Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2024-07-03 12:26:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 27660.13 | 597.15 | 597.15 |
Net Site Energy | 27049.52 | 583.97 | 583.97 |
Total Source Energy | 86275.11 | 1862.57 | 1862.57 |
Net Source Energy | 84341.30 | 1820.82 | 1820.82 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 635.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2191.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1711.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 263.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1641.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2895.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 446.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 623.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6464.11 |
Humidification | 2159.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.29 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 415.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27024.26 | 635.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9547.56 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 635.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2191.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1711.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 263.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1582.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2895.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 446.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 623.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6464.11 |
Humidification | General | 2159.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.29 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 415.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 635.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2191.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1711.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 263.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1641.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2895.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 446.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 623.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6464.11 |
Humidification | Unassigned | 2159.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.29 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 415.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 188.50 | 13.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Other | 352.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 583.42 | 13.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 188.50 | 13.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Other | 352.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 583.42 | 13.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 637.148 | 2.36 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -26.53 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 610.615 | 2.26 |
Electricity Coming From Utility | 26413.643 | 97.74 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 26413.643 | 97.74 |
Total On-Site and Utility Electric Sources | 27024.259 | 100.00 |
Total Electricity End Uses | 27024.259 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9547.56 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9547.56 | 100.00 |
Total Water End Uses | 9547.56 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.17 |
Time Setpoint Not Met During Occupied Cooling | 2244.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5858.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-AUG-15:20 | 21-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 28-JUN-16:10 |
Heating | 0.00 | 728838.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 395821.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 154849.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 287042.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 40045.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 73784.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 16704.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 30641.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1923249.04 | 728838.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 728838.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 395821.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3359.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 151268.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 287042.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 40045.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 73784.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 16704.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 30641.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 689.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6940.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5421.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 833.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 5198.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9168.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1414.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1974.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 6838.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1314.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 85585.83 | 689.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 149.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 112.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 197.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 30.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 42.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 147.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1847.69 | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 149.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 112.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 197.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 30.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 42.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 147.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1847.69 | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.90 | 0.358997 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.38 | 0.298338 | 0.254000 | 1.62 | 0.795567 | 0.500000 | 0.001277 | 0.000293 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 59.72 | 0.318482 | 0.271000 | 16.18 | 0.849286 | 0.500000 | 0.001196 | 0.007563 | 16.18 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.03 | 0.315635 | 0.268000 | 1.61 | 0.841692 | 0.500000 | 0.001207 | 0.001659 | 2.74 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.15 | 0.207335 | 0.176000 | 0.202727 | 0.552894 | 0.500000 | 0.001838 | 0.000190 | 0.314004 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.48 | 0.104106 | 0.088000 | 0.130095 | 0.300000 | 0.500000 | 0.003660 | 0.000137 | 0.226266 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.47 | 0.162815 | 0.138000 | 0.202426 | 0.434173 | 0.500000 | 0.002340 | 0.000241 | 0.399735 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.85 | 0.083053 | 0.071000 | 0.131569 | 0.300000 | 0.500000 | 0.004587 | 0.000086 | 0.142224 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.83 | 0.220476 | 0.187000 | 2.03 | 0.587937 | 0.500000 | 0.001728 | 0.004027 | 6.67 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 15.79 | 0.300000 | 0.500000 | 0.003908 | 0.002675 | 4.43 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.16 | 0.168699 | 0.143000 | 2.02 | 0.449865 | 0.500000 | 0.002258 | 0.003988 | 6.61 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 16.95 | 0.090810 | 0.077000 | 1.30 | 0.300000 | 0.500000 | 0.004196 | 0.002503 | 4.15 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.25 | 0.191555 | 0.163000 | 0.203220 | 0.510813 | 0.500000 | 0.001989 | 0.000518 | 0.859431 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.60 | 0.096432 | 0.082000 | 0.130871 | 0.300000 | 0.500000 | 0.003951 | 0.000342 | 0.566980 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.57 | 0.152457 | 0.130000 | 0.203647 | 0.406552 | 0.500000 | 0.002499 | 0.000514 | 0.852628 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.80 | 0.085324 | 0.073000 | 0.131676 | 0.300000 | 0.500000 | 0.004465 | 0.000328 | 0.544274 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 13410.71 | 0.000293 | 374.29 | |
CORE_MID VAV BOX REHEAT COIL | 345740.44 | 0.007563 | 11836.03 | |
CORE_TOP VAV BOX REHEAT COIL | 75838.30 | 0.001659 | 2951.15 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8678.22 | 0.000190 | 337.74 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6250.47 | 0.000137 | 243.18 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11038.17 | 0.000241 | 429.34 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3937.12 | 0.000086 | 153.39 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 184074.04 | 0.004027 | 7153.65 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 122268.52 | 0.002675 | 4751.52 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 182310.81 | 0.003988 | 7085.22 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 114413.70 | 0.002503 | 4446.63 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23690.29 | 0.000518 | 920.41 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15628.27 | 0.000342 | 607.17 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 23503.08 | 0.000514 | 913.14 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15003.21 | 0.000328 | 582.91 | |
VAV_BOT WITH REHEAT HEATING COIL | 44583.02 | 0.000975 | 963.36 | |
VAV_MID WITH REHEAT HEATING COIL | 355238.59 | 0.007771 | 7874.94 | |
VAV_TOP WITH REHEAT HEATING COIL | 35098.38 | 0.000768 | 788.62 | |
CAV_BAS HEATING COIL | 244290.61 | 0.002188 | 3851.88 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.577987 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.54 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.565621 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 29.77 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.16 | 2.29 | 12.33 | 2.29 | 10.73 | 10.73 | 0.300000 | 0.213038 | 10.73 |
VAV_MID WITH REHEAT | 58.72 | 22.85 | 117.45 | 32.68 | 99.90 | 99.90 | 0.300000 | 0.327116 | 99.90 |
VAV_TOP WITH REHEAT | 6.12 | 2.28 | 12.24 | 5.57 | 11.18 | 11.18 | 0.300000 | 0.497952 | 11.18 |
CAV_BAS | 0.000000 | 0.000000 | 5.90 | 1.20 | 5.90 | 5.90 | 1.00 | 0.203431 | 5.90 |
AIRLOOP DATACENTER BASEMENT | 29.77 | 29.77 | 29.77 | 29.77 | 29.77 | 29.77 | 1.00 | 0.999989 | 29.77 |
AIRLOOP DATACENTER BOT | 0.577987 | 0.577987 | 0.577987 | 0.577987 | 0.577987 | 0.577987 | 1.00 | 1.00 | 0.577987 |
AIRLOOP DATACENTER MID | 5.54 | 5.54 | 5.54 | 5.54 | 5.54 | 5.54 | 1.00 | 1.00 | 5.54 |
AIRLOOP DATACENTER TOP | 0.565621 | 0.565621 | 0.565621 | 0.565621 | 0.565621 | 0.565621 | 1.00 | 1.00 | 0.565621 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.73 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 99.90 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.18 | |
CAV_BAS_OA_CONTROLLER | 5.90 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 29.77 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.577987 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.54 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.565621 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.17 | 6.67 | 10.67 | 0.007035 | 0.007035 | 167660.69 | 0.004795 | 10.73 |
VAV_MID WITH REHEAT COOLING COIL | 26.40 | 6.67 | 10.66 | 0.007024 | 0.007024 | 1585357.73 | 0.045341 | 99.90 |
VAV_TOP WITH REHEAT COOLING COIL | 26.02 | 6.67 | 10.67 | 0.007030 | 0.007030 | 173086.74 | 0.004950 | 11.18 |
CAV_BAS COOLING COIL | 26.40 | 6.67 | 10.64 | 0.007142 | 0.007142 | 93708.53 | 0.002680 | 5.90 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.73 |
VAV_MID WITH REHEAT FAN | 99.90 |
VAV_TOP WITH REHEAT FAN | 11.18 |
CAV_BAS FAN | 5.90 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004795 | 0.000099 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000975 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.045341 | 0.000011 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.007771 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.004950 | 0.000096 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000768 | |
CAV_BAS_COOLC_CONTROLLER | 0.002680 | 0.000178 |
CAV_BAS_HEATC_CONTROLLER | 0.002188 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 29.77 | 544662.22 | 288931.97 | 0.013339 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.577987 | 10310.22 | 5518.44 | 0.000252 |
AIRLOOP DATACENTER MID COOLING COIL | 5.54 | 98834.18 | 52886.49 | 0.002420 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.565621 | 10092.11 | 5400.99 | 0.000247 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 29.77 | 29.77 | 29.77 | 29.77 | 544662.22 | 544662.22 | 16131.55 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.577987 | 0.577987 | 0.577987 | 0.577987 | 10310.22 | 10310.22 | 745.21 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.54 | 5.54 | 5.54 | 5.54 | 98834.18 | 98834.18 | 7452.11 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.565621 | 0.565621 | 0.565621 | 0.565621 | 10092.11 | 10092.11 | 745.21 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 29.77 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.577987 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.54 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.565621 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 29.77 | 544662.22 | 0.013339 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.577987 | 10310.22 | 0.000252 |
AIRLOOP DATACENTER MID HEATING COIL | 5.54 | 98834.18 | 0.002420 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.565621 | 10092.11 | 0.000247 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 16131.55 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 745.21 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 7452.11 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 745.21 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000161 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.057766 | 9338.11 | |
HEATSYS1 PUMP | 0.036765 | 10962.52 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.057766 | 6.93 |
HEATSYS1 | 0.036765 | 4.41 |
COOLSYS1_SUPPLY | 0.057766 | 6.93 |
SINGLE WATER PLANT LOOP | 0.016259 | 1.95 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.057766 | 0.057766 | 242474.63 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1680705.35 | 1680705.35 | 0.036765 |
CENTRAL BOILER | 669724.71 | 654172.95 | 0.016259 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.028883 | 3232.54 |
COOLSYS1 CHILLER2 PUMP | 0.028883 | 3232.54 |
PLANT CIRC PUMP | 0.016259 | 4105.76 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.057766 | 0.029268 | 1023361.18 | 1023360.49 | 0.052599 |
COOLSYS1 CHILLER2 | 0.057766 | 0.029268 | 1023361.18 | 1023360.49 | 0.052599 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.016259 | 161438.19 | 81728.17 | 80719.10 | 7004.20 | 49036.90 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.105197 | 12.62 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.105197 | 25786.70 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 48.01 | 1226484.79 | 9.60 | 153310.60 |
TOWERWATERSYS COOLTOWER 2 | 48.01 | 1226484.79 | 9.60 | 153310.60 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.053067 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.9398 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.9084 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8967 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9335 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8058 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.29018797E-14 | 0.36812723E-16 | -0.14924019E-09 | 0.48847313E-16 |
51 | 8 | 0.21807402E-07 | 0.12652057E-12 | 0.37708831E-03 | -0.24795767E-09 |
52 | 7 | -0.12220551E-01 | 0.65729479E-08 | -0.23055577E-01 | 0.13895212E-03 |
53 | 6 | 0.40477966 | 0.22909352E-05 | 0.47160541 | -0.47410351E-02 |
54 | 5 | -5.1849947 | 0.85678555E-04 | -4.4375337 | 0.63114796E-01 |
55 | 4 | 32.978226 | 0.70190469E-03 | 21.425779 | -0.42179587 |
56 | 3 | -111.17384 | 0.15317614E-02 | -55.595241 | 1.5144378 |
57 | 2 | 197.07933 | 0.86263138E-03 | 77.848428 | -2.8998938 |
58 | 1 | -171.14541 | 0.92189209E-04 | -55.246988 | 2.7452524 |
59 | 0 | 57.057407 | 0.52547460E-06 | 15.559906 | |
60 | 9 | -0.29188985E-14 | 0.30841220E-16 | -0.15071594E-09 | 0.45756810E-16 |
61 | 8 | 0.22014798E-07 | 0.12246996E-12 | 0.37926559E-03 | -0.25031584E-09 |
62 | 7 | -0.12285514E-01 | 0.63488536E-08 | -0.23149110E-01 | 0.13969077E-03 |
63 | 6 | 0.40654483 | 0.22108485E-05 | 0.47310859 | -0.47618422E-02 |
64 | 5 | -5.2022205 | 0.82619656E-04 | -4.4490782 | 0.63328388E-01 |
65 | 4 | 33.054419 | 0.67637415E-03 | 21.470902 | -0.42280751 |
66 | 3 | -111.33595 | 0.14751306E-02 | -55.684449 | 1.5167798 |
67 | 2 | 197.23999 | 0.83027991E-03 | 77.930247 | -2.9024452 |
68 | 1 | -171.20475 | 0.88686394E-04 | -55.270783 | 2.7462925 |
69 | 0 | 57.057407 | 0.50524406E-06 | 15.555978 | |
70 | 9 | -0.57207635E-15 | 0.35733182E-16 | -0.14510758E-09 | 0.92780423E-20 |
71 | 8 | 0.21226260E-07 | 0.13767829E-12 | 0.37094976E-03 | -0.24134990E-09 |
72 | 7 | -0.12037268E-01 | 0.71989887E-08 | -0.22791647E-01 | 0.13686812E-03 |
73 | 6 | 0.39979937 | 0.25155658E-05 | 0.46736115 | -0.46823295E-02 |
74 | 5 | -5.1363910 | 0.94286903E-04 | -4.4049234 | 0.62512134E-01 |
75 | 4 | 32.763227 | 0.77396227E-03 | 21.298286 | -0.41894130 |
76 | 3 | -110.71637 | 0.16919998E-02 | -55.343173 | 1.5078286 |
77 | 2 | 196.62589 | 0.95437189E-03 | 77.617295 | -2.8926932 |
78 | 1 | -170.97790 | 0.10214201E-03 | -55.179873 | 2.7423166 |
79 | 0 | 57.057407 | 0.58311013E-06 | 15.571069 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1565E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.1585E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.6869E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.6886E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5086E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5100E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4917E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4924E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2043E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3466E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7273E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.8514E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5430E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6453E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5122E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5645E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1548 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1468E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1740 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9324E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1116 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3459E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5025E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5661E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2064E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3557E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7293E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.8606E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5448E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6519E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5127E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5660E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1562E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.1584E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.6866E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.6884E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5084E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5098E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4916E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4923E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3648E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6284E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0585E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3416E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8901E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0129E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2602E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2962E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8755E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8662E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3955E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5596E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7605E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3812E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6880E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7537E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2881E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3868E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9600E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0314E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8511E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8785E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2603E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2968E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5559E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5579E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1754E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1770E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9260E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9271E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4917E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4925E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6005E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7163E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2115E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3025E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9546E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0182E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5127E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5660E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0491E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1330E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1040E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6144E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7926E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0891E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5025E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5656E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5993E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7134E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2104E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2996E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9533E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0141E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5122E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5645E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5558E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5577E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1753E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1769E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9259E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9270E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4916E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4923E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1946E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2939E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8439E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9156E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7729E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8000E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2604E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2969E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7124E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8027E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1947E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4813E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6162E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3245E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6880E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7537E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2684E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5214E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9391E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2088E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8114E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9320E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2601E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2961E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1507 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.9232E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1637 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1090 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1221 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.4473E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.5140E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7277E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.0228E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1475E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.4857E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7700E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.8525E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.5385E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.6552E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7590E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0467E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.3627E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.9753E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6538E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6320E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9949E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5140E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7273E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8383E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0598E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2584E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6616E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6907E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4629E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6552E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7590E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1508 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.9441E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1639 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1092 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1223 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.4634E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.5258E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7338E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.0278E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1538E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.4914E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7759E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.8632E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.5459E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.6670E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7650E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0471E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.3665E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.9760E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6568E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6377E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9985E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5258E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7333E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8430E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0658E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2637E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6672E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.7012E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4701E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6670E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7650E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 67194.14223 | 67194.14223 | 5.89956 | 5.89956 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72615.18146 | 72615.18146 | 6.37547 | 6.37547 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 680396.37539 | 680396.37539 | 59.72216 | 59.72216 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 211707.81339 | 211707.81339 | 11.03916 | 11.03916 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 68029.60311 | 68029.60311 | 6.02610 | 6.02610 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.69938E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 53109.99755 | 53109.99755 | 2.74449 | 2.74449 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13003.80620 | 13003.80620 | 1.15186 | 1.15186 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 6080.08607 | 6080.08607 | 0.31400 | 0.31400 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 16689.92040 | 16689.92040 | 1.47835 | 1.47835 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.67500 | 5.68796E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 4378.04628 | 4378.04628 | 0.22627 | 0.22627 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 16560.01097 | 16560.01097 | 1.46686 | 1.46686 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 34.53750 | 5.69851E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 7729.57937 | 7729.57937 | 0.39974 | 0.39974 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20920.61804 | 20920.61804 | 1.85309 | 1.85309 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2761.12566 | 2761.12566 | 0.14222 | 0.14222 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 122288.32426 | 122288.32426 | 10.83203 | 10.83203 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 128821.79238 | 128821.79238 | 6.67484 | 6.67484 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 178239.87305 | 178239.87305 | 15.78792 | 15.78792 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44000 | 5.68912E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 85565.65800 | 85565.65800 | 4.43394 | 4.43394 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 159824.69348 | 159824.69348 | 14.15688 | 14.15688 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 34.65000 | 5.69869E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 127589.19898 | 127589.19898 | 6.61077 | 6.61077 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 191336.99403 | 191336.99403 | 16.94802 | 16.94802 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 80074.45770 | 80074.45770 | 4.14858 | 4.14858 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14075.22739 | 14075.22739 | 1.24675 | 1.24675 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 16576.02490 | 16576.02490 | 0.85943 | 0.85943 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 18018.19327 | 18018.19327 | 1.59599 | 1.59599 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.82250 | 5.68971E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 10934.89665 | 10934.89665 | 0.56698 | 0.56698 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 17685.27639 | 17685.27639 | 1.56651 | 1.56651 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 16445.14275 | 16445.14275 | 0.85263 | 0.85263 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 20364.09256 | 20364.09256 | 1.80378 | 1.80378 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 10497.86982 | 10497.86982 | 0.54427 | 0.54427 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8272.82471 | 8272.82471 | 0.57799 | 0.57799 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.17250 | 5.69177E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 79265.03521 | 79265.03521 | 5.53795 | 5.53795 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.17250 | 5.69177E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8095.79838 | 8095.79838 | 0.56562 | 0.56562 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.51000 | 5.69229E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370470.89409 | 426041.52820 | 25.88280 | 29.76521 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 22.81500 | 5.68069E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -7.90000 | 2.34317E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 138403.54 | 10.73134 | 10.73134 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 42130.42 | 2.16005 | 2.16005 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1271332.29 | 99.89701 | 99.89701 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 418293.96 | 32.67788 | 32.67788 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 146559.29 | 11.18140 | 11.18140 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 41639.83 | 5.56780 | 5.56780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 |
7 | CAV_BAS | Cooling | Sensible | 70634.52 | 5.89956 | 5.89956 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 57212.75 | 1.20016 | 1.20016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 422864.15 | 29.76555 | 29.76555 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 16131.55 | 0.33839 | 0.33839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8220.12 | 0.57799 | 0.57799 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 745.21 | 1.56323E-002 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78761.16 | 5.53795 | 5.53795 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 7452.11 | 0.15632 | 0.15632 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8047.08 | 0.56562 | 0.56562 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 745.21 | 1.56323E-002 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.89956 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.35900 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.37547 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29834 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25400 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61937 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79557 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27708E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.93360E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61937 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13410.71062 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.93360E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 374.29428 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 59.72216 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31848 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27100 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.18470 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84929 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19630E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.56308E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.18470 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 345740.43986 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.56308E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11836.03215 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.02610 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31563 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26800 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61499 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84169 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20709E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.65896E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.74449 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 75838.30111 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.65896E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2951.14691 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15186 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20734 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17600 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20273 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55289 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83760E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.89836E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31400 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8678.22292 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89836E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 337.73589 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.47835 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10411 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.80000E-002 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13009 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.65974E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36729E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22627 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6250.46847 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36729E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 243.17967 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46686 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16281 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13800 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20243 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43417 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34008E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.41460E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39974 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11038.16969 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.41460E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 429.34164 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.85309 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.30532E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.10000E-002 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13157 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.58742E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.61246E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.14222 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3937.12131 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.61246E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 153.38639 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.83203 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22048 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18700 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02559 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58794 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72808E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.02662E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.67484 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 184074.04328 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.02662E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7153.65077 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.78792 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.90838E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.67463E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.43394 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 122268.51924 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.67463E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4751.51971 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.15688 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16870 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14300 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02443 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44987 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.25845E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.98805E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.61077 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 182310.80848 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.98805E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7085.21646 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.94802 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.08100E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.70000E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30500 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.19557E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.50280E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.14858 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 114413.69721 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.50280E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4446.62714 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24675 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19155 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16300 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20322 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51081 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.98899E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.18226E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.85943 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23690.29272 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.18226E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 920.41010 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59599 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.64324E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.20000E-002 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13087 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.95096E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.41869E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.56698 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15628.26946 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.41869E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 607.17109 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.56651 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15246 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20365 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40655 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.49906E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.14131E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.85263 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23503.08245 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.14131E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 913.14404 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.80378 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.53236E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.30000E-002 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13168 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.46535E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.28196E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54427 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15003.21098 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.28196E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 582.90759 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.57799 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.53795 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.56562 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 29.76521 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.16281 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28619 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.32563 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28619 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.73134 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.73134 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.21304 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 58.72351 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.85013 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 117.44702 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 32.67788 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 99.89701 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 99.89701 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32712 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.11956 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28441 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.23912 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.56780 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.18140 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.18140 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.49795 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.89956 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.89956 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.89956 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.20343 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 29.76521 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 29.76521 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 29.76521 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 29.76521 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 29.76555 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 29.76555 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.57799 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.57799 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.57799 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.57799 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.57799 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.57799 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.53795 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.53795 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.53795 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.53795 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.53795 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.53795 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.56562 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.56562 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.56562 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.56562 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.56562 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.56562 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.73134 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 99.89701 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.18140 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.89956 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 29.76555 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.57799 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.53795 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.56562 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.73134 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.16500 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66792 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.03528E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.03528E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 167660.68862 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.79507E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.73134 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 44583.02342 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.75255E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 963.35625 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.73134 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.79507E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.93083E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.75255E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 99.89701 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.39836 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.65649 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.02417E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.02417E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1585357.73041 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.53410E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 99.89701 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 355238.59311 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.77085E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7874.93741 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 99.89701 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.53410E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.05024E-005 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.77085E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.18140 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.02272 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66790 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.02972E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.02972E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 173086.74335 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.95026E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.18140 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 35098.37621 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.67778E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 788.61883 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.18140 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.95026E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.61951E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.67778E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.89956 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.39556 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.64312 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.14159E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.14159E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 93708.52863 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.68005E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.89956 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 244290.61043 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.18750E-003 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3851.88490 |
350 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.89956 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.68005E-003 |
352 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.77680E-004 |
353 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.18750E-003 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 29.76555 |
355 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 29.76555 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 544662.22377 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 288931.96711 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.33387E-002 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 29.76555 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 29.76555 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 29.76555 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 29.76555 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 544662.22377 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 544662.22377 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 16131.54879 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
368 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 29.76555 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 29.76555 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 544662.22377 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.33387E-002 |
372 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 16131.54879 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.60989E-004 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.57799 |
378 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.57799 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10310.22099 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5518.44357 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.52497E-004 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.57799 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.57799 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.57799 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.57799 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10310.22099 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10310.22099 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.21073 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
391 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.57799 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.57799 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10310.22099 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.52497E-004 |
395 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 745.21073 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.53795 |
397 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.53795 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 98834.17528 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 52886.48955 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42044E-003 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.53795 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.53795 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.53795 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.53795 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 98834.17528 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 98834.17528 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 7452.10725 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
410 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.53795 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.53795 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 98834.17528 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42044E-003 |
414 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7452.10725 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.56562 |
416 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56562 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10092.11448 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5400.99108 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47155E-004 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.56562 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.56562 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.56562 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.56562 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10092.11448 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10092.11448 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.21073 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
429 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.56562 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56562 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10092.11448 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47155E-004 |
433 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 745.21073 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.77664E-002 |
435 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 9338.10947 |
436 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.77664E-002 |
437 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.93197 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.77664E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.77664E-002 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 242474.63277 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
442 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.67655E-002 |
443 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 4.41186 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.67655E-002 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 10962.52168 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
447 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1680705.35055 |
448 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1680705.35000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.67655E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.77664E-002 |
451 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.93197 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.88832E-002 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3232.54405 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.88832E-002 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3232.54405 |
456 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.77664E-002 |
457 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.92680E-002 |
458 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1023361.18346 |
459 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1023360.49000 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.25987E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.77664E-002 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.92680E-002 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1023361.18346 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1023360.49000 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.25987E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.62588E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.95106 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.62588E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 4105.75898 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.62588E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 161438.19258 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 81728.17170 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 80719.09629 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 49036.90302 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 669724.70807 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 654172.95000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.62588E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10520 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.62370 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10520 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 25786.70052 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 48.01281 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1226484.79135 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.60256 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 153310.59892 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 48.01281 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1226484.79135 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.60256 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 153310.59892 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.30675E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.30675E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18674.12 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 481741.76 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 105619.09 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 12086.05 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8704.96 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 15372.74 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5483.17 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 256358.40 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 170282.37 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 253902.75 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 159343.00 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 32993.30 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 21765.38 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 32732.57 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 20894.86 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 48016.46 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 395550.67 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 39984.15 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 139487.57 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 209251.88 | 140999.20 | 68252.67 | 0.67 | 29053.36 | 294.68 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1964700.41 | 1318582.88 | 646117.53 | 0.67 | 271322.13 | 2751.90 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 216987.93 | 146549.71 | 70438.22 | 0.68 | 30256.51 | 306.88 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 116163.55 | 77930.10 | 38233.45 | 0.67 | 16070.83 | 163.00 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 7.93 | 27.04 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 7.93 | 27.04 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.7451751431E-003 | 1.1162399324E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.3110888812 | 0.2338119485 | Pass | Pass | 0.2676212190 | 0.4411291764 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.2506073142E-002 | 0.1286971908 | Pass | Pass | 0.1595393568 | 0.3614431265 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.1821350945E-002 | 6.7206921551E-002 | Pass | Pass | 0.1686612788 | 0.3688885193 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1819411044 | 0.1486280526 | Pass | Pass | 0.2656972829 | 0.4386070701 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2681061260 | 0.2916548541 | Pass | Pass | 0.2718559983 | 0.4454679980 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4904188999 | 0.7379219929 | Pass | Pass | 0.2765401379 | 0.4509754011 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2726508440 | 0.3573943036 | Pass | Pass | 0.2740646208 | 0.4571518984 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.1330913389E-002 | 7.5880259101E-002 | Pass | Pass | 0.1586799932 | 0.3550717932 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1442869091 | 0.1648907045 | Pass | Pass | 0.1615062445 | 0.3662034140 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4434571599 | 0.7776803982 | Pass | Pass | 0.1899906036 | 0.4576808397 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1324604333 | 0.1850871853 | Pass | Pass | 0.1593189380 | 0.3516783324 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.7184160269E-002 | 8.3830644082E-002 | Pass | Pass | 0.2360122701 | 0.6731234650 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1221984526 | 0.1384949922 | Pass | Pass | 0.2145112516 | 0.6212406404 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3472297919 | 0.5468325229 | Pass | Pass | 0.1754819613 | 0.3698938719 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1321598926 | 0.1522892163 | Pass | Pass | 0.1736222257 | 0.3813102185 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.9652883828E-002 | 3.7338466266E-002 | Pass | Pass | 1.4601680003 | 6.1114037882 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.4918055418E-002 | 5.3473918474E-002 | Pass | Pass | 0.4368452164 | 2.6383252393 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.8681992662E-002 | 7.8529093034E-002 | Pass | Pass | 0.1847810526 | 0.3972820603 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.7328962208E-006 | 4.1528648019E-006 | Pass | Pass | 7.8631359943E-003 | 1.0821031409E-002 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.5088155807E-006 | 3.7246954382E-006 | Pass | Pass | 2.6189280905E-002 | 1.5572798764E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.6177493036E-002 | 2.6480091079E-002 | Pass | Pass | 0.2232169035 | 1.1268529281 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.5254417155E-005 | 5.7215202995E-005 | Pass | Pass | 1.0957454360E-004 | 1.0810171514E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8515.20 | 67.56 | 0.00 | 25044.91 | 15239.49 | 48867.17 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 1390.74 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.062 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 116.04 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 1042.11 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.93 | 0.0000 | Y | 7.45 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.88 | 0.0000 | Y | 4.79 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.72 | 0.0000 | Y | 7.38 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.71 | 0.0000 | Y | 4.76 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.90 | 0.0000 | Y | 74.44 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.86 | 0.0000 | Y | 47.88 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.70 | 0.0000 | Y | 73.77 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.69 | 0.0000 | Y | 47.52 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.90 | 0.0000 | Y | 7.44 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.86 | 0.0000 | Y | 4.79 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.70 | 0.0000 | Y | 7.38 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.69 | 0.0000 | Y | 4.75 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.66 | 0.0000 | Y | 32.85 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 16.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 539.66 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 41.81 | 41.81 | 101.67 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.71 | 62.76 | 10.84 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.71 | 46.63 | 150.69 | |
Exterior Lighting Total | 31088.59 | 263.19 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2013592.48 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1680705.35 | 0.94 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1023360.49 | 5.17 | 1019895.05 | 5.11 | 7.93 | 27.04 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1023360.49 | 5.17 | 1019895.05 | 5.11 | 7.93 | 27.04 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 672793.67 | |||||
CENTRAL BOILER | Boiler:HotWater | 654172.95 | 0.94 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1226484.79 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1226484.79 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 167660.69 | 209251.88 | 140999.20 | 68252.67 | 0.67 | - | 29053.36 | 294.68 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1585357.73 | 1964700.41 | 1318582.88 | 646117.53 | 0.67 | - | 271322.13 | 2751.90 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 173086.74 | 216987.93 | 146549.71 | 70438.22 | 0.68 | - | 30256.51 | 306.88 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 93708.53 | 116163.55 | 77930.10 | 38233.45 | 0.67 | - | 16070.83 | 163.00 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 544662.22 | 288931.97 | 255730.26 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10310.22 | 5518.44 | 4791.78 | 0.54 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 98834.18 | 52886.49 | 45947.69 | 0.54 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10092.11 | 5400.99 | 4691.12 | 0.54 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 13410.71 | 18674.12 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 345740.44 | 481741.76 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 75838.30 | 105619.09 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 8678.22 | 12086.05 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6250.47 | 8704.96 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11038.17 | 15372.74 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3937.12 | 5483.17 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 184074.04 | 256358.40 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 122268.52 | 170282.37 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 182310.81 | 253902.75 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 114413.70 | 159343.00 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 23690.29 | 32993.30 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 15628.27 | 21765.38 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23503.08 | 32732.57 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 15003.21 | 20894.86 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 44583.02 | 48016.46 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 355238.59 | 395550.67 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 35098.38 | 39984.15 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 139487.57 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 544662.22 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10310.22 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 98834.18 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10092.11 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 16131.55 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 745.21 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 7452.11 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 745.21 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.73 | 23066.64 | 2149.46 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 99.90 | 215872.11 | 2160.95 | 1.00 | 1.08 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.18 | 24034.02 | 2149.46 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.90 | 12830.89 | 2174.89 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 29.77 | 48884.91 | 1642.33 | 1.00 | 1.14 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.58 | 647.41 | 1120.11 | 1.00 | 1.54 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.54 | 6203.11 | 1120.11 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.57 | 633.56 | 1120.11 | 1.00 | 1.55 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.057766 | 9338.11 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.036765 | 10962.52 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028883 | 3232.54 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028883 | 3232.54 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.016259 | 4105.76 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.105197 | 25786.70 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 67194.14 | 67194.14 | 24.18 | 5.900 | 5.900 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00752 | 25.11 | 0.00568 | 1.200 | 0.00 |
CORE_BOTTOM | 72615.18 | 72615.18 | 29.09 | 6.375 | 6.375 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 25.11 | 0.00568 | 1.078 | 0.00 |
CORE_MID | 680396.38 | 680396.38 | 272.58 | 59.722 | 59.722 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00746 | 25.11 | 0.00568 | 10.778 | 0.00 |
CORE_TOP | 68029.60 | 68029.60 | 27.25 | 6.026 | 6.026 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00745 | 35.10 | 0.00570 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13003.81 | 13003.81 | 41.49 | 1.152 | 1.152 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00728 | 35.10 | 0.00570 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 16689.92 | 16689.92 | 82.63 | 1.478 | 1.478 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00714 | 27.68 | 0.00569 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 16560.01 | 16560.01 | 52.84 | 1.467 | 1.467 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00722 | 34.54 | 0.00570 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20920.62 | 20920.62 | 103.58 | 1.853 | 1.853 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00711 | 33.39 | 0.00570 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 122288.32 | 122288.32 | 390.18 | 10.832 | 10.832 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00727 | 35.10 | 0.00570 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 178239.87 | 178239.87 | 882.48 | 15.788 | 15.788 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00712 | 28.44 | 0.00569 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 159824.69 | 159824.69 | 509.94 | 14.157 | 14.157 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00721 | 34.65 | 0.00570 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 191336.99 | 191336.99 | 947.33 | 16.948 | 16.948 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00711 | 33.21 | 0.00570 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14075.23 | 14075.23 | 44.91 | 1.247 | 1.247 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00723 | 35.10 | 0.00570 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 18018.19 | 18018.19 | 89.21 | 1.596 | 1.596 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00712 | 28.82 | 0.00569 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 17685.28 | 17685.28 | 56.43 | 1.567 | 1.567 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00718 | 34.88 | 0.00570 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 20364.09 | 20364.09 | 100.82 | 1.804 | 1.804 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00710 | 33.21 | 0.00570 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8272.82 | 8272.82 | 228.51 | 0.578 | 0.578 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 30.17 | 0.00569 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 79265.04 | 79265.04 | 2189.48 | 5.538 | 5.538 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 30.17 | 0.00569 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8095.80 | 8095.80 | 223.62 | 0.566 | 0.566 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00709 | 30.51 | 0.00569 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370470.89 | 426041.53 | 543.64 | 25.883 | 29.765 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 22.82 | 0.00568 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 24.58 | 0.00234 | -7.90 | 0.00234 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 19.60 | 22.17 | 0.00234 | -7.90 | 0.00234 | 1.078 | 0.00 |
CORE_MID | 211707.81 | 211707.81 | 84.81 | 11.039 | 11.039 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 10.778 | 0.00 |
CORE_TOP | 53110.00 | 53110.00 | 21.28 | 2.744 | 2.744 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 6080.09 | 6080.09 | 19.40 | 0.314 | 0.314 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00759 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 4378.05 | 4378.05 | 21.68 | 0.226 | 0.226 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 7729.58 | 7729.58 | 24.66 | 0.400 | 0.400 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2761.13 | 2761.13 | 13.67 | 0.142 | 0.142 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00723 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 128821.79 | 128821.79 | 411.03 | 6.675 | 6.675 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 85565.66 | 85565.66 | 423.64 | 4.434 | 4.434 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 127589.20 | 127589.20 | 407.09 | 6.611 | 6.611 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 80074.46 | 80074.46 | 396.46 | 4.149 | 4.149 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 16576.02 | 16576.02 | 52.89 | 0.859 | 0.859 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 10934.90 | 10934.90 | 54.14 | 0.567 | 0.567 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 16445.14 | 16445.14 | 52.47 | 0.853 | 0.853 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 10497.87 | 10497.87 | 51.98 | 0.544 | 0.544 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -7.90 | 0.00234 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 18.00 | 26.57 | 0.00700 | -7.90 | 0.00234 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.30 | 0.00469 | -7.90 | 0.00234 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.53 | 0.00285 | -7.90 | 0.00234 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 18.00 | 27.00 | 0.00700 | -7.90 | 0.00234 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.73 | 10.73 | 2.16 | 2.16 | 10.7313 | 2.2862 | 10.7313 | 0.2130 | 0.3000 |
VAV_MID WITH REHEAT | 99.90 | 99.90 | 32.68 | 32.68 | 99.8970 | 32.6779 | 99.8970 | 0.3271 | 0.3000 |
VAV_TOP WITH REHEAT | 11.18 | 11.18 | 5.57 | 5.57 | 11.1814 | 5.5678 | 11.1814 | 0.4980 | 0.3000 |
CAV_BAS | 5.90 | 5.90 | 1.20 | 1.20 | 5.8996 | 1.2002 | 5.8996 | 0.2034 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 29.77 | 29.77 | 0.34 | 0.34 | 29.7656 | 29.7652 | 29.7656 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.58 | 0.58 | 0.02 | 0.02 | 0.5780 | 0.5780 | 0.5780 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.54 | 5.54 | 0.16 | 0.16 | 5.5380 | 5.5380 | 5.5380 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.57 | 0.57 | 0.02 | 0.02 | 0.5656 | 0.5656 | 0.5656 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 13410.711 | 13410.711 | 1.619370 | 0.00029336 | 374.294 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 13410.71 | 13410.71 | 1.619370 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 13433.73 | 13433.73 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 345740.440 | 345740.440 | 16.184705 | 0.00756308 | 11836.032 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 345740.44 | 345740.44 | 16.184705 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 211707.81 | 0.00 | 346565.83 | 346565.83 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 75838.301 | 75838.301 | 2.744488 | 0.00165896 | 2951.147 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 75838.30 | 75838.30 | 2.744488 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 53110.00 | 0.00 | 75999.77 | 75999.77 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8678.223 | 8678.223 | 0.314004 | 0.00018984 | 337.736 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8678.22 | 8678.22 | 0.314004 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00758812 | 40.3756 | 6080.09 | 0.00 | 8696.70 | 8696.70 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6250.468 | 6250.468 | 0.226266 | 0.00013673 | 243.180 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6250.47 | 6250.47 | 0.226266 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00765542 | 40.7292 | 4378.05 | 0.00 | 6263.78 | 6263.78 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 11038.170 | 11038.170 | 0.399735 | 0.00024146 | 429.342 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11038.17 | 11038.17 | 0.399735 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00775203 | 41.2363 | 7729.58 | 0.00 | 11061.67 | 11061.67 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3937.121 | 3937.121 | 0.142224 | 0.00008612 | 153.386 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3937.12 | 3937.12 | 0.142224 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00723326 | 38.5098 | 2761.13 | 0.00 | 3945.50 | 3945.50 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 184074.043 | 184074.043 | 6.674837 | 0.00402662 | 7153.651 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 184074.04 | 184074.04 | 6.674837 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00780473 | 41.5134 | 128821.79 | 0.00 | 184466.08 | 184466.08 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 122268.519 | 122268.519 | 4.433937 | 0.00267463 | 4751.520 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 122268.52 | 122268.52 | 4.433937 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00780636 | 41.5219 | 85565.66 | 0.00 | 122528.93 | 122528.93 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 182310.808 | 182310.808 | 6.610769 | 0.00398805 | 7085.216 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 182310.81 | 182310.81 | 6.610769 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00780204 | 41.4993 | 127589.20 | 0.00 | 182699.09 | 182699.09 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 114413.697 | 114413.697 | 4.148576 | 0.00250280 | 4446.627 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 114413.70 | 114413.70 | 4.148576 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00778635 | 41.4170 | 80074.46 | 0.00 | 114657.37 | 114657.37 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 23690.293 | 23690.293 | 0.859431 | 0.00051823 | 920.410 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23690.29 | 23690.29 | 0.859431 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00782146 | 41.6014 | 16576.02 | 0.00 | 23740.75 | 23740.75 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 15628.269 | 15628.269 | 0.566980 | 0.00034187 | 607.171 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15628.27 | 15628.27 | 0.566980 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00781985 | 41.5930 | 10934.90 | 0.00 | 15661.56 | 15661.56 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 23503.082 | 23503.082 | 0.852628 | 0.00051413 | 913.144 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23503.08 | 23503.08 | 0.852628 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00782001 | 41.5938 | 16445.14 | 0.00 | 23553.14 | 23553.14 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15003.211 | 15003.211 | 0.544274 | 0.00032820 | 582.908 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15003.21 | 15003.21 | 0.544274 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00781201 | 41.5518 | 10497.87 | 0.00 | 15035.17 | 15035.17 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 167660.689 | -999.000 | 10.731341 | 0.00479507 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 167660.69 | 167660.69 | 10.731341 | 26.17 | 13.91 | 0.00703528 | 10.67 | 8.02 | 0.00703528 | 35.10 | 0.00569938 | 15.77 | 18.9212 | 24.00 | 0.00735917 | 32.6444 | 117469.72 | 0.00 | 142086.67 | 142086.67 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 44583.023 | 44583.023 | 3.219402 | 0.00097525 | 963.356 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 44583.02 | 44583.02 | 3.219402 | -1.11 | -2.37 | 0.00331878 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 63.0707 | 21.36 | 0.00604998 | 31.5637 | 20948.84 | 0.00 | 41819.52 | 41819.52 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1585357.730 | -999.000 | 99.897006 | 0.04534103 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1585357.73 | 1585357.73 | 99.897006 | 26.40 | 13.98 | 0.00702417 | 10.66 | 8.00 | 0.00702417 | 35.10 | 0.00569938 | 15.77 | 20.3269 | 24.00 | 0.00738951 | 32.7773 | 1060526.02 | 0.00 | 1344652.36 | 1344652.36 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 355238.593 | 355238.593 | 29.969102 | 0.00777085 | 7874.937 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 355238.59 | 355238.59 | 29.969102 | 0.89 | -0.30 | 0.00405948 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 67.7565 | 19.37 | 0.00734781 | 43.2625 | 230178.25 | 0.00 | 344567.10 | 344567.10 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 173086.743 | -999.000 | 11.181400 | 0.00495026 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 173086.74 | 173086.74 | 11.181400 | 26.02 | 13.86 | 0.00702972 | 10.67 | 8.01 | 0.00702972 | 35.10 | 0.00569938 | 15.77 | 18.1596 | 24.00 | 0.00732635 | 32.5004 | 125731.05 | 0.00 | 146449.64 | 146449.64 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 35098.376 | 35098.376 | 3.354420 | 0.00076778 | 788.619 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 35098.38 | 35098.38 | 3.354420 | 2.29 | 1.04 | 0.00445451 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 60.5321 | 17.62 | 0.00746442 | 49.0320 | 27789.00 | 0.00 | 34831.39 | 34831.39 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 93708.529 | -999.000 | 5.899562 | 0.00268005 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 93708.53 | 93708.53 | 5.899562 | 26.40 | 14.08 | 0.00714159 | 10.64 | 8.12 | 0.00714159 | 34.43 | 0.00569833 | 15.56 | 20.3431 | 24.00 | 0.00757245 | 33.5795 | 58933.26 | 0.00 | 80387.00 | 80387.00 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.694125 | 0.00218750 | 3851.885 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.694125 | -1.61 | -4.13 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 32.4882 | 24.63 | 0.00234317 | 10.0874 | 0.00 | 0.00 | 99870.90 | 99870.90 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 544662.224 | 288931.967 | 29.765551 | 0.01333874 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 464821.47 | 463449.55 | -999.0 | 28.78 | 14.78 | 0.00702701 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | -999.0000 | 27.00 | 0.00704229 | 26.1562 | 370059.26 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10310.221 | 5518.444 | 0.577987 | 0.00025250 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8757.46 | 8709.22 | -999.0 | 28.24 | 14.62 | 0.00704939 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00708712 | 26.3189 | 8271.08 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 98834.175 | 52886.490 | 5.537953 | 0.00242044 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 83956.86 | 83475.79 | -999.0 | 28.25 | 14.63 | 0.00705139 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00709089 | 26.3329 | 79226.22 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10092.114 | 5400.991 | 0.565621 | 0.00024716 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8572.60 | 8524.37 | -999.0 | 28.25 | 14.62 | 0.00705044 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00708904 | 26.3260 | 8095.80 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 544662.224 | 544662.224 | 29.765551 | 0.01333874 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 544662.22 | 544662.22 | 29.765551 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.1369 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10310.221 | 10310.221 | 0.577987 | 0.00025250 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10310.22 | 10310.22 | 0.577987 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7046 | 26.88 | 0.00700000 | 26.1740 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 98834.175 | 98834.175 | 5.537953 | 0.00242044 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 98834.18 | 98834.18 | 5.537953 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.8228 | 24.48 | 0.00468604 | 20.2773 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10092.114 | 10092.114 | 0.565621 | 0.00024716 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10092.11 | 10092.11 | 0.565621 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7637 | 23.35 | 0.00284683 | 13.2226 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 16131.549 | 16131.549 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 16131.55 | 16131.55 | 29.765551 | -0.09 | -0.09 | 0.00694706 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.1369 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.21 | 745.21 | 0.577987 | -0.21 | -0.21 | 0.00687405 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7046 | 26.88 | 0.00700000 | 26.1740 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 7452.107 | 7452.107 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7452.11 | 7452.11 | 5.537953 | -0.22 | -0.22 | 0.00461990 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.8228 | 24.48 | 0.00468604 | 20.2773 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.21 | 745.21 | 0.565621 | -0.22 | -2.62 | 0.00283291 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7637 | 23.35 | 0.00284683 | 13.2226 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 13410.711 | 13410.711 | 1.619370 | 0.00029336 | 374.294 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 0.7822 | 0.797922 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | Sensible | 13410.71 | 13410.71 | 1.0000 | 1.60383830 | 1.619370 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.29332974 | 60.00 | 48.89 | 11.11 | 0.000 | 13410.71 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 13433.73 | 13433.73 | 1.60383830 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 345740.440 | 345740.440 | 16.184705 | 0.00756308 | 11836.032 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 20.1653 | 20.571151 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 345740.44 | 345740.44 | 1.0000 | 16.02947564 | 16.184705 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 7.56231022 | 60.00 | 48.89 | 11.11 | 0.000 | 345740.44 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.01 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 211707.81 | 0.00 | 346565.83 | 346565.83 | 16.02947564 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.00 | 19.34 | 0.00800000 | 54680.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 75838.301 | 75838.301 | 2.744488 | 0.00165896 | 2951.147 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 4.4233 | 4.512290 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 75838.30 | 75838.30 | 1.0000 | 2.71816496 | 2.744488 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.65879571 | 60.00 | 48.89 | 11.11 | 0.000 | 75838.30 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 53110.00 | 0.00 | 75999.77 | 75999.77 | 2.71816496 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61019.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8678.223 | 8678.223 | 0.314004 | 0.00018984 | 337.736 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 0.5062 | 0.516344 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8678.22 | 8678.22 | 1.0000 | 0.31099254 | 0.314004 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.18981700 | 60.00 | 48.89 | 11.11 | 0.000 | 8678.22 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00758812 | 21.00 | 0.00758812 | 40.3756 | 6080.09 | 0.00 | 8696.70 | 8696.70 | 0.31099254 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61024.2 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6250.468 | 6250.468 | 0.226266 | 0.00013673 | 243.180 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 0.3646 | 0.371896 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6250.47 | 6250.47 | 1.0000 | 0.22409628 | 0.226266 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.13671522 | 60.00 | 48.89 | 11.11 | 0.000 | 6250.47 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00765542 | 21.00 | 0.00765542 | 40.7292 | 4378.05 | 0.00 | 6263.78 | 6263.78 | 0.22409628 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61011.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11038.170 | 11038.170 | 0.399735 | 0.00024146 | 429.342 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 0.6438 | 0.656758 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11038.17 | 11038.17 | 1.0000 | 0.39590122 | 0.399735 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.24143564 | 60.00 | 48.89 | 11.11 | 0.000 | 11038.17 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00775203 | 21.00 | 0.00775203 | 41.2363 | 7729.58 | 0.00 | 11061.67 | 11061.67 | 0.39590122 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.3 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3937.121 | 3937.121 | 0.142224 | 0.00008612 | 153.386 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 0.2296 | 0.234254 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 3937.12 | 3937.12 | 1.0000 | 0.14086031 | 0.142224 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.08611585 | 60.00 | 48.89 | 11.11 | 0.000 | 3937.12 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.86 | 0.00723326 | 21.00 | 0.00723326 | 38.5098 | 2761.13 | 0.00 | 3945.50 | 3945.50 | 0.14086031 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.27 | 21.26 | 0.00800000 | 61069.9 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 184074.043 | 184074.043 | 6.674837 | 0.00402662 | 7153.651 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 10.7361 | 10.952190 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 184074.04 | 184074.04 | 1.0000 | 6.61081794 | 6.674837 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 4.02621405 | 60.00 | 48.89 | 11.11 | 0.000 | 184074.04 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00780473 | 21.00 | 0.00780473 | 41.5134 | 128821.79 | 0.00 | 184466.08 | 184466.08 | 6.61081794 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 122268.519 | 122268.519 | 4.433937 | 0.00267463 | 4751.520 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 7.1313 | 7.274834 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 122268.52 | 122268.52 | 1.0000 | 4.39141086 | 4.433937 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 2.67435442 | 60.00 | 48.89 | 11.11 | 0.000 | 122268.52 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00780636 | 21.00 | 0.00780636 | 41.5219 | 85565.66 | 0.00 | 122528.93 | 122528.93 | 4.39141086 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60961.8 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 182310.808 | 182310.808 | 6.610769 | 0.00398805 | 7085.216 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 10.6333 | 10.847280 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 182310.81 | 182310.81 | 1.0000 | 6.54736443 | 6.610769 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 3.98764718 | 60.00 | 48.89 | 11.11 | 0.000 | 182310.81 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00780204 | 21.00 | 0.00780204 | 41.4993 | 127589.20 | 0.00 | 182699.09 | 182699.09 | 6.54736443 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60964.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 114413.697 | 114413.697 | 4.148576 | 0.00250280 | 4446.627 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 6.6732 | 6.807481 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 114413.70 | 114413.70 | 1.0000 | 4.10878642 | 4.148576 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 2.50254749 | 60.00 | 48.89 | 11.11 | 0.000 | 114413.70 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00778635 | 21.00 | 0.00778635 | 41.4170 | 80074.46 | 0.00 | 114657.37 | 114657.37 | 4.10878642 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60965.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23690.293 | 23690.293 | 0.859431 | 0.00051823 | 920.410 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 1.3817 | 1.409545 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23690.29 | 23690.29 | 1.0000 | 0.85118787 | 0.859431 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.51817295 | 60.00 | 48.89 | 11.11 | 0.000 | 23690.29 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00782146 | 21.00 | 0.00782146 | 41.6014 | 16576.02 | 0.00 | 23740.75 | 23740.75 | 0.85118787 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60951.1 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15628.269 | 15628.269 | 0.566980 | 0.00034187 | 607.171 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 0.9115 | 0.929864 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15628.27 | 15628.27 | 1.0000 | 0.56154240 | 0.566980 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.34183395 | 60.00 | 48.89 | 11.11 | 0.000 | 15628.27 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00781985 | 21.00 | 0.00781985 | 41.5930 | 10934.90 | 0.00 | 15661.56 | 15661.56 | 0.56154240 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60950.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23503.082 | 23503.082 | 0.852628 | 0.00051413 | 913.144 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 1.3708 | 1.398406 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23503.08 | 23503.08 | 1.0000 | 0.84445084 | 0.852628 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.51407813 | 60.00 | 48.89 | 11.11 | 0.000 | 23503.08 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00782001 | 21.00 | 0.00782001 | 41.5938 | 16445.14 | 0.00 | 23553.14 | 23553.14 | 0.84445084 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60951.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15003.211 | 15003.211 | 0.544274 | 0.00032820 | 582.908 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 0.8751 | 0.892673 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15003.21 | 15003.21 | 1.0000 | 0.53905388 | 0.544274 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.32816218 | 60.00 | 48.89 | 11.11 | 0.000 | 15003.21 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00781201 | 21.00 | 0.00781201 | 41.5518 | 10497.87 | 0.00 | 15035.17 | 15035.17 | 0.53905388 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60951.6 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 167660.689 | -999.000 | 10.731341 | 0.00479507 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9182 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.731341 | 10.62841508 | 4197.9300 | 999.8980 | 57.76052311 | 15.00 | 6.67 | 8.33 | 2019813.69 | 8.3008 | 8.300800 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 167660.69 | 167660.69 | 1.0000 | 10.62841508 | 10.731341 | 26.17 | 13.91 | 0.00703528 | 44228.6 | 10.67 | 8.02 | 0.00703528 | 28453.9 | 4.79458532 | 6.67 | 15.00 | 8.33 | 23066.636 | 144594.05 | 35.10 | 0.00569938 | 15.77 | 2.03050000 | 18.9212 | 24.00 | 0.00735917 | 24.00 | 0.00735917 | 32.6444 | 117469.72 | 0.00 | 142086.67 | 142086.67 | 10.62841508 | 26.17 | 15.89 | 0.00703528 | 44228.6 | 13.03 | 10.69 | 0.00703528 | 30860.1 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 44583.023 | 44583.023 | 3.219402 | 0.00097525 | 963.356 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.731341 | 10.62841508 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 2.6003 | 2.652638 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 44583.02 | 44583.02 | 1.0000 | 3.18852453 | 3.219402 | -1.11 | -2.37 | 0.00331878 | 7173.1 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 0.97515539 | 60.00 | 48.89 | 11.11 | 0.000 | 44583.02 | -7.90 | 0.00234317 | -7.90 | 2.03050000 | 63.0707 | 10.47 | 0.00498501 | 21.36 | 0.00604998 | 31.5637 | 20948.84 | 0.00 | 41819.52 | 41819.52 | 3.18852453 | 2.80 | 0.98 | 0.00331878 | 11130.9 | 15.77 | 7.80 | 0.00331878 | 24246.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1585357.730 | -999.000 | 99.897006 | 0.04534103 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8976 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 99.897006 | 98.93888338 | 4197.9300 | 999.8980 | 57.76052311 | 15.00 | 6.67 | 8.33 | 2019813.69 | 78.4903 | 78.490295 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1585357.73 | 1585357.73 | 1.0000 | 98.93888338 | 99.897006 | 26.40 | 13.98 | 0.00702417 | 44437.9 | 10.66 | 8.00 | 0.00702417 | 28414.3 | 45.33640515 | 6.67 | 15.00 | 8.33 | 215872.110 | 1369485.62 | 35.10 | 0.00569938 | 15.77 | 20.30600000 | 20.3269 | 24.00 | 0.00738951 | 24.00 | 0.00738951 | 32.7773 | 1060526.02 | 0.00 | 1344652.36 | 1344652.36 | 98.93888338 | 26.40 | 15.96 | 0.00702417 | 44437.9 | 13.05 | 10.69 | 0.00702417 | 30847.1 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 355238.593 | 355238.593 | 29.969102 | 0.00777085 | 7874.937 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 99.897006 | 98.93888338 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 20.7193 | 21.136280 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 355238.59 | 355238.59 | 1.0000 | 29.68166501 | 29.969102 | 0.89 | -0.30 | 0.00405948 | 11053.1 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 7.77006139 | 60.00 | 48.89 | 11.11 | 0.000 | 355238.59 | -7.90 | 0.00234317 | -7.90 | 20.30600000 | 67.7565 | 19.36 | 0.00766611 | 19.37 | 0.00734781 | 43.2625 | 230178.25 | 0.00 | 344567.10 | 344567.10 | 29.68166501 | 2.80 | 2.03 | 0.00405948 | 12987.2 | 14.27 | 7.96 | 0.00405948 | 24595.9 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 173086.743 | -999.000 | 11.181400 | 0.00495026 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9079 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.181400 | 11.07415752 | 4197.9300 | 999.8980 | 57.76052311 | 15.00 | 6.67 | 8.33 | 2019813.69 | 8.5694 | 8.569441 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 173086.74 | 173086.74 | 1.0000 | 11.07415752 | 11.181400 | 26.02 | 13.86 | 0.00702972 | 44069.6 | 10.67 | 8.01 | 0.00702972 | 28439.9 | 4.94975397 | 6.67 | 15.00 | 8.33 | 24034.022 | 149052.72 | 35.10 | 0.00569938 | 15.77 | 2.03050000 | 18.1596 | 24.00 | 0.00732635 | 24.00 | 0.00732635 | 32.5004 | 125731.05 | 0.00 | 146449.64 | 146449.64 | 11.07415752 | 26.02 | 15.83 | 0.00702972 | 44069.6 | 13.03 | 10.69 | 0.00702972 | 30845.2 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 35098.376 | 35098.376 | 3.354420 | 0.00076778 | 788.619 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.181400 | 11.07415752 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 2.0471 | 2.088312 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 35098.38 | 35098.38 | 1.0000 | 3.32224726 | 3.354420 | 2.29 | 1.04 | 0.00445451 | 13456.9 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 0.76769963 | 60.00 | 48.89 | 11.11 | 0.000 | 35098.38 | -7.90 | 0.00234317 | -7.90 | 2.03050000 | 60.5321 | 17.91 | 0.00769267 | 17.62 | 0.00746442 | 49.0320 | 27789.00 | 0.00 | 34831.39 | 34831.39 | 3.32224726 | 2.80 | 2.57 | 0.00445451 | 13977.2 | 13.15 | 7.89 | 0.00445451 | 24461.5 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 93708.529 | -999.000 | 5.899562 | 0.00268005 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1159 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:VariableVolume | 5.899562 | 5.84297853 | 4197.9300 | 999.8980 | 57.76052311 | 15.00 | 6.67 | 8.33 | 2019813.69 | 4.6395 | 4.639464 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 93708.53 | 93708.53 | 1.0000 | 5.84297853 | 5.899562 | 26.40 | 14.08 | 0.00714159 | 44734.4 | 10.64 | 8.12 | 0.00714159 | 28696.6 | 2.67977866 | 6.67 | 15.00 | 8.33 | 12830.888 | 80877.64 | 34.43 | 0.00569833 | 15.56 | 1.20015641 | 20.3431 | 24.00 | 0.00757245 | 24.00 | 0.00757245 | 33.5795 | 58933.26 | 0.00 | 80387.00 | 80387.00 | 5.84297853 | 26.40 | 16.07 | 0.00714159 | 44734.4 | 12.88 | 10.74 | 0.00714159 | 30976.6 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.694125 | 0.00218750 | 3851.885 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:VariableVolume | 5.899562 | 5.84297853 | 4197.9300 | 999.8980 | 36.76172578 | 48.89 | 60.00 | 11.11 | 1714530.21 | 5.8325 | 5.949883 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.694125 | -1.61 | -4.13 | 0.00234317 | 4238.2 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 2.18727963 | 60.00 | 48.89 | 11.11 | 0.000 | 100000.00 | -7.90 | 0.00234317 | -7.90 | 1.20015641 | 32.4882 | 0.00 | 0.00234317 | 24.63 | 0.00234317 | 10.0874 | 0.00 | 0.00 | 99870.90 | 99870.90 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 39.96 | 14.57 | 0.00000000 | 40184.1 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 544662.224 | 288931.967 | 29.765551 | 0.01333874 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9029 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 464821.47 | 463449.55 | 0.8534 | -999.0 | -999.0 | 28.78 | 14.78 | 0.00702701 | 46865.9 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 464821.47 | 35.10 | 0.00569938 | 15.77 | 0.33839277 | -999.0000 | 27.00 | 0.00704229 | 27.00 | 0.00704229 | 26.1562 | 370059.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10310.221 | 5518.444 | 0.577987 | 0.00025250 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9445 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8757.46 | 8709.22 | 0.8494 | -999.0 | -999.0 | 28.24 | 14.62 | 0.00704939 | 46381.0 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8757.46 | 30.51 | 0.00569229 | 14.27 | 0.01563234 | -999.0000 | 27.00 | 0.00708712 | 27.00 | 0.00708712 | 26.3189 | 8271.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 98834.175 | 52886.490 | 5.537953 | 0.00242044 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9482 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 83956.86 | 83475.79 | 0.8495 | -999.0 | -999.0 | 28.25 | 14.63 | 0.00705139 | 46390.3 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83956.86 | 30.51 | 0.00569229 | 14.27 | 0.15632344 | -999.0000 | 27.00 | 0.00709089 | 27.00 | 0.00709089 | 26.3329 | 79226.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10092.114 | 5400.991 | 0.565621 | 0.00024716 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9464 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8572.60 | 8524.37 | 0.8494 | -999.0 | -999.0 | 28.25 | 14.62 | 0.00705044 | 46385.7 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8572.60 | 30.51 | 0.00569229 | 14.27 | 0.01563234 | -999.0000 | 27.00 | 0.00708904 | 27.00 | 0.00708904 | 26.3260 | 8095.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 544662.224 | 544662.224 | 29.765551 | 0.01333874 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 544662.22 | 544662.22 | 1.0000 | 29.48006638 | 29.765551 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 544662.22 | -7.90 | 0.00234317 | -7.90 | 0.33839277 | 1.1369 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10310.221 | 10310.221 | 0.577987 | 0.00025250 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10310.22 | 10310.22 | 1.0000 | 0.57244366 | 0.577987 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10310.22 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.7046 | 0.00 | 0.00700000 | 26.88 | 0.00700000 | 26.1740 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 98834.175 | 98834.175 | 5.537953 | 0.00242044 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 98834.18 | 98834.18 | 1.0000 | 5.48483776 | 5.537953 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 98834.18 | -7.90 | 0.00234317 | -7.90 | 0.15632344 | 2.8228 | 0.00 | 0.00468604 | 24.48 | 0.00468604 | 20.2773 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10092.114 | 10092.114 | 0.565621 | 0.00024716 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10092.11 | 10092.11 | 1.0000 | 0.56019607 | 0.565621 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10092.11 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.7637 | 0.00 | 0.00284683 | 23.35 | 0.00284683 | 13.2226 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16131.549 | 16131.549 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 29.765551 | 29.48006638 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 16131.55 | 16131.55 | 1.0000 | 29.48006638 | 29.765551 | -0.09 | -0.09 | 0.00694706 | 17282.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16131.55 | -7.90 | 0.00234317 | -7.90 | 0.33839277 | 1.1369 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.577987 | 0.57244366 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 745.21 | 745.21 | 1.0000 | 0.57244366 | 0.577987 | -0.21 | -0.21 | 0.00687405 | 16974.2 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.21 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.7046 | 0.00 | 0.00700000 | 26.88 | 0.00700000 | 26.1740 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7452.107 | 7452.107 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.537953 | 5.48483776 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 7452.11 | 7452.11 | 1.0000 | 5.48483776 | 5.537953 | -0.22 | -0.22 | 0.00461990 | 11328.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7452.11 | -7.90 | 0.00234317 | -7.90 | 0.15632344 | 2.8228 | 0.00 | 0.00468604 | 24.48 | 0.00468604 | 20.2773 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.565621 | 0.56019607 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 745.21 | 745.21 | 1.0000 | 0.56019607 | 0.565621 | -0.22 | -2.62 | 0.00283291 | 6864.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.21 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.7637 | 0.00 | 0.00284683 | 23.35 | 0.00284683 | 13.2226 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.73 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 99.90 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.18 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.90 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 29.77 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2887.00 | 2385.17 | 1302.50 |
CORE_BOTTOM | 2237.67 | 1378.00 | 156.33 |
CORE_MID | 1649.67 | 3237.00 | 294.00 |
CORE_TOP | 2038.17 | 3629.83 | 658.83 |
PERIMETER_BOT_ZN_3 | 2018.67 | 3210.50 | 224.17 |
PERIMETER_BOT_ZN_2 | 2633.33 | 2629.17 | 414.33 |
PERIMETER_BOT_ZN_1 | 3060.00 | 2099.17 | 442.50 |
PERIMETER_BOT_ZN_4 | 3188.67 | 1673.67 | 509.50 |
PERIMETER_MID_ZN_3 | 2596.83 | 3769.83 | 1121.33 |
PERIMETER_MID_ZN_2 | 2345.50 | 2642.67 | 715.00 |
PERIMETER_MID_ZN_1 | 2995.17 | 2480.83 | 715.33 |
PERIMETER_MID_ZN_4 | 2770.50 | 2926.00 | 721.00 |
PERIMETER_TOP_ZN_3 | 3272.17 | 3899.83 | 1865.00 |
PERIMETER_TOP_ZN_2 | 3174.83 | 3235.50 | 1280.33 |
PERIMETER_TOP_ZN_1 | 3157.17 | 2701.33 | 983.00 |
PERIMETER_TOP_ZN_4 | 3202.83 | 3208.17 | 1300.33 |
DATACENTER_BOT_ZN_6 | 5943.00 | 600.67 | 600.67 |
DATACENTER_MID_ZN_6 | 5883.00 | 94.17 | 94.17 |
DATACENTER_TOP_ZN_6 | 5340.00 | 293.33 | 206.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5819.50 | 5819.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5930.17 | 5858.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 2782.83 | 0.00 | 1718.67 |
CORE_BOTTOM | 0.00 | 25.17 | 0.00 | 8.17 |
CORE_MID | 0.00 | 0.33 | 0.00 | 0.17 |
CORE_TOP | 1.17 | 0.33 | 0.00 | 0.33 |
PERIMETER_BOT_ZN_3 | 0.00 | 75.50 | 0.00 | 56.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 130.67 | 0.00 | 111.67 |
PERIMETER_BOT_ZN_1 | 0.00 | 332.67 | 0.00 | 314.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 233.83 | 0.00 | 121.00 |
PERIMETER_MID_ZN_3 | 3.00 | 11.83 | 0.00 | 8.83 |
PERIMETER_MID_ZN_2 | 2.33 | 84.00 | 0.00 | 77.67 |
PERIMETER_MID_ZN_1 | 0.67 | 449.50 | 0.00 | 444.00 |
PERIMETER_MID_ZN_4 | 0.67 | 77.00 | 0.00 | 46.50 |
PERIMETER_TOP_ZN_3 | 35.67 | 27.33 | 3.17 | 20.67 |
PERIMETER_TOP_ZN_2 | 25.33 | 83.67 | 0.00 | 71.83 |
PERIMETER_TOP_ZN_1 | 17.00 | 239.33 | 0.00 | 228.83 |
PERIMETER_TOP_ZN_4 | 15.67 | 83.33 | 0.00 | 49.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 29.17 | 0.00 | 18.50 |
DATACENTER_MID_ZN_6 | 0.00 | 15.00 | 0.00 | 7.17 |
DATACENTER_TOP_ZN_6 | 0.00 | 16.83 | 0.00 | 7.83 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 42.17 | 0.00 | 38.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 38.33 | 3335.00 | 3.17 | 2244.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 1.036 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 1.029 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.728 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.706 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 1.000 | 0.019 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.752 | 0.020 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 1.704 | 0.019 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.144 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.780 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.539 | 0.050 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 1.584 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.416 | 0.047 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.804 | 0.056 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.680 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 1.624 | 0.056 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.460 | 0.058 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 33.192 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.01 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.48 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1027.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41108844.72 | 0.00 | 41108844.72 | 0.00 | 41108844.72 | 37848132.68 | 5361.88 | 497.16 | 2900.97 | 0.00 |
CORE_BOTTOM | 45300512.09 | 0.00 | 45300512.09 | 0.00 | 45300512.09 | 33990283.35 | 4365.87 | 28.26 | 4365.87 | 686.48 |
CORE_MID | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 0.34E+09 | 5304.04 | 212.59 | 3243.37 | 213.63 |
CORE_TOP | 29382396.67 | 0.00 | 29382396.67 | 0.00 | 29382396.67 | 33990283.35 | 5558.90 | 469.86 | 2731.24 | 296.08 |
PERIMETER_BOT_ZN_3 | 5510427.49 | 0.00 | 5510427.49 | 196195.19 | 5706622.68 | 4267819.30 | 4742.73 | 69.59 | 3947.68 | 686.48 |
PERIMETER_BOT_ZN_2 | 5989679.98 | 0.00 | 5989679.98 | 130796.71 | 6120476.69 | 2750345.05 | 4304.95 | 61.33 | 4393.72 | 686.48 |
PERIMETER_BOT_ZN_1 | 9058108.73 | 0.00 | 9058108.73 | 196195.19 | 9254303.92 | 4267912.63 | 3930.72 | 50.38 | 4778.90 | 686.48 |
PERIMETER_BOT_ZN_4 | 7438497.10 | 0.00 | 7438497.10 | 130796.71 | 7569293.81 | 2750345.05 | 3585.75 | 39.51 | 5134.75 | 686.48 |
PERIMETER_MID_ZN_3 | 40619425.42 | 0.00 | 40619425.42 | 460129.09 | 41079554.51 | 42678193.03 | 4992.03 | 339.09 | 3428.88 | 213.63 |
PERIMETER_MID_ZN_2 | 52381386.07 | 0.00 | 52381386.07 | 306752.52 | 52688138.58 | 27503450.52 | 4543.89 | 152.45 | 4063.66 | 977.10 |
PERIMETER_MID_ZN_1 | 81130761.17 | 0.00 | 81130761.17 | 460129.09 | 81590890.26 | 42679126.28 | 4059.53 | 298.51 | 4401.96 | 213.63 |
PERIMETER_MID_ZN_4 | 47233689.31 | 0.00 | 47233689.31 | 306752.52 | 47540441.82 | 27503450.52 | 4577.59 | 323.41 | 3859.00 | 213.63 |
PERIMETER_TOP_ZN_3 | 4193914.83 | 0.00 | 4193914.83 | 571294.83 | 4765209.65 | 4267819.30 | 4716.52 | 298.01 | 3745.47 | 296.08 |
PERIMETER_TOP_ZN_2 | 5543070.01 | 0.00 | 5543070.01 | 380862.96 | 5923932.97 | 2750345.05 | 4375.39 | 360.60 | 4024.01 | 296.08 |
PERIMETER_TOP_ZN_1 | 8323487.70 | 0.00 | 8323487.70 | 571294.83 | 8894782.53 | 4267912.63 | 3977.28 | 186.72 | 4595.99 | 296.08 |
PERIMETER_TOP_ZN_4 | 4882522.32 | 0.00 | 4882522.32 | 380862.96 | 5263385.28 | 2750345.05 | 4370.09 | 117.52 | 4272.39 | 296.08 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.54E+09 | 0.00 | 0.54E+09 | 0.00 | 0.54E+09 | 10671554.30 | 163.00 | 691.50 | 7905.50 | 2770.50 |
Total Facility | 0.60E+10 | 0.00 | 0.60E+10 | 17895931.45 | 0.60E+10 | 0.50E+10 | 7493.26 | 4377.52 | 8609.76 | 3534.96 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.9214 | 0.0000 | 1.9214 | 0.0000 | 1.9214 | 1.2002 | 2544.88 | 497.16 | 2900.97 |
CORE_BOTTOM | 1.9266 | 0.0000 | 1.9266 | 0.0000 | 1.9266 | 1.0778 | 2155.17 | 26.31 | 3761.52 |
CORE_MID | 13.6351 | 0.0000 | 13.6351 | 0.0000 | 13.6351 | 10.7782 | 2652.51 | 212.13 | 3078.36 |
CORE_TOP | 1.3226 | 0.0000 | 1.3226 | 0.0000 | 1.3226 | 1.0778 | 2898.17 | 469.86 | 2574.97 |
PERIMETER_BOT_ZN_3 | 0.2352 | 0.0000 | 0.2352 | 0.0046 | 0.2397 | 0.1353 | 2515.86 | 67.80 | 3359.34 |
PERIMETER_BOT_ZN_2 | 0.2655 | 0.0000 | 0.2655 | 0.0030 | 0.2686 | 0.0872 | 2077.58 | 59.75 | 3805.67 |
PERIMETER_BOT_ZN_1 | 0.4010 | 0.0000 | 0.4010 | 0.0046 | 0.4055 | 0.1353 | 1703.62 | 48.61 | 4190.77 |
PERIMETER_BOT_ZN_4 | 0.3248 | 0.0000 | 0.3248 | 0.0030 | 0.3279 | 0.0872 | 1368.71 | 37.19 | 4537.10 |
PERIMETER_MID_ZN_3 | 1.8364 | 0.0000 | 1.8364 | 0.0107 | 1.8471 | 1.3533 | 2342.56 | 338.17 | 3262.27 |
PERIMETER_MID_ZN_2 | 2.3326 | 0.0000 | 2.3326 | 0.0077 | 2.3403 | 0.8721 | 1618.93 | 150.60 | 3264.47 |
PERIMETER_MID_ZN_1 | 3.7279 | 0.0000 | 3.7279 | 0.0107 | 3.7386 | 1.3533 | 1408.19 | 297.72 | 4237.09 |
PERIMETER_MID_ZN_4 | 2.1462 | 0.0000 | 2.1462 | 0.0071 | 2.1533 | 0.8721 | 1926.51 | 322.71 | 3693.79 |
PERIMETER_TOP_ZN_3 | 0.1895 | 0.0000 | 0.1895 | 0.0133 | 0.2028 | 0.1353 | 2057.02 | 297.96 | 3588.02 |
PERIMETER_TOP_ZN_2 | 0.2546 | 0.0000 | 0.2546 | 0.0088 | 0.2635 | 0.0872 | 1718.07 | 360.47 | 3864.46 |
PERIMETER_TOP_ZN_1 | 0.3823 | 0.0000 | 0.3823 | 0.0133 | 0.3956 | 0.1353 | 1317.28 | 186.64 | 4439.08 |
PERIMETER_TOP_ZN_4 | 0.2213 | 0.0000 | 0.2213 | 0.0088 | 0.2302 | 0.0872 | 1711.25 | 117.47 | 4114.29 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 17.1703 | 0.0000 | 17.1703 | 0.0000 | 17.1703 | 0.3384 | 116.50 | 691.50 | 5135.00 |
Total Facility | 262.5613 | 0.0000 | 262.5613 | 0.4209 | 262.9822 | 158.4706 | 4676.26 | 4372.43 | 5838.28 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 71897997.13 | 0.00 | 71897997.13 | 48026705.38 | 3242.50 | 73.00 | 5444.50 | 686.48 |
VAV_MID WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.48E+09 | 3959.30 | 447.15 | 4353.55 | 213.63 |
VAV_TOP WITH REHEAT | 51326486.91 | 0.00 | 51326486.91 | 48026705.38 | 4112.26 | 507.83 | 4139.91 | 296.08 |
CAV_BAS | 40324080.12 | 0.00 | 40324080.12 | 37848132.68 | 5858.37 | 14.58 | 2887.05 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.53E+09 | 0.00 | 0.53E+09 | 10671554.30 | 854.50 | 0.00 | 7905.50 | 2770.50 |
AIRLOOP DATACENTER BOT | 239632.35 | 0.00 | 239632.35 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 2396323.53 | 0.00 | 2396323.53 | 4929815.99 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 239632.35 | 0.00 | 239632.35 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.0929 | 0.0000 | 3.0929 | 1.5229 | 1029.57 | 71.47 | 4841.96 |
VAV_MID WITH REHEAT | 23.2988 | 0.0000 | 23.2988 | 15.2292 | 1307.52 | 446.46 | 4189.02 |
VAV_TOP WITH REHEAT | 2.3251 | 0.0000 | 2.3251 | 1.5229 | 1451.53 | 507.83 | 3983.64 |
CAV_BAS | 1.8848 | 0.0000 | 1.8848 | 1.2002 | 3041.37 | 14.58 | 2887.05 |
AIRLOOP DATACENTER BASEMENT | 16.8425 | 0.0000 | 16.8425 | 0.3384 | 808.00 | 0.00 | 5135.00 |
AIRLOOP DATACENTER BOT | 0.0112 | 0.0000 | 0.0112 | 0.0156 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.1120 | 0.0000 | 0.1120 | 0.1563 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.0112 | 0.0000 | 0.0112 | 0.0156 | 5943.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 927.27 | 3475.11 | 0.00 | 0.00 | 0.00 | 1353.54 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 844.97 | 2769.66 | 0.00 | 0.00 | 0.00 | 1543.55 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 483.83 | 2727.85 | 0.00 | 0.00 | 0.00 | 2032.34 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 492.22 | 2905.74 | 0.00 | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 691.50 | 7905.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.0196 | 5.1191 | 0.0000 | 0.0000 | 0.0000 | 1.6463 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 19.8577 | 37.6224 | 0.0000 | 0.0000 | 0.0000 | 16.5305 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 1.9773 | 3.9377 | 0.0000 | 0.0000 | 0.0000 | 1.6163 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.1778 | 3.6535 | 0.0000 | 0.7622 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3322 | 19.4480 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1534 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1519 |
Defaulted Fields | 1189 |
Fields with Defaults | 3894 |
Autosized Fields | 335 |
Autosizable Fields | 413 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27024.26 | 295741.64 | 29-MAY-05:00 | 1923249.04 | 08-AUG-15:20 |
Electricity:Building | 16388.29 | 215366.33 | 07-MAY-17:10 | 948093.84 | 01-DEC-17:00 |
Electricity:Zone:BASEMENT | 540.44 | 14022.76 | 01-JAN-00:10 | 23631.68 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16388.29 | 215366.33 | 07-MAY-17:10 | 948093.84 | 01-DEC-17:00 |
InteriorLights:Electricity | 1711.90 | 8110.17 | 01-JAN-08:50 | 169722.15 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1711.90 | 8110.17 | 01-JAN-08:50 | 169722.15 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity | 1711.90 | 8110.17 | 01-JAN-08:50 | 169722.15 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1711.90 | 8110.17 | 01-JAN-08:50 | 169722.15 | 13-NOV-17:00 |
Electricity:Zone:CORE_BOTTOM | 393.83 | 4960.84 | 01-JAN-00:10 | 26343.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3938.24 | 49608.19 | 01-JAN-00:10 | 263436.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 393.82 | 4960.82 | 01-JAN-00:10 | 26343.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 43.82 | 589.50 | 26-MAR-17:10 | 3307.80 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.45 | 30.32 | 01-JAN-08:50 | 1147.25 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.45 | 30.32 | 01-JAN-08:50 | 1147.25 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.23 | 379.89 | 09-APR-17:10 | 2131.68 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.79 | 19.54 | 01-JAN-07:40 | 739.33 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.79 | 19.54 | 01-JAN-07:40 | 739.33 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.75 | 589.50 | 12-MAR-17:10 | 3307.86 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.38 | 30.33 | 01-JAN-07:40 | 1147.28 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.38 | 30.33 | 01-JAN-07:40 | 1147.28 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.19 | 379.89 | 12-MAR-17:10 | 2131.67 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.76 | 19.54 | 01-JAN-08:50 | 739.33 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.76 | 19.54 | 01-JAN-08:50 | 739.33 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 438.10 | 5894.96 | 12-MAR-17:10 | 33078.05 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 74.44 | 303.25 | 01-JAN-08:40 | 11472.53 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 74.44 | 303.25 | 01-JAN-08:40 | 11472.53 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 282.23 | 3798.93 | 26-MAR-17:10 | 21316.76 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 47.88 | 195.42 | 01-JAN-07:40 | 7393.34 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 47.88 | 195.42 | 01-JAN-07:40 | 7393.34 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 437.43 | 5895.05 | 12-MAR-17:10 | 33078.63 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 73.77 | 303.26 | 01-JAN-07:40 | 11472.78 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 73.77 | 303.26 | 01-JAN-07:40 | 11472.78 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 281.87 | 3798.91 | 12-MAR-17:10 | 21316.66 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 47.52 | 195.42 | 01-JAN-08:40 | 7393.34 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 47.52 | 195.42 | 01-JAN-08:40 | 7393.34 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 43.81 | 589.50 | 12-MAR-17:10 | 3307.80 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.44 | 30.32 | 01-JAN-08:40 | 1147.25 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.44 | 30.32 | 01-JAN-08:40 | 1147.25 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.22 | 379.89 | 26-MAR-17:10 | 2131.68 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.79 | 19.54 | 01-JAN-07:40 | 739.33 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.79 | 19.54 | 01-JAN-07:40 | 739.33 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.74 | 589.50 | 12-MAR-17:10 | 3307.86 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.38 | 30.33 | 01-JAN-07:40 | 1147.28 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.38 | 30.33 | 01-JAN-07:40 | 1147.28 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.19 | 379.89 | 12-MAR-17:10 | 2131.67 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.75 | 19.54 | 01-JAN-08:40 | 739.33 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.75 | 19.54 | 01-JAN-08:40 | 739.33 | 13-NOV-17:00 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7527.71 | 95067.50 | 01-JAN-00:10 | 382501.19 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1555.56 | 19567.35 | 01-JAN-00:10 | 79407.42 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2365.38 | 4272.26 | 22-JAN-05:50 | 429627.29 | 05-SEP-13:00 |
HeatRejection:Electricity | 623.52 | 108.76 | 21-JAN-07:20 | 73784.96 | 22-JUL-10:20 |
General:HeatRejection:Electricity | 623.52 | 108.76 | 21-JAN-07:20 | 73784.96 | 22-JUL-10:20 |
ElectricityProduced:Facility | 610.62 | -0.00 | 15-APR-18:30 | 89495.83 | 24-APR-11:10 |
ElectricityProduced:Plant | 610.62 | -0.00 | 15-APR-18:30 | 89495.83 | 24-APR-11:10 |
Photovoltaic:ElectricityProduced | 637.15 | 0.00 | 01-JAN-00:10 | 98401.39 | 09-JUN-12:30 |
PowerConversion:ElectricityProduced | -26.53 | -8905.56 | 09-JUN-12:30 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 6420.29 | 62475.37 | 25-MAY-05:00 | 497145.19 | 21-JUL-16:00 |
ExteriorEquipment:Electricity | 1641.46 | 10611.42 | 01-JAN-00:10 | 154952.78 | 02-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.35 | 979.82 | 01-JAN-00:10 | 3372.05 | 05-DEC-17:00 |
ElectricityPurchased:Facility | 26413.64 | 289031.46 | 24-SEP-09:00 | 1869585.45 | 08-AUG-15:20 |
ElectricityPurchased:Plant | 26413.64 | 289031.46 | 24-SEP-09:00 | 1869585.45 | 08-AUG-15:20 |
Cogeneration:ElectricityPurchased | 26413.64 | 289031.46 | 24-SEP-09:00 | 1869585.45 | 08-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 26413.64 | 289031.46 | 24-SEP-09:00 | 1869585.45 | 08-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 26413.64 | 289031.46 | 24-SEP-09:00 | 1869585.45 | 08-AUG-15:20 |
ElectricityNet:Plant | 26413.64 | 289031.46 | 24-SEP-09:00 | 1869585.45 | 08-AUG-15:20 |
Cogeneration:ElectricityNet | 26413.64 | 289031.46 | 24-SEP-09:00 | 1869585.45 | 08-AUG-15:20 |
General:Cogeneration:ElectricityNet | 26413.64 | 289031.46 | 24-SEP-09:00 | 1869585.45 | 08-AUG-15:20 |
Fans:Electricity | 2895.15 | 56368.98 | 02-JAN-23:20 | 321036.89 | 03-AUG-08:50 |
General:Fans:Electricity | 2895.15 | 56368.98 | 02-JAN-23:20 | 321036.89 | 03-AUG-08:50 |
ExteriorLights:Electricity | 263.19 | 0.00 | 01-JAN-07:20 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 263.19 | 0.00 | 01-JAN-07:20 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1582.20 | 9600.00 | 01-JAN-00:10 | 151268.49 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
Cooling:Electricity | 2191.50 | 2754.35 | 18-JAN-07:10 | 404994.86 | 16-AUG-15:10 |
General:Cooling:Electricity | 2191.50 | 2754.35 | 18-JAN-07:10 | 404994.86 | 16-AUG-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 2159.37 | 0.00 | 21-MAY-01:20 | 100000.00 | 01-JAN-10:50 |
General:Humidifier:Electricity | 2159.37 | 0.00 | 21-MAY-01:20 | 100000.00 | 01-JAN-10:50 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 415.15 | 0.00 | 01-JAN-00:10 | 52232.51 | 07-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 415.15 | 0.00 | 01-JAN-00:10 | 52232.51 | 07-FEB-12:40 |
Pumps:Electricity | 446.62 | 4105.76 | 01-JAN-00:10 | 45662.44 | 10-OCT-11:40 |
General:Pumps:Electricity | 446.62 | 4105.76 | 01-JAN-00:10 | 45662.44 | 10-OCT-11:40 |
WIRED_LTG_ELECTRICITY | 48.10 | 0.00 | 01-JAN-00:10 | 4769.19 | 13-NOV-17:10 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 635.87 | 0.00 | 01-JAN-00:10 | 728838.58 | 21-JAN-07:10 |
NaturalGas:Plant | 635.87 | 0.00 | 01-JAN-00:10 | 728838.58 | 21-JAN-07:10 |
Heating:NaturalGas | 635.87 | 0.00 | 01-JAN-00:10 | 728838.58 | 21-JAN-07:10 |
Boiler:Heating:NaturalGas | 635.87 | 0.00 | 01-JAN-00:10 | 728838.58 | 21-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 12598.51 | 8598.22 | 18-JAN-07:10 | 2396407.98 | 23-AUG-16:00 |
PlantLoopCoolingDemand:HVAC | 12598.51 | 8598.22 | 18-JAN-07:10 | 2396407.98 | 23-AUG-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 12598.51 | 8598.22 | 18-JAN-07:10 | 2396407.98 | 23-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9547.56 | 0.00 | 21-MAY-01:20 | 0.00 | 28-JUN-16:10 |
Water:HVAC | 803.29 | 0.00 | 21-MAY-01:20 | 0.00 | 01-JAN-11:10 |
Humidifier:Water | 803.29 | 0.00 | 21-MAY-01:20 | 0.00 | 01-JAN-11:10 |
General:Humidifier:Water | 803.29 | 0.00 | 21-MAY-01:20 | 0.00 | 01-JAN-11:10 |
MainsWater:Facility | 9547.56 | 0.00 | 21-MAY-01:20 | 0.00 | 28-JUN-16:10 |
MainsWater:HVAC | 803.29 | 0.00 | 21-MAY-01:20 | 0.00 | 01-JAN-11:10 |
Humidifier:MainsWater | 803.29 | 0.00 | 21-MAY-01:20 | 0.00 | 01-JAN-11:10 |
General:Humidifier:MainsWater | 803.29 | 0.00 | 21-MAY-01:20 | 0.00 | 01-JAN-11:10 |
Water:Plant | 8744.27 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 8744.27 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 6464.11 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:10 |
General:HeatRejection:Water | 6464.11 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:10 |
HeatRejection:MainsWater | 6464.11 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:10 |
General:HeatRejection:MainsWater | 6464.11 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 53677.06 | 100518.77 | 22-JAN-06:00 | 8790311.25 | 23-AUG-16:00 |
EnergyTransfer:Building | 19173.28 | 88917.09 | 22-JAN-05:20 | 1609412.34 | 16-AUG-15:00 |
EnergyTransfer:Zone:BASEMENT | 496.62 | 0.00 | 01-JAN-00:10 | 97568.21 | 02-JAN-07:10 |
Heating:EnergyTransfer | 141.22 | 0.00 | 01-JAN-16:50 | 343527.71 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 141.22 | 0.00 | 01-JAN-16:50 | 343527.71 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 19032.06 | 88184.94 | 22-JAN-06:00 | 1609412.34 | 16-AUG-15:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 496.62 | 0.00 | 01-JAN-00:10 | 97568.21 | 02-JAN-07:10 |
General:Cooling:EnergyTransfer | 19032.06 | 88184.94 | 22-JAN-06:00 | 1609412.34 | 16-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 496.62 | 0.00 | 01-JAN-00:10 | 97568.21 | 02-JAN-07:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 655.05 | 0.00 | 01-JAN-00:10 | 68062.50 | 06-JUL-08:40 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 655.05 | 0.00 | 01-JAN-00:10 | 68062.50 | 06-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 655.05 | 0.00 | 01-JAN-00:10 | 68062.50 | 06-JUL-08:40 |
EnergyTransfer:Zone:CORE_MID | 4201.38 | 0.00 | 01-JAN-00:10 | 423931.93 | 06-JUL-08:30 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4201.38 | 0.00 | 01-JAN-00:10 | 423931.93 | 06-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4201.38 | 0.00 | 01-JAN-00:10 | 423931.93 | 06-JUL-08:30 |
EnergyTransfer:Zone:CORE_TOP | 385.41 | 0.00 | 01-JAN-00:10 | 49785.21 | 28-JUN-13:50 |
Heating:EnergyTransfer:Zone:CORE_TOP | 2.84 | 0.00 | 01-JAN-00:10 | 46279.56 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 2.84 | 0.00 | 01-JAN-00:10 | 46279.56 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 382.57 | 0.00 | 01-JAN-00:10 | 49785.21 | 28-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 382.57 | 0.00 | 01-JAN-00:10 | 49785.21 | 28-JUN-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 81.86 | 0.00 | 01-JAN-00:10 | 13033.10 | 28-JUN-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 319.08 | 21-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 319.08 | 21-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 81.86 | 0.00 | 01-JAN-00:10 | 13033.10 | 28-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 81.86 | 0.00 | 01-JAN-00:10 | 13033.10 | 28-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 86.51 | 0.00 | 01-JAN-00:10 | 17396.90 | 03-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1037.60 | 21-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1037.60 | 21-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 86.51 | 0.00 | 01-JAN-00:10 | 17396.90 | 03-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 86.51 | 0.00 | 01-JAN-00:10 | 17396.90 | 03-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 143.80 | 0.00 | 01-JAN-00:10 | 19234.22 | 10-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 3137.70 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 3137.70 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 143.77 | 0.00 | 01-JAN-00:10 | 19234.22 | 10-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 143.77 | 0.00 | 01-JAN-00:10 | 19234.22 | 10-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 115.54 | 0.00 | 01-JAN-00:10 | 21427.35 | 21-JUL-17:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 115.54 | 0.00 | 01-JAN-00:10 | 21427.35 | 21-JUL-17:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 115.54 | 0.00 | 01-JAN-00:10 | 21427.35 | 21-JUL-17:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 577.26 | 0.00 | 01-JAN-00:10 | 103425.96 | 31-JUL-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 22.76 | 0.00 | 01-JAN-00:10 | 78208.58 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 22.76 | 0.00 | 01-JAN-00:10 | 78208.58 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 554.51 | 0.00 | 01-JAN-00:10 | 103425.96 | 31-JUL-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 554.51 | 0.00 | 01-JAN-00:10 | 103425.96 | 31-JUL-12:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 741.61 | 0.00 | 01-JAN-00:10 | 178675.44 | 06-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 9.08 | 0.00 | 01-JAN-00:10 | 53543.12 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 9.08 | 0.00 | 01-JAN-00:10 | 53543.12 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 732.53 | 0.00 | 01-JAN-00:10 | 178675.44 | 06-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 732.53 | 0.00 | 01-JAN-00:10 | 178675.44 | 06-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1284.83 | 0.00 | 01-JAN-00:10 | 208786.65 | 01-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 5.36 | 0.00 | 01-JAN-00:10 | 63165.90 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 5.36 | 0.00 | 01-JAN-00:10 | 63165.90 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1279.47 | 0.00 | 01-JAN-00:10 | 208786.65 | 01-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1279.47 | 0.00 | 01-JAN-00:10 | 208786.65 | 01-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 750.08 | 0.00 | 01-JAN-00:10 | 192178.79 | 27-JUN-16:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 5.47 | 0.00 | 01-JAN-00:10 | 49437.26 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 5.47 | 0.00 | 01-JAN-00:10 | 49437.26 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 744.61 | 0.00 | 01-JAN-00:10 | 192178.79 | 27-JUN-16:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 744.61 | 0.00 | 01-JAN-00:10 | 192178.79 | 27-JUN-16:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 64.45 | 0.00 | 01-JAN-00:10 | 13274.17 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 10.84 | 0.00 | 01-JAN-00:10 | 13274.17 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 10.84 | 0.00 | 01-JAN-00:10 | 13274.17 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 53.61 | 0.00 | 01-JAN-00:10 | 11583.05 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 53.61 | 0.00 | 01-JAN-00:10 | 11583.05 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 77.14 | 0.00 | 01-JAN-00:10 | 17723.93 | 19-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.44 | 0.00 | 01-JAN-00:10 | 11167.85 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.44 | 0.00 | 01-JAN-00:10 | 11167.85 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 72.70 | 0.00 | 01-JAN-00:10 | 17723.93 | 19-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 72.70 | 0.00 | 01-JAN-00:10 | 17723.93 | 19-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 125.22 | 0.00 | 01-JAN-00:10 | 21545.50 | 01-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.33 | 0.00 | 01-JAN-00:10 | 14981.71 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.33 | 0.00 | 01-JAN-00:10 | 14981.71 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 120.89 | 0.00 | 01-JAN-00:10 | 21545.50 | 01-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 120.89 | 0.00 | 01-JAN-00:10 | 21545.50 | 01-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 75.97 | 0.00 | 01-JAN-00:10 | 20818.53 | 27-JUN-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.35 | 0.00 | 01-JAN-00:10 | 9582.08 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.35 | 0.00 | 01-JAN-00:10 | 9582.08 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 72.62 | 0.00 | 01-JAN-00:10 | 20818.53 | 27-JUN-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 72.62 | 0.00 | 01-JAN-00:10 | 20818.53 | 27-JUN-16:40 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 74.75 | 0.00 | 01-JAN-00:10 | 15080.18 | 24-JUL-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.94 | 0.00 | 01-JAN-00:10 | 3684.86 | 24-DEC-14:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.94 | 0.00 | 01-JAN-00:10 | 3684.86 | 24-DEC-14:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 72.81 | 0.00 | 01-JAN-00:10 | 15080.18 | 24-JUL-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 72.81 | 0.00 | 01-JAN-00:10 | 15080.18 | 24-JUL-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 440.85 | 0.00 | 01-JAN-00:10 | 79281.01 | 05-JUL-14:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 50.31 | 0.00 | 01-JAN-00:10 | 48786.67 | 24-DEC-12:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 50.31 | 0.00 | 01-JAN-00:10 | 48786.67 | 24-DEC-12:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 390.54 | 0.00 | 01-JAN-00:10 | 79281.01 | 05-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 390.54 | 0.00 | 01-JAN-00:10 | 79281.01 | 05-JUL-14:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 96.19 | 0.00 | 01-JAN-00:10 | 22108.68 | 28-JUN-14:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 19.79 | 0.00 | 01-JAN-00:10 | 17622.37 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 19.79 | 0.00 | 01-JAN-00:10 | 17622.37 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 76.40 | 0.00 | 01-JAN-00:10 | 22108.68 | 28-JUN-14:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 76.40 | 0.00 | 01-JAN-00:10 | 22108.68 | 28-JUN-14:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.03 | 845.18 | 21-JAN-08:00 | 8410.50 | 16-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.03 | 845.18 | 21-JAN-08:00 | 8410.50 | 16-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.03 | 845.18 | 21-JAN-08:00 | 8410.50 | 16-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1259.97 | 6.49 | 18-JAN-02:30 | 80185.55 | 16-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.04 | 0.00 | 01-JAN-00:10 | 1607.45 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.04 | 0.00 | 01-JAN-00:10 | 1607.45 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1259.94 | 0.00 | 17-JAN-01:00 | 80185.55 | 16-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1259.94 | 0.00 | 17-JAN-01:00 | 80185.55 | 16-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 118.40 | 5.06 | 01-JAN-19:10 | 8157.19 | 16-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.63 | 0.00 | 01-JAN-15:10 | 676.37 | 16-JAN-18:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.63 | 0.00 | 01-JAN-15:10 | 676.37 | 16-JAN-18:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 117.76 | 0.00 | 01-JAN-00:10 | 8157.19 | 16-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 117.76 | 0.00 | 01-JAN-00:10 | 8157.19 | 16-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7179.34 | 87293.94 | 22-JAN-09:00 | 370219.13 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7179.34 | 87293.94 | 22-JAN-09:00 | 370219.13 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7179.34 | 87293.94 | 22-JAN-09:00 | 370219.13 | 21-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 999.59 | 0.00 | 01-JAN-00:10 | 606696.64 | 06-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 409.97 | 0.00 | 01-JAN-00:10 | 51585.45 | 06-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 409.97 | 0.00 | 01-JAN-00:10 | 51585.45 | 06-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 409.97 | 0.00 | 01-JAN-00:10 | 51585.45 | 06-FEB-12:30 |
EnergyTransfer:HVAC | 11876.70 | 10579.32 | 17-JAN-04:20 | 2232440.01 | 23-AUG-16:00 |
HeatingCoils:EnergyTransfer | 589.61 | 0.00 | 01-JAN-00:10 | 589501.49 | 06-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 589.61 | 0.00 | 01-JAN-00:10 | 589501.49 | 06-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 589.61 | 0.00 | 01-JAN-00:10 | 589501.49 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 11287.09 | 5843.87 | 18-JAN-07:10 | 2232440.01 | 23-AUG-16:00 |
EnergyTransfer:Plant | 22627.07 | 0.00 | 01-JAN-00:10 | 5669166.28 | 05-SEP-13:00 |
LoopToLoop:EnergyTransfer | 6909.33 | 0.00 | 01-JAN-00:10 | 1786934.67 | 05-SEP-13:00 |
WaterSystems:EnergyTransfer | 409.97 | 0.00 | 01-JAN-00:10 | 51585.45 | 06-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 409.97 | 0.00 | 01-JAN-00:10 | 51585.45 | 06-FEB-12:30 |
Boilers:EnergyTransfer | 588.61 | 0.00 | 01-JAN-00:10 | 655078.73 | 21-JAN-07:10 |
Chillers:EnergyTransfer | 6919.54 | 0.00 | 01-JAN-00:10 | 1784852.65 | 05-SEP-13:00 |
HeatRejection:EnergyTransfer | 7799.62 | 0.00 | 01-JAN-00:10 | 2060073.55 | 05-SEP-13:00 |
General:HeatRejection:EnergyTransfer | 7799.62 | 0.00 | 01-JAN-00:10 | 2060073.55 | 05-SEP-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -496.595 | 0.000 | 0.000 | 84.807 | 116.039 | 424.397 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -128.649 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -655.048 | 0.000 | 0.000 | 83.332 | 104.212 | 289.614 | 0.000 | 0.000 | 0.000 | 177.890 | 0.000 | 0.000 | 0.000 | 0.000 | -0.008 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4201.366 | 0.000 | 0.000 | 837.422 | 1042.115 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -574.299 |
CORE_TOP | 0.000 | 0.000 | 2.839 | -382.568 | 0.000 | 0.000 | 85.894 | 104.212 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -99.989 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.001 | -81.863 | 0.000 | 0.000 | 10.622 | 7.453 | 36.365 | 37.900 | 0.000 | 0.079 | 49.934 | 0.000 | -58.266 | 0.000 | -2.226 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.005 | -86.509 | 0.000 | 0.000 | 6.786 | 4.792 | 23.435 | 91.837 | 0.000 | 0.052 | 0.002 | 0.000 | -36.084 | 0.000 | -1.501 | -2.813 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.029 | -143.773 | 0.000 | 0.000 | 10.457 | 7.382 | 36.366 | 164.659 | 0.000 | 0.078 | 0.001 | 0.000 | -54.684 | 0.000 | -2.295 | -18.219 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -115.540 | 0.000 | 0.000 | 6.746 | 4.755 | 23.435 | 83.822 | 0.000 | 0.050 | 40.410 | 0.000 | -42.028 | 0.000 | -1.651 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 22.758 | -554.497 | 0.000 | 0.000 | 110.418 | 74.444 | 363.654 | 394.176 | 0.000 | 1.900 | 165.571 | 0.000 | -531.185 | 0.000 | -47.239 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 9.085 | -732.529 | 0.000 | 0.000 | 50.425 | 47.880 | 234.352 | 916.775 | 0.000 | 1.190 | 0.069 | 0.000 | -343.811 | 0.000 | -33.499 | -149.869 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 5.360 | -1279.447 | 0.000 | 0.000 | 104.707 | 73.770 | 363.660 | 1640.813 | 0.000 | 1.830 | 0.020 | 0.000 | -533.695 | 0.000 | -52.348 | -324.649 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 5.467 | -744.584 | 0.000 | 0.000 | 69.510 | 47.518 | 234.351 | 848.474 | 0.000 | 1.163 | 0.001 | 0.000 | -375.868 | 0.000 | -34.572 | -51.458 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 10.839 | -53.609 | 0.000 | 0.000 | 11.221 | 7.444 | 36.365 | 39.841 | 0.000 | 0.222 | 3.166 | 0.000 | -49.985 | 0.000 | -5.505 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.443 | -72.695 | 0.000 | 0.000 | 6.961 | 4.788 | 23.435 | 92.183 | 0.000 | 0.144 | 0.001 | 0.000 | -32.460 | 0.000 | -3.915 | -22.883 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 4.332 | -120.884 | 0.000 | 0.000 | 10.654 | 7.377 | 36.366 | 164.595 | 0.000 | 0.218 | 0.002 | 0.000 | -50.683 | 0.000 | -6.162 | -45.813 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 3.353 | -72.613 | 0.000 | 0.000 | 7.052 | 4.752 | 23.435 | 84.948 | 0.000 | 0.139 | 0.000 | 0.000 | -35.774 | 0.000 | -4.083 | -11.208 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -141.031 | 0.000 | 0.000 | 0.950 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -15.475 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.038 | -1259.934 | 0.000 | 0.000 | 9.500 | 16.758 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -305.167 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.633 | -117.764 | 0.000 | 0.000 | 0.951 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -39.377 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7179.348 | 0.000 | 0.000 | 20.537 | 32.854 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -368.900 |
GROUNDFLOOR_PLENUM | 1.938 | -72.812 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.144 | 75.511 | 0.000 | 0.000 | 0.000 | -4.781 | 0.000 |
MIDFLOOR_PLENUM | 50.313 | -390.538 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.813 | 419.607 | 0.000 | 0.000 | 0.000 | -82.196 | -0.002 |
TOPFLOOR_PLENUM | 19.792 | -76.399 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.231 | 65.101 | 0.000 | 0.000 | 0.000 | -8.725 | -0.006 |
Total Facility | 72.043 | -539.749 | 69.183 | -18492.198 | 0.000 | 0.000 | 1528.951 | 1711.896 | 14676.396 | 4560.022 | 0.000 | 10.255 | 997.290 | 0.000 | -2144.524 | 0.000 | -290.699 | -2158.784 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 19-JUN-06:11 | 0.00 | 0.00 | 0.00 | -112755.44 | 0.00 | 0.00 | 1246.73 | 3391.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 94659.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 08-JUL-04:13 | 0.00 | 0.00 | 0.00 | -89706.51 | 0.00 | 0.00 | 0.00 | 507.60 | 4453.23 | 0.00 | 0.00 | 0.00 | 84745.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 01-AUG-05:03 | 0.00 | 0.00 | 0.00 | -751687.37 | 0.00 | 0.00 | 8681.14 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 661159.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-04:13 | 0.00 | 0.00 | 0.00 | -82651.04 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 76176.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 25-JUN-17:42 | 0.00 | 0.00 | 0.00 | -18369.20 | 0.00 | 0.00 | 0.00 | 30.32 | 559.17 | 6438.45 | 0.00 | 81.88 | 11259.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-08:22 | 0.00 | 0.00 | 0.00 | -26488.02 | 0.00 | 0.00 | 14.66 | 19.54 | 464.11 | 20932.42 | 0.00 | 0.00 | 5065.76 | 0.00 | -0.00 | 0.00 | -8.48 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-14:41 | 0.00 | 0.00 | 0.00 | -24196.31 | 0.00 | 0.00 | 29.97 | 30.33 | 720.19 | 17810.59 | 0.00 | 0.00 | 5609.95 | 0.00 | -0.00 | 0.00 | -4.72 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JUL-15:41 | 0.00 | 0.00 | 0.00 | -33056.80 | 0.00 | 0.00 | 12.13 | 19.54 | 464.11 | 21880.92 | 0.00 | 18.12 | 10661.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 18-JUN-18:12 | 0.00 | 0.00 | 0.00 | -158070.03 | 0.00 | 0.00 | 0.00 | 303.25 | 5591.71 | 77862.20 | 0.00 | 1596.77 | 72716.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18-JUN-08:51 | 0.00 | 0.00 | 0.00 | -277001.69 | 0.00 | 0.00 | 150.54 | 195.42 | 4641.14 | 193110.54 | 0.00 | 0.00 | 80518.90 | 0.00 | -0.00 | 0.00 | -1614.86 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-12:11 | 0.00 | 0.00 | 0.00 | -255229.72 | 0.00 | 0.00 | 238.87 | 303.26 | 7201.95 | 287208.12 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -444.19 | -39278.29 |
PERIMETER_MID_ZN_4 | 18-JUN-16:51 | 0.00 | 0.00 | 0.00 | -303755.35 | 0.00 | 0.00 | 112.78 | 195.42 | 4641.11 | 226005.10 | 0.00 | 159.21 | 72641.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-JUL-16:51 | 0.00 | 0.00 | 0.00 | -17874.63 | 0.00 | 0.00 | 37.53 | 30.32 | 720.18 | 5842.67 | 0.00 | 554.54 | 10689.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 09-JUL-08:11 | 0.00 | 0.00 | 0.00 | -26901.59 | 0.00 | 0.00 | 17.83 | 19.54 | 464.11 | 19611.14 | 0.00 | 0.00 | 6966.87 | 0.00 | -0.00 | 0.00 | -177.91 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-13:11 | 0.00 | 0.00 | 0.00 | -27495.16 | 0.00 | 0.00 | 26.08 | 30.33 | 720.19 | 26373.99 | 0.00 | 0.00 | 471.49 | 0.00 | -0.00 | 0.00 | -126.92 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:41 | 0.00 | 0.00 | 0.00 | -32268.97 | 0.00 | 0.00 | 11.42 | 19.54 | 464.11 | 22728.91 | 0.00 | 0.00 | 9096.04 | 0.00 | -0.00 | 0.00 | -51.05 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-18:20 | 0.00 | 0.00 | 0.00 | -8414.63 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 612.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 16-APR-18:10 | 0.00 | 0.00 | 0.00 | -80218.04 | 0.00 | 0.00 | 0.00 | 81.29 | 77944.22 | 0.00 | 0.00 | 0.00 | 2192.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 16-APR-18:00 | 0.00 | 0.00 | 0.00 | -8160.03 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 357.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 13-AUG-13:42 | 0.00 | 0.00 | 0.00 | -376740.39 | 0.00 | 0.00 | 114.64 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3166.14 |
GROUNDFLOOR_PLENUM | 24-JUL-05:20 | 0.00 | -17369.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17378.21 | 0.00 | -0.00 | 0.00 | -8.59 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-05:13 | 0.00 | -94169.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94312.02 | 0.00 | -0.00 | 0.00 | -143.02 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-13:48 | 0.00 | -24506.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 24410.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-AUG-04:12 | 0.00 | 43201.60 | 0.00 | -1854734.03 | 0.00 | 0.00 | 0.00 | 10223.35 | 587299.42 | 0.00 | 0.00 | 0.00 | 1257231.94 | 0.00 | -42245.26 | 0.00 | -977.03 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JAN-05:01 | 0.00 | 0.00 | 66100.91 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -73053.73 |
PERIMETER_BOT_ZN_3 | 21-JAN-06:01 | 0.00 | 0.00 | 2124.97 | 0.00 | 0.00 | 0.00 | 140.24 | 127.47 | 960.25 | 0.00 | 0.00 | 0.00 | 2337.98 | 0.00 | -5690.90 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 21-JAN-06:01 | 0.00 | 0.00 | 5417.42 | 0.00 | 0.00 | 0.00 | 91.75 | 82.15 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3754.98 | 0.00 | 0.00 | -2455.16 |
PERIMETER_BOT_ZN_1 | 06-FEB-06:01 | 0.00 | 0.00 | 9960.67 | 0.00 | 0.00 | 0.00 | 145.35 | 67.47 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5325.00 | 0.00 | -102.65 | -5706.11 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-FEB-04:01 | 0.00 | 0.00 | 121459.40 | 0.00 | 0.00 | 0.00 | 0.00 | 637.34 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -49476.59 | 0.00 | -9576.02 | -70499.74 |
PERIMETER_MID_ZN_2 | 17-JAN-05:01 | 0.00 | 0.00 | 136814.03 | 0.00 | 0.00 | 0.00 | 0.00 | 821.46 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30793.44 | 0.00 | -7772.01 | -103874.72 |
PERIMETER_MID_ZN_1 | 17-JAN-05:01 | 0.00 | 0.00 | 150552.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46182.46 | 0.00 | -11778.24 | -101321.86 |
PERIMETER_MID_ZN_4 | 17-JAN-05:01 | 0.00 | 0.00 | 132981.23 | 0.00 | 0.00 | 0.00 | 0.00 | 821.46 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30502.51 | 0.00 | -7849.02 | -100255.80 |
PERIMETER_TOP_ZN_3 | 06-FEB-04:01 | 0.00 | 0.00 | 15384.46 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4313.83 | 0.00 | -1073.63 | -10806.30 |
PERIMETER_TOP_ZN_2 | 06-FEB-04:01 | 0.00 | 0.00 | 17842.75 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2903.75 | 0.00 | -735.67 | -14724.87 |
PERIMETER_TOP_ZN_1 | 06-FEB-04:01 | 0.00 | 0.00 | 18909.73 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4390.94 | 0.00 | -1102.06 | -14226.03 |
PERIMETER_TOP_ZN_4 | 06-FEB-04:01 | 0.00 | 0.00 | 18198.23 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3026.51 | 0.00 | -753.61 | -14939.64 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 17-JAN-05:17 | 0.00 | 0.00 | 1607.45 | 0.00 | 0.00 | 0.00 | 0.00 | 162.57 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21256.07 |
DATACENTER_TOP_ZN_6 | 16-JAN-18:10 | 0.00 | 0.00 | 676.37 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2633.11 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 31-DEC-15:11 | 12137.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12137.95 |
MIDFLOOR_PLENUM | 30-JUL-15:51 | 129329.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2565.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -131895.39 |
TOPFLOOR_PLENUM | 06-FEB-06:13 | 22640.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -384.07 | -22256.18 |
Total Facility | 17-JAN-05:01 | -351445.50 | 286969.49 | 673639.04 | -286969.49 | 0.00 | 0.00 | 0.00 | 18857.47 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -184219.89 | 0.00 | -68737.52 | -320518.83 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.3256 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.7313 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 117.4470 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 99.8970 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.2391 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.1814 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.8996 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.8996 | 0.2034 | 1.0000 | Not calculated | 1.2002 | 0.2034 | ||
AIRLOOP DATACENTER BASEMENT | 29.7652 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 29.7656 | 0.0114 | 1.0000 | Not calculated | 0.3384 | 0.0114 | ||
AIRLOOP DATACENTER BOT | 0.5780 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5780 | 0.0270 | 1.0000 | Not calculated | 0.0156 | 0.0270 | ||
AIRLOOP DATACENTER MID | 5.5380 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.5380 | 0.0282 | 1.0000 | Not calculated | 0.1563 | 0.0282 | ||
AIRLOOP DATACENTER TOP | 0.5656 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5656 | 0.0276 | 1.0000 | Not calculated | 0.0156 | 0.0276 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.1628 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2862 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 58.7235 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8501 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.1196 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2844 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 29.7652 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 29.7652 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0114 | ||
AIRLOOP DATACENTER BOT | 0.5780 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5780 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0270 | ||
AIRLOOP DATACENTER MID | 5.5380 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.5380 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0282 | ||
AIRLOOP DATACENTER TOP | 0.5656 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5656 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0276 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.8996 | 5.8996 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3755 | 6.3755 | 1.6194 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 59.7222 | 59.7222 | 16.1847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0261 | 6.0261 | 1.6150 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1519 | 1.1519 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4784 | 1.4784 | 0.1301 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4669 | 1.4669 | 0.2024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8531 | 1.8531 | 0.1316 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.8320 | 10.8320 | 2.0256 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.7879 | 15.7879 | 1.3104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.1569 | 14.1569 | 2.0244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.9480 | 16.9480 | 1.3050 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2467 | 1.2467 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5960 | 1.5960 | 0.1309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5665 | 1.5665 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8038 | 1.8038 | 0.1317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5780 | 0.5780 | 0.5780 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5380 | 5.5380 | 5.5380 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5656 | 0.5656 | 0.5656 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 29.7652 | 29.7652 | 29.7652 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.3256 | 10.7313 | 12.3256 | 2.2862 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 117.4470 | 99.8970 | 117.4470 | 22.8501 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.2391 | 11.1814 | 12.2391 | 2.2844 | 0.0000 | 1.0000 |
CAV_BAS | 5.8996 | 5.8996 | 5.8996 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 29.7652 | 29.7656 | 29.7652 | 29.7652 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5780 | 0.5780 | 0.5780 | 0.5780 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.5380 | 5.5380 | 5.5380 | 5.5380 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5656 | 0.5656 | 0.5656 | 0.5656 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1877 | 3.1877 | 1.6194 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 29.8611 | 29.8611 | 16.1847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0130 | 3.0130 | 1.6150 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5759 | 0.5759 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7392 | 0.7392 | 0.1301 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7334 | 0.7334 | 0.2024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9265 | 0.9265 | 0.1316 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4160 | 5.4160 | 2.0256 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.8940 | 7.8940 | 1.3104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0784 | 7.0784 | 2.0244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.4740 | 8.4740 | 1.3050 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6234 | 0.6234 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7980 | 0.7980 | 0.1309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7833 | 0.7833 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9019 | 0.9019 | 0.1317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5780 | 0.5780 | 0.5780 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5380 | 5.5380 | 5.5380 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5656 | 0.5656 | 0.5656 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 29.7652 | 29.7652 | 29.7652 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.1628 | 2.2862 | 2.2862 | 2.2862 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 58.7235 | 22.8501 | 22.8501 | 22.8501 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.1196 | 2.2844 | 2.2844 | 2.2844 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 29.7652 | 29.7652 | 29.7652 | 29.7652 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5780 | 0.5780 | 0.5780 | 0.5780 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.5380 | 5.5380 | 5.5380 | 5.5380 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5656 | 0.5656 | 0.5656 | 0.5656 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 3.17 |
Number of hours cooling loads not met | 2244.33 |
Number of hours not met | 2244.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 635.87 | 728838.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2191.50 | 404994.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1711.90 | 169722.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 263.19 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.35 | 3372.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1582.20 | 151268.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2895.15 | 321036.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 446.62 | 45662.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 623.52 | 73784.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 2159.37 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 415.15 | 52232.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 27024.26 |
Natural Gas | 0.00 | 635.87 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 27660.13 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 637.15 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 36.96 |
Space Heating | 0.00 |
Space Cooling | 47.31 |
Fans (All) | 62.50 |
Service Water Heating | 8.96 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 583.42 |
Subtotal | 583.42 |
Natural Gas [MJ/m2] | |
Space Heating | 13.73 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 13.73 |
Subtotal | 13.73 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.19 |
Space Heating | 2.30 |
Space Cooling | 7.92 |
Fans (All) | 10.47 |
Service Water Heating | 1.50 |
Receptacle Equipment | 53.06 |
Miscellaneous | 18.56 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2069. | 8760. |
LTG_SCH_DATACENTER | 1840. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 649. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 6683.83 | 865.33 | 208.00 | 1002.83 | 0.00 |
CORE_BOTTOM | 8736.17 | 23.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8695.67 | 64.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8635.17 | 124.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8653.67 | 106.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8460.00 | 300.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8648.00 | 112.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8670.83 | 89.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8644.67 | 115.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8724.17 | 35.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8644.50 | 115.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8677.83 | 82.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8641.00 | 119.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8739.00 | 21.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8222.83 | 537.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8718.50 | 41.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8593.33 | 166.67 | 0.00 | 0.00 | 0.00 |
Min | 6683.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 865.33 | 208.00 | 1002.83 | 0.00 |
Average | 8578.57 | 128.78 | 9.04 | 43.60 | 0.00 |
Sum | 197307.17 | 2962.00 | 208.00 | 1002.83 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 293225.50 | 23303.33 | 9263.50 | 42823.67 | 0.00 |
CORE_BOTTOM | 330780.00 | 33.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24902.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38917.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38922.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38922.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2266.50 | 1.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2267.83 | 0.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 97932.67 | 5462.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330813.00 | 23303.33 | 9263.50 | 42823.67 | 0.00 |
Average | 76817.20 | 1253.06 | 402.76 | 1861.90 | 0.00 |
Sum | 1766795.50 | 28820.33 | 9263.50 | 42823.67 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 6744.17 | 816.00 | 183.50 | 1016.33 | 0.00 |
CORE_BOTTOM | 8559.67 | 200.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8657.17 | 102.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8657.83 | 102.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8593.83 | 166.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8567.17 | 192.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8575.83 | 184.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8389.33 | 370.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8663.67 | 96.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8587.00 | 173.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8632.50 | 127.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8545.17 | 214.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8650.17 | 109.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8582.50 | 177.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8621.17 | 138.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8554.50 | 205.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8371.17 | 388.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8549.83 | 210.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8667.00 | 93.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8492.00 | 268.00 | 0.00 | 0.00 | 0.00 |
Min | 6744.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 816.00 | 183.50 | 1016.33 | 0.00 |
Average | 8519.12 | 188.72 | 7.98 | 44.19 | 0.00 |
Sum | 195939.67 | 4340.50 | 183.50 | 1016.33 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 293844.67 | 24111.83 | 6390.50 | 44269.00 | 0.00 |
CORE_BOTTOM | 330366.00 | 447.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330708.00 | 105.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330670.00 | 143.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24905.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38922.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38922.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38922.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 99911.17 | 3483.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330708.00 | 24111.83 | 6390.50 | 44269.00 | 0.00 |
Average | 76901.80 | 1230.52 | 277.85 | 1924.74 | 0.00 |
Sum | 1768741.50 | 28302.00 | 6390.50 | 44269.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:30
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448996E+11 | 107684.55 | 02-JAN-07:03 | -3.1 | -4.4 | 0.569247E+10 | 7781.23 | 02-JAN-10:09 | 4.97 | 0.87 |
February | 0.401344E+11 | 93979.27 | 21-FEB-07:05 | 3.98 | 1.48 | 0.515493E+10 | 7499.26 | 15-FEB-10:09 | 3.98 | 1.48 |
March | 0.487047E+11 | 96180.06 | 20-MAR-06:11 | 7.97 | 4.12 | 0.615348E+10 | 7499.24 | 28-MAR-13:20 | 16.13 | 7.51 |
April | 0.473120E+11 | 97796.78 | 17-APR-06:11 | 8.50 | 2.58 | 0.547041E+10 | 7499.31 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.436902E+11 | 100069.42 | 20-MAY-06:11 | 13.87 | 4.40 | 0.628260E+10 | 10855.95 | 22-MAY-13:00 | 29.40 | 13.32 |
June | 0.256411E+11 | 112899.24 | 19-JUN-06:11 | 14.97 | 6.13 | 0.766283E+10 | 12456.43 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.122184E+11 | 103809.28 | 28-JUL-06:11 | 18.67 | 14.43 | 0.844424E+10 | 12630.07 | 26-JUL-13:00 | 18.67 | 14.43 |
August | 0.346109E+11 | 105271.90 | 16-AUG-06:11 | 18.87 | 13.50 | 0.809025E+10 | 12727.04 | 22-AUG-13:00 | 32.20 | 16.94 |
September | 0.466489E+11 | 101930.15 | 25-SEP-06:11 | 12.40 | 9.94 | 0.595273E+10 | 10502.28 | 12-SEP-13:00 | 12.40 | 9.94 |
October | 0.524480E+11 | 104614.18 | 10-OCT-06:11 | 13.90 | 11.14 | 0.584539E+10 | 10904.24 | 11-OCT-13:00 | 26.70 | 14.80 |
November | 0.517179E+11 | 96332.61 | 13-NOV-07:05 | 0.97 | -1.1 | 0.563839E+10 | 7499.16 | 30-NOV-14:20 | 12.07 | 4.47 |
December | 0.485950E+11 | 94960.29 | 26-DEC-07:05 | -1.8 | -2.5 | 0.549230E+10 | 7499.14 | 20-DEC-10:20 | -1.8 | -2.5 |
Annual Sum or Average | 0.496621E+12 | 0.758800E+11 | ||||||||
Minimum of Months | 0.122184E+11 | 93979.27 | -3.1 | -4.4 | 0.515493E+10 | 7499.14 | -1.8 | -2.5 | ||
Maximum of Months | 0.524480E+11 | 112899.24 | 18.87 | 14.43 | 0.844424E+10 | 12727.04 | 32.20 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375771E+11 | 80140.89 | 02-JAN-05:01 | -2.6 | -4.0 | 0.507115E+10 | 6734.77 | 06-JAN-10:00 | 2.20 | -1.4 |
February | 0.364666E+11 | 83631.91 | 21-FEB-05:11 | 2.57 | 0.44 | 0.460339E+10 | 6734.79 | 22-FEB-10:39 | 2.03 | 0.93 |
March | 0.494419E+11 | 81326.53 | 27-MAR-04:12 | 5.20 | 0.41 | 0.549853E+10 | 6734.77 | 02-MAR-14:20 | 5.20 | 0.41 |
April | 0.536831E+11 | 83662.53 | 24-APR-04:12 | 6.10 | 2.66 | 0.488217E+10 | 6734.73 | 17-APR-13:00 | 6.10 | 2.66 |
May | 0.511595E+11 | 88339.69 | 30-MAY-04:13 | 14.27 | 10.94 | 0.528759E+10 | 6734.98 | 11-MAY-09:09 | 14.27 | 10.94 |
June | 0.671915E+11 | 89197.73 | 23-JUN-04:13 | 16.50 | 10.18 | 0.529496E+10 | 7331.51 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.822894E+11 | 89737.70 | 08-JUL-04:13 | 16.30 | 14.75 | 0.492528E+10 | 7544.49 | 19-JUL-09:20 | 26.83 | 16.10 |
August | 0.814793E+11 | 87423.18 | 23-AUG-04:23 | 18.60 | 14.48 | 0.551403E+10 | 7406.37 | 03-AUG-09:09 | 18.60 | 14.48 |
September | 0.527440E+11 | 87645.59 | 18-SEP-04:13 | 14.23 | 11.08 | 0.488788E+10 | 6898.45 | 12-SEP-12:20 | 14.23 | 11.08 |
October | 0.517865E+11 | 86382.79 | 11-OCT-04:13 | 17.40 | 13.72 | 0.508230E+10 | 6893.86 | 10-OCT-10:00 | 17.40 | 13.72 |
November | 0.470137E+11 | 82627.41 | 24-NOV-05:12 | 2.40 | -2.3 | 0.502783E+10 | 6734.73 | 30-NOV-10:20 | 6.70 | 0.80 |
December | 0.442177E+11 | 81115.15 | 04-DEC-04:01 | -0.1 | -1.9 | 0.490103E+10 | 6734.76 | 26-DEC-10:20 | 2.57 | 0.95 |
Annual Sum or Average | 0.655050E+12 | 0.609761E+11 | ||||||||
Minimum of Months | 0.364666E+11 | 80140.89 | -2.6 | -4.0 | 0.460339E+10 | 6734.73 | 2.03 | -1.4 | ||
Maximum of Months | 0.822894E+11 | 89737.70 | 18.60 | 14.75 | 0.551403E+10 | 7544.49 | 37.70 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245381E+11 | 53556.28 | 04-JAN-06:02 | -2.3 | -3.9 | 0.498381E+10 | 6734.74 | 06-JAN-10:00 | 2.20 | -1.4 |
February | 0.240035E+11 | 68137.85 | 16-FEB-06:02 | 1.70 | -0.5 | 0.454701E+10 | 6734.76 | 15-FEB-10:20 | 1.70 | -0.5 |
March | 0.325138E+11 | 67953.23 | 17-MAR-05:03 | 7.02 | 1.62 | 0.547567E+10 | 6734.73 | 27-MAR-09:20 | 9.63 | 4.16 |
April | 0.348800E+11 | 71369.17 | 14-APR-04:11 | 9.43 | 2.43 | 0.487231E+10 | 6734.71 | 07-APR-09:20 | 9.43 | 2.43 |
May | 0.398771E+11 | 73151.62 | 30-MAY-04:12 | 14.27 | 10.94 | 0.527998E+10 | 6734.93 | 11-MAY-09:09 | 14.27 | 10.94 |
June | 0.433532E+11 | 74249.87 | 05-JUN-04:12 | 15.00 | 13.05 | 0.526608E+10 | 6740.16 | 28-JUN-13:30 | 37.50 | 13.98 |
July | 0.442174E+11 | 74657.92 | 14-JUL-05:03 | 17.67 | 13.64 | 0.489501E+10 | 7025.92 | 19-JUL-09:20 | 26.83 | 16.10 |
August | 0.465947E+11 | 75192.93 | 01-AUG-05:03 | 19.50 | 14.33 | 0.549569E+10 | 6829.59 | 03-AUG-09:09 | 24.68 | 15.80 |
September | 0.400299E+11 | 73464.49 | 18-SEP-04:12 | 14.23 | 11.08 | 0.487896E+10 | 6735.32 | 12-SEP-09:50 | 14.23 | 11.08 |
October | 0.365226E+11 | 73217.77 | 03-OCT-04:12 | 14.63 | 11.58 | 0.506256E+10 | 6734.75 | 18-OCT-09:20 | 13.00 | 5.98 |
November | 0.292230E+11 | 70766.74 | 01-NOV-05:02 | 7.70 | 5.59 | 0.499693E+10 | 6734.75 | 08-NOV-10:30 | 13.60 | 6.17 |
December | 0.243847E+11 | 64834.27 | 01-DEC-06:03 | 3.90 | -0.5 | 0.481228E+10 | 6734.70 | 20-DEC-10:20 | 1.10 | -3.7 |
Annual Sum or Average | 0.420138E+12 | 0.605663E+11 | ||||||||
Minimum of Months | 0.240035E+11 | 53556.28 | -2.3 | -3.9 | 0.454701E+10 | 6734.70 | 1.10 | -3.7 | ||
Maximum of Months | 0.465947E+11 | 75192.93 | 19.50 | 14.33 | 0.549569E+10 | 7025.92 | 37.50 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161820E+11 | 19724.09 | 05-JAN-17:00 | 13.30 | 5.53 | 0.438994E+10 | 6692.78 | 04-JAN-14:00 | 13.30 | 5.53 |
February | 0.168238E+11 | 31382.50 | 15-FEB-16:20 | 17.03 | 6.28 | 0.418169E+10 | 6734.73 | 15-FEB-10:20 | 17.03 | 6.28 |
March | 0.251946E+11 | 32327.98 | 08-MAR-15:00 | 22.20 | 9.10 | 0.531164E+10 | 6734.72 | 02-MAR-14:20 | 22.20 | 9.10 |
April | 0.316068E+11 | 67197.31 | 27-APR-05:03 | 9.40 | 3.12 | 0.482929E+10 | 6734.67 | 18-APR-09:20 | 9.40 | 3.12 |
May | 0.392817E+11 | 74676.88 | 30-MAY-04:12 | 14.27 | 10.94 | 0.526493E+10 | 6734.88 | 11-MAY-09:09 | 14.27 | 10.94 |
June | 0.465856E+11 | 74830.18 | 05-JUN-04:12 | 15.00 | 13.05 | 0.526694E+10 | 6982.73 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.495455E+11 | 82382.78 | 31-JUL-04:13 | 19.60 | 14.51 | 0.489875E+10 | 7018.38 | 19-JUL-09:20 | 19.60 | 14.51 |
August | 0.507377E+11 | 82640.39 | 07-AUG-04:13 | 19.23 | 14.19 | 0.549854E+10 | 6739.15 | 03-AUG-09:09 | 19.23 | 14.19 |
September | 0.398179E+11 | 76320.34 | 05-SEP-04:12 | 17.23 | 15.17 | 0.487608E+10 | 6878.35 | 12-SEP-12:20 | 27.77 | 15.72 |
October | 0.305265E+11 | 72508.76 | 02-OCT-04:12 | 17.60 | 12.86 | 0.496629E+10 | 6734.71 | 02-OCT-09:50 | 21.93 | 14.41 |
November | 0.204602E+11 | 34014.82 | 01-NOV-15:20 | 12.07 | 7.11 | 0.470609E+10 | 6734.77 | 01-NOV-09:20 | 12.07 | 7.11 |
December | 0.158101E+11 | 20594.49 | 01-DEC-17:00 | 12.20 | 4.22 | 0.422415E+10 | 6734.54 | 01-DEC-14:20 | 12.20 | 4.22 |
Annual Sum or Average | 0.382573E+12 | 0.584143E+11 | ||||||||
Minimum of Months | 0.158101E+11 | 19724.09 | 9.40 | 3.12 | 0.418169E+10 | 6692.78 | 9.40 | 3.12 | ||
Maximum of Months | 0.507377E+11 | 82640.39 | 22.20 | 15.17 | 0.549854E+10 | 7018.38 | 37.70 | 15.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241337E+10 | 3806.22 | 02-JAN-13:10 | 12.98 | 5.03 | 0.585283E+09 | 845.62 | 02-JAN-10:20 | 12.98 | 5.03 |
February | 0.253607E+10 | 4629.50 | 21-FEB-13:30 | 12.20 | 6.00 | 0.547715E+09 | 845.62 | 13-FEB-10:20 | 12.20 | 6.00 |
March | 0.442998E+10 | 6840.97 | 27-MAR-14:30 | 18.05 | 6.97 | 0.678709E+09 | 845.63 | 02-MAR-14:20 | 18.05 | 6.97 |
April | 0.647068E+10 | 8415.12 | 14-APR-14:00 | 23.30 | 10.26 | 0.610534E+09 | 845.63 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.741692E+10 | 15776.41 | 29-MAY-16:51 | 26.10 | 13.34 | 0.663209E+09 | 845.65 | 11-MAY-09:09 | 26.10 | 13.34 |
June | 0.119080E+11 | 18369.03 | 25-JUN-17:42 | 32.88 | 15.68 | 0.667149E+09 | 957.54 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.144202E+11 | 17904.26 | 23-JUL-13:43 | 36.52 | 17.57 | 0.619744E+09 | 939.55 | 19-JUL-09:20 | 36.52 | 17.57 |
August | 0.134495E+11 | 15967.21 | 13-AUG-16:21 | 30.55 | 17.22 | 0.693065E+09 | 899.77 | 03-AUG-09:09 | 30.55 | 17.22 |
September | 0.758154E+10 | 15766.83 | 03-SEP-13:31 | 32.23 | 16.77 | 0.613467E+09 | 869.00 | 12-SEP-12:20 | 27.77 | 15.72 |
October | 0.529293E+10 | 11167.65 | 10-OCT-05:03 | 13.90 | 11.14 | 0.629870E+09 | 860.41 | 11-OCT-12:00 | 26.70 | 14.59 |
November | 0.339882E+10 | 4926.06 | 08-NOV-13:40 | 15.73 | 6.89 | 0.616383E+09 | 845.62 | 30-NOV-10:20 | 6.70 | 0.80 |
December | 0.254539E+10 | 3705.52 | 01-DEC-13:30 | 11.70 | 4.38 | 0.572671E+09 | 845.61 | 01-DEC-10:20 | 11.70 | 4.38 |
Annual Sum or Average | 0.818634E+11 | 0.749780E+10 | ||||||||
Minimum of Months | 0.241337E+10 | 3705.52 | 11.70 | 4.38 | 0.547715E+09 | 845.61 | 6.70 | 0.80 | ||
Maximum of Months | 0.144202E+11 | 18369.03 | 36.52 | 17.57 | 0.693065E+09 | 957.54 | 37.70 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255253E+10 | 11305.42 | 01-JAN-09:13 | 3.13 | -1.0 | 0.393398E+09 | 544.95 | 24-JAN-10:20 | 8.33 | 2.77 |
February | 0.291224E+10 | 15631.44 | 19-FEB-08:53 | 5.60 | 2.33 | 0.363971E+09 | 544.96 | 15-FEB-10:09 | 5.60 | 2.33 |
March | 0.526682E+10 | 19909.24 | 26-MAR-08:32 | 9.67 | 3.27 | 0.440931E+09 | 544.96 | 02-MAR-14:20 | 9.67 | 3.27 |
April | 0.797495E+10 | 24591.57 | 30-APR-08:11 | 15.20 | 5.08 | 0.394783E+09 | 546.60 | 28-APR-09:00 | 15.20 | 5.08 |
May | 0.888948E+10 | 24886.71 | 29-MAY-07:31 | 15.00 | 12.19 | 0.428462E+09 | 546.54 | 23-MAY-09:00 | 15.00 | 12.19 |
June | 0.120344E+11 | 25475.74 | 25-JUN-08:21 | 25.30 | 15.78 | 0.431011E+09 | 619.81 | 26-JUN-09:09 | 27.57 | 15.11 |
July | 0.134582E+11 | 26489.09 | 23-JUL-08:22 | 27.80 | 16.31 | 0.401850E+09 | 706.38 | 19-JUL-09:20 | 27.80 | 16.31 |
August | 0.126907E+11 | 23471.46 | 20-AUG-08:21 | 25.25 | 15.06 | 0.447912E+09 | 674.21 | 03-AUG-09:09 | 25.25 | 15.06 |
September | 0.841639E+10 | 24109.34 | 03-SEP-07:31 | 22.40 | 13.79 | 0.396042E+09 | 585.12 | 01-SEP-10:30 | 22.40 | 13.79 |
October | 0.613577E+10 | 23634.19 | 01-OCT-08:41 | 17.43 | 11.07 | 0.408773E+09 | 552.37 | 02-OCT-09:50 | 21.93 | 14.41 |
November | 0.368692E+10 | 15956.14 | 05-NOV-08:23 | 5.00 | 1.63 | 0.401603E+09 | 544.95 | 30-NOV-10:20 | 6.70 | 0.80 |
December | 0.249043E+10 | 7467.83 | 29-DEC-09:15 | 1.67 | -0.9 | 0.382472E+09 | 544.95 | 26-DEC-10:20 | 1.67 | -0.9 |
Annual Sum or Average | 0.865089E+11 | 0.489121E+10 | ||||||||
Minimum of Months | 0.249043E+10 | 7467.83 | 1.67 | -1.0 | 0.363971E+09 | 544.95 | 1.67 | -0.9 | ||
Maximum of Months | 0.134582E+11 | 26489.09 | 27.80 | 16.31 | 0.447912E+09 | 706.38 | 27.80 | 16.31 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.955059E+10 | 23924.40 | 29-JAN-13:11 | 9.60 | 2.93 | 0.623723E+09 | 961.42 | 02-JAN-14:09 | 9.60 | 2.93 |
February | 0.959559E+10 | 23489.99 | 12-FEB-14:51 | 18.30 | 6.40 | 0.573051E+09 | 965.59 | 14-FEB-14:09 | 20.78 | 7.02 |
March | 0.103125E+11 | 23327.44 | 26-MAR-12:31 | 17.80 | 6.78 | 0.684428E+09 | 891.62 | 13-MAR-13:20 | 17.80 | 6.78 |
April | 0.104672E+11 | 22049.18 | 30-APR-12:52 | 20.60 | 7.16 | 0.611055E+09 | 847.56 | 17-APR-13:00 | 20.60 | 7.16 |
May | 0.880845E+10 | 20616.20 | 28-MAY-13:32 | 24.80 | 13.74 | 0.662696E+09 | 846.03 | 30-MAY-13:09 | 27.20 | 12.26 |
June | 0.117502E+11 | 20719.89 | 25-JUN-13:41 | 34.03 | 17.74 | 0.664430E+09 | 944.97 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.151927E+11 | 23112.41 | 23-JUL-13:43 | 36.52 | 17.57 | 0.618366E+09 | 899.15 | 19-JUL-09:20 | 36.52 | 17.57 |
August | 0.168595E+11 | 21475.61 | 20-AUG-12:22 | 32.80 | 17.08 | 0.695893E+09 | 954.11 | 30-AUG-12:09 | 25.87 | 15.40 |
September | 0.139368E+11 | 23166.14 | 03-SEP-10:51 | 28.90 | 16.43 | 0.622542E+09 | 1053.76 | 12-SEP-12:20 | 27.77 | 15.72 |
October | 0.141861E+11 | 24196.30 | 01-OCT-14:41 | 28.30 | 13.02 | 0.653360E+09 | 1063.13 | 11-OCT-12:00 | 26.70 | 14.59 |
November | 0.118390E+11 | 22923.97 | 19-NOV-13:01 | 11.47 | 2.76 | 0.641312E+09 | 994.51 | 01-NOV-13:09 | 11.47 | 2.76 |
December | 0.112760E+11 | 24129.99 | 31-DEC-11:11 | 4.23 | -1.4 | 0.612156E+09 | 954.08 | 29-DEC-14:09 | 4.23 | -1.4 |
Annual Sum or Average | 0.143775E+12 | 0.766301E+10 | ||||||||
Minimum of Months | 0.880845E+10 | 20616.20 | 4.23 | -1.4 | 0.573051E+09 | 846.03 | 4.23 | -1.4 | ||
Maximum of Months | 0.168595E+11 | 24196.30 | 36.52 | 17.74 | 0.695893E+09 | 1063.13 | 37.70 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.368085E+10 | 18690.25 | 22-JAN-15:21 | 13.60 | 4.02 | 0.400602E+09 | 544.95 | 06-JAN-10:00 | 13.60 | 4.02 |
February | 0.509535E+10 | 27262.45 | 12-FEB-14:51 | 18.30 | 6.40 | 0.370257E+09 | 544.96 | 15-FEB-10:09 | 11.38 | 5.33 |
March | 0.848515E+10 | 28156.60 | 26-MAR-14:31 | 20.40 | 7.68 | 0.445494E+09 | 544.96 | 28-MAR-13:39 | 15.57 | 7.44 |
April | 0.119255E+11 | 29668.01 | 16-APR-16:31 | 20.20 | 8.02 | 0.396624E+09 | 544.98 | 26-APR-13:30 | 25.00 | 9.94 |
May | 0.971219E+10 | 31015.37 | 07-MAY-15:51 | 24.40 | 8.93 | 0.428917E+09 | 544.98 | 11-MAY-09:09 | 12.57 | 6.21 |
June | 0.133266E+11 | 32809.35 | 11-JUN-16:51 | 28.30 | 13.17 | 0.429516E+09 | 622.34 | 27-JUN-15:00 | 37.80 | 15.32 |
July | 0.152676E+11 | 33058.72 | 30-JUL-15:41 | 33.80 | 17.55 | 0.400088E+09 | 613.16 | 21-JUL-15:00 | 33.80 | 17.55 |
August | 0.167285E+11 | 30896.87 | 20-AUG-15:42 | 35.00 | 15.92 | 0.447771E+09 | 570.76 | 01-AUG-15:00 | 35.00 | 15.92 |
September | 0.983395E+10 | 27824.07 | 24-SEP-16:21 | 25.30 | 15.57 | 0.396454E+09 | 545.26 | 12-SEP-09:50 | 25.30 | 15.57 |
October | 0.881799E+10 | 30131.97 | 01-OCT-15:21 | 28.60 | 13.08 | 0.411558E+09 | 549.50 | 02-OCT-09:50 | 21.93 | 14.41 |
November | 0.676012E+10 | 26482.10 | 19-NOV-15:01 | 14.90 | 3.99 | 0.407131E+09 | 544.95 | 30-NOV-10:20 | 6.70 | 0.80 |
December | 0.590853E+10 | 27914.95 | 31-DEC-15:51 | 10.00 | 1.48 | 0.396301E+09 | 544.95 | 26-DEC-10:20 | 10.00 | 1.48 |
Annual Sum or Average | 0.115542E+12 | 0.493071E+10 | ||||||||
Minimum of Months | 0.368085E+10 | 18690.25 | 10.00 | 1.48 | 0.370257E+09 | 544.95 | 6.70 | 0.80 | ||
Maximum of Months | 0.167285E+11 | 33058.72 | 35.00 | 17.55 | 0.447771E+09 | 622.34 | 37.80 | 17.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133138E+10 | 2079.83 | 05-JAN-15:50 | 16.10 | 6.84 | 0.503386E+09 | 784.72 | 04-JAN-14:00 | 16.10 | 6.84 |
February | 0.151158E+10 | 2732.88 | 15-FEB-15:00 | 17.20 | 6.67 | 0.479250E+09 | 845.60 | 15-FEB-14:20 | 17.20 | 6.67 |
March | 0.261719E+10 | 4583.09 | 27-MAR-14:30 | 18.05 | 6.97 | 0.636123E+09 | 845.62 | 28-MAR-13:20 | 16.13 | 7.51 |
April | 0.406091E+10 | 7237.85 | 14-APR-14:00 | 23.30 | 10.26 | 0.597282E+09 | 845.63 | 26-APR-13:20 | 24.80 | 9.90 |
May | 0.589749E+10 | 10021.57 | 22-MAY-05:02 | 16.78 | 12.20 | 0.659273E+09 | 845.64 | 11-MAY-09:09 | 16.78 | 12.20 |
June | 0.892607E+10 | 15806.47 | 18-JUN-18:12 | 29.43 | 10.52 | 0.662029E+09 | 867.45 | 28-JUN-13:30 | 37.50 | 13.98 |
July | 0.953023E+10 | 15464.35 | 02-JUL-18:01 | 31.42 | 16.51 | 0.616443E+09 | 888.19 | 19-JUL-09:20 | 26.83 | 16.10 |
August | 0.890945E+10 | 14768.62 | 13-AUG-17:31 | 29.63 | 17.01 | 0.690640E+09 | 846.45 | 03-AUG-09:09 | 29.63 | 17.01 |
September | 0.587712E+10 | 14412.37 | 04-SEP-17:11 | 26.33 | 15.98 | 0.610595E+09 | 845.71 | 12-SEP-09:50 | 24.03 | 15.08 |
October | 0.360529E+10 | 8515.85 | 11-OCT-12:53 | 26.70 | 14.59 | 0.601908E+09 | 845.62 | 24-OCT-13:00 | 7.20 | 3.69 |
November | 0.203910E+10 | 2989.31 | 03-NOV-13:40 | 12.03 | 2.27 | 0.548471E+09 | 845.61 | 21-NOV-14:20 | 15.37 | 5.87 |
December | 0.114472E+10 | 1936.06 | 29-DEC-16:10 | 11.42 | 3.74 | 0.472210E+09 | 818.88 | 01-DEC-14:00 | 11.42 | 3.74 |
Annual Sum or Average | 0.554505E+11 | 0.707761E+10 | ||||||||
Minimum of Months | 0.114472E+10 | 1936.06 | 11.42 | 2.27 | 0.472210E+09 | 784.72 | 7.20 | 3.69 | ||
Maximum of Months | 0.953023E+10 | 15806.47 | 31.42 | 17.01 | 0.690640E+09 | 888.19 | 37.50 | 17.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139048E+10 | 5761.87 | 27-JAN-09:40 | 2.07 | -2.9 | 0.272306E+09 | 548.49 | 30-JAN-11:09 | 7.43 | 1.38 |
February | 0.190560E+10 | 12667.27 | 19-FEB-10:02 | 9.60 | 4.44 | 0.257286E+09 | 548.49 | 13-FEB-11:09 | 9.60 | 4.44 |
March | 0.424558E+10 | 19099.66 | 26-MAR-09:32 | 13.13 | 5.03 | 0.318794E+09 | 548.50 | 30-MAR-10:09 | 9.68 | 3.98 |
April | 0.730172E+10 | 26315.80 | 30-APR-08:61 | 15.10 | 5.14 | 0.290838E+09 | 548.51 | 17-APR-14:09 | 15.10 | 5.14 |
May | 0.855285E+10 | 27267.94 | 29-MAY-09:01 | 18.68 | 12.90 | 0.315976E+09 | 548.52 | 15-MAY-12:09 | 18.68 | 12.90 |
June | 0.109265E+11 | 27688.15 | 18-JUN-08:51 | 25.60 | 11.91 | 0.315511E+09 | 599.68 | 30-JUN-08:30 | 25.30 | 15.58 |
July | 0.111977E+11 | 27661.45 | 16-JUL-08:41 | 23.62 | 18.10 | 0.295563E+09 | 654.52 | 06-JUL-08:30 | 23.62 | 18.10 |
August | 0.109627E+11 | 26605.16 | 13-AUG-08:11 | 20.73 | 17.37 | 0.329182E+09 | 629.66 | 03-AUG-08:00 | 20.73 | 17.37 |
September | 0.781375E+10 | 25351.43 | 17-SEP-09:21 | 18.60 | 13.20 | 0.292299E+09 | 596.90 | 01-SEP-10:30 | 18.60 | 13.20 |
October | 0.523209E+10 | 24378.59 | 01-OCT-08:11 | 16.33 | 10.50 | 0.298387E+09 | 548.51 | 06-OCT-10:09 | 21.57 | 12.33 |
November | 0.248651E+10 | 13470.72 | 23-NOV-10:02 | 7.48 | 1.96 | 0.288964E+09 | 548.49 | 20-NOV-11:09 | 7.48 | 1.96 |
December | 0.123755E+10 | 5431.62 | 29-DEC-09:25 | 1.95 | -0.8 | 0.264069E+09 | 548.49 | 29-DEC-11:09 | 5.97 | 1.69 |
Annual Sum or Average | 0.732530E+11 | 0.353917E+10 | ||||||||
Minimum of Months | 0.123755E+10 | 5431.62 | 1.95 | -2.9 | 0.257286E+09 | 548.49 | 5.97 | 1.38 | ||
Maximum of Months | 0.111977E+11 | 27688.15 | 25.60 | 18.10 | 0.329182E+09 | 654.52 | 25.30 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.965407E+10 | 22520.51 | 01-JAN-14:12 | 15.77 | 5.71 | 0.621667E+09 | 1039.71 | 23-JAN-14:09 | 14.60 | 4.35 |
February | 0.953843E+10 | 22807.47 | 19-FEB-11:21 | 11.70 | 4.98 | 0.571037E+09 | 1044.69 | 14-FEB-14:09 | 11.70 | 4.98 |
March | 0.949627E+10 | 23103.32 | 12-MAR-13:01 | 16.88 | 5.49 | 0.675967E+09 | 923.15 | 13-MAR-13:50 | 20.32 | 6.92 |
April | 0.884894E+10 | 21455.70 | 30-APR-13:22 | 21.15 | 7.38 | 0.605128E+09 | 846.83 | 14-APR-13:20 | 21.15 | 7.38 |
May | 0.775062E+10 | 19880.15 | 21-MAY-13:02 | 26.88 | 12.21 | 0.659566E+09 | 846.35 | 30-MAY-13:20 | 27.20 | 12.25 |
June | 0.908267E+10 | 19513.52 | 18-JUN-15:31 | 32.03 | 11.80 | 0.661225E+09 | 868.04 | 28-JUN-13:30 | 37.50 | 13.98 |
July | 0.107865E+11 | 21494.17 | 30-JUL-12:32 | 31.10 | 17.67 | 0.616382E+09 | 855.84 | 19-JUL-09:20 | 31.10 | 17.67 |
August | 0.131457E+11 | 21526.12 | 13-AUG-12:52 | 28.30 | 18.16 | 0.692480E+09 | 901.37 | 31-AUG-13:09 | 29.50 | 15.73 |
September | 0.133376E+11 | 23198.74 | 17-SEP-13:21 | 23.90 | 14.61 | 0.627874E+09 | 1061.90 | 12-SEP-12:20 | 23.90 | 14.61 |
October | 0.139196E+11 | 25518.27 | 01-OCT-12:11 | 26.13 | 14.41 | 0.660718E+09 | 1076.11 | 31-OCT-13:39 | 21.87 | 8.72 |
November | 0.116275E+11 | 23742.30 | 12-NOV-11:41 | 6.93 | 2.37 | 0.646608E+09 | 1071.67 | 01-NOV-13:20 | 6.93 | 2.37 |
December | 0.107589E+11 | 23914.18 | 24-DEC-12:31 | 9.83 | 1.91 | 0.610424E+09 | 1024.05 | 29-DEC-14:09 | 10.68 | 3.53 |
Annual Sum or Average | 0.127947E+12 | 0.764908E+10 | ||||||||
Minimum of Months | 0.775062E+10 | 19513.52 | 6.93 | 1.91 | 0.571037E+09 | 846.35 | 6.93 | 2.37 | ||
Maximum of Months | 0.139196E+11 | 25518.27 | 32.03 | 18.16 | 0.692480E+09 | 1076.11 | 37.50 | 17.67 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211173E+10 | 9228.73 | 26-JAN-16:30 | 10.30 | 1.40 | 0.356994E+09 | 544.94 | 25-JAN-14:00 | 10.30 | 1.40 |
February | 0.286936E+10 | 13456.33 | 15-FEB-16:30 | 16.95 | 6.18 | 0.335678E+09 | 544.95 | 15-FEB-10:20 | 16.95 | 6.18 |
March | 0.448501E+10 | 26913.55 | 12-MAR-16:21 | 20.00 | 6.24 | 0.425520E+09 | 544.95 | 31-MAR-13:20 | 12.60 | 4.51 |
April | 0.679820E+10 | 26160.30 | 16-APR-16:51 | 20.60 | 8.14 | 0.391332E+09 | 544.96 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.783353E+10 | 28680.53 | 14-MAY-16:11 | 28.30 | 10.92 | 0.426573E+09 | 544.97 | 09-MAY-13:20 | 28.30 | 10.92 |
June | 0.101613E+11 | 30377.52 | 18-JUN-16:51 | 31.70 | 11.85 | 0.427362E+09 | 610.87 | 27-JUN-15:00 | 37.80 | 15.32 |
July | 0.105066E+11 | 30017.03 | 30-JUL-16:31 | 32.77 | 17.30 | 0.397998E+09 | 583.22 | 21-JUL-15:00 | 32.77 | 17.30 |
August | 0.106855E+11 | 28884.81 | 13-AUG-16:11 | 30.37 | 17.21 | 0.445968E+09 | 545.11 | 03-AUG-09:09 | 30.37 | 17.21 |
September | 0.786800E+10 | 28621.07 | 24-SEP-16:41 | 25.10 | 15.48 | 0.395481E+09 | 545.03 | 12-SEP-09:50 | 25.10 | 15.48 |
October | 0.585357E+10 | 27427.90 | 01-OCT-15:31 | 28.70 | 13.14 | 0.399111E+09 | 544.96 | 04-OCT-13:50 | 25.32 | 13.57 |
November | 0.318762E+10 | 23664.11 | 12-NOV-15:01 | 9.40 | 2.60 | 0.381200E+09 | 544.96 | 03-NOV-13:20 | 9.40 | 2.60 |
December | 0.210045E+10 | 8384.66 | 31-DEC-16:02 | 9.82 | 1.41 | 0.342596E+09 | 544.94 | 01-DEC-14:20 | 9.82 | 1.41 |
Annual Sum or Average | 0.744609E+11 | 0.472581E+10 | ||||||||
Minimum of Months | 0.210045E+10 | 8384.66 | 9.40 | 1.40 | 0.335678E+09 | 544.94 | 9.40 | 1.40 | ||
Maximum of Months | 0.106855E+11 | 30377.52 | 32.77 | 17.30 | 0.445968E+09 | 610.87 | 37.80 | 17.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.649704E+09 | 1978.34 | 05-JAN-15:40 | 16.10 | 6.84 | 0.479256E+09 | 738.42 | 24-JAN-14:00 | 16.10 | 4.97 |
February | 0.963472E+09 | 2445.54 | 15-FEB-15:50 | 17.20 | 6.53 | 0.452765E+09 | 845.50 | 15-FEB-14:00 | 17.20 | 6.53 |
March | 0.208317E+10 | 3923.40 | 16-MAR-14:40 | 20.20 | 8.60 | 0.604892E+09 | 845.62 | 28-MAR-13:20 | 16.13 | 7.51 |
April | 0.379645E+10 | 7605.90 | 14-APR-14:30 | 23.60 | 10.45 | 0.582830E+09 | 845.63 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.589054E+10 | 13282.65 | 29-MAY-16:31 | 26.47 | 13.23 | 0.653598E+09 | 845.64 | 31-MAY-13:20 | 26.50 | 11.57 |
June | 0.940307E+10 | 17815.93 | 11-JUN-18:01 | 27.33 | 12.53 | 0.661635E+09 | 902.13 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.103138E+11 | 17873.91 | 04-JUL-16:51 | 36.10 | 14.82 | 0.616412E+09 | 868.64 | 19-JUL-09:20 | 26.83 | 16.10 |
August | 0.952551E+10 | 17704.88 | 13-AUG-17:31 | 29.63 | 17.01 | 0.690404E+09 | 845.79 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.595738E+10 | 17598.30 | 04-SEP-16:01 | 26.70 | 16.46 | 0.607577E+09 | 850.48 | 12-SEP-12:20 | 27.77 | 15.72 |
October | 0.318757E+10 | 8420.53 | 11-OCT-12:53 | 26.70 | 14.59 | 0.580423E+09 | 845.63 | 02-OCT-13:30 | 26.70 | 14.59 |
November | 0.136338E+10 | 2313.89 | 01-NOV-15:10 | 12.43 | 7.32 | 0.513651E+09 | 845.61 | 03-NOV-13:20 | 11.87 | 2.12 |
December | 0.475970E+09 | 1841.09 | 29-DEC-15:50 | 11.60 | 3.89 | 0.454473E+09 | 764.85 | 01-DEC-14:00 | 11.60 | 3.89 |
Annual Sum or Average | 0.536101E+11 | 0.689792E+10 | ||||||||
Minimum of Months | 0.475970E+09 | 1841.09 | 11.60 | 3.89 | 0.452765E+09 | 738.42 | 11.60 | 2.12 | ||
Maximum of Months | 0.103138E+11 | 17873.91 | 36.10 | 17.01 | 0.690404E+09 | 902.13 | 37.70 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.965559E+09 | 3497.59 | 27-JAN-10:00 | 2.80 | -2.5 | 0.350031E+09 | 544.95 | 24-JAN-10:20 | 2.80 | -2.5 |
February | 0.147513E+10 | 7367.07 | 14-FEB-09:50 | 9.45 | 2.98 | 0.336356E+09 | 544.95 | 13-FEB-10:20 | 9.45 | 2.98 |
March | 0.367441E+10 | 19094.78 | 26-MAR-09:21 | 12.50 | 4.76 | 0.427454E+09 | 544.96 | 02-MAR-14:20 | 12.50 | 4.76 |
April | 0.707916E+10 | 23664.03 | 30-APR-09:02 | 15.78 | 4.89 | 0.392812E+09 | 545.97 | 26-APR-09:00 | 15.78 | 4.89 |
May | 0.867911E+10 | 24554.23 | 29-MAY-09:11 | 19.07 | 13.00 | 0.427311E+09 | 545.95 | 19-MAY-09:00 | 19.07 | 13.00 |
June | 0.114892E+11 | 26526.27 | 11-JUN-08:61 | 18.58 | 10.83 | 0.427363E+09 | 553.32 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.119462E+11 | 26913.99 | 09-JUL-08:11 | 22.77 | 17.42 | 0.398777E+09 | 674.16 | 19-JUL-09:20 | 26.83 | 16.10 |
August | 0.116835E+11 | 26901.33 | 13-AUG-08:11 | 20.73 | 17.37 | 0.446032E+09 | 612.40 | 03-AUG-09:09 | 20.73 | 17.37 |
September | 0.807185E+10 | 24532.97 | 03-SEP-09:01 | 25.97 | 15.10 | 0.394962E+09 | 586.20 | 01-SEP-10:30 | 25.97 | 15.10 |
October | 0.485623E+10 | 22917.29 | 01-OCT-09:02 | 18.35 | 11.47 | 0.400057E+09 | 544.97 | 02-OCT-13:30 | 26.15 | 15.30 |
November | 0.187073E+10 | 8788.61 | 01-NOV-09:10 | 10.47 | 6.68 | 0.382216E+09 | 544.96 | 01-NOV-09:20 | 10.93 | 6.89 |
December | 0.904529E+09 | 3238.65 | 29-DEC-09:25 | 1.95 | -0.8 | 0.332768E+09 | 544.95 | 14-DEC-10:20 | 1.95 | -0.8 |
Annual Sum or Average | 0.726956E+11 | 0.471614E+10 | ||||||||
Minimum of Months | 0.904529E+09 | 3238.65 | 1.95 | -2.5 | 0.332768E+09 | 544.95 | 1.95 | -2.5 | ||
Maximum of Months | 0.119462E+11 | 26913.99 | 25.97 | 17.42 | 0.446032E+09 | 674.16 | 37.70 | 17.37 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.779966E+10 | 25705.54 | 22-JAN-13:51 | 11.10 | 2.36 | 0.590137E+09 | 950.35 | 26-JAN-14:20 | 10.20 | 1.54 |
February | 0.810892E+10 | 25596.71 | 12-FEB-14:51 | 18.30 | 6.40 | 0.546620E+09 | 982.45 | 14-FEB-14:20 | 20.97 | 7.09 |
March | 0.833775E+10 | 25006.58 | 26-MAR-14:01 | 20.10 | 7.60 | 0.654662E+09 | 880.92 | 24-MAR-13:39 | 20.10 | 7.60 |
April | 0.840902E+10 | 22214.58 | 30-APR-13:02 | 20.78 | 7.24 | 0.595661E+09 | 846.95 | 17-APR-13:00 | 20.78 | 7.24 |
May | 0.775634E+10 | 22113.76 | 21-MAY-13:13 | 27.07 | 12.24 | 0.654031E+09 | 845.68 | 08-MAY-13:39 | 27.07 | 12.24 |
June | 0.959737E+10 | 21650.82 | 25-JUN-15:51 | 35.60 | 14.95 | 0.659965E+09 | 902.92 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.115885E+11 | 22734.59 | 30-JUL-14:02 | 32.38 | 17.78 | 0.616353E+09 | 847.91 | 19-JUL-09:20 | 32.38 | 17.78 |
August | 0.138356E+11 | 24004.60 | 13-AUG-12:52 | 28.30 | 18.16 | 0.691598E+09 | 880.32 | 31-AUG-13:09 | 29.50 | 15.73 |
September | 0.135225E+11 | 25284.66 | 17-SEP-12:11 | 22.43 | 14.07 | 0.621575E+09 | 1061.10 | 12-SEP-12:20 | 22.43 | 14.07 |
October | 0.132314E+11 | 27499.53 | 09-OCT-13:11 | 20.97 | 10.38 | 0.638361E+09 | 1027.67 | 11-OCT-12:00 | 26.70 | 14.59 |
November | 0.987414E+10 | 25044.26 | 12-NOV-15:01 | 9.40 | 2.60 | 0.617908E+09 | 1012.26 | 01-NOV-13:30 | 9.40 | 2.60 |
December | 0.882490E+10 | 25007.68 | 31-DEC-13:51 | 10.00 | 1.60 | 0.579185E+09 | 942.39 | 29-DEC-14:09 | 10.00 | 1.60 |
Annual Sum or Average | 0.120886E+12 | 0.746605E+10 | ||||||||
Minimum of Months | 0.775634E+10 | 21650.82 | 9.40 | 1.60 | 0.546620E+09 | 845.68 | 9.40 | 1.54 | ||
Maximum of Months | 0.138356E+11 | 27499.53 | 35.60 | 18.16 | 0.691598E+09 | 1061.10 | 37.70 | 17.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158173E+10 | 8536.69 | 26-JAN-16:30 | 10.30 | 1.40 | 0.341172E+09 | 544.93 | 02-JAN-14:20 | 10.30 | 1.40 |
February | 0.239959E+10 | 13391.52 | 15-FEB-16:30 | 16.95 | 6.18 | 0.320846E+09 | 544.94 | 27-FEB-14:20 | 11.47 | 4.37 |
March | 0.399166E+10 | 26753.83 | 12-MAR-16:31 | 20.20 | 6.28 | 0.408615E+09 | 544.95 | 28-MAR-13:20 | 16.13 | 7.51 |
April | 0.659095E+10 | 27599.32 | 16-APR-16:51 | 20.60 | 8.14 | 0.384735E+09 | 544.97 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.785136E+10 | 30438.23 | 07-MAY-16:21 | 24.40 | 9.02 | 0.423706E+09 | 544.97 | 08-MAY-13:39 | 25.93 | 9.77 |
June | 0.105140E+11 | 32257.34 | 11-JUN-16:41 | 28.22 | 13.16 | 0.427014E+09 | 614.08 | 27-JUN-15:00 | 37.80 | 15.32 |
July | 0.110164E+11 | 30286.58 | 04-JUL-16:51 | 36.10 | 14.82 | 0.398179E+09 | 596.77 | 21-JUL-15:00 | 37.20 | 15.00 |
August | 0.111268E+11 | 31340.71 | 13-AUG-16:51 | 31.10 | 17.22 | 0.445933E+09 | 545.08 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.794404E+10 | 30578.00 | 24-SEP-16:11 | 25.40 | 15.61 | 0.394523E+09 | 544.99 | 13-SEP-13:30 | 25.40 | 15.61 |
October | 0.548762E+10 | 28530.02 | 09-OCT-16:31 | 23.17 | 12.61 | 0.388758E+09 | 544.97 | 06-OCT-13:39 | 23.17 | 12.61 |
November | 0.258279E+10 | 12733.64 | 12-NOV-15:41 | 9.40 | 2.60 | 0.363751E+09 | 544.94 | 03-NOV-13:20 | 9.40 | 2.60 |
December | 0.152891E+10 | 7245.31 | 29-DEC-16:00 | 11.70 | 3.88 | 0.327942E+09 | 544.94 | 01-DEC-14:20 | 11.70 | 3.88 |
Annual Sum or Average | 0.726158E+11 | 0.462517E+10 | ||||||||
Minimum of Months | 0.152891E+10 | 7245.31 | 9.40 | 1.40 | 0.320846E+09 | 544.93 | 9.40 | 1.40 | ||
Maximum of Months | 0.111268E+11 | 32257.34 | 36.10 | 17.22 | 0.445933E+09 | 614.08 | 37.80 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140813E+10 | 7890.68 | 02-JAN-06:07 | -4.2 | -5.0 | 0.00 | 0.00 | 01-JAN-00:10 | -4.2 | -5.0 |
February | 0.176369E+10 | 4997.42 | 21-FEB-06:15 | 3.50 | 0.93 | 0.00 | 0.00 | 01-FEB-00:10 | 3.50 | 0.93 |
March | 0.382481E+10 | 6000.66 | 27-MAR-05:15 | 5.40 | 0.66 | 0.00 | 0.00 | 01-MAR-00:10 | 5.40 | 0.66 |
April | 0.581217E+10 | 6560.44 | 03-APR-05:15 | 7.40 | 1.11 | 0.00 | 0.00 | 01-APR-00:10 | 7.40 | 1.11 |
May | 0.637081E+10 | 10809.10 | 30-MAY-05:10 | 14.72 | 10.93 | 0.00 | 0.00 | 01-MAY-00:10 | 14.72 | 10.93 |
June | 0.997657E+10 | 14473.53 | 26-JUN-05:15 | 16.47 | 10.58 | 0.00 | 0.00 | 01-JUN-00:10 | 16.47 | 10.58 |
July | 0.127263E+11 | 17369.17 | 24-JUL-05:20 | 22.20 | 14.92 | 0.00 | 0.00 | 01-JUL-00:10 | 22.20 | 14.92 |
August | 0.123325E+11 | 15282.61 | 21-AUG-05:15 | 21.50 | 15.46 | 0.00 | 0.00 | 01-AUG-00:10 | 21.50 | 15.46 |
September | 0.743125E+10 | 13942.46 | 05-SEP-05:10 | 15.92 | 14.88 | 0.00 | 0.00 | 01-SEP-00:10 | 15.92 | 14.88 |
October | 0.562308E+10 | 12340.15 | 10-OCT-05:10 | 13.90 | 11.14 | 0.00 | 0.00 | 01-OCT-00:10 | 13.90 | 11.14 |
November | 0.349380E+10 | 5251.67 | 13-NOV-06:15 | 0.20 | -1.4 | 0.00 | 0.00 | 01-NOV-00:10 | 0.20 | -1.4 |
December | 0.204917E+10 | 3546.20 | 18-DEC-06:06 | -2.2 | -4.5 | 0.00 | 0.00 | 01-DEC-00:10 | -2.2 | -4.5 |
Annual Sum or Average | 0.728123E+11 | 0.00 | ||||||||
Minimum of Months | 0.140813E+10 | 3546.20 | -4.2 | -5.0 | 0.00 | 0.00 | -4.2 | -5.0 | ||
Maximum of Months | 0.127263E+11 | 17369.17 | 22.20 | 15.46 | 0.00 | 0.00 | 22.20 | 15.46 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303824E+09 | 8517.62 | 17-JAN-05:01 | -3.3 | -5.0 | 0.00 | 0.00 | 01-JAN-00:10 | -3.3 | -5.0 |
February | 0.408424E+09 | 8901.35 | 06-FEB-05:01 | -4.4 | -6.9 | 0.00 | 0.00 | 01-FEB-00:10 | -4.4 | -6.9 |
March | 0.113792E+10 | 3888.79 | 06-MAR-06:01 | -2.9 | -4.2 | 0.00 | 0.00 | 01-MAR-00:10 | -2.9 | -4.2 |
April | 0.286864E+10 | 4774.94 | 28-APR-15:10 | 25.00 | 10.42 | 0.00 | 0.00 | 01-APR-00:10 | 25.00 | 10.42 |
May | 0.422622E+10 | 5967.03 | 30-MAY-14:20 | 27.20 | 12.25 | 0.00 | 0.00 | 01-MAY-00:10 | 27.20 | 12.25 |
June | 0.631212E+10 | 7335.64 | 28-JUN-05:15 | 19.83 | 11.86 | 0.00 | 0.00 | 01-JUN-00:10 | 19.83 | 11.86 |
July | 0.729525E+10 | 9416.41 | 24-JUL-05:13 | 22.20 | 14.92 | 0.00 | 0.00 | 01-JUL-00:10 | 22.20 | 14.92 |
August | 0.736464E+10 | 8200.23 | 21-AUG-05:15 | 21.50 | 15.46 | 0.00 | 0.00 | 01-AUG-00:10 | 21.50 | 15.46 |
September | 0.507344E+10 | 8593.39 | 05-SEP-05:15 | 15.73 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 15.73 | 14.76 |
October | 0.290379E+10 | 6124.35 | 02-OCT-09:43 | 21.93 | 14.41 | 0.00 | 0.00 | 01-OCT-00:10 | 21.93 | 14.41 |
November | 0.863221E+09 | 6743.46 | 28-NOV-06:01 | -2.1 | -4.4 | 0.00 | 0.00 | 01-NOV-00:10 | -2.1 | -4.4 |
December | 0.296601E+09 | 7892.67 | 22-DEC-05:01 | -4.7 | -6.6 | 0.00 | 0.00 | 01-DEC-00:10 | -4.7 | -6.6 |
Annual Sum or Average | 0.390541E+11 | 0.00 | ||||||||
Minimum of Months | 0.296601E+09 | 3888.79 | -4.7 | -6.9 | 0.00 | 0.00 | -4.7 | -6.9 | ||
Maximum of Months | 0.736464E+10 | 9416.41 | 27.20 | 15.46 | 0.00 | 0.00 | 27.20 | 15.46 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164775E+09 | 2754.16 | 15-JAN-15:14 | 12.03 | 3.51 | 0.00 | 0.00 | 01-JAN-00:10 | 12.03 | 3.51 |
February | 0.744318E+09 | 6489.26 | 15-FEB-15:20 | 17.20 | 6.61 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 6.61 |
March | 0.261430E+10 | 9610.08 | 08-MAR-15:05 | 22.30 | 9.09 | 0.00 | 0.00 | 01-MAR-00:10 | 22.30 | 9.09 |
April | 0.637609E+10 | 15155.53 | 28-APR-14:40 | 24.80 | 10.38 | 0.00 | 0.00 | 01-APR-00:10 | 24.80 | 10.38 |
May | 0.884924E+10 | 18173.90 | 30-MAY-14:20 | 27.20 | 12.25 | 0.00 | 0.00 | 01-MAY-00:10 | 27.20 | 12.25 |
June | 0.133931E+11 | 24508.36 | 28-JUN-13:48 | 37.70 | 14.07 | 0.00 | 0.00 | 01-JUN-00:10 | 37.70 | 14.07 |
July | 0.152050E+11 | 22094.58 | 21-JUL-14:40 | 37.80 | 15.30 | 0.00 | 0.00 | 01-JUL-00:10 | 37.80 | 15.30 |
August | 0.145263E+11 | 20631.39 | 07-AUG-14:20 | 33.13 | 15.81 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 15.81 |
September | 0.924667E+10 | 19785.54 | 01-SEP-12:02 | 26.28 | 16.35 | 0.00 | 0.00 | 01-SEP-00:10 | 26.28 | 16.35 |
October | 0.442370E+10 | 17389.68 | 02-OCT-12:03 | 25.10 | 14.89 | 0.00 | 0.00 | 01-OCT-00:10 | 25.10 | 14.89 |
November | 0.794606E+09 | 5581.49 | 02-NOV-15:00 | 17.20 | 9.31 | 0.00 | 0.00 | 01-NOV-00:10 | 17.20 | 9.31 |
December | 63145854.82 | 2723.87 | 24-DEC-14:24 | 12.75 | 3.65 | 0.00 | 0.00 | 01-DEC-00:10 | 12.75 | 3.65 |
Annual Sum or Average | 0.764011E+11 | 0.00 | ||||||||
Minimum of Months | 63145854.82 | 2723.87 | 12.03 | 3.51 | 0.00 | 0.00 | 12.03 | 3.51 | ||
Maximum of Months | 0.152050E+11 | 24508.36 | 37.80 | 16.35 | 0.00 | 0.00 | 37.80 | 16.35 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350752E+10 | 2580.33 | 01-JAN-16:45 | 12.35 | 4.14 | 95230032.96 | 126.82 | 20-JAN-14:00 | 5.60 | 2.15 |
February | 0.805716E+10 | 4347.96 | 15-FEB-17:00 | 16.70 | 5.85 | 86396701.76 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.143360E+11 | 7096.80 | 31-MAR-24:00 | 6.90 | 3.36 | 0.103236E+09 | 126.83 | 15-MAR-09:00 | 6.90 | 3.36 |
April | 0.190030E+11 | 8414.63 | 16-APR-18:20 | 19.03 | 7.42 | 91613067.15 | 126.82 | 20-APR-09:00 | 12.20 | 5.87 |
May | 0.449994E+10 | 3513.36 | 31-MAY-24:00 | 18.60 | 7.93 | 99235224.09 | 126.85 | 24-MAY-09:00 | 18.60 | 7.93 |
June | 0.953583E+10 | 5453.19 | 30-JUN-24:00 | 22.10 | 13.89 | 98962073.85 | 126.85 | 08-JUN-13:00 | 22.10 | 13.89 |
July | 0.150772E+11 | 7364.58 | 31-JUL-24:00 | 21.00 | 17.53 | 91885957.90 | 126.84 | 10-JUL-09:09 | 21.00 | 17.53 |
August | 0.199522E+11 | 7970.49 | 27-AUG-18:37 | 24.07 | 15.15 | 0.103564E+09 | 128.70 | 21-AUG-13:00 | 24.07 | 15.15 |
September | 0.450677E+10 | 3484.46 | 30-SEP-24:00 | 17.40 | 10.77 | 91612440.85 | 126.85 | 06-SEP-13:00 | 17.40 | 10.77 |
October | 0.953442E+10 | 5289.47 | 31-OCT-24:00 | 13.00 | 4.55 | 95233117.81 | 126.85 | 11-OCT-09:09 | 13.00 | 4.55 |
November | 0.138569E+11 | 6478.98 | 05-NOV-16:50 | 11.78 | 2.80 | 94300854.99 | 126.83 | 02-NOV-13:09 | 11.78 | 2.80 |
December | 0.191646E+11 | 8206.14 | 31-DEC-16:34 | 9.27 | 1.21 | 91881252.73 | 126.82 | 08-DEC-14:09 | 9.27 | 1.21 |
Annual Sum or Average | 0.141032E+12 | 0.114315E+10 | ||||||||
Minimum of Months | 0.350752E+10 | 2580.33 | 6.90 | 1.21 | 86396701.76 | 126.82 | 5.60 | 1.21 | ||
Maximum of Months | 0.199522E+11 | 8414.63 | 24.07 | 17.53 | 0.103564E+09 | 128.70 | 24.07 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185446E+10 | 2235.85 | 26-JAN-17:00 | 10.00 | 1.21 | 95230047.23 | 126.82 | 20-JAN-14:00 | 10.00 | 1.21 |
February | 0.654917E+10 | 4134.50 | 15-FEB-17:00 | 16.70 | 5.85 | 86396712.37 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.128803E+11 | 6592.35 | 31-MAR-23:30 | 6.60 | 3.23 | 0.103236E+09 | 126.83 | 15-MAR-09:00 | 6.60 | 3.23 |
April | 0.177675E+11 | 8021.80 | 16-APR-18:10 | 19.22 | 7.51 | 91611735.99 | 126.82 | 20-APR-09:00 | 12.20 | 5.87 |
May | 0.394627E+10 | 3290.72 | 31-MAY-24:00 | 18.60 | 7.93 | 99234958.53 | 126.84 | 23-MAY-13:00 | 18.60 | 7.93 |
June | 0.882690E+10 | 5136.23 | 30-JUN-24:00 | 22.10 | 13.89 | 98961816.68 | 126.85 | 08-JUN-13:00 | 22.10 | 13.89 |
July | 0.140813E+11 | 6964.91 | 31-JUL-24:00 | 21.00 | 17.53 | 91886308.66 | 126.84 | 17-JUL-09:09 | 21.00 | 17.53 |
August | 0.188486E+11 | 7638.62 | 30-AUG-17:50 | 28.40 | 14.66 | 0.103376E+09 | 127.47 | 17-AUG-13:00 | 28.40 | 14.66 |
September | 0.396899E+10 | 3289.01 | 30-SEP-24:00 | 17.40 | 10.77 | 91611610.37 | 126.84 | 08-SEP-13:00 | 17.40 | 10.77 |
October | 0.847318E+10 | 4878.18 | 31-OCT-24:00 | 13.00 | 4.55 | 95232980.95 | 126.84 | 11-OCT-09:09 | 13.00 | 4.55 |
November | 0.121701E+11 | 5916.03 | 02-NOV-16:50 | 16.20 | 9.61 | 94300841.69 | 126.83 | 02-NOV-09:00 | 16.20 | 9.61 |
December | 0.166268E+11 | 7500.43 | 29-DEC-16:50 | 10.28 | 3.14 | 91880784.26 | 126.82 | 08-DEC-14:09 | 10.28 | 3.14 |
Annual Sum or Average | 0.125994E+12 | 0.114296E+10 | ||||||||
Minimum of Months | 0.185446E+10 | 2235.85 | 6.60 | 1.21 | 86396712.37 | 126.82 | 6.60 | 1.21 | ||
Maximum of Months | 0.188486E+11 | 8021.80 | 28.40 | 17.53 | 0.103376E+09 | 127.47 | 28.40 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.700361E+09 | 2133.29 | 26-JAN-17:00 | 10.00 | 1.21 | 94094045.74 | 127.51 | 26-JAN-10:09 | 10.00 | 1.21 |
February | 0.509502E+10 | 4154.32 | 15-FEB-17:00 | 16.70 | 5.85 | 86396714.57 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.119154E+11 | 6268.74 | 31-MAR-23:20 | 6.50 | 3.19 | 0.103236E+09 | 126.83 | 15-MAR-09:00 | 6.50 | 3.19 |
April | 0.173444E+11 | 8160.03 | 16-APR-18:00 | 19.40 | 7.60 | 91608604.61 | 126.82 | 20-APR-09:00 | 12.20 | 5.87 |
May | 0.376213E+10 | 3216.40 | 31-MAY-23:50 | 18.77 | 8.04 | 99234850.43 | 126.84 | 23-MAY-13:00 | 18.77 | 8.04 |
June | 0.884067E+10 | 5124.29 | 30-JUN-24:00 | 22.10 | 13.89 | 98961947.60 | 126.85 | 08-JUN-13:00 | 22.10 | 13.89 |
July | 0.141959E+11 | 7000.85 | 04-JUL-18:35 | 32.77 | 13.53 | 91886574.29 | 126.84 | 17-JUL-09:09 | 22.77 | 17.51 |
August | 0.189152E+11 | 7769.39 | 30-AUG-17:40 | 28.50 | 14.73 | 0.103324E+09 | 126.83 | 23-AUG-09:00 | 28.50 | 14.73 |
September | 0.386488E+10 | 3236.35 | 30-SEP-23:40 | 17.50 | 10.08 | 91611716.26 | 126.85 | 01-SEP-13:00 | 17.50 | 10.08 |
October | 0.780345E+10 | 4655.87 | 31-OCT-23:30 | 13.50 | 5.10 | 95233016.98 | 126.84 | 11-OCT-09:09 | 13.50 | 5.10 |
November | 0.107414E+11 | 5908.36 | 02-NOV-16:50 | 16.20 | 9.61 | 94300861.82 | 126.83 | 02-NOV-09:00 | 16.20 | 9.61 |
December | 0.145856E+11 | 7407.64 | 29-DEC-16:50 | 10.28 | 3.14 | 91880805.56 | 126.82 | 08-DEC-14:09 | 10.28 | 3.14 |
Annual Sum or Average | 0.117764E+12 | 0.114177E+10 | ||||||||
Minimum of Months | 0.700361E+09 | 2133.29 | 6.50 | 1.21 | 86396714.57 | 126.82 | 6.50 | 1.21 | ||
Maximum of Months | 0.189152E+11 | 8160.03 | 32.77 | 14.73 | 0.103324E+09 | 127.51 | 28.50 | 17.51 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238001E+12 | 92207.47 | 02-JAN-17:00 | 11.10 | 4.18 | 0.206154E+10 | 2745.49 | 12-JAN-14:09 | 7.20 | 2.17 |
February | 0.435325E+12 | 182873.61 | 15-FEB-17:00 | 16.70 | 5.85 | 0.187030E+10 | 2745.65 | 22-FEB-14:09 | 8.90 | 2.93 |
March | 0.728270E+12 | 358503.50 | 31-MAR-24:00 | 6.90 | 3.36 | 0.223481E+10 | 2745.67 | 23-MAR-09:09 | 6.90 | 3.36 |
April | 0.942643E+12 | 366476.30 | 17-APR-16:00 | 25.00 | 8.95 | 0.198300E+10 | 2745.64 | 21-APR-09:39 | 16.47 | 7.54 |
May | 0.240504E+12 | 176154.88 | 31-MAY-24:00 | 18.60 | 7.93 | 0.214824E+10 | 2747.16 | 19-MAY-13:00 | 18.60 | 7.93 |
June | 0.471493E+12 | 268787.50 | 30-JUN-23:55 | 22.10 | 13.89 | 0.214296E+10 | 2749.16 | 01-JUN-13:00 | 22.10 | 13.89 |
July | 0.735303E+12 | 361084.44 | 31-JUL-24:00 | 21.00 | 17.53 | 0.198992E+10 | 2749.90 | 27-JUL-09:00 | 21.00 | 17.53 |
August | 0.979615E+12 | 376867.55 | 13-AUG-13:42 | 29.72 | 18.15 | 0.226365E+10 | 3216.95 | 17-AUG-10:50 | 29.72 | 18.55 |
September | 0.236271E+12 | 176474.29 | 30-SEP-24:00 | 17.40 | 10.77 | 0.198338E+10 | 2747.56 | 14-SEP-13:09 | 17.40 | 10.77 |
October | 0.487824E+12 | 268474.74 | 31-OCT-24:00 | 13.00 | 4.55 | 0.206170E+10 | 2748.92 | 10-OCT-13:30 | 13.00 | 4.55 |
November | 0.708117E+12 | 275949.87 | 20-NOV-17:00 | 12.80 | 4.32 | 0.204138E+10 | 2746.33 | 09-NOV-14:00 | 12.80 | 4.32 |
December | 0.975976E+12 | 367251.65 | 26-DEC-17:00 | 6.70 | 3.21 | 0.198897E+10 | 2745.64 | 04-DEC-10:50 | 6.70 | 3.21 |
Annual Sum or Average | 0.717934E+13 | 0.247698E+11 | ||||||||
Minimum of Months | 0.236271E+12 | 92207.47 | 6.70 | 3.21 | 0.187030E+10 | 2745.49 | 6.70 | 2.17 | ||
Maximum of Months | 0.979615E+12 | 376867.55 | 29.72 | 18.15 | 0.226365E+10 | 3216.95 | 29.72 | 18.55 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121146E+10 | 66101.12 | 17-JAN-05:01 | -3.3 |
February | 0.420409E+09 | 65623.17 | 06-FEB-05:01 | -4.4 |
March | 9030925.77 | 57892.36 | 06-MAR-06:01 | -2.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 252926.19 | 2107.72 | 26-OCT-05:02 | -2.5 |
November | 0.167723E+09 | 61527.27 | 27-NOV-05:11 | -4.1 |
December | 0.103009E+10 | 65773.58 | 26-DEC-05:01 | -1.0 |
Annual Sum or Average | 0.283897E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.121146E+10 | 66101.12 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 781913.74 | 2124.97 | 21-JAN-06:01 | -6.5 |
February | 34905.09 | 407.23 | 04-FEB-06:01 | -6.7 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 816818.83 | |||
Minimum of Months | 0.00 | 0.00 | -6.7 | |
Maximum of Months | 781913.74 | 2124.97 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3645077.40 | 5417.49 | 21-JAN-06:01 | -6.5 |
February | 566820.63 | 2744.84 | 04-FEB-06:01 | -6.7 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 960533.21 | 2430.26 | 22-DEC-06:01 | -6.1 |
Annual Sum or Average | 5172431.24 | |||
Minimum of Months | 0.00 | 0.00 | -6.7 | |
Maximum of Months | 3645077.40 | 5417.49 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19889268.71 | 9867.92 | 18-JAN-06:01 | -2.9 |
February | 5965016.88 | 9960.64 | 06-FEB-06:01 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 3546299.43 | 7830.30 | 22-DEC-06:01 | -6.1 |
Annual Sum or Average | 29400585.02 | |||
Minimum of Months | 0.00 | 0.00 | -6.1 | |
Maximum of Months | 19889268.71 | 9960.64 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.801058E+09 | 11805.85 | 17-JAN-05:01 | -3.3 |
February | 0.438904E+09 | 12145.92 | 06-FEB-04:01 | -4.4 |
March | 43023333.52 | 10720.18 | 06-MAR-06:01 | -2.9 |
April | 294067.93 | 1923.95 | 08-APR-05:03 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 20965424.28 | 10529.00 | 26-OCT-05:02 | -2.5 |
November | 0.126467E+09 | 11163.93 | 27-NOV-05:02 | -4.0 |
December | 0.845127E+09 | 11488.95 | 23-DEC-05:01 | -5.1 |
Annual Sum or Average | 0.227584E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.845127E+09 | 12145.92 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361285E+09 | 13681.22 | 17-JAN-05:01 | -3.3 |
February | 0.160328E+09 | 13467.98 | 06-FEB-05:01 | -4.4 |
March | 7755696.38 | 12272.32 | 04-MAR-06:02 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 9538807.22 | 11013.54 | 26-OCT-05:02 | -2.5 |
November | 29778000.26 | 11789.35 | 28-NOV-06:01 | -2.1 |
December | 0.339803E+09 | 13077.36 | 26-DEC-05:01 | -1.0 |
Annual Sum or Average | 0.908488E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.361285E+09 | 13681.22 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213331E+09 | 15055.11 | 17-JAN-05:01 | -3.3 |
February | 0.103750E+09 | 14925.19 | 06-FEB-05:01 | -4.4 |
March | 6019641.07 | 13615.41 | 04-MAR-06:02 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 7407277.40 | 12488.38 | 26-OCT-05:02 | -2.5 |
November | 6615191.76 | 12240.67 | 28-NOV-06:01 | -2.1 |
December | 0.198905E+09 | 14437.14 | 26-DEC-05:01 | -1.0 |
Annual Sum or Average | 0.536028E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.213331E+09 | 15055.11 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217668E+09 | 13297.93 | 17-JAN-05:01 | -3.3 |
February | 0.107872E+09 | 13220.89 | 06-FEB-05:01 | -4.4 |
March | 4681442.27 | 9272.18 | 04-MAR-06:02 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 4716246.23 | 7285.32 | 26-OCT-05:02 | -2.5 |
November | 11097391.10 | 11433.85 | 28-NOV-06:01 | -2.1 |
December | 0.200633E+09 | 12288.89 | 22-DEC-05:01 | -4.7 |
Annual Sum or Average | 0.546668E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.7 | |
Maximum of Months | 0.217668E+09 | 13297.93 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331099E+10 | 14948.70 | 02-JAN-04:01 | -1.8 |
February | 0.200743E+10 | 15384.38 | 06-FEB-04:01 | -4.4 |
March | 0.597136E+09 | 13658.50 | 04-MAR-05:01 | -1.2 |
April | 60579353.24 | 12025.41 | 06-APR-05:02 | 2.12 |
May | 4378755.84 | 6396.02 | 06-MAY-05:03 | 6.02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.280412E+09 | 13608.54 | 26-OCT-04:01 | -2.8 |
November | 0.108938E+10 | 14751.05 | 27-NOV-04:01 | -3.9 |
December | 0.348862E+10 | 15131.15 | 26-DEC-04:11 | 0.03 |
Annual Sum or Average | 0.108389E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.348862E+10 | 15384.38 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147290E+10 | 17194.49 | 17-JAN-04:01 | -3.3 |
February | 0.805942E+09 | 17842.52 | 06-FEB-04:01 | -4.4 |
March | 0.199127E+09 | 15693.43 | 04-MAR-05:01 | -1.2 |
April | 15155485.54 | 8071.06 | 08-APR-05:03 | 2.62 |
May | 991971.24 | 2110.54 | 06-MAY-05:03 | 6.02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.119866E+09 | 15730.19 | 26-OCT-04:01 | -2.8 |
November | 0.373189E+09 | 16947.17 | 27-NOV-04:01 | -3.9 |
December | 0.145549E+10 | 17563.34 | 26-DEC-04:11 | 0.03 |
Annual Sum or Average | 0.444266E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.147290E+10 | 17842.52 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143520E+10 | 18496.85 | 17-JAN-04:01 | -3.3 |
February | 0.842048E+09 | 18909.56 | 06-FEB-04:01 | -4.4 |
March | 0.251475E+09 | 16748.04 | 04-MAR-05:01 | -1.2 |
April | 27623777.11 | 12093.74 | 08-APR-05:03 | 2.62 |
May | 3349837.59 | 4887.04 | 05-MAY-05:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.128139E+09 | 16821.98 | 26-OCT-04:01 | -2.8 |
November | 0.267139E+09 | 17062.41 | 27-NOV-05:11 | -4.1 |
December | 0.137747E+10 | 18765.14 | 26-DEC-04:11 | 0.03 |
Annual Sum or Average | 0.433244E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.143520E+10 | 18909.56 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115136E+10 | 17777.18 | 17-JAN-04:01 | -3.3 |
February | 0.639256E+09 | 18197.91 | 06-FEB-04:01 | -4.4 |
March | 0.134841E+09 | 15560.96 | 04-MAR-05:01 | -1.2 |
April | 3589691.17 | 5832.96 | 08-APR-05:03 | 2.62 |
May | 127055.24 | 847.03 | 05-MAY-05:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 75197973.11 | 15591.32 | 26-OCT-04:01 | -2.8 |
November | 0.257674E+09 | 16420.74 | 27-NOV-05:11 | -4.1 |
December | 0.109117E+10 | 17491.77 | 26-DEC-04:11 | 0.03 |
Annual Sum or Average | 0.335322E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.115136E+10 | 18197.91 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250086E+09 | 11201.26 | 22-JAN-15:21 | 13.60 |
February | 0.147819E+09 | 11991.75 | 12-FEB-14:51 | 18.30 |
March | 0.164739E+09 | 11891.55 | 05-MAR-15:41 | 14.22 |
April | 0.176347E+09 | 10319.48 | 30-APR-14:51 | 22.20 |
May | 98839538.80 | 11714.03 | 14-MAY-16:11 | 28.30 |
June | 0.134916E+09 | 11369.60 | 11-JUN-16:51 | 28.30 |
July | 0.185172E+09 | 11904.77 | 30-JUL-15:41 | 33.80 |
August | 0.120573E+09 | 11539.44 | 13-AUG-15:41 | 29.90 |
September | 83594480.88 | 11860.71 | 03-SEP-13:31 | 32.23 |
October | 0.137182E+09 | 11228.22 | 01-OCT-14:41 | 28.30 |
November | 0.218006E+09 | 11412.36 | 19-NOV-14:21 | 14.15 |
December | 0.220997E+09 | 12138.09 | 31-DEC-15:11 | 10.73 |
Annual Sum or Average | 0.193827E+10 | |||
Minimum of Months | 83594480.88 | 10319.48 | 10.73 | |
Maximum of Months | 0.250086E+09 | 12138.09 | 33.80 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147902E+10 | 8725.22 | 22-JAN-16:12 | 12.20 |
February | 0.876683E+09 | 8594.60 | 19-FEB-10:42 | 10.40 |
March | 0.176329E+09 | 12628.08 | 05-MAR-15:52 | 14.40 |
April | 81108186.85 | 10219.63 | 30-APR-15:21 | 21.95 |
May | 82830206.08 | 12148.91 | 14-MAY-16:11 | 28.30 |
June | 76210276.87 | 12319.18 | 18-JUN-16:51 | 31.70 |
July | 99271154.49 | 12933.09 | 30-JUL-15:51 | 33.90 |
August | 70540380.95 | 12360.52 | 20-AUG-15:21 | 35.00 |
September | 75862612.20 | 10748.19 | 03-SEP-13:41 | 32.52 |
October | 0.156351E+09 | 11505.39 | 01-OCT-14:11 | 28.30 |
November | 0.452097E+09 | 12545.66 | 12-NOV-15:01 | 9.40 |
December | 0.140494E+10 | 8830.85 | 24-DEC-12:33 | 9.83 |
Annual Sum or Average | 0.503125E+10 | |||
Minimum of Months | 70540380.95 | 8594.60 | 9.40 | |
Maximum of Months | 0.147902E+10 | 12933.09 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460052E+10 | 21314.25 | 17-JAN-05:12 | -3.3 |
February | 0.306358E+10 | 22640.26 | 06-FEB-06:13 | -4.8 |
March | 0.189727E+10 | 10997.95 | 26-MAR-08:41 | 10.13 |
April | 0.821036E+09 | 12006.65 | 12-APR-05:03 | 10.50 |
May | 0.452468E+09 | 13053.06 | 12-MAY-05:03 | 9.60 |
June | 0.169092E+09 | 11966.98 | 20-JUN-05:03 | 12.77 |
July | 72086080.73 | 10759.44 | 03-JUL-04:12 | 19.23 |
August | 75805197.53 | 10257.17 | 31-AUG-05:02 | 13.72 |
September | 0.246543E+09 | 11514.45 | 27-SEP-05:02 | 11.60 |
October | 0.123373E+10 | 11324.10 | 04-OCT-05:03 | 12.80 |
November | 0.233344E+10 | 17151.89 | 27-NOV-06:02 | -4.4 |
December | 0.482567E+10 | 17577.45 | 04-DEC-06:13 | -0.6 |
Annual Sum or Average | 0.197912E+11 | |||
Minimum of Months | 72086080.73 | 10257.17 | -4.8 | |
Maximum of Months | 0.482567E+10 | 22640.26 | 19.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3752507.46 | 160.74 | 17-JAN-05:17 | -3.3 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 3752507.46 | |||
Minimum of Months | 0.00 | 0.00 | -3.3 | |
Maximum of Months | 3752507.46 | 160.74 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.632280E+09 | 676.37 | 16-JAN-18:10 | -1.6 |
February | 952509.07 | 436.32 | 06-FEB-02:15 | -5.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.633233E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.632280E+09 | 676.37 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968216E+10 | 10174.14 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.878253E+10 | 10174.14 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.104353E+11 | 10174.14 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.932187E+10 | 10174.14 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.100587E+11 | 10174.14 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.100099E+11 | 10174.14 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.937071E+10 | 10174.14 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.104353E+11 | 10174.14 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.932187E+10 | 10174.14 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.968216E+10 | 10174.14 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.956821E+10 | 10174.14 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.937071E+10 | 10174.14 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.116039E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.878253E+10 | 10174.14 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.104353E+11 | 10174.14 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.668321E+09 | 1004.17 | 09-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.585843E+09 | 888.42 | 16-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.662769E+09 | 754.15 | 20-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.571670E+09 | 545.86 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.609563E+09 | 613.47 | 22-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.597626E+09 | 624.30 | 08-JUN-15:00 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.565637E+09 | 620.65 | 07-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.632701E+09 | 545.86 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.584101E+09 | 868.83 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.632863E+09 | 867.48 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.663154E+09 | 1147.25 | 13-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.679187E+09 | 1147.25 | 01-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.745343E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.565637E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.679187E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.426004E+09 | 651.44 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.375358E+09 | 560.06 | 16-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.425754E+09 | 410.74 | 01-MAR-17:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.369633E+09 | 351.77 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.395161E+09 | 384.68 | 22-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.387673E+09 | 402.63 | 08-JUN-15:00 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.366143E+09 | 400.37 | 07-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.408972E+09 | 351.77 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.375883E+09 | 549.64 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.403091E+09 | 519.11 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.425641E+09 | 739.33 | 13-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.432552E+09 | 739.33 | 01-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.479187E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.366143E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.432552E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.648944E+09 | 943.63 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.576143E+09 | 878.01 | 16-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.659450E+09 | 733.54 | 20-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.573471E+09 | 545.88 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.613396E+09 | 615.94 | 22-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.602389E+09 | 624.51 | 08-JUN-15:00 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.569382E+09 | 620.71 | 07-JUL-15:00 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.634936E+09 | 545.88 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.583436E+09 | 866.69 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.622303E+09 | 843.47 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.646277E+09 | 1147.28 | 13-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.651846E+09 | 1147.28 | 01-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.738197E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.569382E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.659450E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.421780E+09 | 588.60 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.372393E+09 | 573.48 | 16-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.424936E+09 | 524.74 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.367187E+09 | 351.77 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.391807E+09 | 400.69 | 22-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.385527E+09 | 408.57 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.365097E+09 | 396.91 | 07-JUL-15:00 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.407429E+09 | 351.77 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.375007E+09 | 562.57 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.403452E+09 | 570.26 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.416723E+09 | 739.33 | 13-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.423796E+09 | 739.33 | 01-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.475513E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.365097E+09 | 351.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.424936E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.666630E+09 | 1002.19 | 09-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.584869E+09 | 885.71 | 16-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.662007E+09 | 749.67 | 20-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.571493E+09 | 545.86 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.609296E+09 | 608.21 | 22-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.597398E+09 | 619.61 | 08-JUN-15:00 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.565347E+09 | 615.76 | 07-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.632503E+09 | 545.86 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.583539E+09 | 865.94 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.631639E+09 | 864.30 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.662129E+09 | 1147.25 | 13-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.677592E+09 | 1147.25 | 01-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.744444E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.565347E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.677592E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.425514E+09 | 649.21 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.374925E+09 | 555.56 | 16-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.425435E+09 | 410.74 | 01-MAR-17:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.369517E+09 | 351.77 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.394974E+09 | 381.06 | 22-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.387367E+09 | 399.74 | 08-JUN-15:00 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.365915E+09 | 397.36 | 07-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.408823E+09 | 351.77 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.375647E+09 | 545.01 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.402769E+09 | 514.08 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.425142E+09 | 739.33 | 13-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.431972E+09 | 739.33 | 01-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.478800E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.365915E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.431972E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.648507E+09 | 941.80 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.575677E+09 | 875.24 | 16-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.658903E+09 | 640.59 | 20-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.573284E+09 | 545.88 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.613065E+09 | 610.79 | 22-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.601942E+09 | 619.84 | 08-JUN-15:00 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.569068E+09 | 615.82 | 07-JUL-15:00 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.634656E+09 | 545.88 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.583037E+09 | 863.78 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.621349E+09 | 840.15 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.645880E+09 | 1147.28 | 13-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.651651E+09 | 1147.28 | 01-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.737702E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.569068E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.658903E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.421208E+09 | 585.68 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.371976E+09 | 569.19 | 16-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.424639E+09 | 518.79 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.367102E+09 | 351.77 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.391649E+09 | 397.70 | 22-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.385343E+09 | 405.99 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.364936E+09 | 393.76 | 07-JUL-15:00 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.407254E+09 | 351.77 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.374783E+09 | 557.98 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.403000E+09 | 565.87 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.416467E+09 | 739.33 | 13-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.423404E+09 | 739.33 | 01-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.475176E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.364936E+09 | 351.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.424639E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.666579E+09 | 1002.12 | 09-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.584846E+09 | 885.15 | 16-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.661976E+09 | 748.88 | 20-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.571488E+09 | 545.86 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.609284E+09 | 608.00 | 22-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.597387E+09 | 619.43 | 08-JUN-15:00 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.565338E+09 | 615.56 | 07-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.632490E+09 | 545.86 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.583527E+09 | 865.34 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.631619E+09 | 863.73 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.662106E+09 | 1147.25 | 13-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.677573E+09 | 1147.25 | 01-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.744421E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.565338E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.677573E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.425502E+09 | 649.05 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.374915E+09 | 555.19 | 16-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.425424E+09 | 410.74 | 01-MAR-17:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.369510E+09 | 351.77 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.394969E+09 | 380.90 | 22-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.387348E+09 | 399.63 | 08-JUN-15:00 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.365908E+09 | 397.24 | 07-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.408813E+09 | 351.77 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.375640E+09 | 544.62 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.402764E+09 | 513.67 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.425130E+09 | 739.33 | 13-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.431963E+09 | 739.33 | 01-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.478789E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.365908E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.431963E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.648498E+09 | 941.45 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.575644E+09 | 874.67 | 16-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.658867E+09 | 640.45 | 20-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.573278E+09 | 545.88 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.613056E+09 | 610.59 | 22-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.601924E+09 | 619.65 | 08-JUN-15:00 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.569044E+09 | 615.62 | 07-JUL-15:00 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.634647E+09 | 545.88 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.582999E+09 | 863.18 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.621324E+09 | 839.55 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.645869E+09 | 1147.28 | 13-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.651645E+09 | 1147.28 | 01-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.737679E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.569044E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.658867E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.421186E+09 | 585.44 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.371967E+09 | 568.83 | 16-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.424629E+09 | 518.42 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.367100E+09 | 351.77 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.391634E+09 | 397.58 | 22-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.385337E+09 | 405.90 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.364931E+09 | 393.63 | 07-JUL-15:00 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.407246E+09 | 351.77 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.374777E+09 | 557.61 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.402994E+09 | 565.52 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.416479E+09 | 739.33 | 13-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.423399E+09 | 739.33 | 01-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.475168E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.364931E+09 | 351.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.424629E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274130E+10 | 2868.67 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.248656E+10 | 2868.67 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.295472E+10 | 2868.67 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.263917E+10 | 2868.67 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.284801E+10 | 2868.67 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.283424E+10 | 2868.67 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.265294E+10 | 2868.67 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.295472E+10 | 2868.67 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.263917E+10 | 2868.67 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.274130E+10 | 2868.67 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.270917E+10 | 2868.67 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.265294E+10 | 2868.67 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.328542E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.248656E+10 | 2868.67 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.295472E+10 | 2868.67 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.100587E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.100099E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.956821E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.116039E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.668321E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319876E+09 |
February | 0.136985E+10 | 0.585843E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295720E+09 |
March | 0.163685E+10 | 0.662769E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290030E+09 |
April | 0.145243E+10 | 0.571670E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 480709.68 | 0.206947E+09 |
May | 0.157338E+10 | 0.609563E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4310184.16 | 0.140356E+09 |
June | 0.156900E+10 | 0.597626E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21554467.51 | 75732624.63 |
July | 0.145680E+10 | 0.565637E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30713563.19 | 43169403.15 |
August | 0.163685E+10 | 0.632701E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15796839.10 | 54992173.64 |
September | 0.145243E+10 | 0.584101E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5349584.68 | 84848353.41 |
October | 0.150991E+10 | 0.632863E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1290319.81 | 0.158166E+09 |
November | 0.149516E+10 | 0.663154E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258231E+09 |
December | 0.145680E+10 | 0.679187E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298071E+09 |
Annual Sum or Average | 0.181194E+11 | 0.745343E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79495668.14 | 0.222614E+10 |
Minimum of Months | 0.136985E+10 | 0.565637E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43169403.15 |
Maximum of Months | 0.163685E+10 | 0.679187E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30713563.19 | 0.319876E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.426004E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217220E+09 |
February | 0.882782E+09 | 0.375358E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199337E+09 |
March | 0.105485E+10 | 0.425754E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194123E+09 |
April | 0.936002E+09 | 0.369633E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 318738.35 | 0.140115E+09 |
May | 0.101394E+10 | 0.395161E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2698911.76 | 95957453.18 |
June | 0.101113E+10 | 0.387673E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14329349.06 | 50553398.12 |
July | 0.938820E+09 | 0.366143E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20307316.16 | 29286171.11 |
August | 0.105485E+10 | 0.408972E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10452919.35 | 36678110.61 |
September | 0.936002E+09 | 0.375883E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3442996.51 | 57992518.25 |
October | 0.973041E+09 | 0.403091E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 826302.95 | 0.107472E+09 |
November | 0.963541E+09 | 0.425641E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173895E+09 |
December | 0.938820E+09 | 0.432552E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198511E+09 |
Annual Sum or Average | 0.116768E+11 | 0.479187E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52376534.13 | 0.150114E+10 |
Minimum of Months | 0.882782E+09 | 0.366143E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29286171.11 |
Maximum of Months | 0.105485E+10 | 0.432552E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20307316.16 | 0.217220E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.648944E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331695E+09 |
February | 0.136988E+10 | 0.576143E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306512E+09 |
March | 0.163688E+10 | 0.659450E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296201E+09 |
April | 0.145246E+10 | 0.573471E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 475001.94 | 0.211374E+09 |
May | 0.157341E+10 | 0.613396E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4090384.56 | 0.140800E+09 |
June | 0.156904E+10 | 0.602389E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21882793.22 | 73939823.91 |
July | 0.145684E+10 | 0.569382E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30743071.41 | 42250368.89 |
August | 0.163688E+10 | 0.634936E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15516988.43 | 56167713.55 |
September | 0.145246E+10 | 0.583436E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4786866.36 | 89413251.39 |
October | 0.150994E+10 | 0.622303E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 920980.98 | 0.166967E+09 |
November | 0.149520E+10 | 0.646277E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271709E+09 |
December | 0.145684E+10 | 0.651846E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308343E+09 |
Annual Sum or Average | 0.181198E+11 | 0.738197E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78416086.90 | 0.229537E+10 |
Minimum of Months | 0.136988E+10 | 0.569382E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42250368.89 |
Maximum of Months | 0.163688E+10 | 0.659450E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30743071.41 | 0.331695E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.421780E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226911E+09 |
February | 0.882782E+09 | 0.372393E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214253E+09 |
March | 0.105485E+10 | 0.424936E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213863E+09 |
April | 0.936002E+09 | 0.367187E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 316077.33 | 0.159503E+09 |
May | 0.101394E+10 | 0.391807E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2506718.14 | 0.104301E+09 |
June | 0.101113E+10 | 0.385527E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13677098.57 | 57602147.65 |
July | 0.938820E+09 | 0.365097E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19331902.03 | 33895261.54 |
August | 0.105485E+10 | 0.407429E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10085731.30 | 45174938.31 |
September | 0.936002E+09 | 0.375007E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3360009.34 | 64267624.82 |
October | 0.973041E+09 | 0.403452E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 807309.96 | 0.117475E+09 |
November | 0.963541E+09 | 0.416723E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191153E+09 |
December | 0.938820E+09 | 0.423796E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222169E+09 |
Annual Sum or Average | 0.116768E+11 | 0.475513E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50084846.66 | 0.165057E+10 |
Minimum of Months | 0.882782E+09 | 0.365097E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33895261.54 |
Maximum of Months | 0.105485E+10 | 0.424936E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19331902.03 | 0.226911E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.666630E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666554E+09 |
February | 0.136985E+10 | 0.584869E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622625E+09 |
March | 0.163685E+10 | 0.662007E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619686E+09 |
April | 0.145243E+10 | 0.571493E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1033313.78 | 0.449101E+09 |
May | 0.157338E+10 | 0.609296E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10208807.07 | 0.312307E+09 |
June | 0.156900E+10 | 0.597398E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51308923.95 | 0.168563E+09 |
July | 0.145680E+10 | 0.565347E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73862940.69 | 95618922.51 |
August | 0.163685E+10 | 0.632503E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37833267.02 | 0.125039E+09 |
September | 0.145243E+10 | 0.583539E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12715589.55 | 0.185176E+09 |
October | 0.150991E+10 | 0.631639E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3006947.88 | 0.335471E+09 |
November | 0.149516E+10 | 0.662129E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536288E+09 |
December | 0.145680E+10 | 0.677592E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607458E+09 |
Annual Sum or Average | 0.181194E+11 | 0.744444E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189970E+09 | 0.472389E+10 |
Minimum of Months | 0.136985E+10 | 0.565347E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95618922.51 |
Maximum of Months | 0.163685E+10 | 0.677592E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73862940.69 | 0.666554E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.425514E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468057E+09 |
February | 0.649041E+09 | 0.374925E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437771E+09 |
March | 0.773965E+09 | 0.425435E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436257E+09 |
April | 0.688021E+09 | 0.369517E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 619958.79 | 0.326019E+09 |
May | 0.744847E+09 | 0.394974E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5735978.23 | 0.222255E+09 |
June | 0.742030E+09 | 0.387367E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32961674.45 | 0.117042E+09 |
July | 0.690839E+09 | 0.365915E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46869232.01 | 70205949.04 |
August | 0.773965E+09 | 0.408823E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23653717.58 | 90903663.78 |
September | 0.688021E+09 | 0.375647E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7483304.80 | 0.132777E+09 |
October | 0.715730E+09 | 0.402769E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1699842.27 | 0.241855E+09 |
November | 0.708685E+09 | 0.425142E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381810E+09 |
December | 0.690839E+09 | 0.431972E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424948E+09 |
Annual Sum or Average | 0.858171E+10 | 0.478800E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119024E+09 | 0.334990E+10 |
Minimum of Months | 0.649041E+09 | 0.365915E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70205949.04 |
Maximum of Months | 0.773965E+09 | 0.431972E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46869232.01 | 0.468057E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.648507E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758719E+09 |
February | 0.136988E+10 | 0.575677E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700801E+09 |
March | 0.163688E+10 | 0.658903E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672528E+09 |
April | 0.145246E+10 | 0.573284E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 978135.28 | 0.480588E+09 |
May | 0.157341E+10 | 0.613065E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9077050.25 | 0.320521E+09 |
June | 0.156904E+10 | 0.601942E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51849045.94 | 0.166358E+09 |
July | 0.145684E+10 | 0.569068E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72899633.76 | 96820169.93 |
August | 0.163688E+10 | 0.634656E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36167691.07 | 0.133219E+09 |
September | 0.145246E+10 | 0.583037E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10233741.85 | 0.205839E+09 |
October | 0.150994E+10 | 0.621349E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1756171.72 | 0.384304E+09 |
November | 0.149520E+10 | 0.645880E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619734E+09 |
December | 0.145684E+10 | 0.651651E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695376E+09 |
Annual Sum or Average | 0.181198E+11 | 0.737702E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182961E+09 | 0.523481E+10 |
Minimum of Months | 0.136988E+10 | 0.569068E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96820169.93 |
Maximum of Months | 0.163688E+10 | 0.658903E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72899633.76 | 0.758719E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.421208E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477676E+09 |
February | 0.882782E+09 | 0.371976E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448707E+09 |
March | 0.105485E+10 | 0.424639E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447966E+09 |
April | 0.936002E+09 | 0.367102E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 651506.50 | 0.334974E+09 |
May | 0.101394E+10 | 0.391649E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5573730.31 | 0.229900E+09 |
June | 0.101113E+10 | 0.385343E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31820405.60 | 0.126213E+09 |
July | 0.938820E+09 | 0.364936E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45372334.15 | 75391082.72 |
August | 0.105485E+10 | 0.407254E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23443076.24 | 98337016.74 |
September | 0.936002E+09 | 0.374783E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7631567.73 | 0.140187E+09 |
October | 0.973041E+09 | 0.403000E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1787407.37 | 0.247904E+09 |
November | 0.963541E+09 | 0.416467E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391406E+09 |
December | 0.938820E+09 | 0.423404E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438501E+09 |
Annual Sum or Average | 0.116768E+11 | 0.475176E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116280E+09 | 0.345716E+10 |
Minimum of Months | 0.882782E+09 | 0.364936E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75391082.72 |
Maximum of Months | 0.105485E+10 | 0.424639E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45372334.15 | 0.477676E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.666579E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752031E+09 |
February | 0.136985E+10 | 0.584846E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717059E+09 |
March | 0.163685E+10 | 0.661976E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720816E+09 |
April | 0.145243E+10 | 0.571488E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1094228.75 | 0.536550E+09 |
May | 0.157338E+10 | 0.609284E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10869924.27 | 0.380632E+09 |
June | 0.156900E+10 | 0.597387E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60920869.47 | 0.208664E+09 |
July | 0.145680E+10 | 0.565338E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87289061.03 | 0.122150E+09 |
August | 0.163685E+10 | 0.632490E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44235169.75 | 0.158124E+09 |
September | 0.145243E+10 | 0.583527E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14550827.93 | 0.227899E+09 |
October | 0.150991E+10 | 0.631619E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3384569.42 | 0.392378E+09 |
November | 0.149516E+10 | 0.662106E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605543E+09 |
December | 0.145680E+10 | 0.677573E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683128E+09 |
Annual Sum or Average | 0.181194E+11 | 0.744421E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222345E+09 | 0.550497E+10 |
Minimum of Months | 0.136985E+10 | 0.565338E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122150E+09 |
Maximum of Months | 0.163685E+10 | 0.677573E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87289061.03 | 0.752031E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.425502E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526946E+09 |
February | 0.882782E+09 | 0.374915E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503732E+09 |
March | 0.105485E+10 | 0.425424E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512240E+09 |
April | 0.936002E+09 | 0.369510E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 706206.11 | 0.393963E+09 |
May | 0.101394E+10 | 0.394969E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6808141.33 | 0.271320E+09 |
June | 0.101113E+10 | 0.387348E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39933412.10 | 0.144558E+09 |
July | 0.938820E+09 | 0.365908E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56584873.79 | 89025926.18 |
August | 0.105485E+10 | 0.408813E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28820447.41 | 0.114032E+09 |
September | 0.936002E+09 | 0.375640E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9160924.22 | 0.162928E+09 |
October | 0.973041E+09 | 0.402764E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2103569.43 | 0.286524E+09 |
November | 0.963541E+09 | 0.425130E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434155E+09 |
December | 0.938820E+09 | 0.431963E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475781E+09 |
Annual Sum or Average | 0.116768E+11 | 0.478789E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144118E+09 | 0.391521E+10 |
Minimum of Months | 0.882782E+09 | 0.365908E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89025926.18 |
Maximum of Months | 0.105485E+10 | 0.431963E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56584873.79 | 0.526946E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.648498E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867311E+09 |
February | 0.136988E+10 | 0.575644E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815794E+09 |
March | 0.163688E+10 | 0.658867E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792377E+09 |
April | 0.145246E+10 | 0.573278E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1054728.42 | 0.577926E+09 |
May | 0.157341E+10 | 0.613056E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10423448.96 | 0.390501E+09 |
June | 0.156904E+10 | 0.601924E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61464569.57 | 0.205702E+09 |
July | 0.145684E+10 | 0.569044E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86583605.75 | 0.123489E+09 |
August | 0.163688E+10 | 0.634647E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43181486.06 | 0.167668E+09 |
September | 0.145246E+10 | 0.582999E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12508594.61 | 0.252611E+09 |
October | 0.150994E+10 | 0.621324E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2404641.22 | 0.456756E+09 |
November | 0.149520E+10 | 0.645869E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718235E+09 |
December | 0.145684E+10 | 0.651645E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794018E+09 |
Annual Sum or Average | 0.181198E+11 | 0.737679E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217621E+09 | 0.616239E+10 |
Minimum of Months | 0.136988E+10 | 0.569044E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123489E+09 |
Maximum of Months | 0.163688E+10 | 0.658867E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86583605.75 | 0.867311E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.421186E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547483E+09 |
February | 0.882782E+09 | 0.371967E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524536E+09 |
March | 0.105485E+10 | 0.424629E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530207E+09 |
April | 0.936002E+09 | 0.367100E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 703633.54 | 0.404386E+09 |
May | 0.101394E+10 | 0.391634E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6526480.25 | 0.280412E+09 |
June | 0.101113E+10 | 0.385337E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38381363.08 | 0.155554E+09 |
July | 0.938820E+09 | 0.364931E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54490944.64 | 94737889.49 |
August | 0.105485E+10 | 0.407246E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28205606.56 | 0.122957E+09 |
September | 0.936002E+09 | 0.374777E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9062044.24 | 0.172000E+09 |
October | 0.973041E+09 | 0.402994E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2081645.47 | 0.295266E+09 |
November | 0.963541E+09 | 0.416479E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453175E+09 |
December | 0.938820E+09 | 0.423399E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502756E+09 |
Annual Sum or Average | 0.116768E+11 | 0.475168E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139452E+09 | 0.408347E+10 |
Minimum of Months | 0.882782E+09 | 0.364931E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94737889.49 |
Maximum of Months | 0.105485E+10 | 0.424629E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54490944.64 | 0.547483E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.274130E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.248656E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.295472E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.263917E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.284801E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.283424E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.265294E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.295472E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.263917E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.274130E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.270917E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.265294E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.328542E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.248656E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.295472E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694903E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637514E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618933E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357489.16 | 0.439815E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7671391.88 | 0.295496E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40003640.25 | 0.158636E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57257098.98 | 93256053.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27902439.34 | 0.121604E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8749507.31 | 0.179595E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1560589.47 | 0.340378E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557638E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643362E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143502E+09 | 0.478113E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93256053.89 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57257098.98 | 0.694903E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118656E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109913E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107470E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 681128.71 | 0.763861E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14860834.93 | 0.519499E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77905229.38 | 0.272157E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114112E+09 | 0.148001E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54444218.49 | 0.203316E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16360652.57 | 0.311211E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2972563.52 | 0.590529E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961505E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108913E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281337E+09 | 0.821960E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148001E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114112E+09 | 0.118656E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118770E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113981E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115250E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26516.73 | 0.860990E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7357803.46 | 0.593514E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68469545.92 | 0.310724E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97945592.09 | 0.177369E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45433789.11 | 0.239341E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10774654.04 | 0.356907E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1412250.09 | 0.632824E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987570E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108612E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231420E+09 | 0.872537E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177369E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97945592.09 | 0.118770E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10174.14 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10174.14 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10174.14 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10174.14 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10174.14 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10174.14 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10174.14 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10174.14 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10174.14 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10174.14 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10174.14 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10174.14 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1004.17 | 09-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 932.57 | 16-JAN-18:00 |
February | 2010.79 | 01-FEB-10:09 | 888.42 | 16-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 695.06 | 05-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 754.15 | 20-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 620.97 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 545.86 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.88 | 29-APR-16:00 | 674.77 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 613.47 | 22-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.29 | 14-MAY-17:00 | 416.42 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 624.30 | 08-JUN-15:00 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.17 | 18-JUN-15:44 | 318.92 | 10-JUN-01:10 |
July | 2010.79 | 03-JUL-09:09 | 620.65 | 07-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.71 | 04-JUL-15:00 | 176.30 | 15-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 545.86 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.90 | 20-AUG-16:51 | 186.21 | 22-AUG-21:40 |
September | 2010.79 | 01-SEP-09:09 | 868.83 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.48 | 03-SEP-14:54 | 243.02 | 18-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 867.48 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.78 | 11-OCT-13:00 | 391.44 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 13-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 701.48 | 26-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 981.72 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.30 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 222.71 | 981.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 651.44 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 624.77 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 560.06 | 16-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 465.78 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 410.74 | 01-MAR-17:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 410.81 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 351.77 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 29-APR-16:00 | 455.69 | 23-APR-09:00 |
May | 1295.83 | 01-MAY-09:09 | 384.68 | 22-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.97 | 14-MAY-16:13 | 275.44 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 402.63 | 08-JUN-15:00 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.58 | 18-JUN-15:44 | 208.81 | 10-JUN-01:10 |
July | 1295.83 | 03-JUL-09:09 | 400.37 | 07-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.47 | 04-JUL-15:00 | 121.22 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.90 | 20-AUG-16:51 | 145.38 | 27-AUG-07:40 |
September | 1295.83 | 01-SEP-09:09 | 549.64 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.91 | 03-SEP-14:54 | 166.83 | 18-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 519.11 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 | 11-OCT-12:58 | 259.99 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 13-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 460.10 | 26-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 645.09 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.22 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 148.47 | 645.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 943.63 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 932.50 | 16-JAN-18:00 |
February | 2010.83 | 01-FEB-10:09 | 878.01 | 16-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 718.27 | 05-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 733.54 | 20-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 628.24 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 545.88 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.88 | 29-APR-16:00 | 681.28 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 615.94 | 22-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.81 | 14-MAY-16:54 | 411.23 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 624.51 | 08-JUN-15:00 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.36 | 18-JUN-15:44 | 312.06 | 10-JUN-01:10 |
July | 2010.83 | 03-JUL-09:09 | 620.71 | 07-JUL-15:00 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.71 | 04-JUL-15:00 | 176.27 | 15-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 545.88 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.32 | 20-AUG-16:51 | 189.95 | 22-AUG-21:40 |
September | 2010.83 | 01-SEP-09:09 | 866.69 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.90 | 03-SEP-14:40 | 256.93 | 18-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 843.47 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 11-OCT-15:00 | 401.18 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 13-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 713.41 | 26-NOV-10:00 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 995.73 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.27 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 222.71 | 995.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 588.60 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 654.97 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 573.48 | 16-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 509.14 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 524.74 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 462.44 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 351.77 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 29-APR-16:00 | 509.48 | 07-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 400.69 | 22-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.81 | 14-MAY-16:53 | 299.35 | 18-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 408.57 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.74 | 18-JUN-16:00 | 250.24 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 396.91 | 07-JUL-15:00 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.48 | 04-JUL-15:00 | 134.06 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.30 | 20-AUG-16:46 | 147.67 | 22-AUG-21:40 |
September | 1295.83 | 01-SEP-09:09 | 562.57 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.13 | 03-SEP-14:54 | 183.10 | 18-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 570.26 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 11-OCT-12:58 | 280.41 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 13-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 512.01 | 26-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 726.93 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.06 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 148.48 | 726.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1002.19 | 09-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1874.70 | 16-JAN-18:00 |
February | 2010.79 | 01-FEB-10:09 | 885.71 | 16-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1431.00 | 05-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 749.67 | 20-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1282.80 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 545.86 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.95 | 29-APR-16:00 | 1461.25 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 608.21 | 22-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.54 | 14-MAY-17:00 | 925.34 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 619.61 | 08-JUN-15:00 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 371.51 | 18-JUN-16:14 | 689.68 | 10-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 615.76 | 07-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 529.82 | 04-JUL-14:54 | 379.47 | 15-JUL-18:55 |
August | 2010.79 | 01-AUG-09:09 | 545.86 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.07 | 20-AUG-16:51 | 366.04 | 22-AUG-22:00 |
September | 2010.79 | 01-SEP-09:09 | 865.94 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.86 | 03-SEP-14:40 | 510.93 | 07-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 864.30 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.40 | 01-OCT-16:00 | 844.47 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 13-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1449.77 | 03-NOV-21:03 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1990.81 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.04 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 529.82 | 1990.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 649.21 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1284.22 | 16-JAN-18:00 |
February | 1239.33 | 01-FEB-08:09 | 555.56 | 16-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 990.73 | 05-FEB-01:00 |
March | 1239.33 | 01-MAR-08:09 | 410.74 | 01-MAR-17:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 885.71 | 14-MAR-03:00 |
April | 1239.33 | 03-APR-07:10 | 351.77 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 | 29-APR-16:00 | 1032.17 | 23-APR-09:20 |
May | 1239.33 | 01-MAY-07:10 | 381.06 | 22-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.07 | 14-MAY-16:13 | 621.57 | 03-MAY-22:00 |
June | 1239.33 | 01-JUN-07:10 | 399.74 | 08-JUN-15:00 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.09 | 18-JUN-16:13 | 465.13 | 10-JUN-01:00 |
July | 1239.33 | 03-JUL-07:10 | 397.36 | 07-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.65 | 04-JUL-14:53 | 274.42 | 15-JUL-18:55 |
August | 1239.33 | 01-AUG-07:10 | 351.77 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.75 | 20-AUG-16:51 | 357.55 | 27-AUG-08:00 |
September | 1239.33 | 01-SEP-07:10 | 545.01 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.16 | 03-SEP-14:23 | 363.49 | 18-SEP-01:00 |
October | 1239.33 | 02-OCT-07:10 | 514.08 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.68 | 11-OCT-13:00 | 570.83 | 11-OCT-23:00 |
November | 1239.33 | 01-NOV-07:10 | 739.33 | 13-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1006.85 | 26-NOV-09:53 |
December | 1239.33 | 01-DEC-08:09 | 739.33 | 01-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1356.74 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.42 | |||||
Maximum of Months | 1239.33 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 360.65 | 1356.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 941.80 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2099.42 | 16-JAN-18:00 |
February | 2010.83 | 01-FEB-10:09 | 875.24 | 16-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1604.73 | 05-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 640.59 | 20-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1371.86 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 545.88 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.95 | 29-APR-16:00 | 1511.07 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 610.79 | 22-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.93 | 14-MAY-16:53 | 920.11 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 619.84 | 08-JUN-15:00 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.76 | 18-JUN-16:14 | 682.96 | 10-JUN-01:20 |
July | 2010.83 | 03-JUL-09:09 | 615.82 | 07-JUL-15:00 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 526.25 | 04-JUL-14:53 | 390.68 | 15-JUL-18:55 |
August | 2010.83 | 01-AUG-09:09 | 545.88 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.57 | 20-AUG-16:54 | 387.13 | 22-AUG-22:00 |
September | 2010.83 | 01-SEP-09:09 | 863.78 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.11 | 03-SEP-14:43 | 571.36 | 18-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 840.15 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.58 | 01-OCT-15:54 | 887.43 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 13-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1631.62 | 26-NOV-09:57 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2169.73 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.13 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 526.25 | 2169.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 585.68 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1339.01 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 569.19 | 16-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1040.77 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 518.79 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 904.62 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 351.77 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 | 29-APR-16:00 | 1074.96 | 15-APR-17:02 |
May | 1295.83 | 01-MAY-09:09 | 397.70 | 22-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.46 | 14-MAY-16:53 | 636.99 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 405.99 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.49 | 18-JUN-16:00 | 511.34 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 393.76 | 07-JUL-15:00 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.94 | 04-JUL-15:00 | 291.22 | 15-JUL-18:55 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.72 | 20-AUG-17:00 | 282.10 | 08-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 557.98 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.39 | 03-SEP-14:23 | 399.28 | 17-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 565.87 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.68 | 11-OCT-13:00 | 592.28 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 13-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1045.24 | 03-NOV-21:10 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1402.50 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.10 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 343.94 | 1402.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1002.12 | 09-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1939.81 | 16-JAN-18:00 |
February | 2010.79 | 01-FEB-10:09 | 885.15 | 16-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1590.50 | 05-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 748.88 | 20-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1475.36 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 545.86 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.87 | 29-APR-16:00 | 1742.29 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 608.00 | 22-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.80 | 14-MAY-16:40 | 1105.93 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 619.43 | 08-JUN-15:00 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.18 | 18-JUN-15:44 | 818.28 | 10-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 615.56 | 07-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 634.24 | 04-JUL-14:54 | 485.61 | 15-JUL-18:55 |
August | 2010.79 | 01-AUG-09:09 | 545.86 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.88 | 20-AUG-16:54 | 451.91 | 22-AUG-22:00 |
September | 2010.79 | 01-SEP-09:09 | 865.34 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.70 | 03-SEP-14:25 | 616.54 | 07-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 863.73 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.71 | 11-OCT-13:00 | 1021.51 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 13-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1728.08 | 03-NOV-21:03 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2256.41 | 14-DEC-04:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.91 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 634.24 | 2256.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 649.05 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1336.75 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 555.19 | 16-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1099.17 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 410.74 | 01-MAR-17:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1026.50 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 351.77 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 | 29-APR-16:00 | 1278.01 | 23-APR-09:10 |
May | 1295.83 | 01-MAY-09:09 | 380.90 | 22-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.20 | 14-MAY-16:24 | 743.09 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 399.63 | 08-JUN-15:00 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.14 | 18-JUN-15:44 | 560.92 | 04-JUN-16:55 |
July | 1295.83 | 03-JUL-09:09 | 397.24 | 07-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 450.05 | 04-JUL-14:54 | 348.60 | 15-JUL-18:55 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.66 | 20-AUG-16:51 | 422.13 | 27-AUG-08:10 |
September | 1295.83 | 01-SEP-09:09 | 544.62 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.75 | 03-SEP-14:23 | 444.77 | 18-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 513.67 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.14 | 11-OCT-13:00 | 690.38 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 13-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1184.09 | 03-NOV-21:03 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1516.63 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.60 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 450.05 | 1516.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 941.45 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2229.69 | 16-JAN-18:00 |
February | 2010.83 | 01-FEB-10:09 | 874.67 | 16-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1811.57 | 05-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 640.45 | 20-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1593.30 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 545.88 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.87 | 29-APR-16:00 | 1811.23 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 610.59 | 22-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.05 | 14-MAY-16:24 | 1098.49 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 619.65 | 08-JUN-15:00 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.04 | 18-JUN-15:44 | 809.55 | 10-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 615.62 | 07-JUL-15:00 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 634.31 | 04-JUL-14:54 | 499.45 | 15-JUL-18:55 |
August | 2010.83 | 01-AUG-09:09 | 545.88 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.88 | 20-AUG-16:54 | 478.08 | 22-AUG-22:00 |
September | 2010.83 | 01-SEP-09:09 | 863.18 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.74 | 03-SEP-14:43 | 697.34 | 18-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 839.55 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.10 | 11-OCT-15:00 | 1075.09 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 13-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1892.08 | 03-NOV-21:03 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2441.22 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.08 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 634.31 | 2441.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 585.44 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1451.23 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 568.83 | 16-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1188.76 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 518.42 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1055.66 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 351.77 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 | 29-APR-16:00 | 1337.49 | 15-APR-17:02 |
May | 1295.83 | 01-MAY-09:09 | 397.58 | 22-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.80 | 19-MAY-15:00 | 765.59 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 405.90 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.55 | 18-JUN-16:00 | 611.93 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 393.63 | 07-JUL-15:00 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.72 | 04-JUL-15:00 | 368.65 | 15-JUL-18:55 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.58 | 20-AUG-17:00 | 349.29 | 08-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 557.61 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.18 | 03-SEP-14:23 | 476.89 | 18-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 565.52 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.14 | 11-OCT-13:00 | 719.85 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 13-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1259.98 | 03-NOV-21:03 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1597.00 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.29 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 421.72 | 1597.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2868.67 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2868.67 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2868.67 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2868.67 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2868.67 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2868.67 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2868.67 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2868.67 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2868.67 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2868.67 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2868.67 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2868.67 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1999.19 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1540.12 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1333.90 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26-APR-15:00 | 1424.83 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.93 | 14-MAY-17:00 | 869.48 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.64 | 18-JUN-16:00 | 674.11 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.31 | 04-JUL-15:00 | 337.40 | 15-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.28 | 05-AUG-17:01 | 370.61 | 22-AUG-22:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.02 | 03-SEP-14:42 | 504.34 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.00 | 01-OCT-15:52 | 807.91 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1539.95 | 26-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2144.08 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.40 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.31 | 2144.08 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3368.03 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2649.58 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2285.13 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 26-APR-15:00 | 2503.52 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.56 | 14-MAY-17:00 | 1541.11 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 640.04 | 18-JUN-16:00 | 1176.48 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837.30 | 04-JUL-15:00 | 566.43 | 15-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.32 | 05-AUG-17:01 | 583.22 | 22-AUG-22:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.79 | 03-SEP-14:50 | 855.01 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.00 | 01-OCT-16:00 | 1405.49 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2632.14 | 26-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3665.22 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.43 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837.30 | 3665.22 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3242.39 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2590.86 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2376.12 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.42 | 13-APR-17:00 | 2723.80 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.95 | 19-MAY-15:00 | 1671.54 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.53 | 18-JUN-16:10 | 1276.46 | 04-JUN-16:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 710.52 | 04-JUL-17:00 | 743.62 | 15-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.50 | 20-AUG-17:00 | 652.65 | 08-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.59 | 03-SEP-14:10 | 972.63 | 17-SEP-19:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.87 | 01-OCT-16:00 | 1555.66 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2790.23 | 03-NOV-21:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3651.42 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.65 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 710.52 | 3651.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 107684.55 | 02-JAN-07:03 | 10771.35 | 10174.29 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 93979.27 | 21-FEB-07:05 | 7180.90 | 6782.86 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96180.06 | 20-MAR-06:11 | 28723.60 | 27131.43 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97796.78 | 17-APR-06:11 | 32314.05 | 30522.86 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 100069.42 | 20-MAY-06:11 | 16157.03 | 10173.84 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 112899.24 | 19-JUN-06:11 | 35904.50 | 33914.29 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 103809.28 | 28-JUL-06:11 | 35904.50 | 33914.29 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 105271.90 | 16-AUG-06:11 | 35904.50 | 33914.29 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 101930.15 | 25-SEP-06:11 | 35904.50 | 33914.29 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 104614.18 | 10-OCT-06:11 | 35904.50 | 33914.29 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 96332.61 | 13-NOV-07:05 | 7180.90 | 6782.86 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 94960.29 | 26-DEC-07:05 | 7180.90 | 6782.86 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93979.27 | 7180.90 | 6782.86 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 112899.24 | 35904.50 | 33914.29 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 80140.89 | 02-JAN-05:01 | 0.00 | 7106.42 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83631.91 | 21-FEB-05:11 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81326.53 | 27-MAR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 83662.53 | 24-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88339.69 | 30-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89197.73 | 23-JUN-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 89737.70 | 08-JUL-04:13 | 0.00 | 3045.61 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87423.18 | 23-AUG-04:23 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87645.59 | 18-SEP-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86382.79 | 11-OCT-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 82627.41 | 24-NOV-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 81115.15 | 04-DEC-04:01 | 0.00 | 4060.81 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 80140.89 | 0.00 | 2686.80 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89737.70 | 0.00 | 7106.42 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 53556.28 | 04-JAN-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 68137.85 | 16-FEB-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 67953.23 | 17-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71369.17 | 14-APR-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73151.62 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74249.87 | 05-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 74657.92 | 14-JUL-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75192.93 | 01-AUG-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 73464.49 | 18-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73217.77 | 03-OCT-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 70766.74 | 01-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 64834.27 | 01-DEC-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 53556.28 | 0.00 | 2149.44 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75192.93 | 9673.43 | 3761.52 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19724.09 | 05-JAN-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31382.50 | 15-FEB-16:20 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32327.98 | 08-MAR-15:00 | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67197.31 | 27-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74676.88 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74830.18 | 05-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82382.78 | 31-JUL-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82640.39 | 07-AUG-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76320.34 | 05-SEP-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72508.76 | 02-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34014.82 | 01-NOV-15:20 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20594.49 | 01-DEC-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19724.09 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82640.39 | 16014.58 | 9137.09 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3806.22 | 02-JAN-13:10 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 |
February | 4629.50 | 21-FEB-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.99 |
March | 6840.97 | 27-MAR-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.64 |
April | 8415.12 | 14-APR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 |
May | 15776.41 | 29-MAY-16:51 | 910.95 | 272.92 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 |
June | 18369.03 | 25-JUN-17:42 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 81.88 | 0.00 |
July | 17904.26 | 23-JUL-13:43 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 144.65 | 0.00 |
August | 15967.21 | 13-AUG-16:21 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 20.18 | 0.00 |
September | 15766.83 | 03-SEP-13:31 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 50.36 | 0.00 |
October | 11167.65 | 10-OCT-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.78 |
November | 4926.06 | 08-NOV-13:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.25 |
December | 3705.52 | 01-DEC-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3705.52 | 0.00 | 242.60 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18369.03 | 3846.22 | 1091.73 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 144.65 | 50.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11305.42 | 01-JAN-09:13 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.35 |
February | 15631.44 | 19-FEB-08:53 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.24 |
March | 19909.24 | 26-MAR-08:32 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.40 |
April | 24591.57 | 30-APR-08:11 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.14 |
May | 24886.71 | 29-MAY-07:31 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.65 |
June | 25475.74 | 25-JUN-08:21 | 652.28 | 195.42 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 |
July | 26489.09 | 23-JUL-08:22 | 652.28 | 195.42 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
August | 23471.46 | 20-AUG-08:21 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 |
September | 24109.34 | 03-SEP-07:31 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 |
October | 23634.19 | 01-OCT-08:41 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.11 |
November | 15956.14 | 05-NOV-08:23 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.29 |
December | 7467.83 | 29-DEC-09:15 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7467.83 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | |
Maximum of Months | 26489.09 | 2478.65 | 703.55 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23924.40 | 29-JAN-13:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.17 |
February | 23489.99 | 12-FEB-14:51 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.22 |
March | 23327.44 | 26-MAR-12:31 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.07 |
April | 22049.18 | 30-APR-12:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.38 |
May | 20616.20 | 28-MAY-13:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 |
June | 20719.89 | 25-JUN-13:41 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 41.32 | 0.00 |
July | 23112.41 | 23-JUL-13:43 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 141.43 | 0.00 |
August | 21475.61 | 20-AUG-12:22 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 20.64 | 0.00 |
September | 23166.14 | 03-SEP-10:51 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 0.00 |
October | 24196.30 | 01-OCT-14:41 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.72 |
November | 22923.97 | 19-NOV-13:01 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.13 |
December | 24129.99 | 31-DEC-11:11 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20616.20 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24196.30 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 141.43 | 147.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18690.25 | 22-JAN-15:21 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.99 |
February | 27262.45 | 12-FEB-14:51 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.99 |
March | 28156.60 | 26-MAR-14:31 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.32 |
April | 29668.01 | 16-APR-16:31 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 |
May | 31015.37 | 07-MAY-15:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.87 |
June | 32809.35 | 11-JUN-16:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.40 |
July | 33058.72 | 30-JUL-15:41 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 0.00 |
August | 30896.87 | 20-AUG-15:42 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.90 | 0.00 |
September | 27824.07 | 24-SEP-16:21 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.22 |
October | 30131.97 | 01-OCT-15:21 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 |
November | 26482.10 | 19-NOV-15:01 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.15 |
December | 27914.95 | 31-DEC-15:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18690.25 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33058.72 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 34.90 | 154.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2079.83 | 05-JAN-15:50 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.03 |
February | 2732.88 | 15-FEB-15:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 |
March | 4583.09 | 27-MAR-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.91 |
April | 7237.85 | 14-APR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 |
May | 10021.57 | 22-MAY-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.58 |
June | 15806.47 | 18-JUN-18:12 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 159.68 | 0.00 |
July | 15464.35 | 02-JUL-18:01 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 128.27 | 0.00 |
August | 14768.62 | 13-AUG-17:31 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 38.73 | 0.00 |
September | 14412.37 | 04-SEP-17:11 | 0.00 | 272.92 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 |
October | 8515.85 | 11-OCT-12:53 | 7692.44 | 2183.45 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 66.93 | 0.00 |
November | 2989.31 | 03-NOV-13:40 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.11 |
December | 1936.06 | 29-DEC-16:10 | 1923.11 | 843.09 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1936.06 | 0.00 | 272.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15806.47 | 7692.44 | 2183.45 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 159.68 | 94.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5761.87 | 27-JAN-09:40 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12667.27 | 19-FEB-10:02 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.71 |
March | 19099.66 | 26-MAR-09:32 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.58 |
April | 26315.80 | 30-APR-08:61 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.35 |
May | 27267.94 | 29-MAY-09:01 | 652.28 | 195.42 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.77 |
June | 27688.15 | 18-JUN-08:51 | 652.28 | 195.42 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.49 |
July | 27661.45 | 16-JUL-08:41 | 652.28 | 195.42 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.03 |
August | 26605.16 | 13-AUG-08:11 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.74 |
September | 25351.43 | 17-SEP-09:21 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.62 |
October | 24378.59 | 01-OCT-08:11 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.91 |
November | 13470.72 | 23-NOV-10:02 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5431.62 | 29-DEC-09:25 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5431.62 | 260.91 | 78.17 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27688.15 | 2478.65 | 703.55 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22520.51 | 01-JAN-14:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.95 |
February | 22807.47 | 19-FEB-11:21 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.73 |
March | 23103.32 | 12-MAR-13:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.59 |
April | 21455.70 | 30-APR-13:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.57 |
May | 19880.15 | 21-MAY-13:02 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 |
June | 19513.52 | 18-JUN-15:31 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 319.71 | 0.00 |
July | 21494.17 | 30-JUL-12:32 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 | 0.00 |
August | 21526.12 | 13-AUG-12:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 | 0.00 |
September | 23198.74 | 17-SEP-13:21 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.25 |
October | 25518.27 | 01-OCT-12:11 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.42 |
November | 23742.30 | 12-NOV-11:41 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.90 |
December | 23914.18 | 24-DEC-12:31 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19513.52 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25518.27 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 319.71 | 592.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9228.73 | 26-JAN-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.15 |
February | 13456.33 | 15-FEB-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.27 |
March | 26913.55 | 12-MAR-16:21 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.41 |
April | 26160.30 | 16-APR-16:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.63 |
May | 28680.53 | 14-MAY-16:11 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.01 |
June | 30377.52 | 18-JUN-16:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 0.00 |
July | 30017.03 | 30-JUL-16:31 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 52.22 | 0.00 |
August | 28884.81 | 13-AUG-16:11 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
September | 28621.07 | 24-SEP-16:41 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.82 |
October | 27427.90 | 01-OCT-15:31 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 |
November | 23664.11 | 12-NOV-15:01 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.39 |
December | 8384.66 | 31-DEC-16:02 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8384.66 | 326.14 | 97.71 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30377.52 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 52.22 | 146.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1978.34 | 05-JAN-15:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.06 |
February | 2445.54 | 15-FEB-15:50 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.54 |
March | 3923.40 | 16-MAR-14:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.27 |
April | 7605.90 | 14-APR-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 |
May | 13282.65 | 29-MAY-16:31 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.09 |
June | 17815.93 | 11-JUN-18:01 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 |
July | 17873.91 | 04-JUL-16:51 | 910.95 | 272.92 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 554.54 | 0.00 |
August | 17704.88 | 13-AUG-17:31 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 36.56 | 0.00 |
September | 17598.30 | 04-SEP-16:01 | 910.95 | 272.92 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.12 |
October | 8420.53 | 11-OCT-12:53 | 7692.44 | 2183.45 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 79.62 | 0.00 |
November | 2313.89 | 01-NOV-15:10 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.39 |
December | 1841.09 | 29-DEC-15:50 | 1923.11 | 605.23 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1841.09 | 0.00 | 242.60 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17873.91 | 7692.44 | 2183.45 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 554.54 | 291.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3497.59 | 27-JAN-10:00 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7367.07 | 14-FEB-09:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.91 |
March | 19094.78 | 26-MAR-09:21 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.18 |
April | 23664.03 | 30-APR-09:02 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.03 |
May | 24554.23 | 29-MAY-09:11 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.01 |
June | 26526.27 | 11-JUN-08:61 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.41 |
July | 26913.99 | 09-JUL-08:11 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.91 |
August | 26901.33 | 13-AUG-08:11 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.32 |
September | 24532.97 | 03-SEP-09:01 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.77 |
October | 22917.29 | 01-OCT-09:02 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.21 |
November | 8788.61 | 01-NOV-09:10 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.39 |
December | 3238.65 | 29-DEC-09:25 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3238.65 | 391.37 | 117.25 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26913.99 | 2591.66 | 703.55 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25705.54 | 22-JAN-13:51 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.83 |
February | 25596.71 | 12-FEB-14:51 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.64 |
March | 25006.58 | 26-MAR-14:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.21 |
April | 22214.58 | 30-APR-13:02 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.53 |
May | 22113.76 | 21-MAY-13:13 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 |
June | 21650.82 | 25-JUN-15:51 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 164.14 | 0.00 |
July | 22734.59 | 30-JUL-14:02 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 127.64 | 0.00 |
August | 24004.60 | 13-AUG-12:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 |
September | 25284.66 | 17-SEP-12:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.91 |
October | 27499.53 | 09-OCT-13:11 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.92 |
November | 25044.26 | 12-NOV-15:01 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.95 |
December | 25007.68 | 31-DEC-13:51 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 21650.82 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27499.53 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 164.14 | 353.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8536.69 | 26-JAN-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.75 |
February | 13391.52 | 15-FEB-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.37 |
March | 26753.83 | 12-MAR-16:31 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.60 |
April | 27599.32 | 16-APR-16:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.10 |
May | 30438.23 | 07-MAY-16:21 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.03 |
June | 32257.34 | 11-JUN-16:41 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.05 |
July | 30286.58 | 04-JUL-16:51 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.69 | 0.00 |
August | 31340.71 | 13-AUG-16:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 | 0.00 |
September | 30578.00 | 24-SEP-16:11 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.63 |
October | 28530.02 | 09-OCT-16:31 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.36 |
November | 12733.64 | 12-NOV-15:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.62 |
December | 7245.31 | 29-DEC-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7245.31 | 456.59 | 136.80 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32257.34 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 264.69 | 192.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7890.68 | 02-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.28 |
February | 4997.42 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.90 |
March | 6000.66 | 27-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.65 |
April | 6560.44 | 03-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.38 |
May | 10809.10 | 30-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.28 |
June | 14473.53 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.11 |
July | 17369.17 | 24-JUL-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.59 |
August | 15282.61 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 |
September | 13942.46 | 05-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.49 |
October | 12340.15 | 10-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 |
November | 5251.67 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 |
December | 3546.20 | 18-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3546.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.59 | |
Maximum of Months | 17369.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8517.62 | 17-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2041.06 |
February | 8901.35 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1878.87 |
March | 3888.79 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.81 |
April | 4774.94 | 28-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.43 | 0.00 |
May | 5967.03 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 | 0.00 |
June | 7335.64 | 28-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 |
July | 9416.41 | 24-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 |
August | 8200.23 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.56 |
September | 8593.39 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.93 |
October | 6124.35 | 02-OCT-09:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.87 |
November | 6743.46 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.04 |
December | 7892.67 | 22-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1041.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3888.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 | 2041.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2754.16 | 15-JAN-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.54 |
February | 6489.26 | 15-FEB-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.79 |
March | 9610.08 | 08-MAR-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.77 |
April | 15155.53 | 28-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 |
May | 18173.90 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 0.00 |
June | 24508.36 | 28-JUN-13:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 0.00 |
July | 22094.58 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.97 | 0.00 |
August | 20631.39 | 07-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 | 0.00 |
September | 19785.54 | 01-SEP-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 | 0.00 |
October | 17389.68 | 02-OCT-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.13 |
November | 5581.49 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.85 |
December | 2723.87 | 24-DEC-14:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2723.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24508.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.97 | 586.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2580.33 | 01-JAN-16:45 | 46.77 | 32.52 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4347.96 | 15-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7096.80 | 31-MAR-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8414.63 | 16-APR-18:20 | 0.00 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3513.36 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5453.19 | 30-JUN-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7364.58 | 31-JUL-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7970.49 | 27-AUG-18:37 | 0.00 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3484.46 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5289.47 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6478.98 | 05-NOV-16:50 | 11.69 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8206.14 | 31-DEC-16:34 | 58.46 | 40.65 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2580.33 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8414.63 | 222.14 | 146.32 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2235.85 | 26-JAN-17:00 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4134.50 | 15-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6592.35 | 31-MAR-23:30 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8021.80 | 16-APR-18:10 | 0.00 | 56.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3290.72 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5136.23 | 30-JUN-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6964.91 | 31-JUL-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7638.62 | 30-AUG-17:50 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3289.01 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4878.18 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5916.03 | 02-NOV-16:50 | 70.15 | 81.29 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7500.43 | 29-DEC-16:50 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2235.85 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8021.80 | 222.14 | 146.32 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2133.29 | 26-JAN-17:00 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4154.32 | 15-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6268.74 | 31-MAR-23:20 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8160.03 | 16-APR-18:00 | 0.00 | 56.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3216.40 | 31-MAY-23:50 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5124.29 | 30-JUN-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7000.85 | 04-JUL-18:35 | 0.00 | 65.03 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7769.39 | 30-AUG-17:40 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3236.35 | 30-SEP-23:40 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4655.87 | 31-OCT-23:30 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5908.36 | 02-NOV-16:50 | 70.15 | 81.29 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7407.64 | 29-DEC-16:50 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2133.29 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8160.03 | 222.14 | 146.32 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92207.47 | 02-JAN-17:00 | 4808.68 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182873.61 | 15-FEB-17:00 | 4808.68 | 2868.67 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358503.50 | 31-MAR-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366476.30 | 17-APR-16:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176154.88 | 31-MAY-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268787.50 | 30-JUN-23:55 | 0.00 | 318.73 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 361084.44 | 31-JUL-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 376867.55 | 13-AUG-13:42 | 1518.53 | 956.20 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176474.29 | 30-SEP-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268474.74 | 31-OCT-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275949.87 | 20-NOV-17:00 | 4808.68 | 2868.67 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367251.65 | 26-DEC-17:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92207.47 | 0.00 | 159.37 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 376867.55 | 4808.68 | 2868.67 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.157092E+13 | 1063996.32 | 09-JAN-16:00 | 0.197220E+12 | 728838.58 | 21-JAN-07:10 |
February | 0.178235E+13 | 1374031.27 | 14-FEB-16:40 | 0.121776E+12 | 679888.24 | 06-FEB-07:10 |
March | 0.238334E+13 | 1556777.52 | 08-MAR-16:30 | 0.394840E+11 | 378143.79 | 30-MAR-06:10 |
April | 0.274320E+13 | 1820246.22 | 28-APR-15:09 | 0.679012E+10 | 231832.48 | 08-APR-06:10 |
May | 0.178158E+13 | 1357435.55 | 16-MAY-15:20 | 0.121337E+10 | 104220.96 | 06-MAY-06:10 |
June | 0.223625E+13 | 1618071.33 | 27-JUN-15:20 | 3352526.78 | 2756.08 | 09-JUN-06:10 |
July | 0.274225E+13 | 1784879.13 | 21-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.318729E+13 | 1923249.04 | 08-AUG-15:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.167539E+13 | 1381923.70 | 01-SEP-10:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.206032E+13 | 1477318.32 | 05-OCT-15:30 | 0.229781E+11 | 407762.71 | 26-OCT-06:10 |
November | 0.225108E+13 | 1410052.53 | 02-NOV-15:09 | 0.538179E+11 | 512025.40 | 27-NOV-07:10 |
December | 0.261027E+13 | 1471791.21 | 29-DEC-16:00 | 0.192590E+12 | 700323.37 | 15-DEC-07:10 |
Annual Sum or Average | 0.270243E+14 | 0.635874E+12 | ||||
Minimum of Months | 0.157092E+13 | 1063996.32 | 0.00 | 0.00 | ||
Maximum of Months | 0.318729E+13 | 1923249.04 | 0.197220E+12 | 728838.58 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.309939E+11 | 62111.19 | 19-JAN-12:30 | 0.00 | 0.00 |
February | 0.372592E+11 | 75039.34 | 24-FEB-12:30 | 0.00 | 0.00 |
March | 0.502014E+11 | 83372.76 | 25-MAR-12:09 | 0.00 | 0.00 |
April | 0.640648E+11 | 89495.83 | 24-APR-11:09 | 0.00 | 0.00 |
May | 0.689245E+11 | 89495.83 | 01-MAY-12:09 | 0.00 | 0.00 |
June | 0.685975E+11 | 89495.83 | 09-JUN-12:50 | 0.00 | 0.00 |
July | 0.684214E+11 | 86536.08 | 12-JUL-11:30 | 0.00 | 0.00 |
August | 0.649971E+11 | 85841.97 | 07-AUG-12:00 | 0.00 | 0.00 |
September | 0.528672E+11 | 81911.75 | 13-SEP-12:30 | 0.00 | 0.00 |
October | 0.434712E+11 | 72612.81 | 13-OCT-11:39 | 0.00 | 0.00 |
November | 0.322321E+11 | 65151.23 | 01-NOV-11:50 | 0.00 | 0.00 |
December | 0.285848E+11 | 53905.19 | 14-DEC-12:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.610615E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.285848E+11 | 53905.19 | 0.00 | 0.00 | |
Maximum of Months | 0.689245E+11 | 89495.83 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.144390E+12 | 0.291364E+11 | 0.766053E+12 | 0.136274E+12 | 0.196251E+12 | 0.211884E+11 | 0.00 | 0.245558E+11 | 0.124969E+10 | 0.212613E+12 | 0.00 | 0.392123E+11 | 0.00 |
February | 0.130331E+12 | 0.238094E+11 | 0.978954E+12 | 0.124863E+12 | 0.181686E+12 | 0.215865E+11 | 0.00 | 0.427587E+11 | 0.446077E+10 | 0.238003E+12 | 0.00 | 0.358978E+11 | 0.00 |
March | 0.153712E+12 | 0.228313E+11 | 0.141687E+13 | 0.144887E+12 | 0.216855E+12 | 0.269988E+11 | 0.00 | 0.776631E+11 | 0.157632E+11 | 0.266576E+12 | 0.00 | 0.411859E+11 | 0.00 |
April | 0.136614E+12 | 0.187498E+11 | 0.165903E+13 | 0.135268E+12 | 0.242393E+12 | 0.319814E+11 | 0.00 | 0.178498E+12 | 0.463097E+11 | 0.258912E+12 | 0.00 | 0.354548E+11 | 0.00 |
May | 0.147160E+12 | 0.166381E+11 | 0.774844E+12 | 0.140580E+12 | 0.260978E+12 | 0.374513E+11 | 0.00 | 0.121035E+12 | 0.587867E+11 | 0.188812E+12 | 0.00 | 0.352926E+11 | 0.00 |
June | 0.146120E+12 | 0.150332E+11 | 0.106252E+13 | 0.139647E+12 | 0.286761E+12 | 0.531063E+11 | 0.00 | 0.295712E+12 | 0.942413E+11 | 0.110582E+12 | 0.00 | 0.325298E+11 | 0.00 |
July | 0.137018E+12 | 0.159855E+11 | 0.139340E+13 | 0.136200E+12 | 0.305604E+12 | 0.633437E+11 | 0.00 | 0.490404E+12 | 0.139241E+12 | 0.316142E+11 | 0.00 | 0.294330E+11 | 0.00 |
August | 0.152658E+12 | 0.182064E+11 | 0.173200E+13 | 0.144887E+12 | 0.306934E+12 | 0.631480E+11 | 0.00 | 0.556057E+12 | 0.134271E+12 | 0.472561E+11 | 0.00 | 0.318760E+11 | 0.00 |
September | 0.137042E+12 | 0.205644E+11 | 0.740713E+12 | 0.135267E+12 | 0.254128E+12 | 0.452098E+11 | 0.00 | 0.167434E+12 | 0.806342E+11 | 0.644784E+11 | 0.00 | 0.299192E+11 | 0.00 |
October | 0.143152E+12 | 0.248835E+11 | 0.108340E+13 | 0.136274E+12 | 0.235301E+12 | 0.345141E+11 | 0.00 | 0.114475E+12 | 0.398000E+11 | 0.215645E+12 | 0.00 | 0.328785E+11 | 0.00 |
November | 0.142848E+12 | 0.273234E+11 | 0.135889E+13 | 0.131109E+12 | 0.207438E+12 | 0.242347E+11 | 0.00 | 0.624368E+11 | 0.507695E+10 | 0.257037E+12 | 0.00 | 0.346889E+11 | 0.00 |
December | 0.140852E+12 | 0.300317E+11 | 0.170972E+13 | 0.136200E+12 | 0.200820E+12 | 0.238610E+11 | 0.00 | 0.604739E+11 | 0.368729E+10 | 0.267840E+12 | 0.00 | 0.367843E+11 | 0.00 |
Annual Sum or Average | 0.171190E+13 | 0.263193E+12 | 0.146764E+14 | 0.164146E+13 | 0.289515E+13 | 0.446624E+12 | 0.00 | 0.219150E+13 | 0.623522E+12 | 0.215937E+13 | 0.00 | 0.415153E+12 | 0.00 |
Minimum of Months | 0.130331E+12 | 0.150332E+11 | 0.740713E+12 | 0.124863E+12 | 0.181686E+12 | 0.211884E+11 | 0.00 | 0.245558E+11 | 0.124969E+10 | 0.316142E+11 | 0.00 | 0.294330E+11 | 0.00 |
Maximum of Months | 0.153712E+12 | 0.300317E+11 | 0.173200E+13 | 0.144887E+12 | 0.306934E+12 | 0.633437E+11 | 0.00 | 0.556057E+12 | 0.139241E+12 | 0.267840E+12 | 0.00 | 0.411859E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.197220E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.121776E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.394840E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.679012E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.121337E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3352526.78 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.229781E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.538179E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.192590E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.635874E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.197220E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 162474.38 | 04-JAN-16:00 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 154946.65 | 03-JAN-08:20 | 126649.47 | 03-JAN-16:49 | 20552.81 | 17-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 159084.56 | 16-FEB-08:09 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 154950.89 | 16-FEB-08:20 | 156264.28 | 15-FEB-16:00 | 37924.54 | 14-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 152128.77 | 20-MAR-07:10 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 154947.24 | 20-MAR-07:19 | 178724.99 | 08-MAR-16:30 | 21373.88 | 13-MAR-14:50 | 0.00 | 01-MAR-00:10 |
April | 145987.23 | 03-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 154944.03 | 03-APR-07:19 | 234613.22 | 28-APR-15:09 | 39023.38 | 13-APR-13:39 | 0.00 | 01-APR-00:10 |
May | 148433.29 | 22-MAY-07:10 | 31088.59 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 154945.31 | 22-MAY-07:19 | 258126.70 | 30-MAY-14:30 | 40315.27 | 23-MAY-09:00 | 0.00 | 01-MAY-00:10 |
June | 148889.42 | 08-JUN-15:00 | 22480.63 | 01-JUN-19:10 | 541788.89 | 01-JUN-07:10 | 154945.13 | 08-JUN-07:19 | 319236.56 | 27-JUN-15:20 | 44609.35 | 27-JUN-14:50 | 0.00 | 01-JUN-00:10 |
July | 148731.48 | 07-JUL-15:00 | 31088.59 | 19-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 154944.03 | 03-JUL-07:19 | 319236.56 | 06-JUL-08:20 | 44627.75 | 06-JUL-08:20 | 0.00 | 01-JUL-00:10 |
August | 145987.23 | 01-AUG-07:10 | 31088.59 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 154944.03 | 01-AUG-07:19 | 321036.89 | 03-AUG-08:50 | 45510.51 | 31-AUG-09:39 | 0.00 | 01-AUG-00:10 |
September | 158449.44 | 08-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 154950.56 | 08-SEP-07:19 | 319236.56 | 01-SEP-10:09 | 45656.92 | 18-SEP-13:39 | 0.00 | 01-SEP-00:10 |
October | 157870.59 | 25-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 154950.26 | 25-OCT-07:19 | 276271.24 | 11-OCT-12:50 | 45662.44 | 10-OCT-11:39 | 0.00 | 01-OCT-00:10 |
November | 169722.15 | 13-NOV-16:00 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 154952.78 | 02-NOV-07:19 | 157174.87 | 03-NOV-15:00 | 22677.84 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 169722.15 | 01-DEC-16:00 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 154949.01 | 08-DEC-08:20 | 130066.87 | 20-DEC-16:30 | 20393.99 | 29-DEC-15:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 145987.23 | 22480.63 | 423497.50 | 154944.03 | 126649.47 | 20393.99 | 0.00 | |||||||
Maximum of Months | 169722.15 | 31088.59 | 778371.69 | 154952.78 | 321036.89 | 45662.44 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 70866.32 | 05-JAN-15:39 | 3065.68 | 05-JAN-15:00 | 100000.00 | 01-JAN-10:50 | 0.00 | 52205.20 | 31-JAN-12:30 | 0.00 | 01-JAN-00:10 |
February | 199759.15 | 14-FEB-16:40 | 44897.85 | 14-FEB-15:30 | 100000.00 | 01-FEB-05:19 | 0.00 | 52232.51 | 07-FEB-12:39 | 0.00 | 01-FEB-00:10 |
March | 221931.09 | 08-MAR-15:00 | 44934.97 | 08-MAR-14:30 | 100000.00 | 01-MAR-05:10 | 0.00 | 51897.54 | 01-MAR-12:30 | 0.00 | 01-MAR-00:10 |
April | 310866.97 | 13-APR-16:49 | 46791.04 | 27-APR-12:00 | 100000.00 | 01-APR-04:19 | 0.00 | 49335.04 | 03-APR-11:39 | 0.00 | 01-APR-00:10 |
May | 233101.72 | 19-MAY-16:30 | 58780.60 | 22-MAY-12:20 | 100000.00 | 02-MAY-21:19 | 0.00 | 46407.79 | 01-MAY-11:00 | 0.00 | 01-MAY-00:10 |
June | 341392.56 | 28-JUN-14:50 | 73784.96 | 06-JUN-12:00 | 100000.00 | 03-JUN-17:40 | 0.00 | 43123.75 | 01-JUN-11:39 | 0.00 | 01-JUN-00:10 |
July | 384619.90 | 31-JUL-14:00 | 73784.96 | 22-JUL-10:20 | 100000.00 | 03-JUL-21:19 | 0.00 | 40025.43 | 03-JUL-11:39 | 0.00 | 01-JUL-00:10 |
August | 404994.86 | 16-AUG-15:09 | 73784.96 | 01-AUG-09:30 | 100000.00 | 15-AUG-21:19 | 0.00 | 39465.77 | 31-AUG-11:50 | 0.00 | 01-AUG-00:10 |
September | 311812.07 | 05-SEP-14:09 | 73784.96 | 01-SEP-10:50 | 100000.00 | 26-SEP-21:19 | 0.00 | 41462.95 | 29-SEP-11:50 | 0.00 | 01-SEP-00:10 |
October | 277430.07 | 02-OCT-12:09 | 73784.96 | 02-OCT-13:39 | 100000.00 | 05-OCT-04:19 | 0.00 | 44848.77 | 31-OCT-11:20 | 0.00 | 01-OCT-00:10 |
November | 132957.11 | 02-NOV-15:09 | 43954.68 | 09-NOV-13:00 | 100000.00 | 01-NOV-06:00 | 0.00 | 47775.29 | 30-NOV-12:20 | 0.00 | 01-NOV-00:10 |
December | 69598.00 | 29-DEC-15:00 | 3591.45 | 24-DEC-14:00 | 100000.00 | 01-DEC-08:09 | 0.00 | 50983.57 | 29-DEC-12:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 69598.00 | 3065.68 | 100000.00 | 0.00 | 39465.77 | 0.00 | |||||
Maximum of Months | 404994.86 | 73784.96 | 100000.00 | 0.00 | 52232.51 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1063996.32 | 09-JAN-16:00 | 161050.80 | 423497.50 | 0.00 | 154853.96 | 120223.37 | 20267.00 | 0.00 | 43238.54 | 1342.30 |
February | 1374031.27 | 14-FEB-16:40 | 145987.23 | 541788.89 | 0.00 | 154849.24 | 125241.66 | 21568.10 | 0.00 | 199759.15 | 44846.10 |
March | 1556777.52 | 08-MAR-16:30 | 145987.23 | 660080.29 | 0.00 | 154849.24 | 178724.99 | 20828.48 | 0.00 | 212159.54 | 44740.21 |
April | 1820246.22 | 28-APR-15:09 | 145987.23 | 778371.69 | 0.00 | 154849.24 | 234613.22 | 37169.40 | 0.00 | 287759.85 | 46360.31 |
May | 1357435.55 | 16-MAY-15:20 | 145987.23 | 423497.50 | 0.00 | 154849.24 | 227773.19 | 37153.60 | 0.00 | 188818.59 | 44816.46 |
June | 1618071.33 | 27-JUN-15:20 | 145987.23 | 541788.89 | 0.00 | 154849.24 | 319236.56 | 44607.89 | 0.00 | 326319.57 | 48373.02 |
July | 1784879.13 | 21-JUL-15:50 | 145987.23 | 660080.29 | 0.00 | 154849.24 | 319236.56 | 44609.46 | 0.00 | 376680.96 | 47856.59 |
August | 1923249.04 | 08-AUG-15:20 | 145987.23 | 778371.69 | 0.00 | 154849.24 | 287042.22 | 40045.66 | 0.00 | 395821.94 | 73784.96 |
September | 1381923.70 | 01-SEP-10:30 | 145987.23 | 423497.50 | 0.00 | 154722.86 | 292827.81 | 44474.88 | 0.00 | 227524.00 | 60403.68 |
October | 1477318.32 | 05-OCT-15:30 | 145987.23 | 541788.89 | 0.00 | 154849.24 | 168187.02 | 37979.03 | 0.00 | 248007.41 | 48507.67 |
November | 1410052.53 | 02-NOV-15:09 | 145987.23 | 660080.29 | 0.00 | 154849.24 | 133437.83 | 20975.44 | 0.00 | 132957.11 | 28147.96 |
December | 1471791.21 | 29-DEC-16:00 | 169722.15 | 778371.69 | 31088.59 | 154860.37 | 120335.06 | 20258.97 | 0.00 | 55451.06 | 2594.83 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1063996.32 | 145987.23 | 423497.50 | 0.00 | 154722.86 | 120223.37 | 20258.97 | 0.00 | 43238.54 | 1342.30 | |
Maximum of Months | 1923249.04 | 169722.15 | 778371.69 | 31088.59 | 154860.37 | 319236.56 | 44609.46 | 0.00 | 395821.94 | 73784.96 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 728838.58 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 679888.24 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 378143.79 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 231832.48 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 104220.96 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2756.08 | 09-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 407762.71 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 512025.40 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 700323.37 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 728838.58 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 87.17 | 27.27 | 39.33 | 27.22 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 64.50 | 26.45 | 26.00 | 26.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 | 26.24 | 29.00 | 26.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 | 26.38 | 26.50 | 26.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 160.50 | 27.16 | 105.83 | 27.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 441.67 | 28.70 | 304.17 | 28.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 733.83 | 29.11 | 486.83 | 29.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 570.00 | 28.43 | 380.00 | 28.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 263.50 | 27.43 | 160.17 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 182.17 | 27.40 | 89.33 | 27.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 91.00 | 26.98 | 35.00 | 26.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 84.83 | 26.71 | 36.50 | 26.71 |
Annual Sum or Average | 0.00 | 0.00 | 2782.83 | 28.16 | 1718.67 | 28.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 | 26.24 | 26.00 | 26.23 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 733.83 | 29.11 | 486.83 | 29.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.61 | 0.00 | 26.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.56 | 0.00 | 25.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.59 | 0.00 | 25.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 25.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 25.30 | 3.67 | 25.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 25.65 | 2.67 | 25.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.84 | 0.67 | 25.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.36 | 0.33 | 25.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.23 | 0.83 | 25.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
Annual Sum or Average | 0.00 | 0.00 | 25.17 | 25.57 | 8.17 | 25.39 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.23 | 0.00 | 25.08 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 26.61 | 3.67 | 26.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.06 | 0.17 | 24.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 25.06 | 0.17 | 24.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.06 | 0.17 | 24.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
February | 0.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.64 | 0.33 | 24.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
December | 0.33 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
Annual Sum or Average | 1.17 | 19.19 | 0.00 | 19.19 | 0.33 | 20.40 | 0.33 | 21.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.31 | 0.00 | 19.31 | 0.33 | 24.64 | 0.33 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 25.81 | 19.33 | 25.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 26.57 | 21.00 | 26.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 26.29 | 13.00 | 26.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.81 | 2.67 | 26.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 75.50 | 26.27 | 56.00 | 26.21 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 26.81 | 21.00 | 26.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.75 | 0.83 | 27.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.73 | 1.00 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.14 | 2.67 | 28.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.15 | 6.00 | 28.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.19 | 11.33 | 28.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 26.69 | 22.83 | 26.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 27.19 | 30.50 | 27.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.14 | 17.00 | 27.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.70 | 9.17 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.92 | 7.83 | 27.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.73 | 2.17 | 27.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.46 | 0.33 | 27.46 |
Annual Sum or Average | 0.00 | 0.00 | 130.67 | 27.33 | 111.67 | 27.37 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.69 | 0.33 | 26.69 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 28.19 | 30.50 | 28.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 25.76 | 36.33 | 25.76 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 25.67 | 25.83 | 25.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.71 | 5.50 | 27.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.73 | 5.17 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.55 | 5.50 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.53 | 7.83 | 26.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 27.36 | 12.50 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 26.29 | 22.00 | 26.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 26.07 | 29.83 | 26.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 67.17 | 25.72 | 66.33 | 25.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 | 25.63 | 55.00 | 25.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 42.17 | 25.47 | 42.17 | 25.47 |
Annual Sum or Average | 0.00 | 0.00 | 332.67 | 25.97 | 314.00 | 25.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.47 | 5.17 | 25.47 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 67.17 | 27.73 | 66.33 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.85 | 3.17 | 27.85 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.00 | 2.83 | 28.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.57 | 3.83 | 28.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.77 | 10.83 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.09 | 6.33 | 28.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 27.34 | 18.00 | 27.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 64.33 | 27.47 | 30.17 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 63.17 | 27.49 | 22.33 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 28.02 | 8.00 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.06 | 6.17 | 28.30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.17 | 5.83 | 28.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.18 | 3.50 | 28.18 |
Annual Sum or Average | 0.00 | 0.00 | 233.83 | 27.63 | 121.00 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.34 | 2.83 | 27.30 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 64.33 | 28.57 | 30.17 | 28.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
February | 0.67 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.10 | 2.00 | 27.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.22 | 4.83 | 27.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.39 | 2.00 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
December | 1.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Annual Sum or Average | 3.00 | 19.24 | 0.00 | 19.24 | 11.83 | 25.61 | 8.83 | 26.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.41 | 0.00 | 19.41 | 6.17 | 27.39 | 4.83 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
February | 0.67 | 19.13 | 0.00 | 19.13 | 0.50 | 22.75 | 0.50 | 24.19 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.07 | 2.33 | 28.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.18 | 6.00 | 28.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.32 | 11.67 | 28.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.23 | 10.83 | 28.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 28.16 | 18.50 | 28.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 28.33 | 11.00 | 28.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.83 | 9.33 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.94 | 6.50 | 27.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.41 | 1.00 | 27.41 |
December | 0.67 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Annual Sum or Average | 2.33 | 19.26 | 0.00 | 19.26 | 84.00 | 27.91 | 77.67 | 28.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.26 | 0.00 | 19.26 |
Maximum of Months | 1.00 | 19.37 | 0.00 | 19.37 | 21.83 | 28.33 | 18.50 | 28.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.31 | 0.00 | 19.31 | 59.33 | 25.87 | 59.33 | 25.89 |
February | 0.33 | 19.25 | 0.00 | 19.25 | 45.00 | 25.65 | 45.00 | 25.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 25.85 | 15.50 | 25.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.75 | 4.00 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.53 | 4.83 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.48 | 3.50 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.69 | 9.33 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.46 | 8.67 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 25.67 | 50.67 | 25.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 96.17 | 25.84 | 95.00 | 25.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 77.00 | 25.81 | 77.00 | 25.81 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 71.17 | 25.53 | 71.17 | 25.53 |
Annual Sum or Average | 0.67 | 19.28 | 0.00 | 19.28 | 449.50 | 25.88 | 444.00 | 25.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 25.53 | 3.50 | 25.53 |
Maximum of Months | 0.33 | 19.31 | 0.00 | 19.31 | 96.17 | 27.75 | 95.00 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.31 | 0.00 | 19.31 | 0.50 | 24.13 | 0.50 | 25.34 |
February | 0.33 | 19.12 | 0.00 | 19.12 | 1.00 | 25.53 | 1.00 | 26.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.28 | 2.83 | 28.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.58 | 3.33 | 28.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.37 | 5.00 | 28.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.27 | 6.67 | 28.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.99 | 10.00 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.22 | 5.67 | 28.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.30 | 5.83 | 28.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.54 | 3.83 | 28.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.72 | 1.67 | 27.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.61 | 0.17 | 27.61 |
Annual Sum or Average | 0.67 | 19.22 | 0.00 | 19.22 | 77.00 | 28.15 | 46.50 | 28.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.13 | 0.17 | 25.34 |
Maximum of Months | 0.33 | 19.31 | 0.00 | 19.31 | 18.50 | 28.58 | 10.00 | 28.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.00 | 17.91 | 1.17 | 18.12 | 0.00 | 18.12 | 0.00 | 18.12 |
February | 8.33 | 17.91 | 1.00 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
March | 0.83 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.29 | 1.00 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.14 | 4.50 | 27.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.63 | 8.33 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.58 | 4.83 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.41 | 2.00 | 27.42 |
October | 0.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
November | 3.83 | 18.94 | 0.33 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
December | 10.17 | 18.19 | 0.67 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
Annual Sum or Average | 35.67 | 18.15 | 3.17 | 18.32 | 27.33 | 22.10 | 20.67 | 23.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.00 | 19.27 | 1.17 | 19.27 | 11.17 | 27.63 | 8.33 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
February | 5.67 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
March | 0.67 | 19.06 | 0.00 | 19.06 | 1.33 | 24.91 | 1.33 | 26.09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.06 | 5.00 | 28.06 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.33 | 11.50 | 28.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 28.40 | 10.33 | 28.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 28.31 | 18.33 | 28.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 28.39 | 10.83 | 28.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.88 | 9.50 | 27.89 |
October | 0.33 | 19.19 | 0.00 | 19.19 | 5.00 | 27.31 | 5.00 | 27.58 |
November | 1.67 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
December | 8.33 | 18.07 | 0.00 | 18.07 | 0.00 | 18.07 | 0.00 | 18.07 |
Annual Sum or Average | 25.33 | 18.00 | 0.00 | 18.00 | 83.67 | 25.86 | 71.83 | 26.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 0.00 | 17.68 |
Maximum of Months | 8.67 | 19.19 | 0.00 | 19.19 | 23.33 | 28.40 | 18.33 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.83 | 18.40 | 0.00 | 18.40 | 24.67 | 24.36 | 24.67 | 24.99 |
February | 3.33 | 18.80 | 0.00 | 18.80 | 22.17 | 24.67 | 22.17 | 25.08 |
March | 0.50 | 19.25 | 0.00 | 19.25 | 4.00 | 27.17 | 3.83 | 27.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.76 | 3.33 | 27.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.71 | 5.33 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.50 | 4.83 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.86 | 10.17 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.07 | 7.17 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 26.08 | 33.00 | 26.05 |
October | 0.17 | 19.08 | 0.00 | 19.08 | 63.00 | 25.75 | 61.83 | 25.74 |
November | 0.67 | 18.63 | 0.00 | 18.63 | 38.33 | 25.52 | 38.33 | 25.58 |
December | 6.50 | 18.63 | 0.00 | 18.63 | 14.17 | 23.68 | 14.17 | 24.63 |
Annual Sum or Average | 17.00 | 18.61 | 0.00 | 18.61 | 239.33 | 25.66 | 228.83 | 25.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 23.68 | 3.33 | 24.63 |
Maximum of Months | 6.50 | 19.25 | 0.00 | 19.25 | 63.00 | 28.07 | 61.83 | 28.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
February | 2.50 | 18.64 | 0.00 | 18.64 | 0.33 | 19.70 | 0.33 | 20.53 |
March | 0.17 | 19.18 | 0.00 | 19.18 | 2.67 | 27.78 | 2.17 | 28.02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.56 | 3.33 | 28.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.39 | 5.50 | 28.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 28.12 | 8.67 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.97 | 12.00 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 28.30 | 6.67 | 28.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.34 | 6.33 | 28.43 |
October | 0.17 | 19.23 | 0.00 | 19.23 | 4.67 | 28.22 | 3.67 | 28.42 |
November | 0.67 | 18.56 | 0.00 | 18.56 | 0.67 | 22.96 | 0.67 | 24.42 |
December | 6.67 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
Annual Sum or Average | 15.67 | 18.67 | 0.00 | 18.67 | 83.33 | 26.71 | 49.33 | 27.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 | 0.00 | 18.65 |
Maximum of Months | 6.67 | 19.23 | 0.00 | 19.23 | 21.17 | 28.56 | 12.00 | 28.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.01 | 1.83 | 28.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 28.12 | 16.67 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 29.17 | 28.10 | 18.50 | 28.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 28.12 | 16.67 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.04 | 1.67 | 28.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.18 | 5.50 | 28.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.00 | 28.15 | 7.17 | 28.11 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.18 | 5.50 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.92 | 1.33 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 28.38 | 6.50 | 28.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.83 | 28.30 | 7.83 | 28.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 28.38 | 6.50 | 28.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 42.17 | 28.18 | 38.50 | 28.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 42.17 | 28.18 | 38.50 | 28.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 42.17 | 28.18 | 38.50 | 28.19 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 206.83 | 24.34 | 93.67 | 25.05 | 13.33 | 25.23 |
February | 167.67 | 24.00 | 86.17 | 24.79 | 0.00 | 24.79 |
March | 156.17 | 24.00 | 88.00 | 24.82 | 0.00 | 24.82 |
April | 168.00 | 24.00 | 99.83 | 24.91 | 0.00 | 24.91 |
May | 133.83 | 25.57 | 225.00 | 26.02 | 58.83 | 26.24 |
June | 277.33 | 28.95 | 436.00 | 28.10 | 277.33 | 28.33 |
July | 454.33 | 29.39 | 497.00 | 29.20 | 454.33 | 29.26 |
August | 338.50 | 28.68 | 509.17 | 27.88 | 338.50 | 28.11 |
September | 114.83 | 27.56 | 396.00 | 26.15 | 114.83 | 26.41 |
October | 90.67 | 26.00 | 220.00 | 26.20 | 44.33 | 26.44 |
November | 83.33 | 24.05 | 129.17 | 25.58 | 1.00 | 25.59 |
December | 193.67 | 24.00 | 107.00 | 24.93 | 0.00 | 24.93 |
Annual Sum or Average | 2385.17 | 26.63 | 2887.00 | 26.89 | 1302.50 | 27.27 |
Minimum of Months | 83.33 | 24.00 | 86.17 | 24.79 | 0.00 | 24.79 |
Maximum of Months | 454.33 | 29.39 | 509.17 | 29.20 | 454.33 | 29.26 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 269.50 | 24.00 | 21.33 | 24.15 | 0.00 | 24.15 |
February | 176.50 | 24.00 | 24.33 | 24.21 | 0.00 | 24.21 |
March | 157.00 | 24.01 | 32.17 | 24.34 | 0.00 | 24.34 |
April | 136.83 | 24.01 | 35.50 | 24.38 | 0.00 | 24.38 |
May | 95.83 | 24.00 | 131.67 | 24.50 | 1.33 | 24.49 |
June | 0.00 | 0.00 | 344.00 | 24.49 | 0.00 | 24.49 |
July | 94.00 | 25.22 | 492.67 | 24.62 | 94.00 | 24.70 |
August | 47.50 | 24.55 | 512.17 | 24.36 | 47.50 | 24.38 |
September | 13.50 | 24.00 | 377.33 | 24.46 | 13.50 | 24.45 |
October | 71.83 | 24.00 | 170.00 | 24.65 | 0.00 | 24.65 |
November | 112.00 | 24.00 | 56.50 | 24.60 | 0.00 | 24.60 |
December | 203.50 | 24.01 | 40.00 | 24.36 | 0.00 | 24.36 |
Annual Sum or Average | 1378.00 | 24.11 | 2237.67 | 24.44 | 156.33 | 24.46 |
Minimum of Months | 0.00 | 0.00 | 21.33 | 24.15 | 0.00 | 24.15 |
Maximum of Months | 269.50 | 25.22 | 512.17 | 24.65 | 94.00 | 24.70 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.83 | 23.60 | 0.00 | 23.60 | 0.00 | 23.60 |
February | 408.17 | 23.73 | 0.00 | 23.73 | 0.00 | 23.73 |
March | 383.00 | 23.90 | 1.00 | 23.91 | 0.00 | 23.91 |
April | 339.17 | 23.99 | 1.83 | 24.00 | 0.00 | 24.00 |
May | 203.17 | 23.99 | 79.67 | 24.12 | 1.50 | 24.12 |
June | 27.17 | 23.99 | 224.00 | 24.28 | 0.00 | 24.28 |
July | 162.17 | 24.20 | 461.17 | 24.24 | 162.17 | 24.23 |
August | 109.50 | 24.21 | 471.83 | 24.23 | 109.50 | 24.23 |
September | 23.17 | 24.19 | 314.67 | 24.34 | 18.83 | 24.33 |
October | 205.00 | 23.92 | 93.83 | 24.09 | 2.00 | 24.09 |
November | 384.83 | 23.87 | 1.67 | 23.88 | 0.00 | 23.88 |
December | 492.83 | 23.62 | 0.00 | 23.62 | 0.00 | 23.62 |
Annual Sum or Average | 3237.00 | 23.83 | 1649.67 | 23.99 | 294.00 | 24.00 |
Minimum of Months | 23.17 | 23.60 | 0.00 | 23.60 | 0.00 | 23.60 |
Maximum of Months | 498.83 | 24.21 | 471.83 | 24.34 | 162.17 | 24.33 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.90 | 138.17 | 21.58 | 138.17 | 21.37 |
February | 452.00 | 22.50 | 49.50 | 22.31 | 49.50 | 22.16 |
March | 495.67 | 23.35 | 6.33 | 23.32 | 6.33 | 23.29 |
April | 365.17 | 23.76 | 1.17 | 23.77 | 0.00 | 23.77 |
May | 207.17 | 23.84 | 77.17 | 24.02 | 2.17 | 24.02 |
June | 30.33 | 23.85 | 255.50 | 24.29 | 0.00 | 24.29 |
July | 163.33 | 24.24 | 473.67 | 24.30 | 163.33 | 24.29 |
August | 104.00 | 24.27 | 483.83 | 24.28 | 104.00 | 24.28 |
September | 45.17 | 23.96 | 303.67 | 24.29 | 21.50 | 24.27 |
October | 305.83 | 23.42 | 78.00 | 23.59 | 2.67 | 23.59 |
November | 462.17 | 22.81 | 26.83 | 22.71 | 26.83 | 22.61 |
December | 497.00 | 21.88 | 144.33 | 21.58 | 144.33 | 21.39 |
Annual Sum or Average | 3629.83 | 22.93 | 2038.17 | 23.19 | 658.83 | 23.08 |
Minimum of Months | 30.33 | 21.88 | 1.17 | 21.58 | 0.00 | 21.37 |
Maximum of Months | 502.00 | 24.27 | 483.83 | 24.30 | 163.33 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.33 | 22.60 | 13.83 | 22.56 | 13.83 | 22.52 |
February | 441.00 | 23.00 | 8.33 | 22.96 | 8.33 | 22.92 |
March | 440.67 | 23.56 | 0.00 | 23.56 | 0.00 | 23.56 |
April | 258.50 | 23.91 | 17.00 | 24.03 | 0.00 | 24.03 |
May | 136.17 | 23.93 | 130.17 | 24.37 | 1.50 | 24.37 |
June | 14.83 | 26.73 | 382.17 | 24.63 | 13.50 | 24.71 |
July | 105.00 | 25.86 | 495.17 | 24.83 | 105.00 | 24.98 |
August | 59.33 | 25.51 | 509.83 | 24.53 | 59.33 | 24.62 |
September | 41.17 | 24.57 | 342.50 | 24.49 | 18.67 | 24.53 |
October | 258.17 | 23.62 | 115.67 | 23.89 | 0.00 | 23.89 |
November | 459.33 | 23.44 | 0.00 | 23.44 | 0.00 | 23.44 |
December | 497.00 | 22.86 | 4.00 | 22.85 | 4.00 | 22.83 |
Annual Sum or Average | 3210.50 | 23.40 | 2018.67 | 23.82 | 224.17 | 23.88 |
Minimum of Months | 14.83 | 22.60 | 0.00 | 22.56 | 0.00 | 22.52 |
Maximum of Months | 499.33 | 26.73 | 509.83 | 24.83 | 105.00 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 421.50 | 22.87 | 34.17 | 22.98 | 12.17 | 22.94 |
February | 342.67 | 23.11 | 36.17 | 23.24 | 7.50 | 23.21 |
March | 290.00 | 23.55 | 73.50 | 23.81 | 5.67 | 23.87 |
April | 162.50 | 24.16 | 143.50 | 24.55 | 14.33 | 24.67 |
May | 122.83 | 24.86 | 247.17 | 24.81 | 36.00 | 25.01 |
June | 53.17 | 26.48 | 424.33 | 24.77 | 50.50 | 24.95 |
July | 124.00 | 26.04 | 495.33 | 24.96 | 124.00 | 25.14 |
August | 81.33 | 25.80 | 510.17 | 24.64 | 81.33 | 24.78 |
September | 61.33 | 26.00 | 404.67 | 24.73 | 49.00 | 24.90 |
October | 191.33 | 23.91 | 205.33 | 24.39 | 17.33 | 24.50 |
November | 344.83 | 23.43 | 35.83 | 23.62 | 2.33 | 23.65 |
December | 433.67 | 22.94 | 23.17 | 22.95 | 14.17 | 22.89 |
Annual Sum or Average | 2629.17 | 23.70 | 2633.33 | 24.16 | 414.33 | 24.29 |
Minimum of Months | 53.17 | 22.87 | 23.17 | 22.95 | 2.33 | 22.89 |
Maximum of Months | 433.67 | 26.48 | 510.17 | 24.96 | 124.00 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 311.17 | 23.11 | 156.67 | 23.62 | 43.83 | 23.69 |
February | 243.83 | 23.30 | 147.67 | 23.80 | 21.83 | 23.86 |
March | 259.83 | 23.65 | 112.00 | 23.97 | 9.83 | 24.05 |
April | 174.83 | 23.89 | 106.67 | 24.30 | 4.00 | 24.35 |
May | 147.33 | 24.08 | 155.67 | 24.47 | 14.00 | 24.57 |
June | 28.67 | 25.32 | 359.33 | 24.56 | 13.33 | 24.64 |
July | 102.50 | 25.80 | 494.00 | 24.79 | 102.50 | 24.94 |
August | 64.67 | 25.75 | 511.83 | 24.61 | 64.67 | 24.72 |
September | 67.50 | 25.95 | 402.17 | 24.85 | 56.00 | 25.01 |
October | 167.50 | 24.50 | 278.17 | 24.82 | 53.83 | 25.02 |
November | 245.17 | 23.99 | 172.50 | 24.50 | 31.17 | 24.68 |
December | 286.17 | 23.30 | 163.33 | 23.82 | 27.50 | 23.91 |
Annual Sum or Average | 2099.17 | 23.90 | 3060.00 | 24.37 | 442.50 | 24.49 |
Minimum of Months | 28.67 | 23.11 | 106.67 | 23.62 | 4.00 | 23.69 |
Maximum of Months | 311.17 | 25.95 | 511.83 | 24.85 | 102.50 | 25.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 378.67 | 23.45 | 52.00 | 23.65 | 3.33 | 23.68 |
February | 230.83 | 23.86 | 93.67 | 24.17 | 5.67 | 24.22 |
March | 112.17 | 24.40 | 136.00 | 24.79 | 13.83 | 24.92 |
April | 40.17 | 25.97 | 235.33 | 25.36 | 24.50 | 25.51 |
May | 63.83 | 25.17 | 288.17 | 24.90 | 24.67 | 25.04 |
June | 44.33 | 26.83 | 457.50 | 24.82 | 44.33 | 24.99 |
July | 166.67 | 25.92 | 497.00 | 25.04 | 166.67 | 25.22 |
August | 137.83 | 25.77 | 514.00 | 24.84 | 137.83 | 25.01 |
September | 47.67 | 26.50 | 431.00 | 24.83 | 47.67 | 24.99 |
October | 90.00 | 24.69 | 264.50 | 24.85 | 20.50 | 24.98 |
November | 134.83 | 24.32 | 121.50 | 24.68 | 12.83 | 24.81 |
December | 226.67 | 24.12 | 98.00 | 24.41 | 7.67 | 24.48 |
Annual Sum or Average | 1673.67 | 24.54 | 3188.67 | 24.71 | 509.50 | 24.86 |
Minimum of Months | 40.17 | 23.45 | 52.00 | 23.65 | 3.33 | 23.68 |
Maximum of Months | 378.67 | 26.83 | 514.00 | 25.36 | 166.67 | 25.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.08 | 280.17 | 20.88 | 280.17 | 20.79 |
February | 454.00 | 21.56 | 138.50 | 21.34 | 138.50 | 21.20 |
March | 511.67 | 22.64 | 40.33 | 22.50 | 40.33 | 22.39 |
April | 405.17 | 23.45 | 1.33 | 23.44 | 1.33 | 23.43 |
May | 220.17 | 23.70 | 87.33 | 23.99 | 1.17 | 23.99 |
June | 23.50 | 24.05 | 317.33 | 24.43 | 2.83 | 24.45 |
July | 139.00 | 24.87 | 486.83 | 24.57 | 139.00 | 24.62 |
August | 78.33 | 24.56 | 482.33 | 24.37 | 76.67 | 24.39 |
September | 82.67 | 23.80 | 277.50 | 24.22 | 16.33 | 24.24 |
October | 373.67 | 22.85 | 75.83 | 22.97 | 15.67 | 22.90 |
November | 482.67 | 21.94 | 87.33 | 21.75 | 87.33 | 21.61 |
December | 497.00 | 20.92 | 322.00 | 20.78 | 322.00 | 20.72 |
Annual Sum or Average | 3769.83 | 22.31 | 2596.83 | 22.64 | 1121.33 | 22.46 |
Minimum of Months | 23.50 | 20.92 | 1.33 | 20.78 | 1.17 | 20.72 |
Maximum of Months | 511.67 | 24.87 | 486.83 | 24.57 | 322.00 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 403.83 | 22.00 | 113.17 | 21.74 | 110.33 | 21.55 |
February | 333.50 | 22.32 | 66.17 | 22.18 | 55.00 | 22.00 |
March | 301.50 | 23.03 | 59.00 | 23.28 | 11.67 | 23.27 |
April | 172.00 | 23.90 | 117.17 | 24.44 | 13.00 | 24.56 |
May | 140.00 | 24.72 | 186.67 | 24.87 | 39.83 | 25.11 |
June | 49.00 | 26.25 | 326.00 | 24.87 | 37.17 | 25.06 |
July | 128.67 | 25.80 | 412.67 | 25.01 | 128.67 | 25.16 |
August | 80.50 | 25.77 | 418.00 | 24.75 | 79.83 | 24.89 |
September | 72.33 | 25.42 | 305.17 | 24.79 | 46.33 | 24.97 |
October | 207.67 | 23.46 | 152.50 | 24.04 | 23.67 | 24.13 |
November | 341.00 | 22.71 | 43.50 | 22.74 | 25.00 | 22.61 |
December | 412.67 | 21.91 | 145.50 | 21.59 | 144.50 | 21.40 |
Annual Sum or Average | 2642.67 | 23.09 | 2345.50 | 23.59 | 715.00 | 23.59 |
Minimum of Months | 49.00 | 21.91 | 43.50 | 21.59 | 11.67 | 21.40 |
Maximum of Months | 412.67 | 26.25 | 418.00 | 25.01 | 144.50 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 342.67 | 22.95 | 202.17 | 23.36 | 108.33 | 23.35 |
February | 265.17 | 22.99 | 168.50 | 23.55 | 51.00 | 23.58 |
March | 292.50 | 23.17 | 116.33 | 23.59 | 15.00 | 23.67 |
April | 224.00 | 23.53 | 78.83 | 23.91 | 3.33 | 23.95 |
May | 190.67 | 23.81 | 125.50 | 24.22 | 11.83 | 24.31 |
June | 58.50 | 24.16 | 289.17 | 24.42 | 9.33 | 24.48 |
July | 139.50 | 25.04 | 479.17 | 24.62 | 139.50 | 24.70 |
August | 82.67 | 25.16 | 491.83 | 24.52 | 82.67 | 24.60 |
September | 87.50 | 25.49 | 374.00 | 24.85 | 62.83 | 25.01 |
October | 209.17 | 24.35 | 271.67 | 24.81 | 77.00 | 25.03 |
November | 279.33 | 23.71 | 182.83 | 24.32 | 61.83 | 24.51 |
December | 309.17 | 22.80 | 215.17 | 23.26 | 92.67 | 23.17 |
Annual Sum or Average | 2480.83 | 23.59 | 2995.17 | 24.13 | 715.33 | 24.21 |
Minimum of Months | 58.50 | 22.80 | 78.83 | 23.26 | 3.33 | 23.17 |
Maximum of Months | 342.67 | 25.49 | 491.83 | 24.85 | 139.50 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 432.67 | 21.85 | 140.00 | 21.69 | 124.83 | 21.52 |
February | 358.33 | 22.27 | 99.17 | 22.31 | 57.50 | 22.14 |
March | 375.17 | 23.14 | 71.67 | 23.33 | 15.83 | 23.36 |
April | 236.33 | 23.92 | 104.17 | 24.19 | 17.50 | 24.34 |
May | 132.00 | 24.23 | 212.50 | 24.52 | 21.00 | 24.67 |
June | 41.50 | 25.73 | 388.00 | 24.68 | 26.00 | 24.82 |
July | 154.67 | 25.11 | 496.00 | 24.72 | 154.67 | 24.79 |
August | 90.00 | 25.10 | 510.67 | 24.56 | 90.00 | 24.63 |
September | 60.50 | 25.33 | 369.33 | 24.67 | 39.83 | 24.79 |
October | 237.00 | 23.40 | 170.17 | 23.87 | 16.50 | 23.97 |
November | 373.83 | 22.69 | 64.50 | 22.82 | 20.67 | 22.74 |
December | 434.00 | 21.84 | 144.33 | 21.65 | 136.67 | 21.49 |
Annual Sum or Average | 2926.00 | 22.97 | 2770.50 | 23.53 | 721.00 | 23.50 |
Minimum of Months | 41.50 | 21.84 | 64.50 | 21.65 | 15.83 | 21.49 |
Maximum of Months | 434.00 | 25.73 | 510.67 | 24.72 | 154.67 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.37 | 395.67 | 20.22 | 395.67 | 20.17 |
February | 454.00 | 20.89 | 274.00 | 20.66 | 274.00 | 20.56 |
March | 513.00 | 22.08 | 132.00 | 21.77 | 132.00 | 21.56 |
April | 402.83 | 23.05 | 33.17 | 22.91 | 31.00 | 22.77 |
May | 231.00 | 23.41 | 84.67 | 23.75 | 5.83 | 23.72 |
June | 45.67 | 24.18 | 319.50 | 24.43 | 9.67 | 24.49 |
July | 151.83 | 24.92 | 484.33 | 24.59 | 151.83 | 24.66 |
August | 91.00 | 24.72 | 478.50 | 24.40 | 85.50 | 24.46 |
September | 125.33 | 23.64 | 259.17 | 24.12 | 22.50 | 24.16 |
October | 399.17 | 22.37 | 123.00 | 22.35 | 68.83 | 22.16 |
November | 487.00 | 21.15 | 248.17 | 20.85 | 248.17 | 20.70 |
December | 497.00 | 20.27 | 440.00 | 20.19 | 440.00 | 20.17 |
Annual Sum or Average | 3899.83 | 21.83 | 3272.17 | 22.08 | 1865.00 | 21.84 |
Minimum of Months | 45.67 | 20.27 | 33.17 | 20.19 | 5.83 | 20.17 |
Maximum of Months | 513.00 | 24.92 | 484.33 | 24.59 | 440.00 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.37 | 267.17 | 21.00 | 267.17 | 20.83 |
February | 424.67 | 21.89 | 141.50 | 21.49 | 140.00 | 21.24 |
March | 366.33 | 22.70 | 89.33 | 22.64 | 55.00 | 22.45 |
April | 180.67 | 23.52 | 136.50 | 24.05 | 17.17 | 24.05 |
May | 155.17 | 24.46 | 226.33 | 24.65 | 41.67 | 24.86 |
June | 61.50 | 25.92 | 401.50 | 24.71 | 42.50 | 24.91 |
July | 161.33 | 25.44 | 488.33 | 24.84 | 161.33 | 24.96 |
August | 99.50 | 25.42 | 499.67 | 24.62 | 97.17 | 24.74 |
September | 93.67 | 24.93 | 366.83 | 24.58 | 51.00 | 24.75 |
October | 251.67 | 23.04 | 184.17 | 23.51 | 39.50 | 23.43 |
November | 442.00 | 22.27 | 101.17 | 21.98 | 95.50 | 21.75 |
December | 497.00 | 21.16 | 272.33 | 20.79 | 272.33 | 20.62 |
Annual Sum or Average | 3235.50 | 22.59 | 3174.83 | 23.01 | 1280.33 | 22.86 |
Minimum of Months | 61.50 | 21.16 | 89.33 | 20.79 | 17.17 | 20.62 |
Maximum of Months | 502.00 | 25.92 | 499.67 | 24.84 | 272.33 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 351.67 | 21.93 | 249.33 | 22.13 | 158.50 | 21.91 |
February | 284.33 | 22.12 | 199.17 | 22.42 | 102.67 | 22.19 |
March | 328.50 | 22.65 | 148.67 | 22.80 | 67.17 | 22.65 |
April | 244.33 | 23.11 | 102.83 | 23.39 | 26.33 | 23.27 |
May | 221.50 | 23.58 | 132.33 | 23.99 | 20.33 | 24.05 |
June | 74.33 | 23.97 | 294.00 | 24.37 | 12.50 | 24.45 |
July | 146.83 | 25.01 | 477.33 | 24.62 | 146.83 | 24.69 |
August | 89.83 | 25.07 | 486.67 | 24.51 | 85.67 | 24.60 |
September | 113.83 | 24.88 | 356.50 | 24.69 | 63.17 | 24.86 |
October | 225.00 | 23.60 | 272.83 | 24.16 | 77.17 | 24.23 |
November | 291.00 | 22.70 | 193.67 | 23.15 | 75.00 | 23.05 |
December | 330.17 | 21.84 | 243.83 | 22.00 | 147.67 | 21.73 |
Annual Sum or Average | 2701.33 | 22.94 | 3157.17 | 23.49 | 983.00 | 23.40 |
Minimum of Months | 74.33 | 21.84 | 102.83 | 22.00 | 12.50 | 21.73 |
Maximum of Months | 351.67 | 25.07 | 486.67 | 24.69 | 158.50 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 452.67 | 21.16 | 256.83 | 20.86 | 255.00 | 20.70 |
February | 375.00 | 21.63 | 179.17 | 21.50 | 146.00 | 21.28 |
March | 397.67 | 22.59 | 125.50 | 22.60 | 74.00 | 22.44 |
April | 260.67 | 23.50 | 112.17 | 23.79 | 26.83 | 23.87 |
May | 159.50 | 23.90 | 205.83 | 24.33 | 23.67 | 24.47 |
June | 61.00 | 25.15 | 381.17 | 24.64 | 32.17 | 24.79 |
July | 175.83 | 25.05 | 494.33 | 24.71 | 175.83 | 24.78 |
August | 104.50 | 25.05 | 506.83 | 24.56 | 104.50 | 24.63 |
September | 90.00 | 24.71 | 347.83 | 24.57 | 43.17 | 24.71 |
October | 274.50 | 22.90 | 188.00 | 23.31 | 47.83 | 23.26 |
November | 404.83 | 22.01 | 135.67 | 21.85 | 103.83 | 21.61 |
December | 452.00 | 21.17 | 269.50 | 20.87 | 267.50 | 20.73 |
Annual Sum or Average | 3208.17 | 22.49 | 3202.83 | 22.96 | 1300.33 | 22.81 |
Minimum of Months | 61.00 | 21.16 | 112.17 | 20.86 | 23.67 | 20.70 |
Maximum of Months | 452.67 | 25.15 | 506.83 | 24.71 | 267.50 | 24.79 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 27.00 | 502.00 | 27.00 | 1.67 | 27.00 |
February | 5.17 | 27.00 | 454.00 | 27.00 | 5.17 | 27.00 |
March | 16.83 | 27.00 | 514.00 | 27.00 | 16.83 | 27.00 |
April | 35.17 | 27.10 | 485.00 | 27.01 | 35.17 | 27.02 |
May | 2.67 | 27.00 | 508.00 | 27.00 | 2.67 | 27.00 |
June | 39.33 | 27.00 | 496.00 | 27.00 | 39.33 | 27.00 |
July | 165.67 | 27.00 | 497.00 | 27.00 | 165.67 | 27.00 |
August | 253.00 | 27.12 | 514.00 | 27.08 | 253.00 | 27.09 |
September | 16.33 | 27.00 | 485.00 | 27.00 | 16.33 | 27.00 |
October | 28.50 | 27.00 | 502.00 | 27.00 | 28.50 | 27.00 |
November | 18.33 | 27.00 | 489.00 | 27.00 | 18.33 | 27.00 |
December | 18.00 | 27.01 | 497.00 | 27.00 | 18.00 | 27.00 |
Annual Sum or Average | 600.67 | 27.06 | 5943.00 | 27.01 | 600.67 | 27.01 |
Minimum of Months | 1.67 | 27.00 | 454.00 | 27.00 | 1.67 | 27.00 |
Maximum of Months | 253.00 | 27.12 | 514.00 | 27.08 | 253.00 | 27.09 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 474.50 | 27.00 | 0.00 | 27.00 |
February | 0.33 | 27.00 | 442.50 | 27.00 | 0.33 | 27.00 |
March | 2.50 | 27.00 | 514.00 | 27.00 | 2.50 | 27.00 |
April | 8.50 | 27.28 | 485.00 | 27.01 | 8.50 | 27.02 |
May | 0.50 | 27.00 | 508.00 | 27.00 | 0.50 | 27.00 |
June | 7.33 | 27.00 | 496.00 | 27.00 | 7.33 | 27.00 |
July | 14.50 | 27.00 | 497.00 | 27.00 | 14.50 | 27.00 |
August | 44.00 | 27.31 | 514.00 | 27.05 | 44.00 | 27.07 |
September | 6.17 | 27.00 | 485.00 | 27.00 | 6.17 | 27.00 |
October | 9.33 | 27.00 | 502.00 | 27.00 | 9.33 | 27.00 |
November | 1.00 | 27.00 | 489.00 | 27.00 | 1.00 | 27.00 |
December | 0.00 | 0.00 | 476.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 94.17 | 27.17 | 5883.00 | 27.01 | 94.17 | 27.01 |
Minimum of Months | 0.00 | 0.00 | 442.50 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 44.00 | 27.31 | 514.00 | 27.05 | 44.00 | 27.07 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 73.50 | 25.72 | 281.17 | 26.74 | 0.00 | 26.74 |
February | 7.67 | 27.00 | 344.83 | 27.00 | 0.50 | 27.00 |
March | 3.17 | 27.00 | 485.50 | 27.00 | 3.17 | 27.00 |
April | 9.83 | 27.17 | 485.00 | 27.01 | 9.83 | 27.01 |
May | 2.17 | 27.00 | 505.50 | 27.00 | 2.17 | 27.00 |
June | 23.00 | 27.00 | 496.00 | 27.00 | 23.00 | 27.00 |
July | 61.67 | 27.00 | 497.00 | 27.00 | 61.67 | 27.00 |
August | 79.00 | 27.19 | 514.00 | 27.05 | 79.00 | 27.07 |
September | 13.67 | 27.00 | 485.00 | 27.00 | 13.67 | 27.00 |
October | 12.83 | 27.00 | 489.17 | 27.00 | 12.83 | 27.00 |
November | 1.00 | 27.00 | 434.00 | 27.00 | 1.00 | 27.00 |
December | 5.83 | 27.00 | 322.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 293.33 | 26.74 | 5340.00 | 26.99 | 206.83 | 26.99 |
Minimum of Months | 1.00 | 25.72 | 281.17 | 26.74 | 0.00 | 26.74 |
Maximum of Months | 79.00 | 27.19 | 514.00 | 27.05 | 79.00 | 27.07 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.83 | 27.00 | 502.00 | 27.00 | 491.83 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 394.67 | 27.00 | 508.00 | 27.00 | 394.67 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.12 | 514.00 | 27.12 | 514.00 | 27.12 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5819.50 | 27.01 | 5943.00 | 27.01 | 5819.50 | 27.01 |
Minimum of Months | 394.67 | 27.00 | 454.00 | 27.00 | 394.67 | 27.00 |
Maximum of Months | 514.00 | 27.12 | 514.00 | 27.12 | 514.00 | 27.12 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 16.94563 | 0.73056 | 16.33347 |
February | 454.00000 | 27.00001 | 17.45222 | 0.78562 | 18.09927 |
March | 514.00000 | 27.00001 | 18.10914 | 0.83889 | 19.91485 |
April | 485.00000 | 27.00739 | 16.85835 | 0.88558 | 21.62644 |
May | 508.00000 | 27.00018 | 20.15101 | 0.15300 | 5.59954 |
June | 496.00000 | 27.00041 | 24.18542 | 0.26594 | 6.57261 |
July | 497.00000 | 27.00051 | 26.42527 | 0.35207 | 7.65913 |
August | 514.00000 | 27.06139 | 26.09532 | 0.39150 | 8.40239 |
September | 485.00000 | 27.00073 | 25.44112 | 0.21383 | 6.04826 |
October | 502.00000 | 27.00025 | 20.89624 | 0.85473 | 20.52309 |
November | 489.00000 | 27.00004 | 18.22520 | 0.84010 | 19.96671 |
December | 497.00000 | 27.00054 | 14.78612 | 0.82361 | 19.38661 |
Annual Sum or Average | 5943.00000 | 27.00614 | 20.49186 | 0.59278 | 14.13535 |
Minimum of Months | 454.00000 | 27.00000 | 14.78612 | 0.15300 | 5.59954 |
Maximum of Months | 514.00000 | 27.06139 | 26.42527 | 0.88558 | 21.62644 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 16.92582 | 0.63251 | 13.54316 |
February | 454.00000 | 27.00002 | 17.43354 | 0.67893 | 14.85977 |
March | 514.00000 | 27.00001 | 18.08306 | 0.73603 | 16.53329 |
April | 485.00000 | 27.00623 | 16.83344 | 0.78256 | 18.02105 |
May | 508.00000 | 27.00016 | 20.16402 | 0.08892 | 5.31469 |
June | 496.00000 | 27.00039 | 24.19891 | 0.17276 | 5.73846 |
July | 497.00000 | 27.00053 | 26.45645 | 0.22735 | 6.16379 |
August | 514.00000 | 27.02966 | 26.14350 | 0.25065 | 6.46270 |
September | 485.00000 | 27.00064 | 25.55244 | 0.14831 | 5.57960 |
October | 502.00000 | 27.00024 | 20.89578 | 0.77576 | 17.84113 |
November | 489.00000 | 27.00004 | 18.20742 | 0.72191 | 16.10073 |
December | 497.00000 | 26.99999 | 14.76274 | 0.65753 | 14.24642 |
Annual Sum or Average | 5943.00000 | 27.00324 | 20.49911 | 0.48754 | 11.66595 |
Minimum of Months | 454.00000 | 26.99999 | 14.76274 | 0.08892 | 5.31469 |
Maximum of Months | 514.00000 | 27.02966 | 26.45645 | 0.78256 | 18.02105 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.77491 | 17.09349 | 0.50183 | 10.96699 |
February | 454.00000 | 27.00002 | 17.44958 | 0.60729 | 13.06479 |
March | 514.00000 | 27.00001 | 18.09893 | 0.69014 | 15.27998 |
April | 485.00000 | 27.00388 | 16.84821 | 0.76323 | 17.49340 |
May | 508.00000 | 27.00015 | 20.18160 | 0.08431 | 5.43848 |
June | 496.00000 | 27.00040 | 24.20833 | 0.18646 | 5.94251 |
July | 497.00000 | 27.00055 | 26.45851 | 0.24979 | 6.46900 |
August | 514.00000 | 27.02907 | 26.14465 | 0.26726 | 6.74898 |
September | 485.00000 | 27.00065 | 25.56117 | 0.14868 | 5.69016 |
October | 502.00000 | 27.00024 | 20.91482 | 0.74381 | 16.95475 |
November | 489.00000 | 27.00004 | 18.22099 | 0.65193 | 14.19886 |
December | 497.00000 | 27.00000 | 14.77473 | 0.56464 | 11.97853 |
Annual Sum or Average | 5943.00000 | 26.98399 | 20.52408 | 0.45336 | 10.82567 |
Minimum of Months | 454.00000 | 26.77491 | 14.77473 | 0.08431 | 5.43848 |
Maximum of Months | 514.00000 | 27.02907 | 26.45851 | 0.76323 | 17.49340 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00052 | 28.72062 | 1.03754 | 27.73673 |
February | 454.00000 | 27.00040 | 24.31633 | 1.15778 | 33.22664 |
March | 514.00000 | 27.00024 | 19.41332 | 1.26560 | 38.52888 |
April | 485.00000 | 27.00022 | 15.98811 | 1.38089 | 44.50449 |
May | 508.00000 | 27.00075 | 24.76186 | 0.43825 | 9.11093 |
June | 496.00000 | 27.00419 | 29.52264 | 0.72826 | 16.20281 |
July | 497.00000 | 27.00538 | 32.98707 | 0.98732 | 25.60574 |
August | 514.00000 | 27.12087 | 31.77081 | 1.19291 | 34.99252 |
September | 485.00000 | 27.00196 | 32.30974 | 0.55846 | 11.60040 |
October | 502.00000 | 27.00134 | 24.90011 | 1.21247 | 35.89820 |
November | 489.00000 | 27.00029 | 20.27395 | 1.30236 | 40.40068 |
December | 497.00000 | 27.00010 | 16.92949 | 1.39317 | 45.15433 |
Annual Sum or Average | 5943.00000 | 27.01174 | 25.17837 | 1.05388 | 30.22365 |
Minimum of Months | 454.00000 | 27.00010 | 15.98811 | 0.43825 | 9.11093 |
Maximum of Months | 514.00000 | 27.12087 | 32.98707 | 1.39317 | 45.15433 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.67926 | 16.20022 | 0.34704 | 8.83186 |
February | 454.00000 | 24.59720 | 16.20309 | 0.32462 | 7.70476 |
March | 514.00000 | 24.52325 | 16.10597 | 0.31437 | 7.44010 |
April | 485.00000 | 24.63081 | 13.97802 | 0.32757 | 7.78655 |
May | 508.00000 | 25.09255 | 26.10265 | -0.2958 | 11.04714 |
June | 496.00000 | 27.12601 | 67.14087 | 0.69089 | 32.18651 |
July | 497.00000 | 29.02170 | 83.94809 | 1.45830 | 52.63770 |
August | 514.00000 | 27.32150 | 67.12493 | 0.77657 | 30.73428 |
September | 485.00000 | 25.42092 | 41.83557 | -0.0536 | 9.97250 |
October | 502.00000 | 25.03824 | 24.08930 | 0.50580 | 12.51038 |
November | 489.00000 | 24.73843 | 16.24298 | 0.37723 | 8.75508 |
December | 497.00000 | 24.70590 | 12.75696 | 0.33542 | 8.02340 |
Annual Sum or Average | 5943.00000 | 25.58469 | 33.65288 | 0.42698 | 16.56618 |
Minimum of Months | 454.00000 | 24.52325 | 12.75696 | -0.2958 | 7.44010 |
Maximum of Months | 514.00000 | 29.02170 | 83.94809 | 1.45830 | 52.63770 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.24279 | 17.11967 | 0.25155 | 6.52637 |
February | 454.00000 | 24.28577 | 17.87279 | 0.27494 | 6.74571 |
March | 514.00000 | 24.26510 | 16.74234 | 0.28186 | 6.81455 |
April | 485.00000 | 24.30614 | 14.51021 | 0.29081 | 6.95362 |
May | 508.00000 | 24.29559 | 22.70401 | -0.5258 | 11.34906 |
June | 496.00000 | 24.34733 | 33.36203 | -0.3818 | 8.67460 |
July | 497.00000 | 24.50022 | 46.17698 | -0.1997 | 6.77021 |
August | 514.00000 | 24.34361 | 45.34762 | -0.2699 | 7.05894 |
September | 485.00000 | 24.37704 | 38.64461 | -0.3713 | 8.59242 |
October | 502.00000 | 24.38734 | 24.02319 | 0.37268 | 8.34074 |
November | 489.00000 | 24.34674 | 17.47245 | 0.30784 | 7.19259 |
December | 497.00000 | 24.36891 | 14.91235 | 0.28307 | 6.93933 |
Annual Sum or Average | 5943.00000 | 24.33893 | 25.82011 | 0.02369 | 7.67212 |
Minimum of Months | 454.00000 | 24.24279 | 14.51021 | -0.5258 | 6.52637 |
Maximum of Months | 514.00000 | 24.50022 | 46.17698 | 0.37268 | 11.34906 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.60714 | 18.45716 | 0.06814 | 5.45488 |
February | 454.00000 | 23.78069 | 19.50561 | 0.12480 | 5.60268 |
March | 514.00000 | 24.01727 | 18.67140 | 0.19310 | 5.93392 |
April | 485.00000 | 24.13904 | 15.54547 | 0.21518 | 6.06621 |
May | 508.00000 | 24.16882 | 23.26549 | -0.6036 | 12.97536 |
June | 496.00000 | 24.18049 | 33.76647 | -0.5104 | 10.69151 |
July | 497.00000 | 24.23932 | 47.83467 | -0.3863 | 8.37455 |
August | 514.00000 | 24.21525 | 46.86044 | -0.4006 | 8.58095 |
September | 485.00000 | 24.23520 | 39.39024 | -0.4592 | 9.76837 |
October | 502.00000 | 24.14023 | 25.21975 | 0.28415 | 6.98300 |
November | 489.00000 | 23.97430 | 19.76821 | 0.18612 | 5.89974 |
December | 497.00000 | 23.62952 | 16.31893 | 0.05973 | 5.39849 |
Annual Sum or Average | 5943.00000 | 24.02897 | 27.12882 | -0.1048 | 7.66490 |
Minimum of Months | 454.00000 | 23.60714 | 15.54547 | -0.6036 | 5.39849 |
Maximum of Months | 514.00000 | 24.23932 | 47.83467 | 0.28415 | 12.97536 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.89835 | 20.52638 | -0.3620 | 9.60858 |
February | 454.00000 | 22.50431 | 21.37061 | -0.2006 | 7.48865 |
March | 514.00000 | 23.37705 | 19.39705 | 0.01905 | 5.91775 |
April | 485.00000 | 23.88868 | 15.76719 | 0.14749 | 5.83715 |
May | 508.00000 | 24.09556 | 23.14882 | -0.6276 | 13.90235 |
June | 496.00000 | 24.19927 | 33.75436 | -0.4869 | 10.32028 |
July | 497.00000 | 24.30676 | 47.81406 | -0.3386 | 7.85898 |
August | 514.00000 | 24.26519 | 46.68301 | -0.3664 | 8.19452 |
September | 485.00000 | 24.22126 | 39.07456 | -0.4641 | 9.95590 |
October | 502.00000 | 23.71609 | 25.75595 | 0.16719 | 6.57178 |
November | 489.00000 | 22.87742 | 21.66746 | -0.0982 | 6.62611 |
December | 497.00000 | 21.88154 | 18.38438 | -0.3792 | 9.63117 |
Annual Sum or Average | 5943.00000 | 23.44319 | 27.84741 | -0.2501 | 8.50576 |
Minimum of Months | 454.00000 | 21.88154 | 15.76719 | -0.6276 | 5.83715 |
Maximum of Months | 514.00000 | 24.30676 | 47.81406 | 0.16719 | 13.90235 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.61359 | 18.59923 | -0.1707 | 6.64517 |
February | 454.00000 | 23.03545 | 19.02117 | -0.0615 | 6.07417 |
March | 514.00000 | 23.65020 | 17.01245 | 0.09470 | 5.70494 |
April | 485.00000 | 24.10503 | 14.09947 | 0.22034 | 6.34311 |
May | 508.00000 | 24.25357 | 22.06523 | -0.5395 | 12.17028 |
June | 496.00000 | 24.43538 | 32.44260 | -0.3075 | 8.09566 |
July | 497.00000 | 24.60665 | 45.19300 | -0.1140 | 6.77318 |
August | 514.00000 | 24.40797 | 44.45985 | -0.2172 | 6.95785 |
September | 485.00000 | 24.35577 | 37.84858 | -0.3830 | 9.10827 |
October | 502.00000 | 23.95956 | 24.07799 | 0.23418 | 7.02120 |
November | 489.00000 | 23.46994 | 18.32500 | 0.04673 | 5.53040 |
December | 497.00000 | 22.86087 | 16.42698 | -0.1251 | 6.08431 |
Annual Sum or Average | 5943.00000 | 23.81829 | 25.86873 | -0.1111 | 7.22081 |
Minimum of Months | 454.00000 | 22.61359 | 14.09947 | -0.5395 | 5.53040 |
Maximum of Months | 514.00000 | 24.60665 | 45.19300 | 0.23418 | 12.17028 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.15010 | 17.62864 | -0.0237 | 6.87977 |
February | 454.00000 | 23.43717 | 18.04011 | 0.06577 | 6.72336 |
March | 514.00000 | 23.85859 | 16.31143 | 0.20037 | 7.03200 |
April | 485.00000 | 24.28591 | 13.49706 | 0.35365 | 8.82911 |
May | 508.00000 | 24.41311 | 21.45945 | -0.3583 | 10.57861 |
June | 496.00000 | 24.49169 | 32.15200 | -0.1590 | 7.90773 |
July | 497.00000 | 24.68901 | 44.81890 | 0.03610 | 8.14239 |
August | 514.00000 | 24.45620 | 44.11303 | -0.0833 | 7.31600 |
September | 485.00000 | 24.46623 | 37.28958 | -0.2313 | 8.23324 |
October | 502.00000 | 24.21743 | 23.27545 | 0.35778 | 9.47312 |
November | 489.00000 | 23.72857 | 17.56145 | 0.14486 | 6.62616 |
December | 497.00000 | 23.12628 | 15.83530 | -0.0406 | 6.56173 |
Annual Sum or Average | 5943.00000 | 24.03075 | 25.23898 | 0.02100 | 7.86740 |
Minimum of Months | 454.00000 | 23.12628 | 13.49706 | -0.3583 | 6.56173 |
Maximum of Months | 514.00000 | 24.68901 | 44.81890 | 0.35778 | 10.57861 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.62989 | 16.29033 | 0.16383 | 9.58301 |
February | 454.00000 | 23.81206 | 16.83870 | 0.22810 | 8.97971 |
March | 514.00000 | 23.94236 | 15.93524 | 0.24598 | 7.74437 |
April | 485.00000 | 24.21227 | 13.59694 | 0.30625 | 7.88094 |
May | 508.00000 | 24.26170 | 21.89107 | -0.5082 | 12.14077 |
June | 496.00000 | 24.37269 | 32.53513 | -0.3332 | 8.53363 |
July | 497.00000 | 24.57455 | 45.23928 | -0.1102 | 6.94954 |
August | 514.00000 | 24.45938 | 44.16010 | -0.1361 | 6.88770 |
September | 485.00000 | 24.54828 | 36.98168 | -0.1862 | 8.22552 |
October | 502.00000 | 24.49214 | 22.56136 | 0.48454 | 12.47126 |
November | 489.00000 | 24.25131 | 16.27292 | 0.35096 | 10.08810 |
December | 497.00000 | 23.77520 | 14.20654 | 0.20991 | 9.36626 |
Annual Sum or Average | 5943.00000 | 24.19617 | 24.79018 | 0.05745 | 9.07333 |
Minimum of Months | 454.00000 | 23.62989 | 13.59694 | -0.5082 | 6.88770 |
Maximum of Months | 514.00000 | 24.57455 | 45.23928 | 0.48454 | 12.47126 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.69301 | 16.56621 | 0.12281 | 6.64701 |
February | 454.00000 | 24.14820 | 16.63947 | 0.27527 | 7.63126 |
March | 514.00000 | 24.37818 | 15.37694 | 0.37944 | 8.84003 |
April | 485.00000 | 24.61665 | 13.10330 | 0.50049 | 11.47863 |
May | 508.00000 | 24.50063 | 21.37210 | -0.3136 | 9.32560 |
June | 496.00000 | 24.57999 | 31.96088 | -0.1108 | 7.69245 |
July | 497.00000 | 24.74962 | 44.66796 | 0.08325 | 7.94501 |
August | 514.00000 | 24.59538 | 43.70840 | 0.04610 | 7.21155 |
September | 485.00000 | 24.57881 | 36.95267 | -0.1584 | 7.90697 |
October | 502.00000 | 24.50917 | 22.63871 | 0.47480 | 11.06105 |
November | 489.00000 | 24.40767 | 16.10935 | 0.36298 | 8.54551 |
December | 497.00000 | 24.36191 | 13.62500 | 0.30694 | 7.70670 |
Annual Sum or Average | 5943.00000 | 24.42786 | 24.47264 | 0.16267 | 8.50027 |
Minimum of Months | 454.00000 | 23.69301 | 13.10330 | -0.3136 | 6.64701 |
Maximum of Months | 514.00000 | 24.74962 | 44.66796 | 0.50049 | 11.47863 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.07775 | 19.42775 | -0.5617 | 12.70642 |
February | 454.00000 | 21.56239 | 20.71568 | -0.4261 | 10.20419 |
March | 514.00000 | 22.64415 | 19.49641 | -0.1543 | 6.96386 |
April | 485.00000 | 23.56983 | 15.29390 | 0.06897 | 5.96314 |
May | 508.00000 | 24.03003 | 22.62463 | -0.6421 | 14.92435 |
June | 496.00000 | 24.29667 | 32.34749 | -0.4128 | 9.37538 |
July | 497.00000 | 24.47174 | 46.07722 | -0.2418 | 7.30014 |
August | 514.00000 | 24.31019 | 45.32184 | -0.3243 | 7.90463 |
September | 485.00000 | 24.15645 | 38.44042 | -0.4849 | 10.87420 |
October | 502.00000 | 23.18080 | 25.67675 | 0.03407 | 6.85215 |
November | 489.00000 | 21.96745 | 20.96354 | -0.3145 | 8.51676 |
December | 497.00000 | 20.92218 | 17.14986 | -0.6150 | 13.75724 |
Annual Sum or Average | 5943.00000 | 23.02712 | 27.02975 | -0.3393 | 9.61157 |
Minimum of Months | 454.00000 | 20.92218 | 15.29390 | -0.6421 | 5.96314 |
Maximum of Months | 514.00000 | 24.47174 | 46.07722 | 0.06897 | 14.92435 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.13679 | 17.70554 | -0.2986 | 9.33748 |
February | 385.00000 | 22.60604 | 18.65904 | -0.1560 | 8.24220 |
March | 433.00000 | 23.44205 | 17.22340 | 0.08114 | 7.29363 |
April | 410.00000 | 24.24082 | 13.55029 | 0.31911 | 8.92828 |
May | 430.00000 | 24.42210 | 21.47550 | -0.3794 | 11.96931 |
June | 418.00000 | 24.51550 | 31.23826 | -0.2036 | 8.62170 |
July | 422.00000 | 24.74734 | 44.59488 | -0.0198 | 8.79096 |
August | 433.00000 | 24.53502 | 43.88597 | -0.1190 | 8.02119 |
September | 410.00000 | 24.47635 | 36.82702 | -0.2693 | 9.19382 |
October | 427.00000 | 23.98141 | 23.32100 | 0.27416 | 9.31985 |
November | 417.00000 | 23.04929 | 18.76799 | -0.0344 | 7.17339 |
December | 422.00000 | 21.96647 | 15.77030 | -0.3506 | 9.88544 |
Annual Sum or Average | 5034.00000 | 23.68249 | 25.30980 | -0.0964 | 8.90440 |
Minimum of Months | 385.00000 | 21.96647 | 13.55029 | -0.3794 | 7.17339 |
Maximum of Months | 433.00000 | 24.74734 | 44.59488 | 0.31911 | 11.96931 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.45559 | 15.97065 | 0.11909 | 11.23321 |
February | 454.00000 | 23.60595 | 17.14490 | 0.18035 | 10.23272 |
March | 514.00000 | 23.65033 | 17.14093 | 0.17682 | 8.19510 |
April | 485.00000 | 23.97472 | 14.09631 | 0.23613 | 7.58505 |
May | 508.00000 | 24.11569 | 22.24066 | -0.5745 | 14.01688 |
June | 496.00000 | 24.25939 | 32.36996 | -0.4235 | 9.89911 |
July | 497.00000 | 24.47952 | 45.96886 | -0.2134 | 7.46346 |
August | 514.00000 | 24.39386 | 44.83669 | -0.2135 | 7.43495 |
September | 485.00000 | 24.53083 | 36.94042 | -0.2047 | 8.97165 |
October | 502.00000 | 24.44889 | 22.83944 | 0.47303 | 13.36505 |
November | 489.00000 | 24.06929 | 17.26260 | 0.31353 | 11.28447 |
December | 497.00000 | 23.47408 | 13.76032 | 0.12657 | 10.89577 |
Annual Sum or Average | 5943.00000 | 24.04027 | 25.13147 | -0.0027 | 10.05065 |
Minimum of Months | 454.00000 | 23.45559 | 13.76032 | -0.5745 | 7.43495 |
Maximum of Months | 514.00000 | 24.53083 | 45.96886 | 0.47303 | 14.01688 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.20227 | 17.84410 | -0.2635 | 9.28981 |
February | 454.00000 | 22.70711 | 18.74371 | -0.1084 | 8.22336 |
March | 514.00000 | 23.43413 | 17.90121 | 0.08912 | 7.36115 |
April | 485.00000 | 24.10170 | 14.20125 | 0.28470 | 8.22097 |
May | 508.00000 | 24.28075 | 21.97017 | -0.4402 | 11.74639 |
June | 496.00000 | 24.43199 | 31.96545 | -0.2482 | 8.71998 |
July | 497.00000 | 24.59505 | 45.60568 | -0.0803 | 7.46848 |
August | 514.00000 | 24.45835 | 44.68656 | -0.1373 | 7.26311 |
September | 485.00000 | 24.41436 | 37.35579 | -0.2721 | 8.91135 |
October | 502.00000 | 23.85179 | 24.11192 | 0.26613 | 8.86442 |
November | 489.00000 | 23.08207 | 19.02102 | -0.0110 | 7.31727 |
December | 497.00000 | 22.15385 | 15.60290 | -0.2879 | 9.33771 |
Annual Sum or Average | 5943.00000 | 23.64957 | 25.82610 | -0.1012 | 8.56402 |
Minimum of Months | 454.00000 | 22.15385 | 14.20125 | -0.4402 | 7.26311 |
Maximum of Months | 514.00000 | 24.59505 | 45.60568 | 0.28470 | 11.74639 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.36544 | 20.04321 | -0.7822 | 20.17842 |
February | 454.00000 | 20.89031 | 21.29922 | -0.6234 | 15.33914 |
March | 514.00000 | 22.08001 | 19.60810 | -0.3105 | 9.32216 |
April | 485.00000 | 23.24658 | 15.47749 | -0.0124 | 6.73008 |
May | 508.00000 | 23.89099 | 22.66362 | -0.6862 | 17.16841 |
June | 496.00000 | 24.27535 | 32.58712 | -0.4043 | 9.64673 |
July | 497.00000 | 24.47640 | 46.40501 | -0.2163 | 7.34715 |
August | 514.00000 | 24.30940 | 45.45380 | -0.3081 | 8.00969 |
September | 485.00000 | 24.06374 | 38.41479 | -0.5131 | 12.12708 |
October | 502.00000 | 22.72631 | 25.93848 | -0.0868 | 8.16315 |
November | 489.00000 | 21.16177 | 21.64094 | -0.5354 | 13.51646 |
December | 497.00000 | 20.26667 | 17.79592 | -0.8264 | 21.42882 |
Annual Sum or Average | 5943.00000 | 22.66003 | 27.34290 | -0.4411 | 12.39496 |
Minimum of Months | 454.00000 | 20.26667 | 15.47749 | -0.8264 | 6.73008 |
Maximum of Months | 514.00000 | 24.47640 | 46.40501 | -0.0124 | 21.42882 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.37080 | 19.11259 | -0.5150 | 13.72609 |
February | 454.00000 | 22.03733 | 19.87315 | -0.3168 | 10.80290 |
March | 514.00000 | 23.15425 | 17.57162 | -0.0017 | 7.78179 |
April | 485.00000 | 24.06017 | 13.70220 | 0.28534 | 8.68742 |
May | 508.00000 | 24.28453 | 21.40311 | -0.4034 | 12.40414 |
June | 496.00000 | 24.41640 | 32.02383 | -0.1944 | 8.45115 |
July | 497.00000 | 24.63407 | 45.77184 | -0.0041 | 8.45774 |
August | 514.00000 | 24.44206 | 44.75959 | -0.1020 | 7.77554 |
September | 485.00000 | 24.34132 | 37.19710 | -0.2822 | 9.38269 |
October | 502.00000 | 23.70684 | 23.88282 | 0.20641 | 9.21129 |
November | 489.00000 | 22.45386 | 20.02666 | -0.2005 | 8.81450 |
December | 497.00000 | 21.15772 | 17.17036 | -0.5767 | 15.17220 |
Annual Sum or Average | 5943.00000 | 23.34825 | 26.10843 | -0.1747 | 10.04998 |
Minimum of Months | 454.00000 | 21.15772 | 13.70220 | -0.5767 | 7.77554 |
Maximum of Months | 514.00000 | 24.63407 | 45.77184 | 0.28534 | 15.17220 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.70332 | 16.70741 | -0.1078 | 12.49639 |
February | 454.00000 | 22.97313 | 17.77004 | -0.0074 | 11.15972 |
March | 514.00000 | 23.21792 | 17.17577 | 0.04812 | 8.77541 |
April | 485.00000 | 23.71620 | 14.24314 | 0.16820 | 7.95276 |
May | 508.00000 | 23.96729 | 22.27399 | -0.6214 | 16.25236 |
June | 496.00000 | 24.21756 | 32.65226 | -0.4209 | 10.44978 |
July | 497.00000 | 24.47811 | 46.33258 | -0.1900 | 7.60787 |
August | 514.00000 | 24.37839 | 45.02352 | -0.2020 | 7.65686 |
September | 485.00000 | 24.41258 | 36.94056 | -0.2406 | 9.89404 |
October | 502.00000 | 24.06292 | 23.02459 | 0.36633 | 12.46003 |
November | 489.00000 | 23.41825 | 17.84721 | 0.12547 | 10.74524 |
December | 497.00000 | 22.67765 | 14.64133 | -0.1081 | 12.62506 |
Annual Sum or Average | 5943.00000 | 23.68983 | 25.46687 | -0.1008 | 10.67575 |
Minimum of Months | 454.00000 | 22.67765 | 14.24314 | -0.6214 | 7.60787 |
Maximum of Months | 514.00000 | 24.47811 | 46.33258 | 0.36633 | 16.25236 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.46146 | 18.50143 | -0.4752 | 13.92356 |
February | 454.00000 | 22.09598 | 19.30948 | -0.2819 | 11.06075 |
March | 514.00000 | 22.96314 | 17.99387 | -0.0415 | 8.45053 |
April | 485.00000 | 23.83984 | 14.38070 | 0.21833 | 8.45757 |
May | 508.00000 | 24.15209 | 21.98579 | -0.4810 | 13.56550 |
June | 496.00000 | 24.39807 | 32.23208 | -0.2443 | 9.25017 |
July | 497.00000 | 24.59376 | 45.97818 | -0.0586 | 7.77650 |
August | 514.00000 | 24.45250 | 44.84918 | -0.1240 | 7.48107 |
September | 485.00000 | 24.33996 | 37.29422 | -0.2950 | 9.74744 |
October | 502.00000 | 23.49880 | 24.27951 | 0.16997 | 9.29071 |
November | 489.00000 | 22.40896 | 19.61370 | -0.1952 | 9.52851 |
December | 497.00000 | 21.43545 | 16.31923 | -0.4949 | 14.05325 |
Annual Sum or Average | 5943.00000 | 23.31241 | 26.13411 | -0.1917 | 10.21060 |
Minimum of Months | 454.00000 | 21.43545 | 14.38070 | -0.4949 | 7.48107 |
Maximum of Months | 514.00000 | 24.59376 | 45.97818 | 0.21833 | 14.05325 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.897991E+10 | 62452.32 | 05-JAN-15:40 | 173.38 | 0.757769E+11 | 0.00 | 0.847568E+11 | 1.95 | 8.68 | 26-JAN-16:10 | 0.00 | 0.00 |
February | 0.135949E+11 | 160598.91 | 14-FEB-16:40 | 198.31 | 0.110856E+12 | 0.00 | 0.124451E+12 | 2.46 | 8.68 | 10-FEB-13:25 | 0.00 | 0.00 |
March | 0.244059E+11 | 146699.25 | 13-MAR-14:50 | 273.70 | 0.197808E+12 | 0.00 | 0.222213E+12 | 3.06 | 8.68 | 25-MAR-14:20 | 0.00 | 0.00 |
April | 0.423041E+11 | 158607.70 | 25-APR-14:30 | 341.25 | 0.338233E+12 | 0.00 | 0.380538E+12 | 3.91 | 8.68 | 29-APR-11:30 | 0.00 | 0.00 |
May | 0.674666E+11 | 152023.10 | 16-MAY-13:00 | 404.25 | 0.533467E+12 | 0.00 | 0.600934E+12 | 4.44 | 8.70 | 22-MAY-04:13 | 0.00 | 0.00 |
June | 0.106840E+12 | 163675.19 | 24-JUN-13:40 | 545.46 | 0.837087E+12 | 0.00 | 0.943927E+12 | 6.13 | 8.71 | 22-JUN-05:03 | 0.00 | 0.00 |
July | 0.129652E+12 | 168509.06 | 29-JUL-14:20 | 667.95 | 0.996562E+12 | 0.00 | 0.112621E+13 | 7.21 | 8.70 | 17-JUL-04:12 | 0.00 | 0.00 |
August | 0.126388E+12 | 165232.87 | 12-AUG-11:00 | 674.60 | 0.974440E+12 | 0.00 | 0.110083E+13 | 7.29 | 8.71 | 19-AUG-04:12 | 0.00 | 0.00 |
September | 0.884127E+11 | 165228.74 | 12-SEP-12:00 | 462.10 | 0.692115E+12 | 0.00 | 0.780528E+12 | 5.20 | 8.68 | 05-SEP-04:12 | 0.00 | 0.00 |
October | 0.513063E+11 | 161733.50 | 11-OCT-12:50 | 358.14 | 0.405830E+12 | 0.00 | 0.457136E+12 | 3.95 | 8.73 | 15-OCT-15:23 | 0.00 | 0.00 |
November | 0.181703E+11 | 105677.37 | 02-NOV-15:10 | 232.45 | 0.152776E+12 | 0.00 | 0.170946E+12 | 2.70 | 8.68 | 03-NOV-13:20 | 0.00 | 0.00 |
December | 0.431519E+10 | 47176.81 | 29-DEC-15:50 | 220.11 | 0.360866E+11 | 0.00 | 0.404018E+11 | 2.47 | 8.68 | 29-DEC-15:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.681836E+12 | 4551.68 | 0.535104E+13 | 0.00 | 0.603287E+13 | 4.24 | 0.00 | 0.00 | ||||
Minimum of Months | 0.431519E+10 | 47176.81 | 173.38 | 0.360866E+11 | 0.00 | 0.404018E+11 | 1.95 | 8.68 | 0.00 | 0.00 | ||
Maximum of Months | 0.129652E+12 | 168509.06 | 674.60 | 0.996562E+12 | 0.00 | 0.112621E+13 | 7.29 | 8.73 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 84127871.25 | 69632.00 | 14-FEB-16:10 | 0.50 | 0.679205E+09 | 0.00 | 0.763333E+09 | 0.01 | 8.61 | 14-FEB-15:30 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.523396E+10 | 94211.66 | 14-APR-14:05 | 22.50 | 0.430362E+11 | 0.00 | 0.482701E+11 | 0.26 | 8.65 | 14-APR-14:00 | 0.00 | 0.00 |
May | 0.102524E+11 | 100855.17 | 19-MAY-12:05 | 42.33 | 0.837996E+11 | 0.00 | 0.940520E+11 | 0.47 | 8.67 | 31-MAY-16:40 | 0.00 | 0.00 |
June | 0.414093E+11 | 141609.51 | 30-JUN-08:20 | 151.75 | 0.329796E+12 | 0.00 | 0.371206E+12 | 1.69 | 8.67 | 21-JUN-18:30 | 0.00 | 0.00 |
July | 0.558512E+11 | 156420.63 | 06-JUL-08:21 | 194.60 | 0.435538E+12 | 0.00 | 0.491389E+12 | 2.05 | 8.66 | 21-JUL-19:20 | 0.00 | 0.00 |
August | 0.513034E+11 | 148859.95 | 24-AUG-12:13 | 180.51 | 0.402408E+12 | 0.00 | 0.453712E+12 | 1.91 | 8.63 | 31-AUG-17:20 | 0.00 | 0.00 |
September | 0.257475E+11 | 159102.89 | 01-SEP-12:10 | 96.55 | 0.205375E+12 | 0.00 | 0.231123E+12 | 1.08 | 8.67 | 12-SEP-16:30 | 0.00 | 0.00 |
October | 0.835917E+10 | 151196.05 | 10-OCT-12:07 | 33.78 | 0.678722E+11 | 0.00 | 0.762314E+11 | 0.37 | 8.64 | 04-OCT-17:00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.198241E+12 | 722.52 | 0.156851E+13 | 0.00 | 0.176675E+13 | 0.66 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.558512E+11 | 159102.89 | 194.60 | 0.435538E+12 | 0.00 | 0.491389E+12 | 2.05 | 8.67 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.124969E+10 | 744.00 | 3065.68 | 05-JAN-16:00 | 49938.08 | 26-JAN-17:00 | 18.79 | 18.33 | 17.32 |
February | 0.443465E+10 | 672.00 | 43776.24 | 12-FEB-14:41 | 192101.22 | 14-FEB-16:00 | 19.38 | 18.38 | 17.31 |
March | 0.156780E+11 | 744.00 | 43776.24 | 06-MAR-15:50 | 363916.27 | 08-MAR-16:00 | 20.19 | 18.50 | 17.32 |
April | 0.460227E+11 | 720.00 | 43776.24 | 01-APR-10:20 | 660266.80 | 13-APR-17:00 | 23.87 | 19.97 | 17.32 |
May | 0.580563E+11 | 744.00 | 43776.24 | 02-MAY-12:20 | 277200.65 | 22-MAY-14:05 | 21.95 | 20.79 | 17.32 |
June | 0.886614E+11 | 720.00 | 43776.24 | 01-JUN-00:10 | 494211.93 | 30-JUN-14:00 | 29.21 | 25.34 | 17.32 |
July | 0.116423E+12 | 744.00 | 43776.24 | 01-JUL-00:10 | 749179.08 | 31-JUL-24:00 | 36.59 | 28.51 | 17.32 |
August | 0.115883E+12 | 744.00 | 43776.24 | 01-AUG-00:10 | 813998.71 | 26-AUG-13:05 | 38.27 | 27.83 | 17.32 |
September | 0.759569E+11 | 720.00 | 43776.24 | 01-SEP-00:03 | 277755.12 | 02-SEP-18:12 | 23.38 | 21.92 | 17.32 |
October | 0.386494E+11 | 744.00 | 43776.24 | 01-OCT-09:02 | 430887.19 | 01-OCT-16:11 | 21.16 | 19.55 | 17.32 |
November | 0.503840E+10 | 720.00 | 43776.24 | 09-NOV-12:30 | 225735.28 | 09-NOV-14:05 | 19.82 | 18.34 | 17.32 |
December | 0.368554E+10 | 744.00 | 3605.36 | 24-DEC-15:00 | 168036.76 | 29-DEC-07:15 | 20.17 | 18.33 | 17.31 |
Annual Sum or Average | 0.569739E+12 | 8760.00 | 24.44 | 21.34 | 17.32 | ||||
Minimum of Months | 0.124969E+10 | 672.00 | 3065.68 | 49938.08 | 18.79 | 18.33 | 17.31 | ||
Maximum of Months | 0.116423E+12 | 744.00 | 43776.24 | 813998.71 | 38.27 | 28.51 | 17.32 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 596778.89 | 05-JAN-15:40 | 21.14 | 20.98 | 6.92 |
February | 26115774.96 | 39.50 | 1121.61 | 14-FEB-15:30 | 1189659.85 | 14-FEB-16:40 | 21.18 | 20.93 | 8.91 |
March | 85285792.20 | 128.51 | 1158.72 | 08-MAR-14:30 | 1118997.39 | 13-MAR-14:50 | 21.35 | 20.95 | 13.14 |
April | 0.238523E+09 | 197.44 | 1537.22 | 13-APR-17:00 | 1166521.45 | 27-APR-12:40 | 21.76 | 21.03 | 18.81 |
May | 0.646825E+09 | 310.86 | 15004.36 | 22-MAY-12:20 | 1142534.50 | 16-MAY-13:00 | 22.37 | 21.25 | 25.35 |
June | 0.369757E+10 | 440.71 | 15004.36 | 06-JUN-10:50 | 1177530.00 | 20-JUN-08:50 | 23.05 | 21.17 | 35.53 |
July | 0.142472E+11 | 520.27 | 15004.36 | 01-JUL-09:20 | 1181443.30 | 06-JUL-08:70 | 23.39 | 21.35 | 41.90 |
August | 0.115917E+11 | 503.40 | 15004.36 | 01-AUG-07:50 | 1149641.46 | 24-AUG-12:00 | 23.26 | 21.23 | 41.28 |
September | 0.331264E+10 | 396.81 | 15004.36 | 01-SEP-09:10 | 1193080.33 | 12-SEP-12:00 | 22.90 | 21.36 | 31.81 |
October | 0.881854E+09 | 238.46 | 15004.36 | 02-OCT-10:30 | 1163234.80 | 03-OCT-12:50 | 21.97 | 21.11 | 20.95 |
November | 38554372.30 | 113.92 | 953.35 | 02-NOV-16:00 | 891782.03 | 02-NOV-15:20 | 21.28 | 20.96 | 11.92 |
December | 1745253.12 | 9.00 | 120.77 | 29-DEC-15:50 | 466345.33 | 29-DEC-16:00 | 20.97 | 20.89 | 4.94 |
Annual Sum or Average | 0.347681E+11 | 2898.87 | 22.06 | 21.10 | 21.86 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 466345.33 | 20.97 | 20.89 | 4.94 | ||
Maximum of Months | 0.142472E+11 | 520.27 | 15004.36 | 1193080.33 | 23.39 | 21.36 | 41.90 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 21.14 | 21.14 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.18 | 21.18 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.35 | 21.35 | 0.00 |
April | 48431115.67 | 17.83 | 1507.40 | 27-APR-13:00 | 1008082.19 | 26-APR-13:05 | 21.76 | 21.65 | 1.30 |
May | 83536384.32 | 34.67 | 3515.32 | 22-MAY-12:45 | 1069932.37 | 15-MAY-15:20 | 22.37 | 22.17 | 2.44 |
June | 0.188226E+10 | 141.08 | 15004.36 | 06-JUN-12:55 | 1069610.44 | 19-JUN-14:50 | 23.05 | 22.24 | 10.24 |
July | 0.857088E+10 | 182.10 | 15004.36 | 01-JUL-10:30 | 1097432.79 | 12-JUL-08:13 | 23.39 | 22.49 | 12.73 |
August | 0.679610E+10 | 164.16 | 15004.36 | 01-AUG-09:30 | 1128987.78 | 24-AUG-12:13 | 23.26 | 22.42 | 11.53 |
September | 0.136467E+10 | 85.35 | 15004.36 | 01-SEP-10:30 | 1114442.51 | 06-SEP-12:02 | 22.90 | 22.39 | 6.21 |
October | 0.268771E+09 | 28.28 | 15004.36 | 02-OCT-13:40 | 1127368.01 | 11-OCT-12:53 | 21.97 | 21.80 | 1.99 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.28 | 21.28 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.97 | 20.97 | 0.00 |
Annual Sum or Average | 0.190146E+11 | 653.47 | 22.06 | 21.76 | 3.90 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 20.97 | 0.00 | ||
Maximum of Months | 0.857088E+10 | 182.10 | 15004.36 | 1128987.78 | 23.39 | 22.49 | 12.73 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.181605E+12 | 0.00 | 366.59 | 1097705.52 | 19-JAN-06:01 | 0.00 | 37.88 | 48.62 | 0.88 | 0.00 | 0.04 | 0.65 | 19-JAN-06:01 |
February | 0.112764E+12 | 0.00 | 286.67 | 1095565.02 | 01-FEB-06:01 | 0.00 | 36.56 | 46.22 | 0.56 | 0.00 | 0.03 | 0.65 | 01-FEB-06:01 |
March | 0.370808E+11 | 0.00 | 193.20 | 872276.31 | 04-MAR-06:02 | 0.00 | 34.29 | 40.90 | 0.14 | 0.00 | 0.01 | 0.52 | 04-MAR-06:02 |
April | 0.641046E+10 | 0.00 | 58.72 | 222795.34 | 08-APR-06:05 | 0.00 | 32.50 | 34.65 | 0.02 | 0.00 | 0.00 | 0.13 | 08-APR-06:05 |
May | 0.115818E+10 | 0.00 | 16.86 | 100012.96 | 06-MAY-06:03 | 0.00 | 31.51 | 32.16 | 0.00 | 0.00 | 0.00 | 0.06 | 06-MAY-06:03 |
June | 3201770.62 | 0.00 | 0.67 | 2632.06 | 09-JUN-06:10 | 0.00 | 31.54 | 31.57 | 0.00 | 0.00 | 0.00 | 0.00 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 31.53 | 31.53 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 31.53 | 31.53 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 31.53 | 31.53 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.215012E+11 | 0.00 | 91.60 | 930264.12 | 26-OCT-05:02 | 0.00 | 32.68 | 35.78 | 0.09 | 0.00 | 0.00 | 0.55 | 26-OCT-05:02 |
November | 0.503832E+11 | 0.00 | 227.21 | 1037704.83 | 28-NOV-06:01 | 0.00 | 34.30 | 42.13 | 0.21 | 0.00 | 0.01 | 0.62 | 28-NOV-06:01 |
December | 0.177701E+12 | 0.00 | 391.83 | 1174981.59 | 04-DEC-05:01 | 0.00 | 36.81 | 48.66 | 0.84 | 0.00 | 0.04 | 0.70 | 04-DEC-05:01 |
Annual Sum or Average | 0.588608E+12 | 0.00 | 1633.35 | 0.00 | 33.54 | 37.90 | 0.23 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.51 | 31.53 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.181605E+12 | 0.00 | 391.83 | 1174981.59 | 0.00 | 37.88 | 48.66 | 0.88 | 0.00 | 0.04 | 0.70 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 18.79 | 18.79 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.38 | 19.38 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.19 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 23.87 | 23.87 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 21.95 | 21.95 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 29.21 | 29.21 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 36.59 | 36.59 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 38.27 | 38.27 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 23.38 | 23.38 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 21.16 | 21.16 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.82 | 19.82 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.17 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 24.44 | 24.44 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.79 | 18.79 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.27 | 38.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.138862E+11 | 0.00 | 154.45 | 0.138862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62193.28 | 03-JAN-15:00 | 62193.28 | 03-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.136920E+11 | 0.00 | 157.62 | 0.136920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72055.44 | 14-FEB-16:00 | 72055.44 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.156565E+11 | 0.00 | 187.52 | 0.156565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77892.10 | 08-MAR-16:00 | 77892.10 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.369160E+11 | 0.00 | 289.10 | 0.369160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112125.08 | 17-APR-15:20 | 112125.08 | 17-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.571789E+11 | 0.00 | 360.43 | 0.571789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117748.38 | 30-MAY-14:30 | 117748.38 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.124065E+12 | 0.00 | 523.03 | 0.123972E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 176567.31 | 28-JUN-13:45 | 176567.31 | 28-JUN-13:45 | 0.00 | 0.00 | 0.00 |
July | 0.172752E+12 | 0.00 | 636.91 | 0.165404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 189226.32 | 16-JUL-09:21 | 169173.15 | 21-JUL-17:12 | 0.00 | 0.00 | 0.00 |
August | 0.159139E+12 | 0.00 | 650.80 | 0.152956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 183900.93 | 23-AUG-16:00 | 160081.06 | 21-AUG-16:05 | 0.00 | 0.00 | 0.00 |
September | 0.825700E+11 | 0.00 | 438.87 | 0.811634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167061.41 | 05-SEP-13:10 | 144537.69 | 01-SEP-10:32 | 0.00 | 0.00 | 0.00 |
October | 0.431692E+11 | 0.00 | 310.93 | 0.431465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147127.71 | 11-OCT-12:55 | 142009.88 | 11-OCT-12:55 | 0.00 | 0.00 | 0.00 |
November | 0.129330E+11 | 0.00 | 152.81 | 0.129330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58956.37 | 06-NOV-13:05 | 58956.37 | 06-NOV-13:05 | 0.00 | 0.00 | 0.00 |
December | 0.174817E+11 | 0.00 | 190.84 | 0.174817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58766.85 | 26-DEC-15:00 | 58766.85 | 26-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.749440E+12 | 0.00 | 4053.29 | 0.734387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.129330E+11 | 0.00 | 152.81 | 0.129330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58766.85 | 58766.85 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.172752E+12 | 0.00 | 650.80 | 0.165404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 189226.32 | 176567.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.550471E+11 | 0.00 | 112.15 | 0.550471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 433762.34 | 05-JAN-15:40 | 433762.34 | 05-JAN-15:40 | 0.00 | 0.00 | 0.00 |
February | 0.851283E+11 | 0.00 | 130.22 | 0.851283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 671779.59 | 14-FEB-16:00 | 671779.59 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.157491E+12 | 0.00 | 204.48 | 0.157491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 629684.86 | 13-MAR-15:00 | 629684.86 | 13-MAR-15:00 | 0.00 | 0.00 | 0.00 |
April | 0.284171E+12 | 0.00 | 274.87 | 0.284171E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 907305.86 | 13-APR-15:20 | 907305.86 | 13-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.474317E+12 | 0.00 | 350.58 | 0.474317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1008605.63 | 19-MAY-15:10 | 1008605.63 | 19-MAY-15:10 | 0.00 | 0.00 | 0.00 |
June | 0.905619E+12 | 0.00 | 451.63 | 0.905562E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1250941.29 | 28-JUN-14:50 | 1250941.29 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.109072E+13 | 0.00 | 486.28 | 0.106923E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1368795.05 | 02-JUL-16:01 | 1283032.57 | 06-JUL-08:23 | 0.00 | 0.00 | 0.00 |
August | 0.104310E+13 | 0.00 | 492.04 | 0.102074E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1323897.77 | 13-AUG-14:51 | 1214178.72 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.687725E+12 | 0.00 | 418.17 | 0.677553E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1395350.19 | 01-SEP-10:32 | 1340788.64 | 01-SEP-10:32 | 0.00 | 0.00 | 0.00 |
October | 0.360184E+12 | 0.00 | 304.10 | 0.360103E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1061252.29 | 11-OCT-12:53 | 1026418.15 | 11-OCT-12:53 | 0.00 | 0.00 | 0.00 |
November | 0.127798E+12 | 0.00 | 179.87 | 0.127798E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 584751.38 | 02-NOV-15:20 | 584751.38 | 02-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.145850E+11 | 0.00 | 71.53 | 0.145850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 331235.58 | 29-DEC-16:00 | 331235.58 | 29-DEC-16:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.528588E+13 | 0.00 | 3475.93 | 0.523173E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.145850E+11 | 0.00 | 71.53 | 0.145850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 331235.58 | 331235.58 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.109072E+13 | 0.00 | 492.04 | 0.106923E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1395350.19 | 1340788.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.371390E+10 | 0.00 | 72.49 | 0.371390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31955.45 | 23-JAN-15:40 | 31955.45 | 23-JAN-15:40 | 0.00 | 0.00 | 0.00 |
February | 0.580385E+10 | 0.00 | 82.53 | 0.580385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68448.75 | 14-FEB-16:00 | 68448.75 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.854119E+10 | 0.00 | 133.20 | 0.854119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65967.64 | 15-MAR-16:00 | 65967.64 | 15-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.289208E+11 | 0.00 | 252.50 | 0.289208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110173.49 | 26-APR-15:10 | 110173.49 | 26-APR-15:10 | 0.00 | 0.00 | 0.00 |
May | 0.523440E+11 | 0.00 | 351.68 | 0.523440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123856.41 | 30-MAY-14:30 | 123856.41 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.103094E+12 | 0.00 | 449.64 | 0.103092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 184014.90 | 28-JUN-13:43 | 184014.90 | 28-JUN-13:43 | 0.00 | 0.00 | 0.00 |
July | 0.125157E+12 | 0.00 | 490.63 | 0.122947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 160547.38 | 16-JUL-14:52 | 155081.57 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 |
August | 0.118052E+12 | 0.00 | 492.16 | 0.115843E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 156996.20 | 13-AUG-14:11 | 147136.70 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.747200E+11 | 0.00 | 411.11 | 0.738785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152795.90 | 05-SEP-13:40 | 145073.60 | 12-SEP-12:13 | 0.00 | 0.00 | 0.00 |
October | 0.336305E+11 | 0.00 | 269.42 | 0.336286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124873.21 | 11-OCT-12:53 | 124873.21 | 11-OCT-12:53 | 0.00 | 0.00 | 0.00 |
November | 0.813049E+10 | 0.00 | 127.88 | 0.813049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54410.82 | 01-NOV-15:00 | 54410.82 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.177269E+10 | 0.00 | 66.40 | 0.177269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24532.07 | 29-DEC-15:50 | 24532.07 | 29-DEC-15:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.563880E+12 | 0.00 | 3199.64 | 0.558616E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.177269E+10 | 0.00 | 66.40 | 0.177269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24532.07 | 24532.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.125157E+12 | 0.00 | 492.16 | 0.122947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 184014.90 | 184014.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.153803E+10 | 0.00 | 53.00 | 0.153803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30470.45 | 02-JAN-14:10 | 30470.45 | 02-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.230971E+10 | 0.00 | 54.33 | 0.230971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43682.10 | 13-FEB-16:00 | 43682.10 | 13-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.801790E+10 | 0.00 | 172.85 | 0.801790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44516.14 | 13-MAR-15:00 | 44516.14 | 13-MAR-15:00 | 0.00 | 0.00 | 0.00 |
April | 0.204858E+11 | 0.00 | 208.83 | 0.204858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61761.68 | 17-APR-14:00 | 61761.68 | 17-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.274510E+11 | 0.00 | 237.36 | 0.273308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77471.08 | 23-MAY-09:50 | 77471.08 | 23-MAY-09:50 | 0.00 | 0.00 | 0.00 |
June | 0.222848E+11 | 0.00 | 141.56 | 0.220665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88180.16 | 12-JUN-13:55 | 88180.16 | 12-JUN-13:55 | 0.00 | 0.00 | 0.00 |
July | 0.159998E+11 | 0.00 | 52.67 | 0.126465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104132.48 | 17-JUL-10:00 | 88807.70 | 28-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.404123E+11 | 0.00 | 172.41 | 0.370199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102860.55 | 23-AUG-15:40 | 91820.16 | 16-AUG-17:50 | 0.00 | 0.00 | 0.00 |
September | 0.470443E+11 | 0.00 | 268.26 | 0.451165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102092.54 | 05-SEP-13:00 | 76003.67 | 13-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.225356E+11 | 0.00 | 196.86 | 0.224422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82156.53 | 10-OCT-14:00 | 82156.53 | 10-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.152230E+10 | 0.00 | 47.42 | 0.152230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26783.90 | 09-NOV-14:00 | 26783.90 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209602E+12 | 0.00 | 1605.57 | 0.200496E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.470443E+11 | 0.00 | 268.26 | 0.451165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104132.48 | 91820.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.118753E+11 | 0.592176E+10 | 744.00 | 0.103156E+11 | 0.155967E+10 | 0.00 | 0.02 | 01-JAN-10:43 | 0.02 | 20-JAN-13:10 | 5617.22 | 01-JAN-10:43 | 4891.25 | 22-JAN-17:23 | 766.04 | 01-JAN-10:32 | 2513.28 | 01-JAN-10:43 | 0.00 |
February | 0.149217E+11 | 0.674527E+10 | 672.00 | 0.135522E+11 | 0.136958E+10 | 0.00 | 0.27 | 14-FEB-16:00 | 0.02 | 17-FEB-09:00 | 93453.13 | 14-FEB-16:00 | 93453.13 | 14-FEB-16:00 | 1200.65 | 19-FEB-07:57 | 32355.04 | 14-FEB-16:00 | 0.00 |
March | 0.362737E+11 | 0.138610E+11 | 744.00 | 0.354590E+11 | 0.814645E+09 | 0.00 | 0.53 | 08-MAR-16:00 | 0.02 | 14-MAR-17:00 | 202456.01 | 08-MAR-16:00 | 202456.01 | 08-MAR-16:00 | 3377.03 | 16-MAR-12:20 | 66647.92 | 08-MAR-16:00 | 0.00 |
April | 0.235883E+12 | 0.769356E+11 | 720.00 | 0.234631E+12 | 0.125111E+10 | 0.00 | 0.96 | 13-APR-17:00 | 0.02 | 15-APR-07:00 | 391794.46 | 13-APR-17:00 | 391794.46 | 13-APR-17:00 | 27313.87 | 15-APR-01:00 | 134124.23 | 13-APR-17:00 | 0.00 |
May | 0.678380E+11 | 0.252581E+11 | 669.98 | 0.655721E+11 | 0.226590E+10 | 0.00 | 0.39 | 08-MAY-15:30 | 0.00 | 21-MAY-05:53 | 154009.26 | 22-MAY-12:05 | 143549.09 | 30-MAY-12:30 | 14748.38 | 22-MAY-10:30 | 53527.80 | 22-MAY-13:00 | 0.00 |
June | 0.322089E+12 | 0.110579E+12 | 657.99 | 0.298760E+12 | 0.233291E+11 | 0.00 | 0.66 | 30-JUN-14:00 | 0.00 | 01-JUN-07:05 | 317587.35 | 30-JUN-14:00 | 237892.39 | 28-JUN-16:00 | 92093.33 | 30-JUN-14:00 | 105348.51 | 28-JUN-16:00 | 0.00 |
July | 0.801244E+12 | 0.247014E+12 | 742.53 | 0.627767E+12 | 0.173476E+12 | 0.00 | 0.95 | 31-JUL-24:00 | 0.01 | 08-JUL-02:35 | 499520.31 | 31-JUL-24:00 | 329281.59 | 21-JUL-16:00 | 269528.40 | 31-JUL-24:00 | 140072.32 | 22-JUL-15:00 | 0.00 |
August | 0.105388E+13 | 0.307516E+12 | 743.58 | 0.795431E+12 | 0.258445E+12 | 0.00 | 1.00 | 03-AUG-18:30 | 0.01 | 31-AUG-24:00 | 539856.19 | 26-AUG-10:00 | 432918.37 | 13-AUG-13:34 | 309474.39 | 26-AUG-10:00 | 165979.02 | 01-AUG-16:00 | 0.00 |
September | 0.975463E+11 | 0.346792E+11 | 524.97 | 0.877674E+11 | 0.977886E+10 | 0.00 | 0.40 | 01-SEP-12:50 | 0.00 | 02-SEP-22:45 | 177063.93 | 01-SEP-12:50 | 146606.23 | 01-SEP-14:00 | 45511.61 | 05-SEP-14:00 | 56394.30 | 03-SEP-14:00 | 0.00 |
October | 0.743368E+11 | 0.254589E+11 | 708.92 | 0.674859E+11 | 0.685091E+10 | 0.00 | 0.58 | 10-OCT-13:30 | 0.00 | 07-OCT-06:10 | 258740.23 | 10-OCT-13:30 | 234914.11 | 10-OCT-14:00 | 65200.12 | 11-OCT-11:00 | 82721.57 | 01-OCT-16:00 | 0.00 |
November | 0.157066E+11 | 0.733346E+10 | 719.83 | 0.146737E+11 | 0.103294E+10 | 0.00 | 0.28 | 09-NOV-14:00 | 0.01 | 01-NOV-01:10 | 106878.99 | 09-NOV-14:00 | 101053.32 | 09-NOV-14:00 | 7043.07 | 09-NOV-15:10 | 31713.47 | 09-NOV-14:00 | 0.00 |
December | 0.150883E+11 | 0.759385E+10 | 744.00 | 0.146985E+11 | 0.389736E+09 | 0.00 | 0.04 | 24-DEC-14:52 | 0.03 | 04-DEC-13:15 | 9918.71 | 24-DEC-14:52 | 9918.71 | 24-DEC-14:52 | 1684.86 | 25-DEC-09:10 | 4300.42 | 24-DEC-14:52 | 0.00 |
Annual Sum or Average | 0.274668E+13 | 0.868896E+12 | 8391.81 | 0.226611E+13 | 0.480564E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.118753E+11 | 0.592176E+10 | 524.97 | 0.103156E+11 | 0.389736E+09 | 0.00 | 0.02 | 0.00 | 5617.22 | 4891.25 | 766.04 | 2513.28 | 0.00 | ||||||
Maximum of Months | 0.105388E+13 | 0.307516E+12 | 744.00 | 0.795431E+12 | 0.258445E+12 | 0.00 | 1.00 | 0.03 | 539856.19 | 432918.37 | 309474.39 | 165979.02 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.479320E+10 | 0.122250E+10 | 744.00 | 0.479255E+10 | 646057.96 | 0.00 | 0.39 | 01-JAN-16:42 | 0.13 | 21-JAN-07:03 | 3234.71 | 01-JAN-16:42 | 3227.79 | 01-JAN-16:45 | 29.97 | 20-JAN-17:00 | 756.23 | 01-JAN-16:42 | 0.00 |
February | 0.924696E+10 | 0.221055E+10 | 672.00 | 0.924397E+10 | 2987154.51 | 0.00 | 0.58 | 14-FEB-17:00 | 0.38 | 04-FEB-07:25 | 4833.71 | 15-FEB-17:00 | 4833.71 | 15-FEB-17:00 | 81.90 | 17-FEB-11:10 | 1254.13 | 14-FEB-17:00 | 0.00 |
March | 0.157329E+11 | 0.359700E+10 | 744.00 | 0.157273E+11 | 5582607.79 | 0.00 | 0.87 | 12-MAR-17:31 | 0.61 | 04-MAR-07:03 | 7744.21 | 31-MAR-24:00 | 7744.21 | 31-MAR-24:00 | 97.52 | 20-MAR-14:30 | 1844.14 | 12-MAR-17:01 | 0.00 |
April | 0.204666E+11 | 0.476864E+10 | 720.00 | 0.204658E+11 | 797276.68 | 0.00 | 1.00 | 01-APR-16:25 | 0.34 | 30-APR-24:00 | 9078.02 | 16-APR-18:22 | 9078.02 | 16-APR-18:22 | 66.74 | 15-APR-08:00 | 2575.43 | 13-APR-17:00 | 0.00 |
May | 0.611851E+10 | 0.165128E+10 | 744.00 | 0.607908E+10 | 39428784.93 | 0.00 | 0.50 | 31-MAY-23:50 | 0.21 | 05-MAY-06:03 | 4160.77 | 31-MAY-24:00 | 4160.77 | 31-MAY-24:00 | 259.21 | 24-MAY-15:40 | 1070.33 | 20-MAY-18:10 | 0.00 |
June | 0.112902E+11 | 0.326616E+10 | 720.00 | 0.112001E+11 | 90130812.61 | 0.00 | 0.75 | 18-JUN-18:40 | 0.44 | 09-JUN-06:20 | 6124.91 | 30-JUN-23:55 | 6100.73 | 30-JUN-24:00 | 309.39 | 30-JUN-14:00 | 2107.11 | 28-JUN-16:00 | 0.00 |
July | 0.170603E+11 | 0.509875E+10 | 744.00 | 0.168402E+11 | 0.220050E+09 | 0.00 | 0.95 | 04-JUL-18:21 | 0.67 | 08-JUL-06:10 | 8011.98 | 31-JUL-24:00 | 8011.98 | 31-JUL-24:00 | 467.97 | 07-JUL-17:00 | 2823.96 | 21-JUL-17:00 | 0.00 |
August | 0.219087E+11 | 0.619118E+10 | 744.00 | 0.216702E+11 | 0.238539E+09 | 0.00 | 1.00 | 01-AUG-13:30 | 0.32 | 31-AUG-24:00 | 8732.10 | 11-AUG-18:33 | 8634.25 | 30-AUG-18:10 | 438.33 | 23-AUG-14:00 | 3089.53 | 01-AUG-16:00 | 0.00 |
September | 0.624678E+10 | 0.169154E+10 | 720.00 | 0.610220E+10 | 0.144587E+09 | 0.00 | 0.48 | 30-SEP-24:00 | 0.23 | 09-SEP-06:05 | 4144.54 | 30-SEP-24:00 | 4131.97 | 30-SEP-24:00 | 308.78 | 05-SEP-16:20 | 1142.19 | 02-SEP-17:42 | 0.00 |
October | 0.110949E+11 | 0.269211E+10 | 744.00 | 0.110386E+11 | 56385018.91 | 0.00 | 0.69 | 31-OCT-24:00 | 0.40 | 26-OCT-06:53 | 5936.88 | 31-OCT-24:00 | 5936.88 | 31-OCT-24:00 | 304.92 | 02-OCT-17:00 | 1609.80 | 01-OCT-16:01 | 0.00 |
November | 0.151936E+11 | 0.343960E+10 | 720.00 | 0.151820E+11 | 11614944.70 | 0.00 | 0.83 | 19-NOV-16:33 | 0.62 | 10-NOV-07:50 | 7126.38 | 05-NOV-16:50 | 7126.38 | 05-NOV-16:50 | 154.35 | 09-NOV-15:40 | 1609.03 | 19-NOV-16:33 | 0.00 |
December | 0.204277E+11 | 0.456788E+10 | 744.00 | 0.204275E+11 | 159239.47 | 0.00 | 1.00 | 17-DEC-16:02 | 0.80 | 09-DEC-07:05 | 8851.76 | 31-DEC-16:50 | 8851.76 | 31-DEC-16:50 | 24.88 | 27-DEC-17:05 | 1951.53 | 31-DEC-16:50 | 0.00 |
Annual Sum or Average | 0.159580E+12 | 0.403972E+11 | 8760.00 | 0.158769E+12 | 0.810908E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.479320E+10 | 0.122250E+10 | 672.00 | 0.479255E+10 | 159239.47 | 0.00 | 0.39 | 0.13 | 3234.71 | 3227.79 | 24.88 | 756.23 | 0.00 | ||||||
Maximum of Months | 0.219087E+11 | 0.619118E+10 | 744.00 | 0.216702E+11 | 0.238539E+09 | 0.00 | 1.00 | 0.80 | 9078.02 | 9078.02 | 467.97 | 3089.53 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.306390E+11 | 0.806979E+10 | 744.00 | 0.306322E+11 | 6766679.93 | 0.00 | 0.34 | 26-JAN-17:00 | 0.02 | 17-JAN-07:05 | 25906.55 | 26-JAN-17:00 | 25906.55 | 26-JAN-17:00 | 296.35 | 20-JAN-17:00 | 6450.81 | 26-JAN-17:00 | 0.00 |
February | 0.767349E+11 | 0.185851E+11 | 672.00 | 0.767047E+11 | 30229345.68 | 0.00 | 0.57 | 14-FEB-17:00 | 0.27 | 06-FEB-07:03 | 45931.44 | 15-FEB-17:00 | 45931.44 | 15-FEB-17:00 | 799.33 | 17-FEB-11:10 | 11870.47 | 14-FEB-17:00 | 0.00 |
March | 0.142047E+12 | 0.327131E+11 | 744.00 | 0.141990E+12 | 57311370.32 | 0.00 | 0.84 | 31-MAR-23:30 | 0.54 | 04-MAR-07:03 | 72126.57 | 31-MAR-23:30 | 72126.57 | 31-MAR-23:30 | 953.64 | 20-MAR-14:30 | 17029.69 | 12-MAR-17:01 | 0.00 |
April | 0.191608E+12 | 0.448334E+11 | 720.00 | 0.191600E+12 | 8400571.92 | 0.00 | 1.00 | 01-APR-16:40 | 0.30 | 30-APR-24:00 | 86577.21 | 16-APR-18:13 | 86577.21 | 16-APR-18:13 | 679.70 | 15-APR-08:00 | 24687.73 | 13-APR-17:00 | 0.00 |
May | 0.549160E+11 | 0.149403E+11 | 744.00 | 0.545284E+11 | 0.387641E+09 | 0.00 | 0.49 | 31-MAY-23:40 | 0.16 | 05-MAY-06:03 | 39110.34 | 31-MAY-24:00 | 39110.34 | 31-MAY-24:00 | 2535.33 | 24-MAY-15:40 | 10318.99 | 20-MAY-18:10 | 0.00 |
June | 0.105103E+12 | 0.305350E+11 | 720.00 | 0.104210E+12 | 0.893334E+09 | 0.00 | 0.73 | 18-JUN-18:40 | 0.40 | 09-JUN-06:20 | 57808.74 | 30-JUN-23:55 | 57566.73 | 30-JUN-24:00 | 3008.22 | 30-JUN-14:00 | 19858.96 | 28-JUN-16:00 | 0.00 |
July | 0.159905E+12 | 0.479356E+11 | 744.00 | 0.157717E+12 | 0.218802E+10 | 0.00 | 0.93 | 04-JUL-18:31 | 0.65 | 08-JUL-06:10 | 75852.22 | 31-JUL-24:00 | 75852.22 | 31-JUL-24:00 | 4559.94 | 07-JUL-17:00 | 26309.11 | 21-JUL-18:10 | 0.00 |
August | 0.207324E+12 | 0.587365E+11 | 744.00 | 0.204944E+12 | 0.237952E+10 | 0.00 | 1.00 | 01-AUG-14:00 | 0.29 | 31-AUG-24:00 | 83374.56 | 11-AUG-18:20 | 82763.48 | 30-AUG-18:10 | 4343.14 | 23-AUG-14:00 | 29611.54 | 01-AUG-16:00 | 0.00 |
September | 0.563616E+11 | 0.153736E+11 | 720.00 | 0.549415E+11 | 0.142011E+10 | 0.00 | 0.48 | 30-SEP-24:00 | 0.20 | 09-SEP-06:05 | 39236.16 | 30-SEP-23:30 | 39094.28 | 30-SEP-24:00 | 3047.47 | 05-SEP-16:20 | 10846.33 | 02-SEP-17:42 | 0.00 |
October | 0.996049E+11 | 0.243556E+11 | 744.00 | 0.990476E+11 | 0.557233E+09 | 0.00 | 0.67 | 31-OCT-24:00 | 0.33 | 26-OCT-06:53 | 54984.90 | 31-OCT-24:00 | 54984.90 | 31-OCT-24:00 | 2999.64 | 02-OCT-17:00 | 15145.70 | 01-OCT-16:01 | 0.00 |
November | 0.134366E+12 | 0.307052E+11 | 720.00 | 0.134250E+12 | 0.115764E+09 | 0.00 | 0.78 | 19-NOV-16:45 | 0.53 | 27-NOV-07:03 | 64416.92 | 02-NOV-16:40 | 64198.66 | 05-NOV-16:50 | 1496.96 | 09-NOV-15:40 | 14645.46 | 19-NOV-16:45 | 0.00 |
December | 0.178174E+12 | 0.403557E+11 | 744.00 | 0.178172E+12 | 1939114.17 | 0.00 | 0.96 | 17-DEC-16:42 | 0.70 | 27-DEC-07:05 | 79555.18 | 31-DEC-16:45 | 79555.18 | 31-DEC-16:45 | 249.56 | 27-DEC-17:05 | 17838.47 | 17-DEC-16:42 | 0.00 |
Annual Sum or Average | 0.143678E+13 | 0.367139E+12 | 8760.00 | 0.142874E+13 | 0.804627E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.306390E+11 | 0.806979E+10 | 672.00 | 0.306322E+11 | 1939114.17 | 0.00 | 0.34 | 0.02 | 25906.55 | 25906.55 | 249.56 | 6450.81 | 0.00 | ||||||
Maximum of Months | 0.207324E+12 | 0.587365E+11 | 744.00 | 0.204944E+12 | 0.237952E+10 | 0.00 | 1.00 | 0.70 | 86577.21 | 86577.21 | 4559.94 | 29611.54 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.132094E+10 | 0.361790E+09 | 507.64 | 0.132041E+10 | 528091.50 | 0.00 | 0.33 | 26-JAN-17:00 | 0.00 | 01-JAN-00:10 | 2501.36 | 26-JAN-17:00 | 2501.36 | 26-JAN-17:00 | 26.24 | 20-JAN-17:00 | 625.93 | 26-JAN-17:00 | 0.00 |
February | 0.625037E+10 | 0.153879E+10 | 671.92 | 0.624746E+10 | 2905218.93 | 0.00 | 0.57 | 14-FEB-17:00 | 0.00 | 06-FEB-02:15 | 4626.23 | 15-FEB-17:00 | 4626.23 | 15-FEB-17:00 | 77.35 | 17-FEB-11:20 | 1194.52 | 14-FEB-17:00 | 0.00 |
March | 0.132752E+11 | 0.308601E+10 | 744.00 | 0.132696E+11 | 5591451.32 | 0.00 | 0.81 | 12-MAR-17:22 | 0.43 | 04-MAR-07:03 | 6902.30 | 31-MAR-23:20 | 6902.30 | 31-MAR-23:20 | 93.84 | 20-MAR-14:30 | 1690.90 | 12-MAR-17:01 | 0.00 |
April | 0.187721E+11 | 0.442194E+10 | 720.00 | 0.187713E+11 | 810857.93 | 0.00 | 1.00 | 01-APR-16:50 | 0.28 | 30-APR-24:00 | 8795.44 | 16-APR-18:00 | 8795.44 | 16-APR-18:00 | 66.33 | 15-APR-08:00 | 2520.84 | 13-APR-17:00 | 0.00 |
May | 0.534281E+10 | 0.146594E+10 | 744.00 | 0.530417E+10 | 38632917.45 | 0.00 | 0.48 | 31-MAY-23:20 | 0.09 | 05-MAY-06:03 | 3849.96 | 31-MAY-23:50 | 3849.96 | 31-MAY-23:50 | 252.32 | 24-MAY-15:40 | 1086.50 | 20-MAY-18:10 | 0.00 |
June | 0.105583E+11 | 0.308236E+10 | 720.00 | 0.104691E+11 | 89287137.27 | 0.00 | 0.75 | 18-JUN-18:40 | 0.34 | 09-JUN-06:10 | 5782.57 | 30-JUN-23:55 | 5757.99 | 30-JUN-24:00 | 303.88 | 30-JUN-14:00 | 2043.65 | 28-JUN-16:00 | 0.00 |
July | 0.161406E+11 | 0.485227E+10 | 744.00 | 0.159219E+11 | 0.218787E+09 | 0.00 | 0.96 | 04-JUL-18:21 | 0.62 | 08-JUL-06:10 | 7634.41 | 04-JUL-18:35 | 7634.41 | 04-JUL-18:35 | 458.60 | 07-JUL-17:00 | 2773.07 | 04-JUL-17:51 | 0.00 |
August | 0.208347E+11 | 0.592204E+10 | 744.00 | 0.205968E+11 | 0.237901E+09 | 0.00 | 1.00 | 01-AUG-14:20 | 0.28 | 31-AUG-24:00 | 8452.38 | 11-AUG-18:10 | 8425.92 | 30-AUG-18:10 | 434.91 | 23-AUG-14:00 | 3023.27 | 01-AUG-16:00 | 0.00 |
September | 0.556642E+10 | 0.152960E+10 | 720.00 | 0.542438E+10 | 0.142034E+09 | 0.00 | 0.46 | 30-SEP-23:30 | 0.15 | 09-SEP-06:25 | 3892.03 | 30-SEP-23:20 | 3870.05 | 30-SEP-23:40 | 305.94 | 05-SEP-16:20 | 1137.31 | 02-SEP-17:42 | 0.00 |
October | 0.932611E+10 | 0.230265E+10 | 744.00 | 0.927053E+10 | 55577300.95 | 0.00 | 0.63 | 31-OCT-23:30 | 0.21 | 26-OCT-06:05 | 5289.42 | 31-OCT-23:30 | 5289.42 | 31-OCT-23:30 | 300.90 | 02-OCT-17:00 | 1583.24 | 01-OCT-16:01 | 0.00 |
November | 0.120421E+11 | 0.278820E+10 | 720.00 | 0.120307E+11 | 11476829.45 | 0.00 | 0.73 | 19-NOV-16:45 | 0.38 | 27-NOV-07:03 | 6450.21 | 02-NOV-16:40 | 6372.27 | 02-NOV-16:50 | 149.06 | 09-NOV-15:40 | 1401.54 | 03-NOV-16:50 | 0.00 |
December | 0.158117E+11 | 0.364124E+10 | 744.00 | 0.158115E+11 | 171795.99 | 0.00 | 0.88 | 31-DEC-16:42 | 0.54 | 26-DEC-04:30 | 7779.54 | 29-DEC-16:40 | 7779.54 | 29-DEC-16:40 | 24.68 | 27-DEC-17:05 | 1685.87 | 31-DEC-16:42 | 0.00 |
Annual Sum or Average | 0.135242E+12 | 0.349928E+11 | 8523.55 | 0.134438E+12 | 0.803703E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.132094E+10 | 0.361790E+09 | 507.64 | 0.132041E+10 | 171795.99 | 0.00 | 0.33 | 0.00 | 2501.36 | 2501.36 | 24.68 | 625.93 | 0.00 | ||||||
Maximum of Months | 0.208347E+11 | 0.592204E+10 | 744.00 | 0.205968E+11 | 0.237901E+09 | 0.00 | 1.00 | 0.62 | 8795.44 | 8795.44 | 458.60 | 3023.27 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.63 | 0.00 | 159.63 | 22.92 | 663.47 | 0.00 | 0.00 | 0.00 |
February | 199.51 | 0.00 | 199.51 | 58.98 | 597.72 | 0.00 | 0.00 | 0.00 |
March | 251.66 | 0.00 | 251.66 | 144.65 | 468.26 | 0.00 | 0.00 | 0.00 |
April | 319.28 | 2.73 | 316.55 | 247.74 | 309.34 | 0.00 | 0.00 | 0.00 |
May | 347.06 | 22.38 | 324.68 | 354.04 | 218.57 | 0.00 | 0.00 | 0.00 |
June | 394.35 | 64.54 | 329.82 | 548.89 | 147.74 | 0.00 | 0.00 | 0.00 |
July | 361.96 | 30.13 | 331.83 | 542.20 | 105.96 | 0.00 | 0.00 | 0.00 |
August | 335.77 | 7.52 | 328.26 | 460.04 | 116.30 | 0.00 | 0.00 | 0.00 |
September | 268.52 | 0.07 | 268.45 | 313.95 | 200.03 | 0.00 | 0.00 | 0.00 |
October | 200.37 | 0.00 | 200.37 | 136.04 | 366.24 | 0.00 | 0.00 | 0.00 |
November | 170.16 | 0.00 | 170.16 | 38.76 | 538.62 | 0.00 | 0.00 | 0.00 |
December | 135.87 | 0.00 | 135.87 | 4.59 | 714.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 262.24 | 10.63 | 251.61 | 240.36 | 369.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.87 | 0.00 | 135.87 | 4.59 | 105.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.35 | 64.54 | 331.83 | 548.89 | 714.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.63 | 0.00 | 159.63 | 22.91 | 663.47 | 0.00 | 0.00 | 0.00 |
February | 199.51 | 0.00 | 199.51 | 58.98 | 597.72 | 0.00 | 0.00 | 0.00 |
March | 251.66 | 0.00 | 251.66 | 144.65 | 468.26 | 0.00 | 0.00 | 0.00 |
April | 319.28 | 2.73 | 316.55 | 247.74 | 309.34 | 0.00 | 0.00 | 0.00 |
May | 347.06 | 22.38 | 324.68 | 354.04 | 218.57 | 0.00 | 0.00 | 0.00 |
June | 394.35 | 64.54 | 329.82 | 548.89 | 147.74 | 0.00 | 0.00 | 0.00 |
July | 361.96 | 30.13 | 331.83 | 542.20 | 105.96 | 0.00 | 0.00 | 0.00 |
August | 335.77 | 7.52 | 328.26 | 460.04 | 116.30 | 0.00 | 0.00 | 0.00 |
September | 268.52 | 0.07 | 268.45 | 313.95 | 200.03 | 0.00 | 0.00 | 0.00 |
October | 200.37 | 0.00 | 200.37 | 136.04 | 366.24 | 0.00 | 0.00 | 0.00 |
November | 170.16 | 0.00 | 170.16 | 38.76 | 538.62 | 0.00 | 0.00 | 0.00 |
December | 135.87 | 0.00 | 135.87 | 4.59 | 714.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 262.24 | 10.63 | 251.61 | 240.36 | 369.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.87 | 0.00 | 135.87 | 4.59 | 105.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.35 | 64.54 | 331.83 | 548.89 | 714.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.63 | 0.00 | 159.63 | 22.92 | 663.47 | 0.00 | 0.00 | 0.00 |
February | 199.51 | 0.00 | 199.51 | 58.98 | 597.72 | 0.00 | 0.00 | 0.00 |
March | 251.66 | 0.00 | 251.66 | 144.65 | 468.26 | 0.00 | 0.00 | 0.00 |
April | 319.28 | 2.73 | 316.55 | 247.74 | 309.34 | 0.00 | 0.00 | 0.00 |
May | 347.06 | 22.38 | 324.68 | 354.04 | 218.57 | 0.00 | 0.00 | 0.00 |
June | 394.35 | 64.54 | 329.82 | 548.89 | 147.74 | 0.00 | 0.00 | 0.00 |
July | 361.96 | 30.13 | 331.83 | 542.20 | 105.96 | 0.00 | 0.00 | 0.00 |
August | 335.77 | 7.52 | 328.26 | 460.04 | 116.30 | 0.00 | 0.00 | 0.00 |
September | 268.52 | 0.07 | 268.45 | 313.95 | 200.03 | 0.00 | 0.00 | 0.00 |
October | 200.37 | 0.00 | 200.37 | 136.04 | 366.24 | 0.00 | 0.00 | 0.00 |
November | 170.16 | 0.00 | 170.16 | 38.76 | 538.62 | 0.00 | 0.00 | 0.00 |
December | 135.87 | 0.00 | 135.87 | 4.59 | 714.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 262.24 | 10.63 | 251.61 | 240.36 | 369.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.87 | 0.00 | 135.87 | 4.59 | 105.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.35 | 64.54 | 331.83 | 548.89 | 714.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.63 | 0.00 | 159.63 | 22.91 | 663.47 | 0.00 | 0.00 | 0.00 |
February | 199.51 | 0.00 | 199.51 | 58.98 | 597.72 | 0.00 | 0.00 | 0.00 |
March | 251.66 | 0.00 | 251.66 | 144.65 | 468.26 | 0.00 | 0.00 | 0.00 |
April | 319.28 | 2.73 | 316.55 | 247.74 | 309.34 | 0.00 | 0.00 | 0.00 |
May | 347.06 | 22.38 | 324.68 | 354.04 | 218.57 | 0.00 | 0.00 | 0.00 |
June | 394.35 | 64.54 | 329.82 | 548.89 | 147.74 | 0.00 | 0.00 | 0.00 |
July | 361.96 | 30.13 | 331.83 | 542.20 | 105.96 | 0.00 | 0.00 | 0.00 |
August | 335.77 | 7.52 | 328.26 | 460.04 | 116.30 | 0.00 | 0.00 | 0.00 |
September | 268.52 | 0.07 | 268.45 | 313.95 | 200.03 | 0.00 | 0.00 | 0.00 |
October | 200.37 | 0.00 | 200.37 | 136.04 | 366.24 | 0.00 | 0.00 | 0.00 |
November | 170.16 | 0.00 | 170.16 | 38.76 | 538.62 | 0.00 | 0.00 | 0.00 |
December | 135.87 | 0.00 | 135.87 | 4.59 | 714.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 262.24 | 10.63 | 251.61 | 240.36 | 369.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.87 | 0.00 | 135.87 | 4.59 | 105.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.35 | 64.54 | 331.83 | 548.89 | 714.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.63 | 0.00 | 159.63 | 22.91 | 663.44 | 0.00 | 0.00 | 0.00 |
February | 199.51 | 0.00 | 199.51 | 58.98 | 597.70 | 0.00 | 0.00 | 0.00 |
March | 251.65 | 0.00 | 251.65 | 144.65 | 468.24 | 0.00 | 0.00 | 0.00 |
April | 319.27 | 2.73 | 316.53 | 247.73 | 309.33 | 0.00 | 0.00 | 0.00 |
May | 347.05 | 22.38 | 324.67 | 354.03 | 218.56 | 0.00 | 0.00 | 0.00 |
June | 394.34 | 64.53 | 329.81 | 548.87 | 147.73 | 0.00 | 0.00 | 0.00 |
July | 361.94 | 30.12 | 331.82 | 542.18 | 105.96 | 0.00 | 0.00 | 0.00 |
August | 335.76 | 7.52 | 328.24 | 460.02 | 116.30 | 0.00 | 0.00 | 0.00 |
September | 268.50 | 0.07 | 268.44 | 313.94 | 200.02 | 0.00 | 0.00 | 0.00 |
October | 200.36 | 0.00 | 200.36 | 136.04 | 366.23 | 0.00 | 0.00 | 0.00 |
November | 170.15 | 0.00 | 170.15 | 38.76 | 538.60 | 0.00 | 0.00 | 0.00 |
December | 135.87 | 0.00 | 135.87 | 4.59 | 714.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 262.23 | 10.63 | 251.60 | 240.35 | 369.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.87 | 0.00 | 135.87 | 4.59 | 105.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.34 | 64.53 | 331.82 | 548.87 | 714.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 491.21 | 274.63 | 216.58 | 403.25 | 672.11 | 0.00 | 0.00 | 0.00 |
February | 596.81 | 321.74 | 275.06 | 546.56 | 609.20 | 0.00 | 0.00 | 0.00 |
March | 787.28 | 447.55 | 339.72 | 833.27 | 477.52 | 0.00 | 0.00 | 0.00 |
April | 1075.58 | 612.75 | 462.83 | 1267.59 | 325.30 | 0.00 | 0.00 | 0.00 |
May | 1026.33 | 584.90 | 441.43 | 1284.07 | 247.43 | 0.00 | 0.00 | 0.00 |
June | 1106.46 | 681.63 | 424.83 | 1524.64 | 162.88 | 0.00 | 0.00 | 0.00 |
July | 1023.83 | 585.47 | 438.36 | 1469.02 | 117.20 | 0.00 | 0.00 | 0.00 |
August | 1013.15 | 558.57 | 454.58 | 1413.40 | 126.18 | 0.00 | 0.00 | 0.00 |
September | 843.28 | 471.82 | 371.46 | 1110.33 | 213.40 | 0.00 | 0.00 | 0.00 |
October | 733.39 | 465.31 | 268.08 | 841.10 | 374.82 | 0.00 | 0.00 | 0.00 |
November | 573.18 | 336.97 | 236.21 | 543.11 | 547.82 | 0.00 | 0.00 | 0.00 |
December | 464.44 | 282.65 | 181.79 | 389.39 | 716.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 812.04 | 469.25 | 342.79 | 970.72 | 381.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 464.44 | 274.63 | 181.79 | 389.39 | 117.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.46 | 681.63 | 462.83 | 1524.64 | 716.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 491.21 | 274.63 | 216.58 | 403.25 | 672.11 | 0.00 | 0.00 | 0.00 |
February | 596.81 | 321.74 | 275.06 | 546.56 | 609.20 | 0.00 | 0.00 | 0.00 |
March | 787.28 | 447.55 | 339.72 | 833.27 | 477.52 | 0.00 | 0.00 | 0.00 |
April | 1075.58 | 612.75 | 462.83 | 1267.59 | 325.30 | 0.00 | 0.00 | 0.00 |
May | 1026.33 | 584.90 | 441.43 | 1284.07 | 247.43 | 0.00 | 0.00 | 0.00 |
June | 1106.46 | 681.63 | 424.83 | 1524.64 | 162.88 | 0.00 | 0.00 | 0.00 |
July | 1023.83 | 585.47 | 438.36 | 1469.02 | 117.20 | 0.00 | 0.00 | 0.00 |
August | 1013.15 | 558.57 | 454.58 | 1413.40 | 126.18 | 0.00 | 0.00 | 0.00 |
September | 843.28 | 471.82 | 371.46 | 1110.33 | 213.40 | 0.00 | 0.00 | 0.00 |
October | 733.39 | 465.31 | 268.08 | 841.10 | 374.82 | 0.00 | 0.00 | 0.00 |
November | 573.18 | 336.97 | 236.21 | 543.11 | 547.82 | 0.00 | 0.00 | 0.00 |
December | 464.44 | 282.65 | 181.79 | 389.39 | 716.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 812.04 | 469.25 | 342.79 | 970.72 | 381.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 464.44 | 274.63 | 181.79 | 389.39 | 117.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.46 | 681.63 | 462.83 | 1524.64 | 716.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 491.20 | 274.63 | 216.57 | 403.24 | 672.10 | 0.00 | 0.00 | 0.00 |
February | 596.79 | 321.74 | 275.06 | 546.55 | 609.19 | 0.00 | 0.00 | 0.00 |
March | 787.26 | 447.54 | 339.72 | 833.25 | 477.51 | 0.00 | 0.00 | 0.00 |
April | 1075.56 | 612.74 | 462.82 | 1267.57 | 325.30 | 0.00 | 0.00 | 0.00 |
May | 1026.31 | 584.89 | 441.43 | 1284.05 | 247.43 | 0.00 | 0.00 | 0.00 |
June | 1106.44 | 681.62 | 424.82 | 1524.62 | 162.88 | 0.00 | 0.00 | 0.00 |
July | 1023.81 | 585.46 | 438.35 | 1469.00 | 117.20 | 0.00 | 0.00 | 0.00 |
August | 1013.13 | 558.56 | 454.57 | 1413.38 | 126.18 | 0.00 | 0.00 | 0.00 |
September | 843.26 | 471.81 | 371.45 | 1110.31 | 213.39 | 0.00 | 0.00 | 0.00 |
October | 733.38 | 465.30 | 268.08 | 841.08 | 374.81 | 0.00 | 0.00 | 0.00 |
November | 573.17 | 336.96 | 236.21 | 543.10 | 547.81 | 0.00 | 0.00 | 0.00 |
December | 464.43 | 282.65 | 181.78 | 389.38 | 716.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 812.02 | 469.24 | 342.78 | 970.70 | 381.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 464.43 | 274.63 | 181.78 | 389.38 | 117.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.44 | 681.62 | 462.82 | 1524.62 | 716.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1180.17 | 918.33 | 261.83 | 1346.85 | 588.48 | 0.00 | 0.00 | 0.00 |
February | 1154.96 | 843.66 | 311.30 | 1349.09 | 546.42 | 0.00 | 0.00 | 0.00 |
March | 851.08 | 514.53 | 336.55 | 1015.77 | 447.38 | 0.00 | 0.00 | 0.00 |
April | 663.74 | 272.45 | 391.29 | 823.35 | 320.93 | 0.00 | 0.00 | 0.00 |
May | 442.66 | 97.38 | 345.28 | 552.93 | 232.82 | 0.00 | 0.00 | 0.00 |
June | 374.45 | 46.15 | 328.30 | 549.69 | 156.82 | 0.00 | 0.00 | 0.00 |
July | 414.35 | 66.17 | 348.18 | 657.69 | 109.19 | 0.00 | 0.00 | 0.00 |
August | 569.76 | 185.20 | 384.56 | 870.69 | 123.40 | 0.00 | 0.00 | 0.00 |
September | 787.86 | 439.33 | 348.52 | 1121.19 | 205.78 | 0.00 | 0.00 | 0.00 |
October | 1077.88 | 793.86 | 284.03 | 1377.63 | 345.88 | 0.00 | 0.00 | 0.00 |
November | 1200.56 | 921.42 | 279.13 | 1414.23 | 484.52 | 0.00 | 0.00 | 0.00 |
December | 1280.45 | 1056.24 | 224.21 | 1472.94 | 612.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.35 | 511.19 | 320.16 | 1044.27 | 346.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 374.45 | 46.15 | 224.21 | 549.69 | 109.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1280.45 | 1056.24 | 391.29 | 1472.94 | 612.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1180.17 | 918.33 | 261.83 | 1346.85 | 588.48 | 0.00 | 0.00 | 0.00 |
February | 1154.96 | 843.66 | 311.30 | 1349.09 | 546.42 | 0.00 | 0.00 | 0.00 |
March | 851.08 | 514.53 | 336.55 | 1015.77 | 447.38 | 0.00 | 0.00 | 0.00 |
April | 663.74 | 272.45 | 391.28 | 823.35 | 320.93 | 0.00 | 0.00 | 0.00 |
May | 442.66 | 97.38 | 345.28 | 552.93 | 232.82 | 0.00 | 0.00 | 0.00 |
June | 374.45 | 46.15 | 328.30 | 549.69 | 156.82 | 0.00 | 0.00 | 0.00 |
July | 414.35 | 66.17 | 348.18 | 657.69 | 109.19 | 0.00 | 0.00 | 0.00 |
August | 569.76 | 185.20 | 384.56 | 870.69 | 123.40 | 0.00 | 0.00 | 0.00 |
September | 787.86 | 439.33 | 348.52 | 1121.19 | 205.78 | 0.00 | 0.00 | 0.00 |
October | 1077.88 | 793.85 | 284.03 | 1377.62 | 345.88 | 0.00 | 0.00 | 0.00 |
November | 1200.56 | 921.42 | 279.13 | 1414.23 | 484.52 | 0.00 | 0.00 | 0.00 |
December | 1280.45 | 1056.24 | 224.21 | 1472.94 | 612.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.35 | 511.19 | 320.16 | 1044.27 | 346.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 374.45 | 46.15 | 224.21 | 549.69 | 109.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1280.45 | 1056.24 | 391.28 | 1472.94 | 612.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1180.17 | 918.33 | 261.83 | 1346.85 | 588.48 | 0.00 | 0.00 | 0.00 |
February | 1154.96 | 843.66 | 311.30 | 1349.09 | 546.42 | 0.00 | 0.00 | 0.00 |
March | 851.08 | 514.53 | 336.55 | 1015.77 | 447.38 | 0.00 | 0.00 | 0.00 |
April | 663.74 | 272.45 | 391.29 | 823.35 | 320.93 | 0.00 | 0.00 | 0.00 |
May | 442.66 | 97.38 | 345.28 | 552.93 | 232.82 | 0.00 | 0.00 | 0.00 |
June | 374.45 | 46.15 | 328.30 | 549.69 | 156.82 | 0.00 | 0.00 | 0.00 |
July | 414.35 | 66.17 | 348.18 | 657.69 | 109.19 | 0.00 | 0.00 | 0.00 |
August | 569.76 | 185.20 | 384.56 | 870.69 | 123.40 | 0.00 | 0.00 | 0.00 |
September | 787.86 | 439.33 | 348.52 | 1121.19 | 205.78 | 0.00 | 0.00 | 0.00 |
October | 1077.88 | 793.86 | 284.03 | 1377.63 | 345.88 | 0.00 | 0.00 | 0.00 |
November | 1200.56 | 921.42 | 279.13 | 1414.23 | 484.52 | 0.00 | 0.00 | 0.00 |
December | 1280.45 | 1056.24 | 224.21 | 1472.94 | 612.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.35 | 511.19 | 320.16 | 1044.27 | 346.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 374.45 | 46.15 | 224.21 | 549.69 | 109.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1280.45 | 1056.24 | 391.29 | 1472.94 | 612.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1180.17 | 918.33 | 261.83 | 1346.85 | 588.48 | 0.00 | 0.00 | 0.00 |
February | 1154.96 | 843.66 | 311.30 | 1349.09 | 546.42 | 0.00 | 0.00 | 0.00 |
March | 851.08 | 514.53 | 336.55 | 1015.77 | 447.38 | 0.00 | 0.00 | 0.00 |
April | 663.74 | 272.45 | 391.28 | 823.35 | 320.93 | 0.00 | 0.00 | 0.00 |
May | 442.66 | 97.38 | 345.28 | 552.93 | 232.82 | 0.00 | 0.00 | 0.00 |
June | 374.45 | 46.15 | 328.30 | 549.69 | 156.82 | 0.00 | 0.00 | 0.00 |
July | 414.35 | 66.17 | 348.18 | 657.69 | 109.19 | 0.00 | 0.00 | 0.00 |
August | 569.76 | 185.20 | 384.56 | 870.69 | 123.40 | 0.00 | 0.00 | 0.00 |
September | 787.86 | 439.33 | 348.52 | 1121.19 | 205.78 | 0.00 | 0.00 | 0.00 |
October | 1077.88 | 793.85 | 284.03 | 1377.62 | 345.88 | 0.00 | 0.00 | 0.00 |
November | 1200.56 | 921.42 | 279.13 | 1414.23 | 484.52 | 0.00 | 0.00 | 0.00 |
December | 1280.45 | 1056.24 | 224.21 | 1472.94 | 612.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.35 | 511.19 | 320.16 | 1044.27 | 346.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 374.45 | 46.15 | 224.21 | 549.69 | 109.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1280.45 | 1056.24 | 391.28 | 1472.94 | 612.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1180.12 | 918.30 | 261.82 | 1346.80 | 588.46 | 0.00 | 0.00 | 0.00 |
February | 1154.91 | 843.62 | 311.29 | 1349.04 | 546.40 | 0.00 | 0.00 | 0.00 |
March | 851.05 | 514.51 | 336.54 | 1015.73 | 447.36 | 0.00 | 0.00 | 0.00 |
April | 663.71 | 272.44 | 391.27 | 823.32 | 320.91 | 0.00 | 0.00 | 0.00 |
May | 442.64 | 97.37 | 345.27 | 552.91 | 232.81 | 0.00 | 0.00 | 0.00 |
June | 374.44 | 46.15 | 328.29 | 549.67 | 156.81 | 0.00 | 0.00 | 0.00 |
July | 414.33 | 66.17 | 348.17 | 657.67 | 109.18 | 0.00 | 0.00 | 0.00 |
August | 569.74 | 185.19 | 384.54 | 870.66 | 123.39 | 0.00 | 0.00 | 0.00 |
September | 787.83 | 439.31 | 348.51 | 1121.14 | 205.77 | 0.00 | 0.00 | 0.00 |
October | 1077.84 | 793.82 | 284.02 | 1377.57 | 345.86 | 0.00 | 0.00 | 0.00 |
November | 1200.51 | 921.39 | 279.12 | 1414.17 | 484.50 | 0.00 | 0.00 | 0.00 |
December | 1280.40 | 1056.19 | 224.20 | 1472.88 | 612.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.32 | 511.17 | 320.15 | 1044.23 | 346.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 374.44 | 46.15 | 224.20 | 549.67 | 109.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1280.40 | 1056.19 | 391.27 | 1472.88 | 612.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.66 | 288.93 | 217.73 | 461.08 | 749.79 | 0.00 | 0.00 | 0.00 |
February | 652.24 | 376.78 | 275.46 | 642.83 | 696.44 | 0.00 | 0.00 | 0.00 |
March | 728.48 | 387.78 | 340.70 | 764.81 | 562.67 | 0.00 | 0.00 | 0.00 |
April | 929.76 | 494.82 | 434.94 | 1061.84 | 398.78 | 0.00 | 0.00 | 0.00 |
May | 881.55 | 454.23 | 427.31 | 1084.06 | 280.45 | 0.00 | 0.00 | 0.00 |
June | 945.02 | 527.31 | 417.71 | 1307.16 | 201.04 | 0.00 | 0.00 | 0.00 |
July | 852.37 | 417.14 | 435.23 | 1227.25 | 142.90 | 0.00 | 0.00 | 0.00 |
August | 870.98 | 402.86 | 468.11 | 1211.60 | 165.55 | 0.00 | 0.00 | 0.00 |
September | 786.70 | 414.32 | 372.37 | 1041.11 | 247.52 | 0.00 | 0.00 | 0.00 |
October | 719.72 | 447.33 | 272.39 | 840.48 | 441.04 | 0.00 | 0.00 | 0.00 |
November | 564.98 | 332.39 | 232.59 | 545.83 | 631.55 | 0.00 | 0.00 | 0.00 |
December | 488.59 | 306.40 | 182.19 | 433.71 | 827.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 743.99 | 404.00 | 339.99 | 886.00 | 444.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 488.59 | 288.93 | 182.19 | 433.71 | 142.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 945.02 | 527.31 | 468.11 | 1307.16 | 827.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.66 | 288.93 | 217.73 | 461.08 | 749.79 | 0.00 | 0.00 | 0.00 |
February | 652.24 | 376.78 | 275.46 | 642.83 | 696.44 | 0.00 | 0.00 | 0.00 |
March | 728.48 | 387.78 | 340.70 | 764.81 | 562.67 | 0.00 | 0.00 | 0.00 |
April | 929.76 | 494.82 | 434.94 | 1061.84 | 398.78 | 0.00 | 0.00 | 0.00 |
May | 881.55 | 454.23 | 427.31 | 1084.06 | 280.45 | 0.00 | 0.00 | 0.00 |
June | 945.02 | 527.31 | 417.71 | 1307.16 | 201.04 | 0.00 | 0.00 | 0.00 |
July | 852.37 | 417.14 | 435.23 | 1227.25 | 142.90 | 0.00 | 0.00 | 0.00 |
August | 870.98 | 402.86 | 468.11 | 1211.60 | 165.55 | 0.00 | 0.00 | 0.00 |
September | 786.70 | 414.32 | 372.37 | 1041.11 | 247.52 | 0.00 | 0.00 | 0.00 |
October | 719.72 | 447.33 | 272.39 | 840.48 | 441.04 | 0.00 | 0.00 | 0.00 |
November | 564.98 | 332.39 | 232.59 | 545.83 | 631.55 | 0.00 | 0.00 | 0.00 |
December | 488.59 | 306.40 | 182.19 | 433.71 | 827.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 743.99 | 404.00 | 339.99 | 886.00 | 444.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 488.59 | 288.93 | 182.19 | 433.71 | 142.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 945.02 | 527.31 | 468.11 | 1307.16 | 827.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.65 | 288.93 | 217.72 | 461.07 | 749.77 | 0.00 | 0.00 | 0.00 |
February | 652.23 | 376.77 | 275.46 | 642.81 | 696.42 | 0.00 | 0.00 | 0.00 |
March | 728.47 | 387.78 | 340.69 | 764.80 | 562.66 | 0.00 | 0.00 | 0.00 |
April | 929.74 | 494.81 | 434.93 | 1061.82 | 398.78 | 0.00 | 0.00 | 0.00 |
May | 881.53 | 454.23 | 427.30 | 1084.04 | 280.45 | 0.00 | 0.00 | 0.00 |
June | 945.00 | 527.30 | 417.70 | 1307.13 | 201.03 | 0.00 | 0.00 | 0.00 |
July | 852.36 | 417.13 | 435.23 | 1227.23 | 142.90 | 0.00 | 0.00 | 0.00 |
August | 870.96 | 402.85 | 468.11 | 1211.57 | 165.55 | 0.00 | 0.00 | 0.00 |
September | 786.68 | 414.31 | 372.37 | 1041.09 | 247.51 | 0.00 | 0.00 | 0.00 |
October | 719.71 | 447.32 | 272.38 | 840.46 | 441.04 | 0.00 | 0.00 | 0.00 |
November | 564.97 | 332.38 | 232.58 | 545.82 | 631.54 | 0.00 | 0.00 | 0.00 |
December | 488.58 | 306.39 | 182.19 | 433.70 | 827.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 743.97 | 403.99 | 339.98 | 885.98 | 444.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 488.58 | 288.93 | 182.19 | 433.70 | 142.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 945.00 | 527.30 | 468.11 | 1307.13 | 827.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 798.15 | 0.00 | 798.15 | 172.90 | 3018.95 | 0.00 | 0.00 | 0.00 |
February | 997.56 | 0.00 | 997.56 | 366.08 | 2732.89 | 0.00 | 0.00 | 0.00 |
March | 1258.29 | 0.00 | 1258.29 | 783.59 | 2163.20 | 0.00 | 0.00 | 0.00 |
April | 1596.38 | 13.67 | 1582.72 | 1285.77 | 1439.40 | 0.00 | 0.00 | 0.00 |
May | 1735.28 | 111.88 | 1623.40 | 1793.90 | 1044.81 | 0.00 | 0.00 | 0.00 |
June | 1971.75 | 322.67 | 1649.08 | 2788.79 | 691.77 | 0.00 | 0.00 | 0.00 |
July | 1809.76 | 150.63 | 1659.13 | 2774.55 | 465.95 | 0.00 | 0.00 | 0.00 |
August | 1678.85 | 37.59 | 1641.27 | 2350.70 | 527.72 | 0.00 | 0.00 | 0.00 |
September | 1342.56 | 0.34 | 1342.22 | 1595.36 | 941.71 | 0.00 | 0.00 | 0.00 |
October | 1001.82 | 0.00 | 1001.82 | 727.63 | 1681.21 | 0.00 | 0.00 | 0.00 |
November | 850.78 | 0.00 | 850.78 | 248.90 | 2410.90 | 0.00 | 0.00 | 0.00 |
December | 679.35 | 0.00 | 679.35 | 55.05 | 3155.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1311.19 | 53.16 | 1258.03 | 1249.93 | 1684.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 679.35 | 0.00 | 679.35 | 55.05 | 465.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1971.75 | 322.67 | 1659.13 | 2788.79 | 3155.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1473.60 | 823.88 | 649.72 | 1231.90 | 1895.65 | 0.00 | 0.00 | 0.00 |
February | 1790.40 | 965.22 | 825.18 | 1649.91 | 1735.64 | 0.00 | 0.00 | 0.00 |
March | 2361.81 | 1342.64 | 1019.16 | 2489.93 | 1383.09 | 0.00 | 0.00 | 0.00 |
April | 3226.71 | 1838.24 | 1388.47 | 3777.19 | 957.86 | 0.00 | 0.00 | 0.00 |
May | 3078.96 | 1754.68 | 1324.29 | 3824.38 | 727.53 | 0.00 | 0.00 | 0.00 |
June | 3319.36 | 2044.88 | 1274.47 | 4562.84 | 468.82 | 0.00 | 0.00 | 0.00 |
July | 3071.46 | 1756.39 | 1315.08 | 4408.01 | 324.14 | 0.00 | 0.00 | 0.00 |
August | 3039.42 | 1675.69 | 1363.73 | 4227.78 | 365.12 | 0.00 | 0.00 | 0.00 |
September | 2529.80 | 1415.45 | 1114.36 | 3313.07 | 621.37 | 0.00 | 0.00 | 0.00 |
October | 2200.15 | 1395.91 | 804.24 | 2514.45 | 1081.51 | 0.00 | 0.00 | 0.00 |
November | 1719.53 | 1010.90 | 708.63 | 1633.45 | 1556.97 | 0.00 | 0.00 | 0.00 |
December | 1393.31 | 847.95 | 545.35 | 1183.82 | 2002.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2436.09 | 1407.73 | 1028.36 | 2907.08 | 1090.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1393.31 | 823.88 | 545.35 | 1183.82 | 324.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3319.36 | 2044.88 | 1388.47 | 4562.84 | 2002.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5900.78 | 4591.62 | 1309.16 | 6683.93 | 2916.33 | 0.00 | 0.00 | 0.00 |
February | 5774.71 | 4218.23 | 1556.48 | 6696.10 | 2696.32 | 0.00 | 0.00 | 0.00 |
March | 4255.37 | 2572.63 | 1682.74 | 5047.91 | 2187.89 | 0.00 | 0.00 | 0.00 |
April | 3318.65 | 1362.24 | 1956.40 | 4102.46 | 1553.40 | 0.00 | 0.00 | 0.00 |
May | 2213.26 | 486.88 | 1726.39 | 2760.02 | 1131.38 | 0.00 | 0.00 | 0.00 |
June | 1872.23 | 230.73 | 1641.50 | 2782.23 | 737.96 | 0.00 | 0.00 | 0.00 |
July | 2071.72 | 330.83 | 1740.89 | 3331.27 | 492.79 | 0.00 | 0.00 | 0.00 |
August | 2848.77 | 926.00 | 1922.78 | 4370.05 | 577.50 | 0.00 | 0.00 | 0.00 |
September | 3939.24 | 2196.64 | 1742.60 | 5572.42 | 1006.96 | 0.00 | 0.00 | 0.00 |
October | 5389.35 | 3969.23 | 1420.12 | 6840.25 | 1704.69 | 0.00 | 0.00 | 0.00 |
November | 6002.71 | 4607.07 | 1395.65 | 7024.85 | 2379.18 | 0.00 | 0.00 | 0.00 |
December | 6402.17 | 5281.12 | 1121.05 | 7325.94 | 2985.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4156.72 | 2555.94 | 1600.77 | 5202.99 | 1692.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1872.23 | 230.73 | 1121.05 | 2760.02 | 492.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6402.17 | 5281.12 | 1956.40 | 7325.94 | 2985.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1519.97 | 866.79 | 653.18 | 1420.10 | 2054.37 | 0.00 | 0.00 | 0.00 |
February | 1956.70 | 1130.33 | 826.37 | 1970.93 | 1887.59 | 0.00 | 0.00 | 0.00 |
March | 2185.42 | 1163.34 | 1022.08 | 2334.13 | 1517.10 | 0.00 | 0.00 | 0.00 |
April | 2789.25 | 1484.45 | 1304.80 | 3226.07 | 1065.06 | 0.00 | 0.00 | 0.00 |
May | 2644.61 | 1362.69 | 1281.92 | 3257.65 | 793.02 | 0.00 | 0.00 | 0.00 |
June | 2835.02 | 1581.91 | 1253.11 | 3945.18 | 552.67 | 0.00 | 0.00 | 0.00 |
July | 2557.10 | 1251.41 | 1305.69 | 3719.93 | 372.18 | 0.00 | 0.00 | 0.00 |
August | 2612.90 | 1208.57 | 1404.33 | 3675.78 | 425.71 | 0.00 | 0.00 | 0.00 |
September | 2360.06 | 1242.95 | 1117.11 | 3131.91 | 694.24 | 0.00 | 0.00 | 0.00 |
October | 2159.14 | 1341.98 | 817.15 | 2547.29 | 1200.68 | 0.00 | 0.00 | 0.00 |
November | 1694.91 | 997.16 | 697.76 | 1680.22 | 1663.37 | 0.00 | 0.00 | 0.00 |
December | 1465.76 | 919.19 | 546.57 | 1346.50 | 2118.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2231.94 | 1211.99 | 1019.95 | 2690.49 | 1191.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1465.76 | 866.79 | 546.57 | 1346.50 | 372.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2835.02 | 1581.91 | 1404.33 | 3945.18 | 2118.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 798.15 | 0.00 | 798.15 | 218.46 | 2784.26 | 0.00 | 0.00 | 0.00 |
February | 997.56 | 0.00 | 997.56 | 413.47 | 2545.39 | 0.00 | 0.00 | 0.00 |
March | 1258.29 | 0.00 | 1258.29 | 823.82 | 2036.73 | 0.00 | 0.00 | 0.00 |
April | 1596.38 | 13.67 | 1582.72 | 1302.66 | 1376.72 | 0.00 | 0.00 | 0.00 |
May | 1735.28 | 111.88 | 1623.40 | 1792.03 | 1022.60 | 0.00 | 0.00 | 0.00 |
June | 1971.75 | 322.67 | 1649.08 | 2769.78 | 689.64 | 0.00 | 0.00 | 0.00 |
July | 1809.76 | 150.63 | 1659.13 | 2747.71 | 473.58 | 0.00 | 0.00 | 0.00 |
August | 1678.85 | 37.59 | 1641.27 | 2328.32 | 531.88 | 0.00 | 0.00 | 0.00 |
September | 1342.56 | 0.34 | 1342.22 | 1586.52 | 924.08 | 0.00 | 0.00 | 0.00 |
October | 1001.82 | 0.00 | 1001.82 | 750.24 | 1583.65 | 0.00 | 0.00 | 0.00 |
November | 850.78 | 0.00 | 850.78 | 294.82 | 2206.96 | 0.00 | 0.00 | 0.00 |
December | 679.35 | 0.00 | 679.35 | 79.06 | 2900.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1311.19 | 53.16 | 1258.03 | 1263.34 | 1585.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 679.35 | 0.00 | 679.35 | 79.06 | 473.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1971.75 | 322.67 | 1659.13 | 2769.78 | 2900.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1473.60 | 823.88 | 649.72 | 1288.47 | 1745.92 | 0.00 | 0.00 | 0.00 |
February | 1790.40 | 965.22 | 825.18 | 1696.71 | 1617.76 | 0.00 | 0.00 | 0.00 |
March | 2361.81 | 1342.64 | 1019.16 | 2516.20 | 1313.72 | 0.00 | 0.00 | 0.00 |
April | 3226.71 | 1838.24 | 1388.47 | 3784.87 | 926.71 | 0.00 | 0.00 | 0.00 |
May | 3078.96 | 1754.68 | 1324.29 | 3821.22 | 713.48 | 0.00 | 0.00 | 0.00 |
June | 3319.36 | 2044.88 | 1274.47 | 4552.85 | 466.59 | 0.00 | 0.00 | 0.00 |
July | 3071.46 | 1756.39 | 1315.08 | 4394.30 | 327.96 | 0.00 | 0.00 | 0.00 |
August | 3039.42 | 1675.69 | 1363.73 | 4216.60 | 366.62 | 0.00 | 0.00 | 0.00 |
September | 2529.80 | 1415.45 | 1114.36 | 3309.95 | 611.67 | 0.00 | 0.00 | 0.00 |
October | 2200.15 | 1395.91 | 804.24 | 2530.51 | 1031.12 | 0.00 | 0.00 | 0.00 |
November | 1719.53 | 1010.90 | 708.63 | 1674.44 | 1436.71 | 0.00 | 0.00 | 0.00 |
December | 1393.31 | 847.95 | 545.35 | 1224.97 | 1828.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2436.09 | 1407.73 | 1028.36 | 2923.10 | 1029.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1393.31 | 823.88 | 545.35 | 1224.97 | 327.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3319.36 | 2044.88 | 1388.47 | 4552.85 | 1828.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5900.78 | 4591.62 | 1309.16 | 6754.60 | 2715.53 | 0.00 | 0.00 | 0.00 |
February | 5774.71 | 4218.23 | 1556.48 | 6746.02 | 2529.29 | 0.00 | 0.00 | 0.00 |
March | 4255.37 | 2572.63 | 1682.74 | 5076.33 | 2080.46 | 0.00 | 0.00 | 0.00 |
April | 3318.65 | 1362.24 | 1956.40 | 4105.87 | 1494.10 | 0.00 | 0.00 | 0.00 |
May | 2213.26 | 486.88 | 1726.39 | 2752.12 | 1104.69 | 0.00 | 0.00 | 0.00 |
June | 1872.23 | 230.73 | 1641.50 | 2762.59 | 732.98 | 0.00 | 0.00 | 0.00 |
July | 2071.72 | 330.83 | 1740.89 | 3303.68 | 499.91 | 0.00 | 0.00 | 0.00 |
August | 2848.77 | 926.00 | 1922.78 | 4344.92 | 580.32 | 0.00 | 0.00 | 0.00 |
September | 3939.24 | 2196.64 | 1742.60 | 5559.71 | 989.65 | 0.00 | 0.00 | 0.00 |
October | 5389.35 | 3969.23 | 1420.12 | 6861.70 | 1628.43 | 0.00 | 0.00 | 0.00 |
November | 6002.71 | 4607.07 | 1395.65 | 7081.83 | 2222.74 | 0.00 | 0.00 | 0.00 |
December | 6402.17 | 5281.12 | 1121.05 | 7385.42 | 2764.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4156.72 | 2555.94 | 1600.77 | 5219.26 | 1607.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1872.23 | 230.73 | 1121.05 | 2752.12 | 499.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6402.17 | 5281.12 | 1956.40 | 7385.42 | 2764.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1519.97 | 866.79 | 653.18 | 1448.54 | 1918.93 | 0.00 | 0.00 | 0.00 |
February | 1956.70 | 1130.33 | 826.37 | 1993.08 | 1780.30 | 0.00 | 0.00 | 0.00 |
March | 2185.42 | 1163.34 | 1022.08 | 2348.80 | 1445.90 | 0.00 | 0.00 | 0.00 |
April | 2789.25 | 1484.45 | 1304.80 | 3225.65 | 1027.40 | 0.00 | 0.00 | 0.00 |
May | 2644.61 | 1362.69 | 1281.92 | 3248.39 | 775.32 | 0.00 | 0.00 | 0.00 |
June | 2835.02 | 1581.91 | 1253.11 | 3929.37 | 547.84 | 0.00 | 0.00 | 0.00 |
July | 2557.10 | 1251.41 | 1305.69 | 3700.42 | 374.66 | 0.00 | 0.00 | 0.00 |
August | 2612.90 | 1208.57 | 1404.33 | 3658.57 | 426.37 | 0.00 | 0.00 | 0.00 |
September | 2360.06 | 1242.95 | 1117.11 | 3121.64 | 682.69 | 0.00 | 0.00 | 0.00 |
October | 2159.14 | 1341.98 | 817.15 | 2552.54 | 1146.54 | 0.00 | 0.00 | 0.00 |
November | 1694.91 | 997.16 | 697.76 | 1702.78 | 1551.90 | 0.00 | 0.00 | 0.00 |
December | 1465.76 | 919.19 | 546.57 | 1365.30 | 1973.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2231.94 | 1211.99 | 1019.95 | 2693.67 | 1134.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1465.76 | 866.79 | 546.57 | 1365.30 | 374.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2835.02 | 1581.91 | 1404.33 | 3929.37 | 1973.91 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427561E+09 | 0.00 | 0.427561E+09 | 61375675.08 | 0.177703E+10 |
February | 0.482665E+09 | 0.00 | 0.482665E+09 | 0.142696E+09 | 0.144601E+10 |
March | 0.674052E+09 | 0.00 | 0.674052E+09 | 0.387442E+09 | 0.125419E+10 |
April | 0.827576E+09 | 7085351.28 | 0.820490E+09 | 0.642139E+09 | 0.801805E+09 |
May | 0.929568E+09 | 59932262.51 | 0.869635E+09 | 0.948269E+09 | 0.585419E+09 |
June | 0.102217E+10 | 0.167276E+09 | 0.854891E+09 | 0.142272E+10 | 0.382942E+09 |
July | 0.969462E+09 | 80688364.77 | 0.888774E+09 | 0.145222E+10 | 0.283814E+09 |
August | 0.899338E+09 | 20134251.44 | 0.879204E+09 | 0.123218E+10 | 0.311509E+09 |
September | 0.695992E+09 | 178627.27 | 0.695814E+09 | 0.813760E+09 | 0.518484E+09 |
October | 0.536661E+09 | 0.00 | 0.536661E+09 | 0.364379E+09 | 0.980937E+09 |
November | 0.441051E+09 | 0.00 | 0.441051E+09 | 0.100473E+09 | 0.139610E+10 |
December | 0.363918E+09 | 0.00 | 0.363918E+09 | 12303646.97 | 0.191503E+10 |
Annual Sum or Average | 0.827001E+10 | 0.335295E+09 | 0.793472E+10 | 0.757996E+10 | 0.116533E+11 |
Minimum of Months | 0.363918E+09 | 0.00 | 0.363918E+09 | 12303646.97 | 0.283814E+09 |
Maximum of Months | 0.102217E+10 | 0.167276E+09 | 0.888774E+09 | 0.145222E+10 | 0.191503E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427560E+09 | 0.00 | 0.427560E+09 | 61375505.68 | 0.177703E+10 |
February | 0.482664E+09 | 0.00 | 0.482664E+09 | 0.142696E+09 | 0.144601E+10 |
March | 0.674051E+09 | 0.00 | 0.674051E+09 | 0.387442E+09 | 0.125419E+10 |
April | 0.827575E+09 | 7085342.78 | 0.820490E+09 | 0.642139E+09 | 0.801805E+09 |
May | 0.929567E+09 | 59932190.60 | 0.869635E+09 | 0.948268E+09 | 0.585419E+09 |
June | 0.102217E+10 | 0.167276E+09 | 0.854891E+09 | 0.142272E+10 | 0.382941E+09 |
July | 0.969462E+09 | 80688267.96 | 0.888773E+09 | 0.145222E+10 | 0.283814E+09 |
August | 0.899337E+09 | 20134227.28 | 0.879203E+09 | 0.123218E+10 | 0.311509E+09 |
September | 0.695992E+09 | 178627.05 | 0.695813E+09 | 0.813759E+09 | 0.518484E+09 |
October | 0.536661E+09 | 0.00 | 0.536661E+09 | 0.364379E+09 | 0.980937E+09 |
November | 0.441051E+09 | 0.00 | 0.441051E+09 | 0.100473E+09 | 0.139610E+10 |
December | 0.363918E+09 | 0.00 | 0.363918E+09 | 12303588.68 | 0.191503E+10 |
Annual Sum or Average | 0.827001E+10 | 0.335294E+09 | 0.793471E+10 | 0.757996E+10 | 0.116533E+11 |
Minimum of Months | 0.363918E+09 | 0.00 | 0.363918E+09 | 12303588.68 | 0.283814E+09 |
Maximum of Months | 0.102217E+10 | 0.167276E+09 | 0.888773E+09 | 0.145222E+10 | 0.191503E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427561E+09 | 0.00 | 0.427561E+09 | 61375675.08 | 0.177703E+10 |
February | 0.482665E+09 | 0.00 | 0.482665E+09 | 0.142696E+09 | 0.144601E+10 |
March | 0.674052E+09 | 0.00 | 0.674052E+09 | 0.387442E+09 | 0.125419E+10 |
April | 0.827576E+09 | 7085351.28 | 0.820490E+09 | 0.642139E+09 | 0.801805E+09 |
May | 0.929568E+09 | 59932262.51 | 0.869635E+09 | 0.948269E+09 | 0.585419E+09 |
June | 0.102217E+10 | 0.167276E+09 | 0.854891E+09 | 0.142272E+10 | 0.382942E+09 |
July | 0.969462E+09 | 80688364.77 | 0.888774E+09 | 0.145222E+10 | 0.283814E+09 |
August | 0.899338E+09 | 20134251.44 | 0.879204E+09 | 0.123218E+10 | 0.311509E+09 |
September | 0.695992E+09 | 178627.27 | 0.695814E+09 | 0.813760E+09 | 0.518484E+09 |
October | 0.536661E+09 | 0.00 | 0.536661E+09 | 0.364379E+09 | 0.980937E+09 |
November | 0.441051E+09 | 0.00 | 0.441051E+09 | 0.100473E+09 | 0.139610E+10 |
December | 0.363918E+09 | 0.00 | 0.363918E+09 | 12303646.97 | 0.191503E+10 |
Annual Sum or Average | 0.827001E+10 | 0.335295E+09 | 0.793472E+10 | 0.757996E+10 | 0.116533E+11 |
Minimum of Months | 0.363918E+09 | 0.00 | 0.363918E+09 | 12303646.97 | 0.283814E+09 |
Maximum of Months | 0.102217E+10 | 0.167276E+09 | 0.888774E+09 | 0.145222E+10 | 0.191503E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427560E+09 | 0.00 | 0.427560E+09 | 61375505.68 | 0.177703E+10 |
February | 0.482664E+09 | 0.00 | 0.482664E+09 | 0.142696E+09 | 0.144601E+10 |
March | 0.674051E+09 | 0.00 | 0.674051E+09 | 0.387442E+09 | 0.125419E+10 |
April | 0.827575E+09 | 7085342.78 | 0.820490E+09 | 0.642139E+09 | 0.801805E+09 |
May | 0.929567E+09 | 59932190.60 | 0.869635E+09 | 0.948268E+09 | 0.585419E+09 |
June | 0.102217E+10 | 0.167276E+09 | 0.854891E+09 | 0.142272E+10 | 0.382941E+09 |
July | 0.969462E+09 | 80688267.96 | 0.888773E+09 | 0.145222E+10 | 0.283814E+09 |
August | 0.899337E+09 | 20134227.28 | 0.879203E+09 | 0.123218E+10 | 0.311509E+09 |
September | 0.695992E+09 | 178627.05 | 0.695813E+09 | 0.813759E+09 | 0.518484E+09 |
October | 0.536661E+09 | 0.00 | 0.536661E+09 | 0.364379E+09 | 0.980937E+09 |
November | 0.441051E+09 | 0.00 | 0.441051E+09 | 0.100473E+09 | 0.139610E+10 |
December | 0.363918E+09 | 0.00 | 0.363918E+09 | 12303588.68 | 0.191503E+10 |
Annual Sum or Average | 0.827001E+10 | 0.335294E+09 | 0.793471E+10 | 0.757996E+10 | 0.116533E+11 |
Minimum of Months | 0.363918E+09 | 0.00 | 0.363918E+09 | 12303588.68 | 0.283814E+09 |
Maximum of Months | 0.102217E+10 | 0.167276E+09 | 0.888773E+09 | 0.145222E+10 | 0.191503E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427544E+09 | 0.00 | 0.427544E+09 | 61373201.37 | 0.177696E+10 |
February | 0.482645E+09 | 0.00 | 0.482645E+09 | 0.142691E+09 | 0.144595E+10 |
March | 0.674024E+09 | 0.00 | 0.674024E+09 | 0.387426E+09 | 0.125414E+10 |
April | 0.827542E+09 | 7085065.71 | 0.820457E+09 | 0.642113E+09 | 0.801773E+09 |
May | 0.929530E+09 | 59929846.98 | 0.869600E+09 | 0.948230E+09 | 0.585395E+09 |
June | 0.102213E+10 | 0.167269E+09 | 0.854857E+09 | 0.142267E+10 | 0.382926E+09 |
July | 0.969423E+09 | 80685112.68 | 0.888738E+09 | 0.145217E+10 | 0.283802E+09 |
August | 0.899302E+09 | 20133439.94 | 0.879168E+09 | 0.123213E+10 | 0.311497E+09 |
September | 0.695964E+09 | 178620.07 | 0.695785E+09 | 0.813727E+09 | 0.518463E+09 |
October | 0.536639E+09 | 0.00 | 0.536639E+09 | 0.364364E+09 | 0.980898E+09 |
November | 0.441033E+09 | 0.00 | 0.441033E+09 | 0.100469E+09 | 0.139604E+10 |
December | 0.363904E+09 | 0.00 | 0.363904E+09 | 12303151.08 | 0.191495E+10 |
Annual Sum or Average | 0.826968E+10 | 0.335281E+09 | 0.793440E+10 | 0.757966E+10 | 0.116528E+11 |
Minimum of Months | 0.363904E+09 | 0.00 | 0.363904E+09 | 12303151.08 | 0.283802E+09 |
Maximum of Months | 0.102213E+10 | 0.167269E+09 | 0.888738E+09 | 0.145217E+10 | 0.191495E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.131565E+10 | 0.735570E+09 | 0.580075E+09 | 0.108006E+10 | 0.180018E+10 |
February | 0.144379E+10 | 0.778359E+09 | 0.665433E+09 | 0.132225E+10 | 0.147378E+10 |
March | 0.210864E+10 | 0.119872E+10 | 0.909917E+09 | 0.223182E+10 | 0.127898E+10 |
April | 0.278790E+10 | 0.158825E+10 | 0.119965E+10 | 0.328559E+10 | 0.843186E+09 |
May | 0.274893E+10 | 0.156659E+10 | 0.118234E+10 | 0.343925E+10 | 0.662720E+09 |
June | 0.286795E+10 | 0.176680E+10 | 0.110116E+10 | 0.395188E+10 | 0.422188E+09 |
July | 0.274223E+10 | 0.156812E+10 | 0.117411E+10 | 0.393463E+10 | 0.313921E+09 |
August | 0.271362E+10 | 0.149607E+10 | 0.121755E+10 | 0.378565E+10 | 0.337963E+09 |
September | 0.218577E+10 | 0.122296E+10 | 0.962814E+09 | 0.287797E+10 | 0.553126E+09 |
October | 0.196432E+10 | 0.124628E+10 | 0.718034E+09 | 0.225280E+10 | 0.100391E+10 |
November | 0.148569E+10 | 0.873425E+09 | 0.612263E+09 | 0.140775E+10 | 0.141994E+10 |
December | 0.124396E+10 | 0.757062E+09 | 0.486895E+09 | 0.104293E+10 | 0.191831E+10 |
Annual Sum or Average | 0.256084E+11 | 0.147982E+11 | 0.108102E+11 | 0.306126E+11 | 0.120282E+11 |
Minimum of Months | 0.124396E+10 | 0.735570E+09 | 0.486895E+09 | 0.104293E+10 | 0.313921E+09 |
Maximum of Months | 0.286795E+10 | 0.176680E+10 | 0.121755E+10 | 0.395188E+10 | 0.191831E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.131565E+10 | 0.735570E+09 | 0.580075E+09 | 0.108006E+10 | 0.180018E+10 |
February | 0.144379E+10 | 0.778359E+09 | 0.665433E+09 | 0.132225E+10 | 0.147378E+10 |
March | 0.210864E+10 | 0.119872E+10 | 0.909917E+09 | 0.223182E+10 | 0.127898E+10 |
April | 0.278790E+10 | 0.158825E+10 | 0.119965E+10 | 0.328559E+10 | 0.843186E+09 |
May | 0.274893E+10 | 0.156659E+10 | 0.118234E+10 | 0.343925E+10 | 0.662720E+09 |
June | 0.286795E+10 | 0.176680E+10 | 0.110116E+10 | 0.395188E+10 | 0.422188E+09 |
July | 0.274223E+10 | 0.156812E+10 | 0.117411E+10 | 0.393463E+10 | 0.313921E+09 |
August | 0.271362E+10 | 0.149607E+10 | 0.121755E+10 | 0.378565E+10 | 0.337963E+09 |
September | 0.218577E+10 | 0.122296E+10 | 0.962814E+09 | 0.287797E+10 | 0.553126E+09 |
October | 0.196432E+10 | 0.124628E+10 | 0.718034E+09 | 0.225280E+10 | 0.100391E+10 |
November | 0.148569E+10 | 0.873425E+09 | 0.612263E+09 | 0.140775E+10 | 0.141994E+10 |
December | 0.124396E+10 | 0.757062E+09 | 0.486895E+09 | 0.104293E+10 | 0.191831E+10 |
Annual Sum or Average | 0.256084E+11 | 0.147982E+11 | 0.108102E+11 | 0.306126E+11 | 0.120282E+11 |
Minimum of Months | 0.124396E+10 | 0.735570E+09 | 0.486895E+09 | 0.104293E+10 | 0.313921E+09 |
Maximum of Months | 0.286795E+10 | 0.176680E+10 | 0.121755E+10 | 0.395188E+10 | 0.191831E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.131562E+10 | 0.735557E+09 | 0.580065E+09 | 0.108005E+10 | 0.180015E+10 |
February | 0.144376E+10 | 0.778344E+09 | 0.665420E+09 | 0.132222E+10 | 0.147375E+10 |
March | 0.210860E+10 | 0.119870E+10 | 0.909901E+09 | 0.223178E+10 | 0.127896E+10 |
April | 0.278785E+10 | 0.158823E+10 | 0.119963E+10 | 0.328553E+10 | 0.843171E+09 |
May | 0.274888E+10 | 0.156656E+10 | 0.118231E+10 | 0.343919E+10 | 0.662707E+09 |
June | 0.286790E+10 | 0.176677E+10 | 0.110114E+10 | 0.395181E+10 | 0.422180E+09 |
July | 0.274218E+10 | 0.156809E+10 | 0.117409E+10 | 0.393456E+10 | 0.313916E+09 |
August | 0.271357E+10 | 0.149604E+10 | 0.121753E+10 | 0.378558E+10 | 0.337957E+09 |
September | 0.218573E+10 | 0.122294E+10 | 0.962797E+09 | 0.287792E+10 | 0.553116E+09 |
October | 0.196428E+10 | 0.124626E+10 | 0.718021E+09 | 0.225276E+10 | 0.100389E+10 |
November | 0.148566E+10 | 0.873410E+09 | 0.612252E+09 | 0.140772E+10 | 0.141992E+10 |
December | 0.124393E+10 | 0.757048E+09 | 0.486886E+09 | 0.104291E+10 | 0.191828E+10 |
Annual Sum or Average | 0.256080E+11 | 0.147979E+11 | 0.108100E+11 | 0.306120E+11 | 0.120280E+11 |
Minimum of Months | 0.124393E+10 | 0.735557E+09 | 0.486886E+09 | 0.104291E+10 | 0.313916E+09 |
Maximum of Months | 0.286790E+10 | 0.176677E+10 | 0.121753E+10 | 0.395181E+10 | 0.191828E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316097E+10 | 0.245967E+10 | 0.701299E+09 | 0.360741E+10 | 0.157619E+10 |
February | 0.279407E+10 | 0.204097E+10 | 0.753097E+09 | 0.326372E+10 | 0.132190E+10 |
March | 0.227955E+10 | 0.137812E+10 | 0.901420E+09 | 0.272064E+10 | 0.119827E+10 |
April | 0.172041E+10 | 0.706196E+09 | 0.101421E+10 | 0.213412E+10 | 0.831844E+09 |
May | 0.118562E+10 | 0.260814E+09 | 0.924802E+09 | 0.148097E+10 | 0.623589E+09 |
June | 0.970578E+09 | 0.119613E+09 | 0.850965E+09 | 0.142479E+10 | 0.406466E+09 |
July | 0.110979E+10 | 0.177224E+09 | 0.932569E+09 | 0.176157E+10 | 0.292448E+09 |
August | 0.152605E+10 | 0.496044E+09 | 0.103000E+10 | 0.233207E+10 | 0.330506E+09 |
September | 0.204213E+10 | 0.113875E+10 | 0.903376E+09 | 0.290612E+10 | 0.533379E+09 |
October | 0.288700E+10 | 0.212626E+10 | 0.760740E+09 | 0.368983E+10 | 0.926398E+09 |
November | 0.311184E+10 | 0.238833E+10 | 0.723513E+09 | 0.366568E+10 | 0.125586E+10 |
December | 0.342956E+10 | 0.282903E+10 | 0.600531E+09 | 0.394513E+10 | 0.164010E+10 |
Annual Sum or Average | 0.262176E+11 | 0.161210E+11 | 0.100965E+11 | 0.329321E+11 | 0.109369E+11 |
Minimum of Months | 0.970578E+09 | 0.119613E+09 | 0.600531E+09 | 0.142479E+10 | 0.292448E+09 |
Maximum of Months | 0.342956E+10 | 0.282903E+10 | 0.103000E+10 | 0.394513E+10 | 0.164010E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316096E+10 | 0.245967E+10 | 0.701298E+09 | 0.360740E+10 | 0.157619E+10 |
February | 0.279407E+10 | 0.204097E+10 | 0.753096E+09 | 0.326372E+10 | 0.132190E+10 |
March | 0.227954E+10 | 0.137812E+10 | 0.901420E+09 | 0.272064E+10 | 0.119827E+10 |
April | 0.172041E+10 | 0.706195E+09 | 0.101421E+10 | 0.213412E+10 | 0.831843E+09 |
May | 0.118561E+10 | 0.260813E+09 | 0.924801E+09 | 0.148096E+10 | 0.623588E+09 |
June | 0.970577E+09 | 0.119613E+09 | 0.850964E+09 | 0.142479E+10 | 0.406466E+09 |
July | 0.110979E+10 | 0.177223E+09 | 0.932569E+09 | 0.176157E+10 | 0.292448E+09 |
August | 0.152605E+10 | 0.496043E+09 | 0.103000E+10 | 0.233207E+10 | 0.330506E+09 |
September | 0.204212E+10 | 0.113875E+10 | 0.903375E+09 | 0.290611E+10 | 0.533379E+09 |
October | 0.288700E+10 | 0.212626E+10 | 0.760740E+09 | 0.368983E+10 | 0.926398E+09 |
November | 0.311184E+10 | 0.238833E+10 | 0.723512E+09 | 0.366568E+10 | 0.125586E+10 |
December | 0.342955E+10 | 0.282902E+10 | 0.600530E+09 | 0.394513E+10 | 0.164010E+10 |
Annual Sum or Average | 0.262175E+11 | 0.161210E+11 | 0.100965E+11 | 0.329320E+11 | 0.109369E+11 |
Minimum of Months | 0.970577E+09 | 0.119613E+09 | 0.600530E+09 | 0.142479E+10 | 0.292448E+09 |
Maximum of Months | 0.342955E+10 | 0.282902E+10 | 0.103000E+10 | 0.394513E+10 | 0.164010E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316097E+10 | 0.245967E+10 | 0.701299E+09 | 0.360741E+10 | 0.157619E+10 |
February | 0.279407E+10 | 0.204097E+10 | 0.753097E+09 | 0.326372E+10 | 0.132190E+10 |
March | 0.227955E+10 | 0.137812E+10 | 0.901420E+09 | 0.272064E+10 | 0.119827E+10 |
April | 0.172041E+10 | 0.706196E+09 | 0.101421E+10 | 0.213412E+10 | 0.831844E+09 |
May | 0.118562E+10 | 0.260814E+09 | 0.924802E+09 | 0.148097E+10 | 0.623589E+09 |
June | 0.970578E+09 | 0.119613E+09 | 0.850965E+09 | 0.142479E+10 | 0.406466E+09 |
July | 0.110979E+10 | 0.177224E+09 | 0.932569E+09 | 0.176157E+10 | 0.292448E+09 |
August | 0.152605E+10 | 0.496044E+09 | 0.103000E+10 | 0.233207E+10 | 0.330506E+09 |
September | 0.204213E+10 | 0.113875E+10 | 0.903376E+09 | 0.290612E+10 | 0.533379E+09 |
October | 0.288700E+10 | 0.212626E+10 | 0.760740E+09 | 0.368983E+10 | 0.926398E+09 |
November | 0.311184E+10 | 0.238833E+10 | 0.723513E+09 | 0.366568E+10 | 0.125586E+10 |
December | 0.342956E+10 | 0.282903E+10 | 0.600531E+09 | 0.394513E+10 | 0.164010E+10 |
Annual Sum or Average | 0.262176E+11 | 0.161210E+11 | 0.100965E+11 | 0.329321E+11 | 0.109369E+11 |
Minimum of Months | 0.970578E+09 | 0.119613E+09 | 0.600531E+09 | 0.142479E+10 | 0.292448E+09 |
Maximum of Months | 0.342956E+10 | 0.282903E+10 | 0.103000E+10 | 0.394513E+10 | 0.164010E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316096E+10 | 0.245967E+10 | 0.701298E+09 | 0.360740E+10 | 0.157619E+10 |
February | 0.279407E+10 | 0.204097E+10 | 0.753096E+09 | 0.326372E+10 | 0.132190E+10 |
March | 0.227954E+10 | 0.137812E+10 | 0.901420E+09 | 0.272064E+10 | 0.119827E+10 |
April | 0.172041E+10 | 0.706195E+09 | 0.101421E+10 | 0.213412E+10 | 0.831843E+09 |
May | 0.118561E+10 | 0.260813E+09 | 0.924801E+09 | 0.148096E+10 | 0.623588E+09 |
June | 0.970577E+09 | 0.119613E+09 | 0.850964E+09 | 0.142479E+10 | 0.406466E+09 |
July | 0.110979E+10 | 0.177223E+09 | 0.932569E+09 | 0.176157E+10 | 0.292448E+09 |
August | 0.152605E+10 | 0.496043E+09 | 0.103000E+10 | 0.233207E+10 | 0.330506E+09 |
September | 0.204212E+10 | 0.113875E+10 | 0.903375E+09 | 0.290611E+10 | 0.533379E+09 |
October | 0.288700E+10 | 0.212626E+10 | 0.760740E+09 | 0.368983E+10 | 0.926398E+09 |
November | 0.311184E+10 | 0.238833E+10 | 0.723512E+09 | 0.366568E+10 | 0.125586E+10 |
December | 0.342955E+10 | 0.282902E+10 | 0.600530E+09 | 0.394513E+10 | 0.164010E+10 |
Annual Sum or Average | 0.262175E+11 | 0.161210E+11 | 0.100965E+11 | 0.329320E+11 | 0.109369E+11 |
Minimum of Months | 0.970577E+09 | 0.119613E+09 | 0.600530E+09 | 0.142479E+10 | 0.292448E+09 |
Maximum of Months | 0.342955E+10 | 0.282902E+10 | 0.103000E+10 | 0.394513E+10 | 0.164010E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316084E+10 | 0.245957E+10 | 0.701270E+09 | 0.360726E+10 | 0.157613E+10 |
February | 0.279396E+10 | 0.204089E+10 | 0.753067E+09 | 0.326359E+10 | 0.132184E+10 |
March | 0.227945E+10 | 0.137807E+10 | 0.901384E+09 | 0.272053E+10 | 0.119822E+10 |
April | 0.172034E+10 | 0.706167E+09 | 0.101417E+10 | 0.213403E+10 | 0.831810E+09 |
May | 0.118557E+10 | 0.260803E+09 | 0.924764E+09 | 0.148091E+10 | 0.623563E+09 |
June | 0.970539E+09 | 0.119608E+09 | 0.850930E+09 | 0.142473E+10 | 0.406450E+09 |
July | 0.110975E+10 | 0.177217E+09 | 0.932532E+09 | 0.176150E+10 | 0.292437E+09 |
August | 0.152599E+10 | 0.496024E+09 | 0.102996E+10 | 0.233197E+10 | 0.330493E+09 |
September | 0.204204E+10 | 0.113870E+10 | 0.903340E+09 | 0.290600E+10 | 0.533358E+09 |
October | 0.288689E+10 | 0.212618E+10 | 0.760710E+09 | 0.368968E+10 | 0.926361E+09 |
November | 0.311172E+10 | 0.238824E+10 | 0.723484E+09 | 0.366554E+10 | 0.125581E+10 |
December | 0.342942E+10 | 0.282891E+10 | 0.600507E+09 | 0.394497E+10 | 0.164003E+10 |
Annual Sum or Average | 0.262165E+11 | 0.161204E+11 | 0.100961E+11 | 0.329307E+11 | 0.109365E+11 |
Minimum of Months | 0.970539E+09 | 0.119608E+09 | 0.600507E+09 | 0.142473E+10 | 0.292437E+09 |
Maximum of Months | 0.342942E+10 | 0.282891E+10 | 0.102996E+10 | 0.394497E+10 | 0.164003E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135704E+10 | 0.773876E+09 | 0.583162E+09 | 0.123495E+10 | 0.200823E+10 |
February | 0.157790E+10 | 0.911508E+09 | 0.666395E+09 | 0.155513E+10 | 0.168482E+10 |
March | 0.195116E+10 | 0.103864E+10 | 0.912519E+09 | 0.204847E+10 | 0.150706E+10 |
April | 0.240993E+10 | 0.128258E+10 | 0.112736E+10 | 0.275229E+10 | 0.103365E+10 |
May | 0.236113E+10 | 0.121662E+10 | 0.114451E+10 | 0.290354E+10 | 0.751162E+09 |
June | 0.244948E+10 | 0.136678E+10 | 0.108270E+10 | 0.338815E+10 | 0.521089E+09 |
July | 0.228300E+10 | 0.111727E+10 | 0.116573E+10 | 0.328706E+10 | 0.382738E+09 |
August | 0.233282E+10 | 0.107903E+10 | 0.125380E+10 | 0.324514E+10 | 0.443416E+09 |
September | 0.203911E+10 | 0.107392E+10 | 0.965195E+09 | 0.269856E+10 | 0.641561E+09 |
October | 0.192770E+10 | 0.119813E+10 | 0.729563E+09 | 0.225113E+10 | 0.118129E+10 |
November | 0.146442E+10 | 0.861552E+09 | 0.602869E+09 | 0.141480E+10 | 0.163698E+10 |
December | 0.130864E+10 | 0.820657E+09 | 0.487983E+09 | 0.116165E+10 | 0.221741E+10 |
Annual Sum or Average | 0.234623E+11 | 0.127406E+11 | 0.107218E+11 | 0.279409E+11 | 0.140094E+11 |
Minimum of Months | 0.130864E+10 | 0.773876E+09 | 0.487983E+09 | 0.116165E+10 | 0.382738E+09 |
Maximum of Months | 0.244948E+10 | 0.136678E+10 | 0.125380E+10 | 0.338815E+10 | 0.221741E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135704E+10 | 0.773876E+09 | 0.583162E+09 | 0.123495E+10 | 0.200823E+10 |
February | 0.157790E+10 | 0.911508E+09 | 0.666395E+09 | 0.155513E+10 | 0.168482E+10 |
March | 0.195116E+10 | 0.103864E+10 | 0.912519E+09 | 0.204847E+10 | 0.150706E+10 |
April | 0.240993E+10 | 0.128258E+10 | 0.112736E+10 | 0.275229E+10 | 0.103365E+10 |
May | 0.236113E+10 | 0.121662E+10 | 0.114451E+10 | 0.290354E+10 | 0.751162E+09 |
June | 0.244948E+10 | 0.136678E+10 | 0.108270E+10 | 0.338815E+10 | 0.521089E+09 |
July | 0.228300E+10 | 0.111727E+10 | 0.116573E+10 | 0.328706E+10 | 0.382738E+09 |
August | 0.233282E+10 | 0.107903E+10 | 0.125380E+10 | 0.324514E+10 | 0.443416E+09 |
September | 0.203911E+10 | 0.107392E+10 | 0.965195E+09 | 0.269856E+10 | 0.641561E+09 |
October | 0.192770E+10 | 0.119813E+10 | 0.729563E+09 | 0.225113E+10 | 0.118129E+10 |
November | 0.146442E+10 | 0.861552E+09 | 0.602869E+09 | 0.141480E+10 | 0.163698E+10 |
December | 0.130864E+10 | 0.820657E+09 | 0.487983E+09 | 0.116165E+10 | 0.221741E+10 |
Annual Sum or Average | 0.234623E+11 | 0.127406E+11 | 0.107218E+11 | 0.279409E+11 | 0.140094E+11 |
Minimum of Months | 0.130864E+10 | 0.773876E+09 | 0.487983E+09 | 0.116165E+10 | 0.382738E+09 |
Maximum of Months | 0.244948E+10 | 0.136678E+10 | 0.125380E+10 | 0.338815E+10 | 0.221741E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135701E+10 | 0.773862E+09 | 0.583152E+09 | 0.123493E+10 | 0.200819E+10 |
February | 0.157787E+10 | 0.911491E+09 | 0.666383E+09 | 0.155510E+10 | 0.168479E+10 |
March | 0.195112E+10 | 0.103862E+10 | 0.912502E+09 | 0.204843E+10 | 0.150703E+10 |
April | 0.240989E+10 | 0.128256E+10 | 0.112733E+10 | 0.275224E+10 | 0.103363E+10 |
May | 0.236109E+10 | 0.121660E+10 | 0.114449E+10 | 0.290349E+10 | 0.751148E+09 |
June | 0.244944E+10 | 0.136676E+10 | 0.108268E+10 | 0.338809E+10 | 0.521080E+09 |
July | 0.228296E+10 | 0.111725E+10 | 0.116571E+10 | 0.328700E+10 | 0.382731E+09 |
August | 0.233278E+10 | 0.107901E+10 | 0.125377E+10 | 0.324508E+10 | 0.443408E+09 |
September | 0.203908E+10 | 0.107390E+10 | 0.965177E+09 | 0.269852E+10 | 0.641549E+09 |
October | 0.192766E+10 | 0.119811E+10 | 0.729550E+09 | 0.225109E+10 | 0.118127E+10 |
November | 0.146439E+10 | 0.861536E+09 | 0.602858E+09 | 0.141477E+10 | 0.163695E+10 |
December | 0.130862E+10 | 0.820642E+09 | 0.487974E+09 | 0.116163E+10 | 0.221737E+10 |
Annual Sum or Average | 0.234619E+11 | 0.127403E+11 | 0.107216E+11 | 0.279404E+11 | 0.140091E+11 |
Minimum of Months | 0.130862E+10 | 0.773862E+09 | 0.487974E+09 | 0.116163E+10 | 0.382731E+09 |
Maximum of Months | 0.244944E+10 | 0.136676E+10 | 0.125377E+10 | 0.338809E+10 | 0.221737E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213778E+10 | 0.00 | 0.213778E+10 | 0.463090E+09 | 0.808596E+10 |
February | 0.241329E+10 | 0.00 | 0.241329E+10 | 0.885624E+09 | 0.661140E+10 |
March | 0.337022E+10 | 0.00 | 0.337022E+10 | 0.209876E+10 | 0.579392E+10 |
April | 0.413783E+10 | 35426328.02 | 0.410240E+10 | 0.333271E+10 | 0.373091E+10 |
May | 0.464778E+10 | 0.299658E+09 | 0.434812E+10 | 0.480479E+10 | 0.279842E+10 |
June | 0.511077E+10 | 0.836369E+09 | 0.427441E+10 | 0.722855E+10 | 0.179306E+10 |
July | 0.484725E+10 | 0.403437E+09 | 0.444382E+10 | 0.743136E+10 | 0.124801E+10 |
August | 0.449664E+10 | 0.100670E+09 | 0.439597E+10 | 0.629611E+10 | 0.141345E+10 |
September | 0.347992E+10 | 893125.55 | 0.347903E+10 | 0.413517E+10 | 0.244090E+10 |
October | 0.268327E+10 | 0.00 | 0.268327E+10 | 0.194888E+10 | 0.450294E+10 |
November | 0.220523E+10 | 0.00 | 0.220523E+10 | 0.645157E+09 | 0.624905E+10 |
December | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.147451E+09 | 0.845049E+10 |
Annual Sum or Average | 0.413496E+11 | 0.167645E+10 | 0.396731E+11 | 0.394176E+11 | 0.531185E+11 |
Minimum of Months | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.147451E+09 | 0.124801E+10 |
Maximum of Months | 0.511077E+10 | 0.836369E+09 | 0.444382E+10 | 0.743136E+10 | 0.845049E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.394690E+10 | 0.220669E+10 | 0.174021E+10 | 0.329953E+10 | 0.507730E+10 |
February | 0.433133E+10 | 0.233505E+10 | 0.199628E+10 | 0.399147E+10 | 0.419886E+10 |
March | 0.632586E+10 | 0.359614E+10 | 0.272972E+10 | 0.666902E+10 | 0.370447E+10 |
April | 0.836363E+10 | 0.476472E+10 | 0.359891E+10 | 0.979047E+10 | 0.248278E+10 |
May | 0.824670E+10 | 0.469972E+10 | 0.354697E+10 | 0.102432E+11 | 0.194863E+10 |
June | 0.860378E+10 | 0.530034E+10 | 0.330344E+10 | 0.118269E+11 | 0.121518E+10 |
July | 0.822660E+10 | 0.470431E+10 | 0.352230E+10 | 0.118064E+11 | 0.868186E+09 |
August | 0.814078E+10 | 0.448817E+10 | 0.365261E+10 | 0.113237E+11 | 0.977945E+09 |
September | 0.655725E+10 | 0.366884E+10 | 0.288841E+10 | 0.858747E+10 | 0.161059E+10 |
October | 0.589289E+10 | 0.373881E+10 | 0.215408E+10 | 0.673470E+10 | 0.289671E+10 |
November | 0.445702E+10 | 0.262025E+10 | 0.183677E+10 | 0.423390E+10 | 0.403566E+10 |
December | 0.373183E+10 | 0.227116E+10 | 0.146067E+10 | 0.317075E+10 | 0.536480E+10 |
Annual Sum or Average | 0.768246E+11 | 0.443942E+11 | 0.324304E+11 | 0.916775E+11 | 0.343811E+11 |
Minimum of Months | 0.373183E+10 | 0.220669E+10 | 0.146067E+10 | 0.317075E+10 | 0.868186E+09 |
Maximum of Months | 0.860378E+10 | 0.530034E+10 | 0.365261E+10 | 0.118269E+11 | 0.536480E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158046E+11 | 0.122982E+11 | 0.350645E+10 | 0.179022E+11 | 0.781110E+10 |
February | 0.139702E+11 | 0.102047E+11 | 0.376544E+10 | 0.161992E+11 | 0.652293E+10 |
March | 0.113976E+11 | 0.689054E+10 | 0.450705E+10 | 0.135203E+11 | 0.586004E+10 |
April | 0.860193E+10 | 0.353094E+10 | 0.507100E+10 | 0.106336E+11 | 0.402640E+10 |
May | 0.592800E+10 | 0.130405E+10 | 0.462395E+10 | 0.739243E+10 | 0.303029E+10 |
June | 0.485283E+10 | 0.598059E+09 | 0.425477E+10 | 0.721153E+10 | 0.191278E+10 |
July | 0.554890E+10 | 0.886108E+09 | 0.466279E+10 | 0.892247E+10 | 0.131988E+10 |
August | 0.763015E+10 | 0.248019E+10 | 0.514996E+10 | 0.117047E+11 | 0.154676E+10 |
September | 0.102105E+11 | 0.569368E+10 | 0.451683E+10 | 0.144437E+11 | 0.261003E+10 |
October | 0.144348E+11 | 0.106312E+11 | 0.380366E+10 | 0.183209E+11 | 0.456585E+10 |
November | 0.155590E+11 | 0.119415E+11 | 0.361752E+10 | 0.182084E+11 | 0.616684E+10 |
December | 0.171476E+11 | 0.141450E+11 | 0.300262E+10 | 0.196218E+11 | 0.799664E+10 |
Annual Sum or Average | 0.131086E+12 | 0.806042E+11 | 0.504820E+11 | 0.164081E+12 | 0.533695E+11 |
Minimum of Months | 0.485283E+10 | 0.598059E+09 | 0.300262E+10 | 0.721153E+10 | 0.131988E+10 |
Maximum of Months | 0.171476E+11 | 0.141450E+11 | 0.514996E+10 | 0.196218E+11 | 0.799664E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407107E+10 | 0.232161E+10 | 0.174947E+10 | 0.380361E+10 | 0.550243E+10 |
February | 0.473366E+10 | 0.273449E+10 | 0.199917E+10 | 0.476807E+10 | 0.456646E+10 |
March | 0.585342E+10 | 0.311589E+10 | 0.273753E+10 | 0.625174E+10 | 0.406341E+10 |
April | 0.722973E+10 | 0.384770E+10 | 0.338203E+10 | 0.836198E+10 | 0.276062E+10 |
May | 0.708333E+10 | 0.364983E+10 | 0.343350E+10 | 0.872528E+10 | 0.212402E+10 |
June | 0.734836E+10 | 0.410031E+10 | 0.324805E+10 | 0.102259E+11 | 0.143253E+10 |
July | 0.684893E+10 | 0.335178E+10 | 0.349715E+10 | 0.996345E+10 | 0.996847E+09 |
August | 0.699839E+10 | 0.323704E+10 | 0.376135E+10 | 0.984522E+10 | 0.114022E+10 |
September | 0.611728E+10 | 0.322173E+10 | 0.289556E+10 | 0.811791E+10 | 0.179948E+10 |
October | 0.578303E+10 | 0.359437E+10 | 0.218867E+10 | 0.682265E+10 | 0.321591E+10 |
November | 0.439322E+10 | 0.258463E+10 | 0.180859E+10 | 0.435513E+10 | 0.431145E+10 |
December | 0.392588E+10 | 0.246195E+10 | 0.146393E+10 | 0.360646E+10 | 0.567347E+10 |
Annual Sum or Average | 0.703863E+11 | 0.382213E+11 | 0.321650E+11 | 0.848474E+11 | 0.375868E+11 |
Minimum of Months | 0.392588E+10 | 0.232161E+10 | 0.146393E+10 | 0.360646E+10 | 0.996847E+09 |
Maximum of Months | 0.734836E+10 | 0.410031E+10 | 0.376135E+10 | 0.102259E+11 | 0.567347E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213778E+10 | 0.00 | 0.213778E+10 | 0.585134E+09 | 0.745735E+10 |
February | 0.241329E+10 | 0.00 | 0.241329E+10 | 0.100027E+10 | 0.615781E+10 |
March | 0.337022E+10 | 0.00 | 0.337022E+10 | 0.220651E+10 | 0.545517E+10 |
April | 0.413783E+10 | 35426328.02 | 0.410240E+10 | 0.337649E+10 | 0.356845E+10 |
May | 0.464778E+10 | 0.299658E+09 | 0.434812E+10 | 0.479978E+10 | 0.273892E+10 |
June | 0.511077E+10 | 0.836369E+09 | 0.427441E+10 | 0.717927E+10 | 0.178755E+10 |
July | 0.484725E+10 | 0.403437E+09 | 0.444382E+10 | 0.735948E+10 | 0.126845E+10 |
August | 0.449664E+10 | 0.100670E+09 | 0.439597E+10 | 0.623616E+10 | 0.142459E+10 |
September | 0.347992E+10 | 893125.55 | 0.347903E+10 | 0.411226E+10 | 0.239522E+10 |
October | 0.268327E+10 | 0.00 | 0.268327E+10 | 0.200943E+10 | 0.424164E+10 |
November | 0.220523E+10 | 0.00 | 0.220523E+10 | 0.764161E+09 | 0.572045E+10 |
December | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.211743E+09 | 0.776935E+10 |
Annual Sum or Average | 0.413496E+11 | 0.167645E+10 | 0.396731E+11 | 0.398407E+11 | 0.499850E+11 |
Minimum of Months | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.211743E+09 | 0.126845E+10 |
Maximum of Months | 0.511077E+10 | 0.836369E+09 | 0.444382E+10 | 0.735948E+10 | 0.776935E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.394690E+10 | 0.220669E+10 | 0.174021E+10 | 0.345104E+10 | 0.467628E+10 |
February | 0.433133E+10 | 0.233505E+10 | 0.199628E+10 | 0.410468E+10 | 0.391368E+10 |
March | 0.632586E+10 | 0.359614E+10 | 0.272972E+10 | 0.673939E+10 | 0.351867E+10 |
April | 0.836363E+10 | 0.476472E+10 | 0.359891E+10 | 0.981039E+10 | 0.240202E+10 |
May | 0.824670E+10 | 0.469972E+10 | 0.354697E+10 | 0.102348E+11 | 0.191098E+10 |
June | 0.860378E+10 | 0.530034E+10 | 0.330344E+10 | 0.118010E+11 | 0.120939E+10 |
July | 0.822660E+10 | 0.470431E+10 | 0.352230E+10 | 0.117697E+11 | 0.878421E+09 |
August | 0.814078E+10 | 0.448817E+10 | 0.365261E+10 | 0.112937E+11 | 0.981943E+09 |
September | 0.655725E+10 | 0.366884E+10 | 0.288841E+10 | 0.857938E+10 | 0.158545E+10 |
October | 0.589289E+10 | 0.373881E+10 | 0.215408E+10 | 0.677773E+10 | 0.276175E+10 |
November | 0.445702E+10 | 0.262025E+10 | 0.183677E+10 | 0.434015E+10 | 0.372395E+10 |
December | 0.373183E+10 | 0.227116E+10 | 0.146067E+10 | 0.328097E+10 | 0.489708E+10 |
Annual Sum or Average | 0.768246E+11 | 0.443942E+11 | 0.324304E+11 | 0.921829E+11 | 0.324596E+11 |
Minimum of Months | 0.373183E+10 | 0.220669E+10 | 0.146067E+10 | 0.328097E+10 | 0.878421E+09 |
Maximum of Months | 0.860378E+10 | 0.530034E+10 | 0.365261E+10 | 0.118010E+11 | 0.489708E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158046E+11 | 0.122982E+11 | 0.350645E+10 | 0.180915E+11 | 0.727329E+10 |
February | 0.139702E+11 | 0.102047E+11 | 0.376544E+10 | 0.163200E+11 | 0.611885E+10 |
March | 0.113976E+11 | 0.689054E+10 | 0.450705E+10 | 0.135964E+11 | 0.557230E+10 |
April | 0.860193E+10 | 0.353094E+10 | 0.507100E+10 | 0.106424E+11 | 0.387271E+10 |
May | 0.592800E+10 | 0.130405E+10 | 0.462395E+10 | 0.737128E+10 | 0.295880E+10 |
June | 0.485283E+10 | 0.598059E+09 | 0.425477E+10 | 0.716063E+10 | 0.189989E+10 |
July | 0.554890E+10 | 0.886108E+09 | 0.466279E+10 | 0.884858E+10 | 0.133895E+10 |
August | 0.763015E+10 | 0.248019E+10 | 0.514996E+10 | 0.116374E+11 | 0.155433E+10 |
September | 0.102105E+11 | 0.569368E+10 | 0.451683E+10 | 0.144108E+11 | 0.256517E+10 |
October | 0.144348E+11 | 0.106312E+11 | 0.380366E+10 | 0.183784E+11 | 0.436160E+10 |
November | 0.155590E+11 | 0.119415E+11 | 0.361752E+10 | 0.183561E+11 | 0.576134E+10 |
December | 0.171476E+11 | 0.141450E+11 | 0.300262E+10 | 0.197811E+11 | 0.740530E+10 |
Annual Sum or Average | 0.131086E+12 | 0.806042E+11 | 0.504820E+11 | 0.164595E+12 | 0.506825E+11 |
Minimum of Months | 0.485283E+10 | 0.598059E+09 | 0.300262E+10 | 0.716063E+10 | 0.133895E+10 |
Maximum of Months | 0.171476E+11 | 0.141450E+11 | 0.514996E+10 | 0.197811E+11 | 0.740530E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407107E+10 | 0.232161E+10 | 0.174947E+10 | 0.387978E+10 | 0.513965E+10 |
February | 0.473366E+10 | 0.273449E+10 | 0.199917E+10 | 0.482167E+10 | 0.430691E+10 |
March | 0.585342E+10 | 0.311589E+10 | 0.273753E+10 | 0.629102E+10 | 0.387270E+10 |
April | 0.722973E+10 | 0.384770E+10 | 0.338203E+10 | 0.836088E+10 | 0.266301E+10 |
May | 0.708333E+10 | 0.364983E+10 | 0.343350E+10 | 0.870048E+10 | 0.207663E+10 |
June | 0.734836E+10 | 0.410031E+10 | 0.324805E+10 | 0.101849E+11 | 0.142000E+10 |
July | 0.684893E+10 | 0.335178E+10 | 0.349715E+10 | 0.991120E+10 | 0.100348E+10 |
August | 0.699839E+10 | 0.323704E+10 | 0.376135E+10 | 0.979910E+10 | 0.114200E+10 |
September | 0.611728E+10 | 0.322173E+10 | 0.289556E+10 | 0.809130E+10 | 0.176953E+10 |
October | 0.578303E+10 | 0.359437E+10 | 0.218867E+10 | 0.683672E+10 | 0.307089E+10 |
November | 0.439322E+10 | 0.258463E+10 | 0.180859E+10 | 0.441361E+10 | 0.402251E+10 |
December | 0.392588E+10 | 0.246195E+10 | 0.146393E+10 | 0.365681E+10 | 0.528692E+10 |
Annual Sum or Average | 0.703863E+11 | 0.382213E+11 | 0.321650E+11 | 0.849475E+11 | 0.357742E+11 |
Minimum of Months | 0.392588E+10 | 0.232161E+10 | 0.146393E+10 | 0.365681E+10 | 0.100348E+10 |
Maximum of Months | 0.734836E+10 | 0.410031E+10 | 0.376135E+10 | 0.101849E+11 | 0.528692E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 114.57 | 3317.31 | 798.16 | 0.00 | 798.16 | 0.00 | 0.00 |
February | 294.92 | 2988.58 | 997.56 | 0.00 | 997.56 | 0.00 | 0.00 |
March | 723.27 | 2341.28 | 1258.30 | 0.00 | 1258.30 | 0.00 | 0.00 |
April | 1238.68 | 1546.68 | 1596.39 | 13.67 | 1582.72 | 0.00 | 0.00 |
May | 1770.20 | 1092.84 | 1735.29 | 111.88 | 1623.41 | 0.00 | 0.00 |
June | 2744.43 | 738.69 | 1971.76 | 322.67 | 1649.08 | 0.00 | 0.00 |
July | 2710.97 | 529.82 | 1809.76 | 150.63 | 1659.14 | 0.00 | 0.00 |
August | 2300.19 | 581.52 | 1678.86 | 37.59 | 1641.27 | 0.00 | 0.00 |
September | 1569.74 | 1000.15 | 1342.57 | 0.34 | 1342.22 | 0.00 | 0.00 |
October | 680.21 | 1831.19 | 1001.82 | 0.00 | 1001.82 | 0.00 | 0.00 |
November | 193.81 | 2693.07 | 850.79 | 0.00 | 850.79 | 0.00 | 0.00 |
December | 22.97 | 3574.92 | 679.35 | 0.00 | 679.35 | 0.00 | 0.00 |
Annual Sum or Average | 1201.79 | 1847.60 | 1311.19 | 53.16 | 1258.03 | 0.00 | 0.00 |
Minimum of Months | 22.97 | 529.82 | 679.35 | 0.00 | 679.35 | 0.00 | 0.00 |
Maximum of Months | 2744.43 | 3574.92 | 1971.76 | 322.67 | 1659.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1209.74 | 2016.32 | 1473.61 | 823.89 | 649.72 | 0.00 | 0.00 |
February | 1639.68 | 1827.59 | 1790.40 | 965.22 | 825.18 | 0.00 | 0.00 |
March | 2499.78 | 1432.54 | 2361.82 | 1342.65 | 1019.17 | 0.00 | 0.00 |
April | 3802.74 | 975.90 | 3226.72 | 1838.25 | 1388.47 | 0.00 | 0.00 |
May | 3852.19 | 742.29 | 3078.98 | 1754.68 | 1324.29 | 0.00 | 0.00 |
June | 4573.91 | 488.64 | 3319.37 | 2044.89 | 1274.48 | 0.00 | 0.00 |
July | 4407.04 | 351.61 | 3071.47 | 1756.39 | 1315.08 | 0.00 | 0.00 |
August | 4240.18 | 378.54 | 3039.43 | 1675.70 | 1363.73 | 0.00 | 0.00 |
September | 3330.97 | 640.19 | 2529.82 | 1415.45 | 1114.36 | 0.00 | 0.00 |
October | 2523.28 | 1124.45 | 2200.16 | 1395.92 | 804.24 | 0.00 | 0.00 |
November | 1629.33 | 1643.44 | 1719.54 | 1010.90 | 708.63 | 0.00 | 0.00 |
December | 1168.15 | 2148.64 | 1393.31 | 847.96 | 545.35 | 0.00 | 0.00 |
Annual Sum or Average | 2912.14 | 1144.23 | 2436.10 | 1407.74 | 1028.36 | 0.00 | 0.00 |
Minimum of Months | 1168.15 | 351.61 | 1393.31 | 823.89 | 545.35 | 0.00 | 0.00 |
Maximum of Months | 4573.91 | 2148.64 | 3319.37 | 2044.89 | 1388.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6734.20 | 2942.39 | 5900.80 | 4591.64 | 1309.16 | 0.00 | 0.00 |
February | 6745.40 | 2732.07 | 5774.73 | 4218.25 | 1556.49 | 0.00 | 0.00 |
March | 5078.82 | 2236.90 | 4255.39 | 2572.64 | 1682.74 | 0.00 | 0.00 |
April | 4116.71 | 1604.62 | 3318.66 | 1362.25 | 1956.41 | 0.00 | 0.00 |
May | 2764.62 | 1164.10 | 2213.27 | 486.88 | 1726.39 | 0.00 | 0.00 |
June | 2748.42 | 784.07 | 1872.24 | 230.73 | 1641.51 | 0.00 | 0.00 |
July | 3288.45 | 545.93 | 2071.73 | 330.84 | 1740.89 | 0.00 | 0.00 |
August | 4353.44 | 616.98 | 2848.78 | 926.00 | 1922.78 | 0.00 | 0.00 |
September | 5605.88 | 1028.89 | 3939.25 | 2196.64 | 1742.61 | 0.00 | 0.00 |
October | 6888.07 | 1729.37 | 5389.37 | 3969.24 | 1420.13 | 0.00 | 0.00 |
November | 7071.09 | 2422.56 | 6002.74 | 4607.08 | 1395.65 | 0.00 | 0.00 |
December | 7364.65 | 3061.69 | 6402.19 | 5281.14 | 1121.05 | 0.00 | 0.00 |
Annual Sum or Average | 5221.30 | 1734.03 | 4156.73 | 2555.95 | 1600.78 | 0.00 | 0.00 |
Minimum of Months | 2748.42 | 545.93 | 1872.24 | 230.73 | 1121.05 | 0.00 | 0.00 |
Maximum of Months | 7364.65 | 3061.69 | 6402.19 | 5281.14 | 1956.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1383.22 | 2249.35 | 1519.97 | 866.79 | 653.18 | 0.00 | 0.00 |
February | 1928.47 | 2089.30 | 1956.71 | 1130.33 | 826.38 | 0.00 | 0.00 |
March | 2294.42 | 1688.00 | 2185.43 | 1163.35 | 1022.08 | 0.00 | 0.00 |
April | 3185.50 | 1196.34 | 2789.26 | 1484.46 | 1304.80 | 0.00 | 0.00 |
May | 3252.16 | 841.35 | 2644.62 | 1362.69 | 1281.93 | 0.00 | 0.00 |
June | 3921.44 | 603.11 | 2835.03 | 1581.92 | 1253.11 | 0.00 | 0.00 |
July | 3681.72 | 428.69 | 2557.11 | 1251.42 | 1305.69 | 0.00 | 0.00 |
August | 3634.76 | 496.65 | 2612.91 | 1208.58 | 1404.33 | 0.00 | 0.00 |
September | 3123.32 | 742.54 | 2360.07 | 1242.95 | 1117.12 | 0.00 | 0.00 |
October | 2521.41 | 1323.13 | 2159.15 | 1341.99 | 817.16 | 0.00 | 0.00 |
November | 1637.49 | 1894.64 | 1694.92 | 997.16 | 697.76 | 0.00 | 0.00 |
December | 1301.12 | 2483.64 | 1465.76 | 919.19 | 546.57 | 0.00 | 0.00 |
Annual Sum or Average | 2657.98 | 1332.70 | 2231.94 | 1211.99 | 1019.95 | 0.00 | 0.00 |
Minimum of Months | 1301.12 | 428.69 | 1465.76 | 866.79 | 546.57 | 0.00 | 0.00 |
Maximum of Months | 3921.44 | 2483.64 | 2835.03 | 1581.92 | 1404.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 172.90 | 3018.95 | 798.15 | 0.00 | 798.15 | 0.00 | 0.00 |
February | 366.08 | 2732.89 | 997.56 | 0.00 | 997.56 | 0.00 | 0.00 |
March | 783.59 | 2163.20 | 1258.29 | 0.00 | 1258.29 | 0.00 | 0.00 |
April | 1285.77 | 1439.40 | 1596.38 | 13.67 | 1582.72 | 0.00 | 0.00 |
May | 1793.90 | 1044.81 | 1735.28 | 111.88 | 1623.40 | 0.00 | 0.00 |
June | 2788.79 | 691.77 | 1971.75 | 322.67 | 1649.08 | 0.00 | 0.00 |
July | 2774.55 | 465.95 | 1809.76 | 150.63 | 1659.13 | 0.00 | 0.00 |
August | 2350.70 | 527.72 | 1678.85 | 37.59 | 1641.27 | 0.00 | 0.00 |
September | 1595.36 | 941.71 | 1342.56 | 0.34 | 1342.22 | 0.00 | 0.00 |
October | 727.63 | 1681.21 | 1001.82 | 0.00 | 1001.82 | 0.00 | 0.00 |
November | 248.90 | 2410.90 | 850.78 | 0.00 | 850.78 | 0.00 | 0.00 |
December | 55.05 | 3155.05 | 679.35 | 0.00 | 679.35 | 0.00 | 0.00 |
Annual Sum or Average | 1249.93 | 1684.38 | 1311.19 | 53.16 | 1258.03 | 0.00 | 0.00 |
Minimum of Months | 55.05 | 465.95 | 679.35 | 0.00 | 679.35 | 0.00 | 0.00 |
Maximum of Months | 2788.79 | 3155.05 | 1971.75 | 322.67 | 1659.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1231.90 | 1895.65 | 1473.60 | 823.88 | 649.72 | 0.00 | 0.00 |
February | 1649.91 | 1735.64 | 1790.40 | 965.22 | 825.18 | 0.00 | 0.00 |
March | 2489.93 | 1383.09 | 2361.81 | 1342.64 | 1019.16 | 0.00 | 0.00 |
April | 3777.19 | 957.86 | 3226.71 | 1838.24 | 1388.47 | 0.00 | 0.00 |
May | 3824.38 | 727.53 | 3078.96 | 1754.68 | 1324.29 | 0.00 | 0.00 |
June | 4562.84 | 468.82 | 3319.36 | 2044.88 | 1274.47 | 0.00 | 0.00 |
July | 4408.01 | 324.14 | 3071.46 | 1756.39 | 1315.08 | 0.00 | 0.00 |
August | 4227.78 | 365.12 | 3039.42 | 1675.69 | 1363.73 | 0.00 | 0.00 |
September | 3313.07 | 621.37 | 2529.80 | 1415.45 | 1114.36 | 0.00 | 0.00 |
October | 2514.45 | 1081.51 | 2200.15 | 1395.91 | 804.24 | 0.00 | 0.00 |
November | 1633.45 | 1556.97 | 1719.53 | 1010.90 | 708.63 | 0.00 | 0.00 |
December | 1183.82 | 2002.99 | 1393.31 | 847.95 | 545.35 | 0.00 | 0.00 |
Annual Sum or Average | 2907.08 | 1090.22 | 2436.09 | 1407.73 | 1028.36 | 0.00 | 0.00 |
Minimum of Months | 1183.82 | 324.14 | 1393.31 | 823.88 | 545.35 | 0.00 | 0.00 |
Maximum of Months | 4562.84 | 2002.99 | 3319.36 | 2044.88 | 1388.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6683.93 | 2916.33 | 5900.78 | 4591.62 | 1309.16 | 0.00 | 0.00 |
February | 6696.10 | 2696.32 | 5774.71 | 4218.23 | 1556.48 | 0.00 | 0.00 |
March | 5047.91 | 2187.89 | 4255.37 | 2572.63 | 1682.74 | 0.00 | 0.00 |
April | 4102.46 | 1553.40 | 3318.65 | 1362.24 | 1956.40 | 0.00 | 0.00 |
May | 2760.02 | 1131.38 | 2213.26 | 486.88 | 1726.39 | 0.00 | 0.00 |
June | 2782.23 | 737.96 | 1872.23 | 230.73 | 1641.50 | 0.00 | 0.00 |
July | 3331.27 | 492.79 | 2071.72 | 330.83 | 1740.89 | 0.00 | 0.00 |
August | 4370.05 | 577.50 | 2848.77 | 926.00 | 1922.78 | 0.00 | 0.00 |
September | 5572.42 | 1006.96 | 3939.24 | 2196.64 | 1742.60 | 0.00 | 0.00 |
October | 6840.25 | 1704.69 | 5389.35 | 3969.23 | 1420.12 | 0.00 | 0.00 |
November | 7024.85 | 2379.18 | 6002.71 | 4607.07 | 1395.65 | 0.00 | 0.00 |
December | 7325.94 | 2985.60 | 6402.17 | 5281.12 | 1121.05 | 0.00 | 0.00 |
Annual Sum or Average | 5202.99 | 1692.34 | 4156.72 | 2555.94 | 1600.77 | 0.00 | 0.00 |
Minimum of Months | 2760.02 | 492.79 | 1872.23 | 230.73 | 1121.05 | 0.00 | 0.00 |
Maximum of Months | 7325.94 | 2985.60 | 6402.17 | 5281.12 | 1956.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1420.10 | 2054.37 | 1519.97 | 866.79 | 653.18 | 0.00 | 0.00 |
February | 1970.93 | 1887.59 | 1956.70 | 1130.33 | 826.37 | 0.00 | 0.00 |
March | 2334.13 | 1517.10 | 2185.42 | 1163.34 | 1022.08 | 0.00 | 0.00 |
April | 3226.07 | 1065.06 | 2789.25 | 1484.45 | 1304.80 | 0.00 | 0.00 |
May | 3257.65 | 793.02 | 2644.61 | 1362.69 | 1281.92 | 0.00 | 0.00 |
June | 3945.18 | 552.67 | 2835.02 | 1581.91 | 1253.11 | 0.00 | 0.00 |
July | 3719.93 | 372.18 | 2557.10 | 1251.41 | 1305.69 | 0.00 | 0.00 |
August | 3675.78 | 425.71 | 2612.90 | 1208.57 | 1404.33 | 0.00 | 0.00 |
September | 3131.91 | 694.24 | 2360.06 | 1242.95 | 1117.11 | 0.00 | 0.00 |
October | 2547.29 | 1200.68 | 2159.14 | 1341.98 | 817.15 | 0.00 | 0.00 |
November | 1680.22 | 1663.37 | 1694.91 | 997.16 | 697.76 | 0.00 | 0.00 |
December | 1346.50 | 2118.23 | 1465.76 | 919.19 | 546.57 | 0.00 | 0.00 |
Annual Sum or Average | 2690.49 | 1191.87 | 2231.94 | 1211.99 | 1019.95 | 0.00 | 0.00 |
Minimum of Months | 1346.50 | 372.18 | 1465.76 | 866.79 | 546.57 | 0.00 | 0.00 |
Maximum of Months | 3945.18 | 2118.23 | 2835.02 | 1581.91 | 1404.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 218.46 | 2784.26 | 798.15 | 0.00 | 798.15 | 0.00 | 0.00 |
February | 413.47 | 2545.39 | 997.56 | 0.00 | 997.56 | 0.00 | 0.00 |
March | 823.82 | 2036.73 | 1258.29 | 0.00 | 1258.29 | 0.00 | 0.00 |
April | 1302.66 | 1376.72 | 1596.38 | 13.67 | 1582.72 | 0.00 | 0.00 |
May | 1792.03 | 1022.60 | 1735.28 | 111.88 | 1623.40 | 0.00 | 0.00 |
June | 2769.78 | 689.64 | 1971.75 | 322.67 | 1649.08 | 0.00 | 0.00 |
July | 2747.71 | 473.58 | 1809.76 | 150.63 | 1659.13 | 0.00 | 0.00 |
August | 2328.32 | 531.88 | 1678.85 | 37.59 | 1641.27 | 0.00 | 0.00 |
September | 1586.52 | 924.08 | 1342.56 | 0.34 | 1342.22 | 0.00 | 0.00 |
October | 750.24 | 1583.65 | 1001.82 | 0.00 | 1001.82 | 0.00 | 0.00 |
November | 294.82 | 2206.96 | 850.78 | 0.00 | 850.78 | 0.00 | 0.00 |
December | 79.06 | 2900.74 | 679.35 | 0.00 | 679.35 | 0.00 | 0.00 |
Annual Sum or Average | 1263.34 | 1585.01 | 1311.19 | 53.16 | 1258.03 | 0.00 | 0.00 |
Minimum of Months | 79.06 | 473.58 | 679.35 | 0.00 | 679.35 | 0.00 | 0.00 |
Maximum of Months | 2769.78 | 2900.74 | 1971.75 | 322.67 | 1659.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1288.47 | 1745.92 | 1473.60 | 823.88 | 649.72 | 0.00 | 0.00 |
February | 1696.71 | 1617.76 | 1790.40 | 965.22 | 825.18 | 0.00 | 0.00 |
March | 2516.20 | 1313.72 | 2361.81 | 1342.64 | 1019.16 | 0.00 | 0.00 |
April | 3784.87 | 926.71 | 3226.71 | 1838.24 | 1388.47 | 0.00 | 0.00 |
May | 3821.22 | 713.48 | 3078.96 | 1754.68 | 1324.29 | 0.00 | 0.00 |
June | 4552.85 | 466.59 | 3319.36 | 2044.88 | 1274.47 | 0.00 | 0.00 |
July | 4394.30 | 327.96 | 3071.46 | 1756.39 | 1315.08 | 0.00 | 0.00 |
August | 4216.60 | 366.62 | 3039.42 | 1675.69 | 1363.73 | 0.00 | 0.00 |
September | 3309.95 | 611.67 | 2529.80 | 1415.45 | 1114.36 | 0.00 | 0.00 |
October | 2530.51 | 1031.12 | 2200.15 | 1395.91 | 804.24 | 0.00 | 0.00 |
November | 1674.44 | 1436.71 | 1719.53 | 1010.90 | 708.63 | 0.00 | 0.00 |
December | 1224.97 | 1828.36 | 1393.31 | 847.95 | 545.35 | 0.00 | 0.00 |
Annual Sum or Average | 2923.10 | 1029.29 | 2436.09 | 1407.73 | 1028.36 | 0.00 | 0.00 |
Minimum of Months | 1224.97 | 327.96 | 1393.31 | 823.88 | 545.35 | 0.00 | 0.00 |
Maximum of Months | 4552.85 | 1828.36 | 3319.36 | 2044.88 | 1388.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6754.60 | 2715.53 | 5900.78 | 4591.62 | 1309.16 | 0.00 | 0.00 |
February | 6746.02 | 2529.29 | 5774.71 | 4218.23 | 1556.48 | 0.00 | 0.00 |
March | 5076.33 | 2080.46 | 4255.37 | 2572.63 | 1682.74 | 0.00 | 0.00 |
April | 4105.87 | 1494.10 | 3318.65 | 1362.24 | 1956.40 | 0.00 | 0.00 |
May | 2752.12 | 1104.69 | 2213.26 | 486.88 | 1726.39 | 0.00 | 0.00 |
June | 2762.59 | 732.98 | 1872.23 | 230.73 | 1641.50 | 0.00 | 0.00 |
July | 3303.68 | 499.91 | 2071.72 | 330.83 | 1740.89 | 0.00 | 0.00 |
August | 4344.92 | 580.32 | 2848.77 | 926.00 | 1922.78 | 0.00 | 0.00 |
September | 5559.71 | 989.65 | 3939.24 | 2196.64 | 1742.60 | 0.00 | 0.00 |
October | 6861.70 | 1628.43 | 5389.35 | 3969.23 | 1420.12 | 0.00 | 0.00 |
November | 7081.83 | 2222.74 | 6002.71 | 4607.07 | 1395.65 | 0.00 | 0.00 |
December | 7385.42 | 2764.82 | 6402.17 | 5281.12 | 1121.05 | 0.00 | 0.00 |
Annual Sum or Average | 5219.26 | 1607.13 | 4156.72 | 2555.94 | 1600.77 | 0.00 | 0.00 |
Minimum of Months | 2752.12 | 499.91 | 1872.23 | 230.73 | 1121.05 | 0.00 | 0.00 |
Maximum of Months | 7385.42 | 2764.82 | 6402.17 | 5281.12 | 1956.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1448.54 | 1918.93 | 1519.97 | 866.79 | 653.18 | 0.00 | 0.00 |
February | 1993.08 | 1780.30 | 1956.70 | 1130.33 | 826.37 | 0.00 | 0.00 |
March | 2348.80 | 1445.90 | 2185.42 | 1163.34 | 1022.08 | 0.00 | 0.00 |
April | 3225.65 | 1027.40 | 2789.25 | 1484.45 | 1304.80 | 0.00 | 0.00 |
May | 3248.39 | 775.32 | 2644.61 | 1362.69 | 1281.92 | 0.00 | 0.00 |
June | 3929.37 | 547.84 | 2835.02 | 1581.91 | 1253.11 | 0.00 | 0.00 |
July | 3700.42 | 374.66 | 2557.10 | 1251.41 | 1305.69 | 0.00 | 0.00 |
August | 3658.57 | 426.37 | 2612.90 | 1208.57 | 1404.33 | 0.00 | 0.00 |
September | 3121.64 | 682.69 | 2360.06 | 1242.95 | 1117.11 | 0.00 | 0.00 |
October | 2552.54 | 1146.54 | 2159.14 | 1341.98 | 817.15 | 0.00 | 0.00 |
November | 1702.78 | 1551.90 | 1694.91 | 997.16 | 697.76 | 0.00 | 0.00 |
December | 1365.30 | 1973.91 | 1465.76 | 919.19 | 546.57 | 0.00 | 0.00 |
Annual Sum or Average | 2693.67 | 1134.39 | 2231.94 | 1211.99 | 1019.95 | 0.00 | 0.00 |
Minimum of Months | 1365.30 | 374.66 | 1465.76 | 866.79 | 546.57 | 0.00 | 0.00 |
Maximum of Months | 3929.37 | 1973.91 | 2835.02 | 1581.91 | 1404.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.306876E+09 | 0.888509E+10 | 0.213779E+10 | 0.00 | 0.213779E+10 | 0.00 | 0.00 |
February | 0.713475E+09 | 0.722997E+10 | 0.241330E+10 | 0.00 | 0.241330E+10 | 0.00 | 0.00 |
March | 0.193719E+10 | 0.627088E+10 | 0.337023E+10 | 0.00 | 0.337023E+10 | 0.00 | 0.00 |
April | 0.321067E+10 | 0.400899E+10 | 0.413784E+10 | 35426453.82 | 0.410242E+10 | 0.00 | 0.00 |
May | 0.474130E+10 | 0.292707E+10 | 0.464780E+10 | 0.299659E+09 | 0.434814E+10 | 0.00 | 0.00 |
June | 0.711356E+10 | 0.191469E+10 | 0.511079E+10 | 0.836372E+09 | 0.427442E+10 | 0.00 | 0.00 |
July | 0.726106E+10 | 0.141906E+10 | 0.484727E+10 | 0.403438E+09 | 0.444383E+10 | 0.00 | 0.00 |
August | 0.616084E+10 | 0.155753E+10 | 0.449665E+10 | 0.100670E+09 | 0.439598E+10 | 0.00 | 0.00 |
September | 0.406876E+10 | 0.259240E+10 | 0.347993E+10 | 893128.72 | 0.347904E+10 | 0.00 | 0.00 |
October | 0.182188E+10 | 0.490465E+10 | 0.268328E+10 | 0.00 | 0.268328E+10 | 0.00 | 0.00 |
November | 0.502362E+09 | 0.698043E+10 | 0.220524E+10 | 0.00 | 0.220524E+10 | 0.00 | 0.00 |
December | 61517622.40 | 0.957508E+10 | 0.181958E+10 | 0.00 | 0.181958E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.378995E+11 | 0.582658E+11 | 0.413497E+11 | 0.167646E+10 | 0.396733E+11 | 0.00 | 0.00 |
Minimum of Months | 61517622.40 | 0.141906E+10 | 0.181958E+10 | 0.00 | 0.181958E+10 | 0.00 | 0.00 |
Maximum of Months | 0.726106E+10 | 0.957508E+10 | 0.511079E+10 | 0.836372E+09 | 0.444383E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.324018E+10 | 0.540051E+10 | 0.394691E+10 | 0.220670E+10 | 0.174021E+10 | 0.00 | 0.00 |
February | 0.396671E+10 | 0.442130E+10 | 0.433135E+10 | 0.233506E+10 | 0.199629E+10 | 0.00 | 0.00 |
March | 0.669542E+10 | 0.383692E+10 | 0.632589E+10 | 0.359615E+10 | 0.272973E+10 | 0.00 | 0.00 |
April | 0.985671E+10 | 0.252954E+10 | 0.836366E+10 | 0.476474E+10 | 0.359893E+10 | 0.00 | 0.00 |
May | 0.103177E+11 | 0.198815E+10 | 0.824673E+10 | 0.469974E+10 | 0.354699E+10 | 0.00 | 0.00 |
June | 0.118556E+11 | 0.126656E+10 | 0.860381E+10 | 0.530036E+10 | 0.330345E+10 | 0.00 | 0.00 |
July | 0.118038E+11 | 0.941758E+09 | 0.822664E+10 | 0.470432E+10 | 0.352231E+10 | 0.00 | 0.00 |
August | 0.113569E+11 | 0.101388E+10 | 0.814081E+10 | 0.448818E+10 | 0.365263E+10 | 0.00 | 0.00 |
September | 0.863387E+10 | 0.165937E+10 | 0.655728E+10 | 0.366886E+10 | 0.288842E+10 | 0.00 | 0.00 |
October | 0.675835E+10 | 0.301172E+10 | 0.589291E+10 | 0.373882E+10 | 0.215409E+10 | 0.00 | 0.00 |
November | 0.422322E+10 | 0.425980E+10 | 0.445704E+10 | 0.262026E+10 | 0.183678E+10 | 0.00 | 0.00 |
December | 0.312877E+10 | 0.575491E+10 | 0.373185E+10 | 0.227117E+10 | 0.146068E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.918372E+11 | 0.360844E+11 | 0.768249E+11 | 0.443944E+11 | 0.324305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.312877E+10 | 0.941758E+09 | 0.373185E+10 | 0.220670E+10 | 0.146068E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118556E+11 | 0.575491E+10 | 0.860381E+10 | 0.530036E+10 | 0.365263E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180369E+11 | 0.788089E+10 | 0.158047E+11 | 0.122982E+11 | 0.350646E+10 | 0.00 | 0.00 |
February | 0.163185E+11 | 0.660942E+10 | 0.139702E+11 | 0.102048E+11 | 0.376545E+10 | 0.00 | 0.00 |
March | 0.136031E+11 | 0.599130E+10 | 0.113976E+11 | 0.689057E+10 | 0.450706E+10 | 0.00 | 0.00 |
April | 0.106705E+11 | 0.415918E+10 | 0.860196E+10 | 0.353095E+10 | 0.507101E+10 | 0.00 | 0.00 |
May | 0.740476E+10 | 0.311792E+10 | 0.592803E+10 | 0.130406E+10 | 0.462397E+10 | 0.00 | 0.00 |
June | 0.712389E+10 | 0.203232E+10 | 0.485285E+10 | 0.598061E+09 | 0.425479E+10 | 0.00 | 0.00 |
July | 0.880777E+10 | 0.146223E+10 | 0.554892E+10 | 0.886111E+09 | 0.466281E+10 | 0.00 | 0.00 |
August | 0.116602E+11 | 0.165252E+10 | 0.763018E+10 | 0.248020E+10 | 0.514998E+10 | 0.00 | 0.00 |
September | 0.145305E+11 | 0.266687E+10 | 0.102105E+11 | 0.569370E+10 | 0.451684E+10 | 0.00 | 0.00 |
October | 0.184490E+11 | 0.463195E+10 | 0.144349E+11 | 0.106312E+11 | 0.380367E+10 | 0.00 | 0.00 |
November | 0.183283E+11 | 0.627927E+10 | 0.155591E+11 | 0.119416E+11 | 0.361754E+10 | 0.00 | 0.00 |
December | 0.197255E+11 | 0.820042E+10 | 0.171476E+11 | 0.141450E+11 | 0.300263E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.164659E+12 | 0.546843E+11 | 0.131087E+12 | 0.806044E+11 | 0.504822E+11 | 0.00 | 0.00 |
Minimum of Months | 0.712389E+10 | 0.146223E+10 | 0.485285E+10 | 0.598061E+09 | 0.300263E+10 | 0.00 | 0.00 |
Maximum of Months | 0.197255E+11 | 0.820042E+10 | 0.171476E+11 | 0.141450E+11 | 0.514998E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.370482E+10 | 0.602465E+10 | 0.407109E+10 | 0.232162E+10 | 0.174948E+10 | 0.00 | 0.00 |
February | 0.466535E+10 | 0.505443E+10 | 0.473368E+10 | 0.273451E+10 | 0.199917E+10 | 0.00 | 0.00 |
March | 0.614537E+10 | 0.452114E+10 | 0.585344E+10 | 0.311590E+10 | 0.273754E+10 | 0.00 | 0.00 |
April | 0.825681E+10 | 0.310092E+10 | 0.722976E+10 | 0.384771E+10 | 0.338204E+10 | 0.00 | 0.00 |
May | 0.871058E+10 | 0.225347E+10 | 0.708336E+10 | 0.364984E+10 | 0.343351E+10 | 0.00 | 0.00 |
June | 0.101644E+11 | 0.156326E+10 | 0.734839E+10 | 0.410033E+10 | 0.324807E+10 | 0.00 | 0.00 |
July | 0.986112E+10 | 0.114821E+10 | 0.684896E+10 | 0.335179E+10 | 0.349717E+10 | 0.00 | 0.00 |
August | 0.973535E+10 | 0.133024E+10 | 0.699842E+10 | 0.323706E+10 | 0.376136E+10 | 0.00 | 0.00 |
September | 0.809564E+10 | 0.192467E+10 | 0.611731E+10 | 0.322174E+10 | 0.289557E+10 | 0.00 | 0.00 |
October | 0.675335E+10 | 0.354386E+10 | 0.578306E+10 | 0.359438E+10 | 0.218868E+10 | 0.00 | 0.00 |
November | 0.424437E+10 | 0.491090E+10 | 0.439324E+10 | 0.258464E+10 | 0.180860E+10 | 0.00 | 0.00 |
December | 0.348493E+10 | 0.665219E+10 | 0.392590E+10 | 0.246196E+10 | 0.146394E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.838221E+11 | 0.420279E+11 | 0.703866E+11 | 0.382215E+11 | 0.321651E+11 | 0.00 | 0.00 |
Minimum of Months | 0.348493E+10 | 0.114821E+10 | 0.392590E+10 | 0.232162E+10 | 0.146394E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101644E+11 | 0.665219E+10 | 0.734839E+10 | 0.410033E+10 | 0.376136E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.463090E+09 | 0.808596E+10 | 0.213778E+10 | 0.00 | 0.213778E+10 | 0.00 | 0.00 |
February | 0.885624E+09 | 0.661140E+10 | 0.241329E+10 | 0.00 | 0.241329E+10 | 0.00 | 0.00 |
March | 0.209876E+10 | 0.579392E+10 | 0.337022E+10 | 0.00 | 0.337022E+10 | 0.00 | 0.00 |
April | 0.333271E+10 | 0.373091E+10 | 0.413783E+10 | 35426328.02 | 0.410240E+10 | 0.00 | 0.00 |
May | 0.480479E+10 | 0.279842E+10 | 0.464778E+10 | 0.299658E+09 | 0.434812E+10 | 0.00 | 0.00 |
June | 0.722855E+10 | 0.179306E+10 | 0.511077E+10 | 0.836369E+09 | 0.427441E+10 | 0.00 | 0.00 |
July | 0.743136E+10 | 0.124801E+10 | 0.484725E+10 | 0.403437E+09 | 0.444382E+10 | 0.00 | 0.00 |
August | 0.629611E+10 | 0.141345E+10 | 0.449664E+10 | 0.100670E+09 | 0.439597E+10 | 0.00 | 0.00 |
September | 0.413517E+10 | 0.244090E+10 | 0.347992E+10 | 893125.55 | 0.347903E+10 | 0.00 | 0.00 |
October | 0.194888E+10 | 0.450294E+10 | 0.268327E+10 | 0.00 | 0.268327E+10 | 0.00 | 0.00 |
November | 0.645157E+09 | 0.624905E+10 | 0.220523E+10 | 0.00 | 0.220523E+10 | 0.00 | 0.00 |
December | 0.147451E+09 | 0.845049E+10 | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.394176E+11 | 0.531185E+11 | 0.413496E+11 | 0.167645E+10 | 0.396731E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147451E+09 | 0.124801E+10 | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.00 | 0.00 |
Maximum of Months | 0.743136E+10 | 0.845049E+10 | 0.511077E+10 | 0.836369E+09 | 0.444382E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.329953E+10 | 0.507730E+10 | 0.394690E+10 | 0.220669E+10 | 0.174021E+10 | 0.00 | 0.00 |
February | 0.399147E+10 | 0.419886E+10 | 0.433133E+10 | 0.233505E+10 | 0.199628E+10 | 0.00 | 0.00 |
March | 0.666902E+10 | 0.370447E+10 | 0.632586E+10 | 0.359614E+10 | 0.272972E+10 | 0.00 | 0.00 |
April | 0.979047E+10 | 0.248278E+10 | 0.836363E+10 | 0.476472E+10 | 0.359891E+10 | 0.00 | 0.00 |
May | 0.102432E+11 | 0.194863E+10 | 0.824670E+10 | 0.469972E+10 | 0.354697E+10 | 0.00 | 0.00 |
June | 0.118269E+11 | 0.121518E+10 | 0.860378E+10 | 0.530034E+10 | 0.330344E+10 | 0.00 | 0.00 |
July | 0.118064E+11 | 0.868186E+09 | 0.822660E+10 | 0.470431E+10 | 0.352230E+10 | 0.00 | 0.00 |
August | 0.113237E+11 | 0.977945E+09 | 0.814078E+10 | 0.448817E+10 | 0.365261E+10 | 0.00 | 0.00 |
September | 0.858747E+10 | 0.161059E+10 | 0.655725E+10 | 0.366884E+10 | 0.288841E+10 | 0.00 | 0.00 |
October | 0.673470E+10 | 0.289671E+10 | 0.589289E+10 | 0.373881E+10 | 0.215408E+10 | 0.00 | 0.00 |
November | 0.423390E+10 | 0.403566E+10 | 0.445702E+10 | 0.262025E+10 | 0.183677E+10 | 0.00 | 0.00 |
December | 0.317075E+10 | 0.536480E+10 | 0.373183E+10 | 0.227116E+10 | 0.146067E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.916775E+11 | 0.343811E+11 | 0.768246E+11 | 0.443942E+11 | 0.324304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.317075E+10 | 0.868186E+09 | 0.373183E+10 | 0.220669E+10 | 0.146067E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118269E+11 | 0.536480E+10 | 0.860378E+10 | 0.530034E+10 | 0.365261E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.179022E+11 | 0.781110E+10 | 0.158046E+11 | 0.122982E+11 | 0.350645E+10 | 0.00 | 0.00 |
February | 0.161992E+11 | 0.652293E+10 | 0.139702E+11 | 0.102047E+11 | 0.376544E+10 | 0.00 | 0.00 |
March | 0.135203E+11 | 0.586004E+10 | 0.113976E+11 | 0.689054E+10 | 0.450705E+10 | 0.00 | 0.00 |
April | 0.106336E+11 | 0.402640E+10 | 0.860193E+10 | 0.353094E+10 | 0.507100E+10 | 0.00 | 0.00 |
May | 0.739243E+10 | 0.303029E+10 | 0.592800E+10 | 0.130405E+10 | 0.462395E+10 | 0.00 | 0.00 |
June | 0.721153E+10 | 0.191278E+10 | 0.485283E+10 | 0.598059E+09 | 0.425477E+10 | 0.00 | 0.00 |
July | 0.892247E+10 | 0.131988E+10 | 0.554890E+10 | 0.886108E+09 | 0.466279E+10 | 0.00 | 0.00 |
August | 0.117047E+11 | 0.154676E+10 | 0.763015E+10 | 0.248019E+10 | 0.514996E+10 | 0.00 | 0.00 |
September | 0.144437E+11 | 0.261003E+10 | 0.102105E+11 | 0.569368E+10 | 0.451683E+10 | 0.00 | 0.00 |
October | 0.183209E+11 | 0.456585E+10 | 0.144348E+11 | 0.106312E+11 | 0.380366E+10 | 0.00 | 0.00 |
November | 0.182084E+11 | 0.616684E+10 | 0.155590E+11 | 0.119415E+11 | 0.361752E+10 | 0.00 | 0.00 |
December | 0.196218E+11 | 0.799664E+10 | 0.171476E+11 | 0.141450E+11 | 0.300262E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.164081E+12 | 0.533695E+11 | 0.131086E+12 | 0.806042E+11 | 0.504820E+11 | 0.00 | 0.00 |
Minimum of Months | 0.721153E+10 | 0.131988E+10 | 0.485283E+10 | 0.598059E+09 | 0.300262E+10 | 0.00 | 0.00 |
Maximum of Months | 0.196218E+11 | 0.799664E+10 | 0.171476E+11 | 0.141450E+11 | 0.514996E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.380361E+10 | 0.550243E+10 | 0.407107E+10 | 0.232161E+10 | 0.174947E+10 | 0.00 | 0.00 |
February | 0.476807E+10 | 0.456646E+10 | 0.473366E+10 | 0.273449E+10 | 0.199917E+10 | 0.00 | 0.00 |
March | 0.625174E+10 | 0.406341E+10 | 0.585342E+10 | 0.311589E+10 | 0.273753E+10 | 0.00 | 0.00 |
April | 0.836198E+10 | 0.276062E+10 | 0.722973E+10 | 0.384770E+10 | 0.338203E+10 | 0.00 | 0.00 |
May | 0.872528E+10 | 0.212402E+10 | 0.708333E+10 | 0.364983E+10 | 0.343350E+10 | 0.00 | 0.00 |
June | 0.102259E+11 | 0.143253E+10 | 0.734836E+10 | 0.410031E+10 | 0.324805E+10 | 0.00 | 0.00 |
July | 0.996345E+10 | 0.996847E+09 | 0.684893E+10 | 0.335178E+10 | 0.349715E+10 | 0.00 | 0.00 |
August | 0.984522E+10 | 0.114022E+10 | 0.699839E+10 | 0.323704E+10 | 0.376135E+10 | 0.00 | 0.00 |
September | 0.811791E+10 | 0.179948E+10 | 0.611728E+10 | 0.322173E+10 | 0.289556E+10 | 0.00 | 0.00 |
October | 0.682265E+10 | 0.321591E+10 | 0.578303E+10 | 0.359437E+10 | 0.218867E+10 | 0.00 | 0.00 |
November | 0.435513E+10 | 0.431145E+10 | 0.439322E+10 | 0.258463E+10 | 0.180859E+10 | 0.00 | 0.00 |
December | 0.360646E+10 | 0.567347E+10 | 0.392588E+10 | 0.246195E+10 | 0.146393E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.848474E+11 | 0.375868E+11 | 0.703863E+11 | 0.382213E+11 | 0.321650E+11 | 0.00 | 0.00 |
Minimum of Months | 0.360646E+10 | 0.996847E+09 | 0.392588E+10 | 0.232161E+10 | 0.146393E+10 | 0.00 | 0.00 |
Maximum of Months | 0.102259E+11 | 0.567347E+10 | 0.734836E+10 | 0.410031E+10 | 0.376135E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.585134E+09 | 0.745735E+10 | 0.213778E+10 | 0.00 | 0.213778E+10 | 0.00 | 0.00 |
February | 0.100027E+10 | 0.615781E+10 | 0.241329E+10 | 0.00 | 0.241329E+10 | 0.00 | 0.00 |
March | 0.220651E+10 | 0.545517E+10 | 0.337022E+10 | 0.00 | 0.337022E+10 | 0.00 | 0.00 |
April | 0.337649E+10 | 0.356845E+10 | 0.413783E+10 | 35426328.02 | 0.410240E+10 | 0.00 | 0.00 |
May | 0.479978E+10 | 0.273892E+10 | 0.464778E+10 | 0.299658E+09 | 0.434812E+10 | 0.00 | 0.00 |
June | 0.717927E+10 | 0.178755E+10 | 0.511077E+10 | 0.836369E+09 | 0.427441E+10 | 0.00 | 0.00 |
July | 0.735948E+10 | 0.126845E+10 | 0.484725E+10 | 0.403437E+09 | 0.444382E+10 | 0.00 | 0.00 |
August | 0.623616E+10 | 0.142459E+10 | 0.449664E+10 | 0.100670E+09 | 0.439597E+10 | 0.00 | 0.00 |
September | 0.411226E+10 | 0.239522E+10 | 0.347992E+10 | 893125.55 | 0.347903E+10 | 0.00 | 0.00 |
October | 0.200943E+10 | 0.424164E+10 | 0.268327E+10 | 0.00 | 0.268327E+10 | 0.00 | 0.00 |
November | 0.764161E+09 | 0.572045E+10 | 0.220523E+10 | 0.00 | 0.220523E+10 | 0.00 | 0.00 |
December | 0.211743E+09 | 0.776935E+10 | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.398407E+11 | 0.499850E+11 | 0.413496E+11 | 0.167645E+10 | 0.396731E+11 | 0.00 | 0.00 |
Minimum of Months | 0.211743E+09 | 0.126845E+10 | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.00 | 0.00 |
Maximum of Months | 0.735948E+10 | 0.776935E+10 | 0.511077E+10 | 0.836369E+09 | 0.444382E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.345104E+10 | 0.467628E+10 | 0.394690E+10 | 0.220669E+10 | 0.174021E+10 | 0.00 | 0.00 |
February | 0.410468E+10 | 0.391368E+10 | 0.433133E+10 | 0.233505E+10 | 0.199628E+10 | 0.00 | 0.00 |
March | 0.673939E+10 | 0.351867E+10 | 0.632586E+10 | 0.359614E+10 | 0.272972E+10 | 0.00 | 0.00 |
April | 0.981039E+10 | 0.240202E+10 | 0.836363E+10 | 0.476472E+10 | 0.359891E+10 | 0.00 | 0.00 |
May | 0.102348E+11 | 0.191098E+10 | 0.824670E+10 | 0.469972E+10 | 0.354697E+10 | 0.00 | 0.00 |
June | 0.118010E+11 | 0.120939E+10 | 0.860378E+10 | 0.530034E+10 | 0.330344E+10 | 0.00 | 0.00 |
July | 0.117697E+11 | 0.878421E+09 | 0.822660E+10 | 0.470431E+10 | 0.352230E+10 | 0.00 | 0.00 |
August | 0.112937E+11 | 0.981943E+09 | 0.814078E+10 | 0.448817E+10 | 0.365261E+10 | 0.00 | 0.00 |
September | 0.857938E+10 | 0.158545E+10 | 0.655725E+10 | 0.366884E+10 | 0.288841E+10 | 0.00 | 0.00 |
October | 0.677773E+10 | 0.276175E+10 | 0.589289E+10 | 0.373881E+10 | 0.215408E+10 | 0.00 | 0.00 |
November | 0.434015E+10 | 0.372395E+10 | 0.445702E+10 | 0.262025E+10 | 0.183677E+10 | 0.00 | 0.00 |
December | 0.328097E+10 | 0.489708E+10 | 0.373183E+10 | 0.227116E+10 | 0.146067E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.921829E+11 | 0.324596E+11 | 0.768246E+11 | 0.443942E+11 | 0.324304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.328097E+10 | 0.878421E+09 | 0.373183E+10 | 0.220669E+10 | 0.146067E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118010E+11 | 0.489708E+10 | 0.860378E+10 | 0.530034E+10 | 0.365261E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180915E+11 | 0.727329E+10 | 0.158046E+11 | 0.122982E+11 | 0.350645E+10 | 0.00 | 0.00 |
February | 0.163200E+11 | 0.611885E+10 | 0.139702E+11 | 0.102047E+11 | 0.376544E+10 | 0.00 | 0.00 |
March | 0.135964E+11 | 0.557230E+10 | 0.113976E+11 | 0.689054E+10 | 0.450705E+10 | 0.00 | 0.00 |
April | 0.106424E+11 | 0.387271E+10 | 0.860193E+10 | 0.353094E+10 | 0.507100E+10 | 0.00 | 0.00 |
May | 0.737128E+10 | 0.295880E+10 | 0.592800E+10 | 0.130405E+10 | 0.462395E+10 | 0.00 | 0.00 |
June | 0.716063E+10 | 0.189989E+10 | 0.485283E+10 | 0.598059E+09 | 0.425477E+10 | 0.00 | 0.00 |
July | 0.884858E+10 | 0.133895E+10 | 0.554890E+10 | 0.886108E+09 | 0.466279E+10 | 0.00 | 0.00 |
August | 0.116374E+11 | 0.155433E+10 | 0.763015E+10 | 0.248019E+10 | 0.514996E+10 | 0.00 | 0.00 |
September | 0.144108E+11 | 0.256517E+10 | 0.102105E+11 | 0.569368E+10 | 0.451683E+10 | 0.00 | 0.00 |
October | 0.183784E+11 | 0.436160E+10 | 0.144348E+11 | 0.106312E+11 | 0.380366E+10 | 0.00 | 0.00 |
November | 0.183561E+11 | 0.576134E+10 | 0.155590E+11 | 0.119415E+11 | 0.361752E+10 | 0.00 | 0.00 |
December | 0.197811E+11 | 0.740530E+10 | 0.171476E+11 | 0.141450E+11 | 0.300262E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.164595E+12 | 0.506825E+11 | 0.131086E+12 | 0.806042E+11 | 0.504820E+11 | 0.00 | 0.00 |
Minimum of Months | 0.716063E+10 | 0.133895E+10 | 0.485283E+10 | 0.598059E+09 | 0.300262E+10 | 0.00 | 0.00 |
Maximum of Months | 0.197811E+11 | 0.740530E+10 | 0.171476E+11 | 0.141450E+11 | 0.514996E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.387978E+10 | 0.513965E+10 | 0.407107E+10 | 0.232161E+10 | 0.174947E+10 | 0.00 | 0.00 |
February | 0.482167E+10 | 0.430691E+10 | 0.473366E+10 | 0.273449E+10 | 0.199917E+10 | 0.00 | 0.00 |
March | 0.629102E+10 | 0.387270E+10 | 0.585342E+10 | 0.311589E+10 | 0.273753E+10 | 0.00 | 0.00 |
April | 0.836088E+10 | 0.266301E+10 | 0.722973E+10 | 0.384770E+10 | 0.338203E+10 | 0.00 | 0.00 |
May | 0.870048E+10 | 0.207663E+10 | 0.708333E+10 | 0.364983E+10 | 0.343350E+10 | 0.00 | 0.00 |
June | 0.101849E+11 | 0.142000E+10 | 0.734836E+10 | 0.410031E+10 | 0.324805E+10 | 0.00 | 0.00 |
July | 0.991120E+10 | 0.100348E+10 | 0.684893E+10 | 0.335178E+10 | 0.349715E+10 | 0.00 | 0.00 |
August | 0.979910E+10 | 0.114200E+10 | 0.699839E+10 | 0.323704E+10 | 0.376135E+10 | 0.00 | 0.00 |
September | 0.809130E+10 | 0.176953E+10 | 0.611728E+10 | 0.322173E+10 | 0.289556E+10 | 0.00 | 0.00 |
October | 0.683672E+10 | 0.307089E+10 | 0.578303E+10 | 0.359437E+10 | 0.218867E+10 | 0.00 | 0.00 |
November | 0.441361E+10 | 0.402251E+10 | 0.439322E+10 | 0.258463E+10 | 0.180859E+10 | 0.00 | 0.00 |
December | 0.365681E+10 | 0.528692E+10 | 0.392588E+10 | 0.246195E+10 | 0.146393E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.849475E+11 | 0.357742E+11 | 0.703863E+11 | 0.382213E+11 | 0.321650E+11 | 0.00 | 0.00 |
Minimum of Months | 0.365681E+10 | 0.100348E+10 | 0.392588E+10 | 0.232161E+10 | 0.146393E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101849E+11 | 0.528692E+10 | 0.734836E+10 | 0.410031E+10 | 0.376135E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.392123E+11 | -0.387699E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442400647.8 | 60.05 | 0.00 | 0.00 |
February | 0.358982E+11 | -0.354973E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -400882942.5 | 60.05 | 0.00 | 0.00 |
March | 0.411858E+11 | -0.407411E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444771991.9 | 60.05 | 0.00 | 0.00 |
April | 0.354546E+11 | -0.350261E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428503019.0 | 60.05 | 0.00 | 0.00 |
May | 0.352928E+11 | -0.348546E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -438225029.7 | 60.05 | 0.00 | 0.00 |
June | 0.325294E+11 | -0.321274E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -402030556.2 | 60.05 | 0.00 | 0.00 |
July | 0.294333E+11 | -0.290397E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -393609225.3 | 60.05 | 0.00 | 0.00 |
August | 0.318757E+11 | -0.314639E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -411830440.1 | 60.05 | 0.00 | 0.00 |
September | 0.299194E+11 | -0.295003E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -419092058.3 | 60.05 | 0.00 | 0.00 |
October | 0.328783E+11 | -0.324413E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -437033858.9 | 60.05 | 0.00 | 0.00 |
November | 0.346889E+11 | -0.342622E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -426660972.7 | 60.05 | 0.00 | 0.00 |
December | 0.367843E+11 | -0.363427E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -441627942.8 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.415153E+12 | -0.410066E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.508667E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.294333E+11 | -0.407411E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -444771991.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.411858E+11 | -0.290397E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -393609225.3 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.49 | 0.48 | 01-JAN-07:40 | 10435.93 | 37.84 | 289.17 | 286.83 | 2693.06 | 28.20 | 207.00 | 276.17 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-07:40 | 12790.87 | 37.90 | 272.83 | 275.17 | 1925.66 | 23.54 | 165.00 | 259.50 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:10 | 2372.78 | 20.28 | 119.50 | 331.17 | 1388.68 | 21.43 | 162.67 | 299.83 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:30 | 1925.93 | 20.44 | 126.67 | 352.83 | 1166.15 | 21.82 | 244.67 | 328.83 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-06:30 | 1490.06 | 19.76 | 58.83 | 372.67 | 921.30 | 21.19 | 192.67 | 339.83 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-05:00 | 1189.73 | 18.88 | 40.33 | 375.17 | 745.44 | 20.36 | 118.50 | 327.50 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:49 | 1439.54 | 19.60 | 68.67 | 376.67 | 881.06 | 21.07 | 170.17 | 337.67 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:19 | 1791.43 | 20.19 | 142.33 | 373.33 | 1071.12 | 21.60 | 236.33 | 343.00 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:40 | 2329.37 | 20.71 | 118.83 | 330.17 | 1297.93 | 21.46 | 169.17 | 303.33 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:49 | 6228.00 | 29.21 | 209.17 | 316.00 | 1730.04 | 21.61 | 132.67 | 303.00 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:00 | 11795.16 | 38.88 | 280.17 | 284.50 | 2658.97 | 27.85 | 204.00 | 273.00 |
December | 265.67 | 0.49 | 0.48 | 01-DEC-07:49 | 11922.36 | 40.19 | 263.83 | 269.50 | 3923.68 | 31.51 | 191.50 | 261.17 |
Annual Sum or Average | 4149.83 | 0.50 | 4839.61 | 25.80 | 1990.33 | 3944.00 | 1581.73 | 23.06 | 2194.33 | 3652.83 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 1189.73 | 18.88 | 40.33 | 269.50 | 745.44 | 20.36 | 118.50 | 259.50 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 12790.87 | 40.19 | 289.17 | 376.67 | 3923.68 | 31.51 | 244.67 | 343.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-07:40 | 2701.31 | 24.98 | 126.33 | 265.33 | 1502.63 | 24.85 | 144.17 | 237.50 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-07:30 | 3433.30 | 24.91 | 116.33 | 266.83 | 1904.16 | 24.88 | 140.00 | 241.00 |
March | 351.33 | 0.49 | 0.48 | 01-MAR-06:49 | 3482.74 | 24.42 | 130.00 | 327.50 | 1873.42 | 24.46 | 166.17 | 299.33 |
April | 381.83 | 0.50 | 0.48 | 01-APR-05:00 | 4954.48 | 25.70 | 131.33 | 358.00 | 1979.27 | 24.47 | 179.67 | 339.17 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-05:00 | 3971.82 | 23.52 | 97.00 | 377.33 | 2205.68 | 23.89 | 125.17 | 349.33 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:19 | 3791.25 | 23.16 | 116.00 | 393.00 | 2145.59 | 23.55 | 135.83 | 357.67 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:40 | 3784.80 | 23.69 | 113.67 | 385.50 | 2016.30 | 23.90 | 146.33 | 356.17 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:40 | 4572.04 | 25.27 | 139.50 | 381.00 | 1865.77 | 24.21 | 184.67 | 359.33 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3900.78 | 24.37 | 126.00 | 333.33 | 2164.96 | 24.59 | 156.33 | 309.33 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:30 | 3554.94 | 24.82 | 115.67 | 305.50 | 1962.03 | 24.75 | 137.50 | 281.33 |
November | 284.17 | 0.50 | 0.48 | 01-NOV-06:49 | 2891.92 | 24.88 | 106.33 | 266.67 | 1558.68 | 24.74 | 129.00 | 240.83 |
December | 265.67 | 0.52 | 0.48 | 01-DEC-07:49 | 3142.03 | 25.19 | 105.50 | 248.50 | 1816.67 | 24.84 | 108.17 | 210.17 |
Annual Sum or Average | 4149.83 | 0.50 | 3749.01 | 24.53 | 1423.67 | 3908.50 | 1935.59 | 24.37 | 1753.00 | 3581.17 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 2701.31 | 23.16 | 97.00 | 248.50 | 1502.63 | 23.55 | 108.17 | 210.17 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 4954.48 | 25.70 | 139.50 | 393.00 | 2205.68 | 24.88 | 184.67 | 359.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-08:50 | 671.63 | 17.16 | 0.00 | 246.67 | 428.81 | 18.97 | 13.83 | 192.33 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-08:09 | 792.35 | 17.94 | 0.00 | 254.17 | 520.07 | 19.69 | 62.00 | 209.83 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:19 | 937.39 | 18.61 | 0.17 | 318.83 | 586.70 | 20.12 | 104.50 | 272.83 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:19 | 1178.90 | 20.06 | 43.50 | 361.17 | 746.99 | 21.44 | 203.33 | 341.00 |
May | 378.00 | 0.49 | 0.48 | 01-MAY-06:19 | 1367.85 | 20.26 | 84.83 | 389.17 | 795.30 | 21.62 | 193.67 | 356.00 |
June | 412.83 | 0.48 | 0.48 | 01-JUN-05:40 | 1412.86 | 22.41 | 129.50 | 404.00 | 772.29 | 22.22 | 190.33 | 380.00 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:49 | 1395.71 | 22.13 | 123.00 | 395.00 | 804.47 | 21.54 | 208.00 | 369.17 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1246.00 | 20.13 | 89.83 | 383.33 | 787.55 | 21.53 | 226.67 | 366.00 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:40 | 994.22 | 19.11 | 8.83 | 328.33 | 635.22 | 20.61 | 119.50 | 291.67 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-07:10 | 726.13 | 17.46 | 0.00 | 288.00 | 494.16 | 19.17 | 37.17 | 239.67 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-07:19 | 714.14 | 17.79 | 0.00 | 254.67 | 471.73 | 19.62 | 17.50 | 208.33 |
December | 265.67 | 0.54 | 0.48 | 01-DEC-08:20 | 595.56 | 16.35 | 0.00 | 230.83 | 407.70 | 18.35 | 4.83 | 169.50 |
Annual Sum or Average | 4149.83 | 0.50 | 1042.02 | 19.36 | 479.67 | 3854.17 | 640.98 | 20.57 | 1381.33 | 3396.33 | ||
Minimum of Months | 265.67 | 0.48 | 0.48 | 595.56 | 16.35 | 0.00 | 230.83 | 407.70 | 18.35 | 4.83 | 169.50 | |
Maximum of Months | 412.83 | 0.54 | 0.48 | 1412.86 | 22.41 | 129.50 | 404.00 | 804.47 | 22.22 | 226.67 | 380.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-08:50 | 2333.26 | 23.62 | 107.67 | 271.50 | 1168.56 | 23.37 | 127.50 | 238.50 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-08:20 | 3410.48 | 25.33 | 117.67 | 264.67 | 1867.19 | 25.18 | 143.50 | 238.00 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:30 | 3599.97 | 23.99 | 129.83 | 329.67 | 1374.94 | 22.74 | 155.83 | 298.50 |
April | 381.83 | 0.49 | 0.48 | 01-APR-06:40 | 4446.74 | 24.11 | 113.17 | 361.67 | 1824.99 | 23.33 | 155.83 | 341.17 |
May | 378.00 | 0.49 | 0.48 | 01-MAY-06:40 | 3292.88 | 20.35 | 50.50 | 386.17 | 1844.52 | 20.66 | 82.67 | 364.50 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-06:10 | 3492.75 | 17.27 | 5.33 | 385.83 | 2017.50 | 19.75 | 92.83 | 357.83 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:00 | 3366.38 | 18.22 | 13.67 | 385.83 | 1849.15 | 20.44 | 129.00 | 359.67 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:40 | 3335.75 | 21.18 | 71.83 | 377.17 | 1746.78 | 21.16 | 171.50 | 353.83 |
September | 359.33 | 0.49 | 0.48 | 01-SEP-06:49 | 3755.70 | 24.21 | 127.00 | 334.17 | 1484.87 | 23.12 | 143.67 | 312.33 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-07:19 | 3384.19 | 24.29 | 116.00 | 306.00 | 1850.44 | 24.25 | 131.83 | 281.00 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-07:19 | 3312.66 | 26.00 | 118.00 | 275.83 | 1932.01 | 25.90 | 143.17 | 250.17 |
December | 265.67 | 0.51 | 0.48 | 01-DEC-08:20 | 3047.79 | 26.23 | 111.00 | 253.33 | 1793.09 | 25.92 | 121.67 | 225.83 |
Annual Sum or Average | 4149.83 | 0.50 | 3427.41 | 22.56 | 1081.67 | 3931.83 | 1735.44 | 22.72 | 1599.00 | 3621.33 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 2333.26 | 17.27 | 5.33 | 253.33 | 1168.56 | 19.75 | 82.67 | 225.83 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 4446.74 | 26.23 | 129.83 | 386.17 | 2017.50 | 25.92 | 171.50 | 364.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.49 | 0.48 | 01-JAN-07:40 | 10528.15 | 37.22 | 288.33 | 287.00 | 2844.35 | 24.36 | 127.17 | 277.33 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-07:40 | 12890.49 | 37.39 | 271.67 | 275.33 | 2226.91 | 21.31 | 79.17 | 264.17 |
March | 351.33 | 0.49 | 0.48 | 01-MAR-06:00 | 2436.71 | 13.66 | 10.67 | 331.17 | 1499.59 | 16.96 | 7.83 | 302.67 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:30 | 1975.08 | 14.52 | 0.00 | 353.00 | 1252.16 | 18.05 | 5.17 | 330.67 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:19 | 1526.62 | 13.96 | 0.00 | 373.67 | 986.76 | 17.50 | 0.00 | 343.00 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-05:00 | 1219.01 | 12.90 | 0.00 | 375.83 | 797.94 | 16.54 | 0.00 | 333.83 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:49 | 1472.14 | 13.67 | 0.00 | 377.33 | 942.51 | 17.26 | 0.33 | 342.83 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:19 | 1833.26 | 14.26 | 0.00 | 373.83 | 1147.48 | 17.79 | 0.17 | 347.00 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:30 | 2393.95 | 14.52 | 16.50 | 330.83 | 1398.52 | 17.21 | 4.50 | 306.17 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:49 | 6359.23 | 25.58 | 183.50 | 319.00 | 1879.45 | 17.03 | 17.17 | 305.00 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:49 | 11896.79 | 38.44 | 280.17 | 284.83 | 2851.96 | 24.39 | 112.67 | 275.00 |
December | 265.67 | 0.49 | 0.48 | 01-DEC-07:49 | 12049.44 | 39.79 | 263.50 | 269.67 | 4101.89 | 28.14 | 146.67 | 261.83 |
Annual Sum or Average | 4149.83 | 0.50 | 4907.57 | 21.46 | 1314.33 | 3951.50 | 1700.24 | 19.26 | 500.83 | 3689.50 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 1219.01 | 12.90 | 0.00 | 269.67 | 797.94 | 16.54 | 0.00 | 261.83 | |
Maximum of Months | 412.83 | 0.50 | 0.48 | 12890.49 | 39.79 | 288.33 | 377.33 | 4101.89 | 28.14 | 146.67 | 347.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-07:40 | 2747.16 | 22.49 | 106.33 | 266.00 | 1561.26 | 22.97 | 83.33 | 241.50 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-07:30 | 3490.95 | 22.32 | 96.83 | 268.00 | 1972.48 | 22.87 | 72.67 | 245.17 |
March | 351.33 | 0.49 | 0.48 | 01-MAR-06:49 | 3556.82 | 21.40 | 105.33 | 328.50 | 1956.30 | 22.04 | 75.83 | 302.50 |
April | 381.83 | 0.50 | 0.48 | 01-APR-05:00 | 4961.89 | 21.62 | 114.83 | 357.67 | 2081.65 | 21.80 | 67.17 | 342.67 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-05:00 | 4030.68 | 20.19 | 95.50 | 377.67 | 2309.74 | 21.20 | 66.33 | 352.33 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:19 | 3867.06 | 19.76 | 111.83 | 393.83 | 2240.65 | 20.82 | 82.50 | 360.67 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:40 | 3853.35 | 20.34 | 103.83 | 386.17 | 2115.48 | 21.19 | 71.83 | 358.50 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:40 | 4629.05 | 22.41 | 134.00 | 381.17 | 1959.75 | 21.62 | 75.00 | 361.67 |
September | 359.33 | 0.49 | 0.48 | 01-SEP-06:10 | 3970.05 | 21.36 | 109.50 | 333.33 | 2248.47 | 22.20 | 80.83 | 311.33 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:30 | 3606.67 | 21.71 | 103.00 | 305.83 | 2041.90 | 22.51 | 77.33 | 285.83 |
November | 284.17 | 0.50 | 0.48 | 01-NOV-06:49 | 2897.14 | 21.27 | 80.50 | 267.83 | 1628.27 | 22.70 | 67.33 | 244.17 |
December | 265.67 | 0.51 | 0.48 | 01-DEC-07:49 | 3191.96 | 22.88 | 95.67 | 249.00 | 1877.75 | 23.11 | 74.00 | 216.17 |
Annual Sum or Average | 4149.83 | 0.50 | 3801.91 | 21.39 | 1257.17 | 3915.00 | 2020.81 | 21.99 | 894.17 | 3622.50 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 2747.16 | 19.76 | 80.50 | 249.00 | 1561.26 | 20.82 | 66.33 | 216.17 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 4961.89 | 22.88 | 134.00 | 393.83 | 2309.74 | 23.11 | 83.33 | 361.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-08:39 | 683.90 | 11.26 | 0.00 | 247.50 | 457.08 | 15.06 | 0.00 | 201.00 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-08:09 | 808.72 | 12.24 | 0.00 | 254.50 | 554.97 | 15.99 | 0.00 | 216.67 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:19 | 957.38 | 12.97 | 0.00 | 319.67 | 626.17 | 16.56 | 0.00 | 280.50 |
April | 381.83 | 0.49 | 0.48 | 01-APR-06:19 | 1205.20 | 14.86 | 0.00 | 361.33 | 797.03 | 18.40 | 6.67 | 343.33 |
May | 378.00 | 0.49 | 0.48 | 01-MAY-06:10 | 1399.08 | 14.62 | 1.00 | 389.17 | 850.68 | 18.24 | 15.50 | 359.50 |
June | 412.83 | 0.48 | 0.48 | 01-JUN-05:40 | 1446.21 | 17.39 | 77.17 | 404.00 | 826.93 | 18.73 | 31.00 | 382.33 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1430.45 | 17.07 | 54.00 | 395.50 | 870.32 | 18.82 | 23.50 | 373.17 |
August | 408.83 | 0.49 | 0.48 | 01-AUG-05:00 | 1294.63 | 14.69 | 0.00 | 385.00 | 839.59 | 18.25 | 6.33 | 368.50 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:40 | 1016.68 | 13.69 | 0.00 | 328.67 | 678.39 | 17.28 | 0.00 | 297.17 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-07:10 | 743.83 | 11.88 | 0.00 | 290.00 | 528.23 | 15.64 | 0.00 | 249.17 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-07:19 | 727.30 | 12.12 | 0.00 | 256.00 | 503.00 | 15.93 | 0.00 | 216.67 |
December | 265.67 | 0.53 | 0.48 | 01-DEC-08:20 | 606.80 | 10.57 | 0.00 | 231.67 | 434.93 | 14.45 | 0.00 | 181.50 |
Annual Sum or Average | 4149.83 | 0.50 | 1067.37 | 13.88 | 132.17 | 3863.00 | 685.55 | 17.15 | 83.00 | 3469.50 | ||
Minimum of Months | 265.67 | 0.48 | 0.48 | 606.80 | 10.57 | 0.00 | 231.67 | 434.93 | 14.45 | 0.00 | 181.50 | |
Maximum of Months | 412.83 | 0.53 | 0.48 | 1446.21 | 17.39 | 77.17 | 404.00 | 870.32 | 18.82 | 31.00 | 382.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-08:39 | 2378.04 | 20.81 | 85.33 | 272.17 | 1224.76 | 21.21 | 60.67 | 243.33 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-08:09 | 3474.89 | 22.64 | 93.17 | 265.67 | 1942.52 | 23.10 | 68.00 | 241.67 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:30 | 3666.09 | 21.03 | 106.00 | 330.50 | 1449.79 | 20.06 | 48.00 | 303.00 |
April | 381.83 | 0.49 | 0.48 | 01-APR-06:40 | 4510.59 | 21.02 | 110.33 | 361.83 | 1913.74 | 20.53 | 51.00 | 344.00 |
May | 378.00 | 0.49 | 0.48 | 01-MAY-06:40 | 3346.56 | 16.32 | 46.67 | 386.33 | 1932.59 | 17.20 | 0.00 | 366.83 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-06:10 | 3532.82 | 12.40 | 0.00 | 385.17 | 2104.69 | 16.18 | 0.00 | 360.83 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:49 | 3407.14 | 13.55 | 3.67 | 386.50 | 1935.66 | 16.99 | 0.00 | 362.67 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:30 | 3377.78 | 17.35 | 62.50 | 377.17 | 1831.01 | 17.84 | 5.17 | 357.00 |
September | 359.33 | 0.49 | 0.48 | 01-SEP-06:49 | 3804.28 | 21.21 | 110.00 | 333.83 | 1567.39 | 20.42 | 54.33 | 314.50 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3454.41 | 21.41 | 100.00 | 306.83 | 1929.02 | 21.95 | 70.17 | 284.67 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-07:19 | 3363.46 | 23.63 | 105.00 | 276.33 | 1996.93 | 24.09 | 80.33 | 254.33 |
December | 265.67 | 0.51 | 0.48 | 01-DEC-08:20 | 3096.62 | 24.07 | 106.17 | 253.33 | 1852.89 | 24.32 | 84.33 | 230.00 |
Annual Sum or Average | 4149.83 | 0.50 | 3479.79 | 19.18 | 928.83 | 3935.67 | 1814.03 | 19.96 | 522.00 | 3662.83 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 2378.04 | 12.40 | 0.00 | 253.33 | 1224.76 | 16.18 | 0.00 | 230.00 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 4510.59 | 24.07 | 110.33 | 386.50 | 2104.69 | 24.32 | 84.33 | 366.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.49 | 0.48 | 01-JAN-07:40 | 10529.66 | 37.21 | 288.33 | 287.00 | 2846.39 | 24.35 | 127.17 | 277.33 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-07:40 | 12892.78 | 37.38 | 271.67 | 275.50 | 2229.09 | 21.30 | 79.17 | 264.33 |
March | 351.33 | 0.49 | 0.48 | 01-MAR-06:00 | 2439.54 | 13.63 | 10.67 | 331.17 | 1501.44 | 16.95 | 7.83 | 302.83 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:30 | 1977.40 | 14.49 | 0.00 | 353.00 | 1253.71 | 18.04 | 5.17 | 330.67 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:19 | 1528.22 | 13.93 | 0.00 | 373.83 | 987.91 | 17.49 | 0.00 | 343.00 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-05:00 | 1220.27 | 12.87 | 0.00 | 375.83 | 798.84 | 16.53 | 0.00 | 333.83 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:49 | 1473.76 | 13.64 | 0.00 | 377.33 | 943.64 | 17.25 | 0.33 | 343.17 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:19 | 1835.43 | 14.23 | 0.00 | 373.83 | 1148.95 | 17.77 | 0.00 | 347.00 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:30 | 2396.44 | 14.49 | 16.50 | 331.17 | 1400.18 | 17.19 | 4.33 | 306.17 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:49 | 6361.27 | 25.56 | 183.50 | 319.00 | 1881.08 | 17.01 | 17.17 | 305.00 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:49 | 11898.44 | 38.43 | 280.00 | 284.83 | 2854.11 | 24.37 | 112.67 | 275.00 |
December | 265.67 | 0.49 | 0.48 | 01-DEC-07:49 | 12050.41 | 39.78 | 263.50 | 269.67 | 4103.76 | 28.13 | 146.67 | 261.83 |
Annual Sum or Average | 4149.83 | 0.50 | 4909.48 | 21.44 | 1314.17 | 3952.17 | 1701.82 | 19.25 | 500.50 | 3690.17 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 1220.27 | 12.87 | 0.00 | 269.67 | 798.84 | 16.53 | 0.00 | 261.83 | |
Maximum of Months | 412.83 | 0.50 | 0.48 | 12892.78 | 39.78 | 288.33 | 377.33 | 4103.76 | 28.13 | 146.67 | 347.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-07:40 | 2748.06 | 22.46 | 106.33 | 266.00 | 1562.25 | 22.95 | 83.00 | 241.50 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-07:30 | 3492.00 | 22.29 | 96.83 | 268.00 | 1973.66 | 22.86 | 72.67 | 245.17 |
March | 351.33 | 0.49 | 0.48 | 01-MAR-06:49 | 3558.26 | 21.37 | 105.33 | 328.50 | 1957.64 | 22.03 | 75.83 | 302.50 |
April | 381.83 | 0.50 | 0.48 | 01-APR-05:00 | 4963.38 | 21.59 | 114.83 | 357.67 | 2083.32 | 21.79 | 67.17 | 342.67 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-05:00 | 4032.07 | 20.16 | 95.50 | 377.67 | 2311.31 | 21.18 | 66.33 | 352.83 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:19 | 3868.32 | 19.73 | 111.83 | 393.83 | 2241.88 | 20.80 | 82.50 | 360.83 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:40 | 3854.72 | 20.31 | 103.83 | 386.33 | 2116.90 | 21.17 | 71.83 | 358.67 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:40 | 4630.56 | 22.39 | 134.00 | 381.17 | 1961.29 | 21.61 | 75.00 | 361.67 |
September | 359.33 | 0.49 | 0.48 | 01-SEP-06:10 | 3971.39 | 21.33 | 109.50 | 333.33 | 2249.86 | 22.19 | 80.67 | 311.33 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:30 | 3607.41 | 21.68 | 103.00 | 305.83 | 2042.87 | 22.50 | 77.33 | 285.83 |
November | 284.17 | 0.50 | 0.48 | 01-NOV-06:49 | 2897.87 | 21.24 | 80.50 | 267.83 | 1629.31 | 22.69 | 67.17 | 244.17 |
December | 265.67 | 0.51 | 0.48 | 01-DEC-07:49 | 3192.52 | 22.86 | 95.67 | 249.17 | 1878.56 | 23.10 | 73.83 | 216.17 |
Annual Sum or Average | 4149.83 | 0.50 | 3803.10 | 21.37 | 1257.17 | 3915.33 | 2022.10 | 21.97 | 893.33 | 3623.33 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 2748.06 | 19.73 | 80.50 | 249.17 | 1562.25 | 20.80 | 66.33 | 216.17 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 4963.38 | 22.86 | 134.00 | 393.83 | 2311.31 | 23.10 | 83.00 | 361.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-08:39 | 684.39 | 11.22 | 0.00 | 247.50 | 457.59 | 15.05 | 0.00 | 201.00 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-08:09 | 809.20 | 12.20 | 0.00 | 254.67 | 555.54 | 15.97 | 0.00 | 216.83 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:19 | 958.24 | 12.94 | 0.00 | 319.67 | 626.90 | 16.55 | 0.00 | 280.50 |
April | 381.83 | 0.49 | 0.48 | 01-APR-06:19 | 1206.07 | 14.83 | 0.00 | 361.33 | 797.89 | 18.39 | 6.67 | 343.67 |
May | 378.00 | 0.49 | 0.48 | 01-MAY-06:10 | 1400.12 | 14.59 | 1.00 | 389.17 | 851.63 | 18.23 | 14.83 | 359.50 |
June | 412.83 | 0.48 | 0.48 | 01-JUN-05:40 | 1447.22 | 17.37 | 77.17 | 404.00 | 827.80 | 18.72 | 30.83 | 382.33 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1431.56 | 17.04 | 54.00 | 395.50 | 871.29 | 18.81 | 23.33 | 373.17 |
August | 408.83 | 0.49 | 0.48 | 01-AUG-05:00 | 1295.67 | 14.66 | 0.00 | 385.00 | 840.54 | 18.24 | 5.83 | 368.50 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:40 | 1017.45 | 13.66 | 0.00 | 328.67 | 679.13 | 17.26 | 0.00 | 297.17 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-07:10 | 744.19 | 11.85 | 0.00 | 290.00 | 528.71 | 15.63 | 0.00 | 249.33 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-07:19 | 727.66 | 12.09 | 0.00 | 256.00 | 503.50 | 15.91 | 0.00 | 216.67 |
December | 265.67 | 0.53 | 0.48 | 01-DEC-08:20 | 607.00 | 10.54 | 0.00 | 231.83 | 435.32 | 14.44 | 0.00 | 181.67 |
Annual Sum or Average | 4149.83 | 0.50 | 1068.13 | 13.85 | 132.17 | 3863.33 | 686.29 | 17.13 | 81.50 | 3470.33 | ||
Minimum of Months | 265.67 | 0.48 | 0.48 | 607.00 | 10.54 | 0.00 | 231.83 | 435.32 | 14.44 | 0.00 | 181.67 | |
Maximum of Months | 412.83 | 0.53 | 0.48 | 1447.22 | 17.37 | 77.17 | 404.00 | 871.29 | 18.81 | 30.83 | 382.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-08:39 | 2378.90 | 20.78 | 85.33 | 272.17 | 1225.74 | 21.20 | 60.67 | 243.50 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-08:09 | 3475.83 | 22.61 | 93.17 | 265.67 | 1943.69 | 23.09 | 67.67 | 242.00 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:30 | 3667.63 | 21.00 | 106.00 | 330.67 | 1451.15 | 20.04 | 48.00 | 303.00 |
April | 381.83 | 0.49 | 0.48 | 01-APR-06:40 | 4512.16 | 20.99 | 110.33 | 361.83 | 1915.24 | 20.51 | 51.00 | 344.17 |
May | 378.00 | 0.49 | 0.48 | 01-MAY-06:40 | 3348.01 | 16.29 | 46.67 | 386.33 | 1934.02 | 17.18 | 0.00 | 366.83 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-06:10 | 3534.16 | 12.36 | 0.00 | 385.17 | 2105.91 | 16.16 | 0.00 | 361.00 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:49 | 3408.77 | 13.52 | 3.67 | 386.50 | 1937.14 | 16.98 | 0.00 | 362.83 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:30 | 3379.69 | 17.32 | 62.50 | 377.33 | 1832.77 | 17.82 | 5.17 | 357.00 |
September | 359.33 | 0.49 | 0.48 | 01-SEP-06:49 | 3805.76 | 21.18 | 110.00 | 333.83 | 1568.82 | 20.40 | 54.33 | 314.50 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3455.21 | 21.38 | 100.00 | 306.83 | 1930.02 | 21.93 | 70.17 | 284.83 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-07:19 | 3364.24 | 23.60 | 105.00 | 276.33 | 1997.97 | 24.08 | 80.17 | 254.50 |
December | 265.67 | 0.51 | 0.48 | 01-DEC-08:20 | 3097.16 | 24.04 | 106.17 | 253.33 | 1853.66 | 24.31 | 84.00 | 230.17 |
Annual Sum or Average | 4149.83 | 0.50 | 3481.08 | 19.15 | 928.83 | 3936.00 | 1815.33 | 19.95 | 521.17 | 3664.33 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 2378.90 | 12.36 | 0.00 | 253.33 | 1225.74 | 16.16 | 0.00 | 230.17 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 4512.16 | 24.04 | 110.33 | 386.50 | 2105.91 | 24.31 | 84.00 | 366.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.860882E+10 | 28703.24 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.491894E+10 | 27943.23 | 04-FEB-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137884E+10 | 19989.29 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 94160827.42 | 12785.70 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32992211.99 | 6257.18 | 06-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.818963E+09 | 22450.98 | 26-OCT-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165809E+10 | 22107.46 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.622594E+10 | 32731.09 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.860882E+10 | 32731.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 18862133.49 | 3677.72 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7940638.04 | 1999.11 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1622925.42 | 354.65 | 15-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28425696.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18862133.49 | 3677.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 22350750.04 | 8395.46 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8674889.94 | 3876.89 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16498406.31 | 3448.51 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47524046.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22350750.04 | 8395.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 62939953.88 | 15328.15 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23359480.80 | 15334.27 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 644378.39 | 384.15 | 26-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20300346.47 | 11048.79 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 62939953.88 | 15334.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116966E+12 | 297931.54 | 21-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.756728E+11 | 337071.80 | 03-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274903E+11 | 292384.05 | 02-MAR-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.500783E+10 | 139297.80 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.898775E+09 | 73777.97 | 06-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159841E+11 | 216413.36 | 27-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.355316E+11 | 237111.39 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114349E+12 | 318557.41 | 15-DEC-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391901E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116966E+12 | 337071.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143206E+11 | 134896.73 | 04-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.825101E+10 | 135962.24 | 10-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145410E+10 | 144455.10 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38233672.10 | 34952.27 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.600346E+09 | 139766.47 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.294311E+10 | 144395.54 | 25-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162437E+11 | 132954.76 | 27-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162437E+11 | 144455.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.578714E+10 | 159364.99 | 17-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.270357E+10 | 159517.62 | 27-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.284299E+09 | 159444.95 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6787488.74 | 5169.19 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246923E+09 | 160782.75 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.715788E+09 | 159195.03 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.559491E+10 | 159485.37 | 11-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.578714E+10 | 160782.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.409280E+10 | 172446.81 | 17-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216293E+10 | 173154.32 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190506E+09 | 165818.11 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 658332.25 | 873.73 | 08-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220777E+09 | 168934.76 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148021E+09 | 156720.21 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.382650E+10 | 172901.53 | 09-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.409280E+10 | 173154.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.420214E+10 | 158999.22 | 17-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221543E+10 | 158977.69 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127830E+09 | 113907.34 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147241E+09 | 98557.63 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.284619E+09 | 158827.18 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.394938E+10 | 158819.09 | 05-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.420214E+10 | 158999.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142625E+11 | 32708.61 | 30-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.959270E+10 | 33969.08 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409067E+10 | 22277.53 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101453E+10 | 16263.69 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195138E+09 | 9385.85 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3600300.72 | 2860.76 | 09-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.245142E+10 | 24575.40 | 26-OCT-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.557264E+10 | 29672.99 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147014E+11 | 32781.93 | 15-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.518846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147014E+11 | 33969.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.254308E+10 | 74055.31 | 17-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.996843E+09 | 74028.05 | 06-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 58904584.72 | 72806.76 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14804360.27 | 10784.08 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.449843E+09 | 73214.78 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246159E+10 | 74081.08 | 04-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.652506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.254308E+10 | 74081.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.469650E+10 | 15395.81 | 19-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288938E+10 | 15394.57 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.949888E+09 | 15381.51 | 29-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140974E+09 | 15327.44 | 24-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12744966.99 | 8226.36 | 06-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.460496E+09 | 15318.14 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171572E+10 | 15400.14 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.502254E+10 | 15400.61 | 04-DEC-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.502254E+10 | 15400.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.204241E+10 | 18086.50 | 20-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111955E+10 | 18068.29 | 10-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.323120E+09 | 18031.64 | 06-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32362566.86 | 10393.93 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3566494.56 | 2821.73 | 06-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187413E+09 | 18023.47 | 26-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.554687E+09 | 18095.40 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201234E+10 | 18090.99 | 11-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.627546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204241E+10 | 18095.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195899E+10 | 19329.24 | 19-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116974E+10 | 19319.44 | 01-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.463498E+09 | 19283.39 | 18-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 83727546.75 | 15581.99 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18490874.45 | 6288.20 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.216449E+09 | 19192.15 | 26-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459640E+09 | 19212.01 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183406E+10 | 19335.26 | 04-DEC-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.620459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.195899E+10 | 19335.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163941E+10 | 18876.43 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.932305E+09 | 18869.52 | 06-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.263683E+09 | 18844.83 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16780829.03 | 7517.72 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2646153.72 | 1567.06 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141210E+09 | 18851.06 | 26-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.430077E+09 | 18927.92 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157645E+10 | 18923.05 | 11-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163941E+10 | 18927.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.746507E+09 | 16414.33 | 21-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312673E+09 | 14038.70 | 06-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 67920635.40 | 11416.29 | 30-MAR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3154545.04 | 4454.76 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 421713.31 | 1108.46 | 04-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5498310.77 | 9299.03 | 27-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4389922.95 | 8948.46 | 28-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111788E+09 | 13395.84 | 21-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.746507E+09 | 16414.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.138862E+11 | 0.138862E+11 | 62193.28 | 03-JAN-15:00 | 62193.28 | 0.00 |
February | 0.00 | 0.00 | 0.136920E+11 | 0.136920E+11 | 72055.44 | 14-FEB-16:00 | 72055.44 | 0.00 |
March | 0.00 | 0.00 | 0.156565E+11 | 0.156565E+11 | 77892.10 | 08-MAR-16:00 | 77892.10 | 0.00 |
April | 0.00 | 0.00 | 0.369160E+11 | 0.369160E+11 | 112125.08 | 17-APR-15:20 | 112125.08 | 0.00 |
May | 0.00 | 0.00 | 0.571789E+11 | 0.571789E+11 | 117748.38 | 30-MAY-14:30 | 117748.38 | 0.09 |
June | 0.00 | 0.00 | 0.124065E+12 | 0.123972E+12 | 176567.31 | 28-JUN-13:45 | 176567.31 | 0.34 |
July | 0.00 | 0.00 | 0.172752E+12 | 0.165404E+12 | 189226.32 | 16-JUL-09:21 | 127417.49 | 0.81 |
August | 0.00 | 0.00 | 0.159139E+12 | 0.152956E+12 | 183900.93 | 23-AUG-16:00 | 111942.56 | 0.85 |
September | 0.00 | 0.00 | 0.825700E+11 | 0.811634E+11 | 167061.41 | 05-SEP-13:10 | 104095.58 | 0.45 |
October | 0.00 | 0.00 | 0.431692E+11 | 0.431465E+11 | 147127.71 | 11-OCT-12:55 | 142009.88 | 0.11 |
November | 0.00 | 0.00 | 0.129330E+11 | 0.129330E+11 | 58956.37 | 06-NOV-13:05 | 58956.37 | 0.00 |
December | 0.00 | 0.00 | 0.174817E+11 | 0.174817E+11 | 58766.85 | 26-DEC-15:00 | 58766.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.749440E+12 | 0.734387E+12 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.129330E+11 | 0.129330E+11 | 58766.85 | 58766.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.172752E+12 | 0.165404E+12 | 189226.32 | 176567.31 | 0.85 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.550471E+11 | 0.550471E+11 | 433762.34 | 05-JAN-15:40 | 433762.34 | 0.00 |
February | 0.00 | 0.00 | 0.851283E+11 | 0.851283E+11 | 671779.59 | 14-FEB-16:00 | 671779.59 | 0.00 |
March | 0.00 | 0.00 | 0.157491E+12 | 0.157491E+12 | 629684.86 | 13-MAR-15:00 | 629684.86 | 0.00 |
April | 0.00 | 0.00 | 0.284171E+12 | 0.284171E+12 | 907305.86 | 13-APR-15:20 | 907305.86 | 0.00 |
May | 0.00 | 0.00 | 0.474317E+12 | 0.474317E+12 | 1008605.63 | 19-MAY-15:10 | 1008605.63 | 0.08 |
June | 0.00 | 0.00 | 0.905619E+12 | 0.905562E+12 | 1250941.29 | 28-JUN-14:50 | 1250941.29 | 0.29 |
July | 0.00 | 0.00 | 0.109072E+13 | 0.106923E+13 | 1368795.05 | 02-JUL-16:01 | 1034967.13 | 0.61 |
August | 0.00 | 0.00 | 0.104310E+13 | 0.102074E+13 | 1323897.77 | 13-AUG-14:51 | 1012747.57 | 0.64 |
September | 0.00 | 0.00 | 0.687725E+12 | 0.677553E+12 | 1395350.19 | 01-SEP-10:32 | 1340788.64 | 0.42 |
October | 0.00 | 0.00 | 0.360184E+12 | 0.360103E+12 | 1061252.29 | 11-OCT-12:53 | 1026418.15 | 0.10 |
November | 0.00 | 0.00 | 0.127798E+12 | 0.127798E+12 | 584751.38 | 02-NOV-15:20 | 584751.38 | 0.00 |
December | 0.00 | 0.00 | 0.145850E+11 | 0.145850E+11 | 331235.58 | 29-DEC-16:00 | 331235.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.528588E+13 | 0.523173E+13 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 0.145850E+11 | 0.145850E+11 | 331235.58 | 331235.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109072E+13 | 0.106923E+13 | 1395350.19 | 1340788.64 | 0.64 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.371390E+10 | 0.371390E+10 | 31955.45 | 23-JAN-15:40 | 31955.45 | 0.00 |
February | 0.00 | 0.00 | 0.580385E+10 | 0.580385E+10 | 68448.75 | 14-FEB-16:00 | 68448.75 | 0.00 |
March | 0.00 | 0.00 | 0.854119E+10 | 0.854119E+10 | 65967.64 | 15-MAR-16:00 | 65967.64 | 0.00 |
April | 0.00 | 0.00 | 0.289208E+11 | 0.289208E+11 | 110173.49 | 26-APR-15:10 | 110173.49 | 0.00 |
May | 0.00 | 0.00 | 0.523440E+11 | 0.523440E+11 | 123856.41 | 30-MAY-14:30 | 123856.41 | 0.08 |
June | 0.00 | 0.00 | 0.103094E+12 | 0.103092E+12 | 184014.90 | 28-JUN-13:43 | 184014.90 | 0.29 |
July | 0.00 | 0.00 | 0.125157E+12 | 0.122947E+12 | 160547.38 | 16-JUL-14:52 | 127386.56 | 0.62 |
August | 0.00 | 0.00 | 0.118052E+12 | 0.115843E+12 | 156996.20 | 13-AUG-14:11 | 131522.67 | 0.65 |
September | 0.00 | 0.00 | 0.747200E+11 | 0.738785E+11 | 152795.90 | 05-SEP-13:40 | 97094.89 | 0.41 |
October | 0.00 | 0.00 | 0.336305E+11 | 0.336286E+11 | 124873.21 | 11-OCT-12:53 | 124873.21 | 0.08 |
November | 0.00 | 0.00 | 0.813049E+10 | 0.813049E+10 | 54410.82 | 01-NOV-15:00 | 54410.82 | 0.00 |
December | 0.00 | 0.00 | 0.177269E+10 | 0.177269E+10 | 24532.07 | 29-DEC-15:50 | 24532.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.563880E+12 | 0.558616E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 0.177269E+10 | 0.177269E+10 | 24532.07 | 24532.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125157E+12 | 0.122947E+12 | 184014.90 | 184014.90 | 0.65 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.153803E+10 | 0.153803E+10 | 30470.45 | 02-JAN-14:10 | 30470.45 | 0.00 |
February | 0.00 | 0.00 | 0.230971E+10 | 0.230971E+10 | 43682.10 | 13-FEB-16:00 | 43682.10 | 0.00 |
March | 0.00 | 0.00 | 0.801790E+10 | 0.801790E+10 | 44516.14 | 13-MAR-15:00 | 44516.14 | 0.00 |
April | 0.00 | 0.00 | 0.204858E+11 | 0.204858E+11 | 61761.68 | 17-APR-14:00 | 61761.68 | 0.00 |
May | 0.00 | 0.00 | 0.274510E+11 | 0.273308E+11 | 77471.08 | 23-MAY-09:50 | 77471.08 | 0.04 |
June | 0.00 | 0.00 | 0.222848E+11 | 0.220665E+11 | 88180.16 | 12-JUN-13:55 | 88180.16 | 0.10 |
July | 0.00 | 0.00 | 0.159998E+11 | 0.126465E+11 | 104132.48 | 17-JUL-10:00 | 76098.40 | 0.07 |
August | 0.00 | 0.00 | 0.404123E+11 | 0.370199E+11 | 102860.55 | 23-AUG-15:40 | 65679.58 | 0.22 |
September | 0.00 | 0.00 | 0.470443E+11 | 0.451165E+11 | 102092.54 | 05-SEP-13:00 | 66130.65 | 0.24 |
October | 0.00 | 0.00 | 0.225356E+11 | 0.224422E+11 | 82156.53 | 10-OCT-14:00 | 82156.53 | 0.06 |
November | 0.00 | 0.00 | 0.152230E+10 | 0.152230E+10 | 26783.90 | 09-NOV-14:00 | 26783.90 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.209602E+12 | 0.200496E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.470443E+11 | 0.451165E+11 | 104132.48 | 88180.16 | 0.24 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.118753E+11 | 0.103156E+11 | 5617.22 | 01-JAN-10:43 | 4853.43 | 0.00 |
February | 0.00 | 0.00 | 0.149217E+11 | 0.135522E+11 | 93453.13 | 14-FEB-16:00 | 93453.13 | 0.00 |
March | 0.00 | 0.00 | 0.362737E+11 | 0.354590E+11 | 202456.01 | 08-MAR-16:00 | 202456.01 | 0.00 |
April | 0.00 | 0.00 | 0.235883E+12 | 0.234631E+12 | 391794.46 | 13-APR-17:00 | 391794.46 | 0.00 |
May | 0.00 | 0.00 | 0.678380E+11 | 0.655721E+11 | 154009.26 | 22-MAY-12:05 | 141251.47 | 0.00 |
June | 0.00 | 0.00 | 0.322089E+12 | 0.298760E+12 | 317587.35 | 30-JUN-14:00 | 225494.02 | 0.00 |
July | 0.00 | 0.00 | 0.801244E+12 | 0.627767E+12 | 499520.31 | 31-JUL-24:00 | 229991.92 | 0.00 |
August | 0.00 | 0.00 | 0.105388E+13 | 0.795431E+12 | 539856.19 | 26-AUG-10:00 | 230381.80 | 0.00 |
September | 0.00 | 0.00 | 0.975463E+11 | 0.877674E+11 | 177063.93 | 01-SEP-12:50 | 146134.26 | 0.00 |
October | 0.00 | 0.00 | 0.743368E+11 | 0.674859E+11 | 258740.23 | 10-OCT-13:30 | 232299.88 | 0.00 |
November | 0.00 | 0.00 | 0.157066E+11 | 0.146737E+11 | 106878.99 | 09-NOV-14:00 | 101053.32 | 0.00 |
December | 0.00 | 0.00 | 0.150883E+11 | 0.146985E+11 | 9918.71 | 24-DEC-14:52 | 9918.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.274668E+13 | 0.226611E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.118753E+11 | 0.103156E+11 | 5617.22 | 4853.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105388E+13 | 0.795431E+12 | 539856.19 | 391794.46 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.479320E+10 | 0.479255E+10 | 3234.71 | 01-JAN-16:42 | 3227.79 | 0.00 |
February | 0.00 | 0.00 | 0.924696E+10 | 0.924397E+10 | 4833.71 | 15-FEB-17:00 | 4833.71 | 0.00 |
March | 0.00 | 0.00 | 0.157329E+11 | 0.157273E+11 | 7744.21 | 31-MAR-24:00 | 7744.21 | 0.00 |
April | 0.00 | 0.00 | 0.204666E+11 | 0.204658E+11 | 9078.02 | 16-APR-18:22 | 9078.02 | 0.00 |
May | 0.00 | 0.00 | 0.611851E+10 | 0.607908E+10 | 4160.77 | 31-MAY-24:00 | 4160.77 | 0.00 |
June | 0.00 | 0.00 | 0.112902E+11 | 0.112001E+11 | 6124.91 | 30-JUN-23:55 | 6100.58 | 0.00 |
July | 0.00 | 0.00 | 0.170603E+11 | 0.168402E+11 | 8011.98 | 31-JUL-24:00 | 8011.98 | 0.00 |
August | 0.00 | 0.00 | 0.219087E+11 | 0.216702E+11 | 8732.10 | 11-AUG-18:33 | 8544.26 | 0.00 |
September | 0.00 | 0.00 | 0.624678E+10 | 0.610220E+10 | 4144.54 | 30-SEP-24:00 | 4131.97 | 0.00 |
October | 0.00 | 0.00 | 0.110949E+11 | 0.110386E+11 | 5936.88 | 31-OCT-24:00 | 5936.88 | 0.00 |
November | 0.00 | 0.00 | 0.151936E+11 | 0.151820E+11 | 7126.38 | 05-NOV-16:50 | 7126.38 | 0.00 |
December | 0.00 | 0.00 | 0.204277E+11 | 0.204275E+11 | 8851.76 | 31-DEC-16:50 | 8851.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159580E+12 | 0.158769E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.479320E+10 | 0.479255E+10 | 3234.71 | 3227.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219087E+11 | 0.216702E+11 | 9078.02 | 9078.02 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.306390E+11 | 0.306322E+11 | 25906.55 | 26-JAN-17:00 | 25906.55 | 0.00 |
February | 0.00 | 0.00 | 0.767349E+11 | 0.767047E+11 | 45931.44 | 15-FEB-17:00 | 45931.44 | 0.00 |
March | 0.00 | 0.00 | 0.142047E+12 | 0.141990E+12 | 72126.57 | 31-MAR-23:30 | 72126.57 | 0.00 |
April | 0.00 | 0.00 | 0.191608E+12 | 0.191600E+12 | 86577.21 | 16-APR-18:13 | 86577.21 | 0.00 |
May | 0.00 | 0.00 | 0.549160E+11 | 0.545284E+11 | 39110.34 | 31-MAY-24:00 | 39110.34 | 0.00 |
June | 0.00 | 0.00 | 0.105103E+12 | 0.104210E+12 | 57808.74 | 30-JUN-23:55 | 57565.18 | 0.00 |
July | 0.00 | 0.00 | 0.159905E+12 | 0.157717E+12 | 75852.22 | 31-JUL-24:00 | 75852.22 | 0.00 |
August | 0.00 | 0.00 | 0.207324E+12 | 0.204944E+12 | 83374.56 | 11-AUG-18:20 | 81692.62 | 0.00 |
September | 0.00 | 0.00 | 0.563616E+11 | 0.549415E+11 | 39236.16 | 30-SEP-23:30 | 39022.26 | 0.00 |
October | 0.00 | 0.00 | 0.996049E+11 | 0.990476E+11 | 54984.90 | 31-OCT-24:00 | 54984.90 | 0.00 |
November | 0.00 | 0.00 | 0.134366E+12 | 0.134250E+12 | 64416.92 | 02-NOV-16:40 | 63606.99 | 0.00 |
December | 0.00 | 0.00 | 0.178174E+12 | 0.178172E+12 | 79555.18 | 31-DEC-16:45 | 79555.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143678E+13 | 0.142874E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.306390E+11 | 0.306322E+11 | 25906.55 | 25906.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.207324E+12 | 0.204944E+12 | 86577.21 | 86577.21 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.132094E+10 | 0.132041E+10 | 2501.36 | 26-JAN-17:00 | 2501.36 | 0.00 |
February | 0.00 | 0.00 | 0.625037E+10 | 0.624746E+10 | 4626.23 | 15-FEB-17:00 | 4626.23 | 0.00 |
March | 0.00 | 0.00 | 0.132752E+11 | 0.132696E+11 | 6902.30 | 31-MAR-23:20 | 6902.30 | 0.00 |
April | 0.00 | 0.00 | 0.187721E+11 | 0.187713E+11 | 8795.44 | 16-APR-18:00 | 8795.44 | 0.00 |
May | 0.00 | 0.00 | 0.534281E+10 | 0.530417E+10 | 3849.96 | 31-MAY-23:50 | 3849.96 | 0.00 |
June | 0.00 | 0.00 | 0.105583E+11 | 0.104691E+11 | 5782.57 | 30-JUN-23:55 | 5757.83 | 0.00 |
July | 0.00 | 0.00 | 0.161406E+11 | 0.159219E+11 | 7634.41 | 04-JUL-18:35 | 7634.41 | 0.00 |
August | 0.00 | 0.00 | 0.208347E+11 | 0.205968E+11 | 8452.38 | 11-AUG-18:10 | 8286.30 | 0.00 |
September | 0.00 | 0.00 | 0.556642E+10 | 0.542438E+10 | 3892.03 | 30-SEP-23:20 | 3866.57 | 0.00 |
October | 0.00 | 0.00 | 0.932611E+10 | 0.927053E+10 | 5289.42 | 31-OCT-23:30 | 5289.42 | 0.00 |
November | 0.00 | 0.00 | 0.120421E+11 | 0.120307E+11 | 6450.21 | 02-NOV-16:40 | 6368.81 | 0.00 |
December | 0.00 | 0.00 | 0.158117E+11 | 0.158115E+11 | 7779.54 | 29-DEC-16:40 | 7779.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135242E+12 | 0.134438E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.132094E+10 | 0.132041E+10 | 2501.36 | 2501.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208347E+11 | 0.205968E+11 | 8795.44 | 8795.44 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3.58 | 51898.83 | 02-JAN-05:01 | 67803.71 | 1097705.52 | 19-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 46612.25 | 1095565.02 | 01-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 13844.39 | 872276.31 | 04-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2473.17 | 222795.34 | 08-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 432.42 | 100012.96 | 06-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1.24 | 2632.06 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 8027.63 | 930264.12 | 26-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 19437.97 | 1037704.83 | 28-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 66345.84 | 1174981.59 | 04-DEC-05:01 |
Annual Sum or Average | 0.30 | 18664.63 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 3.58 | 51898.83 | 67803.71 | 1174981.59 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 28291.84 | 523661.04 | 05-JAN-15:40 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46276.23 | 1115213.88 | 14-FEB-16:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 73852.87 | 962837.23 | 13-MAR-14:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 148874.48 | 1423588.85 | 14-APR-14:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 237334.46 | 1501133.76 | 19-MAY-12:05 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 457476.08 | 1881997.69 | 30-JUN-08:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 539527.64 | 1996744.82 | 06-JUL-08:21 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 517845.40 | 1919653.69 | 03-AUG-09:02 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 350170.18 | 2007562.48 | 01-SEP-12:10 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 178370.33 | 1962914.60 | 10-OCT-12:07 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 58941.42 | 775169.46 | 02-NOV-15:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 13473.18 | 408698.57 | 29-DEC-15:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 221942.92 | 0.00 | ||||
Minimum of Months | 13473.18 | 408698.57 | 0.00 | 0.00 | ||
Maximum of Months | 539527.64 | 2007562.48 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27624.16 | 521941.78 | 05-JAN-15:40 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 45436.15 | 1104770.97 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 72853.64 | 963235.41 | 13-MAR-14:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 147428.40 | 1423256.89 | 13-APR-13:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 236989.79 | 1440015.03 | 23-MAY-12:30 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 459167.16 | 2357776.16 | 06-JUN-12:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 545702.59 | 2158198.85 | 16-JUL-14:41 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 528552.55 | 2295031.95 | 31-AUG-09:40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 367110.30 | 2222874.77 | 18-SEP-13:40 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 184738.97 | 2253247.37 | 10-OCT-11:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 58067.50 | 773880.94 | 02-NOV-15:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 12606.96 | 407191.29 | 29-DEC-15:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 224949.43 | 0.00 | ||||
Minimum of Months | 12606.96 | 407191.29 | 0.00 | 0.00 | ||
Maximum of Months | 545702.59 | 2357776.16 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27714.79 | 49938.08 | 26-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 62828.40 | 493082.28 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 111607.02 | 763280.16 | 08-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 335641.39 | 1372528.19 | 13-APR-17:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 219223.59 | 1052464.07 | 19-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 663708.09 | 1855013.97 | 28-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1117193.19 | 2027431.09 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1221866.57 | 2039182.28 | 01-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 305739.90 | 1222036.07 | 03-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 170878.35 | 1200430.55 | 01-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 89675.26 | 366768.61 | 09-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 110578.27 | 168036.76 | 29-DEC-07:15 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 372474.11 | 0.00 | ||||
Minimum of Months | 27714.79 | 49938.08 | 0.00 | 0.00 | ||
Maximum of Months | 1221866.57 | 2039182.28 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 14391.25 | 51437.51 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 14589.14 | 51477.10 | 06-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15126.23 | 50996.50 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13430.64 | 48739.33 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 12931.27 | 45864.57 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12313.76 | 42483.15 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 10763.15 | 39736.83 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11667.08 | 39032.74 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 11301.58 | 40954.89 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12031.42 | 44195.21 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13136.21 | 47469.94 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 13486.23 | 50033.79 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 12921.25 | ||||
Minimum of Months | 0.00 | 0.00 | 10763.15 | 39032.74 | ||
Maximum of Months | 0.00 | 0.00 | 15126.23 | 51477.10 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 26157.91 | 596778.89 | 05-JAN-15:40 | 3358.73 | 120916.87 | 10-JAN-11:40 |
February | 45506.32 | 1331342.47 | 14-FEB-16:10 | 4769.01 | 129533.08 | 28-FEB-06:40 |
March | 77427.00 | 1118997.39 | 13-MAR-14:50 | 3814.68 | 116559.83 | 22-MAR-08:50 |
April | 177161.03 | 2016164.39 | 26-APR-13:05 | 3592.02 | 109498.73 | 03-APR-09:50 |
May | 289495.01 | 2139864.74 | 15-MAY-15:20 | 1548.08 | 101162.56 | 05-MAY-09:20 |
June | 600946.22 | 2139220.88 | 19-JUN-14:50 | 1529.56 | 92774.70 | 09-JUN-06:00 |
July | 730591.79 | 2969682.68 | 31-JUL-15:00 | 1069.62 | 45989.65 | 22-JUL-03:40 |
August | 683170.79 | 2760688.38 | 24-AUG-12:13 | 1695.59 | 54196.37 | 31-AUG-01:20 |
September | 464474.57 | 3085805.40 | 05-SEP-13:00 | 534.56 | 57076.01 | 11-SEP-05:40 |
October | 221646.62 | 2362994.22 | 11-OCT-12:32 | 2072.89 | 123936.05 | 30-OCT-06:43 |
November | 61212.61 | 891782.03 | 02-NOV-15:20 | 3343.72 | 120954.74 | 25-NOV-09:10 |
December | 5795.63 | 466345.33 | 29-DEC-16:00 | 8485.79 | 131808.04 | 14-DEC-05:01 |
Annual Sum or Average | 283426.95 | 2977.90 | ||||
Minimum of Months | 5795.63 | 466345.33 | 534.56 | 45989.65 | ||
Maximum of Months | 730591.79 | 3085805.40 | 8485.79 | 131808.04 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.480776E+10 | 0.42 | 15183.31 | 02-JAN-09:20 | 1.65 |
February | 0.520149E+10 | 0.44 | 12533.56 | 15-FEB-16:50 | 1.46 |
March | 0.833702E+10 | 0.55 | 14575.38 | 13-MAR-15:20 | 1.61 |
April | 0.115819E+11 | 0.70 | 19723.72 | 17-APR-15:20 | 1.94 |
May | 0.109834E+11 | 0.63 | 23057.41 | 22-MAY-04:12 | 2.13 |
June | 0.182431E+11 | 0.91 | 23057.41 | 06-JUN-12:40 | 2.12 |
July | 0.234267E+11 | 1.08 | 23057.41 | 01-JUL-05:02 | 2.11 |
August | 0.222412E+11 | 1.06 | 23057.41 | 01-AUG-04:22 | 2.12 |
September | 0.109056E+11 | 0.64 | 23057.41 | 01-SEP-05:02 | 2.13 |
October | 0.915815E+10 | 0.57 | 23057.41 | 02-OCT-04:12 | 2.12 |
November | 0.707140E+10 | 0.50 | 14143.84 | 13-NOV-16:00 | 1.58 |
December | 0.607074E+10 | 0.45 | 13030.06 | 26-DEC-16:00 | 1.49 |
Annual Sum or Average | 0.138029E+12 | 0.66 | |||
Minimum of Months | 0.480776E+10 | 0.42 | 12533.56 | 1.46 | |
Maximum of Months | 0.234267E+11 | 1.08 | 23057.41 | 2.13 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.317559E+11 | 0.39 | 97993.60 | 04-JAN-06:02 | 1.32 |
February | 0.321592E+11 | 0.39 | 99328.53 | 24-FEB-06:02 | 1.33 |
March | 0.469438E+11 | 0.44 | 138976.20 | 04-MAR-06:02 | 1.63 |
April | 0.662156E+11 | 0.51 | 135083.95 | 28-APR-15:10 | 1.60 |
May | 0.798886E+11 | 0.55 | 215785.76 | 22-MAY-05:02 | 2.14 |
June | 0.104851E+12 | 0.65 | 215785.76 | 06-JUN-12:40 | 2.13 |
July | 0.115987E+12 | 0.67 | 215785.76 | 01-JUL-05:02 | 2.13 |
August | 0.113679E+12 | 0.67 | 215785.76 | 01-AUG-05:02 | 2.13 |
September | 0.773244E+11 | 0.54 | 215785.76 | 01-SEP-09:57 | 2.13 |
October | 0.571058E+11 | 0.46 | 215785.76 | 10-OCT-11:00 | 2.13 |
November | 0.386930E+11 | 0.40 | 89373.07 | 25-NOV-06:03 | 1.25 |
December | 0.315213E+11 | 0.38 | 74399.15 | 02-DEC-06:02 | 1.12 |
Annual Sum or Average | 0.796124E+12 | 0.50 | |||
Minimum of Months | 0.315213E+11 | 0.38 | 74399.15 | 1.12 | |
Maximum of Months | 0.115987E+12 | 0.67 | 215785.76 | 2.14 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.311432E+10 | 0.43 | 5331.51 | 02-JAN-05:01 | 0.87 |
February | 0.293897E+10 | 0.42 | 7697.42 | 15-FEB-17:00 | 1.07 |
March | 0.388994E+10 | 0.43 | 8900.69 | 08-MAR-16:10 | 1.16 |
April | 0.596514E+10 | 0.47 | 15292.57 | 26-APR-15:10 | 1.61 |
May | 0.772698E+10 | 0.52 | 18155.81 | 30-MAY-14:30 | 1.79 |
June | 0.112057E+11 | 0.64 | 24024.41 | 06-JUN-12:40 | 2.12 |
July | 0.127417E+11 | 0.67 | 24024.41 | 05-JUL-04:12 | 2.13 |
August | 0.121388E+11 | 0.65 | 24024.41 | 14-AUG-04:12 | 2.12 |
September | 0.768337E+10 | 0.52 | 24024.41 | 01-SEP-10:03 | 2.12 |
October | 0.491106E+10 | 0.43 | 24024.41 | 11-OCT-12:48 | 2.12 |
November | 0.316382E+10 | 0.40 | 6861.41 | 03-NOV-16:00 | 1.00 |
December | 0.308186E+10 | 0.41 | 5331.51 | 04-DEC-05:01 | 0.87 |
Annual Sum or Average | 0.785617E+11 | 0.50 | |||
Minimum of Months | 0.293897E+10 | 0.40 | 5331.51 | 0.87 | |
Maximum of Months | 0.127417E+11 | 0.67 | 24024.41 | 2.13 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.559408E+10 | 0.51 | 12825.76 | 02-JAN-07:03 | 2.16 |
February | 0.501890E+10 | 0.51 | 12825.76 | 01-FEB-07:05 | 2.17 |
March | 0.670510E+10 | 0.58 | 12825.76 | 01-MAR-07:03 | 2.17 |
April | 0.125216E+11 | 0.88 | 12825.76 | 01-APR-06:03 | 2.18 |
May | 0.114003E+11 | 0.77 | 12825.76 | 01-MAY-06:10 | 2.17 |
June | 0.635285E+10 | 0.43 | 12825.76 | 01-JUN-06:10 | 2.10 |
July | 0.247019E+10 | 0.15 | 12825.76 | 01-JUL-06:10 | 2.07 |
August | 0.789684E+10 | 0.50 | 12825.76 | 03-AUG-06:10 | 2.08 |
September | 0.121066E+11 | 0.80 | 12825.76 | 02-SEP-06:10 | 2.10 |
October | 0.131469E+11 | 0.87 | 12825.76 | 02-OCT-06:10 | 2.15 |
November | 0.124018E+11 | 0.88 | 12825.76 | 01-NOV-06:10 | 2.17 |
December | 0.916693E+10 | 0.69 | 12825.76 | 01-DEC-07:05 | 2.17 |
Annual Sum or Average | 0.104782E+12 | 0.63 | |||
Minimum of Months | 0.247019E+10 | 0.15 | 12825.76 | 2.07 | |
Maximum of Months | 0.131469E+11 | 0.88 | 12825.76 | 2.18 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130933E+12 | 1.63 | 48884.91 | 01-JAN-00:10 | 1.63 |
February | 0.118262E+12 | 1.63 | 48884.91 | 01-FEB-00:10 | 1.63 |
March | 0.130933E+12 | 1.64 | 48884.91 | 01-MAR-00:10 | 1.63 |
April | 0.126710E+12 | 1.64 | 48884.91 | 01-APR-00:10 | 1.64 |
May | 0.130933E+12 | 1.63 | 48884.91 | 01-MAY-00:10 | 1.64 |
June | 0.126710E+12 | 1.63 | 48884.91 | 01-JUN-00:10 | 1.64 |
July | 0.130933E+12 | 1.62 | 48884.91 | 01-JUL-00:10 | 1.62 |
August | 0.130933E+12 | 1.62 | 48884.91 | 01-AUG-00:10 | 1.61 |
September | 0.126710E+12 | 1.62 | 48884.91 | 01-SEP-00:03 | 1.62 |
October | 0.130933E+12 | 1.63 | 48884.91 | 01-OCT-00:10 | 1.63 |
November | 0.126710E+12 | 1.64 | 48884.91 | 01-NOV-00:10 | 1.64 |
December | 0.130933E+12 | 1.64 | 48884.91 | 01-DEC-00:10 | 1.64 |
Annual Sum or Average | 0.154163E+13 | 1.63 | |||
Minimum of Months | 0.118262E+12 | 1.62 | 48884.91 | 1.61 | |
Maximum of Months | 0.130933E+12 | 1.64 | 48884.91 | 1.64 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.173402E+10 | 1.12 | 647.41 | 01-JAN-00:10 | 1.11 |
February | 0.156621E+10 | 1.12 | 647.41 | 01-FEB-00:10 | 1.12 |
March | 0.173402E+10 | 1.12 | 647.41 | 01-MAR-00:10 | 1.12 |
April | 0.167808E+10 | 1.12 | 647.41 | 01-APR-00:10 | 1.12 |
May | 0.173402E+10 | 1.11 | 647.41 | 01-MAY-00:05 | 1.12 |
June | 0.167808E+10 | 1.11 | 647.41 | 01-JUN-00:10 | 1.12 |
July | 0.173402E+10 | 1.11 | 647.41 | 01-JUL-00:10 | 1.11 |
August | 0.173402E+10 | 1.11 | 647.41 | 01-AUG-00:10 | 1.11 |
September | 0.167808E+10 | 1.11 | 647.41 | 01-SEP-00:03 | 1.11 |
October | 0.173402E+10 | 1.11 | 647.41 | 01-OCT-00:10 | 1.11 |
November | 0.167808E+10 | 1.12 | 647.41 | 01-NOV-00:10 | 1.12 |
December | 0.173402E+10 | 1.12 | 647.41 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.204167E+11 | 1.11 | |||
Minimum of Months | 0.156621E+10 | 1.11 | 647.41 | 1.11 | |
Maximum of Months | 0.173402E+10 | 1.12 | 647.41 | 1.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166144E+11 | 1.12 | 6203.11 | 01-JAN-00:10 | 1.11 |
February | 0.150066E+11 | 1.12 | 6203.11 | 01-FEB-00:10 | 1.12 |
March | 0.166144E+11 | 1.12 | 6203.11 | 01-MAR-00:10 | 1.12 |
April | 0.160784E+11 | 1.12 | 6203.11 | 01-APR-00:10 | 1.12 |
May | 0.166144E+11 | 1.11 | 6203.11 | 01-MAY-00:05 | 1.12 |
June | 0.160784E+11 | 1.11 | 6203.11 | 01-JUN-00:10 | 1.12 |
July | 0.166144E+11 | 1.11 | 6203.11 | 01-JUL-00:10 | 1.11 |
August | 0.166144E+11 | 1.11 | 6203.11 | 01-AUG-00:10 | 1.11 |
September | 0.160784E+11 | 1.11 | 6203.11 | 01-SEP-00:03 | 1.11 |
October | 0.166144E+11 | 1.11 | 6203.11 | 01-OCT-00:10 | 1.11 |
November | 0.160784E+11 | 1.12 | 6203.11 | 01-NOV-00:10 | 1.12 |
December | 0.166144E+11 | 1.12 | 6203.11 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.195621E+12 | 1.11 | |||
Minimum of Months | 0.150066E+11 | 1.11 | 6203.11 | 1.11 | |
Maximum of Months | 0.166144E+11 | 1.12 | 6203.11 | 1.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169692E+10 | 1.12 | 633.56 | 01-JAN-00:10 | 1.11 |
February | 0.153270E+10 | 1.12 | 633.56 | 01-FEB-00:10 | 1.12 |
March | 0.169692E+10 | 1.12 | 633.56 | 01-MAR-00:10 | 1.12 |
April | 0.164218E+10 | 1.12 | 633.56 | 01-APR-00:10 | 1.12 |
May | 0.169692E+10 | 1.11 | 633.56 | 01-MAY-00:05 | 1.12 |
June | 0.164218E+10 | 1.11 | 633.56 | 01-JUN-00:10 | 1.12 |
July | 0.169692E+10 | 1.11 | 633.56 | 01-JUL-00:10 | 1.11 |
August | 0.169692E+10 | 1.11 | 633.56 | 01-AUG-00:10 | 1.11 |
September | 0.164218E+10 | 1.11 | 633.56 | 01-SEP-00:03 | 1.11 |
October | 0.169692E+10 | 1.11 | 633.56 | 01-OCT-00:10 | 1.11 |
November | 0.164218E+10 | 1.12 | 633.56 | 01-NOV-00:10 | 1.12 |
December | 0.169692E+10 | 1.12 | 633.56 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.199798E+11 | 1.11 | |||
Minimum of Months | 0.153270E+10 | 1.11 | 633.56 | 1.11 | |
Maximum of Months | 0.169692E+10 | 1.12 | 633.56 | 1.12 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 51241150.21 | 46578205.54 | 1157.51 | 20-JAN-06:01 | 1052.18 | 1052.18 | 42.62 | 14.28 |
February | 25545684.47 | 23221027.18 | 1148.37 | 06-FEB-06:01 | 1043.87 | 1043.87 | 44.73 | 14.22 |
March | 4473682.49 | 4066577.38 | 767.71 | 04-MAR-06:02 | 697.85 | 697.85 | 42.42 | 11.87 |
April | 593634.59 | 539613.84 | 28.29 | 08-APR-06:10 | 25.72 | 25.72 | 35.15 | 2.07 |
May | 75944.40 | 69033.46 | 7.63 | 06-MAY-06:07 | 6.93 | 6.93 | 31.74 | 0.84 |
June | 166.95 | 151.76 | 0.14 | 09-JUN-06:10 | 0.13 | 0.13 | 31.56 | 0.02 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 31.53 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 31.53 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 31.53 | 0.00 |
October | 3044235.78 | 2767210.32 | 805.59 | 26-OCT-05:02 | 732.28 | 732.28 | 41.66 | 12.13 |
November | 7110151.01 | 6463127.27 | 1022.48 | 28-NOV-06:01 | 929.43 | 929.43 | 41.63 | 13.51 |
December | 47960162.51 | 43595787.72 | 1142.21 | 22-DEC-06:01 | 1038.27 | 1038.27 | 41.64 | 14.20 |
Annual Sum or Average | 0.140045E+09 | 0.127301E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 | 0.00 | |
Maximum of Months | 51241150.21 | 46578205.54 | 1157.51 | 1052.18 | 1052.18 | 44.73 | 14.28 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 23412679.44 | 21282125.61 | 288.86 | 05-JAN-15:05 | 262.57 | 262.57 | 6.70 | 12.80 |
February | 51912439.27 | 47188407.30 | 1659.56 | 14-FEB-16:00 | 1508.54 | 1508.54 | 8.88 | 28.40 |
March | 87323914.61 | 79377438.38 | 1139.28 | 13-MAR-14:40 | 1035.61 | 1035.61 | 6.71 | 24.12 |
April | 0.193105E+09 | 0.175532E+09 | 2758.24 | 13-APR-13:40 | 2507.24 | 2507.24 | 10.63 | 35.21 |
May | 0.406379E+09 | 0.369398E+09 | 7411.87 | 23-MAY-12:30 | 6737.39 | 6737.39 | 9.94 | 52.60 |
June | 0.191616E+10 | 0.174179E+10 | 9393.20 | 06-JUN-12:40 | 8538.42 | 8538.42 | 10.62 | 57.76 |
July | 0.230617E+10 | 0.209631E+10 | 8332.95 | 06-JUL-08:20 | 7574.65 | 7574.65 | 12.01 | 55.08 |
August | 0.256222E+10 | 0.232906E+10 | 9393.20 | 03-AUG-08:38 | 8538.42 | 8538.42 | 10.28 | 57.76 |
September | 0.211295E+10 | 0.192067E+10 | 9393.20 | 02-SEP-13:20 | 8538.42 | 8538.42 | 9.93 | 57.76 |
October | 0.742176E+09 | 0.674638E+09 | 9393.20 | 02-OCT-09:40 | 8538.42 | 8538.42 | 9.83 | 57.76 |
November | 60975897.49 | 55427090.82 | 2458.76 | 02-NOV-16:00 | 2235.01 | 2235.01 | 7.33 | 33.56 |
December | 6250364.11 | 5681580.98 | 188.49 | 29-DEC-15:50 | 171.34 | 171.34 | 6.70 | 10.36 |
Annual Sum or Average | 0.104690E+11 | 0.951635E+10 | ||||||
Minimum of Months | 6250364.11 | 5681580.98 | 188.49 | 171.34 | 171.34 | 6.70 | 10.36 | |
Maximum of Months | 0.256222E+10 | 0.232906E+10 | 9393.20 | 8538.42 | 8538.42 | 12.01 | 57.76 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.201760E+10 | 0.183400E+10 | 3232.54 | 01-JAN-12:21 | 2938.38 | 2938.38 | 7.17 | 28.88 |
February | 0.230772E+10 | 0.209771E+10 | 3232.54 | 01-FEB-10:45 | 2938.38 | 2938.38 | 6.75 | 28.88 |
March | 0.318514E+10 | 0.289529E+10 | 3232.54 | 01-MAR-08:10 | 2938.38 | 2938.38 | 6.84 | 28.88 |
April | 0.397120E+10 | 0.360982E+10 | 3232.54 | 01-APR-05:03 | 2938.38 | 2938.38 | 6.73 | 28.88 |
May | 0.470432E+10 | 0.427623E+10 | 3232.54 | 01-MAY-06:11 | 2938.38 | 2938.38 | 6.94 | 28.88 |
June | 0.634763E+10 | 0.576999E+10 | 3232.54 | 01-JUN-04:12 | 2938.38 | 2938.38 | 9.52 | 28.88 |
July | 0.777300E+10 | 0.706566E+10 | 3232.54 | 01-JUL-00:10 | 2938.38 | 2938.38 | 6.86 | 28.88 |
August | 0.785038E+10 | 0.713599E+10 | 3232.54 | 01-AUG-00:10 | 2938.38 | 2938.38 | 6.86 | 28.88 |
September | 0.537756E+10 | 0.488820E+10 | 3232.54 | 01-SEP-00:15 | 2938.38 | 2938.38 | 6.88 | 28.88 |
October | 0.416768E+10 | 0.378842E+10 | 3232.54 | 01-OCT-06:50 | 2938.38 | 2938.38 | 6.91 | 28.88 |
November | 0.270501E+10 | 0.245885E+10 | 3232.54 | 01-NOV-08:70 | 2938.38 | 2938.38 | 6.79 | 28.88 |
December | 0.256145E+10 | 0.232836E+10 | 3232.54 | 01-DEC-06:03 | 2938.38 | 2938.38 | 6.86 | 28.88 |
Annual Sum or Average | 0.529687E+11 | 0.481485E+11 | ||||||
Minimum of Months | 0.201760E+10 | 0.183400E+10 | 3232.54 | 2938.38 | 2938.38 | 6.73 | 28.88 | |
Maximum of Months | 0.785038E+10 | 0.713599E+10 | 3232.54 | 2938.38 | 2938.38 | 9.52 | 28.88 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 7.30 | 0.00 |
February | 7758105.72 | 7052118.10 | 3232.54 | 14-FEB-15:30 | 2938.38 | 2938.38 | 15.47 | 14.44 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.98 | 0.00 |
April | 0.288020E+09 | 0.261810E+09 | 3232.54 | 11-APR-13:00 | 2938.38 | 2938.38 | 15.58 | 14.44 |
May | 0.633255E+09 | 0.575629E+09 | 3232.54 | 08-MAY-12:05 | 2938.38 | 2938.38 | 11.17 | 28.88 |
June | 0.190365E+10 | 0.173041E+10 | 3232.54 | 02-JUN-15:00 | 2938.38 | 2938.38 | 13.30 | 14.44 |
July | 0.234382E+10 | 0.213053E+10 | 3232.54 | 01-JUL-10:30 | 2938.38 | 2938.38 | 15.30 | 14.44 |
August | 0.216332E+10 | 0.196645E+10 | 3232.54 | 01-AUG-08:20 | 2938.38 | 2938.38 | 15.38 | 14.44 |
September | 0.119113E+10 | 0.108274E+10 | 3232.54 | 01-SEP-10:25 | 2938.38 | 2938.38 | 15.26 | 14.44 |
October | 0.411503E+09 | 0.374056E+09 | 3232.54 | 02-OCT-11:00 | 2938.38 | 2938.38 | 15.42 | 14.44 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 7.04 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.97 | 0.00 |
Annual Sum or Average | 0.894245E+10 | 0.812868E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 | 0.00 | |
Maximum of Months | 0.234382E+10 | 0.213053E+10 | 3232.54 | 2938.38 | 2938.38 | 15.58 | 28.88 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.109969E+11 | 0.999615E+10 | 4105.76 | 01-JAN-00:10 | 3732.13 | 3732.13 | 18.80 | 17.32 |
February | 0.993265E+10 | 0.902878E+10 | 4105.76 | 01-FEB-00:10 | 3732.13 | 3732.13 | 19.22 | 17.32 |
March | 0.109969E+11 | 0.999615E+10 | 4105.76 | 01-MAR-00:10 | 3732.13 | 3732.13 | 19.75 | 17.32 |
April | 0.106421E+11 | 0.967369E+10 | 4105.76 | 01-APR-00:10 | 3732.13 | 3732.13 | 20.31 | 17.32 |
May | 0.109969E+11 | 0.999615E+10 | 4105.76 | 01-MAY-00:05 | 3732.13 | 3732.13 | 19.08 | 17.32 |
June | 0.106421E+11 | 0.967369E+10 | 4105.76 | 01-JUN-00:10 | 3732.13 | 3732.13 | 20.00 | 17.32 |
July | 0.109969E+11 | 0.999615E+10 | 4105.76 | 01-JUL-00:10 | 3732.13 | 3732.13 | 30.99 | 17.32 |
August | 0.109969E+11 | 0.999615E+10 | 4105.76 | 01-AUG-00:10 | 3732.13 | 3732.13 | 36.63 | 17.32 |
September | 0.106421E+11 | 0.967369E+10 | 4105.76 | 01-SEP-00:03 | 3732.13 | 3732.13 | 22.86 | 17.32 |
October | 0.109969E+11 | 0.999615E+10 | 4105.76 | 01-OCT-00:10 | 3732.13 | 3732.13 | 19.42 | 17.32 |
November | 0.106421E+11 | 0.967369E+10 | 4105.76 | 01-NOV-00:10 | 3732.13 | 3732.13 | 19.88 | 17.32 |
December | 0.109969E+11 | 0.999615E+10 | 4105.76 | 01-DEC-00:10 | 3732.13 | 3732.13 | 20.20 | 17.32 |
Annual Sum or Average | 0.129479E+12 | 0.117697E+12 | ||||||
Minimum of Months | 0.993265E+10 | 0.902878E+10 | 4105.76 | 3732.13 | 3732.13 | 18.80 | 17.32 | |
Maximum of Months | 0.109969E+11 | 0.999615E+10 | 4105.76 | 3732.13 | 3732.13 | 36.63 | 17.32 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:10 | 16.86 | 16.86 | 56.84 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 57.14 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 57.00 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 57.13 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 57.47 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.51 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 57.71 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 57.83 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 57.76 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.38 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 57.46 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 57.21 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.84 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.83 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.798634E+10 | 0.725958E+10 | 12816.49 | 05-JAN-15:40 | 11650.19 | 11650.19 | 23.83 | 52.38 |
February | 0.915897E+10 | 0.832550E+10 | 25638.95 | 14-FEB-16:10 | 23305.81 | 23305.81 | 24.14 | 104.75 |
March | 0.126121E+11 | 0.114644E+11 | 12840.38 | 13-MAR-14:50 | 11671.91 | 11671.91 | 26.21 | 52.38 |
April | 0.167771E+11 | 0.152504E+11 | 25669.93 | 26-APR-13:05 | 23333.96 | 23333.96 | 25.71 | 104.75 |
May | 0.205975E+11 | 0.187231E+11 | 25676.00 | 15-MAY-15:20 | 23339.49 | 23339.49 | 25.99 | 104.75 |
June | 0.321875E+11 | 0.292584E+11 | 25675.97 | 19-JUN-14:50 | 23339.46 | 23339.46 | 25.99 | 104.75 |
July | 0.398109E+11 | 0.361881E+11 | 25716.85 | 31-JUL-15:00 | 23376.61 | 23376.61 | 27.88 | 104.75 |
August | 0.394623E+11 | 0.358713E+11 | 25706.55 | 24-AUG-12:13 | 23367.25 | 23367.25 | 27.41 | 104.75 |
September | 0.257767E+11 | 0.234311E+11 | 25722.57 | 05-SEP-13:00 | 23381.82 | 23381.82 | 28.15 | 104.75 |
October | 0.180799E+11 | 0.164346E+11 | 25686.97 | 11-OCT-12:32 | 23349.46 | 23349.46 | 26.50 | 104.75 |
November | 0.107102E+11 | 0.973557E+10 | 12829.20 | 02-NOV-15:20 | 11661.74 | 11661.74 | 25.17 | 52.38 |
December | 0.101355E+11 | 0.921321E+10 | 12811.00 | 29-DEC-16:00 | 11645.20 | 11645.20 | 23.23 | 52.38 |
Annual Sum or Average | 0.243295E+12 | 0.221155E+12 | ||||||
Minimum of Months | 0.798634E+10 | 0.725958E+10 | 12811.00 | 11645.20 | 11645.20 | 23.23 | 52.38 | |
Maximum of Months | 0.398109E+11 | 0.361881E+11 | 25722.57 | 23381.82 | 23381.82 | 28.15 | 104.75 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3.58 | 51898.83 | 02-JAN-05:01 | 50.65 | 50.65 | 67803.71 | 1097705.52 | 19-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 41.93 | 41.93 | 46612.25 | 1095565.02 | 01-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 35.90 | 35.90 | 13844.39 | 872276.31 | 04-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 34.35 | 34.35 | 2473.17 | 222795.34 | 08-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 32.13 | 32.13 | 432.42 | 100012.96 | 06-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 31.57 | 31.57 | 1.24 | 2632.06 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.53 | 31.53 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 31.53 | 31.53 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.53 | 31.53 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 31.53 | 31.53 | 8027.63 | 930264.12 | 26-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 35.15 | 35.15 | 19437.97 | 1037704.83 | 28-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 33.18 | 33.18 | 66345.84 | 1174981.59 | 04-DEC-05:01 |
Annual Sum or Average | 0.30 | 18664.63 | ||||||
Minimum of Months | 0.00 | 0.00 | 31.53 | 31.53 | 0.00 | 0.00 | ||
Maximum of Months | 3.58 | 51898.83 | 50.65 | 50.65 | 67803.71 | 1174981.59 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 28291.84 | 523661.04 | 05-JAN-15:40 | 11.03 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46276.23 | 1115213.88 | 14-FEB-16:10 | 11.31 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 73852.87 | 962837.23 | 13-MAR-14:50 | 14.67 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 148874.48 | 1423588.85 | 14-APR-14:05 | 12.59 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 237334.46 | 1501133.76 | 19-MAY-12:05 | 12.91 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 457476.08 | 1881997.69 | 30-JUN-08:20 | 14.48 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 539527.64 | 1996744.82 | 06-JUL-08:21 | 14.96 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 517845.40 | 1919653.69 | 03-AUG-09:02 | 14.64 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 350170.18 | 2007562.48 | 01-SEP-12:10 | 15.01 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 178370.33 | 1962914.60 | 10-OCT-12:07 | 14.82 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 58941.42 | 775169.46 | 02-NOV-15:10 | 13.11 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 13473.18 | 408698.57 | 29-DEC-15:50 | 10.08 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 221942.92 | 0.00 | ||||||
Minimum of Months | 13473.18 | 408698.57 | 10.08 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 539527.64 | 2007562.48 | 15.01 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27624.16 | 521941.78 | 05-JAN-15:40 | 16.46 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 45436.15 | 1104770.97 | 14-FEB-16:00 | 16.00 | 9.34 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 72853.64 | 963235.41 | 13-MAR-14:50 | 16.25 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 147428.40 | 1423256.89 | 13-APR-13:40 | 16.36 | 10.94 | 0.00 | 0.00 | 01-APR-00:10 |
May | 236989.79 | 1440015.03 | 23-MAY-12:30 | 13.24 | 9.97 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 459167.16 | 2357776.16 | 06-JUN-12:50 | 16.66 | 11.56 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 545702.59 | 2158198.85 | 16-JUL-14:41 | 16.99 | 11.05 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 528552.55 | 2295031.95 | 31-AUG-09:40 | 16.26 | 11.43 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 367110.30 | 2222874.77 | 18-SEP-13:40 | 15.90 | 11.62 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 184738.97 | 2253247.37 | 10-OCT-11:40 | 16.02 | 11.35 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 58067.50 | 773880.94 | 02-NOV-15:10 | 15.93 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 12606.96 | 407191.29 | 29-DEC-15:50 | 16.10 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 224949.43 | 0.00 | ||||||
Minimum of Months | 12606.96 | 407191.29 | 13.24 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 545702.59 | 2357776.16 | 16.99 | 11.62 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27714.79 | 49938.08 | 26-JAN-17:00 | 19.16 | 18.33 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 62828.40 | 493082.28 | 14-FEB-16:00 | 26.49 | 23.31 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 111607.02 | 763280.16 | 08-MAR-16:00 | 30.90 | 24.91 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 335641.39 | 1372528.19 | 13-APR-17:00 | 40.73 | 29.96 | 0.00 | 0.00 | 01-APR-00:10 |
May | 219223.59 | 1052464.07 | 19-MAY-16:00 | 35.59 | 31.46 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 663708.09 | 1855013.97 | 28-JUN-16:00 | 48.39 | 41.42 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1117193.19 | 2027431.09 | 22-JUL-15:00 | 51.10 | 41.72 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1221866.57 | 2039182.28 | 01-AUG-16:00 | 51.28 | 39.35 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 305739.90 | 1222036.07 | 03-SEP-14:00 | 38.32 | 34.25 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 170878.35 | 1200430.55 | 01-OCT-16:00 | 37.98 | 31.28 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 89675.26 | 366768.61 | 09-NOV-14:00 | 24.41 | 20.69 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 110578.27 | 168036.76 | 29-DEC-07:15 | 21.12 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 372474.11 | 0.00 | ||||||
Minimum of Months | 27714.79 | 49938.08 | 19.16 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1221866.57 | 2039182.28 | 51.28 | 41.72 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.14 | 58.14 | 14391.25 | 51437.51 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.60 | 57.60 | 14589.14 | 51477.10 | 06-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.62 | 57.62 | 15126.23 | 50996.50 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.72 | 57.72 | 13430.64 | 48739.33 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.30 | 58.30 | 12931.27 | 45864.57 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.02 | 58.02 | 12313.76 | 42483.15 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.15 | 58.15 | 10763.15 | 39736.83 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.21 | 58.21 | 11667.08 | 39032.74 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 58.19 | 58.19 | 11301.58 | 40954.89 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.10 | 58.10 | 12031.42 | 44195.21 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.95 | 57.95 | 13136.21 | 47469.94 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.79 | 57.79 | 13486.23 | 50033.79 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 12921.25 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.60 | 57.60 | 10763.15 | 39032.74 | ||
Maximum of Months | 0.00 | 0.00 | 58.30 | 58.30 | 15126.23 | 51477.10 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 26157.91 | 596778.89 | 05-JAN-15:40 | 23.83 | 21.10 | 3358.73 | 120916.87 | 10-JAN-11:40 |
February | 45506.32 | 1331342.47 | 14-FEB-16:10 | 24.14 | 22.60 | 4769.01 | 129533.08 | 28-FEB-06:40 |
March | 77427.00 | 1118997.39 | 13-MAR-14:50 | 26.21 | 21.10 | 3814.68 | 116559.83 | 22-MAR-08:50 |
April | 177161.03 | 2016164.39 | 26-APR-13:05 | 25.71 | 21.10 | 3592.02 | 109498.73 | 03-APR-09:50 |
May | 289495.01 | 2139864.74 | 15-MAY-15:20 | 25.99 | 21.10 | 1548.08 | 101162.56 | 05-MAY-09:20 |
June | 600946.22 | 2139220.88 | 19-JUN-14:50 | 25.99 | 21.10 | 1529.56 | 92774.70 | 09-JUN-06:00 |
July | 730591.79 | 2969682.68 | 31-JUL-15:00 | 27.88 | 23.70 | 1069.62 | 45989.65 | 22-JUL-03:40 |
August | 683170.79 | 2760688.38 | 24-AUG-12:13 | 27.41 | 22.25 | 1695.59 | 54196.37 | 31-AUG-01:20 |
September | 464474.57 | 3085805.40 | 05-SEP-13:00 | 28.15 | 23.43 | 534.56 | 57076.01 | 11-SEP-05:40 |
October | 221646.62 | 2362994.22 | 11-OCT-12:32 | 26.50 | 21.42 | 2072.89 | 123936.05 | 30-OCT-06:43 |
November | 61212.61 | 891782.03 | 02-NOV-15:20 | 25.17 | 21.10 | 3343.72 | 120954.74 | 25-NOV-09:10 |
December | 5795.63 | 466345.33 | 29-DEC-16:00 | 23.23 | 21.10 | 8485.79 | 131808.04 | 14-DEC-05:01 |
Annual Sum or Average | 283426.95 | 2977.90 | ||||||
Minimum of Months | 5795.63 | 466345.33 | 23.23 | 21.10 | 534.56 | 45989.65 | ||
Maximum of Months | 730591.79 | 3085805.40 | 28.15 | 23.70 | 8485.79 | 131808.04 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.871297E+10 | 0.00 | 0.138862E+11 | 0.480776E+10 | 0.00 | 0.00 |
February | 0.495891E+10 | 0.00 | 0.136920E+11 | 0.520149E+10 | 0.00 | 0.00 |
March | 0.137884E+10 | 0.00 | 0.156565E+11 | 0.833702E+10 | 0.00 | 0.00 |
April | 94160827.42 | 0.00 | 0.369160E+11 | 0.115819E+11 | 0.00 | 0.00 |
May | 32992211.99 | 0.00 | 0.571789E+11 | 0.109834E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.124065E+12 | 0.182431E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.172752E+12 | 0.234267E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.159139E+12 | 0.222412E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.825700E+11 | 0.109056E+11 | 0.00 | 0.00 |
October | 0.819607E+09 | 0.00 | 0.431692E+11 | 0.915815E+10 | 0.00 | 0.00 |
November | 0.165809E+10 | 0.00 | 0.129330E+11 | 0.707140E+10 | 0.00 | 0.00 |
December | 0.626436E+10 | 0.00 | 0.174817E+11 | 0.607074E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.239199E+11 | 0.00 | 0.749440E+12 | 0.138029E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.129330E+11 | 0.480776E+10 | 0.00 | 0.00 |
Maximum of Months | 0.871297E+10 | 0.00 | 0.172752E+12 | 0.234267E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.145369E+12 | 0.00 | 0.550471E+11 | 0.317559E+11 | 0.00 | 0.00 |
February | 0.910057E+11 | 0.00 | 0.851283E+11 | 0.321592E+11 | 0.00 | 0.00 |
March | 0.295470E+11 | 0.00 | 0.157491E+12 | 0.469438E+11 | 0.00 | 0.00 |
April | 0.505351E+10 | 0.00 | 0.284171E+12 | 0.662156E+11 | 0.00 | 0.00 |
May | 0.898775E+09 | 0.00 | 0.474317E+12 | 0.798886E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.905619E+12 | 0.104851E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.109072E+13 | 0.115987E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.104310E+13 | 0.113679E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.687725E+12 | 0.773244E+11 | 0.00 | 0.00 |
October | 0.171994E+11 | 0.00 | 0.360184E+12 | 0.571058E+11 | 0.00 | 0.00 |
November | 0.396231E+11 | 0.00 | 0.127798E+12 | 0.386930E+11 | 0.00 | 0.00 |
December | 0.143964E+12 | 0.00 | 0.145850E+11 | 0.315213E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.472660E+12 | 0.00 | 0.528588E+13 | 0.796124E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.145850E+11 | 0.315213E+11 | 0.00 | 0.00 |
Maximum of Months | 0.145369E+12 | 0.00 | 0.109072E+13 | 0.115987E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.271429E+11 | 0.00 | 0.371390E+10 | 0.311432E+10 | 0.00 | 0.00 |
February | 0.167005E+11 | 0.00 | 0.580385E+10 | 0.293897E+10 | 0.00 | 0.00 |
March | 0.614976E+10 | 0.00 | 0.854119E+10 | 0.388994E+10 | 0.00 | 0.00 |
April | 0.128838E+10 | 0.00 | 0.289208E+11 | 0.596514E+10 | 0.00 | 0.00 |
May | 0.232586E+09 | 0.00 | 0.523440E+11 | 0.772698E+10 | 0.00 | 0.00 |
June | 3600300.72 | 0.00 | 0.103094E+12 | 0.112057E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.125157E+12 | 0.127417E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.118052E+12 | 0.121388E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.747200E+11 | 0.768337E+10 | 0.00 | 0.00 |
October | 0.347179E+10 | 0.00 | 0.336305E+11 | 0.491106E+10 | 0.00 | 0.00 |
November | 0.918261E+10 | 0.00 | 0.813049E+10 | 0.316382E+10 | 0.00 | 0.00 |
December | 0.276084E+11 | 0.00 | 0.177269E+10 | 0.308186E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.917805E+11 | 0.00 | 0.563880E+12 | 0.785617E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.177269E+10 | 0.293897E+10 | 0.00 | 0.00 |
Maximum of Months | 0.276084E+11 | 0.00 | 0.125157E+12 | 0.127417E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.746507E+09 | 0.00 | 0.153803E+10 | 0.559408E+10 | 0.00 | 0.00 |
February | 0.312673E+09 | 0.00 | 0.230971E+10 | 0.501890E+10 | 0.00 | 0.00 |
March | 67920635.40 | 0.00 | 0.801790E+10 | 0.670510E+10 | 0.00 | 0.00 |
April | 3154545.04 | 0.00 | 0.204858E+11 | 0.125216E+11 | 0.00 | 0.00 |
May | 421713.31 | 0.00 | 0.274510E+11 | 0.114003E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.222848E+11 | 0.635285E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.159998E+11 | 0.247019E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.404123E+11 | 0.789684E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.470443E+11 | 0.121066E+11 | 0.00 | 0.00 |
October | 5498310.77 | 0.00 | 0.225356E+11 | 0.131469E+11 | 0.00 | 0.00 |
November | 4389922.95 | 0.00 | 0.152230E+10 | 0.124018E+11 | 0.00 | 0.00 |
December | 0.111788E+09 | 0.00 | 0.00 | 0.916693E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.125235E+10 | 0.00 | 0.209602E+12 | 0.104782E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.247019E+10 | 0.00 | 0.00 |
Maximum of Months | 0.746507E+09 | 0.00 | 0.470443E+11 | 0.131469E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.177970E+11 | 0.349468E+12 | 0.00 | 79.09 |
February | 0.00 | 0.00 | 0.216670E+11 | 0.363011E+12 | 0.00 | 88.54 |
March | 0.00 | 0.00 | 0.501347E+11 | 0.411371E+12 | 0.00 | 99.17 |
April | 0.00 | 0.00 | 0.312818E+12 | 0.462557E+12 | 0.00 | 96.32 |
May | 0.00 | 0.00 | 0.930961E+11 | 0.345004E+12 | 0.00 | 70.24 |
June | 0.00 | 0.00 | 0.432669E+12 | 0.347871E+12 | 0.00 | 41.14 |
July | 0.00 | 0.00 | 0.104826E+13 | 0.409561E+12 | 0.00 | 11.76 |
August | 0.00 | 0.00 | 0.136139E+13 | 0.485705E+12 | 0.00 | 17.58 |
September | 0.00 | 0.00 | 0.132225E+12 | 0.225867E+12 | 0.00 | 23.99 |
October | 0.00 | 0.00 | 0.997957E+11 | 0.372037E+12 | 0.00 | 80.22 |
November | 0.00 | 0.00 | 0.230401E+11 | 0.391080E+12 | 0.00 | 95.62 |
December | 0.00 | 0.00 | 0.226821E+11 | 0.406367E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.361557E+13 | 0.456990E+13 | 0.00 | 803.29 |
Minimum of Months | 0.00 | 0.00 | 0.177970E+11 | 0.225867E+12 | 0.00 | 11.76 |
Maximum of Months | 0.00 | 0.00 | 0.136139E+13 | 0.485705E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.601570E+10 | 0.295652E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.114575E+11 | 0.377676E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.193299E+11 | 0.533102E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.252352E+11 | 0.644672E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.776979E+10 | 0.338530E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.145564E+11 | 0.494424E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.221590E+11 | 0.683277E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.280999E+11 | 0.792520E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.793832E+10 | 0.336962E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.137870E+11 | 0.442612E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.186332E+11 | 0.511768E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.249955E+11 | 0.630190E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.199978E+12 | 0.608138E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.601570E+10 | 0.295652E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.280999E+11 | 0.792520E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.387088E+11 | 0.246842E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.953200E+11 | 0.335917E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.174761E+12 | 0.493275E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.236441E+12 | 0.609118E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.698563E+11 | 0.315547E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.135638E+12 | 0.466134E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.207841E+12 | 0.645500E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.266060E+12 | 0.753509E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.717352E+11 | 0.314520E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.123960E+12 | 0.409700E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.165071E+12 | 0.467836E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.218530E+12 | 0.569701E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180392E+13 | 0.562760E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.387088E+11 | 0.246842E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.266060E+12 | 0.753509E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.168272E+10 | 0.205871E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.778916E+10 | 0.307149E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.163612E+11 | 0.478292E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.231940E+11 | 0.606412E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.680875E+10 | 0.316286E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.136407E+11 | 0.472453E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.209929E+11 | 0.654919E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.267568E+11 | 0.761896E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.709602E+10 | 0.317178E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.116288E+11 | 0.399956E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.148303E+11 | 0.443038E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.194529E+11 | 0.533816E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.170234E+12 | 0.549727E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.168272E+10 | 0.205871E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.267568E+11 | 0.761896E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.480776E+10 | 0.138862E+11 | 0.871297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.520149E+10 | 0.136920E+11 | 0.495891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.833702E+10 | 0.156565E+11 | 0.137884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115819E+11 | 0.369160E+11 | 94160827.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109834E+11 | 0.571789E+11 | 32992211.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182431E+11 | 0.124065E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.234267E+11 | 0.172752E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.222412E+11 | 0.159139E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109056E+11 | 0.825700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.915815E+10 | 0.431692E+11 | 0.819607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.707140E+10 | 0.129330E+11 | 0.165809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.607074E+10 | 0.174817E+11 | 0.626436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138029E+12 | 0.749440E+12 | 0.239199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.480776E+10 | 0.129330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.234267E+11 | 0.172752E+12 | 0.871297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.317559E+11 | 0.550471E+11 | 0.145369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.321592E+11 | 0.851283E+11 | 0.910057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.469438E+11 | 0.157491E+12 | 0.295470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662156E+11 | 0.284171E+12 | 0.505351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.798886E+11 | 0.474317E+12 | 0.898775E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104851E+12 | 0.905619E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115987E+12 | 0.109072E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113679E+12 | 0.104310E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.773244E+11 | 0.687725E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.571058E+11 | 0.360184E+12 | 0.171994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.386930E+11 | 0.127798E+12 | 0.396231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315213E+11 | 0.145850E+11 | 0.143964E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.796124E+12 | 0.528588E+13 | 0.472660E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.315213E+11 | 0.145850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115987E+12 | 0.109072E+13 | 0.145369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.311432E+10 | 0.371390E+10 | 0.271429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293897E+10 | 0.580385E+10 | 0.167005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388994E+10 | 0.854119E+10 | 0.614976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.596514E+10 | 0.289208E+11 | 0.128838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.772698E+10 | 0.523440E+11 | 0.232586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112057E+11 | 0.103094E+12 | 3600300.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127417E+11 | 0.125157E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121388E+11 | 0.118052E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.768337E+10 | 0.747200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.491106E+10 | 0.336305E+11 | 0.347179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316382E+10 | 0.813049E+10 | 0.918261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.308186E+10 | 0.177269E+10 | 0.276084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.785617E+11 | 0.563880E+12 | 0.917805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.293897E+10 | 0.177269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127417E+11 | 0.125157E+12 | 0.276084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.559408E+10 | 0.153803E+10 | 0.746507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.501890E+10 | 0.230971E+10 | 0.312673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.670510E+10 | 0.801790E+10 | 67920635.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125216E+11 | 0.204858E+11 | 3154545.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114003E+11 | 0.274510E+11 | 421713.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.635285E+10 | 0.222848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.247019E+10 | 0.159998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.789684E+10 | 0.404123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121066E+11 | 0.470443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131469E+11 | 0.225356E+11 | 5498310.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124018E+11 | 0.152230E+10 | 4389922.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.916693E+10 | 0.00 | 0.111788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104782E+12 | 0.209602E+12 | 0.125235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.247019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131469E+11 | 0.470443E+11 | 0.746507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.130933E+12 | 0.118753E+11 | 0.00 | 0.00 | 0.00 | 0.211660E+12 | 0.00 | 0.00 |
February | 0.118262E+12 | 0.149217E+11 | 0.00 | 0.00 | 0.00 | 0.236937E+12 | 0.00 | 0.00 |
March | 0.130933E+12 | 0.362737E+11 | 0.00 | 0.00 | 0.00 | 0.265382E+12 | 0.00 | 0.00 |
April | 0.126710E+12 | 0.235883E+12 | 0.00 | 0.00 | 0.00 | 0.257752E+12 | 0.00 | 0.00 |
May | 0.130933E+12 | 0.678380E+11 | 0.00 | 0.00 | 0.00 | 0.187966E+12 | 0.00 | 0.00 |
June | 0.126710E+12 | 0.322089E+12 | 0.00 | 0.00 | 0.00 | 0.110086E+12 | 0.00 | 0.00 |
July | 0.130933E+12 | 0.801244E+12 | 0.00 | 0.00 | 0.00 | 0.314725E+11 | 0.00 | 0.00 |
August | 0.130933E+12 | 0.105388E+13 | 0.00 | 0.00 | 0.00 | 0.470444E+11 | 0.00 | 0.00 |
September | 0.126710E+12 | 0.975463E+11 | 0.00 | 0.00 | 0.00 | 0.641895E+11 | 0.00 | 0.00 |
October | 0.130933E+12 | 0.743368E+11 | 0.00 | 0.00 | 0.00 | 0.214678E+12 | 0.00 | 0.00 |
November | 0.126710E+12 | 0.157066E+11 | 0.00 | 0.00 | 0.00 | 0.255885E+12 | 0.00 | 0.00 |
December | 0.130933E+12 | 0.150883E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.154163E+13 | 0.274668E+13 | 0.00 | 0.00 | 0.00 | 0.214969E+13 | 0.00 | 0.00 |
Minimum of Months | 0.118262E+12 | 0.118753E+11 | 0.00 | 0.00 | 0.00 | 0.314725E+11 | 0.00 | 0.00 |
Maximum of Months | 0.130933E+12 | 0.105388E+13 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.173402E+10 | 0.479320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156621E+10 | 0.924696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173402E+10 | 0.157329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167808E+10 | 0.204666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173402E+10 | 0.611851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167808E+10 | 0.112902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173402E+10 | 0.170603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173402E+10 | 0.219087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167808E+10 | 0.624678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173402E+10 | 0.110949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167808E+10 | 0.151936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173402E+10 | 0.204277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204167E+11 | 0.159580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156621E+10 | 0.479320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173402E+10 | 0.219087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166144E+11 | 0.306390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150066E+11 | 0.767349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166144E+11 | 0.142047E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160784E+11 | 0.191608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166144E+11 | 0.549160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160784E+11 | 0.105103E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166144E+11 | 0.159905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166144E+11 | 0.207324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160784E+11 | 0.563616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166144E+11 | 0.996049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160784E+11 | 0.134366E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166144E+11 | 0.178174E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195621E+12 | 0.143678E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150066E+11 | 0.306390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166144E+11 | 0.207324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169692E+10 | 0.132094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153270E+10 | 0.625037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169692E+10 | 0.132752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164218E+10 | 0.187721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169692E+10 | 0.534281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164218E+10 | 0.105583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169692E+10 | 0.161406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169692E+10 | 0.208347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164218E+10 | 0.556642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169692E+10 | 0.932611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164218E+10 | 0.120421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169692E+10 | 0.158117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199798E+11 | 0.135242E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153270E+10 | 0.132094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169692E+10 | 0.208347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.480776E+10 | 0.871297E+10 | 0.138862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.520149E+10 | 0.495891E+10 | 0.136920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.833702E+10 | 0.137884E+10 | 0.156565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115819E+11 | 94160827.42 | 0.369160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109834E+11 | 32992211.99 | 0.571789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182431E+11 | 0.00 | 0.124065E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.234267E+11 | 0.00 | 0.172752E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.222412E+11 | 0.00 | 0.159139E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109056E+11 | 0.00 | 0.825700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.915815E+10 | 0.819607E+09 | 0.431692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.707140E+10 | 0.165809E+10 | 0.129330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.607074E+10 | 0.626436E+10 | 0.174817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138029E+12 | 0.239199E+11 | 0.749440E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.480776E+10 | 0.00 | 0.129330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.234267E+11 | 0.871297E+10 | 0.172752E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.317559E+11 | 0.145369E+12 | 0.550471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.321592E+11 | 0.910057E+11 | 0.851283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.469438E+11 | 0.295470E+11 | 0.157491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662156E+11 | 0.505351E+10 | 0.284171E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.798886E+11 | 0.898775E+09 | 0.474317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104851E+12 | 0.00 | 0.905619E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115987E+12 | 0.00 | 0.109072E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113679E+12 | 0.00 | 0.104310E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.773244E+11 | 0.00 | 0.687725E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.571058E+11 | 0.171994E+11 | 0.360184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.386930E+11 | 0.396231E+11 | 0.127798E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315213E+11 | 0.143964E+12 | 0.145850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.796124E+12 | 0.472660E+12 | 0.528588E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.315213E+11 | 0.00 | 0.145850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115987E+12 | 0.145369E+12 | 0.109072E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.311432E+10 | 0.271429E+11 | 0.371390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293897E+10 | 0.167005E+11 | 0.580385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388994E+10 | 0.614976E+10 | 0.854119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.596514E+10 | 0.128838E+10 | 0.289208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.772698E+10 | 0.232586E+09 | 0.523440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112057E+11 | 3600300.72 | 0.103094E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127417E+11 | 0.00 | 0.125157E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121388E+11 | 0.00 | 0.118052E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.768337E+10 | 0.00 | 0.747200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.491106E+10 | 0.347179E+10 | 0.336305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316382E+10 | 0.918261E+10 | 0.813049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.308186E+10 | 0.276084E+11 | 0.177269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.785617E+11 | 0.917805E+11 | 0.563880E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.293897E+10 | 0.00 | 0.177269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127417E+11 | 0.276084E+11 | 0.125157E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.559408E+10 | 0.746507E+09 | 0.153803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.501890E+10 | 0.312673E+09 | 0.230971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.670510E+10 | 67920635.40 | 0.801790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125216E+11 | 3154545.04 | 0.204858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114003E+11 | 421713.31 | 0.274510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.635285E+10 | 0.00 | 0.222848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.247019E+10 | 0.00 | 0.159998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.789684E+10 | 0.00 | 0.404123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121066E+11 | 0.00 | 0.470443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131469E+11 | 5498310.77 | 0.225356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124018E+11 | 4389922.95 | 0.152230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.916693E+10 | 0.111788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104782E+12 | 0.125235E+10 | 0.209602E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.247019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131469E+11 | 0.746507E+09 | 0.470443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.130933E+12 | 0.00 | 0.177970E+11 | 0.00 | 0.592176E+10 | 0.00 | 0.00 | 0.00 | 0.212613E+12 | 0.00 | 0.00 | 0.00 |
February | 0.118262E+12 | 0.00 | 0.216670E+11 | 0.00 | 0.674527E+10 | 0.00 | 0.00 | 0.00 | 0.238003E+12 | 0.00 | 0.00 | 0.00 |
March | 0.130933E+12 | 0.00 | 0.501347E+11 | 0.00 | 0.138610E+11 | 0.00 | 0.00 | 0.00 | 0.266576E+12 | 0.00 | 0.00 | 0.00 |
April | 0.126710E+12 | 0.00 | 0.312818E+12 | 0.00 | 0.769356E+11 | 0.00 | 0.00 | 0.00 | 0.258912E+12 | 0.00 | 0.00 | 0.00 |
May | 0.130933E+12 | 0.00 | 0.930961E+11 | 0.00 | 0.252581E+11 | 0.00 | 0.00 | 0.00 | 0.188812E+12 | 0.00 | 0.00 | 0.00 |
June | 0.126710E+12 | 0.00 | 0.432669E+12 | 0.00 | 0.110579E+12 | 0.00 | 0.00 | 0.00 | 0.110582E+12 | 0.00 | 0.00 | 0.00 |
July | 0.130933E+12 | 0.00 | 0.104826E+13 | 0.00 | 0.247014E+12 | 0.00 | 0.00 | 0.00 | 0.316142E+11 | 0.00 | 0.00 | 0.00 |
August | 0.130933E+12 | 0.00 | 0.136139E+13 | 0.00 | 0.307516E+12 | 0.00 | 0.00 | 0.00 | 0.472561E+11 | 0.00 | 0.00 | 0.00 |
September | 0.126710E+12 | 0.00 | 0.132225E+12 | 0.00 | 0.346792E+11 | 0.00 | 0.00 | 0.00 | 0.644784E+11 | 0.00 | 0.00 | 0.00 |
October | 0.130933E+12 | 0.00 | 0.997957E+11 | 0.00 | 0.254589E+11 | 0.00 | 0.00 | 0.00 | 0.215645E+12 | 0.00 | 0.00 | 0.00 |
November | 0.126710E+12 | 0.00 | 0.230401E+11 | 0.00 | 0.733346E+10 | 0.00 | 0.00 | 0.00 | 0.257037E+12 | 0.00 | 0.00 | 0.00 |
December | 0.130933E+12 | 0.00 | 0.226821E+11 | 0.00 | 0.759385E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154163E+13 | 0.00 | 0.361557E+13 | 0.00 | 0.868896E+12 | 0.00 | 0.00 | 0.00 | 0.215937E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118262E+12 | 0.00 | 0.177970E+11 | 0.00 | 0.592176E+10 | 0.00 | 0.00 | 0.00 | 0.316142E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130933E+12 | 0.00 | 0.136139E+13 | 0.00 | 0.307516E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.173402E+10 | 0.00 | 0.601570E+10 | 0.00 | 0.122250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156621E+10 | 0.00 | 0.114575E+11 | 0.00 | 0.221055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173402E+10 | 0.00 | 0.193299E+11 | 0.00 | 0.359700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167808E+10 | 0.00 | 0.252352E+11 | 0.00 | 0.476864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173402E+10 | 0.00 | 0.776979E+10 | 0.00 | 0.165128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167808E+10 | 0.00 | 0.145564E+11 | 0.00 | 0.326616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173402E+10 | 0.00 | 0.221590E+11 | 0.00 | 0.509875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173402E+10 | 0.00 | 0.280999E+11 | 0.00 | 0.619118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167808E+10 | 0.00 | 0.793832E+10 | 0.00 | 0.169154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173402E+10 | 0.00 | 0.137870E+11 | 0.00 | 0.269211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167808E+10 | 0.00 | 0.186332E+11 | 0.00 | 0.343960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173402E+10 | 0.00 | 0.249955E+11 | 0.00 | 0.456788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204167E+11 | 0.00 | 0.199978E+12 | 0.00 | 0.403972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156621E+10 | 0.00 | 0.601570E+10 | 0.00 | 0.122250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173402E+10 | 0.00 | 0.280999E+11 | 0.00 | 0.619118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166144E+11 | 0.00 | 0.387088E+11 | 0.00 | 0.806979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150066E+11 | 0.00 | 0.953200E+11 | 0.00 | 0.185851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166144E+11 | 0.00 | 0.174761E+12 | 0.00 | 0.327131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160784E+11 | 0.00 | 0.236441E+12 | 0.00 | 0.448334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166144E+11 | 0.00 | 0.698563E+11 | 0.00 | 0.149403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160784E+11 | 0.00 | 0.135638E+12 | 0.00 | 0.305350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166144E+11 | 0.00 | 0.207841E+12 | 0.00 | 0.479356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166144E+11 | 0.00 | 0.266060E+12 | 0.00 | 0.587365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160784E+11 | 0.00 | 0.717352E+11 | 0.00 | 0.153736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166144E+11 | 0.00 | 0.123960E+12 | 0.00 | 0.243556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160784E+11 | 0.00 | 0.165071E+12 | 0.00 | 0.307052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166144E+11 | 0.00 | 0.218530E+12 | 0.00 | 0.403557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195621E+12 | 0.00 | 0.180392E+13 | 0.00 | 0.367139E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150066E+11 | 0.00 | 0.387088E+11 | 0.00 | 0.806979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166144E+11 | 0.00 | 0.266060E+12 | 0.00 | 0.587365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169692E+10 | 0.00 | 0.168272E+10 | 0.00 | 0.361790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153270E+10 | 0.00 | 0.778916E+10 | 0.00 | 0.153879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169692E+10 | 0.00 | 0.163612E+11 | 0.00 | 0.308601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164218E+10 | 0.00 | 0.231940E+11 | 0.00 | 0.442194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169692E+10 | 0.00 | 0.680875E+10 | 0.00 | 0.146594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164218E+10 | 0.00 | 0.136407E+11 | 0.00 | 0.308236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169692E+10 | 0.00 | 0.209929E+11 | 0.00 | 0.485227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169692E+10 | 0.00 | 0.267568E+11 | 0.00 | 0.592204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164218E+10 | 0.00 | 0.709602E+10 | 0.00 | 0.152960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169692E+10 | 0.00 | 0.116288E+11 | 0.00 | 0.230265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164218E+10 | 0.00 | 0.148303E+11 | 0.00 | 0.278820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169692E+10 | 0.00 | 0.194529E+11 | 0.00 | 0.364124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199798E+11 | 0.00 | 0.170234E+12 | 0.00 | 0.349928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153270E+10 | 0.00 | 0.168272E+10 | 0.00 | 0.361790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169692E+10 | 0.00 | 0.267568E+11 | 0.00 | 0.592204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.102722E+09 | 0.00 | 0.00 | 0.557123E+11 | 0.00 | 0.57 |
February | 0.00 | 0.00 | 0.00 | 89358998.75 | 0.00 | 0.00 | 0.482707E+11 | 0.00 | 0.61 |
March | 0.00 | 0.00 | 0.00 | 0.108599E+09 | 0.00 | 0.00 | 0.535332E+11 | 0.00 | 0.82 |
April | 0.00 | 11980447.14 | 0.00 | 97430797.75 | 0.00 | 0.00 | 0.448519E+11 | 0.00 | 1.10 |
May | 0.00 | 0.111130E+09 | 0.00 | 97583152.92 | 0.00 | 0.00 | 0.341663E+11 | 0.00 | 0.92 |
June | 0.00 | 0.173560E+09 | 0.00 | 66822839.21 | 0.00 | 0.00 | 0.143042E+11 | 0.00 | 0.48 |
July | 0.00 | 0.110376E+10 | 0.00 | 54207036.91 | 0.00 | 0.00 | 0.322487E+10 | 0.00 | 0.14 |
August | 0.00 | 0.873458E+09 | 0.00 | 0.123752E+09 | 0.00 | 0.00 | 0.100990E+11 | 0.00 | 0.44 |
September | 0.00 | 0.494976E+09 | 0.00 | 0.114090E+09 | 0.00 | 0.00 | 0.192225E+11 | 0.00 | 0.79 |
October | 0.00 | 0.00 | 0.00 | 0.143808E+09 | 0.00 | 0.00 | 0.491970E+11 | 0.00 | 1.05 |
November | 0.00 | 0.00 | 0.00 | 0.117586E+09 | 0.00 | 0.00 | 0.682502E+11 | 0.00 | 0.93 |
December | 0.00 | 0.00 | 0.00 | 0.113531E+09 | 0.00 | 0.00 | 0.633755E+11 | 0.00 | 0.59 |
Annual Sum or Average | 0.00 | 0.276887E+10 | 0.00 | 0.122949E+10 | 0.00 | 0.00 | 0.464208E+12 | 0.00 | 0.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 54207036.91 | 0.00 | 0.00 | 0.322487E+10 | 0.00 | 0.14 |
Maximum of Months | 0.00 | 0.110376E+10 | 0.00 | 0.143808E+09 | 0.00 | 0.00 | 0.682502E+11 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.306341E+10 | 0.00 | 0.00 | 79893729.41 | 0.00 | 0.00 | 0.421846E+11 | 0.00 | 0.41 |
February | 0.204095E+10 | 0.00 | 0.00 | 79776638.18 | 0.00 | 0.00 | 0.395747E+11 | 0.00 | 0.49 |
March | 0.271484E+10 | 0.00 | 0.00 | 0.104552E+09 | 0.00 | 0.00 | 0.524729E+11 | 0.00 | 0.81 |
April | 0.615667E+10 | 2045080.85 | 0.00 | 0.100777E+09 | 0.00 | 0.00 | 0.429651E+11 | 0.00 | 1.05 |
May | 0.182586E+10 | 48272401.68 | 0.00 | 97000348.74 | 19756611.25 | 0.00 | 0.332004E+11 | 0.00 | 0.93 |
June | 0.312667E+10 | 0.964866E+09 | 0.00 | 90134197.56 | 0.129475E+09 | 0.00 | 0.170270E+11 | 0.00 | 0.84 |
July | 0.370477E+10 | 0.229444E+10 | 0.00 | 77669734.54 | 0.301911E+09 | 0.00 | 0.780849E+10 | 0.00 | 0.85 |
August | 0.528477E+10 | 0.133821E+10 | 0.00 | 0.104482E+09 | 72831579.09 | 0.00 | 0.135132E+11 | 0.00 | 1.02 |
September | 0.179653E+10 | 0.329543E+09 | 0.00 | 99088580.97 | 16249859.75 | 0.00 | 0.221423E+11 | 0.00 | 0.86 |
October | 0.340554E+10 | 480591.63 | 0.00 | 0.110449E+09 | 869092.72 | 0.00 | 0.400181E+11 | 0.00 | 0.85 |
November | 0.332629E+10 | 0.00 | 0.00 | 0.101830E+09 | 0.00 | 0.00 | 0.495434E+11 | 0.00 | 0.67 |
December | 0.270430E+10 | 0.00 | 0.00 | 0.104354E+09 | 0.00 | 0.00 | 0.464122E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.391506E+11 | 0.497786E+10 | 0.00 | 0.115001E+10 | 0.541094E+09 | 0.00 | 0.406863E+12 | 0.00 | 0.77 |
Minimum of Months | 0.179653E+10 | 0.00 | 0.00 | 77669734.54 | 0.00 | 0.00 | 0.780849E+10 | 0.00 | 0.41 |
Maximum of Months | 0.615667E+10 | 0.229444E+10 | 0.00 | 0.110449E+09 | 0.301911E+09 | 0.00 | 0.524729E+11 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150100E+12 | 0.00 | 0.00 | 0.296337E+09 | 0.00 | 0.00 | 0.209064E+12 | 0.00 | 0.34 |
February | 0.101491E+12 | 0.00 | 0.00 | 0.329038E+09 | 0.00 | 0.00 | 0.205751E+12 | 0.00 | 0.35 |
March | 0.391459E+11 | 0.00 | 0.00 | 0.565867E+09 | 0.00 | 0.00 | 0.309577E+12 | 0.00 | 0.49 |
April | 0.268489E+11 | 18782289.26 | 0.00 | 0.639982E+09 | 0.00 | 0.00 | 0.280533E+12 | 0.00 | 0.68 |
May | 0.168476E+11 | 0.444693E+09 | 0.00 | 0.723445E+09 | 0.154899E+09 | 0.00 | 0.254070E+12 | 0.00 | 0.73 |
June | 0.115736E+11 | 0.110338E+11 | 0.00 | 0.553048E+09 | 0.497758E+09 | 0.00 | 0.111835E+12 | 0.00 | 0.57 |
July | 0.696225E+10 | 0.130803E+11 | 0.00 | 0.450236E+09 | 0.199004E+10 | 0.00 | 0.380636E+11 | 0.00 | 0.46 |
August | 0.776841E+10 | 0.736944E+10 | 0.00 | 0.688023E+09 | 0.849591E+09 | 0.00 | 0.890626E+11 | 0.00 | 0.58 |
September | 0.120863E+11 | 0.244274E+10 | 0.00 | 0.719989E+09 | 0.147777E+09 | 0.00 | 0.158808E+12 | 0.00 | 0.65 |
October | 0.335372E+11 | 0.00 | 0.00 | 0.693875E+09 | 16033930.23 | 0.00 | 0.259889E+12 | 0.00 | 0.58 |
November | 0.569561E+11 | 0.00 | 0.00 | 0.486440E+09 | 0.00 | 0.00 | 0.265009E+12 | 0.00 | 0.39 |
December | 0.152036E+12 | 0.00 | 0.00 | 0.294848E+09 | 0.00 | 0.00 | 0.219019E+12 | 0.00 | 0.33 |
Annual Sum or Average | 0.615354E+12 | 0.343897E+11 | 0.00 | 0.644113E+10 | 0.365610E+10 | 0.00 | 0.240068E+13 | 0.00 | 0.51 |
Minimum of Months | 0.696225E+10 | 0.00 | 0.00 | 0.294848E+09 | 0.00 | 0.00 | 0.380636E+11 | 0.00 | 0.33 |
Maximum of Months | 0.152036E+12 | 0.130803E+11 | 0.00 | 0.723445E+09 | 0.199004E+10 | 0.00 | 0.309577E+12 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.251050E+11 | 0.00 | 0.00 | 2903447.11 | 0.00 | 0.109494E+10 | 0.298933E+10 | 0.00 | 0.30 |
February | 0.188823E+11 | 0.00 | 0.00 | 7800996.79 | 0.00 | 0.375601E+09 | 0.601429E+10 | 0.00 | 0.30 |
March | 0.114318E+11 | 0.00 | 0.00 | 27440667.26 | 0.00 | 11069457.49 | 0.197313E+11 | 0.00 | 0.47 |
April | 0.525033E+10 | 0.00 | 0.00 | 47289699.05 | 7919.06 | 0.00 | 0.229110E+11 | 0.00 | 0.68 |
May | 0.323010E+10 | 19716432.11 | 0.00 | 63030789.39 | 32144052.80 | 0.00 | 0.222907E+11 | 0.00 | 0.74 |
June | 0.156560E+10 | 0.732261E+09 | 0.00 | 61445541.07 | 51753092.77 | 0.00 | 0.102010E+11 | 0.00 | 0.57 |
July | 0.868134E+09 | 0.834189E+09 | 0.00 | 59810732.55 | 0.192410E+09 | 0.00 | 0.374874E+10 | 0.00 | 0.48 |
August | 0.878966E+09 | 0.463528E+09 | 0.00 | 79852655.64 | 75980858.30 | 0.00 | 0.876755E+10 | 0.00 | 0.61 |
September | 0.151545E+10 | 0.152787E+09 | 0.00 | 68677209.51 | 7226275.36 | 0.00 | 0.137764E+11 | 0.00 | 0.65 |
October | 0.818664E+10 | 129906.35 | 0.00 | 44540660.16 | 0.00 | 779510.97 | 0.163732E+11 | 0.00 | 0.54 |
November | 0.154771E+11 | 0.00 | 0.00 | 15038314.74 | 0.00 | 0.185439E+09 | 0.102877E+11 | 0.00 | 0.33 |
December | 0.258714E+11 | 0.00 | 0.00 | 1987388.32 | 0.00 | 0.112451E+10 | 0.241604E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.118263E+12 | 0.220261E+10 | 0.00 | 0.479818E+09 | 0.359522E+09 | 0.279234E+10 | 0.139507E+12 | 0.00 | 0.50 |
Minimum of Months | 0.868134E+09 | 0.00 | 0.00 | 1987388.32 | 0.00 | 0.00 | 0.241604E+10 | 0.00 | 0.28 |
Maximum of Months | 0.258714E+11 | 0.834189E+09 | 0.00 | 79852655.64 | 0.192410E+09 | 0.112451E+10 | 0.229110E+11 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.310166E+10 | 0.00 | 0.00 | 959131.62 | 0.00 | 14794032.18 | 0.544774E+09 | 0.00 | 0.26 |
February | 0.220109E+10 | 0.00 | 0.00 | 1901274.95 | 0.00 | 222230.14 | 0.111216E+10 | 0.00 | 0.32 |
March | 0.147865E+10 | 0.00 | 0.00 | 6020025.27 | 0.00 | 0.00 | 0.363460E+10 | 0.00 | 0.64 |
April | 0.110619E+10 | 474838.55 | 0.00 | 9891466.73 | 0.00 | 0.00 | 0.433460E+10 | 0.00 | 1.05 |
May | 0.442010E+09 | 12332920.05 | 0.00 | 12313333.90 | 2473304.32 | 0.00 | 0.392496E+10 | 0.00 | 1.03 |
June | 0.432519E+09 | 0.197390E+09 | 0.00 | 14214786.19 | 15529763.21 | 0.00 | 0.242177E+10 | 0.00 | 1.07 |
July | 0.498784E+09 | 0.456391E+09 | 0.00 | 11722933.91 | 36385239.49 | 0.00 | 0.107776E+10 | 0.00 | 1.06 |
August | 0.690970E+09 | 0.248871E+09 | 0.00 | 15303602.09 | 8190928.79 | 0.00 | 0.182595E+10 | 0.00 | 1.20 |
September | 0.331603E+09 | 59017176.48 | 0.00 | 12677959.15 | 2008651.81 | 0.00 | 0.245690E+10 | 0.00 | 0.90 |
October | 0.110550E+10 | 108972.43 | 0.00 | 8415458.59 | 108800.58 | 0.00 | 0.285990E+10 | 0.00 | 0.70 |
November | 0.179408E+10 | 0.00 | 0.00 | 3792833.97 | 0.00 | 0.00 | 0.235702E+10 | 0.00 | 0.43 |
December | 0.279727E+10 | 0.00 | 0.00 | 1055070.19 | 0.00 | 0.00 | 0.601270E+09 | 0.00 | 0.23 |
Annual Sum or Average | 0.159803E+11 | 0.974586E+09 | 0.00 | 98267876.54 | 64696688.21 | 15016262.32 | 0.271517E+11 | 0.00 | 0.74 |
Minimum of Months | 0.331603E+09 | 0.00 | 0.00 | 959131.62 | 0.00 | 0.00 | 0.544774E+09 | 0.00 | 0.23 |
Maximum of Months | 0.310166E+10 | 0.456391E+09 | 0.00 | 15303602.09 | 36385239.49 | 14794032.18 | 0.433460E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160525E+10 | 0.00 | 0.00 | 4090151.66 | 0.00 | 15694916.12 | 0.155986E+10 | 0.00 | 0.36 |
February | 0.103343E+10 | 0.00 | 0.00 | 5479195.96 | 0.00 | 4218197.61 | 0.227223E+10 | 0.00 | 0.48 |
March | 0.750330E+09 | 0.00 | 0.00 | 11211411.86 | 0.00 | 0.00 | 0.501089E+10 | 0.00 | 1.03 |
April | 0.595334E+09 | 379774.64 | 0.00 | 17062873.37 | 0.00 | 0.00 | 0.696280E+10 | 0.00 | 1.94 |
May | 0.182721E+09 | 11030539.31 | 0.00 | 20975859.85 | 1433069.55 | 0.00 | 0.609041E+10 | 0.00 | 2.02 |
June | 0.251609E+09 | 0.154365E+09 | 0.00 | 19395146.46 | 9847521.97 | 0.00 | 0.291343E+10 | 0.00 | 1.81 |
July | 0.297948E+09 | 0.403286E+09 | 0.00 | 16719931.61 | 21137731.25 | 0.00 | 0.109608E+10 | 0.00 | 1.59 |
August | 0.425321E+09 | 0.229514E+09 | 0.00 | 19319700.39 | 4820800.61 | 0.00 | 0.207524E+10 | 0.00 | 1.89 |
September | 0.165284E+09 | 44635532.43 | 0.00 | 16981103.14 | 1129573.28 | 0.00 | 0.339954E+10 | 0.00 | 1.73 |
October | 0.530036E+09 | 149889.10 | 0.00 | 14100853.68 | 30627.36 | 0.00 | 0.447435E+10 | 0.00 | 1.25 |
November | 0.950456E+09 | 0.00 | 0.00 | 7163450.61 | 0.00 | 0.00 | 0.311295E+10 | 0.00 | 0.62 |
December | 0.142073E+10 | 0.00 | 0.00 | 4123985.50 | 0.00 | 7483883.28 | 0.151806E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.820845E+10 | 0.843361E+09 | 0.00 | 0.156624E+09 | 38399324.03 | 27396997.01 | 0.404858E+11 | 0.00 | 1.25 |
Minimum of Months | 0.165284E+09 | 0.00 | 0.00 | 4090151.66 | 0.00 | 0.00 | 0.109608E+10 | 0.00 | 0.30 |
Maximum of Months | 0.160525E+10 | 0.403286E+09 | 0.00 | 20975859.85 | 21137731.25 | 15694916.12 | 0.696280E+10 | 0.00 | 2.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179134E+10 | 0.00 | 0.00 | 28783141.26 | 0.00 | 67574114.18 | 0.731563E+10 | 0.00 | 0.75 |
February | 0.121170E+10 | 0.00 | 0.00 | 23612084.03 | 0.00 | 15076030.51 | 0.806705E+10 | 0.00 | 0.98 |
March | 0.103116E+10 | 0.00 | 0.00 | 22101054.23 | 0.00 | 0.00 | 0.960136E+10 | 0.00 | 1.42 |
April | 0.103171E+10 | 672797.34 | 0.00 | 19320134.75 | 0.00 | 0.00 | 0.749808E+10 | 0.00 | 1.70 |
May | 0.503636E+09 | 18351427.57 | 0.00 | 14994046.68 | 2448546.38 | 0.00 | 0.444123E+10 | 0.00 | 1.22 |
June | 0.493179E+09 | 0.199744E+09 | 0.00 | 12667427.80 | 15762997.03 | 0.00 | 0.203468E+10 | 0.00 | 1.00 |
July | 0.520497E+09 | 0.510477E+09 | 0.00 | 10391251.24 | 36094772.58 | 0.00 | 0.934860E+09 | 0.00 | 1.03 |
August | 0.675105E+09 | 0.331138E+09 | 0.00 | 19315043.20 | 6836867.78 | 0.00 | 0.198264E+10 | 0.00 | 1.37 |
September | 0.251104E+09 | 0.111322E+09 | 0.00 | 28677126.81 | 1242570.73 | 0.00 | 0.379613E+10 | 0.00 | 1.49 |
October | 0.675534E+09 | 883596.72 | 0.00 | 41032335.33 | 0.00 | 0.00 | 0.888916E+10 | 0.00 | 1.72 |
November | 0.774396E+09 | 0.00 | 0.00 | 31905932.45 | 0.00 | 0.00 | 0.112782E+11 | 0.00 | 1.25 |
December | 0.136499E+10 | 0.00 | 0.00 | 31813072.17 | 0.00 | 17739397.20 | 0.891725E+10 | 0.00 | 0.74 |
Annual Sum or Average | 0.103244E+11 | 0.117259E+10 | 0.00 | 0.284613E+09 | 62385754.49 | 0.100390E+09 | 0.747562E+11 | 0.00 | 1.22 |
Minimum of Months | 0.251104E+09 | 0.00 | 0.00 | 10391251.24 | 0.00 | 0.00 | 0.934860E+09 | 0.00 | 0.74 |
Maximum of Months | 0.179134E+10 | 0.510477E+09 | 0.00 | 41032335.33 | 36094772.58 | 67574114.18 | 0.112782E+11 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119491E+10 | 0.00 | 0.00 | 6860830.49 | 0.00 | 0.00 | 0.277538E+10 | 0.00 | 0.50 |
February | 0.491753E+09 | 0.00 | 0.00 | 10281232.34 | 0.00 | 0.00 | 0.468943E+10 | 0.00 | 0.87 |
March | 0.163745E+09 | 0.00 | 0.00 | 19611605.09 | 0.00 | 0.00 | 0.874044E+10 | 0.00 | 1.86 |
April | 0.206825E+09 | 710207.19 | 0.00 | 29240171.74 | 0.00 | 0.00 | 0.913065E+10 | 0.00 | 2.89 |
May | 0.133400E+09 | 27778635.38 | 0.00 | 18483196.36 | 418352.41 | 0.00 | 0.496865E+10 | 0.00 | 1.97 |
June | 0.130889E+09 | 0.241445E+09 | 0.00 | 16907038.04 | 709997.81 | 0.00 | 0.256572E+10 | 0.00 | 1.68 |
July | 80137719.97 | 0.505309E+09 | 0.00 | 14235452.95 | 5858712.14 | 0.00 | 0.133380E+10 | 0.00 | 1.53 |
August | 54621199.10 | 0.318920E+09 | 0.00 | 23467058.91 | 743790.66 | 0.00 | 0.274471E+10 | 0.00 | 2.13 |
September | 96805285.95 | 72374578.52 | 0.00 | 20404049.34 | 163650.45 | 0.00 | 0.295239E+10 | 0.00 | 1.60 |
October | 0.250792E+09 | 193301.66 | 0.00 | 21216771.59 | 33497.09 | 0.00 | 0.569211E+10 | 0.00 | 1.71 |
November | 0.228239E+09 | 0.00 | 0.00 | 14848838.60 | 0.00 | 0.00 | 0.722992E+10 | 0.00 | 1.26 |
December | 0.288217E+09 | 0.00 | 0.00 | 13444785.10 | 0.00 | 0.00 | 0.558474E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.332033E+10 | 0.116673E+10 | 0.00 | 0.209001E+09 | 7928000.56 | 0.00 | 0.584079E+11 | 0.00 | 1.56 |
Minimum of Months | 54621199.10 | 0.00 | 0.00 | 6860830.49 | 0.00 | 0.00 | 0.133380E+10 | 0.00 | 0.50 |
Maximum of Months | 0.119491E+10 | 0.505309E+09 | 0.00 | 29240171.74 | 5858712.14 | 0.00 | 0.913065E+10 | 0.00 | 2.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.274854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127683E+11 | 0.00 | 0.00 | 0.29 |
February | 0.246539E+11 | 0.00 | 0.00 | 1316256.16 | 0.00 | 0.749165E+10 | 0.457440E+09 | 0.00 | 0.29 |
March | 0.221143E+11 | 0.00 | 0.00 | 17308910.26 | 0.00 | 0.979304E+09 | 0.109634E+11 | 0.00 | 0.39 |
April | 0.115717E+11 | 5332294.56 | 0.00 | 54067291.54 | 0.00 | 6069752.60 | 0.213405E+11 | 0.00 | 0.67 |
May | 0.644203E+10 | 0.136211E+09 | 0.00 | 89430759.27 | 19386384.02 | 0.00 | 0.267535E+11 | 0.00 | 0.82 |
June | 0.256033E+10 | 0.303599E+10 | 0.00 | 91745940.16 | 52171843.44 | 0.00 | 0.156937E+11 | 0.00 | 0.83 |
July | 0.102230E+10 | 0.362891E+10 | 0.00 | 78674894.26 | 0.254419E+09 | 0.00 | 0.611243E+10 | 0.00 | 0.71 |
August | 0.152169E+10 | 0.186667E+10 | 0.00 | 0.110589E+09 | 0.107394E+09 | 0.00 | 0.121178E+11 | 0.00 | 0.79 |
September | 0.457120E+10 | 0.483904E+09 | 0.00 | 86761973.33 | 18418516.46 | 0.00 | 0.153493E+11 | 0.00 | 0.69 |
October | 0.163986E+11 | 0.00 | 0.00 | 41723410.16 | 2006720.29 | 0.750451E+09 | 0.110836E+11 | 0.00 | 0.49 |
November | 0.256982E+11 | 0.00 | 0.00 | 4718512.44 | 0.00 | 0.292949E+10 | 0.305211E+10 | 0.00 | 0.29 |
December | 0.253196E+11 | 0.00 | 0.00 | 27591.38 | 0.00 | 0.159636E+11 | 93295804.67 | 0.00 | 0.29 |
Annual Sum or Average | 0.169359E+12 | 0.915702E+10 | 0.00 | 0.576364E+09 | 0.453797E+09 | 0.408889E+11 | 0.123017E+12 | 0.00 | 0.55 |
Minimum of Months | 0.102230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.274854E+11 | 0.362891E+10 | 0.00 | 0.110589E+09 | 0.254419E+09 | 0.159636E+11 | 0.267535E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129441E+11 | 0.00 | 0.00 | 17019514.28 | 0.00 | 0.492396E+10 | 0.894825E+10 | 0.00 | 0.30 |
February | 0.109698E+11 | 0.00 | 0.00 | 30625716.52 | 0.00 | 0.177359E+10 | 0.138933E+11 | 0.00 | 0.37 |
March | 0.821867E+10 | 0.00 | 0.00 | 87731823.90 | 0.00 | 0.116106E+09 | 0.354360E+11 | 0.00 | 0.75 |
April | 0.318480E+10 | 5938627.28 | 0.00 | 0.161770E+09 | 0.00 | 0.00 | 0.623439E+11 | 0.00 | 1.73 |
May | 0.203621E+10 | 0.137206E+09 | 0.00 | 0.208915E+09 | 12541464.46 | 0.00 | 0.566166E+11 | 0.00 | 1.94 |
June | 0.117927E+10 | 0.254091E+10 | 0.00 | 0.161103E+09 | 20686205.76 | 0.00 | 0.249426E+11 | 0.00 | 1.71 |
July | 0.482313E+09 | 0.402087E+10 | 0.00 | 0.147939E+09 | 63532609.42 | 0.00 | 0.838209E+10 | 0.00 | 1.36 |
August | 0.613335E+09 | 0.182003E+10 | 0.00 | 0.191372E+09 | 59959778.64 | 0.00 | 0.196019E+11 | 0.00 | 1.66 |
September | 0.162470E+10 | 0.391629E+09 | 0.00 | 0.155081E+09 | 8529558.44 | 0.00 | 0.295271E+11 | 0.00 | 1.58 |
October | 0.559321E+10 | 2512115.42 | 0.00 | 0.117165E+09 | 70562.74 | 0.283683E+09 | 0.343574E+11 | 0.00 | 1.04 |
November | 0.107184E+11 | 0.00 | 0.00 | 41628616.61 | 0.00 | 0.437748E+09 | 0.180377E+11 | 0.00 | 0.42 |
December | 0.142621E+11 | 0.00 | 0.00 | 12519838.16 | 0.00 | 0.423766E+10 | 0.796638E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.718269E+11 | 0.891909E+10 | 0.00 | 0.133287E+10 | 0.165320E+09 | 0.117728E+11 | 0.320053E+12 | 0.00 | 1.10 |
Minimum of Months | 0.482313E+09 | 0.00 | 0.00 | 12519838.16 | 0.00 | 0.00 | 0.796638E+10 | 0.00 | 0.28 |
Maximum of Months | 0.142621E+11 | 0.402087E+10 | 0.00 | 0.208915E+09 | 63532609.42 | 0.492396E+10 | 0.623439E+11 | 0.00 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.171758E+11 | 0.00 | 0.00 | 0.331561E+09 | 0.00 | 0.359608E+10 | 0.875054E+11 | 0.00 | 0.94 |
February | 0.126583E+11 | 0.00 | 0.00 | 0.256808E+09 | 0.00 | 0.188733E+10 | 0.846848E+11 | 0.00 | 1.00 |
March | 0.120316E+11 | 0.00 | 0.00 | 0.212911E+09 | 0.00 | 84932928.28 | 0.743736E+11 | 0.00 | 1.10 |
April | 0.795615E+10 | 9705925.73 | 0.00 | 0.168249E+09 | 0.00 | 0.00 | 0.603164E+11 | 0.00 | 1.42 |
May | 0.628533E+10 | 0.227620E+09 | 0.00 | 0.125055E+09 | 19375319.79 | 0.00 | 0.359011E+11 | 0.00 | 1.07 |
June | 0.312928E+10 | 0.305446E+10 | 0.00 | 87869942.19 | 52142067.83 | 0.00 | 0.138377E+11 | 0.00 | 0.80 |
July | 0.100362E+10 | 0.425332E+10 | 0.00 | 82107032.04 | 0.255236E+09 | 0.00 | 0.577859E+10 | 0.00 | 0.74 |
August | 0.124147E+10 | 0.284851E+10 | 0.00 | 0.166438E+09 | 97645113.21 | 0.00 | 0.155870E+11 | 0.00 | 1.05 |
September | 0.257993E+10 | 0.110709E+10 | 0.00 | 0.280435E+09 | 6791473.03 | 0.00 | 0.323053E+11 | 0.00 | 1.38 |
October | 0.673415E+10 | 14019026.74 | 0.00 | 0.440441E+09 | 0.00 | 0.190678E+09 | 0.789421E+11 | 0.00 | 1.57 |
November | 0.100001E+11 | 0.00 | 0.00 | 0.351002E+09 | 0.00 | 0.112835E+09 | 0.961307E+11 | 0.00 | 1.02 |
December | 0.144985E+11 | 0.00 | 0.00 | 0.338960E+09 | 0.00 | 0.347970E+10 | 0.118572E+12 | 0.00 | 1.02 |
Annual Sum or Average | 0.952942E+11 | 0.115147E+11 | 0.00 | 0.284184E+10 | 0.431190E+09 | 0.935155E+10 | 0.703935E+12 | 0.00 | 1.09 |
Minimum of Months | 0.100362E+10 | 0.00 | 0.00 | 82107032.04 | 0.00 | 0.00 | 0.577859E+10 | 0.00 | 0.74 |
Maximum of Months | 0.171758E+11 | 0.425332E+10 | 0.00 | 0.440441E+09 | 0.255236E+09 | 0.359608E+10 | 0.118572E+12 | 0.00 | 1.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.171993E+11 | 0.00 | 0.00 | 25105942.08 | 0.00 | 0.440440E+10 | 0.115088E+11 | 0.00 | 0.41 |
February | 0.133703E+11 | 0.00 | 0.00 | 41455404.63 | 0.00 | 0.199804E+10 | 0.182879E+11 | 0.00 | 0.53 |
March | 0.938777E+10 | 0.00 | 0.00 | 87744792.66 | 0.00 | 0.123832E+09 | 0.336592E+11 | 0.00 | 0.88 |
April | 0.421415E+10 | 7001435.88 | 0.00 | 0.155994E+09 | 0.00 | 0.00 | 0.431720E+11 | 0.00 | 1.67 |
May | 0.271529E+10 | 0.312121E+09 | 0.00 | 0.136150E+09 | 2122093.28 | 0.00 | 0.337648E+11 | 0.00 | 1.56 |
June | 0.122281E+10 | 0.408914E+10 | 0.00 | 99070005.04 | 12948340.51 | 0.00 | 0.134856E+11 | 0.00 | 1.28 |
July | 0.396070E+09 | 0.445842E+10 | 0.00 | 78884160.69 | 0.114854E+09 | 0.00 | 0.551778E+10 | 0.00 | 1.05 |
August | 0.565757E+09 | 0.240221E+10 | 0.00 | 0.128296E+09 | 18659796.85 | 0.00 | 0.126346E+11 | 0.00 | 1.29 |
September | 0.139259E+10 | 0.659909E+09 | 0.00 | 0.149892E+09 | 1233036.42 | 0.00 | 0.190724E+11 | 0.00 | 1.20 |
October | 0.679560E+10 | 0.00 | 0.00 | 0.125897E+09 | 1292840.65 | 0.135434E+09 | 0.275489E+11 | 0.00 | 1.07 |
November | 0.127122E+11 | 0.00 | 0.00 | 46339063.09 | 0.00 | 0.282990E+09 | 0.195295E+11 | 0.00 | 0.50 |
December | 0.177282E+11 | 0.00 | 0.00 | 24410537.60 | 0.00 | 0.395585E+10 | 0.147086E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.877001E+11 | 0.119288E+11 | 0.00 | 0.109924E+10 | 0.151110E+09 | 0.109005E+11 | 0.252890E+12 | 0.00 | 0.99 |
Minimum of Months | 0.396070E+09 | 0.00 | 0.00 | 24410537.60 | 0.00 | 0.00 | 0.551778E+10 | 0.00 | 0.41 |
Maximum of Months | 0.177282E+11 | 0.445842E+10 | 0.00 | 0.155994E+09 | 0.114854E+09 | 0.440440E+10 | 0.431720E+11 | 0.00 | 1.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263796E+10 | 0.00 | 0.00 | 0.32 |
February | 0.167870E+10 | 0.00 | 0.00 | 70033.74 | 0.00 | 0.156165E+10 | 44227828.59 | 0.00 | 0.31 |
March | 0.223850E+10 | 0.00 | 0.00 | 1018482.24 | 0.00 | 0.490741E+09 | 0.755672E+09 | 0.00 | 0.41 |
April | 0.118076E+10 | 0.00 | 0.00 | 4941395.28 | 996.48 | 95557110.22 | 0.199810E+10 | 0.00 | 0.69 |
May | 0.708144E+09 | 5418040.52 | 0.00 | 9014885.44 | 3805865.13 | 4921143.87 | 0.260059E+10 | 0.00 | 0.86 |
June | 0.272408E+09 | 0.181877E+09 | 0.00 | 11490331.13 | 4996467.17 | 0.00 | 0.152884E+10 | 0.00 | 0.82 |
July | 0.117821E+09 | 0.204876E+09 | 0.00 | 11217942.77 | 24424070.77 | 0.00 | 0.627020E+09 | 0.00 | 0.71 |
August | 0.180677E+09 | 0.105679E+09 | 0.00 | 13599063.72 | 9179322.93 | 0.00 | 0.125550E+10 | 0.00 | 0.81 |
September | 0.465387E+09 | 27934443.12 | 0.00 | 9496425.38 | 1132171.22 | 0.00 | 0.150047E+10 | 0.00 | 0.72 |
October | 0.157171E+10 | 18741.83 | 0.00 | 3568074.58 | 0.00 | 0.277515E+09 | 0.889737E+09 | 0.00 | 0.50 |
November | 0.201662E+10 | 0.00 | 0.00 | 179503.67 | 0.00 | 0.951989E+09 | 0.131466E+09 | 0.00 | 0.31 |
December | 0.122710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283746E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.130389E+11 | 0.525803E+09 | 0.00 | 64596137.94 | 43538893.70 | 0.885780E+10 | 0.113316E+11 | 0.00 | 0.56 |
Minimum of Months | 0.117821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.223850E+10 | 0.204876E+09 | 0.00 | 13599063.72 | 24424070.77 | 0.283746E+10 | 0.260059E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123892E+10 | 0.00 | 0.00 | 485511.50 | 0.00 | 0.100846E+10 | 0.350728E+09 | 0.00 | 0.32 |
February | 0.114090E+10 | 0.00 | 0.00 | 1722768.88 | 0.00 | 0.467991E+09 | 0.900747E+09 | 0.00 | 0.38 |
March | 0.791524E+09 | 0.00 | 0.00 | 6917535.26 | 0.00 | 0.141758E+09 | 0.368587E+10 | 0.00 | 0.84 |
April | 0.305070E+09 | 0.00 | 0.00 | 15068563.71 | 641.72 | 16639356.63 | 0.635169E+10 | 0.00 | 1.83 |
May | 0.190344E+09 | 7424231.50 | 0.00 | 21028386.91 | 978012.18 | 1996663.24 | 0.584001E+10 | 0.00 | 2.06 |
June | 0.111825E+09 | 0.155824E+09 | 0.00 | 19544985.38 | 1935442.29 | 0.00 | 0.258023E+10 | 0.00 | 1.77 |
July | 49287109.56 | 0.276073E+09 | 0.00 | 18927043.77 | 4555512.31 | 0.00 | 0.889977E+09 | 0.00 | 1.41 |
August | 64895278.08 | 0.112713E+09 | 0.00 | 22950412.21 | 4555537.18 | 0.00 | 0.209223E+10 | 0.00 | 1.77 |
September | 0.163695E+09 | 22801514.88 | 0.00 | 16767093.12 | 611779.36 | 0.00 | 0.298950E+10 | 0.00 | 1.72 |
October | 0.540519E+09 | 16269.28 | 0.00 | 10343275.15 | 0.00 | 0.108466E+09 | 0.323347E+10 | 0.00 | 1.08 |
November | 0.104287E+10 | 0.00 | 0.00 | 2389847.23 | 0.00 | 0.234741E+09 | 0.126934E+10 | 0.00 | 0.39 |
December | 0.144151E+10 | 0.00 | 0.00 | 227825.34 | 0.00 | 0.954215E+09 | 0.189123E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.708135E+10 | 0.574852E+09 | 0.00 | 0.136373E+09 | 12636925.04 | 0.293427E+10 | 0.303729E+11 | 0.00 | 1.16 |
Minimum of Months | 49287109.56 | 0.00 | 0.00 | 227825.34 | 0.00 | 0.00 | 0.189123E+09 | 0.00 | 0.30 |
Maximum of Months | 0.144151E+10 | 0.276073E+09 | 0.00 | 22950412.21 | 4555537.18 | 0.100846E+10 | 0.635169E+10 | 0.00 | 2.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139021E+10 | 0.00 | 0.00 | 23023445.86 | 0.00 | 0.863381E+09 | 0.713651E+10 | 0.00 | 0.87 |
February | 0.114743E+10 | 0.00 | 0.00 | 19844709.98 | 0.00 | 0.460035E+09 | 0.771815E+10 | 0.00 | 0.96 |
March | 0.113435E+10 | 0.00 | 0.00 | 17956191.06 | 0.00 | 0.259456E+09 | 0.831639E+10 | 0.00 | 1.27 |
April | 0.768215E+09 | 0.00 | 0.00 | 15824175.29 | 998.57 | 49444732.57 | 0.625671E+10 | 0.00 | 1.48 |
May | 0.637327E+09 | 9294497.69 | 0.00 | 13652515.89 | 2898696.13 | 9201571.51 | 0.374973E+10 | 0.00 | 1.14 |
June | 0.338515E+09 | 0.176615E+09 | 0.00 | 11519033.71 | 5162709.79 | 0.00 | 0.143672E+10 | 0.00 | 0.80 |
July | 0.115405E+09 | 0.233630E+09 | 0.00 | 12535759.92 | 23779345.30 | 0.00 | 0.623016E+09 | 0.00 | 0.73 |
August | 0.160077E+09 | 0.153432E+09 | 0.00 | 21571222.15 | 7497918.66 | 0.00 | 0.171881E+10 | 0.00 | 1.09 |
September | 0.281351E+09 | 60908083.19 | 0.00 | 31572437.61 | 581647.19 | 0.00 | 0.349373E+10 | 0.00 | 1.51 |
October | 0.652938E+09 | 42118.22 | 0.00 | 40764170.61 | 0.00 | 0.139220E+09 | 0.824060E+10 | 0.00 | 1.71 |
November | 0.100522E+10 | 0.00 | 0.00 | 24954827.45 | 0.00 | 0.212926E+09 | 0.876119E+10 | 0.00 | 1.00 |
December | 0.132240E+10 | 0.00 | 0.00 | 23440746.74 | 0.00 | 0.706474E+09 | 0.942276E+10 | 0.00 | 0.89 |
Annual Sum or Average | 0.895344E+10 | 0.633922E+09 | 0.00 | 0.256659E+09 | 39921315.64 | 0.270014E+10 | 0.668743E+11 | 0.00 | 1.12 |
Minimum of Months | 0.115405E+09 | 0.00 | 0.00 | 11519033.71 | 0.00 | 0.00 | 0.623016E+09 | 0.00 | 0.73 |
Maximum of Months | 0.139021E+10 | 0.233630E+09 | 0.00 | 40764170.61 | 23779345.30 | 0.863381E+09 | 0.942276E+10 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127054E+10 | 0.00 | 0.00 | 1781296.16 | 0.00 | 0.839868E+09 | 0.999689E+09 | 0.00 | 0.41 |
February | 0.108229E+10 | 0.00 | 0.00 | 3392097.09 | 0.00 | 0.466082E+09 | 0.179459E+10 | 0.00 | 0.53 |
March | 0.980037E+09 | 0.00 | 0.00 | 7714077.59 | 0.00 | 0.178872E+09 | 0.354788E+10 | 0.00 | 1.00 |
April | 0.474911E+09 | 0.00 | 0.00 | 15047517.90 | 645.67 | 8249395.75 | 0.443310E+10 | 0.00 | 1.77 |
May | 0.314660E+09 | 13155851.15 | 0.00 | 15657448.47 | 1071146.78 | 125662.32 | 0.352091E+10 | 0.00 | 1.67 |
June | 0.129255E+09 | 0.224279E+09 | 0.00 | 14478005.30 | 2106644.74 | 0.00 | 0.143149E+10 | 0.00 | 1.27 |
July | 43844552.41 | 0.234919E+09 | 0.00 | 12063744.84 | 11810843.32 | 0.00 | 0.593140E+09 | 0.00 | 1.01 |
August | 54966202.63 | 0.128831E+09 | 0.00 | 16580706.39 | 1122383.06 | 0.00 | 0.135988E+10 | 0.00 | 1.31 |
September | 0.175908E+09 | 36261450.14 | 0.00 | 17765303.07 | 158355.97 | 0.00 | 0.191628E+10 | 0.00 | 1.28 |
October | 0.705101E+09 | 31253.59 | 0.00 | 12021535.42 | 0.00 | 97026740.99 | 0.265781E+10 | 0.00 | 1.12 |
November | 0.117249E+10 | 0.00 | 0.00 | 3429974.93 | 0.00 | 0.237512E+09 | 0.163894E+10 | 0.00 | 0.49 |
December | 0.127006E+10 | 0.00 | 0.00 | 1699836.36 | 0.00 | 0.838961E+09 | 0.107490E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.767406E+10 | 0.637477E+09 | 0.00 | 0.121632E+09 | 16270019.54 | 0.266670E+10 | 0.249686E+11 | 0.00 | 1.02 |
Minimum of Months | 43844552.41 | 0.00 | 0.00 | 1699836.36 | 0.00 | 0.00 | 0.593140E+09 | 0.00 | 0.37 |
Maximum of Months | 0.127054E+10 | 0.234919E+09 | 0.00 | 17765303.07 | 11810843.32 | 0.839868E+09 | 0.443310E+10 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3847143.90 | 0.00 | 0.00 | 0.543691E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8772476.68 | 0.00 | 0.00 | 0.454439E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 15921235.96 | 0.00 | 0.00 | 0.427163E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 18439556.42 | 0.00 | 0.00 | 0.289349E+09 | 0.00 | 0.29 |
May | 0.00 | 478273.36 | 0.00 | 4274716.86 | 0.00 | 0.00 | 0.214849E+09 | 0.00 | 0.29 |
June | 0.00 | 26143623.34 | 0.00 | 5654854.91 | 0.00 | 0.00 | 48171190.78 | 0.00 | 0.30 |
July | 0.00 | 0.145682E+09 | 0.00 | 206615.55 | 0.00 | 0.00 | 209993.96 | 0.00 | 0.28 |
August | 0.00 | 0.114079E+09 | 0.00 | 1232217.97 | 0.00 | 0.00 | 936206.66 | 0.00 | 0.30 |
September | 0.00 | 18863222.77 | 0.00 | 2840831.45 | 0.00 | 0.00 | 55073507.81 | 0.00 | 0.29 |
October | 0.00 | 4369450.93 | 0.00 | 8725570.69 | 0.00 | 0.00 | 0.273538E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 14172336.87 | 0.00 | 0.00 | 0.423030E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 20594504.35 | 0.00 | 0.00 | 0.545436E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.309615E+09 | 0.00 | 0.104682E+09 | 0.00 | 0.00 | 0.327589E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 206615.55 | 0.00 | 0.00 | 209993.96 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.145682E+09 | 0.00 | 20594504.35 | 0.00 | 0.00 | 0.545436E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9519048.48 | 0.00 | 0.00 | 24263548.15 | 0.00 | 0.00 | 0.544032E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 73893661.03 | 0.00 | 0.00 | 0.455780E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.144740E+09 | 0.00 | 0.00 | 0.428450E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.173800E+09 | 0.00 | 0.00 | 0.290273E+10 | 0.00 | 0.29 |
May | 0.00 | 4264234.62 | 0.00 | 38333682.99 | 0.00 | 0.00 | 0.215697E+10 | 0.00 | 0.29 |
June | 0.00 | 0.259132E+09 | 0.00 | 52966224.64 | 0.00 | 0.00 | 0.486673E+09 | 0.00 | 0.30 |
July | 0.00 | 0.145068E+10 | 0.00 | 1972978.78 | 0.00 | 0.00 | 2036868.35 | 0.00 | 0.28 |
August | 0.00 | 0.114486E+10 | 0.00 | 11562877.79 | 0.00 | 0.00 | 9207175.13 | 0.00 | 0.30 |
September | 0.00 | 0.178572E+09 | 0.00 | 25919524.15 | 0.00 | 0.00 | 0.562148E+09 | 0.00 | 0.29 |
October | 0.00 | 42308661.83 | 0.00 | 78542309.60 | 0.00 | 0.00 | 0.274447E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.127233E+09 | 0.00 | 0.00 | 0.424391E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.182586E+09 | 0.00 | 0.00 | 0.547644E+10 | 0.00 | 0.28 |
Annual Sum or Average | 9519048.48 | 0.307982E+10 | 0.00 | 0.935815E+09 | 0.00 | 0.00 | 0.328672E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1972978.78 | 0.00 | 0.00 | 2036868.35 | 0.00 | 0.28 |
Maximum of Months | 9519048.48 | 0.145068E+10 | 0.00 | 0.182586E+09 | 0.00 | 0.00 | 0.547644E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.181100E+09 | 0.00 | 0.00 | 1257760.35 | 0.00 | 0.00 | 0.361409E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6254740.68 | 0.00 | 0.00 | 0.457045E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 13628832.77 | 0.00 | 0.00 | 0.429429E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 17112998.95 | 0.00 | 0.00 | 0.290568E+09 | 0.00 | 0.29 |
May | 0.00 | 432876.62 | 0.00 | 3745308.66 | 0.00 | 0.00 | 0.215962E+09 | 0.00 | 0.29 |
June | 0.00 | 25947515.23 | 0.00 | 5299074.44 | 0.00 | 0.00 | 48780180.27 | 0.00 | 0.30 |
July | 0.00 | 0.145082E+09 | 0.00 | 199510.30 | 0.00 | 0.00 | 209765.94 | 0.00 | 0.28 |
August | 0.00 | 0.114766E+09 | 0.00 | 1135283.43 | 0.00 | 0.00 | 901397.80 | 0.00 | 0.30 |
September | 0.00 | 17926676.98 | 0.00 | 2528663.94 | 0.00 | 0.00 | 56397047.56 | 0.00 | 0.29 |
October | 0.00 | 4217606.15 | 0.00 | 7298715.30 | 0.00 | 0.00 | 0.275217E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11658889.80 | 0.00 | 0.00 | 0.425575E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16679555.72 | 0.00 | 0.00 | 0.549292E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.181100E+09 | 0.308372E+09 | 0.00 | 86799334.34 | 0.00 | 0.00 | 0.311078E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 199510.30 | 0.00 | 0.00 | 209765.94 | 0.00 | 0.28 |
Maximum of Months | 0.181100E+09 | 0.145082E+09 | 0.00 | 17112998.95 | 0.00 | 0.00 | 0.549292E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.633910E+09 | 0.00 | 0.00 | 0.569953E+12 | 0.00 | 11.61 |
February | 0.00 | 0.00 | 0.00 | 0.107533E+10 | 0.00 | 0.00 | 0.776050E+12 | 0.00 | 21.21 |
March | 0.00 | 0.00 | 0.00 | 0.178651E+10 | 0.00 | 0.00 | 0.108848E+13 | 0.00 | 36.55 |
April | 0.00 | 0.00 | 0.00 | 0.263769E+10 | 0.00 | 0.00 | 0.109066E+13 | 0.00 | 51.41 |
May | 0.00 | 0.00 | 0.00 | 0.608011E+09 | 0.00 | 0.00 | 0.493016E+12 | 0.00 | 30.89 |
June | 0.00 | 0.140416E+10 | 0.00 | 0.108453E+10 | 0.00 | 0.00 | 0.388736E+12 | 0.00 | 34.68 |
July | 0.00 | 0.275631E+11 | 0.00 | 0.105463E+10 | 0.00 | 0.00 | 0.124985E+12 | 0.00 | 35.14 |
August | 0.00 | 0.404069E+11 | 0.00 | 0.156268E+10 | 0.00 | 0.00 | 0.145056E+12 | 0.00 | 41.89 |
September | 0.00 | 0.502239E+09 | 0.00 | 0.578303E+09 | 0.00 | 0.00 | 0.331645E+12 | 0.00 | 33.34 |
October | 0.00 | 0.127085E+09 | 0.00 | 0.132397E+10 | 0.00 | 0.00 | 0.759944E+12 | 0.00 | 36.48 |
November | 0.00 | 0.00 | 0.00 | 0.177630E+10 | 0.00 | 0.00 | 0.107489E+13 | 0.00 | 32.63 |
December | 0.00 | 0.00 | 0.00 | 0.252784E+10 | 0.00 | 0.00 | 0.135784E+13 | 0.00 | 32.99 |
Annual Sum or Average | 0.00 | 0.700035E+11 | 0.00 | 0.166497E+11 | 0.00 | 0.00 | 0.820126E+13 | 0.00 | 33.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.578303E+09 | 0.00 | 0.00 | 0.124985E+12 | 0.00 | 11.61 |
Maximum of Months | 0.00 | 0.404069E+11 | 0.00 | 0.263769E+10 | 0.00 | 0.00 | 0.135784E+13 | 0.00 | 51.41 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:30
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.449052E+12 | 0.985777E+10 | 0.00 | 0.233505E+13 | 0.184741E+12 |
February | 0.554610E+12 | 0.918439E+10 | 0.00 | 0.240568E+13 | 0.292195E+12 |
March | 0.721880E+12 | 0.891143E+10 | 0.00 | 0.290813E+13 | 0.522335E+12 |
April | 0.892159E+12 | 0.643214E+10 | 0.00 | 0.285139E+13 | 0.113079E+13 |
May | 0.952867E+12 | 0.410403E+10 | 0.00 | 0.192678E+13 | 0.101935E+13 |
June | 0.894181E+12 | 0.201899E+10 | 0.00 | 0.122140E+13 | 0.222582E+13 |
July | 0.920572E+12 | 0.840504E+09 | 0.00 | 0.464859E+12 | 0.317690E+13 |
August | 0.901192E+12 | 0.155424E+10 | 0.00 | 0.783534E+12 | 0.352341E+13 |
September | 0.732458E+12 | 0.261867E+10 | 0.00 | 0.152675E+13 | 0.147364E+13 |
October | 0.597611E+12 | 0.498822E+10 | 0.00 | 0.249217E+13 | 0.902116E+12 |
November | 0.479580E+12 | 0.813167E+10 | 0.00 | 0.292248E+13 | 0.421187E+12 |
December | 0.419036E+12 | 0.891992E+10 | 0.00 | 0.320603E+13 | 0.366997E+12 |
Annual Sum or Average | 0.851520E+13 | 0.675620E+11 | 0.00 | 0.250443E+14 | 0.152395E+14 |
Minimum of Months | 0.419036E+12 | 0.840504E+09 | 0.00 | 0.464859E+12 | 0.184741E+12 |
Maximum of Months | 0.952867E+12 | 0.985777E+10 | 0.00 | 0.320603E+13 | 0.352341E+13 |