Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2024-07-03 12:21:46
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 25730.46 | 555.49 | 555.49 |
Net Site Energy | 25276.28 | 545.68 | 545.68 |
Total Source Energy | 80409.10 | 1735.93 | 1735.93 |
Net Source Energy | 78970.71 | 1704.88 | 1704.88 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 518.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1806.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1717.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 265.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1641.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2274.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 412.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 674.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4636.61 |
Humidification | 1273.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.80 |
Heat Recovery | 43.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 426.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 25212.33 | 518.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7390.57 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 518.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1806.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1717.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 265.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1582.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2274.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 412.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 674.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4636.61 |
Humidification | General | 1273.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.80 |
Heat Recovery | General | 43.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 426.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 518.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1806.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1717.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 265.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1641.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2274.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 412.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 674.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4636.61 |
Humidification | Unassigned | 1273.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.80 |
Heat Recovery | Unassigned | 43.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 426.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 148.28 | 11.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 353.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 544.30 | 11.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 148.28 | 11.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 353.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 544.30 | 11.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 475.327 | 1.89 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -21.15 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 454.180 | 1.80 |
Electricity Coming From Utility | 24758.149 | 98.20 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 24758.149 | 98.20 |
Total On-Site and Utility Electric Sources | 25212.329 | 100.00 |
Total Electricity End Uses | 25212.329 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 477.02 | 27.76 |
Air to Air Heat Recovery for Heating | 1241.40 | 72.24 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1718.42 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 7390.57 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 7390.57 | 100.00 |
Total Water End Uses | 7390.57 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 29.50 |
Time Setpoint Not Met During Occupied Cooling | 1628.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5933.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-AUG-14:30 | 02-JAN-05:10 | - | - | - | - | - | - | - | - | - | - | 30-AUG-15:50 |
Heating | 0.00 | 1501293.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 407412.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 154722.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 258556.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 48135.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 79373.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23278.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1895837.77 | 1501293.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1501293.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 407412.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3359.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 151268.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 94.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 258556.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 48135.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 79373.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 23278.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 561.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5720.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5438.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 841.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 5198.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7204.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1307.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2136.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4033.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 137.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1350.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 79847.45 | 561.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 123.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 112.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 46.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 87.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1723.81 | 12.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 123.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 112.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 46.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 87.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1723.81 | 12.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 4.80 | 0.441158 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.23 | 0.363630 | 0.309000 | 1.62 | 0.969680 | 0.500000 | 0.001048 | 0.000356 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 49.03 | 0.387937 | 0.330000 | 16.18 | 1.00 | 0.500000 | 0.000982 | 0.009089 | 16.18 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.00 | 0.380040 | 0.323000 | 1.62 | 1.00 | 0.500000 | 0.001003 | 0.001810 | 2.46 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.926770 | 0.257691 | 0.219000 | 0.202963 | 0.687177 | 0.500000 | 0.001479 | 0.000272 | 0.369889 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.17 | 0.131075 | 0.111000 | 0.130334 | 0.349533 | 0.500000 | 0.002907 | 0.000187 | 0.254825 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.35 | 0.177098 | 0.151000 | 0.203632 | 0.472261 | 0.500000 | 0.002151 | 0.000314 | 0.428175 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.44 | 0.106686 | 0.091000 | 0.131277 | 0.300000 | 0.500000 | 0.003571 | 0.000140 | 0.190133 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.72 | 0.273778 | 0.233000 | 2.03 | 0.730075 | 0.500000 | 0.001392 | 0.004893 | 6.68 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 12.53 | 0.327430 | 0.500000 | 0.003103 | 0.003210 | 4.38 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 13.27 | 0.179959 | 0.153000 | 2.03 | 0.479890 | 0.500000 | 0.002117 | 0.004835 | 6.60 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 13.04 | 0.118055 | 0.100000 | 1.30 | 0.314812 | 0.500000 | 0.003227 | 0.003091 | 4.22 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.997106 | 0.239514 | 0.204000 | 0.203410 | 0.638703 | 0.500000 | 0.001591 | 0.000618 | 0.843439 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.28 | 0.120603 | 0.103000 | 0.131442 | 0.321607 | 0.500000 | 0.003159 | 0.000404 | 0.551314 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.44 | 0.165362 | 0.141000 | 0.203641 | 0.440966 | 0.500000 | 0.002304 | 0.000612 | 0.835140 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.39 | 0.111024 | 0.094000 | 0.130306 | 0.300000 | 0.500000 | 0.003432 | 0.000395 | 0.539782 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16266.37 | 0.000356 | 454.00 | |
CORE_MID VAV BOX REHEAT COIL | 415508.39 | 0.009089 | 14166.36 | |
CORE_TOP VAV BOX REHEAT COIL | 82739.32 | 0.001810 | 3220.76 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 12412.54 | 0.000272 | 482.80 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8549.46 | 0.000187 | 332.49 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 14363.26 | 0.000314 | 558.54 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6385.61 | 0.000140 | 248.51 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 223669.03 | 0.004893 | 8691.46 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 146725.82 | 0.003210 | 5701.41 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 221018.50 | 0.004835 | 8588.59 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 141309.19 | 0.003091 | 5491.15 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 28249.85 | 0.000618 | 1097.45 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 18465.01 | 0.000404 | 717.32 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 27972.32 | 0.000612 | 1086.68 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 18079.17 | 0.000395 | 702.34 | |
VAV_BOT WITH REHEAT HEATING COIL | 58946.48 | 0.001289 | 1211.67 | |
VAV_MID WITH REHEAT HEATING COIL | 540378.15 | 0.011821 | 11150.58 | |
VAV_TOP WITH REHEAT HEATING COIL | 50990.30 | 0.001115 | 1082.14 | |
CAV_BAS HEATING COIL | 247784.23 | 0.002188 | 3856.29 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.469189 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.49 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.457633 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.41 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.06 | 2.28 | 10.12 | 2.32 | 8.90 | 8.90 | 0.300000 | 0.260915 | 8.90 |
VAV_MID WITH REHEAT | 48.30 | 22.85 | 96.60 | 32.65 | 83.20 | 83.20 | 0.300000 | 0.392381 | 83.20 |
VAV_TOP WITH REHEAT | 5.05 | 2.29 | 10.11 | 5.23 | 9.12 | 9.12 | 0.300000 | 0.573890 | 9.12 |
CAV_BAS | 0.000000 | 0.000000 | 4.80 | 1.20 | 4.80 | 4.80 | 1.00 | 0.249990 | 4.80 |
AIRLOOP DATACENTER BASEMENT | 24.41 | 24.41 | 24.41 | 24.41 | 24.41 | 24.41 | 1.00 | 0.999988 | 24.41 |
AIRLOOP DATACENTER BOT | 0.469189 | 0.469189 | 0.469189 | 0.469189 | 0.469189 | 0.469189 | 1.00 | 1.00 | 0.469189 |
AIRLOOP DATACENTER MID | 4.49 | 4.49 | 4.49 | 4.49 | 4.49 | 4.49 | 1.00 | 1.00 | 4.49 |
AIRLOOP DATACENTER TOP | 0.457633 | 0.457633 | 0.457633 | 0.457633 | 0.457633 | 0.457633 | 1.00 | 1.00 | 0.457633 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.90 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 83.20 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.12 | |
CAV_BAS_OA_CONTROLLER | 4.80 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.41 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.469189 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.49 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.457633 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.03 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 20.31 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.03 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.92 | 6.67 | 11.05 | 0.010129 | 0.008500 | 206943.01 | 0.005919 | 8.90 |
VAV_MID WITH REHEAT COOLING COIL | 26.11 | 6.67 | 11.05 | 0.010316 | 0.008500 | 2003320.57 | 0.057295 | 83.20 |
VAV_TOP WITH REHEAT COOLING COIL | 25.80 | 6.67 | 11.05 | 0.010079 | 0.008500 | 209428.49 | 0.005990 | 9.12 |
CAV_BAS COOLING COIL | 24.77 | 6.67 | 11.02 | 0.010299 | 0.008500 | 107570.32 | 0.003076 | 4.80 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.90 |
VAV_MID WITH REHEAT FAN | 83.20 |
VAV_TOP WITH REHEAT FAN | 9.12 |
CAV_BAS FAN | 4.80 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005919 | 0.000080 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001289 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.057295 | 0.000008 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.011821 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005990 | 0.000080 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001115 | |
CAV_BAS_COOLC_CONTROLLER | 0.003076 | 0.000155 |
CAV_BAS_HEATC_CONTROLLER | 0.002188 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.41 | 492768.69 | 356200.12 | 0.012068 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.469189 | 9443.78 | 6832.11 | 0.000231 |
AIRLOOP DATACENTER MID COOLING COIL | 4.49 | 90558.88 | 65452.24 | 0.002218 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.457633 | 9223.37 | 6667.94 | 0.000226 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.41 | 24.41 | 24.41 | 24.41 | 492768.69 | 492768.69 | 20749.82 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.469189 | 0.469189 | 0.469189 | 0.469189 | 9443.78 | 9443.78 | 958.56 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.49 | 4.49 | 4.49 | 4.49 | 90558.88 | 90558.88 | 9585.56 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.457633 | 0.457633 | 0.457633 | 0.457633 | 9223.37 | 9223.37 | 958.56 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.41 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.469189 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.49 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.457633 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.41 | 492768.69 | 0.012068 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.469189 | 9443.78 | 0.000231 |
AIRLOOP DATACENTER MID HEATING COIL | 4.49 | 90558.88 | 0.002218 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.457633 | 9223.37 | 0.000226 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 20749.82 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 958.56 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 9585.56 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 958.56 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000198 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.072279 | 11684.17 | |
HEATSYS1 PUMP | 0.046638 | 13906.31 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.072279 | 8.67 |
HEATSYS1 | 0.046638 | 5.60 |
COOLSYS1_SUPPLY | 0.072279 | 8.67 |
SINGLE WATER PLANT LOOP | 0.014743 | 1.77 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.072279 | 0.072279 | 303392.84 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2132028.77 | 2132028.77 | 0.046638 |
CENTRAL BOILER | 607277.47 | 595320.93 | 0.014743 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.036140 | 4044.67 |
COOLSYS1 CHILLER2 PUMP | 0.036140 | 4044.67 |
PLANT CIRC PUMP | 0.014743 | 3722.93 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.072279 | 0.036454 | 1274626.28 | 1274625.79 | 0.064184 |
COOLSYS1 CHILLER2 | 0.072279 | 0.036454 | 1274626.28 | 1274625.79 | 0.064184 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.014743 | 146385.19 | 74104.31 | 73192.59 | 7004.20 | 44462.59 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.128368 | 15.40 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.128368 | 31466.31 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 46.87 | 1525721.25 | 9.37 | 190715.16 |
TOWERWATERSYS COOLTOWER 2 | 46.87 | 1525721.25 | 9.37 | 190715.16 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.066098 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.9398 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.9084 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8967 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9335 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8058 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.29018797E-14 | 0.36812723E-16 | -0.14924019E-09 | 0.48847313E-16 |
51 | 8 | 0.21807402E-07 | 0.12652057E-12 | 0.37708831E-03 | -0.24795767E-09 |
52 | 7 | -0.12220551E-01 | 0.65729479E-08 | -0.23055577E-01 | 0.13895212E-03 |
53 | 6 | 0.40477966 | 0.22909352E-05 | 0.47160541 | -0.47410351E-02 |
54 | 5 | -5.1849947 | 0.85678555E-04 | -4.4375337 | 0.63114796E-01 |
55 | 4 | 32.978226 | 0.70190469E-03 | 21.425779 | -0.42179587 |
56 | 3 | -111.17384 | 0.15317614E-02 | -55.595241 | 1.5144378 |
57 | 2 | 197.07933 | 0.86263138E-03 | 77.848428 | -2.8998938 |
58 | 1 | -171.14541 | 0.92189209E-04 | -55.246988 | 2.7452524 |
59 | 0 | 57.057407 | 0.52547460E-06 | 15.559906 | |
60 | 9 | -0.29188985E-14 | 0.30841220E-16 | -0.15071594E-09 | 0.45756810E-16 |
61 | 8 | 0.22014798E-07 | 0.12246996E-12 | 0.37926559E-03 | -0.25031584E-09 |
62 | 7 | -0.12285514E-01 | 0.63488536E-08 | -0.23149110E-01 | 0.13969077E-03 |
63 | 6 | 0.40654483 | 0.22108485E-05 | 0.47310859 | -0.47618422E-02 |
64 | 5 | -5.2022205 | 0.82619656E-04 | -4.4490782 | 0.63328388E-01 |
65 | 4 | 33.054419 | 0.67637415E-03 | 21.470902 | -0.42280751 |
66 | 3 | -111.33595 | 0.14751306E-02 | -55.684449 | 1.5167798 |
67 | 2 | 197.23999 | 0.83027991E-03 | 77.930247 | -2.9024452 |
68 | 1 | -171.20475 | 0.88686394E-04 | -55.270783 | 2.7462925 |
69 | 0 | 57.057407 | 0.50524406E-06 | 15.555978 | |
70 | 9 | -0.57207635E-15 | 0.35733182E-16 | -0.14510758E-09 | 0.92780423E-20 |
71 | 8 | 0.21226260E-07 | 0.13767829E-12 | 0.37094976E-03 | -0.24134990E-09 |
72 | 7 | -0.12037268E-01 | 0.71989887E-08 | -0.22791647E-01 | 0.13686812E-03 |
73 | 6 | 0.39979937 | 0.25155658E-05 | 0.46736115 | -0.46823295E-02 |
74 | 5 | -5.1363910 | 0.94286903E-04 | -4.4049234 | 0.62512134E-01 |
75 | 4 | 32.763227 | 0.77396227E-03 | 21.298286 | -0.41894130 |
76 | 3 | -110.71637 | 0.16919998E-02 | -55.343173 | 1.5078286 |
77 | 2 | 196.62589 | 0.95437189E-03 | 77.617295 | -2.8926932 |
78 | 1 | -170.97790 | 0.10214201E-03 | -55.179873 | 2.7423166 |
79 | 0 | 57.057407 | 0.58311013E-06 | 15.571069 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3569E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3590E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9511E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9529E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5254E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5268E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4917E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4924E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4051E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5483E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9918E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1170E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5603E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6638E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5122E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5645E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1579 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5943E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1783 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5187E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1115 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4149E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5025E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5661E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4078E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5608E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9945E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1301E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5626E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6727E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5127E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5660E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3567E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3588E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9509E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9527E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5252E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5267E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4916E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4923E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4525E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7393E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1616E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4743E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9559E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0822E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2602E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2962E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0027E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9330E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5444E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6356E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8814E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4384E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6880E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7537E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3654E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4663E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0490E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1220E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9156E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9438E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2603E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2968E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5875E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5895E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1978E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1994E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9464E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9475E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4917E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4925E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6326E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7498E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2344E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3268E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9759E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0415E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5127E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5660E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1313E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1799E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1624E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6479E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8556E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1125E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5025E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5656E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6313E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7471E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2331E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3237E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9741E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0360E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5122E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5645E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5873E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5893E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1977E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1993E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9463E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9474E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4916E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4923E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2128E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3147E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8585E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9320E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7924E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8200E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2604E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2969E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7369E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8281E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2150E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5054E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6540E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3481E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6880E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7537E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2947E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5617E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9646E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2522E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8319E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9547E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2601E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2961E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1536 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1041 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1676 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1154 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1224 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5201E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.5140E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7277E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.1673E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.2374E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6549E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8733E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.9870E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6115E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.6552E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7590E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.1380E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.4253E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0404E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6986E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7042E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0286E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5140E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7273E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8666E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0927E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2819E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6932E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.7321E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4915E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6552E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7590E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1537 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1043 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1677 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1156 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1225 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5363E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.5258E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7338E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.1723E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.2439E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6605E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8794E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.9979E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6191E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.6670E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7650E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.1384E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.4292E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0411E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7016E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7101E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0323E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5258E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7333E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8711E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0987E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2870E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6988E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.7426E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4988E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6670E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7650E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 66689.05651 | 66689.05651 | 4.80083 | 4.80083 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | -10.70000 | 1.50390E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72654.05922 | 72654.05922 | 5.23071 | 5.23071 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 681228.99628 | 681228.99628 | 49.02974 | 49.02974 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 252674.32845 | 252674.32845 | 10.65029 | 10.77825 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 69528.72348 | 69528.72348 | 5.00486 | 5.00486 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 57955.46963 | 57955.46963 | 2.46262 | 2.46262 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12749.36099 | 12749.36099 | 0.92677 | 0.92677 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 8695.54562 | 8695.54562 | 0.36989 | 0.36989 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 16153.03501 | 16153.03501 | 1.17418 | 1.17418 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 27.79567 | 1.41119E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 5988.37150 | 5988.37150 | 0.25482 | 0.25482 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 18551.82731 | 18551.82731 | 1.34855 | 1.34855 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 31.73000 | 1.41190E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 10058.96535 | 10058.96535 | 0.42817 | 0.42817 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19845.73778 | 19845.73778 | 1.44260 | 1.44260 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 31.36000 | 1.41183E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 4476.62367 | 4476.62367 | 0.19013 | 0.19013 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 119997.99476 | 119997.99476 | 8.72314 | 8.72314 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 156568.47877 | 156568.47877 | 6.67518 | 6.67518 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 172428.27285 | 172428.27285 | 12.53437 | 12.53437 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.41127E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 102707.10033 | 102707.10033 | 4.37906 | 4.37906 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 182562.74673 | 182562.74673 | 13.27115 | 13.27115 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 154715.49465 | 154715.49465 | 6.59593 | 6.59593 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 179339.47272 | 179339.47272 | 13.03677 | 13.03677 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 98920.09305 | 98920.09305 | 4.21714 | 4.21714 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13716.30980 | 13716.30980 | 0.99711 | 0.99711 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 19771.33933 | 19771.33933 | 0.84344 | 0.84344 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 17554.80286 | 17554.80286 | 1.27613 | 1.27613 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.41127E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 12923.15231 | 12923.15231 | 0.55131 | 0.55131 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 19867.52382 | 19867.52382 | 1.44426 | 1.44426 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 19577.29825 | 19577.29825 | 0.83514 | 0.83514 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 19069.45404 | 19069.45404 | 1.38624 | 1.38624 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 12653.35621 | 12653.35621 | 0.53978 | 0.53978 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8183.53584 | 8183.53584 | 0.46919 | 0.46919 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.41151E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 78332.99759 | 78332.99759 | 4.49112 | 4.49112 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.41151E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7981.95123 | 7981.95123 | 0.45763 | 0.45763 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.76900 | 1.41154E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370277.85473 | 425819.53294 | 21.22888 | 24.41321 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 25.36600 | 1.41076E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -10.70000 | 1.50390E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 136133.13 | 8.89504 | 8.89504 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 58273.06 | 2.32085 | 2.32085 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1253464.23 | 83.19850 | 83.19850 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 576888.56 | 32.64555 | 32.64555 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 143378.12 | 9.11723 | 9.11723 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 57654.23 | 5.23229 | 5.23229 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 |
7 | CAV_BAS | Cooling | Sensible | 69389.00 | 4.80083 | 4.80083 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 73592.09 | 1.20016 | 1.20016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 420903.11 | 24.41350 | 24.41350 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 20749.82 | 0.33839 | 0.33839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8105.88 | 0.46919 | 0.46919 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 958.56 | 1.56323E-002 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 77610.57 | 4.49112 | 4.49112 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 9585.56 | 0.15632 | 0.15632 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7910.91 | 0.45763 | 0.45763 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 958.56 | 1.56323E-002 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 4.80083 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.44116 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.23071 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36363 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61629 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96968 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04777E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.55827E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61629 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16266.37347 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.55827E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 453.99611 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 49.02974 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38794 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.17981 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.82119E-004 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.08926E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.17981 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 415508.38970 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.08926E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 14166.36464 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.00486 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38004 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32300 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61657 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00253E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.80992E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.46262 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 82739.31768 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80992E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3220.75841 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92677 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25769 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21900 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20296 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68718 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47851E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.71525E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36989 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12412.54375 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.71525E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 482.79870 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17418 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13107 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11100 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13033 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34953 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90674E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.87020E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25482 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8549.45909 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.87020E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 332.49425 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.34855 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17710 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15100 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20363 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47226 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.15135E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.14197E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42817 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14363.25973 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.14197E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 558.54246 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.44260 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10669 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.10000E-002 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13128 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.57123E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.39685E-004 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19013 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6385.60744 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39685E-004 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 248.50633 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.72314 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27378 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23300 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03249 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73007 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39164E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.89277E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.67518 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 223669.03003 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.89277E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8691.46059 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.53437 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32743 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10295E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.20963E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.37906 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 146725.82018 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.20963E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5701.41164 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.27115 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17996 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15300 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03049 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47989 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11715E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.83479E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.59593 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 221018.49641 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.83479E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8588.59020 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.03677 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11805 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30368 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31481 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22732E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.09114E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.21714 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 141309.18839 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.09114E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5491.15304 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99711 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23951 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20400 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20341 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63870 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.59072E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.17966E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84344 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 28249.85327 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.17966E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1097.45474 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27613 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12060 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10300 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13144 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32161 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.15914E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.03923E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55131 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18465.00829 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.03923E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 717.31880 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.44426 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16536 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14100 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20364 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44097 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.30403E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.11895E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.83514 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27972.32057 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.11895E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1086.68347 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38624 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11102 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.40000E-002 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13031 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.43170E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.95482E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.53978 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18079.17306 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.95482E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 702.34025 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46919 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.49112 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45763 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.41321 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.06141 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28449 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.12281 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.32085 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.89504 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.89504 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.26091 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 48.29759 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.85004 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 96.59517 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 32.64555 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 83.19850 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 83.19850 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.39238 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.05430 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28537 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.10859 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.23229 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.11723 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.11723 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.57389 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.80083 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.80083 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 4.80083 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.24999 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.41321 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.41321 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.41321 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.41321 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.41350 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.41350 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46919 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46919 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46919 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46919 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46919 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46919 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.49112 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.49112 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.49112 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.49112 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.49112 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.49112 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45763 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45763 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45763 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45763 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45763 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45763 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.89504 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 83.19850 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.11723 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 4.80083 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.41350 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46919 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.49112 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45763 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.89504 |
289 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.91541 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04610 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.01293E-002 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 206943.01368 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.91854E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.89504 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 58946.47834 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.28946E-003 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1211.67370 |
301 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.89504 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.91854E-003 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.04574E-005 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.28946E-003 |
305 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 83.19850 |
306 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 20.30600 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.11141 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04670 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.03161E-002 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2003320.56527 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.72947E-002 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 83.19850 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 540378.14748 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18208E-002 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 11150.58027 |
318 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 83.19850 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.72947E-002 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.31125E-006 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.18208E-002 |
322 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.11723 |
323 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.80273 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04594 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.00786E-002 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 209428.48896 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.98963E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.11723 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 50990.30199 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11541E-003 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1082.14108 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.11723 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.98963E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.95025E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.11541E-003 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.80083 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.77357 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02387 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.02993E-002 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 107570.32475 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.07650E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.80083 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 247784.22786 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.18750E-003 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3856.29059 |
353 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 4.80083 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.07650E-003 |
355 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.54783E-004 |
356 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.18750E-003 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.41350 |
358 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.41350 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 492768.69228 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 356200.11830 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.20679E-002 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.41350 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.41350 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.41350 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.41350 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 492768.69228 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 492768.69228 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 20749.82071 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
371 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.41350 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.41350 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 492768.69228 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.20679E-002 |
375 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 20749.82071 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.97946E-004 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46919 |
381 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46919 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9443.77973 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6832.11393 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31278E-004 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46919 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46919 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46919 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46919 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9443.77973 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9443.77973 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.55576 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
394 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46919 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46919 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9443.77973 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31278E-004 |
398 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 958.55576 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.49112 |
400 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.49112 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 90558.88213 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 65452.24170 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.21778E-003 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.49112 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.49112 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.49112 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.49112 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 90558.88213 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 90558.88213 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 9585.55755 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
413 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.49112 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.49112 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 90558.88213 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.21778E-003 |
417 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 9585.55755 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45763 |
419 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45763 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9223.37486 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6667.93766 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25880E-004 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45763 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45763 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45763 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45763 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9223.37486 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9223.37486 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.55576 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
432 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45763 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45763 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9223.37486 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25880E-004 |
436 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 958.55576 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 7.22794E-002 |
438 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 11684.17314 |
439 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 7.22794E-002 |
440 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 8.67353 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 7.22794E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 7.22794E-002 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 303392.84426 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
445 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.66382E-002 |
446 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 5.59658 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.66382E-002 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 13906.31117 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
450 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2132028.76886 |
451 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2132028.77000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.66382E-002 |
453 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 7.22794E-002 |
454 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 8.67353 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.61397E-002 |
456 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4044.67355 |
457 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.61397E-002 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4044.67355 |
459 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.22794E-002 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.64542E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1274626.28420 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1274625.79500 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 6.41838E-002 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.22794E-002 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.64542E-002 |
466 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1274626.28420 |
467 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1274625.79500 |
468 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 6.41838E-002 |
469 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.47428E-002 |
470 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.76914 |
471 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.47428E-002 |
472 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3722.92510 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.47428E-002 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 146385.18789 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 74104.30954 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 73192.59395 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 44462.58572 |
479 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 607277.47047 |
480 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 595320.93000 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.47428E-002 |
482 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
483 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
484 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
486 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.12837 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 15.40411 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.12837 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 31466.30729 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 46.86606 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1525721.24833 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.37321 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 190715.15604 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 46.86606 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1525721.24833 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.37321 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 190715.15604 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.60975E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.60975E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 22644.02 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 578641.98 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 115136.74 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17272.85 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11897.13 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 19987.42 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8885.97 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 311251.06 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 204179.24 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 307562.64 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 196641.58 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 39311.68 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 25695.38 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 38925.48 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 25158.46 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 59263.12 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 546268.05 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 53590.35 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 139463.85 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 227966.27 | 160144.36 | 67821.91 | 0.70 | 34819.72 | 353.16 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2163988.73 | 1511394.47 | 652594.25 | 0.70 | 328450.19 | 3331.32 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 232422.05 | 163623.34 | 68798.71 | 0.70 | 35617.59 | 361.25 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 121738.17 | 85932.24 | 35805.93 | 0.71 | 19083.71 | 193.56 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 8.97 | 30.62 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 8.97 | 30.62 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.8254939171E-003 | 1.5870300181E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.2388328397E-003 | 6.5954521386E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.1191521878E-002 | 1.7235281776E-002 | Pass | Pass | 0.4859404786 | 0.4916890658 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.2593747860E-002 | 8.0360412106E-002 | Pass | Pass | 3.2129667168 | 22.4966641436 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.9914869585E-002 | 2.2763442304E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.4752766379E-002 | 9.2710035672E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1083500262 | 0.1349586724 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.7628153215E-002 | 5.0647443494E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4333257922 | 0.4171724192 | Pass | Pass | 0.9405263220 | 1.6050332002 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3495194677 | 0.4180667586 | Pass | Pass | 1.0443098105 | 1.5521740674 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2965497306 | 0.3189728995 | Pass | Pass | 0.9434063811 | 1.9283602622 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3290008465 | 0.3693417620 | Pass | Pass | 17.0641937677 | 165.6953320431 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6026692979 | 0.5613243603 | Pass | Pass | 0.6823612062 | 0.6094863580 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5080273597 | 0.5876952970 | Pass | Pass | 5.8205761479 | 59.2978686395 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4243609656 | 0.4895318709 | Pass | Pass | 7.6561842073 | 82.5331591972 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5095823916 | 0.5465411087 | Pass | Pass | 2.6886527790 | 20.7956866251 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.7788472152E-003 | 4.5498898291E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.4612302039E-002 | 3.2774553669E-002 | Pass | Pass | 0.4865224384 | 0.4792596575 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1290949908 | 9.2938246548E-002 | Pass | Pass | 0.5067091116 | 0.4944104354 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.7629882945E-007 | 4.8070068909E-007 | Pass | Pass | 1.3223275807E-002 | 9.5628088886E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.2487210462E-002 | 1.0467043223E-002 | Pass | Pass | 4.6888974872E-003 | 5.3176726543E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.7504053667E-002 | 1.4203934492E-002 | Pass | Pass | 6.4009964032E-003 | 7.1861086912E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1764043454E-005 | 7.6268482457E-006 | Pass | Pass | 8.4136617748E-005 | 1.1065336161E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6737.92 | 107.09 | 0.00 | 22349.03 | 13444.19 | 42638.22 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 1390.74 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.062 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 116.04 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 1042.11 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.34 | 0.0000 | Y | 7.60 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.29 | 0.0000 | Y | 4.88 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.09 | 0.0000 | Y | 7.51 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.11 | 0.0000 | Y | 4.84 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.31 | 0.0000 | Y | 75.84 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.26 | 0.0000 | Y | 48.76 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.07 | 0.0000 | Y | 75.03 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.09 | 0.0000 | Y | 48.39 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.31 | 0.0000 | Y | 7.58 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.26 | 0.0000 | Y | 4.88 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.07 | 0.0000 | Y | 7.50 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.09 | 0.0000 | Y | 4.84 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.66 | 0.0000 | Y | 32.85 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 16.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 540.99 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 42.43 | 42.43 | 103.18 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.64 | 63.04 | 10.88 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.64 | 46.90 | 151.57 | |
Exterior Lighting Total | 31088.59 | 265.63 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2519478.20 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2132028.77 | 0.94 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1274625.79 | 5.91 | 1267265.47 | 5.88 | 8.97 | 30.62 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1274625.79 | 5.91 | 1267265.47 | 5.88 | 8.97 | 30.62 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 610060.27 | |||||
CENTRAL BOILER | Boiler:HotWater | 595320.93 | 0.94 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1525721.25 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1525721.25 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 206943.01 | 227966.27 | 160144.36 | 67821.91 | 0.70 | - | 34819.72 | 353.16 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2003320.57 | 2163988.73 | 1511394.47 | 652594.25 | 0.70 | - | 328450.19 | 3331.32 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 209428.49 | 232422.05 | 163623.34 | 68798.71 | 0.70 | - | 35617.59 | 361.25 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 107570.32 | 121738.17 | 85932.24 | 35805.93 | 0.71 | - | 19083.71 | 193.56 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 492768.69 | 356200.12 | 136568.57 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9443.78 | 6832.11 | 2611.67 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 90558.88 | 65452.24 | 25106.64 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9223.37 | 6667.94 | 2555.44 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16266.37 | 22644.02 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 415508.39 | 578641.98 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 82739.32 | 115136.74 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12412.54 | 17272.85 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 8549.46 | 11897.13 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14363.26 | 19987.42 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 6385.61 | 8885.97 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 223669.03 | 311251.06 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 146725.82 | 204179.24 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 221018.50 | 307562.64 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 141309.19 | 196641.58 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 28249.85 | 39311.68 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 18465.01 | 25695.38 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 27972.32 | 38925.48 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 18079.17 | 25158.46 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 58946.48 | 59263.12 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 540378.15 | 546268.05 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 50990.30 | 53590.35 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 139463.85 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 492768.69 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9443.78 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 90558.88 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9223.37 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 20749.82 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 958.56 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 9585.56 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 958.56 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.90 | 19221.72 | 2160.95 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 83.20 | 179787.53 | 2160.95 | 1.00 | 1.08 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.12 | 19701.86 | 2160.95 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.80 | 10509.06 | 2189.01 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.41 | 40263.89 | 1649.25 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 525.54 | 1120.11 | 1.00 | 1.64 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.49 | 5030.54 | 1120.11 | 1.00 | 1.16 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 512.60 | 1120.11 | 1.00 | 1.65 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.072279 | 11684.17 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.046638 | 13906.31 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.036140 | 4044.67 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.036140 | 4044.67 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014743 | 3722.93 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.128368 | 31466.31 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 66689.06 | 66689.06 | 23.99 | 4.801 | 4.801 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00903 | 26.62 | 0.01411 | 1.200 | 0.00 |
CORE_BOTTOM | 72654.06 | 72654.06 | 29.11 | 5.231 | 5.231 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 26.62 | 0.01411 | 1.078 | 0.00 |
CORE_MID | 681229.00 | 681229.00 | 272.92 | 49.030 | 49.030 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 26.62 | 0.01411 | 10.778 | 0.00 |
CORE_TOP | 69528.72 | 69528.72 | 27.85 | 5.005 | 5.005 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 26.62 | 0.01411 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12749.36 | 12749.36 | 40.68 | 0.927 | 0.927 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00888 | 32.10 | 0.01412 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 16153.04 | 16153.04 | 79.98 | 1.174 | 1.174 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00870 | 27.80 | 0.01411 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 18551.83 | 18551.83 | 59.19 | 1.349 | 1.349 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24.00 | 24.00 | 0.00876 | 31.73 | 0.01412 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19845.74 | 19845.74 | 98.26 | 1.443 | 1.443 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00866 | 31.36 | 0.01412 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 119997.99 | 119997.99 | 382.88 | 8.723 | 8.723 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00901 | 32.10 | 0.01412 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 172428.27 | 172428.27 | 853.71 | 12.534 | 12.534 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00874 | 28.24 | 0.01411 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 182562.75 | 182562.75 | 582.49 | 13.271 | 13.271 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00884 | 31.79 | 0.01412 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 179339.47 | 179339.47 | 887.93 | 13.037 | 13.037 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00873 | 31.26 | 0.01412 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13716.31 | 13716.31 | 43.76 | 0.997 | 0.997 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00899 | 32.10 | 0.01412 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 17554.80 | 17554.80 | 86.92 | 1.276 | 1.276 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00876 | 28.24 | 0.01411 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 19867.52 | 19867.52 | 63.39 | 1.444 | 1.444 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00884 | 31.85 | 0.01412 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 19069.45 | 19069.45 | 94.41 | 1.386 | 1.386 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00873 | 31.26 | 0.01412 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8183.54 | 8183.54 | 226.05 | 0.469 | 0.469 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 29.58 | 0.01412 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78333.00 | 78333.00 | 2163.73 | 4.491 | 4.491 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 29.58 | 0.01412 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7981.95 | 7981.95 | 220.48 | 0.458 | 0.458 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 27.00 | 27.00 | 0.00859 | 29.77 | 0.01412 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370277.85 | 425819.53 | 543.36 | 21.229 | 24.413 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 25.37 | 0.01411 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | 21.00 | 23.91 | 0.00150 | -10.70 | 0.00150 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 17.60 | 21.51 | 0.00150 | -10.70 | 0.00150 | 1.078 | 0.00 |
CORE_MID | 252674.33 | 252674.33 | 101.23 | 10.650 | 10.778 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 10.778 | 0.00 |
CORE_TOP | 57955.47 | 57955.47 | 23.22 | 2.463 | 2.463 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 8695.55 | 8695.55 | 27.74 | 0.370 | 0.370 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00732 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 5988.37 | 5988.37 | 29.65 | 0.255 | 0.255 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00739 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 10058.97 | 10058.97 | 32.09 | 0.428 | 0.428 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 4476.62 | 4476.62 | 22.16 | 0.190 | 0.190 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00688 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 156568.48 | 156568.48 | 499.56 | 6.675 | 6.675 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 102707.10 | 102707.10 | 508.51 | 4.379 | 4.379 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 154715.49 | 154715.49 | 493.64 | 6.596 | 6.596 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 98920.09 | 98920.09 | 489.76 | 4.217 | 4.217 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 19771.34 | 19771.34 | 63.08 | 0.843 | 0.843 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12923.15 | 12923.15 | 63.98 | 0.551 | 0.551 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 19577.30 | 19577.30 | 62.46 | 0.835 | 0.835 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 12653.36 | 12653.36 | 62.65 | 0.540 | 0.540 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -10.70 | 0.00150 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | 18.00 | 25.82 | 0.00838 | -10.70 | 0.00150 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 23.01 | 0.00244 | -10.70 | 0.00150 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 21.20 | 0.00199 | -10.70 | 0.00150 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 18.00 | 27.00 | 0.00850 | -10.70 | 0.00150 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.90 | 8.90 | 2.32 | 2.32 | 8.8950 | 2.3208 | 8.8950 | 0.2609 | 0.3000 |
VAV_MID WITH REHEAT | 83.20 | 83.20 | 32.65 | 32.65 | 83.1985 | 32.6455 | 83.1985 | 0.3924 | 0.3000 |
VAV_TOP WITH REHEAT | 9.12 | 9.12 | 5.23 | 5.23 | 9.1172 | 5.2323 | 9.1172 | 0.5739 | 0.3000 |
CAV_BAS | 4.80 | 4.80 | 1.20 | 1.20 | 4.8008 | 1.2002 | 4.8008 | 0.2500 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.41 | 24.41 | 0.34 | 0.34 | 24.4135 | 24.4132 | 24.4135 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4692 | 0.4692 | 0.4692 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.49 | 4.49 | 0.16 | 0.16 | 4.4911 | 4.4911 | 4.4911 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4576 | 0.4576 | 0.4576 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16266.373 | 16266.373 | 1.616290 | 0.00035583 | 453.996 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 16266.37 | 16266.37 | 1.616290 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 16294.29 | 16294.29 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 415508.390 | 415508.390 | 16.179815 | 0.00908926 | 14166.365 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 415508.39 | 415508.39 | 16.179815 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 252674.33 | 0.00 | 416501.73 | 416501.73 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 82739.318 | 82739.318 | 2.462619 | 0.00180992 | 3220.758 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 82739.32 | 82739.32 | 2.462619 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 57955.47 | 0.00 | 82915.47 | 82915.47 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 12412.544 | 12412.544 | 0.369889 | 0.00027152 | 482.799 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12412.54 | 12412.54 | 0.369889 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00731577 | 47.3289 | 8695.55 | 0.00 | 12438.97 | 12438.97 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8549.459 | 8549.459 | 0.254825 | 0.00018702 | 332.494 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8549.46 | 8549.46 | 0.254825 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00738645 | 47.7805 | 5988.37 | 0.00 | 8567.66 | 8567.66 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 14363.260 | 14363.260 | 0.428175 | 0.00031420 | 558.542 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14363.26 | 14363.26 | 0.428175 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00749374 | 48.4655 | 10058.97 | 0.00 | 14393.85 | 14393.85 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6385.607 | 6385.607 | 0.190133 | 0.00013969 | 248.506 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6385.61 | 6385.61 | 0.190133 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00688253 | 44.5586 | 4476.62 | 0.00 | 6399.20 | 6399.20 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 223669.030 | 223669.030 | 6.675178 | 0.00489277 | 8691.461 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 223669.03 | 223669.03 | 6.675178 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00750265 | 48.5239 | 156568.48 | 0.00 | 224145.41 | 224145.41 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 146725.820 | 146725.820 | 4.379058 | 0.00320963 | 5701.412 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 146725.82 | 146725.82 | 4.379058 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00749715 | 48.4888 | 102707.10 | 0.00 | 147038.32 | 147038.32 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 221018.496 | 221018.496 | 6.595926 | 0.00483479 | 8588.590 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 221018.50 | 221018.50 | 6.595926 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00749587 | 48.4806 | 154715.49 | 0.00 | 221489.23 | 221489.23 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 141309.188 | 141309.188 | 4.217137 | 0.00309114 | 5491.153 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 141309.19 | 141309.19 | 4.217137 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00747478 | 48.3460 | 98920.09 | 0.00 | 141610.15 | 141610.15 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 28249.853 | 28249.853 | 0.843439 | 0.00061797 | 1097.455 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28249.85 | 28249.85 | 0.843439 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00752509 | 48.6681 | 19771.34 | 0.00 | 28310.02 | 28310.02 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 18465.008 | 18465.008 | 0.551314 | 0.00040392 | 717.319 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18465.01 | 18465.01 | 0.551314 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00751665 | 48.6143 | 12923.15 | 0.00 | 18504.34 | 18504.34 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 27972.321 | 27972.321 | 0.835140 | 0.00061190 | 1086.683 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27972.32 | 27972.32 | 0.835140 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00752050 | 48.6388 | 19577.30 | 0.00 | 28031.90 | 28031.90 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 18079.173 | 18079.173 | 0.539782 | 0.00039548 | 702.340 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18079.17 | 18079.17 | 0.539782 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00750643 | 48.5491 | 12653.36 | 0.00 | 18117.68 | 18117.68 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 206943.014 | -999.000 | 8.895044 | 0.00591854 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 206943.01 | 161159.16 | 8.895044 | 25.92 | 18.39 | 0.01012933 | 11.05 | 11.05 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 22.8273 | 24.00 | 0.00889265 | 47.8212 | 118063.76 | 0.00 | 207211.06 | 158295.88 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 58946.478 | 58946.478 | 2.668513 | 0.00128946 | 1211.674 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 58946.48 | 58946.48 | 2.668513 | -5.46 | -5.70 | 0.00224935 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 76.0911 | 21.15 | 0.00574251 | 36.8931 | 29219.51 | 0.00 | 51607.80 | 51607.80 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2003320.565 | -999.000 | 83.198500 | 0.05729471 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2003320.57 | 1526428.16 | 83.198500 | 26.11 | 18.60 | 0.01031609 | 11.05 | 11.05 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 24.4067 | 24.00 | 0.00897408 | 48.2535 | 1071061.19 | 0.00 | 2006390.89 | 1501897.84 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 540378.147 | 540378.147 | 24.959550 | 0.01182079 | 11150.580 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 540378.15 | 540378.15 | 24.959550 | -5.10 | -5.10 | 0.00260238 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 81.3556 | 18.10 | 0.00723568 | 56.0503 | 265069.47 | 0.00 | 475749.54 | 475749.54 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 209428.489 | -999.000 | 9.117233 | 0.00598963 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 209428.49 | 163949.07 | 9.117233 | 25.80 | 18.31 | 0.01007857 | 11.05 | 11.05 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 22.2710 | 24.00 | 0.00892072 | 47.9707 | 125421.93 | 0.00 | 209706.61 | 160964.28 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 50990.302 | 50990.302 | 2.735170 | 0.00111541 | 1082.141 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50990.30 | 50990.30 | 2.735170 | -2.61 | -2.61 | 0.00304428 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 74.2367 | 17.54 | 0.00732412 | 58.7897 | 36336.29 | 0.00 | 46680.20 | 46680.20 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 107570.325 | -999.000 | 4.800826 | 0.00307650 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 107570.32 | 80238.85 | 4.800826 | 24.77 | 18.14 | 0.01029935 | 11.02 | 11.02 | 0.00850000 | 27.09 | 0.01411064 | 21.71 | 24.9990 | 24.00 | 0.00902573 | 48.5266 | 65917.20 | 0.00 | 107733.59 | 78880.63 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.039805 | 0.00218750 | 3856.291 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.039805 | -2.67 | -5.26 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 39.4814 | 23.99 | 0.00150390 | 8.1882 | 0.00 | 0.00 | 99932.15 | 99932.15 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 492768.692 | 356200.118 | 24.413499 | 0.01206787 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 461044.59 | 452995.24 | -999.0 | 28.46 | 18.02 | 0.00861980 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | -999.0000 | 27.00 | 0.00854243 | 38.4650 | 369906.75 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9443.780 | 6832.114 | 0.469189 | 0.00023128 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8830.97 | 8479.23 | -999.0 | 28.03 | 18.00 | 0.00877263 | 12.80 | 12.09 | 0.00850000 | 29.58 | 0.01411511 | 22.43 | -999.0000 | 27.00 | 0.00858849 | 38.6672 | 8183.54 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90558.882 | 65452.242 | 4.491121 | 0.00221778 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 84707.74 | 81192.14 | -999.0 | 28.03 | 18.01 | 0.00878464 | 12.80 | 12.09 | 0.00850000 | 29.58 | 0.01411511 | 22.43 | -999.0000 | 27.00 | 0.00859241 | 38.6848 | 78333.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9223.375 | 6667.938 | 0.457633 | 0.00022588 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 8626.80 | 8275.26 | -999.0 | 28.04 | 18.01 | 0.00877934 | 12.80 | 12.09 | 0.00850000 | 29.77 | 0.01411544 | 22.48 | -999.0000 | 27.00 | 0.00859061 | 38.6767 | 7981.95 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 492768.692 | 492768.692 | 24.413499 | 0.01206787 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 492768.69 | 492768.69 | 24.413499 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.3861 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9443.780 | 9443.780 | 0.469189 | 0.00023128 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9443.78 | 9443.78 | 0.469189 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3318 | 26.33 | 0.00838395 | 39.2731 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90558.882 | 90558.882 | 4.491121 | 0.00221778 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 90558.88 | 90558.88 | 4.491121 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4807 | 24.14 | 0.00243655 | 13.1258 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9223.375 | 9223.375 | 0.457633 | 0.00022588 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9223.37 | 9223.37 | 0.457633 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4159 | 23.07 | 0.00198803 | 11.4327 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 20749.821 | 20749.821 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 20749.82 | 20749.82 | 24.413499 | -0.15 | -0.15 | 0.00840303 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.3861 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.56 | 958.56 | 0.469189 | -0.36 | -0.36 | 0.00815472 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3318 | 26.33 | 0.00838395 | 39.2731 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 9585.558 | 9585.558 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9585.56 | 9585.56 | 4.491121 | -0.37 | -2.34 | 0.00240409 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4807 | 24.14 | 0.00243655 | 13.1258 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.56 | 958.56 | 0.457633 | -0.37 | -3.04 | 0.00197149 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4159 | 23.07 | 0.00198803 | 11.4327 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16266.373 | 16266.373 | 1.616290 | 0.00035583 | 453.996 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 0.7479 | 0.762953 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 16266.37 | 16266.37 | 1.0000 | 1.94535796 | 1.616290 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.35579107 | 60.00 | 48.89 | 11.11 | 0.000 | 16266.37 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 16294.29 | 16294.29 | 1.94535796 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 415508.390 | 415508.390 | 16.179815 | 0.00908926 | 14166.365 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 19.1044 | 19.488873 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 415508.39 | 415508.39 | 1.0000 | 19.47394399 | 16.179815 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 9.08833037 | 60.00 | 48.89 | 11.11 | 0.000 | 415508.39 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.85 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 252674.33 | 0.00 | 416501.73 | 416501.73 | 19.47394399 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.77 | 19.27 | 0.00800000 | 54447.5 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 82739.318 | 82739.318 | 2.462619 | 0.00180992 | 3220.758 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 3.8042 | 3.880779 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 82739.32 | 82739.32 | 1.0000 | 2.96399540 | 2.462619 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 1.80974024 | 60.00 | 48.89 | 11.11 | 0.000 | 82739.32 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 57955.47 | 0.00 | 82915.47 | 82915.47 | 2.96399540 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61034.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12412.544 | 12412.544 | 0.369889 | 0.00027152 | 482.799 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 0.5707 | 0.582194 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12412.54 | 12412.54 | 1.0000 | 0.44519633 | 0.369889 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.27149704 | 60.00 | 48.89 | 11.11 | 0.000 | 12412.54 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00731577 | 21.00 | 0.00731577 | 47.3289 | 8695.55 | 0.00 | 12438.97 | 12438.97 | 0.44519633 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8549.459 | 8549.459 | 0.254825 | 0.00018702 | 332.494 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 0.3931 | 0.401001 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8549.46 | 8549.46 | 1.0000 | 0.30670559 | 0.254825 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.18700058 | 60.00 | 48.89 | 11.11 | 0.000 | 8549.46 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00738645 | 21.00 | 0.00738645 | 47.7805 | 5988.37 | 0.00 | 8567.66 | 8567.66 | 0.30670559 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60994.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14363.260 | 14363.260 | 0.428175 | 0.00031420 | 558.542 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 0.6604 | 0.673690 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14363.26 | 14363.26 | 1.0000 | 0.51534895 | 0.428175 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.31416465 | 60.00 | 48.89 | 11.11 | 0.000 | 14363.26 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00749374 | 21.00 | 0.00749374 | 48.4655 | 10058.97 | 0.00 | 14393.85 | 14393.85 | 0.51534895 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60990.1 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6385.607 | 6385.607 | 0.190133 | 0.00013969 | 248.506 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 0.2936 | 0.299509 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6385.61 | 6385.61 | 1.0000 | 0.22884351 | 0.190133 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.13967109 | 60.00 | 48.89 | 11.11 | 0.000 | 6385.61 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00688253 | 21.00 | 0.00688253 | 44.5586 | 4476.62 | 0.00 | 6399.20 | 6399.20 | 0.22884351 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61023.1 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 223669.030 | 223669.030 | 6.675178 | 0.00489277 | 8691.461 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 10.2839 | 10.490901 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 223669.03 | 223669.03 | 1.0000 | 8.03421065 | 6.675178 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 4.89226713 | 60.00 | 48.89 | 11.11 | 0.000 | 223669.03 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00750265 | 21.00 | 0.00750265 | 48.5239 | 156568.48 | 0.00 | 224145.41 | 224145.41 | 8.03421065 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60958.7 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 146725.820 | 146725.820 | 4.379058 | 0.00320963 | 5701.412 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 6.7462 | 6.881981 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 146725.82 | 146725.82 | 1.0000 | 5.27061176 | 4.379058 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 3.20930398 | 60.00 | 48.89 | 11.11 | 0.000 | 146725.82 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00749715 | 21.00 | 0.00749715 | 48.4888 | 102707.10 | 0.00 | 147038.32 | 147038.32 | 5.27061176 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60957.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 221018.496 | 221018.496 | 6.595926 | 0.00483479 | 8588.590 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 10.1621 | 10.366581 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 221018.50 | 221018.50 | 1.0000 | 7.93882356 | 6.595926 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 4.83429255 | 60.00 | 48.89 | 11.11 | 0.000 | 221018.50 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00749587 | 21.00 | 0.00749587 | 48.4806 | 154715.49 | 0.00 | 221489.23 | 221489.23 | 7.93882356 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60959.3 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 141309.188 | 141309.188 | 4.217137 | 0.00309114 | 5491.153 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 6.4972 | 6.627921 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 141309.19 | 141309.19 | 1.0000 | 5.07572531 | 4.217137 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 3.09082709 | 60.00 | 48.89 | 11.11 | 0.000 | 141309.19 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00747478 | 21.00 | 0.00747478 | 48.3460 | 98920.09 | 0.00 | 141610.15 | 141610.15 | 5.07572531 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60959.3 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 28249.853 | 28249.853 | 0.843439 | 0.00061797 | 1097.455 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 1.2989 | 1.325022 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28249.85 | 28249.85 | 1.0000 | 1.01515879 | 0.843439 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.61790329 | 60.00 | 48.89 | 11.11 | 0.000 | 28249.85 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00752509 | 21.00 | 0.00752509 | 48.6681 | 19771.34 | 0.00 | 28310.02 | 28310.02 | 1.01515879 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60947.1 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18465.008 | 18465.008 | 0.551314 | 0.00040392 | 717.319 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 0.8490 | 0.866077 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18465.01 | 18465.01 | 1.0000 | 0.66355855 | 0.551314 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.40388137 | 60.00 | 48.89 | 11.11 | 0.000 | 18465.01 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00751665 | 21.00 | 0.00751665 | 48.6143 | 12923.15 | 0.00 | 18504.34 | 18504.34 | 0.66355855 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60946.3 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27972.321 | 27972.321 | 0.835140 | 0.00061190 | 1086.683 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 1.2861 | 1.312005 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27972.32 | 27972.32 | 1.0000 | 1.00517081 | 0.835140 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.61183287 | 60.00 | 48.89 | 11.11 | 0.000 | 27972.32 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00752050 | 21.00 | 0.00752050 | 48.6388 | 19577.30 | 0.00 | 28031.90 | 28031.90 | 1.00517081 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60947.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18079.173 | 18079.173 | 0.539782 | 0.00039548 | 702.340 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 0.8313 | 0.847980 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18079.17 | 18079.17 | 1.0000 | 0.64967859 | 0.539782 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.39544207 | 60.00 | 48.89 | 11.11 | 0.000 | 18079.17 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00750643 | 21.00 | 0.00750643 | 48.5491 | 12653.36 | 0.00 | 18117.68 | 18117.68 | 0.64967859 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60947.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 206943.014 | -999.000 | 8.895044 | 0.00591854 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6699 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.895044 | 10.70603077 | 4197.9300 | 999.8980 | 72.27201127 | 15.00 | 6.67 | 8.33 | 2527262.39 | 8.1884 | 8.188426 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 206943.01 | 161159.16 | 1.0000 | 10.70603077 | 8.895044 | 25.92 | 18.39 | 0.01012933 | 51861.7 | 11.05 | 11.05 | 0.00850000 | 32532.1 | 5.91794024 | 6.67 | 15.00 | 8.33 | 19221.717 | 187721.30 | 32.10 | 0.01411964 | 23.13 | 2.03050000 | 22.8273 | 24.00 | 0.00889265 | 24.00 | 0.00889265 | 47.8212 | 118063.76 | 0.00 | 207211.06 | 158295.88 | 10.70603077 | 25.92 | 18.39 | 0.01012933 | 51861.7 | 11.47 | 11.36 | 0.00831789 | 32507.1 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 58946.478 | 58946.478 | 2.668513 | 0.00128946 | 1211.674 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.895044 | 10.70603077 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 2.7103 | 2.764807 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 58946.48 | 58946.48 | 1.0000 | 3.21180923 | 2.668513 | -5.46 | -5.70 | 0.00224935 | 111.9 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 1.28932431 | 60.00 | 48.89 | 11.11 | 0.000 | 58946.48 | -10.70 | 0.00150390 | -10.70 | 2.03050000 | 76.0911 | 11.20 | 0.00462178 | 21.15 | 0.00574251 | 36.8931 | 29219.51 | 0.00 | 51607.80 | 51607.80 | 3.21180923 | 2.80 | -0.80 | 0.00224935 | 8450.7 | 18.72 | 7.95 | 0.00224935 | 24518.9 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2003320.565 | -999.000 | 83.198500 | 0.05729471 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0171 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 83.198500 | 100.13729720 | 4197.9300 | 999.8980 | 72.27201127 | 15.00 | 6.67 | 8.33 | 2527262.39 | 79.2684 | 79.268404 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2003320.57 | 1526428.16 | 1.0000 | 100.13729720 | 83.198500 | 26.11 | 18.60 | 0.01031609 | 52538.4 | 11.05 | 11.05 | 0.00850000 | 32532.7 | 57.28886992 | 6.67 | 15.00 | 8.33 | 179787.528 | 1823533.04 | 32.10 | 0.01411964 | 23.13 | 20.30600000 | 24.4067 | 24.00 | 0.00897408 | 24.00 | 0.00897408 | 48.2535 | 1071061.19 | 0.00 | 2006390.89 | 1501897.84 | 100.13729720 | 26.11 | 18.61 | 0.01031609 | 52538.4 | 11.46 | 11.36 | 0.00831866 | 32502.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 540378.147 | 540378.147 | 24.959550 | 0.01182079 | 11150.580 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 83.198500 | 100.13729720 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 24.8457 | 25.345725 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 540378.15 | 540378.15 | 1.0000 | 30.04118916 | 24.959550 | -5.10 | -5.10 | 0.00260238 | 1358.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 11.81958115 | 60.00 | 48.89 | 11.11 | 0.000 | 540378.15 | -10.70 | 0.00150390 | -10.70 | 20.30600000 | 81.3556 | 19.33 | 0.00739569 | 18.10 | 0.00723568 | 56.0503 | 265069.47 | 0.00 | 475749.54 | 475749.54 | 30.04118916 | 2.80 | -0.26 | 0.00260238 | 9335.5 | 18.48 | 8.25 | 0.00260238 | 25172.1 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 209428.489 | -999.000 | 9.117233 | 0.00598963 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5756 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.117233 | 10.97345635 | 4197.9300 | 999.8980 | 72.27201127 | 15.00 | 6.67 | 8.33 | 2527262.39 | 8.2868 | 8.286773 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 209428.49 | 163949.07 | 1.0000 | 10.97345635 | 9.117233 | 25.80 | 18.31 | 0.01007857 | 51616.9 | 11.05 | 11.05 | 0.00850000 | 32531.9 | 5.98901727 | 6.67 | 15.00 | 8.33 | 19701.856 | 189726.63 | 32.10 | 0.01411964 | 23.13 | 2.03050000 | 22.2710 | 24.00 | 0.00892072 | 24.00 | 0.00892072 | 47.9707 | 125421.93 | 0.00 | 209706.61 | 160964.28 | 10.97345635 | 25.80 | 18.32 | 0.01007857 | 51616.9 | 11.47 | 11.36 | 0.00831752 | 32506.6 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 50990.302 | 50990.302 | 2.735170 | 0.00111541 | 1082.141 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.117233 | 10.97345635 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 2.3444 | 2.391633 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 50990.30 | 50990.30 | 1.0000 | 3.29203691 | 2.735170 | -2.61 | -2.61 | 0.00304428 | 4972.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 1.11530049 | 60.00 | 48.89 | 11.11 | 0.000 | 50990.30 | -10.70 | 0.00150390 | -10.70 | 2.03050000 | 74.2367 | 20.69 | 0.00748288 | 17.54 | 0.00732412 | 58.7897 | 36336.29 | 0.00 | 46680.20 | 46680.20 | 3.29203691 | 2.80 | 0.59 | 0.00304428 | 10443.0 | 16.83 | 7.99 | 0.00304428 | 24622.7 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 107570.325 | -999.000 | 4.800826 | 0.00307650 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9860 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:VariableVolume | 4.800826 | 5.77824982 | 4197.9300 | 999.8980 | 72.27201127 | 15.00 | 6.67 | 8.33 | 2527262.39 | 4.2564 | 4.256397 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 107570.32 | 80238.85 | 1.0000 | 5.77824982 | 4.800826 | 24.77 | 18.14 | 0.01029935 | 51125.8 | 11.02 | 11.02 | 0.00850000 | 32509.4 | 3.07618384 | 6.67 | 15.00 | 8.33 | 10509.060 | 97061.26 | 27.09 | 0.01411064 | 21.71 | 1.20015641 | 24.9990 | 24.00 | 0.00902573 | 24.00 | 0.00902573 | 48.5266 | 65917.20 | 0.00 | 107733.59 | 78880.63 | 5.77824982 | 24.77 | 18.15 | 0.01029935 | 51125.8 | 11.44 | 11.35 | 0.00831958 | 32481.2 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.039805 | 0.00218750 | 3856.291 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:VariableVolume | 4.800826 | 5.77824982 | 4197.9300 | 999.8980 | 46.63343098 | 48.89 | 60.00 | 11.11 | 2174936.69 | 4.5978 | 4.690368 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.039805 | -2.67 | -5.26 | 0.00150390 | 1065.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 2.18727963 | 60.00 | 48.89 | 11.11 | 0.000 | 100000.00 | -10.70 | 0.00150390 | -10.70 | 1.20015641 | 39.4814 | 0.00 | 0.00150390 | 23.99 | 0.00150390 | 8.1882 | 0.00 | 0.00 | 99932.15 | 99932.15 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 39.98 | 14.58 | 0.00000000 | 40200.8 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 492768.692 | 356200.118 | 24.413499 | 0.01206787 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8638 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 461044.59 | 452995.24 | 0.9356 | -999.0 | -999.0 | 28.46 | 18.02 | 0.00861980 | 50613.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 461044.59 | 32.10 | 0.01411964 | 23.13 | 0.33839277 | -999.0000 | 27.00 | 0.00854243 | 27.00 | 0.00854243 | 38.4650 | 369906.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9443.780 | 6832.114 | 0.469189 | 0.00023128 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1479 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8830.97 | 8479.23 | 0.9351 | -999.0 | -999.0 | 28.03 | 18.00 | 0.00877263 | 50563.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8830.97 | 29.58 | 0.01411511 | 22.43 | 0.01563234 | -999.0000 | 27.00 | 0.00858849 | 27.00 | 0.00858849 | 38.6672 | 8183.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 90558.882 | 65452.242 | 4.491121 | 0.00221778 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1702 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 84707.74 | 81192.14 | 0.9354 | -999.0 | -999.0 | 28.03 | 18.01 | 0.00878464 | 50598.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84707.74 | 29.58 | 0.01411511 | 22.43 | 0.15632344 | -999.0000 | 27.00 | 0.00859241 | 27.00 | 0.00859241 | 38.6848 | 78333.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9223.375 | 6667.938 | 0.457633 | 0.00022588 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1603 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 8626.80 | 8275.26 | 0.9353 | -999.0 | -999.0 | 28.04 | 18.01 | 0.00877934 | 50589.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8626.80 | 29.77 | 0.01411544 | 22.48 | 0.01563234 | -999.0000 | 27.00 | 0.00859061 | 27.00 | 0.00859061 | 38.6767 | 7981.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 492768.692 | 492768.692 | 24.413499 | 0.01206787 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 492768.69 | 492768.69 | 1.0000 | 29.38396512 | 24.413499 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 492768.69 | -10.70 | 0.00150390 | -10.70 | 0.33839277 | 1.3861 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9443.780 | 9443.780 | 0.469189 | 0.00023128 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9443.78 | 9443.78 | 1.0000 | 0.56471375 | 0.469189 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9443.78 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.3318 | 0.00 | 0.00838395 | 26.33 | 0.00838395 | 39.2731 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 90558.882 | 90558.882 | 4.491121 | 0.00221778 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 90558.88 | 90558.88 | 1.0000 | 5.40549033 | 4.491121 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90558.88 | -10.70 | 0.00150390 | -10.70 | 0.15632344 | 3.4807 | 0.00 | 0.00243655 | 24.14 | 0.00243655 | 13.1258 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9223.375 | 9223.375 | 0.457633 | 0.00022588 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9223.37 | 9223.37 | 1.0000 | 0.55080504 | 0.457633 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9223.37 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.4159 | 0.00 | 0.00198803 | 23.07 | 0.00198803 | 11.4327 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20749.821 | 20749.821 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.413499 | 29.38396512 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 20749.82 | 20749.82 | 1.0000 | 29.38396512 | 24.413499 | -0.15 | -0.15 | 0.00840303 | 20864.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20749.82 | -10.70 | 0.00150390 | -10.70 | 0.33839277 | 1.3861 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.469189 | 0.56471375 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 958.56 | 958.56 | 1.0000 | 0.56471375 | 0.469189 | -0.36 | -0.36 | 0.00815472 | 20030.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.56 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.3318 | 0.00 | 0.00838395 | 26.33 | 0.00838395 | 39.2731 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9585.558 | 9585.558 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.491121 | 5.40549033 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9585.56 | 9585.56 | 1.0000 | 5.40549033 | 4.491121 | -0.37 | -2.34 | 0.00240409 | 5636.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9585.56 | -10.70 | 0.00150390 | -10.70 | 0.15632344 | 3.4807 | 0.00 | 0.00243655 | 24.14 | 0.00243655 | 13.1258 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.457633 | 0.55080504 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 958.56 | 958.56 | 1.0000 | 0.55080504 | 0.457633 | -0.37 | -3.04 | 0.00197149 | 4562.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.56 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.4159 | 0.00 | 0.00198803 | 23.07 | 0.00198803 | 11.4327 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.90 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 83.20 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 9.12 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 4.80 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialEnthalpy | 0.34 | 24.41 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3210.33 | 2088.00 | 1198.83 |
CORE_BOTTOM | 2818.50 | 1178.17 | 12.67 |
CORE_MID | 2262.00 | 2767.83 | 58.50 |
CORE_TOP | 2681.33 | 3287.67 | 665.17 |
PERIMETER_BOT_ZN_3 | 2562.83 | 2943.17 | 306.83 |
PERIMETER_BOT_ZN_2 | 2798.67 | 2798.50 | 372.00 |
PERIMETER_BOT_ZN_1 | 3058.67 | 2396.83 | 375.50 |
PERIMETER_BOT_ZN_4 | 3300.50 | 1816.17 | 396.00 |
PERIMETER_MID_ZN_3 | 3341.00 | 3559.50 | 1464.67 |
PERIMETER_MID_ZN_2 | 2882.67 | 2825.33 | 1129.83 |
PERIMETER_MID_ZN_1 | 3282.50 | 2797.67 | 845.17 |
PERIMETER_MID_ZN_4 | 3354.17 | 3123.17 | 1074.83 |
PERIMETER_TOP_ZN_3 | 3850.17 | 3764.17 | 2100.00 |
PERIMETER_TOP_ZN_2 | 3807.33 | 3450.17 | 1743.67 |
PERIMETER_TOP_ZN_1 | 3594.00 | 3072.67 | 1335.33 |
PERIMETER_TOP_ZN_4 | 3738.83 | 3343.33 | 1601.00 |
DATACENTER_BOT_ZN_6 | 5936.83 | 963.83 | 963.83 |
DATACENTER_MID_ZN_6 | 5545.67 | 213.17 | 143.00 |
DATACENTER_TOP_ZN_6 | 4941.00 | 536.67 | 316.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5576.50 | 5576.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5933.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 2403.33 | 0.00 | 1509.17 |
CORE_BOTTOM | 0.00 | 11.83 | 0.00 | 0.67 |
CORE_MID | 2.50 | 0.00 | 1.50 | 0.00 |
CORE_TOP | 8.00 | 0.00 | 1.83 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 25.17 | 0.00 | 14.50 |
PERIMETER_BOT_ZN_2 | 0.00 | 54.00 | 0.00 | 46.17 |
PERIMETER_BOT_ZN_1 | 0.33 | 73.00 | 0.00 | 62.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 152.83 | 0.00 | 69.00 |
PERIMETER_MID_ZN_3 | 30.67 | 2.00 | 8.00 | 1.83 |
PERIMETER_MID_ZN_2 | 31.17 | 45.17 | 1.00 | 44.50 |
PERIMETER_MID_ZN_1 | 13.83 | 74.17 | 0.67 | 73.00 |
PERIMETER_MID_ZN_4 | 14.00 | 46.83 | 1.33 | 29.00 |
PERIMETER_TOP_ZN_3 | 106.33 | 10.33 | 28.83 | 8.83 |
PERIMETER_TOP_ZN_2 | 63.33 | 48.67 | 5.83 | 45.00 |
PERIMETER_TOP_ZN_1 | 50.33 | 52.50 | 3.50 | 48.17 |
PERIMETER_TOP_ZN_4 | 42.00 | 50.67 | 3.67 | 30.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 1.33 | 0.00 | 1.33 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 6.50 | 0.00 | 6.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 127.50 | 2536.67 | 29.50 | 1628.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.814 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.776 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.595 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.582 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.758 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 1.035 | 0.026 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 1.187 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 1.504 | 0.026 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.669 | 0.058 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.937 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 1.154 | 0.058 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 1.067 | 0.060 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.680 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 1.017 | 0.074 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 1.146 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 1.074 | 0.074 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 21.113 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.22 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.95 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.54 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1031.21 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 32142664.57 | 0.00 | 32142664.57 | 0.00 | 32142664.57 | 37848132.68 | 5298.58 | 933.28 | 2528.14 | 0.00 |
CORE_BOTTOM | 32510487.73 | 0.00 | 32510487.73 | 0.00 | 32510487.73 | 33990283.35 | 4976.06 | 155.65 | 3628.29 | 281.18 |
CORE_MID | 0.24E+09 | 0.00 | 0.24E+09 | 0.00 | 0.24E+09 | 0.34E+09 | 5511.56 | 602.38 | 2646.07 | 163.24 |
CORE_TOP | 23700673.35 | 0.00 | 23700673.35 | 0.00 | 23700673.35 | 33990283.35 | 5622.86 | 942.34 | 2194.80 | 251.48 |
PERIMETER_BOT_ZN_3 | 3973951.81 | 0.00 | 3973951.81 | 244309.16 | 4218260.97 | 4267819.30 | 5270.51 | 237.60 | 3251.89 | 281.18 |
PERIMETER_BOT_ZN_2 | 3457143.51 | 0.00 | 3457143.51 | 162872.66 | 3620016.17 | 2750345.05 | 5140.13 | 273.15 | 3346.72 | 281.18 |
PERIMETER_BOT_ZN_1 | 6131578.36 | 0.00 | 6131578.36 | 244309.16 | 6375887.52 | 4267912.63 | 4743.17 | 198.10 | 3818.73 | 281.18 |
PERIMETER_BOT_ZN_4 | 5023230.74 | 0.00 | 5023230.74 | 162872.66 | 5186103.40 | 2750345.05 | 4214.91 | 142.08 | 4403.01 | 281.18 |
PERIMETER_MID_ZN_3 | 34194469.38 | 0.00 | 34194469.38 | 572971.12 | 34767440.50 | 42678193.03 | 4840.74 | 562.81 | 3356.45 | 163.24 |
PERIMETER_MID_ZN_2 | 31071686.04 | 0.00 | 31071686.04 | 381980.48 | 31453666.52 | 27503450.52 | 4953.46 | 788.28 | 3018.26 | 737.38 |
PERIMETER_MID_ZN_1 | 58495733.61 | 0.00 | 58495733.61 | 572971.12 | 59068704.72 | 42679126.28 | 4300.47 | 590.42 | 3869.11 | 163.24 |
PERIMETER_MID_ZN_4 | 34961219.23 | 0.00 | 34961219.23 | 381980.48 | 35343199.71 | 27503450.52 | 4630.31 | 806.96 | 3322.74 | 163.24 |
PERIMETER_TOP_ZN_3 | 3475098.50 | 0.00 | 3475098.50 | 711401.85 | 4186500.35 | 4267819.30 | 4586.51 | 731.13 | 3442.35 | 251.48 |
PERIMETER_TOP_ZN_2 | 3325951.72 | 0.00 | 3325951.72 | 474267.57 | 3800219.29 | 2750345.05 | 4464.85 | 547.19 | 3747.95 | 251.48 |
PERIMETER_TOP_ZN_1 | 5807218.79 | 0.00 | 5807218.79 | 711401.85 | 6518620.63 | 4267912.63 | 4246.79 | 645.80 | 3867.41 | 251.48 |
PERIMETER_TOP_ZN_4 | 3522106.51 | 0.00 | 3522106.51 | 474267.57 | 3996374.09 | 2750345.05 | 4532.12 | 1066.59 | 3161.29 | 251.48 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.33E+09 | 0.00 | 0.33E+09 | 0.00 | 0.33E+09 | 10671554.30 | 882.51 | 971.84 | 6905.65 | 2253.50 |
Total Facility | 0.45E+10 | 0.00 | 0.45E+10 | 22284734.42 | 0.45E+10 | 0.50E+10 | 7307.29 | 4362.90 | 7964.00 | 2889.91 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.5024 | 0.0000 | 1.5024 | 0.0000 | 1.5024 | 1.2002 | 2481.58 | 933.28 | 2528.14 |
CORE_BOTTOM | 1.4469 | 0.0000 | 1.4469 | 0.0000 | 1.4469 | 1.0778 | 2383.72 | 154.15 | 3405.13 |
CORE_MID | 11.0912 | 0.0000 | 11.0912 | 0.0000 | 11.0912 | 10.7782 | 2753.10 | 602.21 | 2587.69 |
CORE_TOP | 1.0874 | 0.0000 | 1.0874 | 0.0000 | 1.0874 | 1.0778 | 2854.25 | 942.34 | 2146.41 |
PERIMETER_BOT_ZN_3 | 0.1774 | 0.0000 | 0.1774 | 0.0058 | 0.1832 | 0.1353 | 2672.17 | 235.67 | 3035.16 |
PERIMETER_BOT_ZN_2 | 0.1562 | 0.0000 | 0.1562 | 0.0039 | 0.1601 | 0.0872 | 2541.79 | 270.83 | 3130.39 |
PERIMETER_BOT_ZN_1 | 0.2782 | 0.0000 | 0.2782 | 0.0058 | 0.2840 | 0.1353 | 2145.26 | 196.32 | 3601.42 |
PERIMETER_BOT_ZN_4 | 0.2268 | 0.0000 | 0.2268 | 0.0039 | 0.2307 | 0.0872 | 1622.22 | 140.76 | 4180.02 |
PERIMETER_MID_ZN_3 | 1.5684 | 0.0000 | 1.5684 | 0.0136 | 1.5821 | 1.3533 | 2085.04 | 562.19 | 3295.77 |
PERIMETER_MID_ZN_2 | 1.4145 | 0.0000 | 1.4145 | 0.0097 | 1.4242 | 0.8721 | 1753.29 | 784.78 | 2495.93 |
PERIMETER_MID_ZN_1 | 2.7043 | 0.0000 | 2.7043 | 0.0136 | 2.7179 | 1.3533 | 1544.78 | 590.15 | 3808.08 |
PERIMETER_MID_ZN_4 | 1.6093 | 0.0000 | 1.6093 | 0.0091 | 1.6184 | 0.8721 | 1875.29 | 806.74 | 3260.97 |
PERIMETER_TOP_ZN_3 | 0.1596 | 0.0000 | 0.1596 | 0.0169 | 0.1765 | 0.1353 | 1819.51 | 730.92 | 3392.57 |
PERIMETER_TOP_ZN_2 | 0.1536 | 0.0000 | 0.1536 | 0.0113 | 0.1649 | 0.0872 | 1701.41 | 547.03 | 3694.56 |
PERIMETER_TOP_ZN_1 | 0.2686 | 0.0000 | 0.2686 | 0.0169 | 0.2855 | 0.1353 | 1480.87 | 645.74 | 3816.39 |
PERIMETER_TOP_ZN_4 | 0.1621 | 0.0000 | 0.1621 | 0.0113 | 0.1734 | 0.0872 | 1766.07 | 1066.53 | 3110.40 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 10.8684 | 0.0000 | 10.8684 | 0.0000 | 10.8684 | 0.3384 | 319.01 | 971.84 | 4652.15 |
Total Facility | 201.5289 | 0.0000 | 201.5289 | 0.5367 | 202.0656 | 158.4706 | 4490.29 | 4358.86 | 5648.22 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 74018165.89 | 0.00 | 74018165.89 | 48026705.38 | 3782.64 | 4.95 | 4972.40 | 281.18 |
VAV_MID WITH REHEAT | 0.58E+09 | 0.00 | 0.58E+09 | 0.48E+09 | 4074.74 | 3.62 | 4681.64 | 163.24 |
VAV_TOP WITH REHEAT | 57697488.91 | 0.00 | 57697488.91 | 48026705.38 | 4121.17 | 1.07 | 4637.76 | 251.48 |
CAV_BAS | 46563181.46 | 0.00 | 46563181.46 | 37848132.68 | 5266.33 | 0.02 | 3493.66 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.48E+09 | 0.00 | 0.48E+09 | 10671554.30 | 882.51 | 0.00 | 7877.49 | 2253.50 |
AIRLOOP DATACENTER BOT | 353897.20 | 0.00 | 353897.20 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3538971.99 | 0.00 | 3538971.99 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 353897.20 | 0.00 | 353897.20 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.3109 | 0.0000 | 3.3109 | 1.5229 | 1220.14 | 2.77 | 4720.09 |
VAV_MID WITH REHEAT | 26.6625 | 0.0000 | 26.6625 | 15.2292 | 1319.78 | 3.38 | 4619.84 |
VAV_TOP WITH REHEAT | 2.6527 | 0.0000 | 2.6527 | 1.5229 | 1355.50 | 0.80 | 4586.70 |
CAV_BAS | 2.1764 | 0.0000 | 2.1764 | 1.2002 | 2449.33 | 0.02 | 3493.66 |
AIRLOOP DATACENTER BASEMENT | 15.7445 | 0.0000 | 15.7445 | 0.3384 | 319.01 | 0.00 | 5623.99 |
AIRLOOP DATACENTER BOT | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1654 | 0.0000 | 0.1654 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 637.71 | 2505.96 | 0.00 | 0.00 | 0.00 | 1938.09 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 315.22 | 2062.77 | 0.00 | 0.00 | 0.00 | 2533.11 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 69.99 | 2186.04 | 0.00 | 0.00 | 0.00 | 2771.23 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 913.87 | 2541.25 | 0.00 | 50.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 971.84 | 6905.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.9472 | 5.9130 | 0.0000 | 0.0000 | 0.0000 | 2.3911 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 29.1473 | 46.8690 | 0.0000 | 0.0000 | 0.0000 | 23.7869 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.9154 | 4.6855 | 0.0000 | 0.0000 | 0.0000 | 2.3464 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7402 | 4.4368 | 0.0000 | 1.4299 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4906 | 20.0114 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0227 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0227 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1525 |
Defaulted Fields | 1189 |
Fields with Defaults | 3954 |
Autosized Fields | 338 |
Autosizable Fields | 416 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 25212.33 | 282285.80 | 07-MAY-05:00 | 1895837.77 | 22-AUG-14:30 |
Electricity:Building | 16393.59 | 215366.33 | 14-MAY-17:10 | 948093.84 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 540.44 | 14022.76 | 01-JAN-00:10 | 23631.68 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16393.59 | 215366.33 | 14-MAY-17:10 | 948093.84 | 01-DEC-16:30 |
InteriorLights:Electricity | 1717.19 | 8110.17 | 01-JAN-08:40 | 169722.15 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1717.19 | 8110.17 | 01-JAN-08:40 | 169722.15 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 1717.19 | 8110.17 | 01-JAN-08:40 | 169722.15 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1717.19 | 8110.17 | 01-JAN-08:40 | 169722.15 | 02-JAN-16:40 |
Electricity:Zone:CORE_BOTTOM | 393.83 | 4960.84 | 01-JAN-00:10 | 26343.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3938.24 | 49608.19 | 01-JAN-00:10 | 263436.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 393.82 | 4960.82 | 01-JAN-00:10 | 26343.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 43.96 | 589.50 | 02-APR-17:10 | 3307.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.60 | 30.32 | 01-JAN-08:40 | 1147.25 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.60 | 30.32 | 01-JAN-08:40 | 1147.25 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.32 | 379.89 | 09-APR-17:10 | 2131.68 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.88 | 19.54 | 01-JAN-07:50 | 739.33 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.88 | 19.54 | 01-JAN-07:50 | 739.33 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.88 | 589.50 | 19-MAR-17:10 | 3307.86 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.51 | 30.33 | 01-JAN-07:50 | 1147.28 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.51 | 30.33 | 01-JAN-07:50 | 1147.28 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.28 | 379.89 | 12-MAR-17:10 | 2131.67 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.84 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.84 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 439.49 | 5894.96 | 26-MAR-17:10 | 33078.05 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 75.84 | 303.25 | 01-JAN-08:30 | 11472.53 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 75.84 | 303.25 | 01-JAN-08:30 | 11472.53 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 283.12 | 3798.93 | 02-APR-17:10 | 21316.76 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.76 | 195.42 | 01-JAN-07:50 | 7393.34 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.76 | 195.42 | 01-JAN-07:50 | 7393.34 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 438.69 | 5895.05 | 19-MAR-17:10 | 33078.63 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 75.03 | 303.26 | 01-JAN-07:50 | 11472.78 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 75.03 | 303.26 | 01-JAN-07:50 | 11472.78 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 282.74 | 3798.91 | 12-MAR-17:10 | 21316.66 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.39 | 195.42 | 01-JAN-08:30 | 7393.34 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.39 | 195.42 | 01-JAN-08:30 | 7393.34 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 43.95 | 589.50 | 26-MAR-17:10 | 3307.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.58 | 30.32 | 01-JAN-08:30 | 1147.25 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.58 | 30.32 | 01-JAN-08:30 | 1147.25 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.31 | 379.89 | 02-APR-17:10 | 2131.68 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.88 | 19.54 | 01-JAN-07:50 | 739.33 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.88 | 19.54 | 01-JAN-07:50 | 739.33 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.87 | 589.50 | 19-MAR-17:10 | 3307.86 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.50 | 30.33 | 01-JAN-07:50 | 1147.28 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.50 | 30.33 | 01-JAN-07:50 | 1147.28 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.27 | 379.89 | 12-MAR-17:10 | 2131.67 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.84 | 19.54 | 01-JAN-08:30 | 739.33 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.84 | 19.54 | 01-JAN-08:30 | 739.33 | 02-JAN-16:40 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7527.71 | 95067.50 | 01-JAN-00:10 | 382501.19 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1555.56 | 19567.35 | 01-JAN-00:10 | 79407.42 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2265.45 | 3787.24 | 02-JAN-04:00 | 403885.54 | 22-AUG-14:30 |
HeatRejection:Electricity | 674.53 | 57.99 | 02-JAN-07:20 | 79373.33 | 07-APR-14:40 |
General:HeatRejection:Electricity | 674.53 | 57.99 | 02-JAN-07:20 | 79373.33 | 07-APR-14:40 |
ElectricityProduced:Facility | 454.18 | -0.00 | 01-JAN-16:30 | 87214.16 | 02-JUN-11:50 |
ElectricityProduced:Plant | 454.18 | -0.00 | 01-JAN-16:30 | 87214.16 | 02-JUN-11:50 |
Photovoltaic:ElectricityProduced | 475.33 | 0.00 | 01-JAN-00:10 | 90823.46 | 02-JUN-11:50 |
PowerConversion:ElectricityProduced | -21.15 | -3609.30 | 02-JUN-11:50 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 4700.56 | 48705.61 | 15-JAN-10:10 | 452607.76 | 30-AUG-15:50 |
ExteriorEquipment:Electricity | 1641.46 | 10611.42 | 01-JAN-00:10 | 154952.96 | 03-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.35 | 979.82 | 01-JAN-00:10 | 3372.05 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 24758.15 | 279212.62 | 07-MAY-05:00 | 1838969.78 | 22-AUG-14:30 |
ElectricityPurchased:Plant | 24758.15 | 279212.62 | 07-MAY-05:00 | 1838969.78 | 22-AUG-14:30 |
Cogeneration:ElectricityPurchased | 24758.15 | 279212.62 | 07-MAY-05:00 | 1838969.78 | 22-AUG-14:30 |
General:Cogeneration:ElectricityPurchased | 24758.15 | 279212.62 | 07-MAY-05:00 | 1838969.78 | 22-AUG-14:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 24758.15 | 279212.62 | 07-MAY-05:00 | 1838969.78 | 22-AUG-14:30 |
ElectricityNet:Plant | 24758.15 | 279212.62 | 07-MAY-05:00 | 1838969.78 | 22-AUG-14:30 |
Cogeneration:ElectricityNet | 24758.15 | 279212.62 | 07-MAY-05:00 | 1838969.78 | 22-AUG-14:30 |
General:Cogeneration:ElectricityNet | 24758.15 | 279212.62 | 07-MAY-05:00 | 1838969.78 | 22-AUG-14:30 |
Fans:Electricity | 2274.88 | 46332.57 | 13-AUG-15:00 | 275461.04 | 30-MAY-09:20 |
General:Fans:Electricity | 2274.88 | 46332.57 | 13-AUG-15:00 | 275461.04 | 30-MAY-09:20 |
ExteriorLights:Electricity | 265.63 | 0.00 | 01-JAN-07:30 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 265.63 | 0.00 | 01-JAN-07:30 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1582.20 | 9600.00 | 01-JAN-00:10 | 151268.49 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
HeatRecovery:Electricity | 43.27 | 0.00 | 01-JAN-00:10 | 4520.72 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 43.27 | 0.00 | 01-JAN-00:10 | 4520.72 | 02-JAN-07:10 |
Cooling:Electricity | 1806.13 | 1200.45 | 03-JAN-09:00 | 407412.53 | 22-AUG-14:30 |
General:Cooling:Electricity | 1806.13 | 1200.45 | 03-JAN-09:00 | 407412.53 | 22-AUG-14:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1273.64 | 0.00 | 03-JAN-09:20 | 100000.00 | 02-FEB-05:50 |
General:Humidifier:Electricity | 1273.64 | 0.00 | 03-JAN-09:20 | 100000.00 | 02-FEB-05:50 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 426.33 | 0.00 | 01-JAN-00:10 | 53226.59 | 14-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 426.33 | 0.00 | 01-JAN-00:10 | 53226.59 | 14-FEB-12:40 |
Pumps:Electricity | 412.86 | 3722.93 | 02-JAN-04:40 | 49868.07 | 01-SEP-14:10 |
General:Pumps:Electricity | 412.86 | 3722.93 | 02-JAN-04:40 | 49868.07 | 01-SEP-14:10 |
WIRED_LTG_ELECTRICITY | 48.25 | 0.00 | 01-JAN-00:10 | 4769.19 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 518.13 | 0.00 | 01-JAN-00:40 | 1501293.39 | 02-JAN-05:10 |
NaturalGas:Plant | 518.13 | 0.00 | 01-JAN-00:40 | 1501293.39 | 02-JAN-05:10 |
Heating:NaturalGas | 518.13 | 0.00 | 01-JAN-00:40 | 1501293.39 | 02-JAN-05:10 |
Boiler:Heating:NaturalGas | 518.13 | 0.00 | 01-JAN-00:40 | 1501293.39 | 02-JAN-05:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 11452.15 | 2216.71 | 03-JAN-09:10 | 2667813.91 | 22-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 11452.15 | 2216.71 | 03-JAN-09:10 | 2667813.91 | 22-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 11452.15 | 2216.71 | 03-JAN-09:10 | 2667813.91 | 22-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 7390.57 | 0.00 | 24-JAN-00:10 | 0.00 | 30-AUG-15:50 |
Water:HVAC | 473.80 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
Humidifier:Water | 473.80 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
General:Humidifier:Water | 473.80 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
MainsWater:Facility | 7390.57 | 0.00 | 24-JAN-00:10 | 0.00 | 30-AUG-15:50 |
MainsWater:HVAC | 473.80 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
Humidifier:MainsWater | 473.80 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
General:Humidifier:MainsWater | 473.80 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
Water:Plant | 6916.78 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
MainsWater:Plant | 6916.78 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 4636.61 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
General:HeatRejection:Water | 4636.61 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
HeatRejection:MainsWater | 4636.61 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
General:HeatRejection:MainsWater | 4636.61 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 51453.93 | 94698.41 | 02-JAN-04:40 | 10363092.33 | 22-AUG-14:30 |
EnergyTransfer:Building | 17830.20 | 88373.19 | 07-JAN-18:20 | 1603693.20 | 21-AUG-14:30 |
EnergyTransfer:Zone:BASEMENT | 476.83 | 0.00 | 01-JAN-00:10 | 92502.88 | 13-NOV-07:10 |
Heating:EnergyTransfer | 406.50 | 0.00 | 19-JAN-22:10 | 1235075.34 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 406.50 | 0.00 | 19-JAN-22:10 | 1235075.34 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 17423.70 | 85921.47 | 02-JAN-05:00 | 1603693.20 | 21-AUG-14:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 476.83 | 0.00 | 01-JAN-00:10 | 92502.88 | 13-NOV-07:10 |
General:Cooling:EnergyTransfer | 17423.70 | 85921.47 | 02-JAN-05:00 | 1603693.20 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 476.83 | 0.00 | 01-JAN-00:10 | 92502.88 | 13-NOV-07:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 608.06 | 0.00 | 01-JAN-00:10 | 64867.74 | 14-AUG-07:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 608.06 | 0.00 | 01-JAN-00:10 | 64867.74 | 14-AUG-07:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 608.06 | 0.00 | 01-JAN-00:10 | 64867.74 | 14-AUG-07:30 |
EnergyTransfer:Zone:CORE_MID | 3855.86 | 0.00 | 01-JAN-00:40 | 420187.85 | 07-AUG-04:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 8.32 | 0.00 | 01-JAN-00:10 | 399882.23 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 8.32 | 0.00 | 01-JAN-00:10 | 399882.23 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3847.54 | 0.00 | 01-JAN-00:40 | 420187.85 | 07-AUG-04:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3847.54 | 0.00 | 01-JAN-00:40 | 420187.85 | 07-AUG-04:20 |
EnergyTransfer:Zone:CORE_TOP | 360.93 | 0.00 | 01-JAN-00:40 | 65892.26 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:CORE_TOP | 10.15 | 0.00 | 01-JAN-00:40 | 65892.26 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 10.15 | 0.00 | 01-JAN-00:40 | 65892.26 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 350.78 | 0.00 | 01-JAN-00:20 | 46523.88 | 30-MAY-13:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 350.78 | 0.00 | 01-JAN-00:20 | 46523.88 | 30-MAY-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 75.77 | 0.00 | 01-JAN-00:10 | 12510.79 | 17-AUG-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.25 | 0.00 | 01-JAN-00:10 | 5262.64 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.25 | 0.00 | 01-JAN-00:10 | 5262.64 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 75.52 | 0.00 | 01-JAN-00:10 | 12510.79 | 17-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 75.52 | 0.00 | 01-JAN-00:10 | 12510.79 | 17-AUG-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.77 | 0.00 | 01-JAN-00:10 | 15924.72 | 02-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.17 | 0.00 | 01-JAN-00:10 | 3534.45 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.17 | 0.00 | 01-JAN-00:10 | 3534.45 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.60 | 0.00 | 01-JAN-00:10 | 15924.72 | 02-AUG-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.60 | 0.00 | 01-JAN-00:10 | 15924.72 | 02-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 114.62 | 0.00 | 01-JAN-00:10 | 20433.06 | 30-AUG-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.45 | 0.00 | 01-JAN-00:10 | 8899.87 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.45 | 0.00 | 01-JAN-00:10 | 8899.87 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 114.17 | 0.00 | 01-JAN-00:10 | 20433.06 | 30-AUG-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 114.17 | 0.00 | 01-JAN-00:10 | 20433.06 | 30-AUG-12:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 95.77 | 0.00 | 01-JAN-00:10 | 18878.80 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 2495.56 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 2495.56 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 95.76 | 0.00 | 01-JAN-00:10 | 18878.80 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 95.76 | 0.00 | 01-JAN-00:10 | 18878.80 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 570.73 | 0.00 | 01-JAN-00:40 | 121078.77 | 02-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 82.74 | 0.00 | 01-JAN-00:40 | 121078.77 | 02-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 82.74 | 0.00 | 01-JAN-00:40 | 121078.77 | 02-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 487.99 | 0.00 | 01-JAN-00:10 | 102495.26 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 487.99 | 0.00 | 01-JAN-00:10 | 102495.26 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 535.89 | 0.00 | 01-JAN-00:40 | 156883.02 | 26-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 40.17 | 0.00 | 01-JAN-00:40 | 127279.17 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 40.17 | 0.00 | 01-JAN-00:40 | 127279.17 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 495.72 | 0.00 | 01-JAN-00:20 | 156883.02 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 495.72 | 0.00 | 01-JAN-00:20 | 156883.02 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 991.73 | 0.00 | 01-JAN-00:40 | 204894.40 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.68 | 0.00 | 01-JAN-00:40 | 167947.22 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.68 | 0.00 | 01-JAN-00:40 | 167947.22 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 951.05 | 0.00 | 01-JAN-00:20 | 204894.40 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 951.05 | 0.00 | 01-JAN-00:20 | 204894.40 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 599.66 | 0.00 | 01-JAN-00:40 | 166340.92 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.09 | 0.00 | 01-JAN-00:40 | 121237.42 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.09 | 0.00 | 01-JAN-00:40 | 121237.42 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 568.57 | 0.00 | 01-JAN-00:20 | 166340.92 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 568.57 | 0.00 | 01-JAN-00:20 | 166340.92 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 68.14 | 0.00 | 01-JAN-00:40 | 14366.96 | 06-FEB-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.49 | 0.00 | 01-JAN-00:40 | 14366.96 | 06-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.49 | 0.00 | 01-JAN-00:40 | 14366.96 | 06-FEB-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.65 | 0.00 | 01-JAN-00:10 | 11572.32 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.65 | 0.00 | 01-JAN-00:10 | 11572.32 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 60.93 | 0.00 | 01-JAN-00:40 | 15934.82 | 26-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 10.98 | 0.00 | 01-JAN-00:40 | 15505.89 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 10.98 | 0.00 | 01-JAN-00:40 | 15505.89 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.95 | 0.00 | 01-JAN-00:10 | 15934.82 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.95 | 0.00 | 01-JAN-00:10 | 15934.82 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 101.36 | 0.00 | 01-JAN-00:40 | 21753.85 | 04-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 12.36 | 0.00 | 01-JAN-00:40 | 18955.58 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 12.36 | 0.00 | 01-JAN-00:40 | 18955.58 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 88.99 | 0.00 | 01-JAN-00:10 | 21753.85 | 04-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 88.99 | 0.00 | 01-JAN-00:10 | 21753.85 | 04-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 63.62 | 0.00 | 01-JAN-00:40 | 17248.99 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 8.48 | 0.00 | 01-JAN-00:40 | 14294.75 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 8.48 | 0.00 | 01-JAN-00:40 | 14294.75 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 55.13 | 0.00 | 01-JAN-00:20 | 17248.99 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 55.13 | 0.00 | 01-JAN-00:20 | 17248.99 | 15-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 63.06 | 0.00 | 01-JAN-00:10 | 13764.03 | 14-AUG-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 2.64 | 0.00 | 01-JAN-00:10 | 3968.15 | 03-DEC-09:50 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 2.64 | 0.00 | 01-JAN-00:10 | 3968.15 | 03-DEC-09:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 60.42 | 0.00 | 01-JAN-00:10 | 13764.03 | 14-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 60.42 | 0.00 | 01-JAN-00:10 | 13764.03 | 14-AUG-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 432.44 | 0.00 | 01-JAN-00:40 | 157214.39 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 100.60 | 0.00 | 01-JAN-00:40 | 157214.39 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 100.60 | 0.00 | 01-JAN-00:40 | 157214.39 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 331.84 | 0.00 | 01-JAN-00:10 | 74017.01 | 22-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 331.84 | 0.00 | 01-JAN-00:10 | 74017.01 | 22-AUG-14:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 88.83 | 0.00 | 01-JAN-00:40 | 26408.38 | 06-FEB-05:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.39 | 0.00 | 01-JAN-00:40 | 26408.38 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.39 | 0.00 | 01-JAN-00:40 | 26408.38 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 57.44 | 0.00 | 01-JAN-00:10 | 20399.77 | 19-JUN-13:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 57.44 | 0.00 | 01-JAN-00:10 | 20399.77 | 19-JUN-13:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.67 | 292.05 | 02-JAN-06:00 | 8337.04 | 23-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.67 | 292.05 | 02-JAN-06:00 | 8337.04 | 23-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.67 | 292.05 | 02-JAN-06:00 | 8337.04 | 23-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1189.67 | 0.18 | 07-JAN-12:10 | 77015.48 | 31-AUG-17:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.75 | 0.00 | 02-JAN-07:10 | 5243.92 | 03-JAN-01:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.75 | 0.00 | 02-JAN-07:10 | 5243.92 | 03-JAN-01:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1185.92 | 0.00 | 01-JAN-00:10 | 77015.48 | 31-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1185.92 | 0.00 | 01-JAN-00:10 | 77015.48 | 31-AUG-17:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 110.34 | 0.03 | 07-JAN-11:00 | 7846.31 | 13-AUG-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.76 | 0.00 | 02-JAN-07:10 | 564.41 | 16-JAN-18:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.76 | 0.00 | 02-JAN-07:10 | 564.41 | 16-JAN-18:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 109.58 | 0.00 | 01-JAN-00:10 | 7846.31 | 13-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 109.58 | 0.00 | 01-JAN-00:10 | 7846.31 | 13-AUG-18:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7163.51 | 85611.76 | 02-JAN-05:00 | 369189.79 | 22-AUG-17:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7163.51 | 85611.76 | 02-JAN-05:00 | 369189.79 | 22-AUG-17:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7163.51 | 85611.76 | 02-JAN-05:00 | 369189.79 | 22-AUG-17:10 |
PlantLoopHeatingDemand:Facility | 905.12 | 0.00 | 01-JAN-00:40 | 1307095.14 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-13:00 |
WaterSystems:PlantLoopHeatingDemand | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-13:00 |
EnergyTransfer:HVAC | 12600.18 | 1089.47 | 15-JAN-10:10 | 2637317.38 | 16-AUG-12:30 |
HeatingCoils:EnergyTransfer | 484.02 | 0.00 | 01-JAN-00:40 | 1300751.49 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 484.02 | 0.00 | 01-JAN-00:40 | 1300751.49 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 484.02 | 0.00 | 01-JAN-00:40 | 1300751.49 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 10397.75 | 1010.13 | 03-JAN-09:10 | 2513500.22 | 22-AUG-14:30 |
HeatRecoveryForHeating:EnergyTransfer | 1241.40 | 0.00 | 01-JAN-00:10 | 649288.90 | 06-FEB-07:10 |
HeatRecoveryForCooling:EnergyTransfer | 477.02 | 0.00 | 01-JAN-00:10 | 514202.12 | 08-JUL-12:20 |
EnergyTransfer:Plant | 21023.55 | 0.00 | 01-JAN-00:40 | 6244529.08 | 22-AUG-14:30 |
LoopToLoop:EnergyTransfer | 6465.77 | 0.00 | 01-JAN-00:10 | 1985809.82 | 22-AUG-14:30 |
WaterSystems:EnergyTransfer | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-13:00 |
Boilers:EnergyTransfer | 483.29 | 0.00 | 01-JAN-00:40 | 1339446.43 | 02-JAN-05:10 |
Chillers:EnergyTransfer | 6450.83 | 0.00 | 01-JAN-00:10 | 1965492.94 | 22-AUG-14:30 |
HeatRejection:EnergyTransfer | 7202.56 | 0.00 | 01-JAN-00:10 | 2218591.78 | 22-AUG-14:30 |
General:HeatRejection:EnergyTransfer | 7202.56 | 0.00 | 01-JAN-00:10 | 2218591.78 | 22-AUG-14:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -476.813 | 0.000 | 0.000 | 86.058 | 116.039 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -149.681 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -608.062 | 0.000 | 0.000 | 83.443 | 104.212 | 289.614 | 0.000 | 0.000 | 0.000 | 130.794 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 8.319 | -3847.521 | 0.000 | 0.000 | 850.977 | 1042.115 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -950.017 |
CORE_TOP | 0.000 | 0.000 | 10.149 | -350.781 | 0.000 | 0.000 | 87.948 | 104.212 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -141.141 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.252 | -75.522 | 0.000 | 0.000 | 10.787 | 7.595 | 36.365 | 31.476 | 0.000 | 0.049 | 52.514 | 0.000 | -59.595 | 0.000 | -3.921 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.173 | -64.601 | 0.000 | 0.000 | 6.901 | 4.882 | 23.435 | 57.844 | 0.000 | 0.032 | 10.871 | 0.000 | -36.931 | 0.000 | -2.607 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.449 | -114.169 | 0.000 | 0.000 | 10.672 | 7.509 | 36.366 | 118.655 | 0.000 | 0.048 | 0.001 | 0.000 | -54.213 | 0.000 | -3.943 | -1.373 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.016 | -95.757 | 0.000 | 0.000 | 6.790 | 4.844 | 23.435 | 57.897 | 0.000 | 0.031 | 47.994 | 0.000 | -42.369 | 0.000 | -2.880 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 82.745 | -487.983 | 0.000 | 0.000 | 112.801 | 75.840 | 363.654 | 326.758 | 0.000 | 1.140 | 134.091 | 0.000 | -528.078 | 0.000 | -80.967 | -0.006 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 40.171 | -495.716 | 0.000 | 0.000 | 52.185 | 48.764 | 234.352 | 579.544 | 0.000 | 0.698 | 0.002 | 0.000 | -339.355 | 0.000 | -55.845 | -64.798 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 40.679 | -951.040 | 0.000 | 0.000 | 108.425 | 75.031 | 363.660 | 1184.657 | 0.000 | 1.081 | 0.031 | 0.000 | -515.149 | 0.000 | -87.150 | -220.194 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 31.087 | -568.570 | 0.000 | 0.000 | 71.262 | 48.387 | 234.351 | 589.810 | 0.000 | 0.699 | 11.656 | 0.000 | -361.052 | 0.000 | -57.630 | -0.010 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 21.494 | -46.649 | 0.000 | 0.000 | 11.421 | 7.583 | 36.365 | 32.992 | 0.000 | 0.132 | 0.000 | 0.000 | -49.596 | 0.000 | -9.472 | -4.270 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 10.979 | -49.950 | 0.000 | 0.000 | 7.210 | 4.876 | 23.435 | 58.400 | 0.000 | 0.085 | 0.000 | 0.000 | -31.848 | 0.000 | -6.515 | -16.671 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 12.364 | -88.992 | 0.000 | 0.000 | 10.994 | 7.503 | 36.366 | 118.880 | 0.000 | 0.127 | 0.001 | 0.000 | -48.445 | 0.000 | -10.179 | -38.617 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 8.484 | -55.133 | 0.000 | 0.000 | 7.221 | 4.839 | 23.435 | 59.097 | 0.000 | 0.083 | 0.000 | 0.000 | -34.209 | 0.000 | -6.788 | -7.028 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -137.668 | 0.000 | 0.000 | 0.950 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -18.839 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 3.748 | -1185.924 | 0.000 | 0.000 | 9.516 | 16.758 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -382.904 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.765 | -109.578 | 0.000 | 0.000 | 0.955 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -47.698 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7163.519 | 0.000 | 0.000 | 20.563 | 32.854 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -384.756 |
GROUNDFLOOR_PLENUM | 2.644 | -60.419 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.079 | 66.114 | 0.000 | 0.000 | 0.000 | -8.419 | 0.000 |
MIDFLOOR_PLENUM | 100.603 | -331.835 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.581 | 369.858 | 0.000 | 0.000 | 0.000 | -140.208 | -0.002 |
TOPFLOOR_PLENUM | 31.389 | -57.436 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.128 | 40.635 | 0.000 | 0.000 | 0.000 | -14.716 | -0.005 |
Total Facility | 134.637 | -449.690 | 271.872 | -16973.949 | 0.000 | 0.000 | 1557.077 | 1717.194 | 14676.396 | 3216.009 | 0.000 | 5.994 | 864.563 | 0.000 | -2100.839 | 0.000 | -491.241 | -2428.012 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 15-SEP-06:11 | 0.00 | 0.00 | 0.00 | -105423.23 | 0.00 | 0.00 | 1404.33 | 3391.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 87169.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 30-MAY-04:13 | 0.00 | 0.00 | 0.00 | -88541.12 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 82066.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 07-AUG-04:14 | 0.00 | 0.00 | 0.00 | -784837.66 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 720087.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 28-AUG-04:14 | 0.00 | 0.00 | 0.00 | -81061.75 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 74586.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-JUL-16:32 | 0.00 | 0.00 | 0.00 | -16454.21 | 0.00 | 0.00 | 41.57 | 30.32 | 720.18 | 3591.10 | 0.00 | 0.00 | 12094.19 | 0.00 | -0.00 | 0.00 | -23.16 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-08:11 | 0.00 | 0.00 | 0.00 | -23773.16 | 0.00 | 0.00 | 18.66 | 19.54 | 464.11 | 18437.09 | 0.00 | 0.00 | 4845.46 | 0.00 | -0.00 | 0.00 | -11.71 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-12:11 | 0.00 | 0.00 | 0.00 | -27094.77 | 0.00 | 0.00 | 29.82 | 30.33 | 720.19 | 23456.02 | 0.00 | 0.00 | 2900.36 | 0.00 | -0.00 | 0.00 | -41.94 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JUL-16:01 | 0.00 | 0.00 | 0.00 | -30279.30 | 0.00 | 0.00 | 15.36 | 19.54 | 464.11 | 18623.84 | 0.00 | 0.00 | 11240.64 | 0.00 | -0.00 | 0.00 | -84.19 | 0.00 |
PERIMETER_MID_ZN_3 | 09-JUL-14:31 | 0.00 | 0.00 | 0.00 | -146911.41 | 0.00 | 0.00 | 419.86 | 303.25 | 7201.84 | 65166.58 | 0.00 | 760.21 | 73059.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-08:51 | 0.00 | 0.00 | 0.00 | -261351.54 | 0.00 | 0.00 | 175.77 | 195.42 | 4641.14 | 178782.88 | 0.00 | 0.00 | 78322.30 | 0.00 | -0.00 | 0.00 | -765.98 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-11:41 | 0.00 | 0.00 | 0.00 | -270900.50 | 0.00 | 0.00 | 298.42 | 303.26 | 7201.95 | 238710.50 | 0.00 | 0.00 | 25382.88 | 0.00 | -0.00 | 0.00 | -996.51 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-16:11 | 0.00 | 0.00 | 0.00 | -271590.98 | 0.00 | 0.00 | 166.07 | 195.42 | 4641.11 | 182219.85 | 0.00 | 0.00 | 86357.62 | 0.00 | -0.00 | 0.00 | -1989.10 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-AUG-15:01 | 0.00 | 0.00 | 0.00 | -16997.28 | 0.00 | 0.00 | 39.85 | 30.32 | 720.18 | 5337.90 | 0.00 | 109.86 | 10759.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -25763.17 | 0.00 | 0.00 | 18.86 | 19.54 | 464.11 | 19161.03 | 0.00 | 0.00 | 6192.21 | 0.00 | -0.00 | 0.00 | -92.58 | 0.00 |
PERIMETER_TOP_ZN_1 | 20-AUG-13:11 | 0.00 | 0.00 | 0.00 | -27439.16 | 0.00 | 0.00 | 33.08 | 30.33 | 720.19 | 17048.90 | 0.00 | 0.00 | 9633.01 | 0.00 | -0.00 | 0.00 | -26.36 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-16:21 | 0.00 | 0.00 | 0.00 | -26236.62 | 0.00 | 0.00 | 15.41 | 19.54 | 464.11 | 17723.21 | 0.00 | 0.00 | 8194.46 | 0.00 | -0.00 | 0.00 | -180.12 | 0.00 |
DATACENTER_BOT_ZN_6 | 23-APR-17:41 | 0.00 | 0.00 | 0.00 | -8337.04 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 534.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 31-AUG-17:40 | 0.00 | 0.00 | 0.00 | -77014.83 | 0.00 | 0.00 | 105.07 | 487.73 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1522.19 |
DATACENTER_TOP_ZN_6 | 13-AUG-18:22 | 0.00 | 0.00 | 0.00 | -7854.98 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 52.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 24-AUG-18:23 | 0.00 | 0.00 | 0.00 | -393177.35 | 0.00 | 0.00 | 229.80 | 956.24 | 379632.52 | 0.00 | 0.00 | 0.00 | 12358.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 14-AUG-05:13 | 0.00 | -15648.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15663.17 | 0.00 | -0.00 | 0.00 | -14.24 | 0.00 |
MIDFLOOR_PLENUM | 13-FEB-04:11 | 0.00 | -93928.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114275.23 | 0.00 | -0.00 | 0.00 | -20346.85 | 0.00 |
TOPFLOOR_PLENUM | 19-JUN-13:20 | 0.00 | -20399.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.89 | 20248.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:02 | 0.00 | -89406.67 | 0.00 | -1787987.01 | 0.00 | 0.00 | 15976.30 | 10223.35 | 616289.16 | 0.00 | 0.00 | 0.00 | 1276783.17 | 0.00 | -39987.14 | 0.00 | -1891.16 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 458050.95 | 0.00 | 0.00 | 0.00 | 0.00 | 5076.02 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -522503.19 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 73809.45 | 0.00 | 0.00 | 0.00 | 0.00 | 507.60 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -80254.68 |
PERIMETER_BOT_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 11357.84 | 0.00 | 0.00 | 0.00 | 0.00 | 127.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6658.31 | 0.00 | -323.75 | -5248.80 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 9891.02 | 0.00 | 0.00 | 0.00 | 0.00 | 82.15 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4580.38 | 0.00 | -632.57 | -5240.69 |
PERIMETER_BOT_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 15567.84 | 0.00 | 0.00 | 0.00 | 0.00 | 127.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6252.34 | 0.00 | -311.61 | -9876.93 |
PERIMETER_BOT_ZN_4 | 02-JAN-06:01 | 0.00 | 0.00 | 7401.62 | 0.00 | 0.00 | 0.00 | 94.15 | 43.48 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4517.71 | 0.00 | -66.53 | -3573.82 |
PERIMETER_MID_ZN_3 | 02-JAN-02:62 | 0.00 | 0.00 | 135656.62 | 0.00 | 0.00 | 0.00 | 0.00 | 637.34 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -55997.36 | 0.00 | -10867.23 | -76884.98 |
PERIMETER_MID_ZN_2 | 02-JAN-02:62 | 0.00 | 0.00 | 174696.78 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -36507.01 | 0.00 | -7468.43 | -135936.74 |
PERIMETER_MID_ZN_1 | 02-JAN-02:62 | 0.00 | 0.00 | 200323.39 | 0.00 | 0.00 | 0.00 | 0.00 | 637.36 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -55422.19 | 0.00 | -11162.31 | -141831.97 |
PERIMETER_MID_ZN_4 | 02-JAN-02:62 | 0.00 | 0.00 | 173821.19 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37882.08 | 0.00 | -7525.57 | -133628.92 |
PERIMETER_TOP_ZN_3 | 02-JAN-02:62 | 0.00 | 0.00 | 15838.36 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5497.13 | 0.00 | -1325.92 | -9824.61 |
PERIMETER_TOP_ZN_2 | 02-JAN-02:62 | 0.00 | 0.00 | 19596.54 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3578.15 | 0.00 | -913.50 | -15626.43 |
PERIMETER_TOP_ZN_1 | 02-JAN-02:62 | 0.00 | 0.00 | 22318.58 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5420.96 | 0.00 | -1360.94 | -16345.99 |
PERIMETER_TOP_ZN_4 | 02-JAN-02:62 | 0.00 | 0.00 | 20470.81 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3713.97 | 0.00 | -921.52 | -16356.85 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-JAN-01:00 | 0.00 | 0.00 | 5243.92 | 0.00 | 0.00 | 0.00 | 0.00 | 81.29 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24811.27 |
DATACENTER_TOP_ZN_6 | 16-JAN-18:05 | 0.00 | 0.00 | 570.75 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2527.48 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-05:11 | 11773.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -476.28 | -11297.68 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 167242.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2959.76 | -164282.55 |
TOPFLOOR_PLENUM | 06-FEB-05:22 | 27233.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3372.50 | -23861.18 |
Total Facility | 02-JAN-05:21 | 21384.36 | 100653.39 | 1223525.46 | -100653.39 | 0.00 | 0.00 | 0.00 | 10223.35 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -237183.77 | 0.00 | -43591.59 | -1206783.04 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.1228 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.8950 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 96.5952 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 83.1985 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.1086 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.1172 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.8008 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.8008 | 0.2500 | 1.0000 | Not calculated | 1.2002 | 0.2500 | ||
AIRLOOP DATACENTER BASEMENT | 24.4132 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.4135 | 0.0139 | 1.0000 | Not calculated | 0.3384 | 0.0139 | ||
AIRLOOP DATACENTER BOT | 0.4692 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4692 | 0.0333 | 1.0000 | Not calculated | 0.0156 | 0.0333 | ||
AIRLOOP DATACENTER MID | 4.4911 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4911 | 0.0348 | 1.0000 | Not calculated | 0.1563 | 0.0348 | ||
AIRLOOP DATACENTER TOP | 0.4576 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4576 | 0.0342 | 1.0000 | Not calculated | 0.0156 | 0.0342 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.0614 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2845 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 48.2976 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8500 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.0543 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2854 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 24.4132 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.4132 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0139 | ||
AIRLOOP DATACENTER BOT | 0.4692 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4692 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0333 | ||
AIRLOOP DATACENTER MID | 4.4911 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4911 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0348 | ||
AIRLOOP DATACENTER TOP | 0.4576 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4576 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0342 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 4.8008 | 4.8008 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2307 | 5.2307 | 1.6163 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 49.0297 | 49.0297 | 16.1798 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0049 | 5.0049 | 1.6166 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9268 | 0.9268 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1742 | 1.1742 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3486 | 1.3486 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4426 | 1.4426 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.7231 | 8.7231 | 2.0325 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.5344 | 12.5344 | 1.3036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.2711 | 13.2711 | 2.0305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.0368 | 13.0368 | 1.3037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9971 | 0.9971 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2761 | 1.2761 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4443 | 1.4443 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3862 | 1.3862 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4692 | 0.4692 | 0.4692 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4911 | 4.4911 | 4.4911 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4576 | 0.4576 | 0.4576 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.4132 | 24.4132 | 24.4132 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.1228 | 8.8950 | 10.1228 | 2.2845 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 96.5952 | 83.1985 | 96.5952 | 22.8500 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.1086 | 9.1172 | 10.1086 | 2.2854 | 0.0000 | 1.0000 |
CAV_BAS | 4.8008 | 4.8008 | 4.8008 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.4132 | 24.4135 | 24.4132 | 24.4132 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4692 | 0.4692 | 0.4692 | 0.4692 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4911 | 4.4911 | 4.4911 | 4.4911 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4576 | 0.4576 | 0.4576 | 0.4576 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6154 | 2.6154 | 1.6163 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.5149 | 24.5149 | 16.1798 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5024 | 2.5024 | 1.6166 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4634 | 0.4634 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5871 | 0.5871 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6743 | 0.6743 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7213 | 0.7213 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.3616 | 4.3616 | 2.0325 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.2672 | 6.2672 | 1.3036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.6356 | 6.6356 | 2.0305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.5184 | 6.5184 | 1.3037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4986 | 0.4986 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6381 | 0.6381 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7221 | 0.7221 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6931 | 0.6931 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4692 | 0.4692 | 0.4692 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4911 | 4.4911 | 4.4911 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4576 | 0.4576 | 0.4576 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.4132 | 24.4132 | 24.4132 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.0614 | 2.2845 | 2.2845 | 2.2845 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 48.2976 | 22.8500 | 22.8500 | 22.8500 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.0543 | 2.2854 | 2.2854 | 2.2854 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.4132 | 24.4132 | 24.4132 | 24.4132 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4692 | 0.4692 | 0.4692 | 0.4692 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4911 | 4.4911 | 4.4911 | 4.4911 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4576 | 0.4576 | 0.4576 | 0.4576 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 29.50 |
Number of hours cooling loads not met | 1628.00 |
Number of hours not met | 1643.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 518.13 | 1501293.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1806.13 | 407412.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1717.19 | 169722.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 265.63 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.35 | 3372.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1582.20 | 151268.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2274.88 | 275461.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 412.86 | 49868.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 674.53 | 79373.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1273.64 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 43.27 | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 426.33 | 53226.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 25212.33 |
Natural Gas | 0.00 | 518.13 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 25730.46 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 475.33 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 37.07 |
Space Heating | 0.00 |
Space Cooling | 38.99 |
Fans (All) | 49.11 |
Service Water Heating | 9.20 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 544.30 |
Subtotal | 544.30 |
Natural Gas [MJ/m2] | |
Space Heating | 11.19 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 11.19 |
Subtotal | 11.19 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.67 |
Space Heating | 2.01 |
Space Cooling | 7.02 |
Fans (All) | 8.84 |
Service Water Heating | 1.66 |
Receptacle Equipment | 57.04 |
Miscellaneous | 16.76 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2069. | 8760. |
LTG_SCH_DATACENTER | 1840. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 814. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 6716.67 | 736.00 | 527.33 | 780.00 | 0.00 |
CORE_BOTTOM | 8703.00 | 57.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8692.17 | 67.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8638.00 | 122.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8631.83 | 128.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8105.17 | 654.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8737.83 | 22.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8630.50 | 129.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8648.17 | 111.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8385.83 | 374.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8706.50 | 53.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8596.50 | 163.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8616.67 | 143.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8386.00 | 374.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6385.17 | 2374.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6395.83 | 2364.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6366.50 | 2393.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5573.17 | 3186.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8720.00 | 40.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8635.33 | 124.67 | 0.00 | 0.00 | 0.00 |
Min | 5573.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3186.83 | 527.33 | 780.00 | 0.00 |
Average | 8110.53 | 592.63 | 22.93 | 33.91 | 0.00 |
Sum | 186542.17 | 13630.50 | 527.33 | 780.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 298133.83 | 16821.17 | 19048.17 | 34612.83 | 0.00 |
CORE_BOTTOM | 330769.00 | 44.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330808.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1329.00 | 939.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1321.17 | 946.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1316.67 | 951.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 63723.83 | 39671.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330813.00 | 39671.17 | 19048.17 | 34612.83 | 0.00 |
Average | 75420.15 | 2581.67 | 828.18 | 1504.91 | 0.00 |
Sum | 1734663.50 | 59378.50 | 19048.17 | 34612.83 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 6324.67 | 1133.33 | 354.83 | 947.17 | 0.00 |
CORE_BOTTOM | 7650.50 | 1109.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7885.00 | 875.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7903.33 | 856.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7805.33 | 954.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7827.50 | 932.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7752.00 | 1008.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7502.00 | 1258.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7881.00 | 879.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7798.33 | 961.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7757.17 | 1002.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7720.67 | 1039.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7869.33 | 890.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7812.17 | 947.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7791.17 | 968.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7753.83 | 1006.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7455.67 | 1304.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7423.00 | 1337.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7405.50 | 1354.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6482.67 | 2277.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7574.83 | 1185.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7564.00 | 1196.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7206.00 | 1554.00 | 0.00 | 0.00 | 0.00 |
Min | 6324.67 | 856.67 | 0.00 | 0.00 | 0.00 |
Max | 7903.33 | 2277.33 | 354.83 | 947.17 | 0.00 |
Average | 7571.55 | 1131.84 | 15.43 | 41.18 | 0.00 |
Sum | 174145.67 | 26032.33 | 354.83 | 947.17 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 294176.83 | 21479.00 | 13799.83 | 39160.33 | 0.00 |
CORE_BOTTOM | 328800.00 | 2013.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 329607.00 | 1206.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 328771.17 | 2041.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38918.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18348.33 | 5.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38919.83 | 5.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24906.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38905.83 | 19.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24895.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38899.67 | 25.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24895.17 | 13.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1501.83 | 766.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1485.17 | 782.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1475.83 | 792.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 67260.83 | 36134.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 329607.00 | 36134.17 | 13799.83 | 39160.33 | 0.00 |
Average | 75192.86 | 2839.44 | 599.99 | 1702.62 | 0.00 |
Sum | 1729435.67 | 65307.17 | 13799.83 | 39160.33 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361852E+11 | 89894.06 | 02-JAN-07:03 | -11.6 | -13.1 | 0.567107E+10 | 7499.37 | 03-JAN-10:09 | 10.33 | 9.75 |
February | 0.349213E+11 | 91692.71 | 21-FEB-07:05 | 2.80 | 1.83 | 0.514789E+10 | 7499.20 | 28-FEB-10:09 | 7.12 | 6.63 |
March | 0.458273E+11 | 92030.84 | 13-MAR-06:03 | -0.5 | -3.7 | 0.614820E+10 | 7499.31 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.444688E+11 | 95881.47 | 17-APR-06:11 | 11.70 | 10.63 | 0.546653E+10 | 7499.33 | 26-APR-09:00 | 16.10 | 12.59 |
May | 0.464486E+11 | 92279.17 | 22-MAY-06:11 | 15.70 | 12.63 | 0.592307E+10 | 8119.64 | 30-MAY-09:30 | 26.95 | 17.37 |
June | 0.353159E+11 | 98029.21 | 09-JUN-06:11 | 15.97 | 10.39 | 0.693404E+10 | 11859.19 | 26-JUN-13:00 | 27.20 | 20.21 |
July | 0.154372E+11 | 103447.65 | 11-JUL-06:11 | 21.13 | 15.72 | 0.791434E+10 | 12283.76 | 21-JUL-13:00 | 29.40 | 25.29 |
August | 0.283022E+11 | 104272.12 | 19-AUG-06:11 | 20.37 | 16.31 | 0.837871E+10 | 12685.10 | 18-AUG-13:00 | 20.37 | 16.31 |
September | 0.414255E+11 | 105497.14 | 15-SEP-06:11 | 15.73 | 12.49 | 0.621364E+10 | 11581.14 | 07-SEP-13:00 | 15.73 | 12.49 |
October | 0.538080E+11 | 99395.63 | 23-OCT-06:11 | 12.97 | 11.69 | 0.571020E+10 | 9384.08 | 06-OCT-08:20 | 12.97 | 11.69 |
November | 0.490538E+11 | 97914.50 | 13-NOV-07:05 | 6.10 | 5.08 | 0.563475E+10 | 7499.38 | 09-NOV-14:00 | 6.10 | 5.08 |
December | 0.456338E+11 | 94157.13 | 18-DEC-07:03 | 0.68 | -1.2 | 0.548709E+10 | 7499.18 | 18-DEC-14:39 | 6.67 | 2.71 |
Annual Sum or Average | 0.476828E+12 | 0.746295E+11 | ||||||||
Minimum of Months | 0.154372E+11 | 89894.06 | -11.6 | -13.1 | 0.514789E+10 | 7499.18 | 6.10 | 2.71 | ||
Maximum of Months | 0.538080E+11 | 105497.14 | 21.13 | 16.31 | 0.837871E+10 | 12685.10 | 29.40 | 25.29 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293807E+11 | 72910.03 | 24-JAN-06:03 | 11.10 | 11.10 | 0.503801E+10 | 6734.94 | 03-JAN-10:50 | 11.10 | 11.10 |
February | 0.301983E+11 | 79982.25 | 21-FEB-05:11 | 2.20 | 1.34 | 0.458914E+10 | 6734.77 | 01-FEB-10:20 | 2.20 | 1.34 |
March | 0.437624E+11 | 81112.99 | 06-MAR-05:11 | 8.70 | 8.70 | 0.549861E+10 | 6734.84 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.483522E+11 | 81410.98 | 11-APR-04:12 | 6.10 | 1.61 | 0.488141E+10 | 6734.84 | 26-APR-09:00 | 16.10 | 12.59 |
May | 0.471005E+11 | 88559.24 | 30-MAY-04:13 | 17.80 | 14.10 | 0.528558E+10 | 6941.82 | 30-MAY-09:30 | 26.95 | 17.37 |
June | 0.615107E+11 | 87628.02 | 12-JUN-04:13 | 18.70 | 17.72 | 0.527196E+10 | 6818.12 | 22-JUN-13:09 | 28.58 | 17.26 |
July | 0.784549E+11 | 86502.54 | 24-JUL-04:23 | 20.85 | 20.22 | 0.490374E+10 | 6790.85 | 11-JUL-13:00 | 20.85 | 20.22 |
August | 0.841589E+11 | 86938.52 | 07-AUG-04:23 | 18.85 | 16.95 | 0.550243E+10 | 6769.06 | 14-AUG-09:39 | 27.60 | 22.96 |
September | 0.534300E+11 | 88028.27 | 15-SEP-04:13 | 16.50 | 12.91 | 0.488600E+10 | 6734.98 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.492566E+11 | 86643.08 | 10-OCT-04:12 | 10.40 | 8.15 | 0.507855E+10 | 6735.13 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.420548E+11 | 87744.75 | 13-NOV-05:11 | 5.60 | 4.52 | 0.503108E+10 | 6734.88 | 09-NOV-14:00 | 5.60 | 4.52 |
December | 0.404031E+11 | 82309.81 | 26-DEC-05:12 | 5.77 | 4.97 | 0.489868E+10 | 6734.75 | 20-DEC-10:20 | 5.77 | 4.97 |
Annual Sum or Average | 0.608063E+12 | 0.608652E+11 | ||||||||
Minimum of Months | 0.293807E+11 | 72910.03 | 2.20 | 1.34 | 0.458914E+10 | 6734.75 | 2.20 | 1.34 | ||
Maximum of Months | 0.841589E+11 | 88559.24 | 20.85 | 20.22 | 0.550243E+10 | 6941.82 | 28.58 | 22.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186930E+11 | 22518.54 | 17-JAN-19:20 | 3.67 | 1.50 | 0.444690E+10 | 6734.64 | 20-JAN-14:50 | 7.70 | 3.92 |
February | 0.195047E+11 | 23967.44 | 03-FEB-10:00 | -5.0 | -7.6 | 0.421599E+10 | 6734.77 | 03-FEB-10:09 | -4.6 | -7.3 |
March | 0.266370E+11 | 66307.67 | 29-MAR-05:02 | 2.12 | 0.18 | 0.537078E+10 | 6734.76 | 23-MAR-09:09 | 2.12 | 0.18 |
April | 0.294085E+11 | 72524.98 | 10-APR-05:02 | 15.10 | 13.73 | 0.482516E+10 | 6738.31 | 20-APR-13:50 | 8.90 | 7.51 |
May | 0.377877E+11 | 73639.92 | 31-MAY-04:12 | 16.10 | 14.49 | 0.527064E+10 | 6758.83 | 30-MAY-09:30 | 16.10 | 14.49 |
June | 0.423750E+11 | 75124.62 | 12-JUN-04:12 | 18.70 | 17.72 | 0.526495E+10 | 6734.89 | 26-JUN-09:20 | 25.37 | 19.69 |
July | 0.436802E+11 | 72336.46 | 01-JUL-04:12 | 20.00 | 19.55 | 0.489115E+10 | 6734.86 | 17-JUL-09:20 | 27.97 | 21.33 |
August | 0.464566E+11 | 78511.84 | 07-AUG-04:14 | 18.67 | 17.05 | 0.549508E+10 | 6734.86 | 21-AUG-09:20 | 26.33 | 19.26 |
September | 0.385968E+11 | 75805.29 | 18-SEP-04:12 | 17.07 | 16.12 | 0.487351E+10 | 6734.96 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.350086E+11 | 73185.76 | 17-OCT-05:02 | 10.10 | 8.56 | 0.505507E+10 | 6735.06 | 16-OCT-09:09 | 10.10 | 8.56 |
November | 0.248060E+11 | 67760.32 | 10-NOV-06:02 | 14.60 | 14.60 | 0.488713E+10 | 6772.51 | 17-NOV-10:30 | 11.70 | 7.59 |
December | 0.217996E+11 | 26240.87 | 29-DEC-14:40 | 3.70 | 2.52 | 0.461446E+10 | 6734.74 | 22-DEC-10:39 | 3.70 | 2.52 |
Annual Sum or Average | 0.384754E+12 | 0.592108E+11 | ||||||||
Minimum of Months | 0.186930E+11 | 22518.54 | -5.0 | -7.6 | 0.421599E+10 | 6734.64 | -4.6 | -7.3 | ||
Maximum of Months | 0.464566E+11 | 78511.84 | 20.00 | 19.55 | 0.549508E+10 | 6772.51 | 27.97 | 21.33 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133327E+11 | 15847.83 | 20-JAN-17:00 | 5.60 | 3.19 | 0.403513E+10 | 6335.18 | 20-JAN-14:00 | 5.60 | 3.19 |
February | 0.132875E+11 | 15925.90 | 17-FEB-17:00 | 5.60 | 1.58 | 0.371331E+10 | 6386.12 | 17-FEB-14:00 | 5.60 | 1.58 |
March | 0.209668E+11 | 27751.51 | 29-MAR-16:00 | 7.20 | 4.88 | 0.490519E+10 | 6734.67 | 29-MAR-13:20 | 7.20 | 4.88 |
April | 0.251696E+11 | 68144.99 | 08-APR-05:03 | 14.32 | 11.97 | 0.463231E+10 | 6734.77 | 07-APR-13:20 | 14.32 | 11.97 |
May | 0.358897E+11 | 75039.19 | 30-MAY-04:13 | 17.80 | 14.10 | 0.522845E+10 | 6808.94 | 30-MAY-09:30 | 26.95 | 17.37 |
June | 0.445307E+11 | 76108.61 | 12-JUN-04:12 | 18.70 | 17.72 | 0.526354E+10 | 6753.33 | 22-JUN-13:09 | 28.58 | 17.26 |
July | 0.481889E+11 | 76703.10 | 05-JUL-04:13 | 20.60 | 19.57 | 0.489602E+10 | 6734.81 | 12-JUL-13:09 | 28.80 | 18.62 |
August | 0.502079E+11 | 81087.58 | 28-AUG-04:14 | 19.80 | 17.37 | 0.549640E+10 | 6736.33 | 22-AUG-13:00 | 19.80 | 17.37 |
September | 0.372762E+11 | 74064.39 | 06-SEP-04:12 | 21.30 | 18.82 | 0.485408E+10 | 6734.92 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.293867E+11 | 70561.74 | 06-OCT-05:03 | 19.40 | 18.22 | 0.492958E+10 | 6735.01 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.177833E+11 | 26873.67 | 03-NOV-16:00 | 15.00 | 10.26 | 0.441287E+10 | 6734.72 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.147628E+11 | 15562.28 | 20-DEC-17:00 | 6.70 | 3.52 | 0.399346E+10 | 6354.94 | 20-DEC-14:00 | 6.70 | 3.52 |
Annual Sum or Average | 0.350783E+12 | 0.563603E+11 | ||||||||
Minimum of Months | 0.132875E+11 | 15562.28 | 5.60 | 1.58 | 0.371331E+10 | 6335.18 | 5.60 | 1.58 | ||
Maximum of Months | 0.502079E+11 | 81087.58 | 21.30 | 19.57 | 0.549640E+10 | 6808.94 | 28.80 | 18.62 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186670E+10 | 2319.05 | 24-JAN-06:03 | 11.10 | 11.10 | 0.535150E+09 | 821.01 | 20-JAN-14:50 | 11.10 | 11.10 |
February | 0.189101E+10 | 2700.25 | 20-FEB-13:22 | 9.15 | 4.45 | 0.492504E+09 | 840.42 | 24-FEB-14:20 | 9.03 | 2.95 |
March | 0.344029E+10 | 6208.57 | 27-MAR-13:30 | 20.85 | 16.76 | 0.658666E+09 | 845.63 | 27-MAR-09:09 | 20.85 | 16.76 |
April | 0.504525E+10 | 7373.02 | 26-APR-13:40 | 18.30 | 12.75 | 0.603618E+09 | 845.64 | 26-APR-09:00 | 18.30 | 12.75 |
May | 0.668690E+10 | 15380.69 | 29-MAY-14:52 | 25.60 | 17.03 | 0.662152E+09 | 883.35 | 30-MAY-09:30 | 26.95 | 17.37 |
June | 0.105049E+11 | 15655.24 | 25-JUN-12:23 | 26.40 | 23.04 | 0.662501E+09 | 865.47 | 22-JUN-13:09 | 26.40 | 23.04 |
July | 0.136624E+11 | 16455.91 | 04-JUL-16:32 | 25.37 | 18.16 | 0.616929E+09 | 865.38 | 11-JUL-13:00 | 28.90 | 17.83 |
August | 0.139306E+11 | 15945.45 | 13-AUG-15:01 | 30.50 | 20.85 | 0.691432E+09 | 850.96 | 14-AUG-09:39 | 27.60 | 22.96 |
September | 0.745110E+10 | 15835.85 | 04-SEP-13:31 | 26.10 | 18.42 | 0.612469E+09 | 845.65 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.532192E+10 | 8308.87 | 06-OCT-05:03 | 19.40 | 18.22 | 0.631702E+09 | 845.67 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.314925E+10 | 4782.21 | 03-NOV-13:30 | 17.50 | 10.63 | 0.605385E+09 | 845.64 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.257180E+10 | 3275.42 | 26-DEC-13:30 | 9.45 | 5.02 | 0.560137E+09 | 845.62 | 18-DEC-14:30 | 9.45 | 5.02 |
Annual Sum or Average | 0.755222E+11 | 0.733265E+10 | ||||||||
Minimum of Months | 0.186670E+10 | 2319.05 | 9.15 | 4.45 | 0.492504E+09 | 821.01 | 9.03 | 2.95 | ||
Maximum of Months | 0.139306E+11 | 16455.91 | 30.50 | 23.04 | 0.691432E+09 | 883.35 | 28.90 | 23.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140354E+10 | 4689.17 | 19-JAN-09:30 | 6.10 | 3.63 | 0.361540E+09 | 544.95 | 05-JAN-10:30 | 6.10 | 3.63 |
February | 0.152239E+10 | 6162.93 | 22-FEB-09:20 | 0.20 | -3.3 | 0.337887E+09 | 544.95 | 01-FEB-10:20 | 0.20 | -3.3 |
March | 0.330725E+10 | 11558.33 | 26-MAR-08:13 | 9.07 | 8.23 | 0.428761E+09 | 544.95 | 02-MAR-10:39 | 9.07 | 8.23 |
April | 0.464214E+10 | 19639.11 | 16-APR-07:33 | 12.40 | 10.64 | 0.388085E+09 | 544.97 | 26-APR-09:50 | 16.38 | 12.56 |
May | 0.654620E+10 | 23441.02 | 29-MAY-07:31 | 23.17 | 16.45 | 0.427348E+09 | 614.49 | 30-MAY-09:30 | 26.95 | 17.37 |
June | 0.850351E+10 | 21283.11 | 25-JUN-09:02 | 25.68 | 23.57 | 0.427131E+09 | 554.74 | 22-JUN-13:09 | 25.68 | 23.57 |
July | 0.107730E+11 | 23512.74 | 02-JUL-07:21 | 23.60 | 20.87 | 0.397750E+09 | 553.11 | 12-JUL-09:00 | 27.80 | 18.38 |
August | 0.117769E+11 | 20794.32 | 13-AUG-09:42 | 28.72 | 19.36 | 0.445782E+09 | 550.84 | 14-AUG-09:39 | 27.60 | 22.96 |
September | 0.682545E+10 | 23787.10 | 04-SEP-08:11 | 23.17 | 18.66 | 0.395351E+09 | 545.81 | 06-SEP-09:30 | 26.15 | 19.35 |
October | 0.501887E+10 | 19035.39 | 15-OCT-09:13 | 17.57 | 12.46 | 0.408437E+09 | 545.00 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.246834E+10 | 6850.45 | 02-NOV-08:50 | 10.82 | 5.71 | 0.393979E+09 | 544.96 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.181427E+10 | 5168.60 | 20-DEC-09:30 | 7.20 | 4.58 | 0.363687E+09 | 544.95 | 20-DEC-10:20 | 8.50 | 5.06 |
Annual Sum or Average | 0.646019E+11 | 0.477574E+10 | ||||||||
Minimum of Months | 0.140354E+10 | 4689.17 | 0.20 | -3.3 | 0.337887E+09 | 544.95 | 0.20 | -3.3 | ||
Maximum of Months | 0.117769E+11 | 23787.10 | 28.72 | 23.57 | 0.445782E+09 | 614.49 | 27.80 | 23.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.397648E+10 | 16956.50 | 29-JAN-13:33 | 2.60 | -0.9 | 0.571840E+09 | 846.06 | 19-JAN-14:20 | 2.60 | -0.9 |
February | 0.467709E+10 | 24279.52 | 20-FEB-13:22 | 9.15 | 4.45 | 0.534840E+09 | 846.26 | 22-FEB-14:50 | 4.50 | -1.0 |
March | 0.747169E+10 | 18375.73 | 01-MAR-13:05 | 13.90 | 6.68 | 0.663354E+09 | 847.36 | 28-MAR-13:09 | 13.80 | 8.65 |
April | 0.758271E+10 | 18022.71 | 16-APR-11:33 | 20.03 | 12.96 | 0.600642E+09 | 849.80 | 07-APR-13:50 | 20.03 | 12.96 |
May | 0.823411E+10 | 24439.06 | 29-MAY-12:12 | 28.33 | 17.95 | 0.661247E+09 | 876.38 | 30-MAY-09:30 | 26.95 | 17.37 |
June | 0.115662E+11 | 23486.03 | 25-JUN-12:23 | 26.40 | 23.04 | 0.662534E+09 | 867.13 | 22-JUN-13:09 | 26.40 | 23.04 |
July | 0.152404E+11 | 24877.87 | 30-JUL-13:02 | 27.20 | 24.02 | 0.616981E+09 | 861.64 | 11-JUL-13:00 | 27.20 | 24.02 |
August | 0.183617E+11 | 25083.90 | 27-AUG-12:22 | 28.05 | 22.61 | 0.692835E+09 | 891.65 | 30-AUG-13:50 | 28.62 | 15.51 |
September | 0.125280E+11 | 27099.98 | 04-SEP-12:11 | 26.10 | 17.96 | 0.615413E+09 | 910.68 | 28-SEP-13:09 | 22.98 | 13.55 |
October | 0.125938E+11 | 25103.98 | 09-OCT-13:42 | 13.80 | 8.02 | 0.637687E+09 | 922.50 | 04-OCT-13:30 | 13.80 | 8.02 |
November | 0.652375E+10 | 19177.94 | 02-NOV-12:40 | 15.40 | 8.14 | 0.614978E+09 | 882.52 | 02-NOV-13:09 | 15.68 | 8.29 |
December | 0.541343E+10 | 25640.58 | 17-DEC-12:52 | 12.20 | 4.95 | 0.575396E+09 | 846.42 | 21-DEC-14:39 | 3.30 | -1.8 |
Annual Sum or Average | 0.114169E+12 | 0.744775E+10 | ||||||||
Minimum of Months | 0.397648E+10 | 16956.50 | 2.60 | -0.9 | 0.534840E+09 | 846.06 | 2.60 | -1.8 | ||
Maximum of Months | 0.183617E+11 | 27099.98 | 28.33 | 24.02 | 0.692835E+09 | 922.50 | 28.62 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202143E+10 | 7015.37 | 17-JAN-15:30 | 10.30 | 4.98 | 0.378732E+09 | 544.95 | 20-JAN-10:09 | 4.60 | 1.17 |
February | 0.263055E+10 | 18365.89 | 20-FEB-15:23 | 7.75 | 4.55 | 0.356387E+09 | 544.95 | 01-FEB-10:39 | 7.75 | 4.55 |
March | 0.633808E+10 | 19600.80 | 26-MAR-16:32 | 10.97 | 9.75 | 0.444267E+09 | 544.96 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.878959E+10 | 26497.88 | 09-APR-16:22 | 16.65 | 13.97 | 0.396096E+09 | 544.97 | 26-APR-09:50 | 16.38 | 12.56 |
May | 0.819500E+10 | 24633.72 | 29-MAY-14:52 | 25.60 | 17.03 | 0.428647E+09 | 563.18 | 30-MAY-09:30 | 26.95 | 17.37 |
June | 0.118460E+11 | 27056.81 | 18-JUN-15:51 | 25.60 | 22.09 | 0.428004E+09 | 556.87 | 22-JUN-13:09 | 28.58 | 17.26 |
July | 0.143650E+11 | 30289.21 | 02-JUL-16:01 | 24.90 | 20.78 | 0.398505E+09 | 551.73 | 11-JUL-13:00 | 28.90 | 17.83 |
August | 0.167448E+11 | 26876.38 | 13-AUG-15:41 | 30.10 | 20.54 | 0.446818E+09 | 549.17 | 14-AUG-09:39 | 27.60 | 22.96 |
September | 0.838252E+10 | 29208.56 | 10-SEP-15:31 | 23.67 | 13.25 | 0.396051E+09 | 544.97 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.787111E+10 | 25729.06 | 09-OCT-14:22 | 13.60 | 7.85 | 0.411519E+09 | 544.99 | 04-OCT-13:30 | 13.60 | 7.85 |
November | 0.453714E+10 | 14995.92 | 10-NOV-06:02 | 14.60 | 14.60 | 0.405939E+09 | 544.97 | 09-NOV-14:00 | 14.60 | 14.60 |
December | 0.403604E+10 | 20466.67 | 17-DEC-14:12 | 12.20 | 5.36 | 0.395505E+09 | 544.95 | 29-DEC-14:00 | 3.90 | 3.16 |
Annual Sum or Average | 0.957573E+11 | 0.488647E+10 | ||||||||
Minimum of Months | 0.202143E+10 | 7015.37 | 7.75 | 4.55 | 0.356387E+09 | 544.95 | 3.90 | 1.17 | ||
Maximum of Months | 0.167448E+11 | 30289.21 | 30.10 | 22.09 | 0.446818E+09 | 563.18 | 28.90 | 22.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.426205E+09 | 1729.13 | 20-JAN-12:50 | 6.10 | 2.70 | 0.469284E+09 | 702.40 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.493031E+09 | 1872.53 | 01-FEB-13:40 | 8.50 | 3.99 | 0.429215E+09 | 712.32 | 24-FEB-14:00 | 8.30 | 2.27 |
March | 0.187884E+10 | 3137.45 | 28-MAR-13:50 | 13.40 | 8.46 | 0.565925E+09 | 845.61 | 28-MAR-13:20 | 13.40 | 8.46 |
April | 0.291960E+10 | 5529.13 | 07-APR-14:00 | 26.10 | 15.95 | 0.560860E+09 | 845.64 | 10-APR-13:20 | 20.20 | 10.17 |
May | 0.535332E+10 | 11207.89 | 31-MAY-05:02 | 16.38 | 14.99 | 0.654594E+09 | 857.55 | 30-MAY-09:30 | 16.38 | 14.99 |
June | 0.801531E+10 | 11233.61 | 22-JUN-05:02 | 22.88 | 15.44 | 0.661574E+09 | 846.60 | 23-JUN-13:20 | 29.43 | 19.15 |
July | 0.916933E+10 | 14693.85 | 09-JUL-14:31 | 28.70 | 24.38 | 0.616061E+09 | 846.73 | 11-JUL-13:00 | 28.90 | 17.83 |
August | 0.904588E+10 | 14217.05 | 13-AUG-15:01 | 30.50 | 20.85 | 0.690658E+09 | 845.65 | 08-AUG-13:30 | 30.50 | 20.85 |
September | 0.553715E+10 | 10689.75 | 02-SEP-05:02 | 22.12 | 16.30 | 0.607261E+09 | 845.65 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.366193E+10 | 5762.10 | 05-OCT-14:00 | 23.30 | 18.86 | 0.607630E+09 | 845.64 | 16-OCT-09:30 | 17.25 | 14.25 |
November | 0.161231E+10 | 2646.01 | 03-NOV-14:00 | 17.80 | 10.67 | 0.519689E+09 | 845.61 | 03-NOV-13:50 | 17.80 | 10.67 |
December | 0.685849E+09 | 1780.77 | 21-DEC-13:30 | 3.05 | -1.7 | 0.456547E+09 | 709.91 | 20-DEC-14:09 | 3.05 | -1.7 |
Annual Sum or Average | 0.487988E+11 | 0.683930E+10 | ||||||||
Minimum of Months | 0.426205E+09 | 1729.13 | 3.05 | -1.7 | 0.429215E+09 | 702.40 | 3.05 | -1.7 | ||
Maximum of Months | 0.916933E+10 | 14693.85 | 30.50 | 24.38 | 0.690658E+09 | 857.55 | 30.50 | 20.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.386037E+09 | 3132.24 | 19-JAN-11:05 | 7.70 | 4.65 | 0.232316E+09 | 548.49 | 19-JAN-11:09 | 7.70 | 4.65 |
February | 0.560221E+09 | 4422.36 | 03-FEB-10:00 | -5.0 | -7.6 | 0.219066E+09 | 548.49 | 03-FEB-11:09 | -2.7 | -5.9 |
March | 0.198870E+10 | 9734.62 | 29-MAR-10:05 | 7.07 | 3.67 | 0.295933E+09 | 548.49 | 23-MAR-10:09 | 7.07 | 3.67 |
April | 0.350707E+10 | 13027.10 | 16-APR-08:53 | 15.60 | 11.57 | 0.277464E+09 | 550.78 | 07-APR-12:09 | 15.60 | 11.57 |
May | 0.604578E+10 | 24362.07 | 28-MAY-08:51 | 20.60 | 12.82 | 0.313256E+09 | 548.52 | 15-MAY-14:09 | 20.60 | 12.82 |
June | 0.741051E+10 | 23958.41 | 04-JUN-09:11 | 23.67 | 12.90 | 0.314924E+09 | 548.51 | 22-JUN-12:09 | 28.30 | 17.33 |
July | 0.844792E+10 | 26146.14 | 02-JUL-08:51 | 25.60 | 21.66 | 0.294392E+09 | 548.52 | 12-JUL-12:09 | 28.90 | 18.27 |
August | 0.955428E+10 | 23391.20 | 20-AUG-09:02 | 22.07 | 14.87 | 0.328756E+09 | 549.85 | 22-AUG-10:09 | 28.48 | 18.44 |
September | 0.576661E+10 | 25206.18 | 04-SEP-09:01 | 24.18 | 18.48 | 0.290793E+09 | 551.58 | 01-SEP-14:09 | 24.18 | 18.48 |
October | 0.404526E+10 | 17922.88 | 15-OCT-10:22 | 18.85 | 13.18 | 0.297250E+09 | 548.50 | 02-OCT-10:09 | 18.85 | 13.18 |
November | 0.129064E+10 | 6808.20 | 02-NOV-10:05 | 12.48 | 6.40 | 0.265838E+09 | 548.49 | 09-NOV-15:09 | 13.80 | 12.65 |
December | 0.569170E+09 | 3466.61 | 20-DEC-11:05 | 8.90 | 5.16 | 0.233266E+09 | 548.48 | 20-DEC-11:09 | 8.90 | 5.16 |
Annual Sum or Average | 0.495722E+11 | 0.336325E+10 | ||||||||
Minimum of Months | 0.386037E+09 | 3132.24 | -5.0 | -7.6 | 0.219066E+09 | 548.48 | -2.7 | -5.9 | ||
Maximum of Months | 0.955428E+10 | 26146.14 | 25.60 | 21.66 | 0.328756E+09 | 551.58 | 28.90 | 18.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305580E+10 | 17281.72 | 05-JAN-13:10 | -2.1 | -5.6 | 0.539343E+09 | 882.77 | 05-JAN-10:20 | -2.1 | -5.6 |
February | 0.389139E+10 | 23252.54 | 19-FEB-12:43 | 8.22 | 4.22 | 0.510149E+09 | 865.64 | 17-FEB-14:00 | 8.22 | 4.22 |
March | 0.644519E+10 | 18417.94 | 01-MAR-13:20 | 13.90 | 6.52 | 0.633900E+09 | 853.51 | 01-MAR-14:09 | 13.62 | 5.85 |
April | 0.606632E+10 | 17318.35 | 07-APR-12:30 | 26.15 | 15.90 | 0.581219E+09 | 852.64 | 07-APR-13:50 | 26.20 | 16.03 |
May | 0.746852E+10 | 23029.11 | 28-MAY-14:51 | 26.70 | 15.43 | 0.655959E+09 | 859.70 | 30-MAY-13:39 | 29.60 | 17.29 |
June | 0.949078E+10 | 22796.45 | 18-JUN-12:23 | 26.70 | 22.66 | 0.661757E+09 | 846.49 | 19-JUN-13:20 | 34.80 | 23.85 |
July | 0.111808E+11 | 23639.78 | 09-JUL-11:12 | 29.60 | 25.14 | 0.616519E+09 | 856.52 | 11-JUL-13:30 | 28.35 | 17.93 |
August | 0.143308E+11 | 24958.40 | 20-AUG-12:22 | 27.25 | 15.63 | 0.692761E+09 | 904.79 | 30-AUG-13:39 | 28.33 | 15.54 |
September | 0.115710E+11 | 27091.50 | 04-SEP-11:41 | 26.02 | 17.75 | 0.615046E+09 | 961.49 | 28-SEP-13:20 | 23.17 | 13.55 |
October | 0.121931E+11 | 26639.91 | 15-OCT-12:21 | 20.30 | 13.25 | 0.636026E+09 | 956.70 | 04-OCT-13:30 | 20.30 | 13.25 |
November | 0.550763E+10 | 19576.99 | 02-NOV-13:05 | 15.68 | 8.29 | 0.592158E+09 | 919.06 | 02-NOV-13:20 | 15.77 | 8.37 |
December | 0.390362E+10 | 23510.94 | 17-DEC-13:02 | 12.20 | 5.01 | 0.542405E+09 | 847.85 | 15-DEC-14:09 | 12.20 | 5.01 |
Annual Sum or Average | 0.951050E+11 | 0.727724E+10 | ||||||||
Minimum of Months | 0.305580E+10 | 17281.72 | -2.1 | -5.6 | 0.510149E+09 | 846.49 | -2.1 | -5.6 | ||
Maximum of Months | 0.143308E+11 | 27091.50 | 29.60 | 25.14 | 0.692761E+09 | 961.49 | 34.80 | 23.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.689562E+09 | 3973.02 | 31-JAN-16:00 | -1.1 | -5.7 | 0.320546E+09 | 544.94 | 31-JAN-14:50 | -1.1 | -5.7 |
February | 0.923383E+09 | 6228.23 | 24-FEB-15:30 | 8.05 | 2.04 | 0.297383E+09 | 544.94 | 03-FEB-14:00 | 8.05 | 2.04 |
March | 0.279425E+10 | 11048.94 | 29-MAR-16:00 | 7.20 | 4.88 | 0.393821E+09 | 544.95 | 03-MAR-14:20 | 7.20 | 4.88 |
April | 0.404666E+10 | 25277.47 | 09-APR-16:41 | 16.28 | 13.85 | 0.375685E+09 | 545.15 | 20-APR-13:50 | 8.90 | 7.51 |
May | 0.624063E+10 | 24739.51 | 14-MAY-16:11 | 13.30 | 9.05 | 0.425015E+09 | 548.03 | 30-MAY-09:30 | 26.95 | 17.37 |
June | 0.866455E+10 | 26770.59 | 18-JUN-17:01 | 24.72 | 21.89 | 0.427274E+09 | 550.28 | 22-JUN-15:50 | 29.60 | 17.59 |
July | 0.933739E+10 | 27168.19 | 02-JUL-16:11 | 24.80 | 20.74 | 0.397835E+09 | 544.98 | 14-JUL-09:30 | 29.75 | 21.24 |
August | 0.106076E+11 | 25440.16 | 20-AUG-16:21 | 25.30 | 17.31 | 0.446065E+09 | 544.99 | 08-AUG-13:30 | 25.30 | 17.31 |
September | 0.625421E+10 | 26526.06 | 10-SEP-15:41 | 23.48 | 13.06 | 0.393899E+09 | 544.97 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.479002E+10 | 22757.47 | 15-OCT-14:21 | 20.85 | 13.17 | 0.401659E+09 | 544.98 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.158430E+10 | 7151.22 | 03-NOV-15:30 | 16.10 | 10.65 | 0.355234E+09 | 544.96 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.924639E+09 | 3888.22 | 08-DEC-15:30 | 6.40 | 2.12 | 0.316203E+09 | 544.94 | 18-DEC-14:39 | 6.67 | 2.71 |
Annual Sum or Average | 0.568573E+11 | 0.455062E+10 | ||||||||
Minimum of Months | 0.689562E+09 | 3888.22 | -1.1 | -5.7 | 0.297383E+09 | 544.94 | -1.1 | -5.7 | ||
Maximum of Months | 0.106076E+11 | 27168.19 | 25.30 | 21.89 | 0.446065E+09 | 550.28 | 29.75 | 21.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181576E+09 | 1468.98 | 20-JAN-15:00 | 7.80 | 3.97 | 0.464620E+09 | 660.35 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.205663E+09 | 1495.93 | 24-FEB-15:40 | 7.97 | 1.96 | 0.422473E+09 | 664.79 | 17-FEB-14:00 | 7.97 | 1.96 |
March | 0.119292E+10 | 2927.67 | 28-MAR-14:00 | 13.30 | 8.41 | 0.540677E+09 | 845.61 | 28-MAR-13:20 | 13.30 | 8.41 |
April | 0.248764E+10 | 6260.88 | 07-APR-14:00 | 26.10 | 15.95 | 0.536260E+09 | 845.63 | 07-APR-13:20 | 26.10 | 15.95 |
May | 0.518643E+10 | 16917.02 | 29-MAY-14:02 | 26.02 | 17.36 | 0.643424E+09 | 858.51 | 30-MAY-09:30 | 26.95 | 17.37 |
June | 0.829273E+10 | 13184.16 | 22-JUN-05:02 | 22.88 | 15.44 | 0.661022E+09 | 852.29 | 22-JUN-13:09 | 28.58 | 17.26 |
July | 0.981577E+10 | 16953.76 | 09-JUL-14:42 | 27.95 | 24.21 | 0.616273E+09 | 845.85 | 07-JUL-13:00 | 27.95 | 24.21 |
August | 0.956707E+10 | 16998.49 | 13-AUG-15:01 | 30.50 | 20.85 | 0.690391E+09 | 845.93 | 22-AUG-13:00 | 31.10 | 18.52 |
September | 0.542359E+10 | 12579.25 | 02-SEP-05:02 | 22.12 | 16.30 | 0.601591E+09 | 845.65 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.315194E+10 | 6116.14 | 04-OCT-13:40 | 24.60 | 18.82 | 0.583904E+09 | 845.62 | 04-OCT-13:30 | 24.60 | 18.82 |
November | 0.977838E+09 | 2470.64 | 02-NOV-13:50 | 16.02 | 8.62 | 0.489103E+09 | 831.04 | 03-NOV-13:00 | 17.80 | 10.67 |
December | 0.166195E+09 | 1453.79 | 20-DEC-13:50 | 9.90 | 5.86 | 0.448748E+09 | 656.32 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.466494E+11 | 0.669848E+10 | ||||||||
Minimum of Months | 0.166195E+09 | 1453.79 | 7.80 | 1.96 | 0.422473E+09 | 656.32 | 7.80 | 1.96 | ||
Maximum of Months | 0.981577E+10 | 16998.49 | 30.50 | 24.21 | 0.690391E+09 | 858.51 | 31.10 | 24.21 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302674E+09 | 1298.86 | 19-JAN-10:30 | 7.80 | 4.48 | 0.307501E+09 | 528.87 | 19-JAN-10:39 | 7.80 | 4.59 |
February | 0.448695E+09 | 1710.25 | 22-FEB-10:10 | 0.87 | -3.0 | 0.284821E+09 | 544.95 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.163096E+10 | 7312.37 | 29-MAR-09:30 | 6.15 | 3.19 | 0.388086E+09 | 544.95 | 29-MAR-13:20 | 7.80 | 5.34 |
April | 0.325597E+10 | 11443.23 | 28-APR-08:50 | 15.82 | 8.80 | 0.368989E+09 | 544.97 | 26-APR-09:50 | 15.82 | 8.80 |
May | 0.609242E+10 | 25761.06 | 29-MAY-08:61 | 24.27 | 16.71 | 0.421018E+09 | 603.00 | 30-MAY-09:30 | 26.95 | 17.37 |
June | 0.783138E+10 | 23120.87 | 25-JUN-09:02 | 25.68 | 23.57 | 0.426764E+09 | 547.43 | 22-JUN-13:09 | 25.68 | 23.57 |
July | 0.917269E+10 | 23741.47 | 02-JUL-09:02 | 25.68 | 21.69 | 0.397680E+09 | 546.86 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.101938E+11 | 23612.51 | 20-AUG-09:12 | 22.43 | 14.98 | 0.445676E+09 | 546.58 | 22-AUG-09:30 | 28.05 | 18.47 |
September | 0.587374E+10 | 23117.99 | 04-SEP-09:12 | 24.47 | 18.42 | 0.392010E+09 | 546.14 | 06-SEP-09:50 | 26.52 | 19.55 |
October | 0.371600E+10 | 12764.76 | 15-OCT-09:13 | 17.57 | 12.46 | 0.397760E+09 | 544.99 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.101681E+10 | 3754.22 | 02-NOV-09:40 | 11.83 | 6.09 | 0.338622E+09 | 544.95 | 08-NOV-14:00 | 13.30 | 11.09 |
December | 0.416055E+09 | 1299.59 | 20-DEC-10:00 | 8.30 | 5.00 | 0.298190E+09 | 529.69 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.499512E+11 | 0.446711E+10 | ||||||||
Minimum of Months | 0.302674E+09 | 1298.86 | 0.87 | -3.0 | 0.284821E+09 | 528.87 | 1.13 | -2.8 | ||
Maximum of Months | 0.101938E+11 | 25761.06 | 25.68 | 23.57 | 0.445676E+09 | 603.00 | 30.60 | 23.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226724E+10 | 14286.54 | 19-JAN-13:30 | 9.40 | 3.94 | 0.526587E+09 | 845.64 | 26-JAN-14:39 | 4.40 | 1.05 |
February | 0.289299E+10 | 14957.29 | 22-FEB-13:30 | 4.45 | -1.1 | 0.492439E+09 | 845.69 | 02-FEB-14:30 | 4.45 | -1.1 |
March | 0.530825E+10 | 18850.82 | 01-MAR-13:30 | 13.90 | 6.36 | 0.609155E+09 | 846.25 | 03-MAR-14:50 | 15.00 | 8.43 |
April | 0.542455E+10 | 19220.75 | 09-APR-13:32 | 19.40 | 15.47 | 0.562528E+09 | 846.30 | 07-APR-13:39 | 19.40 | 15.47 |
May | 0.727886E+10 | 26583.92 | 29-MAY-13:22 | 26.65 | 17.22 | 0.645985E+09 | 878.87 | 30-MAY-12:09 | 29.50 | 17.65 |
June | 0.976681E+10 | 24919.70 | 25-JUN-12:23 | 26.40 | 23.04 | 0.660989E+09 | 862.69 | 22-JUN-13:09 | 26.40 | 23.04 |
July | 0.118869E+11 | 25201.23 | 30-JUL-12:32 | 26.83 | 23.77 | 0.616605E+09 | 855.02 | 11-JUL-13:09 | 26.83 | 23.77 |
August | 0.149109E+11 | 27433.04 | 20-AUG-13:11 | 28.17 | 15.57 | 0.691985E+09 | 886.79 | 30-AUG-13:30 | 28.05 | 15.56 |
September | 0.114197E+11 | 27188.41 | 04-SEP-12:32 | 26.10 | 18.14 | 0.609967E+09 | 933.24 | 28-SEP-13:30 | 23.35 | 13.54 |
October | 0.110718E+11 | 26052.97 | 15-OCT-12:32 | 20.40 | 13.11 | 0.622241E+09 | 933.10 | 04-OCT-13:30 | 20.40 | 13.11 |
November | 0.413871E+10 | 20133.78 | 02-NOV-13:10 | 15.68 | 8.29 | 0.566472E+09 | 865.00 | 02-NOV-13:20 | 15.77 | 8.37 |
December | 0.262693E+10 | 25844.06 | 17-DEC-13:32 | 12.20 | 5.18 | 0.521301E+09 | 845.64 | 14-DEC-14:09 | 12.20 | 5.18 |
Annual Sum or Average | 0.889936E+11 | 0.712625E+10 | ||||||||
Minimum of Months | 0.226724E+10 | 14286.54 | 4.45 | -1.1 | 0.492439E+09 | 845.64 | 4.40 | -1.1 | ||
Maximum of Months | 0.149109E+11 | 27433.04 | 28.17 | 23.77 | 0.691985E+09 | 933.24 | 29.50 | 23.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448836E+09 | 3593.29 | 19-JAN-15:30 | 8.60 | 3.27 | 0.314008E+09 | 544.92 | 19-JAN-14:00 | 8.60 | 3.27 |
February | 0.634814E+09 | 5394.10 | 24-FEB-15:30 | 8.05 | 2.04 | 0.290114E+09 | 544.93 | 17-FEB-14:00 | 8.05 | 2.04 |
March | 0.235667E+10 | 10883.83 | 29-MAR-16:00 | 7.20 | 4.88 | 0.375880E+09 | 544.95 | 29-MAR-13:20 | 7.20 | 4.88 |
April | 0.373865E+10 | 25430.93 | 09-APR-16:11 | 16.83 | 14.03 | 0.362483E+09 | 544.96 | 07-APR-13:20 | 16.83 | 14.03 |
May | 0.613911E+10 | 26136.25 | 14-MAY-16:01 | 13.30 | 9.05 | 0.420145E+09 | 553.76 | 30-MAY-09:30 | 26.95 | 17.37 |
June | 0.883122E+10 | 26163.67 | 18-JUN-15:51 | 25.60 | 22.09 | 0.426980E+09 | 547.46 | 22-JUN-13:09 | 28.58 | 17.26 |
July | 0.981163E+10 | 26246.80 | 02-JUL-16:21 | 24.70 | 20.69 | 0.397889E+09 | 545.19 | 11-JUL-15:30 | 28.30 | 17.39 |
August | 0.109761E+11 | 25598.79 | 13-AUG-15:41 | 30.10 | 20.54 | 0.446044E+09 | 549.28 | 22-AUG-15:00 | 29.40 | 17.12 |
September | 0.617593E+10 | 25309.49 | 10-SEP-15:52 | 23.30 | 12.88 | 0.391566E+09 | 544.97 | 01-SEP-13:20 | 23.30 | 12.88 |
October | 0.435465E+10 | 18031.35 | 15-OCT-15:12 | 20.20 | 12.62 | 0.390665E+09 | 544.97 | 16-OCT-09:30 | 17.25 | 14.25 |
November | 0.115474E+10 | 6791.99 | 03-NOV-15:30 | 16.10 | 10.65 | 0.335801E+09 | 544.96 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.510513E+09 | 3029.64 | 08-DEC-15:30 | 6.40 | 2.12 | 0.304540E+09 | 544.93 | 18-DEC-14:00 | 6.10 | 2.61 |
Annual Sum or Average | 0.551328E+11 | 0.445612E+10 | ||||||||
Minimum of Months | 0.448836E+09 | 3029.64 | 6.40 | 2.04 | 0.290114E+09 | 544.92 | 6.10 | 2.04 | ||
Maximum of Months | 0.109761E+11 | 26246.80 | 30.10 | 22.09 | 0.446044E+09 | 553.76 | 29.40 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315310E+09 | 4974.14 | 14-JAN-06:01 | -7.8 | -8.5 | 0.00 | 0.00 | 01-JAN-00:10 | -7.8 | -8.5 |
February | 0.448947E+09 | 4802.54 | 07-FEB-06:01 | -9.4 | -10.4 | 0.00 | 0.00 | 01-FEB-00:10 | -9.4 | -10.4 |
March | 0.207367E+10 | 4199.70 | 28-MAR-05:15 | 9.60 | 7.49 | 0.00 | 0.00 | 01-MAR-00:10 | 9.60 | 7.49 |
April | 0.393152E+10 | 6668.57 | 10-APR-14:40 | 20.20 | 11.22 | 0.00 | 0.00 | 01-APR-00:10 | 20.20 | 11.22 |
May | 0.508318E+10 | 10550.59 | 30-MAY-09:30 | 26.95 | 17.37 | 0.00 | 0.00 | 01-MAY-00:10 | 26.95 | 17.37 |
June | 0.868761E+10 | 13303.67 | 26-JUN-05:15 | 20.97 | 17.23 | 0.00 | 0.00 | 01-JUN-00:10 | 20.97 | 17.23 |
July | 0.113615E+11 | 13970.92 | 11-JUL-05:10 | 19.60 | 15.11 | 0.00 | 0.00 | 01-JUL-00:10 | 19.60 | 15.11 |
August | 0.124261E+11 | 15649.55 | 14-AUG-05:13 | 22.57 | 20.98 | 0.00 | 0.00 | 01-AUG-00:10 | 22.57 | 20.98 |
September | 0.710030E+10 | 13685.76 | 05-SEP-05:15 | 20.60 | 18.00 | 0.00 | 0.00 | 01-SEP-00:10 | 20.60 | 18.00 |
October | 0.532337E+10 | 8171.93 | 23-OCT-05:15 | 13.13 | 11.01 | 0.00 | 0.00 | 01-OCT-00:10 | 13.13 | 11.01 |
November | 0.239033E+10 | 6943.92 | 13-NOV-06:10 | 5.68 | 4.62 | 0.00 | 0.00 | 01-NOV-00:10 | 5.68 | 4.62 |
December | 0.127684E+10 | 3133.68 | 18-DEC-06:13 | 0.60 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | 0.60 | -1.3 |
Annual Sum or Average | 0.604187E+11 | 0.00 | ||||||||
Minimum of Months | 0.315310E+09 | 3133.68 | -9.4 | -10.4 | 0.00 | 0.00 | -9.4 | -10.4 | ||
Maximum of Months | 0.124261E+11 | 15649.55 | 26.95 | 20.98 | 0.00 | 0.00 | 26.95 | 20.98 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101058E+09 | 7419.21 | 31-JAN-05:01 | -7.9 | -10.4 | 0.00 | 0.00 | 01-JAN-00:10 | -7.9 | -10.4 |
February | 0.148959E+09 | 9393.05 | 13-FEB-04:11 | -8.9 | -11.0 | 0.00 | 0.00 | 01-FEB-00:10 | -8.9 | -11.0 |
March | 0.491490E+09 | 7405.33 | 17-MAR-04:01 | -1.6 | -2.4 | 0.00 | 0.00 | 01-MAR-00:10 | -1.6 | -2.4 |
April | 0.139008E+10 | 3762.61 | 10-APR-15:10 | 20.00 | 11.51 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 11.51 |
May | 0.318448E+10 | 7551.66 | 30-MAY-14:10 | 29.22 | 16.98 | 0.00 | 0.00 | 01-MAY-00:10 | 29.22 | 16.98 |
June | 0.566930E+10 | 7125.46 | 26-JUN-05:15 | 20.97 | 17.23 | 0.00 | 0.00 | 01-JUN-00:10 | 20.97 | 17.23 |
July | 0.675271E+10 | 7847.81 | 24-JUL-05:15 | 20.97 | 20.39 | 0.00 | 0.00 | 01-JUL-00:10 | 20.97 | 20.39 |
August | 0.748074E+10 | 8759.03 | 07-AUG-05:15 | 19.40 | 16.84 | 0.00 | 0.00 | 01-AUG-00:10 | 19.40 | 16.84 |
September | 0.450671E+10 | 8403.69 | 05-SEP-05:15 | 20.60 | 18.00 | 0.00 | 0.00 | 01-SEP-00:10 | 20.60 | 18.00 |
October | 0.269060E+10 | 4580.59 | 05-OCT-15:50 | 21.78 | 19.16 | 0.00 | 0.00 | 01-OCT-00:10 | 21.78 | 19.16 |
November | 0.576808E+09 | 7793.96 | 24-NOV-05:01 | -4.0 | -6.0 | 0.00 | 0.00 | 01-NOV-00:10 | -4.0 | -6.0 |
December | 0.190742E+09 | 6566.76 | 23-DEC-05:11 | 2.97 | 2.63 | 0.00 | 0.00 | 01-DEC-00:10 | 2.97 | 2.63 |
Annual Sum or Average | 0.331837E+11 | 0.00 | ||||||||
Minimum of Months | 0.101058E+09 | 3762.61 | -8.9 | -11.0 | 0.00 | 0.00 | -8.9 | -11.0 | ||
Maximum of Months | 0.748074E+10 | 9393.05 | 29.22 | 20.39 | 0.00 | 0.00 | 29.22 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -9.6 | -11.5 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.5 |
February | 10727061.40 | 1254.25 | 20-FEB-14:30 | 8.60 | 4.58 | 0.00 | 0.00 | 01-FEB-00:10 | 8.60 | 4.58 |
March | 0.731795E+09 | 6297.15 | 03-MAR-14:50 | 15.00 | 8.43 | 0.00 | 0.00 | 01-MAR-00:10 | 15.00 | 8.43 |
April | 0.275892E+10 | 13314.22 | 07-APR-14:50 | 25.68 | 15.95 | 0.00 | 0.00 | 01-APR-00:10 | 25.68 | 15.95 |
May | 0.625768E+10 | 20001.15 | 30-MAY-13:15 | 29.80 | 17.64 | 0.00 | 0.00 | 01-MAY-00:10 | 29.80 | 17.64 |
June | 0.106645E+11 | 20399.77 | 19-JUN-13:20 | 34.80 | 23.85 | 0.00 | 0.00 | 01-JUN-00:10 | 34.80 | 23.85 |
July | 0.128995E+11 | 19426.21 | 10-JUL-13:40 | 32.60 | 20.74 | 0.00 | 0.00 | 01-JUL-00:10 | 32.60 | 20.74 |
August | 0.137130E+11 | 19422.88 | 22-AUG-14:20 | 30.73 | 18.19 | 0.00 | 0.00 | 01-AUG-00:10 | 30.73 | 18.19 |
September | 0.671892E+10 | 20142.35 | 01-SEP-13:33 | 30.93 | 17.69 | 0.00 | 0.00 | 01-SEP-00:10 | 30.93 | 17.69 |
October | 0.343873E+10 | 11004.63 | 04-OCT-13:20 | 24.80 | 18.68 | 0.00 | 0.00 | 01-OCT-00:10 | 24.80 | 18.68 |
November | 0.239534E+09 | 3892.70 | 03-NOV-14:10 | 17.70 | 10.72 | 0.00 | 0.00 | 01-NOV-00:10 | 17.70 | 10.72 |
December | 3845714.06 | 1467.31 | 17-DEC-13:35 | 12.20 | 5.18 | 0.00 | 0.00 | 01-DEC-00:10 | 12.20 | 5.18 |
Annual Sum or Average | 0.574372E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 0.00 | 0.00 | -9.6 | -11.5 | ||
Maximum of Months | 0.137130E+11 | 20399.77 | 34.80 | 23.85 | 0.00 | 0.00 | 34.80 | 23.85 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263092E+10 | 1945.50 | 20-JAN-16:30 | 6.40 | 3.51 | 95230512.64 | 126.83 | 24-JAN-14:00 | 11.00 | 11.00 |
February | 0.741475E+10 | 4053.18 | 14-FEB-17:00 | 0.00 | -4.1 | 86396466.84 | 126.82 | 02-FEB-14:20 | 0.00 | -4.1 |
March | 0.140628E+11 | 6957.33 | 31-MAR-24:00 | 5.40 | 5.40 | 0.103237E+09 | 126.83 | 06-MAR-14:00 | 5.40 | 5.40 |
April | 0.187332E+11 | 8337.04 | 23-APR-17:41 | 12.38 | 8.83 | 91605529.43 | 126.83 | 17-APR-09:00 | 12.38 | 8.83 |
May | 0.431925E+10 | 3492.53 | 31-MAY-24:00 | 18.50 | 16.73 | 99236939.49 | 126.85 | 31-MAY-09:00 | 18.50 | 16.73 |
June | 0.937532E+10 | 5341.58 | 30-JUN-24:00 | 20.00 | 19.21 | 98972749.47 | 126.86 | 15-JUN-13:00 | 20.00 | 19.21 |
July | 0.149045E+11 | 7319.81 | 31-JUL-23:57 | 23.90 | 22.01 | 91891883.53 | 126.85 | 18-JUL-09:09 | 23.90 | 22.01 |
August | 0.199374E+11 | 8139.30 | 20-AUG-17:32 | 23.87 | 18.39 | 0.103503E+09 | 131.25 | 16-AUG-13:00 | 23.87 | 18.39 |
September | 0.439416E+10 | 3392.50 | 30-SEP-24:00 | 12.60 | 11.96 | 91610378.78 | 126.85 | 06-SEP-13:00 | 12.60 | 11.96 |
October | 0.942831E+10 | 5141.77 | 31-OCT-24:00 | 10.60 | 9.48 | 95237390.19 | 126.85 | 06-OCT-09:00 | 10.60 | 9.48 |
November | 0.135642E+11 | 5820.55 | 06-NOV-16:10 | 13.03 | 7.67 | 94301111.49 | 126.84 | 10-NOV-10:00 | 15.60 | 14.59 |
December | 0.189027E+11 | 7776.33 | 17-DEC-15:55 | 10.00 | 4.16 | 91880795.66 | 126.82 | 21-DEC-14:09 | 3.30 | -1.7 |
Annual Sum or Average | 0.137668E+12 | 0.114310E+10 | ||||||||
Minimum of Months | 0.263092E+10 | 1945.50 | 0.00 | -4.1 | 86396466.84 | 126.82 | 0.00 | -4.1 | ||
Maximum of Months | 0.199374E+11 | 8337.04 | 23.90 | 22.01 | 0.103503E+09 | 131.25 | 23.90 | 22.01 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.523563E+09 | 1612.03 | 20-JAN-16:40 | 6.13 | 3.40 | 93680701.50 | 126.83 | 24-JAN-10:20 | 10.60 | 10.60 |
February | 0.500061E+10 | 3615.26 | 22-FEB-17:00 | 3.30 | -0.7 | 86396475.74 | 126.82 | 02-FEB-14:20 | 3.30 | -0.7 |
March | 0.119388E+11 | 6126.06 | 31-MAR-23:40 | 5.67 | 5.67 | 0.103237E+09 | 126.83 | 06-MAR-14:00 | 5.67 | 5.67 |
April | 0.169671E+11 | 7672.14 | 09-APR-17:31 | 15.37 | 13.32 | 91605560.61 | 126.83 | 17-APR-09:00 | 13.30 | 12.36 |
May | 0.368257E+10 | 3313.27 | 31-MAY-24:00 | 18.50 | 16.73 | 99235272.82 | 126.84 | 05-MAY-13:50 | 18.50 | 16.73 |
June | 0.870830E+10 | 5010.19 | 30-JUN-24:00 | 20.00 | 19.21 | 98972020.30 | 126.86 | 15-JUN-13:00 | 20.00 | 19.21 |
July | 0.139892E+11 | 6932.54 | 31-JUL-23:57 | 23.90 | 22.01 | 91892238.54 | 126.85 | 18-JUL-09:00 | 23.90 | 22.01 |
August | 0.188579E+11 | 7701.55 | 31-AUG-17:40 | 25.20 | 22.10 | 0.103372E+09 | 129.88 | 16-AUG-13:00 | 25.20 | 22.10 |
September | 0.375445E+10 | 3106.67 | 30-SEP-23:30 | 13.00 | 12.21 | 91608666.70 | 126.84 | 06-SEP-09:00 | 13.00 | 12.21 |
October | 0.829550E+10 | 4495.72 | 31-OCT-24:00 | 10.60 | 9.48 | 95237158.80 | 126.85 | 06-OCT-09:50 | 10.60 | 9.48 |
November | 0.112520E+11 | 5468.80 | 03-NOV-16:00 | 15.00 | 10.26 | 94301091.21 | 126.84 | 10-NOV-10:50 | 15.68 | 14.79 |
December | 0.156225E+11 | 7106.53 | 08-DEC-16:10 | 5.92 | 1.77 | 91880824.33 | 126.82 | 21-DEC-14:09 | 3.30 | -1.7 |
Annual Sum or Average | 0.118592E+12 | 0.114142E+10 | ||||||||
Minimum of Months | 0.523563E+09 | 1612.03 | 3.30 | -0.7 | 86396475.74 | 126.82 | 3.30 | -1.7 | ||
Maximum of Months | 0.188579E+11 | 7701.55 | 25.20 | 22.10 | 0.103372E+09 | 129.88 | 25.20 | 22.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214502E+09 | 1517.17 | 20-JAN-16:40 | 6.13 | 3.40 | 90593172.66 | 127.33 | 27-JAN-10:00 | 5.00 | 1.60 |
February | 0.335096E+10 | 3475.66 | 22-FEB-17:00 | 3.30 | -0.7 | 86396264.21 | 126.82 | 02-FEB-14:20 | 3.30 | -0.7 |
March | 0.105654E+11 | 5670.62 | 29-MAR-17:20 | 5.73 | 4.14 | 0.103237E+09 | 126.83 | 06-MAR-14:00 | 5.73 | 4.14 |
April | 0.160834E+11 | 7732.01 | 09-APR-17:23 | 15.55 | 13.44 | 91605605.05 | 126.83 | 17-APR-09:00 | 13.30 | 12.36 |
May | 0.336962E+10 | 3261.70 | 31-MAY-24:00 | 18.50 | 16.73 | 99235365.22 | 126.84 | 31-MAY-09:00 | 18.50 | 16.73 |
June | 0.870307E+10 | 4938.17 | 30-JUN-24:00 | 20.00 | 19.21 | 98972463.82 | 126.86 | 15-JUN-13:00 | 20.00 | 19.21 |
July | 0.140932E+11 | 6927.21 | 31-JUL-23:57 | 23.90 | 22.01 | 91892786.37 | 126.85 | 28-JUL-13:00 | 23.90 | 22.01 |
August | 0.189087E+11 | 7855.08 | 13-AUG-18:22 | 27.25 | 20.34 | 0.103306E+09 | 128.76 | 16-AUG-13:00 | 32.20 | 25.36 |
September | 0.354394E+10 | 2823.23 | 30-SEP-23:20 | 13.13 | 12.30 | 91608645.66 | 126.84 | 06-SEP-09:00 | 13.13 | 12.30 |
October | 0.749126E+10 | 3992.80 | 15-OCT-16:50 | 18.48 | 11.81 | 95237237.36 | 126.85 | 06-OCT-09:00 | 18.48 | 11.81 |
November | 0.963594E+10 | 5444.51 | 03-NOV-16:00 | 15.00 | 10.26 | 94301113.80 | 126.84 | 10-NOV-10:09 | 16.02 | 15.59 |
December | 0.136181E+11 | 6901.32 | 08-DEC-16:10 | 5.92 | 1.77 | 91880833.54 | 126.82 | 21-DEC-14:09 | 3.30 | -1.7 |
Annual Sum or Average | 0.109578E+12 | 0.113827E+10 | ||||||||
Minimum of Months | 0.214502E+09 | 1517.17 | 3.30 | -0.7 | 86396264.21 | 126.82 | 3.30 | -1.7 | ||
Maximum of Months | 0.189087E+11 | 7855.08 | 27.25 | 22.01 | 0.103306E+09 | 128.76 | 32.20 | 25.36 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235132E+12 | 90616.02 | 20-JAN-17:00 | 5.60 | 3.19 | 0.206143E+10 | 2745.29 | 19-JAN-14:00 | 5.60 | 3.19 |
February | 0.433119E+12 | 182029.19 | 22-FEB-17:00 | 3.30 | -0.7 | 0.187023E+10 | 2745.43 | 02-FEB-14:20 | 3.30 | -0.7 |
March | 0.727172E+12 | 357769.01 | 31-MAR-24:00 | 5.40 | 5.40 | 0.223479E+10 | 2746.39 | 27-MAR-13:09 | 5.40 | 5.40 |
April | 0.941188E+12 | 366456.49 | 10-APR-16:00 | 20.00 | 11.13 | 0.198340E+10 | 2750.53 | 10-APR-09:09 | 20.00 | 11.13 |
May | 0.239098E+12 | 175642.21 | 31-MAY-24:00 | 18.50 | 16.73 | 0.214808E+10 | 2746.53 | 31-MAY-13:09 | 18.50 | 16.73 |
June | 0.470022E+12 | 267428.25 | 30-JUN-24:00 | 20.00 | 19.21 | 0.214259E+10 | 2748.72 | 05-JUN-13:09 | 20.00 | 19.21 |
July | 0.733668E+12 | 360483.72 | 31-JUL-23:57 | 23.90 | 22.01 | 0.198932E+10 | 2748.20 | 11-JUL-09:09 | 23.90 | 22.01 |
August | 0.979618E+12 | 393351.49 | 24-AUG-18:23 | 30.25 | 17.47 | 0.223862E+10 | 3067.61 | 30-AUG-15:09 | 29.22 | 15.03 |
September | 0.235817E+12 | 176204.84 | 30-SEP-24:00 | 12.60 | 11.96 | 0.198315E+10 | 2746.85 | 14-SEP-09:09 | 12.60 | 11.96 |
October | 0.487173E+12 | 267629.19 | 31-OCT-24:00 | 10.60 | 9.48 | 0.206157E+10 | 2748.64 | 02-OCT-13:00 | 10.60 | 9.48 |
November | 0.706965E+12 | 275699.41 | 06-NOV-17:00 | 11.70 | 7.36 | 0.204131E+10 | 2747.05 | 09-NOV-10:09 | 14.40 | 10.88 |
December | 0.974544E+12 | 366793.01 | 18-DEC-17:00 | 3.30 | 0.83 | 0.198896E+10 | 2745.39 | 08-DEC-10:39 | 3.30 | 0.83 |
Annual Sum or Average | 0.716351E+13 | 0.247434E+11 | ||||||||
Minimum of Months | 0.235132E+12 | 90616.02 | 3.30 | -0.7 | 0.187023E+10 | 2745.29 | 3.30 | -0.7 | ||
Maximum of Months | 0.979618E+12 | 393351.49 | 30.25 | 22.01 | 0.223862E+10 | 3067.61 | 29.22 | 22.01 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.812421E+09 | 45805.14 | 02-JAN-04:01 | -11.8 |
February | 19493791.70 | 34452.21 | 06-FEB-06:02 | -12.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.831915E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.812421E+09 | 45805.14 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.435877E+10 | 73809.53 | 02-JAN-04:01 | -11.8 |
February | 0.287078E+10 | 71583.29 | 06-FEB-04:01 | -13.3 |
March | 0.404824E+09 | 64461.16 | 20-MAR-04:01 | -0.8 |
April | 55929957.76 | 59921.69 | 03-APR-05:02 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.970302E+09 | 66462.59 | 24-NOV-05:01 | -4.0 |
December | 0.148837E+10 | 68410.09 | 26-DEC-05:11 | 5.77 |
Annual Sum or Average | 0.101490E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.435877E+10 | 73809.53 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140434E+09 | 11357.87 | 02-JAN-05:01 | -12.1 |
February | 0.111585E+09 | 11353.79 | 06-FEB-05:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.252019E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.140434E+09 | 11357.87 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104575E+09 | 9829.99 | 02-JAN-05:01 | -12.1 |
February | 67346861.32 | 9890.51 | 06-FEB-05:01 | -13.2 |
March | 158591.68 | 1638.07 | 17-MAR-05:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 321450.58 | 2136.82 | 22-NOV-06:01 | -2.2 |
December | 511228.37 | 3213.42 | 07-DEC-06:01 | 0.10 |
Annual Sum or Average | 0.172913E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.104575E+09 | 9890.51 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280246E+09 | 15567.92 | 02-JAN-05:01 | -12.1 |
February | 0.156781E+09 | 15222.13 | 06-FEB-05:01 | -13.2 |
March | 2046364.23 | 8495.64 | 17-MAR-05:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 3924926.85 | 12101.44 | 24-NOV-06:01 | -4.4 |
December | 5563169.92 | 12129.96 | 07-DEC-06:01 | 0.10 |
Annual Sum or Average | 0.448561E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.280246E+09 | 15567.92 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12473952.52 | 7400.14 | 02-JAN-06:01 | -11.7 |
February | 3890113.02 | 7113.82 | 06-FEB-06:02 | -12.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 16364065.54 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 12473952.52 | 7400.14 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345387E+10 | 13565.86 | 02-JAN-02:62 | -11.7 |
February | 0.243257E+10 | 13006.75 | 05-FEB-22:32 | -11.8 |
March | 0.441018E+09 | 11288.94 | 13-MAR-04:01 | -0.1 |
April | 46016773.51 | 10736.08 | 03-APR-04:11 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 778763.61 | 3687.57 | 28-OCT-05:03 | 3.90 |
November | 0.516224E+09 | 11995.57 | 24-NOV-04:01 | -3.4 |
December | 0.138395E+10 | 11714.00 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.827443E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.345387E+10 | 13565.86 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179204E+10 | 17469.78 | 02-JAN-02:62 | -11.7 |
February | 0.106010E+10 | 16635.51 | 13-FEB-04:11 | -8.9 |
March | 0.207568E+09 | 14315.18 | 17-MAR-04:01 | -1.6 |
April | 21649778.37 | 12909.94 | 03-APR-05:02 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.238104E+09 | 14764.31 | 24-NOV-05:01 | -4.0 |
December | 0.697574E+09 | 15183.33 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.401704E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.7 | |
Maximum of Months | 0.179204E+10 | 17469.78 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192318E+10 | 20032.48 | 02-JAN-02:62 | -11.7 |
February | 0.101657E+10 | 19084.22 | 06-FEB-04:01 | -13.3 |
March | 0.208792E+09 | 16616.99 | 17-MAR-04:01 | -1.6 |
April | 25586111.34 | 14374.44 | 03-APR-05:02 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.206029E+09 | 16842.60 | 24-NOV-05:01 | -4.0 |
December | 0.687725E+09 | 17511.33 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.406788E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.192318E+10 | 20032.48 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148895E+10 | 17382.17 | 02-JAN-02:62 | -11.7 |
February | 0.901437E+09 | 16447.67 | 06-FEB-04:01 | -13.3 |
March | 0.104183E+09 | 13859.88 | 17-MAR-04:01 | -1.6 |
April | 4193893.96 | 6180.77 | 22-APR-05:03 | 5.50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.167657E+09 | 14709.65 | 24-NOV-05:01 | -4.0 |
December | 0.442224E+09 | 14509.74 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.310864E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.148895E+10 | 17382.17 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.667443E+10 | 15838.62 | 02-JAN-02:62 | -11.7 |
February | 0.577679E+10 | 15749.13 | 05-FEB-22:32 | -11.8 |
March | 0.181755E+10 | 14664.25 | 13-MAR-03:01 | 0.50 |
April | 0.473565E+09 | 14015.28 | 03-APR-04:11 | 2.80 |
May | 7456489.03 | 12005.81 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.139407E+09 | 12264.96 | 10-OCT-04:12 | 10.40 |
November | 0.211992E+10 | 14893.32 | 24-NOV-04:01 | -3.4 |
December | 0.448433E+10 | 15459.00 | 31-DEC-23:12 | -8.0 |
Annual Sum or Average | 0.214935E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.667443E+10 | 15838.62 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363969E+10 | 19596.70 | 02-JAN-02:62 | -11.7 |
February | 0.278291E+10 | 19456.17 | 05-FEB-22:32 | -11.8 |
March | 0.840851E+09 | 18329.59 | 20-MAR-03:01 | -0.1 |
April | 0.244479E+09 | 17320.13 | 03-APR-04:11 | 2.80 |
May | 3384918.31 | 14223.68 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 56851746.23 | 13524.73 | 27-OCT-05:02 | 6.02 |
November | 0.105412E+10 | 18647.79 | 24-NOV-04:01 | -3.4 |
December | 0.235649E+10 | 19068.96 | 31-DEC-23:12 | -8.0 |
Annual Sum or Average | 0.109788E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.363969E+10 | 19596.70 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.413920E+10 | 22318.84 | 02-JAN-02:62 | -11.7 |
February | 0.307354E+10 | 21955.71 | 05-FEB-22:32 | -11.8 |
March | 0.108639E+10 | 20353.87 | 13-MAR-03:01 | 0.50 |
April | 0.361711E+09 | 19354.27 | 03-APR-04:11 | 2.80 |
May | 9120208.88 | 17146.06 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 26075095.39 | 13813.65 | 28-OCT-05:03 | 3.90 |
November | 0.109099E+10 | 21014.61 | 24-NOV-04:01 | -3.4 |
December | 0.257650E+10 | 21648.83 | 31-DEC-23:12 | -8.0 |
Annual Sum or Average | 0.123635E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.413920E+10 | 22318.84 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306682E+10 | 20470.95 | 02-JAN-02:62 | -11.7 |
February | 0.229826E+10 | 19948.15 | 05-FEB-22:32 | -11.8 |
March | 0.567149E+09 | 18161.17 | 13-MAR-03:01 | 0.50 |
April | 0.123810E+09 | 16651.72 | 03-APR-04:11 | 2.80 |
May | 564098.66 | 3081.21 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 17949518.70 | 9515.75 | 27-OCT-05:02 | 6.02 |
November | 0.776606E+09 | 19231.20 | 24-NOV-04:01 | -3.4 |
December | 0.163250E+10 | 19176.04 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.848365E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.306682E+10 | 20470.95 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.912026E+09 | 8549.06 | 18-JAN-06:03 | 7.38 |
February | 0.608479E+09 | 9801.45 | 20-FEB-15:23 | 7.75 |
March | 0.105333E+09 | 9423.20 | 13-MAR-04:01 | -0.1 |
April | 0.161563E+09 | 10857.31 | 24-APR-04:12 | 8.13 |
May | 79630117.18 | 8038.63 | 01-MAY-04:12 | 6.50 |
June | 0.111266E+09 | 8498.15 | 15-JUN-04:11 | 20.93 |
July | 0.162480E+09 | 9894.48 | 02-JUL-16:01 | 24.90 |
August | 88144540.44 | 9530.11 | 13-AUG-15:01 | 30.50 |
September | 91816317.28 | 9046.10 | 08-SEP-04:12 | 21.70 |
October | 0.104770E+09 | 8840.99 | 08-OCT-14:32 | 12.20 |
November | 83307553.56 | 10151.29 | 27-NOV-05:11 | 6.30 |
December | 0.135498E+09 | 11773.65 | 26-DEC-05:11 | 5.77 |
Annual Sum or Average | 0.264431E+10 | |||
Minimum of Months | 79630117.18 | 8038.63 | -0.1 | |
Maximum of Months | 0.912026E+09 | 11773.65 | 30.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363946E+10 | 16724.24 | 02-JAN-06:12 | -11.7 |
February | 0.214713E+10 | 8431.95 | 19-FEB-12:43 | 8.22 |
March | 0.118341E+10 | 5674.25 | 26-MAR-15:50 | 11.78 |
April | 0.342312E+09 | 8644.78 | 16-APR-15:32 | 21.30 |
May | 66426608.28 | 10458.07 | 28-MAY-14:51 | 26.70 |
June | 49333899.81 | 9005.21 | 04-JUN-15:51 | 22.20 |
July | 73238470.28 | 9708.34 | 02-JUL-16:11 | 24.80 |
August | 47998913.75 | 9692.41 | 13-AUG-15:01 | 30.50 |
September | 65426123.41 | 9900.92 | 10-SEP-15:01 | 24.22 |
October | 77953770.21 | 8804.72 | 15-OCT-15:01 | 20.40 |
November | 0.774410E+09 | 6467.42 | 23-NOV-12:43 | 2.12 |
December | 0.159297E+10 | 8498.93 | 17-DEC-12:22 | 12.20 |
Annual Sum or Average | 0.100601E+11 | |||
Minimum of Months | 47998913.75 | 5674.25 | -11.7 | |
Maximum of Months | 0.363946E+10 | 16724.24 | 30.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.848624E+10 | 26802.17 | 02-JAN-06:12 | -11.7 |
February | 0.701681E+10 | 27233.70 | 06-FEB-05:22 | -13.1 |
March | 0.313281E+10 | 18039.16 | 20-MAR-05:13 | -1.3 |
April | 0.140055E+10 | 12811.72 | 03-APR-05:02 | 2.70 |
May | 0.316222E+09 | 13238.52 | 17-MAY-05:02 | 10.28 |
June | 61872209.94 | 12107.97 | 05-JUN-05:03 | 14.68 |
July | 37908182.22 | 10280.16 | 03-JUL-04:12 | 22.60 |
August | 47481785.19 | 10264.91 | 08-AUG-05:03 | 15.37 |
September | 0.213868E+09 | 12280.78 | 29-SEP-05:02 | 11.78 |
October | 0.874769E+09 | 11556.71 | 12-OCT-05:02 | 12.70 |
November | 0.359660E+10 | 21781.57 | 24-NOV-06:13 | -4.4 |
December | 0.620375E+10 | 19128.98 | 11-DEC-05:12 | 1.70 |
Annual Sum or Average | 0.313889E+11 | |||
Minimum of Months | 37908182.22 | 10264.91 | -13.1 | |
Maximum of Months | 0.848624E+10 | 27233.70 | 22.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374842E+09 | 524.39 | 03-JAN-01:00 | -3.9 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.374842E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 0.374842E+09 | 524.39 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.725451E+09 | 570.75 | 16-JAN-18:05 | 3.80 |
February | 39052660.13 | 525.10 | 06-FEB-00:20 | -13.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.764503E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.725451E+09 | 570.75 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968216E+10 | 10174.14 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.878253E+10 | 10174.14 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.104353E+11 | 10174.14 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.932187E+10 | 10174.14 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.100587E+11 | 10174.14 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.100099E+11 | 10174.14 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.937071E+10 | 10174.14 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.104353E+11 | 10174.14 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.932187E+10 | 10174.14 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.968216E+10 | 10174.14 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.956821E+10 | 10174.14 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.937071E+10 | 10174.14 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.116039E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.878253E+10 | 10174.14 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.104353E+11 | 10174.14 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718471E+09 | 1147.25 | 02-JAN-16:40 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.604189E+09 | 1034.33 | 15-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.674284E+09 | 807.19 | 02-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.576599E+09 | 603.91 | 21-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.607969E+09 | 603.16 | 08-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.595309E+09 | 588.24 | 29-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.561877E+09 | 583.74 | 24-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.633830E+09 | 614.36 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.587828E+09 | 640.19 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.636255E+09 | 895.25 | 31-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.689708E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.708849E+09 | 1147.25 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.759517E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.561877E+09 | 583.74 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.718471E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.457675E+09 | 739.33 | 02-JAN-16:40 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.386781E+09 | 674.54 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.433597E+09 | 587.08 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.372067E+09 | 377.92 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.394018E+09 | 389.37 | 19-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.386192E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.364157E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.409703E+09 | 378.16 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.378484E+09 | 398.70 | 26-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.408462E+09 | 582.73 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.442381E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.448631E+09 | 739.33 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.488215E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.364157E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.457675E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.694641E+09 | 1147.28 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.590323E+09 | 1027.23 | 15-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.668852E+09 | 730.41 | 02-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.577363E+09 | 600.21 | 21-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.610469E+09 | 604.61 | 08-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.598701E+09 | 593.59 | 29-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.564852E+09 | 589.61 | 24-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.635799E+09 | 614.34 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.586308E+09 | 635.71 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.628825E+09 | 858.81 | 31-OCT-15:00 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.674510E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.678444E+09 | 1147.28 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.750909E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.564852E+09 | 589.61 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.694641E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451714E+09 | 739.33 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.382425E+09 | 656.63 | 15-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.430201E+09 | 514.25 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.371435E+09 | 402.31 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.390817E+09 | 397.37 | 08-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.383538E+09 | 390.75 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.362326E+09 | 390.29 | 24-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.407910E+09 | 403.57 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.377783E+09 | 488.59 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.406328E+09 | 559.69 | 06-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.436103E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.443162E+09 | 739.33 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.484374E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.362326E+09 | 390.29 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.451714E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.716582E+09 | 1147.25 | 02-JAN-16:40 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.602743E+09 | 1033.14 | 15-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.673278E+09 | 802.47 | 02-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.576119E+09 | 598.12 | 21-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.607646E+09 | 597.32 | 08-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.595062E+09 | 581.56 | 29-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.561510E+09 | 545.86 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.633591E+09 | 609.17 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.587232E+09 | 636.47 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.635440E+09 | 892.45 | 31-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.688367E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.706426E+09 | 1147.25 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.758400E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.561510E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.716582E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.456518E+09 | 739.33 | 02-JAN-16:40 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.386141E+09 | 672.87 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.433068E+09 | 582.93 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.371825E+09 | 373.65 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.393756E+09 | 385.74 | 19-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.385974E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.363947E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.409549E+09 | 374.57 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.378111E+09 | 395.77 | 27-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.408116E+09 | 578.70 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.441761E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.447616E+09 | 739.33 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.487638E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.363947E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.456518E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.693741E+09 | 1147.28 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.589742E+09 | 1026.03 | 15-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.667920E+09 | 637.90 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.576957E+09 | 594.24 | 21-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.610107E+09 | 598.83 | 08-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.598397E+09 | 587.16 | 29-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.564493E+09 | 582.97 | 24-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.635548E+09 | 609.14 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.585866E+09 | 631.78 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.628378E+09 | 855.98 | 31-OCT-15:00 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.674085E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.677838E+09 | 1147.28 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.750307E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.564493E+09 | 582.97 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.693741E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.450753E+09 | 739.33 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.381804E+09 | 654.67 | 15-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.429794E+09 | 508.36 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.371088E+09 | 399.37 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.390583E+09 | 394.19 | 08-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.383360E+09 | 387.20 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.362103E+09 | 386.70 | 24-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.407736E+09 | 400.74 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.377416E+09 | 482.01 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.406081E+09 | 555.03 | 06-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.435630E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.442390E+09 | 739.33 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.483874E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.362103E+09 | 386.70 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.450753E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.716422E+09 | 1147.25 | 02-JAN-16:40 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.602618E+09 | 1032.91 | 15-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.673252E+09 | 801.91 | 02-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.576079E+09 | 597.88 | 21-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.607637E+09 | 597.08 | 08-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.595052E+09 | 581.28 | 29-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.561500E+09 | 545.86 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.633581E+09 | 608.96 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.587210E+09 | 636.33 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.635399E+09 | 891.93 | 31-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.688324E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.706297E+09 | 1147.25 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.758337E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.561500E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.716422E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.456479E+09 | 739.33 | 02-JAN-16:40 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.386119E+09 | 672.75 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.433056E+09 | 582.67 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.371804E+09 | 373.48 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.393748E+09 | 385.59 | 19-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.385961E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.363938E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.409544E+09 | 374.39 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.378100E+09 | 395.63 | 27-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.408106E+09 | 578.38 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.441739E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.447584E+09 | 739.33 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.487618E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.363938E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.456479E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.693698E+09 | 1147.28 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.589718E+09 | 1025.79 | 15-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.667903E+09 | 637.75 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.576934E+09 | 594.00 | 21-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.610094E+09 | 598.60 | 08-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.598382E+09 | 586.91 | 29-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.564470E+09 | 582.70 | 24-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.635515E+09 | 608.93 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.585848E+09 | 631.62 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.628367E+09 | 855.41 | 31-OCT-15:00 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.674065E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.677811E+09 | 1147.28 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.750281E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.564470E+09 | 582.70 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.693698E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.450722E+09 | 739.33 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.381786E+09 | 654.51 | 15-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.429783E+09 | 507.91 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.371082E+09 | 399.26 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.390578E+09 | 394.06 | 08-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.383354E+09 | 387.06 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.362075E+09 | 386.56 | 24-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.407732E+09 | 400.63 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.377400E+09 | 481.50 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.406071E+09 | 554.65 | 06-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.435614E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.442351E+09 | 739.33 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.483855E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.362075E+09 | 386.56 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.450722E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274130E+10 | 2868.67 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.248656E+10 | 2868.67 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.295472E+10 | 2868.67 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.263917E+10 | 2868.67 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.284801E+10 | 2868.67 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.283424E+10 | 2868.67 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.265294E+10 | 2868.67 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.295472E+10 | 2868.67 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.263917E+10 | 2868.67 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.274130E+10 | 2868.67 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.270917E+10 | 2868.67 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.265294E+10 | 2868.67 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.328542E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.248656E+10 | 2868.67 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.295472E+10 | 2868.67 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.100587E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.100099E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.956821E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.116039E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.718471E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680853E+09 |
February | 0.136985E+10 | 0.604189E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593341E+09 |
March | 0.163685E+10 | 0.674284E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496516E+09 |
April | 0.145243E+10 | 0.576599E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 226993.10 | 0.332394E+09 |
May | 0.157338E+10 | 0.607969E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 932415.36 | 0.186641E+09 |
June | 0.156900E+10 | 0.595309E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7109172.25 | 95230260.13 |
July | 0.145680E+10 | 0.561877E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16807472.46 | 32500775.98 |
August | 0.163685E+10 | 0.633830E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20964633.19 | 39386734.58 |
September | 0.145243E+10 | 0.587828E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2586829.61 | 0.104556E+09 |
October | 0.150991E+10 | 0.636255E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42924.06 | 0.260291E+09 |
November | 0.149516E+10 | 0.689708E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500670E+09 |
December | 0.145680E+10 | 0.708849E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598973E+09 |
Annual Sum or Average | 0.181194E+11 | 0.759517E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48670440.02 | 0.392135E+10 |
Minimum of Months | 0.136985E+10 | 0.561877E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32500775.98 |
Maximum of Months | 0.163685E+10 | 0.718471E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20964633.19 | 0.680853E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.457675E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454018E+09 |
February | 0.882782E+09 | 0.386781E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399297E+09 |
March | 0.105485E+10 | 0.433597E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328349E+09 |
April | 0.936002E+09 | 0.372067E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 151485.69 | 0.220138E+09 |
May | 0.101394E+10 | 0.394018E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 563193.19 | 0.125724E+09 |
June | 0.101113E+10 | 0.386192E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4690593.29 | 62885963.07 |
July | 0.938820E+09 | 0.364157E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11226578.86 | 21002959.29 |
August | 0.105485E+10 | 0.409703E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14009465.40 | 25731574.91 |
September | 0.936002E+09 | 0.378484E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1720859.54 | 71265483.45 |
October | 0.973041E+09 | 0.408462E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28608.45 | 0.174900E+09 |
November | 0.963541E+09 | 0.442381E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330930E+09 |
December | 0.938820E+09 | 0.448631E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392877E+09 |
Annual Sum or Average | 0.116768E+11 | 0.488215E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32390784.41 | 0.260712E+10 |
Minimum of Months | 0.882782E+09 | 0.364157E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21002959.29 |
Maximum of Months | 0.105485E+10 | 0.457675E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14009465.40 | 0.454018E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.694641E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675399E+09 |
February | 0.136988E+10 | 0.590323E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605920E+09 |
March | 0.163688E+10 | 0.668852E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496776E+09 |
April | 0.145246E+10 | 0.577363E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 226211.72 | 0.331439E+09 |
May | 0.157341E+10 | 0.610469E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 815719.43 | 0.186604E+09 |
June | 0.156904E+10 | 0.598701E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7008364.69 | 94831528.51 |
July | 0.145684E+10 | 0.564852E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16671150.91 | 32305768.35 |
August | 0.163688E+10 | 0.635799E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20510188.77 | 41056341.46 |
September | 0.145246E+10 | 0.586308E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2508710.77 | 0.109284E+09 |
October | 0.150994E+10 | 0.628825E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22569.38 | 0.273088E+09 |
November | 0.149520E+10 | 0.674510E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500643E+09 |
December | 0.145684E+10 | 0.678444E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595739E+09 |
Annual Sum or Average | 0.181198E+11 | 0.750909E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47762915.67 | 0.394308E+10 |
Minimum of Months | 0.136988E+10 | 0.564852E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32305768.35 |
Maximum of Months | 0.163688E+10 | 0.694641E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20510188.77 | 0.675399E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.451714E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477809E+09 |
February | 0.882782E+09 | 0.382425E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424913E+09 |
March | 0.105485E+10 | 0.430201E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364224E+09 |
April | 0.936002E+09 | 0.371435E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 150887.86 | 0.251406E+09 |
May | 0.101394E+10 | 0.390817E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 573427.39 | 0.136688E+09 |
June | 0.101113E+10 | 0.383538E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4547787.51 | 75127651.03 |
July | 0.938820E+09 | 0.362326E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10558791.05 | 29305118.25 |
August | 0.105485E+10 | 0.407910E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12959730.58 | 35422430.23 |
September | 0.936002E+09 | 0.377783E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1706278.65 | 78630271.53 |
October | 0.973041E+09 | 0.406328E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28621.83 | 0.194219E+09 |
November | 0.963541E+09 | 0.436103E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367556E+09 |
December | 0.938820E+09 | 0.443162E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445167E+09 |
Annual Sum or Average | 0.116768E+11 | 0.484374E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30525524.86 | 0.288047E+10 |
Minimum of Months | 0.882782E+09 | 0.362326E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29305118.25 |
Maximum of Months | 0.105485E+10 | 0.451714E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12959730.58 | 0.477809E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.716582E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139206E+10 |
February | 0.136985E+10 | 0.602743E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123965E+10 |
March | 0.163685E+10 | 0.673278E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102392E+10 |
April | 0.145243E+10 | 0.576119E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 496007.62 | 0.684787E+09 |
May | 0.157338E+10 | 0.607646E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2365597.65 | 0.412521E+09 |
June | 0.156900E+10 | 0.595062E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16683652.73 | 0.212519E+09 |
July | 0.145680E+10 | 0.561510E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39712373.02 | 73382491.82 |
August | 0.163685E+10 | 0.633591E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48778649.01 | 93765953.29 |
September | 0.145243E+10 | 0.587232E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5860688.07 | 0.220974E+09 |
October | 0.150991E+10 | 0.635440E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77876.06 | 0.545136E+09 |
November | 0.149516E+10 | 0.688367E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100539E+10 |
December | 0.145680E+10 | 0.706426E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119257E+10 |
Annual Sum or Average | 0.181194E+11 | 0.758400E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113975E+09 | 0.809667E+10 |
Minimum of Months | 0.136985E+10 | 0.561510E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73382491.82 |
Maximum of Months | 0.163685E+10 | 0.716582E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48778649.01 | 0.139206E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.456518E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934259E+09 |
February | 0.649041E+09 | 0.386141E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850681E+09 |
March | 0.773965E+09 | 0.433068E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707742E+09 |
April | 0.688021E+09 | 0.371825E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 297019.65 | 0.482560E+09 |
May | 0.744847E+09 | 0.393756E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1169652.32 | 0.287157E+09 |
June | 0.742030E+09 | 0.385974E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10211982.48 | 0.148273E+09 |
July | 0.690839E+09 | 0.363947E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24419685.95 | 53177498.10 |
August | 0.773965E+09 | 0.409549E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30098331.92 | 68263304.04 |
September | 0.688021E+09 | 0.378111E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3624352.98 | 0.160157E+09 |
October | 0.715730E+09 | 0.408116E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28658.20 | 0.387204E+09 |
November | 0.708685E+09 | 0.441761E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694272E+09 |
December | 0.690839E+09 | 0.447616E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810736E+09 |
Annual Sum or Average | 0.858171E+10 | 0.487638E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69849683.49 | 0.558448E+10 |
Minimum of Months | 0.649041E+09 | 0.363947E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53177498.10 |
Maximum of Months | 0.773965E+09 | 0.456518E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30098331.92 | 0.934259E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.693741E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146060E+10 |
February | 0.136988E+10 | 0.589742E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135028E+10 |
March | 0.163688E+10 | 0.667920E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109789E+10 |
April | 0.145246E+10 | 0.576957E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 491721.81 | 0.729899E+09 |
May | 0.157341E+10 | 0.610107E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1825275.65 | 0.423952E+09 |
June | 0.156904E+10 | 0.598397E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16054346.46 | 0.216877E+09 |
July | 0.145684E+10 | 0.564493E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38138448.27 | 78219402.19 |
August | 0.163688E+10 | 0.635548E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45988942.76 | 0.103883E+09 |
September | 0.145246E+10 | 0.585866E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5569981.36 | 0.248825E+09 |
October | 0.150994E+10 | 0.628378E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35734.80 | 0.621530E+09 |
November | 0.149520E+10 | 0.674085E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109359E+10 |
December | 0.145684E+10 | 0.677838E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128945E+10 |
Annual Sum or Average | 0.181198E+11 | 0.750307E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108104E+09 | 0.871499E+10 |
Minimum of Months | 0.136988E+10 | 0.564493E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78219402.19 |
Maximum of Months | 0.163688E+10 | 0.693741E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45988942.76 | 0.146060E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.450753E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959662E+09 |
February | 0.882782E+09 | 0.381804E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864326E+09 |
March | 0.105485E+10 | 0.429794E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735447E+09 |
April | 0.936002E+09 | 0.371088E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 323577.73 | 0.498986E+09 |
May | 0.101394E+10 | 0.390583E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1346682.54 | 0.297333E+09 |
June | 0.101113E+10 | 0.383360E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10332376.26 | 0.160904E+09 |
July | 0.938820E+09 | 0.362103E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24311778.10 | 64901743.59 |
August | 0.105485E+10 | 0.407736E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29723103.87 | 78317406.21 |
September | 0.936002E+09 | 0.377416E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3832816.04 | 0.165800E+09 |
October | 0.973041E+09 | 0.406081E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51932.75 | 0.402174E+09 |
November | 0.963541E+09 | 0.435630E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700753E+09 |
December | 0.938820E+09 | 0.442390E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834398E+09 |
Annual Sum or Average | 0.116768E+11 | 0.483874E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69922267.29 | 0.576300E+10 |
Minimum of Months | 0.882782E+09 | 0.362103E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64901743.59 |
Maximum of Months | 0.105485E+10 | 0.450753E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29723103.87 | 0.959662E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.716422E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165820E+10 |
February | 0.136985E+10 | 0.602618E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147006E+10 |
March | 0.163685E+10 | 0.673252E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118721E+10 |
April | 0.145243E+10 | 0.576079E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 574456.77 | 0.787074E+09 |
May | 0.157338E+10 | 0.607637E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2488373.15 | 0.493667E+09 |
June | 0.156900E+10 | 0.595052E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19325676.80 | 0.265871E+09 |
July | 0.145680E+10 | 0.561500E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45353925.07 | 98375040.96 |
August | 0.163685E+10 | 0.633581E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57225259.19 | 0.119180E+09 |
September | 0.145243E+10 | 0.587210E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6849710.60 | 0.265434E+09 |
October | 0.150991E+10 | 0.635399E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72378.79 | 0.623003E+09 |
November | 0.149516E+10 | 0.688324E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113295E+10 |
December | 0.145680E+10 | 0.706297E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137126E+10 |
Annual Sum or Average | 0.181194E+11 | 0.758337E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131890E+09 | 0.947229E+10 |
Minimum of Months | 0.136985E+10 | 0.561500E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98375040.96 |
Maximum of Months | 0.163685E+10 | 0.716422E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57225259.19 | 0.165820E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.456479E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111115E+10 |
February | 0.882782E+09 | 0.386119E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997828E+09 |
March | 0.105485E+10 | 0.433056E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818620E+09 |
April | 0.936002E+09 | 0.371804E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 382650.81 | 0.558721E+09 |
May | 0.101394E+10 | 0.393748E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1433947.37 | 0.343521E+09 |
June | 0.101113E+10 | 0.385961E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12556423.06 | 0.183880E+09 |
July | 0.938820E+09 | 0.363938E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29356003.58 | 69742579.73 |
August | 0.105485E+10 | 0.409544E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36836889.89 | 86016806.01 |
September | 0.936002E+09 | 0.378100E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4547258.84 | 0.192286E+09 |
October | 0.973041E+09 | 0.408106E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48220.38 | 0.447022E+09 |
November | 0.963541E+09 | 0.441739E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780165E+09 |
December | 0.938820E+09 | 0.447584E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925640E+09 |
Annual Sum or Average | 0.116768E+11 | 0.487618E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85161393.93 | 0.651459E+10 |
Minimum of Months | 0.882782E+09 | 0.363938E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69742579.73 |
Maximum of Months | 0.105485E+10 | 0.456479E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36836889.89 | 0.111115E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.693698E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172362E+10 |
February | 0.136988E+10 | 0.589718E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157690E+10 |
March | 0.163688E+10 | 0.667903E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127715E+10 |
April | 0.145246E+10 | 0.576934E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 572241.17 | 0.845532E+09 |
May | 0.157341E+10 | 0.610094E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2131059.72 | 0.507746E+09 |
June | 0.156904E+10 | 0.598382E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18895648.69 | 0.270202E+09 |
July | 0.145684E+10 | 0.564470E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44314965.42 | 0.103093E+09 |
August | 0.163688E+10 | 0.635515E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54725515.65 | 0.131175E+09 |
September | 0.145246E+10 | 0.585848E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6674979.80 | 0.299714E+09 |
October | 0.150994E+10 | 0.628367E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31485.76 | 0.730884E+09 |
November | 0.149520E+10 | 0.674065E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123857E+10 |
December | 0.145684E+10 | 0.677811E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147477E+10 |
Annual Sum or Average | 0.181198E+11 | 0.750281E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127346E+09 | 0.101794E+11 |
Minimum of Months | 0.136988E+10 | 0.564470E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103093E+09 |
Maximum of Months | 0.163688E+10 | 0.693698E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54725515.65 | 0.172362E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.450722E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113764E+10 |
February | 0.882782E+09 | 0.381786E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102338E+10 |
March | 0.105485E+10 | 0.429783E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862838E+09 |
April | 0.936002E+09 | 0.371082E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 382628.05 | 0.584309E+09 |
May | 0.101394E+10 | 0.390578E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1528301.83 | 0.358450E+09 |
June | 0.101113E+10 | 0.383354E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12347155.61 | 0.199830E+09 |
July | 0.938820E+09 | 0.362075E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28696835.16 | 83273544.15 |
August | 0.105485E+10 | 0.407732E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35500693.23 | 98265526.16 |
September | 0.936002E+09 | 0.377400E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4537041.47 | 0.200503E+09 |
October | 0.973041E+09 | 0.406071E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48270.71 | 0.471681E+09 |
November | 0.963541E+09 | 0.435614E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802501E+09 |
December | 0.938820E+09 | 0.442351E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965283E+09 |
Annual Sum or Average | 0.116768E+11 | 0.483855E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83040926.06 | 0.678796E+10 |
Minimum of Months | 0.882782E+09 | 0.362075E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83273544.15 |
Maximum of Months | 0.105485E+10 | 0.450722E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35500693.23 | 0.113764E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.274130E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.248656E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.295472E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.263917E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.284801E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.283424E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.265294E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.295472E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.263917E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.274130E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.270917E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.265294E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.328542E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.248656E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.295472E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147392E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128672E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105663E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295534.21 | 0.704728E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1797125.45 | 0.392176E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11566554.88 | 0.199965E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27870156.99 | 70656217.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34241897.91 | 90539906.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3509250.72 | 0.221896E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5213.18 | 0.559354E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107065E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129198E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79285733.33 | 0.841922E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70656217.42 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34241897.91 | 0.147392E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236481E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215530E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178326E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586445.69 | 0.118842E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3934030.43 | 0.686298E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23087416.77 | 0.343449E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57960682.79 | 0.107721E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66224133.92 | 0.150519E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6337212.39 | 0.377978E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10831.70 | 0.965238E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178443E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211338E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158141E+09 | 0.140208E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107721E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66224133.92 | 0.236481E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247017E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223353E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187903E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126085.81 | 0.126122E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1315582.72 | 0.783088E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17876283.47 | 0.414346E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43757356.53 | 0.148417E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59565555.56 | 0.179272E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5249151.28 | 0.425814E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102097E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178960E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211035E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127890E+09 | 0.147158E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148417E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59565555.56 | 0.247017E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10174.14 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10174.14 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10174.14 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10174.14 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10174.14 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10174.14 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10174.14 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10174.14 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10174.14 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10174.14 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10174.14 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10174.14 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:40 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1144.84 | 31-JAN-01:00 |
February | 2010.79 | 01-FEB-10:09 | 1034.33 | 15-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1152.59 | 05-FEB-07:53 |
March | 2010.79 | 01-MAR-10:09 | 807.19 | 02-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 929.75 | 12-MAR-10:00 |
April | 2010.79 | 03-APR-09:09 | 603.91 | 21-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | 07-APR-13:00 | 712.93 | 11-APR-04:00 |
May | 2010.79 | 01-MAY-09:09 | 603.16 | 08-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.69 | 29-MAY-11:52 | 421.00 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 588.24 | 29-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.64 | 19-JUN-21:02 | 235.88 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 583.74 | 24-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.36 | 09-JUL-14:00 | 114.51 | 02-JUL-18:40 |
August | 2010.79 | 01-AUG-09:09 | 614.36 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.15 | 04-AUG-21:02 | 160.03 | 20-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 640.19 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.65 | 14-SEP-14:00 | 224.65 | 17-SEP-10:00 |
October | 2010.79 | 02-OCT-09:09 | 895.25 | 31-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | 25-OCT-11:00 | 619.88 | 08-OCT-08:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 952.24 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1244.30 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 583.74 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.51 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 123.15 | 1244.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:40 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 763.61 | 31-JAN-01:00 |
February | 1295.83 | 01-FEB-10:09 | 674.54 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 835.03 | 05-FEB-09:00 |
March | 1295.83 | 01-MAR-10:09 | 587.08 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 700.61 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 377.92 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 | 07-APR-13:00 | 464.31 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 389.37 | 19-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.84 | 29-MAY-12:16 | 278.87 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 | 19-JUN-21:02 | 155.58 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.11 | 09-JUL-13:43 | 79.51 | 02-JUL-18:40 |
August | 1295.83 | 01-AUG-09:09 | 378.16 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.07 | 04-AUG-21:02 | 108.94 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 398.70 | 26-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 14-SEP-14:00 | 147.30 | 17-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 582.73 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 25-OCT-11:00 | 466.68 | 08-OCT-08:20 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 628.21 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 818.46 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.51 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 82.07 | 835.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1155.51 | 31-JAN-01:00 |
February | 2010.83 | 01-FEB-10:09 | 1027.23 | 15-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1185.86 | 05-FEB-10:00 |
March | 2010.83 | 01-MAR-10:09 | 730.41 | 02-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1021.26 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 600.21 | 21-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 07-APR-13:00 | 710.07 | 11-APR-04:00 |
May | 2010.83 | 01-MAY-09:09 | 604.61 | 08-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.82 | 29-MAY-11:55 | 418.44 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 593.59 | 29-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.54 | 19-JUN-21:02 | 236.93 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 589.61 | 24-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.36 | 09-JUL-14:00 | 117.48 | 02-JUL-18:40 |
August | 2010.83 | 01-AUG-09:09 | 614.34 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.85 | 04-AUG-21:02 | 158.57 | 20-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 635.71 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.60 | 14-SEP-14:00 | 219.43 | 17-SEP-10:00 |
October | 2010.83 | 02-OCT-09:09 | 858.81 | 31-OCT-15:00 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 25-OCT-11:00 | 650.21 | 08-OCT-08:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 946.83 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1227.82 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 589.61 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.48 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 122.85 | 1227.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 799.43 | 31-JAN-01:00 |
February | 1295.83 | 01-FEB-10:09 | 656.63 | 15-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 811.45 | 05-FEB-07:53 |
March | 1295.83 | 01-MAR-10:09 | 514.25 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 693.18 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 402.31 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 | 07-APR-13:00 | 539.10 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 397.37 | 08-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 | 29-MAY-12:16 | 310.60 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 390.75 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.07 | 19-JUN-21:02 | 184.36 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 390.29 | 24-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.57 | 09-JUL-14:00 | 112.01 | 02-JUL-18:00 |
August | 1295.83 | 01-AUG-09:09 | 403.57 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.33 | 04-AUG-21:02 | 127.69 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 488.59 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 14-SEP-14:00 | 164.60 | 17-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 559.69 | 06-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 25-OCT-11:00 | 448.07 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 689.13 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 909.75 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 390.29 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.01 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 80.33 | 909.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:40 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2372.57 | 31-JAN-01:00 |
February | 2010.79 | 01-FEB-10:09 | 1033.14 | 15-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2421.14 | 06-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 802.47 | 02-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1847.09 | 21-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 598.12 | 21-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.91 | 07-APR-13:00 | 1492.41 | 11-APR-04:00 |
May | 2010.79 | 01-MAY-09:09 | 597.32 | 08-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.80 | 29-MAY-12:00 | 886.76 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 581.56 | 29-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.65 | 19-JUN-21:02 | 524.55 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 545.86 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.48 | 09-JUL-13:54 | 234.60 | 11-JUL-05:00 |
August | 2010.79 | 01-AUG-09:09 | 609.17 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.16 | 04-AUG-21:02 | 345.36 | 20-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 636.47 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.93 | 14-SEP-14:00 | 456.13 | 17-SEP-10:00 |
October | 2010.79 | 02-OCT-09:09 | 892.45 | 31-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 | 25-OCT-11:00 | 1251.33 | 08-OCT-08:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1940.42 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2406.31 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.60 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 289.16 | 2421.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 739.33 | 02-JAN-16:40 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1601.44 | 31-JAN-01:00 |
February | 1239.33 | 01-FEB-08:09 | 672.87 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1684.23 | 05-FEB-09:00 |
March | 1239.33 | 01-MAR-08:09 | 582.93 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1425.04 | 12-MAR-10:00 |
April | 1239.33 | 03-APR-07:10 | 373.65 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 | 07-APR-13:00 | 1003.17 | 11-APR-04:00 |
May | 1239.33 | 01-MAY-07:10 | 385.74 | 19-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.19 | 29-MAY-11:52 | 600.77 | 03-MAY-04:00 |
June | 1239.33 | 01-JUN-07:10 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.01 | 19-JUN-21:02 | 355.87 | 02-JUN-22:00 |
July | 1239.33 | 03-JUL-07:10 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.68 | 09-JUL-13:53 | 182.67 | 02-JUL-18:53 |
August | 1239.33 | 01-AUG-07:10 | 374.57 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.99 | 04-AUG-21:02 | 247.81 | 20-AUG-06:00 |
September | 1239.33 | 01-SEP-07:10 | 395.77 | 27-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.79 | 14-SEP-14:10 | 327.95 | 10-SEP-08:20 |
October | 1239.33 | 02-OCT-07:10 | 578.70 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 | 25-OCT-11:00 | 983.36 | 08-OCT-08:30 |
November | 1239.33 | 01-NOV-07:10 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1312.35 | 23-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 739.33 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1604.15 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.67 | |||||
Maximum of Months | 1239.33 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 191.99 | 1684.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2524.51 | 31-JAN-01:00 |
February | 2010.83 | 01-FEB-10:09 | 1026.03 | 15-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2596.50 | 05-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 637.90 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2155.10 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 594.24 | 21-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 | 07-APR-13:00 | 1536.56 | 11-APR-04:00 |
May | 2010.83 | 01-MAY-09:09 | 598.83 | 08-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.75 | 29-MAY-11:55 | 911.21 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 587.16 | 29-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.19 | 19-JUN-21:02 | 529.60 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 582.97 | 24-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.41 | 09-JUL-13:54 | 256.71 | 02-JUL-18:53 |
August | 2010.83 | 01-AUG-09:09 | 609.14 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.97 | 04-AUG-21:02 | 357.80 | 20-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 631.78 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.81 | 14-SEP-14:00 | 498.91 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 855.98 | 31-OCT-15:00 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 25-OCT-11:00 | 1423.50 | 08-OCT-09:50 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2037.46 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2583.73 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 582.97 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.71 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 287.97 | 2596.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1630.70 | 31-JAN-01:00 |
February | 1295.83 | 01-FEB-10:09 | 654.67 | 15-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1614.07 | 06-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 508.36 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1301.30 | 21-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 399.37 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 | 07-APR-13:00 | 1049.39 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 394.19 | 08-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.03 | 29-MAY-11:52 | 634.93 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 387.20 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.14 | 19-JUN-21:02 | 418.20 | 03-JUN-19:00 |
July | 1295.83 | 03-JUL-09:09 | 386.70 | 24-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.05 | 09-JUL-13:53 | 254.22 | 02-JUL-17:30 |
August | 1295.83 | 01-AUG-09:09 | 400.74 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.47 | 04-AUG-21:02 | 257.44 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 482.01 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.29 | 14-SEP-14:00 | 333.19 | 10-SEP-19:55 |
October | 1295.83 | 02-OCT-09:09 | 555.03 | 06-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 | 25-OCT-11:00 | 873.31 | 17-OCT-24:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1330.03 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1660.21 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 386.70 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.22 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 190.47 | 1660.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:40 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2913.09 | 14-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 1032.91 | 15-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3017.41 | 06-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 801.91 | 02-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2286.73 | 21-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 597.88 | 21-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.57 | 07-APR-13:00 | 1731.17 | 11-APR-04:00 |
May | 2010.79 | 01-MAY-09:09 | 597.08 | 08-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.15 | 29-MAY-12:10 | 1024.44 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 581.28 | 29-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.05 | 19-JUN-21:02 | 637.54 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 545.86 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.24 | 09-JUL-13:43 | 342.21 | 02-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 608.96 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.96 | 04-AUG-21:02 | 406.60 | 20-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 636.33 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.57 | 14-SEP-14:00 | 524.72 | 23-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 891.93 | 31-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.88 | 25-OCT-11:00 | 1423.96 | 17-OCT-24:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2230.86 | 22-NOV-22:03 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3001.85 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.21 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 352.96 | 3017.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:40 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1948.86 | 14-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 672.75 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2011.67 | 06-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 582.67 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1557.72 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 373.48 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.71 | 07-APR-13:00 | 1164.05 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 385.59 | 19-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.13 | 29-MAY-12:04 | 695.47 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.17 | 19-JUN-21:02 | 432.25 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.16 | 09-JUL-13:50 | 255.26 | 02-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 374.39 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.39 | 04-AUG-21:02 | 292.17 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 395.63 | 27-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.05 | 14-SEP-14:00 | 408.75 | 10-SEP-07:50 |
October | 1295.83 | 02-OCT-09:09 | 578.38 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 | 25-OCT-11:00 | 1074.61 | 08-OCT-08:30 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1489.26 | 22-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2001.26 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.26 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 234.39 | 2011.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2923.32 | 14-JAN-05:58 |
February | 2010.83 | 01-FEB-10:09 | 1025.79 | 15-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3017.28 | 06-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 637.75 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2369.14 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 594.00 | 21-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.50 | 07-APR-13:00 | 1787.41 | 11-APR-04:00 |
May | 2010.83 | 01-MAY-09:09 | 598.60 | 08-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.10 | 29-MAY-12:04 | 1056.15 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 586.91 | 29-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.48 | 19-JUN-21:02 | 644.31 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 582.70 | 24-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.23 | 09-JUL-13:50 | 362.17 | 02-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 608.93 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.48 | 04-AUG-21:02 | 422.25 | 20-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 631.62 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.45 | 14-SEP-14:00 | 584.46 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 855.41 | 31-OCT-15:00 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 | 25-OCT-11:00 | 1570.34 | 08-OCT-09:50 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2295.77 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3005.21 | 31-DEC-21:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 582.70 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.17 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 351.48 | 3017.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1948.87 | 14-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 654.51 | 15-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2011.46 | 06-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 507.91 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1571.70 | 21-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 399.26 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.71 | 07-APR-13:00 | 1228.25 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 394.06 | 08-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.20 | 29-MAY-12:06 | 743.56 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 387.06 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.57 | 19-JUN-21:02 | 525.96 | 03-JUN-17:40 |
July | 1295.83 | 03-JUL-09:09 | 386.56 | 24-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.16 | 09-JUL-13:42 | 334.39 | 02-JUL-17:40 |
August | 1295.83 | 01-AUG-09:09 | 400.63 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.45 | 04-AUG-21:02 | 304.48 | 20-AUG-05:53 |
September | 1295.83 | 01-SEP-09:09 | 481.50 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.05 | 14-SEP-14:00 | 413.90 | 10-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 554.65 | 06-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.25 | 25-OCT-11:00 | 1029.95 | 17-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1518.17 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2004.84 | 31-DEC-21:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 386.56 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.48 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 232.45 | 2011.46 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2868.67 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2868.67 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2868.67 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2868.67 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2868.67 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2868.67 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2868.67 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2868.67 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2868.67 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2868.67 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2868.67 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2868.67 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2522.52 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2534.88 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1895.65 | 12-MAR-10:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.59 | 07-APR-13:00 | 1530.16 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.58 | 29-MAY-12:00 | 902.36 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.27 | 19-JUN-21:02 | 486.35 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.10 | 09-JUL-14:00 | 221.42 | 11-JUL-04:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.80 | 12-AUG-18:53 | 335.71 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.86 | 14-SEP-14:00 | 443.18 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 | 25-OCT-11:00 | 1319.68 | 08-OCT-08:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2097.01 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2717.10 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.80 | 2717.10 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4258.57 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4242.90 | 05-FEB-07:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3109.69 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.87 | 07-APR-13:00 | 2650.55 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.95 | 29-MAY-12:00 | 1557.97 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.59 | 19-JUN-21:02 | 863.47 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.41 | 09-JUL-14:00 | 380.64 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.88 | 12-AUG-18:53 | 576.01 | 20-AUG-05:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.05 | 14-SEP-14:00 | 768.89 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 25-OCT-11:00 | 2273.72 | 08-OCT-07:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3553.91 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4401.85 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.64 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.88 | 4401.85 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4309.76 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4211.51 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3465.25 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 08-APR-10:00 | 2743.80 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.50 | 30-MAY-13:00 | 1631.55 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.17 | 19-JUN-21:02 | 912.91 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.11 | 07-JUL-22:00 | 503.25 | 02-JUL-18:23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.80 | 04-AUG-21:02 | 585.56 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.59 | 14-SEP-14:00 | 811.62 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2270.30 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3488.02 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4273.35 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.25 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.80 | 4309.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 89894.06 | 02-JAN-07:03 | 14361.80 | 13565.72 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91692.71 | 21-FEB-07:05 | 7180.90 | 6782.86 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 92030.84 | 13-MAR-06:03 | 10771.35 | 10174.29 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95881.47 | 17-APR-06:11 | 28723.60 | 27131.43 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92279.17 | 22-MAY-06:11 | 28723.60 | 27131.43 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98029.21 | 09-JUN-06:11 | 28723.60 | 27131.43 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 103447.65 | 11-JUL-06:11 | 32314.05 | 30522.86 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 104272.12 | 19-AUG-06:11 | 16157.03 | 10173.84 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 105497.14 | 15-SEP-06:11 | 32314.05 | 30522.86 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99395.63 | 23-OCT-06:11 | 32314.05 | 30522.86 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 97914.50 | 13-NOV-07:05 | 7180.90 | 6782.86 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 94157.13 | 18-DEC-07:03 | 10771.35 | 10174.29 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 89894.06 | 7180.90 | 6782.86 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 105497.14 | 32314.05 | 30522.86 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 72910.03 | 24-JAN-06:03 | 6448.95 | 2149.44 | 30589.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 79982.25 | 21-FEB-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81112.99 | 06-MAR-05:11 | 0.00 | 4836.24 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81410.98 | 11-APR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88559.24 | 30-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87628.02 | 12-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 86502.54 | 24-JUL-04:23 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86938.52 | 07-AUG-04:23 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88028.27 | 15-SEP-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86643.08 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87744.75 | 13-NOV-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82309.81 | 26-DEC-05:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 72910.03 | 0.00 | 2149.44 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88559.24 | 6448.95 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22518.54 | 17-JAN-19:20 | 3224.48 | 6091.48 | 15294.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23967.44 | 03-FEB-10:00 | 30632.53 | 18274.19 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66307.67 | 29-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72524.98 | 10-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73639.92 | 31-MAY-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75124.62 | 12-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 72336.46 | 01-JUL-04:12 | 0.00 | 3045.61 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78511.84 | 07-AUG-04:14 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75805.29 | 18-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73185.76 | 17-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 67760.32 | 10-NOV-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26240.87 | 29-DEC-14:40 | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 22518.54 | 0.00 | 2686.80 | 15294.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78511.84 | 30632.53 | 18274.19 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15847.83 | 20-JAN-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15925.90 | 17-FEB-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27751.51 | 29-MAR-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68144.99 | 08-APR-05:03 | 6448.95 | 4060.81 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75039.19 | 30-MAY-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76108.61 | 12-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76703.10 | 05-JUL-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81087.58 | 28-AUG-04:14 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74064.39 | 06-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70561.74 | 06-OCT-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26873.67 | 03-NOV-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15562.28 | 20-DEC-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15562.28 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81087.58 | 15316.26 | 9137.09 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2319.05 | 24-JAN-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.15 |
February | 2700.25 | 20-FEB-13:22 | 506.08 | 151.62 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.28 |
March | 6208.57 | 27-MAR-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.22 |
April | 7373.02 | 26-APR-13:40 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.45 |
May | 15380.69 | 29-MAY-14:52 | 506.08 | 151.62 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.91 |
June | 15655.24 | 25-JUN-12:23 | 404.87 | 121.30 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 |
July | 16455.91 | 04-JUL-16:32 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.16 |
August | 15945.45 | 13-AUG-15:01 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 39.35 | 0.00 |
September | 15835.85 | 04-SEP-13:31 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 |
October | 8308.87 | 06-OCT-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.01 |
November | 4782.21 | 03-NOV-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.57 |
December | 3275.42 | 26-DEC-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2319.05 | 404.87 | 121.30 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16455.91 | 2010.79 | 545.86 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 39.35 | 213.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4689.17 | 19-JAN-09:30 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.45 |
February | 6162.93 | 22-FEB-09:20 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.17 |
March | 11558.33 | 26-MAR-08:13 | 195.68 | 58.63 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.23 |
April | 19639.11 | 16-APR-07:33 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.39 |
May | 23441.02 | 29-MAY-07:31 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.45 |
June | 21283.11 | 25-JUN-09:02 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 |
July | 23512.74 | 02-JUL-07:21 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.42 |
August | 20794.32 | 13-AUG-09:42 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 11.13 | 0.00 |
September | 23787.10 | 04-SEP-08:11 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 |
October | 19035.39 | 15-OCT-09:13 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.08 |
November | 6850.45 | 02-NOV-08:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.74 |
December | 5168.60 | 20-DEC-09:30 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4689.17 | 195.68 | 58.63 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23787.10 | 2478.65 | 703.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 11.13 | 143.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16956.50 | 29-JAN-13:33 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.45 |
February | 24279.52 | 20-FEB-13:22 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.66 |
March | 18375.73 | 01-MAR-13:05 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 |
April | 18022.71 | 16-APR-11:33 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.78 |
May | 24439.06 | 29-MAY-12:12 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 | 0.00 |
June | 23486.03 | 25-JUN-12:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.35 |
July | 24877.87 | 30-JUL-13:02 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 |
August | 25083.90 | 27-AUG-12:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 |
September | 27099.98 | 04-SEP-12:11 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.94 |
October | 25103.98 | 09-OCT-13:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.48 |
November | 19177.94 | 02-NOV-12:40 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.13 |
December | 25640.58 | 17-DEC-12:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16956.50 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27099.98 | 3846.30 | 1091.75 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 | 482.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7015.37 | 17-JAN-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 |
February | 18365.89 | 20-FEB-15:23 | 260.91 | 78.17 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.84 |
March | 19600.80 | 26-MAR-16:32 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.52 |
April | 26497.88 | 09-APR-16:22 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.13 |
May | 24633.72 | 29-MAY-14:52 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.28 |
June | 27056.81 | 18-JUN-15:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.44 |
July | 30289.21 | 02-JUL-16:01 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.19 |
August | 26876.38 | 13-AUG-15:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 15.47 | 0.00 |
September | 29208.56 | 10-SEP-15:31 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.93 |
October | 25729.06 | 09-OCT-14:22 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.61 |
November | 14995.92 | 10-NOV-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.39 |
December | 20466.67 | 17-DEC-14:12 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7015.37 | 260.91 | 78.17 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30289.21 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 15.47 | 186.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1729.13 | 20-JAN-12:50 | 1058.31 | 545.86 | 1920.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.26 |
February | 1872.53 | 01-FEB-13:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.71 |
March | 3137.45 | 28-MAR-13:50 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.21 |
April | 5529.13 | 07-APR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 26.73 | 0.00 |
May | 11207.89 | 31-MAY-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11233.61 | 22-JUN-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 |
July | 14693.85 | 09-JUL-14:31 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 76.02 | 0.00 |
August | 14217.05 | 13-AUG-15:01 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 99.26 | 0.00 |
September | 10689.75 | 02-SEP-05:02 | 1012.16 | 637.34 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.92 |
October | 5762.10 | 05-OCT-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 |
November | 2646.01 | 03-NOV-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.52 |
December | 1780.77 | 21-DEC-13:30 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1729.13 | 708.51 | 212.27 | 1920.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14693.85 | 3846.22 | 1091.73 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 99.26 | 191.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3132.24 | 19-JAN-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.65 |
February | 4422.36 | 03-FEB-10:00 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.96 |
March | 9734.62 | 29-MAR-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.93 |
April | 13027.10 | 16-APR-08:53 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.06 |
May | 24362.07 | 28-MAY-08:51 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.44 |
June | 23958.41 | 04-JUN-09:11 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.98 |
July | 26146.14 | 02-JUL-08:51 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.60 |
August | 23391.20 | 20-AUG-09:02 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.36 |
September | 25206.18 | 04-SEP-09:01 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.35 |
October | 17922.88 | 15-OCT-10:22 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.34 |
November | 6808.20 | 02-NOV-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.92 |
December | 3466.61 | 20-DEC-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3132.24 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.62 | |
Maximum of Months | 26146.14 | 2478.65 | 703.55 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17281.72 | 05-JAN-13:10 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.66 |
February | 23252.54 | 19-FEB-12:43 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.53 |
March | 18417.94 | 01-MAR-13:20 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.11 |
April | 17318.35 | 07-APR-12:30 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 23.53 | 0.00 |
May | 23029.11 | 28-MAY-14:51 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.82 |
June | 22796.45 | 18-JUN-12:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.26 |
July | 23639.78 | 09-JUL-11:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 62.97 | 0.00 |
August | 24958.40 | 20-AUG-12:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.75 |
September | 27091.50 | 04-SEP-11:41 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.65 |
October | 26639.91 | 15-OCT-12:21 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.27 |
November | 19576.99 | 02-NOV-13:05 | 4021.67 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.75 |
December | 23510.94 | 17-DEC-13:02 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17281.72 | 404.87 | 121.30 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27091.50 | 4021.67 | 1091.75 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 62.97 | 550.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3973.02 | 31-JAN-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6228.23 | 24-FEB-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.63 |
March | 11048.94 | 29-MAR-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.34 |
April | 25277.47 | 09-APR-16:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.82 |
May | 24739.51 | 14-MAY-16:11 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.69 |
June | 26770.59 | 18-JUN-17:01 | 0.00 | 175.88 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.11 |
July | 27168.19 | 02-JUL-16:11 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.91 |
August | 25440.16 | 20-AUG-16:21 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.49 |
September | 26526.06 | 10-SEP-15:41 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.86 |
October | 22757.47 | 15-OCT-14:21 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.95 |
November | 7151.22 | 03-NOV-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.06 |
December | 3888.22 | 08-DEC-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3888.22 | 0.00 | 136.80 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27168.19 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1468.98 | 20-JAN-15:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.87 |
February | 1495.93 | 24-FEB-15:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.60 |
March | 2927.67 | 28-MAR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.18 |
April | 6260.88 | 07-APR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 31.36 | 0.00 |
May | 16917.02 | 29-MAY-14:02 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.78 |
June | 13184.16 | 22-JUN-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.25 |
July | 16953.76 | 09-JUL-14:42 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.42 | 0.00 |
August | 16998.49 | 13-AUG-15:01 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 109.86 | 0.00 |
September | 12579.25 | 02-SEP-05:02 | 1012.16 | 637.34 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.46 |
October | 6116.14 | 04-OCT-13:40 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 0.00 |
November | 2470.64 | 02-NOV-13:50 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.77 |
December | 1453.79 | 20-DEC-13:50 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1453.79 | 607.30 | 181.95 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16998.49 | 2010.79 | 637.34 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 109.86 | 316.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1298.86 | 19-JAN-10:30 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.81 |
February | 1710.25 | 22-FEB-10:10 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.91 |
March | 7312.37 | 29-MAR-09:30 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.81 |
April | 11443.23 | 28-APR-08:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.80 |
May | 25761.06 | 29-MAY-08:61 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.58 |
June | 23120.87 | 25-JUN-09:02 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.88 |
July | 23741.47 | 02-JUL-09:02 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.78 |
August | 23612.51 | 20-AUG-09:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.07 |
September | 23117.99 | 04-SEP-09:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.49 |
October | 12764.76 | 15-OCT-09:13 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.98 |
November | 3754.22 | 02-NOV-09:40 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.68 |
December | 1299.59 | 20-DEC-10:00 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1298.86 | 260.91 | 78.17 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.49 | |
Maximum of Months | 25761.06 | 2591.66 | 703.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14286.54 | 19-JAN-13:30 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.56 |
February | 14957.29 | 22-FEB-13:30 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.36 |
March | 18850.82 | 01-MAR-13:30 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.83 |
April | 19220.75 | 09-APR-13:32 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.18 |
May | 26583.92 | 29-MAY-13:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.87 |
June | 24919.70 | 25-JUN-12:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.18 |
July | 25201.23 | 30-JUL-12:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.07 |
August | 27433.04 | 20-AUG-13:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.36 |
September | 27188.41 | 04-SEP-12:32 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.92 |
October | 26052.97 | 15-OCT-12:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.36 |
November | 20133.78 | 02-NOV-13:10 | 4021.67 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.85 |
December | 25844.06 | 17-DEC-13:32 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14286.54 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.07 | |
Maximum of Months | 27433.04 | 4021.67 | 1091.75 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3593.29 | 19-JAN-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.55 |
February | 5394.10 | 24-FEB-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.79 |
March | 10883.83 | 29-MAR-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.62 |
April | 25430.93 | 09-APR-16:11 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.24 |
May | 26136.25 | 14-MAY-16:01 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.27 |
June | 26163.67 | 18-JUN-15:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.51 |
July | 26246.80 | 02-JUL-16:21 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.12 |
August | 25598.79 | 13-AUG-15:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 42.01 | 0.00 |
September | 25309.49 | 10-SEP-15:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.70 |
October | 18031.35 | 15-OCT-15:12 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.43 |
November | 6791.99 | 03-NOV-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.34 |
December | 3029.64 | 08-DEC-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3029.64 | 326.14 | 97.71 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26246.80 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 42.01 | 455.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4974.14 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.21 |
February | 4802.54 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.62 |
March | 4199.70 | 28-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.20 |
April | 6668.57 | 10-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.41 |
May | 10550.59 | 30-MAY-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 | 0.00 |
June | 13303.67 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 |
July | 13970.92 | 11-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.64 |
August | 15649.55 | 14-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 |
September | 13685.76 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.81 |
October | 8171.93 | 23-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.52 |
November | 6943.92 | 13-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.27 |
December | 3133.68 | 18-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3133.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15649.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 | 529.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7419.21 | 31-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2666.72 |
February | 9393.05 | 13-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.69 |
March | 7405.33 | 17-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1848.50 |
April | 3762.61 | 10-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.17 |
May | 7551.66 | 30-MAY-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.26 | 0.00 |
June | 7125.46 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.53 |
July | 7847.81 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.76 |
August | 8759.03 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 |
September | 8403.69 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.66 |
October | 4580.59 | 05-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.40 |
November | 7793.96 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1195.97 |
December | 6566.76 | 23-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1727.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3762.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9393.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.26 | 2666.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3092.53 |
February | 1254.25 | 20-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 846.75 |
March | 6297.15 | 03-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.00 |
April | 13314.22 | 07-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
May | 20001.15 | 30-MAY-13:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.41 | 0.00 |
June | 20399.77 | 19-JUN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.89 | 0.00 |
July | 19426.21 | 10-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.88 | 0.00 |
August | 19422.88 | 22-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.22 | 0.00 |
September | 20142.35 | 01-SEP-13:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.37 | 0.00 |
October | 11004.63 | 04-OCT-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.10 |
November | 3892.70 | 03-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.72 |
December | 1467.31 | 17-DEC-13:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.89 | 3092.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1945.50 | 20-JAN-16:30 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4053.18 | 14-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6957.33 | 31-MAR-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8337.04 | 23-APR-17:41 | 0.00 | 56.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3492.53 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5341.58 | 30-JUN-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7319.81 | 31-JUL-23:57 | 0.00 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8139.30 | 20-AUG-17:32 | 0.00 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3392.50 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5141.77 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5820.55 | 06-NOV-16:10 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7776.33 | 17-DEC-15:55 | 23.38 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1945.50 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8337.04 | 222.14 | 146.32 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1612.03 | 20-JAN-16:40 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3615.26 | 22-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6126.06 | 31-MAR-23:40 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7672.14 | 09-APR-17:31 | 0.00 | 56.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3313.27 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5010.19 | 30-JUN-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6932.54 | 31-JUL-23:57 | 0.00 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7701.55 | 31-AUG-17:40 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3106.67 | 30-SEP-23:30 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4495.72 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5468.80 | 03-NOV-16:00 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7106.53 | 08-DEC-16:10 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1612.03 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7701.55 | 222.14 | 146.32 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1517.17 | 20-JAN-16:40 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3475.66 | 22-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5670.62 | 29-MAR-17:20 | 23.38 | 48.77 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7732.01 | 09-APR-17:23 | 0.00 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3261.70 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4938.17 | 30-JUN-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6927.21 | 31-JUL-23:57 | 0.00 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7855.08 | 13-AUG-18:22 | 0.00 | 40.65 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2823.23 | 30-SEP-23:20 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3992.80 | 15-OCT-16:50 | 11.69 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5444.51 | 03-NOV-16:00 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6901.32 | 08-DEC-16:10 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1517.17 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7855.08 | 222.14 | 146.32 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90616.02 | 20-JAN-17:00 | 4808.68 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182029.19 | 22-FEB-17:00 | 4808.68 | 2868.67 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357769.01 | 31-MAR-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366456.49 | 10-APR-16:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175642.21 | 31-MAY-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267428.25 | 30-JUN-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360483.72 | 31-JUL-23:57 | 0.00 | 478.10 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 393351.49 | 24-AUG-18:23 | 3037.06 | 5737.43 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176204.84 | 30-SEP-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267629.19 | 31-OCT-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275699.41 | 06-NOV-17:00 | 4808.68 | 2868.67 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366793.01 | 18-DEC-17:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90616.02 | 0.00 | 159.37 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 393351.49 | 4808.68 | 5737.43 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.141965E+13 | 997648.46 | 19-JAN-16:00 | 0.207891E+12 | 1501293.39 | 02-JAN-05:10 |
February | 0.168833E+13 | 1107865.69 | 02-FEB-16:30 | 0.133241E+12 | 1034359.51 | 06-FEB-06:10 |
March | 0.221476E+13 | 1312911.23 | 27-MAR-15:00 | 0.349447E+11 | 441493.08 | 13-MAR-04:10 |
April | 0.242897E+13 | 1696865.26 | 07-APR-15:09 | 0.863281E+10 | 395773.38 | 03-APR-05:10 |
May | 0.150501E+13 | 1389420.87 | 30-MAY-14:09 | 0.752766E+09 | 148492.94 | 30-MAY-11:20 |
June | 0.209730E+13 | 1560818.81 | 22-JUN-15:30 | 0.125594E+10 | 180680.29 | 01-JUN-14:00 |
July | 0.266979E+13 | 1696465.64 | 11-JUL-15:09 | 0.490349E+09 | 74363.72 | 11-JUL-16:10 |
August | 0.310629E+13 | 1895837.77 | 22-AUG-14:30 | 0.113459E+10 | 162018.16 | 24-AUG-18:40 |
September | 0.156577E+13 | 1296522.99 | 05-SEP-10:09 | 0.217076E+09 | 95690.74 | 01-SEP-16:40 |
October | 0.186447E+13 | 1383428.83 | 04-OCT-15:00 | 0.877209E+09 | 64391.46 | 28-OCT-05:10 |
November | 0.210690E+13 | 1348488.01 | 03-NOV-14:09 | 0.373116E+11 | 586315.16 | 24-NOV-05:10 |
December | 0.254512E+13 | 1401625.26 | 18-DEC-16:40 | 0.913780E+11 | 694132.98 | 11-DEC-05:10 |
Annual Sum or Average | 0.252123E+14 | 0.518127E+12 | ||||
Minimum of Months | 0.141965E+13 | 997648.46 | 0.217076E+09 | 64391.46 | ||
Maximum of Months | 0.310629E+13 | 1895837.77 | 0.207891E+12 | 1501293.39 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.166977E+11 | 50558.75 | 31-JAN-11:50 | 0.00 | 0.00 |
February | 0.242189E+11 | 59827.92 | 22-FEB-11:30 | 0.00 | 0.00 |
March | 0.377002E+11 | 78039.49 | 29-MAR-11:00 | 0.00 | 0.00 |
April | 0.434918E+11 | 83049.85 | 12-APR-11:00 | 0.00 | 0.00 |
May | 0.545554E+11 | 84444.02 | 11-MAY-11:00 | 0.00 | 0.00 |
June | 0.562411E+11 | 87214.16 | 02-JUN-11:50 | 0.00 | 0.00 |
July | 0.554138E+11 | 82701.55 | 02-JUL-11:00 | 0.00 | 0.00 |
August | 0.567860E+11 | 77936.84 | 10-AUG-11:30 | 0.00 | 0.00 |
September | 0.391282E+11 | 72835.72 | 10-SEP-11:30 | 0.00 | 0.00 |
October | 0.352911E+11 | 63020.77 | 08-OCT-11:30 | 0.00 | 0.00 |
November | 0.198609E+11 | 49815.93 | 02-NOV-11:30 | 0.00 | 0.00 |
December | 0.147946E+11 | 40859.46 | 02-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.454180E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.147946E+11 | 40859.46 | 0.00 | 0.00 | |
Maximum of Months | 0.567860E+11 | 87214.16 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.146260E+12 | 0.309644E+11 | 0.766053E+12 | 0.136275E+12 | 0.156080E+12 | 0.134341E+11 | 0.00 | 0.720408E+10 | 0.527306E+09 | 0.117133E+12 | 0.550459E+10 | 0.402109E+11 | 0.00 |
February | 0.130967E+12 | 0.247047E+11 | 0.978954E+12 | 0.124864E+12 | 0.141357E+12 | 0.126937E+11 | 0.00 | 0.207532E+11 | 0.140605E+10 | 0.210559E+12 | 0.517533E+10 | 0.368925E+11 | 0.00 |
March | 0.154109E+12 | 0.228844E+11 | 0.141687E+13 | 0.144887E+12 | 0.165832E+12 | 0.205828E+11 | 0.00 | 0.412484E+11 | 0.499358E+10 | 0.196525E+12 | 0.440545E+10 | 0.424159E+11 | 0.00 |
April | 0.136790E+12 | 0.180143E+11 | 0.165903E+13 | 0.135268E+12 | 0.176158E+12 | 0.232787E+11 | 0.00 | 0.845067E+11 | 0.233112E+11 | 0.133904E+12 | 0.214027E+10 | 0.365711E+11 | 0.00 |
May | 0.147077E+12 | 0.159828E+11 | 0.774844E+12 | 0.140580E+12 | 0.202788E+12 | 0.358317E+11 | 0.00 | 0.637301E+11 | 0.391864E+11 | 0.481489E+11 | 0.411237E+09 | 0.364289E+11 | 0.00 |
June | 0.146008E+12 | 0.143201E+11 | 0.106252E+13 | 0.139647E+12 | 0.224504E+12 | 0.544789E+11 | 0.00 | 0.271822E+12 | 0.130030E+12 | 0.167033E+11 | 0.370865E+10 | 0.335550E+11 | 0.00 |
July | 0.136860E+12 | 0.151248E+11 | 0.139340E+13 | 0.136200E+12 | 0.239125E+12 | 0.690101E+11 | 0.00 | 0.472051E+12 | 0.172152E+12 | 0.00 | 0.557149E+10 | 0.302895E+11 | 0.00 |
August | 0.152696E+12 | 0.171731E+11 | 0.173200E+13 | 0.144887E+12 | 0.252342E+12 | 0.704510E+11 | 0.00 | 0.533528E+12 | 0.159851E+12 | 0.625861E+10 | 0.441611E+10 | 0.326906E+11 | 0.00 |
September | 0.137182E+12 | 0.202329E+11 | 0.740713E+12 | 0.135267E+12 | 0.201745E+12 | 0.452427E+11 | 0.00 | 0.141337E+12 | 0.955490E+11 | 0.156805E+11 | 0.221696E+10 | 0.306004E+11 | 0.00 |
October | 0.143382E+12 | 0.254990E+11 | 0.108340E+13 | 0.136274E+12 | 0.192844E+12 | 0.336181E+11 | 0.00 | 0.833097E+11 | 0.382844E+11 | 0.931432E+11 | 0.111963E+10 | 0.335908E+11 | 0.00 |
November | 0.143932E+12 | 0.287784E+11 | 0.135889E+13 | 0.131109E+12 | 0.162799E+12 | 0.176575E+11 | 0.00 | 0.390500E+11 | 0.540287E+10 | 0.180578E+12 | 0.325448E+10 | 0.354451E+11 | 0.00 |
December | 0.141930E+12 | 0.319530E+11 | 0.170972E+13 | 0.136201E+12 | 0.159310E+12 | 0.165855E+11 | 0.00 | 0.475894E+11 | 0.383290E+10 | 0.255010E+12 | 0.534892E+10 | 0.376369E+11 | 0.00 |
Annual Sum or Average | 0.171719E+13 | 0.265632E+12 | 0.146764E+14 | 0.164146E+13 | 0.227488E+13 | 0.412865E+12 | 0.00 | 0.180613E+13 | 0.674527E+12 | 0.127364E+13 | 0.432731E+11 | 0.426328E+12 | 0.00 |
Minimum of Months | 0.130967E+12 | 0.143201E+11 | 0.740713E+12 | 0.124864E+12 | 0.141357E+12 | 0.126937E+11 | 0.00 | 0.720408E+10 | 0.527306E+09 | 0.00 | 0.411237E+09 | 0.302895E+11 | 0.00 |
Maximum of Months | 0.154109E+12 | 0.319530E+11 | 0.173200E+13 | 0.144887E+12 | 0.252342E+12 | 0.704510E+11 | 0.00 | 0.533528E+12 | 0.172152E+12 | 0.255010E+12 | 0.557149E+10 | 0.424159E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.207891E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.133241E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.349447E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.863281E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.752766E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.125594E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.490349E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.113459E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.217076E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.877209E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.373116E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.913780E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.518127E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.217076E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.207891E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 169722.15 | 02-JAN-16:40 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 154952.96 | 03-JAN-08:20 | 94919.37 | 02-JAN-06:19 | 23508.35 | 30-JAN-07:49 | 0.00 | 01-JAN-00:10 |
February | 165021.06 | 15-FEB-16:00 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 154946.78 | 28-FEB-08:20 | 89908.15 | 03-FEB-09:00 | 23662.17 | 10-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 153037.31 | 02-MAR-16:00 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 154947.19 | 16-MAR-07:19 | 125327.23 | 29-MAR-15:20 | 23743.79 | 27-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 147723.13 | 21-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 154944.94 | 21-APR-07:19 | 193735.43 | 07-APR-15:09 | 45286.45 | 07-APR-14:39 | 0.00 | 01-APR-00:10 |
May | 147763.35 | 08-MAY-07:10 | 22480.63 | 01-MAY-18:49 | 423497.50 | 01-MAY-07:10 | 154944.96 | 08-MAY-07:19 | 275461.04 | 30-MAY-09:20 | 48897.67 | 30-MAY-14:09 | 0.00 | 01-MAY-00:10 |
June | 147352.07 | 29-JUN-07:10 | 22480.63 | 01-JUN-19:19 | 541788.89 | 01-JUN-07:10 | 154944.74 | 29-JUN-07:19 | 250427.65 | 22-JUN-12:39 | 48557.81 | 01-JUN-14:50 | 0.00 | 01-JUN-00:10 |
July | 146899.19 | 24-JUL-07:10 | 22480.63 | 01-JUL-19:30 | 660080.29 | 03-JUL-07:10 | 154944.50 | 24-JUL-07:19 | 255134.20 | 11-JUL-14:50 | 47067.07 | 11-JUL-15:39 | 0.00 | 01-JUL-00:10 |
August | 148383.33 | 16-AUG-07:10 | 31088.59 | 16-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 154945.28 | 16-AUG-07:19 | 258556.77 | 22-AUG-14:30 | 49252.39 | 30-AUG-14:39 | 0.00 | 01-AUG-00:10 |
September | 150212.06 | 27-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 154946.24 | 27-SEP-07:19 | 215921.88 | 05-SEP-15:39 | 49868.07 | 01-SEP-14:09 | 0.00 | 01-SEP-00:10 |
October | 158804.52 | 31-OCT-15:00 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 154950.03 | 06-OCT-07:19 | 171676.12 | 05-OCT-15:00 | 47452.74 | 24-OCT-11:50 | 0.00 | 01-OCT-00:10 |
November | 169722.15 | 06-NOV-16:49 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 154950.96 | 30-NOV-08:20 | 127914.08 | 03-NOV-14:50 | 23661.20 | 04-NOV-12:09 | 0.00 | 01-NOV-00:10 |
December | 169722.15 | 01-DEC-16:30 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 154951.22 | 11-DEC-08:20 | 89095.36 | 18-DEC-14:20 | 23630.74 | 19-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 146899.19 | 22480.63 | 423497.50 | 154944.50 | 89095.36 | 23508.35 | 0.00 | |||||||
Maximum of Months | 169722.15 | 31088.59 | 778371.69 | 154952.96 | 275461.04 | 49868.07 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 8721.58 | 19-JAN-14:00 | 2991.43 | 12-JAN-14:39 | 76772.14 | 20-JAN-05:00 | 4520.72 | 02-JAN-07:10 | 53135.92 | 31-JAN-12:30 | 0.00 | 01-JAN-00:10 |
February | 15460.22 | 24-FEB-15:39 | 2338.47 | 24-FEB-14:30 | 100000.00 | 02-FEB-05:49 | 4520.72 | 01-FEB-07:10 | 53226.59 | 14-FEB-12:39 | 0.00 | 01-FEB-00:10 |
March | 129022.76 | 27-MAR-15:00 | 46088.18 | 27-MAR-15:00 | 100000.00 | 01-MAR-05:49 | 4520.72 | 01-MAR-07:10 | 52914.14 | 01-MAR-12:39 | 0.00 | 01-MAR-00:10 |
April | 303943.76 | 07-APR-15:50 | 79373.33 | 07-APR-14:39 | 100000.00 | 01-APR-04:19 | 4520.72 | 01-APR-06:10 | 51319.13 | 03-APR-11:30 | 0.00 | 01-APR-00:10 |
May | 271763.83 | 30-MAY-14:09 | 79373.33 | 30-MAY-09:50 | 100000.00 | 20-MAY-16:19 | 4520.72 | 01-MAY-20:10 | 47703.10 | 01-MAY-11:00 | 0.00 | 01-MAY-00:10 |
June | 320282.82 | 22-JUN-15:30 | 79373.33 | 01-JUN-09:00 | 100000.00 | 04-JUN-06:19 | 4520.72 | 01-JUN-10:09 | 44516.94 | 01-JUN-11:39 | 0.00 | 01-JUN-00:10 |
July | 330715.34 | 10-JUL-12:09 | 79373.33 | 01-JUL-10:20 | 0.00 | 01-JUL-00:10 | 4520.72 | 01-JUL-06:10 | 41369.02 | 03-JUL-11:20 | 0.00 | 01-JUL-00:10 |
August | 407412.53 | 22-AUG-14:30 | 79373.33 | 01-AUG-07:10 | 100000.00 | 20-AUG-13:39 | 4520.72 | 01-AUG-06:10 | 40350.88 | 31-AUG-11:00 | 0.00 | 01-AUG-00:10 |
September | 264131.90 | 01-SEP-13:39 | 79373.33 | 01-SEP-07:19 | 100000.00 | 10-SEP-15:00 | 4520.72 | 01-SEP-06:10 | 42475.88 | 29-SEP-11:39 | 0.00 | 01-SEP-00:10 |
October | 257145.70 | 04-OCT-13:20 | 79373.33 | 03-OCT-10:00 | 100000.00 | 07-OCT-16:19 | 4520.72 | 03-OCT-11:00 | 45759.94 | 31-OCT-11:30 | 0.00 | 01-OCT-00:10 |
November | 77447.34 | 03-NOV-14:09 | 44100.78 | 03-NOV-14:09 | 100000.00 | 01-NOV-04:19 | 4520.72 | 01-NOV-06:10 | 49085.19 | 30-NOV-12:30 | 0.00 | 01-NOV-00:10 |
December | 23220.66 | 21-DEC-14:50 | 3121.96 | 17-DEC-14:00 | 100000.00 | 01-DEC-05:00 | 4520.72 | 01-DEC-07:10 | 52074.98 | 29-DEC-12:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 8721.58 | 2338.47 | 0.00 | 4520.72 | 40350.88 | 0.00 | ||||||
Maximum of Months | 407412.53 | 79373.33 | 100000.00 | 4520.72 | 53226.59 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 997648.46 | 19-JAN-16:00 | 169722.15 | 423497.50 | 31088.59 | 154860.76 | 67007.83 | 23427.94 | 0.00 | 7207.28 | 681.11 |
February | 1107865.69 | 02-FEB-16:30 | 149873.23 | 541788.89 | 0.00 | 154849.98 | 78448.33 | 23430.24 | 0.00 | 12782.40 | 917.72 |
March | 1312911.23 | 27-MAR-15:00 | 145987.23 | 660080.29 | 0.00 | 154849.24 | 113499.92 | 23743.79 | 0.00 | 129022.76 | 46088.18 |
April | 1696865.26 | 07-APR-15:09 | 145987.23 | 778371.69 | 0.00 | 154849.24 | 193735.43 | 26886.69 | 0.00 | 297797.48 | 61574.79 |
May | 1389420.87 | 30-MAY-14:09 | 145987.23 | 423497.50 | 0.00 | 154722.86 | 239307.51 | 48897.67 | 0.00 | 271763.83 | 79373.33 |
June | 1560818.81 | 22-JUN-15:30 | 145987.23 | 541788.89 | 0.00 | 154849.24 | 238016.89 | 47517.50 | 0.00 | 320282.82 | 79373.33 |
July | 1696465.64 | 11-JUL-15:09 | 145987.23 | 660080.29 | 0.00 | 154849.24 | 252133.63 | 46723.85 | 0.00 | 324689.88 | 79373.33 |
August | 1895837.77 | 22-AUG-14:30 | 145987.23 | 778371.69 | 0.00 | 154722.86 | 258556.77 | 48135.00 | 0.00 | 407412.53 | 79373.33 |
September | 1296522.99 | 05-SEP-10:09 | 145987.23 | 423497.50 | 0.00 | 154722.86 | 160867.70 | 46247.09 | 0.00 | 247992.95 | 79373.33 |
October | 1383428.83 | 04-OCT-15:00 | 145987.23 | 541788.89 | 0.00 | 154849.24 | 161380.15 | 45259.77 | 0.00 | 217816.26 | 79373.33 |
November | 1348488.01 | 03-NOV-14:09 | 145987.23 | 660080.29 | 0.00 | 154722.86 | 116154.97 | 23609.27 | 0.00 | 77447.34 | 44100.78 |
December | 1401625.26 | 18-DEC-16:40 | 169722.15 | 778371.69 | 31088.59 | 154861.70 | 77689.84 | 23432.35 | 0.00 | 21040.22 | 1595.46 |
Annual Sum or Average | |||||||||||
Minimum of Months | 997648.46 | 145987.23 | 423497.50 | 0.00 | 154722.86 | 67007.83 | 23427.94 | 0.00 | 7207.28 | 681.11 | |
Maximum of Months | 1895837.77 | 169722.15 | 778371.69 | 31088.59 | 154861.70 | 258556.77 | 48897.67 | 0.00 | 407412.53 | 79373.33 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1501293.39 | 02-JAN-05:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1034359.51 | 06-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 441493.08 | 13-MAR-04:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 395773.38 | 03-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 148492.94 | 30-MAY-11:20 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 180680.29 | 01-JUN-14:00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 74363.72 | 11-JUL-16:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 162018.16 | 24-AUG-18:40 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 95690.74 | 01-SEP-16:40 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 64391.46 | 28-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 586315.16 | 24-NOV-05:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 694132.98 | 11-DEC-05:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 64391.46 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1501293.39 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 42.50 | 25.80 | 25.17 | 25.79 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 25.88 | 23.17 | 25.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 53.67 | 26.08 | 27.67 | 26.08 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 26.23 | 27.00 | 26.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 | 26.49 | 34.67 | 26.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 335.17 | 27.80 | 237.83 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 686.83 | 28.59 | 458.33 | 28.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 557.67 | 28.92 | 369.50 | 28.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 316.67 | 27.78 | 197.17 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 108.33 | 27.11 | 44.50 | 27.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 85.33 | 26.94 | 38.00 | 26.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 | 26.38 | 26.17 | 26.34 |
Annual Sum or Average | 0.00 | 0.00 | 2403.33 | 28.01 | 1509.17 | 28.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 42.50 | 25.80 | 23.17 | 25.79 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 686.83 | 28.92 | 458.33 | 28.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.63 | 0.00 | 25.63 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.74 | 0.00 | 25.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 25.69 | 0.33 | 25.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 25.86 | 0.17 | 25.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 26.30 | 0.17 | 26.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.83 | 25.81 | 0.67 | 25.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.30 | 0.33 | 26.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 19.45 | 1.50 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 19.45 | 1.50 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.45 | 1.50 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 18.89 | 1.50 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
February | 2.00 | 18.78 | 0.33 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
March | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
December | 0.67 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Annual Sum or Average | 8.00 | 18.94 | 1.83 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 19.40 | 1.50 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.85 | 1.33 | 27.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 26.95 | 8.67 | 27.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.79 | 4.00 | 27.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.47 | 0.33 | 26.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 25.17 | 26.88 | 14.50 | 27.09 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.26 | 8.67 | 27.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.57 | 0.17 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.97 | 2.33 | 27.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.87 | 8.17 | 27.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.62 | 5.67 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.54 | 13.33 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.43 | 6.67 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.93 | 8.00 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.59 | 1.83 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 54.00 | 27.66 | 46.17 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.97 | 13.33 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.09 | 0.00 | 19.09 | 0.33 | 24.69 | 0.33 | 25.81 |
February | 0.17 | 19.20 | 0.00 | 19.20 | 1.83 | 26.94 | 1.83 | 27.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.57 | 0.33 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.53 | 3.17 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.65 | 5.00 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.47 | 4.33 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.35 | 11.17 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.24 | 7.33 | 27.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.97 | 12.67 | 26.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.80 | 12.83 | 26.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.54 | 0.83 | 27.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.06 | 2.83 | 28.06 |
Annual Sum or Average | 0.33 | 19.15 | 0.00 | 19.15 | 73.00 | 27.20 | 62.67 | 27.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.69 | 0.33 | 25.81 |
Maximum of Months | 0.17 | 19.20 | 0.00 | 19.20 | 15.50 | 28.06 | 12.83 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.63 | 0.67 | 27.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.92 | 1.83 | 27.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.84 | 6.33 | 27.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.94 | 6.00 | 28.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.46 | 9.17 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 27.57 | 16.67 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 51.50 | 27.45 | 16.17 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.77 | 5.33 | 27.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.78 | 5.00 | 27.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.63 | 1.67 | 27.63 |
Annual Sum or Average | 0.00 | 0.00 | 152.83 | 27.58 | 69.00 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 51.50 | 27.94 | 16.67 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.67 | 17.10 | 5.83 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
February | 10.33 | 18.30 | 2.17 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
March | 0.50 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.36 | 1.17 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.67 | 27.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
December | 2.17 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Annual Sum or Average | 30.67 | 17.74 | 8.00 | 17.83 | 2.00 | 18.30 | 1.83 | 18.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.67 | 19.37 | 5.83 | 19.37 | 1.33 | 27.36 | 1.17 | 27.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.67 | 17.75 | 1.00 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
February | 8.33 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
March | 0.33 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.78 | 2.00 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.05 | 8.50 | 28.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.82 | 6.00 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.90 | 12.50 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.94 | 6.83 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.00 | 7.67 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.56 | 1.00 | 27.56 |
November | 0.83 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
December | 4.00 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 |
Annual Sum or Average | 31.17 | 18.23 | 1.00 | 18.15 | 45.17 | 23.86 | 44.50 | 25.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 | 0.00 | 17.64 |
Maximum of Months | 17.67 | 19.48 | 1.00 | 19.48 | 13.00 | 28.05 | 12.50 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.33 | 16.94 | 0.67 | 16.98 | 0.67 | 17.63 | 0.67 | 18.21 |
February | 3.17 | 18.52 | 0.00 | 18.52 | 1.67 | 21.69 | 1.67 | 23.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.41 | 0.17 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.45 | 2.33 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.68 | 4.67 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.55 | 3.50 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.70 | 8.17 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.14 | 7.83 | 27.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 26.35 | 17.83 | 26.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 26.17 | 21.17 | 26.17 |
November | 0.33 | 19.33 | 0.00 | 19.33 | 2.50 | 24.46 | 2.50 | 24.79 |
December | 1.00 | 19.37 | 0.00 | 19.37 | 2.50 | 25.60 | 2.50 | 26.64 |
Annual Sum or Average | 13.83 | 17.53 | 0.67 | 17.53 | 74.17 | 25.27 | 73.00 | 25.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 17.63 | 0.17 | 18.21 |
Maximum of Months | 9.33 | 19.37 | 0.67 | 19.37 | 21.17 | 27.70 | 21.17 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 16.59 | 1.33 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
February | 3.50 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.33 | 27.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.02 | 2.00 | 28.06 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.96 | 4.67 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.00 | 4.17 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.81 | 7.83 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.68 | 4.67 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.41 | 3.33 | 28.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.75 | 2.00 | 27.75 |
November | 0.50 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
December | 0.50 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Annual Sum or Average | 14.00 | 17.24 | 1.33 | 17.10 | 46.83 | 25.24 | 29.00 | 26.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.47 | 0.00 | 16.47 |
Maximum of Months | 9.50 | 19.40 | 1.33 | 19.40 | 14.67 | 28.41 | 7.83 | 28.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.67 | 16.88 | 12.50 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
February | 34.33 | 17.18 | 11.83 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
March | 5.33 | 18.83 | 0.50 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
April | 1.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.37 | 0.67 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.31 | 0.83 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.42 | 5.67 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.58 | 1.67 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.00 | 17.90 | 1.33 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
December | 15.00 | 17.74 | 2.67 | 17.72 | 0.00 | 17.72 | 0.00 | 17.72 |
Annual Sum or Average | 106.33 | 17.30 | 28.83 | 17.43 | 10.33 | 18.14 | 8.83 | 18.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.67 | 19.20 | 12.50 | 19.20 | 7.00 | 27.58 | 5.67 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.00 | 15.82 | 4.17 | 15.71 | 0.00 | 15.71 | 0.00 | 15.71 |
February | 17.00 | 16.24 | 1.00 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
March | 4.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
April | 0.67 | 19.21 | 0.00 | 19.21 | 0.83 | 23.76 | 0.83 | 25.06 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.98 | 8.83 | 27.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.80 | 7.17 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.97 | 12.83 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.00 | 7.17 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.99 | 7.67 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.43 | 0.50 | 27.43 |
November | 4.83 | 17.74 | 0.00 | 17.74 | 0.00 | 17.74 | 0.00 | 17.74 |
December | 10.83 | 17.27 | 0.67 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
Annual Sum or Average | 63.33 | 16.53 | 5.83 | 16.40 | 48.67 | 21.17 | 45.00 | 23.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.71 | 0.00 | 15.71 |
Maximum of Months | 26.00 | 19.21 | 4.17 | 19.21 | 15.00 | 28.00 | 12.83 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.83 | 16.35 | 2.33 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 |
February | 13.00 | 17.09 | 0.83 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
March | 3.50 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
April | 0.67 | 19.30 | 0.00 | 19.30 | 1.33 | 24.70 | 1.33 | 25.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.73 | 4.83 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.66 | 4.33 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.81 | 9.67 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.13 | 5.67 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.12 | 10.50 | 27.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.72 | 10.33 | 26.72 |
November | 3.50 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
December | 7.83 | 17.99 | 0.33 | 17.87 | 1.50 | 19.38 | 1.50 | 20.49 |
Annual Sum or Average | 50.33 | 17.15 | 3.50 | 17.09 | 52.50 | 22.20 | 48.17 | 23.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 | 0.00 | 16.34 |
Maximum of Months | 21.83 | 19.30 | 2.33 | 19.30 | 11.67 | 28.13 | 10.50 | 28.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.50 | 16.19 | 3.00 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
February | 11.33 | 16.76 | 0.67 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
March | 3.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.98 | 1.83 | 28.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.05 | 4.83 | 28.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.23 | 4.17 | 28.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.90 | 9.83 | 28.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.58 | 5.50 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.43 | 3.50 | 28.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.93 | 0.83 | 27.97 |
November | 3.17 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
December | 7.00 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
Annual Sum or Average | 42.00 | 17.07 | 3.67 | 16.90 | 50.67 | 22.72 | 30.50 | 24.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 | 0.00 | 16.02 |
Maximum of Months | 17.50 | 19.06 | 3.00 | 19.06 | 17.17 | 28.43 | 9.83 | 28.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.61 | 1.33 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 27.61 | 1.33 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.61 | 1.33 | 27.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.18 | 6.50 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.50 | 28.18 | 6.50 | 28.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.18 | 6.50 | 28.18 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 234.00 | 24.01 | 62.33 | 24.36 | 0.00 | 24.36 |
February | 255.50 | 24.01 | 57.17 | 24.40 | 0.00 | 24.40 |
March | 120.00 | 24.00 | 117.67 | 24.81 | 0.00 | 24.81 |
April | 40.17 | 24.01 | 172.00 | 25.25 | 0.00 | 25.25 |
May | 14.50 | 24.04 | 293.33 | 24.96 | 8.50 | 24.93 |
June | 222.17 | 27.77 | 455.67 | 26.75 | 222.17 | 27.00 |
July | 424.33 | 28.84 | 497.00 | 28.54 | 424.33 | 28.63 |
August | 346.33 | 29.16 | 510.00 | 28.31 | 346.33 | 28.56 |
September | 167.17 | 28.00 | 415.00 | 26.68 | 166.33 | 26.97 |
October | 49.83 | 25.01 | 350.50 | 25.07 | 20.17 | 25.14 |
November | 58.83 | 24.69 | 169.33 | 25.58 | 11.00 | 25.67 |
December | 155.17 | 24.00 | 110.33 | 24.98 | 0.00 | 24.98 |
Annual Sum or Average | 2088.00 | 26.61 | 3210.33 | 26.52 | 1198.83 | 26.89 |
Minimum of Months | 14.50 | 24.00 | 57.17 | 24.36 | 0.00 | 24.36 |
Maximum of Months | 424.33 | 29.16 | 510.00 | 28.54 | 424.33 | 28.63 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 375.00 | 23.86 | 27.33 | 23.89 | 12.00 | 23.90 |
February | 312.50 | 23.92 | 6.50 | 23.96 | 0.00 | 23.96 |
March | 129.50 | 23.99 | 78.67 | 24.45 | 0.00 | 24.45 |
April | 38.33 | 23.99 | 146.67 | 24.66 | 0.00 | 24.66 |
May | 10.33 | 23.98 | 247.00 | 24.45 | 0.00 | 24.45 |
June | 0.00 | 0.00 | 438.33 | 24.31 | 0.00 | 24.31 |
July | 0.00 | 0.00 | 497.00 | 24.39 | 0.00 | 24.39 |
August | 0.33 | 26.65 | 494.83 | 24.31 | 0.33 | 24.31 |
September | 1.83 | 24.58 | 394.67 | 24.46 | 0.33 | 24.46 |
October | 47.17 | 24.00 | 313.50 | 24.43 | 0.00 | 24.43 |
November | 82.33 | 23.99 | 116.17 | 24.80 | 0.00 | 24.80 |
December | 180.83 | 23.99 | 57.83 | 24.41 | 0.00 | 24.41 |
Annual Sum or Average | 1178.17 | 23.93 | 2818.50 | 24.34 | 12.67 | 24.34 |
Minimum of Months | 0.00 | 0.00 | 6.50 | 23.89 | 0.00 | 23.90 |
Maximum of Months | 375.00 | 26.65 | 497.00 | 24.80 | 12.00 | 24.80 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.15 | 52.33 | 21.94 | 52.33 | 21.76 |
February | 454.00 | 22.76 | 6.17 | 22.73 | 6.17 | 22.71 |
March | 454.67 | 23.49 | 5.17 | 23.50 | 0.00 | 23.50 |
April | 268.67 | 23.52 | 35.33 | 23.65 | 0.00 | 23.65 |
May | 87.17 | 23.80 | 189.67 | 24.13 | 0.00 | 24.13 |
June | 2.50 | 23.71 | 417.67 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 494.67 | 24.21 | 0.00 | 24.21 |
August | 0.00 | 0.00 | 457.67 | 24.23 | 0.00 | 24.23 |
September | 26.83 | 23.70 | 332.83 | 24.23 | 0.00 | 24.23 |
October | 129.17 | 23.78 | 230.50 | 24.07 | 0.00 | 24.07 |
November | 345.83 | 23.31 | 40.00 | 23.45 | 0.00 | 23.45 |
December | 497.00 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
Annual Sum or Average | 2767.83 | 23.04 | 2262.00 | 23.53 | 58.50 | 23.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.94 | 0.00 | 21.76 |
Maximum of Months | 502.00 | 23.80 | 494.67 | 24.23 | 52.33 | 24.23 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.95 | 205.50 | 20.62 | 205.50 | 20.45 |
February | 454.00 | 21.26 | 190.17 | 21.00 | 190.17 | 20.86 |
March | 498.00 | 22.36 | 32.50 | 22.27 | 31.00 | 22.18 |
April | 364.00 | 22.77 | 34.83 | 22.80 | 9.50 | 22.75 |
May | 160.67 | 23.51 | 151.67 | 23.85 | 0.00 | 23.85 |
June | 10.17 | 23.67 | 414.00 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 496.00 | 24.28 | 0.00 | 24.28 |
August | 0.00 | 0.00 | 455.17 | 24.27 | 0.00 | 24.27 |
September | 68.67 | 23.36 | 316.83 | 24.08 | 0.00 | 24.08 |
October | 262.83 | 23.04 | 157.17 | 23.41 | 3.67 | 23.39 |
November | 470.33 | 22.17 | 73.83 | 21.95 | 71.67 | 21.77 |
December | 497.00 | 21.27 | 153.67 | 20.99 | 153.67 | 20.82 |
Annual Sum or Average | 3287.67 | 21.98 | 2681.33 | 22.54 | 665.17 | 22.30 |
Minimum of Months | 0.00 | 0.00 | 32.50 | 20.62 | 0.00 | 20.45 |
Maximum of Months | 502.00 | 23.67 | 496.00 | 24.28 | 205.50 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.73 | 123.67 | 21.53 | 123.67 | 21.40 |
February | 454.00 | 21.95 | 88.50 | 21.77 | 88.50 | 21.65 |
March | 458.83 | 23.06 | 10.50 | 23.07 | 1.50 | 23.07 |
April | 266.33 | 23.45 | 73.17 | 23.66 | 0.00 | 23.66 |
May | 68.17 | 23.78 | 217.00 | 24.25 | 1.17 | 24.26 |
June | 11.50 | 26.36 | 453.50 | 24.42 | 10.17 | 24.47 |
July | 49.17 | 26.79 | 497.00 | 24.74 | 49.17 | 24.91 |
August | 21.50 | 26.81 | 491.17 | 24.48 | 21.50 | 24.58 |
September | 36.67 | 24.25 | 356.33 | 24.40 | 6.17 | 24.43 |
October | 186.17 | 23.56 | 233.83 | 23.91 | 0.00 | 23.91 |
November | 393.33 | 23.05 | 16.00 | 23.08 | 2.83 | 23.06 |
December | 495.50 | 22.59 | 2.17 | 22.58 | 2.17 | 22.58 |
Annual Sum or Average | 2943.17 | 22.78 | 2562.83 | 23.39 | 306.83 | 23.34 |
Minimum of Months | 11.50 | 21.73 | 2.17 | 21.53 | 0.00 | 21.40 |
Maximum of Months | 502.00 | 26.81 | 497.00 | 24.74 | 123.67 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.83 | 21.93 | 106.83 | 21.71 | 106.83 | 21.56 |
February | 437.17 | 22.30 | 62.67 | 22.17 | 58.33 | 22.03 |
March | 391.67 | 22.91 | 34.67 | 23.02 | 2.33 | 23.02 |
April | 243.50 | 23.32 | 127.33 | 23.77 | 8.83 | 23.85 |
May | 83.33 | 24.71 | 302.50 | 24.55 | 25.67 | 24.71 |
June | 26.50 | 26.74 | 472.83 | 24.51 | 25.00 | 24.63 |
July | 60.50 | 26.94 | 497.00 | 24.81 | 60.50 | 25.02 |
August | 34.67 | 26.92 | 494.33 | 24.56 | 34.67 | 24.71 |
September | 51.33 | 25.65 | 393.50 | 24.63 | 30.00 | 24.78 |
October | 142.83 | 23.64 | 270.33 | 24.11 | 6.83 | 24.16 |
November | 353.67 | 22.92 | 25.50 | 23.01 | 4.67 | 22.98 |
December | 479.50 | 22.46 | 11.17 | 22.46 | 8.33 | 22.43 |
Annual Sum or Average | 2798.50 | 22.92 | 2798.67 | 23.58 | 372.00 | 23.60 |
Minimum of Months | 26.50 | 21.93 | 11.17 | 21.71 | 2.33 | 21.56 |
Maximum of Months | 493.83 | 26.94 | 497.00 | 24.81 | 106.83 | 25.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.50 | 21.78 | 123.33 | 21.65 | 102.50 | 21.46 |
February | 349.50 | 22.21 | 91.17 | 22.27 | 60.33 | 22.12 |
March | 340.17 | 22.87 | 81.83 | 23.09 | 7.67 | 23.06 |
April | 234.83 | 23.28 | 127.83 | 23.74 | 9.17 | 23.82 |
May | 102.83 | 24.00 | 267.50 | 24.31 | 13.50 | 24.41 |
June | 19.83 | 26.36 | 464.33 | 24.45 | 16.50 | 24.53 |
July | 49.33 | 26.92 | 497.00 | 24.75 | 49.33 | 24.93 |
August | 32.83 | 26.97 | 498.50 | 24.58 | 32.83 | 24.72 |
September | 47.67 | 25.71 | 409.33 | 24.65 | 28.00 | 24.79 |
October | 119.50 | 24.30 | 335.17 | 24.47 | 26.17 | 24.61 |
November | 287.17 | 22.88 | 104.67 | 23.25 | 7.83 | 23.21 |
December | 385.67 | 22.46 | 58.00 | 22.66 | 21.67 | 22.67 |
Annual Sum or Average | 2396.83 | 22.90 | 3058.67 | 23.66 | 375.50 | 23.67 |
Minimum of Months | 19.83 | 21.78 | 58.00 | 21.65 | 7.67 | 21.46 |
Maximum of Months | 427.50 | 26.97 | 498.50 | 24.75 | 102.50 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 452.83 | 22.57 | 40.17 | 22.50 | 34.17 | 22.40 |
February | 375.00 | 23.18 | 21.83 | 23.26 | 5.50 | 23.24 |
March | 150.67 | 23.99 | 145.83 | 24.38 | 5.33 | 24.43 |
April | 39.33 | 25.84 | 278.00 | 24.99 | 23.33 | 25.14 |
May | 32.17 | 26.38 | 383.83 | 24.72 | 25.67 | 24.85 |
June | 50.67 | 26.97 | 481.50 | 24.79 | 50.67 | 24.98 |
July | 105.83 | 26.87 | 497.00 | 25.08 | 105.83 | 25.35 |
August | 95.83 | 26.54 | 514.00 | 24.87 | 95.83 | 25.10 |
September | 27.83 | 27.06 | 426.33 | 24.72 | 27.83 | 24.85 |
October | 62.50 | 24.95 | 340.50 | 24.68 | 19.83 | 24.79 |
November | 150.00 | 23.86 | 129.00 | 24.39 | 0.67 | 24.40 |
December | 273.50 | 23.97 | 42.50 | 24.24 | 1.33 | 24.26 |
Annual Sum or Average | 1816.17 | 24.01 | 3300.50 | 24.41 | 396.00 | 24.54 |
Minimum of Months | 27.83 | 22.57 | 21.83 | 22.50 | 0.67 | 22.40 |
Maximum of Months | 452.83 | 27.06 | 514.00 | 25.08 | 105.83 | 25.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.28 | 374.17 | 20.16 | 374.17 | 20.11 |
February | 454.00 | 20.50 | 358.67 | 20.41 | 358.67 | 20.38 |
March | 509.50 | 21.50 | 127.67 | 21.33 | 124.67 | 21.21 |
April | 401.67 | 22.35 | 37.50 | 22.37 | 14.83 | 22.31 |
May | 183.67 | 23.36 | 145.67 | 23.78 | 0.00 | 23.78 |
June | 27.00 | 25.16 | 433.17 | 24.34 | 18.50 | 24.39 |
July | 51.00 | 26.14 | 497.00 | 24.61 | 51.00 | 24.74 |
August | 24.83 | 25.90 | 468.17 | 24.42 | 22.50 | 24.49 |
September | 111.33 | 23.40 | 291.00 | 24.01 | 6.50 | 24.03 |
October | 314.00 | 22.66 | 124.17 | 22.96 | 10.00 | 22.92 |
November | 483.50 | 21.51 | 131.00 | 21.25 | 131.00 | 21.07 |
December | 497.00 | 20.58 | 352.83 | 20.48 | 352.83 | 20.44 |
Annual Sum or Average | 3559.50 | 21.55 | 3341.00 | 22.09 | 1464.67 | 21.83 |
Minimum of Months | 24.83 | 20.28 | 37.50 | 20.16 | 0.00 | 20.11 |
Maximum of Months | 509.50 | 26.14 | 497.00 | 24.61 | 374.17 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.38 | 287.83 | 20.15 | 287.83 | 20.05 |
February | 384.67 | 21.01 | 225.00 | 20.74 | 225.00 | 20.62 |
March | 381.50 | 21.89 | 70.33 | 21.74 | 62.00 | 21.59 |
April | 269.83 | 22.62 | 81.00 | 23.09 | 10.00 | 23.14 |
May | 131.17 | 24.12 | 206.33 | 24.45 | 27.33 | 24.65 |
June | 37.33 | 26.51 | 392.00 | 24.63 | 35.00 | 24.79 |
July | 74.67 | 26.69 | 422.00 | 24.96 | 74.67 | 25.19 |
August | 42.17 | 26.73 | 410.50 | 24.72 | 41.67 | 24.89 |
September | 87.33 | 24.69 | 295.67 | 24.59 | 34.00 | 24.76 |
October | 193.67 | 23.04 | 163.00 | 23.63 | 7.67 | 23.66 |
November | 374.00 | 21.77 | 93.00 | 21.52 | 88.67 | 21.32 |
December | 422.00 | 20.94 | 236.00 | 20.70 | 236.00 | 20.59 |
Annual Sum or Average | 2825.33 | 21.98 | 2882.67 | 22.58 | 1129.83 | 22.40 |
Minimum of Months | 37.33 | 20.38 | 70.33 | 20.15 | 7.67 | 20.05 |
Maximum of Months | 427.00 | 26.73 | 422.00 | 24.96 | 287.83 | 25.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 440.67 | 20.93 | 228.17 | 20.69 | 212.00 | 20.49 |
February | 365.33 | 21.58 | 178.50 | 21.47 | 151.00 | 21.27 |
March | 375.33 | 22.09 | 109.00 | 22.27 | 42.00 | 22.14 |
April | 302.50 | 22.57 | 110.17 | 23.03 | 13.50 | 23.03 |
May | 165.83 | 23.58 | 221.83 | 24.06 | 13.50 | 24.16 |
June | 38.33 | 25.41 | 444.33 | 24.41 | 25.17 | 24.51 |
July | 66.83 | 26.43 | 497.00 | 24.73 | 66.83 | 24.91 |
August | 40.17 | 26.67 | 485.50 | 24.61 | 40.17 | 24.75 |
September | 81.17 | 24.87 | 382.17 | 24.56 | 36.00 | 24.72 |
October | 167.50 | 23.89 | 310.33 | 24.31 | 33.67 | 24.47 |
November | 338.33 | 22.13 | 130.00 | 22.33 | 50.83 | 22.13 |
December | 415.67 | 21.61 | 185.50 | 21.50 | 160.50 | 21.33 |
Annual Sum or Average | 2797.67 | 22.32 | 3282.50 | 23.05 | 845.17 | 22.92 |
Minimum of Months | 38.33 | 20.93 | 109.00 | 20.69 | 13.50 | 20.49 |
Maximum of Months | 440.67 | 26.67 | 497.00 | 24.73 | 212.00 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.83 | 20.73 | 281.67 | 20.48 | 281.67 | 20.36 |
February | 438.17 | 21.11 | 235.00 | 20.87 | 234.00 | 20.75 |
March | 422.83 | 22.13 | 76.67 | 22.19 | 41.33 | 22.10 |
April | 295.00 | 22.77 | 103.67 | 23.17 | 13.83 | 23.21 |
May | 113.17 | 24.07 | 268.00 | 24.34 | 20.83 | 24.48 |
June | 39.17 | 26.41 | 465.83 | 24.59 | 35.33 | 24.73 |
July | 73.00 | 26.71 | 497.00 | 24.87 | 73.00 | 25.08 |
August | 45.17 | 26.78 | 499.33 | 24.68 | 45.17 | 24.84 |
September | 71.50 | 24.42 | 365.67 | 24.41 | 21.50 | 24.52 |
October | 193.17 | 23.15 | 245.50 | 23.79 | 5.00 | 23.83 |
November | 440.17 | 21.90 | 96.00 | 21.72 | 83.33 | 21.55 |
December | 494.00 | 21.20 | 219.83 | 20.97 | 219.83 | 20.86 |
Annual Sum or Average | 3123.17 | 22.06 | 3354.17 | 22.75 | 1074.83 | 22.58 |
Minimum of Months | 39.17 | 20.73 | 76.67 | 20.48 | 5.00 | 20.36 |
Maximum of Months | 497.83 | 26.78 | 499.33 | 24.87 | 281.67 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.97 | 435.67 | 19.90 | 435.67 | 19.87 |
February | 454.00 | 20.10 | 415.00 | 20.05 | 415.00 | 20.03 |
March | 511.50 | 20.98 | 248.17 | 20.74 | 248.17 | 20.62 |
April | 409.33 | 21.74 | 109.00 | 21.62 | 83.33 | 21.42 |
May | 236.83 | 23.04 | 134.67 | 23.52 | 4.67 | 23.56 |
June | 44.17 | 24.86 | 422.00 | 24.34 | 26.33 | 24.42 |
July | 70.17 | 26.22 | 497.00 | 24.69 | 70.17 | 24.86 |
August | 41.33 | 25.61 | 460.33 | 24.46 | 31.50 | 24.57 |
September | 147.83 | 23.05 | 264.83 | 23.82 | 9.33 | 23.84 |
October | 361.00 | 22.04 | 148.50 | 22.15 | 60.83 | 21.94 |
November | 489.00 | 20.81 | 250.50 | 20.54 | 250.50 | 20.41 |
December | 497.00 | 20.07 | 464.50 | 20.04 | 464.50 | 20.03 |
Annual Sum or Average | 3764.17 | 21.19 | 3850.17 | 21.67 | 2100.00 | 21.40 |
Minimum of Months | 41.33 | 19.97 | 109.00 | 19.90 | 4.67 | 19.87 |
Maximum of Months | 511.50 | 26.22 | 497.00 | 24.69 | 464.50 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.12 | 387.00 | 19.95 | 387.00 | 19.88 |
February | 454.00 | 20.49 | 338.33 | 20.30 | 338.33 | 20.22 |
March | 472.50 | 21.51 | 155.50 | 21.16 | 153.67 | 20.94 |
April | 322.00 | 22.06 | 141.00 | 22.37 | 52.67 | 22.20 |
May | 179.50 | 23.62 | 245.50 | 24.16 | 28.83 | 24.34 |
June | 46.17 | 26.13 | 462.50 | 24.52 | 39.83 | 24.67 |
July | 79.33 | 26.65 | 497.00 | 24.85 | 79.33 | 25.07 |
August | 47.00 | 26.64 | 488.83 | 24.62 | 45.17 | 24.79 |
September | 123.17 | 24.10 | 341.00 | 24.35 | 36.50 | 24.50 |
October | 259.17 | 22.52 | 191.83 | 23.05 | 25.33 | 22.94 |
November | 468.33 | 21.22 | 181.83 | 20.86 | 180.00 | 20.65 |
December | 497.00 | 20.32 | 377.00 | 20.16 | 377.00 | 20.09 |
Annual Sum or Average | 3450.17 | 21.54 | 3807.33 | 22.13 | 1743.67 | 21.88 |
Minimum of Months | 46.17 | 20.12 | 141.00 | 19.95 | 25.33 | 19.88 |
Maximum of Months | 502.00 | 26.65 | 497.00 | 24.85 | 387.00 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 456.17 | 20.53 | 288.83 | 20.23 | 280.33 | 20.06 |
February | 390.50 | 21.05 | 247.83 | 20.82 | 231.17 | 20.63 |
March | 395.67 | 21.47 | 185.33 | 21.43 | 133.00 | 21.20 |
April | 329.17 | 21.99 | 144.33 | 22.28 | 58.67 | 22.11 |
May | 209.67 | 23.18 | 207.17 | 23.81 | 16.83 | 23.93 |
June | 52.50 | 25.01 | 432.50 | 24.39 | 30.33 | 24.50 |
July | 73.67 | 26.38 | 496.83 | 24.75 | 73.67 | 24.93 |
August | 49.00 | 26.30 | 480.83 | 24.60 | 43.17 | 24.76 |
September | 103.50 | 24.18 | 359.67 | 24.39 | 35.33 | 24.54 |
October | 197.17 | 22.97 | 291.67 | 23.72 | 38.50 | 23.73 |
November | 380.17 | 21.49 | 177.83 | 21.40 | 127.00 | 21.14 |
December | 435.50 | 20.90 | 281.17 | 20.66 | 267.33 | 20.49 |
Annual Sum or Average | 3072.67 | 21.81 | 3594.00 | 22.49 | 1335.33 | 22.25 |
Minimum of Months | 49.00 | 20.53 | 144.33 | 20.23 | 16.83 | 20.06 |
Maximum of Months | 456.17 | 26.38 | 496.83 | 24.75 | 280.33 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.50 | 20.35 | 342.50 | 20.12 | 342.50 | 20.02 |
February | 443.50 | 20.68 | 308.50 | 20.44 | 308.50 | 20.34 |
March | 434.33 | 21.53 | 167.83 | 21.40 | 139.17 | 21.22 |
April | 328.33 | 22.22 | 130.50 | 22.48 | 48.67 | 22.38 |
May | 163.17 | 23.60 | 246.50 | 24.11 | 23.17 | 24.27 |
June | 46.67 | 26.02 | 460.83 | 24.56 | 37.50 | 24.71 |
July | 80.67 | 26.65 | 497.00 | 24.89 | 80.67 | 25.11 |
August | 49.50 | 26.72 | 494.67 | 24.69 | 49.50 | 24.86 |
September | 102.33 | 23.88 | 342.83 | 24.27 | 24.67 | 24.39 |
October | 240.00 | 22.51 | 232.17 | 23.13 | 33.83 | 23.01 |
November | 458.50 | 21.26 | 169.67 | 20.96 | 167.00 | 20.77 |
December | 496.83 | 20.64 | 345.83 | 20.44 | 345.83 | 20.35 |
Annual Sum or Average | 3343.33 | 21.64 | 3738.83 | 22.28 | 1601.00 | 22.05 |
Minimum of Months | 46.67 | 20.35 | 130.50 | 20.12 | 23.17 | 20.02 |
Maximum of Months | 499.50 | 26.72 | 497.00 | 24.89 | 345.83 | 25.11 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 495.83 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 6.83 | 27.00 | 514.00 | 27.00 | 6.83 | 27.00 |
April | 62.67 | 27.00 | 485.00 | 27.00 | 62.67 | 27.00 |
May | 2.67 | 27.00 | 508.00 | 27.00 | 2.67 | 27.00 |
June | 79.83 | 27.00 | 496.00 | 27.00 | 79.83 | 27.00 |
July | 301.00 | 27.00 | 497.00 | 27.00 | 301.00 | 27.00 |
August | 441.00 | 27.03 | 514.00 | 27.02 | 441.00 | 27.03 |
September | 31.33 | 27.00 | 485.00 | 27.00 | 31.33 | 27.00 |
October | 31.67 | 27.00 | 502.00 | 27.00 | 31.67 | 27.00 |
November | 6.83 | 27.00 | 489.00 | 27.00 | 6.83 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 963.83 | 27.01 | 5936.83 | 27.00 | 963.83 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 441.00 | 27.03 | 514.00 | 27.02 | 441.00 | 27.03 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 76.50 | 25.32 | 302.17 | 26.58 | 6.33 | 26.52 |
February | 0.00 | 0.00 | 302.00 | 27.00 | 0.00 | 27.00 |
March | 0.83 | 27.00 | 511.50 | 27.00 | 0.83 | 27.00 |
April | 3.17 | 27.00 | 485.00 | 27.00 | 3.17 | 27.00 |
May | 0.83 | 27.00 | 508.00 | 27.00 | 0.83 | 27.00 |
June | 5.33 | 27.00 | 496.00 | 27.00 | 5.33 | 27.00 |
July | 28.33 | 27.00 | 497.00 | 27.00 | 28.33 | 27.00 |
August | 82.17 | 27.06 | 514.00 | 27.02 | 82.17 | 27.02 |
September | 8.83 | 27.00 | 485.00 | 27.00 | 8.83 | 27.00 |
October | 7.17 | 27.00 | 502.00 | 27.00 | 7.17 | 27.00 |
November | 0.00 | 0.00 | 469.17 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 473.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 213.17 | 26.42 | 5545.67 | 26.97 | 143.00 | 26.97 |
Minimum of Months | 0.00 | 0.00 | 302.00 | 26.58 | 0.00 | 26.52 |
Maximum of Months | 82.17 | 27.06 | 514.00 | 27.02 | 82.17 | 27.02 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 189.00 | 24.75 | 194.17 | 25.56 | 26.00 | 25.35 |
February | 39.33 | 27.00 | 166.83 | 27.00 | 0.00 | 27.00 |
March | 0.67 | 27.00 | 442.50 | 27.00 | 0.67 | 27.00 |
April | 8.00 | 27.00 | 478.50 | 27.00 | 8.00 | 27.00 |
May | 2.33 | 27.00 | 508.00 | 27.00 | 2.33 | 27.00 |
June | 29.00 | 27.00 | 496.00 | 27.00 | 29.00 | 27.00 |
July | 87.33 | 27.00 | 497.00 | 27.00 | 87.33 | 27.00 |
August | 136.83 | 27.02 | 514.00 | 27.01 | 136.83 | 27.01 |
September | 16.67 | 27.00 | 485.00 | 27.00 | 16.67 | 27.00 |
October | 9.33 | 27.00 | 482.33 | 27.00 | 9.33 | 27.00 |
November | 5.00 | 27.00 | 399.50 | 27.00 | 0.00 | 27.00 |
December | 13.17 | 27.00 | 277.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 536.67 | 26.21 | 4941.00 | 26.90 | 316.17 | 26.89 |
Minimum of Months | 0.67 | 24.75 | 166.83 | 25.56 | 0.00 | 25.35 |
Maximum of Months | 189.00 | 27.02 | 514.00 | 27.01 | 136.83 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 140.83 | 27.00 | 502.00 | 27.00 | 140.83 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 502.67 | 27.00 | 508.00 | 27.00 | 502.67 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.02 | 514.00 | 27.02 | 514.00 | 27.02 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5576.50 | 27.00 | 5943.00 | 27.00 | 5576.50 | 27.00 |
Minimum of Months | 140.83 | 27.00 | 454.00 | 27.00 | 140.83 | 27.00 |
Maximum of Months | 514.00 | 27.02 | 514.00 | 27.02 | 514.00 | 27.02 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00004 | 20.71619 | 0.70672 | 15.67627 |
February | 454.00000 | 27.00000 | 17.42448 | 0.73634 | 16.51268 |
March | 514.00000 | 27.00003 | 24.54704 | 0.87079 | 21.10907 |
April | 485.00000 | 27.00003 | 29.66706 | 0.96320 | 24.68676 |
May | 508.00000 | 27.00037 | 34.17882 | 0.24783 | 6.35549 |
June | 496.00000 | 27.00139 | 37.87626 | 0.35985 | 7.76152 |
July | 497.00000 | 27.00110 | 38.98284 | 0.43705 | 9.04206 |
August | 514.00000 | 27.02289 | 38.17993 | 0.47995 | 9.90741 |
September | 485.00000 | 27.00056 | 37.48468 | 0.29800 | 6.96685 |
October | 502.00000 | 27.00067 | 31.52171 | 0.93369 | 23.54734 |
November | 489.00000 | 27.00006 | 27.01585 | 0.88622 | 21.70045 |
December | 497.00000 | 26.99999 | 20.16530 | 0.84340 | 20.06379 |
Annual Sum or Average | 5943.00000 | 27.00233 | 29.90093 | 0.64578 | 15.25104 |
Minimum of Months | 454.00000 | 26.99999 | 17.42448 | 0.24783 | 6.35549 |
Maximum of Months | 514.00000 | 27.02289 | 38.98284 | 0.96320 | 24.68676 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.70027 | 20.85523 | 0.50481 | 11.47301 |
February | 454.00000 | 27.00000 | 17.42293 | 0.58306 | 12.27098 |
March | 514.00000 | 27.00003 | 24.53244 | 0.73342 | 16.50326 |
April | 485.00000 | 27.00004 | 29.63276 | 0.83134 | 19.74374 |
May | 508.00000 | 27.00024 | 34.24620 | 0.17948 | 5.79324 |
June | 496.00000 | 27.00133 | 37.93465 | 0.27390 | 6.63525 |
July | 497.00000 | 27.00112 | 39.02212 | 0.32004 | 7.19369 |
August | 514.00000 | 27.01072 | 38.18527 | 0.34798 | 7.61518 |
September | 485.00000 | 27.00040 | 37.63981 | 0.22366 | 6.18712 |
October | 502.00000 | 27.00066 | 31.53005 | 0.85217 | 20.52849 |
November | 489.00000 | 27.00006 | 26.99527 | 0.73492 | 16.60367 |
December | 497.00000 | 27.00000 | 20.15356 | 0.64105 | 13.72916 |
Annual Sum or Average | 5943.00000 | 26.97593 | 29.93357 | 0.51783 | 12.00758 |
Minimum of Months | 454.00000 | 26.70027 | 17.42293 | 0.17948 | 5.79324 |
Maximum of Months | 514.00000 | 27.01072 | 39.02212 | 0.85217 | 20.52849 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.05968 | 21.27043 | 0.32654 | 9.86641 |
February | 454.00000 | 26.99995 | 17.42071 | 0.50985 | 10.66528 |
March | 514.00000 | 27.00004 | 24.54536 | 0.67111 | 14.77076 |
April | 485.00000 | 27.00004 | 29.64843 | 0.78851 | 18.43251 |
May | 508.00000 | 27.00025 | 34.30604 | 0.16418 | 5.82110 |
June | 496.00000 | 27.00137 | 37.93690 | 0.28355 | 6.81419 |
July | 497.00000 | 27.00116 | 39.02805 | 0.34040 | 7.53392 |
August | 514.00000 | 27.00570 | 38.20147 | 0.36130 | 7.86928 |
September | 485.00000 | 27.00040 | 37.66371 | 0.21279 | 6.20428 |
October | 502.00000 | 27.00066 | 31.57466 | 0.81389 | 19.34324 |
November | 489.00000 | 27.00006 | 27.01612 | 0.65959 | 14.48410 |
December | 497.00000 | 27.00000 | 20.15860 | 0.55579 | 11.64369 |
Annual Sum or Average | 5943.00000 | 26.92139 | 29.98592 | 0.47320 | 11.11258 |
Minimum of Months | 454.00000 | 26.05968 | 17.42071 | 0.16418 | 5.82110 |
Maximum of Months | 514.00000 | 27.00570 | 39.02805 | 0.81389 | 19.34324 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99996 | 30.41553 | 1.01414 | 26.73543 |
February | 454.00000 | 27.00011 | 29.16090 | 1.17272 | 33.93033 |
March | 514.00000 | 27.00048 | 27.83423 | 1.32586 | 41.62292 |
April | 485.00000 | 27.00252 | 29.01288 | 1.47770 | 49.70133 |
May | 508.00000 | 27.00000 | 36.43032 | 0.51027 | 10.55287 |
June | 496.00000 | 27.00219 | 40.22068 | 0.79708 | 18.48753 |
July | 497.00000 | 27.00173 | 38.77700 | 1.01558 | 26.79432 |
August | 514.00000 | 27.01993 | 37.68926 | 1.20993 | 35.75686 |
September | 485.00000 | 27.00086 | 40.67398 | 0.61984 | 13.23511 |
October | 502.00000 | 27.00048 | 38.10553 | 1.31629 | 41.20017 |
November | 489.00000 | 27.00010 | 29.37245 | 1.36701 | 43.77549 |
December | 497.00000 | 27.00013 | 23.71262 | 1.43785 | 47.54590 |
Annual Sum or Average | 5943.00000 | 27.00243 | 33.48315 | 1.10473 | 32.42292 |
Minimum of Months | 454.00000 | 26.99996 | 23.71262 | 0.51027 | 10.55287 |
Maximum of Months | 514.00000 | 27.01993 | 40.67398 | 1.47770 | 49.70133 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.47370 | 22.50061 | 0.32068 | 7.57358 |
February | 454.00000 | 24.51252 | 18.30305 | 0.30574 | 7.37385 |
March | 514.00000 | 24.47649 | 25.73956 | 0.36555 | 8.23076 |
April | 485.00000 | 24.58413 | 31.53464 | 0.43586 | 9.60352 |
May | 508.00000 | 24.58909 | 39.84526 | -0.3573 | 8.69772 |
June | 496.00000 | 26.06730 | 65.01846 | 0.31537 | 17.56124 |
July | 497.00000 | 28.27820 | 82.31351 | 1.17677 | 40.37722 |
August | 514.00000 | 27.70173 | 78.25695 | 0.98975 | 39.05727 |
September | 485.00000 | 25.83566 | 59.26080 | 0.21570 | 16.04432 |
October | 502.00000 | 24.77745 | 40.11874 | 0.56009 | 12.65553 |
November | 489.00000 | 24.70184 | 27.88853 | 0.44669 | 10.07018 |
December | 497.00000 | 24.64324 | 20.25000 | 0.36775 | 8.41819 |
Annual Sum or Average | 5943.00000 | 25.39589 | 42.79600 | 0.42984 | 15.57335 |
Minimum of Months | 454.00000 | 24.47370 | 18.30305 | -0.3573 | 7.37385 |
Maximum of Months | 514.00000 | 28.27820 | 82.31351 | 1.17677 | 40.37722 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.96830 | 27.58382 | 0.23285 | 6.42151 |
February | 454.00000 | 24.13984 | 21.17739 | 0.24131 | 6.38742 |
March | 514.00000 | 24.26872 | 27.37720 | 0.34078 | 7.69983 |
April | 485.00000 | 24.29241 | 32.90419 | 0.40401 | 8.73764 |
May | 508.00000 | 24.25966 | 41.86906 | -0.4178 | 9.12925 |
June | 496.00000 | 24.28089 | 51.89861 | -0.2921 | 7.27296 |
July | 497.00000 | 24.39253 | 54.21380 | -0.1962 | 6.43026 |
August | 514.00000 | 24.29744 | 50.56237 | -0.2445 | 6.81567 |
September | 485.00000 | 24.37287 | 48.00672 | -0.3054 | 7.73579 |
October | 502.00000 | 24.36073 | 40.52031 | 0.47736 | 10.26536 |
November | 489.00000 | 24.40146 | 29.80341 | 0.39126 | 8.67062 |
December | 497.00000 | 24.33092 | 22.76903 | 0.31780 | 7.35797 |
Annual Sum or Average | 5943.00000 | 24.28091 | 37.51490 | 0.07707 | 7.75114 |
Minimum of Months | 454.00000 | 23.96830 | 21.17739 | -0.4178 | 6.38742 |
Maximum of Months | 514.00000 | 24.40146 | 54.21380 | 0.47736 | 10.26536 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.15431 | 29.57141 | -0.2352 | 8.26311 |
February | 454.00000 | 22.75720 | 24.95917 | -0.1087 | 5.87251 |
March | 514.00000 | 23.55979 | 30.77520 | 0.14301 | 5.84318 |
April | 485.00000 | 23.80903 | 35.56655 | 0.25615 | 6.78674 |
May | 508.00000 | 24.08914 | 42.84128 | -0.5030 | 10.66221 |
June | 496.00000 | 24.17400 | 53.42882 | -0.3793 | 8.29543 |
July | 497.00000 | 24.20419 | 57.38895 | -0.3364 | 7.59804 |
August | 514.00000 | 24.20975 | 53.32013 | -0.3577 | 7.98582 |
September | 485.00000 | 24.18190 | 49.31195 | -0.4142 | 8.99301 |
October | 502.00000 | 24.07259 | 42.16117 | 0.38223 | 8.52686 |
November | 489.00000 | 23.59526 | 33.82617 | 0.17191 | 6.50086 |
December | 497.00000 | 22.98444 | 27.76464 | -0.0308 | 5.54625 |
Annual Sum or Average | 5943.00000 | 23.65560 | 40.19160 | -0.1186 | 7.58851 |
Minimum of Months | 454.00000 | 22.15431 | 24.95917 | -0.5030 | 5.54625 |
Maximum of Months | 514.00000 | 24.20975 | 57.38895 | 0.38223 | 10.66221 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.94600 | 31.89372 | -0.5407 | 14.10535 |
February | 454.00000 | 21.25848 | 26.75078 | -0.4902 | 11.72463 |
March | 514.00000 | 22.41006 | 33.47436 | -0.1431 | 6.80710 |
April | 485.00000 | 23.09522 | 37.57977 | 0.07837 | 6.77122 |
May | 508.00000 | 23.92015 | 43.57443 | -0.5624 | 12.35345 |
June | 496.00000 | 24.17823 | 53.32580 | -0.3653 | 8.12334 |
July | 497.00000 | 24.28381 | 56.98464 | -0.2912 | 7.13346 |
August | 514.00000 | 24.24051 | 53.08541 | -0.3321 | 7.69609 |
September | 485.00000 | 24.05596 | 49.86723 | -0.4567 | 10.05533 |
October | 502.00000 | 23.49589 | 43.73860 | 0.23450 | 7.70818 |
November | 489.00000 | 22.23928 | 37.28125 | -0.1687 | 7.77860 |
December | 497.00000 | 21.27166 | 30.81145 | -0.4589 | 11.04741 |
Annual Sum or Average | 5943.00000 | 22.96278 | 41.63998 | -0.2905 | 9.26018 |
Minimum of Months | 454.00000 | 20.94600 | 26.75078 | -0.5624 | 6.77122 |
Maximum of Months | 514.00000 | 24.28381 | 56.98464 | 0.23450 | 14.10535 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.72719 | 27.38416 | -0.3315 | 8.61499 |
February | 454.00000 | 21.94984 | 22.21025 | -0.3053 | 8.05262 |
March | 514.00000 | 23.16614 | 28.56470 | 0.04391 | 6.00341 |
April | 485.00000 | 23.77754 | 33.16736 | 0.25108 | 7.05371 |
May | 508.00000 | 24.16202 | 41.12638 | -0.4539 | 10.09753 |
June | 496.00000 | 24.34057 | 51.00424 | -0.2386 | 6.96356 |
July | 497.00000 | 24.53344 | 53.27220 | -0.1026 | 6.56114 |
August | 514.00000 | 24.36355 | 49.66397 | -0.1910 | 6.75134 |
September | 485.00000 | 24.28553 | 47.61843 | -0.3429 | 8.47580 |
October | 502.00000 | 23.93556 | 40.47275 | 0.34636 | 8.38233 |
November | 489.00000 | 23.26614 | 31.07466 | 0.08288 | 6.32981 |
December | 497.00000 | 22.59418 | 24.41188 | -0.1321 | 6.09575 |
Annual Sum or Average | 5943.00000 | 23.51936 | 37.61283 | -0.1138 | 7.44498 |
Minimum of Months | 454.00000 | 21.72719 | 22.21025 | -0.4539 | 6.00341 |
Maximum of Months | 514.00000 | 24.53344 | 53.27220 | 0.34636 | 10.09753 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.96266 | 27.14137 | -0.2721 | 8.18590 |
February | 454.00000 | 22.39906 | 21.74172 | -0.1929 | 7.52787 |
March | 514.00000 | 23.20074 | 28.08656 | 0.07865 | 6.53116 |
April | 485.00000 | 23.78386 | 32.87092 | 0.28768 | 8.35945 |
May | 508.00000 | 24.27235 | 40.66895 | -0.3465 | 9.60468 |
June | 496.00000 | 24.37426 | 50.73816 | -0.1756 | 6.97694 |
July | 497.00000 | 24.55589 | 52.99867 | -0.0371 | 6.99949 |
August | 514.00000 | 24.37970 | 49.31005 | -0.1058 | 6.67164 |
September | 485.00000 | 24.38853 | 47.00905 | -0.2437 | 8.30521 |
October | 502.00000 | 24.06858 | 39.83335 | 0.41404 | 9.81943 |
November | 489.00000 | 23.28201 | 30.86879 | 0.09971 | 6.67906 |
December | 497.00000 | 22.53278 | 24.44700 | -0.1397 | 6.62365 |
Annual Sum or Average | 5943.00000 | 23.60841 | 37.25845 | -0.0524 | 7.68996 |
Minimum of Months | 454.00000 | 21.96266 | 21.74172 | -0.3465 | 6.53116 |
Maximum of Months | 514.00000 | 24.55589 | 52.99867 | 0.41404 | 9.81943 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.14511 | 26.40643 | -0.2113 | 9.13553 |
February | 454.00000 | 22.74055 | 20.69874 | -0.0849 | 8.41375 |
March | 514.00000 | 23.29423 | 27.53081 | 0.12667 | 7.17973 |
April | 485.00000 | 23.76759 | 32.82270 | 0.28516 | 8.41278 |
May | 508.00000 | 24.16396 | 41.05296 | -0.4216 | 10.30495 |
June | 496.00000 | 24.34974 | 50.90418 | -0.2147 | 7.01043 |
July | 497.00000 | 24.53574 | 53.15071 | -0.0717 | 6.74425 |
August | 514.00000 | 24.41225 | 49.25130 | -0.0940 | 6.57287 |
September | 485.00000 | 24.42203 | 46.86154 | -0.1946 | 7.98418 |
October | 502.00000 | 24.28484 | 39.01125 | 0.52914 | 12.56956 |
November | 489.00000 | 23.46975 | 30.01452 | 0.17672 | 7.74666 |
December | 497.00000 | 22.87172 | 23.43646 | -0.0297 | 7.69216 |
Annual Sum or Average | 5943.00000 | 23.71128 | 36.88273 | -0.0173 | 8.31436 |
Minimum of Months | 454.00000 | 22.14511 | 20.69874 | -0.4216 | 6.57287 |
Maximum of Months | 514.00000 | 24.53574 | 53.15071 | 0.52914 | 12.56956 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.74030 | 25.62170 | -0.0800 | 6.88014 |
February | 454.00000 | 23.40326 | 19.91674 | 0.06104 | 6.46518 |
March | 514.00000 | 24.23692 | 25.60851 | 0.37260 | 8.62878 |
April | 485.00000 | 24.51419 | 30.86178 | 0.53660 | 12.22302 |
May | 508.00000 | 24.44632 | 40.01386 | -0.2430 | 7.90605 |
June | 496.00000 | 24.54278 | 50.05861 | -0.0284 | 6.89176 |
July | 497.00000 | 24.69829 | 52.42824 | 0.09354 | 7.63977 |
August | 514.00000 | 24.56392 | 48.70601 | 0.07106 | 6.99643 |
September | 485.00000 | 24.50436 | 46.62141 | -0.1609 | 7.39265 |
October | 502.00000 | 24.47861 | 38.64960 | 0.56650 | 12.84321 |
November | 489.00000 | 24.27023 | 28.30522 | 0.36464 | 8.54487 |
December | 497.00000 | 24.23138 | 21.12699 | 0.28796 | 7.24382 |
Annual Sum or Average | 5943.00000 | 24.22425 | 35.77952 | 0.15355 | 8.31086 |
Minimum of Months | 454.00000 | 22.74030 | 19.91674 | -0.2430 | 6.46518 |
Maximum of Months | 514.00000 | 24.69829 | 52.42824 | 0.56650 | 12.84321 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.28319 | 29.66709 | -0.7460 | 19.02256 |
February | 454.00000 | 20.50347 | 24.17476 | -0.7078 | 17.10739 |
March | 514.00000 | 21.52033 | 31.91955 | -0.3601 | 9.11668 |
April | 485.00000 | 22.63698 | 36.33933 | -0.0352 | 6.99619 |
May | 508.00000 | 23.85913 | 42.30168 | -0.5770 | 13.24048 |
June | 496.00000 | 24.24811 | 52.74106 | -0.3058 | 7.58581 |
July | 497.00000 | 24.45307 | 56.75168 | -0.1830 | 6.76651 |
August | 514.00000 | 24.30758 | 52.47027 | -0.2727 | 7.32639 |
September | 485.00000 | 23.98377 | 49.32307 | -0.4764 | 10.89588 |
October | 502.00000 | 23.13809 | 42.87098 | 0.14464 | 7.38212 |
November | 489.00000 | 21.53731 | 35.07392 | -0.3428 | 9.63800 |
December | 497.00000 | 20.58449 | 28.16749 | -0.6482 | 14.84238 |
Annual Sum or Average | 5943.00000 | 22.60400 | 40.26870 | -0.3739 | 10.78456 |
Minimum of Months | 454.00000 | 20.28319 | 24.17476 | -0.7460 | 6.76651 |
Maximum of Months | 514.00000 | 24.45307 | 56.75168 | 0.14464 | 19.02256 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.38259 | 28.80270 | -0.7072 | 18.52264 |
February | 385.00000 | 21.00882 | 23.00801 | -0.5666 | 13.95679 |
March | 433.00000 | 22.15229 | 30.12079 | -0.1921 | 8.22804 |
April | 410.00000 | 23.20046 | 34.34542 | 0.12957 | 8.28643 |
May | 430.00000 | 24.16301 | 41.01205 | -0.4027 | 11.62354 |
June | 418.00000 | 24.42409 | 51.79440 | -0.1922 | 7.47637 |
July | 422.00000 | 24.65422 | 55.80009 | -0.0528 | 7.53171 |
August | 433.00000 | 24.48324 | 51.61690 | -0.1234 | 7.07171 |
September | 410.00000 | 24.31569 | 48.02019 | -0.3049 | 9.62128 |
October | 427.00000 | 23.66355 | 40.63486 | 0.29528 | 8.87230 |
November | 417.00000 | 22.01517 | 33.61366 | -0.2190 | 8.83700 |
December | 422.00000 | 20.94256 | 27.21241 | -0.5521 | 13.07180 |
Annual Sum or Average | 5034.00000 | 22.96234 | 38.93597 | -0.2389 | 10.23856 |
Minimum of Months | 385.00000 | 20.38259 | 23.00801 | -0.7072 | 7.07171 |
Maximum of Months | 433.00000 | 24.65422 | 55.80009 | 0.29528 | 18.52264 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.33518 | 27.91417 | -0.4318 | 14.08290 |
February | 454.00000 | 22.14797 | 21.95589 | -0.2431 | 11.00484 |
March | 514.00000 | 22.63719 | 29.29847 | -0.0329 | 8.10454 |
April | 485.00000 | 23.19789 | 34.53735 | 0.14168 | 8.30143 |
May | 508.00000 | 23.97207 | 41.78692 | -0.4957 | 12.33709 |
June | 496.00000 | 24.28446 | 52.46315 | -0.2643 | 7.56174 |
July | 497.00000 | 24.49727 | 56.31650 | -0.1278 | 6.94583 |
August | 514.00000 | 24.40975 | 51.68954 | -0.1387 | 6.84779 |
September | 485.00000 | 24.32901 | 47.77547 | -0.2390 | 8.87397 |
October | 502.00000 | 24.11280 | 39.68826 | 0.48883 | 12.42449 |
November | 489.00000 | 22.79179 | 32.18833 | 0.01390 | 8.58363 |
December | 497.00000 | 22.04395 | 25.86881 | -0.2436 | 10.52177 |
Annual Sum or Average | 5943.00000 | 23.32186 | 38.58146 | -0.1309 | 9.62731 |
Minimum of Months | 454.00000 | 21.33518 | 21.95589 | -0.4957 | 6.84779 |
Maximum of Months | 514.00000 | 24.49727 | 56.31650 | 0.48883 | 14.08290 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.75997 | 28.93338 | -0.6017 | 15.57934 |
February | 454.00000 | 21.21811 | 23.23420 | -0.5035 | 12.93349 |
March | 514.00000 | 22.49199 | 29.81652 | -0.0948 | 7.67877 |
April | 485.00000 | 23.31454 | 34.45285 | 0.17071 | 8.20158 |
May | 508.00000 | 24.14838 | 41.30653 | -0.3970 | 10.56173 |
June | 496.00000 | 24.40754 | 51.89853 | -0.1499 | 7.18884 |
July | 497.00000 | 24.60181 | 55.82594 | -0.0350 | 7.29399 |
August | 514.00000 | 24.47230 | 51.57609 | -0.0820 | 6.82499 |
September | 485.00000 | 24.25187 | 48.17941 | -0.3033 | 8.96667 |
October | 502.00000 | 23.78992 | 40.84061 | 0.34907 | 9.55254 |
November | 489.00000 | 22.11049 | 33.81261 | -0.1906 | 8.33111 |
December | 497.00000 | 21.21395 | 27.25964 | -0.4744 | 11.30185 |
Annual Sum or Average | 5943.00000 | 23.07966 | 39.04436 | -0.1906 | 9.50978 |
Minimum of Months | 454.00000 | 20.75997 | 23.23420 | -0.6017 | 6.82499 |
Maximum of Months | 514.00000 | 24.60181 | 55.82594 | 0.34907 | 15.57934 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97227 | 30.67975 | -0.8623 | 23.61341 |
February | 454.00000 | 20.09684 | 25.32138 | -0.8546 | 22.79308 |
March | 514.00000 | 20.99474 | 33.24680 | -0.5175 | 12.77520 |
April | 485.00000 | 22.10220 | 37.53239 | -0.1764 | 8.84376 |
May | 508.00000 | 23.62422 | 43.03901 | -0.6555 | 16.51048 |
June | 496.00000 | 24.22285 | 52.88507 | -0.3034 | 7.83911 |
July | 497.00000 | 24.47598 | 56.80416 | -0.1568 | 6.89308 |
August | 514.00000 | 24.30637 | 52.55110 | -0.2591 | 7.46185 |
September | 485.00000 | 23.81851 | 50.01160 | -0.5300 | 12.95559 |
October | 502.00000 | 22.56474 | 44.11421 | -0.0004 | 8.61466 |
November | 489.00000 | 20.81012 | 36.95670 | -0.5509 | 14.25925 |
December | 497.00000 | 20.07362 | 30.00818 | -0.8228 | 21.59709 |
Annual Sum or Average | 5943.00000 | 22.27272 | 41.21047 | -0.4716 | 13.61417 |
Minimum of Months | 454.00000 | 19.97227 | 25.32138 | -0.8623 | 6.89308 |
Maximum of Months | 514.00000 | 24.47598 | 56.80416 | -0.0004 | 23.61341 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.12394 | 30.50338 | -0.7991 | 21.89929 |
February | 454.00000 | 20.48744 | 24.89939 | -0.7219 | 18.79166 |
March | 514.00000 | 21.71340 | 31.92813 | -0.3176 | 10.72482 |
April | 485.00000 | 22.81273 | 35.49136 | 0.02861 | 9.01716 |
May | 508.00000 | 23.95112 | 41.81602 | -0.4612 | 13.41112 |
June | 496.00000 | 24.33267 | 52.16315 | -0.1925 | 7.44487 |
July | 497.00000 | 24.56197 | 55.99114 | -0.0445 | 7.43125 |
August | 514.00000 | 24.40158 | 51.67872 | -0.1116 | 6.94404 |
September | 485.00000 | 24.13666 | 48.62263 | -0.3476 | 10.55240 |
October | 502.00000 | 23.28026 | 41.87085 | 0.20442 | 9.06383 |
November | 489.00000 | 21.33883 | 35.91833 | -0.4058 | 12.35450 |
December | 497.00000 | 20.31781 | 29.67021 | -0.7382 | 19.01865 |
Annual Sum or Average | 5943.00000 | 22.63838 | 40.15793 | -0.3229 | 12.17237 |
Minimum of Months | 454.00000 | 20.12394 | 24.89939 | -0.7991 | 6.94404 |
Maximum of Months | 514.00000 | 24.56197 | 55.99114 | 0.20442 | 21.89929 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.85587 | 29.17961 | -0.5806 | 18.23379 |
February | 454.00000 | 21.51640 | 23.31106 | -0.4329 | 14.81234 |
March | 514.00000 | 22.06818 | 30.75477 | -0.1963 | 10.40927 |
April | 485.00000 | 22.71398 | 35.69281 | 0.01116 | 9.36428 |
May | 508.00000 | 23.74400 | 42.51495 | -0.5722 | 15.44671 |
June | 496.00000 | 24.24650 | 52.66507 | -0.2657 | 7.91163 |
July | 497.00000 | 24.50416 | 56.45552 | -0.1064 | 7.13341 |
August | 514.00000 | 24.39589 | 51.82835 | -0.1289 | 7.04459 |
September | 485.00000 | 24.18029 | 48.42605 | -0.2879 | 10.23232 |
October | 502.00000 | 23.73578 | 40.51470 | 0.38299 | 11.83022 |
November | 489.00000 | 22.07488 | 34.11799 | -0.1891 | 10.72321 |
December | 497.00000 | 21.34254 | 27.98391 | -0.4534 | 15.07244 |
Annual Sum or Average | 5943.00000 | 22.95951 | 39.57340 | -0.2339 | 11.49985 |
Minimum of Months | 454.00000 | 20.85587 | 23.31106 | -0.5806 | 7.04459 |
Maximum of Months | 514.00000 | 24.50416 | 56.45552 | 0.38299 | 18.23379 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.37067 | 30.04027 | -0.7284 | 19.82452 |
February | 454.00000 | 20.75513 | 24.40267 | -0.6484 | 17.35650 |
March | 514.00000 | 21.92892 | 31.16968 | -0.2482 | 9.80215 |
April | 485.00000 | 22.83470 | 35.56762 | 0.04728 | 9.05677 |
May | 508.00000 | 23.96178 | 41.93513 | -0.4594 | 12.90268 |
June | 496.00000 | 24.37839 | 52.06591 | -0.1493 | 7.44442 |
July | 497.00000 | 24.60285 | 55.97076 | -0.0167 | 7.53688 |
August | 514.00000 | 24.46550 | 51.67722 | -0.0709 | 6.97754 |
September | 485.00000 | 24.12376 | 48.76759 | -0.3452 | 10.33034 |
October | 502.00000 | 23.35955 | 41.73628 | 0.23716 | 9.65069 |
November | 489.00000 | 21.42911 | 35.56823 | -0.3772 | 11.35364 |
December | 497.00000 | 20.63884 | 29.07208 | -0.6475 | 16.22423 |
Annual Sum or Average | 5943.00000 | 22.75370 | 39.94337 | -0.2813 | 11.49455 |
Minimum of Months | 454.00000 | 20.37067 | 24.40267 | -0.7284 | 6.97754 |
Maximum of Months | 514.00000 | 24.60285 | 55.97076 | 0.23716 | 19.82452 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.168586E+09 | 9620.33 | 24-JAN-07:14 | 46.31 | 0.164479E+10 | 0.00 | 0.181337E+10 | 0.61 | 9.85 | 19-JAN-14:30 | 0.00 | 0.00 |
February | 0.220662E+09 | 4373.03 | 02-FEB-11:05 | 50.24 | 0.215441E+10 | 0.00 | 0.237507E+10 | 0.73 | 9.86 | 24-FEB-15:30 | 0.00 | 0.00 |
March | 0.321075E+10 | 58061.88 | 27-MAR-16:00 | 148.22 | 0.314145E+11 | 0.00 | 0.346252E+11 | 1.94 | 10.00 | 27-MAR-14:10 | 0.00 | 0.00 |
April | 0.143856E+11 | 178263.72 | 07-APR-15:50 | 189.50 | 0.134786E+12 | 0.00 | 0.149172E+12 | 2.55 | 10.00 | 10-APR-16:10 | 0.00 | 0.00 |
May | 0.384504E+11 | 185424.09 | 30-MAY-11:45 | 347.11 | 0.360955E+12 | 0.00 | 0.399406E+12 | 4.51 | 10.01 | 28-MAY-09:33 | 0.00 | 0.00 |
June | 0.121626E+12 | 199573.26 | 19-JUN-07:10 | 524.99 | 0.103562E+13 | 0.00 | 0.115725E+13 | 6.61 | 10.01 | 08-JUN-04:12 | 0.00 | 0.00 |
July | 0.152594E+12 | 199898.33 | 21-JUL-16:50 | 657.10 | 0.126311E+13 | 0.00 | 0.141571E+13 | 7.81 | 10.00 | 11-JUL-20:40 | 0.00 | 0.00 |
August | 0.148770E+12 | 201205.96 | 17-AUG-07:10 | 668.35 | 0.123744E+13 | 0.00 | 0.138621E+13 | 8.05 | 10.01 | 21-AUG-04:12 | 0.00 | 0.00 |
September | 0.862383E+11 | 192347.81 | 13-SEP-12:20 | 440.97 | 0.753470E+12 | 0.00 | 0.839708E+12 | 5.68 | 10.01 | 28-SEP-05:04 | 0.00 | 0.00 |
October | 0.434260E+11 | 191373.48 | 11-OCT-14:30 | 306.10 | 0.385969E+12 | 0.00 | 0.429395E+12 | 3.90 | 10.00 | 05-OCT-18:50 | 0.00 | 0.00 |
November | 0.391961E+10 | 52568.53 | 03-NOV-14:05 | 111.40 | 0.383270E+11 | 0.00 | 0.422466E+11 | 1.51 | 10.00 | 02-NOV-14:50 | 0.00 | 0.00 |
December | 0.528217E+09 | 4593.90 | 20-DEC-10:50 | 91.71 | 0.515954E+10 | 0.00 | 0.568775E+10 | 1.20 | 9.85 | 19-DEC-10:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.613539E+12 | 3582.00 | 0.525005E+13 | 0.00 | 0.586359E+13 | 3.78 | 0.00 | 0.00 | ||||
Minimum of Months | 0.168586E+09 | 4373.03 | 46.31 | 0.164479E+10 | 0.00 | 0.181337E+10 | 0.61 | 9.85 | 0.00 | 0.00 | ||
Maximum of Months | 0.152594E+12 | 201205.96 | 668.35 | 0.126311E+13 | 0.00 | 0.141571E+13 | 8.05 | 10.01 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 55422981.53 | 84342.67 | 07-APR-14:40 | 0.33 | 0.506008E+09 | 0.00 | 0.561431E+09 | 0.00 | 10.52 | 07-APR-14:30 | 0.00 | 0.00 |
May | 0.343667E+10 | 151311.62 | 30-MAY-12:03 | 12.28 | 0.308941E+11 | 0.00 | 0.343308E+11 | 0.15 | 10.57 | 30-MAY-12:00 | 0.00 | 0.00 |
June | 0.249286E+11 | 121155.16 | 21-JUN-12:05 | 89.21 | 0.220413E+12 | 0.00 | 0.245342E+12 | 1.10 | 10.49 | 20-JUN-15:40 | 0.00 | 0.00 |
July | 0.443160E+11 | 191504.94 | 24-JUL-05:05 | 151.08 | 0.381210E+12 | 0.00 | 0.425526E+12 | 1.75 | 10.49 | 11-JUL-09:20 | 0.00 | 0.00 |
August | 0.469633E+11 | 126549.42 | 22-AUG-14:30 | 157.44 | 0.403440E+12 | 0.00 | 0.450403E+12 | 1.83 | 10.71 | 30-AUG-17:00 | 0.00 | 0.00 |
September | 0.134131E+11 | 149353.64 | 01-SEP-13:33 | 47.07 | 0.118069E+12 | 0.00 | 0.131482E+12 | 0.58 | 10.22 | 14-SEP-16:00 | 0.00 | 0.00 |
October | 0.507583E+10 | 100199.28 | 13-OCT-12:45 | 19.50 | 0.462440E+11 | 0.00 | 0.513198E+11 | 0.24 | 10.41 | 13-OCT-14:40 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.138189E+12 | 476.91 | 0.120078E+13 | 0.00 | 0.133896E+13 | 0.48 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.469633E+11 | 191504.94 | 157.44 | 0.403440E+12 | 0.00 | 0.450403E+12 | 1.83 | 10.71 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.527306E+09 | 744.00 | 2991.43 | 12-JAN-14:40 | 63430.89 | 12-JAN-14:50 | 18.57 | 18.33 | 15.66 |
February | 0.140605E+10 | 672.00 | 2338.47 | 24-FEB-14:30 | 98322.97 | 24-FEB-15:50 | 19.15 | 18.33 | 15.69 |
March | 0.496063E+10 | 744.00 | 43776.24 | 27-MAR-12:20 | 354621.16 | 27-MAR-16:00 | 19.85 | 18.36 | 15.68 |
April | 0.228297E+11 | 720.00 | 43776.24 | 06-APR-09:00 | 633324.81 | 07-APR-13:05 | 21.65 | 18.84 | 15.67 |
May | 0.360087E+11 | 744.00 | 43776.24 | 05-MAY-11:30 | 329011.88 | 31-MAY-23:20 | 20.04 | 19.28 | 15.70 |
June | 0.100596E+12 | 720.00 | 43776.24 | 01-JUN-00:10 | 470151.80 | 21-JUN-16:40 | 27.89 | 23.48 | 15.70 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:10 | 625759.35 | 31-JUL-24:00 | 37.24 | 28.25 | 15.70 |
August | 0.116573E+12 | 744.00 | 43776.24 | 01-AUG-00:10 | 708951.27 | 22-AUG-14:44 | 39.74 | 28.73 | 15.70 |
September | 0.801616E+11 | 720.00 | 43776.24 | 01-SEP-00:05 | 315198.71 | 01-SEP-13:33 | 22.80 | 21.36 | 15.70 |
October | 0.325241E+11 | 744.00 | 43776.24 | 02-OCT-09:05 | 411638.35 | 25-OCT-10:50 | 20.21 | 18.91 | 15.69 |
November | 0.538350E+10 | 720.00 | 43776.24 | 03-NOV-13:40 | 140624.17 | 03-NOV-14:05 | 19.76 | 18.33 | 15.68 |
December | 0.383290E+10 | 744.00 | 3124.22 | 17-DEC-14:58 | 168502.64 | 20-DEC-11:10 | 20.18 | 18.33 | 15.68 |
Annual Sum or Average | 0.522054E+12 | 8760.00 | 23.97 | 20.90 | 15.69 | ||||
Minimum of Months | 0.527306E+09 | 672.00 | 2338.47 | 63430.89 | 18.57 | 18.33 | 15.66 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 708951.27 | 39.74 | 28.73 | 15.70 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 246303.70 | 31-JAN-09:27 | 20.95 | 20.95 | 0.47 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 246490.68 | 02-FEB-15:30 | 20.90 | 20.89 | 0.45 |
March | 32948382.48 | 10.58 | 2311.94 | 27-MAR-16:00 | 632135.22 | 27-MAR-16:00 | 21.05 | 20.99 | 4.30 |
April | 0.468486E+09 | 93.69 | 17798.55 | 07-APR-12:10 | 1393878.38 | 07-APR-15:30 | 21.27 | 21.04 | 11.77 |
May | 0.241238E+10 | 249.38 | 17798.55 | 18-MAY-09:50 | 1403938.28 | 30-MAY-08:40 | 21.75 | 21.16 | 26.64 |
June | 0.214249E+11 | 491.24 | 17798.55 | 01-JUN-09:30 | 1338638.94 | 22-JUN-09:00 | 24.07 | 22.38 | 43.94 |
July | 0.386586E+11 | 649.26 | 17798.55 | 01-JUL-04:12 | 1304466.39 | 11-JUL-17:00 | 25.83 | 23.81 | 51.90 |
August | 0.289885E+11 | 598.07 | 17798.55 | 01-AUG-00:10 | 1436072.56 | 23-AUG-10:40 | 25.03 | 23.03 | 51.85 |
September | 0.109000E+11 | 376.87 | 17798.55 | 01-SEP-04:12 | 1334484.70 | 28-SEP-14:40 | 23.22 | 21.98 | 36.39 |
October | 0.446279E+10 | 222.38 | 17798.55 | 02-OCT-12:40 | 1332616.96 | 05-OCT-10:50 | 21.87 | 21.25 | 22.77 |
November | 19376025.10 | 32.39 | 897.61 | 10-NOV-10:10 | 585211.59 | 03-NOV-14:10 | 21.19 | 21.12 | 5.07 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 247075.45 | 21-DEC-12:40 | 20.95 | 20.93 | 0.90 |
Annual Sum or Average | 0.107368E+12 | 2723.87 | 22.35 | 21.63 | 21.51 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 246303.70 | 20.90 | 20.89 | 0.45 | ||
Maximum of Months | 0.386586E+11 | 649.26 | 17798.55 | 1436072.56 | 25.83 | 23.81 | 51.90 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 20.95 | 20.95 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 20.90 | 20.90 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.05 | 21.05 | 0.00 |
April | 13018234.36 | 0.33 | 17798.55 | 07-APR-14:40 | 1141074.21 | 07-APR-14:40 | 21.27 | 21.27 | 0.03 |
May | 0.765338E+09 | 11.94 | 17798.55 | 30-MAY-09:23 | 1070298.04 | 30-MAY-14:07 | 21.75 | 21.69 | 0.98 |
June | 0.800957E+10 | 125.00 | 17798.55 | 01-JUN-10:00 | 1071578.45 | 22-JUN-15:30 | 24.07 | 23.46 | 9.43 |
July | 0.162431E+11 | 253.50 | 17798.55 | 01-JUL-10:10 | 1040741.08 | 11-JUL-10:20 | 25.83 | 24.64 | 17.36 |
August | 0.142892E+11 | 226.86 | 17798.55 | 01-AUG-07:10 | 1303537.89 | 30-AUG-15:50 | 25.03 | 23.95 | 16.29 |
September | 0.448737E+10 | 70.03 | 17798.55 | 01-SEP-07:20 | 1284205.77 | 01-SEP-13:33 | 23.22 | 22.87 | 5.19 |
October | 0.129751E+10 | 20.25 | 17798.55 | 03-OCT-10:05 | 1073747.46 | 13-OCT-12:45 | 21.87 | 21.78 | 1.66 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.19 | 21.19 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.95 | 20.95 | 0.00 |
Annual Sum or Average | 0.451052E+11 | 707.93 | 22.35 | 22.07 | 4.29 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 20.90 | 0.00 | ||
Maximum of Months | 0.162431E+11 | 253.50 | 17798.55 | 1303537.89 | 25.83 | 24.64 | 17.36 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.192673E+12 | 0.00 | 497.28 | 2052943.92 | 23-JAN-05:11 | 0.00 | 33.14 | 50.47 | 0.87 | 0.00 | 0.03 | 0.96 | 23-JAN-05:11 |
February | 0.123995E+12 | 0.00 | 426.30 | 1675446.03 | 22-FEB-05:01 | 0.00 | 32.51 | 49.13 | 0.60 | 0.00 | 0.02 | 0.79 | 22-FEB-05:01 |
March | 0.329511E+11 | 0.00 | 322.56 | 1503753.18 | 17-MAR-04:01 | 0.00 | 30.17 | 42.41 | 0.12 | 0.00 | 0.01 | 0.71 | 17-MAR-04:01 |
April | 0.821476E+10 | 0.00 | 164.65 | 1203312.68 | 03-APR-05:02 | 0.00 | 29.78 | 36.55 | 0.03 | 0.00 | 0.00 | 0.56 | 03-APR-05:02 |
May | 0.711486E+09 | 0.00 | 14.18 | 143641.52 | 30-MAY-14:10 | 0.00 | 30.97 | 31.51 | 0.00 | 0.00 | 0.00 | 0.07 | 30-MAY-14:10 |
June | 0.114832E+10 | 0.00 | 12.61 | 167922.35 | 01-JUN-15:00 | 0.00 | 44.72 | 44.98 | 0.01 | 0.00 | 0.00 | 0.08 | 01-JUN-15:00 |
July | 0.448654E+09 | 0.00 | 8.50 | 79735.82 | 11-JUL-16:05 | 0.00 | 48.07 | 48.25 | 0.00 | 0.00 | 0.00 | 0.04 | 11-JUL-16:05 |
August | 0.104273E+10 | 0.00 | 18.02 | 153203.85 | 24-AUG-17:03 | 0.00 | 44.63 | 45.05 | 0.01 | 0.00 | 0.00 | 0.07 | 24-AUG-17:03 |
September | 0.203335E+09 | 0.00 | 4.35 | 89790.99 | 01-SEP-16:40 | 0.00 | 36.83 | 36.97 | 0.00 | 0.00 | 0.00 | 0.04 | 01-SEP-16:40 |
October | 0.835384E+09 | 0.00 | 64.33 | 197000.35 | 28-OCT-05:03 | 0.00 | 33.69 | 36.07 | 0.00 | 0.00 | 0.00 | 0.09 | 28-OCT-05:03 |
November | 0.350380E+11 | 0.00 | 285.10 | 1725387.79 | 21-NOV-05:01 | 0.00 | 31.03 | 42.03 | 0.14 | 0.00 | 0.01 | 0.81 | 21-NOV-05:01 |
December | 0.860242E+11 | 0.00 | 438.88 | 1781275.13 | 11-DEC-05:01 | 0.00 | 30.84 | 47.31 | 0.32 | 0.00 | 0.02 | 0.84 | 11-DEC-05:01 |
Annual Sum or Average | 0.483286E+12 | 0.00 | 2256.75 | 0.00 | 35.56 | 42.53 | 0.17 | 0.00 | 0.01 | ||||
Minimum of Months | 0.203335E+09 | 0.00 | 4.35 | 79735.82 | 0.00 | 29.78 | 31.51 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.192673E+12 | 0.00 | 497.28 | 2052943.92 | 0.00 | 48.07 | 50.47 | 0.87 | 0.00 | 0.03 | 0.96 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 18.57 | 18.57 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.15 | 19.15 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.85 | 19.85 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 21.65 | 21.65 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 20.04 | 20.04 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 27.89 | 27.89 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 37.24 | 37.24 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 39.74 | 39.74 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 22.80 | 22.80 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 20.21 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.76 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.18 | 20.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 23.97 | 23.97 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.57 | 18.57 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.74 | 39.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.849817E+09 | 0.00 | 32.26 | 0.849817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22104.59 | 19-JAN-14:30 | 22104.59 | 19-JAN-14:30 | 0.00 | 0.00 | 0.00 |
February | 0.125199E+10 | 0.00 | 44.31 | 0.125199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24291.57 | 24-FEB-15:30 | 24291.57 | 24-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 0.513188E+10 | 0.00 | 106.72 | 0.508283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67669.95 | 27-MAR-16:00 | 67669.95 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.127418E+11 | 0.00 | 133.64 | 0.127397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113320.14 | 07-APR-14:40 | 113320.14 | 07-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.347046E+11 | 0.00 | 314.03 | 0.312502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 166403.52 | 30-MAY-13:35 | 166403.52 | 30-MAY-13:35 | 0.00 | 0.00 | 0.00 |
June | 0.126642E+12 | 0.00 | 513.97 | 0.105871E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 197259.98 | 15-JUN-04:11 | 174141.87 | 23-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.187679E+12 | 0.00 | 627.85 | 0.160610E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 222966.59 | 10-JUL-03:02 | 173305.97 | 11-JUL-13:55 | 0.00 | 0.00 | 0.00 |
August | 0.187504E+12 | 0.00 | 652.18 | 0.167595E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 216424.79 | 15-AUG-04:12 | 208896.25 | 24-AUG-17:07 | 0.00 | 0.00 | 0.00 |
September | 0.848009E+11 | 0.00 | 424.45 | 0.734516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205370.46 | 22-SEP-04:12 | 176971.78 | 01-SEP-14:05 | 0.00 | 0.00 | 0.00 |
October | 0.395126E+11 | 0.00 | 264.85 | 0.301706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 164083.14 | 06-OCT-04:12 | 97543.27 | 04-OCT-14:40 | 0.00 | 0.00 | 0.00 |
November | 0.336029E+10 | 0.00 | 85.17 | 0.326669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60437.66 | 10-NOV-06:02 | 40008.67 | 01-NOV-10:00 | 0.00 | 0.00 | 0.00 |
December | 0.356318E+10 | 0.00 | 87.94 | 0.356318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36131.12 | 18-DEC-14:30 | 36131.12 | 18-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.687742E+12 | 0.00 | 3287.38 | 0.595703E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.849817E+09 | 0.00 | 32.26 | 0.849817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22104.59 | 22104.59 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.187679E+12 | 0.00 | 652.18 | 0.167595E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 222966.59 | 208896.25 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.139159E+09 | 0.00 | 23.62 | 0.139159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39191.92 | 20-JAN-10:50 | 39191.92 | 20-JAN-10:50 | 0.00 | 0.00 | 0.00 |
February | 0.250504E+09 | 0.00 | 30.80 | 0.250504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47630.82 | 02-FEB-11:05 | 47630.82 | 02-FEB-11:05 | 0.00 | 0.00 | 0.00 |
March | 0.218981E+11 | 0.00 | 96.06 | 0.218695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 431527.00 | 27-MAR-16:00 | 431527.00 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.104413E+12 | 0.00 | 151.45 | 0.104387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 957684.71 | 07-APR-15:10 | 957684.71 | 07-APR-15:10 | 0.00 | 0.00 | 0.00 |
May | 0.301001E+12 | 0.00 | 315.63 | 0.272151E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1497939.64 | 30-MAY-14:03 | 1497939.64 | 30-MAY-14:03 | 0.00 | 0.00 | 0.00 |
June | 0.945556E+12 | 0.00 | 452.70 | 0.753566E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1737563.93 | 24-JUN-04:12 | 1581079.68 | 22-JUN-15:15 | 0.00 | 0.00 | 0.00 |
July | 0.124304E+13 | 0.00 | 480.55 | 0.981283E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1841080.14 | 24-JUL-04:12 | 1401758.28 | 11-JUL-15:05 | 0.00 | 0.00 | 0.00 |
August | 0.123091E+13 | 0.00 | 481.57 | 0.105122E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1705295.58 | 22-AUG-14:15 | 1705295.58 | 22-AUG-14:15 | 0.00 | 0.00 | 0.00 |
September | 0.662543E+12 | 0.00 | 399.63 | 0.558462E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1749016.61 | 07-SEP-04:11 | 1474035.99 | 01-SEP-14:05 | 0.00 | 0.00 | 0.00 |
October | 0.328121E+12 | 0.00 | 267.54 | 0.253209E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1312600.85 | 06-OCT-05:03 | 866237.63 | 04-OCT-14:05 | 0.00 | 0.00 | 0.00 |
November | 0.323225E+11 | 0.00 | 85.74 | 0.318925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 470374.24 | 03-NOV-14:05 | 470374.24 | 03-NOV-14:05 | 0.00 | 0.00 | 0.00 |
December | 0.346014E+09 | 0.00 | 58.51 | 0.346014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16819.39 | 15-DEC-14:50 | 16819.39 | 15-DEC-14:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.487054E+13 | 0.00 | 2843.79 | 0.402878E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.139159E+09 | 0.00 | 23.62 | 0.139159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16819.39 | 16819.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.124304E+13 | 0.00 | 481.57 | 0.105122E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1841080.14 | 1705295.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 15100802.44 | 0.00 | 27.52 | 15100802.44 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.07 | 15-JAN-10:40 | 1840.07 | 15-JAN-10:40 | 0.00 | 0.00 | 0.00 |
February | 22000573.56 | 0.00 | 30.69 | 22000573.56 | 0.00 | 0.00 | 0.00 | 0.00 | 613.37 | 17-FEB-14:30 | 613.37 | 17-FEB-14:30 | 0.00 | 0.00 | 0.00 |
March | 0.941381E+09 | 0.00 | 87.39 | 0.941381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35805.79 | 27-MAR-16:00 | 35805.79 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.921487E+10 | 0.00 | 134.31 | 0.921431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103816.01 | 07-APR-14:50 | 103816.01 | 07-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.307821E+11 | 0.00 | 302.90 | 0.280876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170025.65 | 30-MAY-13:20 | 170025.65 | 30-MAY-13:20 | 0.00 | 0.00 | 0.00 |
June | 0.102491E+12 | 0.00 | 449.73 | 0.832128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 185418.53 | 19-JUN-04:12 | 165682.67 | 22-JUN-15:05 | 0.00 | 0.00 | 0.00 |
July | 0.139133E+12 | 0.00 | 483.07 | 0.111734E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 213841.29 | 20-JUL-05:02 | 166038.65 | 11-JUL-14:00 | 0.00 | 0.00 | 0.00 |
August | 0.136144E+12 | 0.00 | 483.18 | 0.117777E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 187703.41 | 22-AUG-14:20 | 187703.41 | 22-AUG-14:20 | 0.00 | 0.00 | 0.00 |
September | 0.676418E+11 | 0.00 | 395.24 | 0.571579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 177145.92 | 22-SEP-05:02 | 175035.30 | 01-SEP-13:33 | 0.00 | 0.00 | 0.00 |
October | 0.281384E+11 | 0.00 | 245.46 | 0.212421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123193.61 | 04-OCT-15:00 | 96906.46 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 |
November | 0.679857E+09 | 0.00 | 59.06 | 0.650257E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17589.47 | 03-NOV-14:00 | 17589.47 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 31060803.06 | 0.00 | 63.28 | 31060803.06 | 0.00 | 0.00 | 0.00 | 0.00 | 531.77 | 21-DEC-11:30 | 531.77 | 21-DEC-11:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.515234E+12 | 0.00 | 2761.82 | 0.430086E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 15100802.44 | 0.00 | 27.52 | 15100802.44 | 0.00 | 0.00 | 0.00 | 0.00 | 531.77 | 531.77 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.139133E+12 | 0.00 | 483.18 | 0.117777E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 213841.29 | 187703.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.187602E+09 | 0.00 | 14.65 | 0.108979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35644.72 | 24-JAN-07:12 | 15741.81 | 24-JAN-07:12 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.150773E+10 | 0.00 | 46.00 | 0.148228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41682.61 | 27-MAR-16:00 | 41682.61 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.629500E+10 | 0.00 | 94.28 | 0.618133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65329.42 | 10-APR-06:25 | 54160.48 | 10-APR-10:00 | 0.00 | 0.00 | 0.00 |
May | 0.200306E+11 | 0.00 | 221.41 | 0.176975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96688.83 | 30-MAY-14:00 | 96688.83 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.430033E+11 | 0.00 | 212.73 | 0.333950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141045.45 | 27-JUN-07:10 | 87434.24 | 21-JUN-06:11 | 0.00 | 0.00 | 0.00 |
July | 0.234277E+11 | 0.00 | 66.00 | 0.176126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136274.57 | 14-JUL-19:11 | 88238.27 | 11-JUL-13:55 | 0.00 | 0.00 | 0.00 |
August | 0.366682E+11 | 0.00 | 138.31 | 0.320459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121458.70 | 31-AUG-07:10 | 88529.85 | 21-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.346849E+11 | 0.00 | 218.04 | 0.298811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138717.86 | 08-SEP-06:22 | 83430.98 | 05-SEP-12:00 | 0.00 | 0.00 | 0.00 |
October | 0.258923E+11 | 0.00 | 215.79 | 0.200315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105816.39 | 06-OCT-08:35 | 58199.94 | 23-OCT-12:05 | 0.00 | 0.00 | 0.00 |
November | 0.589735E+09 | 0.00 | 23.98 | 0.473183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81481.48 | 10-NOV-07:25 | 31776.61 | 10-NOV-07:25 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192287E+12 | 0.00 | 1251.18 | 0.158909E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.430033E+11 | 0.00 | 221.41 | 0.333950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141045.45 | 96688.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.568164E+10 | 0.382769E+10 | 703.62 | 0.568155E+10 | 83238.66 | 0.00 | 0.02 | 19-JAN-15:00 | 0.01 | 24-JAN-18:40 | 3725.74 | 20-JAN-05:57 | 3725.74 | 20-JAN-05:57 | 24.63 | 18-JAN-18:40 | 2255.80 | 19-JAN-15:00 | 0.00 |
February | 0.106621E+11 | 0.488479E+10 | 672.00 | 0.106565E+11 | 5626479.64 | 0.00 | 0.03 | 24-FEB-15:40 | 0.01 | 28-FEB-16:00 | 5094.29 | 20-FEB-13:22 | 5094.29 | 20-FEB-13:22 | 59.08 | 28-FEB-17:30 | 2873.78 | 24-FEB-15:00 | 0.00 |
March | 0.143911E+11 | 0.617823E+10 | 697.81 | 0.131170E+11 | 0.127413E+10 | 0.00 | 0.51 | 27-MAR-16:00 | 0.01 | 26-MAR-20:10 | 215284.76 | 27-MAR-16:00 | 169846.80 | 27-MAR-16:00 | 70858.38 | 27-MAR-13:00 | 54750.23 | 27-MAR-16:00 | 0.00 |
April | 0.100006E+12 | 0.275497E+11 | 614.32 | 0.849500E+11 | 0.150564E+11 | 0.00 | 0.91 | 07-APR-13:00 | 0.01 | 16-APR-01:10 | 397089.10 | 07-APR-13:00 | 397089.10 | 07-APR-13:00 | 137861.85 | 09-APR-10:53 | 112591.79 | 07-APR-13:00 | 0.00 |
May | 0.222377E+11 | 0.857511E+10 | 465.63 | 0.216137E+11 | 0.624093E+09 | 0.00 | 0.52 | 30-MAY-13:30 | 0.01 | 25-MAY-05:15 | 217391.55 | 31-MAY-23:20 | 215661.14 | 31-MAY-23:20 | 34581.44 | 31-MAY-10:05 | 65638.50 | 30-MAY-13:30 | 0.00 |
June | 0.366363E+12 | 0.959833E+11 | 631.36 | 0.348613E+12 | 0.177502E+11 | 0.00 | 0.71 | 01-JUN-15:00 | 0.01 | 04-JUN-19:05 | 347069.07 | 21-JUN-16:40 | 307692.79 | 30-JUN-24:00 | 128786.83 | 21-JUN-16:30 | 90246.32 | 01-JUN-15:00 | 0.00 |
July | 0.846238E+12 | 0.225814E+12 | 744.00 | 0.829487E+12 | 0.167517E+11 | 0.00 | 0.88 | 31-JUL-24:00 | 0.30 | 11-JUL-05:00 | 400849.65 | 31-JUL-23:53 | 400747.62 | 31-JUL-23:57 | 141780.24 | 12-JUL-02:55 | 108822.06 | 07-JUL-12:00 | 0.00 |
August | 0.102340E+13 | 0.274735E+12 | 744.00 | 0.982346E+12 | 0.410585E+11 | 0.00 | 1.00 | 19-AUG-13:40 | 0.19 | 08-AUG-05:00 | 451957.01 | 31-AUG-06:11 | 445751.45 | 22-AUG-14:42 | 186005.02 | 31-AUG-06:10 | 137812.76 | 24-AUG-15:30 | 0.00 |
September | 0.928656E+11 | 0.270183E+11 | 448.53 | 0.884422E+11 | 0.442346E+10 | 0.00 | 0.61 | 01-SEP-13:33 | 0.01 | 28-SEP-06:35 | 254597.37 | 01-SEP-13:33 | 254597.37 | 01-SEP-13:33 | 88174.14 | 13-SEP-11:00 | 78371.65 | 01-SEP-13:33 | 0.00 |
October | 0.316249E+11 | 0.105786E+11 | 514.12 | 0.229414E+11 | 0.868348E+10 | 0.00 | 0.61 | 25-OCT-10:50 | 0.01 | 21-OCT-06:20 | 284932.13 | 25-OCT-10:50 | 223218.31 | 25-OCT-11:00 | 84487.76 | 25-OCT-10:40 | 71367.97 | 25-OCT-10:50 | 0.00 |
November | 0.107207E+11 | 0.517490E+10 | 621.87 | 0.104723E+11 | 0.248436E+09 | 0.00 | 0.14 | 03-NOV-14:00 | 0.01 | 11-NOV-14:55 | 45892.26 | 03-NOV-14:00 | 45892.26 | 03-NOV-14:00 | 7260.57 | 04-NOV-13:00 | 12627.48 | 03-NOV-14:00 | 0.00 |
December | 0.142067E+11 | 0.642848E+10 | 738.50 | 0.139926E+11 | 0.214160E+09 | 0.00 | 0.03 | 15-DEC-15:10 | 0.01 | 25-DEC-12:10 | 5976.22 | 26-DEC-00:50 | 5638.08 | 19-DEC-22:25 | 563.94 | 04-DEC-05:11 | 3178.78 | 15-DEC-14:20 | 0.00 |
Annual Sum or Average | 0.253840E+13 | 0.696748E+12 | 7595.75 | 0.243231E+13 | 0.106090E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.568164E+10 | 0.382769E+10 | 448.53 | 0.568155E+10 | 83238.66 | 0.00 | 0.02 | 0.01 | 3725.74 | 3725.74 | 24.63 | 2255.80 | 0.00 | ||||||
Maximum of Months | 0.102340E+13 | 0.274735E+12 | 744.00 | 0.982346E+12 | 0.410585E+11 | 0.00 | 1.00 | 0.30 | 451957.01 | 445751.45 | 186005.02 | 137812.76 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.343660E+10 | 0.815513E+09 | 744.00 | 0.343119E+10 | 5410094.65 | 0.00 | 0.30 | 16-JAN-16:25 | 0.03 | 02-JAN-07:03 | 2335.49 | 29-JAN-16:40 | 2335.49 | 29-JAN-16:40 | 98.86 | 24-JAN-15:20 | 517.88 | 16-JAN-16:25 | 0.00 |
February | 0.810138E+10 | 0.180567E+10 | 672.00 | 0.810138E+10 | -0.0 | 0.00 | 0.55 | 20-FEB-16:25 | 0.30 | 06-FEB-07:03 | 4370.14 | 20-FEB-16:30 | 4370.14 | 20-FEB-16:30 | 0.00 | 28-FEB-05:54 | 936.37 | 20-FEB-16:25 | 0.00 |
March | 0.149349E+11 | 0.305308E+10 | 744.00 | 0.149236E+11 | 11307166.31 | 0.00 | 0.82 | 31-MAR-24:00 | 0.58 | 01-MAR-07:03 | 7482.87 | 31-MAR-24:00 | 7482.87 | 31-MAR-24:00 | 234.76 | 27-MAR-15:00 | 1440.09 | 27-MAR-17:00 | 0.00 |
April | 0.197517E+11 | 0.385557E+10 | 720.00 | 0.197256E+11 | 26095278.09 | 0.00 | 0.97 | 23-APR-17:41 | 0.31 | 30-APR-24:00 | 8862.58 | 23-APR-17:41 | 8862.58 | 23-APR-17:41 | 255.77 | 27-APR-16:00 | 2131.06 | 07-APR-17:00 | 0.00 |
May | 0.557343E+10 | 0.124452E+10 | 744.00 | 0.547873E+10 | 94697920.00 | 0.00 | 0.48 | 31-MAY-23:20 | 0.20 | 04-MAY-07:00 | 4089.76 | 31-MAY-23:40 | 4018.52 | 31-MAY-24:00 | 276.67 | 18-MAY-15:30 | 890.59 | 31-MAY-23:20 | 0.00 |
June | 0.109602E+11 | 0.258980E+10 | 720.00 | 0.106386E+11 | 0.321622E+09 | 0.00 | 0.68 | 30-JUN-24:00 | 0.44 | 02-JUN-06:13 | 5888.54 | 30-JUN-24:00 | 5867.15 | 30-JUN-24:00 | 532.24 | 15-JUN-14:00 | 1634.34 | 19-JUN-12:05 | 0.00 |
July | 0.167872E+11 | 0.432982E+10 | 744.00 | 0.163005E+11 | 0.486704E+09 | 0.00 | 0.90 | 31-JUL-23:53 | 0.68 | 01-JUL-06:10 | 7852.97 | 31-JUL-23:53 | 7845.36 | 31-JUL-23:57 | 619.67 | 20-JUL-15:00 | 2106.18 | 10-JUL-15:00 | 0.00 |
August | 0.217212E+11 | 0.550749E+10 | 744.00 | 0.213341E+11 | 0.387158E+09 | 0.00 | 1.00 | 01-AUG-13:05 | 0.32 | 31-AUG-24:00 | 8893.87 | 31-AUG-17:50 | 8664.84 | 20-AUG-17:35 | 619.52 | 03-AUG-15:00 | 2659.34 | 24-AUG-15:40 | 0.00 |
September | 0.581815E+10 | 0.136678E+10 | 720.00 | 0.561672E+10 | 0.201436E+09 | 0.00 | 0.46 | 30-SEP-24:00 | 0.20 | 30-SEP-06:45 | 3918.04 | 30-SEP-24:00 | 3918.04 | 30-SEP-24:00 | 446.55 | 07-SEP-15:00 | 842.79 | 14-SEP-14:00 | 0.00 |
October | 0.107085E+11 | 0.224736E+10 | 744.00 | 0.105622E+11 | 0.146244E+09 | 0.00 | 0.64 | 31-OCT-24:00 | 0.42 | 28-OCT-06:55 | 5668.06 | 31-OCT-24:00 | 5667.32 | 31-OCT-24:00 | 351.97 | 24-OCT-16:00 | 1141.72 | 25-OCT-11:00 | 0.00 |
November | 0.145005E+11 | 0.292700E+10 | 720.00 | 0.144832E+11 | 17322386.11 | 0.00 | 0.74 | 23-NOV-16:05 | 0.60 | 01-NOV-06:15 | 6114.88 | 12-NOV-15:45 | 6108.57 | 12-NOV-15:45 | 249.19 | 10-NOV-10:10 | 1259.02 | 23-NOV-16:05 | 0.00 |
December | 0.197463E+11 | 0.397268E+10 | 744.00 | 0.197463E+11 | 0.00 | 0.00 | 0.98 | 03-DEC-15:55 | 0.80 | 04-DEC-22:00 | 8301.83 | 17-DEC-15:55 | 8301.83 | 17-DEC-15:55 | 0.00 | 03-DEC-00:40 | 1664.33 | 03-DEC-15:55 | 0.00 |
Annual Sum or Average | 0.152040E+12 | 0.337153E+11 | 8760.00 | 0.150342E+12 | 0.169800E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.343660E+10 | 0.815513E+09 | 672.00 | 0.343119E+10 | -0.0 | 0.00 | 0.30 | 0.03 | 2335.49 | 2335.49 | 0.00 | 517.88 | 0.00 | ||||||
Maximum of Months | 0.217212E+11 | 0.550749E+10 | 744.00 | 0.213341E+11 | 0.486704E+09 | 0.00 | 1.00 | 0.80 | 8893.87 | 8862.58 | 619.67 | 2659.34 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.896252E+10 | 0.231907E+10 | 505.86 | 0.892526E+10 | 37258119.04 | 0.00 | 0.24 | 20-JAN-16:30 | 0.00 | 01-JAN-00:02 | 17213.63 | 20-JAN-16:30 | 17213.63 | 20-JAN-16:30 | 800.49 | 24-JAN-15:20 | 3935.26 | 20-JAN-16:30 | 0.00 |
February | 0.563291E+11 | 0.129099E+11 | 672.00 | 0.563291E+11 | -0.0 | 0.00 | 0.49 | 22-FEB-17:00 | 0.13 | 06-FEB-07:03 | 36679.99 | 22-FEB-17:00 | 36679.99 | 22-FEB-17:00 | 0.00 | 06-FEB-05:04 | 8402.71 | 24-FEB-15:40 | 0.00 |
March | 0.127509E+12 | 0.264145E+11 | 744.00 | 0.127394E+12 | 0.114191E+09 | 0.00 | 0.77 | 31-MAR-23:40 | 0.48 | 01-MAR-07:03 | 66291.19 | 31-MAR-23:40 | 66291.19 | 31-MAR-23:40 | 2316.39 | 27-MAR-15:00 | 13519.80 | 27-MAR-17:00 | 0.00 |
April | 0.179275E+12 | 0.352728E+11 | 720.00 | 0.179013E+12 | 0.262437E+09 | 0.00 | 0.96 | 12-APR-17:40 | 0.22 | 30-APR-24:00 | 81783.77 | 09-APR-17:31 | 81751.97 | 09-APR-17:31 | 2526.75 | 27-APR-16:00 | 20345.16 | 07-APR-17:00 | 0.00 |
May | 0.487495E+11 | 0.109812E+11 | 744.00 | 0.478180E+11 | 0.931499E+09 | 0.00 | 0.48 | 31-MAY-23:20 | 0.14 | 01-MAY-06:05 | 38911.20 | 31-MAY-23:40 | 38167.78 | 31-MAY-24:00 | 2727.21 | 18-MAY-15:30 | 8483.31 | 31-MAY-23:20 | 0.00 |
June | 0.102324E+12 | 0.242565E+11 | 720.00 | 0.991325E+11 | 0.319136E+10 | 0.00 | 0.67 | 30-JUN-24:00 | 0.42 | 07-JUN-06:10 | 55348.51 | 30-JUN-24:00 | 55132.74 | 30-JUN-24:00 | 5275.68 | 15-JUN-14:00 | 15503.21 | 19-JUN-12:05 | 0.00 |
July | 0.158094E+12 | 0.408700E+11 | 744.00 | 0.153249E+12 | 0.484475E+10 | 0.00 | 0.89 | 31-JUL-23:53 | 0.66 | 01-JUL-06:10 | 74434.86 | 31-JUL-23:53 | 74355.99 | 31-JUL-23:57 | 6167.86 | 20-JUL-15:00 | 20002.85 | 07-JUL-12:10 | 0.00 |
August | 0.205811E+12 | 0.522899E+11 | 744.00 | 0.201944E+12 | 0.386731E+10 | 0.00 | 1.00 | 01-AUG-13:50 | 0.29 | 31-AUG-24:00 | 85285.04 | 31-AUG-17:50 | 81786.69 | 31-AUG-17:50 | 6226.22 | 03-AUG-15:00 | 25498.86 | 24-AUG-15:40 | 0.00 |
September | 0.511646E+11 | 0.121233E+11 | 720.00 | 0.491866E+11 | 0.197806E+10 | 0.00 | 0.45 | 30-SEP-23:30 | 0.17 | 30-SEP-06:55 | 36097.28 | 30-SEP-23:30 | 36097.28 | 30-SEP-23:30 | 4412.84 | 07-SEP-15:00 | 7915.11 | 14-SEP-14:00 | 0.00 |
October | 0.951443E+11 | 0.201195E+11 | 744.00 | 0.936921E+11 | 0.145221E+10 | 0.00 | 0.59 | 31-OCT-24:00 | 0.35 | 28-OCT-06:55 | 50007.66 | 31-OCT-24:00 | 49987.88 | 31-OCT-24:00 | 3500.08 | 24-OCT-16:00 | 10871.19 | 04-OCT-16:00 | 0.00 |
November | 0.121301E+12 | 0.248399E+11 | 720.00 | 0.121128E+12 | 0.173569E+09 | 0.00 | 0.68 | 03-NOV-16:00 | 0.47 | 24-NOV-07:03 | 57421.36 | 03-NOV-16:00 | 57421.36 | 03-NOV-16:00 | 2492.84 | 10-NOV-10:20 | 11273.32 | 03-NOV-16:00 | 0.00 |
December | 0.164059E+12 | 0.336491E+11 | 744.00 | 0.164059E+12 | -0.0 | 0.00 | 0.89 | 03-DEC-15:55 | 0.65 | 31-DEC-23:55 | 72080.10 | 08-DEC-16:10 | 72080.10 | 08-DEC-16:10 | 0.00 | 06-DEC-22:27 | 14527.79 | 03-DEC-15:55 | 0.00 |
Annual Sum or Average | 0.131872E+13 | 0.296046E+12 | 8521.86 | 0.130187E+13 | 0.168526E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.896252E+10 | 0.231907E+10 | 505.86 | 0.892526E+10 | -0.0 | 0.00 | 0.24 | 0.00 | 17213.63 | 17213.63 | 0.00 | 3935.26 | 0.00 | ||||||
Maximum of Months | 0.205811E+12 | 0.522899E+11 | 744.00 | 0.201944E+12 | 0.484475E+10 | 0.00 | 1.00 | 0.66 | 85285.04 | 81786.69 | 6226.22 | 25498.86 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.272098E+09 | 73212245.46 | 199.21 | 0.269826E+09 | 2271944.33 | 0.00 | 0.22 | 20-JAN-16:30 | 0.00 | 01-JAN-00:02 | 1656.69 | 19-JAN-16:30 | 1656.69 | 19-JAN-16:30 | 63.96 | 24-JAN-15:20 | 375.69 | 19-JAN-16:30 | 0.00 |
February | 0.396738E+10 | 0.932140E+09 | 663.17 | 0.396738E+10 | -0.0 | 0.00 | 0.47 | 02-FEB-16:50 | 0.00 | 05-FEB-18:05 | 3537.97 | 22-FEB-17:00 | 3537.97 | 22-FEB-17:00 | 0.00 | 13-FEB-05:31 | 780.71 | 02-FEB-16:50 | 0.00 |
March | 0.114028E+11 | 0.239183E+10 | 744.00 | 0.113917E+11 | 11190532.94 | 0.00 | 0.71 | 27-MAR-17:10 | 0.38 | 20-MAR-06:03 | 6106.39 | 27-MAR-17:20 | 6073.48 | 31-MAR-23:20 | 232.26 | 27-MAR-15:00 | 1353.17 | 27-MAR-17:00 | 0.00 |
April | 0.170684E+11 | 0.338759E+10 | 720.00 | 0.170423E+11 | 26070135.92 | 0.00 | 0.94 | 12-APR-17:40 | 0.14 | 30-APR-24:00 | 8251.25 | 09-APR-17:22 | 8244.63 | 09-APR-17:23 | 252.99 | 27-APR-16:00 | 2059.82 | 07-APR-17:00 | 0.00 |
May | 0.458680E+10 | 0.104222E+10 | 744.00 | 0.449444E+10 | 92361736.15 | 0.00 | 0.47 | 31-MAY-23:20 | 0.04 | 01-MAY-06:05 | 3852.74 | 31-MAY-23:30 | 3774.77 | 31-MAY-24:00 | 274.15 | 31-MAY-16:00 | 842.37 | 31-MAY-23:20 | 0.00 |
June | 0.102521E+11 | 0.243756E+10 | 720.00 | 0.993276E+10 | 0.319287E+09 | 0.00 | 0.65 | 30-JUN-24:00 | 0.38 | 03-JUN-06:11 | 5472.78 | 30-JUN-24:00 | 5450.80 | 30-JUN-24:00 | 529.78 | 15-JUN-14:00 | 1589.98 | 19-JUN-12:05 | 0.00 |
July | 0.159390E+11 | 0.412722E+10 | 744.00 | 0.154545E+11 | 0.484489E+09 | 0.00 | 0.88 | 31-JUL-23:53 | 0.64 | 01-JUL-06:10 | 7447.80 | 31-JUL-23:53 | 7439.81 | 31-JUL-23:57 | 617.63 | 20-JUL-15:00 | 2030.33 | 07-JUL-12:10 | 0.00 |
August | 0.206576E+11 | 0.526251E+10 | 744.00 | 0.202710E+11 | 0.386580E+09 | 0.00 | 1.00 | 01-AUG-15:40 | 0.28 | 31-AUG-24:00 | 8664.84 | 31-AUG-17:30 | 8386.02 | 13-AUG-18:13 | 628.03 | 03-AUG-15:00 | 2596.75 | 24-AUG-15:30 | 0.00 |
September | 0.493054E+10 | 0.117744E+10 | 720.00 | 0.473290E+10 | 0.197644E+09 | 0.00 | 0.41 | 10-SEP-17:21 | 0.11 | 30-SEP-06:55 | 3335.83 | 30-SEP-23:20 | 3335.83 | 30-SEP-23:20 | 444.78 | 07-SEP-15:00 | 821.04 | 14-SEP-14:00 | 0.00 |
October | 0.873521E+10 | 0.186237E+10 | 744.00 | 0.859055E+10 | 0.144668E+09 | 0.00 | 0.56 | 04-OCT-16:00 | 0.26 | 29-OCT-07:20 | 4638.20 | 04-OCT-16:30 | 4505.41 | 15-OCT-16:50 | 350.24 | 24-OCT-16:00 | 1102.69 | 04-OCT-16:00 | 0.00 |
November | 0.105387E+11 | 0.218861E+10 | 720.00 | 0.105215E+11 | 17144859.14 | 0.00 | 0.67 | 03-NOV-16:00 | 0.31 | 24-NOV-04:20 | 5727.40 | 03-NOV-16:00 | 5727.40 | 03-NOV-16:00 | 250.16 | 10-NOV-10:20 | 1127.38 | 03-NOV-16:00 | 0.00 |
December | 0.144272E+11 | 0.301087E+10 | 744.00 | 0.144272E+11 | 0.00 | 0.00 | 0.84 | 21-DEC-16:10 | 0.48 | 31-DEC-23:53 | 7012.40 | 08-DEC-16:10 | 7012.40 | 08-DEC-16:10 | 0.00 | 04-DEC-15:40 | 1409.72 | 21-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.122778E+12 | 0.278936E+11 | 8206.37 | 0.121096E+12 | 0.168171E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.272098E+09 | 73212245.46 | 199.21 | 0.269826E+09 | -0.0 | 0.00 | 0.22 | 0.00 | 1656.69 | 1656.69 | 0.00 | 375.69 | 0.00 | ||||||
Maximum of Months | 0.206576E+11 | 0.526251E+10 | 744.00 | 0.202710E+11 | 0.484489E+09 | 0.00 | 1.00 | 0.64 | 8664.84 | 8386.02 | 628.03 | 2596.75 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.39 | 0.00 | 116.39 | 2.73 | 721.68 | 0.00 | 0.00 | 0.00 |
February | 159.28 | 0.00 | 159.28 | 9.11 | 741.49 | 0.00 | 0.00 | 0.00 |
March | 220.88 | 0.00 | 220.88 | 63.68 | 510.62 | 0.00 | 0.00 | 0.00 |
April | 265.31 | 0.75 | 264.55 | 150.95 | 363.35 | 0.00 | 0.00 | 0.00 |
May | 351.98 | 11.73 | 340.25 | 323.20 | 208.22 | 0.00 | 0.00 | 0.00 |
June | 373.27 | 20.06 | 353.21 | 457.66 | 113.98 | 0.00 | 0.00 | 0.00 |
July | 360.73 | 13.05 | 347.68 | 505.08 | 67.38 | 0.00 | 0.00 | 0.00 |
August | 319.59 | 3.80 | 315.79 | 440.72 | 88.80 | 0.00 | 0.00 | 0.00 |
September | 240.92 | 0.05 | 240.87 | 251.84 | 177.64 | 0.00 | 0.00 | 0.00 |
October | 208.50 | 0.00 | 208.50 | 143.77 | 329.33 | 0.00 | 0.00 | 0.00 |
November | 146.24 | 0.00 | 146.24 | 29.84 | 534.53 | 0.00 | 0.00 | 0.00 |
December | 101.53 | 0.00 | 101.53 | 1.36 | 703.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.18 | 4.14 | 235.04 | 199.62 | 377.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.53 | 0.00 | 101.53 | 1.36 | 67.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.27 | 20.06 | 353.21 | 505.08 | 741.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.39 | 0.00 | 116.39 | 2.73 | 721.68 | 0.00 | 0.00 | 0.00 |
February | 159.28 | 0.00 | 159.28 | 9.11 | 741.49 | 0.00 | 0.00 | 0.00 |
March | 220.88 | 0.00 | 220.88 | 63.68 | 510.62 | 0.00 | 0.00 | 0.00 |
April | 265.31 | 0.75 | 264.55 | 150.95 | 363.35 | 0.00 | 0.00 | 0.00 |
May | 351.98 | 11.73 | 340.25 | 323.20 | 208.22 | 0.00 | 0.00 | 0.00 |
June | 373.27 | 20.06 | 353.21 | 457.66 | 113.98 | 0.00 | 0.00 | 0.00 |
July | 360.73 | 13.05 | 347.68 | 505.08 | 67.38 | 0.00 | 0.00 | 0.00 |
August | 319.59 | 3.80 | 315.79 | 440.72 | 88.80 | 0.00 | 0.00 | 0.00 |
September | 240.92 | 0.05 | 240.87 | 251.84 | 177.64 | 0.00 | 0.00 | 0.00 |
October | 208.50 | 0.00 | 208.50 | 143.77 | 329.33 | 0.00 | 0.00 | 0.00 |
November | 146.24 | 0.00 | 146.24 | 29.84 | 534.53 | 0.00 | 0.00 | 0.00 |
December | 101.53 | 0.00 | 101.53 | 1.36 | 703.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.18 | 4.14 | 235.04 | 199.62 | 377.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.53 | 0.00 | 101.53 | 1.36 | 67.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.27 | 20.06 | 353.21 | 505.08 | 741.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.39 | 0.00 | 116.39 | 2.73 | 721.68 | 0.00 | 0.00 | 0.00 |
February | 159.28 | 0.00 | 159.28 | 9.11 | 741.49 | 0.00 | 0.00 | 0.00 |
March | 220.88 | 0.00 | 220.88 | 63.68 | 510.62 | 0.00 | 0.00 | 0.00 |
April | 265.31 | 0.75 | 264.55 | 150.95 | 363.35 | 0.00 | 0.00 | 0.00 |
May | 351.98 | 11.73 | 340.25 | 323.20 | 208.22 | 0.00 | 0.00 | 0.00 |
June | 373.27 | 20.06 | 353.21 | 457.66 | 113.98 | 0.00 | 0.00 | 0.00 |
July | 360.73 | 13.05 | 347.68 | 505.08 | 67.38 | 0.00 | 0.00 | 0.00 |
August | 319.59 | 3.80 | 315.79 | 440.72 | 88.80 | 0.00 | 0.00 | 0.00 |
September | 240.92 | 0.05 | 240.87 | 251.84 | 177.64 | 0.00 | 0.00 | 0.00 |
October | 208.50 | 0.00 | 208.50 | 143.77 | 329.33 | 0.00 | 0.00 | 0.00 |
November | 146.24 | 0.00 | 146.24 | 29.84 | 534.53 | 0.00 | 0.00 | 0.00 |
December | 101.53 | 0.00 | 101.53 | 1.36 | 703.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.18 | 4.14 | 235.04 | 199.62 | 377.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.53 | 0.00 | 101.53 | 1.36 | 67.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.27 | 20.06 | 353.21 | 505.08 | 741.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.39 | 0.00 | 116.39 | 2.73 | 721.68 | 0.00 | 0.00 | 0.00 |
February | 159.28 | 0.00 | 159.28 | 9.11 | 741.49 | 0.00 | 0.00 | 0.00 |
March | 220.88 | 0.00 | 220.88 | 63.68 | 510.62 | 0.00 | 0.00 | 0.00 |
April | 265.31 | 0.75 | 264.55 | 150.95 | 363.35 | 0.00 | 0.00 | 0.00 |
May | 351.98 | 11.73 | 340.25 | 323.20 | 208.22 | 0.00 | 0.00 | 0.00 |
June | 373.27 | 20.06 | 353.21 | 457.66 | 113.98 | 0.00 | 0.00 | 0.00 |
July | 360.73 | 13.05 | 347.68 | 505.08 | 67.38 | 0.00 | 0.00 | 0.00 |
August | 319.59 | 3.80 | 315.79 | 440.72 | 88.80 | 0.00 | 0.00 | 0.00 |
September | 240.92 | 0.05 | 240.87 | 251.84 | 177.64 | 0.00 | 0.00 | 0.00 |
October | 208.50 | 0.00 | 208.50 | 143.77 | 329.33 | 0.00 | 0.00 | 0.00 |
November | 146.24 | 0.00 | 146.24 | 29.84 | 534.53 | 0.00 | 0.00 | 0.00 |
December | 101.53 | 0.00 | 101.53 | 1.36 | 703.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.18 | 4.14 | 235.04 | 199.62 | 377.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.53 | 0.00 | 101.53 | 1.36 | 67.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.27 | 20.06 | 353.21 | 505.08 | 741.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.39 | 0.00 | 116.39 | 2.73 | 721.65 | 0.00 | 0.00 | 0.00 |
February | 159.27 | 0.00 | 159.27 | 9.11 | 741.46 | 0.00 | 0.00 | 0.00 |
March | 220.87 | 0.00 | 220.87 | 63.68 | 510.60 | 0.00 | 0.00 | 0.00 |
April | 265.30 | 0.75 | 264.54 | 150.95 | 363.34 | 0.00 | 0.00 | 0.00 |
May | 351.97 | 11.73 | 340.24 | 323.19 | 208.21 | 0.00 | 0.00 | 0.00 |
June | 373.26 | 20.06 | 353.20 | 457.64 | 113.97 | 0.00 | 0.00 | 0.00 |
July | 360.72 | 13.04 | 347.67 | 505.06 | 67.38 | 0.00 | 0.00 | 0.00 |
August | 319.58 | 3.80 | 315.77 | 440.70 | 88.79 | 0.00 | 0.00 | 0.00 |
September | 240.91 | 0.05 | 240.86 | 251.83 | 177.63 | 0.00 | 0.00 | 0.00 |
October | 208.49 | 0.00 | 208.49 | 143.77 | 329.32 | 0.00 | 0.00 | 0.00 |
November | 146.23 | 0.00 | 146.23 | 29.84 | 534.51 | 0.00 | 0.00 | 0.00 |
December | 101.52 | 0.00 | 101.52 | 1.36 | 703.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.17 | 4.14 | 235.03 | 199.61 | 377.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.52 | 0.00 | 101.52 | 1.36 | 67.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.26 | 20.06 | 353.20 | 505.06 | 741.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 270.15 | 108.31 | 161.84 | 154.18 | 743.38 | 0.00 | 0.00 | 0.00 |
February | 418.94 | 195.44 | 223.50 | 277.69 | 738.67 | 0.00 | 0.00 | 0.00 |
March | 534.44 | 227.30 | 307.14 | 452.85 | 533.88 | 0.00 | 0.00 | 0.00 |
April | 641.36 | 280.94 | 360.43 | 637.79 | 377.42 | 0.00 | 0.00 | 0.00 |
May | 777.84 | 310.87 | 466.97 | 897.86 | 234.03 | 0.00 | 0.00 | 0.00 |
June | 720.89 | 260.96 | 459.93 | 940.32 | 127.06 | 0.00 | 0.00 | 0.00 |
July | 724.05 | 261.29 | 462.76 | 1020.15 | 73.44 | 0.00 | 0.00 | 0.00 |
August | 815.29 | 367.62 | 447.68 | 1144.62 | 95.38 | 0.00 | 0.00 | 0.00 |
September | 608.05 | 272.81 | 335.24 | 754.90 | 189.94 | 0.00 | 0.00 | 0.00 |
October | 551.24 | 249.84 | 301.40 | 604.15 | 348.60 | 0.00 | 0.00 | 0.00 |
November | 340.90 | 130.91 | 209.99 | 257.79 | 544.03 | 0.00 | 0.00 | 0.00 |
December | 265.58 | 124.70 | 140.88 | 167.03 | 701.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.61 | 232.84 | 323.77 | 611.41 | 390.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.58 | 108.31 | 140.88 | 154.18 | 73.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 815.29 | 367.62 | 466.97 | 1144.62 | 743.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 270.15 | 108.31 | 161.84 | 154.18 | 743.38 | 0.00 | 0.00 | 0.00 |
February | 418.94 | 195.44 | 223.50 | 277.69 | 738.67 | 0.00 | 0.00 | 0.00 |
March | 534.44 | 227.30 | 307.14 | 452.85 | 533.88 | 0.00 | 0.00 | 0.00 |
April | 641.36 | 280.94 | 360.43 | 637.79 | 377.42 | 0.00 | 0.00 | 0.00 |
May | 777.84 | 310.87 | 466.97 | 897.86 | 234.03 | 0.00 | 0.00 | 0.00 |
June | 720.89 | 260.96 | 459.93 | 940.32 | 127.06 | 0.00 | 0.00 | 0.00 |
July | 724.05 | 261.29 | 462.76 | 1020.15 | 73.44 | 0.00 | 0.00 | 0.00 |
August | 815.29 | 367.62 | 447.68 | 1144.62 | 95.38 | 0.00 | 0.00 | 0.00 |
September | 608.05 | 272.81 | 335.24 | 754.90 | 189.94 | 0.00 | 0.00 | 0.00 |
October | 551.24 | 249.84 | 301.40 | 604.15 | 348.60 | 0.00 | 0.00 | 0.00 |
November | 340.90 | 130.91 | 209.99 | 257.79 | 544.03 | 0.00 | 0.00 | 0.00 |
December | 265.58 | 124.70 | 140.88 | 167.03 | 701.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.61 | 232.84 | 323.77 | 611.41 | 390.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.58 | 108.31 | 140.88 | 154.18 | 73.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 815.29 | 367.62 | 466.97 | 1144.62 | 743.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 270.14 | 108.31 | 161.84 | 154.17 | 743.37 | 0.00 | 0.00 | 0.00 |
February | 418.93 | 195.43 | 223.50 | 277.68 | 738.65 | 0.00 | 0.00 | 0.00 |
March | 534.43 | 227.30 | 307.13 | 452.84 | 533.87 | 0.00 | 0.00 | 0.00 |
April | 641.35 | 280.93 | 360.42 | 637.78 | 377.41 | 0.00 | 0.00 | 0.00 |
May | 777.82 | 310.86 | 466.96 | 897.84 | 234.03 | 0.00 | 0.00 | 0.00 |
June | 720.88 | 260.95 | 459.92 | 940.30 | 127.06 | 0.00 | 0.00 | 0.00 |
July | 724.03 | 261.29 | 462.75 | 1020.14 | 73.44 | 0.00 | 0.00 | 0.00 |
August | 815.28 | 367.61 | 447.67 | 1144.60 | 95.38 | 0.00 | 0.00 | 0.00 |
September | 608.04 | 272.80 | 335.24 | 754.88 | 189.94 | 0.00 | 0.00 | 0.00 |
October | 551.23 | 249.84 | 301.40 | 604.14 | 348.59 | 0.00 | 0.00 | 0.00 |
November | 340.89 | 130.91 | 209.99 | 257.79 | 544.02 | 0.00 | 0.00 | 0.00 |
December | 265.58 | 124.70 | 140.88 | 167.02 | 701.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.60 | 232.84 | 323.76 | 611.40 | 390.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.58 | 108.31 | 140.88 | 154.17 | 73.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 815.28 | 367.61 | 466.96 | 1144.60 | 743.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.13 | 394.28 | 207.85 | 584.11 | 620.77 | 0.00 | 0.00 | 0.00 |
February | 794.19 | 525.69 | 268.50 | 785.01 | 626.36 | 0.00 | 0.00 | 0.00 |
March | 716.51 | 397.68 | 318.83 | 752.78 | 475.01 | 0.00 | 0.00 | 0.00 |
April | 555.99 | 219.85 | 336.13 | 600.89 | 358.92 | 0.00 | 0.00 | 0.00 |
May | 487.24 | 101.63 | 385.61 | 564.41 | 221.09 | 0.00 | 0.00 | 0.00 |
June | 457.26 | 69.90 | 387.36 | 613.44 | 120.95 | 0.00 | 0.00 | 0.00 |
July | 479.30 | 83.25 | 396.05 | 710.53 | 68.46 | 0.00 | 0.00 | 0.00 |
August | 640.05 | 237.41 | 402.65 | 958.85 | 93.48 | 0.00 | 0.00 | 0.00 |
September | 694.47 | 359.21 | 335.26 | 925.03 | 179.30 | 0.00 | 0.00 | 0.00 |
October | 951.36 | 596.57 | 354.79 | 1181.27 | 320.34 | 0.00 | 0.00 | 0.00 |
November | 659.69 | 396.17 | 263.51 | 692.61 | 473.53 | 0.00 | 0.00 | 0.00 |
December | 652.62 | 463.32 | 189.30 | 658.58 | 587.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 640.18 | 319.37 | 320.80 | 752.51 | 343.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.26 | 69.90 | 189.30 | 564.41 | 68.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 951.36 | 596.57 | 402.65 | 1181.27 | 626.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.13 | 394.28 | 207.85 | 584.11 | 620.77 | 0.00 | 0.00 | 0.00 |
February | 794.19 | 525.69 | 268.50 | 785.01 | 626.36 | 0.00 | 0.00 | 0.00 |
March | 716.51 | 397.67 | 318.83 | 752.77 | 475.01 | 0.00 | 0.00 | 0.00 |
April | 555.99 | 219.85 | 336.13 | 600.89 | 358.92 | 0.00 | 0.00 | 0.00 |
May | 487.24 | 101.63 | 385.61 | 564.41 | 221.09 | 0.00 | 0.00 | 0.00 |
June | 457.26 | 69.90 | 387.36 | 613.44 | 120.95 | 0.00 | 0.00 | 0.00 |
July | 479.30 | 83.25 | 396.05 | 710.53 | 68.46 | 0.00 | 0.00 | 0.00 |
August | 640.05 | 237.41 | 402.65 | 958.85 | 93.48 | 0.00 | 0.00 | 0.00 |
September | 694.47 | 359.21 | 335.26 | 925.03 | 179.30 | 0.00 | 0.00 | 0.00 |
October | 951.36 | 596.57 | 354.79 | 1181.27 | 320.34 | 0.00 | 0.00 | 0.00 |
November | 659.69 | 396.17 | 263.51 | 692.61 | 473.53 | 0.00 | 0.00 | 0.00 |
December | 652.62 | 463.32 | 189.30 | 658.58 | 587.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 640.18 | 319.37 | 320.80 | 752.51 | 343.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.26 | 69.90 | 189.30 | 564.41 | 68.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 951.36 | 596.57 | 402.65 | 1181.27 | 626.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.13 | 394.28 | 207.85 | 584.11 | 620.77 | 0.00 | 0.00 | 0.00 |
February | 794.19 | 525.69 | 268.50 | 785.01 | 626.36 | 0.00 | 0.00 | 0.00 |
March | 716.51 | 397.68 | 318.83 | 752.78 | 475.01 | 0.00 | 0.00 | 0.00 |
April | 555.99 | 219.85 | 336.13 | 600.89 | 358.92 | 0.00 | 0.00 | 0.00 |
May | 487.24 | 101.63 | 385.61 | 564.41 | 221.09 | 0.00 | 0.00 | 0.00 |
June | 457.26 | 69.90 | 387.36 | 613.44 | 120.95 | 0.00 | 0.00 | 0.00 |
July | 479.30 | 83.25 | 396.05 | 710.53 | 68.46 | 0.00 | 0.00 | 0.00 |
August | 640.05 | 237.41 | 402.65 | 958.85 | 93.48 | 0.00 | 0.00 | 0.00 |
September | 694.47 | 359.21 | 335.26 | 925.03 | 179.30 | 0.00 | 0.00 | 0.00 |
October | 951.36 | 596.57 | 354.79 | 1181.27 | 320.34 | 0.00 | 0.00 | 0.00 |
November | 659.69 | 396.17 | 263.51 | 692.61 | 473.53 | 0.00 | 0.00 | 0.00 |
December | 652.62 | 463.32 | 189.30 | 658.58 | 587.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 640.18 | 319.37 | 320.80 | 752.51 | 343.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.26 | 69.90 | 189.30 | 564.41 | 68.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 951.36 | 596.57 | 402.65 | 1181.27 | 626.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.13 | 394.28 | 207.85 | 584.11 | 620.77 | 0.00 | 0.00 | 0.00 |
February | 794.19 | 525.69 | 268.50 | 785.01 | 626.36 | 0.00 | 0.00 | 0.00 |
March | 716.51 | 397.67 | 318.83 | 752.77 | 475.01 | 0.00 | 0.00 | 0.00 |
April | 555.99 | 219.85 | 336.13 | 600.89 | 358.92 | 0.00 | 0.00 | 0.00 |
May | 487.24 | 101.63 | 385.61 | 564.41 | 221.09 | 0.00 | 0.00 | 0.00 |
June | 457.26 | 69.90 | 387.36 | 613.44 | 120.95 | 0.00 | 0.00 | 0.00 |
July | 479.30 | 83.25 | 396.05 | 710.53 | 68.46 | 0.00 | 0.00 | 0.00 |
August | 640.05 | 237.41 | 402.65 | 958.85 | 93.48 | 0.00 | 0.00 | 0.00 |
September | 694.47 | 359.21 | 335.26 | 925.03 | 179.30 | 0.00 | 0.00 | 0.00 |
October | 951.36 | 596.57 | 354.79 | 1181.27 | 320.34 | 0.00 | 0.00 | 0.00 |
November | 659.69 | 396.17 | 263.51 | 692.61 | 473.53 | 0.00 | 0.00 | 0.00 |
December | 652.62 | 463.32 | 189.30 | 658.58 | 587.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 640.18 | 319.37 | 320.80 | 752.51 | 343.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.26 | 69.90 | 189.30 | 564.41 | 68.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 951.36 | 596.57 | 402.65 | 1181.27 | 626.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.11 | 394.26 | 207.84 | 584.09 | 620.74 | 0.00 | 0.00 | 0.00 |
February | 794.16 | 525.67 | 268.49 | 784.98 | 626.33 | 0.00 | 0.00 | 0.00 |
March | 716.48 | 397.66 | 318.82 | 752.75 | 474.99 | 0.00 | 0.00 | 0.00 |
April | 555.96 | 219.84 | 336.12 | 600.87 | 358.91 | 0.00 | 0.00 | 0.00 |
May | 487.22 | 101.63 | 385.59 | 564.39 | 221.08 | 0.00 | 0.00 | 0.00 |
June | 457.24 | 69.89 | 387.35 | 613.41 | 120.95 | 0.00 | 0.00 | 0.00 |
July | 479.28 | 83.25 | 396.03 | 710.51 | 68.45 | 0.00 | 0.00 | 0.00 |
August | 640.03 | 237.40 | 402.63 | 958.81 | 93.47 | 0.00 | 0.00 | 0.00 |
September | 694.44 | 359.19 | 335.25 | 924.99 | 179.29 | 0.00 | 0.00 | 0.00 |
October | 951.33 | 596.55 | 354.78 | 1181.22 | 320.33 | 0.00 | 0.00 | 0.00 |
November | 659.66 | 396.16 | 263.50 | 692.58 | 473.51 | 0.00 | 0.00 | 0.00 |
December | 652.59 | 463.30 | 189.30 | 658.55 | 587.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 640.15 | 319.36 | 320.79 | 752.48 | 343.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.24 | 69.89 | 189.30 | 564.39 | 68.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 951.33 | 596.55 | 402.63 | 1181.22 | 626.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 266.70 | 109.24 | 157.46 | 151.37 | 803.09 | 0.00 | 0.00 | 0.00 |
February | 393.28 | 172.73 | 220.55 | 251.24 | 831.22 | 0.00 | 0.00 | 0.00 |
March | 580.73 | 268.11 | 312.62 | 494.99 | 597.54 | 0.00 | 0.00 | 0.00 |
April | 634.71 | 271.58 | 363.13 | 616.11 | 454.04 | 0.00 | 0.00 | 0.00 |
May | 739.37 | 280.78 | 458.59 | 844.00 | 263.87 | 0.00 | 0.00 | 0.00 |
June | 809.22 | 326.38 | 482.84 | 1050.38 | 155.52 | 0.00 | 0.00 | 0.00 |
July | 757.88 | 285.39 | 472.48 | 1052.19 | 96.77 | 0.00 | 0.00 | 0.00 |
August | 838.42 | 388.13 | 450.29 | 1165.37 | 129.10 | 0.00 | 0.00 | 0.00 |
September | 595.21 | 260.11 | 335.10 | 739.11 | 216.69 | 0.00 | 0.00 | 0.00 |
October | 590.11 | 286.95 | 303.15 | 647.55 | 397.27 | 0.00 | 0.00 | 0.00 |
November | 277.11 | 80.09 | 197.02 | 164.10 | 632.17 | 0.00 | 0.00 | 0.00 |
December | 246.49 | 106.65 | 139.83 | 136.29 | 823.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 561.94 | 236.89 | 325.06 | 611.97 | 447.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.49 | 80.09 | 139.83 | 136.29 | 96.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 838.42 | 388.13 | 482.84 | 1165.37 | 831.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 266.70 | 109.24 | 157.46 | 151.37 | 803.09 | 0.00 | 0.00 | 0.00 |
February | 393.28 | 172.73 | 220.55 | 251.24 | 831.22 | 0.00 | 0.00 | 0.00 |
March | 580.73 | 268.11 | 312.62 | 494.99 | 597.54 | 0.00 | 0.00 | 0.00 |
April | 634.71 | 271.58 | 363.13 | 616.11 | 454.04 | 0.00 | 0.00 | 0.00 |
May | 739.37 | 280.78 | 458.59 | 844.00 | 263.87 | 0.00 | 0.00 | 0.00 |
June | 809.22 | 326.38 | 482.84 | 1050.38 | 155.52 | 0.00 | 0.00 | 0.00 |
July | 757.88 | 285.39 | 472.48 | 1052.19 | 96.77 | 0.00 | 0.00 | 0.00 |
August | 838.42 | 388.13 | 450.29 | 1165.37 | 129.10 | 0.00 | 0.00 | 0.00 |
September | 595.21 | 260.11 | 335.10 | 739.11 | 216.69 | 0.00 | 0.00 | 0.00 |
October | 590.11 | 286.95 | 303.15 | 647.55 | 397.27 | 0.00 | 0.00 | 0.00 |
November | 277.11 | 80.09 | 197.02 | 164.10 | 632.17 | 0.00 | 0.00 | 0.00 |
December | 246.49 | 106.65 | 139.83 | 136.29 | 823.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 561.94 | 236.89 | 325.06 | 611.97 | 447.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.49 | 80.09 | 139.83 | 136.29 | 96.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 838.42 | 388.13 | 482.84 | 1165.37 | 831.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 266.69 | 109.24 | 157.45 | 151.37 | 803.07 | 0.00 | 0.00 | 0.00 |
February | 393.27 | 172.73 | 220.55 | 251.24 | 831.20 | 0.00 | 0.00 | 0.00 |
March | 580.72 | 268.10 | 312.62 | 494.98 | 597.52 | 0.00 | 0.00 | 0.00 |
April | 634.70 | 271.57 | 363.13 | 616.10 | 454.03 | 0.00 | 0.00 | 0.00 |
May | 739.36 | 280.78 | 458.58 | 843.99 | 263.86 | 0.00 | 0.00 | 0.00 |
June | 809.20 | 326.37 | 482.83 | 1050.36 | 155.51 | 0.00 | 0.00 | 0.00 |
July | 757.86 | 285.39 | 472.47 | 1052.17 | 96.77 | 0.00 | 0.00 | 0.00 |
August | 838.40 | 388.12 | 450.28 | 1165.35 | 129.09 | 0.00 | 0.00 | 0.00 |
September | 595.20 | 260.10 | 335.10 | 739.10 | 216.68 | 0.00 | 0.00 | 0.00 |
October | 590.09 | 286.95 | 303.15 | 647.54 | 397.26 | 0.00 | 0.00 | 0.00 |
November | 277.11 | 80.09 | 197.02 | 164.10 | 632.16 | 0.00 | 0.00 | 0.00 |
December | 246.48 | 106.65 | 139.83 | 136.28 | 823.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 561.93 | 236.88 | 325.05 | 611.96 | 447.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.48 | 80.09 | 139.83 | 136.28 | 96.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 838.40 | 388.12 | 482.83 | 1165.35 | 831.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 581.96 | 0.00 | 581.96 | 36.52 | 3186.44 | 0.00 | 0.00 | 0.00 |
February | 796.39 | 0.00 | 796.39 | 73.41 | 3328.09 | 0.00 | 0.00 | 0.00 |
March | 1104.39 | 0.00 | 1104.39 | 385.80 | 2252.28 | 0.00 | 0.00 | 0.00 |
April | 1326.53 | 3.77 | 1322.76 | 823.63 | 1609.86 | 0.00 | 0.00 | 0.00 |
May | 1759.88 | 58.64 | 1701.24 | 1634.32 | 989.62 | 0.00 | 0.00 | 0.00 |
June | 1866.33 | 100.29 | 1766.05 | 2309.11 | 531.58 | 0.00 | 0.00 | 0.00 |
July | 1803.63 | 65.23 | 1738.40 | 2569.55 | 291.20 | 0.00 | 0.00 | 0.00 |
August | 1597.93 | 19.02 | 1578.91 | 2252.44 | 396.08 | 0.00 | 0.00 | 0.00 |
September | 1204.57 | 0.23 | 1204.35 | 1289.37 | 810.63 | 0.00 | 0.00 | 0.00 |
October | 1042.47 | 0.00 | 1042.47 | 764.65 | 1494.03 | 0.00 | 0.00 | 0.00 |
November | 731.19 | 0.00 | 731.19 | 195.41 | 2308.56 | 0.00 | 0.00 | 0.00 |
December | 507.63 | 0.00 | 507.63 | 21.59 | 3009.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1195.87 | 20.71 | 1175.16 | 1036.14 | 1674.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 507.63 | 0.00 | 507.63 | 21.59 | 291.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1866.33 | 100.29 | 1766.05 | 2569.55 | 3328.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 810.43 | 324.92 | 485.51 | 491.97 | 1988.84 | 0.00 | 0.00 | 0.00 |
February | 1256.81 | 586.30 | 670.51 | 860.76 | 2030.65 | 0.00 | 0.00 | 0.00 |
March | 1603.29 | 681.89 | 921.40 | 1366.65 | 1480.66 | 0.00 | 0.00 | 0.00 |
April | 1924.06 | 842.80 | 1081.26 | 1915.05 | 1062.57 | 0.00 | 0.00 | 0.00 |
May | 2333.49 | 932.60 | 1400.88 | 2668.34 | 684.51 | 0.00 | 0.00 | 0.00 |
June | 2162.65 | 782.86 | 1379.78 | 2804.05 | 369.43 | 0.00 | 0.00 | 0.00 |
July | 2172.12 | 783.86 | 1388.25 | 3057.52 | 203.22 | 0.00 | 0.00 | 0.00 |
August | 2445.85 | 1102.84 | 1343.02 | 3425.27 | 274.64 | 0.00 | 0.00 | 0.00 |
September | 1824.13 | 818.42 | 1005.72 | 2253.63 | 539.83 | 0.00 | 0.00 | 0.00 |
October | 1653.71 | 749.52 | 904.19 | 1809.21 | 992.29 | 0.00 | 0.00 | 0.00 |
November | 1022.69 | 392.72 | 629.97 | 795.43 | 1475.67 | 0.00 | 0.00 | 0.00 |
December | 796.74 | 374.10 | 422.64 | 523.72 | 1875.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1669.81 | 698.53 | 971.29 | 1837.72 | 1076.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 796.74 | 324.92 | 422.64 | 491.97 | 203.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2445.85 | 1102.84 | 1400.88 | 3425.27 | 2030.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3010.62 | 1971.37 | 1039.25 | 2930.02 | 2919.52 | 0.00 | 0.00 | 0.00 |
February | 3970.90 | 2628.41 | 1342.49 | 3913.09 | 3009.93 | 0.00 | 0.00 | 0.00 |
March | 3582.50 | 1988.35 | 1594.15 | 3750.14 | 2261.03 | 0.00 | 0.00 | 0.00 |
April | 2779.90 | 1099.25 | 1680.64 | 3004.34 | 1695.62 | 0.00 | 0.00 | 0.00 |
May | 2436.17 | 508.15 | 1928.02 | 2805.24 | 1076.73 | 0.00 | 0.00 | 0.00 |
June | 2286.27 | 349.48 | 1936.79 | 3065.39 | 574.80 | 0.00 | 0.00 | 0.00 |
July | 2396.47 | 416.27 | 1980.20 | 3571.03 | 304.98 | 0.00 | 0.00 | 0.00 |
August | 3200.22 | 1187.01 | 2013.20 | 4801.43 | 435.55 | 0.00 | 0.00 | 0.00 |
September | 3472.30 | 1796.02 | 1676.29 | 4602.44 | 863.10 | 0.00 | 0.00 | 0.00 |
October | 4756.76 | 2982.83 | 1773.93 | 5861.72 | 1566.89 | 0.00 | 0.00 | 0.00 |
November | 3298.41 | 1980.85 | 1317.56 | 3462.05 | 2239.44 | 0.00 | 0.00 | 0.00 |
December | 3263.06 | 2316.55 | 946.51 | 3297.78 | 2750.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3200.85 | 1596.85 | 1604.00 | 3756.52 | 1633.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2286.27 | 349.48 | 946.51 | 2805.24 | 304.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4756.76 | 2982.83 | 2013.20 | 5861.72 | 3009.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 800.08 | 327.71 | 472.36 | 484.36 | 2086.40 | 0.00 | 0.00 | 0.00 |
February | 1179.83 | 518.19 | 661.64 | 792.82 | 2164.57 | 0.00 | 0.00 | 0.00 |
March | 1742.16 | 804.31 | 937.85 | 1535.62 | 1524.34 | 0.00 | 0.00 | 0.00 |
April | 1904.10 | 814.72 | 1089.39 | 1907.83 | 1142.97 | 0.00 | 0.00 | 0.00 |
May | 2218.09 | 842.34 | 1375.74 | 2542.55 | 734.32 | 0.00 | 0.00 | 0.00 |
June | 2427.63 | 979.13 | 1448.50 | 3165.81 | 414.05 | 0.00 | 0.00 | 0.00 |
July | 2273.60 | 856.17 | 1417.44 | 3188.03 | 239.08 | 0.00 | 0.00 | 0.00 |
August | 2515.23 | 1164.38 | 1350.84 | 3534.71 | 321.48 | 0.00 | 0.00 | 0.00 |
September | 1785.61 | 780.31 | 1005.30 | 2232.23 | 586.77 | 0.00 | 0.00 | 0.00 |
October | 1770.30 | 860.85 | 909.45 | 1972.73 | 1060.28 | 0.00 | 0.00 | 0.00 |
November | 831.33 | 240.26 | 591.07 | 541.33 | 1552.17 | 0.00 | 0.00 | 0.00 |
December | 739.45 | 319.96 | 419.49 | 452.84 | 1982.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1685.81 | 710.66 | 975.16 | 1870.27 | 1144.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 739.45 | 240.26 | 419.49 | 452.84 | 239.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2515.23 | 1164.38 | 1448.50 | 3534.71 | 2164.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 581.96 | 0.00 | 581.96 | 45.19 | 3034.59 | 0.00 | 0.00 | 0.00 |
February | 796.39 | 0.00 | 796.39 | 87.80 | 3139.71 | 0.00 | 0.00 | 0.00 |
March | 1104.39 | 0.00 | 1104.39 | 417.93 | 2093.49 | 0.00 | 0.00 | 0.00 |
April | 1326.53 | 3.77 | 1322.76 | 861.12 | 1495.23 | 0.00 | 0.00 | 0.00 |
May | 1759.88 | 58.64 | 1701.24 | 1643.04 | 953.06 | 0.00 | 0.00 | 0.00 |
June | 1866.33 | 100.29 | 1766.05 | 2289.87 | 528.97 | 0.00 | 0.00 | 0.00 |
July | 1803.63 | 65.23 | 1738.40 | 2540.48 | 300.89 | 0.00 | 0.00 | 0.00 |
August | 1597.93 | 19.02 | 1578.91 | 2231.72 | 398.12 | 0.00 | 0.00 | 0.00 |
September | 1204.57 | 0.23 | 1204.35 | 1290.16 | 780.17 | 0.00 | 0.00 | 0.00 |
October | 1042.47 | 0.00 | 1042.47 | 802.37 | 1383.18 | 0.00 | 0.00 | 0.00 |
November | 731.19 | 0.00 | 731.19 | 233.35 | 2097.48 | 0.00 | 0.00 | 0.00 |
December | 507.63 | 0.00 | 507.63 | 34.02 | 2773.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1195.87 | 20.71 | 1175.16 | 1046.17 | 1572.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 507.63 | 0.00 | 507.63 | 34.02 | 300.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1866.33 | 100.29 | 1766.05 | 2540.48 | 3139.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 810.43 | 324.92 | 485.51 | 507.86 | 1889.81 | 0.00 | 0.00 | 0.00 |
February | 1256.81 | 586.30 | 670.51 | 891.43 | 1903.90 | 0.00 | 0.00 | 0.00 |
March | 1603.29 | 681.89 | 921.40 | 1395.82 | 1373.67 | 0.00 | 0.00 | 0.00 |
April | 1924.06 | 842.80 | 1081.26 | 1941.57 | 993.62 | 0.00 | 0.00 | 0.00 |
May | 2333.49 | 932.60 | 1400.88 | 2674.45 | 661.44 | 0.00 | 0.00 | 0.00 |
June | 2162.65 | 782.86 | 1379.78 | 2796.06 | 367.24 | 0.00 | 0.00 | 0.00 |
July | 2172.12 | 783.86 | 1388.25 | 3044.21 | 208.75 | 0.00 | 0.00 | 0.00 |
August | 2445.85 | 1102.84 | 1343.02 | 3415.40 | 275.21 | 0.00 | 0.00 | 0.00 |
September | 1824.13 | 818.42 | 1005.72 | 2256.80 | 521.49 | 0.00 | 0.00 | 0.00 |
October | 1653.71 | 749.52 | 904.19 | 1833.49 | 926.81 | 0.00 | 0.00 | 0.00 |
November | 1022.69 | 392.72 | 629.97 | 834.61 | 1339.33 | 0.00 | 0.00 | 0.00 |
December | 796.74 | 374.10 | 422.64 | 551.12 | 1717.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1669.81 | 698.53 | 971.29 | 1851.85 | 1009.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 796.74 | 324.92 | 422.64 | 507.86 | 208.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2445.85 | 1102.84 | 1400.88 | 3415.40 | 1903.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3010.62 | 1971.37 | 1039.25 | 2955.56 | 2760.40 | 0.00 | 0.00 | 0.00 |
February | 3970.90 | 2628.41 | 1342.49 | 3956.68 | 2821.05 | 0.00 | 0.00 | 0.00 |
March | 3582.50 | 1988.35 | 1594.15 | 3780.10 | 2104.88 | 0.00 | 0.00 | 0.00 |
April | 2779.90 | 1099.25 | 1680.64 | 3032.01 | 1585.02 | 0.00 | 0.00 | 0.00 |
May | 2436.17 | 508.15 | 1928.02 | 2806.59 | 1037.52 | 0.00 | 0.00 | 0.00 |
June | 2286.27 | 349.48 | 1936.79 | 3044.18 | 571.84 | 0.00 | 0.00 | 0.00 |
July | 2396.47 | 416.27 | 1980.20 | 3540.83 | 314.40 | 0.00 | 0.00 | 0.00 |
August | 3200.22 | 1187.01 | 2013.20 | 4776.31 | 436.84 | 0.00 | 0.00 | 0.00 |
September | 3472.30 | 1796.02 | 1676.29 | 4596.52 | 835.72 | 0.00 | 0.00 | 0.00 |
October | 4756.76 | 2982.83 | 1773.93 | 5878.47 | 1476.06 | 0.00 | 0.00 | 0.00 |
November | 3298.41 | 1980.85 | 1317.56 | 3512.59 | 2049.27 | 0.00 | 0.00 | 0.00 |
December | 3263.06 | 2316.55 | 946.51 | 3345.33 | 2529.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3200.85 | 1596.85 | 1604.00 | 3769.66 | 1536.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2286.27 | 349.48 | 946.51 | 2806.59 | 314.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4756.76 | 2982.83 | 2013.20 | 5878.47 | 2821.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 800.08 | 327.71 | 472.36 | 493.38 | 1985.40 | 0.00 | 0.00 | 0.00 |
February | 1179.83 | 518.19 | 661.64 | 804.24 | 2054.02 | 0.00 | 0.00 | 0.00 |
March | 1742.16 | 804.31 | 937.85 | 1553.19 | 1431.23 | 0.00 | 0.00 | 0.00 |
April | 1904.10 | 814.72 | 1089.39 | 1923.05 | 1075.99 | 0.00 | 0.00 | 0.00 |
May | 2218.09 | 842.34 | 1375.74 | 2539.93 | 710.73 | 0.00 | 0.00 | 0.00 |
June | 2427.63 | 979.13 | 1448.50 | 3149.16 | 410.87 | 0.00 | 0.00 | 0.00 |
July | 2273.60 | 856.17 | 1417.44 | 3167.79 | 242.73 | 0.00 | 0.00 | 0.00 |
August | 2515.23 | 1164.38 | 1350.84 | 3518.03 | 321.46 | 0.00 | 0.00 | 0.00 |
September | 1785.61 | 780.31 | 1005.30 | 2227.86 | 569.42 | 0.00 | 0.00 | 0.00 |
October | 1770.30 | 860.85 | 909.45 | 1986.44 | 1000.39 | 0.00 | 0.00 | 0.00 |
November | 831.33 | 240.26 | 591.07 | 565.08 | 1433.71 | 0.00 | 0.00 | 0.00 |
December | 739.45 | 319.96 | 419.49 | 467.60 | 1847.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1685.81 | 710.66 | 975.16 | 1873.95 | 1084.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 739.45 | 240.26 | 419.49 | 467.60 | 242.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2515.23 | 1164.38 | 1448.50 | 3518.03 | 2054.02 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311750E+09 | 0.00 | 0.311750E+09 | 7301561.56 | 0.193296E+10 |
February | 0.385331E+09 | 0.00 | 0.385331E+09 | 22035376.66 | 0.179381E+10 |
March | 0.591609E+09 | 0.00 | 0.591609E+09 | 0.170568E+09 | 0.136765E+10 |
April | 0.687681E+09 | 1955975.73 | 0.685725E+09 | 0.391275E+09 | 0.941813E+09 |
May | 0.942744E+09 | 31412772.00 | 0.911332E+09 | 0.865667E+09 | 0.557704E+09 |
June | 0.967518E+09 | 51988794.86 | 0.915529E+09 | 0.118626E+10 | 0.295425E+09 |
July | 0.966180E+09 | 34940286.43 | 0.931239E+09 | 0.135281E+10 | 0.180473E+09 |
August | 0.855989E+09 | 10187475.72 | 0.845802E+09 | 0.118042E+10 | 0.237829E+09 |
September | 0.624458E+09 | 116935.68 | 0.624341E+09 | 0.652766E+09 | 0.460433E+09 |
October | 0.558438E+09 | 0.00 | 0.558438E+09 | 0.385081E+09 | 0.882082E+09 |
November | 0.379055E+09 | 0.00 | 0.379055E+09 | 77342866.84 | 0.138550E+10 |
December | 0.271928E+09 | 0.00 | 0.271928E+09 | 3632918.28 | 0.188333E+10 |
Annual Sum or Average | 0.754268E+10 | 0.130602E+09 | 0.741208E+10 | 0.629516E+10 | 0.119190E+11 |
Minimum of Months | 0.271928E+09 | 0.00 | 0.271928E+09 | 3632918.28 | 0.180473E+09 |
Maximum of Months | 0.967518E+09 | 51988794.86 | 0.931239E+09 | 0.135281E+10 | 0.193296E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311749E+09 | 0.00 | 0.311749E+09 | 7301503.34 | 0.193296E+10 |
February | 0.385330E+09 | 0.00 | 0.385330E+09 | 22035295.20 | 0.179381E+10 |
March | 0.591609E+09 | 0.00 | 0.591609E+09 | 0.170568E+09 | 0.136765E+10 |
April | 0.687680E+09 | 1955973.39 | 0.685724E+09 | 0.391274E+09 | 0.941813E+09 |
May | 0.942744E+09 | 31412734.31 | 0.911331E+09 | 0.865666E+09 | 0.557704E+09 |
June | 0.967517E+09 | 51988732.48 | 0.915528E+09 | 0.118626E+10 | 0.295425E+09 |
July | 0.966179E+09 | 34940244.51 | 0.931239E+09 | 0.135281E+10 | 0.180473E+09 |
August | 0.855988E+09 | 10187463.49 | 0.845801E+09 | 0.118042E+10 | 0.237829E+09 |
September | 0.624458E+09 | 116935.54 | 0.624341E+09 | 0.652766E+09 | 0.460433E+09 |
October | 0.558438E+09 | 0.00 | 0.558438E+09 | 0.385080E+09 | 0.882082E+09 |
November | 0.379055E+09 | 0.00 | 0.379055E+09 | 77342677.71 | 0.138550E+10 |
December | 0.271928E+09 | 0.00 | 0.271928E+09 | 3632891.07 | 0.188333E+10 |
Annual Sum or Average | 0.754267E+10 | 0.130602E+09 | 0.741207E+10 | 0.629515E+10 | 0.119190E+11 |
Minimum of Months | 0.271928E+09 | 0.00 | 0.271928E+09 | 3632891.07 | 0.180473E+09 |
Maximum of Months | 0.967517E+09 | 51988732.48 | 0.931239E+09 | 0.135281E+10 | 0.193296E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311750E+09 | 0.00 | 0.311750E+09 | 7301561.56 | 0.193296E+10 |
February | 0.385331E+09 | 0.00 | 0.385331E+09 | 22035376.66 | 0.179381E+10 |
March | 0.591609E+09 | 0.00 | 0.591609E+09 | 0.170568E+09 | 0.136765E+10 |
April | 0.687681E+09 | 1955975.73 | 0.685725E+09 | 0.391275E+09 | 0.941813E+09 |
May | 0.942744E+09 | 31412772.00 | 0.911332E+09 | 0.865667E+09 | 0.557704E+09 |
June | 0.967518E+09 | 51988794.86 | 0.915529E+09 | 0.118626E+10 | 0.295425E+09 |
July | 0.966180E+09 | 34940286.43 | 0.931239E+09 | 0.135281E+10 | 0.180473E+09 |
August | 0.855989E+09 | 10187475.72 | 0.845802E+09 | 0.118042E+10 | 0.237829E+09 |
September | 0.624458E+09 | 116935.68 | 0.624341E+09 | 0.652766E+09 | 0.460433E+09 |
October | 0.558438E+09 | 0.00 | 0.558438E+09 | 0.385081E+09 | 0.882082E+09 |
November | 0.379055E+09 | 0.00 | 0.379055E+09 | 77342866.84 | 0.138550E+10 |
December | 0.271928E+09 | 0.00 | 0.271928E+09 | 3632918.28 | 0.188333E+10 |
Annual Sum or Average | 0.754268E+10 | 0.130602E+09 | 0.741208E+10 | 0.629516E+10 | 0.119190E+11 |
Minimum of Months | 0.271928E+09 | 0.00 | 0.271928E+09 | 3632918.28 | 0.180473E+09 |
Maximum of Months | 0.967518E+09 | 51988794.86 | 0.931239E+09 | 0.135281E+10 | 0.193296E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311749E+09 | 0.00 | 0.311749E+09 | 7301503.34 | 0.193296E+10 |
February | 0.385330E+09 | 0.00 | 0.385330E+09 | 22035295.20 | 0.179381E+10 |
March | 0.591609E+09 | 0.00 | 0.591609E+09 | 0.170568E+09 | 0.136765E+10 |
April | 0.687680E+09 | 1955973.39 | 0.685724E+09 | 0.391274E+09 | 0.941813E+09 |
May | 0.942744E+09 | 31412734.31 | 0.911331E+09 | 0.865666E+09 | 0.557704E+09 |
June | 0.967517E+09 | 51988732.48 | 0.915528E+09 | 0.118626E+10 | 0.295425E+09 |
July | 0.966179E+09 | 34940244.51 | 0.931239E+09 | 0.135281E+10 | 0.180473E+09 |
August | 0.855988E+09 | 10187463.49 | 0.845801E+09 | 0.118042E+10 | 0.237829E+09 |
September | 0.624458E+09 | 116935.54 | 0.624341E+09 | 0.652766E+09 | 0.460433E+09 |
October | 0.558438E+09 | 0.00 | 0.558438E+09 | 0.385080E+09 | 0.882082E+09 |
November | 0.379055E+09 | 0.00 | 0.379055E+09 | 77342677.71 | 0.138550E+10 |
December | 0.271928E+09 | 0.00 | 0.271928E+09 | 3632891.07 | 0.188333E+10 |
Annual Sum or Average | 0.754267E+10 | 0.130602E+09 | 0.741207E+10 | 0.629515E+10 | 0.119190E+11 |
Minimum of Months | 0.271928E+09 | 0.00 | 0.271928E+09 | 3632891.07 | 0.180473E+09 |
Maximum of Months | 0.967517E+09 | 51988732.48 | 0.931239E+09 | 0.135281E+10 | 0.193296E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311737E+09 | 0.00 | 0.311737E+09 | 7301267.28 | 0.193288E+10 |
February | 0.385315E+09 | 0.00 | 0.385315E+09 | 22034488.54 | 0.179374E+10 |
March | 0.591585E+09 | 0.00 | 0.591585E+09 | 0.170562E+09 | 0.136759E+10 |
April | 0.687653E+09 | 1955896.90 | 0.685697E+09 | 0.391259E+09 | 0.941775E+09 |
May | 0.942706E+09 | 31411505.93 | 0.911295E+09 | 0.865632E+09 | 0.557682E+09 |
June | 0.967479E+09 | 51986699.49 | 0.915492E+09 | 0.118621E+10 | 0.295413E+09 |
July | 0.966141E+09 | 34938878.18 | 0.931202E+09 | 0.135275E+10 | 0.180466E+09 |
August | 0.855955E+09 | 10187065.12 | 0.845768E+09 | 0.118037E+10 | 0.237819E+09 |
September | 0.624433E+09 | 116930.97 | 0.624316E+09 | 0.652740E+09 | 0.460415E+09 |
October | 0.558415E+09 | 0.00 | 0.558415E+09 | 0.385065E+09 | 0.882046E+09 |
November | 0.379040E+09 | 0.00 | 0.379040E+09 | 77339749.58 | 0.138544E+10 |
December | 0.271917E+09 | 0.00 | 0.271917E+09 | 3632771.86 | 0.188325E+10 |
Annual Sum or Average | 0.754238E+10 | 0.130597E+09 | 0.741178E+10 | 0.629491E+10 | 0.119185E+11 |
Minimum of Months | 0.271917E+09 | 0.00 | 0.271917E+09 | 3632771.86 | 0.180466E+09 |
Maximum of Months | 0.967479E+09 | 51986699.49 | 0.931202E+09 | 0.135275E+10 | 0.193288E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723562E+09 | 0.290090E+09 | 0.433472E+09 | 0.412949E+09 | 0.199108E+10 |
February | 0.101350E+10 | 0.472798E+09 | 0.540701E+09 | 0.671781E+09 | 0.178698E+10 |
March | 0.143144E+10 | 0.608800E+09 | 0.822636E+09 | 0.121292E+10 | 0.142996E+10 |
April | 0.166241E+10 | 0.728186E+09 | 0.934222E+09 | 0.165316E+10 | 0.978260E+09 |
May | 0.208336E+10 | 0.832635E+09 | 0.125072E+10 | 0.240482E+10 | 0.626837E+09 |
June | 0.186855E+10 | 0.676401E+09 | 0.119215E+10 | 0.243730E+10 | 0.329342E+09 |
July | 0.193928E+10 | 0.699840E+09 | 0.123944E+10 | 0.273238E+10 | 0.196710E+09 |
August | 0.218368E+10 | 0.984622E+09 | 0.119906E+10 | 0.306576E+10 | 0.255461E+09 |
September | 0.157607E+10 | 0.707119E+09 | 0.868947E+09 | 0.195669E+10 | 0.492336E+09 |
October | 0.147645E+10 | 0.669176E+09 | 0.807272E+09 | 0.161816E+10 | 0.933689E+09 |
November | 0.883615E+09 | 0.339317E+09 | 0.544298E+09 | 0.668204E+09 | 0.141012E+10 |
December | 0.711333E+09 | 0.333998E+09 | 0.377334E+09 | 0.447361E+09 | 0.187957E+10 |
Annual Sum or Average | 0.175532E+11 | 0.734298E+10 | 0.102103E+11 | 0.192815E+11 | 0.123103E+11 |
Minimum of Months | 0.711333E+09 | 0.290090E+09 | 0.377334E+09 | 0.412949E+09 | 0.196710E+09 |
Maximum of Months | 0.218368E+10 | 0.984622E+09 | 0.125072E+10 | 0.306576E+10 | 0.199108E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723562E+09 | 0.290090E+09 | 0.433472E+09 | 0.412949E+09 | 0.199108E+10 |
February | 0.101350E+10 | 0.472798E+09 | 0.540701E+09 | 0.671781E+09 | 0.178698E+10 |
March | 0.143144E+10 | 0.608800E+09 | 0.822636E+09 | 0.121292E+10 | 0.142996E+10 |
April | 0.166241E+10 | 0.728186E+09 | 0.934222E+09 | 0.165316E+10 | 0.978260E+09 |
May | 0.208336E+10 | 0.832635E+09 | 0.125072E+10 | 0.240482E+10 | 0.626837E+09 |
June | 0.186855E+10 | 0.676401E+09 | 0.119215E+10 | 0.243730E+10 | 0.329342E+09 |
July | 0.193928E+10 | 0.699840E+09 | 0.123944E+10 | 0.273238E+10 | 0.196710E+09 |
August | 0.218368E+10 | 0.984622E+09 | 0.119906E+10 | 0.306576E+10 | 0.255461E+09 |
September | 0.157607E+10 | 0.707119E+09 | 0.868947E+09 | 0.195669E+10 | 0.492336E+09 |
October | 0.147645E+10 | 0.669176E+09 | 0.807272E+09 | 0.161816E+10 | 0.933689E+09 |
November | 0.883615E+09 | 0.339317E+09 | 0.544298E+09 | 0.668204E+09 | 0.141012E+10 |
December | 0.711333E+09 | 0.333998E+09 | 0.377334E+09 | 0.447361E+09 | 0.187957E+10 |
Annual Sum or Average | 0.175532E+11 | 0.734298E+10 | 0.102103E+11 | 0.192815E+11 | 0.123103E+11 |
Minimum of Months | 0.711333E+09 | 0.290090E+09 | 0.377334E+09 | 0.412949E+09 | 0.196710E+09 |
Maximum of Months | 0.218368E+10 | 0.984622E+09 | 0.125072E+10 | 0.306576E+10 | 0.199108E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723549E+09 | 0.290085E+09 | 0.433464E+09 | 0.412942E+09 | 0.199104E+10 |
February | 0.101348E+10 | 0.472789E+09 | 0.540691E+09 | 0.671769E+09 | 0.178695E+10 |
March | 0.143141E+10 | 0.608788E+09 | 0.822621E+09 | 0.121290E+10 | 0.142993E+10 |
April | 0.166238E+10 | 0.728173E+09 | 0.934205E+09 | 0.165313E+10 | 0.978242E+09 |
May | 0.208332E+10 | 0.832620E+09 | 0.125070E+10 | 0.240478E+10 | 0.626825E+09 |
June | 0.186851E+10 | 0.676388E+09 | 0.119212E+10 | 0.243725E+10 | 0.329336E+09 |
July | 0.193925E+10 | 0.699827E+09 | 0.123942E+10 | 0.273233E+10 | 0.196706E+09 |
August | 0.218364E+10 | 0.984604E+09 | 0.119904E+10 | 0.306570E+10 | 0.255456E+09 |
September | 0.157604E+10 | 0.707106E+09 | 0.868931E+09 | 0.195666E+10 | 0.492327E+09 |
October | 0.147642E+10 | 0.669164E+09 | 0.807257E+09 | 0.161813E+10 | 0.933672E+09 |
November | 0.883599E+09 | 0.339311E+09 | 0.544288E+09 | 0.668192E+09 | 0.141010E+10 |
December | 0.711320E+09 | 0.333992E+09 | 0.377327E+09 | 0.447353E+09 | 0.187953E+10 |
Annual Sum or Average | 0.175529E+11 | 0.734285E+10 | 0.102101E+11 | 0.192811E+11 | 0.123101E+11 |
Minimum of Months | 0.711320E+09 | 0.290085E+09 | 0.377327E+09 | 0.412942E+09 | 0.196706E+09 |
Maximum of Months | 0.218364E+10 | 0.984604E+09 | 0.125070E+10 | 0.306570E+10 | 0.199104E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161275E+10 | 0.105604E+10 | 0.556710E+09 | 0.156449E+10 | 0.166266E+10 |
February | 0.192130E+10 | 0.127175E+10 | 0.649557E+09 | 0.189909E+10 | 0.151529E+10 |
March | 0.191910E+10 | 0.106513E+10 | 0.853966E+09 | 0.201623E+10 | 0.127226E+10 |
April | 0.144112E+10 | 0.569860E+09 | 0.871255E+09 | 0.155751E+10 | 0.930319E+09 |
May | 0.130502E+10 | 0.272207E+09 | 0.103281E+10 | 0.151173E+10 | 0.592154E+09 |
June | 0.118522E+10 | 0.181173E+09 | 0.100404E+10 | 0.159003E+10 | 0.313504E+09 |
July | 0.128376E+10 | 0.222988E+09 | 0.106077E+10 | 0.190309E+10 | 0.183352E+09 |
August | 0.171431E+10 | 0.635868E+09 | 0.107845E+10 | 0.256818E+10 | 0.250371E+09 |
September | 0.180006E+10 | 0.931067E+09 | 0.868997E+09 | 0.239768E+10 | 0.464738E+09 |
October | 0.254813E+10 | 0.159786E+10 | 0.950270E+09 | 0.316392E+10 | 0.858002E+09 |
November | 0.170991E+10 | 0.102689E+10 | 0.683029E+09 | 0.179524E+10 | 0.122740E+10 |
December | 0.174798E+10 | 0.124095E+10 | 0.507030E+09 | 0.176393E+10 | 0.157265E+10 |
Annual Sum or Average | 0.201887E+11 | 0.100718E+11 | 0.101169E+11 | 0.237311E+11 | 0.108427E+11 |
Minimum of Months | 0.118522E+10 | 0.181173E+09 | 0.507030E+09 | 0.151173E+10 | 0.183352E+09 |
Maximum of Months | 0.254813E+10 | 0.159786E+10 | 0.107845E+10 | 0.316392E+10 | 0.166266E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161275E+10 | 0.105604E+10 | 0.556709E+09 | 0.156449E+10 | 0.166266E+10 |
February | 0.192130E+10 | 0.127175E+10 | 0.649556E+09 | 0.189909E+10 | 0.151529E+10 |
March | 0.191910E+10 | 0.106513E+10 | 0.853965E+09 | 0.201623E+10 | 0.127226E+10 |
April | 0.144111E+10 | 0.569860E+09 | 0.871254E+09 | 0.155751E+10 | 0.930319E+09 |
May | 0.130502E+10 | 0.272207E+09 | 0.103281E+10 | 0.151173E+10 | 0.592154E+09 |
June | 0.118522E+10 | 0.181172E+09 | 0.100404E+10 | 0.159003E+10 | 0.313504E+09 |
July | 0.128375E+10 | 0.222988E+09 | 0.106077E+10 | 0.190309E+10 | 0.183352E+09 |
August | 0.171431E+10 | 0.635867E+09 | 0.107845E+10 | 0.256818E+10 | 0.250370E+09 |
September | 0.180006E+10 | 0.931066E+09 | 0.868996E+09 | 0.239768E+10 | 0.464738E+09 |
October | 0.254813E+10 | 0.159786E+10 | 0.950269E+09 | 0.316391E+10 | 0.858002E+09 |
November | 0.170991E+10 | 0.102688E+10 | 0.683029E+09 | 0.179523E+10 | 0.122740E+10 |
December | 0.174797E+10 | 0.124095E+10 | 0.507029E+09 | 0.176393E+10 | 0.157265E+10 |
Annual Sum or Average | 0.201886E+11 | 0.100718E+11 | 0.101169E+11 | 0.237311E+11 | 0.108427E+11 |
Minimum of Months | 0.118522E+10 | 0.181172E+09 | 0.507029E+09 | 0.151173E+10 | 0.183352E+09 |
Maximum of Months | 0.254813E+10 | 0.159786E+10 | 0.107845E+10 | 0.316391E+10 | 0.166266E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161275E+10 | 0.105604E+10 | 0.556710E+09 | 0.156449E+10 | 0.166266E+10 |
February | 0.192130E+10 | 0.127175E+10 | 0.649557E+09 | 0.189909E+10 | 0.151529E+10 |
March | 0.191910E+10 | 0.106513E+10 | 0.853966E+09 | 0.201623E+10 | 0.127226E+10 |
April | 0.144112E+10 | 0.569860E+09 | 0.871255E+09 | 0.155751E+10 | 0.930319E+09 |
May | 0.130502E+10 | 0.272207E+09 | 0.103281E+10 | 0.151173E+10 | 0.592154E+09 |
June | 0.118522E+10 | 0.181173E+09 | 0.100404E+10 | 0.159003E+10 | 0.313504E+09 |
July | 0.128376E+10 | 0.222988E+09 | 0.106077E+10 | 0.190309E+10 | 0.183352E+09 |
August | 0.171431E+10 | 0.635868E+09 | 0.107845E+10 | 0.256818E+10 | 0.250371E+09 |
September | 0.180006E+10 | 0.931067E+09 | 0.868997E+09 | 0.239768E+10 | 0.464738E+09 |
October | 0.254813E+10 | 0.159786E+10 | 0.950270E+09 | 0.316392E+10 | 0.858002E+09 |
November | 0.170991E+10 | 0.102689E+10 | 0.683029E+09 | 0.179524E+10 | 0.122740E+10 |
December | 0.174798E+10 | 0.124095E+10 | 0.507030E+09 | 0.176393E+10 | 0.157265E+10 |
Annual Sum or Average | 0.201887E+11 | 0.100718E+11 | 0.101169E+11 | 0.237311E+11 | 0.108427E+11 |
Minimum of Months | 0.118522E+10 | 0.181173E+09 | 0.507030E+09 | 0.151173E+10 | 0.183352E+09 |
Maximum of Months | 0.254813E+10 | 0.159786E+10 | 0.107845E+10 | 0.316392E+10 | 0.166266E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161275E+10 | 0.105604E+10 | 0.556709E+09 | 0.156449E+10 | 0.166266E+10 |
February | 0.192130E+10 | 0.127175E+10 | 0.649556E+09 | 0.189909E+10 | 0.151529E+10 |
March | 0.191910E+10 | 0.106513E+10 | 0.853965E+09 | 0.201623E+10 | 0.127226E+10 |
April | 0.144111E+10 | 0.569860E+09 | 0.871254E+09 | 0.155751E+10 | 0.930319E+09 |
May | 0.130502E+10 | 0.272207E+09 | 0.103281E+10 | 0.151173E+10 | 0.592154E+09 |
June | 0.118522E+10 | 0.181172E+09 | 0.100404E+10 | 0.159003E+10 | 0.313504E+09 |
July | 0.128375E+10 | 0.222988E+09 | 0.106077E+10 | 0.190309E+10 | 0.183352E+09 |
August | 0.171431E+10 | 0.635867E+09 | 0.107845E+10 | 0.256818E+10 | 0.250370E+09 |
September | 0.180006E+10 | 0.931066E+09 | 0.868996E+09 | 0.239768E+10 | 0.464738E+09 |
October | 0.254813E+10 | 0.159786E+10 | 0.950269E+09 | 0.316391E+10 | 0.858002E+09 |
November | 0.170991E+10 | 0.102688E+10 | 0.683029E+09 | 0.179523E+10 | 0.122740E+10 |
December | 0.174797E+10 | 0.124095E+10 | 0.507029E+09 | 0.176393E+10 | 0.157265E+10 |
Annual Sum or Average | 0.201886E+11 | 0.100718E+11 | 0.101169E+11 | 0.237311E+11 | 0.108427E+11 |
Minimum of Months | 0.118522E+10 | 0.181172E+09 | 0.507029E+09 | 0.151173E+10 | 0.183352E+09 |
Maximum of Months | 0.254813E+10 | 0.159786E+10 | 0.107845E+10 | 0.316391E+10 | 0.166266E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161268E+10 | 0.105600E+10 | 0.556687E+09 | 0.156442E+10 | 0.166260E+10 |
February | 0.192123E+10 | 0.127170E+10 | 0.649531E+09 | 0.189902E+10 | 0.151523E+10 |
March | 0.191902E+10 | 0.106509E+10 | 0.853931E+09 | 0.201615E+10 | 0.127221E+10 |
April | 0.144106E+10 | 0.569837E+09 | 0.871220E+09 | 0.155745E+10 | 0.930282E+09 |
May | 0.130497E+10 | 0.272196E+09 | 0.103277E+10 | 0.151167E+10 | 0.592130E+09 |
June | 0.118517E+10 | 0.181165E+09 | 0.100400E+10 | 0.158997E+10 | 0.313491E+09 |
July | 0.128370E+10 | 0.222979E+09 | 0.106073E+10 | 0.190302E+10 | 0.183345E+09 |
August | 0.171425E+10 | 0.635842E+09 | 0.107840E+10 | 0.256808E+10 | 0.250360E+09 |
September | 0.179999E+10 | 0.931029E+09 | 0.868962E+09 | 0.239758E+10 | 0.464720E+09 |
October | 0.254803E+10 | 0.159780E+10 | 0.950232E+09 | 0.316379E+10 | 0.857968E+09 |
November | 0.170985E+10 | 0.102684E+10 | 0.683002E+09 | 0.179516E+10 | 0.122735E+10 |
December | 0.174791E+10 | 0.124090E+10 | 0.507010E+09 | 0.176386E+10 | 0.157259E+10 |
Annual Sum or Average | 0.201878E+11 | 0.100714E+11 | 0.101165E+11 | 0.237302E+11 | 0.108423E+11 |
Minimum of Months | 0.118517E+10 | 0.181165E+09 | 0.507010E+09 | 0.151167E+10 | 0.183345E+09 |
Maximum of Months | 0.254803E+10 | 0.159780E+10 | 0.107840E+10 | 0.316379E+10 | 0.166260E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.714317E+09 | 0.292586E+09 | 0.421730E+09 | 0.405438E+09 | 0.215099E+10 |
February | 0.951424E+09 | 0.417869E+09 | 0.533555E+09 | 0.607808E+09 | 0.201089E+10 |
March | 0.155542E+10 | 0.718094E+09 | 0.837324E+09 | 0.132579E+10 | 0.160044E+10 |
April | 0.164516E+10 | 0.703923E+09 | 0.941239E+09 | 0.159695E+10 | 0.117688E+10 |
May | 0.198033E+10 | 0.752052E+09 | 0.122828E+10 | 0.226057E+10 | 0.706739E+09 |
June | 0.209749E+10 | 0.845979E+09 | 0.125151E+10 | 0.272259E+10 | 0.403095E+09 |
July | 0.202990E+10 | 0.764396E+09 | 0.126550E+10 | 0.281819E+10 | 0.259197E+09 |
August | 0.224562E+10 | 0.103957E+10 | 0.120604E+10 | 0.312133E+10 | 0.345771E+09 |
September | 0.154278E+10 | 0.674193E+09 | 0.868590E+09 | 0.191578E+10 | 0.561656E+09 |
October | 0.158054E+10 | 0.768578E+09 | 0.811961E+09 | 0.173439E+10 | 0.106404E+10 |
November | 0.718273E+09 | 0.207586E+09 | 0.510687E+09 | 0.425342E+09 | 0.163858E+10 |
December | 0.660186E+09 | 0.285664E+09 | 0.374521E+09 | 0.365026E+09 | 0.220480E+10 |
Annual Sum or Average | 0.177214E+11 | 0.747049E+10 | 0.102509E+11 | 0.192992E+11 | 0.141231E+11 |
Minimum of Months | 0.660186E+09 | 0.207586E+09 | 0.374521E+09 | 0.365026E+09 | 0.259197E+09 |
Maximum of Months | 0.224562E+10 | 0.103957E+10 | 0.126550E+10 | 0.312133E+10 | 0.220480E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.714317E+09 | 0.292586E+09 | 0.421730E+09 | 0.405438E+09 | 0.215099E+10 |
February | 0.951424E+09 | 0.417869E+09 | 0.533555E+09 | 0.607808E+09 | 0.201089E+10 |
March | 0.155542E+10 | 0.718094E+09 | 0.837324E+09 | 0.132579E+10 | 0.160044E+10 |
April | 0.164516E+10 | 0.703923E+09 | 0.941239E+09 | 0.159695E+10 | 0.117688E+10 |
May | 0.198033E+10 | 0.752052E+09 | 0.122828E+10 | 0.226057E+10 | 0.706739E+09 |
June | 0.209749E+10 | 0.845979E+09 | 0.125151E+10 | 0.272259E+10 | 0.403095E+09 |
July | 0.202990E+10 | 0.764396E+09 | 0.126550E+10 | 0.281819E+10 | 0.259197E+09 |
August | 0.224562E+10 | 0.103957E+10 | 0.120604E+10 | 0.312133E+10 | 0.345771E+09 |
September | 0.154278E+10 | 0.674193E+09 | 0.868590E+09 | 0.191578E+10 | 0.561656E+09 |
October | 0.158054E+10 | 0.768578E+09 | 0.811961E+09 | 0.173439E+10 | 0.106404E+10 |
November | 0.718273E+09 | 0.207586E+09 | 0.510687E+09 | 0.425342E+09 | 0.163858E+10 |
December | 0.660186E+09 | 0.285664E+09 | 0.374521E+09 | 0.365026E+09 | 0.220480E+10 |
Annual Sum or Average | 0.177214E+11 | 0.747049E+10 | 0.102509E+11 | 0.192992E+11 | 0.141231E+11 |
Minimum of Months | 0.660186E+09 | 0.207586E+09 | 0.374521E+09 | 0.365026E+09 | 0.259197E+09 |
Maximum of Months | 0.224562E+10 | 0.103957E+10 | 0.126550E+10 | 0.312133E+10 | 0.220480E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.714304E+09 | 0.292581E+09 | 0.421723E+09 | 0.405431E+09 | 0.215095E+10 |
February | 0.951407E+09 | 0.417862E+09 | 0.533545E+09 | 0.607797E+09 | 0.201085E+10 |
March | 0.155539E+10 | 0.718081E+09 | 0.837309E+09 | 0.132577E+10 | 0.160041E+10 |
April | 0.164513E+10 | 0.703910E+09 | 0.941222E+09 | 0.159692E+10 | 0.117686E+10 |
May | 0.198029E+10 | 0.752038E+09 | 0.122825E+10 | 0.226053E+10 | 0.706726E+09 |
June | 0.209745E+10 | 0.845964E+09 | 0.125149E+10 | 0.272254E+10 | 0.403088E+09 |
July | 0.202986E+10 | 0.764382E+09 | 0.126548E+10 | 0.281814E+10 | 0.259192E+09 |
August | 0.224558E+10 | 0.103955E+10 | 0.120602E+10 | 0.312127E+10 | 0.345765E+09 |
September | 0.154275E+10 | 0.674180E+09 | 0.868575E+09 | 0.191574E+10 | 0.561646E+09 |
October | 0.158051E+10 | 0.768564E+09 | 0.811947E+09 | 0.173436E+10 | 0.106402E+10 |
November | 0.718260E+09 | 0.207582E+09 | 0.510678E+09 | 0.425335E+09 | 0.163855E+10 |
December | 0.660173E+09 | 0.285659E+09 | 0.374514E+09 | 0.365019E+09 | 0.220476E+10 |
Annual Sum or Average | 0.177211E+11 | 0.747036E+10 | 0.102508E+11 | 0.192989E+11 | 0.141228E+11 |
Minimum of Months | 0.660173E+09 | 0.207582E+09 | 0.374514E+09 | 0.365019E+09 | 0.259192E+09 |
Maximum of Months | 0.224558E+10 | 0.103955E+10 | 0.126548E+10 | 0.312127E+10 | 0.220476E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.155873E+10 | 0.00 | 0.155873E+10 | 97819743.30 | 0.853455E+10 |
February | 0.192663E+10 | 0.00 | 0.192663E+10 | 0.177590E+09 | 0.805131E+10 |
March | 0.295801E+10 | 0.00 | 0.295801E+10 | 0.103333E+10 | 0.603252E+10 |
April | 0.343836E+10 | 9779760.41 | 0.342858E+10 | 0.213486E+10 | 0.417275E+10 |
May | 0.471366E+10 | 0.157062E+09 | 0.455660E+10 | 0.437736E+10 | 0.265060E+10 |
June | 0.483753E+10 | 0.259941E+09 | 0.457759E+10 | 0.598521E+10 | 0.137785E+10 |
July | 0.483084E+10 | 0.174699E+09 | 0.465614E+10 | 0.688228E+10 | 0.779959E+09 |
August | 0.427989E+10 | 50936762.66 | 0.422896E+10 | 0.603294E+10 | 0.106086E+10 |
September | 0.312225E+10 | 584671.33 | 0.312167E+10 | 0.334204E+10 | 0.210114E+10 |
October | 0.279216E+10 | 0.00 | 0.279216E+10 | 0.204804E+10 | 0.400162E+10 |
November | 0.189525E+10 | 0.00 | 0.189525E+10 | 0.506499E+09 | 0.598379E+10 |
December | 0.135963E+10 | 0.00 | 0.135963E+10 | 57819336.13 | 0.806084E+10 |
Annual Sum or Average | 0.377129E+11 | 0.653003E+09 | 0.370599E+11 | 0.326758E+11 | 0.528078E+11 |
Minimum of Months | 0.135963E+10 | 0.00 | 0.135963E+10 | 57819336.13 | 0.779959E+09 |
Maximum of Months | 0.483753E+10 | 0.259941E+09 | 0.465614E+10 | 0.688228E+10 | 0.853455E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217066E+10 | 0.870261E+09 | 0.130040E+10 | 0.131769E+10 | 0.532691E+10 |
February | 0.304047E+10 | 0.141838E+10 | 0.162209E+10 | 0.208235E+10 | 0.491255E+10 |
March | 0.429426E+10 | 0.182638E+10 | 0.246788E+10 | 0.366043E+10 | 0.396579E+10 |
April | 0.498717E+10 | 0.218454E+10 | 0.280264E+10 | 0.496382E+10 | 0.275419E+10 |
May | 0.625001E+10 | 0.249788E+10 | 0.375213E+10 | 0.714687E+10 | 0.183340E+10 |
June | 0.560558E+10 | 0.202918E+10 | 0.357640E+10 | 0.726811E+10 | 0.957564E+09 |
July | 0.581779E+10 | 0.209950E+10 | 0.371830E+10 | 0.818925E+10 | 0.544317E+09 |
August | 0.655098E+10 | 0.295384E+10 | 0.359714E+10 | 0.917425E+10 | 0.735601E+09 |
September | 0.472815E+10 | 0.212134E+10 | 0.260681E+10 | 0.584140E+10 | 0.139923E+10 |
October | 0.442930E+10 | 0.200751E+10 | 0.242179E+10 | 0.484578E+10 | 0.265774E+10 |
November | 0.265082E+10 | 0.101794E+10 | 0.163288E+10 | 0.206176E+10 | 0.382495E+10 |
December | 0.213398E+10 | 0.100198E+10 | 0.113199E+10 | 0.140274E+10 | 0.502322E+10 |
Annual Sum or Average | 0.526592E+11 | 0.220287E+11 | 0.306305E+11 | 0.579544E+11 | 0.339355E+11 |
Minimum of Months | 0.213398E+10 | 0.870261E+09 | 0.113199E+10 | 0.131769E+10 | 0.544317E+09 |
Maximum of Months | 0.655098E+10 | 0.295384E+10 | 0.375213E+10 | 0.917425E+10 | 0.532691E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.806364E+10 | 0.528012E+10 | 0.278352E+10 | 0.784776E+10 | 0.781965E+10 |
February | 0.960641E+10 | 0.635866E+10 | 0.324775E+10 | 0.946654E+10 | 0.728162E+10 |
March | 0.959538E+10 | 0.532560E+10 | 0.426978E+10 | 0.100444E+11 | 0.605595E+10 |
April | 0.720549E+10 | 0.284927E+10 | 0.435622E+10 | 0.778726E+10 | 0.439505E+10 |
May | 0.652503E+10 | 0.136102E+10 | 0.516401E+10 | 0.751356E+10 | 0.288390E+10 |
June | 0.592601E+10 | 0.905852E+09 | 0.502016E+10 | 0.794549E+10 | 0.148988E+10 |
July | 0.641870E+10 | 0.111493E+10 | 0.530378E+10 | 0.956464E+10 | 0.816869E+09 |
August | 0.857147E+10 | 0.317930E+10 | 0.539217E+10 | 0.128601E+11 | 0.116659E+10 |
September | 0.900021E+10 | 0.465528E+10 | 0.434493E+10 | 0.119295E+11 | 0.223716E+10 |
October | 0.127405E+11 | 0.798922E+10 | 0.475129E+10 | 0.157000E+11 | 0.419677E+10 |
November | 0.854947E+10 | 0.513436E+10 | 0.341510E+10 | 0.897363E+10 | 0.580463E+10 |
December | 0.873978E+10 | 0.620466E+10 | 0.253512E+10 | 0.883278E+10 | 0.736682E+10 |
Annual Sum or Average | 0.100942E+12 | 0.503583E+11 | 0.505838E+11 | 0.118466E+12 | 0.515149E+11 |
Minimum of Months | 0.592601E+10 | 0.905852E+09 | 0.253512E+10 | 0.751356E+10 | 0.816869E+09 |
Maximum of Months | 0.127405E+11 | 0.798922E+10 | 0.539217E+10 | 0.157000E+11 | 0.781965E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214293E+10 | 0.877750E+09 | 0.126518E+10 | 0.129730E+10 | 0.558822E+10 |
February | 0.285424E+10 | 0.125359E+10 | 0.160065E+10 | 0.191799E+10 | 0.523652E+10 |
March | 0.466621E+10 | 0.215426E+10 | 0.251195E+10 | 0.411301E+10 | 0.408278E+10 |
April | 0.493543E+10 | 0.211175E+10 | 0.282369E+10 | 0.494509E+10 | 0.296257E+10 |
May | 0.594092E+10 | 0.225613E+10 | 0.368479E+10 | 0.680997E+10 | 0.196680E+10 |
June | 0.629242E+10 | 0.253791E+10 | 0.375450E+10 | 0.820577E+10 | 0.107322E+10 |
July | 0.608962E+10 | 0.229317E+10 | 0.379646E+10 | 0.853881E+10 | 0.640358E+09 |
August | 0.673678E+10 | 0.311869E+10 | 0.361809E+10 | 0.946737E+10 | 0.861057E+09 |
September | 0.462830E+10 | 0.202256E+10 | 0.260574E+10 | 0.578593E+10 | 0.152090E+10 |
October | 0.474157E+10 | 0.230571E+10 | 0.243586E+10 | 0.528375E+10 | 0.283986E+10 |
November | 0.215480E+10 | 0.622752E+09 | 0.153205E+10 | 0.140313E+10 | 0.402323E+10 |
December | 0.198054E+10 | 0.856984E+09 | 0.112355E+10 | 0.121288E+10 | 0.530967E+10 |
Annual Sum or Average | 0.531638E+11 | 0.224112E+11 | 0.307525E+11 | 0.589810E+11 | 0.361052E+11 |
Minimum of Months | 0.198054E+10 | 0.622752E+09 | 0.112355E+10 | 0.121288E+10 | 0.640358E+09 |
Maximum of Months | 0.673678E+10 | 0.311869E+10 | 0.379646E+10 | 0.946737E+10 | 0.558822E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.155873E+10 | 0.00 | 0.155873E+10 | 0.121033E+09 | 0.812784E+10 |
February | 0.192663E+10 | 0.00 | 0.192663E+10 | 0.212398E+09 | 0.759559E+10 |
March | 0.295801E+10 | 0.00 | 0.295801E+10 | 0.111940E+10 | 0.560720E+10 |
April | 0.343836E+10 | 9779760.41 | 0.342858E+10 | 0.223201E+10 | 0.387564E+10 |
May | 0.471366E+10 | 0.157062E+09 | 0.455660E+10 | 0.440073E+10 | 0.255269E+10 |
June | 0.483753E+10 | 0.259941E+09 | 0.457759E+10 | 0.593534E+10 | 0.137108E+10 |
July | 0.483084E+10 | 0.174699E+09 | 0.465614E+10 | 0.680443E+10 | 0.805915E+09 |
August | 0.427989E+10 | 50936762.66 | 0.422896E+10 | 0.597745E+10 | 0.106634E+10 |
September | 0.312225E+10 | 584671.33 | 0.312167E+10 | 0.334409E+10 | 0.202221E+10 |
October | 0.279216E+10 | 0.00 | 0.279216E+10 | 0.214907E+10 | 0.370472E+10 |
November | 0.189525E+10 | 0.00 | 0.189525E+10 | 0.604832E+09 | 0.543667E+10 |
December | 0.135963E+10 | 0.00 | 0.135963E+10 | 91106871.26 | 0.742985E+10 |
Annual Sum or Average | 0.377129E+11 | 0.653003E+09 | 0.370599E+11 | 0.329919E+11 | 0.495957E+11 |
Minimum of Months | 0.135963E+10 | 0.00 | 0.135963E+10 | 91106871.26 | 0.805915E+09 |
Maximum of Months | 0.483753E+10 | 0.259941E+09 | 0.465614E+10 | 0.680443E+10 | 0.812784E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217066E+10 | 0.870261E+09 | 0.130040E+10 | 0.136025E+10 | 0.506167E+10 |
February | 0.304047E+10 | 0.141838E+10 | 0.162209E+10 | 0.215656E+10 | 0.460592E+10 |
March | 0.429426E+10 | 0.182638E+10 | 0.246788E+10 | 0.373856E+10 | 0.367924E+10 |
April | 0.498717E+10 | 0.218454E+10 | 0.280264E+10 | 0.503255E+10 | 0.257546E+10 |
May | 0.625001E+10 | 0.249788E+10 | 0.375213E+10 | 0.716324E+10 | 0.177159E+10 |
June | 0.560558E+10 | 0.202918E+10 | 0.357640E+10 | 0.724740E+10 | 0.951880E+09 |
July | 0.581779E+10 | 0.209950E+10 | 0.371830E+10 | 0.815361E+10 | 0.559121E+09 |
August | 0.655098E+10 | 0.295384E+10 | 0.359714E+10 | 0.914781E+10 | 0.737131E+09 |
September | 0.472815E+10 | 0.212134E+10 | 0.260681E+10 | 0.584961E+10 | 0.135170E+10 |
October | 0.442930E+10 | 0.200751E+10 | 0.242179E+10 | 0.491081E+10 | 0.248237E+10 |
November | 0.265082E+10 | 0.101794E+10 | 0.163288E+10 | 0.216330E+10 | 0.347154E+10 |
December | 0.213398E+10 | 0.100198E+10 | 0.113199E+10 | 0.147613E+10 | 0.460083E+10 |
Annual Sum or Average | 0.526592E+11 | 0.220287E+11 | 0.306305E+11 | 0.583998E+11 | 0.318484E+11 |
Minimum of Months | 0.213398E+10 | 0.870261E+09 | 0.113199E+10 | 0.136025E+10 | 0.559121E+09 |
Maximum of Months | 0.655098E+10 | 0.295384E+10 | 0.375213E+10 | 0.914781E+10 | 0.506167E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.806364E+10 | 0.528012E+10 | 0.278352E+10 | 0.791617E+10 | 0.739346E+10 |
February | 0.960641E+10 | 0.635866E+10 | 0.324775E+10 | 0.957201E+10 | 0.682469E+10 |
March | 0.959538E+10 | 0.532560E+10 | 0.426978E+10 | 0.101246E+11 | 0.563771E+10 |
April | 0.720549E+10 | 0.284927E+10 | 0.435622E+10 | 0.785896E+10 | 0.410837E+10 |
May | 0.652503E+10 | 0.136102E+10 | 0.516401E+10 | 0.751716E+10 | 0.277890E+10 |
June | 0.592601E+10 | 0.905852E+09 | 0.502016E+10 | 0.789050E+10 | 0.148221E+10 |
July | 0.641870E+10 | 0.111493E+10 | 0.530378E+10 | 0.948377E+10 | 0.842095E+09 |
August | 0.857147E+10 | 0.317930E+10 | 0.539217E+10 | 0.127929E+11 | 0.117003E+10 |
September | 0.900021E+10 | 0.465528E+10 | 0.434493E+10 | 0.119142E+11 | 0.216618E+10 |
October | 0.127405E+11 | 0.798922E+10 | 0.475129E+10 | 0.157449E+11 | 0.395348E+10 |
November | 0.854947E+10 | 0.513436E+10 | 0.341510E+10 | 0.910464E+10 | 0.531170E+10 |
December | 0.873978E+10 | 0.620466E+10 | 0.253512E+10 | 0.896013E+10 | 0.677598E+10 |
Annual Sum or Average | 0.100942E+12 | 0.503583E+11 | 0.505838E+11 | 0.118880E+12 | 0.484448E+11 |
Minimum of Months | 0.592601E+10 | 0.905852E+09 | 0.253512E+10 | 0.751716E+10 | 0.842095E+09 |
Maximum of Months | 0.127405E+11 | 0.798922E+10 | 0.539217E+10 | 0.157449E+11 | 0.739346E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214293E+10 | 0.877750E+09 | 0.126518E+10 | 0.132148E+10 | 0.531771E+10 |
February | 0.285424E+10 | 0.125359E+10 | 0.160065E+10 | 0.194563E+10 | 0.496907E+10 |
March | 0.466621E+10 | 0.215426E+10 | 0.251195E+10 | 0.416005E+10 | 0.383339E+10 |
April | 0.493543E+10 | 0.211175E+10 | 0.282369E+10 | 0.498455E+10 | 0.278897E+10 |
May | 0.594092E+10 | 0.225613E+10 | 0.368479E+10 | 0.680294E+10 | 0.190362E+10 |
June | 0.629242E+10 | 0.253791E+10 | 0.375450E+10 | 0.816261E+10 | 0.106497E+10 |
July | 0.608962E+10 | 0.229317E+10 | 0.379646E+10 | 0.848462E+10 | 0.650129E+09 |
August | 0.673678E+10 | 0.311869E+10 | 0.361809E+10 | 0.942268E+10 | 0.860987E+09 |
September | 0.462830E+10 | 0.202256E+10 | 0.260574E+10 | 0.577462E+10 | 0.147593E+10 |
October | 0.474157E+10 | 0.230571E+10 | 0.243586E+10 | 0.532047E+10 | 0.267944E+10 |
November | 0.215480E+10 | 0.622752E+09 | 0.153205E+10 | 0.146469E+10 | 0.371618E+10 |
December | 0.198054E+10 | 0.856984E+09 | 0.112355E+10 | 0.125242E+10 | 0.494849E+10 |
Annual Sum or Average | 0.531638E+11 | 0.224112E+11 | 0.307525E+11 | 0.590967E+11 | 0.342089E+11 |
Minimum of Months | 0.198054E+10 | 0.622752E+09 | 0.112355E+10 | 0.125242E+10 | 0.650129E+09 |
Maximum of Months | 0.673678E+10 | 0.311869E+10 | 0.379646E+10 | 0.942268E+10 | 0.531771E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.63 | 3608.39 | 581.96 | 0.00 | 581.96 | 0.00 | 0.00 |
February | 45.54 | 3707.42 | 796.39 | 0.00 | 796.39 | 0.00 | 0.00 |
March | 318.41 | 2553.08 | 1104.40 | 0.00 | 1104.40 | 0.00 | 0.00 |
April | 754.77 | 1816.75 | 1326.53 | 3.77 | 1322.76 | 0.00 | 0.00 |
May | 1616.00 | 1041.11 | 1759.89 | 58.64 | 1701.25 | 0.00 | 0.00 |
June | 2288.29 | 569.87 | 1866.34 | 100.29 | 1766.05 | 0.00 | 0.00 |
July | 2525.38 | 336.90 | 1803.64 | 65.23 | 1738.41 | 0.00 | 0.00 |
August | 2203.58 | 443.97 | 1597.94 | 19.02 | 1578.92 | 0.00 | 0.00 |
September | 1259.18 | 888.17 | 1204.58 | 0.23 | 1204.35 | 0.00 | 0.00 |
October | 718.86 | 1646.64 | 1042.48 | 0.00 | 1042.48 | 0.00 | 0.00 |
November | 149.19 | 2672.62 | 731.20 | 0.00 | 731.20 | 0.00 | 0.00 |
December | 6.78 | 3515.75 | 507.63 | 0.00 | 507.63 | 0.00 | 0.00 |
Annual Sum or Average | 998.08 | 1889.73 | 1195.87 | 20.71 | 1175.17 | 0.00 | 0.00 |
Minimum of Months | 6.78 | 336.90 | 507.63 | 0.00 | 507.63 | 0.00 | 0.00 |
Maximum of Months | 2525.38 | 3707.42 | 1866.34 | 100.29 | 1766.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 462.53 | 2230.14 | 810.44 | 324.92 | 485.52 | 0.00 | 0.00 |
February | 833.06 | 2215.98 | 1256.81 | 586.30 | 670.51 | 0.00 | 0.00 |
March | 1358.55 | 1601.64 | 1603.30 | 681.90 | 921.41 | 0.00 | 0.00 |
April | 1913.36 | 1132.24 | 1924.07 | 842.80 | 1081.27 | 0.00 | 0.00 |
May | 2693.55 | 702.10 | 2333.50 | 932.61 | 1400.89 | 0.00 | 0.00 |
June | 2820.93 | 381.18 | 2162.66 | 782.87 | 1379.79 | 0.00 | 0.00 |
July | 3060.44 | 220.33 | 2172.12 | 783.87 | 1388.26 | 0.00 | 0.00 |
August | 3433.85 | 286.13 | 2445.86 | 1102.84 | 1343.02 | 0.00 | 0.00 |
September | 2264.68 | 569.83 | 1824.14 | 818.42 | 1005.72 | 0.00 | 0.00 |
October | 1812.45 | 1045.79 | 1653.72 | 749.52 | 904.20 | 0.00 | 0.00 |
November | 773.38 | 1632.08 | 1022.70 | 392.73 | 629.97 | 0.00 | 0.00 |
December | 501.07 | 2105.24 | 796.74 | 374.10 | 422.64 | 0.00 | 0.00 |
Annual Sum or Average | 1834.22 | 1171.07 | 1669.82 | 698.53 | 971.29 | 0.00 | 0.00 |
Minimum of Months | 462.53 | 220.33 | 796.74 | 324.92 | 422.64 | 0.00 | 0.00 |
Maximum of Months | 3433.85 | 2230.14 | 2445.86 | 1102.84 | 1400.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2920.54 | 3103.81 | 3010.63 | 1971.38 | 1039.25 | 0.00 | 0.00 |
February | 3925.01 | 3131.77 | 3970.92 | 2628.42 | 1342.49 | 0.00 | 0.00 |
March | 3763.84 | 2375.02 | 3582.52 | 1988.36 | 1594.16 | 0.00 | 0.00 |
April | 3004.44 | 1794.58 | 2779.91 | 1099.26 | 1680.65 | 0.00 | 0.00 |
May | 2822.05 | 1105.42 | 2436.18 | 508.15 | 1928.03 | 0.00 | 0.00 |
June | 3067.17 | 604.75 | 2286.28 | 349.48 | 1936.80 | 0.00 | 0.00 |
July | 3552.64 | 342.28 | 2396.48 | 416.27 | 1980.21 | 0.00 | 0.00 |
August | 4794.20 | 467.38 | 3200.23 | 1187.02 | 2013.21 | 0.00 | 0.00 |
September | 4625.12 | 896.48 | 3472.32 | 1796.02 | 1676.29 | 0.00 | 0.00 |
October | 5906.31 | 1601.69 | 4756.78 | 2982.84 | 1773.94 | 0.00 | 0.00 |
November | 3463.00 | 2367.64 | 3298.42 | 1980.86 | 1317.56 | 0.00 | 0.00 |
December | 3292.85 | 2935.78 | 3263.07 | 2316.56 | 946.51 | 0.00 | 0.00 |
Annual Sum or Average | 3762.51 | 1719.09 | 3200.86 | 1596.86 | 1604.01 | 0.00 | 0.00 |
Minimum of Months | 2822.05 | 342.28 | 2286.28 | 349.48 | 946.51 | 0.00 | 0.00 |
Maximum of Months | 5906.31 | 3131.77 | 4756.78 | 2982.84 | 2013.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 454.12 | 2409.25 | 800.08 | 327.72 | 472.37 | 0.00 | 0.00 |
February | 753.73 | 2493.65 | 1179.83 | 518.19 | 661.65 | 0.00 | 0.00 |
March | 1484.97 | 1792.60 | 1742.17 | 804.31 | 937.86 | 0.00 | 0.00 |
April | 1848.31 | 1362.12 | 1904.11 | 814.72 | 1089.39 | 0.00 | 0.00 |
May | 2531.99 | 791.59 | 2218.10 | 842.35 | 1375.75 | 0.00 | 0.00 |
June | 3151.13 | 466.54 | 2427.64 | 979.14 | 1448.50 | 0.00 | 0.00 |
July | 3156.56 | 290.32 | 2273.61 | 856.17 | 1417.44 | 0.00 | 0.00 |
August | 3496.09 | 387.29 | 2515.24 | 1164.39 | 1350.85 | 0.00 | 0.00 |
September | 2217.32 | 650.06 | 1785.62 | 780.31 | 1005.31 | 0.00 | 0.00 |
October | 1942.63 | 1191.79 | 1770.31 | 860.86 | 909.45 | 0.00 | 0.00 |
November | 492.29 | 1896.50 | 831.33 | 240.26 | 591.07 | 0.00 | 0.00 |
December | 408.85 | 2469.52 | 739.45 | 319.96 | 419.49 | 0.00 | 0.00 |
Annual Sum or Average | 1835.91 | 1343.51 | 1685.82 | 710.66 | 975.16 | 0.00 | 0.00 |
Minimum of Months | 408.85 | 290.32 | 739.45 | 240.26 | 419.49 | 0.00 | 0.00 |
Maximum of Months | 3496.09 | 2493.65 | 2515.24 | 1164.39 | 1448.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 36.52 | 3186.44 | 581.96 | 0.00 | 581.96 | 0.00 | 0.00 |
February | 73.41 | 3328.09 | 796.39 | 0.00 | 796.39 | 0.00 | 0.00 |
March | 385.80 | 2252.28 | 1104.39 | 0.00 | 1104.39 | 0.00 | 0.00 |
April | 823.63 | 1609.86 | 1326.53 | 3.77 | 1322.76 | 0.00 | 0.00 |
May | 1634.32 | 989.62 | 1759.88 | 58.64 | 1701.24 | 0.00 | 0.00 |
June | 2309.11 | 531.58 | 1866.33 | 100.29 | 1766.05 | 0.00 | 0.00 |
July | 2569.55 | 291.20 | 1803.63 | 65.23 | 1738.40 | 0.00 | 0.00 |
August | 2252.44 | 396.08 | 1597.93 | 19.02 | 1578.91 | 0.00 | 0.00 |
September | 1289.37 | 810.63 | 1204.57 | 0.23 | 1204.35 | 0.00 | 0.00 |
October | 764.65 | 1494.03 | 1042.47 | 0.00 | 1042.47 | 0.00 | 0.00 |
November | 195.41 | 2308.56 | 731.19 | 0.00 | 731.19 | 0.00 | 0.00 |
December | 21.59 | 3009.57 | 507.63 | 0.00 | 507.63 | 0.00 | 0.00 |
Annual Sum or Average | 1036.14 | 1674.52 | 1195.87 | 20.71 | 1175.16 | 0.00 | 0.00 |
Minimum of Months | 21.59 | 291.20 | 507.63 | 0.00 | 507.63 | 0.00 | 0.00 |
Maximum of Months | 2569.55 | 3328.09 | 1866.33 | 100.29 | 1766.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 491.97 | 1988.84 | 810.43 | 324.92 | 485.51 | 0.00 | 0.00 |
February | 860.76 | 2030.65 | 1256.81 | 586.30 | 670.51 | 0.00 | 0.00 |
March | 1366.65 | 1480.66 | 1603.29 | 681.89 | 921.40 | 0.00 | 0.00 |
April | 1915.05 | 1062.57 | 1924.06 | 842.80 | 1081.26 | 0.00 | 0.00 |
May | 2668.34 | 684.51 | 2333.49 | 932.60 | 1400.88 | 0.00 | 0.00 |
June | 2804.05 | 369.43 | 2162.65 | 782.86 | 1379.78 | 0.00 | 0.00 |
July | 3057.52 | 203.22 | 2172.12 | 783.86 | 1388.25 | 0.00 | 0.00 |
August | 3425.27 | 274.64 | 2445.85 | 1102.84 | 1343.02 | 0.00 | 0.00 |
September | 2253.63 | 539.83 | 1824.13 | 818.42 | 1005.72 | 0.00 | 0.00 |
October | 1809.21 | 992.29 | 1653.71 | 749.52 | 904.19 | 0.00 | 0.00 |
November | 795.43 | 1475.67 | 1022.69 | 392.72 | 629.97 | 0.00 | 0.00 |
December | 523.72 | 1875.45 | 796.74 | 374.10 | 422.64 | 0.00 | 0.00 |
Annual Sum or Average | 1837.72 | 1076.09 | 1669.81 | 698.53 | 971.29 | 0.00 | 0.00 |
Minimum of Months | 491.97 | 203.22 | 796.74 | 324.92 | 422.64 | 0.00 | 0.00 |
Maximum of Months | 3425.27 | 2030.65 | 2445.85 | 1102.84 | 1400.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2930.02 | 2919.52 | 3010.62 | 1971.37 | 1039.25 | 0.00 | 0.00 |
February | 3913.09 | 3009.93 | 3970.90 | 2628.41 | 1342.49 | 0.00 | 0.00 |
March | 3750.14 | 2261.03 | 3582.50 | 1988.35 | 1594.15 | 0.00 | 0.00 |
April | 3004.34 | 1695.62 | 2779.90 | 1099.25 | 1680.64 | 0.00 | 0.00 |
May | 2805.24 | 1076.73 | 2436.17 | 508.15 | 1928.02 | 0.00 | 0.00 |
June | 3065.39 | 574.80 | 2286.27 | 349.48 | 1936.79 | 0.00 | 0.00 |
July | 3571.03 | 304.98 | 2396.47 | 416.27 | 1980.20 | 0.00 | 0.00 |
August | 4801.43 | 435.55 | 3200.22 | 1187.01 | 2013.20 | 0.00 | 0.00 |
September | 4602.44 | 863.10 | 3472.30 | 1796.02 | 1676.29 | 0.00 | 0.00 |
October | 5861.72 | 1566.89 | 4756.76 | 2982.83 | 1773.93 | 0.00 | 0.00 |
November | 3462.05 | 2239.44 | 3298.41 | 1980.85 | 1317.56 | 0.00 | 0.00 |
December | 3297.78 | 2750.46 | 3263.06 | 2316.55 | 946.51 | 0.00 | 0.00 |
Annual Sum or Average | 3756.52 | 1633.53 | 3200.85 | 1596.85 | 1604.00 | 0.00 | 0.00 |
Minimum of Months | 2805.24 | 304.98 | 2286.27 | 349.48 | 946.51 | 0.00 | 0.00 |
Maximum of Months | 5861.72 | 3009.93 | 4756.76 | 2982.83 | 2013.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 484.36 | 2086.40 | 800.08 | 327.71 | 472.36 | 0.00 | 0.00 |
February | 792.82 | 2164.57 | 1179.83 | 518.19 | 661.64 | 0.00 | 0.00 |
March | 1535.62 | 1524.34 | 1742.16 | 804.31 | 937.85 | 0.00 | 0.00 |
April | 1907.83 | 1142.97 | 1904.10 | 814.72 | 1089.39 | 0.00 | 0.00 |
May | 2542.55 | 734.32 | 2218.09 | 842.34 | 1375.74 | 0.00 | 0.00 |
June | 3165.81 | 414.05 | 2427.63 | 979.13 | 1448.50 | 0.00 | 0.00 |
July | 3188.03 | 239.08 | 2273.60 | 856.17 | 1417.44 | 0.00 | 0.00 |
August | 3534.71 | 321.48 | 2515.23 | 1164.38 | 1350.84 | 0.00 | 0.00 |
September | 2232.23 | 586.77 | 1785.61 | 780.31 | 1005.30 | 0.00 | 0.00 |
October | 1972.73 | 1060.28 | 1770.30 | 860.85 | 909.45 | 0.00 | 0.00 |
November | 541.33 | 1552.17 | 831.33 | 240.26 | 591.07 | 0.00 | 0.00 |
December | 452.84 | 1982.40 | 739.45 | 319.96 | 419.49 | 0.00 | 0.00 |
Annual Sum or Average | 1870.27 | 1144.89 | 1685.81 | 710.66 | 975.16 | 0.00 | 0.00 |
Minimum of Months | 452.84 | 239.08 | 739.45 | 240.26 | 419.49 | 0.00 | 0.00 |
Maximum of Months | 3534.71 | 2164.57 | 2515.23 | 1164.38 | 1448.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 45.19 | 3034.59 | 581.96 | 0.00 | 581.96 | 0.00 | 0.00 |
February | 87.80 | 3139.71 | 796.39 | 0.00 | 796.39 | 0.00 | 0.00 |
March | 417.93 | 2093.49 | 1104.39 | 0.00 | 1104.39 | 0.00 | 0.00 |
April | 861.12 | 1495.23 | 1326.53 | 3.77 | 1322.76 | 0.00 | 0.00 |
May | 1643.04 | 953.06 | 1759.88 | 58.64 | 1701.24 | 0.00 | 0.00 |
June | 2289.87 | 528.97 | 1866.33 | 100.29 | 1766.05 | 0.00 | 0.00 |
July | 2540.48 | 300.89 | 1803.63 | 65.23 | 1738.40 | 0.00 | 0.00 |
August | 2231.72 | 398.12 | 1597.93 | 19.02 | 1578.91 | 0.00 | 0.00 |
September | 1290.16 | 780.17 | 1204.57 | 0.23 | 1204.35 | 0.00 | 0.00 |
October | 802.37 | 1383.18 | 1042.47 | 0.00 | 1042.47 | 0.00 | 0.00 |
November | 233.35 | 2097.48 | 731.19 | 0.00 | 731.19 | 0.00 | 0.00 |
December | 34.02 | 2773.99 | 507.63 | 0.00 | 507.63 | 0.00 | 0.00 |
Annual Sum or Average | 1046.17 | 1572.67 | 1195.87 | 20.71 | 1175.16 | 0.00 | 0.00 |
Minimum of Months | 34.02 | 300.89 | 507.63 | 0.00 | 507.63 | 0.00 | 0.00 |
Maximum of Months | 2540.48 | 3139.71 | 1866.33 | 100.29 | 1766.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 507.86 | 1889.81 | 810.43 | 324.92 | 485.51 | 0.00 | 0.00 |
February | 891.43 | 1903.90 | 1256.81 | 586.30 | 670.51 | 0.00 | 0.00 |
March | 1395.82 | 1373.67 | 1603.29 | 681.89 | 921.40 | 0.00 | 0.00 |
April | 1941.57 | 993.62 | 1924.06 | 842.80 | 1081.26 | 0.00 | 0.00 |
May | 2674.45 | 661.44 | 2333.49 | 932.60 | 1400.88 | 0.00 | 0.00 |
June | 2796.06 | 367.24 | 2162.65 | 782.86 | 1379.78 | 0.00 | 0.00 |
July | 3044.21 | 208.75 | 2172.12 | 783.86 | 1388.25 | 0.00 | 0.00 |
August | 3415.40 | 275.21 | 2445.85 | 1102.84 | 1343.02 | 0.00 | 0.00 |
September | 2256.80 | 521.49 | 1824.13 | 818.42 | 1005.72 | 0.00 | 0.00 |
October | 1833.49 | 926.81 | 1653.71 | 749.52 | 904.19 | 0.00 | 0.00 |
November | 834.61 | 1339.33 | 1022.69 | 392.72 | 629.97 | 0.00 | 0.00 |
December | 551.12 | 1717.75 | 796.74 | 374.10 | 422.64 | 0.00 | 0.00 |
Annual Sum or Average | 1851.85 | 1009.91 | 1669.81 | 698.53 | 971.29 | 0.00 | 0.00 |
Minimum of Months | 507.86 | 208.75 | 796.74 | 324.92 | 422.64 | 0.00 | 0.00 |
Maximum of Months | 3415.40 | 1903.90 | 2445.85 | 1102.84 | 1400.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2955.56 | 2760.40 | 3010.62 | 1971.37 | 1039.25 | 0.00 | 0.00 |
February | 3956.68 | 2821.05 | 3970.90 | 2628.41 | 1342.49 | 0.00 | 0.00 |
March | 3780.10 | 2104.88 | 3582.50 | 1988.35 | 1594.15 | 0.00 | 0.00 |
April | 3032.01 | 1585.02 | 2779.90 | 1099.25 | 1680.64 | 0.00 | 0.00 |
May | 2806.59 | 1037.52 | 2436.17 | 508.15 | 1928.02 | 0.00 | 0.00 |
June | 3044.18 | 571.84 | 2286.27 | 349.48 | 1936.79 | 0.00 | 0.00 |
July | 3540.83 | 314.40 | 2396.47 | 416.27 | 1980.20 | 0.00 | 0.00 |
August | 4776.31 | 436.84 | 3200.22 | 1187.01 | 2013.20 | 0.00 | 0.00 |
September | 4596.52 | 835.72 | 3472.30 | 1796.02 | 1676.29 | 0.00 | 0.00 |
October | 5878.47 | 1476.06 | 4756.76 | 2982.83 | 1773.93 | 0.00 | 0.00 |
November | 3512.59 | 2049.27 | 3298.41 | 1980.85 | 1317.56 | 0.00 | 0.00 |
December | 3345.33 | 2529.86 | 3263.06 | 2316.55 | 946.51 | 0.00 | 0.00 |
Annual Sum or Average | 3769.66 | 1536.17 | 3200.85 | 1596.85 | 1604.00 | 0.00 | 0.00 |
Minimum of Months | 2806.59 | 314.40 | 2286.27 | 349.48 | 946.51 | 0.00 | 0.00 |
Maximum of Months | 5878.47 | 2821.05 | 4756.76 | 2982.83 | 2013.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 493.38 | 1985.40 | 800.08 | 327.71 | 472.36 | 0.00 | 0.00 |
February | 804.24 | 2054.02 | 1179.83 | 518.19 | 661.64 | 0.00 | 0.00 |
March | 1553.19 | 1431.23 | 1742.16 | 804.31 | 937.85 | 0.00 | 0.00 |
April | 1923.05 | 1075.99 | 1904.10 | 814.72 | 1089.39 | 0.00 | 0.00 |
May | 2539.93 | 710.73 | 2218.09 | 842.34 | 1375.74 | 0.00 | 0.00 |
June | 3149.16 | 410.87 | 2427.63 | 979.13 | 1448.50 | 0.00 | 0.00 |
July | 3167.79 | 242.73 | 2273.60 | 856.17 | 1417.44 | 0.00 | 0.00 |
August | 3518.03 | 321.46 | 2515.23 | 1164.38 | 1350.84 | 0.00 | 0.00 |
September | 2227.86 | 569.42 | 1785.61 | 780.31 | 1005.30 | 0.00 | 0.00 |
October | 1986.44 | 1000.39 | 1770.30 | 860.85 | 909.45 | 0.00 | 0.00 |
November | 565.08 | 1433.71 | 831.33 | 240.26 | 591.07 | 0.00 | 0.00 |
December | 467.60 | 1847.56 | 739.45 | 319.96 | 419.49 | 0.00 | 0.00 |
Annual Sum or Average | 1873.95 | 1084.76 | 1685.81 | 710.66 | 975.16 | 0.00 | 0.00 |
Minimum of Months | 467.60 | 242.73 | 739.45 | 240.26 | 419.49 | 0.00 | 0.00 |
Maximum of Months | 3518.03 | 2054.02 | 2515.23 | 1164.38 | 1448.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 36507397.08 | 0.966471E+10 | 0.155873E+10 | 0.00 | 0.155873E+10 | 0.00 | 0.00 |
February | 0.110176E+09 | 0.896899E+10 | 0.192664E+10 | 0.00 | 0.192664E+10 | 0.00 | 0.00 |
March | 0.852835E+09 | 0.683818E+10 | 0.295802E+10 | 0.00 | 0.295802E+10 | 0.00 | 0.00 |
April | 0.195636E+10 | 0.470903E+10 | 0.343837E+10 | 9779795.14 | 0.342859E+10 | 0.00 | 0.00 |
May | 0.432830E+10 | 0.278850E+10 | 0.471368E+10 | 0.157063E+09 | 0.455662E+10 | 0.00 | 0.00 |
June | 0.593125E+10 | 0.147711E+10 | 0.483755E+10 | 0.259942E+09 | 0.457761E+10 | 0.00 | 0.00 |
July | 0.676398E+10 | 0.902360E+09 | 0.483086E+10 | 0.174700E+09 | 0.465616E+10 | 0.00 | 0.00 |
August | 0.590206E+10 | 0.118913E+10 | 0.427991E+10 | 50936943.54 | 0.422897E+10 | 0.00 | 0.00 |
September | 0.326380E+10 | 0.230215E+10 | 0.312227E+10 | 584673.41 | 0.312168E+10 | 0.00 | 0.00 |
October | 0.192539E+10 | 0.441037E+10 | 0.279217E+10 | 0.00 | 0.279217E+10 | 0.00 | 0.00 |
November | 0.386711E+09 | 0.692743E+10 | 0.189526E+10 | 0.00 | 0.189526E+10 | 0.00 | 0.00 |
December | 18164390.57 | 0.941658E+10 | 0.135963E+10 | 0.00 | 0.135963E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.314755E+11 | 0.595945E+11 | 0.377131E+11 | 0.653006E+09 | 0.370601E+11 | 0.00 | 0.00 |
Minimum of Months | 18164390.57 | 0.902360E+09 | 0.135963E+10 | 0.00 | 0.135963E+10 | 0.00 | 0.00 |
Maximum of Months | 0.676398E+10 | 0.966471E+10 | 0.483755E+10 | 0.259942E+09 | 0.465616E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123884E+10 | 0.597321E+10 | 0.217067E+10 | 0.870265E+09 | 0.130041E+10 | 0.00 | 0.00 |
February | 0.201533E+10 | 0.536090E+10 | 0.304048E+10 | 0.141839E+10 | 0.162209E+10 | 0.00 | 0.00 |
March | 0.363874E+10 | 0.428984E+10 | 0.429428E+10 | 0.182639E+10 | 0.246789E+10 | 0.00 | 0.00 |
April | 0.495944E+10 | 0.293476E+10 | 0.498720E+10 | 0.218455E+10 | 0.280265E+10 | 0.00 | 0.00 |
May | 0.721441E+10 | 0.188050E+10 | 0.625004E+10 | 0.249789E+10 | 0.375215E+10 | 0.00 | 0.00 |
June | 0.731185E+10 | 0.988020E+09 | 0.560561E+10 | 0.202919E+10 | 0.357642E+10 | 0.00 | 0.00 |
July | 0.819709E+10 | 0.590125E+09 | 0.581782E+10 | 0.209951E+10 | 0.371831E+10 | 0.00 | 0.00 |
August | 0.919721E+10 | 0.766379E+09 | 0.655100E+10 | 0.295385E+10 | 0.359716E+10 | 0.00 | 0.00 |
September | 0.587005E+10 | 0.147700E+10 | 0.472817E+10 | 0.212134E+10 | 0.260682E+10 | 0.00 | 0.00 |
October | 0.485446E+10 | 0.280105E+10 | 0.442932E+10 | 0.200752E+10 | 0.242180E+10 | 0.00 | 0.00 |
November | 0.200460E+10 | 0.423034E+10 | 0.265083E+10 | 0.101795E+10 | 0.163288E+10 | 0.00 | 0.00 |
December | 0.134208E+10 | 0.563867E+10 | 0.213398E+10 | 0.100199E+10 | 0.113200E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.578441E+11 | 0.369308E+11 | 0.526594E+11 | 0.220288E+11 | 0.306306E+11 | 0.00 | 0.00 |
Minimum of Months | 0.123884E+10 | 0.590125E+09 | 0.213398E+10 | 0.870265E+09 | 0.113200E+10 | 0.00 | 0.00 |
Maximum of Months | 0.919721E+10 | 0.597321E+10 | 0.655100E+10 | 0.295385E+10 | 0.375215E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.782237E+10 | 0.831325E+10 | 0.806367E+10 | 0.528014E+10 | 0.278353E+10 | 0.00 | 0.00 |
February | 0.949539E+10 | 0.757638E+10 | 0.960644E+10 | 0.635868E+10 | 0.324776E+10 | 0.00 | 0.00 |
March | 0.100811E+11 | 0.636124E+10 | 0.959541E+10 | 0.532562E+10 | 0.426979E+10 | 0.00 | 0.00 |
April | 0.778750E+10 | 0.465156E+10 | 0.720552E+10 | 0.284928E+10 | 0.435624E+10 | 0.00 | 0.00 |
May | 0.755858E+10 | 0.296075E+10 | 0.652505E+10 | 0.136102E+10 | 0.516403E+10 | 0.00 | 0.00 |
June | 0.795010E+10 | 0.156751E+10 | 0.592603E+10 | 0.905855E+09 | 0.502018E+10 | 0.00 | 0.00 |
July | 0.951539E+10 | 0.916755E+09 | 0.641873E+10 | 0.111493E+10 | 0.530380E+10 | 0.00 | 0.00 |
August | 0.128408E+11 | 0.125184E+10 | 0.857150E+10 | 0.317931E+10 | 0.539219E+10 | 0.00 | 0.00 |
September | 0.119883E+11 | 0.232367E+10 | 0.900024E+10 | 0.465529E+10 | 0.434495E+10 | 0.00 | 0.00 |
October | 0.158194E+11 | 0.428998E+10 | 0.127406E+11 | 0.798924E+10 | 0.475131E+10 | 0.00 | 0.00 |
November | 0.897610E+10 | 0.613693E+10 | 0.854950E+10 | 0.513438E+10 | 0.341512E+10 | 0.00 | 0.00 |
December | 0.881958E+10 | 0.786320E+10 | 0.873981E+10 | 0.620468E+10 | 0.253513E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.118655E+12 | 0.542131E+11 | 0.100942E+12 | 0.503584E+11 | 0.505840E+11 | 0.00 | 0.00 |
Minimum of Months | 0.755858E+10 | 0.916755E+09 | 0.592603E+10 | 0.905855E+09 | 0.253513E+10 | 0.00 | 0.00 |
Maximum of Months | 0.158194E+11 | 0.831325E+10 | 0.127406E+11 | 0.798924E+10 | 0.539219E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121631E+10 | 0.645294E+10 | 0.214294E+10 | 0.877754E+09 | 0.126518E+10 | 0.00 | 0.00 |
February | 0.182341E+10 | 0.603263E+10 | 0.285425E+10 | 0.125360E+10 | 0.160065E+10 | 0.00 | 0.00 |
March | 0.397735E+10 | 0.480129E+10 | 0.466623E+10 | 0.215427E+10 | 0.251196E+10 | 0.00 | 0.00 |
April | 0.479083E+10 | 0.353061E+10 | 0.493545E+10 | 0.211175E+10 | 0.282370E+10 | 0.00 | 0.00 |
May | 0.678168E+10 | 0.212020E+10 | 0.594095E+10 | 0.225614E+10 | 0.368481E+10 | 0.00 | 0.00 |
June | 0.816773E+10 | 0.120928E+10 | 0.629244E+10 | 0.253792E+10 | 0.375452E+10 | 0.00 | 0.00 |
July | 0.845452E+10 | 0.777587E+09 | 0.608965E+10 | 0.229317E+10 | 0.379647E+10 | 0.00 | 0.00 |
August | 0.936394E+10 | 0.103731E+10 | 0.673681E+10 | 0.311870E+10 | 0.361811E+10 | 0.00 | 0.00 |
September | 0.574730E+10 | 0.168496E+10 | 0.462832E+10 | 0.202257E+10 | 0.260576E+10 | 0.00 | 0.00 |
October | 0.520314E+10 | 0.319210E+10 | 0.474159E+10 | 0.230572E+10 | 0.243587E+10 | 0.00 | 0.00 |
November | 0.127602E+10 | 0.491572E+10 | 0.215481E+10 | 0.622754E+09 | 0.153205E+10 | 0.00 | 0.00 |
December | 0.109507E+10 | 0.661436E+10 | 0.198054E+10 | 0.856988E+09 | 0.112356E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.578973E+11 | 0.423690E+11 | 0.531640E+11 | 0.224113E+11 | 0.307526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.109507E+10 | 0.777587E+09 | 0.198054E+10 | 0.622754E+09 | 0.112356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.936394E+10 | 0.661436E+10 | 0.673681E+10 | 0.311870E+10 | 0.379647E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 97819743.30 | 0.853455E+10 | 0.155873E+10 | 0.00 | 0.155873E+10 | 0.00 | 0.00 |
February | 0.177590E+09 | 0.805131E+10 | 0.192663E+10 | 0.00 | 0.192663E+10 | 0.00 | 0.00 |
March | 0.103333E+10 | 0.603252E+10 | 0.295801E+10 | 0.00 | 0.295801E+10 | 0.00 | 0.00 |
April | 0.213486E+10 | 0.417275E+10 | 0.343836E+10 | 9779760.41 | 0.342858E+10 | 0.00 | 0.00 |
May | 0.437736E+10 | 0.265060E+10 | 0.471366E+10 | 0.157062E+09 | 0.455660E+10 | 0.00 | 0.00 |
June | 0.598521E+10 | 0.137785E+10 | 0.483753E+10 | 0.259941E+09 | 0.457759E+10 | 0.00 | 0.00 |
July | 0.688228E+10 | 0.779959E+09 | 0.483084E+10 | 0.174699E+09 | 0.465614E+10 | 0.00 | 0.00 |
August | 0.603294E+10 | 0.106086E+10 | 0.427989E+10 | 50936762.66 | 0.422896E+10 | 0.00 | 0.00 |
September | 0.334204E+10 | 0.210114E+10 | 0.312225E+10 | 584671.33 | 0.312167E+10 | 0.00 | 0.00 |
October | 0.204804E+10 | 0.400162E+10 | 0.279216E+10 | 0.00 | 0.279216E+10 | 0.00 | 0.00 |
November | 0.506499E+09 | 0.598379E+10 | 0.189525E+10 | 0.00 | 0.189525E+10 | 0.00 | 0.00 |
December | 57819336.13 | 0.806084E+10 | 0.135963E+10 | 0.00 | 0.135963E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.326758E+11 | 0.528078E+11 | 0.377129E+11 | 0.653003E+09 | 0.370599E+11 | 0.00 | 0.00 |
Minimum of Months | 57819336.13 | 0.779959E+09 | 0.135963E+10 | 0.00 | 0.135963E+10 | 0.00 | 0.00 |
Maximum of Months | 0.688228E+10 | 0.853455E+10 | 0.483753E+10 | 0.259941E+09 | 0.465614E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.131769E+10 | 0.532691E+10 | 0.217066E+10 | 0.870261E+09 | 0.130040E+10 | 0.00 | 0.00 |
February | 0.208235E+10 | 0.491255E+10 | 0.304047E+10 | 0.141838E+10 | 0.162209E+10 | 0.00 | 0.00 |
March | 0.366043E+10 | 0.396579E+10 | 0.429426E+10 | 0.182638E+10 | 0.246788E+10 | 0.00 | 0.00 |
April | 0.496382E+10 | 0.275419E+10 | 0.498717E+10 | 0.218454E+10 | 0.280264E+10 | 0.00 | 0.00 |
May | 0.714687E+10 | 0.183340E+10 | 0.625001E+10 | 0.249788E+10 | 0.375213E+10 | 0.00 | 0.00 |
June | 0.726811E+10 | 0.957564E+09 | 0.560558E+10 | 0.202918E+10 | 0.357640E+10 | 0.00 | 0.00 |
July | 0.818925E+10 | 0.544317E+09 | 0.581779E+10 | 0.209950E+10 | 0.371830E+10 | 0.00 | 0.00 |
August | 0.917425E+10 | 0.735601E+09 | 0.655098E+10 | 0.295384E+10 | 0.359714E+10 | 0.00 | 0.00 |
September | 0.584140E+10 | 0.139923E+10 | 0.472815E+10 | 0.212134E+10 | 0.260681E+10 | 0.00 | 0.00 |
October | 0.484578E+10 | 0.265774E+10 | 0.442930E+10 | 0.200751E+10 | 0.242179E+10 | 0.00 | 0.00 |
November | 0.206176E+10 | 0.382495E+10 | 0.265082E+10 | 0.101794E+10 | 0.163288E+10 | 0.00 | 0.00 |
December | 0.140274E+10 | 0.502322E+10 | 0.213398E+10 | 0.100198E+10 | 0.113199E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.579544E+11 | 0.339355E+11 | 0.526592E+11 | 0.220287E+11 | 0.306305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.131769E+10 | 0.544317E+09 | 0.213398E+10 | 0.870261E+09 | 0.113199E+10 | 0.00 | 0.00 |
Maximum of Months | 0.917425E+10 | 0.532691E+10 | 0.655098E+10 | 0.295384E+10 | 0.375213E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.784776E+10 | 0.781965E+10 | 0.806364E+10 | 0.528012E+10 | 0.278352E+10 | 0.00 | 0.00 |
February | 0.946654E+10 | 0.728162E+10 | 0.960641E+10 | 0.635866E+10 | 0.324775E+10 | 0.00 | 0.00 |
March | 0.100444E+11 | 0.605595E+10 | 0.959538E+10 | 0.532560E+10 | 0.426978E+10 | 0.00 | 0.00 |
April | 0.778726E+10 | 0.439505E+10 | 0.720549E+10 | 0.284927E+10 | 0.435622E+10 | 0.00 | 0.00 |
May | 0.751356E+10 | 0.288390E+10 | 0.652503E+10 | 0.136102E+10 | 0.516401E+10 | 0.00 | 0.00 |
June | 0.794549E+10 | 0.148988E+10 | 0.592601E+10 | 0.905852E+09 | 0.502016E+10 | 0.00 | 0.00 |
July | 0.956464E+10 | 0.816869E+09 | 0.641870E+10 | 0.111493E+10 | 0.530378E+10 | 0.00 | 0.00 |
August | 0.128601E+11 | 0.116659E+10 | 0.857147E+10 | 0.317930E+10 | 0.539217E+10 | 0.00 | 0.00 |
September | 0.119295E+11 | 0.223716E+10 | 0.900021E+10 | 0.465528E+10 | 0.434493E+10 | 0.00 | 0.00 |
October | 0.157000E+11 | 0.419677E+10 | 0.127405E+11 | 0.798922E+10 | 0.475129E+10 | 0.00 | 0.00 |
November | 0.897363E+10 | 0.580463E+10 | 0.854947E+10 | 0.513436E+10 | 0.341510E+10 | 0.00 | 0.00 |
December | 0.883278E+10 | 0.736682E+10 | 0.873978E+10 | 0.620466E+10 | 0.253512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.118466E+12 | 0.515149E+11 | 0.100942E+12 | 0.503583E+11 | 0.505838E+11 | 0.00 | 0.00 |
Minimum of Months | 0.751356E+10 | 0.816869E+09 | 0.592601E+10 | 0.905852E+09 | 0.253512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.157000E+11 | 0.781965E+10 | 0.127405E+11 | 0.798922E+10 | 0.539217E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.129730E+10 | 0.558822E+10 | 0.214293E+10 | 0.877750E+09 | 0.126518E+10 | 0.00 | 0.00 |
February | 0.191799E+10 | 0.523652E+10 | 0.285424E+10 | 0.125359E+10 | 0.160065E+10 | 0.00 | 0.00 |
March | 0.411301E+10 | 0.408278E+10 | 0.466621E+10 | 0.215426E+10 | 0.251195E+10 | 0.00 | 0.00 |
April | 0.494509E+10 | 0.296257E+10 | 0.493543E+10 | 0.211175E+10 | 0.282369E+10 | 0.00 | 0.00 |
May | 0.680997E+10 | 0.196680E+10 | 0.594092E+10 | 0.225613E+10 | 0.368479E+10 | 0.00 | 0.00 |
June | 0.820577E+10 | 0.107322E+10 | 0.629242E+10 | 0.253791E+10 | 0.375450E+10 | 0.00 | 0.00 |
July | 0.853881E+10 | 0.640358E+09 | 0.608962E+10 | 0.229317E+10 | 0.379646E+10 | 0.00 | 0.00 |
August | 0.946737E+10 | 0.861057E+09 | 0.673678E+10 | 0.311869E+10 | 0.361809E+10 | 0.00 | 0.00 |
September | 0.578593E+10 | 0.152090E+10 | 0.462830E+10 | 0.202256E+10 | 0.260574E+10 | 0.00 | 0.00 |
October | 0.528375E+10 | 0.283986E+10 | 0.474157E+10 | 0.230571E+10 | 0.243586E+10 | 0.00 | 0.00 |
November | 0.140313E+10 | 0.402323E+10 | 0.215480E+10 | 0.622752E+09 | 0.153205E+10 | 0.00 | 0.00 |
December | 0.121288E+10 | 0.530967E+10 | 0.198054E+10 | 0.856984E+09 | 0.112355E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.589810E+11 | 0.361052E+11 | 0.531638E+11 | 0.224112E+11 | 0.307525E+11 | 0.00 | 0.00 |
Minimum of Months | 0.121288E+10 | 0.640358E+09 | 0.198054E+10 | 0.622752E+09 | 0.112355E+10 | 0.00 | 0.00 |
Maximum of Months | 0.946737E+10 | 0.558822E+10 | 0.673678E+10 | 0.311869E+10 | 0.379646E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121033E+09 | 0.812784E+10 | 0.155873E+10 | 0.00 | 0.155873E+10 | 0.00 | 0.00 |
February | 0.212398E+09 | 0.759559E+10 | 0.192663E+10 | 0.00 | 0.192663E+10 | 0.00 | 0.00 |
March | 0.111940E+10 | 0.560720E+10 | 0.295801E+10 | 0.00 | 0.295801E+10 | 0.00 | 0.00 |
April | 0.223201E+10 | 0.387564E+10 | 0.343836E+10 | 9779760.41 | 0.342858E+10 | 0.00 | 0.00 |
May | 0.440073E+10 | 0.255269E+10 | 0.471366E+10 | 0.157062E+09 | 0.455660E+10 | 0.00 | 0.00 |
June | 0.593534E+10 | 0.137108E+10 | 0.483753E+10 | 0.259941E+09 | 0.457759E+10 | 0.00 | 0.00 |
July | 0.680443E+10 | 0.805915E+09 | 0.483084E+10 | 0.174699E+09 | 0.465614E+10 | 0.00 | 0.00 |
August | 0.597745E+10 | 0.106634E+10 | 0.427989E+10 | 50936762.66 | 0.422896E+10 | 0.00 | 0.00 |
September | 0.334409E+10 | 0.202221E+10 | 0.312225E+10 | 584671.33 | 0.312167E+10 | 0.00 | 0.00 |
October | 0.214907E+10 | 0.370472E+10 | 0.279216E+10 | 0.00 | 0.279216E+10 | 0.00 | 0.00 |
November | 0.604832E+09 | 0.543667E+10 | 0.189525E+10 | 0.00 | 0.189525E+10 | 0.00 | 0.00 |
December | 91106871.26 | 0.742985E+10 | 0.135963E+10 | 0.00 | 0.135963E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.329919E+11 | 0.495957E+11 | 0.377129E+11 | 0.653003E+09 | 0.370599E+11 | 0.00 | 0.00 |
Minimum of Months | 91106871.26 | 0.805915E+09 | 0.135963E+10 | 0.00 | 0.135963E+10 | 0.00 | 0.00 |
Maximum of Months | 0.680443E+10 | 0.812784E+10 | 0.483753E+10 | 0.259941E+09 | 0.465614E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136025E+10 | 0.506167E+10 | 0.217066E+10 | 0.870261E+09 | 0.130040E+10 | 0.00 | 0.00 |
February | 0.215656E+10 | 0.460592E+10 | 0.304047E+10 | 0.141838E+10 | 0.162209E+10 | 0.00 | 0.00 |
March | 0.373856E+10 | 0.367924E+10 | 0.429426E+10 | 0.182638E+10 | 0.246788E+10 | 0.00 | 0.00 |
April | 0.503255E+10 | 0.257546E+10 | 0.498717E+10 | 0.218454E+10 | 0.280264E+10 | 0.00 | 0.00 |
May | 0.716324E+10 | 0.177159E+10 | 0.625001E+10 | 0.249788E+10 | 0.375213E+10 | 0.00 | 0.00 |
June | 0.724740E+10 | 0.951880E+09 | 0.560558E+10 | 0.202918E+10 | 0.357640E+10 | 0.00 | 0.00 |
July | 0.815361E+10 | 0.559121E+09 | 0.581779E+10 | 0.209950E+10 | 0.371830E+10 | 0.00 | 0.00 |
August | 0.914781E+10 | 0.737131E+09 | 0.655098E+10 | 0.295384E+10 | 0.359714E+10 | 0.00 | 0.00 |
September | 0.584961E+10 | 0.135170E+10 | 0.472815E+10 | 0.212134E+10 | 0.260681E+10 | 0.00 | 0.00 |
October | 0.491081E+10 | 0.248237E+10 | 0.442930E+10 | 0.200751E+10 | 0.242179E+10 | 0.00 | 0.00 |
November | 0.216330E+10 | 0.347154E+10 | 0.265082E+10 | 0.101794E+10 | 0.163288E+10 | 0.00 | 0.00 |
December | 0.147613E+10 | 0.460083E+10 | 0.213398E+10 | 0.100198E+10 | 0.113199E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.583998E+11 | 0.318484E+11 | 0.526592E+11 | 0.220287E+11 | 0.306305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.136025E+10 | 0.559121E+09 | 0.213398E+10 | 0.870261E+09 | 0.113199E+10 | 0.00 | 0.00 |
Maximum of Months | 0.914781E+10 | 0.506167E+10 | 0.655098E+10 | 0.295384E+10 | 0.375213E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.791617E+10 | 0.739346E+10 | 0.806364E+10 | 0.528012E+10 | 0.278352E+10 | 0.00 | 0.00 |
February | 0.957201E+10 | 0.682469E+10 | 0.960641E+10 | 0.635866E+10 | 0.324775E+10 | 0.00 | 0.00 |
March | 0.101246E+11 | 0.563771E+10 | 0.959538E+10 | 0.532560E+10 | 0.426978E+10 | 0.00 | 0.00 |
April | 0.785896E+10 | 0.410837E+10 | 0.720549E+10 | 0.284927E+10 | 0.435622E+10 | 0.00 | 0.00 |
May | 0.751716E+10 | 0.277890E+10 | 0.652503E+10 | 0.136102E+10 | 0.516401E+10 | 0.00 | 0.00 |
June | 0.789050E+10 | 0.148221E+10 | 0.592601E+10 | 0.905852E+09 | 0.502016E+10 | 0.00 | 0.00 |
July | 0.948377E+10 | 0.842095E+09 | 0.641870E+10 | 0.111493E+10 | 0.530378E+10 | 0.00 | 0.00 |
August | 0.127929E+11 | 0.117003E+10 | 0.857147E+10 | 0.317930E+10 | 0.539217E+10 | 0.00 | 0.00 |
September | 0.119142E+11 | 0.216618E+10 | 0.900021E+10 | 0.465528E+10 | 0.434493E+10 | 0.00 | 0.00 |
October | 0.157449E+11 | 0.395348E+10 | 0.127405E+11 | 0.798922E+10 | 0.475129E+10 | 0.00 | 0.00 |
November | 0.910464E+10 | 0.531170E+10 | 0.854947E+10 | 0.513436E+10 | 0.341510E+10 | 0.00 | 0.00 |
December | 0.896013E+10 | 0.677598E+10 | 0.873978E+10 | 0.620466E+10 | 0.253512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.118880E+12 | 0.484448E+11 | 0.100942E+12 | 0.503583E+11 | 0.505838E+11 | 0.00 | 0.00 |
Minimum of Months | 0.751716E+10 | 0.842095E+09 | 0.592601E+10 | 0.905852E+09 | 0.253512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.157449E+11 | 0.739346E+10 | 0.127405E+11 | 0.798922E+10 | 0.539217E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.132148E+10 | 0.531771E+10 | 0.214293E+10 | 0.877750E+09 | 0.126518E+10 | 0.00 | 0.00 |
February | 0.194563E+10 | 0.496907E+10 | 0.285424E+10 | 0.125359E+10 | 0.160065E+10 | 0.00 | 0.00 |
March | 0.416005E+10 | 0.383339E+10 | 0.466621E+10 | 0.215426E+10 | 0.251195E+10 | 0.00 | 0.00 |
April | 0.498455E+10 | 0.278897E+10 | 0.493543E+10 | 0.211175E+10 | 0.282369E+10 | 0.00 | 0.00 |
May | 0.680294E+10 | 0.190362E+10 | 0.594092E+10 | 0.225613E+10 | 0.368479E+10 | 0.00 | 0.00 |
June | 0.816261E+10 | 0.106497E+10 | 0.629242E+10 | 0.253791E+10 | 0.375450E+10 | 0.00 | 0.00 |
July | 0.848462E+10 | 0.650129E+09 | 0.608962E+10 | 0.229317E+10 | 0.379646E+10 | 0.00 | 0.00 |
August | 0.942268E+10 | 0.860987E+09 | 0.673678E+10 | 0.311869E+10 | 0.361809E+10 | 0.00 | 0.00 |
September | 0.577462E+10 | 0.147593E+10 | 0.462830E+10 | 0.202256E+10 | 0.260574E+10 | 0.00 | 0.00 |
October | 0.532047E+10 | 0.267944E+10 | 0.474157E+10 | 0.230571E+10 | 0.243586E+10 | 0.00 | 0.00 |
November | 0.146469E+10 | 0.371618E+10 | 0.215480E+10 | 0.622752E+09 | 0.153205E+10 | 0.00 | 0.00 |
December | 0.125242E+10 | 0.494849E+10 | 0.198054E+10 | 0.856984E+09 | 0.112355E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.590967E+11 | 0.342089E+11 | 0.531638E+11 | 0.224112E+11 | 0.307525E+11 | 0.00 | 0.00 |
Minimum of Months | 0.125242E+10 | 0.650129E+09 | 0.198054E+10 | 0.622752E+09 | 0.112355E+10 | 0.00 | 0.00 |
Maximum of Months | 0.942268E+10 | 0.531771E+10 | 0.673678E+10 | 0.311869E+10 | 0.379646E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.402113E+11 | -0.397645E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446805404.6 | 60.05 | 0.00 | 0.00 |
February | 0.368922E+11 | -0.364896E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -402673538.8 | 60.05 | 0.00 | 0.00 |
March | 0.424161E+11 | -0.419703E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445844140.2 | 60.05 | 0.00 | 0.00 |
April | 0.365709E+11 | -0.361413E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429586471.8 | 60.05 | 0.00 | 0.00 |
May | 0.364291E+11 | -0.359852E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443944654.7 | 60.05 | 0.00 | 0.00 |
June | 0.335549E+11 | -0.331414E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -413537287.7 | 60.05 | 0.00 | 0.00 |
July | 0.302896E+11 | -0.298871E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -402493544.6 | 60.05 | 0.00 | 0.00 |
August | 0.326905E+11 | -0.322827E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -407734803.2 | 60.05 | 0.00 | 0.00 |
September | 0.306003E+11 | -0.301854E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -414885481.1 | 60.05 | 0.00 | 0.00 |
October | 0.335909E+11 | -0.331507E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440220805.9 | 60.05 | 0.00 | 0.00 |
November | 0.354449E+11 | -0.350175E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427469134.0 | 60.05 | 0.00 | 0.00 |
December | 0.376370E+11 | -0.371940E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442954101.0 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.426328E+12 | -0.421210E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.511815E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.302896E+11 | -0.419703E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -446805404.6 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.424161E+11 | -0.298871E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -402493544.6 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6516.47 | 36.94 | 196.67 | 243.33 | 3351.63 | 33.73 | 200.17 | 196.83 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9267.66 | 37.81 | 211.17 | 259.50 | 2106.72 | 28.00 | 209.83 | 235.50 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:00 | 3550.10 | 24.99 | 164.33 | 318.17 | 1572.98 | 22.61 | 217.50 | 285.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 2114.75 | 20.62 | 97.83 | 341.17 | 1229.54 | 22.02 | 226.83 | 299.50 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:00 | 1854.56 | 20.47 | 144.50 | 391.50 | 1028.75 | 21.84 | 278.17 | 348.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:40 | 1773.70 | 20.45 | 129.67 | 384.33 | 998.65 | 21.87 | 268.33 | 341.67 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:40 | 1951.98 | 20.72 | 163.17 | 391.50 | 1074.71 | 22.14 | 288.00 | 346.00 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2156.42 | 20.70 | 180.83 | 371.67 | 1230.92 | 22.09 | 298.00 | 340.67 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3832.95 | 22.85 | 156.33 | 325.00 | 1454.32 | 22.36 | 230.00 | 290.00 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 10144.17 | 36.46 | 284.33 | 306.50 | 2014.31 | 24.31 | 271.67 | 288.17 |
November | 240.83 | 0.49 | 0.48 | 01-NOV-06:00 | 6467.15 | 36.72 | 236.67 | 257.50 | 2232.23 | 29.50 | 233.00 | 235.00 |
December | 211.17 | 0.50 | 0.48 | 01-DEC-07:30 | 6094.53 | 37.97 | 207.83 | 245.00 | 5368.24 | 39.14 | 212.67 | 214.50 |
Annual Sum or Average | 3472.67 | 0.50 | 4242.72 | 26.71 | 2173.33 | 3835.17 | 1780.89 | 24.89 | 2934.17 | 3421.67 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1773.70 | 20.45 | 97.83 | 243.33 | 998.65 | 21.84 | 200.17 | 196.83 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 10144.17 | 37.97 | 284.33 | 391.50 | 5368.24 | 39.14 | 298.00 | 348.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 2071.63 | 24.91 | 90.67 | 224.67 | 1130.67 | 24.88 | 121.00 | 160.83 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:40 | 2855.67 | 25.87 | 96.00 | 247.17 | 1633.20 | 25.86 | 138.33 | 209.00 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:49 | 2969.68 | 23.64 | 94.00 | 314.67 | 1645.84 | 24.09 | 160.50 | 263.50 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3922.37 | 25.77 | 97.17 | 343.50 | 1567.53 | 24.60 | 171.67 | 305.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:40 | 3232.23 | 23.57 | 103.33 | 397.67 | 1738.76 | 24.15 | 225.33 | 357.33 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2905.62 | 23.59 | 95.00 | 389.50 | 1607.09 | 24.40 | 220.33 | 355.33 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:49 | 2993.76 | 23.98 | 116.33 | 397.83 | 1612.03 | 24.62 | 258.00 | 360.33 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 3974.05 | 25.41 | 143.17 | 374.83 | 1647.60 | 24.54 | 241.50 | 348.50 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3469.64 | 25.26 | 105.50 | 323.33 | 1502.20 | 24.40 | 179.67 | 287.83 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3074.77 | 25.37 | 142.17 | 295.50 | 1614.08 | 25.50 | 208.00 | 267.83 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 2097.39 | 24.97 | 117.33 | 246.33 | 1073.19 | 24.74 | 153.00 | 202.50 |
December | 211.17 | 0.52 | 0.48 | 01-DEC-07:30 | 1929.46 | 25.24 | 94.33 | 225.33 | 1106.63 | 25.18 | 113.00 | 161.17 |
Annual Sum or Average | 3472.67 | 0.50 | 3045.94 | 24.71 | 1295.00 | 3780.33 | 1525.14 | 24.69 | 2190.33 | 3279.50 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1929.46 | 23.57 | 90.67 | 224.67 | 1073.19 | 24.09 | 113.00 | 160.83 | |
Maximum of Months | 389.17 | 0.52 | 0.48 | 3974.05 | 25.87 | 143.17 | 397.83 | 1738.76 | 25.86 | 258.00 | 360.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-08:39 | 663.49 | 17.27 | 0.00 | 209.83 | 398.73 | 18.87 | 3.00 | 122.00 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:39 | 725.15 | 18.20 | 0.00 | 232.83 | 461.49 | 19.88 | 6.83 | 167.17 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:19 | 955.78 | 18.94 | 0.17 | 308.83 | 587.34 | 20.39 | 90.67 | 240.50 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1076.64 | 19.87 | 9.50 | 344.83 | 664.44 | 21.28 | 126.33 | 296.50 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1374.85 | 20.67 | 101.00 | 404.33 | 782.43 | 21.93 | 266.83 | 363.33 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:10 | 1548.41 | 23.69 | 165.83 | 402.67 | 853.92 | 23.41 | 294.50 | 370.67 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1528.31 | 22.47 | 154.83 | 408.67 | 845.59 | 22.27 | 289.33 | 368.33 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1264.17 | 20.26 | 66.00 | 378.50 | 753.77 | 21.65 | 271.83 | 350.50 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 988.01 | 19.48 | 0.83 | 321.50 | 615.01 | 20.95 | 117.17 | 271.17 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 899.09 | 19.17 | 0.00 | 290.83 | 569.51 | 20.79 | 136.17 | 246.67 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:19 | 738.13 | 17.96 | 0.00 | 235.33 | 435.17 | 19.47 | 15.33 | 157.83 |
December | 211.17 | 0.55 | 0.48 | 01-DEC-08:39 | 537.50 | 16.36 | 0.00 | 200.83 | 332.30 | 18.09 | 0.17 | 94.33 |
Annual Sum or Average | 3472.67 | 0.51 | 1090.56 | 19.89 | 498.17 | 3739.00 | 642.83 | 21.03 | 1618.17 | 3049.00 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 537.50 | 16.36 | 0.00 | 200.83 | 332.30 | 18.09 | 0.17 | 94.33 | |
Maximum of Months | 389.17 | 0.55 | 0.48 | 1548.41 | 23.69 | 165.83 | 408.67 | 853.92 | 23.41 | 294.50 | 370.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-08:39 | 2006.30 | 25.13 | 89.67 | 231.50 | 1119.28 | 25.10 | 118.83 | 164.67 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-08:39 | 2268.45 | 24.81 | 93.17 | 247.00 | 1193.03 | 24.83 | 130.67 | 207.83 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:30 | 3228.49 | 25.77 | 117.00 | 319.33 | 1805.64 | 26.00 | 182.83 | 275.17 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3698.33 | 24.31 | 83.00 | 342.33 | 1515.01 | 23.40 | 163.83 | 302.17 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:10 | 3470.34 | 21.99 | 75.00 | 396.33 | 1531.87 | 21.31 | 209.00 | 360.00 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:49 | 3365.67 | 19.39 | 19.67 | 393.67 | 1809.63 | 21.52 | 209.50 | 354.83 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-05:49 | 3172.12 | 21.51 | 64.17 | 399.17 | 1687.44 | 21.60 | 236.00 | 359.00 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 4047.55 | 22.91 | 106.33 | 374.33 | 1753.72 | 21.68 | 220.83 | 347.50 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:30 | 3285.42 | 24.88 | 107.00 | 324.33 | 1706.96 | 24.97 | 179.33 | 287.00 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 3536.98 | 27.18 | 160.33 | 305.00 | 1496.52 | 25.80 | 223.33 | 278.17 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-07:30 | 1738.14 | 24.69 | 110.50 | 247.17 | 923.05 | 24.77 | 155.83 | 206.00 |
December | 211.17 | 0.52 | 0.48 | 01-DEC-08:39 | 1628.67 | 24.74 | 90.33 | 224.00 | 894.55 | 24.52 | 117.00 | 165.83 |
Annual Sum or Average | 3472.67 | 0.50 | 3090.74 | 23.66 | 1116.17 | 3804.17 | 1507.17 | 23.50 | 2147.00 | 3308.17 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1628.67 | 19.39 | 19.67 | 224.00 | 894.55 | 21.31 | 117.00 | 164.67 | |
Maximum of Months | 389.17 | 0.52 | 0.48 | 4047.55 | 27.18 | 160.33 | 399.17 | 1809.63 | 26.00 | 236.00 | 360.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6565.12 | 36.52 | 196.17 | 243.50 | 3470.15 | 31.82 | 144.00 | 199.50 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9332.01 | 37.32 | 210.00 | 259.83 | 2239.50 | 24.09 | 80.00 | 237.83 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:00 | 3653.81 | 20.19 | 90.67 | 320.50 | 1688.13 | 18.23 | 22.67 | 289.33 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 2161.66 | 14.43 | 0.00 | 341.17 | 1318.38 | 17.96 | 1.17 | 304.00 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:00 | 1883.11 | 14.50 | 0.00 | 391.50 | 1097.06 | 17.89 | 0.00 | 353.67 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:40 | 1801.20 | 14.49 | 0.00 | 384.67 | 1064.62 | 17.95 | 0.00 | 344.83 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:40 | 1978.94 | 14.66 | 0.00 | 391.83 | 1144.83 | 18.11 | 0.00 | 350.83 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2197.90 | 14.74 | 0.00 | 371.83 | 1316.84 | 18.19 | 3.83 | 343.67 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3893.23 | 17.10 | 29.50 | 326.00 | 1561.48 | 18.04 | 4.67 | 293.33 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 10219.96 | 35.69 | 283.50 | 307.67 | 2239.27 | 20.15 | 27.00 | 291.83 |
November | 240.83 | 0.49 | 0.48 | 01-NOV-06:49 | 6501.37 | 36.31 | 236.17 | 258.17 | 2778.68 | 29.03 | 144.17 | 238.67 |
December | 211.17 | 0.50 | 0.48 | 01-DEC-07:30 | 6153.49 | 37.56 | 207.67 | 245.50 | 5485.28 | 38.83 | 207.83 | 218.33 |
Annual Sum or Average | 3472.67 | 0.50 | 4292.17 | 22.66 | 1253.67 | 3842.17 | 1916.37 | 21.43 | 635.33 | 3465.83 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1801.20 | 14.43 | 0.00 | 243.50 | 1064.62 | 17.89 | 0.00 | 199.50 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 10219.96 | 37.56 | 283.50 | 391.83 | 5485.28 | 38.83 | 207.83 | 353.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 2103.61 | 22.61 | 72.83 | 226.17 | 1175.88 | 23.15 | 68.33 | 164.67 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:40 | 2898.17 | 23.51 | 80.67 | 248.83 | 1690.74 | 24.07 | 60.00 | 213.33 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:49 | 3031.30 | 20.75 | 71.50 | 315.17 | 1716.12 | 21.86 | 51.67 | 271.50 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3982.58 | 23.07 | 92.67 | 344.67 | 1646.72 | 22.13 | 50.17 | 308.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:40 | 3272.76 | 20.46 | 99.50 | 398.00 | 1815.56 | 21.69 | 72.83 | 361.00 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2949.83 | 20.40 | 88.50 | 390.33 | 1681.26 | 21.97 | 68.83 | 358.17 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:49 | 3030.83 | 20.33 | 89.67 | 399.00 | 1688.55 | 22.18 | 70.00 | 363.83 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 4022.65 | 22.54 | 128.17 | 375.17 | 1727.62 | 22.08 | 70.50 | 351.50 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3509.49 | 21.50 | 82.67 | 324.17 | 1577.27 | 21.98 | 48.50 | 292.00 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3120.89 | 22.48 | 91.17 | 296.33 | 1683.68 | 23.50 | 74.00 | 272.50 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 2116.32 | 21.45 | 73.33 | 247.17 | 1123.19 | 22.81 | 75.00 | 206.33 |
December | 211.17 | 0.52 | 0.48 | 01-DEC-07:30 | 1958.74 | 23.02 | 82.83 | 226.00 | 1146.82 | 23.59 | 79.00 | 166.83 |
Annual Sum or Average | 3472.67 | 0.50 | 3088.42 | 21.69 | 1053.50 | 3791.00 | 1593.79 | 22.47 | 788.83 | 3330.50 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1958.74 | 20.33 | 71.50 | 226.00 | 1123.19 | 21.69 | 48.50 | 164.67 | |
Maximum of Months | 389.17 | 0.52 | 0.48 | 4022.65 | 23.51 | 128.17 | 399.00 | 1815.56 | 24.07 | 79.00 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-08:30 | 671.65 | 11.60 | 0.00 | 210.17 | 423.72 | 15.13 | 0.00 | 132.00 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-08:39 | 736.57 | 12.67 | 0.00 | 233.67 | 491.33 | 16.37 | 0.00 | 177.17 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:19 | 972.29 | 13.62 | 0.00 | 309.00 | 625.65 | 17.07 | 0.00 | 250.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1098.08 | 14.57 | 0.00 | 345.17 | 708.64 | 18.08 | 0.00 | 303.00 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:40 | 1398.39 | 15.04 | 3.17 | 404.50 | 833.96 | 18.46 | 10.83 | 369.00 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-04:00 | 1575.90 | 19.17 | 73.00 | 402.67 | 918.42 | 21.16 | 51.83 | 375.67 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1554.29 | 17.45 | 41.33 | 408.83 | 908.77 | 20.65 | 46.17 | 376.17 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1287.99 | 14.98 | 0.00 | 378.50 | 803.56 | 18.44 | 3.50 | 354.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 1006.59 | 14.22 | 0.00 | 321.67 | 655.54 | 17.73 | 0.00 | 277.00 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 913.08 | 13.93 | 0.00 | 291.17 | 606.32 | 17.48 | 0.00 | 252.00 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:19 | 747.59 | 12.16 | 0.00 | 235.67 | 462.39 | 15.68 | 0.00 | 166.50 |
December | 211.17 | 0.55 | 0.48 | 01-DEC-08:30 | 543.95 | 10.49 | 0.00 | 201.33 | 353.15 | 14.19 | 0.00 | 103.33 |
Annual Sum or Average | 3472.67 | 0.50 | 1109.18 | 14.57 | 117.50 | 3742.33 | 686.49 | 17.90 | 112.33 | 3136.83 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 543.95 | 10.49 | 0.00 | 201.33 | 353.15 | 14.19 | 0.00 | 103.33 | |
Maximum of Months | 389.17 | 0.55 | 0.48 | 1575.90 | 19.17 | 73.00 | 408.83 | 918.42 | 21.16 | 51.83 | 376.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-08:30 | 2037.12 | 22.87 | 73.33 | 232.33 | 1162.98 | 23.43 | 65.83 | 170.00 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-08:39 | 2279.05 | 20.90 | 57.00 | 247.83 | 1250.27 | 22.84 | 45.17 | 213.00 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:19 | 3292.31 | 23.14 | 95.83 | 320.83 | 1878.74 | 24.00 | 74.83 | 283.50 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3756.97 | 21.31 | 76.83 | 343.17 | 1593.57 | 20.73 | 37.00 | 306.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:10 | 3510.82 | 18.43 | 69.17 | 397.33 | 1606.29 | 18.04 | 0.00 | 364.33 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:49 | 3402.51 | 14.80 | 1.83 | 394.17 | 1893.52 | 18.18 | 0.00 | 360.00 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-05:49 | 3209.65 | 17.66 | 49.00 | 399.83 | 1766.88 | 18.33 | 0.00 | 362.83 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 4102.31 | 19.58 | 86.33 | 374.50 | 1835.50 | 18.51 | 8.50 | 351.67 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:30 | 3333.55 | 21.79 | 85.33 | 324.83 | 1780.67 | 22.70 | 61.67 | 291.17 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 3574.67 | 23.93 | 111.83 | 305.17 | 1568.63 | 23.75 | 70.67 | 282.00 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-07:19 | 1764.67 | 22.04 | 79.67 | 248.33 | 965.30 | 22.95 | 70.67 | 212.17 |
December | 211.17 | 0.52 | 0.48 | 01-DEC-08:30 | 1622.90 | 20.94 | 68.50 | 224.33 | 933.34 | 22.88 | 67.00 | 171.50 |
Annual Sum or Average | 3472.67 | 0.50 | 3129.55 | 20.27 | 854.67 | 3812.67 | 1576.61 | 20.94 | 501.33 | 3369.00 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1622.90 | 14.80 | 1.83 | 224.33 | 933.34 | 18.04 | 0.00 | 170.00 | |
Maximum of Months | 389.17 | 0.52 | 0.48 | 4102.31 | 23.93 | 111.83 | 399.83 | 1893.52 | 24.00 | 74.83 | 364.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6566.78 | 36.52 | 196.17 | 243.50 | 3472.65 | 31.81 | 144.00 | 199.67 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9334.04 | 37.31 | 210.00 | 260.00 | 2242.05 | 24.08 | 80.00 | 238.00 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:00 | 3657.09 | 20.16 | 90.67 | 320.50 | 1690.50 | 18.21 | 22.00 | 289.33 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 2164.50 | 14.40 | 0.00 | 341.17 | 1320.20 | 17.95 | 1.17 | 304.17 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:00 | 1885.82 | 14.47 | 0.00 | 391.67 | 1098.74 | 17.88 | 0.00 | 354.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:40 | 1803.67 | 14.46 | 0.00 | 384.67 | 1066.18 | 17.94 | 0.00 | 344.83 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:40 | 1981.83 | 14.63 | 0.00 | 391.83 | 1146.60 | 18.10 | 0.00 | 350.83 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:00 | 2200.87 | 14.71 | 0.00 | 371.83 | 1318.72 | 18.17 | 3.67 | 343.67 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3896.46 | 17.07 | 29.50 | 326.00 | 1563.63 | 18.03 | 4.67 | 293.50 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 10223.06 | 35.68 | 283.50 | 307.67 | 2242.25 | 20.13 | 26.83 | 291.83 |
November | 240.83 | 0.49 | 0.48 | 01-NOV-06:49 | 6503.38 | 36.30 | 236.17 | 258.33 | 2781.45 | 29.02 | 144.17 | 238.67 |
December | 211.17 | 0.50 | 0.48 | 01-DEC-07:30 | 6154.29 | 37.55 | 207.67 | 245.67 | 5487.32 | 38.82 | 207.83 | 218.33 |
Annual Sum or Average | 3472.67 | 0.50 | 4294.76 | 22.64 | 1253.67 | 3842.83 | 1918.49 | 21.42 | 634.33 | 3467.00 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1803.67 | 14.40 | 0.00 | 243.50 | 1066.18 | 17.88 | 0.00 | 199.67 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 10223.06 | 37.55 | 283.50 | 391.83 | 5487.32 | 38.82 | 207.83 | 354.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 2104.60 | 22.59 | 72.83 | 226.17 | 1177.02 | 23.13 | 68.00 | 164.83 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:40 | 2899.11 | 23.49 | 80.67 | 249.00 | 1691.96 | 24.06 | 59.83 | 213.50 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:49 | 3032.66 | 20.72 | 71.50 | 315.17 | 1717.70 | 21.85 | 51.67 | 271.83 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3984.28 | 23.05 | 92.67 | 344.67 | 1648.33 | 22.11 | 50.17 | 308.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:40 | 3275.05 | 20.44 | 99.50 | 398.00 | 1817.46 | 21.68 | 72.83 | 361.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2951.96 | 20.37 | 88.50 | 390.33 | 1683.00 | 21.96 | 68.83 | 358.17 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:49 | 3033.33 | 20.30 | 89.67 | 399.17 | 1690.49 | 22.16 | 70.00 | 363.83 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 4024.76 | 22.51 | 128.17 | 375.17 | 1729.47 | 22.07 | 70.50 | 351.50 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3511.07 | 21.47 | 82.67 | 324.17 | 1578.83 | 21.97 | 48.50 | 292.00 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3122.13 | 22.46 | 91.17 | 296.50 | 1685.27 | 23.49 | 73.50 | 272.83 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 2117.60 | 21.42 | 73.33 | 247.33 | 1124.52 | 22.79 | 74.00 | 206.50 |
December | 211.17 | 0.52 | 0.48 | 01-DEC-07:30 | 1959.40 | 23.00 | 82.83 | 226.00 | 1147.69 | 23.57 | 78.67 | 166.83 |
Annual Sum or Average | 3472.67 | 0.50 | 3090.10 | 21.67 | 1053.50 | 3791.67 | 1595.39 | 22.46 | 786.50 | 3331.83 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1959.40 | 20.30 | 71.50 | 226.00 | 1124.52 | 21.68 | 48.50 | 164.83 | |
Maximum of Months | 389.17 | 0.52 | 0.48 | 4024.76 | 23.49 | 128.17 | 399.17 | 1817.46 | 24.06 | 78.67 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-08:30 | 672.22 | 11.57 | 0.00 | 210.17 | 424.27 | 15.11 | 0.00 | 132.17 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-08:39 | 737.01 | 12.64 | 0.00 | 233.83 | 491.88 | 16.35 | 0.00 | 177.50 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:19 | 973.10 | 13.59 | 0.00 | 309.00 | 626.42 | 17.05 | 0.00 | 251.00 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1098.97 | 14.54 | 0.00 | 345.17 | 709.49 | 18.06 | 0.00 | 303.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:40 | 1399.89 | 15.01 | 3.17 | 404.50 | 835.14 | 18.44 | 10.33 | 369.17 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-04:00 | 1577.44 | 19.14 | 73.00 | 402.83 | 919.65 | 21.15 | 51.83 | 375.83 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1555.91 | 17.42 | 41.33 | 409.00 | 910.04 | 20.64 | 46.17 | 376.50 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1289.09 | 14.95 | 0.00 | 378.50 | 804.57 | 18.42 | 3.50 | 354.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 1007.37 | 14.19 | 0.00 | 321.83 | 656.32 | 17.71 | 0.00 | 277.00 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 913.63 | 13.90 | 0.00 | 291.33 | 607.01 | 17.47 | 0.00 | 252.00 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:19 | 748.31 | 12.13 | 0.00 | 235.83 | 463.03 | 15.66 | 0.00 | 166.67 |
December | 211.17 | 0.55 | 0.48 | 01-DEC-08:30 | 544.32 | 10.46 | 0.00 | 201.50 | 353.58 | 14.17 | 0.00 | 103.33 |
Annual Sum or Average | 3472.67 | 0.50 | 1110.16 | 14.54 | 117.50 | 3743.50 | 687.37 | 17.89 | 111.83 | 3138.83 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 544.32 | 10.46 | 0.00 | 201.50 | 353.58 | 14.17 | 0.00 | 103.33 | |
Maximum of Months | 389.17 | 0.55 | 0.48 | 1577.44 | 19.14 | 73.00 | 409.00 | 919.65 | 21.15 | 51.83 | 376.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-08:30 | 2038.06 | 22.84 | 73.33 | 232.50 | 1164.06 | 23.42 | 65.50 | 170.17 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-08:39 | 2280.00 | 20.87 | 57.00 | 247.83 | 1251.45 | 22.83 | 45.17 | 213.00 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:19 | 3293.72 | 23.12 | 95.83 | 320.83 | 1880.37 | 23.99 | 74.83 | 283.83 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3728.70 | 21.29 | 76.83 | 343.33 | 1595.22 | 20.72 | 37.00 | 306.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:10 | 3513.10 | 18.40 | 69.17 | 397.33 | 1608.14 | 18.02 | 0.00 | 364.33 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:49 | 3405.00 | 14.76 | 1.83 | 394.17 | 1895.56 | 18.16 | 0.00 | 360.00 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-05:49 | 3212.24 | 17.63 | 49.00 | 400.17 | 1768.90 | 18.32 | 0.00 | 362.83 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 4104.43 | 19.55 | 86.33 | 374.50 | 1837.36 | 18.50 | 8.50 | 351.83 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:30 | 3335.17 | 21.76 | 85.17 | 325.00 | 1782.28 | 22.69 | 61.50 | 291.33 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 3576.05 | 23.91 | 111.83 | 305.17 | 1570.20 | 23.74 | 70.33 | 282.00 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-07:19 | 1765.94 | 22.02 | 79.67 | 248.33 | 966.51 | 22.94 | 70.33 | 212.33 |
December | 211.17 | 0.52 | 0.48 | 01-DEC-08:30 | 1623.60 | 20.91 | 68.50 | 224.33 | 934.19 | 22.87 | 66.83 | 171.50 |
Annual Sum or Average | 3472.67 | 0.50 | 3129.04 | 20.24 | 854.50 | 3813.50 | 1578.23 | 20.93 | 500.00 | 3370.00 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1623.60 | 14.76 | 1.83 | 224.33 | 934.19 | 18.02 | 0.00 | 170.17 | |
Maximum of Months | 389.17 | 0.52 | 0.48 | 4104.43 | 23.91 | 111.83 | 400.17 | 1895.56 | 23.99 | 74.83 | 364.33 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.146781E+09 | 15045.46 | 19-JAN-08:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158652E+09 | 14324.68 | 22-FEB-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158544E+09 | 13107.45 | 08-MAR-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40579909.62 | 4025.41 | 14-APR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14084186.84 | 10473.46 | 30-MAY-14:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74707448.57 | 18510.32 | 01-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 48469902.44 | 13299.90 | 11-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85553157.38 | 21339.25 | 30-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12427642.81 | 7717.90 | 01-SEP-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9645391.41 | 1635.16 | 07-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 85673647.17 | 10190.14 | 20-NOV-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180161E+09 | 13182.61 | 21-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9645391.41 | 1635.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.180161E+09 | 21339.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.459253E+09 | 14023.67 | 31-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323869E+09 | 14052.37 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 857000.52 | 586.34 | 24-NOV-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 254398.23 | 196.08 | 15-DEC-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.784234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.459253E+09 | 14052.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.291570E+09 | 13083.38 | 31-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192130E+09 | 13111.84 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10078084.91 | 2914.83 | 17-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8091431.16 | 3391.84 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19894738.38 | 4540.85 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.521764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.291570E+09 | 13111.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.593762E+09 | 18456.21 | 26-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.357503E+09 | 18516.04 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28252840.79 | 12077.44 | 17-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26213802.49 | 18523.67 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 66665986.94 | 18503.01 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.593762E+09 | 18523.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 43117609.30 | 11537.16 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14830180.52 | 11505.01 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57947789.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43117609.30 | 11537.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.556145E+10 | 283390.64 | 31-JAN-09:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.396014E+10 | 364442.71 | 03-FEB-09:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.283590E+10 | 185453.54 | 22-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199685E+10 | 212170.80 | 13-APR-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.511878E+09 | 172552.79 | 30-MAY-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.892032E+09 | 162188.12 | 01-JUN-14:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.352276E+09 | 106393.57 | 11-JUL-15:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.963812E+09 | 171233.24 | 24-AUG-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.209085E+09 | 78086.72 | 01-SEP-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144914E+09 | 52934.65 | 07-OCT-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184396E+10 | 176545.48 | 24-NOV-21:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207990E+10 | 154210.64 | 27-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.144914E+09 | 52934.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.556145E+10 | 364442.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.183234E+11 | 489930.46 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.947360E+09 | 485785.37 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.183234E+11 | 489930.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.507098E+11 | 130718.54 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.383437E+11 | 130448.78 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.948523E+10 | 137281.39 | 16-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154901E+10 | 130346.79 | 21-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149434E+09 | 56269.71 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104586E+11 | 142166.05 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267177E+11 | 130422.66 | 12-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137413E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.507098E+11 | 142166.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.255548E+11 | 171460.45 | 03-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161605E+11 | 171197.77 | 13-FEB-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.387945E+10 | 170929.69 | 01-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.691909E+09 | 168520.41 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33262610.14 | 9270.58 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.454202E+10 | 171044.11 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124994E+11 | 171083.68 | 11-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.633613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255548E+11 | 171460.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.281300E+11 | 199216.75 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165058E+11 | 198098.34 | 06-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.435278E+10 | 196888.43 | 01-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104050E+10 | 184210.91 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.403934E+10 | 197555.85 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131220E+11 | 197959.03 | 11-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.671904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.281300E+11 | 199216.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225009E+11 | 172039.05 | 03-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149248E+11 | 171496.54 | 27-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242709E+10 | 171187.63 | 17-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.311147E+09 | 79131.69 | 22-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1663980.68 | 940.77 | 28-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367980E+10 | 171202.39 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.952356E+10 | 171317.45 | 30-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225009E+11 | 172039.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142626E+10 | 15995.64 | 02-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.961823E+09 | 12683.61 | 06-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96940686.81 | 3844.98 | 28-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31906795.50 | 2973.83 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27553561.38 | 19136.84 | 30-MAY-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 70920748.98 | 13225.67 | 01-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 52093133.41 | 8408.60 | 11-JUL-13:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100502E+09 | 17772.25 | 24-AUG-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11759157.93 | 8137.35 | 01-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12313935.10 | 3806.30 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 66749530.99 | 4455.10 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 93001808.75 | 5502.99 | 31-DEC-23:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.295182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11759157.93 | 2973.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142626E+10 | 19136.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.893505E+10 | 75163.20 | 23-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.649209E+10 | 74924.04 | 21-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129764E+10 | 74841.82 | 20-MAR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217027E+09 | 73882.57 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7694609.55 | 2614.06 | 30-OCT-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242722E+10 | 75205.55 | 27-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.471650E+10 | 74947.35 | 26-DEC-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.893505E+10 | 75205.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.872550E+10 | 15016.08 | 23-JAN-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.763257E+10 | 14945.43 | 16-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.297275E+10 | 14942.32 | 20-MAR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.883299E+09 | 14941.38 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21820551.02 | 14889.84 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.279551E+09 | 14844.93 | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322525E+10 | 15017.80 | 27-NOV-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.641887E+10 | 15008.84 | 30-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.872550E+10 | 15017.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.482760E+10 | 19085.33 | 23-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.372147E+10 | 19103.82 | 21-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133897E+10 | 19082.53 | 06-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.458883E+09 | 18997.62 | 03-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7867718.79 | 18122.45 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112594E+09 | 17269.78 | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157436E+10 | 19139.14 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334169E+10 | 19107.57 | 04-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.482760E+10 | 19139.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.551009E+10 | 21712.52 | 23-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.414138E+10 | 21642.64 | 28-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172528E+10 | 21633.68 | 17-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.692845E+09 | 21600.47 | 22-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24320164.62 | 21571.25 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95436575.70 | 17680.69 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167677E+10 | 21684.04 | 27-NOV-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.367772E+10 | 21649.75 | 11-DEC-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.551009E+10 | 21712.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.414192E+10 | 19890.53 | 14-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318850E+10 | 19876.86 | 09-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.930204E+09 | 19834.82 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.264123E+09 | 19827.01 | 22-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4014638.20 | 3941.30 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 65576263.27 | 12176.55 | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125075E+10 | 19871.60 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252381E+10 | 19861.74 | 30-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.414192E+10 | 19890.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.716221E+10 | 25014.14 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.623772E+10 | 25793.60 | 07-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140878E+10 | 15068.42 | 17-MAR-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73888728.39 | 5481.66 | 01-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 268.32 | 0.89 | 11-SEP-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1133.68 | 0.80 | 10-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.220215E+09 | 18144.53 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100313E+10 | 10934.73 | 14-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.716221E+10 | 25793.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.849817E+09 | 0.849817E+09 | 22104.59 | 19-JAN-14:30 | 22104.59 | 0.00 |
February | 0.00 | 0.00 | 0.125199E+10 | 0.125199E+10 | 24291.57 | 24-FEB-15:30 | 24291.57 | 0.00 |
March | 0.00 | 0.00 | 0.513188E+10 | 0.508283E+10 | 67669.95 | 27-MAR-16:00 | 67669.95 | 0.02 |
April | 0.00 | 0.00 | 0.127418E+11 | 0.127397E+11 | 113320.14 | 07-APR-14:40 | 113320.14 | 0.13 |
May | 0.00 | 0.00 | 0.347046E+11 | 0.312502E+11 | 166403.52 | 30-MAY-13:35 | 166403.52 | 0.29 |
June | 0.00 | 0.00 | 0.126642E+12 | 0.105871E+12 | 197259.98 | 15-JUN-04:11 | 142799.12 | 0.68 |
July | 0.00 | 0.00 | 0.187679E+12 | 0.160610E+12 | 222966.59 | 10-JUL-03:02 | 162312.18 | 0.84 |
August | 0.00 | 0.00 | 0.187504E+12 | 0.167595E+12 | 216424.79 | 15-AUG-04:12 | 158498.36 | 0.85 |
September | 0.00 | 0.00 | 0.848009E+11 | 0.734516E+11 | 205370.46 | 22-SEP-04:12 | 142720.51 | 0.54 |
October | 0.00 | 0.00 | 0.395126E+11 | 0.301706E+11 | 164083.14 | 06-OCT-04:12 | 69686.39 | 0.29 |
November | 0.00 | 0.00 | 0.336029E+10 | 0.326669E+10 | 60437.66 | 10-NOV-06:02 | 23548.24 | 0.02 |
December | 0.00 | 0.00 | 0.356318E+10 | 0.356318E+10 | 36131.12 | 18-DEC-14:30 | 36131.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.687742E+12 | 0.595703E+12 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.849817E+09 | 0.849817E+09 | 22104.59 | 22104.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.187679E+12 | 0.167595E+12 | 222966.59 | 166403.52 | 0.85 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.139159E+09 | 0.139159E+09 | 39191.92 | 20-JAN-10:50 | 39191.92 | 0.01 |
February | 0.00 | 0.00 | 0.250504E+09 | 0.250504E+09 | 47630.82 | 02-FEB-11:05 | 47630.82 | 0.00 |
March | 0.00 | 0.00 | 0.218981E+11 | 0.218695E+11 | 431527.00 | 27-MAR-16:00 | 431527.00 | 0.02 |
April | 0.00 | 0.00 | 0.104413E+12 | 0.104387E+12 | 957684.71 | 07-APR-15:10 | 957684.71 | 0.12 |
May | 0.00 | 0.00 | 0.301001E+12 | 0.272151E+12 | 1497939.64 | 30-MAY-14:03 | 1497939.64 | 0.30 |
June | 0.00 | 0.00 | 0.945556E+12 | 0.753566E+12 | 1737563.93 | 24-JUN-04:12 | 1211530.10 | 0.59 |
July | 0.00 | 0.00 | 0.124304E+13 | 0.981283E+12 | 1841080.14 | 24-JUL-04:12 | 1215590.42 | 0.65 |
August | 0.00 | 0.00 | 0.123091E+13 | 0.105122E+13 | 1705295.58 | 22-AUG-14:15 | 1705295.58 | 0.63 |
September | 0.00 | 0.00 | 0.662543E+12 | 0.558462E+12 | 1749016.61 | 07-SEP-04:11 | 1252271.73 | 0.50 |
October | 0.00 | 0.00 | 0.328121E+12 | 0.253209E+12 | 1312600.85 | 06-OCT-05:03 | 562722.31 | 0.29 |
November | 0.00 | 0.00 | 0.323225E+11 | 0.318925E+11 | 470374.24 | 03-NOV-14:05 | 470374.24 | 0.03 |
December | 0.00 | 0.00 | 0.346014E+09 | 0.346014E+09 | 16819.39 | 15-DEC-14:50 | 16819.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.487054E+13 | 0.402878E+13 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 0.139159E+09 | 0.139159E+09 | 16819.39 | 16819.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.124304E+13 | 0.105122E+13 | 1841080.14 | 1705295.58 | 0.65 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 15100802.44 | 15100802.44 | 1840.07 | 15-JAN-10:40 | 1840.07 | 0.02 |
February | 0.00 | 0.00 | 22000573.56 | 22000573.56 | 613.37 | 17-FEB-14:30 | 613.37 | 0.00 |
March | 0.00 | 0.00 | 0.941381E+09 | 0.941381E+09 | 35805.79 | 27-MAR-16:00 | 35805.79 | 0.03 |
April | 0.00 | 0.00 | 0.921487E+10 | 0.921431E+10 | 103816.01 | 07-APR-14:50 | 103816.01 | 0.12 |
May | 0.00 | 0.00 | 0.307821E+11 | 0.280876E+11 | 170025.65 | 30-MAY-13:20 | 170025.65 | 0.28 |
June | 0.00 | 0.00 | 0.102491E+12 | 0.832128E+11 | 185418.53 | 19-JUN-04:12 | 133033.79 | 0.59 |
July | 0.00 | 0.00 | 0.139133E+12 | 0.111734E+12 | 213841.29 | 20-JUL-05:02 | 138118.21 | 0.65 |
August | 0.00 | 0.00 | 0.136144E+12 | 0.117777E+12 | 187703.41 | 22-AUG-14:20 | 187703.41 | 0.63 |
September | 0.00 | 0.00 | 0.676418E+11 | 0.571579E+11 | 177145.92 | 22-SEP-05:02 | 121483.26 | 0.50 |
October | 0.00 | 0.00 | 0.281384E+11 | 0.212421E+11 | 123193.61 | 04-OCT-15:00 | 96816.03 | 0.28 |
November | 0.00 | 0.00 | 0.679857E+09 | 0.650257E+09 | 17589.47 | 03-NOV-14:00 | 17589.47 | 0.02 |
December | 0.00 | 0.00 | 31060803.06 | 31060803.06 | 531.77 | 21-DEC-11:30 | 531.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.515234E+12 | 0.430086E+12 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 15100802.44 | 15100802.44 | 531.77 | 531.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.139133E+12 | 0.117777E+12 | 213841.29 | 187703.41 | 0.65 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.187602E+09 | 0.108979E+09 | 35644.72 | 24-JAN-07:12 | 15741.81 | 0.02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.150773E+10 | 0.148228E+10 | 41682.61 | 27-MAR-16:00 | 41682.61 | 0.02 |
April | 0.00 | 0.00 | 0.629500E+10 | 0.618133E+10 | 65329.42 | 10-APR-06:25 | 38276.26 | 0.08 |
May | 0.00 | 0.00 | 0.200306E+11 | 0.176975E+11 | 96688.83 | 30-MAY-14:00 | 96688.83 | 0.20 |
June | 0.00 | 0.00 | 0.430033E+11 | 0.333950E+11 | 141045.45 | 27-JUN-07:10 | 54483.88 | 0.27 |
July | 0.00 | 0.00 | 0.234277E+11 | 0.176126E+11 | 136274.57 | 14-JUL-19:11 | 51205.25 | 0.09 |
August | 0.00 | 0.00 | 0.366682E+11 | 0.320459E+11 | 121458.70 | 31-AUG-07:10 | 58400.30 | 0.18 |
September | 0.00 | 0.00 | 0.346849E+11 | 0.298811E+11 | 138717.86 | 08-SEP-06:22 | 51406.09 | 0.27 |
October | 0.00 | 0.00 | 0.258923E+11 | 0.200315E+11 | 105816.39 | 06-OCT-08:35 | 46356.00 | 0.25 |
November | 0.00 | 0.00 | 0.589735E+09 | 0.473183E+09 | 81481.48 | 10-NOV-07:25 | 31776.61 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192287E+12 | 0.158909E+12 | 0.12 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.430033E+11 | 0.333950E+11 | 141045.45 | 96688.83 | 0.27 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.568164E+10 | 0.568155E+10 | 3725.74 | 20-JAN-05:57 | 3725.74 | 0.00 |
February | 0.00 | 0.00 | 0.106621E+11 | 0.106565E+11 | 5094.29 | 20-FEB-13:22 | 5094.29 | 0.00 |
March | 0.00 | 0.00 | 0.143911E+11 | 0.131170E+11 | 215284.76 | 27-MAR-16:00 | 169846.80 | 0.00 |
April | 0.00 | 0.00 | 0.100006E+12 | 0.849500E+11 | 397089.10 | 07-APR-13:00 | 397089.10 | 0.00 |
May | 0.00 | 0.00 | 0.222377E+11 | 0.216137E+11 | 217391.55 | 31-MAY-23:20 | 215661.14 | 0.00 |
June | 0.00 | 0.00 | 0.366363E+12 | 0.348613E+12 | 347069.07 | 21-JUN-16:40 | 220557.58 | 0.00 |
July | 0.00 | 0.00 | 0.846238E+12 | 0.829487E+12 | 400849.65 | 31-JUL-23:53 | 400747.61 | 0.00 |
August | 0.00 | 0.00 | 0.102340E+13 | 0.982346E+12 | 451957.01 | 31-AUG-06:11 | 404373.74 | 0.00 |
September | 0.00 | 0.00 | 0.928656E+11 | 0.884422E+11 | 254597.37 | 01-SEP-13:33 | 254597.37 | 0.00 |
October | 0.00 | 0.00 | 0.316249E+11 | 0.229414E+11 | 284932.13 | 25-OCT-10:50 | 223122.85 | 0.00 |
November | 0.00 | 0.00 | 0.107207E+11 | 0.104723E+11 | 45892.26 | 03-NOV-14:00 | 45892.26 | 0.00 |
December | 0.00 | 0.00 | 0.142067E+11 | 0.139926E+11 | 5976.22 | 26-DEC-00:50 | 5491.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.253840E+13 | 0.243231E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.568164E+10 | 0.568155E+10 | 3725.74 | 3725.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102340E+13 | 0.982346E+12 | 451957.01 | 404373.74 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.343660E+10 | 0.343119E+10 | 2335.49 | 29-JAN-16:40 | 2335.49 | 0.00 |
February | 0.00 | 0.00 | 0.810138E+10 | 0.810138E+10 | 4370.14 | 20-FEB-16:30 | 4370.14 | 0.00 |
March | 0.00 | 0.00 | 0.149349E+11 | 0.149236E+11 | 7482.87 | 31-MAR-24:00 | 7482.87 | 0.00 |
April | 0.00 | 0.00 | 0.197517E+11 | 0.197256E+11 | 8862.58 | 23-APR-17:41 | 8862.58 | 0.00 |
May | 0.00 | 0.00 | 0.557343E+10 | 0.547873E+10 | 4089.76 | 31-MAY-23:40 | 4005.85 | 0.00 |
June | 0.00 | 0.00 | 0.109602E+11 | 0.106386E+11 | 5888.54 | 30-JUN-24:00 | 5867.15 | 0.00 |
July | 0.00 | 0.00 | 0.167872E+11 | 0.163005E+11 | 7852.97 | 31-JUL-23:53 | 7845.35 | 0.00 |
August | 0.00 | 0.00 | 0.217212E+11 | 0.213341E+11 | 8893.87 | 31-AUG-17:50 | 8544.61 | 0.00 |
September | 0.00 | 0.00 | 0.581815E+10 | 0.561672E+10 | 3918.04 | 30-SEP-24:00 | 3918.04 | 0.00 |
October | 0.00 | 0.00 | 0.107085E+11 | 0.105622E+11 | 5668.06 | 31-OCT-24:00 | 5667.32 | 0.00 |
November | 0.00 | 0.00 | 0.145005E+11 | 0.144832E+11 | 6114.88 | 12-NOV-15:45 | 6108.57 | 0.00 |
December | 0.00 | 0.00 | 0.197463E+11 | 0.197463E+11 | 8301.83 | 17-DEC-15:55 | 8301.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152040E+12 | 0.150342E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.343660E+10 | 0.343119E+10 | 2335.49 | 2335.49 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217212E+11 | 0.213341E+11 | 8893.87 | 8862.58 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.896252E+10 | 0.892526E+10 | 17213.63 | 20-JAN-16:30 | 17213.63 | 0.00 |
February | 0.00 | 0.00 | 0.563291E+11 | 0.563291E+11 | 36679.99 | 22-FEB-17:00 | 36679.99 | 0.00 |
March | 0.00 | 0.00 | 0.127509E+12 | 0.127394E+12 | 66291.19 | 31-MAR-23:40 | 66291.19 | 0.00 |
April | 0.00 | 0.00 | 0.179275E+12 | 0.179013E+12 | 81783.77 | 09-APR-17:31 | 81751.97 | 0.00 |
May | 0.00 | 0.00 | 0.487495E+11 | 0.478180E+11 | 38911.20 | 31-MAY-23:40 | 38058.97 | 0.00 |
June | 0.00 | 0.00 | 0.102324E+12 | 0.991325E+11 | 55348.51 | 30-JUN-24:00 | 55132.74 | 0.00 |
July | 0.00 | 0.00 | 0.158094E+12 | 0.153249E+12 | 74434.86 | 31-JUL-23:53 | 74355.90 | 0.00 |
August | 0.00 | 0.00 | 0.205811E+12 | 0.201944E+12 | 85285.04 | 31-AUG-17:50 | 81786.69 | 0.00 |
September | 0.00 | 0.00 | 0.511646E+11 | 0.491866E+11 | 36097.28 | 30-SEP-23:30 | 36097.28 | 0.00 |
October | 0.00 | 0.00 | 0.951443E+11 | 0.936921E+11 | 50007.66 | 31-OCT-24:00 | 49987.88 | 0.00 |
November | 0.00 | 0.00 | 0.121301E+12 | 0.121128E+12 | 57421.36 | 03-NOV-16:00 | 57421.36 | 0.00 |
December | 0.00 | 0.00 | 0.164059E+12 | 0.164059E+12 | 72080.10 | 08-DEC-16:10 | 72080.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.131872E+13 | 0.130187E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.896252E+10 | 0.892526E+10 | 17213.63 | 17213.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.205811E+12 | 0.201944E+12 | 85285.04 | 81786.69 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.272098E+09 | 0.269826E+09 | 1656.69 | 19-JAN-16:30 | 1656.69 | 0.00 |
February | 0.00 | 0.00 | 0.396738E+10 | 0.396738E+10 | 3537.97 | 22-FEB-17:00 | 3537.97 | 0.00 |
March | 0.00 | 0.00 | 0.114028E+11 | 0.113917E+11 | 6106.39 | 27-MAR-17:20 | 5980.88 | 0.00 |
April | 0.00 | 0.00 | 0.170684E+11 | 0.170423E+11 | 8251.25 | 09-APR-17:22 | 8244.57 | 0.00 |
May | 0.00 | 0.00 | 0.458680E+10 | 0.449444E+10 | 3852.74 | 31-MAY-23:30 | 3759.22 | 0.00 |
June | 0.00 | 0.00 | 0.102521E+11 | 0.993276E+10 | 5472.78 | 30-JUN-24:00 | 5450.80 | 0.00 |
July | 0.00 | 0.00 | 0.159390E+11 | 0.154545E+11 | 7447.80 | 31-JUL-23:53 | 7439.80 | 0.00 |
August | 0.00 | 0.00 | 0.206576E+11 | 0.202710E+11 | 8664.84 | 31-AUG-17:30 | 8294.42 | 0.00 |
September | 0.00 | 0.00 | 0.493054E+10 | 0.473290E+10 | 3335.83 | 30-SEP-23:20 | 3335.83 | 0.00 |
October | 0.00 | 0.00 | 0.873521E+10 | 0.859055E+10 | 4638.20 | 04-OCT-16:30 | 4343.40 | 0.00 |
November | 0.00 | 0.00 | 0.105387E+11 | 0.105215E+11 | 5727.40 | 03-NOV-16:00 | 5727.40 | 0.00 |
December | 0.00 | 0.00 | 0.144272E+11 | 0.144272E+11 | 7012.40 | 08-DEC-16:10 | 7012.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.122778E+12 | 0.121096E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.272098E+09 | 0.269826E+09 | 1656.69 | 1656.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206576E+11 | 0.202710E+11 | 8664.84 | 8294.42 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 71935.91 | 2052943.92 | 23-JAN-05:11 |
February | 1.85 | 7022.45 | 13-FEB-10:50 | 51254.45 | 1675446.03 | 22-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 12302.51 | 1503753.18 | 17-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3169.27 | 1203312.68 | 03-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 265.64 | 143641.52 | 30-MAY-14:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 443.02 | 167922.35 | 01-JUN-15:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 167.51 | 79735.82 | 11-JUL-16:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 389.31 | 153203.85 | 24-AUG-17:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 78.45 | 89790.99 | 01-SEP-16:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 311.90 | 197000.35 | 28-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13517.74 | 1725387.79 | 21-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 32117.77 | 1781275.13 | 11-DEC-05:01 |
Annual Sum or Average | 0.14 | 15324.89 | ||||
Minimum of Months | 0.00 | 0.00 | 78.45 | 79735.82 | ||
Maximum of Months | 1.85 | 7022.45 | 71935.91 | 2052943.92 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 614.09 | 94048.07 | 24-JAN-07:14 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 890.55 | 42722.65 | 02-FEB-11:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 11728.83 | 568836.80 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 52304.03 | 1517695.71 | 07-APR-14:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 147362.82 | 2209641.60 | 30-MAY-12:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 493477.07 | 1895517.28 | 22-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 625098.85 | 2746306.06 | 24-JUL-05:05 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 619194.49 | 1965492.94 | 22-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 341250.41 | 2172777.26 | 01-SEP-13:33 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 163466.84 | 1691147.48 | 05-OCT-12:05 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 14786.64 | 521483.08 | 03-NOV-14:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1926.35 | 44775.22 | 20-DEC-10:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 207481.21 | 0.00 | ||||
Minimum of Months | 614.09 | 42722.65 | 0.00 | 0.00 | ||
Maximum of Months | 625098.85 | 2746306.06 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 385.44 | 121101.22 | 24-JAN-07:12 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 615.68 | 51671.53 | 02-FEB-11:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 11001.39 | 573701.63 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 51758.20 | 1630403.33 | 07-APR-14:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 147053.75 | 2559653.83 | 30-MAY-09:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 493090.72 | 3209348.38 | 24-JUN-04:12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 623892.88 | 3224126.29 | 24-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 619423.96 | 3172303.79 | 16-AUG-04:12 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 342910.21 | 3222112.73 | 14-SEP-04:12 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 166367.90 | 2472149.52 | 04-OCT-13:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 14224.57 | 526086.04 | 03-NOV-14:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1473.18 | 44100.21 | 20-DEC-10:05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 207491.24 | 0.00 | ||||
Minimum of Months | 385.44 | 44100.21 | 0.00 | 0.00 | ||
Maximum of Months | 623892.88 | 3224126.29 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12798.62 | 63430.89 | 12-JAN-14:50 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 44581.36 | 98322.97 | 24-FEB-15:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 82286.55 | 692392.48 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 180944.74 | 1323454.66 | 07-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 93657.05 | 1045552.10 | 30-MAY-13:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 526395.98 | 1566090.45 | 19-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1047768.73 | 1605093.84 | 07-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1189749.02 | 1813571.89 | 24-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 245383.03 | 1126305.06 | 01-SEP-13:33 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 102462.19 | 920914.41 | 25-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 77546.73 | 159923.82 | 03-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 100435.12 | 168502.64 | 20-DEC-11:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 311397.99 | 0.00 | ||||
Minimum of Months | 12798.62 | 63430.89 | 0.00 | 0.00 | ||
Maximum of Months | 1189749.02 | 1813571.89 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 14762.12 | 52818.53 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 14998.81 | 52891.59 | 09-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15584.59 | 52482.88 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13860.34 | 50266.78 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 13352.86 | 47350.68 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12704.42 | 43855.28 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11079.10 | 40948.16 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11972.37 | 39991.04 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 11565.51 | 41873.63 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12295.95 | 45155.99 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13427.21 | 48541.79 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 13803.68 | 51250.13 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 13274.14 | ||||
Minimum of Months | 0.00 | 0.00 | 11079.10 | 39991.04 | ||
Maximum of Months | 0.00 | 0.00 | 15584.59 | 52891.59 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 50.02 | 23935.54 | 20-JAN-11:00 | 2260.15 | 141193.34 | 27-JAN-10:50 |
February | 65.08 | 46985.97 | 24-FEB-15:50 | 3351.08 | 155235.19 | 22-FEB-11:20 |
March | 8480.75 | 632135.22 | 27-MAR-16:00 | 5373.79 | 151677.27 | 13-MAR-10:40 |
April | 56891.29 | 2438209.66 | 07-APR-14:40 | 2517.94 | 121443.35 | 03-APR-08:50 |
May | 181089.37 | 2877744.25 | 31-MAY-14:05 | 1185.84 | 103481.46 | 13-MAY-08:40 |
June | 914393.36 | 5252084.71 | 15-JUN-12:05 | 253.78 | 77492.50 | 02-JUN-21:00 |
July | 1594840.86 | 5568416.08 | 08-JUL-12:10 | 11.78 | 13388.84 | 11-JUL-03:10 |
August | 1403877.71 | 5837744.26 | 03-AUG-14:05 | 517.49 | 58987.86 | 26-AUG-03:40 |
September | 568146.59 | 4579339.91 | 07-SEP-14:05 | 466.42 | 76404.57 | 23-SEP-11:30 |
October | 213334.73 | 2982850.11 | 24-OCT-13:05 | 1583.89 | 121094.16 | 28-OCT-13:00 |
November | 14211.26 | 585211.59 | 03-NOV-14:10 | 3090.73 | 142908.29 | 21-NOV-11:30 |
December | 123.27 | 33494.70 | 15-DEC-14:50 | 5341.42 | 153830.78 | 13-DEC-10:00 |
Annual Sum or Average | 416621.36 | 2159.46 | ||||
Minimum of Months | 50.02 | 23935.54 | 11.78 | 13388.84 | ||
Maximum of Months | 1594840.86 | 5837744.26 | 5373.79 | 155235.19 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.276630E+10 | 0.28 | 10415.64 | 06-JAN-06:01 | 1.21 |
February | 0.300307E+10 | 0.31 | 10415.64 | 03-FEB-06:01 | 1.21 |
March | 0.533775E+10 | 0.38 | 10406.60 | 27-MAR-15:40 | 1.19 |
April | 0.715989E+10 | 0.46 | 15878.69 | 10-APR-14:40 | 1.57 |
May | 0.730898E+10 | 0.45 | 19214.03 | 30-MAY-04:12 | 1.76 |
June | 0.122982E+11 | 0.64 | 19214.03 | 01-JUN-15:30 | 1.76 |
July | 0.168852E+11 | 0.80 | 19214.03 | 05-JUL-05:03 | 1.75 |
August | 0.182122E+11 | 0.85 | 19214.03 | 01-AUG-05:02 | 1.76 |
September | 0.905894E+10 | 0.51 | 19214.03 | 02-SEP-05:02 | 1.76 |
October | 0.744484E+10 | 0.44 | 14273.11 | 10-OCT-15:20 | 1.46 |
November | 0.489675E+10 | 0.36 | 11607.74 | 06-NOV-14:40 | 1.29 |
December | 0.426184E+10 | 0.33 | 9502.38 | 04-DEC-05:11 | 1.14 |
Annual Sum or Average | 0.986340E+11 | 0.49 | |||
Minimum of Months | 0.276630E+10 | 0.28 | 9502.38 | 1.14 | |
Maximum of Months | 0.182122E+11 | 0.85 | 19214.03 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.239158E+11 | 0.30 | 45294.20 | 02-JAN-04:01 | 0.77 |
February | 0.218289E+11 | 0.30 | 45294.20 | 06-FEB-06:02 | 0.77 |
March | 0.285493E+11 | 0.31 | 72194.53 | 31-MAR-05:03 | 1.00 |
April | 0.362667E+11 | 0.33 | 122031.69 | 07-APR-15:10 | 1.38 |
May | 0.544279E+11 | 0.40 | 179715.61 | 30-MAY-09:15 | 1.76 |
June | 0.764457E+11 | 0.49 | 179715.61 | 01-JUN-14:50 | 1.76 |
July | 0.860594E+11 | 0.51 | 179715.61 | 05-JUL-04:12 | 1.76 |
August | 0.945660E+11 | 0.54 | 179715.61 | 01-AUG-05:02 | 1.76 |
September | 0.584288E+11 | 0.41 | 179715.61 | 01-SEP-04:12 | 1.76 |
October | 0.454853E+11 | 0.36 | 95690.67 | 05-OCT-16:00 | 1.18 |
November | 0.252833E+11 | 0.28 | 70594.97 | 06-NOV-06:03 | 0.99 |
December | 0.224915E+11 | 0.28 | 30712.96 | 11-DEC-05:01 | 0.63 |
Annual Sum or Average | 0.573749E+12 | 0.38 | |||
Minimum of Months | 0.218289E+11 | 0.28 | 30712.96 | 0.63 | |
Maximum of Months | 0.945660E+11 | 0.54 | 179715.61 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.285230E+10 | 0.35 | 4491.21 | 02-JAN-04:01 | 0.73 |
February | 0.251282E+10 | 0.34 | 4491.21 | 03-FEB-06:01 | 0.73 |
March | 0.267593E+10 | 0.31 | 5159.13 | 29-MAR-15:20 | 0.78 |
April | 0.328810E+10 | 0.32 | 11691.79 | 07-APR-15:00 | 1.27 |
May | 0.513750E+10 | 0.38 | 19693.98 | 30-MAY-09:15 | 1.76 |
June | 0.803806E+10 | 0.48 | 19693.98 | 19-JUN-04:12 | 1.75 |
July | 0.955092E+10 | 0.51 | 19693.98 | 03-JUL-04:12 | 1.76 |
August | 0.102717E+11 | 0.54 | 19693.98 | 01-AUG-05:02 | 1.75 |
September | 0.558682E+10 | 0.39 | 19693.98 | 02-SEP-05:02 | 1.76 |
October | 0.384801E+10 | 0.32 | 10276.16 | 04-OCT-16:00 | 1.17 |
November | 0.231969E+10 | 0.29 | 4491.21 | 20-NOV-05:01 | 0.73 |
December | 0.247710E+10 | 0.31 | 4491.21 | 02-DEC-06:01 | 0.73 |
Annual Sum or Average | 0.585589E+11 | 0.38 | |||
Minimum of Months | 0.231969E+10 | 0.29 | 4491.21 | 0.73 | |
Maximum of Months | 0.102717E+11 | 0.54 | 19693.98 | 1.76 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.244809E+10 | 0.32 | 10504.86 | 02-JAN-07:03 | 1.79 |
February | 0.192399E+10 | 0.30 | 10504.86 | 01-FEB-07:05 | 1.80 |
March | 0.517191E+10 | 0.47 | 10504.86 | 01-MAR-07:03 | 1.80 |
April | 0.934938E+10 | 0.68 | 10504.86 | 01-APR-06:05 | 1.79 |
May | 0.118168E+11 | 0.79 | 10504.86 | 01-MAY-06:05 | 1.79 |
June | 0.762801E+10 | 0.52 | 10504.86 | 01-JUN-06:10 | 1.77 |
July | 0.253246E+10 | 0.16 | 10504.86 | 05-JUL-06:10 | 1.74 |
August | 0.519478E+10 | 0.33 | 10504.86 | 07-AUG-06:10 | 1.74 |
September | 0.857632E+10 | 0.58 | 10504.86 | 05-SEP-06:10 | 1.74 |
October | 0.119687E+11 | 0.79 | 10504.86 | 02-OCT-06:05 | 1.79 |
November | 0.102056E+11 | 0.72 | 10504.86 | 01-NOV-06:05 | 1.79 |
December | 0.598205E+10 | 0.49 | 10504.86 | 01-DEC-07:05 | 1.80 |
Annual Sum or Average | 0.827981E+11 | 0.51 | |||
Minimum of Months | 0.192399E+10 | 0.16 | 10504.86 | 1.74 | |
Maximum of Months | 0.119687E+11 | 0.79 | 10504.86 | 1.80 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107843E+12 | 1.35 | 40263.89 | 01-JAN-00:02 | 1.35 |
February | 0.974064E+11 | 1.35 | 40263.89 | 01-FEB-00:10 | 1.35 |
March | 0.107843E+12 | 1.35 | 40263.89 | 01-MAR-00:10 | 1.35 |
April | 0.104364E+12 | 1.35 | 40263.89 | 01-APR-00:10 | 1.35 |
May | 0.107843E+12 | 1.34 | 40263.89 | 01-MAY-00:10 | 1.34 |
June | 0.104364E+12 | 1.34 | 40263.89 | 01-JUN-00:10 | 1.34 |
July | 0.107843E+12 | 1.34 | 40263.89 | 01-JUL-00:10 | 1.34 |
August | 0.107843E+12 | 1.34 | 40263.89 | 01-AUG-00:10 | 1.34 |
September | 0.104364E+12 | 1.34 | 40263.89 | 01-SEP-00:05 | 1.34 |
October | 0.107843E+12 | 1.34 | 40263.89 | 01-OCT-00:10 | 1.34 |
November | 0.104364E+12 | 1.35 | 40263.89 | 01-NOV-00:10 | 1.35 |
December | 0.107843E+12 | 1.35 | 40263.89 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.126976E+13 | 1.35 | |||
Minimum of Months | 0.974064E+11 | 1.34 | 40263.89 | 1.34 | |
Maximum of Months | 0.107843E+12 | 1.35 | 40263.89 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140761E+10 | 0.92 | 525.54 | 01-JAN-00:02 | 0.92 |
February | 0.127139E+10 | 0.92 | 525.54 | 01-FEB-00:10 | 0.92 |
March | 0.140761E+10 | 0.92 | 525.54 | 01-MAR-00:10 | 0.92 |
April | 0.136221E+10 | 0.92 | 525.54 | 01-APR-00:10 | 0.91 |
May | 0.140761E+10 | 0.91 | 525.54 | 01-MAY-00:10 | 0.91 |
June | 0.136221E+10 | 0.91 | 525.54 | 01-JUN-00:20 | 0.91 |
July | 0.140761E+10 | 0.91 | 525.54 | 01-JUL-00:10 | 0.91 |
August | 0.140761E+10 | 0.91 | 525.54 | 01-AUG-00:10 | 0.91 |
September | 0.136221E+10 | 0.91 | 525.54 | 01-SEP-00:05 | 0.91 |
October | 0.140761E+10 | 0.91 | 525.54 | 01-OCT-00:10 | 0.91 |
November | 0.136221E+10 | 0.92 | 525.54 | 01-NOV-00:10 | 0.91 |
December | 0.140761E+10 | 0.92 | 525.54 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.165735E+11 | 0.92 | |||
Minimum of Months | 0.127139E+10 | 0.91 | 525.54 | 0.91 | |
Maximum of Months | 0.140761E+10 | 0.92 | 525.54 | 0.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134738E+11 | 0.92 | 5030.54 | 01-JAN-00:02 | 0.92 |
February | 0.121699E+11 | 0.92 | 5030.54 | 01-FEB-00:10 | 0.92 |
March | 0.134738E+11 | 0.92 | 5030.54 | 01-MAR-00:10 | 0.92 |
April | 0.130392E+11 | 0.92 | 5030.54 | 01-APR-00:10 | 0.91 |
May | 0.134738E+11 | 0.91 | 5030.54 | 01-MAY-00:10 | 0.91 |
June | 0.130392E+11 | 0.91 | 5030.54 | 01-JUN-00:10 | 0.91 |
July | 0.134738E+11 | 0.91 | 5030.54 | 01-JUL-00:10 | 0.91 |
August | 0.134738E+11 | 0.91 | 5030.54 | 01-AUG-00:10 | 0.91 |
September | 0.130392E+11 | 0.91 | 5030.54 | 01-SEP-00:05 | 0.91 |
October | 0.134738E+11 | 0.91 | 5030.54 | 01-OCT-00:10 | 0.91 |
November | 0.130392E+11 | 0.92 | 5030.54 | 01-NOV-00:10 | 0.91 |
December | 0.134738E+11 | 0.92 | 5030.54 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.158643E+12 | 0.92 | |||
Minimum of Months | 0.121699E+11 | 0.91 | 5030.54 | 0.91 | |
Maximum of Months | 0.134738E+11 | 0.92 | 5030.54 | 0.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137294E+10 | 0.92 | 512.60 | 01-JAN-00:02 | 0.92 |
February | 0.124008E+10 | 0.92 | 512.60 | 01-FEB-00:10 | 0.92 |
March | 0.137294E+10 | 0.92 | 512.60 | 01-MAR-00:10 | 0.92 |
April | 0.132866E+10 | 0.92 | 512.60 | 01-APR-00:10 | 0.91 |
May | 0.137294E+10 | 0.91 | 512.60 | 01-MAY-00:10 | 0.91 |
June | 0.132866E+10 | 0.91 | 512.60 | 01-JUN-00:10 | 0.91 |
July | 0.137294E+10 | 0.91 | 512.60 | 01-JUL-00:10 | 0.91 |
August | 0.137294E+10 | 0.91 | 512.60 | 01-AUG-00:10 | 0.91 |
September | 0.132866E+10 | 0.91 | 512.60 | 01-SEP-00:05 | 0.91 |
October | 0.137294E+10 | 0.91 | 512.60 | 01-OCT-00:10 | 0.91 |
November | 0.132866E+10 | 0.92 | 512.60 | 01-NOV-00:10 | 0.91 |
December | 0.137294E+10 | 0.92 | 512.60 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.161653E+11 | 0.92 | |||
Minimum of Months | 0.124008E+10 | 0.91 | 512.60 | 0.91 | |
Maximum of Months | 0.137294E+10 | 0.92 | 512.60 | 0.92 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 73501458.16 | 66812825.47 | 3225.83 | 02-JAN-05:01 | 2932.28 | 2932.28 | 45.11 | 25.44 |
February | 30536112.42 | 27757326.19 | 3190.27 | 06-FEB-06:02 | 2899.96 | 2899.96 | 46.67 | 25.30 |
March | 4573851.06 | 4157630.61 | 1059.50 | 17-MAR-05:01 | 963.09 | 963.09 | 40.71 | 15.65 |
April | 771095.54 | 700925.85 | 615.73 | 03-APR-05:02 | 559.70 | 559.70 | 36.39 | 12.19 |
May | 58212.33 | 52915.01 | 19.10 | 30-MAY-14:10 | 17.37 | 17.37 | 40.18 | 1.73 |
June | 155677.87 | 141511.18 | 22.23 | 01-JUN-15:00 | 20.20 | 20.20 | 39.09 | 1.92 |
July | 52860.10 | 48049.83 | 9.67 | 11-JUL-16:05 | 8.79 | 8.79 | 42.06 | 1.06 |
August | 118797.99 | 107987.37 | 24.87 | 24-AUG-18:40 | 22.61 | 22.61 | 42.83 | 2.07 |
September | 16094.62 | 14630.01 | 8.01 | 01-SEP-16:40 | 7.28 | 7.28 | 36.74 | 0.92 |
October | 49145.44 | 44673.20 | 19.04 | 28-OCT-05:03 | 17.31 | 17.31 | 32.82 | 1.73 |
November | 5795018.90 | 5267672.18 | 1071.05 | 24-NOV-06:01 | 973.58 | 973.58 | 43.90 | 15.71 |
December | 12734063.36 | 11575263.59 | 1076.89 | 07-DEC-06:01 | 978.90 | 978.90 | 43.49 | 15.75 |
Annual Sum or Average | 0.128362E+09 | 0.116681E+09 | ||||||
Minimum of Months | 16094.62 | 14630.01 | 8.01 | 7.28 | 7.28 | 32.82 | 0.92 | |
Maximum of Months | 73501458.16 | 66812825.47 | 3225.83 | 2932.28 | 2932.28 | 46.67 | 25.44 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 144220.91 | 131096.81 | 19.41 | 24-JAN-07:14 | 17.64 | 17.64 | 6.70 | 3.08 |
February | 139881.59 | 127152.36 | 6.57 | 02-FEB-11:05 | 5.97 | 5.97 | 6.70 | 1.41 |
March | 6397982.50 | 5815766.09 | 284.66 | 27-MAR-16:00 | 258.76 | 258.76 | 6.70 | 14.24 |
April | 81932510.13 | 74476651.71 | 5325.54 | 07-APR-14:05 | 4840.91 | 4840.91 | 8.64 | 52.68 |
May | 0.277185E+09 | 0.251962E+09 | 11753.11 | 30-MAY-09:15 | 10683.58 | 10683.58 | 12.30 | 72.27 |
June | 0.983774E+09 | 0.894251E+09 | 10527.47 | 19-JUN-05:03 | 9569.47 | 9569.47 | 10.25 | 69.20 |
July | 0.131025E+10 | 0.119102E+10 | 10530.79 | 24-JUL-05:03 | 9572.49 | 9572.49 | 11.29 | 69.20 |
August | 0.163748E+10 | 0.148847E+10 | 10530.70 | 01-AUG-05:04 | 9572.41 | 9572.41 | 11.26 | 69.20 |
September | 0.786129E+09 | 0.714591E+09 | 10530.61 | 22-SEP-05:04 | 9572.32 | 9572.32 | 11.23 | 69.20 |
October | 0.436072E+09 | 0.396390E+09 | 11642.77 | 03-OCT-10:45 | 10583.27 | 10583.27 | 11.23 | 71.98 |
November | 9384169.24 | 8530209.84 | 343.89 | 10-NOV-06:02 | 312.60 | 312.60 | 6.70 | 15.63 |
December | 351753.69 | 319744.10 | 4.19 | 20-DEC-10:05 | 3.81 | 3.81 | 6.70 | 0.99 |
Annual Sum or Average | 0.552924E+10 | 0.502608E+10 | ||||||
Minimum of Months | 139881.59 | 127152.36 | 4.19 | 3.81 | 3.81 | 6.70 | 0.99 | |
Maximum of Months | 0.163748E+10 | 0.148847E+10 | 11753.11 | 10683.58 | 10683.58 | 12.30 | 72.27 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.674264E+09 | 0.612906E+09 | 4044.67 | 02-JAN-07:03 | 3676.61 | 3676.61 | 6.71 | 36.14 |
February | 0.731595E+09 | 0.665020E+09 | 4044.67 | 01-FEB-11:30 | 3676.61 | 3676.61 | 6.73 | 36.14 |
March | 0.215824E+10 | 0.196184E+10 | 4044.67 | 01-MAR-08:25 | 3676.61 | 3676.61 | 6.72 | 36.14 |
April | 0.275924E+10 | 0.250815E+10 | 4044.67 | 01-APR-09:00 | 3676.61 | 3676.61 | 6.72 | 36.14 |
May | 0.505425E+10 | 0.459431E+10 | 4044.67 | 01-MAY-08:20 | 3676.61 | 3676.61 | 6.73 | 36.14 |
June | 0.764428E+10 | 0.694865E+10 | 4044.67 | 01-JUN-04:12 | 3676.61 | 3676.61 | 9.52 | 36.14 |
July | 0.956785E+10 | 0.869717E+10 | 4044.67 | 01-JUL-04:12 | 3676.61 | 3676.61 | 12.18 | 36.14 |
August | 0.973168E+10 | 0.884610E+10 | 4044.67 | 01-AUG-00:10 | 3676.61 | 3676.61 | 6.93 | 36.14 |
September | 0.642091E+10 | 0.583660E+10 | 4044.67 | 01-SEP-00:05 | 3676.61 | 3676.61 | 6.92 | 36.14 |
October | 0.445705E+10 | 0.405146E+10 | 4044.67 | 02-OCT-06:05 | 3676.61 | 3676.61 | 7.16 | 36.14 |
November | 0.162212E+10 | 0.147450E+10 | 4044.67 | 01-NOV-07:10 | 3676.61 | 3676.61 | 6.80 | 36.14 |
December | 0.133535E+10 | 0.121383E+10 | 4044.67 | 01-DEC-08:35 | 3676.61 | 3676.61 | 6.73 | 36.14 |
Annual Sum or Average | 0.521568E+11 | 0.474105E+11 | ||||||
Minimum of Months | 0.674264E+09 | 0.612906E+09 | 4044.67 | 3676.61 | 3676.61 | 6.71 | 36.14 | |
Maximum of Months | 0.973168E+10 | 0.884610E+10 | 4044.67 | 3676.61 | 3676.61 | 12.18 | 36.14 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 4853608.26 | 4411929.91 | 4044.67 | 07-APR-14:30 | 3676.61 | 3676.61 | 15.69 | 18.07 |
May | 0.200616E+09 | 0.182360E+09 | 4044.67 | 30-MAY-08:50 | 3676.61 | 3676.61 | 14.95 | 18.07 |
June | 0.147489E+10 | 0.134068E+10 | 4044.67 | 01-JUN-10:00 | 3676.61 | 3676.61 | 15.87 | 18.07 |
July | 0.243408E+10 | 0.221258E+10 | 4044.67 | 03-JUL-07:20 | 3676.61 | 3676.61 | 15.15 | 18.07 |
August | 0.241629E+10 | 0.219641E+10 | 4044.67 | 01-AUG-07:20 | 3676.61 | 3676.61 | 15.78 | 18.07 |
September | 0.788469E+09 | 0.716718E+09 | 4044.67 | 01-SEP-07:30 | 3676.61 | 3676.61 | 15.30 | 18.07 |
October | 0.320338E+09 | 0.291187E+09 | 4044.67 | 03-OCT-10:05 | 3676.61 | 3676.61 | 11.23 | 36.14 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.86 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
Annual Sum or Average | 0.763954E+10 | 0.694434E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.243408E+10 | 0.221258E+10 | 4044.67 | 3676.61 | 3676.61 | 15.87 | 36.14 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.997148E+10 | 0.906408E+10 | 3722.93 | 01-JAN-00:02 | 3384.14 | 3384.14 | 18.49 | 15.70 |
February | 0.900650E+10 | 0.818691E+10 | 3722.93 | 01-FEB-00:10 | 3384.14 | 3384.14 | 19.14 | 15.70 |
March | 0.997148E+10 | 0.906408E+10 | 3722.93 | 01-MAR-00:10 | 3384.14 | 3384.14 | 19.58 | 15.70 |
April | 0.964982E+10 | 0.877169E+10 | 3722.93 | 01-APR-00:10 | 3384.14 | 3384.14 | 20.26 | 15.70 |
May | 0.997148E+10 | 0.906408E+10 | 3722.93 | 01-MAY-00:10 | 3384.14 | 3384.14 | 18.86 | 15.70 |
June | 0.964982E+10 | 0.877169E+10 | 3722.93 | 01-JUN-00:10 | 3384.14 | 3384.14 | 19.90 | 15.70 |
July | 0.997148E+10 | 0.906408E+10 | 3722.93 | 01-JUL-00:10 | 3384.14 | 3384.14 | 31.53 | 15.70 |
August | 0.997148E+10 | 0.906408E+10 | 3722.93 | 01-AUG-00:10 | 3384.14 | 3384.14 | 39.22 | 15.70 |
September | 0.964982E+10 | 0.877169E+10 | 3722.93 | 01-SEP-00:05 | 3384.14 | 3384.14 | 28.85 | 15.70 |
October | 0.997148E+10 | 0.906408E+10 | 3722.93 | 01-OCT-00:10 | 3384.14 | 3384.14 | 19.35 | 15.70 |
November | 0.964982E+10 | 0.877169E+10 | 3722.93 | 01-NOV-00:10 | 3384.14 | 3384.14 | 19.75 | 15.70 |
December | 0.997148E+10 | 0.906408E+10 | 3722.93 | 01-DEC-00:10 | 3384.14 | 3384.14 | 20.18 | 15.70 |
Annual Sum or Average | 0.117406E+12 | 0.106722E+12 | ||||||
Minimum of Months | 0.900650E+10 | 0.818691E+10 | 3722.93 | 3384.14 | 3384.14 | 18.49 | 15.70 | |
Maximum of Months | 0.997148E+10 | 0.906408E+10 | 3722.93 | 3384.14 | 3384.14 | 39.22 | 15.70 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 57.15 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.96 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.91 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 57.04 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 57.47 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 57.49 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.59 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 57.73 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.60 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.32 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 57.35 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 57.15 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.91 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.73 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.260179E+10 | 0.236503E+10 | 15609.74 | 20-JAN-11:00 | 14189.26 | 14189.26 | 21.19 | 63.91 |
February | 0.282295E+10 | 0.256606E+10 | 15610.71 | 24-FEB-15:50 | 14190.14 | 14190.14 | 21.28 | 63.91 |
March | 0.832917E+10 | 0.757122E+10 | 15635.32 | 27-MAR-16:00 | 14212.51 | 14212.51 | 23.47 | 63.91 |
April | 0.106728E+11 | 0.970161E+10 | 31322.73 | 07-APR-14:40 | 28472.36 | 28472.36 | 25.66 | 127.82 |
May | 0.202152E+11 | 0.183756E+11 | 31344.34 | 31-MAY-14:05 | 28492.00 | 28492.00 | 26.49 | 127.82 |
June | 0.346167E+11 | 0.314666E+11 | 31422.25 | 15-JUN-11:30 | 28562.83 | 28562.83 | 29.49 | 127.82 |
July | 0.456135E+11 | 0.414627E+11 | 31422.25 | 06-JUL-09:20 | 28562.83 | 28562.83 | 29.60 | 127.82 |
August | 0.465811E+11 | 0.423422E+11 | 31422.25 | 01-AUG-13:00 | 28562.83 | 28562.83 | 29.49 | 127.82 |
September | 0.274881E+11 | 0.249867E+11 | 31422.25 | 07-SEP-13:50 | 28562.83 | 28562.83 | 29.46 | 127.82 |
October | 0.183202E+11 | 0.166530E+11 | 31349.51 | 24-OCT-13:05 | 28496.70 | 28496.70 | 26.68 | 127.82 |
November | 0.626110E+10 | 0.569134E+10 | 15633.34 | 03-NOV-14:10 | 14210.71 | 14210.71 | 23.29 | 63.91 |
December | 0.515264E+10 | 0.468375E+10 | 15610.14 | 15-DEC-14:50 | 14189.62 | 14189.62 | 21.23 | 63.91 |
Annual Sum or Average | 0.228675E+12 | 0.207866E+12 | ||||||
Minimum of Months | 0.260179E+10 | 0.236503E+10 | 15609.74 | 14189.26 | 14189.26 | 21.19 | 63.91 | |
Maximum of Months | 0.465811E+11 | 0.423422E+11 | 31422.25 | 28562.83 | 28562.83 | 29.60 | 127.82 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 42.82 | 42.82 | 71935.91 | 2052943.92 | 23-JAN-05:11 |
February | 1.85 | 7022.45 | 13-FEB-10:50 | 51.41 | 51.41 | 51254.45 | 1675446.03 | 22-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 28.28 | 28.28 | 12302.51 | 1503753.18 | 17-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 32.33 | 32.33 | 3169.27 | 1203312.68 | 03-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.06 | 30.06 | 265.64 | 143641.52 | 30-MAY-14:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 38.67 | 38.67 | 443.02 | 167922.35 | 01-JUN-15:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 48.76 | 48.76 | 167.51 | 79735.82 | 11-JUL-16:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 47.99 | 47.99 | 389.31 | 153203.85 | 24-AUG-17:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 38.90 | 38.90 | 78.45 | 89790.99 | 01-SEP-16:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 36.37 | 36.37 | 311.90 | 197000.35 | 28-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 29.91 | 29.91 | 13517.74 | 1725387.79 | 21-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 26.48 | 26.48 | 32117.77 | 1781275.13 | 11-DEC-05:01 |
Annual Sum or Average | 0.14 | 15324.89 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.48 | 26.48 | 78.45 | 79735.82 | ||
Maximum of Months | 1.85 | 7022.45 | 51.41 | 51.41 | 71935.91 | 2052943.92 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 614.09 | 94048.07 | 24-JAN-07:14 | 7.32 | 6.70 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 890.55 | 42722.65 | 02-FEB-11:05 | 6.98 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 11728.83 | 568836.80 | 27-MAR-16:00 | 10.46 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 52304.03 | 1517695.71 | 07-APR-14:40 | 11.71 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 147362.82 | 2209641.60 | 30-MAY-12:03 | 14.00 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 493477.07 | 1895517.28 | 22-JUN-15:20 | 12.96 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 625098.85 | 2746306.06 | 24-JUL-05:05 | 15.78 | 7.35 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 619194.49 | 1965492.94 | 22-AUG-14:30 | 13.20 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 341250.41 | 2172777.26 | 01-SEP-13:33 | 13.88 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 163466.84 | 1691147.48 | 05-OCT-12:05 | 12.29 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 14786.64 | 521483.08 | 03-NOV-14:05 | 10.14 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1926.35 | 44775.22 | 20-DEC-10:50 | 7.00 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 207481.21 | 0.00 | ||||||
Minimum of Months | 614.09 | 42722.65 | 6.98 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 625098.85 | 2746306.06 | 15.78 | 7.35 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 385.44 | 121101.22 | 24-JAN-07:12 | 16.11 | 6.70 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 615.68 | 51671.53 | 02-FEB-11:05 | 15.44 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 11001.39 | 573701.63 | 27-MAR-16:00 | 16.33 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 51758.20 | 1630403.33 | 07-APR-14:20 | 14.50 | 8.84 | 0.00 | 0.00 | 01-APR-00:10 |
May | 147053.75 | 2559653.83 | 30-MAY-09:20 | 15.16 | 11.53 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 493090.72 | 3209348.38 | 24-JUN-04:12 | 17.79 | 11.98 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 623892.88 | 3224126.29 | 24-JUL-05:02 | 17.84 | 12.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 619423.96 | 3172303.79 | 16-AUG-04:12 | 17.66 | 11.92 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 342910.21 | 3222112.73 | 14-SEP-04:12 | 17.83 | 12.00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 166367.90 | 2472149.52 | 04-OCT-13:20 | 14.94 | 12.45 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 14224.57 | 526086.04 | 03-NOV-14:05 | 18.64 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1473.18 | 44100.21 | 20-DEC-10:05 | 17.36 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 207491.24 | 0.00 | ||||||
Minimum of Months | 385.44 | 44100.21 | 14.50 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 623892.88 | 3224126.29 | 18.64 | 12.45 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12798.62 | 63430.89 | 12-JAN-14:50 | 19.50 | 18.33 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 44581.36 | 98322.97 | 24-FEB-15:50 | 20.14 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 82286.55 | 692392.48 | 27-MAR-16:00 | 30.91 | 24.47 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 180944.74 | 1323454.66 | 07-APR-13:00 | 42.12 | 30.77 | 0.00 | 0.00 | 01-APR-00:10 |
May | 93657.05 | 1045552.10 | 30-MAY-13:30 | 37.21 | 31.67 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 526395.98 | 1566090.45 | 19-JUN-12:00 | 46.37 | 39.27 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1047768.73 | 1605093.84 | 07-JUL-12:00 | 47.05 | 37.39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1189749.02 | 1813571.89 | 24-AUG-15:30 | 50.67 | 38.37 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 245383.03 | 1126305.06 | 01-SEP-13:33 | 38.65 | 32.96 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 102462.19 | 920914.41 | 25-OCT-11:00 | 35.00 | 27.62 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 77546.73 | 159923.82 | 03-NOV-14:00 | 21.26 | 18.69 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 100435.12 | 168502.64 | 20-DEC-11:10 | 21.42 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 311397.99 | 0.00 | ||||||
Minimum of Months | 12798.62 | 63430.89 | 19.50 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1189749.02 | 1813571.89 | 50.67 | 39.27 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 58.09 | 58.09 | 14762.12 | 52818.53 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.54 | 57.54 | 14998.81 | 52891.59 | 09-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.55 | 57.55 | 15584.59 | 52482.88 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.64 | 57.64 | 13860.34 | 50266.78 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.24 | 58.24 | 13352.86 | 47350.68 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.96 | 57.96 | 12704.42 | 43855.28 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.09 | 58.09 | 11079.10 | 40948.16 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.16 | 58.16 | 11972.37 | 39991.04 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 58.15 | 58.15 | 11565.51 | 41873.63 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.05 | 58.05 | 12295.95 | 45155.99 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.90 | 57.90 | 13427.21 | 48541.79 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.74 | 57.74 | 13803.68 | 51250.13 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 13274.14 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.54 | 57.54 | 11079.10 | 39991.04 | ||
Maximum of Months | 0.00 | 0.00 | 58.24 | 58.24 | 15584.59 | 52891.59 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 50.02 | 23935.54 | 20-JAN-11:00 | 21.19 | 20.35 | 2260.15 | 141193.34 | 27-JAN-10:50 |
February | 65.08 | 46985.97 | 24-FEB-15:50 | 21.28 | 20.44 | 3351.08 | 155235.19 | 22-FEB-11:20 |
March | 8480.75 | 632135.22 | 27-MAR-16:00 | 23.47 | 21.10 | 5373.79 | 151677.27 | 13-MAR-10:40 |
April | 56891.29 | 2438209.66 | 07-APR-14:40 | 25.66 | 21.39 | 2517.94 | 121443.35 | 03-APR-08:50 |
May | 181089.37 | 2877744.25 | 31-MAY-14:05 | 26.49 | 23.47 | 1185.84 | 103481.46 | 13-MAY-08:40 |
June | 914393.36 | 5252084.71 | 15-JUN-12:05 | 30.93 | 27.56 | 253.78 | 77492.50 | 02-JUN-21:00 |
July | 1594840.86 | 5568416.08 | 08-JUL-12:10 | 31.52 | 28.42 | 11.78 | 13388.84 | 11-JUL-03:10 |
August | 1403877.71 | 5837744.26 | 03-AUG-14:05 | 32.03 | 28.51 | 517.49 | 58987.86 | 26-AUG-03:40 |
September | 568146.59 | 4579339.91 | 07-SEP-14:05 | 29.67 | 26.40 | 466.42 | 76404.57 | 23-SEP-11:30 |
October | 213334.73 | 2982850.11 | 24-OCT-13:05 | 26.68 | 23.03 | 1583.89 | 121094.16 | 28-OCT-13:00 |
November | 14211.26 | 585211.59 | 03-NOV-14:10 | 23.29 | 21.10 | 3090.73 | 142908.29 | 21-NOV-11:30 |
December | 123.27 | 33494.70 | 15-DEC-14:50 | 21.23 | 20.34 | 5341.42 | 153830.78 | 13-DEC-10:00 |
Annual Sum or Average | 416621.36 | 2159.46 | ||||||
Minimum of Months | 50.02 | 23935.54 | 21.19 | 20.34 | 11.78 | 13388.84 | ||
Maximum of Months | 1594840.86 | 5837744.26 | 32.03 | 28.51 | 5373.79 | 155235.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.153448E+10 | 0.00 | 0.849817E+09 | 0.276630E+10 | 0.00 | 0.00 |
February | 0.104698E+10 | 0.00 | 0.125199E+10 | 0.300307E+10 | 0.00 | 0.00 |
March | 0.196875E+09 | 0.00 | 0.513188E+10 | 0.533775E+10 | 0.00 | 0.00 |
April | 40579909.62 | 0.00 | 0.127418E+11 | 0.715989E+10 | 0.00 | 0.00 |
May | 14084186.84 | 0.00 | 0.347046E+11 | 0.730898E+10 | 0.00 | 0.00 |
June | 74707448.57 | 0.00 | 0.126642E+12 | 0.122982E+11 | 0.00 | 0.00 |
July | 48469902.44 | 0.00 | 0.187679E+12 | 0.168852E+11 | 0.00 | 0.00 |
August | 85553157.38 | 0.00 | 0.187504E+12 | 0.182122E+11 | 0.00 | 0.00 |
September | 12427642.81 | 0.00 | 0.848009E+11 | 0.905894E+10 | 0.00 | 0.00 |
October | 9645391.41 | 0.00 | 0.395126E+11 | 0.744484E+10 | 0.00 | 0.00 |
November | 0.120836E+09 | 0.00 | 0.336029E+10 | 0.489675E+10 | 0.00 | 0.00 |
December | 0.266976E+09 | 0.00 | 0.356318E+10 | 0.426184E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.345162E+10 | 0.00 | 0.687742E+12 | 0.986340E+11 | 0.00 | 0.00 |
Minimum of Months | 9645391.41 | 0.00 | 0.849817E+09 | 0.276630E+10 | 0.00 | 0.00 |
Maximum of Months | 0.153448E+10 | 0.00 | 0.187679E+12 | 0.182122E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.150780E+12 | 0.00 | 0.139159E+09 | 0.239158E+11 | 0.00 | 0.00 |
February | 0.908422E+11 | 0.00 | 0.250504E+09 | 0.218289E+11 | 0.00 | 0.00 |
March | 0.229805E+11 | 0.00 | 0.218981E+11 | 0.285493E+11 | 0.00 | 0.00 |
April | 0.558940E+10 | 0.00 | 0.104413E+12 | 0.362667E+11 | 0.00 | 0.00 |
May | 0.511878E+09 | 0.00 | 0.301001E+12 | 0.544279E+11 | 0.00 | 0.00 |
June | 0.892032E+09 | 0.00 | 0.945556E+12 | 0.764457E+11 | 0.00 | 0.00 |
July | 0.352276E+09 | 0.00 | 0.124304E+13 | 0.860594E+11 | 0.00 | 0.00 |
August | 0.963812E+09 | 0.00 | 0.123091E+13 | 0.945660E+11 | 0.00 | 0.00 |
September | 0.209085E+09 | 0.00 | 0.662543E+12 | 0.584288E+11 | 0.00 | 0.00 |
October | 0.329275E+09 | 0.00 | 0.328121E+12 | 0.454853E+11 | 0.00 | 0.00 |
November | 0.245637E+11 | 0.00 | 0.323225E+11 | 0.252833E+11 | 0.00 | 0.00 |
December | 0.639425E+11 | 0.00 | 0.346014E+09 | 0.224915E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.361957E+12 | 0.00 | 0.487054E+13 | 0.573749E+12 | 0.00 | 0.00 |
Minimum of Months | 0.209085E+09 | 0.00 | 0.139159E+09 | 0.218289E+11 | 0.00 | 0.00 |
Maximum of Months | 0.150780E+12 | 0.00 | 0.124304E+13 | 0.945660E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.335664E+11 | 0.00 | 15100802.44 | 0.285230E+10 | 0.00 | 0.00 |
February | 0.261378E+11 | 0.00 | 22000573.56 | 0.251282E+10 | 0.00 | 0.00 |
March | 0.836179E+10 | 0.00 | 0.941381E+09 | 0.267593E+10 | 0.00 | 0.00 |
April | 0.254808E+10 | 0.00 | 0.921487E+10 | 0.328810E+10 | 0.00 | 0.00 |
May | 85576634.02 | 0.00 | 0.307821E+11 | 0.513750E+10 | 0.00 | 0.00 |
June | 70920748.98 | 0.00 | 0.102491E+12 | 0.803806E+10 | 0.00 | 0.00 |
July | 52093133.41 | 0.00 | 0.139133E+12 | 0.955092E+10 | 0.00 | 0.00 |
August | 0.100502E+09 | 0.00 | 0.136144E+12 | 0.102717E+11 | 0.00 | 0.00 |
September | 11759157.93 | 0.00 | 0.676418E+11 | 0.558682E+10 | 0.00 | 0.00 |
October | 0.573167E+09 | 0.00 | 0.281384E+11 | 0.384801E+10 | 0.00 | 0.00 |
November | 0.102211E+11 | 0.00 | 0.679857E+09 | 0.231969E+10 | 0.00 | 0.00 |
December | 0.207716E+11 | 0.00 | 31060803.06 | 0.247710E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.102501E+12 | 0.00 | 0.515234E+12 | 0.585589E+11 | 0.00 | 0.00 |
Minimum of Months | 11759157.93 | 0.00 | 15100802.44 | 0.231969E+10 | 0.00 | 0.00 |
Maximum of Months | 0.335664E+11 | 0.00 | 0.139133E+12 | 0.102717E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.716221E+10 | 0.00 | 0.187602E+09 | 0.244809E+10 | 0.00 | 0.00 |
February | 0.623772E+10 | 0.00 | 0.00 | 0.192399E+10 | 0.00 | 0.00 |
March | 0.140878E+10 | 0.00 | 0.150773E+10 | 0.517191E+10 | 0.00 | 0.00 |
April | 73888728.39 | 0.00 | 0.629500E+10 | 0.934938E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.200306E+11 | 0.118168E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.430033E+11 | 0.762801E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.234277E+11 | 0.253246E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.366682E+11 | 0.519478E+10 | 0.00 | 0.00 |
September | 268.32 | 0.00 | 0.346849E+11 | 0.857632E+10 | 0.00 | 0.00 |
October | 1133.68 | 0.00 | 0.258923E+11 | 0.119687E+11 | 0.00 | 0.00 |
November | 0.220215E+09 | 0.00 | 0.589735E+09 | 0.102056E+11 | 0.00 | 0.00 |
December | 0.100313E+10 | 0.00 | 0.00 | 0.598205E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.161059E+11 | 0.00 | 0.192287E+12 | 0.827981E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.192399E+10 | 0.00 | 0.00 |
Maximum of Months | 0.716221E+10 | 0.00 | 0.430033E+11 | 0.119687E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.950933E+10 | 0.228804E+12 | 0.00 | 43.57 |
February | 0.00 | 0.00 | 0.155469E+11 | 0.312850E+12 | 0.00 | 78.33 |
March | 0.00 | 0.00 | 0.205693E+11 | 0.310546E+12 | 0.00 | 73.11 |
April | 0.00 | 0.00 | 0.127556E+12 | 0.265817E+12 | 0.00 | 49.81 |
May | 0.00 | 0.00 | 0.308129E+11 | 0.164567E+12 | 0.00 | 17.91 |
June | 0.00 | 0.00 | 0.462347E+12 | 0.217051E+12 | 0.00 | 6.21 |
July | 0.00 | 0.00 | 0.107205E+13 | 0.333657E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.129814E+13 | 0.388836E+12 | 0.00 | 2.33 |
September | 0.00 | 0.00 | 0.119884E+12 | 0.147063E+12 | 0.00 | 5.83 |
October | 0.00 | 0.00 | 0.422035E+11 | 0.211565E+12 | 0.00 | 34.65 |
November | 0.00 | 0.00 | 0.158956E+11 | 0.290117E+12 | 0.00 | 67.18 |
December | 0.00 | 0.00 | 0.206352E+11 | 0.369281E+12 | 0.00 | 94.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.323515E+13 | 0.324015E+13 | 0.00 | 473.80 |
Minimum of Months | 0.00 | 0.00 | 0.950933E+10 | 0.147063E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.129814E+13 | 0.388836E+12 | 0.00 | 94.86 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.425211E+10 | 0.222313E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.990705E+10 | 0.307706E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.179880E+11 | 0.446069E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.236073E+11 | 0.521777E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.681795E+10 | 0.265213E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.135500E+11 | 0.395201E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.211171E+11 | 0.573743E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.272287E+11 | 0.691511E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.718493E+10 | 0.272898E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.129558E+11 | 0.365497E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.174275E+11 | 0.428921E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.237190E+11 | 0.538029E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.185755E+12 | 0.502888E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.425211E+10 | 0.222313E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.272287E+11 | 0.691511E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.112816E+11 | 0.157929E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.692390E+11 | 0.250798E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.153923E+12 | 0.398883E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.214548E+12 | 0.483120E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.597306E+11 | 0.244550E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126580E+12 | 0.372956E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.198964E+12 | 0.543438E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.258101E+12 | 0.657637E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.632880E+11 | 0.251625E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.115264E+12 | 0.335933E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.146141E+12 | 0.378791E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.197708E+12 | 0.471229E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161477E+13 | 0.454689E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.112816E+11 | 0.157929E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.258101E+12 | 0.657637E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.345311E+09 | 0.144616E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.489952E+10 | 0.217222E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.137947E+11 | 0.376477E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.204560E+11 | 0.471625E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.562902E+10 | 0.241516E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126896E+11 | 0.376622E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.200662E+11 | 0.550017E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.259201E+11 | 0.663546E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.610799E+10 | 0.250610E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.105976E+11 | 0.323531E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.127273E+11 | 0.351727E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.174380E+11 | 0.438381E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150671E+12 | 0.440589E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.345311E+09 | 0.144616E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.259201E+11 | 0.663546E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.276630E+10 | 0.849817E+09 | 0.153448E+10 | 0.234667E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300307E+10 | 0.125199E+10 | 0.104698E+10 | 0.215525E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.533775E+10 | 0.513188E+10 | 0.196875E+09 | 0.808935E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.715989E+10 | 0.127418E+11 | 40579909.62 | 0.157479E+10 | 12043917.40 | 0.00 | 0.00 | 0.00 |
May | 0.730898E+10 | 0.347046E+11 | 14084186.84 | 909588.76 | 0.243626E+09 | 0.00 | 0.00 | 0.00 |
June | 0.122982E+11 | 0.126642E+12 | 74707448.57 | 0.00 | 0.405322E+10 | 0.00 | 0.00 | 0.00 |
July | 0.168852E+11 | 0.187679E+12 | 48469902.44 | 0.00 | 0.167277E+11 | 0.00 | 0.00 | 0.00 |
August | 0.182122E+11 | 0.187504E+12 | 85553157.38 | 0.00 | 0.166999E+11 | 0.00 | 0.00 | 0.00 |
September | 0.905894E+10 | 0.848009E+11 | 12427642.81 | 0.00 | 0.230911E+10 | 0.00 | 0.00 | 0.00 |
October | 0.744484E+10 | 0.395126E+11 | 9645391.41 | 0.267942E+09 | 22917465.17 | 0.00 | 0.00 | 0.00 |
November | 0.489675E+10 | 0.336029E+10 | 0.120836E+09 | 0.457968E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.426184E+10 | 0.356318E+10 | 0.266976E+09 | 0.110431E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.986340E+11 | 0.687742E+12 | 0.345162E+10 | 0.705750E+11 | 0.400686E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.276630E+10 | 0.849817E+09 | 9645391.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182122E+11 | 0.187679E+12 | 0.153448E+10 | 0.234667E+11 | 0.167277E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.239158E+11 | 0.139159E+09 | 0.150780E+12 | 0.281673E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218289E+11 | 0.250504E+09 | 0.908422E+11 | 0.273436E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.285493E+11 | 0.218981E+11 | 0.229805E+11 | 0.147194E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362667E+11 | 0.104413E+12 | 0.558940E+10 | 0.354275E+11 | 0.132115E+09 | 0.00 | 0.00 | 0.00 |
May | 0.544279E+11 | 0.301001E+12 | 0.511878E+09 | 0.537827E+09 | 0.240264E+10 | 0.00 | 0.00 | 0.00 |
June | 0.764457E+11 | 0.945556E+12 | 0.892032E+09 | 0.00 | 0.408251E+11 | 0.00 | 0.00 | 0.00 |
July | 0.860594E+11 | 0.124304E+13 | 0.352276E+09 | 0.00 | 0.167191E+12 | 0.00 | 0.00 | 0.00 |
August | 0.945660E+11 | 0.123091E+13 | 0.963812E+09 | 0.00 | 0.167260E+12 | 0.00 | 0.00 | 0.00 |
September | 0.584288E+11 | 0.662543E+12 | 0.209085E+09 | 35814391.89 | 0.234721E+11 | 0.00 | 0.00 | 0.00 |
October | 0.454853E+11 | 0.328121E+12 | 0.329275E+09 | 0.595362E+10 | 0.311927E+09 | 0.00 | 0.00 | 0.00 |
November | 0.252833E+11 | 0.323225E+11 | 0.245637E+11 | 0.952467E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224915E+11 | 0.346014E+09 | 0.639425E+11 | 0.211774E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.573749E+12 | 0.487054E+13 | 0.361957E+12 | 0.105128E+13 | 0.401595E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.218289E+11 | 0.139159E+09 | 0.209085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.945660E+11 | 0.124304E+13 | 0.150780E+12 | 0.281673E+12 | 0.167260E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.285230E+10 | 15100802.44 | 0.335664E+11 | 0.298112E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.251282E+10 | 22000573.56 | 0.261378E+11 | 0.293556E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.267593E+10 | 0.941381E+09 | 0.836179E+10 | 0.172483E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328810E+10 | 0.921487E+10 | 0.254808E+10 | 0.508716E+10 | 2401658.21 | 0.00 | 0.00 | 0.00 |
May | 0.513750E+10 | 0.307821E+11 | 85576634.02 | 96074544.26 | 0.144048E+09 | 0.00 | 0.00 | 0.00 |
June | 0.803806E+10 | 0.102491E+12 | 70920748.98 | 0.00 | 0.336923E+10 | 0.00 | 0.00 | 0.00 |
July | 0.955092E+10 | 0.139133E+12 | 52093133.41 | 0.00 | 0.148210E+11 | 0.00 | 0.00 | 0.00 |
August | 0.102717E+11 | 0.136144E+12 | 0.100502E+09 | 0.00 | 0.151706E+11 | 0.00 | 0.00 | 0.00 |
September | 0.558682E+10 | 0.676418E+11 | 11759157.93 | 1449626.01 | 0.184557E+10 | 0.00 | 0.00 | 0.00 |
October | 0.384801E+10 | 0.281384E+11 | 0.573167E+09 | 0.106479E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231969E+10 | 0.679857E+09 | 0.102211E+11 | 0.119565E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.247710E+10 | 31060803.06 | 0.207716E+11 | 0.249269E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.585589E+11 | 0.515234E+12 | 0.102501E+12 | 0.119548E+12 | 0.353528E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.231969E+10 | 15100802.44 | 11759157.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102717E+11 | 0.139133E+12 | 0.335664E+11 | 0.298112E+11 | 0.151706E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.244809E+10 | 0.188755E+09 | 0.716221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192399E+10 | 0.00 | 0.623772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.517191E+10 | 0.150773E+10 | 0.140878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.934938E+10 | 0.629500E+10 | 73888728.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118168E+11 | 0.200306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.762801E+10 | 0.430033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.253246E+10 | 0.234277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.519478E+10 | 0.366682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.857632E+10 | 0.346849E+11 | 268.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119687E+11 | 0.258923E+11 | 1133.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102056E+11 | 0.589735E+09 | 0.220215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.598205E+10 | 0.00 | 0.100313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.827981E+11 | 0.192288E+12 | 0.161059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.192399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119687E+11 | 0.430033E+11 | 0.716221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.107843E+12 | 0.568164E+10 | 0.00 | 0.00 | 0.00 | 0.116609E+12 | 0.00 | 0.00 |
February | 0.974064E+11 | 0.106621E+11 | 0.00 | 0.00 | 0.00 | 0.209615E+12 | 0.00 | 0.00 |
March | 0.107843E+12 | 0.143911E+11 | 0.00 | 0.00 | 0.00 | 0.195644E+12 | 0.00 | 0.00 |
April | 0.104364E+12 | 0.100006E+12 | 0.00 | 0.00 | 0.00 | 0.133303E+12 | 0.00 | 0.00 |
May | 0.107843E+12 | 0.222377E+11 | 0.00 | 0.00 | 0.00 | 0.479331E+11 | 0.00 | 0.00 |
June | 0.104364E+12 | 0.366363E+12 | 0.00 | 0.00 | 0.00 | 0.166284E+11 | 0.00 | 0.00 |
July | 0.107843E+12 | 0.846238E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107843E+12 | 0.102340E+13 | 0.00 | 0.00 | 0.00 | 0.623057E+10 | 0.00 | 0.00 |
September | 0.104364E+12 | 0.928656E+11 | 0.00 | 0.00 | 0.00 | 0.156102E+11 | 0.00 | 0.00 |
October | 0.107843E+12 | 0.316249E+11 | 0.00 | 0.00 | 0.00 | 0.927258E+11 | 0.00 | 0.00 |
November | 0.104364E+12 | 0.107207E+11 | 0.00 | 0.00 | 0.00 | 0.179769E+12 | 0.00 | 0.00 |
December | 0.107843E+12 | 0.142067E+11 | 0.00 | 0.00 | 0.00 | 0.253867E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.126976E+13 | 0.253840E+13 | 0.00 | 0.00 | 0.00 | 0.126794E+13 | 0.00 | 0.00 |
Minimum of Months | 0.974064E+11 | 0.568164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107843E+12 | 0.102340E+13 | 0.00 | 0.00 | 0.00 | 0.253867E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140761E+10 | 0.343660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127139E+10 | 0.810138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140761E+10 | 0.149349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136221E+10 | 0.197517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140761E+10 | 0.557343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136221E+10 | 0.109602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140761E+10 | 0.167872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140761E+10 | 0.217212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136221E+10 | 0.581815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140761E+10 | 0.107085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136221E+10 | 0.145005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140761E+10 | 0.197463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165735E+11 | 0.152040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127139E+10 | 0.343660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140761E+10 | 0.217212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134738E+11 | 0.896252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121699E+11 | 0.563291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134738E+11 | 0.127509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130392E+11 | 0.179275E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134738E+11 | 0.487495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130392E+11 | 0.102324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134738E+11 | 0.158094E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134738E+11 | 0.205811E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130392E+11 | 0.511646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134738E+11 | 0.951443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130392E+11 | 0.121301E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134738E+11 | 0.164059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158643E+12 | 0.131872E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121699E+11 | 0.896252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134738E+11 | 0.205811E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137294E+10 | 0.272098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124008E+10 | 0.396738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137294E+10 | 0.114028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132866E+10 | 0.170684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137294E+10 | 0.458680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132866E+10 | 0.102521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137294E+10 | 0.159390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137294E+10 | 0.206576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132866E+10 | 0.493054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137294E+10 | 0.873521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132866E+10 | 0.105387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137294E+10 | 0.144272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161653E+11 | 0.122778E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124008E+10 | 0.272098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137294E+10 | 0.206576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.276630E+10 | 0.153448E+10 | 0.849817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300307E+10 | 0.104698E+10 | 0.125199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.533775E+10 | 0.196875E+09 | 0.513188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.715989E+10 | 40579909.62 | 0.127418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.730898E+10 | 14084186.84 | 0.347046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122982E+11 | 74707448.57 | 0.126642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168852E+11 | 48469902.44 | 0.187679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182122E+11 | 85553157.38 | 0.187504E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.905894E+10 | 12427642.81 | 0.848009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.744484E+10 | 9645391.41 | 0.395126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.489675E+10 | 0.120836E+09 | 0.336029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.426184E+10 | 0.266976E+09 | 0.356318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.986340E+11 | 0.345162E+10 | 0.687742E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.276630E+10 | 9645391.41 | 0.849817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182122E+11 | 0.153448E+10 | 0.187679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.239158E+11 | 0.150780E+12 | 0.139159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218289E+11 | 0.908422E+11 | 0.250504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.285493E+11 | 0.229805E+11 | 0.218981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362667E+11 | 0.558940E+10 | 0.104413E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.544279E+11 | 0.511878E+09 | 0.301001E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.764457E+11 | 0.892032E+09 | 0.945556E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.860594E+11 | 0.352276E+09 | 0.124304E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.945660E+11 | 0.963812E+09 | 0.123091E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.584288E+11 | 0.209085E+09 | 0.662543E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.454853E+11 | 0.329275E+09 | 0.328121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252833E+11 | 0.245637E+11 | 0.323225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224915E+11 | 0.639425E+11 | 0.346014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.573749E+12 | 0.361957E+12 | 0.487054E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.218289E+11 | 0.209085E+09 | 0.139159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.945660E+11 | 0.150780E+12 | 0.124304E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.285230E+10 | 0.335664E+11 | 15100802.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.251282E+10 | 0.261378E+11 | 22000573.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.267593E+10 | 0.836179E+10 | 0.941381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328810E+10 | 0.254808E+10 | 0.921487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.513750E+10 | 85576634.02 | 0.307821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.803806E+10 | 70920748.98 | 0.102491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.955092E+10 | 52093133.41 | 0.139133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102717E+11 | 0.100502E+09 | 0.136144E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.558682E+10 | 11759157.93 | 0.676418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.384801E+10 | 0.573167E+09 | 0.281384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231969E+10 | 0.102211E+11 | 0.679857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.247710E+10 | 0.207716E+11 | 31060803.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.585589E+11 | 0.102501E+12 | 0.515234E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.231969E+10 | 11759157.93 | 15100802.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102717E+11 | 0.335664E+11 | 0.139133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.244809E+10 | 0.716221E+10 | 0.187602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192399E+10 | 0.623772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.517191E+10 | 0.140878E+10 | 0.150773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.934938E+10 | 73888728.39 | 0.629500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118168E+11 | 0.00 | 0.200306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.762801E+10 | 0.00 | 0.430033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.253246E+10 | 0.00 | 0.234277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.519478E+10 | 0.00 | 0.366682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.857632E+10 | 268.32 | 0.346849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119687E+11 | 1133.68 | 0.258923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102056E+11 | 0.220215E+09 | 0.589735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.598205E+10 | 0.100313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.827981E+11 | 0.161059E+11 | 0.192287E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.192399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119687E+11 | 0.716221E+10 | 0.430033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.107843E+12 | 0.00 | 0.950933E+10 | 0.00 | 0.382769E+10 | 0.00 | 0.00 | 0.00 | 0.117133E+12 | 0.00 | 0.00 | 0.00 |
February | 0.974064E+11 | 0.00 | 0.155469E+11 | 0.00 | 0.488479E+10 | 0.00 | 0.00 | 0.00 | 0.210559E+12 | 0.00 | 0.00 | 0.00 |
March | 0.107843E+12 | 0.00 | 0.205693E+11 | 0.00 | 0.617823E+10 | 0.00 | 0.00 | 0.00 | 0.196525E+12 | 0.00 | 0.00 | 0.00 |
April | 0.104364E+12 | 0.00 | 0.127556E+12 | 0.00 | 0.275497E+11 | 0.00 | 0.00 | 0.00 | 0.133904E+12 | 0.00 | 0.00 | 0.00 |
May | 0.107843E+12 | 0.00 | 0.308129E+11 | 0.00 | 0.857511E+10 | 0.00 | 0.00 | 0.00 | 0.481489E+11 | 0.00 | 0.00 | 0.00 |
June | 0.104364E+12 | 0.00 | 0.462347E+12 | 0.00 | 0.959833E+11 | 0.00 | 0.00 | 0.00 | 0.167033E+11 | 0.00 | 0.00 | 0.00 |
July | 0.107843E+12 | 0.00 | 0.107205E+13 | 0.00 | 0.225814E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107843E+12 | 0.00 | 0.129814E+13 | 0.00 | 0.274735E+12 | 0.00 | 0.00 | 0.00 | 0.625861E+10 | 0.00 | 0.00 | 0.00 |
September | 0.104364E+12 | 0.00 | 0.119884E+12 | 0.00 | 0.270183E+11 | 0.00 | 0.00 | 0.00 | 0.156805E+11 | 0.00 | 0.00 | 0.00 |
October | 0.107843E+12 | 0.00 | 0.422035E+11 | 0.00 | 0.105786E+11 | 0.00 | 0.00 | 0.00 | 0.931432E+11 | 0.00 | 0.00 | 0.00 |
November | 0.104364E+12 | 0.00 | 0.158956E+11 | 0.00 | 0.517490E+10 | 0.00 | 0.00 | 0.00 | 0.180578E+12 | 0.00 | 0.00 | 0.00 |
December | 0.107843E+12 | 0.00 | 0.206352E+11 | 0.00 | 0.642848E+10 | 0.00 | 0.00 | 0.00 | 0.255010E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126976E+13 | 0.00 | 0.323515E+13 | 0.00 | 0.696748E+12 | 0.00 | 0.00 | 0.00 | 0.127364E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.974064E+11 | 0.00 | 0.950933E+10 | 0.00 | 0.382769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107843E+12 | 0.00 | 0.129814E+13 | 0.00 | 0.274735E+12 | 0.00 | 0.00 | 0.00 | 0.255010E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140761E+10 | 0.00 | 0.425211E+10 | 0.00 | 0.815513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127139E+10 | 0.00 | 0.990705E+10 | 0.00 | 0.180567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140761E+10 | 0.00 | 0.179880E+11 | 0.00 | 0.305308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136221E+10 | 0.00 | 0.236073E+11 | 0.00 | 0.385557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140761E+10 | 0.00 | 0.681795E+10 | 0.00 | 0.124452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136221E+10 | 0.00 | 0.135500E+11 | 0.00 | 0.258980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140761E+10 | 0.00 | 0.211171E+11 | 0.00 | 0.432982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140761E+10 | 0.00 | 0.272287E+11 | 0.00 | 0.550749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136221E+10 | 0.00 | 0.718493E+10 | 0.00 | 0.136678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140761E+10 | 0.00 | 0.129558E+11 | 0.00 | 0.224736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136221E+10 | 0.00 | 0.174275E+11 | 0.00 | 0.292700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140761E+10 | 0.00 | 0.237190E+11 | 0.00 | 0.397268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165735E+11 | 0.00 | 0.185755E+12 | 0.00 | 0.337153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127139E+10 | 0.00 | 0.425211E+10 | 0.00 | 0.815513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140761E+10 | 0.00 | 0.272287E+11 | 0.00 | 0.550749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.134738E+11 | 0.00 | 0.112816E+11 | 0.00 | 0.231907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121699E+11 | 0.00 | 0.692390E+11 | 0.00 | 0.129099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134738E+11 | 0.00 | 0.153923E+12 | 0.00 | 0.264145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130392E+11 | 0.00 | 0.214548E+12 | 0.00 | 0.352728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134738E+11 | 0.00 | 0.597306E+11 | 0.00 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130392E+11 | 0.00 | 0.126580E+12 | 0.00 | 0.242565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134738E+11 | 0.00 | 0.198964E+12 | 0.00 | 0.408700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134738E+11 | 0.00 | 0.258101E+12 | 0.00 | 0.522899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130392E+11 | 0.00 | 0.632880E+11 | 0.00 | 0.121233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134738E+11 | 0.00 | 0.115264E+12 | 0.00 | 0.201195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130392E+11 | 0.00 | 0.146141E+12 | 0.00 | 0.248399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134738E+11 | 0.00 | 0.197708E+12 | 0.00 | 0.336491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158643E+12 | 0.00 | 0.161477E+13 | 0.00 | 0.296046E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121699E+11 | 0.00 | 0.112816E+11 | 0.00 | 0.231907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134738E+11 | 0.00 | 0.258101E+12 | 0.00 | 0.522899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137294E+10 | 0.00 | 0.345311E+09 | 0.00 | 73212245.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124008E+10 | 0.00 | 0.489952E+10 | 0.00 | 0.932140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137294E+10 | 0.00 | 0.137947E+11 | 0.00 | 0.239183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132866E+10 | 0.00 | 0.204560E+11 | 0.00 | 0.338759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137294E+10 | 0.00 | 0.562902E+10 | 0.00 | 0.104222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132866E+10 | 0.00 | 0.126896E+11 | 0.00 | 0.243756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137294E+10 | 0.00 | 0.200662E+11 | 0.00 | 0.412722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137294E+10 | 0.00 | 0.259201E+11 | 0.00 | 0.526251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132866E+10 | 0.00 | 0.610799E+10 | 0.00 | 0.117744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137294E+10 | 0.00 | 0.105976E+11 | 0.00 | 0.186237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132866E+10 | 0.00 | 0.127273E+11 | 0.00 | 0.218861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137294E+10 | 0.00 | 0.174380E+11 | 0.00 | 0.301087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161653E+11 | 0.00 | 0.150671E+12 | 0.00 | 0.278936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124008E+10 | 0.00 | 0.345311E+09 | 0.00 | 73212245.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137294E+10 | 0.00 | 0.259201E+11 | 0.00 | 0.526251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 77880049.82 | 0.00 | 0.00 | 0.514046E+11 | 0.00 | 0.36 |
February | 0.00 | 0.00 | 0.00 | 75036606.39 | 0.00 | 0.00 | 0.480474E+11 | 0.00 | 0.35 |
March | 0.00 | 0.00 | 0.00 | 98720823.76 | 0.00 | 0.00 | 0.570192E+11 | 0.00 | 0.53 |
April | 0.00 | 8116389.53 | 0.00 | 93932806.90 | 0.00 | 0.00 | 0.530283E+11 | 0.00 | 0.74 |
May | 0.00 | 0.478221E+09 | 0.00 | 94885266.37 | 0.00 | 0.00 | 0.444987E+11 | 0.00 | 1.00 |
June | 0.00 | 0.436003E+10 | 0.00 | 66452670.66 | 0.00 | 0.00 | 0.101460E+11 | 0.00 | 0.47 |
July | 0.00 | 0.364344E+10 | 0.00 | 44777248.01 | 0.00 | 0.00 | 0.200412E+10 | 0.00 | 0.08 |
August | 0.00 | 0.287838E+10 | 0.00 | 64885242.82 | 0.00 | 0.00 | 0.431023E+10 | 0.00 | 0.25 |
September | 0.00 | 0.200435E+10 | 0.00 | 0.109176E+09 | 0.00 | 0.00 | 0.232362E+11 | 0.00 | 0.72 |
October | 0.00 | 0.393679E+09 | 0.00 | 0.124568E+09 | 0.00 | 0.00 | 0.462031E+11 | 0.00 | 0.96 |
November | 0.00 | 0.00 | 0.00 | 0.106615E+09 | 0.00 | 0.00 | 0.647471E+11 | 0.00 | 0.72 |
December | 0.00 | 0.00 | 0.00 | 97230855.15 | 0.00 | 0.00 | 0.580674E+11 | 0.00 | 0.45 |
Annual Sum or Average | 0.00 | 0.137662E+11 | 0.00 | 0.105416E+10 | 0.00 | 0.00 | 0.462712E+12 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 44777248.01 | 0.00 | 0.00 | 0.200412E+10 | 0.00 | 0.08 |
Maximum of Months | 0.00 | 0.436003E+10 | 0.00 | 0.124568E+09 | 0.00 | 0.00 | 0.647471E+11 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.625171E+10 | 0.00 | 0.00 | 45937943.70 | 0.00 | 0.00 | 0.291363E+11 | 0.00 | 0.34 |
February | 0.276711E+10 | 0.00 | 0.00 | 55443841.15 | 0.00 | 0.00 | 0.329554E+11 | 0.00 | 0.36 |
March | 0.183897E+10 | 0.00 | 0.00 | 94464746.25 | 0.00 | 0.00 | 0.494129E+11 | 0.00 | 0.50 |
April | 0.473076E+10 | 3246643.09 | 0.00 | 92657023.79 | 0.00 | 0.00 | 0.487611E+11 | 0.00 | 0.73 |
May | 0.259255E+10 | 0.105895E+09 | 0.00 | 84490481.10 | 0.00 | 0.00 | 0.381368E+11 | 0.00 | 0.82 |
June | 0.148915E+10 | 0.479617E+10 | 0.00 | 44553799.52 | 0.101946E+09 | 0.00 | 0.904019E+10 | 0.00 | 0.60 |
July | 0.284807E+09 | 0.101584E+11 | 0.00 | 4345092.02 | 0.175304E+09 | 0.00 | 0.412923E+09 | 0.00 | 0.29 |
August | 0.256901E+10 | 0.692999E+10 | 0.00 | 39626647.72 | 0.147106E+09 | 0.00 | 0.472875E+10 | 0.00 | 0.59 |
September | 0.204558E+10 | 0.318138E+10 | 0.00 | 66157330.54 | 31763108.30 | 0.00 | 0.201455E+11 | 0.00 | 0.70 |
October | 0.314428E+10 | 0.425288E+09 | 0.00 | 95543473.49 | 0.00 | 0.00 | 0.374556E+11 | 0.00 | 0.75 |
November | 0.163333E+10 | 0.00 | 0.00 | 91151758.12 | 0.00 | 0.00 | 0.492384E+11 | 0.00 | 0.55 |
December | 0.208120E+10 | 0.00 | 0.00 | 88241284.61 | 0.00 | 0.00 | 0.451765E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.314285E+11 | 0.256004E+11 | 0.00 | 0.802613E+09 | 0.456119E+09 | 0.00 | 0.364600E+12 | 0.00 | 0.55 |
Minimum of Months | 0.284807E+09 | 0.00 | 0.00 | 4345092.02 | 0.00 | 0.00 | 0.412923E+09 | 0.00 | 0.29 |
Maximum of Months | 0.625171E+10 | 0.101584E+11 | 0.00 | 95543473.49 | 0.175304E+09 | 0.00 | 0.494129E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202020E+12 | 0.00 | 0.00 | 17223843.52 | 0.00 | 0.612224E+10 | 0.246178E+11 | 0.00 | 0.29 |
February | 0.188318E+12 | 0.00 | 0.00 | 39660121.95 | 0.00 | 0.128729E+09 | 0.455024E+11 | 0.00 | 0.30 |
March | 0.136601E+12 | 0.00 | 0.00 | 0.264933E+09 | 0.00 | 0.00 | 0.179457E+12 | 0.00 | 0.35 |
April | 0.816955E+11 | 78186302.84 | 0.00 | 0.389137E+09 | 0.00 | 0.00 | 0.233683E+12 | 0.00 | 0.46 |
May | 0.262002E+11 | 0.970668E+09 | 0.00 | 0.587766E+09 | 0.00 | 0.00 | 0.290784E+12 | 0.00 | 0.65 |
June | 0.919295E+10 | 0.423190E+11 | 0.00 | 0.325195E+09 | 0.101184E+10 | 0.00 | 0.695934E+11 | 0.00 | 0.49 |
July | 0.467174E+09 | 0.882175E+11 | 0.00 | 23936835.11 | 0.166661E+10 | 0.00 | 0.274023E+10 | 0.00 | 0.26 |
August | 0.400802E+10 | 0.585129E+11 | 0.00 | 0.291909E+09 | 0.132004E+10 | 0.00 | 0.369724E+11 | 0.00 | 0.43 |
September | 0.186207E+11 | 0.287300E+11 | 0.00 | 0.430263E+09 | 0.308651E+09 | 0.00 | 0.142943E+12 | 0.00 | 0.54 |
October | 0.399718E+11 | 0.394867E+10 | 0.00 | 0.537811E+09 | 2883937.81 | 0.00 | 0.230789E+12 | 0.00 | 0.52 |
November | 0.114853E+12 | 0.00 | 0.00 | 0.263870E+09 | 0.00 | 0.00 | 0.177797E+12 | 0.00 | 0.35 |
December | 0.180817E+12 | 0.00 | 0.00 | 87915711.49 | 0.00 | 0.00 | 0.841989E+11 | 0.00 | 0.30 |
Annual Sum or Average | 0.100277E+13 | 0.222777E+12 | 0.00 | 0.325962E+10 | 0.431003E+10 | 0.625097E+10 | 0.151908E+13 | 0.00 | 0.41 |
Minimum of Months | 0.467174E+09 | 0.00 | 0.00 | 17223843.52 | 0.00 | 0.00 | 0.274023E+10 | 0.00 | 0.26 |
Maximum of Months | 0.202020E+12 | 0.882175E+11 | 0.00 | 0.587766E+09 | 0.166661E+10 | 0.612224E+10 | 0.290784E+12 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168068E+11 | 0.00 | 0.00 | 18892.00 | 0.00 | 0.209006E+10 | 0.135248E+09 | 0.00 | 0.28 |
February | 0.161269E+11 | 0.00 | 0.00 | 83076.07 | 0.00 | 0.151116E+10 | 0.368557E+09 | 0.00 | 0.29 |
March | 0.195901E+11 | 0.00 | 0.00 | 6004611.79 | 0.00 | 0.306384E+09 | 0.599104E+10 | 0.00 | 0.33 |
April | 0.123000E+11 | 463480.85 | 0.00 | 22693980.64 | 0.00 | 73113482.56 | 0.151673E+11 | 0.00 | 0.43 |
May | 0.699666E+10 | 91306479.56 | 0.00 | 45621785.59 | 0.00 | 0.00 | 0.237161E+11 | 0.00 | 0.64 |
June | 0.108231E+10 | 0.413027E+10 | 0.00 | 30528151.66 | 93850796.83 | 0.00 | 0.712746E+10 | 0.00 | 0.50 |
July | 0.124473E+09 | 0.900877E+10 | 0.00 | 3012752.66 | 0.167334E+09 | 0.00 | 0.290756E+09 | 0.00 | 0.27 |
August | 0.400986E+09 | 0.585784E+10 | 0.00 | 29317323.73 | 0.139631E+09 | 0.00 | 0.367282E+10 | 0.00 | 0.46 |
September | 0.400585E+10 | 0.285430E+10 | 0.00 | 31671304.31 | 26087607.00 | 0.00 | 0.109486E+11 | 0.00 | 0.53 |
October | 0.948128E+10 | 0.277766E+09 | 0.00 | 28838288.04 | 0.00 | 0.00 | 0.137328E+11 | 0.00 | 0.49 |
November | 0.174577E+11 | 0.00 | 0.00 | 5021399.52 | 0.00 | 0.485530E+09 | 0.472702E+10 | 0.00 | 0.32 |
December | 0.186168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107251E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.122990E+12 | 0.222207E+11 | 0.00 | 0.202812E+09 | 0.426903E+09 | 0.553876E+10 | 0.858778E+11 | 0.00 | 0.40 |
Minimum of Months | 0.124473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.195901E+11 | 0.900877E+10 | 0.00 | 45621785.59 | 0.167334E+09 | 0.209006E+10 | 0.237161E+11 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.307593E+10 | 0.00 | 0.00 | 1714.02 | 0.00 | 0.351783E+09 | 8702189.48 | 0.00 | 0.27 |
February | 0.290331E+10 | 0.00 | 0.00 | 45291.44 | 0.00 | 0.213358E+09 | 92102786.97 | 0.00 | 0.26 |
March | 0.248074E+10 | 0.00 | 0.00 | 2786233.61 | 0.00 | 0.00 | 0.195615E+10 | 0.00 | 0.36 |
April | 0.172656E+10 | 549346.31 | 0.00 | 6381502.05 | 0.00 | 0.00 | 0.379771E+10 | 0.00 | 0.66 |
May | 0.658822E+09 | 21694548.76 | 0.00 | 9977841.41 | 0.00 | 0.00 | 0.466779E+10 | 0.00 | 0.92 |
June | 0.223109E+09 | 0.884019E+09 | 0.00 | 6304971.58 | 12801670.11 | 0.00 | 0.135402E+10 | 0.00 | 0.79 |
July | 35780843.17 | 0.184303E+10 | 0.00 | 1255591.03 | 21376706.60 | 0.00 | 64735662.64 | 0.00 | 0.42 |
August | 0.338134E+09 | 0.124419E+10 | 0.00 | 5728244.04 | 18472625.65 | 0.00 | 0.635503E+09 | 0.00 | 0.75 |
September | 0.452832E+09 | 0.483962E+09 | 0.00 | 7043329.80 | 3988595.82 | 0.00 | 0.216123E+10 | 0.00 | 0.74 |
October | 0.115986E+10 | 65174643.40 | 0.00 | 6700689.58 | 0.00 | 0.00 | 0.290004E+10 | 0.00 | 0.65 |
November | 0.213218E+10 | 0.00 | 0.00 | 2759458.44 | 0.00 | 0.00 | 0.201695E+10 | 0.00 | 0.37 |
December | 0.320116E+10 | 0.00 | 0.00 | 462430.92 | 0.00 | 0.00 | 0.418288E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.183884E+11 | 0.454261E+10 | 0.00 | 49447297.91 | 56639598.18 | 0.565140E+09 | 0.200732E+11 | 0.00 | 0.54 |
Minimum of Months | 35780843.17 | 0.00 | 0.00 | 1714.02 | 0.00 | 0.00 | 8702189.48 | 0.00 | 0.25 |
Maximum of Months | 0.320116E+10 | 0.184303E+10 | 0.00 | 9977841.41 | 21376706.60 | 0.351783E+09 | 0.466779E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.173671E+10 | 0.00 | 0.00 | 797207.66 | 0.00 | 0.206127E+09 | 0.415835E+09 | 0.00 | 0.28 |
February | 0.153094E+10 | 0.00 | 0.00 | 1254450.67 | 0.00 | 0.114302E+09 | 0.663175E+09 | 0.00 | 0.29 |
March | 0.138243E+10 | 0.00 | 0.00 | 5411393.25 | 0.00 | 510557.49 | 0.268259E+10 | 0.00 | 0.48 |
April | 0.112876E+10 | 405186.88 | 0.00 | 7736319.24 | 0.00 | 0.00 | 0.392172E+10 | 0.00 | 0.93 |
May | 0.374059E+09 | 19879729.36 | 0.00 | 13158343.23 | 0.00 | 0.00 | 0.491250E+10 | 0.00 | 1.38 |
June | 0.120379E+09 | 0.660568E+09 | 0.00 | 6302953.58 | 8220671.41 | 0.00 | 0.145757E+10 | 0.00 | 1.04 |
July | 23407213.21 | 0.140741E+10 | 0.00 | 1066577.77 | 14136070.78 | 0.00 | 72660214.92 | 0.00 | 0.52 |
August | 0.208931E+09 | 0.101935E+10 | 0.00 | 5958642.76 | 11862310.49 | 0.00 | 0.745066E+09 | 0.00 | 1.04 |
September | 0.218831E+09 | 0.375735E+09 | 0.00 | 11110630.48 | 2561301.40 | 0.00 | 0.241685E+10 | 0.00 | 1.07 |
October | 0.659991E+09 | 52402108.95 | 0.00 | 7869913.20 | 0.00 | 0.00 | 0.324425E+10 | 0.00 | 0.94 |
November | 0.125012E+10 | 0.00 | 0.00 | 3365737.80 | 0.00 | 701433.91 | 0.194771E+10 | 0.00 | 0.44 |
December | 0.188261E+10 | 0.00 | 0.00 | 1253316.32 | 0.00 | 865000.66 | 0.644080E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.105172E+11 | 0.353575E+10 | 0.00 | 65285485.97 | 36780354.08 | 0.322506E+09 | 0.231240E+11 | 0.00 | 0.73 |
Minimum of Months | 23407213.21 | 0.00 | 0.00 | 797207.66 | 0.00 | 0.00 | 72660214.92 | 0.00 | 0.27 |
Maximum of Months | 0.188261E+10 | 0.140741E+10 | 0.00 | 13158343.23 | 14136070.78 | 0.206127E+09 | 0.491250E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212857E+10 | 0.00 | 0.00 | 5849150.75 | 0.00 | 0.373116E+09 | 0.322335E+10 | 0.00 | 0.41 |
February | 0.176801E+10 | 0.00 | 0.00 | 7768827.19 | 0.00 | 0.197492E+09 | 0.418257E+10 | 0.00 | 0.47 |
March | 0.194487E+10 | 0.00 | 0.00 | 12223215.19 | 0.00 | 9518151.32 | 0.699506E+10 | 0.00 | 0.72 |
April | 0.171806E+10 | 1134174.01 | 0.00 | 11803232.47 | 0.00 | 0.00 | 0.625046E+10 | 0.00 | 1.00 |
May | 0.830218E+09 | 27785848.72 | 0.00 | 12923871.01 | 0.00 | 0.00 | 0.546375E+10 | 0.00 | 1.13 |
June | 0.230939E+09 | 0.975969E+09 | 0.00 | 6801326.34 | 12843860.15 | 0.00 | 0.141988E+10 | 0.00 | 0.87 |
July | 36478745.31 | 0.201899E+10 | 0.00 | 1456566.73 | 20800488.13 | 0.00 | 60805100.31 | 0.00 | 0.46 |
August | 0.332461E+09 | 0.159311E+10 | 0.00 | 8549718.47 | 16853600.91 | 0.00 | 0.802164E+09 | 0.00 | 0.99 |
September | 0.365117E+09 | 0.659243E+09 | 0.00 | 21254498.63 | 4001740.90 | 0.00 | 0.400496E+10 | 0.00 | 1.27 |
October | 0.637789E+09 | 0.170712E+09 | 0.00 | 23305618.30 | 0.00 | 0.00 | 0.845473E+10 | 0.00 | 1.45 |
November | 0.158911E+10 | 0.00 | 0.00 | 10768347.39 | 0.00 | 11177380.18 | 0.637785E+10 | 0.00 | 0.73 |
December | 0.224198E+10 | 0.00 | 0.00 | 9021395.46 | 0.00 | 16869304.21 | 0.433136E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.138236E+11 | 0.544694E+10 | 0.00 | 0.131726E+09 | 54499690.08 | 0.608173E+09 | 0.515669E+11 | 0.00 | 0.83 |
Minimum of Months | 36478745.31 | 0.00 | 0.00 | 1456566.73 | 0.00 | 0.00 | 60805100.31 | 0.00 | 0.41 |
Maximum of Months | 0.224198E+10 | 0.201899E+10 | 0.00 | 23305618.30 | 20800488.13 | 0.373116E+09 | 0.845473E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.158941E+10 | 0.00 | 0.00 | 1622967.20 | 0.00 | 18288064.46 | 0.111160E+10 | 0.00 | 0.32 |
February | 0.109599E+10 | 0.00 | 0.00 | 3321351.44 | 0.00 | 11526526.78 | 0.212810E+10 | 0.00 | 0.39 |
March | 0.264183E+09 | 0.00 | 0.00 | 12337654.44 | 0.00 | 0.00 | 0.710830E+10 | 0.00 | 0.93 |
April | 0.198076E+09 | 955402.01 | 0.00 | 19270992.96 | 0.00 | 0.00 | 0.901746E+10 | 0.00 | 1.70 |
May | 0.161815E+09 | 27703601.96 | 0.00 | 15593118.39 | 0.00 | 0.00 | 0.620529E+10 | 0.00 | 1.73 |
June | 55103208.62 | 0.979177E+09 | 0.00 | 9043321.31 | 6018216.30 | 0.00 | 0.174705E+10 | 0.00 | 1.42 |
July | 7012249.56 | 0.191544E+10 | 0.00 | 2554191.68 | 3429230.35 | 0.00 | 81557309.98 | 0.00 | 0.69 |
August | 51000447.68 | 0.146335E+10 | 0.00 | 9492391.48 | 3312190.44 | 0.00 | 0.103965E+10 | 0.00 | 1.43 |
September | 0.145988E+09 | 0.502467E+09 | 0.00 | 12388885.56 | 1862673.38 | 0.00 | 0.278738E+10 | 0.00 | 1.32 |
October | 0.197040E+09 | 0.103964E+09 | 0.00 | 14509429.16 | 0.00 | 0.00 | 0.555920E+10 | 0.00 | 1.46 |
November | 0.280147E+09 | 0.00 | 0.00 | 8450198.24 | 0.00 | 0.00 | 0.519613E+10 | 0.00 | 0.78 |
December | 0.285061E+09 | 0.00 | 0.00 | 7514423.90 | 0.00 | 0.00 | 0.438557E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.433083E+10 | 0.499306E+10 | 0.00 | 0.116099E+09 | 14622310.47 | 29814591.24 | 0.463673E+11 | 0.00 | 1.06 |
Minimum of Months | 7012249.56 | 0.00 | 0.00 | 1622967.20 | 0.00 | 0.00 | 81557309.98 | 0.00 | 0.32 |
Maximum of Months | 0.158941E+10 | 0.191544E+10 | 0.00 | 19270992.96 | 6018216.30 | 18288064.46 | 0.901746E+10 | 0.00 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.961539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209307E+11 | 0.00 | 0.00 | 0.30 |
February | 0.113459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189927E+11 | 0.00 | 0.00 | 0.31 |
March | 0.293773E+11 | 0.00 | 0.00 | 1596917.33 | 0.00 | 0.602984E+10 | 0.113767E+10 | 0.00 | 0.32 |
April | 0.234728E+11 | 13603858.47 | 0.00 | 19895502.22 | 0.00 | 0.970505E+09 | 0.107948E+11 | 0.00 | 0.43 |
May | 0.112346E+11 | 0.218844E+09 | 0.00 | 66760439.76 | 0.00 | 0.00 | 0.299550E+11 | 0.00 | 0.74 |
June | 0.150962E+10 | 0.891190E+10 | 0.00 | 48931492.20 | 0.127597E+09 | 0.00 | 0.107723E+11 | 0.00 | 0.71 |
July | 53832665.70 | 0.192630E+11 | 0.00 | 4508753.75 | 0.209357E+09 | 0.00 | 0.482005E+09 | 0.00 | 0.45 |
August | 0.778646E+09 | 0.128886E+11 | 0.00 | 40433154.01 | 0.166609E+09 | 0.00 | 0.492205E+10 | 0.00 | 0.63 |
September | 0.740796E+10 | 0.459291E+10 | 0.00 | 39292913.76 | 47037601.23 | 0.00 | 0.121292E+11 | 0.00 | 0.59 |
October | 0.187397E+11 | 0.595891E+09 | 0.00 | 25845692.97 | 362277.44 | 29112347.56 | 0.981638E+10 | 0.00 | 0.46 |
November | 0.248411E+11 | 0.00 | 0.00 | 1340065.08 | 0.00 | 0.613100E+10 | 0.145190E+10 | 0.00 | 0.30 |
December | 0.163779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166399E+11 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.154755E+12 | 0.464847E+11 | 0.00 | 0.248605E+09 | 0.550963E+09 | 0.697238E+11 | 0.814613E+11 | 0.00 | 0.46 |
Minimum of Months | 53832665.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.293773E+11 | 0.192630E+11 | 0.00 | 66760439.76 | 0.209357E+09 | 0.209307E+11 | 0.299550E+11 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.655477E+10 | 0.00 | 0.00 | 576920.31 | 0.00 | 0.943916E+10 | 0.277516E+09 | 0.00 | 0.25 |
February | 0.794390E+10 | 0.00 | 0.00 | 2331866.28 | 0.00 | 0.735333E+10 | 0.100721E+10 | 0.00 | 0.25 |
March | 0.115047E+11 | 0.00 | 0.00 | 27839783.80 | 0.00 | 0.234331E+10 | 0.140836E+11 | 0.00 | 0.38 |
April | 0.926599E+10 | 13023791.04 | 0.00 | 56609317.50 | 0.00 | 0.451628E+09 | 0.266111E+11 | 0.00 | 0.72 |
May | 0.442283E+10 | 0.211386E+09 | 0.00 | 0.120142E+09 | 0.00 | 0.00 | 0.418253E+11 | 0.00 | 1.25 |
June | 0.663591E+09 | 0.707425E+10 | 0.00 | 65217644.96 | 81522203.93 | 0.00 | 0.141241E+11 | 0.00 | 1.06 |
July | 35913492.30 | 0.162763E+11 | 0.00 | 7441404.20 | 0.134275E+09 | 0.00 | 0.735092E+09 | 0.00 | 0.63 |
August | 0.303527E+09 | 0.122188E+11 | 0.00 | 60517062.64 | 0.106353E+09 | 0.00 | 0.758498E+10 | 0.00 | 1.07 |
September | 0.268872E+10 | 0.377744E+10 | 0.00 | 80760027.22 | 26335529.08 | 0.00 | 0.189283E+11 | 0.00 | 0.92 |
October | 0.750870E+10 | 0.539675E+09 | 0.00 | 57064750.33 | 0.00 | 0.00 | 0.216951E+11 | 0.00 | 0.75 |
November | 0.110282E+11 | 0.00 | 0.00 | 11975144.09 | 0.00 | 0.270572E+10 | 0.645930E+10 | 0.00 | 0.30 |
December | 0.951123E+10 | 0.00 | 0.00 | 638710.33 | 0.00 | 0.737569E+10 | 0.392723E+09 | 0.00 | 0.24 |
Annual Sum or Average | 0.714320E+11 | 0.401109E+11 | 0.00 | 0.491115E+09 | 0.348486E+09 | 0.296688E+11 | 0.153724E+12 | 0.00 | 0.65 |
Minimum of Months | 35913492.30 | 0.00 | 0.00 | 576920.31 | 0.00 | 0.00 | 0.277516E+09 | 0.00 | 0.24 |
Maximum of Months | 0.115047E+11 | 0.162763E+11 | 0.00 | 0.120142E+09 | 0.134275E+09 | 0.943916E+10 | 0.418253E+11 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125159E+11 | 0.00 | 0.00 | 46849506.53 | 0.00 | 0.103433E+11 | 0.245205E+11 | 0.00 | 0.45 |
February | 0.122238E+11 | 0.00 | 0.00 | 67081913.96 | 0.00 | 0.776688E+10 | 0.349095E+11 | 0.00 | 0.53 |
March | 0.185845E+11 | 0.00 | 0.00 | 0.102577E+09 | 0.00 | 0.270086E+10 | 0.584465E+11 | 0.00 | 0.69 |
April | 0.167967E+11 | 33513127.33 | 0.00 | 89593683.58 | 0.00 | 0.745824E+09 | 0.429334E+11 | 0.00 | 0.80 |
May | 0.102296E+11 | 0.297307E+09 | 0.00 | 0.109020E+09 | 0.00 | 0.00 | 0.451219E+11 | 0.00 | 1.02 |
June | 0.191269E+10 | 0.103952E+11 | 0.00 | 59165958.57 | 0.126981E+09 | 0.00 | 0.120478E+11 | 0.00 | 0.83 |
July | 59458187.97 | 0.226209E+11 | 0.00 | 7461654.73 | 0.209151E+09 | 0.00 | 0.462529E+09 | 0.00 | 0.54 |
August | 0.608809E+09 | 0.187526E+11 | 0.00 | 78147220.36 | 0.165659E+09 | 0.00 | 0.743753E+10 | 0.00 | 0.98 |
September | 0.428208E+10 | 0.731333E+10 | 0.00 | 0.185378E+09 | 41020988.58 | 0.00 | 0.348808E+11 | 0.00 | 1.20 |
October | 0.706168E+10 | 0.200980E+10 | 0.00 | 0.231218E+09 | 0.00 | 0.00 | 0.726811E+11 | 0.00 | 1.33 |
November | 0.158056E+11 | 0.00 | 0.00 | 87483920.60 | 0.00 | 0.213099E+10 | 0.469386E+11 | 0.00 | 0.63 |
December | 0.147438E+11 | 0.00 | 0.00 | 66313679.24 | 0.00 | 0.783431E+10 | 0.338966E+11 | 0.00 | 0.49 |
Annual Sum or Average | 0.114825E+12 | 0.614227E+11 | 0.00 | 0.113029E+10 | 0.542812E+09 | 0.315222E+11 | 0.414277E+12 | 0.00 | 0.79 |
Minimum of Months | 59458187.97 | 0.00 | 0.00 | 7461654.73 | 0.00 | 0.00 | 0.462529E+09 | 0.00 | 0.45 |
Maximum of Months | 0.185845E+11 | 0.226209E+11 | 0.00 | 0.231218E+09 | 0.209151E+09 | 0.103433E+11 | 0.726811E+11 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.973653E+10 | 0.00 | 0.00 | 2302684.76 | 0.00 | 0.869359E+10 | 0.171422E+10 | 0.00 | 0.31 |
February | 0.103907E+11 | 0.00 | 0.00 | 5685524.31 | 0.00 | 0.717359E+10 | 0.403007E+10 | 0.00 | 0.33 |
March | 0.151750E+11 | 0.00 | 0.00 | 31666378.07 | 0.00 | 0.163763E+10 | 0.195927E+11 | 0.00 | 0.50 |
April | 0.991797E+10 | 28822209.33 | 0.00 | 69872830.73 | 0.00 | 0.188212E+09 | 0.300353E+11 | 0.00 | 0.83 |
May | 0.429142E+10 | 0.286040E+09 | 0.00 | 0.106774E+09 | 0.00 | 0.00 | 0.407767E+11 | 0.00 | 1.29 |
June | 0.728786E+09 | 0.969317E+10 | 0.00 | 60420005.13 | 59701552.14 | 0.00 | 0.113990E+11 | 0.00 | 1.17 |
July | 27049284.61 | 0.194114E+11 | 0.00 | 9503105.70 | 69208385.02 | 0.00 | 0.366798E+09 | 0.00 | 0.71 |
August | 0.347574E+09 | 0.152517E+11 | 0.00 | 52907531.09 | 68673954.35 | 0.00 | 0.517933E+10 | 0.00 | 1.16 |
September | 0.294902E+10 | 0.512194E+10 | 0.00 | 78032325.98 | 18855729.28 | 0.00 | 0.169122E+11 | 0.00 | 1.01 |
October | 0.725675E+10 | 0.101368E+10 | 0.00 | 63306363.93 | 0.00 | 0.00 | 0.228276E+11 | 0.00 | 0.84 |
November | 0.151304E+11 | 0.00 | 0.00 | 10878872.28 | 0.00 | 0.211962E+10 | 0.600815E+10 | 0.00 | 0.35 |
December | 0.140010E+11 | 0.00 | 0.00 | 2448754.62 | 0.00 | 0.597924E+10 | 0.187216E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.899521E+11 | 0.508067E+11 | 0.00 | 0.493798E+09 | 0.216440E+09 | 0.257919E+11 | 0.160714E+12 | 0.00 | 0.73 |
Minimum of Months | 27049284.61 | 0.00 | 0.00 | 2302684.76 | 0.00 | 0.00 | 0.366798E+09 | 0.00 | 0.30 |
Maximum of Months | 0.151750E+11 | 0.194114E+11 | 0.00 | 0.106774E+09 | 69208385.02 | 0.869359E+10 | 0.407767E+11 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.483412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216020E+10 | 0.00 | 0.00 | 0.31 |
February | 0.505337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200443E+10 | 0.00 | 0.00 | 0.32 |
March | 0.204388E+10 | 0.00 | 0.00 | 104373.52 | 0.00 | 0.111909E+10 | 0.104002E+09 | 0.00 | 0.33 |
April | 0.202598E+10 | 75255.82 | 0.00 | 1808672.27 | 0.00 | 0.374483E+09 | 0.982290E+09 | 0.00 | 0.44 |
May | 0.132148E+10 | 19190148.62 | 0.00 | 6312013.59 | 0.00 | 11153304.41 | 0.284391E+10 | 0.00 | 0.73 |
June | 0.188288E+09 | 0.830309E+09 | 0.00 | 4937520.76 | 12691952.26 | 0.00 | 0.113523E+10 | 0.00 | 0.72 |
July | 11058865.07 | 0.187446E+10 | 0.00 | 892021.40 | 21326922.64 | 0.00 | 58433714.57 | 0.00 | 0.44 |
August | 88262447.24 | 0.122238E+10 | 0.00 | 4380376.19 | 20493175.57 | 0.00 | 0.523955E+09 | 0.00 | 0.66 |
September | 0.797733E+09 | 0.442565E+09 | 0.00 | 3572444.44 | 10260375.24 | 0.00 | 0.111221E+10 | 0.00 | 0.58 |
October | 0.180082E+10 | 41298242.96 | 0.00 | 1956005.06 | 68984.77 | 95924745.78 | 0.788628E+09 | 0.00 | 0.46 |
November | 0.173919E+10 | 0.00 | 0.00 | 21606.57 | 0.00 | 0.109488E+10 | 25706670.44 | 0.00 | 0.32 |
December | 0.601571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201311E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.116070E+11 | 0.443027E+10 | 0.00 | 23985033.80 | 64841410.48 | 0.887327E+10 | 0.757436E+10 | 0.00 | 0.47 |
Minimum of Months | 11058865.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.204388E+10 | 0.187446E+10 | 0.00 | 6312013.59 | 21326922.64 | 0.216020E+10 | 0.284391E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.556944E+09 | 0.00 | 0.00 | 513.54 | 0.00 | 0.112063E+10 | 2559472.64 | 0.00 | 0.31 |
February | 0.681194E+09 | 0.00 | 0.00 | 23467.10 | 0.00 | 0.869468E+09 | 16222422.49 | 0.00 | 0.30 |
March | 0.110686E+10 | 0.00 | 0.00 | 1865522.28 | 0.00 | 0.429784E+09 | 0.106848E+10 | 0.00 | 0.40 |
April | 0.849306E+09 | 79690.62 | 0.00 | 5012355.43 | 0.00 | 0.197982E+09 | 0.262864E+10 | 0.00 | 0.75 |
May | 0.595672E+09 | 19461089.65 | 0.00 | 12405045.72 | 0.00 | 2748701.01 | 0.426309E+10 | 0.00 | 1.29 |
June | 57554464.40 | 0.698017E+09 | 0.00 | 6671694.35 | 7896671.47 | 0.00 | 0.154722E+10 | 0.00 | 1.10 |
July | 5926623.82 | 0.163705E+10 | 0.00 | 1228276.49 | 13605777.80 | 0.00 | 89544061.35 | 0.00 | 0.65 |
August | 26591551.40 | 0.120482E+10 | 0.00 | 6779628.90 | 11353244.51 | 0.00 | 0.830373E+09 | 0.00 | 1.16 |
September | 0.331994E+09 | 0.388743E+09 | 0.00 | 8450057.52 | 4639801.24 | 0.00 | 0.186506E+10 | 0.00 | 0.98 |
October | 0.681207E+09 | 39539871.22 | 0.00 | 5016124.49 | 0.00 | 44641163.84 | 0.203300E+10 | 0.00 | 0.76 |
November | 0.103888E+10 | 0.00 | 0.00 | 570227.28 | 0.00 | 0.491861E+09 | 0.410891E+09 | 0.00 | 0.34 |
December | 0.699225E+09 | 0.00 | 0.00 | 719.20 | 0.00 | 0.982593E+09 | 3480099.19 | 0.00 | 0.30 |
Annual Sum or Average | 0.663136E+10 | 0.398771E+10 | 0.00 | 48023632.29 | 37495495.01 | 0.413971E+10 | 0.147586E+11 | 0.00 | 0.70 |
Minimum of Months | 5926623.82 | 0.00 | 0.00 | 513.54 | 0.00 | 0.00 | 2559472.64 | 0.00 | 0.30 |
Maximum of Months | 0.110686E+10 | 0.163705E+10 | 0.00 | 12405045.72 | 13605777.80 | 0.112063E+10 | 0.426309E+10 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.793589E+09 | 0.00 | 0.00 | 3406945.00 | 0.00 | 0.119370E+10 | 0.182287E+10 | 0.00 | 0.41 |
February | 0.798299E+09 | 0.00 | 0.00 | 4505037.43 | 0.00 | 0.878251E+09 | 0.247718E+10 | 0.00 | 0.46 |
March | 0.139199E+10 | 0.00 | 0.00 | 8401956.21 | 0.00 | 0.491708E+09 | 0.542347E+10 | 0.00 | 0.68 |
April | 0.143497E+10 | 227702.17 | 0.00 | 8100212.04 | 0.00 | 0.287409E+09 | 0.436129E+10 | 0.00 | 0.81 |
May | 0.115593E+10 | 25521322.26 | 0.00 | 11483683.16 | 0.00 | 14101270.28 | 0.459845E+10 | 0.00 | 1.01 |
June | 0.215237E+09 | 0.949876E+09 | 0.00 | 6180310.61 | 12543555.89 | 0.00 | 0.135232E+10 | 0.00 | 0.84 |
July | 9454990.77 | 0.216921E+10 | 0.00 | 1418054.69 | 21079209.67 | 0.00 | 66764032.11 | 0.00 | 0.53 |
August | 69818852.29 | 0.173863E+10 | 0.00 | 9062099.74 | 17589396.58 | 0.00 | 0.862285E+09 | 0.00 | 1.03 |
September | 0.495088E+09 | 0.701373E+09 | 0.00 | 19382283.61 | 5091091.18 | 0.00 | 0.361203E+10 | 0.00 | 1.23 |
October | 0.711802E+09 | 0.138183E+09 | 0.00 | 19690580.04 | 0.00 | 47247627.24 | 0.731493E+10 | 0.00 | 1.37 |
November | 0.117068E+10 | 0.00 | 0.00 | 6163057.36 | 0.00 | 0.500408E+09 | 0.384239E+10 | 0.00 | 0.61 |
December | 0.913251E+09 | 0.00 | 0.00 | 4081798.83 | 0.00 | 0.994568E+09 | 0.200164E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.916010E+10 | 0.572302E+10 | 0.00 | 0.101876E+09 | 56303253.32 | 0.440739E+10 | 0.377356E+11 | 0.00 | 0.79 |
Minimum of Months | 9454990.77 | 0.00 | 0.00 | 1418054.69 | 0.00 | 0.00 | 66764032.11 | 0.00 | 0.41 |
Maximum of Months | 0.143497E+10 | 0.216921E+10 | 0.00 | 19690580.04 | 21079209.67 | 0.119370E+10 | 0.731493E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.580934E+09 | 0.00 | 0.00 | 164752.18 | 0.00 | 0.987957E+09 | 0.128292E+09 | 0.00 | 0.31 |
February | 0.623221E+09 | 0.00 | 0.00 | 416839.09 | 0.00 | 0.777862E+09 | 0.317781E+09 | 0.00 | 0.32 |
March | 0.120599E+10 | 0.00 | 0.00 | 2673862.95 | 0.00 | 0.275027E+09 | 0.190333E+10 | 0.00 | 0.51 |
April | 0.945879E+09 | 75644.86 | 0.00 | 6537485.64 | 0.00 | 0.102537E+09 | 0.299077E+10 | 0.00 | 0.84 |
May | 0.526680E+09 | 23430267.23 | 0.00 | 11335270.36 | 0.00 | 1435889.42 | 0.418878E+10 | 0.00 | 1.30 |
June | 71196069.97 | 0.873367E+09 | 0.00 | 6458566.21 | 5712671.84 | 0.00 | 0.128193E+10 | 0.00 | 1.17 |
July | 4236166.82 | 0.184366E+10 | 0.00 | 1942684.08 | 6672942.47 | 0.00 | 60082637.89 | 0.00 | 0.69 |
August | 26140728.00 | 0.140746E+10 | 0.00 | 5836147.30 | 7074547.12 | 0.00 | 0.574738E+09 | 0.00 | 1.18 |
September | 0.353149E+09 | 0.489754E+09 | 0.00 | 8417632.95 | 1773931.30 | 0.00 | 0.168003E+10 | 0.00 | 1.01 |
October | 0.738724E+09 | 70580699.25 | 0.00 | 5469153.13 | 0.00 | 31009047.07 | 0.230654E+10 | 0.00 | 0.86 |
November | 0.113700E+10 | 0.00 | 0.00 | 724961.33 | 0.00 | 0.401592E+09 | 0.527742E+09 | 0.00 | 0.36 |
December | 0.781040E+09 | 0.00 | 0.00 | 119291.30 | 0.00 | 0.782231E+09 | 94633343.75 | 0.00 | 0.30 |
Annual Sum or Average | 0.699419E+10 | 0.470833E+10 | 0.00 | 50096646.53 | 21234092.73 | 0.335965E+10 | 0.160547E+11 | 0.00 | 0.74 |
Minimum of Months | 4236166.82 | 0.00 | 0.00 | 119291.30 | 0.00 | 0.00 | 60082637.89 | 0.00 | 0.30 |
Maximum of Months | 0.120599E+10 | 0.184366E+10 | 0.00 | 11335270.36 | 7074547.12 | 0.987957E+09 | 0.418878E+10 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3008147.42 | 0.00 | 0.00 | 0.698156E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7729992.56 | 0.00 | 0.00 | 0.659508E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 15312399.68 | 0.00 | 0.00 | 0.623557E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 17970080.39 | 0.00 | 0.00 | 0.421706E+09 | 0.00 | 0.29 |
May | 0.00 | 4460805.44 | 0.00 | 3990802.26 | 0.00 | 0.00 | 0.255758E+09 | 0.00 | 0.29 |
June | 0.00 | 0.149440E+09 | 0.00 | 2869672.30 | 0.00 | 0.00 | 42984909.02 | 0.00 | 0.31 |
July | 0.00 | 0.362649E+09 | 0.00 | 406885.00 | 0.00 | 0.00 | 758539.28 | 0.00 | 0.28 |
August | 0.00 | 0.287518E+09 | 0.00 | 4712822.33 | 0.00 | 0.00 | 19597559.53 | 0.00 | 0.31 |
September | 0.00 | 76161821.11 | 0.00 | 2547332.05 | 0.00 | 0.00 | 0.113994E+09 | 0.00 | 0.29 |
October | 0.00 | 12763069.90 | 0.00 | 7594133.44 | 0.00 | 0.00 | 0.236461E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 13262988.41 | 0.00 | 0.00 | 0.511393E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18527676.91 | 0.00 | 0.00 | 0.637805E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.892992E+09 | 0.00 | 97932932.75 | 0.00 | 0.00 | 0.422168E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 406885.00 | 0.00 | 0.00 | 758539.28 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.362649E+09 | 0.00 | 18527676.91 | 0.00 | 0.00 | 0.698156E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.198067E+10 | 0.00 | 0.00 | 8534460.63 | 0.00 | 0.00 | 0.496903E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 56258535.35 | 0.00 | 0.00 | 0.661723E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.132968E+09 | 0.00 | 0.00 | 0.625451E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.165339E+09 | 0.00 | 0.00 | 0.422726E+10 | 0.00 | 0.29 |
May | 0.00 | 43086288.74 | 0.00 | 35140319.25 | 0.00 | 0.00 | 0.257542E+10 | 0.00 | 0.29 |
June | 0.00 | 0.148241E+10 | 0.00 | 27009577.94 | 0.00 | 0.00 | 0.431134E+09 | 0.00 | 0.31 |
July | 0.00 | 0.361723E+10 | 0.00 | 3896951.66 | 0.00 | 0.00 | 7692718.06 | 0.00 | 0.28 |
August | 0.00 | 0.287999E+10 | 0.00 | 44983515.17 | 0.00 | 0.00 | 0.196740E+09 | 0.00 | 0.31 |
September | 0.00 | 0.742344E+09 | 0.00 | 22191267.08 | 0.00 | 0.00 | 0.115067E+10 | 0.00 | 0.29 |
October | 0.00 | 0.124114E+09 | 0.00 | 68221953.07 | 0.00 | 0.00 | 0.237393E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.113542E+09 | 0.00 | 0.00 | 0.513157E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.157862E+09 | 0.00 | 0.00 | 0.640508E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.198067E+10 | 0.888918E+10 | 0.00 | 0.835948E+09 | 0.00 | 0.00 | 0.403403E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3896951.66 | 0.00 | 0.00 | 7692718.06 | 0.00 | 0.28 |
Maximum of Months | 0.198067E+10 | 0.361723E+10 | 0.00 | 0.165339E+09 | 0.00 | 0.00 | 0.661723E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.444394E+09 | 0.00 | 0.00 | 369726.36 | 0.00 | 0.00 | 0.239397E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4512839.64 | 0.00 | 0.00 | 0.662743E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 12179409.96 | 0.00 | 0.00 | 0.626750E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15945379.44 | 0.00 | 0.00 | 0.423518E+09 | 0.00 | 0.29 |
May | 0.00 | 4354721.07 | 0.00 | 3319899.76 | 0.00 | 0.00 | 0.258654E+09 | 0.00 | 0.29 |
June | 0.00 | 0.148304E+09 | 0.00 | 2709661.28 | 0.00 | 0.00 | 43149574.02 | 0.00 | 0.31 |
July | 0.00 | 0.361680E+09 | 0.00 | 390560.26 | 0.00 | 0.00 | 772028.49 | 0.00 | 0.28 |
August | 0.00 | 0.288236E+09 | 0.00 | 4508270.45 | 0.00 | 0.00 | 19708839.09 | 0.00 | 0.31 |
September | 0.00 | 74406724.39 | 0.00 | 2082166.88 | 0.00 | 0.00 | 0.115603E+09 | 0.00 | 0.29 |
October | 0.00 | 12313452.57 | 0.00 | 6279341.42 | 0.00 | 0.00 | 0.238465E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10183471.92 | 0.00 | 0.00 | 0.514598E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 14442254.77 | 0.00 | 0.00 | 0.641869E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.444394E+09 | 0.889296E+09 | 0.00 | 76922982.14 | 0.00 | 0.00 | 0.378523E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 369726.36 | 0.00 | 0.00 | 772028.49 | 0.00 | 0.28 |
Maximum of Months | 0.444394E+09 | 0.361680E+09 | 0.00 | 15945379.44 | 0.00 | 0.00 | 0.662743E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.600768E+09 | 0.00 | 0.00 | 0.455375E+12 | 0.00 | 8.22 |
February | 0.00 | 0.00 | 0.00 | 0.109821E+10 | 0.00 | 0.00 | 0.730233E+12 | 0.00 | 13.33 |
March | 0.00 | 0.00 | 0.00 | 0.159234E+10 | 0.00 | 0.00 | 0.101684E+13 | 0.00 | 24.13 |
April | 0.00 | 0.00 | 0.00 | 0.223936E+10 | 0.00 | 0.00 | 0.107852E+13 | 0.00 | 38.76 |
May | 0.00 | 89232975.39 | 0.00 | 0.538552E+09 | 0.00 | 0.00 | 0.374400E+12 | 0.00 | 19.55 |
June | 0.00 | 0.304292E+10 | 0.00 | 0.560340E+09 | 0.00 | 0.00 | 0.230415E+12 | 0.00 | 19.96 |
July | 0.00 | 0.799920E+10 | 0.00 | 71431167.85 | 0.00 | 0.00 | 0.631074E+10 | 0.00 | 1.83 |
August | 0.00 | 0.627723E+10 | 0.00 | 0.732019E+09 | 0.00 | 0.00 | 0.783587E+11 | 0.00 | 12.37 |
September | 0.00 | 0.135339E+10 | 0.00 | 0.483064E+09 | 0.00 | 0.00 | 0.266000E+12 | 0.00 | 21.92 |
October | 0.00 | 3533813.70 | 0.00 | 0.113295E+10 | 0.00 | 0.00 | 0.657232E+12 | 0.00 | 29.75 |
November | 0.00 | 0.00 | 0.00 | 0.151474E+10 | 0.00 | 0.00 | 0.980910E+12 | 0.00 | 26.85 |
December | 0.00 | 0.00 | 0.00 | 0.226695E+10 | 0.00 | 0.00 | 0.132178E+13 | 0.00 | 27.77 |
Annual Sum or Average | 0.00 | 0.187655E+11 | 0.00 | 0.128307E+11 | 0.00 | 0.00 | 0.719637E+13 | 0.00 | 20.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 71431167.85 | 0.00 | 0.00 | 0.631074E+10 | 0.00 | 1.83 |
Maximum of Months | 0.00 | 0.799920E+10 | 0.00 | 0.226695E+10 | 0.00 | 0.00 | 0.132178E+13 | 0.00 | 38.76 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.226063E+12 | 0.210858E+11 | 0.00 | 0.202493E+13 | 0.535815E+11 |
February | 0.369383E+12 | 0.190851E+11 | 0.00 | 0.235289E+13 | 0.122443E+12 |
March | 0.627982E+12 | 0.156617E+11 | 0.00 | 0.293044E+13 | 0.263412E+12 |
April | 0.674262E+12 | 0.102597E+11 | 0.00 | 0.289267E+13 | 0.579429E+12 |
May | 0.861872E+12 | 0.580761E+10 | 0.00 | 0.210286E+13 | 0.603065E+12 |
June | 0.843971E+12 | -27376569.2 | 0.00 | 0.650385E+12 | 0.218660E+13 |
July | 0.826271E+12 | -0.554050E+10 | 0.00 | -0.323797E+12 | 0.338687E+13 |
August | 0.790571E+12 | -0.274409E+10 | 0.00 | 0.105105E+12 | 0.369008E+13 |
September | 0.554660E+12 | 0.210425E+10 | 0.00 | 0.120654E+13 | 0.129402E+13 |
October | 0.523937E+12 | 0.797995E+10 | 0.00 | 0.248001E+13 | 0.722259E+12 |
November | 0.256355E+12 | 0.152830E+11 | 0.00 | 0.285560E+13 | 0.255818E+12 |
December | 0.182596E+12 | 0.181304E+11 | 0.00 | 0.307138E+13 | 0.286610E+12 |
Annual Sum or Average | 0.673792E+13 | 0.107086E+12 | 0.00 | 0.223490E+14 | 0.134442E+14 |
Minimum of Months | 0.182596E+12 | -0.554050E+10 | 0.00 | -0.323797E+12 | 0.535815E+11 |
Maximum of Months | 0.861872E+12 | 0.210858E+11 | 0.00 | 0.307138E+13 | 0.369008E+13 |