Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2024-07-03 12:21:59
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 25571.22 | 552.05 | 552.05 |
Net Site Energy | 25134.07 | 542.61 | 542.61 |
Total Source Energy | 79029.44 | 1706.15 | 1706.15 |
Net Source Energy | 77644.98 | 1676.26 | 1676.26 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 938.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1279.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1715.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 266.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1641.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2295.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 334.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 464.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3055.38 |
Humidification | 1461.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.68 |
Heat Recovery | 37.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 459.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 24632.85 | 938.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5879.23 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 938.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1279.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1715.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 266.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1582.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2295.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 334.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 464.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3055.38 |
Humidification | General | 1461.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.68 |
Heat Recovery | General | 37.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 459.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 938.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1279.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1715.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 266.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1641.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2295.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 334.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 464.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3055.38 |
Humidification | Unassigned | 1461.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.68 |
Heat Recovery | Unassigned | 37.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 459.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 135.92 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 353.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 531.79 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 135.92 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 353.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 531.79 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 457.739 | 1.86 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -20.59 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 437.151 | 1.77 |
Electricity Coming From Utility | 24195.702 | 98.23 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 24195.702 | 98.23 |
Total On-Site and Utility Electric Sources | 24632.854 | 100.00 |
Total Electricity End Uses | 24632.854 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 115.19 | 5.31 |
Air to Air Heat Recovery for Heating | 2056.04 | 94.69 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2171.23 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5879.23 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5879.23 | 100.00 |
Total Water End Uses | 5879.23 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 81.50 |
Time Setpoint Not Met During Occupied Cooling | 933.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5905.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-AUG-14:20 | 02-JAN-05:10 | - | - | - | - | - | - | - | - | - | - | 04-AUG-12:30 |
Heating | 0.00 | 1478009.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 430832.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 154722.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 214976.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44075.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 75503.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26369.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1870839.05 | 1478009.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1478009.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 430832.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3359.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 151268.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 94.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 214976.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 44075.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 75503.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 26369.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1017.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4050.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5432.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 5198.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7270.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1060.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1472.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4628.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 118.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1456.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 78012.25 | 1017.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 21.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 87.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 112.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 31.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 99.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1684.19 | 21.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 21.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 87.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 112.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 31.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 99.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1684.19 | 21.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 4.88 | 0.433868 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.33 | 0.356581 | 0.303000 | 1.62 | 0.950882 | 0.500000 | 0.001068 | 0.000347 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 49.98 | 0.380571 | 0.323000 | 16.14 | 1.00 | 0.500000 | 0.001001 | 0.009230 | 16.14 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.96 | 0.383683 | 0.326000 | 1.62 | 1.00 | 0.500000 | 0.000993 | 0.001973 | 2.75 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.909694 | 0.262528 | 0.223000 | 0.202862 | 0.700076 | 0.500000 | 0.001451 | 0.000322 | 0.449981 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.26 | 0.122189 | 0.104000 | 0.130994 | 0.325838 | 0.500000 | 0.003118 | 0.000221 | 0.308650 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.43 | 0.166706 | 0.142000 | 0.203431 | 0.444550 | 0.500000 | 0.002285 | 0.000367 | 0.512490 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.54 | 0.099696 | 0.085000 | 0.131218 | 0.300000 | 0.500000 | 0.003822 | 0.000170 | 0.236916 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.49 | 0.281318 | 0.239000 | 2.03 | 0.750181 | 0.500000 | 0.001354 | 0.005152 | 7.21 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.48 | 0.304490 | 0.500000 | 0.003337 | 0.003376 | 4.72 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.23 | 0.167796 | 0.143000 | 2.04 | 0.447456 | 0.500000 | 0.002271 | 0.005152 | 7.21 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.15 | 0.108760 | 0.092000 | 1.30 | 0.300000 | 0.500000 | 0.003503 | 0.003270 | 4.57 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.968256 | 0.246650 | 0.210000 | 0.203334 | 0.657734 | 0.500000 | 0.001545 | 0.000654 | 0.915871 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.36 | 0.113226 | 0.096000 | 0.130490 | 0.301936 | 0.500000 | 0.003365 | 0.000427 | 0.597820 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.54 | 0.155553 | 0.132000 | 0.202664 | 0.414808 | 0.500000 | 0.002449 | 0.000654 | 0.915879 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.49 | 0.103048 | 0.088000 | 0.131430 | 0.300000 | 0.500000 | 0.003697 | 0.000421 | 0.588750 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 15864.88 | 0.000347 | 442.79 | |
CORE_MID VAV BOX REHEAT COIL | 421955.20 | 0.009230 | 14627.04 | |
CORE_TOP VAV BOX REHEAT COIL | 90205.61 | 0.001973 | 3510.23 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14721.30 | 0.000322 | 572.43 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10096.20 | 0.000221 | 392.55 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16761.81 | 0.000367 | 651.66 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7755.02 | 0.000170 | 301.66 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 235525.80 | 0.005152 | 9151.75 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 154333.57 | 0.003376 | 5996.76 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 235527.17 | 0.005152 | 9151.80 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 149501.38 | 0.003270 | 5809.18 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 29918.14 | 0.000654 | 1162.23 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 19528.12 | 0.000427 | 758.59 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 29918.38 | 0.000654 | 1162.24 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 19232.12 | 0.000421 | 747.10 | |
VAV_BOT WITH REHEAT HEATING COIL | 71102.94 | 0.001555 | 1400.11 | |
VAV_MID WITH REHEAT HEATING COIL | 661872.65 | 0.014478 | 13029.31 | |
VAV_TOP WITH REHEAT HEATING COIL | 65199.11 | 0.001426 | 1315.16 | |
CAV_BAS HEATING COIL | 253410.45 | 0.002188 | 3855.77 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.489392 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.69 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.477518 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 25.02 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.24 | 2.28 | 10.48 | 2.59 | 8.96 | 8.96 | 0.300000 | 0.288664 | 8.96 |
VAV_MID WITH REHEAT | 50.17 | 22.82 | 100.33 | 35.10 | 83.33 | 83.33 | 0.300000 | 0.421212 | 83.33 |
VAV_TOP WITH REHEAT | 5.16 | 2.28 | 10.31 | 5.77 | 9.20 | 9.20 | 0.300000 | 0.627161 | 9.20 |
CAV_BAS | 0.000000 | 0.000000 | 4.88 | 1.20 | 4.88 | 4.88 | 1.00 | 0.245859 | 4.88 |
AIRLOOP DATACENTER BASEMENT | 25.02 | 25.02 | 25.02 | 25.02 | 25.02 | 25.02 | 1.00 | 0.999992 | 25.02 |
AIRLOOP DATACENTER BOT | 0.489392 | 0.489392 | 0.489392 | 0.489392 | 0.489392 | 0.489392 | 1.00 | 1.00 | 0.489392 |
AIRLOOP DATACENTER MID | 4.69 | 4.69 | 4.69 | 4.69 | 4.69 | 4.69 | 1.00 | 1.00 | 4.69 |
AIRLOOP DATACENTER TOP | 0.477518 | 0.477518 | 0.477518 | 0.477518 | 0.477518 | 0.477518 | 1.00 | 1.00 | 0.477518 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.96 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 83.33 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.20 | |
CAV_BAS_OA_CONTROLLER | 4.88 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 25.02 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.489392 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.69 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.477518 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.03 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 20.31 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.03 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.47 | 6.67 | 10.90 | 0.009934 | 0.008500 | 194762.34 | 0.005570 | 8.96 |
VAV_MID WITH REHEAT COOLING COIL | 25.62 | 6.67 | 10.90 | 0.010098 | 0.008500 | 1867793.92 | 0.053419 | 83.33 |
VAV_TOP WITH REHEAT COOLING COIL | 25.39 | 6.67 | 10.90 | 0.009900 | 0.008500 | 198363.47 | 0.005673 | 9.20 |
CAV_BAS COOLING COIL | 25.39 | 6.67 | 10.89 | 0.010241 | 0.008500 | 110215.30 | 0.003152 | 4.88 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.96 |
VAV_MID WITH REHEAT FAN | 83.33 |
VAV_TOP WITH REHEAT FAN | 9.20 |
CAV_BAS FAN | 4.88 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005570 | 0.000085 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001555 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.053419 | 0.000009 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.014478 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005673 | 0.000084 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001426 | |
CAV_BAS_COOLC_CONTROLLER | 0.003152 | 0.000151 |
CAV_BAS_HEATC_CONTROLLER | 0.002188 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 25.02 | 495536.67 | 348941.98 | 0.012136 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.489392 | 9596.72 | 6786.32 | 0.000235 |
AIRLOOP DATACENTER MID COOLING COIL | 4.69 | 92173.41 | 65133.21 | 0.002257 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.477518 | 9373.65 | 6624.81 | 0.000230 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 25.02 | 25.02 | 25.02 | 25.02 | 495536.67 | 495536.67 | 22473.72 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.489392 | 0.489392 | 0.489392 | 0.489392 | 9596.72 | 9596.72 | 1038.19 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.69 | 4.69 | 4.69 | 4.69 | 92173.41 | 92173.41 | 10381.93 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.477518 | 0.477518 | 0.477518 | 0.477518 | 9373.65 | 9373.65 | 1038.19 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 25.02 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.489392 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.69 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.477518 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 25.02 | 495536.67 | 0.012136 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.489392 | 9596.72 | 0.000235 |
AIRLOOP DATACENTER MID HEATING COIL | 4.69 | 92173.41 | 0.002257 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.477518 | 9373.65 | 0.000230 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 22473.72 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1038.19 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 10381.93 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1038.19 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000214 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.067814 | 10962.36 | |
HEATSYS1 PUMP | 0.051385 | 15321.65 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.067814 | 8.14 |
HEATSYS1 | 0.051385 | 6.17 |
COOLSYS1_SUPPLY | 0.067814 | 8.14 |
SINGLE WATER PLANT LOOP | 0.014858 | 1.78 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.067814 | 0.067814 | 284650.06 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2349019.39 | 2349019.39 | 0.051385 |
CENTRAL BOILER | 612004.32 | 599658.79 | 0.014858 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.033907 | 3794.80 |
COOLSYS1 CHILLER2 PUMP | 0.033907 | 3794.80 |
PLANT CIRC PUMP | 0.014858 | 3751.90 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.067814 | 0.034037 | 1190124.16 | 1190123.79 | 0.059929 |
COOLSYS1 CHILLER2 | 0.067814 | 0.034037 | 1190124.16 | 1190123.79 | 0.059929 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.014858 | 147524.60 | 74681.50 | 73762.30 | 7004.20 | 44808.90 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.119857 | 14.38 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.119857 | 29380.23 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 42.83 | 1424658.96 | 8.57 | 178082.37 |
TOWERWATERSYS COOLTOWER 2 | 42.83 | 1424658.96 | 8.57 | 178082.37 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.061718 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.8378 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.8072 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 0.9232 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.026 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.072 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9158 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.24829308E-14 | 0.29135133E-16 | -0.15401821E-09 | 0.38773647E-16 |
51 | 8 | 0.22478683E-07 | 0.11333425E-12 | 0.38411067E-03 | -0.25559038E-09 |
52 | 7 | -0.12429992E-01 | 0.58464112E-08 | -0.23357103E-01 | 0.14133354E-03 |
53 | 6 | 0.41047043 | 0.20318695E-05 | 0.47644950 | -0.48081157E-02 |
54 | 5 | -5.2405281 | 0.75802388E-04 | -4.4747275 | 0.63803387E-01 |
55 | 4 | 33.223854 | 0.61961214E-03 | 21.571135 | -0.42505714 |
56 | 3 | -111.69641 | 0.13494874E-02 | -55.882598 | 1.5219877 |
57 | 2 | 197.59721 | 0.75863434E-03 | 78.112020 | -2.9081180 |
58 | 1 | -171.33669 | 0.80942272E-04 | -55.323717 | 2.7486048 |
59 | 0 | 57.057407 | 0.46049242E-06 | 15.547298 | |
60 | 9 | -0.15339349E-14 | 0.29979511E-16 | -0.15544574E-09 | 0.39943344E-16 |
61 | 8 | 0.22679133E-07 | 0.10934645E-12 | 0.38619381E-03 | -0.25786952E-09 |
62 | 7 | -0.12492075E-01 | 0.56288006E-08 | -0.23446467E-01 | 0.14203945E-03 |
63 | 6 | 0.41215724 | 0.19545976E-05 | 0.47788421 | -0.48279991E-02 |
64 | 5 | -5.2569880 | 0.72866980E-04 | -4.4857383 | 0.64007484E-01 |
65 | 4 | 33.296652 | 0.59522869E-03 | 21.614155 | -0.42602372 |
66 | 3 | -111.85128 | 0.12956249E-02 | -55.967640 | 1.5242251 |
67 | 2 | 197.75067 | 0.72797512E-03 | 78.190049 | -2.9105550 |
68 | 1 | -171.39336 | 0.77633808E-04 | -55.346469 | 2.7495981 |
69 | 0 | 57.057407 | 0.44138471E-06 | 15.543591 | |
70 | 9 | -0.23125622E-14 | 0.35111754E-16 | -0.15002006E-09 | 0.46457589E-16 |
71 | 8 | 0.21917045E-07 | 0.12438460E-12 | 0.37824022E-03 | -0.24920433E-09 |
72 | 7 | -0.12254923E-01 | 0.64545218E-08 | -0.23105067E-01 | 0.13934294E-03 |
73 | 6 | 0.40571362 | 0.22485912E-05 | 0.47240083 | -0.47520443E-02 |
74 | 5 | -5.1941091 | 0.84060576E-04 | -4.4436429 | 0.63227810E-01 |
75 | 4 | 33.018541 | 0.68839572E-03 | 21.449658 | -0.42233114 |
76 | 3 | -111.25962 | 0.15017871E-02 | -55.642450 | 1.5156770 |
77 | 2 | 197.16434 | 0.84550337E-03 | 77.891725 | -2.9012438 |
78 | 1 | -171.17681 | 0.90334265E-04 | -55.259577 | 2.7458027 |
79 | 0 | 57.057407 | 0.51475124E-06 | 15.557826 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9711E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9733E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7029E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7047E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7604E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7618E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6225E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6233E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0211E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1665E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7448E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8708E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7958E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9006E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6441E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6991E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1690 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5323E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1920 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.7001E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1162 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6850E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7407E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6489E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0293E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2095E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7538E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9179E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8031E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9288E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6446E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7007E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9709E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9733E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7026E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7048E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7603E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7619E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6224E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6232E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1587E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5280E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9523E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3690E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4722E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6137E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4838E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5217E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.0030E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3903E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6810E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1426E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6647E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7667E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9359E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8463E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0464E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1548E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8060E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8851E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4282E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4598E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4839E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5223E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7816E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7838E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3613E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3631E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0808E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0822E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6225E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6233E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8311E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9573E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4023E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5035E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1147E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1901E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6447E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7008E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5023E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3766E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4554E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8016E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1047E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2079E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7407E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6484E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8288E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9561E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3991E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4981E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1090E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1723E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6441E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6992E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7815E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7836E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3612E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3629E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0807E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0818E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6224E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6232E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3693E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4822E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9508E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0323E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9114E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9403E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4840E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5224E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8213E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9167E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1982E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5470E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7098E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3837E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9359E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8463E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4561E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7262E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0647E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3543E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9525E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0786E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4837E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5217E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1697 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1177 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1874 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1324 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1291 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.9209E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.8052E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.8715E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.3178E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.8708E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.9604E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.5790E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.8841E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.0631E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9539E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9044E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5810E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.7169E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.3959E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.9319E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0121E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1882E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8053E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8710E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.9814E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.2179E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2823E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.7563E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8143E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.5550E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9539E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9044E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1698 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1179 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1875 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1327 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1293 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.9380E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.8177E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.8779E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.3238E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.8784E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.9673E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.5864E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.8962E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.0718E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9663E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9108E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5814E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.7212E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.3966E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.9353E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0185E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1922E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8177E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8774E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.9853E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.2240E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2867E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.7618E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8247E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.5624E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9663E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9108E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 66132.67601 | 66132.67601 | 4.88149 | 4.88149 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | -16.30000 | 9.24091E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72257.94588 | 72257.94588 | 5.33412 | 5.33412 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 677237.74171 | 677237.74171 | 49.97874 | 49.97874 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 263495.25924 | 263495.25924 | 11.38877 | 11.38877 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 67173.38005 | 67173.38005 | 4.95734 | 4.95734 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 63171.51598 | 63171.51598 | 2.75410 | 2.75410 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12205.97799 | 12205.97799 | 0.90969 | 0.90969 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 10308.29106 | 10308.29106 | 0.44998 | 0.44998 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 16900.57061 | 16900.57061 | 1.25956 | 1.25956 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 7069.01127 | 7069.01127 | 0.30865 | 0.30865 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 19222.45009 | 19222.45009 | 1.43261 | 1.43261 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.99000 | 1.33664E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 11734.66344 | 11734.66344 | 0.51249 | 0.51249 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20713.67755 | 20713.67755 | 1.54374 | 1.54374 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 5432.67152 | 5432.67152 | 0.23692 | 0.23692 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 113903.78786 | 113903.78786 | 8.48935 | 8.48935 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 164840.39273 | 164840.39273 | 7.20723 | 7.20723 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 180849.50530 | 180849.50530 | 13.47870 | 13.47870 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.71200 | 1.33588E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 108014.37299 | 108014.37299 | 4.72286 | 4.72286 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 190970.81578 | 190970.81578 | 14.23312 | 14.23312 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 164841.34692 | 164841.34692 | 7.20727 | 7.20727 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 189868.04315 | 189868.04315 | 14.15084 | 14.15084 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 28.68800 | 1.33641E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 104635.97371 | 104635.97371 | 4.57476 | 4.57476 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 12991.21245 | 12991.21245 | 0.96826 | 0.96826 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 20935.60944 | 20935.60944 | 0.91587 | 0.91587 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 18237.70986 | 18237.70986 | 1.35927 | 1.35927 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 13665.02805 | 13665.02805 | 0.59782 | 0.59782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 20599.89151 | 20599.89151 | 1.53533 | 1.53533 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 20935.78177 | 20935.78177 | 0.91588 | 0.91588 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 20039.02540 | 20039.02540 | 1.49352 | 1.49352 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 13458.04602 | 13458.04602 | 0.58875 | 0.58875 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8325.48948 | 8325.48948 | 0.48939 | 0.48939 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 79858.15873 | 79858.15873 | 4.69428 | 4.69428 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8123.46891 | 8123.46891 | 0.47752 | 0.47752 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370057.15470 | 425565.72791 | 21.75247 | 25.01534 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 21.83700 | 1.33520E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 10:10:00 | -16.30000 | 9.24091E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 130326.05 | 8.95804 | 8.95804 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 70404.83 | 2.58586 | 2.58586 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1195504.87 | 83.33310 | 83.33310 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 694665.63 | 35.10088 | 35.10088 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 136488.22 | 9.20405 | 9.20405 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 68720.09 | 5.77242 | 5.77242 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
7 | CAV_BAS | Cooling | Sensible | 65417.36 | 4.88149 | 4.88149 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 79706.12 | 1.20016 | 1.20016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 419843.59 | 25.01553 | 25.01553 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 22473.72 | 0.33839 | 0.33839 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8187.61 | 0.48939 | 0.48939 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1038.19 | 1.56323E-002 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78531.86 | 4.69428 | 4.69428 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 10381.93 | 0.15632 | 0.15632 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7990.80 | 0.47752 | 0.47752 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1038.19 | 1.56323E-002 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 4.88149 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.43387 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.33412 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35658 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30300 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61624 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95088 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06848E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.47045E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61624 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15864.87947 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.47045E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 442.79037 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 49.97874 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38057 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32300 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.14313 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00113E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.23028E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.14313 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 421955.19766 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.23028E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 14627.03776 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.95734 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38368 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32600 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61609 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.93008E-004 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.97325E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.75410 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 90205.60876 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97325E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3510.23251 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90969 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26253 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22300 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20286 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70008 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45127E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.22029E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.44998 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14721.30219 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.22029E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 572.43121 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25956 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12219 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10400 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13099 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32584 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.11811E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.20855E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30865 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10096.20321 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.20855E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 392.55149 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43261 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16671 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14200 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20343 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44455 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.28546E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.66665E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51249 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16761.80591 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.66665E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 651.66229 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.54374 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.96963E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.50000E-002 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13122 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.82161E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69641E-004 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23692 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7755.02275 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69641E-004 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 301.65740 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.48935 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28132 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23900 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02895 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75018 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35434E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.15213E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.20723 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 235525.80499 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.15213E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9151.75028 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.47870 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30449 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33672E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.37605E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.72286 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 154333.56538 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.37605E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5996.75842 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.23312 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16780 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14300 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03534 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44746 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27062E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.15216E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.20727 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 235527.16547 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.15216E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9151.80333 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.15084 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10876 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.20000E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30188 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.50311E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.27035E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.57476 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 149501.38255 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.27035E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5809.18419 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96826 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24665 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20333 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65773 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54470E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.54460E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.91587 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29918.13782 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.54460E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1162.22545 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.35927 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11323 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.60000E-002 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13049 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30194 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36495E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.27178E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59782 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19528.11743 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.27178E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 758.59476 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.53533 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15555 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13200 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20266 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41481 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44932E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.54465E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.91588 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29918.38392 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.54465E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1162.23503 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.49352 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10305 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.80000E-002 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13143 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.69729E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.20703E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58875 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19232.11682 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.20703E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 747.10286 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48939 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.69428 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47752 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 25.01534 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.23986 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28474 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.47973 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.58586 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.95804 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.95804 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.28866 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 50.16537 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.81673 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 100.33075 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 35.10088 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 83.33310 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 83.33310 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.42121 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.15686 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28401 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.31372 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.77242 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.20405 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.20405 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.62716 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.88149 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.88149 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 4.88149 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.24586 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 25.01534 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 25.01534 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.01534 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 25.01534 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 25.01553 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 25.01553 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48939 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48939 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48939 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48939 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48939 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.48939 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.69428 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.69428 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.69428 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.69428 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.69428 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.69428 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47752 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47752 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47752 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47752 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47752 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.47752 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.95804 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 83.33310 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.20405 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 4.88149 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 25.01553 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.48939 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.69428 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.47752 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.95804 |
289 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.46547 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.89893 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.93361E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 194762.33983 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.57018E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.95804 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 71102.94162 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55538E-003 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1400.10959 |
301 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.95804 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.57018E-003 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.54893E-005 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.55538E-003 |
305 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 83.33310 |
306 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 20.30600 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.61671 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.89950 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.00977E-002 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1867793.92311 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.34187E-002 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 83.33310 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 661872.64589 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44785E-002 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 13029.30799 |
318 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 83.33310 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.34187E-002 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.91431E-006 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.44785E-002 |
322 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.20405 |
323 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.39082 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.89881 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.90007E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 198363.47088 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.67317E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.20405 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 65199.11079 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42623E-003 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1315.16328 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.20405 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.67317E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.39373E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.42623E-003 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.88149 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.38567 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.88773 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.02408E-002 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 110215.30242 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.15214E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.88149 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 253410.45311 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.18750E-003 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3855.77237 |
353 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 4.88149 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.15214E-003 |
355 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.51069E-004 |
356 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.18750E-003 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 25.01553 |
358 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.01553 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 495536.66716 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 348941.98029 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.21357E-002 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 25.01553 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 25.01553 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 25.01553 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 25.01553 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 495536.66716 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 495536.66716 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 22473.71574 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
371 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 25.01553 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.01553 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 495536.66716 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.21357E-002 |
375 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 22473.71574 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.14296E-004 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48939 |
381 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48939 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9596.72423 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6786.31627 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35023E-004 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48939 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48939 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48939 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48939 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9596.72423 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9596.72423 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1038.19256 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
394 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48939 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48939 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9596.72423 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35023E-004 |
398 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1038.19256 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.69428 |
400 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.69428 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 92173.41298 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 65133.20731 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25732E-003 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.69428 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.69428 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.69428 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.69428 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 92173.41298 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 92173.41298 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 10381.92564 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
413 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.69428 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.69428 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 92173.41298 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25732E-003 |
417 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 10381.92564 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47752 |
419 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47752 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9373.65471 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6624.81424 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29560E-004 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47752 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47752 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47752 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47752 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9373.65471 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9373.65471 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1038.19256 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
432 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47752 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47752 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9373.65471 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29560E-004 |
436 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1038.19256 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 6.78142E-002 |
438 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 10962.35689 |
439 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 6.78142E-002 |
440 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 8.13770 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 6.78142E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 6.78142E-002 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 284650.06438 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
445 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.13849E-002 |
446 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 6.16618 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.13849E-002 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 15321.64814 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
450 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2349019.39263 |
451 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2349019.39000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.13849E-002 |
453 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 6.78142E-002 |
454 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 8.13770 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.39071E-002 |
456 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3794.80468 |
457 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.39071E-002 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3794.80468 |
459 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.78142E-002 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.40374E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1190124.16106 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1190123.79500 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.99287E-002 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.78142E-002 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.40374E-002 |
466 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1190124.16106 |
467 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1190123.79500 |
468 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.99287E-002 |
469 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.48576E-002 |
470 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.78291 |
471 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.48576E-002 |
472 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3751.90313 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.48576E-002 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 147524.60232 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 74681.50058 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 73762.30116 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 44808.90035 |
479 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 612004.31967 |
480 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 599658.79000 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.48576E-002 |
482 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
483 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
484 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
486 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11986 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 14.38289 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11986 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 29380.23159 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 42.82706 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1424658.96208 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.56541 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 178082.37026 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 42.82706 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1424658.96208 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.56541 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 178082.37026 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.17175E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.17175E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 22085.86 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 587616.28 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 125538.62 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 20487.61 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 14050.87 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 23327.39 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10792.64 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 327781.69 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 214786.32 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 327783.58 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 208061.33 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 41637.17 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 27177.34 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 41637.51 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 26765.40 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 67215.99 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 625489.90 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 63830.55 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 139466.64 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 226448.00 | 157327.27 | 69120.73 | 0.69 | 37216.89 | 377.47 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2134787.33 | 1475157.81 | 659629.52 | 0.69 | 347516.92 | 3524.71 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 231806.96 | 161298.39 | 70508.57 | 0.70 | 38233.63 | 387.79 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 125677.72 | 86682.86 | 38994.86 | 0.69 | 20538.20 | 208.31 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 8.97 | 30.62 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 8.97 | 30.62 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 8.2815466011E-004 | 1.2970841365E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.1924081519E-003 | 5.9852157210E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.3170574561E-002 | 2.1684403510E-002 | Pass | Pass | 0.4541694073 | 0.4976560102 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.4163094161E-002 | 3.9842102368E-002 | Pass | Pass | 38.0180965618 | 147.6882096510 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.8541568749E-002 | 1.4903897710E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.8615788105E-002 | 1.5022953462E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.2012217138E-002 | 1.9529832842E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.9758316220E-002 | 1.7442503041E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2523389426 | 0.2324833288 | Pass | Pass | 48.8222955180 | 161.1030504593 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2560665348 | 0.2372731648 | Pass | Pass | 49.7211272202 | 160.9397398970 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2062228468 | 0.2131114382 | Pass | Pass | 47.5585129057 | 152.6832319607 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1278941202 | 0.1441249137 | Pass | Pass | 73.5946310944 | 577.0801585379 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3607892666 | 0.3564976612 | Pass | Pass | 17.4634604444 | 57.0264265018 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4000482017 | 0.3783874611 | Pass | Pass | 52.8531674572 | 113.4142451545 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3623087265 | 0.3560310810 | Pass | Pass | 57.0631130320 | 130.1148420382 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2850989757 | 0.2882421441 | Pass | Pass | 58.0127482127 | 157.9063480817 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.6340975682E-003 | 2.9244129016E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.0697570950E-002 | 1.9662366207E-002 | Pass | Pass | 0.4583185024 | 0.4601729564 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.1789769820E-002 | 6.1866989251E-002 | Pass | Pass | 0.4896753658 | 0.4753706366 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.6921175215E-006 | 5.4930270169E-006 | Pass | Pass | 3.3969341484E-003 | 2.6005405080E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.1956360898E-003 | 4.1612555116E-003 | Pass | Pass | 1.7107922164E-003 | 1.5625660163E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.7238453272E-003 | 6.5421449327E-003 | Pass | Pass | 2.7930312808E-003 | 2.5219618633E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.9605131978E-006 | 2.3606330492E-006 | Pass | Pass | 4.1499184547E-005 | 1.0846888605E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6641.23 | 148.32 | 0.00 | 25844.69 | 9730.99 | 42365.22 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
North Total or Average | 1390.74 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.062 | 0.379 | 0.417 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 116.04 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 1042.11 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.20 | 0.0000 | Y | 7.55 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.09 | 0.0000 | Y | 4.84 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.97 | 0.0000 | Y | 7.47 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.06 | 0.0000 | Y | 4.83 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.16 | 0.0000 | Y | 75.34 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.06 | 0.0000 | Y | 48.33 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.95 | 0.0000 | Y | 74.61 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.03 | 0.0000 | Y | 48.25 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.16 | 0.0000 | Y | 7.53 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.06 | 0.0000 | Y | 4.83 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.95 | 0.0000 | Y | 7.46 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.03 | 0.0000 | Y | 4.82 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.66 | 0.0000 | Y | 32.85 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 16.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 540.54 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 42.04 | 42.04 | 102.22 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.67 | 62.85 | 10.85 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.67 | 47.45 | 153.34 | |
Exterior Lighting Total | 31088.59 | 266.41 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2363831.73 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2349019.39 | 0.94 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1190123.79 | 5.91 | 1183251.42 | 5.88 | 8.97 | 30.62 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1190123.79 | 5.91 | 1183251.42 | 5.88 | 8.97 | 30.62 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 614808.78 | |||||
CENTRAL BOILER | Boiler:HotWater | 599658.79 | 0.94 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1424658.96 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1424658.96 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 194762.34 | 226448.00 | 157327.27 | 69120.73 | 0.69 | - | 37216.89 | 377.47 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1867793.92 | 2134787.33 | 1475157.81 | 659629.52 | 0.69 | - | 347516.92 | 3524.71 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 198363.47 | 231806.96 | 161298.39 | 70508.57 | 0.70 | - | 38233.63 | 387.79 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 110215.30 | 125677.72 | 86682.86 | 38994.86 | 0.69 | - | 20538.20 | 208.31 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 495536.67 | 348941.98 | 146594.69 | 0.70 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9596.72 | 6786.32 | 2810.41 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 92173.41 | 65133.21 | 27040.21 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9373.65 | 6624.81 | 2748.84 | 0.71 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 15864.88 | 22085.86 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 421955.20 | 587616.28 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 90205.61 | 125538.62 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14721.30 | 20487.61 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 10096.20 | 14050.87 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16761.81 | 23327.39 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7755.02 | 10792.64 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 235525.80 | 327781.69 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 154333.57 | 214786.32 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 235527.17 | 327783.58 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 149501.38 | 208061.33 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 29918.14 | 41637.17 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 19528.12 | 27177.34 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29918.38 | 41637.51 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 19232.12 | 26765.40 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 71102.94 | 67215.99 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 661872.65 | 625489.90 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 65199.11 | 63830.55 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 139466.64 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 495536.67 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9596.72 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 92173.41 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9373.65 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 22473.72 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1038.19 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 10381.93 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1038.19 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 8.96 | 20457.72 | 2283.73 | 1.00 | 1.12 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 83.33 | 190310.11 | 2283.73 | 1.00 | 1.07 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.20 | 21019.54 | 2283.73 | 1.00 | 1.12 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.88 | 11219.92 | 2298.46 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 25.02 | 41256.79 | 1649.25 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 548.17 | 1120.11 | 1.00 | 1.62 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.69 | 5258.10 | 1120.11 | 1.00 | 1.16 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 534.87 | 1120.11 | 1.00 | 1.63 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.067814 | 10962.36 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.051385 | 15321.65 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.033907 | 3794.80 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.033907 | 3794.80 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014858 | 3751.90 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.119857 | 29380.23 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 66132.68 | 66132.68 | 23.79 | 4.881 | 4.881 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00903 | 23.42 | 0.01335 | 1.200 | 0.00 |
CORE_BOTTOM | 72257.95 | 72257.95 | 28.95 | 5.334 | 5.334 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 23.42 | 0.01335 | 1.078 | 0.00 |
CORE_MID | 677237.74 | 677237.74 | 271.32 | 49.979 | 49.979 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 23.42 | 0.01335 | 10.778 | 0.00 |
CORE_TOP | 67173.38 | 67173.38 | 26.91 | 4.957 | 4.957 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00897 | 23.42 | 0.01335 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12205.98 | 12205.98 | 38.95 | 0.910 | 0.910 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00888 | 30.30 | 0.01337 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 16900.57 | 16900.57 | 83.68 | 1.260 | 1.260 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00868 | 25.18 | 0.01336 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 19222.45 | 19222.45 | 61.33 | 1.433 | 1.433 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00875 | 29.99 | 0.01337 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20713.68 | 20713.68 | 102.56 | 1.544 | 1.544 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00865 | 28.84 | 0.01336 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 113903.79 | 113903.79 | 363.43 | 8.489 | 8.489 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00901 | 30.30 | 0.01337 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 180849.51 | 180849.51 | 895.40 | 13.479 | 13.479 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00871 | 25.71 | 0.01336 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 190970.82 | 190970.82 | 609.31 | 14.233 | 14.233 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00881 | 30.07 | 0.01337 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 189868.04 | 189868.04 | 940.06 | 14.151 | 14.151 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00870 | 28.69 | 0.01336 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12991.21 | 12991.21 | 41.45 | 0.968 | 0.968 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00898 | 30.30 | 0.01337 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 18237.71 | 18237.71 | 90.30 | 1.359 | 1.359 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00873 | 25.98 | 0.01336 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20599.89 | 20599.89 | 65.73 | 1.535 | 1.535 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00881 | 30.14 | 0.01337 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 20039.03 | 20039.03 | 99.22 | 1.494 | 1.494 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00871 | 28.84 | 0.01336 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8325.49 | 8325.49 | 229.97 | 0.489 | 0.489 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 26.50 | 0.01336 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 79858.16 | 79858.16 | 2205.86 | 4.694 | 4.694 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 26.50 | 0.01336 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8123.47 | 8123.47 | 224.39 | 0.478 | 0.478 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 26.50 | 0.01336 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370057.15 | 425565.73 | 543.04 | 21.752 | 25.015 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 21.84 | 0.01335 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | 21.00 | 23.41 | 0.00092 | -16.30 | 0.00092 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 17.60 | 21.08 | 0.00092 | -16.30 | 0.00092 | 1.078 | 0.00 |
CORE_MID | 263495.26 | 263495.26 | 105.56 | 11.389 | 11.389 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 10.778 | 0.00 |
CORE_TOP | 63171.52 | 63171.52 | 25.31 | 2.754 | 2.754 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 10308.29 | 10308.29 | 32.89 | 0.450 | 0.450 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00760 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 7069.01 | 7069.01 | 35.00 | 0.309 | 0.309 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 11734.66 | 11734.66 | 37.44 | 0.512 | 0.512 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 5432.67 | 5432.67 | 26.90 | 0.237 | 0.237 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00737 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 164840.39 | 164840.39 | 525.95 | 7.207 | 7.207 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -16.30 | 0.00092 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 108014.37 | 108014.37 | 534.79 | 4.723 | 4.723 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -16.30 | 0.00092 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 164841.35 | 164841.35 | 525.94 | 7.207 | 7.207 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -16.30 | 0.00092 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 104635.97 | 104635.97 | 518.06 | 4.575 | 4.575 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -16.30 | 0.00092 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 20935.61 | 20935.61 | 66.80 | 0.916 | 0.916 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13665.03 | 13665.03 | 67.66 | 0.598 | 0.598 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20935.78 | 20935.78 | 66.80 | 0.916 | 0.916 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 13458.05 | 13458.05 | 66.63 | 0.589 | 0.589 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 25.34 | 0.00724 | -16.30 | 0.00092 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.86 | 0.00163 | -16.30 | 0.00092 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 20.82 | 0.00148 | -16.30 | 0.00092 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 10:10:00 | 18.00 | 27.00 | 0.00850 | -16.30 | 0.00092 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.96 | 8.96 | 2.59 | 2.59 | 8.9580 | 2.5859 | 8.9580 | 0.2887 | 0.3000 |
VAV_MID WITH REHEAT | 83.33 | 83.33 | 35.10 | 35.10 | 83.3331 | 35.1009 | 83.3331 | 0.4212 | 0.3000 |
VAV_TOP WITH REHEAT | 9.20 | 9.20 | 5.77 | 5.77 | 9.2040 | 5.7724 | 9.2040 | 0.6272 | 0.3000 |
CAV_BAS | 4.88 | 4.88 | 1.20 | 1.20 | 4.8815 | 1.2002 | 4.8815 | 0.2459 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.02 | 25.02 | 0.34 | 0.34 | 25.0155 | 25.0153 | 25.0155 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.49 | 0.49 | 0.02 | 0.02 | 0.4894 | 0.4894 | 0.4894 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.69 | 4.69 | 0.16 | 0.16 | 4.6943 | 4.6943 | 4.6943 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.48 | 0.48 | 0.02 | 0.02 | 0.4775 | 0.4775 | 0.4775 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 15864.879 | 15864.879 | 1.616237 | 0.00034704 | 442.790 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 15864.88 | 15864.88 | 1.616237 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 0.00 | 0.00 | 15892.11 | 15892.11 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 421955.198 | 421955.198 | 16.143132 | 0.00923028 | 14627.038 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 421955.20 | 421955.20 | 16.143132 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 263495.26 | 0.00 | 422960.30 | 422960.30 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 90205.609 | 90205.609 | 2.754103 | 0.00197325 | 3510.233 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 90205.61 | 90205.61 | 2.754103 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 63171.52 | 0.00 | 90397.67 | 90397.67 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 14721.302 | 14721.302 | 0.449981 | 0.00032203 | 572.431 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14721.30 | 14721.30 | 0.449981 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00760171 | 47.9429 | 10308.29 | 0.00 | 14752.65 | 14752.65 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10096.203 | 10096.203 | 0.308650 | 0.00022085 | 392.551 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10096.20 | 10096.20 | 0.308650 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00763862 | 48.1726 | 7069.01 | 0.00 | 10117.70 | 10117.70 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 16761.806 | 16761.806 | 0.512490 | 0.00036666 | 651.662 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16761.81 | 16761.81 | 0.512490 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00770319 | 48.5743 | 11734.66 | 0.00 | 16797.50 | 16797.50 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7755.023 | 7755.023 | 0.236916 | 0.00016964 | 301.657 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7755.02 | 7755.02 | 0.236916 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00737072 | 46.5044 | 5432.67 | 0.00 | 7771.54 | 7771.54 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 235525.805 | 235525.805 | 7.207228 | 0.00515213 | 9151.750 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 235525.80 | 235525.80 | 7.207228 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00764258 | 48.1982 | 164840.39 | 0.00 | 236027.44 | 236027.44 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 154333.565 | 154333.565 | 4.722858 | 0.00337605 | 5996.758 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 154333.57 | 154333.57 | 4.722858 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00763791 | 48.1692 | 108014.37 | 0.00 | 154662.27 | 154662.27 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 235527.165 | 235527.165 | 7.207270 | 0.00515216 | 9151.803 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 235527.17 | 235527.17 | 7.207270 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00764258 | 48.1982 | 164841.35 | 0.00 | 236028.80 | 236028.80 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 149501.383 | 149501.383 | 4.574761 | 0.00327035 | 5809.184 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 149501.38 | 149501.38 | 4.574761 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00762404 | 48.0828 | 104635.97 | 0.00 | 149819.80 | 149819.80 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 29918.138 | 29918.138 | 0.915871 | 0.00065446 | 1162.225 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29918.14 | 29918.14 | 0.915871 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00766003 | 48.3075 | 20935.61 | 0.00 | 29981.86 | 29981.86 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 19528.117 | 19528.117 | 0.597820 | 0.00042718 | 758.595 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19528.12 | 19528.12 | 0.597820 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765329 | 48.2656 | 13665.03 | 0.00 | 19569.71 | 19569.71 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 29918.384 | 29918.384 | 0.915879 | 0.00065447 | 1162.235 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29918.38 | 29918.38 | 0.915879 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00766003 | 48.3075 | 20935.78 | 0.00 | 29982.11 | 29982.11 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 19232.117 | 19232.117 | 0.588750 | 0.00042070 | 747.103 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19232.12 | 19232.12 | 0.588750 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00764791 | 48.2322 | 13458.05 | 0.00 | 19273.08 | 19273.08 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 194762.340 | -999.000 | 8.958038 | 0.00557018 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 194762.34 | 155664.49 | 8.958038 | 25.47 | 17.82 | 0.00993361 | 10.90 | 10.90 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 22.6668 | 24.00 | 0.00889193 | 46.6387 | 117042.75 | 0.00 | 198423.74 | 153046.71 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 71102.942 | 71102.942 | 2.687411 | 0.00155538 | 1400.110 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 71102.94 | 71102.94 | 2.687411 | -9.63 | -9.63 | 0.00177868 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 75.5560 | 21.03 | 0.00550939 | 34.7883 | 30243.83 | 0.00 | 58513.90 | 58513.90 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1867793.923 | -999.000 | 83.333098 | 0.05341867 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1867793.92 | 1462632.68 | 83.333098 | 25.62 | 18.00 | 0.01009771 | 10.90 | 10.90 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 24.3673 | 24.00 | 0.00896808 | 47.0329 | 1060967.29 | 0.00 | 1902082.91 | 1439580.45 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 661872.646 | 661872.646 | 24.999929 | 0.01447848 | 13029.308 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 661872.65 | 661872.65 | 24.999929 | -9.64 | -9.64 | 0.00215689 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 81.2242 | 18.09 | 0.00737633 | 55.7590 | 269336.41 | 0.00 | 544571.40 | 544571.40 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 198363.471 | -999.000 | 9.204049 | 0.00567317 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 198363.47 | 159127.53 | 9.204049 | 25.39 | 17.76 | 0.00990007 | 10.90 | 10.90 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 22.0609 | 24.00 | 0.00891677 | 46.7677 | 123301.16 | 0.00 | 202119.79 | 156413.68 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 65199.111 | 65199.111 | 2.761215 | 0.00142623 | 1315.163 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 65199.11 | 65199.11 | 2.761215 | -7.22 | -7.22 | 0.00267418 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 73.5365 | 17.39 | 0.00725975 | 57.3550 | 39255.04 | 0.00 | 55585.69 | 55585.69 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 110215.302 | -999.000 | 4.881491 | 0.00315214 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 110215.30 | 84346.74 | 4.881491 | 25.39 | 18.03 | 0.01024084 | 10.89 | 10.89 | 0.00850000 | 29.09 | 0.01336481 | 21.48 | 24.5859 | 24.00 | 0.00907143 | 47.5667 | 59122.13 | 0.00 | 112234.24 | 83060.79 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.116633 | 0.00218750 | 3855.772 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.116633 | -4.01 | -7.27 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 38.5081 | 23.51 | 0.00092409 | 5.0556 | 0.00 | 0.00 | 99924.95 | 99924.95 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 495536.667 | 348941.980 | 25.015531 | 0.01213566 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 460208.66 | 453126.58 | -999.0 | 28.47 | 17.75 | 0.00860779 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | -999.0000 | 27.00 | 0.00854246 | 37.5170 | 369651.02 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9596.724 | 6786.316 | 0.489392 | 0.00023502 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 8896.46 | 8589.17 | -999.0 | 27.95 | 17.68 | 0.00873941 | 12.80 | 11.87 | 0.00850000 | 26.50 | 0.01336023 | 20.72 | -999.0000 | 27.00 | 0.00858694 | 37.7073 | 8325.49 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92173.413 | 65133.207 | 4.694276 | 0.00225732 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 85465.90 | 82394.60 | -999.0 | 27.95 | 17.69 | 0.00874943 | 12.80 | 11.87 | 0.00850000 | 26.50 | 0.01336023 | 20.72 | -999.0000 | 27.00 | 0.00859060 | 37.7233 | 79858.16 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9373.655 | 6624.814 | 0.477518 | 0.00022956 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 8691.18 | 8384.08 | -999.0 | 27.96 | 17.69 | 0.00874519 | 12.80 | 11.87 | 0.00850000 | 26.67 | 0.01336053 | 20.77 | -999.0000 | 27.00 | 0.00858896 | 37.7162 | 8122.40 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 495536.667 | 495536.667 | 25.015531 | 0.01213566 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 495536.67 | 495536.67 | 25.015531 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 1.3527 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9596.724 | 9596.724 | 0.489392 | 0.00023502 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9596.72 | 9596.72 | 0.489392 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.1942 | 25.93 | 0.00723647 | 33.9216 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92173.413 | 92173.413 | 4.694276 | 0.00225732 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 92173.41 | 92173.41 | 4.694276 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.3301 | 23.99 | 0.00163279 | 8.6662 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9373.655 | 9373.655 | 0.477518 | 0.00022956 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9373.65 | 9373.65 | 0.477518 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.2737 | 22.79 | 0.00147928 | 8.4459 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 22473.716 | 22473.716 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 22473.72 | 22473.72 | 25.015531 | -0.22 | -0.22 | 0.00839752 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 1.3527 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1038.19 | 1038.19 | 0.489392 | -0.52 | -0.52 | 0.00703484 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.1942 | 25.93 | 0.00723647 | 33.9216 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 10381.926 | 10381.926 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10381.93 | 10381.93 | 4.694276 | -0.54 | -3.87 | 0.00160919 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.3301 | 23.99 | 0.00163279 | 8.6662 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1038.19 | 1038.19 | 0.477518 | -0.53 | -4.12 | 0.00146111 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.2737 | 22.79 | 0.00147928 | 8.4459 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 15864.879 | 15864.879 | 1.616237 | 0.00034704 | 442.790 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 0.6621 | 0.675383 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | Sensible | 15864.88 | 15864.88 | 1.0000 | 1.89734176 | 1.616237 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.34700928 | 60.00 | 48.89 | 11.11 | 0.000 | 15864.88 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 0.00 | 0.00 | 15892.11 | 15892.11 | 1.89734176 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 421955.198 | 421955.198 | 16.143132 | 0.00923028 | 14627.038 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 17.6087 | 17.963036 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 421955.20 | 421955.20 | 1.0000 | 18.95083152 | 16.143132 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 9.22934009 | 60.00 | 48.89 | 11.11 | 0.000 | 421955.20 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.82 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 263495.26 | 0.00 | 422960.30 | 422960.30 | 18.95083152 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.69 | 19.56 | 0.00800000 | 55378.7 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 90205.609 | 90205.609 | 2.754103 | 0.00197325 | 3510.233 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 3.7644 | 3.840139 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 90205.61 | 90205.61 | 1.0000 | 3.23311080 | 2.754103 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.97304891 | 60.00 | 48.89 | 11.11 | 0.000 | 90205.61 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 63171.52 | 0.00 | 90397.67 | 90397.67 | 3.23311080 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61019.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14721.302 | 14721.302 | 0.449981 | 0.00032203 | 572.431 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 0.6143 | 0.626700 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14721.30 | 14721.30 | 1.0000 | 0.52824442 | 0.449981 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.32199604 | 60.00 | 48.89 | 11.11 | 0.000 | 14721.30 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00760171 | 21.00 | 0.00760171 | 47.9429 | 10308.29 | 0.00 | 14752.65 | 14752.65 | 0.52824442 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60987.5 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10096.203 | 10096.203 | 0.308650 | 0.00022085 | 392.551 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 0.4213 | 0.429805 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10096.20 | 10096.20 | 1.0000 | 0.36233166 | 0.308650 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.22083220 | 60.00 | 48.89 | 11.11 | 0.000 | 10096.20 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00763862 | 21.00 | 0.00763862 | 48.1726 | 7069.01 | 0.00 | 10117.70 | 10117.70 | 0.36233166 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.7 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16761.806 | 16761.806 | 0.512490 | 0.00036666 | 651.662 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 0.6995 | 0.713566 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16761.81 | 16761.81 | 1.0000 | 0.60162492 | 0.512490 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.36662757 | 60.00 | 48.89 | 11.11 | 0.000 | 16761.81 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00770319 | 21.00 | 0.00770319 | 48.5743 | 11734.66 | 0.00 | 16797.50 | 16797.50 | 0.60162492 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.1 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7755.023 | 7755.023 | 0.236916 | 0.00016964 | 301.657 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 0.3236 | 0.330139 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7755.02 | 7755.02 | 1.0000 | 0.27812137 | 0.236916 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.16962403 | 60.00 | 48.89 | 11.11 | 0.000 | 7755.02 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00737072 | 21.00 | 0.00737072 | 46.5044 | 5432.67 | 0.00 | 7771.54 | 7771.54 | 0.27812137 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 235525.805 | 235525.805 | 7.207228 | 0.00515213 | 9151.750 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 9.8288 | 10.026559 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 235525.80 | 235525.80 | 1.0000 | 8.46074785 | 7.207228 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 5.15160796 | 60.00 | 48.89 | 11.11 | 0.000 | 235525.80 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00764258 | 21.00 | 0.00764258 | 48.1982 | 164840.39 | 0.00 | 236027.44 | 236027.44 | 8.46074785 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60956.6 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 154333.565 | 154333.565 | 4.722858 | 0.00337605 | 5996.758 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 6.4405 | 6.570127 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 154333.57 | 154333.57 | 1.0000 | 5.54428256 | 4.722858 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 3.37570664 | 60.00 | 48.89 | 11.11 | 0.000 | 154333.57 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00763791 | 21.00 | 0.00763791 | 48.1692 | 108014.37 | 0.00 | 154662.27 | 154662.27 | 5.54428256 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60955.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 235527.165 | 235527.165 | 7.207270 | 0.00515216 | 9151.803 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 9.8288 | 10.026616 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 235527.17 | 235527.17 | 1.0000 | 8.46079645 | 7.207270 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 5.15163772 | 60.00 | 48.89 | 11.11 | 0.000 | 235527.17 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00764258 | 21.00 | 0.00764258 | 48.1982 | 164841.35 | 0.00 | 236028.80 | 236028.80 | 8.46079645 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60956.6 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 149501.383 | 149501.383 | 4.574761 | 0.00327035 | 5809.184 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 6.2389 | 6.364417 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 149501.38 | 149501.38 | 1.0000 | 5.37042737 | 4.574761 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 3.27001329 | 60.00 | 48.89 | 11.11 | 0.000 | 149501.38 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00762404 | 21.00 | 0.00762404 | 48.0828 | 104635.97 | 0.00 | 149819.80 | 149819.80 | 5.37042737 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60957.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29918.138 | 29918.138 | 0.915871 | 0.00065446 | 1162.225 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 1.2485 | 1.273644 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29918.14 | 29918.14 | 1.0000 | 1.07516463 | 0.915871 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.65439333 | 60.00 | 48.89 | 11.11 | 0.000 | 29918.14 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00766003 | 21.00 | 0.00766003 | 48.3075 | 20935.61 | 0.00 | 29981.86 | 29981.86 | 1.07516463 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60945.7 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19528.117 | 19528.117 | 0.597820 | 0.00042718 | 758.595 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 0.8149 | 0.831331 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19528.12 | 19528.12 | 1.0000 | 0.70179562 | 0.597820 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.42713453 | 60.00 | 48.89 | 11.11 | 0.000 | 19528.12 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765329 | 21.00 | 0.00765329 | 48.2656 | 13665.03 | 0.00 | 19569.71 | 19569.71 | 0.70179562 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60945.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29918.384 | 29918.384 | 0.915879 | 0.00065447 | 1162.235 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 1.2485 | 1.273654 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29918.38 | 29918.38 | 1.0000 | 1.07517345 | 0.915879 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.65439872 | 60.00 | 48.89 | 11.11 | 0.000 | 29918.38 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00766003 | 21.00 | 0.00766003 | 48.3075 | 20935.78 | 0.00 | 29982.11 | 29982.11 | 1.07517345 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60945.7 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19232.117 | 19232.117 | 0.588750 | 0.00042070 | 747.103 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 0.8026 | 0.818730 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19232.12 | 19232.12 | 1.0000 | 0.69114854 | 0.588750 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.42066017 | 60.00 | 48.89 | 11.11 | 0.000 | 19232.12 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00764791 | 21.00 | 0.00764791 | 48.2322 | 13458.05 | 0.00 | 19273.08 | 19273.08 | 0.69114854 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60945.4 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 194762.340 | -999.000 | 8.958038 | 0.00557018 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3061 | 1004.8586 | 1.1739 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.958038 | 10.51606699 | 4197.9300 | 999.8980 | 67.80724414 | 15.00 | 6.67 | 8.33 | 2371135.04 | 8.2139 | 8.213886 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 194762.34 | 155664.49 | 1.0000 | 10.51606699 | 8.958038 | 25.47 | 17.82 | 0.00993361 | 50902.3 | 10.90 | 10.90 | 0.00850000 | 32381.9 | 5.56961005 | 6.67 | 15.00 | 8.33 | 20457.719 | 174304.62 | 30.30 | 0.01336696 | 21.83 | 2.03050000 | 22.6668 | 24.00 | 0.00889193 | 24.00 | 0.00889193 | 46.6387 | 117042.75 | 0.00 | 198423.74 | 153046.71 | 10.51606699 | 25.47 | 18.09 | 0.00993361 | 50902.3 | 11.24 | 11.16 | 0.00822255 | 32033.7 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 71102.942 | 71102.942 | 2.687411 | 0.00155538 | 1400.110 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.958038 | 10.51606699 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 2.9672 | 3.026920 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 71102.94 | 71102.94 | 1.0000 | 3.15482010 | 2.687411 | -9.63 | -9.63 | 0.00177868 | -5259.0 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 1.55522016 | 60.00 | 48.89 | 11.11 | 0.000 | 71102.94 | -16.30 | 0.00092409 | -16.30 | 2.03050000 | 75.5560 | 10.99 | 0.00442018 | 21.03 | 0.00550939 | 34.7883 | 30243.83 | 0.00 | 58513.90 | 58513.90 | 3.15482010 | 2.80 | -1.53 | 0.00177868 | 7271.2 | 21.20 | 8.56 | 0.00177868 | 25818.6 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1867793.923 | -999.000 | 83.333098 | 0.05341867 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6111 | 1004.8586 | 1.1739 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 83.333098 | 97.82683306 | 4197.9300 | 999.8980 | 67.80724414 | 15.00 | 6.67 | 8.33 | 2371135.04 | 78.7721 | 78.772145 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1867793.92 | 1462632.68 | 1.0000 | 97.82683306 | 83.333098 | 25.62 | 18.00 | 0.01009771 | 51475.3 | 10.90 | 10.90 | 0.00850000 | 32382.5 | 53.41322051 | 6.67 | 15.00 | 8.33 | 190310.113 | 1677483.81 | 30.30 | 0.01336696 | 21.83 | 20.30600000 | 24.3673 | 24.00 | 0.00896808 | 24.00 | 0.00896808 | 47.0329 | 1060967.29 | 0.00 | 1902082.91 | 1439580.45 | 97.82683306 | 25.62 | 18.27 | 0.01009771 | 51475.3 | 11.24 | 11.16 | 0.00822298 | 32032.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 661872.646 | 661872.646 | 24.999929 | 0.01447848 | 13029.308 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 83.333098 | 97.82683306 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 27.6207 | 28.176551 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 661872.65 | 661872.65 | 1.0000 | 29.34804992 | 24.999929 | -9.64 | -9.64 | 0.00215689 | -4334.6 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 14.47700556 | 60.00 | 48.89 | 11.11 | 0.000 | 661872.65 | -16.30 | 0.00092409 | -16.30 | 20.30600000 | 81.2242 | 19.15 | 0.00748998 | 18.09 | 0.00737633 | 55.7590 | 269336.41 | 0.00 | 544571.40 | 544571.40 | 29.34804992 | 2.80 | -0.94 | 0.00215689 | 8219.0 | 21.19 | 8.99 | 0.00215689 | 26774.6 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 198363.471 | -999.000 | 9.204049 | 0.00567317 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2437 | 1004.8586 | 1.1739 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.204049 | 10.80486575 | 4197.9300 | 999.8980 | 67.80724414 | 15.00 | 6.67 | 8.33 | 2371135.04 | 8.3658 | 8.365760 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 198363.47 | 159127.53 | 1.0000 | 10.80486575 | 9.204049 | 25.39 | 17.76 | 0.00990007 | 50740.5 | 10.90 | 10.90 | 0.00850000 | 32381.8 | 5.67259143 | 6.67 | 15.00 | 8.33 | 21019.542 | 177343.93 | 30.30 | 0.01336696 | 21.83 | 2.03050000 | 22.0609 | 24.00 | 0.00891677 | 24.00 | 0.00891677 | 46.7677 | 123301.16 | 0.00 | 202119.79 | 156413.68 | 10.80486575 | 25.39 | 18.04 | 0.00990007 | 50740.5 | 11.24 | 11.16 | 0.00822267 | 32034.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 65199.111 | 65199.111 | 2.761215 | 0.00142623 | 1315.163 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.204049 | 10.80486575 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 2.7208 | 2.775588 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 65199.11 | 65199.11 | 1.0000 | 3.24145973 | 2.761215 | -7.22 | -7.22 | 0.00267418 | -599.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 1.42608687 | 60.00 | 48.89 | 11.11 | 0.000 | 65199.11 | -16.30 | 0.00092409 | -16.30 | 2.03050000 | 73.5365 | 18.02 | 0.00753731 | 17.39 | 0.00725975 | 57.3550 | 39255.04 | 0.00 | 55585.69 | 55585.69 | 3.24145973 | 2.80 | 0.05 | 0.00267418 | 9515.4 | 19.78 | 8.93 | 0.00267418 | 26663.8 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 110215.302 | -999.000 | 4.881491 | 0.00315214 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8772 | 1004.8586 | 1.1739 | CAV_BAS FAN | Fan:VariableVolume | 4.881491 | 5.73050542 | 4197.9300 | 999.8980 | 67.80724414 | 15.00 | 6.67 | 8.33 | 2371135.04 | 4.6482 | 4.648209 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 110215.30 | 84346.74 | 1.0000 | 5.73050542 | 4.881491 | 25.39 | 18.03 | 0.01024084 | 51603.5 | 10.89 | 10.89 | 0.00850000 | 32370.5 | 3.15182215 | 6.67 | 15.00 | 8.33 | 11219.918 | 98995.38 | 29.09 | 0.01336481 | 21.48 | 1.20015641 | 24.5859 | 24.00 | 0.00907143 | 24.00 | 0.00907143 | 47.5667 | 59122.13 | 0.00 | 112234.24 | 83060.79 | 5.73050542 | 25.39 | 18.31 | 0.01024084 | 51603.5 | 11.23 | 11.16 | 0.00822210 | 32018.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.116633 | 0.00218750 | 3855.772 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | CAV_BAS FAN | Fan:VariableVolume | 4.881491 | 5.73050542 | 4197.9300 | 999.8980 | 51.37962270 | 48.89 | 60.00 | 11.11 | 2396294.34 | 4.1731 | 4.257096 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.116633 | -4.01 | -7.27 | 0.00092409 | -1722.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.18727963 | 60.00 | 48.89 | 11.11 | 0.000 | 100000.00 | -16.30 | 0.00092409 | -16.30 | 1.20015641 | 38.5081 | 0.00 | 0.00092409 | 23.51 | 0.00092409 | 5.0556 | 0.00 | 0.00 | 99924.95 | 99924.95 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 39.98 | 14.58 | 0.00000000 | 40198.8 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 495536.667 | 348941.980 | 25.015531 | 0.01213566 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8414 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 460208.66 | 453126.58 | 0.9287 | -999.0 | -999.0 | 28.47 | 17.75 | 0.00860779 | 50591.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 460208.66 | 30.30 | 0.01336696 | 21.83 | 0.33839277 | -999.0000 | 27.00 | 0.00854246 | 27.00 | 0.00854246 | 37.5170 | 369651.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9596.724 | 6786.316 | 0.489392 | 0.00023502 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0861 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 8896.46 | 8589.17 | 0.9270 | -999.0 | -999.0 | 27.95 | 17.68 | 0.00873941 | 50398.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8896.46 | 26.50 | 0.01336023 | 20.72 | 0.01563234 | -999.0000 | 27.00 | 0.00858694 | 27.00 | 0.00858694 | 37.7073 | 8325.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 92173.413 | 65133.207 | 4.694276 | 0.00225732 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1048 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 85465.90 | 82394.60 | 0.9272 | -999.0 | -999.0 | 27.95 | 17.69 | 0.00874943 | 50423.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85465.90 | 26.50 | 0.01336023 | 20.72 | 0.15632344 | -999.0000 | 27.00 | 0.00859060 | 27.00 | 0.00859060 | 37.7233 | 79858.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9373.655 | 6624.814 | 0.477518 | 0.00022956 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0969 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 8691.18 | 8384.08 | 0.9272 | -999.0 | -999.0 | 27.96 | 17.69 | 0.00874519 | 50418.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8691.18 | 26.67 | 0.01336053 | 20.77 | 0.01563234 | -999.0000 | 27.00 | 0.00858896 | 27.00 | 0.00858896 | 37.7162 | 8122.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 495536.667 | 495536.667 | 25.015531 | 0.01213566 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 495536.67 | 495536.67 | 1.0000 | 29.36636546 | 25.015531 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 495536.67 | -16.30 | 0.00092409 | -16.30 | 0.33839277 | 1.3527 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9596.724 | 9596.724 | 0.489392 | 0.00023502 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9596.72 | 9596.72 | 1.0000 | 0.57450909 | 0.489392 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9596.72 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.1942 | 0.00 | 0.00723647 | 25.93 | 0.00723647 | 33.9216 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92173.413 | 92173.413 | 4.694276 | 0.00225732 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 92173.41 | 92173.41 | 1.0000 | 5.51072899 | 4.694276 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92173.41 | -16.30 | 0.00092409 | -16.30 | 0.15632344 | 3.3301 | 0.00 | 0.00163279 | 23.99 | 0.00163279 | 8.6662 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9373.655 | 9373.655 | 0.477518 | 0.00022956 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9373.65 | 9373.65 | 1.0000 | 0.56056994 | 0.477518 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9373.65 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.2737 | 0.00 | 0.00147928 | 22.79 | 0.00147928 | 8.4459 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22473.716 | 22473.716 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 25.015531 | 29.36636546 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 22473.72 | 22473.72 | 1.0000 | 29.36636546 | 25.015531 | -0.22 | -0.22 | 0.00839752 | 20776.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22473.72 | -16.30 | 0.00092409 | -16.30 | 0.33839277 | 1.3527 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.489392 | 0.57450909 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1038.19 | 1038.19 | 1.0000 | 0.57450909 | 0.489392 | -0.52 | -0.52 | 0.00703484 | 17063.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1038.19 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.1942 | 0.00 | 0.00723647 | 25.93 | 0.00723647 | 33.9216 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10381.926 | 10381.926 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.694276 | 5.51072899 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10381.93 | 10381.93 | 1.0000 | 5.51072899 | 4.694276 | -0.54 | -3.87 | 0.00160919 | 3477.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10381.93 | -16.30 | 0.00092409 | -16.30 | 0.15632344 | 3.3301 | 0.00 | 0.00163279 | 23.99 | 0.00163279 | 8.6662 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.477518 | 0.56056994 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1038.19 | 1038.19 | 1.0000 | 0.56056994 | 0.477518 | -0.53 | -4.12 | 0.00146111 | 3116.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1038.19 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.2737 | 0.00 | 0.00147928 | 22.79 | 0.00147928 | 8.4459 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.96 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 83.33 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.20 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 4.88 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 25.02 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2622.50 | 1685.83 | 527.67 |
CORE_BOTTOM | 2356.83 | 1474.00 | 13.00 |
CORE_MID | 1745.50 | 3116.83 | 121.67 |
CORE_TOP | 2477.67 | 3685.50 | 1020.33 |
PERIMETER_BOT_ZN_3 | 2189.17 | 3240.83 | 465.83 |
PERIMETER_BOT_ZN_2 | 2516.00 | 3119.00 | 551.67 |
PERIMETER_BOT_ZN_1 | 2698.17 | 2895.50 | 592.17 |
PERIMETER_BOT_ZN_4 | 2867.00 | 2134.17 | 387.00 |
PERIMETER_MID_ZN_3 | 3162.50 | 3912.67 | 1791.83 |
PERIMETER_MID_ZN_2 | 2922.33 | 3104.17 | 1492.00 |
PERIMETER_MID_ZN_1 | 3097.67 | 3282.83 | 1221.17 |
PERIMETER_MID_ZN_4 | 3292.17 | 3487.50 | 1489.83 |
PERIMETER_TOP_ZN_3 | 3594.67 | 4137.17 | 2326.67 |
PERIMETER_TOP_ZN_2 | 3802.17 | 3748.83 | 2131.17 |
PERIMETER_TOP_ZN_1 | 3432.33 | 3581.33 | 1734.50 |
PERIMETER_TOP_ZN_4 | 3627.67 | 3749.67 | 1941.83 |
DATACENTER_BOT_ZN_6 | 5918.50 | 656.67 | 656.67 |
DATACENTER_MID_ZN_6 | 5069.00 | 202.67 | 89.17 |
DATACENTER_TOP_ZN_6 | 4570.67 | 624.50 | 205.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5412.00 | 5412.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5905.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 1326.67 | 0.00 | 794.33 |
CORE_BOTTOM | 0.00 | 3.17 | 0.00 | 0.00 |
CORE_MID | 1.67 | 0.00 | 0.83 | 0.00 |
CORE_TOP | 15.00 | 0.00 | 3.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.50 | 6.33 | 0.00 | 4.50 |
PERIMETER_BOT_ZN_2 | 0.67 | 34.17 | 0.00 | 33.33 |
PERIMETER_BOT_ZN_1 | 1.83 | 42.83 | 0.00 | 40.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 110.33 | 0.00 | 54.00 |
PERIMETER_MID_ZN_3 | 73.67 | 0.33 | 21.17 | 0.33 |
PERIMETER_MID_ZN_2 | 75.17 | 32.33 | 0.33 | 31.83 |
PERIMETER_MID_ZN_1 | 27.17 | 41.67 | 0.33 | 40.83 |
PERIMETER_MID_ZN_4 | 24.00 | 44.33 | 0.00 | 25.00 |
PERIMETER_TOP_ZN_3 | 226.00 | 5.83 | 80.17 | 5.00 |
PERIMETER_TOP_ZN_2 | 109.83 | 34.33 | 13.00 | 31.83 |
PERIMETER_TOP_ZN_1 | 98.50 | 33.67 | 8.50 | 30.83 |
PERIMETER_TOP_ZN_4 | 74.17 | 47.83 | 7.00 | 27.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 127.33 | 0.00 | 92.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 282.50 | 1507.00 | 81.50 | 933.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 149.60 | 6779.02 | 0.927 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.32 | 134.35 | 6849.35 | 0.902 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.32 | 134.35 | 6849.35 | 0.672 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.32 | 134.35 | 6849.35 | 0.659 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.95 | 16.87 | 860.00 | 0.894 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.48 | 10.87 | 554.22 | 1.248 | 0.028 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.95 | 16.87 | 860.02 | 1.260 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.48 | 10.87 | 554.22 | 1.759 | 0.028 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.95 | 16.87 | 860.00 | 0.739 | 0.062 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.91 | 10.87 | 554.22 | 1.072 | 0.068 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.95 | 16.87 | 860.02 | 1.157 | 0.062 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.48 | 10.87 | 554.22 | 1.170 | 0.064 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.95 | 16.87 | 860.00 | 0.768 | 0.077 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.48 | 10.87 | 554.22 | 1.200 | 0.080 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.95 | 16.87 | 860.02 | 1.172 | 0.077 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.48 | 10.87 | 554.22 | 1.205 | 0.080 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.37 | 42.18 | 1911.37 | 27.246 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.32 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.32 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.32 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.95 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.95 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.95 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.91 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.95 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.95 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.95 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.37 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.60 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.32 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.32 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.32 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.95 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.95 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.95 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.91 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.95 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.95 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.95 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.37 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1020.85 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 36568062.49 | 0.00 | 36568062.49 | 0.00 | 36568062.49 | 37848132.68 | 4902.60 | 1138.14 | 2719.26 | 0.00 |
CORE_BOTTOM | 38589621.15 | 0.00 | 38589621.15 | 0.00 | 38589621.15 | 33990283.35 | 3981.45 | 230.79 | 4547.76 | 497.06 |
CORE_MID | 0.28E+09 | 0.00 | 0.28E+09 | 0.00 | 0.28E+09 | 0.34E+09 | 4696.39 | 841.21 | 3222.40 | 312.79 |
CORE_TOP | 27156929.51 | 0.00 | 27156929.51 | 0.00 | 27156929.51 | 33990283.35 | 4918.56 | 1166.63 | 2674.81 | 404.56 |
PERIMETER_BOT_ZN_3 | 4792839.87 | 0.00 | 4792839.87 | 263099.47 | 5055939.34 | 4267819.30 | 5088.20 | 324.13 | 3347.67 | 497.06 |
PERIMETER_BOT_ZN_2 | 4229108.18 | 0.00 | 4229108.18 | 175399.53 | 4404507.71 | 2750345.05 | 4927.97 | 254.75 | 3577.28 | 497.06 |
PERIMETER_BOT_ZN_1 | 6627736.52 | 0.00 | 6627736.52 | 263099.47 | 6890835.99 | 4267912.63 | 4741.74 | 232.62 | 3785.64 | 497.06 |
PERIMETER_BOT_ZN_4 | 6001610.94 | 0.00 | 6001610.94 | 175399.53 | 6177010.47 | 2750345.05 | 4105.04 | 175.71 | 4479.25 | 497.06 |
PERIMETER_MID_ZN_3 | 38299803.49 | 0.00 | 38299803.49 | 617042.04 | 38916845.53 | 42678193.03 | 4631.97 | 683.22 | 3444.82 | 312.79 |
PERIMETER_MID_ZN_2 | 36343001.22 | 0.00 | 36343001.22 | 411361.08 | 36754362.30 | 27503450.52 | 4780.25 | 660.97 | 3318.78 | 824.81 |
PERIMETER_MID_ZN_1 | 59270288.55 | 0.00 | 59270288.55 | 617042.04 | 59887330.59 | 42679126.28 | 4247.17 | 490.71 | 4022.12 | 312.79 |
PERIMETER_MID_ZN_4 | 39025600.20 | 0.00 | 39025600.20 | 411361.08 | 39436961.28 | 27503450.52 | 4484.40 | 1041.10 | 3234.50 | 312.79 |
PERIMETER_TOP_ZN_3 | 3967594.61 | 0.00 | 3967594.61 | 766123.54 | 4733718.15 | 4267819.30 | 4366.50 | 887.58 | 3505.92 | 404.56 |
PERIMETER_TOP_ZN_2 | 3949963.60 | 0.00 | 3949963.60 | 510748.68 | 4460712.28 | 2750345.05 | 4353.02 | 1236.95 | 3170.03 | 404.56 |
PERIMETER_TOP_ZN_1 | 5987996.63 | 0.00 | 5987996.63 | 766123.54 | 6754120.17 | 4267912.63 | 4241.47 | 1229.27 | 3289.26 | 404.56 |
PERIMETER_TOP_ZN_4 | 4023021.83 | 0.00 | 4023021.83 | 510748.68 | 4533770.51 | 2750345.05 | 4304.15 | 728.79 | 3727.06 | 404.56 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.43E+09 | 0.00 | 0.43E+09 | 0.00 | 0.43E+09 | 10671554.30 | 19.00 | 123.42 | 8617.58 | 2815.33 |
Total Facility | 0.51E+10 | 0.00 | 0.51E+10 | 23998804.81 | 0.51E+10 | 0.50E+10 | 7033.92 | 4361.84 | 8746.38 | 3328.53 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.7092 | 0.0000 | 1.7092 | 0.0000 | 1.7092 | 1.2002 | 2085.60 | 1138.14 | 2719.26 |
CORE_BOTTOM | 1.6786 | 0.0000 | 1.6786 | 0.0000 | 1.6786 | 1.0778 | 1576.43 | 228.22 | 4138.34 |
CORE_MID | 12.5162 | 0.0000 | 12.5162 | 0.0000 | 12.5162 | 10.7782 | 2009.15 | 841.04 | 3092.81 |
CORE_TOP | 1.2300 | 0.0000 | 1.2300 | 0.0000 | 1.2300 | 1.0778 | 2216.54 | 1166.44 | 2560.02 |
PERIMETER_BOT_ZN_3 | 0.2091 | 0.0000 | 0.2091 | 0.0062 | 0.2154 | 0.1353 | 2675.65 | 320.99 | 2946.36 |
PERIMETER_BOT_ZN_2 | 0.1881 | 0.0000 | 0.1881 | 0.0042 | 0.1923 | 0.0872 | 2515.87 | 251.88 | 3175.25 |
PERIMETER_BOT_ZN_1 | 0.2948 | 0.0000 | 0.2948 | 0.0062 | 0.3010 | 0.1353 | 2330.34 | 230.09 | 3382.57 |
PERIMETER_BOT_ZN_4 | 0.2648 | 0.0000 | 0.2648 | 0.0042 | 0.2690 | 0.0872 | 1699.90 | 173.74 | 4069.36 |
PERIMETER_MID_ZN_3 | 1.7317 | 0.0000 | 1.7317 | 0.0146 | 1.7463 | 1.3533 | 1945.95 | 682.97 | 3314.07 |
PERIMETER_MID_ZN_2 | 1.6169 | 0.0000 | 1.6169 | 0.0103 | 1.6273 | 0.8721 | 1637.60 | 659.07 | 2737.34 |
PERIMETER_MID_ZN_1 | 2.7112 | 0.0000 | 2.7112 | 0.0146 | 2.7258 | 1.3533 | 1563.76 | 490.12 | 3889.12 |
PERIMETER_MID_ZN_4 | 1.7639 | 0.0000 | 1.7639 | 0.0098 | 1.7737 | 0.8721 | 1803.38 | 1040.83 | 3098.79 |
PERIMETER_TOP_ZN_3 | 0.1802 | 0.0000 | 0.1802 | 0.0182 | 0.1984 | 0.1353 | 1665.75 | 887.20 | 3390.05 |
PERIMETER_TOP_ZN_2 | 0.1811 | 0.0000 | 0.1811 | 0.0121 | 0.1932 | 0.0872 | 1655.21 | 1236.58 | 3051.21 |
PERIMETER_TOP_ZN_1 | 0.2745 | 0.0000 | 0.2745 | 0.0182 | 0.2927 | 0.1353 | 1541.83 | 1228.91 | 3172.27 |
PERIMETER_TOP_ZN_4 | 0.1818 | 0.0000 | 0.1818 | 0.0121 | 0.1939 | 0.0872 | 1604.94 | 728.61 | 3609.44 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 13.9932 | 0.0000 | 13.9932 | 0.0000 | 13.9932 | 0.3384 | 17.33 | 123.42 | 5802.25 |
Total Facility | 224.9491 | 0.0000 | 224.9491 | 0.5751 | 225.5242 | 158.4706 | 4216.92 | 4356.68 | 5929.88 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 83017983.16 | 0.00 | 83017983.16 | 48026705.38 | 3501.99 | 5.41 | 5252.60 | 497.06 |
VAV_MID WITH REHEAT | 0.62E+09 | 0.00 | 0.62E+09 | 0.48E+09 | 3959.64 | 1.94 | 4798.42 | 312.79 |
VAV_TOP WITH REHEAT | 62132782.38 | 0.00 | 62132782.38 | 48026705.38 | 4001.06 | 2.22 | 4756.72 | 404.31 |
CAV_BAS | 50394479.08 | 0.00 | 50394479.08 | 37848132.68 | 4796.61 | 0.12 | 3963.26 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.60E+09 | 0.00 | 0.60E+09 | 10671554.30 | 19.00 | 0.00 | 8741.00 | 2815.33 |
AIRLOOP DATACENTER BOT | 336664.50 | 0.00 | 336664.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3366645.00 | 0.00 | 3366645.00 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 336664.50 | 0.00 | 336664.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.6319 | 0.0000 | 3.6319 | 1.5229 | 1126.97 | 3.70 | 4812.33 |
VAV_MID WITH REHEAT | 28.0925 | 0.0000 | 28.0925 | 15.2292 | 1278.65 | 1.77 | 4662.59 |
VAV_TOP WITH REHEAT | 2.8218 | 0.0000 | 2.8218 | 1.5229 | 1302.76 | 2.03 | 4638.22 |
CAV_BAS | 2.3555 | 0.0000 | 2.3555 | 1.2002 | 1979.61 | 0.12 | 3963.26 |
AIRLOOP DATACENTER BASEMENT | 19.2840 | 0.0000 | 19.2840 | 0.3384 | 17.33 | 0.00 | 5925.67 |
AIRLOOP DATACENTER BOT | 0.0157 | 0.0000 | 0.0157 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1574 | 0.0000 | 0.1574 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0157 | 0.0000 | 0.0157 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 674.92 | 3253.74 | 0.00 | 0.00 | 0.00 | 1495.50 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 264.42 | 2696.57 | 0.00 | 0.00 | 0.00 | 2177.61 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 58.63 | 2843.86 | 0.00 | 0.00 | 0.00 | 2379.08 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1115.72 | 2731.01 | 0.00 | 134.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 123.42 | 8617.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.7958 | 5.8835 | 0.0000 | 0.0000 | 0.0000 | 2.3250 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 27.6475 | 46.7495 | 0.0000 | 0.0000 | 0.0000 | 22.1551 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.7516 | 4.6685 | 0.0000 | 0.0000 | 0.0000 | 2.1959 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6550 | 4.3798 | 0.0000 | 1.4313 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4679 | 19.7428 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2155 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1525 |
Defaulted Fields | 1189 |
Fields with Defaults | 3954 |
Autosized Fields | 338 |
Autosizable Fields | 416 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 24632.85 | 284716.97 | 21-MAY-05:00 | 1870839.05 | 28-AUG-14:20 |
Electricity:Building | 16391.81 | 215366.33 | 07-MAY-17:10 | 948093.84 | 01-DEC-16:40 |
Electricity:Zone:BASEMENT | 540.44 | 14022.76 | 01-JAN-00:10 | 23631.68 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16391.81 | 215366.33 | 07-MAY-17:10 | 948093.84 | 01-DEC-16:40 |
InteriorLights:Electricity | 1715.41 | 8110.17 | 01-JAN-10:10 | 169722.15 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1715.41 | 8110.17 | 01-JAN-10:10 | 169722.15 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 1715.41 | 8110.17 | 01-JAN-10:10 | 169722.15 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1715.41 | 8110.17 | 01-JAN-10:10 | 169722.15 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 393.83 | 4960.84 | 01-JAN-00:10 | 26343.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3938.24 | 49608.19 | 01-JAN-00:10 | 263436.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 393.82 | 4960.82 | 01-JAN-00:10 | 26343.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 43.91 | 589.50 | 12-MAR-17:10 | 3307.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.55 | 30.32 | 01-JAN-10:10 | 1147.25 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.55 | 30.32 | 01-JAN-10:10 | 1147.25 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.27 | 379.89 | 26-MAR-17:10 | 2131.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.84 | 19.54 | 01-JAN-09:10 | 739.33 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.84 | 19.54 | 01-JAN-09:10 | 739.33 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.83 | 589.50 | 12-MAR-17:10 | 3307.86 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.47 | 30.33 | 01-JAN-09:10 | 1147.28 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.47 | 30.33 | 01-JAN-09:10 | 1147.28 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.27 | 379.89 | 12-MAR-17:10 | 2131.67 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.83 | 19.54 | 01-JAN-09:50 | 739.33 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.83 | 19.54 | 01-JAN-09:50 | 739.33 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 438.99 | 5894.96 | 12-MAR-17:10 | 33078.05 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 75.34 | 303.25 | 01-JAN-10:00 | 11472.53 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 75.34 | 303.25 | 01-JAN-10:00 | 11472.53 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 282.69 | 3798.93 | 26-MAR-17:10 | 21316.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.33 | 195.42 | 01-JAN-09:00 | 7393.34 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.33 | 195.42 | 01-JAN-09:00 | 7393.34 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 438.27 | 5895.05 | 12-MAR-17:10 | 33078.63 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 74.61 | 303.26 | 01-JAN-09:00 | 11472.78 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 74.61 | 303.26 | 01-JAN-09:00 | 11472.78 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 282.60 | 3798.91 | 12-MAR-17:10 | 21316.66 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.25 | 195.42 | 01-JAN-09:40 | 7393.34 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.25 | 195.42 | 01-JAN-09:40 | 7393.34 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 43.90 | 589.50 | 12-MAR-17:10 | 3307.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.53 | 30.32 | 01-JAN-10:00 | 1147.25 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.53 | 30.32 | 01-JAN-10:00 | 1147.25 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.27 | 379.89 | 26-MAR-17:10 | 2131.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.83 | 19.54 | 01-JAN-09:00 | 739.33 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.83 | 19.54 | 01-JAN-09:00 | 739.33 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.83 | 589.50 | 12-MAR-17:10 | 3307.86 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.46 | 30.33 | 01-JAN-09:00 | 1147.28 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.46 | 30.33 | 01-JAN-09:00 | 1147.28 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.26 | 379.89 | 12-MAR-17:10 | 2131.67 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.82 | 19.54 | 01-JAN-09:40 | 739.33 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.82 | 19.54 | 01-JAN-09:40 | 739.33 | 02-JAN-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7527.71 | 95067.50 | 01-JAN-00:10 | 382501.19 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1555.56 | 19567.35 | 01-JAN-00:10 | 79407.42 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1756.24 | 3812.68 | 31-JAN-02:00 | 545175.84 | 05-JUL-16:00 |
HeatRejection:Electricity | 464.80 | 55.28 | 06-JAN-08:00 | 75503.64 | 17-JUL-05:10 |
General:HeatRejection:Electricity | 464.80 | 55.28 | 06-JAN-08:00 | 75503.64 | 17-JUL-05:10 |
ElectricityProduced:Facility | 437.15 | -0.00 | 28-NOV-07:30 | 89495.83 | 14-JUN-11:50 |
ElectricityProduced:Plant | 437.15 | -0.00 | 28-NOV-07:30 | 89495.83 | 14-JUN-11:50 |
Photovoltaic:ElectricityProduced | 457.74 | 0.00 | 01-JAN-00:10 | 93928.67 | 14-JUN-12:20 |
PowerConversion:ElectricityProduced | -20.59 | -4432.83 | 14-JUN-12:20 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 4631.29 | 53221.31 | 29-SEP-05:00 | 435568.29 | 03-AUG-15:30 |
ExteriorEquipment:Electricity | 1641.46 | 10611.42 | 01-JAN-00:10 | 154955.59 | 02-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.35 | 979.82 | 01-JAN-00:10 | 3372.05 | 01-DEC-16:50 |
ElectricityPurchased:Facility | 24195.70 | 262964.39 | 21-MAY-10:30 | 1830272.70 | 15-AUG-14:50 |
ElectricityPurchased:Plant | 24195.70 | 262964.39 | 21-MAY-10:30 | 1830272.70 | 15-AUG-14:50 |
Cogeneration:ElectricityPurchased | 24195.70 | 262964.39 | 21-MAY-10:30 | 1830272.70 | 15-AUG-14:50 |
General:Cogeneration:ElectricityPurchased | 24195.70 | 262964.39 | 21-MAY-10:30 | 1830272.70 | 15-AUG-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 24195.70 | 262964.39 | 21-MAY-10:30 | 1830272.70 | 15-AUG-14:50 |
ElectricityNet:Plant | 24195.70 | 262964.39 | 21-MAY-10:30 | 1830272.70 | 15-AUG-14:50 |
Cogeneration:ElectricityNet | 24195.70 | 262964.39 | 21-MAY-10:30 | 1830272.70 | 15-AUG-14:50 |
General:Cogeneration:ElectricityNet | 24195.70 | 262964.39 | 21-MAY-10:30 | 1830272.70 | 15-AUG-14:50 |
Fans:Electricity | 2295.76 | 47597.93 | 05-JAN-01:10 | 255082.31 | 10-AUG-15:20 |
General:Fans:Electricity | 2295.76 | 47597.93 | 05-JAN-01:10 | 255082.31 | 10-AUG-15:20 |
ExteriorLights:Electricity | 266.41 | 0.00 | 01-JAN-08:00 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 266.41 | 0.00 | 01-JAN-08:00 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1582.20 | 9600.00 | 01-JAN-00:10 | 151268.49 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
HeatRecovery:Electricity | 37.30 | 0.00 | 01-JAN-00:10 | 4520.72 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 37.30 | 0.00 | 01-JAN-00:10 | 4520.72 | 02-JAN-07:10 |
Cooling:Electricity | 1279.04 | 1456.36 | 14-JAN-16:30 | 511425.81 | 05-JUL-16:00 |
General:Cooling:Electricity | 1279.04 | 1456.36 | 14-JAN-16:30 | 511425.81 | 05-JUL-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1461.52 | 0.00 | 11-JAN-13:10 | 100000.00 | 14-FEB-13:20 |
General:Humidifier:Electricity | 1461.52 | 0.00 | 11-JAN-13:10 | 100000.00 | 14-FEB-13:20 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 459.87 | 0.00 | 01-JAN-00:10 | 56293.64 | 13-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 459.87 | 0.00 | 01-JAN-00:10 | 56293.64 | 13-FEB-12:30 |
Pumps:Electricity | 334.89 | 3751.90 | 01-JAN-00:40 | 46170.89 | 16-AUG-12:50 |
General:Pumps:Electricity | 334.89 | 3751.90 | 01-JAN-00:40 | 46170.89 | 16-AUG-12:50 |
WIRED_LTG_ELECTRICITY | 48.20 | 0.00 | 01-JAN-00:10 | 4769.19 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 938.37 | 0.00 | 01-JAN-00:40 | 1478009.75 | 02-JAN-05:10 |
NaturalGas:Plant | 938.37 | 0.00 | 01-JAN-00:40 | 1478009.75 | 02-JAN-05:10 |
Heating:NaturalGas | 938.37 | 0.00 | 01-JAN-00:40 | 1478009.75 | 02-JAN-05:10 |
Boiler:Heating:NaturalGas | 938.37 | 0.00 | 01-JAN-00:40 | 1478009.75 | 02-JAN-05:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 8328.59 | 3467.23 | 11-JAN-07:30 | 3013472.95 | 05-JUL-16:00 |
PlantLoopCoolingDemand:HVAC | 8328.59 | 3467.23 | 11-JAN-07:30 | 3013472.95 | 05-JUL-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 8328.59 | 3467.23 | 11-JAN-07:30 | 3013472.95 | 05-JUL-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 5879.23 | 0.00 | 11-MAR-01:00 | 0.00 | 04-AUG-12:30 |
Water:HVAC | 543.68 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
Humidifier:Water | 543.68 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
General:Humidifier:Water | 543.68 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
MainsWater:Facility | 5879.23 | 0.00 | 11-MAR-01:00 | 0.00 | 04-AUG-12:30 |
MainsWater:HVAC | 543.68 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
Humidifier:MainsWater | 543.68 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
General:Humidifier:MainsWater | 543.68 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
Water:Plant | 5335.55 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-12:30 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5335.55 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-12:30 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3055.38 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-14:30 |
General:HeatRejection:Water | 3055.38 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-14:30 |
HeatRejection:MainsWater | 3055.38 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-14:30 |
General:HeatRejection:MainsWater | 3055.38 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-14:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 42330.55 | 94750.42 | 30-JAN-04:40 | 11758732.46 | 05-JUL-16:00 |
EnergyTransfer:Building | 17073.77 | 88366.33 | 27-JAN-22:20 | 1573822.60 | 09-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 509.70 | 0.00 | 01-JAN-00:10 | 92851.76 | 13-JUN-06:10 |
Heating:EnergyTransfer | 712.95 | 0.00 | 15-JAN-16:30 | 1135222.67 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 712.95 | 0.00 | 15-JAN-16:30 | 1135222.67 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 16360.83 | 85633.54 | 30-JAN-04:40 | 1573822.60 | 09-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 509.70 | 0.00 | 01-JAN-00:10 | 92851.76 | 13-JUN-06:10 |
General:Cooling:EnergyTransfer | 16360.83 | 85633.54 | 30-JAN-04:40 | 1573822.60 | 09-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 509.70 | 0.00 | 01-JAN-00:10 | 92851.76 | 13-JUN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 545.77 | 0.00 | 01-JAN-00:10 | 55911.90 | 15-AUG-15:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 545.77 | 0.00 | 01-JAN-00:10 | 55911.90 | 15-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 545.77 | 0.00 | 01-JAN-00:10 | 55911.90 | 15-AUG-15:00 |
EnergyTransfer:Zone:CORE_MID | 3597.06 | 0.00 | 01-JAN-00:40 | 409521.38 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 9.97 | 0.00 | 01-JAN-00:10 | 409521.38 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 9.97 | 0.00 | 01-JAN-00:10 | 409521.38 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3587.09 | 0.00 | 01-JAN-00:40 | 375911.15 | 07-SEP-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3587.09 | 0.00 | 01-JAN-00:40 | 375911.15 | 07-SEP-05:10 |
EnergyTransfer:Zone:CORE_TOP | 328.04 | 0.00 | 01-JAN-00:40 | 62733.81 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 18.69 | 0.00 | 01-JAN-00:40 | 62733.81 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 18.69 | 0.00 | 01-JAN-00:40 | 62733.81 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 309.35 | 0.00 | 01-JAN-00:10 | 44047.84 | 17-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 309.35 | 0.00 | 01-JAN-00:10 | 44047.84 | 17-JUL-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 62.63 | 0.00 | 01-JAN-00:10 | 11529.27 | 21-JUL-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.88 | 0.00 | 01-JAN-00:10 | 6392.67 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.88 | 0.00 | 01-JAN-00:10 | 6392.67 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 61.75 | 0.00 | 01-JAN-00:10 | 11529.27 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 61.75 | 0.00 | 01-JAN-00:10 | 11529.27 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 55.22 | 0.00 | 01-JAN-00:10 | 14892.06 | 30-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.78 | 0.00 | 01-JAN-00:10 | 4927.69 | 07-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.78 | 0.00 | 01-JAN-00:10 | 4927.69 | 07-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 54.44 | 0.00 | 01-JAN-00:10 | 14892.06 | 30-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 54.44 | 0.00 | 01-JAN-00:10 | 14892.06 | 30-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 91.67 | 0.00 | 01-JAN-00:10 | 20567.73 | 31-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.64 | 0.00 | 01-JAN-00:10 | 9450.89 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.64 | 0.00 | 01-JAN-00:10 | 9450.89 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 90.03 | 0.00 | 01-JAN-00:10 | 20567.73 | 31-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 90.03 | 0.00 | 01-JAN-00:10 | 20567.73 | 31-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 84.22 | 0.00 | 01-JAN-00:10 | 17986.94 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.07 | 0.00 | 01-JAN-00:10 | 2565.54 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.07 | 0.00 | 01-JAN-00:10 | 2565.54 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 84.15 | 0.00 | 01-JAN-00:10 | 17986.94 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 84.15 | 0.00 | 01-JAN-00:10 | 17986.94 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 551.32 | 0.00 | 01-JAN-00:40 | 118122.14 | 06-FEB-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 154.68 | 0.00 | 01-JAN-00:40 | 118122.14 | 06-FEB-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 154.68 | 0.00 | 01-JAN-00:40 | 118122.14 | 06-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 396.64 | 0.00 | 01-JAN-00:10 | 95100.70 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 396.64 | 0.00 | 01-JAN-00:10 | 95100.70 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 512.45 | 0.00 | 01-JAN-00:40 | 154911.50 | 13-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 84.37 | 0.00 | 01-JAN-00:40 | 119462.40 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 84.37 | 0.00 | 01-JAN-00:40 | 119462.40 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 428.09 | 0.00 | 01-JAN-00:10 | 154911.50 | 13-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 428.09 | 0.00 | 01-JAN-00:10 | 154911.50 | 13-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 840.83 | 0.00 | 01-JAN-00:40 | 214863.18 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 93.11 | 0.00 | 01-JAN-00:40 | 166067.54 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 93.11 | 0.00 | 01-JAN-00:40 | 166067.54 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 747.73 | 0.00 | 01-JAN-00:10 | 214863.18 | 31-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 747.73 | 0.00 | 01-JAN-00:10 | 214863.18 | 31-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 546.60 | 0.00 | 01-JAN-00:40 | 159661.63 | 04-AUG-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 67.22 | 0.00 | 01-JAN-00:40 | 110400.42 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 67.22 | 0.00 | 01-JAN-00:40 | 110400.42 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 479.38 | 0.00 | 01-JAN-00:10 | 159661.63 | 04-AUG-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 479.38 | 0.00 | 01-JAN-00:10 | 159661.63 | 04-AUG-16:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 70.18 | 0.00 | 01-JAN-00:40 | 13991.57 | 06-FEB-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 33.48 | 0.00 | 01-JAN-00:40 | 13991.57 | 06-FEB-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 33.48 | 0.00 | 01-JAN-00:40 | 13991.57 | 06-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.70 | 0.00 | 01-JAN-00:10 | 10526.44 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.70 | 0.00 | 01-JAN-00:10 | 10526.44 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 61.18 | 0.00 | 01-JAN-00:40 | 16753.89 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 19.03 | 0.00 | 01-JAN-00:40 | 16753.89 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 19.03 | 0.00 | 01-JAN-00:40 | 16753.89 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.15 | 0.00 | 01-JAN-00:10 | 15308.69 | 03-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.15 | 0.00 | 01-JAN-00:10 | 15308.69 | 03-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 91.30 | 0.00 | 01-JAN-00:40 | 21779.16 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 22.73 | 0.00 | 01-JAN-00:40 | 19799.83 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 22.73 | 0.00 | 01-JAN-00:40 | 19799.83 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 68.57 | 0.00 | 01-JAN-00:10 | 21779.16 | 31-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 68.57 | 0.00 | 01-JAN-00:10 | 21779.16 | 31-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 60.69 | 0.00 | 01-JAN-00:40 | 16557.07 | 02-JUL-17:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 14.95 | 0.00 | 01-JAN-00:40 | 15790.62 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 14.95 | 0.00 | 01-JAN-00:40 | 15790.62 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.74 | 0.00 | 01-JAN-00:10 | 16557.07 | 02-JUL-17:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.74 | 0.00 | 01-JAN-00:10 | 16557.07 | 02-JUL-17:20 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 49.97 | 0.00 | 01-JAN-00:10 | 9671.86 | 17-JUL-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.96 | 0.00 | 01-JAN-00:10 | 3996.25 | 10-DEC-12:20 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.96 | 0.00 | 01-JAN-00:10 | 3996.25 | 10-DEC-12:20 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 46.01 | 0.00 | 01-JAN-00:10 | 9671.86 | 17-JUL-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 46.01 | 0.00 | 01-JAN-00:10 | 9671.86 | 17-JUL-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 393.38 | 0.00 | 01-JAN-00:40 | 145283.99 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 135.11 | 0.00 | 01-JAN-00:40 | 145283.99 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 135.11 | 0.00 | 01-JAN-00:40 | 145283.99 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 258.27 | 0.00 | 01-JAN-00:10 | 64017.06 | 17-JUL-10:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 258.27 | 0.00 | 01-JAN-00:10 | 64017.06 | 17-JUL-10:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 88.72 | 0.00 | 01-JAN-00:40 | 26566.01 | 11-DEC-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 45.75 | 0.00 | 01-JAN-00:40 | 26566.01 | 11-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 45.75 | 0.00 | 01-JAN-00:40 | 26566.01 | 11-DEC-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 42.97 | 0.00 | 01-JAN-00:10 | 17707.00 | 12-JUN-13:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 42.97 | 0.00 | 01-JAN-00:10 | 17707.00 | 12-JUN-13:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.36 | 293.82 | 30-JAN-06:00 | 8191.91 | 02-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.36 | 293.82 | 30-JAN-06:00 | 8191.91 | 02-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.36 | 293.82 | 30-JAN-06:00 | 8191.91 | 02-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1149.32 | 0.23 | 07-JAN-15:40 | 78595.51 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.65 | 0.00 | 03-JAN-07:30 | 5444.77 | 08-JAN-18:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.65 | 0.00 | 03-JAN-07:30 | 5444.77 | 08-JAN-18:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1143.67 | 0.00 | 01-JAN-00:10 | 78595.51 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1143.67 | 0.00 | 01-JAN-00:10 | 78595.51 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 104.98 | 0.03 | 03-JAN-07:30 | 7913.99 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.88 | 0.00 | 03-JAN-07:30 | 581.38 | 15-JAN-18:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.88 | 0.00 | 03-JAN-07:30 | 581.38 | 15-JAN-18:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 104.09 | 0.00 | 01-JAN-00:10 | 7913.99 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 104.09 | 0.00 | 01-JAN-00:10 | 7913.99 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7143.19 | 85302.03 | 30-JAN-05:00 | 374218.13 | 15-AUG-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7143.19 | 85302.03 | 30-JAN-05:00 | 374218.13 | 15-AUG-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7143.19 | 85302.03 | 30-JAN-05:00 | 374218.13 | 15-AUG-17:00 |
PlantLoopHeatingDemand:Facility | 1326.83 | 0.00 | 01-JAN-00:40 | 1237527.46 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
EnergyTransfer:HVAC | 10589.78 | 3338.39 | 30-JAN-02:00 | 2890541.23 | 05-JUL-16:00 |
HeatingCoils:EnergyTransfer | 872.31 | 0.00 | 01-JAN-00:40 | 1230844.11 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 872.31 | 0.00 | 01-JAN-00:40 | 1230844.11 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 872.31 | 0.00 | 01-JAN-00:40 | 1230844.11 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 7546.24 | 1831.49 | 11-JAN-07:30 | 2890541.23 | 05-JUL-16:00 |
HeatRecoveryForHeating:EnergyTransfer | 2056.04 | 0.00 | 01-JAN-00:10 | 723498.38 | 07-FEB-07:10 |
HeatRecoveryForCooling:EnergyTransfer | 115.19 | 0.00 | 01-JAN-00:10 | 350811.58 | 15-JUL-14:00 |
EnergyTransfer:Plant | 14667.00 | 0.00 | 01-JAN-00:40 | 7542003.85 | 05-JUL-16:00 |
LoopToLoop:EnergyTransfer | 4276.60 | 0.00 | 01-JAN-00:10 | 2357900.59 | 05-JUL-16:00 |
WaterSystems:EnergyTransfer | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
Boilers:EnergyTransfer | 871.04 | 0.00 | 01-JAN-00:40 | 1326119.35 | 02-JAN-05:10 |
Chillers:EnergyTransfer | 4284.08 | 0.00 | 01-JAN-00:10 | 2380247.59 | 05-JUL-16:00 |
HeatRejection:EnergyTransfer | 4780.76 | 0.00 | 01-JAN-00:10 | 2768741.67 | 05-JUL-16:00 |
General:HeatRejection:EnergyTransfer | 4780.76 | 0.00 | 01-JAN-00:10 | 2768741.67 | 05-JUL-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -509.689 | 0.000 | 0.000 | 90.484 | 116.039 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -121.232 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -545.773 | 0.000 | 0.000 | 83.494 | 104.212 | 289.614 | 0.000 | 0.000 | 0.000 | 68.453 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 9.975 | -3587.079 | 0.000 | 0.000 | 859.027 | 1042.115 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1220.165 |
CORE_TOP | 0.000 | 0.000 | 18.694 | -309.344 | 0.000 | 0.000 | 89.023 | 104.212 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -192.198 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.884 | -61.748 | 0.000 | 0.000 | 10.925 | 7.545 | 36.365 | 27.951 | 0.000 | 0.022 | 54.216 | 0.000 | -71.257 | 0.000 | -4.904 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.780 | -54.439 | 0.000 | 0.000 | 7.006 | 4.839 | 23.435 | 53.467 | 0.000 | 0.015 | 12.220 | 0.000 | -44.071 | 0.000 | -3.251 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 1.642 | -90.030 | 0.000 | 0.000 | 10.822 | 7.467 | 36.366 | 99.873 | 0.000 | 0.021 | 3.537 | 0.000 | -64.808 | 0.000 | -4.889 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.068 | -84.149 | 0.000 | 0.000 | 6.836 | 4.831 | 23.435 | 52.640 | 0.000 | 0.014 | 50.370 | 0.000 | -50.483 | 0.000 | -3.562 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 154.678 | -396.641 | 0.000 | 0.000 | 114.018 | 75.338 | 363.654 | 289.524 | 0.000 | 0.508 | 144.064 | 0.000 | -642.485 | 0.000 | -102.659 | -0.002 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 84.366 | -428.083 | 0.000 | 0.000 | 53.075 | 48.333 | 234.352 | 535.246 | 0.000 | 0.303 | 0.003 | 0.000 | -408.656 | 0.000 | -70.092 | -48.843 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 93.105 | -747.722 | 0.000 | 0.000 | 110.654 | 74.612 | 363.660 | 997.405 | 0.000 | 0.470 | 0.028 | 0.000 | -620.065 | 0.000 | -108.209 | -163.909 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 67.223 | -479.374 | 0.000 | 0.000 | 72.335 | 48.253 | 234.351 | 536.532 | 0.000 | 0.307 | 29.365 | 0.000 | -436.866 | 0.000 | -72.128 | -0.015 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 33.477 | -36.700 | 0.000 | 0.000 | 11.560 | 7.533 | 36.365 | 29.416 | 0.000 | 0.057 | 0.001 | 0.000 | -60.875 | 0.000 | -12.136 | -8.698 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 19.029 | -42.146 | 0.000 | 0.000 | 7.312 | 4.833 | 23.435 | 54.034 | 0.000 | 0.037 | 0.001 | 0.000 | -38.776 | 0.000 | -8.285 | -19.474 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 22.731 | -68.568 | 0.000 | 0.000 | 11.237 | 7.461 | 36.366 | 100.363 | 0.000 | 0.055 | 0.000 | 0.000 | -58.728 | 0.000 | -12.749 | -38.168 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 14.946 | -45.741 | 0.000 | 0.000 | 7.333 | 4.825 | 23.435 | 53.845 | 0.000 | 0.036 | 0.002 | 0.000 | -41.678 | 0.000 | -8.562 | -8.438 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -135.359 | 0.000 | 0.000 | 0.950 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -21.147 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 5.652 | -1143.669 | 0.000 | 0.000 | 9.529 | 16.758 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -427.076 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.881 | -104.095 | 0.000 | 0.000 | 0.958 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -53.300 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7143.181 | 0.000 | 0.000 | 20.485 | 32.854 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -405.015 |
GROUNDFLOOR_PLENUM | 3.958 | -46.007 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.038 | 52.482 | 0.000 | 0.000 | 0.000 | -10.470 | -0.001 |
MIDFLOOR_PLENUM | 135.115 | -258.269 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.732 | 297.211 | 0.000 | 0.000 | 0.000 | -174.789 | -0.002 |
TOPFLOOR_PLENUM | 45.747 | -42.972 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.046 | 15.744 | 0.000 | 0.000 | 0.000 | -18.565 | -0.001 |
Total Facility | 184.820 | -347.248 | 528.131 | -16013.530 | 0.000 | 0.000 | 1577.064 | 1715.411 | 14676.396 | 2830.296 | 0.000 | 2.660 | 727.697 | 0.000 | -2538.748 | 0.000 | -615.250 | -2727.687 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 12-JUL-06:11 | 0.00 | 0.00 | 0.00 | -100202.65 | 0.00 | 0.00 | 1545.14 | 3391.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 81808.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 28-JUN-04:13 | 0.00 | 0.00 | 0.00 | -88441.73 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 81966.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 18-SEP-04:12 | 0.00 | 0.00 | 0.00 | -751212.63 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 686462.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-04:14 | 0.00 | 0.00 | 0.00 | -75270.83 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 68795.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 11-JUN-18:41 | 0.00 | 0.00 | 0.00 | -15387.16 | 0.00 | 0.00 | 0.00 | 30.32 | 559.17 | 5921.77 | 0.00 | 0.00 | 8925.48 | 0.00 | -0.00 | 0.00 | -49.59 | 0.00 |
PERIMETER_BOT_ZN_2 | 16-JUL-09:11 | 0.00 | 0.00 | 0.00 | -23528.77 | 0.00 | 0.00 | 20.58 | 19.54 | 464.11 | 17597.40 | 0.00 | 0.00 | 5443.52 | 0.00 | -0.00 | 0.00 | -16.38 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-12:11 | 0.00 | 0.00 | 0.00 | -27133.14 | 0.00 | 0.00 | 33.30 | 30.33 | 720.19 | 26696.96 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -163.92 | -183.71 |
PERIMETER_BOT_ZN_4 | 11-JUN-16:41 | 0.00 | 0.00 | 0.00 | -31079.56 | 0.00 | 0.00 | 15.82 | 19.54 | 464.11 | 18934.15 | 0.00 | 0.00 | 11711.78 | 0.00 | -0.00 | 0.00 | -65.84 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-13:23 | 0.00 | 0.00 | 0.00 | -138023.33 | 0.00 | 0.00 | 433.03 | 303.25 | 7201.84 | 79646.59 | 0.00 | 385.38 | 50053.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 11-JUN-10:01 | 0.00 | 0.00 | 0.00 | -253000.94 | 0.00 | 0.00 | 205.03 | 195.42 | 4641.14 | 128275.78 | 0.00 | 0.00 | 121474.58 | 0.00 | -0.00 | 0.00 | -1791.02 | 0.00 |
PERIMETER_MID_ZN_1 | 03-SEP-12:32 | 0.00 | 0.00 | 0.00 | -264583.87 | 0.00 | 0.00 | 340.95 | 303.26 | 7201.95 | 225991.06 | 0.00 | 0.00 | 33459.38 | 0.00 | -0.00 | 0.00 | -2712.72 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-16:41 | 0.00 | 0.00 | 0.00 | -285458.29 | 0.00 | 0.00 | 163.22 | 195.42 | 4641.11 | 188286.78 | 0.00 | 0.00 | 93746.78 | 0.00 | -0.00 | 0.00 | -1575.03 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-15:51 | 0.00 | 0.00 | 0.00 | -16090.53 | 0.00 | 0.00 | 40.01 | 30.32 | 720.18 | 5644.64 | 0.00 | 134.20 | 9521.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 16-JUL-09:11 | 0.00 | 0.00 | 0.00 | -26321.89 | 0.00 | 0.00 | 19.12 | 19.54 | 464.11 | 17426.39 | 0.00 | 0.00 | 8455.35 | 0.00 | -0.00 | 0.00 | -62.62 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-12:41 | 0.00 | 0.00 | 0.00 | -29676.22 | 0.00 | 0.00 | 31.30 | 30.33 | 720.19 | 26203.41 | 0.00 | 0.00 | 3208.38 | 0.00 | -0.00 | 0.00 | -517.39 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-17:01 | 0.00 | 0.00 | 0.00 | -28321.10 | 0.00 | 0.00 | 0.00 | 19.54 | 360.35 | 20947.60 | 0.00 | 0.00 | 7140.94 | 0.00 | -0.00 | 0.00 | -147.33 | 0.00 |
DATACENTER_BOT_ZN_6 | 02-AUG-18:50 | 0.00 | 0.00 | 0.00 | -8191.74 | 0.00 | 0.00 | 10.62 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 337.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -78593.90 | 0.00 | 0.00 | 106.16 | 487.73 | 77944.22 | 0.00 | 0.00 | 0.00 | 55.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -7913.83 | 0.00 | 0.00 | 10.62 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 60.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 15-AUG-16:41 | 0.00 | 0.00 | 0.00 | -377651.88 | 0.00 | 0.00 | 666.19 | 1593.70 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4240.53 |
GROUNDFLOOR_PLENUM | 24-JUL-05:15 | 0.00 | -11068.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11079.01 | 0.00 | -0.00 | 0.00 | -10.56 | 0.00 |
MIDFLOOR_PLENUM | 04-MAR-05:11 | 0.00 | -98880.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110880.92 | 0.00 | -0.00 | 0.00 | -11999.95 | 0.00 |
TOPFLOOR_PLENUM | 12-JUN-13:40 | 0.00 | -17706.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.08 | 17572.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-AUG-05:03 | 0.00 | -24301.50 | 0.00 | -1746449.00 | 0.00 | 0.00 | 16054.08 | 10223.35 | 616289.16 | 0.00 | 0.00 | 0.00 | 1203824.40 | 0.00 | -73273.68 | 0.00 | -2366.81 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 465927.36 | 0.00 | 0.00 | 0.00 | 0.00 | 5076.02 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -530379.60 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 71231.98 | 0.00 | 0.00 | 0.00 | 0.00 | 507.60 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -77677.20 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 11447.33 | 0.00 | 0.00 | 0.00 | 0.00 | 127.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7193.60 | 0.00 | -935.45 | -4191.31 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 11720.83 | 0.00 | 0.00 | 0.00 | 0.00 | 82.15 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4638.02 | 0.00 | -624.01 | -7021.42 |
PERIMETER_BOT_ZN_1 | 07-FEB-05:01 | 0.00 | 0.00 | 17115.21 | 0.00 | 0.00 | 0.00 | 0.00 | 127.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7115.82 | 0.00 | -942.85 | -9929.59 |
PERIMETER_BOT_ZN_4 | 30-JAN-06:01 | 0.00 | 0.00 | 8851.94 | 0.00 | 0.00 | 0.00 | 94.15 | 43.48 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4211.84 | 0.00 | -68.40 | -5328.14 |
PERIMETER_MID_ZN_3 | 05-FEB-21:32 | 0.00 | 0.00 | 125835.20 | 0.00 | 0.00 | 0.00 | 0.00 | 637.34 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58845.92 | 0.00 | -20350.46 | -52867.87 |
PERIMETER_MID_ZN_2 | 06-FEB-04:11 | 0.00 | 0.00 | 180625.56 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41903.92 | 0.00 | -12790.47 | -131146.58 |
PERIMETER_MID_ZN_1 | 06-FEB-04:11 | 0.00 | 0.00 | 207028.14 | 0.00 | 0.00 | 0.00 | 0.00 | 637.36 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -65433.84 | 0.00 | -19112.32 | -130575.07 |
PERIMETER_MID_ZN_4 | 06-FEB-04:11 | 0.00 | 0.00 | 181077.64 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43865.91 | 0.00 | -12871.56 | -129555.55 |
PERIMETER_TOP_ZN_3 | 05-FEB-21:32 | 0.00 | 0.00 | 15044.02 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5589.27 | 0.00 | -2430.73 | -7646.92 |
PERIMETER_TOP_ZN_2 | 26-DEC-04:01 | 0.00 | 0.00 | 20383.53 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3620.30 | 0.00 | -1775.48 | -15509.29 |
PERIMETER_TOP_ZN_1 | 26-DEC-01:22 | 0.00 | 0.00 | 23336.32 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5555.10 | 0.00 | -2324.45 | -16266.09 |
PERIMETER_TOP_ZN_4 | 06-FEB-04:11 | 0.00 | 0.00 | 21460.54 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4205.84 | 0.00 | -1569.77 | -16206.47 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 08-JAN-18:10 | 0.00 | 0.00 | 5444.77 | 0.00 | 0.00 | 0.00 | 0.00 | 81.29 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25012.12 |
DATACENTER_TOP_ZN_6 | 15-JAN-18:50 | 0.00 | 0.00 | 581.38 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2538.12 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 13-AUG-15:31 | 11947.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.19 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12159.39 |
MIDFLOOR_PLENUM | 02-JAN-06:13 | 165898.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2404.51 | -163494.17 |
TOPFLOOR_PLENUM | 11-DEC-05:42 | 28174.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1088.65 | -27086.06 |
Total Facility | 02-JAN-04:01 | -71063.97 | 87211.66 | 1305572.87 | -87211.66 | 0.00 | 0.00 | 0.00 | 9428.74 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -136911.25 | 0.00 | -35727.39 | -1303724.23 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.4797 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.9580 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 100.3307 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 83.3331 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.3137 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.2040 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.8815 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.8815 | 0.2459 | 1.0000 | Not calculated | 1.2002 | 0.2459 | ||
AIRLOOP DATACENTER BASEMENT | 25.0153 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.0155 | 0.0135 | 1.0000 | Not calculated | 0.3384 | 0.0135 | ||
AIRLOOP DATACENTER BOT | 0.4894 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4894 | 0.0319 | 1.0000 | Not calculated | 0.0156 | 0.0319 | ||
AIRLOOP DATACENTER MID | 4.6943 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6943 | 0.0333 | 1.0000 | Not calculated | 0.1563 | 0.0333 | ||
AIRLOOP DATACENTER TOP | 0.4775 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4775 | 0.0327 | 1.0000 | Not calculated | 0.0156 | 0.0327 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.2399 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2847 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 50.1654 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8167 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.1569 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2840 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 25.0153 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.0153 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0135 | ||
AIRLOOP DATACENTER BOT | 0.4894 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4894 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0319 | ||
AIRLOOP DATACENTER MID | 4.6943 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6943 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0333 | ||
AIRLOOP DATACENTER TOP | 0.4775 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4775 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0327 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 4.8815 | 4.8815 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3341 | 5.3341 | 1.6162 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 49.9787 | 49.9787 | 16.1431 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9573 | 4.9573 | 1.6161 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9097 | 0.9097 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2596 | 1.2596 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4326 | 1.4326 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5437 | 1.5437 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.4894 | 8.4894 | 2.0290 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.4787 | 13.4787 | 1.3074 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.2331 | 14.2331 | 2.0353 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.1508 | 14.1508 | 1.3019 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9683 | 0.9683 | 0.2033 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3593 | 1.3593 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5353 | 1.5353 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4935 | 1.4935 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4894 | 0.4894 | 0.4894 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6943 | 4.6943 | 4.6943 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4775 | 0.4775 | 0.4775 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.0153 | 25.0153 | 25.0153 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.4797 | 8.9580 | 10.4797 | 2.2847 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 100.3307 | 83.3331 | 100.3307 | 22.8167 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.3137 | 9.2040 | 10.3137 | 2.2840 | 0.0000 | 1.0000 |
CAV_BAS | 4.8815 | 4.8815 | 4.8815 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.0153 | 25.0155 | 25.0153 | 25.0153 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4894 | 0.4894 | 0.4894 | 0.4894 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6943 | 4.6943 | 4.6943 | 4.6943 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4775 | 0.4775 | 0.4775 | 0.4775 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6671 | 2.6671 | 1.6162 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.9894 | 24.9894 | 16.1431 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4787 | 2.4787 | 1.6161 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4548 | 0.4548 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6298 | 0.6298 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7163 | 0.7163 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7719 | 0.7719 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.2447 | 4.2447 | 2.0290 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7394 | 6.7394 | 1.3074 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.1166 | 7.1166 | 2.0353 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0754 | 7.0754 | 1.3019 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4841 | 0.4841 | 0.2033 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6796 | 0.6796 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7677 | 0.7677 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7468 | 0.7468 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4894 | 0.4894 | 0.4894 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6943 | 4.6943 | 4.6943 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4775 | 0.4775 | 0.4775 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.0153 | 25.0153 | 25.0153 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.2399 | 2.2847 | 2.2847 | 2.2847 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 50.1654 | 22.8167 | 22.8167 | 22.8167 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.1569 | 2.2840 | 2.2840 | 2.2840 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.0153 | 25.0153 | 25.0153 | 25.0153 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4894 | 0.4894 | 0.4894 | 0.4894 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6943 | 4.6943 | 4.6943 | 4.6943 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4775 | 0.4775 | 0.4775 | 0.4775 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 81.50 |
Number of hours cooling loads not met | 933.17 |
Number of hours not met | 973.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 938.37 | 1478009.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1279.04 | 511425.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1715.41 | 169722.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 266.41 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.35 | 3372.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1582.20 | 151268.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2295.76 | 255082.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 334.89 | 46170.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 464.80 | 75503.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1461.52 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 37.30 | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 459.87 | 56293.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 24632.85 |
Natural Gas | 0.00 | 938.37 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 25571.22 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 457.74 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 37.03 |
Space Heating | 0.00 |
Space Cooling | 27.61 |
Fans (All) | 49.56 |
Service Water Heating | 9.93 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 531.79 |
Subtotal | 531.79 |
Natural Gas [MJ/m2] | |
Space Heating | 20.26 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 20.26 |
Subtotal | 20.26 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.71 |
Space Heating | 3.67 |
Space Cooling | 5.00 |
Fans (All) | 8.98 |
Service Water Heating | 1.80 |
Receptacle Equipment | 57.39 |
Miscellaneous | 16.45 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2069. | 8760. |
LTG_SCH_DATACENTER | 1840. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 759. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7758.00 | 693.17 | 266.00 | 42.83 | 0.00 |
CORE_BOTTOM | 8734.17 | 25.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8729.67 | 30.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8681.83 | 78.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8674.83 | 85.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8292.00 | 468.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8662.50 | 97.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8682.17 | 77.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8534.83 | 225.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8727.50 | 32.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8653.50 | 106.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8670.17 | 89.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8529.17 | 230.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7827.33 | 932.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7811.00 | 949.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7794.67 | 965.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6644.00 | 2113.00 | 3.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8666.67 | 93.33 | 0.00 | 0.00 | 0.00 |
Min | 6644.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2113.00 | 266.00 | 42.83 | 0.00 |
Average | 8428.88 | 317.56 | 11.70 | 1.86 | 0.00 |
Sum | 193864.33 | 7303.83 | 269.00 | 42.83 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 341069.17 | 13326.33 | 10318.50 | 3902.00 | 0.00 |
CORE_BOTTOM | 330810.00 | 3.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1750.50 | 517.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1736.67 | 531.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1725.67 | 542.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 78851.67 | 24539.00 | 4.33 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 341069.17 | 24539.00 | 10318.50 | 3902.00 | 0.00 |
Average | 78000.81 | 1715.63 | 448.82 | 169.65 | 0.00 |
Sum | 1794018.67 | 39459.50 | 10322.83 | 3902.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7477.33 | 974.50 | 224.33 | 83.83 | 0.00 |
CORE_BOTTOM | 8194.83 | 565.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8280.00 | 480.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8249.50 | 510.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8254.67 | 505.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8295.83 | 464.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8223.17 | 536.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7900.83 | 859.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8268.67 | 491.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8194.50 | 565.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8201.33 | 558.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8089.33 | 670.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8263.33 | 496.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8198.83 | 561.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8207.83 | 552.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8107.17 | 652.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8344.33 | 415.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8324.67 | 435.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8320.33 | 439.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6868.83 | 1891.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8120.33 | 639.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8178.33 | 581.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7883.83 | 876.17 | 0.00 | 0.00 | 0.00 |
Min | 6868.83 | 415.67 | 0.00 | 0.00 | 0.00 |
Max | 8344.33 | 1891.17 | 224.33 | 83.83 | 0.00 |
Average | 8106.43 | 640.17 | 9.75 | 3.64 | 0.00 |
Sum | 186447.83 | 14724.00 | 224.33 | 83.83 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 339021.17 | 15561.50 | 7738.50 | 6294.83 | 0.00 |
CORE_BOTTOM | 329751.17 | 1061.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330102.00 | 711.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 329983.00 | 830.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38923.50 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18353.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38924.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38923.17 | 1.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24907.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38923.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24908.00 | 1.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1993.67 | 274.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1979.33 | 288.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1976.00 | 292.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 81233.33 | 22161.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 339021.17 | 22161.67 | 7738.50 | 6294.83 | 0.00 |
Average | 77933.91 | 1790.86 | 336.46 | 273.69 | 0.00 |
Sum | 1792480.00 | 41189.67 | 7738.50 | 6294.83 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331684E+11 | 92417.10 | 02-JAN-07:03 | -1.1 | -1.7 | 0.566865E+10 | 7499.29 | 11-JAN-10:09 | 7.98 | 6.90 |
February | 0.310327E+11 | 91068.57 | 21-FEB-07:03 | -13.9 | -14.7 | 0.514237E+10 | 7499.26 | 01-FEB-10:20 | -13.9 | -14.7 |
March | 0.428714E+11 | 90294.70 | 16-MAR-06:12 | 11.67 | 10.33 | 0.614522E+10 | 7499.39 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.429859E+11 | 92866.98 | 24-APR-06:03 | 1.38 | 0.25 | 0.546419E+10 | 7499.30 | 12-APR-13:09 | 1.38 | 0.25 |
May | 0.444589E+11 | 95884.71 | 30-MAY-06:11 | 12.20 | 11.93 | 0.594063E+10 | 9588.73 | 17-MAY-09:00 | 12.20 | 11.93 |
June | 0.419504E+11 | 98482.55 | 13-JUN-06:05 | 8.80 | 7.96 | 0.641006E+10 | 11201.90 | 27-JUN-13:00 | 27.20 | 22.77 |
July | 0.381496E+11 | 100273.11 | 12-JUL-06:11 | 14.83 | 11.88 | 0.639684E+10 | 11603.35 | 21-JUL-13:00 | 31.70 | 21.73 |
August | 0.504549E+11 | 97516.34 | 21-AUG-06:11 | 14.80 | 13.30 | 0.662954E+10 | 11631.76 | 15-AUG-13:00 | 14.80 | 13.30 |
September | 0.474156E+11 | 98372.82 | 11-SEP-06:11 | 11.70 | 9.59 | 0.559998E+10 | 10197.85 | 14-SEP-08:39 | 20.20 | 18.93 |
October | 0.496800E+11 | 98278.66 | 23-OCT-06:11 | 11.50 | 10.45 | 0.569179E+10 | 7499.31 | 27-OCT-13:09 | 9.78 | 7.31 |
November | 0.467184E+11 | 94375.72 | 13-NOV-07:05 | 6.20 | 5.12 | 0.563204E+10 | 7499.39 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.408141E+11 | 94505.07 | 26-DEC-07:03 | -12.3 | -13.4 | 0.548167E+10 | 7499.18 | 26-DEC-14:30 | -9.4 | -11.0 |
Annual Sum or Average | 0.509700E+12 | 0.702030E+11 | ||||||||
Minimum of Months | 0.310327E+11 | 90294.70 | -13.9 | -14.7 | 0.514237E+10 | 7499.18 | -13.9 | -14.7 | ||
Maximum of Months | 0.504549E+11 | 100273.11 | 14.83 | 13.30 | 0.662954E+10 | 11631.76 | 31.70 | 22.77 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.275631E+11 | 70856.08 | 17-JAN-06:03 | 7.20 | 2.95 | 0.502553E+10 | 6734.83 | 11-JAN-10:09 | 7.20 | 2.95 |
February | 0.268042E+11 | 73570.87 | 24-FEB-06:02 | -7.2 | -8.2 | 0.457435E+10 | 6734.82 | 06-FEB-10:20 | -7.2 | -8.2 |
March | 0.416839E+11 | 83343.35 | 16-MAR-04:13 | 18.13 | 13.40 | 0.549529E+10 | 6734.91 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.463580E+11 | 82919.80 | 10-APR-04:12 | 3.50 | 2.94 | 0.488270E+10 | 6734.81 | 19-APR-09:20 | 9.07 | 6.91 |
May | 0.452829E+11 | 85480.99 | 30-MAY-04:12 | 12.20 | 11.68 | 0.528607E+10 | 6734.88 | 10-MAY-09:09 | 12.20 | 11.68 |
June | 0.564437E+11 | 88467.23 | 28-JUN-04:13 | 17.60 | 15.52 | 0.527024E+10 | 6735.15 | 22-JUN-13:09 | 17.60 | 15.52 |
July | 0.664819E+11 | 83542.48 | 10-JUL-04:13 | 13.70 | 13.03 | 0.489695E+10 | 6746.54 | 24-JUL-09:00 | 23.90 | 17.87 |
August | 0.694600E+11 | 81693.88 | 22-AUG-04:13 | 14.40 | 12.82 | 0.549722E+10 | 6737.81 | 16-AUG-09:00 | 14.40 | 12.82 |
September | 0.470563E+11 | 86409.35 | 18-SEP-04:12 | 10.20 | 9.28 | 0.488307E+10 | 6735.19 | 12-SEP-13:09 | 10.20 | 9.28 |
October | 0.434893E+11 | 83187.45 | 10-OCT-04:12 | 10.00 | 8.72 | 0.507856E+10 | 6734.78 | 10-OCT-09:20 | 14.80 | 11.94 |
November | 0.403698E+11 | 83893.09 | 13-NOV-05:11 | 5.57 | 4.40 | 0.502976E+10 | 6734.88 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.347809E+11 | 78045.20 | 18-DEC-05:01 | 1.70 | 0.81 | 0.489439E+10 | 6734.79 | 08-DEC-10:39 | 1.70 | 0.81 |
Annual Sum or Average | 0.545774E+12 | 0.608141E+11 | ||||||||
Minimum of Months | 0.268042E+11 | 70856.08 | -7.2 | -8.2 | 0.457435E+10 | 6734.78 | -7.2 | -8.2 | ||
Maximum of Months | 0.694600E+11 | 88467.23 | 18.13 | 15.52 | 0.549722E+10 | 6746.54 | 23.90 | 17.87 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176768E+11 | 17777.31 | 06-JAN-11:20 | -5.0 | -6.7 | 0.430457E+10 | 6447.52 | 20-JAN-14:00 | 0.60 | -3.3 |
February | 0.171488E+11 | 19443.80 | 28-FEB-11:48 | -1.3 | -3.8 | 0.397102E+10 | 6525.37 | 17-FEB-14:00 | -1.3 | -3.8 |
March | 0.256186E+11 | 70141.97 | 17-MAR-05:02 | 10.50 | 9.94 | 0.529146E+10 | 6734.84 | 16-MAR-13:00 | 10.50 | 9.94 |
April | 0.278996E+11 | 67796.30 | 10-APR-05:03 | 3.98 | 3.28 | 0.482446E+10 | 6777.57 | 04-APR-09:00 | 3.98 | 3.28 |
May | 0.358170E+11 | 73480.50 | 30-MAY-04:12 | 12.20 | 11.68 | 0.527007E+10 | 6734.88 | 10-MAY-09:09 | 12.20 | 11.68 |
June | 0.411832E+11 | 73101.42 | 30-JUN-04:12 | 16.50 | 15.77 | 0.526246E+10 | 6735.14 | 22-JUN-13:09 | 16.50 | 15.77 |
July | 0.423903E+11 | 73281.18 | 06-JUL-04:12 | 12.03 | 9.89 | 0.489158E+10 | 6734.79 | 03-JUL-13:30 | 12.03 | 9.89 |
August | 0.440334E+11 | 73400.78 | 01-AUG-04:12 | 12.23 | 11.69 | 0.549351E+10 | 6735.11 | 02-AUG-13:09 | 23.90 | 16.41 |
September | 0.362363E+11 | 75141.46 | 18-SEP-04:12 | 10.20 | 9.28 | 0.487071E+10 | 6735.19 | 12-SEP-13:09 | 10.20 | 9.28 |
October | 0.286909E+11 | 70282.17 | 13-OCT-05:03 | 10.50 | 10.16 | 0.502492E+10 | 6734.79 | 10-OCT-09:09 | 10.50 | 10.16 |
November | 0.228416E+11 | 65187.39 | 01-NOV-05:02 | 5.68 | 3.03 | 0.489411E+10 | 6743.67 | 02-NOV-13:09 | 7.12 | 3.81 |
December | 0.191724E+11 | 19655.64 | 01-DEC-17:00 | 7.20 | 4.89 | 0.430692E+10 | 6734.28 | 01-DEC-14:50 | 7.20 | 4.89 |
Annual Sum or Average | 0.358709E+12 | 0.584058E+11 | ||||||||
Minimum of Months | 0.171488E+11 | 17777.31 | -5.0 | -6.7 | 0.397102E+10 | 6447.52 | -1.3 | -3.8 | ||
Maximum of Months | 0.440334E+11 | 75141.46 | 16.50 | 15.77 | 0.549351E+10 | 6777.57 | 23.90 | 16.41 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105954E+11 | 13646.71 | 11-JAN-17:00 | 11.10 | 9.84 | 0.388859E+10 | 5829.09 | 12-JAN-14:00 | -5.6 | -8.1 |
February | 0.111637E+11 | 14554.07 | 28-FEB-14:10 | 0.00 | -3.0 | 0.360412E+10 | 5979.91 | 17-FEB-14:00 | 0.00 | -3.0 |
March | 0.196710E+11 | 67769.89 | 16-MAR-05:03 | 14.03 | 11.42 | 0.478015E+10 | 6736.01 | 17-MAR-09:50 | 9.90 | 9.35 |
April | 0.222930E+11 | 32566.98 | 21-APR-16:00 | 13.30 | 8.77 | 0.455697E+10 | 6734.70 | 20-APR-13:20 | 13.30 | 8.77 |
May | 0.322825E+11 | 69597.85 | 24-MAY-05:02 | 18.80 | 15.75 | 0.520857E+10 | 6736.20 | 18-MAY-09:30 | 18.80 | 15.75 |
June | 0.417611E+11 | 72488.43 | 19-JUN-04:12 | 16.70 | 15.97 | 0.525279E+10 | 6735.13 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.450714E+11 | 72489.66 | 21-JUL-05:03 | 25.60 | 23.14 | 0.489362E+10 | 6734.74 | 12-JUL-09:00 | 25.60 | 23.14 |
August | 0.445583E+11 | 75287.50 | 07-AUG-04:14 | 20.00 | 18.50 | 0.548960E+10 | 6735.11 | 02-AUG-13:09 | 20.00 | 18.50 |
September | 0.325580E+11 | 72186.21 | 18-SEP-04:12 | 10.20 | 9.28 | 0.483070E+10 | 6735.14 | 12-SEP-13:09 | 10.20 | 9.28 |
October | 0.218060E+11 | 46758.53 | 13-OCT-05:03 | 10.50 | 10.16 | 0.469515E+10 | 6734.73 | 12-OCT-09:20 | 10.50 | 10.16 |
November | 0.160214E+11 | 19288.34 | 01-NOV-16:00 | 9.40 | 6.91 | 0.429278E+10 | 6734.53 | 01-NOV-13:20 | 9.40 | 6.91 |
December | 0.115634E+11 | 14429.76 | 01-DEC-17:00 | 7.20 | 4.89 | 0.379217E+10 | 6084.45 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.309345E+12 | 0.552852E+11 | ||||||||
Minimum of Months | 0.105954E+11 | 13646.71 | 0.00 | -3.0 | 0.360412E+10 | 5829.09 | -5.6 | -8.1 | ||
Maximum of Months | 0.450714E+11 | 75287.50 | 25.60 | 23.14 | 0.548960E+10 | 6736.20 | 25.60 | 23.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136579E+10 | 2104.98 | 17-JAN-06:03 | 7.20 | 2.95 | 0.502329E+09 | 783.80 | 17-JAN-14:00 | 6.70 | 5.64 |
February | 0.148792E+10 | 2091.87 | 28-FEB-13:30 | 0.00 | -2.9 | 0.474093E+09 | 803.31 | 22-FEB-14:00 | 0.00 | -2.9 |
March | 0.327208E+10 | 8857.83 | 16-MAR-04:11 | 18.13 | 13.40 | 0.638860E+09 | 845.65 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.431024E+10 | 6677.74 | 07-APR-13:30 | 20.00 | 10.05 | 0.601275E+09 | 845.63 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.568650E+10 | 8689.30 | 24-MAY-05:02 | 18.80 | 15.75 | 0.660093E+09 | 845.64 | 10-MAY-09:09 | 18.80 | 15.75 |
June | 0.912727E+10 | 15388.11 | 11-JUN-18:41 | 24.08 | 17.29 | 0.661977E+09 | 845.82 | 27-JUN-13:00 | 27.20 | 22.77 |
July | 0.112345E+11 | 14988.55 | 16-JUL-15:51 | 30.60 | 23.38 | 0.615901E+09 | 847.38 | 24-JUL-09:00 | 23.90 | 17.87 |
August | 0.108013E+11 | 15203.88 | 06-AUG-16:21 | 27.80 | 18.95 | 0.690574E+09 | 846.44 | 14-AUG-13:09 | 26.47 | 20.73 |
September | 0.588291E+10 | 11724.10 | 15-SEP-05:02 | 18.30 | 16.87 | 0.610168E+09 | 845.69 | 12-SEP-13:09 | 18.30 | 16.87 |
October | 0.384334E+10 | 5665.46 | 12-OCT-12:10 | 17.20 | 13.87 | 0.621652E+09 | 845.63 | 10-OCT-09:20 | 17.20 | 13.87 |
November | 0.279207E+10 | 4559.05 | 27-NOV-12:00 | 15.00 | 10.52 | 0.599013E+09 | 845.64 | 16-NOV-14:09 | 15.00 | 10.52 |
December | 0.194431E+10 | 2570.32 | 01-DEC-13:10 | 12.97 | 11.34 | 0.518898E+09 | 845.58 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.617483E+11 | 0.719483E+10 | ||||||||
Minimum of Months | 0.136579E+10 | 2091.87 | 0.00 | -2.9 | 0.474093E+09 | 783.80 | 0.00 | -2.9 | ||
Maximum of Months | 0.112345E+11 | 15388.11 | 30.60 | 23.38 | 0.690574E+09 | 847.38 | 27.20 | 22.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.962523E+09 | 1660.87 | 12-JAN-10:10 | -9.8 | -12.2 | 0.335626E+09 | 544.95 | 06-JAN-10:30 | -9.8 | -12.2 |
February | 0.109411E+10 | 6107.09 | 28-FEB-09:35 | -5.2 | -6.5 | 0.318606E+09 | 544.95 | 28-FEB-10:09 | -3.6 | -5.3 |
March | 0.285144E+10 | 9165.44 | 21-MAR-08:55 | 1.70 | -0.5 | 0.425750E+09 | 544.97 | 14-MAR-09:50 | 1.70 | -0.5 |
April | 0.433221E+10 | 16077.30 | 23-APR-10:32 | 14.80 | 7.30 | 0.389186E+09 | 545.72 | 24-APR-09:09 | 6.28 | 2.92 |
May | 0.604810E+10 | 18250.57 | 07-MAY-07:33 | 8.90 | 6.12 | 0.426300E+09 | 545.64 | 31-MAY-09:39 | 18.13 | 13.58 |
June | 0.835489E+10 | 23357.78 | 11-JUN-08:41 | 23.03 | 15.86 | 0.426961E+09 | 546.14 | 12-JUN-09:00 | 27.80 | 19.41 |
July | 0.970107E+10 | 23538.56 | 16-JUL-09:11 | 27.03 | 22.10 | 0.397247E+09 | 547.18 | 24-JUL-09:00 | 23.90 | 17.87 |
August | 0.896109E+10 | 21511.05 | 06-AUG-09:01 | 24.18 | 17.35 | 0.445019E+09 | 546.52 | 16-AUG-09:50 | 21.42 | 16.29 |
September | 0.577819E+10 | 21820.24 | 10-SEP-08:12 | 13.67 | 10.66 | 0.394041E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.334394E+10 | 10934.42 | 11-OCT-08:50 | 14.53 | 11.11 | 0.403316E+09 | 544.96 | 03-OCT-09:00 | 14.53 | 11.11 |
November | 0.191360E+10 | 6454.22 | 03-NOV-08:55 | 3.90 | 1.83 | 0.381225E+09 | 544.96 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.109828E+10 | 3611.68 | 04-DEC-09:50 | -1.8 | -3.7 | 0.327156E+09 | 544.95 | 04-DEC-10:39 | -1.3 | -3.6 |
Annual Sum or Average | 0.544394E+11 | 0.467043E+10 | ||||||||
Minimum of Months | 0.962523E+09 | 1660.87 | -9.8 | -12.2 | 0.318606E+09 | 544.95 | -9.8 | -12.2 | ||
Maximum of Months | 0.970107E+10 | 23538.56 | 27.03 | 22.10 | 0.445019E+09 | 547.18 | 27.80 | 19.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241412E+10 | 18710.38 | 15-JAN-13:13 | 4.60 | 2.04 | 0.541356E+09 | 845.69 | 12-JAN-14:09 | 4.60 | 2.04 |
February | 0.275989E+10 | 17485.48 | 28-FEB-13:30 | 0.00 | -2.9 | 0.509484E+09 | 846.13 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.645453E+10 | 18702.55 | 15-MAR-13:30 | 25.55 | 15.84 | 0.660127E+09 | 847.21 | 14-MAR-13:00 | 25.55 | 15.84 |
April | 0.688186E+10 | 20646.70 | 23-APR-14:32 | 15.20 | 9.59 | 0.598792E+09 | 846.56 | 24-APR-13:00 | 12.80 | 6.89 |
May | 0.786382E+10 | 24238.99 | 14-MAY-13:13 | 24.27 | 17.84 | 0.658601E+09 | 845.67 | 10-MAY-13:09 | 24.27 | 17.84 |
June | 0.106594E+11 | 24386.94 | 18-JUN-14:12 | 25.77 | 20.82 | 0.661678E+09 | 845.71 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.133763E+11 | 24576.97 | 30-JUL-12:12 | 25.60 | 19.74 | 0.616233E+09 | 847.73 | 24-JUL-09:00 | 25.60 | 19.74 |
August | 0.143616E+11 | 25383.02 | 27-AUG-12:42 | 23.12 | 18.75 | 0.691065E+09 | 858.98 | 16-AUG-13:09 | 23.12 | 18.75 |
September | 0.105595E+11 | 27129.61 | 10-SEP-12:11 | 16.87 | 10.71 | 0.611470E+09 | 860.05 | 21-SEP-13:09 | 25.10 | 16.52 |
October | 0.762223E+10 | 24280.41 | 09-OCT-13:13 | 12.20 | 8.37 | 0.625384E+09 | 913.15 | 31-OCT-13:09 | 15.00 | 10.18 |
November | 0.450581E+10 | 17939.55 | 03-NOV-12:30 | 8.35 | 4.56 | 0.593778E+09 | 846.92 | 15-NOV-14:50 | 11.60 | 6.55 |
December | 0.257163E+10 | 17323.35 | 17-DEC-11:33 | 1.50 | -0.3 | 0.529750E+09 | 845.64 | 11-DEC-14:20 | 1.50 | -0.3 |
Annual Sum or Average | 0.900308E+11 | 0.729772E+10 | ||||||||
Minimum of Months | 0.241412E+10 | 17323.35 | 0.00 | -2.9 | 0.509484E+09 | 845.64 | 0.00 | -2.8 | ||
Maximum of Months | 0.143616E+11 | 27129.61 | 25.77 | 20.82 | 0.691065E+09 | 913.15 | 25.60 | 19.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139614E+10 | 4557.33 | 12-JAN-15:40 | -5.9 | -8.2 | 0.356482E+09 | 544.94 | 05-JAN-14:39 | -5.9 | -8.2 |
February | 0.189118E+10 | 9461.71 | 28-FEB-16:30 | 0.00 | -2.6 | 0.345761E+09 | 544.95 | 07-FEB-14:00 | 0.00 | -2.6 |
March | 0.551526E+10 | 22053.74 | 16-MAR-04:11 | 18.13 | 13.40 | 0.441399E+09 | 544.98 | 14-MAR-13:00 | 18.13 | 13.40 |
April | 0.813855E+10 | 26848.44 | 02-APR-16:32 | 7.23 | 5.51 | 0.395985E+09 | 544.97 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.769000E+10 | 29744.00 | 07-MAY-16:11 | 15.00 | 5.96 | 0.428417E+09 | 544.97 | 10-MAY-09:09 | 18.68 | 14.82 |
June | 0.117945E+11 | 31083.02 | 11-JUN-16:41 | 25.60 | 17.82 | 0.427832E+09 | 545.00 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.137625E+11 | 29040.62 | 02-JUL-16:41 | 25.00 | 17.06 | 0.398328E+09 | 546.36 | 24-JUL-09:00 | 23.90 | 17.87 |
August | 0.148102E+11 | 30917.81 | 06-AUG-16:21 | 27.80 | 18.95 | 0.446545E+09 | 545.33 | 16-AUG-09:00 | 21.70 | 16.44 |
September | 0.725944E+10 | 28247.91 | 10-SEP-17:31 | 16.10 | 10.54 | 0.395750E+09 | 545.00 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.526762E+10 | 17992.22 | 09-OCT-15:53 | 13.30 | 9.53 | 0.410190E+09 | 544.96 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.395289E+10 | 15747.32 | 27-NOV-05:12 | 17.97 | 12.28 | 0.405912E+09 | 544.97 | 16-NOV-14:09 | 17.97 | 12.28 |
December | 0.267109E+10 | 7861.83 | 04-DEC-15:30 | -0.3 | -3.1 | 0.387973E+09 | 544.95 | 12-DEC-14:30 | -3.9 | -4.2 |
Annual Sum or Average | 0.841493E+11 | 0.484057E+10 | ||||||||
Minimum of Months | 0.139614E+10 | 4557.33 | -5.9 | -8.2 | 0.345761E+09 | 544.94 | -5.9 | -8.2 | ||
Maximum of Months | 0.148102E+11 | 31083.02 | 27.80 | 18.95 | 0.446545E+09 | 546.36 | 23.90 | 17.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109573E+09 | 1338.95 | 11-JAN-16:00 | 11.70 | 10.14 | 0.464701E+09 | 625.90 | 31-JAN-10:09 | -11.6 | -12.7 |
February | 0.181739E+09 | 1382.57 | 17-FEB-15:00 | 3.30 | 1.08 | 0.422521E+09 | 648.35 | 17-FEB-14:00 | 3.30 | 1.08 |
March | 0.160304E+10 | 5684.89 | 15-MAR-14:00 | 26.10 | 16.06 | 0.560259E+09 | 845.64 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.239962E+10 | 4354.90 | 07-APR-13:50 | 20.00 | 10.11 | 0.544380E+09 | 845.63 | 20-APR-13:20 | 12.97 | 9.40 |
May | 0.433011E+10 | 6892.88 | 23-MAY-14:40 | 23.90 | 13.32 | 0.647660E+09 | 845.64 | 10-MAY-09:20 | 23.90 | 13.32 |
June | 0.707929E+10 | 12530.73 | 11-JUN-18:41 | 24.08 | 17.29 | 0.659920E+09 | 846.63 | 27-JUN-13:20 | 29.47 | 23.48 |
July | 0.809606E+10 | 13806.36 | 16-JUL-13:23 | 27.75 | 21.04 | 0.615308E+09 | 846.55 | 27-JUL-13:20 | 29.40 | 21.64 |
August | 0.741397E+10 | 9740.36 | 11-AUG-05:03 | 17.80 | 15.36 | 0.688502E+09 | 846.17 | 15-AUG-13:20 | 27.23 | 22.54 |
September | 0.447518E+10 | 6982.76 | 14-SEP-05:03 | 20.60 | 19.14 | 0.599779E+09 | 845.68 | 12-SEP-13:09 | 20.60 | 19.14 |
October | 0.244507E+10 | 3981.47 | 12-OCT-14:40 | 18.30 | 15.11 | 0.565601E+09 | 846.92 | 06-OCT-13:30 | 18.30 | 15.11 |
November | 0.133816E+10 | 2364.70 | 07-NOV-11:30 | 3.05 | 2.33 | 0.498607E+09 | 804.29 | 16-NOV-14:00 | 17.20 | 13.27 |
December | 0.192499E+09 | 1599.25 | 01-DEC-13:30 | 11.10 | 9.57 | 0.450305E+09 | 697.32 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.396643E+11 | 0.671754E+10 | ||||||||
Minimum of Months | 0.109573E+09 | 1338.95 | 3.05 | 1.08 | 0.422521E+09 | 625.90 | -11.6 | -12.7 | ||
Maximum of Months | 0.809606E+10 | 13806.36 | 27.75 | 21.04 | 0.688502E+09 | 846.92 | 29.47 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138541E+09 | 1322.20 | 06-JAN-11:20 | -5.0 | -6.7 | 0.219452E+09 | 449.96 | 06-JAN-11:09 | -5.0 | -6.7 |
February | 0.250068E+09 | 7632.71 | 28-FEB-09:58 | -3.9 | -5.5 | 0.206744E+09 | 548.49 | 28-FEB-11:09 | -2.0 | -4.1 |
March | 0.160634E+10 | 8611.29 | 21-MAR-10:13 | 2.97 | 0.65 | 0.289923E+09 | 548.97 | 21-MAR-10:09 | 2.97 | 0.65 |
April | 0.319238E+10 | 17058.08 | 23-APR-10:32 | 14.80 | 7.30 | 0.276523E+09 | 550.78 | 06-APR-10:09 | 14.80 | 7.30 |
May | 0.544307E+10 | 18387.25 | 21-MAY-09:12 | 16.50 | 11.82 | 0.311738E+09 | 548.51 | 26-MAY-10:09 | 18.98 | 12.55 |
June | 0.766582E+10 | 25303.35 | 11-JUN-10:01 | 24.50 | 16.94 | 0.314511E+09 | 548.52 | 22-JUN-12:09 | 19.18 | 13.72 |
July | 0.852680E+10 | 24473.60 | 04-JUL-09:12 | 21.47 | 17.29 | 0.294138E+09 | 548.52 | 12-JUL-10:09 | 20.87 | 14.79 |
August | 0.776340E+10 | 22985.74 | 20-AUG-09:42 | 20.40 | 14.16 | 0.327978E+09 | 548.61 | 17-AUG-10:09 | 20.40 | 14.16 |
September | 0.505660E+10 | 21296.17 | 04-SEP-09:02 | 16.88 | 13.13 | 0.288375E+09 | 548.52 | 12-SEP-12:09 | 20.68 | 15.09 |
October | 0.220072E+10 | 10679.70 | 11-OCT-10:05 | 17.15 | 12.50 | 0.285287E+09 | 548.50 | 10-OCT-10:09 | 17.15 | 12.50 |
November | 0.827563E+09 | 5855.24 | 03-NOV-10:05 | 5.78 | 3.09 | 0.246857E+09 | 548.49 | 16-NOV-13:09 | 18.62 | 13.01 |
December | 0.137232E+09 | 1107.81 | 04-DEC-09:55 | -1.7 | -3.7 | 0.212670E+09 | 472.33 | 04-DEC-11:09 | -0.9 | -3.4 |
Annual Sum or Average | 0.428085E+11 | 0.327420E+10 | ||||||||
Minimum of Months | 0.137232E+09 | 1107.81 | -5.0 | -6.7 | 0.206744E+09 | 449.96 | -5.0 | -6.7 | ||
Maximum of Months | 0.852680E+10 | 25303.35 | 24.50 | 17.29 | 0.327978E+09 | 550.78 | 20.87 | 15.09 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151393E+10 | 17181.17 | 15-JAN-14:33 | 5.40 | 1.82 | 0.508986E+09 | 845.85 | 06-JAN-14:09 | 5.40 | 1.82 |
February | 0.194957E+10 | 19341.54 | 28-FEB-11:48 | -1.3 | -3.8 | 0.474009E+09 | 877.69 | 28-FEB-10:00 | -1.3 | -3.8 |
March | 0.543806E+10 | 19016.79 | 01-MAR-13:50 | -0.1 | -2.5 | 0.630891E+09 | 861.68 | 06-MAR-10:20 | -7.0 | -9.1 |
April | 0.552228E+10 | 21872.36 | 23-APR-14:32 | 15.20 | 9.59 | 0.575059E+09 | 846.60 | 21-APR-13:20 | 15.20 | 9.59 |
May | 0.716922E+10 | 24330.74 | 14-MAY-13:23 | 24.45 | 17.92 | 0.650972E+09 | 845.67 | 10-MAY-13:09 | 24.45 | 17.92 |
June | 0.911415E+10 | 23825.83 | 25-JUN-13:02 | 26.10 | 17.26 | 0.659253E+09 | 847.13 | 12-JUN-13:20 | 26.10 | 17.26 |
July | 0.107211E+11 | 24558.54 | 30-JUL-12:32 | 25.60 | 19.52 | 0.615720E+09 | 847.21 | 19-JUL-13:20 | 25.60 | 19.52 |
August | 0.116363E+11 | 25313.10 | 27-AUG-13:12 | 23.50 | 18.92 | 0.689863E+09 | 847.09 | 02-AUG-13:20 | 23.50 | 18.92 |
September | 0.101173E+11 | 26457.80 | 03-SEP-12:32 | 19.03 | 12.28 | 0.607847E+09 | 892.62 | 21-SEP-13:20 | 25.20 | 16.54 |
October | 0.690466E+10 | 25264.39 | 09-OCT-11:42 | 11.60 | 7.43 | 0.612364E+09 | 964.06 | 31-OCT-13:39 | 15.00 | 10.41 |
November | 0.346112E+10 | 18993.80 | 03-NOV-12:30 | 8.35 | 4.56 | 0.551204E+09 | 847.43 | 02-NOV-13:09 | 8.35 | 4.56 |
December | 0.122499E+10 | 12592.87 | 04-DEC-11:50 | -0.2 | -2.9 | 0.478213E+09 | 845.65 | 11-DEC-14:30 | -8.1 | -9.1 |
Annual Sum or Average | 0.747727E+11 | 0.705438E+10 | ||||||||
Minimum of Months | 0.122499E+10 | 12592.87 | -1.3 | -3.8 | 0.474009E+09 | 845.65 | -8.1 | -9.1 | ||
Maximum of Months | 0.116363E+11 | 26457.80 | 26.10 | 19.52 | 0.689863E+09 | 964.06 | 26.10 | 19.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248534E+09 | 1477.90 | 12-JAN-15:50 | -6.0 | -8.3 | 0.304717E+09 | 521.18 | 12-JAN-16:30 | -6.4 | -8.3 |
February | 0.459329E+09 | 6005.83 | 28-FEB-16:30 | 0.00 | -2.6 | 0.282621E+09 | 544.91 | 28-FEB-14:00 | 0.00 | -2.6 |
March | 0.214003E+10 | 8990.06 | 21-MAR-16:00 | 4.40 | 1.34 | 0.386989E+09 | 544.97 | 16-MAR-13:00 | 4.40 | 1.34 |
April | 0.344430E+10 | 23688.14 | 30-APR-15:51 | 15.00 | 12.10 | 0.369018E+09 | 544.96 | 20-APR-13:30 | 15.00 | 12.10 |
May | 0.579733E+10 | 24859.64 | 07-MAY-16:32 | 15.00 | 5.92 | 0.422383E+09 | 544.96 | 10-MAY-09:09 | 18.68 | 14.82 |
June | 0.870321E+10 | 28545.69 | 11-JUN-16:41 | 25.60 | 17.82 | 0.426411E+09 | 544.99 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.909665E+10 | 26702.00 | 02-JUL-17:21 | 24.45 | 16.81 | 0.397526E+09 | 544.98 | 03-JUL-13:30 | 25.00 | 16.74 |
August | 0.862613E+10 | 25822.48 | 27-AUG-16:31 | 22.57 | 18.97 | 0.445362E+09 | 545.00 | 02-AUG-13:09 | 22.57 | 18.97 |
September | 0.525304E+10 | 24567.92 | 04-SEP-17:02 | 18.03 | 12.75 | 0.391058E+09 | 545.00 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.257924E+10 | 11766.06 | 11-OCT-16:00 | 21.70 | 14.52 | 0.381074E+09 | 544.95 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.125019E+10 | 5071.86 | 15-NOV-15:20 | 11.70 | 6.66 | 0.340960E+09 | 544.96 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.339826E+09 | 1984.82 | 04-DEC-15:50 | -0.5 | -3.2 | 0.295159E+09 | 521.53 | 04-DEC-14:00 | -0.5 | -3.2 |
Annual Sum or Average | 0.479378E+11 | 0.444328E+10 | ||||||||
Minimum of Months | 0.248534E+09 | 1477.90 | -6.0 | -8.3 | 0.282621E+09 | 521.18 | -6.4 | -8.3 | ||
Maximum of Months | 0.909665E+10 | 28545.69 | 25.60 | 18.97 | 0.445362E+09 | 545.00 | 25.00 | 18.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21236594.94 | 1209.01 | 14-JAN-17:03 | 3.22 | 2.72 | 0.462791E+09 | 625.93 | 31-JAN-10:09 | -11.6 | -12.7 |
February | 55252478.27 | 1310.56 | 22-FEB-16:30 | 11.15 | 5.29 | 0.419481E+09 | 625.94 | 21-FEB-10:50 | 11.15 | 5.29 |
March | 0.110594E+10 | 6188.31 | 15-MAR-14:30 | 25.85 | 16.15 | 0.540283E+09 | 845.64 | 15-MAR-13:30 | 25.85 | 16.15 |
April | 0.187023E+10 | 4111.29 | 20-APR-15:40 | 14.80 | 10.94 | 0.513359E+09 | 845.62 | 20-APR-13:20 | 14.80 | 10.94 |
May | 0.397908E+10 | 7165.33 | 23-MAY-14:40 | 23.90 | 13.32 | 0.630394E+09 | 845.64 | 10-MAY-13:50 | 23.90 | 13.32 |
June | 0.715375E+10 | 11528.70 | 18-JUN-11:43 | 26.02 | 20.76 | 0.656983E+09 | 846.05 | 12-JUN-13:50 | 26.02 | 20.76 |
July | 0.847366E+10 | 16093.46 | 16-JUL-15:51 | 30.60 | 23.38 | 0.615175E+09 | 845.73 | 20-JUL-13:00 | 30.00 | 23.95 |
August | 0.752200E+10 | 15864.08 | 13-AUG-15:31 | 29.60 | 23.37 | 0.686189E+09 | 845.69 | 02-AUG-13:09 | 29.60 | 23.37 |
September | 0.413048E+10 | 7064.42 | 15-SEP-14:00 | 25.60 | 21.03 | 0.586656E+09 | 845.68 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.176552E+10 | 3864.53 | 12-OCT-15:00 | 18.30 | 15.23 | 0.530553E+09 | 845.61 | 12-OCT-13:00 | 18.30 | 15.23 |
November | 0.564831E+09 | 1786.38 | 16-NOV-16:50 | 18.12 | 13.51 | 0.471616E+09 | 756.67 | 16-NOV-14:00 | 18.12 | 13.51 |
December | 58726256.70 | 1375.67 | 01-DEC-13:30 | 11.10 | 9.57 | 0.446157E+09 | 632.12 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.367007E+11 | 0.655964E+10 | ||||||||
Minimum of Months | 21236594.94 | 1209.01 | 3.22 | 2.72 | 0.419481E+09 | 625.93 | -11.6 | -12.7 | ||
Maximum of Months | 0.847366E+10 | 16093.46 | 30.60 | 23.38 | 0.686189E+09 | 846.05 | 30.00 | 23.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41960832.11 | 905.68 | 20-JAN-06:04 | -0.7 | -3.0 | 0.299108E+09 | 414.79 | 06-JAN-10:50 | -0.7 | -3.0 |
February | 0.211944E+09 | 1821.62 | 28-FEB-10:10 | -3.6 | -5.3 | 0.277434E+09 | 544.96 | 28-FEB-10:09 | -3.6 | -5.3 |
March | 0.136875E+10 | 5932.02 | 15-MAR-09:30 | 20.25 | 14.29 | 0.377282E+09 | 544.97 | 15-MAR-13:30 | 25.55 | 15.84 |
April | 0.283058E+10 | 12248.17 | 23-APR-10:32 | 14.80 | 7.30 | 0.362433E+09 | 544.96 | 21-APR-13:00 | 14.80 | 7.30 |
May | 0.527858E+10 | 16676.01 | 21-MAY-10:53 | 16.70 | 11.75 | 0.418511E+09 | 545.33 | 31-MAY-09:30 | 18.05 | 13.49 |
June | 0.790336E+10 | 23134.04 | 11-JUN-09:32 | 24.03 | 16.62 | 0.426000E+09 | 545.99 | 20-JUN-09:00 | 23.30 | 16.76 |
July | 0.907802E+10 | 26331.15 | 16-JUL-09:11 | 27.03 | 22.10 | 0.397341E+09 | 545.98 | 13-JUL-09:50 | 27.03 | 22.10 |
August | 0.810009E+10 | 21090.97 | 06-AUG-09:12 | 24.47 | 17.45 | 0.444350E+09 | 545.98 | 04-AUG-09:00 | 24.47 | 17.45 |
September | 0.494042E+10 | 23057.63 | 10-SEP-10:02 | 15.68 | 10.52 | 0.387007E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.180800E+10 | 8111.34 | 11-OCT-09:30 | 15.85 | 11.81 | 0.371906E+09 | 544.95 | 31-OCT-13:20 | 15.00 | 10.26 |
November | 0.528741E+09 | 2320.50 | 03-NOV-09:50 | 5.32 | 2.80 | 0.315314E+09 | 544.95 | 03-NOV-09:09 | 5.32 | 2.80 |
December | 55709948.19 | 912.28 | 13-DEC-06:04 | 1.20 | 0.92 | 0.288567E+09 | 422.64 | 04-DEC-10:30 | 1.20 | 0.92 |
Annual Sum or Average | 0.421462E+11 | 0.436525E+10 | ||||||||
Minimum of Months | 41960832.11 | 905.68 | -3.6 | -5.3 | 0.277434E+09 | 414.79 | -3.6 | -5.3 | ||
Maximum of Months | 0.907802E+10 | 26331.15 | 27.03 | 22.10 | 0.444350E+09 | 545.99 | 27.03 | 22.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100797E+10 | 12401.71 | 12-JAN-13:40 | -6.5 | -9.0 | 0.497489E+09 | 845.64 | 30-JAN-14:20 | -8.2 | -9.8 |
February | 0.146458E+10 | 16907.06 | 28-FEB-13:55 | 0.00 | -3.0 | 0.460432E+09 | 845.79 | 28-FEB-14:09 | 0.00 | -3.0 |
March | 0.434371E+10 | 18868.88 | 15-MAR-13:30 | 25.55 | 15.84 | 0.606241E+09 | 846.46 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.466752E+10 | 19295.58 | 23-APR-14:32 | 15.20 | 9.59 | 0.550299E+09 | 846.12 | 24-APR-13:00 | 12.80 | 6.89 |
May | 0.670211E+10 | 26662.14 | 14-MAY-13:42 | 24.82 | 18.07 | 0.637069E+09 | 845.69 | 10-MAY-13:50 | 24.82 | 18.07 |
June | 0.919475E+10 | 25766.61 | 25-JUN-13:02 | 26.10 | 17.26 | 0.655969E+09 | 846.13 | 12-JUN-13:39 | 26.10 | 17.26 |
July | 0.111850E+11 | 26524.42 | 30-JUL-12:32 | 25.60 | 19.52 | 0.615051E+09 | 846.59 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.117837E+11 | 26884.97 | 13-AUG-12:12 | 29.27 | 22.26 | 0.687895E+09 | 846.53 | 03-AUG-13:00 | 29.27 | 22.26 |
September | 0.958348E+10 | 29671.73 | 10-SEP-12:41 | 17.12 | 10.59 | 0.599159E+09 | 871.05 | 21-SEP-13:30 | 25.30 | 16.56 |
October | 0.561504E+10 | 21779.16 | 31-OCT-13:30 | 15.00 | 10.33 | 0.587181E+09 | 901.61 | 31-OCT-13:39 | 15.00 | 10.41 |
November | 0.229302E+10 | 16829.60 | 03-NOV-12:40 | 8.53 | 4.68 | 0.519386E+09 | 845.66 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.727991E+09 | 10321.58 | 16-DEC-13:30 | 5.60 | 3.03 | 0.466282E+09 | 845.64 | 11-DEC-14:30 | 5.60 | 3.03 |
Annual Sum or Average | 0.685689E+11 | 0.688245E+10 | ||||||||
Minimum of Months | 0.727991E+09 | 10321.58 | -6.5 | -9.0 | 0.460432E+09 | 845.64 | -8.2 | -9.8 | ||
Maximum of Months | 0.117837E+11 | 29671.73 | 29.27 | 22.26 | 0.687895E+09 | 901.61 | 29.27 | 22.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127388E+09 | 1239.68 | 12-JAN-16:00 | -6.1 | -8.3 | 0.301563E+09 | 499.10 | 12-JAN-16:10 | -6.2 | -8.3 |
February | 0.323868E+09 | 5786.65 | 28-FEB-16:30 | 0.00 | -2.6 | 0.278783E+09 | 544.71 | 28-FEB-14:00 | 0.00 | -2.6 |
March | 0.172755E+10 | 8427.48 | 21-MAR-16:00 | 4.40 | 1.34 | 0.372547E+09 | 544.97 | 15-MAR-13:30 | 4.40 | 1.34 |
April | 0.302574E+10 | 14979.31 | 30-APR-17:03 | 14.82 | 11.93 | 0.351046E+09 | 544.96 | 21-APR-13:00 | 14.82 | 11.93 |
May | 0.556653E+10 | 28267.26 | 07-MAY-17:41 | 14.08 | 5.36 | 0.414045E+09 | 544.97 | 10-MAY-13:50 | 25.92 | 17.78 |
June | 0.875116E+10 | 27482.90 | 11-JUN-16:51 | 25.60 | 17.82 | 0.424971E+09 | 544.99 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.941732E+10 | 28322.86 | 02-JUL-17:01 | 24.82 | 16.94 | 0.397333E+09 | 544.96 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.872447E+10 | 26685.16 | 13-AUG-15:31 | 29.60 | 23.37 | 0.444569E+09 | 545.00 | 02-AUG-13:09 | 29.60 | 23.37 |
September | 0.500407E+10 | 27537.65 | 10-SEP-16:01 | 17.52 | 11.16 | 0.385295E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.212285E+10 | 11719.93 | 11-OCT-16:00 | 21.70 | 14.52 | 0.361955E+09 | 544.95 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.779459E+09 | 4184.31 | 15-NOV-15:20 | 11.70 | 6.66 | 0.320752E+09 | 544.93 | 09-NOV-14:00 | 11.70 | 6.66 |
December | 0.171284E+09 | 1265.41 | 04-DEC-15:50 | -0.5 | -3.2 | 0.290985E+09 | 506.42 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.457417E+11 | 0.434384E+10 | ||||||||
Minimum of Months | 0.127388E+09 | 1239.68 | -6.1 | -8.3 | 0.278783E+09 | 499.10 | -6.2 | -8.3 | ||
Maximum of Months | 0.941732E+10 | 28322.86 | 29.60 | 23.37 | 0.444569E+09 | 545.00 | 29.60 | 23.37 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150775E+09 | 6164.40 | 04-JAN-06:01 | -12.3 | -12.9 | 0.00 | 0.00 | 01-JAN-00:10 | -12.3 | -12.9 |
February | 0.129694E+09 | 6015.11 | 06-FEB-05:01 | -14.8 | -15.7 | 0.00 | 0.00 | 01-FEB-00:10 | -14.8 | -15.7 |
March | 0.160324E+10 | 5282.73 | 16-MAR-05:15 | 13.67 | 11.27 | 0.00 | 0.00 | 01-MAR-00:10 | 13.67 | 11.27 |
April | 0.333298E+10 | 6730.29 | 10-APR-05:15 | 4.07 | 3.41 | 0.00 | 0.00 | 01-APR-00:10 | 4.07 | 3.41 |
May | 0.436002E+10 | 8121.53 | 30-MAY-05:15 | 12.20 | 11.93 | 0.00 | 0.00 | 01-MAY-00:10 | 12.20 | 11.93 |
June | 0.741634E+10 | 10532.28 | 28-JUN-05:10 | 17.20 | 15.14 | 0.00 | 0.00 | 01-JUN-00:10 | 17.20 | 15.14 |
July | 0.915983E+10 | 11069.81 | 24-JUL-05:15 | 16.10 | 15.07 | 0.00 | 0.00 | 01-JUL-00:10 | 16.10 | 15.07 |
August | 0.906216E+10 | 11000.36 | 14-AUG-05:15 | 22.80 | 21.58 | 0.00 | 0.00 | 01-AUG-00:10 | 22.80 | 21.58 |
September | 0.542942E+10 | 9097.26 | 18-SEP-05:10 | 9.50 | 8.65 | 0.00 | 0.00 | 01-SEP-00:10 | 9.50 | 8.65 |
October | 0.315615E+10 | 6616.72 | 23-OCT-05:15 | 11.70 | 10.06 | 0.00 | 0.00 | 01-OCT-00:10 | 11.70 | 10.06 |
November | 0.189770E+10 | 5289.07 | 06-NOV-06:15 | 8.90 | 6.78 | 0.00 | 0.00 | 01-NOV-00:10 | 8.90 | 6.78 |
December | 0.309135E+09 | 4633.52 | 28-DEC-06:01 | -12.2 | -12.5 | 0.00 | 0.00 | 01-DEC-00:10 | -12.2 | -12.5 |
Annual Sum or Average | 0.460075E+11 | 0.00 | ||||||||
Minimum of Months | 0.129694E+09 | 4633.52 | -14.8 | -15.7 | 0.00 | 0.00 | -14.8 | -15.7 | ||
Maximum of Months | 0.915983E+10 | 11069.81 | 22.80 | 21.58 | 0.00 | 0.00 | 22.80 | 21.58 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 96069962.77 | 9028.63 | 24-JAN-04:01 | -11.7 | -13.2 | 0.00 | 0.00 | 01-JAN-00:10 | -11.7 | -13.2 |
February | 0.104983E+09 | 9866.37 | 21-FEB-04:11 | -11.3 | -12.5 | 0.00 | 0.00 | 01-FEB-00:10 | -11.3 | -12.5 |
March | 0.474644E+09 | 9888.31 | 04-MAR-05:11 | -10.2 | -11.1 | 0.00 | 0.00 | 01-MAR-00:10 | -10.2 | -11.1 |
April | 0.894065E+09 | 5221.13 | 17-APR-05:01 | -4.0 | -5.3 | 0.00 | 0.00 | 01-APR-00:10 | -4.0 | -5.3 |
May | 0.251046E+10 | 4269.51 | 30-MAY-05:15 | 12.20 | 11.93 | 0.00 | 0.00 | 01-MAY-00:10 | 12.20 | 11.93 |
June | 0.483083E+10 | 5676.12 | 21-JUN-05:15 | 18.30 | 16.18 | 0.00 | 0.00 | 01-JUN-00:10 | 18.30 | 16.18 |
July | 0.601541E+10 | 6401.71 | 17-JUL-10:20 | 25.77 | 20.61 | 0.00 | 0.00 | 01-JUL-00:10 | 25.77 | 20.61 |
August | 0.583478E+10 | 7094.26 | 07-AUG-05:15 | 20.20 | 18.58 | 0.00 | 0.00 | 01-AUG-00:10 | 20.20 | 18.58 |
September | 0.343980E+10 | 5619.20 | 18-SEP-05:15 | 9.60 | 8.73 | 0.00 | 0.00 | 01-SEP-00:10 | 9.60 | 8.73 |
October | 0.108559E+10 | 6329.05 | 17-OCT-05:02 | -2.8 | -3.4 | 0.00 | 0.00 | 01-OCT-00:10 | -2.8 | -3.4 |
November | 0.385989E+09 | 7669.55 | 24-NOV-05:01 | -3.0 | -3.7 | 0.00 | 0.00 | 01-NOV-00:10 | -3.0 | -3.7 |
December | 0.154443E+09 | 8476.33 | 27-DEC-04:11 | -11.7 | -12.1 | 0.00 | 0.00 | 01-DEC-00:10 | -11.7 | -12.1 |
Annual Sum or Average | 0.258271E+11 | 0.00 | ||||||||
Minimum of Months | 96069962.77 | 4269.51 | -11.7 | -13.2 | 0.00 | 0.00 | -11.7 | -13.2 | ||
Maximum of Months | 0.601541E+10 | 9888.31 | 25.77 | 20.61 | 0.00 | 0.00 | 25.77 | 20.61 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
March | 0.485280E+09 | 10569.41 | 15-MAR-14:20 | 25.93 | 16.12 | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 16.12 |
April | 0.167453E+10 | 8983.64 | 21-APR-14:00 | 14.40 | 8.43 | 0.00 | 0.00 | 01-APR-00:10 | 14.40 | 8.43 |
May | 0.485292E+10 | 13230.58 | 31-MAY-14:20 | 21.70 | 14.12 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 14.12 |
June | 0.925985E+10 | 17707.00 | 12-JUN-13:40 | 30.20 | 20.07 | 0.00 | 0.00 | 01-JUN-00:10 | 30.20 | 20.07 |
July | 0.112537E+11 | 17290.00 | 21-JUL-13:40 | 31.33 | 21.85 | 0.00 | 0.00 | 01-JUL-00:10 | 31.33 | 21.85 |
August | 0.979907E+10 | 16962.48 | 09-AUG-15:20 | 29.40 | 18.24 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.24 |
September | 0.478240E+10 | 12830.02 | 21-SEP-15:40 | 26.10 | 17.00 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.00 |
October | 0.839114E+09 | 6912.11 | 11-OCT-15:40 | 21.87 | 14.55 | 0.00 | 0.00 | 01-OCT-00:10 | 21.87 | 14.55 |
November | 25863932.36 | 1071.87 | 04-NOV-15:20 | 18.30 | 13.65 | 0.00 | 0.00 | 01-NOV-00:10 | 18.30 | 13.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.429727E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 0.00 | 0.00 | -3.3 | -4.7 | ||
Maximum of Months | 0.112537E+11 | 17707.00 | 31.33 | 21.85 | 0.00 | 0.00 | 31.33 | 21.85 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225726E+10 | 1850.67 | 12-JAN-16:40 | -6.5 | -8.3 | 95230015.12 | 126.82 | 12-JAN-10:09 | -6.5 | -8.3 |
February | 0.701816E+10 | 4065.94 | 28-FEB-17:00 | -0.6 | -3.0 | 86396461.23 | 126.82 | 21-FEB-10:39 | -0.6 | -3.0 |
March | 0.138789E+11 | 6981.42 | 31-MAR-24:00 | 4.20 | 3.93 | 0.103237E+09 | 126.83 | 14-MAR-09:00 | 4.20 | 3.93 |
April | 0.187026E+11 | 8178.36 | 02-APR-17:58 | 6.10 | 4.84 | 91605160.47 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.425563E+10 | 3447.57 | 31-MAY-24:00 | 17.10 | 14.03 | 99235773.30 | 126.84 | 17-MAY-13:09 | 17.10 | 14.03 |
June | 0.934766E+10 | 5362.59 | 30-JUN-24:00 | 16.90 | 13.02 | 98966637.87 | 126.86 | 27-JUN-13:00 | 16.90 | 13.02 |
July | 0.148036E+11 | 7268.09 | 31-JUL-24:00 | 19.10 | 16.93 | 91889062.41 | 126.85 | 05-JUL-13:00 | 19.10 | 16.93 |
August | 0.197579E+11 | 8191.91 | 02-AUG-18:50 | 21.88 | 14.61 | 0.103239E+09 | 126.83 | 30-AUG-09:00 | 17.80 | 17.48 |
September | 0.424214E+10 | 3224.05 | 30-SEP-24:00 | 14.40 | 12.09 | 91610577.51 | 126.85 | 25-SEP-13:09 | 14.40 | 12.09 |
October | 0.907906E+10 | 5140.24 | 31-OCT-24:00 | 6.60 | 4.77 | 95232202.47 | 126.84 | 12-OCT-13:00 | 6.60 | 4.77 |
November | 0.134979E+11 | 5758.38 | 24-NOV-16:20 | 3.87 | 1.42 | 94300313.35 | 126.82 | 10-NOV-14:00 | 3.87 | 1.42 |
December | 0.185184E+11 | 7646.42 | 04-DEC-16:20 | -1.1 | -3.7 | 91880854.46 | 126.82 | 01-DEC-14:09 | -1.1 | -3.7 |
Annual Sum or Average | 0.135359E+12 | 0.114282E+10 | ||||||||
Minimum of Months | 0.225726E+10 | 1850.67 | -6.5 | -8.3 | 86396461.23 | 126.82 | -6.5 | -8.3 | ||
Maximum of Months | 0.197579E+11 | 8191.91 | 21.88 | 16.93 | 0.103239E+09 | 126.86 | 19.10 | 17.48 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256231E+09 | 1435.81 | 12-JAN-16:50 | -6.6 | -8.3 | 92514155.54 | 126.82 | 12-JAN-14:09 | -6.6 | -8.3 |
February | 0.412965E+10 | 3531.80 | 28-FEB-17:00 | -0.6 | -3.0 | 86396473.76 | 126.82 | 21-FEB-10:39 | -0.6 | -3.0 |
March | 0.115630E+11 | 6207.41 | 31-MAR-23:40 | 4.40 | 4.06 | 0.103237E+09 | 126.83 | 14-MAR-09:00 | 4.40 | 4.06 |
April | 0.168674E+11 | 7629.63 | 24-APR-18:00 | 11.70 | 8.10 | 91605169.47 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.358673E+10 | 3259.10 | 31-MAY-24:00 | 17.10 | 14.03 | 99235614.23 | 126.84 | 24-MAY-09:00 | 17.10 | 14.03 |
June | 0.865231E+10 | 5113.74 | 30-JUN-24:00 | 16.90 | 13.02 | 98966270.33 | 126.86 | 27-JUN-13:00 | 16.90 | 13.02 |
July | 0.139677E+11 | 6983.65 | 31-JUL-24:00 | 19.10 | 16.93 | 91888988.16 | 126.84 | 05-JUL-13:00 | 19.10 | 16.93 |
August | 0.186984E+11 | 7859.55 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103239E+09 | 126.83 | 30-AUG-09:00 | 17.80 | 17.48 |
September | 0.356617E+10 | 2758.58 | 30-SEP-24:00 | 14.40 | 12.09 | 91609101.88 | 126.84 | 08-SEP-13:39 | 14.40 | 12.09 |
October | 0.749452E+10 | 4503.74 | 31-OCT-23:50 | 6.67 | 4.81 | 95232132.43 | 126.84 | 12-OCT-13:00 | 6.67 | 4.81 |
November | 0.110384E+11 | 5295.42 | 15-NOV-16:20 | 10.93 | 6.40 | 94300330.59 | 126.82 | 10-NOV-14:00 | 10.93 | 6.40 |
December | 0.145464E+11 | 6861.01 | 04-DEC-16:30 | -1.4 | -3.9 | 91880872.35 | 126.82 | 01-DEC-14:09 | -1.4 | -3.9 |
Annual Sum or Average | 0.114367E+12 | 0.114010E+10 | ||||||||
Minimum of Months | 0.256231E+09 | 1435.81 | -6.6 | -8.3 | 86396473.76 | 126.82 | -6.6 | -8.3 | ||
Maximum of Months | 0.186984E+11 | 7859.55 | 22.07 | 16.93 | 0.103239E+09 | 126.86 | 19.10 | 17.48 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 99192267.07 | 1202.34 | 12-JAN-16:40 | -6.5 | -8.3 | 87267959.72 | 126.83 | 20-JAN-14:09 | -0.4 | -3.5 |
February | 0.266228E+10 | 3479.95 | 28-FEB-17:00 | -0.6 | -3.0 | 86395862.93 | 126.82 | 21-FEB-10:39 | -0.6 | -3.0 |
March | 0.997749E+10 | 5752.50 | 31-MAR-23:20 | 4.60 | 4.18 | 0.103237E+09 | 126.83 | 14-MAR-09:00 | 4.60 | 4.18 |
April | 0.157973E+11 | 7625.39 | 24-APR-18:00 | 11.70 | 8.10 | 91605176.73 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.315044E+10 | 3156.94 | 31-MAY-23:40 | 17.17 | 13.97 | 99235594.20 | 126.84 | 30-MAY-13:00 | 17.17 | 13.97 |
June | 0.856459E+10 | 5035.84 | 30-JUN-23:40 | 17.07 | 12.89 | 98966550.60 | 126.86 | 27-JUN-13:00 | 17.07 | 12.89 |
July | 0.140061E+11 | 6963.42 | 31-JUL-24:00 | 19.10 | 16.93 | 91889340.85 | 126.85 | 05-JUL-13:09 | 19.10 | 16.93 |
August | 0.186508E+11 | 7913.99 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103239E+09 | 126.83 | 30-AUG-09:00 | 17.80 | 17.48 |
September | 0.317690E+10 | 2495.23 | 04-SEP-17:42 | 16.97 | 12.18 | 91609083.62 | 126.85 | 08-SEP-13:00 | 22.80 | 18.10 |
October | 0.612260E+10 | 4061.01 | 31-OCT-23:20 | 6.87 | 4.91 | 95232108.59 | 126.84 | 12-OCT-13:00 | 6.87 | 4.91 |
November | 0.921603E+10 | 5139.37 | 15-NOV-16:30 | 10.55 | 6.20 | 94300331.35 | 126.82 | 10-NOV-14:00 | 10.55 | 6.20 |
December | 0.126712E+11 | 6512.02 | 04-DEC-16:30 | -1.4 | -3.9 | 91880878.64 | 126.82 | 01-DEC-14:09 | -1.4 | -3.9 |
Annual Sum or Average | 0.104095E+12 | 0.113486E+10 | ||||||||
Minimum of Months | 99192267.07 | 1202.34 | -6.5 | -8.3 | 86395862.93 | 126.82 | -1.4 | -3.9 | ||
Maximum of Months | 0.186508E+11 | 7913.99 | 22.07 | 16.93 | 0.103239E+09 | 126.86 | 22.80 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233704E+12 | 89738.06 | 18-JAN-17:00 | 1.70 | 1.21 | 0.206144E+10 | 2745.29 | 13-JAN-14:00 | 1.70 | 1.21 |
February | 0.431470E+12 | 181259.62 | 23-FEB-17:00 | -0.6 | -1.8 | 0.187023E+10 | 2745.34 | 22-FEB-14:50 | -0.6 | -1.8 |
March | 0.725601E+12 | 357516.10 | 31-MAR-24:00 | 4.20 | 3.93 | 0.223487E+10 | 2749.28 | 14-MAR-13:09 | 4.20 | 3.93 |
April | 0.940275E+12 | 365970.78 | 24-APR-16:00 | 13.30 | 7.63 | 0.198305E+10 | 2748.63 | 28-APR-09:09 | 10.00 | 8.84 |
May | 0.238386E+12 | 175302.80 | 31-MAY-24:00 | 17.10 | 14.03 | 0.214808E+10 | 2745.71 | 10-MAY-13:09 | 17.10 | 14.03 |
June | 0.469005E+12 | 267600.67 | 30-JUN-24:00 | 16.90 | 13.02 | 0.214234E+10 | 2748.51 | 01-JUN-13:00 | 16.90 | 13.02 |
July | 0.731225E+12 | 359741.06 | 31-JUL-24:00 | 19.10 | 16.93 | 0.199606E+10 | 2988.52 | 21-JUL-09:09 | 19.10 | 16.93 |
August | 0.975743E+12 | 377688.32 | 15-AUG-16:41 | 20.87 | 19.23 | 0.231107E+10 | 3744.47 | 15-AUG-13:09 | 20.87 | 19.23 |
September | 0.234397E+12 | 175294.51 | 30-SEP-24:00 | 14.40 | 12.09 | 0.198297E+10 | 2746.27 | 21-SEP-13:09 | 14.40 | 12.09 |
October | 0.485164E+12 | 267718.26 | 31-OCT-24:00 | 6.60 | 4.77 | 0.206145E+10 | 2746.12 | 23-OCT-09:30 | 6.60 | 4.77 |
November | 0.705890E+12 | 275036.03 | 06-NOV-15:00 | 5.60 | 4.05 | 0.204137E+10 | 2746.84 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.972325E+12 | 365881.43 | 04-DEC-16:55 | -2.2 | -4.4 | 0.198898E+10 | 2747.44 | 01-DEC-10:00 | -2.2 | -4.4 |
Annual Sum or Average | 0.714319E+13 | 0.248219E+11 | ||||||||
Minimum of Months | 0.233704E+12 | 89738.06 | -2.2 | -4.4 | 0.187023E+10 | 2745.29 | -2.2 | -4.4 | ||
Maximum of Months | 0.975743E+12 | 377688.32 | 20.87 | 19.23 | 0.231107E+10 | 3744.47 | 20.87 | 19.23 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.783632E+09 | 46592.83 | 02-JAN-04:01 | -1.0 |
February | 0.119958E+09 | 38501.80 | 06-FEB-05:01 | -14.8 |
March | 3728233.78 | 5821.17 | 06-MAR-20:10 | -10.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 90131349.67 | 38580.11 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.997449E+09 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.783632E+09 | 46592.83 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.614127E+10 | 71232.12 | 02-JAN-04:01 | -1.0 |
February | 0.501458E+10 | 70958.07 | 06-FEB-04:11 | -15.0 |
March | 0.162219E+10 | 67389.12 | 06-MAR-04:01 | -11.1 |
April | 0.252354E+09 | 63300.29 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.235641E+09 | 61896.75 | 30-OCT-04:01 | -0.5 |
November | 0.874249E+09 | 64490.86 | 24-NOV-05:01 | -3.0 |
December | 0.455353E+10 | 70968.03 | 11-DEC-04:11 | -17.2 |
Annual Sum or Average | 0.186938E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.614127E+10 | 71232.12 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.453548E+09 | 11133.77 | 24-JAN-05:01 | -11.8 |
February | 0.298630E+09 | 11447.15 | 06-FEB-05:01 | -14.8 |
March | 35337346.84 | 10575.36 | 07-MAR-06:01 | -13.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 96831583.15 | 10917.93 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.884347E+09 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.453548E+09 | 11447.15 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334638E+09 | 11227.11 | 10-JAN-05:01 | -13.3 |
February | 0.253529E+09 | 11720.36 | 06-FEB-05:01 | -14.8 |
March | 23310054.86 | 10599.42 | 06-MAR-06:01 | -11.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.168684E+09 | 11241.42 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.780161E+09 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.334638E+09 | 11720.36 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.709341E+09 | 17065.75 | 30-JAN-05:01 | -9.5 |
February | 0.581378E+09 | 17114.95 | 07-FEB-05:01 | -15.7 |
March | 62568408.75 | 15730.27 | 06-MAR-05:01 | -11.1 |
April | 726213.88 | 5435.79 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 553030.28 | 7334.14 | 30-OCT-05:01 | -0.1 |
November | 6927285.53 | 11968.62 | 24-NOV-06:03 | -3.8 |
December | 0.280112E+09 | 16535.07 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.164161E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.709341E+09 | 17114.95 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 51568720.64 | 8851.64 | 30-JAN-06:01 | -10.1 |
February | 16719204.52 | 8651.80 | 06-FEB-06:02 | -13.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 68287925.16 | |||
Minimum of Months | 0.00 | 0.00 | -13.9 | |
Maximum of Months | 51568720.64 | 8851.64 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.529593E+10 | 12371.70 | 30-JAN-04:01 | -9.9 |
February | 0.417583E+10 | 12583.69 | 05-FEB-21:32 | -12.4 |
March | 0.130900E+10 | 12213.30 | 06-MAR-04:01 | -11.1 |
April | 0.103737E+09 | 10648.80 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 78657235.15 | 10355.87 | 30-OCT-04:01 | -0.5 |
November | 0.447619E+09 | 11052.06 | 24-NOV-05:01 | -3.0 |
December | 0.405697E+10 | 12363.39 | 26-DEC-03:52 | -11.7 |
Annual Sum or Average | 0.154677E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.529593E+10 | 12583.69 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288801E+10 | 17814.79 | 02-JAN-04:01 | -1.0 |
February | 0.226909E+10 | 18062.39 | 06-FEB-04:11 | -15.0 |
March | 0.489347E+09 | 16894.40 | 06-MAR-04:01 | -11.1 |
April | 41547416.34 | 14872.93 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 43370792.73 | 14584.10 | 30-OCT-04:01 | -0.5 |
November | 0.273009E+09 | 15893.53 | 24-NOV-05:01 | -3.0 |
December | 0.243221E+10 | 17548.16 | 12-DEC-04:01 | -10.9 |
Annual Sum or Average | 0.843658E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.288801E+10 | 18062.39 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.322419E+10 | 20520.06 | 02-JAN-04:01 | -1.0 |
February | 0.263507E+10 | 20702.69 | 06-FEB-04:11 | -15.0 |
March | 0.499516E+09 | 18244.61 | 06-MAR-05:01 | -11.1 |
April | 61473230.38 | 16934.87 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 32297199.08 | 16404.44 | 30-OCT-05:01 | -0.1 |
November | 0.272859E+09 | 18137.29 | 24-NOV-05:01 | -3.0 |
December | 0.258512E+10 | 20118.55 | 26-DEC-04:01 | -11.8 |
Annual Sum or Average | 0.931052E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.322419E+10 | 20702.69 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253142E+10 | 17885.01 | 30-JAN-04:01 | -9.9 |
February | 0.186721E+10 | 18107.58 | 06-FEB-04:11 | -15.0 |
March | 0.364163E+09 | 15778.96 | 06-MAR-05:01 | -11.1 |
April | 14484096.56 | 13844.30 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 20920172.31 | 13856.33 | 30-OCT-05:01 | -0.1 |
November | 0.152622E+09 | 15230.67 | 24-NOV-05:01 | -3.0 |
December | 0.177151E+10 | 17586.66 | 26-DEC-04:01 | -11.8 |
Annual Sum or Average | 0.672233E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.253142E+10 | 18107.58 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.952838E+10 | 14681.06 | 09-JAN-01:03 | -7.9 |
February | 0.800844E+10 | 15044.56 | 05-FEB-21:32 | -12.4 |
March | 0.364747E+10 | 14584.82 | 06-MAR-03:42 | -11.0 |
April | 0.770572E+09 | 13943.33 | 17-APR-03:01 | -2.9 |
May | 13580671.03 | 11282.68 | 01-MAY-05:02 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 13295485.96 | 11122.75 | 30-SEP-05:03 | 7.20 |
October | 0.738382E+09 | 13852.45 | 30-OCT-03:01 | -0.1 |
November | 0.230256E+10 | 13900.03 | 20-NOV-05:11 | 5.00 |
December | 0.845462E+10 | 15034.09 | 26-DEC-01:22 | -11.4 |
Annual Sum or Average | 0.334773E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.952838E+10 | 15044.56 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.548608E+10 | 20015.27 | 30-JAN-04:01 | -9.9 |
February | 0.461686E+10 | 20365.66 | 21-FEB-03:42 | -11.1 |
March | 0.161172E+10 | 19109.91 | 27-MAR-03:01 | -6.0 |
April | 0.330665E+09 | 19125.86 | 17-APR-03:01 | -2.9 |
May | 5260115.06 | 12607.75 | 01-MAY-05:02 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 7925401.82 | 9641.43 | 30-SEP-05:03 | 7.20 |
October | 0.362182E+09 | 19082.73 | 30-OCT-03:01 | -0.1 |
November | 0.132495E+10 | 19256.08 | 20-NOV-05:11 | 5.00 |
December | 0.528359E+10 | 20383.15 | 26-DEC-04:01 | -11.8 |
Annual Sum or Average | 0.190292E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.548608E+10 | 20383.15 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.643848E+10 | 22747.91 | 30-JAN-04:01 | -9.9 |
February | 0.566917E+10 | 23226.74 | 13-FEB-03:02 | -8.9 |
March | 0.193362E+10 | 21524.27 | 06-MAR-04:01 | -11.1 |
April | 0.565762E+09 | 21648.74 | 17-APR-03:01 | -2.9 |
May | 11208081.37 | 12151.45 | 01-MAY-05:02 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 7283284.08 | 9364.99 | 30-SEP-05:03 | 7.20 |
October | 0.409517E+09 | 21144.34 | 30-OCT-03:01 | -0.1 |
November | 0.158262E+10 | 21588.47 | 20-NOV-05:11 | 5.00 |
December | 0.611360E+10 | 23337.31 | 26-DEC-01:22 | -11.4 |
Annual Sum or Average | 0.227313E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.4 | |
Maximum of Months | 0.643848E+10 | 23337.31 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490474E+10 | 21244.46 | 30-JAN-04:01 | -9.9 |
February | 0.369514E+10 | 21460.24 | 06-FEB-04:11 | -15.0 |
March | 0.121829E+10 | 20028.09 | 06-MAR-04:01 | -11.1 |
April | 0.211065E+09 | 18064.45 | 17-APR-04:01 | -3.4 |
May | 31185.62 | 207.90 | 12-MAY-05:03 | 8.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 1145510.69 | 2331.35 | 30-SEP-05:03 | 7.20 |
October | 0.232473E+09 | 18113.17 | 30-OCT-04:01 | -0.5 |
November | 0.859762E+09 | 19885.26 | 24-NOV-04:01 | -3.2 |
December | 0.382289E+10 | 21359.42 | 26-DEC-04:01 | -11.8 |
Annual Sum or Average | 0.149455E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.490474E+10 | 21460.24 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122896E+10 | 9548.16 | 11-JAN-06:03 | 5.68 |
February | 0.114297E+10 | 10150.82 | 15-FEB-06:02 | 5.60 |
March | 0.219415E+09 | 9913.01 | 02-MAR-06:01 | 1.10 |
April | 0.127164E+09 | 10245.18 | 20-APR-04:12 | 11.50 |
May | 84058596.57 | 8857.48 | 14-MAY-14:32 | 25.73 |
June | 0.106998E+09 | 11445.44 | 11-JUN-15:21 | 25.85 |
July | 0.149859E+09 | 10762.62 | 16-JUL-15:51 | 30.60 |
August | 0.123642E+09 | 11947.04 | 13-AUG-15:31 | 29.60 |
September | 80867545.79 | 9147.09 | 10-SEP-14:51 | 17.20 |
October | 97553598.51 | 8724.71 | 10-OCT-04:12 | 10.00 |
November | 84970714.60 | 10966.56 | 27-NOV-05:12 | 17.97 |
December | 0.511246E+09 | 10582.61 | 14-DEC-06:03 | 5.68 |
Annual Sum or Average | 0.395771E+10 | |||
Minimum of Months | 80867545.79 | 8724.71 | 1.10 | |
Maximum of Months | 0.122896E+10 | 11947.04 | 30.60 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.401566E+10 | 16589.93 | 02-JAN-06:13 | -1.1 |
February | 0.314820E+10 | 9750.16 | 28-FEB-09:58 | -3.9 |
March | 0.167666E+10 | 6163.17 | 26-MAR-13:03 | -0.6 |
April | 0.426585E+09 | 7561.02 | 23-APR-14:32 | 15.20 |
May | 61481085.25 | 8937.03 | 14-MAY-14:42 | 25.92 |
June | 66980728.71 | 11780.95 | 11-JUN-16:01 | 25.60 |
July | 77413863.25 | 8953.60 | 16-JUL-16:02 | 30.03 |
August | 50441334.63 | 9368.51 | 13-AUG-15:42 | 29.50 |
September | 65904170.06 | 9265.48 | 10-SEP-15:42 | 17.70 |
October | 0.340597E+09 | 7516.21 | 09-OCT-11:42 | 11.60 |
November | 0.870770E+09 | 5272.00 | 06-NOV-06:02 | 8.90 |
December | 0.271042E+10 | 6877.79 | 26-DEC-06:12 | -12.2 |
Annual Sum or Average | 0.135111E+11 | |||
Minimum of Months | 50441334.63 | 5272.00 | -12.2 | |
Maximum of Months | 0.401566E+10 | 16589.93 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113542E+11 | 26339.85 | 09-JAN-05:12 | -9.4 |
February | 0.972141E+10 | 27551.64 | 06-FEB-05:08 | -14.8 |
March | 0.496842E+10 | 25533.66 | 06-MAR-05:13 | -11.1 |
April | 0.191804E+10 | 20096.79 | 17-APR-05:13 | -4.1 |
May | 0.643129E+09 | 13144.19 | 16-MAY-05:02 | 11.10 |
June | 0.195001E+09 | 10772.88 | 06-JUN-05:03 | 6.78 |
July | 0.104252E+09 | 11673.86 | 03-JUL-04:12 | 11.70 |
August | 0.144467E+09 | 11543.53 | 03-AUG-05:03 | 11.10 |
September | 0.517814E+09 | 12226.80 | 19-SEP-05:03 | 10.60 |
October | 0.192338E+10 | 16815.41 | 30-OCT-05:13 | -0.2 |
November | 0.403620E+10 | 20050.22 | 24-NOV-05:12 | -3.2 |
December | 0.102205E+11 | 28174.74 | 11-DEC-05:42 | -18.6 |
Annual Sum or Average | 0.457468E+11 | |||
Minimum of Months | 0.104252E+09 | 10772.88 | -18.6 | |
Maximum of Months | 0.113542E+11 | 28174.74 | 11.70 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.565208E+09 | 544.48 | 08-JAN-18:10 | -4.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.565208E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.565208E+09 | 544.48 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.774676E+09 | 581.38 | 15-JAN-18:50 | 0.18 |
February | 0.106037E+09 | 548.40 | 05-FEB-22:40 | -12.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.880713E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.774676E+09 | 581.38 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968216E+10 | 10174.14 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.878253E+10 | 10174.14 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.104353E+11 | 10174.14 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.932187E+10 | 10174.14 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.100587E+11 | 10174.14 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.100099E+11 | 10174.14 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.937071E+10 | 10174.14 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.104353E+11 | 10174.14 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.932187E+10 | 10174.14 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.968216E+10 | 10174.14 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.956821E+10 | 10174.14 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.937071E+10 | 10174.14 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.116039E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.878253E+10 | 10174.14 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.104353E+11 | 10174.14 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.700137E+09 | 1147.25 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.597392E+09 | 994.63 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.664154E+09 | 799.25 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.573108E+09 | 634.49 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.601338E+09 | 599.04 | 11-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.590430E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.557141E+09 | 589.66 | 11-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.627072E+09 | 598.33 | 24-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.586358E+09 | 765.26 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.643248E+09 | 1103.90 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.702142E+09 | 1147.25 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.702742E+09 | 1147.25 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.754526E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.557141E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.702742E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.444043E+09 | 739.33 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.382670E+09 | 647.24 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.426523E+09 | 410.74 | 01-MAR-17:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.369741E+09 | 394.56 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.389342E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.382411E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.360679E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.405686E+09 | 380.91 | 28-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.377123E+09 | 406.11 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.410037E+09 | 588.57 | 26-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.445393E+09 | 739.33 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.444902E+09 | 739.33 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.483855E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.360679E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.445393E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.677332E+09 | 1147.28 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.588401E+09 | 970.78 | 01-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.659983E+09 | 773.30 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.574231E+09 | 633.48 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.604749E+09 | 602.15 | 11-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.593592E+09 | 545.88 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.560391E+09 | 593.25 | 11-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.629548E+09 | 600.49 | 24-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.585207E+09 | 745.73 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.632857E+09 | 964.76 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.680968E+09 | 1147.28 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.679707E+09 | 1147.28 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.746697E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.560391E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.680968E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.442530E+09 | 739.33 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.381351E+09 | 637.99 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.426435E+09 | 545.92 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.369284E+09 | 414.07 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.388049E+09 | 396.37 | 11-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.380600E+09 | 377.90 | 21-JUN-08:09 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.359569E+09 | 391.71 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.404333E+09 | 398.95 | 24-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.377772E+09 | 524.17 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.412329E+09 | 711.21 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.444330E+09 | 739.33 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.444666E+09 | 739.33 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.483125E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.359569E+09 | 377.90 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.444666E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.697923E+09 | 1147.25 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.596463E+09 | 992.91 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.663347E+09 | 795.16 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.572828E+09 | 630.46 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.600970E+09 | 592.98 | 11-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.590162E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.556916E+09 | 583.04 | 11-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.626712E+09 | 592.27 | 24-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.585829E+09 | 760.71 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.642161E+09 | 1103.27 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.699848E+09 | 1147.25 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.700689E+09 | 1147.25 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.753385E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.556916E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.700689E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.443253E+09 | 739.33 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.382164E+09 | 644.87 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.426124E+09 | 410.74 | 01-MAR-17:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.369501E+09 | 391.71 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.389050E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.382201E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.360498E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.405361E+09 | 376.79 | 28-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.376820E+09 | 403.80 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.409639E+09 | 585.34 | 26-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.444574E+09 | 739.33 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.444077E+09 | 739.33 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.483326E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.360498E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.444574E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.676589E+09 | 1147.28 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.587777E+09 | 969.03 | 01-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.659516E+09 | 769.08 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.573881E+09 | 629.39 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.604315E+09 | 596.24 | 11-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.593299E+09 | 545.88 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.560011E+09 | 586.81 | 11-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.629125E+09 | 594.53 | 24-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.584703E+09 | 741.03 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.632486E+09 | 960.86 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.680388E+09 | 1147.28 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.679099E+09 | 1147.28 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.746119E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.560011E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.680388E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.441649E+09 | 739.33 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.380807E+09 | 635.37 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.425970E+09 | 540.85 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.369010E+09 | 411.83 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.387726E+09 | 393.13 | 11-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.380441E+09 | 373.40 | 21-JUN-08:09 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.359351E+09 | 388.20 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.404047E+09 | 395.87 | 24-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.377443E+09 | 518.52 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.411666E+09 | 710.81 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.443405E+09 | 739.33 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.443760E+09 | 739.33 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.482528E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.359351E+09 | 373.40 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.443760E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.697814E+09 | 1147.25 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.596427E+09 | 992.60 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.663320E+09 | 794.49 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.572815E+09 | 630.29 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.600930E+09 | 592.74 | 11-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.590153E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.556908E+09 | 582.77 | 11-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.626693E+09 | 592.02 | 24-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.585807E+09 | 759.95 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.642120E+09 | 1103.25 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.699779E+09 | 1147.25 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.700557E+09 | 1147.25 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.753332E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.556908E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.700557E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.443218E+09 | 739.33 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.382146E+09 | 644.68 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.426121E+09 | 410.74 | 01-MAR-17:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.369493E+09 | 391.57 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.389040E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.382195E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.360491E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.405352E+09 | 376.62 | 28-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.376809E+09 | 403.69 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.409624E+09 | 585.07 | 26-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.444517E+09 | 739.33 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.444040E+09 | 739.33 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.483305E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.360491E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.444517E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.676499E+09 | 1147.28 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.587738E+09 | 968.70 | 01-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.659470E+09 | 768.37 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.573867E+09 | 629.23 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.604280E+09 | 596.01 | 11-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.593282E+09 | 545.88 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.559997E+09 | 586.55 | 11-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.629093E+09 | 594.29 | 24-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.584685E+09 | 740.25 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.632465E+09 | 960.83 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.680354E+09 | 1147.28 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.679009E+09 | 1147.28 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.746074E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.559997E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.680354E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.441558E+09 | 739.33 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.380766E+09 | 635.16 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.425950E+09 | 540.47 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.368988E+09 | 411.74 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.387717E+09 | 393.00 | 11-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.380436E+09 | 373.26 | 21-JUN-08:09 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.359346E+09 | 388.06 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.404018E+09 | 395.75 | 24-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.377419E+09 | 518.08 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.411623E+09 | 710.80 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.443362E+09 | 739.33 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.443688E+09 | 739.33 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.482487E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.359346E+09 | 373.26 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.443688E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274130E+10 | 2868.67 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.248656E+10 | 2868.67 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.295472E+10 | 2868.67 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.263917E+10 | 2868.67 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.284801E+10 | 2868.67 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.283424E+10 | 2868.67 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.265294E+10 | 2868.67 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.295472E+10 | 2868.67 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.263917E+10 | 2868.67 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.274130E+10 | 2868.67 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.270917E+10 | 2868.67 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.265294E+10 | 2868.67 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.328542E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.248656E+10 | 2868.67 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.295472E+10 | 2868.67 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.100587E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.100099E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.956821E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.116039E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.700137E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777036E+09 |
February | 0.136985E+10 | 0.597392E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826712E+09 |
March | 0.163685E+10 | 0.664154E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 162078.41 | 0.521970E+09 |
April | 0.145243E+10 | 0.573108E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429753E+09 |
May | 0.157338E+10 | 0.601338E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79153.15 | 0.245097E+09 |
June | 0.156900E+10 | 0.590430E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3843259.45 | 0.138599E+09 |
July | 0.145680E+10 | 0.557141E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9875654.48 | 77727284.34 |
August | 0.163685E+10 | 0.627072E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7379418.33 | 89134141.30 |
September | 0.145243E+10 | 0.586358E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 542001.89 | 0.143944E+09 |
October | 0.150991E+10 | 0.643248E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336376E+09 |
November | 0.149516E+10 | 0.702142E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465421E+09 |
December | 0.145680E+10 | 0.702742E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852514E+09 |
Annual Sum or Average | 0.181194E+11 | 0.754526E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21881565.71 | 0.490428E+10 |
Minimum of Months | 0.136985E+10 | 0.557141E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77727284.34 |
Maximum of Months | 0.163685E+10 | 0.702742E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9875654.48 | 0.852514E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.444043E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518551E+09 |
February | 0.882782E+09 | 0.382670E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548614E+09 |
March | 0.105485E+10 | 0.426523E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108048.20 | 0.347555E+09 |
April | 0.936002E+09 | 0.369741E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283474E+09 |
May | 0.101394E+10 | 0.389342E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49236.27 | 0.166532E+09 |
June | 0.101113E+10 | 0.382411E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2560693.77 | 92629004.00 |
July | 0.938820E+09 | 0.360679E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6617348.86 | 51063781.09 |
August | 0.105485E+10 | 0.405686E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4868530.91 | 58128004.90 |
September | 0.936002E+09 | 0.377123E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 355213.40 | 97087181.84 |
October | 0.973041E+09 | 0.410037E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224259E+09 |
November | 0.963541E+09 | 0.445393E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304876E+09 |
December | 0.938820E+09 | 0.444902E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557918E+09 |
Annual Sum or Average | 0.116768E+11 | 0.483855E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14559071.40 | 0.325069E+10 |
Minimum of Months | 0.882782E+09 | 0.360679E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51063781.09 |
Maximum of Months | 0.105485E+10 | 0.445393E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6617348.86 | 0.557918E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.677332E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774176E+09 |
February | 0.136988E+10 | 0.588401E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815877E+09 |
March | 0.163688E+10 | 0.659983E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161528.07 | 0.528431E+09 |
April | 0.145246E+10 | 0.574231E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427736E+09 |
May | 0.157341E+10 | 0.604749E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73810.87 | 0.248209E+09 |
June | 0.156904E+10 | 0.593592E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3819238.10 | 0.138719E+09 |
July | 0.145684E+10 | 0.560391E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9707603.52 | 78852057.16 |
August | 0.163688E+10 | 0.629548E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6979517.84 | 92254339.39 |
September | 0.145246E+10 | 0.585207E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 495842.31 | 0.148700E+09 |
October | 0.150994E+10 | 0.632857E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339884E+09 |
November | 0.149520E+10 | 0.680968E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456798E+09 |
December | 0.145684E+10 | 0.679707E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839280E+09 |
Annual Sum or Average | 0.181198E+11 | 0.746697E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21237540.70 | 0.488892E+10 |
Minimum of Months | 0.136988E+10 | 0.560391E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78852057.16 |
Maximum of Months | 0.163688E+10 | 0.680968E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9707603.52 | 0.839280E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.442530E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539072E+09 |
February | 0.882782E+09 | 0.381351E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583702E+09 |
March | 0.105485E+10 | 0.426435E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108048.17 | 0.382095E+09 |
April | 0.936002E+09 | 0.369284E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318305E+09 |
May | 0.101394E+10 | 0.388049E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49208.22 | 0.179874E+09 |
June | 0.101113E+10 | 0.380600E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2429361.65 | 0.105889E+09 |
July | 0.938820E+09 | 0.359569E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6078046.37 | 64740549.61 |
August | 0.105485E+10 | 0.404333E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4546058.91 | 74303882.58 |
September | 0.936002E+09 | 0.377772E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 325399.37 | 0.106375E+09 |
October | 0.973041E+09 | 0.412329E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245299E+09 |
November | 0.963541E+09 | 0.444330E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339776E+09 |
December | 0.938820E+09 | 0.444666E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622630E+09 |
Annual Sum or Average | 0.116768E+11 | 0.483125E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13536122.70 | 0.356206E+10 |
Minimum of Months | 0.882782E+09 | 0.359569E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64740549.61 |
Maximum of Months | 0.105485E+10 | 0.444666E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6078046.37 | 0.622630E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.697923E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162693E+10 |
February | 0.136985E+10 | 0.596463E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173263E+10 |
March | 0.163685E+10 | 0.663347E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 337499.45 | 0.109368E+10 |
April | 0.145243E+10 | 0.572828E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899942E+09 |
May | 0.157338E+10 | 0.600970E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 220628.46 | 0.540193E+09 |
June | 0.156900E+10 | 0.590162E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8909886.66 | 0.308635E+09 |
July | 0.145680E+10 | 0.556916E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22267620.27 | 0.180573E+09 |
August | 0.163685E+10 | 0.626712E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17787034.82 | 0.206750E+09 |
September | 0.145243E+10 | 0.585829E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1260913.50 | 0.312156E+09 |
October | 0.150991E+10 | 0.642161E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693289E+09 |
November | 0.149516E+10 | 0.699848E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932525E+09 |
December | 0.145680E+10 | 0.700689E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173858E+10 |
Annual Sum or Average | 0.181194E+11 | 0.753385E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50783583.16 | 0.102659E+11 |
Minimum of Months | 0.136985E+10 | 0.556916E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180573E+09 |
Maximum of Months | 0.163685E+10 | 0.700689E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22267620.27 | 0.173858E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.443253E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109155E+10 |
February | 0.649041E+09 | 0.382164E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116282E+10 |
March | 0.773965E+09 | 0.426124E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 178408.57 | 0.753031E+09 |
April | 0.688021E+09 | 0.369501E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623470E+09 |
May | 0.744847E+09 | 0.389050E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93978.20 | 0.381479E+09 |
June | 0.742030E+09 | 0.382201E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5380322.65 | 0.216522E+09 |
July | 0.690839E+09 | 0.360498E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13616508.39 | 0.128114E+09 |
August | 0.773965E+09 | 0.405361E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10332655.39 | 0.147354E+09 |
September | 0.688021E+09 | 0.376820E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 717364.51 | 0.220665E+09 |
October | 0.715730E+09 | 0.409639E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486311E+09 |
November | 0.708685E+09 | 0.444574E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635586E+09 |
December | 0.690839E+09 | 0.444077E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116233E+10 |
Annual Sum or Average | 0.858171E+10 | 0.483326E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30319237.71 | 0.700924E+10 |
Minimum of Months | 0.649041E+09 | 0.360498E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128114E+09 |
Maximum of Months | 0.773965E+09 | 0.444574E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13616508.39 | 0.116282E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.676589E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169976E+10 |
February | 0.136988E+10 | 0.587777E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178828E+10 |
March | 0.163688E+10 | 0.659516E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 336629.72 | 0.118238E+10 |
April | 0.145246E+10 | 0.573881E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947665E+09 |
May | 0.157341E+10 | 0.604315E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 158292.22 | 0.566525E+09 |
June | 0.156904E+10 | 0.593299E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8566993.05 | 0.316521E+09 |
July | 0.145684E+10 | 0.560011E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21237822.09 | 0.189035E+09 |
August | 0.163688E+10 | 0.629125E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15630631.20 | 0.223075E+09 |
September | 0.145246E+10 | 0.584703E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1053473.91 | 0.340136E+09 |
October | 0.150994E+10 | 0.632486E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762675E+09 |
November | 0.149520E+10 | 0.680388E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993912E+09 |
December | 0.145684E+10 | 0.679099E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181097E+10 |
Annual Sum or Average | 0.181198E+11 | 0.746119E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46983842.19 | 0.108209E+11 |
Minimum of Months | 0.136988E+10 | 0.560011E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189035E+09 |
Maximum of Months | 0.163688E+10 | 0.680388E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21237822.09 | 0.181097E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.441649E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110886E+10 |
February | 0.882782E+09 | 0.380807E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118713E+10 |
March | 0.105485E+10 | 0.425970E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 224990.48 | 0.781295E+09 |
April | 0.936002E+09 | 0.369010E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646633E+09 |
May | 0.101394E+10 | 0.387726E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105532.15 | 0.395271E+09 |
June | 0.101113E+10 | 0.380441E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5413402.76 | 0.229970E+09 |
July | 0.938820E+09 | 0.359351E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13886364.61 | 0.141628E+09 |
August | 0.105485E+10 | 0.404047E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10399196.11 | 0.161193E+09 |
September | 0.936002E+09 | 0.377443E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 717997.54 | 0.228096E+09 |
October | 0.973041E+09 | 0.411666E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493416E+09 |
November | 0.963541E+09 | 0.443405E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648209E+09 |
December | 0.938820E+09 | 0.443760E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119106E+10 |
Annual Sum or Average | 0.116768E+11 | 0.482528E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30747483.65 | 0.721277E+10 |
Minimum of Months | 0.882782E+09 | 0.359351E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141628E+09 |
Maximum of Months | 0.105485E+10 | 0.443760E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13886364.61 | 0.119106E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.697814E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195732E+10 |
February | 0.136985E+10 | 0.596427E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208121E+10 |
March | 0.163685E+10 | 0.663320E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 369461.98 | 0.127739E+10 |
April | 0.145243E+10 | 0.572815E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104166E+10 |
May | 0.157338E+10 | 0.600930E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 179945.86 | 0.648951E+09 |
June | 0.156900E+10 | 0.590153E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10058612.30 | 0.382144E+09 |
July | 0.145680E+10 | 0.556908E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25360113.94 | 0.230688E+09 |
August | 0.163685E+10 | 0.626693E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19754878.29 | 0.258833E+09 |
September | 0.145243E+10 | 0.585807E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1403321.28 | 0.370880E+09 |
October | 0.150991E+10 | 0.642120E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775445E+09 |
November | 0.149516E+10 | 0.699779E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104839E+10 |
December | 0.145680E+10 | 0.700557E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206299E+10 |
Annual Sum or Average | 0.181194E+11 | 0.753332E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57126333.65 | 0.121359E+11 |
Minimum of Months | 0.136985E+10 | 0.556908E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230688E+09 |
Maximum of Months | 0.163685E+10 | 0.700557E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25360113.94 | 0.208121E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.443218E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131218E+10 |
February | 0.882782E+09 | 0.382146E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139776E+10 |
March | 0.105485E+10 | 0.426121E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 245916.58 | 0.873660E+09 |
April | 0.936002E+09 | 0.369493E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722975E+09 |
May | 0.101394E+10 | 0.389040E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119585.82 | 0.460913E+09 |
June | 0.101113E+10 | 0.382195E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6616571.12 | 0.267239E+09 |
July | 0.938820E+09 | 0.360491E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16567736.78 | 0.161379E+09 |
August | 0.105485E+10 | 0.405352E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12515922.03 | 0.183272E+09 |
September | 0.936002E+09 | 0.376809E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 897108.35 | 0.263602E+09 |
October | 0.973041E+09 | 0.409624E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547488E+09 |
November | 0.963541E+09 | 0.444517E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712529E+09 |
December | 0.938820E+09 | 0.444040E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138178E+10 |
Annual Sum or Average | 0.116768E+11 | 0.483305E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36962840.67 | 0.828478E+10 |
Minimum of Months | 0.882782E+09 | 0.360491E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161379E+09 |
Maximum of Months | 0.105485E+10 | 0.444517E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16567736.78 | 0.139776E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.676499E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201921E+10 |
February | 0.136988E+10 | 0.587738E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212877E+10 |
March | 0.163688E+10 | 0.659470E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 367969.77 | 0.137795E+10 |
April | 0.145246E+10 | 0.573867E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110342E+10 |
May | 0.157341E+10 | 0.604280E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 179374.39 | 0.683036E+09 |
June | 0.156904E+10 | 0.593282E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9951986.93 | 0.390982E+09 |
July | 0.145684E+10 | 0.559997E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24817050.12 | 0.238715E+09 |
August | 0.163688E+10 | 0.629093E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18271347.62 | 0.277992E+09 |
September | 0.145246E+10 | 0.584685E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1249550.91 | 0.409188E+09 |
October | 0.150994E+10 | 0.632465E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871158E+09 |
November | 0.149520E+10 | 0.680354E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112161E+10 |
December | 0.145684E+10 | 0.679009E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212725E+10 |
Annual Sum or Average | 0.181198E+11 | 0.746074E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54837279.75 | 0.127493E+11 |
Minimum of Months | 0.136988E+10 | 0.559997E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238715E+09 |
Maximum of Months | 0.163688E+10 | 0.680354E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24817050.12 | 0.212877E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.441558E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132793E+10 |
February | 0.882782E+09 | 0.380766E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142133E+10 |
March | 0.105485E+10 | 0.425950E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 245942.88 | 0.919045E+09 |
April | 0.936002E+09 | 0.368988E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760238E+09 |
May | 0.101394E+10 | 0.387717E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119588.50 | 0.478627E+09 |
June | 0.101113E+10 | 0.380436E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6357926.90 | 0.283616E+09 |
July | 0.938820E+09 | 0.359346E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16266001.52 | 0.177150E+09 |
August | 0.105485E+10 | 0.404018E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12241169.58 | 0.200077E+09 |
September | 0.936002E+09 | 0.377419E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 836809.45 | 0.274531E+09 |
October | 0.973041E+09 | 0.411623E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566159E+09 |
November | 0.963541E+09 | 0.443362E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742013E+09 |
December | 0.938820E+09 | 0.443688E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141149E+10 |
Annual Sum or Average | 0.116768E+11 | 0.482487E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36067438.83 | 0.856221E+10 |
Minimum of Months | 0.882782E+09 | 0.359346E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177150E+09 |
Maximum of Months | 0.105485E+10 | 0.443688E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16266001.52 | 0.142133E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.274130E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.248656E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.295472E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.263917E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.284801E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.283424E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.265294E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.295472E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.263917E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.274130E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.270917E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.265294E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.328542E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.248656E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.295472E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167752E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177233E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168531.28 | 0.111702E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906095E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184126.17 | 0.511002E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6301607.55 | 0.288106E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16587154.92 | 0.165517E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13999693.43 | 0.194890E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734846.22 | 0.305424E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713283E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988338E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183056E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37975959.58 | 0.104701E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165517E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16587154.92 | 0.183056E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274977E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291932E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494159.47 | 0.188771E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154507E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568814.96 | 0.892490E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13104078.00 | 0.500843E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30987020.50 | 0.284481E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26621978.42 | 0.340714E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1378586.64 | 0.532349E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121189E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163810E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297612E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73154637.98 | 0.174789E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284481E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30987020.50 | 0.297612E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289686E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308434E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35260.45 | 0.198280E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165242E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34624.61 | 0.102701E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7221316.84 | 0.599517E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21882082.53 | 0.359692E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16055509.61 | 0.406726E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 684345.86 | 0.595480E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124016E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163468E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308514E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45913139.90 | 0.185648E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359692E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21882082.53 | 0.308514E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10174.14 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10174.14 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10174.14 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10174.14 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10174.14 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10174.14 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10174.14 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10174.14 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10174.14 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10174.14 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10174.14 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10174.14 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1377.79 | 12-JAN-02:00 |
February | 2010.79 | 01-FEB-10:09 | 994.63 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1420.16 | 13-FEB-05:56 |
March | 2010.79 | 01-MAR-10:09 | 799.25 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.95 | 15-MAR-14:00 | 889.66 | 02-MAR-01:00 |
April | 2010.79 | 03-APR-09:09 | 634.49 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 856.43 | 16-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 599.04 | 11-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 | 14-MAY-15:00 | 472.61 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.02 | 17-JUN-17:02 | 423.03 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 589.66 | 11-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.07 | 21-JUL-03:08 | 305.31 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 598.33 | 24-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.51 | 13-AUG-12:56 | 190.82 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 765.26 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 | 16-SEP-13:00 | 358.68 | 29-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1103.90 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 478.15 | 08-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 838.91 | 17-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1362.37 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.82 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 126.51 | 1420.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 910.92 | 12-JAN-05:54 |
February | 1295.83 | 01-FEB-10:09 | 647.24 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 946.77 | 13-FEB-05:56 |
March | 1295.83 | 01-MAR-10:09 | 410.74 | 01-MAR-17:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 15-MAR-14:00 | 599.78 | 26-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 394.56 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 556.69 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | 10-MAY-14:00 | 333.21 | 29-MAY-14:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.77 | 17-JUN-17:02 | 281.67 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.69 | 21-JUL-02:50 | 196.06 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 380.91 | 28-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.74 | 13-AUG-12:56 | 122.75 | 30-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 406.11 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 | 16-SEP-13:00 | 234.30 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 588.57 | 26-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 327.91 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 544.29 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 893.35 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.75 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 84.74 | 946.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1366.39 | 12-JAN-05:56 |
February | 2010.83 | 01-FEB-10:09 | 970.78 | 01-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1420.17 | 13-FEB-05:56 |
March | 2010.83 | 01-MAR-10:09 | 773.30 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 15-MAR-14:00 | 920.31 | 26-MAR-13:00 |
April | 2010.83 | 03-APR-09:09 | 633.48 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 816.19 | 16-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 602.15 | 11-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 10-MAY-14:00 | 504.60 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 545.88 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.36 | 17-JUN-17:02 | 421.23 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 593.25 | 11-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.00 | 21-JUL-03:06 | 302.86 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 600.49 | 24-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.91 | 13-AUG-12:54 | 190.23 | 30-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 745.73 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 | 16-SEP-13:10 | 348.86 | 29-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 964.76 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 473.88 | 08-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 821.84 | 17-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1348.35 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.23 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 126.91 | 1420.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 953.90 | 12-JAN-02:00 |
February | 1295.83 | 01-FEB-10:09 | 637.99 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 953.71 | 13-FEB-05:52 |
March | 1295.83 | 01-MAR-10:09 | 545.92 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 15-MAR-14:00 | 665.96 | 02-MAR-01:00 |
April | 1295.83 | 03-APR-09:09 | 414.07 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 628.75 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 396.37 | 11-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | 10-MAY-14:00 | 372.74 | 29-MAY-15:20 |
June | 1295.83 | 01-JUN-09:09 | 377.90 | 21-JUN-08:09 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.62 | 12-JUN-13:00 | 303.51 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 391.71 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.38 | 21-JUL-03:06 | 240.89 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 398.95 | 24-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.53 | 13-AUG-12:54 | 168.64 | 27-AUG-16:40 |
September | 1295.83 | 01-SEP-09:09 | 524.17 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 | 16-SEP-13:00 | 254.76 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 711.21 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 345.51 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 615.20 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 989.50 | 09-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 377.90 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.64 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 83.53 | 989.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3198.33 | 12-JAN-05:47 |
February | 2010.79 | 01-FEB-10:09 | 992.91 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3202.71 | 13-FEB-06:00 |
March | 2010.79 | 01-MAR-10:09 | 795.16 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 | 15-MAR-14:00 | 1840.70 | 02-MAR-05:10 |
April | 2010.79 | 03-APR-09:09 | 630.46 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1710.32 | 16-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 592.98 | 11-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.88 | 14-MAY-15:00 | 1060.56 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.81 | 17-JUN-17:02 | 900.37 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 583.04 | 11-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.72 | 21-JUL-03:10 | 653.87 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 592.27 | 24-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.17 | 13-AUG-12:52 | 420.23 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 760.71 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.38 | 16-SEP-17:02 | 754.89 | 29-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1103.27 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 960.96 | 08-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1689.79 | 17-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2923.98 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.23 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 288.17 | 3202.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 739.33 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2132.20 | 12-JAN-05:45 |
February | 1239.33 | 01-FEB-08:09 | 644.87 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2228.82 | 13-FEB-05:56 |
March | 1239.33 | 01-MAR-08:09 | 410.74 | 01-MAR-17:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 | 15-MAR-14:10 | 1240.85 | 26-MAR-10:00 |
April | 1239.33 | 03-APR-07:10 | 391.71 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1150.53 | 16-APR-07:00 |
May | 1239.33 | 01-MAY-07:10 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 | 10-MAY-14:30 | 805.04 | 29-MAY-14:00 |
June | 1239.33 | 01-JUN-07:10 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.03 | 17-JUN-17:02 | 610.54 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.93 | 21-JUL-03:06 | 438.16 | 06-JUL-02:00 |
August | 1239.33 | 01-AUG-07:10 | 376.79 | 28-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.46 | 13-AUG-13:05 | 280.78 | 30-AUG-21:10 |
September | 1239.33 | 01-SEP-07:10 | 403.80 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 | 16-SEP-13:00 | 501.19 | 29-SEP-04:00 |
October | 1239.33 | 02-OCT-07:10 | 585.34 | 26-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 679.64 | 08-OCT-09:00 |
November | 1239.33 | 01-NOV-07:10 | 739.33 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1132.52 | 17-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 739.33 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1940.36 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.78 | |||||
Maximum of Months | 1239.33 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 181.46 | 2228.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3198.28 | 12-JAN-05:42 |
February | 2010.83 | 01-FEB-10:09 | 969.03 | 01-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3343.12 | 13-FEB-05:58 |
March | 2010.83 | 01-MAR-10:09 | 769.08 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.19 | 15-MAR-14:00 | 2138.53 | 26-MAR-13:00 |
April | 2010.83 | 03-APR-09:09 | 629.39 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1719.19 | 16-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 596.24 | 11-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.68 | 10-MAY-14:00 | 1196.13 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 545.88 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.63 | 17-JUN-17:02 | 912.94 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 586.81 | 11-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.15 | 21-JUL-03:06 | 658.96 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 594.53 | 24-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.24 | 13-AUG-13:05 | 425.88 | 20-AUG-15:00 |
September | 2010.83 | 01-SEP-09:09 | 741.03 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.54 | 16-SEP-13:05 | 761.49 | 29-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 960.86 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1027.09 | 08-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1740.35 | 17-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2969.60 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.88 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 264.24 | 3343.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2132.17 | 12-JAN-05:47 |
February | 1295.83 | 01-FEB-10:09 | 635.37 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2228.80 | 13-FEB-05:56 |
March | 1295.83 | 01-MAR-10:09 | 540.85 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 15-MAR-14:00 | 1371.34 | 25-MAR-17:04 |
April | 1295.83 | 03-APR-09:09 | 411.83 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1167.24 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 393.13 | 11-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 | 10-MAY-14:00 | 831.37 | 29-MAY-15:10 |
June | 1295.83 | 01-JUN-09:09 | 373.40 | 21-JUN-08:09 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.95 | 12-JUN-13:00 | 625.83 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 388.20 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.77 | 21-JUL-03:06 | 463.32 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 395.87 | 24-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.57 | 13-AUG-13:05 | 367.86 | 27-AUG-16:30 |
September | 1295.83 | 01-SEP-09:09 | 518.52 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 | 16-SEP-13:00 | 509.07 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 710.81 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 665.90 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1160.45 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1994.83 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 373.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.86 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 181.57 | 2228.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3926.36 | 12-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 992.60 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3776.80 | 13-FEB-06:00 |
March | 2010.79 | 01-MAR-10:09 | 794.49 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.58 | 15-MAR-14:00 | 2298.51 | 02-MAR-05:09 |
April | 2010.79 | 03-APR-09:09 | 630.29 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1878.07 | 04-APR-21:03 |
May | 2010.79 | 01-MAY-09:09 | 592.74 | 11-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 10-MAY-14:00 | 1309.78 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.48 | 17-JUN-17:02 | 1096.68 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 582.77 | 11-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.30 | 21-JUL-03:10 | 784.47 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 592.02 | 24-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.85 | 13-AUG-12:56 | 511.81 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 759.95 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.35 | 16-SEP-13:00 | 837.36 | 29-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1103.25 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1036.55 | 30-OCT-04:52 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1979.55 | 17-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3521.19 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.81 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 341.85 | 3926.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2673.95 | 12-JAN-05:58 |
February | 1295.83 | 01-FEB-10:09 | 644.68 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2777.48 | 13-FEB-06:00 |
March | 1295.83 | 01-MAR-10:09 | 410.74 | 01-MAR-17:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 | 15-MAR-14:00 | 1543.37 | 02-MAR-05:04 |
April | 1295.83 | 03-APR-09:09 | 391.57 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1252.28 | 04-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 10-MAY-14:00 | 1000.86 | 29-MAY-13:53 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.52 | 17-JUN-17:02 | 743.15 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.74 | 21-JUL-03:06 | 524.73 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 376.62 | 28-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.06 | 13-AUG-12:56 | 341.24 | 30-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 403.69 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 | 16-SEP-13:00 | 555.49 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 585.07 | 26-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 713.84 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1319.70 | 17-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2345.46 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.24 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 233.06 | 2777.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4010.94 | 12-JAN-06:00 |
February | 2010.83 | 01-FEB-10:09 | 968.70 | 01-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4102.61 | 13-FEB-05:50 |
March | 2010.83 | 01-MAR-10:09 | 768.37 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 15-MAR-14:00 | 2439.44 | 26-MAR-13:00 |
April | 2010.83 | 03-APR-09:09 | 629.23 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1878.94 | 04-APR-21:03 |
May | 2010.83 | 01-MAY-09:09 | 596.01 | 11-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 10-MAY-14:00 | 1475.31 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 545.88 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.64 | 17-JUN-17:02 | 1111.89 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 586.55 | 11-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.63 | 21-JUL-03:06 | 790.35 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 594.29 | 24-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 335.33 | 13-AUG-12:54 | 524.99 | 20-AUG-15:20 |
September | 2010.83 | 01-SEP-09:09 | 740.25 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.35 | 16-SEP-13:00 | 848.47 | 29-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 960.83 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1148.24 | 09-OCT-11:42 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1986.19 | 17-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3568.92 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.99 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 335.33 | 4102.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2673.95 | 12-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 635.16 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2777.53 | 13-FEB-05:58 |
March | 1295.83 | 01-MAR-10:09 | 540.47 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 | 15-MAR-14:00 | 1709.26 | 25-MAR-17:08 |
April | 1295.83 | 03-APR-09:09 | 411.74 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1289.15 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 393.00 | 11-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 10-MAY-14:00 | 1036.06 | 29-MAY-15:10 |
June | 1295.83 | 01-JUN-09:09 | 373.26 | 21-JUN-08:09 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.14 | 12-JUN-13:00 | 762.17 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 388.06 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.42 | 21-JUL-03:06 | 557.31 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 395.75 | 24-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.04 | 13-AUG-12:56 | 470.30 | 27-AUG-16:50 |
September | 1295.83 | 01-SEP-09:09 | 518.08 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 | 16-SEP-13:00 | 574.21 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 710.80 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 721.84 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1333.75 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2409.39 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 373.26 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.30 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 238.04 | 2777.53 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2868.67 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2868.67 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2868.67 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2868.67 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2868.67 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2868.67 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2868.67 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2868.67 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2868.67 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2868.67 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2868.67 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2868.67 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2985.64 | 12-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3038.04 | 13-FEB-05:54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.98 | 15-MAR-14:00 | 1959.42 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1843.39 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 | 14-MAY-15:00 | 876.99 | 29-MAY-13:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.29 | 17-JUN-17:02 | 865.96 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.07 | 21-JUL-02:53 | 627.88 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.13 | 13-AUG-13:00 | 392.62 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.01 | 16-SEP-13:00 | 770.06 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 999.73 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1790.56 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2955.47 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.62 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.13 | 3038.04 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4954.54 | 12-JAN-05:52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4954.29 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.06 | 15-MAR-14:00 | 3217.27 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3109.42 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.23 | 14-MAY-15:00 | 1496.75 | 29-MAY-14:40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.91 | 17-JUN-17:02 | 1498.59 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.89 | 21-JUL-02:53 | 1092.34 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.35 | 13-AUG-12:52 | 699.42 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.80 | 16-SEP-17:02 | 1348.76 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1703.00 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3020.52 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4938.32 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 699.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.35 | 4954.54 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5390.94 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5381.47 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.62 | 15-MAR-14:00 | 3281.02 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2969.22 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 | 10-MAY-15:00 | 2077.03 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.29 | 17-JUN-17:02 | 1695.42 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.17 | 21-JUL-02:00 | 1197.13 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.76 | 13-AUG-13:00 | 783.80 | 30-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.40 | 16-SEP-13:00 | 1344.30 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1602.53 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3106.88 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5518.54 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 783.80 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.76 | 5518.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92417.10 | 02-JAN-07:03 | 10771.35 | 10174.29 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91068.57 | 21-FEB-07:03 | 14361.80 | 13565.72 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90294.70 | 16-MAR-06:12 | 21542.70 | 20348.58 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 92866.98 | 24-APR-06:03 | 10771.35 | 10174.29 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95884.71 | 30-MAY-06:11 | 32314.05 | 30522.86 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98482.55 | 13-JUN-06:05 | 7180.90 | 6782.86 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 100273.11 | 12-JUL-06:11 | 32314.05 | 30522.86 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 97516.34 | 21-AUG-06:11 | 28723.60 | 27131.43 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 98372.82 | 11-SEP-06:11 | 32314.05 | 30522.86 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 98278.66 | 23-OCT-06:11 | 32314.05 | 30522.86 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94375.72 | 13-NOV-07:05 | 7180.90 | 6782.86 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 94505.07 | 26-DEC-07:03 | 14361.80 | 13565.72 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90294.70 | 7180.90 | 6782.86 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100273.11 | 32314.05 | 30522.86 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 70856.08 | 17-JAN-06:03 | 6448.95 | 2149.44 | 30589.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73570.87 | 24-FEB-06:02 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 83343.35 | 16-MAR-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82919.80 | 10-APR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85480.99 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88467.23 | 28-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83542.48 | 10-JUL-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81693.88 | 22-AUG-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86409.35 | 18-SEP-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83187.45 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 83893.09 | 13-NOV-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 78045.20 | 18-DEC-05:01 | 0.00 | 7106.42 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 70856.08 | 0.00 | 2149.44 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88467.23 | 12897.91 | 7106.42 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17777.31 | 06-JAN-11:20 | 30632.53 | 18274.19 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19443.80 | 28-FEB-11:48 | 61265.06 | 36548.37 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70141.97 | 17-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67796.30 | 10-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73480.50 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73101.42 | 30-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73281.18 | 06-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 73400.78 | 01-AUG-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75141.46 | 18-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70282.17 | 13-OCT-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65187.39 | 01-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19655.64 | 01-DEC-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17777.31 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75141.46 | 61265.06 | 36548.37 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13646.71 | 11-JAN-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14554.07 | 28-FEB-14:10 | 32029.16 | 18274.19 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 67769.89 | 16-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32566.98 | 21-APR-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69597.85 | 24-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72488.43 | 19-JUN-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 72489.66 | 21-JUL-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75287.50 | 07-AUG-04:14 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72186.21 | 18-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 46758.53 | 13-OCT-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19288.34 | 01-NOV-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14429.76 | 01-DEC-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13646.71 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75287.50 | 32029.16 | 18274.19 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2104.98 | 17-JAN-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.36 |
February | 2091.87 | 28-FEB-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.25 |
March | 8857.83 | 16-MAR-04:11 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.59 |
April | 6677.74 | 07-APR-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 |
May | 8689.30 | 24-MAY-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.71 |
June | 15388.11 | 11-JUN-18:41 | 0.00 | 272.92 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.59 |
July | 14988.55 | 16-JUL-15:51 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 51.58 | 0.00 |
August | 15203.88 | 06-AUG-16:21 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 10.66 | 0.00 |
September | 11724.10 | 15-SEP-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 |
October | 5665.46 | 12-OCT-12:10 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.29 |
November | 4559.05 | 27-NOV-12:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.45 |
December | 2570.32 | 01-DEC-13:10 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2091.87 | 0.00 | 242.60 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15388.11 | 3846.22 | 1091.73 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 51.58 | 123.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1660.87 | 12-JAN-10:10 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.21 |
February | 6107.09 | 28-FEB-09:35 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.33 |
March | 9165.44 | 21-MAR-08:55 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.59 |
April | 16077.30 | 23-APR-10:32 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.30 |
May | 18250.57 | 07-MAY-07:33 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.65 |
June | 23357.78 | 11-JUN-08:41 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.53 |
July | 23538.56 | 16-JUL-09:11 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.38 |
August | 21511.05 | 06-AUG-09:01 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.16 |
September | 21820.24 | 10-SEP-08:12 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.56 |
October | 10934.42 | 11-OCT-08:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 |
November | 6454.22 | 03-NOV-08:55 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.90 |
December | 3611.68 | 04-DEC-09:50 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1660.87 | 260.91 | 78.17 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | |
Maximum of Months | 23538.56 | 2591.66 | 703.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18710.38 | 15-JAN-13:13 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.71 |
February | 17485.48 | 28-FEB-13:30 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.24 |
March | 18702.55 | 15-MAR-13:30 | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 0.00 |
April | 20646.70 | 23-APR-14:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.79 |
May | 24238.99 | 14-MAY-13:13 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.08 |
June | 24386.94 | 18-JUN-14:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.92 |
July | 24576.97 | 30-JUL-12:12 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 |
August | 25383.02 | 27-AUG-12:42 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.17 |
September | 27129.61 | 10-SEP-12:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.92 |
October | 24280.41 | 09-OCT-13:13 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.59 |
November | 17939.55 | 03-NOV-12:30 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.36 |
December | 17323.35 | 17-DEC-11:33 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 750.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17323.35 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27129.61 | 2010.83 | 545.88 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 750.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4557.33 | 12-JAN-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.45 |
February | 9461.71 | 28-FEB-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.98 |
March | 22053.74 | 16-MAR-04:11 | 0.00 | 304.37 | 3363.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 |
April | 26848.44 | 02-APR-16:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.18 |
May | 29744.00 | 07-MAY-16:11 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.53 |
June | 31083.02 | 11-JUN-16:41 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.84 |
July | 29040.62 | 02-JUL-16:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.44 |
August | 30917.81 | 06-AUG-16:21 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.65 |
September | 28247.91 | 10-SEP-17:31 | 0.00 | 136.80 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.91 |
October | 17992.22 | 09-OCT-15:53 | 260.91 | 78.17 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.24 |
November | 15747.32 | 27-NOV-05:12 | 0.00 | 217.40 | 2402.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.21 |
December | 7861.83 | 04-DEC-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4557.33 | 0.00 | 78.17 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.65 | |
Maximum of Months | 31083.02 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1338.95 | 11-JAN-16:00 | 1923.11 | 617.21 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.90 |
February | 1382.57 | 17-FEB-15:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.40 |
March | 5684.89 | 15-MAR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 | 0.00 |
April | 4354.90 | 07-APR-13:50 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 |
May | 6892.88 | 23-MAY-14:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 |
June | 12530.73 | 11-JUN-18:41 | 0.00 | 272.92 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.97 |
July | 13806.36 | 16-JUL-13:23 | 404.87 | 121.30 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 38.54 | 0.00 |
August | 9740.36 | 11-AUG-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.99 |
September | 6982.76 | 14-SEP-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 |
October | 3981.47 | 12-OCT-14:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.74 |
November | 2364.70 | 07-NOV-11:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.50 |
December | 1599.25 | 01-DEC-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1338.95 | 0.00 | 121.30 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13806.36 | 2010.79 | 617.21 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 38.54 | 269.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1322.20 | 06-JAN-11:20 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.11 |
February | 7632.71 | 28-FEB-09:58 | 4957.30 | 1407.10 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.10 |
March | 8611.29 | 21-MAR-10:13 | 3717.98 | 1055.32 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.39 |
April | 17058.08 | 23-APR-10:32 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.07 |
May | 18387.25 | 21-MAY-09:12 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.59 |
June | 25303.35 | 11-JUN-10:01 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.10 |
July | 24473.60 | 04-JUL-09:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.68 |
August | 22985.74 | 20-AUG-09:42 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.31 |
September | 21296.17 | 04-SEP-09:02 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.46 |
October | 10679.70 | 11-OCT-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 |
November | 5855.24 | 03-NOV-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.62 |
December | 1107.81 | 04-DEC-09:55 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1107.81 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 | |
Maximum of Months | 25303.35 | 4957.30 | 1407.10 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17181.17 | 15-JAN-14:33 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.05 |
February | 19341.54 | 28-FEB-11:48 | 7692.61 | 2183.50 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.30 |
March | 19016.79 | 01-MAR-13:50 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.13 |
April | 21872.36 | 23-APR-14:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.29 |
May | 24330.74 | 14-MAY-13:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.88 |
June | 23825.83 | 25-JUN-13:02 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.70 |
July | 24558.54 | 30-JUL-12:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.81 |
August | 25313.10 | 27-AUG-13:12 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.35 |
September | 26457.80 | 03-SEP-12:32 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.27 |
October | 25264.39 | 09-OCT-11:42 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 948.38 |
November | 18993.80 | 03-NOV-12:30 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.28 |
December | 12592.87 | 04-DEC-11:50 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12592.87 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.70 | |
Maximum of Months | 26457.80 | 7692.61 | 2183.50 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1477.90 | 12-JAN-15:50 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.93 |
February | 6005.83 | 28-FEB-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.78 |
March | 8990.06 | 21-MAR-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.18 |
April | 23688.14 | 30-APR-15:51 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.20 |
May | 24859.64 | 07-MAY-16:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.23 |
June | 28545.69 | 11-JUN-16:41 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.50 |
July | 26702.00 | 02-JUL-17:21 | 0.00 | 136.80 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.86 |
August | 25822.48 | 27-AUG-16:31 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.16 |
September | 24567.92 | 04-SEP-17:02 | 0.00 | 117.25 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.74 |
October | 11766.06 | 11-OCT-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 |
November | 5071.86 | 15-NOV-15:20 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.18 |
December | 1984.82 | 04-DEC-15:50 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1477.90 | 0.00 | 117.25 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 | |
Maximum of Months | 28545.69 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1209.01 | 14-JAN-17:03 | 303.65 | 191.20 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 |
February | 1310.56 | 22-FEB-16:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.20 |
March | 6188.31 | 15-MAR-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 0.00 |
April | 4111.29 | 20-APR-15:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.84 |
May | 7165.33 | 23-MAY-14:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 |
June | 11528.70 | 18-JUN-11:43 | 404.87 | 121.30 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.45 |
July | 16093.46 | 16-JUL-15:51 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 134.20 | 0.00 |
August | 15864.08 | 13-AUG-15:31 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 226.84 | 0.00 |
September | 7064.42 | 15-SEP-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 9.76 | 0.00 |
October | 3864.53 | 12-OCT-15:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.09 |
November | 1786.38 | 16-NOV-16:50 | 1923.11 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.88 |
December | 1375.67 | 01-DEC-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1209.01 | 303.65 | 121.30 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16093.46 | 2010.79 | 1147.25 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 226.84 | 310.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 905.68 | 20-JAN-06:04 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.52 |
February | 1821.62 | 28-FEB-10:10 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.57 |
March | 5932.02 | 15-MAR-09:30 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
April | 12248.17 | 23-APR-10:32 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.97 |
May | 16676.01 | 21-MAY-10:53 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.95 |
June | 23134.04 | 11-JUN-09:32 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.80 |
July | 26331.15 | 16-JUL-09:11 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 |
August | 21090.97 | 06-AUG-09:12 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.70 |
September | 23057.63 | 10-SEP-10:02 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.86 |
October | 8111.34 | 11-OCT-09:30 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.71 |
November | 2320.50 | 03-NOV-09:50 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.06 |
December | 912.28 | 13-DEC-06:04 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 905.68 | 260.91 | 78.17 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 | |
Maximum of Months | 26331.15 | 2591.66 | 703.55 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12401.71 | 12-JAN-13:40 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 930.41 |
February | 16907.06 | 28-FEB-13:55 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.94 |
March | 18868.88 | 15-MAR-13:30 | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 0.00 |
April | 19295.58 | 23-APR-14:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.55 |
May | 26662.14 | 14-MAY-13:42 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.12 |
June | 25766.61 | 25-JUN-13:02 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.21 |
July | 26524.42 | 30-JUL-12:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.25 |
August | 26884.97 | 13-AUG-12:12 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 123.55 | 0.00 |
September | 29671.73 | 10-SEP-12:41 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.39 |
October | 21779.16 | 31-OCT-13:30 | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.96 |
November | 16829.60 | 03-NOV-12:40 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.01 |
December | 10321.58 | 16-DEC-13:30 | 202.44 | 90.98 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10321.58 | 202.44 | 90.98 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29671.73 | 3846.30 | 1091.75 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 123.55 | 930.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1239.68 | 12-JAN-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.86 |
February | 5786.65 | 28-FEB-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.95 |
March | 8427.48 | 21-MAR-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.46 |
April | 14979.31 | 30-APR-17:03 | 0.00 | 78.17 | 1441.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.36 |
May | 28267.26 | 07-MAY-17:41 | 0.00 | 156.34 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.33 |
June | 27482.90 | 11-JUN-16:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.24 |
July | 28322.86 | 02-JUL-17:01 | 0.00 | 136.80 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.33 |
August | 26685.16 | 13-AUG-15:31 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 77.02 | 0.00 |
September | 27537.65 | 10-SEP-16:01 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.23 |
October | 11719.93 | 11-OCT-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 |
November | 4184.31 | 15-NOV-15:20 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.44 |
December | 1265.41 | 04-DEC-15:50 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1239.68 | 0.00 | 78.17 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28322.86 | 1239.33 | 351.77 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 77.02 | 550.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6164.40 | 04-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.61 |
February | 6015.11 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2039.77 |
March | 5282.73 | 16-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.21 |
April | 6730.29 | 10-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.79 |
May | 8121.53 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.82 |
June | 10532.28 | 28-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.97 |
July | 11069.81 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 |
August | 11000.36 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 |
September | 9097.26 | 18-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.02 |
October | 6616.72 | 23-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.50 |
November | 5289.07 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.70 |
December | 4633.52 | 28-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4633.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 | |
Maximum of Months | 11069.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2039.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9028.63 | 24-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3521.81 |
February | 9866.37 | 21-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3742.42 |
March | 9888.31 | 04-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1200.00 |
April | 5221.13 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 |
May | 4269.51 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.12 |
June | 5676.12 | 21-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.11 |
July | 6401.71 | 17-JUL-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.92 | 0.00 |
August | 7094.26 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.80 |
September | 5619.20 | 18-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.54 |
October | 6329.05 | 17-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.18 |
November | 7669.55 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.24 |
December | 8476.33 | 27-DEC-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2924.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4269.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9888.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.92 | 3742.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 974.72 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.47 |
March | 10569.41 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 0.00 |
April | 8983.64 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.59 |
May | 13230.58 | 31-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.27 |
June | 17707.00 | 12-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.08 | 0.00 |
July | 17290.00 | 21-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.03 | 0.00 |
August | 16962.48 | 09-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 | 0.00 |
September | 12830.02 | 21-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 0.00 |
October | 6912.11 | 11-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.29 |
November | 1071.87 | 04-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.66 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1226.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17707.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.08 | 1449.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1850.67 | 12-JAN-16:40 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4065.94 | 28-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6981.42 | 31-MAR-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8178.36 | 02-APR-17:58 | 0.00 | 40.65 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3447.57 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5362.59 | 30-JUN-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7268.09 | 31-JUL-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8191.91 | 02-AUG-18:50 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3224.05 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5140.24 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5758.38 | 24-NOV-16:20 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7646.42 | 04-DEC-16:20 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1850.67 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8191.91 | 222.14 | 146.32 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1435.81 | 12-JAN-16:50 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3531.80 | 28-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6207.41 | 31-MAR-23:40 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7629.63 | 24-APR-18:00 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3259.10 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5113.74 | 30-JUN-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6983.65 | 31-JUL-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7859.55 | 02-AUG-18:40 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2758.58 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4503.74 | 31-OCT-23:50 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5295.42 | 15-NOV-16:20 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6861.01 | 04-DEC-16:30 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1435.81 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7859.55 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1202.34 | 12-JAN-16:40 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3479.95 | 28-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5752.50 | 31-MAR-23:20 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7625.39 | 24-APR-18:00 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3156.94 | 31-MAY-23:40 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5035.84 | 30-JUN-23:40 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6963.42 | 31-JUL-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7913.99 | 02-AUG-18:40 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2495.23 | 04-SEP-17:42 | 0.00 | 40.65 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4061.01 | 31-OCT-23:20 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5139.37 | 15-NOV-16:30 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6512.02 | 04-DEC-16:30 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1202.34 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7913.99 | 222.14 | 146.32 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 89738.06 | 18-JAN-17:00 | 4808.68 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 181259.62 | 23-FEB-17:00 | 4808.68 | 2868.67 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357516.10 | 31-MAR-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 365970.78 | 24-APR-16:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175302.80 | 31-MAY-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267600.67 | 30-JUN-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359741.06 | 31-JUL-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377688.32 | 15-AUG-16:41 | 10629.71 | 11155.92 | 2657427.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175294.51 | 30-SEP-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267718.26 | 31-OCT-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275036.03 | 06-NOV-15:00 | 5027.92 | 2868.67 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 365881.43 | 04-DEC-16:55 | 9617.36 | 5737.34 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 89738.06 | 0.00 | 159.37 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 377688.32 | 10629.71 | 11155.92 | 2657427.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.144098E+13 | 974364.12 | 13-JAN-16:00 | 0.314229E+12 | 1478009.75 | 02-JAN-05:10 |
February | 0.168099E+13 | 1107361.18 | 28-FEB-16:10 | 0.242836E+12 | 1128919.07 | 06-FEB-06:10 |
March | 0.223384E+13 | 1494784.63 | 15-MAR-14:30 | 0.746725E+11 | 853267.07 | 24-MAR-08:30 |
April | 0.245957E+13 | 1525312.31 | 07-APR-14:09 | 0.118879E+11 | 415804.33 | 17-APR-05:10 |
May | 0.149185E+13 | 1296217.02 | 23-MAY-14:30 | 0.139188E+10 | 300456.80 | 11-MAY-13:20 |
June | 0.196075E+13 | 1502650.99 | 27-JUN-07:40 | 0.192217E+09 | 137899.26 | 13-JUN-11:09 |
July | 0.254200E+13 | 1830750.07 | 05-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.290138E+13 | 1870839.05 | 28-AUG-14:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.144968E+13 | 1314045.07 | 15-SEP-10:39 | 0.199580E+09 | 74155.63 | 29-SEP-13:30 |
October | 0.178077E+13 | 1212696.21 | 11-OCT-15:00 | 0.104887E+11 | 389410.29 | 17-OCT-05:10 |
November | 0.214507E+13 | 1280562.90 | 17-NOV-16:00 | 0.429998E+11 | 610245.93 | 24-NOV-05:10 |
December | 0.254596E+13 | 1391906.28 | 18-DEC-16:40 | 0.239468E+12 | 1131230.13 | 11-DEC-06:10 |
Annual Sum or Average | 0.246329E+14 | 0.938366E+12 | ||||
Minimum of Months | 0.144098E+13 | 974364.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.290138E+13 | 1870839.05 | 0.314229E+12 | 1478009.75 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.157600E+11 | 50236.52 | 30-JAN-12:30 | 0.00 | 0.00 |
February | 0.224470E+11 | 64700.70 | 28-FEB-12:30 | 0.00 | 0.00 |
March | 0.360968E+11 | 77982.28 | 25-MAR-12:30 | 0.00 | 0.00 |
April | 0.445712E+11 | 84986.98 | 17-APR-12:20 | 0.00 | 0.00 |
May | 0.559169E+11 | 85929.22 | 31-MAY-12:20 | 0.00 | 0.00 |
June | 0.617871E+11 | 89495.83 | 14-JUN-11:50 | 0.00 | 0.00 |
July | 0.584419E+11 | 84194.36 | 01-JUL-12:30 | 0.00 | 0.00 |
August | 0.502898E+11 | 76456.40 | 08-AUG-12:20 | 0.00 | 0.00 |
September | 0.375999E+11 | 71284.12 | 07-SEP-12:30 | 0.00 | 0.00 |
October | 0.256783E+11 | 57850.45 | 11-OCT-11:00 | 0.00 | 0.00 |
November | 0.147183E+11 | 45750.50 | 03-NOV-11:30 | 0.00 | 0.00 |
December | 0.138440E+11 | 42450.58 | 10-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.437151E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.138440E+11 | 42450.58 | 0.00 | 0.00 | |
Maximum of Months | 0.617871E+11 | 89495.83 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.145562E+12 | 0.317292E+11 | 0.766053E+12 | 0.136274E+12 | 0.161155E+12 | 0.110083E+11 | 0.00 | 0.565074E+10 | 0.325044E+09 | 0.135059E+12 | 0.580144E+10 | 0.423663E+11 | 0.00 |
February | 0.130808E+12 | 0.251338E+11 | 0.978954E+12 | 0.124863E+12 | 0.145632E+12 | 0.100770E+11 | 0.00 | 0.175933E+11 | 0.101609E+10 | 0.202617E+12 | 0.525805E+10 | 0.390366E+11 | 0.00 |
March | 0.153759E+12 | 0.231481E+11 | 0.141687E+13 | 0.144887E+12 | 0.170138E+12 | 0.180854E+11 | 0.00 | 0.474337E+11 | 0.879339E+10 | 0.200382E+12 | 0.506050E+10 | 0.452821E+11 | 0.00 |
April | 0.136661E+12 | 0.180246E+11 | 0.165903E+13 | 0.135268E+12 | 0.175621E+12 | 0.200369E+11 | 0.00 | 0.566729E+11 | 0.103808E+11 | 0.205542E+12 | 0.282923E+10 | 0.395106E+11 | 0.00 |
May | 0.146837E+12 | 0.151986E+11 | 0.774844E+12 | 0.140580E+12 | 0.203173E+12 | 0.285248E+11 | 0.00 | 0.381065E+11 | 0.237969E+11 | 0.803537E+11 | 0.576423E+09 | 0.398592E+11 | 0.00 |
June | 0.145808E+12 | 0.134537E+11 | 0.106252E+13 | 0.139647E+12 | 0.232084E+12 | 0.441028E+11 | 0.00 | 0.160967E+12 | 0.836998E+11 | 0.404233E+11 | 0.923133E+09 | 0.371238E+11 | 0.00 |
July | 0.136676E+12 | 0.142444E+11 | 0.139340E+13 | 0.136200E+12 | 0.249690E+12 | 0.602136E+11 | 0.00 | 0.376616E+12 | 0.136570E+12 | 0.241738E+10 | 0.230713E+10 | 0.336604E+11 | 0.00 |
August | 0.152442E+12 | 0.170229E+11 | 0.173200E+13 | 0.144887E+12 | 0.248944E+12 | 0.562776E+11 | 0.00 | 0.384226E+12 | 0.123292E+12 | 0.438976E+10 | 0.174319E+10 | 0.361534E+11 | 0.00 |
September | 0.137136E+12 | 0.203784E+11 | 0.740713E+12 | 0.135267E+12 | 0.203825E+12 | 0.355474E+11 | 0.00 | 0.771540E+11 | 0.553787E+11 | 0.104668E+11 | 0.410073E+09 | 0.334005E+11 | 0.00 |
October | 0.143598E+12 | 0.258161E+11 | 0.108340E+13 | 0.136274E+12 | 0.180746E+12 | 0.218774E+11 | 0.00 | 0.346807E+11 | 0.111703E+11 | 0.104701E+12 | 0.238730E+10 | 0.361224E+11 | 0.00 |
November | 0.144274E+12 | 0.293566E+11 | 0.135889E+13 | 0.131109E+12 | 0.163936E+12 | 0.174480E+11 | 0.00 | 0.365768E+11 | 0.754541E+10 | 0.213935E+12 | 0.435015E+10 | 0.376521E+11 | 0.00 |
December | 0.141850E+12 | 0.329043E+11 | 0.170972E+13 | 0.136201E+12 | 0.160818E+12 | 0.116925E+11 | 0.00 | 0.433589E+11 | 0.283393E+10 | 0.261231E+12 | 0.565633E+10 | 0.396977E+11 | 0.00 |
Annual Sum or Average | 0.171541E+13 | 0.266411E+12 | 0.146764E+14 | 0.164146E+13 | 0.229576E+13 | 0.334892E+12 | 0.00 | 0.127904E+13 | 0.464802E+12 | 0.146152E+13 | 0.373029E+11 | 0.459865E+12 | 0.00 |
Minimum of Months | 0.130808E+12 | 0.134537E+11 | 0.740713E+12 | 0.124863E+12 | 0.145632E+12 | 0.100770E+11 | 0.00 | 0.565074E+10 | 0.325044E+09 | 0.241738E+10 | 0.410073E+09 | 0.334005E+11 | 0.00 |
Maximum of Months | 0.153759E+12 | 0.329043E+11 | 0.173200E+13 | 0.144887E+12 | 0.249690E+12 | 0.602136E+11 | 0.00 | 0.384226E+12 | 0.136570E+12 | 0.261231E+12 | 0.580144E+10 | 0.452821E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.314229E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.242836E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.746725E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.118879E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.139188E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.192217E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.199580E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104887E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.429998E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.239468E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.938366E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.314229E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 169722.15 | 02-JAN-16:49 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 154953.34 | 11-JAN-08:20 | 95862.42 | 02-JAN-06:19 | 22264.60 | 10-JAN-11:30 | 0.00 | 01-JAN-00:10 |
February | 163051.29 | 01-FEB-16:00 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 154952.82 | 01-FEB-08:20 | 87380.28 | 28-FEB-15:30 | 22244.20 | 28-FEB-10:30 | 0.00 | 01-FEB-00:10 |
March | 154605.14 | 17-MAR-07:10 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 154948.54 | 17-MAR-07:19 | 158074.65 | 15-MAR-14:30 | 23829.71 | 15-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 149217.08 | 12-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 154945.72 | 12-APR-07:19 | 157966.03 | 26-APR-14:39 | 22409.23 | 20-APR-13:20 | 0.00 | 01-APR-00:10 |
May | 147667.94 | 11-MAY-07:10 | 31088.59 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 154944.91 | 11-MAY-07:19 | 186890.28 | 23-MAY-14:30 | 41779.69 | 10-MAY-14:30 | 0.00 | 01-MAY-00:10 |
June | 146251.09 | 21-JUN-08:09 | 22480.63 | 01-JUN-19:49 | 541788.89 | 01-JUN-07:10 | 154944.04 | 19-JUN-07:19 | 217924.70 | 12-JUN-15:50 | 44791.42 | 01-JUN-15:20 | 0.00 | 01-JUN-00:10 |
July | 147358.89 | 11-JUL-07:30 | 22480.63 | 01-JUL-19:00 | 660080.29 | 03-JUL-07:10 | 154944.74 | 11-JUL-07:40 | 237002.01 | 18-JUL-15:20 | 45613.78 | 05-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 147671.56 | 24-AUG-07:10 | 31088.59 | 02-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 154944.91 | 24-AUG-07:19 | 255082.31 | 10-AUG-15:20 | 46170.89 | 16-AUG-12:50 | 0.00 | 01-AUG-00:10 |
September | 153547.64 | 26-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 154947.99 | 26-SEP-07:19 | 206624.21 | 21-SEP-15:00 | 43685.18 | 15-SEP-10:00 | 0.00 | 01-SEP-00:10 |
October | 164664.84 | 30-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 154953.82 | 30-OCT-07:19 | 154883.78 | 12-OCT-14:30 | 23441.78 | 11-OCT-14:09 | 0.00 | 01-OCT-00:10 |
November | 169722.15 | 06-NOV-16:00 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 154955.59 | 02-NOV-07:19 | 108234.34 | 01-NOV-12:09 | 22328.91 | 16-NOV-13:09 | 0.00 | 01-NOV-00:10 |
December | 169722.15 | 01-DEC-16:40 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 154953.84 | 18-DEC-08:20 | 88228.95 | 26-DEC-06:10 | 22264.14 | 12-DEC-19:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 146251.09 | 22480.63 | 423497.50 | 154944.04 | 87380.28 | 22244.20 | 0.00 | |||||||
Maximum of Months | 169722.15 | 31088.59 | 778371.69 | 154955.59 | 255082.31 | 46170.89 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 5249.87 | 12-JAN-16:40 | 862.12 | 17-JAN-16:30 | 78428.74 | 13-JAN-18:10 | 4520.72 | 02-JAN-07:10 | 56183.44 | 31-JAN-12:00 | 0.00 | 01-JAN-00:10 |
February | 11237.60 | 22-FEB-16:00 | 1927.32 | 22-FEB-17:00 | 100000.00 | 14-FEB-13:20 | 4520.72 | 01-FEB-07:10 | 56293.64 | 13-FEB-12:30 | 0.00 | 01-FEB-00:10 |
March | 258927.70 | 15-MAR-13:50 | 75503.64 | 14-MAR-12:00 | 100000.00 | 01-MAR-04:49 | 4520.72 | 01-MAR-07:10 | 56194.09 | 01-MAR-12:00 | 0.00 | 01-MAR-00:10 |
April | 129112.35 | 07-APR-13:20 | 44689.55 | 08-APR-13:20 | 100000.00 | 01-APR-05:10 | 4520.72 | 01-APR-06:10 | 55046.68 | 03-APR-11:00 | 0.00 | 01-APR-00:10 |
May | 210752.13 | 10-MAY-14:20 | 75503.64 | 10-MAY-13:39 | 100000.00 | 07-MAY-13:39 | 4520.72 | 01-MAY-06:10 | 52289.10 | 01-MAY-11:30 | 0.00 | 01-MAY-00:10 |
June | 369777.03 | 27-JUN-07:40 | 75503.64 | 01-JUN-14:50 | 100000.00 | 03-JUN-17:49 | 4520.72 | 01-JUN-16:49 | 48862.39 | 01-JUN-11:20 | 0.00 | 01-JUN-00:10 |
July | 511425.81 | 05-JUL-15:00 | 75503.64 | 17-JUL-05:10 | 100000.00 | 06-JUL-13:20 | 4520.72 | 03-JUL-14:09 | 46096.94 | 03-JUL-11:20 | 0.00 | 01-JUL-00:10 |
August | 461187.85 | 15-AUG-08:20 | 75503.64 | 10-AUG-12:00 | 88665.43 | 22-AUG-13:00 | 4520.72 | 03-AUG-11:00 | 44705.54 | 01-AUG-11:30 | 0.00 | 01-AUG-00:10 |
September | 273779.80 | 15-SEP-10:00 | 75503.64 | 08-SEP-12:00 | 70237.24 | 19-SEP-13:00 | 4520.72 | 06-SEP-06:10 | 46042.52 | 29-SEP-11:39 | 0.00 | 01-SEP-00:10 |
October | 123705.78 | 11-OCT-14:00 | 47305.31 | 11-OCT-14:00 | 100000.00 | 30-OCT-21:10 | 4520.72 | 02-OCT-06:10 | 48504.58 | 31-OCT-11:20 | 0.00 | 01-OCT-00:10 |
November | 59991.36 | 16-NOV-13:09 | 44306.05 | 16-NOV-13:09 | 100000.00 | 01-NOV-04:19 | 4520.72 | 01-NOV-06:10 | 52161.76 | 30-NOV-12:39 | 0.00 | 01-NOV-00:10 |
December | 32896.52 | 01-DEC-10:00 | 6231.75 | 01-DEC-10:00 | 100000.00 | 01-DEC-22:10 | 4520.72 | 01-DEC-17:10 | 54791.46 | 27-DEC-12:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 5249.87 | 862.12 | 70237.24 | 4520.72 | 44705.54 | 0.00 | ||||||
Maximum of Months | 511425.81 | 75503.64 | 100000.00 | 4520.72 | 56293.64 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 974364.12 | 13-JAN-16:00 | 169722.15 | 423497.50 | 31088.59 | 154857.58 | 67627.99 | 3808.92 | 0.00 | 4081.19 | 300.37 |
February | 1107361.18 | 28-FEB-16:10 | 145987.23 | 541788.89 | 0.00 | 154849.24 | 84424.03 | 22173.56 | 0.00 | 10680.18 | 686.15 |
March | 1494784.63 | 15-MAR-14:30 | 145987.23 | 660080.29 | 0.00 | 154722.86 | 158074.65 | 23478.49 | 0.00 | 256303.67 | 59639.94 |
April | 1525312.31 | 07-APR-14:09 | 145987.23 | 778371.69 | 0.00 | 154722.86 | 134889.45 | 22305.37 | 0.00 | 113348.74 | 44149.09 |
May | 1296217.02 | 23-MAY-14:30 | 145987.23 | 423497.50 | 0.00 | 154722.86 | 186890.28 | 22832.52 | 0.00 | 173827.83 | 59639.94 |
June | 1502650.99 | 27-JUN-07:40 | 145987.23 | 541788.89 | 0.00 | 154944.03 | 142427.93 | 43431.37 | 0.00 | 369777.03 | 75503.64 |
July | 1830750.07 | 05-JUL-15:00 | 145987.23 | 660080.29 | 0.00 | 154849.24 | 201725.75 | 45613.78 | 0.00 | 511425.81 | 75503.64 |
August | 1870839.05 | 28-AUG-14:20 | 145987.23 | 778371.69 | 0.00 | 154722.86 | 214976.23 | 44075.49 | 0.00 | 430832.23 | 75503.64 |
September | 1314045.07 | 15-SEP-10:39 | 145987.23 | 423497.50 | 0.00 | 154722.86 | 175561.52 | 43237.11 | 0.00 | 259011.74 | 75503.64 |
October | 1212696.21 | 11-OCT-15:00 | 145987.23 | 541788.89 | 0.00 | 154849.24 | 153415.63 | 23007.87 | 0.00 | 110427.08 | 46562.13 |
November | 1280562.90 | 17-NOV-16:00 | 169722.15 | 660080.29 | 31088.59 | 154861.70 | 83366.99 | 22177.02 | 0.00 | 14336.08 | 1294.49 |
December | 1391906.28 | 18-DEC-16:40 | 169722.15 | 778371.69 | 31088.59 | 154860.17 | 78182.97 | 22176.40 | 0.00 | 16674.01 | 1373.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 974364.12 | 145987.23 | 423497.50 | 0.00 | 154722.86 | 67627.99 | 3808.92 | 0.00 | 4081.19 | 300.37 | |
Maximum of Months | 1870839.05 | 169722.15 | 778371.69 | 31088.59 | 154944.03 | 214976.23 | 45613.78 | 0.00 | 511425.81 | 75503.64 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1478009.75 | 02-JAN-05:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1128919.07 | 06-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 853267.07 | 24-MAR-08:30 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 415804.33 | 17-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 300456.80 | 11-MAY-13:20 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 137899.26 | 13-JUN-11:09 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 74155.63 | 29-SEP-13:30 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 389410.29 | 17-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 610245.93 | 24-NOV-05:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1131230.13 | 11-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1478009.75 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 25.69 | 25.00 | 25.66 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 25.69 | 23.00 | 25.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 25.93 | 27.83 | 25.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 26.18 | 25.83 | 26.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 64.50 | 26.33 | 33.33 | 26.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 183.00 | 27.36 | 127.33 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 349.50 | 27.66 | 223.67 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 215.83 | 27.47 | 132.33 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 142.33 | 27.13 | 84.67 | 27.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 75.83 | 26.79 | 35.50 | 26.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 67.33 | 26.64 | 30.17 | 26.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 26.08 | 25.67 | 26.07 |
Annual Sum or Average | 0.00 | 0.00 | 1326.67 | 27.07 | 794.33 | 27.06 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 25.69 | 23.00 | 25.66 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 349.50 | 27.66 | 223.67 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.64 | 0.00 | 25.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.69 | 0.00 | 25.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 25.65 | 0.00 | 25.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.69 | 0.00 | 25.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.42 | 0.83 | 19.61 | 0.00 | 19.61 | 0.00 | 19.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 19.42 | 0.83 | 19.61 | 0.00 | 19.61 | 0.00 | 19.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.42 | 0.83 | 19.61 | 0.00 | 19.61 | 0.00 | 19.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 18.77 | 1.17 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
February | 4.33 | 18.72 | 0.83 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
March | 0.83 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
April | 0.17 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
December | 4.33 | 18.87 | 1.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
Annual Sum or Average | 15.00 | 18.80 | 3.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.17 | 19.39 | 1.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.03 | 2.67 | 27.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.98 | 1.83 | 27.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 19.25 | 0.00 | 19.25 | 6.33 | 26.44 | 4.50 | 26.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.25 | 0.00 | 19.25 | 4.00 | 27.03 | 2.67 | 27.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
February | 0.50 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.94 | 1.00 | 27.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.73 | 3.33 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.70 | 8.00 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.75 | 10.67 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.59 | 5.33 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.86 | 4.17 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.58 | 0.83 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 19.20 | 0.00 | 19.20 | 34.17 | 27.56 | 33.33 | 27.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.44 | 0.00 | 19.44 | 11.50 | 27.94 | 10.67 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.20 | 0.00 | 19.20 | 0.67 | 23.39 | 0.67 | 24.79 |
February | 0.83 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.59 | 0.83 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.68 | 2.33 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.58 | 2.83 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.61 | 5.17 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.59 | 8.83 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.67 | 7.17 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.10 | 5.33 | 28.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.28 | 5.50 | 26.28 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.36 | 0.83 | 27.36 |
December | 0.33 | 19.30 | 0.00 | 19.30 | 0.67 | 24.89 | 0.67 | 26.01 |
Annual Sum or Average | 1.83 | 19.11 | 0.00 | 19.11 | 42.83 | 27.16 | 40.17 | 27.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.95 | 0.00 | 18.95 |
Maximum of Months | 0.83 | 19.30 | 0.00 | 19.30 | 10.67 | 28.10 | 8.83 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.79 | 2.00 | 27.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.00 | 6.50 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.16 | 4.00 | 28.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.89 | 8.17 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 27.70 | 15.83 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 27.58 | 12.00 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.20 | 4.00 | 28.24 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.72 | 1.17 | 27.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.72 | 0.33 | 26.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 110.33 | 27.77 | 54.00 | 27.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 28.20 | 15.83 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.00 | 18.54 | 7.50 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
February | 24.67 | 18.42 | 7.67 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
March | 5.00 | 18.88 | 0.67 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
December | 18.67 | 18.28 | 5.33 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
Annual Sum or Average | 73.67 | 18.46 | 21.17 | 18.81 | 0.33 | 18.84 | 0.33 | 18.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.00 | 19.26 | 7.67 | 19.26 | 0.33 | 27.31 | 0.33 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.17 | 18.68 | 0.17 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
February | 19.33 | 18.07 | 0.17 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
March | 2.67 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.89 | 0.83 | 27.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.79 | 2.83 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.81 | 8.17 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.95 | 10.83 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.70 | 5.67 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.94 | 3.50 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
December | 25.67 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
Annual Sum or Average | 75.17 | 18.54 | 0.33 | 18.52 | 32.33 | 21.32 | 31.83 | 22.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.17 | 19.20 | 0.17 | 19.20 | 11.17 | 27.95 | 10.83 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.33 | 18.11 | 0.33 | 18.19 | 0.67 | 18.79 | 0.67 | 19.32 |
February | 8.67 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
March | 1.83 | 18.97 | 0.00 | 18.97 | 0.67 | 21.26 | 0.67 | 22.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.69 | 1.83 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.60 | 2.67 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.60 | 4.50 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.72 | 8.33 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.89 | 5.50 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.76 | 6.17 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.70 | 10.17 | 25.70 |
November | 0.17 | 19.26 | 0.00 | 19.26 | 0.17 | 23.32 | 0.17 | 24.67 |
December | 7.17 | 18.08 | 0.00 | 18.08 | 0.17 | 18.29 | 0.17 | 18.49 |
Annual Sum or Average | 27.17 | 18.03 | 0.33 | 18.06 | 41.67 | 23.58 | 40.83 | 24.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 0.00 | 17.67 |
Maximum of Months | 9.33 | 19.26 | 0.33 | 19.26 | 10.17 | 27.89 | 10.17 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.83 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
February | 8.00 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
March | 2.00 | 18.99 | 0.00 | 18.99 | 0.17 | 19.64 | 0.17 | 20.19 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.75 | 2.17 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.11 | 3.17 | 28.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.36 | 4.67 | 28.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 28.15 | 7.00 | 28.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.99 | 4.83 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.22 | 3.00 | 28.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
December | 6.00 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
Annual Sum or Average | 24.00 | 18.16 | 0.00 | 18.16 | 44.33 | 24.63 | 25.00 | 25.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.00 | 19.43 | 0.00 | 19.43 | 13.67 | 28.36 | 7.00 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 70.17 | 17.19 | 26.83 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 |
February | 64.83 | 17.00 | 23.83 | 17.36 | 0.00 | 17.36 | 0.00 | 17.36 |
March | 22.67 | 17.89 | 7.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
April | 2.33 | 18.98 | 0.50 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.36 | 0.67 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.48 | 2.33 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.39 | 2.00 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.17 | 18.94 | 0.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
November | 7.50 | 18.97 | 1.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
December | 56.33 | 17.18 | 20.67 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 |
Annual Sum or Average | 226.00 | 17.30 | 80.17 | 17.59 | 5.83 | 17.78 | 5.00 | 17.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.17 | 18.98 | 26.83 | 19.17 | 3.00 | 27.48 | 2.33 | 27.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.33 | 15.62 | 5.67 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
February | 31.00 | 15.56 | 2.67 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
March | 10.17 | 16.80 | 0.17 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
April | 1.33 | 18.59 | 0.00 | 18.59 | 0.50 | 21.04 | 0.50 | 22.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.74 | 1.83 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.82 | 8.33 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.97 | 11.83 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.70 | 6.83 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.82 | 2.50 | 27.82 |
October | 1.33 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
November | 3.83 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
December | 28.83 | 15.66 | 4.50 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
Annual Sum or Average | 109.83 | 15.89 | 13.00 | 15.79 | 34.33 | 18.43 | 31.83 | 20.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 0.00 | 15.50 |
Maximum of Months | 33.33 | 18.59 | 5.67 | 18.59 | 13.17 | 27.97 | 11.83 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.00 | 16.07 | 3.33 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 |
February | 30.33 | 16.24 | 2.50 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
March | 7.83 | 17.56 | 0.17 | 17.51 | 0.00 | 17.51 | 0.00 | 17.51 |
April | 1.17 | 18.62 | 0.00 | 18.62 | 1.17 | 23.14 | 1.17 | 24.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.70 | 2.17 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.68 | 5.17 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.84 | 9.00 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.95 | 6.00 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.19 | 4.83 | 28.20 |
October | 1.00 | 18.45 | 0.00 | 18.45 | 2.50 | 23.85 | 2.50 | 24.75 |
November | 3.67 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
December | 24.50 | 16.37 | 2.50 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
Annual Sum or Average | 98.50 | 16.47 | 8.50 | 16.46 | 33.67 | 19.16 | 30.83 | 20.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | 0.00 | 16.03 |
Maximum of Months | 30.33 | 18.72 | 3.33 | 18.72 | 10.50 | 28.19 | 9.00 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.83 | 15.83 | 4.33 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
February | 19.00 | 16.13 | 0.67 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
March | 5.17 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
April | 0.50 | 18.89 | 0.00 | 18.89 | 2.67 | 26.23 | 2.00 | 26.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.09 | 3.50 | 28.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.42 | 4.83 | 28.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 28.18 | 8.17 | 28.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.03 | 5.33 | 28.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.12 | 3.17 | 28.17 |
October | 0.83 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
November | 2.83 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
December | 18.00 | 16.24 | 2.00 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
Annual Sum or Average | 74.17 | 16.32 | 7.00 | 16.21 | 47.83 | 20.64 | 27.00 | 21.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 0.00 | 15.70 |
Maximum of Months | 27.83 | 18.89 | 4.33 | 18.89 | 15.67 | 28.42 | 8.17 | 28.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 28.42 | 14.00 | 28.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 29.23 | 78.17 | 29.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 127.33 | 29.05 | 92.17 | 29.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 29.23 | 78.17 | 29.20 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 320.33 | 24.12 | 38.33 | 24.32 | 13.83 | 24.40 |
February | 294.83 | 24.01 | 21.33 | 24.15 | 0.00 | 24.15 |
March | 209.83 | 24.01 | 101.50 | 24.41 | 0.00 | 24.41 |
April | 46.67 | 24.00 | 117.00 | 25.51 | 0.00 | 25.51 |
May | 38.83 | 24.00 | 192.50 | 25.20 | 0.00 | 25.20 |
June | 118.17 | 27.26 | 357.50 | 26.14 | 118.17 | 26.36 |
July | 218.17 | 27.68 | 486.17 | 26.55 | 218.17 | 26.82 |
August | 117.50 | 27.56 | 472.83 | 25.79 | 117.50 | 26.09 |
September | 57.67 | 27.06 | 375.67 | 25.43 | 57.67 | 25.62 |
October | 5.83 | 24.66 | 222.67 | 25.52 | 1.00 | 25.53 |
November | 54.50 | 24.09 | 146.17 | 25.50 | 1.33 | 25.52 |
December | 203.50 | 24.01 | 90.83 | 24.66 | 0.00 | 24.66 |
Annual Sum or Average | 1685.83 | 25.09 | 2622.50 | 25.43 | 527.67 | 25.65 |
Minimum of Months | 5.83 | 24.00 | 21.33 | 24.15 | 0.00 | 24.15 |
Maximum of Months | 320.33 | 27.68 | 486.17 | 26.55 | 218.17 | 26.82 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 439.50 | 23.84 | 13.33 | 23.86 | 13.00 | 23.89 |
February | 381.67 | 23.90 | 6.67 | 23.93 | 0.00 | 23.93 |
March | 226.17 | 23.99 | 89.17 | 24.20 | 0.00 | 24.20 |
April | 34.33 | 24.00 | 87.17 | 25.04 | 0.00 | 25.04 |
May | 47.00 | 23.99 | 164.67 | 24.56 | 0.00 | 24.56 |
June | 0.00 | 0.00 | 350.33 | 24.36 | 0.00 | 24.36 |
July | 0.00 | 0.00 | 487.00 | 24.30 | 0.00 | 24.30 |
August | 0.00 | 0.00 | 482.83 | 24.25 | 0.00 | 24.25 |
September | 0.00 | 0.00 | 345.00 | 24.45 | 0.00 | 24.45 |
October | 20.83 | 23.98 | 189.67 | 24.81 | 0.00 | 24.81 |
November | 71.33 | 24.00 | 94.67 | 24.88 | 0.00 | 24.88 |
December | 253.17 | 23.96 | 46.33 | 24.21 | 0.00 | 24.21 |
Annual Sum or Average | 1474.00 | 23.92 | 2356.83 | 24.30 | 13.00 | 24.30 |
Minimum of Months | 0.00 | 0.00 | 6.67 | 23.86 | 0.00 | 23.89 |
Maximum of Months | 439.50 | 24.00 | 487.00 | 25.04 | 13.00 | 25.04 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.85 | 67.00 | 21.67 | 67.00 | 21.52 |
February | 454.00 | 22.11 | 28.67 | 22.05 | 28.67 | 21.99 |
March | 432.33 | 23.23 | 26.00 | 23.28 | 0.50 | 23.27 |
April | 317.67 | 23.64 | 7.83 | 23.67 | 0.00 | 23.67 |
May | 169.00 | 23.81 | 116.67 | 24.10 | 0.00 | 24.10 |
June | 32.50 | 23.86 | 285.50 | 24.18 | 0.00 | 24.18 |
July | 0.00 | 0.00 | 468.67 | 24.22 | 0.00 | 24.22 |
August | 0.00 | 0.00 | 431.17 | 24.22 | 0.00 | 24.22 |
September | 26.67 | 23.60 | 244.83 | 24.28 | 0.00 | 24.28 |
October | 260.17 | 23.65 | 42.17 | 23.77 | 0.00 | 23.77 |
November | 430.50 | 23.44 | 1.50 | 23.44 | 0.00 | 23.44 |
December | 492.00 | 22.24 | 25.50 | 22.17 | 25.50 | 22.11 |
Annual Sum or Average | 3116.83 | 22.84 | 1745.50 | 23.26 | 121.67 | 23.19 |
Minimum of Months | 0.00 | 0.00 | 1.50 | 21.67 | 0.00 | 21.52 |
Maximum of Months | 502.00 | 23.86 | 468.67 | 24.28 | 67.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.68 | 307.67 | 20.48 | 307.67 | 20.39 |
February | 454.00 | 20.89 | 235.50 | 20.64 | 235.50 | 20.51 |
March | 464.50 | 21.86 | 129.33 | 21.68 | 111.67 | 21.49 |
April | 430.33 | 22.82 | 18.50 | 22.72 | 18.17 | 22.63 |
May | 246.17 | 23.52 | 71.33 | 23.69 | 0.00 | 23.69 |
June | 56.33 | 23.68 | 281.83 | 24.12 | 0.00 | 24.12 |
July | 1.67 | 23.72 | 462.83 | 24.28 | 0.00 | 24.28 |
August | 8.50 | 23.56 | 418.17 | 24.23 | 0.00 | 24.23 |
September | 130.50 | 23.34 | 198.00 | 23.88 | 2.83 | 23.89 |
October | 407.83 | 22.54 | 32.67 | 22.47 | 22.67 | 22.38 |
November | 486.67 | 21.87 | 69.67 | 21.68 | 69.67 | 21.53 |
December | 497.00 | 20.83 | 252.17 | 20.61 | 252.17 | 20.50 |
Annual Sum or Average | 3685.50 | 21.83 | 2477.67 | 22.13 | 1020.33 | 21.86 |
Minimum of Months | 1.67 | 20.68 | 18.50 | 20.48 | 0.00 | 20.39 |
Maximum of Months | 502.00 | 23.72 | 462.83 | 24.28 | 307.67 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.29 | 200.00 | 21.14 | 200.00 | 21.05 |
February | 454.00 | 21.58 | 120.83 | 21.41 | 120.83 | 21.30 |
March | 428.17 | 22.56 | 67.50 | 22.54 | 36.67 | 22.43 |
April | 314.00 | 23.43 | 21.00 | 23.54 | 0.00 | 23.54 |
May | 173.17 | 23.66 | 112.33 | 24.04 | 0.00 | 24.04 |
June | 14.50 | 25.28 | 344.50 | 24.44 | 7.00 | 24.48 |
July | 22.50 | 26.75 | 484.83 | 24.54 | 22.50 | 24.63 |
August | 11.83 | 26.67 | 462.50 | 24.37 | 11.33 | 24.43 |
September | 68.33 | 23.47 | 258.33 | 24.17 | 0.00 | 24.17 |
October | 325.50 | 23.32 | 40.67 | 23.45 | 0.00 | 23.45 |
November | 433.33 | 23.02 | 9.17 | 23.06 | 0.00 | 23.06 |
December | 493.50 | 21.91 | 67.50 | 21.77 | 67.50 | 21.66 |
Annual Sum or Average | 3240.83 | 22.48 | 2189.17 | 22.97 | 465.83 | 22.84 |
Minimum of Months | 11.83 | 21.29 | 9.17 | 21.14 | 0.00 | 21.05 |
Maximum of Months | 502.00 | 26.75 | 484.83 | 24.54 | 200.00 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.49 | 174.50 | 21.30 | 174.50 | 21.19 |
February | 449.33 | 21.75 | 112.83 | 21.55 | 112.83 | 21.41 |
March | 399.33 | 22.70 | 63.50 | 22.71 | 26.17 | 22.62 |
April | 257.67 | 23.27 | 77.83 | 23.60 | 2.33 | 23.62 |
May | 131.83 | 23.85 | 207.83 | 24.32 | 11.17 | 24.41 |
June | 45.17 | 25.96 | 397.33 | 24.59 | 30.33 | 24.74 |
July | 49.17 | 26.91 | 488.83 | 24.70 | 49.17 | 24.89 |
August | 33.67 | 26.19 | 456.83 | 24.46 | 27.33 | 24.58 |
September | 65.83 | 24.09 | 326.50 | 24.40 | 13.00 | 24.49 |
October | 268.33 | 23.16 | 91.83 | 23.54 | 1.00 | 23.55 |
November | 420.50 | 22.77 | 14.33 | 22.85 | 0.00 | 22.85 |
December | 496.17 | 21.67 | 103.83 | 21.51 | 103.83 | 21.40 |
Annual Sum or Average | 3119.00 | 22.53 | 2516.00 | 23.12 | 551.67 | 23.04 |
Minimum of Months | 33.67 | 21.49 | 14.33 | 21.30 | 0.00 | 21.19 |
Maximum of Months | 502.00 | 26.91 | 488.83 | 24.70 | 174.50 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 465.83 | 21.51 | 193.50 | 21.30 | 187.00 | 21.15 |
February | 414.17 | 21.77 | 136.67 | 21.53 | 131.17 | 21.36 |
March | 337.83 | 22.64 | 95.17 | 22.85 | 25.83 | 22.74 |
April | 261.33 | 23.24 | 93.50 | 23.57 | 9.17 | 23.59 |
May | 165.67 | 23.65 | 181.67 | 24.14 | 8.00 | 24.21 |
June | 48.83 | 25.01 | 373.33 | 24.47 | 19.67 | 24.57 |
July | 41.17 | 26.90 | 479.33 | 24.67 | 41.17 | 24.83 |
August | 30.50 | 26.61 | 467.50 | 24.51 | 27.17 | 24.63 |
September | 68.33 | 24.48 | 348.67 | 24.49 | 21.00 | 24.61 |
October | 234.00 | 23.18 | 144.50 | 23.71 | 7.33 | 23.78 |
November | 367.33 | 22.67 | 58.50 | 22.95 | 2.00 | 22.94 |
December | 460.50 | 21.79 | 125.83 | 21.68 | 112.67 | 21.54 |
Annual Sum or Average | 2895.50 | 22.54 | 2698.17 | 23.17 | 592.17 | 23.06 |
Minimum of Months | 30.50 | 21.51 | 58.50 | 21.30 | 2.00 | 21.15 |
Maximum of Months | 465.83 | 26.90 | 479.33 | 24.67 | 187.00 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.50 | 22.10 | 67.83 | 21.97 | 65.50 | 21.86 |
February | 425.83 | 22.83 | 23.00 | 22.78 | 18.33 | 22.71 |
March | 217.17 | 23.78 | 132.33 | 24.09 | 6.50 | 24.15 |
April | 47.67 | 25.28 | 224.00 | 25.05 | 19.33 | 25.19 |
May | 62.00 | 25.01 | 266.50 | 24.81 | 22.50 | 24.95 |
June | 41.67 | 27.04 | 456.67 | 24.78 | 41.67 | 24.96 |
July | 103.67 | 26.65 | 497.00 | 25.03 | 103.67 | 25.27 |
August | 74.67 | 26.54 | 514.00 | 24.81 | 74.67 | 25.00 |
September | 36.17 | 26.39 | 391.50 | 24.72 | 29.83 | 24.87 |
October | 89.00 | 24.04 | 200.67 | 24.50 | 5.00 | 24.54 |
November | 184.33 | 23.92 | 80.67 | 24.30 | 0.00 | 24.30 |
December | 357.50 | 23.56 | 12.83 | 23.62 | 0.00 | 23.62 |
Annual Sum or Average | 2134.17 | 23.60 | 2867.00 | 24.15 | 387.00 | 24.25 |
Minimum of Months | 36.17 | 22.10 | 12.83 | 21.97 | 0.00 | 21.86 |
Maximum of Months | 494.50 | 27.04 | 514.00 | 25.05 | 103.67 | 25.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.10 | 469.00 | 20.07 | 469.00 | 20.06 |
February | 454.00 | 20.24 | 407.17 | 20.19 | 407.17 | 20.18 |
March | 480.33 | 21.19 | 243.17 | 21.02 | 225.33 | 20.88 |
April | 450.83 | 22.26 | 37.33 | 22.12 | 36.83 | 22.00 |
May | 276.17 | 23.24 | 70.17 | 23.47 | 0.00 | 23.47 |
June | 67.50 | 23.97 | 286.50 | 24.23 | 9.33 | 24.28 |
July | 23.50 | 25.63 | 464.67 | 24.45 | 22.33 | 24.51 |
August | 36.17 | 23.73 | 400.83 | 24.22 | 4.00 | 24.24 |
September | 188.67 | 23.21 | 168.17 | 23.69 | 10.00 | 23.75 |
October | 447.50 | 22.12 | 45.00 | 22.04 | 37.33 | 21.94 |
November | 489.00 | 21.22 | 150.67 | 21.03 | 150.67 | 20.92 |
December | 497.00 | 20.23 | 419.83 | 20.16 | 419.83 | 20.13 |
Annual Sum or Average | 3912.67 | 21.39 | 3162.50 | 21.68 | 1791.83 | 21.40 |
Minimum of Months | 23.50 | 20.10 | 37.33 | 20.07 | 0.00 | 20.06 |
Maximum of Months | 502.00 | 25.63 | 469.00 | 24.45 | 469.00 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.09 | 393.33 | 20.04 | 393.33 | 20.03 |
February | 385.00 | 20.35 | 312.17 | 20.21 | 312.17 | 20.16 |
March | 391.67 | 21.68 | 141.67 | 21.48 | 122.17 | 21.29 |
April | 292.33 | 22.47 | 60.33 | 22.73 | 12.83 | 22.67 |
May | 169.00 | 23.51 | 149.17 | 24.10 | 10.50 | 24.19 |
June | 64.00 | 25.36 | 313.00 | 24.66 | 33.67 | 24.84 |
July | 63.17 | 26.71 | 411.67 | 24.90 | 63.00 | 25.11 |
August | 46.00 | 25.59 | 366.17 | 24.59 | 29.33 | 24.74 |
September | 116.17 | 23.71 | 234.17 | 24.29 | 21.00 | 24.42 |
October | 321.50 | 22.40 | 66.17 | 22.58 | 19.50 | 22.48 |
November | 406.33 | 21.43 | 110.17 | 21.21 | 110.17 | 21.07 |
December | 422.00 | 20.20 | 364.33 | 20.13 | 364.33 | 20.10 |
Annual Sum or Average | 3104.17 | 21.62 | 2922.33 | 22.07 | 1492.00 | 21.82 |
Minimum of Months | 46.00 | 20.09 | 60.33 | 20.04 | 10.50 | 20.03 |
Maximum of Months | 427.00 | 26.71 | 411.67 | 24.90 | 393.33 | 25.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 476.50 | 20.75 | 330.67 | 20.54 | 324.33 | 20.42 |
February | 422.67 | 20.87 | 260.50 | 20.62 | 255.17 | 20.49 |
March | 368.83 | 21.92 | 144.00 | 22.02 | 82.50 | 21.82 |
April | 325.17 | 22.53 | 90.33 | 22.84 | 19.83 | 22.79 |
May | 211.33 | 23.31 | 158.17 | 23.85 | 8.17 | 23.92 |
June | 86.83 | 24.24 | 333.17 | 24.33 | 22.33 | 24.44 |
July | 60.33 | 26.10 | 464.17 | 24.66 | 52.50 | 24.83 |
August | 48.33 | 25.21 | 440.50 | 24.46 | 24.50 | 24.58 |
September | 121.33 | 24.05 | 312.50 | 24.36 | 30.83 | 24.53 |
October | 287.83 | 22.65 | 138.00 | 23.16 | 23.33 | 23.16 |
November | 398.83 | 21.77 | 117.00 | 21.84 | 75.83 | 21.67 |
December | 474.83 | 20.76 | 308.67 | 20.60 | 301.83 | 20.49 |
Annual Sum or Average | 3282.83 | 21.91 | 3097.67 | 22.44 | 1221.17 | 22.22 |
Minimum of Months | 48.33 | 20.75 | 90.33 | 20.54 | 8.17 | 20.42 |
Maximum of Months | 476.50 | 26.10 | 464.17 | 24.66 | 324.33 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.35 | 417.00 | 20.25 | 417.00 | 20.22 |
February | 450.67 | 20.63 | 321.67 | 20.47 | 321.67 | 20.40 |
March | 420.50 | 21.79 | 147.33 | 21.72 | 113.00 | 21.53 |
April | 337.50 | 22.74 | 77.83 | 22.97 | 19.67 | 22.94 |
May | 189.83 | 23.75 | 188.83 | 24.18 | 19.00 | 24.32 |
June | 60.50 | 25.16 | 385.67 | 24.55 | 29.00 | 24.69 |
July | 56.17 | 26.69 | 482.00 | 24.79 | 56.17 | 24.97 |
August | 30.50 | 26.39 | 470.17 | 24.55 | 25.67 | 24.67 |
September | 120.33 | 23.97 | 282.17 | 24.30 | 25.67 | 24.45 |
October | 354.83 | 22.49 | 73.67 | 22.66 | 17.17 | 22.58 |
November | 467.67 | 21.70 | 88.00 | 21.52 | 88.00 | 21.39 |
December | 497.00 | 20.53 | 357.83 | 20.40 | 357.83 | 20.35 |
Annual Sum or Average | 3487.50 | 21.76 | 3292.17 | 22.26 | 1489.83 | 22.03 |
Minimum of Months | 30.50 | 20.35 | 73.67 | 20.25 | 17.17 | 20.22 |
Maximum of Months | 502.00 | 26.69 | 482.00 | 24.79 | 417.00 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 490.83 | 19.82 | 490.83 | 19.82 |
February | 454.00 | 19.89 | 435.33 | 19.87 | 435.33 | 19.86 |
March | 486.67 | 20.68 | 318.83 | 20.51 | 304.67 | 20.39 |
April | 467.17 | 21.65 | 114.17 | 21.35 | 114.17 | 21.15 |
May | 319.83 | 22.84 | 64.33 | 23.03 | 7.00 | 22.99 |
June | 92.00 | 23.69 | 282.67 | 24.15 | 12.83 | 24.22 |
July | 50.50 | 25.70 | 457.83 | 24.54 | 43.50 | 24.67 |
August | 64.83 | 23.69 | 377.83 | 24.19 | 10.50 | 24.24 |
September | 240.33 | 22.79 | 153.17 | 23.33 | 13.50 | 23.38 |
October | 473.83 | 21.38 | 128.50 | 21.08 | 123.17 | 20.87 |
November | 489.00 | 20.51 | 300.83 | 20.33 | 300.83 | 20.24 |
December | 497.00 | 19.85 | 470.33 | 19.81 | 470.33 | 19.80 |
Annual Sum or Average | 4137.17 | 21.02 | 3594.67 | 21.27 | 2326.67 | 21.00 |
Minimum of Months | 50.50 | 19.83 | 64.33 | 19.81 | 7.00 | 19.80 |
Maximum of Months | 502.00 | 25.70 | 490.83 | 24.54 | 490.83 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.93 | 488.00 | 19.91 | 488.00 | 19.91 |
February | 454.00 | 20.08 | 386.83 | 19.96 | 386.83 | 19.91 |
March | 469.50 | 21.15 | 237.50 | 20.90 | 213.33 | 20.69 |
April | 355.17 | 21.89 | 106.67 | 21.87 | 65.50 | 21.63 |
May | 203.67 | 23.13 | 177.83 | 23.78 | 12.67 | 23.85 |
June | 77.00 | 24.89 | 375.67 | 24.50 | 32.83 | 24.66 |
July | 69.67 | 26.61 | 483.17 | 24.79 | 68.67 | 24.99 |
August | 61.17 | 25.10 | 430.83 | 24.47 | 32.83 | 24.61 |
September | 164.50 | 23.19 | 276.17 | 23.96 | 21.00 | 24.05 |
October | 406.17 | 21.79 | 111.50 | 21.63 | 81.50 | 21.39 |
November | 489.00 | 20.79 | 261.33 | 20.54 | 261.33 | 20.42 |
December | 497.00 | 19.93 | 466.67 | 19.90 | 466.67 | 19.89 |
Annual Sum or Average | 3748.83 | 21.23 | 3802.17 | 21.67 | 2131.17 | 21.40 |
Minimum of Months | 61.17 | 19.93 | 106.67 | 19.90 | 12.67 | 19.89 |
Maximum of Months | 502.00 | 26.61 | 488.00 | 24.79 | 488.00 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 483.50 | 20.33 | 387.83 | 20.14 | 384.67 | 20.06 |
February | 430.83 | 20.36 | 319.00 | 20.11 | 315.00 | 20.00 |
March | 404.17 | 21.37 | 206.50 | 21.24 | 163.33 | 21.00 |
April | 353.00 | 21.87 | 139.00 | 21.94 | 82.33 | 21.73 |
May | 247.50 | 22.89 | 147.33 | 23.45 | 13.67 | 23.48 |
June | 106.67 | 23.88 | 327.67 | 24.24 | 24.00 | 24.36 |
July | 73.00 | 25.70 | 457.17 | 24.65 | 56.67 | 24.82 |
August | 69.33 | 24.56 | 417.83 | 24.40 | 25.67 | 24.53 |
September | 160.00 | 23.45 | 285.17 | 24.10 | 30.67 | 24.27 |
October | 336.67 | 21.89 | 155.17 | 22.12 | 66.17 | 21.90 |
November | 432.83 | 21.10 | 201.83 | 20.88 | 186.00 | 20.70 |
December | 483.83 | 20.29 | 387.83 | 20.13 | 386.33 | 20.06 |
Annual Sum or Average | 3581.33 | 21.45 | 3432.33 | 21.89 | 1734.50 | 21.62 |
Minimum of Months | 69.33 | 20.29 | 139.00 | 20.11 | 13.67 | 20.00 |
Maximum of Months | 483.83 | 25.70 | 457.17 | 24.65 | 386.33 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 453.17 | 19.97 | 453.17 | 19.95 |
February | 451.83 | 20.24 | 364.17 | 20.09 | 364.17 | 20.04 |
March | 441.17 | 21.28 | 226.33 | 21.12 | 196.33 | 20.92 |
April | 371.33 | 22.11 | 116.00 | 22.19 | 63.17 | 22.02 |
May | 228.83 | 23.29 | 171.00 | 23.84 | 19.50 | 23.99 |
June | 75.33 | 24.66 | 376.83 | 24.47 | 29.67 | 24.62 |
July | 70.00 | 26.26 | 477.17 | 24.79 | 63.67 | 24.97 |
August | 58.33 | 25.18 | 453.50 | 24.51 | 31.67 | 24.64 |
September | 171.67 | 23.42 | 255.00 | 24.02 | 27.00 | 24.17 |
October | 401.50 | 21.82 | 112.50 | 21.76 | 71.50 | 21.54 |
November | 480.67 | 21.02 | 202.33 | 20.76 | 202.33 | 20.61 |
December | 497.00 | 20.11 | 419.67 | 20.02 | 419.67 | 19.98 |
Annual Sum or Average | 3749.67 | 21.38 | 3627.67 | 21.83 | 1941.83 | 21.57 |
Minimum of Months | 58.33 | 20.04 | 112.50 | 19.97 | 19.50 | 19.95 |
Maximum of Months | 502.00 | 26.26 | 477.17 | 24.79 | 453.17 | 24.97 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 477.50 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 1.00 | 27.00 | 514.00 | 27.00 | 1.00 | 27.00 |
April | 33.67 | 27.00 | 485.00 | 27.00 | 33.67 | 27.00 |
May | 5.83 | 27.00 | 508.00 | 27.00 | 5.83 | 27.00 |
June | 66.17 | 27.00 | 496.00 | 27.00 | 66.17 | 27.00 |
July | 217.83 | 27.00 | 497.00 | 27.00 | 217.83 | 27.00 |
August | 311.00 | 27.00 | 514.00 | 27.00 | 311.00 | 27.00 |
September | 14.33 | 27.00 | 485.00 | 27.00 | 14.33 | 27.00 |
October | 5.83 | 27.00 | 502.00 | 27.00 | 5.83 | 27.00 |
November | 1.00 | 27.00 | 489.00 | 27.00 | 1.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 656.67 | 27.00 | 5918.50 | 27.00 | 656.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 311.00 | 27.00 | 514.00 | 27.00 | 311.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 112.00 | 25.54 | 123.33 | 26.30 | 0.00 | 26.30 |
February | 1.50 | 27.00 | 194.50 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 452.17 | 27.00 | 0.00 | 27.00 |
April | 2.00 | 27.00 | 485.00 | 27.00 | 2.00 | 27.00 |
May | 2.00 | 27.00 | 508.00 | 27.00 | 2.00 | 27.00 |
June | 5.50 | 27.00 | 496.00 | 27.00 | 5.50 | 27.00 |
July | 27.33 | 27.00 | 497.00 | 27.00 | 27.33 | 27.00 |
August | 48.33 | 27.00 | 514.00 | 27.00 | 48.33 | 27.00 |
September | 2.83 | 27.00 | 485.00 | 27.00 | 2.83 | 27.00 |
October | 1.17 | 27.00 | 502.00 | 27.00 | 1.17 | 27.00 |
November | 0.00 | 0.00 | 488.83 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 323.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 202.67 | 26.19 | 5069.00 | 26.97 | 89.17 | 26.97 |
Minimum of Months | 0.00 | 0.00 | 123.33 | 26.30 | 0.00 | 26.30 |
Maximum of Months | 112.00 | 27.00 | 514.00 | 27.00 | 48.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 319.33 | 25.02 | 74.00 | 25.09 | 26.67 | 24.93 |
February | 68.50 | 27.00 | 110.33 | 27.00 | 0.00 | 27.00 |
March | 11.50 | 27.00 | 350.33 | 27.00 | 0.00 | 27.00 |
April | 1.67 | 27.00 | 469.33 | 27.00 | 1.67 | 27.00 |
May | 3.83 | 27.00 | 508.00 | 27.00 | 3.83 | 27.00 |
June | 23.50 | 27.00 | 496.00 | 27.00 | 23.50 | 27.00 |
July | 66.50 | 27.00 | 497.00 | 27.00 | 66.50 | 27.00 |
August | 77.67 | 27.00 | 514.00 | 27.00 | 77.67 | 27.00 |
September | 4.67 | 27.00 | 485.00 | 27.00 | 4.67 | 27.00 |
October | 1.33 | 27.00 | 471.83 | 27.00 | 1.33 | 27.00 |
November | 0.00 | 0.00 | 402.33 | 27.00 | 0.00 | 27.00 |
December | 46.00 | 27.00 | 192.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 624.50 | 25.99 | 4570.67 | 26.86 | 205.83 | 26.84 |
Minimum of Months | 0.00 | 0.00 | 74.00 | 25.09 | 0.00 | 24.93 |
Maximum of Months | 319.33 | 27.00 | 514.00 | 27.00 | 77.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.00 | 27.00 | 502.00 | 27.00 | 12.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 467.00 | 27.00 | 508.00 | 27.00 | 467.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.05 | 497.00 | 27.05 | 497.00 | 27.05 |
August | 514.00 | 27.35 | 514.00 | 27.35 | 514.00 | 27.35 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5412.00 | 27.04 | 5943.00 | 27.04 | 5412.00 | 27.04 |
Minimum of Months | 12.00 | 27.00 | 454.00 | 27.00 | 12.00 | 27.00 |
Maximum of Months | 514.00 | 27.35 | 514.00 | 27.35 | 514.00 | 27.35 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 16.97924 | 0.65088 | 14.02113 |
February | 454.00000 | 27.00000 | 16.09621 | 0.69926 | 15.37336 |
March | 514.00000 | 27.00006 | 21.75105 | 0.83544 | 19.90164 |
April | 485.00000 | 27.00001 | 26.59909 | 0.93493 | 23.52410 |
May | 508.00000 | 27.00021 | 30.37917 | 0.20935 | 6.02766 |
June | 496.00000 | 27.00082 | 34.76709 | 0.32905 | 7.33638 |
July | 497.00000 | 27.00080 | 37.04795 | 0.40645 | 8.50633 |
August | 514.00000 | 27.00041 | 36.27537 | 0.43220 | 8.96964 |
September | 485.00000 | 27.00053 | 35.88252 | 0.26601 | 6.55248 |
October | 502.00000 | 27.00016 | 30.18484 | 0.89395 | 21.93751 |
November | 489.00000 | 27.00001 | 26.01612 | 0.87052 | 21.06755 |
December | 497.00000 | 27.00000 | 19.04346 | 0.80518 | 18.75779 |
Annual Sum or Average | 5943.00000 | 27.00025 | 27.66105 | 0.60986 | 14.30438 |
Minimum of Months | 454.00000 | 27.00000 | 16.09621 | 0.20935 | 6.02766 |
Maximum of Months | 514.00000 | 27.00082 | 37.04795 | 0.93493 | 23.52410 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.59224 | 17.31214 | 0.42571 | 9.48228 |
February | 454.00000 | 27.00000 | 16.08122 | 0.52768 | 10.95688 |
March | 514.00000 | 27.00006 | 21.74399 | 0.69053 | 15.34180 |
April | 485.00000 | 27.00001 | 26.57632 | 0.79899 | 18.59756 |
May | 508.00000 | 27.00020 | 30.38817 | 0.13770 | 5.56084 |
June | 496.00000 | 27.00079 | 34.78440 | 0.24230 | 6.33879 |
July | 497.00000 | 27.00079 | 37.06616 | 0.29977 | 6.94812 |
August | 514.00000 | 27.00023 | 36.26492 | 0.30428 | 7.02258 |
September | 485.00000 | 27.00042 | 35.99600 | 0.19046 | 5.87594 |
October | 502.00000 | 27.00016 | 30.16978 | 0.79021 | 18.29011 |
November | 489.00000 | 27.00001 | 25.97885 | 0.71066 | 15.75613 |
December | 497.00000 | 27.00000 | 19.01905 | 0.57765 | 12.13653 |
Annual Sum or Average | 5943.00000 | 26.96578 | 27.69127 | 0.47365 | 11.01125 |
Minimum of Months | 454.00000 | 26.59224 | 16.08122 | 0.13770 | 5.56084 |
Maximum of Months | 514.00000 | 27.00079 | 37.06616 | 0.79899 | 18.59756 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.64979 | 17.67598 | 0.18961 | 7.69601 |
February | 454.00000 | 27.00016 | 16.07959 | 0.46565 | 9.76167 |
March | 514.00000 | 27.00006 | 21.75096 | 0.62330 | 13.65191 |
April | 485.00000 | 27.00001 | 26.58588 | 0.74475 | 16.96189 |
May | 508.00000 | 27.00020 | 30.41289 | 0.11045 | 5.57215 |
June | 496.00000 | 27.00082 | 34.79160 | 0.24394 | 6.45921 |
July | 497.00000 | 27.00082 | 37.07223 | 0.31263 | 7.18306 |
August | 514.00000 | 27.00025 | 36.27831 | 0.30690 | 7.13528 |
September | 485.00000 | 27.00042 | 36.04663 | 0.16431 | 5.81591 |
October | 502.00000 | 27.00015 | 30.19450 | 0.72579 | 16.36318 |
November | 489.00000 | 27.00001 | 25.99613 | 0.62484 | 13.39711 |
December | 497.00000 | 27.00000 | 19.02925 | 0.50545 | 10.55534 |
Annual Sum or Average | 5943.00000 | 26.88619 | 27.73614 | 0.41716 | 10.03583 |
Minimum of Months | 454.00000 | 25.64979 | 16.07959 | 0.11045 | 5.57215 |
Maximum of Months | 514.00000 | 27.00082 | 37.07223 | 0.74475 | 16.96189 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99998 | 30.03011 | 0.98935 | 25.68115 |
February | 454.00000 | 27.00018 | 29.84629 | 1.15987 | 33.31719 |
March | 514.00000 | 27.00059 | 27.46425 | 1.30921 | 40.76752 |
April | 485.00000 | 27.00076 | 27.11632 | 1.45420 | 48.42544 |
May | 508.00000 | 27.00001 | 32.40717 | 0.46237 | 9.52934 |
June | 496.00000 | 27.00136 | 40.00431 | 0.78121 | 18.03314 |
July | 497.00000 | 27.05062 | 44.33627 | 1.05262 | 28.51787 |
August | 514.00000 | 27.34639 | 38.33654 | 1.28434 | 39.57617 |
September | 485.00000 | 27.00004 | 39.51354 | 0.58717 | 12.40280 |
October | 502.00000 | 27.00015 | 31.39159 | 1.24203 | 37.33893 |
November | 489.00000 | 27.00047 | 28.79638 | 1.35312 | 43.03766 |
December | 497.00000 | 27.00020 | 24.33564 | 1.42497 | 46.85307 |
Annual Sum or Average | 5943.00000 | 27.03450 | 32.81800 | 1.09125 | 31.94524 |
Minimum of Months | 454.00000 | 26.99998 | 24.33564 | 0.46237 | 9.52934 |
Maximum of Months | 514.00000 | 27.34639 | 44.33627 | 1.45420 | 48.42544 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.45130 | 18.99065 | 0.28361 | 7.46508 |
February | 454.00000 | 24.44240 | 16.92284 | 0.26807 | 6.76823 |
March | 514.00000 | 24.44130 | 23.92383 | 0.33672 | 7.76058 |
April | 485.00000 | 24.56599 | 27.11079 | 0.39571 | 8.76010 |
May | 508.00000 | 24.58350 | 32.31773 | -0.4195 | 9.72938 |
June | 496.00000 | 25.27733 | 48.36825 | -0.0682 | 11.22905 |
July | 497.00000 | 26.00275 | 61.89922 | 0.27391 | 15.08816 |
August | 514.00000 | 25.24382 | 53.14233 | -0.0219 | 10.86736 |
September | 485.00000 | 24.91553 | 46.10059 | -0.1892 | 8.73346 |
October | 502.00000 | 24.69606 | 32.19916 | 0.47465 | 10.43828 |
November | 489.00000 | 24.66794 | 25.74870 | 0.41692 | 9.30613 |
December | 497.00000 | 24.58225 | 19.72923 | 0.33786 | 7.86179 |
Annual Sum or Average | 5943.00000 | 24.82498 | 34.00106 | 0.17253 | 9.52185 |
Minimum of Months | 454.00000 | 24.44130 | 16.92284 | -0.4195 | 6.76823 |
Maximum of Months | 514.00000 | 26.00275 | 61.89922 | 0.47465 | 15.08816 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.89359 | 24.75175 | 0.18810 | 6.23154 |
February | 454.00000 | 24.02596 | 22.00805 | 0.20581 | 6.07752 |
March | 514.00000 | 24.22351 | 25.90663 | 0.31427 | 7.36316 |
April | 485.00000 | 24.31161 | 28.26820 | 0.37209 | 8.14003 |
May | 508.00000 | 24.26858 | 34.16542 | -0.4759 | 10.24002 |
June | 496.00000 | 24.25914 | 45.36454 | -0.3617 | 8.18498 |
July | 497.00000 | 24.29406 | 53.49122 | -0.2699 | 6.89883 |
August | 514.00000 | 24.23695 | 50.51126 | -0.3115 | 7.32780 |
September | 485.00000 | 24.32037 | 45.80636 | -0.3601 | 8.27761 |
October | 502.00000 | 24.36129 | 34.52993 | 0.41778 | 8.95290 |
November | 489.00000 | 24.37861 | 28.55977 | 0.37160 | 8.19386 |
December | 497.00000 | 24.28458 | 23.22231 | 0.29221 | 7.02988 |
Annual Sum or Average | 5943.00000 | 24.23904 | 34.81494 | 0.02969 | 7.75476 |
Minimum of Months | 454.00000 | 23.89359 | 22.00805 | -0.4759 | 6.07752 |
Maximum of Months | 514.00000 | 24.37861 | 53.49122 | 0.41778 | 10.24002 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.85340 | 26.66151 | -0.3335 | 8.69020 |
February | 454.00000 | 22.11049 | 26.15540 | -0.2696 | 7.21615 |
March | 514.00000 | 23.35817 | 29.56048 | 0.08152 | 6.06760 |
April | 485.00000 | 23.83133 | 31.26906 | 0.22615 | 6.34346 |
May | 508.00000 | 24.10209 | 35.01483 | -0.5616 | 12.05358 |
June | 496.00000 | 24.13170 | 46.56387 | -0.4473 | 9.51316 |
July | 497.00000 | 24.20904 | 55.09311 | -0.3555 | 7.89945 |
August | 514.00000 | 24.18278 | 51.90340 | -0.3864 | 8.35303 |
September | 485.00000 | 24.15403 | 46.92897 | -0.4512 | 9.69987 |
October | 502.00000 | 23.89359 | 37.02594 | 0.28049 | 6.93190 |
November | 489.00000 | 23.51748 | 32.65183 | 0.13675 | 5.86231 |
December | 497.00000 | 22.25691 | 28.79731 | -0.2136 | 6.83152 |
Annual Sum or Average | 5943.00000 | 23.47617 | 37.38644 | -0.1915 | 7.96590 |
Minimum of Months | 454.00000 | 21.85340 | 26.15540 | -0.5616 | 5.86231 |
Maximum of Months | 514.00000 | 24.20904 | 55.09311 | 0.28049 | 12.05358 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.67934 | 28.05136 | -0.6438 | 15.93287 |
February | 454.00000 | 20.88602 | 27.27087 | -0.5914 | 14.52817 |
March | 514.00000 | 22.07228 | 31.91006 | -0.2416 | 8.97356 |
April | 485.00000 | 22.95748 | 33.49356 | 0.00570 | 6.46469 |
May | 508.00000 | 23.85907 | 35.79214 | -0.6541 | 14.92664 |
June | 496.00000 | 24.09473 | 46.71974 | -0.4518 | 9.79729 |
July | 497.00000 | 24.25980 | 54.77101 | -0.3267 | 7.59348 |
August | 514.00000 | 24.17962 | 51.80536 | -0.3835 | 8.36790 |
September | 485.00000 | 23.91561 | 47.93922 | -0.5400 | 12.07393 |
October | 502.00000 | 22.81334 | 40.25930 | 0.00992 | 6.70423 |
November | 489.00000 | 21.87898 | 37.16807 | -0.2661 | 7.87843 |
December | 497.00000 | 20.83363 | 30.96221 | -0.5821 | 13.98782 |
Annual Sum or Average | 5943.00000 | 22.71650 | 38.92606 | -0.3879 | 10.58136 |
Minimum of Months | 454.00000 | 20.67934 | 27.27087 | -0.6541 | 6.46469 |
Maximum of Months | 514.00000 | 24.25980 | 54.77101 | 0.00992 | 15.93287 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.29070 | 23.77327 | -0.4691 | 10.40893 |
February | 454.00000 | 21.57800 | 23.10140 | -0.3970 | 9.21091 |
March | 514.00000 | 22.81627 | 27.09714 | -0.0493 | 7.11197 |
April | 485.00000 | 23.70382 | 28.64814 | 0.19178 | 6.43184 |
May | 508.00000 | 24.04889 | 33.86617 | -0.5659 | 12.70109 |
June | 496.00000 | 24.29532 | 44.44958 | -0.3291 | 8.13481 |
July | 497.00000 | 24.42771 | 52.38414 | -0.1911 | 6.79286 |
August | 514.00000 | 24.28230 | 49.60778 | -0.2828 | 7.44400 |
September | 485.00000 | 24.12706 | 45.55536 | -0.4477 | 10.12930 |
October | 502.00000 | 23.61149 | 35.20342 | 0.20355 | 6.62504 |
November | 489.00000 | 23.15166 | 29.88851 | 0.03956 | 5.91266 |
December | 497.00000 | 21.91985 | 24.91689 | -0.2967 | 7.86389 |
Annual Sum or Average | 5943.00000 | 23.28238 | 34.96457 | -0.2157 | 8.22976 |
Minimum of Months | 454.00000 | 21.29070 | 23.10140 | -0.5659 | 5.91266 |
Maximum of Months | 514.00000 | 24.42771 | 52.38414 | 0.20355 | 12.70109 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.49053 | 23.62452 | -0.4220 | 9.74272 |
February | 454.00000 | 21.77040 | 22.86911 | -0.3496 | 8.94641 |
March | 514.00000 | 23.00868 | 26.74479 | 0.01385 | 6.97377 |
April | 485.00000 | 23.71496 | 28.30184 | 0.23414 | 7.34070 |
May | 508.00000 | 24.16924 | 33.24678 | -0.4502 | 11.31210 |
June | 496.00000 | 24.35699 | 44.04097 | -0.2322 | 7.86412 |
July | 497.00000 | 24.47436 | 52.01909 | -0.1001 | 7.07617 |
August | 514.00000 | 24.28933 | 49.39857 | -0.2193 | 7.37912 |
September | 485.00000 | 24.25218 | 44.94639 | -0.3395 | 9.31125 |
October | 502.00000 | 23.67034 | 34.78703 | 0.23906 | 7.42855 |
November | 489.00000 | 22.99197 | 30.07378 | 0.00774 | 6.27093 |
December | 497.00000 | 21.66914 | 25.27956 | -0.3587 | 8.65470 |
Annual Sum or Average | 5943.00000 | 23.33252 | 34.70056 | -0.1641 | 8.18898 |
Minimum of Months | 454.00000 | 21.49053 | 22.86911 | -0.4502 | 6.27093 |
Maximum of Months | 514.00000 | 24.47436 | 52.01909 | 0.23906 | 11.31210 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.72032 | 23.13504 | -0.3628 | 10.47881 |
February | 454.00000 | 21.96387 | 22.29674 | -0.2973 | 9.41980 |
March | 514.00000 | 23.19254 | 26.01541 | 0.07712 | 7.74927 |
April | 485.00000 | 23.69950 | 28.24780 | 0.22884 | 7.66622 |
May | 508.00000 | 24.07237 | 33.55610 | -0.5129 | 12.54605 |
June | 496.00000 | 24.29294 | 44.35541 | -0.2988 | 8.30912 |
July | 497.00000 | 24.45969 | 52.11704 | -0.1382 | 7.01707 |
August | 514.00000 | 24.33277 | 49.22427 | -0.1980 | 7.24385 |
September | 485.00000 | 24.28471 | 44.75054 | -0.2968 | 9.09656 |
October | 502.00000 | 23.75064 | 34.26292 | 0.28846 | 8.60769 |
November | 489.00000 | 23.10686 | 29.53571 | 0.05147 | 7.11047 |
December | 497.00000 | 21.99824 | 24.78952 | -0.2774 | 8.89213 |
Annual Sum or Average | 5943.00000 | 23.41667 | 34.44829 | -0.1443 | 8.67795 |
Minimum of Months | 454.00000 | 21.72032 | 22.29674 | -0.5129 | 7.01707 |
Maximum of Months | 514.00000 | 24.45969 | 52.11704 | 0.28846 | 12.54605 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.13696 | 22.71830 | -0.2573 | 7.72160 |
February | 454.00000 | 22.92314 | 21.16459 | -0.0636 | 6.45475 |
March | 514.00000 | 24.07945 | 24.36198 | 0.30868 | 8.15347 |
April | 485.00000 | 24.49012 | 26.35664 | 0.48757 | 11.01420 |
May | 508.00000 | 24.42327 | 32.57897 | -0.3219 | 9.21029 |
June | 496.00000 | 24.52901 | 43.50986 | -0.0859 | 7.31356 |
July | 497.00000 | 24.69126 | 51.23498 | 0.06682 | 7.58839 |
August | 514.00000 | 24.55431 | 48.36794 | 0.01123 | 7.09487 |
September | 485.00000 | 24.45761 | 44.26289 | -0.2289 | 7.91215 |
October | 502.00000 | 24.30803 | 32.98208 | 0.42289 | 9.43487 |
November | 489.00000 | 24.25309 | 27.01491 | 0.33534 | 7.91947 |
December | 497.00000 | 23.79912 | 21.92161 | 0.15992 | 6.28151 |
Annual Sum or Average | 5943.00000 | 24.06071 | 33.13210 | 0.06977 | 8.01485 |
Minimum of Months | 454.00000 | 22.13696 | 21.16459 | -0.3219 | 6.28151 |
Maximum of Months | 514.00000 | 24.69126 | 51.23498 | 0.48757 | 11.01420 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10093 | 25.40863 | -0.8463 | 22.15014 |
February | 454.00000 | 20.23807 | 25.21730 | -0.7966 | 20.12663 |
March | 514.00000 | 21.37365 | 30.18510 | -0.4220 | 11.95430 |
April | 485.00000 | 22.39189 | 31.98639 | -0.1311 | 7.17828 |
May | 508.00000 | 23.65490 | 35.28515 | -0.7170 | 17.40810 |
June | 496.00000 | 24.13957 | 45.66141 | -0.4135 | 9.52852 |
July | 497.00000 | 24.36618 | 54.05332 | -0.2539 | 7.18680 |
August | 514.00000 | 24.16874 | 50.95431 | -0.3665 | 8.56351 |
September | 485.00000 | 23.72433 | 47.27939 | -0.6058 | 14.37503 |
October | 502.00000 | 22.32823 | 38.45997 | -0.1081 | 7.06372 |
November | 489.00000 | 21.22358 | 33.80498 | -0.4320 | 10.09791 |
December | 497.00000 | 20.23243 | 28.37777 | -0.7769 | 19.61040 |
Annual Sum or Average | 5943.00000 | 22.34502 | 37.30978 | -0.4873 | 12.89381 |
Minimum of Months | 454.00000 | 20.10093 | 25.21730 | -0.8463 | 7.06372 |
Maximum of Months | 514.00000 | 24.36618 | 54.05332 | -0.1081 | 22.15014 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.08802 | 24.74422 | -0.8390 | 21.84275 |
February | 385.00000 | 20.34924 | 24.47323 | -0.7551 | 19.14072 |
March | 433.00000 | 21.90013 | 28.86051 | -0.2755 | 9.74651 |
April | 410.00000 | 23.01162 | 29.97199 | 0.04850 | 7.68015 |
May | 430.00000 | 24.01324 | 33.65601 | -0.5277 | 13.96241 |
June | 418.00000 | 24.37228 | 44.55242 | -0.2540 | 8.70707 |
July | 422.00000 | 24.60495 | 52.93934 | -0.0893 | 7.60146 |
August | 433.00000 | 24.37087 | 49.85525 | -0.2265 | 7.97611 |
September | 410.00000 | 24.10652 | 45.71059 | -0.4196 | 11.63628 |
October | 427.00000 | 22.86516 | 36.57290 | 0.03040 | 7.35352 |
November | 417.00000 | 21.50350 | 32.53490 | -0.3659 | 9.59464 |
December | 422.00000 | 20.19645 | 27.70749 | -0.7851 | 19.79274 |
Annual Sum or Average | 5034.00000 | 22.62926 | 36.03762 | -0.3695 | 12.04496 |
Minimum of Months | 385.00000 | 20.08802 | 24.47323 | -0.8390 | 7.35352 |
Maximum of Months | 433.00000 | 24.60495 | 52.93934 | 0.04850 | 21.84275 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.93974 | 24.35838 | -0.5906 | 16.48001 |
February | 454.00000 | 21.08740 | 23.97449 | -0.5348 | 14.83476 |
March | 514.00000 | 22.57772 | 28.02260 | -0.0745 | 9.05536 |
April | 485.00000 | 23.10447 | 30.05410 | 0.08225 | 7.94014 |
May | 508.00000 | 23.85458 | 34.35342 | -0.5915 | 15.12052 |
June | 496.00000 | 24.17104 | 45.33972 | -0.3607 | 9.53711 |
July | 497.00000 | 24.43315 | 53.55155 | -0.1787 | 7.41159 |
August | 514.00000 | 24.28797 | 50.19813 | -0.2441 | 7.92692 |
September | 485.00000 | 24.14719 | 45.49257 | -0.3477 | 10.63698 |
October | 502.00000 | 23.33108 | 35.63131 | 0.18878 | 8.76601 |
November | 489.00000 | 22.25797 | 31.67895 | -0.1550 | 8.66003 |
December | 497.00000 | 20.93235 | 27.48565 | -0.5700 | 14.91159 |
Annual Sum or Average | 5943.00000 | 22.94151 | 35.93326 | -0.2800 | 10.91844 |
Minimum of Months | 454.00000 | 20.93235 | 23.97449 | -0.5915 | 7.41159 |
Maximum of Months | 514.00000 | 24.43315 | 53.55155 | 0.18878 | 16.48001 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.35244 | 25.09660 | -0.7573 | 19.17059 |
February | 454.00000 | 20.65076 | 24.65653 | -0.6636 | 16.36011 |
March | 514.00000 | 22.23022 | 28.63332 | -0.1848 | 9.29487 |
April | 485.00000 | 23.19039 | 30.06626 | 0.09897 | 7.82105 |
May | 508.00000 | 24.04228 | 34.08523 | -0.4989 | 13.11744 |
June | 496.00000 | 24.33896 | 44.83588 | -0.2277 | 8.37088 |
July | 497.00000 | 24.55348 | 53.13381 | -0.0822 | 7.37768 |
August | 514.00000 | 24.38289 | 49.93916 | -0.1844 | 7.59950 |
September | 485.00000 | 24.10356 | 45.90479 | -0.4050 | 10.95608 |
October | 502.00000 | 22.96920 | 36.71017 | 0.06390 | 7.22267 |
November | 489.00000 | 21.80135 | 32.67207 | -0.2833 | 8.40165 |
December | 497.00000 | 20.52827 | 27.95195 | -0.6778 | 16.22948 |
Annual Sum or Average | 5943.00000 | 22.77835 | 36.22471 | -0.3147 | 10.95815 |
Minimum of Months | 454.00000 | 20.35244 | 24.65653 | -0.7573 | 7.22267 |
Maximum of Months | 514.00000 | 24.55348 | 53.13381 | 0.09897 | 19.17059 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83462 | 26.22488 | -0.9574 | 26.91163 |
February | 454.00000 | 19.89358 | 25.94109 | -0.9245 | 25.69860 |
March | 514.00000 | 20.85136 | 31.41520 | -0.5832 | 16.48223 |
April | 485.00000 | 21.73474 | 33.33851 | -0.3048 | 9.79781 |
May | 508.00000 | 23.32514 | 36.08543 | -0.8321 | 22.28756 |
June | 496.00000 | 24.06013 | 45.95912 | -0.4333 | 10.55738 |
July | 497.00000 | 24.37360 | 54.03584 | -0.2406 | 7.44228 |
August | 514.00000 | 24.11538 | 51.06616 | -0.3801 | 9.26618 |
September | 485.00000 | 23.41658 | 48.27282 | -0.7136 | 18.66004 |
October | 502.00000 | 21.52201 | 40.46153 | -0.3198 | 10.35601 |
November | 489.00000 | 20.50716 | 35.87518 | -0.6470 | 15.93804 |
December | 497.00000 | 19.84513 | 29.54552 | -0.9201 | 25.67276 |
Annual Sum or Average | 5943.00000 | 21.97404 | 38.27036 | -0.6025 | 16.52746 |
Minimum of Months | 454.00000 | 19.83462 | 25.94109 | -0.9574 | 7.44228 |
Maximum of Months | 514.00000 | 24.37360 | 54.03584 | -0.2406 | 26.91163 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.93010 | 26.14908 | -0.9125 | 25.13351 |
February | 454.00000 | 20.07671 | 25.80411 | -0.8517 | 23.42323 |
March | 514.00000 | 21.39812 | 30.64575 | -0.4173 | 13.35888 |
April | 485.00000 | 22.52130 | 31.44133 | -0.0768 | 9.14395 |
May | 508.00000 | 23.80099 | 34.40775 | -0.5894 | 16.06944 |
June | 496.00000 | 24.26899 | 44.88905 | -0.2624 | 8.89928 |
July | 497.00000 | 24.50741 | 53.12533 | -0.0870 | 7.50382 |
August | 514.00000 | 24.27244 | 50.14268 | -0.2311 | 8.14187 |
September | 485.00000 | 23.87079 | 46.43657 | -0.4882 | 13.66402 |
October | 502.00000 | 22.22657 | 38.75518 | -0.1354 | 9.14566 |
November | 489.00000 | 20.79219 | 35.36819 | -0.5687 | 14.33708 |
December | 497.00000 | 19.93490 | 29.45073 | -0.8892 | 24.34201 |
Annual Sum or Average | 5943.00000 | 22.31799 | 37.29976 | -0.4565 | 14.36498 |
Minimum of Months | 454.00000 | 19.93010 | 25.80411 | -0.9125 | 7.50382 |
Maximum of Months | 514.00000 | 24.50741 | 53.12533 | -0.0768 | 25.13351 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.48023 | 25.44324 | -0.7394 | 21.17305 |
February | 454.00000 | 20.54286 | 25.00787 | -0.7003 | 20.61529 |
March | 514.00000 | 21.95574 | 29.45319 | -0.2540 | 11.84858 |
April | 485.00000 | 22.51546 | 31.35834 | -0.0770 | 9.46214 |
May | 508.00000 | 23.57234 | 35.06867 | -0.6931 | 19.28860 |
June | 496.00000 | 24.08048 | 45.69003 | -0.3837 | 10.74672 |
July | 497.00000 | 24.41016 | 53.64443 | -0.1741 | 7.80516 |
August | 514.00000 | 24.23120 | 50.34138 | -0.2587 | 8.60382 |
September | 485.00000 | 23.92208 | 46.22022 | -0.4325 | 13.39063 |
October | 502.00000 | 22.65391 | 37.38155 | 0.00384 | 9.78424 |
November | 489.00000 | 21.44220 | 33.94366 | -0.3866 | 12.26676 |
December | 497.00000 | 20.39086 | 28.86782 | -0.7438 | 20.47167 |
Annual Sum or Average | 5943.00000 | 22.53274 | 36.95369 | -0.4014 | 13.74340 |
Minimum of Months | 454.00000 | 20.39086 | 25.00787 | -0.7438 | 7.80516 |
Maximum of Months | 514.00000 | 24.41016 | 53.64443 | 0.00384 | 21.17305 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.03839 | 25.97308 | -0.8747 | 23.82605 |
February | 454.00000 | 20.26055 | 25.44869 | -0.7894 | 21.32468 |
March | 514.00000 | 21.69109 | 29.90860 | -0.3381 | 12.17346 |
April | 485.00000 | 22.60510 | 31.31442 | -0.0527 | 9.10631 |
May | 508.00000 | 23.77787 | 34.77510 | -0.5923 | 16.74319 |
June | 496.00000 | 24.26331 | 45.14131 | -0.2466 | 9.26274 |
July | 497.00000 | 24.53751 | 53.20522 | -0.0767 | 7.67751 |
August | 514.00000 | 24.33896 | 50.05266 | -0.1956 | 8.07634 |
September | 485.00000 | 23.86894 | 46.69245 | -0.4894 | 13.82571 |
October | 502.00000 | 22.27327 | 38.44726 | -0.1161 | 8.91119 |
November | 489.00000 | 21.07193 | 34.71908 | -0.4855 | 12.37112 |
December | 497.00000 | 20.11325 | 29.15237 | -0.8146 | 21.57255 |
Annual Sum or Average | 5943.00000 | 22.42091 | 37.15149 | -0.4201 | 13.68543 |
Minimum of Months | 454.00000 | 20.03839 | 25.44869 | -0.8747 | 7.67751 |
Maximum of Months | 514.00000 | 24.53751 | 53.20522 | -0.0527 | 23.82605 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 15822492.88 | 556.34 | 11-JAN-17:00 | 11.41 | 0.154238E+09 | 0.00 | 0.170061E+09 | 0.15 | 9.81 | 11-JAN-07:30 | 0.00 | 0.00 |
February | 21649813.97 | 925.96 | 28-FEB-15:20 | 12.59 | 0.211140E+09 | 0.00 | 0.232790E+09 | 0.18 | 9.84 | 28-FEB-15:30 | 0.00 | 0.00 |
March | 0.678216E+10 | 164965.46 | 15-MAR-13:50 | 119.04 | 0.579465E+11 | 0.00 | 0.647287E+11 | 1.54 | 10.00 | 14-MAR-10:30 | 0.00 | 0.00 |
April | 0.489280E+10 | 56380.69 | 07-APR-13:20 | 154.09 | 0.478396E+11 | 0.00 | 0.527324E+11 | 2.09 | 10.00 | 26-APR-13:20 | 0.00 | 0.00 |
May | 0.214620E+11 | 170936.23 | 10-MAY-14:20 | 275.38 | 0.201522E+12 | 0.00 | 0.222984E+12 | 3.58 | 10.01 | 24-MAY-05:02 | 0.00 | 0.00 |
June | 0.769591E+11 | 180789.05 | 20-JUN-10:40 | 451.87 | 0.674154E+12 | 0.00 | 0.751113E+12 | 5.85 | 10.02 | 02-JUN-04:11 | 0.00 | 0.00 |
July | 0.126734E+12 | 194247.04 | 05-JUL-16:00 | 607.13 | 0.106026E+13 | 0.00 | 0.118699E+13 | 7.35 | 10.00 | 24-JUL-05:02 | 0.00 | 0.00 |
August | 0.110588E+12 | 186540.30 | 14-AUG-05:03 | 588.52 | 0.938787E+12 | 0.00 | 0.104937E+13 | 7.25 | 10.00 | 29-AUG-11:40 | 0.00 | 0.00 |
September | 0.512166E+11 | 176371.78 | 08-SEP-12:50 | 356.23 | 0.456119E+12 | 0.00 | 0.507335E+12 | 4.67 | 10.00 | 09-SEP-12:20 | 0.00 | 0.00 |
October | 0.941030E+10 | 90038.90 | 11-OCT-15:10 | 176.32 | 0.910470E+11 | 0.00 | 0.100457E+12 | 2.31 | 10.00 | 25-OCT-14:40 | 0.00 | 0.00 |
November | 0.161677E+10 | 28759.36 | 16-NOV-13:10 | 115.01 | 0.157433E+11 | 0.00 | 0.173601E+11 | 1.56 | 9.83 | 09-NOV-15:10 | 0.00 | 0.00 |
December | 66253296.28 | 3242.18 | 01-DEC-07:13 | 22.34 | 0.646185E+09 | 0.00 | 0.712438E+09 | 0.29 | 9.84 | 05-DEC-10:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.409765E+12 | 2889.93 | 0.354443E+13 | 0.00 | 0.395420E+13 | 3.09 | 0.00 | 0.00 | ||||
Minimum of Months | 15822492.88 | 556.34 | 11.41 | 0.154238E+09 | 0.00 | 0.170061E+09 | 0.15 | 9.81 | 0.00 | 0.00 | ||
Maximum of Months | 0.126734E+12 | 194247.04 | 607.13 | 0.106026E+13 | 0.00 | 0.118699E+13 | 7.35 | 10.02 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.119923E+09 | 68297.22 | 10-MAY-15:50 | 0.50 | 0.110187E+10 | 0.00 | 0.122180E+10 | 0.01 | 9.29 | 10-MAY-14:40 | 0.00 | 0.00 |
June | 0.149396E+11 | 142497.10 | 27-JUN-07:40 | 55.25 | 0.131029E+12 | 0.00 | 0.145969E+12 | 0.68 | 10.34 | 01-JUN-14:40 | 0.00 | 0.00 |
July | 0.386783E+11 | 194247.04 | 05-JUL-16:00 | 128.79 | 0.324142E+12 | 0.00 | 0.362821E+12 | 1.48 | 10.60 | 28-JUL-05:05 | 0.00 | 0.00 |
August | 0.263730E+11 | 186540.30 | 14-AUG-05:03 | 90.07 | 0.223635E+12 | 0.00 | 0.250008E+12 | 1.05 | 10.51 | 01-AUG-14:30 | 0.00 | 0.00 |
September | 0.680780E+10 | 124767.59 | 15-SEP-11:00 | 24.83 | 0.597373E+11 | 0.00 | 0.665451E+11 | 0.30 | 9.39 | 21-SEP-14:05 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.869187E+11 | 299.45 | 0.739646E+12 | 0.00 | 0.826564E+12 | 0.30 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.386783E+11 | 194247.04 | 128.79 | 0.324142E+12 | 0.00 | 0.362821E+12 | 1.48 | 10.60 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.325044E+09 | 744.00 | 862.12 | 17-JAN-16:30 | 27699.98 | 15-JAN-16:40 | 18.52 | 18.33 | 15.81 |
February | 0.101609E+10 | 672.00 | 1927.32 | 22-FEB-18:00 | 68995.49 | 28-FEB-09:58 | 19.04 | 18.33 | 15.82 |
March | 0.815199E+10 | 744.00 | 43776.24 | 12-MAR-13:00 | 483511.92 | 14-MAR-13:10 | 20.14 | 18.56 | 15.78 |
April | 0.103554E+11 | 720.00 | 43776.24 | 07-APR-10:20 | 404603.31 | 08-APR-13:50 | 20.62 | 18.39 | 15.75 |
May | 0.230128E+11 | 744.00 | 43776.24 | 09-MAY-11:50 | 197178.26 | 10-MAY-15:00 | 19.34 | 18.73 | 15.80 |
June | 0.696794E+11 | 720.00 | 43776.24 | 01-JUN-09:50 | 606191.31 | 27-JUN-14:20 | 23.75 | 21.19 | 15.82 |
July | 0.104737E+12 | 744.00 | 43776.24 | 01-JUL-07:00 | 782150.72 | 21-JUL-03:02 | 32.63 | 25.06 | 15.83 |
August | 0.101221E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 800514.90 | 13-AUG-16:01 | 33.39 | 24.42 | 15.83 |
September | 0.476858E+11 | 720.00 | 43776.24 | 01-SEP-13:00 | 256680.10 | 15-SEP-12:05 | 20.23 | 19.53 | 15.82 |
October | 0.110023E+11 | 744.00 | 43776.24 | 03-OCT-13:05 | 173876.82 | 11-OCT-15:00 | 19.43 | 18.43 | 15.77 |
November | 0.753179E+10 | 720.00 | 43776.24 | 04-NOV-13:50 | 210730.80 | 05-NOV-14:00 | 19.81 | 18.36 | 15.80 |
December | 0.283393E+10 | 744.00 | 6231.75 | 01-DEC-11:00 | 180046.63 | 01-DEC-11:00 | 20.05 | 18.33 | 15.83 |
Annual Sum or Average | 0.387552E+12 | 8760.00 | 22.29 | 19.82 | 15.80 | ||||
Minimum of Months | 0.325044E+09 | 672.00 | 862.12 | 27699.98 | 18.52 | 18.33 | 15.75 | ||
Maximum of Months | 0.104737E+12 | 744.00 | 43776.24 | 800514.90 | 33.39 | 25.06 | 15.83 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 210446.51 | 07-JAN-12:00 | 20.91 | 20.91 | 0.09 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 210323.57 | 28-FEB-15:10 | 20.96 | 20.96 | 0.07 |
March | 0.612852E+09 | 28.65 | 15863.70 | 14-MAR-11:00 | 1262935.06 | 15-MAR-13:40 | 21.14 | 21.03 | 3.69 |
April | 25437949.16 | 37.29 | 913.31 | 08-APR-13:20 | 602821.05 | 07-APR-13:20 | 21.06 | 20.97 | 6.37 |
May | 0.741318E+09 | 160.01 | 15863.70 | 10-MAY-12:05 | 1255313.75 | 23-MAY-14:40 | 21.44 | 21.08 | 18.05 |
June | 0.103044E+11 | 390.67 | 15863.70 | 01-JUN-13:00 | 1244301.34 | 30-JUN-14:10 | 22.88 | 21.70 | 35.14 |
July | 0.219435E+11 | 541.55 | 15863.70 | 01-JUL-13:50 | 1383796.92 | 05-JUL-16:00 | 24.31 | 22.50 | 45.11 |
August | 0.164516E+11 | 486.81 | 15863.70 | 01-AUG-12:00 | 1291457.64 | 03-AUG-12:40 | 23.49 | 21.88 | 42.80 |
September | 0.610330E+10 | 285.51 | 15863.70 | 08-SEP-10:40 | 1279379.01 | 20-SEP-15:30 | 22.36 | 21.55 | 27.30 |
October | 0.167979E+09 | 82.71 | 3529.07 | 11-OCT-15:00 | 884502.53 | 11-OCT-15:10 | 21.32 | 21.16 | 9.80 |
November | 13614769.05 | 16.04 | 549.42 | 16-NOV-13:10 | 317189.22 | 16-NOV-13:10 | 20.98 | 20.94 | 3.29 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 210376.12 | 04-DEC-11:00 | 20.89 | 20.89 | 0.25 |
Annual Sum or Average | 0.563640E+11 | 2029.25 | 21.82 | 21.30 | 16.10 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 210323.57 | 20.89 | 20.89 | 0.07 | ||
Maximum of Months | 0.219435E+11 | 541.55 | 15863.70 | 1383796.92 | 24.31 | 22.50 | 45.11 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 20.91 | 20.91 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 20.96 | 20.96 | 0.00 |
March | 28554657.81 | 0.50 | 15863.70 | 14-MAR-13:00 | 777873.57 | 14-MAR-13:20 | 21.14 | 21.13 | 0.02 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.06 | 21.06 | 0.00 |
May | 42831986.71 | 0.75 | 15863.70 | 10-MAY-13:40 | 808661.32 | 10-MAY-14:30 | 21.44 | 21.43 | 0.05 |
June | 0.371595E+10 | 65.60 | 15863.70 | 01-JUN-14:50 | 1131549.23 | 27-JUN-07:40 | 22.88 | 22.57 | 4.92 |
July | 0.988918E+10 | 173.16 | 15863.70 | 03-JUL-12:05 | 1383796.92 | 05-JUL-16:00 | 24.31 | 23.47 | 12.06 |
August | 0.561954E+10 | 98.98 | 15863.70 | 01-AUG-14:30 | 1237484.56 | 14-AUG-11:00 | 23.49 | 23.01 | 7.23 |
September | 0.158954E+10 | 27.83 | 15863.70 | 08-SEP-13:00 | 1057944.06 | 15-SEP-11:00 | 22.36 | 22.23 | 2.17 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.32 | 21.32 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.98 | 20.98 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.89 | 20.89 | 0.00 |
Annual Sum or Average | 0.208856E+11 | 366.83 | 21.82 | 21.67 | 2.23 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 20.89 | 0.00 | ||
Maximum of Months | 0.988918E+10 | 173.16 | 15863.70 | 1383796.92 | 24.31 | 23.47 | 12.06 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.290810E+12 | 0.00 | 540.25 | 2065285.24 | 02-JAN-04:01 | 0.00 | 35.52 | 53.11 | 1.34 | 0.00 | 0.05 | 0.88 | 02-JAN-04:01 |
February | 0.224840E+12 | 0.00 | 487.11 | 1715396.62 | 18-FEB-05:01 | 0.00 | 34.03 | 52.52 | 1.15 | 0.00 | 0.04 | 0.73 | 18-FEB-05:01 |
March | 0.697679E+11 | 0.00 | 376.03 | 1595914.08 | 28-MAR-04:01 | 0.00 | 30.67 | 44.58 | 0.29 | 0.00 | 0.01 | 0.68 | 28-MAR-04:01 |
April | 0.112304E+11 | 0.00 | 207.21 | 1321222.18 | 05-APR-05:02 | 0.00 | 31.09 | 39.27 | 0.04 | 0.00 | 0.00 | 0.56 | 05-APR-05:02 |
May | 0.131832E+10 | 0.00 | 41.10 | 283435.71 | 11-MAY-13:20 | 0.00 | 33.90 | 35.36 | 0.00 | 0.00 | 0.00 | 0.12 | 11-MAY-13:20 |
June | 0.181362E+09 | 0.00 | 4.46 | 260352.85 | 13-JUN-11:05 | 0.00 | 34.93 | 35.09 | 0.00 | 0.00 | 0.00 | 0.11 | 13-JUN-11:05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 35.18 | 35.18 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 35.18 | 35.18 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.189293E+09 | 0.00 | 15.99 | 76504.00 | 30-SEP-05:03 | 0.00 | 34.51 | 35.09 | 0.00 | 0.00 | 0.00 | 0.03 | 30-SEP-05:03 |
October | 0.990823E+10 | 0.00 | 187.76 | 1375465.11 | 17-OCT-05:02 | 0.00 | 31.85 | 38.93 | 0.04 | 0.00 | 0.00 | 0.59 | 17-OCT-05:02 |
November | 0.406245E+11 | 0.00 | 347.14 | 1798803.60 | 18-NOV-05:01 | 0.00 | 29.66 | 43.61 | 0.15 | 0.00 | 0.01 | 0.77 | 18-NOV-05:01 |
December | 0.222172E+12 | 0.00 | 513.70 | 1787167.44 | 02-DEC-05:11 | 0.00 | 34.17 | 51.46 | 1.00 | 0.00 | 0.04 | 0.76 | 02-DEC-05:11 |
Annual Sum or Average | 0.871042E+12 | 0.00 | 2720.75 | 0.00 | 33.39 | 41.56 | 0.33 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.66 | 35.09 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.290810E+12 | 0.00 | 540.25 | 2065285.24 | 0.00 | 35.52 | 53.11 | 1.34 | 0.00 | 0.05 | 0.88 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 18.52 | 18.52 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 19.04 | 19.04 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.14 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 20.62 | 20.62 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 19.34 | 19.34 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 23.75 | 23.75 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 32.63 | 32.63 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 33.39 | 33.39 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 20.23 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.43 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.81 | 19.81 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.05 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 | 22.29 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 | 18.52 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 33.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3459758.71 | 0.00 | 4.96 | 3459758.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3330.18 | 17-JAN-17:05 | 3330.18 | 17-JAN-17:05 | 0.00 | 0.00 | 0.00 |
February | 24985500.29 | 0.00 | 7.86 | 24985500.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3700.45 | 22-FEB-13:20 | 3700.45 | 22-FEB-13:20 | 0.00 | 0.00 | 0.00 |
March | 0.770629E+10 | 0.00 | 100.68 | 0.753467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 101035.55 | 14-MAR-13:05 | 94782.86 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 |
April | 0.446168E+10 | 0.00 | 95.18 | 0.446168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49312.62 | 07-APR-14:00 | 49312.62 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.174544E+11 | 0.00 | 220.67 | 0.172592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95321.44 | 24-MAY-05:02 | 84594.48 | 23-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.808469E+11 | 0.00 | 433.71 | 0.643671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 242811.38 | 27-JUN-07:50 | 120002.82 | 27-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.149173E+12 | 0.00 | 579.53 | 0.107748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 294539.05 | 21-JUL-05:02 | 149873.93 | 21-JUL-04:23 | 0.00 | 0.00 | 0.00 |
August | 0.124921E+12 | 0.00 | 567.28 | 0.978560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 266881.67 | 15-AUG-08:20 | 131562.77 | 16-AUG-12:47 | 0.00 | 0.00 | 0.00 |
September | 0.479276E+11 | 0.00 | 323.95 | 0.382648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 196816.25 | 14-SEP-04:12 | 100171.99 | 21-SEP-15:40 | 0.00 | 0.00 | 0.00 |
October | 0.948484E+10 | 0.00 | 139.15 | 0.948157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75286.49 | 11-OCT-14:50 | 75286.49 | 11-OCT-14:50 | 0.00 | 0.00 | 0.00 |
November | 0.423613E+10 | 0.00 | 101.87 | 0.423613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51327.85 | 27-NOV-06:03 | 51327.85 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.122076E+09 | 0.00 | 14.89 | 0.122076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10162.44 | 04-DEC-14:50 | 10162.44 | 04-DEC-14:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.446362E+12 | 0.00 | 2589.71 | 0.351360E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3459758.71 | 0.00 | 4.96 | 3459758.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3330.18 | 3330.18 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.149173E+12 | 0.00 | 579.53 | 0.107748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 294539.05 | 149873.93 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 5686099.32 | 0.00 | 7.03 | 5686099.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3500.23 | 11-JAN-15:10 | 3500.23 | 11-JAN-15:10 | 0.00 | 0.00 | 0.00 |
February | 38586832.67 | 0.00 | 4.81 | 38586832.67 | 0.00 | 0.00 | 0.00 | 0.00 | 9211.79 | 28-FEB-15:10 | 9211.79 | 28-FEB-15:10 | 0.00 | 0.00 | 0.00 |
March | 0.385120E+11 | 0.00 | 85.31 | 0.374167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 734603.47 | 15-MAR-14:05 | 734603.47 | 15-MAR-14:05 | 0.00 | 0.00 | 0.00 |
April | 0.381293E+11 | 0.00 | 114.74 | 0.381293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 463771.77 | 07-APR-13:10 | 463771.77 | 07-APR-13:10 | 0.00 | 0.00 | 0.00 |
May | 0.155614E+12 | 0.00 | 229.46 | 0.154128E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 850911.71 | 24-MAY-05:02 | 770427.80 | 23-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.610348E+12 | 0.00 | 399.58 | 0.497592E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1632493.60 | 27-JUN-05:03 | 1021903.39 | 12-JUN-04:12 | 0.00 | 0.00 | 0.00 |
July | 0.102918E+13 | 0.00 | 456.95 | 0.770181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2250860.42 | 20-JUL-05:03 | 1323978.96 | 21-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.856364E+12 | 0.00 | 440.05 | 0.698812E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2396710.64 | 14-AUG-05:03 | 1046709.56 | 09-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.388309E+12 | 0.00 | 318.88 | 0.318492E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1538580.56 | 16-SEP-05:02 | 919310.10 | 21-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.703791E+11 | 0.00 | 140.59 | 0.703545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 605441.38 | 11-OCT-15:00 | 605441.38 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.877950E+10 | 0.00 | 76.46 | 0.877950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 231840.88 | 16-NOV-13:05 | 231840.88 | 16-NOV-13:05 | 0.00 | 0.00 | 0.00 |
December | 31698071.39 | 0.00 | 9.54 | 31698071.39 | 0.00 | 0.00 | 0.00 | 0.00 | 7967.15 | 04-DEC-11:10 | 7967.15 | 04-DEC-11:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319569E+13 | 0.00 | 2283.40 | 0.259396E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5686099.32 | 0.00 | 4.81 | 5686099.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3500.23 | 3500.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.102918E+13 | 0.00 | 456.95 | 0.770181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2396710.64 | 1323978.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 861254.08 | 0.00 | 6.35 | 861254.08 | 0.00 | 0.00 | 0.00 | 0.00 | 188.21 | 02-JAN-07:03 | 188.21 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 |
February | 3543274.83 | 0.00 | 4.78 | 3543274.83 | 0.00 | 0.00 | 0.00 | 0.00 | 847.35 | 28-FEB-15:00 | 847.35 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.375378E+10 | 0.00 | 91.07 | 0.375268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87230.94 | 15-MAR-14:20 | 87230.94 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 |
April | 0.140052E+10 | 0.00 | 92.94 | 0.140052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32239.37 | 07-APR-14:00 | 32239.37 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.147617E+11 | 0.00 | 216.25 | 0.146546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100154.93 | 14-MAY-15:02 | 88335.60 | 10-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.665018E+11 | 0.00 | 394.64 | 0.540228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167083.73 | 27-JUN-05:03 | 123223.21 | 12-JUN-14:00 | 0.00 | 0.00 | 0.00 |
July | 0.114689E+12 | 0.00 | 457.41 | 0.859911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 234515.75 | 21-JUL-05:02 | 146919.49 | 21-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.932509E+11 | 0.00 | 434.21 | 0.756916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 254014.00 | 14-AUG-05:03 | 126761.90 | 09-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.375945E+11 | 0.00 | 309.87 | 0.306849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158358.88 | 15-SEP-13:10 | 107177.76 | 21-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.418650E+10 | 0.00 | 125.30 | 0.418650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57124.43 | 11-OCT-15:00 | 57124.43 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.487509E+09 | 0.00 | 78.50 | 0.487509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11950.20 | 16-NOV-13:00 | 11950.20 | 16-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 3624892.55 | 0.00 | 10.18 | 3624892.55 | 0.00 | 0.00 | 0.00 | 0.00 | 817.35 | 01-DEC-13:30 | 817.35 | 01-DEC-13:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.336634E+12 | 0.00 | 2221.50 | 0.270880E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 861254.08 | 0.00 | 4.78 | 861254.08 | 0.00 | 0.00 | 0.00 | 0.00 | 188.21 | 188.21 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.114689E+12 | 0.00 | 457.41 | 0.859911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 254014.00 | 146919.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 34993610.45 | 0.00 | 4.00 | 34993610.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4590.06 | 11-JAN-16:00 | 4590.06 | 11-JAN-16:00 | 0.00 | 0.00 | 0.00 |
February | 33976704.27 | 0.00 | 3.83 | 33976704.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5443.34 | 22-FEB-17:00 | 5443.34 | 22-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.355343E+10 | 0.00 | 41.39 | 0.354066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51107.62 | 15-MAR-14:00 | 51107.62 | 15-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.207960E+10 | 0.00 | 57.83 | 0.207960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24487.29 | 07-APR-13:10 | 24487.29 | 07-APR-13:10 | 0.00 | 0.00 | 0.00 |
May | 0.111671E+11 | 0.00 | 191.95 | 0.106360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82419.11 | 24-MAY-06:11 | 53813.94 | 17-MAY-09:51 | 0.00 | 0.00 | 0.00 |
June | 0.282952E+11 | 0.00 | 227.06 | 0.221672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119870.10 | 28-JUN-14:10 | 78379.93 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 |
July | 0.514019E+11 | 0.00 | 220.27 | 0.376552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159991.83 | 29-JUL-10:50 | 82499.98 | 24-JUL-11:05 | 0.00 | 0.00 | 0.00 |
August | 0.549081E+11 | 0.00 | 297.98 | 0.454428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131302.27 | 28-AUG-12:05 | 85539.34 | 08-AUG-13:05 | 0.00 | 0.00 | 0.00 |
September | 0.308164E+11 | 0.00 | 241.34 | 0.243200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128392.48 | 14-SEP-16:00 | 64941.49 | 25-SEP-12:05 | 0.00 | 0.00 | 0.00 |
October | 0.506104E+10 | 0.00 | 89.55 | 0.471990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70290.68 | 26-OCT-06:25 | 46420.56 | 11-OCT-13:10 | 0.00 | 0.00 | 0.00 |
November | 0.819778E+09 | 0.00 | 24.82 | 0.816644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53081.31 | 27-NOV-07:11 | 53081.31 | 27-NOV-07:11 | 0.00 | 0.00 | 0.00 |
December | 0.238701E+09 | 0.00 | 6.25 | 0.213400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18460.68 | 01-DEC-11:00 | 15688.76 | 01-DEC-07:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188410E+12 | 0.00 | 1406.28 | 0.151660E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 33976704.27 | 0.00 | 3.83 | 33976704.27 | 0.00 | 0.00 | 0.00 | 0.00 | 4590.06 | 4590.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.549081E+11 | 0.00 | 297.98 | 0.454428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159991.83 | 85539.34 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.654828E+10 | 0.386492E+10 | 739.92 | 0.654823E+10 | 44611.38 | 0.00 | 0.02 | 13-JAN-18:00 | 0.01 | 11-JAN-18:10 | 3805.06 | 13-JAN-18:00 | 3805.06 | 13-JAN-18:00 | 17.90 | 11-JAN-18:30 | 2050.76 | 17-JAN-10:00 | 0.00 |
February | 0.102627E+11 | 0.456812E+10 | 672.00 | 0.102524E+11 | 10249251.34 | 0.00 | 0.02 | 22-FEB-18:00 | 0.01 | 01-FEB-05:11 | 5068.22 | 14-FEB-17:15 | 5068.22 | 14-FEB-17:15 | 87.54 | 01-FEB-08:00 | 2563.47 | 28-FEB-10:30 | 0.00 |
March | 0.313903E+11 | 0.102245E+11 | 680.34 | 0.283318E+11 | 0.305849E+10 | 0.00 | 0.70 | 14-MAR-13:00 | 0.01 | 11-MAR-01:10 | 313113.40 | 14-MAR-13:00 | 287943.34 | 15-MAR-14:00 | 86196.34 | 14-MAR-11:00 | 78666.23 | 14-MAR-13:00 | 0.00 |
April | 0.364191E+11 | 0.113777E+11 | 689.71 | 0.339197E+11 | 0.249942E+10 | 0.00 | 0.58 | 08-APR-13:00 | 0.01 | 09-APR-08:25 | 234035.32 | 08-APR-14:00 | 228100.62 | 08-APR-13:00 | 33742.80 | 08-APR-17:55 | 58613.66 | 08-APR-13:00 | 0.00 |
May | 0.719024E+10 | 0.426762E+10 | 532.28 | 0.673881E+10 | 0.451431E+09 | 0.00 | 0.30 | 10-MAY-15:00 | 0.01 | 13-MAY-22:50 | 123948.14 | 10-MAY-15:00 | 104640.78 | 10-MAY-15:00 | 19426.40 | 14-MAY-13:53 | 33204.23 | 10-MAY-15:00 | 0.00 |
June | 0.166435E+12 | 0.431295E+11 | 548.80 | 0.118295E+12 | 0.481392E+11 | 0.00 | 0.84 | 27-JUN-14:05 | 0.01 | 25-JUN-06:50 | 430611.59 | 27-JUN-14:05 | 226023.97 | 27-JUN-13:00 | 221901.54 | 27-JUN-15:00 | 100730.26 | 27-JUN-14:10 | 0.00 |
July | 0.710033E+12 | 0.168127E+12 | 694.46 | 0.441563E+12 | 0.268470E+12 | 0.00 | 1.00 | 08-JUL-13:50 | 0.01 | 12-JUL-06:23 | 543491.57 | 20-JUL-22:13 | 332985.93 | 15-JUL-13:25 | 354914.11 | 20-JUL-22:00 | 128315.31 | 21-JUL-02:50 | 0.00 |
August | 0.825398E+12 | 0.194220E+12 | 708.95 | 0.554051E+12 | 0.271346E+12 | 0.00 | 1.00 | 06-AUG-17:42 | 0.01 | 31-AUG-04:40 | 527231.79 | 14-AUG-02:53 | 427853.60 | 10-AUG-12:53 | 326435.72 | 25-AUG-19:00 | 130835.25 | 13-AUG-15:00 | 0.00 |
September | 0.149250E+11 | 0.654727E+10 | 365.21 | 0.111504E+11 | 0.377456E+10 | 0.00 | 0.39 | 16-SEP-14:30 | 0.01 | 02-SEP-22:40 | 176437.68 | 15-SEP-12:00 | 130985.81 | 16-SEP-13:00 | 70890.75 | 15-SEP-12:00 | 44279.32 | 16-SEP-14:30 | 0.00 |
October | 0.852388E+10 | 0.450848E+10 | 581.42 | 0.820364E+10 | 0.320237E+09 | 0.00 | 0.23 | 11-OCT-15:00 | 0.00 | 10-OCT-23:50 | 87652.77 | 11-OCT-15:00 | 81374.83 | 11-OCT-14:00 | 9119.00 | 22-OCT-12:53 | 23153.63 | 11-OCT-15:00 | 0.00 |
November | 0.172473E+11 | 0.649038E+10 | 700.79 | 0.159245E+11 | 0.132278E+10 | 0.00 | 0.27 | 05-NOV-14:00 | 0.01 | 04-NOV-12:20 | 104937.91 | 05-NOV-13:55 | 85937.80 | 05-NOV-13:55 | 19900.42 | 05-NOV-14:25 | 25544.14 | 05-NOV-14:00 | 0.00 |
December | 0.150327E+11 | 0.634028E+10 | 742.31 | 0.146498E+11 | 0.382967E+09 | 0.00 | 0.18 | 01-DEC-11:00 | 0.01 | 01-DEC-08:25 | 67245.55 | 01-DEC-11:00 | 45080.49 | 01-DEC-11:00 | 22165.06 | 01-DEC-11:00 | 16155.42 | 01-DEC-11:00 | 0.00 |
Annual Sum or Average | 0.184940E+13 | 0.463665E+12 | 7656.18 | 0.124963E+13 | 0.599775E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.654828E+10 | 0.386492E+10 | 365.21 | 0.654823E+10 | 44611.38 | 0.00 | 0.02 | 0.00 | 3805.06 | 3805.06 | 17.90 | 2050.76 | 0.00 | ||||||
Maximum of Months | 0.825398E+12 | 0.194220E+12 | 742.31 | 0.554051E+12 | 0.271346E+12 | 0.00 | 1.00 | 0.01 | 543491.57 | 427853.60 | 354914.11 | 130835.25 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.299648E+10 | 0.701116E+09 | 744.00 | 0.299619E+10 | 293838.00 | 0.00 | 0.29 | 15-JAN-16:35 | 0.04 | 30-JAN-07:03 | 2197.57 | 15-JAN-16:35 | 2197.57 | 15-JAN-16:35 | 11.00 | 02-JAN-07:03 | 475.05 | 15-JAN-16:35 | 0.00 |
February | 0.767073E+10 | 0.166003E+10 | 672.00 | 0.767073E+10 | -0.0 | 0.00 | 0.52 | 28-FEB-17:00 | 0.30 | 07-FEB-07:03 | 4102.65 | 28-FEB-17:00 | 4102.65 | 28-FEB-17:00 | 0.00 | 01-FEB-10:05 | 857.55 | 28-FEB-17:00 | 0.00 |
March | 0.147721E+11 | 0.296199E+10 | 744.00 | 0.147509E+11 | 21163313.85 | 0.00 | 0.83 | 25-MAR-17:55 | 0.58 | 01-MAR-07:03 | 7529.59 | 31-MAR-24:00 | 7529.59 | 31-MAR-24:00 | 265.10 | 16-MAR-15:40 | 1556.31 | 15-MAR-14:00 | 0.00 |
April | 0.196934E+11 | 0.367991E+10 | 720.00 | 0.196905E+11 | 2932774.40 | 0.00 | 0.96 | 02-APR-17:52 | 0.30 | 30-APR-24:00 | 8726.53 | 02-APR-17:58 | 8726.53 | 02-APR-17:58 | 99.24 | 12-APR-16:10 | 1661.94 | 08-APR-13:00 | 0.00 |
May | 0.545954E+10 | 0.116215E+10 | 744.00 | 0.542433E+10 | 35213708.28 | 0.00 | 0.46 | 31-MAY-24:00 | 0.19 | 12-MAY-06:12 | 3995.74 | 31-MAY-24:00 | 3995.74 | 31-MAY-24:00 | 218.06 | 17-MAY-15:20 | 773.41 | 31-MAY-24:00 | 0.00 |
June | 0.107736E+11 | 0.230170E+10 | 720.00 | 0.105921E+11 | 0.181546E+09 | 0.00 | 0.67 | 30-JUN-24:00 | 0.42 | 10-JUN-06:40 | 5910.76 | 30-JUN-24:00 | 5910.76 | 30-JUN-24:00 | 482.44 | 27-JUN-14:00 | 1348.25 | 27-JUN-13:00 | 0.00 |
July | 0.165113E+11 | 0.376847E+10 | 744.00 | 0.161971E+11 | 0.314280E+09 | 0.00 | 0.87 | 31-JUL-23:20 | 0.63 | 07-JUL-06:40 | 7852.17 | 31-JUL-24:00 | 7816.32 | 31-JUL-24:00 | 484.40 | 20-JUL-15:00 | 1931.23 | 21-JUL-14:00 | 0.00 |
August | 0.213447E+11 | 0.463386E+10 | 744.00 | 0.211062E+11 | 0.238493E+09 | 0.00 | 1.00 | 13-AUG-15:02 | 0.29 | 31-AUG-24:00 | 8711.83 | 14-AUG-18:00 | 8685.76 | 04-AUG-18:40 | 474.10 | 14-AUG-10:00 | 2422.33 | 13-AUG-15:02 | 0.00 |
September | 0.558490E+10 | 0.118894E+10 | 720.00 | 0.545338E+10 | 0.131527E+09 | 0.00 | 0.45 | 30-SEP-24:00 | 0.18 | 30-SEP-06:45 | 3772.22 | 30-SEP-24:00 | 3772.22 | 30-SEP-24:00 | 337.95 | 15-SEP-15:20 | 746.32 | 30-SEP-24:00 | 0.00 |
October | 0.101919E+11 | 0.203162E+10 | 744.00 | 0.101612E+11 | 30652491.76 | 0.00 | 0.64 | 31-OCT-24:00 | 0.39 | 17-OCT-06:45 | 5688.41 | 31-OCT-24:00 | 5688.41 | 31-OCT-24:00 | 184.33 | 12-OCT-15:30 | 1069.70 | 31-OCT-24:00 | 0.00 |
November | 0.144396E+11 | 0.281228E+10 | 720.00 | 0.144376E+11 | 2013991.33 | 0.00 | 0.73 | 26-NOV-14:10 | 0.60 | 15-NOV-07:05 | 6010.19 | 12-NOV-15:50 | 6010.19 | 12-NOV-15:50 | 143.51 | 16-NOV-16:20 | 1262.48 | 26-NOV-14:00 | 0.00 |
December | 0.193026E+11 | 0.375703E+10 | 744.00 | 0.193021E+11 | 539374.45 | 0.00 | 0.91 | 10-DEC-16:03 | 0.76 | 11-DEC-07:03 | 7843.08 | 17-DEC-16:10 | 7843.08 | 17-DEC-16:10 | 90.53 | 01-DEC-13:30 | 1506.39 | 10-DEC-16:03 | 0.00 |
Annual Sum or Average | 0.148741E+12 | 0.306591E+11 | 8760.00 | 0.147782E+12 | 0.958656E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.299648E+10 | 0.701116E+09 | 672.00 | 0.299619E+10 | -0.0 | 0.00 | 0.29 | 0.04 | 2197.57 | 2197.57 | 0.00 | 475.05 | 0.00 | ||||||
Maximum of Months | 0.213447E+11 | 0.463386E+10 | 744.00 | 0.211062E+11 | 0.314280E+09 | 0.00 | 1.00 | 0.76 | 8726.53 | 8726.53 | 484.40 | 2422.33 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.377535E+10 | 0.105321E+10 | 375.73 | 0.377532E+10 | 34654.47 | 0.00 | 0.20 | 12-JAN-16:50 | 0.00 | 01-JAN-00:03 | 13407.62 | 15-JAN-16:35 | 13407.62 | 15-JAN-16:35 | 16.69 | 11-JAN-18:10 | 3102.43 | 12-JAN-16:50 | 0.00 |
February | 0.472823E+11 | 0.106130E+11 | 672.00 | 0.472823E+11 | 0.00 | 0.00 | 0.47 | 28-FEB-17:00 | 0.11 | 06-FEB-07:03 | 35461.92 | 28-FEB-17:00 | 35461.92 | 28-FEB-17:00 | 0.00 | 20-FEB-16:30 | 7492.32 | 28-FEB-17:00 | 0.00 |
March | 0.123963E+12 | 0.252303E+11 | 744.00 | 0.123752E+12 | 0.210904E+09 | 0.00 | 0.80 | 25-MAR-17:55 | 0.43 | 06-MAR-07:03 | 67332.23 | 31-MAR-23:40 | 67332.23 | 31-MAR-23:40 | 2607.26 | 16-MAR-15:40 | 14718.34 | 15-MAR-14:05 | 0.00 |
April | 0.178005E+12 | 0.335367E+11 | 720.00 | 0.177974E+12 | 30751141.50 | 0.00 | 0.94 | 22-APR-18:23 | 0.23 | 30-APR-23:55 | 80242.08 | 02-APR-18:00 | 80242.08 | 02-APR-18:00 | 1049.67 | 12-APR-16:10 | 15654.66 | 07-APR-14:00 | 0.00 |
May | 0.473024E+11 | 0.101597E+11 | 744.00 | 0.469555E+11 | 0.346861E+09 | 0.00 | 0.46 | 31-MAY-24:00 | 0.13 | 01-MAY-06:05 | 37849.13 | 31-MAY-24:00 | 37849.13 | 31-MAY-24:00 | 2134.90 | 17-MAY-15:20 | 7337.08 | 31-MAY-24:00 | 0.00 |
June | 0.100191E+12 | 0.214936E+11 | 720.00 | 0.983877E+11 | 0.180369E+10 | 0.00 | 0.67 | 30-JUN-24:00 | 0.39 | 14-JUN-06:05 | 56395.53 | 30-JUN-24:00 | 56395.53 | 30-JUN-24:00 | 4773.64 | 27-JUN-14:00 | 12786.86 | 27-JUN-13:00 | 0.00 |
July | 0.156141E+12 | 0.357141E+11 | 744.00 | 0.153012E+12 | 0.312891E+10 | 0.00 | 0.87 | 31-JUL-23:20 | 0.61 | 06-JUL-06:20 | 75443.91 | 31-JUL-24:00 | 75095.14 | 31-JUL-24:00 | 4828.08 | 20-JUL-15:00 | 18292.27 | 21-JUL-14:00 | 0.00 |
August | 0.202247E+12 | 0.440019E+11 | 744.00 | 0.199868E+12 | 0.237850E+10 | 0.00 | 0.99 | 04-AUG-18:40 | 0.23 | 31-AUG-24:00 | 83356.71 | 04-AUG-18:40 | 83356.71 | 04-AUG-18:40 | 4725.33 | 14-AUG-10:00 | 22778.00 | 13-AUG-15:21 | 0.00 |
September | 0.484841E+11 | 0.104206E+11 | 720.00 | 0.471941E+11 | 0.128995E+10 | 0.00 | 0.41 | 30-SEP-24:00 | 0.12 | 30-SEP-06:55 | 32843.92 | 30-SEP-24:00 | 32843.92 | 30-SEP-24:00 | 3325.40 | 15-SEP-15:20 | 6714.87 | 21-SEP-17:00 | 0.00 |
October | 0.854745E+11 | 0.172574E+11 | 744.00 | 0.851683E+11 | 0.306229E+09 | 0.00 | 0.60 | 31-OCT-23:50 | 0.28 | 30-OCT-06:03 | 50295.55 | 31-OCT-23:50 | 50295.55 | 31-OCT-23:50 | 1836.18 | 12-OCT-15:30 | 9756.98 | 11-OCT-17:00 | 0.00 |
November | 0.119225E+12 | 0.236175E+11 | 720.00 | 0.119202E+12 | 22034779.87 | 0.00 | 0.66 | 15-NOV-16:20 | 0.47 | 24-NOV-07:03 | 55219.64 | 15-NOV-16:20 | 55219.64 | 15-NOV-16:20 | 1421.24 | 16-NOV-16:20 | 10705.09 | 18-NOV-15:30 | 0.00 |
December | 0.152709E+12 | 0.304736E+11 | 744.00 | 0.152703E+12 | 6129823.86 | 0.00 | 0.84 | 04-DEC-16:20 | 0.58 | 11-DEC-07:03 | 68611.47 | 04-DEC-16:20 | 68611.47 | 04-DEC-16:20 | 913.87 | 01-DEC-13:30 | 13339.73 | 04-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.126480E+13 | 0.263572E+12 | 8391.73 | 0.125528E+13 | 0.952400E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.377535E+10 | 0.105321E+10 | 375.73 | 0.377532E+10 | 0.00 | 0.00 | 0.20 | 0.00 | 13407.62 | 13407.62 | 0.00 | 3102.43 | 0.00 | ||||||
Maximum of Months | 0.202247E+12 | 0.440019E+11 | 744.00 | 0.199868E+12 | 0.312891E+10 | 0.00 | 0.99 | 0.61 | 83356.71 | 83356.71 | 4828.08 | 22778.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 54410184.05 | 15676651.71 | 62.98 | 54410184.05 | -0.0 | 0.00 | 0.16 | 12-JAN-16:40 | 0.00 | 01-JAN-00:03 | 1117.85 | 12-JAN-16:40 | 1117.85 | 12-JAN-16:40 | 0.00 | 27-JAN-17:15 | 263.60 | 12-JAN-16:40 | 0.00 |
February | 0.317684E+10 | 0.730516E+09 | 648.04 | 0.317684E+10 | 0.00 | 0.00 | 0.46 | 28-FEB-17:00 | 0.00 | 01-FEB-00:03 | 3503.42 | 28-FEB-17:00 | 3503.42 | 28-FEB-17:00 | 0.00 | 19-FEB-15:50 | 742.24 | 28-FEB-17:00 | 0.00 |
March | 0.108350E+11 | 0.223471E+10 | 744.00 | 0.108140E+11 | 20995063.51 | 0.00 | 0.75 | 25-MAR-17:42 | 0.27 | 06-MAR-04:01 | 6287.37 | 31-MAR-23:20 | 6287.37 | 31-MAR-23:20 | 260.84 | 16-MAR-15:40 | 1495.11 | 15-MAR-14:05 | 0.00 |
April | 0.167539E+11 | 0.318581E+10 | 720.00 | 0.167509E+11 | 3011673.02 | 0.00 | 0.92 | 22-APR-18:15 | 0.17 | 30-APR-23:55 | 7933.97 | 09-APR-17:57 | 7933.97 | 09-APR-17:57 | 98.59 | 12-APR-16:10 | 1575.75 | 07-APR-14:00 | 0.00 |
May | 0.431794E+10 | 0.935163E+09 | 744.00 | 0.428354E+10 | 34399795.64 | 0.00 | 0.44 | 31-MAY-23:40 | 0.03 | 01-MAY-06:05 | 3691.81 | 31-MAY-23:40 | 3691.81 | 31-MAY-23:40 | 213.15 | 17-MAY-15:20 | 718.50 | 31-MAY-23:40 | 0.00 |
June | 0.995500E+10 | 0.214379E+10 | 720.00 | 0.977454E+10 | 0.180462E+09 | 0.00 | 0.65 | 30-JUN-23:40 | 0.33 | 14-JUN-06:05 | 5570.71 | 30-JUN-23:40 | 5570.71 | 30-JUN-23:40 | 479.72 | 27-JUN-14:00 | 1305.72 | 27-JUN-13:00 | 0.00 |
July | 0.156768E+11 | 0.359493E+10 | 744.00 | 0.153639E+11 | 0.312852E+09 | 0.00 | 0.85 | 31-JUL-23:20 | 0.58 | 13-JUL-06:20 | 7533.45 | 31-JUL-24:00 | 7498.35 | 31-JUL-24:00 | 482.95 | 20-JUL-15:00 | 1859.45 | 21-JUL-14:00 | 0.00 |
August | 0.202011E+11 | 0.441045E+10 | 744.00 | 0.199635E+11 | 0.237579E+09 | 0.00 | 1.00 | 13-AUG-15:42 | 0.20 | 31-AUG-24:00 | 8418.34 | 04-AUG-18:40 | 8418.34 | 04-AUG-18:40 | 472.46 | 14-AUG-10:00 | 2343.11 | 13-AUG-15:42 | 0.00 |
September | 0.448202E+10 | 0.972793E+09 | 720.00 | 0.435365E+10 | 0.128373E+09 | 0.00 | 0.37 | 04-SEP-17:44 | 0.05 | 30-SEP-06:55 | 3030.10 | 04-SEP-17:42 | 3030.10 | 04-SEP-17:42 | 334.57 | 15-SEP-15:20 | 689.06 | 21-SEP-17:00 | 0.00 |
October | 0.719950E+10 | 0.147283E+10 | 744.00 | 0.716922E+10 | 30280042.59 | 0.00 | 0.54 | 31-OCT-23:20 | 0.13 | 30-OCT-06:03 | 4595.88 | 31-OCT-23:20 | 4595.88 | 31-OCT-23:20 | 183.91 | 12-OCT-15:30 | 981.75 | 11-OCT-17:00 | 0.00 |
November | 0.101235E+11 | 0.203990E+10 | 720.00 | 0.101214E+11 | 2070800.08 | 0.00 | 0.64 | 03-NOV-16:00 | 0.31 | 24-NOV-04:17 | 5371.71 | 15-NOV-16:20 | 5371.71 | 15-NOV-16:20 | 139.00 | 16-NOV-16:20 | 1039.73 | 03-NOV-16:00 | 0.00 |
December | 0.134200E+11 | 0.272171E+10 | 744.00 | 0.134194E+11 | 578247.38 | 0.00 | 0.79 | 04-DEC-16:20 | 0.43 | 11-DEC-04:12 | 6524.71 | 04-DEC-16:20 | 6524.71 | 04-DEC-16:20 | 87.33 | 01-DEC-13:30 | 1279.68 | 04-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.116196E+12 | 0.244583E+11 | 8055.03 | 0.115245E+12 | 0.950602E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 54410184.05 | 15676651.71 | 62.98 | 54410184.05 | -0.0 | 0.00 | 0.16 | 0.00 | 1117.85 | 1117.85 | 0.00 | 263.60 | 0.00 | ||||||
Maximum of Months | 0.202011E+11 | 0.441045E+10 | 744.00 | 0.199635E+11 | 0.312852E+09 | 0.00 | 1.00 | 0.58 | 8418.34 | 8418.34 | 482.95 | 2343.11 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.06 | 0.00 | 128.06 | 0.02 | 852.41 | 0.00 | 0.00 | 0.00 |
February | 195.11 | 0.00 | 195.11 | 5.23 | 801.02 | 0.00 | 0.00 | 0.00 |
March | 236.61 | 0.00 | 236.61 | 62.00 | 592.00 | 0.00 | 0.00 | 0.00 |
April | 301.50 | 1.20 | 300.29 | 140.91 | 426.00 | 0.00 | 0.00 | 0.00 |
May | 350.32 | 14.86 | 335.47 | 264.64 | 255.81 | 0.00 | 0.00 | 0.00 |
June | 421.37 | 35.87 | 385.50 | 447.63 | 163.12 | 0.00 | 0.00 | 0.00 |
July | 390.87 | 25.23 | 365.64 | 480.45 | 113.23 | 0.00 | 0.00 | 0.00 |
August | 338.21 | 5.15 | 333.07 | 391.63 | 150.18 | 0.00 | 0.00 | 0.00 |
September | 257.39 | 0.05 | 257.33 | 226.12 | 252.59 | 0.00 | 0.00 | 0.00 |
October | 192.41 | 0.00 | 192.41 | 78.36 | 424.76 | 0.00 | 0.00 | 0.00 |
November | 129.29 | 0.00 | 129.29 | 16.96 | 571.70 | 0.00 | 0.00 | 0.00 |
December | 119.86 | 0.00 | 119.86 | 0.59 | 841.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.33 | 6.89 | 248.44 | 177.27 | 451.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.86 | 0.00 | 119.86 | 0.02 | 113.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.37 | 35.87 | 385.50 | 480.45 | 852.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.06 | 0.00 | 128.06 | 0.02 | 852.41 | 0.00 | 0.00 | 0.00 |
February | 195.11 | 0.00 | 195.11 | 5.23 | 801.02 | 0.00 | 0.00 | 0.00 |
March | 236.61 | 0.00 | 236.61 | 61.99 | 592.00 | 0.00 | 0.00 | 0.00 |
April | 301.50 | 1.20 | 300.29 | 140.91 | 426.00 | 0.00 | 0.00 | 0.00 |
May | 350.32 | 14.86 | 335.47 | 264.64 | 255.81 | 0.00 | 0.00 | 0.00 |
June | 421.36 | 35.87 | 385.50 | 447.63 | 163.12 | 0.00 | 0.00 | 0.00 |
July | 390.87 | 25.23 | 365.64 | 480.45 | 113.23 | 0.00 | 0.00 | 0.00 |
August | 338.21 | 5.15 | 333.07 | 391.63 | 150.18 | 0.00 | 0.00 | 0.00 |
September | 257.39 | 0.05 | 257.33 | 226.12 | 252.59 | 0.00 | 0.00 | 0.00 |
October | 192.41 | 0.00 | 192.41 | 78.36 | 424.76 | 0.00 | 0.00 | 0.00 |
November | 129.29 | 0.00 | 129.29 | 16.96 | 571.70 | 0.00 | 0.00 | 0.00 |
December | 119.86 | 0.00 | 119.86 | 0.59 | 841.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.33 | 6.89 | 248.44 | 177.27 | 451.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.86 | 0.00 | 119.86 | 0.02 | 113.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.36 | 35.87 | 385.50 | 480.45 | 852.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.06 | 0.00 | 128.06 | 0.02 | 852.41 | 0.00 | 0.00 | 0.00 |
February | 195.11 | 0.00 | 195.11 | 5.23 | 801.02 | 0.00 | 0.00 | 0.00 |
March | 236.61 | 0.00 | 236.61 | 62.00 | 592.00 | 0.00 | 0.00 | 0.00 |
April | 301.50 | 1.20 | 300.29 | 140.91 | 426.00 | 0.00 | 0.00 | 0.00 |
May | 350.32 | 14.86 | 335.47 | 264.64 | 255.81 | 0.00 | 0.00 | 0.00 |
June | 421.37 | 35.87 | 385.50 | 447.63 | 163.12 | 0.00 | 0.00 | 0.00 |
July | 390.87 | 25.23 | 365.64 | 480.45 | 113.23 | 0.00 | 0.00 | 0.00 |
August | 338.21 | 5.15 | 333.07 | 391.63 | 150.18 | 0.00 | 0.00 | 0.00 |
September | 257.39 | 0.05 | 257.33 | 226.12 | 252.59 | 0.00 | 0.00 | 0.00 |
October | 192.41 | 0.00 | 192.41 | 78.36 | 424.76 | 0.00 | 0.00 | 0.00 |
November | 129.29 | 0.00 | 129.29 | 16.96 | 571.70 | 0.00 | 0.00 | 0.00 |
December | 119.86 | 0.00 | 119.86 | 0.59 | 841.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.33 | 6.89 | 248.44 | 177.27 | 451.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.86 | 0.00 | 119.86 | 0.02 | 113.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.37 | 35.87 | 385.50 | 480.45 | 852.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.06 | 0.00 | 128.06 | 0.02 | 852.41 | 0.00 | 0.00 | 0.00 |
February | 195.11 | 0.00 | 195.11 | 5.23 | 801.02 | 0.00 | 0.00 | 0.00 |
March | 236.61 | 0.00 | 236.61 | 61.99 | 592.00 | 0.00 | 0.00 | 0.00 |
April | 301.50 | 1.20 | 300.29 | 140.91 | 426.00 | 0.00 | 0.00 | 0.00 |
May | 350.32 | 14.86 | 335.47 | 264.64 | 255.81 | 0.00 | 0.00 | 0.00 |
June | 421.36 | 35.87 | 385.50 | 447.63 | 163.12 | 0.00 | 0.00 | 0.00 |
July | 390.87 | 25.23 | 365.64 | 480.45 | 113.23 | 0.00 | 0.00 | 0.00 |
August | 338.21 | 5.15 | 333.07 | 391.63 | 150.18 | 0.00 | 0.00 | 0.00 |
September | 257.39 | 0.05 | 257.33 | 226.12 | 252.59 | 0.00 | 0.00 | 0.00 |
October | 192.41 | 0.00 | 192.41 | 78.36 | 424.76 | 0.00 | 0.00 | 0.00 |
November | 129.29 | 0.00 | 129.29 | 16.96 | 571.70 | 0.00 | 0.00 | 0.00 |
December | 119.86 | 0.00 | 119.86 | 0.59 | 841.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.33 | 6.89 | 248.44 | 177.27 | 451.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.86 | 0.00 | 119.86 | 0.02 | 113.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.36 | 35.87 | 385.50 | 480.45 | 852.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.05 | 0.00 | 128.05 | 0.02 | 852.37 | 0.00 | 0.00 | 0.00 |
February | 195.10 | 0.00 | 195.10 | 5.23 | 800.99 | 0.00 | 0.00 | 0.00 |
March | 236.61 | 0.00 | 236.61 | 61.99 | 591.98 | 0.00 | 0.00 | 0.00 |
April | 301.48 | 1.20 | 300.28 | 140.90 | 425.98 | 0.00 | 0.00 | 0.00 |
May | 350.31 | 14.86 | 335.45 | 264.63 | 255.80 | 0.00 | 0.00 | 0.00 |
June | 421.35 | 35.87 | 385.48 | 447.62 | 163.12 | 0.00 | 0.00 | 0.00 |
July | 390.86 | 25.23 | 365.63 | 480.43 | 113.23 | 0.00 | 0.00 | 0.00 |
August | 338.20 | 5.14 | 333.05 | 391.61 | 150.17 | 0.00 | 0.00 | 0.00 |
September | 257.38 | 0.05 | 257.32 | 226.11 | 252.58 | 0.00 | 0.00 | 0.00 |
October | 192.40 | 0.00 | 192.40 | 78.36 | 424.75 | 0.00 | 0.00 | 0.00 |
November | 129.29 | 0.00 | 129.29 | 16.95 | 571.68 | 0.00 | 0.00 | 0.00 |
December | 119.85 | 0.00 | 119.85 | 0.59 | 841.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.32 | 6.89 | 248.43 | 177.26 | 451.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.85 | 0.00 | 119.85 | 0.02 | 113.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.35 | 35.87 | 385.48 | 480.43 | 852.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 260.38 | 83.96 | 176.42 | 92.58 | 861.61 | 0.00 | 0.00 | 0.00 |
February | 382.06 | 114.65 | 267.41 | 165.30 | 811.34 | 0.00 | 0.00 | 0.00 |
March | 548.24 | 229.60 | 318.64 | 409.61 | 596.93 | 0.00 | 0.00 | 0.00 |
April | 725.63 | 320.62 | 405.01 | 662.33 | 434.97 | 0.00 | 0.00 | 0.00 |
May | 812.97 | 359.62 | 453.35 | 874.49 | 286.55 | 0.00 | 0.00 | 0.00 |
June | 907.95 | 401.27 | 506.68 | 1098.52 | 182.47 | 0.00 | 0.00 | 0.00 |
July | 871.87 | 383.87 | 488.00 | 1133.95 | 123.77 | 0.00 | 0.00 | 0.00 |
August | 787.40 | 330.51 | 456.89 | 1002.79 | 160.32 | 0.00 | 0.00 | 0.00 |
September | 655.25 | 290.64 | 364.61 | 749.24 | 266.72 | 0.00 | 0.00 | 0.00 |
October | 444.64 | 183.92 | 260.73 | 380.88 | 437.43 | 0.00 | 0.00 | 0.00 |
November | 252.21 | 80.91 | 171.30 | 140.23 | 589.97 | 0.00 | 0.00 | 0.00 |
December | 203.04 | 41.95 | 161.09 | 45.70 | 858.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 571.82 | 235.70 | 336.12 | 565.14 | 465.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 203.04 | 41.95 | 161.09 | 45.70 | 123.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 907.95 | 401.27 | 506.68 | 1133.95 | 861.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 260.38 | 83.96 | 176.42 | 92.58 | 861.61 | 0.00 | 0.00 | 0.00 |
February | 382.06 | 114.65 | 267.41 | 165.30 | 811.34 | 0.00 | 0.00 | 0.00 |
March | 548.24 | 229.60 | 318.64 | 409.61 | 596.93 | 0.00 | 0.00 | 0.00 |
April | 725.63 | 320.62 | 405.01 | 662.33 | 434.97 | 0.00 | 0.00 | 0.00 |
May | 812.97 | 359.62 | 453.35 | 874.49 | 286.55 | 0.00 | 0.00 | 0.00 |
June | 907.95 | 401.27 | 506.68 | 1098.52 | 182.47 | 0.00 | 0.00 | 0.00 |
July | 871.87 | 383.87 | 488.00 | 1133.95 | 123.77 | 0.00 | 0.00 | 0.00 |
August | 787.40 | 330.51 | 456.89 | 1002.79 | 160.32 | 0.00 | 0.00 | 0.00 |
September | 655.25 | 290.64 | 364.61 | 749.24 | 266.72 | 0.00 | 0.00 | 0.00 |
October | 444.64 | 183.92 | 260.73 | 380.88 | 437.43 | 0.00 | 0.00 | 0.00 |
November | 252.21 | 80.91 | 171.30 | 140.23 | 589.97 | 0.00 | 0.00 | 0.00 |
December | 203.04 | 41.95 | 161.09 | 45.70 | 858.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 571.82 | 235.70 | 336.12 | 565.14 | 465.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 203.04 | 41.95 | 161.09 | 45.70 | 123.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 907.95 | 401.27 | 506.68 | 1133.95 | 861.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 260.38 | 83.96 | 176.42 | 92.58 | 861.59 | 0.00 | 0.00 | 0.00 |
February | 382.05 | 114.64 | 267.41 | 165.29 | 811.33 | 0.00 | 0.00 | 0.00 |
March | 548.23 | 229.60 | 318.64 | 409.60 | 596.92 | 0.00 | 0.00 | 0.00 |
April | 725.62 | 320.62 | 405.00 | 662.32 | 434.96 | 0.00 | 0.00 | 0.00 |
May | 812.96 | 359.61 | 453.34 | 874.48 | 286.54 | 0.00 | 0.00 | 0.00 |
June | 907.93 | 401.26 | 506.67 | 1098.50 | 182.46 | 0.00 | 0.00 | 0.00 |
July | 871.85 | 383.87 | 487.99 | 1133.93 | 123.77 | 0.00 | 0.00 | 0.00 |
August | 787.38 | 330.50 | 456.88 | 1002.77 | 160.32 | 0.00 | 0.00 | 0.00 |
September | 655.24 | 290.64 | 364.60 | 749.23 | 266.72 | 0.00 | 0.00 | 0.00 |
October | 444.63 | 183.91 | 260.72 | 380.87 | 437.43 | 0.00 | 0.00 | 0.00 |
November | 252.20 | 80.90 | 171.30 | 140.23 | 589.96 | 0.00 | 0.00 | 0.00 |
December | 203.04 | 41.95 | 161.09 | 45.70 | 858.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 571.81 | 235.69 | 336.11 | 565.13 | 465.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 203.04 | 41.95 | 161.09 | 45.70 | 123.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 907.93 | 401.26 | 506.67 | 1133.93 | 861.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 550.65 | 321.43 | 229.22 | 434.76 | 706.67 | 0.00 | 0.00 | 0.00 |
February | 628.70 | 303.15 | 325.55 | 487.52 | 692.62 | 0.00 | 0.00 | 0.00 |
March | 767.37 | 431.18 | 336.19 | 739.43 | 526.84 | 0.00 | 0.00 | 0.00 |
April | 635.51 | 253.95 | 381.56 | 637.29 | 421.80 | 0.00 | 0.00 | 0.00 |
May | 556.12 | 161.52 | 394.60 | 613.69 | 277.89 | 0.00 | 0.00 | 0.00 |
June | 540.37 | 114.51 | 425.87 | 667.49 | 179.07 | 0.00 | 0.00 | 0.00 |
July | 551.63 | 133.84 | 417.79 | 753.46 | 123.13 | 0.00 | 0.00 | 0.00 |
August | 619.30 | 200.79 | 418.51 | 833.10 | 159.01 | 0.00 | 0.00 | 0.00 |
September | 720.06 | 350.72 | 369.34 | 894.63 | 253.97 | 0.00 | 0.00 | 0.00 |
October | 688.99 | 393.56 | 295.43 | 734.40 | 392.20 | 0.00 | 0.00 | 0.00 |
November | 493.44 | 278.56 | 214.88 | 454.61 | 507.45 | 0.00 | 0.00 | 0.00 |
December | 460.45 | 238.30 | 222.15 | 340.10 | 709.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.86 | 264.99 | 335.88 | 633.39 | 411.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.45 | 114.51 | 214.88 | 340.10 | 123.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 767.37 | 431.18 | 425.87 | 894.63 | 709.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 550.65 | 321.43 | 229.22 | 434.76 | 706.67 | 0.00 | 0.00 | 0.00 |
February | 628.70 | 303.15 | 325.55 | 487.52 | 692.62 | 0.00 | 0.00 | 0.00 |
March | 767.37 | 431.18 | 336.19 | 739.43 | 526.84 | 0.00 | 0.00 | 0.00 |
April | 635.50 | 253.95 | 381.56 | 637.29 | 421.80 | 0.00 | 0.00 | 0.00 |
May | 556.12 | 161.52 | 394.60 | 613.69 | 277.89 | 0.00 | 0.00 | 0.00 |
June | 540.37 | 114.51 | 425.86 | 667.49 | 179.07 | 0.00 | 0.00 | 0.00 |
July | 551.63 | 133.84 | 417.79 | 753.46 | 123.13 | 0.00 | 0.00 | 0.00 |
August | 619.30 | 200.79 | 418.51 | 833.10 | 159.01 | 0.00 | 0.00 | 0.00 |
September | 720.06 | 350.72 | 369.34 | 894.63 | 253.97 | 0.00 | 0.00 | 0.00 |
October | 688.99 | 393.56 | 295.43 | 734.40 | 392.20 | 0.00 | 0.00 | 0.00 |
November | 493.44 | 278.56 | 214.88 | 454.61 | 507.45 | 0.00 | 0.00 | 0.00 |
December | 460.45 | 238.30 | 222.15 | 340.10 | 709.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.86 | 264.99 | 335.88 | 633.39 | 411.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.45 | 114.51 | 214.88 | 340.10 | 123.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 767.37 | 431.18 | 425.86 | 894.63 | 709.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 550.65 | 321.43 | 229.22 | 434.76 | 706.67 | 0.00 | 0.00 | 0.00 |
February | 628.70 | 303.15 | 325.55 | 487.52 | 692.62 | 0.00 | 0.00 | 0.00 |
March | 767.37 | 431.18 | 336.19 | 739.43 | 526.84 | 0.00 | 0.00 | 0.00 |
April | 635.51 | 253.95 | 381.56 | 637.29 | 421.80 | 0.00 | 0.00 | 0.00 |
May | 556.12 | 161.52 | 394.60 | 613.69 | 277.89 | 0.00 | 0.00 | 0.00 |
June | 540.37 | 114.51 | 425.87 | 667.49 | 179.07 | 0.00 | 0.00 | 0.00 |
July | 551.63 | 133.84 | 417.79 | 753.46 | 123.13 | 0.00 | 0.00 | 0.00 |
August | 619.30 | 200.79 | 418.51 | 833.10 | 159.01 | 0.00 | 0.00 | 0.00 |
September | 720.06 | 350.72 | 369.34 | 894.63 | 253.97 | 0.00 | 0.00 | 0.00 |
October | 688.99 | 393.56 | 295.43 | 734.40 | 392.20 | 0.00 | 0.00 | 0.00 |
November | 493.44 | 278.56 | 214.88 | 454.61 | 507.45 | 0.00 | 0.00 | 0.00 |
December | 460.45 | 238.30 | 222.15 | 340.10 | 709.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.86 | 264.99 | 335.88 | 633.39 | 411.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.45 | 114.51 | 214.88 | 340.10 | 123.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 767.37 | 431.18 | 425.87 | 894.63 | 709.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 550.65 | 321.43 | 229.22 | 434.76 | 706.67 | 0.00 | 0.00 | 0.00 |
February | 628.70 | 303.15 | 325.55 | 487.52 | 692.62 | 0.00 | 0.00 | 0.00 |
March | 767.37 | 431.18 | 336.19 | 739.43 | 526.84 | 0.00 | 0.00 | 0.00 |
April | 635.50 | 253.95 | 381.56 | 637.29 | 421.80 | 0.00 | 0.00 | 0.00 |
May | 556.12 | 161.52 | 394.60 | 613.69 | 277.89 | 0.00 | 0.00 | 0.00 |
June | 540.37 | 114.51 | 425.86 | 667.49 | 179.07 | 0.00 | 0.00 | 0.00 |
July | 551.63 | 133.84 | 417.79 | 753.46 | 123.13 | 0.00 | 0.00 | 0.00 |
August | 619.30 | 200.79 | 418.51 | 833.10 | 159.01 | 0.00 | 0.00 | 0.00 |
September | 720.06 | 350.72 | 369.34 | 894.63 | 253.97 | 0.00 | 0.00 | 0.00 |
October | 688.99 | 393.56 | 295.43 | 734.40 | 392.20 | 0.00 | 0.00 | 0.00 |
November | 493.44 | 278.56 | 214.88 | 454.61 | 507.45 | 0.00 | 0.00 | 0.00 |
December | 460.45 | 238.30 | 222.15 | 340.10 | 709.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.86 | 264.99 | 335.88 | 633.39 | 411.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.45 | 114.51 | 214.88 | 340.10 | 123.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 767.37 | 431.18 | 425.86 | 894.63 | 709.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 550.63 | 321.42 | 229.21 | 434.74 | 706.64 | 0.00 | 0.00 | 0.00 |
February | 628.68 | 303.14 | 325.53 | 487.50 | 692.59 | 0.00 | 0.00 | 0.00 |
March | 767.34 | 431.16 | 336.18 | 739.40 | 526.82 | 0.00 | 0.00 | 0.00 |
April | 635.48 | 253.94 | 381.54 | 637.27 | 421.79 | 0.00 | 0.00 | 0.00 |
May | 556.10 | 161.52 | 394.59 | 613.67 | 277.87 | 0.00 | 0.00 | 0.00 |
June | 540.35 | 114.50 | 425.85 | 667.46 | 179.06 | 0.00 | 0.00 | 0.00 |
July | 551.61 | 133.84 | 417.77 | 753.43 | 123.12 | 0.00 | 0.00 | 0.00 |
August | 619.27 | 200.78 | 418.49 | 833.07 | 159.01 | 0.00 | 0.00 | 0.00 |
September | 720.03 | 350.71 | 369.32 | 894.60 | 253.96 | 0.00 | 0.00 | 0.00 |
October | 688.96 | 393.55 | 295.41 | 734.37 | 392.19 | 0.00 | 0.00 | 0.00 |
November | 493.42 | 278.55 | 214.87 | 454.59 | 507.43 | 0.00 | 0.00 | 0.00 |
December | 460.43 | 238.29 | 222.14 | 340.08 | 709.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.84 | 264.98 | 335.86 | 633.37 | 411.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.43 | 114.50 | 214.87 | 340.08 | 123.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 767.34 | 431.16 | 425.85 | 894.60 | 709.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 223.40 | 52.45 | 170.96 | 54.11 | 934.67 | 0.00 | 0.00 | 0.00 |
February | 362.07 | 93.06 | 269.02 | 133.55 | 899.57 | 0.00 | 0.00 | 0.00 |
March | 567.49 | 242.98 | 324.50 | 420.56 | 677.66 | 0.00 | 0.00 | 0.00 |
April | 694.81 | 284.90 | 409.91 | 611.53 | 518.72 | 0.00 | 0.00 | 0.00 |
May | 819.64 | 370.42 | 449.21 | 878.80 | 327.12 | 0.00 | 0.00 | 0.00 |
June | 988.92 | 465.15 | 523.77 | 1198.41 | 222.91 | 0.00 | 0.00 | 0.00 |
July | 884.13 | 387.63 | 496.50 | 1136.83 | 163.71 | 0.00 | 0.00 | 0.00 |
August | 799.64 | 340.02 | 459.63 | 1007.36 | 210.37 | 0.00 | 0.00 | 0.00 |
September | 627.97 | 271.19 | 356.78 | 711.11 | 304.10 | 0.00 | 0.00 | 0.00 |
October | 407.08 | 143.40 | 263.68 | 328.55 | 500.36 | 0.00 | 0.00 | 0.00 |
November | 241.24 | 69.52 | 171.72 | 121.12 | 678.89 | 0.00 | 0.00 | 0.00 |
December | 209.13 | 45.57 | 163.56 | 47.47 | 987.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 569.73 | 231.19 | 338.54 | 556.41 | 533.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.13 | 45.57 | 163.56 | 47.47 | 163.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 988.92 | 465.15 | 523.77 | 1198.41 | 987.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 223.40 | 52.45 | 170.96 | 54.11 | 934.67 | 0.00 | 0.00 | 0.00 |
February | 362.07 | 93.06 | 269.02 | 133.55 | 899.57 | 0.00 | 0.00 | 0.00 |
March | 567.49 | 242.98 | 324.50 | 420.56 | 677.66 | 0.00 | 0.00 | 0.00 |
April | 694.81 | 284.90 | 409.91 | 611.53 | 518.72 | 0.00 | 0.00 | 0.00 |
May | 819.64 | 370.42 | 449.21 | 878.80 | 327.12 | 0.00 | 0.00 | 0.00 |
June | 988.92 | 465.15 | 523.77 | 1198.41 | 222.91 | 0.00 | 0.00 | 0.00 |
July | 884.13 | 387.63 | 496.50 | 1136.83 | 163.71 | 0.00 | 0.00 | 0.00 |
August | 799.64 | 340.02 | 459.63 | 1007.36 | 210.37 | 0.00 | 0.00 | 0.00 |
September | 627.97 | 271.19 | 356.78 | 711.11 | 304.10 | 0.00 | 0.00 | 0.00 |
October | 407.08 | 143.40 | 263.68 | 328.55 | 500.36 | 0.00 | 0.00 | 0.00 |
November | 241.24 | 69.52 | 171.72 | 121.12 | 678.89 | 0.00 | 0.00 | 0.00 |
December | 209.13 | 45.57 | 163.56 | 47.47 | 987.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 569.73 | 231.19 | 338.54 | 556.41 | 533.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.13 | 45.57 | 163.56 | 47.47 | 163.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 988.92 | 465.15 | 523.77 | 1198.41 | 987.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 223.40 | 52.45 | 170.95 | 54.11 | 934.66 | 0.00 | 0.00 | 0.00 |
February | 362.07 | 93.05 | 269.01 | 133.54 | 899.55 | 0.00 | 0.00 | 0.00 |
March | 567.48 | 242.98 | 324.50 | 420.55 | 677.65 | 0.00 | 0.00 | 0.00 |
April | 694.80 | 284.89 | 409.90 | 611.52 | 518.71 | 0.00 | 0.00 | 0.00 |
May | 819.62 | 370.42 | 449.21 | 878.78 | 327.12 | 0.00 | 0.00 | 0.00 |
June | 988.90 | 465.14 | 523.76 | 1198.39 | 222.90 | 0.00 | 0.00 | 0.00 |
July | 884.11 | 387.63 | 496.49 | 1136.81 | 163.70 | 0.00 | 0.00 | 0.00 |
August | 799.63 | 340.01 | 459.62 | 1007.34 | 210.37 | 0.00 | 0.00 | 0.00 |
September | 627.96 | 271.19 | 356.77 | 711.10 | 304.09 | 0.00 | 0.00 | 0.00 |
October | 407.07 | 143.39 | 263.68 | 328.55 | 500.36 | 0.00 | 0.00 | 0.00 |
November | 241.23 | 69.51 | 171.72 | 121.12 | 678.88 | 0.00 | 0.00 | 0.00 |
December | 209.13 | 45.57 | 163.56 | 47.47 | 987.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 569.72 | 231.19 | 338.53 | 556.40 | 533.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.13 | 45.57 | 163.56 | 47.47 | 163.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 988.90 | 465.14 | 523.76 | 1198.39 | 987.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.28 | 0.00 | 640.28 | 5.54 | 3855.35 | 0.00 | 0.00 | 0.00 |
February | 975.54 | 0.00 | 975.54 | 54.87 | 3618.02 | 0.00 | 0.00 | 0.00 |
March | 1183.06 | 0.00 | 1183.06 | 362.75 | 2659.82 | 0.00 | 0.00 | 0.00 |
April | 1507.46 | 6.02 | 1501.45 | 779.92 | 1912.60 | 0.00 | 0.00 | 0.00 |
May | 1751.60 | 74.28 | 1677.32 | 1349.34 | 1215.25 | 0.00 | 0.00 | 0.00 |
June | 2106.80 | 179.34 | 1927.46 | 2255.79 | 777.80 | 0.00 | 0.00 | 0.00 |
July | 1954.34 | 126.16 | 1828.18 | 2425.76 | 540.40 | 0.00 | 0.00 | 0.00 |
August | 1691.04 | 25.73 | 1665.32 | 1982.74 | 717.85 | 0.00 | 0.00 | 0.00 |
September | 1286.92 | 0.27 | 1286.65 | 1154.60 | 1179.65 | 0.00 | 0.00 | 0.00 |
October | 962.03 | 0.00 | 962.03 | 448.98 | 1901.05 | 0.00 | 0.00 | 0.00 |
November | 646.46 | 0.00 | 646.46 | 125.62 | 2465.90 | 0.00 | 0.00 | 0.00 |
December | 599.28 | 0.00 | 599.28 | 8.23 | 3698.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1276.64 | 34.46 | 1242.18 | 918.07 | 2037.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.28 | 0.00 | 599.28 | 5.54 | 540.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2106.80 | 179.34 | 1927.46 | 2425.76 | 3855.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 781.13 | 251.88 | 529.25 | 298.94 | 2340.36 | 0.00 | 0.00 | 0.00 |
February | 1146.16 | 343.94 | 802.23 | 531.12 | 2229.24 | 0.00 | 0.00 | 0.00 |
March | 1644.71 | 688.79 | 955.92 | 1246.12 | 1667.02 | 0.00 | 0.00 | 0.00 |
April | 2176.88 | 961.86 | 1215.02 | 1990.46 | 1233.66 | 0.00 | 0.00 | 0.00 |
May | 2438.88 | 1078.85 | 1360.04 | 2602.62 | 837.81 | 0.00 | 0.00 | 0.00 |
June | 2723.82 | 1203.80 | 1520.03 | 3270.33 | 536.93 | 0.00 | 0.00 | 0.00 |
July | 2615.59 | 1151.61 | 1463.98 | 3379.47 | 371.39 | 0.00 | 0.00 | 0.00 |
August | 2362.16 | 991.51 | 1370.65 | 2983.62 | 486.61 | 0.00 | 0.00 | 0.00 |
September | 1965.73 | 871.92 | 1093.81 | 2233.83 | 772.30 | 0.00 | 0.00 | 0.00 |
October | 1333.91 | 551.74 | 782.17 | 1153.74 | 1224.15 | 0.00 | 0.00 | 0.00 |
November | 756.62 | 242.71 | 513.90 | 446.07 | 1590.77 | 0.00 | 0.00 | 0.00 |
December | 609.12 | 125.86 | 483.26 | 155.00 | 2316.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1715.44 | 707.09 | 1008.35 | 1697.25 | 1295.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 609.12 | 125.86 | 483.26 | 155.00 | 371.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2723.82 | 1203.80 | 1520.03 | 3379.47 | 2340.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2753.21 | 1607.13 | 1146.08 | 2188.36 | 3360.38 | 0.00 | 0.00 | 0.00 |
February | 3143.47 | 1515.75 | 1627.72 | 2454.33 | 3307.73 | 0.00 | 0.00 | 0.00 |
March | 3836.82 | 2155.88 | 1680.93 | 3684.51 | 2537.20 | 0.00 | 0.00 | 0.00 |
April | 3177.49 | 1269.73 | 1907.75 | 3184.06 | 2018.89 | 0.00 | 0.00 | 0.00 |
May | 2780.58 | 807.60 | 1972.99 | 3046.83 | 1360.45 | 0.00 | 0.00 | 0.00 |
June | 2701.83 | 572.53 | 2129.30 | 3325.64 | 864.63 | 0.00 | 0.00 | 0.00 |
July | 2758.13 | 669.21 | 2088.92 | 3761.51 | 596.77 | 0.00 | 0.00 | 0.00 |
August | 3096.46 | 1003.95 | 2092.51 | 4153.25 | 778.14 | 0.00 | 0.00 | 0.00 |
September | 3600.26 | 1753.59 | 1846.66 | 4445.18 | 1242.61 | 0.00 | 0.00 | 0.00 |
October | 3444.91 | 1967.80 | 1477.11 | 3652.72 | 1896.82 | 0.00 | 0.00 | 0.00 |
November | 2467.18 | 1392.80 | 1074.37 | 2281.49 | 2398.80 | 0.00 | 0.00 | 0.00 |
December | 2302.23 | 1191.51 | 1110.72 | 1725.46 | 3318.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3004.28 | 1324.92 | 1679.36 | 3162.75 | 1966.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2302.23 | 572.53 | 1074.37 | 1725.46 | 596.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3836.82 | 2155.88 | 2129.30 | 4445.18 | 3360.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 670.20 | 157.34 | 512.86 | 179.21 | 2483.07 | 0.00 | 0.00 | 0.00 |
February | 1086.21 | 279.16 | 807.05 | 449.07 | 2355.70 | 0.00 | 0.00 | 0.00 |
March | 1702.44 | 728.94 | 973.49 | 1315.45 | 1756.15 | 0.00 | 0.00 | 0.00 |
April | 2084.41 | 854.69 | 1229.72 | 1897.44 | 1336.89 | 0.00 | 0.00 | 0.00 |
May | 2458.89 | 1111.26 | 1347.63 | 2643.35 | 919.95 | 0.00 | 0.00 | 0.00 |
June | 2966.72 | 1395.42 | 1571.30 | 3603.47 | 613.00 | 0.00 | 0.00 | 0.00 |
July | 2652.36 | 1162.89 | 1489.48 | 3435.84 | 437.62 | 0.00 | 0.00 | 0.00 |
August | 2398.91 | 1020.04 | 1378.87 | 3057.69 | 551.40 | 0.00 | 0.00 | 0.00 |
September | 1883.89 | 813.57 | 1070.32 | 2145.72 | 839.92 | 0.00 | 0.00 | 0.00 |
October | 1221.23 | 430.19 | 791.04 | 1031.69 | 1302.66 | 0.00 | 0.00 | 0.00 |
November | 723.70 | 208.55 | 515.16 | 406.09 | 1665.95 | 0.00 | 0.00 | 0.00 |
December | 627.39 | 136.70 | 490.69 | 170.00 | 2420.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1709.18 | 693.57 | 1015.61 | 1701.33 | 1385.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 627.39 | 136.70 | 490.69 | 170.00 | 437.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2966.72 | 1395.42 | 1571.30 | 3603.47 | 2483.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.28 | 0.00 | 640.28 | 12.27 | 3716.16 | 0.00 | 0.00 | 0.00 |
February | 975.54 | 0.00 | 975.54 | 71.08 | 3474.48 | 0.00 | 0.00 | 0.00 |
March | 1183.06 | 0.00 | 1183.06 | 393.58 | 2495.27 | 0.00 | 0.00 | 0.00 |
April | 1507.46 | 6.02 | 1501.45 | 829.40 | 1780.29 | 0.00 | 0.00 | 0.00 |
May | 1751.60 | 74.28 | 1677.32 | 1370.28 | 1164.31 | 0.00 | 0.00 | 0.00 |
June | 2106.80 | 179.34 | 1927.46 | 2244.32 | 767.84 | 0.00 | 0.00 | 0.00 |
July | 1954.34 | 126.16 | 1828.18 | 2400.99 | 543.47 | 0.00 | 0.00 | 0.00 |
August | 1691.04 | 25.73 | 1665.32 | 1969.41 | 710.80 | 0.00 | 0.00 | 0.00 |
September | 1286.92 | 0.27 | 1286.65 | 1167.60 | 1124.59 | 0.00 | 0.00 | 0.00 |
October | 962.03 | 0.00 | 962.03 | 500.65 | 1724.78 | 0.00 | 0.00 | 0.00 |
November | 646.46 | 0.00 | 646.46 | 158.63 | 2235.39 | 0.00 | 0.00 | 0.00 |
December | 599.28 | 0.00 | 599.28 | 13.28 | 3517.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1276.64 | 34.46 | 1242.18 | 932.78 | 1930.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.28 | 0.00 | 599.28 | 12.27 | 543.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2106.80 | 179.34 | 1927.46 | 2400.99 | 3716.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 781.13 | 251.88 | 529.25 | 311.11 | 2258.41 | 0.00 | 0.00 | 0.00 |
February | 1146.16 | 343.94 | 802.23 | 553.20 | 2142.71 | 0.00 | 0.00 | 0.00 |
March | 1644.71 | 688.79 | 955.92 | 1282.17 | 1555.88 | 0.00 | 0.00 | 0.00 |
April | 2176.88 | 961.86 | 1215.02 | 2029.11 | 1154.59 | 0.00 | 0.00 | 0.00 |
May | 2438.88 | 1078.85 | 1360.04 | 2613.42 | 807.97 | 0.00 | 0.00 | 0.00 |
June | 2723.82 | 1203.80 | 1520.03 | 3265.04 | 530.74 | 0.00 | 0.00 | 0.00 |
July | 2615.59 | 1151.61 | 1463.98 | 3368.53 | 372.91 | 0.00 | 0.00 | 0.00 |
August | 2362.16 | 991.51 | 1370.65 | 2978.23 | 481.98 | 0.00 | 0.00 | 0.00 |
September | 1965.73 | 871.92 | 1093.81 | 2243.93 | 741.31 | 0.00 | 0.00 | 0.00 |
October | 1333.91 | 551.74 | 782.17 | 1196.28 | 1115.65 | 0.00 | 0.00 | 0.00 |
November | 756.62 | 242.71 | 513.90 | 480.90 | 1437.46 | 0.00 | 0.00 | 0.00 |
December | 609.12 | 125.86 | 483.26 | 164.41 | 2209.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1715.44 | 707.09 | 1008.35 | 1713.42 | 1229.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 609.12 | 125.86 | 483.26 | 164.41 | 372.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2723.82 | 1203.80 | 1520.03 | 3368.53 | 2258.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2753.21 | 1607.13 | 1146.08 | 2218.83 | 3213.44 | 0.00 | 0.00 | 0.00 |
February | 3143.47 | 1515.75 | 1627.72 | 2493.64 | 3161.83 | 0.00 | 0.00 | 0.00 |
March | 3836.82 | 2155.88 | 1680.93 | 3729.75 | 2374.25 | 0.00 | 0.00 | 0.00 |
April | 3177.49 | 1269.73 | 1907.75 | 3223.75 | 1892.41 | 0.00 | 0.00 | 0.00 |
May | 2780.58 | 807.60 | 1972.99 | 3053.46 | 1307.10 | 0.00 | 0.00 | 0.00 |
June | 2701.83 | 572.53 | 2129.30 | 3308.79 | 851.40 | 0.00 | 0.00 | 0.00 |
July | 2758.13 | 669.21 | 2088.92 | 3735.19 | 598.23 | 0.00 | 0.00 | 0.00 |
August | 3096.46 | 1003.95 | 2092.51 | 4134.53 | 770.14 | 0.00 | 0.00 | 0.00 |
September | 3600.26 | 1753.59 | 1846.66 | 4446.93 | 1194.97 | 0.00 | 0.00 | 0.00 |
October | 3444.91 | 1967.80 | 1477.11 | 3701.27 | 1742.15 | 0.00 | 0.00 | 0.00 |
November | 2467.18 | 1392.80 | 1074.37 | 2335.63 | 2181.25 | 0.00 | 0.00 | 0.00 |
December | 2302.23 | 1191.51 | 1110.72 | 1760.30 | 3142.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3004.28 | 1324.92 | 1679.36 | 3182.49 | 1862.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2302.23 | 572.53 | 1074.37 | 1760.30 | 598.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3836.82 | 2155.88 | 2129.30 | 4446.93 | 3213.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 670.20 | 157.34 | 512.86 | 187.14 | 2390.83 | 0.00 | 0.00 | 0.00 |
February | 1086.21 | 279.16 | 807.05 | 461.70 | 2269.98 | 0.00 | 0.00 | 0.00 |
March | 1702.44 | 728.94 | 973.49 | 1334.37 | 1658.19 | 0.00 | 0.00 | 0.00 |
April | 2084.41 | 854.69 | 1229.72 | 1920.33 | 1260.92 | 0.00 | 0.00 | 0.00 |
May | 2458.89 | 1111.26 | 1347.63 | 2644.65 | 887.30 | 0.00 | 0.00 | 0.00 |
June | 2966.72 | 1395.42 | 1571.30 | 3588.11 | 603.41 | 0.00 | 0.00 | 0.00 |
July | 2652.36 | 1162.89 | 1489.48 | 3416.62 | 436.12 | 0.00 | 0.00 | 0.00 |
August | 2398.91 | 1020.04 | 1378.87 | 3044.38 | 545.36 | 0.00 | 0.00 | 0.00 |
September | 1883.89 | 813.57 | 1070.32 | 2146.85 | 809.15 | 0.00 | 0.00 | 0.00 |
October | 1221.23 | 430.19 | 791.04 | 1058.76 | 1205.03 | 0.00 | 0.00 | 0.00 |
November | 723.70 | 208.55 | 515.16 | 428.24 | 1535.07 | 0.00 | 0.00 | 0.00 |
December | 627.39 | 136.70 | 490.69 | 177.62 | 2314.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1709.18 | 693.57 | 1015.61 | 1707.41 | 1321.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 627.39 | 136.70 | 490.69 | 177.62 | 436.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2966.72 | 1395.42 | 1571.30 | 3588.11 | 2390.83 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342989E+09 | 0.00 | 0.342989E+09 | 48234.98 | 0.228309E+10 |
February | 0.472013E+09 | 0.00 | 0.472013E+09 | 12657997.65 | 0.193783E+10 |
March | 0.633749E+09 | 0.00 | 0.633749E+09 | 0.166048E+09 | 0.158562E+10 |
April | 0.781477E+09 | 3118403.21 | 0.778359E+09 | 0.365233E+09 | 0.110418E+10 |
May | 0.938306E+09 | 39789500.73 | 0.898516E+09 | 0.708808E+09 | 0.685154E+09 |
June | 0.109218E+10 | 92971783.14 | 0.999207E+09 | 0.116027E+10 | 0.422815E+09 |
July | 0.104691E+10 | 67580513.96 | 0.979331E+09 | 0.128685E+10 | 0.303280E+09 |
August | 0.905870E+09 | 13780841.18 | 0.892089E+09 | 0.104893E+10 | 0.402238E+09 |
September | 0.667148E+09 | 138604.48 | 0.667009E+09 | 0.586099E+09 | 0.654707E+09 |
October | 0.515346E+09 | 0.00 | 0.515346E+09 | 0.209882E+09 | 0.113769E+10 |
November | 0.335129E+09 | 0.00 | 0.335129E+09 | 43947878.77 | 0.148185E+10 |
December | 0.321027E+09 | 0.00 | 0.321027E+09 | 1567672.14 | 0.225306E+10 |
Annual Sum or Average | 0.805214E+10 | 0.217380E+09 | 0.783476E+10 | 0.559034E+10 | 0.142515E+11 |
Minimum of Months | 0.321027E+09 | 0.00 | 0.321027E+09 | 48234.98 | 0.303280E+09 |
Maximum of Months | 0.109218E+10 | 92971783.14 | 0.999207E+09 | 0.128685E+10 | 0.228309E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342988E+09 | 0.00 | 0.342988E+09 | 48233.60 | 0.228309E+10 |
February | 0.472013E+09 | 0.00 | 0.472013E+09 | 12657896.98 | 0.193783E+10 |
March | 0.633749E+09 | 0.00 | 0.633749E+09 | 0.166047E+09 | 0.158562E+10 |
April | 0.781476E+09 | 3118399.47 | 0.778358E+09 | 0.365233E+09 | 0.110418E+10 |
May | 0.938305E+09 | 39789452.98 | 0.898516E+09 | 0.708807E+09 | 0.685154E+09 |
June | 0.109218E+10 | 92971671.58 | 0.999206E+09 | 0.116027E+10 | 0.422815E+09 |
July | 0.104691E+10 | 67580432.87 | 0.979331E+09 | 0.128685E+10 | 0.303280E+09 |
August | 0.905869E+09 | 13780824.64 | 0.892088E+09 | 0.104893E+10 | 0.402238E+09 |
September | 0.667148E+09 | 138604.32 | 0.667009E+09 | 0.586099E+09 | 0.654707E+09 |
October | 0.515345E+09 | 0.00 | 0.515345E+09 | 0.209882E+09 | 0.113769E+10 |
November | 0.335128E+09 | 0.00 | 0.335128E+09 | 43947757.88 | 0.148185E+10 |
December | 0.321027E+09 | 0.00 | 0.321027E+09 | 1567662.33 | 0.225306E+10 |
Annual Sum or Average | 0.805214E+10 | 0.217379E+09 | 0.783476E+10 | 0.559033E+10 | 0.142515E+11 |
Minimum of Months | 0.321027E+09 | 0.00 | 0.321027E+09 | 48233.60 | 0.303280E+09 |
Maximum of Months | 0.109218E+10 | 92971671.58 | 0.999206E+09 | 0.128685E+10 | 0.228309E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342989E+09 | 0.00 | 0.342989E+09 | 48234.98 | 0.228309E+10 |
February | 0.472013E+09 | 0.00 | 0.472013E+09 | 12657997.65 | 0.193783E+10 |
March | 0.633749E+09 | 0.00 | 0.633749E+09 | 0.166048E+09 | 0.158562E+10 |
April | 0.781477E+09 | 3118403.21 | 0.778359E+09 | 0.365233E+09 | 0.110418E+10 |
May | 0.938306E+09 | 39789500.73 | 0.898516E+09 | 0.708808E+09 | 0.685154E+09 |
June | 0.109218E+10 | 92971783.14 | 0.999207E+09 | 0.116027E+10 | 0.422815E+09 |
July | 0.104691E+10 | 67580513.96 | 0.979331E+09 | 0.128685E+10 | 0.303280E+09 |
August | 0.905870E+09 | 13780841.18 | 0.892089E+09 | 0.104893E+10 | 0.402238E+09 |
September | 0.667148E+09 | 138604.48 | 0.667009E+09 | 0.586099E+09 | 0.654707E+09 |
October | 0.515346E+09 | 0.00 | 0.515346E+09 | 0.209882E+09 | 0.113769E+10 |
November | 0.335129E+09 | 0.00 | 0.335129E+09 | 43947878.77 | 0.148185E+10 |
December | 0.321027E+09 | 0.00 | 0.321027E+09 | 1567672.14 | 0.225306E+10 |
Annual Sum or Average | 0.805214E+10 | 0.217380E+09 | 0.783476E+10 | 0.559034E+10 | 0.142515E+11 |
Minimum of Months | 0.321027E+09 | 0.00 | 0.321027E+09 | 48234.98 | 0.303280E+09 |
Maximum of Months | 0.109218E+10 | 92971783.14 | 0.999207E+09 | 0.128685E+10 | 0.228309E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342988E+09 | 0.00 | 0.342988E+09 | 48233.60 | 0.228309E+10 |
February | 0.472013E+09 | 0.00 | 0.472013E+09 | 12657896.98 | 0.193783E+10 |
March | 0.633749E+09 | 0.00 | 0.633749E+09 | 0.166047E+09 | 0.158562E+10 |
April | 0.781476E+09 | 3118399.47 | 0.778358E+09 | 0.365233E+09 | 0.110418E+10 |
May | 0.938305E+09 | 39789452.98 | 0.898516E+09 | 0.708807E+09 | 0.685154E+09 |
June | 0.109218E+10 | 92971671.58 | 0.999206E+09 | 0.116027E+10 | 0.422815E+09 |
July | 0.104691E+10 | 67580432.87 | 0.979331E+09 | 0.128685E+10 | 0.303280E+09 |
August | 0.905869E+09 | 13780824.64 | 0.892088E+09 | 0.104893E+10 | 0.402238E+09 |
September | 0.667148E+09 | 138604.32 | 0.667009E+09 | 0.586099E+09 | 0.654707E+09 |
October | 0.515345E+09 | 0.00 | 0.515345E+09 | 0.209882E+09 | 0.113769E+10 |
November | 0.335128E+09 | 0.00 | 0.335128E+09 | 43947757.88 | 0.148185E+10 |
December | 0.321027E+09 | 0.00 | 0.321027E+09 | 1567662.33 | 0.225306E+10 |
Annual Sum or Average | 0.805214E+10 | 0.217379E+09 | 0.783476E+10 | 0.559033E+10 | 0.142515E+11 |
Minimum of Months | 0.321027E+09 | 0.00 | 0.321027E+09 | 48233.60 | 0.303280E+09 |
Maximum of Months | 0.109218E+10 | 92971671.58 | 0.999206E+09 | 0.128685E+10 | 0.228309E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342975E+09 | 0.00 | 0.342975E+09 | 48233.04 | 0.228300E+10 |
February | 0.471994E+09 | 0.00 | 0.471994E+09 | 12657487.47 | 0.193775E+10 |
March | 0.633724E+09 | 0.00 | 0.633724E+09 | 0.166041E+09 | 0.158555E+10 |
April | 0.781446E+09 | 3118277.53 | 0.778327E+09 | 0.365219E+09 | 0.110414E+10 |
May | 0.938268E+09 | 39787897.04 | 0.898480E+09 | 0.708779E+09 | 0.685126E+09 |
June | 0.109213E+10 | 92968035.97 | 0.999166E+09 | 0.116022E+10 | 0.422798E+09 |
July | 0.104687E+10 | 67577790.16 | 0.979292E+09 | 0.128680E+10 | 0.303268E+09 |
August | 0.905833E+09 | 13780285.75 | 0.892053E+09 | 0.104889E+10 | 0.402222E+09 |
September | 0.667121E+09 | 138598.90 | 0.666983E+09 | 0.586076E+09 | 0.654680E+09 |
October | 0.515325E+09 | 0.00 | 0.515325E+09 | 0.209874E+09 | 0.113764E+10 |
November | 0.335115E+09 | 0.00 | 0.335115E+09 | 43946107.48 | 0.148179E+10 |
December | 0.321014E+09 | 0.00 | 0.321014E+09 | 1567608.95 | 0.225297E+10 |
Annual Sum or Average | 0.805182E+10 | 0.217371E+09 | 0.783445E+10 | 0.559011E+10 | 0.142509E+11 |
Minimum of Months | 0.321014E+09 | 0.00 | 0.321014E+09 | 48233.04 | 0.303268E+09 |
Maximum of Months | 0.109213E+10 | 92968035.97 | 0.999166E+09 | 0.128680E+10 | 0.228300E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.697404E+09 | 0.224882E+09 | 0.472522E+09 | 0.247967E+09 | 0.230772E+10 |
February | 0.924275E+09 | 0.277352E+09 | 0.646923E+09 | 0.399885E+09 | 0.196280E+10 |
March | 0.146841E+10 | 0.614962E+09 | 0.853451E+09 | 0.109709E+10 | 0.159881E+10 |
April | 0.188084E+10 | 0.831058E+09 | 0.104979E+10 | 0.171677E+10 | 0.112745E+10 |
May | 0.217746E+10 | 0.963207E+09 | 0.121425E+10 | 0.234224E+10 | 0.767489E+09 |
June | 0.235341E+10 | 0.104009E+10 | 0.131332E+10 | 0.284736E+10 | 0.472954E+09 |
July | 0.233522E+10 | 0.102816E+10 | 0.130705E+10 | 0.303717E+10 | 0.331500E+09 |
August | 0.210896E+10 | 0.885226E+09 | 0.122373E+10 | 0.268587E+10 | 0.429412E+09 |
September | 0.169841E+10 | 0.753348E+09 | 0.945059E+09 | 0.194204E+10 | 0.691339E+09 |
October | 0.119093E+10 | 0.492599E+09 | 0.698327E+09 | 0.102014E+10 | 0.117162E+10 |
November | 0.653724E+09 | 0.209707E+09 | 0.444017E+09 | 0.363476E+09 | 0.152921E+10 |
December | 0.543824E+09 | 0.112366E+09 | 0.431458E+09 | 0.122405E+09 | 0.230028E+10 |
Annual Sum or Average | 0.180329E+11 | 0.743296E+10 | 0.105999E+11 | 0.178224E+11 | 0.146906E+11 |
Minimum of Months | 0.543824E+09 | 0.112366E+09 | 0.431458E+09 | 0.122405E+09 | 0.331500E+09 |
Maximum of Months | 0.235341E+10 | 0.104009E+10 | 0.131332E+10 | 0.303717E+10 | 0.230772E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.697404E+09 | 0.224882E+09 | 0.472522E+09 | 0.247967E+09 | 0.230772E+10 |
February | 0.924275E+09 | 0.277352E+09 | 0.646923E+09 | 0.399885E+09 | 0.196280E+10 |
March | 0.146841E+10 | 0.614962E+09 | 0.853451E+09 | 0.109709E+10 | 0.159881E+10 |
April | 0.188084E+10 | 0.831058E+09 | 0.104979E+10 | 0.171677E+10 | 0.112745E+10 |
May | 0.217746E+10 | 0.963207E+09 | 0.121425E+10 | 0.234224E+10 | 0.767489E+09 |
June | 0.235341E+10 | 0.104009E+10 | 0.131332E+10 | 0.284736E+10 | 0.472954E+09 |
July | 0.233522E+10 | 0.102816E+10 | 0.130705E+10 | 0.303717E+10 | 0.331500E+09 |
August | 0.210896E+10 | 0.885226E+09 | 0.122373E+10 | 0.268587E+10 | 0.429412E+09 |
September | 0.169841E+10 | 0.753348E+09 | 0.945059E+09 | 0.194204E+10 | 0.691339E+09 |
October | 0.119093E+10 | 0.492599E+09 | 0.698327E+09 | 0.102014E+10 | 0.117162E+10 |
November | 0.653724E+09 | 0.209707E+09 | 0.444017E+09 | 0.363476E+09 | 0.152921E+10 |
December | 0.543824E+09 | 0.112366E+09 | 0.431458E+09 | 0.122405E+09 | 0.230028E+10 |
Annual Sum or Average | 0.180329E+11 | 0.743296E+10 | 0.105999E+11 | 0.178224E+11 | 0.146906E+11 |
Minimum of Months | 0.543824E+09 | 0.112366E+09 | 0.431458E+09 | 0.122405E+09 | 0.331500E+09 |
Maximum of Months | 0.235341E+10 | 0.104009E+10 | 0.131332E+10 | 0.303717E+10 | 0.230772E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.697391E+09 | 0.224878E+09 | 0.472513E+09 | 0.247963E+09 | 0.230768E+10 |
February | 0.924258E+09 | 0.277347E+09 | 0.646911E+09 | 0.399878E+09 | 0.196276E+10 |
March | 0.146839E+10 | 0.614951E+09 | 0.853435E+09 | 0.109707E+10 | 0.159878E+10 |
April | 0.188081E+10 | 0.831042E+09 | 0.104977E+10 | 0.171674E+10 | 0.112743E+10 |
May | 0.217742E+10 | 0.963189E+09 | 0.121423E+10 | 0.234219E+10 | 0.767475E+09 |
June | 0.235336E+10 | 0.104007E+10 | 0.131329E+10 | 0.284731E+10 | 0.472945E+09 |
July | 0.233518E+10 | 0.102815E+10 | 0.130703E+10 | 0.303711E+10 | 0.331494E+09 |
August | 0.210892E+10 | 0.885210E+09 | 0.122371E+10 | 0.268582E+10 | 0.429404E+09 |
September | 0.169838E+10 | 0.753334E+09 | 0.945041E+09 | 0.194201E+10 | 0.691326E+09 |
October | 0.119090E+10 | 0.492590E+09 | 0.698315E+09 | 0.102012E+10 | 0.117160E+10 |
November | 0.653712E+09 | 0.209703E+09 | 0.444009E+09 | 0.363469E+09 | 0.152918E+10 |
December | 0.543814E+09 | 0.112364E+09 | 0.431450E+09 | 0.122403E+09 | 0.230024E+10 |
Annual Sum or Average | 0.180325E+11 | 0.743283E+10 | 0.105997E+11 | 0.178221E+11 | 0.146903E+11 |
Minimum of Months | 0.543814E+09 | 0.112364E+09 | 0.431450E+09 | 0.122403E+09 | 0.331494E+09 |
Maximum of Months | 0.235336E+10 | 0.104007E+10 | 0.131329E+10 | 0.303711E+10 | 0.230768E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147486E+10 | 0.860917E+09 | 0.613939E+09 | 0.116447E+10 | 0.189275E+10 |
February | 0.152096E+10 | 0.733392E+09 | 0.787564E+09 | 0.117941E+10 | 0.167559E+10 |
March | 0.205533E+10 | 0.115488E+10 | 0.900453E+09 | 0.198049E+10 | 0.141109E+10 |
April | 0.164723E+10 | 0.658238E+09 | 0.988992E+09 | 0.165186E+10 | 0.109331E+10 |
May | 0.148952E+10 | 0.432620E+09 | 0.105690E+10 | 0.164371E+10 | 0.744288E+09 |
June | 0.140065E+10 | 0.296804E+09 | 0.110384E+10 | 0.173013E+10 | 0.464140E+09 |
July | 0.147749E+10 | 0.358488E+09 | 0.111901E+10 | 0.201807E+10 | 0.329780E+09 |
August | 0.165873E+10 | 0.537802E+09 | 0.112093E+10 | 0.223139E+10 | 0.425903E+09 |
September | 0.186640E+10 | 0.909074E+09 | 0.957322E+09 | 0.231889E+10 | 0.658282E+09 |
October | 0.184539E+10 | 0.105412E+10 | 0.791269E+09 | 0.196703E+10 | 0.105047E+10 |
November | 0.127900E+10 | 0.722038E+09 | 0.556961E+09 | 0.117834E+10 | 0.131532E+10 |
December | 0.123327E+10 | 0.638274E+09 | 0.594998E+09 | 0.910913E+09 | 0.190084E+10 |
Annual Sum or Average | 0.189488E+11 | 0.835665E+10 | 0.105922E+11 | 0.199747E+11 | 0.129618E+11 |
Minimum of Months | 0.123327E+10 | 0.296804E+09 | 0.556961E+09 | 0.910913E+09 | 0.329780E+09 |
Maximum of Months | 0.205533E+10 | 0.115488E+10 | 0.112093E+10 | 0.231889E+10 | 0.190084E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147485E+10 | 0.860916E+09 | 0.613938E+09 | 0.116446E+10 | 0.189275E+10 |
February | 0.152095E+10 | 0.733391E+09 | 0.787563E+09 | 0.117940E+10 | 0.167559E+10 |
March | 0.205533E+10 | 0.115488E+10 | 0.900452E+09 | 0.198049E+10 | 0.141109E+10 |
April | 0.164723E+10 | 0.658237E+09 | 0.988991E+09 | 0.165186E+10 | 0.109331E+10 |
May | 0.148952E+10 | 0.432619E+09 | 0.105690E+10 | 0.164370E+10 | 0.744288E+09 |
June | 0.140065E+10 | 0.296804E+09 | 0.110384E+10 | 0.173013E+10 | 0.464140E+09 |
July | 0.147749E+10 | 0.358488E+09 | 0.111900E+10 | 0.201807E+10 | 0.329780E+09 |
August | 0.165873E+10 | 0.537801E+09 | 0.112093E+10 | 0.223138E+10 | 0.425903E+09 |
September | 0.186639E+10 | 0.909072E+09 | 0.957322E+09 | 0.231888E+10 | 0.658282E+09 |
October | 0.184539E+10 | 0.105412E+10 | 0.791268E+09 | 0.196702E+10 | 0.105047E+10 |
November | 0.127900E+10 | 0.722037E+09 | 0.556961E+09 | 0.117834E+10 | 0.131532E+10 |
December | 0.123327E+10 | 0.638273E+09 | 0.594997E+09 | 0.910912E+09 | 0.190084E+10 |
Annual Sum or Average | 0.189488E+11 | 0.835664E+10 | 0.105922E+11 | 0.199747E+11 | 0.129618E+11 |
Minimum of Months | 0.123327E+10 | 0.296804E+09 | 0.556961E+09 | 0.910912E+09 | 0.329780E+09 |
Maximum of Months | 0.205533E+10 | 0.115488E+10 | 0.112093E+10 | 0.231888E+10 | 0.190084E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147486E+10 | 0.860917E+09 | 0.613939E+09 | 0.116447E+10 | 0.189275E+10 |
February | 0.152096E+10 | 0.733392E+09 | 0.787564E+09 | 0.117941E+10 | 0.167559E+10 |
March | 0.205533E+10 | 0.115488E+10 | 0.900453E+09 | 0.198049E+10 | 0.141109E+10 |
April | 0.164723E+10 | 0.658238E+09 | 0.988992E+09 | 0.165186E+10 | 0.109331E+10 |
May | 0.148952E+10 | 0.432620E+09 | 0.105690E+10 | 0.164371E+10 | 0.744288E+09 |
June | 0.140065E+10 | 0.296804E+09 | 0.110384E+10 | 0.173013E+10 | 0.464140E+09 |
July | 0.147749E+10 | 0.358488E+09 | 0.111901E+10 | 0.201807E+10 | 0.329780E+09 |
August | 0.165873E+10 | 0.537802E+09 | 0.112093E+10 | 0.223139E+10 | 0.425903E+09 |
September | 0.186640E+10 | 0.909074E+09 | 0.957322E+09 | 0.231889E+10 | 0.658282E+09 |
October | 0.184539E+10 | 0.105412E+10 | 0.791269E+09 | 0.196703E+10 | 0.105047E+10 |
November | 0.127900E+10 | 0.722038E+09 | 0.556961E+09 | 0.117834E+10 | 0.131532E+10 |
December | 0.123327E+10 | 0.638274E+09 | 0.594998E+09 | 0.910913E+09 | 0.190084E+10 |
Annual Sum or Average | 0.189488E+11 | 0.835665E+10 | 0.105922E+11 | 0.199747E+11 | 0.129618E+11 |
Minimum of Months | 0.123327E+10 | 0.296804E+09 | 0.556961E+09 | 0.910913E+09 | 0.329780E+09 |
Maximum of Months | 0.205533E+10 | 0.115488E+10 | 0.112093E+10 | 0.231889E+10 | 0.190084E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147485E+10 | 0.860916E+09 | 0.613938E+09 | 0.116446E+10 | 0.189275E+10 |
February | 0.152095E+10 | 0.733391E+09 | 0.787563E+09 | 0.117940E+10 | 0.167559E+10 |
March | 0.205533E+10 | 0.115488E+10 | 0.900452E+09 | 0.198049E+10 | 0.141109E+10 |
April | 0.164723E+10 | 0.658237E+09 | 0.988991E+09 | 0.165186E+10 | 0.109331E+10 |
May | 0.148952E+10 | 0.432619E+09 | 0.105690E+10 | 0.164370E+10 | 0.744288E+09 |
June | 0.140065E+10 | 0.296804E+09 | 0.110384E+10 | 0.173013E+10 | 0.464140E+09 |
July | 0.147749E+10 | 0.358488E+09 | 0.111900E+10 | 0.201807E+10 | 0.329780E+09 |
August | 0.165873E+10 | 0.537801E+09 | 0.112093E+10 | 0.223138E+10 | 0.425903E+09 |
September | 0.186639E+10 | 0.909072E+09 | 0.957322E+09 | 0.231888E+10 | 0.658282E+09 |
October | 0.184539E+10 | 0.105412E+10 | 0.791268E+09 | 0.196702E+10 | 0.105047E+10 |
November | 0.127900E+10 | 0.722037E+09 | 0.556961E+09 | 0.117834E+10 | 0.131532E+10 |
December | 0.123327E+10 | 0.638273E+09 | 0.594997E+09 | 0.910912E+09 | 0.190084E+10 |
Annual Sum or Average | 0.189488E+11 | 0.835664E+10 | 0.105922E+11 | 0.199747E+11 | 0.129618E+11 |
Minimum of Months | 0.123327E+10 | 0.296804E+09 | 0.556961E+09 | 0.910912E+09 | 0.329780E+09 |
Maximum of Months | 0.205533E+10 | 0.115488E+10 | 0.112093E+10 | 0.231888E+10 | 0.190084E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147480E+10 | 0.860882E+09 | 0.613914E+09 | 0.116442E+10 | 0.189267E+10 |
February | 0.152089E+10 | 0.733362E+09 | 0.787532E+09 | 0.117936E+10 | 0.167552E+10 |
March | 0.205525E+10 | 0.115483E+10 | 0.900417E+09 | 0.198041E+10 | 0.141104E+10 |
April | 0.164716E+10 | 0.658211E+09 | 0.988952E+09 | 0.165179E+10 | 0.109327E+10 |
May | 0.148946E+10 | 0.432602E+09 | 0.105686E+10 | 0.164364E+10 | 0.744258E+09 |
June | 0.140059E+10 | 0.296792E+09 | 0.110380E+10 | 0.173006E+10 | 0.464121E+09 |
July | 0.147743E+10 | 0.358474E+09 | 0.111896E+10 | 0.201799E+10 | 0.329767E+09 |
August | 0.165866E+10 | 0.537780E+09 | 0.112088E+10 | 0.223130E+10 | 0.425886E+09 |
September | 0.186632E+10 | 0.909037E+09 | 0.957284E+09 | 0.231879E+10 | 0.658255E+09 |
October | 0.184532E+10 | 0.105408E+10 | 0.791237E+09 | 0.196695E+10 | 0.105043E+10 |
November | 0.127895E+10 | 0.722009E+09 | 0.556939E+09 | 0.117830E+10 | 0.131527E+10 |
December | 0.123322E+10 | 0.638249E+09 | 0.594974E+09 | 0.910877E+09 | 0.190077E+10 |
Annual Sum or Average | 0.189481E+11 | 0.835631E+10 | 0.105917E+11 | 0.199739E+11 | 0.129613E+11 |
Minimum of Months | 0.123322E+10 | 0.296792E+09 | 0.556939E+09 | 0.910877E+09 | 0.329767E+09 |
Maximum of Months | 0.205525E+10 | 0.115483E+10 | 0.112088E+10 | 0.231879E+10 | 0.190077E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.598360E+09 | 0.140472E+09 | 0.457889E+09 | 0.144923E+09 | 0.250343E+10 |
February | 0.875928E+09 | 0.225120E+09 | 0.650808E+09 | 0.323073E+09 | 0.217624E+10 |
March | 0.151995E+10 | 0.650808E+09 | 0.869145E+09 | 0.112642E+10 | 0.181505E+10 |
April | 0.180095E+10 | 0.738460E+09 | 0.106249E+10 | 0.158510E+10 | 0.134452E+10 |
May | 0.219532E+10 | 0.992142E+09 | 0.120318E+10 | 0.235377E+10 | 0.876164E+09 |
June | 0.256328E+10 | 0.120566E+10 | 0.135762E+10 | 0.310628E+10 | 0.577779E+09 |
July | 0.236805E+10 | 0.103824E+10 | 0.132982E+10 | 0.304488E+10 | 0.438474E+09 |
August | 0.214177E+10 | 0.910699E+09 | 0.123107E+10 | 0.269811E+10 | 0.563457E+09 |
September | 0.162769E+10 | 0.702930E+09 | 0.924764E+09 | 0.184321E+10 | 0.788224E+09 |
October | 0.109032E+10 | 0.384073E+09 | 0.706247E+09 | 0.880002E+09 | 0.134018E+10 |
November | 0.625285E+09 | 0.180185E+09 | 0.445100E+09 | 0.313941E+09 | 0.175970E+10 |
December | 0.560136E+09 | 0.122047E+09 | 0.438088E+09 | 0.127134E+09 | 0.264456E+10 |
Annual Sum or Average | 0.179670E+11 | 0.729083E+10 | 0.106762E+11 | 0.175468E+11 | 0.168278E+11 |
Minimum of Months | 0.560136E+09 | 0.122047E+09 | 0.438088E+09 | 0.127134E+09 | 0.438474E+09 |
Maximum of Months | 0.256328E+10 | 0.120566E+10 | 0.135762E+10 | 0.310628E+10 | 0.264456E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.598360E+09 | 0.140472E+09 | 0.457889E+09 | 0.144923E+09 | 0.250343E+10 |
February | 0.875928E+09 | 0.225120E+09 | 0.650808E+09 | 0.323073E+09 | 0.217624E+10 |
March | 0.151995E+10 | 0.650808E+09 | 0.869145E+09 | 0.112642E+10 | 0.181505E+10 |
April | 0.180095E+10 | 0.738460E+09 | 0.106249E+10 | 0.158510E+10 | 0.134452E+10 |
May | 0.219532E+10 | 0.992142E+09 | 0.120318E+10 | 0.235377E+10 | 0.876164E+09 |
June | 0.256328E+10 | 0.120566E+10 | 0.135762E+10 | 0.310628E+10 | 0.577779E+09 |
July | 0.236805E+10 | 0.103824E+10 | 0.132982E+10 | 0.304488E+10 | 0.438474E+09 |
August | 0.214177E+10 | 0.910699E+09 | 0.123107E+10 | 0.269811E+10 | 0.563457E+09 |
September | 0.162769E+10 | 0.702930E+09 | 0.924764E+09 | 0.184321E+10 | 0.788224E+09 |
October | 0.109032E+10 | 0.384073E+09 | 0.706247E+09 | 0.880002E+09 | 0.134018E+10 |
November | 0.625285E+09 | 0.180185E+09 | 0.445100E+09 | 0.313941E+09 | 0.175970E+10 |
December | 0.560136E+09 | 0.122047E+09 | 0.438088E+09 | 0.127134E+09 | 0.264456E+10 |
Annual Sum or Average | 0.179670E+11 | 0.729083E+10 | 0.106762E+11 | 0.175468E+11 | 0.168278E+11 |
Minimum of Months | 0.560136E+09 | 0.122047E+09 | 0.438088E+09 | 0.127134E+09 | 0.438474E+09 |
Maximum of Months | 0.256328E+10 | 0.120566E+10 | 0.135762E+10 | 0.310628E+10 | 0.264456E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.598349E+09 | 0.140469E+09 | 0.457880E+09 | 0.144921E+09 | 0.250339E+10 |
February | 0.875912E+09 | 0.225116E+09 | 0.650796E+09 | 0.323067E+09 | 0.217620E+10 |
March | 0.151993E+10 | 0.650797E+09 | 0.869129E+09 | 0.112640E+10 | 0.181502E+10 |
April | 0.180091E+10 | 0.738447E+09 | 0.106247E+10 | 0.158507E+10 | 0.134449E+10 |
May | 0.219528E+10 | 0.992124E+09 | 0.120315E+10 | 0.235373E+10 | 0.876148E+09 |
June | 0.256323E+10 | 0.120564E+10 | 0.135759E+10 | 0.310622E+10 | 0.577768E+09 |
July | 0.236801E+10 | 0.103822E+10 | 0.132979E+10 | 0.304482E+10 | 0.438466E+09 |
August | 0.214173E+10 | 0.910683E+09 | 0.123104E+10 | 0.269806E+10 | 0.563447E+09 |
September | 0.162766E+10 | 0.702917E+09 | 0.924747E+09 | 0.184317E+10 | 0.788210E+09 |
October | 0.109030E+10 | 0.384066E+09 | 0.706234E+09 | 0.879985E+09 | 0.134015E+10 |
November | 0.625274E+09 | 0.180182E+09 | 0.445092E+09 | 0.313935E+09 | 0.175966E+10 |
December | 0.560125E+09 | 0.122045E+09 | 0.438080E+09 | 0.127132E+09 | 0.264451E+10 |
Annual Sum or Average | 0.179667E+11 | 0.729070E+10 | 0.106760E+11 | 0.175465E+11 | 0.168275E+11 |
Minimum of Months | 0.560125E+09 | 0.122045E+09 | 0.438080E+09 | 0.127132E+09 | 0.438466E+09 |
Maximum of Months | 0.256323E+10 | 0.120564E+10 | 0.135759E+10 | 0.310622E+10 | 0.264451E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171492E+10 | 0.00 | 0.171492E+10 | 14839454.69 | 0.103262E+11 |
February | 0.236004E+10 | 0.00 | 0.236004E+10 | 0.132736E+09 | 0.875271E+10 |
March | 0.316871E+10 | 0.00 | 0.316871E+10 | 0.971584E+09 | 0.712406E+10 |
April | 0.390734E+10 | 15591827.53 | 0.389175E+10 | 0.202155E+10 | 0.495746E+10 |
May | 0.469147E+10 | 0.198945E+09 | 0.449253E+10 | 0.361407E+10 | 0.325493E+10 |
June | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.584700E+10 | 0.201606E+10 |
July | 0.523450E+10 | 0.337898E+09 | 0.489660E+10 | 0.649715E+10 | 0.144741E+10 |
August | 0.452929E+10 | 68903372.72 | 0.446039E+10 | 0.531056E+10 | 0.192270E+10 |
September | 0.333570E+10 | 693014.03 | 0.333501E+10 | 0.299273E+10 | 0.305765E+10 |
October | 0.257670E+10 | 0.00 | 0.257670E+10 | 0.120254E+10 | 0.509177E+10 |
November | 0.167562E+10 | 0.00 | 0.167562E+10 | 0.325604E+09 | 0.639161E+10 |
December | 0.160512E+10 | 0.00 | 0.160512E+10 | 22044245.29 | 0.990597E+10 |
Annual Sum or Average | 0.402602E+11 | 0.108689E+10 | 0.391733E+11 | 0.289524E+11 | 0.642485E+11 |
Minimum of Months | 0.160512E+10 | 0.00 | 0.160512E+10 | 14839454.69 | 0.144741E+10 |
Maximum of Months | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.649715E+10 | 0.103262E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209219E+10 | 0.674639E+09 | 0.141755E+10 | 0.800694E+09 | 0.626841E+10 |
February | 0.277280E+10 | 0.832048E+09 | 0.194075E+10 | 0.128489E+10 | 0.539299E+10 |
March | 0.440520E+10 | 0.184487E+10 | 0.256033E+10 | 0.333762E+10 | 0.446495E+10 |
April | 0.564247E+10 | 0.249315E+10 | 0.314932E+10 | 0.515927E+10 | 0.319764E+10 |
May | 0.653231E+10 | 0.288959E+10 | 0.364272E+10 | 0.697085E+10 | 0.224398E+10 |
June | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.847670E+10 | 0.139172E+10 |
July | 0.700558E+10 | 0.308446E+10 | 0.392112E+10 | 0.905157E+10 | 0.994732E+09 |
August | 0.632681E+10 | 0.265565E+10 | 0.367116E+10 | 0.799134E+10 | 0.130334E+10 |
September | 0.509517E+10 | 0.226002E+10 | 0.283515E+10 | 0.579010E+10 | 0.200180E+10 |
October | 0.357274E+10 | 0.147778E+10 | 0.209496E+10 | 0.309018E+10 | 0.327876E+10 |
November | 0.196115E+10 | 0.629115E+09 | 0.133204E+10 | 0.115621E+10 | 0.412327E+10 |
December | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.415153E+09 | 0.620399E+10 |
Annual Sum or Average | 0.540980E+11 | 0.222987E+11 | 0.317994E+11 | 0.535246E+11 | 0.408656E+11 |
Minimum of Months | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.415153E+09 | 0.994732E+09 |
Maximum of Months | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.905157E+10 | 0.626841E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.737419E+10 | 0.430453E+10 | 0.306966E+10 | 0.586129E+10 | 0.900044E+10 |
February | 0.760469E+10 | 0.366691E+10 | 0.393777E+10 | 0.593752E+10 | 0.800207E+10 |
March | 0.102765E+11 | 0.577432E+10 | 0.450221E+10 | 0.986858E+10 | 0.679565E+10 |
April | 0.823605E+10 | 0.329115E+10 | 0.494490E+10 | 0.825308E+10 | 0.523295E+10 |
May | 0.744752E+10 | 0.216307E+10 | 0.528444E+10 | 0.816062E+10 | 0.364384E+10 |
June | 0.700315E+10 | 0.148400E+10 | 0.551915E+10 | 0.862005E+10 | 0.224112E+10 |
July | 0.738738E+10 | 0.179242E+10 | 0.559496E+10 | 0.100748E+11 | 0.159839E+10 |
August | 0.829355E+10 | 0.268898E+10 | 0.560457E+10 | 0.111241E+11 | 0.208416E+10 |
September | 0.933187E+10 | 0.454531E+10 | 0.478655E+10 | 0.115219E+11 | 0.322083E+10 |
October | 0.922686E+10 | 0.527056E+10 | 0.395630E+10 | 0.978346E+10 | 0.508045E+10 |
November | 0.639492E+10 | 0.361015E+10 | 0.278477E+10 | 0.591362E+10 | 0.621770E+10 |
December | 0.616629E+10 | 0.319133E+10 | 0.297495E+10 | 0.462148E+10 | 0.888894E+10 |
Annual Sum or Average | 0.947430E+11 | 0.417827E+11 | 0.529602E+11 | 0.997405E+11 | 0.620065E+11 |
Minimum of Months | 0.616629E+10 | 0.148400E+10 | 0.278477E+10 | 0.462148E+10 | 0.159839E+10 |
Maximum of Months | 0.102765E+11 | 0.577432E+10 | 0.560457E+10 | 0.115219E+11 | 0.900044E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179506E+10 | 0.421410E+09 | 0.137365E+10 | 0.479985E+09 | 0.665064E+10 |
February | 0.262776E+10 | 0.675353E+09 | 0.195240E+10 | 0.108639E+10 | 0.569891E+10 |
March | 0.455981E+10 | 0.195241E+10 | 0.260741E+10 | 0.352330E+10 | 0.470368E+10 |
April | 0.540278E+10 | 0.221536E+10 | 0.318742E+10 | 0.491816E+10 | 0.346522E+10 |
May | 0.658589E+10 | 0.297640E+10 | 0.360949E+10 | 0.707994E+10 | 0.246400E+10 |
June | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.934020E+10 | 0.158889E+10 |
July | 0.710409E+10 | 0.311468E+10 | 0.398941E+10 | 0.920255E+10 | 0.117213E+10 |
August | 0.642523E+10 | 0.273207E+10 | 0.369316E+10 | 0.818972E+10 | 0.147688E+10 |
September | 0.488303E+10 | 0.210877E+10 | 0.277426E+10 | 0.556171E+10 | 0.217707E+10 |
October | 0.327093E+10 | 0.115221E+10 | 0.211872E+10 | 0.276329E+10 | 0.348904E+10 |
November | 0.187584E+10 | 0.540549E+09 | 0.133529E+10 | 0.105260E+10 | 0.431814E+10 |
December | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.455330E+09 | 0.648195E+10 |
Annual Sum or Average | 0.539006E+11 | 0.218723E+11 | 0.320283E+11 | 0.536532E+11 | 0.436866E+11 |
Minimum of Months | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.455330E+09 | 0.117213E+10 |
Maximum of Months | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.934020E+10 | 0.665064E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171492E+10 | 0.00 | 0.171492E+10 | 32871608.83 | 0.995337E+10 |
February | 0.236004E+10 | 0.00 | 0.236004E+10 | 0.171951E+09 | 0.840547E+10 |
March | 0.316871E+10 | 0.00 | 0.316871E+10 | 0.105417E+10 | 0.668334E+10 |
April | 0.390734E+10 | 15591827.53 | 0.389175E+10 | 0.214981E+10 | 0.461452E+10 |
May | 0.469147E+10 | 0.198945E+09 | 0.449253E+10 | 0.367016E+10 | 0.311849E+10 |
June | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.581727E+10 | 0.199024E+10 |
July | 0.523450E+10 | 0.337898E+09 | 0.489660E+10 | 0.643082E+10 | 0.145562E+10 |
August | 0.452929E+10 | 68903372.72 | 0.446039E+10 | 0.527485E+10 | 0.190380E+10 |
September | 0.333570E+10 | 693014.03 | 0.333501E+10 | 0.302641E+10 | 0.291495E+10 |
October | 0.257670E+10 | 0.00 | 0.257670E+10 | 0.134095E+10 | 0.461965E+10 |
November | 0.167562E+10 | 0.00 | 0.167562E+10 | 0.411176E+09 | 0.579413E+10 |
December | 0.160512E+10 | 0.00 | 0.160512E+10 | 35561773.98 | 0.942102E+10 |
Annual Sum or Average | 0.402602E+11 | 0.108689E+10 | 0.391733E+11 | 0.294160E+11 | 0.608746E+11 |
Minimum of Months | 0.160512E+10 | 0.00 | 0.160512E+10 | 32871608.83 | 0.145562E+10 |
Maximum of Months | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.643082E+10 | 0.995337E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209219E+10 | 0.674639E+09 | 0.141755E+10 | 0.833282E+09 | 0.604892E+10 |
February | 0.277280E+10 | 0.832048E+09 | 0.194075E+10 | 0.133831E+10 | 0.518365E+10 |
March | 0.440520E+10 | 0.184487E+10 | 0.256033E+10 | 0.343416E+10 | 0.416727E+10 |
April | 0.564247E+10 | 0.249315E+10 | 0.314932E+10 | 0.525944E+10 | 0.299270E+10 |
May | 0.653231E+10 | 0.288959E+10 | 0.364272E+10 | 0.699977E+10 | 0.216406E+10 |
June | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.846298E+10 | 0.137567E+10 |
July | 0.700558E+10 | 0.308446E+10 | 0.392112E+10 | 0.902226E+10 | 0.998808E+09 |
August | 0.632681E+10 | 0.265565E+10 | 0.367116E+10 | 0.797690E+10 | 0.129092E+10 |
September | 0.509517E+10 | 0.226002E+10 | 0.283515E+10 | 0.581626E+10 | 0.192147E+10 |
October | 0.357274E+10 | 0.147778E+10 | 0.209496E+10 | 0.320412E+10 | 0.298815E+10 |
November | 0.196115E+10 | 0.629115E+09 | 0.133204E+10 | 0.124650E+10 | 0.372589E+10 |
December | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.440343E+09 | 0.591823E+10 |
Annual Sum or Average | 0.540980E+11 | 0.222987E+11 | 0.317994E+11 | 0.540343E+11 | 0.387757E+11 |
Minimum of Months | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.440343E+09 | 0.998808E+09 |
Maximum of Months | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.902226E+10 | 0.604892E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.737419E+10 | 0.430453E+10 | 0.306966E+10 | 0.594291E+10 | 0.860688E+10 |
February | 0.760469E+10 | 0.366691E+10 | 0.393777E+10 | 0.603261E+10 | 0.764910E+10 |
March | 0.102765E+11 | 0.577432E+10 | 0.450221E+10 | 0.998976E+10 | 0.635920E+10 |
April | 0.823605E+10 | 0.329115E+10 | 0.494490E+10 | 0.835597E+10 | 0.490512E+10 |
May | 0.744752E+10 | 0.216307E+10 | 0.528444E+10 | 0.817839E+10 | 0.350094E+10 |
June | 0.700315E+10 | 0.148400E+10 | 0.551915E+10 | 0.857639E+10 | 0.220683E+10 |
July | 0.738738E+10 | 0.179242E+10 | 0.559496E+10 | 0.100043E+11 | 0.160229E+10 |
August | 0.829355E+10 | 0.268898E+10 | 0.560457E+10 | 0.110739E+11 | 0.206274E+10 |
September | 0.933187E+10 | 0.454531E+10 | 0.478655E+10 | 0.115264E+11 | 0.309736E+10 |
October | 0.922686E+10 | 0.527056E+10 | 0.395630E+10 | 0.991348E+10 | 0.466617E+10 |
November | 0.639492E+10 | 0.361015E+10 | 0.278477E+10 | 0.605396E+10 | 0.565381E+10 |
December | 0.616629E+10 | 0.319133E+10 | 0.297495E+10 | 0.471479E+10 | 0.841758E+10 |
Annual Sum or Average | 0.947430E+11 | 0.417827E+11 | 0.529602E+11 | 0.100363E+12 | 0.587280E+11 |
Minimum of Months | 0.616629E+10 | 0.148400E+10 | 0.278477E+10 | 0.471479E+10 | 0.160229E+10 |
Maximum of Months | 0.102765E+11 | 0.577432E+10 | 0.560457E+10 | 0.115264E+11 | 0.860688E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179506E+10 | 0.421410E+09 | 0.137365E+10 | 0.501246E+09 | 0.640360E+10 |
February | 0.262776E+10 | 0.675353E+09 | 0.195240E+10 | 0.111694E+10 | 0.549155E+10 |
March | 0.455981E+10 | 0.195241E+10 | 0.260741E+10 | 0.357397E+10 | 0.444131E+10 |
April | 0.540278E+10 | 0.221536E+10 | 0.318742E+10 | 0.497750E+10 | 0.326831E+10 |
May | 0.658589E+10 | 0.297640E+10 | 0.360949E+10 | 0.708342E+10 | 0.237653E+10 |
June | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.930039E+10 | 0.156404E+10 |
July | 0.710409E+10 | 0.311468E+10 | 0.398941E+10 | 0.915108E+10 | 0.116810E+10 |
August | 0.642523E+10 | 0.273207E+10 | 0.369316E+10 | 0.815406E+10 | 0.146068E+10 |
September | 0.488303E+10 | 0.210877E+10 | 0.277426E+10 | 0.556463E+10 | 0.209732E+10 |
October | 0.327093E+10 | 0.115221E+10 | 0.211872E+10 | 0.283578E+10 | 0.322755E+10 |
November | 0.187584E+10 | 0.540549E+09 | 0.133529E+10 | 0.110999E+10 | 0.397889E+10 |
December | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.475745E+09 | 0.620039E+10 |
Annual Sum or Average | 0.539006E+11 | 0.218723E+11 | 0.320283E+11 | 0.538447E+11 | 0.416783E+11 |
Minimum of Months | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.475745E+09 | 0.116810E+10 |
Maximum of Months | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.930039E+10 | 0.640360E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.09 | 4262.01 | 640.28 | 0.00 | 640.28 | 0.00 | 0.00 |
February | 26.16 | 4005.06 | 975.55 | 0.00 | 975.55 | 0.00 | 0.00 |
March | 309.97 | 2959.98 | 1183.06 | 0.00 | 1183.06 | 0.00 | 0.00 |
April | 704.53 | 2129.97 | 1507.47 | 6.02 | 1501.45 | 0.00 | 0.00 |
May | 1323.18 | 1279.03 | 1751.60 | 74.28 | 1677.32 | 0.00 | 0.00 |
June | 2238.15 | 815.61 | 2106.81 | 179.34 | 1927.47 | 0.00 | 0.00 |
July | 2402.25 | 566.16 | 1954.34 | 126.16 | 1828.19 | 0.00 | 0.00 |
August | 1958.11 | 750.89 | 1691.05 | 25.73 | 1665.33 | 0.00 | 0.00 |
September | 1130.58 | 1262.93 | 1286.93 | 0.27 | 1286.66 | 0.00 | 0.00 |
October | 391.80 | 2123.80 | 962.03 | 0.00 | 962.03 | 0.00 | 0.00 |
November | 84.78 | 2858.49 | 646.46 | 0.00 | 646.46 | 0.00 | 0.00 |
December | 2.93 | 4205.95 | 599.28 | 0.00 | 599.28 | 0.00 | 0.00 |
Annual Sum or Average | 886.33 | 2259.54 | 1276.65 | 34.47 | 1242.18 | 0.00 | 0.00 |
Minimum of Months | 0.09 | 566.16 | 599.28 | 0.00 | 599.28 | 0.00 | 0.00 |
Maximum of Months | 2402.25 | 4262.01 | 2106.81 | 179.34 | 1927.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 277.74 | 2584.80 | 781.14 | 251.88 | 529.26 | 0.00 | 0.00 |
February | 495.89 | 2434.01 | 1146.17 | 343.94 | 802.23 | 0.00 | 0.00 |
March | 1228.81 | 1790.77 | 1644.72 | 688.80 | 955.92 | 0.00 | 0.00 |
April | 1986.99 | 1304.91 | 2176.89 | 961.87 | 1215.02 | 0.00 | 0.00 |
May | 2623.46 | 859.64 | 2438.89 | 1078.85 | 1360.04 | 0.00 | 0.00 |
June | 3295.53 | 547.40 | 2723.83 | 1203.80 | 1520.03 | 0.00 | 0.00 |
July | 3401.82 | 371.30 | 2615.60 | 1151.61 | 1463.99 | 0.00 | 0.00 |
August | 3008.35 | 480.97 | 2362.17 | 991.51 | 1370.66 | 0.00 | 0.00 |
September | 2247.72 | 800.16 | 1965.74 | 871.93 | 1093.81 | 0.00 | 0.00 |
October | 1142.62 | 1312.29 | 1333.92 | 551.74 | 782.17 | 0.00 | 0.00 |
November | 420.69 | 1769.91 | 756.62 | 242.72 | 513.91 | 0.00 | 0.00 |
December | 137.10 | 2576.46 | 609.12 | 125.86 | 483.26 | 0.00 | 0.00 |
Annual Sum or Average | 1695.42 | 1397.50 | 1715.44 | 707.09 | 1008.36 | 0.00 | 0.00 |
Minimum of Months | 137.10 | 371.30 | 609.12 | 125.86 | 483.26 | 0.00 | 0.00 |
Maximum of Months | 3401.82 | 2584.80 | 2723.83 | 1203.80 | 1520.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2173.79 | 3533.33 | 2753.22 | 1607.13 | 1146.08 | 0.00 | 0.00 |
February | 2437.58 | 3463.08 | 3143.48 | 1515.76 | 1627.72 | 0.00 | 0.00 |
March | 3697.12 | 2634.19 | 3836.83 | 2155.89 | 1680.94 | 0.00 | 0.00 |
April | 3186.43 | 2109.00 | 3177.50 | 1269.74 | 1907.76 | 0.00 | 0.00 |
May | 3068.42 | 1389.42 | 2780.59 | 807.60 | 1972.99 | 0.00 | 0.00 |
June | 3337.42 | 895.32 | 2701.84 | 572.53 | 2129.31 | 0.00 | 0.00 |
July | 3767.27 | 615.62 | 2758.14 | 669.22 | 2088.93 | 0.00 | 0.00 |
August | 4165.49 | 795.06 | 3096.47 | 1003.95 | 2092.52 | 0.00 | 0.00 |
September | 4473.12 | 1269.82 | 3600.27 | 1753.60 | 1846.67 | 0.00 | 0.00 |
October | 3671.99 | 1960.99 | 3444.93 | 1967.81 | 1477.12 | 0.00 | 0.00 |
November | 2273.02 | 2537.25 | 2467.18 | 1392.81 | 1074.38 | 0.00 | 0.00 |
December | 1700.47 | 3548.44 | 2302.24 | 1191.51 | 1110.72 | 0.00 | 0.00 |
Annual Sum or Average | 3166.94 | 2055.06 | 3004.29 | 1324.93 | 1679.36 | 0.00 | 0.00 |
Minimum of Months | 1700.47 | 615.62 | 2302.24 | 572.53 | 1074.38 | 0.00 | 0.00 |
Maximum of Months | 4473.12 | 3548.44 | 3836.83 | 2155.89 | 2129.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 162.32 | 2804.01 | 670.20 | 157.34 | 512.87 | 0.00 | 0.00 |
February | 400.63 | 2698.70 | 1086.21 | 279.16 | 807.05 | 0.00 | 0.00 |
March | 1261.66 | 2032.98 | 1702.45 | 728.95 | 973.50 | 0.00 | 0.00 |
April | 1834.59 | 1556.15 | 2084.41 | 854.69 | 1229.72 | 0.00 | 0.00 |
May | 2636.37 | 981.36 | 2458.90 | 1111.26 | 1347.64 | 0.00 | 0.00 |
June | 3595.21 | 668.72 | 2966.74 | 1395.43 | 1571.31 | 0.00 | 0.00 |
July | 3410.46 | 491.12 | 2652.38 | 1162.89 | 1489.48 | 0.00 | 0.00 |
August | 3022.06 | 631.11 | 2398.92 | 1020.04 | 1378.87 | 0.00 | 0.00 |
September | 2133.33 | 912.29 | 1883.89 | 813.57 | 1070.32 | 0.00 | 0.00 |
October | 985.66 | 1501.08 | 1221.23 | 430.19 | 791.04 | 0.00 | 0.00 |
November | 363.36 | 2036.67 | 723.71 | 208.55 | 515.16 | 0.00 | 0.00 |
December | 142.40 | 2962.07 | 627.39 | 136.70 | 490.69 | 0.00 | 0.00 |
Annual Sum or Average | 1669.21 | 1600.81 | 1709.18 | 693.57 | 1015.61 | 0.00 | 0.00 |
Minimum of Months | 142.40 | 491.12 | 627.39 | 136.70 | 490.69 | 0.00 | 0.00 |
Maximum of Months | 3595.21 | 2962.07 | 2966.74 | 1395.43 | 1571.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.54 | 3855.35 | 640.28 | 0.00 | 640.28 | 0.00 | 0.00 |
February | 54.87 | 3618.02 | 975.54 | 0.00 | 975.54 | 0.00 | 0.00 |
March | 362.75 | 2659.82 | 1183.06 | 0.00 | 1183.06 | 0.00 | 0.00 |
April | 779.92 | 1912.60 | 1507.46 | 6.02 | 1501.45 | 0.00 | 0.00 |
May | 1349.34 | 1215.25 | 1751.60 | 74.28 | 1677.32 | 0.00 | 0.00 |
June | 2255.79 | 777.80 | 2106.80 | 179.34 | 1927.46 | 0.00 | 0.00 |
July | 2425.76 | 540.40 | 1954.34 | 126.16 | 1828.18 | 0.00 | 0.00 |
August | 1982.74 | 717.85 | 1691.04 | 25.73 | 1665.32 | 0.00 | 0.00 |
September | 1154.60 | 1179.65 | 1286.92 | 0.27 | 1286.65 | 0.00 | 0.00 |
October | 448.98 | 1901.05 | 962.03 | 0.00 | 962.03 | 0.00 | 0.00 |
November | 125.62 | 2465.90 | 646.46 | 0.00 | 646.46 | 0.00 | 0.00 |
December | 8.23 | 3698.47 | 599.28 | 0.00 | 599.28 | 0.00 | 0.00 |
Annual Sum or Average | 918.07 | 2037.31 | 1276.64 | 34.46 | 1242.18 | 0.00 | 0.00 |
Minimum of Months | 5.54 | 540.40 | 599.28 | 0.00 | 599.28 | 0.00 | 0.00 |
Maximum of Months | 2425.76 | 3855.35 | 2106.80 | 179.34 | 1927.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 298.94 | 2340.36 | 781.13 | 251.88 | 529.25 | 0.00 | 0.00 |
February | 531.12 | 2229.24 | 1146.16 | 343.94 | 802.23 | 0.00 | 0.00 |
March | 1246.12 | 1667.02 | 1644.71 | 688.79 | 955.92 | 0.00 | 0.00 |
April | 1990.46 | 1233.66 | 2176.88 | 961.86 | 1215.02 | 0.00 | 0.00 |
May | 2602.62 | 837.81 | 2438.88 | 1078.85 | 1360.04 | 0.00 | 0.00 |
June | 3270.33 | 536.93 | 2723.82 | 1203.80 | 1520.03 | 0.00 | 0.00 |
July | 3379.47 | 371.39 | 2615.59 | 1151.61 | 1463.98 | 0.00 | 0.00 |
August | 2983.62 | 486.61 | 2362.16 | 991.51 | 1370.65 | 0.00 | 0.00 |
September | 2233.83 | 772.30 | 1965.73 | 871.92 | 1093.81 | 0.00 | 0.00 |
October | 1153.74 | 1224.15 | 1333.91 | 551.74 | 782.17 | 0.00 | 0.00 |
November | 446.07 | 1590.77 | 756.62 | 242.71 | 513.90 | 0.00 | 0.00 |
December | 155.00 | 2316.30 | 609.12 | 125.86 | 483.26 | 0.00 | 0.00 |
Annual Sum or Average | 1697.25 | 1295.84 | 1715.44 | 707.09 | 1008.35 | 0.00 | 0.00 |
Minimum of Months | 155.00 | 371.39 | 609.12 | 125.86 | 483.26 | 0.00 | 0.00 |
Maximum of Months | 3379.47 | 2340.36 | 2723.82 | 1203.80 | 1520.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2188.36 | 3360.38 | 2753.21 | 1607.13 | 1146.08 | 0.00 | 0.00 |
February | 2454.33 | 3307.73 | 3143.47 | 1515.75 | 1627.72 | 0.00 | 0.00 |
March | 3684.51 | 2537.20 | 3836.82 | 2155.88 | 1680.93 | 0.00 | 0.00 |
April | 3184.06 | 2018.89 | 3177.49 | 1269.73 | 1907.75 | 0.00 | 0.00 |
May | 3046.83 | 1360.45 | 2780.58 | 807.60 | 1972.99 | 0.00 | 0.00 |
June | 3325.64 | 864.63 | 2701.83 | 572.53 | 2129.30 | 0.00 | 0.00 |
July | 3761.51 | 596.77 | 2758.13 | 669.21 | 2088.92 | 0.00 | 0.00 |
August | 4153.25 | 778.14 | 3096.46 | 1003.95 | 2092.51 | 0.00 | 0.00 |
September | 4445.18 | 1242.61 | 3600.26 | 1753.59 | 1846.66 | 0.00 | 0.00 |
October | 3652.72 | 1896.82 | 3444.91 | 1967.80 | 1477.11 | 0.00 | 0.00 |
November | 2281.49 | 2398.80 | 2467.18 | 1392.80 | 1074.37 | 0.00 | 0.00 |
December | 1725.46 | 3318.75 | 2302.23 | 1191.51 | 1110.72 | 0.00 | 0.00 |
Annual Sum or Average | 3162.75 | 1966.21 | 3004.28 | 1324.92 | 1679.36 | 0.00 | 0.00 |
Minimum of Months | 1725.46 | 596.77 | 2302.23 | 572.53 | 1074.37 | 0.00 | 0.00 |
Maximum of Months | 4445.18 | 3360.38 | 3836.82 | 2155.88 | 2129.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.21 | 2483.07 | 670.20 | 157.34 | 512.86 | 0.00 | 0.00 |
February | 449.07 | 2355.70 | 1086.21 | 279.16 | 807.05 | 0.00 | 0.00 |
March | 1315.45 | 1756.15 | 1702.44 | 728.94 | 973.49 | 0.00 | 0.00 |
April | 1897.44 | 1336.89 | 2084.41 | 854.69 | 1229.72 | 0.00 | 0.00 |
May | 2643.35 | 919.95 | 2458.89 | 1111.26 | 1347.63 | 0.00 | 0.00 |
June | 3603.47 | 613.00 | 2966.72 | 1395.42 | 1571.30 | 0.00 | 0.00 |
July | 3435.84 | 437.62 | 2652.36 | 1162.89 | 1489.48 | 0.00 | 0.00 |
August | 3057.69 | 551.40 | 2398.91 | 1020.04 | 1378.87 | 0.00 | 0.00 |
September | 2145.72 | 839.92 | 1883.89 | 813.57 | 1070.32 | 0.00 | 0.00 |
October | 1031.69 | 1302.66 | 1221.23 | 430.19 | 791.04 | 0.00 | 0.00 |
November | 406.09 | 1665.95 | 723.70 | 208.55 | 515.16 | 0.00 | 0.00 |
December | 170.00 | 2420.08 | 627.39 | 136.70 | 490.69 | 0.00 | 0.00 |
Annual Sum or Average | 1701.33 | 1385.29 | 1709.18 | 693.57 | 1015.61 | 0.00 | 0.00 |
Minimum of Months | 170.00 | 437.62 | 627.39 | 136.70 | 490.69 | 0.00 | 0.00 |
Maximum of Months | 3603.47 | 2483.07 | 2966.72 | 1395.42 | 1571.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.27 | 3716.16 | 640.28 | 0.00 | 640.28 | 0.00 | 0.00 |
February | 71.08 | 3474.48 | 975.54 | 0.00 | 975.54 | 0.00 | 0.00 |
March | 393.58 | 2495.27 | 1183.06 | 0.00 | 1183.06 | 0.00 | 0.00 |
April | 829.40 | 1780.29 | 1507.46 | 6.02 | 1501.45 | 0.00 | 0.00 |
May | 1370.28 | 1164.31 | 1751.60 | 74.28 | 1677.32 | 0.00 | 0.00 |
June | 2244.32 | 767.84 | 2106.80 | 179.34 | 1927.46 | 0.00 | 0.00 |
July | 2400.99 | 543.47 | 1954.34 | 126.16 | 1828.18 | 0.00 | 0.00 |
August | 1969.41 | 710.80 | 1691.04 | 25.73 | 1665.32 | 0.00 | 0.00 |
September | 1167.60 | 1124.59 | 1286.92 | 0.27 | 1286.65 | 0.00 | 0.00 |
October | 500.65 | 1724.78 | 962.03 | 0.00 | 962.03 | 0.00 | 0.00 |
November | 158.63 | 2235.39 | 646.46 | 0.00 | 646.46 | 0.00 | 0.00 |
December | 13.28 | 3517.41 | 599.28 | 0.00 | 599.28 | 0.00 | 0.00 |
Annual Sum or Average | 932.78 | 1930.32 | 1276.64 | 34.46 | 1242.18 | 0.00 | 0.00 |
Minimum of Months | 12.27 | 543.47 | 599.28 | 0.00 | 599.28 | 0.00 | 0.00 |
Maximum of Months | 2400.99 | 3716.16 | 2106.80 | 179.34 | 1927.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 311.11 | 2258.41 | 781.13 | 251.88 | 529.25 | 0.00 | 0.00 |
February | 553.20 | 2142.71 | 1146.16 | 343.94 | 802.23 | 0.00 | 0.00 |
March | 1282.17 | 1555.88 | 1644.71 | 688.79 | 955.92 | 0.00 | 0.00 |
April | 2029.11 | 1154.59 | 2176.88 | 961.86 | 1215.02 | 0.00 | 0.00 |
May | 2613.42 | 807.97 | 2438.88 | 1078.85 | 1360.04 | 0.00 | 0.00 |
June | 3265.04 | 530.74 | 2723.82 | 1203.80 | 1520.03 | 0.00 | 0.00 |
July | 3368.53 | 372.91 | 2615.59 | 1151.61 | 1463.98 | 0.00 | 0.00 |
August | 2978.23 | 481.98 | 2362.16 | 991.51 | 1370.65 | 0.00 | 0.00 |
September | 2243.93 | 741.31 | 1965.73 | 871.92 | 1093.81 | 0.00 | 0.00 |
October | 1196.28 | 1115.65 | 1333.91 | 551.74 | 782.17 | 0.00 | 0.00 |
November | 480.90 | 1437.46 | 756.62 | 242.71 | 513.90 | 0.00 | 0.00 |
December | 164.41 | 2209.61 | 609.12 | 125.86 | 483.26 | 0.00 | 0.00 |
Annual Sum or Average | 1713.42 | 1229.57 | 1715.44 | 707.09 | 1008.35 | 0.00 | 0.00 |
Minimum of Months | 164.41 | 372.91 | 609.12 | 125.86 | 483.26 | 0.00 | 0.00 |
Maximum of Months | 3368.53 | 2258.41 | 2723.82 | 1203.80 | 1520.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2218.83 | 3213.44 | 2753.21 | 1607.13 | 1146.08 | 0.00 | 0.00 |
February | 2493.64 | 3161.83 | 3143.47 | 1515.75 | 1627.72 | 0.00 | 0.00 |
March | 3729.75 | 2374.25 | 3836.82 | 2155.88 | 1680.93 | 0.00 | 0.00 |
April | 3223.75 | 1892.41 | 3177.49 | 1269.73 | 1907.75 | 0.00 | 0.00 |
May | 3053.46 | 1307.10 | 2780.58 | 807.60 | 1972.99 | 0.00 | 0.00 |
June | 3308.79 | 851.40 | 2701.83 | 572.53 | 2129.30 | 0.00 | 0.00 |
July | 3735.19 | 598.23 | 2758.13 | 669.21 | 2088.92 | 0.00 | 0.00 |
August | 4134.53 | 770.14 | 3096.46 | 1003.95 | 2092.51 | 0.00 | 0.00 |
September | 4446.93 | 1194.97 | 3600.26 | 1753.59 | 1846.66 | 0.00 | 0.00 |
October | 3701.27 | 1742.15 | 3444.91 | 1967.80 | 1477.11 | 0.00 | 0.00 |
November | 2335.63 | 2181.25 | 2467.18 | 1392.80 | 1074.37 | 0.00 | 0.00 |
December | 1760.30 | 3142.76 | 2302.23 | 1191.51 | 1110.72 | 0.00 | 0.00 |
Annual Sum or Average | 3182.49 | 1862.25 | 3004.28 | 1324.92 | 1679.36 | 0.00 | 0.00 |
Minimum of Months | 1760.30 | 598.23 | 2302.23 | 572.53 | 1074.37 | 0.00 | 0.00 |
Maximum of Months | 4446.93 | 3213.44 | 3836.82 | 2155.88 | 2129.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 187.14 | 2390.83 | 670.20 | 157.34 | 512.86 | 0.00 | 0.00 |
February | 461.70 | 2269.98 | 1086.21 | 279.16 | 807.05 | 0.00 | 0.00 |
March | 1334.37 | 1658.19 | 1702.44 | 728.94 | 973.49 | 0.00 | 0.00 |
April | 1920.33 | 1260.92 | 2084.41 | 854.69 | 1229.72 | 0.00 | 0.00 |
May | 2644.65 | 887.30 | 2458.89 | 1111.26 | 1347.63 | 0.00 | 0.00 |
June | 3588.11 | 603.41 | 2966.72 | 1395.42 | 1571.30 | 0.00 | 0.00 |
July | 3416.62 | 436.12 | 2652.36 | 1162.89 | 1489.48 | 0.00 | 0.00 |
August | 3044.38 | 545.36 | 2398.91 | 1020.04 | 1378.87 | 0.00 | 0.00 |
September | 2146.85 | 809.15 | 1883.89 | 813.57 | 1070.32 | 0.00 | 0.00 |
October | 1058.76 | 1205.03 | 1221.23 | 430.19 | 791.04 | 0.00 | 0.00 |
November | 428.24 | 1535.07 | 723.70 | 208.55 | 515.16 | 0.00 | 0.00 |
December | 177.62 | 2314.96 | 627.39 | 136.70 | 490.69 | 0.00 | 0.00 |
Annual Sum or Average | 1707.41 | 1321.61 | 1709.18 | 693.57 | 1015.61 | 0.00 | 0.00 |
Minimum of Months | 177.62 | 436.12 | 627.39 | 136.70 | 490.69 | 0.00 | 0.00 |
Maximum of Months | 3588.11 | 2390.83 | 2966.72 | 1395.42 | 1571.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 241170.21 | 0.114154E+11 | 0.171493E+10 | 0.00 | 0.171493E+10 | 0.00 | 0.00 |
February | 63289276.71 | 0.968905E+10 | 0.236005E+10 | 0.00 | 0.236005E+10 | 0.00 | 0.00 |
March | 0.830230E+09 | 0.792802E+10 | 0.316872E+10 | 0.00 | 0.316872E+10 | 0.00 | 0.00 |
April | 0.182615E+10 | 0.552088E+10 | 0.390735E+10 | 15591882.90 | 0.389176E+10 | 0.00 | 0.00 |
May | 0.354401E+10 | 0.342574E+10 | 0.469149E+10 | 0.198946E+09 | 0.449254E+10 | 0.00 | 0.00 |
June | 0.580129E+10 | 0.211406E+10 | 0.546085E+10 | 0.464855E+09 | 0.499599E+10 | 0.00 | 0.00 |
July | 0.643419E+10 | 0.151639E+10 | 0.523452E+10 | 0.337900E+09 | 0.489662E+10 | 0.00 | 0.00 |
August | 0.524460E+10 | 0.201118E+10 | 0.452931E+10 | 68903617.40 | 0.446041E+10 | 0.00 | 0.00 |
September | 0.293047E+10 | 0.327351E+10 | 0.333571E+10 | 693016.49 | 0.333502E+10 | 0.00 | 0.00 |
October | 0.104940E+10 | 0.568838E+10 | 0.257671E+10 | 0.00 | 0.257671E+10 | 0.00 | 0.00 |
November | 0.219737E+09 | 0.740919E+10 | 0.167563E+10 | 0.00 | 0.167563E+10 | 0.00 | 0.00 |
December | 7838277.88 | 0.112652E+11 | 0.160512E+10 | 0.00 | 0.160512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.279514E+11 | 0.712570E+11 | 0.402604E+11 | 0.108689E+10 | 0.391735E+11 | 0.00 | 0.00 |
Minimum of Months | 241170.21 | 0.151639E+10 | 0.160512E+10 | 0.00 | 0.160512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.643419E+10 | 0.114154E+11 | 0.546085E+10 | 0.464855E+09 | 0.499599E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.743898E+09 | 0.692313E+10 | 0.209220E+10 | 0.674642E+09 | 0.141756E+10 | 0.00 | 0.00 |
February | 0.119965E+10 | 0.588835E+10 | 0.277281E+10 | 0.832051E+09 | 0.194076E+10 | 0.00 | 0.00 |
March | 0.329125E+10 | 0.479640E+10 | 0.440521E+10 | 0.184488E+10 | 0.256034E+10 | 0.00 | 0.00 |
April | 0.515027E+10 | 0.338233E+10 | 0.564249E+10 | 0.249316E+10 | 0.314934E+10 | 0.00 | 0.00 |
May | 0.702667E+10 | 0.230245E+10 | 0.653234E+10 | 0.288960E+10 | 0.364273E+10 | 0.00 | 0.00 |
June | 0.854202E+10 | 0.141885E+10 | 0.706018E+10 | 0.312025E+10 | 0.393993E+10 | 0.00 | 0.00 |
July | 0.911145E+10 | 0.994494E+09 | 0.700561E+10 | 0.308447E+10 | 0.392114E+10 | 0.00 | 0.00 |
August | 0.805756E+10 | 0.128823E+10 | 0.632684E+10 | 0.265566E+10 | 0.367118E+10 | 0.00 | 0.00 |
September | 0.582609E+10 | 0.207400E+10 | 0.509519E+10 | 0.226003E+10 | 0.283516E+10 | 0.00 | 0.00 |
October | 0.306040E+10 | 0.351485E+10 | 0.357276E+10 | 0.147779E+10 | 0.209497E+10 | 0.00 | 0.00 |
November | 0.109042E+10 | 0.458760E+10 | 0.196116E+10 | 0.629118E+09 | 0.133204E+10 | 0.00 | 0.00 |
December | 0.367214E+09 | 0.690079E+10 | 0.163146E+10 | 0.337095E+09 | 0.129437E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.534669E+11 | 0.440715E+11 | 0.540982E+11 | 0.222987E+11 | 0.317995E+11 | 0.00 | 0.00 |
Minimum of Months | 0.367214E+09 | 0.994494E+09 | 0.163146E+10 | 0.337095E+09 | 0.129437E+10 | 0.00 | 0.00 |
Maximum of Months | 0.911145E+10 | 0.692313E+10 | 0.706018E+10 | 0.312025E+10 | 0.393993E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.582228E+10 | 0.946367E+10 | 0.737422E+10 | 0.430455E+10 | 0.306967E+10 | 0.00 | 0.00 |
February | 0.589698E+10 | 0.837789E+10 | 0.760471E+10 | 0.366693E+10 | 0.393779E+10 | 0.00 | 0.00 |
March | 0.990237E+10 | 0.705541E+10 | 0.102766E+11 | 0.577434E+10 | 0.450223E+10 | 0.00 | 0.00 |
April | 0.825923E+10 | 0.546653E+10 | 0.823608E+10 | 0.329116E+10 | 0.494492E+10 | 0.00 | 0.00 |
May | 0.821846E+10 | 0.372141E+10 | 0.744754E+10 | 0.216308E+10 | 0.528446E+10 | 0.00 | 0.00 |
June | 0.865059E+10 | 0.232068E+10 | 0.700317E+10 | 0.148401E+10 | 0.551917E+10 | 0.00 | 0.00 |
July | 0.100903E+11 | 0.164889E+10 | 0.738741E+10 | 0.179243E+10 | 0.559498E+10 | 0.00 | 0.00 |
August | 0.111568E+11 | 0.212950E+10 | 0.829358E+10 | 0.268899E+10 | 0.560459E+10 | 0.00 | 0.00 |
September | 0.115943E+11 | 0.329138E+10 | 0.933190E+10 | 0.454533E+10 | 0.478657E+10 | 0.00 | 0.00 |
October | 0.983505E+10 | 0.525232E+10 | 0.922689E+10 | 0.527058E+10 | 0.395631E+10 | 0.00 | 0.00 |
November | 0.589167E+10 | 0.657655E+10 | 0.639494E+10 | 0.361016E+10 | 0.278478E+10 | 0.00 | 0.00 |
December | 0.455453E+10 | 0.950414E+10 | 0.616631E+10 | 0.319134E+10 | 0.297496E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.998726E+11 | 0.648084E+11 | 0.947433E+11 | 0.417829E+11 | 0.529604E+11 | 0.00 | 0.00 |
Minimum of Months | 0.455453E+10 | 0.164889E+10 | 0.616631E+10 | 0.148401E+10 | 0.278478E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115943E+11 | 0.950414E+10 | 0.102766E+11 | 0.577434E+10 | 0.560459E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.434767E+09 | 0.751025E+10 | 0.179507E+10 | 0.421412E+09 | 0.137366E+10 | 0.00 | 0.00 |
February | 0.969214E+09 | 0.652868E+10 | 0.262777E+10 | 0.675356E+09 | 0.195241E+10 | 0.00 | 0.00 |
March | 0.337924E+10 | 0.544512E+10 | 0.455983E+10 | 0.195241E+10 | 0.260742E+10 | 0.00 | 0.00 |
April | 0.475526E+10 | 0.403353E+10 | 0.540280E+10 | 0.221537E+10 | 0.318744E+10 | 0.00 | 0.00 |
May | 0.706126E+10 | 0.262848E+10 | 0.658592E+10 | 0.297641E+10 | 0.360951E+10 | 0.00 | 0.00 |
June | 0.931878E+10 | 0.173333E+10 | 0.768978E+10 | 0.361696E+10 | 0.407283E+10 | 0.00 | 0.00 |
July | 0.913457E+10 | 0.131541E+10 | 0.710412E+10 | 0.311469E+10 | 0.398943E+10 | 0.00 | 0.00 |
August | 0.809429E+10 | 0.169036E+10 | 0.642526E+10 | 0.273208E+10 | 0.369318E+10 | 0.00 | 0.00 |
September | 0.552959E+10 | 0.236466E+10 | 0.488305E+10 | 0.210878E+10 | 0.277427E+10 | 0.00 | 0.00 |
October | 0.263999E+10 | 0.402050E+10 | 0.327094E+10 | 0.115221E+10 | 0.211873E+10 | 0.00 | 0.00 |
November | 0.941817E+09 | 0.527906E+10 | 0.187584E+10 | 0.540552E+09 | 0.133529E+10 | 0.00 | 0.00 |
December | 0.381400E+09 | 0.793362E+10 | 0.168040E+10 | 0.366140E+09 | 0.131426E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.526402E+11 | 0.504830E+11 | 0.539008E+11 | 0.218724E+11 | 0.320284E+11 | 0.00 | 0.00 |
Minimum of Months | 0.381400E+09 | 0.131541E+10 | 0.168040E+10 | 0.366140E+09 | 0.131426E+10 | 0.00 | 0.00 |
Maximum of Months | 0.931878E+10 | 0.793362E+10 | 0.768978E+10 | 0.361696E+10 | 0.407283E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 14839454.69 | 0.103262E+11 | 0.171492E+10 | 0.00 | 0.171492E+10 | 0.00 | 0.00 |
February | 0.132736E+09 | 0.875271E+10 | 0.236004E+10 | 0.00 | 0.236004E+10 | 0.00 | 0.00 |
March | 0.971584E+09 | 0.712406E+10 | 0.316871E+10 | 0.00 | 0.316871E+10 | 0.00 | 0.00 |
April | 0.202155E+10 | 0.495746E+10 | 0.390734E+10 | 15591827.53 | 0.389175E+10 | 0.00 | 0.00 |
May | 0.361407E+10 | 0.325493E+10 | 0.469147E+10 | 0.198945E+09 | 0.449253E+10 | 0.00 | 0.00 |
June | 0.584700E+10 | 0.201606E+10 | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.00 | 0.00 |
July | 0.649715E+10 | 0.144741E+10 | 0.523450E+10 | 0.337898E+09 | 0.489660E+10 | 0.00 | 0.00 |
August | 0.531056E+10 | 0.192270E+10 | 0.452929E+10 | 68903372.72 | 0.446039E+10 | 0.00 | 0.00 |
September | 0.299273E+10 | 0.305765E+10 | 0.333570E+10 | 693014.03 | 0.333501E+10 | 0.00 | 0.00 |
October | 0.120254E+10 | 0.509177E+10 | 0.257670E+10 | 0.00 | 0.257670E+10 | 0.00 | 0.00 |
November | 0.325604E+09 | 0.639161E+10 | 0.167562E+10 | 0.00 | 0.167562E+10 | 0.00 | 0.00 |
December | 22044245.29 | 0.990597E+10 | 0.160512E+10 | 0.00 | 0.160512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.289524E+11 | 0.642485E+11 | 0.402602E+11 | 0.108689E+10 | 0.391733E+11 | 0.00 | 0.00 |
Minimum of Months | 14839454.69 | 0.144741E+10 | 0.160512E+10 | 0.00 | 0.160512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.649715E+10 | 0.103262E+11 | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.800694E+09 | 0.626841E+10 | 0.209219E+10 | 0.674639E+09 | 0.141755E+10 | 0.00 | 0.00 |
February | 0.128489E+10 | 0.539299E+10 | 0.277280E+10 | 0.832048E+09 | 0.194075E+10 | 0.00 | 0.00 |
March | 0.333762E+10 | 0.446495E+10 | 0.440520E+10 | 0.184487E+10 | 0.256033E+10 | 0.00 | 0.00 |
April | 0.515927E+10 | 0.319764E+10 | 0.564247E+10 | 0.249315E+10 | 0.314932E+10 | 0.00 | 0.00 |
May | 0.697085E+10 | 0.224398E+10 | 0.653231E+10 | 0.288959E+10 | 0.364272E+10 | 0.00 | 0.00 |
June | 0.847670E+10 | 0.139172E+10 | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.00 | 0.00 |
July | 0.905157E+10 | 0.994732E+09 | 0.700558E+10 | 0.308446E+10 | 0.392112E+10 | 0.00 | 0.00 |
August | 0.799134E+10 | 0.130334E+10 | 0.632681E+10 | 0.265565E+10 | 0.367116E+10 | 0.00 | 0.00 |
September | 0.579010E+10 | 0.200180E+10 | 0.509517E+10 | 0.226002E+10 | 0.283515E+10 | 0.00 | 0.00 |
October | 0.309018E+10 | 0.327876E+10 | 0.357274E+10 | 0.147778E+10 | 0.209496E+10 | 0.00 | 0.00 |
November | 0.115621E+10 | 0.412327E+10 | 0.196115E+10 | 0.629115E+09 | 0.133204E+10 | 0.00 | 0.00 |
December | 0.415153E+09 | 0.620399E+10 | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.535246E+11 | 0.408656E+11 | 0.540980E+11 | 0.222987E+11 | 0.317994E+11 | 0.00 | 0.00 |
Minimum of Months | 0.415153E+09 | 0.994732E+09 | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.00 | 0.00 |
Maximum of Months | 0.905157E+10 | 0.626841E+10 | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.586129E+10 | 0.900044E+10 | 0.737419E+10 | 0.430453E+10 | 0.306966E+10 | 0.00 | 0.00 |
February | 0.593752E+10 | 0.800207E+10 | 0.760469E+10 | 0.366691E+10 | 0.393777E+10 | 0.00 | 0.00 |
March | 0.986858E+10 | 0.679565E+10 | 0.102765E+11 | 0.577432E+10 | 0.450221E+10 | 0.00 | 0.00 |
April | 0.825308E+10 | 0.523295E+10 | 0.823605E+10 | 0.329115E+10 | 0.494490E+10 | 0.00 | 0.00 |
May | 0.816062E+10 | 0.364384E+10 | 0.744752E+10 | 0.216307E+10 | 0.528444E+10 | 0.00 | 0.00 |
June | 0.862005E+10 | 0.224112E+10 | 0.700315E+10 | 0.148400E+10 | 0.551915E+10 | 0.00 | 0.00 |
July | 0.100748E+11 | 0.159839E+10 | 0.738738E+10 | 0.179242E+10 | 0.559496E+10 | 0.00 | 0.00 |
August | 0.111241E+11 | 0.208416E+10 | 0.829355E+10 | 0.268898E+10 | 0.560457E+10 | 0.00 | 0.00 |
September | 0.115219E+11 | 0.322083E+10 | 0.933187E+10 | 0.454531E+10 | 0.478655E+10 | 0.00 | 0.00 |
October | 0.978346E+10 | 0.508045E+10 | 0.922686E+10 | 0.527056E+10 | 0.395630E+10 | 0.00 | 0.00 |
November | 0.591362E+10 | 0.621770E+10 | 0.639492E+10 | 0.361015E+10 | 0.278477E+10 | 0.00 | 0.00 |
December | 0.462148E+10 | 0.888894E+10 | 0.616629E+10 | 0.319133E+10 | 0.297495E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.997405E+11 | 0.620065E+11 | 0.947430E+11 | 0.417827E+11 | 0.529602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.462148E+10 | 0.159839E+10 | 0.616629E+10 | 0.148400E+10 | 0.278477E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115219E+11 | 0.900044E+10 | 0.102765E+11 | 0.577432E+10 | 0.560457E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.479985E+09 | 0.665064E+10 | 0.179506E+10 | 0.421410E+09 | 0.137365E+10 | 0.00 | 0.00 |
February | 0.108639E+10 | 0.569891E+10 | 0.262776E+10 | 0.675353E+09 | 0.195240E+10 | 0.00 | 0.00 |
March | 0.352330E+10 | 0.470368E+10 | 0.455981E+10 | 0.195241E+10 | 0.260741E+10 | 0.00 | 0.00 |
April | 0.491816E+10 | 0.346522E+10 | 0.540278E+10 | 0.221536E+10 | 0.318742E+10 | 0.00 | 0.00 |
May | 0.707994E+10 | 0.246400E+10 | 0.658589E+10 | 0.297640E+10 | 0.360949E+10 | 0.00 | 0.00 |
June | 0.934020E+10 | 0.158889E+10 | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.00 | 0.00 |
July | 0.920255E+10 | 0.117213E+10 | 0.710409E+10 | 0.311468E+10 | 0.398941E+10 | 0.00 | 0.00 |
August | 0.818972E+10 | 0.147688E+10 | 0.642523E+10 | 0.273207E+10 | 0.369316E+10 | 0.00 | 0.00 |
September | 0.556171E+10 | 0.217707E+10 | 0.488303E+10 | 0.210877E+10 | 0.277426E+10 | 0.00 | 0.00 |
October | 0.276329E+10 | 0.348904E+10 | 0.327093E+10 | 0.115221E+10 | 0.211872E+10 | 0.00 | 0.00 |
November | 0.105260E+10 | 0.431814E+10 | 0.187584E+10 | 0.540549E+09 | 0.133529E+10 | 0.00 | 0.00 |
December | 0.455330E+09 | 0.648195E+10 | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.536532E+11 | 0.436866E+11 | 0.539006E+11 | 0.218723E+11 | 0.320283E+11 | 0.00 | 0.00 |
Minimum of Months | 0.455330E+09 | 0.117213E+10 | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.00 | 0.00 |
Maximum of Months | 0.934020E+10 | 0.665064E+10 | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 32871608.83 | 0.995337E+10 | 0.171492E+10 | 0.00 | 0.171492E+10 | 0.00 | 0.00 |
February | 0.171951E+09 | 0.840547E+10 | 0.236004E+10 | 0.00 | 0.236004E+10 | 0.00 | 0.00 |
March | 0.105417E+10 | 0.668334E+10 | 0.316871E+10 | 0.00 | 0.316871E+10 | 0.00 | 0.00 |
April | 0.214981E+10 | 0.461452E+10 | 0.390734E+10 | 15591827.53 | 0.389175E+10 | 0.00 | 0.00 |
May | 0.367016E+10 | 0.311849E+10 | 0.469147E+10 | 0.198945E+09 | 0.449253E+10 | 0.00 | 0.00 |
June | 0.581727E+10 | 0.199024E+10 | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.00 | 0.00 |
July | 0.643082E+10 | 0.145562E+10 | 0.523450E+10 | 0.337898E+09 | 0.489660E+10 | 0.00 | 0.00 |
August | 0.527485E+10 | 0.190380E+10 | 0.452929E+10 | 68903372.72 | 0.446039E+10 | 0.00 | 0.00 |
September | 0.302641E+10 | 0.291495E+10 | 0.333570E+10 | 693014.03 | 0.333501E+10 | 0.00 | 0.00 |
October | 0.134095E+10 | 0.461965E+10 | 0.257670E+10 | 0.00 | 0.257670E+10 | 0.00 | 0.00 |
November | 0.411176E+09 | 0.579413E+10 | 0.167562E+10 | 0.00 | 0.167562E+10 | 0.00 | 0.00 |
December | 35561773.98 | 0.942102E+10 | 0.160512E+10 | 0.00 | 0.160512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.294160E+11 | 0.608746E+11 | 0.402602E+11 | 0.108689E+10 | 0.391733E+11 | 0.00 | 0.00 |
Minimum of Months | 32871608.83 | 0.145562E+10 | 0.160512E+10 | 0.00 | 0.160512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.643082E+10 | 0.995337E+10 | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.833282E+09 | 0.604892E+10 | 0.209219E+10 | 0.674639E+09 | 0.141755E+10 | 0.00 | 0.00 |
February | 0.133831E+10 | 0.518365E+10 | 0.277280E+10 | 0.832048E+09 | 0.194075E+10 | 0.00 | 0.00 |
March | 0.343416E+10 | 0.416727E+10 | 0.440520E+10 | 0.184487E+10 | 0.256033E+10 | 0.00 | 0.00 |
April | 0.525944E+10 | 0.299270E+10 | 0.564247E+10 | 0.249315E+10 | 0.314932E+10 | 0.00 | 0.00 |
May | 0.699977E+10 | 0.216406E+10 | 0.653231E+10 | 0.288959E+10 | 0.364272E+10 | 0.00 | 0.00 |
June | 0.846298E+10 | 0.137567E+10 | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.00 | 0.00 |
July | 0.902226E+10 | 0.998808E+09 | 0.700558E+10 | 0.308446E+10 | 0.392112E+10 | 0.00 | 0.00 |
August | 0.797690E+10 | 0.129092E+10 | 0.632681E+10 | 0.265565E+10 | 0.367116E+10 | 0.00 | 0.00 |
September | 0.581626E+10 | 0.192147E+10 | 0.509517E+10 | 0.226002E+10 | 0.283515E+10 | 0.00 | 0.00 |
October | 0.320412E+10 | 0.298815E+10 | 0.357274E+10 | 0.147778E+10 | 0.209496E+10 | 0.00 | 0.00 |
November | 0.124650E+10 | 0.372589E+10 | 0.196115E+10 | 0.629115E+09 | 0.133204E+10 | 0.00 | 0.00 |
December | 0.440343E+09 | 0.591823E+10 | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.540343E+11 | 0.387757E+11 | 0.540980E+11 | 0.222987E+11 | 0.317994E+11 | 0.00 | 0.00 |
Minimum of Months | 0.440343E+09 | 0.998808E+09 | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.00 | 0.00 |
Maximum of Months | 0.902226E+10 | 0.604892E+10 | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.594291E+10 | 0.860688E+10 | 0.737419E+10 | 0.430453E+10 | 0.306966E+10 | 0.00 | 0.00 |
February | 0.603261E+10 | 0.764910E+10 | 0.760469E+10 | 0.366691E+10 | 0.393777E+10 | 0.00 | 0.00 |
March | 0.998976E+10 | 0.635920E+10 | 0.102765E+11 | 0.577432E+10 | 0.450221E+10 | 0.00 | 0.00 |
April | 0.835597E+10 | 0.490512E+10 | 0.823605E+10 | 0.329115E+10 | 0.494490E+10 | 0.00 | 0.00 |
May | 0.817839E+10 | 0.350094E+10 | 0.744752E+10 | 0.216307E+10 | 0.528444E+10 | 0.00 | 0.00 |
June | 0.857639E+10 | 0.220683E+10 | 0.700315E+10 | 0.148400E+10 | 0.551915E+10 | 0.00 | 0.00 |
July | 0.100043E+11 | 0.160229E+10 | 0.738738E+10 | 0.179242E+10 | 0.559496E+10 | 0.00 | 0.00 |
August | 0.110739E+11 | 0.206274E+10 | 0.829355E+10 | 0.268898E+10 | 0.560457E+10 | 0.00 | 0.00 |
September | 0.115264E+11 | 0.309736E+10 | 0.933187E+10 | 0.454531E+10 | 0.478655E+10 | 0.00 | 0.00 |
October | 0.991348E+10 | 0.466617E+10 | 0.922686E+10 | 0.527056E+10 | 0.395630E+10 | 0.00 | 0.00 |
November | 0.605396E+10 | 0.565381E+10 | 0.639492E+10 | 0.361015E+10 | 0.278477E+10 | 0.00 | 0.00 |
December | 0.471479E+10 | 0.841758E+10 | 0.616629E+10 | 0.319133E+10 | 0.297495E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100363E+12 | 0.587280E+11 | 0.947430E+11 | 0.417827E+11 | 0.529602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.471479E+10 | 0.160229E+10 | 0.616629E+10 | 0.148400E+10 | 0.278477E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115264E+11 | 0.860688E+10 | 0.102765E+11 | 0.577432E+10 | 0.560457E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.501246E+09 | 0.640360E+10 | 0.179506E+10 | 0.421410E+09 | 0.137365E+10 | 0.00 | 0.00 |
February | 0.111694E+10 | 0.549155E+10 | 0.262776E+10 | 0.675353E+09 | 0.195240E+10 | 0.00 | 0.00 |
March | 0.357397E+10 | 0.444131E+10 | 0.455981E+10 | 0.195241E+10 | 0.260741E+10 | 0.00 | 0.00 |
April | 0.497750E+10 | 0.326831E+10 | 0.540278E+10 | 0.221536E+10 | 0.318742E+10 | 0.00 | 0.00 |
May | 0.708342E+10 | 0.237653E+10 | 0.658589E+10 | 0.297640E+10 | 0.360949E+10 | 0.00 | 0.00 |
June | 0.930039E+10 | 0.156404E+10 | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.00 | 0.00 |
July | 0.915108E+10 | 0.116810E+10 | 0.710409E+10 | 0.311468E+10 | 0.398941E+10 | 0.00 | 0.00 |
August | 0.815406E+10 | 0.146068E+10 | 0.642523E+10 | 0.273207E+10 | 0.369316E+10 | 0.00 | 0.00 |
September | 0.556463E+10 | 0.209732E+10 | 0.488303E+10 | 0.210877E+10 | 0.277426E+10 | 0.00 | 0.00 |
October | 0.283578E+10 | 0.322755E+10 | 0.327093E+10 | 0.115221E+10 | 0.211872E+10 | 0.00 | 0.00 |
November | 0.110999E+10 | 0.397889E+10 | 0.187584E+10 | 0.540549E+09 | 0.133529E+10 | 0.00 | 0.00 |
December | 0.475745E+09 | 0.620039E+10 | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.538447E+11 | 0.416783E+11 | 0.539006E+11 | 0.218723E+11 | 0.320283E+11 | 0.00 | 0.00 |
Minimum of Months | 0.475745E+09 | 0.116810E+10 | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.00 | 0.00 |
Maximum of Months | 0.930039E+10 | 0.640360E+10 | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.423664E+11 | -0.419189E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -447431889.9 | 60.05 | 0.00 | 0.00 |
February | 0.390367E+11 | -0.386325E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -404166539.5 | 60.05 | 0.00 | 0.00 |
March | 0.452824E+11 | -0.448357E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446741324.0 | 60.05 | 0.00 | 0.00 |
April | 0.395103E+11 | -0.390803E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429968909.9 | 60.05 | 0.00 | 0.00 |
May | 0.398592E+11 | -0.394149E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444313550.7 | 60.05 | 0.00 | 0.00 |
June | 0.371237E+11 | -0.367014E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -422248029.2 | 60.05 | 0.00 | 0.00 |
July | 0.336607E+11 | -0.332332E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -427448424.2 | 60.05 | 0.00 | 0.00 |
August | 0.361533E+11 | -0.357176E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -435676183.7 | 60.05 | 0.00 | 0.00 |
September | 0.334007E+11 | -0.329757E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -424998560.7 | 60.05 | 0.00 | 0.00 |
October | 0.361220E+11 | -0.356802E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -441829247.9 | 60.05 | 0.00 | 0.00 |
November | 0.376522E+11 | -0.372240E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428202381.4 | 60.05 | 0.00 | 0.00 |
December | 0.396976E+11 | -0.392532E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444409543.0 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.459865E+12 | -0.454668E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.519743E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.334007E+11 | -0.448357E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -447431889.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.452824E+11 | -0.329757E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -404166539.5 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.49 | 0.48 | 01-JAN-09:09 | 4421.25 | 32.94 | 239.17 | 251.33 | 3523.72 | 33.90 | 243.67 | 223.67 |
February | 262.50 | 0.49 | 0.48 | 01-FEB-09:39 | 5558.69 | 33.10 | 251.67 | 256.83 | 1787.44 | 26.25 | 228.17 | 233.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:40 | 7928.68 | 30.46 | 270.00 | 327.50 | 1469.56 | 22.61 | 233.50 | 293.67 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:00 | 2108.09 | 20.44 | 152.00 | 346.67 | 1164.55 | 21.82 | 251.67 | 312.17 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:30 | 1928.19 | 20.48 | 119.33 | 385.67 | 1121.20 | 21.91 | 251.17 | 338.83 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1743.49 | 20.25 | 139.50 | 394.67 | 992.53 | 21.66 | 285.50 | 354.67 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1823.91 | 20.30 | 162.67 | 401.83 | 1023.05 | 21.71 | 279.50 | 356.17 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:19 | 2149.77 | 20.80 | 201.33 | 378.33 | 1176.85 | 22.19 | 290.83 | 338.33 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3037.97 | 22.24 | 174.83 | 325.67 | 1532.12 | 22.84 | 256.50 | 292.67 |
October | 314.33 | 0.49 | 0.48 | 01-OCT-07:19 | 6416.85 | 32.63 | 283.33 | 298.83 | 1558.11 | 23.31 | 230.67 | 276.83 |
November | 258.33 | 0.50 | 0.48 | 01-NOV-07:40 | 4168.44 | 32.78 | 243.50 | 241.50 | 1668.95 | 28.44 | 232.33 | 217.00 |
December | 230.67 | 0.49 | 0.48 | 01-DEC-08:09 | 3740.64 | 32.03 | 219.50 | 239.50 | 2890.37 | 33.26 | 227.00 | 208.00 |
Annual Sum or Average | 3928.50 | 0.50 | 3553.59 | 25.57 | 2456.83 | 3848.33 | 1541.73 | 24.29 | 3010.50 | 3445.50 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1743.49 | 20.25 | 119.33 | 239.50 | 992.53 | 21.66 | 227.00 | 208.00 | |
Maximum of Months | 439.00 | 0.50 | 0.48 | 7928.68 | 33.10 | 283.33 | 401.83 | 3523.72 | 33.90 | 290.83 | 356.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:09 | 1545.78 | 23.03 | 97.00 | 238.00 | 763.99 | 23.03 | 135.83 | 190.33 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:39 | 2133.33 | 24.04 | 129.83 | 248.83 | 1095.46 | 24.24 | 175.83 | 218.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:19 | 2893.60 | 24.69 | 147.00 | 321.33 | 1251.40 | 24.00 | 191.67 | 287.67 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:30 | 3129.52 | 24.13 | 139.00 | 352.00 | 1749.58 | 24.63 | 219.17 | 318.33 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:30 | 4151.88 | 24.83 | 108.33 | 394.00 | 1755.13 | 24.12 | 211.50 | 350.50 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3779.99 | 24.08 | 142.50 | 404.50 | 1656.21 | 23.85 | 230.17 | 374.67 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-04:00 | 3580.14 | 24.28 | 146.17 | 411.50 | 1567.59 | 23.85 | 247.33 | 374.67 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:49 | 3328.10 | 24.56 | 151.00 | 381.00 | 1461.57 | 24.07 | 258.50 | 347.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3361.73 | 25.07 | 124.17 | 326.33 | 1831.96 | 25.31 | 205.17 | 289.33 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-06:00 | 2159.24 | 23.95 | 125.50 | 290.67 | 1140.43 | 24.11 | 185.50 | 256.50 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:40 | 1554.74 | 23.28 | 105.33 | 231.67 | 843.53 | 23.45 | 137.33 | 179.50 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-07:00 | 1339.82 | 22.86 | 89.83 | 227.00 | 666.70 | 23.06 | 124.33 | 175.17 |
Annual Sum or Average | 3928.50 | 0.50 | 2899.16 | 24.14 | 1505.67 | 3826.83 | 1373.11 | 24.01 | 2322.33 | 3362.67 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1339.82 | 22.86 | 89.83 | 227.00 | 666.70 | 23.03 | 124.33 | 175.17 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 4151.88 | 25.07 | 151.00 | 411.50 | 1831.96 | 25.31 | 258.50 | 374.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-10:09 | 675.95 | 17.63 | 0.00 | 222.50 | 376.23 | 19.04 | 0.50 | 142.33 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:20 | 887.79 | 18.62 | 0.00 | 243.00 | 491.89 | 19.96 | 48.83 | 194.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 945.30 | 19.13 | 0.00 | 315.67 | 551.73 | 20.56 | 84.67 | 267.33 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 1095.02 | 19.63 | 6.67 | 350.83 | 639.04 | 20.95 | 171.83 | 316.67 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:00 | 1314.37 | 21.69 | 90.00 | 402.83 | 789.95 | 22.88 | 249.67 | 363.33 |
June | 430.67 | 0.49 | 0.48 | 01-JUN-05:00 | 1462.21 | 23.01 | 173.50 | 413.33 | 822.76 | 22.17 | 308.33 | 385.17 |
July | 439.00 | 0.49 | 0.48 | 01-JUL-05:19 | 1391.56 | 22.69 | 158.83 | 419.50 | 808.59 | 22.98 | 313.67 | 389.17 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:00 | 1234.54 | 20.33 | 57.50 | 388.00 | 729.18 | 21.67 | 268.00 | 354.00 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 1038.23 | 19.85 | 1.17 | 322.50 | 638.49 | 21.28 | 147.83 | 273.67 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:40 | 827.60 | 18.39 | 0.00 | 282.33 | 474.32 | 19.81 | 33.33 | 225.17 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:20 | 655.42 | 17.08 | 0.00 | 218.50 | 363.17 | 18.41 | 1.50 | 130.33 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-11:00 | 678.92 | 17.56 | 0.00 | 208.17 | 369.54 | 18.88 | 1.50 | 121.33 |
Annual Sum or Average | 3928.50 | 0.50 | 1068.46 | 19.98 | 487.67 | 3787.17 | 618.57 | 20.97 | 1629.67 | 3162.83 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 655.42 | 17.08 | 0.00 | 208.17 | 363.17 | 18.41 | 0.50 | 121.33 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 1462.21 | 23.01 | 173.50 | 419.50 | 822.76 | 22.98 | 313.67 | 389.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:50 | 1450.50 | 23.30 | 105.00 | 237.50 | 781.71 | 23.62 | 142.00 | 191.50 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-10:09 | 1994.06 | 23.88 | 126.83 | 249.17 | 1046.13 | 24.22 | 177.00 | 218.33 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-08:09 | 2842.91 | 24.52 | 143.17 | 324.17 | 1598.40 | 24.93 | 203.50 | 289.33 |
April | 371.17 | 0.50 | 0.48 | 01-APR-07:10 | 3328.04 | 23.25 | 131.17 | 347.83 | 1402.88 | 22.80 | 193.33 | 314.83 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-06:30 | 3578.51 | 21.19 | 52.17 | 392.50 | 1958.75 | 21.25 | 175.83 | 355.67 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:19 | 3767.46 | 20.99 | 64.00 | 402.67 | 1614.32 | 21.23 | 214.83 | 371.50 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:10 | 3367.44 | 21.01 | 74.83 | 408.83 | 1522.14 | 21.35 | 218.33 | 373.00 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-06:30 | 3156.61 | 22.56 | 119.17 | 384.17 | 1697.89 | 23.18 | 234.67 | 349.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3485.23 | 24.81 | 116.67 | 323.50 | 1508.91 | 23.99 | 197.67 | 291.83 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:49 | 2026.91 | 23.74 | 125.50 | 289.83 | 1063.88 | 24.02 | 181.83 | 255.83 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-08:20 | 1487.39 | 22.86 | 102.50 | 230.50 | 784.38 | 23.02 | 134.17 | 184.00 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-11:39 | 1396.86 | 22.82 | 91.33 | 223.50 | 731.65 | 23.21 | 129.17 | 175.33 |
Annual Sum or Average | 3928.50 | 0.50 | 2804.12 | 22.76 | 1252.33 | 3814.17 | 1370.18 | 22.93 | 2202.33 | 3370.67 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1396.86 | 20.99 | 52.17 | 223.50 | 731.65 | 21.23 | 129.17 | 175.33 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 3767.46 | 24.81 | 143.17 | 408.83 | 1958.75 | 24.93 | 234.67 | 373.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.49 | 0.48 | 01-JAN-08:00 | 4435.75 | 32.12 | 233.00 | 251.50 | 3611.30 | 33.12 | 231.83 | 226.17 |
February | 262.50 | 0.49 | 0.48 | 01-FEB-09:39 | 5578.25 | 32.40 | 241.33 | 256.83 | 1934.82 | 24.28 | 106.33 | 239.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:30 | 7974.67 | 28.59 | 228.50 | 327.67 | 1584.66 | 18.07 | 11.33 | 297.17 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 2141.69 | 14.09 | 0.00 | 347.67 | 1244.90 | 17.54 | 1.33 | 317.33 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:30 | 1966.89 | 14.42 | 0.00 | 385.67 | 1199.75 | 17.95 | 0.00 | 343.50 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1772.96 | 14.29 | 0.00 | 394.83 | 1059.34 | 17.75 | 0.00 | 360.00 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:00 | 1853.17 | 14.23 | 0.00 | 402.83 | 1091.64 | 17.69 | 0.00 | 362.17 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:10 | 2180.57 | 14.62 | 0.00 | 378.33 | 1255.74 | 18.06 | 0.67 | 342.33 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3083.52 | 16.27 | 17.00 | 326.00 | 1640.50 | 18.60 | 7.17 | 295.67 |
October | 314.33 | 0.49 | 0.48 | 01-OCT-07:10 | 6449.09 | 31.60 | 269.67 | 299.00 | 1745.40 | 18.81 | 25.33 | 279.33 |
November | 258.33 | 0.50 | 0.48 | 01-NOV-07:40 | 4179.28 | 32.08 | 237.33 | 241.50 | 2030.10 | 27.51 | 160.50 | 220.17 |
December | 230.67 | 0.49 | 0.48 | 01-DEC-07:00 | 3738.53 | 30.70 | 203.67 | 239.50 | 2970.83 | 32.59 | 216.00 | 210.50 |
Annual Sum or Average | 3928.50 | 0.50 | 3582.46 | 21.58 | 1430.50 | 3851.33 | 1656.03 | 20.90 | 760.50 | 3493.83 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1772.96 | 14.09 | 0.00 | 239.50 | 1059.34 | 17.54 | 0.00 | 210.50 | |
Maximum of Months | 439.00 | 0.50 | 0.48 | 7974.67 | 32.40 | 269.67 | 402.83 | 3611.30 | 33.12 | 231.83 | 362.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-08:00 | 1571.55 | 20.20 | 70.17 | 239.00 | 801.18 | 20.89 | 66.67 | 196.50 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:39 | 2170.24 | 21.37 | 83.00 | 250.00 | 1144.30 | 22.16 | 70.00 | 221.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:19 | 2944.56 | 22.02 | 115.33 | 321.67 | 1312.51 | 21.66 | 61.50 | 291.17 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:19 | 3162.35 | 20.39 | 104.00 | 352.00 | 1820.78 | 22.35 | 87.50 | 321.83 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:30 | 4205.63 | 21.89 | 103.50 | 395.17 | 1841.06 | 21.51 | 55.83 | 353.83 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3828.26 | 21.15 | 132.67 | 405.00 | 1735.49 | 21.28 | 75.83 | 377.50 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-04:00 | 3627.44 | 21.36 | 135.83 | 412.83 | 1645.72 | 21.29 | 75.50 | 377.67 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:49 | 3380.42 | 21.62 | 122.67 | 382.17 | 1535.91 | 21.51 | 67.33 | 351.33 |
September | 289.17 | 0.49 | 0.48 | 01-SEP-07:40 | 3423.63 | 22.24 | 86.50 | 326.83 | 1908.08 | 23.06 | 63.17 | 293.33 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-06:00 | 2200.27 | 21.17 | 91.67 | 291.83 | 1192.56 | 21.96 | 65.83 | 260.83 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:40 | 1579.49 | 20.59 | 86.83 | 232.67 | 878.82 | 21.49 | 73.83 | 185.67 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-07:00 | 1358.33 | 19.48 | 59.67 | 227.67 | 699.37 | 21.01 | 60.83 | 180.67 |
Annual Sum or Average | 3928.50 | 0.50 | 2941.88 | 21.19 | 1191.83 | 3836.83 | 1437.18 | 21.67 | 823.83 | 3411.83 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1358.33 | 19.48 | 59.67 | 227.67 | 699.37 | 20.89 | 55.83 | 180.67 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 4205.63 | 22.24 | 135.83 | 412.83 | 1908.08 | 23.06 | 87.50 | 377.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-09:00 | 683.53 | 11.40 | 0.00 | 222.83 | 399.33 | 14.92 | 0.00 | 153.17 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:09 | 899.64 | 12.75 | 0.00 | 243.00 | 522.40 | 16.11 | 0.00 | 201.00 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:00 | 959.79 | 13.47 | 0.00 | 316.50 | 587.03 | 16.92 | 0.00 | 273.33 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 1113.32 | 14.03 | 0.00 | 351.00 | 680.14 | 17.44 | 0.00 | 321.00 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:00 | 1341.52 | 16.57 | 26.17 | 403.00 | 845.41 | 19.86 | 28.83 | 367.83 |
June | 430.67 | 0.49 | 0.48 | 01-JUN-05:00 | 1489.62 | 18.33 | 74.33 | 413.67 | 906.31 | 19.95 | 41.33 | 391.50 |
July | 439.00 | 0.49 | 0.48 | 01-JUL-05:19 | 1416.63 | 17.96 | 71.00 | 419.83 | 860.56 | 19.70 | 45.00 | 391.33 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:00 | 1255.96 | 14.76 | 0.00 | 388.33 | 775.94 | 18.23 | 2.67 | 357.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 1056.95 | 14.70 | 0.00 | 322.83 | 680.28 | 18.15 | 0.00 | 279.33 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:40 | 839.02 | 12.56 | 0.00 | 282.83 | 504.16 | 16.00 | 0.00 | 235.17 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:09 | 662.80 | 10.93 | 0.00 | 218.83 | 385.52 | 14.31 | 0.00 | 140.33 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-11:50 | 686.45 | 11.27 | 0.00 | 209.17 | 392.07 | 14.73 | 0.00 | 132.17 |
Annual Sum or Average | 3928.50 | 0.50 | 1086.26 | 14.49 | 171.50 | 3791.83 | 661.79 | 17.53 | 117.83 | 3243.67 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 662.80 | 10.93 | 0.00 | 209.17 | 385.52 | 14.31 | 0.00 | 132.17 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 1489.62 | 18.33 | 74.33 | 419.83 | 906.31 | 19.95 | 45.00 | 391.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:39 | 1473.48 | 20.84 | 85.17 | 238.83 | 814.71 | 21.76 | 76.17 | 196.17 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-10:09 | 2029.49 | 21.18 | 81.67 | 249.50 | 1093.24 | 22.15 | 68.83 | 221.67 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:00 | 2871.65 | 21.00 | 101.67 | 325.00 | 1661.88 | 22.81 | 85.83 | 293.50 |
April | 371.17 | 0.50 | 0.48 | 01-APR-07:10 | 3380.06 | 20.18 | 104.33 | 349.33 | 1470.85 | 20.09 | 49.33 | 318.67 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-06:30 | 3617.56 | 17.24 | 43.00 | 393.50 | 2044.84 | 17.88 | 0.00 | 359.00 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:19 | 3816.63 | 17.00 | 52.50 | 403.50 | 1698.03 | 17.84 | 0.00 | 373.83 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:00 | 3415.10 | 17.08 | 54.50 | 409.67 | 1599.53 | 18.06 | 3.67 | 376.50 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-06:30 | 3205.06 | 19.16 | 85.17 | 384.67 | 1771.95 | 20.49 | 53.67 | 353.17 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3509.63 | 21.92 | 84.67 | 324.33 | 1584.33 | 21.45 | 41.67 | 294.67 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:49 | 2064.11 | 20.91 | 89.50 | 290.83 | 1113.02 | 21.83 | 64.33 | 260.67 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-08:09 | 1511.11 | 20.32 | 87.00 | 231.17 | 818.10 | 21.05 | 68.67 | 190.17 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-11:39 | 1419.85 | 20.15 | 63.67 | 225.17 | 764.60 | 21.21 | 66.17 | 179.00 |
Annual Sum or Average | 3928.50 | 0.50 | 2842.08 | 19.50 | 932.83 | 3825.50 | 1433.77 | 20.32 | 578.33 | 3417.00 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1419.85 | 17.00 | 43.00 | 225.17 | 764.60 | 17.84 | 0.00 | 179.00 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 3816.63 | 21.92 | 104.33 | 409.67 | 2044.84 | 22.81 | 85.83 | 376.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.49 | 0.48 | 01-JAN-08:00 | 4437.52 | 32.11 | 233.00 | 251.50 | 3613.53 | 33.11 | 231.83 | 226.33 |
February | 262.50 | 0.49 | 0.48 | 01-FEB-09:39 | 5581.26 | 32.39 | 241.33 | 256.83 | 1937.72 | 24.27 | 106.33 | 239.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:30 | 7978.04 | 28.58 | 228.33 | 327.67 | 1586.98 | 18.06 | 11.17 | 297.17 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 2144.89 | 14.06 | 0.00 | 347.67 | 1246.85 | 17.52 | 1.17 | 317.67 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:30 | 1969.46 | 14.39 | 0.00 | 385.67 | 1201.38 | 17.94 | 0.00 | 343.67 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1775.35 | 14.26 | 0.00 | 394.83 | 1060.86 | 17.74 | 0.00 | 360.17 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:00 | 1855.78 | 14.20 | 0.00 | 402.83 | 1093.26 | 17.68 | 0.00 | 362.17 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:10 | 2183.84 | 14.59 | 0.00 | 378.33 | 1257.73 | 18.05 | 0.67 | 342.33 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3087.24 | 16.24 | 17.00 | 326.00 | 1642.96 | 18.58 | 7.00 | 295.67 |
October | 314.33 | 0.49 | 0.48 | 01-OCT-07:10 | 6451.90 | 31.59 | 269.67 | 299.00 | 1841.00 | 19.07 | 28.83 | 279.33 |
November | 258.33 | 0.50 | 0.48 | 01-NOV-07:40 | 4181.22 | 32.07 | 237.33 | 241.50 | 2298.75 | 29.22 | 186.50 | 220.50 |
December | 230.67 | 0.49 | 0.48 | 01-DEC-07:00 | 3740.25 | 30.69 | 203.67 | 239.50 | 2973.05 | 32.59 | 216.00 | 210.67 |
Annual Sum or Average | 3928.50 | 0.50 | 3585.21 | 21.56 | 1430.33 | 3851.33 | 1683.07 | 21.02 | 789.50 | 3495.17 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1775.35 | 14.06 | 0.00 | 239.50 | 1060.86 | 17.52 | 0.00 | 210.67 | |
Maximum of Months | 439.00 | 0.50 | 0.48 | 7978.04 | 32.39 | 269.67 | 402.83 | 3613.53 | 33.11 | 231.83 | 362.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-08:00 | 1572.86 | 20.17 | 70.17 | 239.00 | 802.33 | 20.87 | 66.33 | 196.67 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:39 | 2172.13 | 21.34 | 83.00 | 250.00 | 1145.84 | 22.15 | 69.83 | 221.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:19 | 2916.41 | 21.00 | 103.17 | 321.83 | 1314.00 | 21.65 | 61.50 | 291.33 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:19 | 3164.34 | 20.36 | 104.00 | 352.17 | 1822.43 | 22.33 | 87.50 | 322.00 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:30 | 4207.62 | 21.86 | 103.50 | 395.33 | 1842.81 | 21.50 | 55.83 | 353.83 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3830.38 | 21.12 | 132.67 | 405.00 | 1737.25 | 21.26 | 75.83 | 377.50 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-04:00 | 3629.52 | 21.34 | 135.83 | 412.83 | 1647.45 | 21.27 | 75.50 | 377.67 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:49 | 3382.59 | 21.59 | 122.67 | 382.17 | 1537.72 | 21.50 | 67.33 | 351.50 |
September | 289.17 | 0.49 | 0.48 | 01-SEP-07:40 | 3425.42 | 22.21 | 86.50 | 326.83 | 1909.88 | 23.05 | 63.17 | 293.67 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-06:00 | 2201.84 | 21.14 | 91.50 | 291.83 | 1193.91 | 21.95 | 65.83 | 260.83 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:40 | 1580.79 | 20.57 | 86.83 | 232.67 | 879.91 | 21.48 | 73.33 | 186.00 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-07:00 | 1359.72 | 19.45 | 59.67 | 228.00 | 700.49 | 21.00 | 60.67 | 180.67 |
Annual Sum or Average | 3928.50 | 0.50 | 2941.13 | 21.07 | 1179.50 | 3837.67 | 1438.74 | 21.66 | 822.67 | 3413.17 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1359.72 | 19.45 | 59.67 | 228.00 | 700.49 | 20.87 | 55.83 | 180.67 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 4207.62 | 22.21 | 135.83 | 412.83 | 1909.88 | 23.05 | 87.50 | 377.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-09:00 | 684.39 | 11.37 | 0.00 | 223.33 | 399.97 | 14.91 | 0.00 | 153.50 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:09 | 900.82 | 12.72 | 0.00 | 243.17 | 523.24 | 16.10 | 0.00 | 201.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:00 | 960.85 | 13.44 | 0.00 | 316.67 | 587.86 | 16.91 | 0.00 | 273.50 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 1114.58 | 14.00 | 0.00 | 351.00 | 681.10 | 17.42 | 0.00 | 321.50 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:00 | 1342.63 | 16.54 | 26.17 | 403.00 | 846.41 | 19.85 | 28.67 | 368.00 |
June | 430.67 | 0.49 | 0.48 | 01-JUN-05:00 | 1491.05 | 18.31 | 74.33 | 413.67 | 907.48 | 19.94 | 40.50 | 391.50 |
July | 439.00 | 0.49 | 0.48 | 01-JUL-05:19 | 1418.06 | 17.93 | 71.00 | 419.83 | 861.70 | 19.69 | 44.50 | 391.33 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:00 | 1257.28 | 14.73 | 0.00 | 388.33 | 776.99 | 18.21 | 2.17 | 357.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 1057.81 | 14.66 | 0.00 | 322.83 | 681.12 | 18.13 | 0.00 | 279.67 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:40 | 839.99 | 12.53 | 0.00 | 283.00 | 504.91 | 15.98 | 0.00 | 235.50 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:09 | 663.66 | 10.90 | 0.00 | 219.00 | 386.14 | 14.30 | 0.00 | 141.17 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-11:50 | 687.38 | 11.24 | 0.00 | 209.67 | 392.73 | 14.71 | 0.00 | 132.17 |
Annual Sum or Average | 3928.50 | 0.50 | 1087.41 | 14.46 | 171.50 | 3793.50 | 662.70 | 17.51 | 115.83 | 3246.67 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 663.66 | 10.90 | 0.00 | 209.67 | 386.14 | 14.30 | 0.00 | 132.17 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 1491.05 | 18.31 | 74.33 | 419.83 | 907.48 | 19.94 | 44.50 | 391.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:39 | 1474.79 | 20.81 | 85.17 | 238.83 | 815.80 | 21.75 | 76.17 | 196.33 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-10:09 | 2031.36 | 21.16 | 81.67 | 249.50 | 1094.79 | 22.14 | 68.17 | 222.00 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:00 | 2873.40 | 20.98 | 101.67 | 325.00 | 1663.40 | 22.79 | 85.83 | 293.67 |
April | 371.17 | 0.50 | 0.48 | 01-APR-07:10 | 3382.09 | 20.16 | 104.33 | 349.33 | 1472.51 | 20.08 | 49.33 | 318.67 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-06:30 | 3619.45 | 17.21 | 43.00 | 393.67 | 2046.55 | 17.86 | 0.00 | 359.00 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:19 | 3818.73 | 16.96 | 52.50 | 403.83 | 1699.87 | 17.83 | 0.00 | 373.83 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:00 | 3417.29 | 17.04 | 54.50 | 409.83 | 1601.33 | 18.04 | 3.67 | 376.83 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-06:30 | 3207.33 | 19.13 | 85.00 | 384.67 | 1773.81 | 20.48 | 53.67 | 353.17 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3511.36 | 21.89 | 84.67 | 324.33 | 1586.00 | 21.43 | 41.67 | 294.83 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:49 | 2065.73 | 20.89 | 89.50 | 290.83 | 1114.40 | 21.82 | 64.00 | 260.67 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-08:09 | 1512.42 | 20.30 | 87.00 | 231.17 | 819.17 | 21.04 | 68.17 | 190.17 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-11:39 | 1421.24 | 20.13 | 63.67 | 225.17 | 765.74 | 21.19 | 66.17 | 179.00 |
Annual Sum or Average | 3928.50 | 0.50 | 2843.93 | 19.48 | 932.67 | 3826.17 | 1435.34 | 20.31 | 576.83 | 3418.17 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1421.24 | 16.96 | 43.00 | 225.17 | 765.74 | 17.83 | 0.00 | 179.00 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 3818.73 | 21.89 | 104.33 | 409.83 | 2046.55 | 22.79 | 85.83 | 376.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 88696771.72 | 5909.00 | 17-JAN-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161028E+09 | 15758.37 | 24-FEB-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204478E+09 | 13904.91 | 27-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89874669.38 | 15045.67 | 03-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8651768.24 | 2151.10 | 12-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 136.46 | 0.16 | 20-AUG-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2025505.29 | 2237.40 | 06-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 62852851.17 | 11278.36 | 24-OCT-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144369E+09 | 11908.83 | 15-NOV-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.202817E+09 | 16186.16 | 12-DEC-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.964793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204478E+09 | 16186.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108739E+10 | 14242.80 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.706738E+09 | 14251.13 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113882E+09 | 14327.34 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.314745E+09 | 14333.29 | 08-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108739E+10 | 14333.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.715366E+09 | 14632.70 | 03-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.538999E+09 | 14656.06 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69242323.34 | 14670.86 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5039267.10 | 1192.79 | 25-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.431257E+09 | 14733.15 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.715366E+09 | 14733.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.130523E+10 | 20204.43 | 19-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103218E+10 | 20191.16 | 16-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155954E+09 | 20186.72 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6796928.37 | 7691.41 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7388784.48 | 10308.12 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28692049.94 | 16920.88 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.647101E+09 | 20283.95 | 04-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130523E+10 | 20283.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.174097E+09 | 13164.64 | 12-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46975394.98 | 13158.51 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174097E+09 | 13164.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.883267E+10 | 454388.53 | 04-JAN-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.801982E+10 | 542156.80 | 28-FEB-09:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.412792E+10 | 591648.70 | 24-MAR-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169034E+10 | 253408.16 | 25-APR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111823E+10 | 247789.83 | 11-MAY-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170617E+09 | 237326.01 | 13-JUN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 762.00 | 1.27 | 24-AUG-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109018E+09 | 74005.99 | 29-SEP-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174645E+10 | 227807.52 | 27-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182111E+10 | 202056.10 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.677242E+10 | 350864.97 | 28-DEC-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.883267E+10 | 591648.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.197993E+11 | 504977.37 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.588693E+10 | 503634.08 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5612255.79 | 4676.97 | 06-MAR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.402004E+10 | 503874.90 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197993E+11 | 504977.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.726726E+11 | 124561.44 | 03-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.588933E+11 | 124334.39 | 21-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217680E+11 | 123760.13 | 21-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.250210E+10 | 123544.91 | 17-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.207207E+10 | 124742.12 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105810E+11 | 123808.16 | 29-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.586568E+11 | 123872.87 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227146E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.726726E+11 | 124742.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.391351E+11 | 180151.50 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311181E+11 | 180173.02 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.801676E+10 | 179676.58 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.913662E+09 | 179532.56 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 157806.04 | 374.20 | 30-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.939292E+09 | 179513.01 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.575594E+10 | 179772.89 | 24-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.340733E+11 | 180145.92 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119952E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.391351E+11 | 180173.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.457050E+11 | 207898.48 | 02-JAN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.367698E+11 | 207605.95 | 02-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.833841E+10 | 206651.55 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165255E+10 | 205277.30 | 17-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.890530E+09 | 205347.52 | 17-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.618364E+10 | 206546.36 | 24-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.391296E+11 | 207612.32 | 20-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138670E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.457050E+11 | 207898.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.363113E+11 | 182160.74 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272136E+11 | 182181.17 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.630233E+10 | 181508.03 | 04-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.507141E+09 | 180997.17 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.575243E+09 | 181110.96 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.382537E+10 | 181082.01 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273332E+11 | 182155.44 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102068E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.363113E+11 | 182181.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.311802E+10 | 11710.69 | 30-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.274101E+10 | 15530.22 | 06-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.662332E+09 | 11067.90 | 07-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74323470.86 | 5894.17 | 20-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23339239.61 | 5157.65 | 12-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3949897.74 | 2819.71 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7398348.18 | 3846.98 | 12-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 45959701.00 | 7047.10 | 31-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 47265580.18 | 2671.04 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234835E+10 | 15338.97 | 11-DEC-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.907195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.311802E+10 | 15530.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129456E+11 | 72471.37 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103713E+11 | 72420.06 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.364288E+10 | 72276.65 | 20-MAR-04:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.498973E+09 | 72115.03 | 17-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.586253E+09 | 72496.17 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.233641E+10 | 72800.21 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104414E+11 | 72419.55 | 09-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.408228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129456E+11 | 72800.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.119077E+11 | 14166.76 | 03-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100988E+11 | 14164.38 | 03-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.507159E+10 | 14164.63 | 03-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128582E+10 | 14160.81 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 58480494.94 | 14111.97 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45005557.77 | 14082.30 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129010E+10 | 14175.83 | 30-OCT-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.368369E+10 | 14168.71 | 14-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106878E+11 | 14197.67 | 15-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119077E+11 | 14197.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.704617E+10 | 19811.07 | 18-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.588303E+10 | 19835.22 | 03-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224872E+10 | 19761.67 | 04-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.522058E+09 | 19748.10 | 05-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18419677.19 | 16103.16 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19469745.30 | 12351.08 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.602997E+09 | 19756.71 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211039E+10 | 19851.97 | 13-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.678021E+10 | 19832.38 | 22-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.704617E+10 | 19851.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.832763E+10 | 22501.69 | 03-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.721103E+10 | 22453.52 | 03-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271305E+10 | 22449.38 | 20-MAR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.925740E+09 | 22351.46 | 17-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62178941.89 | 15559.81 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1015592.92 | 739.45 | 14-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25916779.21 | 12011.24 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.701910E+09 | 22503.93 | 16-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248243E+10 | 22493.60 | 29-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.801353E+10 | 22450.18 | 22-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.832763E+10 | 22503.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.634114E+10 | 21019.88 | 12-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.484523E+10 | 21015.66 | 01-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176901E+10 | 21007.48 | 04-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.382631E+09 | 20924.68 | 05-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5895161.05 | 1056.29 | 12-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12417377.03 | 3177.46 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.414143E+09 | 20921.35 | 17-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145781E+10 | 20979.12 | 21-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.511637E+10 | 20962.48 | 06-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.634114E+10 | 21019.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156980E+11 | 30758.25 | 30-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137322E+11 | 35419.32 | 07-FEB-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.463949E+10 | 26017.45 | 06-MAR-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217298E+09 | 15964.98 | 17-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1207839.21 | 2478.33 | 04-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 423.29 | 0.42 | 03-JUN-06:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32.79 | 0.38 | 14-JUL-06:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 212.26 | 0.34 | 24-AUG-06:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 247.33 | 0.76 | 29-SEP-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9370407.36 | 9216.77 | 17-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250877E+09 | 11280.15 | 22-NOV-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.739109E+10 | 29949.99 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.419395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 32.79 | 0.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156980E+11 | 35419.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3459758.71 | 3459758.71 | 3330.18 | 17-JAN-17:05 | 3330.18 | 0.00 |
February | 0.00 | 0.00 | 24985500.29 | 24985500.29 | 3700.45 | 22-FEB-13:20 | 3700.45 | 0.00 |
March | 0.00 | 0.00 | 0.770629E+10 | 0.753467E+10 | 101035.55 | 14-MAR-13:05 | 86060.14 | 0.05 |
April | 0.00 | 0.00 | 0.446168E+10 | 0.446168E+10 | 49312.62 | 07-APR-14:00 | 49312.62 | 0.02 |
May | 0.00 | 0.00 | 0.174544E+11 | 0.172592E+11 | 95321.44 | 24-MAY-05:02 | 65390.78 | 0.15 |
June | 0.00 | 0.00 | 0.808469E+11 | 0.643671E+11 | 242811.38 | 27-JUN-07:50 | 104767.55 | 0.51 |
July | 0.00 | 0.00 | 0.149173E+12 | 0.107748E+12 | 294539.05 | 21-JUL-05:02 | 118890.30 | 0.77 |
August | 0.00 | 0.00 | 0.124921E+12 | 0.978560E+11 | 266881.67 | 15-AUG-08:20 | 115447.75 | 0.75 |
September | 0.00 | 0.00 | 0.479276E+11 | 0.382648E+11 | 196816.25 | 14-SEP-04:12 | 85469.71 | 0.41 |
October | 0.00 | 0.00 | 0.948484E+10 | 0.948157E+10 | 75286.49 | 11-OCT-14:50 | 75286.49 | 0.11 |
November | 0.00 | 0.00 | 0.423613E+10 | 0.423613E+10 | 51327.85 | 27-NOV-06:03 | 51327.85 | 0.05 |
December | 0.00 | 0.00 | 0.122076E+09 | 0.122076E+09 | 10162.44 | 04-DEC-14:50 | 10162.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.446362E+12 | 0.351360E+12 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 3459758.71 | 3459758.71 | 3330.18 | 3330.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.149173E+12 | 0.107748E+12 | 294539.05 | 118890.30 | 0.77 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 5686099.32 | 5686099.32 | 3500.23 | 11-JAN-15:10 | 3500.23 | 0.00 |
February | 0.00 | 0.00 | 38586832.67 | 38586832.67 | 9211.79 | 28-FEB-15:10 | 9211.79 | 0.00 |
March | 0.00 | 0.00 | 0.385120E+11 | 0.374167E+11 | 734603.47 | 15-MAR-14:05 | 734603.47 | 0.06 |
April | 0.00 | 0.00 | 0.381293E+11 | 0.381293E+11 | 463771.77 | 07-APR-13:10 | 463771.77 | 0.02 |
May | 0.00 | 0.00 | 0.155614E+12 | 0.154128E+12 | 850911.71 | 24-MAY-05:02 | 575715.86 | 0.15 |
June | 0.00 | 0.00 | 0.610348E+12 | 0.497592E+12 | 1632493.60 | 27-JUN-05:03 | 705436.46 | 0.46 |
July | 0.00 | 0.00 | 0.102918E+13 | 0.770181E+12 | 2250860.42 | 20-JUL-05:03 | 907944.32 | 0.60 |
August | 0.00 | 0.00 | 0.856364E+12 | 0.698812E+12 | 2396710.64 | 14-AUG-05:03 | 909760.36 | 0.58 |
September | 0.00 | 0.00 | 0.388309E+12 | 0.318492E+12 | 1538580.56 | 16-SEP-05:02 | 709693.90 | 0.40 |
October | 0.00 | 0.00 | 0.703791E+11 | 0.703545E+11 | 605441.38 | 11-OCT-15:00 | 605441.38 | 0.11 |
November | 0.00 | 0.00 | 0.877950E+10 | 0.877950E+10 | 231840.88 | 16-NOV-13:05 | 231840.88 | 0.04 |
December | 0.00 | 0.00 | 31698071.39 | 31698071.39 | 7967.15 | 04-DEC-11:10 | 7967.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.319569E+13 | 0.259396E+13 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 5686099.32 | 5686099.32 | 3500.23 | 3500.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102918E+13 | 0.770181E+12 | 2396710.64 | 909760.36 | 0.60 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 861254.08 | 861254.08 | 188.21 | 02-JAN-07:03 | 188.21 | 0.01 |
February | 0.00 | 0.00 | 3543274.83 | 3543274.83 | 847.35 | 28-FEB-15:00 | 847.35 | 0.00 |
March | 0.00 | 0.00 | 0.375378E+10 | 0.375268E+10 | 87230.94 | 15-MAR-14:20 | 87230.94 | 0.06 |
April | 0.00 | 0.00 | 0.140052E+10 | 0.140052E+10 | 32239.37 | 07-APR-14:00 | 32239.37 | 0.02 |
May | 0.00 | 0.00 | 0.147617E+11 | 0.146546E+11 | 100154.93 | 14-MAY-15:02 | 88011.92 | 0.14 |
June | 0.00 | 0.00 | 0.665018E+11 | 0.540228E+11 | 167083.73 | 27-JUN-05:03 | 71724.76 | 0.46 |
July | 0.00 | 0.00 | 0.114689E+12 | 0.859911E+11 | 234515.75 | 21-JUL-05:02 | 146919.49 | 0.60 |
August | 0.00 | 0.00 | 0.932509E+11 | 0.756916E+11 | 254014.00 | 14-AUG-05:03 | 96436.88 | 0.57 |
September | 0.00 | 0.00 | 0.375945E+11 | 0.306849E+11 | 158358.88 | 15-SEP-13:10 | 86958.49 | 0.39 |
October | 0.00 | 0.00 | 0.418650E+10 | 0.418650E+10 | 57124.43 | 11-OCT-15:00 | 57124.43 | 0.10 |
November | 0.00 | 0.00 | 0.487509E+09 | 0.487509E+09 | 11950.20 | 16-NOV-13:00 | 11950.20 | 0.04 |
December | 0.00 | 0.00 | 3624892.55 | 3624892.55 | 817.35 | 01-DEC-13:30 | 817.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.336634E+12 | 0.270880E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 861254.08 | 861254.08 | 188.21 | 188.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114689E+12 | 0.859911E+11 | 254014.00 | 146919.49 | 0.60 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 34993610.45 | 34993610.45 | 4590.06 | 11-JAN-16:00 | 4590.06 | 0.01 |
February | 0.00 | 0.00 | 33976704.27 | 33976704.27 | 5443.34 | 22-FEB-17:00 | 5443.34 | 0.00 |
March | 0.00 | 0.00 | 0.355343E+10 | 0.354066E+10 | 51107.62 | 15-MAR-14:00 | 51107.62 | 0.04 |
April | 0.00 | 0.00 | 0.207960E+10 | 0.207960E+10 | 24487.29 | 07-APR-13:10 | 24487.29 | 0.02 |
May | 0.00 | 0.00 | 0.111671E+11 | 0.106360E+11 | 82419.11 | 24-MAY-06:11 | 44712.76 | 0.13 |
June | 0.00 | 0.00 | 0.282952E+11 | 0.221672E+11 | 119870.10 | 28-JUN-14:10 | 72119.89 | 0.25 |
July | 0.00 | 0.00 | 0.514019E+11 | 0.376552E+11 | 159991.83 | 29-JUL-10:50 | 61287.37 | 0.29 |
August | 0.00 | 0.00 | 0.549081E+11 | 0.454428E+11 | 131302.27 | 28-AUG-12:05 | 68273.74 | 0.39 |
September | 0.00 | 0.00 | 0.308164E+11 | 0.243200E+11 | 128392.48 | 14-SEP-16:00 | 64325.41 | 0.31 |
October | 0.00 | 0.00 | 0.506104E+10 | 0.471990E+10 | 70290.68 | 26-OCT-06:25 | 33191.01 | 0.10 |
November | 0.00 | 0.00 | 0.819778E+09 | 0.816644E+09 | 53081.31 | 27-NOV-07:11 | 53081.31 | 0.02 |
December | 0.00 | 0.00 | 0.238701E+09 | 0.213400E+09 | 18460.68 | 01-DEC-11:00 | 14671.15 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.188410E+12 | 0.151660E+12 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 33976704.27 | 33976704.27 | 4590.06 | 4590.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.549081E+11 | 0.454428E+11 | 159991.83 | 72119.89 | 0.39 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.654828E+10 | 0.654823E+10 | 3805.06 | 13-JAN-18:00 | 3805.06 | 0.00 |
February | 0.00 | 0.00 | 0.102627E+11 | 0.102524E+11 | 5068.22 | 14-FEB-17:15 | 5068.22 | 0.00 |
March | 0.00 | 0.00 | 0.313903E+11 | 0.283318E+11 | 313113.40 | 14-MAR-13:00 | 254292.27 | 0.00 |
April | 0.00 | 0.00 | 0.364191E+11 | 0.339197E+11 | 234035.32 | 08-APR-14:00 | 212350.20 | 0.00 |
May | 0.00 | 0.00 | 0.719024E+10 | 0.673881E+10 | 123948.14 | 10-MAY-15:00 | 104640.78 | 0.00 |
June | 0.00 | 0.00 | 0.166435E+12 | 0.118295E+12 | 430611.59 | 27-JUN-14:05 | 225146.84 | 0.00 |
July | 0.00 | 0.00 | 0.710033E+12 | 0.441563E+12 | 543491.57 | 20-JUL-22:13 | 191696.43 | 0.00 |
August | 0.00 | 0.00 | 0.825398E+12 | 0.554051E+12 | 527231.79 | 14-AUG-02:53 | 210507.68 | 0.00 |
September | 0.00 | 0.00 | 0.149250E+11 | 0.111504E+11 | 176437.68 | 15-SEP-12:00 | 105546.94 | 0.00 |
October | 0.00 | 0.00 | 0.852388E+10 | 0.820364E+10 | 87652.77 | 11-OCT-15:00 | 81331.30 | 0.00 |
November | 0.00 | 0.00 | 0.172473E+11 | 0.159245E+11 | 104937.91 | 05-NOV-13:55 | 85937.80 | 0.00 |
December | 0.00 | 0.00 | 0.150327E+11 | 0.146498E+11 | 67245.55 | 01-DEC-11:00 | 45080.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184940E+13 | 0.124963E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.654828E+10 | 0.654823E+10 | 3805.06 | 3805.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.825398E+12 | 0.554051E+12 | 543491.57 | 254292.27 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.299648E+10 | 0.299619E+10 | 2197.57 | 15-JAN-16:35 | 2197.57 | 0.00 |
February | 0.00 | 0.00 | 0.767073E+10 | 0.767073E+10 | 4102.65 | 28-FEB-17:00 | 4102.65 | 0.00 |
March | 0.00 | 0.00 | 0.147721E+11 | 0.147509E+11 | 7529.59 | 31-MAR-24:00 | 7529.59 | 0.00 |
April | 0.00 | 0.00 | 0.196934E+11 | 0.196905E+11 | 8726.53 | 02-APR-17:58 | 8726.53 | 0.00 |
May | 0.00 | 0.00 | 0.545954E+10 | 0.542433E+10 | 3995.74 | 31-MAY-24:00 | 3995.74 | 0.00 |
June | 0.00 | 0.00 | 0.107736E+11 | 0.105921E+11 | 5910.76 | 30-JUN-24:00 | 5910.76 | 0.00 |
July | 0.00 | 0.00 | 0.165113E+11 | 0.161971E+11 | 7852.17 | 31-JUL-24:00 | 7816.32 | 0.00 |
August | 0.00 | 0.00 | 0.213447E+11 | 0.211062E+11 | 8711.83 | 14-AUG-18:00 | 8387.04 | 0.00 |
September | 0.00 | 0.00 | 0.558490E+10 | 0.545338E+10 | 3772.22 | 30-SEP-24:00 | 3772.22 | 0.00 |
October | 0.00 | 0.00 | 0.101919E+11 | 0.101612E+11 | 5688.41 | 31-OCT-24:00 | 5688.41 | 0.00 |
November | 0.00 | 0.00 | 0.144396E+11 | 0.144376E+11 | 6010.19 | 12-NOV-15:50 | 6010.19 | 0.00 |
December | 0.00 | 0.00 | 0.193026E+11 | 0.193021E+11 | 7843.08 | 17-DEC-16:10 | 7843.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.148741E+12 | 0.147782E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.299648E+10 | 0.299619E+10 | 2197.57 | 2197.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.213447E+11 | 0.211062E+11 | 8726.53 | 8726.53 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.377535E+10 | 0.377532E+10 | 13407.62 | 15-JAN-16:35 | 13407.62 | 0.00 |
February | 0.00 | 0.00 | 0.472823E+11 | 0.472823E+11 | 35461.92 | 28-FEB-17:00 | 35461.92 | 0.00 |
March | 0.00 | 0.00 | 0.123963E+12 | 0.123752E+12 | 67332.23 | 31-MAR-23:40 | 67332.23 | 0.00 |
April | 0.00 | 0.00 | 0.178005E+12 | 0.177974E+12 | 80242.08 | 02-APR-18:00 | 80242.08 | 0.00 |
May | 0.00 | 0.00 | 0.473024E+11 | 0.469555E+11 | 37849.13 | 31-MAY-24:00 | 37849.13 | 0.00 |
June | 0.00 | 0.00 | 0.100191E+12 | 0.983877E+11 | 56395.53 | 30-JUN-24:00 | 56395.53 | 0.00 |
July | 0.00 | 0.00 | 0.156141E+12 | 0.153012E+12 | 75443.91 | 31-JUL-24:00 | 75095.14 | 0.00 |
August | 0.00 | 0.00 | 0.202247E+12 | 0.199868E+12 | 83356.71 | 04-AUG-18:40 | 83356.71 | 0.00 |
September | 0.00 | 0.00 | 0.484841E+11 | 0.471941E+11 | 32843.92 | 30-SEP-24:00 | 32843.92 | 0.00 |
October | 0.00 | 0.00 | 0.854745E+11 | 0.851683E+11 | 50295.55 | 31-OCT-23:50 | 50295.55 | 0.00 |
November | 0.00 | 0.00 | 0.119225E+12 | 0.119202E+12 | 55219.64 | 15-NOV-16:20 | 55219.64 | 0.00 |
December | 0.00 | 0.00 | 0.152709E+12 | 0.152703E+12 | 68611.47 | 04-DEC-16:20 | 68611.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126480E+13 | 0.125528E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.377535E+10 | 0.377532E+10 | 13407.62 | 13407.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202247E+12 | 0.199868E+12 | 83356.71 | 83356.71 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 54410184.05 | 54410184.05 | 1117.85 | 12-JAN-16:40 | 1117.85 | 0.00 |
February | 0.00 | 0.00 | 0.317684E+10 | 0.317684E+10 | 3503.42 | 28-FEB-17:00 | 3503.42 | 0.00 |
March | 0.00 | 0.00 | 0.108350E+11 | 0.108140E+11 | 6287.37 | 31-MAR-23:20 | 6287.37 | 0.00 |
April | 0.00 | 0.00 | 0.167539E+11 | 0.167509E+11 | 7933.97 | 09-APR-17:57 | 7933.97 | 0.00 |
May | 0.00 | 0.00 | 0.431794E+10 | 0.428354E+10 | 3691.81 | 31-MAY-23:40 | 3691.81 | 0.00 |
June | 0.00 | 0.00 | 0.995500E+10 | 0.977454E+10 | 5570.71 | 30-JUN-23:40 | 5570.71 | 0.00 |
July | 0.00 | 0.00 | 0.156768E+11 | 0.153639E+11 | 7533.45 | 31-JUL-24:00 | 7498.35 | 0.00 |
August | 0.00 | 0.00 | 0.202011E+11 | 0.199635E+11 | 8418.34 | 04-AUG-18:40 | 8418.34 | 0.00 |
September | 0.00 | 0.00 | 0.448202E+10 | 0.435365E+10 | 3030.10 | 04-SEP-17:42 | 3030.10 | 0.00 |
October | 0.00 | 0.00 | 0.719950E+10 | 0.716922E+10 | 4595.88 | 31-OCT-23:20 | 4595.88 | 0.00 |
November | 0.00 | 0.00 | 0.101235E+11 | 0.101214E+11 | 5371.71 | 15-NOV-16:20 | 5371.71 | 0.00 |
December | 0.00 | 0.00 | 0.134200E+11 | 0.134194E+11 | 6524.71 | 04-DEC-16:20 | 6524.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.116196E+12 | 0.115245E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 54410184.05 | 54410184.05 | 1117.85 | 1117.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202011E+11 | 0.199635E+11 | 8418.34 | 8418.34 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 108576.07 | 2065285.24 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 92939.76 | 1715396.62 | 18-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 26048.35 | 1595914.08 | 28-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4332.70 | 1321222.18 | 05-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 492.21 | 283435.71 | 11-MAY-13:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 69.97 | 260352.85 | 13-JUN-11:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.19 | 14-JUL-06:19 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.70 | 24-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 73.03 | 76504.00 | 30-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3699.31 | 1375465.11 | 17-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15673.03 | 1798803.60 | 18-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 82949.60 | 1787167.44 | 02-DEC-05:11 |
Annual Sum or Average | 0.00 | 27620.57 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.19 | ||
Maximum of Months | 0.00 | 0.00 | 108576.07 | 2065285.24 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 57.59 | 5418.31 | 11-JAN-16:50 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 87.28 | 9044.02 | 28-FEB-15:20 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 21634.75 | 1129278.35 | 15-MAR-13:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18456.63 | 548946.55 | 07-APR-13:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 76189.94 | 1243728.33 | 10-MAY-15:50 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 314858.60 | 1973009.62 | 27-JUN-07:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 522541.03 | 2462157.59 | 20-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 438668.66 | 2660431.75 | 14-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 200750.99 | 1845493.73 | 15-SEP-11:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 33993.07 | 781884.39 | 11-OCT-15:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6073.82 | 279461.44 | 16-NOV-13:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 241.26 | 31593.85 | 01-DEC-07:13 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 137259.62 | 0.00 | ||||
Minimum of Months | 57.59 | 5418.31 | 0.00 | 0.00 | ||
Maximum of Months | 522541.03 | 2660431.75 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4.83 | 1971.17 | 11-JAN-16:50 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 22.65 | 5868.92 | 28-FEB-15:10 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 21113.27 | 1128770.97 | 15-MAR-13:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 17727.74 | 552572.79 | 07-APR-13:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74913.17 | 1214878.67 | 10-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 313266.18 | 2924644.81 | 27-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 520794.51 | 3369930.42 | 17-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 439124.70 | 3482200.14 | 14-AUG-04:11 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 201153.75 | 2877993.39 | 16-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 33203.55 | 779958.32 | 11-OCT-15:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5520.31 | 283992.07 | 16-NOV-13:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 137.68 | 40232.73 | 01-DEC-07:12 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 136708.81 | 0.00 | ||||
Minimum of Months | 4.83 | 1971.17 | 0.00 | 0.00 | ||
Maximum of Months | 520794.51 | 3482200.14 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 10501.38 | 27699.98 | 15-JAN-16:40 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 38967.96 | 68995.49 | 28-FEB-09:58 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 98854.26 | 1054498.50 | 15-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 123492.41 | 695836.59 | 08-APR-13:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 55509.40 | 697544.81 | 10-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 300349.54 | 1296880.00 | 27-JUN-14:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 797327.99 | 1646986.23 | 21-JUL-02:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 840927.72 | 1725920.04 | 13-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 104860.60 | 813700.27 | 16-SEP-14:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 59675.16 | 448322.64 | 11-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80599.10 | 343035.82 | 05-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 94570.45 | 180046.63 | 01-DEC-11:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 219310.99 | 0.00 | ||||
Minimum of Months | 10501.38 | 27699.98 | 0.00 | 0.00 | ||
Maximum of Months | 840927.72 | 1725920.04 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 15565.50 | 55761.25 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 15883.48 | 55957.89 | 15-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16653.06 | 55779.68 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14992.81 | 54071.96 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14631.73 | 51559.60 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14076.09 | 48363.91 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12326.76 | 45521.93 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 13253.11 | 44047.86 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12640.60 | 45462.28 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13239.12 | 48280.09 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14277.43 | 51374.95 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14571.55 | 54008.71 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 14333.73 | ||||
Minimum of Months | 0.00 | 0.00 | 12326.76 | 44047.86 | ||
Maximum of Months | 0.00 | 0.00 | 16653.06 | 55957.89 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 11.15 | 12797.80 | 11-JAN-15:10 | 556.75 | 133735.60 | 30-JAN-01:40 |
February | 6.66 | 17142.60 | 22-FEB-16:50 | 656.58 | 124434.91 | 09-FEB-07:03 |
March | 26342.89 | 1857775.20 | 14-MAR-13:20 | 3540.95 | 133444.90 | 23-MAR-15:40 |
April | 16600.81 | 602821.05 | 07-APR-13:20 | 3450.44 | 126977.09 | 17-APR-12:40 |
May | 84061.90 | 2371481.51 | 10-MAY-14:30 | 1631.99 | 103016.94 | 08-MAY-08:30 |
June | 521730.71 | 5146367.75 | 27-JUN-07:40 | 539.84 | 63742.04 | 03-JUN-10:20 |
July | 1051639.69 | 5877217.31 | 05-JUL-16:00 | 302.78 | 53738.38 | 07-JUL-07:00 |
August | 761445.51 | 5578435.05 | 14-AUG-10:05 | 898.47 | 62574.12 | 12-AUG-22:10 |
September | 303595.68 | 4207487.78 | 15-SEP-11:00 | 624.00 | 65809.56 | 05-SEP-19:20 |
October | 35581.36 | 884502.53 | 11-OCT-15:10 | 2065.18 | 114184.21 | 24-OCT-08:70 |
November | 4529.73 | 317189.22 | 16-NOV-13:10 | 3791.97 | 121816.02 | 24-NOV-07:03 |
December | 28.15 | 15142.32 | 01-DEC-11:10 | 1054.52 | 134564.52 | 28-DEC-15:02 |
Annual Sum or Average | 235962.53 | 1594.91 | ||||
Minimum of Months | 6.66 | 12797.80 | 302.78 | 53738.38 | ||
Maximum of Months | 1051639.69 | 5877217.31 | 3791.97 | 134564.52 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.264478E+10 | 0.30 | 11617.26 | 13-JAN-06:01 | 1.35 |
February | 0.266135E+10 | 0.31 | 11617.26 | 03-FEB-06:01 | 1.35 |
March | 0.531072E+10 | 0.40 | 17198.01 | 16-MAR-04:11 | 1.71 |
April | 0.708837E+10 | 0.47 | 15002.35 | 24-APR-14:30 | 1.58 |
May | 0.732521E+10 | 0.47 | 15296.42 | 24-MAY-05:02 | 1.58 |
June | 0.118774E+11 | 0.65 | 20449.54 | 12-JUN-04:12 | 1.90 |
July | 0.148535E+11 | 0.77 | 20449.54 | 15-JUL-05:02 | 1.90 |
August | 0.149375E+11 | 0.78 | 20449.54 | 07-AUG-04:22 | 1.90 |
September | 0.817696E+10 | 0.50 | 20449.54 | 14-SEP-04:12 | 1.90 |
October | 0.584243E+10 | 0.41 | 13931.94 | 10-OCT-15:40 | 1.50 |
November | 0.457737E+10 | 0.37 | 10727.47 | 27-NOV-11:00 | 1.27 |
December | 0.344232E+10 | 0.32 | 11617.26 | 07-DEC-06:01 | 1.35 |
Annual Sum or Average | 0.887379E+11 | 0.48 | |||
Minimum of Months | 0.264478E+10 | 0.30 | 10727.47 | 1.27 | |
Maximum of Months | 0.149375E+11 | 0.78 | 20449.54 | 1.90 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.258355E+11 | 0.34 | 51997.85 | 02-JAN-04:01 | 0.87 |
February | 0.231063E+11 | 0.33 | 51997.85 | 14-FEB-06:01 | 0.87 |
March | 0.298314E+11 | 0.34 | 79566.02 | 15-MAR-14:30 | 1.11 |
April | 0.343216E+11 | 0.34 | 85050.75 | 21-APR-15:00 | 1.16 |
May | 0.534613E+11 | 0.41 | 116020.43 | 24-MAY-05:02 | 1.39 |
June | 0.789800E+11 | 0.53 | 190233.99 | 12-JUN-04:12 | 1.90 |
July | 0.900481E+11 | 0.54 | 190233.99 | 17-JUL-04:12 | 1.90 |
August | 0.875545E+11 | 0.54 | 190233.99 | 07-AUG-04:12 | 1.90 |
September | 0.570103E+11 | 0.43 | 149410.72 | 14-SEP-05:03 | 1.63 |
October | 0.330352E+11 | 0.33 | 83871.50 | 18-OCT-05:02 | 1.15 |
November | 0.235657E+11 | 0.30 | 71540.06 | 17-NOV-06:03 | 1.05 |
December | 0.240909E+11 | 0.32 | 51997.85 | 11-DEC-05:01 | 0.88 |
Annual Sum or Average | 0.560841E+12 | 0.40 | |||
Minimum of Months | 0.231063E+11 | 0.30 | 51997.85 | 0.87 | |
Maximum of Months | 0.900481E+11 | 0.54 | 190233.99 | 1.90 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.326120E+10 | 0.41 | 4901.74 | 02-JAN-04:01 | 0.80 |
February | 0.298406E+10 | 0.41 | 4901.74 | 01-FEB-05:11 | 0.80 |
March | 0.305935E+10 | 0.36 | 9110.34 | 15-MAR-14:20 | 1.13 |
April | 0.292880E+10 | 0.33 | 7981.12 | 21-APR-15:20 | 1.05 |
May | 0.464398E+10 | 0.38 | 11230.23 | 31-MAY-15:50 | 1.29 |
June | 0.785179E+10 | 0.50 | 18514.16 | 12-JUN-04:12 | 1.76 |
July | 0.943283E+10 | 0.53 | 21011.13 | 15-JUL-05:02 | 1.90 |
August | 0.866084E+10 | 0.51 | 21011.13 | 07-AUG-05:02 | 1.90 |
September | 0.494263E+10 | 0.39 | 13422.34 | 21-SEP-16:00 | 1.43 |
October | 0.273165E+10 | 0.31 | 7457.44 | 11-OCT-16:00 | 1.01 |
November | 0.229361E+10 | 0.31 | 4901.74 | 13-NOV-05:11 | 0.80 |
December | 0.306133E+10 | 0.39 | 4901.74 | 04-DEC-04:01 | 0.80 |
Annual Sum or Average | 0.558521E+11 | 0.40 | |||
Minimum of Months | 0.229361E+10 | 0.31 | 4901.74 | 0.80 | |
Maximum of Months | 0.943283E+10 | 0.53 | 21011.13 | 1.90 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.192768E+10 | 0.31 | 11215.43 | 02-JAN-07:03 | 1.92 |
February | 0.173147E+10 | 0.31 | 11215.43 | 01-FEB-07:30 | 1.94 |
March | 0.445064E+10 | 0.45 | 11215.43 | 01-MAR-07:03 | 1.94 |
April | 0.790868E+10 | 0.62 | 11215.43 | 01-APR-06:05 | 1.93 |
May | 0.102564E+11 | 0.73 | 11215.43 | 01-MAY-06:05 | 1.93 |
June | 0.100006E+11 | 0.69 | 11215.43 | 01-JUN-06:10 | 1.92 |
July | 0.786950E+10 | 0.53 | 11215.43 | 01-JUL-06:10 | 1.92 |
August | 0.103046E+11 | 0.70 | 11215.43 | 01-AUG-06:10 | 1.91 |
September | 0.103211E+11 | 0.73 | 11215.43 | 01-SEP-06:10 | 1.92 |
October | 0.116503E+11 | 0.79 | 11215.43 | 02-OCT-06:05 | 1.93 |
November | 0.101254E+11 | 0.74 | 11215.43 | 01-NOV-06:05 | 1.93 |
December | 0.273748E+10 | 0.34 | 11215.43 | 01-DEC-07:10 | 1.93 |
Annual Sum or Average | 0.892839E+11 | 0.58 | |||
Minimum of Months | 0.173147E+10 | 0.31 | 11215.43 | 1.91 | |
Maximum of Months | 0.116503E+11 | 0.79 | 11215.43 | 1.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110502E+12 | 1.38 | 41256.79 | 01-JAN-00:03 | 1.38 |
February | 0.998084E+11 | 1.38 | 41256.79 | 01-FEB-00:03 | 1.38 |
March | 0.110502E+12 | 1.38 | 41256.79 | 01-MAR-00:10 | 1.39 |
April | 0.106938E+12 | 1.38 | 41256.79 | 01-APR-00:10 | 1.38 |
May | 0.110502E+12 | 1.38 | 41256.79 | 01-MAY-00:05 | 1.38 |
June | 0.106938E+12 | 1.37 | 41256.79 | 01-JUN-00:10 | 1.38 |
July | 0.110502E+12 | 1.37 | 41256.79 | 01-JUL-00:20 | 1.38 |
August | 0.110502E+12 | 1.37 | 41256.79 | 01-AUG-00:05 | 1.37 |
September | 0.106938E+12 | 1.38 | 41256.79 | 01-SEP-00:10 | 1.38 |
October | 0.110502E+12 | 1.38 | 41256.79 | 01-OCT-00:10 | 1.38 |
November | 0.106938E+12 | 1.38 | 41256.79 | 01-NOV-00:10 | 1.38 |
December | 0.110502E+12 | 1.39 | 41256.79 | 01-DEC-00:10 | 1.39 |
Annual Sum or Average | 0.130107E+13 | 1.38 | |||
Minimum of Months | 0.998084E+11 | 1.37 | 41256.79 | 1.37 | |
Maximum of Months | 0.110502E+12 | 1.39 | 41256.79 | 1.39 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146822E+10 | 0.94 | 548.17 | 01-JAN-00:03 | 0.94 |
February | 0.132614E+10 | 0.94 | 548.17 | 01-FEB-00:03 | 0.95 |
March | 0.146822E+10 | 0.94 | 548.17 | 01-MAR-00:10 | 0.94 |
April | 0.142086E+10 | 0.94 | 548.17 | 01-APR-00:10 | 0.94 |
May | 0.146822E+10 | 0.94 | 548.17 | 01-MAY-00:05 | 0.94 |
June | 0.142086E+10 | 0.94 | 548.17 | 01-JUN-00:10 | 0.94 |
July | 0.146822E+10 | 0.94 | 548.17 | 01-JUL-00:10 | 0.94 |
August | 0.146822E+10 | 0.94 | 548.17 | 01-AUG-00:05 | 0.94 |
September | 0.142086E+10 | 0.94 | 548.17 | 01-SEP-00:10 | 0.94 |
October | 0.146822E+10 | 0.94 | 548.17 | 01-OCT-00:10 | 0.94 |
November | 0.142086E+10 | 0.94 | 548.17 | 01-NOV-00:10 | 0.94 |
December | 0.146822E+10 | 0.94 | 548.17 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.172871E+11 | 0.94 | |||
Minimum of Months | 0.132614E+10 | 0.94 | 548.17 | 0.94 | |
Maximum of Months | 0.146822E+10 | 0.94 | 548.17 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140833E+11 | 0.94 | 5258.10 | 01-JAN-00:03 | 0.94 |
February | 0.127204E+11 | 0.94 | 5258.10 | 01-FEB-00:03 | 0.95 |
March | 0.140833E+11 | 0.94 | 5258.10 | 01-MAR-00:10 | 0.94 |
April | 0.136290E+11 | 0.94 | 5258.10 | 01-APR-00:10 | 0.94 |
May | 0.140833E+11 | 0.94 | 5258.10 | 01-MAY-00:05 | 0.94 |
June | 0.136290E+11 | 0.94 | 5258.10 | 01-JUN-00:10 | 0.94 |
July | 0.140833E+11 | 0.94 | 5258.10 | 01-JUL-00:10 | 0.94 |
August | 0.140833E+11 | 0.94 | 5258.10 | 01-AUG-00:05 | 0.94 |
September | 0.136290E+11 | 0.94 | 5258.10 | 01-SEP-00:10 | 0.94 |
October | 0.140833E+11 | 0.94 | 5258.10 | 01-OCT-00:10 | 0.94 |
November | 0.136290E+11 | 0.94 | 5258.10 | 01-NOV-00:10 | 0.94 |
December | 0.140833E+11 | 0.94 | 5258.10 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.165819E+12 | 0.94 | |||
Minimum of Months | 0.127204E+11 | 0.94 | 5258.10 | 0.94 | |
Maximum of Months | 0.140833E+11 | 0.94 | 5258.10 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143260E+10 | 0.94 | 534.87 | 01-JAN-00:03 | 0.94 |
February | 0.129396E+10 | 0.94 | 534.87 | 01-FEB-00:03 | 0.95 |
March | 0.143260E+10 | 0.94 | 534.87 | 01-MAR-00:10 | 0.94 |
April | 0.138639E+10 | 0.94 | 534.87 | 01-APR-00:10 | 0.94 |
May | 0.143260E+10 | 0.94 | 534.87 | 01-MAY-00:05 | 0.94 |
June | 0.138639E+10 | 0.94 | 534.87 | 01-JUN-00:10 | 0.94 |
July | 0.143260E+10 | 0.94 | 534.87 | 01-JUL-00:10 | 0.94 |
August | 0.143260E+10 | 0.94 | 534.87 | 01-AUG-00:05 | 0.94 |
September | 0.138639E+10 | 0.94 | 534.87 | 01-SEP-00:10 | 0.94 |
October | 0.143260E+10 | 0.94 | 534.87 | 01-OCT-00:10 | 0.94 |
November | 0.138639E+10 | 0.94 | 534.87 | 01-NOV-00:10 | 0.94 |
December | 0.143260E+10 | 0.94 | 534.87 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.168677E+11 | 0.94 | |||
Minimum of Months | 0.129396E+10 | 0.94 | 534.87 | 0.94 | |
Maximum of Months | 0.143260E+10 | 0.94 | 534.87 | 0.95 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 91677398.51 | 83334755.24 | 2952.67 | 30-JAN-06:02 | 2683.97 | 2683.97 | 46.32 | 25.89 |
February | 65982745.12 | 59978315.32 | 2940.45 | 13-FEB-06:03 | 2672.87 | 2672.87 | 46.68 | 25.84 |
March | 12927332.40 | 11750945.15 | 1065.21 | 01-MAR-06:01 | 968.28 | 968.28 | 43.97 | 16.52 |
April | 1261067.88 | 1146310.70 | 956.07 | 17-APR-05:01 | 869.07 | 869.07 | 40.46 | 15.74 |
May | 120609.18 | 109633.75 | 35.32 | 11-MAY-13:20 | 32.10 | 32.10 | 34.82 | 2.69 |
June | 19936.23 | 18122.04 | 30.66 | 13-JUN-11:05 | 27.87 | 27.87 | 34.67 | 2.46 |
July | 0.00 | 0.00 | 0.00 | 14-JUL-06:19 | 0.00 | 0.00 | 35.18 | 0.00 |
August | 0.04 | 0.03 | 0.00 | 24-AUG-07:00 | 0.00 | 0.00 | 35.18 | 0.00 |
September | 11811.26 | 10736.43 | 5.41 | 30-SEP-05:03 | 4.91 | 4.91 | 33.47 | 0.69 |
October | 1086991.97 | 988075.70 | 969.42 | 30-OCT-05:01 | 881.21 | 881.21 | 39.50 | 15.85 |
November | 5345723.45 | 4859262.61 | 947.75 | 25-NOV-06:01 | 861.51 | 861.51 | 41.47 | 15.67 |
December | 55373263.88 | 50334296.87 | 2910.28 | 11-DEC-05:01 | 2645.45 | 2645.45 | 45.02 | 25.75 |
Annual Sum or Average | 0.233807E+09 | 0.212530E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.47 | 0.00 | |
Maximum of Months | 91677398.51 | 83334755.24 | 2952.67 | 2683.97 | 2683.97 | 46.68 | 25.89 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 23255.01 | 21138.80 | 20.80 | 11-JAN-07:30 | 18.91 | 18.91 | 6.70 | 3.15 |
February | 13961.29 | 12690.81 | 1.33 | 28-FEB-15:10 | 1.21 | 1.21 | 6.70 | 0.36 |
March | 35821539.74 | 32561779.62 | 1576.85 | 15-MAR-13:30 | 1433.36 | 1433.36 | 6.71 | 30.43 |
April | 10633014.22 | 9665409.93 | 218.98 | 20-APR-13:20 | 199.05 | 199.05 | 6.70 | 12.10 |
May | 89677954.73 | 81517260.85 | 1563.74 | 24-MAY-05:02 | 1421.44 | 1421.44 | 6.71 | 30.32 |
June | 0.582397E+09 | 0.529399E+09 | 9776.39 | 29-JUN-05:04 | 8886.74 | 8886.74 | 10.77 | 64.66 |
July | 0.114357E+10 | 0.103950E+10 | 9778.95 | 29-JUL-05:04 | 8889.06 | 8889.06 | 11.63 | 64.66 |
August | 0.105938E+10 | 0.962977E+09 | 10125.04 | 16-AUG-12:43 | 9203.66 | 9203.66 | 10.88 | 65.55 |
September | 0.435295E+09 | 0.395684E+09 | 10788.82 | 21-SEP-12:40 | 9807.04 | 9807.04 | 10.87 | 67.21 |
October | 50933234.81 | 46298310.45 | 1284.82 | 11-OCT-14:05 | 1167.90 | 1167.90 | 6.71 | 27.82 |
November | 3212399.67 | 2920071.30 | 144.98 | 16-NOV-13:05 | 131.79 | 131.79 | 6.70 | 9.78 |
December | 65895.63 | 59899.13 | 9.04 | 01-DEC-07:13 | 8.22 | 8.22 | 6.70 | 1.77 |
Annual Sum or Average | 0.341102E+10 | 0.310062E+10 | ||||||
Minimum of Months | 13961.29 | 12690.81 | 1.33 | 1.21 | 1.21 | 6.70 | 0.36 | |
Maximum of Months | 0.114357E+10 | 0.103950E+10 | 10788.82 | 9807.04 | 9807.04 | 11.63 | 67.21 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.155912E+09 | 0.141724E+09 | 3794.80 | 02-JAN-07:03 | 3449.48 | 3449.48 | 6.71 | 33.90 |
February | 0.171986E+09 | 0.156335E+09 | 3794.80 | 01-FEB-11:40 | 3449.48 | 3449.48 | 6.72 | 33.90 |
March | 0.162628E+10 | 0.147829E+10 | 3794.80 | 01-MAR-07:03 | 3449.48 | 3449.48 | 6.72 | 33.90 |
April | 0.210502E+10 | 0.191346E+10 | 3794.80 | 01-APR-08:65 | 3449.48 | 3449.48 | 6.73 | 33.90 |
May | 0.376210E+10 | 0.341975E+10 | 3794.80 | 01-MAY-06:50 | 3449.48 | 3449.48 | 6.74 | 33.90 |
June | 0.617307E+10 | 0.561132E+10 | 3794.80 | 01-JUN-04:12 | 3449.48 | 3449.48 | 8.16 | 33.90 |
July | 0.829420E+10 | 0.753943E+10 | 3794.80 | 01-JUL-04:12 | 3449.48 | 3449.48 | 7.85 | 33.90 |
August | 0.803989E+10 | 0.730826E+10 | 3794.80 | 01-AUG-00:20 | 3449.48 | 3449.48 | 6.82 | 33.90 |
September | 0.486654E+10 | 0.442369E+10 | 3794.80 | 01-SEP-04:12 | 3449.48 | 3449.48 | 6.84 | 33.90 |
October | 0.240877E+10 | 0.218957E+10 | 3794.80 | 01-OCT-12:55 | 3449.48 | 3449.48 | 6.77 | 33.90 |
November | 0.157115E+10 | 0.142818E+10 | 3794.80 | 01-NOV-07:10 | 3449.48 | 3449.48 | 6.95 | 33.90 |
December | 0.305216E+09 | 0.277441E+09 | 3794.80 | 01-DEC-07:12 | 3449.48 | 3449.48 | 6.82 | 33.90 |
Annual Sum or Average | 0.394801E+11 | 0.358875E+11 | ||||||
Minimum of Months | 0.155912E+09 | 0.141724E+09 | 3794.80 | 3449.48 | 3449.48 | 6.71 | 33.90 | |
Maximum of Months | 0.829420E+10 | 0.753943E+10 | 3794.80 | 3449.48 | 3449.48 | 8.16 | 33.90 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
May | 18215062.49 | 16557491.80 | 3794.80 | 10-MAY-14:30 | 3449.48 | 3449.48 | 15.21 | 16.95 |
June | 0.839031E+09 | 0.762679E+09 | 3794.80 | 01-JUN-14:40 | 3449.48 | 3449.48 | 15.28 | 16.95 |
July | 0.186188E+10 | 0.169245E+10 | 3794.80 | 03-JUL-12:05 | 3449.48 | 3449.48 | 11.02 | 33.90 |
August | 0.131137E+10 | 0.119203E+10 | 3794.80 | 01-AUG-14:30 | 3449.48 | 3449.48 | 16.57 | 16.95 |
September | 0.375686E+09 | 0.341498E+09 | 3794.80 | 08-SEP-13:00 | 3449.48 | 3449.48 | 15.63 | 16.95 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.85 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 7.33 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.440618E+10 | 0.400522E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.186188E+10 | 0.169245E+10 | 3794.80 | 3449.48 | 3449.48 | 16.57 | 33.90 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.100491E+11 | 0.913463E+10 | 3751.90 | 01-JAN-00:03 | 3410.48 | 3410.48 | 18.49 | 15.83 |
February | 0.907660E+10 | 0.825063E+10 | 3751.90 | 01-FEB-00:03 | 3410.48 | 3410.48 | 18.84 | 15.83 |
March | 0.100491E+11 | 0.913463E+10 | 3751.90 | 01-MAR-00:10 | 3410.48 | 3410.48 | 19.61 | 15.83 |
April | 0.972493E+10 | 0.883996E+10 | 3751.90 | 01-APR-00:10 | 3410.48 | 3410.48 | 20.29 | 15.83 |
May | 0.100491E+11 | 0.913463E+10 | 3751.90 | 01-MAY-00:05 | 3410.48 | 3410.48 | 18.89 | 15.83 |
June | 0.972493E+10 | 0.883996E+10 | 3751.90 | 01-JUN-00:10 | 3410.48 | 3410.48 | 19.38 | 15.83 |
July | 0.100491E+11 | 0.913463E+10 | 3751.90 | 01-JUL-00:10 | 3410.48 | 3410.48 | 20.02 | 15.83 |
August | 0.100491E+11 | 0.913463E+10 | 3751.90 | 01-AUG-00:05 | 3410.48 | 3410.48 | 30.79 | 15.83 |
September | 0.972493E+10 | 0.883996E+10 | 3751.90 | 01-SEP-00:10 | 3410.48 | 3410.48 | 18.88 | 15.83 |
October | 0.100491E+11 | 0.913463E+10 | 3751.90 | 01-OCT-00:10 | 3410.48 | 3410.48 | 19.26 | 15.83 |
November | 0.972493E+10 | 0.883996E+10 | 3751.90 | 01-NOV-00:10 | 3410.48 | 3410.48 | 19.84 | 15.83 |
December | 0.100491E+11 | 0.913463E+10 | 3751.90 | 01-DEC-00:10 | 3410.48 | 3410.48 | 20.13 | 15.83 |
Annual Sum or Average | 0.118320E+12 | 0.107553E+12 | ||||||
Minimum of Months | 0.907660E+10 | 0.825063E+10 | 3751.90 | 3410.48 | 3410.48 | 18.49 | 15.83 | |
Maximum of Months | 0.100491E+11 | 0.913463E+10 | 3751.90 | 3410.48 | 3410.48 | 30.79 | 15.83 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 56.88 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.79 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 56.94 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.88 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 57.25 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.16 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.32 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.42 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.35 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.09 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 57.22 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.98 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.79 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.42 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.598720E+09 | 0.544236E+09 | 14574.48 | 11-JAN-15:10 | 13248.21 | 13248.21 | 21.15 | 59.67 |
February | 0.660446E+09 | 0.600345E+09 | 14574.67 | 22-FEB-16:50 | 13248.37 | 13248.37 | 21.17 | 59.67 |
March | 0.624840E+10 | 0.567980E+10 | 14658.51 | 14-MAR-13:20 | 13324.58 | 13324.58 | 28.55 | 59.67 |
April | 0.808576E+10 | 0.734995E+10 | 14599.30 | 07-APR-13:20 | 13270.76 | 13270.76 | 23.52 | 59.67 |
May | 0.144927E+11 | 0.131738E+11 | 29250.84 | 10-MAY-14:30 | 26589.01 | 26589.01 | 25.85 | 119.35 |
June | 0.266741E+11 | 0.242468E+11 | 29339.10 | 27-JUN-07:20 | 26669.24 | 26669.24 | 30.68 | 119.35 |
July | 0.387520E+11 | 0.352255E+11 | 29339.10 | 05-JUL-09:50 | 26669.24 | 26669.24 | 29.75 | 119.35 |
August | 0.357050E+11 | 0.324558E+11 | 29339.10 | 07-AUG-14:30 | 26669.24 | 26669.24 | 29.63 | 119.35 |
September | 0.200357E+11 | 0.182125E+11 | 29339.10 | 15-SEP-11:00 | 26669.24 | 26669.24 | 29.53 | 119.35 |
October | 0.925465E+10 | 0.841248E+10 | 14611.17 | 11-OCT-15:10 | 13281.55 | 13281.55 | 24.65 | 59.67 |
November | 0.603409E+10 | 0.548499E+10 | 14587.28 | 16-NOV-13:10 | 13259.84 | 13259.84 | 22.37 | 59.67 |
December | 0.116988E+10 | 0.106342E+10 | 14574.58 | 01-DEC-11:10 | 13248.30 | 13248.30 | 21.16 | 59.67 |
Annual Sum or Average | 0.167711E+12 | 0.152450E+12 | ||||||
Minimum of Months | 0.598720E+09 | 0.544236E+09 | 14574.48 | 13248.21 | 13248.21 | 21.15 | 59.67 | |
Maximum of Months | 0.387520E+11 | 0.352255E+11 | 29339.10 | 26669.24 | 26669.24 | 30.68 | 119.35 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 39.07 | 39.07 | 108576.07 | 2065285.24 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 41.42 | 41.42 | 92939.76 | 1715396.62 | 18-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 33.65 | 33.65 | 26048.35 | 1595914.08 | 28-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 34.77 | 34.77 | 4332.70 | 1321222.18 | 05-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 32.88 | 32.88 | 492.21 | 283435.71 | 11-MAY-13:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 34.71 | 34.71 | 69.97 | 260352.85 | 13-JUN-11:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 35.18 | 35.18 | 0.00 | 0.19 | 14-JUL-06:19 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 35.18 | 35.18 | 0.00 | 0.70 | 24-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 35.18 | 35.18 | 73.03 | 76504.00 | 30-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 32.71 | 32.71 | 3699.31 | 1375465.11 | 17-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 30.91 | 30.91 | 15673.03 | 1798803.60 | 18-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 28.19 | 28.19 | 82949.60 | 1787167.44 | 02-DEC-05:11 |
Annual Sum or Average | 0.00 | 27620.57 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.19 | 28.19 | 0.00 | 0.19 | ||
Maximum of Months | 0.00 | 0.00 | 41.42 | 41.42 | 108576.07 | 2065285.24 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 57.59 | 5418.31 | 11-JAN-16:50 | 6.74 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 87.28 | 9044.02 | 28-FEB-15:20 | 6.76 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 21634.75 | 1129278.35 | 15-MAR-13:50 | 14.66 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18456.63 | 548946.55 | 07-APR-13:20 | 10.56 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 76189.94 | 1243728.33 | 10-MAY-15:50 | 11.08 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 314858.60 | 1973009.62 | 27-JUN-07:40 | 13.65 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 522541.03 | 2462157.59 | 20-JUL-05:03 | 15.38 | 6.99 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 438668.66 | 2660431.75 | 14-AUG-05:03 | 16.08 | 7.69 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 200750.99 | 1845493.73 | 15-SEP-11:00 | 13.20 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 33993.07 | 781884.39 | 11-OCT-15:10 | 12.21 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6073.82 | 279461.44 | 16-NOV-13:10 | 8.67 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 241.26 | 31593.85 | 01-DEC-07:13 | 6.92 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 137259.62 | 0.00 | ||||||
Minimum of Months | 57.59 | 5418.31 | 6.74 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 522541.03 | 2660431.75 | 16.08 | 7.69 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4.83 | 1971.17 | 11-JAN-16:50 | 8.34 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 22.65 | 5868.92 | 28-FEB-15:10 | 10.57 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 21113.27 | 1128770.97 | 15-MAR-13:50 | 15.77 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 17727.74 | 552572.79 | 07-APR-13:20 | 19.83 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74913.17 | 1214878.67 | 10-MAY-15:00 | 17.82 | 9.35 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 313266.18 | 2924644.81 | 27-JUN-05:03 | 17.51 | 11.83 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 520794.51 | 3369930.42 | 17-JUL-05:03 | 19.16 | 13.48 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 439124.70 | 3482200.14 | 14-AUG-04:11 | 19.58 | 12.80 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 201153.75 | 2877993.39 | 16-SEP-05:02 | 17.34 | 11.74 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 33203.55 | 779958.32 | 11-OCT-15:10 | 13.80 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5520.31 | 283992.07 | 16-NOV-13:05 | 13.63 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 137.68 | 40232.73 | 01-DEC-07:12 | 12.17 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 136708.81 | 0.00 | ||||||
Minimum of Months | 4.83 | 1971.17 | 8.34 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 520794.51 | 3482200.14 | 19.83 | 13.48 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 10501.38 | 27699.98 | 15-JAN-16:40 | 18.84 | 18.33 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 38967.96 | 68995.49 | 28-FEB-09:58 | 19.59 | 18.33 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 98854.26 | 1054498.50 | 15-MAR-14:00 | 37.23 | 29.02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 123492.41 | 695836.59 | 08-APR-13:05 | 30.87 | 23.58 | 0.00 | 0.00 | 01-APR-00:10 |
May | 55509.40 | 697544.81 | 10-MAY-15:00 | 30.91 | 27.35 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 300349.54 | 1296880.00 | 27-JUN-14:10 | 41.48 | 30.77 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 797327.99 | 1646986.23 | 21-JUL-02:50 | 47.56 | 33.86 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 840927.72 | 1725920.04 | 13-AUG-15:00 | 48.92 | 35.04 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 104860.60 | 813700.27 | 16-SEP-14:30 | 32.97 | 28.52 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 59675.16 | 448322.64 | 11-OCT-15:00 | 26.45 | 23.30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80599.10 | 343035.82 | 05-NOV-14:00 | 24.55 | 20.73 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 94570.45 | 180046.63 | 01-DEC-11:00 | 21.61 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 219310.99 | 0.00 | ||||||
Minimum of Months | 10501.38 | 27699.98 | 18.84 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 840927.72 | 1725920.04 | 48.92 | 35.04 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.98 | 57.98 | 15565.50 | 55761.25 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 57.39 | 57.39 | 15883.48 | 55957.89 | 15-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.39 | 57.39 | 16653.06 | 55779.68 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.46 | 57.46 | 14992.81 | 54071.96 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.08 | 58.08 | 14631.73 | 51559.60 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.74 | 57.74 | 14076.09 | 48363.91 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.87 | 57.87 | 12326.76 | 45521.93 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.95 | 57.95 | 13253.11 | 44047.86 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.95 | 57.95 | 12640.60 | 45462.28 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.88 | 57.88 | 13239.12 | 48280.09 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.75 | 57.75 | 14277.43 | 51374.95 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.60 | 57.60 | 14571.55 | 54008.71 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 14333.73 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.39 | 57.39 | 12326.76 | 44047.86 | ||
Maximum of Months | 0.00 | 0.00 | 58.08 | 58.08 | 16653.06 | 55957.89 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 11.15 | 12797.80 | 11-JAN-15:10 | 21.15 | 20.67 | 556.75 | 133735.60 | 30-JAN-01:40 |
February | 6.66 | 17142.60 | 22-FEB-16:50 | 21.17 | 20.53 | 656.58 | 124434.91 | 09-FEB-07:03 |
March | 26342.89 | 1857775.20 | 14-MAR-13:20 | 28.55 | 22.31 | 3540.95 | 133444.90 | 23-MAR-15:40 |
April | 16600.81 | 602821.05 | 07-APR-13:20 | 23.52 | 21.10 | 3450.44 | 126977.09 | 17-APR-12:40 |
May | 84061.90 | 2371481.51 | 10-MAY-14:30 | 25.85 | 22.61 | 1631.99 | 103016.94 | 08-MAY-08:30 |
June | 521730.71 | 5146367.75 | 27-JUN-07:40 | 31.42 | 26.88 | 539.84 | 63742.04 | 03-JUN-10:20 |
July | 1051639.69 | 5877217.31 | 05-JUL-16:00 | 32.88 | 27.33 | 302.78 | 53738.38 | 07-JUL-07:00 |
August | 761445.51 | 5578435.05 | 14-AUG-10:05 | 32.28 | 27.34 | 898.47 | 62574.12 | 12-AUG-22:10 |
September | 303595.68 | 4207487.78 | 15-SEP-11:00 | 29.53 | 25.29 | 624.00 | 65809.56 | 05-SEP-19:20 |
October | 35581.36 | 884502.53 | 11-OCT-15:10 | 24.65 | 21.10 | 2065.18 | 114184.21 | 24-OCT-08:70 |
November | 4529.73 | 317189.22 | 16-NOV-13:10 | 22.37 | 21.10 | 3791.97 | 121816.02 | 24-NOV-07:03 |
December | 28.15 | 15142.32 | 01-DEC-11:10 | 21.16 | 20.77 | 1054.52 | 134564.52 | 28-DEC-15:02 |
Annual Sum or Average | 235962.53 | 1594.91 | ||||||
Minimum of Months | 6.66 | 12797.80 | 21.15 | 20.53 | 302.78 | 53738.38 | ||
Maximum of Months | 1051639.69 | 5877217.31 | 32.88 | 27.34 | 3791.97 | 134564.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.337078E+10 | 0.00 | 3459758.71 | 0.264478E+10 | 0.00 | 0.00 |
February | 0.248593E+10 | 0.00 | 24985500.29 | 0.266135E+10 | 0.00 | 0.00 |
March | 0.543556E+09 | 0.00 | 0.770629E+10 | 0.531072E+10 | 0.00 | 0.00 |
April | 96671597.76 | 0.00 | 0.446168E+10 | 0.708837E+10 | 0.00 | 0.00 |
May | 8651768.24 | 0.00 | 0.174544E+11 | 0.732521E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.808469E+11 | 0.118774E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.149173E+12 | 0.148535E+11 | 0.00 | 0.00 |
August | 136.46 | 0.00 | 0.124921E+12 | 0.149375E+11 | 0.00 | 0.00 |
September | 2025505.29 | 0.00 | 0.479276E+11 | 0.817696E+10 | 0.00 | 0.00 |
October | 70241635.64 | 0.00 | 0.948484E+10 | 0.584243E+10 | 0.00 | 0.00 |
November | 0.178100E+09 | 0.00 | 0.423613E+10 | 0.457737E+10 | 0.00 | 0.00 |
December | 0.159592E+10 | 0.00 | 0.122076E+09 | 0.344232E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.835188E+10 | 0.00 | 0.446362E+12 | 0.887379E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 3459758.71 | 0.264478E+10 | 0.00 | 0.00 |
Maximum of Months | 0.337078E+10 | 0.00 | 0.149173E+12 | 0.149375E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.222456E+12 | 0.00 | 5686099.32 | 0.258355E+11 | 0.00 | 0.00 |
February | 0.167902E+12 | 0.00 | 38586832.67 | 0.231063E+11 | 0.00 | 0.00 |
March | 0.485590E+11 | 0.00 | 0.385120E+11 | 0.298314E+11 | 0.00 | 0.00 |
April | 0.726579E+10 | 0.00 | 0.381293E+11 | 0.343216E+11 | 0.00 | 0.00 |
May | 0.111823E+10 | 0.00 | 0.155614E+12 | 0.534613E+11 | 0.00 | 0.00 |
June | 0.170617E+09 | 0.00 | 0.610348E+12 | 0.789800E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.102918E+13 | 0.900481E+11 | 0.00 | 0.00 |
August | 762.00 | 0.00 | 0.856364E+12 | 0.875545E+11 | 0.00 | 0.00 |
September | 0.109176E+09 | 0.00 | 0.388309E+12 | 0.570103E+11 | 0.00 | 0.00 |
October | 0.622358E+10 | 0.00 | 0.703791E+11 | 0.330352E+11 | 0.00 | 0.00 |
November | 0.281670E+11 | 0.00 | 0.877950E+10 | 0.235657E+11 | 0.00 | 0.00 |
December | 0.169985E+12 | 0.00 | 31698071.39 | 0.240909E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.651956E+12 | 0.00 | 0.319569E+13 | 0.560841E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 5686099.32 | 0.231063E+11 | 0.00 | 0.00 |
Maximum of Months | 0.222456E+12 | 0.00 | 0.102918E+13 | 0.900481E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.496863E+11 | 0.00 | 861254.08 | 0.326120E+10 | 0.00 | 0.00 |
February | 0.411504E+11 | 0.00 | 3543274.83 | 0.298406E+10 | 0.00 | 0.00 |
March | 0.161076E+11 | 0.00 | 0.375378E+10 | 0.305935E+10 | 0.00 | 0.00 |
April | 0.368955E+10 | 0.00 | 0.140052E+10 | 0.292880E+10 | 0.00 | 0.00 |
May | 0.168314E+09 | 0.00 | 0.147617E+11 | 0.464398E+10 | 0.00 | 0.00 |
June | 4965490.66 | 0.00 | 0.665018E+11 | 0.785179E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.114689E+12 | 0.943283E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.932509E+11 | 0.866084E+10 | 0.00 | 0.00 |
September | 0.110208E+09 | 0.00 | 0.375945E+11 | 0.494263E+10 | 0.00 | 0.00 |
October | 0.364137E+10 | 0.00 | 0.418650E+10 | 0.273165E+10 | 0.00 | 0.00 |
November | 0.121180E+11 | 0.00 | 0.487509E+09 | 0.229361E+10 | 0.00 | 0.00 |
December | 0.433877E+11 | 0.00 | 3624892.55 | 0.306133E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.170064E+12 | 0.00 | 0.336634E+12 | 0.558521E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 861254.08 | 0.229361E+10 | 0.00 | 0.00 |
Maximum of Months | 0.496863E+11 | 0.00 | 0.114689E+12 | 0.943283E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.156980E+11 | 0.00 | 34993610.45 | 0.192768E+10 | 0.00 | 0.00 |
February | 0.137322E+11 | 0.00 | 33976704.27 | 0.173147E+10 | 0.00 | 0.00 |
March | 0.463949E+10 | 0.00 | 0.355343E+10 | 0.445064E+10 | 0.00 | 0.00 |
April | 0.217298E+09 | 0.00 | 0.207960E+10 | 0.790868E+10 | 0.00 | 0.00 |
May | 1207839.21 | 0.00 | 0.111671E+11 | 0.102564E+11 | 0.00 | 0.00 |
June | 423.29 | 0.00 | 0.282952E+11 | 0.100006E+11 | 0.00 | 0.00 |
July | 32.79 | 0.00 | 0.514019E+11 | 0.786950E+10 | 0.00 | 0.00 |
August | 212.26 | 0.00 | 0.549081E+11 | 0.103046E+11 | 0.00 | 0.00 |
September | 247.33 | 0.00 | 0.308164E+11 | 0.103211E+11 | 0.00 | 0.00 |
October | 9370407.36 | 0.00 | 0.506104E+10 | 0.116503E+11 | 0.00 | 0.00 |
November | 0.250877E+09 | 0.00 | 0.819778E+09 | 0.101254E+11 | 0.00 | 0.00 |
December | 0.739109E+10 | 0.00 | 0.238701E+09 | 0.273748E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.419395E+11 | 0.00 | 0.188410E+12 | 0.892839E+11 | 0.00 | 0.00 |
Minimum of Months | 32.79 | 0.00 | 33976704.27 | 0.173147E+10 | 0.00 | 0.00 |
Maximum of Months | 0.156980E+11 | 0.00 | 0.549081E+11 | 0.116503E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.104132E+11 | 0.249426E+12 | 0.00 | 50.24 |
February | 0.00 | 0.00 | 0.148308E+11 | 0.306994E+12 | 0.00 | 75.37 |
March | 0.00 | 0.00 | 0.416148E+11 | 0.321109E+12 | 0.00 | 74.54 |
April | 0.00 | 0.00 | 0.477969E+11 | 0.323857E+12 | 0.00 | 76.46 |
May | 0.00 | 0.00 | 0.114579E+11 | 0.195123E+12 | 0.00 | 29.89 |
June | 0.00 | 0.00 | 0.209564E+12 | 0.190490E+12 | 0.00 | 15.04 |
July | 0.00 | 0.00 | 0.878160E+12 | 0.281046E+12 | 0.00 | 0.90 |
August | 0.00 | 0.00 | 0.101962E+13 | 0.309112E+12 | 0.00 | 1.63 |
September | 0.00 | 0.00 | 0.214723E+11 | 0.123952E+12 | 0.00 | 3.89 |
October | 0.00 | 0.00 | 0.130324E+11 | 0.219712E+12 | 0.00 | 38.95 |
November | 0.00 | 0.00 | 0.237377E+11 | 0.327363E+12 | 0.00 | 79.58 |
December | 0.00 | 0.00 | 0.213730E+11 | 0.378073E+12 | 0.00 | 97.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.231307E+13 | 0.322626E+13 | 0.00 | 543.68 |
Minimum of Months | 0.00 | 0.00 | 0.104132E+11 | 0.123952E+12 | 0.00 | 0.90 |
Maximum of Months | 0.00 | 0.00 | 0.101962E+13 | 0.378073E+12 | 0.00 | 97.18 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.369760E+10 | 0.216934E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.933076E+10 | 0.298617E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.177341E+11 | 0.443021E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.233733E+11 | 0.510077E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.662169E+10 | 0.263037E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.130753E+11 | 0.372256E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202798E+11 | 0.523669E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.259786E+11 | 0.610208E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.677384E+10 | 0.260980E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.122235E+11 | 0.349984E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.172519E+11 | 0.423314E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.230596E+11 | 0.522526E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.179400E+12 | 0.479462E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.369760E+10 | 0.216934E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.259786E+11 | 0.610208E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.482856E+10 | 0.151365E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.578953E+11 | 0.233334E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.149193E+12 | 0.393136E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.211541E+12 | 0.471656E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.574620E+11 | 0.242430E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.121685E+12 | 0.351226E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.191855E+12 | 0.497974E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.246249E+12 | 0.580851E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.589047E+11 | 0.240496E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.102732E+12 | 0.313407E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.142842E+12 | 0.372465E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.183183E+12 | 0.445569E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152837E+13 | 0.429391E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.482856E+10 | 0.151365E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.246249E+12 | 0.580851E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 70086835.76 | 0.144828E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.390736E+10 | 0.202448E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.130697E+11 | 0.366731E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.199397E+11 | 0.457220E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.525310E+10 | 0.236776E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.120988E+11 | 0.353018E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.192717E+11 | 0.502753E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.246115E+11 | 0.584305E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.545481E+10 | 0.235918E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.867233E+10 | 0.290543E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.121634E+11 | 0.342628E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.161417E+11 | 0.415431E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.140654E+12 | 0.413260E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 70086835.76 | 0.144828E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.246115E+11 | 0.584305E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.264478E+10 | 3459758.71 | 0.337078E+10 | 0.417996E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.266135E+10 | 24985500.29 | 0.248593E+10 | 0.371689E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.531072E+10 | 0.770629E+10 | 0.543556E+09 | 0.154787E+11 | 876258.32 | 0.00 | 0.00 | 0.00 |
April | 0.708837E+10 | 0.446168E+10 | 96671597.76 | 0.295585E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.732521E+10 | 0.174544E+11 | 8651768.24 | 0.179612E+09 | 103530.64 | 0.00 | 0.00 | 0.00 |
June | 0.118774E+11 | 0.808469E+11 | 0.00 | 0.148251E+09 | 0.189223E+10 | 0.00 | 0.00 | 0.00 |
July | 0.148535E+11 | 0.149173E+12 | 0.00 | 0.146109E+09 | 0.551849E+10 | 0.00 | 0.00 | 0.00 |
August | 0.149375E+11 | 0.124921E+12 | 136.46 | 0.599114E+09 | 0.218187E+10 | 0.00 | 0.00 | 0.00 |
September | 0.817696E+10 | 0.479276E+11 | 2025505.29 | 72066888.76 | 0.278231E+09 | 0.00 | 0.00 | 0.00 |
October | 0.584243E+10 | 0.948484E+10 | 70241635.64 | 0.208100E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.457737E+10 | 0.423613E+10 | 0.178100E+09 | 0.659737E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344232E+10 | 0.122076E+09 | 0.159592E+10 | 0.308627E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.887379E+11 | 0.446362E+12 | 0.835188E+10 | 0.138089E+12 | 0.987180E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.264478E+10 | 3459758.71 | 0.00 | 72066888.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149375E+11 | 0.149173E+12 | 0.337078E+10 | 0.417996E+11 | 0.551849E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.258355E+11 | 5686099.32 | 0.222456E+12 | 0.438288E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231063E+11 | 38586832.67 | 0.167902E+12 | 0.400877E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.298314E+11 | 0.385120E+11 | 0.485590E+11 | 0.242546E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.343216E+11 | 0.381293E+11 | 0.726579E+10 | 0.728353E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.534613E+11 | 0.155614E+12 | 0.111823E+10 | 0.440119E+10 | 2614748.65 | 0.00 | 0.00 | 0.00 |
June | 0.789800E+11 | 0.610348E+12 | 0.170617E+09 | 0.197719E+10 | 0.189129E+11 | 0.00 | 0.00 | 0.00 |
July | 0.900481E+11 | 0.102918E+13 | 0.00 | 0.209124E+10 | 0.545101E+11 | 0.00 | 0.00 | 0.00 |
August | 0.875545E+11 | 0.856364E+12 | 762.00 | 0.690385E+10 | 0.212715E+11 | 0.00 | 0.00 | 0.00 |
September | 0.570103E+11 | 0.388309E+12 | 0.109176E+09 | 0.132352E+10 | 0.298455E+10 | 0.00 | 0.00 | 0.00 |
October | 0.330352E+11 | 0.703791E+11 | 0.622358E+10 | 0.437001E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235657E+11 | 0.877950E+10 | 0.281670E+11 | 0.139163E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240909E+11 | 31698071.39 | 0.169985E+12 | 0.377503E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.560841E+12 | 0.319569E+13 | 0.651956E+12 | 0.173161E+13 | 0.976816E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.231063E+11 | 5686099.32 | 0.00 | 0.132352E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.900481E+11 | 0.102918E+13 | 0.222456E+12 | 0.438288E+12 | 0.545101E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.326120E+10 | 861254.08 | 0.496863E+11 | 0.446422E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298406E+10 | 3543274.83 | 0.411504E+11 | 0.406278E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305935E+10 | 0.375378E+10 | 0.161076E+11 | 0.262679E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.292880E+10 | 0.140052E+10 | 0.368955E+10 | 0.939680E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.464398E+10 | 0.147617E+11 | 0.168314E+09 | 0.776723E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.785179E+10 | 0.665018E+11 | 4965490.66 | 0.235676E+09 | 0.150345E+10 | 0.00 | 0.00 | 0.00 |
July | 0.943283E+10 | 0.114689E+12 | 0.00 | 0.161781E+09 | 0.440596E+10 | 0.00 | 0.00 | 0.00 |
August | 0.866084E+10 | 0.932509E+11 | 0.00 | 0.697403E+09 | 0.155353E+10 | 0.00 | 0.00 | 0.00 |
September | 0.494263E+10 | 0.375945E+11 | 0.110208E+09 | 0.253981E+09 | 0.176013E+09 | 0.00 | 0.00 | 0.00 |
October | 0.273165E+10 | 0.418650E+10 | 0.364137E+10 | 0.640203E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229361E+10 | 0.487509E+09 | 0.121180E+11 | 0.173138E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306133E+10 | 3624892.55 | 0.433877E+11 | 0.395613E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.558521E+11 | 0.336634E+12 | 0.170064E+12 | 0.186337E+12 | 0.763895E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.229361E+10 | 861254.08 | 0.00 | 0.161781E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.943283E+10 | 0.114689E+12 | 0.496863E+11 | 0.446422E+11 | 0.440596E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.192768E+10 | 36699789.90 | 0.156980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173147E+10 | 33976704.27 | 0.137322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.445064E+10 | 0.355343E+10 | 0.463949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.790868E+10 | 0.207960E+10 | 0.217298E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102564E+11 | 0.111671E+11 | 1207839.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100006E+11 | 0.282952E+11 | 423.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.786950E+10 | 0.514019E+11 | 32.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103046E+11 | 0.549081E+11 | 212.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103211E+11 | 0.308164E+11 | 247.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116503E+11 | 0.506104E+10 | 9370407.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101254E+11 | 0.819778E+09 | 0.250877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273748E+10 | 0.238701E+09 | 0.739109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.892839E+11 | 0.188412E+12 | 0.419395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.173147E+10 | 33976704.27 | 32.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116503E+11 | 0.549081E+11 | 0.156980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.110502E+12 | 0.654828E+10 | 0.00 | 0.00 | 0.00 | 0.134453E+12 | 0.00 | 0.00 |
February | 0.998084E+11 | 0.102627E+11 | 0.00 | 0.00 | 0.00 | 0.201709E+12 | 0.00 | 0.00 |
March | 0.110502E+12 | 0.313903E+11 | 0.00 | 0.00 | 0.00 | 0.199484E+12 | 0.00 | 0.00 |
April | 0.106938E+12 | 0.364191E+11 | 0.00 | 0.00 | 0.00 | 0.204621E+12 | 0.00 | 0.00 |
May | 0.110502E+12 | 0.719024E+10 | 0.00 | 0.00 | 0.00 | 0.799936E+11 | 0.00 | 0.00 |
June | 0.106938E+12 | 0.166435E+12 | 0.00 | 0.00 | 0.00 | 0.402421E+11 | 0.00 | 0.00 |
July | 0.110502E+12 | 0.710033E+12 | 0.00 | 0.00 | 0.00 | 0.240655E+10 | 0.00 | 0.00 |
August | 0.110502E+12 | 0.825398E+12 | 0.00 | 0.00 | 0.00 | 0.437009E+10 | 0.00 | 0.00 |
September | 0.106938E+12 | 0.149250E+11 | 0.00 | 0.00 | 0.00 | 0.104199E+11 | 0.00 | 0.00 |
October | 0.110502E+12 | 0.852388E+10 | 0.00 | 0.00 | 0.00 | 0.104232E+12 | 0.00 | 0.00 |
November | 0.106938E+12 | 0.172473E+11 | 0.00 | 0.00 | 0.00 | 0.212976E+12 | 0.00 | 0.00 |
December | 0.110502E+12 | 0.150327E+11 | 0.00 | 0.00 | 0.00 | 0.260060E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.130107E+13 | 0.184940E+13 | 0.00 | 0.00 | 0.00 | 0.145497E+13 | 0.00 | 0.00 |
Minimum of Months | 0.998084E+11 | 0.654828E+10 | 0.00 | 0.00 | 0.00 | 0.240655E+10 | 0.00 | 0.00 |
Maximum of Months | 0.110502E+12 | 0.825398E+12 | 0.00 | 0.00 | 0.00 | 0.260060E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146822E+10 | 0.299648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132614E+10 | 0.767073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146822E+10 | 0.147721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142086E+10 | 0.196934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146822E+10 | 0.545954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142086E+10 | 0.107736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146822E+10 | 0.165113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146822E+10 | 0.213447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142086E+10 | 0.558490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146822E+10 | 0.101919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142086E+10 | 0.144396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146822E+10 | 0.193026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172871E+11 | 0.148741E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132614E+10 | 0.299648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146822E+10 | 0.213447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140833E+11 | 0.377535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127204E+11 | 0.472823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140833E+11 | 0.123963E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136290E+11 | 0.178005E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140833E+11 | 0.473024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136290E+11 | 0.100191E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140833E+11 | 0.156141E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140833E+11 | 0.202247E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136290E+11 | 0.484841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140833E+11 | 0.854745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136290E+11 | 0.119225E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140833E+11 | 0.152709E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165819E+12 | 0.126480E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127204E+11 | 0.377535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140833E+11 | 0.202247E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143260E+10 | 54410184.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129396E+10 | 0.317684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143260E+10 | 0.108350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138639E+10 | 0.167539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143260E+10 | 0.431794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138639E+10 | 0.995500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143260E+10 | 0.156768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143260E+10 | 0.202011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138639E+10 | 0.448202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143260E+10 | 0.719950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138639E+10 | 0.101235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143260E+10 | 0.134200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168677E+11 | 0.116196E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129396E+10 | 54410184.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143260E+10 | 0.202011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.264478E+10 | 0.337078E+10 | 3459758.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.266135E+10 | 0.248593E+10 | 24985500.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.531072E+10 | 0.543556E+09 | 0.770629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.708837E+10 | 96671597.76 | 0.446168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.732521E+10 | 8651768.24 | 0.174544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118774E+11 | 0.00 | 0.808469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148535E+11 | 0.00 | 0.149173E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149375E+11 | 136.46 | 0.124921E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.817696E+10 | 2025505.29 | 0.479276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.584243E+10 | 70241635.64 | 0.948484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.457737E+10 | 0.178100E+09 | 0.423613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344232E+10 | 0.159592E+10 | 0.122076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.887379E+11 | 0.835188E+10 | 0.446362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.264478E+10 | 0.00 | 3459758.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149375E+11 | 0.337078E+10 | 0.149173E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.258355E+11 | 0.222456E+12 | 5686099.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231063E+11 | 0.167902E+12 | 38586832.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.298314E+11 | 0.485590E+11 | 0.385120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.343216E+11 | 0.726579E+10 | 0.381293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.534613E+11 | 0.111823E+10 | 0.155614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.789800E+11 | 0.170617E+09 | 0.610348E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.900481E+11 | 0.00 | 0.102918E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.875545E+11 | 762.00 | 0.856364E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.570103E+11 | 0.109176E+09 | 0.388309E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330352E+11 | 0.622358E+10 | 0.703791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235657E+11 | 0.281670E+11 | 0.877950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240909E+11 | 0.169985E+12 | 31698071.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.560841E+12 | 0.651956E+12 | 0.319569E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.231063E+11 | 0.00 | 5686099.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.900481E+11 | 0.222456E+12 | 0.102918E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.326120E+10 | 0.496863E+11 | 861254.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298406E+10 | 0.411504E+11 | 3543274.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305935E+10 | 0.161076E+11 | 0.375378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.292880E+10 | 0.368955E+10 | 0.140052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.464398E+10 | 0.168314E+09 | 0.147617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.785179E+10 | 4965490.66 | 0.665018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.943283E+10 | 0.00 | 0.114689E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.866084E+10 | 0.00 | 0.932509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.494263E+10 | 0.110208E+09 | 0.375945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.273165E+10 | 0.364137E+10 | 0.418650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229361E+10 | 0.121180E+11 | 0.487509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306133E+10 | 0.433877E+11 | 3624892.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.558521E+11 | 0.170064E+12 | 0.336634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.229361E+10 | 0.00 | 861254.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.943283E+10 | 0.496863E+11 | 0.114689E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.192768E+10 | 0.156980E+11 | 34993610.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173147E+10 | 0.137322E+11 | 33976704.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.445064E+10 | 0.463949E+10 | 0.355343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.790868E+10 | 0.217298E+09 | 0.207960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102564E+11 | 1207839.21 | 0.111671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100006E+11 | 423.29 | 0.282952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.786950E+10 | 32.79 | 0.514019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103046E+11 | 212.26 | 0.549081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103211E+11 | 247.33 | 0.308164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116503E+11 | 9370407.36 | 0.506104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101254E+11 | 0.250877E+09 | 0.819778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273748E+10 | 0.739109E+10 | 0.238701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.892839E+11 | 0.419395E+11 | 0.188410E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.173147E+10 | 32.79 | 33976704.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116503E+11 | 0.156980E+11 | 0.549081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.110502E+12 | 0.00 | 0.104132E+11 | 0.00 | 0.386492E+10 | 0.00 | 0.00 | 0.00 | 0.135059E+12 | 0.00 | 0.00 | 0.00 |
February | 0.998084E+11 | 0.00 | 0.148308E+11 | 0.00 | 0.456812E+10 | 0.00 | 0.00 | 0.00 | 0.202617E+12 | 0.00 | 0.00 | 0.00 |
March | 0.110502E+12 | 0.00 | 0.416148E+11 | 0.00 | 0.102245E+11 | 0.00 | 0.00 | 0.00 | 0.200382E+12 | 0.00 | 0.00 | 0.00 |
April | 0.106938E+12 | 0.00 | 0.477969E+11 | 0.00 | 0.113777E+11 | 0.00 | 0.00 | 0.00 | 0.205542E+12 | 0.00 | 0.00 | 0.00 |
May | 0.110502E+12 | 0.00 | 0.114579E+11 | 0.00 | 0.426762E+10 | 0.00 | 0.00 | 0.00 | 0.803537E+11 | 0.00 | 0.00 | 0.00 |
June | 0.106938E+12 | 0.00 | 0.209564E+12 | 0.00 | 0.431295E+11 | 0.00 | 0.00 | 0.00 | 0.404233E+11 | 0.00 | 0.00 | 0.00 |
July | 0.110502E+12 | 0.00 | 0.878160E+12 | 0.00 | 0.168127E+12 | 0.00 | 0.00 | 0.00 | 0.241738E+10 | 0.00 | 0.00 | 0.00 |
August | 0.110502E+12 | 0.00 | 0.101962E+13 | 0.00 | 0.194220E+12 | 0.00 | 0.00 | 0.00 | 0.438976E+10 | 0.00 | 0.00 | 0.00 |
September | 0.106938E+12 | 0.00 | 0.214723E+11 | 0.00 | 0.654727E+10 | 0.00 | 0.00 | 0.00 | 0.104668E+11 | 0.00 | 0.00 | 0.00 |
October | 0.110502E+12 | 0.00 | 0.130324E+11 | 0.00 | 0.450848E+10 | 0.00 | 0.00 | 0.00 | 0.104701E+12 | 0.00 | 0.00 | 0.00 |
November | 0.106938E+12 | 0.00 | 0.237377E+11 | 0.00 | 0.649038E+10 | 0.00 | 0.00 | 0.00 | 0.213935E+12 | 0.00 | 0.00 | 0.00 |
December | 0.110502E+12 | 0.00 | 0.213730E+11 | 0.00 | 0.634028E+10 | 0.00 | 0.00 | 0.00 | 0.261231E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130107E+13 | 0.00 | 0.231307E+13 | 0.00 | 0.463665E+12 | 0.00 | 0.00 | 0.00 | 0.146152E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.998084E+11 | 0.00 | 0.104132E+11 | 0.00 | 0.386492E+10 | 0.00 | 0.00 | 0.00 | 0.241738E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110502E+12 | 0.00 | 0.101962E+13 | 0.00 | 0.194220E+12 | 0.00 | 0.00 | 0.00 | 0.261231E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146822E+10 | 0.00 | 0.369760E+10 | 0.00 | 0.701116E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132614E+10 | 0.00 | 0.933076E+10 | 0.00 | 0.166003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146822E+10 | 0.00 | 0.177341E+11 | 0.00 | 0.296199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142086E+10 | 0.00 | 0.233733E+11 | 0.00 | 0.367991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146822E+10 | 0.00 | 0.662169E+10 | 0.00 | 0.116215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142086E+10 | 0.00 | 0.130753E+11 | 0.00 | 0.230170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146822E+10 | 0.00 | 0.202798E+11 | 0.00 | 0.376847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146822E+10 | 0.00 | 0.259786E+11 | 0.00 | 0.463386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142086E+10 | 0.00 | 0.677384E+10 | 0.00 | 0.118894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146822E+10 | 0.00 | 0.122235E+11 | 0.00 | 0.203162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142086E+10 | 0.00 | 0.172519E+11 | 0.00 | 0.281228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146822E+10 | 0.00 | 0.230596E+11 | 0.00 | 0.375703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172871E+11 | 0.00 | 0.179400E+12 | 0.00 | 0.306591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132614E+10 | 0.00 | 0.369760E+10 | 0.00 | 0.701116E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146822E+10 | 0.00 | 0.259786E+11 | 0.00 | 0.463386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140833E+11 | 0.00 | 0.482856E+10 | 0.00 | 0.105321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127204E+11 | 0.00 | 0.578953E+11 | 0.00 | 0.106130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140833E+11 | 0.00 | 0.149193E+12 | 0.00 | 0.252303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136290E+11 | 0.00 | 0.211541E+12 | 0.00 | 0.335367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140833E+11 | 0.00 | 0.574620E+11 | 0.00 | 0.101597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136290E+11 | 0.00 | 0.121685E+12 | 0.00 | 0.214936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140833E+11 | 0.00 | 0.191855E+12 | 0.00 | 0.357141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140833E+11 | 0.00 | 0.246249E+12 | 0.00 | 0.440019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136290E+11 | 0.00 | 0.589047E+11 | 0.00 | 0.104206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140833E+11 | 0.00 | 0.102732E+12 | 0.00 | 0.172574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136290E+11 | 0.00 | 0.142842E+12 | 0.00 | 0.236175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140833E+11 | 0.00 | 0.183183E+12 | 0.00 | 0.304736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165819E+12 | 0.00 | 0.152837E+13 | 0.00 | 0.263572E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127204E+11 | 0.00 | 0.482856E+10 | 0.00 | 0.105321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140833E+11 | 0.00 | 0.246249E+12 | 0.00 | 0.440019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143260E+10 | 0.00 | 70086835.76 | 0.00 | 15676651.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129396E+10 | 0.00 | 0.390736E+10 | 0.00 | 0.730516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143260E+10 | 0.00 | 0.130697E+11 | 0.00 | 0.223471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138639E+10 | 0.00 | 0.199397E+11 | 0.00 | 0.318581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143260E+10 | 0.00 | 0.525310E+10 | 0.00 | 0.935163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138639E+10 | 0.00 | 0.120988E+11 | 0.00 | 0.214379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143260E+10 | 0.00 | 0.192717E+11 | 0.00 | 0.359493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143260E+10 | 0.00 | 0.246115E+11 | 0.00 | 0.441045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138639E+10 | 0.00 | 0.545481E+10 | 0.00 | 0.972793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143260E+10 | 0.00 | 0.867233E+10 | 0.00 | 0.147283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138639E+10 | 0.00 | 0.121634E+11 | 0.00 | 0.203990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143260E+10 | 0.00 | 0.161417E+11 | 0.00 | 0.272171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168677E+11 | 0.00 | 0.140654E+12 | 0.00 | 0.244583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129396E+10 | 0.00 | 70086835.76 | 0.00 | 15676651.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143260E+10 | 0.00 | 0.246115E+11 | 0.00 | 0.441045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 72300940.47 | 0.00 | 0.00 | 0.567528E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 67683663.92 | 0.00 | 0.00 | 0.514484E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 94115946.05 | 0.00 | 0.00 | 0.544081E+11 | 0.00 | 0.47 |
April | 0.00 | 0.00 | 0.00 | 88376962.72 | 0.00 | 0.00 | 0.544344E+11 | 0.00 | 0.62 |
May | 0.00 | 13053919.61 | 0.00 | 97235599.43 | 0.00 | 0.00 | 0.495228E+11 | 0.00 | 0.89 |
June | 0.00 | 0.133268E+10 | 0.00 | 96724525.21 | 0.00 | 0.00 | 0.315705E+11 | 0.00 | 0.90 |
July | 0.00 | 0.850042E+10 | 0.00 | 84704722.15 | 0.00 | 0.00 | 0.859191E+10 | 0.00 | 0.54 |
August | 0.00 | 0.404737E+10 | 0.00 | 0.110400E+09 | 0.00 | 0.00 | 0.167508E+11 | 0.00 | 0.76 |
September | 0.00 | 0.337198E+10 | 0.00 | 0.107678E+09 | 0.00 | 0.00 | 0.360705E+11 | 0.00 | 0.95 |
October | 0.00 | 0.00 | 0.00 | 0.112892E+09 | 0.00 | 0.00 | 0.620376E+11 | 0.00 | 0.82 |
November | 0.00 | 0.00 | 0.00 | 98297428.61 | 0.00 | 0.00 | 0.619989E+11 | 0.00 | 0.61 |
December | 0.00 | 0.00 | 0.00 | 89050402.05 | 0.00 | 0.00 | 0.561024E+11 | 0.00 | 0.34 |
Annual Sum or Average | 0.00 | 0.172655E+11 | 0.00 | 0.111946E+10 | 0.00 | 0.00 | 0.539689E+12 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 67683663.92 | 0.00 | 0.00 | 0.859191E+10 | 0.00 | 0.32 |
Maximum of Months | 0.00 | 0.850042E+10 | 0.00 | 0.112892E+09 | 0.00 | 0.00 | 0.620376E+11 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.976881E+10 | 0.00 | 0.00 | 38617046.24 | 0.00 | 0.00 | 0.236555E+11 | 0.00 | 0.34 |
February | 0.543504E+10 | 0.00 | 0.00 | 42429877.28 | 0.00 | 0.00 | 0.267468E+11 | 0.00 | 0.35 |
March | 0.178297E+10 | 7180.74 | 0.00 | 88482261.75 | 0.00 | 0.00 | 0.456931E+11 | 0.00 | 0.47 |
April | 0.397477E+10 | 0.00 | 0.00 | 92287935.42 | 0.00 | 0.00 | 0.518540E+11 | 0.00 | 0.63 |
May | 0.319337E+10 | 13453141.42 | 0.00 | 86848120.85 | 29543713.93 | 0.00 | 0.453376E+11 | 0.00 | 0.79 |
June | 0.229708E+10 | 0.287679E+10 | 0.00 | 82543640.44 | 0.742584E+09 | 0.00 | 0.288871E+11 | 0.00 | 0.97 |
July | 0.402719E+10 | 0.118500E+11 | 0.00 | 49528528.74 | 0.247024E+10 | 0.00 | 0.994059E+10 | 0.00 | 0.92 |
August | 0.656978E+10 | 0.695794E+10 | 0.00 | 80237346.03 | 0.127935E+10 | 0.00 | 0.199841E+11 | 0.00 | 1.07 |
September | 0.272697E+10 | 0.233903E+10 | 0.00 | 79828264.14 | 97319612.36 | 0.00 | 0.327683E+11 | 0.00 | 0.87 |
October | 0.206457E+10 | 0.00 | 0.00 | 90816010.45 | 0.00 | 0.00 | 0.477538E+11 | 0.00 | 0.61 |
November | 0.131220E+10 | 0.00 | 0.00 | 84373572.56 | 0.00 | 0.00 | 0.467516E+11 | 0.00 | 0.48 |
December | 0.143919E+10 | 0.00 | 0.00 | 73028386.69 | 0.00 | 0.00 | 0.405121E+11 | 0.00 | 0.38 |
Annual Sum or Average | 0.445919E+11 | 0.240372E+11 | 0.00 | 0.889021E+09 | 0.461903E+10 | 0.00 | 0.419885E+12 | 0.00 | 0.66 |
Minimum of Months | 0.131220E+10 | 0.00 | 0.00 | 38617046.24 | 0.00 | 0.00 | 0.994059E+10 | 0.00 | 0.34 |
Maximum of Months | 0.976881E+10 | 0.118500E+11 | 0.00 | 92287935.42 | 0.247024E+10 | 0.00 | 0.518540E+11 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.214084E+12 | 0.00 | 0.00 | 370231.95 | 0.00 | 0.710001E+10 | 0.185453E+10 | 0.00 | 0.30 |
February | 0.203817E+12 | 0.00 | 0.00 | 1641941.77 | 0.00 | 0.160265E+10 | 0.454802E+10 | 0.00 | 0.30 |
March | 0.149672E+12 | 0.00 | 0.00 | 0.210683E+09 | 0.00 | 0.00 | 0.147211E+12 | 0.00 | 0.35 |
April | 0.883092E+11 | 0.00 | 0.00 | 0.348810E+09 | 0.00 | 0.00 | 0.241627E+12 | 0.00 | 0.40 |
May | 0.336545E+11 | 83946885.81 | 0.00 | 0.595188E+09 | 0.212258E+09 | 0.00 | 0.342786E+12 | 0.00 | 0.63 |
June | 0.163847E+11 | 0.173191E+11 | 0.00 | 0.585374E+09 | 0.251525E+10 | 0.00 | 0.214046E+12 | 0.00 | 0.71 |
July | 0.105739E+11 | 0.711622E+11 | 0.00 | 0.355809E+09 | 0.907300E+10 | 0.00 | 0.744546E+11 | 0.00 | 0.59 |
August | 0.119457E+11 | 0.382776E+11 | 0.00 | 0.606371E+09 | 0.464660E+10 | 0.00 | 0.150545E+12 | 0.00 | 0.67 |
September | 0.326578E+11 | 0.152566E+11 | 0.00 | 0.539874E+09 | 0.280701E+09 | 0.00 | 0.235418E+12 | 0.00 | 0.67 |
October | 0.728086E+11 | 0.00 | 0.00 | 0.397576E+09 | 0.00 | 0.00 | 0.254542E+12 | 0.00 | 0.42 |
November | 0.120171E+12 | 0.00 | 0.00 | 0.209388E+09 | 96788316.00 | 0.00 | 0.159572E+12 | 0.00 | 0.33 |
December | 0.218855E+12 | 0.00 | 0.00 | 8263653.02 | 0.00 | 0.127699E+10 | 0.130784E+11 | 0.00 | 0.30 |
Annual Sum or Average | 0.117293E+13 | 0.142099E+12 | 0.00 | 0.385935E+10 | 0.168246E+11 | 0.997964E+10 | 0.183968E+13 | 0.00 | 0.47 |
Minimum of Months | 0.105739E+11 | 0.00 | 0.00 | 370231.95 | 0.00 | 0.00 | 0.185453E+10 | 0.00 | 0.30 |
Maximum of Months | 0.218855E+12 | 0.711622E+11 | 0.00 | 0.606371E+09 | 0.907300E+10 | 0.710001E+10 | 0.342786E+12 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344503E+10 | 0.00 | 0.00 | 0.28 |
February | 0.141987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286569E+10 | 0.00 | 0.00 | 0.28 |
March | 0.182870E+11 | 0.00 | 0.00 | 7323806.82 | 0.00 | 0.796434E+09 | 0.470293E+10 | 0.00 | 0.34 |
April | 0.146511E+11 | 0.00 | 0.00 | 14347250.98 | 0.00 | 97844346.20 | 0.128259E+11 | 0.00 | 0.37 |
May | 0.798933E+10 | 15948972.43 | 0.00 | 42068246.70 | 2072308.89 | 0.00 | 0.267506E+11 | 0.00 | 0.59 |
June | 0.252412E+10 | 0.190405E+10 | 0.00 | 52596159.33 | 0.337497E+09 | 0.00 | 0.203522E+11 | 0.00 | 0.75 |
July | 0.136557E+10 | 0.787397E+10 | 0.00 | 33112527.19 | 0.104753E+10 | 0.00 | 0.717795E+10 | 0.00 | 0.64 |
August | 0.156151E+10 | 0.446321E+10 | 0.00 | 54935405.47 | 0.590195E+09 | 0.00 | 0.135830E+11 | 0.00 | 0.70 |
September | 0.611737E+10 | 0.143489E+10 | 0.00 | 37916356.38 | 28439400.29 | 0.00 | 0.172948E+11 | 0.00 | 0.63 |
October | 0.142796E+11 | 0.00 | 0.00 | 14080978.03 | 0.00 | 0.164887E+09 | 0.113052E+11 | 0.00 | 0.37 |
November | 0.183791E+11 | 0.00 | 0.00 | 1100798.60 | 25180147.22 | 0.481837E+09 | 0.144980E+10 | 0.00 | 0.30 |
December | 0.149423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273009E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.128609E+12 | 0.156921E+11 | 0.00 | 0.257482E+09 | 0.203091E+10 | 0.105818E+11 | 0.115442E+12 | 0.00 | 0.46 |
Minimum of Months | 0.136557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.183791E+11 | 0.787397E+10 | 0.00 | 54935405.47 | 0.104753E+10 | 0.344503E+10 | 0.267506E+11 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.261457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785310E+09 | 0.00 | 0.00 | 0.27 |
February | 0.260457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479470E+09 | 0.00 | 0.00 | 0.27 |
March | 0.258402E+10 | 1165.50 | 0.00 | 2523633.25 | 0.00 | 90768620.42 | 0.147685E+10 | 0.00 | 0.35 |
April | 0.175653E+10 | 0.00 | 0.00 | 5224933.06 | 0.00 | 0.00 | 0.361604E+10 | 0.00 | 0.51 |
May | 0.100796E+10 | 590633.99 | 0.00 | 8755722.70 | 4386536.38 | 0.00 | 0.485714E+10 | 0.00 | 0.82 |
June | 0.361235E+09 | 0.552507E+09 | 0.00 | 11354341.02 | 82696624.85 | 0.00 | 0.403985E+10 | 0.00 | 1.22 |
July | 0.540098E+09 | 0.211288E+10 | 0.00 | 7344583.23 | 0.298141E+09 | 0.00 | 0.145187E+10 | 0.00 | 1.17 |
August | 0.892588E+09 | 0.118379E+10 | 0.00 | 11140651.63 | 0.159484E+09 | 0.00 | 0.256838E+10 | 0.00 | 1.26 |
September | 0.818670E+09 | 0.359793E+09 | 0.00 | 7202788.11 | 11950427.61 | 0.00 | 0.313074E+10 | 0.00 | 0.88 |
October | 0.174580E+10 | 0.00 | 0.00 | 4351092.45 | 0.00 | 0.00 | 0.282801E+10 | 0.00 | 0.47 |
November | 0.238506E+10 | 0.00 | 0.00 | 1676138.35 | 0.00 | 0.00 | 0.130764E+10 | 0.00 | 0.31 |
December | 0.310043E+10 | 0.00 | 0.00 | 63863.15 | 0.00 | 0.234604E+09 | 82314385.99 | 0.00 | 0.25 |
Annual Sum or Average | 0.204115E+11 | 0.420956E+10 | 0.00 | 59637746.97 | 0.556658E+09 | 0.159015E+10 | 0.253588E+11 | 0.00 | 0.65 |
Minimum of Months | 0.361235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.310043E+10 | 0.211288E+10 | 0.00 | 11354341.02 | 0.298141E+09 | 0.785310E+09 | 0.485714E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.166852E+10 | 0.00 | 0.00 | 49556.95 | 0.00 | 0.505646E+09 | 29493478.35 | 0.00 | 0.28 |
February | 0.150943E+10 | 0.00 | 0.00 | 592097.52 | 0.00 | 0.344994E+09 | 0.266404E+09 | 0.00 | 0.29 |
March | 0.142470E+10 | 848.14 | 0.00 | 4153587.70 | 0.00 | 41819874.51 | 0.195315E+10 | 0.00 | 0.45 |
April | 0.103255E+10 | 0.00 | 0.00 | 7390971.51 | 0.00 | 0.00 | 0.418051E+10 | 0.00 | 0.74 |
May | 0.545558E+09 | 1623955.04 | 0.00 | 11296658.34 | 1854222.72 | 0.00 | 0.584769E+10 | 0.00 | 1.33 |
June | 0.209664E+09 | 0.498350E+09 | 0.00 | 11626036.95 | 39518212.47 | 0.00 | 0.449563E+10 | 0.00 | 1.75 |
July | 0.332808E+09 | 0.166222E+10 | 0.00 | 9918338.31 | 0.192434E+09 | 0.00 | 0.185786E+10 | 0.00 | 1.64 |
August | 0.598007E+09 | 0.797780E+09 | 0.00 | 10751260.58 | 0.103379E+09 | 0.00 | 0.257072E+10 | 0.00 | 1.65 |
September | 0.434628E+09 | 0.276597E+09 | 0.00 | 9604155.23 | 7985900.97 | 0.00 | 0.378885E+10 | 0.00 | 1.33 |
October | 0.100139E+10 | 0.00 | 0.00 | 5349971.50 | 0.00 | 0.00 | 0.283558E+10 | 0.00 | 0.61 |
November | 0.167791E+10 | 0.00 | 0.00 | 1482037.97 | 0.00 | 0.00 | 0.879045E+09 | 0.00 | 0.33 |
December | 0.184132E+10 | 0.00 | 0.00 | 88507.64 | 0.00 | 0.338423E+09 | 47527276.90 | 0.00 | 0.26 |
Annual Sum or Average | 0.122765E+11 | 0.323658E+10 | 0.00 | 72303180.21 | 0.345171E+09 | 0.123088E+10 | 0.287525E+11 | 0.00 | 0.89 |
Minimum of Months | 0.209664E+09 | 0.00 | 0.00 | 49556.95 | 0.00 | 0.00 | 29493478.35 | 0.00 | 0.26 |
Maximum of Months | 0.184132E+10 | 0.166222E+10 | 0.00 | 11626036.95 | 0.192434E+09 | 0.505646E+09 | 0.584769E+10 | 0.00 | 1.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.210549E+10 | 0.00 | 0.00 | 2769821.80 | 0.00 | 0.804896E+09 | 0.151274E+10 | 0.00 | 0.35 |
February | 0.181995E+10 | 0.00 | 0.00 | 3552459.56 | 0.00 | 0.604087E+09 | 0.207412E+10 | 0.00 | 0.37 |
March | 0.179002E+10 | 3252.61 | 0.00 | 10633380.03 | 0.00 | 0.117695E+09 | 0.536184E+10 | 0.00 | 0.57 |
April | 0.162512E+10 | 0.00 | 0.00 | 10933517.42 | 0.00 | 3545062.03 | 0.678732E+10 | 0.00 | 0.83 |
May | 0.103022E+10 | 4532764.72 | 0.00 | 13113854.59 | 2913417.60 | 0.00 | 0.683484E+10 | 0.00 | 1.14 |
June | 0.454828E+09 | 0.620621E+09 | 0.00 | 12913906.78 | 75336096.69 | 0.00 | 0.449554E+10 | 0.00 | 1.41 |
July | 0.534100E+09 | 0.232935E+10 | 0.00 | 9644481.70 | 0.290179E+09 | 0.00 | 0.153379E+10 | 0.00 | 1.31 |
August | 0.890227E+09 | 0.136939E+10 | 0.00 | 16014383.46 | 0.152191E+09 | 0.00 | 0.314855E+10 | 0.00 | 1.56 |
September | 0.663416E+09 | 0.501672E+09 | 0.00 | 19186243.97 | 11654493.77 | 0.00 | 0.612273E+10 | 0.00 | 1.54 |
October | 0.137092E+10 | 0.00 | 0.00 | 13552404.37 | 0.00 | 982812.07 | 0.666622E+10 | 0.00 | 0.90 |
November | 0.221337E+10 | 0.00 | 0.00 | 6052918.84 | 0.00 | 15694381.87 | 0.328232E+10 | 0.00 | 0.46 |
December | 0.257756E+10 | 0.00 | 0.00 | 2667574.98 | 0.00 | 0.372720E+09 | 0.135659E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.170752E+11 | 0.482557E+10 | 0.00 | 0.121035E+09 | 0.532274E+09 | 0.191962E+10 | 0.491766E+11 | 0.00 | 0.90 |
Minimum of Months | 0.454828E+09 | 0.00 | 0.00 | 2667574.98 | 0.00 | 0.00 | 0.135659E+10 | 0.00 | 0.31 |
Maximum of Months | 0.257756E+10 | 0.232935E+10 | 0.00 | 19186243.97 | 0.290179E+09 | 0.804896E+09 | 0.683484E+10 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184291E+10 | 0.00 | 0.00 | 342081.75 | 0.00 | 0.112405E+09 | 0.310855E+09 | 0.00 | 0.28 |
February | 0.129128E+10 | 0.00 | 0.00 | 1781061.75 | 0.00 | 27496587.28 | 0.123240E+10 | 0.00 | 0.34 |
March | 0.396452E+09 | 1330.61 | 0.00 | 10501590.56 | 0.00 | 0.00 | 0.568964E+10 | 0.00 | 0.76 |
April | 0.141880E+09 | 0.00 | 0.00 | 17389424.74 | 0.00 | 0.00 | 0.950542E+10 | 0.00 | 1.44 |
May | 0.207017E+09 | 4509548.51 | 0.00 | 16047256.67 | 1333981.79 | 0.00 | 0.742456E+10 | 0.00 | 1.70 |
June | 0.104491E+09 | 0.651724E+09 | 0.00 | 19628415.53 | 25290903.89 | 0.00 | 0.552250E+10 | 0.00 | 2.41 |
July | 0.148559E+09 | 0.253592E+10 | 0.00 | 14985697.99 | 40433923.80 | 0.00 | 0.206439E+10 | 0.00 | 2.09 |
August | 0.207684E+09 | 0.155200E+10 | 0.00 | 20789848.19 | 8239341.46 | 0.00 | 0.417791E+10 | 0.00 | 2.50 |
September | 0.186205E+09 | 0.356947E+09 | 0.00 | 14018285.43 | 3426583.56 | 0.00 | 0.457418E+10 | 0.00 | 1.65 |
October | 0.272497E+09 | 0.00 | 0.00 | 9945647.50 | 0.00 | 0.00 | 0.551109E+10 | 0.00 | 0.97 |
November | 0.286863E+09 | 0.00 | 0.00 | 7140526.62 | 0.00 | 0.00 | 0.431931E+10 | 0.00 | 0.59 |
December | 0.756775E+09 | 0.00 | 0.00 | 3985681.25 | 0.00 | 0.00 | 0.256861E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.584262E+10 | 0.510110E+10 | 0.00 | 0.136556E+09 | 78724734.50 | 0.139902E+09 | 0.529009E+11 | 0.00 | 1.26 |
Minimum of Months | 0.104491E+09 | 0.00 | 0.00 | 342081.75 | 0.00 | 0.00 | 0.310855E+09 | 0.00 | 0.28 |
Maximum of Months | 0.184291E+10 | 0.253592E+10 | 0.00 | 20789848.19 | 40433923.80 | 0.112405E+09 | 0.950542E+10 | 0.00 | 2.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.356001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271728E+11 | 0.00 | 0.00 | 0.32 |
February | 0.590702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230673E+11 | 0.00 | 0.00 | 0.32 |
March | 0.210597E+11 | 0.00 | 0.00 | 6989771.70 | 0.00 | 0.115621E+11 | 0.294767E+10 | 0.00 | 0.33 |
April | 0.264688E+11 | 0.00 | 0.00 | 9287148.83 | 0.00 | 0.158413E+10 | 0.699616E+10 | 0.00 | 0.35 |
May | 0.147475E+11 | 4136768.80 | 0.00 | 54620665.09 | 28932019.11 | 0.00 | 0.296243E+11 | 0.00 | 0.63 |
June | 0.466235E+10 | 0.382439E+10 | 0.00 | 80860469.03 | 0.312880E+09 | 0.00 | 0.283455E+11 | 0.00 | 0.94 |
July | 0.181718E+10 | 0.146000E+11 | 0.00 | 54406290.25 | 0.112350E+10 | 0.00 | 0.108486E+11 | 0.00 | 0.83 |
August | 0.451224E+10 | 0.736250E+10 | 0.00 | 78532584.42 | 0.593658E+09 | 0.00 | 0.170006E+11 | 0.00 | 0.85 |
September | 0.133435E+11 | 0.242298E+10 | 0.00 | 42631086.65 | 45337753.45 | 0.00 | 0.166296E+11 | 0.00 | 0.67 |
October | 0.268363E+11 | 0.00 | 0.00 | 9542631.48 | 0.00 | 0.122065E+10 | 0.620099E+10 | 0.00 | 0.35 |
November | 0.253305E+11 | 0.00 | 0.00 | 0.00 | 12164871.60 | 0.678206E+10 | 0.00 | 0.00 | 0.30 |
December | 0.576874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255216E+11 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.154014E+12 | 0.282140E+11 | 0.00 | 0.336871E+09 | 0.211647E+10 | 0.969106E+11 | 0.118593E+12 | 0.00 | 0.52 |
Minimum of Months | 0.181718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.268363E+11 | 0.146000E+11 | 0.00 | 80860469.03 | 0.112350E+10 | 0.271728E+11 | 0.296243E+11 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.326114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136076E+11 | 0.00 | 0.00 | 0.26 |
February | 0.416615E+10 | 0.00 | 0.00 | 901974.42 | 0.00 | 0.114536E+11 | 0.307572E+09 | 0.00 | 0.26 |
March | 0.107315E+11 | 0.00 | 0.00 | 20024828.01 | 0.00 | 0.408813E+10 | 0.840533E+10 | 0.00 | 0.36 |
April | 0.963483E+10 | 0.00 | 0.00 | 50951542.10 | 0.00 | 0.547988E+09 | 0.274905E+11 | 0.00 | 0.58 |
May | 0.595887E+10 | 4168136.66 | 0.00 | 99267755.00 | 17540349.62 | 0.00 | 0.492827E+11 | 0.00 | 1.18 |
June | 0.199038E+10 | 0.374106E+10 | 0.00 | 0.107959E+09 | 78415847.76 | 0.00 | 0.411953E+11 | 0.00 | 1.58 |
July | 0.839479E+09 | 0.129018E+11 | 0.00 | 0.102234E+09 | 0.627297E+09 | 0.00 | 0.186204E+11 | 0.00 | 1.43 |
August | 0.193036E+10 | 0.575067E+10 | 0.00 | 0.105954E+09 | 0.367121E+09 | 0.00 | 0.241354E+11 | 0.00 | 1.40 |
September | 0.547005E+10 | 0.202967E+10 | 0.00 | 81417018.49 | 23100479.56 | 0.00 | 0.302080E+11 | 0.00 | 1.14 |
October | 0.104437E+11 | 0.00 | 0.00 | 28726947.16 | 0.00 | 0.601285E+09 | 0.149889E+11 | 0.00 | 0.44 |
November | 0.117189E+11 | 0.00 | 0.00 | 3055299.12 | 7838896.76 | 0.383290E+10 | 0.197064E+10 | 0.00 | 0.25 |
December | 0.320592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139232E+11 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.693513E+11 | 0.244274E+11 | 0.00 | 0.600492E+09 | 0.112131E+10 | 0.480547E+11 | 0.216605E+12 | 0.00 | 0.76 |
Minimum of Months | 0.839479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.117189E+11 | 0.129018E+11 | 0.00 | 0.107959E+09 | 0.627297E+09 | 0.139232E+11 | 0.492827E+11 | 0.00 | 1.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.994058E+10 | 0.00 | 0.00 | 20312166.47 | 0.00 | 0.169475E+11 | 0.914528E+10 | 0.00 | 0.37 |
February | 0.108354E+11 | 0.00 | 0.00 | 25848075.44 | 0.00 | 0.137449E+11 | 0.127709E+11 | 0.00 | 0.40 |
March | 0.178715E+11 | 0.00 | 0.00 | 87260385.19 | 0.00 | 0.393894E+10 | 0.427916E+11 | 0.00 | 0.60 |
April | 0.171739E+11 | 0.00 | 0.00 | 83246392.53 | 0.00 | 0.121898E+10 | 0.472969E+11 | 0.00 | 0.68 |
May | 0.122930E+11 | 47846692.33 | 0.00 | 0.114539E+09 | 13181513.91 | 0.00 | 0.577672E+11 | 0.00 | 1.04 |
June | 0.547689E+10 | 0.440039E+10 | 0.00 | 0.108311E+09 | 0.290263E+09 | 0.00 | 0.366925E+11 | 0.00 | 1.20 |
July | 0.239625E+10 | 0.174770E+11 | 0.00 | 80598657.64 | 0.102306E+10 | 0.00 | 0.123912E+11 | 0.00 | 1.03 |
August | 0.395123E+10 | 0.947457E+10 | 0.00 | 0.140119E+09 | 0.553074E+09 | 0.00 | 0.256391E+11 | 0.00 | 1.24 |
September | 0.855224E+10 | 0.399893E+10 | 0.00 | 0.187287E+09 | 35016236.98 | 0.00 | 0.535366E+11 | 0.00 | 1.43 |
October | 0.141477E+11 | 0.00 | 0.00 | 0.123491E+09 | 0.00 | 0.532422E+09 | 0.554032E+11 | 0.00 | 0.81 |
November | 0.201421E+11 | 5008408.41 | 0.00 | 44517027.45 | 8395814.04 | 0.418986E+10 | 0.259290E+11 | 0.00 | 0.46 |
December | 0.116216E+11 | 0.00 | 0.00 | 13696458.52 | 0.00 | 0.172684E+11 | 0.593403E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.134402E+12 | 0.354037E+11 | 0.00 | 0.102923E+10 | 0.192299E+10 | 0.578411E+11 | 0.385297E+12 | 0.00 | 0.80 |
Minimum of Months | 0.239625E+10 | 0.00 | 0.00 | 13696458.52 | 0.00 | 0.00 | 0.593403E+10 | 0.00 | 0.35 |
Maximum of Months | 0.201421E+11 | 0.174770E+11 | 0.00 | 0.187287E+09 | 0.102306E+10 | 0.172684E+11 | 0.577672E+11 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.480361E+10 | 0.00 | 0.00 | 88510.75 | 0.00 | 0.144774E+11 | 70658714.13 | 0.00 | 0.31 |
February | 0.673723E+10 | 0.00 | 0.00 | 1815928.44 | 0.00 | 0.109102E+11 | 0.111744E+10 | 0.00 | 0.32 |
March | 0.136491E+11 | 0.00 | 0.00 | 22652737.57 | 0.00 | 0.311618E+10 | 0.126148E+11 | 0.00 | 0.43 |
April | 0.111780E+11 | 0.00 | 0.00 | 54312041.77 | 0.00 | 0.254126E+09 | 0.296455E+11 | 0.00 | 0.66 |
May | 0.551925E+10 | 13626678.28 | 0.00 | 0.112406E+09 | 13557224.25 | 0.00 | 0.501407E+11 | 0.00 | 1.29 |
June | 0.214744E+10 | 0.417485E+10 | 0.00 | 0.132022E+09 | 0.149609E+09 | 0.00 | 0.365852E+11 | 0.00 | 1.76 |
July | 0.774115E+09 | 0.150307E+11 | 0.00 | 91384753.10 | 0.285735E+09 | 0.00 | 0.112009E+11 | 0.00 | 1.36 |
August | 0.126272E+10 | 0.738708E+10 | 0.00 | 0.109963E+09 | 0.152352E+09 | 0.00 | 0.195176E+11 | 0.00 | 1.41 |
September | 0.548353E+10 | 0.226033E+10 | 0.00 | 91507589.59 | 8635598.79 | 0.00 | 0.263757E+11 | 0.00 | 1.16 |
October | 0.126063E+11 | 0.00 | 0.00 | 28714430.13 | 0.00 | 0.370976E+09 | 0.158777E+11 | 0.00 | 0.50 |
November | 0.159977E+11 | 0.00 | 0.00 | 4666956.93 | 7805577.93 | 0.278085E+10 | 0.323024E+10 | 0.00 | 0.32 |
December | 0.706954E+10 | 0.00 | 0.00 | 146573.01 | 0.00 | 0.125784E+11 | 0.111369E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.872285E+11 | 0.288666E+11 | 0.00 | 0.649681E+09 | 0.617695E+09 | 0.444881E+11 | 0.206488E+12 | 0.00 | 0.82 |
Minimum of Months | 0.774115E+09 | 0.00 | 0.00 | 88510.75 | 0.00 | 0.00 | 70658714.13 | 0.00 | 0.30 |
Maximum of Months | 0.159977E+11 | 0.150307E+11 | 0.00 | 0.132022E+09 | 0.285735E+09 | 0.144774E+11 | 0.501407E+11 | 0.00 | 1.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 59905082.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268742E+10 | 0.00 | 0.00 | 0.34 |
February | 0.223416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235875E+10 | 0.00 | 0.00 | 0.34 |
March | 0.140014E+10 | 0.00 | 0.00 | 581120.46 | 0.00 | 0.149277E+10 | 0.227220E+09 | 0.00 | 0.36 |
April | 0.236462E+10 | 0.00 | 0.00 | 612778.89 | 0.00 | 0.468463E+09 | 0.491874E+09 | 0.00 | 0.36 |
May | 0.168591E+10 | 133145.30 | 0.00 | 4524607.68 | 1673267.72 | 21132508.46 | 0.261284E+10 | 0.00 | 0.61 |
June | 0.511956E+09 | 0.420812E+09 | 0.00 | 8106142.57 | 33895234.08 | 0.00 | 0.284573E+10 | 0.00 | 0.98 |
July | 0.219701E+09 | 0.159580E+10 | 0.00 | 5681686.64 | 0.122208E+09 | 0.00 | 0.109492E+10 | 0.00 | 0.90 |
August | 0.476960E+09 | 0.848271E+09 | 0.00 | 7897028.58 | 69066811.83 | 0.00 | 0.166566E+10 | 0.00 | 0.89 |
September | 0.134644E+10 | 0.217706E+09 | 0.00 | 3694596.49 | 11786952.28 | 25734089.57 | 0.146044E+10 | 0.00 | 0.65 |
October | 0.223988E+10 | 0.00 | 0.00 | 530440.37 | 0.00 | 0.467463E+09 | 0.378264E+09 | 0.00 | 0.36 |
November | 0.118419E+10 | 0.00 | 3056454.08 | 0.00 | 254737.44 | 0.144336E+10 | 0.00 | 39686.90 | 0.31 |
December | 0.163261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249065E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.118764E+11 | 0.308272E+10 | 3056454.08 | 31628401.68 | 0.238885E+09 | 0.114557E+11 | 0.107769E+11 | 39686.90 | 0.54 |
Minimum of Months | 59905082.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.236462E+10 | 0.159580E+10 | 3056454.08 | 8106142.57 | 0.122208E+09 | 0.268742E+10 | 0.284573E+10 | 39686.90 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 93928033.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161830E+10 | 0.00 | 0.00 | 0.33 |
February | 0.355537E+09 | 0.00 | 0.00 | 28212.25 | 0.00 | 0.124435E+10 | 7877933.05 | 0.00 | 0.33 |
March | 0.102767E+10 | 0.00 | 0.00 | 1387558.05 | 0.00 | 0.581462E+09 | 0.547032E+09 | 0.00 | 0.40 |
April | 0.107946E+10 | 0.00 | 0.00 | 4086839.99 | 0.00 | 0.152301E+09 | 0.243361E+10 | 0.00 | 0.61 |
May | 0.677891E+09 | 685617.62 | 0.00 | 9224681.54 | 536621.78 | 7138141.81 | 0.491355E+10 | 0.00 | 1.19 |
June | 0.191358E+09 | 0.417330E+09 | 0.00 | 11224294.99 | 9249817.96 | 0.00 | 0.434979E+10 | 0.00 | 1.70 |
July | 68324607.71 | 0.149472E+10 | 0.00 | 11207174.02 | 67436552.98 | 0.00 | 0.201301E+10 | 0.00 | 1.60 |
August | 0.175656E+09 | 0.684479E+09 | 0.00 | 11410191.85 | 39104919.79 | 0.00 | 0.252550E+10 | 0.00 | 1.52 |
September | 0.584309E+09 | 0.195761E+09 | 0.00 | 7511342.49 | 3209592.52 | 13419054.98 | 0.294753E+10 | 0.00 | 1.17 |
October | 0.110678E+10 | 0.00 | 0.00 | 1934526.04 | 0.00 | 0.199043E+09 | 0.108662E+10 | 0.00 | 0.44 |
November | 0.889599E+09 | 0.00 | 1898446.46 | 54844.01 | 240883.57 | 0.763701E+09 | 44685326.63 | 17253.74 | 0.31 |
December | 0.129413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155428E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.637992E+10 | 0.279297E+10 | 1898446.46 | 58069665.24 | 0.119778E+09 | 0.613399E+10 | 0.208692E+11 | 17253.74 | 0.83 |
Minimum of Months | 68324607.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.110678E+10 | 0.149472E+10 | 1898446.46 | 11410191.85 | 67436552.98 | 0.161830E+10 | 0.491355E+10 | 17253.74 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.534886E+09 | 0.00 | 0.00 | 1303852.51 | 0.00 | 0.178822E+10 | 0.571336E+09 | 0.00 | 0.35 |
February | 0.748140E+09 | 0.00 | 0.00 | 1948395.06 | 0.00 | 0.137769E+10 | 0.984140E+09 | 0.00 | 0.39 |
March | 0.130155E+10 | 0.00 | 0.00 | 6780856.39 | 0.00 | 0.648599E+09 | 0.336883E+10 | 0.00 | 0.58 |
April | 0.153710E+10 | 0.00 | 0.00 | 6756539.15 | 0.00 | 0.306782E+09 | 0.462092E+10 | 0.00 | 0.69 |
May | 0.130061E+10 | 1007874.04 | 0.00 | 10812443.47 | 1018182.43 | 25378305.77 | 0.573843E+10 | 0.00 | 1.01 |
June | 0.540107E+09 | 0.494950E+09 | 0.00 | 11332708.09 | 26395139.85 | 0.00 | 0.392059E+10 | 0.00 | 1.26 |
July | 0.260219E+09 | 0.196003E+10 | 0.00 | 10011930.37 | 0.114776E+09 | 0.00 | 0.140987E+10 | 0.00 | 1.14 |
August | 0.414485E+09 | 0.109990E+10 | 0.00 | 15439393.64 | 56592954.96 | 0.00 | 0.269835E+10 | 0.00 | 1.32 |
September | 0.813002E+09 | 0.360964E+09 | 0.00 | 17803963.36 | 5402595.85 | 15135016.80 | 0.546044E+10 | 0.00 | 1.43 |
October | 0.135289E+10 | 0.00 | 0.00 | 8963177.14 | 0.00 | 0.228336E+09 | 0.478504E+10 | 0.00 | 0.79 |
November | 0.122370E+10 | 0.00 | 130196.25 | 2921267.31 | 3025778.87 | 0.848382E+09 | 0.171645E+10 | 1708.72 | 0.42 |
December | 0.507718E+09 | 0.00 | 0.00 | 768219.10 | 0.00 | 0.184534E+10 | 0.338471E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.105344E+11 | 0.391685E+10 | 130196.25 | 94842745.59 | 0.207211E+09 | 0.708387E+10 | 0.356129E+11 | 1708.72 | 0.81 |
Minimum of Months | 0.260219E+09 | 0.00 | 0.00 | 768219.10 | 0.00 | 0.00 | 0.338471E+09 | 0.00 | 0.33 |
Maximum of Months | 0.153710E+10 | 0.196003E+10 | 130196.25 | 17803963.36 | 0.114776E+09 | 0.184534E+10 | 0.573843E+10 | 1708.72 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.251730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142466E+10 | 0.00 | 0.00 | 0.32 |
February | 0.446031E+09 | 0.00 | 0.00 | 143373.01 | 0.00 | 0.106372E+10 | 95537458.99 | 0.00 | 0.32 |
March | 0.101929E+10 | 0.00 | 0.00 | 1789229.29 | 0.00 | 0.460255E+09 | 0.101664E+10 | 0.00 | 0.43 |
April | 0.110824E+10 | 0.00 | 0.00 | 4360588.52 | 0.00 | 0.133511E+09 | 0.280660E+10 | 0.00 | 0.67 |
May | 0.677690E+09 | 1232160.21 | 0.00 | 10932236.54 | 197046.72 | 162151.80 | 0.498886E+10 | 0.00 | 1.27 |
June | 0.231986E+09 | 0.453384E+09 | 0.00 | 14539004.85 | 12576194.75 | 0.00 | 0.387802E+10 | 0.00 | 1.84 |
July | 90374342.25 | 0.163500E+10 | 0.00 | 10599008.32 | 32070372.09 | 0.00 | 0.122427E+10 | 0.00 | 1.48 |
August | 0.178685E+09 | 0.874328E+09 | 0.00 | 12356287.77 | 15496780.85 | 0.00 | 0.194273E+10 | 0.00 | 1.50 |
September | 0.580417E+09 | 0.205751E+09 | 0.00 | 8796648.08 | 778866.81 | 6026556.24 | 0.260337E+10 | 0.00 | 1.16 |
October | 0.120002E+10 | 0.00 | 0.00 | 2097399.32 | 0.00 | 0.141050E+09 | 0.132356E+10 | 0.00 | 0.51 |
November | 0.103875E+10 | 0.00 | 0.00 | 235333.38 | 2047796.18 | 0.521625E+09 | 0.190945E+09 | 0.00 | 0.32 |
December | 0.339588E+09 | 0.00 | 0.00 | 539.53 | 0.00 | 0.124894E+10 | 2393552.36 | 0.00 | 0.31 |
Annual Sum or Average | 0.716280E+10 | 0.316970E+10 | 0.00 | 65849648.61 | 63167057.40 | 0.499996E+10 | 0.200729E+11 | 0.00 | 0.85 |
Minimum of Months | 90374342.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.120002E+10 | 0.163500E+10 | 0.00 | 14539004.85 | 32070372.09 | 0.142466E+10 | 0.498886E+10 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2630821.20 | 0.00 | 0.00 | 0.829024E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7551057.47 | 0.00 | 0.00 | 0.752082E+09 | 0.00 | 0.28 |
March | 0.00 | 337295.18 | 0.00 | 15139684.20 | 0.00 | 0.00 | 0.661892E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 18284807.92 | 0.00 | 0.00 | 0.502810E+09 | 0.00 | 0.29 |
May | 0.00 | 185136.97 | 0.00 | 4166636.81 | 0.00 | 0.00 | 0.361592E+09 | 0.00 | 0.29 |
June | 0.00 | 57955751.76 | 0.00 | 6200493.74 | 0.00 | 0.00 | 0.158620E+09 | 0.00 | 0.30 |
July | 0.00 | 0.162913E+09 | 0.00 | 3605121.82 | 0.00 | 0.00 | 27265512.29 | 0.00 | 0.28 |
August | 0.00 | 83961910.35 | 0.00 | 11435979.88 | 0.00 | 0.00 | 71703359.49 | 0.00 | 0.31 |
September | 0.00 | 22928739.46 | 0.00 | 3357865.78 | 0.00 | 0.00 | 0.196365E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8902382.41 | 0.00 | 0.00 | 0.443445E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12770753.28 | 0.00 | 0.00 | 0.563401E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18523841.05 | 0.00 | 0.00 | 0.759834E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.328282E+09 | 0.00 | 0.112569E+09 | 0.00 | 0.00 | 0.532803E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2630821.20 | 0.00 | 0.00 | 27265512.29 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.162913E+09 | 0.00 | 18523841.05 | 0.00 | 0.00 | 0.829024E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.414830E+10 | 0.00 | 0.00 | 3746438.59 | 0.00 | 0.00 | 0.405713E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 50410102.14 | 0.00 | 0.00 | 0.754561E+10 | 0.00 | 0.28 |
March | 0.00 | 3233246.57 | 0.00 | 0.129480E+09 | 0.00 | 0.00 | 0.664152E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.167237E+09 | 0.00 | 0.00 | 0.504205E+10 | 0.00 | 0.29 |
May | 0.00 | 1668339.55 | 0.00 | 36044987.83 | 0.00 | 0.00 | 0.362564E+10 | 0.00 | 0.29 |
June | 0.00 | 0.573899E+09 | 0.00 | 57879040.68 | 0.00 | 0.00 | 0.158965E+10 | 0.00 | 0.30 |
July | 0.00 | 0.162392E+10 | 0.00 | 34163430.36 | 0.00 | 0.00 | 0.274212E+09 | 0.00 | 0.28 |
August | 0.00 | 0.838154E+09 | 0.00 | 0.108797E+09 | 0.00 | 0.00 | 0.720561E+09 | 0.00 | 0.31 |
September | 0.00 | 0.219535E+09 | 0.00 | 28793955.38 | 0.00 | 0.00 | 0.197895E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 76088987.35 | 0.00 | 0.00 | 0.444714E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.108035E+09 | 0.00 | 0.00 | 0.565088E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.151538E+09 | 0.00 | 0.00 | 0.763027E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.414830E+10 | 0.326041E+10 | 0.00 | 0.952215E+09 | 0.00 | 0.00 | 0.492036E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3746438.59 | 0.00 | 0.00 | 0.274212E+09 | 0.00 | 0.28 |
Maximum of Months | 0.414830E+10 | 0.162392E+10 | 0.00 | 0.167237E+09 | 0.00 | 0.00 | 0.763027E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.692526E+09 | 0.00 | 0.00 | 86289.36 | 0.00 | 0.00 | 0.105985E+09 | 0.00 | 0.28 |
February | 378148.56 | 0.00 | 0.00 | 4132015.46 | 0.00 | 0.00 | 0.754987E+09 | 0.00 | 0.28 |
March | 0.00 | 315168.73 | 0.00 | 11753980.39 | 0.00 | 0.00 | 0.665384E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15933033.41 | 0.00 | 0.00 | 0.505068E+09 | 0.00 | 0.29 |
May | 0.00 | 176263.57 | 0.00 | 3290597.79 | 0.00 | 0.00 | 0.363231E+09 | 0.00 | 0.29 |
June | 0.00 | 57472539.88 | 0.00 | 5738957.40 | 0.00 | 0.00 | 0.159142E+09 | 0.00 | 0.30 |
July | 0.00 | 0.162368E+09 | 0.00 | 3401266.84 | 0.00 | 0.00 | 27481653.67 | 0.00 | 0.28 |
August | 0.00 | 83730038.25 | 0.00 | 10844039.02 | 0.00 | 0.00 | 72226024.89 | 0.00 | 0.31 |
September | 0.00 | 21996729.36 | 0.00 | 2596618.71 | 0.00 | 0.00 | 0.198968E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6622751.17 | 0.00 | 0.00 | 0.446050E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9513630.29 | 0.00 | 0.00 | 0.566520E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13994893.26 | 0.00 | 0.00 | 0.764263E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.692904E+09 | 0.326059E+09 | 0.00 | 87908073.10 | 0.00 | 0.00 | 0.462931E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 86289.36 | 0.00 | 0.00 | 27481653.67 | 0.00 | 0.28 |
Maximum of Months | 0.692526E+09 | 0.162368E+09 | 0.00 | 15933033.41 | 0.00 | 0.00 | 0.764263E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.648247E+09 | 0.00 | 0.00 | 0.473518E+12 | 0.00 | 7.15 |
February | 0.00 | 0.00 | 0.00 | 0.120192E+10 | 0.00 | 0.00 | 0.723378E+12 | 0.00 | 11.94 |
March | 0.00 | 0.00 | 0.00 | 0.172217E+10 | 0.00 | 0.00 | 0.100469E+13 | 0.00 | 22.99 |
April | 0.00 | 0.00 | 0.00 | 0.213599E+10 | 0.00 | 0.00 | 0.121524E+13 | 0.00 | 34.99 |
May | 0.00 | 0.00 | 0.00 | 0.542201E+09 | 0.00 | 0.00 | 0.423170E+12 | 0.00 | 18.40 |
June | 0.00 | 0.144114E+11 | 0.00 | 0.105903E+10 | 0.00 | 0.00 | 0.465669E+12 | 0.00 | 38.33 |
July | 0.00 | 0.945158E+11 | 0.00 | 0.130590E+10 | 0.00 | 0.00 | 0.229883E+12 | 0.00 | 43.61 |
August | 0.00 | 0.586528E+11 | 0.00 | 0.179246E+10 | 0.00 | 0.00 | 0.324626E+12 | 0.00 | 45.21 |
September | 0.00 | 0.681149E+09 | 0.00 | 0.555627E+09 | 0.00 | 0.00 | 0.338939E+12 | 0.00 | 24.30 |
October | 0.00 | 0.00 | 0.00 | 0.103115E+10 | 0.00 | 0.00 | 0.692477E+12 | 0.00 | 23.03 |
November | 0.00 | 0.00 | 0.00 | 0.147357E+10 | 0.00 | 0.00 | 0.100918E+13 | 0.00 | 26.00 |
December | 0.00 | 0.00 | 0.00 | 0.260587E+10 | 0.00 | 0.00 | 0.132730E+13 | 0.00 | 23.60 |
Annual Sum or Average | 0.00 | 0.168261E+12 | 0.00 | 0.160741E+11 | 0.00 | 0.00 | 0.822808E+13 | 0.00 | 26.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.542201E+09 | 0.00 | 0.00 | 0.229883E+12 | 0.00 | 7.15 |
Maximum of Months | 0.00 | 0.945158E+11 | 0.00 | 0.260587E+10 | 0.00 | 0.00 | 0.132730E+13 | 0.00 | 45.21 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.241523E+12 | 0.249079E+11 | 0.00 | 0.211894E+13 | 0.525077E+11 |
February | 0.378965E+12 | 0.260475E+11 | 0.00 | 0.226433E+13 | 0.113844E+12 |
March | 0.575119E+12 | 0.164999E+11 | 0.00 | 0.283220E+13 | 0.312967E+12 |
April | 0.699388E+12 | 0.134609E+11 | 0.00 | 0.313855E+13 | 0.382311E+12 |
May | 0.865254E+12 | 0.752325E+10 | 0.00 | 0.224736E+13 | 0.350501E+12 |
June | 0.933182E+12 | 0.320818E+10 | 0.00 | 0.152703E+13 | 0.136468E+13 |
July | 0.867402E+12 | -313790467.6 | 0.00 | 0.364829E+12 | 0.284393E+13 |
August | 0.739517E+12 | 0.138939E+10 | 0.00 | 0.105242E+13 | 0.278798E+13 |
September | 0.557985E+12 | 0.431786E+10 | 0.00 | 0.183195E+13 | 0.745789E+12 |
October | 0.370354E+12 | 0.103676E+11 | 0.00 | 0.262986E+13 | 0.264468E+12 |
November | 0.195401E+12 | 0.144405E+11 | 0.00 | 0.281288E+13 | 0.237172E+12 |
December | 0.217137E+12 | 0.264670E+11 | 0.00 | 0.302427E+13 | 0.274842E+12 |
Annual Sum or Average | 0.664123E+13 | 0.148316E+12 | 0.00 | 0.258446E+14 | 0.973098E+13 |
Minimum of Months | 0.195401E+12 | -313790467.6 | 0.00 | 0.364829E+12 | 0.525077E+11 |
Maximum of Months | 0.933182E+12 | 0.264670E+11 | 0.00 | 0.313855E+13 | 0.284393E+13 |