Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21

Tabular Output Report in Format: HTML

Building: OfficeMedium

Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860

Simulation Timestamp: 2024-07-03 12:21:49


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1531.33 307.36 307.36
Net Site Energy 1395.26 280.05 280.05
Total Source Energy 4166.64 836.31 836.31
Net Source Energy 3735.69 749.81 749.81


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4982.19
Net Conditioned Building Area 4982.19
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 327.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 175.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 167.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 34.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 658.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 25.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 87.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 52.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1203.40 327.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 327.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 175.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 167.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 34.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 73.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 0.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 584.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 25.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 87.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 1.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
  Water Heater 52.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 327.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 175.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 167.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 34.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 658.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 25.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 87.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 1.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 52.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 40.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 63.85 65.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 137.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 241.54 65.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 40.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 63.85 65.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 137.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 241.54 65.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 142.412 11.83
Wind Power 0.000 0.00
Power Conversion -6.34 -0.5
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 136.076 11.31
     
Electricity Coming From Utility 1067.907 88.74
Surplus Electricity Going To Utility 0.587 0.05
Net Electricity From Utility 1067.320 88.69
     
Total On-Site and Utility Electric Sources 1203.396 100.00
Total Electricity End Uses 1203.396 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 271.06 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 271.06 100.00
Total Water End Uses 271.06 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 337.83
Time Setpoint Not Met During Occupied Cooling 122.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 2433.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneHeatingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneElectricSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

SpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EnergyConsumptionElectricityGeneratedPropaneMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ComfortReportSimple55Monthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

OccupantComfortDataSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

WindowEnergyZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

FanReportMonthly

| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |

PumpReportMonthly

| HEATSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AirLoopSystemEnergyAndWaterUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentLoadsMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentEnergyUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

MechanicalVentilationLoadsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
RunPeriod RUNPERIOD 1
Weather File New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Latitude [deg] 40.65
Longitude [deg] -73.8
Elevation [m] 5.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1660.73
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_BOTTOM 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 5.8040 18.58 61.8568
TOPFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
FIRSTFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
CORE_MID 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 5.8040 18.58 8.0700
CORE_TOP 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 5.8040 18.58 8.0700
PERIMETER_TOP_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 5.8040 18.58 8.0700
PERIMETER_TOP_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 5.8040 18.58 8.0695
PERIMETER_TOP_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 5.8040 18.58 8.0699
PERIMETER_TOP_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 5.8040 18.58 8.0700
PERIMETER_BOT_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 5.8040 18.58 8.0700
PERIMETER_BOT_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 5.8040 18.58 8.0695
PERIMETER_BOT_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 5.8040 18.58 8.0699
PERIMETER_BOT_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 5.8040 18.58 8.0700
PERIMETER_MID_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 5.8040 18.58 8.0700
PERIMETER_MID_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 5.8040 18.58 8.0695
PERIMETER_MID_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 5.8040 18.58 8.0699
PERIMETER_MID_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 5.8040 18.58 8.0700
Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 5.8040 18.58 18.6880
Conditioned Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 5.8040 18.58 18.6880
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 4982.19     6074.28   608.51 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_BOTTOM 983.54 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 5.8040 18.58 61.8568  
TOPFLOOR_PLENUM 1660.73 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 1660.73 Yes No 1.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
FIRSTFLOOR_PLENUM 1660.73 Yes No 1.00 FIRSTFLOOR_PLENUM GENERAL FIRSTFLOOR_PLENUM 0.0000 0.00 0.0000  
CORE_MID 983.54 Yes Yes 1.00 CORE_MID GENERAL CORE_MID 5.8040 18.58 8.0700  
CORE_TOP 983.54 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 5.8040 18.58 8.0700  
PERIMETER_TOP_ZN_3 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 5.8040 18.58 8.0700  
PERIMETER_TOP_ZN_2 131.26 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 5.8040 18.58 8.0695  
PERIMETER_TOP_ZN_1 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 5.8040 18.58 8.0699  
PERIMETER_TOP_ZN_4 131.25 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 5.8040 18.58 8.0700  
PERIMETER_BOT_ZN_3 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 5.8040 18.58 8.0700  
PERIMETER_BOT_ZN_2 131.26 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 5.8040 18.58 8.0695  
PERIMETER_BOT_ZN_1 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 5.8040 18.58 8.0699  
PERIMETER_BOT_ZN_4 131.25 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 5.8040 18.58 8.0700  
PERIMETER_MID_ZN_3 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 5.8040 18.58 8.0700  
PERIMETER_MID_ZN_2 131.26 Yes Yes 1.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 5.8040 18.58 8.0695  
PERIMETER_MID_ZN_1 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 5.8040 18.58 8.0699  
PERIMETER_MID_ZN_4 131.25 Yes Yes 1.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 5.8040 18.58 8.0700  
Total 4982.19             5.8040 9.29 18.6880  
Conditioned Total 4982.19             5.8040 9.29 18.6880  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 4982.19             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 4982.19 4982.19 0.00 4982.19 5.8040 18.58 18.6880
Total 4982.19 4982.19 0.00 4982.19      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 19-JUN-10:30 02-JAN-07:19 - - - - - - - - - - 02-JAN-12:09
Heating 0.00 234932.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 62643.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 13903.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 38858.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 24929.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 6.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4523.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 146275.93 234932.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 234932.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 62643.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 13903.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 4325.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 45.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 24929.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 6.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4523.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 355.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 556.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 528.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 107.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 2086.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 80.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 278.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 5.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 167.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 3811.16 355.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 71.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 111.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 106.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 21.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 418.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 16.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 55.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 33.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 764.96 71.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 71.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 111.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 106.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 21.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 418.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 16.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 55.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 33.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 764.96 71.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 2.19 0.341682 0.290000 0.636094 0.911151 0.500000 0.001115 0.000124 0.636094 12.80 0.008000
CORE_MID VAV BOX COMPONENT 1.92 0.390211 0.332000 0.637653 1.00 0.500000 0.000976 0.000178 0.637653 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 2.07 0.362845 0.308000 0.636173 0.967586 0.500000 0.001050 0.000304 1.03 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.652605 0.242094 0.206000 0.134437 0.645583 0.500000 0.001574 0.000143 0.486746 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 0.729729 0.137067 0.117000 0.085378 0.365512 0.500000 0.002780 0.000093 0.316080 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 0.892239 0.177073 0.151000 0.134728 0.472196 0.500000 0.002152 0.000142 0.482802 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 0.785539 0.127320 0.108000 0.084838 0.339521 0.500000 0.002992 0.000093 0.318472 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.514774 0.306915 0.261000 0.134356 0.818440 0.500000 0.001241 0.000110 0.374058 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.601937 0.166167 0.141000 0.084873 0.443111 0.500000 0.002293 0.000072 0.244314 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 0.720228 0.219363 0.186000 0.133962 0.584969 0.500000 0.001737 0.000109 0.370272 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 0.616957 0.162111 0.138000 0.085140 0.432295 0.500000 0.002350 0.000072 0.246731 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 0.565913 0.279180 0.237000 0.134121 0.744481 0.500000 0.001365 0.000113 0.385192 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 0.710815       0.375238 0.500000 0.002708 0.000074 0.251312 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 0.807919 0.195554 0.166000 0.134115 0.521477 0.500000 0.001948 0.000112 0.381342 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 0.725429 0.137870 0.117000 0.084875 0.367654 0.500000 0.002763 0.000074 0.253592 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 14179.00 0.000124 325.13
CORE_MID VAV BOX REHEAT COIL 20339.03 0.000178 524.92
CORE_TOP VAV BOX REHEAT COIL 34713.47 0.000304 916.46
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 16307.75 0.000143 430.04
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 10589.28 0.000093 279.24
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 16175.86 0.000142 426.57
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 10669.29 0.000093 281.34
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 12539.23 0.000110 330.75
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 8189.33 0.000072 216.00
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 12412.56 0.000109 327.41
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 8270.16 0.000072 218.13
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 12911.29 0.000113 340.55
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 8423.16 0.000074 222.16
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 12782.51 0.000112 337.15
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 8499.42 0.000074 224.17
PACU_VAV_BOT HEATING COIL 25001.33 0.000219 410.11
PACU_VAV_MID HEATING COIL 25295.42 0.000221 413.46
PACU_VAV_TOP HEATING COIL 24556.05 0.000215 408.02
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PACU_VAV_BOT 2.32 1.07 4.65 1.66 4.13 4.13 0.300000 0.401999 4.13
PACU_VAV_MID 2.37 1.08 4.73 1.86 4.02 4.02 0.300000 0.462240 4.02
PACU_VAV_TOP 2.56 1.08 5.13 2.64 4.69 4.69 0.300000 0.562910 4.69
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s]
PACU_VAV_BOT_OA_CONTROLLER 4.13
PACU_VAV_MID_OA_CONTROLLER 4.02
PACU_VAV_TOP_OA_CONTROLLER 4.69
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:TwoSpeed

Design Size High Speed Rated Air Flow Rate [m3/s] Design Size High Speed Gross Rated Total Cooling Capacity [W] Design Size High Speed Rated Sensible Heat Ratio Design Size Low Speed Rated Air Flow Rate [m3/s] Design Size Low Speed Gross Rated Total Cooling Capacity [W] Design Size Low Speed Gross Rated Sensible Heat Ratio
PACU_VAV_BOT COOLING COIL 4.13 90591.55 0.741425 1.38 30194.16 0.741425
PACU_VAV_MID COOLING COIL 4.02 89043.87 0.739100 1.34 29678.32 0.739100
PACU_VAV_TOP COOLING COIL 4.69 100003.11 0.751162 1.56 33331.04 0.751162
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
PACU_VAV_BOT FAN 4.13
PACU_VAV_MID FAN 4.02
PACU_VAV_TOP FAN 4.69
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s]
PACU_VAV_BOT_HEATC_CONTROLLER 0.000219
PACU_VAV_MID_HEATC_CONTROLLER 0.000221
PACU_VAV_TOP_HEATC_CONTROLLER 0.000215
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.002466 0.295894
SWHSYS1 0.000054 0.006435
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
HEATSYS1 PUMP 0.002466 735.23 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 281854.16 281854.16 0.002466
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000054 6.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000054
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 14.00 7.30 3.30 1.20 -0.20 5.60 10.90 16.10 21.70 25.00 24.80 19.90


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 40.65 -73.80 -5.00 5.00 101265 1.2036


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 12.47 25.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeMedium 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 18 167 24


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_BOTTOM 0.0 0.00 0.00 0.00 24.96 16.64 1.37 1 1 1 4.57 45.34 4.57 28.70 0.00 2.74 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
2 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 11.28 1 1 1 0.00 49.91 0.00 33.27 10.67 11.89 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 10 0 0 No
3 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 7.32 1 1 1 0.00 49.91 0.00 33.27 6.71 7.92 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
4 FIRSTFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 3.35 1 1 1 0.00 49.91 0.00 33.27 2.74 3.96 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
5 CORE_MID 0.0 0.00 0.00 0.00 24.96 16.64 5.33 1 1 1 4.57 45.34 4.57 28.70 3.96 6.71 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
6 CORE_TOP 0.0 0.00 0.00 0.00 24.96 16.64 9.30 1 1 1 4.57 45.34 4.57 28.70 7.92 10.67 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
7 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 9.30 1 1 1 0.00 49.91 28.70 33.27 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
8 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 9.30 1 1 1 45.34 49.91 0.00 33.27 7.92 10.67 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
9 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 9.30 1 1 1 0.00 49.91 0.00 4.57 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
10 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 9.30 1 1 1 0.00 4.57 0.00 33.27 7.92 10.67 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes
11 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 1.37 1 1 1 0.00 49.91 28.70 33.27 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
12 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 1.37 1 1 1 45.34 49.91 0.00 33.27 0.00 2.74 2.74 360.08 TARP TARP 131.26 91.28 45.82 43.51 6 3 0 Yes
13 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 1.37 1 1 1 0.00 49.91 0.00 4.57 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
14 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 1.37 1 1 1 0.00 4.57 0.00 33.27 0.00 2.74 2.74 360.05 TARP TARP 131.25 91.28 45.82 43.51 6 3 0 Yes
15 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 5.33 1 1 1 0.00 49.91 28.70 33.27 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
16 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 5.33 1 1 1 45.34 49.91 0.00 33.27 3.96 6.71 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
17 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 5.33 1 1 1 0.00 49.91 0.00 4.57 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
18 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 5.33 1 1 1 0.00 4.57 0.00 33.27 3.96 6.71 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_BOTTOM 983.54 52.9 18.579 5.382E-002 5.804 61.857 0.000 0.000 0.000 0.000 67.661 No
2 TOPFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 MIDFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
4 FIRSTFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
5 CORE_MID 983.54 52.9 18.579 5.382E-002 5.804 8.070 0.000 0.000 0.000 0.000 13.874 No
6 CORE_TOP 983.54 52.9 18.579 5.382E-002 5.804 8.070 0.000 0.000 0.000 0.000 13.874 No
7 PERIMETER_TOP_ZN_3 207.34 11.2 18.579 5.382E-002 5.804 8.070 0.000 0.000 0.000 0.000 13.874 No
8 PERIMETER_TOP_ZN_2 131.26 7.1 18.579 5.382E-002 5.804 8.069 0.000 0.000 0.000 0.000 13.873 No
9 PERIMETER_TOP_ZN_1 207.34 11.2 18.579 5.382E-002 5.804 8.070 0.000 0.000 0.000 0.000 13.874 No
10 PERIMETER_TOP_ZN_4 131.25 7.1 18.579 5.382E-002 5.804 8.070 0.000 0.000 0.000 0.000 13.874 No
11 PERIMETER_BOT_ZN_3 207.34 11.2 18.579 5.382E-002 5.804 8.070 0.000 0.000 0.000 0.000 13.874 No
12 PERIMETER_BOT_ZN_2 131.26 7.1 18.579 5.382E-002 5.804 8.069 0.000 0.000 0.000 0.000 13.873 No
13 PERIMETER_BOT_ZN_1 207.34 11.2 18.579 5.382E-002 5.804 8.070 0.000 0.000 0.000 0.000 13.874 No
14 PERIMETER_BOT_ZN_4 131.25 7.1 18.579 5.382E-002 5.804 8.070 0.000 0.000 0.000 0.000 13.874 No
15 PERIMETER_MID_ZN_3 207.34 11.2 18.579 5.382E-002 5.804 8.070 0.000 0.000 0.000 0.000 13.874 No
16 PERIMETER_MID_ZN_2 131.26 7.1 18.579 5.382E-002 5.804 8.069 0.000 0.000 0.000 0.000 13.873 No
17 PERIMETER_MID_ZN_1 207.34 11.2 18.579 5.382E-002 5.804 8.070 0.000 0.000 0.000 0.000 13.874 No
18 PERIMETER_MID_ZN_4 131.25 7.1 18.579 5.382E-002 5.804 8.070 0.000 0.000 0.000 0.000 13.874 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 983.54 52.9 5708.430 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 5708.430
2 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 983.54 52.9 5708.430 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 5708.430
3 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 983.54 52.9 5708.430 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 5708.430
4 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 207.34 11.2 1203.387 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1203.387
5 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 131.26 7.1 761.844 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 761.844
6 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 207.34 11.2 1203.387 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1203.387
7 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 131.25 7.1 761.794 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 761.794
8 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 207.34 11.2 1203.387 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1203.387
9 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 131.26 7.1 761.844 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 761.844
10 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 207.34 11.2 1203.387 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1203.387
11 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 131.25 7.1 761.794 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 761.794
12 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 207.34 11.2 1203.387 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1203.387
13 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 131.26 7.1 761.844 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 761.844
14 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 207.34 11.2 1203.387 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1203.387
15 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 131.25 7.1 761.794 5.804 107.831 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 761.794


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 ELEVATOR_LIFT_RUNNING ELEVATOR_RUNNING_SCH CORE_BOTTOM 983.54 52.9 51196.000 52.053 967.081 0.000 0.500 0.000 0.500 ElevatorLift 0.000 3043.602
2 ELEVATOR_LIFT_STANDBY ELEVATOR_STANDBY_SCH CORE_BOTTOM 983.54 52.9 1600.000 1.627 30.224 0.000 0.500 0.000 0.500 ElevatorLift 1281.968 1600.000
3 ELEVATORS_LIGHTS_FAN ELEV_LIGHT_FAN_SCH_ADD_DF CORE_BOTTOM 983.54 52.9 105.310 0.107 1.989 0.000 0.500 0.000 0.500 ElevatorLightsFan 0.000 72.664
4 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
5 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
6 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
7 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
8 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
9 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
10 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
11 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
12 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
13 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
14 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
15 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
16 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
17 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
18 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
7 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
8 NONRES_EXT_WALL_GRD 20 4 7 0.167 0.5960 0.900 0.900 0.700 0.700 Smooth
9 NONRES_EXT_WALL_MID 21 4 7 0.167 0.5902 0.900 0.900 0.700 0.700 Smooth
10 NONRES_EXT_WALL_TOP 22 4 7 0.167 0.7087 0.900 0.900 0.700 0.700 Smooth
11 PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 39 2 7 0.167 0.2242 0.000 0.900 0.000 0.700 MediumRough
12 PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 40 2 7 0.167 0.2365 0.000 0.900 0.000 0.700 MediumRough
13 PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 41 2 7 0.167 0.2242 0.000 0.900 0.000 0.700 MediumRough
14 PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 42 2 7 0.167 0.2366 0.000 0.900 0.000 0.700 MediumRough
15 CORE_BOT_ZN_5_FLOOR_FFACTOR 43 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
9 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
10 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
11 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
12 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
13 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.444
16 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
17 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
18 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.460
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 1.177
24 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
25 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 4.383
26 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
27 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 4.151
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 4.383
30 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
31 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 4.150
32 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
33 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 176.9
34 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
23 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
24 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
25 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
26 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
27 2 51.553741 0.22121684 1.2284947 -0.25833933
28 1 -128.86110 0.21944682 -5.1479470 1.1228340
29 0 81.526494 0.16043334E-01 4.4519351  
30 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
31 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
32 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
33 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
34 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
35 2 1.2284947 0.22121684 51.553741 -0.25833933
36 1 -5.1479470 0.21944682 -128.86110 1.1228340
37 0 4.4519351 0.16043334E-01 81.526494  
38 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
39 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
40 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
41 0 21.357363 0.71091016E-01 5.4032014  
42 7 -0.34210526E-12 0.10412655E-14 -0.10417952E-12 0.10409145E-15
43 6 0.30802088E-07 0.17108976E-09 0.70383009E-08 -0.14667926E-12
44 5 -0.20086572E-03 0.14450046E-05 -0.10316412E-03 0.69507809E-08
45 4 0.30464713 0.69501731E-03 0.10418329 -0.35343869E-04
46 3 -7.5136835 0.21306369E-01 -2.4123261 0.30221796E-01
47 2 41.686696 0.75037385E-01 15.565716 -0.34242481
48 1 -81.170502 0.33581009E-01 -29.411065 1.0919325
49 0 46.824335 0.67004661E-03 16.284887  
50 7 -0.34244365E-12 0.92212740E-15 -0.10449257E-12 0.10448628E-15
51 6 0.30869821E-07 0.16952917E-09 0.70532514E-08 -0.14704533E-12
52 5 -0.20120586E-03 0.14312561E-05 -0.10333395E-03 0.69653235E-08
53 4 0.30503960 0.68816038E-03 0.10432471 -0.35399819E-04
54 3 -7.5214432 0.21089521E-01 -2.4146296 0.30259860E-01
55 2 41.712273 0.74252889E-01 15.575132 -0.34270975
56 1 -81.190086 0.33221761E-01 -29.419498 1.0923499
57 0 46.824335 0.66271842E-03 16.284691  
58 7 -0.32374075E-12 0.12045207E-14 -0.10360241E-12 0.16221974E-15
59 6 0.29475593E-07 0.20098913E-09 0.67455071E-08 -0.13952197E-12
60 5 -0.19418177E-03 0.17111334E-05 -0.99823337E-04 0.66657971E-08
61 4 0.29690150 0.82890285E-03 0.10139402 -0.34243177E-04
62 3 -7.3604632 0.25571829E-01 -2.3668478 0.29470418E-01
63 2 41.181572 0.90565943E-01 15.379610 -0.33679792
64 1 -80.783638 0.40729985E-01 -29.244332 1.0836880
65 0 46.824337 0.81662197E-03 16.288791  
66 7 -0.18778705E-08 -0.48456698E-15 0.68415356E-14 -0.90766841E-16
67 6 0.62832840E-05 0.42957215E-08 0.31879255E-02 -0.26742991E-04
68 5 -0.45150393E-03 0.25448514E-05 -0.22361406 0.19551748E-02
69 4 0.10383635E-01 0.11583744E-03 4.8277051 -0.45247288E-01
70 3 -0.91177470E-01 0.92119394E-03 -38.011019 0.39853883
71 2 0.32374524 0.15324382E-02 116.46371 -1.4176686
72 1 -0.46727348 0.46697369E-03 -143.89540 2.0488441
73 0 0.22781756 0.11275910E-04 60.838472  
74 7 -0.17777358E-08 -0.41207670E-15 0.60771148E-14 -0.79247013E-16
75 6 0.66205355E-05 0.45347915E-08 0.31869553E-02 -0.26734852E-04
76 5 -0.47643654E-03 0.26865296E-05 -0.22355891 0.19546881E-02
77 4 0.10961386E-01 0.12229770E-03 4.8267865 -0.45238458E-01
78 3 -0.96263561E-01 0.97262436E-03 -38.005829 0.39848146
79 2 0.34182167 0.16181264E-02 116.45361 -1.4175335
80 1 -0.49337445 0.49308431E-03 -143.88945 2.0487464
81 0 0.24054552 0.11921404E-04 60.838472  
82 7 -0.18778705E-08 -0.48456747E-15 0.68415356E-14 -0.90766840E-16
83 6 0.62832840E-05 0.42957215E-08 0.31879255E-02 -0.26742991E-04
84 5 -0.45150393E-03 0.25448514E-05 -0.22361406 0.19551748E-02
85 4 0.10383635E-01 0.11583744E-03 4.8277051 -0.45247288E-01
86 3 -0.91177470E-01 0.92119394E-03 -38.011019 0.39853883
87 2 0.32374524 0.15324382E-02 116.46371 -1.4176686
88 1 -0.46727348 0.46697369E-03 -143.89540 2.0488441
89 0 0.22781756 0.11275910E-04 60.838472  
90 7 -0.17776120E-08 -0.41258204E-15 0.60425363E-14 -0.82023253E-16
91 6 0.66209765E-05 0.45351028E-08 0.31869540E-02 -0.26734841E-04
92 5 -0.47646911E-03 0.26867147E-05 -0.22355884 0.19546874E-02
93 4 0.10962140E-01 0.12230614E-03 4.8267853 -0.45238446E-01
94 3 -0.96270204E-01 0.97269154E-03 -38.005822 0.39848139
95 2 0.34184528 0.16182383E-02 116.45360 -1.4175333
96 1 -0.49340854 0.49311848E-03 -143.88944 2.0487463
97 0 0.24056214 0.11922214E-04 60.838472  
98 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
99 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
100 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
101 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
102 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
103 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
104 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
105 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
106 0 0.84795330E-02 0.69040512E-07 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.363_SHGC_EAST_0.359 35 1 VerySmooth 2.062 2.062 1.000 0.360    
2 WINDOW_U_0.363_SHGC_SOUTH_0.359 36 1 VerySmooth 2.062 2.062 1.000 0.360    
3 WINDOW_U_0.363_SHGC_WEST_0.359 37 1 VerySmooth 2.062 2.062 1.000 0.360    
4 WINDOW_U_0.363_SHGC_NORTH_0.359 38 1 VerySmooth 2.062 2.062 1.000 0.360    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.62716E-002 0.27216 0.52063 0.52063 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11617 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.62716E-002 0.27216 0.52063 0.52063 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11617 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.62716E-002 0.27216 0.52063 0.52063 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11617 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.62716E-002 0.27216 0.52063 0.52063 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11617 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_TOP_ZN_3 1 0
2 PERIMETER_TOP_ZN_2 1 0
3 PERIMETER_TOP_ZN_1 1 0
4 PERIMETER_TOP_ZN_4 1 0
5 PERIMETER_BOT_ZN_3 3 0
6 PERIMETER_BOT_ZN_2 2 0
7 PERIMETER_BOT_ZN_1 3 0
8 PERIMETER_BOT_ZN_4 2 0
9 PERIMETER_MID_ZN_3 1 0
10 PERIMETER_MID_ZN_2 1 0
11 PERIMETER_MID_ZN_1 1 0
12 PERIMETER_MID_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_TOP_ZN_3 0  
2 PERIMETER_TOP_ZN_2 0  
3 PERIMETER_TOP_ZN_1 0  
4 PERIMETER_TOP_ZN_4 0  
5 PERIMETER_BOT_ZN_3 0  
6 PERIMETER_BOT_ZN_2 0  
7 PERIMETER_BOT_ZN_1 0  
8 PERIMETER_BOT_ZN_4 0  
9 PERIMETER_MID_ZN_3 0  
10 PERIMETER_MID_ZN_2 0  
11 PERIMETER_MID_ZN_1 0  
12 PERIMETER_MID_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.3785 29307.1 27.185 0.8451


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
2 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
3 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
4 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
5 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
6 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
7 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
8 PERIMETER_TOP_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
9 PERIMETER_TOP_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
10 PERIMETER_TOP_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
11 PERIMETER_TOP_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
12 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
13 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
14 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
15 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
16 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
17 BUILDING_ROOF 0 1660.73 183.01 0.00 0 1.22 166.37 39.93 0.00 0 No No
18 PERIMETER_MID_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
19 PERIMETER_MID_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
20 PERIMETER_MID_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
21 PERIMETER_MID_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
22 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
23 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
24 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
25 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
26 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
27 iz-PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
28 iz-PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
29 iz-PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
30 iz-PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
31 iz-CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
32 PERIMETER_BOT_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
33 PERIMETER_BOT_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
34 PERIMETER_BOT_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
35 PERIMETER_BOT_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
36 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
37 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
38 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
39 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
40 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
41 iz-PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
42 iz-PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
43 iz-PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
44 iz-PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
45 iz-CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
46 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
47 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
48 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
49 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
50 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
51 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
52 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
53 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
54 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
55 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
56 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
57 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
58 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
59 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
60 PERIMETER_TOP_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
62 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
64 iz-CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
65 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
66 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
68 PERIMETER_TOP_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
70 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
72 iz-CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
73 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
74 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
76 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
78 PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
80 iz-CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
81 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
82 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
84 PERIMETER_TOP_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
86 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
88 iz-CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
89 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
90 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
92 PERIMETER_BOT_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
98 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
100 iz-CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
101 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
102 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
104 PERIMETER_BOT_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 0 No No
108 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
110 iz-CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
111 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
112 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
114 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
120 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
122 iz-CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
123 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
124 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
126 PERIMETER_BOT_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 0 No No
130 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
132 iz-CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
133 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
134 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
136 PERIMETER_MID_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
138 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
140 iz-CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
141 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
142 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
144 PERIMETER_MID_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
146 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
147 iz-PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
148 iz-CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
149 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
150 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
152 PERIMETER_MID_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
154 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
156 iz-CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
157 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
158 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
160 PERIMETER_MID_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
162 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
163 iz-PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
164 iz-CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
165 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
166 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
2 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
3 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
4 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
5 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
6 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
7 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
8 PERIMETER_BOT_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_BOT_ZN_1 207.34 11.2 0.679 3.273E-003 4.819E-003 4.296 1.000 0.000 0.000 0.000
9 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
10 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
11 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
12 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
13 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
14 FIRSTFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL FIRSTFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
15 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
16 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.790E-005 9.244E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_BOTTOM Mixing/Well-Stirred
2 TOPFLOOR_PLENUM Mixing/Well-Stirred
3 MIDFLOOR_PLENUM Mixing/Well-Stirred
4 FIRSTFLOOR_PLENUM Mixing/Well-Stirred
5 CORE_MID Mixing/Well-Stirred
6 CORE_TOP Mixing/Well-Stirred
7 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
8 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
9 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
10 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
11 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
12 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
13 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
14 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
15 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
16 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
17 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
18 PERIMETER_MID_ZN_4 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.1124E-002
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.1187E-002
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2194E-002
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2249E-002
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.8114E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.8556E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1337E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.1567E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1563
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.9739E-002
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1765
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.9275E-002
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1119
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.6836E-002
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.5658E-002
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7130E-002
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.1124E-002
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.1190E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2194E-002
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2251E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.8115E-003
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.8575E-003
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1335E-003
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.1565E-003
25 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.7428E-002
26 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.9320E-002
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.2596E-002
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5853E-002
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.6333E-002
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.3432E-002
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.3611E-002
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5268E-002
33 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.1671E-004
34 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.1914E-004
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.7866E-004
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.8041E-004
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.6390E-004
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.6450E-004
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.8245E-004
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.8324E-004
41 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.3163E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.3697E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.6094E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.6519E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1524E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.1828E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.1335E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.1565E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.0803E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3362E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1402E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7783E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9035E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2280E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.5658E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7130E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.3164E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.3700E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.6094E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.6517E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1521E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.1813E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.1337E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.1567E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.4526E-002
66 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.7922E-002
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.9000E-002
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4113E-002
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.3865E-002
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.2276E-002
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.3611E-002
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.5268E-002
73 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.9946E-004
74 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 6.0637E-004
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.5721E-004
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.6477E-004
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.4945E-004
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.5233E-004
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.8247E-004
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.8326E-004
81 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1550
82 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 9.6090E-002
83 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1720
84 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1070
85 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1194
86 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.9373E-002
87 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 5.2056E-002
88 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.4300E-002
89 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.5226E-002
90 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.8067E-002
91 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.0667E-002
92 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.4757E-002
93 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.4791E-002
94 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.2519E-002
95 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.2614E-002
96 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.4669E-002
97 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.6586E-002
98 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.0538E-002
99 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.6548E-002
100 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.3959E-002
101 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.4190E-002
102 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.7955E-002
103 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.2056E-002
104 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.4300E-002
105 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.2420E-002
106 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.6743E-002
107 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.7191E-002
108 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.3111E-002
109 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.2399E-002
110 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.1418E-002
111 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.2615E-002
112 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.4670E-002
113 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1550
114 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 9.6081E-002
115 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1720
116 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1069
117 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1194
118 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.9365E-002
119 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 5.2051E-002
120 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.4297E-002
121 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.5225E-002
122 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.8064E-002
123 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.0666E-002
124 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.4754E-002
125 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.4787E-002
126 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.2515E-002
127 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.2609E-002
128 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.4667E-002
129 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.6588E-002
130 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.0537E-002
131 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.6549E-002
132 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.3958E-002
133 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.4187E-002
134 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.7954E-002
135 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.2051E-002
136 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.4297E-002
137 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.2419E-002
138 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.6741E-002
139 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.7190E-002
140 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.3109E-002
141 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.2395E-002
142 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.1415E-002
143 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.2610E-002
144 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.4667E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_BOTTOM Cooling 30453.17847 30453.17847 2.19343 2.19343 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 26.62400 1.41098E-002 983.53657 52.93867 0.42469 0.00000
2 CORE_BOTTOM Heating 7777.32352 7777.32352 0.32700 0.42469 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 983.53657 52.93867 0.42469 0.00000
3 CORE_MID Cooling 26685.31259 26685.31259 1.92064 1.92064 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 26.62400 1.41098E-002 983.53657 52.93867 0.42469 0.00000
4 CORE_MID Heating 13921.67292 13921.67292 0.58906 0.58906 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 983.53657 52.93867 0.42469 0.00000
5 CORE_TOP Cooling 28414.96241 28414.96241 2.06550 2.06550 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 32.10000 1.41196E-002 983.53657 52.93867 0.42469 0.00000
6 CORE_TOP Heating 24312.12705 24312.12705 1.03352 1.03352 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 983.53657 52.93867 0.42469 0.00000
7 PERIMETER_TOP_ZN_3 Cooling 8977.53686 8977.53686 0.65261 0.65261 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 32.10000 1.41196E-002 207.33814 11.15994 8.95286E-002 0.00000
8 PERIMETER_TOP_ZN_3 Heating 11413.52611 11413.52611 0.48675 0.48675 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 207.33814 11.15994 8.95286E-002 0.00000
9 PERIMETER_TOP_ZN_2 Cooling 10038.55885 10038.55885 0.72973 0.72973 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 28.23967 1.41127E-002 131.26219 7.06516 5.66790E-002 0.00000
10 PERIMETER_TOP_ZN_2 Heating 7411.16671 7411.16671 0.31608 0.31608 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 131.26219 7.06516 5.66790E-002 0.00000
11 PERIMETER_TOP_ZN_1 Cooling 12274.09420 12274.09420 0.89224 0.89224 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 31.79167 1.41191E-002 207.33814 11.15994 8.95286E-002 0.00000
12 PERIMETER_TOP_ZN_1 Heating 11321.32464 11321.32464 0.48280 0.48280 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 207.33814 11.15994 8.95286E-002 0.00000
13 PERIMETER_TOP_ZN_4 Cooling 10806.33413 10806.33413 0.78554 0.78554 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 131.25358 7.06470 5.66753E-002 0.00000
14 PERIMETER_TOP_ZN_4 Heating 7467.10151 7467.10151 0.31847 0.31847 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 131.25358 7.06470 5.66753E-002 0.00000
15 PERIMETER_BOT_ZN_3 Cooling 7081.59617 7081.59617 0.51477 0.51477 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 32.10000 1.41196E-002 207.33814 11.15994 8.95286E-002 0.00000
16 PERIMETER_BOT_ZN_3 Heating 8777.66433 8777.66433 0.37406 0.37406 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 207.33814 11.15994 8.95286E-002 0.00000
17 PERIMETER_BOT_ZN_2 Cooling 8280.74694 8280.74694 0.60194 0.60194 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 28.65900 1.41134E-002 131.26219 7.06516 5.66790E-002 0.00000
18 PERIMETER_BOT_ZN_2 Heating 5732.45695 5732.45695 0.24431 0.24431 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 131.26219 7.06516 5.66790E-002 0.00000
19 PERIMETER_BOT_ZN_1 Cooling 9908.01587 9908.01587 0.72023 0.72023 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 31.85333 1.41192E-002 207.33814 11.15994 8.95286E-002 0.00000
20 PERIMETER_BOT_ZN_1 Heating 8689.14490 8689.14490 0.37027 0.37027 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 207.33814 11.15994 8.95286E-002 0.00000
21 PERIMETER_BOT_ZN_4 Cooling 8487.38015 8487.38015 0.61696 0.61696 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 31.06400 1.41178E-002 131.25358 7.06470 5.66753E-002 0.00000
22 PERIMETER_BOT_ZN_4 Heating 5788.94690 5788.94690 0.24673 0.24673 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 131.25358 7.06470 5.66753E-002 0.00000
23 PERIMETER_MID_ZN_3 Cooling 7784.99920 7784.99920 0.56591 0.56591 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 32.10000 1.41196E-002 207.33814 11.15994 8.95286E-002 0.00000
24 PERIMETER_MID_ZN_3 Heating 9038.61529 9038.61529 0.38519 0.38519 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 207.33814 11.15994 8.95286E-002 0.00000
25 PERIMETER_MID_ZN_2 Cooling 9778.43732 9778.43732 0.71081 0.71081 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 28.03000 1.41123E-002 131.26219 7.06516 5.66790E-002 0.00000
26 PERIMETER_MID_ZN_2 Heating 5896.49964 5896.49964 0.25131 0.25131 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 131.26219 7.06516 5.66790E-002 0.00000
27 PERIMETER_MID_ZN_1 Cooling 11114.22244 11114.22244 0.80792 0.80792 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 31.73000 1.41190E-002 207.33814 11.15994 8.95286E-002 0.00000
28 PERIMETER_MID_ZN_1 Heating 8948.60541 8948.60541 0.38134 0.38134 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 207.33814 11.15994 8.95286E-002 0.00000
29 PERIMETER_MID_ZN_4 Cooling 9979.48722 9979.48722 0.72543 0.72543 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 131.25358 7.06470 5.66753E-002 0.00000
30 PERIMETER_MID_ZN_4 Heating 5949.80833 5949.80833 0.25359 0.25359 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 131.25358 7.06470 5.66753E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PACU_VAV_BOT Cooling Sensible 65298.86 4.12953 4.12953 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 PACU_VAV_BOT Heating Sensible 27042.88 1.66007 1.66007 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:20:00
3 PACU_VAV_MID Cooling Sensible 63882.24 4.02497 4.02497 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 PACU_VAV_MID Heating Sensible 26977.94 1.86050 1.86050 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:10:00
5 PACU_VAV_TOP Cooling Sensible 72823.40 4.68568 4.68568 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 PACU_VAV_TOP Heating Sensible 26913.20 2.63762 2.63762 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:30:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.19343
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34168
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.29000
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63609
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.91115
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.11507E-003
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.24044E-004
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.63609
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14178.99643
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.24044E-004
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 325.13391
15 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.92064
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.39021
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33200
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63765
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.76396E-004
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.77935E-004
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.63765
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 20339.02716
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.77935E-004
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 524.91853
29 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.06550
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.36284
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30800
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63617
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.96759
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.05004E-003
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.03689E-004
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.03352
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 34713.47305
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.03689E-004
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 916.45578
43 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.65261
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24209
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20600
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13444
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.64558
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.57377E-003
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.42667E-004
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.48675
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16307.74717
55 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.42667E-004
56 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 430.04017
57 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.72973
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13707
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11700
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.53783E-002
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36551
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.77966E-003
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.26396E-005
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.31608
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10589.28025
69 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.26396E-005
70 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 279.23584
71 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.89224
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17707
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15100
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13473
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.47220
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.15165E-003
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.41513E-004
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.48280
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16175.86237
83 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.41513E-004
84 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 426.56515
85 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.78554
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12732
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10800
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.48383E-002
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33952
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.99245E-003
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.33396E-005
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.31847
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10669.28909
97 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.33396E-005
98 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 281.34396
99 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.51477
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30691
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.26100
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13436
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.81844
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.24139E-003
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.09699E-004
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.37406
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12539.22909
111 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.09699E-004
112 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 330.74658
113 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.60194
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16617
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.14100
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.48731E-002
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44311
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.29288E-003
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.16438E-005
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.24431
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
124 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8189.33032
125 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.16438E-005
126 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 216.00237
127 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.72023
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21936
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.18600
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13396
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58497
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.73684E-003
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.08591E-004
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.37027
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
138 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12412.56287
139 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.08591E-004
140 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 327.40877
141 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.61696
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16211
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.13800
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.51401E-002
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.43229
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.35025E-003
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.23510E-005
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.24673
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
152 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8270.16243
153 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.23510E-005
154 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 218.13235
155 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.56591
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27918
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23700
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13412
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.74448
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.36471E-003
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.12954E-004
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.38519
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
166 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12911.29281
167 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.12954E-004
168 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 340.54665
169 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.71081
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37524
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.70761E-003
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.36894E-005
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.25131
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
177 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8423.15502
178 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.36894E-005
179 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 222.16077
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.80792
181 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19555
182 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.16600
183 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13411
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52148
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.94831E-003
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.11827E-004
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.38134
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
191 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12782.51497
192 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.11827E-004
193 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 337.15334
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.72543
195 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13787
196 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11700
197 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.48752E-002
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36765
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.76346E-003
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.43566E-005
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.25359
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
205 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8499.42143
206 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.43566E-005
207 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 224.17035
208 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.32366
209 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.07443
210 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 4.64732
211 AirLoopHVAC PACU_VAV_BOT Adjusted Heating Design Air Flow Rate [m3/s] 1.66007
212 AirLoopHVAC PACU_VAV_BOT Adjusted Cooling Design Air Flow Rate [m3/s] 4.12953
213 AirLoopHVAC PACU_VAV_BOT Adjusted Main Design Air Flow Rate [m3/s] 4.12953
214 AirLoopHVAC PACU_VAV_BOT User Heating Air Flow Ratio [] 0.30000
215 AirLoopHVAC PACU_VAV_BOT Calculated Heating Air Flow Ratio [] 0.40200
216 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.36536
217 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.07606
218 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.73072
219 AirLoopHVAC PACU_VAV_MID Adjusted Heating Design Air Flow Rate [m3/s] 1.86050
220 AirLoopHVAC PACU_VAV_MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.02497
221 AirLoopHVAC PACU_VAV_MID Adjusted Main Design Air Flow Rate [m3/s] 4.02497
222 AirLoopHVAC PACU_VAV_MID User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC PACU_VAV_MID Calculated Heating Air Flow Ratio [] 0.46224
224 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.56281
225 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.07555
226 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 5.12561
227 AirLoopHVAC PACU_VAV_TOP Adjusted Heating Design Air Flow Rate [m3/s] 2.63762
228 AirLoopHVAC PACU_VAV_TOP Adjusted Cooling Design Air Flow Rate [m3/s] 4.68568
229 AirLoopHVAC PACU_VAV_TOP Adjusted Main Design Air Flow Rate [m3/s] 4.68568
230 AirLoopHVAC PACU_VAV_TOP User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC PACU_VAV_TOP Calculated Heating Air Flow Ratio [] 0.56291
232 AirLoopHVAC PACU_VAV_BOT Design Supply Air Flow Rate [m3/s] 4.12953
233 AirLoopHVAC PACU_VAV_MID Design Supply Air Flow Rate [m3/s] 4.02497
234 AirLoopHVAC PACU_VAV_TOP Design Supply Air Flow Rate [m3/s] 4.68568
235 Controller:OutdoorAir PACU_VAV_BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.12953
236 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.12953
237 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 90591.55350
238 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.74142
239 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.37637
240 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 30194.16478
241 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.74142
242 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size Rated Capacity [W] 25001.33252
243 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.18723E-004
244 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size U-Factor Times Area Value [W/K] 410.10600
245 Fan:VariableVolume PACU_VAV_BOT FAN Design Size Maximum Flow Rate [m3/s] 4.12953
246 Controller:WaterCoil PACU_VAV_BOT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.18723E-004
247 Controller:OutdoorAir PACU_VAV_MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.02497
248 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.02497
249 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 89043.86962
250 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.73910
251 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.34152
252 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 29678.32175
253 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.73910
254 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size Rated Capacity [W] 25295.42390
255 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.21295E-004
256 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size U-Factor Times Area Value [W/K] 413.46441
257 Fan:VariableVolume PACU_VAV_MID FAN Design Size Maximum Flow Rate [m3/s] 4.02497
258 Controller:WaterCoil PACU_VAV_MID_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.21295E-004
259 Controller:OutdoorAir PACU_VAV_TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.68568
260 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.68568
261 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 100003.10815
262 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.75116
263 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.56174
264 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 33331.03595
265 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.75116
266 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size Rated Capacity [W] 24556.05416
267 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.14827E-004
268 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size U-Factor Times Area Value [W/K] 408.01648
269 Fan:VariableVolume PACU_VAV_TOP FAN Design Size Maximum Flow Rate [m3/s] 4.68568
270 Controller:WaterCoil PACU_VAV_TOP_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.14827E-004
271 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.46578E-003
272 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.29589
273 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.46578E-003
274 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 735.23325
275 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
276 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 281854.15505
277 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 281854.16000
278 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.46578E-003
279 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 5.36267E-005
280 PlantLoop SWHSYS1 Plant Loop Volume [m3] 6.43520E-003
281 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 5.36267E-005
282 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 6.85023
283 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 5.36267E-005


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 13434.63
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 19260.22
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 32895.03
4 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 15450.17
5 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 10032.38
6 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 15325.24
7 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 10108.17
8 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 11880.39
9 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 7758.99
10 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 11760.40
11 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 7835.56
12 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 12232.81
13 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 7980.47
14 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 12110.82
15 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 8052.72
16 Coil:Heating:Water PACU_VAV_BOT HEATING COIL 19111.31
17 Coil:Heating:Water PACU_VAV_MID HEATING COIL 19194.89
18 Coil:Heating:Water PACU_VAV_TOP HEATING COIL 19271.65


VAV DX Cooling Coil Standard Rating Information

DX Coil Type DX Coil Name Fan Type Fan Name Standard Net Cooling Capacity {W} Standard Net Cooling Capacity {Btu/h} IEER {Btu/W-h} COP 100% Capacity {W/W} COP 75% Capacity {W/W} COP 50% Capacity {W/W} COP 25% Capacity {W/W} EER 100% Capacity {Btu/W-h} EER 75% Capacity {Btu/W-h} EER 50% Capacity {Btu/W-h} EER 25% Capacity {Btu/W-h} Supply Air Flow 100% {kg/s} Supply Air Flow 75% {kg/s} Supply Air Flow 50% {kg/s} Supply Air Flow 25% {kg/s}
1 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL N/A N/A 90071.32 307336.10 12.77 3.29 3.66 3.85 4.03 11.23 12.47 13.13 13.76 4.7740 3.7959 2.5539 1.0584
2 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL N/A N/A 88558.83 302175.27 12.79 3.29 3.66 3.85 4.04 11.24 12.49 13.15 13.78 4.6531 3.7031 2.4942 1.0327
3 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL N/A N/A 99330.52 338929.79 12.69 3.28 3.63 3.82 4.02 11.18 12.40 13.05 13.71 5.4169 4.3163 2.9067 1.1914


Zone Surfaces

Zone Name # Surfaces
1 CORE_BOTTOM 7
2 TOPFLOOR_PLENUM 10
3 MIDFLOOR_PLENUM 14
4 FIRSTFLOOR_PLENUM 14
5 CORE_MID 7
6 CORE_TOP 7
7 PERIMETER_TOP_ZN_3 8
8 PERIMETER_TOP_ZN_2 8
9 PERIMETER_TOP_ZN_1 8
10 PERIMETER_TOP_ZN_4 8
11 PERIMETER_BOT_ZN_3 12
12 PERIMETER_BOT_ZN_2 10
13 PERIMETER_BOT_ZN_1 12
14 PERIMETER_BOT_ZN_4 10
15 PERIMETER_MID_ZN_3 8
16 PERIMETER_MID_ZN_2 8
17 PERIMETER_MID_ZN_1 8
18 PERIMETER_MID_ZN_4 8


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction CORE_BOT_ZN_5_FLOOR_FFACTOR 5.650E-003 5.642E-003   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
8 PERIMETER_TOP_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.709 0.641   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 PERIMETER_TOP_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.709 0.641   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 PERIMETER_TOP_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.709 0.641   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 PERIMETER_TOP_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.709 0.641   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
12 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 225.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
13 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 135.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
14 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 45.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
15 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 315.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
16 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 180.00 180.00 40.76 24.13 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
17 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   1660.73 1660.73 1660.73 0.00 0.00 49.91 33.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
18 PERIMETER_MID_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.590 0.542   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
19 PERIMETER_MID_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.590 0.542   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
20 PERIMETER_MID_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.590 0.542   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
21 PERIMETER_MID_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.590 0.542   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
23 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
25 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
26 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
27 iz-PERIMETER_TOP_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
28 iz-PERIMETER_TOP_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
29 iz-PERIMETER_TOP_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 iz-PERIMETER_TOP_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
31 iz-CORE_TOP_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 PERIMETER_BOT_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.596 0.547   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
33 PERIMETER_BOT_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.596 0.547   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.596 0.547   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.596 0.547   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
37 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
38 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
39 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
40 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
41 iz-PERIMETER_MID_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
42 iz-PERIMETER_MID_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
43 iz-PERIMETER_MID_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
44 iz-PERIMETER_MID_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 iz-CORE_MID_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
46 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
47 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
48 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
49 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
51 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
52 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
53 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
55 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
56 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
57 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
58 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 0.00 0.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
59 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
60 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.709 0.641   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
62 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
64 iz-CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
65 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
66 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 225.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
68 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.709 0.641   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.359 N/A 2.062 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 iz-CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
74 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 315.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
76 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.709 0.641   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
78 PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 iz-CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
82 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 45.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
84 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.709 0.641   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.359 N/A 2.062 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 iz-CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
89 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
90 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 135.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
92 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.596 0.547   67.75 136.92 67.75 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 iz-CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 0.224 0.213   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.596 0.547   45.82 91.28 45.82 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.359 N/A 2.062 No 41.85 41.85 41.85 90.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.359 N/A 2.062 No 1.65 1.65 1.65 90.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
108 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
110 iz-CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 0.237 0.224   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
112 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
114 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.596 0.547   67.75 136.92 67.75 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 iz-CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
123 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 0.224 0.213   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
124 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
126 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.596 0.547   45.82 91.28 45.82 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.359 N/A 2.062 No 41.85 41.85 41.85 270.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.359 N/A 2.062 No 1.65 1.65 1.65 270.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 iz-CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
133 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 0.237 0.224   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.590 0.542   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 iz-CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.590 0.542   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.359 N/A 2.062 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 iz-PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 iz-CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
150 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
152 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.590 0.542   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 iz-CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
157 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
160 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.590 0.542   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.359 N/A 2.062 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
163 iz-PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
164 iz-CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
165 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_BOTTOM RunPeriod: RUNPERIOD 1 4.3732816448E-002 2.4553165758E-002 Pass Pass 0.4909755313 0.4930284247 Pass Pass
2 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.1344893723 9.8835097822E-002 Pass Pass 0.5014597137 0.4864039703 Pass Pass
3 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.5751364935E-002 3.8191603080E-002 Pass Pass 0.4852089215 0.4796245595 Pass Pass
4 FIRSTFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.3059545350E-002 3.4111631635E-002 Pass Pass 0.4840233309 0.4747712605 Pass Pass
5 CORE_MID RunPeriod: RUNPERIOD 1 1.2789866078E-002 9.1358078103E-003 Pass Pass 0.6845162102 2.4332194412 Pass Pass
6 CORE_TOP RunPeriod: RUNPERIOD 1 8.9752088499E-002 0.1083177794 Pass Pass 17.6428115930 124.5637218392 Pass Pass
7 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.4807775399 0.4404406071 Pass Pass 7.6368385887 31.5667073767 Pass Pass
8 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.4141258001 0.4545379878 Pass Pass 114.5840100762 1232.8438426758 Pass Pass
9 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.3655774546 0.3864634420 Pass Pass 1.1213200280 3.0683458320 Pass Pass
10 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.4715667372 0.4690490817 Pass Pass 23.5485377808 120.2201432904 Pass Pass
11 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 0.3134711195 0.2880002589 Pass Pass 8.9397874315 37.2588585059 Pass Pass
12 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.2317195338 0.2782048054 Pass Pass 6.1077652726 30.6862258891 Pass Pass
13 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.1759184753 0.1758561730 Pass Pass 2.4808453693 13.6649614408 Pass Pass
14 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.2885179782 0.3027046567 Pass Pass 19.4238360500 129.4082562670 Pass Pass
15 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.3461220282 0.3217695638 Pass Pass 6.9001465175 35.4975566349 Pass Pass
16 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.2951087902 0.3318603016 Pass Pass 6.1668075911 29.2230825816 Pass Pass
17 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.2671589680 0.2661500328 Pass Pass 12.6249520514 141.0075860975 Pass Pass
18 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.3339987929 0.3471287087 Pass Pass 42.5071844339 251.4646669441 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3541.00 74.15 0.00 1445.69 1075.00 6135.86



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB -10.70 0.00 -10.70 Wetbulb [C] 7.50 320.00
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 32.10 7.40 23.10 Wetbulb [C] 5.60 230.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 172.00 59      
Feb 49.00 37      
Mar 40.00 38      
Apr 70.00 48      
May 70.00 36      
Jun 25.00 15      
Jul 64.00 20      
Aug 2.00 4      
Sep 73.00 32      
Oct 7.00 8      
Nov 88.00 34      
Dec 62.00 39      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.641 0.709 60.85 60.85 0.00 90.00 N
PERIMETER_TOP_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.641 0.709 40.57 40.57 90.00 90.00 E
PERIMETER_TOP_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.641 0.709 60.85 60.85 180.00 90.00 S
PERIMETER_TOP_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.641 0.709 40.57 40.57 270.00 90.00 W
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 1660.73 1660.73 0.00 0.00  
PERIMETER_MID_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.542 0.590 60.85 60.85 0.00 90.00 N
PERIMETER_MID_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.542 0.590 40.57 40.57 90.00 90.00 E
PERIMETER_MID_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.542 0.590 60.85 60.85 180.00 90.00 S
PERIMETER_MID_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.542 0.590 40.57 40.57 270.00 90.00 W
PERIMETER_BOT_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.547 0.596 60.85 60.85 0.00 90.00 N
PERIMETER_BOT_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.547 0.596 40.57 40.57 90.00 90.00 E
PERIMETER_BOT_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.547 0.596 60.85 60.85 180.00 90.00 S
PERIMETER_BOT_PLENUM_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.547 0.596 40.57 40.57 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.641 0.709 136.92 71.65 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.641 0.709 91.28 47.77 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.641 0.709 136.92 71.65 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.641 0.709 91.28 47.77 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.547 0.596 136.92 67.75 0.00 90.00 N
PERIMETER_BOT_ZN_3_FLOOR PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 1.00 0.216 0.224 207.34 207.34 0.00 180.00  
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.547 0.596 91.28 45.82 90.00 90.00 E
PERIMETER_BOT_ZN_2_FLOOR PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 1.00 0.228 0.237 131.26 131.26 90.00 180.00  
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.547 0.596 136.92 67.75 180.00 90.00 S
PERIMETER_BOT_ZN_1_FLOOR PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 1.00 0.216 0.224 207.34 207.34 180.00 180.00  
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.547 0.596 91.28 45.82 270.00 90.00 W
PERIMETER_BOT_ZN_4_FLOOR PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 1.00 0.228 0.237 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.542 0.590 136.92 71.65 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.542 0.590 91.28 47.77 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.542 0.590 136.92 71.65 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.542 0.590 91.28 47.77 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_BOT_ZN_5_FLOOR CORE_BOT_ZN_5_FLOOR_FFACTOR 1.00 0.006 0.006 983.54 983.54 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 135.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 315.00 180.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_TOP_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_MID_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_MID_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_MID_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_MID_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_MID_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 315.00 0.00  
PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 135.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.363_SHGC_NORTH_0.359   65.26 0.00 0.00 65.26 65.26 2.062 0.360 0.396             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.363_SHGC_EAST_0.359   43.51 0.00 0.00 43.51 43.51 2.062 0.360 0.396             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.363_SHGC_SOUTH_0.359   65.26 0.00 0.00 65.26 65.26 2.062 0.360 0.396             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.363_SHGC_WEST_0.359   43.51 0.00 0.00 43.51 43.51 2.062 0.360 0.396             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.363_SHGC_NORTH_0.359   21.75 0.00 0.00 21.75 21.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.363_SHGC_NORTH_0.359   21.75 0.00 0.00 21.75 21.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.363_SHGC_NORTH_0.359   21.75 0.00 0.00 21.75 21.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.363_SHGC_EAST_0.359   41.85 0.00 0.00 41.85 41.85 2.062 0.360 0.396             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.363_SHGC_EAST_0.359   1.65 0.00 0.00 1.65 1.65 2.062 0.360 0.396             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.363_SHGC_SOUTH_0.359   21.75 0.00 0.00 21.75 21.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.363_SHGC_SOUTH_0.359   21.75 0.00 0.00 21.75 21.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.363_SHGC_SOUTH_0.359   21.75 0.00 0.00 21.75 21.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.363_SHGC_WEST_0.359   41.85 0.00 0.00 41.85 41.85 2.062 0.360 0.396             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.363_SHGC_WEST_0.359   1.65 0.00 0.00 1.65 1.65 2.062 0.360 0.396             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.363_SHGC_NORTH_0.359   65.26 0.00 0.00 65.26 65.26 2.062 0.360 0.396             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.363_SHGC_EAST_0.359   43.51 0.00 0.00 43.51 43.51 2.062 0.360 0.396             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.363_SHGC_SOUTH_0.359   65.26 0.00 0.00 65.26 65.26 2.062 0.360 0.396             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.363_SHGC_WEST_0.359   43.51 0.00 0.00 43.51 43.51 2.062 0.360 0.396             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             652.62 2.062 0.360 0.396                      
North Total or Average             195.79 2.062 0.360 0.396                      
Non-North Total or Average             456.84 2.062 0.360 0.396                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 5.8040 983.54 5708.43 LightsWired LTG_SCH_OFFICE 38.28 168.00 37.14 0.0000 Y 39.80
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 5.8040 983.54 5708.43 LightsWired LTG_SCH_OFFICE 38.28 168.00 37.14 0.0000 Y 39.80
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 5.8040 983.54 5708.43 LightsWired LTG_SCH_OFFICE 38.28 168.00 37.14 0.0000 Y 39.80
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 5.8040 207.34 1203.39 LightsWired LTG_SCH_OFFICE 38.28 168.00 21.67 0.0000 Y 4.89
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 5.8040 131.26 761.84 LightsWired LTG_SCH_OFFICE 38.28 168.00 21.60 0.0000 Y 3.09
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 5.8040 207.34 1203.39 LightsWired LTG_SCH_OFFICE 38.28 168.00 21.39 0.0000 Y 4.83
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 5.8040 131.25 761.79 LightsWired LTG_SCH_OFFICE 38.28 168.00 21.43 0.0000 Y 3.06
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 5.8040 207.34 1203.39 LightsWired LTG_SCH_OFFICE 38.28 168.00 21.62 0.0000 Y 4.88
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 5.8040 131.26 761.84 LightsWired LTG_SCH_OFFICE 38.28 168.00 21.57 0.0000 Y 3.08
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 5.8040 207.34 1203.39 LightsWired LTG_SCH_OFFICE 38.28 168.00 21.36 0.0000 Y 4.83
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 5.8040 131.25 761.79 LightsWired LTG_SCH_OFFICE 38.28 168.00 21.40 0.0000 Y 3.06
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 5.8040 207.34 1203.39 LightsWired LTG_SCH_OFFICE 38.28 168.00 21.67 0.0000 Y 4.89
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 5.8040 131.26 761.84 LightsWired LTG_SCH_OFFICE 38.28 168.00 21.60 0.0000 Y 3.09
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 5.8040 207.34 1203.39 LightsWired LTG_SCH_OFFICE 38.28 168.00 21.39 0.0000 Y 4.83
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 5.8040 131.25 761.79 LightsWired LTG_SCH_OFFICE 38.28 168.00 21.43 0.0000 Y 3.06
Interior Lighting Total       5.8040 4982.19 28916.52               167.00


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.38 1203.39 461.50
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1203.39 167.87
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.38 761.84 292.17
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 761.84 106.28
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.38 1203.39 461.50
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1203.39 167.87
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.38 761.79 292.15
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 761.79 106.27
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.38 1203.39 461.50
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1203.39 167.87
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.38 761.84 292.17
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 761.84 106.28
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.38 1203.39 461.50
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1203.39 167.87
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.38 761.79 292.15
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 761.79 106.27
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.38 1203.39 461.50
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1203.39 167.87
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.38 761.84 292.17
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 761.84 106.28
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.38 1203.39 461.50
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1203.39 167.87
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.38 761.79 292.15
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 761.79 106.27


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 542.49 AstronomicalClock -   42.43 42.43 4.32
EXTERIOR_LIGHTS_B 280.18 AstronomicalClock -   83.64 63.04 3.32
EXTERIOR_LIGHTS_C 3002.07 AstronomicalClock -   83.64 46.90 26.43
Exterior Lighting Total 3824.74           34.07



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 281854.16 0.84        


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed   90591.55 67166.81 23424.75 0.74 3.88    
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed   89043.87 65812.30 23231.57 0.74 3.88    
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed   100003.11 75118.52 24884.59 0.75 3.88    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PACU_VAV_BOT COOLING COIL   90071.3 3.29 11.23 N/A N/A 12.77
PACU_VAV_MID COOLING COIL   88558.8 3.29 11.24 N/A N/A 12.79
PACU_VAV_TOP COOLING COIL   99330.5 3.28 11.18 N/A N/A 12.69
ANSI/AHRI ratings include supply fan

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 14179.00 13434.63 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 20339.03 19260.22 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 34713.47 32895.03 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 16307.75 15450.17 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 10589.28 10032.38 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 16175.86 15325.24 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 10669.29 10108.17 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 12539.23 11880.39 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 8189.33 7758.99 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 12412.56 11760.40 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 8270.16 7835.56 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 12911.29 12232.81 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 8423.16 7980.47 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 12782.51 12110.82 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 8499.42 8052.72 -
PACU_VAV_BOT HEATING COIL Coil:Heating:Water 25001.33 19111.31 -
PACU_VAV_MID HEATING COIL Coil:Heating:Water 25295.42 19194.89 -
PACU_VAV_TOP HEATING COIL Coil:Heating:Water 24556.05 19271.65 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PACU_VAV_BOT FAN Fan:VariableVolume 0.60 1314.72 4.13 9039.59 2189.01 1.00 1.14 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00
PACU_VAV_MID FAN Fan:VariableVolume 0.60 1314.72 4.02 8810.69 2189.01 1.00 1.15 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00
PACU_VAV_TOP FAN Fan:VariableVolume 0.60 1314.72 4.69 10257.01 2189.01 1.00 1.14 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.002466 735.23 298174.34 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000054 6.85 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.38 29307.11 1.00 27.19 0.85


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed None 90071.32 3.29 11.23 12.77 4.7740 3.66 12.47 3.7959 3.85 13.13 2.5539 4.03 13.76 1.0584
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed None 88558.83 3.29 11.24 12.79 4.6531 3.66 12.49 3.7031 3.85 13.15 2.4942 4.04 13.78 1.0327
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed None 99330.52 3.28 11.18 12.69 5.4169 3.63 12.40 4.3163 3.82 13.05 2.9067 4.02 13.71 1.1914
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {{W/1000cfm}} (773.3 {{W/(m3/s)}})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 30453.18 30453.18 30.96 2.193 2.193 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00890 26.62 0.01411 0.425 0.00
CORE_MID 26685.31 26685.31 27.13 1.921 1.921 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00896 26.62 0.01411 0.425 0.00
CORE_TOP 28414.96 28414.96 28.89 2.065 2.065 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00892 32.10 0.01412 0.425 0.00
PERIMETER_TOP_ZN_3 8977.54 8977.54 43.30 0.653 0.653 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00893 32.10 0.01412 0.090 0.00
PERIMETER_TOP_ZN_2 10038.56 10038.56 76.48 0.730 0.730 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 24.00 24.00 0.00875 28.24 0.01411 0.057 0.00
PERIMETER_TOP_ZN_1 12274.09 12274.09 59.20 0.892 0.892 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 24.00 24.00 0.00881 31.79 0.01412 0.090 0.00
PERIMETER_TOP_ZN_4 10806.33 10806.33 82.33 0.786 0.786 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 24.00 24.00 0.00873 31.26 0.01412 0.057 0.00
PERIMETER_BOT_ZN_3 7081.60 7081.60 34.15 0.515 0.515 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00895 32.10 0.01412 0.090 0.00
PERIMETER_BOT_ZN_2 8280.75 8280.75 63.09 0.602 0.602 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00875 28.66 0.01411 0.057 0.00
PERIMETER_BOT_ZN_1 9908.02 9908.02 47.79 0.720 0.720 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 24.00 24.00 0.00883 31.85 0.01412 0.090 0.00
PERIMETER_BOT_ZN_4 8487.38 8487.38 64.66 0.617 0.617 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 24.00 0.00874 31.06 0.01412 0.057 0.00
PERIMETER_MID_ZN_3 7785.00 7785.00 37.55 0.566 0.566 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00896 32.10 0.01412 0.090 0.00
PERIMETER_MID_ZN_2 9778.44 9778.44 74.50 0.711 0.711 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 24.00 24.00 0.00874 28.03 0.01411 0.057 0.00
PERIMETER_MID_ZN_1 11114.22 11114.22 53.60 0.808 0.808 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 24.00 24.00 0.00883 31.73 0.01412 0.090 0.00
PERIMETER_MID_ZN_4 9979.49 9979.49 76.03 0.725 0.725 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 24.00 24.00 0.00873 31.26 0.01412 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 7777.32 7777.32 7.91 0.327 0.425 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -10.70 0.00150 0.425 0.00
CORE_MID 13921.67 13921.67 14.15 0.589 0.589 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -10.70 0.00150 0.425 0.00
CORE_TOP 24312.13 24312.13 24.72 1.034 1.034 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -10.70 0.00150 0.425 0.00
PERIMETER_TOP_ZN_3 11413.53 11413.53 55.05 0.487 0.487 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00762 -10.70 0.00150 0.090 0.00
PERIMETER_TOP_ZN_2 7411.17 7411.17 56.46 0.316 0.316 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00762 -10.70 0.00150 0.057 0.00
PERIMETER_TOP_ZN_1 11321.32 11321.32 54.60 0.483 0.483 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00762 -10.70 0.00150 0.090 0.00
PERIMETER_TOP_ZN_4 7467.10 7467.10 56.89 0.318 0.318 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00762 -10.70 0.00150 0.057 0.00
PERIMETER_BOT_ZN_3 8777.66 8777.66 42.34 0.374 0.374 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00766 -10.70 0.00150 0.090 0.00
PERIMETER_BOT_ZN_2 5732.46 5732.46 43.67 0.244 0.244 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00767 -10.70 0.00150 0.057 0.00
PERIMETER_BOT_ZN_1 8689.14 8689.14 41.91 0.370 0.370 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00765 -10.70 0.00150 0.090 0.00
PERIMETER_BOT_ZN_4 5788.95 5788.95 44.11 0.247 0.247 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00768 -10.70 0.00150 0.057 0.00
PERIMETER_MID_ZN_3 9038.62 9038.62 43.59 0.385 0.385 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00756 -10.70 0.00150 0.090 0.00
PERIMETER_MID_ZN_2 5896.50 5896.50 44.92 0.251 0.251 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00756 -10.70 0.00150 0.057 0.00
PERIMETER_MID_ZN_1 8948.61 8948.61 43.16 0.381 0.381 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00756 -10.70 0.00150 0.090 0.00
PERIMETER_MID_ZN_4 5949.81 5949.81 45.33 0.254 0.254 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00757 -10.70 0.00150 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PACU_VAV_BOT 4.13 4.13 1.66 1.66 4.1295 1.6601 4.1295 0.4020 0.3000
PACU_VAV_MID 4.02 4.02 1.86 1.86 4.0250 1.8605 4.0250 0.4622 0.3000
PACU_VAV_TOP 4.69 4.69 2.64 2.64 4.6857 2.6376 4.6857 0.5629 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 14178.996 14178.996 0.636094 0.00012404 325.134 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 14179.00 14179.00 0.636094 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00800000 51.6928 7777.32 0.00 14226.13 14226.13
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 20339.027 20339.027 0.637653 0.00017793 524.919 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 20339.03 20339.03 0.637653 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00800000 51.6928 13921.67 0.00 20401.46 20401.46
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 34713.473 34713.473 1.033518 0.00030369 916.456 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 34713.47 34713.47 1.033518 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00800000 51.6928 24312.13 0.00 34834.34 34834.34
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 16307.747 16307.747 0.486746 0.00014267 430.040 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 16307.75 16307.75 0.486746 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00762369 49.2959 11413.53 0.00 16360.98 16360.98
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 10589.280 10589.280 0.316080 0.00009264 279.236 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10589.28 10589.28 0.316080 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00761576 49.2454 7411.17 0.00 10623.80 10623.80
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 16175.862 16175.862 0.482802 0.00014151 426.565 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 16175.86 16175.86 0.482802 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00762031 49.2744 11321.32 0.00 16228.68 16228.68
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 10669.289 10669.289 0.318472 0.00009334 281.344 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10669.29 10669.29 0.318472 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00761885 49.2652 7467.10 0.00 10704.05 10704.05
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 12539.229 12539.229 0.374058 0.00010970 330.747 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12539.23 12539.23 0.374058 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00766246 49.5426 8777.66 0.00 12580.76 12580.76
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 8189.330 8189.330 0.244314 0.00007164 216.002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8189.33 8189.33 0.244314 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00766823 49.5794 5732.46 0.00 8216.40 8216.40
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 12412.563 12412.563 0.370272 0.00010859 327.409 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12412.56 12412.56 0.370272 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00765427 49.4904 8689.14 0.00 12453.70 12453.70
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 8270.162 8270.162 0.246731 0.00007235 218.132 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8270.16 8270.16 0.246731 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00767555 49.6261 5788.95 0.00 8297.49 8297.49
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 12911.293 12911.293 0.385192 0.00011295 340.547 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12911.29 12911.29 0.385192 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00756463 48.9187 9038.62 0.00 12953.95 12953.95
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 8423.155 8423.155 0.251312 0.00007369 222.161 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8423.16 8423.16 0.251312 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00756395 48.9144 5896.50 0.00 8450.93 8450.93
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 12782.515 12782.515 0.381342 0.00011183 337.153 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12782.51 12782.51 0.381342 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00755736 48.8722 8948.61 0.00 12824.77 12824.77
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 8499.421 8499.421 0.253592 0.00007436 224.170 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8499.42 8499.42 0.253592 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00756993 48.9526 5949.81 0.00 8527.44 8527.44
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_BOT 90591.554 67166.808 4.129531 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 92652.33 72337.50 4.129531 25.87 18.35 0.01010608 11.02 11.02 0.00850000 32.10 0.01411964 23.13 23.1527 24.00 0.00889687 47.8436 56809.34 0.00 93412.05 68201.22
PACU_VAV_BOT HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_BOT 25001.333 25001.333 1.238859 0.00021872 410.106 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:20:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 25001.33 25001.33 1.238859 -3.89 -3.89 0.00281807 12.80 11.59 0.00800000 -10.70 0.00150390 -10.70 77.1758 19.60 0.00671567 47.4142 14920.77 0.00 23121.26 23121.26
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_MID 89043.870 65812.298 4.024966 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 91197.08 70705.15 4.024966 25.92 18.42 0.01016307 11.02 11.02 0.00850000 32.10 0.01411964 23.13 23.7542 24.00 0.00893041 48.0217 55370.35 0.00 91816.18 66849.33
PACU_VAV_MID HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_MID 25295.424 25295.424 1.207490 0.00022130 413.464 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 25295.42 25295.42 1.207490 -4.52 -4.52 0.00269911 12.80 11.59 0.00800000 -10.70 0.00150390 -10.70 79.1808 19.41 0.00686255 49.0066 17617.99 0.00 23221.14 23221.14
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_TOP 100003.108 75118.518 4.685684 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 101824.69 80967.22 4.685684 25.65 18.16 0.00995051 11.02 11.02 0.00850000 32.10 0.01411964 23.13 20.4047 24.00 0.00888157 47.7629 64451.91 0.00 103116.63 76249.09
PACU_VAV_TOP HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_TOP 24556.054 24556.054 1.405705 0.00021483 408.016 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24556.05 24556.05 1.405705 -1.64 -1.64 0.00337532 12.80 11.59 0.00800000 -10.70 0.00150390 -10.70 68.0157 17.63 0.00708607 56.5728 20204.88 0.00 23319.94 23319.94



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 14178.996 14178.996 0.636094 0.00012404 325.134 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 4.9314 5.030615 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 14179.00 14179.00 1.0000 0.76560013 0.636094 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.12403139 60.00 32.22 27.78 0.000 14179.00 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.58 0.00800000 21.00 0.00800000 51.6928 7777.32 0.00 14226.13 14226.13 0.76560013 12.80 11.60 0.00800000 33059.8 31.02 18.38 0.00800000 51641.5
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 20339.027 20339.027 0.637653 0.00017793 524.919 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 7.0738 7.216153 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 20339.03 20339.03 1.0000 0.76747600 0.637653 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.17791653 60.00 32.22 27.78 0.000 20339.03 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 51.6928 13921.67 0.00 20401.46 20401.46 0.76747600 12.80 11.60 0.00800000 33059.8 38.87 20.84 0.00800000 59642.4
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 34713.473 34713.473 1.033518 0.00030369 916.456 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 12.0731 12.316112 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 34713.47 34713.47 1.0000 1.24393684 1.033518 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.30365763 60.00 32.22 27.78 0.000 34713.47 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 51.6928 24312.13 0.00 34834.34 34834.34 1.24393684 12.80 11.60 0.00800000 33059.8 40.26 21.26 0.00800000 61063.1
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 16307.747 16307.747 0.486746 0.00014267 430.040 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 5.6717 5.785881 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 16307.75 16307.75 1.0000 0.58584455 0.486746 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.14265273 60.00 32.22 27.78 0.000 16307.75 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00762369 21.00 0.00762369 49.2959 11413.53 0.00 16360.98 16360.98 0.58584455 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60987.0
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 10589.280 10589.280 0.316080 0.00009264 279.236 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 3.6829 3.757007 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 10589.28 10589.28 1.0000 0.38043239 0.316080 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.09263019 60.00 32.22 27.78 0.000 10589.28 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00761576 21.00 0.00761576 49.2454 7411.17 0.00 10623.80 10623.80 0.38043239 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60985.4
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 16175.862 16175.862 0.482802 0.00014151 426.565 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 5.6259 5.739090 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 16175.86 16175.86 1.0000 0.58109826 0.482802 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.14149906 60.00 32.22 27.78 0.000 16175.86 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00762031 21.00 0.00762031 49.2744 11321.32 0.00 16228.68 16228.68 0.58109826 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60987.4
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 10669.289 10669.289 0.318472 0.00009334 281.344 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 3.7107 3.785394 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 10669.29 10669.29 1.0000 0.38331184 0.318472 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.09333007 60.00 32.22 27.78 0.000 10669.29 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00761885 21.00 0.00761885 49.2652 7467.10 0.00 10704.05 10704.05 0.38331184 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60985.0
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 12539.229 12539.229 0.374058 0.00010970 330.747 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 4.3611 4.448836 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12539.23 12539.23 1.0000 0.45021493 0.374058 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.10968746 60.00 32.22 27.78 0.000 12539.23 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00766246 21.00 0.00766246 49.5426 8777.66 0.00 12580.76 12580.76 0.45021493 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61003.7
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 8189.330 8189.330 0.244314 0.00007164 216.002 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 2.8482 2.905521 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8189.33 8189.33 1.0000 0.29405522 0.244314 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.07163653 60.00 32.22 27.78 0.000 8189.33 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00766823 21.00 0.00766823 49.5794 5732.46 0.00 8216.40 8216.40 0.29405522 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61001.5
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 12412.563 12412.563 0.370272 0.00010859 327.409 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 4.3170 4.403896 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12412.56 12412.56 1.0000 0.44565732 0.370272 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.10857944 60.00 32.22 27.78 0.000 12412.56 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00765427 21.00 0.00765427 49.4904 8689.14 0.00 12453.70 12453.70 0.44565732 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61004.4
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 8270.162 8270.162 0.246731 0.00007235 218.132 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 2.8763 2.934199 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8270.16 8270.16 1.0000 0.29696380 0.246731 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.07234361 60.00 32.22 27.78 0.000 8270.16 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00767555 21.00 0.00767555 49.6261 5788.95 0.00 8297.49 8297.49 0.29696380 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61000.9
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 12911.293 12911.293 0.385192 0.00011295 340.547 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 4.4905 4.580842 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12911.29 12911.29 1.0000 0.46361483 0.385192 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.11294210 60.00 32.22 27.78 0.000 12911.29 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00756463 21.00 0.00756463 48.9187 9038.62 0.00 12953.95 12953.95 0.46361483 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61001.0
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 8423.155 8423.155 0.251312 0.00007369 222.161 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 2.9295 2.988480 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8423.16 8423.16 1.0000 0.30247791 0.251312 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.07368192 60.00 32.22 27.78 0.000 8423.16 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00756395 21.00 0.00756395 48.9144 5896.50 0.00 8450.93 8450.93 0.30247791 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60998.8
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 12782.515 12782.515 0.381342 0.00011183 337.153 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 4.4457 4.535152 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12782.51 12782.51 1.0000 0.45898084 0.381342 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.11181561 60.00 32.22 27.78 0.000 12782.51 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00755736 21.00 0.00755736 48.8722 8948.61 0.00 12824.77 12824.77 0.45898084 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61001.7
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 8499.421 8499.421 0.253592 0.00007436 224.170 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 2.9560 3.015539 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8499.42 8499.42 1.0000 0.30522246 0.253592 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.07434906 60.00 32.22 27.78 0.000 8499.42 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00756993 21.00 0.00756993 48.9526 5949.81 0.00 8527.44 8527.44 0.30522246 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60998.3
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 90591.554 67166.808 4.129531 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.6267 1004.8586 1.2036 PACU_VAV_BOT FAN Fan:VariableVolume 4.129531 4.97028315   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 Sensible 92652.33 72337.50 1.0227 4.97028315 4.129531 25.87 18.35 0.01010608 51760.4 11.02 11.02 0.00850000 32508.8 -999.0 -999.00 -999.00 -999.00 9039.589 83612.74 32.10 0.01411964 23.13 0.95610000 23.1527 24.00 0.00889687 24.00 0.00889687 47.8436 56809.34 0.00 93412.05 68201.22 4.77399454 26.67 19.44 0.01118466 55322.4 12.69 12.66 0.00911415 35755.5
PACU_VAV_BOT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 25001.333 25001.333 1.238859 0.00021872 410.106 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PACU_VAV_BOT FAN Fan:VariableVolume 4.129531 4.97028315   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 8.6953 8.870308 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:20:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 25001.33 25001.33 1.0000 1.49108495 1.238859 -3.89 -3.89 0.00281807 3122.5 12.80 11.59 0.00800000 33059.8 0.21870025 60.00 32.22 27.78 0.000 25001.33 -10.70 0.00150390 -10.70 0.95610000 77.1758 19.15 0.00726173 19.60 0.00671567 47.4142 14920.77 0.00 23121.26 23121.26 1.49108495 2.80 0.26 0.00281807 9876.1 18.15 8.34 0.00281807 25382.4
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 89043.870 65812.298 4.024966 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.7326 1004.8586 1.2036 PACU_VAV_MID FAN Fan:VariableVolume 4.024966 4.84442878   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 Sensible 91197.08 70705.15 1.0242 4.84442878 4.024966 25.92 18.42 0.01016307 51955.4 11.02 11.02 0.00850000 32509.0 -999.0 -999.00 -999.00 -999.00 8810.695 82386.39 32.10 0.01411964 23.13 0.95610000 23.7542 24.00 0.00893041 24.00 0.00893041 48.0217 55370.35 0.00 91816.18 66849.33 4.65311047 26.67 19.44 0.01118466 55322.4 12.61 12.60 0.00908092 35590.2
PACU_VAV_MID HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 25295.424 25295.424 1.207490 0.00022130 413.464 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PACU_VAV_MID FAN Fan:VariableVolume 4.024966 4.84442878   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 8.7976 8.974650 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 25295.42 25295.42 1.0000 1.45332864 1.207490 -4.52 -4.52 0.00269911 2184.7 12.80 11.59 0.00800000 33059.8 0.22127283 60.00 32.22 27.78 0.000 25295.42 -10.70 0.00150390 -10.70 0.95610000 79.1808 18.98 0.00724481 19.41 0.00686255 49.0066 17617.99 0.00 23221.14 23221.14 1.45332864 2.80 0.08 0.00269911 9577.9 18.62 8.43 0.00269911 25555.8
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 100003.108 75118.518 4.685684 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.3375 1004.8586 1.2036 PACU_VAV_TOP FAN Fan:VariableVolume 4.685684 5.63966517   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 Sensible 101824.69 80967.22 1.0182 5.63966517 4.685684 25.65 18.16 0.00995051 51136.1 11.02 11.02 0.00850000 32508.3 -999.0 -999.00 -999.00 -999.00 10257.013 91567.67 32.10 0.01411964 23.13 0.95610000 20.4047 24.00 0.00888157 24.00 0.00888157 47.7629 64451.91 0.00 103116.63 76249.09 5.41694102 26.67 19.44 0.01118466 55322.4 12.89 12.87 0.00923999 36286.4
PACU_VAV_TOP HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 24556.054 24556.054 1.405705 0.00021483 408.016 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PACU_VAV_TOP FAN Fan:VariableVolume 4.685684 5.63966517   4197.9300 999.8980 2.46553157 54.44 82.22 27.78 287526.58 8.5404 8.712326 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:30:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24556.05 24556.05 1.0000 1.69189955 1.405705 -1.64 -1.64 0.00337532 6779.5 12.80 11.59 0.00800000 33059.8 0.21480516 60.00 32.22 27.78 0.000 24556.05 -10.70 0.00150390 -10.70 0.95610000 68.0157 17.61 0.00735495 17.63 0.00708607 56.5728 20204.88 0.00 23319.94 23319.94 1.69189955 2.80 1.06 0.00337532 11272.6 16.43 8.18 0.00337532 25055.9



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PACU_VAV_BOT_OA_CONTROLLER DifferentialEnthalpy 0.00 4.13 -      
PACU_VAV_MID_OA_CONTROLLER DifferentialEnthalpy 0.00 4.02 -      
PACU_VAV_TOP_OA_CONTROLLER DifferentialEnthalpy 0.00 4.69 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area PERIMETER_MID_ZN_2_OA_MULT 1.00 1.00  
PERIMETER_MID_ZN_1 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_BOTTOM 2428.17 2598.33 76.17
CORE_MID 2437.67 3110.67 375.83
CORE_TOP 2929.50 3342.83 1035.33
PERIMETER_TOP_ZN_3 3689.83 3629.17 1905.33
PERIMETER_TOP_ZN_2 3698.00 3420.50 1674.33
PERIMETER_TOP_ZN_1 3508.67 3170.17 1374.83
PERIMETER_TOP_ZN_4 3740.83 3439.83 1747.67
PERIMETER_BOT_ZN_3 3466.83 3667.50 1683.17
PERIMETER_BOT_ZN_2 3423.00 3246.17 1266.00
PERIMETER_BOT_ZN_1 3310.33 3520.33 1394.83
PERIMETER_BOT_ZN_4 3504.50 3303.33 1361.50
PERIMETER_MID_ZN_3 3424.50 3428.67 1486.17
PERIMETER_MID_ZN_2 2941.00 2815.17 1175.33
PERIMETER_MID_ZN_1 3274.33 2943.00 974.83
PERIMETER_MID_ZN_4 3498.33 3233.83 1344.33
TOPFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00
Facility 4840.50 4270.17 2433.83
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_BOTTOM 8.33 0.00 8.33 0.00
CORE_MID 5.50 0.00 5.00 0.00
CORE_TOP 8.33 0.00 7.67 0.00
PERIMETER_TOP_ZN_3 43.50 4.67 26.67 4.33
PERIMETER_TOP_ZN_2 23.50 38.00 8.67 37.33
PERIMETER_TOP_ZN_1 20.67 32.83 9.83 32.00
PERIMETER_TOP_ZN_4 25.33 32.33 11.50 22.67
PERIMETER_BOT_ZN_3 28.67 0.00 22.83 0.00
PERIMETER_BOT_ZN_2 8.67 18.67 3.83 18.67
PERIMETER_BOT_ZN_1 323.00 38.17 322.00 37.83
PERIMETER_BOT_ZN_4 12.67 18.50 7.67 14.33
PERIMETER_MID_ZN_3 19.67 0.50 13.33 0.50
PERIMETER_MID_ZN_2 10.33 31.83 4.67 31.67
PERIMETER_MID_ZN_1 9.50 30.33 4.50 30.17
PERIMETER_MID_ZN_4 13.50 27.50 7.83 19.83
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 356.33 136.83 337.83 122.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.88 52.94 2698.04 0.682 0.000 0.000 0.000
CORE_MID 21.88 52.94 2698.04 0.567 0.000 0.000 0.000
CORE_TOP 21.88 52.94 2698.04 0.560 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.61 11.16 568.77 0.651 0.048 0.000 0.000
PERIMETER_TOP_ZN_2 2.92 7.07 360.08 0.895 0.050 0.000 0.000
PERIMETER_TOP_ZN_1 4.61 11.16 568.77 0.969 0.048 0.000 0.000
PERIMETER_TOP_ZN_4 2.92 7.06 360.05 0.903 0.050 0.000 0.000
PERIMETER_BOT_ZN_3 4.61 11.16 568.77 0.568 0.025 0.000 0.000
PERIMETER_BOT_ZN_2 2.92 7.07 360.08 0.803 0.027 0.000 0.000
PERIMETER_BOT_ZN_1 4.61 11.16 568.77 0.828 0.832 0.000 0.000
PERIMETER_BOT_ZN_4 2.92 7.06 360.05 0.792 0.027 0.000 0.000
PERIMETER_MID_ZN_3 4.61 11.16 568.77 0.647 0.040 0.000 0.000
PERIMETER_MID_ZN_2 2.56 7.07 360.08 0.825 0.045 0.000 0.000
PERIMETER_MID_ZN_1 4.61 11.16 568.77 0.978 0.040 0.000 0.000
PERIMETER_MID_ZN_4 2.92 7.06 360.05 0.898 0.042 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.88 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_MID 21.88 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_TOP 21.88 52.94 2698.04 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.61 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 2.92 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 4.61 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 2.92 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 4.61 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 2.92 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 4.61 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 2.92 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 4.61 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 2.56 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 4.61 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 2.92 7.06 360.05 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_BOTTOM PACU_VAV_BOT 21.88 52.94 2698.04 983.54 0.0000 0.425
CORE_MID PACU_VAV_MID 21.88 52.94 2698.04 983.54 0.0000 0.425
CORE_TOP PACU_VAV_TOP 21.88 52.94 2698.04 983.54 0.0000 0.425
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 4.61 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 2.92 7.07 360.08 131.26 0.0000 0.057
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 4.61 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 2.92 7.06 360.05 131.25 0.0000 0.057
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 4.61 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 2.92 7.07 360.08 131.26 0.0000 0.057
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 4.61 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 2.92 7.06 360.05 131.25 0.0000 0.057
PERIMETER_MID_ZN_3 PACU_VAV_MID 4.61 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_2 PACU_VAV_MID 2.56 7.07 360.08 131.26 0.0000 0.057
PERIMETER_MID_ZN_1 PACU_VAV_MID 4.61 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_4 PACU_VAV_MID 2.92 7.06 360.05 131.25 0.0000 0.057
Total Facility   110.49 268.17 13667.13 4982.19 0.0000 2.151


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_BOTTOM 10745149.23 0.00 10745149.23 0.00 10745149.23 13393058.27 5440.85 607.51 2711.63 28.51
CORE_MID 8953122.00 0.00 8953122.00 0.00 8953122.00 13393058.27 5692.90 837.12 2229.98 26.00
CORE_TOP 8859979.81 0.00 8859979.81 0.00 8859979.81 13393058.27 5740.29 1042.69 1977.03 44.18
PERIMETER_TOP_ZN_3 2171052.05 0.00 2171052.05 313577.76 2484629.80 2823374.22 4623.15 847.18 3289.67 44.18
PERIMETER_TOP_ZN_2 1884746.82 0.00 1884746.82 209050.58 2093797.41 1787429.43 4513.59 598.93 3647.49 44.18
PERIMETER_TOP_ZN_1 3224612.86 0.00 3224612.86 313577.76 3538190.62 2823374.22 4364.58 665.48 3729.94 44.18
PERIMETER_TOP_ZN_4 1903507.17 0.00 1903507.17 209050.58 2112557.76 1787312.18 4547.18 1050.51 3162.31 44.18
PERIMETER_BOT_ZN_3 1890781.85 0.00 1890781.85 166727.58 2057509.43 2823374.22 5614.48 599.17 2546.35 28.51
PERIMETER_BOT_ZN_2 1690318.05 0.00 1690318.05 111151.05 1801469.10 1787429.43 4970.70 665.45 3123.85 28.51
PERIMETER_BOT_ZN_1 2757340.18 0.00 2757340.18 2860908.58 5618248.77 2823374.22 4785.32 698.48 3276.20 28.51
PERIMETER_BOT_ZN_4 1665787.30 0.00 1665787.30 111151.05 1776938.35 1787312.18 4942.31 489.89 3327.80 28.51
PERIMETER_MID_ZN_3 2152928.79 0.00 2152928.79 261029.36 2413958.15 2823374.22 4735.02 1020.51 3004.47 26.00
PERIMETER_MID_ZN_2 1739435.89 0.00 1739435.89 174018.53 1913454.42 1601953.02 4419.13 524.74 3816.13 935.00
PERIMETER_MID_ZN_1 3251730.81 0.00 3251730.81 261029.36 3512760.17 2823374.22 4375.41 980.48 3404.11 26.00
PERIMETER_MID_ZN_4 1891122.16 0.00 1891122.16 174018.53 2065140.69 1787312.18 4604.79 1010.24 3144.97 26.00
Total Facility 54781614.97 0.00 54781614.97 5165290.72 59946905.69 67658168.57 6412.82 1555.42 4347.55 980.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_BOTTOM 0.5012 0.0000 0.5012 0.0000 0.5012 0.4247 2632.41 607.35 2703.25
CORE_MID 0.4170 0.0000 0.4170 0.0000 0.4170 0.4247 2888.01 837.01 2217.98
CORE_TOP 0.4123 0.0000 0.4123 0.0000 0.4123 0.4247 2938.79 1042.69 1961.53
PERIMETER_TOP_ZN_3 0.1011 0.0000 0.1011 0.0075 0.1086 0.0895 1821.65 847.18 3274.17
PERIMETER_TOP_ZN_2 0.0878 0.0000 0.0878 0.0050 0.0928 0.0567 1712.09 598.93 3631.99
PERIMETER_TOP_ZN_1 0.1503 0.0000 0.1503 0.0075 0.1578 0.0895 1563.08 665.48 3714.44
PERIMETER_TOP_ZN_4 0.0886 0.0000 0.0886 0.0050 0.0936 0.0567 1745.68 1050.51 3146.81
PERIMETER_BOT_ZN_3 0.0882 0.0000 0.0882 0.0040 0.0921 0.0895 2806.04 599.17 2537.79
PERIMETER_BOT_ZN_2 0.0789 0.0000 0.0789 0.0026 0.0815 0.0567 2162.27 665.29 3115.44
PERIMETER_BOT_ZN_1 0.1287 0.0000 0.1287 0.1299 0.2586 0.0895 1976.88 698.31 3267.81
PERIMETER_BOT_ZN_4 0.0777 0.0000 0.0777 0.0026 0.0803 0.0567 2133.88 489.89 3319.22
PERIMETER_MID_ZN_3 0.1003 0.0000 0.1003 0.0062 0.1065 0.0895 1930.02 1020.51 2992.47
PERIMETER_MID_ZN_2 0.0809 0.0000 0.0809 0.0044 0.0853 0.0567 1614.35 524.55 2895.10
PERIMETER_MID_ZN_1 0.1517 0.0000 0.1517 0.0062 0.1579 0.0895 1570.41 980.48 3392.11
PERIMETER_MID_ZN_4 0.0881 0.0000 0.0881 0.0041 0.0923 0.0567 1799.86 1010.22 3132.92
Total Facility 2.5529 0.0000 2.5529 0.1851 2.7379 2.1513 3601.46 1555.04 4328.82


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PACU_VAV_BOT 27161113.42 0.00 27161113.42 22614548.33 4210.95 1.33 4547.72 28.51
PACU_VAV_MID 26058644.17 0.00 26058644.17 22429071.92 4188.06 3.39 4568.55 26.00
PACU_VAV_TOP 26139129.32 0.00 26139129.32 22614548.33 4209.74 0.91 4549.35 44.10


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PACU_VAV_BOT 1.2669 0.0000 1.2669 0.7171 1402.50 1.33 4539.17
PACU_VAV_MID 1.2144 0.0000 1.2144 0.7084 1383.27 3.39 4556.34
PACU_VAV_TOP 1.2171 0.0000 1.2171 0.7171 1408.24 0.91 4533.85


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PACU_VAV_BOT 0.00 136.84 1838.48 0.00 0.00 0.00 2718.97 0.00 0.00 0.00
PACU_VAV_MID 0.00 102.10 1816.25 0.00 0.00 0.00 2793.10 0.00 0.00 0.00
PACU_VAV_TOP 0.00 64.62 1803.64 0.00 0.00 0.00 2854.38 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PACU_VAV_BOT 0.0000 1.3140 2.3937 0.0000 0.0000 0.0000 1.1113 0.0000 0.0000 0.0000
PACU_VAV_MID 0.0000 1.2804 2.2570 0.0000 0.0000 0.0000 1.0907 0.0000 0.0000 0.0000
PACU_VAV_TOP 0.0000 1.2294 2.2841 0.0000 0.0000 0.0000 1.0992 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Surfaces by Class

Total Outdoors
Wall 72 24
Floor 30 4
Roof 26 1
Internal Mass 15 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 18 18
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 3
Conditioned Zones 18
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1010
Defaulted Fields 582
Fields with Defaults 2434
Autosized Fields 194
Autosizable Fields 250
Autocalculated Fields 156
Autocalculatable Fields 277



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 1203.40 11981.96 23-APR-17:10 146275.93 19-JUN-10:30
Electricity:Building 825.91 11650.06 09-APR-17:10 56534.15 02-JAN-16:40
Electricity:Zone:CORE_BOTTOM 229.44 3625.33 01-JAN-00:10 14695.26 02-JAN-08:10
Electricity:SpaceType:GENERAL 825.91 11650.06 09-APR-17:10 56534.15 02-JAN-16:40
InteriorLights:Electricity 167.00 772.31 01-JAN-08:50 17672.30 02-JAN-16:40
InteriorLights:Electricity:Zone:CORE_BOTTOM 39.80 193.79 01-JAN-00:10 3488.70 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 167.00 772.31 01-JAN-08:50 17672.30 02-JAN-16:40
LightsWired:InteriorLights:Electricity 167.00 772.31 01-JAN-08:50 17672.30 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 39.80 193.79 01-JAN-00:10 3488.70 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 167.00 772.31 01-JAN-08:50 17672.30 02-JAN-16:40
Electricity:Zone:CORE_MID 155.22 2025.33 01-JAN-00:10 10297.02 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 39.80 193.79 01-JAN-00:10 3488.70 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 39.80 193.79 01-JAN-00:10 3488.70 02-JAN-08:10
Electricity:Zone:CORE_TOP 155.22 2025.33 01-JAN-00:10 10297.02 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 39.80 193.79 01-JAN-00:10 3488.70 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 39.80 193.79 01-JAN-00:10 3488.70 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 29.23 405.59 02-APR-17:10 2170.70 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 4.89 19.49 01-JAN-08:50 735.45 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 4.89 19.49 01-JAN-08:50 735.45 02-JAN-16:40
Electricity:Zone:PERIMETER_TOP_ZN_2 18.49 256.76 09-APR-17:10 1374.17 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 3.09 12.34 01-JAN-07:50 465.60 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 3.09 12.34 01-JAN-07:50 465.60 02-JAN-16:40
Electricity:Zone:PERIMETER_TOP_ZN_1 29.16 405.59 19-MAR-17:10 2170.69 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 4.83 19.49 01-JAN-07:50 735.45 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 4.83 19.49 01-JAN-07:50 735.45 02-JAN-16:40
Electricity:Zone:PERIMETER_TOP_ZN_4 18.47 256.75 12-MAR-17:10 1374.14 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 3.06 12.34 01-JAN-08:40 465.57 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 3.06 12.34 01-JAN-08:40 465.57 02-JAN-16:40
Electricity:Zone:PERIMETER_BOT_ZN_3 29.22 405.59 02-APR-17:10 2170.70 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 4.88 19.49 01-JAN-08:40 735.45 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 4.88 19.49 01-JAN-08:40 735.45 02-JAN-16:40
Electricity:Zone:PERIMETER_BOT_ZN_2 18.49 256.76 09-APR-17:10 1374.17 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 3.08 12.34 01-JAN-07:50 465.60 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 3.08 12.34 01-JAN-07:50 465.60 02-JAN-16:40
Electricity:Zone:PERIMETER_BOT_ZN_1 29.16 405.59 19-MAR-17:10 2170.69 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 4.83 19.49 01-JAN-07:50 735.45 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 4.83 19.49 01-JAN-07:50 735.45 02-JAN-16:40
Electricity:Zone:PERIMETER_BOT_ZN_4 18.46 256.75 12-MAR-17:10 1374.14 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 3.06 12.34 01-JAN-08:40 465.57 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 3.06 12.34 01-JAN-08:40 465.57 02-JAN-16:40
Electricity:Zone:PERIMETER_MID_ZN_3 29.23 405.59 02-APR-17:10 2170.70 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 4.89 19.49 01-JAN-08:50 735.45 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 4.89 19.49 01-JAN-08:50 735.45 02-JAN-16:40
Electricity:Zone:PERIMETER_MID_ZN_2 18.49 256.76 09-APR-17:10 1374.17 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 3.09 12.34 01-JAN-07:50 465.60 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 3.09 12.34 01-JAN-07:50 465.60 02-JAN-16:40
Electricity:Zone:PERIMETER_MID_ZN_1 29.16 405.59 19-MAR-17:10 2170.69 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 4.83 19.49 01-JAN-07:50 735.45 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 4.83 19.49 01-JAN-07:50 735.45 02-JAN-16:40
Electricity:Zone:PERIMETER_MID_ZN_4 18.47 256.75 12-MAR-17:10 1374.14 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 3.06 12.34 01-JAN-08:40 465.57 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 3.06 12.34 01-JAN-08:40 465.57 02-JAN-16:40
InteriorEquipment:Electricity 658.91 10877.75 01-JAN-00:10 38886.07 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 189.64 3431.54 01-JAN-00:10 11206.55 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 658.91 10877.75 01-JAN-00:10 38886.07 02-JAN-08:10
ElevatorLift:InteriorEquipment:Electricity 73.68 1600.00 01-JAN-00:10 4325.57 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 73.68 1600.00 01-JAN-00:10 4325.57 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL 73.68 1600.00 01-JAN-00:10 4325.57 02-JAN-07:10
ElevatorLightsFan:InteriorEquipment:Electricity 0.54 0.00 01-JAN-00:10 72.66 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 0.54 0.00 01-JAN-00:10 72.66 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL 0.54 0.00 01-JAN-00:10 72.66 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
ElectricityProduced:Facility 136.08 -0.00 01-JAN-16:30 26130.14 02-JUN-11:50
ElectricityProduced:Plant 136.08 -0.00 01-JAN-16:30 26130.14 02-JUN-11:50
Photovoltaic:ElectricityProduced 142.41 0.00 01-JAN-00:10 27211.52 02-JUN-11:50
PowerConversion:ElectricityProduced -6.34 -1081.38 02-JUN-11:50 0.00 01-JAN-00:10
Electricity:Plant 54.73 0.00 01-JAN-00:40 7265.86 06-FEB-12:20
Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
DCtoACInverter Ancillary:Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 288.69 331.90 13-AUG-17:10 88983.42 19-JUN-10:30
ExteriorEquipment:Electricity 25.33 331.43 01-JAN-00:10 1410.29 09-JAN-08:20
Transformer:ExteriorEquipment:Electricity 25.33 331.43 01-JAN-00:10 1410.29 09-JAN-08:20
ElectricityPurchased:Facility 1067.91 0.00 12-FEB-11:00 128041.36 16-AUG-15:30
ElectricityPurchased:Plant 1067.91 0.00 12-FEB-11:00 128041.36 16-AUG-15:30
Cogeneration:ElectricityPurchased 1067.91 0.00 12-FEB-11:00 128041.36 16-AUG-15:30
General:Cogeneration:ElectricityPurchased 1067.91 0.00 12-FEB-11:00 128041.36 16-AUG-15:30
ElectricitySurplusSold:Facility 0.59 0.00 01-JAN-00:10 9242.09 14-MAY-11:50
ElectricitySurplusSold:Plant 0.59 0.00 01-JAN-00:10 9242.09 14-MAY-11:50
Cogeneration:ElectricitySurplusSold 0.59 0.00 01-JAN-00:10 9242.09 14-MAY-11:50
General:Cogeneration:ElectricitySurplusSold 0.59 0.00 01-JAN-00:10 9242.09 14-MAY-11:50
ElectricityNet:Facility 1067.32 -9242.09 14-MAY-11:50 128041.36 16-AUG-15:30
ElectricityNet:Plant 1067.32 -9242.09 14-MAY-11:50 128041.36 16-AUG-15:30
Cogeneration:ElectricityNet 1067.32 -9242.09 14-MAY-11:50 128041.36 16-AUG-15:30
General:Cogeneration:ElectricityNet 1067.32 -9242.09 14-MAY-11:50 128041.36 16-AUG-15:30
Fans:Electricity 87.80 0.00 01-JAN-00:40 26290.20 30-MAY-14:30
General:Fans:Electricity 87.80 0.00 01-JAN-00:40 26290.20 30-MAY-14:30
ExteriorLights:Electricity 34.07 0.00 01-JAN-07:30 3824.74 01-JAN-06:10
General:ExteriorLights:Electricity 34.07 0.00 01-JAN-07:30 3824.74 01-JAN-06:10
Cooling:Electricity 175.56 0.00 01-JAN-00:10 67361.36 19-JUN-12:10
General:Cooling:Electricity 175.56 0.00 01-JAN-00:10 67361.36 19-JUN-12:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:Electricity 52.88 0.00 01-JAN-00:10 6688.84 06-FEB-12:40
Water Heater:WaterSystems:Electricity 52.88 0.00 01-JAN-00:10 6688.84 06-FEB-12:40
Pumps:Electricity 1.85 0.00 01-JAN-00:40 766.86 02-JAN-07:10
General:Pumps:Electricity 1.85 0.00 01-JAN-00:40 766.86 02-JAN-07:10
WIRED_LTG_ELECTRICITY 4.69 0.00 01-JAN-00:10 496.59 02-JAN-16:50
WIRED_INT_EQUIP1 632.98 10877.75 01-JAN-00:10 36042.38 02-JAN-13:10
WIRED_INT_EQUIP2 611.16 9277.75 01-JAN-00:10 37604.10 02-JAN-08:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 327.94 0.00 01-JAN-00:40 234932.43 02-JAN-07:20
NaturalGas:Plant 327.94 0.00 01-JAN-00:40 234932.43 02-JAN-07:20
Heating:NaturalGas 327.94 0.00 01-JAN-00:40 234932.43 02-JAN-07:20
Boiler:Heating:NaturalGas 327.94 0.00 01-JAN-00:40 234932.43 02-JAN-07:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Facility 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 2348.85 0.00 01-JAN-00:40 515821.39 02-JAN-07:20
EnergyTransfer:Building 1006.49 0.00 01-JAN-00:40 159142.56 14-AUG-14:10
EnergyTransfer:Zone:CORE_BOTTOM 178.29 0.00 01-JAN-00:40 22681.94 05-SEP-07:20
Heating:EnergyTransfer 87.06 0.00 01-JAN-00:40 136157.08 02-JAN-05:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.33 0.00 01-JAN-00:10 7785.45 02-JAN-06:10
General:Heating:EnergyTransfer 87.06 0.00 01-JAN-00:40 136157.08 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.33 0.00 01-JAN-00:10 7785.45 02-JAN-06:10
Cooling:EnergyTransfer 919.43 0.00 01-JAN-00:40 159142.56 14-AUG-14:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 177.96 0.00 01-JAN-00:40 22681.94 05-SEP-07:20
General:Cooling:EnergyTransfer 919.43 0.00 01-JAN-00:40 159142.56 14-AUG-14:10
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 177.96 0.00 01-JAN-00:40 22681.94 05-SEP-07:20
EnergyTransfer:Zone:TOPFLOOR_PLENUM 43.65 0.00 01-JAN-00:40 12061.05 06-FEB-06:20
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 13.71 0.00 01-JAN-00:40 12061.05 06-FEB-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 13.71 0.00 01-JAN-00:40 12061.05 06-FEB-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 29.94 0.00 01-JAN-00:10 11152.89 19-JUN-13:30
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 29.94 0.00 01-JAN-00:10 11152.89 19-JUN-13:30
EnergyTransfer:Zone:MIDFLOOR_PLENUM 24.02 0.00 01-JAN-00:40 8268.63 02-JAN-08:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 7.14 0.00 01-JAN-00:40 8268.63 02-JAN-08:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 7.14 0.00 01-JAN-00:40 8268.63 02-JAN-08:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 16.88 0.00 01-JAN-00:10 5154.81 14-AUG-14:40
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 16.88 0.00 01-JAN-00:10 5154.81 14-AUG-14:40
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 24.10 0.00 01-JAN-00:40 6626.93 02-JAN-09:10
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 4.22 0.00 01-JAN-00:40 6626.93 02-JAN-09:10
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 4.22 0.00 01-JAN-00:40 6626.93 02-JAN-09:10
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 19.89 0.00 01-JAN-00:10 5115.74 05-SEP-07:10
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 19.89 0.00 01-JAN-00:10 5115.74 05-SEP-07:10
EnergyTransfer:Zone:CORE_MID 139.78 0.00 01-JAN-00:40 18910.61 05-SEP-07:20
Heating:EnergyTransfer:Zone:CORE_MID 0.86 0.00 01-JAN-00:20 13949.00 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.86 0.00 01-JAN-00:20 13949.00 02-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_MID 138.92 0.00 01-JAN-00:40 18910.61 05-SEP-07:20
General:Cooling:EnergyTransfer:Zone:CORE_MID 138.92 0.00 01-JAN-00:40 18910.61 05-SEP-07:20
EnergyTransfer:Zone:CORE_TOP 135.34 0.00 01-JAN-00:40 20280.23 02-JAN-05:10
Heating:EnergyTransfer:Zone:CORE_TOP 4.33 0.00 01-JAN-00:40 20280.23 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 4.33 0.00 01-JAN-00:40 20280.23 02-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_TOP 131.00 0.00 01-JAN-00:20 19625.45 14-AUG-13:10
General:Cooling:EnergyTransfer:Zone:CORE_TOP 131.00 0.00 01-JAN-00:20 19625.45 14-AUG-13:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 39.82 0.00 01-JAN-00:40 7947.38 02-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 8.83 0.00 01-JAN-00:40 7947.38 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 8.83 0.00 01-JAN-00:40 7947.38 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 30.99 0.00 01-JAN-00:10 7482.96 19-JUN-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 30.99 0.00 01-JAN-00:10 7482.96 19-JUN-14:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 33.93 0.00 01-JAN-00:40 9115.09 26-JUN-08:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 4.51 0.00 01-JAN-00:40 6471.13 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 4.51 0.00 01-JAN-00:40 6471.13 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 29.42 0.00 01-JAN-00:10 9115.09 26-JUN-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 29.42 0.00 01-JAN-00:10 9115.09 26-JUN-08:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 55.76 0.00 01-JAN-00:40 12561.13 28-SEP-12:50
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 5.48 0.00 01-JAN-00:40 9034.20 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 5.48 0.00 01-JAN-00:40 9034.20 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 50.28 0.00 01-JAN-00:10 12561.13 28-SEP-12:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 50.28 0.00 01-JAN-00:10 12561.13 28-SEP-12:50
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 34.91 0.00 01-JAN-00:40 9365.46 15-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 5.23 0.00 01-JAN-00:40 6639.90 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 5.23 0.00 01-JAN-00:40 6639.90 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 29.67 0.00 01-JAN-00:10 9365.46 15-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 29.67 0.00 01-JAN-00:10 9365.46 15-AUG-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 31.99 0.00 01-JAN-00:40 6166.18 02-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 4.79 0.00 01-JAN-00:40 6166.18 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 4.79 0.00 01-JAN-00:40 6166.18 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 27.20 0.00 01-JAN-00:10 5869.75 14-AUG-13:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 27.20 0.00 01-JAN-00:10 5869.75 14-AUG-13:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 29.25 0.00 01-JAN-00:40 7214.91 05-SEP-09:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 2.06 0.00 01-JAN-00:40 4827.67 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 2.06 0.00 01-JAN-00:40 4827.67 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 27.18 0.00 01-JAN-00:10 7214.91 05-SEP-09:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 27.18 0.00 01-JAN-00:10 7214.91 05-SEP-09:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 53.11 0.00 01-JAN-00:40 11814.80 19-JUN-12:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 12.38 0.00 01-JAN-00:40 9970.55 02-JAN-07:50
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 12.38 0.00 01-JAN-00:40 9970.55 02-JAN-07:50
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 40.73 0.00 01-JAN-00:20 11814.80 19-JUN-12:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 40.73 0.00 01-JAN-00:20 11814.80 19-JUN-12:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 29.35 0.00 01-JAN-00:40 7501.58 21-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 2.40 0.00 01-JAN-00:40 5055.01 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 2.40 0.00 01-JAN-00:40 5055.01 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 26.95 0.00 01-JAN-00:10 7501.58 21-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 26.95 0.00 01-JAN-00:10 7501.58 21-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 35.95 0.00 01-JAN-00:40 6743.49 19-JUN-14:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 4.09 0.00 01-JAN-00:40 6570.31 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 4.09 0.00 01-JAN-00:40 6570.31 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 31.86 0.00 01-JAN-00:10 6743.49 19-JUN-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 31.86 0.00 01-JAN-00:10 6743.49 19-JUN-14:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 30.42 0.00 01-JAN-00:40 8975.63 26-JUN-08:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 2.05 0.00 01-JAN-00:40 5320.09 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 2.05 0.00 01-JAN-00:40 5320.09 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 28.37 0.00 01-JAN-00:10 8975.63 26-JUN-08:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 28.37 0.00 01-JAN-00:10 8975.63 26-JUN-08:20
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 54.30 0.00 01-JAN-00:40 11679.45 28-SEP-12:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 2.27 0.00 01-JAN-00:40 7541.64 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 2.27 0.00 01-JAN-00:40 7541.64 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 52.03 0.00 01-JAN-00:10 11679.45 28-SEP-12:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 52.03 0.00 01-JAN-00:10 11679.45 28-SEP-12:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 32.53 0.00 01-JAN-00:40 8968.87 15-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 2.38 0.00 01-JAN-00:40 5393.37 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 2.38 0.00 01-JAN-00:40 5393.37 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 30.15 0.00 01-JAN-00:10 8968.87 15-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 30.15 0.00 01-JAN-00:10 8968.87 15-AUG-16:00
PlantLoopHeatingDemand:Facility 291.55 0.00 01-JAN-00:40 198866.89 02-JAN-08:10
PlantLoopHeatingDemand:Plant 50.06 0.00 01-JAN-00:10 6459.49 09-FEB-12:10
WaterSystems:PlantLoopHeatingDemand 50.06 0.00 01-JAN-00:10 6459.49 09-FEB-12:10
General:WaterSystems:PlantLoopHeatingDemand 50.06 0.00 01-JAN-00:10 6459.49 09-FEB-12:10
EnergyTransfer:HVAC 1052.65 0.00 01-JAN-00:40 269701.26 16-AUG-12:30
HeatingCoils:EnergyTransfer 241.49 0.00 01-JAN-00:40 196628.79 02-JAN-07:10
PlantLoopHeatingDemand:HVAC 241.49 0.00 01-JAN-00:40 196628.79 02-JAN-07:10
HeatingCoils:PlantLoopHeatingDemand 241.49 0.00 01-JAN-00:40 196628.79 02-JAN-07:10
CoolingCoils:EnergyTransfer 811.16 0.00 01-JAN-00:10 269697.70 16-AUG-12:30
EnergyTransfer:Plant 289.71 0.00 01-JAN-00:40 198029.09 02-JAN-08:10
WaterSystems:EnergyTransfer 50.06 0.00 01-JAN-00:10 6459.49 09-FEB-12:10
WaterUse:WaterSystems:EnergyTransfer 50.06 0.00 01-JAN-00:10 6459.49 09-FEB-12:10
Boilers:EnergyTransfer 239.65 0.00 01-JAN-00:40 195541.05 02-JAN-07:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_BOTTOM 0.000 0.000 0.327 -177.962 0.000 0.000 33.258 39.795 189.644 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -85.063
CORE_MID 0.000 0.000 0.857 -138.924 0.000 0.000 34.185 39.795 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -51.339
CORE_TOP 0.000 0.000 4.334 -131.003 0.000 0.000 34.763 39.795 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -63.314
PERIMETER_TOP_ZN_3 0.000 0.000 8.833 -30.985 0.000 0.000 7.477 4.894 24.333 18.669 0.000 0.062 0.000 0.000 -28.352 0.000 -4.267 -0.663
PERIMETER_TOP_ZN_2 0.000 0.000 4.509 -29.419 0.000 0.000 4.660 3.089 15.404 33.279 0.000 0.040 0.001 0.000 -18.010 0.000 -2.899 -10.653
PERIMETER_TOP_ZN_1 0.000 0.000 5.483 -50.281 0.000 0.000 7.258 4.832 24.332 67.868 0.000 0.060 0.000 0.000 -27.004 0.000 -4.474 -28.074
PERIMETER_TOP_ZN_4 0.000 0.000 5.232 -29.674 0.000 0.000 4.690 3.065 15.403 33.891 0.000 0.040 0.001 0.000 -18.542 0.000 -2.914 -11.189
PERIMETER_BOT_ZN_3 0.000 0.000 4.789 -27.196 0.000 0.000 7.465 4.884 24.333 19.056 0.000 0.037 0.000 0.000 -29.233 0.000 -2.372 -1.763
PERIMETER_BOT_ZN_2 0.000 0.000 2.065 -27.184 0.000 0.000 4.636 3.084 15.404 33.494 0.000 0.022 0.000 0.000 -18.907 0.000 -1.635 -10.978
PERIMETER_BOT_ZN_1 0.000 0.000 12.378 -40.733 0.000 0.000 7.453 4.826 24.332 68.721 0.000 1.975 0.001 0.000 -28.281 0.000 -31.550 -19.122
PERIMETER_BOT_ZN_4 0.000 0.000 2.400 -26.947 0.000 0.000 4.664 3.060 15.403 34.176 0.000 0.022 0.000 0.000 -19.493 0.000 -1.644 -11.640
PERIMETER_MID_ZN_3 0.000 0.000 4.095 -31.857 0.000 0.000 7.412 4.894 24.333 18.545 0.000 0.053 6.116 0.000 -29.852 0.000 -3.738 -0.000
PERIMETER_MID_ZN_2 0.000 0.000 2.054 -28.369 0.000 0.000 3.406 3.089 15.404 33.072 0.000 0.033 0.001 0.000 -18.952 0.000 -2.543 -7.194
PERIMETER_MID_ZN_1 0.000 0.000 2.265 -52.032 0.000 0.000 7.184 4.832 24.332 67.690 0.000 0.051 0.001 0.000 -28.406 0.000 -3.918 -21.997
PERIMETER_MID_ZN_4 0.000 0.000 2.378 -30.149 0.000 0.000 4.645 3.065 15.403 33.812 0.000 0.034 0.000 0.000 -19.519 0.000 -2.552 -7.118
TOPFLOOR_PLENUM 13.708 -29.938 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.062 22.750 0.000 0.000 0.000 -6.582 -0.001
MIDFLOOR_PLENUM 7.138 -16.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.072 16.129 0.000 0.000 0.000 -6.459 -0.001
FIRSTFLOOR_PLENUM 4.216 -19.888 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.058 20.814 0.000 0.000 0.000 -5.200 -0.000
Total Facility 25.062 -66.707 61.998 -852.716 0.000 0.000 173.156 167.000 658.911 462.272 0.000 2.621 65.813 0.000 -284.552 0.000 -82.747 -330.111


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 05-SEP-05:14 0.00 0.00 0.00 -34983.72 0.00 0.00 313.61 387.63 5448.38 0.00 0.00 0.00 28834.11 0.00 -0.00 0.00 0.00 0.00
CORE_MID 05-SEP-05:14 0.00 0.00 0.00 -31492.37 0.00 0.00 315.30 387.63 3025.92 0.00 0.00 0.00 27763.52 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 19-JUN-05:04 0.00 0.00 0.00 -33708.19 0.00 0.00 302.42 211.73 3025.92 0.00 0.00 0.00 30168.11 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 13-AUG-15:52 0.00 0.00 0.00 -10355.74 0.00 0.00 27.42 19.49 478.42 2483.84 0.00 52.95 7293.63 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 04-JUN-09:02 0.00 0.00 0.00 -12941.77 0.00 0.00 15.56 12.34 302.86 8680.09 0.00 0.00 3963.53 0.00 -0.00 0.00 -32.60 0.00
PERIMETER_TOP_ZN_1 04-SEP-12:32 0.00 0.00 0.00 -15972.97 0.00 0.00 21.30 19.49 478.41 12883.52 0.00 0.00 2593.42 0.00 -0.00 0.00 -23.17 0.00
PERIMETER_TOP_ZN_4 02-JUL-16:32 0.00 0.00 0.00 -14077.21 0.00 0.00 12.66 12.34 302.86 9499.42 0.00 0.00 4311.06 0.00 -0.00 0.00 -61.13 0.00
PERIMETER_BOT_ZN_3 17-JUL-06:03 0.00 0.00 0.00 -7151.29 0.00 0.00 144.57 116.94 637.89 2255.15 0.00 0.00 4000.32 0.00 -0.00 0.00 -3.57 0.00
PERIMETER_BOT_ZN_2 03-SEP-08:52 0.00 0.00 0.00 -10509.79 0.00 0.00 16.66 12.34 302.86 9344.76 0.00 0.00 849.54 0.00 -0.00 0.00 -16.37 0.00
PERIMETER_BOT_ZN_1 03-SEP-12:12 0.00 0.00 0.00 -13138.32 0.00 0.00 25.38 19.49 478.41 12641.71 0.00 0.00 2.94 0.00 -0.00 0.00 -29.61 0.00
PERIMETER_BOT_ZN_4 03-SEP-16:12 0.00 0.00 0.00 -10963.30 0.00 0.00 15.97 12.34 302.86 8184.77 0.00 0.00 2461.80 0.00 -0.00 0.00 -14.42 0.00
PERIMETER_MID_ZN_3 09-JUL-15:21 0.00 0.00 0.00 -8661.81 0.00 0.00 28.55 19.49 478.42 3560.85 0.00 7.92 4566.59 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 02-JUL-08:21 0.00 0.00 0.00 -13819.52 0.00 0.00 13.63 12.34 302.86 11020.08 0.00 0.00 2496.74 0.00 -0.00 0.00 -26.13 0.00
PERIMETER_MID_ZN_1 03-SEP-12:12 0.00 0.00 0.00 -15181.00 0.00 0.00 23.56 19.49 478.41 12532.00 0.00 0.00 2180.35 0.00 -0.00 0.00 -52.81 0.00
PERIMETER_MID_ZN_4 04-JUL-16:41 0.00 0.00 0.00 -13633.83 0.00 0.00 13.65 12.34 302.86 8421.68 0.00 0.00 4921.41 0.00 -0.00 0.00 -38.11 0.00
TOPFLOOR_PLENUM 19-JUN-13:30 0.00 -11152.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 66.00 11086.38 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 14-AUG-10:10 0.00 -5254.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.93 5239.24 0.00 -0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 05-SEP-06:10 0.00 -5517.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5532.79 0.00 -0.00 0.00 -14.83 0.00
Total Facility 19-JUN-05:02 0.00 8513.38 0.00 -189350.31 0.00 0.00 1542.88 1072.56 17750.38 17285.90 0.00 0.00 143357.40 0.00 0.00 0.00 -172.19 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 02-JAN-05:02 0.00 0.00 9192.64 0.00 0.00 0.00 0.00 387.63 4042.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -13622.33
CORE_MID 02-JAN-05:02 0.00 0.00 14860.70 0.00 0.00 0.00 0.00 387.63 2442.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -17690.38
CORE_TOP 01-JAN-01:23 0.00 0.00 21810.05 0.00 0.00 0.00 0.00 193.79 1831.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -23835.38
PERIMETER_TOP_ZN_3 01-JAN-22:03 0.00 0.00 8835.45 0.00 0.00 0.00 0.00 40.85 386.10 0.00 0.00 0.00 0.00 0.00 -2945.11 0.00 -849.32 -5467.98
PERIMETER_TOP_ZN_2 01-JAN-22:03 0.00 0.00 7588.86 0.00 0.00 0.00 0.00 25.86 244.42 0.00 0.00 0.00 0.00 0.00 -1923.68 0.00 -574.28 -5361.19
PERIMETER_TOP_ZN_1 01-JAN-22:03 0.00 0.00 10247.11 0.00 0.00 0.00 0.00 40.85 386.10 0.00 0.00 0.00 0.00 0.00 -2916.66 0.00 -864.43 -6892.97
PERIMETER_TOP_ZN_4 01-JAN-22:03 0.00 0.00 7918.69 0.00 0.00 0.00 0.00 25.86 244.42 0.00 0.00 0.00 0.00 0.00 -1965.89 0.00 -574.39 -5648.69
PERIMETER_BOT_ZN_3 01-JAN-22:03 0.00 0.00 6726.33 0.00 0.00 0.00 0.00 40.85 386.10 0.00 0.00 0.00 0.00 0.00 -2981.75 0.00 -460.48 -3711.05
PERIMETER_BOT_ZN_2 01-JAN-00:06 0.00 0.00 5857.70 0.00 0.00 0.00 0.00 25.86 244.42 0.00 0.00 0.00 0.00 0.00 -1967.64 0.00 -357.84 -3802.51
PERIMETER_BOT_ZN_1 02-JAN-07:50 0.00 0.00 9970.17 0.00 0.00 0.00 255.88 116.94 637.88 300.24 0.00 0.00 8414.42 0.00 -0.00 0.00 -19695.53 0.00
PERIMETER_BOT_ZN_4 01-JAN-22:03 0.00 0.00 5990.38 0.00 0.00 0.00 0.00 25.86 244.42 0.00 0.00 0.00 0.00 0.00 -1995.24 0.00 -310.75 -3954.67
PERIMETER_MID_ZN_3 01-JAN-22:03 0.00 0.00 7241.00 0.00 0.00 0.00 0.00 40.85 386.10 0.00 0.00 0.00 0.00 0.00 -2999.61 0.00 -718.11 -3950.24
PERIMETER_MID_ZN_2 01-JAN-00:06 0.00 0.00 6535.56 0.00 0.00 0.00 0.00 25.86 244.42 0.00 0.00 0.00 0.00 0.00 -1970.71 0.00 -557.89 -4277.24
PERIMETER_MID_ZN_1 01-JAN-00:06 0.00 0.00 8521.50 0.00 0.00 0.00 0.00 40.85 386.10 0.00 0.00 0.00 0.00 0.00 -2975.05 0.00 -837.49 -5135.92
PERIMETER_MID_ZN_4 01-JAN-22:03 0.00 0.00 6646.99 0.00 0.00 0.00 0.00 25.86 244.42 0.00 0.00 0.00 0.00 0.00 -2002.34 0.00 -484.70 -4430.24
TOPFLOOR_PLENUM 02-JAN-06:10 13321.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -164.80 -13156.23
MIDFLOOR_PLENUM 02-JAN-08:19 8392.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -149.00 -8243.23
FIRSTFLOOR_PLENUM 02-JAN-09:00 6679.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -126.84 -6553.04
Total Facility 02-JAN-05:02 14080.12 0.00 128908.78 0.00 0.00 0.00 0.00 1963.59 13970.33 0.00 0.00 0.00 0.00 0.00 -32004.68 0.00 -4325.63 -122592.52



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 4.6473 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.1295 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 4.7307 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.0250 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 5.1256 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.6857 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 2.3237 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.0744 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 2.3654 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.0761 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 2.5628 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.0756 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_BOTTOM PACU_VAV_BOT 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID PACU_VAV_MID 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP PACU_VAV_TOP 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PACU_VAV_BOT   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_MID   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_TOP   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1934 2.1934 0.6361 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.9206 1.9206 0.6377 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.0655 2.0655 0.6362 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6526 0.6526 0.1344 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7297 0.7297 0.0854 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8922 0.8922 0.1347 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7855 0.7855 0.0848 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5148 0.5148 0.1344 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6019 0.6019 0.0849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7202 0.7202 0.1340 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6170 0.6170 0.0851 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5659 0.5659 0.1341 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7108 0.7108 0.0853 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8079 0.8079 0.1341 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7254 0.7254 0.0849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 4.6473 4.1295 4.6473 1.0744 0.0000 1.0000
PACU_VAV_MID 4.7307 4.0250 4.7307 1.0761 0.0000 1.0000
PACU_VAV_TOP 5.1256 4.6857 5.1256 1.0756 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0967 1.0967 0.6361 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9603 0.9603 0.6377 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0327 1.0327 0.6362 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3263 0.3263 0.1344 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3649 0.3649 0.0854 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4461 0.4461 0.1347 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3928 0.3928 0.0848 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2574 0.2574 0.1344 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3010 0.3010 0.0849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3601 0.3601 0.1340 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3085 0.3085 0.0851 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2830 0.2830 0.1341 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3554 0.3554 0.0853 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4040 0.4040 0.1341 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3627 0.3627 0.0849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 2.3237 1.0744 1.0744 1.0744 0.0000 1.0000
PACU_VAV_MID 2.3654 1.0761 1.0761 1.0761 0.0000 1.0000
PACU_VAV_TOP 2.5628 1.0756 1.0756 1.0756 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Total gross floor area [m2] 4982.19
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_BOTTOM 983.54 983.54 0.00 113.98
CORE_MID 983.54 983.54 0.00 113.98
CORE_TOP 983.54 983.54 0.00 113.98
PERIMETER_TOP_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_TOP_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_BOT_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_BOT_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_MID_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_2 131.26 131.26 0.00 96.54
PERIMETER_MID_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_4 131.25 131.25 0.00 113.98
TOPFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
MIDFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
FIRSTFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
Totals 4982.19 4982.19 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 337.83
Number of hours cooling loads not met 122.83
Number of hours not met 460.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 327.94 234932.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 175.56 67361.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 167.00 17672.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 34.07 3824.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLift 73.68 4325.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLightsFan 0.54 72.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 584.69 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 25.33 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 87.80 26290.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 1.85 766.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 52.88 6688.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 658.91 1203.40
Natural Gas 0.00 327.94
Additional 0.00 0.00
Total 658.91 1531.33


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 142.41
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 33.52
Space Heating 0.00
Space Cooling 35.24
Fans (All) 17.62
Service Water Heating 10.61
Receptacle Equipment 132.25
Miscellaneous (All) 241.54
Subtotal 241.54


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 65.82
Service Water Heating 0.00
Miscellaneous (All) 65.82
Subtotal 65.82


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 10.91
Space Heating 21.42
Space Cooling 11.46
Fans (All) 5.73
Service Water Heating 3.45
Receptacle Equipment 43.03
Miscellaneous 4.00


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
PV_SCH 8760. 8760.
ELEVATOR_RUNNING_SCH 145. 3744.
ELEVATOR_STANDBY_SCH 8276. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 1996. 8760.
BLDG_EQUIP_SCH 4095. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2545. 5992.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 1470. 4212.
BLDG_SWH_SCH 1441. 5992.
WORK_EFF_SCH 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
INFIL_SCH_PNNL 5172. 8760.
INFIL_DOOR_OPENING_SCH 1121. 3380.
PERIMETER_MID_ZN_2_OA_MULT 7824. 7824.
PERIMETER_MID_ZN_2_MDP_SCH 948. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 8734.83 25.17 0.00 0.00 0.00
CORE_MID 8749.67 10.33 0.00 0.00 0.00
CORE_TOP 8757.33 2.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8722.50 37.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8656.00 104.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8676.00 84.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8618.83 141.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8750.83 9.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8693.00 67.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8706.17 53.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8651.67 108.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8733.17 26.83 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8656.17 103.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8672.67 87.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8621.50 138.50 0.00 0.00 0.00
TOPFLOOR_PLENUM 8620.83 139.17 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 8618.83 0.00 0.00 0.00 0.00
Max 8760.00 141.17 0.00 0.00 0.00
Average 8696.73 63.27 0.00 0.00 0.00
Sum 156541.17 1138.83 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 128292.00 12.00 0.00 0.00 0.00
CORE_MID 128304.00 0.00 0.00 0.00 0.00
CORE_TOP 128302.00 2.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128304.00 12.00 0.00 0.00 0.00
Average 34142.56 0.78 0.00 0.00 0.00
Sum 614566.00 14.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 8028.17 731.83 0.00 0.00 0.00
CORE_MID 8244.00 516.00 0.00 0.00 0.00
CORE_TOP 8370.17 389.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8064.17 695.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8010.17 749.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8033.17 726.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7965.33 794.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8167.00 593.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8005.83 754.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 7750.67 1009.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7916.17 843.83 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8025.00 735.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 7935.67 824.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 7973.17 786.83 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7906.67 853.33 0.00 0.00 0.00
TOPFLOOR_PLENUM 7579.33 1180.67 0.00 0.00 0.00
MIDFLOOR_PLENUM 7973.83 786.17 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 7980.17 779.83 0.00 0.00 0.00
Min 7579.33 389.83 0.00 0.00 0.00
Max 8370.17 1180.67 0.00 0.00 0.00
Average 7996.04 763.96 0.00 0.00 0.00
Sum 143928.67 13751.33 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 127919.83 384.17 0.00 0.00 0.00
CORE_MID 128048.83 255.17 0.00 0.00 0.00
CORE_TOP 128130.00 174.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24766.33 142.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 13918.00 98.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24784.83 124.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 13900.83 115.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24759.50 149.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 13942.67 73.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 23408.83 1500.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 13923.67 92.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24871.50 37.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10127.33 6.67 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24875.67 33.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 13959.00 57.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128130.00 1500.17 0.00 0.00 0.00
Average 33963.16 180.18 0.00 0.00 0.00
Sum 611336.83 3243.17 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:49

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 10134.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 14016.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 24909.00 0.00
Average 0.00 0.00 12759.33 0.00
Sum 0.00 0.00 229668.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.701893E+10 7452.32 27-JAN-16:40 4.80 2.53 0.173284E+10 2567.23 27-JAN-14:00 4.80 2.53
February 0.739104E+10 8468.01 24-FEB-17:00 6.70 1.42 0.165681E+10 2606.56 03-FEB-14:50 6.70 1.42
March 0.104602E+11 13275.33 30-MAR-07:03 2.30 1.13 0.211847E+10 2606.66 27-MAR-09:09 2.30 1.13
April 0.124048E+11 29008.00 10-APR-06:03 15.78 13.94 0.190503E+10 2606.66 05-APR-09:39 15.78 13.94
May 0.174891E+11 32737.07 30-MAY-05:12 18.53 14.51 0.207427E+10 2606.76 15-MAY-13:00 18.53 14.51
June 0.207893E+11 34698.81 19-JUN-05:04 24.08 22.05 0.207086E+10 2606.66 22-JUN-09:20 25.77 16.91
July 0.215818E+11 33663.56 24-JUL-05:12 20.97 20.39 0.192483E+10 2606.65 12-JUL-13:20 20.97 20.39
August 0.233209E+11 34268.65 07-AUG-05:12 19.40 16.84 0.216107E+10 2606.67 23-AUG-13:20 25.60 17.10
September 0.197108E+11 34980.62 05-SEP-05:14 20.60 18.00 0.191812E+10 2606.72 19-SEP-09:39 19.43 14.80
October 0.180806E+11 31154.17 16-OCT-06:01 9.18 8.72 0.199263E+10 2606.73 16-OCT-09:09 16.88 14.11
November 0.112899E+11 15574.27 03-NOV-16:00 15.00 10.26 0.194319E+10 2606.69 09-NOV-14:00 13.90 12.65
December 0.842424E+10 10017.40 21-DEC-16:10 2.62 -2.3 0.183770E+10 2606.63 20-DEC-10:20 2.62 -2.3
                     
Annual Sum or Average 0.177962E+12         0.233358E+11        
Minimum of Months 0.701893E+10 7452.32   2.30 -2.3 0.165681E+10 2567.23   2.30 -2.3
Maximum of Months 0.233209E+11 34980.62   24.08 22.05 0.216107E+10 2606.76   25.77 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 887833.21 130.60 17-JAN-15:00 10.60 5.07 0.00 0.00 01-JAN-00:10 10.60 5.07
February 20424277.30 556.15 11-FEB-14:00 6.10 2.34 0.00 0.00 01-FEB-00:10 6.10 2.34
March 0.461593E+09 2734.08 28-MAR-13:00 13.90 8.69 0.00 0.00 01-MAR-00:10 13.90 8.69
April 0.139751E+10 6906.61 07-APR-13:20 26.50 16.25 0.00 0.00 01-APR-00:10 26.50 16.25
May 0.323571E+10 10210.20 30-MAY-14:10 29.22 16.98 0.00 0.00 01-MAY-00:10 29.22 16.98
June 0.543773E+10 11152.89 19-JUN-13:30 34.70 23.81 0.00 0.00 01-JUN-00:10 34.70 23.81
July 0.660150E+10 10447.91 10-JUL-13:50 32.70 20.82 0.00 0.00 01-JUL-00:10 32.70 20.82
August 0.708384E+10 9977.94 01-AUG-14:40 30.97 22.94 0.00 0.00 01-AUG-00:10 30.97 22.94
September 0.354889E+10 8725.45 01-SEP-14:40 30.77 17.43 0.00 0.00 01-SEP-00:10 30.77 17.43
October 0.196826E+10 6191.17 04-OCT-14:50 23.98 19.09 0.00 0.00 01-OCT-00:10 23.98 19.09
November 0.178119E+09 2250.29 03-NOV-14:10 17.70 10.72 0.00 0.00 01-NOV-00:10 17.70 10.72
December 4106843.89 851.54 17-DEC-14:00 12.20 5.29 0.00 0.00 01-DEC-00:10 12.20 5.29
                     
Annual Sum or Average 0.299386E+11         0.00        
Minimum of Months 887833.21 130.60   6.10 2.34 0.00 0.00   6.10 2.34
Maximum of Months 0.708384E+10 11152.89   34.70 23.81 0.00 0.00   34.70 23.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 11551805.83 2133.12 05-JAN-05:01 -7.8 -9.6 0.00 0.00 01-JAN-00:10 -7.8 -9.6
February 17293368.55 1960.48 03-FEB-06:01 -7.8 -9.5 0.00 0.00 01-FEB-00:10 -7.8 -9.5
March 0.162345E+09 2127.06 24-MAR-06:01 1.38 0.88 0.00 0.00 01-MAR-00:10 1.38 0.88
April 0.553201E+09 2285.40 10-APR-15:40 20.00 11.28 0.00 0.00 01-APR-00:10 20.00 11.28
May 0.152499E+10 4865.68 30-MAY-10:10 27.98 17.74 0.00 0.00 01-MAY-00:10 27.98 17.74
June 0.305763E+10 4811.07 26-JUN-10:10 26.38 20.16 0.00 0.00 01-JUN-00:10 26.38 20.16
July 0.381812E+10 4995.60 10-JUL-12:10 31.28 20.14 0.00 0.00 01-JUL-00:10 31.28 20.14
August 0.413850E+10 5254.38 14-AUG-10:10 27.88 23.11 0.00 0.00 01-AUG-00:10 27.88 23.11
September 0.230249E+10 5238.19 05-SEP-06:10 20.78 18.13 0.00 0.00 01-SEP-00:10 20.78 18.13
October 0.114977E+10 2938.79 04-OCT-15:50 22.98 19.12 0.00 0.00 01-OCT-00:10 22.98 19.12
November 0.129967E+09 1712.15 15-NOV-07:02 2.98 1.06 0.00 0.00 01-NOV-00:10 2.98 1.06
December 14674071.71 1569.02 23-DEC-06:11 2.93 2.42 0.00 0.00 01-DEC-00:10 2.93 2.42
                     
Annual Sum or Average 0.168805E+11         0.00        
Minimum of Months 11551805.83 1569.02   -7.8 -9.6 0.00 0.00   -7.8 -9.6
Maximum of Months 0.413850E+10 5254.38   31.28 23.11 0.00 0.00   31.28 23.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 82974812.48 1891.80 31-JAN-07:10 -8.8 -11.0 0.00 0.00 01-JAN-00:10 -8.8 -11.0
February 0.115053E+09 2235.66 03-FEB-07:10 -7.7 -9.4 0.00 0.00 01-FEB-00:10 -7.7 -9.4
March 0.370150E+09 2772.36 16-MAR-06:02 1.20 -1.9 0.00 0.00 01-MAR-00:10 1.20 -1.9
April 0.800715E+09 2835.51 21-APR-06:02 5.68 5.41 0.00 0.00 01-APR-00:10 5.68 5.41
May 0.175601E+10 4817.82 30-MAY-12:10 29.50 17.65 0.00 0.00 01-MAY-00:10 29.50 17.65
June 0.318034E+10 5507.24 19-JUN-12:08 36.42 24.23 0.00 0.00 01-JUN-00:10 36.42 24.23
July 0.394324E+10 5158.61 10-JUL-12:10 31.28 20.14 0.00 0.00 01-JUL-00:10 31.28 20.14
August 0.443208E+10 5038.60 14-AUG-07:10 24.60 22.21 0.00 0.00 01-AUG-00:10 24.60 22.21
September 0.283607E+10 5517.57 05-SEP-06:10 20.78 18.13 0.00 0.00 01-SEP-00:10 20.78 18.13
October 0.188252E+10 3401.68 16-OCT-06:06 9.18 8.72 0.00 0.00 01-OCT-00:10 9.18 8.72
November 0.364818E+09 1806.38 30-NOV-07:03 5.00 3.93 0.00 0.00 01-NOV-00:10 5.00 3.93
December 0.123778E+09 2172.89 20-DEC-07:02 1.78 1.02 0.00 0.00 01-DEC-00:10 1.78 1.02
                     
Annual Sum or Average 0.198877E+11         0.00        
Minimum of Months 82974812.48 1806.38   -8.8 -11.0 0.00 0.00   -8.8 -11.0
Maximum of Months 0.443208E+10 5517.57   36.42 24.23 0.00 0.00   36.42 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.523017E+10 6245.75 31-JAN-08:20 -8.1 -10.5 0.157832E+10 2373.02 20-JAN-14:00 -8.1 -10.5
February 0.562784E+10 6022.10 24-FEB-17:00 6.70 1.42 0.147535E+10 2404.18 24-FEB-14:00 6.70 1.42
March 0.833533E+10 9223.34 29-MAR-16:00 7.20 4.88 0.196512E+10 2606.63 29-MAR-13:20 7.20 4.88
April 0.971134E+10 13268.53 10-APR-16:00 20.00 11.13 0.185083E+10 2606.65 07-APR-13:20 20.00 11.13
May 0.138385E+11 28019.88 30-MAY-05:12 18.53 14.51 0.206315E+10 2606.73 15-MAY-13:00 18.53 14.51
June 0.167933E+11 31215.93 19-JUN-05:04 24.08 22.05 0.206780E+10 2606.72 26-JUN-09:20 25.37 19.69
July 0.179163E+11 31257.66 24-JUL-05:14 20.97 20.39 0.192264E+10 2606.71 17-JUL-09:20 20.97 20.39
August 0.190108E+11 31439.55 14-AUG-05:14 22.57 20.98 0.215873E+10 2609.20 14-AUG-09:20 27.40 22.88
September 0.151159E+11 31488.08 05-SEP-05:14 20.60 18.00 0.191294E+10 2608.77 05-SEP-09:20 24.07 19.46
October 0.129063E+11 21086.86 16-OCT-06:01 9.18 8.72 0.197933E+10 2606.72 16-OCT-09:09 16.88 14.11
November 0.783581E+10 10816.55 03-NOV-16:00 15.00 10.26 0.181253E+10 2606.66 09-NOV-14:00 13.90 12.65
December 0.660202E+10 6234.52 21-DEC-16:20 2.43 -2.4 0.162246E+10 2487.75 21-DEC-14:00 2.43 -2.4
                     
Annual Sum or Average 0.138924E+12         0.224092E+11        
Minimum of Months 0.523017E+10 6022.10   -8.1 -10.5 0.147535E+10 2373.02   -8.1 -10.5
Maximum of Months 0.190108E+11 31488.08   24.08 22.05 0.215873E+10 2609.20   27.40 22.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.359259E+10 5866.10 14-JAN-17:02 -6.0 -6.6 0.151426E+10 2301.44 20-JAN-16:49 5.87 3.30
February 0.388890E+10 5815.12 24-FEB-16:50 6.88 1.49 0.140095E+10 2346.36 02-FEB-14:00 6.88 1.49
March 0.740947E+10 9200.97 29-MAR-16:00 7.20 4.88 0.186430E+10 2606.63 29-MAR-13:20 7.20 4.88
April 0.911690E+10 14261.73 10-APR-15:40 20.00 11.28 0.179695E+10 2606.65 07-APR-13:20 20.00 11.28
May 0.137252E+11 30336.75 30-MAY-05:12 18.53 14.51 0.204894E+10 2606.74 15-MAY-13:00 18.53 14.51
June 0.174689E+11 33704.74 19-JUN-05:04 24.08 22.05 0.206634E+10 2606.67 23-JUN-09:20 27.80 18.74
July 0.190425E+11 30696.67 24-JUL-05:12 20.97 20.39 0.192304E+10 2606.65 14-JUL-09:00 20.97 20.39
August 0.198537E+11 31503.09 07-AUG-05:12 19.40 16.84 0.215812E+10 2606.69 29-AUG-09:09 23.77 18.41
September 0.146127E+11 30775.22 05-SEP-05:12 20.60 18.00 0.190562E+10 2606.68 19-SEP-09:50 19.72 15.05
October 0.114484E+11 14825.76 04-OCT-15:00 23.90 19.11 0.194396E+10 2606.70 16-OCT-09:09 16.88 14.11
November 0.631471E+10 9765.76 03-NOV-16:00 15.00 10.26 0.170019E+10 2606.65 09-NOV-14:00 13.90 12.65
December 0.452910E+10 5769.66 21-DEC-16:25 2.25 -2.5 0.150885E+10 2355.91 21-DEC-14:00 2.25 -2.5
                     
Annual Sum or Average 0.131003E+12         0.218315E+11        
Minimum of Months 0.359259E+10 5769.66   -6.0 -6.6 0.140095E+10 2301.44   2.25 -2.5
Maximum of Months 0.198537E+11 33704.74   24.08 22.05 0.215812E+10 2606.74   27.80 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.144883E+09 1194.52 14-JAN-17:02 -6.0 -6.6 0.305482E+09 432.42 20-JAN-14:00 7.80 3.97
February 0.179145E+09 1022.46 24-FEB-15:40 7.97 1.96 0.278757E+09 440.98 24-FEB-14:00 7.97 1.96
March 0.950884E+09 1851.38 28-MAR-14:00 13.30 8.41 0.361768E+09 549.49 28-MAR-13:20 13.30 8.41
April 0.176830E+10 3942.99 07-APR-14:20 25.93 15.95 0.360712E+09 549.50 07-APR-13:20 25.93 15.95
May 0.347141E+10 8772.26 30-MAY-06:03 20.47 15.45 0.427673E+09 549.52 15-MAY-13:00 20.47 15.45
June 0.528147E+10 9144.88 26-JUN-05:12 20.97 17.23 0.435670E+09 549.59 19-JUN-13:39 20.97 17.23
July 0.610337E+10 9516.29 10-JUL-04:02 26.10 21.38 0.406119E+09 549.73 10-JUL-13:00 32.80 20.89
August 0.608015E+10 10355.80 13-AUG-15:52 30.00 20.46 0.454999E+09 549.51 29-AUG-09:09 23.77 18.41
September 0.366720E+10 7217.27 05-SEP-06:03 20.78 18.13 0.398827E+09 549.51 19-SEP-09:20 18.87 14.31
October 0.232660E+10 4063.61 04-OCT-13:40 24.60 18.82 0.396203E+09 549.50 02-OCT-13:20 24.60 18.82
November 0.817651E+09 1658.36 03-NOV-14:00 17.80 10.67 0.330869E+09 549.49 03-NOV-13:20 17.80 10.67
December 0.194255E+09 1016.24 20-DEC-14:00 10.00 5.91 0.296241E+09 442.02 20-DEC-14:09 9.72 5.77
                     
Annual Sum or Average 0.309853E+11         0.445332E+10        
Minimum of Months 0.144883E+09 1016.24   -6.0 -6.6 0.278757E+09 432.42   7.80 1.96
Maximum of Months 0.610337E+10 10355.80   30.00 21.38 0.454999E+09 549.73   32.80 20.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.196235E+09 925.86 31-JAN-09:10 -7.6 -10.2 0.197310E+09 319.13 19-JAN-10:30 -7.6 -10.2
February 0.281404E+09 931.99 09-FEB-09:10 -7.0 -8.9 0.182793E+09 333.87 22-FEB-10:09 0.87 -3.0
March 0.962939E+09 3770.26 29-MAR-09:30 6.15 3.19 0.249833E+09 347.88 29-MAR-13:20 7.80 5.34
April 0.187438E+10 6235.23 28-APR-08:40 15.53 8.75 0.239747E+09 347.89 26-APR-09:00 15.53 8.75
May 0.352324E+10 12814.68 29-MAY-08:42 25.73 16.73 0.273543E+09 348.42 30-MAY-09:00 27.80 17.82
June 0.460682E+10 12941.25 04-JUN-09:02 23.48 12.89 0.276236E+09 348.42 26-JUN-09:00 26.10 20.11
July 0.525365E+10 12865.58 02-JUL-08:32 25.20 21.54 0.257463E+09 348.98 14-JUL-09:00 30.60 21.74
August 0.587379E+10 12335.75 13-AUG-09:12 28.17 19.21 0.288449E+09 348.52 02-AUG-09:00 28.17 19.21
September 0.349610E+10 12716.46 04-SEP-08:32 23.53 18.61 0.254233E+09 348.60 06-SEP-09:50 26.52 19.55
October 0.235107E+10 5448.66 05-OCT-09:10 19.08 16.88 0.258887E+09 347.89 16-OCT-09:09 16.88 14.11
November 0.711030E+09 2205.39 03-NOV-09:30 13.05 8.24 0.221273E+09 347.88 06-NOV-10:20 9.47 5.35
December 0.288562E+09 815.77 20-DEC-10:00 8.30 5.00 0.193136E+09 329.29 20-DEC-10:09 8.40 5.03
                     
Annual Sum or Average 0.294192E+11         0.289290E+10        
Minimum of Months 0.196235E+09 815.77   -7.6 -10.2 0.182793E+09 319.13   -7.6 -10.2
Maximum of Months 0.587379E+10 12941.25   28.17 21.54 0.288449E+09 348.98   30.60 21.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.890623E+09 5849.28 19-JAN-13:25 9.40 3.94 0.340277E+09 549.50 30-JAN-14:30 2.80 -1.1
February 0.117857E+10 6309.15 02-FEB-13:50 5.78 -0.8 0.315737E+09 549.50 17-FEB-14:09 6.60 2.15
March 0.265214E+10 8861.41 29-MAR-13:10 7.80 5.30 0.399982E+09 549.51 23-MAR-13:00 7.80 5.30
April 0.314879E+10 9775.44 07-APR-12:30 26.15 15.90 0.372531E+09 549.88 07-APR-13:30 26.40 16.17
May 0.451323E+10 12314.76 29-MAY-12:43 27.48 17.22 0.428225E+09 550.14 30-MAY-13:00 29.40 16.93
June 0.605578E+10 11787.98 19-JUN-05:02 24.08 22.05 0.435574E+09 549.80 19-JUN-13:30 34.70 23.81
July 0.711266E+10 15628.66 30-JUL-11:32 26.10 23.28 0.406253E+09 550.03 10-JUL-13:50 26.10 23.28
August 0.872477E+10 15551.72 13-AUG-12:32 30.93 19.36 0.455391E+09 550.27 30-AUG-13:09 27.48 15.59
September 0.653608E+10 15973.09 04-SEP-12:32 26.10 18.14 0.401348E+09 565.52 28-SEP-13:09 22.98 13.55
October 0.612782E+10 15735.04 22-OCT-12:02 21.28 16.35 0.409790E+09 555.87 04-OCT-13:09 21.28 16.35
November 0.219846E+10 10632.39 02-NOV-13:00 15.60 8.21 0.369846E+09 549.62 02-NOV-13:50 16.02 8.62
December 0.114268E+10 6174.65 21-DEC-13:25 3.05 -1.7 0.337367E+09 549.49 14-DEC-14:09 3.05 -1.7
                     
Annual Sum or Average 0.502816E+11         0.467232E+10        
Minimum of Months 0.890623E+09 5849.28   3.05 -1.7 0.315737E+09 549.49   2.80 -1.7
Maximum of Months 0.872477E+10 15973.09   30.93 23.28 0.455391E+09 565.52   34.70 23.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.193995E+09 1285.51 20-JAN-15:30 7.50 3.89 0.199678E+09 345.51 19-JAN-14:00 7.50 3.89
February 0.273184E+09 2172.22 24-FEB-15:30 8.05 2.04 0.184398E+09 347.83 17-FEB-14:00 8.05 2.04
March 0.112668E+10 5510.59 29-MAR-15:50 7.20 4.93 0.239140E+09 347.85 29-MAR-13:20 7.20 4.93
April 0.193514E+10 8924.99 09-APR-16:23 16.65 13.97 0.231456E+09 347.85 07-APR-13:20 16.65 13.97
May 0.336091E+10 11625.35 14-MAY-15:13 13.70 9.24 0.271247E+09 347.88 15-MAY-13:00 17.80 11.36
June 0.481267E+10 13879.53 18-JUN-15:52 25.60 22.09 0.275975E+09 347.86 20-JUN-13:09 26.78 17.87
July 0.524675E+10 14076.89 02-JUL-16:32 24.60 20.65 0.257318E+09 347.86 14-JUL-09:00 30.60 21.74
August 0.586612E+10 13743.86 13-AUG-15:52 30.00 20.46 0.288336E+09 347.86 08-AUG-13:50 30.00 20.46
September 0.346403E+10 13669.23 10-SEP-15:52 23.30 12.88 0.253140E+09 347.86 19-SEP-09:20 18.87 14.31
October 0.249170E+10 11472.58 15-OCT-15:13 20.20 12.62 0.253226E+09 347.86 16-OCT-09:20 17.07 14.18
November 0.674499E+09 3631.72 03-NOV-15:30 16.10 10.65 0.215114E+09 347.85 09-NOV-14:00 13.90 12.65
December 0.229244E+09 1116.14 08-DEC-15:30 6.40 2.12 0.193908E+09 341.74 21-DEC-14:00 3.30 -1.8
                     
Annual Sum or Average 0.296749E+11         0.286294E+10        
Minimum of Months 0.193995E+09 1116.14   6.40 2.04 0.184398E+09 341.74   3.30 -1.8
Maximum of Months 0.586612E+10 14076.89   30.00 22.09 0.288336E+09 347.88   30.60 21.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.183904E+09 1018.61 14-JAN-17:02 -6.0 -6.6 0.305344E+09 423.23 20-JAN-14:00 7.80 3.97
February 0.169352E+09 965.51 24-FEB-14:10 9.22 3.12 0.278769E+09 428.34 24-FEB-14:20 9.03 2.95
March 0.890204E+09 1258.50 28-MAR-14:00 13.30 8.41 0.352006E+09 511.76 28-MAR-13:00 13.30 8.41
April 0.140932E+10 2148.04 10-APR-14:00 20.60 10.45 0.350079E+09 549.50 07-APR-13:20 20.60 10.45
May 0.243839E+10 4303.24 30-MAY-13:10 29.90 17.82 0.421958E+09 549.51 15-MAY-13:00 29.90 17.82
June 0.402582E+10 7137.73 26-JUN-06:03 21.97 17.81 0.435060E+09 549.50 05-JUN-09:20 21.97 17.81
July 0.503883E+10 7151.27 17-JUL-06:03 22.48 19.71 0.405485E+09 549.50 12-JUL-13:20 22.48 19.71
August 0.532330E+10 6976.50 14-AUG-06:03 23.48 21.76 0.454926E+09 549.51 08-AUG-13:20 23.48 21.76
September 0.357031E+10 6330.68 05-SEP-06:03 20.78 18.13 0.401781E+09 549.51 19-SEP-09:39 19.43 14.80
October 0.250398E+10 3623.17 05-OCT-14:00 23.30 18.86 0.409105E+09 549.51 16-OCT-09:09 16.88 14.11
November 0.119621E+10 1691.20 06-NOV-13:07 12.98 7.45 0.350562E+09 549.49 03-NOV-13:20 12.98 7.45
December 0.446697E+09 1047.74 20-DEC-13:50 9.90 5.86 0.300083E+09 450.86 20-DEC-14:09 9.72 5.77
                     
Annual Sum or Average 0.271963E+11         0.446516E+10        
Minimum of Months 0.169352E+09 965.51   -6.0 -6.6 0.278769E+09 423.23   7.80 2.95
Maximum of Months 0.532330E+10 7151.27   29.90 21.76 0.454926E+09 549.51   29.90 21.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.225453E+09 821.12 31-JAN-08:40 -8.0 -10.4 0.197965E+09 311.29 27-JAN-10:30 -8.0 -10.4
February 0.289798E+09 797.38 09-FEB-08:50 -7.3 -9.1 0.182552E+09 317.12 22-FEB-10:09 0.87 -3.0
March 0.890521E+09 2321.59 29-MAR-09:30 6.15 3.19 0.247138E+09 347.88 29-MAR-13:20 7.80 5.34
April 0.149206E+10 4113.59 28-APR-09:10 16.28 8.96 0.239493E+09 347.88 26-APR-09:00 16.28 8.96
May 0.269181E+10 8101.08 28-MAY-10:02 22.48 13.77 0.272383E+09 348.16 30-MAY-09:00 27.80 17.82
June 0.379793E+10 10380.41 04-JUN-09:42 24.22 12.91 0.276152E+09 348.16 26-JUN-09:00 26.10 20.11
July 0.458931E+10 9316.87 09-JUL-09:32 29.43 25.37 0.257333E+09 348.51 14-JUL-09:00 30.60 21.74
August 0.548003E+10 8942.47 20-AUG-10:32 25.37 15.92 0.288606E+09 348.28 18-AUG-09:30 25.37 15.92
September 0.357005E+10 10507.60 03-SEP-08:52 22.80 14.85 0.255630E+09 348.04 06-SEP-09:09 25.78 19.15
October 0.267808E+10 4882.50 05-OCT-09:10 19.08 16.88 0.263768E+09 347.89 16-OCT-09:09 16.88 14.11
November 0.100754E+10 2449.23 03-NOV-09:30 13.05 8.24 0.235261E+09 347.88 06-NOV-10:20 9.47 5.35
December 0.471823E+09 842.84 20-DEC-09:50 7.93 4.87 0.200487E+09 339.00 20-DEC-10:09 8.40 5.03
                     
Annual Sum or Average 0.271844E+11         0.291677E+10        
Minimum of Months 0.225453E+09 797.38   -8.0 -10.4 0.182552E+09 311.29   -8.0 -10.4
Maximum of Months 0.548003E+10 10507.60   29.43 25.37 0.288606E+09 348.51   30.60 21.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.331724E+09 1348.78 19-JAN-14:30 9.15 3.65 0.301554E+09 542.53 19-JAN-14:39 9.07 3.63
February 0.396090E+09 2311.07 25-FEB-13:10 2.88 -1.9 0.278241E+09 538.84 02-FEB-14:39 2.88 -1.9
March 0.110873E+10 4736.38 03-MAR-13:20 14.60 8.23 0.364723E+09 549.51 29-MAR-13:20 7.80 5.34
April 0.170856E+10 6680.79 07-APR-12:00 25.60 15.40 0.347535E+09 549.51 07-APR-13:20 26.50 16.25
May 0.268658E+10 10274.95 30-MAY-12:00 29.40 17.58 0.407659E+09 556.15 30-MAY-12:09 29.50 17.65
June 0.472601E+10 11814.80 19-JUN-12:00 36.70 24.28 0.432914E+09 644.15 19-JUN-12:09 36.42 24.23
July 0.667106E+10 11246.72 07-JUL-12:00 33.90 23.31 0.406351E+09 609.80 07-JUL-12:09 33.72 23.31
August 0.872287E+10 12364.87 13-AUG-12:32 30.93 19.36 0.456635E+09 613.72 18-AUG-12:09 32.88 20.21
September 0.626792E+10 13138.12 03-SEP-12:12 24.23 15.64 0.402124E+09 597.91 01-SEP-12:09 24.23 15.64
October 0.566787E+10 12769.15 22-OCT-12:53 22.20 16.91 0.411724E+09 573.57 04-OCT-13:20 22.20 16.91
November 0.172559E+10 9801.25 06-NOV-13:07 12.98 7.45 0.355204E+09 549.62 02-NOV-13:00 12.98 7.45
December 0.720545E+09 4481.12 17-DEC-12:43 12.20 4.87 0.312372E+09 549.51 21-DEC-14:09 3.30 -1.7
                     
Annual Sum or Average 0.407336E+11         0.447704E+10        
Minimum of Months 0.331724E+09 1348.78   2.88 -1.9 0.278241E+09 538.84   2.88 -1.9
Maximum of Months 0.872287E+10 13138.12   36.70 24.28 0.456635E+09 644.15   36.42 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.215506E+09 856.47 20-JAN-16:00 7.20 3.80 0.198266E+09 333.49 20-JAN-16:10 6.93 3.71
February 0.256517E+09 1215.02 22-FEB-16:30 3.85 -0.7 0.182811E+09 338.68 22-FEB-16:00 3.30 -0.7
March 0.955062E+09 3354.51 27-MAR-16:50 21.28 15.57 0.239055E+09 347.85 28-MAR-13:20 13.70 8.60
April 0.147180E+10 5438.58 10-APR-16:00 20.00 11.13 0.232376E+09 347.85 07-APR-13:20 20.00 11.13
May 0.246752E+10 7343.82 28-MAY-15:23 25.30 15.55 0.270327E+09 347.87 15-MAY-13:00 25.30 15.55
June 0.399800E+10 10845.74 18-JUN-16:21 25.30 22.03 0.276149E+09 347.86 22-JUN-09:20 25.77 16.91
July 0.458161E+10 10664.66 02-JUL-16:32 24.60 20.65 0.257263E+09 347.86 12-JUL-13:20 28.70 18.81
August 0.545856E+10 10599.74 13-AUG-15:52 30.00 20.46 0.288598E+09 347.86 08-AUG-13:20 30.00 20.46
September 0.349211E+10 10963.60 03-SEP-16:12 24.80 16.47 0.255297E+09 347.86 19-SEP-09:20 18.87 14.31
October 0.272538E+10 8179.82 15-OCT-15:13 20.20 12.62 0.262918E+09 347.86 16-OCT-09:09 16.88 14.11
November 0.915653E+09 3406.22 03-NOV-15:30 16.10 10.65 0.228195E+09 347.85 09-NOV-14:00 13.90 12.65
December 0.409735E+09 870.88 08-DEC-15:40 6.30 2.04 0.197543E+09 338.37 21-DEC-15:50 2.88 -2.1
                     
Annual Sum or Average 0.269475E+11         0.288880E+10        
Minimum of Months 0.215506E+09 856.47   3.85 -0.7 0.182811E+09 333.49   2.88 -2.1
Maximum of Months 0.545856E+10 10963.60   30.00 22.03 0.288598E+09 347.87   30.00 20.46



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.257491E+09 1032.54 20-JAN-15:00 7.80 3.97 0.307575E+09 447.35 20-JAN-14:00 7.80 3.97
February 0.306661E+09 1062.29 24-FEB-15:40 7.97 1.96 0.282020E+09 454.37 24-FEB-14:30 7.97 1.96
March 0.124425E+10 1797.08 28-MAR-14:00 13.30 8.41 0.372771E+09 549.49 28-MAR-13:20 13.30 8.41
April 0.192436E+10 3532.21 10-APR-14:00 20.60 10.45 0.371552E+09 549.50 07-APR-13:20 20.60 10.45
May 0.347025E+10 7765.59 30-MAY-06:03 20.47 15.45 0.431999E+09 549.52 15-MAY-13:00 20.47 15.45
June 0.511074E+10 7748.25 22-JUN-06:03 23.40 15.45 0.435987E+09 550.31 19-JUN-13:20 23.40 15.45
July 0.580630E+10 8662.60 09-JUL-15:21 27.20 24.16 0.406135E+09 550.43 25-JUL-13:20 28.53 24.38
August 0.584251E+10 7684.02 14-AUG-06:03 23.48 21.76 0.455244E+09 550.20 14-AUG-09:20 27.40 22.88
September 0.374199E+10 7136.30 05-SEP-05:12 20.60 18.00 0.401503E+09 550.01 05-SEP-09:20 24.07 19.46
October 0.257475E+10 3897.52 05-OCT-14:00 23.30 18.86 0.407243E+09 549.51 16-OCT-09:09 16.88 14.11
November 0.112454E+10 1949.98 03-NOV-14:00 17.80 10.67 0.346283E+09 549.50 09-NOV-14:20 14.23 11.96
December 0.453423E+09 1089.50 20-DEC-14:00 10.00 5.91 0.300642E+09 463.33 20-DEC-14:09 9.72 5.77
                     
Annual Sum or Average 0.318573E+11         0.451895E+10        
Minimum of Months 0.257491E+09 1032.54   7.80 1.96 0.282020E+09 447.35   7.80 1.96
Maximum of Months 0.584251E+10 8662.60   27.20 24.16 0.455244E+09 550.43   28.53 24.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.220432E+09 910.89 31-JAN-09:30 -7.2 -9.9 0.147692E+09 331.71 19-JAN-11:09 -7.2 -9.9
February 0.288569E+09 1529.62 22-FEB-11:05 2.38 -2.1 0.138453E+09 350.99 22-FEB-11:09 2.38 -2.1
March 0.100988E+10 5711.05 29-MAR-12:02 7.80 5.26 0.189028E+09 356.45 29-MAR-12:09 7.80 5.26
April 0.186634E+10 6568.37 28-APR-10:05 17.30 9.69 0.180100E+09 356.47 26-APR-10:09 17.30 9.69
May 0.336872E+10 13738.12 29-MAY-08:31 25.37 16.74 0.203742E+09 356.47 15-MAY-14:09 25.37 16.74
June 0.427922E+10 12314.62 25-JUN-08:42 25.40 23.51 0.204896E+09 356.46 02-JUN-12:09 25.40 23.51
July 0.488741E+10 13818.87 02-JUL-08:21 25.00 21.47 0.191595E+09 356.46 11-JUL-10:09 25.18 17.11
August 0.548693E+10 11873.59 13-AUG-09:12 28.17 19.21 0.213925E+09 357.03 14-AUG-10:09 27.88 23.11
September 0.339337E+10 12825.67 03-SEP-08:52 22.80 14.85 0.189328E+09 356.47 19-SEP-10:09 20.00 15.38
October 0.243790E+10 6426.72 15-OCT-09:33 17.93 12.69 0.193898E+09 356.46 02-OCT-10:09 17.93 12.69
November 0.795439E+09 5375.55 01-NOV-12:02 12.88 7.12 0.170429E+09 356.45 09-NOV-15:09 13.80 12.65
December 0.334716E+09 1414.25 20-DEC-11:05 8.90 5.16 0.148073E+09 349.36 20-DEC-11:09 8.90 5.16
                     
Annual Sum or Average 0.283689E+11         0.217116E+10        
Minimum of Months 0.220432E+09 910.89   -7.2 -9.9 0.138453E+09 331.71   -7.2 -9.9
Maximum of Months 0.548693E+10 13818.87   28.17 23.51 0.213925E+09 357.03   27.88 23.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.116013E+10 6066.17 19-JAN-13:25 9.40 3.94 0.346403E+09 549.50 30-JAN-14:50 2.80 -1.0
February 0.147124E+10 6686.53 02-FEB-13:40 5.97 -0.5 0.324246E+09 549.50 17-FEB-14:09 6.60 2.15
March 0.300392E+10 8911.13 29-MAR-12:50 7.80 5.26 0.412035E+09 549.69 29-MAR-13:00 7.80 5.51
April 0.332488E+10 9221.02 07-APR-12:30 26.15 15.90 0.381898E+09 550.49 10-APR-13:20 20.20 10.17
May 0.449278E+10 13085.47 29-MAY-12:32 27.77 17.46 0.432403E+09 550.59 30-MAY-13:20 29.80 17.64
June 0.584381E+10 10125.10 19-JUN-05:02 24.08 22.05 0.436053E+09 550.17 19-JUN-13:20 34.80 23.85
July 0.680018E+10 14128.23 30-JUL-11:32 26.10 23.28 0.406341E+09 550.95 17-JUL-13:20 26.10 23.28
August 0.841670E+10 14053.93 13-AUG-12:32 30.93 19.36 0.455809E+09 561.57 30-AUG-13:20 27.77 15.58
September 0.661183E+10 15181.69 03-SEP-12:12 24.23 15.64 0.403695E+09 581.19 28-SEP-13:09 22.98 13.55
October 0.658354E+10 14413.94 15-OCT-10:53 19.40 13.43 0.416028E+09 573.18 04-OCT-13:20 19.40 13.43
November 0.272641E+10 11017.01 02-NOV-12:40 15.40 8.14 0.383504E+09 549.77 03-NOV-13:20 17.40 10.62
December 0.159718E+10 7149.16 21-DEC-13:03 2.88 -1.7 0.348185E+09 549.49 14-DEC-14:09 2.88 -1.7
                     
Annual Sum or Average 0.520326E+11         0.474660E+10        
Minimum of Months 0.116013E+10 6066.17   2.88 -1.7 0.324246E+09 549.49   2.80 -1.7
Maximum of Months 0.841670E+10 15181.69   30.93 23.28 0.455809E+09 581.19   34.80 23.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.275284E+09 1471.23 20-JAN-15:50 7.30 3.83 0.201799E+09 347.63 19-JAN-14:00 7.30 3.83
February 0.368645E+09 2460.72 24-FEB-15:30 8.05 2.04 0.187252E+09 347.83 17-FEB-14:00 8.05 2.04
March 0.131649E+10 5516.63 29-MAR-15:50 7.20 4.93 0.246562E+09 347.85 29-MAR-13:20 7.20 4.93
April 0.202134E+10 8626.26 09-APR-16:23 16.65 13.97 0.238339E+09 347.85 07-APR-13:20 16.65 13.97
May 0.333700E+10 12661.91 21-MAY-15:12 20.37 13.43 0.273948E+09 347.87 15-MAY-13:00 20.37 13.43
June 0.465719E+10 12779.23 18-JUN-15:52 25.60 22.09 0.276241E+09 347.87 26-JUN-09:20 25.37 19.69
July 0.503218E+10 13633.86 04-JUL-16:41 25.18 18.20 0.257362E+09 347.87 17-JUL-09:20 27.97 21.33
August 0.566810E+10 12645.41 13-AUG-15:52 30.00 20.46 0.288494E+09 348.32 14-AUG-09:20 27.40 22.88
September 0.350566E+10 13078.26 03-SEP-16:12 24.80 16.47 0.254710E+09 348.19 05-SEP-09:20 24.07 19.46
October 0.268778E+10 11492.78 15-OCT-15:32 19.80 12.41 0.259635E+09 347.86 16-OCT-09:09 16.88 14.11
November 0.883725E+09 3803.65 03-NOV-15:30 16.10 10.65 0.224675E+09 347.85 09-NOV-14:00 13.90 12.65
December 0.395531E+09 1390.70 08-DEC-15:30 6.40 2.12 0.198327E+09 347.83 21-DEC-14:50 3.30 -1.8
                     
Annual Sum or Average 0.301489E+11         0.290735E+10        
Minimum of Months 0.275284E+09 1390.70   6.40 2.04 0.187252E+09 347.63   3.30 -1.8
Maximum of Months 0.566810E+10 13633.86   30.00 22.09 0.288494E+09 348.32   27.97 22.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.326924E+09 9192.65 02-JAN-05:02 -12.1
February 0.00 0.00 01-FEB-00:10 -1.1
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 0.326924E+09      
Minimum of Months 0.00 0.00   -12.1
Maximum of Months 0.326924E+09 9192.65   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.369941E+10 13321.01 02-JAN-06:10 -11.7
February 0.297480E+10 13225.14 06-FEB-06:10 -12.9
March 0.136425E+10 9448.71 20-MAR-06:12 -0.6
April 0.676734E+09 6496.82 03-APR-06:02 2.38
May 0.198776E+09 3230.75 14-MAY-07:27 11.95
June 42707623.84 4525.20 19-JUN-05:02 24.08
July 22662618.30 3895.29 25-JUL-05:02 23.90
August 39444148.46 3458.48 01-AUG-05:03 23.90
September 0.146295E+09 2764.91 01-SEP-05:03 24.08
October 0.459186E+09 3149.43 19-OCT-05:03 5.37
November 0.148738E+10 10069.52 24-NOV-07:12 -4.2
December 0.259603E+10 9811.61 11-DEC-06:08 1.70
         
Annual Sum or Average 0.137077E+11      
Minimum of Months 22662618.30 2764.91   -12.9
Maximum of Months 0.369941E+10 13321.01   24.08



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.203087E+10 8392.16 02-JAN-08:19 -10.9
February 0.145871E+10 5729.72 06-FEB-07:20 -13.1
March 0.942953E+09 3232.28 01-MAR-11:05 13.90
April 0.334640E+09 2520.30 23-APR-15:20 13.70
May 60005685.81 2421.73 29-MAY-09:52 26.70
June 16132763.37 2268.17 04-JUN-14:32 24.07
July 25867818.76 3044.50 09-JUL-14:41 27.95
August 18425303.63 2767.08 20-AUG-10:23 25.00
September 23052627.74 3429.47 03-SEP-09:32 23.87
October 0.106308E+09 4093.58 29-OCT-12:43 11.52
November 0.835310E+09 3074.62 24-NOV-07:03 -4.3
December 0.128594E+10 4098.90 11-DEC-07:12 1.70
         
Annual Sum or Average 0.713822E+10      
Minimum of Months 16132763.37 2268.17   -13.1
Maximum of Months 0.203087E+10 8392.16   27.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.146475E+10 6679.58 02-JAN-09:00 -10.6
February 0.875537E+09 2487.57 06-FEB-09:40 -11.5
March 0.466105E+09 1524.84 01-MAR-11:40 13.90
April 0.112085E+09 1379.78 21-APR-07:08 6.10
May 11591896.60 1643.65 21-MAY-13:20 22.07
June 11925331.40 1900.21 19-JUN-05:02 24.08
July 18765422.53 2073.03 25-JUL-05:02 23.90
August 15563265.83 2260.42 22-AUG-04:03 25.92
September 22340110.38 2397.47 01-SEP-05:03 24.08
October 31909430.50 2291.48 09-OCT-13:23 13.60
November 0.388042E+09 1898.80 05-NOV-10:15 11.47
December 0.796784E+09 2891.26 17-DEC-12:43 12.20
         
Annual Sum or Average 0.421540E+10      
Minimum of Months 11591896.60 1379.78   -11.5
Maximum of Months 0.146475E+10 6679.58   25.92



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.694789E+09 14860.70 02-JAN-05:02 -12.1
February 0.117695E+09 11520.69 06-FEB-06:02 -12.9
March 3574446.23 9759.60 01-MAR-07:02 4.97
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 11675220.83 10127.99 27-NOV-07:03 7.30
December 29277229.12 10239.90 11-DEC-07:01 1.70
         
Annual Sum or Average 0.857010E+09      
Minimum of Months 0.00 0.00   -12.9
Maximum of Months 0.694789E+09 14860.70   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.212209E+10 21810.07 01-JAN-01:23 -4.4
February 0.116439E+10 20312.43 06-FEB-05:01 -13.2
March 0.150006E+09 17366.15 20-MAR-05:01 -1.5
April 14445859.44 16041.39 03-APR-06:01 2.38
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.313638E+09 18362.72 24-NOV-06:01 -4.4
December 0.569648E+09 18313.93 26-DEC-06:11 6.30
         
Annual Sum or Average 0.433421E+10      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.212209E+10 21810.07   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.314885E+10 8835.56 01-JAN-22:03 -9.5
February 0.247466E+10 8778.18 06-FEB-04:42 -13.3
March 0.566708E+09 7364.64 17-MAR-05:01 -1.1
April 89697173.57 7214.78 03-APR-05:11 2.60
May 289456.44 964.85 01-MAY-06:05 7.67
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 8866092.40 6279.45 31-OCT-06:02 5.68
November 0.732999E+09 8290.95 24-NOV-05:01 -4.0
December 0.181058E+10 8421.92 31-DEC-23:43 -8.2
         
Annual Sum or Average 0.883265E+10      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.314885E+10 8835.56   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.170408E+10 7588.90 01-JAN-22:03 -9.5
February 0.119758E+10 7537.99 06-FEB-04:42 -13.3
March 0.249897E+09 6089.25 17-MAR-05:01 -1.1
April 40131964.20 5831.50 03-APR-05:11 2.60
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 4756573.91 4802.75 31-OCT-06:02 5.68
November 0.363672E+09 7038.54 24-NOV-05:01 -4.0
December 0.948655E+09 6821.55 11-DEC-05:51 1.70
         
Annual Sum or Average 0.450877E+10      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.170408E+10 7588.90   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.206637E+10 10247.17 01-JAN-22:03 -9.5
February 0.143501E+10 10151.97 06-FEB-04:42 -13.3
March 0.368194E+09 8379.11 17-MAR-05:01 -1.1
April 77074468.17 8042.71 03-APR-05:11 2.60
May 633480.01 1930.59 01-MAY-06:05 7.67
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 3052964.38 6242.84 28-OCT-06:03 3.90
November 0.410091E+09 9270.38 24-NOV-05:01 -4.0
December 0.112266E+10 9299.43 11-DEC-05:51 1.70
         
Annual Sum or Average 0.548309E+10      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.206637E+10 10247.17   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.189915E+10 7918.73 01-JAN-22:03 -9.5
February 0.143754E+10 7864.31 06-FEB-04:42 -13.3
March 0.307971E+09 6268.02 17-MAR-05:01 -1.1
April 55464425.98 5904.07 03-APR-05:11 2.60
May 304177.58 993.94 01-MAY-06:05 7.67
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 4632672.44 4893.19 28-OCT-06:03 3.90
November 0.447092E+09 7278.53 24-NOV-05:01 -4.0
December 0.107941E+10 7068.42 11-DEC-05:51 1.70
         
Annual Sum or Average 0.523156E+10      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.189915E+10 7918.73   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.215688E+10 6726.36 01-JAN-22:03 -9.5
February 0.165309E+10 6414.27 06-FEB-05:01 -13.2
March 0.300205E+09 5475.57 20-MAR-05:01 -1.5
April 30024057.03 5247.67 03-APR-05:11 2.60
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.128505E+09 5406.18 24-NOV-06:01 -4.4
December 0.520648E+09 5406.32 11-DEC-06:01 1.70
         
Annual Sum or Average 0.478936E+10      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.215688E+10 6726.36   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.108519E+10 5857.69 01-JAN-00:06 -9.6
February 0.624884E+09 5434.94 06-FEB-05:01 -13.2
March 82622993.88 4461.23 20-MAR-05:01 -1.5
April 6384708.24 4130.88 03-APR-05:11 2.60
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 37433251.42 4276.44 24-NOV-06:01 -4.4
December 0.228131E+09 4404.83 11-DEC-06:01 1.70
         
Annual Sum or Average 0.206465E+10      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.108519E+10 5857.69   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.349306E+10 9970.55 02-JAN-07:50 -11.2
February 0.277448E+10 8930.52 06-FEB-07:10 -13.2
March 0.170550E+10 7973.23 23-MAR-06:10 -4.7
April 0.826278E+09 7228.46 03-APR-06:10 2.38
May 0.264221E+09 5973.26 01-MAY-06:15 8.13
June 195108.20 1066.19 02-JUN-06:10 13.98
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 2874353.03 4071.86 20-SEP-06:07 12.48
October 0.153011E+09 5777.28 27-OCT-06:08 5.68
November 0.106927E+10 7790.34 24-NOV-07:10 -4.3
December 0.209000E+10 8015.16 15-DEC-07:10 -3.6
         
Annual Sum or Average 0.123789E+11      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.349306E+10 9970.55   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.120861E+10 5990.39 01-JAN-22:03 -9.5
February 0.778377E+09 5624.91 06-FEB-05:01 -13.2
March 84432643.36 4450.43 01-MAR-06:11 4.07
April 9457648.23 4020.28 03-APR-06:01 2.38
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 56273641.37 4335.02 24-NOV-06:01 -4.4
December 0.262774E+09 4473.96 11-DEC-06:01 1.70
         
Annual Sum or Average 0.239993E+10      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.120861E+10 5990.39   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.184363E+10 7241.06 01-JAN-22:03 -9.5
February 0.121758E+10 7028.08 06-FEB-05:11 -13.1
March 0.145526E+09 5782.75 13-MAR-05:01 -0.6
April 12795945.27 5465.64 03-APR-05:11 2.60
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.229094E+09 6086.86 24-NOV-06:01 -4.4
December 0.646312E+09 6026.03 11-DEC-06:01 1.70
         
Annual Sum or Average 0.409494E+10      
Minimum of Months 0.00 0.00   -13.1
Maximum of Months 0.184363E+10 7241.06   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.984504E+09 6535.55 01-JAN-00:06 -9.6
February 0.550492E+09 6310.17 06-FEB-05:11 -13.1
March 65080397.92 4788.66 20-MAR-05:01 -1.5
April 3987334.08 4368.82 03-APR-05:11 2.60
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.110144E+09 5167.43 24-NOV-06:01 -4.4
December 0.339389E+09 5147.03 11-DEC-06:01 1.70
         
Annual Sum or Average 0.205360E+10      
Minimum of Months 0.00 0.00   -13.1
Maximum of Months 0.984504E+09 6535.55   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.111398E+10 8521.49 01-JAN-00:06 -9.6
February 0.590245E+09 8146.72 06-FEB-05:11 -13.1
March 81123609.68 6446.47 13-MAR-05:01 -0.6
April 9181655.03 5933.82 03-APR-06:01 2.38
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.100408E+09 6676.69 24-NOV-06:01 -4.4
December 0.370227E+09 6899.29 11-DEC-06:01 1.70
         
Annual Sum or Average 0.226517E+10      
Minimum of Months 0.00 0.00   -13.1
Maximum of Months 0.111398E+10 8521.49   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.109486E+10 6647.00 01-JAN-22:03 -9.5
February 0.680563E+09 6433.57 06-FEB-05:11 -13.1
March 76008937.55 4845.73 13-MAR-05:01 -0.6
April 7008372.32 4267.52 03-APR-06:01 2.38
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.134106E+09 5189.86 24-NOV-06:01 -4.4
December 0.385718E+09 5197.74 11-DEC-06:01 1.70
         
Annual Sum or Average 0.237826E+10      
Minimum of Months 0.00 0.00   -13.1
Maximum of Months 0.109486E+10 6647.00   23.90



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.332047E+10 3488.70 02-JAN-08:09 0.159593E+11 11206.55 02-JAN-08:09
February 0.301195E+10 3488.70 01-FEB-08:09 0.144673E+11 11206.55 01-FEB-08:09
March 0.357877E+10 3488.70 01-MAR-08:09 0.165050E+11 11206.55 01-MAR-08:09
April 0.319691E+10 3488.70 03-APR-07:10 0.154860E+11 11206.55 03-APR-07:10
May 0.344962E+10 3488.70 01-MAY-07:10 0.162322E+11 11206.55 01-MAY-07:10
June 0.343288E+10 3488.70 01-JUN-07:10 0.159146E+11 11206.55 01-JUN-07:10
July 0.321365E+10 3488.70 03-JUL-07:10 0.158014E+11 11206.55 03-JUL-07:10
August 0.357877E+10 3488.70 01-AUG-07:10 0.165050E+11 11206.55 01-AUG-07:10
September 0.319691E+10 3488.70 01-SEP-07:10 0.154816E+11 11206.55 01-SEP-07:10
October 0.332047E+10 3488.70 02-OCT-07:10 0.159615E+11 11206.55 02-OCT-07:10
November 0.328140E+10 3488.70 01-NOV-07:10 0.155311E+11 11206.55 01-NOV-07:10
December 0.321365E+10 3488.70 01-DEC-08:09 0.157992E+11 11206.55 01-DEC-08:09
             
Annual Sum or Average 0.397954E+11     0.189644E+12    
Minimum of Months 0.301195E+10 3488.70   0.144673E+11 11206.55  
Maximum of Months 0.357877E+10 3488.70   0.165050E+11 11206.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.332047E+10 3488.70 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.301195E+10 3488.70 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.357877E+10 3488.70 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.319691E+10 3488.70 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.344962E+10 3488.70 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.343288E+10 3488.70 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.321365E+10 3488.70 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.357877E+10 3488.70 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.319691E+10 3488.70 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.332047E+10 3488.70 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.328140E+10 3488.70 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.321365E+10 3488.70 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.397954E+11     0.115425E+12    
Minimum of Months 0.301195E+10 3488.70   0.879311E+10 6808.32  
Maximum of Months 0.357877E+10 3488.70   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.332047E+10 3488.70 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.301195E+10 3488.70 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.357877E+10 3488.70 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.319691E+10 3488.70 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.344962E+10 3488.70 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.343288E+10 3488.70 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.321365E+10 3488.70 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.357877E+10 3488.70 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.319691E+10 3488.70 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.332047E+10 3488.70 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.328140E+10 3488.70 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.321365E+10 3488.70 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.397954E+11     0.115425E+12    
Minimum of Months 0.301195E+10 3488.70   0.879311E+10 6808.32  
Maximum of Months 0.357877E+10 3488.70   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.464352E+09 735.45 02-JAN-16:40 0.204758E+10 1435.25 02-JAN-08:09
February 0.390009E+09 667.35 15-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.434368E+09 531.16 02-MAR-16:00 0.212947E+10 1435.25 01-MAR-08:09
April 0.370981E+09 391.89 21-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.390957E+09 391.44 08-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.382864E+09 382.31 29-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.361354E+09 379.54 24-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.407519E+09 398.27 16-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.378498E+09 470.79 27-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.409914E+09 583.53 31-OCT-15:00 0.204804E+10 1435.25 02-OCT-07:10
November 0.444718E+09 735.45 06-NOV-16:49 0.200273E+10 1435.25 01-NOV-07:10
December 0.458810E+09 735.45 01-DEC-16:30 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.489434E+10     0.243325E+11    
Minimum of Months 0.361354E+09 379.54   0.185366E+10 1435.25  
Maximum of Months 0.464352E+09 735.45   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.290231E+09 465.60 02-JAN-16:40 0.129621E+10 908.57 02-JAN-08:09
February 0.245055E+09 427.17 01-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.274259E+09 375.66 02-MAR-16:00 0.134804E+10 908.57 01-MAR-08:09
April 0.235270E+09 241.46 21-APR-15:00 0.125169E+10 908.57 03-APR-07:10
May 0.249049E+09 248.28 19-MAY-15:00 0.132213E+10 908.57 01-MAY-07:10
June 0.244130E+09 222.09 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.230237E+09 222.09 03-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.258920E+09 241.47 16-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.239371E+09 253.88 26-SEP-15:00 0.125111E+10 908.57 01-SEP-07:10
October 0.258485E+09 372.55 31-OCT-15:00 0.129650E+10 908.57 02-OCT-07:10
November 0.280012E+09 465.60 06-NOV-16:49 0.126781E+10 908.57 01-NOV-07:10
December 0.284453E+09 465.60 01-DEC-16:30 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.308947E+10     0.154036E+11    
Minimum of Months 0.230237E+09 222.09   0.117344E+10 908.57  
Maximum of Months 0.290231E+09 465.60   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.447252E+09 735.45 02-JAN-16:40 0.204757E+10 1435.24 02-JAN-08:09
February 0.379988E+09 663.06 15-FEB-16:00 0.185364E+10 1435.24 01-FEB-08:09
March 0.429973E+09 476.86 16-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.371468E+09 389.60 21-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.392644E+09 392.34 08-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.385220E+09 385.63 29-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.363481E+09 383.18 24-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.408905E+09 398.25 16-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.377330E+09 411.26 27-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.404314E+09 561.61 31-OCT-15:00 0.204803E+10 1435.24 02-OCT-07:10
November 0.433844E+09 735.45 06-NOV-16:49 0.200271E+10 1435.24 01-NOV-07:10
December 0.437148E+09 735.45 01-DEC-16:30 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.483157E+10     0.243324E+11    
Minimum of Months 0.363481E+09 383.18   0.185364E+10 1435.24  
Maximum of Months 0.447252E+09 735.45   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.286419E+09 465.57 02-JAN-16:40 0.129620E+10 908.57 02-JAN-08:09
February 0.242142E+09 416.47 15-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.271983E+09 331.89 16-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.234881E+09 256.12 14-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.246914E+09 253.05 08-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.242401E+09 249.10 29-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.229021E+09 248.83 24-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.257744E+09 256.76 16-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.238934E+09 316.62 27-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.256869E+09 358.77 06-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.276033E+09 465.57 06-NOV-16:49 0.126780E+10 908.57 01-NOV-07:10
December 0.281313E+09 465.57 01-DEC-16:30 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.306465E+10     0.154035E+11    
Minimum of Months 0.229021E+09 248.83   0.117344E+10 908.57  
Maximum of Months 0.286419E+09 465.57   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.462462E+09 735.45 02-JAN-16:40 0.204758E+10 1435.25 02-JAN-08:09
February 0.388722E+09 664.74 15-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.433450E+09 522.83 02-MAR-16:00 0.212947E+10 1435.25 01-MAR-08:09
April 0.370592E+09 388.99 21-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.390687E+09 388.50 08-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.382566E+09 378.93 29-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.361012E+09 376.02 24-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.407305E+09 395.66 16-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.377844E+09 412.18 27-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.409039E+09 577.70 31-OCT-15:00 0.204804E+10 1435.25 02-OCT-07:10
November 0.443517E+09 735.45 06-NOV-16:49 0.200273E+10 1435.25 01-NOV-07:10
December 0.456469E+09 735.45 01-DEC-16:30 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.488366E+10     0.243325E+11    
Minimum of Months 0.361012E+09 376.02   0.185366E+10 1435.25  
Maximum of Months 0.462462E+09 735.45   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.289349E+09 465.60 02-JAN-16:40 0.129621E+10 908.57 02-JAN-08:09
February 0.244489E+09 425.97 01-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.273859E+09 372.93 02-MAR-16:00 0.134804E+10 908.57 01-MAR-08:09
April 0.235011E+09 239.55 21-APR-15:00 0.125169E+10 908.57 03-APR-07:10
May 0.248860E+09 246.63 19-MAY-15:00 0.132213E+10 908.57 01-MAY-07:10
June 0.243939E+09 222.09 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.230008E+09 222.09 03-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.258746E+09 239.34 16-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.239058E+09 252.50 26-SEP-15:00 0.125111E+10 908.57 01-SEP-07:10
October 0.258056E+09 369.68 31-OCT-15:00 0.129650E+10 908.57 02-OCT-07:10
November 0.279461E+09 465.60 06-NOV-16:49 0.126781E+10 908.57 01-NOV-07:10
December 0.283561E+09 465.60 01-DEC-16:30 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.308440E+10     0.154036E+11    
Minimum of Months 0.230008E+09 222.09   0.117344E+10 908.57  
Maximum of Months 0.289349E+09 465.60   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.446352E+09 735.45 02-JAN-16:40 0.204757E+10 1435.24 02-JAN-08:09
February 0.379584E+09 660.24 15-FEB-16:00 0.185364E+10 1435.24 01-FEB-08:09
March 0.429547E+09 412.91 16-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.371083E+09 386.57 21-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.392360E+09 389.45 08-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.384835E+09 382.44 29-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.363111E+09 379.87 24-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.408652E+09 395.64 16-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.376784E+09 409.24 27-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.403967E+09 554.67 31-OCT-15:00 0.204803E+10 1435.24 02-OCT-07:10
November 0.433292E+09 735.45 06-NOV-16:49 0.200271E+10 1435.24 01-NOV-07:10
December 0.436165E+09 735.45 01-DEC-16:30 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.482573E+10     0.243324E+11    
Minimum of Months 0.363111E+09 379.87   0.185364E+10 1435.24  
Maximum of Months 0.446352E+09 735.45   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.285413E+09 465.57 02-JAN-16:40 0.129620E+10 908.57 02-JAN-08:09
February 0.241639E+09 414.87 15-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.271654E+09 327.80 16-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.234608E+09 254.98 14-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.246759E+09 251.61 08-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.242233E+09 247.50 29-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.228830E+09 247.23 24-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.257559E+09 255.48 16-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.238639E+09 312.08 27-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.256627E+09 355.50 06-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.275466E+09 465.57 06-NOV-16:49 0.126780E+10 908.57 01-NOV-07:10
December 0.280233E+09 465.57 01-DEC-16:30 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.305966E+10     0.154035E+11    
Minimum of Months 0.228830E+09 247.23   0.117344E+10 908.57  
Maximum of Months 0.285413E+09 465.57   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.464349E+09 735.45 02-JAN-16:40 0.204758E+10 1435.25 02-JAN-08:09
February 0.390008E+09 667.34 15-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.434367E+09 531.15 02-MAR-16:00 0.212947E+10 1435.25 01-MAR-08:09
April 0.370980E+09 391.88 21-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.390957E+09 391.43 08-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.382864E+09 382.31 29-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.361354E+09 379.53 24-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.407519E+09 398.26 16-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.378497E+09 470.77 27-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.409913E+09 583.52 31-OCT-15:00 0.204804E+10 1435.25 02-OCT-07:10
November 0.444717E+09 735.45 06-NOV-16:49 0.200273E+10 1435.25 01-NOV-07:10
December 0.458807E+09 735.45 01-DEC-16:30 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.489433E+10     0.243325E+11    
Minimum of Months 0.361354E+09 379.53   0.185366E+10 1435.25  
Maximum of Months 0.464349E+09 735.45   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.290229E+09 465.60 02-JAN-16:40 0.129621E+10 908.57 02-JAN-08:09
February 0.245054E+09 427.16 01-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.274259E+09 375.65 02-MAR-16:00 0.134804E+10 908.57 01-MAR-08:09
April 0.235269E+09 241.45 21-APR-15:00 0.125169E+10 908.57 03-APR-07:10
May 0.249049E+09 248.28 19-MAY-15:00 0.132213E+10 908.57 01-MAY-07:10
June 0.244129E+09 222.09 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.230236E+09 222.09 03-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.258942E+09 241.46 16-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.239371E+09 253.88 26-SEP-15:00 0.125111E+10 908.57 01-SEP-07:10
October 0.258485E+09 372.54 31-OCT-15:00 0.129650E+10 908.57 02-OCT-07:10
November 0.280012E+09 465.60 06-NOV-16:49 0.126781E+10 908.57 01-NOV-07:10
December 0.284444E+09 465.60 01-DEC-16:30 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.308948E+10     0.154036E+11    
Minimum of Months 0.230236E+09 222.09   0.117344E+10 908.57  
Maximum of Months 0.290229E+09 465.60   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.447251E+09 735.45 02-JAN-16:40 0.204757E+10 1435.24 02-JAN-08:09
February 0.379987E+09 663.06 15-FEB-16:00 0.185364E+10 1435.24 01-FEB-08:09
March 0.429960E+09 476.84 16-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.371468E+09 389.60 21-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.392644E+09 392.33 08-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.385220E+09 385.62 29-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.363481E+09 383.17 24-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.408905E+09 398.25 16-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.377330E+09 411.25 27-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.404314E+09 561.59 31-OCT-15:00 0.204803E+10 1435.24 02-OCT-07:10
November 0.433843E+09 735.45 06-NOV-16:49 0.200271E+10 1435.24 01-NOV-07:10
December 0.437147E+09 735.45 01-DEC-16:30 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.483155E+10     0.243324E+11    
Minimum of Months 0.363481E+09 383.17   0.185364E+10 1435.24  
Maximum of Months 0.447251E+09 735.45   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.286418E+09 465.57 02-JAN-16:40 0.129620E+10 908.57 02-JAN-08:09
February 0.242141E+09 416.47 15-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.271983E+09 331.88 16-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.234881E+09 256.12 14-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.246914E+09 253.05 08-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.242400E+09 249.10 29-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.229021E+09 248.83 24-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.257744E+09 256.76 16-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.238934E+09 316.60 27-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.256869E+09 358.76 06-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.276033E+09 465.57 06-NOV-16:49 0.126780E+10 908.57 01-NOV-07:10
December 0.281312E+09 465.57 01-DEC-16:30 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.306465E+10     0.154035E+11    
Minimum of Months 0.229021E+09 248.83   0.117344E+10 908.57  
Maximum of Months 0.286418E+09 465.57   0.134804E+10 908.57  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.332047E+10 0.159593E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.301195E+10 0.144673E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.357877E+10 0.165050E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.319691E+10 0.154860E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.344962E+10 0.162322E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.343288E+10 0.159146E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.321365E+10 0.158014E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.357877E+10 0.165050E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.319691E+10 0.154816E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.332047E+10 0.159615E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.328140E+10 0.155311E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.321365E+10 0.157992E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.397954E+11 0.189644E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.301195E+10 0.144673E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.357877E+10 0.165050E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.332047E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.301195E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.357877E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.319691E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.344962E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.343288E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.321365E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.357877E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.319691E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.332047E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.328140E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.321365E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.397954E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.301195E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.357877E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.332047E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.301195E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.357877E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.319691E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.344962E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.343288E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.321365E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.357877E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.319691E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.332047E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.328140E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.321365E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.397954E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.301195E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.357877E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.464352E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.733084E+09
February 0.901968E+09 0.390009E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.654299E+09
March 0.107774E+10 0.434368E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.536968E+09
April 0.956342E+09 0.370981E+09 0.197726E+10 0.00 0.00 0.00 0.00 281881.45 0.360921E+09
May 0.103597E+10 0.390957E+09 0.208852E+10 0.00 0.00 0.00 0.00 1203663.39 0.220959E+09
June 0.103308E+10 0.382864E+09 0.205071E+10 0.00 0.00 0.00 0.00 9084741.98 0.115980E+09
July 0.959235E+09 0.361354E+09 0.201461E+10 0.00 0.00 0.00 0.00 21653862.77 41963668.82
August 0.107774E+10 0.407519E+09 0.212947E+10 0.00 0.00 0.00 0.00 26434048.10 51688386.68
September 0.956342E+09 0.378498E+09 0.197634E+10 0.00 0.00 0.00 0.00 3251180.67 0.119228E+09
October 0.994195E+09 0.409914E+09 0.204804E+10 0.00 0.00 0.00 0.00 48854.36 0.292883E+09
November 0.984487E+09 0.444718E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.521510E+09
December 0.959235E+09 0.458810E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.617712E+09
                   
Annual Sum or Average 0.119305E+11 0.489434E+10 0.243325E+11 0.00 0.00 0.00 0.00 61958232.72 0.426720E+10
Minimum of Months 0.901968E+09 0.361354E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 41963668.82
Maximum of Months 0.107774E+10 0.464352E+09 0.212947E+10 0.00 0.00 0.00 0.00 26434048.10 0.733084E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.290231E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.489656E+09
February 0.571020E+09 0.245055E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.442177E+09
March 0.682301E+09 0.274259E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.365202E+09
April 0.605444E+09 0.235270E+09 0.125169E+10 0.00 0.00 0.00 0.00 187846.86 0.249919E+09
May 0.655854E+09 0.249049E+09 0.132213E+10 0.00 0.00 0.00 0.00 696375.15 0.151445E+09
June 0.654023E+09 0.244130E+09 0.129819E+10 0.00 0.00 0.00 0.00 5933848.89 78994312.80
July 0.607275E+09 0.230237E+09 0.127534E+10 0.00 0.00 0.00 0.00 13934785.09 29098457.26
August 0.682301E+09 0.258920E+09 0.134804E+10 0.00 0.00 0.00 0.00 17128828.00 36140378.11
September 0.605444E+09 0.239371E+09 0.125111E+10 0.00 0.00 0.00 0.00 2155036.85 83739523.34
October 0.629407E+09 0.258485E+09 0.129650E+10 0.00 0.00 0.00 0.00 32564.72 0.202798E+09
November 0.623262E+09 0.280012E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.354191E+09
December 0.607275E+09 0.284453E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.415192E+09
                   
Annual Sum or Average 0.755301E+10 0.308947E+10 0.154036E+11 0.00 0.00 0.00 0.00 40069285.57 0.289855E+10
Minimum of Months 0.571020E+09 0.230237E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 29098457.26
Maximum of Months 0.682301E+09 0.290231E+09 0.134804E+10 0.00 0.00 0.00 0.00 17128828.00 0.489656E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.447252E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.754835E+09
February 0.901968E+09 0.379988E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.689345E+09
March 0.107774E+10 0.429973E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.562736E+09
April 0.956342E+09 0.371468E+09 0.197725E+10 0.00 0.00 0.00 0.00 281653.43 0.377123E+09
May 0.103597E+10 0.392644E+09 0.208851E+10 0.00 0.00 0.00 0.00 1047778.95 0.224456E+09
June 0.103308E+10 0.385220E+09 0.205070E+10 0.00 0.00 0.00 0.00 8938866.73 0.116739E+09
July 0.959235E+09 0.363481E+09 0.201460E+10 0.00 0.00 0.00 0.00 21091749.76 43142963.75
August 0.107774E+10 0.408905E+09 0.212945E+10 0.00 0.00 0.00 0.00 25594940.39 54432609.11
September 0.956342E+09 0.377330E+09 0.197632E+10 0.00 0.00 0.00 0.00 3221096.53 0.128414E+09
October 0.994195E+09 0.404314E+09 0.204803E+10 0.00 0.00 0.00 0.00 45518.40 0.320756E+09
November 0.984487E+09 0.433844E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.551258E+09
December 0.959235E+09 0.437148E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.651231E+09
                   
Annual Sum or Average 0.119305E+11 0.483157E+10 0.243324E+11 0.00 0.00 0.00 0.00 60221604.19 0.447447E+10
Minimum of Months 0.901968E+09 0.363481E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 43142963.75
Maximum of Months 0.107774E+10 0.447252E+09 0.212945E+10 0.00 0.00 0.00 0.00 25594940.39 0.754835E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.286419E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.492004E+09
February 0.570983E+09 0.242142E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.442762E+09
March 0.682256E+09 0.271983E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.369654E+09
April 0.605404E+09 0.234881E+09 0.125169E+10 0.00 0.00 0.00 0.00 187857.62 0.250194E+09
May 0.655811E+09 0.246914E+09 0.132212E+10 0.00 0.00 0.00 0.00 784488.69 0.152624E+09
June 0.653980E+09 0.242401E+09 0.129818E+10 0.00 0.00 0.00 0.00 5884330.02 81602336.50
July 0.607235E+09 0.229021E+09 0.127533E+10 0.00 0.00 0.00 0.00 13894182.78 31546976.89
August 0.682256E+09 0.257744E+09 0.134804E+10 0.00 0.00 0.00 0.00 16948479.38 37642083.27
September 0.605404E+09 0.238934E+09 0.125110E+10 0.00 0.00 0.00 0.00 2152665.35 83867983.77
October 0.629366E+09 0.256869E+09 0.129649E+10 0.00 0.00 0.00 0.00 32587.17 0.204852E+09
November 0.623221E+09 0.276033E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.350831E+09
December 0.607235E+09 0.281313E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.416674E+09
                   
Annual Sum or Average 0.755252E+10 0.306465E+10 0.154035E+11 0.00 0.00 0.00 0.00 39884591.00 0.291425E+10
Minimum of Months 0.570983E+09 0.229021E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 31546976.89
Maximum of Months 0.682256E+09 0.286419E+09 0.134804E+10 0.00 0.00 0.00 0.00 16948479.38 0.492004E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.462462E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.409403E+09
February 0.901968E+09 0.388722E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.363012E+09
March 0.107774E+10 0.433450E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.290927E+09
April 0.956342E+09 0.370592E+09 0.197726E+10 0.00 0.00 0.00 0.00 185178.64 0.192528E+09
May 0.103597E+10 0.390687E+09 0.208852E+10 0.00 0.00 0.00 0.00 1125578.97 0.112698E+09
June 0.103308E+10 0.382566E+09 0.205071E+10 0.00 0.00 0.00 0.00 5654370.22 58151316.24
July 0.959235E+09 0.361012E+09 0.201461E+10 0.00 0.00 0.00 0.00 13291646.95 19367155.45
August 0.107774E+10 0.407305E+09 0.212947E+10 0.00 0.00 0.00 0.00 15164915.23 26766976.06
September 0.956342E+09 0.377844E+09 0.197634E+10 0.00 0.00 0.00 0.00 1822369.82 65961745.08
October 0.994195E+09 0.409039E+09 0.204804E+10 0.00 0.00 0.00 0.00 29313.44 0.169018E+09
November 0.984487E+09 0.443517E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.307740E+09
December 0.959235E+09 0.456469E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.356731E+09
                   
Annual Sum or Average 0.119305E+11 0.488366E+10 0.243325E+11 0.00 0.00 0.00 0.00 37273373.27 0.237230E+10
Minimum of Months 0.901968E+09 0.361012E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 19367155.45
Maximum of Months 0.107774E+10 0.462462E+09 0.212947E+10 0.00 0.00 0.00 0.00 15164915.23 0.409403E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.289349E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.274483E+09
February 0.571020E+09 0.244489E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.247273E+09
March 0.682301E+09 0.273859E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.201110E+09
April 0.605444E+09 0.235011E+09 0.125169E+10 0.00 0.00 0.00 0.00 103155.34 0.136139E+09
May 0.655854E+09 0.248860E+09 0.132213E+10 0.00 0.00 0.00 0.00 387274.82 79949864.85
June 0.654023E+09 0.243939E+09 0.129819E+10 0.00 0.00 0.00 0.00 3328225.87 41324291.63
July 0.607275E+09 0.230008E+09 0.127534E+10 0.00 0.00 0.00 0.00 7751894.99 14719295.79
August 0.682301E+09 0.258746E+09 0.134804E+10 0.00 0.00 0.00 0.00 9301919.55 20098763.22
September 0.605444E+09 0.239058E+09 0.125111E+10 0.00 0.00 0.00 0.00 1167110.95 47745806.61
October 0.629407E+09 0.258056E+09 0.129650E+10 0.00 0.00 0.00 0.00 19540.12 0.118593E+09
November 0.623262E+09 0.279461E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.211542E+09
December 0.607275E+09 0.283561E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.241719E+09
                   
Annual Sum or Average 0.755301E+10 0.308440E+10 0.154036E+11 0.00 0.00 0.00 0.00 22059121.64 0.163470E+10
Minimum of Months 0.571020E+09 0.230008E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 14719295.79
Maximum of Months 0.682301E+09 0.289349E+09 0.134804E+10 0.00 0.00 0.00 0.00 9301919.55 0.274483E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.446352E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.510065E+10
February 0.901968E+09 0.379584E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.510259E+10
March 0.107774E+10 0.429547E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.462420E+10
April 0.956342E+09 0.371083E+09 0.197725E+10 0.00 0.00 0.00 0.00 10880013.74 0.274898E+10
May 0.103597E+10 0.392360E+09 0.208851E+10 0.00 0.00 0.00 0.00 44360796.59 0.167051E+10
June 0.103308E+10 0.384835E+09 0.205070E+10 0.00 0.00 0.00 0.00 0.314659E+09 0.565305E+09
July 0.959235E+09 0.363111E+09 0.201460E+10 0.00 0.00 0.00 0.00 0.665115E+09 77781244.55
August 0.107774E+10 0.408652E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.806870E+09 0.189216E+09
September 0.956342E+09 0.376784E+09 0.197632E+10 0.00 0.00 0.00 0.00 0.131490E+09 0.801511E+09
October 0.994195E+09 0.403967E+09 0.204803E+10 0.00 0.00 0.00 0.00 1592739.32 0.215003E+10
November 0.984487E+09 0.433292E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.388603E+10
December 0.959235E+09 0.436165E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.463325E+10
                   
Annual Sum or Average 0.119305E+11 0.482573E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.197497E+10 0.315501E+11
Minimum of Months 0.901968E+09 0.363111E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 77781244.55
Maximum of Months 0.107774E+10 0.446352E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.806870E+09 0.510259E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.285413E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.275357E+09
February 0.570983E+09 0.241639E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.246955E+09
March 0.682256E+09 0.271654E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.203965E+09
April 0.605404E+09 0.234608E+09 0.125169E+10 0.00 0.00 0.00 0.00 103844.65 0.136682E+09
May 0.655811E+09 0.246759E+09 0.132212E+10 0.00 0.00 0.00 0.00 540999.56 81001219.70
June 0.653980E+09 0.242233E+09 0.129818E+10 0.00 0.00 0.00 0.00 3251080.66 43635689.03
July 0.607235E+09 0.228830E+09 0.127533E+10 0.00 0.00 0.00 0.00 7773489.88 16579800.64
August 0.682256E+09 0.257559E+09 0.134804E+10 0.00 0.00 0.00 0.00 9267960.76 21175321.10
September 0.605404E+09 0.238639E+09 0.125110E+10 0.00 0.00 0.00 0.00 1165960.86 47885551.70
October 0.629366E+09 0.256627E+09 0.129649E+10 0.00 0.00 0.00 0.00 19552.17 0.120408E+09
November 0.623221E+09 0.275466E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.208472E+09
December 0.607235E+09 0.280233E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.241724E+09
                   
Annual Sum or Average 0.755252E+10 0.305966E+10 0.154035E+11 0.00 0.00 0.00 0.00 22122888.55 0.164384E+10
Minimum of Months 0.570983E+09 0.228830E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 16579800.64
Maximum of Months 0.682256E+09 0.285413E+09 0.134804E+10 0.00 0.00 0.00 0.00 9267960.76 0.275357E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.464349E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.636302E+09
February 0.901968E+09 0.390008E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.569593E+09
March 0.107774E+10 0.434367E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.470061E+09
April 0.956342E+09 0.370980E+09 0.197726E+10 0.00 0.00 0.00 0.00 238404.64 0.316478E+09
May 0.103597E+10 0.390957E+09 0.208852E+10 0.00 0.00 0.00 0.00 1117354.35 0.189798E+09
June 0.103308E+10 0.382864E+09 0.205071E+10 0.00 0.00 0.00 0.00 7969367.52 98218633.83
July 0.959235E+09 0.361354E+09 0.201461E+10 0.00 0.00 0.00 0.00 18604501.58 35108281.75
August 0.107774E+10 0.407519E+09 0.212947E+10 0.00 0.00 0.00 0.00 22528845.49 44220785.83
September 0.956342E+09 0.378497E+09 0.197634E+10 0.00 0.00 0.00 0.00 2745030.10 0.103717E+09
October 0.994195E+09 0.409913E+09 0.204804E+10 0.00 0.00 0.00 0.00 43189.97 0.259620E+09
November 0.984487E+09 0.444717E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.467714E+09
December 0.959235E+09 0.458807E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.547143E+09
                   
Annual Sum or Average 0.119305E+11 0.489433E+10 0.243325E+11 0.00 0.00 0.00 0.00 53246693.65 0.373797E+10
Minimum of Months 0.901968E+09 0.361354E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 35108281.75
Maximum of Months 0.107774E+10 0.464349E+09 0.212947E+10 0.00 0.00 0.00 0.00 22528845.49 0.636302E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.465148E+09 0.290229E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.425276E+09
February 0.421807E+09 0.245054E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.386087E+09
March 0.502994E+09 0.274259E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.320444E+09
April 0.447140E+09 0.235269E+09 0.125169E+10 0.00 0.00 0.00 0.00 143004.22 0.218893E+09
May 0.484071E+09 0.249049E+09 0.132213E+10 0.00 0.00 0.00 0.00 566384.16 0.130396E+09
June 0.482240E+09 0.244129E+09 0.129819E+10 0.00 0.00 0.00 0.00 4843378.98 67394510.69
July 0.448971E+09 0.230236E+09 0.127534E+10 0.00 0.00 0.00 0.00 11466521.64 24612191.61
August 0.502994E+09 0.258942E+09 0.134804E+10 0.00 0.00 0.00 0.00 14034204.96 31034611.36
September 0.447140E+09 0.239371E+09 0.125111E+10 0.00 0.00 0.00 0.00 1710925.94 72962770.70
October 0.465148E+09 0.258485E+09 0.129650E+10 0.00 0.00 0.00 0.00 16314.42 0.179079E+09
November 0.460569E+09 0.280012E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.317955E+09
December 0.448971E+09 0.284444E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.368804E+09
                   
Annual Sum or Average 0.557719E+10 0.308948E+10 0.154036E+11 0.00 0.00 0.00 0.00 32780734.32 0.254294E+10
Minimum of Months 0.421807E+09 0.230236E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 24612191.61
Maximum of Months 0.502994E+09 0.290229E+09 0.134804E+10 0.00 0.00 0.00 0.00 14034204.96 0.425276E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.447251E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.656800E+09
February 0.901968E+09 0.379987E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.602355E+09
March 0.107774E+10 0.429960E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.492022E+09
April 0.956342E+09 0.371468E+09 0.197725E+10 0.00 0.00 0.00 0.00 238203.82 0.329778E+09
May 0.103597E+10 0.392644E+09 0.208851E+10 0.00 0.00 0.00 0.00 889826.02 0.193004E+09
June 0.103308E+10 0.385220E+09 0.205070E+10 0.00 0.00 0.00 0.00 7572910.84 99258208.52
July 0.959235E+09 0.363481E+09 0.201460E+10 0.00 0.00 0.00 0.00 17882249.97 36406772.45
August 0.107774E+10 0.408905E+09 0.212945E+10 0.00 0.00 0.00 0.00 21560694.29 46675296.82
September 0.956342E+09 0.377330E+09 0.197632E+10 0.00 0.00 0.00 0.00 2690842.60 0.111571E+09
October 0.994195E+09 0.404314E+09 0.204803E+10 0.00 0.00 0.00 0.00 28452.24 0.280559E+09
November 0.984487E+09 0.433843E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.492457E+09
December 0.959235E+09 0.437147E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.577307E+09
                   
Annual Sum or Average 0.119305E+11 0.483155E+10 0.243324E+11 0.00 0.00 0.00 0.00 50863179.78 0.391819E+10
Minimum of Months 0.901968E+09 0.363481E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 36406772.45
Maximum of Months 0.107774E+10 0.447251E+09 0.212945E+10 0.00 0.00 0.00 0.00 21560694.29 0.656800E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.286418E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.427037E+09
February 0.570983E+09 0.242141E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.385558E+09
March 0.682256E+09 0.271983E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.323260E+09
April 0.605404E+09 0.234881E+09 0.125169E+10 0.00 0.00 0.00 0.00 158941.41 0.219002E+09
May 0.655811E+09 0.246914E+09 0.132212E+10 0.00 0.00 0.00 0.00 694184.58 0.131252E+09
June 0.653980E+09 0.242400E+09 0.129818E+10 0.00 0.00 0.00 0.00 4991634.44 69509933.74
July 0.607235E+09 0.229021E+09 0.127533E+10 0.00 0.00 0.00 0.00 11734215.38 26760465.05
August 0.682256E+09 0.257744E+09 0.134804E+10 0.00 0.00 0.00 0.00 14333099.44 32284037.05
September 0.605404E+09 0.238934E+09 0.125110E+10 0.00 0.00 0.00 0.00 1809891.07 72954411.26
October 0.629366E+09 0.256869E+09 0.129649E+10 0.00 0.00 0.00 0.00 28813.56 0.180518E+09
November 0.623221E+09 0.276033E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.314319E+09
December 0.607235E+09 0.281312E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.369194E+09
                   
Annual Sum or Average 0.755252E+10 0.306465E+10 0.154035E+11 0.00 0.00 0.00 0.00 33750779.87 0.255165E+10
Minimum of Months 0.570983E+09 0.229021E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 26760465.05
Maximum of Months 0.682256E+09 0.286418E+09 0.134804E+10 0.00 0.00 0.00 0.00 14333099.44 0.427037E+09



Table of Contents

Report: SpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.872413E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.792966E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.653125E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 224853.63 0.437798E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1334282.82 0.255845E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8350721.72 0.130375E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20777132.75 42585711.28
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24469177.50 58094780.95
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2350664.84 0.145024E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3449.24 0.369030E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.665824E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.776521E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57510282.50 0.519960E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42585711.28
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24469177.50 0.872413E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.108292E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.985004E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.816325E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 284363.19 0.548975E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1528523.91 0.328269E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10448360.23 0.168717E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25825956.09 56307830.27
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31331554.64 74721436.76
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3052725.42 0.182288E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6791.85 0.458292E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.810088E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.947260E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 72478275.33 0.645916E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 56307830.27
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31331554.64 0.108292E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.109904E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.100054E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.836900E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70843.19 0.569130E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 586601.13 0.352464E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8622969.59 0.183597E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21451578.68 64631591.71
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28917336.80 75983457.23
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2650709.64 0.189882E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.466116E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.801986E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.941736E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62300039.04 0.658201E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64631591.71
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28917336.80 0.109904E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 3488.70 02-JAN-08:09 11206.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 3488.70 01-FEB-08:09 11206.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 3488.70 01-MAR-08:09 11206.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 3488.70 03-APR-07:10 11206.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 3488.70 01-MAY-07:10 11206.55 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 3488.70 01-JUN-07:10 11206.55 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 3488.70 03-JUL-07:10 11206.55 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 3488.70 01-AUG-07:10 11206.55 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 3488.70 01-SEP-07:10 11206.55 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 3488.70 02-OCT-07:10 11206.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 3488.70 01-NOV-07:10 11206.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 3488.70 01-DEC-08:09 11206.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   3488.70   11206.55   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   3488.70   11206.55   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 3488.70 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 3488.70 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 3488.70 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 3488.70 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 3488.70 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 3488.70 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 3488.70 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 3488.70 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 3488.70 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 3488.70 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 3488.70 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 3488.70 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   3488.70   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   3488.70   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 3488.70 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 3488.70 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 3488.70 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 3488.70 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 3488.70 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 3488.70 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 3488.70 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 3488.70 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 3488.70 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 3488.70 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 3488.70 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 3488.70 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   3488.70   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   3488.70   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 735.45 02-JAN-16:40 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1249.29 31-JAN-01:00
February 1306.65 01-FEB-10:09 667.35 15-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1322.39 06-FEB-01:00
March 1306.65 01-MAR-10:09 531.16 02-MAR-16:00 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 999.57 21-MAR-21:05
April 1306.65 03-APR-09:09 391.89 21-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 16.73 07-APR-13:00 803.48 11-APR-04:00
May 1306.65 01-MAY-09:09 391.44 08-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 53.82 29-MAY-12:10 470.38 03-MAY-04:00
June 1306.65 01-JUN-09:09 382.31 29-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 112.91 19-JUN-21:03 282.96 02-JUN-22:00
July 1306.65 03-JUL-09:09 379.54 24-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 115.04 09-JUL-13:52 134.02 02-JUL-18:33
August 1306.65 01-AUG-09:09 398.27 16-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 157.57 04-AUG-21:03 180.40 20-AUG-06:00
September 1306.65 01-SEP-09:09 470.79 27-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 44.13 14-SEP-14:00 238.07 23-SEP-04:00
October 1306.65 02-OCT-09:09 583.53 31-OCT-15:00 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 7.42 25-OCT-11:00 667.79 17-OCT-24:00
November 1306.65 01-NOV-09:09 735.45 06-NOV-16:49 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1016.25 23-NOV-02:00
December 1306.65 01-DEC-10:09 735.45 01-DEC-16:30 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1313.50 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   379.54   1435.25   0.00 0.00 0.00 0.00 0.00   134.02  
Maximum of Months 1306.65   735.45   1435.25   0.00 0.00 0.00 0.00 157.57   1322.39  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 465.60 02-JAN-16:40 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 833.14 31-JAN-01:00
February 827.22 01-FEB-10:09 427.17 01-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 881.58 06-FEB-01:00
March 827.22 01-MAR-10:09 375.66 02-MAR-16:00 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 706.54 12-MAR-10:00
April 827.22 03-APR-09:09 241.46 21-APR-15:00 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 11.15 07-APR-13:00 535.08 11-APR-04:00
May 827.22 01-MAY-09:09 248.28 19-MAY-15:00 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 34.41 29-MAY-12:05 314.71 03-MAY-04:00
June 827.22 01-JUN-09:09 222.09 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 75.03 19-JUN-21:03 188.87 02-JUN-22:00
July 827.22 03-JUL-09:09 222.09 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 75.68 09-JUL-13:52 95.57 02-JUL-18:33
August 827.22 01-AUG-09:09 241.47 16-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 104.71 04-AUG-21:03 126.46 20-AUG-06:00
September 827.22 01-SEP-09:09 253.88 26-SEP-15:00 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 29.42 14-SEP-14:00 168.26 10-SEP-07:50
October 827.22 02-OCT-09:09 372.55 31-OCT-15:00 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 4.94 25-OCT-11:00 496.46 08-OCT-08:20
November 827.22 01-NOV-09:09 465.60 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 678.30 23-NOV-02:00
December 827.22 01-DEC-10:09 465.60 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 875.73 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   222.09   908.57   0.00 0.00 0.00 0.00 0.00   95.57  
Maximum of Months 827.22   465.60   908.57   0.00 0.00 0.00 0.00 104.71   881.58  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 735.45 02-JAN-16:40 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1292.86 31-JAN-01:00
February 1306.65 01-FEB-10:09 663.06 15-FEB-16:00 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1322.39 06-FEB-01:00
March 1306.65 01-MAR-10:09 476.86 16-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1058.86 12-MAR-10:00
April 1306.65 03-APR-09:09 389.60 21-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 16.69 07-APR-13:00 814.69 11-APR-04:00
May 1306.65 01-MAY-09:09 392.34 08-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 50.88 29-MAY-12:05 476.45 03-MAY-04:00
June 1306.65 01-JUN-09:09 385.63 29-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 112.82 19-JUN-21:03 283.29 02-JUN-22:00
July 1306.65 03-JUL-09:09 383.18 24-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 113.52 09-JUL-13:52 138.06 02-JUL-18:33
August 1306.65 01-AUG-09:09 398.25 16-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 157.08 04-AUG-21:03 181.57 20-AUG-06:00
September 1306.65 01-SEP-09:09 411.26 27-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 44.07 14-SEP-14:00 250.44 30-SEP-24:00
October 1306.65 02-OCT-09:09 561.61 31-OCT-15:00 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 7.40 25-OCT-11:00 708.90 08-OCT-08:00
November 1306.65 01-NOV-09:09 735.45 06-NOV-16:49 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1043.12 23-NOV-02:00
December 1306.65 01-DEC-10:09 735.45 01-DEC-16:30 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1313.52 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   383.18   1435.24   0.00 0.00 0.00 0.00 0.00   138.06  
Maximum of Months 1306.65   735.45   1435.24   0.00 0.00 0.00 0.00 157.08   1322.39  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 465.57 02-JAN-16:40 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 835.25 31-JAN-01:00
February 827.17 01-FEB-10:09 416.47 15-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 881.57 06-FEB-01:00
March 827.17 01-MAR-10:09 331.89 16-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 671.58 21-MAR-21:05
April 827.17 03-APR-09:09 256.12 14-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 11.16 07-APR-13:00 543.31 11-APR-04:00
May 827.17 01-MAY-09:09 253.05 08-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 35.06 29-MAY-12:10 321.06 03-MAY-04:00
June 827.17 01-JUN-09:09 249.10 29-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 74.02 19-JUN-21:03 212.23 03-JUN-19:00
July 827.17 03-JUL-09:09 248.83 24-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 75.68 09-JUL-13:52 123.24 02-JUL-17:50
August 827.17 01-AUG-09:09 256.76 16-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 104.24 04-AUG-21:03 122.93 20-AUG-06:00
September 827.17 01-SEP-09:09 316.62 27-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 29.42 14-SEP-14:00 168.05 10-SEP-20:00
October 827.17 02-OCT-09:09 358.77 06-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 4.95 25-OCT-11:00 453.88 17-OCT-24:00
November 827.17 01-NOV-09:09 465.57 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 677.60 23-NOV-02:00
December 827.17 01-DEC-10:09 465.57 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 875.70 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   248.83   908.57   0.00 0.00 0.00 0.00 0.00   122.93  
Maximum of Months 827.17   465.57   908.57   0.00 0.00 0.00 0.00 104.24   881.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 735.45 02-JAN-16:40 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 713.75 31-JAN-01:00
February 1306.65 01-FEB-10:09 664.74 15-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 705.89 06-FEB-00:55
March 1306.65 01-MAR-10:09 522.83 02-MAR-16:00 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 532.08 21-MAR-21:05
April 1306.65 03-APR-09:09 388.99 21-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 9.07 07-APR-13:00 442.60 11-APR-04:00
May 1306.65 01-MAY-09:09 388.50 08-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 50.37 29-MAY-12:00 250.42 03-MAY-04:00
June 1306.65 01-JUN-09:09 378.93 29-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 61.58 19-JUN-21:03 150.38 02-JUN-22:00
July 1306.65 03-JUL-09:09 376.02 24-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 71.26 09-JUL-13:52 70.18 11-JUL-05:00
August 1306.65 01-AUG-09:09 395.66 16-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 84.62 04-AUG-21:03 101.24 20-AUG-06:00
September 1306.65 01-SEP-09:09 412.18 27-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 23.65 14-SEP-14:00 137.33 17-SEP-10:00
October 1306.65 02-OCT-09:09 577.70 31-OCT-15:00 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 4.16 25-OCT-11:00 403.38 08-OCT-08:00
November 1306.65 01-NOV-09:09 735.45 06-NOV-16:49 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 602.58 23-NOV-02:00
December 1306.65 01-DEC-10:09 735.45 01-DEC-16:30 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 741.72 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   376.02   1435.25   0.00 0.00 0.00 0.00 0.00   70.18  
Maximum of Months 1306.65   735.45   1435.25   0.00 0.00 0.00 0.00 84.62   741.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 465.60 02-JAN-16:40 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 481.49 31-JAN-01:00
February 827.22 01-FEB-10:09 425.97 01-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 500.22 05-FEB-08:40
March 827.22 01-MAR-10:09 372.93 02-MAR-16:00 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 389.47 12-MAR-10:00
April 827.22 03-APR-09:09 239.55 21-APR-15:00 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 6.05 07-APR-13:00 303.04 11-APR-04:00
May 827.22 01-MAY-09:09 246.63 19-MAY-15:00 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 18.12 29-MAY-11:52 176.04 03-MAY-04:00
June 827.22 01-JUN-09:09 222.09 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 40.57 19-JUN-21:03 104.70 02-JUN-22:00
July 827.22 03-JUL-09:09 222.09 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 41.73 09-JUL-13:52 49.75 11-JUL-05:00
August 827.22 01-AUG-09:09 239.34 16-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 55.82 04-AUG-21:03 73.34 20-AUG-06:00
September 827.22 01-SEP-09:09 252.50 26-SEP-15:00 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 15.77 14-SEP-14:00 94.12 17-SEP-10:00
October 827.22 02-OCT-09:09 369.68 31-OCT-15:00 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 2.77 25-OCT-11:00 298.37 08-OCT-08:00
November 827.22 01-NOV-09:09 465.60 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 409.75 23-NOV-02:00
December 827.22 01-DEC-10:09 465.60 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 499.22 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   222.09   908.57   0.00 0.00 0.00 0.00 0.00   49.75  
Maximum of Months 827.22   465.60   908.57   0.00 0.00 0.00 0.00 55.82   500.22  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 735.45 02-JAN-16:40 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 26254.47 31-JAN-07:01
February 1306.65 01-FEB-10:09 660.24 15-FEB-16:00 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 28695.22 06-FEB-07:01
March 1306.65 01-MAR-10:09 412.91 16-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 21950.55 23-MAR-06:01
April 1306.65 03-APR-09:09 386.57 21-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 1695.31 07-APR-17:00 15270.99 03-APR-06:01
May 1306.65 01-MAY-09:09 389.45 08-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 4014.77 30-MAY-12:00 10628.95 01-MAY-06:05
June 1306.65 01-JUN-09:09 382.44 29-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 9145.42 19-JUN-11:02 7103.75 02-JUN-06:02
July 1306.65 03-JUL-09:09 379.87 24-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 7093.58 07-JUL-11:03 2593.31 11-JUL-06:03
August 1306.65 01-AUG-09:09 395.64 16-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 7320.19 24-AUG-16:05 4752.38 08-AUG-06:03
September 1306.65 01-SEP-09:09 409.24 27-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 4396.58 14-SEP-16:10 9743.90 11-SEP-06:01
October 1306.65 02-OCT-09:09 554.67 31-OCT-15:00 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 657.64 25-OCT-11:10 13729.81 31-OCT-06:02
November 1306.65 01-NOV-09:09 735.45 06-NOV-16:49 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 21588.78 24-NOV-07:01
December 1306.65 01-DEC-10:09 735.45 01-DEC-16:30 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 22140.59 22-DEC-07:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   379.87   1435.24   0.00 0.00 0.00 0.00 0.00   2593.31  
Maximum of Months 1306.65   735.45   1435.24   0.00 0.00 0.00 0.00 9145.42   28695.22  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 465.57 02-JAN-16:40 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 482.12 31-JAN-01:00
February 827.17 01-FEB-10:09 414.87 15-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 473.74 06-FEB-00:55
March 827.17 01-MAR-10:09 327.80 16-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 360.11 21-MAR-21:10
April 827.17 03-APR-09:09 254.98 14-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 6.05 07-APR-13:00 312.94 11-APR-04:00
May 827.17 01-MAY-09:09 251.61 08-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 29.12 29-MAY-12:00 177.76 03-MAY-04:00
June 827.17 01-JUN-09:09 247.50 29-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 39.67 19-JUN-21:03 110.01 02-JUN-22:00
July 827.17 03-JUL-09:09 247.23 24-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 40.67 09-JUL-13:52 57.30 02-JUL-17:50
August 827.17 01-AUG-09:09 255.48 16-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 55.60 04-AUG-21:03 73.05 20-AUG-06:00
September 827.17 01-SEP-09:09 312.08 27-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 15.77 14-SEP-14:00 97.10 30-SEP-24:00
October 827.17 02-OCT-09:09 355.50 06-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 2.77 25-OCT-11:00 276.63 08-OCT-08:00
November 827.17 01-NOV-09:09 465.57 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 405.09 23-NOV-02:00
December 827.17 01-DEC-10:09 465.57 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 500.84 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   247.23   908.57   0.00 0.00 0.00 0.00 0.00   57.30  
Maximum of Months 827.17   465.57   908.57   0.00 0.00 0.00 0.00 55.60   500.84  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 735.45 02-JAN-16:40 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1103.45 31-JAN-01:00
February 1306.65 01-FEB-10:09 667.34 15-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1091.89 06-FEB-00:55
March 1306.65 01-MAR-10:09 531.15 02-MAR-16:00 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 838.27 21-MAR-21:05
April 1306.65 03-APR-09:09 391.88 21-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 14.06 07-APR-13:00 709.76 11-APR-04:00
May 1306.65 01-MAY-09:09 391.43 08-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 57.63 29-MAY-12:00 416.34 03-MAY-04:00
June 1306.65 01-JUN-09:09 382.31 29-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 94.79 19-JUN-21:03 242.81 02-JUN-22:00
July 1306.65 03-JUL-09:09 379.53 24-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 92.15 09-JUL-13:52 113.93 11-JUL-05:00
August 1306.65 01-AUG-09:09 398.26 16-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 131.82 04-AUG-21:03 160.31 20-AUG-06:00
September 1306.65 01-SEP-09:09 470.77 27-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 36.88 14-SEP-14:00 212.83 17-SEP-10:00
October 1306.65 02-OCT-09:09 583.52 31-OCT-15:00 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 6.34 25-OCT-11:00 604.02 08-OCT-08:00
November 1306.65 01-NOV-09:09 735.45 06-NOV-16:49 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 910.90 23-NOV-02:00
December 1306.65 01-DEC-10:09 735.45 01-DEC-16:30 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1099.07 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   379.53   1435.25   0.00 0.00 0.00 0.00 0.00   113.93  
Maximum of Months 1306.65   735.45   1435.25   0.00 0.00 0.00 0.00 131.82   1103.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 805.43 02-JAN-08:09 465.60 02-JAN-16:40 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 737.36 31-JAN-01:00
February 805.43 01-FEB-08:09 427.16 01-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 777.95 05-FEB-09:00
March 805.43 01-MAR-08:09 375.65 02-MAR-16:00 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 636.00 12-MAR-10:00
April 805.43 03-APR-07:10 241.45 21-APR-15:00 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 9.38 07-APR-13:00 472.92 11-APR-04:00
May 805.43 01-MAY-07:10 248.28 19-MAY-15:00 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 31.88 29-MAY-11:54 278.58 03-MAY-04:00
June 805.43 01-JUN-07:10 222.09 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 62.95 19-JUN-21:03 162.39 02-JUN-22:00
July 805.43 03-JUL-07:10 222.09 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 60.37 09-JUL-13:50 77.50 11-JUL-05:00
August 805.43 01-AUG-07:10 241.46 16-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 87.57 04-AUG-21:03 112.23 20-AUG-06:00
September 805.43 01-SEP-07:10 253.88 26-SEP-15:00 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 23.90 14-SEP-14:10 142.53 17-SEP-10:00
October 805.43 02-OCT-07:10 372.54 31-OCT-15:00 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 4.23 25-OCT-11:00 453.51 08-OCT-08:00
November 805.43 01-NOV-07:10 465.60 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 609.45 23-NOV-02:00
December 805.43 01-DEC-08:09 465.60 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 736.94 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 805.43   222.09   908.57   0.00 0.00 0.00 0.00 0.00   77.50  
Maximum of Months 805.43   465.60   908.57   0.00 0.00 0.00 0.00 87.57   777.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 735.45 02-JAN-16:40 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1141.96 31-JAN-01:00
February 1306.65 01-FEB-10:09 663.06 15-FEB-16:00 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1145.18 05-FEB-10:00
March 1306.65 01-MAR-10:09 476.84 16-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 952.23 12-MAR-10:00
April 1306.65 03-APR-09:09 389.60 21-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 14.04 07-APR-13:00 718.97 11-APR-04:00
May 1306.65 01-MAY-09:09 392.33 08-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 47.62 29-MAY-11:54 421.39 03-MAY-04:00
June 1306.65 01-JUN-09:09 385.62 29-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 94.71 19-JUN-21:03 243.19 02-JUN-22:00
July 1306.65 03-JUL-09:09 383.17 24-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 90.56 09-JUL-13:50 112.23 11-JUL-05:00
August 1306.65 01-AUG-09:09 398.25 16-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 131.41 04-AUG-21:03 161.32 20-AUG-06:00
September 1306.65 01-SEP-09:09 411.25 27-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 36.83 14-SEP-14:00 220.28 30-SEP-24:00
October 1306.65 02-OCT-09:09 561.59 31-OCT-15:00 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 6.21 25-OCT-11:00 650.41 08-OCT-08:00
November 1306.65 01-NOV-09:09 735.45 06-NOV-16:49 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 935.55 23-NOV-02:00
December 1306.65 01-DEC-10:09 735.45 01-DEC-16:30 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1159.27 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   383.17   1435.24   0.00 0.00 0.00 0.00 0.00   112.23  
Maximum of Months 1306.65   735.45   1435.24   0.00 0.00 0.00 0.00 131.41   1159.27  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 465.57 02-JAN-16:40 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 738.31 31-JAN-01:00
February 827.17 01-FEB-10:09 416.47 15-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 728.06 06-FEB-00:55
March 827.17 01-MAR-10:09 331.88 16-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 566.48 21-MAR-21:05
April 827.17 03-APR-09:09 256.12 14-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 9.38 07-APR-13:00 479.35 11-APR-04:00
May 827.17 01-MAY-09:09 253.05 08-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 36.47 29-MAY-12:00 283.72 03-MAY-04:00
June 827.17 01-JUN-09:09 249.10 29-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 62.17 19-JUN-21:03 175.66 03-JUN-19:00
July 827.17 03-JUL-09:09 248.83 24-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 60.38 09-JUL-13:50 95.43 02-JUL-17:40
August 827.17 01-AUG-09:09 256.76 16-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 87.22 04-AUG-21:03 109.19 20-AUG-06:00
September 827.17 01-SEP-09:09 316.60 27-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 24.59 14-SEP-14:00 145.25 30-SEP-24:00
October 827.17 02-OCT-09:09 358.76 06-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 4.23 25-OCT-11:00 404.11 08-OCT-08:00
November 827.17 01-NOV-09:09 465.57 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 608.02 23-NOV-02:00
December 827.17 01-DEC-10:09 465.57 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 741.55 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   248.83   908.57   0.00 0.00 0.00 0.00 0.00   95.43  
Maximum of Months 827.17   465.57   908.57   0.00 0.00 0.00 0.00 87.22   741.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1573.80 31-JAN-01:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1567.84 06-FEB-00:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1147.02 21-MAR-21:05
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.29 07-APR-13:00 994.68 11-APR-04:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75.93 29-MAY-12:00 577.30 03-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 99.92 19-JUN-21:03 324.31 02-JUN-22:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 133.71 09-JUL-14:00 145.93 11-JUL-05:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 157.95 12-AUG-18:53 215.66 20-AUG-06:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.92 14-SEP-14:00 291.68 30-SEP-24:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.87 25-OCT-11:00 859.20 08-OCT-08:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1319.09 23-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1625.57 31-DEC-22:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   145.93  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 157.95   1625.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1956.74 31-JAN-01:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1920.96 06-FEB-00:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1453.27 21-MAR-21:05
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.66 07-APR-13:00 1266.09 11-APR-04:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 89.13 29-MAY-12:00 733.00 03-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 126.04 19-JUN-21:03 417.49 02-JUN-22:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 166.91 09-JUL-13:52 188.53 11-JUL-05:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 205.18 12-AUG-18:53 274.64 20-AUG-06:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52.89 14-SEP-14:00 364.88 30-SEP-24:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.58 25-OCT-11:00 1055.22 17-OCT-24:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1626.31 23-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1966.88 31-DEC-22:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   188.53  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 205.18   1966.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1915.91 31-JAN-01:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1913.37 06-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1524.89 21-MAR-21:05
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.12 08-APR-10:00 1217.31 11-APR-04:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.10 30-MAY-13:00 711.46 03-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 150.96 19-JUN-21:03 418.33 03-JUN-18:55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 146.70 07-JUL-22:00 241.25 02-JUL-18:33
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 226.29 04-AUG-21:03 250.52 20-AUG-06:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.72 14-SEP-14:00 358.15 23-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1014.25 17-OCT-24:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1550.41 23-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1940.02 31-DEC-22:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   241.25  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 226.29   1940.02  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 7452.32 27-JAN-16:40 6035.01 3488.70 11182.33 0.00 0.00 0.00 0.00 0.00 0.00
February 8468.01 24-FEB-17:00 6035.01 3488.70 11182.33 0.00 0.00 0.00 0.00 0.00 0.00
March 13275.33 30-MAR-07:03 60350.08 34887.01 112065.54 0.00 0.00 0.00 0.00 0.00 0.00
April 29008.00 10-APR-06:03 5082.11 4651.60 29553.39 0.00 0.00 0.00 0.00 0.00 0.00
May 32737.07 30-MAY-05:12 2541.06 1550.53 21793.50 0.00 0.00 0.00 0.00 0.00 0.00
June 34698.81 19-JUN-05:04 3176.32 1058.67 27241.88 0.00 0.00 0.00 0.00 0.00 0.00
July 33663.56 24-JUL-05:12 3176.32 1938.17 27241.88 0.00 0.00 0.00 0.00 0.00 0.00
August 34268.65 07-AUG-05:12 3176.32 1938.17 27241.88 0.00 0.00 0.00 0.00 0.00 0.00
September 34980.62 05-SEP-05:14 3176.32 1938.17 27241.88 0.00 0.00 0.00 0.00 0.00 0.00
October 31154.17 16-OCT-06:01 10164.22 9303.20 59106.79 0.00 0.00 0.00 0.00 0.00 0.00
November 15574.27 03-NOV-16:00 6035.01 3488.70 11182.33 0.00 0.00 0.00 0.00 0.00 0.00
December 10017.40 21-DEC-16:10 6035.01 3488.70 11182.33 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 7452.32   2541.06 1058.67 11182.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 34980.62   60350.08 34887.01 112065.54 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 130.60 17-JAN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52.09
February 556.15 11-FEB-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 180.97
March 2734.08 28-MAR-13:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 169.48
April 6906.61 07-APR-13:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.29 0.00
May 10210.20 30-MAY-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.14 0.00
June 11152.89 19-JUN-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 66.00 0.00
July 10447.91 10-JUL-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.92 0.00
August 9977.94 01-AUG-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53.90 0.00
September 8725.45 01-SEP-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.76 0.00
October 6191.17 04-OCT-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.26
November 2250.29 03-NOV-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.12
December 851.54 17-DEC-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 332.29
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 130.60   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11152.89   0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.92 332.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2133.12 05-JAN-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 900.94
February 1960.48 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 242.76
March 2127.06 24-MAR-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 138.89
April 2285.40 10-APR-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64.12
May 4865.68 30-MAY-10:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.70 0.00
June 4811.07 26-JUN-10:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.59 0.00
July 4995.60 10-JUL-12:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.83 0.00
August 5254.38 14-AUG-10:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.93 0.00
September 5238.19 05-SEP-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.37
October 2938.79 04-OCT-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.63
November 1712.15 15-NOV-07:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 161.16
December 1569.02 23-DEC-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 252.16
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1569.02   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5254.38   0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.83 900.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1891.80 31-JAN-07:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 282.98
February 2235.66 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 147.58
March 2772.36 16-MAR-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 133.88
April 2835.51 21-APR-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 205.79
May 4817.82 30-MAY-12:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.65 0.00
June 5507.24 19-JUN-12:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62.34 0.00
July 5158.61 10-JUL-12:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34.43 0.00
August 5038.60 14-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.18
September 5517.57 05-SEP-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.83
October 3401.68 16-OCT-06:06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64.67
November 1806.38 30-NOV-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 100.81
December 2172.89 20-DEC-07:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.47
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1806.38   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5517.57   0.00 0.00 0.00 0.00 0.00 0.00 0.00 62.34 282.98



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6245.75 31-JAN-08:20 60350.08 34887.01 68083.20 0.00 0.00 0.00 0.00 0.00 0.00
February 6022.10 24-FEB-17:00 6035.01 3488.70 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 9223.34 29-MAR-16:00 6035.01 3488.70 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 13268.53 10-APR-16:00 6035.01 3488.70 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 28019.88 30-MAY-05:12 2541.06 1550.53 12103.68 0.00 0.00 0.00 0.00 0.00 0.00
June 31215.93 19-JUN-05:04 3176.32 1058.67 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
July 31257.66 24-JUL-05:14 3176.32 1938.17 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
August 31439.55 14-AUG-05:14 3176.32 1938.17 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
September 31488.08 05-SEP-05:14 3176.32 1938.17 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
October 21086.86 16-OCT-06:01 10164.22 9303.20 24207.36 0.00 0.00 0.00 0.00 0.00 0.00
November 10816.55 03-NOV-16:00 6035.01 3488.70 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 6234.52 21-DEC-16:20 6035.01 3488.70 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6022.10   2541.06 1058.67 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31488.08   60350.08 34887.01 68083.20 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5866.10 14-JAN-17:02 1588.16 968.95 11347.20 0.00 0.00 0.00 0.00 0.00 0.00
February 5815.12 24-FEB-16:50 6035.01 3488.70 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 9200.97 29-MAR-16:00 6035.01 3488.70 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 14261.73 10-APR-15:40 6035.01 3488.70 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 30336.75 30-MAY-05:12 2541.06 1550.53 12103.68 0.00 0.00 0.00 0.00 0.00 0.00
June 33704.74 19-JUN-05:04 3176.32 1058.67 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
July 30696.67 24-JUL-05:12 3176.32 1938.17 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
August 31503.09 07-AUG-05:12 3176.32 1938.17 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
September 30775.22 05-SEP-05:12 3176.32 1938.17 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
October 14825.76 04-OCT-15:00 6035.01 3488.70 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 9765.76 03-NOV-16:00 6035.01 3488.70 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 5769.66 21-DEC-16:25 12070.02 6977.40 13616.64 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5769.66   1588.16 968.95 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 33704.74   12070.02 6977.40 15129.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1194.52 14-JAN-17:02 334.80 204.26 2392.08 0.00 0.00 0.00 0.00 0.00 337.04
February 1022.46 24-FEB-15:40 1272.23 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 139.98
March 1851.38 28-MAR-14:00 1306.65 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 83.85
April 3942.99 07-APR-14:20 1272.23 350.81 1435.25 0.00 0.00 0.00 0.00 13.51 0.00
May 8772.26 30-MAY-06:03 803.52 350.81 1913.66 0.00 0.00 0.00 0.00 0.00 8.76
June 9144.88 26-JUN-05:12 669.60 194.89 3189.44 0.00 0.00 0.00 0.00 0.00 20.62
July 9516.29 10-JUL-04:02 0.00 408.58 2574.02 0.00 0.00 0.00 0.00 7.66 0.00
August 10355.80 13-AUG-15:52 401.76 116.92 2870.49 0.00 0.00 0.00 0.00 52.95 0.00
September 7217.27 05-SEP-06:03 1071.35 518.34 2551.55 0.00 0.00 0.00 0.00 0.00 9.91
October 4063.61 04-OCT-13:40 1306.65 350.81 1435.25 0.00 0.00 0.00 0.00 2.53 0.00
November 1658.36 03-NOV-14:00 1306.65 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 13.84
December 1016.24 20-DEC-14:00 1272.23 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 66.27
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1016.24   0.00 116.92 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10355.80   1306.65 518.34 3189.44 0.00 0.00 0.00 0.00 52.95 337.04



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 925.86 31-JAN-09:10 805.43 222.09 908.57 0.00 0.00 0.00 0.00 0.00 176.68
February 931.99 09-FEB-09:10 805.43 222.09 908.57 0.00 0.00 0.00 0.00 0.00 135.46
March 3770.26 29-MAR-09:30 827.22 222.09 908.57 0.00 0.00 0.00 0.00 0.00 54.51
April 6235.23 28-APR-08:40 805.43 222.09 908.57 0.00 0.00 0.00 0.00 0.00 31.04
May 12814.68 29-MAY-08:42 211.95 61.68 1514.29 0.00 0.00 0.00 0.00 0.00 15.54
June 12941.25 04-JUN-09:02 211.95 61.68 1514.29 0.00 0.00 0.00 0.00 0.00 32.60
July 12865.58 02-JUL-08:32 211.95 61.68 1514.29 0.00 0.00 0.00 0.00 0.00 18.24
August 12335.75 13-AUG-09:12 211.95 61.68 1514.29 0.00 0.00 0.00 0.00 15.82 0.00
September 12716.46 04-SEP-08:32 211.95 61.68 1514.29 0.00 0.00 0.00 0.00 0.00 17.08
October 5448.66 05-OCT-09:10 1654.44 444.18 1817.15 0.00 0.00 0.00 0.00 0.00 15.99
November 2205.39 03-NOV-09:30 827.22 222.09 908.57 0.00 0.00 0.00 0.00 0.00 30.35
December 815.77 20-DEC-10:00 805.43 222.09 908.57 0.00 0.00 0.00 0.00 0.00 23.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 815.77   211.95 61.68 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12941.25   1654.44 444.18 1817.15 0.00 0.00 0.00 0.00 15.82 176.68



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5849.28 19-JAN-13:25 2544.47 701.62 2870.47 0.00 0.00 0.00 0.00 0.00 138.40
February 6309.15 02-FEB-13:50 2544.47 701.62 2870.47 0.00 0.00 0.00 0.00 0.00 114.70
March 8861.41 29-MAR-13:10 2613.31 701.62 2870.47 0.00 0.00 0.00 0.00 0.00 112.98
April 9775.44 07-APR-12:30 1272.23 350.81 1435.24 0.00 0.00 0.00 0.00 13.27 0.00
May 12314.76 29-MAY-12:43 267.84 77.95 1913.65 0.00 0.00 0.00 0.00 15.77 0.00
June 11787.98 19-JUN-05:02 669.60 223.18 3189.42 0.00 0.00 0.00 0.00 0.00 4.65
July 15628.66 30-JUL-11:32 267.84 77.95 1913.65 0.00 0.00 0.00 0.00 0.00 26.70
August 15551.72 13-AUG-12:32 334.80 97.43 2392.06 0.00 0.00 0.00 0.00 62.85 0.00
September 15973.09 04-SEP-12:32 334.80 97.43 2392.06 0.00 0.00 0.00 0.00 0.00 23.17
October 15735.04 22-OCT-12:02 267.84 77.95 1913.65 0.00 0.00 0.00 0.00 0.00 74.45
November 10632.39 02-NOV-13:00 1272.23 350.81 1435.24 0.00 0.00 0.00 0.00 0.00 55.64
December 6174.65 21-DEC-13:25 2544.47 701.62 2870.47 0.00 0.00 0.00 0.00 0.00 120.95
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5849.28   267.84 77.95 1435.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15973.09   2613.31 701.62 3189.42 0.00 0.00 0.00 0.00 62.85 138.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1285.51 20-JAN-15:30 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 46.45
February 2172.22 24-FEB-15:30 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 107.22
March 5510.59 29-MAR-15:50 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 78.14
April 8924.99 09-APR-16:23 169.55 49.34 1211.42 0.00 0.00 0.00 0.00 0.00 96.18
May 11625.35 14-MAY-15:13 169.55 49.34 1211.42 0.00 0.00 0.00 0.00 0.00 202.28
June 13879.53 18-JUN-15:52 211.94 61.68 1514.28 0.00 0.00 0.00 0.00 0.00 30.62
July 14076.89 02-JUL-16:32 254.33 74.02 1817.13 0.00 0.00 0.00 0.00 0.00 61.13
August 13743.86 13-AUG-15:52 254.33 74.02 1817.13 0.00 0.00 0.00 0.00 27.02 0.00
September 13669.23 10-SEP-15:52 211.94 61.68 1514.28 0.00 0.00 0.00 0.00 0.00 61.49
October 11472.58 15-OCT-15:13 169.55 49.34 1211.42 0.00 0.00 0.00 0.00 0.00 157.52
November 3631.72 03-NOV-15:30 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 17.42
December 1116.14 08-DEC-15:30 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 79.84
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1116.14   169.55 49.34 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14076.89   805.38 222.08 1817.13 0.00 0.00 0.00 0.00 27.02 202.28



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1018.61 14-JAN-17:02 334.80 204.26 2392.08 0.00 0.00 0.00 0.00 0.00 179.61
February 965.51 24-FEB-14:10 1306.65 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 68.14
March 1258.50 28-MAR-14:00 1306.65 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 41.28
April 2148.04 10-APR-14:00 1306.65 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 14.35
May 4303.24 30-MAY-13:10 2613.31 701.62 2870.49 0.00 0.00 0.00 0.00 16.27 0.00
June 7137.73 26-JUN-06:03 803.52 350.81 1913.66 0.00 0.00 0.00 0.00 0.00 4.67
July 7151.27 17-JUL-06:03 803.52 350.81 1913.66 0.00 0.00 0.00 0.00 0.00 3.57
August 6976.50 14-AUG-06:03 803.52 350.81 1913.66 0.00 0.00 0.00 0.00 0.00 1.15
September 6330.68 05-SEP-06:03 1071.35 514.38 2551.55 0.00 0.00 0.00 0.00 0.00 5.39
October 3623.17 05-OCT-14:00 1306.65 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 1.99
November 1691.20 06-NOV-13:07 3816.70 1052.43 4305.74 0.00 0.00 0.00 0.00 0.00 31.91
December 1047.74 20-DEC-13:50 1272.23 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 34.12
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 965.51   334.80 204.26 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7151.27   3816.70 1052.43 4305.74 0.00 0.00 0.00 0.00 16.27 179.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 821.12 31-JAN-08:40 1610.86 444.18 1817.15 0.00 0.00 0.00 0.00 0.00 97.99
February 797.38 09-FEB-08:50 1610.86 444.18 1817.15 0.00 0.00 0.00 0.00 0.00 67.10
March 2321.59 29-MAR-09:30 827.22 222.09 908.57 0.00 0.00 0.00 0.00 0.00 28.90
April 4113.59 28-APR-09:10 1654.44 444.18 1817.15 0.00 0.00 0.00 0.00 0.00 12.64
May 8101.08 28-MAY-10:02 169.56 49.35 1211.43 0.00 0.00 0.00 0.00 0.00 23.28
June 10380.41 04-JUN-09:42 211.95 61.68 1514.29 0.00 0.00 0.00 0.00 0.00 10.75
July 9316.87 09-JUL-09:32 211.95 61.68 1514.29 0.00 0.00 0.00 0.00 12.89 0.00
August 8942.47 20-AUG-10:32 169.56 49.35 1211.43 0.00 0.00 0.00 0.00 0.00 9.46
September 10507.60 03-SEP-08:52 211.95 61.68 1514.29 0.00 0.00 0.00 0.00 0.00 16.37
October 4882.50 05-OCT-09:10 1654.44 444.18 1817.15 0.00 0.00 0.00 0.00 0.00 8.42
November 2449.23 03-NOV-09:30 827.22 222.09 908.57 0.00 0.00 0.00 0.00 0.00 16.06
December 842.84 20-DEC-09:50 805.43 222.09 908.57 0.00 0.00 0.00 0.00 0.00 12.79
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 797.38   169.56 49.35 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10507.60   1654.44 444.18 1817.15 0.00 0.00 0.00 0.00 12.89 97.99



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1348.78 19-JAN-14:30 1306.65 350.81 1435.24 0.00 0.00 0.00 0.00 0.00 1714.57
February 2311.07 25-FEB-13:10 267.84 116.93 1116.30 0.00 0.00 0.00 0.00 0.00 79.74
March 4736.38 03-MAR-13:20 2544.47 701.62 2870.47 0.00 0.00 0.00 0.00 0.00 1089.44
April 6680.79 07-APR-12:00 687.71 350.81 1275.77 0.00 0.00 0.00 0.00 1296.09 0.00
May 10274.95 30-MAY-12:00 687.71 350.81 1275.77 0.00 0.00 0.00 0.00 4014.77 0.00
June 11814.80 19-JUN-12:00 687.71 350.81 1275.77 0.00 0.00 0.00 0.00 8297.85 0.00
July 11246.72 07-JUL-12:00 687.71 350.81 1275.77 0.00 0.00 0.00 0.00 6672.68 0.00
August 12364.87 13-AUG-12:32 334.80 97.43 2392.06 0.00 0.00 0.00 0.00 37.22 0.00
September 13138.12 03-SEP-12:12 401.76 116.92 2870.47 0.00 0.00 0.00 0.00 0.00 29.61
October 12769.15 22-OCT-12:53 267.84 77.95 1913.65 0.00 0.00 0.00 0.00 0.00 0.00
November 9801.25 06-NOV-13:07 3816.70 1052.43 4305.71 0.00 0.00 0.00 0.00 0.00 1254.03
December 4481.12 17-DEC-12:43 200.88 58.46 1435.24 0.00 0.00 0.00 0.00 0.00 124.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1348.78   200.88 58.46 1116.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13138.12   3816.70 1052.43 4305.71 0.00 0.00 0.00 0.00 8297.85 1714.57



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 856.47 20-JAN-16:00 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 20.01
February 1215.02 22-FEB-16:30 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 36.32
March 3354.51 27-MAR-16:50 254.33 123.38 504.76 0.00 0.00 0.00 0.00 0.00 5.48
April 5438.58 10-APR-16:00 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 15.09
May 7343.82 28-MAY-15:23 169.55 49.34 1211.42 0.00 0.00 0.00 0.00 0.00 9.84
June 10845.74 18-JUN-16:21 339.11 98.69 2422.85 0.00 0.00 0.00 0.00 0.00 17.87
July 10664.66 02-JUL-16:32 254.33 74.02 1817.13 0.00 0.00 0.00 0.00 0.00 25.57
August 10599.74 13-AUG-15:52 254.33 74.02 1817.13 0.00 0.00 0.00 0.00 17.59 0.00
September 10963.60 03-SEP-16:12 254.33 74.02 1817.13 0.00 0.00 0.00 0.00 0.00 14.42
October 8179.82 15-OCT-15:13 169.55 49.34 1211.42 0.00 0.00 0.00 0.00 0.00 82.20
November 3406.22 03-NOV-15:30 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 9.20
December 870.88 08-DEC-15:40 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 40.25
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 856.47   169.55 49.34 504.76 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10963.60   805.38 222.08 2422.85 0.00 0.00 0.00 0.00 17.59 82.20



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1032.54 20-JAN-15:00 1306.65 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 59.12
February 1062.29 24-FEB-15:40 1272.23 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 118.40
March 1797.08 28-MAR-14:00 1306.65 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 69.63
April 3532.21 10-APR-14:00 1306.65 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 22.64
May 7765.59 30-MAY-06:03 803.52 350.81 1913.66 0.00 0.00 0.00 0.00 0.00 7.57
June 7748.25 22-JUN-06:03 803.52 350.81 1913.66 0.00 0.00 0.00 0.00 0.00 4.37
July 8662.60 09-JUL-15:21 468.72 136.41 3348.91 0.00 0.00 0.00 0.00 7.92 0.00
August 7684.02 14-AUG-06:03 803.52 350.81 1913.66 0.00 0.00 0.00 0.00 0.00 1.84
September 7136.30 05-SEP-05:12 669.60 408.58 3189.44 0.00 0.00 0.00 0.00 0.00 10.20
October 3897.52 05-OCT-14:00 1306.65 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 3.24
November 1949.98 03-NOV-14:00 1306.65 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 11.47
December 1089.50 20-DEC-14:00 1272.23 350.81 1435.25 0.00 0.00 0.00 0.00 0.00 57.18
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1032.54   468.72 136.41 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8662.60   1306.65 408.58 3348.91 0.00 0.00 0.00 0.00 7.92 118.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 910.89 31-JAN-09:30 1610.86 444.18 1817.15 0.00 0.00 0.00 0.00 0.00 135.61
February 1529.62 22-FEB-11:05 1610.86 444.18 1817.15 0.00 0.00 0.00 0.00 0.00 79.33
March 5711.05 29-MAR-12:02 4832.57 1332.55 5451.44 0.00 0.00 0.00 0.00 0.00 66.14
April 6568.37 28-APR-10:05 1610.86 444.18 1817.15 0.00 0.00 0.00 0.00 0.00 14.50
May 13738.12 29-MAY-08:31 296.74 86.36 2120.00 0.00 0.00 0.00 0.00 0.00 27.04
June 12314.62 25-JUN-08:42 211.95 61.68 1514.29 0.00 0.00 0.00 0.00 0.00 15.43
July 13818.87 02-JUL-08:21 296.74 86.36 2120.00 0.00 0.00 0.00 0.00 0.00 26.13
August 11873.59 13-AUG-09:12 211.95 61.68 1514.29 0.00 0.00 0.00 0.00 13.60 0.00
September 12825.67 03-SEP-08:52 211.95 61.68 1514.29 0.00 0.00 0.00 0.00 0.00 28.99
October 6426.72 15-OCT-09:33 127.17 37.01 908.57 0.00 0.00 0.00 0.00 0.00 132.08
November 5375.55 01-NOV-12:02 4832.57 1332.55 5451.44 0.00 0.00 0.00 0.00 0.00 63.51
December 1414.25 20-DEC-11:05 1610.86 444.18 1817.15 0.00 0.00 0.00 0.00 0.00 22.90
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 910.89   127.17 37.01 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13818.87   4832.57 1332.55 5451.44 0.00 0.00 0.00 0.00 13.60 135.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6066.17 19-JAN-13:25 2544.47 701.62 2870.47 0.00 0.00 0.00 0.00 0.00 115.01
February 6686.53 02-FEB-13:40 2544.47 701.62 2870.47 0.00 0.00 0.00 0.00 0.00 95.68
March 8911.13 29-MAR-12:50 1272.23 350.81 1435.24 0.00 0.00 0.00 0.00 0.00 93.93
April 9221.02 07-APR-12:30 1272.23 350.81 1435.24 0.00 0.00 0.00 0.00 11.16 0.00
May 13085.47 29-MAY-12:32 334.80 97.43 2392.06 0.00 0.00 0.00 0.00 21.26 0.00
June 10125.10 19-JUN-05:02 669.60 223.18 3189.42 0.00 0.00 0.00 0.00 0.00 4.24
July 14128.23 30-JUL-11:32 267.84 77.95 1913.65 0.00 0.00 0.00 0.00 0.00 20.18
August 14053.93 13-AUG-12:32 334.80 97.43 2392.06 0.00 0.00 0.00 0.00 54.37 0.00
September 15181.69 03-SEP-12:12 401.76 116.92 2870.47 0.00 0.00 0.00 0.00 0.00 52.81
October 14413.94 15-OCT-10:53 267.84 77.95 1913.65 0.00 0.00 0.00 0.00 0.00 216.40
November 11017.01 02-NOV-12:40 1272.23 350.81 1435.24 0.00 0.00 0.00 0.00 0.00 49.87
December 7149.16 21-DEC-13:03 7633.40 2104.85 8611.42 0.00 0.00 0.00 0.00 0.00 108.64
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6066.17   267.84 77.95 1435.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15181.69   7633.40 2104.85 8611.42 0.00 0.00 0.00 0.00 54.37 216.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1471.23 20-JAN-15:50 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 34.03
February 2460.72 24-FEB-15:30 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 89.11
March 5516.63 29-MAR-15:50 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 64.94
April 8626.26 09-APR-16:23 169.55 49.34 1211.42 0.00 0.00 0.00 0.00 0.00 79.74
May 12661.91 21-MAY-15:12 211.94 61.68 1514.28 0.00 0.00 0.00 0.00 0.00 98.51
June 12779.23 18-JUN-15:52 211.94 61.68 1514.28 0.00 0.00 0.00 0.00 0.00 24.30
July 13633.86 04-JUL-16:41 296.72 86.35 2119.99 0.00 0.00 0.00 0.00 0.00 38.11
August 12645.41 13-AUG-15:52 254.33 74.02 1817.13 0.00 0.00 0.00 0.00 23.89 0.00
September 13078.26 03-SEP-16:12 254.33 74.02 1817.13 0.00 0.00 0.00 0.00 0.00 25.26
October 11492.78 15-OCT-15:32 169.55 49.34 1211.42 0.00 0.00 0.00 0.00 0.00 124.47
November 3803.65 03-NOV-15:30 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 14.45
December 1390.70 08-DEC-15:30 805.38 222.08 908.57 0.00 0.00 0.00 0.00 0.00 66.37
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1390.70   169.55 49.34 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13633.86   805.38 222.08 2119.99 0.00 0.00 0.00 0.00 23.89 124.47



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.849167E+11 69838.68 02-JAN-16:00 0.969282E+11 234932.43 02-JAN-07:19
February 0.760848E+11 64822.63 06-FEB-16:00 0.822813E+11 221764.97 06-FEB-07:19
March 0.870078E+11 76224.99 27-MAR-15:00 0.398217E+11 138281.62 20-MAR-06:10
April 0.829657E+11 96721.46 07-APR-15:09 0.111441E+11 103496.38 03-APR-06:10
May 0.968760E+11 135858.78 30-MAY-14:09 0.695646E+09 30602.23 01-MAY-06:10
June 0.122458E+12 146275.93 19-JUN-10:30 3324180.28 630.91 02-JUN-06:10
July 0.137875E+12 138153.14 07-JUL-14:30 4075585.70 11.43 25-JUL-16:19
August 0.145510E+12 140989.70 16-AUG-15:09 4134211.24 12.19 18-AUG-10:30
September 0.108388E+12 122988.25 05-SEP-15:20 17752176.96 3958.53 20-SEP-06:10
October 0.961770E+11 103872.66 04-OCT-15:30 0.170264E+10 48456.12 31-OCT-06:10
November 0.822792E+11 70846.01 03-NOV-14:09 0.291559E+11 165174.75 24-NOV-07:10
December 0.828581E+11 69289.79 21-DEC-16:49 0.661786E+11 149052.70 11-DEC-07:10
             
Annual Sum or Average 0.120340E+13     0.327937E+12    
Minimum of Months 0.760848E+11 64822.63   3324180.28 11.43  
Maximum of Months 0.145510E+12 146275.93   0.969282E+11 234932.43  



Table of Contents

Report: EnergyConsumptionElectricityGeneratedPropaneMonthly

For: Meter

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ELECTRICITYPRODUCED:FACILITY [J] ELECTRICITYPRODUCED:FACILITY {Maximum} [W] ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} PROPANE:FACILITY [] PROPANE:FACILITY []
January 0.500277E+10 15147.85 31-JAN-11:50 0.00 0.00
February 0.725621E+10 17924.98 22-FEB-11:30 0.00 0.00
March 0.112953E+11 23381.33 29-MAR-11:00 0.00 0.00
April 0.130305E+11 24882.48 12-APR-11:00 0.00 0.00
May 0.163453E+11 25300.18 11-MAY-11:00 0.00 0.00
June 0.168503E+11 26130.14 02-JUN-11:50 0.00 0.00
July 0.166025E+11 24778.12 02-JUL-11:00 0.00 0.00
August 0.170136E+11 23350.57 10-AUG-11:30 0.00 0.00
September 0.117232E+11 21822.23 10-SEP-11:30 0.00 0.00
October 0.105735E+11 18881.58 08-OCT-11:30 0.00 0.00
November 0.595049E+10 14925.30 02-NOV-11:30 0.00 0.00
December 0.443260E+10 12241.86 02-DEC-12:30 0.00 0.00
           
Annual Sum or Average 0.136076E+12     0.00 0.00
Minimum of Months 0.443260E+10 12241.86   0.00 0.00
Maximum of Months 0.170136E+11 26130.14   0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY [J]
January 0.144215E+11 0.391471E+10 0.554480E+11 0.212634E+10 0.352345E+10 0.509949E+09 0.00 94540.61 0.00 0.00 0.00 0.497267E+10 0.00
February 0.128047E+11 0.313442E+10 0.502161E+11 0.192873E+10 0.300053E+10 0.444800E+09 0.00 19799.41 0.00 0.00 0.00 0.455555E+10 0.00
March 0.149660E+11 0.292145E+10 0.575730E+11 0.222306E+10 0.355281E+10 0.224111E+09 0.00 0.292031E+09 0.00 0.00 0.00 0.525539E+10 0.00
April 0.132272E+11 0.233720E+10 0.536187E+11 0.206170E+10 0.438695E+10 69619945.39 0.00 0.274894E+10 0.00 0.00 0.00 0.451541E+10 0.00
May 0.141867E+11 0.209590E+10 0.565105E+11 0.217421E+10 0.725319E+10 18167739.33 0.00 0.101156E+11 0.00 0.00 0.00 0.452185E+10 0.00
June 0.140614E+11 0.189025E+10 0.554637E+11 0.214012E+10 0.118606E+11 12256868.36 0.00 0.328471E+11 0.00 0.00 0.00 0.418249E+10 0.00
July 0.131921E+11 0.200552E+10 0.546543E+11 0.209503E+10 0.148325E+11 12284655.25 0.00 0.473147E+11 0.00 0.00 0.00 0.376805E+10 0.00
August 0.147348E+11 0.225197E+10 0.575730E+11 0.222278E+10 0.163450E+11 12702464.07 0.00 0.482794E+11 0.00 0.00 0.00 0.409049E+10 0.00
September 0.132913E+11 0.259477E+10 0.535964E+11 0.206061E+10 0.955467E+10 12066933.52 0.00 0.234731E+11 0.00 0.00 0.00 0.380557E+10 0.00
October 0.139483E+11 0.324232E+10 0.554592E+11 0.212659E+10 0.701542E+10 21751267.60 0.00 0.101939E+11 0.00 0.00 0.00 0.416962E+10 0.00
November 0.141451E+11 0.364237E+10 0.541547E+11 0.207545E+10 0.340581E+10 0.162088E+09 0.00 0.295861E+09 0.00 0.00 0.00 0.439779E+10 0.00
December 0.140208E+11 0.403634E+10 0.546432E+11 0.209513E+10 0.306823E+10 0.350691E+09 0.00 23489.90 0.00 0.00 0.00 0.464373E+10 0.00
                           
Annual Sum or Average 0.167000E+12 0.340672E+11 0.658911E+12 0.253297E+11 0.877992E+11 0.185049E+10 0.00 0.175561E+12 0.00 0.00 0.00 0.528786E+11 0.00
Minimum of Months 0.128047E+11 0.189025E+10 0.502161E+11 0.192873E+10 0.300053E+10 12066933.52 0.00 19799.41 0.00 0.00 0.00 0.376805E+10 0.00
Maximum of Months 0.149660E+11 0.403634E+10 0.575730E+11 0.222306E+10 0.163450E+11 0.509949E+09 0.00 0.482794E+11 0.00 0.00 0.00 0.525539E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.969282E+11 0.00 0.00 0.00 0.00
February 0.00 0.00 0.822813E+11 0.00 0.00 0.00 0.00
March 0.00 0.00 0.398217E+11 0.00 0.00 0.00 0.00
April 0.00 0.00 0.111441E+11 0.00 0.00 0.00 0.00
May 0.00 0.00 0.695646E+09 0.00 0.00 0.00 0.00
June 0.00 0.00 3324180.28 0.00 0.00 0.00 0.00
July 0.00 0.00 4075585.70 0.00 0.00 0.00 0.00
August 0.00 0.00 4134211.24 0.00 0.00 0.00 0.00
September 0.00 0.00 17752176.96 0.00 0.00 0.00 0.00
October 0.00 0.00 0.170264E+10 0.00 0.00 0.00 0.00
November 0.00 0.00 0.291559E+11 0.00 0.00 0.00 0.00
December 0.00 0.00 0.661786E+11 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.327937E+12 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 3324180.28 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.969282E+11 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 17672.30 02-JAN-16:40 3824.74 01-JAN-06:10 38886.07 02-JAN-08:09 1410.29 09-JAN-08:20 6680.66 02-JAN-07:10 766.86 02-JAN-07:10 0.00 01-JAN-00:10
February 16969.69 15-FEB-16:00 3824.74 01-FEB-06:10 38886.07 01-FEB-08:09 1410.29 02-FEB-12:09 5929.94 06-FEB-07:10 728.54 06-FEB-07:10 0.00 01-FEB-00:10
March 15082.41 02-MAR-16:00 3824.74 01-MAR-06:10 38886.07 01-MAR-08:09 1410.29 01-MAR-08:09 5433.18 29-MAR-15:20 593.10 20-MAR-06:10 0.00 01-MAR-00:10
April 14229.36 21-APR-07:10 3824.74 01-APR-05:10 38886.07 03-APR-07:10 1410.29 03-APR-11:09 13460.40 10-APR-14:30 491.01 03-APR-06:10 0.00 01-APR-00:10
May 14264.07 08-MAY-07:10 2323.70 01-MAY-18:49 38886.07 01-MAY-07:10 1410.29 03-MAY-11:09 26290.20 30-MAY-14:30 188.44 01-MAY-06:10 0.00 01-MAY-00:10
June 14175.33 29-JUN-07:10 2323.70 01-JUN-19:19 38886.07 01-JUN-07:10 1410.29 19-JUN-12:09 24929.21 19-JUN-10:30 11.84 02-JUN-06:10 0.00 01-JUN-00:10
July 14158.58 24-JUL-07:10 2323.70 01-JUL-19:30 38886.07 03-JUL-07:10 1410.29 07-JUL-11:09 25734.78 17-JUL-14:30 6.93 03-JUL-12:20 0.00 01-JUL-00:10
August 14341.69 16-AUG-07:10 3824.74 16-AUG-05:10 38886.07 01-AUG-07:10 1410.29 01-AUG-12:09 24899.63 14-AUG-14:50 6.93 18-AUG-10:30 0.00 01-AUG-00:10
September 14756.22 27-SEP-07:10 3824.74 01-SEP-05:10 38886.07 01-SEP-07:10 1410.29 11-SEP-07:10 21444.21 05-SEP-15:30 30.13 20-SEP-06:10 0.00 01-SEP-00:10
October 16041.13 31-OCT-15:00 3824.74 01-OCT-05:10 38886.07 02-OCT-07:10 1410.29 06-OCT-12:09 15263.14 04-OCT-15:50 241.89 31-OCT-06:10 0.00 01-OCT-00:10
November 17672.30 06-NOV-16:49 3824.74 01-NOV-05:10 38886.07 01-NOV-07:10 1410.29 01-NOV-12:09 7137.78 03-NOV-14:09 631.18 24-NOV-07:19 0.00 01-NOV-00:10
December 17672.30 01-DEC-16:30 3824.74 01-DEC-06:10 38886.07 01-DEC-08:09 1410.29 01-DEC-12:09 4365.78 11-DEC-07:10 604.36 11-DEC-07:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 14158.58   2323.70   38886.07   1410.29   4365.78   6.93   0.00  
Maximum of Months 17672.30   3824.74   38886.07   1410.29   26290.20   766.86   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY {Maximum} [W] COGENERATION:ELECTRICITY {TIMESTAMP}
January 51.53 30-JAN-05:30 0.00 0.00 0.00 6685.58 31-JAN-12:50 0.00 01-JAN-00:10
February 26.60 05-FEB-09:30 0.00 0.00 0.00 6688.84 06-FEB-12:39 0.00 01-FEB-00:10
March 13309.38 27-MAR-15:00 0.00 0.00 0.00 6670.06 03-MAR-12:50 0.00 01-MAR-00:10
April 26749.34 07-APR-14:30 0.00 0.00 0.00 6265.15 03-APR-11:39 0.00 01-APR-00:10
May 53463.35 30-MAY-14:09 0.00 0.00 0.00 6011.33 01-MAY-11:30 0.00 01-MAY-00:10
June 67361.36 19-JUN-12:09 0.00 0.00 0.00 5527.79 02-JUN-11:20 0.00 01-JUN-00:10
July 58403.95 07-JUL-14:09 0.00 0.00 0.00 5239.06 03-JUL-11:39 0.00 01-JUL-00:10
August 62428.05 04-AUG-14:09 0.00 0.00 0.00 5003.79 31-AUG-11:20 0.00 01-AUG-00:10
September 49510.78 07-SEP-14:09 0.00 0.00 0.00 5364.96 28-SEP-11:50 0.00 01-SEP-00:10
October 34910.57 04-OCT-14:09 0.00 0.00 0.00 5775.71 30-OCT-11:30 0.00 01-OCT-00:10
November 6259.46 03-NOV-14:09 0.00 0.00 0.00 6208.63 30-NOV-12:00 0.00 01-NOV-00:10
December 39.15 31-DEC-09:20 0.00 0.00 0.00 6499.23 27-DEC-12:50 0.00 01-DEC-00:10
                   
Annual Sum or Average     0.00 0.00 0.00        
Minimum of Months 26.60   0.00 0.00 0.00 5003.79   0.00  
Maximum of Months 67361.36   0.00 0.00 0.00 6688.84   0.00  



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 69838.68 02-JAN-16:00 17672.30 38861.85 3824.74 1410.29 2464.51 605.24 0.00 0.00 0.00
February 64822.63 06-FEB-16:00 16841.28 38861.85 0.00 1410.29 2136.36 548.14 0.00 0.00 0.00
March 76224.99 27-MAR-15:00 13903.46 38861.85 0.00 1410.29 4024.31 6.85 0.00 13309.38 0.00
April 96721.46 07-APR-15:09 13903.46 38861.85 0.00 1410.29 11819.13 6.85 0.00 26086.22 0.00
May 135858.78 30-MAY-14:09 13903.46 38852.37 0.00 1410.29 25014.65 6.85 0.00 53463.35 0.00
June 146275.93 19-JUN-10:30 13903.46 38858.69 0.00 1410.29 24929.21 6.90 0.00 62643.92 0.00
July 138153.14 07-JUL-14:30 13903.46 38852.37 0.00 1410.29 22763.46 6.92 0.00 58328.15 0.00
August 140989.70 16-AUG-15:09 13903.46 38861.85 0.00 1410.29 22435.29 6.90 0.00 60504.42 0.00
September 122988.25 05-SEP-15:20 13903.46 38861.85 0.00 1410.29 21019.28 6.91 0.00 43895.95 0.00
October 103872.66 04-OCT-15:30 13903.46 38861.85 0.00 1410.29 14029.25 6.90 0.00 31498.57 0.00
November 70846.01 03-NOV-14:09 13903.46 38852.37 0.00 1410.29 7137.78 6.85 0.00 6259.46 0.00
December 69289.79 21-DEC-16:49 17672.30 38861.85 3824.74 1410.29 2326.58 214.05 0.00 0.00 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 64822.63   13903.46 38852.37 0.00 1410.29 2136.36 6.85 0.00 0.00 0.00
Maximum of Months 146275.93   17672.30 38861.85 3824.74 1410.29 25014.65 605.24 0.00 62643.92 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 234932.43 02-JAN-07:19 0.00 0.00 0.00
February 0.00 0.00 221764.97 06-FEB-07:19 0.00 0.00 0.00
March 0.00 0.00 138281.62 20-MAR-06:10 0.00 0.00 0.00
April 0.00 0.00 103496.38 03-APR-06:10 0.00 0.00 0.00
May 0.00 0.00 30602.23 01-MAY-06:10 0.00 0.00 0.00
June 0.00 0.00 630.91 02-JUN-06:10 0.00 0.00 0.00
July 0.00 0.00 11.43 25-JUL-16:19 0.00 0.00 0.00
August 0.00 0.00 12.19 18-AUG-10:30 0.00 0.00 0.00
September 0.00 0.00 3958.53 20-SEP-06:10 0.00 0.00 0.00
October 0.00 0.00 48456.12 31-OCT-06:10 0.00 0.00 0.00
November 0.00 0.00 165174.75 24-NOV-07:10 0.00 0.00 0.00
December 0.00 0.00 149052.70 11-DEC-07:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 11.43   0.00 0.00 0.00
Maximum of Months 0.00 0.00 234932.43   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 8.33 19.85 8.33 19.85 0.00 19.85 0.00 19.85
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 8.33 19.85 8.33 19.85 0.00 19.85 0.00 19.85
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8.33 19.85 8.33 19.85 0.00 19.85 0.00 19.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.50 19.19 5.00 19.29 0.00 19.29 0.00 19.29
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 5.50 19.19 5.00 19.29 0.00 19.29 0.00 19.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.50 19.19 5.00 19.29 0.00 19.29 0.00 19.29



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.67 18.95 5.00 19.09 0.00 19.09 0.00 19.09
February 2.17 19.58 2.17 19.58 0.00 19.58 0.00 19.58
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.28 0.17 19.28 0.00 19.28 0.00 19.28
December 0.33 19.35 0.33 19.35 0.00 19.35 0.00 19.35
                 
Annual Sum or Average 8.33 19.14 7.67 19.24 0.00 19.24 0.00 19.24
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.67 19.58 5.00 19.58 0.00 19.58 0.00 19.58



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 22.83 16.92 13.50 17.37 0.00 17.37 0.00 17.37
February 16.33 17.92 10.17 18.46 0.00 18.46 0.00 18.46
March 0.33 19.43 0.33 19.43 0.00 19.43 0.00 19.43
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.33 27.34 0.33 27.34
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 2.83 27.36 2.67 27.36
August 0.00 0.00 0.00 0.00 1.50 27.44 1.33 27.45
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.33 18.83 1.00 19.09 0.00 19.09 0.00 19.09
December 2.67 17.77 1.67 18.34 0.00 18.34 0.00 18.34
                 
Annual Sum or Average 43.50 17.43 26.67 17.92 4.67 18.51 4.33 18.99
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22.83 19.43 13.50 19.43 2.83 27.44 2.67 27.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 14.33 16.03 5.17 16.47 0.00 16.47 0.00 16.47
February 7.50 16.95 2.83 17.61 0.00 17.61 0.00 17.61
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 7.00 27.81 7.00 27.81
June 0.00 0.00 0.00 0.00 5.33 27.62 5.33 27.62
July 0.00 0.00 0.00 0.00 12.67 27.77 12.33 27.78
August 0.00 0.00 0.00 0.00 7.00 27.75 6.67 27.76
September 0.00 0.00 0.00 0.00 5.67 27.85 5.67 27.85
October 0.00 0.00 0.00 0.00 0.33 27.29 0.33 27.29
November 0.50 18.55 0.33 18.89 0.00 18.89 0.00 18.89
December 1.17 16.43 0.33 17.03 0.00 17.03 0.00 17.03
                 
Annual Sum or Average 23.50 16.39 8.67 16.93 38.00 22.79 37.33 24.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14.33 18.55 5.17 18.89 12.67 27.85 12.33 27.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 13.00 16.48 5.50 16.97 0.00 16.97 0.00 16.97
February 6.67 17.69 3.50 18.28 0.00 18.28 0.00 18.28
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 27.36 0.17 27.36
May 0.00 0.00 0.00 0.00 4.00 27.65 4.00 27.65
June 0.00 0.00 0.00 0.00 3.67 27.49 3.67 27.49
July 0.00 0.00 0.00 0.00 9.00 27.68 8.67 27.69
August 0.00 0.00 0.00 0.00 5.50 27.92 5.17 27.93
September 0.00 0.00 0.00 0.00 6.17 28.12 6.00 28.13
October 0.00 0.00 0.00 0.00 4.33 27.67 4.33 27.67
November 0.50 18.63 0.33 18.94 0.00 18.94 0.00 18.94
December 0.50 19.21 0.50 19.21 0.00 19.21 0.00 19.21
                 
Annual Sum or Average 20.67 16.99 9.83 17.53 32.83 22.84 32.00 24.50
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13.00 19.21 5.50 19.21 9.00 28.12 8.67 28.13



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 14.83 16.04 6.33 16.43 0.00 16.43 0.00 16.43
February 8.67 17.41 4.50 18.06 0.00 18.06 0.00 18.06
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.67 27.62 1.33 27.65
May 0.00 0.00 0.00 0.00 6.00 27.76 4.17 27.82
June 0.00 0.00 0.00 0.00 5.83 28.00 3.67 28.07
July 0.00 0.00 0.00 0.00 9.83 28.02 6.50 28.07
August 0.00 0.00 0.00 0.00 4.50 28.07 3.33 28.11
September 0.00 0.00 0.00 0.00 3.83 28.27 3.00 28.28
October 0.00 0.00 0.00 0.00 0.67 27.75 0.67 27.75
November 0.50 17.85 0.17 18.24 0.00 18.24 0.00 18.24
December 1.33 16.28 0.50 16.70 0.00 16.70 0.00 16.70
                 
Annual Sum or Average 25.33 16.56 11.50 17.06 32.33 22.17 22.67 23.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14.83 17.85 6.33 18.24 9.83 28.27 6.50 28.28



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 21.83 18.29 16.67 18.71 0.00 18.71 0.00 18.71
February 6.83 19.48 6.17 19.61 0.00 19.61 0.00 19.61
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 28.67 18.57 22.83 18.94 0.00 18.94 0.00 18.94
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21.83 19.48 16.67 19.61 0.00 19.61 0.00 19.61



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.67 16.40 3.00 16.99 0.00 16.99 0.00 16.99
February 1.00 19.41 0.83 19.63 0.00 19.63 0.00 19.63
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 3.00 27.55 3.00 27.55
June 0.00 0.00 0.00 0.00 1.50 27.54 1.50 27.54
July 0.00 0.00 0.00 0.00 5.67 27.60 5.67 27.60
August 0.00 0.00 0.00 0.00 3.83 27.55 3.83 27.55
September 0.00 0.00 0.00 0.00 4.67 27.67 4.67 27.67
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 8.67 16.74 3.83 17.37 18.67 23.50 18.67 25.03
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7.67 19.41 3.00 19.63 5.67 27.67 5.67 27.67



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 85.50 17.80 84.50 17.81 0.00 17.81 0.00 17.81
February 68.83 17.53 68.83 17.53 0.00 17.53 0.00 17.53
March 51.83 18.56 51.83 18.56 0.00 18.56 0.00 18.56
April 21.67 19.27 21.67 19.27 0.00 19.27 0.00 19.27
May 2.50 20.08 2.50 20.08 0.50 20.74 0.50 21.29
June 0.00 0.00 0.00 0.00 1.17 25.58 1.17 25.58
July 0.00 0.00 0.00 0.00 6.33 25.97 6.33 25.97
August 0.00 0.00 0.00 0.00 13.33 25.62 13.33 25.62
September 0.00 0.00 0.00 0.00 11.00 26.41 10.67 26.40
October 3.17 20.20 3.17 20.20 5.67 23.67 5.67 24.91
November 32.67 19.01 32.67 19.01 0.00 19.01 0.00 19.01
December 56.83 18.31 56.83 18.31 0.17 18.32 0.17 18.33
                 
Annual Sum or Average 323.00 18.21 322.00 18.22 38.17 18.67 37.83 19.06
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.53 0.00 17.53
Maximum of Months 85.50 20.20 84.50 20.20 13.33 26.41 13.33 26.40



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 10.17 16.93 5.50 17.50 0.00 17.50 0.00 17.50
February 2.50 19.56 2.17 19.74 0.00 19.74 0.00 19.74
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 27.44 0.17 27.46
May 0.00 0.00 0.00 0.00 2.00 27.34 2.00 27.34
June 0.00 0.00 0.00 0.00 3.33 27.65 2.83 27.65
July 0.00 0.00 0.00 0.00 5.83 27.69 4.00 27.71
August 0.00 0.00 0.00 0.00 3.17 27.75 2.33 27.76
September 0.00 0.00 0.00 0.00 3.33 27.86 2.50 27.88
October 0.00 0.00 0.00 0.00 0.50 27.55 0.50 27.55
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 12.67 17.45 7.67 18.02 18.50 22.62 14.33 23.99
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10.17 19.56 5.50 19.74 5.83 27.86 4.00 27.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 13.83 17.17 8.50 17.66 0.00 17.66 0.00 17.66
February 5.67 18.97 4.67 19.23 0.00 19.23 0.00 19.23
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 27.27 0.50 27.27
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.32 0.17 19.32 0.00 19.32 0.00 19.32
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 19.67 17.71 13.33 18.17 0.50 18.30 0.50 18.44
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13.83 19.32 8.50 19.32 0.50 27.27 0.50 27.27



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 8.67 16.49 3.83 17.07 0.00 17.07 0.00 17.07
February 1.67 18.02 0.83 18.50 0.00 18.50 0.00 18.50
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 27.34 0.50 27.34
May 0.00 0.00 0.00 0.00 6.17 27.82 6.17 27.82
June 0.00 0.00 0.00 0.00 3.67 27.67 3.67 27.67
July 0.00 0.00 0.00 0.00 9.67 27.74 9.50 27.75
August 0.00 0.00 0.00 0.00 5.83 27.70 5.83 27.70
September 0.00 0.00 0.00 0.00 5.50 27.84 5.50 27.84
October 0.00 0.00 0.00 0.00 0.50 27.39 0.50 27.39
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 10.33 16.73 4.67 17.31 31.83 24.40 31.67 25.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8.67 18.02 3.83 18.50 9.67 27.84 9.50 27.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.83 16.52 3.33 17.13 0.00 17.13 0.00 17.13
February 1.67 18.62 1.17 19.00 0.00 19.00 0.00 19.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 27.31 0.17 27.31
May 0.00 0.00 0.00 0.00 2.83 27.55 2.83 27.55
June 0.00 0.00 0.00 0.00 2.17 27.38 2.17 27.38
July 0.00 0.00 0.00 0.00 6.50 27.58 6.50 27.58
August 0.00 0.00 0.00 0.00 4.83 27.80 4.67 27.81
September 0.00 0.00 0.00 0.00 7.50 27.46 7.50 27.46
October 0.00 0.00 0.00 0.00 5.50 27.70 5.50 27.70
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.83 27.33 0.83 27.33
                 
Annual Sum or Average 9.50 16.89 4.50 17.50 30.33 24.40 30.17 25.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7.83 18.62 3.33 19.00 7.50 27.80 7.50 27.81



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 10.33 16.87 5.67 17.45 0.00 17.45 0.00 17.45
February 3.17 18.75 2.17 19.21 0.00 19.21 0.00 19.21
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.33 27.65 1.00 27.69
May 0.00 0.00 0.00 0.00 5.00 27.66 4.00 27.69
June 0.00 0.00 0.00 0.00 5.00 27.90 3.17 27.96
July 0.00 0.00 0.00 0.00 7.83 27.96 5.17 28.02
August 0.00 0.00 0.00 0.00 3.83 27.95 2.83 28.00
September 0.00 0.00 0.00 0.00 3.83 28.09 3.00 28.12
October 0.00 0.00 0.00 0.00 0.67 27.69 0.67 27.69
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 13.50 17.31 7.83 17.89 27.50 23.52 19.83 24.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10.33 18.75 5.67 19.21 7.83 28.09 5.17 28.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 22.17 72.00 21.92 72.00 21.73
February 454.00 22.86 4.17 22.84 4.17 22.83
March 480.17 23.64 0.00 23.64 0.00 23.64
April 256.17 23.81 45.17 24.01 0.00 24.01
May 35.83 24.00 207.67 24.46 0.00 24.46
June 0.00 0.00 429.00 24.39 0.00 24.39
July 0.00 0.00 497.00 24.41 0.00 24.41
August 0.00 0.00 475.17 24.41 0.00 24.41
September 6.83 24.00 367.33 24.48 0.00 24.48
October 68.67 24.03 268.67 24.36 0.00 24.36
November 297.67 23.59 62.00 23.85 0.00 23.85
December 497.00 23.25 0.00 23.25 0.00 23.25
             
Annual Sum or Average 2598.33 23.17 2428.17 23.73 76.17 23.68
Minimum of Months 0.00 0.00 0.00 21.92 0.00 21.73
Maximum of Months 502.00 24.03 497.00 24.48 72.00 24.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.18 192.17 20.95 192.17 20.81
February 454.00 21.65 112.83 21.51 112.83 21.41
March 511.83 22.73 2.00 22.73 2.00 22.72
April 369.50 23.23 15.67 23.29 0.00 23.29
May 134.50 23.69 158.17 24.02 0.00 24.02
June 0.00 0.00 408.50 24.29 0.00 24.29
July 0.00 0.00 495.67 24.33 0.00 24.33
August 0.00 0.00 462.33 24.34 0.00 24.34
September 31.33 23.72 312.33 24.31 0.00 24.31
October 177.50 23.75 205.00 24.03 0.00 24.03
November 433.00 22.73 26.50 22.65 22.33 22.57
December 497.00 21.84 46.50 21.74 46.50 21.66
             
Annual Sum or Average 3110.67 22.35 2437.67 22.96 375.83 22.81
Minimum of Months 0.00 0.00 2.00 20.95 0.00 20.81
Maximum of Months 511.83 23.75 495.67 24.34 192.17 24.34



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.65 313.50 20.46 313.50 20.38
February 454.00 21.01 283.00 20.85 283.00 20.77
March 511.67 22.08 56.33 21.94 56.33 21.83
April 388.50 22.75 24.67 22.74 10.67 22.69
May 168.33 23.49 130.00 23.84 0.00 23.84
June 10.33 23.68 402.17 24.27 0.00 24.27
July 0.00 0.00 491.50 24.36 0.00 24.36
August 1.50 23.73 437.17 24.34 0.00 24.34
September 73.00 23.48 278.50 24.14 0.00 24.14
October 262.50 23.26 139.67 23.56 0.00 23.56
November 474.00 22.02 99.17 21.77 98.00 21.58
December 497.00 21.04 273.83 20.85 273.83 20.76
             
Annual Sum or Average 3342.83 21.83 2929.50 22.35 1035.33 22.08
Minimum of Months 0.00 0.00 24.67 20.46 0.00 20.38
Maximum of Months 511.67 23.73 491.50 24.36 313.50 24.36



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.02 433.67 19.94 433.67 19.92
February 454.00 20.22 409.33 20.17 409.33 20.15
March 510.83 21.17 216.33 20.93 216.33 20.79
April 405.33 22.04 83.83 21.94 58.50 21.77
May 207.00 23.17 136.83 23.65 5.17 23.66
June 33.17 24.75 414.50 24.36 17.17 24.41
July 49.17 26.09 495.83 24.64 49.17 24.76
August 32.67 25.54 448.50 24.47 24.00 24.55
September 126.50 23.31 261.50 23.97 5.83 23.99
October 322.50 22.50 131.83 22.73 28.50 22.61
November 489.00 21.15 203.00 20.85 203.00 20.68
December 497.00 20.25 454.67 20.21 454.67 20.20
             
Annual Sum or Average 3629.17 21.31 3689.83 21.80 1905.33 21.52
Minimum of Months 32.67 20.02 83.83 19.94 5.17 19.92
Maximum of Months 510.83 26.09 495.83 24.64 454.67 24.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.14 392.83 19.99 392.83 19.93
February 454.00 20.54 339.17 20.38 339.17 20.31
March 487.83 21.60 144.50 21.27 144.50 21.06
April 332.83 22.22 114.33 22.49 34.50 22.34
May 169.50 23.64 232.00 24.16 29.00 24.29
June 38.50 26.05 449.33 24.53 32.00 24.65
July 78.33 26.53 496.17 24.85 78.33 25.05
August 44.17 26.53 480.00 24.62 42.50 24.77
September 106.33 24.10 331.67 24.37 26.83 24.49
October 245.83 22.78 179.17 23.25 17.83 23.16
November 464.17 21.40 164.83 21.06 162.83 20.85
December 497.00 20.47 374.00 20.32 374.00 20.26
             
Annual Sum or Average 3420.50 21.60 3698.00 22.18 1674.33 21.93
Minimum of Months 38.50 20.14 114.33 19.99 17.83 19.93
Maximum of Months 502.00 26.53 496.17 24.85 392.83 25.05



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 487.33 20.63 314.00 20.28 314.00 20.13
February 424.17 21.10 268.17 20.80 263.00 20.64
March 420.33 21.54 164.83 21.39 135.50 21.19
April 333.33 22.11 118.50 22.35 44.33 22.18
May 196.67 23.28 198.83 23.87 15.33 23.95
June 44.83 25.02 420.83 24.41 25.33 24.50
July 65.83 26.32 494.50 24.73 65.83 24.90
August 46.00 26.11 464.50 24.59 38.67 24.73
September 103.17 24.17 340.00 24.37 27.83 24.52
October 189.00 22.93 262.17 23.70 23.33 23.69
November 399.50 21.59 161.67 21.40 129.17 21.16
December 460.00 21.00 300.67 20.74 292.50 20.58
             
Annual Sum or Average 3170.17 21.82 3508.67 22.43 1374.83 22.17
Minimum of Months 44.83 20.63 118.50 20.28 15.33 20.13
Maximum of Months 487.33 26.32 494.50 24.73 314.00 24.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.23 381.67 20.04 381.67 19.97
February 453.50 20.57 344.17 20.37 344.17 20.29
March 456.83 21.37 186.83 21.15 174.67 20.98
April 354.83 22.09 110.67 22.23 50.17 22.08
May 194.00 23.50 217.67 23.99 30.33 24.11
June 44.33 25.44 438.17 24.48 30.67 24.59
July 70.17 26.38 495.50 24.79 70.17 24.96
August 42.67 26.17 471.50 24.60 37.00 24.73
September 110.50 23.78 311.00 24.22 20.67 24.33
October 251.50 22.58 201.83 23.13 27.33 23.03
November 462.50 21.20 187.67 20.90 186.67 20.73
December 497.00 20.49 394.17 20.35 394.17 20.29
             
Annual Sum or Average 3439.83 21.52 3740.83 22.10 1747.67 21.84
Minimum of Months 42.67 20.23 110.67 20.04 20.67 19.97
Maximum of Months 502.00 26.38 495.50 24.79 394.17 24.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.28 434.00 20.22 434.00 20.20
February 454.00 20.47 419.17 20.44 419.17 20.43
March 514.00 21.09 230.33 20.94 230.33 20.87
April 466.83 22.06 34.50 21.97 33.00 21.87
May 345.00 23.18 71.50 23.35 12.83 23.36
June 25.17 24.13 376.00 24.23 6.33 24.24
July 19.17 25.68 496.83 24.43 19.17 24.48
August 15.67 26.06 457.83 24.40 14.83 24.45
September 81.33 23.57 291.17 24.12 0.50 24.12
October 263.67 23.18 142.17 23.49 0.00 23.49
November 483.67 21.88 113.83 21.63 113.50 21.46
December 497.00 20.69 399.50 20.63 399.50 20.61
             
Annual Sum or Average 3667.50 21.54 3466.83 22.00 1683.17 21.72
Minimum of Months 15.67 20.28 34.50 20.22 0.00 20.20
Maximum of Months 514.00 26.06 496.83 24.43 434.00 24.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.43 381.17 20.31 381.17 20.26
February 454.00 20.80 324.67 20.67 324.67 20.62
March 510.50 21.76 100.50 21.54 100.50 21.39
April 361.50 22.45 52.17 22.62 9.83 22.57
May 208.33 23.31 173.50 23.92 20.50 23.95
June 12.33 25.94 445.33 24.41 9.83 24.46
July 46.33 26.47 497.00 24.72 46.33 24.86
August 29.67 26.65 499.17 24.59 29.67 24.69
September 51.17 24.77 381.17 24.51 18.17 24.60
October 153.33 23.53 236.17 23.98 0.67 23.99
November 420.00 22.13 76.67 21.95 69.17 21.78
December 497.00 21.03 255.50 20.85 255.50 20.75
             
Annual Sum or Average 3246.17 21.79 3423.00 22.46 1266.00 22.22
Minimum of Months 12.33 20.43 52.17 20.31 0.67 20.26
Maximum of Months 510.50 26.65 499.17 24.72 381.17 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 500.17 20.16 337.17 19.90 337.17 19.79
February 445.67 20.61 278.67 20.33 275.83 20.19
March 486.17 21.28 123.33 21.00 119.33 20.79
April 398.67 21.82 72.83 21.89 35.83 21.73
May 328.00 22.69 87.67 23.07 18.33 23.07
June 106.67 23.73 387.83 24.15 77.83 24.13
July 105.00 24.60 494.33 24.50 105.00 24.52
August 65.33 25.12 487.50 24.55 62.33 24.62
September 96.00 24.10 386.67 24.44 50.67 24.51
October 127.17 23.29 311.17 24.20 16.00 24.26
November 385.50 21.69 97.83 21.66 62.33 21.45
December 476.00 20.97 245.33 20.76 234.17 20.59
             
Annual Sum or Average 3520.33 21.63 3310.33 22.27 1394.83 22.04
Minimum of Months 65.33 20.16 72.83 19.90 16.00 19.79
Maximum of Months 500.17 25.12 494.33 24.55 337.17 24.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.46 376.50 20.33 376.50 20.28
February 454.00 20.79 339.50 20.65 339.50 20.59
March 496.50 21.70 122.00 21.52 118.33 21.38
April 383.50 22.36 58.67 22.48 19.33 22.40
May 227.67 23.26 165.17 23.77 17.33 23.78
June 22.67 25.79 446.83 24.46 17.33 24.53
July 40.83 26.51 495.83 24.69 40.83 24.82
August 24.67 26.62 497.33 24.57 24.67 24.67
September 53.17 24.40 358.17 24.43 13.50 24.50
October 153.33 23.49 247.83 23.99 0.67 23.99
November 448.00 22.00 93.00 21.79 89.83 21.62
December 497.00 20.97 303.67 20.81 303.67 20.74
             
Annual Sum or Average 3303.33 21.75 3504.50 22.40 1361.50 22.15
Minimum of Months 22.67 20.46 58.67 20.33 0.67 20.28
Maximum of Months 502.00 26.62 497.33 24.69 376.50 24.82



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.28 393.50 20.17 393.50 20.13
February 454.00 20.54 371.33 20.47 371.33 20.44
March 510.33 21.53 119.67 21.34 119.67 21.22
April 399.67 22.45 36.17 22.47 14.33 22.40
May 166.17 23.43 145.00 23.85 0.00 23.85
June 13.83 25.06 430.83 24.35 10.00 24.37
July 32.67 25.90 496.83 24.58 32.67 24.66
August 17.17 26.25 468.50 24.45 16.83 24.51
September 90.00 23.60 296.83 24.14 5.17 24.16
October 266.67 23.00 142.67 23.37 0.00 23.37
November 479.17 21.66 137.83 21.38 137.33 21.20
December 497.00 20.60 385.33 20.52 385.33 20.49
             
Annual Sum or Average 3428.67 21.55 3424.50 22.11 1486.17 21.83
Minimum of Months 13.83 20.28 36.17 20.17 0.00 20.13
Maximum of Months 510.33 26.25 496.83 24.58 393.50 24.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.29 310.00 20.11 310.00 20.04
February 385.00 20.85 252.67 20.64 252.67 20.54
March 410.67 21.86 74.83 21.65 73.33 21.49
April 282.33 22.58 70.33 22.93 7.67 22.89
May 119.83 23.92 196.83 24.37 17.83 24.51
June 24.83 26.32 388.50 24.59 22.83 24.70
July 69.33 26.55 422.00 24.96 69.33 25.15
August 38.33 26.69 411.00 24.73 38.33 24.88
September 71.33 24.60 291.50 24.57 24.50 24.71
October 188.33 23.24 163.33 23.75 3.67 23.78
November 376.17 21.75 101.17 21.49 96.33 21.28
December 422.00 20.82 258.83 20.61 258.83 20.52
             
Annual Sum or Average 2815.17 21.86 2941.00 22.48 1175.33 22.25
Minimum of Months 24.83 20.29 70.33 20.11 3.67 20.04
Maximum of Months 427.00 26.69 422.00 24.96 310.00 25.15



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 480.33 20.92 271.17 20.60 268.67 20.43
February 413.67 21.47 210.33 21.20 202.33 21.01
March 411.67 21.99 85.17 21.96 56.83 21.81
April 322.83 22.56 87.83 22.88 12.50 22.81
May 150.50 23.49 205.17 24.03 6.00 24.09
June 28.17 25.35 440.67 24.41 19.00 24.48
July 57.33 26.33 497.00 24.71 57.33 24.87
August 34.33 26.68 483.17 24.60 34.33 24.73
September 72.67 24.73 369.33 24.51 27.00 24.64
October 152.50 23.57 288.00 24.16 12.17 24.24
November 372.83 22.08 117.50 22.05 70.83 21.83
December 446.17 21.40 219.00 21.18 207.83 21.00
             
Annual Sum or Average 2943.00 22.13 3274.33 22.81 974.83 22.60
Minimum of Months 28.17 20.92 85.17 20.60 6.00 20.43
Maximum of Months 480.33 26.68 497.00 24.71 268.67 24.87



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.49 343.00 20.29 343.00 20.21
February 452.33 20.91 303.17 20.69 303.17 20.60
March 451.50 21.77 100.17 21.64 87.67 21.50
April 342.67 22.53 80.33 22.77 17.83 22.71
May 135.00 23.71 231.17 24.16 14.67 24.26
June 32.50 25.89 452.67 24.50 26.33 24.60
July 60.17 26.39 497.00 24.77 60.17 24.92
August 31.00 26.64 487.17 24.59 31.00 24.71
September 77.17 24.23 340.00 24.37 19.33 24.47
October 203.67 23.13 221.83 23.72 3.00 23.74
November 448.83 21.71 125.83 21.45 122.17 21.27
December 497.00 20.89 316.00 20.70 316.00 20.62
             
Annual Sum or Average 3233.83 21.79 3498.33 22.43 1344.33 22.20
Minimum of Months 31.00 20.49 80.33 20.29 3.00 20.21
Maximum of Months 502.00 26.64 497.00 24.77 343.00 24.92



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.17441 24.53883 -0.2900 8.81806
February 454.00000 22.85804 20.35710 -0.1415 5.93840
March 514.00000 23.68082 27.95102 0.12646 5.65695
April 485.00000 24.07105 33.23827 0.28584 7.04129
May 508.00000 24.28732 40.27702 -0.4553 9.70135
June 496.00000 24.35528 49.74430 -0.3263 7.62727
July 497.00000 24.40679 53.07102 -0.2749 6.98331
August 514.00000 24.37946 49.76131 -0.3005 7.40012
September 485.00000 24.38547 45.49457 -0.3510 8.04273
October 502.00000 24.34827 39.02287 0.43862 9.43678
November 489.00000 23.91886 30.41035 0.21595 6.79634
December 497.00000 23.25332 23.31732 -0.0225 5.31274
           
Annual Sum or Average 5943.00000 23.84956 36.55548 -0.0919 7.40922
Minimum of Months 454.00000 22.17441 20.35710 -0.4553 5.31274
Maximum of Months 514.00000 24.40679 53.07102 0.43862 9.70135



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.17918 25.81136 -0.5138 12.27719
February 454.00000 21.64778 21.57792 -0.4155 9.22230
March 514.00000 22.73825 29.78835 -0.0830 5.86895
April 485.00000 23.44775 35.00874 0.14638 6.28427
May 508.00000 24.05485 41.57448 -0.5344 11.43483
June 496.00000 24.25006 50.49249 -0.3692 8.15488
July 497.00000 24.32933 54.22746 -0.3033 7.23328
August 514.00000 24.30330 50.84318 -0.3327 7.70817
September 485.00000 24.22772 46.36911 -0.4178 9.09699
October 502.00000 24.03222 40.23973 0.35213 8.15421
November 489.00000 22.89387 32.79692 -0.0232 6.71864
December 497.00000 21.83872 25.15027 -0.3405 8.00583
           
Annual Sum or Average 5943.00000 23.25672 37.94707 -0.2358 8.34511
Minimum of Months 454.00000 21.17918 21.57792 -0.5344 5.86895
Maximum of Months 514.00000 24.32933 54.22746 0.35213 12.27719



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.64918 26.47386 -0.6618 16.34785
February 454.00000 21.00678 21.82601 -0.5932 13.44798
March 514.00000 22.09267 30.66634 -0.2425 7.49355
April 485.00000 23.01667 35.81028 0.04126 6.56037
May 508.00000 23.92638 41.92316 -0.5755 12.71086
June 496.00000 24.23542 50.16386 -0.3680 8.17963
July 497.00000 24.35388 53.52753 -0.2859 7.05239
August 514.00000 24.29947 50.38897 -0.3271 7.66247
September 485.00000 24.11152 46.20848 -0.4629 10.11862
October 502.00000 23.62776 41.15636 0.24868 7.42926
November 489.00000 22.08243 34.28366 -0.2289 8.40654
December 497.00000 21.04029 25.92997 -0.5529 12.41684
           
Annual Sum or Average 5943.00000 22.88430 38.31974 -0.3328 9.79677
Minimum of Months 454.00000 20.64918 21.82601 -0.6618 6.56037
Maximum of Months 514.00000 24.35388 53.52753 0.24868 16.34785



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.02060 28.08630 -0.8539 22.94291
February 454.00000 20.22348 22.79433 -0.8220 21.21793
March 514.00000 21.18548 32.76406 -0.4637 11.37774
April 485.00000 22.37374 37.56617 -0.1057 7.92809
May 508.00000 23.76437 42.82011 -0.6117 14.73131
June 496.00000 24.26492 51.36825 -0.3104 7.82752
July 497.00000 24.49606 55.38812 -0.1725 6.67110
August 514.00000 24.33797 51.65525 -0.2636 7.39606
September 485.00000 23.96092 48.02903 -0.4943 11.59499
October 502.00000 23.02682 43.29333 0.11232 7.70825
November 489.00000 21.14845 36.25799 -0.4608 12.27012
December 497.00000 20.25327 27.80021 -0.7757 19.25444
           
Annual Sum or Average 5943.00000 22.43856 39.94488 -0.4327 12.51713
Minimum of Months 454.00000 20.02060 22.79433 -0.8539 6.67110
Maximum of Months 514.00000 24.49606 55.38812 0.11232 22.94291



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.13612 28.94025 -0.8026 21.47774
February 454.00000 20.53973 23.49626 -0.7164 18.01724
March 514.00000 21.72608 32.59810 -0.3135 9.96277
April 485.00000 22.87902 36.43123 0.04086 8.32265
May 508.00000 24.00944 42.08815 -0.4670 12.45024
June 496.00000 24.35605 50.98302 -0.2234 7.39521
July 497.00000 24.58336 54.87321 -0.0803 6.88518
August 514.00000 24.41749 51.08367 -0.1490 6.83628
September 485.00000 24.18659 47.25515 -0.3612 9.99703
October 502.00000 23.45817 42.01633 0.24304 8.56593
November 489.00000 21.53101 36.33184 -0.3535 11.15678
December 497.00000 20.46659 28.50769 -0.7031 17.22661
           
Annual Sum or Average 5943.00000 22.70737 39.67067 -0.3213 11.47795
Minimum of Months 454.00000 20.13612 23.49626 -0.8026 6.83628
Maximum of Months 514.00000 24.58336 54.87321 0.24304 21.47774



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.73146 27.01333 -0.6404 18.53222
February 454.00000 21.32151 21.32779 -0.5115 14.97029
March 514.00000 22.00854 30.50774 -0.2296 9.83403
April 485.00000 22.79015 35.91527 0.02050 8.56318
May 508.00000 23.83041 42.34004 -0.5579 14.23801
June 496.00000 24.27443 51.18782 -0.2843 7.88435
July 497.00000 24.51956 55.10279 -0.1340 6.82159
August 514.00000 24.39373 51.00537 -0.1708 7.01521
September 485.00000 24.18881 46.71936 -0.3302 9.87016
October 502.00000 23.75426 40.27399 0.35743 10.49952
November 489.00000 22.04743 33.97244 -0.2100 10.17070
December 497.00000 21.27380 26.20013 -0.4948 14.44098
           
Annual Sum or Average 5943.00000 22.94023 38.59239 -0.2642 11.04756
Minimum of Months 454.00000 20.73146 21.32779 -0.6404 6.82159
Maximum of Months 514.00000 24.51956 55.10279 0.35743 18.53222



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.22641 28.77530 -0.7901 21.31041
February 454.00000 20.57827 23.25396 -0.7196 18.91551
March 514.00000 21.66938 32.22458 -0.3265 10.46610
April 485.00000 22.65724 37.13964 -0.0092 8.66411
May 508.00000 23.88875 42.69347 -0.5153 13.56150
June 496.00000 24.33073 51.12314 -0.2230 7.60770
July 497.00000 24.55928 55.16177 -0.0913 6.92583
August 514.00000 24.41362 51.30088 -0.1530 6.95802
September 485.00000 24.08978 47.68542 -0.3966 10.63516
October 502.00000 23.35204 42.40504 0.22239 8.88269
November 489.00000 21.35270 36.57148 -0.4012 11.72909
December 497.00000 20.49469 28.46644 -0.7053 17.57565
           
Annual Sum or Average 5943.00000 22.65097 39.85430 -0.3398 11.88560
Minimum of Months 454.00000 20.22641 23.25396 -0.7901 6.92583
Maximum of Months 514.00000 24.55928 55.16177 0.22239 21.31041



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.27885 27.95221 -0.7803 19.56414
February 454.00000 20.46741 22.95980 -0.7581 18.05381
March 514.00000 21.09268 33.27868 -0.4877 10.83785
April 485.00000 22.14104 38.80867 -0.1720 7.18513
May 508.00000 23.47730 44.24858 -0.7517 18.17426
June 496.00000 24.16947 51.97015 -0.3882 8.53192
July 497.00000 24.38555 55.06517 -0.2540 6.81180
August 514.00000 24.30527 51.28821 -0.3045 7.46569
September 485.00000 24.10648 47.76682 -0.4510 9.90383
October 502.00000 23.56426 42.20699 0.24148 7.31358
November 489.00000 21.90381 35.05426 -0.2553 8.44263
December 497.00000 20.68880 27.38077 -0.6340 13.94423
           
Annual Sum or Average 5943.00000 22.56327 39.95841 -0.4147 11.32320
Minimum of Months 454.00000 20.27885 22.95980 -0.7803 6.81180
Maximum of Months 514.00000 24.38555 55.06517 0.24148 19.56414



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.43489 28.81428 -0.7196 17.76030
February 454.00000 20.80182 23.73493 -0.6432 14.73724
March 514.00000 21.77496 33.23134 -0.3005 8.52466
April 485.00000 22.91752 37.14724 0.03617 7.27080
May 508.00000 23.92027 42.77247 -0.5448 13.49708
June 496.00000 24.33146 51.28158 -0.2745 7.43176
July 497.00000 24.55317 54.29658 -0.1331 6.52819
August 514.00000 24.44983 50.43496 -0.1616 6.51191
September 485.00000 24.35955 46.78074 -0.3026 8.28105
October 502.00000 24.00228 40.66359 0.37999 8.96989
November 489.00000 22.40884 34.73662 -0.1209 7.73641
December 497.00000 21.03375 28.02343 -0.5324 11.81348
           
Annual Sum or Average 5943.00000 22.93033 39.44581 -0.2746 9.89774
Minimum of Months 454.00000 20.43489 23.73493 -0.7196 6.51191
Maximum of Months 514.00000 24.55317 54.29658 0.37999 17.76030



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.17395 25.41565 -0.7186 18.88326
February 454.00000 20.70239 20.10083 -0.5957 15.59757
March 514.00000 21.43403 29.97264 -0.3316 9.75868
April 485.00000 22.27393 36.10579 -0.0934 7.96373
May 508.00000 23.26940 43.85049 -0.7667 20.01712
June 496.00000 24.14421 54.03718 -0.3524 8.50772
July 497.00000 24.47424 57.99126 -0.1697 6.40418
August 514.00000 24.43801 52.62909 -0.1635 6.55936
September 485.00000 24.31303 47.78376 -0.2684 8.41392
October 502.00000 24.11993 39.70208 0.47696 11.39647
November 489.00000 22.23589 31.72121 -0.1080 8.49417
December 497.00000 21.16629 24.17988 -0.4513 12.18496
           
Annual Sum or Average 5943.00000 22.74279 38.76625 -0.2940 11.17169
Minimum of Months 454.00000 20.17395 20.10083 -0.7667 6.40418
Maximum of Months 514.00000 24.47424 57.99126 0.47696 20.01712



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.46330 28.71265 -0.7190 17.89376
February 454.00000 20.79284 23.64266 -0.6545 15.44669
March 514.00000 21.78153 32.80154 -0.2994 8.72596
April 485.00000 22.75334 37.65481 -0.0031 7.31223
May 508.00000 23.84039 43.29598 -0.5826 14.14035
June 496.00000 24.35028 51.15187 -0.2584 7.31782
July 497.00000 24.54250 54.45135 -0.1374 6.52535
August 514.00000 24.45790 50.58824 -0.1605 6.49286
September 485.00000 24.29925 47.07497 -0.3269 8.46314
October 502.00000 24.00608 40.77274 0.38240 9.10730
November 489.00000 22.16905 35.21978 -0.1818 8.10684
December 497.00000 20.97147 28.04472 -0.5525 12.32046
           
Annual Sum or Average 5943.00000 22.88422 39.56931 -0.2892 10.12694
Minimum of Months 454.00000 20.46330 23.64266 -0.7190 6.49286
Maximum of Months 514.00000 24.54250 54.45135 0.38240 17.89376



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.27742 27.81286 -0.7620 19.28456
February 454.00000 20.54388 22.59801 -0.7121 16.91812
March 514.00000 21.54462 32.28881 -0.3569 9.04423
April 485.00000 22.73715 36.97192 -0.0123 6.88123
May 508.00000 23.91924 42.37979 -0.5626 12.68822
June 496.00000 24.28594 51.46138 -0.3096 7.53213
July 497.00000 24.49333 55.64517 -0.1853 6.59025
August 514.00000 24.35374 51.80429 -0.2667 7.21272
September 485.00000 24.09618 47.91841 -0.4458 10.04010
October 502.00000 23.45902 42.26040 0.21944 7.41312
November 489.00000 21.70305 35.27126 -0.3053 9.37349
December 497.00000 20.60411 27.35191 -0.6525 14.78835
           
Annual Sum or Average 5943.00000 22.68409 39.60675 -0.3607 10.60682
Minimum of Months 454.00000 20.27742 22.59801 -0.7620 6.59025
Maximum of Months 514.00000 24.49333 55.64517 0.21944 19.28456



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.29398 28.34412 -0.7400 19.03798
February 385.00000 20.84550 23.02838 -0.6187 14.80090
March 433.00000 21.97676 31.91688 -0.2381 8.37862
April 410.00000 23.14354 35.83086 0.10587 7.71359
May 430.00000 24.16278 41.43680 -0.4306 11.31526
June 418.00000 24.45612 50.56930 -0.2176 7.27977
July 422.00000 24.69376 54.76316 -0.0773 6.96720
August 433.00000 24.52181 51.04409 -0.1479 6.87186
September 410.00000 24.35223 47.00540 -0.3192 9.13433
October 427.00000 23.76321 40.83737 0.31095 8.58039
November 417.00000 21.98509 35.13429 -0.2265 8.95858
December 422.00000 20.81899 27.90956 -0.5873 13.59955
           
Annual Sum or Average 5034.00000 22.93045 39.09139 -0.2636 10.19585
Minimum of Months 385.00000 20.29398 23.02838 -0.7400 6.87186
Maximum of Months 433.00000 24.69376 54.76316 0.31095 19.03798



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.06753 26.56581 -0.5341 15.17387
February 454.00000 21.74517 20.93924 -0.3831 11.81455
March 514.00000 22.41442 29.85747 -0.1162 8.00585
April 485.00000 23.13827 35.27314 0.11015 7.72108
May 508.00000 23.99235 41.85104 -0.5075 12.12132
June 496.00000 24.31345 51.23104 -0.2790 7.48656
July 497.00000 24.52852 55.28040 -0.1439 6.67906
August 514.00000 24.42184 51.09624 -0.1714 6.76857
September 485.00000 24.31420 46.62323 -0.2856 8.61233
October 502.00000 24.06464 39.50831 0.44035 10.83965
November 489.00000 22.58803 32.84945 -0.0600 8.42819
December 497.00000 21.73206 25.51170 -0.3532 11.15241
           
Annual Sum or Average 5943.00000 23.20403 38.17829 -0.1895 9.55627
Minimum of Months 454.00000 21.06753 20.93924 -0.5341 6.67906
Maximum of Months 514.00000 24.52852 55.28040 0.44035 15.17387



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.49413 28.50700 -0.6964 17.84847
February 454.00000 20.92092 23.02427 -0.6063 14.95644
March 514.00000 22.05874 31.65700 -0.2154 8.41615
April 485.00000 23.02626 36.47282 0.08448 7.73786
May 508.00000 24.04890 42.18418 -0.4655 11.49698
June 496.00000 24.36640 51.16276 -0.2186 7.21235
July 497.00000 24.56968 55.35861 -0.1006 6.74841
August 514.00000 24.43742 51.43781 -0.1544 6.71768
September 485.00000 24.22094 47.55595 -0.3500 9.19859
October 502.00000 23.74500 41.43384 0.32136 8.82413
November 489.00000 21.90106 35.53023 -0.2481 9.05395
December 497.00000 20.88507 27.95028 -0.5758 13.38814
           
Annual Sum or Average 5943.00000 22.90480 39.47722 -0.2667 10.10026
Minimum of Months 454.00000 20.49413 23.02427 -0.6964 6.71768
Maximum of Months 514.00000 24.56968 55.35861 0.32136 17.84847



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.735199E+11 0.00 443.49 195683.51 02-JAN-07:10 0.00 36.86 50.52 0.34 0.00 0.10 0.69 02-JAN-07:10
February 0.617516E+11 0.00 386.72 184996.26 06-FEB-07:10 0.00 36.62 49.79 0.31 0.00 0.09 0.66 06-FEB-07:10
March 0.279272E+11 0.00 357.25 183162.08 24-MAR-06:01 0.00 31.64 44.64 0.10 0.00 0.04 0.65 24-MAR-06:01
April 0.761856E+10 0.00 190.36 169664.73 04-APR-06:02 0.00 33.94 41.52 0.03 0.00 0.01 0.60 04-APR-06:02
May 0.444618E+09 0.00 39.11 21619.04 01-MAY-06:05 0.00 42.64 43.60 0.00 0.00 0.00 0.08 01-MAY-06:05
June 2097156.43 0.00 84.68 1215.32 02-JUN-06:10 0.00 40.23 42.56 0.00 0.00 0.00 0.00 02-JUN-06:10
July 2572647.06 0.00 161.32 7.21 25-JUL-16:20 0.00 38.71 43.33 0.00 0.00 0.00 0.00 25-JUL-16:20
August 2612198.05 0.00 159.53 7.69 18-AUG-10:30 0.00 37.12 42.00 0.00 0.00 0.00 0.00 18-AUG-10:30
September 11416686.63 0.00 62.20 10847.19 20-SEP-06:07 0.00 35.58 37.65 0.00 0.00 0.00 0.04 20-SEP-06:07
October 0.118466E+10 0.00 76.94 77735.21 28-OCT-06:03 0.00 34.23 36.94 0.00 0.00 0.00 0.28 28-OCT-06:03
November 0.204163E+11 0.00 263.64 176340.25 28-NOV-07:02 0.00 32.40 42.50 0.08 0.00 0.03 0.63 28-NOV-07:02
December 0.467711E+11 0.00 390.35 176770.26 20-DEC-07:02 0.00 33.79 47.41 0.18 0.00 0.06 0.63 20-DEC-07:02
                           
Annual Sum or Average 0.239653E+12 0.00 2615.58     0.00 36.15 43.52 0.08 0.00 0.03    
Minimum of Months 2097156.43 0.00 39.11 7.21   0.00 31.64 36.94 0.00 0.00 0.00 0.00  
Maximum of Months 0.735199E+11 0.00 443.49 195683.51   0.00 42.64 50.52 0.34 0.00 0.10 0.69  



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00
March 0.390328E+09 90570102.54 15.89 0.263875E+09 0.126453E+09 0.00 0.70 27-MAR-16:00 0.00 01-MAR-00:10 20076.27 27-MAR-16:00 16323.35 27-MAR-16:00 6719.42 27-MAR-12:55 4371.78 27-MAR-16:00 0.00
April 0.355549E+10 0.808509E+09 94.54 0.316111E+10 0.394376E+09 0.00 1.00 07-APR-12:50 0.00 01-APR-00:10 36832.47 07-APR-14:30 36832.47 07-APR-14:30 7801.18 10-APR-06:03 7747.90 07-APR-14:20 0.00
May 0.142683E+11 0.319953E+10 286.88 0.120152E+11 0.225311E+10 0.00 1.00 30-MAY-06:03 0.00 01-MAY-00:10 73164.59 30-MAY-14:20 73164.59 30-MAY-14:20 20541.63 31-MAY-06:03 16714.82 30-MAY-14:10 0.00
June 0.507730E+11 0.108426E+11 424.09 0.386187E+11 0.121543E+11 0.00 1.00 01-JUN-06:03 0.00 01-JUN-00:10 96993.89 19-JUN-06:03 70705.89 19-JUN-05:02 44432.31 27-JUN-06:03 22481.32 19-JUN-12:03 0.00
July 0.736567E+11 0.158661E+11 439.02 0.533849E+11 0.202718E+11 0.00 1.00 01-JUL-06:03 0.00 01-JUL-00:10 101094.71 22-JUL-06:03 75260.68 10-JUL-06:03 45721.50 28-JUL-06:03 20588.44 22-JUL-06:03 0.00
August 0.757497E+11 0.165330E+11 450.64 0.593058E+11 0.164439E+11 0.00 1.00 01-AUG-04:03 0.00 01-AUG-00:10 99593.35 17-AUG-06:03 75071.65 22-AUG-15:50 39222.99 16-AUG-06:03 20903.50 16-AUG-12:30 0.00
September 0.392336E+11 0.831336E+10 388.58 0.312979E+11 0.793577E+10 0.00 1.00 01-SEP-05:03 0.00 01-SEP-00:10 98858.46 07-SEP-06:03 72672.50 05-SEP-05:12 38650.90 08-SEP-06:03 20164.18 01-SEP-06:03 0.00
October 0.177031E+11 0.374499E+10 240.04 0.124441E+11 0.525892E+10 0.00 1.00 02-OCT-12:30 0.00 01-OCT-00:10 58936.03 04-OCT-15:20 45920.49 04-OCT-15:00 30192.08 06-OCT-06:03 11922.27 25-OCT-10:30 0.00
November 0.517289E+09 0.126955E+09 33.68 0.448438E+09 68850318.51 0.00 0.45 06-NOV-12:00 0.00 01-NOV-00:10 12162.18 06-NOV-12:00 12162.18 06-NOV-12:00 3530.01 10-NOV-10:00 2827.35 06-NOV-12:00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.275848E+12 0.595256E+11 2373.36 0.210940E+12 0.649076E+11 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.757497E+11 0.165330E+11 450.64 0.593058E+11 0.202718E+11 0.00 1.00   0.00   101094.71   75260.68   45721.50   22481.32   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00
March 0.387773E+09 89249778.05 14.08 0.265031E+09 0.122742E+09 0.00 0.70 27-MAR-16:00 0.00 01-MAR-00:10 19829.96 27-MAR-16:00 16335.04 27-MAR-16:00 6849.69 27-MAR-12:55 4314.74 27-MAR-16:00 0.00
April 0.415834E+10 0.939818E+09 103.70 0.376140E+10 0.396949E+09 0.00 1.00 07-APR-12:05 0.00 01-APR-00:10 44142.60 07-APR-14:05 44142.60 07-APR-14:05 4784.05 09-APR-12:30 9307.32 07-APR-14:05 0.00
May 0.150636E+11 0.335505E+10 295.59 0.129247E+11 0.213890E+10 0.00 1.00 22-MAY-10:05 0.00 01-MAY-00:10 77304.64 30-MAY-14:05 77304.64 30-MAY-14:05 22458.05 31-MAY-06:03 17680.89 30-MAY-14:05 0.00
June 0.496504E+11 0.106161E+11 431.37 0.382456E+11 0.114048E+11 0.00 1.00 01-JUN-09:40 0.00 01-JUN-00:10 97589.20 27-JUN-06:03 70572.39 19-JUN-05:02 46276.20 20-JUN-06:03 24461.77 19-JUN-12:02 0.00
July 0.704051E+11 0.151640E+11 443.85 0.511096E+11 0.192955E+11 0.00 1.00 01-JUL-06:03 0.00 01-JUL-00:10 100844.01 22-JUL-05:03 73081.84 10-JUL-06:03 43831.13 22-JUL-06:03 20327.83 22-JUL-06:03 0.00
August 0.702807E+11 0.153479E+11 453.75 0.552194E+11 0.150612E+11 0.00 1.00 01-AUG-05:03 0.00 01-AUG-00:10 98372.13 17-AUG-06:03 75922.40 22-AUG-15:10 38209.79 17-AUG-06:03 20517.72 04-AUG-14:05 0.00
September 0.350338E+11 0.747242E+10 386.72 0.278348E+11 0.719901E+10 0.00 1.00 01-SEP-05:03 0.00 01-SEP-00:10 80398.57 06-SEP-06:03 70758.30 05-SEP-05:12 28251.04 06-SEP-05:12 16245.97 07-SEP-14:05 0.00
October 0.153277E+11 0.326531E+10 232.28 0.107602E+11 0.456757E+10 0.00 1.00 02-OCT-12:40 0.00 01-OCT-00:10 57054.35 04-OCT-14:05 44859.49 04-OCT-14:05 22054.19 24-OCT-09:10 11604.46 04-OCT-14:05 0.00
November 0.366993E+09 90415287.52 25.17 0.310628E+09 56365418.24 0.00 0.36 03-NOV-14:05 0.00 01-NOV-00:10 9175.68 03-NOV-14:05 9175.68 03-NOV-14:05 2871.84 10-NOV-10:00 2185.83 03-NOV-14:05 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.260674E+12 0.563403E+11 2386.52 0.200431E+12 0.602431E+11 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.704051E+11 0.153479E+11 453.75 0.552194E+11 0.192955E+11 0.00 1.00   0.00   100844.01   77304.64   46276.20   24461.77   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 365002.76 94540.61 0.58 329120.92 35881.84 0.00 0.01 30-JAN-05:30 0.00 01-JAN-00:02 198.99 30-JAN-05:30 170.93 30-JAN-05:30 28.06 30-JAN-05:30 51.53 30-JAN-05:30 0.00
February 76454.15 19799.41 0.11 70901.71 5552.45 0.00 0.01 05-FEB-09:30 0.00 01-FEB-00:10 205.41 05-FEB-09:30 187.72 05-FEB-09:30 17.69 05-FEB-09:30 53.19 05-FEB-09:30 0.00
March 0.478201E+09 0.112211E+09 18.52 0.341393E+09 0.136808E+09 0.00 0.67 27-MAR-16:00 0.00 01-MAR-00:10 21059.80 27-MAR-16:00 16524.83 27-MAR-16:00 7298.29 27-MAR-12:55 4622.86 27-MAR-16:00 0.00
April 0.442743E+10 0.100061E+10 98.77 0.397133E+10 0.456092E+09 0.00 1.00 07-APR-12:00 0.00 01-APR-00:10 47633.86 07-APR-14:30 47633.86 07-APR-14:30 6250.91 09-APR-11:53 10005.52 07-APR-14:00 0.00
May 0.159106E+11 0.356099E+10 294.99 0.136679E+11 0.224279E+10 0.00 1.00 29-MAY-10:02 0.00 01-MAY-00:10 85061.11 30-MAY-14:10 85061.11 30-MAY-14:10 14569.80 19-MAY-12:07 19535.75 30-MAY-14:00 0.00
June 0.529443E+11 0.113883E+11 431.92 0.410323E+11 0.119120E+11 0.00 1.00 01-JUN-09:40 0.00 01-JUN-00:10 107324.67 19-JUN-06:03 78718.18 19-JUN-05:02 32251.78 19-JUN-06:03 24080.79 19-JUN-12:05 0.00
July 0.752831E+11 0.162846E+11 447.43 0.555946E+11 0.196885E+11 0.00 1.00 01-JUL-08:50 0.00 01-JUL-00:10 113615.32 22-JUL-05:03 76537.99 10-JUL-04:02 53961.84 22-JUL-05:03 22737.41 22-JUL-05:03 0.00
August 0.747777E+11 0.163985E+11 453.83 0.594985E+11 0.152792E+11 0.00 1.00 01-AUG-05:03 0.00 01-AUG-00:10 101386.16 05-AUG-05:03 86669.28 22-AUG-14:50 39186.43 04-AUG-05:03 21943.39 04-AUG-14:00 0.00
September 0.357133E+11 0.768731E+10 386.25 0.280936E+11 0.761970E+10 0.00 1.00 01-SEP-05:03 0.00 01-SEP-00:10 81808.84 01-SEP-14:20 81808.84 01-SEP-14:20 25693.11 07-SEP-12:30 19557.10 01-SEP-14:20 0.00
October 0.147839E+11 0.318362E+10 225.39 0.102275E+11 0.455643E+10 0.00 1.00 03-OCT-10:50 0.00 01-OCT-00:10 59240.14 04-OCT-14:00 48461.01 04-OCT-14:50 22174.07 24-OCT-10:00 12090.31 04-OCT-13:50 0.00
November 0.315152E+09 78490251.61 24.54 0.253249E+09 61903061.00 0.00 0.27 03-NOV-14:00 0.00 01-NOV-00:10 7752.95 03-NOV-14:00 7752.95 03-NOV-14:00 2246.32 10-NOV-10:00 1885.03 03-NOV-14:00 0.00
December 90671.00 23489.90 0.17 81671.48 8999.52 0.00 0.01 31-DEC-09:20 0.00 01-DEC-00:10 151.12 31-DEC-09:20 136.12 31-DEC-09:20 15.00 31-DEC-09:20 39.15 31-DEC-09:20 0.00
                                       
Annual Sum or Average 0.274634E+12 0.596947E+11 2382.51 0.212681E+12 0.619535E+11 0.00                         0.00
Minimum of Months 76454.15 19799.41 0.11 70901.71 5552.45 0.00 0.01   0.00   151.12   136.12   15.00   39.15   0.00
Maximum of Months 0.752831E+11 0.163985E+11 453.83 0.594985E+11 0.196885E+11 0.00 1.00   0.00   113615.32   86669.28   53961.84   24080.79   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 327.71 0.00 327.71 26.14 1708.89 0.00 0.00 0.00
February 448.46 0.00 448.46 48.35 1781.23 0.00 0.00 0.00
March 621.90 0.00 621.90 235.74 1197.35 0.00 0.00 0.00
April 746.98 2.12 744.86 481.67 863.05 0.00 0.00 0.00
May 991.01 33.02 957.99 934.18 542.72 0.00 0.00 0.00
June 1050.95 56.47 994.48 1305.27 295.29 0.00 0.00 0.00
July 1015.65 36.73 978.92 1447.02 165.44 0.00 0.00 0.00
August 899.81 10.71 889.10 1268.90 222.25 0.00 0.00 0.00
September 678.31 0.13 678.18 730.58 448.38 0.00 0.00 0.00
October 587.03 0.00 587.03 440.50 819.17 0.00 0.00 0.00
November 411.74 0.00 411.74 124.82 1217.13 0.00 0.00 0.00
December 285.85 0.00 285.85 16.87 1588.17 0.00 0.00 0.00
                 
Annual Sum or Average 673.41 11.66 661.75 591.98 899.05 0.00 0.00 0.00
Minimum of Months 285.85 0.00 285.85 16.87 165.44 0.00 0.00 0.00
Maximum of Months 1050.95 56.47 994.48 1447.02 1781.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 456.37 182.97 273.40 291.43 1061.80 0.00 0.00 0.00
February 707.73 330.16 377.57 509.57 1074.10 0.00 0.00 0.00
March 902.84 383.99 518.86 799.00 775.47 0.00 0.00 0.00
April 1083.48 474.60 608.88 1107.28 563.37 0.00 0.00 0.00
May 1314.03 525.17 788.86 1526.49 371.67 0.00 0.00 0.00
June 1217.83 440.84 776.98 1594.09 202.44 0.00 0.00 0.00
July 1223.16 441.41 781.75 1733.80 112.58 0.00 0.00 0.00
August 1377.31 621.03 756.28 1944.79 149.95 0.00 0.00 0.00
September 1027.20 460.87 566.34 1286.11 292.80 0.00 0.00 0.00
October 931.23 422.07 509.17 1040.30 534.37 0.00 0.00 0.00
November 575.90 221.15 354.75 472.83 769.01 0.00 0.00 0.00
December 448.66 210.66 237.99 312.37 979.46 0.00 0.00 0.00
                 
Annual Sum or Average 940.30 393.35 546.95 1055.26 571.09 0.00 0.00 0.00
Minimum of Months 448.66 182.97 237.99 291.43 112.58 0.00 0.00 0.00
Maximum of Months 1377.31 621.03 788.86 1944.79 1074.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1695.32 1110.10 585.21 1694.48 1535.17 0.00 0.00 0.00
February 2236.06 1480.09 755.97 2268.57 1564.95 0.00 0.00 0.00
March 2017.35 1119.66 897.69 2161.41 1171.90 0.00 0.00 0.00
April 1565.39 619.00 946.39 1729.28 892.75 0.00 0.00 0.00
May 1371.84 286.14 1085.69 1601.90 584.16 0.00 0.00 0.00
June 1287.43 196.80 1090.63 1738.09 316.61 0.00 0.00 0.00
July 1349.48 234.40 1115.08 2019.64 170.32 0.00 0.00 0.00
August 1802.08 668.42 1133.66 2722.24 236.07 0.00 0.00 0.00
September 1955.30 1011.36 943.94 2620.50 461.46 0.00 0.00 0.00
October 2678.59 1679.67 998.92 3349.87 824.24 0.00 0.00 0.00
November 1857.37 1115.44 741.93 2003.10 1151.59 0.00 0.00 0.00
December 1837.47 1304.48 532.99 1910.64 1415.56 0.00 0.00 0.00
                 
Annual Sum or Average 1802.44 899.21 903.23 2152.10 856.30 0.00 0.00 0.00
Minimum of Months 1287.43 196.80 532.99 1601.90 170.32 0.00 0.00 0.00
Maximum of Months 2678.59 1679.67 1133.66 3349.87 1564.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 450.54 184.54 266.00 287.21 1085.56 0.00 0.00 0.00
February 664.38 291.80 372.58 467.24 1120.43 0.00 0.00 0.00
March 981.04 452.92 528.12 897.39 771.85 0.00 0.00 0.00
April 1072.24 458.78 613.45 1106.64 579.84 0.00 0.00 0.00
May 1249.05 474.34 774.71 1455.72 384.28 0.00 0.00 0.00
June 1367.04 551.37 815.68 1802.48 214.09 0.00 0.00 0.00
July 1280.31 482.12 798.18 1812.14 119.94 0.00 0.00 0.00
August 1416.37 655.69 760.68 2009.05 161.64 0.00 0.00 0.00
September 1005.51 439.41 566.10 1272.77 306.77 0.00 0.00 0.00
October 996.89 484.76 512.13 1133.80 550.82 0.00 0.00 0.00
November 468.13 135.29 332.84 327.30 789.03 0.00 0.00 0.00
December 416.40 180.18 236.22 272.32 1007.92 0.00 0.00 0.00
                 
Annual Sum or Average 949.31 400.18 549.13 1074.67 587.96 0.00 0.00 0.00
Minimum of Months 416.40 135.29 236.22 272.32 119.94 0.00 0.00 0.00
Maximum of Months 1416.37 655.69 815.68 2009.05 1120.43 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.23 0.00 109.23 8.48 586.88 0.00 0.00 0.00
February 149.48 0.00 149.48 16.70 607.27 0.00 0.00 0.00
March 207.29 0.00 207.29 84.44 400.32 0.00 0.00 0.00
April 248.98 0.71 248.27 170.07 283.99 0.00 0.00 0.00
May 330.32 11.01 319.31 327.17 172.58 0.00 0.00 0.00
June 350.30 18.82 331.48 445.79 94.15 0.00 0.00 0.00
July 338.53 12.24 326.29 492.00 51.26 0.00 0.00 0.00
August 299.92 3.57 296.35 428.12 73.59 0.00 0.00 0.00
September 226.09 0.04 226.05 244.68 156.31 0.00 0.00 0.00
October 195.67 0.00 195.67 143.15 294.08 0.00 0.00 0.00
November 137.24 0.00 137.24 36.91 444.45 0.00 0.00 0.00
December 95.28 0.00 95.28 4.60 563.47 0.00 0.00 0.00
                 
Annual Sum or Average 224.46 3.89 220.57 201.42 308.98 0.00 0.00 0.00
Minimum of Months 95.28 0.00 95.28 4.60 51.26 0.00 0.00 0.00
Maximum of Months 350.30 18.82 331.48 492.00 607.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.24 0.00 109.24 8.48 586.92 0.00 0.00 0.00
February 149.48 0.00 149.48 16.70 607.31 0.00 0.00 0.00
March 207.30 0.00 207.30 84.44 400.34 0.00 0.00 0.00
April 248.99 0.71 248.28 170.07 284.00 0.00 0.00 0.00
May 330.33 11.01 319.33 327.18 172.59 0.00 0.00 0.00
June 350.32 18.82 331.49 445.80 94.15 0.00 0.00 0.00
July 338.55 12.24 326.30 492.02 51.26 0.00 0.00 0.00
August 299.94 3.57 296.37 428.14 73.60 0.00 0.00 0.00
September 226.10 0.04 226.06 244.69 156.32 0.00 0.00 0.00
October 195.67 0.00 195.67 143.15 294.09 0.00 0.00 0.00
November 137.25 0.00 137.25 36.91 444.48 0.00 0.00 0.00
December 95.28 0.00 95.28 4.60 563.51 0.00 0.00 0.00
                 
Annual Sum or Average 224.47 3.89 220.58 201.42 309.00 0.00 0.00 0.00
Minimum of Months 95.28 0.00 95.28 4.60 51.26 0.00 0.00 0.00
Maximum of Months 350.32 18.82 331.49 492.02 607.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.24 0.00 109.24 8.48 586.92 0.00 0.00 0.00
February 149.48 0.00 149.48 16.70 607.31 0.00 0.00 0.00
March 207.30 0.00 207.30 84.44 400.34 0.00 0.00 0.00
April 248.99 0.71 248.28 170.07 284.00 0.00 0.00 0.00
May 330.33 11.01 319.33 327.18 172.59 0.00 0.00 0.00
June 350.32 18.82 331.49 445.80 94.15 0.00 0.00 0.00
July 338.55 12.24 326.30 492.02 51.26 0.00 0.00 0.00
August 299.94 3.57 296.37 428.14 73.60 0.00 0.00 0.00
September 226.10 0.04 226.06 244.69 156.32 0.00 0.00 0.00
October 195.67 0.00 195.67 143.15 294.09 0.00 0.00 0.00
November 137.25 0.00 137.25 36.91 444.48 0.00 0.00 0.00
December 95.28 0.00 95.28 4.60 563.51 0.00 0.00 0.00
                 
Annual Sum or Average 224.47 3.89 220.58 201.42 309.00 0.00 0.00 0.00
Minimum of Months 95.28 0.00 95.28 4.60 51.26 0.00 0.00 0.00
Maximum of Months 350.32 18.82 331.49 492.02 607.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 439.00 176.00 263.00 280.99 1061.14 0.00 0.00 0.00
February 680.80 317.59 363.21 492.20 1070.49 0.00 0.00 0.00
March 868.49 369.37 499.12 781.30 763.43 0.00 0.00 0.00
April 1042.25 456.54 585.71 1080.70 551.32 0.00 0.00 0.00
May 1264.03 505.18 758.85 1494.06 352.51 0.00 0.00 0.00
June 1171.49 424.07 747.42 1552.18 192.92 0.00 0.00 0.00
July 1176.62 424.61 752.01 1684.24 107.27 0.00 0.00 0.00
August 1324.90 597.39 727.50 1880.90 151.81 0.00 0.00 0.00
September 988.12 443.33 544.79 1240.60 302.86 0.00 0.00 0.00
October 895.80 406.01 489.80 994.51 564.76 0.00 0.00 0.00
November 553.98 212.73 341.25 440.60 821.39 0.00 0.00 0.00
December 431.58 202.64 228.94 294.01 1014.61 0.00 0.00 0.00
                 
Annual Sum or Average 904.52 378.38 526.14 1021.68 576.74 0.00 0.00 0.00
Minimum of Months 431.58 176.00 228.94 280.99 107.27 0.00 0.00 0.00
Maximum of Months 1324.90 597.39 758.85 1880.90 1070.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 17.36 6.96 10.40 11.11 41.96 0.00 0.00 0.00
February 26.92 12.56 14.36 19.46 42.33 0.00 0.00 0.00
March 34.34 14.60 19.73 30.89 30.19 0.00 0.00 0.00
April 41.21 18.05 23.16 42.73 21.80 0.00 0.00 0.00
May 49.98 19.97 30.00 59.07 13.94 0.00 0.00 0.00
June 46.32 16.77 29.55 61.37 7.63 0.00 0.00 0.00
July 46.52 16.79 29.73 66.59 4.24 0.00 0.00 0.00
August 52.39 23.62 28.76 74.37 6.00 0.00 0.00 0.00
September 39.07 17.53 21.54 49.05 11.97 0.00 0.00 0.00
October 35.42 16.05 19.37 39.32 22.33 0.00 0.00 0.00
November 21.90 8.41 13.49 17.42 32.48 0.00 0.00 0.00
December 17.06 8.01 9.05 11.63 40.12 0.00 0.00 0.00
                 
Annual Sum or Average 35.76 14.96 20.80 40.40 22.80 0.00 0.00 0.00
Minimum of Months 17.06 6.96 9.05 11.11 4.24 0.00 0.00 0.00
Maximum of Months 52.39 23.62 30.00 74.37 42.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 565.09 370.03 195.07 576.26 530.17 0.00 0.00 0.00
February 745.34 493.35 251.99 769.60 544.29 0.00 0.00 0.00
March 672.44 373.21 299.23 735.91 400.12 0.00 0.00 0.00
April 521.79 206.33 315.46 590.75 296.92 0.00 0.00 0.00
May 457.27 95.38 361.89 552.77 186.14 0.00 0.00 0.00
June 429.14 65.60 363.54 591.20 102.20 0.00 0.00 0.00
July 449.82 78.13 371.69 682.49 54.81 0.00 0.00 0.00
August 600.69 222.80 377.88 912.96 83.00 0.00 0.00 0.00
September 651.76 337.11 314.64 876.80 167.21 0.00 0.00 0.00
October 892.85 559.88 332.97 1118.11 307.34 0.00 0.00 0.00
November 619.11 371.81 247.31 667.75 423.40 0.00 0.00 0.00
December 612.48 434.82 177.66 640.51 508.66 0.00 0.00 0.00
                 
Annual Sum or Average 600.80 299.73 301.07 726.39 298.93 0.00 0.00 0.00
Minimum of Months 429.14 65.60 177.66 552.77 54.81 0.00 0.00 0.00
Maximum of Months 892.85 559.88 377.88 1118.11 544.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 565.09 370.03 195.07 576.26 530.17 0.00 0.00 0.00
February 745.34 493.35 251.99 769.60 544.29 0.00 0.00 0.00
March 672.44 373.21 299.23 735.91 400.12 0.00 0.00 0.00
April 521.79 206.33 315.46 590.75 296.92 0.00 0.00 0.00
May 457.27 95.38 361.89 552.77 186.14 0.00 0.00 0.00
June 429.14 65.60 363.54 591.20 102.20 0.00 0.00 0.00
July 449.82 78.13 371.69 682.49 54.81 0.00 0.00 0.00
August 600.69 222.80 377.88 912.96 83.00 0.00 0.00 0.00
September 651.76 337.11 314.64 876.80 167.21 0.00 0.00 0.00
October 892.85 559.88 332.97 1118.11 307.34 0.00 0.00 0.00
November 619.11 371.81 247.31 667.75 423.40 0.00 0.00 0.00
December 612.48 434.82 177.66 640.51 508.66 0.00 0.00 0.00
                 
Annual Sum or Average 600.80 299.73 301.07 726.39 298.93 0.00 0.00 0.00
Minimum of Months 429.14 65.60 177.66 552.77 54.81 0.00 0.00 0.00
Maximum of Months 892.85 559.88 377.88 1118.11 544.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 565.06 370.00 195.06 576.22 530.14 0.00 0.00 0.00
February 745.29 493.32 251.97 769.55 544.26 0.00 0.00 0.00
March 672.40 373.19 299.21 735.86 400.09 0.00 0.00 0.00
April 521.76 206.32 315.44 590.71 296.90 0.00 0.00 0.00
May 457.24 95.37 361.87 552.74 186.13 0.00 0.00 0.00
June 429.11 65.59 363.52 591.16 102.19 0.00 0.00 0.00
July 449.79 78.13 371.67 682.45 54.81 0.00 0.00 0.00
August 600.65 222.79 377.86 912.90 82.99 0.00 0.00 0.00
September 651.71 337.09 314.62 876.75 167.20 0.00 0.00 0.00
October 892.79 559.84 332.95 1118.04 307.32 0.00 0.00 0.00
November 619.07 371.78 247.29 667.71 423.37 0.00 0.00 0.00
December 612.44 434.79 177.65 640.47 508.63 0.00 0.00 0.00
                 
Annual Sum or Average 600.77 299.71 301.06 726.35 298.91 0.00 0.00 0.00
Minimum of Months 429.11 65.59 177.65 552.74 54.81 0.00 0.00 0.00
Maximum of Months 892.79 559.84 377.86 1118.04 544.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 433.40 177.52 255.88 280.41 1082.84 0.00 0.00 0.00
February 639.11 280.70 358.41 458.30 1115.73 0.00 0.00 0.00
March 943.72 435.69 508.03 878.25 764.96 0.00 0.00 0.00
April 1031.44 441.32 590.11 1082.15 570.01 0.00 0.00 0.00
May 1201.52 456.29 745.23 1425.56 366.80 0.00 0.00 0.00
June 1315.03 530.39 784.64 1753.49 207.97 0.00 0.00 0.00
July 1231.60 463.78 767.82 1760.52 116.40 0.00 0.00 0.00
August 1362.48 630.74 731.74 1943.14 165.19 0.00 0.00 0.00
September 967.25 422.69 544.57 1227.46 317.44 0.00 0.00 0.00
October 958.96 466.32 492.64 1085.30 585.23 0.00 0.00 0.00
November 450.32 130.15 320.18 304.83 838.15 0.00 0.00 0.00
December 400.55 173.32 227.23 260.26 1040.71 0.00 0.00 0.00
                 
Annual Sum or Average 913.19 384.96 528.24 1042.49 594.61 0.00 0.00 0.00
Minimum of Months 400.55 130.15 227.23 260.26 116.40 0.00 0.00 0.00
Maximum of Months 1362.48 630.74 784.64 1943.14 1115.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 17.14 7.02 10.12 11.09 42.81 0.00 0.00 0.00
February 25.27 11.10 14.17 18.12 44.12 0.00 0.00 0.00
March 37.31 17.23 20.09 34.73 30.25 0.00 0.00 0.00
April 40.78 17.45 23.33 42.79 22.54 0.00 0.00 0.00
May 47.51 18.04 29.47 56.37 14.50 0.00 0.00 0.00
June 51.99 20.97 31.02 69.33 8.22 0.00 0.00 0.00
July 48.70 18.34 30.36 69.61 4.60 0.00 0.00 0.00
August 53.87 24.94 28.93 76.83 6.53 0.00 0.00 0.00
September 38.24 16.71 21.53 48.53 12.55 0.00 0.00 0.00
October 37.92 18.44 19.48 42.91 23.14 0.00 0.00 0.00
November 17.81 5.15 12.66 12.05 33.14 0.00 0.00 0.00
December 15.84 6.85 8.98 10.29 41.15 0.00 0.00 0.00
                 
Annual Sum or Average 36.11 15.22 20.89 41.22 23.51 0.00 0.00 0.00
Minimum of Months 15.84 5.15 8.98 10.29 4.60 0.00 0.00 0.00
Maximum of Months 53.87 24.94 31.02 76.83 44.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 327.71 0.00 327.71 22.86 1782.14 0.00 0.00 0.00
February 448.46 0.00 448.46 43.76 1865.48 0.00 0.00 0.00
March 621.90 0.00 621.90 225.83 1263.95 0.00 0.00 0.00
April 746.98 2.12 744.86 470.92 912.56 0.00 0.00 0.00
May 991.01 33.02 957.99 930.89 561.99 0.00 0.00 0.00
June 1050.95 56.47 994.48 1310.26 302.73 0.00 0.00 0.00
July 1015.65 36.73 978.92 1455.15 167.92 0.00 0.00 0.00
August 899.81 10.71 889.10 1274.00 228.59 0.00 0.00 0.00
September 678.31 0.13 678.18 728.42 469.85 0.00 0.00 0.00
October 587.03 0.00 587.03 426.74 872.66 0.00 0.00 0.00
November 411.74 0.00 411.74 110.60 1309.34 0.00 0.00 0.00
December 285.85 0.00 285.85 13.16 1685.37 0.00 0.00 0.00
                 
Annual Sum or Average 673.41 11.66 661.75 588.05 946.60 0.00 0.00 0.00
Minimum of Months 285.85 0.00 285.85 13.16 167.92 0.00 0.00 0.00
Maximum of Months 1050.95 56.47 994.48 1455.15 1865.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 456.37 182.97 273.40 285.08 1108.25 0.00 0.00 0.00
February 707.73 330.16 377.57 497.79 1126.38 0.00 0.00 0.00
March 902.84 383.99 518.86 787.81 818.97 0.00 0.00 0.00
April 1083.48 474.60 608.88 1097.34 593.43 0.00 0.00 0.00
May 1314.03 525.17 788.86 1523.00 384.00 0.00 0.00 0.00
June 1217.83 440.84 776.98 1594.50 207.56 0.00 0.00 0.00
July 1223.16 441.41 781.75 1736.31 114.66 0.00 0.00 0.00
August 1377.31 621.03 756.28 1945.71 154.31 0.00 0.00 0.00
September 1027.20 460.87 566.34 1282.42 305.84 0.00 0.00 0.00
October 931.23 422.07 509.17 1029.54 566.20 0.00 0.00 0.00
November 575.90 221.15 354.75 457.07 825.98 0.00 0.00 0.00
December 448.66 210.66 237.99 302.18 1041.49 0.00 0.00 0.00
                 
Annual Sum or Average 940.30 393.35 546.95 1048.70 600.95 0.00 0.00 0.00
Minimum of Months 448.66 182.97 237.99 285.08 114.66 0.00 0.00 0.00
Maximum of Months 1377.31 621.03 788.86 1945.71 1126.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1695.32 1110.10 585.21 1684.39 1605.74 0.00 0.00 0.00
February 2236.06 1480.09 755.97 2251.93 1642.94 0.00 0.00 0.00
March 2017.35 1119.66 897.69 2151.10 1237.02 0.00 0.00 0.00
April 1565.39 619.00 946.39 1721.24 941.19 0.00 0.00 0.00
May 1371.84 286.14 1085.69 1601.63 605.34 0.00 0.00 0.00
June 1287.43 196.80 1090.63 1744.27 325.01 0.00 0.00 0.00
July 1349.48 234.40 1115.08 2028.67 173.40 0.00 0.00 0.00
August 1802.08 668.42 1133.66 2729.58 242.99 0.00 0.00 0.00
September 1955.30 1011.36 943.94 2620.93 481.56 0.00 0.00 0.00
October 2678.59 1679.67 998.92 3342.28 870.51 0.00 0.00 0.00
November 1857.37 1115.44 741.93 1982.22 1232.26 0.00 0.00 0.00
December 1837.47 1304.48 532.99 1892.49 1502.79 0.00 0.00 0.00
                 
Annual Sum or Average 1802.44 899.21 903.23 2146.43 900.75 0.00 0.00 0.00
Minimum of Months 1287.43 196.80 532.99 1601.63 173.40 0.00 0.00 0.00
Maximum of Months 2678.59 1679.67 1133.66 3342.28 1642.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 450.54 184.54 266.00 283.83 1132.87 0.00 0.00 0.00
February 664.38 291.80 372.58 462.32 1174.55 0.00 0.00 0.00
March 981.04 452.92 528.12 890.51 815.40 0.00 0.00 0.00
April 1072.24 458.78 613.45 1100.64 612.68 0.00 0.00 0.00
May 1249.05 474.34 774.71 1455.56 398.48 0.00 0.00 0.00
June 1367.04 551.37 815.68 1807.36 219.97 0.00 0.00 0.00
July 1280.31 482.12 798.18 1818.54 122.30 0.00 0.00 0.00
August 1416.37 655.69 760.68 2013.92 166.30 0.00 0.00 0.00
September 1005.51 439.41 566.10 1272.43 320.70 0.00 0.00 0.00
October 996.89 484.76 512.13 1126.42 584.89 0.00 0.00 0.00
November 468.13 135.29 332.84 315.91 847.43 0.00 0.00 0.00
December 416.40 180.18 236.22 266.41 1070.19 0.00 0.00 0.00
                 
Annual Sum or Average 949.31 400.18 549.13 1072.18 618.94 0.00 0.00 0.00
Minimum of Months 416.40 135.29 236.22 266.41 122.30 0.00 0.00 0.00
Maximum of Months 1416.37 655.69 815.68 2013.92 1174.55 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.877739E+09 0.00 0.877739E+09 70011345.46 0.457710E+10
February 0.108491E+10 0.00 0.108491E+10 0.116973E+09 0.430916E+10
March 0.166569E+10 0.00 0.166569E+10 0.631413E+09 0.320699E+10
April 0.193618E+10 5507101.70 0.193068E+10 0.124848E+10 0.223702E+10
May 0.265432E+10 88443495.07 0.256588E+10 0.250210E+10 0.145361E+10
June 0.272407E+10 0.146376E+09 0.257770E+10 0.338326E+10 0.765403E+09
July 0.272030E+10 98375305.77 0.262193E+10 0.387570E+10 0.443102E+09
August 0.241006E+10 28683108.84 0.238138E+10 0.339862E+10 0.595275E+09
September 0.175818E+10 329235.52 0.175785E+10 0.189367E+10 0.116221E+10
October 0.157230E+10 0.00 0.157230E+10 0.117983E+10 0.219406E+10
November 0.106724E+10 0.00 0.106724E+10 0.323528E+09 0.315481E+10
December 0.765622E+09 0.00 0.765622E+09 45192612.98 0.425374E+10
           
Annual Sum or Average 0.212366E+11 0.367714E+09 0.208689E+11 0.186688E+11 0.283525E+11
Minimum of Months 0.765622E+09 0.00 0.765622E+09 45192612.98 0.443102E+09
Maximum of Months 0.272407E+10 0.146376E+09 0.262193E+10 0.387570E+10 0.457710E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.122234E+10 0.490060E+09 0.732281E+09 0.780568E+09 0.284393E+10
February 0.171214E+10 0.798716E+09 0.913427E+09 0.123275E+10 0.259847E+10
March 0.241818E+10 0.102847E+10 0.138971E+10 0.214005E+10 0.207702E+10
April 0.280837E+10 0.123015E+10 0.157822E+10 0.287006E+10 0.146025E+10
May 0.351950E+10 0.140660E+10 0.211289E+10 0.408856E+10 0.995485E+09
June 0.315661E+10 0.114267E+10 0.201394E+10 0.413188E+10 0.524722E+09
July 0.327611E+10 0.118227E+10 0.209384E+10 0.464382E+10 0.301544E+09
August 0.368898E+10 0.166336E+10 0.202562E+10 0.520891E+10 0.401619E+09
September 0.266251E+10 0.119456E+10 0.146794E+10 0.333360E+10 0.758948E+09
October 0.249422E+10 0.113046E+10 0.136375E+10 0.278635E+10 0.143125E+10
November 0.149272E+10 0.573221E+09 0.919503E+09 0.122558E+10 0.199327E+10
December 0.120168E+10 0.564236E+09 0.637445E+09 0.836644E+09 0.262339E+10
           
Annual Sum or Average 0.296533E+11 0.124048E+11 0.172486E+11 0.332788E+11 0.180099E+11
Minimum of Months 0.120168E+10 0.490060E+09 0.637445E+09 0.780568E+09 0.301544E+09
Maximum of Months 0.368898E+10 0.166336E+10 0.211289E+10 0.520891E+10 0.284393E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.454073E+10 0.297330E+10 0.156743E+10 0.453848E+10 0.411181E+10
February 0.540948E+10 0.358064E+10 0.182885E+10 0.548813E+10 0.378592E+10
March 0.540327E+10 0.299891E+10 0.240436E+10 0.578912E+10 0.313882E+10
April 0.405750E+10 0.160446E+10 0.245304E+10 0.448229E+10 0.231400E+10
May 0.367432E+10 0.766406E+09 0.290792E+10 0.429054E+10 0.156460E+10
June 0.333701E+10 0.510096E+09 0.282691E+10 0.450514E+10 0.820654E+09
July 0.361445E+10 0.627829E+09 0.298662E+10 0.540941E+10 0.456185E+09
August 0.482670E+10 0.179030E+10 0.303640E+10 0.729126E+10 0.632294E+09
September 0.506813E+10 0.262144E+10 0.244668E+10 0.679234E+10 0.119610E+10
October 0.717434E+10 0.449882E+10 0.267551E+10 0.897228E+10 0.220764E+10
November 0.481431E+10 0.289122E+10 0.192309E+10 0.519204E+10 0.298493E+10
December 0.492147E+10 0.349392E+10 0.142756E+10 0.511746E+10 0.379145E+10
           
Annual Sum or Average 0.568417E+11 0.283574E+11 0.284844E+11 0.678685E+11 0.270044E+11
Minimum of Months 0.333701E+10 0.510096E+09 0.142756E+10 0.429054E+10 0.456185E+09
Maximum of Months 0.717434E+10 0.449882E+10 0.303640E+10 0.897228E+10 0.411181E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.120672E+10 0.494277E+09 0.712445E+09 0.769270E+09 0.290756E+10
February 0.160728E+10 0.705922E+09 0.901354E+09 0.113036E+10 0.271054E+10
March 0.262763E+10 0.121310E+10 0.141452E+10 0.240356E+10 0.206732E+10
April 0.277923E+10 0.118916E+10 0.159007E+10 0.286841E+10 0.150295E+10
May 0.334544E+10 0.127047E+10 0.207497E+10 0.389901E+10 0.102925E+10
June 0.354337E+10 0.142914E+10 0.211423E+10 0.467202E+10 0.554913E+09
July 0.342918E+10 0.129132E+10 0.213786E+10 0.485364E+10 0.321239E+09
August 0.379360E+10 0.175619E+10 0.203741E+10 0.538103E+10 0.432932E+09
September 0.260628E+10 0.113894E+10 0.146734E+10 0.329902E+10 0.795141E+09
October 0.267006E+10 0.129839E+10 0.137168E+10 0.303678E+10 0.147533E+10
November 0.121341E+10 0.350683E+09 0.862723E+09 0.848350E+09 0.204517E+10
December 0.111528E+10 0.482583E+09 0.632693E+09 0.729380E+09 0.269961E+10
           
Annual Sum or Average 0.299375E+11 0.126202E+11 0.173173E+11 0.338908E+11 0.185419E+11
Minimum of Months 0.111528E+10 0.350683E+09 0.632693E+09 0.729380E+09 0.321239E+09
Maximum of Months 0.379360E+10 0.175619E+10 0.213786E+10 0.538103E+10 0.290756E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.292566E+09 0.00 0.292566E+09 22712600.68 0.157191E+10
February 0.361619E+09 0.00 0.361619E+09 40391514.81 0.146912E+10
March 0.555204E+09 0.00 0.555204E+09 0.226174E+09 0.107221E+10
April 0.645364E+09 1835613.72 0.643528E+09 0.440811E+09 0.736091E+09
May 0.884732E+09 29479770.21 0.855252E+09 0.876289E+09 0.462228E+09
June 0.907981E+09 48789636.46 0.859192E+09 0.115548E+10 0.244027E+09
July 0.906725E+09 32790217.14 0.873935E+09 0.131776E+10 0.137294E+09
August 0.803315E+09 9560583.93 0.793755E+09 0.114667E+10 0.197113E+09
September 0.586032E+09 109739.98 0.585922E+09 0.634214E+09 0.405163E+09
October 0.524074E+09 0.00 0.524074E+09 0.383405E+09 0.787656E+09
November 0.355730E+09 0.00 0.355730E+09 95679341.96 0.115202E+10
December 0.255195E+09 0.00 0.255195E+09 12324502.26 0.150920E+10
           
Annual Sum or Average 0.707854E+10 0.122566E+09 0.695597E+10 0.635191E+10 0.974402E+10
Minimum of Months 0.255195E+09 0.00 0.255195E+09 12324502.26 0.137294E+09
Maximum of Months 0.907981E+09 48789636.46 0.873935E+09 0.131776E+10 0.157191E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.292577E+09 0.00 0.292577E+09 22711195.91 0.157201E+10
February 0.361633E+09 0.00 0.361633E+09 40390555.58 0.146921E+10
March 0.555226E+09 0.00 0.555226E+09 0.226177E+09 0.107228E+10
April 0.645390E+09 1835663.06 0.643554E+09 0.440823E+09 0.736138E+09
May 0.884767E+09 29480562.63 0.855286E+09 0.876317E+09 0.462256E+09
June 0.908017E+09 48790947.93 0.859226E+09 0.115553E+10 0.244040E+09
July 0.906761E+09 32791098.55 0.873970E+09 0.131782E+10 0.137301E+09
August 0.803349E+09 9560840.92 0.793788E+09 0.114672E+10 0.197122E+09
September 0.586056E+09 109742.93 0.585946E+09 0.634238E+09 0.405186E+09
October 0.524095E+09 0.00 0.524095E+09 0.383416E+09 0.787703E+09
November 0.355744E+09 0.00 0.355744E+09 95678889.17 0.115209E+10
December 0.255205E+09 0.00 0.255205E+09 12323726.24 0.150930E+10
           
Annual Sum or Average 0.707882E+10 0.122569E+09 0.695625E+10 0.635214E+10 0.974463E+10
Minimum of Months 0.255205E+09 0.00 0.255205E+09 12323726.24 0.137301E+09
Maximum of Months 0.908017E+09 48790947.93 0.873970E+09 0.131782E+10 0.157201E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.292577E+09 0.00 0.292577E+09 22711195.91 0.157201E+10
February 0.361633E+09 0.00 0.361633E+09 40390555.58 0.146921E+10
March 0.555226E+09 0.00 0.555226E+09 0.226177E+09 0.107228E+10
April 0.645390E+09 1835663.06 0.643554E+09 0.440823E+09 0.736138E+09
May 0.884767E+09 29480562.63 0.855286E+09 0.876317E+09 0.462256E+09
June 0.908017E+09 48790947.93 0.859226E+09 0.115553E+10 0.244040E+09
July 0.906761E+09 32791098.55 0.873970E+09 0.131782E+10 0.137301E+09
August 0.803349E+09 9560840.92 0.793788E+09 0.114672E+10 0.197122E+09
September 0.586056E+09 109742.93 0.585946E+09 0.634238E+09 0.405186E+09
October 0.524095E+09 0.00 0.524095E+09 0.383416E+09 0.787703E+09
November 0.355744E+09 0.00 0.355744E+09 95678889.17 0.115209E+10
December 0.255205E+09 0.00 0.255205E+09 12323726.24 0.150930E+10
           
Annual Sum or Average 0.707882E+10 0.122569E+09 0.695625E+10 0.635214E+10 0.974463E+10
Minimum of Months 0.255205E+09 0.00 0.255205E+09 12323726.24 0.137301E+09
Maximum of Months 0.908017E+09 48790947.93 0.873970E+09 0.131782E+10 0.157201E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.117583E+10 0.471411E+09 0.704419E+09 0.752605E+09 0.284215E+10
February 0.164699E+10 0.768321E+09 0.878673E+09 0.119074E+10 0.258972E+10
March 0.232617E+10 0.989331E+09 0.133684E+10 0.209262E+10 0.204476E+10
April 0.270151E+10 0.118334E+10 0.151817E+10 0.280117E+10 0.142902E+10
May 0.338558E+10 0.135308E+10 0.203250E+10 0.400170E+10 0.944157E+09
June 0.303650E+10 0.109919E+10 0.193731E+10 0.402324E+10 0.500058E+09
July 0.315145E+10 0.113728E+10 0.201418E+10 0.451108E+10 0.287314E+09
August 0.354861E+10 0.160006E+10 0.194855E+10 0.503781E+10 0.406615E+09
September 0.256120E+10 0.114910E+10 0.141209E+10 0.321564E+10 0.785006E+09
October 0.239931E+10 0.108745E+10 0.131187E+10 0.266369E+10 0.151264E+10
November 0.143592E+10 0.551408E+09 0.884517E+09 0.114204E+10 0.212904E+10
December 0.115596E+10 0.542764E+09 0.613192E+09 0.787485E+09 0.271753E+10
           
Annual Sum or Average 0.285250E+11 0.119327E+11 0.165923E+11 0.322198E+11 0.181880E+11
Minimum of Months 0.115596E+10 0.471411E+09 0.613192E+09 0.752605E+09 0.287314E+09
Maximum of Months 0.354861E+10 0.160006E+10 0.203250E+10 0.503781E+10 0.284215E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 46491248.53 18639173.47 27852075.06 29757325.55 0.112376E+09
February 65120688.91 30378734.06 34741954.85 47080647.05 0.102395E+09
March 91974516.67 39117249.61 52857267.06 82740465.13 80847889.69
April 0.106815E+09 46788213.91 60027079.77 0.110756E+09 56502069.85
May 0.133863E+09 53499380.13 80363332.10 0.158223E+09 37331098.15
June 0.120060E+09 43460819.36 76599620.23 0.159075E+09 19771829.51
July 0.124606E+09 44966859.13 79638710.84 0.178364E+09 11360148.02
August 0.140309E+09 63265002.36 77043847.34 0.199191E+09 16077182.81
September 0.101267E+09 45434569.04 55832907.16 0.127144E+09 31038418.64
October 94866683.40 42996643.49 51870039.91 0.105320E+09 59808481.72
November 56775167.18 21802171.41 34972995.77 45155381.13 84180400.57
December 45705453.17 21460412.81 24245040.36 31136452.85 0.107449E+09
           
Annual Sum or Average 0.112785E+10 0.471809E+09 0.656045E+09 0.127394E+10 0.719137E+09
Minimum of Months 45705453.17 18639173.47 24245040.36 29757325.55 11360148.02
Maximum of Months 0.140309E+09 63265002.36 80363332.10 0.199191E+09 0.112376E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.151355E+10 0.991081E+09 0.522470E+09 0.154345E+10 0.142001E+10
February 0.180313E+10 0.119352E+10 0.609607E+09 0.186182E+10 0.131675E+10
March 0.180106E+10 0.999616E+09 0.801445E+09 0.197105E+10 0.107167E+10
April 0.135248E+10 0.534808E+09 0.817672E+09 0.153122E+10 0.769606E+09
May 0.122476E+10 0.255463E+09 0.969297E+09 0.148054E+10 0.498556E+09
June 0.111232E+10 0.170029E+09 0.942296E+09 0.153239E+10 0.264892E+09
July 0.120480E+10 0.209272E+09 0.995531E+09 0.182799E+10 0.146800E+09
August 0.160888E+10 0.596755E+09 0.101212E+10 0.244528E+10 0.222306E+09
September 0.168935E+10 0.873796E+09 0.815553E+09 0.227267E+10 0.433414E+09
October 0.239140E+10 0.149958E+10 0.891826E+09 0.299474E+10 0.823181E+09
November 0.160474E+10 0.963721E+09 0.641020E+09 0.173080E+10 0.109745E+10
December 0.164046E+10 0.116462E+10 0.475845E+09 0.171555E+10 0.136240E+10
           
Annual Sum or Average 0.189469E+11 0.945226E+10 0.949469E+10 0.229075E+11 0.942703E+10
Minimum of Months 0.111232E+10 0.170029E+09 0.475845E+09 0.148054E+10 0.146800E+09
Maximum of Months 0.239140E+10 0.149958E+10 0.101212E+10 0.299474E+10 0.142001E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.151355E+10 0.991081E+09 0.522470E+09 0.154345E+10 0.142001E+10
February 0.180313E+10 0.119352E+10 0.609607E+09 0.186182E+10 0.131675E+10
March 0.180106E+10 0.999616E+09 0.801445E+09 0.197105E+10 0.107167E+10
April 0.135248E+10 0.534808E+09 0.817672E+09 0.153122E+10 0.769606E+09
May 0.122476E+10 0.255463E+09 0.969297E+09 0.148054E+10 0.498556E+09
June 0.111232E+10 0.170029E+09 0.942296E+09 0.153239E+10 0.264892E+09
July 0.120480E+10 0.209272E+09 0.995531E+09 0.182799E+10 0.146800E+09
August 0.160888E+10 0.596755E+09 0.101212E+10 0.244528E+10 0.222306E+09
September 0.168935E+10 0.873796E+09 0.815553E+09 0.227267E+10 0.433414E+09
October 0.239140E+10 0.149958E+10 0.891826E+09 0.299474E+10 0.823181E+09
November 0.160474E+10 0.963721E+09 0.641020E+09 0.173080E+10 0.109745E+10
December 0.164046E+10 0.116462E+10 0.475845E+09 0.171555E+10 0.136240E+10
           
Annual Sum or Average 0.189469E+11 0.945226E+10 0.949469E+10 0.229075E+11 0.942703E+10
Minimum of Months 0.111232E+10 0.170029E+09 0.475845E+09 0.148054E+10 0.146800E+09
Maximum of Months 0.239140E+10 0.149958E+10 0.101212E+10 0.299474E+10 0.142001E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.151345E+10 0.991018E+09 0.522437E+09 0.154335E+10 0.141992E+10
February 0.180302E+10 0.119345E+10 0.609569E+09 0.186171E+10 0.131666E+10
March 0.180095E+10 0.999553E+09 0.801394E+09 0.197092E+10 0.107160E+10
April 0.135240E+10 0.534774E+09 0.817621E+09 0.153113E+10 0.769558E+09
May 0.122468E+10 0.255447E+09 0.969236E+09 0.148045E+10 0.498525E+09
June 0.111225E+10 0.170018E+09 0.942237E+09 0.153229E+10 0.264876E+09
July 0.120473E+10 0.209259E+09 0.995468E+09 0.182788E+10 0.146791E+09
August 0.160878E+10 0.596718E+09 0.101206E+10 0.244512E+10 0.222292E+09
September 0.168924E+10 0.873741E+09 0.815501E+09 0.227252E+10 0.433386E+09
October 0.239125E+10 0.149948E+10 0.891770E+09 0.299455E+10 0.823129E+09
November 0.160464E+10 0.963660E+09 0.640979E+09 0.173069E+10 0.109738E+10
December 0.164036E+10 0.116454E+10 0.475815E+09 0.171544E+10 0.136232E+10
           
Annual Sum or Average 0.189457E+11 0.945166E+10 0.949409E+10 0.229061E+11 0.942644E+10
Minimum of Months 0.111225E+10 0.170018E+09 0.475815E+09 0.148045E+10 0.146791E+09
Maximum of Months 0.239125E+10 0.149948E+10 0.101206E+10 0.299455E+10 0.141992E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.116081E+10 0.475470E+09 0.685340E+09 0.751052E+09 0.290027E+10
February 0.154612E+10 0.679061E+09 0.867062E+09 0.110873E+10 0.269918E+10
March 0.252765E+10 0.116694E+10 0.136071E+10 0.235232E+10 0.204888E+10
April 0.267349E+10 0.114391E+10 0.152958E+10 0.280494E+10 0.147747E+10
May 0.321816E+10 0.122213E+10 0.199603E+10 0.381821E+10 0.982444E+09
June 0.340856E+10 0.137476E+10 0.203379E+10 0.454506E+10 0.539064E+09
July 0.329871E+10 0.124219E+10 0.205652E+10 0.471538E+10 0.311760E+09
August 0.364927E+10 0.168936E+10 0.195990E+10 0.520451E+10 0.442444E+09
September 0.250712E+10 0.109560E+10 0.141152E+10 0.318158E+10 0.822806E+09
October 0.256847E+10 0.124898E+10 0.131949E+10 0.290686E+10 0.156749E+10
November 0.116724E+10 0.337339E+09 0.829900E+09 0.790114E+09 0.217248E+10
December 0.107284E+10 0.464221E+09 0.608622E+09 0.697078E+09 0.278745E+10
           
Annual Sum or Average 0.287984E+11 0.121400E+11 0.166585E+11 0.328758E+11 0.187517E+11
Minimum of Months 0.107284E+10 0.337339E+09 0.608622E+09 0.697078E+09 0.311760E+09
Maximum of Months 0.364927E+10 0.168936E+10 0.205652E+10 0.520451E+10 0.290027E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 45897219.76 18799578.49 27097641.27 29695766.44 0.114674E+09
February 61132159.56 26849383.05 34282776.51 43837838.54 0.106723E+09
March 99940809.17 46139769.68 53801039.48 93008078.59 81010765.46
April 0.105707E+09 45229190.01 60477938.52 0.110904E+09 58417724.25
May 0.127243E+09 48321638.08 78921059.36 0.150968E+09 38844951.17
June 0.134771E+09 54356766.41 80414196.70 0.179707E+09 21314087.08
July 0.130428E+09 49114806.49 81312788.21 0.186442E+09 12326694.95
August 0.144288E+09 66795753.60 77492599.82 0.205781E+09 17493808.60
September 99128965.29 43318956.13 55810009.16 0.125796E+09 32532979.17
October 0.101555E+09 49383479.05 52171383.98 0.114934E+09 61976997.64
November 46151441.29 13338037.77 32813403.52 31240236.96 85898001.64
December 42419103.52 18354807.59 24064295.94 27561720.95 0.110213E+09
           
Annual Sum or Average 0.113866E+10 0.480002E+09 0.658659E+09 0.129988E+10 0.741426E+09
Minimum of Months 42419103.52 13338037.77 24064295.94 27561720.95 12326694.95
Maximum of Months 0.144288E+09 66795753.60 81312788.21 0.205781E+09 0.114674E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.877739E+09 0.00 0.877739E+09 61221858.71 0.477329E+10
February 0.108491E+10 0.00 0.108491E+10 0.105874E+09 0.451297E+10
March 0.166569E+10 0.00 0.166569E+10 0.604858E+09 0.338536E+10
April 0.193618E+10 5507101.70 0.193068E+10 0.122061E+10 0.236536E+10
May 0.265432E+10 88443495.07 0.256588E+10 0.249329E+10 0.150524E+10
June 0.272407E+10 0.146376E+09 0.257770E+10 0.339620E+10 0.784666E+09
July 0.272030E+10 98375305.77 0.262193E+10 0.389749E+10 0.449758E+09
August 0.241006E+10 28683108.84 0.238138E+10 0.341227E+10 0.612266E+09
September 0.175818E+10 329235.52 0.175785E+10 0.188807E+10 0.121785E+10
October 0.157230E+10 0.00 0.157230E+10 0.114298E+10 0.233734E+10
November 0.106724E+10 0.00 0.106724E+10 0.286674E+09 0.339381E+10
December 0.765622E+09 0.00 0.765622E+09 35250349.44 0.451409E+10
           
Annual Sum or Average 0.212366E+11 0.367714E+09 0.208689E+11 0.185448E+11 0.298520E+11
Minimum of Months 0.765622E+09 0.00 0.765622E+09 35250349.44 0.449758E+09
Maximum of Months 0.272407E+10 0.146376E+09 0.262193E+10 0.389749E+10 0.477329E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.122234E+10 0.490060E+09 0.732281E+09 0.763546E+09 0.296833E+10
February 0.171214E+10 0.798716E+09 0.913427E+09 0.120426E+10 0.272495E+10
March 0.241818E+10 0.102847E+10 0.138971E+10 0.211008E+10 0.219354E+10
April 0.280837E+10 0.123015E+10 0.157822E+10 0.284431E+10 0.153818E+10
May 0.351950E+10 0.140660E+10 0.211289E+10 0.407919E+10 0.102850E+10
June 0.315661E+10 0.114267E+10 0.201394E+10 0.413295E+10 0.538008E+09
July 0.327611E+10 0.118227E+10 0.209384E+10 0.465053E+10 0.307094E+09
August 0.368898E+10 0.166336E+10 0.202562E+10 0.521140E+10 0.413305E+09
September 0.266251E+10 0.119456E+10 0.146794E+10 0.332403E+10 0.792747E+09
October 0.249422E+10 0.113046E+10 0.136375E+10 0.275752E+10 0.151652E+10
November 0.149272E+10 0.573221E+09 0.919503E+09 0.118472E+10 0.214095E+10
December 0.120168E+10 0.564236E+09 0.637445E+09 0.809364E+09 0.278953E+10
           
Annual Sum or Average 0.296533E+11 0.124048E+11 0.172486E+11 0.330719E+11 0.189516E+11
Minimum of Months 0.120168E+10 0.490060E+09 0.637445E+09 0.763546E+09 0.307094E+09
Maximum of Months 0.368898E+10 0.166336E+10 0.211289E+10 0.521140E+10 0.296833E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.454073E+10 0.297330E+10 0.156743E+10 0.451148E+10 0.430082E+10
February 0.540948E+10 0.358064E+10 0.182885E+10 0.544786E+10 0.397459E+10
March 0.540327E+10 0.299891E+10 0.240436E+10 0.576150E+10 0.331323E+10
April 0.405750E+10 0.160446E+10 0.245304E+10 0.446144E+10 0.243956E+10
May 0.367432E+10 0.766406E+09 0.290792E+10 0.428980E+10 0.162135E+10
June 0.333701E+10 0.510096E+09 0.282691E+10 0.452116E+10 0.842427E+09
July 0.361445E+10 0.627829E+09 0.298662E+10 0.543358E+10 0.464443E+09
August 0.482670E+10 0.179030E+10 0.303640E+10 0.731090E+10 0.650817E+09
September 0.506813E+10 0.262144E+10 0.244668E+10 0.679345E+10 0.124819E+10
October 0.717434E+10 0.449882E+10 0.267551E+10 0.895197E+10 0.233159E+10
November 0.481431E+10 0.289122E+10 0.192309E+10 0.513792E+10 0.319402E+10
December 0.492147E+10 0.349392E+10 0.142756E+10 0.506884E+10 0.402507E+10
           
Annual Sum or Average 0.568417E+11 0.283574E+11 0.284844E+11 0.676899E+11 0.284061E+11
Minimum of Months 0.333701E+10 0.510096E+09 0.142756E+10 0.428980E+10 0.464443E+09
Maximum of Months 0.717434E+10 0.449882E+10 0.303640E+10 0.895197E+10 0.430082E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.120672E+10 0.494277E+09 0.712445E+09 0.760205E+09 0.303429E+10
February 0.160728E+10 0.705922E+09 0.901354E+09 0.111844E+10 0.284146E+10
March 0.262763E+10 0.121310E+10 0.141452E+10 0.238516E+10 0.218397E+10
April 0.277923E+10 0.118916E+10 0.159007E+10 0.285285E+10 0.158808E+10
May 0.334544E+10 0.127047E+10 0.207497E+10 0.389857E+10 0.106728E+10
June 0.354337E+10 0.142914E+10 0.211423E+10 0.468467E+10 0.570159E+09
July 0.342918E+10 0.129132E+10 0.213786E+10 0.487077E+10 0.327568E+09
August 0.379360E+10 0.175619E+10 0.203741E+10 0.539409E+10 0.445428E+09
September 0.260628E+10 0.113894E+10 0.146734E+10 0.329814E+10 0.831254E+09
October 0.267006E+10 0.129839E+10 0.137168E+10 0.301701E+10 0.156657E+10
November 0.121341E+10 0.350683E+09 0.862723E+09 0.818848E+09 0.219653E+10
December 0.111528E+10 0.482583E+09 0.632693E+09 0.713558E+09 0.286641E+10
           
Annual Sum or Average 0.299375E+11 0.126202E+11 0.173173E+11 0.338123E+11 0.195190E+11
Minimum of Months 0.111528E+10 0.350683E+09 0.632693E+09 0.713558E+09 0.327568E+09
Maximum of Months 0.379360E+10 0.175619E+10 0.213786E+10 0.539409E+10 0.303429E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 26.14 1708.89 327.71 0.00 327.71 0.00 0.00
February 48.35 1781.23 448.46 0.00 448.46 0.00 0.00
March 235.74 1197.35 621.90 0.00 621.90 0.00 0.00
April 481.67 863.05 746.98 2.12 744.86 0.00 0.00
May 934.18 542.72 991.01 33.02 957.99 0.00 0.00
June 1305.27 295.29 1050.95 56.47 994.48 0.00 0.00
July 1447.02 165.44 1015.65 36.73 978.92 0.00 0.00
August 1268.90 222.25 899.81 10.71 889.10 0.00 0.00
September 730.58 448.38 678.31 0.13 678.18 0.00 0.00
October 440.50 819.17 587.03 0.00 587.03 0.00 0.00
November 124.82 1217.13 411.74 0.00 411.74 0.00 0.00
December 16.87 1588.17 285.85 0.00 285.85 0.00 0.00
               
Annual Sum or Average 591.98 899.05 673.41 11.66 661.75 0.00 0.00
Minimum of Months 16.87 165.44 285.85 0.00 285.85 0.00 0.00
Maximum of Months 1447.02 1781.23 1050.95 56.47 994.48 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 291.43 1061.80 456.37 182.97 273.40 0.00 0.00
February 509.57 1074.10 707.73 330.16 377.57 0.00 0.00
March 799.00 775.47 902.84 383.99 518.86 0.00 0.00
April 1107.28 563.37 1083.48 474.60 608.88 0.00 0.00
May 1526.49 371.67 1314.03 525.17 788.86 0.00 0.00
June 1594.09 202.44 1217.83 440.84 776.98 0.00 0.00
July 1733.80 112.58 1223.16 441.41 781.75 0.00 0.00
August 1944.79 149.95 1377.31 621.03 756.28 0.00 0.00
September 1286.11 292.80 1027.20 460.87 566.34 0.00 0.00
October 1040.30 534.37 931.23 422.07 509.17 0.00 0.00
November 472.83 769.01 575.90 221.15 354.75 0.00 0.00
December 312.37 979.46 448.66 210.66 237.99 0.00 0.00
               
Annual Sum or Average 1055.26 571.09 940.30 393.35 546.95 0.00 0.00
Minimum of Months 291.43 112.58 448.66 182.97 237.99 0.00 0.00
Maximum of Months 1944.79 1074.10 1377.31 621.03 788.86 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1694.48 1535.17 1695.32 1110.10 585.21 0.00 0.00
February 2268.57 1564.95 2236.06 1480.09 755.97 0.00 0.00
March 2161.41 1171.90 2017.35 1119.66 897.69 0.00 0.00
April 1729.28 892.75 1565.39 619.00 946.39 0.00 0.00
May 1601.90 584.16 1371.84 286.14 1085.69 0.00 0.00
June 1738.09 316.61 1287.43 196.80 1090.63 0.00 0.00
July 2019.64 170.32 1349.48 234.40 1115.08 0.00 0.00
August 2722.24 236.07 1802.08 668.42 1133.66 0.00 0.00
September 2620.50 461.46 1955.30 1011.36 943.94 0.00 0.00
October 3349.87 824.24 2678.59 1679.67 998.92 0.00 0.00
November 2003.10 1151.59 1857.37 1115.44 741.93 0.00 0.00
December 1910.64 1415.56 1837.47 1304.48 532.99 0.00 0.00
               
Annual Sum or Average 2152.10 856.30 1802.44 899.21 903.23 0.00 0.00
Minimum of Months 1601.90 170.32 1287.43 196.80 532.99 0.00 0.00
Maximum of Months 3349.87 1564.95 2678.59 1679.67 1133.66 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 287.21 1085.56 450.54 184.54 266.00 0.00 0.00
February 467.24 1120.43 664.38 291.80 372.58 0.00 0.00
March 897.39 771.85 981.04 452.92 528.12 0.00 0.00
April 1106.64 579.84 1072.24 458.78 613.45 0.00 0.00
May 1455.72 384.28 1249.05 474.34 774.71 0.00 0.00
June 1802.48 214.09 1367.04 551.37 815.68 0.00 0.00
July 1812.14 119.94 1280.31 482.12 798.18 0.00 0.00
August 2009.05 161.64 1416.37 655.69 760.68 0.00 0.00
September 1272.77 306.77 1005.51 439.41 566.10 0.00 0.00
October 1133.80 550.82 996.89 484.76 512.13 0.00 0.00
November 327.30 789.03 468.13 135.29 332.84 0.00 0.00
December 272.32 1007.92 416.40 180.18 236.22 0.00 0.00
               
Annual Sum or Average 1074.67 587.96 949.31 400.18 549.13 0.00 0.00
Minimum of Months 272.32 119.94 416.40 135.29 236.22 0.00 0.00
Maximum of Months 2009.05 1120.43 1416.37 655.69 815.68 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 25.44 1760.72 327.70 0.00 327.70 0.00 0.00
February 50.09 1821.90 448.45 0.00 448.45 0.00 0.00
March 253.33 1201.00 621.88 0.00 621.88 0.00 0.00
April 510.21 851.99 746.97 2.12 744.84 0.00 0.00
May 981.53 517.75 990.99 33.02 957.97 0.00 0.00
June 1337.40 282.45 1050.93 56.47 994.46 0.00 0.00
July 1476.03 153.78 1015.62 36.73 978.90 0.00 0.00
August 1284.39 220.79 899.80 10.71 889.09 0.00 0.00
September 734.06 468.96 678.30 0.13 678.17 0.00 0.00
October 429.45 882.27 587.02 0.00 587.02 0.00 0.00
November 110.74 1333.41 411.74 0.00 411.74 0.00 0.00
December 13.80 1690.49 285.84 0.00 285.84 0.00 0.00
               
Annual Sum or Average 604.27 926.98 673.39 11.66 661.73 0.00 0.00
Minimum of Months 13.80 153.78 285.84 0.00 285.84 0.00 0.00
Maximum of Months 1476.03 1821.90 1050.93 56.47 994.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 292.10 1103.09 456.36 182.96 273.40 0.00 0.00
February 511.66 1112.81 707.72 330.15 377.57 0.00 0.00
March 812.19 793.61 902.83 383.98 518.85 0.00 0.00
April 1123.43 573.12 1083.46 474.59 608.87 0.00 0.00
May 1553.14 366.45 1314.01 525.15 788.85 0.00 0.00
June 1613.55 200.55 1217.81 440.84 776.97 0.00 0.00
July 1750.84 111.51 1223.14 441.40 781.74 0.00 0.00
August 1955.27 157.82 1377.28 621.02 756.27 0.00 0.00
September 1289.66 314.83 1027.19 460.86 566.33 0.00 0.00
October 1033.83 587.09 931.22 422.06 509.16 0.00 0.00
November 458.02 853.87 575.89 221.15 354.74 0.00 0.00
December 305.64 1054.73 448.65 210.66 237.99 0.00 0.00
               
Annual Sum or Average 1062.08 599.54 940.29 393.35 546.94 0.00 0.00
Minimum of Months 292.10 111.51 448.65 182.96 237.99 0.00 0.00
Maximum of Months 1955.27 1112.81 1377.28 621.02 788.85 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1728.74 1590.47 1695.25 1110.06 585.19 0.00 0.00
February 2308.76 1632.84 2235.98 1480.03 755.95 0.00 0.00
March 2207.67 1200.32 2017.28 1119.62 897.66 0.00 0.00
April 1772.21 890.73 1565.34 618.98 946.36 0.00 0.00
May 1658.28 558.41 1371.79 286.13 1085.66 0.00 0.00
June 1773.56 306.58 1287.39 196.79 1090.60 0.00 0.00
July 2047.44 164.42 1349.44 234.39 1115.04 0.00 0.00
August 2738.83 248.99 1802.02 668.39 1133.63 0.00 0.00
September 2630.35 501.63 1955.22 1011.32 943.91 0.00 0.00
October 3354.25 922.00 2678.49 1679.60 998.89 0.00 0.00
November 2003.20 1270.17 1857.30 1115.39 741.91 0.00 0.00
December 1921.50 1525.96 1837.40 1304.43 532.97 0.00 0.00
               
Annual Sum or Average 2179.13 896.77 1802.37 899.17 903.20 0.00 0.00
Minimum of Months 1658.28 164.42 1287.39 196.79 532.97 0.00 0.00
Maximum of Months 3354.25 1632.84 2678.49 1679.60 1133.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 291.50 1125.65 450.53 184.54 265.99 0.00 0.00
February 476.42 1159.85 664.37 291.80 372.58 0.00 0.00
March 912.98 795.21 981.03 452.91 528.12 0.00 0.00
April 1124.94 592.55 1072.22 458.77 613.45 0.00 0.00
May 1481.92 381.31 1249.03 474.33 774.70 0.00 0.00
June 1822.83 216.20 1367.03 551.36 815.67 0.00 0.00
July 1830.13 121.00 1280.29 482.12 798.18 0.00 0.00
August 2019.97 171.72 1416.35 655.68 760.68 0.00 0.00
September 1275.99 329.99 1005.50 439.40 566.10 0.00 0.00
October 1128.21 608.37 996.87 484.75 512.12 0.00 0.00
November 316.88 871.29 468.13 135.29 332.84 0.00 0.00
December 270.55 1081.86 416.39 180.17 236.22 0.00 0.00
               
Annual Sum or Average 1083.70 618.12 949.30 400.18 549.12 0.00 0.00
Minimum of Months 270.55 121.00 416.39 135.29 236.22 0.00 0.00
Maximum of Months 2019.97 1159.85 1416.35 655.68 815.67 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 22.86 1782.14 327.71 0.00 327.71 0.00 0.00
February 43.76 1865.48 448.46 0.00 448.46 0.00 0.00
March 225.83 1263.95 621.90 0.00 621.90 0.00 0.00
April 470.92 912.56 746.98 2.12 744.86 0.00 0.00
May 930.89 561.99 991.01 33.02 957.99 0.00 0.00
June 1310.26 302.73 1050.95 56.47 994.48 0.00 0.00
July 1455.15 167.92 1015.65 36.73 978.92 0.00 0.00
August 1274.00 228.59 899.81 10.71 889.10 0.00 0.00
September 728.42 469.85 678.31 0.13 678.18 0.00 0.00
October 426.74 872.66 587.03 0.00 587.03 0.00 0.00
November 110.60 1309.34 411.74 0.00 411.74 0.00 0.00
December 13.16 1685.37 285.85 0.00 285.85 0.00 0.00
               
Annual Sum or Average 588.05 946.60 673.41 11.66 661.75 0.00 0.00
Minimum of Months 13.16 167.92 285.85 0.00 285.85 0.00 0.00
Maximum of Months 1455.15 1865.48 1050.95 56.47 994.48 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 285.08 1108.25 456.37 182.97 273.40 0.00 0.00
February 497.79 1126.38 707.73 330.16 377.57 0.00 0.00
March 787.81 818.97 902.84 383.99 518.86 0.00 0.00
April 1097.34 593.43 1083.48 474.60 608.88 0.00 0.00
May 1523.00 384.00 1314.03 525.17 788.86 0.00 0.00
June 1594.50 207.56 1217.83 440.84 776.98 0.00 0.00
July 1736.31 114.66 1223.16 441.41 781.75 0.00 0.00
August 1945.71 154.31 1377.31 621.03 756.28 0.00 0.00
September 1282.42 305.84 1027.20 460.87 566.34 0.00 0.00
October 1029.54 566.20 931.23 422.07 509.17 0.00 0.00
November 457.07 825.98 575.90 221.15 354.75 0.00 0.00
December 302.18 1041.49 448.66 210.66 237.99 0.00 0.00
               
Annual Sum or Average 1048.70 600.95 940.30 393.35 546.95 0.00 0.00
Minimum of Months 285.08 114.66 448.66 182.97 237.99 0.00 0.00
Maximum of Months 1945.71 1126.38 1377.31 621.03 788.86 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1684.39 1605.74 1695.32 1110.10 585.21 0.00 0.00
February 2251.93 1642.94 2236.06 1480.09 755.97 0.00 0.00
March 2151.10 1237.02 2017.35 1119.66 897.69 0.00 0.00
April 1721.24 941.19 1565.39 619.00 946.39 0.00 0.00
May 1601.63 605.34 1371.84 286.14 1085.69 0.00 0.00
June 1744.27 325.01 1287.43 196.80 1090.63 0.00 0.00
July 2028.67 173.40 1349.48 234.40 1115.08 0.00 0.00
August 2729.58 242.99 1802.08 668.42 1133.66 0.00 0.00
September 2620.93 481.56 1955.30 1011.36 943.94 0.00 0.00
October 3342.28 870.51 2678.59 1679.67 998.92 0.00 0.00
November 1982.22 1232.26 1857.37 1115.44 741.93 0.00 0.00
December 1892.49 1502.79 1837.47 1304.48 532.99 0.00 0.00
               
Annual Sum or Average 2146.43 900.75 1802.44 899.21 903.23 0.00 0.00
Minimum of Months 1601.63 173.40 1287.43 196.80 532.99 0.00 0.00
Maximum of Months 3342.28 1642.94 2678.59 1679.67 1133.66 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 283.83 1132.87 450.54 184.54 266.00 0.00 0.00
February 462.32 1174.55 664.38 291.80 372.58 0.00 0.00
March 890.51 815.40 981.04 452.92 528.12 0.00 0.00
April 1100.64 612.68 1072.24 458.78 613.45 0.00 0.00
May 1455.56 398.48 1249.05 474.34 774.71 0.00 0.00
June 1807.36 219.97 1367.04 551.37 815.68 0.00 0.00
July 1818.54 122.30 1280.31 482.12 798.18 0.00 0.00
August 2013.92 166.30 1416.37 655.69 760.68 0.00 0.00
September 1272.43 320.70 1005.51 439.41 566.10 0.00 0.00
October 1126.42 584.89 996.89 484.76 512.13 0.00 0.00
November 315.91 847.43 468.13 135.29 332.84 0.00 0.00
December 266.41 1070.19 416.40 180.18 236.22 0.00 0.00
               
Annual Sum or Average 1072.18 618.94 949.31 400.18 549.13 0.00 0.00
Minimum of Months 266.41 122.30 416.40 135.29 236.22 0.00 0.00
Maximum of Months 2013.92 1174.55 1416.37 655.69 815.68 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 70011345.46 0.457710E+10 0.877739E+09 0.00 0.877739E+09 0.00 0.00
February 0.116973E+09 0.430916E+10 0.108491E+10 0.00 0.108491E+10 0.00 0.00
March 0.631413E+09 0.320699E+10 0.166569E+10 0.00 0.166569E+10 0.00 0.00
April 0.124848E+10 0.223702E+10 0.193618E+10 5507101.70 0.193068E+10 0.00 0.00
May 0.250210E+10 0.145361E+10 0.265432E+10 88443495.07 0.256588E+10 0.00 0.00
June 0.338326E+10 0.765403E+09 0.272407E+10 0.146376E+09 0.257770E+10 0.00 0.00
July 0.387570E+10 0.443102E+09 0.272030E+10 98375305.77 0.262193E+10 0.00 0.00
August 0.339862E+10 0.595275E+09 0.241006E+10 28683108.84 0.238138E+10 0.00 0.00
September 0.189367E+10 0.116221E+10 0.175818E+10 329235.52 0.175785E+10 0.00 0.00
October 0.117983E+10 0.219406E+10 0.157230E+10 0.00 0.157230E+10 0.00 0.00
November 0.323528E+09 0.315481E+10 0.106724E+10 0.00 0.106724E+10 0.00 0.00
December 45192612.98 0.425374E+10 0.765622E+09 0.00 0.765622E+09 0.00 0.00
               
Annual Sum or Average 0.186688E+11 0.283525E+11 0.212366E+11 0.367714E+09 0.208689E+11 0.00 0.00
Minimum of Months 45192612.98 0.443102E+09 0.765622E+09 0.00 0.765622E+09 0.00 0.00
Maximum of Months 0.387570E+10 0.457710E+10 0.272407E+10 0.146376E+09 0.262193E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.780568E+09 0.284393E+10 0.122234E+10 0.490060E+09 0.732281E+09 0.00 0.00
February 0.123275E+10 0.259847E+10 0.171214E+10 0.798716E+09 0.913427E+09 0.00 0.00
March 0.214005E+10 0.207702E+10 0.241818E+10 0.102847E+10 0.138971E+10 0.00 0.00
April 0.287006E+10 0.146025E+10 0.280837E+10 0.123015E+10 0.157822E+10 0.00 0.00
May 0.408856E+10 0.995485E+09 0.351950E+10 0.140660E+10 0.211289E+10 0.00 0.00
June 0.413188E+10 0.524722E+09 0.315661E+10 0.114267E+10 0.201394E+10 0.00 0.00
July 0.464382E+10 0.301544E+09 0.327611E+10 0.118227E+10 0.209384E+10 0.00 0.00
August 0.520891E+10 0.401619E+09 0.368898E+10 0.166336E+10 0.202562E+10 0.00 0.00
September 0.333360E+10 0.758948E+09 0.266251E+10 0.119456E+10 0.146794E+10 0.00 0.00
October 0.278635E+10 0.143125E+10 0.249422E+10 0.113046E+10 0.136375E+10 0.00 0.00
November 0.122558E+10 0.199327E+10 0.149272E+10 0.573221E+09 0.919503E+09 0.00 0.00
December 0.836644E+09 0.262339E+10 0.120168E+10 0.564236E+09 0.637445E+09 0.00 0.00
               
Annual Sum or Average 0.332788E+11 0.180099E+11 0.296533E+11 0.124048E+11 0.172486E+11 0.00 0.00
Minimum of Months 0.780568E+09 0.301544E+09 0.120168E+10 0.490060E+09 0.637445E+09 0.00 0.00
Maximum of Months 0.520891E+10 0.284393E+10 0.368898E+10 0.166336E+10 0.211289E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.453848E+10 0.411181E+10 0.454073E+10 0.297330E+10 0.156743E+10 0.00 0.00
February 0.548813E+10 0.378592E+10 0.540948E+10 0.358064E+10 0.182885E+10 0.00 0.00
March 0.578912E+10 0.313882E+10 0.540327E+10 0.299891E+10 0.240436E+10 0.00 0.00
April 0.448229E+10 0.231400E+10 0.405750E+10 0.160446E+10 0.245304E+10 0.00 0.00
May 0.429054E+10 0.156460E+10 0.367432E+10 0.766406E+09 0.290792E+10 0.00 0.00
June 0.450514E+10 0.820654E+09 0.333701E+10 0.510096E+09 0.282691E+10 0.00 0.00
July 0.540941E+10 0.456185E+09 0.361445E+10 0.627829E+09 0.298662E+10 0.00 0.00
August 0.729126E+10 0.632294E+09 0.482670E+10 0.179030E+10 0.303640E+10 0.00 0.00
September 0.679234E+10 0.119610E+10 0.506813E+10 0.262144E+10 0.244668E+10 0.00 0.00
October 0.897228E+10 0.220764E+10 0.717434E+10 0.449882E+10 0.267551E+10 0.00 0.00
November 0.519204E+10 0.298493E+10 0.481431E+10 0.289122E+10 0.192309E+10 0.00 0.00
December 0.511746E+10 0.379145E+10 0.492147E+10 0.349392E+10 0.142756E+10 0.00 0.00
               
Annual Sum or Average 0.678685E+11 0.270044E+11 0.568417E+11 0.283574E+11 0.284844E+11 0.00 0.00
Minimum of Months 0.429054E+10 0.456185E+09 0.333701E+10 0.510096E+09 0.142756E+10 0.00 0.00
Maximum of Months 0.897228E+10 0.411181E+10 0.717434E+10 0.449882E+10 0.303640E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.769270E+09 0.290756E+10 0.120672E+10 0.494277E+09 0.712445E+09 0.00 0.00
February 0.113036E+10 0.271054E+10 0.160728E+10 0.705922E+09 0.901354E+09 0.00 0.00
March 0.240356E+10 0.206732E+10 0.262763E+10 0.121310E+10 0.141452E+10 0.00 0.00
April 0.286841E+10 0.150295E+10 0.277923E+10 0.118916E+10 0.159007E+10 0.00 0.00
May 0.389901E+10 0.102925E+10 0.334544E+10 0.127047E+10 0.207497E+10 0.00 0.00
June 0.467202E+10 0.554913E+09 0.354337E+10 0.142914E+10 0.211423E+10 0.00 0.00
July 0.485364E+10 0.321239E+09 0.342918E+10 0.129132E+10 0.213786E+10 0.00 0.00
August 0.538103E+10 0.432932E+09 0.379360E+10 0.175619E+10 0.203741E+10 0.00 0.00
September 0.329902E+10 0.795141E+09 0.260628E+10 0.113894E+10 0.146734E+10 0.00 0.00
October 0.303678E+10 0.147533E+10 0.267006E+10 0.129839E+10 0.137168E+10 0.00 0.00
November 0.848350E+09 0.204517E+10 0.121341E+10 0.350683E+09 0.862723E+09 0.00 0.00
December 0.729380E+09 0.269961E+10 0.111528E+10 0.482583E+09 0.632693E+09 0.00 0.00
               
Annual Sum or Average 0.338908E+11 0.185419E+11 0.299375E+11 0.126202E+11 0.173173E+11 0.00 0.00
Minimum of Months 0.729380E+09 0.321239E+09 0.111528E+10 0.350683E+09 0.632693E+09 0.00 0.00
Maximum of Months 0.538103E+10 0.290756E+10 0.379360E+10 0.175619E+10 0.213786E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 68134992.50 0.471592E+10 0.877720E+09 0.00 0.877720E+09 0.00 0.00
February 0.121173E+09 0.440754E+10 0.108489E+10 0.00 0.108489E+10 0.00 0.00
March 0.678528E+09 0.321676E+10 0.166566E+10 0.00 0.166566E+10 0.00 0.00
April 0.132246E+10 0.220837E+10 0.193614E+10 5506939.83 0.193064E+10 0.00 0.00
May 0.262892E+10 0.138674E+10 0.265427E+10 88440895.47 0.256582E+10 0.00 0.00
June 0.346653E+10 0.732107E+09 0.272402E+10 0.146372E+09 0.257764E+10 0.00 0.00
July 0.395339E+10 0.411896E+09 0.272025E+10 98372414.25 0.262187E+10 0.00 0.00
August 0.344010E+10 0.591357E+09 0.241001E+10 28682265.77 0.238133E+10 0.00 0.00
September 0.190269E+10 0.121554E+10 0.175814E+10 329225.84 0.175781E+10 0.00 0.00
October 0.115024E+10 0.236306E+10 0.157226E+10 0.00 0.157226E+10 0.00 0.00
November 0.287037E+09 0.345620E+10 0.106722E+10 0.00 0.106722E+10 0.00 0.00
December 36971954.74 0.452780E+10 0.765605E+09 0.00 0.765605E+09 0.00 0.00
               
Annual Sum or Average 0.190562E+11 0.292333E+11 0.212362E+11 0.367703E+09 0.208685E+11 0.00 0.00
Minimum of Months 36971954.74 0.411896E+09 0.765605E+09 0.00 0.765605E+09 0.00 0.00
Maximum of Months 0.395339E+10 0.471592E+10 0.272402E+10 0.146372E+09 0.262187E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.782362E+09 0.295453E+10 0.122232E+10 0.490050E+09 0.732271E+09 0.00 0.00
February 0.123782E+10 0.269211E+10 0.171212E+10 0.798700E+09 0.913415E+09 0.00 0.00
March 0.217536E+10 0.212561E+10 0.241814E+10 0.102845E+10 0.138969E+10 0.00 0.00
April 0.291193E+10 0.148552E+10 0.280833E+10 0.123013E+10 0.157820E+10 0.00 0.00
May 0.415992E+10 0.981488E+09 0.351944E+10 0.140657E+10 0.211287E+10 0.00 0.00
June 0.418232E+10 0.519829E+09 0.315656E+10 0.114265E+10 0.201391E+10 0.00 0.00
July 0.468944E+10 0.298674E+09 0.327606E+10 0.118224E+10 0.209381E+10 0.00 0.00
August 0.523700E+10 0.422692E+09 0.368892E+10 0.166333E+10 0.202559E+10 0.00 0.00
September 0.334279E+10 0.816044E+09 0.266247E+10 0.119454E+10 0.146793E+10 0.00 0.00
October 0.276901E+10 0.157245E+10 0.249418E+10 0.113044E+10 0.136374E+10 0.00 0.00
November 0.118720E+10 0.221322E+10 0.149270E+10 0.573210E+09 0.919490E+09 0.00 0.00
December 0.818622E+09 0.282498E+10 0.120166E+10 0.564225E+09 0.637437E+09 0.00 0.00
               
Annual Sum or Average 0.334938E+11 0.189071E+11 0.296529E+11 0.124045E+11 0.172484E+11 0.00 0.00
Minimum of Months 0.782362E+09 0.298674E+09 0.120166E+10 0.490050E+09 0.637437E+09 0.00 0.00
Maximum of Months 0.523700E+10 0.295453E+10 0.368892E+10 0.166333E+10 0.211287E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.463026E+10 0.425993E+10 0.454055E+10 0.297318E+10 0.156738E+10 0.00 0.00
February 0.558535E+10 0.395016E+10 0.540927E+10 0.358049E+10 0.182878E+10 0.00 0.00
March 0.591302E+10 0.321494E+10 0.540307E+10 0.299879E+10 0.240428E+10 0.00 0.00
April 0.459357E+10 0.230877E+10 0.405736E+10 0.160439E+10 0.245297E+10 0.00 0.00
May 0.444153E+10 0.149564E+10 0.367420E+10 0.766374E+09 0.290783E+10 0.00 0.00
June 0.459706E+10 0.794660E+09 0.333690E+10 0.510075E+09 0.282683E+10 0.00 0.00
July 0.548386E+10 0.440391E+09 0.361433E+10 0.627803E+09 0.298653E+10 0.00 0.00
August 0.733568E+10 0.666905E+09 0.482653E+10 0.179023E+10 0.303630E+10 0.00 0.00
September 0.681786E+10 0.130021E+10 0.506794E+10 0.262133E+10 0.244661E+10 0.00 0.00
October 0.898402E+10 0.246949E+10 0.717406E+10 0.449864E+10 0.267542E+10 0.00 0.00
November 0.519230E+10 0.329229E+10 0.481412E+10 0.289110E+10 0.192302E+10 0.00 0.00
December 0.514654E+10 0.408712E+10 0.492128E+10 0.349377E+10 0.142751E+10 0.00 0.00
               
Annual Sum or Average 0.687211E+11 0.282805E+11 0.568396E+11 0.283562E+11 0.284835E+11 0.00 0.00
Minimum of Months 0.444153E+10 0.440391E+09 0.333690E+10 0.510075E+09 0.142751E+10 0.00 0.00
Maximum of Months 0.898402E+10 0.425993E+10 0.717406E+10 0.449864E+10 0.303630E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.780747E+09 0.301494E+10 0.120671E+10 0.494269E+09 0.712437E+09 0.00 0.00
February 0.115256E+10 0.280590E+10 0.160726E+10 0.705911E+09 0.901345E+09 0.00 0.00
March 0.244532E+10 0.212989E+10 0.262759E+10 0.121308E+10 0.141451E+10 0.00 0.00
April 0.291584E+10 0.153589E+10 0.277920E+10 0.118914E+10 0.159005E+10 0.00 0.00
May 0.396918E+10 0.102129E+10 0.334540E+10 0.127045E+10 0.207495E+10 0.00 0.00
June 0.472476E+10 0.560378E+09 0.354333E+10 0.142912E+10 0.211421E+10 0.00 0.00
July 0.490183E+10 0.324087E+09 0.342914E+10 0.129130E+10 0.213783E+10 0.00 0.00
August 0.541029E+10 0.459938E+09 0.379356E+10 0.175616E+10 0.203739E+10 0.00 0.00
September 0.330737E+10 0.855339E+09 0.260625E+10 0.113892E+10 0.146733E+10 0.00 0.00
October 0.302179E+10 0.162946E+10 0.267003E+10 0.129837E+10 0.137166E+10 0.00 0.00
November 0.821354E+09 0.225838E+10 0.121339E+10 0.350677E+09 0.862713E+09 0.00 0.00
December 0.724640E+09 0.289766E+10 0.111526E+10 0.482575E+09 0.632686E+09 0.00 0.00
               
Annual Sum or Average 0.341757E+11 0.194932E+11 0.299371E+11 0.126200E+11 0.173171E+11 0.00 0.00
Minimum of Months 0.724640E+09 0.324087E+09 0.111526E+10 0.350677E+09 0.632686E+09 0.00 0.00
Maximum of Months 0.541029E+10 0.301494E+10 0.379356E+10 0.175616E+10 0.213783E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 61221858.71 0.477329E+10 0.877739E+09 0.00 0.877739E+09 0.00 0.00
February 0.105874E+09 0.451297E+10 0.108491E+10 0.00 0.108491E+10 0.00 0.00
March 0.604858E+09 0.338536E+10 0.166569E+10 0.00 0.166569E+10 0.00 0.00
April 0.122061E+10 0.236536E+10 0.193618E+10 5507101.70 0.193068E+10 0.00 0.00
May 0.249329E+10 0.150524E+10 0.265432E+10 88443495.07 0.256588E+10 0.00 0.00
June 0.339620E+10 0.784666E+09 0.272407E+10 0.146376E+09 0.257770E+10 0.00 0.00
July 0.389749E+10 0.449758E+09 0.272030E+10 98375305.77 0.262193E+10 0.00 0.00
August 0.341227E+10 0.612266E+09 0.241006E+10 28683108.84 0.238138E+10 0.00 0.00
September 0.188807E+10 0.121785E+10 0.175818E+10 329235.52 0.175785E+10 0.00 0.00
October 0.114298E+10 0.233734E+10 0.157230E+10 0.00 0.157230E+10 0.00 0.00
November 0.286674E+09 0.339381E+10 0.106724E+10 0.00 0.106724E+10 0.00 0.00
December 35250349.44 0.451409E+10 0.765622E+09 0.00 0.765622E+09 0.00 0.00
               
Annual Sum or Average 0.185448E+11 0.298520E+11 0.212366E+11 0.367714E+09 0.208689E+11 0.00 0.00
Minimum of Months 35250349.44 0.449758E+09 0.765622E+09 0.00 0.765622E+09 0.00 0.00
Maximum of Months 0.389749E+10 0.477329E+10 0.272407E+10 0.146376E+09 0.262193E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.763546E+09 0.296833E+10 0.122234E+10 0.490060E+09 0.732281E+09 0.00 0.00
February 0.120426E+10 0.272495E+10 0.171214E+10 0.798716E+09 0.913427E+09 0.00 0.00
March 0.211008E+10 0.219354E+10 0.241818E+10 0.102847E+10 0.138971E+10 0.00 0.00
April 0.284431E+10 0.153818E+10 0.280837E+10 0.123015E+10 0.157822E+10 0.00 0.00
May 0.407919E+10 0.102850E+10 0.351950E+10 0.140660E+10 0.211289E+10 0.00 0.00
June 0.413295E+10 0.538008E+09 0.315661E+10 0.114267E+10 0.201394E+10 0.00 0.00
July 0.465053E+10 0.307094E+09 0.327611E+10 0.118227E+10 0.209384E+10 0.00 0.00
August 0.521140E+10 0.413305E+09 0.368898E+10 0.166336E+10 0.202562E+10 0.00 0.00
September 0.332403E+10 0.792747E+09 0.266251E+10 0.119456E+10 0.146794E+10 0.00 0.00
October 0.275752E+10 0.151652E+10 0.249422E+10 0.113046E+10 0.136375E+10 0.00 0.00
November 0.118472E+10 0.214095E+10 0.149272E+10 0.573221E+09 0.919503E+09 0.00 0.00
December 0.809364E+09 0.278953E+10 0.120168E+10 0.564236E+09 0.637445E+09 0.00 0.00
               
Annual Sum or Average 0.330719E+11 0.189516E+11 0.296533E+11 0.124048E+11 0.172486E+11 0.00 0.00
Minimum of Months 0.763546E+09 0.307094E+09 0.120168E+10 0.490060E+09 0.637445E+09 0.00 0.00
Maximum of Months 0.521140E+10 0.296833E+10 0.368898E+10 0.166336E+10 0.211289E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.451148E+10 0.430082E+10 0.454073E+10 0.297330E+10 0.156743E+10 0.00 0.00
February 0.544786E+10 0.397459E+10 0.540948E+10 0.358064E+10 0.182885E+10 0.00 0.00
March 0.576150E+10 0.331323E+10 0.540327E+10 0.299891E+10 0.240436E+10 0.00 0.00
April 0.446144E+10 0.243956E+10 0.405750E+10 0.160446E+10 0.245304E+10 0.00 0.00
May 0.428980E+10 0.162135E+10 0.367432E+10 0.766406E+09 0.290792E+10 0.00 0.00
June 0.452116E+10 0.842427E+09 0.333701E+10 0.510096E+09 0.282691E+10 0.00 0.00
July 0.543358E+10 0.464443E+09 0.361445E+10 0.627829E+09 0.298662E+10 0.00 0.00
August 0.731090E+10 0.650817E+09 0.482670E+10 0.179030E+10 0.303640E+10 0.00 0.00
September 0.679345E+10 0.124819E+10 0.506813E+10 0.262144E+10 0.244668E+10 0.00 0.00
October 0.895197E+10 0.233159E+10 0.717434E+10 0.449882E+10 0.267551E+10 0.00 0.00
November 0.513792E+10 0.319402E+10 0.481431E+10 0.289122E+10 0.192309E+10 0.00 0.00
December 0.506884E+10 0.402507E+10 0.492147E+10 0.349392E+10 0.142756E+10 0.00 0.00
               
Annual Sum or Average 0.676899E+11 0.284061E+11 0.568417E+11 0.283574E+11 0.284844E+11 0.00 0.00
Minimum of Months 0.428980E+10 0.464443E+09 0.333701E+10 0.510096E+09 0.142756E+10 0.00 0.00
Maximum of Months 0.895197E+10 0.430082E+10 0.717434E+10 0.449882E+10 0.303640E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.760205E+09 0.303429E+10 0.120672E+10 0.494277E+09 0.712445E+09 0.00 0.00
February 0.111844E+10 0.284146E+10 0.160728E+10 0.705922E+09 0.901354E+09 0.00 0.00
March 0.238516E+10 0.218397E+10 0.262763E+10 0.121310E+10 0.141452E+10 0.00 0.00
April 0.285285E+10 0.158808E+10 0.277923E+10 0.118916E+10 0.159007E+10 0.00 0.00
May 0.389857E+10 0.106728E+10 0.334544E+10 0.127047E+10 0.207497E+10 0.00 0.00
June 0.468467E+10 0.570159E+09 0.354337E+10 0.142914E+10 0.211423E+10 0.00 0.00
July 0.487077E+10 0.327568E+09 0.342918E+10 0.129132E+10 0.213786E+10 0.00 0.00
August 0.539409E+10 0.445428E+09 0.379360E+10 0.175619E+10 0.203741E+10 0.00 0.00
September 0.329814E+10 0.831254E+09 0.260628E+10 0.113894E+10 0.146734E+10 0.00 0.00
October 0.301701E+10 0.156657E+10 0.267006E+10 0.129839E+10 0.137168E+10 0.00 0.00
November 0.818848E+09 0.219653E+10 0.121341E+10 0.350683E+09 0.862723E+09 0.00 0.00
December 0.713558E+09 0.286641E+10 0.111528E+10 0.482583E+09 0.632693E+09 0.00 0.00
               
Annual Sum or Average 0.338123E+11 0.195190E+11 0.299375E+11 0.126202E+11 0.173173E+11 0.00 0.00
Minimum of Months 0.713558E+09 0.327568E+09 0.111528E+10 0.350683E+09 0.632693E+09 0.00 0.00
Maximum of Months 0.539409E+10 0.303429E+10 0.379360E+10 0.175619E+10 0.213786E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 1.17 -0.7 -4.4 5.65 -10.4 36.91 88.07 0.05
February -0.2 -2.6 -7.5 5.07 -13.4 46.98 136.68 0.04
March 5.59 3.43 0.29 5.58 -4.1 68.24 153.73 0.03
April 10.94 8.00 4.75 4.99 0.53 82.64 161.98 0.05
May 16.05 12.31 9.14 4.42 7.77 109.28 173.60 0.03
June 21.71 18.08 15.84 4.92 13.23 112.36 186.51 0.01
July 25.05 21.76 20.26 4.06 17.39 114.46 172.96 0.02
August 24.79 19.84 17.14 4.19 14.42 95.56 226.16 0.00
September 19.96 15.96 13.24 3.91 10.59 73.65 166.08 0.03
October 14.02 11.03 7.95 4.86 2.64 61.34 179.75 0.00
November 7.31 4.98 2.14 5.60 -4.0 48.23 90.71 0.03
December 3.33 0.91 -2.8 5.64 -8.5 30.23 98.59 0.04
                 
Annual Sum or Average 12.55 9.49 6.43 4.91 2.28 73.48 153.05 0.03
Minimum of Months -0.2 -2.6 -7.5 3.91 -13.4 30.23 88.07 0.00
Maximum of Months 25.05 21.76 20.26 5.65 17.39 114.46 226.16 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.20 24-JAN-12:20 11.81 11.50 1.00 8.15 93.67 0.00
February 10.00 20-FEB-11:00 4.36 -3.3 2.60 -3.9 151.50 540.00
March 22.20 27-MAR-15:00 16.34 12.80 6.70 11.65 136.50 590.00
April 26.70 07-APR-12:00 16.40 9.40 6.20 11.65 179.00 713.50
May 30.00 30-MAY-12:00 18.00 10.60 5.20 17.39 233.50 730.00
June 36.70 19-JUN-11:00 24.28 19.40 5.20 24.83 185.00 771.50
July 33.90 07-JUL-11:00 23.31 18.90 3.60 23.82 331.00 570.00
August 33.90 24-AUG-14:00 20.23 12.80 8.80 21.61 240.00 432.00
September 31.10 01-SEP-13:00 17.34 8.30 4.60 18.46 182.00 662.00
October 25.00 04-OCT-12:00 18.54 15.00 5.20 11.27 171.50 695.00
November 17.80 04-NOV-12:20 12.57 8.50 3.60 6.15 182.50 595.67
December 12.20 17-DEC-12:20 4.65 -6.1 4.27 -4.7 53.17 801.67
                 
Annual Sum or Average                
Minimum of Months 10.00   4.36 -6.1 1.00 -4.7 53.17 0.00
Maximum of Months 36.70   24.28 19.40 8.80 24.83 331.00 801.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -12.2 02-JAN-04:00 -13.6 -19.4 2.60 -30.7 0.00 0.00
February -13.9 06-FEB-02:00 -15.3 -22.8 7.20 -34.1 0.00 0.00
March -5.0 23-MAR-03:00 -7.6 -14.4 1.50 -23.9 0.00 0.00
April 2.20 01-APR-03:00 0.57 -1.7 3.10 -6.6 0.00 0.00
May 6.10 01-MAY-04:00 4.33 2.20 3.60 -9.7 25.50 0.00
June 13.30 03-JUN-02:00 9.35 5.60 4.60 -2.1 0.00 0.00
July 18.30 02-JUL-02:00 17.54 17.20 0.00 5.33 0.00 0.00
August 15.00 08-AUG-04:00 12.47 10.60 3.10 3.06 0.00 0.00
September 10.00 24-SEP-05:00 8.56 7.20 2.60 -3.4 18.50 158.50
October 2.20 09-OCT-03:00 1.71 1.10 0.00 -13.7 0.00 0.00
November -4.4 24-NOV-05:00 -6.2 -10.0 1.50 -19.7 0.00 0.00
December -8.3 31-DEC-23:00 -10.6 -18.9 9.30 -26.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -13.9   -15.3 -22.8 0.00 -34.1 0.00 0.00
Maximum of Months 18.30   17.54 17.20 9.30 5.33 25.50 158.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.93 24-JAN-11:00 12.20 11.70 1.50 8.15 103.00 0.00
February 6.67 28-FEB-09:00 7.20 6.10 4.10 2.01 101.50 0.00
March 16.99 27-MAR-12:00 20.60 15.00 3.60 10.50 295.50 565.50
April 17.70 09-APR-10:00 21.70 15.60 4.10 14.84 244.50 281.50
May 20.43 31-MAY-12:00 26.10 17.80 4.10 17.03 214.00 772.00
June 24.96 15-JUN-11:00 31.10 22.80 5.20 22.47 380.00 460.00
July 26.10 08-JUL-11:00 32.20 23.90 5.20 22.47 354.00 501.50
August 25.84 03-AUG-13:00 30.00 24.40 6.20 20.57 298.00 500.00
September 23.57 07-SEP-13:00 27.20 22.20 6.20 15.02 148.00 730.50
October 19.76 25-OCT-10:00 25.00 17.20 7.70 14.84 189.00 308.50
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.26 25-DEC-08:00 10.60 10.00 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.67   7.20 6.10 1.50 2.01 43.00 0.00
Maximum of Months 26.10   32.20 24.40 8.20 22.47 380.00 772.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.70 18-JAN-15:00 12.20 11.93 14.90 8.15 22.00 2.00
February 6.10 28-FEB-10:20 7.03 6.58 3.43 1.87 109.83 0.00
March 15.00 27-MAR-12:20 18.00 16.18 3.93 10.11 271.83 611.17
April 15.60 09-APR-10:00 21.70 17.70 4.10 14.84 244.50 281.50
May 18.00 18-MAY-09:00 18.00 18.00 4.60 15.39 265.50 12.00
June 22.80 15-JUN-11:00 31.10 24.96 5.20 22.47 380.00 460.00
July 24.40 09-JUL-07:00 27.20 25.17 2.10 15.39 195.00 504.00
August 25.00 03-AUG-19:00 26.10 25.32 5.70 19.35 0.00 0.00
September 22.20 07-SEP-13:00 27.20 23.57 6.20 15.02 148.00 730.50
October 18.30 05-OCT-18:00 19.40 18.62 7.70 6.55 0.00 0.00
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.00 25-DEC-08:00 10.60 10.26 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.10   7.03 6.58 2.10 1.87 0.00 0.00
Maximum of Months 25.00   31.10 25.32 14.90 22.47 380.00 730.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 10.03 13.58 0.00
February 18.00 13.00 16.00 9.54 21.42 0.00
March 18.00 13.00 16.00 10.65 30.29 0.00
April 18.00 13.00 16.00 13.15 37.02 0.00
May 18.00 13.00 16.00 16.36 45.86 0.00
June 18.00 13.00 16.00 19.42 49.74 0.00
July 18.00 13.00 16.00 21.50 48.12 0.00
August 18.00 13.00 16.00 22.05 49.54 0.00
September 18.00 13.00 16.00 20.89 34.71 0.00
October 18.00 13.00 16.00 18.36 29.93 0.00
November 18.00 13.00 16.00 15.14 17.00 0.00
December 18.00 13.00 16.00 12.10 12.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 15.80 32.53 0.00
Minimum of Months 18.00 13.00 16.00 9.54 12.41 0.00
Maximum of Months 18.00 13.00 16.00 22.05 49.74 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.497281E+10 -0.472086E+10 0.00 0.00 744.00 0.00 -251947282.1 60.05 0.00 0.00
February 0.455540E+10 -0.433271E+10 0.00 0.00 672.00 0.00 -222689740.3 60.05 0.00 0.00
March 0.525554E+10 -0.501498E+10 0.00 0.00 744.00 0.00 -240559945.5 60.05 0.00 0.00
April 0.451540E+10 -0.428604E+10 0.00 0.00 720.00 0.00 -229360557.6 60.05 0.00 0.00
May 0.452177E+10 -0.428732E+10 0.00 0.00 744.00 0.00 -234451045.1 60.05 0.00 0.00
June 0.418244E+10 -0.395667E+10 0.00 0.00 720.00 0.00 -225763765.2 60.05 0.00 0.00
July 0.376814E+10 -0.353550E+10 0.00 0.00 744.00 0.00 -232638098.3 60.05 0.00 0.00
August 0.409050E+10 -0.385767E+10 0.00 0.00 744.00 0.00 -232827964.1 60.05 0.00 0.00
September 0.380553E+10 -0.358006E+10 0.00 0.00 720.00 0.00 -225473304.3 60.05 0.00 0.00
October 0.416966E+10 -0.393596E+10 0.00 0.00 744.00 0.00 -233705507.1 60.05 0.00 0.00
November 0.439776E+10 -0.416705E+10 0.00 0.00 720.00 0.00 -230708320.3 60.05 0.00 0.00
December 0.464367E+10 -0.439982E+10 0.00 0.00 744.00 0.00 -243843688.3 60.05 0.00 0.00
                     
Annual Sum or Average 0.528786E+11 -0.500746E+11 0.00 0.00 8760.00 0.00 -0.280397E+10 60.05 0.00 0.00
Minimum of Months 0.376814E+10 -0.501498E+10 0.00 0.00 672.00 0.00 -251947282.1 60.05 0.00 0.00
Maximum of Months 0.525554E+10 -0.353550E+10 0.00 0.00 744.00 0.00 -222689740.3 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.50 0.48 01-JAN-07:49 6502.60 36.69 196.17 241.50 3388.99 33.30 185.67 196.67
February 216.00 0.49 0.48 01-FEB-07:40 9259.17 37.54 210.00 258.33 2126.96 26.55 176.83 233.50
March 275.00 0.51 0.48 01-MAR-06:00 3276.47 21.57 57.00 318.33 1592.25 21.71 170.17 285.00
April 261.17 0.50 0.48 01-APR-14:39 2073.87 18.95 1.83 339.00 1227.90 21.18 149.83 299.00
May 372.00 0.51 0.48 01-MAY-05:00 1803.96 18.85 0.00 390.67 1014.36 21.02 225.17 347.50
June 351.83 0.50 0.48 01-JUN-05:40 1718.13 18.83 0.00 382.50 978.98 21.06 208.00 340.50
July 365.17 0.50 0.48 01-JUL-05:40 1896.16 19.09 1.00 390.33 1057.77 21.32 237.83 344.33
August 389.17 0.51 0.48 01-AUG-05:00 2107.07 19.07 7.83 370.67 1223.37 21.27 238.00 340.00
September 285.33 0.50 0.48 01-SEP-06:19 3805.78 21.30 36.50 323.83 1466.81 21.48 178.50 289.50
October 305.50 0.49 0.48 01-OCT-14:39 10128.99 36.12 283.50 307.00 2052.87 23.60 258.83 289.00
November 240.83 0.50 0.48 01-NOV-06:49 6447.57 36.31 235.17 257.17 2274.92 29.45 223.33 236.00
December 211.17 0.50 0.48 01-DEC-07:30 6063.17 36.57 198.50 243.33 5410.95 39.04 208.00 214.67
                         
Annual Sum or Average 3472.67 0.50     4187.37 25.32 1227.50 3822.67 1789.52 24.15 2460.17 3415.67
Minimum of Months 199.50 0.49 0.48   1718.13 18.83 0.00 241.50 978.98 21.02 149.83 196.67
Maximum of Months 389.17 0.51 0.48   10128.99 37.54 283.50 390.67 5410.95 39.04 258.83 347.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.52 0.48 01-JAN-07:49 1978.73 21.31 61.00 221.17 1125.41 23.69 88.67 158.83
February 216.00 0.50 0.48 01-FEB-07:40 2816.44 24.01 80.67 245.50 1626.39 24.64 92.17 207.17
March 275.00 0.52 0.48 01-MAR-06:49 2919.56 21.40 71.50 313.50 1635.57 22.57 77.67 260.17
April 261.17 0.50 0.48 01-APR-06:10 3823.68 22.28 80.67 341.33 1557.02 22.91 53.33 302.33
May 372.00 0.50 0.48 01-MAY-05:40 3178.29 21.15 99.17 396.67 1725.36 22.44 73.50 354.83
June 351.83 0.50 0.48 01-JUN-04:00 2835.16 20.46 80.67 387.17 1588.14 22.72 69.83 353.17
July 365.17 0.50 0.48 01-JUL-04:49 2929.24 21.08 89.67 396.00 1588.94 22.48 69.50 358.33
August 389.17 0.50 0.48 01-AUG-05:30 3910.50 23.17 128.17 373.17 1632.37 22.85 82.67 346.33
September 285.33 0.50 0.48 01-SEP-05:49 3397.81 22.17 82.67 320.67 1492.55 22.75 64.17 285.83
October 305.50 0.50 0.48 01-OCT-14:39 3017.01 23.06 91.17 293.50 1597.73 23.88 137.67 265.33
November 240.83 0.51 0.48 01-NOV-06:49 2042.55 22.03 73.33 244.50 1050.61 22.55 114.17 200.67
December 211.17 0.53 0.48 01-DEC-07:30 1895.84 23.20 81.17 221.17 1103.75 24.08 91.33 157.33
                         
Annual Sum or Average 3472.67 0.51     2983.12 22.03 1019.83 3754.33 1511.35 23.03 1014.67 3250.33
Minimum of Months 199.50 0.50 0.48   1895.84 20.46 61.00 221.17 1050.61 22.44 53.33 157.33
Maximum of Months 389.17 0.53 0.48   3910.50 24.01 128.17 396.67 1725.36 24.64 137.67 358.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.54 0.48 01-JAN-08:39 634.71 15.57 0.00 207.50 385.93 17.99 0.00 118.00
February 216.00 0.52 0.48 01-FEB-08:39 688.41 16.52 0.00 230.33 443.21 19.04 0.00 162.67
March 275.00 0.52 0.48 01-MAR-07:19 911.03 17.40 0.00 308.00 564.74 19.64 13.33 237.50
April 261.17 0.50 0.48 01-APR-14:39 1025.43 18.38 0.00 344.00 638.11 20.58 51.17 295.83
May 372.00 0.50 0.48 01-MAY-05:49 1322.13 19.16 7.50 403.67 759.55 21.28 168.33 363.17
June 351.83 0.49 0.48 01-JUN-04:00 1491.61 22.44 74.50 401.83 837.60 23.66 239.00 373.33
July 365.17 0.49 0.48 01-JUL-04:00 1468.07 20.28 26.83 407.50 829.27 23.22 244.50 371.50
August 389.17 0.50 0.48 01-AUG-05:49 1208.24 18.79 0.00 377.83 726.71 20.97 164.67 350.00
September 285.33 0.50 0.48 01-SEP-06:19 940.22 17.95 0.00 320.17 590.55 20.22 27.50 269.67
October 305.50 0.51 0.48 01-OCT-14:39 854.25 17.60 0.00 289.17 548.00 20.01 0.00 243.83
November 240.83 0.52 0.48 01-NOV-07:30 707.70 16.27 0.00 233.83 421.69 18.60 0.00 155.83
December 211.17 0.56 0.48 01-DEC-08:39 512.50 14.57 0.00 196.00 321.08 17.16 0.00 89.17
                         
Annual Sum or Average 3472.67 0.51     1043.72 18.29 108.83 3719.83 622.82 20.54 908.50 3030.50
Minimum of Months 199.50 0.49 0.48   512.50 14.57 0.00 196.00 321.08 17.16 0.00 89.17
Maximum of Months 389.17 0.56 0.48   1491.61 22.44 74.50 407.50 837.60 23.66 244.50 373.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.51 0.48 01-JAN-08:39 1970.59 23.24 73.33 228.67 1113.66 23.83 78.83 162.50
February 216.00 0.51 0.48 01-FEB-08:39 2197.29 21.43 57.00 244.33 1186.09 23.37 76.00 204.50
March 275.00 0.50 0.48 01-MAR-07:30 3178.88 23.68 95.83 317.00 1797.95 24.57 92.50 272.33
April 261.17 0.50 0.48 01-APR-14:39 3617.58 21.96 76.83 340.17 1503.45 21.51 40.33 299.67
May 372.00 0.50 0.48 01-MAY-06:10 3412.56 19.22 69.33 395.17 1516.69 19.00 0.00 357.17
June 351.83 0.50 0.48 01-JUN-05:00 3301.34 15.87 1.83 391.17 1787.28 19.18 2.50 351.83
July 365.17 0.50 0.48 01-JUL-05:49 3106.44 18.53 49.00 397.17 1665.56 19.30 6.17 355.83
August 389.17 0.50 0.48 01-AUG-06:10 3988.07 20.31 86.33 373.33 1740.05 19.43 19.50 346.33
September 285.33 0.50 0.48 01-SEP-06:40 3220.56 22.40 85.33 322.17 1683.18 23.13 68.50 284.67
October 305.50 0.50 0.48 01-OCT-14:39 3451.04 24.12 109.33 303.50 1464.97 23.44 119.17 275.83
November 240.83 0.51 0.48 01-NOV-07:30 1669.38 21.05 68.83 245.33 913.53 23.40 99.67 203.83
December 211.17 0.53 0.48 01-DEC-08:39 1561.79 21.16 67.50 220.17 890.50 23.26 76.33 162.67
                         
Annual Sum or Average 3472.67 0.50     3026.26 20.80 840.50 3778.17 1491.57 21.57 679.50 3277.17
Minimum of Months 199.50 0.50 0.48   1561.79 15.87 1.83 220.17 890.50 19.00 0.00 162.50
Maximum of Months 389.17 0.53 0.48   3988.07 24.12 109.33 397.17 1797.95 24.57 119.17 357.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.50 0.48 01-JAN-07:49 6326.56 36.47 196.17 238.33 3258.62 32.19 144.00 194.00
February 216.00 0.49 0.48 01-FEB-07:40 9075.85 37.27 210.00 256.83 2002.17 24.94 80.00 233.67
March 275.00 0.51 0.48 01-MAR-07:10 3153.97 18.16 45.83 318.33 1479.48 19.19 40.50 279.67
April 261.17 0.50 0.48 01-APR-14:39 1969.95 15.24 0.00 338.33 1152.51 18.82 7.67 295.00
May 372.00 0.51 0.48 01-MAY-05:00 1727.85 15.23 0.00 389.17 964.77 18.66 0.50 342.50
June 351.83 0.50 0.48 01-JUN-05:49 1648.46 15.22 0.00 380.33 935.04 18.73 0.00 335.67
July 365.17 0.50 0.48 01-JUL-05:49 1817.89 15.42 0.00 388.67 1007.82 18.91 1.83 341.00
August 389.17 0.51 0.48 01-AUG-05:00 2007.75 15.51 0.00 368.67 1154.27 19.00 19.33 335.83
September 285.33 0.50 0.48 01-SEP-06:19 3670.97 17.87 29.50 322.33 1365.47 18.97 20.33 287.00
October 305.50 0.49 0.48 01-OCT-14:39 9929.84 35.44 281.00 306.17 1907.88 20.87 46.33 287.33
November 240.83 0.50 0.48 01-NOV-06:49 6268.79 35.30 228.83 255.83 2152.12 27.59 121.17 234.00
December 211.17 0.51 0.48 01-DEC-07:40 5883.17 35.73 195.50 239.17 5278.82 38.86 208.00 212.00
                         
Annual Sum or Average 3472.67 0.50     4061.83 22.74 1186.83 3802.17 1699.27 22.02 689.67 3377.67
Minimum of Months 199.50 0.49 0.48   1648.46 15.22 0.00 238.33 935.04 18.66 0.00 194.00
Maximum of Months 389.17 0.51 0.48   9929.84 37.27 281.00 389.17 5278.82 38.86 208.00 342.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.52 0.48 01-JAN-07:49 1921.04 20.83 61.00 218.83 1081.84 23.47 82.50 156.00
February 216.00 0.51 0.48 01-FEB-07:40 2748.16 23.56 80.67 243.50 1572.21 24.44 82.67 202.67
March 275.00 0.52 0.48 01-MAR-06:49 2742.96 19.56 58.83 311.00 1573.44 22.36 67.83 252.67
April 261.17 0.50 0.48 01-APR-06:10 3732.76 21.83 80.67 338.83 1485.02 22.73 52.00 298.50
May 372.00 0.51 0.48 01-MAY-05:40 3083.31 20.70 99.17 395.67 1656.52 22.27 72.83 351.00
June 351.83 0.50 0.48 01-JUN-04:00 2751.88 19.99 80.67 385.00 1526.79 22.55 69.00 351.17
July 365.17 0.50 0.48 01-JUL-04:00 2838.36 20.58 89.17 394.33 1524.45 22.31 67.00 354.67
August 389.17 0.50 0.48 01-AUG-05:30 3767.85 21.40 111.67 371.00 1554.94 22.54 74.17 344.33
September 285.33 0.50 0.48 01-SEP-05:49 3312.24 21.69 82.67 319.67 1400.88 21.70 49.00 281.33
October 305.50 0.50 0.48 01-OCT-14:39 2932.16 22.58 91.17 291.00 1532.35 23.67 119.67 261.67
November 240.83 0.51 0.48 01-NOV-06:49 1976.18 21.37 72.00 242.17 1002.42 22.32 102.00 197.00
December 211.17 0.53 0.48 01-DEC-07:30 1757.84 20.40 64.00 214.83 1064.80 23.86 86.33 152.17
                         
Annual Sum or Average 3472.67 0.51     2883.09 21.15 971.67 3725.83 1447.10 22.76 925.00 3203.17
Minimum of Months 199.50 0.50 0.48   1757.84 19.56 58.83 214.83 1002.42 21.70 49.00 152.17
Maximum of Months 389.17 0.53 0.48   3767.85 23.56 111.67 395.67 1656.52 24.44 119.67 354.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.54 0.48 01-JAN-08:50 610.06 12.00 0.00 203.17 372.57 15.62 0.00 112.33
February 216.00 0.52 0.48 01-FEB-08:39 662.22 13.10 0.00 226.67 429.60 16.87 0.00 157.67
March 275.00 0.52 0.48 01-MAR-07:30 878.27 14.16 0.00 306.50 547.39 17.66 0.00 229.83
April 261.17 0.50 0.48 01-APR-14:39 989.39 15.16 0.00 342.50 619.11 18.71 0.00 291.33
May 372.00 0.50 0.48 01-MAY-05:49 1274.56 15.68 3.00 401.83 732.99 19.16 36.67 359.00
June 351.83 0.49 0.48 01-JUN-05:10 1434.32 18.89 62.67 398.83 807.88 21.82 76.67 371.50
July 365.17 0.49 0.48 01-JUL-04:00 1411.99 15.75 0.00 405.00 799.54 21.32 63.17 368.17
August 389.17 0.50 0.48 01-AUG-05:49 1165.38 15.59 0.00 377.50 703.61 19.10 8.17 346.50
September 285.33 0.51 0.48 01-SEP-06:19 906.59 14.77 0.00 317.83 572.88 18.32 0.00 263.83
October 305.50 0.51 0.48 01-OCT-14:39 821.12 14.41 0.00 286.67 530.68 18.03 0.00 239.83
November 240.83 0.52 0.48 01-NOV-07:30 680.86 12.60 0.00 230.83 406.95 16.20 0.00 146.83
December 211.17 0.56 0.48 01-DEC-08:50 492.02 10.88 0.00 190.33 310.15 14.69 0.00 84.17
                         
Annual Sum or Average 3472.67 0.51     1004.99 14.78 65.67 3687.67 602.17 18.51 184.67 2971.00
Minimum of Months 199.50 0.49 0.48   492.02 10.88 0.00 190.33 310.15 14.69 0.00 84.17
Maximum of Months 389.17 0.56 0.48   1434.32 18.89 62.67 405.00 807.88 21.82 76.67 371.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.52 0.48 01-JAN-08:39 1832.28 20.59 57.17 224.50 1070.81 23.70 77.00 158.33
February 216.00 0.51 0.48 01-FEB-08:39 2128.10 21.00 57.00 242.83 1100.33 22.17 66.50 199.67
March 275.00 0.50 0.48 01-MAR-07:30 3094.28 23.30 95.83 316.17 1729.71 24.39 88.83 265.00
April 261.17 0.50 0.48 01-APR-14:39 3526.55 21.53 76.83 337.83 1431.94 21.36 38.83 297.17
May 372.00 0.50 0.48 01-MAY-06:19 3325.85 18.75 69.17 393.50 1452.61 18.82 0.00 353.17
June 351.83 0.50 0.48 01-JUN-05:00 3198.87 15.34 1.83 389.50 1714.55 19.00 1.50 347.67
July 365.17 0.50 0.48 01-JUL-05:00 3008.69 18.05 49.00 395.33 1596.86 19.13 4.50 352.33
August 389.17 0.50 0.48 01-AUG-06:10 3842.14 19.86 86.33 371.17 1664.28 19.28 14.83 344.17
September 285.33 0.50 0.48 01-SEP-06:40 3136.61 21.99 85.33 320.83 1615.36 23.01 66.50 280.50
October 305.50 0.50 0.48 01-OCT-14:39 3358.70 23.74 109.33 302.17 1395.36 23.33 115.83 272.83
November 240.83 0.51 0.48 01-NOV-07:30 1619.51 20.64 68.83 243.67 874.07 23.11 94.33 197.83
December 211.17 0.53 0.48 01-DEC-08:50 1513.50 20.77 67.50 218.00 820.02 21.77 65.50 155.33
                         
Annual Sum or Average 3472.67 0.50     2932.74 20.23 824.17 3755.50 1424.33 21.26 634.17 3224.00
Minimum of Months 199.50 0.50 0.48   1513.50 15.34 1.83 218.00 820.02 18.82 0.00 155.33
Maximum of Months 389.17 0.53 0.48   3842.14 23.74 109.33 395.33 1729.71 24.39 115.83 353.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.50 0.48 01-JAN-07:49 6326.55 36.47 196.17 238.33 3258.51 32.19 144.00 193.83
February 216.00 0.49 0.48 01-FEB-07:40 9075.80 37.27 210.00 256.83 2002.06 24.94 80.00 233.67
March 275.00 0.51 0.48 01-MAR-07:10 3153.85 18.16 45.83 318.33 1479.37 19.19 40.50 279.67
April 261.17 0.50 0.48 01-APR-14:39 1969.85 15.25 0.00 338.33 1152.43 18.82 7.67 295.00
May 372.00 0.51 0.48 01-MAY-05:00 1727.75 15.24 0.00 389.17 964.70 18.67 0.83 342.50
June 351.83 0.50 0.48 01-JUN-05:49 1648.37 15.22 0.00 380.33 934.97 18.73 0.00 335.67
July 365.17 0.50 0.48 01-JUL-05:49 1817.78 15.42 0.00 388.67 1007.74 18.91 1.83 341.00
August 389.17 0.51 0.48 01-AUG-05:00 2007.65 15.51 0.00 368.67 1154.19 19.00 19.50 335.83
September 285.33 0.50 0.48 01-SEP-06:19 3670.85 17.87 29.50 322.33 1365.37 18.97 20.33 287.00
October 305.50 0.49 0.48 01-OCT-14:39 9929.75 35.44 281.00 306.17 1907.75 20.87 46.33 287.33
November 240.83 0.50 0.48 01-NOV-06:49 6268.75 35.30 228.83 255.83 2152.00 27.59 121.17 234.00
December 211.17 0.51 0.48 01-DEC-07:40 5883.19 35.73 195.50 239.17 5278.73 38.86 208.00 212.00
                         
Annual Sum or Average 3472.67 0.50     4061.74 22.74 1186.83 3802.17 1699.18 22.02 690.17 3377.50
Minimum of Months 199.50 0.49 0.48   1648.37 15.22 0.00 238.33 934.97 18.67 0.00 193.83
Maximum of Months 389.17 0.51 0.48   9929.75 37.27 281.00 389.17 5278.73 38.86 208.00 342.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.52 0.48 01-JAN-07:49 1921.02 20.83 61.00 218.83 1081.80 23.47 82.50 156.00
February 216.00 0.51 0.48 01-FEB-07:40 2748.14 23.56 80.67 243.50 1572.16 24.44 82.67 202.67
March 275.00 0.52 0.48 01-MAR-06:49 2742.93 19.56 58.83 311.00 1573.37 22.36 67.83 252.67
April 261.17 0.50 0.48 01-APR-06:10 3732.71 21.83 80.67 338.83 1484.95 22.73 52.00 298.50
May 372.00 0.51 0.48 01-MAY-05:40 3083.25 20.70 99.17 395.67 1656.44 22.27 72.83 351.00
June 351.83 0.50 0.48 01-JUN-04:00 2751.81 19.99 80.67 385.00 1526.72 22.56 69.00 351.00
July 365.17 0.50 0.48 01-JUL-04:00 2838.80 20.62 89.67 394.33 1524.37 22.31 67.00 354.67
August 389.17 0.50 0.48 01-AUG-05:30 3815.01 22.74 128.17 372.00 1554.86 22.54 74.33 344.33
September 285.33 0.50 0.48 01-SEP-05:49 3312.20 21.70 82.67 319.67 1400.81 21.70 49.00 281.33
October 305.50 0.50 0.48 01-OCT-14:39 2932.14 22.59 91.17 291.00 1532.29 23.67 119.67 261.67
November 240.83 0.51 0.48 01-NOV-06:49 1976.15 21.37 72.00 242.17 1002.36 22.32 102.00 197.00
December 211.17 0.53 0.48 01-DEC-07:30 1757.83 20.40 64.00 214.83 1064.76 23.86 86.33 152.17
                         
Annual Sum or Average 3472.67 0.51     2888.39 21.30 988.67 3726.83 1447.03 22.76 925.17 3203.00
Minimum of Months 199.50 0.50 0.48   1757.83 19.56 58.83 214.83 1002.36 21.70 49.00 152.17
Maximum of Months 389.17 0.53 0.48   3815.01 23.56 128.17 395.67 1656.44 24.44 119.67 354.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.54 0.48 01-JAN-08:50 610.05 12.00 0.00 203.17 372.54 15.62 0.00 112.17
February 216.00 0.52 0.48 01-FEB-08:39 662.22 13.10 0.00 226.67 429.58 16.87 0.00 157.67
March 275.00 0.52 0.48 01-MAR-07:30 878.25 14.16 0.00 306.50 547.36 17.66 0.00 229.83
April 261.17 0.50 0.48 01-APR-14:39 989.37 15.16 0.00 342.50 619.08 18.71 0.00 291.33
May 372.00 0.50 0.48 01-MAY-05:49 1274.51 15.68 3.00 401.83 732.94 19.17 36.67 359.00
June 351.83 0.49 0.48 01-JUN-05:10 1434.27 18.89 62.83 398.83 807.83 21.83 76.67 371.50
July 365.17 0.49 0.48 01-JUL-04:00 1411.94 15.75 0.00 405.00 799.49 21.32 63.33 368.17
August 389.17 0.50 0.48 01-AUG-05:49 1165.35 15.59 0.00 377.50 703.57 19.10 8.17 346.50
September 285.33 0.51 0.48 01-SEP-06:19 906.57 14.77 0.00 317.83 572.84 18.32 0.00 263.83
October 305.50 0.51 0.48 01-OCT-14:39 821.11 14.41 0.00 286.67 530.65 18.03 0.00 239.83
November 240.83 0.52 0.48 01-NOV-07:30 680.84 12.61 0.00 230.83 406.92 16.20 0.00 146.83
December 211.17 0.56 0.48 01-DEC-08:50 492.02 10.88 0.00 190.33 310.14 14.69 0.00 84.17
                         
Annual Sum or Average 3472.67 0.51     1004.96 14.78 65.83 3687.67 602.13 18.51 184.83 2970.83
Minimum of Months 199.50 0.49 0.48   492.02 10.88 0.00 190.33 310.14 14.69 0.00 84.17
Maximum of Months 389.17 0.56 0.48   1434.27 18.89 62.83 405.00 807.83 21.83 76.67 371.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.52 0.48 01-JAN-08:39 1832.26 20.59 57.17 224.50 1070.77 23.70 77.17 158.33
February 216.00 0.51 0.48 01-FEB-08:39 2128.09 21.01 57.00 242.83 1100.28 22.17 66.50 199.67
March 275.00 0.50 0.48 01-MAR-07:30 3094.25 23.30 95.83 316.17 1729.64 24.40 88.83 265.00
April 261.17 0.50 0.48 01-APR-14:39 3526.51 21.53 76.83 337.83 1431.87 21.36 38.83 297.17
May 372.00 0.50 0.48 01-MAY-06:19 3325.77 18.75 69.17 393.50 1452.53 18.82 0.00 353.17
June 351.83 0.50 0.48 01-JUN-05:00 3198.79 15.34 1.83 389.50 1714.46 19.00 1.50 347.50
July 365.17 0.50 0.48 01-JUL-05:00 3008.61 18.05 49.00 395.33 1596.77 19.13 4.50 352.33
August 389.17 0.50 0.48 01-AUG-06:10 3842.09 19.86 86.33 371.17 1664.20 19.28 15.00 344.17
September 285.33 0.50 0.48 01-SEP-06:40 3136.57 21.99 85.33 320.83 1615.29 23.01 66.50 280.50
October 305.50 0.50 0.48 01-OCT-14:39 3358.68 23.74 109.33 302.17 1395.29 23.33 115.83 272.83
November 240.83 0.51 0.48 01-NOV-07:30 1619.48 20.64 68.83 243.67 874.02 23.11 94.50 197.83
December 211.17 0.53 0.48 01-DEC-08:50 1513.49 20.77 67.50 218.00 819.98 21.77 65.50 155.33
                         
Annual Sum or Average 3472.67 0.50     2932.70 20.23 824.17 3755.50 1424.26 21.26 634.67 3223.83
Minimum of Months 199.50 0.50 0.48   1513.49 15.34 1.83 218.00 819.98 18.82 0.00 155.33
Maximum of Months 389.17 0.53 0.48   3842.09 23.74 109.33 395.33 1729.64 24.40 115.83 353.17



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT HEATING COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.111596E+11 19520.01 02-JAN-07:20 0.00 0.00 0.00 0.00 0.00
February 0.113183E+11 19607.82 06-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.661780E+10 17753.06 23-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.151178E+10 9155.71 03-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 13376422.52 2672.31 01-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 597752.24 4.77 26-JUN-14:10 0.00 0.00 0.00 0.00 0.00
July 1288119.04 5.05 17-JUL-14:10 0.00 0.00 0.00 0.00 0.00
August 1240243.19 4.72 09-AUG-14:40 0.00 0.00 0.00 0.00 0.00
September 454841.45 4.37 01-SEP-09:20 0.00 0.00 0.00 0.00 0.00
October 0.149565E+09 6343.97 28-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.387732E+10 17921.39 24-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.892680E+10 17903.02 22-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.435781E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 454841.45 4.37   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.113183E+11 19607.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.897079E+09 11323.13 02-JAN-07:20 0.00 0.00 0.00 0.00 0.00
February 762997.87 630.00 06-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.897842E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.897079E+09 11323.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.457614E+10 8105.83 31-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.369720E+10 8425.30 06-FEB-08:02 0.00 0.00 0.00 0.00 0.00
March 0.233119E+10 7665.96 23-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.119342E+10 7711.08 11-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.374091E+09 7699.09 15-MAY-06:07 0.00 0.00 0.00 0.00 0.00
June 1590200.58 1951.74 02-JUN-06:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 11452689.58 5265.74 20-SEP-06:07 0.00 0.00 0.00 0.00 0.00
October 0.216640E+09 7695.94 27-OCT-06:04 0.00 0.00 0.00 0.00 0.00
November 0.147727E+10 7670.86 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.285038E+10 7681.28 22-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.167294E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.457614E+10 8425.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.173133E+10 5985.26 31-JAN-07:11 0.00 0.00 0.00 0.00 0.00
February 0.111801E+10 6248.30 06-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.225498E+09 5693.23 18-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 41632674.47 5678.79 22-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.132417E+09 5684.09 21-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.570116E+09 5687.89 26-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.381901E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.173133E+10 6248.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.327358E+10 6855.21 31-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.270289E+10 7123.29 06-FEB-08:02 0.00 0.00 0.00 0.00 0.00
March 0.801888E+09 6476.39 08-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.136772E+09 6475.88 04-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.345530E+09 6481.68 24-NOV-07:12 0.00 0.00 0.00 0.00 0.00
December 0.128917E+10 6481.51 26-DEC-06:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.854983E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.327358E+10 7123.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.188711E+10 6088.45 31-JAN-07:11 0.00 0.00 0.00 0.00 0.00
February 0.135065E+10 6380.70 06-FEB-08:02 0.00 0.00 0.00 0.00 0.00
March 0.234575E+09 5789.89 01-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 47482347.90 5787.25 03-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.176094E+09 5781.90 21-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.659732E+09 5787.75 14-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.435565E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.188711E+10 6380.70   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID HEATING COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.113077E+11 20112.51 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.113025E+11 19931.97 06-FEB-07:35 0.00 0.00 0.00 0.00 0.00
March 0.667646E+10 18724.38 23-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.178742E+10 10051.82 03-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 20506989.17 3322.91 01-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 494058.61 4.46 26-JUN-14:50 0.00 0.00 0.00 0.00 0.00
July 1107581.26 4.72 24-JUL-15:00 0.00 0.00 0.00 0.00 0.00
August 1128946.76 4.91 14-AUG-09:50 0.00 0.00 0.00 0.00 0.00
September 332229.88 4.69 05-SEP-15:50 0.00 0.00 0.00 0.00 0.00
October 0.300569E+09 6682.60 28-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.426507E+10 17726.95 24-NOV-07:12 0.00 0.00 0.00 0.00 0.00
December 0.913239E+10 18811.89 22-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.447956E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 332229.88 4.46   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.113077E+11 20112.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.203539E+10 16397.59 02-JAN-11:20 0.00 0.00 0.00 0.00 0.00
February 0.726227E+09 15601.61 06-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 18275243.06 15521.03 01-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 92675923.96 15540.60 27-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.225038E+09 15525.52 11-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.309761E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.203539E+10 16397.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.177392E+10 8476.10 14-JAN-07:15 0.00 0.00 0.00 0.00 0.00
February 0.106794E+10 8922.64 06-FEB-08:02 0.00 0.00 0.00 0.00 0.00
March 0.205300E+09 8244.90 20-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 34259579.30 8226.21 03-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.238342E+09 8233.90 20-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.798609E+09 8253.04 13-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.411837E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.177392E+10 8922.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.150028E+10 6607.65 02-JAN-11:05 0.00 0.00 0.00 0.00 0.00
February 0.932895E+09 6635.85 06-FEB-07:35 0.00 0.00 0.00 0.00 0.00
March 0.159365E+09 6264.71 20-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 16001853.21 6236.53 03-APR-05:11 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.233114E+09 6251.07 21-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.684608E+09 6255.88 28-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.352626E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.150028E+10 6635.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.290144E+10 7315.17 02-JAN-11:20 0.00 0.00 0.00 0.00 0.00
February 0.211685E+10 7537.32 06-FEB-08:10 0.00 0.00 0.00 0.00 0.00
March 0.403894E+09 6932.99 01-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 44004292.15 6909.54 03-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.502987E+09 6951.02 24-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.141809E+10 6934.49 11-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.738727E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.290144E+10 7537.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.172213E+10 6719.06 02-JAN-11:20 0.00 0.00 0.00 0.00 0.00
February 0.119427E+10 6926.91 06-FEB-08:10 0.00 0.00 0.00 0.00 0.00
March 0.185846E+09 6341.42 10-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 26089936.22 6339.39 03-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.294099E+09 6345.35 20-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.813393E+09 6344.99 28-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.423583E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.172213E+10 6926.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP HEATING COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.116409E+11 19443.47 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.115884E+11 19418.91 06-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.705980E+10 16389.57 23-MAR-06:12 0.00 0.00 0.00 0.00 0.00
April 0.209466E+10 10974.36 01-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 37375791.64 4289.59 01-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 664492.70 5.38 26-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 1260291.08 5.48 07-JUL-14:30 0.00 0.00 0.00 0.00 0.00
August 1273166.26 5.42 16-AUG-14:40 0.00 0.00 0.00 0.00 0.00
September 1462228.58 548.19 30-SEP-06:05 0.00 0.00 0.00 0.00 0.00
October 0.460355E+09 8770.87 28-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.464252E+10 17369.22 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.968786E+10 16493.76 15-DEC-07:06 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.472166E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 664492.70 5.38   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.116409E+11 19443.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.506370E+10 22673.17 02-JAN-09:50 0.00 0.00 0.00 0.00 0.00
February 0.343108E+10 22732.41 06-FEB-08:02 0.00 0.00 0.00 0.00 0.00
March 0.464111E+09 21722.90 07-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 70046409.75 21696.59 03-APR-06:04 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.982798E+09 21731.85 29-NOV-07:04 0.00 0.00 0.00 0.00 0.00
December 0.226444E+10 21728.44 04-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.122762E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.506370E+10 22732.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.299615E+10 10268.59 14-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 0.214338E+10 10291.31 09-FEB-07:09 0.00 0.00 0.00 0.00 0.00
March 0.659164E+09 9742.08 01-MAR-06:13 0.00 0.00 0.00 0.00 0.00
April 0.191412E+09 9727.33 03-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 1701665.11 2811.00 01-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 9765203.90 8462.56 28-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.711022E+09 9743.01 27-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.178055E+10 9747.54 11-DEC-06:09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.849315E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.299615E+10 10291.31   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.245368E+10 7521.20 14-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 0.177540E+10 7386.60 08-FEB-07:09 0.00 0.00 0.00 0.00 0.00
March 0.468330E+09 7135.19 01-MAR-06:13 0.00 0.00 0.00 0.00 0.00
April 0.112942E+09 7118.91 01-APR-05:12 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 11569328.40 7112.95 31-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.608155E+09 7132.54 21-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.148209E+10 7138.61 11-DEC-06:09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.691216E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.245368E+10 7521.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.444427E+10 8906.79 31-JAN-08:04 0.00 0.00 0.00 0.00 0.00
February 0.362756E+10 9138.54 06-FEB-08:25 0.00 0.00 0.00 0.00 0.00
March 0.108401E+10 8485.15 23-MAR-06:12 0.00 0.00 0.00 0.00 0.00
April 0.230600E+09 8308.93 03-APR-06:04 0.00 0.00 0.00 0.00 0.00
May 750984.11 1847.16 01-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 29890647.94 8302.10 10-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.125234E+10 8475.12 24-NOV-07:18 0.00 0.00 0.00 0.00 0.00
December 0.286528E+10 8464.67 15-DEC-07:06 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.135347E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.444427E+10 9138.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.269972E+10 7913.48 31-JAN-07:50 0.00 0.00 0.00 0.00 0.00
February 0.213129E+10 8184.66 06-FEB-08:25 0.00 0.00 0.00 0.00 0.00
March 0.561993E+09 7430.38 01-MAR-06:13 0.00 0.00 0.00 0.00 0.00
April 0.133565E+09 7418.37 03-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 906605.26 1549.16 01-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 15435646.13 7407.50 31-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.748388E+09 7578.15 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.167823E+10 7427.28 13-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.796953E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.269972E+10 8184.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.390328E+09 0.263875E+09 20076.27 27-MAR-16:00 16323.35 0.00
April 0.00 0.00 0.355549E+10 0.316111E+10 36832.47 07-APR-14:30 36832.47 0.00
May 0.00 0.00 0.142683E+11 0.120152E+11 73164.59 30-MAY-14:20 73164.59 0.00
June 0.00 0.00 0.507730E+11 0.386187E+11 96993.89 19-JUN-06:03 70141.53 0.00
July 0.00 0.00 0.736567E+11 0.533849E+11 101094.71 22-JUL-06:03 57543.38 0.00
August 0.00 0.00 0.757497E+11 0.593058E+11 99593.35 17-AUG-06:03 62787.43 0.00
September 0.00 0.00 0.392336E+11 0.312979E+11 98858.46 07-SEP-06:03 61951.83 0.00
October 0.00 0.00 0.177031E+11 0.124441E+11 58936.03 04-OCT-15:20 45853.39 0.00
November 0.00 0.00 0.517289E+09 0.448438E+09 12162.18 06-NOV-12:00 12162.18 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.275848E+12 0.210940E+12       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.757497E+11 0.593058E+11 101094.71   73164.59 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.387773E+09 0.265031E+09 19829.96 27-MAR-16:00 16335.04 0.00
April 0.00 0.00 0.415834E+10 0.376140E+10 44142.60 07-APR-14:05 44142.60 0.00
May 0.00 0.00 0.150636E+11 0.129247E+11 77304.64 30-MAY-14:05 77304.64 0.00
June 0.00 0.00 0.496504E+11 0.382456E+11 97589.20 27-JUN-06:03 58932.58 0.00
July 0.00 0.00 0.704051E+11 0.511096E+11 100844.01 22-JUL-05:03 57051.21 0.00
August 0.00 0.00 0.702807E+11 0.552194E+11 98372.13 17-AUG-06:03 60162.34 0.00
September 0.00 0.00 0.350338E+11 0.278348E+11 80398.57 06-SEP-06:03 53133.32 0.00
October 0.00 0.00 0.153277E+11 0.107602E+11 57054.35 04-OCT-14:05 44859.49 0.00
November 0.00 0.00 0.366993E+09 0.310628E+09 9175.68 03-NOV-14:05 9175.68 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.260674E+12 0.200431E+12       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.704051E+11 0.552194E+11 100844.01   77304.64 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 365002.76 329120.92 198.99 30-JAN-05:30 170.93 0.00
February 0.00 0.00 76454.15 70901.71 205.41 05-FEB-09:30 187.72 0.00
March 0.00 0.00 0.478201E+09 0.341393E+09 21059.80 27-MAR-16:00 16524.83 0.00
April 0.00 0.00 0.442743E+10 0.397133E+10 47633.86 07-APR-14:30 47633.86 0.00
May 0.00 0.00 0.159106E+11 0.136679E+11 85061.11 30-MAY-14:10 85061.11 0.00
June 0.00 0.00 0.529443E+11 0.410323E+11 107324.67 19-JUN-06:03 75072.89 0.00
July 0.00 0.00 0.752831E+11 0.555946E+11 113615.32 22-JUL-05:03 59653.48 0.00
August 0.00 0.00 0.747777E+11 0.594985E+11 101386.16 05-AUG-05:03 65973.70 0.00
September 0.00 0.00 0.357133E+11 0.280936E+11 81808.84 01-SEP-14:20 81808.84 0.00
October 0.00 0.00 0.147839E+11 0.102275E+11 59240.14 04-OCT-14:00 47904.34 0.00
November 0.00 0.00 0.315152E+09 0.253249E+09 7752.95 03-NOV-14:00 7752.95 0.00
December 0.00 0.00 90671.00 81671.48 151.12 31-DEC-09:20 136.12 0.00
                 
Annual Sum or Average 0.00 0.00 0.274634E+12 0.212681E+12       0.00
Minimum of Months 0.00 0.00 76454.15 70901.71 151.12   136.12 0.00
Maximum of Months 0.00 0.00 0.752831E+11 0.594985E+11 113615.32   85061.11 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 27449.18 195683.51 02-JAN-07:10
February 0.00 0.00 01-FEB-00:10 25525.62 184996.26 06-FEB-07:10
March 0.00 0.00 01-MAR-00:10 10426.81 183162.08 24-MAR-06:01
April 0.00 0.00 01-APR-00:10 2939.26 169664.73 04-APR-06:02
May 0.00 0.00 01-MAY-00:10 166.00 21619.04 01-MAY-06:05
June 0.00 0.00 01-JUN-00:10 0.81 1215.32 02-JUN-06:10
July 0.00 0.00 01-JUL-00:10 0.96 7.21 25-JUL-16:20
August 0.00 0.00 01-AUG-00:10 0.98 7.69 18-AUG-10:30
September 0.00 0.00 01-SEP-00:10 4.40 10847.19 20-SEP-06:07
October 0.00 0.00 01-OCT-00:10 442.30 77735.21 28-OCT-06:03
November 0.00 0.00 01-NOV-00:10 7876.65 176340.25 28-NOV-07:02
December 0.00 0.00 01-DEC-00:10 17462.34 176770.26 20-DEC-07:02
             
Annual Sum or Average 0.00     7599.33    
Minimum of Months 0.00 0.00   0.81 7.21  
Maximum of Months 0.00 0.00   27449.18 195683.51  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 1753.16 6437.55 31-JAN-13:00
February 0.00 0.00 01-FEB-00:10 1781.52 6446.37 08-FEB-12:20
March 0.00 0.00 01-MAR-00:10 1862.65 6396.62 01-MAR-12:40
April 0.00 0.00 01-APR-00:10 1644.31 6126.53 03-APR-11:10
May 0.00 0.00 01-MAY-00:10 1591.41 5771.12 01-MAY-11:13
June 0.00 0.00 01-JUN-00:10 1517.24 5345.01 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 1311.24 4990.78 03-JUL-11:40
August 0.00 0.00 01-AUG-00:10 1431.13 4874.11 31-AUG-12:00
September 0.00 0.00 01-SEP-00:10 1372.29 5103.58 29-SEP-11:20
October 0.00 0.00 01-OCT-00:10 1460.48 5503.72 31-OCT-11:10
November 0.00 0.00 01-NOV-00:10 1598.39 5916.29 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 1633.52 6246.35 29-DEC-12:20
             
Annual Sum or Average 0.00     1578.63    
Minimum of Months 0.00 0.00   1311.24 4874.11  
Maximum of Months 0.00 0.00   1862.65 6446.37  



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_BOT FAN

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.113803E+10 0.29 2127.62 02-JAN-05:02 0.76
February 0.937537E+09 0.28 1376.91 01-FEB-07:01 0.61
March 0.115073E+10 0.29 1556.14 29-MAR-15:30 0.64
April 0.142328E+10 0.30 4067.02 10-APR-15:20 1.09
May 0.233151E+10 0.37 8184.24 30-MAY-14:30 1.67
June 0.399798E+10 0.49 9035.97 19-JUN-05:02 1.78
July 0.515186E+10 0.55 9035.97 07-JUL-06:03 1.78
August 0.570868E+10 0.59 9035.97 02-AUG-06:03 1.78
September 0.366099E+10 0.46 9035.97 05-SEP-05:12 1.79
October 0.284242E+10 0.39 6027.53 16-OCT-15:30 1.38
November 0.125692E+10 0.28 3046.29 02-NOV-14:30 0.92
December 0.993829E+09 0.27 1376.91 01-DEC-07:02 0.61
           
Annual Sum or Average 0.305938E+11 0.38      
Minimum of Months 0.937537E+09 0.27 1376.91   0.61
Maximum of Months 0.570868E+10 0.59 9035.97   1.79



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_MID FAN

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.108661E+10 0.29 2280.82 02-JAN-05:02 0.80
February 0.941785E+09 0.28 2280.82 01-FEB-07:01 0.79
March 0.117090E+10 0.30 2280.82 01-MAR-07:02 0.79
April 0.148901E+10 0.31 5308.70 10-APR-14:05 1.30
May 0.251508E+10 0.39 8807.17 30-MAY-10:10 1.78
June 0.401531E+10 0.50 8807.17 19-JUN-05:02 1.78
July 0.491153E+10 0.54 8807.17 08-JUL-06:03 1.78
August 0.540473E+10 0.58 8807.17 02-AUG-06:03 1.78
September 0.309316E+10 0.43 8807.17 05-SEP-05:12 1.78
October 0.223820E+10 0.36 5861.77 04-OCT-15:50 1.37
November 0.105928E+10 0.27 2711.69 03-NOV-14:05 0.87
December 0.976513E+09 0.27 2280.82 07-DEC-07:01 0.79
           
Annual Sum or Average 0.289021E+11 0.38      
Minimum of Months 0.941785E+09 0.27 2280.82   0.79
Maximum of Months 0.540473E+10 0.58 8807.17   1.78



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_TOP FAN

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.129880E+10 0.34 2272.22 01-JAN-01:23 0.73
February 0.112121E+10 0.32 2272.22 01-FEB-06:01 0.73
March 0.123118E+10 0.31 2272.22 01-MAR-06:11 0.73
April 0.147466E+10 0.32 4529.38 07-APR-14:50 1.07
May 0.240660E+10 0.37 9413.03 30-MAY-14:10 1.69
June 0.384730E+10 0.46 10252.91 19-JUN-05:02 1.78
July 0.476915E+10 0.50 9133.91 31-JUL-05:12 1.65
August 0.523158E+10 0.53 9827.61 14-AUG-05:12 1.73
September 0.280052E+10 0.39 8327.20 05-SEP-06:03 1.56
October 0.193480E+10 0.33 5204.50 04-OCT-15:40 1.16
November 0.108961E+10 0.29 2272.22 15-NOV-07:02 0.73
December 0.109789E+10 0.30 2272.22 01-DEC-07:02 0.73
           
Annual Sum or Average 0.283033E+11 0.37      
Minimum of Months 0.108961E+10 0.29 2272.22   0.73
Maximum of Months 0.523158E+10 0.53 10252.91   1.78



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.497569E+09 0.452291E+09 760.01 02-JAN-07:01 690.85 690.85 41.89 2.47
February 0.433604E+09 0.394146E+09 722.65 06-FEB-07:10 656.89 656.89 41.13 2.34
March 0.211436E+09 0.192195E+09 654.08 23-MAR-06:01 594.56 594.56 39.53 2.09
April 57659437.66 52412428.84 601.73 03-APR-06:01 546.97 546.97 37.06 1.73
May 5640032.27 5126789.33 203.07 01-MAY-06:05 184.59 184.59 38.53 0.24
June 25091.39 22808.07 15.19 02-JUN-06:10 13.80 13.80 41.47 0.02
July 28217.44 25649.65 0.08 03-JUL-12:10 0.07 0.07 39.61 0.00
August 26791.97 24353.90 0.08 18-AUG-10:30 0.07 0.07 37.03 0.00
September 106425.79 96741.05 99.16 20-SEP-06:07 90.14 90.14 36.10 0.11
October 9371525.58 8518716.75 417.23 28-OCT-06:03 379.26 379.26 30.78 0.64
November 0.150029E+09 0.136376E+09 683.13 24-NOV-07:12 620.96 620.96 43.25 2.21
December 0.338435E+09 0.307637E+09 655.64 22-DEC-07:01 595.98 595.98 41.19 2.10
                 
Annual Sum or Average 0.170393E+10 0.154887E+10            
Minimum of Months 25091.39 22808.07 0.08   0.07 0.07 30.78 0.00
Maximum of Months 0.497569E+09 0.452291E+09 760.01   690.85 690.85 43.25 2.47



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 12379742.02 3713922.60 6.85 01-JAN-06:03 2.06 2.06 58.09 0.05
February 11196021.66 3358806.50 6.85 01-FEB-06:01 2.06 2.06 57.13 0.05
March 12675672.10 3802701.63 6.85 01-MAR-06:05 2.06 2.06 56.74 0.05
April 11960507.72 3588152.32 6.85 01-APR-05:05 2.06 2.06 56.87 0.05
May 12527707.06 3758312.12 6.85 01-MAY-05:03 2.06 2.06 57.28 0.05
June 12231776.97 3669533.09 6.85 01-JUN-05:03 2.06 2.06 57.36 0.05
July 12256437.81 3676931.34 6.85 01-JUL-05:05 2.06 2.06 57.46 0.05
August 12675672.10 3802701.63 6.85 01-AUG-05:03 2.06 2.06 57.68 0.05
September 11960507.72 3588152.32 6.85 01-SEP-05:03 2.06 2.06 57.65 0.05
October 12379742.02 3713922.60 6.85 01-OCT-05:10 2.06 2.06 58.33 0.05
November 12059151.09 3617745.33 6.85 01-NOV-05:03 2.06 2.06 57.28 0.05
December 12256437.81 3676931.34 6.85 01-DEC-06:05 2.06 2.06 56.99 0.05
                 
Annual Sum or Average 0.146559E+09 43967812.83            
Minimum of Months 11196021.66 3358806.50 6.85   2.06 2.06 56.74 0.05
Maximum of Months 12675672.10 3802701.63 6.85   2.06 2.06 58.33 0.05



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 45.55 45.55 27449.18 195683.51 02-JAN-07:10
February 0.00 0.00 01-FEB-00:10 41.16 41.16 25525.62 184996.26 06-FEB-07:10
March 0.00 0.00 01-MAR-00:10 32.32 32.32 10426.81 183162.08 24-MAR-06:01
April 0.00 0.00 01-APR-00:10 25.60 25.60 2939.26 169664.73 04-APR-06:02
May 0.00 0.00 01-MAY-00:10 39.14 39.14 166.00 21619.04 01-MAY-06:05
June 0.00 0.00 01-JUN-00:10 41.67 41.67 0.81 1215.32 02-JUN-06:10
July 0.00 0.00 01-JUL-00:10 39.70 39.70 0.96 7.21 25-JUL-16:20
August 0.00 0.00 01-AUG-00:10 37.99 37.99 0.98 7.69 18-AUG-10:30
September 0.00 0.00 01-SEP-00:10 36.38 36.38 4.40 10847.19 20-SEP-06:07
October 0.00 0.00 01-OCT-00:10 32.86 32.86 442.30 77735.21 28-OCT-06:03
November 0.00 0.00 01-NOV-00:10 34.25 34.25 7876.65 176340.25 28-NOV-07:02
December 0.00 0.00 01-DEC-00:10 30.22 30.22 17462.34 176770.26 20-DEC-07:02
                 
Annual Sum or Average 0.00         7599.33    
Minimum of Months 0.00 0.00   25.60 25.60 0.81 7.21  
Maximum of Months 0.00 0.00   45.55 45.55 27449.18 195683.51  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 58.09 58.09 1753.16 6437.55 31-JAN-13:00
February 0.00 0.00 01-FEB-00:10 57.53 57.53 1781.52 6446.37 08-FEB-12:20
March 0.00 0.00 01-MAR-00:10 57.54 57.54 1862.65 6396.62 01-MAR-12:40
April 0.00 0.00 01-APR-00:10 57.64 57.64 1644.31 6126.53 03-APR-11:10
May 0.00 0.00 01-MAY-00:10 58.24 58.24 1591.41 5771.12 01-MAY-11:13
June 0.00 0.00 01-JUN-00:10 57.96 57.96 1517.24 5345.01 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 58.09 58.09 1311.24 4990.78 03-JUL-11:40
August 0.00 0.00 01-AUG-00:10 58.16 58.16 1431.13 4874.11 31-AUG-12:00
September 0.00 0.00 01-SEP-00:10 58.15 58.15 1372.29 5103.58 29-SEP-11:20
October 0.00 0.00 01-OCT-00:10 57.25 57.25 1460.48 5503.72 31-OCT-11:10
November 0.00 0.00 01-NOV-00:10 57.90 57.90 1598.39 5916.29 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 57.74 57.74 1633.52 6246.35 29-DEC-12:20
                 
Annual Sum or Average 0.00         1578.63    
Minimum of Months 0.00 0.00   57.25 57.25 1311.24 4874.11  
Maximum of Months 0.00 0.00   58.24 58.24 1862.65 6446.37  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.235248E+11 0.00 0.00 0.113803E+10 0.00 0.00
February 0.201878E+11 0.00 0.00 0.937537E+09 0.00 0.00
March 0.102109E+11 0.00 0.00 0.124130E+10 0.00 0.00
April 0.293109E+10 0.00 0.00 0.223179E+10 0.00 0.00
May 0.387467E+09 0.00 0.00 0.553104E+10 0.00 0.00
June 2187952.82 0.00 0.00 0.148406E+11 0.00 0.00
July 1288119.04 0.00 0.00 0.210179E+11 0.00 0.00
August 1240243.19 0.00 0.00 0.222417E+11 0.00 0.00
September 11907531.02 0.00 0.00 0.119744E+11 0.00 0.00
October 0.366205E+09 0.00 0.00 0.658741E+10 0.00 0.00
November 0.600863E+10 0.00 0.00 0.138387E+10 0.00 0.00
December 0.142962E+11 0.00 0.00 0.993829E+09 0.00 0.00
             
Annual Sum or Average 0.779298E+11 0.00 0.00 0.901194E+11 0.00 0.00
Minimum of Months 1240243.19 0.00 0.00 0.937537E+09 0.00 0.00
Maximum of Months 0.235248E+11 0.00 0.00 0.222417E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.212408E+11 0.00 0.00 0.108661E+10 0.00 0.00
February 0.173407E+11 0.00 0.00 0.941785E+09 0.00 0.00
March 0.764914E+10 0.00 0.00 0.126015E+10 0.00 0.00
April 0.190777E+10 0.00 0.00 0.242883E+10 0.00 0.00
May 20506989.17 0.00 0.00 0.587013E+10 0.00 0.00
June 494058.61 0.00 0.00 0.146314E+11 0.00 0.00
July 1107581.26 0.00 0.00 0.200755E+11 0.00 0.00
August 1128946.76 0.00 0.00 0.207527E+11 0.00 0.00
September 332229.88 0.00 0.00 0.105656E+11 0.00 0.00
October 0.300569E+09 0.00 0.00 0.550351E+10 0.00 0.00
November 0.562629E+10 0.00 0.00 0.114969E+10 0.00 0.00
December 0.130721E+11 0.00 0.00 0.976513E+09 0.00 0.00
             
Annual Sum or Average 0.671610E+11 0.00 0.00 0.852424E+11 0.00 0.00
Minimum of Months 332229.88 0.00 0.00 0.941785E+09 0.00 0.00
Maximum of Months 0.212408E+11 0.00 0.00 0.207527E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.292985E+11 0.00 0.00 0.129889E+10 0.00 0.00
February 0.246972E+11 0.00 0.00 0.112123E+10 0.00 0.00
March 0.102974E+11 0.00 0.00 0.134339E+10 0.00 0.00
April 0.283323E+10 0.00 0.00 0.247528E+10 0.00 0.00
May 40735046.12 0.00 0.00 0.596759E+10 0.00 0.00
June 664492.70 0.00 0.00 0.152356E+11 0.00 0.00
July 1260291.08 0.00 0.00 0.210538E+11 0.00 0.00
August 1273166.26 0.00 0.00 0.216300E+11 0.00 0.00
September 1462228.58 0.00 0.00 0.104878E+11 0.00 0.00
October 0.527016E+09 0.00 0.00 0.511841E+10 0.00 0.00
November 0.894522E+10 0.00 0.00 0.116810E+10 0.00 0.00
December 0.197584E+11 0.00 0.00 0.109791E+10 0.00 0.00
             
Annual Sum or Average 0.964023E+11 0.00 0.00 0.879980E+11 0.00 0.00
Minimum of Months 664492.70 0.00 0.00 0.109791E+10 0.00 0.00
Maximum of Months 0.292985E+11 0.00 0.00 0.216300E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.113803E+10 0.00 0.235248E+11 0.00 0.00 0.00 0.00 0.00
February 0.937537E+09 0.00 0.201878E+11 0.00 0.00 0.00 0.00 0.00
March 0.115073E+10 0.390328E+09 0.102109E+11 0.00 0.00 0.00 0.00 0.00
April 0.142328E+10 0.355549E+10 0.293109E+10 0.00 0.00 0.00 0.00 0.00
May 0.233151E+10 0.142683E+11 0.387467E+09 0.00 0.00 0.00 0.00 0.00
June 0.399798E+10 0.507730E+11 2187952.82 0.00 0.00 0.00 0.00 0.00
July 0.515186E+10 0.736567E+11 1288119.04 0.00 0.00 0.00 0.00 0.00
August 0.570868E+10 0.757497E+11 1240243.19 0.00 0.00 0.00 0.00 0.00
September 0.366099E+10 0.392336E+11 11907531.02 0.00 0.00 0.00 0.00 0.00
October 0.284242E+10 0.177031E+11 0.366205E+09 0.00 0.00 0.00 0.00 0.00
November 0.125692E+10 0.517289E+09 0.600863E+10 0.00 0.00 0.00 0.00 0.00
December 0.993829E+09 0.00 0.142962E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.305938E+11 0.275848E+12 0.779298E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.937537E+09 0.00 1240243.19 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.570868E+10 0.757497E+11 0.235248E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.108661E+10 0.00 0.212408E+11 0.00 0.00 0.00 0.00 0.00
February 0.941785E+09 0.00 0.173407E+11 0.00 0.00 0.00 0.00 0.00
March 0.117090E+10 0.387773E+09 0.764914E+10 0.00 0.00 0.00 0.00 0.00
April 0.148901E+10 0.415834E+10 0.190777E+10 0.00 0.00 0.00 0.00 0.00
May 0.251508E+10 0.150636E+11 20506989.17 0.00 0.00 0.00 0.00 0.00
June 0.401531E+10 0.496504E+11 494058.61 0.00 0.00 0.00 0.00 0.00
July 0.491153E+10 0.704051E+11 1107581.26 0.00 0.00 0.00 0.00 0.00
August 0.540473E+10 0.702807E+11 1128946.76 0.00 0.00 0.00 0.00 0.00
September 0.309316E+10 0.350338E+11 332229.88 0.00 0.00 0.00 0.00 0.00
October 0.223820E+10 0.153277E+11 0.300569E+09 0.00 0.00 0.00 0.00 0.00
November 0.105928E+10 0.366993E+09 0.562629E+10 0.00 0.00 0.00 0.00 0.00
December 0.976513E+09 0.00 0.130721E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.289021E+11 0.260674E+12 0.671610E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.941785E+09 0.00 332229.88 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.540473E+10 0.704051E+11 0.212408E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.129880E+10 365002.76 0.292985E+11 0.00 0.00 0.00 0.00 0.00
February 0.112121E+10 76454.15 0.246972E+11 0.00 0.00 0.00 0.00 0.00
March 0.123118E+10 0.478201E+09 0.102974E+11 0.00 0.00 0.00 0.00 0.00
April 0.147466E+10 0.442743E+10 0.283323E+10 0.00 0.00 0.00 0.00 0.00
May 0.240660E+10 0.159106E+11 40735046.12 0.00 0.00 0.00 0.00 0.00
June 0.384730E+10 0.529443E+11 664492.70 0.00 0.00 0.00 0.00 0.00
July 0.476915E+10 0.752831E+11 1260291.08 0.00 0.00 0.00 0.00 0.00
August 0.523158E+10 0.747777E+11 1273166.26 0.00 0.00 0.00 0.00 0.00
September 0.280052E+10 0.357133E+11 1462228.58 0.00 0.00 0.00 0.00 0.00
October 0.193480E+10 0.147839E+11 0.527016E+09 0.00 0.00 0.00 0.00 0.00
November 0.108961E+10 0.315152E+09 0.894522E+10 0.00 0.00 0.00 0.00 0.00
December 0.109789E+10 90671.00 0.197584E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.283033E+11 0.274634E+12 0.964023E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.108961E+10 76454.15 664492.70 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.523158E+10 0.752831E+11 0.292985E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.113803E+10 0.235248E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.937537E+09 0.201878E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.115073E+10 0.102109E+11 0.00 0.00 90570102.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.142328E+10 0.293109E+10 0.00 0.00 0.808509E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.233151E+10 0.387467E+09 0.00 0.00 0.319953E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.399798E+10 2187952.82 0.00 0.00 0.108426E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.515186E+10 1288119.04 0.00 0.00 0.158661E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.570868E+10 1240243.19 0.00 0.00 0.165330E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.366099E+10 11907531.02 0.00 0.00 0.831336E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.284242E+10 0.366205E+09 0.00 0.00 0.374499E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.125692E+10 0.600863E+10 0.00 0.00 0.126955E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.993829E+09 0.142962E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.305938E+11 0.779298E+11 0.00 0.00 0.595256E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.937537E+09 1240243.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.570868E+10 0.235248E+11 0.00 0.00 0.165330E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.108661E+10 0.212408E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.941785E+09 0.173407E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.117090E+10 0.764914E+10 0.00 0.00 89249778.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.148901E+10 0.190777E+10 0.00 0.00 0.939818E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.251508E+10 20506989.17 0.00 0.00 0.335505E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.401531E+10 494058.61 0.00 0.00 0.106161E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.491153E+10 1107581.26 0.00 0.00 0.151640E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.540473E+10 1128946.76 0.00 0.00 0.153479E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.309316E+10 332229.88 0.00 0.00 0.747242E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.223820E+10 0.300569E+09 0.00 0.00 0.326531E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.105928E+10 0.562629E+10 0.00 0.00 90415287.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.976513E+09 0.130721E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.289021E+11 0.671610E+11 0.00 0.00 0.563403E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.941785E+09 332229.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.540473E+10 0.212408E+11 0.00 0.00 0.153479E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.129880E+10 0.292985E+11 0.00 0.00 94540.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.112121E+10 0.246972E+11 0.00 0.00 19799.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.123118E+10 0.102974E+11 0.00 0.00 0.112211E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.147466E+10 0.283323E+10 0.00 0.00 0.100061E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.240660E+10 40735046.12 0.00 0.00 0.356099E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.384730E+10 664492.70 0.00 0.00 0.113883E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.476915E+10 1260291.08 0.00 0.00 0.162846E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.523158E+10 1273166.26 0.00 0.00 0.163985E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.280052E+10 1462228.58 0.00 0.00 0.768731E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.193480E+10 0.527016E+09 0.00 0.00 0.318362E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.108961E+10 0.894522E+10 0.00 0.00 78490251.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.109789E+10 0.197584E+11 0.00 0.00 23489.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.283033E+11 0.964023E+11 0.00 0.00 0.596947E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.108961E+10 664492.70 0.00 0.00 19799.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.523158E+10 0.292985E+11 0.00 0.00 0.163985E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.126045E+11 0.00 0.00 515107.59 0.00 0.869617E+09 0.108373E+10 0.00 0.28
February 0.121948E+11 0.00 0.00 1472150.36 0.00 0.00 0.222976E+10 0.00 0.29
March 0.614397E+10 0.00 0.00 13080347.55 0.00 0.00 0.965623E+10 0.00 0.36
April 0.232881E+10 5866256.63 0.00 21729519.16 0.00 0.00 0.117215E+11 0.00 0.49
May 0.941327E+09 97548548.71 0.00 30593024.54 0.00 0.00 0.131373E+11 0.00 0.76
June 0.207713E+09 0.305328E+10 0.00 13258523.28 40960413.42 0.00 0.289154E+10 0.00 0.55
July 6836211.72 0.758637E+10 0.00 1048685.00 0.109674E+09 0.00 0.115902E+09 0.00 0.27
August 86893193.14 0.597586E+10 0.00 10939658.12 89476754.34 0.00 0.134072E+10 0.00 0.46
September 0.602450E+09 0.188743E+10 0.00 21849866.84 16027949.34 0.00 0.671831E+10 0.00 0.66
October 0.113838E+10 0.157921E+09 0.00 33576386.44 0.00 0.00 0.128569E+11 0.00 0.71
November 0.377453E+10 0.00 0.00 18854808.08 0.00 0.00 0.117246E+11 0.00 0.42
December 0.923041E+10 0.00 0.00 4963070.78 0.00 0.00 0.535335E+10 0.00 0.29
                   
Annual Sum or Average 0.492606E+11 0.187643E+11 0.00 0.171881E+09 0.256139E+09 0.869617E+09 0.788298E+11 0.00 0.46
Minimum of Months 6836211.72 0.00 0.00 515107.59 0.00 0.00 0.115902E+09 0.00 0.27
Maximum of Months 0.126045E+11 0.758637E+10 0.00 33576386.44 0.109674E+09 0.869617E+09 0.131373E+11 0.00 0.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.129340E+11 0.00 0.00 0.00 0.00 0.142300E+10 0.00 0.00 0.28
February 0.134973E+11 0.00 0.00 0.00 0.00 0.489808E+09 0.00 0.00 0.28
March 0.119895E+11 0.00 0.00 1805712.66 0.00 6852768.10 0.206986E+10 0.00 0.32
April 0.549084E+10 3799879.66 0.00 9461498.34 0.00 0.00 0.614574E+10 0.00 0.41
May 0.219538E+10 79357058.09 0.00 19377771.60 0.00 0.00 0.891448E+10 0.00 0.60
June 0.307834E+09 0.251070E+10 0.00 9960442.73 39781836.50 0.00 0.217779E+10 0.00 0.44
July 7807888.95 0.666998E+10 0.00 917512.25 0.106410E+09 0.00 98175529.72 0.00 0.24
August 0.125505E+09 0.536702E+10 0.00 8576673.45 89725084.83 0.00 0.102593E+10 0.00 0.40
September 0.875318E+09 0.165286E+10 0.00 13998343.52 17948444.20 0.00 0.452672E+10 0.00 0.51
October 0.229203E+10 0.139150E+09 0.00 17800700.30 2091136.23 0.00 0.768571E+10 0.00 0.52
November 0.881852E+10 0.00 0.00 4523860.73 0.00 16854344.32 0.344662E+10 0.00 0.33
December 0.135712E+11 0.00 0.00 10080.60 0.00 74924989.32 72904467.83 0.00 0.28
                   
Annual Sum or Average 0.721052E+11 0.164229E+11 0.00 86432596.18 0.255956E+09 0.201144E+10 0.361639E+11 0.00 0.39
Minimum of Months 7807888.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.24
Maximum of Months 0.135712E+11 0.666998E+10 0.00 19377771.60 0.106410E+09 0.142300E+10 0.891448E+10 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.100323E+11 0.00 0.00 0.00 0.00 0.349472E+10 0.00 0.00 0.27
February 0.107268E+11 0.00 0.00 0.00 0.00 0.243916E+10 0.00 0.00 0.28
March 0.120868E+11 0.00 0.00 1008863.54 0.00 0.293066E+09 0.110678E+10 0.00 0.32
April 0.644202E+10 1901421.39 0.00 7774970.55 0.00 37366943.62 0.475308E+10 0.00 0.40
May 0.288172E+10 73022979.13 0.00 17615492.62 0.00 0.00 0.833067E+10 0.00 0.60
June 0.427456E+09 0.250163E+10 0.00 10090667.72 37057858.07 0.00 0.221109E+10 0.00 0.47
July 10916278.27 0.662064E+10 0.00 1027928.18 98914144.17 0.00 90849198.81 0.00 0.25
August 0.152268E+09 0.528531E+10 0.00 8364742.33 84215183.72 0.00 0.937779E+09 0.00 0.41
September 0.144486E+10 0.167084E+10 0.00 11076954.98 19607533.80 0.00 0.355820E+10 0.00 0.50
October 0.362449E+10 0.104305E+09 0.00 11377927.99 960924.47 0.00 0.515048E+10 0.00 0.48
November 0.904703E+10 0.00 0.00 1642037.46 0.00 0.631331E+09 0.152741E+10 0.00 0.31
December 0.114233E+11 0.00 0.00 0.00 0.00 0.132882E+10 0.00 0.00 0.28
                   
Annual Sum or Average 0.682999E+11 0.162576E+11 0.00 69979585.37 0.240756E+09 0.822445E+10 0.276663E+11 0.00 0.38
Minimum of Months 10916278.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25
Maximum of Months 0.120868E+11 0.662064E+10 0.00 17615492.62 98914144.17 0.349472E+10 0.833067E+10 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.465313E+09 0.00 0.00 0.00 0.00 0.264178E+10 0.00 0.00 0.30
February 0.596470E+09 0.00 0.00 0.00 0.00 0.241909E+10 0.00 0.00 0.30
March 0.202043E+10 0.00 0.00 82269.81 0.00 0.766266E+09 80165269.50 0.00 0.32
April 0.151149E+10 514976.93 0.00 1432500.77 0.00 0.163902E+09 0.727053E+09 0.00 0.42
May 0.739426E+09 23645242.94 0.00 4490715.15 0.00 668427.03 0.194829E+10 0.00 0.72
June 90885186.16 0.810425E+09 0.00 2944720.04 8143304.12 0.00 0.625971E+09 0.00 0.65
July 1150910.76 0.221230E+10 0.00 316939.75 21068908.87 0.00 26646156.11 0.00 0.38
August 34315706.22 0.174587E+10 0.00 2358996.05 18559567.50 0.00 0.252997E+09 0.00 0.58
September 0.393828E+09 0.443545E+09 0.00 2481327.31 7368157.70 0.00 0.739764E+09 0.00 0.57
October 0.103072E+10 24097130.40 0.00 1848115.18 2067883.96 19387411.16 0.733737E+09 0.00 0.48
November 0.145751E+10 0.00 0.00 53719.30 0.00 0.853504E+09 72664362.01 0.00 0.31
December 0.747180E+09 0.00 0.00 0.00 0.00 0.200479E+10 0.00 0.00 0.28
                   
Annual Sum or Average 0.908872E+10 0.526040E+10 0.00 16009303.36 57207822.16 0.886938E+10 0.520729E+10 0.00 0.44
Minimum of Months 1150910.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.202043E+10 0.221230E+10 0.00 4490715.15 21068908.87 0.264178E+10 0.194829E+10 0.00 0.72



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.573880E+09 0.00 0.00 0.00 0.00 0.137760E+10 0.00 0.00 0.30
February 0.776743E+09 0.00 0.00 0.00 0.00 0.106915E+10 0.00 0.00 0.29
March 0.120148E+10 0.00 0.00 859251.47 0.00 0.297052E+09 0.530678E+09 0.00 0.36
April 0.712601E+09 994200.19 0.00 2877640.69 0.00 86614197.17 0.142302E+10 0.00 0.65
May 0.348940E+09 24597069.10 0.00 5882680.75 0.00 0.00 0.237279E+10 0.00 1.11
June 35419037.11 0.663079E+09 0.00 3395897.52 5171668.09 0.00 0.750434E+09 0.00 0.93
July 490649.12 0.184132E+10 0.00 381898.27 13380490.53 0.00 37476357.72 0.00 0.53
August 15539234.18 0.157937E+10 0.00 2778600.34 11302192.49 0.00 0.321195E+09 0.00 0.91
September 0.162516E+09 0.365007E+09 0.00 3461215.74 4578850.52 0.00 0.991487E+09 0.00 0.86
October 0.447768E+09 21169827.81 0.00 3167895.88 519796.63 8069169.52 0.122368E+10 0.00 0.74
November 0.882374E+09 0.00 0.00 415212.88 0.00 0.387370E+09 0.301712E+09 0.00 0.33
December 0.757466E+09 0.00 0.00 0.00 0.00 0.989033E+09 0.00 0.00 0.29
                   
Annual Sum or Average 0.591522E+10 0.449555E+10 0.00 23220293.54 34952998.26 0.421489E+10 0.795247E+10 0.00 0.61
Minimum of Months 490649.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Maximum of Months 0.120148E+10 0.184132E+10 0.00 5882680.75 13380490.53 0.137760E+10 0.237279E+10 0.00 1.11



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.951511E+09 0.00 0.00 1306965.61 0.00 0.159183E+10 0.890548E+09 0.00 0.33
February 0.110614E+10 0.00 0.00 1908203.78 0.00 0.124170E+10 0.125403E+10 0.00 0.36
March 0.157110E+10 0.00 0.00 4858333.50 0.00 0.406431E+09 0.262107E+10 0.00 0.54
April 0.121207E+10 1315375.09 0.00 4981750.48 0.00 0.131549E+09 0.236248E+10 0.00 0.69
May 0.688668E+09 29680427.03 0.00 6727776.18 0.00 1329242.45 0.280089E+10 0.00 0.93
June 0.106189E+09 0.911447E+09 0.00 3556476.10 8390567.11 0.00 0.736906E+09 0.00 0.74
July 4211592.64 0.252850E+10 0.00 371816.76 21501576.01 0.00 24673587.29 0.00 0.44
August 32998147.34 0.230740E+10 0.00 4006489.78 17980324.39 0.00 0.386786E+09 0.00 0.83
September 0.264774E+09 0.654013E+09 0.00 6858484.25 7193703.27 0.00 0.188199E+10 0.00 1.03
October 0.542835E+09 65437011.61 0.00 9835511.51 112677.02 5832775.89 0.384534E+10 0.00 1.17
November 0.119457E+10 0.00 0.00 3406980.57 0.00 0.438635E+09 0.195966E+10 0.00 0.51
December 0.109152E+10 0.00 0.00 1642505.66 0.00 0.119108E+10 0.100380E+10 0.00 0.34
                   
Annual Sum or Average 0.876658E+10 0.649779E+10 0.00 49461294.18 55178847.81 0.500839E+10 0.197682E+11 0.00 0.66
Minimum of Months 4211592.64 0.00 0.00 371816.76 0.00 0.00 24673587.29 0.00 0.33
Maximum of Months 0.157110E+10 0.252850E+10 0.00 9835511.51 21501576.01 0.159183E+10 0.384534E+10 0.00 1.17



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.473872E+09 0.00 0.00 31872.41 0.00 0.151099E+10 39883704.94 0.00 0.30
February 0.557621E+09 0.00 0.00 117171.25 0.00 0.134403E+10 0.121269E+09 0.00 0.31
March 0.112123E+10 0.00 0.00 1431417.14 0.00 0.361971E+09 0.835114E+09 0.00 0.42
April 0.797822E+09 395853.88 0.00 3013321.95 0.00 97071113.62 0.141184E+10 0.00 0.68
May 0.369055E+09 22941369.50 0.00 5571054.53 0.00 837024.15 0.216485E+10 0.00 1.08
June 54944570.39 0.703836E+09 0.00 2978077.94 3787328.17 0.00 0.588525E+09 0.00 0.92
July 2302010.49 0.188303E+10 0.00 252522.56 6310309.52 0.00 16140660.79 0.00 0.51
August 20537374.41 0.164672E+10 0.00 2420774.18 6624063.86 0.00 0.222760E+09 0.00 0.88
September 0.202335E+09 0.404850E+09 0.00 3124591.18 3543344.79 0.00 0.846419E+09 0.00 0.85
October 0.521258E+09 33264521.11 0.00 3024661.92 70952.74 10427349.08 0.120535E+10 0.00 0.77
November 0.861146E+09 0.00 0.00 405154.14 0.00 0.490466E+09 0.281257E+09 0.00 0.35
December 0.583487E+09 0.00 0.00 20124.71 0.00 0.113311E+10 31894618.89 0.00 0.29
                   
Annual Sum or Average 0.556561E+10 0.469504E+10 0.00 22390743.91 20335999.07 0.494890E+10 0.776531E+10 0.00 0.62
Minimum of Months 2302010.49 0.00 0.00 20124.71 0.00 0.00 16140660.79 0.00 0.29
Maximum of Months 0.112123E+10 0.188303E+10 0.00 5571054.53 6624063.86 0.151099E+10 0.216485E+10 0.00 1.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.637633E+09 0.00 0.00 0.00 0.00 0.254111E+10 0.00 0.00 0.29
February 0.639673E+09 0.00 0.00 0.00 0.00 0.255134E+10 0.00 0.00 0.30
March 0.215979E+10 0.00 0.00 0.00 0.00 0.843870E+09 0.00 0.00 0.32
April 0.191847E+10 466601.88 0.00 305128.24 313534.30 96527661.21 0.171955E+09 0.00 0.35
May 0.112522E+10 19907643.45 0.00 1976509.88 0.00 0.00 0.837206E+09 0.00 0.51
June 93119796.16 0.635657E+09 0.00 1959615.13 9667835.92 0.00 0.422828E+09 0.00 0.48
July 1681999.44 0.180310E+10 0.00 216623.67 23165331.78 0.00 22618239.05 0.00 0.30
August 39562128.92 0.150048E+10 0.00 1935373.97 18899284.77 0.00 0.217353E+09 0.00 0.47
September 0.330448E+09 0.382413E+09 0.00 2630601.09 3386423.37 0.00 0.805842E+09 0.00 0.54
October 0.996951E+09 29235047.92 0.00 2246120.05 48434.51 0.00 0.921741E+09 0.00 0.48
November 0.193884E+10 0.00 0.00 132920.37 0.00 0.407376E+09 0.182850E+09 0.00 0.31
December 0.149193E+10 0.00 0.00 0.00 0.00 0.150249E+10 0.00 0.00 0.28
                   
Annual Sum or Average 0.113733E+11 0.437125E+10 0.00 11402892.40 55480844.65 0.794272E+10 0.358239E+10 0.00 0.39
Minimum of Months 1681999.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.215979E+10 0.180310E+10 0.00 2630601.09 23165331.78 0.255134E+10 0.921741E+09 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.708735E+09 0.00 0.00 0.00 0.00 0.133128E+10 0.00 0.00 0.29
February 0.898583E+09 0.00 0.00 0.00 0.00 0.107675E+10 0.00 0.00 0.29
March 0.143331E+10 0.00 0.00 361000.99 0.00 0.245088E+09 0.281377E+09 0.00 0.33
April 0.875680E+09 1400880.51 0.00 1855197.44 0.00 26165786.49 0.917463E+09 0.00 0.51
May 0.457933E+09 24240021.83 0.00 3845463.42 0.00 0.00 0.155344E+10 0.00 0.85
June 31529627.18 0.562164E+09 0.00 2584948.03 5601824.15 0.00 0.583456E+09 0.00 0.75
July 913599.98 0.160677E+10 0.00 276144.75 14787677.69 0.00 31872261.62 0.00 0.44
August 15293397.74 0.145131E+10 0.00 2423906.51 11938745.89 0.00 0.297162E+09 0.00 0.79
September 0.111793E+09 0.343500E+09 0.00 3683984.76 2138584.66 0.00 0.108372E+10 0.00 0.85
October 0.355670E+09 28536077.73 0.00 4094016.03 0.00 0.00 0.158135E+10 0.00 0.80
November 0.113782E+10 0.00 0.00 865700.22 0.00 0.140348E+09 0.488730E+09 0.00 0.35
December 0.122591E+10 0.00 0.00 1150.73 0.00 0.668202E+09 3362216.42 0.00 0.28
                   
Annual Sum or Average 0.725317E+10 0.401792E+10 0.00 19991512.88 34466832.39 0.348783E+10 0.682192E+10 0.00 0.55
Minimum of Months 913599.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.143331E+10 0.160677E+10 0.00 4094016.03 14787677.69 0.133128E+10 0.158135E+10 0.00 0.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.871320E+09 0.00 0.00 8160.68 0.00 0.336499E+10 23823015.05 0.00 0.38
February 0.956457E+09 0.00 0.00 65965.06 0.00 0.317589E+10 81077069.06 0.00 0.39
March 0.160665E+10 0.00 0.00 604599.27 0.00 0.190277E+10 0.408878E+09 0.00 0.41
April 0.142657E+10 2605334.60 0.00 1441777.69 0.00 0.782401E+09 0.607387E+09 0.00 0.49
May 0.120157E+10 30043651.51 0.00 2051172.27 261620.23 0.189897E+09 0.801019E+09 0.00 0.59
June 0.139853E+09 0.783593E+09 0.00 1943393.61 25071894.40 546804.34 0.386640E+09 0.00 0.53
July 6576918.89 0.240147E+10 0.00 252836.67 27649790.25 0.00 16397467.32 0.00 0.39
August 58889641.60 0.243064E+10 0.00 3102927.79 22934826.10 0.00 0.282055E+09 0.00 0.74
September 0.277160E+09 0.636667E+09 0.00 5874323.94 9116543.42 6955994.05 0.158287E+10 0.00 0.92
October 0.523905E+09 79623473.92 0.00 8669975.39 7049.67 0.115507E+09 0.324437E+10 0.00 1.05
November 0.154058E+10 0.00 0.00 1750242.00 0.00 0.104555E+10 0.109746E+10 0.00 0.48
December 0.136612E+10 0.00 0.00 269358.68 0.00 0.232850E+10 0.236026E+09 0.00 0.37
                   
Annual Sum or Average 0.997566E+10 0.636464E+10 0.00 26034733.04 85041724.07 0.129130E+11 0.876801E+10 0.00 0.56
Minimum of Months 6576918.89 0.00 0.00 8160.68 0.00 0.00 16397467.32 0.00 0.37
Maximum of Months 0.160665E+10 0.243064E+10 0.00 8669975.39 27649790.25 0.336499E+10 0.324437E+10 0.00 1.05



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.648504E+09 0.00 0.00 2098.08 0.00 0.143498E+10 4771451.78 0.00 0.30
February 0.719241E+09 0.00 0.00 27196.73 0.00 0.131092E+10 40242443.83 0.00 0.30
March 0.142845E+10 0.00 0.00 666953.63 0.00 0.243080E+09 0.382776E+09 0.00 0.35
April 0.960738E+09 810536.28 0.00 1771629.15 0.00 37500828.74 0.814183E+09 0.00 0.51
May 0.490587E+09 22276642.04 0.00 3349681.95 0.00 0.00 0.132233E+10 0.00 0.79
June 44477756.52 0.637537E+09 0.00 2180030.12 4512310.89 0.00 0.449260E+09 0.00 0.75
July 1065867.21 0.167724E+10 0.00 189907.33 9417691.47 0.00 16262334.51 0.00 0.43
August 19652508.74 0.154733E+10 0.00 2015705.38 8632562.20 0.00 0.202984E+09 0.00 0.76
September 0.150278E+09 0.379657E+09 0.00 3135932.84 1868662.80 0.00 0.892712E+09 0.00 0.82
October 0.365705E+09 40371689.52 0.00 3845336.52 0.00 0.00 0.149274E+10 0.00 0.80
November 0.116271E+10 0.00 0.00 543657.03 0.00 0.206754E+09 0.360035E+09 0.00 0.35
December 0.113861E+10 0.00 0.00 11664.93 0.00 0.745207E+09 20072880.37 0.00 0.28
                   
Annual Sum or Average 0.713002E+10 0.430523E+10 0.00 17739793.70 24431227.35 0.397844E+10 0.599837E+10 0.00 0.54
Minimum of Months 1065867.21 0.00 0.00 2098.08 0.00 0.00 4771451.78 0.00 0.28
Maximum of Months 0.142845E+10 0.167724E+10 0.00 3845336.52 9417691.47 0.143498E+10 0.149274E+10 0.00 0.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.758041E+09 0.00 0.00 0.00 0.00 0.239163E+10 0.00 0.00 0.29
February 0.980361E+09 0.00 0.00 0.00 0.00 0.206456E+10 0.00 0.00 0.29
March 0.247579E+10 0.00 0.00 87291.08 0.00 0.401064E+09 78234518.31 0.00 0.32
April 0.165002E+10 1158996.94 0.00 1461797.69 0.00 34902669.76 0.743276E+09 0.00 0.42
May 0.630592E+09 26573844.51 0.00 4793051.00 0.00 0.00 0.197225E+10 0.00 0.71
June 68652810.84 0.847760E+09 0.00 2844489.51 8367546.33 0.00 0.595683E+09 0.00 0.62
July 1642278.95 0.230028E+10 0.00 274961.81 22381737.05 0.00 26632047.33 0.00 0.38
August 38168810.30 0.182980E+10 0.00 2288946.99 18872401.85 0.00 0.246346E+09 0.00 0.56
September 0.330317E+09 0.450589E+09 0.00 2799090.93 3880096.40 0.00 0.841784E+09 0.00 0.58
October 0.100292E+10 36593921.43 0.00 2301957.38 26653.08 0.00 0.926128E+09 0.00 0.50
November 0.181190E+10 0.00 0.00 199022.75 0.00 0.494252E+09 0.203826E+09 0.00 0.32
December 0.142604E+10 0.00 0.00 0.00 0.00 0.147385E+10 0.00 0.00 0.28
                   
Annual Sum or Average 0.111744E+11 0.549275E+10 0.00 17050609.13 53528434.72 0.686026E+10 0.563416E+10 0.00 0.44
Minimum of Months 1642278.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.247579E+10 0.230028E+10 0.00 4793051.00 22381737.05 0.239163E+10 0.197225E+10 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.620812E+09 0.00 0.00 93.95 0.00 0.107627E+10 1609855.20 0.00 0.25
February 0.763441E+09 0.00 0.00 27440.79 0.00 0.810790E+09 26260337.44 0.00 0.24
March 0.113718E+10 0.00 0.00 1029851.37 0.00 0.146766E+09 0.603395E+09 0.00 0.32
April 0.708138E+09 1386687.50 0.00 2895832.95 0.00 7964001.01 0.135893E+10 0.00 0.60
May 0.289826E+09 24307567.21 0.00 5707594.40 0.00 0.00 0.222144E+10 0.00 1.05
June 26102499.66 0.651816E+09 0.00 3059682.16 5349758.75 0.00 0.689125E+09 0.00 0.84
July 898836.87 0.181441E+10 0.00 324365.99 14309427.32 0.00 37278418.41 0.00 0.50
August 17057597.82 0.156119E+10 0.00 2622851.18 12002373.87 0.00 0.315925E+09 0.00 0.84
September 0.132606E+09 0.346776E+09 0.00 3622047.74 2449369.34 0.00 0.101254E+10 0.00 0.82
October 0.434306E+09 28894011.14 0.00 3479973.68 0.00 0.00 0.131714E+10 0.00 0.73
November 0.865143E+09 0.00 0.00 656784.53 0.00 0.234349E+09 0.392800E+09 0.00 0.30
December 0.841029E+09 0.00 0.00 11710.18 0.00 0.681519E+09 6800300.95 0.00 0.24
                   
Annual Sum or Average 0.583654E+10 0.442879E+10 0.00 23438228.91 34110929.28 0.295766E+10 0.798325E+10 0.00 0.56
Minimum of Months 898836.87 0.00 0.00 93.95 0.00 0.00 1609855.20 0.00 0.24
Maximum of Months 0.113718E+10 0.181441E+10 0.00 5707594.40 14309427.32 0.107627E+10 0.222144E+10 0.00 1.05



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.128975E+10 0.00 0.00 1683838.51 0.00 0.125384E+10 0.111105E+10 0.00 0.34
February 0.142965E+10 0.00 0.00 2392739.90 0.00 0.943004E+09 0.153844E+10 0.00 0.38
March 0.181115E+10 0.00 0.00 5417208.04 0.00 0.192154E+09 0.274879E+10 0.00 0.55
April 0.130011E+10 3024773.94 0.00 5115524.56 0.00 29651143.30 0.231590E+10 0.00 0.69
May 0.611359E+09 34475376.98 0.00 6702848.82 0.00 0.00 0.269167E+10 0.00 0.91
June 81581253.18 0.972956E+09 0.00 3292955.82 8367128.07 0.00 0.667966E+09 0.00 0.71
July 1410277.60 0.266874E+10 0.00 306969.20 22527718.25 0.00 26166447.46 0.00 0.44
August 36890244.86 0.246961E+10 0.00 3614721.74 18909655.52 0.00 0.343813E+09 0.00 0.79
September 0.238547E+09 0.682909E+09 0.00 7265490.75 3775012.53 0.00 0.184966E+10 0.00 1.03
October 0.493095E+09 0.100387E+09 0.00 10791119.36 0.00 0.00 0.405625E+10 0.00 1.20
November 0.137009E+10 0.00 0.00 4482773.86 0.00 0.201124E+09 0.249330E+10 0.00 0.57
December 0.147810E+10 0.00 0.00 2367109.83 0.00 0.783153E+09 0.145385E+10 0.00 0.37
                   
Annual Sum or Average 0.101417E+11 0.693211E+10 0.00 53433300.39 53579514.37 0.340292E+10 0.212969E+11 0.00 0.66
Minimum of Months 1410277.60 0.00 0.00 306969.20 0.00 0.00 26166447.46 0.00 0.34
Maximum of Months 0.181115E+10 0.266874E+10 0.00 10791119.36 22527718.25 0.125384E+10 0.405625E+10 0.00 1.20



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.670624E+09 0.00 0.00 43839.33 0.00 0.133088E+10 50691695.82 0.00 0.30
February 0.794132E+09 0.00 0.00 146009.30 0.00 0.112051E+10 0.145663E+09 0.00 0.31
March 0.133898E+10 0.00 0.00 1524161.61 0.00 0.182360E+09 0.853412E+09 0.00 0.43
April 0.851395E+09 1017059.98 0.00 3047071.53 0.00 19618910.31 0.138923E+10 0.00 0.68
May 0.318230E+09 27286873.94 0.00 5490196.20 0.00 0.00 0.207376E+10 0.00 1.06
June 43535552.50 0.761759E+09 0.00 2681998.86 3941041.86 0.00 0.528533E+09 0.00 0.89
July 1039274.16 0.200936E+10 0.00 218358.38 6589044.08 0.00 17347516.84 0.00 0.52
August 23245456.75 0.177178E+10 0.00 2224992.62 7506425.62 0.00 0.203056E+09 0.00 0.85
September 0.176735E+09 0.419212E+09 0.00 3139539.94 1947197.94 0.00 0.861305E+09 0.00 0.85
October 0.485545E+09 48480135.97 0.00 3419389.60 0.00 0.00 0.132693E+10 0.00 0.79
November 0.109640E+10 0.00 0.00 575723.92 0.00 0.288069E+09 0.360316E+09 0.00 0.36
December 0.997490E+09 0.00 0.00 47810.66 0.00 0.801413E+09 54309221.73 0.00 0.29
                   
Annual Sum or Average 0.679735E+10 0.503889E+10 0.00 22559091.94 19983709.50 0.374285E+10 0.786456E+10 0.00 0.61
Minimum of Months 1039274.16 0.00 0.00 43839.33 0.00 0.00 17347516.84 0.00 0.29
Maximum of Months 0.133898E+10 0.200936E+10 0.00 5490196.20 7506425.62 0.133088E+10 0.207376E+10 0.00 1.06



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:21:49

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.125931E+12 0.147723E+11 0.00 0.136167E+12 0.234088E+11
February 0.199854E+12 0.139640E+11 0.00 0.143394E+12 0.205299E+11
March 0.330313E+12 0.122114E+11 0.00 0.182601E+12 0.134429E+11
April 0.350430E+12 0.780235E+10 0.00 0.188563E+12 0.184158E+11
May 0.447127E+12 0.440313E+10 0.00 0.187914E+12 0.556091E+11
June 0.431785E+12 -913291436.8 0.00 0.346262E+11 0.186216E+12
July 0.424722E+12 -0.547323E+10 0.00 -0.430737E+11 0.266661E+12
August 0.411869E+12 -0.364877E+10 0.00 -0.906005E+10 0.269089E+12
September 0.292122E+12 0.811318E+09 0.00 0.927286E+11 0.133460E+12
October 0.285338E+12 0.576237E+10 0.00 0.194994E+12 0.585266E+11
November 0.139949E+12 0.113603E+11 0.00 0.183790E+12 0.102349E+11
December 0.101559E+12 0.130964E+11 0.00 0.153044E+12 0.194075E+11
           
Annual Sum or Average 0.354100E+13 0.741483E+11 0.00 0.144569E+13 0.107500E+13
Minimum of Months 0.101559E+12 -0.547323E+10 0.00 -0.430737E+11 0.102349E+11
Maximum of Months 0.447127E+12 0.147723E+11 0.00 0.194994E+12 0.269089E+12