Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2024-07-03 12:21:59
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1291.05 | 259.13 | 259.13 |
Net Site Energy | 1172.90 | 235.42 | 235.42 |
Total Source Energy | 3627.45 | 728.08 | 728.08 |
Net Source Energy | 3253.28 | 652.98 | 652.98 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 221.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 60.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 167.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 658.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 25.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 67.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 54.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1069.59 | 221.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 221.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 60.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 167.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 34.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 73.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 25.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 67.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 54.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 221.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 60.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 167.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 34.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 658.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 25.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 67.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 54.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 36.72 | 44.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 137.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 214.68 | 44.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 36.72 | 44.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 137.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 214.68 | 44.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 123.933 | 11.59 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -5.79 | -0.5 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 118.146 | 11.05 |
Electricity Coming From Utility | 951.958 | 89.00 |
Surplus Electricity Going To Utility | 0.514 | 0.05 |
Net Electricity From Utility | 951.444 | 88.95 |
Total On-Site and Utility Electric Sources | 1069.590 | 100.00 |
Total Electricity End Uses | 1069.590 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 328.83 |
Time Setpoint Not Met During Occupied Cooling | 71.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1587.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 61.8568 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 18.6880 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 18.6880 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 61.8568 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 18.6880 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 18.6880 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 18.6880 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:09 | 26-DEC-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 168245.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45670.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 13903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 38861.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24584.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4230.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 128668.41 | 168245.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 168245.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 45670.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 13903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 4325.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 48.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 24584.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4230.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 240.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 191.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 531.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 109.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2086.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 80.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 212.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 171.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3387.39 | 240.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 48.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 38.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 106.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 418.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 16.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 34.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 679.90 | 48.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 48.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 38.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 106.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 418.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 16.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 34.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 679.90 | 48.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.27 | 0.330569 | 0.281000 | 0.637075 | 0.881516 | 0.500000 | 0.001153 | 0.000110 | 0.637075 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 1.97 | 0.380713 | 0.324000 | 0.637812 | 1.00 | 0.500000 | 0.001001 | 0.000151 | 0.637812 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.01 | 0.372003 | 0.316000 | 0.636628 | 0.992009 | 0.500000 | 0.001024 | 0.000251 | 0.866039 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.570365 | 0.277001 | 0.235000 | 0.134036 | 0.738669 | 0.500000 | 0.001375 | 0.000113 | 0.391642 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.754423 | 0.132581 | 0.113000 | 0.085250 | 0.353548 | 0.500000 | 0.002874 | 0.000074 | 0.256122 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.11 | 0.141986 | 0.121000 | 0.134640 | 0.378630 | 0.500000 | 0.002683 | 0.000113 | 0.389399 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.817741 | 0.122307 | 0.104000 | 0.085045 | 0.326151 | 0.500000 | 0.003115 | 0.000074 | 0.254822 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.451588 | 0.349858 | 0.297000 | 0.134122 | 0.932956 | 0.500000 | 0.001089 | 0.000084 | 0.291883 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.620487 | 0.161199 | 0.137000 | 0.085007 | 0.429864 | 0.500000 | 0.002364 | 0.000056 | 0.193340 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.912752 | 0.173094 | 0.147000 | 0.134175 | 0.461583 | 0.500000 | 0.002201 | 0.000084 | 0.289617 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.683641 | 0.146298 | 0.124000 | 0.084772 | 0.390128 | 0.500000 | 0.002604 | 0.000056 | 0.191860 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.501824 | 0.314835 | 0.268000 | 0.134489 | 0.839560 | 0.500000 | 0.001210 | 0.000087 | 0.301595 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.758370 | 0.351708 | 0.500000 | 0.002889 | 0.000058 | 0.199194 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.04 | 0.151950 | 0.129000 | 0.134129 | 0.405200 | 0.500000 | 0.002507 | 0.000087 | 0.299089 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.767849 | 0.130254 | 0.111000 | 0.085231 | 0.347344 | 0.500000 | 0.002925 | 0.000057 | 0.197790 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 12565.03 | 0.000110 | 280.81 |
CORE_MID VAV BOX REHEAT COIL | 17286.41 | 0.000151 | 421.64 |
CORE_TOP VAV BOX REHEAT COIL | 28713.97 | 0.000251 | 758.39 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 12947.41 | 0.000113 | 341.51 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8466.56 | 0.000074 | 223.31 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 12873.41 | 0.000113 | 339.56 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 8423.67 | 0.000074 | 222.18 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9655.71 | 0.000084 | 254.76 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6395.20 | 0.000056 | 168.73 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9580.92 | 0.000084 | 252.79 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6346.33 | 0.000056 | 167.44 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 9976.46 | 0.000087 | 263.22 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 6588.46 | 0.000058 | 173.82 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 9893.73 | 0.000087 | 261.04 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 6542.14 | 0.000057 | 172.60 |
PACU_VAV_BOT HEATING COIL | 16641.16 | 0.000146 | 282.57 |
PACU_VAV_MID HEATING COIL | 17193.87 | 0.000150 | 290.67 |
PACU_VAV_TOP HEATING COIL | 16878.67 | 0.000148 | 288.15 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.47 | 1.08 | 4.94 | 1.39 | 4.26 | 4.26 | 0.300000 | 0.326408 | 4.26 |
PACU_VAV_MID | 2.52 | 1.08 | 5.04 | 1.47 | 4.14 | 4.14 | 0.300000 | 0.354159 | 4.14 |
PACU_VAV_TOP | 2.63 | 1.08 | 5.27 | 2.16 | 4.68 | 4.68 | 0.300000 | 0.460660 | 4.68 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.26 |
PACU_VAV_MID_OA_CONTROLLER | 4.14 |
PACU_VAV_TOP_OA_CONTROLLER | 4.68 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.26 | 74878.10 | 0.800470 | 1.42 | 24956.87 | 0.800470 |
PACU_VAV_MID COOLING COIL | 4.14 | 72957.47 | 0.800351 | 1.38 | 24316.72 | 0.800351 |
PACU_VAV_TOP COOLING COIL | 4.68 | 81482.81 | 0.800898 | 1.56 | 27158.22 | 0.800898 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.26 |
PACU_VAV_MID FAN | 4.14 |
PACU_VAV_TOP FAN | 4.68 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000146 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000150 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000148 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.001898 | 0.227777 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.001898 | 565.98 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 216969.11 | 216969.11 | 0.001898 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 61.857 | 0.000 | 0.000 | 0.000 | 0.000 | 67.661 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 51196.000 | 52.053 | 967.081 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 3043.602 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 1600.000 | 1.627 | 30.224 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1281.968 | 1600.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5960 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5902 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7087 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.444 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.460 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.177 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.34210526E-12 | 0.10412655E-14 | -0.10417952E-12 | 0.10409145E-15 |
43 | 6 | 0.30802088E-07 | 0.17108976E-09 | 0.70383009E-08 | -0.14667926E-12 |
44 | 5 | -0.20086572E-03 | 0.14450046E-05 | -0.10316412E-03 | 0.69507809E-08 |
45 | 4 | 0.30464713 | 0.69501731E-03 | 0.10418329 | -0.35343869E-04 |
46 | 3 | -7.5136835 | 0.21306369E-01 | -2.4123261 | 0.30221796E-01 |
47 | 2 | 41.686696 | 0.75037385E-01 | 15.565716 | -0.34242481 |
48 | 1 | -81.170502 | 0.33581009E-01 | -29.411065 | 1.0919325 |
49 | 0 | 46.824335 | 0.67004661E-03 | 16.284887 | |
50 | 7 | -0.34244365E-12 | 0.92212740E-15 | -0.10449257E-12 | 0.10448628E-15 |
51 | 6 | 0.30869821E-07 | 0.16952917E-09 | 0.70532514E-08 | -0.14704533E-12 |
52 | 5 | -0.20120586E-03 | 0.14312561E-05 | -0.10333395E-03 | 0.69653235E-08 |
53 | 4 | 0.30503960 | 0.68816038E-03 | 0.10432471 | -0.35399819E-04 |
54 | 3 | -7.5214432 | 0.21089521E-01 | -2.4146296 | 0.30259860E-01 |
55 | 2 | 41.712273 | 0.74252889E-01 | 15.575132 | -0.34270975 |
56 | 1 | -81.190086 | 0.33221761E-01 | -29.419498 | 1.0923499 |
57 | 0 | 46.824335 | 0.66271842E-03 | 16.284691 | |
58 | 7 | -0.32374075E-12 | 0.12045207E-14 | -0.10360241E-12 | 0.16221974E-15 |
59 | 6 | 0.29475593E-07 | 0.20098913E-09 | 0.67455071E-08 | -0.13952197E-12 |
60 | 5 | -0.19418177E-03 | 0.17111334E-05 | -0.99823337E-04 | 0.66657971E-08 |
61 | 4 | 0.29690150 | 0.82890285E-03 | 0.10139402 | -0.34243177E-04 |
62 | 3 | -7.3604632 | 0.25571829E-01 | -2.3668478 | 0.29470418E-01 |
63 | 2 | 41.181572 | 0.90565943E-01 | 15.379610 | -0.33679792 |
64 | 1 | -80.783638 | 0.40729985E-01 | -29.244332 | 1.0836880 |
65 | 0 | 46.824337 | 0.81662197E-03 | 16.288791 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2573E-002 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2641E-002 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4224E-002 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4284E-002 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6471E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6944E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1337E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1567E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1623 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.9225E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1866 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1161 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1060 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7045E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5658E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7130E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2572E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2644E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4224E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4288E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6472E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6962E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1335E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1565E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2304E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2846E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8309E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9927E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8970E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5043E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3611E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5268E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5254E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5531E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1996E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2197E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8087E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8154E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8245E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8324E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6869E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7449E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9039E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9509E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3474E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3809E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1335E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1565E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6058E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6401E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5557E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0181E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2282E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3531E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5658E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7130E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6871E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7454E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9039E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9508E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3472E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3794E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1337E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1567E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.9163E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1214E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4250E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7806E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6747E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3962E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3611E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5268E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3487E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.4506E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9713E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0906E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6797E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7106E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8247E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8326E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1612 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1154 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1821 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1336 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1142 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.9166E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.2056E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.4300E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.9837E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1443E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6075E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8659E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.7319E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4067E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2614E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4669E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.2170E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.4103E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0968E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6778E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7687E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9509E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.2056E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4300E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6810E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.9904E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2167E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6662E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.5169E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3039E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2615E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4670E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1613 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1154 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1821 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1336 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1142 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.9159E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.2051E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.4297E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.9837E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1440E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6075E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8657E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.7315E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4064E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2609E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4667E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.2172E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.4102E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0969E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6777E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7684E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9507E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.2051E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4297E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6810E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.9902E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2167E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6659E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.5165E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3036E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2610E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4667E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 31039.90116 | 31039.90116 | 2.26717 | 2.26717 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 6241.94354 | 6241.94354 | 0.26587 | 0.42469 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 26971.92669 | 26971.92669 | 1.96856 | 1.96856 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 10956.00505 | 10956.00505 | 0.46854 | 0.46854 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 27333.00582 | 27333.00582 | 2.01465 | 2.01465 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 20118.37586 | 20118.37586 | 0.86604 | 0.86604 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 7738.33214 | 7738.33214 | 0.57037 | 0.57037 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9062.68041 | 9062.68041 | 0.39164 | 0.39164 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10235.58704 | 10235.58704 | 0.75442 | 0.75442 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 23.35067 | 8.81188E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 5926.06248 | 5926.06248 | 0.25612 | 0.25612 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 15096.84152 | 15096.84152 | 1.11273 | 1.11273 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9010.96029 | 9010.96029 | 0.38940 | 0.38940 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11094.66352 | 11094.66352 | 0.81774 | 0.81774 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 5896.08167 | 5896.08167 | 0.25482 | 0.25482 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6126.81490 | 6126.81490 | 0.45159 | 0.45159 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 6760.91041 | 6760.91041 | 0.29188 | 0.29188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8479.36741 | 8479.36741 | 0.62049 | 0.62049 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4477.66358 | 4477.66358 | 0.19334 | 0.19334 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12383.67149 | 12383.67149 | 0.91275 | 0.91275 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 6708.62999 | 6708.62999 | 0.28962 | 0.28962 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9275.25209 | 9275.25209 | 0.68364 | 0.68364 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90400 | 8.81750E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4443.49754 | 4443.49754 | 0.19186 | 0.19186 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 6808.39498 | 6808.39498 | 0.50182 | 0.50182 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 6985.88977 | 6985.88977 | 0.30159 | 0.30159 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10289.14492 | 10289.14492 | 0.75837 | 0.75837 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.81136E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4613.21105 | 4613.21105 | 0.19919 | 0.19919 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 14106.86876 | 14106.86876 | 1.03976 | 1.03976 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 6928.04833 | 6928.04833 | 0.29909 | 0.29909 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10417.74353 | 10417.74353 | 0.76785 | 0.76785 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4580.84290 | 4580.84290 | 0.19779 | 0.19779 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 63098.84 | 4.26274 | 4.26274 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 19342.69 | 1.39139 | 1.39139 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 61459.25 | 4.13999 | 4.13999 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 19330.08 | 1.46621 | 1.46621 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 68709.17 | 4.68463 | 4.68463 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 19145.13 | 2.15802 | 2.15802 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26717 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33057 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63707 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88152 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15256E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.09924E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63707 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12565.02596 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09924E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 280.80756 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.96856 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38071 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32400 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63781 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00075E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51229E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63781 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17286.40615 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51229E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 421.63953 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.01465 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37200 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31600 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63663 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99201 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02418E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.51202E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.86604 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 28713.97294 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.51202E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 758.39322 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57037 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27700 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23500 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13404 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73867 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37545E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.13270E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39164 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12947.40901 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13270E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 341.51126 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75442 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13258 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52498E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35355 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87372E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.40692E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25612 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8466.56322 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.40692E-005 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 223.31316 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11273 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14199 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12100 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13464 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37863 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.68336E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12622E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38940 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12873.41395 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12622E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 339.56150 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81774 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12231 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10400 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50450E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32615 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.11512E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.36939E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25482 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8423.67019 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.36939E-005 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 222.18292 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.45159 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34986 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29700 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13412 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93296 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08901E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.44723E-005 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29188 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9655.70619 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.44723E-005 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 254.76239 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62049 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16120 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13700 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50067E-002 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42986 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36354E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.59480E-005 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19334 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6395.19992 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.59480E-005 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 168.72731 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91275 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17309 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14700 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13417 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46158 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20112E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.38181E-005 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28962 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9580.92174 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.38181E-005 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 252.79126 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68364 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14630 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12400 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47715E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39013 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60428E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.55205E-005 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19186 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6346.33204 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.55205E-005 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 167.43917 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.50182 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31484 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26800 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13449 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83956 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21016E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.72784E-005 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30159 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9976.46124 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.72784E-005 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 263.21912 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75837 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35171 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88876E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.76387E-005 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19919 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6588.45513 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.76387E-005 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 173.82152 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03976 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15195 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12900 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13413 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40520 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.50740E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.65547E-005 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29909 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9893.72842 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.65547E-005 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 261.03820 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76785 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13025 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11100 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52312E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34734 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.92506E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.72335E-005 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19779 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6542.14294 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.72335E-005 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 172.60111 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.46782 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07515 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.93564 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39139 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.26274 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.26274 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.32641 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.51818 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07660 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.03636 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.46621 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.13999 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.13999 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.35416 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.63495 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07560 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.26990 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.15802 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.68463 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.68463 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.46066 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.26274 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.13999 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.68463 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.26274 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.26274 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 74878.10185 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80047 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.42077 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 24956.87135 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80047 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 16641.15943 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45584E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 282.57299 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.26274 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.45584E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.13999 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.13999 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 72957.46656 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80035 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.37986 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 24316.72360 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80035 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 17193.86630 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50419E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 290.67400 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.13999 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.50419E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.68463 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.68463 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 81482.81370 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80090 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.56139 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27158.22181 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80090 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 16878.67232 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47662E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 288.15316 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.68463 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.47662E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.89814E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.22778 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.89814E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 565.97676 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 216969.10710 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 216969.11000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.89814E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 11907.75 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 16374.98 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 27212.71 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 12267.43 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8021.86 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 12197.33 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7981.23 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9149.11 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6059.62 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9078.26 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6013.32 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 9452.99 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 6242.70 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 9374.62 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 6198.83 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 13635.25 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 13966.89 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 13976.05 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 73791.20 | 251786.01 | 12.21 | 3.17 | 3.49 | 3.67 | 3.89 | 10.81 | 11.92 | 12.53 | 13.28 | 4.8600 | 3.8542 | 2.5867 | 1.0544 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 71908.81 | 245363.05 | 12.22 | 3.17 | 3.50 | 3.67 | 3.89 | 10.82 | 11.93 | 12.54 | 13.29 | 4.7201 | 3.7442 | 2.5127 | 1.0234 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 80264.54 | 273873.99 | 12.18 | 3.16 | 3.49 | 3.66 | 3.88 | 10.80 | 11.89 | 12.50 | 13.24 | 5.3410 | 4.2340 | 2.8400 | 1.1620 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.5209909492E-002 | 3.8103146825E-002 | Pass | Pass | 0.2177542356 | 0.4057898248 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.2176979769E-002 | 5.1446126844E-002 | Pass | Pass | 0.3751701451 | 0.4672830560 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.8344062843E-002 | 2.8791133003E-002 | Pass | Pass | 0.2644162490 | 0.4207487890 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.7006230969E-002 | 3.0498380054E-002 | Pass | Pass | 0.2186082388 | 0.3891689878 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.8914869567E-002 | 1.5030753298E-002 | Pass | Pass | 0.7086067735 | 1.7846602262 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.3094840909E-002 | 1.3749296430E-002 | Pass | Pass | 29.8837511040 | 188.8476339969 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2019895756 | 0.1946045309 | Pass | Pass | 16.3783482775 | 40.6574501399 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2079953047 | 0.2017179948 | Pass | Pass | 17.1119369082 | 42.7597544449 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1922487586 | 0.1877899119 | Pass | Pass | 16.4622176906 | 40.9089816535 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2110419370 | 0.2045615241 | Pass | Pass | 17.1046365932 | 42.6896428347 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1028564520 | 0.1377230378 | Pass | Pass | 1.0201759752 | 2.5950289497 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1134633413 | 0.1531406202 | Pass | Pass | 0.9434985010 | 2.3185833881 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.9752772843E-002 | 0.1298763115 | Pass | Pass | 1.0688944119 | 2.7734809907 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1156445343 | 0.1561737657 | Pass | Pass | 0.9328774452 | 2.2867985832 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1158527807 | 0.1421656763 | Pass | Pass | 1.3864443760 | 3.1148112966 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1245243902 | 0.1535106976 | Pass | Pass | 1.2718082696 | 2.7841827278 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1155252695 | 0.1381071792 | Pass | Pass | 1.4078591304 | 3.1749578270 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1259420316 | 0.1558403990 | Pass | Pass | 1.2726588236 | 2.7945401705 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2997.83 | 77.52 | 0.00 | 2233.10 | 399.84 | 5708.30 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 195.79 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.062 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 22.12 | 0.0000 | Y | 5.00 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.89 | 0.0000 | Y | 3.13 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.68 | 0.0000 | Y | 4.90 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.86 | 0.0000 | Y | 3.13 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 22.05 | 0.0000 | Y | 4.98 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.85 | 0.0000 | Y | 3.12 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.64 | 0.0000 | Y | 4.89 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.81 | 0.0000 | Y | 3.12 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 22.12 | 0.0000 | Y | 5.00 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.89 | 0.0000 | Y | 3.13 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.68 | 0.0000 | Y | 4.90 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.86 | 0.0000 | Y | 3.13 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 167.80 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 42.59 | 42.59 | 4.34 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.55 | 63.07 | 3.32 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.55 | 47.80 | 26.94 | |
Exterior Lighting Total | 3824.74 | 34.59 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 216969.11 | 0.84 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 74878.10 | 59937.68 | 14940.42 | 0.80 | 3.88 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 72957.47 | 58391.61 | 14565.86 | 0.80 | 3.88 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 81482.81 | 65259.43 | 16223.39 | 0.80 | 3.88 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 73791.2 | 3.17 | 10.81 | N/A | N/A | 12.21 | |
PACU_VAV_MID COOLING COIL | 71908.8 | 3.17 | 10.82 | N/A | N/A | 12.22 | |
PACU_VAV_TOP COOLING COIL | 80264.5 | 3.16 | 10.80 | N/A | N/A | 12.18 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 12565.03 | 11907.75 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 17286.41 | 16374.98 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 28713.97 | 27212.71 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12947.41 | 12267.43 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 8466.56 | 8021.86 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12873.41 | 12197.33 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 8423.67 | 7981.23 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 9655.71 | 9149.11 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6395.20 | 6059.62 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9580.92 | 9078.26 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 6346.33 | 6013.32 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 9976.46 | 9452.99 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6588.46 | 6242.70 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9893.73 | 9374.62 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 6542.14 | 6198.83 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 16641.16 | 13635.25 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 17193.87 | 13966.89 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 16878.67 | 13976.05 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.26 | 9331.18 | 2189.01 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.14 | 9062.48 | 2189.01 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.68 | 10254.71 | 2189.01 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.001898 | 565.98 | 298174.34 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 73791.20 | 3.17 | 10.81 | 12.21 | 4.8600 | 3.49 | 11.92 | 3.8542 | 3.67 | 12.53 | 2.5867 | 3.89 | 13.28 | 1.0544 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 71908.81 | 3.17 | 10.82 | 12.22 | 4.7201 | 3.50 | 11.93 | 3.7442 | 3.67 | 12.54 | 2.5127 | 3.89 | 13.29 | 1.0234 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 80264.54 | 3.16 | 10.80 | 12.18 | 5.3410 | 3.49 | 11.89 | 4.2340 | 3.66 | 12.50 | 2.8400 | 3.88 | 13.24 | 1.1620 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 31039.90 | 31039.90 | 31.56 | 2.267 | 2.267 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_MID | 26971.93 | 26971.93 | 27.42 | 1.969 | 1.969 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_TOP | 27333.01 | 27333.01 | 27.79 | 2.015 | 2.015 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00894 | 29.30 | 0.00882 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 7738.33 | 7738.33 | 37.32 | 0.570 | 0.570 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00883 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10235.59 | 10235.59 | 77.98 | 0.754 | 0.754 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00866 | 23.35 | 0.00881 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15096.84 | 15096.84 | 72.81 | 1.113 | 1.113 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00867 | 29.14 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11094.66 | 11094.66 | 84.53 | 0.818 | 0.818 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00865 | 27.94 | 0.00882 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6126.81 | 6126.81 | 29.55 | 0.452 | 0.452 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00891 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8479.37 | 8479.37 | 64.60 | 0.620 | 0.620 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00869 | 21.70 | 0.00881 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12383.67 | 12383.67 | 59.73 | 0.913 | 0.913 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00870 | 29.31 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9275.25 | 9275.25 | 70.67 | 0.684 | 0.684 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00867 | 26.90 | 0.00882 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6808.39 | 6808.39 | 32.84 | 0.502 | 0.502 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00887 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10289.14 | 10289.14 | 78.39 | 0.758 | 0.758 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00866 | 23.02 | 0.00881 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14106.87 | 14106.87 | 68.04 | 1.040 | 1.040 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00868 | 29.05 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10417.74 | 10417.74 | 79.37 | 0.768 | 0.768 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00865 | 27.94 | 0.00882 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 6241.94 | 6241.94 | 6.35 | 0.266 | 0.425 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_MID | 10956.01 | 10956.01 | 11.14 | 0.469 | 0.469 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_TOP | 20118.38 | 20118.38 | 20.46 | 0.866 | 0.866 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9062.68 | 9062.68 | 43.71 | 0.392 | 0.392 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 5926.06 | 5926.06 | 45.15 | 0.256 | 0.256 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9010.96 | 9010.96 | 43.46 | 0.389 | 0.389 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 5896.08 | 5896.08 | 44.92 | 0.255 | 0.255 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6760.91 | 6760.91 | 32.61 | 0.292 | 0.292 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4477.66 | 4477.66 | 34.11 | 0.193 | 0.193 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 6708.63 | 6708.63 | 32.36 | 0.290 | 0.290 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4443.50 | 4443.50 | 33.85 | 0.192 | 0.192 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6985.89 | 6985.89 | 33.69 | 0.302 | 0.302 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4613.21 | 4613.21 | 35.15 | 0.199 | 0.199 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00760 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 6928.05 | 6928.05 | 33.41 | 0.299 | 0.299 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00757 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4580.84 | 4580.84 | 34.90 | 0.198 | 0.198 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00759 | -4.20 | 0.00269 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.26 | 4.26 | 1.39 | 1.39 | 4.2627 | 1.3914 | 4.2627 | 0.3264 | 0.3000 |
PACU_VAV_MID | 4.14 | 4.14 | 1.47 | 1.47 | 4.1400 | 1.4662 | 4.1400 | 0.3542 | 0.3000 |
PACU_VAV_TOP | 4.68 | 4.68 | 2.16 | 2.16 | 4.6846 | 2.1580 | 4.6846 | 0.4607 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 12565.026 | 12565.026 | 0.637075 | 0.00010992 | 280.808 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12565.03 | 12565.03 | 0.637075 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 6241.94 | 0.00 | 12608.10 | 12608.10 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 17286.406 | 17286.406 | 0.637812 | 0.00015123 | 421.640 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17286.41 | 17286.41 | 0.637812 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 10956.01 | 0.00 | 17342.10 | 17342.10 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 28713.973 | 28713.973 | 0.866039 | 0.00025120 | 758.393 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 28713.97 | 28713.97 | 0.866039 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 20118.38 | 0.00 | 28816.30 | 28816.30 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 12947.409 | 12947.409 | 0.391642 | 0.00011327 | 341.511 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12947.41 | 12947.41 | 0.391642 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773312 | 49.3031 | 9062.68 | 0.00 | 12990.28 | 12990.28 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 8466.563 | 8466.563 | 0.256122 | 0.00007407 | 223.313 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8466.56 | 8466.56 | 0.256122 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773548 | 49.3180 | 5926.06 | 0.00 | 8494.54 | 8494.54 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 12873.414 | 12873.414 | 0.389399 | 0.00011262 | 339.561 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12873.41 | 12873.41 | 0.389399 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773020 | 49.2847 | 9010.96 | 0.00 | 12916.05 | 12916.05 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 8423.670 | 8423.670 | 0.254822 | 0.00007369 | 222.183 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8423.67 | 8423.67 | 0.254822 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773283 | 49.3013 | 5896.08 | 0.00 | 8451.51 | 8451.51 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 9655.706 | 9655.706 | 0.291883 | 0.00008447 | 254.762 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9655.71 | 9655.71 | 0.291883 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00766120 | 48.8504 | 6760.91 | 0.00 | 9688.22 | 9688.22 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6395.200 | 6395.200 | 0.193340 | 0.00005595 | 168.727 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6395.20 | 6395.20 | 0.193340 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00767539 | 48.9398 | 4477.66 | 0.00 | 6416.68 | 6416.68 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9580.922 | 9580.922 | 0.289617 | 0.00008382 | 252.791 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9580.92 | 9580.92 | 0.289617 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00765558 | 48.8150 | 6708.63 | 0.00 | 9613.20 | 9613.20 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6346.332 | 6346.332 | 0.191860 | 0.00005552 | 167.439 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6346.33 | 6346.33 | 0.191860 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00767014 | 48.9068 | 4443.50 | 0.00 | 6367.66 | 6367.66 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 9976.461 | 9976.461 | 0.301595 | 0.00008728 | 263.219 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9976.46 | 9976.46 | 0.301595 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00757972 | 48.3379 | 6985.89 | 0.00 | 10010.01 | 10010.01 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 6588.455 | 6588.455 | 0.199194 | 0.00005764 | 173.822 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6588.46 | 6588.46 | 0.199194 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00759587 | 48.4397 | 4613.21 | 0.00 | 6610.55 | 6610.55 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 9893.728 | 9893.728 | 0.299089 | 0.00008655 | 261.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9893.73 | 9893.73 | 0.299089 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00757250 | 48.2925 | 6928.05 | 0.00 | 9927.01 | 9927.01 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 6542.143 | 6542.143 | 0.197790 | 0.00005723 | 172.601 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6542.14 | 6542.14 | 0.197790 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00758998 | 48.4026 | 4580.84 | 0.00 | 6564.09 | 6564.09 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 74878.102 | 59937.677 | 4.262737 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 75712.46 | 71289.54 | 4.262737 | 25.21 | 16.95 | 0.00884370 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 22.4293 | 24.00 | 0.00885011 | 46.9387 | 57833.64 | 0.00 | 77209.37 | 60314.51 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 16641.159 | 16641.159 | 1.278821 | 0.00014558 | 282.573 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16641.16 | 16641.16 | 1.278821 | 1.89 | 1.22 | 0.00391323 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 74.7642 | 19.66 | 0.00745216 | 51.6427 | 13378.37 | 0.00 | 16502.62 | 16502.62 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 72957.467 | 58391.607 | 4.139987 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 73794.53 | 69400.71 | 4.139987 | 25.25 | 16.97 | 0.00885163 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 23.0943 | 24.00 | 0.00886068 | 46.9939 | 56168.31 | 0.00 | 75228.94 | 58757.40 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 17193.866 | 17193.866 | 1.241996 | 0.00015042 | 290.674 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17193.87 | 17193.87 | 1.241996 | 1.19 | 0.63 | 0.00378179 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 76.9809 | 19.60 | 0.00718315 | 49.9802 | 17063.71 | 0.00 | 16903.32 | 16903.32 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 81482.814 | 65259.426 | 4.684633 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 82310.11 | 77783.74 | 4.684633 | 25.10 | 16.90 | 0.00881986 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 20.4093 | 24.00 | 0.00881944 | 46.7782 | 63532.12 | 0.00 | 84019.72 | 65672.32 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 16878.672 | 16878.672 | 1.405390 | 0.00014766 | 288.153 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16878.67 | 16878.67 | 1.405390 | 2.73 | 2.13 | 0.00422773 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 68.0309 | 17.60 | 0.00724761 | 57.1523 | 17263.17 | 0.00 | 16916.25 | 16916.25 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 12565.026 | 12565.026 | 0.637075 | 0.00010992 | 280.808 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 5.6769 | 5.791159 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12565.03 | 12565.03 | 1.0000 | 0.75620167 | 0.637075 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.10991312 | 60.00 | 32.22 | 27.78 | 0.000 | 12565.03 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.62 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 6241.94 | 0.00 | 12608.10 | 12608.10 | 0.75620167 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.15 | 17.75 | 0.00800000 | 49732.8 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 17286.406 | 17286.406 | 0.637812 | 0.00015123 | 421.640 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 7.8100 | 7.967220 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17286.41 | 17286.41 | 1.0000 | 0.75707694 | 0.637812 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.15121360 | 60.00 | 32.22 | 27.78 | 0.000 | 17286.41 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 10956.01 | 0.00 | 17342.10 | 17342.10 | 0.75707694 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.26 | 19.74 | 0.00800000 | 55966.5 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 28713.973 | 28713.973 | 0.866039 | 0.00025120 | 758.393 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 12.9730 | 13.234130 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 28713.97 | 28713.97 | 1.0000 | 1.02798041 | 0.866039 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.25117674 | 60.00 | 32.22 | 27.78 | 0.000 | 28713.97 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 20118.38 | 0.00 | 28816.30 | 28816.30 | 1.02798041 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.29 | 21.27 | 0.00800000 | 61091.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12947.409 | 12947.409 | 0.391642 | 0.00011327 | 341.511 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 5.8497 | 5.967397 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12947.41 | 12947.41 | 1.0000 | 0.46487595 | 0.391642 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.11325803 | 60.00 | 32.22 | 27.78 | 0.000 | 12947.41 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00773312 | 21.00 | 0.00773312 | 49.3031 | 9062.68 | 0.00 | 12990.28 | 12990.28 | 0.46487595 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61003.4 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8466.563 | 8466.563 | 0.256122 | 0.00007407 | 223.313 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 3.8252 | 3.902198 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8466.56 | 8466.56 | 1.0000 | 0.30401439 | 0.256122 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.07406163 | 60.00 | 32.22 | 27.78 | 0.000 | 8466.56 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00773548 | 21.00 | 0.00773548 | 49.3180 | 5926.06 | 0.00 | 8494.54 | 8494.54 | 0.30401439 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61001.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12873.414 | 12873.414 | 0.389399 | 0.00011262 | 339.561 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 5.8162 | 5.933294 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12873.41 | 12873.41 | 1.0000 | 0.46221324 | 0.389399 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.11261075 | 60.00 | 32.22 | 27.78 | 0.000 | 12873.41 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00773020 | 21.00 | 0.00773020 | 49.2847 | 9010.96 | 0.00 | 12916.05 | 12916.05 | 0.46221324 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61003.8 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8423.670 | 8423.670 | 0.254822 | 0.00007369 | 222.183 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 3.8058 | 3.882428 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8423.67 | 8423.67 | 1.0000 | 0.30247094 | 0.254822 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.07368642 | 60.00 | 32.22 | 27.78 | 0.000 | 8423.67 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00773283 | 21.00 | 0.00773283 | 49.3013 | 5896.08 | 0.00 | 8451.51 | 8451.51 | 0.30247094 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61001.4 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9655.706 | 9655.706 | 0.291883 | 0.00008447 | 254.762 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 4.3625 | 4.450268 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9655.71 | 9655.71 | 1.0000 | 0.34646246 | 0.291883 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08446371 | 60.00 | 32.22 | 27.78 | 0.000 | 9655.71 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00766120 | 21.00 | 0.00766120 | 48.8504 | 6760.91 | 0.00 | 9688.22 | 9688.22 | 0.34646246 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61023.1 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6395.200 | 6395.200 | 0.193340 | 0.00005595 | 168.727 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 2.8894 | 2.947516 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6395.20 | 6395.20 | 1.0000 | 0.22949327 | 0.193340 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.05594229 | 60.00 | 32.22 | 27.78 | 0.000 | 6395.20 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00767539 | 21.00 | 0.00767539 | 48.9398 | 4477.66 | 0.00 | 6416.68 | 6416.68 | 0.22949327 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61020.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9580.922 | 9580.922 | 0.289617 | 0.00008382 | 252.791 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 4.3287 | 4.415800 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9580.92 | 9580.92 | 1.0000 | 0.34377305 | 0.289617 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08380953 | 60.00 | 32.22 | 27.78 | 0.000 | 9580.92 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00765558 | 21.00 | 0.00765558 | 48.8150 | 6708.63 | 0.00 | 9613.20 | 9613.20 | 0.34377305 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61023.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6346.332 | 6346.332 | 0.191860 | 0.00005552 | 167.439 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 2.8673 | 2.924993 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6346.33 | 6346.33 | 1.0000 | 0.22773620 | 0.191860 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.05551482 | 60.00 | 32.22 | 27.78 | 0.000 | 6346.33 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00767014 | 21.00 | 0.00767014 | 48.9068 | 4443.50 | 0.00 | 6367.66 | 6367.66 | 0.22773620 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61020.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9976.461 | 9976.461 | 0.301595 | 0.00008728 | 263.219 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 4.5074 | 4.598102 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9976.46 | 9976.46 | 1.0000 | 0.35799031 | 0.301595 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08726953 | 60.00 | 32.22 | 27.78 | 0.000 | 9976.46 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00757972 | 21.00 | 0.00757972 | 48.3379 | 6985.89 | 0.00 | 10010.01 | 10010.01 | 0.35799031 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61021.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6588.455 | 6588.455 | 0.199194 | 0.00005764 | 173.822 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 2.9767 | 3.036587 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6588.46 | 6588.46 | 1.0000 | 0.23644173 | 0.199194 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.05763280 | 60.00 | 32.22 | 27.78 | 0.000 | 6588.46 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00759587 | 21.00 | 0.00759587 | 48.4397 | 4613.21 | 0.00 | 6610.55 | 6610.55 | 0.23644173 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61018.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9893.728 | 9893.728 | 0.299089 | 0.00008655 | 261.038 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 4.4700 | 4.559971 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9893.73 | 9893.73 | 1.0000 | 0.35501593 | 0.299089 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08654582 | 60.00 | 32.22 | 27.78 | 0.000 | 9893.73 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00757250 | 21.00 | 0.00757250 | 48.2925 | 6928.05 | 0.00 | 9927.01 | 9927.01 | 0.35501593 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61022.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6542.143 | 6542.143 | 0.197790 | 0.00005723 | 172.601 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 2.9558 | 3.015242 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6542.14 | 6542.14 | 1.0000 | 0.23477546 | 0.197790 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.05722768 | 60.00 | 32.22 | 27.78 | 0.000 | 6542.14 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00758998 | 21.00 | 0.00758998 | 48.4026 | 4580.84 | 0.00 | 6564.09 | 6564.09 | 0.23477546 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61018.9 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 74878.102 | 59937.677 | 4.262737 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2800 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.262737 | 5.05982979 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 75712.46 | 71289.54 | 1.0111 | 5.05982979 | 4.262737 | 25.21 | 16.95 | 0.00884370 | 47864.3 | 10.99 | 10.99 | 0.00850000 | 32479.2 | -999.0 | -999.00 | -999.00 | -999.00 | 9331.179 | 66381.28 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 22.4293 | 24.00 | 0.00885011 | 24.00 | 0.00885011 | 46.9387 | 57833.64 | 0.00 | 77209.37 | 60314.51 | 4.86000476 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.54 | 14.07 | 0.00982168 | 39435.7 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16641.159 | 16641.159 | 1.278821 | 0.00014558 | 282.573 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.262737 | 5.05982979 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 7.5185 | 7.669829 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16641.16 | 16641.16 | 1.0000 | 1.51794894 | 1.278821 | 1.89 | 1.22 | 0.00391323 | 11699.7 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.14556927 | 60.00 | 32.22 | 27.78 | 0.000 | 16641.16 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 74.7642 | 19.93 | 0.00753625 | 19.66 | 0.00745216 | 51.6427 | 13378.37 | 0.00 | 16502.62 | 16502.62 | 1.51794894 | 2.80 | 1.82 | 0.00391323 | 12620.7 | 13.54 | 7.44 | 0.00391323 | 23492.3 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 72957.467 | 58391.607 | 4.139987 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2947 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.139987 | 4.91412622 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 73794.53 | 69400.71 | 1.0115 | 4.91412622 | 4.139987 | 25.25 | 16.97 | 0.00885163 | 47921.2 | 10.99 | 10.99 | 0.00850000 | 32479.2 | -999.0 | -999.00 | -999.00 | -999.00 | 9062.477 | 64732.05 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 23.0943 | 24.00 | 0.00886068 | 24.00 | 0.00886068 | 46.9939 | 56168.31 | 0.00 | 75228.94 | 58757.40 | 4.72005538 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.50 | 14.05 | 0.00981643 | 39384.2 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 17193.866 | 17193.866 | 1.241996 | 0.00015042 | 290.674 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.139987 | 4.91412622 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 7.7682 | 7.924569 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17193.87 | 17193.87 | 1.0000 | 1.47423787 | 1.241996 | 1.19 | 0.63 | 0.00378179 | 10665.7 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.15040410 | 60.00 | 32.22 | 27.78 | 0.000 | 17193.87 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 76.9809 | 19.23 | 0.00743194 | 19.60 | 0.00718315 | 49.9802 | 17063.71 | 0.00 | 16903.32 | 16903.32 | 1.47423787 | 2.80 | 1.64 | 0.00378179 | 12291.3 | 14.13 | 7.57 | 0.00378179 | 23757.1 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 81482.814 | 65259.426 | 4.684633 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2357 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.684633 | 5.56061628 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 82310.11 | 77783.74 | 1.0102 | 5.56061628 | 4.684633 | 25.10 | 16.90 | 0.00881986 | 47692.6 | 10.99 | 10.99 | 0.00850000 | 32479.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10254.713 | 72055.39 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 20.4093 | 24.00 | 0.00881944 | 24.00 | 0.00881944 | 46.7782 | 63532.12 | 0.00 | 84019.72 | 65672.32 | 5.34101397 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 14.13 | 0.00983780 | 39591.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16878.672 | 16878.672 | 1.405390 | 0.00014766 | 288.153 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.684633 | 5.56061628 | 4197.9300 | 999.8980 | 1.89794677 | 54.44 | 82.22 | 27.78 | 221335.70 | 7.6258 | 7.779297 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16878.67 | 16878.67 | 1.0000 | 1.66818488 | 1.405390 | 2.73 | 2.13 | 0.00422773 | 13338.9 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.14764693 | 60.00 | 32.22 | 27.78 | 0.000 | 16878.67 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 68.0309 | 17.48 | 0.00749938 | 17.60 | 0.00724761 | 57.1523 | 17263.17 | 0.00 | 16916.25 | 16916.25 | 1.66818488 | 2.80 | 2.26 | 0.00422773 | 13408.9 | 12.81 | 7.46 | 0.00422773 | 23549.4 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.26 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.14 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.68 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1568.33 | 2523.50 | 36.33 |
CORE_MID | 1182.50 | 3353.33 | 180.50 |
CORE_TOP | 1427.33 | 3844.67 | 624.33 |
PERIMETER_TOP_ZN_3 | 2154.00 | 4230.17 | 1345.00 |
PERIMETER_TOP_ZN_2 | 2499.50 | 3807.83 | 1214.00 |
PERIMETER_TOP_ZN_1 | 2425.50 | 3670.00 | 1043.00 |
PERIMETER_TOP_ZN_4 | 2489.17 | 3956.67 | 1282.00 |
PERIMETER_BOT_ZN_3 | 1640.00 | 4357.67 | 1050.00 |
PERIMETER_BOT_ZN_2 | 2160.67 | 3699.00 | 895.33 |
PERIMETER_BOT_ZN_1 | 2118.17 | 3916.33 | 922.00 |
PERIMETER_BOT_ZN_4 | 2202.83 | 3708.00 | 910.50 |
PERIMETER_MID_ZN_3 | 1797.83 | 3918.50 | 907.17 |
PERIMETER_MID_ZN_2 | 1886.00 | 3097.67 | 780.33 |
PERIMETER_MID_ZN_1 | 2187.00 | 3308.50 | 661.00 |
PERIMETER_MID_ZN_4 | 2187.33 | 3634.50 | 859.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 3881.50 | 4699.50 | 1587.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 7.67 | 0.00 | 7.67 | 0.00 |
CORE_MID | 4.33 | 0.00 | 4.33 | 0.00 |
CORE_TOP | 5.67 | 0.00 | 5.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 16.67 | 0.00 | 15.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 9.00 | 13.00 | 6.50 | 13.00 |
PERIMETER_TOP_ZN_1 | 5.50 | 15.50 | 4.83 | 15.17 |
PERIMETER_TOP_ZN_4 | 7.83 | 21.83 | 5.67 | 13.33 |
PERIMETER_BOT_ZN_3 | 6.67 | 0.00 | 6.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 4.33 | 8.17 | 3.83 | 8.17 |
PERIMETER_BOT_ZN_1 | 319.83 | 7.67 | 319.83 | 7.67 |
PERIMETER_BOT_ZN_4 | 4.67 | 13.17 | 3.83 | 6.67 |
PERIMETER_MID_ZN_3 | 5.17 | 0.00 | 5.00 | 0.00 |
PERIMETER_MID_ZN_2 | 3.33 | 12.00 | 3.17 | 12.00 |
PERIMETER_MID_ZN_1 | 2.83 | 15.67 | 2.67 | 15.67 |
PERIMETER_MID_ZN_4 | 3.33 | 20.33 | 3.17 | 12.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 332.67 | 89.00 | 328.83 | 71.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.56 | 52.94 | 2698.04 | 0.836 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.56 | 52.94 | 2698.04 | 0.672 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.56 | 52.94 | 2698.04 | 0.656 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.54 | 11.16 | 568.77 | 0.716 | 0.035 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.88 | 7.07 | 360.08 | 1.037 | 0.037 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.54 | 11.16 | 568.77 | 1.128 | 0.036 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.88 | 7.06 | 360.05 | 1.036 | 0.037 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.54 | 11.16 | 568.77 | 0.622 | 0.019 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.88 | 7.07 | 360.08 | 0.923 | 0.020 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.54 | 11.16 | 568.77 | 0.914 | 0.829 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.88 | 7.06 | 360.05 | 0.907 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.54 | 11.16 | 568.77 | 0.722 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.52 | 7.07 | 360.08 | 0.947 | 0.033 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.54 | 11.16 | 568.77 | 1.139 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.88 | 7.06 | 360.05 | 1.031 | 0.031 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.56 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.56 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.56 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.88 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.88 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.88 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.88 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.52 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.88 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.56 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.56 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.56 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.88 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.88 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.88 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.88 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.52 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.88 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.84 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 13187058.21 | 0.00 | 13187058.21 | 0.00 | 13187058.21 | 13393058.27 | 4662.94 | 584.51 | 3512.56 | 40.88 |
CORE_MID | 10644995.60 | 0.00 | 10644995.60 | 0.00 | 10644995.60 | 13393058.27 | 4553.57 | 1099.23 | 3107.20 | 46.81 |
CORE_TOP | 10402485.18 | 0.00 | 10402485.18 | 0.00 | 10402485.18 | 13393058.27 | 4601.18 | 1303.45 | 2855.36 | 45.06 |
PERIMETER_TOP_ZN_3 | 2395648.94 | 0.00 | 2395648.94 | 242662.85 | 2638311.79 | 2823374.22 | 4479.59 | 1398.21 | 2882.20 | 45.06 |
PERIMETER_TOP_ZN_2 | 2188317.05 | 0.00 | 2188317.05 | 161774.26 | 2350091.32 | 1787429.43 | 4328.97 | 1064.39 | 3366.65 | 45.06 |
PERIMETER_TOP_ZN_1 | 3758535.32 | 0.00 | 3758535.32 | 242662.85 | 4001198.17 | 2823374.22 | 4273.73 | 1064.14 | 3422.13 | 45.06 |
PERIMETER_TOP_ZN_4 | 2200742.66 | 0.00 | 2200742.66 | 161774.26 | 2362516.92 | 1787312.18 | 4401.69 | 1234.26 | 3124.05 | 45.06 |
PERIMETER_BOT_ZN_3 | 2079832.69 | 0.00 | 2079832.69 | 129022.55 | 2208855.24 | 2823374.22 | 5154.77 | 726.38 | 2878.85 | 40.88 |
PERIMETER_BOT_ZN_2 | 1945167.64 | 0.00 | 1945167.64 | 86014.52 | 2031182.16 | 1787429.43 | 4930.56 | 661.84 | 3167.60 | 40.88 |
PERIMETER_BOT_ZN_1 | 3052402.53 | 0.00 | 3052402.53 | 2835943.55 | 5888346.08 | 2823374.22 | 4594.53 | 685.44 | 3480.02 | 40.88 |
PERIMETER_BOT_ZN_4 | 1917978.79 | 0.00 | 1917978.79 | 86014.52 | 2003993.31 | 1787312.18 | 5012.64 | 792.58 | 2954.78 | 40.88 |
PERIMETER_MID_ZN_3 | 2409379.64 | 0.00 | 2409379.64 | 201998.19 | 2611377.83 | 2823374.22 | 4488.39 | 1100.29 | 3171.32 | 46.81 |
PERIMETER_MID_ZN_2 | 2022058.98 | 0.00 | 2022058.98 | 134664.65 | 2156723.63 | 1601953.02 | 4299.92 | 1024.05 | 3436.02 | 955.81 |
PERIMETER_MID_ZN_1 | 3788862.55 | 0.00 | 3788862.55 | 201998.19 | 3990860.74 | 2823374.22 | 4292.58 | 1240.79 | 3226.62 | 46.81 |
PERIMETER_MID_ZN_4 | 2184995.12 | 0.00 | 2184995.12 | 134664.65 | 2319659.77 | 1787312.18 | 4416.09 | 990.85 | 3353.06 | 46.81 |
Total Facility | 64178460.91 | 0.00 | 64178460.91 | 4619195.04 | 68797655.95 | 67658168.57 | 5420.01 | 1668.08 | 4257.16 | 977.65 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6130 | 0.0000 | 0.6130 | 0.0000 | 0.6130 | 0.4247 | 1876.10 | 584.51 | 3482.39 |
CORE_MID | 0.4937 | 0.0000 | 0.4937 | 0.0000 | 0.4937 | 0.4247 | 1772.38 | 1099.23 | 3071.39 |
CORE_TOP | 0.4819 | 0.0000 | 0.4819 | 0.0000 | 0.4819 | 0.4247 | 1824.52 | 1303.45 | 2815.03 |
PERIMETER_TOP_ZN_3 | 0.1111 | 0.0000 | 0.1111 | 0.0055 | 0.1166 | 0.0895 | 1702.93 | 1398.21 | 2841.87 |
PERIMETER_TOP_ZN_2 | 0.1017 | 0.0000 | 0.1017 | 0.0037 | 0.1054 | 0.0567 | 1552.30 | 1064.39 | 3326.32 |
PERIMETER_TOP_ZN_1 | 0.1747 | 0.0000 | 0.1747 | 0.0055 | 0.1803 | 0.0895 | 1497.06 | 1064.14 | 3381.80 |
PERIMETER_TOP_ZN_4 | 0.1016 | 0.0000 | 0.1016 | 0.0037 | 0.1052 | 0.0567 | 1625.03 | 1234.26 | 3083.71 |
PERIMETER_BOT_ZN_3 | 0.0965 | 0.0000 | 0.0965 | 0.0029 | 0.0994 | 0.0895 | 2367.94 | 726.38 | 2848.69 |
PERIMETER_BOT_ZN_2 | 0.0905 | 0.0000 | 0.0905 | 0.0020 | 0.0924 | 0.0567 | 2143.72 | 661.84 | 3137.43 |
PERIMETER_BOT_ZN_1 | 0.1420 | 0.0000 | 0.1420 | 0.1295 | 0.2714 | 0.0895 | 1807.70 | 685.44 | 3449.86 |
PERIMETER_BOT_ZN_4 | 0.0889 | 0.0000 | 0.0889 | 0.0020 | 0.0908 | 0.0567 | 2225.81 | 792.58 | 2924.61 |
PERIMETER_MID_ZN_3 | 0.1118 | 0.0000 | 0.1118 | 0.0046 | 0.1164 | 0.0895 | 1707.20 | 1100.29 | 3135.51 |
PERIMETER_MID_ZN_2 | 0.0928 | 0.0000 | 0.0928 | 0.0033 | 0.0961 | 0.0567 | 1518.74 | 1024.05 | 2491.21 |
PERIMETER_MID_ZN_1 | 0.1763 | 0.0000 | 0.1763 | 0.0046 | 0.1809 | 0.0895 | 1511.39 | 1240.79 | 3190.81 |
PERIMETER_MID_ZN_4 | 0.1011 | 0.0000 | 0.1011 | 0.0031 | 0.1041 | 0.0567 | 1634.90 | 990.85 | 3317.25 |
Total Facility | 2.9774 | 0.0000 | 2.9774 | 0.1702 | 3.1476 | 2.1513 | 2620.76 | 1668.08 | 4206.68 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 31253884.78 | 0.00 | 31253884.78 | 22614548.33 | 4096.45 | 5.71 | 4657.84 | 40.88 |
PACU_VAV_MID | 29658748.13 | 0.00 | 29658748.13 | 22429071.92 | 4068.45 | 2.17 | 4689.37 | 46.81 |
PACU_VAV_TOP | 29511424.75 | 0.00 | 29511424.75 | 22614548.33 | 4096.30 | 6.12 | 4657.58 | 45.06 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.4524 | 0.0000 | 1.4524 | 0.7171 | 1309.62 | 5.71 | 4627.67 |
PACU_VAV_MID | 1.3763 | 0.0000 | 1.3763 | 0.7084 | 1287.27 | 2.17 | 4653.56 |
PACU_VAV_TOP | 1.3680 | 0.0000 | 1.3680 | 0.7171 | 1319.64 | 6.12 | 4617.24 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 69.22 | 3017.68 | 0.00 | 0.00 | 0.00 | 1686.47 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 38.76 | 2890.19 | 0.00 | 0.00 | 0.00 | 1889.33 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 30.03 | 2811.89 | 0.00 | 0.00 | 0.00 | 1971.60 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2710 | 2.2584 | 0.0000 | 0.0000 | 0.0000 | 1.0813 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2413 | 2.1779 | 0.0000 | 0.0000 | 0.0000 | 1.0271 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.1620 | 2.1904 | 0.0000 | 0.0000 | 0.0000 | 1.0333 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1010 |
Defaulted Fields | 582 |
Fields with Defaults | 2434 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1069.59 | 11981.96 | 30-APR-17:10 | 128668.41 | 10-AUG-15:10 |
Electricity:Building | 826.71 | 11650.06 | 09-APR-17:10 | 56534.15 | 02-JAN-16:30 |
Electricity:Zone:CORE_BOTTOM | 229.44 | 3625.33 | 01-JAN-00:10 | 14695.26 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 826.71 | 11650.06 | 09-APR-17:10 | 56534.15 | 02-JAN-16:30 |
InteriorLights:Electricity | 167.80 | 772.31 | 08-JAN-10:30 | 17672.30 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 167.80 | 772.31 | 08-JAN-10:30 | 17672.30 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 167.80 | 772.31 | 08-JAN-10:30 | 17672.30 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 167.80 | 772.31 | 08-JAN-10:30 | 17672.30 | 02-JAN-16:30 |
Electricity:Zone:CORE_MID | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.33 | 405.59 | 19-MAR-17:10 | 2170.70 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.00 | 19.49 | 08-JAN-10:30 | 735.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.00 | 19.49 | 08-JAN-10:30 | 735.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.53 | 256.76 | 09-APR-17:10 | 1374.17 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.13 | 12.34 | 01-JAN-09:50 | 465.60 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.13 | 12.34 | 01-JAN-09:50 | 465.60 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.23 | 405.59 | 19-MAR-17:10 | 2170.69 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.90 | 19.49 | 01-JAN-09:50 | 735.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.90 | 19.49 | 01-JAN-09:50 | 735.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.53 | 256.75 | 19-MAR-17:10 | 1374.14 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.13 | 12.34 | 01-JAN-13:00 | 465.57 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.13 | 12.34 | 01-JAN-13:00 | 465.57 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.31 | 405.59 | 19-MAR-17:10 | 2170.70 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.98 | 19.49 | 08-JAN-10:20 | 735.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.98 | 19.49 | 08-JAN-10:20 | 735.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.53 | 256.76 | 09-APR-17:10 | 1374.17 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.12 | 12.34 | 01-JAN-09:50 | 465.60 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.12 | 12.34 | 01-JAN-09:50 | 465.60 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.22 | 405.59 | 19-MAR-17:10 | 2170.69 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.89 | 19.49 | 01-JAN-09:50 | 735.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.89 | 19.49 | 01-JAN-09:50 | 735.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.52 | 256.75 | 19-MAR-17:10 | 1374.14 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.12 | 12.34 | 01-JAN-10:30 | 465.57 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.12 | 12.34 | 01-JAN-10:30 | 465.57 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.33 | 405.59 | 19-MAR-17:10 | 2170.70 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.00 | 19.49 | 08-JAN-10:30 | 735.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.00 | 19.49 | 08-JAN-10:30 | 735.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.53 | 256.76 | 09-APR-17:10 | 1374.17 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.13 | 12.34 | 01-JAN-09:50 | 465.60 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.13 | 12.34 | 01-JAN-09:50 | 465.60 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.23 | 405.59 | 19-MAR-17:10 | 2170.69 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.90 | 19.49 | 01-JAN-09:50 | 735.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.90 | 19.49 | 01-JAN-09:50 | 735.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.53 | 256.75 | 19-MAR-17:10 | 1374.14 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.13 | 12.34 | 01-JAN-13:00 | 465.57 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.13 | 12.34 | 01-JAN-13:00 | 465.57 | 02-JAN-16:30 |
InteriorEquipment:Electricity | 658.91 | 10877.75 | 01-JAN-00:10 | 38886.07 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 189.64 | 3431.54 | 01-JAN-00:10 | 11206.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 658.91 | 10877.75 | 01-JAN-00:10 | 38886.07 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 73.68 | 1600.00 | 01-JAN-00:10 | 4325.57 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 73.68 | 1600.00 | 01-JAN-00:10 | 4325.57 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 73.68 | 1600.00 | 01-JAN-00:10 | 4325.57 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElectricityProduced:Facility | 118.15 | -0.00 | 15-FEB-07:30 | 26813.75 | 10-MAY-11:30 |
ElectricityProduced:Plant | 118.15 | -0.00 | 15-FEB-07:30 | 26813.75 | 10-MAY-11:30 |
Photovoltaic:ElectricityProduced | 123.93 | 0.00 | 01-JAN-00:10 | 28856.33 | 18-MAY-11:30 |
PowerConversion:ElectricityProduced | -5.79 | -2042.58 | 18-MAY-11:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 55.58 | 0.00 | 01-JAN-01:30 | 6847.83 | 13-FEB-12:20 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 152.71 | 331.90 | 15-JUL-18:20 | 71665.46 | 10-AUG-15:10 |
ExteriorEquipment:Electricity | 25.33 | 331.43 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:10 |
Transformer:ExteriorEquipment:Electricity | 25.33 | 331.43 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:10 |
ElectricityPurchased:Facility | 951.96 | 0.00 | 19-MAR-12:20 | 115552.18 | 29-AUG-15:30 |
ElectricityPurchased:Plant | 951.96 | 0.00 | 19-MAR-12:20 | 115552.18 | 29-AUG-15:30 |
Cogeneration:ElectricityPurchased | 951.96 | 0.00 | 19-MAR-12:20 | 115552.18 | 29-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 951.96 | 0.00 | 19-MAR-12:20 | 115552.18 | 29-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.51 | 0.00 | 01-JAN-00:10 | 9135.04 | 21-MAY-12:40 |
ElectricitySurplusSold:Plant | 0.51 | 0.00 | 01-JAN-00:10 | 9135.04 | 21-MAY-12:40 |
Cogeneration:ElectricitySurplusSold | 0.51 | 0.00 | 01-JAN-00:10 | 9135.04 | 21-MAY-12:40 |
General:Cogeneration:ElectricitySurplusSold | 0.51 | 0.00 | 01-JAN-00:10 | 9135.04 | 21-MAY-12:40 |
ElectricityNet:Facility | 951.44 | -9135.04 | 21-MAY-12:40 | 115552.18 | 29-AUG-15:30 |
ElectricityNet:Plant | 951.44 | -9135.04 | 21-MAY-12:40 | 115552.18 | 29-AUG-15:30 |
Cogeneration:ElectricityNet | 951.44 | -9135.04 | 21-MAY-12:40 | 115552.18 | 29-AUG-15:30 |
General:Cogeneration:ElectricityNet | 951.44 | -9135.04 | 21-MAY-12:40 | 115552.18 | 29-AUG-15:30 |
Fans:Electricity | 67.06 | 0.00 | 01-JAN-00:50 | 25430.22 | 14-AUG-15:20 |
General:Fans:Electricity | 67.06 | 0.00 | 01-JAN-00:50 | 25430.22 | 14-AUG-15:20 |
ExteriorLights:Electricity | 34.59 | 0.00 | 01-JAN-08:10 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 34.59 | 0.00 | 01-JAN-08:10 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 60.32 | 0.00 | 01-JAN-00:10 | 46477.71 | 29-AUG-15:30 |
General:Cooling:Electricity | 60.32 | 0.00 | 01-JAN-00:10 | 46477.71 | 29-AUG-15:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 54.31 | 0.00 | 01-JAN-00:10 | 6517.00 | 13-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 54.31 | 0.00 | 01-JAN-00:10 | 6517.00 | 13-FEB-12:20 |
Pumps:Electricity | 1.27 | 0.00 | 01-JAN-00:50 | 525.05 | 26-DEC-07:10 |
General:Pumps:Electricity | 1.27 | 0.00 | 01-JAN-00:50 | 525.05 | 26-DEC-07:10 |
WIRED_LTG_ELECTRICITY | 4.72 | 0.00 | 01-JAN-00:10 | 496.59 | 02-JAN-16:40 |
WIRED_INT_EQUIP1 | 632.98 | 10877.75 | 01-JAN-00:10 | 36042.38 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 611.16 | 9277.75 | 01-JAN-00:10 | 37604.10 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 221.46 | 0.00 | 01-JAN-00:50 | 168245.32 | 26-DEC-07:20 |
NaturalGas:Plant | 221.46 | 0.00 | 01-JAN-00:50 | 168245.32 | 26-DEC-07:20 |
Heating:NaturalGas | 221.46 | 0.00 | 01-JAN-00:50 | 168245.32 | 26-DEC-07:20 |
Boiler:Heating:NaturalGas | 221.46 | 0.00 | 01-JAN-00:50 | 168245.32 | 26-DEC-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1476.25 | 0.00 | 01-JAN-00:50 | 375169.85 | 26-DEC-07:20 |
EnergyTransfer:Building | 822.87 | 0.00 | 01-JAN-00:50 | 144349.38 | 14-AUG-15:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 164.70 | 0.00 | 01-JAN-00:40 | 19747.78 | 14-AUG-07:50 |
Heating:EnergyTransfer | 61.92 | 0.00 | 01-JAN-00:50 | 116301.48 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.20 | 0.00 | 01-JAN-00:10 | 6692.78 | 02-JAN-06:20 |
General:Heating:EnergyTransfer | 61.92 | 0.00 | 01-JAN-00:50 | 116301.48 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.20 | 0.00 | 01-JAN-00:10 | 6692.78 | 02-JAN-06:20 |
Cooling:EnergyTransfer | 760.96 | 0.00 | 01-JAN-00:50 | 144349.38 | 14-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 164.50 | 0.00 | 01-JAN-00:40 | 19747.78 | 14-AUG-07:50 |
General:Cooling:EnergyTransfer | 760.96 | 0.00 | 01-JAN-00:50 | 144349.38 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 164.50 | 0.00 | 01-JAN-00:40 | 19747.78 | 14-AUG-07:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.11 | 0.00 | 01-JAN-00:10 | 9124.70 | 10-AUG-14:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 11.88 | 0.00 | 01-JAN-00:10 | 9070.51 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 11.88 | 0.00 | 01-JAN-00:10 | 9070.51 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 19.23 | 0.00 | 01-JAN-00:10 | 9124.70 | 10-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 19.23 | 0.00 | 01-JAN-00:10 | 9124.70 | 10-AUG-14:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.20 | 0.00 | 01-JAN-00:10 | 7923.55 | 02-JAN-09:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.95 | 0.00 | 01-JAN-00:10 | 7923.55 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.95 | 0.00 | 01-JAN-00:10 | 7923.55 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.25 | 0.00 | 01-JAN-00:10 | 4265.51 | 14-AUG-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.25 | 0.00 | 01-JAN-00:10 | 4265.51 | 14-AUG-14:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.53 | 0.00 | 01-JAN-00:40 | 6230.52 | 02-JAN-10:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.52 | 0.00 | 01-JAN-00:40 | 6230.52 | 02-JAN-10:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.52 | 0.00 | 01-JAN-00:40 | 6230.52 | 02-JAN-10:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 14.01 | 0.00 | 01-JAN-00:10 | 4410.08 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 14.01 | 0.00 | 01-JAN-00:10 | 4410.08 | 14-AUG-15:20 |
EnergyTransfer:Zone:CORE_MID | 125.43 | 0.00 | 01-JAN-00:10 | 16441.28 | 14-AUG-07:30 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.57 | 0.00 | 01-JAN-00:10 | 11212.26 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.57 | 0.00 | 01-JAN-00:10 | 11212.26 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 124.86 | 0.00 | 01-JAN-00:10 | 16441.28 | 14-AUG-07:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 124.86 | 0.00 | 01-JAN-00:10 | 16441.28 | 14-AUG-07:30 |
EnergyTransfer:Zone:CORE_TOP | 115.70 | 0.00 | 01-JAN-00:10 | 17739.68 | 24-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 2.39 | 0.00 | 01-JAN-00:10 | 17667.75 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 2.39 | 0.00 | 01-JAN-00:10 | 17667.75 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 113.32 | 0.00 | 01-JAN-00:10 | 17739.68 | 24-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 113.32 | 0.00 | 01-JAN-00:10 | 17739.68 | 24-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 27.83 | 0.00 | 01-JAN-00:10 | 6310.53 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 5.02 | 0.00 | 01-JAN-00:10 | 6310.53 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 5.02 | 0.00 | 01-JAN-00:10 | 6310.53 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.82 | 0.00 | 01-JAN-00:10 | 6011.37 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.82 | 0.00 | 01-JAN-00:10 | 6011.37 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.59 | 0.00 | 01-JAN-00:10 | 8756.46 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 2.97 | 0.00 | 01-JAN-00:10 | 5322.44 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 2.97 | 0.00 | 01-JAN-00:10 | 5322.44 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.62 | 0.00 | 01-JAN-00:10 | 8756.46 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.62 | 0.00 | 01-JAN-00:10 | 8756.46 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.54 | 0.00 | 01-JAN-00:10 | 13250.78 | 04-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 3.69 | 0.00 | 01-JAN-00:10 | 8058.20 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 3.69 | 0.00 | 01-JAN-00:10 | 8058.20 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 40.85 | 0.00 | 01-JAN-00:10 | 13250.78 | 04-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 40.85 | 0.00 | 01-JAN-00:10 | 13250.78 | 04-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 26.22 | 0.00 | 01-JAN-00:10 | 9329.51 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.12 | 0.00 | 01-JAN-00:10 | 5411.63 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.12 | 0.00 | 01-JAN-00:10 | 5411.63 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.10 | 0.00 | 01-JAN-00:10 | 9329.51 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.10 | 0.00 | 01-JAN-00:10 | 9329.51 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.82 | 0.00 | 01-JAN-00:40 | 4891.55 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.49 | 0.00 | 01-JAN-00:40 | 4891.55 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.49 | 0.00 | 01-JAN-00:40 | 4891.55 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.33 | 0.00 | 01-JAN-00:20 | 4566.76 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.33 | 0.00 | 01-JAN-00:20 | 4566.76 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.30 | 0.00 | 01-JAN-00:40 | 7078.53 | 24-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.44 | 0.00 | 01-JAN-00:40 | 4220.69 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.44 | 0.00 | 01-JAN-00:40 | 4220.69 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.86 | 0.00 | 01-JAN-00:20 | 7078.53 | 24-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.86 | 0.00 | 01-JAN-00:20 | 7078.53 | 24-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 39.49 | 0.00 | 01-JAN-00:40 | 12412.45 | 10-AUG-16:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 11.44 | 0.00 | 01-JAN-00:40 | 7954.06 | 26-DEC-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 11.44 | 0.00 | 01-JAN-00:40 | 7954.06 | 26-DEC-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.05 | 0.00 | 01-JAN-00:20 | 12412.45 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.05 | 0.00 | 01-JAN-00:20 | 12412.45 | 10-AUG-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.39 | 0.00 | 01-JAN-00:40 | 7582.92 | 31-JUL-17:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.45 | 0.00 | 01-JAN-00:40 | 4298.27 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.45 | 0.00 | 01-JAN-00:40 | 4298.27 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.94 | 0.00 | 01-JAN-00:20 | 7582.92 | 31-JUL-17:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.94 | 0.00 | 01-JAN-00:20 | 7582.92 | 31-JUL-17:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.85 | 0.00 | 01-JAN-00:10 | 5509.99 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1.95 | 0.00 | 01-JAN-00:10 | 5196.90 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1.95 | 0.00 | 01-JAN-00:10 | 5196.90 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.90 | 0.00 | 01-JAN-00:10 | 5509.99 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.90 | 0.00 | 01-JAN-00:10 | 5509.99 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.59 | 0.00 | 01-JAN-00:10 | 8805.54 | 31-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.21 | 0.00 | 01-JAN-00:10 | 4481.92 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.21 | 0.00 | 01-JAN-00:10 | 4481.92 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 22.38 | 0.00 | 01-JAN-00:10 | 8805.54 | 31-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 22.38 | 0.00 | 01-JAN-00:10 | 8805.54 | 31-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 44.95 | 0.00 | 01-JAN-00:10 | 13197.87 | 04-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.40 | 0.00 | 01-JAN-00:10 | 6643.43 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.40 | 0.00 | 01-JAN-00:10 | 6643.43 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 43.54 | 0.00 | 01-JAN-00:10 | 13197.87 | 04-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 43.54 | 0.00 | 01-JAN-00:10 | 13197.87 | 04-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 25.63 | 0.00 | 01-JAN-00:10 | 8938.42 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.22 | 0.00 | 01-JAN-00:10 | 4470.49 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.22 | 0.00 | 01-JAN-00:10 | 4470.49 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 24.41 | 0.00 | 01-JAN-00:10 | 8938.42 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 24.41 | 0.00 | 01-JAN-00:10 | 8938.42 | 10-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 213.58 | 0.00 | 01-JAN-00:50 | 143628.40 | 26-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
EnergyTransfer:HVAC | 441.02 | 0.00 | 01-JAN-00:50 | 196702.85 | 31-JUL-14:30 |
HeatingCoils:EnergyTransfer | 162.09 | 0.00 | 01-JAN-00:50 | 141591.22 | 26-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 162.09 | 0.00 | 01-JAN-00:50 | 141591.22 | 26-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 162.09 | 0.00 | 01-JAN-00:50 | 141591.22 | 26-DEC-07:10 |
CoolingCoils:EnergyTransfer | 278.93 | 0.00 | 01-JAN-00:10 | 196692.70 | 31-JUL-14:30 |
EnergyTransfer:Plant | 212.35 | 0.00 | 01-JAN-00:50 | 142014.55 | 26-DEC-07:20 |
WaterSystems:EnergyTransfer | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
Boilers:EnergyTransfer | 160.87 | 0.00 | 01-JAN-00:50 | 139977.37 | 26-DEC-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.202 | -164.501 | 0.000 | 0.000 | 33.183 | 39.795 | 189.644 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -98.324 |
CORE_MID | 0.000 | 0.000 | 0.566 | -124.860 | 0.000 | 0.000 | 34.109 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -65.036 |
CORE_TOP | 0.000 | 0.000 | 2.388 | -113.316 | 0.000 | 0.000 | 34.805 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -79.099 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 5.018 | -22.815 | 0.000 | 0.000 | 7.528 | 4.998 | 24.333 | 13.763 | 0.000 | 0.008 | 0.001 | 0.000 | -28.704 | 0.000 | -3.224 | -0.905 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 2.970 | -22.619 | 0.000 | 0.000 | 4.701 | 3.131 | 15.404 | 26.220 | 0.000 | 0.005 | 0.000 | 0.000 | -18.594 | 0.000 | -2.181 | -9.038 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 3.687 | -40.848 | 0.000 | 0.000 | 7.364 | 4.897 | 24.332 | 56.773 | 0.000 | 0.007 | 0.001 | 0.000 | -28.498 | 0.000 | -3.354 | -24.361 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 3.124 | -23.096 | 0.000 | 0.000 | 4.735 | 3.126 | 15.403 | 28.329 | 0.000 | 0.005 | 0.000 | 0.000 | -19.178 | 0.000 | -2.203 | -10.244 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.490 | -20.326 | 0.000 | 0.000 | 7.504 | 4.982 | 24.333 | 14.089 | 0.000 | 0.006 | 0.001 | 0.000 | -29.545 | 0.000 | -1.774 | -1.758 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.442 | -20.860 | 0.000 | 0.000 | 4.673 | 3.124 | 15.404 | 26.377 | 0.000 | 0.003 | 0.001 | 0.000 | -19.376 | 0.000 | -1.217 | -9.571 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 11.442 | -28.048 | 0.000 | 0.000 | 7.560 | 4.887 | 24.332 | 57.491 | 0.000 | 0.383 | 0.000 | 0.000 | -29.512 | 0.000 | -32.492 | -16.043 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.451 | -20.941 | 0.000 | 0.000 | 4.695 | 3.118 | 15.403 | 28.572 | 0.000 | 0.003 | 0.000 | 0.000 | -20.069 | 0.000 | -1.231 | -11.002 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 1.950 | -24.901 | 0.000 | 0.000 | 7.427 | 4.997 | 24.333 | 13.533 | 0.000 | 0.008 | 5.839 | 0.000 | -30.357 | 0.000 | -2.829 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.209 | -22.381 | 0.000 | 0.000 | 3.428 | 3.131 | 15.404 | 25.959 | 0.000 | 0.004 | 0.001 | 0.000 | -19.627 | 0.000 | -1.915 | -5.212 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.402 | -43.543 | 0.000 | 0.000 | 7.264 | 4.897 | 24.332 | 56.499 | 0.000 | 0.006 | 0.000 | 0.000 | -30.041 | 0.000 | -2.938 | -17.877 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.220 | -24.408 | 0.000 | 0.000 | 4.670 | 3.126 | 15.403 | 28.194 | 0.000 | 0.004 | 0.001 | 0.000 | -20.256 | 0.000 | -1.930 | -6.023 |
TOPFLOOR_PLENUM | 11.877 | -19.234 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.005 | 12.335 | 0.000 | 0.000 | 0.000 | -4.983 | -0.003 |
MIDFLOOR_PLENUM | 5.951 | -10.246 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.009 | 9.162 | 0.000 | 0.000 | 0.000 | -4.876 | -0.000 |
FIRSTFLOOR_PLENUM | 3.523 | -14.010 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.007 | 14.394 | 0.000 | 0.000 | 0.000 | -3.914 | -0.000 |
Total Facility | 21.351 | -43.491 | 40.564 | -717.463 | 0.000 | 0.000 | 173.647 | 167.801 | 658.911 | 375.799 | 0.000 | 0.462 | 41.737 | 0.000 | -293.758 | 0.000 | -71.062 | -354.496 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-SEP-05:12 | 0.00 | 0.00 | 0.00 | -33400.70 | 0.00 | 0.00 | 324.33 | 387.63 | 5448.38 | 0.00 | 0.00 | 0.00 | 27240.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-AUG-05:12 | 0.00 | 0.00 | 0.00 | -29107.63 | 0.00 | 0.00 | 327.49 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 25366.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-AUG-06:02 | 0.00 | 0.00 | 0.00 | -26558.37 | 0.00 | 0.00 | 711.91 | 1162.90 | 3025.92 | 0.00 | 0.00 | 0.00 | 21657.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -7408.82 | 0.00 | 0.00 | 147.65 | 116.94 | 637.89 | 2175.43 | 0.00 | 0.00 | 4345.91 | 0.00 | -0.00 | 0.00 | -14.99 | 0.00 |
PERIMETER_TOP_ZN_2 | 13-AUG-09:02 | 0.00 | 0.00 | 0.00 | -12867.16 | 0.00 | 0.00 | 14.29 | 12.34 | 302.86 | 10122.10 | 0.00 | 0.00 | 2493.46 | 0.00 | -0.00 | 0.00 | -77.89 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:12 | 0.00 | 0.00 | 0.00 | -19072.50 | 0.00 | 0.00 | 22.25 | 19.49 | 478.41 | 14488.11 | 0.00 | 0.00 | 4136.04 | 0.00 | -0.00 | 0.00 | -71.80 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-JUL-16:52 | 0.00 | 0.00 | 0.00 | -14672.73 | 0.00 | 0.00 | 11.91 | 12.34 | 302.86 | 11984.10 | 0.00 | 0.00 | 2381.43 | 0.00 | -0.00 | 0.00 | -19.90 | 0.00 |
PERIMETER_BOT_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -4566.73 | 0.00 | 0.00 | 737.22 | 350.81 | 1435.25 | 3625.28 | 0.00 | 10.79 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1592.63 |
PERIMETER_BOT_ZN_2 | 13-AUG-09:32 | 0.00 | 0.00 | 0.00 | -10998.76 | 0.00 | 0.00 | 16.11 | 12.34 | 302.86 | 9073.54 | 0.00 | 0.00 | 1626.14 | 0.00 | -0.00 | 0.00 | -32.22 | 0.00 |
PERIMETER_BOT_ZN_1 | 13-AUG-12:52 | 0.00 | 0.00 | 0.00 | -16048.95 | 0.00 | 0.00 | 25.71 | 19.49 | 478.41 | 12625.59 | 0.00 | 0.00 | 2909.50 | 0.00 | -0.00 | 0.00 | -9.75 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JUL-18:11 | 0.00 | 0.00 | 0.00 | -12176.24 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 9438.66 | 0.00 | 0.00 | 2492.93 | 0.00 | -0.00 | 0.00 | -12.10 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -6743.83 | 0.00 | 0.00 | 144.83 | 116.94 | 637.89 | 2149.94 | 0.00 | 0.00 | 3707.30 | 0.00 | -0.00 | 0.00 | -13.06 | 0.00 |
PERIMETER_MID_ZN_2 | 13-AUG-08:52 | 0.00 | 0.00 | 0.00 | -14109.21 | 0.00 | 0.00 | 14.05 | 12.34 | 302.86 | 10431.02 | 0.00 | 0.00 | 3436.04 | 0.00 | -0.00 | 0.00 | -87.09 | 0.00 |
PERIMETER_MID_ZN_1 | 13-AUG-12:52 | 0.00 | 0.00 | 0.00 | -18874.38 | 0.00 | 0.00 | 23.53 | 19.49 | 478.41 | 12516.36 | 0.00 | 0.00 | 5860.26 | 0.00 | -0.00 | 0.00 | -23.68 | 0.00 |
PERIMETER_MID_ZN_4 | 07-MAY-16:41 | 0.00 | 0.00 | 0.00 | -14571.13 | 0.00 | 0.00 | 13.68 | 12.34 | 302.86 | 11066.97 | 0.00 | 0.00 | 3238.59 | 0.00 | -0.00 | 0.00 | -63.30 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:40 | 0.00 | -9124.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 | 9107.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 14-AUG-06:13 | 0.00 | -4656.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4692.03 | 0.00 | -0.00 | 0.00 | -35.35 | 0.00 |
FIRSTFLOOR_PLENUM | 14-AUG-06:13 | 0.00 | -4791.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4818.43 | 0.00 | -0.00 | 0.00 | -27.30 | 0.00 |
Total Facility | 24-JUL-06:03 | 0.00 | -4191.57 | 0.00 | -155447.16 | 0.00 | 0.00 | 3560.32 | 4634.49 | 19690.35 | 30662.46 | 0.00 | 0.00 | 106415.39 | 0.00 | -149.77 | 0.00 | -5174.51 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-06:11 | 0.00 | 0.00 | 7468.96 | 0.00 | 0.00 | 0.00 | 509.54 | 387.63 | 5448.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13814.51 |
CORE_MID | 02-JAN-06:11 | 0.00 | 0.00 | 12143.98 | 0.00 | 0.00 | 0.00 | 526.04 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16083.57 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 19052.81 | 0.00 | 0.00 | 0.00 | 536.19 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23002.55 |
PERIMETER_TOP_ZN_3 | 26-DEC-05:01 | 0.00 | 0.00 | 6960.47 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1755.31 | 0.00 | 0.00 | -5801.68 |
PERIMETER_TOP_ZN_2 | 26-DEC-05:01 | 0.00 | 0.00 | 6437.51 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1167.57 | 0.00 | 0.00 | -5647.56 |
PERIMETER_TOP_ZN_1 | 26-DEC-05:01 | 0.00 | 0.00 | 9583.06 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1767.91 | 0.00 | 0.00 | -8411.67 |
PERIMETER_TOP_ZN_4 | 26-DEC-05:01 | 0.00 | 0.00 | 6639.08 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1167.62 | 0.00 | 0.00 | -5849.08 |
PERIMETER_BOT_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 5233.17 | 0.00 | 0.00 | 0.00 | 113.18 | 81.72 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1085.48 | 0.00 | -34.77 | -4945.71 |
PERIMETER_BOT_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 4860.12 | 0.00 | 0.00 | 0.00 | 71.65 | 51.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -737.63 | 0.00 | -23.49 | -4626.20 |
PERIMETER_BOT_ZN_1 | 26-DEC-07:50 | 0.00 | 0.00 | 7953.04 | 0.00 | 0.00 | 0.00 | 232.62 | 245.15 | 637.88 | 0.00 | 0.00 | 0.00 | 6948.73 | 0.00 | -2079.88 | 0.00 | -13937.54 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 5017.95 | 0.00 | 0.00 | 0.00 | 71.65 | 51.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -722.09 | 0.00 | -23.52 | -4799.53 |
PERIMETER_MID_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 5604.04 | 0.00 | 0.00 | 0.00 | 113.18 | 81.72 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1095.38 | 0.00 | -54.70 | -5286.74 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 5323.82 | 0.00 | 0.00 | 0.00 | 71.65 | 51.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -746.47 | 0.00 | -37.03 | -5067.51 |
PERIMETER_MID_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 7750.70 | 0.00 | 0.00 | 0.00 | 113.17 | 81.72 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1121.62 | 0.00 | -55.37 | -7406.48 |
PERIMETER_MID_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 5322.48 | 0.00 | 0.00 | 0.00 | 71.65 | 51.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -729.18 | 0.00 | -37.03 | -5083.45 |
TOPFLOOR_PLENUM | 21-FEB-06:10 | 9669.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -56.12 | -9612.94 |
MIDFLOOR_PLENUM | 02-JAN-09:10 | 7924.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -80.10 | -7844.24 |
FIRSTFLOOR_PLENUM | 02-JAN-08:10 | 6333.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -47.52 | -6285.78 |
Total Facility | 02-JAN-06:11 | 5695.01 | 0.00 | 113639.21 | 0.00 | 0.00 | 0.00 | 2680.71 | 1963.59 | 17750.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10962.33 | 0.00 | -1865.22 | -128901.35 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.9356 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2627 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.0364 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.1400 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.2699 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6846 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.4678 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0751 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5182 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0766 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.6350 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0756 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2672 | 2.2672 | 0.6371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9686 | 1.9686 | 0.6378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0146 | 2.0146 | 0.6366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5704 | 0.5704 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7544 | 0.7544 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1127 | 1.1127 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8177 | 0.8177 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4516 | 0.4516 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6205 | 0.6205 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9128 | 0.9128 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6836 | 0.6836 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5018 | 0.5018 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7584 | 0.7584 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0398 | 1.0398 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7678 | 0.7678 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.9356 | 4.2627 | 4.9356 | 1.0751 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.0364 | 4.1400 | 5.0364 | 1.0766 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.2699 | 4.6846 | 5.2699 | 1.0756 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1336 | 1.1336 | 0.6371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9843 | 0.9843 | 0.6378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0073 | 1.0073 | 0.6366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2852 | 0.2852 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3772 | 0.3772 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5564 | 0.5564 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4089 | 0.4089 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2258 | 0.2258 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3102 | 0.3102 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4564 | 0.4564 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3418 | 0.3418 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2509 | 0.2509 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3792 | 0.3792 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5199 | 0.5199 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3839 | 0.3839 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.4678 | 1.0751 | 1.0751 | 1.0751 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5182 | 1.0766 | 1.0766 | 1.0766 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.6350 | 1.0756 | 1.0756 | 1.0756 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 328.83 |
Number of hours cooling loads not met | 71.67 |
Number of hours not met | 400.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 221.46 | 168245.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 60.32 | 46477.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 167.80 | 17672.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 34.59 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 73.68 | 4325.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 25.33 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 67.06 | 25430.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1.27 | 525.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 54.31 | 6517.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 658.91 | 1069.59 |
Natural Gas | 0.00 | 221.46 |
Additional | 0.00 | 0.00 |
Total | 658.91 | 1291.05 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 123.93 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 33.68 |
Space Heating | 0.00 |
Space Cooling | 12.11 |
Fans (All) | 13.46 |
Service Water Heating | 10.90 |
Receptacle Equipment | 132.25 |
Miscellaneous (All) | 214.68 |
Subtotal | 214.68 |
Natural Gas [MJ/m2] | |
Space Heating | 44.45 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 44.45 |
Subtotal | 44.45 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.00 |
Space Heating | 17.15 |
Space Cooling | 4.67 |
Fans (All) | 5.19 |
Service Water Heating | 4.21 |
Receptacle Equipment | 51.04 |
Miscellaneous | 4.74 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 1996. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 886. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8743.00 | 17.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8738.17 | 21.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8729.50 | 30.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8740.50 | 19.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8737.33 | 22.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8731.00 | 29.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8721.67 | 38.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8721.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 38.33 | 0.00 | 0.00 | 0.00 |
Average | 8747.53 | 12.47 | 0.00 | 0.00 | 0.00 |
Sum | 157455.50 | 224.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8695.33 | 64.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8736.50 | 23.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8724.00 | 36.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8721.17 | 38.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8738.33 | 21.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8730.33 | 29.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8708.33 | 51.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8725.67 | 34.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8719.17 | 40.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8731.67 | 28.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8695.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 64.67 | 0.00 | 0.00 | 0.00 |
Average | 8736.00 | 24.00 | 0.00 | 0.00 | 0.00 |
Sum | 157248.00 | 432.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128265.33 | 38.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128297.33 | 6.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128298.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128298.67 | 38.67 | 0.00 | 0.00 | 0.00 |
Average | 34140.52 | 2.81 | 0.00 | 0.00 | 0.00 |
Sum | 614529.33 | 50.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:59
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.704940E+10 | 6899.85 | 13-JAN-17:00 | 2.20 | 1.77 | 0.175606E+10 | 2556.25 | 13-JAN-14:00 | 2.20 | 1.77 |
February | 0.770083E+10 | 9803.39 | 28-FEB-17:00 | 14.40 | 10.82 | 0.172436E+10 | 2606.63 | 09-FEB-10:09 | 14.40 | 10.82 |
March | 0.116179E+11 | 12787.51 | 20-MAR-07:05 | 6.88 | 4.74 | 0.213916E+10 | 2606.65 | 02-MAR-10:20 | 6.88 | 4.74 |
April | 0.131187E+11 | 30184.53 | 28-APR-06:02 | 11.10 | 10.22 | 0.191217E+10 | 2606.66 | 27-APR-13:20 | 11.10 | 10.22 |
May | 0.172625E+11 | 31097.29 | 08-MAY-06:02 | 9.90 | 9.62 | 0.207493E+10 | 2606.67 | 05-MAY-09:09 | 9.90 | 9.62 |
June | 0.186744E+11 | 31488.73 | 12-JUN-06:02 | 14.60 | 13.50 | 0.206960E+10 | 2606.68 | 09-JUN-13:09 | 14.60 | 13.50 |
July | 0.192672E+11 | 33386.71 | 10-JUL-05:12 | 13.13 | 11.62 | 0.192482E+10 | 2606.65 | 20-JUL-13:20 | 26.30 | 16.68 |
August | 0.209204E+11 | 33290.55 | 14-AUG-05:12 | 15.33 | 13.50 | 0.216002E+10 | 2606.81 | 09-AUG-09:00 | 15.33 | 13.50 |
September | 0.173127E+11 | 33403.65 | 05-SEP-05:12 | 10.77 | 9.27 | 0.191767E+10 | 2606.66 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.138852E+11 | 30955.21 | 10-OCT-06:02 | 12.12 | 10.88 | 0.198799E+10 | 2606.65 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.962985E+10 | 12955.60 | 06-NOV-17:00 | 11.70 | 10.80 | 0.193329E+10 | 2606.63 | 10-NOV-10:09 | 6.88 | 5.74 |
December | 0.806270E+10 | 9363.36 | 06-DEC-15:50 | 3.58 | 3.15 | 0.181061E+10 | 2606.61 | 06-DEC-10:09 | 3.58 | 3.15 |
Annual Sum or Average | 0.164502E+12 | 0.234107E+11 | ||||||||
Minimum of Months | 0.704940E+10 | 6899.85 | 2.20 | 1.77 | 0.172436E+10 | 2556.25 | 2.20 | 1.77 | ||
Maximum of Months | 0.209204E+11 | 33403.65 | 15.33 | 13.50 | 0.216002E+10 | 2606.81 | 26.30 | 16.68 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 44874643.03 | 1555.07 | 27-FEB-15:30 | 19.70 | 12.30 | 0.00 | 0.00 | 01-FEB-00:10 | 19.70 | 12.30 |
March | 0.380890E+09 | 2563.89 | 14-MAR-14:40 | 15.93 | 10.38 | 0.00 | 0.00 | 01-MAR-00:10 | 15.93 | 10.38 |
April | 0.136707E+10 | 7739.33 | 27-APR-14:20 | 26.47 | 16.98 | 0.00 | 0.00 | 01-APR-00:10 | 26.47 | 16.98 |
May | 0.260004E+10 | 8267.93 | 15-MAY-14:20 | 23.30 | 13.21 | 0.00 | 0.00 | 01-MAY-00:10 | 23.30 | 13.21 |
June | 0.335189E+10 | 8022.99 | 28-JUN-14:20 | 25.37 | 15.62 | 0.00 | 0.00 | 01-JUN-00:10 | 25.37 | 15.62 |
July | 0.440969E+10 | 9099.82 | 24-JUL-13:40 | 29.03 | 18.20 | 0.00 | 0.00 | 01-JUL-00:10 | 29.03 | 18.20 |
August | 0.423451E+10 | 9124.70 | 10-AUG-14:40 | 29.93 | 18.99 | 0.00 | 0.00 | 01-AUG-00:10 | 29.93 | 18.99 |
September | 0.221452E+10 | 7083.98 | 14-SEP-14:30 | 23.90 | 17.04 | 0.00 | 0.00 | 01-SEP-00:10 | 23.90 | 17.04 |
October | 0.590415E+09 | 4921.88 | 04-OCT-14:50 | 21.60 | 11.48 | 0.00 | 0.00 | 01-OCT-00:10 | 21.60 | 11.48 |
November | 39331595.42 | 2006.01 | 04-NOV-14:30 | 21.10 | 15.94 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 15.94 |
December | 1349587.03 | 287.88 | 02-DEC-15:05 | 11.52 | 5.36 | 0.00 | 0.00 | 01-DEC-00:10 | 11.52 | 5.36 |
Annual Sum or Average | 0.192346E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 5.92 | 4.99 | 0.00 | 0.00 | 5.92 | 4.99 | ||
Maximum of Months | 0.440969E+10 | 9124.70 | 29.93 | 18.99 | 0.00 | 0.00 | 29.93 | 18.99 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8405332.99 | 1671.92 | 07-JAN-06:01 | -2.2 | -2.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.2 | -2.2 |
February | 66431464.19 | 1970.85 | 10-FEB-07:01 | 0.60 | -0.1 | 0.00 | 0.00 | 01-FEB-00:10 | 0.60 | -0.1 |
March | 0.210597E+09 | 2787.11 | 01-MAR-07:01 | -0.1 | -1.7 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -1.7 |
April | 0.510659E+09 | 2587.62 | 27-APR-16:00 | 27.20 | 16.90 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 16.90 |
May | 0.110917E+10 | 3058.76 | 15-MAY-15:10 | 23.40 | 12.66 | 0.00 | 0.00 | 01-MAY-00:10 | 23.40 | 12.66 |
June | 0.171525E+10 | 2990.85 | 28-JUN-15:40 | 26.10 | 16.04 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.04 |
July | 0.229156E+10 | 4156.82 | 31-JUL-14:20 | 28.30 | 18.91 | 0.00 | 0.00 | 01-JUL-00:10 | 28.30 | 18.91 |
August | 0.252334E+10 | 4656.62 | 14-AUG-06:13 | 15.73 | 13.91 | 0.00 | 0.00 | 01-AUG-00:10 | 15.73 | 13.91 |
September | 0.131496E+10 | 3413.12 | 11-SEP-15:30 | 23.30 | 15.99 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 15.99 |
October | 0.406315E+09 | 2051.39 | 04-OCT-15:40 | 21.30 | 11.43 | 0.00 | 0.00 | 01-OCT-00:10 | 21.30 | 11.43 |
November | 77578336.35 | 2039.20 | 10-NOV-07:02 | 4.08 | 3.61 | 0.00 | 0.00 | 01-NOV-00:10 | 4.08 | 3.61 |
December | 12077059.03 | 1474.19 | 06-DEC-07:01 | 0.18 | -0.1 | 0.00 | 0.00 | 01-DEC-00:10 | 0.18 | -0.1 |
Annual Sum or Average | 0.102463E+11 | 0.00 | ||||||||
Minimum of Months | 8405332.99 | 1474.19 | -2.2 | -2.2 | 0.00 | 0.00 | -2.2 | -2.2 | ||
Maximum of Months | 0.252334E+10 | 4656.62 | 28.30 | 18.91 | 0.00 | 0.00 | 28.30 | 18.91 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104707E+09 | 2233.36 | 13-JAN-06:12 | 3.13 | 2.22 | 0.00 | 0.00 | 01-JAN-00:10 | 3.13 | 2.22 |
February | 0.195866E+09 | 2621.55 | 10-FEB-07:01 | 0.60 | -0.1 | 0.00 | 0.00 | 01-FEB-00:10 | 0.60 | -0.1 |
March | 0.486249E+09 | 3187.18 | 02-MAR-07:02 | 0.78 | -0.1 | 0.00 | 0.00 | 01-MAR-00:10 | 0.78 | -0.1 |
April | 0.863827E+09 | 3076.00 | 18-APR-06:02 | 3.40 | 2.64 | 0.00 | 0.00 | 01-APR-00:10 | 3.40 | 2.64 |
May | 0.156003E+10 | 3427.31 | 15-MAY-06:07 | 11.97 | 9.44 | 0.00 | 0.00 | 01-MAY-00:10 | 11.97 | 9.44 |
June | 0.209682E+10 | 3237.40 | 12-JUN-06:13 | 14.80 | 13.57 | 0.00 | 0.00 | 01-JUN-00:10 | 14.80 | 13.57 |
July | 0.265832E+10 | 4189.68 | 24-JUL-15:00 | 30.60 | 18.78 | 0.00 | 0.00 | 01-JUL-00:10 | 30.60 | 18.78 |
August | 0.298200E+10 | 4791.00 | 14-AUG-06:13 | 15.73 | 13.91 | 0.00 | 0.00 | 01-AUG-00:10 | 15.73 | 13.91 |
September | 0.185308E+10 | 3833.43 | 11-SEP-15:50 | 23.30 | 16.09 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 16.09 |
October | 0.804108E+09 | 2780.21 | 05-OCT-06:06 | 8.48 | 5.36 | 0.00 | 0.00 | 01-OCT-00:10 | 8.48 | 5.36 |
November | 0.259850E+09 | 2448.57 | 16-NOV-07:02 | 3.48 | 2.25 | 0.00 | 0.00 | 01-NOV-00:10 | 3.48 | 2.25 |
December | 0.145400E+09 | 2270.46 | 07-DEC-07:03 | 6.10 | 3.18 | 0.00 | 0.00 | 01-DEC-00:10 | 6.10 | 3.18 |
Annual Sum or Average | 0.140103E+11 | 0.00 | ||||||||
Minimum of Months | 0.104707E+09 | 2233.36 | 0.60 | -0.1 | 0.00 | 0.00 | 0.60 | -0.1 | ||
Maximum of Months | 0.298200E+10 | 4791.00 | 30.60 | 18.78 | 0.00 | 0.00 | 30.60 | 18.78 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.548005E+10 | 5911.45 | 06-JAN-08:20 | -2.6 | -2.6 | 0.159542E+10 | 2354.13 | 12-JAN-14:00 | 7.20 | 5.88 |
February | 0.624321E+10 | 6588.01 | 28-FEB-17:00 | 14.40 | 10.82 | 0.155193E+10 | 2579.11 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.871703E+10 | 8196.56 | 02-MAR-17:00 | 12.80 | 8.57 | 0.203684E+10 | 2606.61 | 02-MAR-14:20 | 12.80 | 8.57 |
April | 0.981771E+10 | 13134.07 | 27-APR-16:00 | 27.20 | 16.90 | 0.187970E+10 | 2606.66 | 14-APR-09:20 | 27.20 | 16.90 |
May | 0.130390E+11 | 20307.45 | 08-MAY-06:02 | 9.90 | 9.62 | 0.206258E+10 | 2606.66 | 05-MAY-09:09 | 9.90 | 9.62 |
June | 0.143855E+11 | 25918.83 | 12-JUN-06:02 | 14.60 | 13.50 | 0.206335E+10 | 2606.67 | 09-JUN-13:09 | 14.60 | 13.50 |
July | 0.150525E+11 | 26578.20 | 10-JUL-06:02 | 12.88 | 11.52 | 0.192011E+10 | 2606.65 | 31-JUL-09:20 | 22.57 | 17.16 |
August | 0.162349E+11 | 29108.23 | 14-AUG-05:12 | 15.33 | 13.50 | 0.215541E+10 | 2606.77 | 09-AUG-09:00 | 15.33 | 13.50 |
September | 0.127007E+11 | 26373.07 | 11-SEP-06:01 | 12.07 | 10.69 | 0.190759E+10 | 2606.65 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.973905E+10 | 12817.72 | 04-OCT-16:00 | 21.10 | 11.40 | 0.193758E+10 | 2606.65 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.718841E+10 | 7788.39 | 06-NOV-17:00 | 11.70 | 10.80 | 0.176803E+10 | 2606.60 | 06-NOV-14:09 | 11.70 | 10.80 |
December | 0.626218E+10 | 6130.27 | 06-DEC-16:00 | 3.30 | 2.91 | 0.160627E+10 | 2486.35 | 06-DEC-14:00 | 3.30 | 2.91 |
Annual Sum or Average | 0.124860E+12 | 0.224848E+11 | ||||||||
Minimum of Months | 0.548005E+10 | 5911.45 | -2.6 | -2.6 | 0.155193E+10 | 2354.13 | 3.30 | 2.91 | ||
Maximum of Months | 0.162349E+11 | 29108.23 | 27.20 | 16.90 | 0.215541E+10 | 2606.77 | 27.20 | 17.16 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380382E+10 | 5506.90 | 06-JAN-10:30 | -0.9 | -0.9 | 0.152618E+10 | 2262.85 | 11-JAN-14:00 | 14.40 | 10.49 |
February | 0.497885E+10 | 6404.42 | 28-FEB-17:00 | 14.40 | 10.82 | 0.146388E+10 | 2550.29 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.788552E+10 | 7651.46 | 02-MAR-17:00 | 12.80 | 8.57 | 0.192552E+10 | 2606.55 | 02-MAR-14:00 | 12.80 | 8.57 |
April | 0.916233E+10 | 14607.02 | 27-APR-15:30 | 27.20 | 17.10 | 0.182519E+10 | 2606.66 | 27-APR-13:20 | 27.20 | 17.10 |
May | 0.123622E+11 | 15863.41 | 15-MAY-15:20 | 23.50 | 12.70 | 0.204242E+10 | 2606.65 | 05-MAY-09:09 | 23.50 | 12.70 |
June | 0.140197E+11 | 16317.94 | 12-JUN-06:02 | 14.60 | 13.50 | 0.205443E+10 | 2606.68 | 09-JUN-13:09 | 14.60 | 13.50 |
July | 0.150150E+11 | 25723.24 | 24-JUL-06:03 | 17.48 | 14.11 | 0.191416E+10 | 2606.65 | 20-JUL-13:20 | 17.48 | 14.11 |
August | 0.158543E+11 | 26559.49 | 14-AUG-06:02 | 15.47 | 13.75 | 0.214887E+10 | 2606.75 | 09-AUG-09:00 | 15.47 | 13.75 |
September | 0.115942E+11 | 15586.32 | 11-SEP-15:30 | 23.30 | 15.99 | 0.188576E+10 | 2606.65 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.846478E+10 | 12779.77 | 04-OCT-16:00 | 21.10 | 11.40 | 0.185306E+10 | 2606.62 | 05-OCT-09:20 | 12.43 | 7.97 |
November | 0.580954E+10 | 6307.26 | 02-NOV-16:00 | 13.30 | 10.88 | 0.164629E+10 | 2538.58 | 06-NOV-14:00 | 11.10 | 10.22 |
December | 0.436597E+10 | 5722.23 | 05-DEC-16:00 | 6.10 | 4.53 | 0.150289E+10 | 2350.76 | 06-DEC-14:00 | 5.00 | 4.36 |
Annual Sum or Average | 0.113316E+12 | 0.217886E+11 | ||||||||
Minimum of Months | 0.380382E+10 | 5506.90 | -0.9 | -0.9 | 0.146388E+10 | 2262.85 | 5.00 | 4.36 | ||
Maximum of Months | 0.158543E+11 | 26559.49 | 27.20 | 17.10 | 0.214887E+10 | 2606.75 | 27.20 | 17.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182618E+09 | 1002.70 | 11-JAN-16:10 | 14.03 | 10.30 | 0.306265E+09 | 439.85 | 11-JAN-14:00 | 14.03 | 10.30 |
February | 0.479187E+09 | 1270.47 | 28-FEB-15:00 | 13.90 | 10.81 | 0.287600E+09 | 518.97 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.125561E+10 | 1349.17 | 10-MAR-14:50 | 16.20 | 11.59 | 0.373501E+09 | 544.76 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.179037E+10 | 4303.65 | 27-APR-15:20 | 27.20 | 17.16 | 0.365798E+09 | 549.50 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.284385E+10 | 4700.35 | 15-MAY-14:30 | 23.30 | 13.06 | 0.421658E+09 | 549.50 | 05-MAY-09:20 | 23.30 | 13.06 |
June | 0.348787E+10 | 4932.55 | 21-JUN-15:30 | 24.70 | 15.68 | 0.429957E+09 | 549.50 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.397852E+10 | 7408.72 | 24-JUL-06:03 | 17.48 | 14.11 | 0.401987E+09 | 549.50 | 20-JUL-13:20 | 17.48 | 14.11 |
August | 0.401783E+10 | 5349.29 | 09-AUG-15:20 | 28.47 | 18.71 | 0.450328E+09 | 549.53 | 09-AUG-09:00 | 28.47 | 18.71 |
September | 0.243505E+10 | 4120.52 | 12-SEP-14:40 | 24.40 | 16.65 | 0.386948E+09 | 549.50 | 05-SEP-09:20 | 24.40 | 16.65 |
October | 0.145363E+10 | 2635.03 | 04-OCT-15:20 | 21.50 | 11.47 | 0.363069E+09 | 549.49 | 05-OCT-13:20 | 16.10 | 10.57 |
November | 0.658977E+09 | 1219.91 | 02-NOV-14:40 | 13.67 | 11.26 | 0.318765E+09 | 501.59 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.231849E+09 | 952.94 | 05-DEC-15:10 | 9.35 | 6.62 | 0.296232E+09 | 427.85 | 05-DEC-14:00 | 9.35 | 6.62 |
Annual Sum or Average | 0.228154E+11 | 0.440211E+10 | ||||||||
Minimum of Months | 0.182618E+09 | 952.94 | 9.35 | 6.62 | 0.287600E+09 | 427.85 | 9.35 | 6.62 | ||
Maximum of Months | 0.401783E+10 | 7408.72 | 28.47 | 18.71 | 0.450328E+09 | 549.53 | 28.47 | 18.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169990E+09 | 697.05 | 05-JAN-09:10 | -0.0 | -0.1 | 0.194772E+09 | 283.04 | 11-JAN-14:00 | 14.40 | 10.49 |
February | 0.394430E+09 | 856.31 | 27-FEB-15:50 | 19.50 | 12.39 | 0.189242E+09 | 340.95 | 27-FEB-14:00 | 19.50 | 12.39 |
March | 0.101680E+10 | 2796.12 | 14-MAR-09:40 | 9.27 | 7.14 | 0.252482E+09 | 347.88 | 02-MAR-10:20 | 9.27 | 7.14 |
April | 0.192081E+10 | 6601.88 | 27-APR-09:00 | 17.80 | 12.21 | 0.243418E+09 | 347.88 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.277469E+10 | 11914.28 | 14-MAY-08:53 | 16.70 | 11.54 | 0.270648E+09 | 347.89 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.366729E+10 | 12287.73 | 25-JUN-08:62 | 15.78 | 11.63 | 0.274178E+09 | 347.88 | 09-JUN-13:09 | 15.78 | 11.63 |
July | 0.393907E+10 | 12713.24 | 30-JUL-09:02 | 20.87 | 15.88 | 0.255635E+09 | 348.45 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.420419E+10 | 12867.54 | 13-AUG-09:02 | 21.20 | 16.02 | 0.286640E+09 | 348.42 | 10-AUG-09:00 | 21.20 | 16.02 |
September | 0.254594E+10 | 12462.14 | 10-SEP-09:13 | 16.47 | 13.50 | 0.249029E+09 | 347.88 | 11-SEP-09:00 | 18.90 | 14.30 |
October | 0.127891E+10 | 4835.12 | 04-OCT-09:10 | 15.87 | 10.58 | 0.240030E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.479187E+09 | 856.27 | 02-NOV-10:40 | 12.43 | 10.47 | 0.205825E+09 | 335.09 | 02-NOV-13:00 | 14.40 | 11.37 |
December | 0.227800E+09 | 708.23 | 05-DEC-10:30 | 7.50 | 5.28 | 0.189729E+09 | 300.41 | 05-DEC-10:50 | 8.03 | 5.37 |
Annual Sum or Average | 0.226191E+11 | 0.285163E+10 | ||||||||
Minimum of Months | 0.169990E+09 | 697.05 | -0.0 | -0.1 | 0.189242E+09 | 283.04 | 8.03 | 5.37 | ||
Maximum of Months | 0.420419E+10 | 12867.54 | 21.20 | 16.02 | 0.286640E+09 | 348.45 | 26.10 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.604906E+09 | 6505.96 | 20-JAN-13:25 | 6.70 | 4.72 | 0.324123E+09 | 549.49 | 20-JAN-14:50 | 7.12 | 4.90 |
February | 0.132225E+10 | 8528.59 | 27-FEB-14:30 | 19.15 | 11.80 | 0.316342E+09 | 549.49 | 27-FEB-14:00 | 20.00 | 12.17 |
March | 0.276563E+10 | 9724.97 | 01-MAR-13:35 | 11.33 | 6.09 | 0.402327E+09 | 549.50 | 02-MAR-14:00 | 13.30 | 8.57 |
April | 0.358896E+10 | 11611.22 | 27-APR-13:05 | 26.10 | 16.37 | 0.379078E+09 | 550.01 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.444530E+10 | 18729.30 | 14-MAY-12:53 | 22.20 | 12.20 | 0.423919E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.479250E+10 | 10442.14 | 11-JUN-12:03 | 21.70 | 15.54 | 0.429795E+09 | 549.51 | 09-JUN-13:09 | 21.70 | 15.54 |
July | 0.585656E+10 | 18702.48 | 23-JUL-13:32 | 27.23 | 16.89 | 0.402189E+09 | 550.03 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.662518E+10 | 18589.88 | 13-AUG-13:02 | 26.62 | 18.46 | 0.451208E+09 | 550.38 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.539069E+10 | 19072.18 | 10-SEP-13:12 | 21.13 | 14.29 | 0.392423E+09 | 550.29 | 15-SEP-13:50 | 21.70 | 16.50 |
October | 0.341890E+10 | 16678.91 | 08-OCT-12:43 | 17.80 | 13.53 | 0.383475E+09 | 549.81 | 04-OCT-13:00 | 17.80 | 13.53 |
November | 0.119440E+10 | 8876.23 | 04-NOV-13:30 | 20.85 | 16.00 | 0.341289E+09 | 549.49 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.843084E+09 | 6710.04 | 05-DEC-12:30 | 10.30 | 6.13 | 0.320149E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.408484E+11 | 0.456632E+10 | ||||||||
Minimum of Months | 0.604906E+09 | 6505.96 | 6.70 | 4.72 | 0.316342E+09 | 549.49 | 7.12 | 4.90 | ||
Maximum of Months | 0.662518E+10 | 19072.18 | 27.23 | 18.46 | 0.451208E+09 | 550.38 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170611E+09 | 789.32 | 20-JAN-15:50 | 5.87 | 4.23 | 0.196307E+09 | 316.68 | 05-JAN-15:00 | 5.87 | 4.23 |
February | 0.404359E+09 | 3477.02 | 27-FEB-15:30 | 19.70 | 12.30 | 0.188758E+09 | 347.83 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.108204E+10 | 5139.16 | 14-MAR-16:00 | 17.20 | 10.94 | 0.242320E+09 | 347.84 | 10-MAR-14:20 | 17.20 | 10.94 |
April | 0.187150E+10 | 8021.23 | 26-APR-16:00 | 24.40 | 14.49 | 0.233941E+09 | 347.85 | 28-APR-09:20 | 11.70 | 11.07 |
May | 0.297214E+10 | 14105.84 | 07-MAY-16:52 | 21.70 | 16.17 | 0.267603E+09 | 347.85 | 05-MAY-09:20 | 21.70 | 16.17 |
June | 0.336655E+10 | 12685.58 | 18-JUN-17:22 | 16.95 | 12.25 | 0.272106E+09 | 347.86 | 05-JUN-13:00 | 16.95 | 12.25 |
July | 0.440694E+10 | 14673.31 | 23-JUL-16:52 | 26.70 | 15.58 | 0.254914E+09 | 347.85 | 20-JUL-13:20 | 26.70 | 15.58 |
August | 0.417795E+10 | 14421.59 | 06-AUG-16:42 | 23.47 | 15.19 | 0.285492E+09 | 347.87 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.268155E+10 | 13544.87 | 10-SEP-16:32 | 22.20 | 14.28 | 0.246557E+09 | 347.85 | 05-SEP-09:20 | 22.20 | 14.28 |
October | 0.128988E+10 | 6483.06 | 04-OCT-16:00 | 21.10 | 11.40 | 0.233260E+09 | 347.85 | 25-OCT-13:20 | 13.50 | 10.37 |
November | 0.466975E+09 | 2669.37 | 04-NOV-15:30 | 20.55 | 15.94 | 0.205026E+09 | 347.84 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.206562E+09 | 938.75 | 05-DEC-15:30 | 8.05 | 5.82 | 0.191448E+09 | 338.68 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.230971E+11 | 0.281773E+10 | ||||||||
Minimum of Months | 0.170611E+09 | 789.32 | 5.87 | 4.23 | 0.188758E+09 | 316.68 | 5.87 | 4.23 | ||
Maximum of Months | 0.440694E+10 | 14673.31 | 26.70 | 16.17 | 0.285492E+09 | 347.87 | 26.70 | 16.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224409E+09 | 954.12 | 11-JAN-15:00 | 14.40 | 10.49 | 0.306717E+09 | 427.97 | 11-JAN-14:00 | 14.40 | 10.49 |
February | 0.516937E+09 | 1150.53 | 28-FEB-14:10 | 14.32 | 11.45 | 0.285451E+09 | 483.82 | 28-FEB-14:20 | 14.23 | 11.32 |
March | 0.128662E+10 | 1205.03 | 10-MAR-14:40 | 16.30 | 11.68 | 0.367812E+09 | 500.23 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.153974E+10 | 2501.49 | 27-APR-16:00 | 27.20 | 16.90 | 0.358441E+09 | 549.50 | 27-APR-13:20 | 27.20 | 16.90 |
May | 0.220768E+10 | 2966.71 | 05-MAY-15:30 | 24.70 | 17.20 | 0.421916E+09 | 549.50 | 05-MAY-09:20 | 24.70 | 17.20 |
June | 0.271678E+10 | 3675.11 | 21-JUN-15:30 | 24.70 | 15.68 | 0.430788E+09 | 549.50 | 09-JUN-13:20 | 24.70 | 15.68 |
July | 0.318925E+10 | 4566.76 | 24-JUL-15:00 | 30.60 | 18.78 | 0.402746E+09 | 549.50 | 20-JUL-13:20 | 30.60 | 18.78 |
August | 0.337535E+10 | 4190.04 | 09-AUG-15:30 | 28.70 | 18.83 | 0.451792E+09 | 549.52 | 09-AUG-09:00 | 28.70 | 18.83 |
September | 0.222139E+10 | 3165.41 | 12-SEP-14:50 | 24.40 | 16.68 | 0.392906E+09 | 549.50 | 08-SEP-09:20 | 24.40 | 16.68 |
October | 0.161134E+10 | 2011.33 | 04-OCT-15:30 | 21.40 | 11.45 | 0.377535E+09 | 549.49 | 03-OCT-13:20 | 21.40 | 11.45 |
November | 0.101392E+10 | 1244.17 | 06-NOV-12:00 | 13.90 | 10.05 | 0.331638E+09 | 507.77 | 07-NOV-14:09 | 12.80 | 10.81 |
December | 0.422293E+09 | 959.25 | 14-DEC-13:40 | 9.63 | 7.19 | 0.299144E+09 | 428.83 | 05-DEC-14:20 | 9.63 | 7.19 |
Annual Sum or Average | 0.203257E+11 | 0.442688E+10 | ||||||||
Minimum of Months | 0.224409E+09 | 954.12 | 9.63 | 7.19 | 0.285451E+09 | 427.97 | 9.63 | 7.19 | ||
Maximum of Months | 0.337535E+10 | 4566.76 | 30.60 | 18.83 | 0.451792E+09 | 549.52 | 30.60 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198204E+09 | 663.99 | 05-JAN-09:00 | -0.6 | -0.6 | 0.195136E+09 | 279.54 | 20-JAN-10:50 | 5.32 | 3.17 |
February | 0.432123E+09 | 770.02 | 27-FEB-15:40 | 19.60 | 12.34 | 0.188118E+09 | 318.80 | 08-FEB-10:39 | 19.60 | 12.34 |
March | 0.997692E+09 | 1581.73 | 25-MAR-08:30 | 5.55 | 0.58 | 0.251390E+09 | 347.88 | 02-MAR-10:20 | 5.55 | 0.58 |
April | 0.158702E+10 | 4878.63 | 27-APR-09:20 | 18.17 | 12.47 | 0.244233E+09 | 347.88 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.225728E+10 | 8250.78 | 15-MAY-06:02 | 11.97 | 9.44 | 0.272146E+09 | 347.89 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.316041E+10 | 8337.05 | 19-JUN-06:02 | 11.88 | 9.64 | 0.275042E+09 | 347.88 | 09-JUN-13:09 | 11.88 | 9.64 |
July | 0.344804E+10 | 9011.21 | 23-JUL-08:42 | 18.72 | 13.76 | 0.256190E+09 | 348.16 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.392446E+10 | 10999.36 | 13-AUG-09:32 | 22.10 | 16.37 | 0.287473E+09 | 348.19 | 14-AUG-09:00 | 21.10 | 15.94 |
September | 0.243069E+10 | 8749.16 | 10-SEP-09:02 | 16.28 | 13.48 | 0.252395E+09 | 347.88 | 11-SEP-09:00 | 18.90 | 14.30 |
October | 0.139257E+10 | 4059.53 | 04-OCT-08:30 | 14.75 | 10.13 | 0.249203E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.690016E+09 | 863.03 | 02-NOV-10:40 | 12.43 | 10.47 | 0.215630E+09 | 337.84 | 02-NOV-10:50 | 12.62 | 10.55 |
December | 0.341042E+09 | 739.87 | 05-DEC-10:30 | 7.50 | 5.28 | 0.193292E+09 | 310.22 | 05-DEC-10:39 | 7.77 | 5.32 |
Annual Sum or Average | 0.208595E+11 | 0.288025E+10 | ||||||||
Minimum of Months | 0.198204E+09 | 663.99 | -0.6 | -0.6 | 0.188118E+09 | 279.54 | 5.32 | 0.58 | ||
Maximum of Months | 0.392446E+10 | 10999.36 | 22.10 | 16.37 | 0.287473E+09 | 348.19 | 26.10 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203352E+09 | 1344.46 | 20-JAN-13:50 | 6.70 | 4.72 | 0.299126E+09 | 540.14 | 20-JAN-14:09 | 6.78 | 4.76 |
February | 0.623609E+09 | 5844.37 | 27-FEB-13:08 | 17.88 | 11.31 | 0.294147E+09 | 549.51 | 07-FEB-14:09 | 17.88 | 11.31 |
March | 0.144790E+10 | 6198.97 | 02-MAR-13:20 | 12.57 | 7.60 | 0.372697E+09 | 549.51 | 24-MAR-13:20 | 8.67 | 2.76 |
April | 0.202601E+10 | 8863.09 | 27-APR-13:30 | 26.10 | 16.55 | 0.356182E+09 | 549.51 | 27-APR-13:50 | 26.10 | 16.74 |
May | 0.258937E+10 | 10551.69 | 14-MAY-14:13 | 22.97 | 12.33 | 0.404487E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.302359E+10 | 6789.72 | 28-JUN-13:30 | 24.70 | 15.69 | 0.416502E+09 | 549.52 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.434766E+10 | 12623.98 | 30-JUL-13:32 | 26.50 | 17.71 | 0.396690E+09 | 549.60 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.569465E+10 | 16049.31 | 13-AUG-12:52 | 26.50 | 18.40 | 0.446235E+09 | 549.93 | 29-AUG-13:39 | 29.43 | 20.04 |
September | 0.422574E+10 | 15952.97 | 10-SEP-15:02 | 22.70 | 14.34 | 0.385324E+09 | 549.94 | 15-SEP-13:00 | 21.70 | 16.45 |
October | 0.256910E+10 | 10849.59 | 04-OCT-13:30 | 20.85 | 11.31 | 0.376340E+09 | 549.68 | 03-OCT-13:00 | 20.85 | 11.31 |
November | 0.855614E+09 | 6428.25 | 04-NOV-13:40 | 20.93 | 15.98 | 0.322373E+09 | 549.50 | 15-NOV-14:09 | 9.82 | 6.80 |
December | 0.442033E+09 | 3814.17 | 05-DEC-12:00 | 10.00 | 6.07 | 0.300863E+09 | 549.51 | 05-DEC-14:09 | 10.50 | 6.49 |
Annual Sum or Average | 0.280486E+11 | 0.437097E+10 | ||||||||
Minimum of Months | 0.203352E+09 | 1344.46 | 6.70 | 4.72 | 0.294147E+09 | 540.14 | 6.78 | 2.76 | ||
Maximum of Months | 0.569465E+10 | 16049.31 | 26.50 | 18.40 | 0.446235E+09 | 549.94 | 29.43 | 20.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194291E+09 | 718.77 | 20-JAN-15:50 | 5.87 | 4.23 | 0.195901E+09 | 296.67 | 20-JAN-15:00 | 5.60 | 4.08 |
February | 0.433298E+09 | 1979.79 | 27-FEB-15:40 | 19.60 | 12.34 | 0.187588E+09 | 347.83 | 27-FEB-14:00 | 19.60 | 12.34 |
March | 0.100296E+10 | 2871.79 | 02-MAR-16:30 | 13.05 | 8.47 | 0.243462E+09 | 347.83 | 02-MAR-14:00 | 13.05 | 8.47 |
April | 0.149020E+10 | 5650.55 | 26-APR-17:30 | 23.60 | 13.73 | 0.236330E+09 | 347.85 | 28-APR-09:20 | 11.70 | 11.07 |
May | 0.237707E+10 | 9366.37 | 14-MAY-17:32 | 22.40 | 11.93 | 0.271211E+09 | 347.85 | 05-MAY-09:20 | 22.40 | 11.93 |
June | 0.283238E+10 | 8465.16 | 18-JUN-17:52 | 16.70 | 12.27 | 0.274047E+09 | 347.85 | 20-JUN-09:20 | 18.87 | 13.67 |
July | 0.387841E+10 | 12176.11 | 30-JUL-18:11 | 25.93 | 17.32 | 0.256382E+09 | 347.85 | 03-JUL-09:20 | 25.93 | 17.32 |
August | 0.383335E+10 | 11875.72 | 06-AUG-17:51 | 23.80 | 15.26 | 0.287312E+09 | 347.88 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.251615E+10 | 11528.31 | 10-SEP-17:02 | 21.93 | 14.12 | 0.252300E+09 | 347.86 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.137183E+10 | 5712.40 | 04-OCT-16:00 | 21.10 | 11.40 | 0.245556E+09 | 347.85 | 05-OCT-09:20 | 12.43 | 7.97 |
November | 0.685785E+09 | 2186.24 | 04-NOV-15:30 | 20.55 | 15.94 | 0.213861E+09 | 347.83 | 10-NOV-14:00 | 10.00 | 6.84 |
December | 0.325681E+09 | 831.21 | 05-DEC-15:30 | 8.05 | 5.82 | 0.193540E+09 | 329.73 | 05-DEC-15:39 | 7.40 | 5.40 |
Annual Sum or Average | 0.209414E+11 | 0.285749E+10 | ||||||||
Minimum of Months | 0.194291E+09 | 718.77 | 5.87 | 4.23 | 0.187588E+09 | 296.67 | 5.60 | 4.08 | ||
Maximum of Months | 0.387841E+10 | 12176.11 | 25.93 | 17.32 | 0.287312E+09 | 347.88 | 25.93 | 17.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362002E+09 | 1046.56 | 11-JAN-15:10 | 14.40 | 10.49 | 0.309051E+09 | 452.29 | 11-JAN-14:00 | 14.40 | 10.49 |
February | 0.735146E+09 | 1293.14 | 28-FEB-15:00 | 13.90 | 10.81 | 0.294127E+09 | 525.18 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.152897E+10 | 1352.96 | 10-MAR-14:50 | 16.20 | 11.59 | 0.391157E+09 | 544.46 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.192619E+10 | 3938.61 | 27-APR-15:20 | 27.20 | 17.16 | 0.378463E+09 | 549.50 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.295181E+10 | 4279.68 | 15-MAY-14:30 | 23.30 | 13.06 | 0.429172E+09 | 549.50 | 05-MAY-09:20 | 23.30 | 13.06 |
June | 0.355361E+10 | 4723.35 | 12-JUN-06:02 | 14.60 | 13.50 | 0.433218E+09 | 549.50 | 09-JUN-13:09 | 14.60 | 13.50 |
July | 0.397066E+10 | 6743.91 | 24-JUL-06:03 | 17.48 | 14.11 | 0.403771E+09 | 550.33 | 24-JUL-13:20 | 28.67 | 18.27 |
August | 0.407059E+10 | 6438.11 | 14-AUG-06:02 | 15.47 | 13.75 | 0.452842E+09 | 549.53 | 09-AUG-09:00 | 15.47 | 13.75 |
September | 0.260153E+10 | 3953.83 | 12-SEP-14:40 | 24.40 | 16.65 | 0.395589E+09 | 549.50 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.171092E+10 | 2668.08 | 04-OCT-15:20 | 21.50 | 11.47 | 0.382187E+09 | 549.49 | 12-OCT-13:20 | 14.27 | 10.74 |
November | 0.100045E+10 | 1277.94 | 06-NOV-12:00 | 13.90 | 10.05 | 0.332514E+09 | 517.71 | 06-NOV-14:09 | 11.60 | 10.16 |
December | 0.489013E+09 | 1016.88 | 05-DEC-15:00 | 10.00 | 7.01 | 0.301632E+09 | 445.21 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.249009E+11 | 0.450372E+10 | ||||||||
Minimum of Months | 0.362002E+09 | 1016.88 | 10.00 | 7.01 | 0.294127E+09 | 445.21 | 10.00 | 7.01 | ||
Maximum of Months | 0.407059E+10 | 6743.91 | 27.20 | 17.16 | 0.452842E+09 | 550.33 | 28.67 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214302E+09 | 724.55 | 20-JAN-11:10 | 5.60 | 3.32 | 0.145541E+09 | 303.46 | 20-JAN-11:09 | 5.60 | 3.32 |
February | 0.425360E+09 | 2091.85 | 08-FEB-11:05 | 4.08 | 2.58 | 0.143988E+09 | 356.46 | 08-FEB-11:09 | 4.08 | 2.58 |
March | 0.105516E+10 | 5703.06 | 01-MAR-13:01 | 10.78 | 5.75 | 0.192523E+09 | 356.46 | 14-MAR-10:09 | 10.28 | 7.92 |
April | 0.191581E+10 | 7250.43 | 27-APR-10:05 | 19.27 | 13.13 | 0.183089E+09 | 356.46 | 20-APR-10:09 | 19.27 | 13.13 |
May | 0.270273E+10 | 11937.74 | 14-MAY-07:53 | 14.40 | 10.27 | 0.202183E+09 | 356.47 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.354667E+10 | 10825.37 | 25-JUN-10:23 | 18.60 | 13.07 | 0.203725E+09 | 356.46 | 07-JUN-10:09 | 18.60 | 13.07 |
July | 0.375844E+10 | 12954.13 | 30-JUL-08:42 | 20.22 | 15.61 | 0.190473E+09 | 356.46 | 07-JUL-12:09 | 20.22 | 15.61 |
August | 0.407697E+10 | 14110.99 | 13-AUG-08:52 | 20.90 | 15.90 | 0.212855E+09 | 356.51 | 09-AUG-10:09 | 20.90 | 15.90 |
September | 0.252853E+10 | 11021.44 | 10-SEP-10:13 | 17.77 | 13.72 | 0.186858E+09 | 356.46 | 11-SEP-10:09 | 19.08 | 14.37 |
October | 0.134232E+10 | 5887.19 | 04-OCT-10:05 | 17.48 | 10.97 | 0.183789E+09 | 356.46 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.535213E+09 | 3712.13 | 02-NOV-12:02 | 13.48 | 11.00 | 0.159608E+09 | 356.45 | 02-NOV-14:09 | 14.22 | 11.35 |
December | 0.279752E+09 | 801.08 | 05-DEC-11:10 | 8.58 | 5.53 | 0.144090E+09 | 328.66 | 05-DEC-11:09 | 8.58 | 5.53 |
Annual Sum or Average | 0.223813E+11 | 0.214872E+10 | ||||||||
Minimum of Months | 0.214302E+09 | 724.55 | 4.08 | 2.58 | 0.143988E+09 | 303.46 | 4.08 | 2.58 | ||
Maximum of Months | 0.407697E+10 | 14110.99 | 20.90 | 15.90 | 0.212855E+09 | 356.51 | 20.90 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.818224E+09 | 6943.55 | 20-JAN-13:20 | 6.70 | 4.72 | 0.331469E+09 | 549.49 | 20-JAN-14:39 | 7.03 | 4.87 |
February | 0.167601E+10 | 8603.82 | 27-FEB-14:10 | 18.58 | 11.55 | 0.324788E+09 | 549.50 | 08-FEB-10:09 | 18.58 | 11.55 |
March | 0.316093E+10 | 10034.02 | 01-MAR-13:25 | 11.15 | 5.98 | 0.417008E+09 | 549.50 | 02-MAR-14:00 | 13.30 | 8.57 |
April | 0.380587E+10 | 11162.26 | 27-APR-13:05 | 26.10 | 16.37 | 0.388493E+09 | 550.62 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.456017E+10 | 17497.46 | 14-MAY-13:13 | 22.40 | 12.22 | 0.430513E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.483105E+10 | 9386.94 | 11-JUN-11:53 | 21.70 | 15.59 | 0.433240E+09 | 549.52 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.579474E+10 | 13886.58 | 30-JUL-13:23 | 26.40 | 17.72 | 0.404206E+09 | 550.86 | 31-JUL-13:20 | 27.57 | 18.47 |
August | 0.666240E+10 | 18875.76 | 13-AUG-12:52 | 26.50 | 18.40 | 0.453556E+09 | 550.89 | 14-AUG-13:20 | 25.93 | 17.49 |
September | 0.559965E+10 | 17891.47 | 10-SEP-12:52 | 20.60 | 14.10 | 0.398908E+09 | 550.64 | 12-SEP-13:20 | 23.33 | 16.02 |
October | 0.385510E+10 | 17824.42 | 08-OCT-12:53 | 17.80 | 13.59 | 0.397531E+09 | 550.16 | 04-OCT-13:20 | 17.80 | 13.59 |
November | 0.159646E+10 | 9060.73 | 04-NOV-13:30 | 20.85 | 16.00 | 0.357087E+09 | 549.49 | 24-NOV-10:30 | 5.85 | 4.21 |
December | 0.118316E+10 | 7590.38 | 05-DEC-12:30 | 10.30 | 6.13 | 0.329932E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.435438E+11 | 0.466673E+10 | ||||||||
Minimum of Months | 0.818224E+09 | 6943.55 | 6.70 | 4.72 | 0.324788E+09 | 549.49 | 5.85 | 4.21 | ||
Maximum of Months | 0.666240E+10 | 18875.76 | 26.50 | 18.40 | 0.453556E+09 | 550.89 | 27.57 | 18.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279762E+09 | 810.36 | 05-JAN-15:50 | 6.20 | 4.71 | 0.198703E+09 | 322.18 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.583411E+09 | 3485.02 | 27-FEB-15:30 | 19.70 | 12.30 | 0.193119E+09 | 347.83 | 28-FEB-14:30 | 14.15 | 11.19 |
March | 0.127113E+10 | 5007.30 | 14-MAR-16:00 | 17.20 | 10.94 | 0.252961E+09 | 347.84 | 10-MAR-14:20 | 17.20 | 10.94 |
April | 0.196353E+10 | 7789.15 | 26-APR-16:00 | 24.40 | 14.49 | 0.241691E+09 | 347.85 | 28-APR-09:20 | 11.70 | 11.07 |
May | 0.303286E+10 | 14572.02 | 07-MAY-16:41 | 21.78 | 16.19 | 0.272249E+09 | 347.85 | 05-MAY-09:20 | 21.78 | 16.19 |
June | 0.338874E+10 | 12147.89 | 18-JUN-17:22 | 16.95 | 12.25 | 0.274324E+09 | 347.86 | 05-JUN-13:00 | 16.95 | 12.25 |
July | 0.436064E+10 | 13726.49 | 23-JUL-17:12 | 26.50 | 15.70 | 0.256068E+09 | 347.86 | 31-JUL-09:20 | 22.57 | 17.16 |
August | 0.419570E+10 | 13375.00 | 06-AUG-17:42 | 23.73 | 15.23 | 0.287072E+09 | 347.88 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.280226E+10 | 12864.02 | 10-SEP-16:12 | 22.20 | 14.38 | 0.251599E+09 | 347.85 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.147941E+10 | 6471.01 | 04-OCT-16:00 | 21.10 | 11.40 | 0.244708E+09 | 347.85 | 04-OCT-09:20 | 21.10 | 11.40 |
November | 0.682426E+09 | 2789.14 | 04-NOV-15:30 | 20.55 | 15.94 | 0.213952E+09 | 347.84 | 08-NOV-14:00 | 9.40 | 8.82 |
December | 0.368731E+09 | 1243.12 | 05-DEC-15:30 | 8.05 | 5.82 | 0.195704E+09 | 347.63 | 05-DEC-14:00 | 8.05 | 5.82 |
Annual Sum or Average | 0.244086E+11 | 0.288215E+10 | ||||||||
Minimum of Months | 0.279762E+09 | 810.36 | 6.20 | 4.71 | 0.193119E+09 | 322.18 | 6.10 | 4.61 | ||
Maximum of Months | 0.436064E+10 | 14572.02 | 26.50 | 16.19 | 0.287072E+09 | 347.88 | 23.80 | 17.16 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202391E+09 | 7468.96 | 02-JAN-06:11 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.202391E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.202391E+09 | 7468.96 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274718E+10 | 9623.39 | 09-JAN-06:07 | -1.5 |
February | 0.159447E+10 | 9669.01 | 21-FEB-06:10 | 1.70 |
March | 0.104450E+10 | 5443.68 | 06-MAR-07:04 | 6.70 |
April | 0.579019E+09 | 2890.64 | 19-APR-05:03 | 1.78 |
May | 0.361476E+09 | 3062.55 | 14-MAY-07:33 | 13.67 |
June | 0.208021E+09 | 2850.72 | 25-JUN-07:23 | 14.75 |
July | 0.150095E+09 | 3456.10 | 23-JUL-06:17 | 14.63 |
August | 0.180666E+09 | 3333.28 | 06-AUG-08:62 | 14.38 |
September | 0.366457E+09 | 3768.45 | 10-SEP-08:32 | 15.53 |
October | 0.767049E+09 | 2692.02 | 12-OCT-05:03 | 6.78 |
November | 0.149709E+10 | 8606.14 | 24-NOV-07:06 | 1.20 |
December | 0.238080E+10 | 9491.27 | 26-DEC-06:10 | -0.8 |
Annual Sum or Average | 0.118768E+11 | |||
Minimum of Months | 0.150095E+09 | 2692.02 | -1.5 | |
Maximum of Months | 0.274718E+10 | 9669.01 | 15.53 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155678E+10 | 7923.55 | 02-JAN-09:10 | 6.70 |
February | 0.947718E+09 | 5084.71 | 21-FEB-07:12 | 1.50 |
March | 0.681266E+09 | 2311.02 | 14-MAR-10:05 | 10.28 |
April | 0.251884E+09 | 3164.76 | 02-APR-13:13 | 18.90 |
May | 47664710.29 | 3574.61 | 29-MAY-17:02 | 16.60 |
June | 18663112.46 | 2515.31 | 18-JUN-16:42 | 17.38 |
July | 27034593.13 | 3090.05 | 30-JUL-15:23 | 27.50 |
August | 20563456.11 | 4119.78 | 13-AUG-10:52 | 24.90 |
September | 45665932.41 | 4975.58 | 10-SEP-10:13 | 17.77 |
October | 0.350438E+09 | 4370.74 | 08-OCT-12:53 | 17.80 |
November | 0.817072E+09 | 2442.82 | 11-NOV-11:45 | 4.72 |
December | 0.118611E+10 | 5631.78 | 26-DEC-07:19 | -1.5 |
Annual Sum or Average | 0.595086E+10 | |||
Minimum of Months | 18663112.46 | 2311.02 | -1.5 | |
Maximum of Months | 0.155678E+10 | 7923.55 | 27.50 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121443E+10 | 6333.24 | 02-JAN-08:10 | 6.70 |
February | 0.585490E+09 | 2181.52 | 21-FEB-08:20 | 1.47 |
March | 0.258394E+09 | 1464.84 | 28-MAR-07:07 | 3.45 |
April | 42052788.51 | 1749.45 | 02-APR-12:33 | 18.33 |
May | 12330199.79 | 1963.37 | 14-MAY-14:13 | 22.97 |
June | 14410693.46 | 1504.52 | 18-JUN-13:07 | 17.88 |
July | 18683604.92 | 2385.65 | 30-JUL-15:31 | 27.60 |
August | 13152399.04 | 2780.70 | 13-AUG-14:52 | 28.10 |
September | 14784807.68 | 3028.84 | 10-SEP-15:02 | 22.70 |
October | 97027887.36 | 2214.95 | 08-OCT-12:23 | 17.80 |
November | 0.453087E+09 | 1623.19 | 10-NOV-08:07 | 5.18 |
December | 0.799236E+09 | 2300.76 | 26-DEC-12:01 | 0.27 |
Annual Sum or Average | 0.352308E+10 | |||
Minimum of Months | 12330199.79 | 1464.84 | 0.27 | |
Maximum of Months | 0.121443E+10 | 6333.24 | 28.10 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472995E+09 | 12143.98 | 02-JAN-06:11 | 6.10 |
February | 26149672.58 | 8126.71 | 21-FEB-06:01 | 1.70 |
March | 314890.90 | 2624.09 | 06-MAR-07:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 4002387.00 | 7702.80 | 27-NOV-07:03 | 11.70 |
December | 62300654.58 | 9041.42 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.565763E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.472995E+09 | 12143.98 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121494E+10 | 19052.80 | 02-JAN-06:11 | 6.10 |
February | 0.351883E+09 | 16437.88 | 21-FEB-06:01 | 1.70 |
March | 32665408.52 | 14435.04 | 06-MAR-06:11 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 3729764.28 | 11860.85 | 23-OCT-06:03 | 10.40 |
November | 0.176060E+09 | 15156.80 | 27-NOV-06:11 | 11.70 |
December | 0.609082E+09 | 17634.39 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.238836E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.121494E+10 | 19052.80 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191368E+10 | 6896.66 | 17-JAN-05:11 | 1.50 |
February | 0.858177E+09 | 6793.52 | 21-FEB-05:51 | 1.70 |
March | 0.177719E+09 | 6033.38 | 06-MAR-06:11 | 6.70 |
April | 27587994.44 | 5263.71 | 18-APR-06:02 | 3.40 |
May | 466611.49 | 3110.74 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 148655.23 | 436.83 | 28-SEP-06:03 | 8.40 |
October | 44150670.39 | 5217.85 | 30-OCT-06:03 | 7.20 |
November | 0.565378E+09 | 6268.51 | 24-NOV-06:11 | 1.83 |
December | 0.143108E+10 | 6960.43 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.501839E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.191368E+10 | 6960.43 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115574E+10 | 6344.97 | 17-JAN-05:11 | 1.50 |
February | 0.478418E+09 | 6194.34 | 21-FEB-05:51 | 1.70 |
March | 84299571.87 | 5242.53 | 06-MAR-06:11 | 6.70 |
April | 11449161.03 | 4200.33 | 18-APR-06:02 | 3.40 |
May | 359251.64 | 2395.01 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 131617.69 | 402.47 | 28-SEP-06:03 | 8.40 |
October | 27654527.36 | 4123.87 | 16-OCT-06:03 | 6.60 |
November | 0.340543E+09 | 5562.31 | 24-NOV-06:11 | 1.83 |
December | 0.871673E+09 | 6437.44 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.297026E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.115574E+10 | 6437.44 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142983E+10 | 9496.64 | 17-JAN-05:11 | 1.50 |
February | 0.573899E+09 | 9054.57 | 21-FEB-05:51 | 1.70 |
March | 0.123860E+09 | 7839.37 | 06-MAR-06:11 | 6.70 |
April | 23586317.12 | 6363.83 | 18-APR-06:02 | 3.40 |
May | 521492.34 | 3476.62 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 30129562.30 | 6238.73 | 16-OCT-06:03 | 6.60 |
November | 0.412023E+09 | 8272.45 | 24-NOV-06:11 | 1.83 |
December | 0.109351E+10 | 9582.96 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.368736E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.142983E+10 | 9582.96 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119718E+10 | 6539.72 | 17-JAN-05:11 | 1.50 |
February | 0.508562E+09 | 6327.08 | 21-FEB-05:51 | 1.70 |
March | 0.110746E+09 | 5357.44 | 06-MAR-06:11 | 6.70 |
April | 18639151.52 | 4224.03 | 18-APR-06:02 | 3.40 |
May | 392280.65 | 2500.47 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 1714.48 | 8.57 | 28-SEP-06:03 | 8.40 |
October | 27670991.89 | 4133.19 | 16-OCT-06:03 | 6.60 |
November | 0.360462E+09 | 5681.12 | 24-NOV-06:11 | 1.83 |
December | 0.900357E+09 | 6639.00 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.312401E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.119718E+10 | 6639.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136630E+10 | 5233.17 | 02-JAN-06:11 | 6.10 |
February | 0.442263E+09 | 4680.22 | 21-FEB-06:01 | 1.70 |
March | 48636303.96 | 4203.31 | 06-MAR-06:11 | 6.70 |
April | 3762592.94 | 3929.26 | 19-APR-06:02 | 2.48 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 648891.31 | 2511.02 | 30-OCT-06:03 | 7.20 |
November | 85415202.54 | 4205.22 | 24-NOV-06:11 | 1.83 |
December | 0.543301E+09 | 4683.27 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.249032E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.136630E+10 | 5233.17 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.822629E+09 | 4860.11 | 02-JAN-06:11 | 6.10 |
February | 0.207115E+09 | 4019.40 | 21-FEB-06:01 | 1.70 |
March | 16368673.78 | 3443.22 | 06-MAR-06:11 | 6.70 |
April | 971214.80 | 3079.40 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 52642.30 | 350.95 | 31-OCT-06:03 | 10.18 |
November | 50624921.01 | 3500.28 | 24-NOV-06:11 | 1.83 |
December | 0.344761E+09 | 4133.01 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.144252E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.822629E+09 | 4860.11 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307716E+10 | 7601.42 | 17-JAN-07:50 | 1.70 |
February | 0.163493E+10 | 7403.66 | 14-FEB-07:10 | 0.68 |
March | 0.108780E+10 | 6826.42 | 01-MAR-07:10 | -0.1 |
April | 0.603505E+09 | 6485.79 | 19-APR-06:10 | 2.48 |
May | 0.391019E+09 | 5717.08 | 18-MAY-06:10 | 5.68 |
June | 0.189545E+09 | 4839.36 | 15-JUN-06:10 | 9.60 |
July | 28319531.29 | 4495.92 | 03-JUL-06:07 | 11.88 |
August | 47773697.90 | 4564.83 | 03-AUG-06:06 | 11.82 |
September | 0.172658E+09 | 5156.60 | 28-SEP-06:10 | 8.40 |
October | 0.555518E+09 | 5609.34 | 24-OCT-06:10 | 6.28 |
November | 0.140199E+10 | 7397.62 | 24-NOV-07:10 | 1.20 |
December | 0.225202E+10 | 7954.06 | 26-DEC-07:50 | -1.2 |
Annual Sum or Average | 0.114422E+11 | |||
Minimum of Months | 28319531.29 | 4495.92 | -1.2 | |
Maximum of Months | 0.307716E+10 | 7954.06 | 11.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.830183E+09 | 5017.94 | 02-JAN-06:11 | 6.10 |
February | 0.212586E+09 | 4055.67 | 21-FEB-06:01 | 1.70 |
March | 21538885.08 | 3506.64 | 06-MAR-06:11 | 6.70 |
April | 1510733.13 | 3089.69 | 19-APR-06:02 | 2.48 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 52570671.55 | 3519.52 | 24-NOV-06:11 | 1.83 |
December | 0.332582E+09 | 4223.53 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.145097E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.830183E+09 | 5017.94 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100266E+10 | 5604.03 | 02-JAN-06:11 | 6.10 |
February | 0.280665E+09 | 5058.67 | 21-FEB-06:01 | 1.70 |
March | 23329257.14 | 4470.92 | 06-MAR-06:11 | 6.70 |
April | 972988.71 | 4074.35 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 2190170.41 | 4080.39 | 30-OCT-06:03 | 7.20 |
November | 0.126684E+09 | 4651.85 | 24-NOV-06:11 | 1.83 |
December | 0.513784E+09 | 5265.60 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.195028E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.100266E+10 | 5604.03 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.614321E+09 | 5323.80 | 02-JAN-06:11 | 6.10 |
February | 0.161380E+09 | 4528.83 | 21-FEB-06:01 | 1.70 |
March | 11917712.73 | 3690.93 | 06-MAR-06:11 | 6.70 |
April | 365852.61 | 2846.56 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 1515167.67 | 2426.58 | 30-OCT-06:03 | 7.20 |
November | 81553434.47 | 3976.57 | 24-NOV-06:11 | 1.83 |
December | 0.338450E+09 | 4870.97 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.120950E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.614321E+09 | 5323.80 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.716851E+09 | 7750.68 | 02-JAN-06:11 | 6.10 |
February | 0.182199E+09 | 6405.45 | 21-FEB-06:01 | 1.70 |
March | 14989313.57 | 5438.43 | 06-MAR-06:11 | 6.70 |
April | 757687.76 | 3757.65 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 656250.97 | 1366.31 | 16-OCT-06:03 | 6.60 |
November | 86624227.32 | 5790.61 | 24-NOV-06:11 | 1.83 |
December | 0.399581E+09 | 6962.78 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.140166E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.716851E+09 | 7750.68 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.620942E+09 | 5322.46 | 02-JAN-06:11 | 6.10 |
February | 0.167497E+09 | 4470.16 | 21-FEB-06:01 | 1.70 |
March | 14972705.50 | 3680.89 | 06-MAR-06:11 | 6.70 |
April | 804937.75 | 3073.96 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 1107228.16 | 1766.97 | 30-OCT-06:03 | 7.20 |
November | 83768263.49 | 3945.55 | 24-NOV-06:11 | 1.83 |
December | 0.331202E+09 | 4858.12 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.122029E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.620942E+09 | 5322.46 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.159593E+11 | 11206.55 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.144673E+11 | 11206.55 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.165050E+11 | 11206.55 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.154860E+11 | 11206.55 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.162322E+11 | 11206.55 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.159146E+11 | 11206.55 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.158014E+11 | 11206.55 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.165050E+11 | 11206.55 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.154816E+11 | 11206.55 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.159615E+11 | 11206.55 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.155311E+11 | 11206.55 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.157992E+11 | 11206.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.189644E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.144673E+11 | 11206.55 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.165050E+11 | 11206.55 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.489237E+09 | 735.45 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.400063E+09 | 668.03 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.436247E+09 | 587.25 | 22-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370257E+09 | 471.46 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.388533E+09 | 382.52 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.379498E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.357720E+09 | 409.74 | 12-JUL-08:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.403172E+09 | 405.84 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.382346E+09 | 591.74 | 25-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.427662E+09 | 726.22 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.472094E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.490688E+09 | 735.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.499752E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.357720E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.490688E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.300179E+09 | 465.60 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.249773E+09 | 427.38 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274616E+09 | 355.50 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234471E+09 | 250.52 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.247223E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241815E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227894E+09 | 240.19 | 12-JUL-08:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256560E+09 | 249.67 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.240332E+09 | 359.41 | 25-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.266844E+09 | 458.26 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.291999E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.299474E+09 | 465.60 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.313118E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.227894E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.300179E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.462988E+09 | 735.45 | 02-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.385787E+09 | 652.24 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.431019E+09 | 580.54 | 22-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.370433E+09 | 412.66 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.390385E+09 | 383.27 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.381834E+09 | 375.11 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.361159E+09 | 406.11 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.405725E+09 | 404.97 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.380090E+09 | 586.70 | 25-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.416659E+09 | 724.47 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.451318E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.459630E+09 | 735.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.489703E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.361159E+09 | 375.11 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.462988E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.300106E+09 | 465.57 | 02-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.247464E+09 | 411.77 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274487E+09 | 377.50 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234373E+09 | 320.97 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.246292E+09 | 249.34 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240583E+09 | 245.05 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227802E+09 | 331.10 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.255743E+09 | 327.17 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241861E+09 | 379.66 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.267118E+09 | 459.85 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.290920E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.299203E+09 | 465.57 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.312595E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227802E+09 | 245.05 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.300106E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.486307E+09 | 735.45 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.398204E+09 | 665.37 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.434899E+09 | 581.53 | 22-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.369745E+09 | 412.20 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.388234E+09 | 379.16 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.379296E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.357436E+09 | 407.75 | 12-JUL-08:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.402764E+09 | 403.59 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.381570E+09 | 586.24 | 25-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.425734E+09 | 725.87 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.469577E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.487815E+09 | 735.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.498158E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.357436E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.487815E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.299115E+09 | 465.60 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.249043E+09 | 426.19 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274101E+09 | 351.84 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234222E+09 | 248.89 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.247002E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241615E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227672E+09 | 237.73 | 12-JUL-08:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256260E+09 | 247.97 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.239922E+09 | 355.90 | 25-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.266123E+09 | 458.01 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.291105E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.298317E+09 | 465.60 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.312450E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.227672E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.299115E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.461325E+09 | 735.45 | 02-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.384872E+09 | 648.34 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.430254E+09 | 574.50 | 22-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.370019E+09 | 410.72 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.390000E+09 | 379.95 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.381455E+09 | 371.42 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.360762E+09 | 403.92 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.405269E+09 | 402.67 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.379600E+09 | 580.95 | 25-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.415745E+09 | 724.03 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.450051E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.458102E+09 | 735.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.488745E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.360762E+09 | 371.42 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.461325E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.298981E+09 | 465.57 | 02-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.246693E+09 | 410.11 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.273893E+09 | 374.81 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234031E+09 | 316.58 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.246090E+09 | 247.76 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240318E+09 | 243.30 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227441E+09 | 327.21 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.255448E+09 | 323.01 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241321E+09 | 377.04 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.266356E+09 | 459.67 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.289839E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.297909E+09 | 465.57 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.311832E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227441E+09 | 243.30 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.298981E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.489234E+09 | 735.45 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.400061E+09 | 668.03 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.436245E+09 | 587.23 | 22-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370256E+09 | 471.44 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.388533E+09 | 382.51 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.379498E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.357720E+09 | 409.73 | 12-JUL-08:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.403172E+09 | 405.83 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.382345E+09 | 591.72 | 25-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.427660E+09 | 726.22 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.472091E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.490685E+09 | 735.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.499750E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.357720E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.490685E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.300178E+09 | 465.60 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.249773E+09 | 427.37 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274615E+09 | 355.50 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234470E+09 | 250.52 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.247222E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241815E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227894E+09 | 240.18 | 12-JUL-08:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256559E+09 | 249.66 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.240332E+09 | 359.40 | 25-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.266843E+09 | 458.26 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.291997E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.299473E+09 | 465.60 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.313117E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.227894E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.300178E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.462986E+09 | 735.45 | 02-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.385786E+09 | 652.23 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.431018E+09 | 580.53 | 22-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.370433E+09 | 412.66 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.390385E+09 | 383.26 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.381834E+09 | 375.10 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.361159E+09 | 406.11 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.405724E+09 | 404.96 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.380090E+09 | 586.68 | 25-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.416658E+09 | 724.47 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.451316E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.459629E+09 | 735.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.489702E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.361159E+09 | 375.10 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.462986E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.300104E+09 | 465.57 | 02-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.247463E+09 | 411.76 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274486E+09 | 377.49 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234373E+09 | 320.96 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.246292E+09 | 249.33 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240582E+09 | 245.05 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227802E+09 | 331.09 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.255743E+09 | 327.16 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241861E+09 | 379.65 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.267117E+09 | 459.85 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.290898E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.299201E+09 | 465.57 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.312592E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227802E+09 | 245.05 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.300104E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.159593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.144673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.165050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.154860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.162322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.159146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.158014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.165050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.154816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.159615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.155311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.157992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.189644E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.144673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.165050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.489237E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372380E+09 |
February | 0.901968E+09 | 0.400063E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336662E+09 |
March | 0.107774E+10 | 0.436247E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336989E+09 |
April | 0.956342E+09 | 0.370257E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 739179.65 | 0.331986E+09 |
May | 0.103597E+10 | 0.388533E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19006.68 | 0.269761E+09 |
June | 0.103308E+10 | 0.379498E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210035.16 | 0.225805E+09 |
July | 0.959235E+09 | 0.357720E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2726971.02 | 0.189390E+09 |
August | 0.107774E+10 | 0.403172E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4765364.90 | 0.153419E+09 |
September | 0.956342E+09 | 0.382346E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19426.32 | 0.123435E+09 |
October | 0.994195E+09 | 0.427662E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270793E+09 |
November | 0.984487E+09 | 0.472094E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295267E+09 |
December | 0.959235E+09 | 0.490688E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318363E+09 |
Annual Sum or Average | 0.119305E+11 | 0.499752E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8479983.73 | 0.322425E+10 |
Minimum of Months | 0.901968E+09 | 0.357720E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123435E+09 |
Maximum of Months | 0.107774E+10 | 0.490688E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4765364.90 | 0.372380E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.300179E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248307E+09 |
February | 0.571020E+09 | 0.249773E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228178E+09 |
March | 0.682301E+09 | 0.274616E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228469E+09 |
April | 0.605444E+09 | 0.234471E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 392324.15 | 0.226361E+09 |
May | 0.655854E+09 | 0.247223E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12672.74 | 0.183366E+09 |
June | 0.654023E+09 | 0.241815E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140027.77 | 0.154233E+09 |
July | 0.607275E+09 | 0.227894E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1297798.64 | 0.128999E+09 |
August | 0.682301E+09 | 0.256560E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2994935.56 | 0.105052E+09 |
September | 0.605444E+09 | 0.240332E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12951.89 | 84137680.72 |
October | 0.629407E+09 | 0.266844E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183891E+09 |
November | 0.623262E+09 | 0.291999E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197403E+09 |
December | 0.607275E+09 | 0.299474E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212564E+09 |
Annual Sum or Average | 0.755301E+10 | 0.313118E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4850710.75 | 0.218096E+10 |
Minimum of Months | 0.571020E+09 | 0.227894E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84137680.72 |
Maximum of Months | 0.682301E+09 | 0.300179E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2994935.56 | 0.248307E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.462988E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382883E+09 |
February | 0.901968E+09 | 0.385787E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360232E+09 |
March | 0.107774E+10 | 0.431019E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352786E+09 |
April | 0.956342E+09 | 0.370433E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 455080.94 | 0.344761E+09 |
May | 0.103597E+10 | 0.390385E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19002.77 | 0.276737E+09 |
June | 0.103308E+10 | 0.381834E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210020.56 | 0.230409E+09 |
July | 0.959235E+09 | 0.361159E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1890827.22 | 0.194554E+09 |
August | 0.107774E+10 | 0.405725E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4454937.05 | 0.159062E+09 |
September | 0.956342E+09 | 0.380090E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19380.67 | 0.130070E+09 |
October | 0.994195E+09 | 0.416659E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288085E+09 |
November | 0.984487E+09 | 0.451318E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305147E+09 |
December | 0.959235E+09 | 0.459630E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329679E+09 |
Annual Sum or Average | 0.119305E+11 | 0.489703E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7049249.21 | 0.335440E+10 |
Minimum of Months | 0.901968E+09 | 0.361159E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130070E+09 |
Maximum of Months | 0.107774E+10 | 0.462988E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4454937.05 | 0.382883E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.300106E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249095E+09 |
February | 0.570983E+09 | 0.247464E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229332E+09 |
March | 0.682256E+09 | 0.274487E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229766E+09 |
April | 0.605404E+09 | 0.234373E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 197978.25 | 0.227632E+09 |
May | 0.655811E+09 | 0.246292E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12671.31 | 0.187006E+09 |
June | 0.653980E+09 | 0.240583E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140022.49 | 0.155262E+09 |
July | 0.607235E+09 | 0.227802E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1270200.47 | 0.133202E+09 |
August | 0.682256E+09 | 0.255743E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2992939.95 | 0.107624E+09 |
September | 0.605404E+09 | 0.241861E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12951.66 | 86681395.68 |
October | 0.629366E+09 | 0.267118E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185471E+09 |
November | 0.623221E+09 | 0.290920E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198083E+09 |
December | 0.607235E+09 | 0.299203E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213358E+09 |
Annual Sum or Average | 0.755252E+10 | 0.312595E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4626764.12 | 0.220251E+10 |
Minimum of Months | 0.570983E+09 | 0.227802E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86681395.68 |
Maximum of Months | 0.682256E+09 | 0.300106E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2992939.95 | 0.249095E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.486307E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208053E+09 |
February | 0.901968E+09 | 0.398204E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188428E+09 |
March | 0.107774E+10 | 0.434899E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182682E+09 |
April | 0.956342E+09 | 0.369745E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 481972.04 | 0.176380E+09 |
May | 0.103597E+10 | 0.388234E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11815.97 | 0.142587E+09 |
June | 0.103308E+10 | 0.379296E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118677.65 | 0.119534E+09 |
July | 0.959235E+09 | 0.357436E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2169900.24 | 0.100376E+09 |
August | 0.107774E+10 | 0.402764E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2803326.40 | 81787566.82 |
September | 0.956342E+09 | 0.381570E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11771.81 | 67309405.50 |
October | 0.994195E+09 | 0.425734E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154116E+09 |
November | 0.984487E+09 | 0.469577E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170672E+09 |
December | 0.959235E+09 | 0.487815E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181879E+09 |
Annual Sum or Average | 0.119305E+11 | 0.498158E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5597464.10 | 0.177380E+10 |
Minimum of Months | 0.901968E+09 | 0.357436E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67309405.50 |
Maximum of Months | 0.107774E+10 | 0.487815E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2803326.40 | 0.208053E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.299115E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138836E+09 |
February | 0.571020E+09 | 0.249043E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128135E+09 |
March | 0.682301E+09 | 0.274101E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125881E+09 |
April | 0.605444E+09 | 0.234222E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 234590.21 | 0.123665E+09 |
May | 0.655854E+09 | 0.247002E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7877.06 | 99123352.03 |
June | 0.654023E+09 | 0.241615E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79117.89 | 83997564.50 |
July | 0.607275E+09 | 0.227672E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 813551.85 | 69873000.78 |
August | 0.682301E+09 | 0.256260E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1629344.93 | 57810071.35 |
September | 0.605444E+09 | 0.239922E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7847.76 | 46826365.00 |
October | 0.629407E+09 | 0.266123E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106096E+09 |
November | 0.623262E+09 | 0.291105E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114657E+09 |
December | 0.607275E+09 | 0.298317E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121719E+09 |
Annual Sum or Average | 0.755301E+10 | 0.312450E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2772329.71 | 0.121662E+10 |
Minimum of Months | 0.571020E+09 | 0.227672E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46826365.00 |
Maximum of Months | 0.682301E+09 | 0.299115E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1629344.93 | 0.138836E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.461325E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393333E+10 |
February | 0.901968E+09 | 0.384872E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345770E+10 |
March | 0.107774E+10 | 0.430254E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368319E+10 |
April | 0.956342E+09 | 0.370019E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14214537.80 | 0.278132E+10 |
May | 0.103597E+10 | 0.390000E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1604570.03 | 0.246169E+10 |
June | 0.103308E+10 | 0.381455E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15758604.03 | 0.188954E+10 |
July | 0.959235E+09 | 0.360762E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93303635.98 | 0.122049E+10 |
August | 0.107774E+10 | 0.405269E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254798E+09 | 0.117090E+10 |
September | 0.956342E+09 | 0.379600E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3499313.14 | 0.177520E+10 |
October | 0.994195E+09 | 0.415745E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281491E+10 |
November | 0.984487E+09 | 0.450051E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348622E+10 |
December | 0.959235E+09 | 0.458102E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381702E+10 |
Annual Sum or Average | 0.119305E+11 | 0.488745E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383179E+09 | 0.324915E+11 |
Minimum of Months | 0.901968E+09 | 0.360762E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117090E+10 |
Maximum of Months | 0.107774E+10 | 0.461325E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254798E+09 | 0.393333E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.298981E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139243E+09 |
February | 0.570983E+09 | 0.246693E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128465E+09 |
March | 0.682256E+09 | 0.273893E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126415E+09 |
April | 0.605404E+09 | 0.234031E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 126780.66 | 0.123707E+09 |
May | 0.655811E+09 | 0.246090E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7877.44 | 0.102200E+09 |
June | 0.653980E+09 | 0.240318E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79118.27 | 84390246.98 |
July | 0.607235E+09 | 0.227441E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 742622.39 | 73709081.07 |
August | 0.682256E+09 | 0.255448E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1631211.02 | 59697913.08 |
September | 0.605404E+09 | 0.241321E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7847.72 | 48683873.92 |
October | 0.629366E+09 | 0.266356E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107041E+09 |
November | 0.623221E+09 | 0.289839E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114976E+09 |
December | 0.607235E+09 | 0.297909E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122053E+09 |
Annual Sum or Average | 0.755252E+10 | 0.311832E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2595457.50 | 0.123058E+10 |
Minimum of Months | 0.570983E+09 | 0.227441E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48683873.92 |
Maximum of Months | 0.682256E+09 | 0.298981E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1631211.02 | 0.139243E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.489234E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326409E+09 |
February | 0.901968E+09 | 0.400061E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298468E+09 |
March | 0.107774E+10 | 0.436245E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297904E+09 |
April | 0.956342E+09 | 0.370256E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 647005.56 | 0.290164E+09 |
May | 0.103597E+10 | 0.388533E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17144.66 | 0.232362E+09 |
June | 0.103308E+10 | 0.379498E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 180270.07 | 0.192896E+09 |
July | 0.959235E+09 | 0.357720E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2760489.51 | 0.161772E+09 |
August | 0.107774E+10 | 0.403172E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4080062.92 | 0.131978E+09 |
September | 0.956342E+09 | 0.382345E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17284.71 | 0.107741E+09 |
October | 0.994195E+09 | 0.427660E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242438E+09 |
November | 0.984487E+09 | 0.472091E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264344E+09 |
December | 0.959235E+09 | 0.490685E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283012E+09 |
Annual Sum or Average | 0.119305E+11 | 0.499750E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7702257.43 | 0.282949E+10 |
Minimum of Months | 0.901968E+09 | 0.357720E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107741E+09 |
Maximum of Months | 0.107774E+10 | 0.490685E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4080062.92 | 0.326409E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.300178E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217663E+09 |
February | 0.421807E+09 | 0.249773E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202585E+09 |
March | 0.502994E+09 | 0.274615E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202201E+09 |
April | 0.447140E+09 | 0.234470E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 340184.52 | 0.197795E+09 |
May | 0.484071E+09 | 0.247222E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10696.56 | 0.158038E+09 |
June | 0.482240E+09 | 0.241815E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115716.96 | 0.131903E+09 |
July | 0.448971E+09 | 0.227894E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1155700.93 | 0.110402E+09 |
August | 0.502994E+09 | 0.256559E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2434282.56 | 90446105.23 |
September | 0.447140E+09 | 0.240332E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10967.34 | 73480275.29 |
October | 0.465148E+09 | 0.266843E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164616E+09 |
November | 0.460569E+09 | 0.291997E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177118E+09 |
December | 0.448971E+09 | 0.299473E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189209E+09 |
Annual Sum or Average | 0.557719E+10 | 0.313117E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4067548.88 | 0.191546E+10 |
Minimum of Months | 0.421807E+09 | 0.227894E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73480275.29 |
Maximum of Months | 0.502994E+09 | 0.300178E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2434282.56 | 0.217663E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.462986E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336105E+09 |
February | 0.901968E+09 | 0.385786E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318503E+09 |
March | 0.107774E+10 | 0.431018E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310590E+09 |
April | 0.956342E+09 | 0.370433E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 406475.08 | 0.300286E+09 |
May | 0.103597E+10 | 0.390385E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17141.08 | 0.238287E+09 |
June | 0.103308E+10 | 0.381834E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 180256.17 | 0.197032E+09 |
July | 0.959235E+09 | 0.361159E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1617084.52 | 0.166182E+09 |
August | 0.107774E+10 | 0.405724E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3742273.58 | 0.136731E+09 |
September | 0.956342E+09 | 0.380090E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17161.06 | 0.112997E+09 |
October | 0.994195E+09 | 0.416658E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255777E+09 |
November | 0.984487E+09 | 0.451316E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272885E+09 |
December | 0.959235E+09 | 0.459629E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293002E+09 |
Annual Sum or Average | 0.119305E+11 | 0.489702E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5980391.49 | 0.293838E+10 |
Minimum of Months | 0.901968E+09 | 0.361159E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112997E+09 |
Maximum of Months | 0.107774E+10 | 0.462986E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3742273.58 | 0.336105E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.300104E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218309E+09 |
February | 0.570983E+09 | 0.247463E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203028E+09 |
March | 0.682256E+09 | 0.274486E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202712E+09 |
April | 0.605404E+09 | 0.234373E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167808.05 | 0.198591E+09 |
May | 0.655811E+09 | 0.246292E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11429.07 | 0.161078E+09 |
June | 0.653980E+09 | 0.240582E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120180.45 | 0.132758E+09 |
July | 0.607235E+09 | 0.227802E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1107189.17 | 0.113802E+09 |
August | 0.682256E+09 | 0.255743E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2521164.64 | 92555109.26 |
September | 0.605404E+09 | 0.241861E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11523.00 | 75343526.12 |
October | 0.629366E+09 | 0.267117E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165468E+09 |
November | 0.623221E+09 | 0.290898E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177212E+09 |
December | 0.607235E+09 | 0.299201E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189628E+09 |
Annual Sum or Average | 0.755252E+10 | 0.312592E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3939294.38 | 0.193048E+10 |
Minimum of Months | 0.570983E+09 | 0.227802E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75343526.12 |
Maximum of Months | 0.682256E+09 | 0.300104E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2521164.64 | 0.218309E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449858E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418311E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414000E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592683.77 | 0.396304E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1534.87 | 0.314945E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87613.33 | 0.260387E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2501619.33 | 0.218456E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3948893.68 | 0.180368E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.49 | 0.149053E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341332E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372994E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397844E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7132894.47 | 0.391385E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149053E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3948893.68 | 0.449858E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554815E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513877E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516690E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 885781.50 | 0.500144E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2014.97 | 0.401435E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111920.19 | 0.333291E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3134559.14 | 0.279108E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5088805.32 | 0.230035E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.21 | 0.187984E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419943E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453289E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485257E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9223752.32 | 0.487587E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187984E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5088805.32 | 0.554815E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558485E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518445E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521725E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416244.52 | 0.518269E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425892E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36891.86 | 0.356375E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1127576.33 | 0.300229E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3652618.25 | 0.240161E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193577E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421308E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448452E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480539E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5233330.96 | 0.498346E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193577E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3652618.25 | 0.558485E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 11206.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 11206.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 11206.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 11206.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 11206.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 11206.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 11206.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 11206.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 11206.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 11206.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 11206.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 11206.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 11206.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 11206.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 630.34 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 668.03 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 573.69 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 587.25 | 22-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 570.06 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 471.46 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.27 | 01-APR-17:03 | 611.31 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 382.52 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 05-MAY-16:00 | 452.46 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 28-JUN-16:00 | 603.99 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 409.74 | 12-JUL-08:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.52 | 23-JUL-13:53 | 302.88 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 405.84 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 08-AUG-17:00 | 422.48 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 591.74 | 25-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 14-SEP-17:00 | 285.33 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 726.22 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 530.84 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 599.27 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 484.70 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.33 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 87.27 | 630.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 417.80 | 12-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 427.38 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 382.16 | 16-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 355.50 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 386.42 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 250.52 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.89 | 01-APR-17:03 | 412.88 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 05-MAY-16:00 | 301.46 | 22-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 28-JUN-16:00 | 401.42 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 240.19 | 12-JUL-08:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.03 | 23-JUL-14:18 | 201.08 | 02-JUL-04:00 |
August | 827.22 | 01-AUG-09:09 | 249.67 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 08-AUG-17:00 | 282.44 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 359.41 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 14-SEP-17:00 | 189.82 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 458.26 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 353.53 | 31-OCT-21:05 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 397.49 | 29-NOV-23:00 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 321.76 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.82 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 45.89 | 417.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 632.50 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 652.24 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 620.17 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 580.54 | 22-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 594.36 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 412.66 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.11 | 01-APR-17:30 | 622.44 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 383.27 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 05-MAY-16:00 | 454.78 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 375.11 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 28-JUN-16:00 | 603.36 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 406.11 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.19 | 23-JUL-14:18 | 305.70 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 404.97 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 08-AUG-17:00 | 428.93 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 586.70 | 25-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 14-SEP-17:00 | 287.51 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 724.47 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 530.93 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 599.34 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 487.60 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 375.11 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.51 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 49.19 | 632.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 417.91 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 411.77 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 382.06 | 16-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 377.50 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 385.37 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 320.97 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.13 | 01-APR-16:00 | 407.96 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 249.34 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 05-MAY-16:00 | 303.10 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 245.05 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 28-JUN-16:00 | 400.00 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 331.10 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 | 23-JUL-14:15 | 204.91 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 327.17 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 08-AUG-17:00 | 289.85 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 379.66 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 14-SEP-17:00 | 190.08 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 459.85 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 353.36 | 31-OCT-21:05 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 396.76 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 322.34 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 245.05 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.08 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 | 417.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 352.67 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 665.37 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 325.96 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 581.53 | 22-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 309.47 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 412.20 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.88 | 01-APR-17:03 | 327.13 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 379.16 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | 05-MAY-16:00 | 251.72 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 28-JUN-16:00 | 337.05 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 407.75 | 12-JUL-08:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.02 | 23-JUL-15:50 | 168.16 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 403.59 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.53 | 13-AUG-15:00 | 231.19 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 586.24 | 25-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 14-SEP-17:00 | 159.81 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 725.87 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 288.33 | 31-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 339.06 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 268.17 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.81 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 61.88 | 352.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 234.18 | 12-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 426.19 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 216.44 | 16-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 351.84 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 217.50 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 248.89 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.37 | 01-APR-17:03 | 230.16 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 05-MAY-16:00 | 167.86 | 18-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 28-JUN-16:00 | 230.13 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 237.73 | 12-JUL-08:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 | 23-JUL-15:50 | 113.01 | 02-JUL-04:00 |
August | 827.22 | 01-AUG-09:09 | 247.97 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 08-AUG-17:00 | 160.79 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 355.90 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 | 14-SEP-17:00 | 106.88 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 458.01 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 192.58 | 31-OCT-21:10 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 225.17 | 29-NOV-23:00 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 178.38 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.88 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 32.37 | 234.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 19084.28 | 06-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 648.34 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 17668.01 | 09-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 574.50 | 22-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 17271.64 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 410.72 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2392.07 | 27-APR-16:10 | 14849.90 | 19-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 379.95 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 508.32 | 05-MAY-16:10 | 12358.82 | 11-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 371.42 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2152.82 | 28-JUN-17:00 | 9615.18 | 15-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 403.92 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3809.73 | 31-JUL-16:10 | 8659.62 | 03-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 402.67 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6055.99 | 10-AUG-17:00 | 9685.86 | 01-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 580.95 | 25-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 802.39 | 14-SEP-17:00 | 10348.06 | 27-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 724.03 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12295.07 | 13-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 16132.91 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 18559.18 | 26-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 371.42 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8659.62 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6055.99 | 19084.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 234.27 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 410.11 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 215.70 | 16-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 374.81 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 213.26 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 316.58 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 | 01-APR-16:00 | 220.46 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 247.76 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 05-MAY-16:00 | 168.83 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 243.30 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 28-JUN-16:00 | 225.22 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 327.21 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.47 | 23-JUL-13:43 | 117.05 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 323.01 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 08-AUG-17:00 | 166.43 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 377.04 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 | 14-SEP-17:00 | 107.09 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 459.67 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 193.42 | 31-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 224.75 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 178.65 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 243.30 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.09 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.47 | 234.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 555.61 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 668.03 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 513.13 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 587.23 | 22-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 506.21 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 471.44 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.21 | 01-APR-17:03 | 532.59 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 382.51 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 05-MAY-16:00 | 396.26 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 28-JUN-16:00 | 532.20 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 409.73 | 12-JUL-08:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.13 | 23-JUL-16:00 | 266.93 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 405.83 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.93 | 13-AUG-15:00 | 365.86 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 591.72 | 25-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 14-SEP-17:00 | 251.68 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 726.22 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 449.65 | 31-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 524.22 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 419.34 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.68 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 77.21 | 555.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 465.60 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 368.39 | 12-JAN-24:00 |
February | 805.43 | 01-FEB-08:09 | 427.37 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 340.14 | 16-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 355.50 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 342.26 | 28-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 250.52 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.84 | 01-APR-17:03 | 359.31 | 07-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 05-MAY-16:00 | 262.55 | 18-MAY-05:00 |
June | 805.43 | 01-JUN-07:10 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 28-JUN-16:00 | 354.09 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 240.18 | 12-JUL-08:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 | 23-JUL-16:00 | 177.35 | 02-JUL-04:00 |
August | 805.43 | 01-AUG-07:10 | 249.66 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.46 | 08-AUG-17:00 | 244.74 | 11-AUG-04:00 |
September | 805.43 | 01-SEP-07:10 | 359.40 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 | 14-SEP-17:00 | 167.54 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 458.26 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 299.10 | 31-OCT-21:10 |
November | 805.43 | 01-NOV-07:10 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 347.74 | 29-NOV-23:00 |
December | 805.43 | 01-DEC-08:09 | 465.60 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 278.41 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.54 | |||||
Maximum of Months | 805.43 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 40.84 | 368.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 557.78 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 652.23 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 554.64 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 580.53 | 22-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 524.97 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 412.66 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.25 | 01-APR-17:30 | 541.39 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 383.26 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 05-MAY-16:00 | 395.33 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 375.10 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 28-JUN-16:00 | 531.80 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 406.11 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.25 | 23-JUL-15:56 | 269.20 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 404.96 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.19 | 08-AUG-17:00 | 371.18 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 586.68 | 25-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 14-SEP-17:00 | 253.43 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 724.47 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 450.11 | 31-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 524.86 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 422.97 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 375.10 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.43 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 40.25 | 557.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 368.36 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 411.76 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 338.92 | 16-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 377.49 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 341.54 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 320.96 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 | 01-APR-16:00 | 355.39 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 249.33 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 05-MAY-16:00 | 262.30 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 245.05 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 28-JUN-16:00 | 352.54 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 331.09 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.66 | 23-JUL-16:00 | 180.38 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 327.16 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.46 | 08-AUG-17:00 | 250.65 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 379.65 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 | 14-SEP-17:00 | 167.62 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 459.85 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 298.68 | 31-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 347.00 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 279.10 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 245.05 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.62 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 21.46 | 368.36 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 777.82 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 726.70 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 709.90 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.37 | 01-APR-17:03 | 735.58 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 | 05-MAY-16:00 | 552.90 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 28-JUN-15:00 | 736.88 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.13 | 23-JUL-13:53 | 369.25 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.54 | 13-AUG-15:20 | 498.59 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 14-SEP-17:00 | 342.15 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 637.78 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 732.85 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 586.25 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.15 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.37 | 777.82 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 970.40 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 895.64 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 891.52 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.11 | 01-APR-17:03 | 936.87 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 05-MAY-16:00 | 696.73 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 | 28-JUN-15:00 | 937.61 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.68 | 23-JUL-13:53 | 467.62 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.28 | 13-AUG-15:20 | 638.40 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 | 14-SEP-17:00 | 424.91 | 30-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 784.80 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 903.20 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 729.27 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.91 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.11 | 970.40 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 954.53 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 872.98 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 861.44 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.12 | 01-APR-17:03 | 939.67 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 680.75 | 22-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.16 | 28-JUN-17:00 | 904.76 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.82 | 24-JUL-14:00 | 452.44 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 08-AUG-17:00 | 635.27 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 427.96 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 804.91 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 909.81 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 756.26 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.96 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.12 | 954.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6899.85 | 13-JAN-17:00 | 6035.01 | 3488.70 | 11182.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9803.39 | 28-FEB-17:00 | 6035.01 | 3488.70 | 11182.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12787.51 | 20-MAR-07:05 | 36210.05 | 20932.21 | 67239.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30184.53 | 28-APR-06:02 | 7623.17 | 6977.40 | 44330.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31097.29 | 08-MAY-06:02 | 7623.17 | 6977.40 | 44330.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31488.73 | 12-JUN-06:02 | 6352.64 | 5814.50 | 36941.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33386.71 | 10-JUL-05:12 | 2541.06 | 1550.53 | 21793.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33290.55 | 14-AUG-05:12 | 2541.06 | 1550.53 | 21793.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33403.65 | 05-SEP-05:12 | 2541.06 | 1550.53 | 21793.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30955.21 | 10-OCT-06:02 | 7623.17 | 6977.40 | 44330.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12955.60 | 06-NOV-17:00 | 6035.01 | 3488.70 | 11182.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9363.36 | 06-DEC-15:50 | 6035.01 | 3488.70 | 11172.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6899.85 | 2541.06 | 1550.53 | 11172.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33403.65 | 36210.05 | 20932.21 | 67239.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.54 |
February | 1555.07 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.26 |
March | 2563.89 | 14-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.40 |
April | 7739.33 | 27-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.63 | 0.00 |
May | 8267.93 | 15-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.32 |
June | 8022.99 | 28-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 |
July | 9099.82 | 24-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.47 | 0.00 |
August | 9124.70 | 10-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 | 0.00 |
September | 7083.98 | 14-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.66 |
October | 4921.88 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 |
November | 2006.01 | 04-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.37 |
December | 287.88 | 02-DEC-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9124.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.47 | 420.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1671.92 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.51 |
February | 1970.85 | 10-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 |
March | 2787.11 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.60 |
April | 2587.62 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 | 0.00 |
May | 3058.76 | 15-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 |
June | 2990.85 | 28-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 0.00 |
July | 4156.82 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.18 | 0.00 |
August | 4656.62 | 14-AUG-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.35 |
September | 3413.12 | 11-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 |
October | 2051.39 | 04-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 |
November | 2039.20 | 10-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.70 |
December | 1474.19 | 06-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1474.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4656.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.18 | 68.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2233.36 | 13-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.02 |
February | 2621.55 | 10-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 |
March | 3187.18 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.97 |
April | 3076.00 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.61 |
May | 3427.31 | 15-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 |
June | 3237.40 | 12-JUN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 |
July | 4189.68 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 0.00 |
August | 4791.00 | 14-AUG-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.30 |
September | 3833.43 | 11-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 |
October | 2780.21 | 05-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 |
November | 2448.57 | 16-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 |
December | 2270.46 | 07-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2233.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4791.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 125.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5911.45 | 06-JAN-08:20 | 48280.06 | 27909.61 | 54466.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6588.01 | 28-FEB-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8196.56 | 02-MAR-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13134.07 | 27-APR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20307.45 | 08-MAY-06:02 | 7623.17 | 6977.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25918.83 | 12-JUN-06:02 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26578.20 | 10-JUL-06:02 | 7623.17 | 6977.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29108.23 | 14-AUG-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26373.07 | 11-SEP-06:01 | 8893.70 | 8140.30 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12817.72 | 04-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7788.39 | 06-NOV-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6130.27 | 06-DEC-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5911.45 | 2541.06 | 1550.53 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29108.23 | 48280.06 | 27909.61 | 54466.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5506.90 | 06-JAN-10:30 | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6404.42 | 28-FEB-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7651.46 | 02-MAR-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14607.02 | 27-APR-15:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15863.41 | 15-MAY-15:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16317.94 | 12-JUN-06:02 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25723.24 | 24-JUL-06:03 | 5082.11 | 4651.60 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26559.49 | 14-AUG-06:02 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15586.32 | 11-SEP-15:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12779.77 | 04-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6307.26 | 02-NOV-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5722.23 | 05-DEC-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5506.90 | 5082.11 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26559.49 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1002.70 | 11-JAN-16:10 | 1272.23 | 647.41 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.34 |
February | 1270.47 | 28-FEB-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1349.17 | 10-MAR-14:50 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 |
April | 4303.65 | 27-APR-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 | 0.00 |
May | 4700.35 | 15-MAY-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
June | 4932.55 | 21-JUN-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.21 | 0.00 |
July | 7408.72 | 24-JUL-06:03 | 1071.35 | 467.75 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 |
August | 5349.29 | 09-AUG-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 | 0.00 |
September | 4120.52 | 12-SEP-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 0.00 |
October | 2635.03 | 04-OCT-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 |
November | 1219.91 | 02-NOV-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.81 |
December | 952.94 | 05-DEC-15:10 | 1272.23 | 493.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 952.94 | 1071.35 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7408.72 | 1306.65 | 647.41 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 | 49.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 697.05 | 05-JAN-09:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.92 |
February | 856.31 | 27-FEB-15:50 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
March | 2796.12 | 14-MAR-09:40 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.03 |
April | 6601.88 | 27-APR-09:00 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 |
May | 11914.28 | 14-MAY-08:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.22 |
June | 12287.73 | 25-JUN-08:62 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 |
July | 12713.24 | 30-JUL-09:02 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.63 |
August | 12867.54 | 13-AUG-09:02 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.89 |
September | 12462.14 | 10-SEP-09:13 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.22 |
October | 4835.12 | 04-OCT-09:10 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 |
November | 856.27 | 02-NOV-10:40 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 |
December | 708.23 | 05-DEC-10:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 697.05 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 | |
Maximum of Months | 12867.54 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6505.96 | 20-JAN-13:25 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 |
February | 8528.59 | 27-FEB-14:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.16 |
March | 9724.97 | 01-MAR-13:35 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.92 |
April | 11611.22 | 27-APR-13:05 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 | 0.00 |
May | 18729.30 | 14-MAY-12:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.18 |
June | 10442.14 | 11-JUN-12:03 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.10 |
July | 18702.48 | 23-JUL-13:32 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 0.00 |
August | 18589.88 | 13-AUG-13:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 |
September | 19072.18 | 10-SEP-13:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.80 |
October | 16678.91 | 08-OCT-12:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.86 |
November | 8876.23 | 04-NOV-13:30 | 275.09 | 116.93 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6710.04 | 05-DEC-12:30 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6505.96 | 200.88 | 58.46 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19072.18 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 158.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 789.32 | 20-JAN-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.10 |
February | 3477.02 | 27-FEB-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.77 |
March | 5139.16 | 14-MAR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 |
April | 8021.23 | 26-APR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 0.00 |
May | 14105.84 | 07-MAY-16:52 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.91 |
June | 12685.58 | 18-JUN-17:22 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.04 |
July | 14673.31 | 23-JUL-16:52 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 |
August | 14421.59 | 06-AUG-16:42 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.87 |
September | 13544.87 | 10-SEP-16:32 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.14 |
October | 6483.06 | 04-OCT-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 |
November | 2669.37 | 04-NOV-15:30 | 84.78 | 37.01 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 |
December | 938.75 | 05-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 789.32 | 0.00 | 37.01 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14673.31 | 805.38 | 222.08 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 130.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 954.12 | 11-JAN-15:00 | 1306.65 | 399.03 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.68 |
February | 1150.53 | 28-FEB-14:10 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 |
March | 1205.03 | 10-MAR-14:40 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 |
April | 2501.49 | 27-APR-16:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 0.00 |
May | 2966.71 | 05-MAY-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
June | 3675.11 | 21-JUN-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 | 0.00 |
July | 4566.76 | 24-JUL-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.79 | 0.00 |
August | 4190.04 | 09-AUG-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 | 0.00 |
September | 3165.41 | 12-SEP-14:50 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
October | 2011.33 | 04-OCT-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 |
November | 1244.17 | 06-NOV-12:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 |
December | 959.25 | 14-DEC-13:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 954.12 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4566.76 | 1306.65 | 399.03 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 | 83.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 663.99 | 05-JAN-09:00 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 |
February | 770.02 | 27-FEB-15:40 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 |
March | 1581.73 | 25-MAR-08:30 | 254.35 | 74.03 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.02 |
April | 4878.63 | 27-APR-09:20 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 |
May | 8250.78 | 15-MAY-06:02 | 1017.38 | 444.18 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 |
June | 8337.05 | 19-JUN-06:02 | 1017.38 | 444.18 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.78 |
July | 9011.21 | 23-JUL-08:42 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.73 |
August | 10999.36 | 13-AUG-09:32 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.22 |
September | 8749.16 | 10-SEP-09:02 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.12 |
October | 4059.53 | 04-OCT-08:30 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.51 |
November | 863.03 | 02-NOV-10:40 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 |
December | 739.87 | 05-DEC-10:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 663.99 | 169.56 | 49.35 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 | |
Maximum of Months | 10999.36 | 1017.38 | 444.18 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1344.46 | 20-JAN-13:50 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1951.36 |
February | 5844.37 | 27-FEB-13:08 | 5088.93 | 1403.24 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.67 |
March | 6198.97 | 02-MAR-13:20 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1264.02 |
April | 8863.09 | 27-APR-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 222.00 | 0.00 |
May | 10551.69 | 14-MAY-14:13 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.77 |
June | 6789.72 | 28-JUN-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 75.14 | 0.00 |
July | 12623.98 | 30-JUL-13:32 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
August | 16049.31 | 13-AUG-12:52 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.75 |
September | 15952.97 | 10-SEP-15:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.61 |
October | 10849.59 | 04-OCT-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.37 |
November | 6428.25 | 04-NOV-13:40 | 137.54 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3814.17 | 05-DEC-12:00 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1557.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1344.46 | 137.54 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16049.31 | 5088.93 | 1403.24 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 222.00 | 1951.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 718.77 | 20-JAN-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.87 |
February | 1979.79 | 27-FEB-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 |
March | 2871.79 | 02-MAR-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
April | 5650.55 | 26-APR-17:30 | 84.78 | 74.03 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
May | 9366.37 | 14-MAY-17:32 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.93 |
June | 8465.16 | 18-JUN-17:52 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.34 |
July | 12176.11 | 30-JUL-18:11 | 0.00 | 98.69 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 |
August | 11875.72 | 06-AUG-17:51 | 0.00 | 86.35 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.66 |
September | 11528.31 | 10-SEP-17:02 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.05 |
October | 5712.40 | 04-OCT-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 |
November | 2186.24 | 04-NOV-15:30 | 84.78 | 37.01 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
December | 831.21 | 05-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 718.77 | 0.00 | 37.01 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 | |
Maximum of Months | 12176.11 | 805.38 | 222.08 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1046.56 | 11-JAN-15:10 | 1272.23 | 406.63 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 |
February | 1293.14 | 28-FEB-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1352.96 | 10-MAR-14:50 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 |
April | 3938.61 | 27-APR-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 | 0.00 |
May | 4279.68 | 15-MAY-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 |
June | 4723.35 | 12-JUN-06:02 | 1339.19 | 584.68 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.62 |
July | 6743.91 | 24-JUL-06:03 | 1071.35 | 467.75 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.06 |
August | 6438.11 | 14-AUG-06:02 | 1339.19 | 584.68 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 |
September | 3953.83 | 12-SEP-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 0.00 |
October | 2668.08 | 04-OCT-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.12 |
November | 1277.94 | 06-NOV-12:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.26 |
December | 1016.88 | 05-DEC-15:00 | 1306.65 | 470.00 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1016.88 | 1071.35 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6743.91 | 1339.19 | 584.68 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 | 55.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 724.55 | 20-JAN-11:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.51 |
February | 2091.85 | 08-FEB-11:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 |
March | 5703.06 | 01-MAR-13:01 | 5638.00 | 1554.64 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.93 |
April | 7250.43 | 27-APR-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 |
May | 11937.74 | 14-MAY-07:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.74 |
June | 10825.37 | 25-JUN-10:23 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.85 |
July | 12954.13 | 30-JUL-08:42 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.13 |
August | 14110.99 | 13-AUG-08:52 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.09 |
September | 11021.44 | 10-SEP-10:13 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 |
October | 5887.19 | 04-OCT-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 |
November | 3712.13 | 02-NOV-12:02 | 4027.14 | 1110.46 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.68 |
December | 801.08 | 05-DEC-11:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 724.55 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | |
Maximum of Months | 14110.99 | 5638.00 | 1554.64 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6943.55 | 20-JAN-13:20 | 5088.93 | 1403.24 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 |
February | 8603.82 | 27-FEB-14:10 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 |
March | 10034.02 | 01-MAR-13:25 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 |
April | 11162.26 | 27-APR-13:05 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 | 0.00 |
May | 17497.46 | 14-MAY-13:13 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.31 |
June | 9386.94 | 11-JUN-11:53 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.91 |
July | 13886.58 | 30-JUL-13:23 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 |
August | 18875.76 | 13-AUG-12:52 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.68 |
September | 17891.47 | 10-SEP-12:52 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.36 |
October | 17824.42 | 08-OCT-12:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.78 |
November | 9060.73 | 04-NOV-13:30 | 275.09 | 116.93 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7590.38 | 05-DEC-12:30 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6943.55 | 200.88 | 58.46 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18875.76 | 5088.93 | 1403.24 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 | 123.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 810.36 | 05-JAN-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.23 |
February | 3485.02 | 27-FEB-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 |
March | 5007.30 | 14-MAR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 |
April | 7789.15 | 26-APR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 0.00 |
May | 14572.02 | 07-MAY-16:41 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.30 |
June | 12147.89 | 18-JUN-17:22 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.70 |
July | 13726.49 | 23-JUL-17:12 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 |
August | 13375.00 | 06-AUG-17:42 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.98 |
September | 12864.02 | 10-SEP-16:12 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.03 |
October | 6471.01 | 04-OCT-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 |
November | 2789.14 | 04-NOV-15:30 | 84.78 | 37.01 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 |
December | 1243.12 | 05-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 810.36 | 0.00 | 37.01 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14572.02 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 107.70 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.849463E+11 | 69437.75 | 02-JAN-16:40 | 0.702210E+11 | 158651.65 | 17-JAN-07:19 |
February | 0.759306E+11 | 69461.50 | 27-FEB-15:20 | 0.379613E+11 | 151571.88 | 21-FEB-07:19 |
March | 0.868255E+11 | 67513.54 | 14-MAR-15:50 | 0.163855E+11 | 92329.47 | 01-MAR-07:10 |
April | 0.823893E+11 | 106543.13 | 27-APR-15:09 | 0.649051E+10 | 70548.59 | 18-APR-06:10 |
May | 0.902658E+11 | 102392.64 | 15-MAY-15:20 | 0.207075E+10 | 41325.86 | 18-MAY-06:10 |
June | 0.938798E+11 | 107264.83 | 28-JUN-15:30 | 0.501719E+09 | 17151.06 | 15-JUN-06:10 |
July | 0.101264E+12 | 126138.62 | 31-JUL-15:09 | 89889457.09 | 8801.29 | 13-JUL-06:19 |
August | 0.113167E+12 | 128668.41 | 10-AUG-15:09 | 0.124012E+09 | 13258.72 | 03-AUG-06:19 |
September | 0.903924E+11 | 107755.92 | 12-SEP-15:39 | 0.583710E+09 | 27134.42 | 28-SEP-06:10 |
October | 0.848128E+11 | 90575.94 | 04-OCT-15:09 | 0.456653E+10 | 58094.84 | 16-OCT-06:10 |
November | 0.823654E+11 | 69055.93 | 06-NOV-16:49 | 0.282533E+11 | 121493.36 | 24-NOV-07:10 |
December | 0.833509E+11 | 69261.13 | 06-DEC-16:00 | 0.542095E+11 | 168245.32 | 26-DEC-07:19 |
Annual Sum or Average | 0.106959E+13 | 0.221458E+12 | ||||
Minimum of Months | 0.759306E+11 | 67513.54 | 89889457.09 | 8801.29 | ||
Maximum of Months | 0.113167E+12 | 128668.41 | 0.702210E+11 | 168245.32 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.300844E+10 | 9871.73 | 30-JAN-11:30 | 0.00 | 0.00 |
February | 0.489241E+10 | 14029.42 | 27-FEB-12:30 | 0.00 | 0.00 |
March | 0.856267E+10 | 19758.56 | 24-MAR-12:30 | 0.00 | 0.00 |
April | 0.126577E+11 | 23186.09 | 25-APR-12:09 | 0.00 | 0.00 |
May | 0.163576E+11 | 26813.75 | 10-MAY-11:30 | 0.00 | 0.00 |
June | 0.169645E+11 | 24929.12 | 19-JUN-12:09 | 0.00 | 0.00 |
July | 0.180432E+11 | 25134.84 | 05-JUL-10:30 | 0.00 | 0.00 |
August | 0.146338E+11 | 22705.68 | 06-AUG-12:30 | 0.00 | 0.00 |
September | 0.104131E+11 | 19847.71 | 07-SEP-12:30 | 0.00 | 0.00 |
October | 0.671528E+10 | 16907.28 | 03-OCT-11:00 | 0.00 | 0.00 |
November | 0.332221E+10 | 10292.05 | 11-NOV-12:20 | 0.00 | 0.00 |
December | 0.257472E+10 | 8214.49 | 01-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.118146E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.257472E+10 | 8214.49 | 0.00 | 0.00 | |
Maximum of Months | 0.180432E+11 | 26813.75 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.146122E+11 | 0.422222E+10 | 0.554480E+11 | 0.212637E+10 | 0.334118E+10 | 0.361407E+09 | 0.00 | 252727.82 | 0.00 | 0.00 | 0.00 | 0.483470E+10 | 0.00 |
February | 0.128808E+11 | 0.329965E+10 | 0.502161E+11 | 0.192878E+10 | 0.285577E+10 | 0.211190E+09 | 0.00 | 0.123339E+09 | 0.00 | 0.00 | 0.00 | 0.441496E+10 | 0.00 |
March | 0.149822E+11 | 0.297020E+10 | 0.575730E+11 | 0.222305E+10 | 0.360779E+10 | 98997770.32 | 0.00 | 0.221204E+09 | 0.00 | 0.00 | 0.00 | 0.514908E+10 | 0.00 |
April | 0.132178E+11 | 0.227402E+10 | 0.536187E+11 | 0.206169E+10 | 0.445851E+10 | 46790620.35 | 0.00 | 0.218409E+10 | 0.00 | 0.00 | 0.00 | 0.452778E+10 | 0.00 |
May | 0.141651E+11 | 0.193555E+10 | 0.565105E+11 | 0.217419E+10 | 0.632589E+10 | 24615944.30 | 0.00 | 0.445115E+10 | 0.00 | 0.00 | 0.00 | 0.467884E+10 | 0.00 |
June | 0.140288E+11 | 0.169225E+10 | 0.554637E+11 | 0.214009E+10 | 0.781057E+10 | 15841963.68 | 0.00 | 0.824972E+10 | 0.00 | 0.00 | 0.00 | 0.447889E+10 | 0.00 |
July | 0.131634E+11 | 0.182237E+10 | 0.546543E+11 | 0.209499E+10 | 0.985531E+10 | 12810012.42 | 0.00 | 0.155299E+11 | 0.00 | 0.00 | 0.00 | 0.413044E+10 | 0.00 |
August | 0.146984E+11 | 0.214067E+10 | 0.575730E+11 | 0.222274E+10 | 0.112593E+11 | 13627982.60 | 0.00 | 0.207511E+11 | 0.00 | 0.00 | 0.00 | 0.450820E+10 | 0.00 |
September | 0.133224E+11 | 0.258687E+10 | 0.535964E+11 | 0.206062E+10 | 0.714422E+10 | 15873896.91 | 0.00 | 0.754105E+10 | 0.00 | 0.00 | 0.00 | 0.412504E+10 | 0.00 |
October | 0.140919E+11 | 0.336165E+10 | 0.554592E+11 | 0.212666E+10 | 0.429847E+10 | 36664244.74 | 0.00 | 0.105031E+10 | 0.00 | 0.00 | 0.00 | 0.438793E+10 | 0.00 |
November | 0.143574E+11 | 0.389481E+10 | 0.541547E+11 | 0.207553E+10 | 0.303620E+10 | 0.153885E+09 | 0.00 | 0.217026E+09 | 0.00 | 0.00 | 0.00 | 0.447585E+10 | 0.00 |
December | 0.142811E+11 | 0.438974E+10 | 0.546432E+11 | 0.209518E+10 | 0.306267E+10 | 0.283069E+09 | 0.00 | 64340.67 | 0.00 | 0.00 | 0.00 | 0.459593E+10 | 0.00 |
Annual Sum or Average | 0.167801E+12 | 0.345900E+11 | 0.658911E+12 | 0.253299E+11 | 0.670559E+11 | 0.127477E+10 | 0.00 | 0.603192E+11 | 0.00 | 0.00 | 0.00 | 0.543076E+11 | 0.00 |
Minimum of Months | 0.128808E+11 | 0.169225E+10 | 0.502161E+11 | 0.192878E+10 | 0.285577E+10 | 12810012.42 | 0.00 | 64340.67 | 0.00 | 0.00 | 0.00 | 0.412504E+10 | 0.00 |
Maximum of Months | 0.149822E+11 | 0.438974E+10 | 0.575730E+11 | 0.222305E+10 | 0.112593E+11 | 0.361407E+09 | 0.00 | 0.207511E+11 | 0.00 | 0.00 | 0.00 | 0.514908E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.702210E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.379613E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.163855E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.649051E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.207075E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.501719E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 89889457.09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.124012E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.583710E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.456653E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.282533E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.542095E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.221458E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 89889457.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.702210E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17672.30 | 02-JAN-16:30 | 3824.74 | 01-JAN-06:10 | 38886.07 | 02-JAN-08:09 | 1410.29 | 02-JAN-08:09 | 7283.27 | 02-JAN-07:19 | 517.92 | 09-JAN-07:49 | 0.00 | 01-JAN-00:10 |
February | 16912.03 | 02-FEB-16:00 | 3824.74 | 01-FEB-06:10 | 38886.07 | 01-FEB-08:09 | 1410.29 | 02-FEB-08:09 | 5828.29 | 21-FEB-07:10 | 518.35 | 21-FEB-07:00 | 0.00 | 01-FEB-00:10 |
March | 16150.34 | 22-MAR-07:10 | 3824.74 | 01-MAR-06:10 | 38886.07 | 01-MAR-08:09 | 1410.29 | 01-MAR-12:09 | 4725.72 | 02-MAR-15:09 | 402.06 | 06-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 14765.68 | 03-APR-07:10 | 3824.74 | 01-APR-05:10 | 38886.07 | 03-APR-07:10 | 1410.29 | 03-APR-11:09 | 17272.68 | 27-APR-14:30 | 343.12 | 19-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 14169.48 | 17-MAY-07:10 | 2323.70 | 01-MAY-19:19 | 38886.07 | 01-MAY-07:10 | 1410.29 | 01-MAY-11:09 | 19091.98 | 15-MAY-14:30 | 215.91 | 18-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 14039.82 | 29-JUN-07:10 | 2323.70 | 01-JUN-19:00 | 38886.07 | 01-JUN-07:10 | 1410.29 | 07-JUN-11:09 | 17731.33 | 28-JUN-15:20 | 100.63 | 15-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 14583.66 | 12-JUL-08:20 | 2323.70 | 01-JUL-20:10 | 38886.07 | 03-JUL-07:10 | 1410.29 | 12-JUL-11:09 | 24949.98 | 31-JUL-14:00 | 63.50 | 13-JUL-06:19 | 0.00 | 01-JUL-00:10 |
August | 14469.09 | 28-AUG-07:30 | 3824.74 | 16-AUG-05:10 | 38886.07 | 01-AUG-07:10 | 1410.29 | 01-AUG-11:09 | 25430.22 | 14-AUG-15:20 | 83.68 | 18-AUG-06:00 | 0.00 | 01-AUG-00:10 |
September | 16201.19 | 25-SEP-07:10 | 3824.74 | 01-SEP-05:10 | 38886.07 | 01-SEP-07:10 | 1410.29 | 01-SEP-11:09 | 21109.03 | 11-SEP-15:30 | 127.41 | 28-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 17571.27 | 31-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 38886.07 | 02-OCT-07:10 | 1410.29 | 11-OCT-12:09 | 14559.43 | 04-OCT-15:30 | 256.89 | 16-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 17672.30 | 06-NOV-16:49 | 3824.74 | 01-NOV-05:10 | 38886.07 | 01-NOV-07:10 | 1410.29 | 06-NOV-12:09 | 4043.68 | 24-NOV-07:10 | 464.46 | 24-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 17672.30 | 01-DEC-16:19 | 3824.74 | 01-DEC-06:10 | 38886.07 | 01-DEC-08:09 | 1410.29 | 01-DEC-08:09 | 6432.42 | 26-DEC-07:10 | 525.05 | 26-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 14039.82 | 2323.70 | 38886.07 | 1410.29 | 4043.68 | 63.50 | 0.00 | |||||||
Maximum of Months | 17672.30 | 3824.74 | 38886.07 | 1410.29 | 25430.22 | 525.05 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 186.50 | 02-JAN-20:30 | 0.00 | 0.00 | 0.00 | 6495.17 | 31-JAN-12:50 | 0.00 | 01-JAN-00:10 |
February | 7656.69 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 6517.00 | 13-FEB-12:20 | 0.00 | 01-FEB-00:10 |
March | 6986.12 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 6437.90 | 01-MAR-12:39 | 0.00 | 01-MAR-00:10 |
April | 31543.30 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 6250.77 | 03-APR-11:30 | 0.00 | 01-APR-00:10 |
May | 25561.17 | 04-MAY-14:00 | 0.00 | 0.00 | 0.00 | 6200.04 | 01-MAY-11:39 | 0.00 | 01-MAY-00:10 |
June | 30855.91 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 | 5815.78 | 01-JUN-11:20 | 0.00 | 01-JUN-00:10 |
July | 44821.86 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 5767.43 | 03-JUL-11:39 | 0.00 | 01-JUL-00:10 |
August | 46477.71 | 29-AUG-15:30 | 0.00 | 0.00 | 0.00 | 5696.28 | 31-AUG-11:39 | 0.00 | 01-AUG-00:10 |
September | 29984.63 | 13-SEP-14:09 | 0.00 | 0.00 | 0.00 | 5775.29 | 28-SEP-11:00 | 0.00 | 01-SEP-00:10 |
October | 18088.23 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 5828.86 | 31-OCT-11:20 | 0.00 | 01-OCT-00:10 |
November | 11180.61 | 04-NOV-14:09 | 0.00 | 0.00 | 0.00 | 6212.66 | 30-NOV-12:00 | 0.00 | 01-NOV-00:10 |
December | 70.09 | 29-DEC-07:10 | 0.00 | 0.00 | 0.00 | 6262.25 | 29-DEC-12:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 70.09 | 0.00 | 0.00 | 0.00 | 5696.28 | 0.00 | |||
Maximum of Months | 46477.71 | 0.00 | 0.00 | 0.00 | 6517.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 69437.75 | 02-JAN-16:40 | 17672.30 | 38861.85 | 3824.74 | 1410.29 | 2321.84 | 370.35 | 0.00 | 0.00 | 0.00 |
February | 69461.50 | 27-FEB-15:20 | 13903.46 | 38852.37 | 0.00 | 1410.29 | 3950.01 | 6.85 | 0.00 | 7476.38 | 0.00 |
March | 67513.54 | 14-MAR-15:50 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 4525.75 | 6.85 | 0.00 | 3824.57 | 0.00 |
April | 106543.13 | 27-APR-15:09 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 16407.36 | 6.85 | 0.00 | 31343.06 | 0.00 |
May | 102392.64 | 15-MAY-15:20 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 18605.53 | 6.85 | 0.00 | 24992.49 | 0.00 |
June | 107264.83 | 28-JUN-15:30 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 17679.95 | 6.85 | 0.00 | 30832.77 | 0.00 |
July | 126138.62 | 31-JUL-15:09 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 24687.04 | 6.90 | 0.00 | 43179.23 | 0.00 |
August | 128668.41 | 10-AUG-15:09 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 24584.27 | 6.91 | 0.00 | 45670.91 | 0.00 |
September | 107755.92 | 12-SEP-15:39 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 19501.73 | 6.89 | 0.00 | 29642.99 | 0.00 |
October | 90575.94 | 04-OCT-15:09 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 14365.49 | 6.85 | 0.00 | 17775.94 | 0.00 |
November | 69055.93 | 06-NOV-16:49 | 17672.30 | 38861.85 | 3824.74 | 1410.29 | 2671.83 | 6.85 | 0.00 | 0.00 | 0.00 |
December | 69261.13 | 06-DEC-16:00 | 17672.30 | 38861.85 | 3824.74 | 1410.29 | 2279.17 | 263.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 67513.54 | 13903.46 | 38852.37 | 0.00 | 1410.29 | 2279.17 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 128668.41 | 17672.30 | 38861.85 | 3824.74 | 1410.29 | 24687.04 | 370.35 | 0.00 | 45670.91 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 158651.65 | 17-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 151571.88 | 21-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 92329.47 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 70548.59 | 18-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 41325.86 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 17151.06 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 8801.29 | 13-JUL-06:19 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 13258.72 | 03-AUG-06:19 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 27134.42 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 58094.84 | 16-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 121493.36 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 168245.32 | 26-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 8801.29 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 168245.32 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.67 | 19.91 | 7.67 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.67 | 19.91 | 7.67 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.67 | 19.91 | 7.67 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 19.29 | 4.33 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.33 | 19.29 | 4.33 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.33 | 19.29 | 4.33 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 19.08 | 3.83 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
February | 0.50 | 19.56 | 0.50 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 19.65 | 1.17 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
Annual Sum or Average | 5.67 | 19.24 | 5.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 19.65 | 3.83 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 18.77 | 8.33 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
February | 2.17 | 19.09 | 2.17 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.08 | 0.33 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
December | 4.67 | 19.10 | 4.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Annual Sum or Average | 16.67 | 18.91 | 15.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.50 | 19.10 | 8.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.00 | 18.01 | 4.00 | 18.54 | 0.00 | 18.54 | 0.00 | 18.54 |
February | 0.83 | 19.49 | 0.83 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.69 | 1.17 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.60 | 2.33 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.78 | 4.67 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.88 | 3.67 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.70 | 1.17 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 18.62 | 0.33 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
December | 1.67 | 18.83 | 1.33 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Annual Sum or Average | 9.00 | 18.33 | 6.50 | 18.78 | 13.00 | 22.88 | 13.00 | 24.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 19.49 | 4.00 | 19.49 | 4.67 | 27.88 | 4.67 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 19.08 | 3.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
February | 0.33 | 19.30 | 0.33 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.49 | 1.00 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.62 | 2.67 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.48 | 2.17 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.81 | 3.67 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.93 | 3.33 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.16 | 1.67 | 28.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.64 | 0.67 | 27.64 |
November | 0.17 | 19.30 | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
December | 1.33 | 19.27 | 1.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Annual Sum or Average | 5.50 | 19.14 | 4.83 | 19.31 | 15.50 | 24.39 | 15.17 | 25.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 19.30 | 3.17 | 19.43 | 3.67 | 28.16 | 3.67 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 17.66 | 3.83 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
February | 0.50 | 19.28 | 0.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.44 | 0.33 | 27.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.03 | 3.33 | 28.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.85 | 2.17 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.26 | 3.17 | 28.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.19 | 2.00 | 28.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.76 | 2.33 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.29 | 0.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
December | 1.50 | 18.79 | 1.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Annual Sum or Average | 7.83 | 18.01 | 5.67 | 18.43 | 21.83 | 24.37 | 13.33 | 25.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 19.29 | 3.83 | 19.29 | 5.83 | 28.26 | 3.33 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.00 | 19.40 | 6.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
February | 0.33 | 19.79 | 0.33 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.71 | 0.33 | 19.71 | 0.00 | 19.71 | 0.00 | 19.71 |
Annual Sum or Average | 6.67 | 19.43 | 6.67 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 19.79 | 6.00 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 18.89 | 3.67 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.34 | 0.83 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.44 | 0.83 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.62 | 2.67 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.59 | 3.00 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.52 | 0.83 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.34 | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 4.33 | 18.91 | 3.83 | 19.15 | 8.17 | 23.35 | 8.17 | 24.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.17 | 19.34 | 3.67 | 19.34 | 3.00 | 27.62 | 3.00 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 79.00 | 18.34 | 79.00 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
February | 47.67 | 18.61 | 47.67 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
March | 37.00 | 19.13 | 37.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
April | 19.00 | 19.29 | 19.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
May | 8.17 | 19.89 | 8.17 | 19.89 | 0.50 | 20.11 | 0.50 | 20.32 |
June | 0.33 | 20.40 | 0.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.46 | 2.00 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.59 | 2.67 | 27.59 |
September | 2.00 | 19.96 | 2.00 | 19.96 | 1.83 | 22.43 | 1.83 | 23.72 |
October | 15.67 | 19.94 | 15.67 | 19.94 | 0.67 | 20.10 | 0.67 | 20.25 |
November | 47.17 | 19.08 | 47.17 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
December | 63.83 | 18.47 | 63.83 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
Annual Sum or Average | 319.83 | 18.79 | 319.83 | 18.79 | 7.67 | 18.90 | 7.67 | 19.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 0.00 | 18.34 |
Maximum of Months | 79.00 | 20.40 | 79.00 | 20.40 | 2.67 | 27.59 | 2.67 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 18.66 | 3.67 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.68 | 1.50 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.56 | 0.50 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.97 | 2.00 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.81 | 1.67 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.72 | 1.00 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.34 | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 4.67 | 18.68 | 3.83 | 19.04 | 13.17 | 24.36 | 6.67 | 25.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 19.34 | 3.67 | 19.34 | 4.17 | 27.97 | 2.00 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 19.09 | 4.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
February | 0.17 | 19.06 | 0.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 19.87 | 0.83 | 19.87 | 0.00 | 19.87 | 0.00 | 19.87 |
Annual Sum or Average | 5.17 | 19.21 | 5.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.17 | 19.87 | 4.00 | 19.87 | 0.00 | 19.87 | 0.00 | 19.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 19.20 | 2.67 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
February | 0.17 | 19.34 | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.75 | 1.33 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.63 | 2.67 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.09 | 3.00 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.89 | 3.67 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.82 | 1.33 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.90 | 0.33 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
Annual Sum or Average | 3.33 | 19.28 | 3.17 | 19.39 | 12.00 | 24.88 | 12.00 | 26.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.90 | 2.67 | 19.90 | 3.67 | 28.09 | 3.67 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 19.13 | 2.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.43 | 1.17 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.56 | 2.33 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.45 | 1.50 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.70 | 3.50 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.82 | 3.50 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.06 | 2.00 | 28.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.68 | 1.00 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.33 | 0.50 | 27.33 |
December | 0.17 | 19.35 | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Annual Sum or Average | 2.83 | 19.15 | 2.67 | 19.27 | 15.67 | 25.50 | 15.67 | 26.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.35 | 2.50 | 19.35 | 3.50 | 28.06 | 3.50 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 19.19 | 2.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
February | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.37 | 0.17 | 27.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.98 | 3.00 | 27.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.82 | 1.83 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.19 | 2.83 | 28.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.06 | 2.17 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.73 | 2.33 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.90 | 0.33 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
Annual Sum or Average | 3.33 | 19.27 | 3.17 | 19.38 | 20.33 | 25.90 | 12.33 | 26.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.90 | 2.67 | 19.90 | 5.33 | 28.19 | 3.00 | 28.16 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.33 | 36.33 | 22.14 | 36.33 | 21.97 |
February | 447.67 | 23.23 | 0.00 | 23.23 | 0.00 | 23.23 |
March | 440.67 | 23.84 | 0.00 | 23.84 | 0.00 | 23.84 |
April | 176.00 | 23.92 | 47.50 | 24.18 | 0.00 | 24.18 |
May | 14.17 | 24.00 | 138.33 | 24.84 | 0.00 | 24.84 |
June | 0.00 | 0.00 | 191.17 | 24.79 | 0.00 | 24.79 |
July | 0.00 | 0.00 | 358.33 | 24.57 | 0.00 | 24.57 |
August | 0.00 | 0.00 | 427.50 | 24.42 | 0.00 | 24.42 |
September | 0.00 | 0.00 | 284.83 | 24.64 | 0.00 | 24.64 |
October | 91.33 | 23.81 | 65.50 | 24.50 | 0.00 | 24.50 |
November | 354.67 | 23.54 | 18.83 | 23.62 | 0.00 | 23.62 |
December | 497.00 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
Annual Sum or Average | 2523.50 | 23.25 | 1568.33 | 23.74 | 36.33 | 23.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.14 | 0.00 | 21.97 |
Maximum of Months | 502.00 | 24.00 | 427.50 | 24.84 | 36.33 | 24.84 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.30 | 115.67 | 21.09 | 115.67 | 20.94 |
February | 453.67 | 22.05 | 36.33 | 21.95 | 36.33 | 21.86 |
March | 511.17 | 23.14 | 0.00 | 23.14 | 0.00 | 23.14 |
April | 345.83 | 23.55 | 27.50 | 23.65 | 0.00 | 23.65 |
May | 149.67 | 23.69 | 60.00 | 23.96 | 0.00 | 23.96 |
June | 38.83 | 23.73 | 106.33 | 24.44 | 0.00 | 24.44 |
July | 2.83 | 23.68 | 262.83 | 24.45 | 0.00 | 24.45 |
August | 9.00 | 23.64 | 344.83 | 24.32 | 0.00 | 24.32 |
September | 51.83 | 23.50 | 184.83 | 24.29 | 0.00 | 24.29 |
October | 327.33 | 23.29 | 15.67 | 23.37 | 0.00 | 23.37 |
November | 464.17 | 22.48 | 0.83 | 22.48 | 0.83 | 22.47 |
December | 497.00 | 21.77 | 27.67 | 21.70 | 27.67 | 21.64 |
Annual Sum or Average | 3353.33 | 22.52 | 1182.50 | 22.86 | 180.50 | 22.77 |
Minimum of Months | 2.83 | 21.30 | 0.00 | 21.09 | 0.00 | 20.94 |
Maximum of Months | 511.17 | 23.73 | 344.83 | 24.45 | 115.67 | 24.45 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.75 | 239.00 | 20.51 | 239.00 | 20.39 |
February | 454.00 | 21.36 | 124.33 | 21.12 | 124.33 | 20.97 |
March | 513.33 | 22.47 | 18.50 | 22.40 | 18.50 | 22.34 |
April | 384.83 | 23.11 | 18.83 | 23.18 | 0.00 | 23.18 |
May | 225.00 | 23.44 | 43.83 | 23.60 | 0.00 | 23.60 |
June | 99.50 | 23.55 | 87.50 | 23.96 | 0.00 | 23.96 |
July | 42.50 | 23.58 | 243.17 | 24.24 | 0.00 | 24.24 |
August | 43.17 | 23.47 | 296.33 | 24.16 | 0.00 | 24.16 |
September | 162.00 | 23.35 | 112.50 | 23.73 | 0.00 | 23.73 |
October | 432.33 | 22.81 | 0.83 | 22.81 | 0.00 | 22.81 |
November | 489.00 | 21.75 | 60.67 | 21.59 | 60.67 | 21.47 |
December | 497.00 | 21.04 | 181.83 | 20.84 | 181.83 | 20.72 |
Annual Sum or Average | 3844.67 | 22.08 | 1427.33 | 22.20 | 624.33 | 21.99 |
Minimum of Months | 42.50 | 20.75 | 0.83 | 20.51 | 0.00 | 20.39 |
Maximum of Months | 513.33 | 23.58 | 296.33 | 24.24 | 239.00 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 387.17 | 20.02 | 387.17 | 19.97 |
February | 454.00 | 20.58 | 248.50 | 20.37 | 248.50 | 20.26 |
March | 514.00 | 21.54 | 103.50 | 21.33 | 103.50 | 21.18 |
April | 412.50 | 22.43 | 35.83 | 22.43 | 16.83 | 22.36 |
May | 272.33 | 22.93 | 59.67 | 23.18 | 0.00 | 23.18 |
June | 148.50 | 23.30 | 103.00 | 23.73 | 0.00 | 23.73 |
July | 93.00 | 23.42 | 255.50 | 24.05 | 0.00 | 24.05 |
August | 113.50 | 23.34 | 281.67 | 23.96 | 0.00 | 23.96 |
September | 260.33 | 22.89 | 90.17 | 23.23 | 0.00 | 23.23 |
October | 474.00 | 22.00 | 27.67 | 21.90 | 27.67 | 21.81 |
November | 489.00 | 20.89 | 200.83 | 20.65 | 200.83 | 20.52 |
December | 497.00 | 20.33 | 360.50 | 20.22 | 360.50 | 20.18 |
Annual Sum or Average | 4230.17 | 21.52 | 2154.00 | 21.55 | 1345.00 | 21.28 |
Minimum of Months | 93.00 | 20.14 | 27.67 | 20.02 | 0.00 | 19.97 |
Maximum of Months | 514.00 | 23.42 | 387.17 | 24.05 | 387.17 | 24.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.19 | 352.33 | 20.03 | 352.33 | 19.97 |
February | 454.00 | 20.88 | 219.33 | 20.62 | 219.33 | 20.48 |
March | 498.33 | 21.94 | 73.50 | 21.70 | 73.50 | 21.52 |
April | 300.67 | 22.54 | 76.17 | 22.80 | 11.17 | 22.72 |
May | 204.83 | 22.97 | 147.67 | 23.60 | 3.67 | 23.64 |
June | 102.17 | 23.50 | 227.67 | 24.16 | 6.17 | 24.22 |
July | 80.50 | 24.17 | 331.33 | 24.39 | 16.00 | 24.49 |
August | 82.17 | 24.02 | 359.50 | 24.27 | 14.83 | 24.36 |
September | 201.17 | 22.96 | 178.50 | 23.62 | 3.67 | 23.65 |
October | 397.00 | 22.06 | 40.67 | 22.08 | 20.50 | 21.99 |
November | 488.00 | 21.03 | 169.33 | 20.77 | 169.33 | 20.61 |
December | 497.00 | 20.41 | 323.50 | 20.26 | 323.50 | 20.19 |
Annual Sum or Average | 3807.83 | 21.57 | 2499.50 | 21.87 | 1214.00 | 21.61 |
Minimum of Months | 80.50 | 20.19 | 40.67 | 20.03 | 3.67 | 19.97 |
Maximum of Months | 502.00 | 24.17 | 359.50 | 24.39 | 352.33 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 20.57 | 298.17 | 20.30 | 298.17 | 20.17 |
February | 404.33 | 21.12 | 187.83 | 20.93 | 173.17 | 20.76 |
March | 409.00 | 21.77 | 103.00 | 21.70 | 71.50 | 21.52 |
April | 294.00 | 22.43 | 103.33 | 22.83 | 15.33 | 22.75 |
May | 232.83 | 22.99 | 151.33 | 23.57 | 8.83 | 23.65 |
June | 148.17 | 23.33 | 187.00 | 23.96 | 5.83 | 24.01 |
July | 108.33 | 23.78 | 298.50 | 24.27 | 12.83 | 24.35 |
August | 109.33 | 23.76 | 331.50 | 24.20 | 13.50 | 24.28 |
September | 196.83 | 23.08 | 210.67 | 23.76 | 7.33 | 23.82 |
October | 348.50 | 22.17 | 109.83 | 22.59 | 19.50 | 22.52 |
November | 451.33 | 21.22 | 172.83 | 21.10 | 148.67 | 20.90 |
December | 471.33 | 20.73 | 271.50 | 20.50 | 268.33 | 20.37 |
Annual Sum or Average | 3670.00 | 21.76 | 2425.50 | 22.11 | 1043.00 | 21.85 |
Minimum of Months | 108.33 | 20.57 | 103.00 | 20.30 | 5.83 | 20.17 |
Maximum of Months | 496.00 | 23.78 | 331.50 | 24.27 | 298.17 | 24.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.22 | 358.67 | 20.06 | 358.67 | 20.00 |
February | 444.17 | 20.81 | 224.50 | 20.55 | 224.00 | 20.42 |
March | 471.83 | 21.65 | 100.50 | 21.47 | 91.83 | 21.30 |
April | 338.33 | 22.36 | 78.83 | 22.62 | 17.17 | 22.55 |
May | 241.33 | 23.09 | 140.33 | 23.61 | 13.50 | 23.73 |
June | 140.83 | 23.40 | 195.00 | 23.98 | 7.50 | 24.05 |
July | 100.50 | 23.94 | 319.17 | 24.33 | 15.67 | 24.42 |
August | 104.33 | 23.69 | 328.83 | 24.17 | 11.00 | 24.24 |
September | 215.33 | 23.10 | 176.00 | 23.69 | 10.83 | 23.78 |
October | 419.83 | 22.03 | 57.17 | 22.10 | 25.33 | 22.00 |
November | 481.17 | 20.99 | 183.33 | 20.76 | 179.67 | 20.61 |
December | 497.00 | 20.46 | 326.83 | 20.29 | 326.83 | 20.22 |
Annual Sum or Average | 3956.67 | 21.59 | 2489.17 | 21.84 | 1282.00 | 21.59 |
Minimum of Months | 100.50 | 20.22 | 57.17 | 20.06 | 7.50 | 20.00 |
Maximum of Months | 502.00 | 23.94 | 358.67 | 24.33 | 358.67 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.39 | 375.33 | 20.30 | 375.33 | 20.26 |
February | 454.00 | 20.76 | 231.33 | 20.62 | 231.33 | 20.55 |
March | 514.00 | 21.48 | 63.33 | 21.38 | 63.33 | 21.29 |
April | 461.33 | 22.40 | 5.83 | 22.39 | 3.67 | 22.38 |
May | 362.67 | 23.16 | 20.17 | 23.22 | 0.00 | 23.22 |
June | 183.67 | 23.48 | 45.33 | 23.64 | 0.00 | 23.64 |
July | 75.17 | 23.60 | 194.33 | 24.07 | 0.00 | 24.07 |
August | 83.00 | 23.49 | 256.17 | 24.01 | 0.00 | 24.01 |
September | 254.83 | 23.24 | 70.83 | 23.45 | 0.00 | 23.45 |
October | 481.00 | 22.55 | 1.00 | 22.55 | 0.00 | 22.55 |
November | 489.00 | 21.42 | 83.33 | 21.28 | 83.33 | 21.17 |
December | 497.00 | 20.68 | 293.00 | 20.58 | 293.00 | 20.53 |
Annual Sum or Average | 4357.67 | 21.80 | 1640.00 | 21.78 | 1050.00 | 21.56 |
Minimum of Months | 75.17 | 20.39 | 1.00 | 20.30 | 0.00 | 20.26 |
Maximum of Months | 514.00 | 23.60 | 375.33 | 24.07 | 375.33 | 24.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.44 | 349.83 | 20.33 | 349.83 | 20.28 |
February | 454.00 | 21.06 | 181.50 | 20.88 | 181.50 | 20.78 |
March | 514.00 | 22.08 | 32.33 | 21.98 | 32.33 | 21.89 |
April | 336.00 | 22.85 | 37.67 | 22.99 | 1.33 | 22.98 |
May | 219.83 | 23.20 | 102.50 | 23.64 | 0.50 | 23.64 |
June | 77.33 | 23.51 | 214.67 | 24.25 | 0.83 | 24.26 |
July | 36.67 | 24.43 | 339.50 | 24.46 | 8.83 | 24.51 |
August | 43.83 | 24.32 | 376.00 | 24.35 | 9.83 | 24.41 |
September | 152.00 | 23.33 | 196.33 | 23.94 | 2.83 | 23.96 |
October | 379.50 | 22.72 | 22.83 | 22.83 | 0.00 | 22.83 |
November | 486.83 | 21.61 | 66.67 | 21.46 | 66.67 | 21.34 |
December | 497.00 | 20.80 | 240.83 | 20.65 | 240.83 | 20.57 |
Annual Sum or Average | 3699.00 | 21.83 | 2160.67 | 22.18 | 895.33 | 21.95 |
Minimum of Months | 36.67 | 20.44 | 22.83 | 20.33 | 0.00 | 20.28 |
Maximum of Months | 514.00 | 24.43 | 376.00 | 24.46 | 349.83 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.83 | 20.25 | 343.17 | 20.06 | 343.17 | 19.97 |
February | 435.83 | 21.00 | 146.00 | 20.73 | 143.67 | 20.55 |
March | 463.67 | 21.53 | 53.00 | 21.37 | 48.67 | 21.21 |
April | 366.00 | 22.14 | 70.67 | 22.35 | 17.00 | 22.24 |
May | 315.33 | 22.55 | 81.50 | 22.98 | 1.83 | 22.96 |
June | 215.83 | 22.81 | 114.50 | 23.45 | 0.00 | 23.45 |
July | 96.17 | 23.03 | 290.33 | 24.11 | 4.50 | 24.15 |
August | 90.67 | 23.15 | 333.00 | 24.11 | 8.83 | 24.17 |
September | 160.17 | 22.73 | 227.00 | 23.78 | 6.50 | 23.83 |
October | 334.50 | 22.26 | 92.33 | 22.81 | 4.00 | 22.80 |
November | 456.83 | 21.17 | 104.00 | 21.09 | 84.17 | 20.91 |
December | 481.50 | 20.63 | 262.67 | 20.41 | 259.67 | 20.29 |
Annual Sum or Average | 3916.33 | 21.55 | 2118.17 | 21.90 | 922.00 | 21.64 |
Minimum of Months | 90.67 | 20.25 | 53.00 | 20.06 | 0.00 | 19.97 |
Maximum of Months | 499.83 | 23.15 | 343.17 | 24.11 | 343.17 | 24.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.46 | 347.67 | 20.34 | 347.67 | 20.29 |
February | 452.83 | 21.04 | 179.83 | 20.84 | 179.83 | 20.73 |
March | 495.83 | 21.89 | 41.17 | 21.79 | 40.50 | 21.70 |
April | 368.50 | 22.67 | 44.83 | 22.86 | 1.83 | 22.85 |
May | 223.33 | 23.34 | 113.00 | 23.76 | 3.00 | 23.79 |
June | 99.67 | 23.51 | 170.83 | 24.10 | 0.67 | 24.11 |
July | 33.17 | 24.61 | 361.50 | 24.51 | 9.00 | 24.57 |
August | 36.17 | 24.16 | 379.83 | 24.33 | 7.50 | 24.38 |
September | 121.67 | 23.46 | 216.50 | 24.10 | 4.33 | 24.14 |
October | 396.50 | 22.70 | 27.83 | 22.85 | 0.00 | 22.85 |
November | 481.33 | 21.56 | 70.00 | 21.44 | 66.33 | 21.33 |
December | 497.00 | 20.81 | 249.83 | 20.65 | 249.83 | 20.58 |
Annual Sum or Average | 3708.00 | 21.80 | 2202.83 | 22.17 | 910.50 | 21.94 |
Minimum of Months | 33.17 | 20.46 | 27.83 | 20.34 | 0.00 | 20.29 |
Maximum of Months | 502.00 | 24.61 | 379.83 | 24.51 | 347.67 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.42 | 326.33 | 20.27 | 326.33 | 20.21 |
February | 454.00 | 20.95 | 181.33 | 20.73 | 181.33 | 20.62 |
March | 514.00 | 22.04 | 31.67 | 21.95 | 31.67 | 21.87 |
April | 399.33 | 22.87 | 18.50 | 22.94 | 0.00 | 22.94 |
May | 235.67 | 23.30 | 61.33 | 23.50 | 0.00 | 23.50 |
June | 93.83 | 23.53 | 105.00 | 23.95 | 0.00 | 23.95 |
July | 37.67 | 23.66 | 270.67 | 24.21 | 0.00 | 24.21 |
August | 47.33 | 23.47 | 314.00 | 24.13 | 0.00 | 24.13 |
September | 198.00 | 23.25 | 113.50 | 23.62 | 0.00 | 23.62 |
October | 450.67 | 22.55 | 8.33 | 22.58 | 0.67 | 22.58 |
November | 489.00 | 21.39 | 104.17 | 21.20 | 104.17 | 21.07 |
December | 497.00 | 20.68 | 263.00 | 20.54 | 263.00 | 20.47 |
Annual Sum or Average | 3918.50 | 21.80 | 1797.83 | 21.93 | 907.17 | 21.69 |
Minimum of Months | 37.67 | 20.42 | 8.33 | 20.27 | 0.00 | 20.21 |
Maximum of Months | 514.00 | 23.66 | 326.33 | 24.21 | 326.33 | 24.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.37 | 274.17 | 20.20 | 274.17 | 20.12 |
February | 384.83 | 21.18 | 134.33 | 20.94 | 134.33 | 20.80 |
March | 415.67 | 22.27 | 26.33 | 22.16 | 26.33 | 22.06 |
April | 253.83 | 22.92 | 55.50 | 23.22 | 0.17 | 23.22 |
May | 166.83 | 23.35 | 116.83 | 23.88 | 4.17 | 23.93 |
June | 72.17 | 23.82 | 193.50 | 24.38 | 6.67 | 24.44 |
July | 32.33 | 24.91 | 283.67 | 24.61 | 11.83 | 24.70 |
August | 40.17 | 24.65 | 309.67 | 24.46 | 13.33 | 24.55 |
September | 144.83 | 23.38 | 161.00 | 23.97 | 4.67 | 24.01 |
October | 326.67 | 22.55 | 26.33 | 22.71 | 0.00 | 22.71 |
November | 411.33 | 21.45 | 89.50 | 21.23 | 89.50 | 21.09 |
December | 422.00 | 20.72 | 215.17 | 20.53 | 215.17 | 20.43 |
Annual Sum or Average | 3097.67 | 21.84 | 1886.00 | 22.20 | 780.33 | 21.97 |
Minimum of Months | 32.33 | 20.37 | 26.33 | 20.20 | 0.00 | 20.12 |
Maximum of Months | 427.00 | 24.91 | 309.67 | 24.61 | 274.17 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 489.67 | 20.88 | 237.17 | 20.63 | 233.83 | 20.48 |
February | 391.67 | 21.48 | 123.50 | 21.38 | 103.67 | 21.21 |
March | 392.33 | 22.26 | 53.17 | 22.37 | 16.83 | 22.30 |
April | 265.50 | 22.86 | 97.33 | 23.33 | 0.67 | 23.34 |
May | 199.67 | 23.40 | 154.00 | 23.87 | 7.33 | 23.93 |
June | 108.83 | 23.60 | 202.50 | 24.15 | 4.17 | 24.19 |
July | 59.83 | 24.25 | 322.67 | 24.43 | 11.33 | 24.50 |
August | 50.83 | 24.33 | 356.83 | 24.35 | 12.83 | 24.43 |
September | 132.50 | 23.48 | 240.83 | 24.09 | 7.83 | 24.15 |
October | 318.17 | 22.75 | 104.67 | 23.23 | 3.33 | 23.26 |
November | 439.67 | 21.72 | 99.83 | 21.72 | 70.83 | 21.56 |
December | 459.83 | 21.10 | 194.50 | 20.91 | 188.33 | 20.76 |
Annual Sum or Average | 3308.50 | 22.06 | 2187.00 | 22.54 | 661.00 | 22.34 |
Minimum of Months | 50.83 | 20.88 | 53.17 | 20.63 | 0.67 | 20.48 |
Maximum of Months | 489.67 | 24.33 | 356.83 | 24.43 | 233.83 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.52 | 294.50 | 20.33 | 294.50 | 20.24 |
February | 440.67 | 21.16 | 150.17 | 20.93 | 149.67 | 20.79 |
March | 466.67 | 22.16 | 38.67 | 22.11 | 28.67 | 22.02 |
April | 316.50 | 22.83 | 67.83 | 23.15 | 1.17 | 23.15 |
May | 200.83 | 23.49 | 143.17 | 23.92 | 12.17 | 24.03 |
June | 93.00 | 23.69 | 202.67 | 24.18 | 5.67 | 24.24 |
July | 51.50 | 24.60 | 343.50 | 24.49 | 14.50 | 24.57 |
August | 47.50 | 24.20 | 363.17 | 24.33 | 10.33 | 24.39 |
September | 152.00 | 23.52 | 208.00 | 24.04 | 10.50 | 24.13 |
October | 393.33 | 22.60 | 38.50 | 22.78 | 0.17 | 22.79 |
November | 473.50 | 21.45 | 101.50 | 21.29 | 96.00 | 21.15 |
December | 497.00 | 20.83 | 235.67 | 20.63 | 235.67 | 20.53 |
Annual Sum or Average | 3634.50 | 21.87 | 2187.33 | 22.25 | 859.00 | 22.03 |
Minimum of Months | 47.50 | 20.52 | 38.50 | 20.33 | 0.17 | 20.24 |
Maximum of Months | 502.00 | 24.60 | 363.17 | 24.49 | 294.50 | 24.57 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.33439 | 32.52702 | -0.2026 | 7.38823 |
February | 454.00000 | 23.24534 | 32.57424 | 0.03570 | 5.48147 |
March | 514.00000 | 23.91671 | 31.05395 | 0.21711 | 6.11700 |
April | 485.00000 | 24.22862 | 33.45181 | 0.33297 | 7.52979 |
May | 508.00000 | 24.30985 | 36.87888 | -0.4762 | 10.05274 |
June | 496.00000 | 24.32374 | 38.69809 | -0.4372 | 9.32831 |
July | 497.00000 | 24.41864 | 42.82304 | -0.3693 | 8.29791 |
August | 514.00000 | 24.34866 | 46.00581 | -0.3625 | 8.12177 |
September | 485.00000 | 24.38281 | 43.68059 | -0.3922 | 8.66651 |
October | 502.00000 | 24.24299 | 36.74799 | 0.36110 | 7.93957 |
November | 489.00000 | 23.73061 | 37.10136 | 0.19936 | 6.30682 |
December | 497.00000 | 23.08861 | 32.65882 | -0.0053 | 5.39220 |
Annual Sum or Average | 5943.00000 | 23.88516 | 37.04669 | -0.0934 | 7.56835 |
Minimum of Months | 454.00000 | 22.33439 | 31.05395 | -0.4762 | 5.39220 |
Maximum of Months | 514.00000 | 24.41864 | 46.00581 | 0.36110 | 10.05274 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.29811 | 34.29436 | -0.4325 | 10.26107 |
February | 454.00000 | 22.05128 | 34.69631 | -0.2290 | 7.04804 |
March | 514.00000 | 23.14491 | 33.26421 | 0.04239 | 5.51723 |
April | 485.00000 | 23.74459 | 35.10027 | 0.22093 | 6.42859 |
May | 508.00000 | 24.03439 | 38.08343 | -0.5758 | 12.28350 |
June | 496.00000 | 24.14470 | 39.62931 | -0.5066 | 10.59896 |
July | 497.00000 | 24.25523 | 43.52013 | -0.4344 | 9.23798 |
August | 514.00000 | 24.21603 | 46.74225 | -0.4205 | 8.95875 |
September | 485.00000 | 24.13293 | 44.89813 | -0.4897 | 10.36745 |
October | 502.00000 | 23.62226 | 39.08456 | 0.21281 | 6.41967 |
November | 489.00000 | 22.56151 | 39.93900 | -0.0668 | 6.14533 |
December | 497.00000 | 21.76808 | 35.07138 | -0.3021 | 7.49408 |
Annual Sum or Average | 5943.00000 | 23.25708 | 38.71842 | -0.2493 | 8.40960 |
Minimum of Months | 454.00000 | 21.29811 | 33.26421 | -0.5758 | 5.51723 |
Maximum of Months | 514.00000 | 24.25523 | 46.74225 | 0.22093 | 12.28350 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.74862 | 35.07919 | -0.5825 | 13.94339 |
February | 454.00000 | 21.36019 | 35.66679 | -0.4068 | 10.12758 |
March | 514.00000 | 22.46703 | 34.41857 | -0.1230 | 6.25696 |
April | 485.00000 | 23.32512 | 35.88039 | 0.11811 | 6.12019 |
May | 508.00000 | 23.81842 | 38.57916 | -0.6527 | 14.68259 |
June | 496.00000 | 24.03460 | 39.77745 | -0.5454 | 11.56711 |
July | 497.00000 | 24.16433 | 43.53717 | -0.4636 | 9.82951 |
August | 514.00000 | 24.11298 | 46.75406 | -0.4578 | 9.71830 |
September | 485.00000 | 23.86617 | 45.65895 | -0.5889 | 12.89878 |
October | 502.00000 | 22.98748 | 40.70062 | 0.05516 | 5.99195 |
November | 489.00000 | 21.74939 | 41.70207 | -0.2713 | 7.93058 |
December | 497.00000 | 21.04197 | 36.34551 | -0.4940 | 11.00804 |
Annual Sum or Average | 5943.00000 | 22.81791 | 39.52975 | -0.3680 | 10.00695 |
Minimum of Months | 454.00000 | 20.74862 | 34.41857 | -0.6527 | 5.99195 |
Maximum of Months | 514.00000 | 24.16433 | 46.75406 | 0.11811 | 14.68259 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13567 | 36.79244 | -0.7622 | 19.58288 |
February | 454.00000 | 20.58467 | 37.42109 | -0.6114 | 15.20521 |
March | 514.00000 | 21.53989 | 37.11749 | -0.3384 | 8.84405 |
April | 485.00000 | 22.67669 | 37.80273 | -0.0280 | 6.80388 |
May | 508.00000 | 23.47247 | 39.95874 | -0.7550 | 19.00728 |
June | 496.00000 | 23.88056 | 40.64036 | -0.5814 | 13.02482 |
July | 497.00000 | 24.06100 | 44.02595 | -0.4775 | 10.56671 |
August | 514.00000 | 23.97227 | 47.68285 | -0.4897 | 10.88055 |
September | 485.00000 | 23.44678 | 47.76379 | -0.7268 | 17.80800 |
October | 502.00000 | 22.11870 | 43.81815 | -0.1448 | 6.96113 |
November | 489.00000 | 20.88986 | 44.14016 | -0.4881 | 11.72434 |
December | 497.00000 | 20.33409 | 38.31585 | -0.6952 | 16.54452 |
Annual Sum or Average | 5943.00000 | 22.27302 | 41.31043 | -0.5078 | 13.06191 |
Minimum of Months | 454.00000 | 20.13567 | 36.79244 | -0.7622 | 6.80388 |
Maximum of Months | 514.00000 | 24.06100 | 47.76379 | -0.0280 | 19.58288 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.18847 | 37.67407 | -0.7387 | 18.80312 |
February | 454.00000 | 20.87975 | 37.87992 | -0.5300 | 13.28703 |
March | 514.00000 | 22.00044 | 37.05039 | -0.2166 | 8.15130 |
April | 485.00000 | 23.15761 | 36.56852 | 0.11430 | 7.27283 |
May | 508.00000 | 23.71335 | 39.27385 | -0.6272 | 16.13749 |
June | 496.00000 | 24.08968 | 39.78267 | -0.4417 | 10.95084 |
July | 497.00000 | 24.24755 | 43.44290 | -0.3482 | 9.29002 |
August | 514.00000 | 24.15090 | 46.93438 | -0.3531 | 9.27122 |
September | 485.00000 | 23.68385 | 46.98416 | -0.5959 | 15.13663 |
October | 502.00000 | 22.48856 | 43.24437 | -0.0427 | 7.09421 |
November | 489.00000 | 21.03716 | 44.80025 | -0.4446 | 11.16543 |
December | 497.00000 | 20.41261 | 39.17185 | -0.6647 | 15.78008 |
Annual Sum or Average | 5943.00000 | 22.51747 | 41.08362 | -0.4068 | 11.84684 |
Minimum of Months | 454.00000 | 20.18847 | 36.56852 | -0.7387 | 7.09421 |
Maximum of Months | 514.00000 | 24.24755 | 46.98416 | 0.11430 | 18.80312 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.61454 | 35.92422 | -0.6257 | 16.52046 |
February | 454.00000 | 21.46410 | 35.37707 | -0.3771 | 11.88336 |
March | 514.00000 | 22.25249 | 34.77470 | -0.1399 | 8.45533 |
April | 485.00000 | 23.15112 | 35.65786 | 0.12030 | 7.93627 |
May | 508.00000 | 23.63931 | 38.85095 | -0.6512 | 17.35649 |
June | 496.00000 | 23.95168 | 39.97861 | -0.5175 | 12.67104 |
July | 497.00000 | 24.16224 | 43.38706 | -0.3873 | 10.17505 |
August | 514.00000 | 24.08919 | 46.74410 | -0.3757 | 9.97650 |
September | 485.00000 | 23.76022 | 45.84042 | -0.5324 | 14.36984 |
October | 502.00000 | 22.83691 | 40.96855 | 0.06211 | 8.03825 |
November | 489.00000 | 21.48002 | 42.61371 | -0.3328 | 10.53374 |
December | 497.00000 | 20.91636 | 36.99489 | -0.5331 | 14.11135 |
Annual Sum or Average | 5943.00000 | 22.70327 | 39.78501 | -0.3579 | 11.83564 |
Minimum of Months | 454.00000 | 20.61454 | 34.77470 | -0.6512 | 7.93627 |
Maximum of Months | 514.00000 | 24.16224 | 46.74410 | 0.12030 | 17.35649 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.22470 | 37.60972 | -0.7314 | 18.76673 |
February | 454.00000 | 20.87800 | 37.69835 | -0.5320 | 13.93383 |
March | 514.00000 | 21.85387 | 36.97737 | -0.2515 | 8.70139 |
April | 485.00000 | 22.93557 | 37.28898 | 0.05977 | 7.63971 |
May | 508.00000 | 23.63899 | 39.65594 | -0.6457 | 17.47993 |
June | 496.00000 | 23.95427 | 40.55366 | -0.5025 | 12.31215 |
July | 497.00000 | 24.19719 | 43.57624 | -0.3496 | 9.82773 |
August | 514.00000 | 24.08394 | 47.31850 | -0.3820 | 10.06152 |
September | 485.00000 | 23.69328 | 47.04355 | -0.5887 | 15.42024 |
October | 502.00000 | 22.39078 | 43.49844 | -0.0660 | 7.25138 |
November | 489.00000 | 21.04134 | 44.77936 | -0.4454 | 11.29721 |
December | 497.00000 | 20.46153 | 39.08278 | -0.6556 | 15.79908 |
Annual Sum or Average | 5943.00000 | 22.45888 | 41.27531 | -0.4238 | 12.36122 |
Minimum of Months | 454.00000 | 20.22470 | 36.97737 | -0.7314 | 7.25138 |
Maximum of Months | 514.00000 | 24.19719 | 47.31850 | 0.05977 | 18.76673 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.39100 | 36.69092 | -0.6933 | 16.44469 |
February | 454.00000 | 20.76004 | 37.57095 | -0.5616 | 12.66510 |
March | 514.00000 | 21.48285 | 37.29646 | -0.3511 | 8.18527 |
April | 485.00000 | 22.48249 | 38.84647 | -0.0823 | 6.15651 |
May | 508.00000 | 23.41107 | 40.91112 | -0.8030 | 19.67695 |
June | 496.00000 | 23.86014 | 41.45431 | -0.6183 | 13.48403 |
July | 497.00000 | 24.06525 | 44.69915 | -0.5044 | 10.65253 |
August | 514.00000 | 24.00428 | 48.27814 | -0.5001 | 10.62967 |
September | 485.00000 | 23.62719 | 47.69191 | -0.6754 | 15.38066 |
October | 502.00000 | 22.61885 | 42.66743 | -0.0232 | 5.79253 |
November | 489.00000 | 21.42156 | 43.22026 | -0.3357 | 8.44872 |
December | 497.00000 | 20.68116 | 37.93253 | -0.5852 | 12.62450 |
Annual Sum or Average | 5943.00000 | 22.41312 | 41.46027 | -0.4779 | 11.67988 |
Minimum of Months | 454.00000 | 20.39100 | 36.69092 | -0.8030 | 5.79253 |
Maximum of Months | 514.00000 | 24.06525 | 48.27814 | -0.0232 | 19.67695 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.44047 | 37.64869 | -0.6710 | 15.77117 |
February | 454.00000 | 21.05916 | 38.12803 | -0.4766 | 10.88230 |
March | 514.00000 | 22.07576 | 37.25986 | -0.1988 | 6.94521 |
April | 485.00000 | 23.25228 | 37.17206 | 0.12403 | 6.58442 |
May | 508.00000 | 23.78214 | 39.72073 | -0.6327 | 15.12252 |
June | 496.00000 | 24.16680 | 39.97903 | -0.4432 | 10.25334 |
July | 497.00000 | 24.30860 | 43.75832 | -0.3533 | 8.70446 |
August | 514.00000 | 24.23490 | 47.08046 | -0.3384 | 8.45607 |
September | 485.00000 | 23.93884 | 46.52631 | -0.5172 | 12.08831 |
October | 502.00000 | 23.07097 | 41.85740 | 0.09882 | 6.30536 |
November | 489.00000 | 21.61590 | 43.87402 | -0.2824 | 8.01609 |
December | 497.00000 | 20.79866 | 38.81388 | -0.5476 | 11.88338 |
Annual Sum or Average | 5943.00000 | 22.74130 | 41.00073 | -0.3529 | 10.08168 |
Minimum of Months | 454.00000 | 20.44047 | 37.17206 | -0.6710 | 6.30536 |
Maximum of Months | 514.00000 | 24.30860 | 47.08046 | 0.12403 | 15.77117 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.27391 | 34.40115 | -0.6733 | 16.56641 |
February | 454.00000 | 21.13758 | 34.38454 | -0.4146 | 11.01118 |
March | 514.00000 | 21.80270 | 34.01749 | -0.2173 | 7.94549 |
April | 485.00000 | 22.69769 | 35.94437 | 0.02478 | 7.24245 |
May | 508.00000 | 23.22340 | 39.55774 | -0.7866 | 20.93029 |
June | 496.00000 | 23.63604 | 40.74700 | -0.6296 | 15.41066 |
July | 497.00000 | 24.06809 | 43.97602 | -0.4341 | 10.71609 |
August | 514.00000 | 24.02387 | 47.30613 | -0.3975 | 10.04357 |
September | 485.00000 | 23.77373 | 45.52857 | -0.5100 | 13.47185 |
October | 502.00000 | 23.00394 | 39.26654 | 0.13049 | 7.62832 |
November | 489.00000 | 21.41081 | 40.49379 | -0.2971 | 9.25817 |
December | 497.00000 | 20.75388 | 35.22648 | -0.5234 | 12.85849 |
Annual Sum or Average | 5943.00000 | 22.49416 | 39.26930 | -0.3946 | 11.93972 |
Minimum of Months | 454.00000 | 20.27391 | 34.01749 | -0.7866 | 7.24245 |
Maximum of Months | 514.00000 | 24.06809 | 47.30613 | 0.13049 | 20.93029 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.46307 | 37.61183 | -0.6658 | 15.69775 |
February | 454.00000 | 21.05071 | 38.05211 | -0.4788 | 11.28837 |
March | 514.00000 | 21.96987 | 37.21384 | -0.2247 | 7.30435 |
April | 485.00000 | 23.05403 | 37.75725 | 0.07310 | 6.66676 |
May | 508.00000 | 23.83567 | 39.64731 | -0.6118 | 14.70501 |
June | 496.00000 | 24.07341 | 40.64368 | -0.4914 | 11.03464 |
July | 497.00000 | 24.36517 | 43.42913 | -0.3180 | 8.27816 |
August | 514.00000 | 24.23480 | 47.21230 | -0.3462 | 8.54047 |
September | 485.00000 | 24.04958 | 46.15921 | -0.4787 | 11.27840 |
October | 502.00000 | 23.03580 | 41.99910 | 0.08933 | 6.34487 |
November | 489.00000 | 21.60380 | 43.88169 | -0.2859 | 8.13782 |
December | 497.00000 | 20.81137 | 38.78682 | -0.5446 | 11.94148 |
Annual Sum or Average | 5943.00000 | 22.72486 | 41.04904 | -0.3567 | 10.09757 |
Minimum of Months | 454.00000 | 20.46307 | 37.21384 | -0.6658 | 6.34487 |
Maximum of Months | 514.00000 | 24.36517 | 47.21230 | 0.08933 | 15.69775 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.41802 | 36.43271 | -0.6665 | 15.94438 |
February | 454.00000 | 20.94526 | 36.89114 | -0.4975 | 11.75305 |
March | 514.00000 | 22.04449 | 36.23504 | -0.2055 | 6.86637 |
April | 485.00000 | 23.08552 | 37.07686 | 0.07302 | 6.22681 |
May | 508.00000 | 23.72658 | 39.33861 | -0.6680 | 15.38499 |
June | 496.00000 | 24.01109 | 40.35051 | -0.5365 | 11.43821 |
July | 497.00000 | 24.16423 | 43.88994 | -0.4439 | 9.49048 |
August | 514.00000 | 24.09246 | 47.50218 | -0.4481 | 9.63436 |
September | 485.00000 | 23.75931 | 46.84627 | -0.6169 | 13.85891 |
October | 502.00000 | 22.71574 | 42.32480 | 0.00451 | 6.03424 |
November | 489.00000 | 21.38784 | 43.09254 | -0.3434 | 8.86576 |
December | 497.00000 | 20.67967 | 37.71858 | -0.5778 | 12.69083 |
Annual Sum or Average | 5943.00000 | 22.59887 | 40.66264 | -0.4104 | 10.67483 |
Minimum of Months | 454.00000 | 20.41802 | 36.23504 | -0.6680 | 6.03424 |
Maximum of Months | 514.00000 | 24.16423 | 47.50218 | 0.07302 | 15.94438 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.37268 | 37.20267 | -0.6692 | 16.18271 |
February | 385.00000 | 21.18511 | 37.09070 | -0.4347 | 10.77914 |
March | 433.00000 | 22.34332 | 35.95093 | -0.1246 | 6.79020 |
April | 410.00000 | 23.43074 | 35.66212 | 0.17650 | 7.04588 |
May | 430.00000 | 23.91218 | 38.40447 | -0.5725 | 13.92490 |
June | 418.00000 | 24.21999 | 39.37237 | -0.4130 | 10.11089 |
July | 422.00000 | 24.39759 | 42.92522 | -0.3191 | 8.67722 |
August | 433.00000 | 24.28259 | 46.42035 | -0.3262 | 8.68470 |
September | 410.00000 | 23.94317 | 45.89345 | -0.5162 | 12.46700 |
October | 427.00000 | 22.94194 | 41.73710 | 0.06999 | 6.53356 |
November | 417.00000 | 21.48214 | 43.59635 | -0.3159 | 8.82234 |
December | 422.00000 | 20.71552 | 38.47311 | -0.5624 | 12.56907 |
Annual Sum or Average | 5034.00000 | 22.77829 | 40.24495 | -0.3338 | 10.21248 |
Minimum of Months | 385.00000 | 20.37268 | 35.66212 | -0.6692 | 6.53356 |
Maximum of Months | 433.00000 | 24.39759 | 46.42035 | 0.17650 | 16.18271 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.97128 | 35.44618 | -0.5158 | 13.36281 |
February | 454.00000 | 21.87887 | 34.71499 | -0.2544 | 9.51617 |
March | 514.00000 | 22.71680 | 33.86808 | -0.0164 | 7.09348 |
April | 485.00000 | 23.50671 | 34.96708 | 0.21013 | 7.63877 |
May | 508.00000 | 23.88437 | 38.25173 | -0.5674 | 13.87193 |
June | 496.00000 | 24.09353 | 39.67200 | -0.4703 | 10.90845 |
July | 497.00000 | 24.28058 | 43.19259 | -0.3507 | 8.93270 |
August | 514.00000 | 24.20741 | 46.55371 | -0.3355 | 8.73895 |
September | 485.00000 | 24.02526 | 45.06932 | -0.4367 | 11.16245 |
October | 502.00000 | 23.33590 | 39.66220 | 0.19147 | 7.80254 |
November | 489.00000 | 22.01119 | 41.46728 | -0.1829 | 8.45186 |
December | 497.00000 | 21.34563 | 36.22261 | -0.4012 | 10.86129 |
Annual Sum or Average | 5943.00000 | 23.03056 | 39.11754 | -0.2614 | 9.86537 |
Minimum of Months | 454.00000 | 20.97128 | 33.86808 | -0.5674 | 7.09348 |
Maximum of Months | 514.00000 | 24.28058 | 46.55371 | 0.21013 | 13.87193 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.51590 | 37.27430 | -0.6340 | 15.24666 |
February | 454.00000 | 21.24803 | 37.13042 | -0.4172 | 10.82989 |
March | 514.00000 | 22.34623 | 36.03290 | -0.1219 | 6.94217 |
April | 485.00000 | 23.33540 | 36.52449 | 0.15838 | 7.18909 |
May | 508.00000 | 23.89406 | 38.98099 | -0.5591 | 13.89252 |
June | 496.00000 | 24.09455 | 40.20425 | -0.4555 | 10.58546 |
July | 497.00000 | 24.31082 | 43.37055 | -0.3139 | 8.63540 |
August | 514.00000 | 24.20493 | 47.10019 | -0.3406 | 8.80610 |
September | 485.00000 | 23.98038 | 46.13547 | -0.4866 | 11.91350 |
October | 502.00000 | 22.96012 | 42.02663 | 0.07742 | 6.58657 |
November | 489.00000 | 21.54253 | 43.68935 | -0.3008 | 8.67043 |
December | 497.00000 | 20.82519 | 38.46478 | -0.5355 | 12.12132 |
Annual Sum or Average | 5943.00000 | 22.78361 | 40.59678 | -0.3273 | 10.11276 |
Minimum of Months | 454.00000 | 20.51590 | 36.03290 | -0.6340 | 6.58657 |
Maximum of Months | 514.00000 | 24.31082 | 47.10019 | 0.15838 | 15.24666 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.524313E+11 | 0.00 | 413.43 | 147074.80 | 25-JAN-07:01 | 0.00 | 36.46 | 49.85 | 0.22 | 0.00 | 0.09 | 0.68 | 25-JAN-07:01 |
February | 0.277959E+11 | 0.00 | 325.18 | 159858.31 | 08-FEB-07:01 | 0.00 | 33.41 | 46.04 | 0.12 | 0.00 | 0.05 | 0.74 | 08-FEB-07:01 |
March | 0.115581E+11 | 0.00 | 304.48 | 151509.81 | 01-MAR-07:01 | 0.00 | 30.41 | 42.08 | 0.04 | 0.00 | 0.02 | 0.70 | 01-MAR-07:01 |
April | 0.455509E+10 | 0.00 | 173.99 | 126515.74 | 18-APR-06:02 | 0.00 | 29.55 | 36.57 | 0.02 | 0.00 | 0.01 | 0.58 | 18-APR-06:02 |
May | 0.141368E+10 | 0.00 | 78.61 | 55445.16 | 18-MAY-06:03 | 0.00 | 33.88 | 36.63 | 0.00 | 0.00 | 0.00 | 0.26 | 18-MAY-06:03 |
June | 0.317498E+09 | 0.00 | 26.26 | 10905.74 | 15-JUN-06:03 | 0.00 | 40.79 | 41.51 | 0.00 | 0.00 | 0.00 | 0.05 | 15-JUN-06:03 |
July | 56752451.84 | 0.00 | 57.15 | 9337.51 | 27-JUL-06:08 | 0.00 | 35.02 | 37.02 | 0.00 | 0.00 | 0.00 | 0.04 | 27-JUL-06:08 |
August | 78227800.38 | 0.00 | 108.92 | 9410.04 | 01-AUG-06:07 | 0.00 | 40.83 | 43.72 | 0.00 | 0.00 | 0.00 | 0.04 | 01-AUG-06:07 |
September | 0.379285E+09 | 0.00 | 63.70 | 19660.44 | 28-SEP-06:03 | 0.00 | 40.20 | 42.03 | 0.00 | 0.00 | 0.00 | 0.09 | 28-SEP-06:03 |
October | 0.309261E+10 | 0.00 | 152.26 | 100459.56 | 23-OCT-06:03 | 0.00 | 31.24 | 36.90 | 0.01 | 0.00 | 0.01 | 0.46 | 23-OCT-06:03 |
November | 0.197051E+11 | 0.00 | 307.86 | 141558.65 | 28-NOV-07:01 | 0.00 | 33.00 | 44.79 | 0.07 | 0.00 | 0.04 | 0.65 | 28-NOV-07:01 |
December | 0.394832E+11 | 0.00 | 379.61 | 150898.82 | 06-DEC-07:01 | 0.00 | 33.75 | 47.14 | 0.15 | 0.00 | 0.07 | 0.70 | 06-DEC-07:01 |
Annual Sum or Average | 0.160867E+12 | 0.00 | 2391.46 | 0.00 | 34.88 | 42.00 | 0.05 | 0.00 | 0.02 | ||||
Minimum of Months | 56752451.84 | 0.00 | 26.26 | 9337.51 | 0.00 | 29.55 | 36.57 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.524313E+11 | 0.00 | 413.43 | 159858.31 | 0.00 | 40.83 | 49.85 | 0.22 | 0.00 | 0.09 | 0.74 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 954266.94 | 245535.22 | 0.40 | 856294.18 | 97972.77 | 0.00 | 0.05 | 11-JAN-07:05 | 0.00 | 01-JAN-00:05 | 981.82 | 11-JAN-07:05 | 838.75 | 11-JAN-07:05 | 143.06 | 11-JAN-07:05 | 251.84 | 11-JAN-07:05 | 0.00 |
February | 0.157599E+09 | 37919477.69 | 8.00 | 0.137190E+09 | 20408956.03 | 0.00 | 0.44 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 9842.03 | 27-FEB-15:10 | 9670.69 | 27-FEB-15:10 | 1227.01 | 27-FEB-17:10 | 2292.97 | 27-FEB-15:10 | 0.00 |
March | 0.243913E+09 | 59937956.05 | 22.25 | 0.211939E+09 | 31973634.73 | 0.00 | 0.41 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 8910.62 | 18-MAR-16:00 | 8910.62 | 18-MAR-16:00 | 1241.40 | 09-MAR-12:00 | 2096.18 | 18-MAR-16:00 | 0.00 |
April | 0.314224E+10 | 0.693971E+09 | 75.62 | 0.301923E+10 | 0.123012E+09 | 0.00 | 1.00 | 26-APR-13:20 | 0.00 | 01-APR-00:10 | 45017.53 | 27-APR-15:00 | 45017.53 | 27-APR-15:00 | 3545.73 | 28-APR-13:00 | 9779.81 | 27-APR-15:00 | 0.00 |
May | 0.648495E+10 | 0.141753E+10 | 162.02 | 0.578371E+10 | 0.701249E+09 | 0.00 | 1.00 | 04-MAY-12:50 | 0.00 | 01-MAY-00:10 | 40796.21 | 15-MAY-16:00 | 40796.21 | 15-MAY-16:00 | 5022.83 | 05-MAY-18:00 | 8174.43 | 15-MAY-16:00 | 0.00 |
June | 0.123393E+11 | 0.268662E+10 | 264.72 | 0.114920E+11 | 0.847310E+09 | 0.00 | 1.00 | 09-JUN-13:50 | 0.00 | 01-JUN-00:10 | 46259.49 | 28-JUN-15:30 | 46259.49 | 28-JUN-15:30 | 8664.32 | 12-JUN-06:02 | 9768.55 | 28-JUN-15:30 | 0.00 |
July | 0.239548E+11 | 0.513055E+10 | 349.20 | 0.212548E+11 | 0.269999E+10 | 0.00 | 1.00 | 06-JUL-14:30 | 0.00 | 01-JUL-00:10 | 63284.65 | 31-JUL-15:50 | 59474.26 | 24-JUL-15:00 | 14712.26 | 31-JUL-06:03 | 14850.48 | 24-JUL-15:00 | 0.00 |
August | 0.326565E+11 | 0.703511E+10 | 374.75 | 0.286644E+11 | 0.399214E+10 | 0.00 | 1.00 | 06-AUG-15:51 | 0.00 | 01-AUG-00:10 | 63345.77 | 10-AUG-15:30 | 59951.87 | 10-AUG-15:50 | 14790.46 | 30-AUG-06:03 | 15116.71 | 10-AUG-15:50 | 0.00 |
September | 0.120271E+11 | 0.256931E+10 | 230.93 | 0.100950E+11 | 0.193205E+10 | 0.00 | 1.00 | 08-SEP-13:50 | 0.00 | 01-SEP-00:10 | 50647.93 | 12-SEP-16:00 | 48377.46 | 12-SEP-15:20 | 13103.47 | 14-SEP-13:00 | 10289.61 | 12-SEP-16:00 | 0.00 |
October | 0.171941E+10 | 0.391604E+09 | 70.46 | 0.161929E+10 | 0.100116E+09 | 0.00 | 1.00 | 04-OCT-13:30 | 0.00 | 01-OCT-00:10 | 30872.97 | 04-OCT-15:00 | 30872.97 | 04-OCT-15:00 | 2457.32 | 08-OCT-13:53 | 6172.70 | 04-OCT-15:00 | 0.00 |
November | 0.300978E+09 | 68107196.68 | 7.71 | 0.204179E+09 | 96798599.81 | 0.00 | 0.67 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 15759.55 | 04-NOV-14:30 | 11678.74 | 04-NOV-14:30 | 4626.31 | 04-NOV-16:00 | 3459.70 | 04-NOV-14:30 | 0.00 |
December | 250647.42 | 64340.67 | 0.08 | 184298.84 | 66348.58 | 0.00 | 0.05 | 29-DEC-07:05 | 0.00 | 01-DEC-00:10 | 1094.49 | 29-DEC-07:05 | 780.76 | 29-DEC-07:05 | 313.72 | 29-DEC-07:05 | 280.38 | 29-DEC-07:05 | 0.00 |
Annual Sum or Average | 0.930279E+11 | 0.200910E+11 | 1566.14 | 0.824827E+11 | 0.105452E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 250647.42 | 64340.67 | 0.08 | 184298.84 | 66348.58 | 0.00 | 0.05 | 0.00 | 981.82 | 780.76 | 143.06 | 251.84 | 0.00 | ||||||
Maximum of Months | 0.326565E+11 | 0.703511E+10 | 374.75 | 0.286644E+11 | 0.399214E+10 | 0.00 | 1.00 | 0.00 | 63345.77 | 59951.87 | 14790.46 | 15116.71 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.176013E+09 | 41897086.17 | 8.00 | 0.161571E+09 | 14441781.92 | 0.00 | 0.55 | 27-FEB-15:05 | 0.00 | 01-FEB-00:10 | 12257.36 | 27-FEB-15:05 | 12257.36 | 27-FEB-15:05 | 1162.11 | 27-FEB-17:13 | 2776.99 | 27-FEB-15:05 | 0.00 |
March | 0.272050E+09 | 66132181.71 | 23.68 | 0.243552E+09 | 28498173.76 | 0.00 | 0.50 | 18-MAR-14:05 | 0.00 | 01-MAR-00:10 | 10977.35 | 18-MAR-14:05 | 10977.35 | 18-MAR-14:05 | 1167.64 | 09-MAR-12:00 | 2520.32 | 18-MAR-14:05 | 0.00 |
April | 0.327395E+10 | 0.719049E+09 | 74.17 | 0.315564E+10 | 0.118302E+09 | 0.00 | 1.00 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 47633.47 | 27-APR-14:05 | 47633.47 | 27-APR-14:05 | 4038.44 | 28-APR-13:00 | 10123.69 | 27-APR-15:00 | 0.00 |
May | 0.678380E+10 | 0.147414E+10 | 163.42 | 0.610356E+10 | 0.680248E+09 | 0.00 | 1.00 | 03-MAY-15:30 | 0.00 | 01-MAY-00:10 | 41704.59 | 15-MAY-14:05 | 41704.59 | 15-MAY-14:05 | 6183.79 | 07-MAY-15:22 | 8414.71 | 04-MAY-15:00 | 0.00 |
June | 0.124106E+11 | 0.269764E+10 | 272.61 | 0.115778E+11 | 0.832730E+09 | 0.00 | 1.00 | 09-JUN-13:00 | 0.00 | 01-JUN-00:10 | 46129.66 | 28-JUN-15:20 | 46129.66 | 28-JUN-15:20 | 9041.92 | 12-JUN-06:02 | 9740.48 | 28-JUN-15:20 | 0.00 |
July | 0.234070E+11 | 0.501079E+10 | 356.14 | 0.208241E+11 | 0.258297E+10 | 0.00 | 1.00 | 06-JUL-14:05 | 0.00 | 01-JUL-00:10 | 64482.35 | 31-JUL-14:05 | 57676.57 | 31-JUL-14:05 | 16754.14 | 31-JUL-06:03 | 14340.22 | 31-JUL-14:05 | 0.00 |
August | 0.308485E+11 | 0.665536E+10 | 376.63 | 0.270887E+11 | 0.375980E+10 | 0.00 | 1.00 | 04-AUG-14:05 | 0.00 | 01-AUG-00:10 | 63568.89 | 29-AUG-14:30 | 57494.05 | 10-AUG-15:10 | 14969.12 | 30-AUG-13:00 | 14942.56 | 29-AUG-15:00 | 0.00 |
September | 0.115493E+11 | 0.246994E+10 | 233.48 | 0.965673E+10 | 0.189257E+10 | 0.00 | 1.00 | 08-SEP-13:20 | 0.00 | 01-SEP-00:10 | 51226.11 | 13-SEP-14:05 | 46959.98 | 12-SEP-14:05 | 14236.38 | 14-SEP-13:00 | 10282.49 | 13-SEP-14:05 | 0.00 |
October | 0.150391E+10 | 0.339169E+09 | 58.42 | 0.141391E+10 | 90000657.12 | 0.00 | 1.00 | 04-OCT-13:10 | 0.00 | 01-OCT-00:10 | 30066.81 | 04-OCT-15:00 | 30066.81 | 04-OCT-15:00 | 4212.52 | 08-OCT-12:53 | 6011.53 | 04-OCT-15:00 | 0.00 |
November | 0.329167E+09 | 73348371.45 | 8.00 | 0.232863E+09 | 96303757.35 | 0.00 | 0.77 | 04-NOV-14:05 | 0.00 | 01-NOV-00:10 | 17956.99 | 04-NOV-14:05 | 14247.38 | 04-NOV-14:05 | 4605.55 | 04-NOV-16:00 | 3842.05 | 04-NOV-14:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.905543E+11 | 0.195475E+11 | 1574.55 | 0.804584E+11 | 0.100959E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.308485E+11 | 0.665536E+10 | 376.63 | 0.270887E+11 | 0.375980E+10 | 0.00 | 1.00 | 0.00 | 64482.35 | 57676.57 | 16754.14 | 14942.56 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 27836.25 | 7192.60 | 0.02 | 25680.72 | 2155.53 | 0.00 | 0.02 | 02-JAN-06:17 | 0.00 | 01-JAN-00:05 | 371.15 | 02-JAN-06:17 | 342.41 | 02-JAN-06:17 | 28.74 | 02-JAN-06:17 | 95.90 | 02-JAN-06:17 | 0.00 |
February | 0.181629E+09 | 43522396.14 | 8.02 | 0.161896E+09 | 19732504.79 | 0.00 | 0.48 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 11693.92 | 27-FEB-15:00 | 11693.92 | 27-FEB-15:00 | 1354.90 | 27-FEB-17:05 | 2699.16 | 27-FEB-15:00 | 0.00 |
March | 0.390689E+09 | 95133935.77 | 27.42 | 0.355969E+09 | 34719858.74 | 0.00 | 0.44 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 10500.47 | 18-MAR-16:00 | 10500.47 | 18-MAR-16:00 | 1284.33 | 09-MAR-12:00 | 2451.26 | 18-MAR-16:00 | 0.00 |
April | 0.349758E+10 | 0.771074E+09 | 73.64 | 0.334153E+10 | 0.156051E+09 | 0.00 | 1.00 | 26-APR-13:05 | 0.00 | 01-APR-00:10 | 53966.13 | 27-APR-14:30 | 53966.13 | 27-APR-14:30 | 3904.24 | 28-APR-13:00 | 11642.60 | 27-APR-14:50 | 0.00 |
May | 0.715776E+10 | 0.155947E+10 | 162.81 | 0.637540E+10 | 0.782363E+09 | 0.00 | 1.00 | 04-MAY-12:30 | 0.00 | 01-MAY-00:10 | 45350.49 | 04-MAY-15:00 | 45350.49 | 04-MAY-15:00 | 6409.81 | 07-MAY-16:12 | 9191.96 | 04-MAY-15:00 | 0.00 |
June | 0.131383E+11 | 0.286545E+10 | 269.97 | 0.121649E+11 | 0.973393E+09 | 0.00 | 1.00 | 09-JUN-13:05 | 0.00 | 01-JUN-00:10 | 53756.26 | 28-JUN-15:20 | 53756.26 | 28-JUN-15:20 | 5171.44 | 12-JUN-12:40 | 11349.42 | 28-JUN-15:20 | 0.00 |
July | 0.250890E+11 | 0.538859E+10 | 355.11 | 0.221419E+11 | 0.294712E+10 | 0.00 | 1.00 | 06-JUL-14:40 | 0.00 | 01-JUL-00:10 | 70629.89 | 31-JUL-14:40 | 64086.41 | 31-JUL-14:40 | 12402.48 | 31-JUL-10:30 | 15946.58 | 24-JUL-15:00 | 0.00 |
August | 0.325395E+11 | 0.706066E+10 | 375.71 | 0.284373E+11 | 0.410229E+10 | 0.00 | 1.00 | 06-AUG-16:02 | 0.00 | 01-AUG-00:10 | 70274.72 | 10-AUG-14:50 | 65693.75 | 10-AUG-15:10 | 15098.82 | 30-AUG-13:00 | 16503.88 | 29-AUG-15:20 | 0.00 |
September | 0.116250E+11 | 0.250179E+10 | 229.86 | 0.959549E+10 | 0.202949E+10 | 0.00 | 1.00 | 08-SEP-14:00 | 0.00 | 01-SEP-00:10 | 50667.03 | 14-SEP-13:30 | 47215.76 | 12-SEP-15:00 | 13749.46 | 14-SEP-13:00 | 10182.61 | 14-SEP-13:05 | 0.00 |
October | 0.139680E+10 | 0.319535E+09 | 55.89 | 0.129113E+10 | 0.105670E+09 | 0.00 | 1.00 | 04-OCT-14:30 | 0.00 | 01-OCT-00:10 | 29522.26 | 04-OCT-15:00 | 29522.26 | 04-OCT-15:00 | 3339.10 | 08-OCT-12:43 | 5904.00 | 04-OCT-15:00 | 0.00 |
November | 0.335408E+09 | 75570682.22 | 7.71 | 0.229261E+09 | 0.106147E+09 | 0.00 | 0.70 | 04-NOV-14:20 | 0.00 | 01-NOV-00:10 | 18002.67 | 04-NOV-14:20 | 13542.29 | 04-NOV-14:10 | 5117.57 | 04-NOV-13:00 | 3922.15 | 04-NOV-14:20 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.953518E+11 | 0.206808E+11 | 1566.16 | 0.840948E+11 | 0.112570E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.325395E+11 | 0.706066E+10 | 375.71 | 0.284373E+11 | 0.410229E+10 | 0.00 | 1.00 | 0.00 | 70629.89 | 65693.75 | 15098.82 | 16503.88 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 240.22 | 0.00 | 240.22 | 11.31 | 1399.70 | 0.00 | 0.00 | 0.00 |
February | 373.79 | 0.00 | 373.79 | 83.50 | 1247.66 | 0.00 | 0.00 | 0.00 |
March | 550.72 | 0.00 | 550.72 | 241.63 | 1047.08 | 0.00 | 0.00 | 0.00 |
April | 779.33 | 2.76 | 776.56 | 510.94 | 856.35 | 0.00 | 0.00 | 0.00 |
May | 1002.80 | 29.79 | 973.01 | 816.01 | 701.03 | 0.00 | 0.00 | 0.00 |
June | 1054.42 | 69.63 | 984.79 | 947.10 | 542.99 | 0.00 | 0.00 | 0.00 |
July | 1002.17 | 78.57 | 923.59 | 1019.37 | 488.65 | 0.00 | 0.00 | 0.00 |
August | 811.26 | 21.93 | 789.33 | 841.31 | 476.71 | 0.00 | 0.00 | 0.00 |
September | 630.16 | 0.19 | 629.97 | 486.83 | 706.45 | 0.00 | 0.00 | 0.00 |
October | 431.76 | 0.00 | 431.76 | 202.66 | 929.81 | 0.00 | 0.00 | 0.00 |
November | 271.97 | 0.00 | 271.97 | 43.87 | 1136.68 | 0.00 | 0.00 | 0.00 |
December | 204.13 | 0.00 | 204.13 | 6.08 | 1409.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.91 | 17.03 | 596.88 | 436.41 | 910.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.13 | 0.00 | 204.13 | 6.08 | 476.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.42 | 78.57 | 984.79 | 1019.37 | 1409.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 257.34 | 65.24 | 192.09 | 96.39 | 886.36 | 0.00 | 0.00 | 0.00 |
February | 472.19 | 167.59 | 304.60 | 316.98 | 788.20 | 0.00 | 0.00 | 0.00 |
March | 705.01 | 255.22 | 449.79 | 590.89 | 672.35 | 0.00 | 0.00 | 0.00 |
April | 1092.89 | 454.11 | 638.78 | 1107.26 | 553.76 | 0.00 | 0.00 | 0.00 |
May | 1162.93 | 404.32 | 758.61 | 1234.99 | 473.24 | 0.00 | 0.00 | 0.00 |
June | 1392.74 | 605.99 | 786.75 | 1590.62 | 372.11 | 0.00 | 0.00 | 0.00 |
July | 1296.96 | 582.15 | 714.81 | 1548.24 | 328.59 | 0.00 | 0.00 | 0.00 |
August | 1274.74 | 637.70 | 637.04 | 1575.60 | 319.56 | 0.00 | 0.00 | 0.00 |
September | 942.48 | 434.68 | 507.80 | 1036.99 | 456.92 | 0.00 | 0.00 | 0.00 |
October | 614.31 | 261.02 | 353.28 | 562.66 | 601.51 | 0.00 | 0.00 | 0.00 |
November | 301.10 | 85.00 | 216.10 | 165.05 | 731.95 | 0.00 | 0.00 | 0.00 |
December | 246.97 | 79.51 | 167.46 | 120.36 | 902.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 814.80 | 336.78 | 478.02 | 831.44 | 589.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.97 | 65.24 | 167.46 | 96.39 | 319.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1392.74 | 637.70 | 786.75 | 1590.62 | 902.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1061.37 | 630.25 | 431.13 | 955.01 | 1272.15 | 0.00 | 0.00 | 0.00 |
February | 1632.23 | 1010.37 | 621.86 | 1671.67 | 1164.90 | 0.00 | 0.00 | 0.00 |
March | 1755.81 | 936.35 | 819.45 | 1871.33 | 1040.82 | 0.00 | 0.00 | 0.00 |
April | 1853.80 | 804.91 | 1048.89 | 2084.44 | 900.72 | 0.00 | 0.00 | 0.00 |
May | 1695.06 | 504.98 | 1190.09 | 1920.69 | 760.24 | 0.00 | 0.00 | 0.00 |
June | 1550.82 | 416.37 | 1134.44 | 1793.58 | 603.29 | 0.00 | 0.00 | 0.00 |
July | 1691.23 | 619.42 | 1071.81 | 2162.88 | 545.74 | 0.00 | 0.00 | 0.00 |
August | 1817.02 | 847.31 | 969.71 | 2405.44 | 525.33 | 0.00 | 0.00 | 0.00 |
September | 2013.18 | 1111.74 | 901.44 | 2503.18 | 724.54 | 0.00 | 0.00 | 0.00 |
October | 1823.60 | 1125.94 | 697.66 | 2075.41 | 925.97 | 0.00 | 0.00 | 0.00 |
November | 1078.17 | 617.88 | 460.29 | 1038.56 | 1080.61 | 0.00 | 0.00 | 0.00 |
December | 1128.08 | 730.02 | 398.05 | 1115.62 | 1315.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1591.01 | 778.19 | 812.82 | 1800.27 | 903.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1061.37 | 416.37 | 398.05 | 955.01 | 525.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2013.18 | 1125.94 | 1190.09 | 2503.18 | 1315.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.43 | 80.04 | 191.39 | 120.38 | 893.61 | 0.00 | 0.00 | 0.00 |
February | 486.65 | 182.90 | 303.75 | 350.11 | 799.09 | 0.00 | 0.00 | 0.00 |
March | 681.92 | 230.17 | 451.75 | 576.74 | 686.89 | 0.00 | 0.00 | 0.00 |
April | 1037.47 | 396.66 | 640.80 | 1047.09 | 582.09 | 0.00 | 0.00 | 0.00 |
May | 1334.98 | 542.33 | 792.65 | 1471.18 | 496.20 | 0.00 | 0.00 | 0.00 |
June | 1283.89 | 498.49 | 785.40 | 1446.21 | 392.37 | 0.00 | 0.00 | 0.00 |
July | 1586.07 | 833.72 | 752.35 | 1961.54 | 359.75 | 0.00 | 0.00 | 0.00 |
August | 1312.06 | 669.97 | 642.08 | 1647.56 | 349.28 | 0.00 | 0.00 | 0.00 |
September | 1068.47 | 512.67 | 555.79 | 1234.57 | 483.02 | 0.00 | 0.00 | 0.00 |
October | 608.28 | 247.85 | 360.44 | 566.03 | 618.85 | 0.00 | 0.00 | 0.00 |
November | 302.92 | 85.44 | 217.48 | 173.13 | 735.78 | 0.00 | 0.00 | 0.00 |
December | 254.66 | 87.27 | 167.40 | 141.83 | 911.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.63 | 365.34 | 489.29 | 898.29 | 608.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.66 | 80.04 | 167.40 | 120.38 | 349.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1586.07 | 833.72 | 792.65 | 1961.54 | 911.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.07 | 0.00 | 80.07 | 3.62 | 481.95 | 0.00 | 0.00 | 0.00 |
February | 124.59 | 0.00 | 124.59 | 28.31 | 428.31 | 0.00 | 0.00 | 0.00 |
March | 183.57 | 0.00 | 183.57 | 84.72 | 351.61 | 0.00 | 0.00 | 0.00 |
April | 259.76 | 0.92 | 258.84 | 179.23 | 282.35 | 0.00 | 0.00 | 0.00 |
May | 334.25 | 9.93 | 324.32 | 281.68 | 232.11 | 0.00 | 0.00 | 0.00 |
June | 351.46 | 23.21 | 328.25 | 324.41 | 179.76 | 0.00 | 0.00 | 0.00 |
July | 334.04 | 26.19 | 307.85 | 347.08 | 162.32 | 0.00 | 0.00 | 0.00 |
August | 270.41 | 7.31 | 263.10 | 285.41 | 159.66 | 0.00 | 0.00 | 0.00 |
September | 210.04 | 0.06 | 209.98 | 164.30 | 242.24 | 0.00 | 0.00 | 0.00 |
October | 143.91 | 0.00 | 143.91 | 65.08 | 329.68 | 0.00 | 0.00 | 0.00 |
November | 90.65 | 0.00 | 90.65 | 12.71 | 408.23 | 0.00 | 0.00 | 0.00 |
December | 68.04 | 0.00 | 68.04 | 1.49 | 495.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.63 | 5.68 | 198.95 | 148.91 | 312.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.04 | 0.00 | 68.04 | 1.49 | 159.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.46 | 26.19 | 328.25 | 347.08 | 495.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.07 | 0.00 | 80.07 | 3.62 | 481.98 | 0.00 | 0.00 | 0.00 |
February | 124.60 | 0.00 | 124.60 | 28.31 | 428.34 | 0.00 | 0.00 | 0.00 |
March | 183.57 | 0.00 | 183.57 | 84.72 | 351.64 | 0.00 | 0.00 | 0.00 |
April | 259.77 | 0.92 | 258.85 | 179.24 | 282.37 | 0.00 | 0.00 | 0.00 |
May | 334.26 | 9.93 | 324.33 | 281.69 | 232.12 | 0.00 | 0.00 | 0.00 |
June | 351.47 | 23.21 | 328.26 | 324.42 | 179.77 | 0.00 | 0.00 | 0.00 |
July | 334.05 | 26.19 | 307.86 | 347.09 | 162.33 | 0.00 | 0.00 | 0.00 |
August | 270.42 | 7.31 | 263.11 | 285.42 | 159.67 | 0.00 | 0.00 | 0.00 |
September | 210.05 | 0.06 | 209.99 | 164.30 | 242.26 | 0.00 | 0.00 | 0.00 |
October | 143.92 | 0.00 | 143.92 | 65.08 | 329.70 | 0.00 | 0.00 | 0.00 |
November | 90.66 | 0.00 | 90.66 | 12.71 | 408.25 | 0.00 | 0.00 | 0.00 |
December | 68.04 | 0.00 | 68.04 | 1.49 | 495.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.64 | 5.68 | 198.96 | 148.92 | 312.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.04 | 0.00 | 68.04 | 1.49 | 159.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.47 | 26.19 | 328.26 | 347.09 | 495.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.07 | 0.00 | 80.07 | 3.62 | 481.98 | 0.00 | 0.00 | 0.00 |
February | 124.60 | 0.00 | 124.60 | 28.31 | 428.34 | 0.00 | 0.00 | 0.00 |
March | 183.57 | 0.00 | 183.57 | 84.72 | 351.64 | 0.00 | 0.00 | 0.00 |
April | 259.77 | 0.92 | 258.85 | 179.24 | 282.37 | 0.00 | 0.00 | 0.00 |
May | 334.26 | 9.93 | 324.33 | 281.69 | 232.12 | 0.00 | 0.00 | 0.00 |
June | 351.47 | 23.21 | 328.26 | 324.42 | 179.77 | 0.00 | 0.00 | 0.00 |
July | 334.05 | 26.19 | 307.86 | 347.09 | 162.33 | 0.00 | 0.00 | 0.00 |
August | 270.42 | 7.31 | 263.11 | 285.42 | 159.67 | 0.00 | 0.00 | 0.00 |
September | 210.05 | 0.06 | 209.99 | 164.30 | 242.26 | 0.00 | 0.00 | 0.00 |
October | 143.92 | 0.00 | 143.92 | 65.08 | 329.70 | 0.00 | 0.00 | 0.00 |
November | 90.66 | 0.00 | 90.66 | 12.71 | 408.25 | 0.00 | 0.00 | 0.00 |
December | 68.04 | 0.00 | 68.04 | 1.49 | 495.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.64 | 5.68 | 198.96 | 148.92 | 312.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.04 | 0.00 | 68.04 | 1.49 | 159.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.47 | 26.19 | 328.26 | 347.09 | 495.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 247.55 | 62.76 | 184.78 | 91.74 | 880.84 | 0.00 | 0.00 | 0.00 |
February | 454.22 | 161.21 | 293.01 | 305.51 | 784.31 | 0.00 | 0.00 | 0.00 |
March | 678.19 | 245.51 | 432.68 | 576.51 | 661.97 | 0.00 | 0.00 | 0.00 |
April | 1051.30 | 436.83 | 614.47 | 1077.35 | 543.27 | 0.00 | 0.00 | 0.00 |
May | 1118.68 | 388.94 | 729.74 | 1202.63 | 462.21 | 0.00 | 0.00 | 0.00 |
June | 1339.75 | 582.93 | 756.82 | 1544.39 | 366.38 | 0.00 | 0.00 | 0.00 |
July | 1247.62 | 560.00 | 687.62 | 1501.83 | 322.60 | 0.00 | 0.00 | 0.00 |
August | 1226.23 | 613.43 | 612.80 | 1524.50 | 318.47 | 0.00 | 0.00 | 0.00 |
September | 906.62 | 418.14 | 488.48 | 1000.13 | 461.52 | 0.00 | 0.00 | 0.00 |
October | 590.93 | 251.09 | 339.84 | 535.51 | 624.50 | 0.00 | 0.00 | 0.00 |
November | 289.64 | 81.77 | 207.87 | 152.51 | 760.77 | 0.00 | 0.00 | 0.00 |
December | 237.57 | 76.48 | 161.09 | 112.24 | 916.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 783.80 | 323.97 | 459.83 | 804.60 | 591.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.57 | 62.76 | 161.09 | 91.74 | 318.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1339.75 | 613.43 | 756.82 | 1544.39 | 916.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.79 | 2.48 | 7.31 | 3.63 | 34.83 | 0.00 | 0.00 | 0.00 |
February | 17.96 | 6.37 | 11.59 | 12.08 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 26.81 | 9.71 | 17.11 | 22.79 | 26.17 | 0.00 | 0.00 | 0.00 |
April | 41.57 | 17.27 | 24.30 | 42.60 | 21.48 | 0.00 | 0.00 | 0.00 |
May | 44.23 | 15.38 | 28.85 | 47.55 | 18.28 | 0.00 | 0.00 | 0.00 |
June | 52.97 | 23.05 | 29.92 | 61.06 | 14.49 | 0.00 | 0.00 | 0.00 |
July | 49.33 | 22.14 | 27.19 | 59.38 | 12.76 | 0.00 | 0.00 | 0.00 |
August | 48.48 | 24.25 | 24.23 | 60.28 | 12.59 | 0.00 | 0.00 | 0.00 |
September | 35.85 | 16.53 | 19.31 | 39.54 | 18.25 | 0.00 | 0.00 | 0.00 |
October | 23.36 | 9.93 | 13.44 | 21.17 | 24.69 | 0.00 | 0.00 | 0.00 |
November | 11.45 | 3.23 | 8.22 | 6.03 | 30.08 | 0.00 | 0.00 | 0.00 |
December | 9.39 | 3.02 | 6.37 | 4.44 | 36.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.99 | 12.81 | 18.18 | 31.81 | 23.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.39 | 2.48 | 6.37 | 3.63 | 12.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.97 | 24.25 | 29.92 | 61.06 | 36.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.78 | 210.08 | 143.71 | 322.93 | 435.09 | 0.00 | 0.00 | 0.00 |
February | 544.07 | 336.78 | 207.28 | 563.78 | 403.94 | 0.00 | 0.00 | 0.00 |
March | 585.26 | 312.11 | 273.15 | 634.70 | 356.02 | 0.00 | 0.00 | 0.00 |
April | 617.92 | 268.30 | 349.63 | 708.63 | 302.10 | 0.00 | 0.00 | 0.00 |
May | 565.01 | 168.32 | 396.69 | 654.89 | 252.90 | 0.00 | 0.00 | 0.00 |
June | 516.93 | 138.79 | 378.14 | 611.46 | 200.37 | 0.00 | 0.00 | 0.00 |
July | 563.74 | 206.47 | 357.27 | 730.82 | 184.55 | 0.00 | 0.00 | 0.00 |
August | 605.66 | 282.43 | 323.23 | 809.39 | 180.93 | 0.00 | 0.00 | 0.00 |
September | 671.05 | 370.57 | 300.48 | 839.15 | 255.22 | 0.00 | 0.00 | 0.00 |
October | 607.86 | 375.31 | 232.55 | 694.02 | 333.98 | 0.00 | 0.00 | 0.00 |
November | 359.38 | 205.96 | 153.43 | 347.11 | 384.55 | 0.00 | 0.00 | 0.00 |
December | 376.02 | 243.34 | 132.68 | 373.60 | 459.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.33 | 259.39 | 270.94 | 607.69 | 311.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.78 | 138.79 | 132.68 | 322.93 | 180.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 671.05 | 375.31 | 396.69 | 839.15 | 459.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.78 | 210.08 | 143.71 | 322.93 | 435.09 | 0.00 | 0.00 | 0.00 |
February | 544.07 | 336.78 | 207.28 | 563.78 | 403.94 | 0.00 | 0.00 | 0.00 |
March | 585.26 | 312.11 | 273.15 | 634.70 | 356.02 | 0.00 | 0.00 | 0.00 |
April | 617.92 | 268.30 | 349.63 | 708.63 | 302.10 | 0.00 | 0.00 | 0.00 |
May | 565.01 | 168.32 | 396.69 | 654.89 | 252.90 | 0.00 | 0.00 | 0.00 |
June | 516.93 | 138.79 | 378.14 | 611.46 | 200.37 | 0.00 | 0.00 | 0.00 |
July | 563.74 | 206.47 | 357.27 | 730.82 | 184.55 | 0.00 | 0.00 | 0.00 |
August | 605.66 | 282.43 | 323.23 | 809.39 | 180.93 | 0.00 | 0.00 | 0.00 |
September | 671.05 | 370.57 | 300.48 | 839.15 | 255.22 | 0.00 | 0.00 | 0.00 |
October | 607.86 | 375.31 | 232.55 | 694.02 | 333.98 | 0.00 | 0.00 | 0.00 |
November | 359.38 | 205.96 | 153.43 | 347.11 | 384.55 | 0.00 | 0.00 | 0.00 |
December | 376.02 | 243.34 | 132.68 | 373.60 | 459.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.33 | 259.39 | 270.94 | 607.69 | 311.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.78 | 138.79 | 132.68 | 322.93 | 180.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 671.05 | 375.31 | 396.69 | 839.15 | 459.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.76 | 210.07 | 143.70 | 322.91 | 435.06 | 0.00 | 0.00 | 0.00 |
February | 544.03 | 336.76 | 207.27 | 563.75 | 403.91 | 0.00 | 0.00 | 0.00 |
March | 585.22 | 312.09 | 273.13 | 634.66 | 356.00 | 0.00 | 0.00 | 0.00 |
April | 617.88 | 268.28 | 349.60 | 708.58 | 302.08 | 0.00 | 0.00 | 0.00 |
May | 564.98 | 168.31 | 396.67 | 654.84 | 252.89 | 0.00 | 0.00 | 0.00 |
June | 516.90 | 138.78 | 378.12 | 611.42 | 200.36 | 0.00 | 0.00 | 0.00 |
July | 563.70 | 206.46 | 357.25 | 730.78 | 184.54 | 0.00 | 0.00 | 0.00 |
August | 605.63 | 282.41 | 323.21 | 809.34 | 180.92 | 0.00 | 0.00 | 0.00 |
September | 671.01 | 370.55 | 300.46 | 839.10 | 255.21 | 0.00 | 0.00 | 0.00 |
October | 607.82 | 375.28 | 232.54 | 693.97 | 333.96 | 0.00 | 0.00 | 0.00 |
November | 359.36 | 205.94 | 153.42 | 347.09 | 384.52 | 0.00 | 0.00 | 0.00 |
December | 376.00 | 243.32 | 132.67 | 373.58 | 459.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.30 | 259.38 | 270.92 | 607.65 | 311.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.76 | 138.78 | 132.67 | 322.91 | 180.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 671.01 | 375.28 | 396.67 | 839.10 | 459.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 261.10 | 76.99 | 184.11 | 117.35 | 889.52 | 0.00 | 0.00 | 0.00 |
February | 468.13 | 175.94 | 292.20 | 341.48 | 798.04 | 0.00 | 0.00 | 0.00 |
March | 655.97 | 221.41 | 434.57 | 565.02 | 678.65 | 0.00 | 0.00 | 0.00 |
April | 998.00 | 381.57 | 616.42 | 1024.33 | 569.95 | 0.00 | 0.00 | 0.00 |
May | 1284.19 | 521.69 | 762.49 | 1432.63 | 490.98 | 0.00 | 0.00 | 0.00 |
June | 1235.04 | 479.52 | 755.51 | 1408.82 | 386.62 | 0.00 | 0.00 | 0.00 |
July | 1525.72 | 801.99 | 723.73 | 1901.74 | 360.90 | 0.00 | 0.00 | 0.00 |
August | 1262.13 | 644.48 | 617.65 | 1595.89 | 351.06 | 0.00 | 0.00 | 0.00 |
September | 1027.82 | 493.17 | 534.65 | 1191.45 | 492.80 | 0.00 | 0.00 | 0.00 |
October | 585.14 | 238.42 | 346.72 | 540.55 | 644.31 | 0.00 | 0.00 | 0.00 |
November | 291.40 | 82.19 | 209.21 | 162.08 | 765.99 | 0.00 | 0.00 | 0.00 |
December | 244.97 | 83.95 | 161.03 | 135.75 | 927.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 822.11 | 351.44 | 470.67 | 871.56 | 612.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 244.97 | 76.99 | 161.03 | 117.35 | 351.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1525.72 | 801.99 | 762.49 | 1901.74 | 927.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.32 | 3.04 | 7.28 | 4.64 | 35.17 | 0.00 | 0.00 | 0.00 |
February | 18.51 | 6.96 | 11.55 | 13.50 | 31.55 | 0.00 | 0.00 | 0.00 |
March | 25.94 | 8.75 | 17.18 | 22.34 | 26.83 | 0.00 | 0.00 | 0.00 |
April | 39.46 | 15.09 | 24.37 | 40.50 | 22.54 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 20.63 | 30.15 | 56.64 | 19.41 | 0.00 | 0.00 | 0.00 |
June | 48.83 | 18.96 | 29.87 | 55.70 | 15.29 | 0.00 | 0.00 | 0.00 |
July | 60.33 | 31.71 | 28.62 | 75.19 | 14.27 | 0.00 | 0.00 | 0.00 |
August | 49.90 | 25.48 | 24.42 | 63.10 | 13.88 | 0.00 | 0.00 | 0.00 |
September | 40.64 | 19.50 | 21.14 | 47.11 | 19.48 | 0.00 | 0.00 | 0.00 |
October | 23.14 | 9.43 | 13.71 | 21.37 | 25.48 | 0.00 | 0.00 | 0.00 |
November | 11.52 | 3.25 | 8.27 | 6.41 | 30.29 | 0.00 | 0.00 | 0.00 |
December | 9.69 | 3.32 | 6.37 | 5.37 | 36.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.51 | 13.90 | 18.61 | 34.46 | 24.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.69 | 3.04 | 6.37 | 4.64 | 13.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.33 | 31.71 | 30.15 | 75.19 | 36.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 240.22 | 0.00 | 240.22 | 9.11 | 1472.37 | 0.00 | 0.00 | 0.00 |
February | 373.79 | 0.00 | 373.79 | 75.22 | 1324.54 | 0.00 | 0.00 | 0.00 |
March | 550.72 | 0.00 | 550.72 | 226.80 | 1114.76 | 0.00 | 0.00 | 0.00 |
April | 779.33 | 2.76 | 776.56 | 497.83 | 902.33 | 0.00 | 0.00 | 0.00 |
May | 1002.80 | 29.79 | 973.01 | 807.97 | 730.91 | 0.00 | 0.00 | 0.00 |
June | 1054.42 | 69.63 | 984.79 | 943.96 | 561.30 | 0.00 | 0.00 | 0.00 |
July | 1002.17 | 78.57 | 923.59 | 1018.90 | 504.22 | 0.00 | 0.00 | 0.00 |
August | 811.26 | 21.93 | 789.33 | 838.69 | 494.35 | 0.00 | 0.00 | 0.00 |
September | 630.16 | 0.19 | 629.97 | 478.01 | 744.63 | 0.00 | 0.00 | 0.00 |
October | 431.76 | 0.00 | 431.76 | 186.51 | 1001.42 | 0.00 | 0.00 | 0.00 |
November | 271.97 | 0.00 | 271.97 | 36.06 | 1224.09 | 0.00 | 0.00 | 0.00 |
December | 204.13 | 0.00 | 204.13 | 3.91 | 1497.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.91 | 17.03 | 596.88 | 429.13 | 962.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.13 | 0.00 | 204.13 | 3.91 | 494.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.42 | 78.57 | 984.79 | 1018.90 | 1497.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 257.34 | 65.24 | 192.09 | 91.55 | 932.00 | 0.00 | 0.00 | 0.00 |
February | 472.19 | 167.59 | 304.60 | 304.54 | 836.10 | 0.00 | 0.00 | 0.00 |
March | 705.01 | 255.22 | 449.79 | 576.51 | 714.80 | 0.00 | 0.00 | 0.00 |
April | 1092.89 | 454.11 | 638.78 | 1095.52 | 580.73 | 0.00 | 0.00 | 0.00 |
May | 1162.93 | 404.32 | 758.61 | 1227.87 | 492.00 | 0.00 | 0.00 | 0.00 |
June | 1392.74 | 605.99 | 786.75 | 1587.30 | 383.87 | 0.00 | 0.00 | 0.00 |
July | 1296.96 | 582.15 | 714.81 | 1545.26 | 338.07 | 0.00 | 0.00 | 0.00 |
August | 1274.74 | 637.70 | 637.04 | 1571.98 | 330.27 | 0.00 | 0.00 | 0.00 |
September | 942.48 | 434.68 | 507.80 | 1028.53 | 479.82 | 0.00 | 0.00 | 0.00 |
October | 614.31 | 261.02 | 353.28 | 548.25 | 645.42 | 0.00 | 0.00 | 0.00 |
November | 301.10 | 85.00 | 216.10 | 154.77 | 788.73 | 0.00 | 0.00 | 0.00 |
December | 246.97 | 79.51 | 167.46 | 113.95 | 959.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 814.80 | 336.78 | 478.02 | 823.14 | 622.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.97 | 65.24 | 167.46 | 91.55 | 330.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1392.74 | 637.70 | 786.75 | 1587.30 | 959.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1061.37 | 630.25 | 431.13 | 941.95 | 1338.22 | 0.00 | 0.00 | 0.00 |
February | 1632.23 | 1010.37 | 621.86 | 1653.49 | 1232.82 | 0.00 | 0.00 | 0.00 |
March | 1755.81 | 936.35 | 819.45 | 1857.75 | 1104.27 | 0.00 | 0.00 | 0.00 |
April | 1853.80 | 804.91 | 1048.89 | 2075.35 | 944.70 | 0.00 | 0.00 | 0.00 |
May | 1695.06 | 504.98 | 1190.09 | 1917.34 | 791.93 | 0.00 | 0.00 | 0.00 |
June | 1550.82 | 416.37 | 1134.44 | 1794.61 | 624.37 | 0.00 | 0.00 | 0.00 |
July | 1691.23 | 619.42 | 1071.81 | 2165.57 | 563.11 | 0.00 | 0.00 | 0.00 |
August | 1817.02 | 847.31 | 969.71 | 2406.91 | 544.19 | 0.00 | 0.00 | 0.00 |
September | 2013.18 | 1111.74 | 901.44 | 2496.96 | 759.69 | 0.00 | 0.00 | 0.00 |
October | 1823.60 | 1125.94 | 697.66 | 2060.38 | 989.60 | 0.00 | 0.00 | 0.00 |
November | 1078.17 | 617.88 | 460.29 | 1020.73 | 1159.14 | 0.00 | 0.00 | 0.00 |
December | 1128.08 | 730.02 | 398.05 | 1101.65 | 1395.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1591.01 | 778.19 | 812.82 | 1791.58 | 952.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1061.37 | 416.37 | 398.05 | 941.95 | 544.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2013.18 | 1125.94 | 1190.09 | 2496.96 | 1395.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.43 | 80.04 | 191.39 | 116.97 | 939.93 | 0.00 | 0.00 | 0.00 |
February | 486.65 | 182.90 | 303.75 | 342.39 | 847.45 | 0.00 | 0.00 | 0.00 |
March | 681.92 | 230.17 | 451.75 | 567.19 | 730.64 | 0.00 | 0.00 | 0.00 |
April | 1037.47 | 396.66 | 640.80 | 1039.74 | 612.15 | 0.00 | 0.00 | 0.00 |
May | 1334.98 | 542.33 | 792.65 | 1468.82 | 517.45 | 0.00 | 0.00 | 0.00 |
June | 1283.89 | 498.49 | 785.40 | 1447.26 | 406.44 | 0.00 | 0.00 | 0.00 |
July | 1586.07 | 833.72 | 752.35 | 1964.22 | 371.62 | 0.00 | 0.00 | 0.00 |
August | 1312.06 | 669.97 | 642.08 | 1648.51 | 361.97 | 0.00 | 0.00 | 0.00 |
September | 1068.47 | 512.67 | 555.79 | 1230.35 | 507.38 | 0.00 | 0.00 | 0.00 |
October | 608.28 | 247.85 | 360.44 | 555.75 | 664.85 | 0.00 | 0.00 | 0.00 |
November | 302.92 | 85.44 | 217.48 | 165.57 | 791.33 | 0.00 | 0.00 | 0.00 |
December | 254.66 | 87.27 | 167.40 | 138.01 | 968.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.63 | 365.34 | 489.29 | 894.02 | 642.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.66 | 80.04 | 167.40 | 116.97 | 361.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1586.07 | 833.72 | 792.65 | 1964.22 | 968.32 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643410E+09 | 0.00 | 0.643410E+09 | 30291330.25 | 0.374895E+10 |
February | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.202010E+09 | 0.301835E+10 |
March | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.647189E+09 | 0.280451E+10 |
April | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.132436E+10 | 0.221966E+10 |
May | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.218561E+10 | 0.187765E+10 |
June | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.245489E+10 | 0.140743E+10 |
July | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.273029E+10 | 0.130881E+10 |
August | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.225337E+10 | 0.127681E+10 |
September | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.126187E+10 | 0.183112E+10 |
October | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.542805E+09 | 0.249042E+10 |
November | 0.704943E+09 | 0.00 | 0.704943E+09 | 0.113711E+09 | 0.294628E+10 |
December | 0.546732E+09 | 0.00 | 0.546732E+09 | 16290821.70 | 0.377395E+10 |
Annual Sum or Average | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.137627E+11 | 0.287039E+11 |
Minimum of Months | 0.546732E+09 | 0.00 | 0.546732E+09 | 16290821.70 | 0.127681E+10 |
Maximum of Months | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.273029E+10 | 0.377395E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.258184E+09 | 0.237403E+10 |
February | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.766827E+09 | 0.190681E+10 |
March | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.158265E+10 | 0.180081E+10 |
April | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.287001E+10 | 0.143534E+10 |
May | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.330780E+10 | 0.126752E+10 |
June | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.412288E+10 | 0.964504E+09 |
July | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.414680E+10 | 0.880102E+09 |
August | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.422008E+10 | 0.855898E+09 |
September | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.268787E+10 | 0.118434E+10 |
October | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.150702E+10 | 0.161109E+10 |
November | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.427822E+09 | 0.189721E+10 |
December | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.322361E+09 | 0.241618E+10 |
Annual Sum or Average | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.262203E+11 | 0.185938E+11 |
Minimum of Months | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.258184E+09 | 0.855898E+09 |
Maximum of Months | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.422008E+10 | 0.241618E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.255789E+10 | 0.340732E+10 |
February | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.404410E+10 | 0.281814E+10 |
March | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.501218E+10 | 0.278773E+10 |
April | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.540287E+10 | 0.233467E+10 |
May | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.514438E+10 | 0.203624E+10 |
June | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.464895E+10 | 0.156372E+10 |
July | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.579306E+10 | 0.146171E+10 |
August | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.644273E+10 | 0.140705E+10 |
September | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.648823E+10 | 0.187802E+10 |
October | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.555879E+10 | 0.248013E+10 |
November | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.269195E+10 | 0.280094E+10 |
December | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.298807E+10 | 0.352259E+10 |
Annual Sum or Average | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.567732E+11 | 0.284983E+11 |
Minimum of Months | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.255789E+10 | 0.140705E+10 |
Maximum of Months | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.648823E+10 | 0.352259E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.322420E+09 | 0.239344E+10 |
February | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.846989E+09 | 0.193316E+10 |
March | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.154474E+10 | 0.183978E+10 |
April | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.271406E+10 | 0.150877E+10 |
May | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.394042E+10 | 0.132903E+10 |
June | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.374857E+10 | 0.101703E+10 |
July | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.525379E+10 | 0.963547E+09 |
August | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.441283E+10 | 0.935499E+09 |
September | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.320002E+10 | 0.125199E+10 |
October | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.151606E+10 | 0.165752E+10 |
November | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.448751E+09 | 0.190714E+10 |
December | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.379871E+09 | 0.244146E+10 |
Annual Sum or Average | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.283285E+11 | 0.191784E+11 |
Minimum of Months | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.322420E+09 | 0.935499E+09 |
Maximum of Months | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.525379E+10 | 0.244146E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214460E+09 | 0.00 | 0.214460E+09 | 9696742.47 | 0.129085E+10 |
February | 0.301411E+09 | 0.00 | 0.301411E+09 | 68487899.60 | 0.103618E+10 |
March | 0.491662E+09 | 0.00 | 0.491662E+09 | 0.226920E+09 | 0.941765E+09 |
April | 0.673308E+09 | 2388428.59 | 0.670920E+09 | 0.464574E+09 | 0.731844E+09 |
May | 0.895257E+09 | 26596794.15 | 0.868661E+09 | 0.754445E+09 | 0.621678E+09 |
June | 0.910975E+09 | 60156990.47 | 0.850818E+09 | 0.840860E+09 | 0.465928E+09 |
July | 0.894693E+09 | 70148169.12 | 0.824545E+09 | 0.929609E+09 | 0.434771E+09 |
August | 0.724260E+09 | 19578934.08 | 0.704681E+09 | 0.764450E+09 | 0.427628E+09 |
September | 0.544432E+09 | 160544.72 | 0.544271E+09 | 0.425853E+09 | 0.627897E+09 |
October | 0.385461E+09 | 0.00 | 0.385461E+09 | 0.174309E+09 | 0.883005E+09 |
November | 0.234970E+09 | 0.00 | 0.234970E+09 | 32952131.70 | 0.105813E+10 |
December | 0.182235E+09 | 0.00 | 0.182235E+09 | 4001659.41 | 0.132823E+10 |
Annual Sum or Average | 0.645312E+10 | 0.179030E+09 | 0.627410E+10 | 0.469616E+10 | 0.984790E+10 |
Minimum of Months | 0.182235E+09 | 0.00 | 0.182235E+09 | 4001659.41 | 0.427628E+09 |
Maximum of Months | 0.910975E+09 | 70148169.12 | 0.868661E+09 | 0.929609E+09 | 0.132823E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214468E+09 | 0.00 | 0.214468E+09 | 9695838.98 | 0.129094E+10 |
February | 0.301422E+09 | 0.00 | 0.301422E+09 | 68486833.76 | 0.103624E+10 |
March | 0.491681E+09 | 0.00 | 0.491681E+09 | 0.226922E+09 | 0.941825E+09 |
April | 0.673334E+09 | 2388492.79 | 0.670946E+09 | 0.464586E+09 | 0.731890E+09 |
May | 0.895292E+09 | 26597509.08 | 0.868695E+09 | 0.754466E+09 | 0.621717E+09 |
June | 0.911011E+09 | 60158607.51 | 0.850852E+09 | 0.840885E+09 | 0.465956E+09 |
July | 0.894729E+09 | 70150054.72 | 0.824579E+09 | 0.929642E+09 | 0.434797E+09 |
August | 0.724290E+09 | 19579460.37 | 0.704710E+09 | 0.764479E+09 | 0.427653E+09 |
September | 0.544454E+09 | 160549.03 | 0.544293E+09 | 0.425865E+09 | 0.627934E+09 |
October | 0.385475E+09 | 0.00 | 0.385475E+09 | 0.174311E+09 | 0.883059E+09 |
November | 0.234979E+09 | 0.00 | 0.234979E+09 | 32950907.95 | 0.105820E+10 |
December | 0.182242E+09 | 0.00 | 0.182242E+09 | 4001234.90 | 0.132831E+10 |
Annual Sum or Average | 0.645338E+10 | 0.179035E+09 | 0.627434E+10 | 0.469629E+10 | 0.984852E+10 |
Minimum of Months | 0.182242E+09 | 0.00 | 0.182242E+09 | 4001234.90 | 0.427653E+09 |
Maximum of Months | 0.911011E+09 | 70150054.72 | 0.868695E+09 | 0.929642E+09 | 0.132831E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214468E+09 | 0.00 | 0.214468E+09 | 9695838.98 | 0.129094E+10 |
February | 0.301422E+09 | 0.00 | 0.301422E+09 | 68486833.76 | 0.103624E+10 |
March | 0.491681E+09 | 0.00 | 0.491681E+09 | 0.226922E+09 | 0.941825E+09 |
April | 0.673334E+09 | 2388492.79 | 0.670946E+09 | 0.464586E+09 | 0.731890E+09 |
May | 0.895292E+09 | 26597509.08 | 0.868695E+09 | 0.754466E+09 | 0.621717E+09 |
June | 0.911011E+09 | 60158607.51 | 0.850852E+09 | 0.840885E+09 | 0.465956E+09 |
July | 0.894729E+09 | 70150054.72 | 0.824579E+09 | 0.929642E+09 | 0.434797E+09 |
August | 0.724290E+09 | 19579460.37 | 0.704710E+09 | 0.764479E+09 | 0.427653E+09 |
September | 0.544454E+09 | 160549.03 | 0.544293E+09 | 0.425865E+09 | 0.627934E+09 |
October | 0.385475E+09 | 0.00 | 0.385475E+09 | 0.174311E+09 | 0.883059E+09 |
November | 0.234979E+09 | 0.00 | 0.234979E+09 | 32950907.95 | 0.105820E+10 |
December | 0.182242E+09 | 0.00 | 0.182242E+09 | 4001234.90 | 0.132831E+10 |
Annual Sum or Average | 0.645338E+10 | 0.179035E+09 | 0.627434E+10 | 0.469629E+10 | 0.984852E+10 |
Minimum of Months | 0.182242E+09 | 0.00 | 0.182242E+09 | 4001234.90 | 0.427653E+09 |
Maximum of Months | 0.911011E+09 | 70150054.72 | 0.868695E+09 | 0.929642E+09 | 0.132831E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.663026E+09 | 0.168099E+09 | 0.494928E+09 | 0.245714E+09 | 0.235925E+10 |
February | 0.109885E+10 | 0.390005E+09 | 0.708849E+09 | 0.739083E+09 | 0.189741E+10 |
March | 0.181645E+10 | 0.657569E+09 | 0.115888E+10 | 0.154414E+10 | 0.177302E+10 |
April | 0.272498E+10 | 0.113226E+10 | 0.159271E+10 | 0.279250E+10 | 0.140815E+10 |
May | 0.299628E+10 | 0.104173E+10 | 0.195454E+10 | 0.322112E+10 | 0.123799E+10 |
June | 0.347262E+10 | 0.151096E+10 | 0.196167E+10 | 0.400305E+10 | 0.949657E+09 |
July | 0.334161E+10 | 0.149990E+10 | 0.184171E+10 | 0.402250E+10 | 0.864054E+09 |
August | 0.328434E+10 | 0.164301E+10 | 0.164133E+10 | 0.408322E+10 | 0.852999E+09 |
September | 0.234995E+10 | 0.108382E+10 | 0.126614E+10 | 0.259234E+10 | 0.119625E+10 |
October | 0.158275E+10 | 0.672519E+09 | 0.910234E+09 | 0.143430E+10 | 0.167265E+10 |
November | 0.750753E+09 | 0.211944E+09 | 0.538809E+09 | 0.395307E+09 | 0.197193E+10 |
December | 0.636312E+09 | 0.204847E+09 | 0.431465E+09 | 0.300622E+09 | 0.245573E+10 |
Annual Sum or Average | 0.247179E+11 | 0.102167E+11 | 0.145013E+11 | 0.253739E+11 | 0.186391E+11 |
Minimum of Months | 0.636312E+09 | 0.168099E+09 | 0.431465E+09 | 0.245714E+09 | 0.852999E+09 |
Maximum of Months | 0.347262E+10 | 0.164301E+10 | 0.196167E+10 | 0.408322E+10 | 0.245573E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 26215457.77 | 6646464.26 | 19568993.51 | 9715302.41 | 93282511.58 |
February | 43447695.55 | 15420448.04 | 28027247.51 | 29222678.72 | 75021698.52 |
March | 71820864.26 | 25999666.84 | 45821197.41 | 61053787.52 | 70103529.57 |
April | 0.107743E+09 | 44768711.23 | 62974500.44 | 0.110413E+09 | 55677154.00 |
May | 0.118470E+09 | 41189145.54 | 77280911.26 | 0.127360E+09 | 48948822.19 |
June | 0.137304E+09 | 59741882.25 | 77562527.03 | 0.158277E+09 | 37548597.70 |
July | 0.132124E+09 | 59304779.97 | 72819649.84 | 0.159046E+09 | 34163915.04 |
August | 0.129860E+09 | 64963042.56 | 64896715.45 | 0.161447E+09 | 33726804.71 |
September | 92915081.92 | 42853079.58 | 50062002.35 | 0.102499E+09 | 47298605.10 |
October | 62580638.09 | 26590795.31 | 35989842.77 | 56711020.45 | 66135246.08 |
November | 29684100.24 | 8380085.62 | 21304014.63 | 15630080.42 | 77968202.38 |
December | 25159213.77 | 8099466.92 | 17059746.85 | 11886325.36 | 97097547.18 |
Annual Sum or Average | 0.977325E+09 | 0.403958E+09 | 0.573367E+09 | 0.100326E+10 | 0.736973E+09 |
Minimum of Months | 25159213.77 | 6646464.26 | 17059746.85 | 9715302.41 | 33726804.71 |
Maximum of Months | 0.137304E+09 | 64963042.56 | 77562527.03 | 0.161447E+09 | 97097547.18 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947578E+09 | 0.562675E+09 | 0.384903E+09 | 0.864942E+09 | 0.116534E+10 |
February | 0.131621E+10 | 0.814748E+09 | 0.501459E+09 | 0.136390E+10 | 0.977203E+09 |
March | 0.156756E+10 | 0.835959E+09 | 0.731600E+09 | 0.169999E+10 | 0.953576E+09 |
April | 0.160166E+10 | 0.695428E+09 | 0.906231E+09 | 0.183676E+10 | 0.783032E+09 |
May | 0.151333E+10 | 0.450834E+09 | 0.106250E+10 | 0.175405E+10 | 0.677370E+09 |
June | 0.133989E+10 | 0.359740E+09 | 0.980149E+09 | 0.158491E+10 | 0.519363E+09 |
July | 0.150991E+10 | 0.553007E+09 | 0.956908E+09 | 0.195743E+10 | 0.494298E+09 |
August | 0.162221E+10 | 0.756459E+09 | 0.865751E+09 | 0.216787E+10 | 0.484601E+09 |
September | 0.173936E+10 | 0.960528E+09 | 0.778832E+09 | 0.217508E+10 | 0.661534E+09 |
October | 0.162808E+10 | 0.100522E+10 | 0.622864E+09 | 0.185886E+10 | 0.894535E+09 |
November | 0.931525E+09 | 0.533841E+09 | 0.397684E+09 | 0.899706E+09 | 0.996742E+09 |
December | 0.100713E+10 | 0.651752E+09 | 0.355377E+09 | 0.100066E+10 | 0.123007E+10 |
Annual Sum or Average | 0.167244E+11 | 0.818019E+10 | 0.854426E+10 | 0.191642E+11 | 0.983766E+10 |
Minimum of Months | 0.931525E+09 | 0.359740E+09 | 0.355377E+09 | 0.864942E+09 | 0.484601E+09 |
Maximum of Months | 0.173936E+10 | 0.100522E+10 | 0.106250E+10 | 0.217508E+10 | 0.123007E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947578E+09 | 0.562675E+09 | 0.384903E+09 | 0.864942E+09 | 0.116534E+10 |
February | 0.131621E+10 | 0.814748E+09 | 0.501459E+09 | 0.136390E+10 | 0.977203E+09 |
March | 0.156756E+10 | 0.835959E+09 | 0.731600E+09 | 0.169999E+10 | 0.953576E+09 |
April | 0.160166E+10 | 0.695428E+09 | 0.906231E+09 | 0.183676E+10 | 0.783032E+09 |
May | 0.151333E+10 | 0.450834E+09 | 0.106250E+10 | 0.175405E+10 | 0.677370E+09 |
June | 0.133989E+10 | 0.359740E+09 | 0.980149E+09 | 0.158491E+10 | 0.519363E+09 |
July | 0.150991E+10 | 0.553007E+09 | 0.956908E+09 | 0.195743E+10 | 0.494298E+09 |
August | 0.162221E+10 | 0.756459E+09 | 0.865751E+09 | 0.216787E+10 | 0.484601E+09 |
September | 0.173936E+10 | 0.960528E+09 | 0.778832E+09 | 0.217508E+10 | 0.661534E+09 |
October | 0.162808E+10 | 0.100522E+10 | 0.622864E+09 | 0.185886E+10 | 0.894535E+09 |
November | 0.931525E+09 | 0.533841E+09 | 0.397684E+09 | 0.899706E+09 | 0.996742E+09 |
December | 0.100713E+10 | 0.651752E+09 | 0.355377E+09 | 0.100066E+10 | 0.123007E+10 |
Annual Sum or Average | 0.167244E+11 | 0.818019E+10 | 0.854426E+10 | 0.191642E+11 | 0.983766E+10 |
Minimum of Months | 0.931525E+09 | 0.359740E+09 | 0.355377E+09 | 0.864942E+09 | 0.484601E+09 |
Maximum of Months | 0.173936E+10 | 0.100522E+10 | 0.106250E+10 | 0.217508E+10 | 0.123007E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947518E+09 | 0.562639E+09 | 0.384879E+09 | 0.864888E+09 | 0.116527E+10 |
February | 0.131612E+10 | 0.814697E+09 | 0.501427E+09 | 0.136381E+10 | 0.977141E+09 |
March | 0.156746E+10 | 0.835906E+09 | 0.731554E+09 | 0.169988E+10 | 0.953516E+09 |
April | 0.160156E+10 | 0.695384E+09 | 0.906174E+09 | 0.183665E+10 | 0.782983E+09 |
May | 0.151324E+10 | 0.450805E+09 | 0.106243E+10 | 0.175394E+10 | 0.677327E+09 |
June | 0.133981E+10 | 0.359718E+09 | 0.980087E+09 | 0.158481E+10 | 0.519330E+09 |
July | 0.150982E+10 | 0.552972E+09 | 0.956847E+09 | 0.195731E+10 | 0.494267E+09 |
August | 0.162211E+10 | 0.756411E+09 | 0.865696E+09 | 0.216773E+10 | 0.484570E+09 |
September | 0.173925E+10 | 0.960467E+09 | 0.778782E+09 | 0.217495E+10 | 0.661493E+09 |
October | 0.162798E+10 | 0.100515E+10 | 0.622825E+09 | 0.185874E+10 | 0.894478E+09 |
November | 0.931466E+09 | 0.533807E+09 | 0.397659E+09 | 0.899650E+09 | 0.996679E+09 |
December | 0.100707E+10 | 0.651711E+09 | 0.355355E+09 | 0.100060E+10 | 0.122999E+10 |
Annual Sum or Average | 0.167234E+11 | 0.817967E+10 | 0.854372E+10 | 0.191630E+11 | 0.983704E+10 |
Minimum of Months | 0.931466E+09 | 0.359718E+09 | 0.355355E+09 | 0.864888E+09 | 0.484570E+09 |
Maximum of Months | 0.173925E+10 | 0.100515E+10 | 0.106243E+10 | 0.217495E+10 | 0.122999E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.699333E+09 | 0.206220E+09 | 0.493113E+09 | 0.314306E+09 | 0.238249E+10 |
February | 0.113251E+10 | 0.425627E+09 | 0.706881E+09 | 0.826112E+09 | 0.193062E+10 |
March | 0.175696E+10 | 0.593020E+09 | 0.116394E+10 | 0.151335E+10 | 0.181770E+10 |
April | 0.258680E+10 | 0.989031E+09 | 0.159777E+10 | 0.265507E+10 | 0.147732E+10 |
May | 0.343957E+10 | 0.139731E+10 | 0.204226E+10 | 0.383716E+10 | 0.131503E+10 |
June | 0.320122E+10 | 0.124292E+10 | 0.195829E+10 | 0.365166E+10 | 0.100212E+10 |
July | 0.408649E+10 | 0.214806E+10 | 0.193843E+10 | 0.509362E+10 | 0.966630E+09 |
August | 0.338050E+10 | 0.172618E+10 | 0.165433E+10 | 0.427444E+10 | 0.940274E+09 |
September | 0.266410E+10 | 0.127829E+10 | 0.138581E+10 | 0.308824E+10 | 0.127734E+10 |
October | 0.156724E+10 | 0.638572E+09 | 0.928664E+09 | 0.144782E+10 | 0.172572E+10 |
November | 0.755297E+09 | 0.213025E+09 | 0.542273E+09 | 0.420101E+09 | 0.198545E+10 |
December | 0.656139E+09 | 0.224842E+09 | 0.431298E+09 | 0.363583E+09 | 0.248529E+10 |
Annual Sum or Average | 0.259262E+11 | 0.110831E+11 | 0.148431E+11 | 0.274855E+11 | 0.193060E+11 |
Minimum of Months | 0.656139E+09 | 0.206220E+09 | 0.431298E+09 | 0.314306E+09 | 0.940274E+09 |
Maximum of Months | 0.408649E+10 | 0.214806E+10 | 0.204226E+10 | 0.509362E+10 | 0.248529E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27650915.06 | 8153722.29 | 19497192.77 | 12427315.50 | 94201654.67 |
February | 44778247.18 | 16828866.23 | 27949380.95 | 32663594.35 | 76334925.56 |
March | 69468548.27 | 23447401.83 | 46021146.44 | 59836308.48 | 71870343.69 |
April | 0.102280E+09 | 39105269.61 | 63174340.74 | 0.104979E+09 | 58411909.40 |
May | 0.135997E+09 | 55248024.25 | 80749036.80 | 0.151717E+09 | 51995054.87 |
June | 0.126573E+09 | 49143820.67 | 77429023.39 | 0.144383E+09 | 39622958.90 |
July | 0.161576E+09 | 84932032.48 | 76643484.53 | 0.201396E+09 | 38219662.79 |
August | 0.133662E+09 | 68251229.16 | 65410395.83 | 0.169007E+09 | 37177581.80 |
September | 0.105336E+09 | 50542232.62 | 54793546.51 | 0.122106E+09 | 50504964.46 |
October | 61966936.11 | 25248478.46 | 36718457.65 | 57245369.97 | 68233295.83 |
November | 29863697.12 | 8422773.34 | 21440923.78 | 16610350.53 | 78502991.35 |
December | 25943078.99 | 8890003.39 | 17053075.60 | 14375686.52 | 98266319.53 |
Annual Sum or Average | 0.102509E+10 | 0.438214E+09 | 0.586880E+09 | 0.108675E+10 | 0.763342E+09 |
Minimum of Months | 25943078.99 | 8153722.29 | 17053075.60 | 12427315.50 | 37177581.80 |
Maximum of Months | 0.161576E+09 | 84932032.48 | 80749036.80 | 0.201396E+09 | 98266319.53 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643410E+09 | 0.00 | 0.643410E+09 | 24400405.70 | 0.394359E+10 |
February | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.181973E+09 | 0.320432E+10 |
March | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.607458E+09 | 0.298578E+10 |
April | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.129039E+10 | 0.233884E+10 |
May | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.216408E+10 | 0.195766E+10 |
June | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.244674E+10 | 0.145489E+10 |
July | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.272903E+10 | 0.135051E+10 |
August | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.224635E+10 | 0.132406E+10 |
September | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.123900E+10 | 0.193009E+10 |
October | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.499555E+09 | 0.268220E+10 |
November | 0.704943E+09 | 0.00 | 0.704943E+09 | 93476951.33 | 0.317285E+10 |
December | 0.546732E+09 | 0.00 | 0.546732E+09 | 10461928.26 | 0.401180E+10 |
Annual Sum or Average | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.135329E+11 | 0.303566E+11 |
Minimum of Months | 0.546732E+09 | 0.00 | 0.546732E+09 | 10461928.26 | 0.132406E+10 |
Maximum of Months | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.272903E+10 | 0.401180E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.245207E+09 | 0.249627E+10 |
February | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.736751E+09 | 0.202269E+10 |
March | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.154412E+10 | 0.191453E+10 |
April | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.283958E+10 | 0.150525E+10 |
May | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.328874E+10 | 0.131778E+10 |
June | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.411428E+10 | 0.995004E+09 |
July | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.413882E+10 | 0.905488E+09 |
August | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.421040E+10 | 0.884583E+09 |
September | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.266595E+10 | 0.124369E+10 |
October | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.146844E+10 | 0.172869E+10 |
November | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.401172E+09 | 0.204439E+10 |
December | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.305207E+09 | 0.256862E+10 |
Annual Sum or Average | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.259587E+11 | 0.196270E+11 |
Minimum of Months | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.245207E+09 | 0.884583E+09 |
Maximum of Months | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.421040E+10 | 0.256862E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.252293E+10 | 0.358428E+10 |
February | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.400013E+10 | 0.298244E+10 |
March | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.497579E+10 | 0.295768E+10 |
April | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.537932E+10 | 0.244867E+10 |
May | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.513539E+10 | 0.212110E+10 |
June | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.465163E+10 | 0.161838E+10 |
July | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.580026E+10 | 0.150824E+10 |
August | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.644668E+10 | 0.145757E+10 |
September | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.647211E+10 | 0.196912E+10 |
October | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.551851E+10 | 0.265054E+10 |
November | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.264574E+10 | 0.300448E+10 |
December | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.295067E+10 | 0.373864E+10 |
Annual Sum or Average | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.564992E+11 | 0.300411E+11 |
Minimum of Months | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.252293E+10 | 0.145757E+10 |
Maximum of Months | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.647211E+10 | 0.373864E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.313300E+09 | 0.251751E+10 |
February | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.828316E+09 | 0.205016E+10 |
March | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.151916E+10 | 0.195696E+10 |
April | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.269500E+10 | 0.158670E+10 |
May | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.393409E+10 | 0.138593E+10 |
June | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.375129E+10 | 0.105349E+10 |
July | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.526097E+10 | 0.995340E+09 |
August | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.441536E+10 | 0.969490E+09 |
September | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.318907E+10 | 0.131513E+10 |
October | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.148851E+10 | 0.178073E+10 |
November | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.429151E+09 | 0.205112E+10 |
December | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.369633E+09 | 0.259355E+10 |
Annual Sum or Average | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.281938E+11 | 0.202561E+11 |
Minimum of Months | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.313300E+09 | 0.969490E+09 |
Maximum of Months | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.526097E+10 | 0.259355E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.31 | 1399.70 | 240.22 | 0.00 | 240.22 | 0.00 | 0.00 |
February | 83.50 | 1247.66 | 373.79 | 0.00 | 373.79 | 0.00 | 0.00 |
March | 241.63 | 1047.08 | 550.72 | 0.00 | 550.72 | 0.00 | 0.00 |
April | 510.94 | 856.35 | 779.33 | 2.76 | 776.56 | 0.00 | 0.00 |
May | 816.01 | 701.03 | 1002.80 | 29.79 | 973.01 | 0.00 | 0.00 |
June | 947.10 | 542.99 | 1054.42 | 69.63 | 984.79 | 0.00 | 0.00 |
July | 1019.37 | 488.65 | 1002.17 | 78.57 | 923.59 | 0.00 | 0.00 |
August | 841.31 | 476.71 | 811.26 | 21.93 | 789.33 | 0.00 | 0.00 |
September | 486.83 | 706.45 | 630.16 | 0.19 | 629.97 | 0.00 | 0.00 |
October | 202.66 | 929.81 | 431.76 | 0.00 | 431.76 | 0.00 | 0.00 |
November | 43.87 | 1136.68 | 271.97 | 0.00 | 271.97 | 0.00 | 0.00 |
December | 6.08 | 1409.03 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Annual Sum or Average | 436.41 | 910.20 | 613.91 | 17.03 | 596.88 | 0.00 | 0.00 |
Minimum of Months | 6.08 | 476.71 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Maximum of Months | 1019.37 | 1409.03 | 1054.42 | 78.57 | 984.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 96.39 | 886.36 | 257.34 | 65.24 | 192.09 | 0.00 | 0.00 |
February | 316.98 | 788.20 | 472.19 | 167.59 | 304.60 | 0.00 | 0.00 |
March | 590.89 | 672.35 | 705.01 | 255.22 | 449.79 | 0.00 | 0.00 |
April | 1107.26 | 553.76 | 1092.89 | 454.11 | 638.78 | 0.00 | 0.00 |
May | 1234.99 | 473.24 | 1162.93 | 404.32 | 758.61 | 0.00 | 0.00 |
June | 1590.62 | 372.11 | 1392.74 | 605.99 | 786.75 | 0.00 | 0.00 |
July | 1548.24 | 328.59 | 1296.96 | 582.15 | 714.81 | 0.00 | 0.00 |
August | 1575.60 | 319.56 | 1274.74 | 637.70 | 637.04 | 0.00 | 0.00 |
September | 1036.99 | 456.92 | 942.48 | 434.68 | 507.80 | 0.00 | 0.00 |
October | 562.66 | 601.51 | 614.31 | 261.02 | 353.28 | 0.00 | 0.00 |
November | 165.05 | 731.95 | 301.10 | 85.00 | 216.10 | 0.00 | 0.00 |
December | 120.36 | 902.10 | 246.97 | 79.51 | 167.46 | 0.00 | 0.00 |
Annual Sum or Average | 831.44 | 589.61 | 814.80 | 336.78 | 478.02 | 0.00 | 0.00 |
Minimum of Months | 96.39 | 319.56 | 246.97 | 65.24 | 167.46 | 0.00 | 0.00 |
Maximum of Months | 1590.62 | 902.10 | 1392.74 | 637.70 | 786.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 955.01 | 1272.15 | 1061.37 | 630.25 | 431.13 | 0.00 | 0.00 |
February | 1671.67 | 1164.90 | 1632.23 | 1010.37 | 621.86 | 0.00 | 0.00 |
March | 1871.33 | 1040.82 | 1755.81 | 936.35 | 819.45 | 0.00 | 0.00 |
April | 2084.44 | 900.72 | 1853.80 | 804.91 | 1048.89 | 0.00 | 0.00 |
May | 1920.69 | 760.24 | 1695.06 | 504.98 | 1190.09 | 0.00 | 0.00 |
June | 1793.58 | 603.29 | 1550.82 | 416.37 | 1134.44 | 0.00 | 0.00 |
July | 2162.88 | 545.74 | 1691.23 | 619.42 | 1071.81 | 0.00 | 0.00 |
August | 2405.44 | 525.33 | 1817.02 | 847.31 | 969.71 | 0.00 | 0.00 |
September | 2503.18 | 724.54 | 2013.18 | 1111.74 | 901.44 | 0.00 | 0.00 |
October | 2075.41 | 925.97 | 1823.60 | 1125.94 | 697.66 | 0.00 | 0.00 |
November | 1038.56 | 1080.61 | 1078.17 | 617.88 | 460.29 | 0.00 | 0.00 |
December | 1115.62 | 1315.18 | 1128.08 | 730.02 | 398.05 | 0.00 | 0.00 |
Annual Sum or Average | 1800.27 | 903.67 | 1591.01 | 778.19 | 812.82 | 0.00 | 0.00 |
Minimum of Months | 955.01 | 525.33 | 1061.37 | 416.37 | 398.05 | 0.00 | 0.00 |
Maximum of Months | 2503.18 | 1315.18 | 2013.18 | 1125.94 | 1190.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 120.38 | 893.61 | 271.43 | 80.04 | 191.39 | 0.00 | 0.00 |
February | 350.11 | 799.09 | 486.65 | 182.90 | 303.75 | 0.00 | 0.00 |
March | 576.74 | 686.89 | 681.92 | 230.17 | 451.75 | 0.00 | 0.00 |
April | 1047.09 | 582.09 | 1037.47 | 396.66 | 640.80 | 0.00 | 0.00 |
May | 1471.18 | 496.20 | 1334.98 | 542.33 | 792.65 | 0.00 | 0.00 |
June | 1446.21 | 392.37 | 1283.89 | 498.49 | 785.40 | 0.00 | 0.00 |
July | 1961.54 | 359.75 | 1586.07 | 833.72 | 752.35 | 0.00 | 0.00 |
August | 1647.56 | 349.28 | 1312.06 | 669.97 | 642.08 | 0.00 | 0.00 |
September | 1234.57 | 483.02 | 1068.47 | 512.67 | 555.79 | 0.00 | 0.00 |
October | 566.03 | 618.85 | 608.28 | 247.85 | 360.44 | 0.00 | 0.00 |
November | 173.13 | 735.78 | 302.92 | 85.44 | 217.48 | 0.00 | 0.00 |
December | 141.83 | 911.54 | 254.66 | 87.27 | 167.40 | 0.00 | 0.00 |
Annual Sum or Average | 898.29 | 608.14 | 854.63 | 365.34 | 489.29 | 0.00 | 0.00 |
Minimum of Months | 120.38 | 349.28 | 254.66 | 80.04 | 167.40 | 0.00 | 0.00 |
Maximum of Months | 1961.54 | 911.54 | 1586.07 | 833.72 | 792.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.86 | 1445.91 | 240.22 | 0.00 | 240.22 | 0.00 | 0.00 |
February | 84.93 | 1285.00 | 373.78 | 0.00 | 373.78 | 0.00 | 0.00 |
March | 254.17 | 1054.89 | 550.71 | 0.00 | 550.71 | 0.00 | 0.00 |
April | 537.71 | 847.08 | 779.31 | 2.76 | 776.55 | 0.00 | 0.00 |
May | 845.05 | 696.35 | 1002.78 | 29.79 | 972.99 | 0.00 | 0.00 |
June | 973.24 | 539.29 | 1054.40 | 69.63 | 984.77 | 0.00 | 0.00 |
July | 1041.25 | 486.99 | 1002.15 | 78.57 | 923.57 | 0.00 | 0.00 |
August | 856.26 | 478.99 | 811.25 | 21.93 | 789.32 | 0.00 | 0.00 |
September | 492.89 | 726.76 | 630.15 | 0.19 | 629.96 | 0.00 | 0.00 |
October | 195.24 | 989.07 | 431.75 | 0.00 | 431.75 | 0.00 | 0.00 |
November | 38.14 | 1224.74 | 271.96 | 0.00 | 271.96 | 0.00 | 0.00 |
December | 4.48 | 1487.78 | 204.12 | 0.00 | 204.12 | 0.00 | 0.00 |
Annual Sum or Average | 446.75 | 936.86 | 613.90 | 17.03 | 596.87 | 0.00 | 0.00 |
Minimum of Months | 4.48 | 478.99 | 204.12 | 0.00 | 204.12 | 0.00 | 0.00 |
Maximum of Months | 1041.25 | 1487.78 | 1054.40 | 78.57 | 984.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 95.37 | 915.67 | 257.33 | 65.24 | 192.09 | 0.00 | 0.00 |
February | 317.59 | 815.32 | 472.18 | 167.59 | 304.59 | 0.00 | 0.00 |
March | 599.31 | 688.14 | 705.00 | 255.22 | 449.79 | 0.00 | 0.00 |
April | 1119.95 | 564.75 | 1092.87 | 454.10 | 638.77 | 0.00 | 0.00 |
May | 1250.18 | 480.49 | 1162.91 | 404.32 | 758.60 | 0.00 | 0.00 |
June | 1605.45 | 380.87 | 1392.72 | 605.98 | 786.74 | 0.00 | 0.00 |
July | 1561.21 | 335.36 | 1296.95 | 582.14 | 714.80 | 0.00 | 0.00 |
August | 1584.78 | 331.07 | 1274.72 | 637.68 | 637.03 | 0.00 | 0.00 |
September | 1039.68 | 479.76 | 942.47 | 434.67 | 507.79 | 0.00 | 0.00 |
October | 556.68 | 649.19 | 614.30 | 261.02 | 353.28 | 0.00 | 0.00 |
November | 158.54 | 790.85 | 301.09 | 85.00 | 216.09 | 0.00 | 0.00 |
December | 116.68 | 953.12 | 246.97 | 79.51 | 167.46 | 0.00 | 0.00 |
Annual Sum or Average | 836.41 | 614.41 | 814.79 | 336.78 | 478.01 | 0.00 | 0.00 |
Minimum of Months | 95.37 | 331.07 | 246.97 | 65.24 | 167.46 | 0.00 | 0.00 |
Maximum of Months | 1605.45 | 953.12 | 1392.72 | 637.68 | 786.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 968.78 | 1305.24 | 1061.33 | 630.22 | 431.11 | 0.00 | 0.00 |
February | 1691.31 | 1211.78 | 1632.17 | 1010.33 | 621.84 | 0.00 | 0.00 |
March | 1904.07 | 1068.05 | 1755.74 | 936.31 | 819.43 | 0.00 | 0.00 |
April | 2125.84 | 906.27 | 1853.73 | 804.88 | 1048.86 | 0.00 | 0.00 |
May | 1964.62 | 758.69 | 1695.00 | 504.96 | 1190.05 | 0.00 | 0.00 |
June | 1834.34 | 601.10 | 1550.77 | 416.36 | 1134.41 | 0.00 | 0.00 |
July | 2192.42 | 553.64 | 1691.18 | 619.39 | 1071.78 | 0.00 | 0.00 |
August | 2428.12 | 542.78 | 1816.95 | 847.27 | 969.68 | 0.00 | 0.00 |
September | 2517.41 | 765.65 | 2013.11 | 1111.70 | 901.41 | 0.00 | 0.00 |
October | 2082.01 | 1001.92 | 1823.53 | 1125.89 | 697.64 | 0.00 | 0.00 |
November | 1041.30 | 1153.61 | 1078.13 | 617.86 | 460.27 | 0.00 | 0.00 |
December | 1120.79 | 1377.74 | 1128.03 | 729.99 | 398.04 | 0.00 | 0.00 |
Annual Sum or Average | 1823.04 | 935.83 | 1590.95 | 778.16 | 812.79 | 0.00 | 0.00 |
Minimum of Months | 968.78 | 542.78 | 1061.33 | 416.36 | 398.04 | 0.00 | 0.00 |
Maximum of Months | 2517.41 | 1377.74 | 2013.11 | 1125.89 | 1190.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 121.99 | 924.69 | 271.42 | 80.04 | 191.39 | 0.00 | 0.00 |
February | 354.98 | 829.59 | 486.64 | 182.89 | 303.75 | 0.00 | 0.00 |
March | 587.36 | 705.49 | 681.91 | 230.16 | 451.75 | 0.00 | 0.00 |
April | 1064.83 | 592.49 | 1037.45 | 396.66 | 640.80 | 0.00 | 0.00 |
May | 1489.28 | 510.39 | 1334.96 | 542.32 | 792.64 | 0.00 | 0.00 |
June | 1464.52 | 401.91 | 1283.87 | 498.48 | 785.39 | 0.00 | 0.00 |
July | 1976.93 | 375.17 | 1586.04 | 833.70 | 752.34 | 0.00 | 0.00 |
August | 1658.99 | 364.94 | 1312.04 | 669.96 | 642.08 | 0.00 | 0.00 |
September | 1238.56 | 512.29 | 1068.45 | 512.67 | 555.79 | 0.00 | 0.00 |
October | 561.93 | 669.78 | 608.27 | 247.84 | 360.43 | 0.00 | 0.00 |
November | 168.48 | 796.28 | 302.92 | 85.43 | 217.48 | 0.00 | 0.00 |
December | 141.11 | 964.59 | 254.66 | 87.27 | 167.39 | 0.00 | 0.00 |
Annual Sum or Average | 906.02 | 636.39 | 854.62 | 365.34 | 489.28 | 0.00 | 0.00 |
Minimum of Months | 121.99 | 364.94 | 254.66 | 80.04 | 167.39 | 0.00 | 0.00 |
Maximum of Months | 1976.93 | 964.59 | 1586.04 | 833.70 | 792.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.11 | 1472.37 | 240.22 | 0.00 | 240.22 | 0.00 | 0.00 |
February | 75.22 | 1324.54 | 373.79 | 0.00 | 373.79 | 0.00 | 0.00 |
March | 226.80 | 1114.76 | 550.72 | 0.00 | 550.72 | 0.00 | 0.00 |
April | 497.83 | 902.33 | 779.33 | 2.76 | 776.56 | 0.00 | 0.00 |
May | 807.97 | 730.91 | 1002.80 | 29.79 | 973.01 | 0.00 | 0.00 |
June | 943.96 | 561.30 | 1054.42 | 69.63 | 984.79 | 0.00 | 0.00 |
July | 1018.90 | 504.22 | 1002.17 | 78.57 | 923.59 | 0.00 | 0.00 |
August | 838.69 | 494.35 | 811.26 | 21.93 | 789.33 | 0.00 | 0.00 |
September | 478.01 | 744.63 | 630.16 | 0.19 | 629.97 | 0.00 | 0.00 |
October | 186.51 | 1001.42 | 431.76 | 0.00 | 431.76 | 0.00 | 0.00 |
November | 36.06 | 1224.09 | 271.97 | 0.00 | 271.97 | 0.00 | 0.00 |
December | 3.91 | 1497.83 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Annual Sum or Average | 429.13 | 962.60 | 613.91 | 17.03 | 596.88 | 0.00 | 0.00 |
Minimum of Months | 3.91 | 494.35 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Maximum of Months | 1018.90 | 1497.83 | 1054.42 | 78.57 | 984.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 91.55 | 932.00 | 257.34 | 65.24 | 192.09 | 0.00 | 0.00 |
February | 304.54 | 836.10 | 472.19 | 167.59 | 304.60 | 0.00 | 0.00 |
March | 576.51 | 714.80 | 705.01 | 255.22 | 449.79 | 0.00 | 0.00 |
April | 1095.52 | 580.73 | 1092.89 | 454.11 | 638.78 | 0.00 | 0.00 |
May | 1227.87 | 492.00 | 1162.93 | 404.32 | 758.61 | 0.00 | 0.00 |
June | 1587.30 | 383.87 | 1392.74 | 605.99 | 786.75 | 0.00 | 0.00 |
July | 1545.26 | 338.07 | 1296.96 | 582.15 | 714.81 | 0.00 | 0.00 |
August | 1571.98 | 330.27 | 1274.74 | 637.70 | 637.04 | 0.00 | 0.00 |
September | 1028.53 | 479.82 | 942.48 | 434.68 | 507.80 | 0.00 | 0.00 |
October | 548.25 | 645.42 | 614.31 | 261.02 | 353.28 | 0.00 | 0.00 |
November | 154.77 | 788.73 | 301.10 | 85.00 | 216.10 | 0.00 | 0.00 |
December | 113.95 | 959.01 | 246.97 | 79.51 | 167.46 | 0.00 | 0.00 |
Annual Sum or Average | 823.14 | 622.37 | 814.80 | 336.78 | 478.02 | 0.00 | 0.00 |
Minimum of Months | 91.55 | 330.27 | 246.97 | 65.24 | 167.46 | 0.00 | 0.00 |
Maximum of Months | 1587.30 | 959.01 | 1392.74 | 637.70 | 786.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 941.95 | 1338.22 | 1061.37 | 630.25 | 431.13 | 0.00 | 0.00 |
February | 1653.49 | 1232.82 | 1632.23 | 1010.37 | 621.86 | 0.00 | 0.00 |
March | 1857.75 | 1104.27 | 1755.81 | 936.35 | 819.45 | 0.00 | 0.00 |
April | 2075.35 | 944.70 | 1853.80 | 804.91 | 1048.89 | 0.00 | 0.00 |
May | 1917.34 | 791.93 | 1695.06 | 504.98 | 1190.09 | 0.00 | 0.00 |
June | 1794.61 | 624.37 | 1550.82 | 416.37 | 1134.44 | 0.00 | 0.00 |
July | 2165.57 | 563.11 | 1691.23 | 619.42 | 1071.81 | 0.00 | 0.00 |
August | 2406.91 | 544.19 | 1817.02 | 847.31 | 969.71 | 0.00 | 0.00 |
September | 2496.96 | 759.69 | 2013.18 | 1111.74 | 901.44 | 0.00 | 0.00 |
October | 2060.38 | 989.60 | 1823.60 | 1125.94 | 697.66 | 0.00 | 0.00 |
November | 1020.73 | 1159.14 | 1078.17 | 617.88 | 460.29 | 0.00 | 0.00 |
December | 1101.65 | 1395.85 | 1128.08 | 730.02 | 398.05 | 0.00 | 0.00 |
Annual Sum or Average | 1791.58 | 952.60 | 1591.01 | 778.19 | 812.82 | 0.00 | 0.00 |
Minimum of Months | 941.95 | 544.19 | 1061.37 | 416.37 | 398.05 | 0.00 | 0.00 |
Maximum of Months | 2496.96 | 1395.85 | 2013.18 | 1125.94 | 1190.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 116.97 | 939.93 | 271.43 | 80.04 | 191.39 | 0.00 | 0.00 |
February | 342.39 | 847.45 | 486.65 | 182.90 | 303.75 | 0.00 | 0.00 |
March | 567.19 | 730.64 | 681.92 | 230.17 | 451.75 | 0.00 | 0.00 |
April | 1039.74 | 612.15 | 1037.47 | 396.66 | 640.80 | 0.00 | 0.00 |
May | 1468.82 | 517.45 | 1334.98 | 542.33 | 792.65 | 0.00 | 0.00 |
June | 1447.26 | 406.44 | 1283.89 | 498.49 | 785.40 | 0.00 | 0.00 |
July | 1964.22 | 371.62 | 1586.07 | 833.72 | 752.35 | 0.00 | 0.00 |
August | 1648.51 | 361.97 | 1312.06 | 669.97 | 642.08 | 0.00 | 0.00 |
September | 1230.35 | 507.38 | 1068.47 | 512.67 | 555.79 | 0.00 | 0.00 |
October | 555.75 | 664.85 | 608.28 | 247.85 | 360.44 | 0.00 | 0.00 |
November | 165.57 | 791.33 | 302.92 | 85.44 | 217.48 | 0.00 | 0.00 |
December | 138.01 | 968.32 | 254.66 | 87.27 | 167.40 | 0.00 | 0.00 |
Annual Sum or Average | 894.02 | 642.32 | 854.63 | 365.34 | 489.29 | 0.00 | 0.00 |
Minimum of Months | 116.97 | 361.97 | 254.66 | 80.04 | 167.40 | 0.00 | 0.00 |
Maximum of Months | 1964.22 | 968.32 | 1586.07 | 833.72 | 792.65 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 30291330.25 | 0.374895E+10 | 0.643410E+09 | 0.00 | 0.643410E+09 | 0.00 | 0.00 |
February | 0.202010E+09 | 0.301835E+10 | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.00 | 0.00 |
March | 0.647189E+09 | 0.280451E+10 | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.00 | 0.00 |
April | 0.132436E+10 | 0.221966E+10 | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.00 | 0.00 |
May | 0.218561E+10 | 0.187765E+10 | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.00 | 0.00 |
June | 0.245489E+10 | 0.140743E+10 | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.00 | 0.00 |
July | 0.273029E+10 | 0.130881E+10 | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.00 | 0.00 |
August | 0.225337E+10 | 0.127681E+10 | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.00 | 0.00 |
September | 0.126187E+10 | 0.183112E+10 | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.00 | 0.00 |
October | 0.542805E+09 | 0.249042E+10 | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.00 | 0.00 |
November | 0.113711E+09 | 0.294628E+10 | 0.704943E+09 | 0.00 | 0.704943E+09 | 0.00 | 0.00 |
December | 16290821.70 | 0.377395E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.137627E+11 | 0.287039E+11 | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.00 | 0.00 |
Minimum of Months | 16290821.70 | 0.127681E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Maximum of Months | 0.273029E+10 | 0.377395E+10 | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.258184E+09 | 0.237403E+10 | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.00 | 0.00 |
February | 0.766827E+09 | 0.190681E+10 | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.00 | 0.00 |
March | 0.158265E+10 | 0.180081E+10 | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.00 | 0.00 |
April | 0.287001E+10 | 0.143534E+10 | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.00 | 0.00 |
May | 0.330780E+10 | 0.126752E+10 | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.00 | 0.00 |
June | 0.412288E+10 | 0.964504E+09 | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.00 | 0.00 |
July | 0.414680E+10 | 0.880102E+09 | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.00 | 0.00 |
August | 0.422008E+10 | 0.855898E+09 | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.00 | 0.00 |
September | 0.268787E+10 | 0.118434E+10 | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.00 | 0.00 |
October | 0.150702E+10 | 0.161109E+10 | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.00 | 0.00 |
November | 0.427822E+09 | 0.189721E+10 | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.00 | 0.00 |
December | 0.322361E+09 | 0.241618E+10 | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.262203E+11 | 0.185938E+11 | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.258184E+09 | 0.855898E+09 | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.00 | 0.00 |
Maximum of Months | 0.422008E+10 | 0.241618E+10 | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.255789E+10 | 0.340732E+10 | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.00 | 0.00 |
February | 0.404410E+10 | 0.281814E+10 | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.00 | 0.00 |
March | 0.501218E+10 | 0.278773E+10 | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.00 | 0.00 |
April | 0.540287E+10 | 0.233467E+10 | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.00 | 0.00 |
May | 0.514438E+10 | 0.203624E+10 | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.00 | 0.00 |
June | 0.464895E+10 | 0.156372E+10 | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.00 | 0.00 |
July | 0.579306E+10 | 0.146171E+10 | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.00 | 0.00 |
August | 0.644273E+10 | 0.140705E+10 | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.00 | 0.00 |
September | 0.648823E+10 | 0.187802E+10 | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.00 | 0.00 |
October | 0.555879E+10 | 0.248013E+10 | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.00 | 0.00 |
November | 0.269195E+10 | 0.280094E+10 | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.00 | 0.00 |
December | 0.298807E+10 | 0.352259E+10 | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.567732E+11 | 0.284983E+11 | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.00 | 0.00 |
Minimum of Months | 0.255789E+10 | 0.140705E+10 | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.00 | 0.00 |
Maximum of Months | 0.648823E+10 | 0.352259E+10 | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.322420E+09 | 0.239344E+10 | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.00 | 0.00 |
February | 0.846989E+09 | 0.193316E+10 | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.00 | 0.00 |
March | 0.154474E+10 | 0.183978E+10 | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.00 | 0.00 |
April | 0.271406E+10 | 0.150877E+10 | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.00 | 0.00 |
May | 0.394042E+10 | 0.132903E+10 | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.00 | 0.00 |
June | 0.374857E+10 | 0.101703E+10 | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.00 | 0.00 |
July | 0.525379E+10 | 0.963547E+09 | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.00 | 0.00 |
August | 0.441283E+10 | 0.935499E+09 | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.00 | 0.00 |
September | 0.320002E+10 | 0.125199E+10 | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.00 | 0.00 |
October | 0.151606E+10 | 0.165752E+10 | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.00 | 0.00 |
November | 0.448751E+09 | 0.190714E+10 | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.00 | 0.00 |
December | 0.379871E+09 | 0.244146E+10 | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.283285E+11 | 0.191784E+11 | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.322420E+09 | 0.935499E+09 | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.00 | 0.00 |
Maximum of Months | 0.525379E+10 | 0.244146E+10 | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 29088420.43 | 0.387272E+10 | 0.643395E+09 | 0.00 | 0.643395E+09 | 0.00 | 0.00 |
February | 0.205462E+09 | 0.310866E+10 | 0.904256E+09 | 0.00 | 0.904256E+09 | 0.00 | 0.00 |
March | 0.680764E+09 | 0.282541E+10 | 0.147502E+10 | 0.00 | 0.147502E+10 | 0.00 | 0.00 |
April | 0.139375E+10 | 0.219562E+10 | 0.201998E+10 | 7165414.18 | 0.201281E+10 | 0.00 | 0.00 |
May | 0.226338E+10 | 0.186511E+10 | 0.268584E+10 | 79791812.30 | 0.260605E+10 | 0.00 | 0.00 |
June | 0.252263E+10 | 0.139784E+10 | 0.273300E+10 | 0.180474E+09 | 0.255252E+10 | 0.00 | 0.00 |
July | 0.278889E+10 | 0.130436E+10 | 0.268415E+10 | 0.210448E+09 | 0.247370E+10 | 0.00 | 0.00 |
August | 0.229341E+10 | 0.128293E+10 | 0.217284E+10 | 58737854.82 | 0.211410E+10 | 0.00 | 0.00 |
September | 0.127758E+10 | 0.188377E+10 | 0.163334E+10 | 481642.78 | 0.163286E+10 | 0.00 | 0.00 |
October | 0.522930E+09 | 0.264912E+10 | 0.115641E+10 | 0.00 | 0.115641E+10 | 0.00 | 0.00 |
November | 98853947.59 | 0.317452E+10 | 0.704927E+09 | 0.00 | 0.704927E+09 | 0.00 | 0.00 |
December | 12004129.22 | 0.398486E+10 | 0.546720E+09 | 0.00 | 0.546720E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.140887E+11 | 0.295449E+11 | 0.193599E+11 | 0.537099E+09 | 0.188228E+11 | 0.00 | 0.00 |
Minimum of Months | 12004129.22 | 0.128293E+10 | 0.546720E+09 | 0.00 | 0.546720E+09 | 0.00 | 0.00 |
Maximum of Months | 0.278889E+10 | 0.398486E+10 | 0.273300E+10 | 0.210448E+09 | 0.260605E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.255429E+09 | 0.245253E+10 | 0.689242E+09 | 0.174745E+09 | 0.514497E+09 | 0.00 | 0.00 |
February | 0.768306E+09 | 0.197243E+10 | 0.114230E+10 | 0.405425E+09 | 0.736876E+09 | 0.00 | 0.00 |
March | 0.160519E+10 | 0.184312E+10 | 0.188827E+10 | 0.683568E+09 | 0.120470E+10 | 0.00 | 0.00 |
April | 0.290292E+10 | 0.146383E+10 | 0.283272E+10 | 0.117703E+10 | 0.165569E+10 | 0.00 | 0.00 |
May | 0.334848E+10 | 0.128693E+10 | 0.311475E+10 | 0.108292E+10 | 0.203182E+10 | 0.00 | 0.00 |
June | 0.416133E+10 | 0.987206E+09 | 0.360993E+10 | 0.157070E+10 | 0.203923E+10 | 0.00 | 0.00 |
July | 0.418154E+10 | 0.898218E+09 | 0.347374E+10 | 0.155921E+10 | 0.191453E+10 | 0.00 | 0.00 |
August | 0.424466E+10 | 0.886726E+09 | 0.341420E+10 | 0.170797E+10 | 0.170623E+10 | 0.00 | 0.00 |
September | 0.269484E+10 | 0.124355E+10 | 0.244287E+10 | 0.112667E+10 | 0.131620E+10 | 0.00 | 0.00 |
October | 0.149101E+10 | 0.173879E+10 | 0.164533E+10 | 0.699110E+09 | 0.946224E+09 | 0.00 | 0.00 |
November | 0.410937E+09 | 0.204989E+10 | 0.780437E+09 | 0.220324E+09 | 0.560113E+09 | 0.00 | 0.00 |
December | 0.312508E+09 | 0.255283E+10 | 0.661471E+09 | 0.212946E+09 | 0.448525E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.263772E+11 | 0.193761E+11 | 0.256953E+11 | 0.106206E+11 | 0.150746E+11 | 0.00 | 0.00 |
Minimum of Months | 0.255429E+09 | 0.886726E+09 | 0.661471E+09 | 0.174745E+09 | 0.448525E+09 | 0.00 | 0.00 |
Maximum of Months | 0.424466E+10 | 0.255283E+10 | 0.360993E+10 | 0.170797E+10 | 0.203923E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.259477E+10 | 0.349594E+10 | 0.284267E+10 | 0.168799E+10 | 0.115468E+10 | 0.00 | 0.00 |
February | 0.409161E+10 | 0.293155E+10 | 0.394854E+10 | 0.244419E+10 | 0.150435E+10 | 0.00 | 0.00 |
March | 0.509986E+10 | 0.286067E+10 | 0.470258E+10 | 0.250782E+10 | 0.219475E+10 | 0.00 | 0.00 |
April | 0.551017E+10 | 0.234905E+10 | 0.480488E+10 | 0.208624E+10 | 0.271864E+10 | 0.00 | 0.00 |
May | 0.526203E+10 | 0.203207E+10 | 0.453990E+10 | 0.135247E+10 | 0.318743E+10 | 0.00 | 0.00 |
June | 0.475462E+10 | 0.155806E+10 | 0.401958E+10 | 0.107920E+10 | 0.294039E+10 | 0.00 | 0.00 |
July | 0.587217E+10 | 0.148286E+10 | 0.452965E+10 | 0.165899E+10 | 0.287066E+10 | 0.00 | 0.00 |
August | 0.650348E+10 | 0.145377E+10 | 0.486653E+10 | 0.226933E+10 | 0.259720E+10 | 0.00 | 0.00 |
September | 0.652512E+10 | 0.198456E+10 | 0.521797E+10 | 0.288152E+10 | 0.233645E+10 | 0.00 | 0.00 |
October | 0.557646E+10 | 0.268355E+10 | 0.488414E+10 | 0.301559E+10 | 0.186855E+10 | 0.00 | 0.00 |
November | 0.269906E+10 | 0.299016E+10 | 0.279452E+10 | 0.160149E+10 | 0.119303E+10 | 0.00 | 0.00 |
December | 0.300192E+10 | 0.369013E+10 | 0.302132E+10 | 0.195522E+10 | 0.106611E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.574913E+11 | 0.295124E+11 | 0.501723E+11 | 0.245400E+11 | 0.256322E+11 | 0.00 | 0.00 |
Minimum of Months | 0.259477E+10 | 0.145377E+10 | 0.279452E+10 | 0.107920E+10 | 0.106611E+10 | 0.00 | 0.00 |
Maximum of Months | 0.652512E+10 | 0.369013E+10 | 0.521797E+10 | 0.301559E+10 | 0.318743E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.326734E+09 | 0.247670E+10 | 0.726984E+09 | 0.214374E+09 | 0.512610E+09 | 0.00 | 0.00 |
February | 0.858776E+09 | 0.200695E+10 | 0.117729E+10 | 0.442456E+09 | 0.734831E+09 | 0.00 | 0.00 |
March | 0.157319E+10 | 0.188957E+10 | 0.182643E+10 | 0.616467E+09 | 0.120996E+10 | 0.00 | 0.00 |
April | 0.276005E+10 | 0.153573E+10 | 0.268908E+10 | 0.102814E+10 | 0.166095E+10 | 0.00 | 0.00 |
May | 0.398887E+10 | 0.136702E+10 | 0.357557E+10 | 0.145255E+10 | 0.212301E+10 | 0.00 | 0.00 |
June | 0.379604E+10 | 0.104174E+10 | 0.332779E+10 | 0.129206E+10 | 0.203572E+10 | 0.00 | 0.00 |
July | 0.529501E+10 | 0.100485E+10 | 0.424806E+10 | 0.223299E+10 | 0.201507E+10 | 0.00 | 0.00 |
August | 0.444345E+10 | 0.977452E+09 | 0.351416E+10 | 0.179443E+10 | 0.171974E+10 | 0.00 | 0.00 |
September | 0.321034E+10 | 0.132785E+10 | 0.276943E+10 | 0.132883E+10 | 0.144060E+10 | 0.00 | 0.00 |
October | 0.150507E+10 | 0.179395E+10 | 0.162920E+10 | 0.663820E+09 | 0.965383E+09 | 0.00 | 0.00 |
November | 0.436712E+09 | 0.206396E+10 | 0.785161E+09 | 0.221447E+09 | 0.563714E+09 | 0.00 | 0.00 |
December | 0.377959E+09 | 0.258356E+10 | 0.682082E+09 | 0.233732E+09 | 0.448351E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.285722E+11 | 0.200693E+11 | 0.269512E+11 | 0.115213E+11 | 0.154299E+11 | 0.00 | 0.00 |
Minimum of Months | 0.326734E+09 | 0.977452E+09 | 0.682082E+09 | 0.214374E+09 | 0.448351E+09 | 0.00 | 0.00 |
Maximum of Months | 0.529501E+10 | 0.258356E+10 | 0.424806E+10 | 0.223299E+10 | 0.212301E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 24400405.70 | 0.394359E+10 | 0.643410E+09 | 0.00 | 0.643410E+09 | 0.00 | 0.00 |
February | 0.181973E+09 | 0.320432E+10 | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.00 | 0.00 |
March | 0.607458E+09 | 0.298578E+10 | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.00 | 0.00 |
April | 0.129039E+10 | 0.233884E+10 | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.00 | 0.00 |
May | 0.216408E+10 | 0.195766E+10 | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.00 | 0.00 |
June | 0.244674E+10 | 0.145489E+10 | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.00 | 0.00 |
July | 0.272903E+10 | 0.135051E+10 | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.00 | 0.00 |
August | 0.224635E+10 | 0.132406E+10 | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.00 | 0.00 |
September | 0.123900E+10 | 0.193009E+10 | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.00 | 0.00 |
October | 0.499555E+09 | 0.268220E+10 | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.00 | 0.00 |
November | 93476951.33 | 0.317285E+10 | 0.704943E+09 | 0.00 | 0.704943E+09 | 0.00 | 0.00 |
December | 10461928.26 | 0.401180E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135329E+11 | 0.303566E+11 | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.00 | 0.00 |
Minimum of Months | 10461928.26 | 0.132406E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Maximum of Months | 0.272903E+10 | 0.401180E+10 | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.245207E+09 | 0.249627E+10 | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.00 | 0.00 |
February | 0.736751E+09 | 0.202269E+10 | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.00 | 0.00 |
March | 0.154412E+10 | 0.191453E+10 | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.00 | 0.00 |
April | 0.283958E+10 | 0.150525E+10 | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.00 | 0.00 |
May | 0.328874E+10 | 0.131778E+10 | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.00 | 0.00 |
June | 0.411428E+10 | 0.995004E+09 | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.00 | 0.00 |
July | 0.413882E+10 | 0.905488E+09 | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.00 | 0.00 |
August | 0.421040E+10 | 0.884583E+09 | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.00 | 0.00 |
September | 0.266595E+10 | 0.124369E+10 | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.00 | 0.00 |
October | 0.146844E+10 | 0.172869E+10 | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.00 | 0.00 |
November | 0.401172E+09 | 0.204439E+10 | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.00 | 0.00 |
December | 0.305207E+09 | 0.256862E+10 | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.259587E+11 | 0.196270E+11 | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.245207E+09 | 0.884583E+09 | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.00 | 0.00 |
Maximum of Months | 0.421040E+10 | 0.256862E+10 | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.252293E+10 | 0.358428E+10 | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.00 | 0.00 |
February | 0.400013E+10 | 0.298244E+10 | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.00 | 0.00 |
March | 0.497579E+10 | 0.295768E+10 | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.00 | 0.00 |
April | 0.537932E+10 | 0.244867E+10 | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.00 | 0.00 |
May | 0.513539E+10 | 0.212110E+10 | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.00 | 0.00 |
June | 0.465163E+10 | 0.161838E+10 | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.00 | 0.00 |
July | 0.580026E+10 | 0.150824E+10 | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.00 | 0.00 |
August | 0.644668E+10 | 0.145757E+10 | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.00 | 0.00 |
September | 0.647211E+10 | 0.196912E+10 | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.00 | 0.00 |
October | 0.551851E+10 | 0.265054E+10 | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.00 | 0.00 |
November | 0.264574E+10 | 0.300448E+10 | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.00 | 0.00 |
December | 0.295067E+10 | 0.373864E+10 | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.564992E+11 | 0.300411E+11 | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.00 | 0.00 |
Minimum of Months | 0.252293E+10 | 0.145757E+10 | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.00 | 0.00 |
Maximum of Months | 0.647211E+10 | 0.373864E+10 | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.313300E+09 | 0.251751E+10 | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.00 | 0.00 |
February | 0.828316E+09 | 0.205016E+10 | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.00 | 0.00 |
March | 0.151916E+10 | 0.195696E+10 | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.00 | 0.00 |
April | 0.269500E+10 | 0.158670E+10 | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.00 | 0.00 |
May | 0.393409E+10 | 0.138593E+10 | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.00 | 0.00 |
June | 0.375129E+10 | 0.105349E+10 | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.00 | 0.00 |
July | 0.526097E+10 | 0.995340E+09 | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.00 | 0.00 |
August | 0.441536E+10 | 0.969490E+09 | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.00 | 0.00 |
September | 0.318907E+10 | 0.131513E+10 | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.00 | 0.00 |
October | 0.148851E+10 | 0.178073E+10 | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.00 | 0.00 |
November | 0.429151E+09 | 0.205112E+10 | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.00 | 0.00 |
December | 0.369633E+09 | 0.259355E+10 | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.281938E+11 | 0.202561E+11 | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.313300E+09 | 0.969490E+09 | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.00 | 0.00 |
Maximum of Months | 0.526097E+10 | 0.259355E+10 | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.483481E+10 | -0.458408E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -250724232.4 | 60.05 | 0.00 | 0.00 |
February | 0.441491E+10 | -0.419457E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -220342076.5 | 60.05 | 0.00 | 0.00 |
March | 0.514915E+10 | -0.491064E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -238508746.9 | 60.05 | 0.00 | 0.00 |
April | 0.452779E+10 | -0.429981E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -227977127.4 | 60.05 | 0.00 | 0.00 |
May | 0.467879E+10 | -0.444432E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234471379.9 | 60.05 | 0.00 | 0.00 |
June | 0.447891E+10 | -0.425257E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -226337064.9 | 60.05 | 0.00 | 0.00 |
July | 0.413045E+10 | -0.389744E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233006515.8 | 60.05 | 0.00 | 0.00 |
August | 0.450811E+10 | -0.427461E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233501175.1 | 60.05 | 0.00 | 0.00 |
September | 0.412515E+10 | -0.389919E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225960016.2 | 60.05 | 0.00 | 0.00 |
October | 0.438779E+10 | -0.415238E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -235410511.0 | 60.05 | 0.00 | 0.00 |
November | 0.447597E+10 | -0.424363E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -232337117.6 | 60.05 | 0.00 | 0.00 |
December | 0.459588E+10 | -0.435083E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -245047841.2 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.543077E+11 | -0.515041E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.280362E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.412515E+10 | -0.491064E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -250724232.4 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.514915E+10 | -0.389744E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -220342076.5 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.50 | 0.48 | 01-JAN-09:50 | 2744.45 | 32.28 | 222.33 | 218.83 | 2191.41 | 33.53 | 225.83 | 187.33 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:30 | 4676.02 | 33.24 | 243.17 | 243.33 | 2064.71 | 29.38 | 222.17 | 221.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7743.27 | 33.05 | 208.83 | 311.67 | 1686.13 | 21.83 | 155.83 | 267.00 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2183.74 | 18.64 | 2.83 | 344.33 | 1216.73 | 20.87 | 212.67 | 307.00 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 1995.02 | 18.53 | 4.83 | 384.83 | 1093.07 | 20.71 | 209.50 | 343.00 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 1742.44 | 18.10 | 0.00 | 393.83 | 1003.97 | 20.32 | 190.50 | 343.67 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1552.52 | 16.89 | 0.00 | 392.83 | 913.22 | 19.11 | 150.83 | 337.00 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 1846.74 | 17.94 | 2.67 | 372.67 | 1111.28 | 20.18 | 159.50 | 326.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2983.68 | 20.78 | 41.67 | 319.00 | 1478.49 | 21.66 | 186.50 | 287.50 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7195.48 | 34.58 | 220.50 | 284.67 | 1968.69 | 23.02 | 157.50 | 256.17 |
November | 242.67 | 0.50 | 0.48 | 01-NOV-08:09 | 3058.65 | 31.81 | 224.67 | 224.17 | 2456.87 | 33.15 | 229.50 | 193.17 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3686.25 | 35.42 | 149.50 | 206.83 | 3141.89 | 36.90 | 149.67 | 167.17 |
Annual Sum or Average | 3714.00 | 0.51 | 3101.84 | 23.95 | 1321.00 | 3697.00 | 1520.01 | 23.68 | 2250.00 | 3236.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1552.52 | 16.89 | 0.00 | 206.83 | 913.22 | 19.11 | 149.67 | 167.17 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7743.27 | 35.42 | 243.17 | 393.83 | 3141.89 | 36.90 | 229.50 | 343.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-09:50 | 911.09 | 18.95 | 61.50 | 198.67 | 567.91 | 21.21 | 75.67 | 128.67 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1469.22 | 19.69 | 68.33 | 226.67 | 787.99 | 21.90 | 79.83 | 178.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2659.52 | 22.08 | 79.00 | 302.00 | 1191.45 | 23.02 | 90.67 | 252.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2796.72 | 21.11 | 105.50 | 346.33 | 1584.43 | 23.20 | 103.83 | 306.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2887.52 | 21.03 | 132.50 | 390.83 | 1263.95 | 21.35 | 91.67 | 349.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 3031.04 | 20.26 | 89.00 | 402.67 | 1682.49 | 22.31 | 77.67 | 355.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2859.15 | 20.72 | 148.50 | 406.33 | 1302.06 | 21.66 | 101.67 | 370.17 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3343.46 | 22.20 | 116.33 | 377.50 | 1464.14 | 21.98 | 74.00 | 337.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2730.18 | 21.78 | 82.67 | 322.83 | 1531.78 | 23.01 | 77.67 | 284.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2444.16 | 21.98 | 83.00 | 270.50 | 1096.07 | 22.64 | 89.17 | 224.67 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1135.34 | 20.34 | 79.17 | 207.17 | 596.33 | 21.16 | 71.67 | 143.50 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:39 | 1069.58 | 21.49 | 56.33 | 182.00 | 582.30 | 22.14 | 57.00 | 104.17 |
Annual Sum or Average | 3714.00 | 0.51 | 2458.32 | 20.98 | 1101.83 | 3633.50 | 1218.50 | 22.12 | 990.50 | 3035.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 911.09 | 18.95 | 56.33 | 182.00 | 567.91 | 21.16 | 57.00 | 104.17 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3343.46 | 22.20 | 148.50 | 406.33 | 1682.49 | 23.20 | 103.83 | 370.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 02-JAN-10:00 | 490.08 | 14.23 | 0.00 | 176.83 | 269.03 | 16.43 | 0.00 | 45.33 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 620.74 | 15.47 | 0.00 | 213.83 | 353.27 | 17.73 | 0.00 | 126.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 834.48 | 17.01 | 0.00 | 297.33 | 497.24 | 19.27 | 4.00 | 214.67 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:10 | 980.20 | 17.76 | 0.00 | 347.83 | 570.78 | 19.89 | 31.83 | 300.33 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1222.56 | 20.01 | 40.00 | 399.33 | 700.78 | 22.06 | 162.17 | 366.67 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:19 | 1281.10 | 21.20 | 60.83 | 412.67 | 757.07 | 23.27 | 193.50 | 383.67 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1083.92 | 20.32 | 79.33 | 423.50 | 651.77 | 22.39 | 180.00 | 382.17 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 951.82 | 17.84 | 0.00 | 390.67 | 584.43 | 20.03 | 53.83 | 344.67 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 906.39 | 17.88 | 0.00 | 313.17 | 553.58 | 20.10 | 16.50 | 254.83 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:09 | 675.74 | 16.03 | 0.00 | 258.50 | 412.10 | 18.37 | 0.33 | 163.83 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-09:00 | 527.98 | 14.57 | 0.00 | 189.67 | 289.61 | 16.71 | 0.00 | 64.00 |
December | 160.33 | 0.57 | 0.48 | 01-DEC-10:09 | 456.51 | 14.21 | 0.00 | 151.17 | 269.27 | 16.68 | 0.00 | 35.50 |
Annual Sum or Average | 3714.00 | 0.52 | 904.42 | 17.80 | 180.17 | 3574.50 | 533.52 | 19.97 | 642.17 | 2682.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 456.51 | 14.21 | 0.00 | 151.17 | 269.03 | 16.43 | 0.00 | 35.50 | |
Maximum of Months | 471.00 | 0.57 | 0.48 | 1281.10 | 21.20 | 79.33 | 423.50 | 757.07 | 23.27 | 193.50 | 383.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-10:30 | 1020.26 | 18.86 | 65.17 | 199.50 | 560.81 | 21.16 | 68.33 | 136.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-09:20 | 1467.67 | 19.86 | 66.67 | 228.83 | 768.83 | 21.67 | 71.67 | 181.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2351.12 | 22.14 | 78.17 | 304.67 | 1270.38 | 23.10 | 93.67 | 251.17 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 2820.83 | 20.83 | 105.50 | 344.17 | 1239.75 | 20.75 | 59.67 | 305.83 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 2912.82 | 17.71 | 52.50 | 390.33 | 1579.16 | 18.62 | 11.67 | 354.67 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 2981.49 | 17.33 | 42.83 | 401.67 | 1352.65 | 18.42 | 1.17 | 361.00 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-06:10 | 3282.06 | 16.47 | 58.83 | 402.67 | 1444.99 | 17.24 | 4.67 | 360.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3109.00 | 19.27 | 75.83 | 380.00 | 1798.21 | 20.73 | 54.50 | 341.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3432.57 | 22.97 | 100.50 | 314.67 | 1944.62 | 23.91 | 95.67 | 270.67 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-08:20 | 2348.42 | 22.32 | 87.33 | 272.00 | 1070.48 | 23.22 | 84.83 | 224.33 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:50 | 1090.60 | 18.82 | 63.33 | 208.50 | 583.82 | 20.51 | 59.83 | 140.17 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:00 | 1090.76 | 20.31 | 48.67 | 182.00 | 585.68 | 21.07 | 49.83 | 100.67 |
Annual Sum or Average | 3714.00 | 0.51 | 2524.17 | 19.42 | 845.33 | 3629.00 | 1271.95 | 20.49 | 655.50 | 3028.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1020.26 | 16.47 | 42.83 | 182.00 | 560.81 | 17.24 | 1.17 | 100.67 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3432.57 | 22.97 | 105.50 | 402.67 | 1944.62 | 23.91 | 95.67 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.51 | 0.48 | 01-JAN-09:50 | 2628.31 | 30.49 | 207.17 | 216.17 | 2123.85 | 33.20 | 222.50 | 182.50 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:39 | 4546.28 | 32.09 | 231.50 | 240.50 | 1973.39 | 27.94 | 157.17 | 219.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7587.42 | 32.25 | 207.67 | 309.83 | 1574.26 | 18.97 | 12.33 | 263.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2076.41 | 14.68 | 0.00 | 342.83 | 1140.44 | 18.19 | 10.50 | 302.67 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 1906.79 | 14.64 | 0.00 | 382.67 | 1033.46 | 18.09 | 3.33 | 339.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 1665.73 | 14.46 | 0.00 | 392.00 | 952.27 | 17.92 | 0.00 | 340.00 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1481.39 | 13.10 | 0.00 | 389.33 | 863.25 | 16.60 | 1.00 | 331.67 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 1751.18 | 14.23 | 0.00 | 369.33 | 1040.53 | 17.80 | 5.67 | 322.17 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2846.76 | 17.24 | 27.00 | 317.83 | 1375.12 | 19.08 | 29.67 | 282.67 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7032.68 | 33.75 | 218.00 | 282.33 | 1850.18 | 20.32 | 28.33 | 254.50 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:09 | 2948.99 | 30.64 | 215.33 | 222.17 | 2389.04 | 32.83 | 227.00 | 189.67 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3551.89 | 34.93 | 149.17 | 204.83 | 3041.51 | 36.50 | 149.67 | 161.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2992.81 | 21.19 | 1255.83 | 3669.83 | 1443.68 | 21.56 | 847.17 | 3189.17 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1481.39 | 13.10 | 0.00 | 204.83 | 863.25 | 16.60 | 0.00 | 161.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7587.42 | 34.93 | 231.50 | 392.00 | 3041.51 | 36.50 | 227.00 | 340.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-09:50 | 881.63 | 18.45 | 61.33 | 197.00 | 546.64 | 20.98 | 72.50 | 124.00 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1425.96 | 19.19 | 68.00 | 225.50 | 754.71 | 21.67 | 74.33 | 174.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2589.99 | 21.61 | 79.00 | 300.00 | 1137.92 | 22.82 | 80.50 | 248.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2721.69 | 20.65 | 105.33 | 344.50 | 1525.45 | 23.02 | 95.33 | 303.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2816.61 | 20.60 | 132.33 | 388.33 | 1209.34 | 21.17 | 85.17 | 344.00 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 2941.69 | 19.80 | 89.00 | 400.67 | 1614.57 | 22.11 | 75.83 | 351.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2778.71 | 20.13 | 146.50 | 404.00 | 1243.00 | 20.67 | 87.17 | 365.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3196.03 | 20.22 | 98.50 | 373.50 | 1398.18 | 21.80 | 71.33 | 332.83 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2656.31 | 21.30 | 82.67 | 319.67 | 1474.21 | 22.80 | 67.67 | 280.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2374.30 | 21.29 | 81.00 | 267.83 | 1047.40 | 22.42 | 76.83 | 221.17 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1081.37 | 18.45 | 65.67 | 203.67 | 572.12 | 20.92 | 67.83 | 137.83 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:39 | 1034.38 | 21.01 | 56.33 | 178.83 | 556.71 | 21.88 | 54.83 | 98.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2383.52 | 20.24 | 1065.67 | 3603.50 | 1167.51 | 21.81 | 909.33 | 2982.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 881.63 | 18.45 | 56.33 | 178.83 | 546.64 | 20.67 | 54.83 | 98.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3196.03 | 21.61 | 146.50 | 404.00 | 1614.57 | 23.02 | 95.33 | 365.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.56 | 0.48 | 02-JAN-11:09 | 471.86 | 10.05 | 0.00 | 172.50 | 258.54 | 13.60 | 0.00 | 33.50 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 598.02 | 11.55 | 0.00 | 210.33 | 340.49 | 15.12 | 0.00 | 120.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 804.54 | 13.48 | 0.00 | 293.00 | 480.87 | 17.02 | 0.00 | 205.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 945.73 | 14.26 | 0.00 | 346.00 | 551.71 | 17.70 | 0.17 | 294.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1176.28 | 16.05 | 26.67 | 397.83 | 676.44 | 19.98 | 51.33 | 362.00 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:30 | 1236.96 | 18.31 | 59.00 | 411.00 | 732.10 | 21.51 | 73.17 | 380.67 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1043.28 | 15.66 | 44.67 | 420.83 | 631.63 | 20.52 | 86.50 | 378.33 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 919.73 | 14.48 | 0.00 | 389.17 | 567.23 | 18.09 | 1.50 | 339.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 873.52 | 14.66 | 0.00 | 311.17 | 535.98 | 18.16 | 0.00 | 247.50 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:20 | 650.67 | 12.50 | 0.00 | 255.67 | 398.59 | 16.11 | 0.00 | 156.00 |
November | 242.67 | 0.55 | 0.48 | 01-NOV-10:09 | 508.67 | 10.41 | 0.00 | 184.00 | 278.51 | 13.91 | 0.00 | 53.00 |
December | 160.33 | 0.57 | 0.48 | 01-DEC-10:09 | 438.08 | 10.25 | 0.00 | 145.00 | 259.03 | 14.04 | 0.00 | 28.67 |
Annual Sum or Average | 3714.00 | 0.52 | 871.66 | 14.06 | 130.33 | 3536.50 | 515.85 | 17.78 | 212.67 | 2599.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 438.08 | 10.05 | 0.00 | 145.00 | 258.54 | 13.60 | 0.00 | 28.67 | |
Maximum of Months | 471.00 | 0.57 | 0.48 | 1236.96 | 18.31 | 59.00 | 420.83 | 732.10 | 21.51 | 86.50 | 380.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-12:00 | 989.65 | 18.46 | 64.83 | 197.67 | 538.11 | 21.05 | 67.50 | 129.83 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:20 | 1422.40 | 19.45 | 66.50 | 227.17 | 721.52 | 20.56 | 60.67 | 175.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2286.33 | 21.74 | 78.17 | 302.17 | 1215.08 | 22.90 | 91.33 | 245.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 2709.70 | 20.40 | 105.50 | 342.00 | 1185.20 | 20.61 | 55.00 | 303.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 2827.03 | 17.22 | 52.33 | 389.67 | 1514.42 | 18.45 | 8.33 | 351.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 2862.82 | 16.84 | 42.83 | 398.50 | 1290.58 | 18.24 | 0.83 | 358.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-06:19 | 3151.66 | 15.98 | 58.83 | 399.00 | 1377.42 | 17.07 | 4.00 | 357.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3022.21 | 18.82 | 75.83 | 376.67 | 1722.52 | 20.58 | 54.17 | 337.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3341.71 | 22.57 | 100.50 | 312.67 | 1840.65 | 23.51 | 90.83 | 266.00 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-08:30 | 2285.19 | 21.93 | 87.33 | 269.00 | 991.96 | 21.85 | 73.50 | 218.83 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:50 | 1057.57 | 18.40 | 62.83 | 206.83 | 559.45 | 20.38 | 58.50 | 132.67 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:00 | 1056.11 | 19.91 | 48.67 | 180.50 | 560.32 | 20.96 | 49.67 | 94.00 |
Annual Sum or Average | 3714.00 | 0.51 | 2441.21 | 18.98 | 844.17 | 3601.83 | 1211.87 | 20.17 | 614.33 | 2971.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 989.65 | 15.98 | 42.83 | 180.50 | 538.11 | 17.07 | 0.83 | 94.00 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3341.71 | 22.57 | 105.50 | 399.00 | 1840.65 | 23.51 | 91.33 | 358.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.51 | 0.48 | 01-JAN-09:50 | 2628.29 | 30.49 | 207.17 | 216.17 | 2123.78 | 33.20 | 222.50 | 182.50 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:39 | 4546.23 | 32.09 | 231.50 | 240.50 | 1973.30 | 27.94 | 157.17 | 219.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7587.32 | 32.25 | 207.67 | 309.83 | 1574.14 | 18.97 | 12.33 | 263.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2076.28 | 14.68 | 0.00 | 342.83 | 1140.35 | 18.19 | 10.50 | 302.67 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 1906.67 | 14.64 | 0.00 | 382.67 | 1033.37 | 18.09 | 3.33 | 339.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 1665.64 | 14.46 | 0.00 | 392.00 | 952.20 | 17.92 | 0.00 | 340.00 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1481.30 | 13.10 | 0.00 | 389.33 | 863.19 | 16.60 | 1.00 | 331.67 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 1751.09 | 14.23 | 0.00 | 369.33 | 1040.46 | 17.80 | 5.83 | 322.17 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2846.65 | 17.25 | 27.00 | 317.83 | 1375.02 | 19.08 | 29.67 | 282.50 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7032.63 | 33.75 | 218.00 | 282.33 | 1850.07 | 20.32 | 28.33 | 254.50 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:09 | 2948.96 | 30.64 | 215.33 | 222.17 | 2388.97 | 32.83 | 227.00 | 189.67 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3551.91 | 34.93 | 149.17 | 204.83 | 3041.45 | 36.50 | 149.67 | 161.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2992.73 | 21.19 | 1255.83 | 3669.83 | 1443.60 | 21.56 | 847.33 | 3189.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1481.30 | 13.10 | 0.00 | 204.83 | 863.19 | 16.60 | 0.00 | 161.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7587.32 | 34.93 | 231.50 | 392.00 | 3041.45 | 36.50 | 227.00 | 340.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-09:50 | 881.60 | 18.45 | 61.33 | 197.00 | 546.60 | 20.98 | 72.50 | 124.00 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1425.92 | 19.19 | 68.00 | 225.50 | 754.66 | 21.67 | 74.33 | 174.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2589.95 | 21.61 | 79.00 | 300.00 | 1137.86 | 22.82 | 80.50 | 248.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2721.63 | 20.65 | 105.33 | 344.50 | 1525.38 | 23.02 | 95.33 | 303.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2816.53 | 20.60 | 132.33 | 388.33 | 1209.26 | 21.17 | 85.17 | 344.00 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 2941.63 | 19.81 | 89.00 | 400.83 | 1614.50 | 22.11 | 75.83 | 351.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2778.66 | 20.14 | 146.50 | 404.00 | 1242.95 | 20.67 | 87.17 | 365.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3195.99 | 20.23 | 98.50 | 373.50 | 1398.12 | 21.80 | 71.33 | 332.83 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2656.27 | 21.30 | 82.67 | 319.67 | 1474.15 | 22.80 | 67.67 | 280.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2374.28 | 21.29 | 81.00 | 267.83 | 1047.35 | 22.42 | 76.83 | 221.00 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1081.33 | 18.45 | 65.67 | 203.67 | 572.09 | 20.92 | 67.83 | 137.83 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:39 | 1034.36 | 21.01 | 56.33 | 178.83 | 556.68 | 21.89 | 54.83 | 98.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2383.47 | 20.24 | 1065.67 | 3603.67 | 1167.45 | 21.81 | 909.33 | 2981.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 881.60 | 18.45 | 56.33 | 178.83 | 546.60 | 20.67 | 54.83 | 98.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3195.99 | 21.61 | 146.50 | 404.00 | 1614.50 | 23.02 | 95.33 | 365.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.56 | 0.48 | 02-JAN-11:09 | 471.83 | 10.05 | 0.00 | 172.50 | 258.52 | 13.60 | 0.00 | 33.50 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 597.99 | 11.55 | 0.00 | 210.33 | 340.46 | 15.12 | 0.00 | 120.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 804.51 | 13.48 | 0.00 | 293.00 | 480.83 | 17.02 | 0.00 | 205.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 945.69 | 14.26 | 0.00 | 346.00 | 551.68 | 17.70 | 0.17 | 294.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1176.23 | 16.06 | 26.67 | 397.83 | 676.39 | 19.98 | 51.33 | 362.00 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:30 | 1236.93 | 18.31 | 59.00 | 411.00 | 732.06 | 21.51 | 73.33 | 380.67 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1043.25 | 15.66 | 44.67 | 420.83 | 631.59 | 20.52 | 86.50 | 378.33 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 919.70 | 14.48 | 0.00 | 389.17 | 567.20 | 18.09 | 1.50 | 339.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 873.50 | 14.66 | 0.00 | 311.17 | 535.95 | 18.16 | 0.00 | 247.50 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:20 | 650.65 | 12.50 | 0.00 | 255.67 | 398.56 | 16.11 | 0.00 | 156.00 |
November | 242.67 | 0.55 | 0.48 | 01-NOV-10:09 | 508.64 | 10.42 | 0.00 | 184.00 | 278.48 | 13.91 | 0.00 | 53.00 |
December | 160.33 | 0.57 | 0.48 | 01-DEC-10:09 | 438.06 | 10.25 | 0.00 | 145.00 | 259.01 | 14.04 | 0.00 | 28.67 |
Annual Sum or Average | 3714.00 | 0.52 | 871.63 | 14.06 | 130.33 | 3536.50 | 515.82 | 17.78 | 212.83 | 2599.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 438.06 | 10.05 | 0.00 | 145.00 | 258.52 | 13.60 | 0.00 | 28.67 | |
Maximum of Months | 471.00 | 0.57 | 0.48 | 1236.93 | 18.31 | 59.00 | 420.83 | 732.06 | 21.51 | 86.50 | 380.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-12:00 | 989.62 | 18.46 | 64.83 | 197.67 | 538.07 | 21.05 | 67.50 | 129.83 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:20 | 1422.37 | 19.45 | 66.50 | 227.17 | 721.47 | 20.56 | 60.67 | 175.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2286.28 | 21.75 | 78.17 | 302.17 | 1215.01 | 22.90 | 91.33 | 245.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 2709.64 | 20.41 | 105.50 | 342.00 | 1185.12 | 20.61 | 55.00 | 303.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 2826.95 | 17.22 | 52.33 | 389.67 | 1514.34 | 18.45 | 8.33 | 351.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 2862.76 | 16.84 | 42.83 | 398.50 | 1290.51 | 18.24 | 0.83 | 358.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-06:19 | 3151.60 | 15.98 | 58.83 | 399.00 | 1377.35 | 17.08 | 4.00 | 357.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3022.18 | 18.82 | 75.83 | 376.67 | 1722.46 | 20.58 | 54.17 | 337.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3341.68 | 22.57 | 100.50 | 312.67 | 1840.58 | 23.51 | 90.83 | 266.00 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-08:30 | 2285.16 | 21.93 | 87.33 | 269.00 | 991.91 | 21.85 | 73.50 | 218.83 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:50 | 1057.54 | 18.41 | 62.83 | 206.83 | 559.41 | 20.39 | 58.50 | 132.67 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:00 | 1056.10 | 19.91 | 48.67 | 180.50 | 560.29 | 20.96 | 49.67 | 94.00 |
Annual Sum or Average | 3714.00 | 0.51 | 2441.16 | 18.98 | 844.17 | 3601.83 | 1211.81 | 20.17 | 614.33 | 2971.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 989.62 | 15.98 | 42.83 | 180.50 | 538.07 | 17.08 | 0.83 | 94.00 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3341.68 | 22.57 | 105.50 | 399.00 | 1840.58 | 23.51 | 91.33 | 358.83 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.738077E+10 | 12509.45 | 07-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.504715E+10 | 12320.33 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.237384E+10 | 11003.90 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.864186E+09 | 8271.07 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134256E+09 | 3766.37 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 320987.08 | 4.58 | 31-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 796224.93 | 4.47 | 08-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4531475.18 | 1077.61 | 27-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.318546E+09 | 4411.40 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.343494E+10 | 10793.62 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.638036E+10 | 12481.74 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.738077E+10 | 12509.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.684675E+09 | 9946.75 | 04-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.684675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.684675E+09 | 9946.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.443953E+10 | 7822.54 | 06-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.245387E+10 | 7584.17 | 09-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162684E+10 | 7479.73 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.898896E+09 | 7469.94 | 26-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.597202E+09 | 7511.15 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.297909E+09 | 7525.12 | 08-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 58937290.78 | 7457.81 | 13-JUL-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74323681.68 | 7466.55 | 21-AUG-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.264053E+09 | 7490.99 | 20-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.832494E+09 | 7510.28 | 02-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215604E+10 | 7470.72 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.336072E+10 | 7715.43 | 26-DEC-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 58937290.78 | 7457.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.443953E+10 | 7822.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145189E+10 | 5168.61 | 07-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.522145E+09 | 5084.98 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 63240150.89 | 5010.24 | 24-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3778701.60 | 4999.79 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 416231.22 | 905.48 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203541E+09 | 5010.88 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.786879E+09 | 5157.63 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145189E+10 | 5168.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.238349E+10 | 5512.65 | 06-JAN-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105068E+10 | 5424.95 | 18-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206451E+09 | 5318.55 | 13-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18036649.05 | 5308.75 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3679320.46 | 3382.19 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.357567E+09 | 5317.23 | 15-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131597E+10 | 5485.93 | 26-DEC-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.238349E+10 | 5512.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147026E+10 | 5354.00 | 07-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.533430E+09 | 5267.17 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 79824797.13 | 5189.23 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7296915.92 | 5183.48 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 174099.28 | 68.69 | 28-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208969E+09 | 5189.88 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.790533E+09 | 5342.49 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147026E+10 | 5354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.758279E+10 | 13186.67 | 06-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.515547E+10 | 13087.25 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269209E+10 | 11271.21 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113214E+10 | 8499.89 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.266696E+09 | 4754.18 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6214584.89 | 1098.19 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 287190.76 | 4.71 | 31-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 745254.53 | 4.59 | 24-AUG-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33796827.07 | 2390.75 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.614428E+09 | 4979.89 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.380644E+10 | 11471.94 | 24-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.658478E+10 | 12713.90 | 26-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 287190.76 | 4.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.758279E+10 | 13186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141004E+10 | 13225.18 | 30-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173610E+09 | 13204.53 | 21-FEB-07:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2221822.84 | 6636.11 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 44297878.57 | 13233.74 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.390632E+09 | 13230.49 | 28-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141004E+10 | 13233.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136370E+10 | 8112.43 | 06-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.440386E+09 | 8045.58 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 49139615.01 | 7995.73 | 08-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3470596.88 | 5067.62 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4470239.69 | 2236.97 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293013E+09 | 8034.22 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.902881E+09 | 8034.48 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.305706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136370E+10 | 8112.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108596E+10 | 5683.46 | 07-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380725E+09 | 5551.66 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34494982.35 | 5543.62 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1795309.77 | 4162.42 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7025514.71 | 3246.79 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248374E+09 | 5543.53 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.717368E+09 | 5584.66 | 26-DEC-13:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108596E+10 | 5683.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187551E+10 | 5848.91 | 07-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.720592E+09 | 5839.58 | 18-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80487379.97 | 5715.48 | 06-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4822955.56 | 5688.70 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11573585.46 | 5694.61 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428510E+09 | 5718.81 | 27-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123835E+10 | 5867.21 | 26-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.435984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187551E+10 | 5867.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116929E+10 | 5685.31 | 07-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.412243E+09 | 5553.40 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 51024160.06 | 5525.94 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4137811.20 | 5528.16 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6983785.98 | 2320.96 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268850E+09 | 5545.20 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.767081E+09 | 5545.37 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.267961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116929E+10 | 5685.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.791223E+10 | 12674.05 | 07-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.543222E+10 | 12797.67 | 18-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.314501E+10 | 12731.21 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143607E+10 | 11191.82 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.413885E+09 | 5812.68 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20977070.95 | 1926.09 | 15-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 305052.76 | 4.82 | 24-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744260.61 | 4.88 | 08-AUG-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76718062.47 | 3330.69 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.907679E+09 | 5842.85 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.419057E+10 | 11572.32 | 24-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.701595E+10 | 12662.54 | 26-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.305524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 305052.76 | 4.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.791223E+10 | 12797.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.357646E+10 | 19477.44 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130175E+10 | 19484.69 | 01-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111088E+09 | 19469.14 | 13-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15717237.08 | 16595.87 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.836568E+09 | 19483.85 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231278E+10 | 19490.62 | 29-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.815437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.357646E+10 | 19490.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.229108E+10 | 9616.33 | 03-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104971E+10 | 9611.16 | 22-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286111E+09 | 9767.34 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63154656.55 | 9583.29 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2250812.51 | 4465.30 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 473275.06 | 730.50 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 93651108.24 | 9579.00 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.851445E+09 | 9610.68 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183093E+10 | 9611.01 | 18-DEC-06:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.646881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.229108E+10 | 9767.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184036E+10 | 6665.62 | 06-JAN-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.868065E+09 | 6414.26 | 13-FEB-06:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192690E+09 | 6511.72 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27447501.61 | 6383.93 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1524339.97 | 3076.14 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 433587.26 | 957.27 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78398848.41 | 6385.91 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.671764E+09 | 6407.13 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145344E+10 | 6545.99 | 26-DEC-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.513412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184036E+10 | 6665.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.300638E+10 | 7293.36 | 07-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154703E+10 | 7217.28 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.408793E+09 | 7016.77 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 75065208.42 | 6907.53 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1997275.08 | 3996.31 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1585361.28 | 1309.41 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141575E+09 | 6902.14 | 18-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114135E+10 | 6991.04 | 24-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.241803E+10 | 7132.30 | 26-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.874182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.300638E+10 | 7293.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189123E+10 | 6892.73 | 06-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.925013E+09 | 6615.81 | 22-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.248377E+09 | 6723.94 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 48967785.75 | 6596.80 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1621857.81 | 3211.29 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 430271.28 | 562.65 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87197117.64 | 6593.31 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.713183E+09 | 6615.51 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151019E+10 | 6750.58 | 26-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.542621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189123E+10 | 6892.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 954266.94 | 856294.18 | 981.82 | 11-JAN-07:05 | 838.75 | 0.00 |
February | 0.00 | 0.00 | 0.157599E+09 | 0.137190E+09 | 9842.03 | 27-FEB-15:10 | 9670.69 | 0.00 |
March | 0.00 | 0.00 | 0.243913E+09 | 0.211939E+09 | 8910.62 | 18-MAR-16:00 | 8910.62 | 0.00 |
April | 0.00 | 0.00 | 0.314224E+10 | 0.301923E+10 | 45017.53 | 27-APR-15:00 | 45017.53 | 0.00 |
May | 0.00 | 0.00 | 0.648495E+10 | 0.578371E+10 | 40796.21 | 15-MAY-16:00 | 40796.21 | 0.00 |
June | 0.00 | 0.00 | 0.123393E+11 | 0.114920E+11 | 46259.49 | 28-JUN-15:30 | 46259.49 | 0.00 |
July | 0.00 | 0.00 | 0.239548E+11 | 0.212548E+11 | 63284.65 | 31-JUL-15:50 | 57503.94 | 0.00 |
August | 0.00 | 0.00 | 0.326565E+11 | 0.286644E+11 | 63345.77 | 10-AUG-15:30 | 59662.57 | 0.00 |
September | 0.00 | 0.00 | 0.120271E+11 | 0.100950E+11 | 50647.93 | 12-SEP-16:00 | 47846.42 | 0.00 |
October | 0.00 | 0.00 | 0.171941E+10 | 0.161929E+10 | 30872.97 | 04-OCT-15:00 | 30872.97 | 0.00 |
November | 0.00 | 0.00 | 0.300978E+09 | 0.204179E+09 | 15759.55 | 04-NOV-14:30 | 11678.74 | 0.00 |
December | 0.00 | 0.00 | 250647.42 | 184298.84 | 1094.49 | 29-DEC-07:05 | 780.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.930279E+11 | 0.824827E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 250647.42 | 184298.84 | 981.82 | 780.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.326565E+11 | 0.286644E+11 | 63345.77 | 59662.57 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.176013E+09 | 0.161571E+09 | 12257.36 | 27-FEB-15:05 | 12257.36 | 0.00 |
March | 0.00 | 0.00 | 0.272050E+09 | 0.243552E+09 | 10977.35 | 18-MAR-14:05 | 10977.35 | 0.00 |
April | 0.00 | 0.00 | 0.327395E+10 | 0.315564E+10 | 47633.47 | 27-APR-14:05 | 47633.47 | 0.00 |
May | 0.00 | 0.00 | 0.678380E+10 | 0.610356E+10 | 41704.59 | 15-MAY-14:05 | 41704.59 | 0.00 |
June | 0.00 | 0.00 | 0.124106E+11 | 0.115778E+11 | 46129.66 | 28-JUN-15:20 | 46129.66 | 0.00 |
July | 0.00 | 0.00 | 0.234070E+11 | 0.208241E+11 | 64482.35 | 31-JUL-14:05 | 57676.57 | 0.00 |
August | 0.00 | 0.00 | 0.308485E+11 | 0.270887E+11 | 63568.89 | 29-AUG-14:30 | 55246.04 | 0.00 |
September | 0.00 | 0.00 | 0.115493E+11 | 0.965673E+10 | 51226.11 | 13-SEP-14:05 | 39807.57 | 0.00 |
October | 0.00 | 0.00 | 0.150391E+10 | 0.141391E+10 | 30066.81 | 04-OCT-15:00 | 30066.81 | 0.00 |
November | 0.00 | 0.00 | 0.329167E+09 | 0.232863E+09 | 17956.99 | 04-NOV-14:05 | 14247.38 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.905543E+11 | 0.804584E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.308485E+11 | 0.270887E+11 | 64482.35 | 57676.57 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 27836.25 | 25680.72 | 371.15 | 02-JAN-06:17 | 342.41 | 0.00 |
February | 0.00 | 0.00 | 0.181629E+09 | 0.161896E+09 | 11693.92 | 27-FEB-15:00 | 11693.92 | 0.00 |
March | 0.00 | 0.00 | 0.390689E+09 | 0.355969E+09 | 10500.47 | 18-MAR-16:00 | 10500.47 | 0.00 |
April | 0.00 | 0.00 | 0.349758E+10 | 0.334153E+10 | 53966.13 | 27-APR-14:30 | 53966.13 | 0.00 |
May | 0.00 | 0.00 | 0.715776E+10 | 0.637540E+10 | 45350.49 | 04-MAY-15:00 | 45350.49 | 0.00 |
June | 0.00 | 0.00 | 0.131383E+11 | 0.121649E+11 | 53756.26 | 28-JUN-15:20 | 53756.26 | 0.00 |
July | 0.00 | 0.00 | 0.250890E+11 | 0.221419E+11 | 70629.89 | 31-JUL-14:40 | 64086.41 | 0.00 |
August | 0.00 | 0.00 | 0.325395E+11 | 0.284373E+11 | 70274.72 | 10-AUG-14:50 | 65304.25 | 0.00 |
September | 0.00 | 0.00 | 0.116250E+11 | 0.959549E+10 | 50667.03 | 14-SEP-13:30 | 40232.31 | 0.00 |
October | 0.00 | 0.00 | 0.139680E+10 | 0.129113E+10 | 29522.26 | 04-OCT-15:00 | 29522.26 | 0.00 |
November | 0.00 | 0.00 | 0.335408E+09 | 0.229261E+09 | 18002.67 | 04-NOV-14:20 | 13542.21 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.953518E+11 | 0.840948E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.325395E+11 | 0.284373E+11 | 70629.89 | 65304.25 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 19575.62 | 147074.80 | 25-JAN-07:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11489.72 | 159858.31 | 08-FEB-07:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 4315.31 | 151509.81 | 01-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1757.36 | 126515.74 | 18-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 527.81 | 55445.16 | 18-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 122.49 | 10905.74 | 15-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.19 | 9337.51 | 27-JUL-06:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.21 | 9410.04 | 01-AUG-06:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 146.33 | 19660.44 | 28-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1154.65 | 100459.56 | 23-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 7602.28 | 141558.65 | 28-NOV-07:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14741.32 | 150898.82 | 06-DEC-07:01 |
Annual Sum or Average | 0.00 | 5101.05 | ||||
Minimum of Months | 0.00 | 0.00 | 21.19 | 9337.51 | ||
Maximum of Months | 0.00 | 0.00 | 19575.62 | 159858.31 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1702.15 | 6226.65 | 31-JAN-12:13 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1724.48 | 6234.24 | 10-FEB-12:13 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1823.75 | 6212.86 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1649.61 | 6074.20 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1649.95 | 5884.96 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1631.24 | 5653.24 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1446.19 | 5455.76 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1586.59 | 5376.20 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1495.25 | 5493.64 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1541.18 | 5706.35 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1627.90 | 5930.80 | 30-NOV-12:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1615.25 | 6114.31 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 1623.90 | ||||
Minimum of Months | 0.00 | 0.00 | 1446.19 | 5376.20 | ||
Maximum of Months | 0.00 | 0.00 | 1823.75 | 6234.24 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111987E+10 | 0.29 | 2336.72 | 02-JAN-06:11 | 0.79 |
February | 0.935231E+09 | 0.28 | 1485.87 | 01-FEB-07:03 | 0.63 |
March | 0.123471E+10 | 0.30 | 1492.32 | 02-MAR-15:40 | 0.63 |
April | 0.150701E+10 | 0.30 | 5119.50 | 27-APR-14:30 | 1.24 |
May | 0.213091E+10 | 0.35 | 5787.96 | 15-MAY-14:40 | 1.34 |
June | 0.267743E+10 | 0.40 | 5718.27 | 28-JUN-15:20 | 1.33 |
July | 0.343449E+10 | 0.43 | 8373.67 | 31-JUL-15:00 | 1.68 |
August | 0.406351E+10 | 0.48 | 8934.75 | 14-AUG-15:20 | 1.76 |
September | 0.262893E+10 | 0.38 | 7824.47 | 11-SEP-15:50 | 1.61 |
October | 0.161775E+10 | 0.30 | 5530.12 | 04-OCT-15:40 | 1.31 |
November | 0.105930E+10 | 0.27 | 1485.87 | 13-NOV-07:01 | 0.63 |
December | 0.101425E+10 | 0.27 | 1485.87 | 01-DEC-06:11 | 0.63 |
Annual Sum or Average | 0.234234E+11 | 0.34 | |||
Minimum of Months | 0.935231E+09 | 0.27 | 1485.87 | 0.63 | |
Maximum of Months | 0.406351E+10 | 0.48 | 8934.75 | 1.76 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.102972E+10 | 0.29 | 2535.02 | 02-JAN-07:03 | 0.84 |
February | 0.916932E+09 | 0.28 | 2535.02 | 13-FEB-07:02 | 0.84 |
March | 0.116560E+10 | 0.30 | 2315.94 | 01-MAR-13:01 | 0.80 |
April | 0.149750E+10 | 0.31 | 6328.26 | 27-APR-14:05 | 1.44 |
May | 0.216092E+10 | 0.36 | 6901.73 | 15-MAY-14:05 | 1.53 |
June | 0.265417E+10 | 0.41 | 6043.32 | 28-JUN-14:05 | 1.40 |
July | 0.329845E+10 | 0.43 | 8795.34 | 24-JUL-06:03 | 1.77 |
August | 0.374226E+10 | 0.47 | 9058.85 | 14-AUG-06:02 | 1.81 |
September | 0.238767E+10 | 0.38 | 7621.12 | 11-SEP-15:00 | 1.62 |
October | 0.138703E+10 | 0.30 | 5285.57 | 04-OCT-15:10 | 1.30 |
November | 0.947561E+09 | 0.28 | 2535.02 | 24-NOV-07:01 | 0.84 |
December | 0.967788E+09 | 0.27 | 2535.02 | 26-DEC-06:04 | 0.84 |
Annual Sum or Average | 0.221556E+11 | 0.34 | |||
Minimum of Months | 0.916932E+09 | 0.27 | 2315.94 | 0.80 | |
Maximum of Months | 0.374226E+10 | 0.47 | 9058.85 | 1.81 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119159E+10 | 0.32 | 2411.52 | 02-JAN-06:11 | 0.76 |
February | 0.100361E+10 | 0.30 | 2411.52 | 01-FEB-07:03 | 0.76 |
March | 0.120747E+10 | 0.32 | 2411.52 | 06-MAR-06:11 | 0.76 |
April | 0.145399E+10 | 0.31 | 6045.05 | 27-APR-14:30 | 1.29 |
May | 0.203406E+10 | 0.35 | 6700.39 | 15-MAY-14:40 | 1.39 |
June | 0.247897E+10 | 0.39 | 6124.24 | 28-JUN-15:20 | 1.31 |
July | 0.312237E+10 | 0.41 | 8380.63 | 31-JUL-14:40 | 1.59 |
August | 0.345357E+10 | 0.43 | 8197.48 | 10-AUG-15:10 | 1.56 |
September | 0.212761E+10 | 0.36 | 6813.09 | 11-SEP-14:50 | 1.40 |
October | 0.129369E+10 | 0.30 | 4454.67 | 04-OCT-15:00 | 1.08 |
November | 0.102934E+10 | 0.30 | 2411.52 | 13-NOV-06:01 | 0.76 |
December | 0.108063E+10 | 0.30 | 2411.52 | 01-DEC-07:01 | 0.76 |
Annual Sum or Average | 0.214769E+11 | 0.34 | |||
Minimum of Months | 0.100361E+10 | 0.30 | 2411.52 | 0.76 | |
Maximum of Months | 0.345357E+10 | 0.43 | 8380.63 | 1.59 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.349028E+09 | 0.317266E+09 | 528.73 | 06-JAN-07:12 | 480.62 | 480.62 | 41.53 | 1.71 |
February | 0.199994E+09 | 0.181794E+09 | 537.28 | 18-FEB-07:03 | 488.39 | 488.39 | 40.82 | 1.75 |
March | 86322098.22 | 78466787.28 | 463.31 | 01-MAR-07:01 | 421.15 | 421.15 | 32.78 | 1.33 |
April | 34830112.63 | 31660572.38 | 447.54 | 18-APR-06:02 | 406.81 | 406.81 | 33.77 | 1.15 |
May | 12088237.24 | 10988207.65 | 328.30 | 18-MAY-06:03 | 298.42 | 298.42 | 33.90 | 0.51 |
June | 3610186.71 | 3281659.72 | 93.81 | 15-JUN-06:03 | 85.27 | 85.27 | 35.02 | 0.10 |
July | 553574.60 | 503199.31 | 76.58 | 05-JUL-06:07 | 69.61 | 69.61 | 38.08 | 0.08 |
August | 952310.50 | 865650.24 | 76.83 | 21-AUG-06:06 | 69.84 | 69.84 | 46.93 | 0.08 |
September | 3913389.19 | 3557270.77 | 129.69 | 28-SEP-06:03 | 117.89 | 117.89 | 28.64 | 0.15 |
October | 24284502.72 | 22074612.98 | 422.85 | 30-OCT-06:03 | 384.37 | 384.37 | 34.20 | 0.91 |
November | 0.141826E+09 | 0.128920E+09 | 494.33 | 24-NOV-07:01 | 449.35 | 449.35 | 42.02 | 1.56 |
December | 0.270812E+09 | 0.246168E+09 | 521.60 | 26-DEC-07:01 | 474.13 | 474.13 | 42.78 | 1.69 |
Annual Sum or Average | 0.112821E+10 | 0.102555E+10 | ||||||
Minimum of Months | 553574.60 | 503199.31 | 76.58 | 69.61 | 69.61 | 28.64 | 0.08 | |
Maximum of Months | 0.349028E+09 | 0.317266E+09 | 537.28 | 488.39 | 488.39 | 46.93 | 1.75 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:05 | 2.06 | 2.06 | 58.14 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:05 | 2.06 | 2.06 | 56.83 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.93 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.91 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.23 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.21 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 57.22 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.36 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.35 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.20 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:05 | 2.06 | 2.06 | 57.10 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.07 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.83 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.20 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 40.47 | 60.00 | 19575.62 | 147074.80 | 25-JAN-07:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 32.44 | 32.44 | 11489.72 | 159858.31 | 08-FEB-07:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 27.27 | 27.27 | 4315.31 | 151509.81 | 01-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.28 | 25.28 | 1757.36 | 126515.74 | 18-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 31.69 | 31.69 | 527.81 | 55445.16 | 18-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 46.32 | 46.32 | 122.49 | 10905.74 | 15-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 38.05 | 38.05 | 21.19 | 9337.51 | 27-JUL-06:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 32.75 | 32.75 | 29.21 | 9410.04 | 01-AUG-06:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 38.16 | 38.16 | 146.33 | 19660.44 | 28-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 40.84 | 40.84 | 1154.65 | 100459.56 | 23-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 29.30 | 29.30 | 7602.28 | 141558.65 | 28-NOV-07:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 34.76 | 34.76 | 14741.32 | 150898.82 | 06-DEC-07:01 |
Annual Sum or Average | 0.00 | 5101.05 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.28 | 25.28 | 21.19 | 9337.51 | ||
Maximum of Months | 0.00 | 0.00 | 46.32 | 60.00 | 19575.62 | 159858.31 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.14 | 58.14 | 1702.15 | 6226.65 | 31-JAN-12:13 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.62 | 57.62 | 1724.48 | 6234.24 | 10-FEB-12:13 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.62 | 57.62 | 1823.75 | 6212.86 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.67 | 57.67 | 1649.61 | 6074.20 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.21 | 58.21 | 1649.95 | 5884.96 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.84 | 57.84 | 1631.24 | 5653.24 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.91 | 57.91 | 1446.19 | 5455.76 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.95 | 57.95 | 1586.59 | 5376.20 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.95 | 57.95 | 1495.25 | 5493.64 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.04 | 57.04 | 1541.18 | 5706.35 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.82 | 57.82 | 1627.90 | 5930.80 | 30-NOV-12:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.73 | 57.73 | 1615.25 | 6114.31 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 1623.90 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.04 | 57.04 | 1446.19 | 5376.20 | ||
Maximum of Months | 0.00 | 0.00 | 58.21 | 58.21 | 1823.75 | 6234.24 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.178106E+11 | 0.00 | 0.00 | 0.112012E+10 | 0.00 | 0.00 |
February | 0.960728E+10 | 0.00 | 0.00 | 0.973151E+09 | 0.00 | 0.00 |
March | 0.435020E+10 | 0.00 | 0.00 | 0.129465E+10 | 0.00 | 0.00 |
April | 0.179219E+10 | 0.00 | 0.00 | 0.220098E+10 | 0.00 | 0.00 |
May | 0.731458E+09 | 0.00 | 0.00 | 0.354844E+10 | 0.00 | 0.00 |
June | 0.297909E+09 | 0.00 | 0.00 | 0.536406E+10 | 0.00 | 0.00 |
July | 59258277.86 | 0.00 | 0.00 | 0.856505E+10 | 0.00 | 0.00 |
August | 75119906.61 | 0.00 | 0.00 | 0.110986E+11 | 0.00 | 0.00 |
September | 0.268584E+09 | 0.00 | 0.00 | 0.519824E+10 | 0.00 | 0.00 |
October | 0.115531E+10 | 0.00 | 0.00 | 0.200936E+10 | 0.00 | 0.00 |
November | 0.636106E+10 | 0.00 | 0.00 | 0.112741E+10 | 0.00 | 0.00 |
December | 0.126345E+11 | 0.00 | 0.00 | 0.101431E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.551434E+11 | 0.00 | 0.00 | 0.435144E+11 | 0.00 | 0.00 |
Minimum of Months | 59258277.86 | 0.00 | 0.00 | 0.973151E+09 | 0.00 | 0.00 |
Maximum of Months | 0.178106E+11 | 0.00 | 0.00 | 0.110986E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.144873E+11 | 0.00 | 0.00 | 0.102972E+10 | 0.00 | 0.00 |
February | 0.728302E+10 | 0.00 | 0.00 | 0.958829E+09 | 0.00 | 0.00 |
March | 0.290946E+10 | 0.00 | 0.00 | 0.123173E+10 | 0.00 | 0.00 |
April | 0.114637E+10 | 0.00 | 0.00 | 0.221655E+10 | 0.00 | 0.00 |
May | 0.266696E+09 | 0.00 | 0.00 | 0.363506E+10 | 0.00 | 0.00 |
June | 6214584.89 | 0.00 | 0.00 | 0.535181E+10 | 0.00 | 0.00 |
July | 287190.76 | 0.00 | 0.00 | 0.830924E+10 | 0.00 | 0.00 |
August | 745254.53 | 0.00 | 0.00 | 0.103976E+11 | 0.00 | 0.00 |
September | 33796827.07 | 0.00 | 0.00 | 0.485761E+10 | 0.00 | 0.00 |
October | 0.644482E+09 | 0.00 | 0.00 | 0.172620E+10 | 0.00 | 0.00 |
November | 0.508948E+10 | 0.00 | 0.00 | 0.102091E+10 | 0.00 | 0.00 |
December | 0.106011E+11 | 0.00 | 0.00 | 0.967788E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.424689E+11 | 0.00 | 0.00 | 0.417031E+11 | 0.00 | 0.00 |
Minimum of Months | 287190.76 | 0.00 | 0.00 | 0.958829E+09 | 0.00 | 0.00 |
Maximum of Months | 0.144873E+11 | 0.00 | 0.00 | 0.103976E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.205177E+11 | 0.00 | 0.00 | 0.119160E+10 | 0.00 | 0.00 |
February | 0.111238E+11 | 0.00 | 0.00 | 0.104713E+10 | 0.00 | 0.00 |
March | 0.439207E+10 | 0.00 | 0.00 | 0.130261E+10 | 0.00 | 0.00 |
April | 0.165071E+10 | 0.00 | 0.00 | 0.222507E+10 | 0.00 | 0.00 |
May | 0.421279E+09 | 0.00 | 0.00 | 0.359354E+10 | 0.00 | 0.00 |
June | 20977070.95 | 0.00 | 0.00 | 0.534442E+10 | 0.00 | 0.00 |
July | 305052.76 | 0.00 | 0.00 | 0.851096E+10 | 0.00 | 0.00 |
August | 744260.61 | 0.00 | 0.00 | 0.105142E+11 | 0.00 | 0.00 |
September | 79640557.35 | 0.00 | 0.00 | 0.462940E+10 | 0.00 | 0.00 |
October | 0.132422E+10 | 0.00 | 0.00 | 0.161322E+10 | 0.00 | 0.00 |
November | 0.840489E+10 | 0.00 | 0.00 | 0.110491E+10 | 0.00 | 0.00 |
December | 0.165413E+11 | 0.00 | 0.00 | 0.108063E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.644777E+11 | 0.00 | 0.00 | 0.421577E+11 | 0.00 | 0.00 |
Minimum of Months | 305052.76 | 0.00 | 0.00 | 0.104713E+10 | 0.00 | 0.00 |
Maximum of Months | 0.205177E+11 | 0.00 | 0.00 | 0.105142E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.111987E+10 | 954266.94 | 0.178106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.935231E+09 | 0.157599E+09 | 0.960728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123471E+10 | 0.243913E+09 | 0.435020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150701E+10 | 0.314224E+10 | 0.179219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.213091E+10 | 0.648495E+10 | 0.731458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267743E+10 | 0.123393E+11 | 0.297909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.343449E+10 | 0.239548E+11 | 59258277.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.406351E+10 | 0.326565E+11 | 75119906.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262893E+10 | 0.120271E+11 | 0.268584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161775E+10 | 0.171941E+10 | 0.115531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105930E+10 | 0.300978E+09 | 0.636106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101425E+10 | 250647.42 | 0.126345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234234E+11 | 0.930279E+11 | 0.551434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.935231E+09 | 250647.42 | 59258277.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.406351E+10 | 0.326565E+11 | 0.178106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.102972E+10 | 0.00 | 0.144873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.916932E+09 | 0.176013E+09 | 0.728302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116560E+10 | 0.272050E+09 | 0.290946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149750E+10 | 0.327395E+10 | 0.114637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.216092E+10 | 0.678380E+10 | 0.266696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.265417E+10 | 0.124106E+11 | 6214584.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.329845E+10 | 0.234070E+11 | 287190.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.374226E+10 | 0.308485E+11 | 745254.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238767E+10 | 0.115493E+11 | 33796827.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138703E+10 | 0.150391E+10 | 0.644482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.947561E+09 | 0.329167E+09 | 0.508948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.967788E+09 | 0.00 | 0.106011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221556E+11 | 0.905543E+11 | 0.424689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.916932E+09 | 0.00 | 287190.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.374226E+10 | 0.308485E+11 | 0.144873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.119159E+10 | 27836.25 | 0.205177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100361E+10 | 0.181629E+09 | 0.111238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120747E+10 | 0.390689E+09 | 0.439207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145399E+10 | 0.349758E+10 | 0.165071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203406E+10 | 0.715776E+10 | 0.421279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.247897E+10 | 0.131383E+11 | 20977070.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.312237E+10 | 0.250890E+11 | 305052.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.345357E+10 | 0.325395E+11 | 744260.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212761E+10 | 0.116250E+11 | 79640557.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129369E+10 | 0.139680E+10 | 0.132422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102934E+10 | 0.335408E+09 | 0.840489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108063E+10 | 0.00 | 0.165413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214769E+11 | 0.953518E+11 | 0.644777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100361E+10 | 0.00 | 305052.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.345357E+10 | 0.325395E+11 | 0.205177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.111987E+10 | 0.178106E+11 | 0.00 | 0.00 | 245535.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.935231E+09 | 0.960728E+10 | 0.00 | 0.00 | 37919477.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123471E+10 | 0.435020E+10 | 0.00 | 0.00 | 59937956.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150701E+10 | 0.179219E+10 | 0.00 | 0.00 | 0.693971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.213091E+10 | 0.731458E+09 | 0.00 | 0.00 | 0.141753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267743E+10 | 0.297909E+09 | 0.00 | 0.00 | 0.268662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.343449E+10 | 59258277.86 | 0.00 | 0.00 | 0.513055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.406351E+10 | 75119906.61 | 0.00 | 0.00 | 0.703511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262893E+10 | 0.268584E+09 | 0.00 | 0.00 | 0.256931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161775E+10 | 0.115531E+10 | 0.00 | 0.00 | 0.391604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105930E+10 | 0.636106E+10 | 0.00 | 0.00 | 68107196.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101425E+10 | 0.126345E+11 | 0.00 | 0.00 | 64340.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234234E+11 | 0.551434E+11 | 0.00 | 0.00 | 0.200910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.935231E+09 | 59258277.86 | 0.00 | 0.00 | 64340.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.406351E+10 | 0.178106E+11 | 0.00 | 0.00 | 0.703511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.102972E+10 | 0.144873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.916932E+09 | 0.728302E+10 | 0.00 | 0.00 | 41897086.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116560E+10 | 0.290946E+10 | 0.00 | 0.00 | 66132181.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149750E+10 | 0.114637E+10 | 0.00 | 0.00 | 0.719049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.216092E+10 | 0.266696E+09 | 0.00 | 0.00 | 0.147414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.265417E+10 | 6214584.89 | 0.00 | 0.00 | 0.269764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.329845E+10 | 287190.76 | 0.00 | 0.00 | 0.501079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.374226E+10 | 745254.53 | 0.00 | 0.00 | 0.665536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238767E+10 | 33796827.07 | 0.00 | 0.00 | 0.246994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138703E+10 | 0.644482E+09 | 0.00 | 0.00 | 0.339169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.947561E+09 | 0.508948E+10 | 0.00 | 0.00 | 73348371.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.967788E+09 | 0.106011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221556E+11 | 0.424689E+11 | 0.00 | 0.00 | 0.195475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.916932E+09 | 287190.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.374226E+10 | 0.144873E+11 | 0.00 | 0.00 | 0.665536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.119159E+10 | 0.205177E+11 | 0.00 | 0.00 | 7192.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100361E+10 | 0.111238E+11 | 0.00 | 0.00 | 43522396.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120747E+10 | 0.439207E+10 | 0.00 | 0.00 | 95133935.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145399E+10 | 0.165071E+10 | 0.00 | 0.00 | 0.771074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203406E+10 | 0.421279E+09 | 0.00 | 0.00 | 0.155947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.247897E+10 | 20977070.95 | 0.00 | 0.00 | 0.286545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.312237E+10 | 305052.76 | 0.00 | 0.00 | 0.538859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.345357E+10 | 744260.61 | 0.00 | 0.00 | 0.706066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212761E+10 | 79640557.35 | 0.00 | 0.00 | 0.250179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129369E+10 | 0.132422E+10 | 0.00 | 0.00 | 0.319535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102934E+10 | 0.840489E+10 | 0.00 | 0.00 | 75570682.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108063E+10 | 0.165413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214769E+11 | 0.644777E+11 | 0.00 | 0.00 | 0.206808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100361E+10 | 305052.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.345357E+10 | 0.205177E+11 | 0.00 | 0.00 | 0.706066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108943E+11 | 0.00 | 0.00 | 572390.22 | 0.00 | 0.397440E+09 | 0.119369E+10 | 0.00 | 0.29 |
February | 0.696587E+10 | 0.00 | 0.00 | 4709196.11 | 0.00 | 0.00 | 0.460714E+10 | 0.00 | 0.31 |
March | 0.319009E+10 | 0.00 | 0.00 | 18507260.85 | 0.00 | 0.00 | 0.119102E+11 | 0.00 | 0.40 |
April | 0.841961E+09 | 8803372.91 | 0.00 | 26443828.56 | 1418311.19 | 0.00 | 0.141845E+11 | 0.00 | 0.50 |
May | 0.103789E+10 | 5760712.76 | 0.00 | 35768543.26 | 0.00 | 0.00 | 0.172734E+11 | 0.00 | 0.74 |
June | 0.858439E+09 | 6443937.65 | 0.00 | 37724552.25 | 1299169.44 | 0.00 | 0.163051E+11 | 0.00 | 0.89 |
July | 0.659284E+09 | 0.113055E+09 | 0.00 | 34399342.35 | 11040531.97 | 0.00 | 0.118541E+11 | 0.00 | 0.86 |
August | 0.518245E+09 | 0.337964E+09 | 0.00 | 33864572.85 | 13443188.26 | 0.00 | 0.103759E+11 | 0.00 | 0.84 |
September | 0.844605E+09 | 5477883.71 | 0.00 | 35298124.00 | 0.00 | 0.00 | 0.150501E+11 | 0.00 | 0.82 |
October | 0.111748E+10 | 0.00 | 0.00 | 27201692.87 | 0.00 | 0.00 | 0.152863E+11 | 0.00 | 0.54 |
November | 0.442368E+10 | 0.00 | 0.00 | 11478944.49 | 0.00 | 0.00 | 0.861494E+10 | 0.00 | 0.35 |
December | 0.869469E+10 | 0.00 | 0.00 | 3698080.43 | 0.00 | 0.00 | 0.388982E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.400465E+11 | 0.477505E+09 | 0.00 | 0.269667E+09 | 27201200.87 | 0.397440E+09 | 0.130545E+12 | 0.00 | 0.57 |
Minimum of Months | 0.518245E+09 | 0.00 | 0.00 | 572390.22 | 0.00 | 0.00 | 0.119369E+10 | 0.00 | 0.29 |
Maximum of Months | 0.108943E+11 | 0.337964E+09 | 0.00 | 37724552.25 | 13443188.26 | 0.397440E+09 | 0.172734E+11 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750788E+09 | 0.00 | 0.00 | 0.29 |
February | 0.104885E+11 | 0.00 | 0.00 | 199597.01 | 0.00 | 42720703.65 | 0.452547E+09 | 0.00 | 0.30 |
March | 0.841743E+10 | 0.00 | 0.00 | 3741813.35 | 0.00 | 574920.31 | 0.411308E+10 | 0.00 | 0.34 |
April | 0.466972E+10 | 4856460.13 | 0.00 | 11339514.55 | 4740212.05 | 0.00 | 0.715795E+10 | 0.00 | 0.39 |
May | 0.244011E+10 | 4011372.69 | 0.00 | 21399029.44 | 0.00 | 0.00 | 0.115842E+11 | 0.00 | 0.57 |
June | 0.126122E+10 | 4351513.83 | 0.00 | 25827852.04 | 1269929.32 | 0.00 | 0.119459E+11 | 0.00 | 0.69 |
July | 0.110859E+10 | 93291228.41 | 0.00 | 24445155.94 | 8566206.67 | 0.00 | 0.854352E+10 | 0.00 | 0.67 |
August | 0.811931E+09 | 0.281963E+09 | 0.00 | 23512109.98 | 10118731.06 | 0.00 | 0.747187E+10 | 0.00 | 0.65 |
September | 0.199593E+10 | 3550237.40 | 0.00 | 21069928.77 | 646958.21 | 0.00 | 0.959977E+10 | 0.00 | 0.61 |
October | 0.501284E+10 | 0.00 | 0.00 | 10101551.47 | 0.00 | 0.00 | 0.713772E+10 | 0.00 | 0.40 |
November | 0.962352E+10 | 0.00 | 0.00 | 1541555.13 | 0.00 | 3392800.86 | 0.167076E+10 | 0.00 | 0.31 |
December | 0.117992E+11 | 0.00 | 0.00 | 5934.08 | 0.00 | 0.190228E+09 | 88732289.08 | 0.00 | 0.28 |
Annual Sum or Average | 0.692916E+11 | 0.392024E+09 | 0.00 | 0.143184E+09 | 25342037.31 | 0.987704E+09 | 0.697660E+11 | 0.00 | 0.46 |
Minimum of Months | 0.811931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.117992E+11 | 0.281963E+09 | 0.00 | 25827852.04 | 10118731.06 | 0.750788E+09 | 0.119459E+11 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.955784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211307E+10 | 0.00 | 0.00 | 0.28 |
February | 0.953370E+10 | 0.00 | 0.00 | 89337.73 | 0.00 | 0.641545E+09 | 0.147726E+09 | 0.00 | 0.30 |
March | 0.100049E+11 | 0.00 | 0.00 | 1489168.24 | 0.00 | 44311438.27 | 0.177177E+10 | 0.00 | 0.33 |
April | 0.575108E+10 | 1247583.92 | 0.00 | 8062704.64 | 87884.81 | 0.00 | 0.554872E+10 | 0.00 | 0.39 |
May | 0.353050E+10 | 1097859.88 | 0.00 | 18231963.77 | 0.00 | 0.00 | 0.100240E+11 | 0.00 | 0.55 |
June | 0.199612E+10 | 1378395.72 | 0.00 | 22998591.52 | 782505.81 | 0.00 | 0.109679E+11 | 0.00 | 0.68 |
July | 0.165197E+10 | 75963775.79 | 0.00 | 21816325.22 | 11359672.39 | 0.00 | 0.788609E+10 | 0.00 | 0.68 |
August | 0.122296E+10 | 0.216778E+09 | 0.00 | 20805605.26 | 25922732.91 | 0.00 | 0.633584E+10 | 0.00 | 0.64 |
September | 0.306601E+10 | 990512.11 | 0.00 | 15463688.01 | 0.00 | 0.00 | 0.735256E+10 | 0.00 | 0.57 |
October | 0.675337E+10 | 0.00 | 0.00 | 5116726.32 | 0.00 | 2141731.17 | 0.400154E+10 | 0.00 | 0.37 |
November | 0.960557E+10 | 0.00 | 0.00 | 207139.45 | 0.00 | 0.273378E+09 | 0.474704E+09 | 0.00 | 0.30 |
December | 0.987025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129907E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.725442E+11 | 0.297456E+09 | 0.00 | 0.114281E+09 | 38152795.92 | 0.437351E+10 | 0.545109E+11 | 0.00 | 0.45 |
Minimum of Months | 0.122296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.100049E+11 | 0.216778E+09 | 0.00 | 22998591.52 | 25922732.91 | 0.211307E+10 | 0.109679E+11 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.650547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187994E+10 | 0.00 | 0.00 | 0.29 |
February | 0.105662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114844E+10 | 0.00 | 0.00 | 0.30 |
March | 0.214345E+10 | 0.00 | 0.00 | 31675.84 | 0.00 | 0.256927E+09 | 88173293.20 | 0.00 | 0.33 |
April | 0.154715E+10 | 361577.77 | 0.00 | 1256776.03 | 18503.29 | 49407307.82 | 0.769233E+09 | 0.00 | 0.39 |
May | 0.986746E+09 | 502339.30 | 0.00 | 4106568.55 | 0.00 | 272341.45 | 0.210206E+10 | 0.00 | 0.63 |
June | 0.551605E+09 | 426205.15 | 0.00 | 5732373.66 | 164748.99 | 0.00 | 0.252886E+10 | 0.00 | 0.82 |
July | 0.428118E+09 | 23895774.68 | 0.00 | 5658107.76 | 2391668.54 | 0.00 | 0.192823E+10 | 0.00 | 0.84 |
August | 0.378725E+09 | 67140185.69 | 0.00 | 4810579.71 | 5388008.27 | 0.00 | 0.135264E+10 | 0.00 | 0.75 |
September | 0.977406E+09 | 270869.08 | 0.00 | 2831655.31 | 0.00 | 631241.55 | 0.120443E+10 | 0.00 | 0.59 |
October | 0.175695E+10 | 0.00 | 0.00 | 438545.92 | 0.00 | 77822524.31 | 0.349836E+09 | 0.00 | 0.36 |
November | 0.135485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840015E+09 | 0.00 | 0.00 | 0.30 |
December | 0.739221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165838E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.125714E+11 | 92596951.67 | 0.00 | 24866282.78 | 7962929.10 | 0.591183E+10 | 0.103235E+11 | 0.00 | 0.49 |
Minimum of Months | 0.378725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.214345E+10 | 67140185.69 | 0.00 | 5732373.66 | 5388008.27 | 0.187994E+10 | 0.252886E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.544792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109510E+10 | 0.00 | 0.00 | 0.30 |
February | 0.779980E+09 | 0.00 | 0.00 | 9793.17 | 0.00 | 0.615839E+09 | 15764674.95 | 0.00 | 0.30 |
March | 0.113980E+10 | 0.00 | 0.00 | 700754.65 | 0.00 | 0.118185E+09 | 0.456132E+09 | 0.00 | 0.36 |
April | 0.688549E+09 | 322462.24 | 0.00 | 3041994.47 | 0.00 | 17314127.20 | 0.157897E+10 | 0.00 | 0.61 |
May | 0.485240E+09 | 445400.56 | 0.00 | 5139814.41 | 0.00 | 209621.03 | 0.246164E+10 | 0.00 | 0.94 |
June | 0.244684E+09 | 295030.44 | 0.00 | 7227807.37 | 104783.99 | 0.00 | 0.313756E+10 | 0.00 | 1.34 |
July | 0.192112E+09 | 20738728.09 | 0.00 | 7334442.26 | 534482.89 | 0.00 | 0.220749E+10 | 0.00 | 1.33 |
August | 0.155512E+09 | 60108714.35 | 0.00 | 6760137.53 | 1064135.77 | 0.00 | 0.170579E+10 | 0.00 | 1.29 |
September | 0.475284E+09 | 300966.93 | 0.00 | 4326588.79 | 0.00 | 401483.56 | 0.171760E+10 | 0.00 | 0.95 |
October | 0.894931E+09 | 0.00 | 0.00 | 1299734.19 | 0.00 | 50281471.39 | 0.774902E+09 | 0.00 | 0.45 |
November | 0.908085E+09 | 0.00 | 0.00 | 6637.37 | 0.00 | 0.480910E+09 | 11963616.43 | 0.00 | 0.30 |
December | 0.587122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963185E+09 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.709609E+10 | 82211302.62 | 0.00 | 35847704.21 | 1703402.65 | 0.334143E+10 | 0.140678E+11 | 0.00 | 0.71 |
Minimum of Months | 0.155512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.113980E+10 | 60108714.35 | 0.00 | 7334442.26 | 1064135.77 | 0.109510E+10 | 0.313756E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107658E+10 | 0.00 | 0.00 | 349431.61 | 0.00 | 0.134512E+10 | 0.224010E+09 | 0.00 | 0.30 |
February | 0.116894E+10 | 0.00 | 0.00 | 1945387.17 | 0.00 | 0.659345E+09 | 0.101250E+10 | 0.00 | 0.39 |
March | 0.153295E+10 | 0.00 | 0.00 | 4621614.09 | 0.00 | 0.188187E+09 | 0.238197E+10 | 0.00 | 0.55 |
April | 0.104118E+10 | 1010295.59 | 0.00 | 6240978.93 | 0.00 | 45326409.92 | 0.315469E+10 | 0.00 | 0.75 |
May | 0.822344E+09 | 944822.84 | 0.00 | 8332078.88 | 0.00 | 304119.89 | 0.392595E+10 | 0.00 | 0.98 |
June | 0.523634E+09 | 533451.14 | 0.00 | 8646070.82 | 165491.47 | 0.00 | 0.366186E+10 | 0.00 | 1.13 |
July | 0.406509E+09 | 44214226.84 | 0.00 | 9133104.17 | 344384.88 | 0.00 | 0.283451E+10 | 0.00 | 1.23 |
August | 0.332400E+09 | 0.137435E+09 | 0.00 | 8594097.00 | 844775.99 | 0.00 | 0.214262E+10 | 0.00 | 1.17 |
September | 0.706598E+09 | 1434011.32 | 0.00 | 9806666.46 | 0.00 | 0.00 | 0.353232E+10 | 0.00 | 1.28 |
October | 0.121096E+10 | 0.00 | 0.00 | 5426745.44 | 0.00 | 58769943.25 | 0.302540E+10 | 0.00 | 0.75 |
November | 0.138263E+10 | 0.00 | 0.00 | 1076839.82 | 0.00 | 0.615053E+09 | 0.455328E+09 | 0.00 | 0.36 |
December | 0.101714E+10 | 0.00 | 0.00 | 981388.17 | 0.00 | 0.117030E+10 | 0.513165E+09 | 0.00 | 0.32 |
Annual Sum or Average | 0.112219E+11 | 0.185571E+09 | 0.00 | 65154402.56 | 1354652.35 | 0.408241E+10 | 0.268643E+11 | 0.00 | 0.77 |
Minimum of Months | 0.332400E+09 | 0.00 | 0.00 | 349431.61 | 0.00 | 0.00 | 0.224010E+09 | 0.00 | 0.30 |
Maximum of Months | 0.153295E+10 | 0.137435E+09 | 0.00 | 9806666.46 | 844775.99 | 0.134512E+10 | 0.392595E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.497082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114420E+10 | 0.00 | 0.00 | 0.30 |
February | 0.689946E+09 | 0.00 | 0.00 | 152888.24 | 0.00 | 0.644381E+09 | 0.116127E+09 | 0.00 | 0.32 |
March | 0.113920E+10 | 0.00 | 0.00 | 921820.78 | 0.00 | 0.163966E+09 | 0.573499E+09 | 0.00 | 0.40 |
April | 0.799867E+09 | 548572.25 | 0.00 | 2620604.87 | 0.00 | 33946917.67 | 0.135758E+10 | 0.00 | 0.62 |
May | 0.500633E+09 | 403772.02 | 0.00 | 6171425.44 | 0.00 | 902219.62 | 0.244775E+10 | 0.00 | 1.03 |
June | 0.311102E+09 | 1098810.16 | 0.00 | 6232717.80 | 104532.38 | 0.00 | 0.236015E+10 | 0.00 | 1.24 |
July | 0.235286E+09 | 41535712.61 | 0.00 | 7595475.06 | 428260.60 | 0.00 | 0.198760E+10 | 0.00 | 1.43 |
August | 0.204648E+09 | 93152900.28 | 0.00 | 5609668.33 | 1650990.81 | 0.00 | 0.128108E+10 | 0.00 | 1.10 |
September | 0.483727E+09 | 522466.30 | 0.00 | 4565240.78 | 0.00 | 197784.34 | 0.159263E+10 | 0.00 | 1.01 |
October | 0.977852E+09 | 0.00 | 0.00 | 1190999.13 | 0.00 | 54468620.15 | 0.718677E+09 | 0.00 | 0.48 |
November | 0.849418E+09 | 0.00 | 0.00 | 70593.93 | 0.00 | 0.512436E+09 | 42051308.76 | 0.00 | 0.31 |
December | 0.535679E+09 | 0.00 | 0.00 | 4835.15 | 0.00 | 0.100645E+10 | 5437696.91 | 0.00 | 0.29 |
Annual Sum or Average | 0.722444E+10 | 0.137262E+09 | 0.00 | 35136269.52 | 2183783.79 | 0.356095E+10 | 0.124826E+11 | 0.00 | 0.71 |
Minimum of Months | 0.204648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.113920E+10 | 93152900.28 | 0.00 | 7595475.06 | 1650990.81 | 0.114420E+10 | 0.244775E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.756202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189920E+10 | 0.00 | 0.00 | 0.29 |
February | 0.134186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102899E+10 | 0.00 | 0.00 | 0.30 |
March | 0.242797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147526E+09 | 0.00 | 0.00 | 0.32 |
April | 0.195690E+10 | 923713.00 | 0.00 | 220373.33 | 834962.95 | 9123150.11 | 0.196356E+09 | 0.00 | 0.33 |
May | 0.123493E+10 | 1137555.69 | 0.00 | 2209320.80 | 0.00 | 0.00 | 0.119277E+10 | 0.00 | 0.48 |
June | 0.626148E+09 | 1158038.40 | 0.00 | 3970338.70 | 273510.45 | 0.00 | 0.177103E+10 | 0.00 | 0.63 |
July | 0.382331E+09 | 23323625.25 | 0.00 | 4457509.74 | 2324331.83 | 0.00 | 0.150675E+10 | 0.00 | 0.66 |
August | 0.389819E+09 | 70315560.95 | 0.00 | 3847007.93 | 2830156.23 | 0.00 | 0.117171E+10 | 0.00 | 0.62 |
September | 0.999356E+09 | 851646.60 | 0.00 | 2338944.64 | 8618.10 | 0.00 | 0.105770E+10 | 0.00 | 0.53 |
October | 0.194779E+10 | 0.00 | 0.00 | 409824.11 | 0.00 | 394730.12 | 0.315446E+09 | 0.00 | 0.35 |
November | 0.201183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360609E+09 | 0.00 | 0.00 | 0.30 |
December | 0.126797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133552E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.153431E+11 | 97710139.89 | 0.00 | 17453319.25 | 6271579.56 | 0.478136E+10 | 0.721176E+10 | 0.00 | 0.43 |
Minimum of Months | 0.382331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.242797E+10 | 70315560.95 | 0.00 | 4457509.74 | 2830156.23 | 0.189920E+10 | 0.177103E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.637084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108836E+10 | 0.00 | 0.00 | 0.29 |
February | 0.103013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480871E+09 | 0.00 | 0.00 | 0.30 |
March | 0.141688E+10 | 0.00 | 0.00 | 302232.33 | 0.00 | 33469425.31 | 0.228692E+09 | 0.00 | 0.33 |
April | 0.784903E+09 | 1202747.08 | 0.00 | 2196252.93 | 529202.67 | 2693612.54 | 0.107063E+10 | 0.00 | 0.48 |
May | 0.521265E+09 | 1310953.75 | 0.00 | 3860460.06 | 0.00 | 0.00 | 0.181224E+10 | 0.00 | 0.76 |
June | 0.233995E+09 | 1027445.69 | 0.00 | 6074838.51 | 173351.96 | 0.00 | 0.256261E+10 | 0.00 | 1.15 |
July | 0.146202E+09 | 26015700.09 | 0.00 | 6099847.94 | 1353940.21 | 0.00 | 0.186891E+10 | 0.00 | 1.13 |
August | 0.132783E+09 | 76267473.07 | 0.00 | 6040776.59 | 966783.42 | 0.00 | 0.162653E+10 | 0.00 | 1.15 |
September | 0.423480E+09 | 1054543.25 | 0.00 | 4218246.52 | 0.00 | 0.00 | 0.166444E+10 | 0.00 | 0.89 |
October | 0.946254E+09 | 0.00 | 0.00 | 1467879.87 | 0.00 | 93501.98 | 0.840440E+09 | 0.00 | 0.45 |
November | 0.129954E+10 | 0.00 | 0.00 | 8709.09 | 0.00 | 0.198126E+09 | 10287146.98 | 0.00 | 0.30 |
December | 0.903884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765040E+09 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.847639E+10 | 0.106879E+09 | 0.00 | 30269243.83 | 3023278.26 | 0.256866E+10 | 0.116848E+11 | 0.00 | 0.63 |
Minimum of Months | 0.132783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.141688E+10 | 76267473.07 | 0.00 | 6099847.94 | 1353940.21 | 0.108836E+10 | 0.256261E+10 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.531111E+09 | 0.00 | 0.00 | 4222.33 | 0.00 | 0.348001E+10 | 12614627.44 | 0.00 | 0.43 |
February | 0.107055E+10 | 0.00 | 0.00 | 229836.76 | 0.00 | 0.212078E+10 | 0.164085E+09 | 0.00 | 0.42 |
March | 0.172004E+10 | 0.00 | 0.00 | 955285.21 | 0.00 | 0.126758E+10 | 0.609160E+09 | 0.00 | 0.46 |
April | 0.143062E+10 | 5495217.25 | 0.00 | 1704189.77 | 0.00 | 0.675340E+09 | 0.849796E+09 | 0.00 | 0.50 |
May | 0.136607E+10 | 2575398.39 | 0.00 | 2854542.40 | 0.00 | 0.396835E+09 | 0.125357E+10 | 0.00 | 0.64 |
June | 0.967463E+09 | 1751089.61 | 0.00 | 3863635.72 | 273618.62 | 0.193970E+09 | 0.145836E+10 | 0.00 | 0.74 |
July | 0.512526E+09 | 51219493.63 | 0.00 | 5469182.76 | 1959362.41 | 42108482.77 | 0.158629E+10 | 0.00 | 0.87 |
August | 0.489617E+09 | 0.173282E+09 | 0.00 | 5718341.02 | 1347123.58 | 43339184.41 | 0.134842E+10 | 0.00 | 0.92 |
September | 0.862532E+09 | 4616893.39 | 0.00 | 6864633.44 | 0.00 | 0.165804E+09 | 0.218654E+10 | 0.00 | 1.03 |
October | 0.134399E+10 | 0.00 | 0.00 | 3153371.55 | 0.00 | 0.569465E+09 | 0.180376E+10 | 0.00 | 0.63 |
November | 0.140262E+10 | 0.00 | 0.00 | 317138.32 | 0.00 | 0.180533E+10 | 99067595.58 | 0.00 | 0.42 |
December | 0.818467E+09 | 0.00 | 0.00 | 191872.30 | 0.00 | 0.294587E+10 | 0.132027E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.125156E+11 | 0.238940E+09 | 0.00 | 31326251.56 | 3580104.60 | 0.137064E+11 | 0.115037E+11 | 0.00 | 0.62 |
Minimum of Months | 0.489617E+09 | 0.00 | 0.00 | 4222.33 | 0.00 | 42108482.77 | 12614627.44 | 0.00 | 0.41 |
Maximum of Months | 0.172004E+10 | 0.173282E+09 | 0.00 | 6864633.44 | 1959362.41 | 0.348001E+10 | 0.218654E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.582354E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114339E+10 | 0.00 | 0.00 | 0.29 |
February | 0.988293E+09 | 0.00 | 0.00 | 50646.84 | 0.00 | 0.484018E+09 | 42846764.07 | 0.00 | 0.31 |
March | 0.139896E+10 | 0.00 | 0.00 | 395507.58 | 0.00 | 69696307.12 | 0.254460E+09 | 0.00 | 0.35 |
April | 0.923662E+09 | 2100738.76 | 0.00 | 1559428.76 | 177885.20 | 4969244.14 | 0.787016E+09 | 0.00 | 0.46 |
May | 0.483292E+09 | 1170157.71 | 0.00 | 4431946.20 | 0.00 | 0.00 | 0.180101E+10 | 0.00 | 0.81 |
June | 0.261120E+09 | 3111112.73 | 0.00 | 5105442.47 | 172872.30 | 0.00 | 0.191949E+10 | 0.00 | 1.01 |
July | 0.142258E+09 | 43096734.43 | 0.00 | 5969103.93 | 411881.79 | 0.00 | 0.178617E+10 | 0.00 | 1.22 |
August | 0.154155E+09 | 0.101514E+09 | 0.00 | 5131517.74 | 1360793.86 | 0.00 | 0.128537E+10 | 0.00 | 1.00 |
September | 0.366696E+09 | 1562771.72 | 0.00 | 4353625.29 | 0.00 | 0.00 | 0.157256E+10 | 0.00 | 0.92 |
October | 0.996483E+09 | 0.00 | 0.00 | 1247531.17 | 0.00 | 0.00 | 0.744254E+09 | 0.00 | 0.46 |
November | 0.126113E+10 | 0.00 | 0.00 | 48886.91 | 0.00 | 0.208882E+09 | 36623400.23 | 0.00 | 0.30 |
December | 0.887818E+09 | 0.00 | 0.00 | 653.58 | 0.00 | 0.776886E+09 | 2825000.27 | 0.00 | 0.28 |
Annual Sum or Average | 0.844622E+10 | 0.152556E+09 | 0.00 | 28294290.45 | 2123433.16 | 0.268784E+10 | 0.102326E+11 | 0.00 | 0.62 |
Minimum of Months | 0.142258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.139896E+10 | 0.101514E+09 | 0.00 | 5969103.93 | 1360793.86 | 0.114339E+10 | 0.191949E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156998E+10 | 0.00 | 0.00 | 0.29 |
February | 0.169755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630581E+09 | 0.00 | 0.00 | 0.30 |
March | 0.243374E+10 | 0.00 | 0.00 | 62282.43 | 0.00 | 59030426.53 | 0.125405E+09 | 0.00 | 0.33 |
April | 0.150781E+10 | 1431924.74 | 0.00 | 1516473.37 | 999518.95 | 1168387.77 | 0.909656E+09 | 0.00 | 0.39 |
May | 0.861503E+09 | 1701518.36 | 0.00 | 4554277.70 | 0.00 | 0.00 | 0.224248E+10 | 0.00 | 0.63 |
June | 0.436426E+09 | 1444263.67 | 0.00 | 6181030.71 | 267776.72 | 0.00 | 0.263788E+10 | 0.00 | 0.82 |
July | 0.308608E+09 | 30469526.00 | 0.00 | 5981538.78 | 1806266.44 | 0.00 | 0.200846E+10 | 0.00 | 0.83 |
August | 0.300132E+09 | 89082448.28 | 0.00 | 5116083.90 | 2133631.03 | 0.00 | 0.153105E+10 | 0.00 | 0.74 |
September | 0.851398E+09 | 1078309.79 | 0.00 | 3451623.31 | 0.00 | 0.00 | 0.146176E+10 | 0.00 | 0.61 |
October | 0.182679E+10 | 0.00 | 0.00 | 754569.56 | 0.00 | 3097354.28 | 0.533957E+09 | 0.00 | 0.37 |
November | 0.196314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414009E+09 | 0.00 | 0.00 | 0.31 |
December | 0.135334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120964E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.146055E+11 | 0.125208E+09 | 0.00 | 27617879.76 | 5207193.14 | 0.388750E+10 | 0.114506E+11 | 0.00 | 0.49 |
Minimum of Months | 0.300132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.243374E+10 | 89082448.28 | 0.00 | 6181030.71 | 2133631.03 | 0.156998E+10 | 0.263788E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.567322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846587E+09 | 0.00 | 0.00 | 0.24 |
February | 0.850850E+09 | 0.00 | 0.00 | 45104.05 | 0.00 | 0.326042E+09 | 47687094.56 | 0.00 | 0.25 |
March | 0.104771E+10 | 0.00 | 0.00 | 969824.45 | 0.00 | 24475650.16 | 0.555716E+09 | 0.00 | 0.32 |
April | 0.580668E+09 | 1716998.25 | 0.00 | 3226723.68 | 2162.31 | 668763.76 | 0.161715E+10 | 0.00 | 0.57 |
May | 0.423800E+09 | 1426995.73 | 0.00 | 5118737.95 | 0.00 | 0.00 | 0.231980E+10 | 0.00 | 0.89 |
June | 0.212925E+09 | 991876.17 | 0.00 | 7125007.02 | 169116.56 | 0.00 | 0.294735E+10 | 0.00 | 1.26 |
July | 0.149488E+09 | 25302031.37 | 0.00 | 7086694.25 | 971692.29 | 0.00 | 0.208867E+10 | 0.00 | 1.23 |
August | 0.131365E+09 | 74447378.94 | 0.00 | 6634150.99 | 666035.37 | 0.00 | 0.174116E+10 | 0.00 | 1.21 |
September | 0.388971E+09 | 929086.25 | 0.00 | 4568722.25 | 382.05 | 0.00 | 0.176961E+10 | 0.00 | 0.92 |
October | 0.796093E+09 | 0.00 | 0.00 | 1598460.88 | 0.00 | 1613052.54 | 0.911644E+09 | 0.00 | 0.43 |
November | 0.965696E+09 | 0.00 | 0.00 | 48543.08 | 0.00 | 0.244948E+09 | 40237007.99 | 0.00 | 0.25 |
December | 0.714522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655440E+09 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.682941E+10 | 0.104814E+09 | 0.00 | 36421968.59 | 1809388.58 | 0.209977E+10 | 0.140390E+11 | 0.00 | 0.65 |
Minimum of Months | 0.131365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.104771E+10 | 74447378.94 | 0.00 | 7125007.02 | 971692.29 | 0.846587E+09 | 0.294735E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140845E+10 | 0.00 | 0.00 | 556890.94 | 0.00 | 0.104471E+10 | 0.334391E+09 | 0.00 | 0.31 |
February | 0.151364E+10 | 0.00 | 0.00 | 2363408.53 | 0.00 | 0.392483E+09 | 0.117068E+10 | 0.00 | 0.41 |
March | 0.171129E+10 | 0.00 | 0.00 | 5330195.10 | 0.00 | 37554039.90 | 0.263754E+10 | 0.00 | 0.58 |
April | 0.101671E+10 | 8062423.32 | 0.00 | 6603201.61 | 0.00 | 815145.27 | 0.323838E+10 | 0.00 | 0.75 |
May | 0.729626E+09 | 3197633.07 | 0.00 | 8686776.60 | 0.00 | 0.00 | 0.388249E+10 | 0.00 | 0.99 |
June | 0.451490E+09 | 1769095.85 | 0.00 | 8885574.42 | 267060.68 | 0.00 | 0.357554E+10 | 0.00 | 1.11 |
July | 0.323665E+09 | 52535510.98 | 0.00 | 8853768.70 | 1499145.27 | 0.00 | 0.271790E+10 | 0.00 | 1.18 |
August | 0.273326E+09 | 0.175467E+09 | 0.00 | 8452142.34 | 816483.48 | 0.00 | 0.221008E+10 | 0.00 | 1.13 |
September | 0.587819E+09 | 5617624.10 | 0.00 | 10502758.82 | 0.00 | 0.00 | 0.364662E+10 | 0.00 | 1.31 |
October | 0.121755E+10 | 0.00 | 0.00 | 6434252.98 | 0.00 | 911021.77 | 0.340263E+10 | 0.00 | 0.80 |
November | 0.181384E+10 | 0.00 | 0.00 | 1499284.22 | 0.00 | 0.247117E+09 | 0.664616E+09 | 0.00 | 0.38 |
December | 0.149754E+10 | 0.00 | 0.00 | 1343793.77 | 0.00 | 0.787578E+09 | 0.691569E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.125449E+11 | 0.246650E+09 | 0.00 | 69512048.02 | 2582689.43 | 0.251117E+10 | 0.281724E+11 | 0.00 | 0.78 |
Minimum of Months | 0.273326E+09 | 0.00 | 0.00 | 556890.94 | 0.00 | 0.00 | 0.334391E+09 | 0.00 | 0.31 |
Maximum of Months | 0.181384E+10 | 0.175467E+09 | 0.00 | 10502758.82 | 1499145.27 | 0.104471E+10 | 0.388249E+10 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.755483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947825E+09 | 0.00 | 0.00 | 0.30 |
February | 0.104376E+10 | 0.00 | 0.00 | 188344.89 | 0.00 | 0.350130E+09 | 0.139157E+09 | 0.00 | 0.32 |
March | 0.131714E+10 | 0.00 | 0.00 | 1049428.41 | 0.00 | 42535498.16 | 0.619769E+09 | 0.00 | 0.41 |
April | 0.784104E+09 | 3791826.76 | 0.00 | 2773985.20 | 98486.77 | 1713639.49 | 0.139005E+10 | 0.00 | 0.60 |
May | 0.432744E+09 | 1465029.27 | 0.00 | 6459171.13 | 0.00 | 0.00 | 0.242037E+10 | 0.00 | 1.04 |
June | 0.251773E+09 | 3776666.27 | 0.00 | 6384373.35 | 169701.44 | 0.00 | 0.232698E+10 | 0.00 | 1.21 |
July | 0.175876E+09 | 51530453.50 | 0.00 | 6738026.90 | 277484.53 | 0.00 | 0.191310E+10 | 0.00 | 1.37 |
August | 0.167690E+09 | 0.121679E+09 | 0.00 | 5586869.22 | 1150953.04 | 0.00 | 0.134268E+10 | 0.00 | 1.08 |
September | 0.402428E+09 | 2053476.67 | 0.00 | 4983902.23 | 0.00 | 0.00 | 0.170777E+10 | 0.00 | 1.03 |
October | 0.100552E+10 | 0.00 | 0.00 | 1502426.61 | 0.00 | 907515.57 | 0.871199E+09 | 0.00 | 0.50 |
November | 0.120884E+10 | 0.00 | 0.00 | 105400.48 | 0.00 | 0.254716E+09 | 60303341.50 | 0.00 | 0.31 |
December | 0.922091E+09 | 0.00 | 0.00 | 15499.66 | 0.00 | 0.704885E+09 | 20373250.69 | 0.00 | 0.29 |
Annual Sum or Average | 0.846745E+10 | 0.184297E+09 | 0.00 | 35787428.11 | 1696625.78 | 0.230271E+10 | 0.128118E+11 | 0.00 | 0.71 |
Minimum of Months | 0.167690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.131714E+10 | 0.121679E+09 | 0.00 | 6738026.90 | 1150953.04 | 0.947825E+09 | 0.242037E+10 | 0.00 | 1.37 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:59
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.587942E+11 | 0.927402E+10 | 0.00 | 0.137176E+12 | 0.177892E+11 |
February | 0.121695E+12 | 0.838203E+10 | 0.00 | 0.147082E+12 | 0.108040E+11 |
March | 0.216339E+12 | 0.852953E+10 | 0.00 | 0.187002E+12 | 0.595526E+10 |
April | 0.336717E+12 | 0.743007E+10 | 0.00 | 0.209550E+12 | 0.140333E+11 |
May | 0.439866E+12 | 0.614001E+10 | 0.00 | 0.224746E+12 | 0.255347E+11 |
June | 0.442213E+12 | 0.482931E+10 | 0.00 | 0.207754E+12 | 0.463222E+11 |
July | 0.469245E+12 | 0.348264E+10 | 0.00 | 0.205465E+12 | 0.880139E+11 |
August | 0.369521E+12 | 0.267970E+10 | 0.00 | 0.160434E+12 | 0.116841E+12 |
September | 0.263389E+12 | 0.347819E+10 | 0.00 | 0.213950E+12 | 0.429468E+11 |
October | 0.166943E+12 | 0.679406E+10 | 0.00 | 0.213342E+12 | 0.714435E+10 |
November | 0.683287E+11 | 0.800176E+10 | 0.00 | 0.173972E+12 | 0.973073E+10 |
December | 0.447754E+11 | 0.849722E+10 | 0.00 | 0.152630E+12 | 0.147266E+11 |
Annual Sum or Average | 0.299783E+13 | 0.775185E+11 | 0.00 | 0.223310E+13 | 0.399842E+12 |
Minimum of Months | 0.447754E+11 | 0.267970E+10 | 0.00 | 0.137176E+12 | 0.595526E+10 |
Maximum of Months | 0.469245E+12 | 0.927402E+10 | 0.00 | 0.224746E+12 | 0.116841E+12 |