627554E+09 |
Annual Sum or Average | 0.933799E+10 | 0.278481E+10 | 0.655318E+10 | 0.211324E+11 | 0.346768E+10 |
Minimum of Months | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.790349E+09 | 618413.72 |
Maximum of Months | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.280658E+10 | 0.766332E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603338E+09 | 0.182539E+09 | 0.420799E+09 | 0.803940E+09 | 0.766318E+09 |
February | 0.593870E+09 | 0.160942E+09 | 0.432929E+09 | 0.887673E+09 | 0.587887E+09 |
March | 0.726276E+09 | 0.179000E+09 | 0.547275E+09 | 0.126435E+10 | 0.492393E+09 |
April | 0.855746E+09 | 0.249336E+09 | 0.606409E+09 | 0.175175E+10 | 0.303954E+09 |
May | 0.988196E+09 | 0.314844E+09 | 0.673351E+09 | 0.242061E+10 | 97540808.09 |
June | 0.936567E+09 | 0.286413E+09 | 0.650155E+09 | 0.246323E+10 | 31379526.70 |
July | 0.903278E+09 | 0.260414E+09 | 0.642865E+09 | 0.272446E+10 | 1750958.97 |
August | 0.924942E+09 | 0.283877E+09 | 0.641065E+09 | 0.280653E+10 | 618402.42 |
September | 0.841503E+09 | 0.260099E+09 | 0.581404E+09 | 0.220753E+10 | 41337145.36 |
October | 0.789033E+09 | 0.257777E+09 | 0.531255E+09 | 0.179424E+10 | 0.163426E+09 |
November | 0.639882E+09 | 0.202682E+09 | 0.437200E+09 | 0.121736E+10 | 0.353472E+09 |
December | 0.535187E+09 | 0.146834E+09 | 0.388353E+09 | 0.790335E+09 | 0.627543E+09 |
Annual Sum or Average | 0.933782E+10 | 0.278476E+10 | 0.655306E+10 | 0.211320E+11 | 0.346762E+10 |
Minimum of Months | 0.535187E+09 | 0.146834E+09 | 0.388353E+09 | 0.790335E+09 | 618402.42 |
Maximum of Months | 0.988196E+09 | 0.314844E+09 | 0.673351E+09 | 0.280653E+10 | 0.766318E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970147E+09 | 0.456110E+09 | 0.514037E+09 | 0.151929E+10 | 0.717547E+09 |
February | 0.822847E+09 | 0.336580E+09 | 0.486266E+09 | 0.137215E+10 | 0.564852E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.139895E+10 | 0.488745E+09 |
April | 0.570387E+09 | 60471832.51 | 0.509915E+09 | 0.125474E+10 | 0.302034E+09 |
May | 0.499273E+09 | 7645866.55 | 0.491627E+09 | 0.145398E+10 | 86648320.33 |
June | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.148110E+10 | 23130458.98 |
July | 0.470187E+09 | 3995158.92 | 0.466192E+09 | 0.179306E+10 | 1207728.41 |
August | 0.545380E+09 | 38642379.00 | 0.506738E+09 | 0.200686E+10 | 533554.97 |
September | 0.695894E+09 | 0.159484E+09 | 0.536409E+09 | 0.195359E+10 | 37986379.20 |
October | 0.941430E+09 | 0.374271E+09 | 0.567158E+09 | 0.212063E+10 | 0.157362E+09 |
November | 0.100509E+10 | 0.484526E+09 | 0.520559E+09 | 0.192315E+10 | 0.351423E+09 |
December | 0.964125E+09 | 0.476248E+09 | 0.487876E+09 | 0.160601E+10 | 0.612884E+09 |
Annual Sum or Average | 0.868959E+10 | 0.260211E+10 | 0.608748E+10 | 0.198835E+11 | 0.334435E+10 |
Minimum of Months | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.125474E+10 | 533554.97 |
Maximum of Months | 0.100509E+10 | 0.484526E+09 | 0.567158E+09 | 0.212063E+10 | 0.717547E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970145E+09 | 0.456109E+09 | 0.514036E+09 | 0.151929E+10 | 0.717547E+09 |
February | 0.822846E+09 | 0.336580E+09 | 0.486266E+09 | 0.137215E+10 | 0.564852E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.139895E+10 | 0.488744E+09 |
April | 0.570387E+09 | 60471759.95 | 0.509915E+09 | 0.125474E+10 | 0.302034E+09 |
May | 0.499272E+09 | 7645857.37 | 0.491627E+09 | 0.145398E+10 | 86648217.18 |
June | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.148110E+10 | 23130403.17 |
July | 0.470187E+09 | 3995154.13 | 0.466192E+09 | 0.179306E+10 | 1207721.55 |
August | 0.545380E+09 | 38642332.63 | 0.506737E+09 | 0.200685E+10 | 533551.71 |
September | 0.695893E+09 | 0.159484E+09 | 0.536409E+09 | 0.195359E+10 | 37986313.11 |
October | 0.941429E+09 | 0.374271E+09 | 0.567158E+09 | 0.212063E+10 | 0.157362E+09 |
November | 0.100508E+10 | 0.484525E+09 | 0.520559E+09 | 0.192315E+10 | 0.351422E+09 |
December | 0.964123E+09 | 0.476248E+09 | 0.487876E+09 | 0.160601E+10 | 0.612884E+09 |
Annual Sum or Average | 0.868958E+10 | 0.260210E+10 | 0.608748E+10 | 0.198835E+11 | 0.334435E+10 |
Minimum of Months | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.125474E+10 | 533551.71 |
Maximum of Months | 0.100508E+10 | 0.484525E+09 | 0.567158E+09 | 0.212063E+10 | 0.717547E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970147E+09 | 0.456110E+09 | 0.514037E+09 | 0.151929E+10 | 0.717547E+09 |
February | 0.822847E+09 | 0.336580E+09 | 0.486266E+09 | 0.137215E+10 | 0.564852E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.139895E+10 | 0.488745E+09 |
April | 0.570387E+09 | 60471832.51 | 0.509915E+09 | 0.125474E+10 | 0.302034E+09 |
May | 0.499273E+09 | 7645866.55 | 0.491627E+09 | 0.145398E+10 | 86648320.33 |
June | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.148110E+10 | 23130458.98 |
July | 0.470187E+09 | 3995158.92 | 0.466192E+09 | 0.179306E+10 | 1207728.41 |
August | 0.545380E+09 | 38642379.00 | 0.506738E+09 | 0.200686E+10 | 533554.97 |
September | 0.695894E+09 | 0.159484E+09 | 0.536409E+09 | 0.195359E+10 | 37986379.20 |
October | 0.941430E+09 | 0.374271E+09 | 0.567158E+09 | 0.212063E+10 | 0.157362E+09 |
November | 0.100509E+10 | 0.484526E+09 | 0.520559E+09 | 0.192315E+10 | 0.351423E+09 |
December | 0.964125E+09 | 0.476248E+09 | 0.487876E+09 | 0.160601E+10 | 0.612884E+09 |
Annual Sum or Average | 0.868959E+10 | 0.260211E+10 | 0.608748E+10 | 0.198835E+11 | 0.334435E+10 |
Minimum of Months | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.125474E+10 | 533554.97 |
Maximum of Months | 0.100509E+10 | 0.484526E+09 | 0.567158E+09 | 0.212063E+10 | 0.717547E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970145E+09 | 0.456109E+09 | 0.514036E+09 | 0.151929E+10 | 0.717547E+09 |
February | 0.822846E+09 | 0.336580E+09 | 0.486266E+09 | 0.137215E+10 | 0.564852E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.139895E+10 | 0.488744E+09 |
April | 0.570387E+09 | 60471759.95 | 0.509915E+09 | 0.125474E+10 | 0.302034E+09 |
May | 0.499272E+09 | 7645857.37 | 0.491627E+09 | 0.145398E+10 | 86648217.18 |
June | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.148110E+10 | 23130403.17 |
July | 0.470187E+09 | 3995154.13 | 0.466192E+09 | 0.179306E+10 | 1207721.55 |
August | 0.545380E+09 | 38642332.63 | 0.506737E+09 | 0.200685E+10 | 533551.71 |
September | 0.695893E+09 | 0.159484E+09 | 0.536409E+09 | 0.195359E+10 | 37986313.11 |
October | 0.941429E+09 | 0.374271E+09 | 0.567158E+09 | 0.212063E+10 | 0.157362E+09 |
November | 0.100508E+10 | 0.484525E+09 | 0.520559E+09 | 0.192315E+10 | 0.351422E+09 |
December | 0.964123E+09 | 0.476248E+09 | 0.487876E+09 | 0.160601E+10 | 0.612884E+09 |
Annual Sum or Average | 0.868958E+10 | 0.260210E+10 | 0.608748E+10 | 0.198835E+11 | 0.334435E+10 |
Minimum of Months | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.125474E+10 | 533551.71 |
Maximum of Months | 0.100508E+10 | 0.484525E+09 | 0.567158E+09 | 0.212063E+10 | 0.717547E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970107E+09 | 0.456091E+09 | 0.514016E+09 | 0.151923E+10 | 0.717518E+09 |
February | 0.822813E+09 | 0.336567E+09 | 0.486247E+09 | 0.137209E+10 | 0.564829E+09 |
March | 0.749771E+09 | 0.203559E+09 | 0.546212E+09 | 0.139890E+10 | 0.488725E+09 |
April | 0.570364E+09 | 60469395.23 | 0.509895E+09 | 0.125469E+10 | 0.302022E+09 |
May | 0.499253E+09 | 7645558.38 | 0.491607E+09 | 0.145392E+10 | 86644828.03 |
June | 0.455014E+09 | 563097.02 | 0.454451E+09 | 0.148104E+10 | 23129526.72 |
July | 0.470168E+09 | 3994997.90 | 0.466173E+09 | 0.179299E+10 | 1207679.73 |
August | 0.545358E+09 | 38640821.54 | 0.506717E+09 | 0.200677E+10 | 533533.46 |
September | 0.695866E+09 | 0.159478E+09 | 0.536388E+09 | 0.195351E+10 | 37984848.18 |
October | 0.941392E+09 | 0.374256E+09 | 0.567135E+09 | 0.212055E+10 | 0.157356E+09 |
November | 0.100504E+10 | 0.484506E+09 | 0.520538E+09 | 0.192307E+10 | 0.351408E+09 |
December | 0.964086E+09 | 0.476229E+09 | 0.487857E+09 | 0.160594E+10 | 0.612859E+09 |
Annual Sum or Average | 0.868924E+10 | 0.260200E+10 | 0.608724E+10 | 0.198827E+11 | 0.334422E+10 |
Minimum of Months | 0.455014E+09 | 563097.02 | 0.454451E+09 | 0.125469E+10 | 533533.46 |
Maximum of Months | 0.100504E+10 | 0.484506E+09 | 0.567135E+09 | 0.212055E+10 | 0.717518E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591693E+09 | 0.169939E+09 | 0.421754E+09 | 0.806119E+09 | 0.906011E+09 |
February | 0.610267E+09 | 0.174024E+09 | 0.436243E+09 | 0.917658E+09 | 0.723747E+09 |
March | 0.800331E+09 | 0.236940E+09 | 0.563391E+09 | 0.137379E+10 | 0.643494E+09 |
April | 0.846411E+09 | 0.237796E+09 | 0.608615E+09 | 0.168520E+10 | 0.431066E+09 |
May | 0.952025E+09 | 0.284979E+09 | 0.667045E+09 | 0.235431E+10 | 0.119774E+09 |
June | 0.952101E+09 | 0.300128E+09 | 0.651974E+09 | 0.246929E+10 | 43605435.60 |
July | 0.902565E+09 | 0.258206E+09 | 0.644359E+09 | 0.266181E+10 | 4607015.74 |
August | 0.925932E+09 | 0.281523E+09 | 0.644409E+09 | 0.271348E+10 | 2750041.67 |
September | 0.852387E+09 | 0.267796E+09 | 0.584591E+09 | 0.222620E+10 | 50384412.83 |
October | 0.782772E+09 | 0.252857E+09 | 0.529915E+09 | 0.177605E+10 | 0.205918E+09 |
November | 0.650996E+09 | 0.212897E+09 | 0.438100E+09 | 0.122894E+10 | 0.477008E+09 |
December | 0.563152E+09 | 0.170231E+09 | 0.392921E+09 | 0.827199E+09 | 0.845765E+09 |
Annual Sum or Average | 0.943063E+10 | 0.284732E+10 | 0.658332E+10 | 0.210400E+11 | 0.445413E+10 |
Minimum of Months | 0.563152E+09 | 0.169939E+09 | 0.392921E+09 | 0.806119E+09 | 2750041.67 |
Maximum of Months | 0.952101E+09 | 0.300128E+09 | 0.667045E+09 | 0.271348E+10 | 0.906011E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591693E+09 | 0.169939E+09 | 0.421754E+09 | 0.806119E+09 | 0.906011E+09 |
February | 0.610267E+09 | 0.174024E+09 | 0.436243E+09 | 0.917658E+09 | 0.723747E+09 |
March | 0.800331E+09 | 0.236940E+09 | 0.563391E+09 | 0.137379E+10 | 0.643494E+09 |
April | 0.846411E+09 | 0.237796E+09 | 0.608615E+09 | 0.168520E+10 | 0.431066E+09 |
May | 0.952025E+09 | 0.284979E+09 | 0.667045E+09 | 0.235431E+10 | 0.119774E+09 |
June | 0.952101E+09 | 0.300128E+09 | 0.651974E+09 | 0.246929E+10 | 43605435.60 |
July | 0.902565E+09 | 0.258206E+09 | 0.644359E+09 | 0.266181E+10 | 4607015.74 |
August | 0.925932E+09 | 0.281523E+09 | 0.644409E+09 | 0.271348E+10 | 2750041.67 |
September | 0.852387E+09 | 0.267796E+09 | 0.584591E+09 | 0.222620E+10 | 50384412.83 |
October | 0.782772E+09 | 0.252857E+09 | 0.529915E+09 | 0.177605E+10 | 0.205918E+09 |
November | 0.650996E+09 | 0.212897E+09 | 0.438100E+09 | 0.122894E+10 | 0.477008E+09 |
December | 0.563152E+09 | 0.170231E+09 | 0.392921E+09 | 0.827199E+09 | 0.845765E+09 |
Annual Sum or Average | 0.943063E+10 | 0.284732E+10 | 0.658332E+10 | 0.210400E+11 | 0.445413E+10 |
Minimum of Months | 0.563152E+09 | 0.169939E+09 | 0.392921E+09 | 0.806119E+09 | 2750041.67 |
Maximum of Months | 0.952101E+09 | 0.300128E+09 | 0.667045E+09 | 0.271348E+10 | 0.906011E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591682E+09 | 0.169936E+09 | 0.421746E+09 | 0.806104E+09 | 0.905994E+09 |
February | 0.610256E+09 | 0.174020E+09 | 0.436235E+09 | 0.917642E+09 | 0.723734E+09 |
March | 0.800316E+09 | 0.236936E+09 | 0.563381E+09 | 0.137377E+10 | 0.643483E+09 |
April | 0.846395E+09 | 0.237792E+09 | 0.608604E+09 | 0.168517E+10 | 0.431058E+09 |
May | 0.952007E+09 | 0.284974E+09 | 0.667033E+09 | 0.235427E+10 | 0.119772E+09 |
June | 0.952084E+09 | 0.300122E+09 | 0.651962E+09 | 0.246924E+10 | 43604638.83 |
July | 0.902549E+09 | 0.258201E+09 | 0.644348E+09 | 0.266176E+10 | 4606931.56 |
August | 0.925915E+09 | 0.281518E+09 | 0.644397E+09 | 0.271343E+10 | 2749991.42 |
September | 0.852371E+09 | 0.267791E+09 | 0.584581E+09 | 0.222615E+10 | 50383492.20 |
October | 0.782758E+09 | 0.252852E+09 | 0.529905E+09 | 0.177602E+10 | 0.205914E+09 |
November | 0.650984E+09 | 0.212893E+09 | 0.438092E+09 | 0.122892E+10 | 0.476999E+09 |
December | 0.563141E+09 | 0.170228E+09 | 0.392914E+09 | 0.827184E+09 | 0.845750E+09 |
Annual Sum or Average | 0.943046E+10 | 0.284726E+10 | 0.658320E+10 | 0.210397E+11 | 0.445405E+10 |
Minimum of Months | 0.563141E+09 | 0.169936E+09 | 0.392914E+09 | 0.806104E+09 | 2749991.42 |
Maximum of Months | 0.952084E+09 | 0.300122E+09 | 0.667033E+09 | 0.271343E+10 | 0.905994E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.174300E+10 | 0.331449E+10 |
February | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.215060E+10 | 0.254298E+10 |
March | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.341300E+10 | 0.218094E+10 |
April | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.479152E+10 | 0.134391E+10 |
May | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.754076E+10 | 0.343777E+09 |
June | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.843205E+10 | 79109052.42 |
July | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.971650E+10 | 1898465.13 |
August | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.957666E+10 | 216718.08 |
September | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.700279E+10 | 0.112362E+09 |
October | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.517625E+10 | 0.569221E+09 |
November | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.316863E+10 | 0.152569E+10 |
December | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.193927E+10 | 0.274489E+10 |
Annual Sum or Average | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.646510E+11 | 0.147595E+11 |
Minimum of Months | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.174300E+10 | 216718.08 |
Maximum of Months | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.971650E+10 | 0.331449E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.243370E+10 | 0.215339E+10 |
February | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.266488E+10 | 0.166725E+10 |
March | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.377529E+10 | 0.143966E+10 |
April | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.524039E+10 | 0.911881E+09 |
May | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.735647E+10 | 0.237380E+09 |
June | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.752650E+10 | 52776510.88 |
July | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.839668E+10 | 1217495.39 |
August | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.866947E+10 | 114553.92 |
September | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.680404E+10 | 75487374.31 |
October | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.548853E+10 | 0.382210E+09 |
November | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.366410E+10 | 0.100983E+10 |
December | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.238259E+10 | 0.179278E+10 |
Annual Sum or Average | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.644026E+11 | 0.972398E+10 |
Minimum of Months | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.238259E+10 | 114553.92 |
Maximum of Months | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.866947E+10 | 0.215339E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.754588E+10 | 0.349037E+10 |
February | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.682887E+10 | 0.271166E+10 |
March | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.699413E+10 | 0.234740E+10 |
April | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.634846E+10 | 0.143002E+10 |
May | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.751427E+10 | 0.349032E+09 |
June | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.775903E+10 | 58693220.59 |
July | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.942464E+10 | 728620.46 |
August | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.105195E+11 | 152909.78 |
September | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.100338E+11 | 0.130049E+09 |
October | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.107283E+11 | 0.661290E+09 |
November | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.960808E+10 | 0.168648E+10 |
December | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.801190E+10 | 0.294584E+10 |
Annual Sum or Average | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.101317E+12 | 0.158117E+11 |
Minimum of Months | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.634846E+10 | 152909.78 |
Maximum of Months | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.107283E+11 | 0.349037E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.251091E+10 | 0.238643E+10 |
February | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.284935E+10 | 0.184518E+10 |
March | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.423510E+10 | 0.162672E+10 |
April | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.519999E+10 | 0.106580E+10 |
May | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.716982E+10 | 0.304532E+09 |
June | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.760885E+10 | 76005012.55 |
July | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.831841E+10 | 3074992.86 |
August | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.855113E+10 | 1020929.38 |
September | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.683062E+10 | 0.110765E+09 |
October | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.547604E+10 | 0.491438E+09 |
November | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.381870E+10 | 0.117086E+10 |
December | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.264773E+10 | 0.202597E+10 |
Annual Sum or Average | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.652167E+11 | 0.111078E+11 |
Minimum of Months | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.251091E+10 | 1020929.38 |
Maximum of Months | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.855113E+10 | 0.238643E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.180753E+10 | 0.310783E+10 |
February | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.217467E+10 | 0.242810E+10 |
March | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.339637E+10 | 0.212869E+10 |
April | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.473788E+10 | 0.135274E+10 |
May | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.744334E+10 | 0.360928E+09 |
June | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.832703E+10 | 88453358.34 |
July | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.957527E+10 | 3160680.04 |
August | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.944986E+10 | 408938.07 |
September | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.690534E+10 | 0.118881E+09 |
October | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.511934E+10 | 0.583539E+09 |
November | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.315070E+10 | 0.149205E+10 |
December | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.197539E+10 | 0.260642E+10 |
Annual Sum or Average | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.640627E+11 | 0.142712E+11 |
Minimum of Months | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.180753E+10 | 408938.07 |
Maximum of Months | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.957527E+10 | 0.310783E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.249637E+10 | 0.203909E+10 |
February | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.269638E+10 | 0.160180E+10 |
March | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.378285E+10 | 0.140828E+10 |
April | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.522408E+10 | 0.914291E+09 |
May | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.731248E+10 | 0.246071E+09 |
June | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.747840E+10 | 57633849.08 |
July | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.832562E+10 | 1837436.28 |
August | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.860975E+10 | 199628.34 |
September | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.675994E+10 | 78421524.46 |
October | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.546823E+10 | 0.387273E+09 |
November | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.366912E+10 | 0.988469E+09 |
December | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.242370E+10 | 0.171400E+10 |
Annual Sum or Average | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.642469E+11 | 0.943738E+10 |
Minimum of Months | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.242370E+10 | 199628.34 |
Maximum of Months | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.860975E+10 | 0.203909E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.758339E+10 | 0.332471E+10 |
February | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.682843E+10 | 0.261304E+10 |
March | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.696215E+10 | 0.229714E+10 |
April | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.629221E+10 | 0.143480E+10 |
May | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.741588E+10 | 0.364440E+09 |
June | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.765186E+10 | 65294461.69 |
July | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.928045E+10 | 1361401.06 |
August | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.103923E+11 | 296023.54 |
September | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.993312E+10 | 0.136146E+09 |
October | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.106582E+11 | 0.671354E+09 |
November | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.957022E+10 | 0.165529E+10 |
December | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.802070E+10 | 0.283645E+10 |
Annual Sum or Average | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.100589E+12 | 0.154003E+11 |
Minimum of Months | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.629221E+10 | 296023.54 |
Maximum of Months | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.106582E+11 | 0.332471E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.252896E+10 | 0.227143E+10 |
February | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.284698E+10 | 0.178034E+10 |
March | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.420835E+10 | 0.159424E+10 |
April | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.515712E+10 | 0.106558E+10 |
May | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.710630E+10 | 0.313177E+09 |
June | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.754346E+10 | 80761047.04 |
July | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.823335E+10 | 4123971.46 |
August | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.847130E+10 | 1307016.82 |
September | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.676950E+10 | 0.115637E+09 |
October | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.543565E+10 | 0.497649E+09 |
November | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.379766E+10 | 0.114867E+10 |
December | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.265111E+10 | 0.194924E+10 |
Annual Sum or Average | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.647497E+11 | 0.108222E+11 |
Minimum of Months | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.252896E+10 | 1307016.82 |
Maximum of Months | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.847130E+10 | 0.227143E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 601.36 | 1388.69 | 560.37 | 0.00 | 560.37 | 0.00 | 0.00 |
February | 844.35 | 1179.19 | 642.34 | 0.00 | 642.34 | 0.00 | 0.00 |
March | 1236.75 | 892.24 | 737.81 | 0.00 | 737.81 | 0.00 | 0.00 |
April | 1794.58 | 565.99 | 831.27 | 1.71 | 829.56 | 0.00 | 0.00 |
May | 2710.82 | 164.64 | 935.67 | 27.44 | 908.23 | 0.00 | 0.00 |
June | 3118.27 | 58.11 | 1001.81 | 55.62 | 946.20 | 0.00 | 0.00 |
July | 3436.26 | 3.82 | 919.26 | 26.49 | 892.78 | 0.00 | 0.00 |
August | 3358.66 | 1.41 | 855.76 | 7.08 | 848.68 | 0.00 | 0.00 |
September | 2542.28 | 74.74 | 779.51 | 0.09 | 779.43 | 0.00 | 0.00 |
October | 1816.57 | 290.20 | 691.02 | 0.00 | 691.02 | 0.00 | 0.00 |
November | 1159.34 | 666.14 | 593.23 | 0.00 | 593.23 | 0.00 | 0.00 |
December | 670.40 | 1167.72 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Annual Sum or Average | 1947.48 | 534.62 | 756.36 | 9.90 | 746.46 | 0.00 | 0.00 |
Minimum of Months | 601.36 | 1.41 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Maximum of Months | 3436.26 | 1388.69 | 1001.81 | 55.62 | 946.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 900.48 | 858.34 | 675.79 | 204.46 | 471.33 | 0.00 | 0.00 |
February | 1100.80 | 729.04 | 736.46 | 199.58 | 536.87 | 0.00 | 0.00 |
March | 1416.18 | 551.52 | 813.49 | 200.50 | 612.99 | 0.00 | 0.00 |
April | 2027.51 | 351.80 | 990.46 | 288.59 | 701.87 | 0.00 | 0.00 |
May | 2711.29 | 109.25 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
June | 2851.00 | 36.32 | 1084.00 | 331.50 | 752.50 | 0.00 | 0.00 |
July | 3051.62 | 1.96 | 1011.75 | 291.69 | 720.06 | 0.00 | 0.00 |
August | 3143.55 | 0.69 | 1036.01 | 317.97 | 718.05 | 0.00 | 0.00 |
September | 2555.04 | 47.84 | 973.97 | 301.04 | 672.93 | 0.00 | 0.00 |
October | 2009.71 | 183.05 | 883.78 | 288.73 | 595.05 | 0.00 | 0.00 |
November | 1409.00 | 409.12 | 740.61 | 234.59 | 506.03 | 0.00 | 0.00 |
December | 885.24 | 702.90 | 599.46 | 164.47 | 434.99 | 0.00 | 0.00 |
Annual Sum or Average | 2010.30 | 329.88 | 888.31 | 264.92 | 623.40 | 0.00 | 0.00 |
Minimum of Months | 885.24 | 0.69 | 599.46 | 164.47 | 434.99 | 0.00 | 0.00 |
Maximum of Months | 3143.55 | 858.34 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2836.17 | 1339.50 | 1811.04 | 851.45 | 959.59 | 0.00 | 0.00 |
February | 2835.93 | 1167.43 | 1700.64 | 695.64 | 1005.01 | 0.00 | 0.00 |
March | 2611.52 | 912.37 | 1399.71 | 380.01 | 1019.69 | 0.00 | 0.00 |
April | 2420.38 | 582.62 | 1100.27 | 116.65 | 983.62 | 0.00 | 0.00 |
May | 2714.25 | 161.75 | 932.03 | 14.27 | 917.75 | 0.00 | 0.00 |
June | 2857.03 | 44.62 | 877.76 | 1.09 | 876.67 | 0.00 | 0.00 |
July | 3347.24 | 2.25 | 877.73 | 7.46 | 870.27 | 0.00 | 0.00 |
August | 3746.34 | 1.00 | 1018.10 | 72.14 | 945.96 | 0.00 | 0.00 |
September | 3768.47 | 73.28 | 1342.38 | 307.64 | 1034.73 | 0.00 | 0.00 |
October | 3958.74 | 293.76 | 1757.43 | 698.68 | 1058.75 | 0.00 | 0.00 |
November | 3709.75 | 677.89 | 1938.81 | 934.65 | 1004.16 | 0.00 | 0.00 |
December | 2998.05 | 1144.11 | 1799.80 | 889.05 | 910.75 | 0.00 | 0.00 |
Annual Sum or Average | 3152.48 | 530.24 | 1377.71 | 412.56 | 965.16 | 0.00 | 0.00 |
Minimum of Months | 2420.38 | 1.00 | 877.73 | 1.09 | 870.27 | 0.00 | 0.00 |
Maximum of Months | 3958.74 | 1339.50 | 1938.81 | 934.65 | 1058.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 902.91 | 1014.79 | 662.73 | 190.34 | 472.39 | 0.00 | 0.00 |
February | 1137.96 | 897.50 | 756.77 | 215.80 | 540.97 | 0.00 | 0.00 |
March | 1538.74 | 720.76 | 896.42 | 265.39 | 631.03 | 0.00 | 0.00 |
April | 1950.45 | 498.92 | 979.64 | 275.23 | 704.41 | 0.00 | 0.00 |
May | 2636.98 | 134.15 | 1066.33 | 319.20 | 747.13 | 0.00 | 0.00 |
June | 2857.95 | 50.47 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
July | 2981.40 | 5.16 | 1010.93 | 289.21 | 721.72 | 0.00 | 0.00 |
August | 3039.27 | 3.08 | 1037.10 | 315.32 | 721.78 | 0.00 | 0.00 |
September | 2576.60 | 58.31 | 986.55 | 309.95 | 676.61 | 0.00 | 0.00 |
October | 1989.29 | 230.64 | 876.76 | 283.22 | 593.54 | 0.00 | 0.00 |
November | 1422.37 | 552.09 | 753.46 | 246.41 | 507.06 | 0.00 | 0.00 |
December | 926.52 | 947.31 | 630.77 | 190.67 | 440.10 | 0.00 | 0.00 |
Annual Sum or Average | 2001.51 | 423.72 | 897.12 | 270.86 | 626.26 | 0.00 | 0.00 |
Minimum of Months | 902.91 | 3.08 | 630.77 | 190.34 | 440.10 | 0.00 | 0.00 |
Maximum of Months | 3039.27 | 1014.79 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 650.76 | 1237.49 | 560.36 | 0.00 | 560.36 | 0.00 | 0.00 |
February | 888.97 | 1051.17 | 642.34 | 0.00 | 642.34 | 0.00 | 0.00 |
March | 1274.27 | 814.27 | 737.81 | 0.00 | 737.81 | 0.00 | 0.00 |
April | 1848.58 | 518.48 | 831.27 | 1.71 | 829.56 | 0.00 | 0.00 |
May | 2815.40 | 128.35 | 935.67 | 27.44 | 908.23 | 0.00 | 0.00 |
June | 3253.11 | 30.52 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
July | 3627.72 | 0.71 | 919.26 | 26.49 | 892.77 | 0.00 | 0.00 |
August | 3575.52 | 0.08 | 855.75 | 7.08 | 848.67 | 0.00 | 0.00 |
September | 2701.69 | 43.35 | 779.51 | 0.09 | 779.42 | 0.00 | 0.00 |
October | 1932.59 | 212.52 | 691.02 | 0.00 | 691.02 | 0.00 | 0.00 |
November | 1222.46 | 588.62 | 593.23 | 0.00 | 593.23 | 0.00 | 0.00 |
December | 724.04 | 1024.82 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Annual Sum or Average | 2050.07 | 468.02 | 756.36 | 9.90 | 746.46 | 0.00 | 0.00 |
Minimum of Months | 650.76 | 0.08 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Maximum of Months | 3627.72 | 1237.49 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 908.64 | 803.98 | 675.79 | 204.46 | 471.33 | 0.00 | 0.00 |
February | 1101.56 | 689.18 | 736.45 | 199.58 | 536.87 | 0.00 | 0.00 |
March | 1409.53 | 537.51 | 813.49 | 200.49 | 612.99 | 0.00 | 0.00 |
April | 2021.76 | 351.81 | 990.45 | 288.59 | 701.87 | 0.00 | 0.00 |
May | 2746.59 | 88.63 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
June | 2903.74 | 20.36 | 1084.00 | 331.50 | 752.50 | 0.00 | 0.00 |
July | 3134.96 | 0.45 | 1011.74 | 291.68 | 720.06 | 0.00 | 0.00 |
August | 3236.81 | 0.04 | 1036.01 | 317.97 | 718.04 | 0.00 | 0.00 |
September | 2625.02 | 29.12 | 973.97 | 301.04 | 672.93 | 0.00 | 0.00 |
October | 2049.18 | 142.70 | 883.78 | 288.73 | 595.05 | 0.00 | 0.00 |
November | 1413.62 | 389.59 | 740.61 | 234.59 | 506.02 | 0.00 | 0.00 |
December | 889.56 | 669.35 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Annual Sum or Average | 2042.19 | 308.35 | 888.31 | 264.91 | 623.39 | 0.00 | 0.00 |
Minimum of Months | 889.56 | 0.04 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Maximum of Months | 3236.81 | 803.98 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2817.31 | 1303.15 | 1811.03 | 851.45 | 959.59 | 0.00 | 0.00 |
February | 2822.78 | 1120.89 | 1700.64 | 695.64 | 1005.00 | 0.00 | 0.00 |
March | 2611.31 | 876.42 | 1399.70 | 380.01 | 1019.69 | 0.00 | 0.00 |
April | 2449.25 | 551.70 | 1100.27 | 116.65 | 983.62 | 0.00 | 0.00 |
May | 2805.51 | 130.31 | 932.02 | 14.27 | 917.75 | 0.00 | 0.00 |
June | 2993.45 | 22.64 | 877.75 | 1.09 | 876.67 | 0.00 | 0.00 |
July | 3518.76 | 0.27 | 877.73 | 7.46 | 870.27 | 0.00 | 0.00 |
August | 3927.55 | 0.06 | 1018.10 | 72.14 | 945.96 | 0.00 | 0.00 |
September | 3871.05 | 50.17 | 1342.37 | 307.64 | 1034.73 | 0.00 | 0.00 |
October | 4005.49 | 246.90 | 1757.43 | 698.68 | 1058.75 | 0.00 | 0.00 |
November | 3706.82 | 650.65 | 1938.80 | 934.65 | 1004.15 | 0.00 | 0.00 |
December | 2991.30 | 1099.85 | 1799.79 | 889.04 | 910.75 | 0.00 | 0.00 |
Annual Sum or Average | 3212.74 | 501.39 | 1377.71 | 412.56 | 965.15 | 0.00 | 0.00 |
Minimum of Months | 2449.25 | 0.06 | 877.73 | 1.09 | 870.27 | 0.00 | 0.00 |
Maximum of Months | 4005.49 | 1303.15 | 1938.80 | 934.65 | 1058.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 937.47 | 890.99 | 662.73 | 190.34 | 472.39 | 0.00 | 0.00 |
February | 1177.81 | 762.72 | 756.77 | 215.80 | 540.97 | 0.00 | 0.00 |
March | 1581.20 | 607.35 | 896.42 | 265.39 | 631.03 | 0.00 | 0.00 |
April | 2006.17 | 411.19 | 979.63 | 275.22 | 704.41 | 0.00 | 0.00 |
May | 2676.90 | 113.70 | 1066.33 | 319.19 | 747.13 | 0.00 | 0.00 |
June | 2935.51 | 29.32 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
July | 3105.74 | 1.15 | 1010.93 | 289.21 | 721.72 | 0.00 | 0.00 |
August | 3192.63 | 0.38 | 1037.10 | 315.32 | 721.78 | 0.00 | 0.00 |
September | 2635.27 | 42.73 | 986.55 | 309.95 | 676.60 | 0.00 | 0.00 |
October | 2044.52 | 183.48 | 876.75 | 283.22 | 593.54 | 0.00 | 0.00 |
November | 1473.26 | 451.72 | 753.46 | 246.41 | 507.05 | 0.00 | 0.00 |
December | 988.55 | 756.41 | 630.76 | 190.67 | 440.10 | 0.00 | 0.00 |
Annual Sum or Average | 2068.01 | 352.23 | 897.12 | 270.86 | 626.26 | 0.00 | 0.00 |
Minimum of Months | 937.47 | 0.38 | 630.76 | 190.34 | 440.10 | 0.00 | 0.00 |
Maximum of Months | 3192.63 | 890.99 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 674.86 | 1160.33 | 560.36 | 0.00 | 560.36 | 0.00 | 0.00 |
February | 898.92 | 1003.68 | 642.34 | 0.00 | 642.34 | 0.00 | 0.00 |
March | 1268.06 | 794.76 | 737.81 | 0.00 | 737.81 | 0.00 | 0.00 |
April | 1827.88 | 521.89 | 831.27 | 1.71 | 829.56 | 0.00 | 0.00 |
May | 2779.02 | 134.76 | 935.67 | 27.44 | 908.23 | 0.00 | 0.00 |
June | 3212.59 | 34.13 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
July | 3575.00 | 1.18 | 919.26 | 26.49 | 892.77 | 0.00 | 0.00 |
August | 3528.17 | 0.15 | 855.75 | 7.08 | 848.67 | 0.00 | 0.00 |
September | 2664.10 | 45.86 | 779.51 | 0.09 | 779.42 | 0.00 | 0.00 |
October | 1911.34 | 217.87 | 691.02 | 0.00 | 691.02 | 0.00 | 0.00 |
November | 1215.55 | 575.64 | 593.23 | 0.00 | 593.23 | 0.00 | 0.00 |
December | 737.53 | 973.12 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Annual Sum or Average | 2031.42 | 452.54 | 756.36 | 9.90 | 746.46 | 0.00 | 0.00 |
Minimum of Months | 674.86 | 0.15 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Maximum of Months | 3575.00 | 1160.33 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 932.04 | 761.31 | 675.79 | 204.46 | 471.33 | 0.00 | 0.00 |
February | 1114.57 | 662.12 | 736.45 | 199.58 | 536.87 | 0.00 | 0.00 |
March | 1412.35 | 525.79 | 813.49 | 200.49 | 612.99 | 0.00 | 0.00 |
April | 2015.46 | 352.74 | 990.45 | 288.59 | 701.87 | 0.00 | 0.00 |
May | 2730.17 | 91.87 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
June | 2885.18 | 22.24 | 1084.00 | 331.50 | 752.50 | 0.00 | 0.00 |
July | 3108.43 | 0.69 | 1011.74 | 291.68 | 720.06 | 0.00 | 0.00 |
August | 3214.51 | 0.07 | 1036.01 | 317.97 | 718.04 | 0.00 | 0.00 |
September | 2608.00 | 30.26 | 973.97 | 301.04 | 672.93 | 0.00 | 0.00 |
October | 2041.60 | 144.59 | 883.78 | 288.73 | 595.05 | 0.00 | 0.00 |
November | 1415.55 | 381.35 | 740.61 | 234.59 | 506.02 | 0.00 | 0.00 |
December | 904.91 | 639.93 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Annual Sum or Average | 2037.26 | 299.26 | 888.31 | 264.91 | 623.39 | 0.00 | 0.00 |
Minimum of Months | 904.91 | 0.07 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Maximum of Months | 3214.51 | 761.31 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2831.31 | 1241.30 | 1811.03 | 851.45 | 959.59 | 0.00 | 0.00 |
February | 2822.60 | 1080.12 | 1700.64 | 695.64 | 1005.00 | 0.00 | 0.00 |
March | 2599.37 | 857.65 | 1399.70 | 380.01 | 1019.69 | 0.00 | 0.00 |
April | 2427.55 | 553.55 | 1100.27 | 116.65 | 983.62 | 0.00 | 0.00 |
May | 2768.77 | 136.07 | 932.02 | 14.27 | 917.75 | 0.00 | 0.00 |
June | 2952.11 | 25.19 | 877.75 | 1.09 | 876.67 | 0.00 | 0.00 |
July | 3464.92 | 0.51 | 877.73 | 7.46 | 870.27 | 0.00 | 0.00 |
August | 3880.04 | 0.11 | 1018.10 | 72.14 | 945.96 | 0.00 | 0.00 |
September | 3832.22 | 52.53 | 1342.37 | 307.64 | 1034.73 | 0.00 | 0.00 |
October | 3979.30 | 250.65 | 1757.43 | 698.68 | 1058.75 | 0.00 | 0.00 |
November | 3692.21 | 638.61 | 1938.80 | 934.65 | 1004.15 | 0.00 | 0.00 |
December | 2994.59 | 1059.01 | 1799.79 | 889.04 | 910.75 | 0.00 | 0.00 |
Annual Sum or Average | 3189.65 | 488.34 | 1377.71 | 412.56 | 965.15 | 0.00 | 0.00 |
Minimum of Months | 2427.55 | 0.11 | 877.73 | 1.09 | 870.27 | 0.00 | 0.00 |
Maximum of Months | 3979.30 | 1241.30 | 1938.80 | 934.65 | 1058.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 944.21 | 848.06 | 662.73 | 190.34 | 472.39 | 0.00 | 0.00 |
February | 1176.83 | 735.92 | 756.77 | 215.80 | 540.97 | 0.00 | 0.00 |
March | 1571.22 | 595.22 | 896.42 | 265.39 | 631.03 | 0.00 | 0.00 |
April | 1989.63 | 411.10 | 979.63 | 275.22 | 704.41 | 0.00 | 0.00 |
May | 2653.19 | 116.93 | 1066.33 | 319.19 | 747.13 | 0.00 | 0.00 |
June | 2910.29 | 31.16 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
July | 3073.98 | 1.54 | 1010.93 | 289.21 | 721.72 | 0.00 | 0.00 |
August | 3162.82 | 0.49 | 1037.10 | 315.32 | 721.78 | 0.00 | 0.00 |
September | 2611.69 | 44.61 | 986.55 | 309.95 | 676.60 | 0.00 | 0.00 |
October | 2029.44 | 185.80 | 876.75 | 283.22 | 593.54 | 0.00 | 0.00 |
November | 1465.15 | 443.16 | 753.46 | 246.41 | 507.05 | 0.00 | 0.00 |
December | 989.81 | 727.76 | 630.76 | 190.67 | 440.10 | 0.00 | 0.00 |
Annual Sum or Average | 2053.20 | 343.17 | 897.12 | 270.86 | 626.26 | 0.00 | 0.00 |
Minimum of Months | 944.21 | 0.49 | 630.76 | 190.34 | 440.10 | 0.00 | 0.00 |
Maximum of Months | 3162.82 | 848.06 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.161069E+10 | 0.371947E+10 | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.00 | 0.00 |
February | 0.204265E+10 | 0.285269E+10 | 0.155395E+10 | 0.00 | 0.155395E+10 | 0.00 | 0.00 |
March | 0.331250E+10 | 0.238977E+10 | 0.197616E+10 | 0.00 | 0.197616E+10 | 0.00 | 0.00 |
April | 0.465155E+10 | 0.146705E+10 | 0.215466E+10 | 4439570.55 | 0.215022E+10 | 0.00 | 0.00 |
May | 0.726065E+10 | 0.440976E+09 | 0.250611E+10 | 73502551.72 | 0.243260E+10 | 0.00 | 0.00 |
June | 0.808257E+10 | 0.150629E+09 | 0.259670E+10 | 0.144161E+09 | 0.245254E+10 | 0.00 | 0.00 |
July | 0.920368E+10 | 10229772.33 | 0.246215E+10 | 70940604.60 | 0.239121E+10 | 0.00 | 0.00 |
August | 0.899583E+10 | 3789628.33 | 0.229205E+10 | 18957563.92 | 0.227310E+10 | 0.00 | 0.00 |
September | 0.658959E+10 | 0.193730E+09 | 0.202050E+10 | 231530.94 | 0.202027E+10 | 0.00 | 0.00 |
October | 0.486550E+10 | 0.777268E+09 | 0.185084E+10 | 0.00 | 0.185084E+10 | 0.00 | 0.00 |
November | 0.300500E+10 | 0.172663E+10 | 0.153765E+10 | 0.00 | 0.153765E+10 | 0.00 | 0.00 |
December | 0.179560E+10 | 0.312762E+10 | 0.140088E+10 | 0.00 | 0.140088E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.614158E+11 | 0.168599E+11 | 0.238525E+11 | 0.312233E+09 | 0.235403E+11 | 0.00 | 0.00 |
Minimum of Months | 0.161069E+10 | 3789628.33 | 0.140088E+10 | 0.00 | 0.140088E+10 | 0.00 | 0.00 |
Maximum of Months | 0.920368E+10 | 0.371947E+10 | 0.259670E+10 | 0.144161E+09 | 0.245254E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.241185E+10 | 0.229898E+10 | 0.181004E+10 | 0.547624E+09 | 0.126241E+10 | 0.00 | 0.00 |
February | 0.266305E+10 | 0.176368E+10 | 0.178163E+10 | 0.482831E+09 | 0.129880E+10 | 0.00 | 0.00 |
March | 0.379311E+10 | 0.147720E+10 | 0.217885E+10 | 0.537008E+09 | 0.164185E+10 | 0.00 | 0.00 |
April | 0.525531E+10 | 0.911874E+09 | 0.256727E+10 | 0.748018E+09 | 0.181925E+10 | 0.00 | 0.00 |
May | 0.726192E+10 | 0.292626E+09 | 0.296462E+10 | 0.944545E+09 | 0.202008E+10 | 0.00 | 0.00 |
June | 0.738979E+10 | 94139726.86 | 0.280974E+10 | 0.859248E+09 | 0.195049E+10 | 0.00 | 0.00 |
July | 0.817347E+10 | 5252940.90 | 0.270987E+10 | 0.781250E+09 | 0.192862E+10 | 0.00 | 0.00 |
August | 0.841968E+10 | 1855229.86 | 0.277486E+10 | 0.851642E+09 | 0.192322E+10 | 0.00 | 0.00 |
September | 0.662268E+10 | 0.124013E+09 | 0.252454E+10 | 0.780305E+09 | 0.174423E+10 | 0.00 | 0.00 |
October | 0.538280E+10 | 0.490284E+09 | 0.236713E+10 | 0.773342E+09 | 0.159379E+10 | 0.00 | 0.00 |
November | 0.365212E+10 | 0.106043E+10 | 0.191967E+10 | 0.608054E+09 | 0.131162E+10 | 0.00 | 0.00 |
December | 0.237103E+10 | 0.188265E+10 | 0.160558E+10 | 0.440507E+09 | 0.116507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.633968E+11 | 0.104030E+11 | 0.280138E+11 | 0.835437E+10 | 0.196594E+11 | 0.00 | 0.00 |
Minimum of Months | 0.237103E+10 | 1855229.86 | 0.160558E+10 | 0.440507E+09 | 0.116507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.841968E+10 | 0.229898E+10 | 0.296462E+10 | 0.944545E+09 | 0.202008E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.759640E+10 | 0.358771E+10 | 0.485069E+10 | 0.228053E+10 | 0.257016E+10 | 0.00 | 0.00 |
February | 0.686067E+10 | 0.282424E+10 | 0.411420E+10 | 0.168289E+10 | 0.243131E+10 | 0.00 | 0.00 |
March | 0.699471E+10 | 0.244370E+10 | 0.374897E+10 | 0.101783E+10 | 0.273115E+10 | 0.00 | 0.00 |
April | 0.627363E+10 | 0.151016E+10 | 0.285191E+10 | 0.302357E+09 | 0.254956E+10 | 0.00 | 0.00 |
May | 0.726985E+10 | 0.433238E+09 | 0.249634E+10 | 38229006.22 | 0.245811E+10 | 0.00 | 0.00 |
June | 0.740542E+10 | 0.115651E+09 | 0.227514E+10 | 2815574.52 | 0.227233E+10 | 0.00 | 0.00 |
July | 0.896525E+10 | 6038579.64 | 0.235092E+10 | 19975623.99 | 0.233094E+10 | 0.00 | 0.00 |
August | 0.100342E+11 | 2667746.82 | 0.272688E+10 | 0.193210E+09 | 0.253367E+10 | 0.00 | 0.00 |
September | 0.976788E+10 | 0.189930E+09 | 0.347944E+10 | 0.797415E+09 | 0.268202E+10 | 0.00 | 0.00 |
October | 0.106031E+11 | 0.786803E+09 | 0.470711E+10 | 0.187134E+10 | 0.283577E+10 | 0.00 | 0.00 |
November | 0.961567E+10 | 0.175710E+10 | 0.502538E+10 | 0.242261E+10 | 0.260278E+10 | 0.00 | 0.00 |
December | 0.802998E+10 | 0.306439E+10 | 0.482058E+10 | 0.238122E+10 | 0.243936E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.994167E+11 | 0.167216E+11 | 0.434476E+11 | 0.130104E+11 | 0.304372E+11 | 0.00 | 0.00 |
Minimum of Months | 0.627363E+10 | 2667746.82 | 0.227514E+10 | 2815574.52 | 0.227233E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106031E+11 | 0.358771E+10 | 0.502538E+10 | 0.242261E+10 | 0.283577E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.241834E+10 | 0.271802E+10 | 0.177507E+10 | 0.509815E+09 | 0.126525E+10 | 0.00 | 0.00 |
February | 0.275296E+10 | 0.217123E+10 | 0.183079E+10 | 0.522068E+09 | 0.130872E+10 | 0.00 | 0.00 |
March | 0.412136E+10 | 0.193047E+10 | 0.240098E+10 | 0.710816E+09 | 0.169016E+10 | 0.00 | 0.00 |
April | 0.505557E+10 | 0.129319E+10 | 0.253922E+10 | 0.713384E+09 | 0.182583E+10 | 0.00 | 0.00 |
May | 0.706290E+10 | 0.359319E+09 | 0.285606E+10 | 0.854933E+09 | 0.200112E+10 | 0.00 | 0.00 |
June | 0.740782E+10 | 0.130816E+09 | 0.285629E+10 | 0.900378E+09 | 0.195591E+10 | 0.00 | 0.00 |
July | 0.798538E+10 | 13820963.05 | 0.270768E+10 | 0.774614E+09 | 0.193307E+10 | 0.00 | 0.00 |
August | 0.814038E+10 | 8250074.77 | 0.277778E+10 | 0.844564E+09 | 0.193322E+10 | 0.00 | 0.00 |
September | 0.667855E+10 | 0.151152E+09 | 0.255715E+10 | 0.803382E+09 | 0.175376E+10 | 0.00 | 0.00 |
October | 0.532812E+10 | 0.617750E+09 | 0.234830E+10 | 0.758567E+09 | 0.158974E+10 | 0.00 | 0.00 |
November | 0.368679E+10 | 0.143101E+10 | 0.195298E+10 | 0.638686E+09 | 0.131429E+10 | 0.00 | 0.00 |
December | 0.248158E+10 | 0.253728E+10 | 0.168944E+10 | 0.510689E+09 | 0.117876E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.631198E+11 | 0.133623E+11 | 0.282917E+11 | 0.854189E+10 | 0.197498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.241834E+10 | 8250074.77 | 0.168944E+10 | 0.509815E+09 | 0.117876E+10 | 0.00 | 0.00 |
Maximum of Months | 0.814038E+10 | 0.271802E+10 | 0.285629E+10 | 0.900378E+09 | 0.200112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.174300E+10 | 0.331449E+10 | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.00 | 0.00 |
February | 0.215060E+10 | 0.254298E+10 | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.00 | 0.00 |
March | 0.341300E+10 | 0.218094E+10 | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.00 | 0.00 |
April | 0.479152E+10 | 0.134391E+10 | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.00 | 0.00 |
May | 0.754076E+10 | 0.343777E+09 | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.00 | 0.00 |
June | 0.843205E+10 | 79109052.42 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
July | 0.971650E+10 | 1898465.13 | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.00 | 0.00 |
August | 0.957666E+10 | 216718.08 | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.00 | 0.00 |
September | 0.700279E+10 | 0.112362E+09 | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.00 | 0.00 |
October | 0.517625E+10 | 0.569221E+09 | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.00 | 0.00 |
November | 0.316863E+10 | 0.152569E+10 | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.00 | 0.00 |
December | 0.193927E+10 | 0.274489E+10 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.646510E+11 | 0.147595E+11 | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.00 | 0.00 |
Minimum of Months | 0.174300E+10 | 216718.08 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Maximum of Months | 0.971650E+10 | 0.331449E+10 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.243370E+10 | 0.215339E+10 | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.00 | 0.00 |
February | 0.266488E+10 | 0.166725E+10 | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.00 | 0.00 |
March | 0.377529E+10 | 0.143966E+10 | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.00 | 0.00 |
April | 0.524039E+10 | 0.911881E+09 | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.00 | 0.00 |
May | 0.735647E+10 | 0.237380E+09 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
June | 0.752650E+10 | 52776510.88 | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.00 | 0.00 |
July | 0.839668E+10 | 1217495.39 | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.00 | 0.00 |
August | 0.866947E+10 | 114553.92 | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.00 | 0.00 |
September | 0.680404E+10 | 75487374.31 | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.00 | 0.00 |
October | 0.548853E+10 | 0.382210E+09 | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.00 | 0.00 |
November | 0.366410E+10 | 0.100983E+10 | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.00 | 0.00 |
December | 0.238259E+10 | 0.179278E+10 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.644026E+11 | 0.972398E+10 | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.00 | 0.00 |
Minimum of Months | 0.238259E+10 | 114553.92 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.866947E+10 | 0.215339E+10 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.754588E+10 | 0.349037E+10 | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.00 | 0.00 |
February | 0.682887E+10 | 0.271166E+10 | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.00 | 0.00 |
March | 0.699413E+10 | 0.234740E+10 | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.00 | 0.00 |
April | 0.634846E+10 | 0.143002E+10 | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.00 | 0.00 |
May | 0.751427E+10 | 0.349032E+09 | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.00 | 0.00 |
June | 0.775903E+10 | 58693220.59 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
July | 0.942464E+10 | 728620.46 | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.00 | 0.00 |
August | 0.105195E+11 | 152909.78 | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.00 | 0.00 |
September | 0.100338E+11 | 0.130049E+09 | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.00 | 0.00 |
October | 0.107283E+11 | 0.661290E+09 | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.00 | 0.00 |
November | 0.960808E+10 | 0.168648E+10 | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.00 | 0.00 |
December | 0.801190E+10 | 0.294584E+10 | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101317E+12 | 0.158117E+11 | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.00 | 0.00 |
Minimum of Months | 0.634846E+10 | 152909.78 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107283E+11 | 0.349037E+10 | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.251091E+10 | 0.238643E+10 | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.00 | 0.00 |
February | 0.284935E+10 | 0.184518E+10 | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.00 | 0.00 |
March | 0.423510E+10 | 0.162672E+10 | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.00 | 0.00 |
April | 0.519999E+10 | 0.106580E+10 | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.00 | 0.00 |
May | 0.716982E+10 | 0.304532E+09 | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.00 | 0.00 |
June | 0.760885E+10 | 76005012.55 | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.00 | 0.00 |
July | 0.831841E+10 | 3074992.86 | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.00 | 0.00 |
August | 0.855113E+10 | 1020929.38 | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.00 | 0.00 |
September | 0.683062E+10 | 0.110765E+09 | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.00 | 0.00 |
October | 0.547604E+10 | 0.491438E+09 | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.00 | 0.00 |
November | 0.381870E+10 | 0.117086E+10 | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.00 | 0.00 |
December | 0.264773E+10 | 0.202597E+10 | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.652167E+11 | 0.111078E+11 | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251091E+10 | 1020929.38 | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.00 | 0.00 |
Maximum of Months | 0.855113E+10 | 0.238643E+10 | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180753E+10 | 0.310783E+10 | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.00 | 0.00 |
February | 0.217467E+10 | 0.242810E+10 | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.00 | 0.00 |
March | 0.339637E+10 | 0.212869E+10 | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.00 | 0.00 |
April | 0.473788E+10 | 0.135274E+10 | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.00 | 0.00 |
May | 0.744334E+10 | 0.360928E+09 | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.00 | 0.00 |
June | 0.832703E+10 | 88453358.34 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
July | 0.957527E+10 | 3160680.04 | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.00 | 0.00 |
August | 0.944986E+10 | 408938.07 | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.00 | 0.00 |
September | 0.690534E+10 | 0.118881E+09 | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.00 | 0.00 |
October | 0.511934E+10 | 0.583539E+09 | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.00 | 0.00 |
November | 0.315070E+10 | 0.149205E+10 | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.00 | 0.00 |
December | 0.197539E+10 | 0.260642E+10 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.640627E+11 | 0.142712E+11 | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.00 | 0.00 |
Minimum of Months | 0.180753E+10 | 408938.07 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Maximum of Months | 0.957527E+10 | 0.310783E+10 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.249637E+10 | 0.203909E+10 | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.00 | 0.00 |
February | 0.269638E+10 | 0.160180E+10 | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.00 | 0.00 |
March | 0.378285E+10 | 0.140828E+10 | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.00 | 0.00 |
April | 0.522408E+10 | 0.914291E+09 | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.00 | 0.00 |
May | 0.731248E+10 | 0.246071E+09 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
June | 0.747840E+10 | 57633849.08 | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.00 | 0.00 |
July | 0.832562E+10 | 1837436.28 | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.00 | 0.00 |
August | 0.860975E+10 | 199628.34 | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.00 | 0.00 |
September | 0.675994E+10 | 78421524.46 | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.00 | 0.00 |
October | 0.546823E+10 | 0.387273E+09 | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.00 | 0.00 |
November | 0.366912E+10 | 0.988469E+09 | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.00 | 0.00 |
December | 0.242370E+10 | 0.171400E+10 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.642469E+11 | 0.943738E+10 | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.00 | 0.00 |
Minimum of Months | 0.242370E+10 | 199628.34 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.860975E+10 | 0.203909E+10 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.758339E+10 | 0.332471E+10 | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.00 | 0.00 |
February | 0.682843E+10 | 0.261304E+10 | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.00 | 0.00 |
March | 0.696215E+10 | 0.229714E+10 | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.00 | 0.00 |
April | 0.629221E+10 | 0.143480E+10 | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.00 | 0.00 |
May | 0.741588E+10 | 0.364440E+09 | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.00 | 0.00 |
June | 0.765186E+10 | 65294461.69 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
July | 0.928045E+10 | 1361401.06 | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.00 | 0.00 |
August | 0.103923E+11 | 296023.54 | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.00 | 0.00 |
September | 0.993312E+10 | 0.136146E+09 | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.00 | 0.00 |
October | 0.106582E+11 | 0.671354E+09 | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.00 | 0.00 |
November | 0.957022E+10 | 0.165529E+10 | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.00 | 0.00 |
December | 0.802070E+10 | 0.283645E+10 | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100589E+12 | 0.154003E+11 | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.00 | 0.00 |
Minimum of Months | 0.629221E+10 | 296023.54 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106582E+11 | 0.332471E+10 | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.252896E+10 | 0.227143E+10 | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.00 | 0.00 |
February | 0.284698E+10 | 0.178034E+10 | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.00 | 0.00 |
March | 0.420835E+10 | 0.159424E+10 | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.00 | 0.00 |
April | 0.515712E+10 | 0.106558E+10 | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.00 | 0.00 |
May | 0.710630E+10 | 0.313177E+09 | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.00 | 0.00 |
June | 0.754346E+10 | 80761047.04 | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.00 | 0.00 |
July | 0.823335E+10 | 4123971.46 | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.00 | 0.00 |
August | 0.847130E+10 | 1307016.82 | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.00 | 0.00 |
September | 0.676950E+10 | 0.115637E+09 | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.00 | 0.00 |
October | 0.543565E+10 | 0.497649E+09 | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.00 | 0.00 |
November | 0.379766E+10 | 0.114867E+10 | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.00 | 0.00 |
December | 0.265111E+10 | 0.194924E+10 | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.647497E+11 | 0.108222E+11 | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.252896E+10 | 1307016.82 | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.00 | 0.00 |
Maximum of Months | 0.847130E+10 | 0.227143E+10 | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.283644E+11 | -0.279220E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442428331.2 | 60.05 | 0.00 | 0.00 |
February | 0.250780E+11 | -0.246830E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -394971596.6 | 60.05 | 0.00 | 0.00 |
March | 0.274751E+11 | -0.270429E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -432218005.8 | 60.05 | 0.00 | 0.00 |
April | 0.225160E+11 | -0.221129E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -403098972.7 | 60.05 | 0.00 | 0.00 |
May | 0.215075E+11 | -0.211188E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -388698626.4 | 60.05 | 0.00 | 0.00 |
June | 0.194887E+11 | -0.191167E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -371999794.7 | 60.05 | 0.00 | 0.00 |
July | 0.180124E+11 | -0.176362E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -376198421.9 | 60.05 | 0.00 | 0.00 |
August | 0.205275E+11 | -0.201569E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -370580247.3 | 60.05 | 0.00 | 0.00 |
September | 0.205227E+11 | -0.201605E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -362229687.6 | 60.05 | 0.00 | 0.00 |
October | 0.236636E+11 | -0.232840E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -379526057.4 | 60.05 | 0.00 | 0.00 |
November | 0.256123E+11 | -0.252094E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -402883387.6 | 60.05 | 0.00 | 0.00 |
December | 0.271863E+11 | -0.267502E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -436086763.6 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.279954E+12 | -0.275193E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.476092E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.180124E+11 | -0.279220E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -442428331.2 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.283644E+11 | -0.176362E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -362229687.6 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4187.85 | 34.38 | 311.00 | 293.00 | 1081.44 | 25.75 | 306.67 | 280.33 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2168.98 | 26.03 | 160.50 | 274.83 | 966.54 | 21.70 | 215.67 | 244.00 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1604.46 | 20.06 | 41.33 | 314.33 | 827.56 | 21.23 | 242.50 | 277.17 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 1258.39 | 18.99 | 0.67 | 322.83 | 663.56 | 20.27 | 226.17 | 284.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1073.66 | 18.93 | 0.00 | 349.67 | 586.61 | 20.25 | 186.33 | 304.17 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:10 | 1029.03 | 18.86 | 0.00 | 344.33 | 571.46 | 20.21 | 187.33 | 298.67 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1080.69 | 18.79 | 0.00 | 345.17 | 592.75 | 20.13 | 219.83 | 304.00 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1265.49 | 19.26 | 13.67 | 343.17 | 675.68 | 20.59 | 261.50 | 304.00 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 1577.57 | 20.02 | 71.00 | 318.67 | 826.79 | 21.36 | 258.00 | 284.83 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:19 | 2096.10 | 21.89 | 116.83 | 316.67 | 992.90 | 22.22 | 272.33 | 287.83 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3529.96 | 32.29 | 257.33 | 298.17 | 1121.01 | 25.39 | 312.67 | 281.83 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4175.93 | 34.74 | 308.17 | 289.00 | 1154.67 | 26.89 | 301.00 | 275.17 |
Annual Sum or Average | 4323.33 | 0.51 | 1994.77 | 23.19 | 1280.50 | 3809.83 | 819.08 | 21.99 | 2990.00 | 3426.67 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 1029.03 | 18.79 | 0.00 | 274.83 | 571.46 | 20.13 | 186.33 | 244.00 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 4187.85 | 34.74 | 311.00 | 349.67 | 1154.67 | 26.89 | 312.67 | 304.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-07:00 | 1543.18 | 23.78 | 112.00 | 275.33 | 805.53 | 23.84 | 173.00 | 236.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-07:40 | 1668.33 | 23.48 | 102.67 | 263.33 | 715.93 | 22.41 | 155.00 | 227.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-07:00 | 1572.14 | 22.75 | 97.50 | 309.17 | 797.96 | 23.01 | 167.50 | 271.33 |
April | 375.00 | 0.52 | 0.48 | 01-APR-06:00 | 1825.70 | 22.64 | 109.33 | 320.50 | 929.51 | 22.97 | 150.83 | 284.33 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2071.31 | 23.40 | 129.50 | 359.00 | 877.24 | 22.68 | 159.00 | 321.33 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:10 | 1995.88 | 23.32 | 126.50 | 353.33 | 866.27 | 22.77 | 164.67 | 318.33 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1880.79 | 23.06 | 123.67 | 348.33 | 828.03 | 22.45 | 167.33 | 312.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1928.76 | 22.77 | 114.17 | 341.50 | 860.57 | 22.16 | 173.50 | 307.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1926.22 | 23.59 | 107.00 | 311.50 | 986.87 | 23.89 | 183.67 | 285.50 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-06:49 | 1793.52 | 23.59 | 107.00 | 305.33 | 921.91 | 23.79 | 194.17 | 275.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1550.71 | 23.61 | 93.83 | 279.17 | 794.12 | 23.73 | 179.17 | 244.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1276.48 | 22.56 | 86.00 | 269.33 | 660.28 | 22.67 | 161.33 | 225.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1770.70 | 23.20 | 1309.17 | 3735.83 | 841.75 | 23.01 | 2029.17 | 3310.50 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1276.48 | 22.56 | 86.00 | 263.33 | 660.28 | 22.16 | 150.83 | 225.33 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 2071.31 | 23.78 | 129.50 | 359.00 | 986.87 | 23.89 | 194.17 | 321.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:30 | 604.68 | 16.87 | 0.00 | 260.33 | 347.02 | 18.18 | 0.00 | 179.83 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-08:50 | 687.65 | 17.71 | 0.00 | 253.33 | 393.69 | 19.02 | 0.00 | 192.67 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:39 | 801.27 | 18.34 | 0.00 | 306.17 | 452.43 | 19.60 | 1.50 | 254.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 917.28 | 18.58 | 0.00 | 327.00 | 510.74 | 19.81 | 75.83 | 286.50 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:49 | 1080.04 | 19.60 | 3.50 | 368.50 | 592.15 | 20.81 | 186.00 | 333.50 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:40 | 1193.52 | 22.45 | 96.17 | 366.00 | 641.39 | 21.25 | 236.00 | 332.17 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1154.75 | 20.50 | 41.00 | 358.50 | 625.87 | 21.84 | 252.83 | 327.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:00 | 1047.22 | 19.26 | 0.17 | 350.17 | 581.18 | 20.57 | 187.00 | 315.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 915.14 | 18.96 | 0.00 | 317.00 | 520.50 | 20.27 | 69.67 | 275.33 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:40 | 758.30 | 18.10 | 0.00 | 300.00 | 441.46 | 19.43 | 1.50 | 247.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-07:00 | 656.68 | 17.78 | 0.00 | 262.33 | 383.67 | 19.16 | 0.00 | 198.67 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:39 | 586.35 | 16.99 | 0.00 | 250.00 | 336.97 | 18.33 | 0.00 | 160.17 |
Annual Sum or Average | 4323.33 | 0.52 | 886.27 | 18.88 | 140.83 | 3719.33 | 495.31 | 19.95 | 1010.33 | 3104.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 586.35 | 16.87 | 0.00 | 250.00 | 336.97 | 18.18 | 0.00 | 160.17 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1193.52 | 22.45 | 96.17 | 368.50 | 641.39 | 21.84 | 252.83 | 333.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-09:30 | 1497.00 | 23.48 | 108.17 | 274.33 | 774.48 | 23.58 | 175.50 | 235.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:00 | 1468.10 | 22.28 | 76.33 | 262.33 | 736.75 | 22.43 | 159.00 | 223.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:00 | 1683.72 | 22.95 | 96.67 | 309.83 | 849.71 | 23.13 | 176.00 | 273.17 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:20 | 1701.17 | 19.62 | 55.00 | 324.67 | 878.74 | 19.49 | 116.83 | 288.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:40 | 1784.67 | 17.87 | 0.00 | 350.17 | 921.79 | 19.83 | 119.50 | 315.50 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:30 | 1898.82 | 18.06 | 0.00 | 345.83 | 974.28 | 20.01 | 130.00 | 313.00 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:40 | 1818.30 | 18.03 | 3.67 | 348.17 | 822.90 | 19.77 | 130.50 | 310.33 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1856.27 | 20.11 | 59.83 | 342.67 | 953.72 | 20.16 | 142.83 | 309.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:49 | 1797.39 | 22.21 | 87.17 | 318.17 | 920.63 | 22.58 | 174.33 | 287.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:00 | 1856.26 | 23.81 | 110.33 | 303.33 | 954.88 | 24.01 | 192.50 | 273.83 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-08:09 | 1614.74 | 24.02 | 99.50 | 278.33 | 828.72 | 24.12 | 180.83 | 245.33 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:39 | 1411.20 | 23.62 | 101.83 | 269.67 | 723.64 | 23.69 | 172.67 | 227.83 |
Annual Sum or Average | 4323.33 | 0.52 | 1712.02 | 21.14 | 798.50 | 3727.50 | 867.49 | 21.75 | 1870.50 | 3303.17 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1411.20 | 17.87 | 0.00 | 262.33 | 723.64 | 19.49 | 116.83 | 223.83 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 1898.82 | 24.02 | 110.33 | 350.17 | 974.28 | 24.12 | 192.50 | 315.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4207.91 | 33.84 | 310.17 | 293.00 | 1147.14 | 21.84 | 91.50 | 280.83 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:00 | 2187.98 | 22.15 | 140.67 | 274.83 | 1028.84 | 16.93 | 0.00 | 246.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1621.56 | 13.67 | 5.00 | 315.00 | 880.29 | 16.86 | 0.00 | 280.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 1273.61 | 13.01 | 0.00 | 323.50 | 705.34 | 16.29 | 0.00 | 289.83 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1088.63 | 13.09 | 0.00 | 350.00 | 623.76 | 16.45 | 0.00 | 310.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:00 | 1044.00 | 12.93 | 0.00 | 344.33 | 607.73 | 16.34 | 0.00 | 304.33 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1095.74 | 12.76 | 0.00 | 345.17 | 630.14 | 16.11 | 0.00 | 308.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1281.34 | 13.32 | 0.00 | 343.83 | 718.02 | 16.66 | 0.00 | 308.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1597.22 | 13.91 | 0.00 | 318.83 | 879.22 | 17.30 | 0.00 | 289.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:10 | 2125.39 | 15.99 | 34.50 | 317.50 | 1057.25 | 18.02 | 10.50 | 291.17 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3549.26 | 30.55 | 255.33 | 298.33 | 1191.68 | 21.59 | 76.33 | 283.67 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4186.97 | 34.28 | 305.83 | 289.50 | 1220.80 | 23.26 | 113.00 | 276.50 |
Annual Sum or Average | 4323.33 | 0.51 | 2012.28 | 18.47 | 1051.50 | 3813.83 | 870.36 | 17.97 | 291.33 | 3469.83 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 1044.00 | 12.76 | 0.00 | 274.83 | 607.73 | 16.11 | 0.00 | 246.67 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 4207.91 | 34.28 | 310.17 | 350.00 | 1220.80 | 23.26 | 113.00 | 310.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-07:00 | 1568.52 | 21.25 | 111.83 | 276.17 | 840.23 | 21.89 | 80.67 | 241.00 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:40 | 1697.93 | 20.78 | 102.33 | 263.67 | 753.19 | 20.04 | 47.17 | 231.00 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-07:00 | 1609.16 | 19.71 | 97.33 | 310.33 | 838.78 | 20.65 | 66.00 | 275.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-06:00 | 1848.78 | 19.73 | 109.33 | 321.17 | 973.06 | 20.70 | 79.67 | 288.67 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2087.84 | 19.65 | 119.33 | 359.83 | 924.35 | 20.19 | 67.83 | 325.83 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:10 | 2026.25 | 20.36 | 125.83 | 354.50 | 912.39 | 20.26 | 66.67 | 321.83 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1904.55 | 19.24 | 114.17 | 348.83 | 873.59 | 19.89 | 61.83 | 315.67 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1948.28 | 19.86 | 113.67 | 342.33 | 907.08 | 19.63 | 56.00 | 311.17 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1959.49 | 20.70 | 106.83 | 311.83 | 1033.19 | 21.66 | 77.33 | 288.17 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-06:49 | 1830.29 | 20.66 | 104.67 | 306.33 | 964.93 | 21.65 | 75.83 | 278.67 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1567.55 | 19.85 | 84.33 | 279.33 | 832.76 | 21.60 | 63.00 | 249.00 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1298.71 | 19.72 | 85.17 | 270.67 | 692.34 | 20.52 | 55.67 | 231.50 |
Annual Sum or Average | 4323.33 | 0.52 | 1796.81 | 20.10 | 1274.83 | 3745.00 | 883.97 | 20.69 | 797.67 | 3358.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1298.71 | 19.24 | 84.33 | 263.67 | 692.34 | 19.63 | 47.17 | 231.00 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 2087.84 | 21.25 | 125.83 | 359.83 | 1033.19 | 21.89 | 80.67 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:20 | 614.13 | 11.11 | 0.00 | 260.50 | 368.96 | 14.50 | 0.00 | 193.17 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:39 | 698.63 | 11.86 | 0.00 | 253.67 | 418.67 | 15.30 | 0.00 | 201.00 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:39 | 814.23 | 12.56 | 0.00 | 306.50 | 481.19 | 15.93 | 0.00 | 260.50 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 931.92 | 12.94 | 0.00 | 327.33 | 543.18 | 16.24 | 0.00 | 291.17 |
May | 405.33 | 0.50 | 0.48 | 01-MAY-06:40 | 1097.14 | 13.76 | 2.83 | 368.67 | 629.82 | 17.15 | 1.17 | 339.00 |
June | 403.50 | 0.50 | 0.48 | 01-JUN-06:19 | 1211.82 | 17.75 | 77.33 | 366.33 | 685.81 | 18.84 | 34.17 | 339.17 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1172.02 | 14.89 | 26.83 | 359.00 | 665.11 | 18.16 | 27.17 | 331.00 |
August | 395.83 | 0.51 | 0.48 | 01-AUG-06:00 | 1063.49 | 13.49 | 0.00 | 350.50 | 617.87 | 16.89 | 0.00 | 319.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 929.92 | 13.46 | 0.00 | 317.33 | 553.57 | 16.82 | 0.00 | 280.67 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 770.75 | 12.66 | 0.00 | 300.67 | 469.62 | 16.06 | 0.00 | 253.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-07:49 | 667.01 | 12.11 | 0.00 | 263.17 | 408.02 | 15.62 | 0.00 | 209.67 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:30 | 595.17 | 11.06 | 0.00 | 251.00 | 358.19 | 14.54 | 0.00 | 174.33 |
Annual Sum or Average | 4323.33 | 0.52 | 900.17 | 13.27 | 107.00 | 3724.67 | 527.04 | 16.45 | 62.50 | 3192.67 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 595.17 | 11.06 | 0.00 | 251.00 | 358.19 | 14.50 | 0.00 | 174.33 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1211.82 | 17.75 | 77.33 | 368.67 | 685.81 | 18.84 | 34.17 | 339.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-09:30 | 1522.02 | 20.93 | 108.17 | 275.83 | 808.86 | 21.62 | 77.17 | 240.83 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:00 | 1498.38 | 19.17 | 76.33 | 263.00 | 774.95 | 20.04 | 48.33 | 227.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:50 | 1723.73 | 19.87 | 96.67 | 311.17 | 893.37 | 20.74 | 65.67 | 277.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:09 | 1722.67 | 15.98 | 55.00 | 325.67 | 921.42 | 16.37 | 0.00 | 292.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1808.02 | 13.42 | 0.00 | 351.00 | 967.92 | 16.65 | 0.00 | 320.67 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-07:19 | 1930.46 | 13.59 | 0.00 | 346.50 | 1020.90 | 16.84 | 0.00 | 317.00 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:30 | 1844.22 | 13.63 | 3.67 | 349.33 | 868.43 | 16.63 | 0.00 | 314.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1874.15 | 16.45 | 59.83 | 342.83 | 1000.35 | 17.08 | 5.50 | 312.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:49 | 1823.98 | 19.10 | 86.83 | 318.00 | 966.96 | 20.14 | 57.33 | 289.67 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:49 | 1894.84 | 21.12 | 110.33 | 304.50 | 997.79 | 21.90 | 79.33 | 277.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-07:00 | 1642.75 | 21.30 | 98.67 | 279.00 | 867.81 | 22.05 | 69.00 | 249.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:30 | 1434.89 | 20.94 | 101.83 | 270.17 | 757.06 | 21.66 | 71.00 | 233.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1739.59 | 17.70 | 797.33 | 3737.00 | 910.00 | 19.12 | 473.33 | 3354.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1434.89 | 13.42 | 0.00 | 263.00 | 757.06 | 16.37 | 0.00 | 227.83 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 1930.46 | 21.30 | 110.33 | 351.00 | 1020.90 | 22.05 | 79.33 | 320.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4210.55 | 33.83 | 310.17 | 293.00 | 1149.14 | 21.83 | 91.50 | 280.83 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:00 | 2190.99 | 22.13 | 140.67 | 274.83 | 1030.70 | 16.91 | 0.00 | 246.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1624.28 | 13.64 | 5.00 | 315.00 | 881.86 | 16.84 | 0.00 | 281.00 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 1275.69 | 12.98 | 0.00 | 323.50 | 706.54 | 16.28 | 0.00 | 289.83 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1090.23 | 13.06 | 0.00 | 350.17 | 624.74 | 16.43 | 0.00 | 310.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:00 | 1045.45 | 12.90 | 0.00 | 344.33 | 608.65 | 16.33 | 0.00 | 304.50 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1097.32 | 12.73 | 0.00 | 345.33 | 631.12 | 16.09 | 0.00 | 308.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1283.33 | 13.29 | 0.00 | 343.83 | 719.21 | 16.64 | 0.00 | 308.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1599.80 | 13.88 | 0.00 | 318.83 | 880.74 | 17.29 | 0.00 | 289.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:10 | 2128.39 | 15.96 | 34.50 | 317.50 | 1059.10 | 18.01 | 10.50 | 291.50 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3552.16 | 30.54 | 255.33 | 298.33 | 1193.74 | 21.58 | 76.33 | 283.67 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4189.43 | 34.27 | 305.83 | 289.50 | 1222.82 | 23.25 | 113.00 | 276.50 |
Annual Sum or Average | 4323.33 | 0.51 | 2014.57 | 18.44 | 1051.50 | 3814.17 | 871.84 | 17.95 | 291.33 | 3471.00 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 1045.45 | 12.73 | 0.00 | 274.83 | 608.65 | 16.09 | 0.00 | 246.67 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 4210.55 | 34.27 | 310.17 | 350.17 | 1222.82 | 23.25 | 113.00 | 310.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-07:00 | 1569.87 | 21.22 | 111.83 | 276.17 | 841.33 | 21.88 | 80.67 | 241.00 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:40 | 1699.51 | 20.75 | 102.33 | 263.67 | 754.37 | 20.03 | 47.17 | 231.33 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-07:00 | 1611.04 | 19.68 | 97.33 | 310.33 | 840.02 | 20.64 | 66.00 | 275.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-06:00 | 1850.67 | 19.70 | 109.33 | 321.17 | 974.33 | 20.68 | 79.67 | 288.67 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2089.68 | 19.62 | 119.33 | 359.83 | 925.65 | 20.18 | 67.83 | 325.83 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:10 | 2028.13 | 20.33 | 125.83 | 354.50 | 913.70 | 20.24 | 66.67 | 321.83 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1906.50 | 19.22 | 114.17 | 348.83 | 874.91 | 19.88 | 61.83 | 316.00 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1950.27 | 19.83 | 113.67 | 342.33 | 908.46 | 19.62 | 56.00 | 311.17 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1961.44 | 20.68 | 106.83 | 312.00 | 1034.60 | 21.65 | 77.33 | 288.17 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-06:49 | 1831.86 | 20.63 | 104.67 | 306.33 | 966.24 | 21.64 | 75.83 | 278.83 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1568.95 | 19.83 | 84.33 | 279.33 | 833.93 | 21.59 | 63.00 | 249.00 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1299.98 | 19.70 | 85.17 | 270.67 | 693.38 | 20.50 | 55.67 | 231.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1798.54 | 20.07 | 1274.83 | 3745.17 | 885.23 | 20.67 | 797.67 | 3359.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1299.98 | 19.22 | 84.33 | 263.67 | 693.38 | 19.62 | 47.17 | 231.33 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 2089.68 | 21.22 | 125.83 | 359.83 | 1034.60 | 21.88 | 80.67 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:20 | 614.83 | 11.08 | 0.00 | 260.50 | 369.50 | 14.48 | 0.00 | 193.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:39 | 699.46 | 11.83 | 0.00 | 253.67 | 419.29 | 15.28 | 0.00 | 201.33 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:39 | 815.27 | 12.53 | 0.00 | 306.67 | 481.92 | 15.92 | 0.00 | 260.67 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 933.17 | 12.91 | 0.00 | 327.33 | 544.02 | 16.23 | 0.00 | 291.50 |
May | 405.33 | 0.50 | 0.48 | 01-MAY-06:40 | 1098.62 | 13.73 | 2.83 | 368.67 | 630.80 | 17.14 | 1.17 | 339.00 |
June | 403.50 | 0.50 | 0.48 | 01-JUN-06:19 | 1213.48 | 17.72 | 77.33 | 366.33 | 686.90 | 18.82 | 34.17 | 339.17 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1173.65 | 14.86 | 26.83 | 359.00 | 666.18 | 18.15 | 27.17 | 331.17 |
August | 395.83 | 0.51 | 0.48 | 01-AUG-06:00 | 1064.89 | 13.46 | 0.00 | 350.50 | 618.83 | 16.87 | 0.00 | 319.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 931.04 | 13.43 | 0.00 | 317.33 | 554.39 | 16.80 | 0.00 | 280.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 771.59 | 12.63 | 0.00 | 300.67 | 470.28 | 16.05 | 0.00 | 253.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-07:49 | 667.71 | 12.08 | 0.00 | 263.17 | 408.59 | 15.61 | 0.00 | 209.83 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:30 | 595.84 | 11.03 | 0.00 | 251.00 | 358.72 | 14.52 | 0.00 | 174.83 |
Annual Sum or Average | 4323.33 | 0.52 | 901.32 | 13.24 | 107.00 | 3724.83 | 527.85 | 16.43 | 62.50 | 3194.83 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 595.84 | 11.03 | 0.00 | 251.00 | 358.72 | 14.48 | 0.00 | 174.83 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1213.48 | 17.72 | 77.33 | 368.67 | 686.90 | 18.82 | 34.17 | 339.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-09:30 | 1523.37 | 20.91 | 108.17 | 276.00 | 809.96 | 21.61 | 77.17 | 240.83 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:00 | 1499.99 | 19.14 | 76.33 | 263.00 | 776.15 | 20.03 | 48.33 | 227.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:50 | 1715.05 | 18.72 | 85.83 | 310.17 | 894.66 | 20.72 | 65.67 | 278.17 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:09 | 1724.59 | 15.95 | 55.00 | 326.00 | 922.72 | 16.36 | 0.00 | 292.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1809.90 | 13.39 | 0.00 | 351.00 | 969.23 | 16.64 | 0.00 | 320.83 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-07:19 | 1932.40 | 13.56 | 0.00 | 346.83 | 1022.24 | 16.82 | 0.00 | 317.00 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:30 | 1846.21 | 13.60 | 3.67 | 349.33 | 869.78 | 16.61 | 0.00 | 314.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1876.18 | 16.42 | 59.83 | 343.00 | 1001.77 | 17.06 | 5.50 | 312.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:49 | 1826.01 | 19.07 | 86.83 | 318.17 | 968.39 | 20.13 | 57.33 | 289.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:49 | 1896.53 | 21.09 | 110.33 | 304.50 | 999.08 | 21.89 | 79.33 | 277.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-07:00 | 1644.13 | 21.27 | 98.67 | 279.17 | 868.98 | 22.04 | 69.00 | 249.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:30 | 1436.18 | 20.92 | 101.83 | 270.17 | 758.12 | 21.65 | 71.00 | 233.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1740.49 | 17.58 | 786.50 | 3737.33 | 911.28 | 19.10 | 473.33 | 3355.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1436.18 | 13.39 | 0.00 | 263.00 | 758.12 | 16.36 | 0.00 | 227.83 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 1932.40 | 21.27 | 110.33 | 351.00 | 1022.24 | 22.04 | 79.33 | 320.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 29563440.10 | 1531.98 | 03-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1257132.59 | 337.01 | 13-FEB-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 76258.51 | 127.10 | 18-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30896831.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29563440.10 | 1531.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6188111.43 | 1070.72 | 02-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6188111.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6188111.43 | 1070.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.659805E+11 | 0.632312E+11 | 224274.84 | 30-JAN-05:12 | 156540.21 | 0.56 |
February | 0.00 | 0.00 | 0.830377E+11 | 0.770555E+11 | 249865.19 | 09-FEB-05:11 | 165995.61 | 0.61 |
March | 0.00 | 0.00 | 0.128488E+12 | 0.120165E+12 | 234376.65 | 24-MAR-04:12 | 158561.36 | 0.71 |
April | 0.00 | 0.00 | 0.176376E+12 | 0.156271E+12 | 228822.89 | 30-APR-16:22 | 135938.48 | 0.84 |
May | 0.00 | 0.00 | 0.257036E+12 | 0.217784E+12 | 302040.70 | 30-MAY-03:02 | 190985.30 | 0.86 |
June | 0.00 | 0.00 | 0.319457E+12 | 0.240362E+12 | 310847.51 | 19-JUN-03:02 | 193123.31 | 0.89 |
July | 0.00 | 0.00 | 0.378905E+12 | 0.270458E+12 | 327522.74 | 24-JUL-03:02 | 202280.35 | 0.88 |
August | 0.00 | 0.00 | 0.420111E+12 | 0.300066E+12 | 326393.62 | 27-AUG-14:21 | 210081.72 | 0.89 |
September | 0.00 | 0.00 | 0.329700E+12 | 0.233681E+12 | 331983.13 | 10-SEP-17:42 | 201483.30 | 0.88 |
October | 0.00 | 0.00 | 0.274492E+12 | 0.214577E+12 | 306399.23 | 02-OCT-03:02 | 191317.80 | 0.86 |
November | 0.00 | 0.00 | 0.173588E+12 | 0.147232E+12 | 249162.23 | 03-NOV-04:12 | 161483.57 | 0.80 |
December | 0.00 | 0.00 | 0.109327E+12 | 0.977051E+11 | 228575.82 | 12-DEC-05:12 | 162748.31 | 0.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.271650E+13 | 0.213859E+13 | 0.79 | |||
Minimum of Months | 0.00 | 0.00 | 0.659805E+11 | 0.632312E+11 | 224274.84 | 135938.48 | 0.56 | |
Maximum of Months | 0.00 | 0.00 | 0.420111E+12 | 0.300066E+12 | 331983.13 | 210081.72 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.471943E+12 | 0.449866E+12 | 1830104.22 | 30-JAN-06:02 | 1219923.49 | 0.54 |
February | 0.00 | 0.00 | 0.576262E+12 | 0.528391E+12 | 2050625.12 | 06-FEB-05:11 | 1418032.63 | 0.57 |
March | 0.00 | 0.00 | 0.880244E+12 | 0.815358E+12 | 2039518.57 | 01-MAR-06:02 | 1357852.45 | 0.60 |
April | 0.00 | 0.00 | 0.119882E+13 | 0.104775E+13 | 2087280.87 | 10-APR-04:12 | 1394515.97 | 0.66 |
May | 0.00 | 0.00 | 0.196357E+13 | 0.160361E+13 | 2721967.57 | 24-MAY-05:02 | 1606864.18 | 0.81 |
June | 0.00 | 0.00 | 0.253204E+13 | 0.175605E+13 | 2902405.58 | 04-JUN-16:41 | 1504333.12 | 0.87 |
July | 0.00 | 0.00 | 0.303350E+13 | 0.195813E+13 | 3181062.67 | 30-JUL-16:22 | 1556944.17 | 0.87 |
August | 0.00 | 0.00 | 0.328584E+13 | 0.210080E+13 | 3021160.18 | 01-AUG-05:01 | 1707911.22 | 0.88 |
September | 0.00 | 0.00 | 0.260503E+13 | 0.167269E+13 | 3117058.35 | 10-SEP-16:52 | 1437751.28 | 0.84 |
October | 0.00 | 0.00 | 0.190632E+13 | 0.139415E+13 | 2738255.28 | 07-OCT-05:02 | 1596602.79 | 0.73 |
November | 0.00 | 0.00 | 0.119330E+13 | 0.977640E+12 | 2123095.39 | 04-NOV-04:12 | 1483883.04 | 0.62 |
December | 0.00 | 0.00 | 0.670524E+12 | 0.588465E+12 | 1951536.59 | 12-DEC-06:03 | 1333034.58 | 0.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.203174E+14 | 0.148929E+14 | 0.71 | |||
Minimum of Months | 0.00 | 0.00 | 0.471943E+12 | 0.449866E+12 | 1830104.22 | 1219923.49 | 0.54 | |
Maximum of Months | 0.00 | 0.00 | 0.328584E+13 | 0.210080E+13 | 3181062.67 | 1707911.22 | 0.88 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.426780E+11 | 0.404979E+11 | 176024.70 | 30-JAN-06:02 | 115130.25 | 0.53 |
February | 0.00 | 0.00 | 0.558652E+11 | 0.510935E+11 | 207526.91 | 06-FEB-05:11 | 137439.84 | 0.56 |
March | 0.00 | 0.00 | 0.887835E+11 | 0.822861E+11 | 201769.68 | 01-MAR-06:02 | 132472.69 | 0.59 |
April | 0.00 | 0.00 | 0.124808E+12 | 0.109675E+12 | 259286.52 | 30-APR-14:51 | 145217.71 | 0.65 |
May | 0.00 | 0.00 | 0.210207E+12 | 0.173980E+12 | 308381.35 | 30-MAY-04:03 | 188097.75 | 0.81 |
June | 0.00 | 0.00 | 0.268905E+12 | 0.191122E+12 | 315219.51 | 04-JUN-16:51 | 169625.54 | 0.87 |
July | 0.00 | 0.00 | 0.321842E+12 | 0.214569E+12 | 345479.52 | 30-JUL-16:22 | 176341.18 | 0.87 |
August | 0.00 | 0.00 | 0.346954E+12 | 0.229013E+12 | 334623.44 | 01-AUG-05:01 | 193983.17 | 0.88 |
September | 0.00 | 0.00 | 0.272762E+12 | 0.179506E+12 | 322409.24 | 11-SEP-05:02 | 190541.73 | 0.84 |
October | 0.00 | 0.00 | 0.195642E+12 | 0.144554E+12 | 298918.45 | 07-OCT-05:02 | 176980.16 | 0.73 |
November | 0.00 | 0.00 | 0.118315E+12 | 0.969432E+11 | 226328.82 | 02-NOV-04:12 | 147166.97 | 0.61 |
December | 0.00 | 0.00 | 0.631197E+11 | 0.550812E+11 | 194603.72 | 11-DEC-06:03 | 127164.33 | 0.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.210988E+13 | 0.156832E+13 | 0.71 | |||
Minimum of Months | 0.00 | 0.00 | 0.426780E+11 | 0.404979E+11 | 176024.70 | 115130.25 | 0.53 | |
Maximum of Months | 0.00 | 0.00 | 0.346954E+12 | 0.229013E+12 | 345479.52 | 193983.17 | 0.88 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.647317E+11 | 0.625269E+11 | 141107.33 | 30-JAN-07:51 | 102311.17 | 0.53 |
February | 0.00 | 0.00 | 0.557204E+11 | 0.528386E+11 | 254032.84 | 09-FEB-16:52 | 76683.82 | 0.45 |
March | 0.00 | 0.00 | 0.591253E+11 | 0.532410E+11 | 258687.15 | 29-MAR-03:55 | 74326.26 | 0.37 |
April | 0.00 | 0.00 | 0.398288E+11 | 0.328570E+11 | 270929.52 | 30-APR-03:03 | 74055.17 | 0.19 |
May | 0.00 | 0.00 | 0.673392E+10 | 0.511817E+10 | 182171.75 | 01-MAY-04:22 | 98031.02 | 0.02 |
June | 0.00 | 0.00 | 0.673713E+10 | 0.499192E+10 | 271847.27 | 22-JUN-07:52 | 75129.82 | 0.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.131663E+11 | 0.103149E+11 | 276767.61 | 29-OCT-02:25 | 77566.26 | 0.03 |
November | 0.00 | 0.00 | 0.635228E+11 | 0.521656E+11 | 269672.82 | 04-NOV-04:33 | 77200.15 | 0.26 |
December | 0.00 | 0.00 | 0.697030E+11 | 0.634370E+11 | 249916.40 | 12-DEC-20:31 | 81302.97 | 0.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.379269E+12 | 0.337491E+12 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.697030E+11 | 0.634370E+11 | 276767.61 | 102311.17 | 0.53 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.353244E+12 | 0.342500E+12 | 142180.98 | 30-JAN-15:00 | 131245.46 | 0.00 |
February | 0.00 | 0.00 | 0.544231E+12 | 0.531136E+12 | 236714.85 | 07-FEB-16:10 | 225002.42 | 0.00 |
March | 0.00 | 0.00 | 0.848318E+12 | 0.835534E+12 | 407952.87 | 31-MAR-23:05 | 397157.98 | 0.00 |
April | 0.00 | 0.00 | 0.106253E+13 | 0.104903E+13 | 421680.79 | 30-APR-14:53 | 407960.63 | 0.00 |
May | 0.00 | 0.00 | 0.376608E+12 | 0.358667E+12 | 230993.11 | 31-MAY-23:03 | 220099.16 | 0.00 |
June | 0.00 | 0.00 | 0.614262E+12 | 0.586444E+12 | 329051.66 | 30-JUN-23:03 | 311106.16 | 0.00 |
July | 0.00 | 0.00 | 0.889514E+12 | 0.856036E+12 | 425123.79 | 31-JUL-23:03 | 404941.77 | 0.00 |
August | 0.00 | 0.00 | 0.113750E+13 | 0.110298E+13 | 444636.27 | 04-AUG-14:00 | 419976.40 | 0.00 |
September | 0.00 | 0.00 | 0.384015E+12 | 0.353367E+12 | 242336.18 | 30-SEP-23:05 | 219613.56 | 0.00 |
October | 0.00 | 0.00 | 0.630464E+12 | 0.606223E+12 | 319457.14 | 31-OCT-23:05 | 310366.05 | 0.00 |
November | 0.00 | 0.00 | 0.834289E+12 | 0.817148E+12 | 334774.11 | 01-NOV-15:00 | 319174.08 | 0.00 |
December | 0.00 | 0.00 | 0.109985E+13 | 0.108247E+13 | 421128.92 | 05-DEC-17:00 | 408240.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.877482E+13 | 0.852154E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.353244E+12 | 0.342500E+12 | 142180.98 | 131245.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.113750E+13 | 0.110298E+13 | 444636.27 | 419976.40 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.552151E+10 | 0.518336E+10 | 2623.58 | 29-JAN-17:35 | 2360.28 | 0.00 |
February | 0.00 | 0.00 | 0.994741E+10 | 0.949677E+10 | 4744.84 | 07-FEB-16:10 | 4255.06 | 0.00 |
March | 0.00 | 0.00 | 0.162563E+11 | 0.157874E+11 | 8098.75 | 31-MAR-23:05 | 7612.79 | 0.00 |
April | 0.00 | 0.00 | 0.210560E+11 | 0.204501E+11 | 8849.21 | 30-APR-21:33 | 8393.87 | 0.00 |
May | 0.00 | 0.00 | 0.733537E+10 | 0.659858E+10 | 4736.75 | 31-MAY-23:03 | 4284.76 | 0.00 |
June | 0.00 | 0.00 | 0.126220E+11 | 0.114208E+11 | 6901.31 | 30-JUN-23:03 | 6099.28 | 0.00 |
July | 0.00 | 0.00 | 0.186869E+11 | 0.171912E+11 | 8654.03 | 31-JUL-24:00 | 7966.64 | 0.00 |
August | 0.00 | 0.00 | 0.228770E+11 | 0.213277E+11 | 8928.92 | 27-AUG-06:00 | 8123.33 | 0.00 |
September | 0.00 | 0.00 | 0.786045E+10 | 0.658139E+10 | 5219.45 | 30-SEP-23:05 | 4229.06 | 0.00 |
October | 0.00 | 0.00 | 0.126213E+11 | 0.115863E+11 | 6329.84 | 31-OCT-23:05 | 5937.00 | 0.00 |
November | 0.00 | 0.00 | 0.163326E+11 | 0.155994E+11 | 6914.23 | 01-NOV-16:00 | 6262.35 | 0.00 |
December | 0.00 | 0.00 | 0.212434E+11 | 0.206675E+11 | 8571.07 | 05-DEC-17:00 | 7992.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.172360E+12 | 0.161890E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.552151E+10 | 0.518336E+10 | 2623.58 | 2360.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.228770E+11 | 0.213277E+11 | 8928.92 | 8393.87 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.458040E+11 | 0.425667E+11 | 23497.93 | 30-JAN-15:00 | 19431.72 | 0.00 |
February | 0.00 | 0.00 | 0.903951E+11 | 0.859457E+11 | 45005.54 | 07-FEB-16:10 | 40144.92 | 0.00 |
March | 0.00 | 0.00 | 0.152822E+12 | 0.148159E+12 | 77851.67 | 31-MAR-23:05 | 72942.04 | 0.00 |
April | 0.00 | 0.00 | 0.200092E+12 | 0.194046E+12 | 83767.97 | 30-APR-17:55 | 78199.29 | 0.00 |
May | 0.00 | 0.00 | 0.668883E+11 | 0.596651E+11 | 45067.22 | 31-MAY-23:03 | 40510.01 | 0.00 |
June | 0.00 | 0.00 | 0.117886E+12 | 0.105978E+12 | 65885.16 | 30-JUN-23:03 | 57791.89 | 0.00 |
July | 0.00 | 0.00 | 0.174884E+12 | 0.160002E+12 | 82550.59 | 31-JUL-24:00 | 75592.07 | 0.00 |
August | 0.00 | 0.00 | 0.217536E+12 | 0.201993E+12 | 84628.21 | 08-AUG-04:53 | 75908.33 | 0.00 |
September | 0.00 | 0.00 | 0.712518E+11 | 0.587087E+11 | 49428.86 | 30-SEP-23:05 | 39216.04 | 0.00 |
October | 0.00 | 0.00 | 0.117081E+12 | 0.106835E+12 | 60735.69 | 31-OCT-23:05 | 56749.43 | 0.00 |
November | 0.00 | 0.00 | 0.153708E+12 | 0.146417E+12 | 66030.29 | 01-NOV-16:00 | 59535.95 | 0.00 |
December | 0.00 | 0.00 | 0.198826E+12 | 0.193085E+12 | 81846.10 | 05-DEC-17:00 | 76077.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160717E+13 | 0.150340E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.458040E+11 | 0.425667E+11 | 23497.93 | 19431.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217536E+12 | 0.201993E+12 | 84628.21 | 78199.29 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.410211E+10 | 0.378732E+10 | 2394.78 | 29-JAN-17:35 | 2136.29 | 0.00 |
February | 0.00 | 0.00 | 0.878321E+10 | 0.833990E+10 | 4558.53 | 07-FEB-16:10 | 4071.47 | 0.00 |
March | 0.00 | 0.00 | 0.151749E+11 | 0.147089E+11 | 7739.84 | 31-MAR-23:05 | 7248.61 | 0.00 |
April | 0.00 | 0.00 | 0.200476E+11 | 0.194428E+11 | 8499.36 | 30-APR-17:55 | 7947.36 | 0.00 |
May | 0.00 | 0.00 | 0.684608E+10 | 0.611997E+10 | 4557.89 | 31-MAY-23:03 | 4102.89 | 0.00 |
June | 0.00 | 0.00 | 0.119489E+11 | 0.107556E+11 | 6611.26 | 30-JUN-23:03 | 5802.92 | 0.00 |
July | 0.00 | 0.00 | 0.177216E+11 | 0.162315E+11 | 8326.19 | 31-JUL-24:00 | 7629.12 | 0.00 |
August | 0.00 | 0.00 | 0.219540E+11 | 0.203997E+11 | 8532.85 | 20-AUG-21:04 | 7684.33 | 0.00 |
September | 0.00 | 0.00 | 0.727804E+10 | 0.601837E+10 | 4994.42 | 30-SEP-23:05 | 3984.03 | 0.00 |
October | 0.00 | 0.00 | 0.117811E+11 | 0.107555E+11 | 6069.44 | 31-OCT-23:05 | 5670.47 | 0.00 |
November | 0.00 | 0.00 | 0.153075E+11 | 0.145787E+11 | 6655.10 | 01-NOV-15:00 | 5984.39 | 0.00 |
December | 0.00 | 0.00 | 0.195883E+11 | 0.190147E+11 | 8210.34 | 05-DEC-17:00 | 7633.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160533E+12 | 0.150153E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.410211E+10 | 0.378732E+10 | 2394.78 | 2136.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219540E+11 | 0.203997E+11 | 8532.85 | 7947.36 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 245496.18 | 1291052.09 | 30-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 328873.60 | 1980703.77 | 07-FEB-13:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 453766.31 | 1988603.45 | 23-MAR-11:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 633080.41 | 1994904.24 | 21-APR-12:05 | 0.00 | 0.00 | 01-APR-00:05 |
May | 951825.51 | 2550899.55 | 30-MAY-05:05 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1239767.15 | 4003922.77 | 11-JUN-15:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1425791.00 | 4223921.68 | 24-JUL-05:01 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1540130.99 | 4187959.96 | 21-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1266485.82 | 3529910.64 | 05-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 930876.03 | 3296647.36 | 07-OCT-17:10 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 635207.01 | 2109158.76 | 28-NOV-13:05 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 354189.47 | 2023731.13 | 04-DEC-13:05 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 836737.02 | 0.00 | ||||
Minimum of Months | 245496.18 | 1291052.09 | 0.00 | 0.00 | ||
Maximum of Months | 1540130.99 | 4223921.68 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 243273.08 | 2837149.56 | 30-JAN-06:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 326829.61 | 3659029.26 | 09-FEB-06:03 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 451117.08 | 3637661.60 | 29-MAR-05:03 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 629975.09 | 3765752.97 | 20-APR-05:02 | 0.00 | 0.00 | 01-APR-00:05 |
May | 946011.59 | 4242165.74 | 30-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1232671.97 | 4597051.25 | 09-JUN-03:12 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1416187.30 | 4532389.01 | 30-JUL-16:22 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1531132.41 | 4558701.78 | 08-AUG-05:01 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1261151.23 | 4348857.75 | 05-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 925646.84 | 4162272.25 | 16-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 632045.46 | 3975015.61 | 02-NOV-04:12 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 351328.63 | 3625949.78 | 11-DEC-06:03 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 831868.89 | 0.00 | ||||
Minimum of Months | 243273.08 | 2837149.56 | 0.00 | 0.00 | ||
Maximum of Months | 1531132.41 | 4597051.25 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 353615.94 | 848466.32 | 23-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 614330.64 | 1338373.45 | 06-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 947306.87 | 1900136.16 | 27-MAR-11:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1366257.00 | 2362600.47 | 28-APR-12:00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1070439.03 | 1727203.81 | 31-MAY-19:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1392306.76 | 2029875.19 | 12-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1749846.94 | 2444520.72 | 21-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1975495.97 | 2635471.57 | 16-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1157011.77 | 1683883.04 | 26-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1171011.83 | 1691473.84 | 04-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 1110042.63 | 1640817.24 | 05-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1019359.65 | 1586772.96 | 10-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 1164025.11 | 0.00 | ||||
Minimum of Months | 353615.94 | 848466.32 | 0.00 | 0.00 | ||
Maximum of Months | 1975495.97 | 2635471.57 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 10346.39 | 36784.59 | 12-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 10124.80 | 36400.82 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 10018.71 | 34668.92 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:05 | 8455.30 | 31368.86 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 7809.91 | 28236.35 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 7301.11 | 25320.02 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 6511.34 | 23922.91 | 31-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 7451.37 | 25781.83 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 7703.10 | 28649.31 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 8617.11 | 32224.16 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9648.27 | 35051.82 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9909.48 | 36590.14 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 8650.20 | ||||
Minimum of Months | 0.00 | 0.00 | 6511.34 | 23922.91 | ||
Maximum of Months | 0.00 | 0.00 | 10346.39 | 36784.59 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 283667.62 | 2308801.76 | 30-JAN-14:00 | 645.49 | 80358.62 | 19-JAN-07:50 |
February | 406149.37 | 4126033.09 | 07-FEB-16:00 | 299.33 | 76422.65 | 15-FEB-05:40 |
March | 596531.06 | 4048324.49 | 28-MAR-12:05 | 692.01 | 80928.28 | 22-MAR-02:70 |
April | 1018404.98 | 4391182.03 | 28-APR-15:00 | 434.31 | 92867.26 | 26-APR-03:00 |
May | 2147993.33 | 7341287.37 | 31-MAY-16:00 | 10.65 | 21119.02 | 07-MAY-06:00 |
June | 3619896.51 | 7644713.94 | 11-JUN-15:03 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 4439653.10 | 8220986.58 | 19-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 4907316.49 | 8309590.25 | 10-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3955461.45 | 7965571.63 | 07-SEP-14:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 2323269.59 | 7035577.44 | 06-OCT-16:00 | 9.44 | 15075.47 | 21-OCT-03:10 |
November | 1125177.63 | 6587053.70 | 01-NOV-14:05 | 292.86 | 42284.55 | 26-NOV-04:40 |
December | 464712.90 | 4433288.73 | 05-DEC-13:05 | 483.94 | 61302.29 | 31-DEC-24:00 |
Annual Sum or Average | 2117802.37 | 239.13 | ||||
Minimum of Months | 283667.62 | 2308801.76 | 0.00 | 0.00 | ||
Maximum of Months | 4907316.49 | 8309590.25 | 692.01 | 92867.26 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.543652E+10 | 0.37 | 21220.02 | 30-JAN-06:02 | 1.76 |
February | 0.669603E+10 | 0.43 | 21220.02 | 06-FEB-05:11 | 1.76 |
March | 0.105071E+11 | 0.57 | 21220.02 | 02-MAR-06:02 | 1.76 |
April | 0.142374E+11 | 0.72 | 21220.02 | 08-APR-05:03 | 1.76 |
May | 0.204189E+11 | 0.86 | 21220.02 | 01-MAY-04:22 | 1.76 |
June | 0.233881E+11 | 0.96 | 21220.02 | 01-JUN-03:12 | 1.76 |
July | 0.253430E+11 | 0.97 | 21220.02 | 01-JUL-03:12 | 1.76 |
August | 0.295877E+11 | 1.08 | 21220.02 | 01-AUG-03:02 | 1.76 |
September | 0.220539E+11 | 0.92 | 21220.02 | 01-SEP-03:12 | 1.76 |
October | 0.203437E+11 | 0.86 | 21220.02 | 01-OCT-11:42 | 1.76 |
November | 0.133400E+11 | 0.68 | 21220.02 | 01-NOV-05:03 | 1.75 |
December | 0.875510E+10 | 0.51 | 21220.02 | 04-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.200107E+12 | 0.74 | |||
Minimum of Months | 0.543652E+10 | 0.37 | 21220.02 | 1.75 | |
Maximum of Months | 0.295877E+11 | 1.08 | 21220.02 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.361214E+11 | 0.31 | 153701.79 | 30-JAN-06:02 | 1.49 |
February | 0.400251E+11 | 0.34 | 199160.15 | 09-FEB-06:03 | 1.76 |
March | 0.595238E+11 | 0.40 | 199160.15 | 27-MAR-04:12 | 1.76 |
April | 0.706660E+11 | 0.46 | 199160.15 | 04-APR-05:02 | 1.76 |
May | 0.105159E+12 | 0.61 | 199160.15 | 01-MAY-04:12 | 1.76 |
June | 0.114563E+12 | 0.66 | 199160.15 | 03-JUN-05:02 | 1.76 |
July | 0.123803E+12 | 0.68 | 199160.15 | 03-JUL-05:01 | 1.76 |
August | 0.141647E+12 | 0.73 | 199160.15 | 01-AUG-05:01 | 1.76 |
September | 0.108179E+12 | 0.63 | 199160.15 | 05-SEP-04:52 | 1.75 |
October | 0.925876E+11 | 0.54 | 199160.15 | 03-OCT-05:02 | 1.76 |
November | 0.695728E+11 | 0.44 | 199160.15 | 01-NOV-04:12 | 1.76 |
December | 0.436394E+11 | 0.34 | 199160.15 | 11-DEC-06:03 | 1.76 |
Annual Sum or Average | 0.100549E+13 | 0.51 | |||
Minimum of Months | 0.361214E+11 | 0.31 | 153701.79 | 1.49 | |
Maximum of Months | 0.141647E+12 | 0.73 | 199160.15 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.315596E+10 | 0.30 | 12648.02 | 30-JAN-06:02 | 1.21 |
February | 0.359865E+10 | 0.33 | 15428.81 | 06-FEB-05:11 | 1.37 |
March | 0.552825E+10 | 0.38 | 22618.81 | 27-MAR-04:12 | 1.75 |
April | 0.689239E+10 | 0.44 | 22618.81 | 03-APR-05:02 | 1.75 |
May | 0.109247E+11 | 0.60 | 22618.81 | 02-MAY-04:11 | 1.75 |
June | 0.120732E+11 | 0.66 | 22618.81 | 06-JUN-05:02 | 1.75 |
July | 0.133050E+11 | 0.67 | 22618.81 | 07-JUL-05:03 | 1.74 |
August | 0.149588E+11 | 0.72 | 22618.81 | 01-AUG-04:42 | 1.74 |
September | 0.111301E+11 | 0.62 | 22618.81 | 05-SEP-04:12 | 1.74 |
October | 0.903387E+10 | 0.52 | 22618.81 | 02-OCT-05:02 | 1.75 |
November | 0.622608E+10 | 0.40 | 22618.81 | 20-NOV-06:02 | 1.75 |
December | 0.379757E+10 | 0.32 | 13210.54 | 11-DEC-06:03 | 1.25 |
Annual Sum or Average | 0.100625E+12 | 0.50 | |||
Minimum of Months | 0.315596E+10 | 0.30 | 12648.02 | 1.21 | |
Maximum of Months | 0.149588E+11 | 0.72 | 22618.81 | 1.75 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148717E+11 | 0.91 | 11456.49 | 01-JAN-00:30 | 1.77 |
February | 0.119701E+11 | 0.79 | 11456.49 | 01-FEB-05:12 | 1.77 |
March | 0.101075E+11 | 0.61 | 11456.49 | 02-MAR-14:50 | 1.73 |
April | 0.544466E+10 | 0.33 | 11456.49 | 01-APR-04:12 | 1.77 |
May | 0.665013E+09 | 0.04 | 11456.49 | 01-MAY-04:22 | 1.77 |
June | 0.549068E+09 | 0.03 | 11456.49 | 22-JUN-07:50 | 1.72 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.124100E+10 | 0.07 | 11456.49 | 20-OCT-03:45 | 1.76 |
November | 0.741865E+10 | 0.45 | 11456.49 | 04-NOV-04:33 | 1.76 |
December | 0.127818E+11 | 0.77 | 11456.49 | 01-DEC-05:12 | 1.77 |
Annual Sum or Average | 0.650495E+11 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148717E+11 | 0.91 | 11456.49 | 1.77 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108567E+12 | 1.35 | 40534.41 | 01-JAN-00:05 | 1.35 |
February | 0.980608E+11 | 1.35 | 40534.41 | 01-FEB-00:10 | 1.35 |
March | 0.108567E+12 | 1.35 | 40534.41 | 01-MAR-00:10 | 1.35 |
April | 0.105065E+12 | 1.35 | 40534.41 | 01-APR-00:05 | 1.35 |
May | 0.108567E+12 | 1.34 | 40534.41 | 01-MAY-00:05 | 1.34 |
June | 0.105065E+12 | 1.34 | 40534.41 | 01-JUN-00:03 | 1.34 |
July | 0.108567E+12 | 1.34 | 40534.41 | 01-JUL-00:05 | 1.34 |
August | 0.108567E+12 | 1.34 | 40534.41 | 01-AUG-00:03 | 1.34 |
September | 0.105065E+12 | 1.34 | 40534.41 | 01-SEP-00:05 | 1.34 |
October | 0.108567E+12 | 1.34 | 40534.41 | 01-OCT-00:05 | 1.34 |
November | 0.105065E+12 | 1.35 | 40534.41 | 01-NOV-00:05 | 1.35 |
December | 0.108567E+12 | 1.35 | 40534.41 | 01-DEC-00:05 | 1.35 |
Annual Sum or Average | 0.127829E+13 | 1.35 | |||
Minimum of Months | 0.980608E+11 | 1.34 | 40534.41 | 1.34 | |
Maximum of Months | 0.108567E+12 | 1.35 | 40534.41 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140284E+10 | 0.91 | 523.76 | 01-JAN-00:05 | 0.92 |
February | 0.126708E+10 | 0.91 | 523.76 | 01-FEB-00:10 | 0.91 |
March | 0.140284E+10 | 0.91 | 523.76 | 01-MAR-00:10 | 0.91 |
April | 0.135759E+10 | 0.91 | 523.76 | 01-APR-00:05 | 0.91 |
May | 0.140284E+10 | 0.91 | 523.76 | 01-MAY-00:05 | 0.91 |
June | 0.135759E+10 | 0.91 | 523.76 | 01-JUN-00:03 | 0.91 |
July | 0.140284E+10 | 0.91 | 523.76 | 01-JUL-00:05 | 0.91 |
August | 0.140284E+10 | 0.91 | 523.76 | 01-AUG-00:03 | 0.91 |
September | 0.135759E+10 | 0.91 | 523.76 | 01-SEP-00:05 | 0.91 |
October | 0.140284E+10 | 0.91 | 523.76 | 01-OCT-00:05 | 0.91 |
November | 0.135759E+10 | 0.91 | 523.76 | 01-NOV-00:05 | 0.91 |
December | 0.140284E+10 | 0.91 | 523.76 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.165173E+11 | 0.91 | |||
Minimum of Months | 0.126708E+10 | 0.91 | 523.76 | 0.91 | |
Maximum of Months | 0.140284E+10 | 0.91 | 523.76 | 0.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133820E+11 | 0.91 | 4996.27 | 01-JAN-00:05 | 0.91 |
February | 0.120870E+11 | 0.91 | 4996.27 | 01-FEB-00:10 | 0.91 |
March | 0.133820E+11 | 0.91 | 4996.27 | 01-MAR-00:10 | 0.91 |
April | 0.129503E+11 | 0.91 | 4996.27 | 01-APR-00:05 | 0.91 |
May | 0.133820E+11 | 0.91 | 4996.27 | 01-MAY-00:05 | 0.91 |
June | 0.129503E+11 | 0.91 | 4996.27 | 01-JUN-00:03 | 0.91 |
July | 0.133820E+11 | 0.91 | 4996.27 | 01-JUL-00:05 | 0.91 |
August | 0.133820E+11 | 0.91 | 4996.27 | 01-AUG-00:03 | 0.91 |
September | 0.129503E+11 | 0.91 | 4996.27 | 01-SEP-00:05 | 0.91 |
October | 0.133820E+11 | 0.91 | 4996.27 | 01-OCT-00:05 | 0.91 |
November | 0.129503E+11 | 0.91 | 4996.27 | 01-NOV-00:05 | 0.91 |
December | 0.133820E+11 | 0.91 | 4996.27 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.157562E+12 | 0.91 | |||
Minimum of Months | 0.120870E+11 | 0.91 | 4996.27 | 0.91 | |
Maximum of Months | 0.133820E+11 | 0.91 | 4996.27 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135029E+10 | 0.91 | 504.14 | 01-JAN-00:05 | 0.91 |
February | 0.121962E+10 | 0.91 | 504.14 | 01-FEB-00:10 | 0.91 |
March | 0.135029E+10 | 0.91 | 504.14 | 01-MAR-00:10 | 0.91 |
April | 0.130673E+10 | 0.91 | 504.14 | 01-APR-00:05 | 0.91 |
May | 0.135029E+10 | 0.91 | 504.14 | 01-MAY-00:05 | 0.91 |
June | 0.130673E+10 | 0.91 | 504.14 | 01-JUN-00:03 | 0.91 |
July | 0.135029E+10 | 0.91 | 504.14 | 01-JUL-00:05 | 0.91 |
August | 0.135029E+10 | 0.91 | 504.14 | 01-AUG-00:03 | 0.91 |
September | 0.130673E+10 | 0.91 | 504.14 | 01-SEP-00:05 | 0.91 |
October | 0.135029E+10 | 0.91 | 504.14 | 01-OCT-00:05 | 0.91 |
November | 0.130673E+10 | 0.91 | 504.14 | 01-NOV-00:05 | 0.91 |
December | 0.135029E+10 | 0.91 | 504.14 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.158986E+11 | 0.91 | |||
Minimum of Months | 0.121962E+10 | 0.91 | 504.14 | 0.91 | |
Maximum of Months | 0.135029E+10 | 0.91 | 504.14 | 0.91 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.238530E+09 | 0.216824E+09 | 6918.52 | 30-JAN-06:02 | 6288.93 | 6288.93 | 8.54 | 63.22 |
February | 0.333242E+09 | 0.302917E+09 | 11833.72 | 09-FEB-06:03 | 10756.85 | 10756.85 | 10.03 | 78.31 |
March | 0.673260E+09 | 0.611994E+09 | 13305.47 | 30-MAR-05:03 | 12094.67 | 12094.67 | 10.05 | 82.00 |
April | 0.966208E+09 | 0.878283E+09 | 13238.14 | 04-APR-05:02 | 12033.47 | 12033.47 | 9.82 | 81.84 |
May | 0.158469E+10 | 0.144049E+10 | 11840.72 | 30-MAY-05:03 | 10763.21 | 10763.21 | 11.97 | 78.31 |
June | 0.209539E+10 | 0.190471E+10 | 11834.14 | 12-JUN-03:02 | 10757.23 | 10757.23 | 10.14 | 78.31 |
July | 0.279501E+10 | 0.254066E+10 | 11836.54 | 06-JUL-04:03 | 10759.42 | 10759.42 | 10.81 | 78.31 |
August | 0.328568E+10 | 0.298668E+10 | 11840.38 | 04-AUG-05:03 | 10762.90 | 10762.90 | 11.87 | 78.31 |
September | 0.221080E+10 | 0.200961E+10 | 11834.01 | 23-SEP-05:02 | 10757.11 | 10757.11 | 10.11 | 78.31 |
October | 0.153812E+10 | 0.139815E+10 | 11834.74 | 31-OCT-05:03 | 10757.77 | 10757.77 | 10.31 | 78.31 |
November | 0.962764E+09 | 0.875152E+09 | 13135.29 | 06-NOV-05:12 | 11939.98 | 11939.98 | 9.42 | 81.59 |
December | 0.393684E+09 | 0.357858E+09 | 11833.66 | 11-DEC-06:03 | 10756.79 | 10756.79 | 10.01 | 78.31 |
Annual Sum or Average | 0.170774E+11 | 0.155233E+11 | ||||||
Minimum of Months | 0.238530E+09 | 0.216824E+09 | 6918.52 | 6288.93 | 6288.93 | 8.54 | 63.22 | |
Maximum of Months | 0.328568E+10 | 0.298668E+10 | 13305.47 | 12094.67 | 12094.67 | 11.97 | 82.00 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.747693E+10 | 0.679653E+10 | 4597.54 | 01-JAN-00:15 | 4179.16 | 4179.16 | 6.95 | 41.08 |
February | 0.700665E+10 | 0.636904E+10 | 4597.54 | 01-FEB-05:12 | 4179.16 | 4179.16 | 8.89 | 41.08 |
March | 0.936518E+10 | 0.851295E+10 | 4597.54 | 01-MAR-04:02 | 4179.16 | 4179.16 | 8.28 | 41.08 |
April | 0.107583E+11 | 0.977925E+10 | 4597.54 | 01-APR-00:35 | 4179.16 | 4179.16 | 6.95 | 41.08 |
May | 0.114368E+11 | 0.103961E+11 | 4597.54 | 01-MAY-00:05 | 4179.16 | 4179.16 | 10.98 | 41.08 |
June | 0.112103E+11 | 0.101902E+11 | 4597.54 | 01-JUN-00:03 | 4179.16 | 4179.16 | 9.00 | 41.08 |
July | 0.113970E+11 | 0.103598E+11 | 4597.54 | 01-JUL-00:05 | 4179.16 | 4179.16 | 7.76 | 41.08 |
August | 0.117562E+11 | 0.106864E+11 | 4597.54 | 01-AUG-00:03 | 4179.16 | 4179.16 | 12.63 | 41.08 |
September | 0.113795E+11 | 0.103440E+11 | 4597.54 | 01-SEP-00:05 | 4179.16 | 4179.16 | 8.96 | 41.08 |
October | 0.115383E+11 | 0.104883E+11 | 4597.54 | 01-OCT-00:05 | 4179.16 | 4179.16 | 12.92 | 41.08 |
November | 0.100521E+11 | 0.913732E+10 | 4597.54 | 01-NOV-00:15 | 4179.16 | 4179.16 | 7.00 | 41.08 |
December | 0.904588E+10 | 0.822271E+10 | 4597.54 | 01-DEC-00:05 | 4179.16 | 4179.16 | 6.86 | 41.08 |
Annual Sum or Average | 0.122423E+12 | 0.111283E+12 | ||||||
Minimum of Months | 0.700665E+10 | 0.636904E+10 | 4597.54 | 4179.16 | 4179.16 | 6.86 | 41.08 | |
Maximum of Months | 0.117562E+11 | 0.106864E+11 | 4597.54 | 4179.16 | 4179.16 | 12.92 | 41.08 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.84 | 0.00 |
February | 0.126892E+09 | 0.115345E+09 | 4597.54 | 06-FEB-14:30 | 4179.16 | 4179.16 | 15.04 | 20.54 |
March | 0.592393E+09 | 0.538485E+09 | 4597.54 | 01-MAR-13:05 | 4179.16 | 4179.16 | 11.10 | 41.08 |
April | 0.134009E+10 | 0.121814E+10 | 4597.54 | 03-APR-07:50 | 4179.16 | 4179.16 | 14.76 | 20.54 |
May | 0.385959E+10 | 0.350836E+10 | 4597.54 | 01-MAY-07:20 | 4179.16 | 4179.16 | 15.39 | 20.54 |
June | 0.600448E+10 | 0.545807E+10 | 4597.54 | 01-JUN-07:20 | 4179.16 | 4179.16 | 14.60 | 20.54 |
July | 0.714218E+10 | 0.649224E+10 | 4597.54 | 01-JUL-03:02 | 4179.16 | 4179.16 | 15.12 | 20.54 |
August | 0.779649E+10 | 0.708701E+10 | 4597.54 | 01-AUG-00:23 | 4179.16 | 4179.16 | 11.70 | 41.08 |
September | 0.597705E+10 | 0.543314E+10 | 4597.54 | 01-SEP-05:03 | 4179.16 | 4179.16 | 12.89 | 41.08 |
October | 0.381672E+10 | 0.346940E+10 | 4597.54 | 01-OCT-14:12 | 4179.16 | 4179.16 | 12.04 | 41.08 |
November | 0.200489E+10 | 0.182245E+10 | 4597.54 | 01-NOV-07:40 | 4179.16 | 4179.16 | 14.86 | 20.54 |
December | 0.255853E+09 | 0.232570E+09 | 4597.54 | 04-DEC-09:50 | 4179.16 | 4179.16 | 14.90 | 20.54 |
Annual Sum or Average | 0.389166E+11 | 0.353752E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 | 0.00 | |
Maximum of Months | 0.779649E+10 | 0.708701E+10 | 4597.54 | 4179.16 | 4179.16 | 15.39 | 41.08 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.104160E+11 | 0.946817E+10 | 3888.90 | 01-JAN-00:05 | 3535.01 | 3535.01 | 21.62 | 16.40 |
February | 0.940803E+10 | 0.855190E+10 | 3888.90 | 01-FEB-00:10 | 3535.01 | 3535.01 | 24.38 | 16.40 |
March | 0.104160E+11 | 0.946817E+10 | 3888.90 | 01-MAR-00:10 | 3535.01 | 3535.01 | 33.70 | 16.40 |
April | 0.100800E+11 | 0.916275E+10 | 3888.90 | 01-APR-00:05 | 3535.01 | 3535.01 | 36.99 | 16.40 |
May | 0.104160E+11 | 0.946817E+10 | 3888.90 | 01-MAY-00:05 | 3535.01 | 3535.01 | 32.71 | 16.40 |
June | 0.100800E+11 | 0.916275E+10 | 3888.90 | 01-JUN-00:03 | 3535.01 | 3535.01 | 41.62 | 16.40 |
July | 0.104160E+11 | 0.946817E+10 | 3888.90 | 01-JUL-00:05 | 3535.01 | 3535.01 | 44.38 | 16.40 |
August | 0.104160E+11 | 0.946817E+10 | 3888.90 | 01-AUG-00:03 | 3535.01 | 3535.01 | 49.71 | 16.40 |
September | 0.100800E+11 | 0.916275E+10 | 3888.90 | 01-SEP-00:05 | 3535.01 | 3535.01 | 38.02 | 16.40 |
October | 0.104160E+11 | 0.946817E+10 | 3888.90 | 01-OCT-00:05 | 3535.01 | 3535.01 | 38.04 | 16.40 |
November | 0.100800E+11 | 0.916275E+10 | 3888.90 | 01-NOV-00:05 | 3535.01 | 3535.01 | 39.25 | 16.40 |
December | 0.104160E+11 | 0.946817E+10 | 3888.90 | 01-DEC-00:05 | 3535.01 | 3535.01 | 34.81 | 16.40 |
Annual Sum or Average | 0.122640E+12 | 0.111480E+12 | ||||||
Minimum of Months | 0.940803E+10 | 0.855190E+10 | 3888.90 | 3535.01 | 3535.01 | 21.62 | 16.40 | |
Maximum of Months | 0.104160E+11 | 0.946817E+10 | 3888.90 | 3535.01 | 3535.01 | 49.71 | 16.40 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 57.81 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 57.92 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 58.02 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 58.23 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 58.55 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 58.51 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 58.60 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 58.70 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 58.47 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:05 | 16.86 | 16.86 | 58.23 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 58.07 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 57.95 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 57.81 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 58.70 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.288134E+11 | 0.261914E+11 | 17802.83 | 30-JAN-14:00 | 16182.77 | 16182.77 | 28.72 | 72.46 |
February | 0.272943E+11 | 0.248105E+11 | 35581.42 | 07-FEB-16:00 | 32343.51 | 32343.51 | 27.91 | 144.93 |
March | 0.377794E+11 | 0.343415E+11 | 35577.59 | 28-MAR-12:05 | 32340.03 | 32340.03 | 27.78 | 144.93 |
April | 0.453375E+11 | 0.412118E+11 | 35594.49 | 28-APR-15:00 | 32355.40 | 32355.40 | 28.35 | 144.93 |
May | 0.570533E+11 | 0.518614E+11 | 35627.26 | 08-MAY-14:00 | 32385.18 | 32385.18 | 29.98 | 144.93 |
June | 0.648080E+11 | 0.589104E+11 | 35627.26 | 01-JUN-19:50 | 32385.18 | 32385.18 | 29.58 | 144.93 |
July | 0.697805E+11 | 0.634305E+11 | 35627.26 | 01-JUL-03:04 | 32385.18 | 32385.18 | 29.88 | 144.93 |
August | 0.736725E+11 | 0.669683E+11 | 35627.26 | 01-AUG-00:23 | 32385.18 | 32385.18 | 32.13 | 144.93 |
September | 0.655447E+11 | 0.595802E+11 | 35627.26 | 01-SEP-07:40 | 32385.18 | 32385.18 | 29.60 | 144.93 |
October | 0.576514E+11 | 0.524051E+11 | 35627.26 | 01-OCT-14:12 | 32385.18 | 32385.18 | 32.19 | 144.93 |
November | 0.445652E+11 | 0.405097E+11 | 35627.26 | 01-NOV-10:00 | 32385.18 | 32385.18 | 29.70 | 144.93 |
December | 0.355263E+11 | 0.322934E+11 | 35596.57 | 05-DEC-13:05 | 32357.28 | 32357.28 | 28.42 | 144.93 |
Annual Sum or Average | 0.607826E+12 | 0.552514E+12 | ||||||
Minimum of Months | 0.272943E+11 | 0.248105E+11 | 17802.83 | 16182.77 | 16182.77 | 27.78 | 72.46 | |
Maximum of Months | 0.736725E+11 | 0.669683E+11 | 35627.26 | 32385.18 | 32385.18 | 32.19 | 144.93 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 245496.18 | 1291052.09 | 30-JAN-14:00 | 14.21 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 328873.60 | 1980703.77 | 07-FEB-13:05 | 12.46 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 453766.31 | 1988603.45 | 23-MAR-11:05 | 12.48 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 633080.41 | 1994904.24 | 21-APR-12:05 | 12.50 | 6.70 | 0.00 | 0.00 | 01-APR-00:05 |
May | 951825.51 | 2550899.55 | 30-MAY-05:05 | 14.12 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1239767.15 | 4003922.77 | 11-JUN-15:02 | 18.35 | 9.92 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1425791.00 | 4223921.68 | 24-JUL-05:01 | 19.00 | 10.56 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1540130.99 | 4187959.96 | 21-AUG-05:03 | 18.89 | 10.46 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1266485.82 | 3529910.64 | 05-SEP-05:03 | 16.97 | 8.54 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 930876.03 | 3296647.36 | 07-OCT-17:10 | 16.29 | 12.08 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 635207.01 | 2109158.76 | 28-NOV-13:05 | 12.83 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 354189.47 | 2023731.13 | 04-DEC-13:05 | 12.58 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 836737.02 | 0.00 | ||||||
Minimum of Months | 245496.18 | 1291052.09 | 12.46 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1540130.99 | 4223921.68 | 19.00 | 12.08 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 243273.08 | 2837149.56 | 30-JAN-06:02 | 17.43 | 10.44 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 326829.61 | 3659029.26 | 09-FEB-06:03 | 17.87 | 11.99 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 451117.08 | 3637661.60 | 29-MAR-05:03 | 17.81 | 11.96 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 629975.09 | 3765752.97 | 20-APR-05:02 | 18.20 | 12.15 | 0.00 | 0.00 | 01-APR-00:05 |
May | 946011.59 | 4242165.74 | 30-MAY-05:02 | 19.66 | 12.84 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1232671.97 | 4597051.25 | 09-JUN-03:12 | 20.74 | 13.35 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1416187.30 | 4532389.01 | 30-JUL-16:22 | 21.35 | 7.54 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1531132.41 | 4558701.78 | 08-AUG-05:01 | 20.62 | 7.49 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1261151.23 | 4348857.75 | 05-SEP-03:02 | 20.08 | 12.99 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 925646.84 | 4162272.25 | 16-OCT-05:02 | 19.41 | 12.72 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 632045.46 | 3975015.61 | 02-NOV-04:12 | 18.84 | 12.45 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 351328.63 | 3625949.78 | 11-DEC-06:03 | 17.77 | 11.95 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 831868.89 | 0.00 | ||||||
Minimum of Months | 243273.08 | 2837149.56 | 17.43 | 7.49 | 0.00 | 0.00 | ||
Maximum of Months | 1531132.41 | 4597051.25 | 21.35 | 13.35 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 353615.94 | 848466.32 | 23-JAN-14:00 | 33.06 | 29.32 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 614330.64 | 1338373.45 | 06-FEB-15:00 | 41.38 | 34.84 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 947306.87 | 1900136.16 | 27-MAR-11:05 | 50.76 | 41.32 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1366257.00 | 2362600.47 | 28-APR-12:00 | 58.38 | 46.41 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1070439.03 | 1727203.81 | 31-MAY-19:00 | 47.89 | 43.64 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1392306.76 | 2029875.19 | 12-JUN-12:00 | 52.91 | 45.65 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1749846.94 | 2444520.72 | 21-JUL-12:00 | 59.71 | 49.70 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1975495.97 | 2635471.57 | 16-AUG-12:00 | 62.81 | 50.55 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1157011.77 | 1683883.04 | 26-SEP-13:00 | 47.17 | 42.79 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1171011.83 | 1691473.84 | 04-OCT-12:00 | 47.30 | 40.47 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 1110042.63 | 1640817.24 | 05-NOV-12:00 | 46.45 | 37.30 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1019359.65 | 1586772.96 | 10-DEC-12:00 | 45.55 | 34.12 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 1164025.11 | 0.00 | ||||||
Minimum of Months | 353615.94 | 848466.32 | 33.06 | 29.32 | 0.00 | 0.00 | ||
Maximum of Months | 1975495.97 | 2635471.57 | 62.81 | 50.55 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.65 | 58.65 | 10346.39 | 36784.59 | 12-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.31 | 58.31 | 10124.80 | 36400.82 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.40 | 58.40 | 10018.71 | 34668.92 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:05 | 58.54 | 58.54 | 8455.30 | 31368.86 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.96 | 58.96 | 7809.91 | 28236.35 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 58.85 | 58.85 | 7301.11 | 25320.02 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 58.92 | 58.92 | 6511.34 | 23922.91 | 31-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 58.91 | 58.91 | 7451.37 | 25781.83 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 58.83 | 58.83 | 7703.10 | 28649.31 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 58.68 | 58.68 | 8617.11 | 32224.16 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 58.52 | 58.52 | 9648.27 | 35051.82 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 58.38 | 58.38 | 9909.48 | 36590.14 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 8650.20 | ||||||
Minimum of Months | 0.00 | 0.00 | 58.31 | 58.31 | 6511.34 | 23922.91 | ||
Maximum of Months | 0.00 | 0.00 | 58.96 | 58.96 | 10346.39 | 36784.59 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 283667.62 | 2308801.76 | 30-JAN-14:00 | 28.72 | 23.90 | 645.49 | 80358.62 | 19-JAN-07:50 |
February | 406149.37 | 4126033.09 | 07-FEB-16:00 | 27.91 | 24.95 | 299.33 | 76422.65 | 15-FEB-05:40 |
March | 596531.06 | 4048324.49 | 28-MAR-12:05 | 27.78 | 24.02 | 692.01 | 80928.28 | 22-MAR-02:70 |
April | 1018404.98 | 4391182.03 | 28-APR-15:00 | 28.35 | 25.12 | 434.31 | 92867.26 | 26-APR-03:00 |
May | 2147993.33 | 7341287.37 | 31-MAY-16:00 | 33.22 | 28.80 | 10.65 | 21119.02 | 07-MAY-06:00 |
June | 3619896.51 | 7644713.94 | 11-JUN-15:03 | 33.72 | 28.96 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 4439653.10 | 8220986.58 | 19-JUL-15:00 | 34.67 | 29.26 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 4907316.49 | 8309590.25 | 10-AUG-16:00 | 34.82 | 29.30 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3955461.45 | 7965571.63 | 07-SEP-14:05 | 34.25 | 29.13 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 2323269.59 | 7035577.44 | 06-OCT-16:00 | 32.71 | 28.63 | 9.44 | 15075.47 | 21-OCT-03:10 |
November | 1125177.63 | 6587053.70 | 01-NOV-14:05 | 31.97 | 28.12 | 292.86 | 42284.55 | 26-NOV-04:40 |
December | 464712.90 | 4433288.73 | 05-DEC-13:05 | 28.42 | 24.84 | 483.94 | 61302.29 | 31-DEC-24:00 |
Annual Sum or Average | 2117802.37 | 239.13 | ||||||
Minimum of Months | 283667.62 | 2308801.76 | 27.78 | 23.90 | 0.00 | 0.00 | ||
Maximum of Months | 4907316.49 | 8309590.25 | 34.82 | 29.30 | 692.01 | 92867.26 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.659805E+11 | 0.543652E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.830377E+11 | 0.669603E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.128488E+12 | 0.105071E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.176376E+12 | 0.142374E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.257036E+12 | 0.204189E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.319457E+12 | 0.233881E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.378905E+12 | 0.253430E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.420111E+12 | 0.295877E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.329700E+12 | 0.220539E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.274492E+12 | 0.203437E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.173588E+12 | 0.133400E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.109327E+12 | 0.875510E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.271650E+13 | 0.200107E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.659805E+11 | 0.543652E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.420111E+12 | 0.295877E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.471943E+12 | 0.361214E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.576262E+12 | 0.400251E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.880244E+12 | 0.595238E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.119882E+13 | 0.706660E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.196357E+13 | 0.105159E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.253204E+13 | 0.114563E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.303350E+13 | 0.123803E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.328584E+13 | 0.141647E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.260503E+13 | 0.108179E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.190632E+13 | 0.925876E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.119330E+13 | 0.695728E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.670524E+12 | 0.436394E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.203174E+14 | 0.100549E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.471943E+12 | 0.361214E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.328584E+13 | 0.141647E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.426780E+11 | 0.319171E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.558652E+11 | 0.359991E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.887835E+11 | 0.552825E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.124808E+12 | 0.689239E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.210207E+12 | 0.109247E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.268905E+12 | 0.120732E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.321842E+12 | 0.133050E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.346954E+12 | 0.149588E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.272762E+12 | 0.111301E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.195642E+12 | 0.903387E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.118315E+12 | 0.622608E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.631197E+11 | 0.379765E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.210988E+13 | 0.100662E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.426780E+11 | 0.319171E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.346954E+12 | 0.149588E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.647317E+11 | 0.148717E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.557204E+11 | 0.119701E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.591253E+11 | 0.101075E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.398288E+11 | 0.544466E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.673392E+10 | 0.665013E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.673713E+10 | 0.549068E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.131663E+11 | 0.124100E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.635228E+11 | 0.741865E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.697030E+11 | 0.127818E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.379269E+12 | 0.650495E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.697030E+11 | 0.148717E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.439131E+12 | 0.197245E+12 | 0.00 | 1.04 |
February | 0.00 | 0.00 | 0.678347E+12 | 0.235120E+12 | 0.00 | 1.09 |
March | 0.00 | 0.00 | 0.106958E+13 | 0.332155E+12 | 0.00 | 0.86 |
April | 0.00 | 0.00 | 0.136486E+13 | 0.407707E+12 | 0.00 | 0.12 |
May | 0.00 | 0.00 | 0.503383E+12 | 0.235349E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.824457E+12 | 0.315260E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.120590E+13 | 0.424954E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.153931E+13 | 0.510379E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.515508E+12 | 0.236558E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.827967E+12 | 0.306146E+12 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.106659E+13 | 0.337741E+12 | 0.00 | 0.14 |
December | 0.00 | 0.00 | 0.136757E+13 | 0.381613E+12 | 0.00 | 1.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.114026E+14 | 0.392023E+13 | 0.00 | 5.26 |
Minimum of Months | 0.00 | 0.00 | 0.439131E+12 | 0.197245E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.153931E+13 | 0.510379E+12 | 0.00 | 1.98 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.685049E+10 | 0.273182E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.123456E+11 | 0.366530E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.203897E+11 | 0.553623E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.268509E+11 | 0.715244E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.970920E+10 | 0.377667E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.167449E+11 | 0.548054E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.250093E+11 | 0.772526E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.304951E+11 | 0.902091E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.104140E+11 | 0.391112E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.164192E+11 | 0.520078E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.207353E+11 | 0.576035E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.262786E+11 | 0.643795E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.222242E+12 | 0.663994E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.685049E+10 | 0.273182E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.304951E+11 | 0.902091E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.569641E+11 | 0.245421E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.112315E+12 | 0.340067E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.191776E+12 | 0.523362E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.255193E+12 | 0.680518E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.885985E+11 | 0.350922E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.156449E+12 | 0.515128E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.234150E+12 | 0.726476E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.290191E+12 | 0.860371E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.944387E+11 | 0.361372E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.152380E+12 | 0.486806E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.195209E+12 | 0.544519E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.246107E+12 | 0.606637E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207377E+13 | 0.624160E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.569641E+11 | 0.245421E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.290191E+12 | 0.860371E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.511494E+10 | 0.236313E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.109254E+11 | 0.336182E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.190555E+11 | 0.523084E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.255776E+11 | 0.683677E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.906948E+10 | 0.357369E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.158591E+11 | 0.521690E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.237275E+11 | 0.735625E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.292867E+11 | 0.868300E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.964829E+10 | 0.367698E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.153372E+11 | 0.490638E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.194508E+11 | 0.545007E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.242664E+11 | 0.602841E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207319E+12 | 0.626843E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.511494E+10 | 0.236313E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.292867E+11 | 0.868300E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.543652E+10 | 0.659805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.669603E+10 | 0.830377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105071E+11 | 0.128488E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142374E+11 | 0.176376E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.204189E+11 | 0.257036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.233881E+11 | 0.319457E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.253430E+11 | 0.378905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.295877E+11 | 0.420111E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220539E+11 | 0.329700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203437E+11 | 0.274492E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133400E+11 | 0.173588E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.875510E+10 | 0.109327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200107E+12 | 0.271650E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.543652E+10 | 0.659805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.295877E+11 | 0.420111E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.361214E+11 | 0.471943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.400251E+11 | 0.576262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.595238E+11 | 0.880244E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.706660E+11 | 0.119882E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105159E+12 | 0.196357E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114563E+12 | 0.253204E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123803E+12 | 0.303350E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141647E+12 | 0.328584E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108179E+12 | 0.260503E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.925876E+11 | 0.190632E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.695728E+11 | 0.119330E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.436394E+11 | 0.670524E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100549E+13 | 0.203174E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.361214E+11 | 0.471943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141647E+12 | 0.328584E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.315596E+10 | 0.426780E+11 | 35751551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359865E+10 | 0.558652E+11 | 1257132.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.552825E+10 | 0.887835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.689239E+10 | 0.124808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109247E+11 | 0.210207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120732E+11 | 0.268905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133050E+11 | 0.321842E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149588E+11 | 0.346954E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111301E+11 | 0.272762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.903387E+10 | 0.195642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.622608E+10 | 0.118315E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379757E+10 | 0.631197E+11 | 76258.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100625E+12 | 0.210988E+13 | 37084942.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.315596E+10 | 0.426780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149588E+11 | 0.346954E+12 | 35751551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148717E+11 | 0.647317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119701E+11 | 0.557204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101075E+11 | 0.591253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.544466E+10 | 0.398288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.665013E+09 | 0.673392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.549068E+09 | 0.673713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124100E+10 | 0.131663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.741865E+10 | 0.635228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127818E+11 | 0.697030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.650495E+11 | 0.379269E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148717E+11 | 0.697030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108567E+12 | 0.353244E+12 | 0.00 | 0.00 | 0.00 | 0.277832E+10 | 0.00 | 0.00 |
February | 0.980608E+11 | 0.544231E+12 | 0.00 | 0.00 | 0.00 | 0.293024E+10 | 0.00 | 0.00 |
March | 0.108567E+12 | 0.848318E+12 | 0.00 | 0.00 | 0.00 | 0.231308E+10 | 0.00 | 0.00 |
April | 0.105065E+12 | 0.106253E+13 | 0.00 | 0.00 | 0.00 | 0.309095E+09 | 0.00 | 0.00 |
May | 0.108567E+12 | 0.376608E+12 | 0.00 | 0.00 | 0.00 | 7227765.61 | 0.00 | 0.00 |
June | 0.105065E+12 | 0.614262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108567E+12 | 0.889514E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108567E+12 | 0.113750E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105065E+12 | 0.384015E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108567E+12 | 0.630464E+12 | 0.00 | 0.00 | 0.00 | 75932280.35 | 0.00 | 0.00 |
November | 0.105065E+12 | 0.834289E+12 | 0.00 | 0.00 | 0.00 | 0.376601E+09 | 0.00 | 0.00 |
December | 0.108567E+12 | 0.109985E+13 | 0.00 | 0.00 | 0.00 | 0.529387E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127829E+13 | 0.877482E+13 | 0.00 | 0.00 | 0.00 | 0.140844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.980608E+11 | 0.353244E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108567E+12 | 0.113750E+13 | 0.00 | 0.00 | 0.00 | 0.529387E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140284E+10 | 0.552151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126708E+10 | 0.994741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140284E+10 | 0.162563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135759E+10 | 0.210560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140284E+10 | 0.733537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135759E+10 | 0.126220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140284E+10 | 0.186869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140284E+10 | 0.228770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135759E+10 | 0.786045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140284E+10 | 0.126213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135759E+10 | 0.163326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140284E+10 | 0.212434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165173E+11 | 0.172360E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126708E+10 | 0.552151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140284E+10 | 0.228770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133820E+11 | 0.458040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120870E+11 | 0.903951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133820E+11 | 0.152822E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129503E+11 | 0.200092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133820E+11 | 0.668883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129503E+11 | 0.117886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133820E+11 | 0.174884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133820E+11 | 0.217536E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129503E+11 | 0.712518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133820E+11 | 0.117081E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129503E+11 | 0.153708E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133820E+11 | 0.198826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157562E+12 | 0.160717E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120870E+11 | 0.458040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133820E+11 | 0.217536E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135029E+10 | 0.410211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121962E+10 | 0.878321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135029E+10 | 0.151749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130673E+10 | 0.200476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135029E+10 | 0.684608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130673E+10 | 0.119489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135029E+10 | 0.177216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135029E+10 | 0.219540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130673E+10 | 0.727804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135029E+10 | 0.117811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130673E+10 | 0.153075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135029E+10 | 0.195883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158986E+11 | 0.160533E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121962E+10 | 0.410211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135029E+10 | 0.219540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.543652E+10 | 0.00 | 0.659805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.669603E+10 | 0.00 | 0.830377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105071E+11 | 0.00 | 0.128488E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142374E+11 | 0.00 | 0.176376E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.204189E+11 | 0.00 | 0.257036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.233881E+11 | 0.00 | 0.319457E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.253430E+11 | 0.00 | 0.378905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.295877E+11 | 0.00 | 0.420111E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220539E+11 | 0.00 | 0.329700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203437E+11 | 0.00 | 0.274492E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133400E+11 | 0.00 | 0.173588E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.875510E+10 | 0.00 | 0.109327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200107E+12 | 0.00 | 0.271650E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.543652E+10 | 0.00 | 0.659805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.295877E+11 | 0.00 | 0.420111E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.361214E+11 | 0.00 | 0.471943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.400251E+11 | 0.00 | 0.576262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.595238E+11 | 0.00 | 0.880244E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.706660E+11 | 0.00 | 0.119882E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105159E+12 | 0.00 | 0.196357E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114563E+12 | 0.00 | 0.253204E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123803E+12 | 0.00 | 0.303350E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141647E+12 | 0.00 | 0.328584E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108179E+12 | 0.00 | 0.260503E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.925876E+11 | 0.00 | 0.190632E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.695728E+11 | 0.00 | 0.119330E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.436394E+11 | 0.00 | 0.670524E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100549E+13 | 0.00 | 0.203174E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.361214E+11 | 0.00 | 0.471943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141647E+12 | 0.00 | 0.328584E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.315596E+10 | 0.00 | 0.426780E+11 | 0.00 | 0.00 | 35751551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359865E+10 | 0.00 | 0.558652E+11 | 0.00 | 0.00 | 1257132.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.552825E+10 | 0.00 | 0.887835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.689239E+10 | 0.00 | 0.124808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109247E+11 | 0.00 | 0.210207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120732E+11 | 0.00 | 0.268905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133050E+11 | 0.00 | 0.321842E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149588E+11 | 0.00 | 0.346954E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111301E+11 | 0.00 | 0.272762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.903387E+10 | 0.00 | 0.195642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.622608E+10 | 0.00 | 0.118315E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379757E+10 | 0.00 | 0.631197E+11 | 0.00 | 0.00 | 76258.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100625E+12 | 0.00 | 0.210988E+13 | 0.00 | 0.00 | 37084942.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.315596E+10 | 0.00 | 0.426780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149588E+11 | 0.00 | 0.346954E+12 | 0.00 | 0.00 | 35751551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148717E+11 | 0.00 | 0.647317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119701E+11 | 0.00 | 0.557204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101075E+11 | 0.00 | 0.591253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.544466E+10 | 0.00 | 0.398288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.665013E+09 | 0.00 | 0.673392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.549068E+09 | 0.00 | 0.673713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124100E+10 | 0.00 | 0.131663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.741865E+10 | 0.00 | 0.635228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127818E+11 | 0.00 | 0.697030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.650495E+11 | 0.00 | 0.379269E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148717E+11 | 0.00 | 0.697030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108567E+12 | 0.00 | 0.439131E+12 | 0.00 | 0.858870E+11 | 0.00 | 0.00 | 0.00 | 0.279082E+10 | 0.00 | 0.00 | 0.00 |
February | 0.980608E+11 | 0.00 | 0.678347E+12 | 0.00 | 0.134116E+12 | 0.00 | 0.00 | 0.00 | 0.294343E+10 | 0.00 | 0.00 | 0.00 |
March | 0.108567E+12 | 0.00 | 0.106958E+13 | 0.00 | 0.221264E+12 | 0.00 | 0.00 | 0.00 | 0.232350E+10 | 0.00 | 0.00 | 0.00 |
April | 0.105065E+12 | 0.00 | 0.136486E+13 | 0.00 | 0.302331E+12 | 0.00 | 0.00 | 0.00 | 0.310486E+09 | 0.00 | 0.00 | 0.00 |
May | 0.108567E+12 | 0.00 | 0.503383E+12 | 0.00 | 0.126775E+12 | 0.00 | 0.00 | 0.00 | 7260300.71 | 0.00 | 0.00 | 0.00 |
June | 0.105065E+12 | 0.00 | 0.824457E+12 | 0.00 | 0.210194E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108567E+12 | 0.00 | 0.120590E+13 | 0.00 | 0.316387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108567E+12 | 0.00 | 0.153931E+13 | 0.00 | 0.401812E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105065E+12 | 0.00 | 0.515508E+12 | 0.00 | 0.131493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108567E+12 | 0.00 | 0.827967E+12 | 0.00 | 0.197503E+12 | 0.00 | 0.00 | 0.00 | 76274082.32 | 0.00 | 0.00 | 0.00 |
November | 0.105065E+12 | 0.00 | 0.106659E+13 | 0.00 | 0.232298E+12 | 0.00 | 0.00 | 0.00 | 0.378296E+09 | 0.00 | 0.00 | 0.00 |
December | 0.108567E+12 | 0.00 | 0.136757E+13 | 0.00 | 0.267728E+12 | 0.00 | 0.00 | 0.00 | 0.531770E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127829E+13 | 0.00 | 0.114026E+14 | 0.00 | 0.262779E+13 | 0.00 | 0.00 | 0.00 | 0.141478E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.980608E+11 | 0.00 | 0.439131E+12 | 0.00 | 0.858870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108567E+12 | 0.00 | 0.153931E+13 | 0.00 | 0.401812E+12 | 0.00 | 0.00 | 0.00 | 0.531770E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140284E+10 | 0.00 | 0.685049E+10 | 0.00 | 0.132898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126708E+10 | 0.00 | 0.123456E+11 | 0.00 | 0.239822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140284E+10 | 0.00 | 0.203897E+11 | 0.00 | 0.413339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135759E+10 | 0.00 | 0.268509E+11 | 0.00 | 0.579485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140284E+10 | 0.00 | 0.970920E+10 | 0.00 | 0.237383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135759E+10 | 0.00 | 0.167449E+11 | 0.00 | 0.412295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140284E+10 | 0.00 | 0.250093E+11 | 0.00 | 0.632242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140284E+10 | 0.00 | 0.304951E+11 | 0.00 | 0.761807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135759E+10 | 0.00 | 0.104140E+11 | 0.00 | 0.255353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140284E+10 | 0.00 | 0.164192E+11 | 0.00 | 0.379794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135759E+10 | 0.00 | 0.207353E+11 | 0.00 | 0.440277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140284E+10 | 0.00 | 0.262786E+11 | 0.00 | 0.503511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165173E+11 | 0.00 | 0.222242E+12 | 0.00 | 0.498821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126708E+10 | 0.00 | 0.685049E+10 | 0.00 | 0.132898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140284E+10 | 0.00 | 0.304951E+11 | 0.00 | 0.761807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.133820E+11 | 0.00 | 0.569641E+11 | 0.00 | 0.111601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120870E+11 | 0.00 | 0.112315E+12 | 0.00 | 0.219198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133820E+11 | 0.00 | 0.191776E+12 | 0.00 | 0.389542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129503E+11 | 0.00 | 0.255193E+12 | 0.00 | 0.551015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133820E+11 | 0.00 | 0.885985E+11 | 0.00 | 0.217102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129503E+11 | 0.00 | 0.156449E+12 | 0.00 | 0.385624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133820E+11 | 0.00 | 0.234150E+12 | 0.00 | 0.592656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133820E+11 | 0.00 | 0.290191E+12 | 0.00 | 0.726551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129503E+11 | 0.00 | 0.944387E+11 | 0.00 | 0.231869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133820E+11 | 0.00 | 0.152380E+12 | 0.00 | 0.352986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129503E+11 | 0.00 | 0.195209E+12 | 0.00 | 0.415016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133820E+11 | 0.00 | 0.246107E+12 | 0.00 | 0.472817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157562E+12 | 0.00 | 0.207377E+13 | 0.00 | 0.466598E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120870E+11 | 0.00 | 0.569641E+11 | 0.00 | 0.111601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133820E+11 | 0.00 | 0.290191E+12 | 0.00 | 0.726551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135029E+10 | 0.00 | 0.511494E+10 | 0.00 | 0.101284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121962E+10 | 0.00 | 0.109254E+11 | 0.00 | 0.214220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135029E+10 | 0.00 | 0.190555E+11 | 0.00 | 0.388055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130673E+10 | 0.00 | 0.255776E+11 | 0.00 | 0.553003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135029E+10 | 0.00 | 0.906948E+10 | 0.00 | 0.222340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130673E+10 | 0.00 | 0.158591E+11 | 0.00 | 0.391017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135029E+10 | 0.00 | 0.237275E+11 | 0.00 | 0.600596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135029E+10 | 0.00 | 0.292867E+11 | 0.00 | 0.733271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130673E+10 | 0.00 | 0.964829E+10 | 0.00 | 0.237025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135029E+10 | 0.00 | 0.153372E+11 | 0.00 | 0.355609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130673E+10 | 0.00 | 0.194508E+11 | 0.00 | 0.414333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135029E+10 | 0.00 | 0.242664E+11 | 0.00 | 0.467812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158986E+11 | 0.00 | 0.207319E+12 | 0.00 | 0.467856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121962E+10 | 0.00 | 0.511494E+10 | 0.00 | 0.101284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135029E+10 | 0.00 | 0.292867E+11 | 0.00 | 0.733271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.790097E+09 | 0.00 | 0.113044E+09 | 0.00 | 0.00 | 0.137115E+11 | 0.00 | 0.36 |
February | 0.00 | 0.112198E+10 | 0.00 | 0.106600E+09 | 0.00 | 0.00 | 0.881341E+10 | 0.00 | 0.30 |
March | 0.00 | 0.327397E+10 | 0.00 | 75755812.64 | 0.00 | 0.00 | 0.573939E+10 | 0.00 | 0.25 |
April | 0.00 | 0.484397E+10 | 0.00 | 43691229.53 | 0.00 | 0.00 | 0.161837E+10 | 0.00 | 0.13 |
May | 0.00 | 0.155183E+10 | 0.00 | 561833.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.172968E+10 | 0.00 | 9760789.54 | 0.00 | 0.00 | 0.114785E+09 | 0.00 | 0.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.171260E+10 | 0.00 | 31391790.03 | 0.00 | 0.00 | 0.631096E+09 | 0.00 | 0.03 |
November | 0.00 | 0.827099E+10 | 0.00 | 65825498.09 | 0.00 | 0.00 | 0.180204E+10 | 0.00 | 0.18 |
December | 0.00 | 0.294019E+10 | 0.00 | 0.113207E+09 | 0.00 | 0.00 | 0.750759E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.262353E+11 | 0.00 | 0.559838E+09 | 0.00 | 0.00 | 0.399381E+11 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.827099E+10 | 0.00 | 0.113207E+09 | 0.00 | 0.00 | 0.137115E+11 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115170E+10 | 0.305998E+09 | 0.00 | 83172193.90 | 0.175474E+09 | 0.00 | 0.138627E+11 | 0.00 | 0.36 |
February | 0.800944E+09 | 0.134197E+10 | 0.00 | 73077695.78 | 0.333103E+09 | 0.00 | 0.885942E+10 | 0.00 | 0.36 |
March | 0.184851E+10 | 0.347928E+10 | 0.00 | 71023929.48 | 0.827396E+09 | 0.00 | 0.684971E+10 | 0.00 | 0.42 |
April | 0.157328E+10 | 0.874444E+10 | 0.00 | 32501643.41 | 0.499569E+10 | 0.00 | 0.205088E+10 | 0.00 | 0.46 |
May | 0.208339E+09 | 0.223243E+11 | 0.00 | 15218832.97 | 0.117312E+11 | 0.00 | 0.362050E+09 | 0.00 | 0.45 |
June | 22974998.35 | 0.392101E+11 | 0.00 | 1501978.96 | 0.205824E+11 | 0.00 | 16193790.18 | 0.00 | 0.45 |
July | 74559619.69 | 0.581854E+11 | 0.00 | 2735783.58 | 0.229869E+11 | 0.00 | 41115593.84 | 0.00 | 0.44 |
August | 0.00 | 0.686697E+11 | 0.00 | 0.00 | 0.190572E+11 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.466712E+11 | 0.00 | 1352575.22 | 0.225285E+11 | 0.00 | 7124109.79 | 0.00 | 0.45 |
October | 0.238183E+09 | 0.304100E+11 | 0.00 | 13148866.01 | 0.117986E+11 | 0.00 | 0.339362E+09 | 0.00 | 0.45 |
November | 0.105600E+10 | 0.115823E+11 | 0.00 | 29378791.56 | 0.263225E+10 | 0.00 | 0.114757E+10 | 0.00 | 0.43 |
December | 0.166708E+10 | 0.228930E+10 | 0.00 | 83338111.07 | 0.104192E+10 | 0.00 | 0.826551E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.864156E+10 | 0.293214E+12 | 0.00 | 0.406450E+09 | 0.118691E+12 | 0.00 | 0.418016E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.305998E+09 | 0.00 | 0.00 | 0.175474E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.184851E+10 | 0.686697E+11 | 0.00 | 83338111.07 | 0.229869E+11 | 0.00 | 0.138627E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.862519E+10 | 0.223749E+10 | 0.00 | 0.543579E+09 | 0.262099E+10 | 0.00 | 0.123190E+12 | 0.00 | 0.35 |
February | 0.586813E+10 | 0.120267E+11 | 0.00 | 0.478363E+09 | 0.297648E+10 | 0.00 | 0.779925E+11 | 0.00 | 0.33 |
March | 0.778840E+10 | 0.323190E+11 | 0.00 | 0.476745E+09 | 0.327144E+10 | 0.00 | 0.630295E+11 | 0.00 | 0.35 |
April | 0.577944E+10 | 0.787500E+11 | 0.00 | 0.221134E+09 | 0.336314E+11 | 0.00 | 0.209314E+11 | 0.00 | 0.36 |
May | 0.213014E+10 | 0.186367E+12 | 0.00 | 55734895.13 | 0.119430E+12 | 0.00 | 0.295545E+10 | 0.00 | 0.40 |
June | 0.286715E+09 | 0.311632E+12 | 0.00 | 6711577.42 | 0.237112E+12 | 0.00 | 0.200972E+09 | 0.00 | 0.43 |
July | 0.902071E+09 | 0.408021E+12 | 0.00 | 3988630.06 | 0.343688E+12 | 0.00 | 82300657.77 | 0.00 | 0.42 |
August | 0.00 | 0.475420E+12 | 0.00 | 0.00 | 0.323011E+12 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.355276E+12 | 0.00 | 6265761.68 | 0.256609E+12 | 0.00 | 0.162212E+09 | 0.00 | 0.41 |
October | 0.167212E+10 | 0.216548E+12 | 0.00 | 58431710.93 | 0.130255E+12 | 0.00 | 0.302737E+10 | 0.00 | 0.37 |
November | 0.185592E+10 | 0.103169E+12 | 0.00 | 0.194391E+09 | 0.133401E+11 | 0.00 | 0.106406E+11 | 0.00 | 0.33 |
December | 0.607311E+10 | 0.213277E+11 | 0.00 | 0.499619E+09 | 0.594796E+10 | 0.00 | 0.729731E+11 | 0.00 | 0.34 |
Annual Sum or Average | 0.409812E+11 | 0.220309E+13 | 0.00 | 0.254496E+10 | 0.147189E+13 | 0.00 | 0.375185E+12 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.223749E+10 | 0.00 | 0.00 | 0.262099E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.862519E+10 | 0.475420E+12 | 0.00 | 0.543579E+09 | 0.343688E+12 | 0.00 | 0.123190E+12 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.427789E+10 | 0.184801E+09 | 0.00 | 35917253.28 | 0.212391E+09 | 0.00 | 0.751964E+10 | 0.00 | 0.32 |
February | 0.236036E+10 | 0.109245E+10 | 0.00 | 34694153.59 | 0.285600E+09 | 0.00 | 0.517464E+10 | 0.00 | 0.32 |
March | 0.105476E+10 | 0.292546E+10 | 0.00 | 39201829.54 | 0.254524E+09 | 0.00 | 0.531456E+10 | 0.00 | 0.33 |
April | 0.536395E+09 | 0.743160E+10 | 0.00 | 20372431.48 | 0.301237E+10 | 0.00 | 0.182403E+10 | 0.00 | 0.35 |
May | 0.195117E+09 | 0.182534E+11 | 0.00 | 5525959.57 | 0.111877E+11 | 0.00 | 0.263261E+09 | 0.00 | 0.41 |
June | 28139465.92 | 0.310239E+11 | 0.00 | 753182.65 | 0.229482E+11 | 0.00 | 18539906.59 | 0.00 | 0.43 |
July | 0.103016E+09 | 0.413852E+11 | 0.00 | 769306.16 | 0.323797E+11 | 0.00 | 11399821.16 | 0.00 | 0.43 |
August | 0.00 | 0.480440E+11 | 0.00 | 0.00 | 0.305072E+11 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 213193.37 | 0.356375E+11 | 0.00 | 516832.84 | 0.247527E+11 | 0.00 | 9280767.22 | 0.00 | 0.41 |
October | 0.181040E+09 | 0.212543E+11 | 0.00 | 5449076.11 | 0.127136E+11 | 0.00 | 0.275677E+09 | 0.00 | 0.37 |
November | 0.176873E+09 | 0.994527E+10 | 0.00 | 15099936.77 | 0.119058E+10 | 0.00 | 0.874788E+09 | 0.00 | 0.33 |
December | 0.205757E+10 | 0.182927E+10 | 0.00 | 34166557.34 | 0.708914E+09 | 0.00 | 0.486363E+10 | 0.00 | 0.32 |
Annual Sum or Average | 0.109714E+11 | 0.219007E+12 | 0.00 | 0.192467E+09 | 0.140154E+12 | 0.00 | 0.261494E+11 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.184801E+09 | 0.00 | 0.00 | 0.212391E+09 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.427789E+10 | 0.480440E+11 | 0.00 | 39201829.54 | 0.323797E+11 | 0.00 | 0.751964E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.586565E+09 | 43966915.73 | 0.00 | 6067689.80 | 21985011.90 | 0.00 | 0.872185E+09 | 0.00 | 0.30 |
February | 0.315027E+09 | 0.205167E+09 | 0.00 | 6607529.39 | 41155642.25 | 0.00 | 0.659650E+09 | 0.00 | 0.34 |
March | 0.299521E+09 | 0.618076E+09 | 0.00 | 7720923.34 | 97653153.49 | 0.00 | 0.665730E+09 | 0.00 | 0.45 |
April | 0.207563E+09 | 0.191874E+10 | 0.00 | 3999840.70 | 0.459642E+09 | 0.00 | 0.236575E+09 | 0.00 | 0.57 |
May | 18465300.76 | 0.617299E+10 | 0.00 | 2791819.07 | 0.553724E+09 | 0.00 | 68166730.81 | 0.00 | 0.68 |
June | 717965.38 | 0.116230E+11 | 0.00 | 297300.76 | 0.695505E+09 | 0.00 | 5595310.13 | 0.00 | 0.73 |
July | 1919371.67 | 0.170389E+11 | 0.00 | 605917.12 | 0.445882E+09 | 0.00 | 16663933.26 | 0.00 | 0.76 |
August | 0.00 | 0.179444E+11 | 0.00 | 0.00 | 0.541301E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 0.00 | 0.121743E+11 | 0.00 | 195630.81 | 0.859710E+09 | 0.00 | 1061648.56 | 0.00 | 0.66 |
October | 27838341.20 | 0.618697E+10 | 0.00 | 1890979.63 | 0.863269E+09 | 0.00 | 49055413.52 | 0.00 | 0.59 |
November | 0.150852E+09 | 0.190108E+10 | 0.00 | 2999745.94 | 0.310235E+09 | 0.00 | 0.104913E+09 | 0.00 | 0.48 |
December | 0.342783E+09 | 0.327336E+09 | 0.00 | 7365853.61 | 0.130238E+09 | 0.00 | 0.644330E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.195125E+10 | 0.761549E+11 | 0.00 | 40543230.16 | 0.502030E+10 | 0.00 | 0.332393E+10 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 43966915.73 | 0.00 | 0.00 | 21985011.90 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.586565E+09 | 0.179444E+11 | 0.00 | 7720923.34 | 0.863269E+09 | 0.00 | 0.872185E+09 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.306245E+09 | 34751114.28 | 0.00 | 5473309.13 | 12545030.96 | 0.00 | 0.816532E+09 | 0.00 | 0.36 |
February | 0.183911E+09 | 0.149308E+09 | 0.00 | 5370189.87 | 20459756.59 | 0.00 | 0.557440E+09 | 0.00 | 0.39 |
March | 0.194814E+09 | 0.456822E+09 | 0.00 | 5697818.34 | 59706206.96 | 0.00 | 0.477638E+09 | 0.00 | 0.50 |
April | 0.138169E+09 | 0.146853E+10 | 0.00 | 3063444.78 | 0.259844E+09 | 0.00 | 0.175343E+09 | 0.00 | 0.65 |
May | 8268609.00 | 0.483672E+10 | 0.00 | 2426286.77 | 0.261196E+09 | 0.00 | 61179823.39 | 0.00 | 0.82 |
June | 463912.86 | 0.854761E+10 | 0.00 | 207605.15 | 0.396398E+09 | 0.00 | 3827673.74 | 0.00 | 0.83 |
July | 1219203.50 | 0.121734E+11 | 0.00 | 383636.75 | 0.270124E+09 | 0.00 | 10916041.72 | 0.00 | 0.85 |
August | 0.00 | 0.128309E+11 | 0.00 | 0.00 | 0.364000E+09 | 0.00 | 0.00 | 0.00 | 0.83 |
September | 0.00 | 0.964450E+10 | 0.00 | 148888.34 | 0.310961E+09 | 0.00 | 841150.02 | 0.00 | 0.80 |
October | 12987077.90 | 0.497431E+10 | 0.00 | 1756542.23 | 0.375716E+09 | 0.00 | 55366506.17 | 0.00 | 0.69 |
November | 87341872.00 | 0.140119E+10 | 0.00 | 2383972.75 | 0.189269E+09 | 0.00 | 92702280.61 | 0.00 | 0.54 |
December | 0.240228E+09 | 0.214334E+09 | 0.00 | 4968518.43 | 84282421.08 | 0.00 | 0.434879E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.117365E+10 | 0.567323E+11 | 0.00 | 31880212.55 | 0.260450E+10 | 0.00 | 0.268667E+10 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 34751114.28 | 0.00 | 0.00 | 12545030.96 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.306245E+09 | 0.128309E+11 | 0.00 | 5697818.34 | 0.396398E+09 | 0.00 | 0.816532E+09 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.399819E+09 | 0.101750E+09 | 0.00 | 13823426.86 | 8177828.26 | 0.00 | 0.186333E+10 | 0.00 | 0.51 |
February | 0.273384E+09 | 0.351725E+09 | 0.00 | 11998559.49 | 17767859.06 | 0.00 | 0.113081E+10 | 0.00 | 0.52 |
March | 0.285396E+09 | 0.850932E+09 | 0.00 | 10701827.69 | 79852709.11 | 0.00 | 0.873661E+09 | 0.00 | 0.57 |
April | 0.207275E+09 | 0.225735E+10 | 0.00 | 4287394.48 | 0.397162E+09 | 0.00 | 0.244796E+09 | 0.00 | 0.62 |
May | 20010315.06 | 0.592329E+10 | 0.00 | 2509001.57 | 0.640102E+09 | 0.00 | 61679916.01 | 0.00 | 0.66 |
June | 1351967.24 | 0.104565E+11 | 0.00 | 251183.59 | 0.103467E+10 | 0.00 | 4488350.34 | 0.00 | 0.68 |
July | 1850748.84 | 0.161451E+11 | 0.00 | 539825.72 | 0.546158E+09 | 0.00 | 15185823.19 | 0.00 | 0.72 |
August | 0.00 | 0.182180E+11 | 0.00 | 0.00 | 0.569913E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 0.00 | 0.144258E+11 | 0.00 | 200286.69 | 0.509380E+09 | 0.00 | 1081254.69 | 0.00 | 0.76 |
October | 16923858.69 | 0.867498E+10 | 0.00 | 3058803.28 | 0.313064E+09 | 0.00 | 84780919.54 | 0.00 | 0.75 |
November | 0.125528E+09 | 0.306251E+10 | 0.00 | 5858676.63 | 0.183984E+09 | 0.00 | 0.189611E+09 | 0.00 | 0.70 |
December | 0.274331E+09 | 0.667091E+09 | 0.00 | 14071577.97 | 78230744.44 | 0.00 | 0.113334E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.160587E+10 | 0.811351E+11 | 0.00 | 67300563.97 | 0.437847E+10 | 0.00 | 0.560276E+10 | 0.00 | 0.65 |
Minimum of Months | 0.00 | 0.101750E+09 | 0.00 | 0.00 | 8177828.26 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.399819E+09 | 0.182180E+11 | 0.00 | 14071577.97 | 0.103467E+10 | 0.00 | 0.186333E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128347E+09 | 60356991.90 | 0.00 | 8646799.18 | 8181250.67 | 0.00 | 0.134837E+10 | 0.00 | 0.50 |
February | 57520513.64 | 0.258452E+09 | 0.00 | 9656295.44 | 9128990.90 | 0.00 | 0.108889E+10 | 0.00 | 0.62 |
March | 77361418.02 | 0.788622E+09 | 0.00 | 12143331.74 | 16063265.39 | 0.00 | 0.112791E+10 | 0.00 | 0.82 |
April | 39239264.12 | 0.270063E+10 | 0.00 | 6631719.21 | 32221798.27 | 0.00 | 0.458821E+09 | 0.00 | 1.00 |
May | 8241765.40 | 0.537914E+10 | 0.00 | 2237512.38 | 0.154586E+09 | 0.00 | 56045830.60 | 0.00 | 0.85 |
June | 444326.82 | 0.104246E+11 | 0.00 | 251690.10 | 0.206309E+09 | 0.00 | 4921216.42 | 0.00 | 0.96 |
July | 315692.66 | 0.152905E+11 | 0.00 | 551025.82 | 0.117256E+09 | 0.00 | 17483482.71 | 0.00 | 1.04 |
August | 0.00 | 0.173132E+11 | 0.00 | 0.00 | 0.126334E+09 | 0.00 | 0.00 | 0.00 | 1.09 |
September | 0.00 | 0.101680E+11 | 0.00 | 137954.19 | 0.256902E+09 | 0.00 | 750616.44 | 0.00 | 0.81 |
October | 10412388.16 | 0.591114E+10 | 0.00 | 1643094.51 | 0.140205E+09 | 0.00 | 50372953.45 | 0.00 | 0.78 |
November | 39347277.73 | 0.222869E+10 | 0.00 | 5232896.16 | 52287432.05 | 0.00 | 0.213016E+09 | 0.00 | 0.78 |
December | 83303231.89 | 0.564538E+09 | 0.00 | 13536481.33 | 18053226.28 | 0.00 | 0.128967E+10 | 0.00 | 0.78 |
Annual Sum or Average | 0.444533E+09 | 0.710880E+11 | 0.00 | 60668800.06 | 0.113753E+10 | 0.00 | 0.565625E+10 | 0.00 | 0.84 |
Minimum of Months | 0.00 | 60356991.90 | 0.00 | 0.00 | 8181250.67 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.128347E+09 | 0.173132E+11 | 0.00 | 13536481.33 | 0.256902E+09 | 0.00 | 0.134837E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.963408E+10 | 0.358419E+09 | 0.00 | 26376090.13 | 0.265189E+09 | 0.00 | 0.414875E+10 | 0.00 | 0.29 |
February | 0.525066E+10 | 0.185824E+10 | 0.00 | 33650943.29 | 0.462890E+09 | 0.00 | 0.396725E+10 | 0.00 | 0.32 |
March | 0.342658E+10 | 0.637158E+10 | 0.00 | 45829693.86 | 0.396710E+09 | 0.00 | 0.473479E+10 | 0.00 | 0.40 |
April | 0.115106E+10 | 0.194455E+11 | 0.00 | 26303036.39 | 0.361087E+10 | 0.00 | 0.218807E+10 | 0.00 | 0.52 |
May | 0.194463E+09 | 0.647194E+11 | 0.00 | 16496203.07 | 0.868074E+10 | 0.00 | 0.748991E+09 | 0.00 | 0.74 |
June | 26792357.17 | 0.122894E+12 | 0.00 | 2392711.07 | 0.154667E+11 | 0.00 | 65768589.85 | 0.00 | 0.85 |
July | 85765494.31 | 0.177425E+12 | 0.00 | 2594777.02 | 0.179837E+11 | 0.00 | 69994557.79 | 0.00 | 0.87 |
August | 0.00 | 0.188126E+12 | 0.00 | 0.00 | 0.194516E+11 | 0.00 | 0.00 | 0.00 | 0.87 |
September | 0.00 | 0.121061E+12 | 0.00 | 1278782.51 | 0.209365E+11 | 0.00 | 31306259.49 | 0.00 | 0.75 |
October | 0.197798E+09 | 0.547666E+11 | 0.00 | 8896045.47 | 0.129597E+11 | 0.00 | 0.464218E+09 | 0.00 | 0.58 |
November | 0.569504E+09 | 0.187139E+11 | 0.00 | 16467985.33 | 0.169754E+10 | 0.00 | 0.833981E+09 | 0.00 | 0.41 |
December | 0.514245E+10 | 0.291054E+10 | 0.00 | 31939735.68 | 0.762540E+09 | 0.00 | 0.342913E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.256792E+11 | 0.778651E+12 | 0.00 | 0.212226E+09 | 0.102675E+12 | 0.00 | 0.206823E+11 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.358419E+09 | 0.00 | 0.00 | 0.265189E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.963408E+10 | 0.188126E+12 | 0.00 | 45829693.86 | 0.209365E+11 | 0.00 | 0.473479E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.406672E+10 | 0.297523E+09 | 0.00 | 33961600.75 | 0.139648E+09 | 0.00 | 0.594736E+10 | 0.00 | 0.34 |
February | 0.230023E+10 | 0.152859E+10 | 0.00 | 37553285.40 | 0.159557E+09 | 0.00 | 0.496361E+10 | 0.00 | 0.39 |
March | 0.165523E+10 | 0.522069E+10 | 0.00 | 45098646.71 | 0.176777E+09 | 0.00 | 0.473553E+10 | 0.00 | 0.50 |
April | 0.561686E+09 | 0.175366E+11 | 0.00 | 29131014.69 | 0.138272E+10 | 0.00 | 0.234197E+10 | 0.00 | 0.67 |
May | 74219910.69 | 0.529484E+11 | 0.00 | 17586815.35 | 0.393304E+10 | 0.00 | 0.721457E+09 | 0.00 | 0.92 |
June | 16828778.17 | 0.960743E+11 | 0.00 | 1954192.01 | 0.768873E+10 | 0.00 | 51345679.64 | 0.00 | 1.00 |
July | 43507780.85 | 0.138233E+12 | 0.00 | 1946260.40 | 0.732412E+10 | 0.00 | 60637775.15 | 0.00 | 1.02 |
August | 0.00 | 0.150302E+12 | 0.00 | 0.00 | 0.805505E+10 | 0.00 | 0.00 | 0.00 | 1.04 |
September | 117594.55 | 0.101253E+12 | 0.00 | 1064713.80 | 0.975313E+10 | 0.00 | 26142965.15 | 0.00 | 0.92 |
October | 53564061.70 | 0.487719E+11 | 0.00 | 11434440.55 | 0.539453E+10 | 0.00 | 0.608847E+09 | 0.00 | 0.72 |
November | 0.210568E+09 | 0.153127E+11 | 0.00 | 18085891.58 | 0.842540E+09 | 0.00 | 0.968656E+09 | 0.00 | 0.51 |
December | 0.224614E+10 | 0.229997E+10 | 0.00 | 32486456.13 | 0.446927E+09 | 0.00 | 0.396439E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.112288E+11 | 0.629778E+12 | 0.00 | 0.230303E+09 | 0.452968E+11 | 0.00 | 0.243899E+11 | 0.00 | 0.70 |
Minimum of Months | 0.00 | 0.297523E+09 | 0.00 | 0.00 | 0.139648E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.406672E+10 | 0.150302E+12 | 0.00 | 45098646.71 | 0.975313E+10 | 0.00 | 0.594736E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.450280E+10 | 0.117492E+10 | 0.00 | 0.119150E+09 | 60341148.75 | 0.00 | 0.192351E+11 | 0.00 | 0.57 |
February | 0.315736E+10 | 0.393425E+10 | 0.00 | 99159904.83 | 92827138.64 | 0.00 | 0.118885E+11 | 0.00 | 0.57 |
March | 0.243178E+10 | 0.974206E+10 | 0.00 | 84225698.18 | 0.198357E+09 | 0.00 | 0.866351E+10 | 0.00 | 0.59 |
April | 0.964965E+09 | 0.248251E+11 | 0.00 | 32957665.43 | 0.267931E+10 | 0.00 | 0.269102E+10 | 0.00 | 0.60 |
May | 0.195242E+09 | 0.644579E+11 | 0.00 | 16355577.39 | 0.888807E+10 | 0.00 | 0.729402E+09 | 0.00 | 0.75 |
June | 29378733.58 | 0.113966E+12 | 0.00 | 2228684.78 | 0.175076E+11 | 0.00 | 58791138.20 | 0.00 | 0.81 |
July | 86765203.42 | 0.173447E+12 | 0.00 | 2439818.64 | 0.190083E+11 | 0.00 | 67478509.12 | 0.00 | 0.86 |
August | 0.00 | 0.204667E+12 | 0.00 | 0.00 | 0.168645E+11 | 0.00 | 0.00 | 0.00 | 0.92 |
September | 0.00 | 0.160554E+12 | 0.00 | 1486503.54 | 0.144575E+11 | 0.00 | 36084102.47 | 0.00 | 0.92 |
October | 70102866.37 | 0.928564E+11 | 0.00 | 22795263.11 | 0.623557E+10 | 0.00 | 0.951276E+09 | 0.00 | 0.86 |
November | 0.272840E+09 | 0.355118E+11 | 0.00 | 45982490.44 | 0.535798E+09 | 0.00 | 0.197486E+10 | 0.00 | 0.74 |
December | 0.256500E+10 | 0.776735E+10 | 0.00 | 0.108569E+09 | 0.250946E+09 | 0.00 | 0.119742E+11 | 0.00 | 0.61 |
Annual Sum or Average | 0.142762E+11 | 0.892904E+12 | 0.00 | 0.535350E+09 | 0.867791E+11 | 0.00 | 0.582703E+11 | 0.00 | 0.73 |
Minimum of Months | 0.00 | 0.117492E+10 | 0.00 | 0.00 | 60341148.75 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.450280E+10 | 0.204667E+12 | 0.00 | 0.119150E+09 | 0.190083E+11 | 0.00 | 0.192351E+11 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.413889E+10 | 0.435525E+09 | 0.00 | 39338641.91 | 0.123424E+09 | 0.00 | 0.663438E+10 | 0.00 | 0.38 |
February | 0.231317E+10 | 0.203310E+10 | 0.00 | 44032461.16 | 0.152625E+09 | 0.00 | 0.546720E+10 | 0.00 | 0.45 |
March | 0.129997E+10 | 0.667220E+10 | 0.00 | 53706769.31 | 67143455.64 | 0.00 | 0.597571E+10 | 0.00 | 0.60 |
April | 0.364627E+09 | 0.216174E+11 | 0.00 | 28067947.37 | 0.832947E+09 | 0.00 | 0.241186E+10 | 0.00 | 0.75 |
May | 88262364.88 | 0.615600E+11 | 0.00 | 15528070.38 | 0.251616E+10 | 0.00 | 0.652651E+09 | 0.00 | 0.98 |
June | 7549443.40 | 0.112424E+12 | 0.00 | 1967886.29 | 0.413159E+10 | 0.00 | 64518163.82 | 0.00 | 1.10 |
July | 17228406.92 | 0.159037E+12 | 0.00 | 3066842.74 | 0.327925E+10 | 0.00 | 0.101485E+09 | 0.00 | 1.12 |
August | 0.00 | 0.176376E+12 | 0.00 | 0.00 | 0.436004E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
September | 118131.83 | 0.118927E+12 | 0.00 | 1012467.06 | 0.591486E+10 | 0.00 | 25681136.35 | 0.00 | 1.00 |
October | 0.101951E+09 | 0.558524E+11 | 0.00 | 8816387.80 | 0.417744E+10 | 0.00 | 0.433165E+09 | 0.00 | 0.79 |
November | 0.231448E+09 | 0.183911E+11 | 0.00 | 20510435.54 | 0.558987E+09 | 0.00 | 0.962911E+09 | 0.00 | 0.58 |
December | 0.204019E+10 | 0.335013E+10 | 0.00 | 41304793.51 | 0.392201E+09 | 0.00 | 0.490910E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.106034E+11 | 0.736676E+12 | 0.00 | 0.257353E+09 | 0.265067E+11 | 0.00 | 0.276387E+11 | 0.00 | 0.78 |
Minimum of Months | 0.00 | 0.435525E+09 | 0.00 | 0.00 | 67143455.64 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.413889E+10 | 0.176376E+12 | 0.00 | 53706769.31 | 0.591486E+10 | 0.00 | 0.663438E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.971918E+09 | 23587921.53 | 0.00 | 2134045.03 | 26706533.96 | 632488.80 | 0.366707E+09 | 0.00 | 0.29 |
February | 0.514917E+09 | 0.162412E+09 | 0.00 | 3056702.20 | 45979820.68 | 0.00 | 0.372203E+09 | 0.00 | 0.31 |
March | 0.336369E+09 | 0.553405E+09 | 0.00 | 4374281.44 | 31586330.37 | 0.00 | 0.447497E+09 | 0.00 | 0.39 |
April | 0.134765E+09 | 0.177446E+10 | 0.00 | 2709263.05 | 0.290498E+09 | 0.00 | 0.182549E+09 | 0.00 | 0.50 |
May | 18685188.33 | 0.606659E+10 | 0.00 | 1605325.39 | 0.756477E+09 | 0.00 | 64240122.72 | 0.00 | 0.73 |
June | 2639716.82 | 0.116447E+11 | 0.00 | 261824.39 | 0.135053E+10 | 0.00 | 6145425.23 | 0.00 | 0.82 |
July | 8010473.69 | 0.169505E+11 | 0.00 | 315210.62 | 0.148522E+10 | 0.00 | 9403423.53 | 0.00 | 0.85 |
August | 0.00 | 0.180244E+11 | 0.00 | 0.00 | 0.159670E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
September | 14394.94 | 0.117357E+11 | 0.00 | 105819.02 | 0.184744E+10 | 0.00 | 1858607.08 | 0.00 | 0.73 |
October | 21623411.15 | 0.527252E+10 | 0.00 | 897028.48 | 0.118822E+10 | 0.00 | 43959612.40 | 0.00 | 0.56 |
November | 65474724.90 | 0.176882E+10 | 0.00 | 1588115.95 | 0.149092E+09 | 0.00 | 68505589.42 | 0.00 | 0.40 |
December | 0.481161E+09 | 0.252078E+09 | 0.00 | 2726366.44 | 82784826.92 | 0.00 | 0.317786E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.255558E+10 | 0.742292E+11 | 0.00 | 19773981.99 | 0.885124E+10 | 632488.80 | 0.188086E+10 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 23587921.53 | 0.00 | 0.00 | 26706533.96 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.971918E+09 | 0.180244E+11 | 0.00 | 4374281.44 | 0.184744E+10 | 632488.80 | 0.447497E+09 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.441182E+09 | 28225959.41 | 0.00 | 3168081.51 | 10821238.92 | 241023.88 | 0.574965E+09 | 0.00 | 0.35 |
February | 0.227005E+09 | 0.142104E+09 | 0.00 | 3793403.95 | 16910585.75 | 0.00 | 0.509164E+09 | 0.00 | 0.41 |
March | 0.163647E+09 | 0.480285E+09 | 0.00 | 4635096.48 | 12771258.12 | 0.00 | 0.479264E+09 | 0.00 | 0.51 |
April | 66836342.99 | 0.161870E+10 | 0.00 | 3097050.30 | 0.119478E+09 | 0.00 | 0.220233E+09 | 0.00 | 0.68 |
May | 7233425.87 | 0.502625E+10 | 0.00 | 1727218.69 | 0.349302E+09 | 0.00 | 64017839.88 | 0.00 | 0.92 |
June | 1701407.63 | 0.922321E+10 | 0.00 | 213763.46 | 0.701227E+09 | 0.00 | 4995869.23 | 0.00 | 0.98 |
July | 4829169.69 | 0.133965E+11 | 0.00 | 237099.52 | 0.531489E+09 | 0.00 | 7135014.60 | 0.00 | 1.01 |
August | 0.00 | 0.144754E+11 | 0.00 | 0.00 | 0.722705E+09 | 0.00 | 0.00 | 0.00 | 1.02 |
September | 15103.94 | 0.991371E+10 | 0.00 | 90643.09 | 0.861413E+09 | 0.00 | 1528157.54 | 0.00 | 0.92 |
October | 6028983.97 | 0.477900E+10 | 0.00 | 1227193.99 | 0.506005E+09 | 0.00 | 59835896.56 | 0.00 | 0.72 |
November | 24275192.03 | 0.152776E+10 | 0.00 | 1949904.51 | 76694100.08 | 0.00 | 87475536.45 | 0.00 | 0.53 |
December | 0.221557E+09 | 0.229619E+09 | 0.00 | 3055539.68 | 39430478.72 | 0.00 | 0.384461E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.116431E+10 | 0.608408E+11 | 0.00 | 23194995.18 | 0.394825E+10 | 241023.88 | 0.239308E+10 | 0.00 | 0.70 |
Minimum of Months | 0.00 | 28225959.41 | 0.00 | 0.00 | 10821238.92 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.441182E+09 | 0.144754E+11 | 0.00 | 4635096.48 | 0.861413E+09 | 241023.88 | 0.574965E+09 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.496628E+09 | 95336888.42 | 0.00 | 10515638.50 | 5829706.27 | 0.00 | 0.183957E+10 | 0.00 | 0.55 |
February | 0.299586E+09 | 0.345479E+09 | 0.00 | 9507616.45 | 9559952.11 | 0.00 | 0.119961E+10 | 0.00 | 0.56 |
March | 0.246180E+09 | 0.823541E+09 | 0.00 | 8301543.39 | 16343032.04 | 0.00 | 0.840274E+09 | 0.00 | 0.56 |
April | 0.122372E+09 | 0.220896E+10 | 0.00 | 3448219.20 | 0.222245E+09 | 0.00 | 0.227687E+09 | 0.00 | 0.58 |
May | 18705144.39 | 0.602946E+10 | 0.00 | 1593082.11 | 0.775559E+09 | 0.00 | 62762996.60 | 0.00 | 0.73 |
June | 2665546.89 | 0.108510E+11 | 0.00 | 243673.17 | 0.151950E+10 | 0.00 | 5746258.64 | 0.00 | 0.78 |
July | 8252328.82 | 0.165888E+11 | 0.00 | 295408.32 | 0.157359E+10 | 0.00 | 8943023.24 | 0.00 | 0.83 |
August | 0.00 | 0.194733E+11 | 0.00 | 0.00 | 0.137399E+10 | 0.00 | 0.00 | 0.00 | 0.89 |
September | 10862.92 | 0.152300E+11 | 0.00 | 125893.75 | 0.127262E+10 | 0.00 | 2158820.67 | 0.00 | 0.89 |
October | 6756355.98 | 0.865906E+10 | 0.00 | 2352159.04 | 0.576352E+09 | 0.00 | 96743602.80 | 0.00 | 0.83 |
November | 28319166.22 | 0.327742E+10 | 0.00 | 5346844.53 | 54856430.14 | 0.00 | 0.190453E+09 | 0.00 | 0.72 |
December | 0.249090E+09 | 0.698938E+09 | 0.00 | 9954492.39 | 23964202.71 | 0.00 | 0.114322E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.147857E+10 | 0.842813E+11 | 0.00 | 51684570.84 | 0.742441E+10 | 0.00 | 0.561717E+10 | 0.00 | 0.71 |
Minimum of Months | 0.00 | 95336888.42 | 0.00 | 0.00 | 5829706.27 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.496628E+09 | 0.194733E+11 | 0.00 | 10515638.50 | 0.157359E+10 | 0.00 | 0.183957E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.464613E+09 | 36861330.63 | 0.00 | 3382349.61 | 8918768.35 | 0.00 | 0.600670E+09 | 0.00 | 0.37 |
February | 0.233564E+09 | 0.180999E+09 | 0.00 | 4162215.67 | 14013358.05 | 0.00 | 0.530890E+09 | 0.00 | 0.44 |
March | 0.144836E+09 | 0.567214E+09 | 0.00 | 5234789.19 | 4980248.85 | 0.00 | 0.559703E+09 | 0.00 | 0.57 |
April | 45044196.80 | 0.188985E+10 | 0.00 | 2885387.70 | 77581910.43 | 0.00 | 0.214010E+09 | 0.00 | 0.71 |
May | 8031292.35 | 0.558856E+10 | 0.00 | 1502901.81 | 0.236488E+09 | 0.00 | 56624976.47 | 0.00 | 0.94 |
June | 711370.74 | 0.103749E+11 | 0.00 | 210507.17 | 0.383540E+09 | 0.00 | 6045201.79 | 0.00 | 1.04 |
July | 1584399.94 | 0.147088E+11 | 0.00 | 329703.07 | 0.315325E+09 | 0.00 | 12173724.26 | 0.00 | 1.07 |
August | 0.00 | 0.163769E+11 | 0.00 | 0.00 | 0.413689E+09 | 0.00 | 0.00 | 0.00 | 1.11 |
September | 9267.25 | 0.111875E+11 | 0.00 | 89417.36 | 0.519524E+09 | 0.00 | 1555447.45 | 0.00 | 0.96 |
October | 11276007.79 | 0.521720E+10 | 0.00 | 896184.90 | 0.393043E+09 | 0.00 | 41631955.37 | 0.00 | 0.76 |
November | 24167058.14 | 0.171730E+10 | 0.00 | 2104781.13 | 53659258.17 | 0.00 | 88024762.79 | 0.00 | 0.57 |
December | 0.215411E+09 | 0.304954E+09 | 0.00 | 3611255.21 | 35917331.02 | 0.00 | 0.442843E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.114925E+10 | 0.681511E+11 | 0.00 | 24409492.82 | 0.245668E+10 | 0.00 | 0.255417E+10 | 0.00 | 0.75 |
Minimum of Months | 0.00 | 36861330.63 | 0.00 | 0.00 | 4980248.85 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.464613E+09 | 0.163769E+11 | 0.00 | 5234789.19 | 0.519524E+09 | 0.00 | 0.600670E+09 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 50260301.54 | 0.00 | 6151337.13 | 0.00 | 0.00 | 0.210619E+09 | 0.00 | 0.58 |
February | 0.00 | 0.137528E+09 | 0.00 | 7826030.85 | 0.00 | 0.00 | 72323231.27 | 0.00 | 0.58 |
March | 0.00 | 0.210367E+09 | 0.00 | 12694452.20 | 0.00 | 0.00 | 53755948.85 | 0.00 | 0.59 |
April | 0.00 | 0.495397E+09 | 0.00 | 4875415.96 | 0.00 | 0.00 | 9440211.41 | 0.00 | 0.59 |
May | 0.00 | 0.844061E+09 | 0.00 | 104861.20 | 0.00 | 0.00 | 618633.93 | 0.00 | 0.59 |
June | 0.00 | 0.137917E+10 | 0.00 | 5202.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.181541E+10 | 0.00 | 5889.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.182739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.145093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.104172E+10 | 0.00 | 435906.28 | 0.00 | 0.00 | 689600.10 | 0.00 | 0.59 |
November | 0.00 | 0.543842E+09 | 0.00 | 1224451.41 | 0.00 | 0.00 | 1402950.06 | 0.00 | 0.58 |
December | 0.00 | 0.240177E+09 | 0.00 | 14877076.53 | 0.00 | 0.00 | 52773371.90 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.100363E+11 | 0.00 | 48200623.10 | 0.00 | 0.00 | 0.401623E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 50260301.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.182739E+10 | 0.00 | 14877076.53 | 0.00 | 0.00 | 0.210619E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.458440E+09 | 0.00 | 48341248.86 | 0.00 | 0.00 | 0.220317E+10 | 0.00 | 0.58 |
February | 0.00 | 0.134877E+10 | 0.00 | 70081255.44 | 0.00 | 0.00 | 0.747298E+09 | 0.00 | 0.58 |
March | 0.00 | 0.209306E+10 | 0.00 | 0.119026E+09 | 0.00 | 0.00 | 0.547231E+09 | 0.00 | 0.59 |
April | 0.00 | 0.495432E+10 | 0.00 | 46646549.11 | 0.00 | 0.00 | 96042946.32 | 0.00 | 0.59 |
May | 0.00 | 0.831835E+10 | 0.00 | 953998.86 | 0.00 | 0.00 | 6528471.85 | 0.00 | 0.59 |
June | 0.00 | 0.137109E+11 | 0.00 | 59886.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.180926E+11 | 0.00 | 58031.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.184655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.142873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.103411E+11 | 0.00 | 4064225.42 | 0.00 | 0.00 | 7334788.93 | 0.00 | 0.59 |
November | 0.00 | 0.541604E+10 | 0.00 | 11514505.87 | 0.00 | 0.00 | 15209114.46 | 0.00 | 0.58 |
December | 0.00 | 0.239279E+10 | 0.00 | 0.139109E+09 | 0.00 | 0.00 | 0.538661E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.998792E+11 | 0.00 | 0.439855E+09 | 0.00 | 0.00 | 0.416147E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.458440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.184655E+11 | 0.00 | 0.139109E+09 | 0.00 | 0.00 | 0.220317E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 44447430.92 | 0.00 | 3908758.09 | 0.00 | 0.00 | 0.228439E+09 | 0.00 | 0.58 |
February | 0.00 | 0.134344E+09 | 0.00 | 6596645.37 | 0.00 | 0.00 | 76173004.07 | 0.00 | 0.58 |
March | 0.00 | 0.209328E+09 | 0.00 | 11676595.30 | 0.00 | 0.00 | 55102265.47 | 0.00 | 0.59 |
April | 0.00 | 0.495350E+09 | 0.00 | 4638871.42 | 0.00 | 0.00 | 9627060.70 | 0.00 | 0.59 |
May | 0.00 | 0.834980E+09 | 0.00 | 94030.54 | 0.00 | 0.00 | 651553.10 | 0.00 | 0.59 |
June | 0.00 | 0.137310E+10 | 0.00 | 5846.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.181085E+10 | 0.00 | 5594.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.184541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.143357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.103485E+10 | 0.00 | 401255.09 | 0.00 | 0.00 | 742332.06 | 0.00 | 0.59 |
November | 0.00 | 0.541462E+09 | 0.00 | 1123951.54 | 0.00 | 0.00 | 1585793.59 | 0.00 | 0.58 |
December | 0.00 | 0.239006E+09 | 0.00 | 13567876.57 | 0.00 | 0.00 | 54364716.77 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.999669E+10 | 0.00 | 42019424.74 | 0.00 | 0.00 | 0.426686E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 44447430.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.184541E+10 | 0.00 | 13567876.57 | 0.00 | 0.00 | 0.228439E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.143715E+10 | 0.00 | 0.335903E+09 | 0.00 | 0.00 | 0.441400E+10 | 0.00 | 0.66 |
February | 0.00 | 0.312292E+10 | 0.00 | 0.390076E+09 | 0.00 | 0.00 | 0.153510E+10 | 0.00 | 0.66 |
March | 0.00 | 0.450768E+10 | 0.00 | 0.602614E+09 | 0.00 | 0.00 | 0.113674E+10 | 0.00 | 0.66 |
April | 0.00 | 0.106064E+11 | 0.00 | 0.210712E+09 | 0.00 | 0.00 | 0.169573E+09 | 0.00 | 0.66 |
May | 0.00 | 0.194357E+11 | 0.00 | 5548564.13 | 0.00 | 0.00 | 13804364.03 | 0.00 | 0.66 |
June | 0.00 | 0.306811E+11 | 0.00 | 134540.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.397659E+11 | 0.00 | 582353.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.418994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.335022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.231816E+11 | 0.00 | 21847239.52 | 0.00 | 0.00 | 12614319.29 | 0.00 | 0.66 |
November | 0.00 | 0.118177E+11 | 0.00 | 58338192.68 | 0.00 | 0.00 | 24713365.75 | 0.00 | 0.66 |
December | 0.00 | 0.505193E+10 | 0.00 | 0.705996E+09 | 0.00 | 0.00 | 0.105250E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.225010E+12 | 0.00 | 0.233175E+10 | 0.00 | 0.00 | 0.835904E+10 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.143715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.418994E+11 | 0.00 | 0.705996E+09 | 0.00 | 0.00 | 0.441400E+10 | 0.00 | 0.67 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.254842E+12 | 0.236102E+10 | 0.00 | 0.460217E+12 | 0.136479E+13 |
February | 0.287411E+12 | 0.186668E+10 | 0.00 | 0.286943E+12 | 0.182925E+13 |
March | 0.352366E+12 | 0.819554E+09 | 0.00 | 0.185901E+12 | 0.281153E+13 |
April | 0.370651E+12 | -0.196980E+10 | 0.00 | -0.180497E+12 | 0.366445E+13 |
May | 0.377349E+12 | -0.568620E+10 | 0.00 | -0.702203E+12 | 0.361469E+13 |
June | 0.359060E+12 | -0.112986E+11 | 0.00 | -0.138182E+13 | 0.482536E+13 |
July | 0.349548E+12 | -0.153150E+11 | 0.00 | -0.193948E+13 | 0.601442E+13 |
August | 0.332550E+12 | -0.151222E+11 | 0.00 | -0.207792E+13 | 0.678802E+13 |
September | 0.291185E+12 | -0.119335E+11 | 0.00 | -0.158879E+13 | 0.453113E+13 |
October | 0.246363E+12 | -0.616885E+10 | 0.00 | -0.864608E+12 | 0.398405E+13 |
November | 0.202096E+12 | -0.135717E+10 | 0.00 | -0.218427E+12 | 0.326617E+13 |
December | 0.215235E+12 | 0.110310E+10 | 0.00 | 0.225604E+12 | 0.288841E+13 |
Annual Sum or Average | 0.363866E+13 | -0.627010E+11 | 0.00 | -0.779509E+13 | 0.455823E+14 |
Minimum of Months | 0.202096E+12 | -0.153150E+11 | 0.00 | -0.207792E+13 | 0.136479E+13 |
Maximum of Months | 0.377349E+12 | 0.236102E+10 | 0.00 | 0.460217E+12 | 0.678802E+13 |