Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2024-07-03 12:21:56
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1497.61 | 300.59 | 300.59 |
Net Site Energy | 1341.94 | 269.35 | 269.35 |
Total Source Energy | 4111.35 | 825.21 | 825.21 |
Net Source Energy | 3618.33 | 726.25 | 726.25 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 303.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 144.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 166.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 658.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 25.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 107.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 55.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1194.40 | 303.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 303.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 144.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 166.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 34.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 73.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 25.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 107.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 55.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 303.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 144.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 166.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 34.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 658.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 25.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 107.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 55.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 62.12 | 60.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 137.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 239.73 | 60.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 62.12 | 60.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 137.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 239.73 | 60.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 162.613 | 13.61 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -6.94 | -0.6 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 155.676 | 13.03 |
Electricity Coming From Utility | 1039.318 | 87.02 |
Surplus Electricity Going To Utility | 0.592 | 0.05 |
Net Electricity From Utility | 1038.727 | 86.97 |
Total On-Site and Utility Electric Sources | 1194.403 | 100.00 |
Total Electricity End Uses | 1194.403 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 282.83 |
Time Setpoint Not Met During Occupied Cooling | 208.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2109.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 61.8568 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 18.6880 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 18.6880 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 61.8568 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 18.6880 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 18.6880 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 18.6880 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-15:09 | 23-DEC-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 222058.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 69391.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 13903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 38861.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31085.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4249.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 158908.33 | 222058.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 222058.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 69391.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 13903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 4325.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 48.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 31085.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4249.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 328.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 457.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 527.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 107.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2086.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 80.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 340.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 176.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3782.68 | 328.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 65.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 91.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 105.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 418.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 16.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 68.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 759.24 | 65.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 65.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 91.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 105.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 418.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 16.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 68.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 759.24 | 65.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.74 | 0.273231 | 0.232000 | 0.636361 | 0.728616 | 0.500000 | 0.001394 | 0.000118 | 0.636361 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.40 | 0.312299 | 0.265000 | 0.635948 | 0.832796 | 0.500000 | 0.001220 | 0.000180 | 0.753226 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.56 | 0.292840 | 0.249000 | 0.637257 | 0.780906 | 0.500000 | 0.001301 | 0.000329 | 1.38 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.804747 | 0.196325 | 0.167000 | 0.134393 | 0.523532 | 0.500000 | 0.001941 | 0.000146 | 0.612873 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.937005 | 0.106746 | 0.091000 | 0.085267 | 0.300000 | 0.500000 | 0.003569 | 0.000096 | 0.403543 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.10 | 0.143625 | 0.122000 | 0.134203 | 0.383000 | 0.500000 | 0.002653 | 0.000147 | 0.616826 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.07 | 0.093421 | 0.079000 | 0.084576 | 0.300000 | 0.500000 | 0.004078 | 0.000096 | 0.403536 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.612609 | 0.257900 | 0.219000 | 0.134161 | 0.687733 | 0.500000 | 0.001477 | 0.000112 | 0.470054 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.756337 | 0.132245 | 0.112000 | 0.084710 | 0.352654 | 0.500000 | 0.002881 | 0.000074 | 0.312479 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.862137 | 0.183256 | 0.156000 | 0.134493 | 0.488682 | 0.500000 | 0.002079 | 0.000113 | 0.474333 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.827938 | 0.120800 | 0.103000 | 0.085278 | 0.322134 | 0.500000 | 0.003154 | 0.000074 | 0.312476 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.694908 | 0.227356 | 0.193000 | 0.134117 | 0.606283 | 0.500000 | 0.001676 | 0.000114 | 0.477501 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.930374 | 0.300000 | 0.500000 | 0.003544 | 0.000075 | 0.317156 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.994929 | 0.158797 | 0.135000 | 0.134315 | 0.423459 | 0.500000 | 0.002399 | 0.000115 | 0.481037 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.990561 | 0.100968 | 0.086000 | 0.085188 | 0.300000 | 0.500000 | 0.003773 | 0.000075 | 0.317153 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 13446.70 | 0.000118 | 322.17 |
CORE_MID VAV BOX REHEAT COIL | 20581.00 | 0.000180 | 543.78 |
CORE_TOP VAV BOX REHEAT COIL | 37610.71 | 0.000329 | 992.48 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16671.17 | 0.000146 | 439.57 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10976.40 | 0.000096 | 289.41 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16778.52 | 0.000147 | 442.40 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10976.21 | 0.000096 | 289.41 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 12791.51 | 0.000112 | 337.34 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8502.65 | 0.000074 | 224.23 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12907.72 | 0.000113 | 340.40 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8502.57 | 0.000074 | 224.22 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 12994.06 | 0.000114 | 342.68 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 8629.86 | 0.000075 | 227.58 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 13090.10 | 0.000115 | 345.21 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 8629.78 | 0.000075 | 227.58 |
PACU_VAV_BOT HEATING COIL | 25359.90 | 0.000222 | 415.29 |
PACU_VAV_MID HEATING COIL | 25595.04 | 0.000224 | 418.26 |
PACU_VAV_TOP HEATING COIL | 25004.29 | 0.000219 | 415.30 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.90 | 1.08 | 5.80 | 1.99 | 5.08 | 5.08 | 0.300000 | 0.392598 | 5.08 |
PACU_VAV_MID | 3.01 | 1.07 | 6.01 | 2.35 | 5.01 | 5.01 | 0.300000 | 0.467830 | 5.01 |
PACU_VAV_TOP | 3.24 | 1.08 | 6.47 | 3.42 | 5.86 | 5.86 | 0.300000 | 0.582991 | 5.86 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.08 |
PACU_VAV_MID_OA_CONTROLLER | 5.01 |
PACU_VAV_TOP_OA_CONTROLLER | 5.86 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.08 | 84076.56 | 0.800655 | 1.69 | 28022.72 | 0.800655 |
PACU_VAV_MID COOLING COIL | 5.01 | 83012.81 | 0.800655 | 1.67 | 27668.17 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 5.86 | 97024.08 | 0.800655 | 1.95 | 32338.12 | 0.800655 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.08 |
PACU_VAV_MID FAN | 5.01 |
PACU_VAV_TOP FAN | 5.86 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000222 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000224 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000219 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002529 | 0.303446 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.002529 | 754.00 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 289048.18 | 289048.18 | 0.002529 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 61.857 | 0.000 | 0.000 | 0.000 | 0.000 | 67.661 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 51196.000 | 52.053 | 967.081 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 3043.602 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 1600.000 | 1.627 | 30.224 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1281.968 | 1600.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5358 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5301 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.6467 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.632 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.652 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.312 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.34415616E-12 | 0.73563561E-15 | -0.10764161E-12 | 0.10685741E-15 |
43 | 6 | 0.31504638E-07 | 0.15474724E-09 | 0.71933787E-08 | -0.15048178E-12 |
44 | 5 | -0.20438857E-03 | 0.13016735E-05 | -0.10492214E-03 | 0.71015789E-08 |
45 | 4 | 0.30870407 | 0.62380386E-03 | 0.10564545 | -0.35923044E-04 |
46 | 3 | -7.5938769 | 0.19061556E-01 | -2.4361333 | 0.30615224E-01 |
47 | 2 | 41.951003 | 0.66938758E-01 | 15.662994 | -0.34536947 |
48 | 1 | -81.372858 | 0.29881068E-01 | -29.498176 | 1.0962451 |
49 | 0 | 46.824334 | 0.59474289E-03 | 16.282875 | |
50 | 7 | -0.34405391E-12 | 0.74902691E-15 | -0.11167434E-12 | 0.10710038E-15 |
51 | 6 | 0.31570920E-07 | 0.15318783E-09 | 0.72080048E-08 | -0.15084089E-12 |
52 | 5 | -0.20472033E-03 | 0.12880691E-05 | -0.10508761E-03 | 0.71158009E-08 |
53 | 4 | 0.30908525 | 0.61707511E-03 | 0.10578288 | -0.35977555E-04 |
54 | 3 | -7.6014096 | 0.18850271E-01 | -2.4383697 | 0.30652185E-01 |
55 | 2 | 41.975828 | 0.66179041E-01 | 15.672127 | -0.34564605 |
56 | 1 | -81.391862 | 0.29534967E-01 | -29.506353 | 1.0966501 |
57 | 0 | 46.824333 | 0.58771801E-03 | 16.282688 | |
58 | 7 | -0.33303739E-12 | 0.11430073E-14 | -0.10564856E-12 | 0.99270328E-16 |
59 | 6 | 0.30206507E-07 | 0.18467178E-09 | 0.69068382E-08 | -0.14346196E-12 |
60 | 5 | -0.19787007E-03 | 0.15652367E-05 | -0.10166770E-03 | 0.68228702E-08 |
61 | 4 | 0.30118360 | 0.75522621E-03 | 0.10293566 | -0.34850853E-04 |
62 | 3 | -7.4451882 | 0.23217066E-01 | -2.3919942 | 0.29885849E-01 |
63 | 2 | 41.460907 | 0.81970212E-01 | 15.482559 | -0.33990950 |
64 | 1 | -80.997597 | 0.36763750E-01 | -29.336578 | 1.0882477 |
65 | 0 | 46.824336 | 0.73512635E-03 | 16.286622 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2115E-002 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2185E-002 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3381E-002 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3442E-002 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2296E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2785E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3510E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3752E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1673 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.9797E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1898 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1018 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1171 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9932E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8073E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8035E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2114E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2182E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3379E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3439E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2287E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2767E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3507E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3749E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9676E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1014E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4146E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7166E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8760E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4795E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6444E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6601E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4127E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.4391E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9814E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0004E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8688E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8752E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0780E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0864E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6216E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6789E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8576E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9030E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3633E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3952E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3507E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3749E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4064E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5257E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3885E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9215E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1342E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3231E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8073E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8035E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6219E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6792E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8579E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9035E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3638E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3963E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3510E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3752E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.1305E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1788E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6184E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8137E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0092E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5415E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6444E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6601E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5398E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.6232E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1423E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.2355E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9599E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.9915E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0782E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0865E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1655 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1068 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1844 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1201 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1252 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3046E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.4807E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.5582E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.7376E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.9712E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2148E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6039E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.7160E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.3853E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5395E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5971E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0217E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.2920E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.9352E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5798E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6825E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9276E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.4807E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5582E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8959E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0471E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.4126E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6992E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8457E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4455E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5395E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5971E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1655 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1068 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1844 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1200 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1252 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3038E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.4802E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.5579E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.7376E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.9709E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.2147E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6037E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.7156E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.3849E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5390E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5968E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0219E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.2919E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.9353E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5797E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6823E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9274E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.4802E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5579E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8959E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0468E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.4125E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6989E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8453E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4451E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5390E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5968E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 30903.25974 | 30903.25974 | 2.74293 | 2.74293 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 8245.73502 | 8245.73502 | 0.43571 | 0.43571 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27054.16412 | 27054.16412 | 2.39980 | 2.39980 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 14424.90528 | 14424.90528 | 0.75323 | 0.75323 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28591.75519 | 28591.75519 | 2.55927 | 2.55927 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 26329.86080 | 26329.86080 | 1.38026 | 1.38026 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8990.83998 | 8990.83998 | 0.80475 | 0.80475 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 11663.55116 | 11663.55116 | 0.61287 | 0.61287 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10468.55630 | 10468.55630 | 0.93701 | 0.93701 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7679.17775 | 7679.17775 | 0.40354 | 0.40354 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12289.83607 | 12289.83607 | 1.10003 | 1.10003 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 11738.60077 | 11738.60077 | 0.61683 | 0.61683 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11960.93914 | 11960.93914 | 1.07058 | 1.07058 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 7679.04389 | 7679.04389 | 0.40354 | 0.40354 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6844.12538 | 6844.12538 | 0.61261 | 0.61261 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 8950.54552 | 8950.54552 | 0.47005 | 0.47005 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8449.96437 | 8449.96437 | 0.75634 | 0.75634 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.59867 | 5.46414E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5949.27800 | 5949.27800 | 0.31248 | 0.31248 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9631.92119 | 9631.92119 | 0.86214 | 0.86214 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 9031.78327 | 9031.78327 | 0.47433 | 0.47433 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9249.92072 | 9249.92072 | 0.82794 | 0.82794 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.08800 | 5.47095E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5949.22283 | 5949.22283 | 0.31248 | 0.31248 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7763.64409 | 7763.64409 | 0.69491 | 0.69491 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 9092.60028 | 9092.60028 | 0.47750 | 0.47750 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10394.44384 | 10394.44384 | 0.93037 | 0.93037 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.29133 | 5.46218E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6038.51372 | 6038.51372 | 0.31716 | 0.31716 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11115.58046 | 11115.58046 | 0.99493 | 0.99493 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 33.28333 | 5.47432E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 9159.73833 | 9159.73833 | 0.48104 | 0.48104 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11066.86383 | 11066.86383 | 0.99056 | 0.99056 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6038.45613 | 6038.45613 | 0.31715 | 0.31715 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 65148.89 | 5.07906 | 5.07906 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 28778.51 | 1.99403 | 1.99403 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 64368.19 | 5.01480 | 5.01480 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 28673.84 | 2.34607 | 2.34607 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 73603.89 | 5.86122 | 5.86122 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 28414.83 | 3.41704 | 3.41704 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.74293 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27323 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63636 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72862 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39442E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17638E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63636 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13446.69760 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17638E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 322.16797 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.39980 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31230 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63595 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83280 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21999E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.80052E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75323 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20581.00209 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80052E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 543.78322 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.55927 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29284 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24900 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63726 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78091 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30105E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.29035E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.38026 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37610.71361 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.29035E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 992.48458 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80475 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19632 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16700 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13439 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52353 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.94066E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45847E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.61287 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16671.16814 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45847E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 439.57494 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93701 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10675 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.10000E-002 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52675E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.56921E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.60264E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40354 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10976.40200 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.60264E-005 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 289.41115 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10003 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14363 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12200 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13420 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38300 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65274E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.46786E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.61683 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16778.51916 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.46786E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 442.40355 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07058 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.34213E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.90000E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.45760E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.07830E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.60247E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40354 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10976.21098 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.60247E-005 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 289.40610 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61261 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25790 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21900 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13416 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68773 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47732E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.11906E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47005 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12791.50512 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11906E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 337.34172 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75634 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13225 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11200 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47097E-002 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35265 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88101E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.43849E-005 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31248 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8502.65002 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.43849E-005 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 224.22528 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86214 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18326 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15600 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13449 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48868 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.07906E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12922E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47433 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12907.71697 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12922E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 340.40381 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82794 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12080 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10300 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52776E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32213 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.15396E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.43842E-005 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31248 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8502.57157 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.43842E-005 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 224.22321 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69491 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22736 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19300 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13412 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60628 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.67578E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.13678E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47750 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12994.05751 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13678E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 342.68226 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93037 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.54395E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.54978E-005 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31716 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8629.86134 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.54978E-005 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 227.57929 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99493 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15880 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13500 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13432 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42346 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.39929E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14518E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.48104 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13090.09660 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14518E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 345.21280 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99056 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10097 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.60000E-002 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51882E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.77346E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.54971E-005 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31715 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8629.77943 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.54971E-005 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 227.57712 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.90098 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07500 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.80195 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.99403 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.07906 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.07906 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.39260 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.00529 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07423 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.01057 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.34607 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.01480 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.01480 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.46783 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.23582 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07570 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.47163 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.41704 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.86122 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.86122 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.58299 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.07906 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.01480 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.86122 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.07906 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.07906 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 84076.55683 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.69285 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28022.71639 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 25359.90384 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.21859E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 415.29019 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.07906 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.21859E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.01480 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.01480 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 83012.81306 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.67143 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27668.17059 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 25595.03846 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.23917E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 418.26182 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.01480 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.23917E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.86122 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.86122 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 97024.07576 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.95355 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32338.12445 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 25004.28580 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.18748E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 415.30058 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.86122 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.18748E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.52872E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.30345 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.52872E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 753.99929 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 289048.18025 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 289048.18000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.52872E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 12744.49 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 19514.32 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 35652.97 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 15801.02 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10403.44 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 15902.76 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10403.26 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 12124.29 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8059.08 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12234.42 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8059.00 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 12316.26 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 8179.65 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 12407.28 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 8179.57 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 19330.34 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 19425.14 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 19618.06 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 82629.81 | 281944.61 | 12.55 | 3.13 | 3.60 | 3.79 | 3.97 | 10.69 | 12.27 | 12.92 | 13.53 | 4.7684 | 3.7699 | 2.5272 | 1.0703 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 81584.37 | 278377.42 | 12.55 | 3.13 | 3.60 | 3.79 | 3.97 | 10.69 | 12.27 | 12.92 | 13.53 | 4.7081 | 3.7222 | 2.4953 | 1.0567 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 95354.53 | 325363.17 | 12.55 | 3.13 | 3.60 | 3.79 | 3.97 | 10.69 | 12.27 | 12.92 | 13.53 | 5.5027 | 4.3505 | 2.9164 | 1.2351 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.0692819980E-002 | 0.1002444581 | Pass | Pass | 9.0443021991E-002 | 0.2841946926 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.7764262464E-002 | 8.1209133691E-002 | Pass | Pass | 7.8052531197E-002 | 0.4416082979 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.3690575930E-002 | 5.2902290156E-002 | Pass | Pass | 0.1021540756 | 0.3468508561 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.3667799758E-002 | 2.9880382879E-002 | Pass | Pass | 0.1390385550 | 0.4533485687 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.9542322026E-002 | 6.9800572863E-002 | Pass | Pass | 7.6728037570E-002 | 0.2639027464 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.0729049140E-002 | 4.1799266052E-002 | Pass | Pass | 3.4873529763E-002 | 0.1789486779 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.0397831116E-002 | 3.4935461590E-002 | Pass | Pass | 3.4301320685E-002 | 0.1715167615 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.1900312278E-002 | 0.1309464562 | Pass | Pass | 3.5164124111E-002 | 0.1815265669 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1729094770 | 0.1652785627 | Pass | Pass | 5.6745587314E-002 | 0.2909996284 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1015402667 | 0.1166051512 | Pass | Pass | 3.2646843363E-002 | 0.1592899180 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.4694876749E-002 | 3.9478694157E-002 | Pass | Pass | 9.2207191633E-002 | 0.2859982969 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.5146280183E-002 | 0.1233319188 | Pass | Pass | 9.1903988133E-002 | 0.2883783097 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1405818554 | 0.1810891196 | Pass | Pass | 0.1014971861 | 0.3005609540 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.4448191851E-002 | 0.1044612242 | Pass | Pass | 8.8205373460E-002 | 0.2755179603 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.6016042455E-002 | 4.1561941315E-002 | Pass | Pass | 7.6453528608E-002 | 0.2639922567 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1011486294 | 0.1453129055 | Pass | Pass | 7.8188487658E-002 | 0.2688671876 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1961153215 | 0.2490483250 | Pass | Pass | 0.1019598894 | 0.3556235685 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.9602521076E-002 | 0.1171118998 | Pass | Pass | 7.3413606479E-002 | 0.2534383153 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4107.14 | 75.41 | 0.00 | 1901.27 | 860.33 | 6944.15 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.378 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.378 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.378 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
North Total or Average | 195.79 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.062 | 0.379 | 0.417 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.51 | 0.0000 | Y | 4.86 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.48 | 0.0000 | Y | 3.07 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.23 | 0.0000 | Y | 4.79 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.23 | 0.0000 | Y | 3.04 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.48 | 0.0000 | Y | 4.85 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.45 | 0.0000 | Y | 3.07 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.20 | 0.0000 | Y | 4.79 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.20 | 0.0000 | Y | 3.03 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.51 | 0.0000 | Y | 4.86 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.48 | 0.0000 | Y | 3.07 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.23 | 0.0000 | Y | 4.79 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.23 | 0.0000 | Y | 3.04 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 166.65 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 42.26 | 42.26 | 4.30 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.67 | 62.97 | 3.31 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.67 | 46.88 | 26.42 | |
Exterior Lighting Total | 3824.74 | 34.03 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 289048.18 | 0.84 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 84076.56 | 67316.34 | 16760.22 | 0.80 | 3.88 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 83012.81 | 66464.65 | 16548.17 | 0.80 | 3.88 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 97024.08 | 77682.84 | 19341.24 | 0.80 | 3.88 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 82629.8 | 3.13 | 10.69 | N/A | N/A | 12.55 | |
PACU_VAV_MID COOLING COIL | 81584.4 | 3.13 | 10.69 | N/A | N/A | 12.55 | |
PACU_VAV_TOP COOLING COIL | 95354.5 | 3.13 | 10.69 | N/A | N/A | 12.55 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 13446.70 | 12744.49 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 20581.00 | 19514.32 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 37610.71 | 35652.97 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16671.17 | 15801.02 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 10976.40 | 10403.44 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16778.52 | 15902.76 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10976.21 | 10403.26 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12791.51 | 12124.29 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 8502.65 | 8059.08 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12907.72 | 12234.42 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 8502.57 | 8059.00 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12994.06 | 12316.26 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 8629.86 | 8179.65 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13090.10 | 12407.28 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 8629.78 | 8179.57 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 25359.90 | 19330.34 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 25595.04 | 19425.14 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 25004.29 | 19618.06 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.08 | 11046.40 | 2174.89 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.01 | 10977.46 | 2189.01 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.86 | 12747.51 | 2174.89 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002529 | 754.00 | 298174.34 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 82629.81 | 3.13 | 10.69 | 12.55 | 4.7684 | 3.60 | 12.27 | 3.7699 | 3.79 | 12.92 | 2.5272 | 3.97 | 13.53 | 1.0703 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 81584.37 | 3.13 | 10.69 | 12.55 | 4.7081 | 3.60 | 12.27 | 3.7222 | 3.79 | 12.92 | 2.4953 | 3.97 | 13.53 | 1.0567 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 95354.53 | 3.13 | 10.69 | 12.55 | 5.5027 | 3.60 | 12.27 | 4.3505 | 3.79 | 12.92 | 2.9164 | 3.97 | 13.53 | 1.2351 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 30903.26 | 30903.26 | 31.42 | 2.743 | 2.743 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 22.95 | 0.00546 | 0.425 | 0.00 |
CORE_MID | 27054.16 | 27054.16 | 27.51 | 2.400 | 2.400 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 22.95 | 0.00546 | 0.425 | 0.00 |
CORE_TOP | 28591.76 | 28591.76 | 29.07 | 2.559 | 2.559 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00892 | 33.75 | 0.00548 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8990.84 | 8990.84 | 43.36 | 0.805 | 0.805 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00873 | 33.75 | 0.00548 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10468.56 | 10468.56 | 79.75 | 0.937 | 0.937 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00863 | 25.76 | 0.00546 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12289.84 | 12289.84 | 59.27 | 1.100 | 1.100 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00867 | 33.53 | 0.00547 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11960.94 | 11960.94 | 91.13 | 1.071 | 1.071 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00861 | 32.03 | 0.00547 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6844.13 | 6844.13 | 33.01 | 0.613 | 0.613 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00884 | 33.90 | 0.00548 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8449.96 | 8449.96 | 64.37 | 0.756 | 0.756 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00867 | 26.60 | 0.00546 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9631.92 | 9631.92 | 46.46 | 0.862 | 0.862 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00874 | 33.53 | 0.00547 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9249.92 | 9249.92 | 70.47 | 0.828 | 0.828 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00866 | 31.09 | 0.00547 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7763.64 | 7763.64 | 37.44 | 0.695 | 0.695 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00878 | 33.90 | 0.00548 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10394.44 | 10394.44 | 79.19 | 0.930 | 0.930 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00863 | 25.29 | 0.00546 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11115.58 | 11115.58 | 53.61 | 0.995 | 0.995 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00870 | 33.28 | 0.00547 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11066.86 | 11066.86 | 84.32 | 0.991 | 0.991 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00862 | 31.83 | 0.00547 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 8245.74 | 8245.74 | 8.38 | 0.436 | 0.436 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
CORE_MID | 14424.91 | 14424.91 | 14.67 | 0.753 | 0.753 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
CORE_TOP | 26329.86 | 26329.86 | 26.77 | 1.380 | 1.380 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11663.55 | 11663.55 | 56.25 | 0.613 | 0.613 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7679.18 | 7679.18 | 58.50 | 0.404 | 0.404 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11738.60 | 11738.60 | 56.62 | 0.617 | 0.617 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 7679.04 | 7679.04 | 58.51 | 0.404 | 0.404 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8950.55 | 8950.55 | 43.17 | 0.470 | 0.470 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5949.28 | 5949.28 | 45.32 | 0.312 | 0.312 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9031.78 | 9031.78 | 43.56 | 0.474 | 0.474 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 5949.22 | 5949.22 | 45.33 | 0.312 | 0.312 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9092.60 | 9092.60 | 43.85 | 0.478 | 0.478 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6038.51 | 6038.51 | 46.00 | 0.317 | 0.317 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9159.74 | 9159.74 | 44.18 | 0.481 | 0.481 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6038.46 | 6038.46 | 46.01 | 0.317 | 0.317 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -17.90 | 0.00096 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.08 | 5.08 | 1.99 | 1.99 | 5.0791 | 1.9940 | 5.0791 | 0.3926 | 0.3000 |
PACU_VAV_MID | 5.01 | 5.01 | 2.35 | 2.35 | 5.0148 | 2.3461 | 5.0148 | 0.4678 | 0.3000 |
PACU_VAV_TOP | 5.86 | 5.86 | 3.42 | 3.42 | 5.8612 | 3.4170 | 5.8612 | 0.5830 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 13446.698 | 13446.698 | 0.636361 | 0.00011764 | 322.168 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 13446.70 | 13446.70 | 0.636361 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 8245.74 | 0.00 | 13490.34 | 13490.34 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 20581.002 | 20581.002 | 0.753226 | 0.00018005 | 543.783 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20581.00 | 20581.00 | 0.753226 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 14424.91 | 0.00 | 20655.76 | 20655.76 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 37610.714 | 37610.714 | 1.380262 | 0.00032903 | 992.485 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 37610.71 | 37610.71 | 1.380262 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 26329.86 | 0.00 | 37738.36 | 37738.36 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 16671.168 | 16671.168 | 0.612873 | 0.00014585 | 439.575 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16671.17 | 16671.17 | 0.612873 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00788666 | 41.3938 | 11663.55 | 0.00 | 16725.23 | 16725.23 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 10976.402 | 10976.402 | 0.403543 | 0.00009603 | 289.411 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10976.40 | 10976.40 | 0.403543 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00788539 | 41.3873 | 7679.18 | 0.00 | 11011.94 | 11011.94 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 16778.519 | 16778.519 | 0.616826 | 0.00014679 | 442.404 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16778.52 | 16778.52 | 0.616826 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00788740 | 41.3976 | 11738.60 | 0.00 | 16832.92 | 16832.92 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 10976.211 | 10976.211 | 0.403536 | 0.00009602 | 289.406 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10976.21 | 10976.21 | 0.403536 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00788539 | 41.3873 | 7679.04 | 0.00 | 11011.75 | 11011.75 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 12791.505 | 12791.505 | 0.470054 | 0.00011191 | 337.342 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12791.51 | 12791.51 | 0.470054 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00791368 | 41.5333 | 8950.55 | 0.00 | 12833.44 | 12833.44 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8502.650 | 8502.650 | 0.312479 | 0.00007438 | 224.225 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8502.65 | 8502.65 | 0.312479 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00791598 | 41.5453 | 5949.28 | 0.00 | 8530.46 | 8530.46 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 12907.717 | 12907.717 | 0.474333 | 0.00011292 | 340.404 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12907.72 | 12907.72 | 0.474333 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00791504 | 41.5404 | 9031.78 | 0.00 | 12950.02 | 12950.02 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8502.572 | 8502.572 | 0.312476 | 0.00007438 | 224.223 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8502.57 | 8502.57 | 0.312476 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00791598 | 41.5453 | 5949.22 | 0.00 | 8530.38 | 8530.38 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 12994.058 | 12994.058 | 0.477501 | 0.00011368 | 342.682 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12994.06 | 12994.06 | 0.477501 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00787410 | 41.3286 | 9092.60 | 0.00 | 13036.65 | 13036.65 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 8629.861 | 8629.861 | 0.317156 | 0.00007550 | 227.579 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8629.86 | 8629.86 | 0.317156 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00787536 | 41.3351 | 6038.51 | 0.00 | 8658.08 | 8658.08 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 13090.097 | 13090.097 | 0.481037 | 0.00011452 | 345.213 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13090.10 | 13090.10 | 0.481037 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00787533 | 41.3350 | 9159.74 | 0.00 | 13132.99 | 13132.99 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 8629.779 | 8629.779 | 0.317153 | 0.00007550 | 227.577 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8629.78 | 8629.78 | 0.317153 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00787536 | 41.3352 | 6038.46 | 0.00 | 8658.00 | 8658.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 84076.557 | 67316.337 | 5.079065 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 81862.43 | 81862.43 | 5.079065 | 25.86 | 14.63 | 0.00820909 | 10.62 | 9.07 | 0.00820909 | 33.90 | 0.00547527 | 15.07 | 18.8243 | 24.00 | 0.00884326 | 38.6227 | 56728.13 | 0.00 | 86694.22 | 61753.57 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 25359.904 | 25359.904 | 1.523719 | 0.00022186 | 415.290 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25359.90 | 25359.90 | 1.523719 | -4.15 | -4.15 | 0.00346993 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 62.7478 | 18.35 | 0.00769755 | 47.6475 | 12226.91 | 0.00 | 23382.14 | 23382.14 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 83012.813 | 66464.645 | 5.014804 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 80826.70 | 80826.70 | 5.014804 | 25.89 | 14.63 | 0.00819790 | 10.60 | 9.05 | 0.00819790 | 33.90 | 0.00547527 | 15.07 | 19.0656 | 24.00 | 0.00884054 | 38.6109 | 55935.22 | 0.00 | 85597.35 | 60972.26 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 25595.038 | 25595.038 | 1.504441 | 0.00022392 | 418.262 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25595.04 | 25595.04 | 1.504441 | -4.52 | -4.52 | 0.00340772 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 63.5518 | 17.82 | 0.00769762 | 49.2620 | 12702.16 | 0.00 | 23496.05 | 23496.05 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 97024.076 | 77682.837 | 5.861224 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 94468.98 | 94468.98 | 5.861224 | 25.62 | 14.58 | 0.00824650 | 10.62 | 9.11 | 0.00824650 | 33.90 | 0.00547527 | 15.07 | 16.3123 | 24.00 | 0.00878830 | 38.3858 | 65316.02 | 0.00 | 100044.85 | 71263.42 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 25004.286 | 25004.286 | 1.758367 | 0.00021875 | 415.301 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25004.29 | 25004.29 | 1.758367 | -1.68 | -1.68 | 0.00405744 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 54.3743 | 17.39 | 0.00765680 | 50.3606 | 17827.85 | 0.00 | 23735.83 | 23735.83 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 13446.698 | 13446.698 | 0.636361 | 0.00011764 | 322.168 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 4.5603 | 4.652061 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 13446.70 | 13446.70 | 1.0000 | 0.62200305 | 0.636361 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.11762558 | 60.00 | 32.22 | 27.78 | 0.000 | 13446.70 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.01 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 8245.74 | 0.00 | 13490.34 | 13490.34 | 0.62200305 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.07 | 19.36 | 0.00800000 | 54748.4 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 20581.002 | 20581.002 | 0.753226 | 0.00018005 | 543.783 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 6.9798 | 7.120267 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20581.00 | 20581.00 | 1.0000 | 0.73623122 | 0.753226 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.18003322 | 60.00 | 32.22 | 27.78 | 0.000 | 20581.00 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 14424.91 | 0.00 | 20655.76 | 20655.76 | 0.73623122 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.31 | 21.28 | 0.00800000 | 61115.9 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 37610.714 | 37610.714 | 1.380262 | 0.00032903 | 992.485 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 12.7552 | 13.011918 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 37610.71 | 37610.71 | 1.0000 | 1.34912043 | 1.380262 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.32900136 | 60.00 | 32.22 | 27.78 | 0.000 | 37610.71 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 26329.86 | 0.00 | 37738.36 | 37738.36 | 1.34912043 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61032.4 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16671.168 | 16671.168 | 0.612873 | 0.00014585 | 439.575 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 5.6538 | 5.767609 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16671.17 | 16671.17 | 1.0000 | 0.59904553 | 0.612873 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.14583177 | 60.00 | 32.22 | 27.78 | 0.000 | 16671.17 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00788666 | 21.00 | 0.00788666 | 41.3938 | 11663.55 | 0.00 | 16725.23 | 16725.23 | 0.59904553 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60979.6 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10976.402 | 10976.402 | 0.403543 | 0.00009603 | 289.411 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 3.7225 | 3.797430 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10976.40 | 10976.40 | 1.0000 | 0.39443849 | 0.403543 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.09601656 | 60.00 | 32.22 | 27.78 | 0.000 | 10976.40 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00788539 | 21.00 | 0.00788539 | 41.3873 | 7679.18 | 0.00 | 11011.94 | 11011.94 | 0.39443849 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60977.8 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16778.519 | 16778.519 | 0.616826 | 0.00014679 | 442.404 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 5.6902 | 5.804748 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16778.52 | 16778.52 | 1.0000 | 0.60290880 | 0.616826 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.14677083 | 60.00 | 32.22 | 27.78 | 0.000 | 16778.52 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00788740 | 21.00 | 0.00788740 | 41.3976 | 11738.60 | 0.00 | 16832.92 | 16832.92 | 0.60290880 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60979.3 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10976.211 | 10976.211 | 0.403536 | 0.00009602 | 289.406 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 3.7224 | 3.797364 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10976.21 | 10976.21 | 1.0000 | 0.39443165 | 0.403536 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.09601489 | 60.00 | 32.22 | 27.78 | 0.000 | 10976.21 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00788539 | 21.00 | 0.00788539 | 41.3873 | 7679.04 | 0.00 | 11011.75 | 11011.75 | 0.39443165 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60977.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12791.505 | 12791.505 | 0.470054 | 0.00011191 | 337.342 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 4.3381 | 4.425389 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12791.51 | 12791.51 | 1.0000 | 0.45944881 | 0.470054 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.11189425 | 60.00 | 32.22 | 27.78 | 0.000 | 12791.51 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00791368 | 21.00 | 0.00791368 | 41.5333 | 8950.55 | 0.00 | 12833.44 | 12833.44 | 0.45944881 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.1 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8502.650 | 8502.650 | 0.312479 | 0.00007438 | 224.225 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 2.8836 | 2.941603 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8502.65 | 8502.65 | 1.0000 | 0.30542840 | 0.312479 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.07437730 | 60.00 | 32.22 | 27.78 | 0.000 | 8502.65 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00791598 | 21.00 | 0.00791598 | 41.5453 | 5949.28 | 0.00 | 8530.46 | 8530.46 | 0.30542840 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12907.717 | 12907.717 | 0.474333 | 0.00011292 | 340.404 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 4.3775 | 4.465594 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12907.72 | 12907.72 | 1.0000 | 0.46363093 | 0.474333 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.11291082 | 60.00 | 32.22 | 27.78 | 0.000 | 12907.72 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00791504 | 21.00 | 0.00791504 | 41.5404 | 9031.78 | 0.00 | 12950.02 | 12950.02 | 0.46363093 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8502.572 | 8502.572 | 0.312476 | 0.00007438 | 224.223 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 2.8835 | 2.941576 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8502.57 | 8502.57 | 1.0000 | 0.30542561 | 0.312476 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.07437662 | 60.00 | 32.22 | 27.78 | 0.000 | 8502.57 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00791598 | 21.00 | 0.00791598 | 41.5453 | 5949.22 | 0.00 | 8530.38 | 8530.38 | 0.30542561 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.3 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12994.058 | 12994.058 | 0.477501 | 0.00011368 | 342.682 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 4.4068 | 4.495464 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12994.06 | 12994.06 | 1.0000 | 0.46672782 | 0.477501 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.11366609 | 60.00 | 32.22 | 27.78 | 0.000 | 12994.06 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00787410 | 21.00 | 0.00787410 | 41.3286 | 9092.60 | 0.00 | 13036.65 | 13036.65 | 0.46672782 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.8 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8629.861 | 8629.861 | 0.317156 | 0.00007550 | 227.579 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 2.9267 | 2.985613 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8629.86 | 8629.86 | 1.0000 | 0.31000016 | 0.317156 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.07549009 | 60.00 | 32.22 | 27.78 | 0.000 | 8629.86 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00787536 | 21.00 | 0.00787536 | 41.3351 | 6038.51 | 0.00 | 8658.08 | 8658.08 | 0.31000016 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.1 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13090.097 | 13090.097 | 0.481037 | 0.00011452 | 345.213 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 4.4393 | 4.528690 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13090.10 | 13090.10 | 1.0000 | 0.47018404 | 0.481037 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.11450619 | 60.00 | 32.22 | 27.78 | 0.000 | 13090.10 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00787533 | 21.00 | 0.00787533 | 41.3350 | 9159.74 | 0.00 | 13132.99 | 13132.99 | 0.47018404 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8629.779 | 8629.779 | 0.317153 | 0.00007550 | 227.577 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 2.9267 | 2.985585 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8629.78 | 8629.78 | 1.0000 | 0.30999725 | 0.317153 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.07548937 | 60.00 | 32.22 | 27.78 | 0.000 | 8629.78 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00787536 | 21.00 | 0.00787536 | 41.3352 | 6038.46 | 0.00 | 8658.00 | 8658.00 | 0.30999725 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.1 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 84076.557 | 67316.337 | 5.079065 | -999.0 | -999.000 | -999.0000 | 1.09062 | 1.00000 | 1020.1003 | 1004.8586 | 0.9774 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.079065 | 4.96446897 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 81862.43 | 81862.43 | 0.9737 | 4.96446897 | 5.079065 | 25.86 | 14.63 | 0.00820909 | 46913.4 | 10.62 | 9.07 | 0.00820909 | 31362.6 | -999.0 | -999.00 | -999.00 | -999.00 | 11046.399 | 70816.03 | 33.90 | 0.00547527 | 15.07 | 0.95610000 | 18.8243 | 24.00 | 0.00884326 | 24.00 | 0.00884326 | 38.6227 | 56728.13 | 0.00 | 86694.22 | 61753.57 | 4.76840997 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 25359.904 | 25359.904 | 1.523719 | 0.00022186 | 415.290 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.079065 | 4.96446897 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 8.6005 | 8.773591 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25359.90 | 25359.90 | 1.0000 | 1.48934069 | 1.523719 | -4.15 | -4.15 | 0.00346993 | 4486.0 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 0.22183687 | 60.00 | 32.22 | 27.78 | 0.000 | 25359.90 | -17.90 | 0.00095524 | -17.90 | 0.95610000 | 62.7478 | 19.02 | 0.00770567 | 18.35 | 0.00769755 | 47.6475 | 12226.91 | 0.00 | 23382.14 | 23382.14 | 1.48934069 | 2.80 | 1.20 | 0.00346993 | 11509.7 | 18.32 | 9.17 | 0.00346993 | 27209.3 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 83012.813 | 66464.645 | 5.014804 | -999.0 | -999.000 | -999.0000 | 1.08779 | 1.00000 | 1020.0795 | 1004.8586 | 0.9774 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.014804 | 4.90165808 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 80826.70 | 80826.70 | 0.9737 | 4.90165808 | 5.014804 | 25.89 | 14.63 | 0.00819790 | 46911.9 | 10.60 | 9.05 | 0.00819790 | 31319.9 | -999.0 | -999.00 | -999.00 | -999.00 | 10977.461 | 69849.24 | 33.90 | 0.00547527 | 15.07 | 0.95610000 | 19.0656 | 24.00 | 0.00884054 | 24.00 | 0.00884054 | 38.6109 | 55935.22 | 0.00 | 85597.35 | 60972.26 | 4.70807964 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 25595.038 | 25595.038 | 1.504441 | 0.00022392 | 418.262 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.014804 | 4.90165808 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 8.6802 | 8.854938 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25595.04 | 25595.04 | 1.0000 | 1.47049743 | 1.504441 | -4.52 | -4.52 | 0.00340772 | 3950.4 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 0.22389372 | 60.00 | 32.22 | 27.78 | 0.000 | 25595.04 | -17.90 | 0.00095524 | -17.90 | 0.95610000 | 63.5518 | 18.81 | 0.00768391 | 17.82 | 0.00769762 | 49.2620 | 12702.16 | 0.00 | 23496.05 | 23496.05 | 1.47049743 | 2.80 | 1.11 | 0.00340772 | 11353.8 | 18.60 | 9.22 | 0.00340772 | 27332.1 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 97024.076 | 77682.837 | 5.861224 | -999.0 | -999.000 | -999.0000 | 1.10757 | 1.00000 | 1020.1698 | 1004.8586 | 0.9774 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.861224 | 5.72898120 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 94468.98 | 94468.98 | 0.9737 | 5.72898120 | 5.861224 | 25.62 | 14.58 | 0.00824650 | 46758.8 | 10.62 | 9.11 | 0.00824650 | 31457.1 | -999.0 | -999.00 | -999.00 | -999.00 | 12747.509 | 81721.47 | 33.90 | 0.00547527 | 15.07 | 0.95610000 | 16.3123 | 24.00 | 0.00878830 | 24.00 | 0.00878830 | 38.3858 | 65316.02 | 0.00 | 100044.85 | 71263.42 | 5.50272975 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 25004.286 | 25004.286 | 1.758367 | 0.00021875 | 415.301 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.861224 | 5.72898120 | 4197.9300 | 999.8980 | 2.52846162 | 54.44 | 82.22 | 27.78 | 294865.39 | 8.4799 | 8.650560 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25004.29 | 25004.29 | 1.0000 | 1.71869436 | 1.758367 | -1.68 | -1.68 | 0.00405744 | 8448.6 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 0.21872609 | 60.00 | 32.22 | 27.78 | 0.000 | 25004.29 | -17.90 | 0.00095524 | -17.90 | 0.95610000 | 54.3743 | 17.65 | 0.00775448 | 17.39 | 0.00765680 | 50.3606 | 17827.85 | 0.00 | 23735.83 | 23735.83 | 1.71869436 | 2.80 | 2.03 | 0.00405744 | 12982.1 | 16.44 | 8.97 | 0.00405744 | 26792.5 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.08 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.01 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.86 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1304.17 | 2978.83 | 50.83 |
CORE_MID | 1260.67 | 3587.17 | 280.83 |
CORE_TOP | 1755.33 | 3835.83 | 816.33 |
PERIMETER_TOP_ZN_3 | 2872.17 | 3960.00 | 1737.00 |
PERIMETER_TOP_ZN_2 | 2940.50 | 3500.83 | 1380.50 |
PERIMETER_TOP_ZN_1 | 2918.00 | 3028.83 | 1159.83 |
PERIMETER_TOP_ZN_4 | 2963.83 | 3584.00 | 1522.17 |
PERIMETER_BOT_ZN_3 | 2386.67 | 4080.33 | 1485.67 |
PERIMETER_BOT_ZN_2 | 2609.33 | 3400.17 | 983.83 |
PERIMETER_BOT_ZN_1 | 2413.50 | 3083.67 | 846.17 |
PERIMETER_BOT_ZN_4 | 2480.00 | 3512.33 | 1027.17 |
PERIMETER_MID_ZN_3 | 2369.50 | 3840.17 | 1181.17 |
PERIMETER_MID_ZN_2 | 2291.33 | 2917.17 | 948.50 |
PERIMETER_MID_ZN_1 | 2691.00 | 2754.50 | 788.33 |
PERIMETER_MID_ZN_4 | 2592.17 | 3381.00 | 1051.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4499.83 | 4453.67 | 2109.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.00 | 0.17 | 0.00 |
CORE_TOP | 4.33 | 0.00 | 4.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 47.83 | 11.83 | 29.00 | 9.33 |
PERIMETER_TOP_ZN_2 | 30.83 | 47.33 | 11.33 | 44.33 |
PERIMETER_TOP_ZN_1 | 23.33 | 59.67 | 11.67 | 57.00 |
PERIMETER_TOP_ZN_4 | 32.83 | 43.83 | 14.17 | 31.00 |
PERIMETER_BOT_ZN_3 | 10.00 | 0.00 | 9.17 | 0.00 |
PERIMETER_BOT_ZN_2 | 3.17 | 32.67 | 2.33 | 32.67 |
PERIMETER_BOT_ZN_1 | 270.33 | 74.50 | 269.50 | 72.83 |
PERIMETER_BOT_ZN_4 | 4.67 | 28.67 | 3.83 | 20.17 |
PERIMETER_MID_ZN_3 | 9.33 | 4.33 | 8.33 | 3.67 |
PERIMETER_MID_ZN_2 | 4.33 | 43.67 | 3.00 | 42.67 |
PERIMETER_MID_ZN_1 | 4.00 | 79.00 | 3.17 | 78.17 |
PERIMETER_MID_ZN_4 | 6.50 | 39.00 | 5.33 | 28.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 306.33 | 230.17 | 282.83 | 208.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 0.838 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.666 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.653 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.761 | 0.038 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 1.304 | 0.040 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 1.388 | 0.038 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 1.143 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.626 | 0.020 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 1.114 | 0.021 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 1.093 | 0.833 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.945 | 0.021 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.747 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 1.226 | 0.035 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 1.394 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 1.123 | 0.033 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.11 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 13344983.50 | 0.00 | 13344983.50 | 0.00 | 13344983.50 | 13393058.27 | 5213.08 | 412.67 | 3134.25 | 46.58 |
CORE_MID | 10653072.41 | 0.00 | 10653072.41 | 0.00 | 10653072.41 | 13393058.27 | 5561.25 | 776.62 | 2422.13 | 59.82 |
CORE_TOP | 10493159.67 | 0.00 | 10493159.67 | 0.00 | 10493159.67 | 13393058.27 | 5633.10 | 662.91 | 2463.99 | 95.06 |
PERIMETER_TOP_ZN_3 | 2573904.07 | 0.00 | 2573904.07 | 260558.58 | 2834462.65 | 2823374.22 | 4793.15 | 613.98 | 3352.87 | 95.06 |
PERIMETER_TOP_ZN_2 | 2779066.82 | 0.00 | 2779066.82 | 173704.68 | 2952771.49 | 1787429.43 | 4564.88 | 497.10 | 3698.02 | 95.06 |
PERIMETER_TOP_ZN_1 | 4669659.71 | 0.00 | 4669659.71 | 260558.58 | 4930218.29 | 2823374.22 | 4282.23 | 706.89 | 3770.88 | 95.06 |
PERIMETER_TOP_ZN_4 | 2455583.72 | 0.00 | 2455583.72 | 173704.68 | 2629288.39 | 1787312.18 | 4632.25 | 889.10 | 3238.66 | 95.06 |
PERIMETER_BOT_ZN_3 | 2112522.38 | 0.00 | 2112522.38 | 138537.43 | 2251059.81 | 2823374.22 | 5921.65 | 474.41 | 2363.94 | 46.58 |
PERIMETER_BOT_ZN_2 | 2368546.93 | 0.00 | 2368546.93 | 92357.73 | 2460904.66 | 1787429.43 | 5170.02 | 512.59 | 3077.39 | 46.58 |
PERIMETER_BOT_ZN_1 | 3680227.17 | 0.00 | 3680227.17 | 2868995.21 | 6549222.37 | 2823374.22 | 4751.09 | 337.25 | 3671.66 | 46.58 |
PERIMETER_BOT_ZN_4 | 2016902.27 | 0.00 | 2016902.27 | 92357.73 | 2109260.00 | 1787312.18 | 5287.34 | 316.53 | 3156.13 | 46.58 |
PERIMETER_MID_ZN_3 | 2517208.70 | 0.00 | 2517208.70 | 216894.87 | 2734103.57 | 2823374.22 | 4920.90 | 758.46 | 3080.64 | 59.82 |
PERIMETER_MID_ZN_2 | 2611476.69 | 0.00 | 2611476.69 | 144595.71 | 2756072.40 | 1601953.02 | 4444.31 | 763.68 | 3552.01 | 968.82 |
PERIMETER_MID_ZN_1 | 4678805.06 | 0.00 | 4678805.06 | 216894.87 | 4895699.93 | 2823374.22 | 4271.61 | 647.53 | 3840.87 | 59.82 |
PERIMETER_MID_ZN_4 | 2398671.44 | 0.00 | 2398671.44 | 144595.71 | 2543267.15 | 1787312.18 | 4664.32 | 518.58 | 3577.10 | 59.82 |
Total Facility | 69353790.53 | 0.00 | 69353790.53 | 4783755.77 | 74137546.31 | 67658168.57 | 6586.92 | 1343.92 | 4660.02 | 1036.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6196 | 0.0000 | 0.6196 | 0.0000 | 0.6196 | 0.4247 | 2434.61 | 412.50 | 3095.89 |
CORE_MID | 0.4932 | 0.0000 | 0.4932 | 0.0000 | 0.4932 | 0.4247 | 2787.58 | 776.46 | 2378.96 |
CORE_TOP | 0.4840 | 0.0000 | 0.4840 | 0.0000 | 0.4840 | 0.4247 | 2875.10 | 662.91 | 2404.99 |
PERIMETER_TOP_ZN_3 | 0.1189 | 0.0000 | 0.1189 | 0.0059 | 0.1248 | 0.0895 | 2035.28 | 613.98 | 3293.74 |
PERIMETER_TOP_ZN_2 | 0.1290 | 0.0000 | 0.1290 | 0.0039 | 0.1329 | 0.0567 | 1807.01 | 497.10 | 3638.88 |
PERIMETER_TOP_ZN_1 | 0.2168 | 0.0000 | 0.2168 | 0.0059 | 0.2227 | 0.0895 | 1524.36 | 706.89 | 3711.75 |
PERIMETER_TOP_ZN_4 | 0.1131 | 0.0000 | 0.1131 | 0.0039 | 0.1170 | 0.0567 | 1874.41 | 889.10 | 3179.49 |
PERIMETER_BOT_ZN_3 | 0.0979 | 0.0000 | 0.0979 | 0.0031 | 0.1010 | 0.0895 | 3143.18 | 474.24 | 2325.58 |
PERIMETER_BOT_ZN_2 | 0.1101 | 0.0000 | 0.1101 | 0.0021 | 0.1122 | 0.0567 | 2391.61 | 512.43 | 3038.96 |
PERIMETER_BOT_ZN_1 | 0.1711 | 0.0000 | 0.1711 | 0.1308 | 0.3018 | 0.0895 | 1972.62 | 337.25 | 3633.13 |
PERIMETER_BOT_ZN_4 | 0.0935 | 0.0000 | 0.0935 | 0.0021 | 0.0955 | 0.0567 | 2508.94 | 316.53 | 3117.53 |
PERIMETER_MID_ZN_3 | 0.1166 | 0.0000 | 0.1166 | 0.0049 | 0.1215 | 0.0895 | 2147.23 | 758.29 | 3037.47 |
PERIMETER_MID_ZN_2 | 0.1212 | 0.0000 | 0.1212 | 0.0035 | 0.1247 | 0.0567 | 1670.80 | 763.52 | 2599.69 |
PERIMETER_MID_ZN_1 | 0.2177 | 0.0000 | 0.2177 | 0.0049 | 0.2226 | 0.0895 | 1498.11 | 647.36 | 3797.53 |
PERIMETER_MID_ZN_4 | 0.1111 | 0.0000 | 0.1111 | 0.0033 | 0.1143 | 0.0567 | 1890.93 | 518.40 | 3533.67 |
Total Facility | 3.2137 | 0.0000 | 3.2137 | 0.1742 | 3.3879 | 2.1513 | 3792.34 | 1343.57 | 4583.68 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 22473678.67 | 0.00 | 22473678.67 | 22614548.33 | 4858.41 | 287.63 | 3613.96 | 46.58 |
PACU_VAV_MID | 21839326.71 | 0.00 | 21839326.71 | 22429071.92 | 5219.92 | 65.79 | 3474.29 | 59.82 |
PACU_VAV_TOP | 21946477.85 | 0.00 | 21946477.85 | 22614548.33 | 5223.01 | 85.04 | 3451.95 | 94.98 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.0434 | 0.0000 | 1.0434 | 0.7171 | 2079.94 | 287.63 | 3575.43 |
PACU_VAV_MID | 1.0127 | 0.0000 | 1.0127 | 0.7084 | 2446.25 | 65.63 | 3431.12 |
PACU_VAV_TOP | 1.0144 | 0.0000 | 1.0144 | 0.7171 | 2465.18 | 84.62 | 3393.20 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 531.33 | 2237.91 | 0.00 | 0.00 | 0.00 | 2085.44 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 434.55 | 2261.54 | 0.00 | 0.00 | 0.00 | 2213.65 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 396.93 | 2275.63 | 0.00 | 0.00 | 0.00 | 2274.07 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.8988 | 1.8979 | 0.0000 | 0.0000 | 0.0000 | 0.7502 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.8952 | 1.8223 | 0.0000 | 0.0000 | 0.0000 | 0.7308 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.8922 | 1.8371 | 0.0000 | 0.0000 | 0.0000 | 0.7342 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1010 |
Defaulted Fields | 582 |
Fields with Defaults | 2434 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1194.40 | 11981.96 | 14-MAY-17:20 | 158908.33 | 26-JUN-15:10 |
Electricity:Building | 825.56 | 11650.06 | 14-MAY-17:10 | 56534.15 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 229.44 | 3625.33 | 01-JAN-00:10 | 14695.26 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 825.56 | 11650.06 | 14-MAY-17:10 | 56534.15 | 02-JAN-16:50 |
InteriorLights:Electricity | 166.65 | 772.31 | 01-JAN-09:00 | 17672.30 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 166.65 | 772.31 | 01-JAN-09:00 | 17672.30 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 166.65 | 772.31 | 01-JAN-09:00 | 17672.30 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 166.65 | 772.31 | 01-JAN-09:00 | 17672.30 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.19 | 405.59 | 09-APR-17:10 | 2170.70 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.86 | 19.49 | 01-JAN-09:00 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.86 | 19.49 | 01-JAN-09:00 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.48 | 256.76 | 14-MAY-17:10 | 1374.17 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.07 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.07 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.13 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.79 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.79 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.44 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.04 | 12.34 | 01-JAN-09:00 | 465.57 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.04 | 12.34 | 01-JAN-09:00 | 465.57 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.18 | 405.59 | 09-APR-17:10 | 2170.70 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.85 | 19.49 | 01-JAN-09:00 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.85 | 19.49 | 01-JAN-09:00 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.47 | 256.76 | 14-MAY-17:10 | 1374.17 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.07 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.07 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.12 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.79 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.79 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.43 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.03 | 12.34 | 01-JAN-09:00 | 465.57 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.03 | 12.34 | 01-JAN-09:00 | 465.57 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.19 | 405.59 | 09-APR-17:10 | 2170.70 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.86 | 19.49 | 01-JAN-09:00 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.86 | 19.49 | 01-JAN-09:00 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.48 | 256.76 | 14-MAY-17:10 | 1374.17 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.07 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.07 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.13 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.79 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.79 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.44 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.04 | 12.34 | 01-JAN-09:00 | 465.57 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.04 | 12.34 | 01-JAN-09:00 | 465.57 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 658.91 | 10877.75 | 01-JAN-00:10 | 38886.07 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 189.64 | 3431.54 | 01-JAN-00:10 | 11206.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 658.91 | 10877.75 | 01-JAN-00:10 | 38886.07 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 73.68 | 1600.00 | 01-JAN-00:10 | 4325.57 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 73.68 | 1600.00 | 01-JAN-00:10 | 4325.57 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 73.68 | 1600.00 | 01-JAN-00:10 | 4325.57 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElectricityProduced:Facility | 155.68 | -0.00 | 27-APR-18:30 | 26811.28 | 26-APR-12:30 |
ElectricityProduced:Plant | 155.68 | -0.00 | 27-APR-18:30 | 26811.28 | 26-APR-12:30 |
Photovoltaic:ElectricityProduced | 162.61 | 0.00 | 01-JAN-00:10 | 27928.39 | 26-APR-12:30 |
PowerConversion:ElectricityProduced | -6.94 | -1117.11 | 26-APR-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 57.52 | 0.00 | 01-JAN-00:10 | 7370.81 | 06-FEB-12:20 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 277.29 | 331.43 | 01-JAN-00:10 | 101886.96 | 26-JUN-15:10 |
ExteriorEquipment:Electricity | 25.33 | 331.43 | 01-JAN-00:10 | 1410.29 | 02-JAN-13:10 |
Transformer:ExteriorEquipment:Electricity | 25.33 | 331.43 | 01-JAN-00:10 | 1410.29 | 02-JAN-13:10 |
ElectricityPurchased:Facility | 1039.32 | 0.00 | 12-FEB-10:20 | 141977.57 | 26-JUN-15:10 |
ElectricityPurchased:Plant | 1039.32 | 0.00 | 12-FEB-10:20 | 141977.57 | 26-JUN-15:10 |
Cogeneration:ElectricityPurchased | 1039.32 | 0.00 | 12-FEB-10:20 | 141977.57 | 26-JUN-15:10 |
General:Cogeneration:ElectricityPurchased | 1039.32 | 0.00 | 12-FEB-10:20 | 141977.57 | 26-JUN-15:10 |
ElectricitySurplusSold:Facility | 0.59 | 0.00 | 01-JAN-00:10 | 9206.10 | 09-APR-11:20 |
ElectricitySurplusSold:Plant | 0.59 | 0.00 | 01-JAN-00:10 | 9206.10 | 09-APR-11:20 |
Cogeneration:ElectricitySurplusSold | 0.59 | 0.00 | 01-JAN-00:10 | 9206.10 | 09-APR-11:20 |
General:Cogeneration:ElectricitySurplusSold | 0.59 | 0.00 | 01-JAN-00:10 | 9206.10 | 09-APR-11:20 |
ElectricityNet:Facility | 1038.73 | -9206.10 | 09-APR-11:20 | 141977.57 | 26-JUN-15:10 |
ElectricityNet:Plant | 1038.73 | -9206.10 | 09-APR-11:20 | 141977.57 | 26-JUN-15:10 |
Cogeneration:ElectricityNet | 1038.73 | -9206.10 | 09-APR-11:20 | 141977.57 | 26-JUN-15:10 |
General:Cogeneration:ElectricityNet | 1038.73 | -9206.10 | 09-APR-11:20 | 141977.57 | 26-JUN-15:10 |
Fans:Electricity | 107.59 | 0.00 | 01-JAN-00:10 | 33125.84 | 24-JUL-15:20 |
General:Fans:Electricity | 107.59 | 0.00 | 01-JAN-00:10 | 33125.84 | 24-JUL-15:20 |
ExteriorLights:Electricity | 34.03 | 0.00 | 01-JAN-07:30 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 34.03 | 0.00 | 01-JAN-07:30 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 144.36 | 0.00 | 01-JAN-00:10 | 69541.96 | 26-JUN-15:00 |
General:Cooling:Electricity | 144.36 | 0.00 | 01-JAN-00:10 | 69541.96 | 26-JUN-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 55.72 | 0.00 | 01-JAN-00:10 | 6802.95 | 13-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 55.72 | 0.00 | 01-JAN-00:10 | 6802.95 | 13-FEB-12:50 |
Pumps:Electricity | 1.80 | 0.00 | 01-JAN-00:10 | 732.49 | 23-DEC-07:10 |
General:Pumps:Electricity | 1.80 | 0.00 | 01-JAN-00:10 | 732.49 | 23-DEC-07:10 |
WIRED_LTG_ELECTRICITY | 4.68 | 0.00 | 01-JAN-00:10 | 496.59 | 02-JAN-17:00 |
WIRED_INT_EQUIP1 | 632.98 | 10877.75 | 01-JAN-00:10 | 36042.38 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 611.16 | 9277.75 | 01-JAN-00:10 | 37604.10 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 303.21 | 0.00 | 01-JAN-00:10 | 222058.41 | 23-DEC-07:20 |
NaturalGas:Plant | 303.21 | 0.00 | 01-JAN-00:10 | 222058.41 | 23-DEC-07:20 |
Heating:NaturalGas | 303.21 | 0.00 | 01-JAN-00:10 | 222058.41 | 23-DEC-07:20 |
Boiler:Heating:NaturalGas | 303.21 | 0.00 | 01-JAN-00:10 | 222058.41 | 23-DEC-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2161.06 | 0.00 | 01-JAN-00:10 | 471255.18 | 23-DEC-07:10 |
EnergyTransfer:Building | 1029.10 | 0.00 | 01-JAN-00:10 | 160561.98 | 26-JUN-15:00 |
EnergyTransfer:Zone:CORE_BOTTOM | 178.05 | 0.00 | 01-JAN-00:10 | 22661.93 | 05-SEP-07:30 |
Heating:EnergyTransfer | 83.13 | 0.00 | 01-JAN-00:10 | 113565.49 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 1853.46 | 26-DEC-07:10 |
General:Heating:EnergyTransfer | 83.13 | 0.00 | 01-JAN-00:10 | 113565.49 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 1853.46 | 26-DEC-07:10 |
Cooling:EnergyTransfer | 945.98 | 0.00 | 01-JAN-00:10 | 160561.98 | 26-JUN-15:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 178.04 | 0.00 | 01-JAN-00:10 | 22661.93 | 05-SEP-07:30 |
General:Cooling:EnergyTransfer | 945.98 | 0.00 | 01-JAN-00:10 | 160561.98 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 178.04 | 0.00 | 01-JAN-00:10 | 22661.93 | 05-SEP-07:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 46.31 | 0.00 | 01-JAN-00:10 | 12750.37 | 22-DEC-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 14.79 | 0.00 | 01-JAN-00:10 | 12750.37 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 14.79 | 0.00 | 01-JAN-00:10 | 12750.37 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.52 | 0.00 | 01-JAN-00:10 | 11359.40 | 26-JUN-13:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.52 | 0.00 | 01-JAN-00:10 | 11359.40 | 26-JUN-13:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 23.02 | 0.00 | 01-JAN-00:10 | 6417.84 | 26-DEC-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.60 | 0.00 | 01-JAN-00:10 | 6417.84 | 26-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.60 | 0.00 | 01-JAN-00:10 | 6417.84 | 26-DEC-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.42 | 0.00 | 01-JAN-00:10 | 5287.12 | 17-JUL-10:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.42 | 0.00 | 01-JAN-00:10 | 5287.12 | 17-JUL-10:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 22.74 | 0.00 | 01-JAN-00:10 | 5104.33 | 17-JUL-12:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.71 | 0.00 | 01-JAN-00:10 | 2663.37 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.71 | 0.00 | 01-JAN-00:10 | 2663.37 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 19.03 | 0.00 | 01-JAN-00:10 | 5104.33 | 17-JUL-12:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 19.03 | 0.00 | 01-JAN-00:10 | 5104.33 | 17-JUL-12:20 |
EnergyTransfer:Zone:CORE_MID | 134.74 | 0.00 | 01-JAN-00:10 | 18790.66 | 17-JUL-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.29 | 0.00 | 01-JAN-00:10 | 10329.60 | 26-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.29 | 0.00 | 01-JAN-00:10 | 10329.60 | 26-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 134.45 | 0.00 | 01-JAN-00:10 | 18790.66 | 17-JUL-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 134.45 | 0.00 | 01-JAN-00:10 | 18790.66 | 17-JUL-07:20 |
EnergyTransfer:Zone:CORE_TOP | 128.91 | 0.00 | 01-JAN-00:10 | 19824.19 | 17-JUL-11:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.82 | 0.00 | 01-JAN-00:10 | 19455.39 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.82 | 0.00 | 01-JAN-00:10 | 19455.39 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 125.09 | 0.00 | 01-JAN-00:10 | 19824.19 | 17-JUL-11:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 125.09 | 0.00 | 01-JAN-00:10 | 19824.19 | 17-JUL-11:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 38.50 | 0.00 | 01-JAN-00:10 | 7623.04 | 17-JUL-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.97 | 0.00 | 01-JAN-00:10 | 7585.36 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.97 | 0.00 | 01-JAN-00:10 | 7585.36 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.53 | 0.00 | 01-JAN-00:10 | 7623.04 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.53 | 0.00 | 01-JAN-00:10 | 7623.04 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 38.14 | 0.00 | 01-JAN-00:10 | 9782.04 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.73 | 0.00 | 01-JAN-00:10 | 5990.06 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.73 | 0.00 | 01-JAN-00:10 | 5990.06 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.41 | 0.00 | 01-JAN-00:10 | 9782.04 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.41 | 0.00 | 01-JAN-00:10 | 9782.04 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 66.02 | 0.00 | 01-JAN-00:10 | 13315.74 | 28-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.70 | 0.00 | 01-JAN-00:10 | 8324.15 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.70 | 0.00 | 01-JAN-00:10 | 8324.15 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.32 | 0.00 | 01-JAN-00:10 | 13315.74 | 28-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.32 | 0.00 | 01-JAN-00:10 | 13315.74 | 28-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 36.36 | 0.00 | 01-JAN-00:10 | 10448.16 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.15 | 0.00 | 01-JAN-00:10 | 6220.08 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.15 | 0.00 | 01-JAN-00:10 | 6220.08 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.21 | 0.00 | 01-JAN-00:10 | 10448.16 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.21 | 0.00 | 01-JAN-00:10 | 10448.16 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.12 | 0.00 | 01-JAN-00:10 | 6144.38 | 17-JUL-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.50 | 0.00 | 01-JAN-00:10 | 5397.72 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.50 | 0.00 | 01-JAN-00:10 | 5397.72 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 24.62 | 0.00 | 01-JAN-00:10 | 6144.38 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 24.62 | 0.00 | 01-JAN-00:10 | 6144.38 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 32.30 | 0.00 | 01-JAN-00:10 | 7896.14 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.89 | 0.00 | 01-JAN-00:10 | 4319.66 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.89 | 0.00 | 01-JAN-00:10 | 4319.66 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 30.41 | 0.00 | 01-JAN-00:10 | 7896.14 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 30.41 | 0.00 | 01-JAN-00:10 | 7896.14 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 57.49 | 0.00 | 01-JAN-00:10 | 11050.58 | 16-AUG-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 10.57 | 0.00 | 01-JAN-00:10 | 9217.30 | 21-DEC-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 10.57 | 0.00 | 01-JAN-00:10 | 9217.30 | 21-DEC-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 46.92 | 0.00 | 01-JAN-00:10 | 11050.58 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 46.92 | 0.00 | 01-JAN-00:10 | 11050.58 | 16-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 29.00 | 0.00 | 01-JAN-00:10 | 8142.48 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.95 | 0.00 | 01-JAN-00:10 | 4412.40 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.95 | 0.00 | 01-JAN-00:10 | 4412.40 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 27.05 | 0.00 | 01-JAN-00:10 | 8142.48 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 27.05 | 0.00 | 01-JAN-00:10 | 8142.48 | 26-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 34.26 | 0.00 | 01-JAN-00:10 | 7098.68 | 17-JUL-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.54 | 0.00 | 01-JAN-00:10 | 5807.07 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.54 | 0.00 | 01-JAN-00:10 | 5807.07 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 30.72 | 0.00 | 01-JAN-00:10 | 7098.68 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 30.72 | 0.00 | 01-JAN-00:10 | 7098.68 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 34.88 | 0.00 | 01-JAN-00:10 | 9682.66 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.88 | 0.00 | 01-JAN-00:10 | 4794.07 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.88 | 0.00 | 01-JAN-00:10 | 4794.07 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.00 | 0.00 | 01-JAN-00:10 | 9682.66 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.00 | 0.00 | 01-JAN-00:10 | 9682.66 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 65.28 | 0.00 | 01-JAN-00:10 | 12360.29 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.07 | 0.00 | 01-JAN-00:10 | 6592.94 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.07 | 0.00 | 01-JAN-00:10 | 6592.94 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 63.21 | 0.00 | 01-JAN-00:10 | 12360.29 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 63.21 | 0.00 | 01-JAN-00:10 | 12360.29 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 33.98 | 0.00 | 01-JAN-00:10 | 9924.91 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.96 | 0.00 | 01-JAN-00:10 | 4859.81 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.96 | 0.00 | 01-JAN-00:10 | 4859.81 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.02 | 0.00 | 01-JAN-00:10 | 9924.91 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.02 | 0.00 | 01-JAN-00:10 | 9924.91 | 16-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 276.20 | 0.00 | 01-JAN-00:10 | 187202.48 | 23-DEC-07:20 |
PlantLoopHeatingDemand:Plant | 52.92 | 0.00 | 01-JAN-00:10 | 6664.15 | 13-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 52.92 | 0.00 | 01-JAN-00:10 | 6664.15 | 13-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 52.92 | 0.00 | 01-JAN-00:10 | 6664.15 | 13-FEB-12:10 |
EnergyTransfer:HVAC | 857.54 | 0.00 | 01-JAN-00:10 | 223522.13 | 26-JUN-15:10 |
HeatingCoils:EnergyTransfer | 223.28 | 0.00 | 01-JAN-00:10 | 185967.00 | 23-DEC-07:20 |
PlantLoopHeatingDemand:HVAC | 223.28 | 0.00 | 01-JAN-00:10 | 185967.00 | 23-DEC-07:20 |
HeatingCoils:PlantLoopHeatingDemand | 223.28 | 0.00 | 01-JAN-00:10 | 185967.00 | 23-DEC-07:20 |
CoolingCoils:EnergyTransfer | 634.26 | 0.00 | 01-JAN-00:10 | 223522.13 | 26-JUN-15:10 |
EnergyTransfer:Plant | 274.41 | 0.00 | 01-JAN-00:10 | 185961.93 | 23-DEC-07:20 |
WaterSystems:EnergyTransfer | 52.92 | 0.00 | 01-JAN-00:10 | 6664.15 | 13-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 52.92 | 0.00 | 01-JAN-00:10 | 6664.15 | 13-FEB-12:10 |
Boilers:EnergyTransfer | 221.50 | 0.00 | 01-JAN-00:10 | 184726.45 | 23-DEC-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.001 | -178.043 | 0.000 | 0.000 | 32.942 | 39.795 | 189.644 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -84.340 |
CORE_MID | 0.000 | 0.000 | 0.292 | -134.446 | 0.000 | 0.000 | 33.726 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -54.793 |
CORE_TOP | 0.000 | 0.000 | 3.819 | -125.089 | 0.000 | 0.000 | 34.408 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -68.359 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 8.970 | -29.531 | 0.000 | 0.000 | 7.452 | 4.860 | 24.333 | 20.493 | 0.000 | 0.070 | 3.176 | 0.000 | -36.439 | 0.000 | -3.383 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.730 | -33.407 | 0.000 | 0.000 | 4.586 | 3.072 | 15.404 | 46.205 | 0.000 | 0.045 | 0.001 | 0.000 | -23.544 | 0.000 | -2.314 | -14.777 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.698 | -60.322 | 0.000 | 0.000 | 7.167 | 4.795 | 24.332 | 95.815 | 0.000 | 0.068 | 0.001 | 0.000 | -35.554 | 0.000 | -3.555 | -38.444 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 5.148 | -31.213 | 0.000 | 0.000 | 4.650 | 3.036 | 15.403 | 42.427 | 0.000 | 0.045 | 0.000 | 0.000 | -24.168 | 0.000 | -2.320 | -13.007 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 4.505 | -24.616 | 0.000 | 0.000 | 7.461 | 4.851 | 24.333 | 20.960 | 0.000 | 0.041 | 1.508 | 0.000 | -37.194 | 0.000 | -1.849 | -0.001 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.890 | -30.411 | 0.000 | 0.000 | 4.564 | 3.067 | 15.404 | 46.446 | 0.000 | 0.025 | 0.001 | 0.000 | -24.591 | 0.000 | -1.295 | -15.098 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 10.567 | -46.923 | 0.000 | 0.000 | 7.294 | 4.789 | 24.332 | 96.588 | 0.000 | 2.288 | 0.002 | 0.000 | -37.424 | 0.000 | -31.330 | -30.180 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.952 | -27.050 | 0.000 | 0.000 | 4.614 | 3.031 | 15.403 | 42.726 | 0.000 | 0.025 | 0.000 | 0.000 | -25.277 | 0.000 | -1.298 | -14.127 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 3.540 | -30.718 | 0.000 | 0.000 | 7.365 | 4.860 | 24.333 | 20.313 | 0.000 | 0.060 | 11.453 | 0.000 | -38.250 | 0.000 | -2.955 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.884 | -33.000 | 0.000 | 0.000 | 3.353 | 3.072 | 15.404 | 45.968 | 0.000 | 0.038 | 0.001 | 0.000 | -24.655 | 0.000 | -2.020 | -10.043 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 2.067 | -63.211 | 0.000 | 0.000 | 7.095 | 4.795 | 24.332 | 95.598 | 0.000 | 0.058 | 0.004 | 0.000 | -37.224 | 0.000 | -3.099 | -30.411 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.965 | -32.017 | 0.000 | 0.000 | 4.597 | 3.036 | 15.403 | 42.315 | 0.000 | 0.038 | 0.000 | 0.000 | -25.357 | 0.000 | -2.024 | -7.956 |
TOPFLOOR_PLENUM | 14.793 | -31.518 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.073 | 21.872 | 0.000 | 0.000 | 0.000 | -5.220 | -0.001 |
MIDFLOOR_PLENUM | 7.598 | -15.418 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.089 | 12.870 | 0.000 | 0.000 | 0.000 | -5.139 | -0.000 |
FIRSTFLOOR_PLENUM | 3.708 | -19.034 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.069 | 19.356 | 0.000 | 0.000 | 0.000 | -4.099 | -0.000 |
Total Facility | 26.099 | -65.971 | 57.029 | -879.997 | 0.000 | 0.000 | 171.273 | 166.649 | 658.911 | 615.855 | 0.000 | 3.031 | 70.247 | 0.000 | -369.678 | 0.000 | -71.901 | -381.538 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-SEP-06:03 | 0.00 | 0.00 | 0.00 | -34031.78 | 0.00 | 0.00 | 685.37 | 1162.90 | 7388.35 | 0.00 | 0.00 | 0.00 | 24795.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-06:03 | 0.00 | 0.00 | 0.00 | -30098.54 | 0.00 | 0.00 | 685.37 | 1162.90 | 3025.92 | 0.00 | 0.00 | 0.00 | 25224.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-SEP-05:12 | 0.00 | 0.00 | 0.00 | -31047.14 | 0.00 | 0.00 | 330.92 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 27302.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-14:22 | 0.00 | 0.00 | 0.00 | -10944.44 | 0.00 | 0.00 | 25.17 | 19.49 | 478.42 | 5898.81 | 0.00 | 180.62 | 4341.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-09:02 | 0.00 | 0.00 | 0.00 | -13588.40 | 0.00 | 0.00 | 12.92 | 12.34 | 302.86 | 11036.33 | 0.00 | 0.00 | 2235.25 | 0.00 | -0.00 | 0.00 | -11.31 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-13:41 | 0.00 | 0.00 | 0.00 | -17373.80 | 0.00 | 0.00 | 21.09 | 19.49 | 478.41 | 14960.04 | 0.00 | 0.00 | 2052.10 | 0.00 | -0.00 | 0.00 | -157.32 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:21 | 0.00 | 0.00 | 0.00 | -15877.53 | 0.00 | 0.00 | 10.63 | 12.34 | 302.86 | 12045.67 | 0.00 | 1.44 | 3504.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | -6916.42 | 0.00 | 0.00 | 144.48 | 116.94 | 637.89 | 2812.09 | 0.00 | 0.00 | 3208.36 | 0.00 | -0.00 | 0.00 | -3.32 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-09:01 | 0.00 | 0.00 | 0.00 | -11047.63 | 0.00 | 0.00 | 15.65 | 12.34 | 302.86 | 10030.13 | 0.00 | 0.00 | 698.50 | 0.00 | -0.00 | 0.00 | -11.84 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-13:41 | 0.00 | 0.00 | 0.00 | -13109.97 | 0.00 | 0.00 | 23.11 | 19.49 | 478.41 | 10547.18 | 0.00 | 7.33 | 2034.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 17-SEP-16:01 | 0.00 | 0.00 | 0.00 | -12361.66 | 0.00 | 0.00 | 14.77 | 12.34 | 302.86 | 11636.80 | 0.00 | 0.00 | 397.81 | 0.00 | -0.00 | 0.00 | -2.91 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-19:02 | 0.00 | 0.00 | 0.00 | -9384.67 | 0.00 | 0.00 | 0.00 | 26.68 | 386.10 | 1646.66 | 0.00 | 28.96 | 7296.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 16-JUL-08:51 | 0.00 | 0.00 | 0.00 | -14449.83 | 0.00 | 0.00 | 13.15 | 12.34 | 302.86 | 9769.02 | 0.00 | 32.21 | 4320.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 05-NOV-12:11 | 0.00 | 0.00 | 0.00 | -15925.09 | 0.00 | 0.00 | 20.77 | 19.49 | 478.41 | 21858.98 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -20.78 | -6431.79 |
PERIMETER_MID_ZN_4 | 25-JUN-16:21 | 0.00 | 0.00 | 0.00 | -15838.52 | 0.00 | 0.00 | 11.06 | 12.34 | 302.86 | 12253.24 | 0.00 | 23.90 | 3235.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:20 | 0.00 | -11358.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.14 | 11328.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-10:10 | 0.00 | -5468.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.70 | 5427.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 26-JUN-12:08 | 0.00 | -5564.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 5541.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUL-06:03 | 0.00 | -7810.95 | 0.00 | -171291.30 | 0.00 | 0.00 | 3473.96 | 4634.49 | 19690.35 | 35378.59 | 0.00 | 0.00 | 117053.11 | 0.00 | 0.00 | 0.00 | -1128.25 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 26-DEC-07:03 | 0.00 | 0.00 | 4893.59 | 0.00 | 0.00 | 0.00 | 899.89 | 1162.90 | 7388.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14344.73 |
CORE_MID | 26-DEC-06:11 | 0.00 | 0.00 | 12609.00 | 0.00 | 0.00 | 0.00 | 490.39 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16512.94 |
CORE_TOP | 06-FEB-05:01 | 0.00 | 0.00 | 21658.73 | 0.00 | 0.00 | 0.00 | 0.00 | 387.63 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24488.42 |
PERIMETER_TOP_ZN_3 | 24-DEC-06:42 | 0.00 | 0.00 | 8914.96 | 0.00 | 0.00 | 0.00 | 59.65 | 40.85 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3918.52 | 0.00 | -766.10 | -4809.27 |
PERIMETER_TOP_ZN_2 | 24-DEC-06:42 | 0.00 | 0.00 | 7928.51 | 0.00 | 0.00 | 0.00 | 37.86 | 25.86 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2688.10 | 0.00 | -514.27 | -5092.71 |
PERIMETER_TOP_ZN_1 | 24-DEC-06:42 | 0.00 | 0.00 | 10460.00 | 0.00 | 0.00 | 0.00 | 59.38 | 40.85 | 478.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4066.08 | 0.00 | -774.22 | -6198.35 |
PERIMETER_TOP_ZN_4 | 24-DEC-06:42 | 0.00 | 0.00 | 8431.85 | 0.00 | 0.00 | 0.00 | 37.81 | 25.86 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2613.14 | 0.00 | -516.35 | -5668.89 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 6212.51 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2996.81 | 0.00 | -176.55 | -3635.68 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 5608.89 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1991.09 | 0.00 | -117.92 | -3877.51 |
PERIMETER_BOT_ZN_1 | 22-DEC-07:10 | 0.00 | 0.00 | 9494.01 | 0.00 | 0.00 | 0.00 | 206.33 | 245.15 | 637.88 | 0.00 | 0.00 | 0.00 | 16008.43 | 0.00 | -4287.30 | 0.00 | -22304.51 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 5835.71 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2034.62 | 0.00 | -118.06 | -4060.66 |
PERIMETER_MID_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 6863.90 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2955.16 | 0.00 | -271.72 | -4233.54 |
PERIMETER_MID_ZN_2 | 23-DEC-05:01 | 0.00 | 0.00 | 6420.62 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2962.40 | 0.00 | -380.93 | -3347.57 |
PERIMETER_MID_ZN_1 | 06-FEB-05:01 | 0.00 | 0.00 | 8204.08 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3027.21 | 0.00 | -272.61 | -5500.77 |
PERIMETER_MID_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 6596.74 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2006.17 | 0.00 | -181.59 | -4786.60 |
TOPFLOOR_PLENUM | 23-DEC-06:08 | 13908.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -293.21 | -13615.38 |
MIDFLOOR_PLENUM | 05-NOV-14:52 | 7198.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -25.00 | -7173.66 |
FIRSTFLOOR_PLENUM | 23-OCT-05:01 | 3979.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -145.15 | -3834.09 |
Total Facility | 06-FEB-06:01 | 8061.90 | 3540.60 | 110387.01 | -3540.60 | 0.00 | 0.00 | 2501.45 | 1072.56 | 17750.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31236.08 | 0.00 | -4069.67 | -104467.55 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.8020 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0791 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.0106 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0148 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.4716 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.8612 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.9010 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0750 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.0053 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0742 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.2358 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0757 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7429 | 2.7429 | 0.6364 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3998 | 2.3998 | 0.6359 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5593 | 2.5593 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8047 | 0.8047 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9370 | 0.9370 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1000 | 1.1000 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0706 | 1.0706 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6126 | 0.6126 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7563 | 0.7563 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8621 | 0.8621 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8279 | 0.8279 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6949 | 0.6949 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9304 | 0.9304 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9949 | 0.9949 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9906 | 0.9906 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.8020 | 5.0791 | 5.8020 | 1.0750 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.0106 | 5.0148 | 6.0106 | 1.0742 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.4716 | 5.8612 | 6.4716 | 1.0757 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3715 | 1.3715 | 0.6364 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1999 | 1.1999 | 0.6359 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2796 | 1.2796 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4024 | 0.4024 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4685 | 0.4685 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5500 | 0.5500 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5353 | 0.5353 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3063 | 0.3063 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3782 | 0.3782 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4311 | 0.4311 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4140 | 0.4140 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3475 | 0.3475 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4652 | 0.4652 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4975 | 0.4975 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4953 | 0.4953 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.9010 | 1.0750 | 1.0750 | 1.0750 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.0053 | 1.0742 | 1.0742 | 1.0742 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.2358 | 1.0757 | 1.0757 | 1.0757 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 282.83 |
Number of hours cooling loads not met | 208.83 |
Number of hours not met | 491.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 303.21 | 222058.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 144.36 | 69541.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 166.65 | 17672.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 34.03 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 73.68 | 4325.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 25.33 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 107.59 | 33125.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1.80 | 732.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 55.72 | 6802.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 658.91 | 1194.40 |
Natural Gas | 0.00 | 303.21 |
Additional | 0.00 | 0.00 |
Total | 658.91 | 1497.61 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 162.61 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 33.45 |
Space Heating | 0.00 |
Space Cooling | 28.98 |
Fans (All) | 21.60 |
Service Water Heating | 11.18 |
Receptacle Equipment | 132.25 |
Miscellaneous (All) | 239.73 |
Subtotal | 239.73 |
Natural Gas [MJ/m2] | |
Space Heating | 60.86 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 60.86 |
Subtotal | 60.86 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.13 |
Space Heating | 20.25 |
Space Cooling | 9.64 |
Fans (All) | 7.18 |
Service Water Heating | 3.72 |
Receptacle Equipment | 44.00 |
Miscellaneous | 4.08 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 1996. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 721. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8730.00 | 30.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8731.00 | 29.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8745.83 | 14.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8733.00 | 27.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8737.00 | 23.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8661.00 | 99.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8661.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 99.00 | 0.00 | 0.00 | 0.00 |
Average | 8743.31 | 16.69 | 0.00 | 0.00 | 0.00 |
Sum | 157379.50 | 300.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8723.17 | 36.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8732.50 | 27.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8735.17 | 24.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8741.83 | 18.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8741.00 | 19.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8734.17 | 25.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8738.17 | 21.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8738.50 | 21.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8723.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 36.83 | 0.00 | 0.00 | 0.00 |
Average | 8745.49 | 14.51 | 0.00 | 0.00 | 0.00 |
Sum | 157418.83 | 261.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128289.33 | 14.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128298.67 | 5.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128303.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128303.00 | 14.67 | 0.00 | 0.00 | 0.00 |
Average | 34142.17 | 1.17 | 0.00 | 0.00 | 0.00 |
Sum | 614559.00 | 21.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:56
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.952702E+10 | 14256.25 | 26-JAN-16:40 | 6.67 | 2.08 | 0.194358E+10 | 2606.64 | 27-JAN-10:20 | 2.33 | 2.17 |
February | 0.844814E+10 | 14135.07 | 27-FEB-16:20 | 13.00 | 4.42 | 0.174592E+10 | 2606.63 | 23-FEB-10:20 | 13.00 | 4.42 |
March | 0.120624E+11 | 29792.09 | 15-MAR-06:02 | 10.00 | 2.57 | 0.213046E+10 | 2606.64 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.108548E+11 | 18480.65 | 13-APR-06:03 | 3.83 | 1.13 | 0.190330E+10 | 2606.65 | 13-APR-13:50 | 15.50 | 9.79 |
May | 0.166540E+11 | 30715.91 | 22-MAY-06:02 | 11.17 | 10.50 | 0.207605E+10 | 2606.68 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.212464E+11 | 32512.76 | 19-JUN-05:12 | 18.27 | 12.22 | 0.207064E+10 | 2606.68 | 08-JUN-13:09 | 18.27 | 12.22 |
July | 0.209294E+11 | 33235.77 | 24-JUL-05:12 | 18.00 | 14.77 | 0.192474E+10 | 2606.66 | 11-JUL-09:30 | 18.00 | 14.77 |
August | 0.222675E+11 | 33477.59 | 28-AUG-05:12 | 15.00 | 14.37 | 0.216076E+10 | 2606.67 | 10-AUG-09:39 | 15.00 | 14.37 |
September | 0.199136E+11 | 34035.97 | 05-SEP-06:03 | 13.90 | 7.58 | 0.191853E+10 | 2606.87 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.154109E+11 | 32563.93 | 12-OCT-05:03 | -0.8 | -0.8 | 0.198787E+10 | 2606.68 | 03-OCT-13:09 | -0.8 | -0.8 |
November | 0.114789E+11 | 29599.12 | 09-NOV-07:01 | 10.17 | 5.62 | 0.195908E+10 | 2606.63 | 29-NOV-10:50 | -9.0 | -9.0 |
December | 0.925062E+10 | 12552.63 | 15-DEC-16:00 | 6.00 | 2.22 | 0.183069E+10 | 2606.63 | 18-DEC-10:20 | 3.33 | -0.7 |
Annual Sum or Average | 0.178044E+12 | 0.236516E+11 | ||||||||
Minimum of Months | 0.844814E+10 | 12552.63 | -0.8 | -0.8 | 0.174592E+10 | 2606.63 | -9.0 | -9.0 | ||
Maximum of Months | 0.222675E+11 | 34035.97 | 18.27 | 14.77 | 0.216076E+10 | 2606.87 | 18.27 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232535E+09 | 2905.73 | 20-JAN-15:05 | 19.67 | 6.93 | 0.00 | 0.00 | 01-JAN-00:10 | 19.67 | 6.93 |
February | 0.337070E+09 | 2968.12 | 18-FEB-14:30 | 19.50 | 7.87 | 0.00 | 0.00 | 01-FEB-00:10 | 19.50 | 7.87 |
March | 0.121739E+10 | 6802.14 | 14-MAR-14:05 | 23.00 | 7.59 | 0.00 | 0.00 | 01-MAR-00:10 | 23.00 | 7.59 |
April | 0.126572E+10 | 6127.91 | 21-APR-13:30 | 15.50 | 6.04 | 0.00 | 0.00 | 01-APR-00:10 | 15.50 | 6.04 |
May | 0.304685E+10 | 8437.17 | 31-MAY-14:30 | 28.00 | 14.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.00 | 14.75 |
June | 0.676589E+10 | 11359.40 | 26-JUN-13:20 | 36.97 | 15.36 | 0.00 | 0.00 | 01-JUN-00:10 | 36.97 | 15.36 |
July | 0.619382E+10 | 9869.06 | 17-JUL-14:00 | 35.00 | 14.93 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 14.93 |
August | 0.629758E+10 | 11117.40 | 16-AUG-15:00 | 36.00 | 16.15 | 0.00 | 0.00 | 01-AUG-00:10 | 36.00 | 16.15 |
September | 0.406875E+10 | 8406.76 | 12-SEP-14:20 | 29.40 | 13.78 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 13.78 |
October | 0.146884E+10 | 6521.11 | 11-OCT-15:10 | 25.67 | 9.32 | 0.00 | 0.00 | 01-OCT-00:10 | 25.67 | 9.32 |
November | 0.493071E+09 | 4066.44 | 09-NOV-13:05 | 20.00 | 8.90 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 8.90 |
December | 0.131184E+09 | 1704.99 | 01-DEC-14:30 | 21.50 | 7.65 | 0.00 | 0.00 | 01-DEC-00:10 | 21.50 | 7.65 |
Annual Sum or Average | 0.315187E+11 | 0.00 | ||||||||
Minimum of Months | 0.131184E+09 | 1704.99 | 15.50 | 6.04 | 0.00 | 0.00 | 15.50 | 6.04 | ||
Maximum of Months | 0.676589E+10 | 11359.40 | 36.97 | 16.15 | 0.00 | 0.00 | 36.97 | 16.15 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70236580.62 | 2945.94 | 05-JAN-05:01 | -17.0 | -17.0 | 0.00 | 0.00 | 01-JAN-00:10 | -17.0 | -17.0 |
February | 67343610.77 | 2290.77 | 10-FEB-06:01 | -8.2 | -9.1 | 0.00 | 0.00 | 01-FEB-00:10 | -8.2 | -9.1 |
March | 0.395720E+09 | 2608.31 | 15-MAR-16:00 | 19.00 | 5.38 | 0.00 | 0.00 | 01-MAR-00:10 | 19.00 | 5.38 |
April | 0.281975E+09 | 2400.53 | 15-APR-06:03 | -4.8 | -5.7 | 0.00 | 0.00 | 01-APR-00:10 | -4.8 | -5.7 |
May | 0.124827E+10 | 2614.81 | 18-MAY-14:20 | 23.67 | 11.39 | 0.00 | 0.00 | 01-MAY-00:10 | 23.67 | 11.39 |
June | 0.346846E+10 | 5112.17 | 26-JUN-10:10 | 31.05 | 15.98 | 0.00 | 0.00 | 01-JUN-00:10 | 31.05 | 15.98 |
July | 0.341875E+10 | 5468.27 | 17-JUL-10:10 | 34.17 | 14.38 | 0.00 | 0.00 | 01-JUL-00:10 | 34.17 | 14.38 |
August | 0.339786E+10 | 4718.04 | 21-AUG-14:40 | 27.00 | 14.47 | 0.00 | 0.00 | 01-AUG-00:10 | 27.00 | 14.47 |
September | 0.232058E+10 | 4677.65 | 05-SEP-15:40 | 24.60 | 13.98 | 0.00 | 0.00 | 01-SEP-00:10 | 24.60 | 13.98 |
October | 0.570354E+09 | 3195.47 | 10-OCT-16:00 | 25.00 | 8.21 | 0.00 | 0.00 | 01-OCT-00:10 | 25.00 | 8.21 |
November | 0.136544E+09 | 2252.59 | 02-NOV-05:01 | -9.0 | -9.0 | 0.00 | 0.00 | 01-NOV-00:10 | -9.0 | -9.0 |
December | 42127189.44 | 3597.80 | 23-DEC-05:01 | -21.4 | -21.6 | 0.00 | 0.00 | 01-DEC-00:10 | -21.4 | -21.6 |
Annual Sum or Average | 0.154182E+11 | 0.00 | ||||||||
Minimum of Months | 42127189.44 | 2252.59 | -21.4 | -21.6 | 0.00 | 0.00 | -21.4 | -21.6 | ||
Maximum of Months | 0.346846E+10 | 5468.27 | 34.17 | 15.98 | 0.00 | 0.00 | 34.17 | 15.98 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278280E+09 | 2819.56 | 05-JAN-06:01 | -17.0 | -17.0 | 0.00 | 0.00 | 01-JAN-00:10 | -17.0 | -17.0 |
February | 0.247608E+09 | 2651.71 | 02-FEB-06:01 | -9.2 | -9.2 | 0.00 | 0.00 | 01-FEB-00:10 | -9.2 | -9.2 |
March | 0.677865E+09 | 2815.07 | 30-MAR-06:01 | -1.7 | -3.0 | 0.00 | 0.00 | 01-MAR-00:10 | -1.7 | -3.0 |
April | 0.502068E+09 | 2543.06 | 03-APR-05:01 | -8.0 | -8.0 | 0.00 | 0.00 | 01-APR-00:10 | -8.0 | -8.0 |
May | 0.155161E+10 | 2598.45 | 16-MAY-15:50 | 27.00 | 11.83 | 0.00 | 0.00 | 01-MAY-00:10 | 27.00 | 11.83 |
June | 0.361671E+10 | 5565.11 | 26-JUN-12:08 | 36.18 | 15.20 | 0.00 | 0.00 | 01-JUN-00:10 | 36.18 | 15.20 |
July | 0.356733E+10 | 5540.10 | 17-JUL-12:08 | 36.00 | 14.76 | 0.00 | 0.00 | 01-JUL-00:10 | 36.00 | 14.76 |
August | 0.375804E+10 | 4575.93 | 21-AUG-15:00 | 26.00 | 14.34 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 14.34 |
September | 0.295027E+10 | 5092.74 | 05-SEP-06:07 | 13.90 | 7.58 | 0.00 | 0.00 | 01-SEP-00:10 | 13.90 | 7.58 |
October | 0.121529E+10 | 3328.80 | 11-OCT-16:20 | 23.33 | 8.54 | 0.00 | 0.00 | 01-OCT-00:10 | 23.33 | 8.54 |
November | 0.458349E+09 | 2373.26 | 24-NOV-07:01 | -4.7 | -4.7 | 0.00 | 0.00 | 01-NOV-00:10 | -4.7 | -4.7 |
December | 0.210934E+09 | 3324.80 | 19-DEC-17:10 | -17.0 | -17.2 | 0.00 | 0.00 | 01-DEC-00:10 | -17.0 | -17.2 |
Annual Sum or Average | 0.190343E+11 | 0.00 | ||||||||
Minimum of Months | 0.210934E+09 | 2373.26 | -17.0 | -17.2 | 0.00 | 0.00 | -17.0 | -17.2 | ||
Maximum of Months | 0.375804E+10 | 5565.11 | 36.18 | 15.20 | 0.00 | 0.00 | 36.18 | 15.20 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.698832E+10 | 9763.55 | 25-JAN-16:20 | 13.67 | 4.08 | 0.180506E+10 | 2606.64 | 27-JAN-10:20 | 2.33 | 2.17 |
February | 0.611320E+10 | 9830.48 | 27-FEB-16:20 | 13.00 | 4.42 | 0.162633E+10 | 2606.63 | 28-FEB-10:20 | 2.67 | 1.45 |
March | 0.896146E+10 | 13376.23 | 15-MAR-16:00 | 19.00 | 5.38 | 0.203041E+10 | 2606.65 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.801348E+10 | 11990.62 | 21-APR-14:00 | 15.00 | 5.55 | 0.181738E+10 | 2606.72 | 13-APR-13:00 | 15.00 | 5.55 |
May | 0.126089E+11 | 15675.05 | 22-MAY-06:02 | 11.17 | 10.50 | 0.206287E+10 | 2606.66 | 18-MAY-09:09 | 11.17 | 10.50 |
June | 0.173453E+11 | 28309.88 | 27-JUN-05:12 | 18.63 | 8.20 | 0.206845E+10 | 2606.67 | 08-JUN-13:09 | 18.63 | 8.20 |
July | 0.171274E+11 | 29515.46 | 03-JUL-06:03 | 11.00 | 7.64 | 0.192250E+10 | 2607.01 | 17-JUL-09:20 | 32.00 | 14.13 |
August | 0.176914E+11 | 29182.55 | 28-AUG-05:12 | 15.00 | 14.37 | 0.215821E+10 | 2606.65 | 10-AUG-09:39 | 15.00 | 14.37 |
September | 0.150998E+11 | 30101.54 | 05-SEP-06:03 | 13.90 | 7.58 | 0.191394E+10 | 2606.85 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.103429E+11 | 26423.85 | 10-OCT-06:01 | 8.33 | 4.27 | 0.192807E+10 | 2606.63 | 03-OCT-13:20 | 8.33 | 4.27 |
November | 0.778302E+10 | 11775.91 | 08-NOV-16:20 | 16.33 | 7.18 | 0.185415E+10 | 2606.62 | 14-NOV-10:20 | 3.33 | 2.24 |
December | 0.637068E+10 | 8072.56 | 21-DEC-16:35 | -20.3 | -20.6 | 0.168033E+10 | 2606.60 | 05-DEC-10:20 | -20.3 | -20.6 |
Annual Sum or Average | 0.134446E+12 | 0.228677E+11 | ||||||||
Minimum of Months | 0.611320E+10 | 8072.56 | -20.3 | -20.6 | 0.162633E+10 | 2606.60 | -20.3 | -20.6 | ||
Maximum of Months | 0.176914E+11 | 30101.54 | 19.00 | 14.37 | 0.215821E+10 | 2607.01 | 32.00 | 14.37 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.537011E+10 | 8696.96 | 20-JAN-16:30 | 15.00 | 6.47 | 0.169005E+10 | 2606.58 | 26-JAN-14:20 | 9.00 | 2.97 |
February | 0.487450E+10 | 8950.56 | 27-FEB-16:10 | 13.00 | 4.38 | 0.154322E+10 | 2606.59 | 22-FEB-14:20 | 13.00 | 4.38 |
March | 0.786604E+10 | 14476.43 | 15-MAR-15:20 | 19.67 | 5.62 | 0.195027E+10 | 2606.65 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.730384E+10 | 13546.70 | 21-APR-14:00 | 15.00 | 5.55 | 0.175873E+10 | 2606.72 | 13-APR-13:00 | 15.00 | 5.55 |
May | 0.122175E+11 | 15477.08 | 31-MAY-15:40 | 28.00 | 14.79 | 0.203999E+10 | 2606.66 | 18-MAY-09:09 | 28.00 | 14.79 |
June | 0.181389E+11 | 30247.80 | 26-JUN-05:12 | 17.53 | 11.60 | 0.206701E+10 | 2606.68 | 08-JUN-13:09 | 17.53 | 11.60 |
July | 0.177806E+11 | 30889.00 | 24-JUL-05:12 | 18.00 | 14.77 | 0.192173E+10 | 2606.65 | 11-JUL-09:30 | 18.00 | 14.77 |
August | 0.180486E+11 | 30567.06 | 21-AUG-05:12 | 19.83 | 12.23 | 0.215620E+10 | 2606.66 | 10-AUG-09:50 | 19.83 | 12.23 |
September | 0.142645E+11 | 31047.42 | 05-SEP-05:12 | 14.20 | 8.43 | 0.190412E+10 | 2606.85 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.841243E+10 | 15318.41 | 10-OCT-14:50 | 25.00 | 8.50 | 0.184436E+10 | 2606.63 | 19-OCT-09:20 | 9.67 | 2.68 |
November | 0.615995E+10 | 11110.04 | 07-NOV-16:10 | 20.00 | 7.03 | 0.173577E+10 | 2606.59 | 08-NOV-14:20 | 19.00 | 7.64 |
December | 0.465215E+10 | 7426.30 | 23-DEC-17:02 | -16.2 | -16.6 | 0.157460E+10 | 2606.48 | 04-DEC-14:00 | -16.2 | -16.6 |
Annual Sum or Average | 0.125089E+12 | 0.221860E+11 | ||||||||
Minimum of Months | 0.465215E+10 | 7426.30 | -16.2 | -16.6 | 0.154322E+10 | 2606.48 | -16.2 | -16.6 | ||
Maximum of Months | 0.181389E+11 | 31047.42 | 28.00 | 14.79 | 0.215620E+10 | 2606.85 | 28.00 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.551728E+09 | 1441.67 | 20-JAN-14:40 | 20.33 | 6.84 | 0.324853E+09 | 535.02 | 20-JAN-16:19 | 16.00 | 6.84 |
February | 0.514101E+09 | 1341.49 | 27-FEB-13:10 | 14.00 | 4.75 | 0.295661E+09 | 546.79 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.117471E+10 | 3706.03 | 14-MAR-14:30 | 23.00 | 7.59 | 0.384525E+09 | 549.49 | 16-MAR-13:20 | 16.00 | 5.23 |
April | 0.133232E+10 | 3742.40 | 20-APR-13:30 | 21.50 | 8.83 | 0.353448E+09 | 549.51 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.310225E+10 | 5533.16 | 17-MAY-13:30 | 29.00 | 11.78 | 0.423957E+09 | 549.50 | 17-MAY-09:20 | 29.00 | 11.78 |
June | 0.584455E+10 | 10856.75 | 25-JUN-17:11 | 32.33 | 14.00 | 0.435930E+09 | 549.92 | 14-JUN-13:50 | 32.33 | 14.00 |
July | 0.568385E+10 | 10944.45 | 16-JUL-14:22 | 35.50 | 14.51 | 0.405429E+09 | 549.79 | 18-JUL-13:09 | 34.33 | 14.01 |
August | 0.520918E+10 | 6561.98 | 20-AUG-15:42 | 28.00 | 14.08 | 0.453721E+09 | 549.50 | 21-AUG-09:20 | 25.67 | 14.10 |
September | 0.359320E+10 | 6481.34 | 10-SEP-16:01 | 31.92 | 12.68 | 0.396846E+09 | 549.54 | 05-SEP-09:09 | 31.92 | 12.68 |
October | 0.139008E+10 | 4022.37 | 11-OCT-14:30 | 26.50 | 9.60 | 0.365402E+09 | 549.49 | 11-OCT-13:20 | 26.50 | 9.60 |
November | 0.743971E+09 | 2446.13 | 09-NOV-13:30 | 20.00 | 8.78 | 0.334708E+09 | 549.48 | 09-NOV-14:20 | 19.33 | 8.45 |
December | 0.391648E+09 | 1522.89 | 23-DEC-17:02 | -16.2 | -16.6 | 0.304433E+09 | 524.61 | 04-DEC-14:00 | -16.2 | -16.6 |
Annual Sum or Average | 0.295316E+11 | 0.447891E+10 | ||||||||
Minimum of Months | 0.391648E+09 | 1341.49 | -16.2 | -16.6 | 0.295661E+09 | 524.61 | -16.2 | -16.6 | ||
Maximum of Months | 0.584455E+10 | 10944.45 | 35.50 | 14.51 | 0.453721E+09 | 549.92 | 34.33 | 14.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.622973E+09 | 2812.43 | 20-JAN-09:40 | 12.67 | 4.18 | 0.225928E+09 | 347.88 | 10-JAN-10:09 | 12.67 | 4.18 |
February | 0.755279E+09 | 4216.25 | 27-FEB-09:10 | 9.17 | 2.67 | 0.210194E+09 | 347.88 | 23-FEB-10:20 | 9.17 | 2.67 |
March | 0.175753E+10 | 8832.13 | 12-MAR-09:53 | 15.00 | 5.59 | 0.263442E+09 | 347.88 | 27-MAR-09:39 | 0.67 | -0.6 |
April | 0.186606E+10 | 7274.19 | 21-APR-08:40 | 11.67 | 5.95 | 0.238142E+09 | 347.89 | 13-APR-13:00 | 11.67 | 5.95 |
May | 0.345302E+10 | 8864.12 | 28-MAY-09:23 | 13.00 | 8.85 | 0.273986E+09 | 347.95 | 16-MAY-09:09 | 13.00 | 8.85 |
June | 0.614733E+10 | 11206.71 | 11-JUN-09:02 | 20.37 | 10.85 | 0.276560E+09 | 348.63 | 05-JUN-09:00 | 20.37 | 10.85 |
July | 0.575591E+10 | 13492.90 | 16-JUL-09:02 | 33.17 | 14.76 | 0.257361E+09 | 348.83 | 18-JUL-09:00 | 31.00 | 14.50 |
August | 0.593555E+10 | 13588.57 | 06-AUG-09:02 | 25.33 | 15.45 | 0.288049E+09 | 348.64 | 14-AUG-09:00 | 28.00 | 11.89 |
September | 0.412394E+10 | 11519.92 | 04-SEP-09:12 | 24.97 | 13.41 | 0.254229E+09 | 348.37 | 18-SEP-09:09 | 23.08 | 10.77 |
October | 0.172307E+10 | 8120.91 | 01-OCT-09:43 | 13.83 | 7.94 | 0.242151E+09 | 347.88 | 03-OCT-09:09 | 8.50 | 7.11 |
November | 0.847876E+09 | 3924.17 | 07-NOV-09:10 | 14.00 | 4.09 | 0.228704E+09 | 347.87 | 14-NOV-10:20 | 3.33 | 2.24 |
December | 0.418790E+09 | 1238.49 | 14-DEC-09:35 | 9.33 | 1.23 | 0.208734E+09 | 347.88 | 18-DEC-10:20 | 3.33 | -0.7 |
Annual Sum or Average | 0.334073E+11 | 0.296748E+10 | ||||||||
Minimum of Months | 0.418790E+09 | 1238.49 | 9.17 | 1.23 | 0.208734E+09 | 347.87 | 0.67 | -0.7 | ||
Maximum of Months | 0.614733E+10 | 13588.57 | 33.17 | 15.45 | 0.288049E+09 | 348.83 | 31.00 | 14.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391910E+10 | 15456.62 | 22-JAN-12:13 | 6.33 | 3.28 | 0.383065E+09 | 567.25 | 20-JAN-14:09 | 6.33 | 3.28 |
February | 0.369752E+10 | 15646.72 | 26-FEB-13:02 | 17.83 | 4.74 | 0.348187E+09 | 549.73 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.425352E+10 | 16990.76 | 12-MAR-12:31 | 18.67 | 6.04 | 0.414375E+09 | 564.44 | 15-MAR-13:20 | 20.33 | 5.93 |
April | 0.285876E+10 | 9303.12 | 21-APR-13:05 | 15.83 | 6.37 | 0.368475E+09 | 549.83 | 21-APR-13:39 | 15.33 | 5.87 |
May | 0.420488E+10 | 8127.07 | 16-MAY-13:10 | 27.17 | 12.14 | 0.425737E+09 | 549.51 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.666756E+10 | 14327.74 | 25-JUN-14:32 | 33.43 | 13.43 | 0.435471E+09 | 549.91 | 30-JUN-13:09 | 34.68 | 13.73 |
July | 0.673073E+10 | 15371.41 | 30-JUL-13:13 | 28.33 | 19.61 | 0.405383E+09 | 549.51 | 11-JUL-09:30 | 28.33 | 19.61 |
August | 0.791371E+10 | 15086.45 | 20-AUG-13:42 | 27.83 | 14.68 | 0.454340E+09 | 562.79 | 31-AUG-13:09 | 30.00 | 11.91 |
September | 0.727279E+10 | 16177.09 | 04-SEP-13:12 | 29.40 | 13.45 | 0.400874E+09 | 603.40 | 28-SEP-13:09 | 30.50 | 11.31 |
October | 0.545001E+10 | 17373.83 | 01-OCT-13:41 | 17.00 | 8.82 | 0.384810E+09 | 591.72 | 10-OCT-13:09 | 24.17 | 8.07 |
November | 0.430306E+10 | 16142.64 | 05-NOV-11:02 | 18.33 | 5.34 | 0.383420E+09 | 574.16 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.305138E+10 | 16507.99 | 03-DEC-13:02 | 17.33 | 6.34 | 0.359458E+09 | 549.63 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.603230E+11 | 0.476359E+10 | ||||||||
Minimum of Months | 0.285876E+10 | 8127.07 | 6.33 | 3.28 | 0.348187E+09 | 549.51 | 6.33 | 3.00 | ||
Maximum of Months | 0.791371E+10 | 17373.83 | 33.43 | 19.61 | 0.454340E+09 | 603.40 | 34.68 | 19.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.790785E+09 | 4921.59 | 20-JAN-15:40 | 18.67 | 7.30 | 0.219945E+09 | 347.83 | 24-JAN-14:20 | 17.67 | 6.59 |
February | 0.870176E+09 | 5328.14 | 17-FEB-16:30 | 13.50 | 6.66 | 0.200841E+09 | 347.84 | 22-FEB-14:20 | 8.00 | 3.90 |
March | 0.177032E+10 | 15433.35 | 12-MAR-15:52 | 18.00 | 5.76 | 0.250073E+09 | 347.84 | 16-MAR-13:20 | 16.00 | 5.23 |
April | 0.169937E+10 | 11119.84 | 08-APR-17:05 | 15.67 | 5.07 | 0.227492E+09 | 347.87 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.315539E+10 | 9855.85 | 28-MAY-14:53 | 20.00 | 10.08 | 0.268860E+09 | 347.85 | 17-MAY-09:20 | 20.00 | 10.08 |
June | 0.562684E+10 | 15880.09 | 11-JUN-16:21 | 28.35 | 12.62 | 0.275947E+09 | 347.86 | 20-JUN-13:00 | 23.30 | 16.53 |
July | 0.495534E+10 | 15812.42 | 02-JUL-16:51 | 28.00 | 12.40 | 0.256721E+09 | 347.86 | 11-JUL-09:30 | 25.50 | 13.66 |
August | 0.512151E+10 | 15477.88 | 13-AUG-16:32 | 22.33 | 9.94 | 0.287522E+09 | 347.86 | 21-AUG-09:20 | 25.67 | 14.10 |
September | 0.372907E+10 | 15669.69 | 10-SEP-16:01 | 31.92 | 12.68 | 0.252021E+09 | 347.88 | 05-SEP-09:09 | 31.92 | 12.68 |
October | 0.196949E+10 | 12058.97 | 09-OCT-16:02 | 21.83 | 8.61 | 0.235092E+09 | 347.85 | 11-OCT-13:20 | 26.33 | 9.54 |
November | 0.100704E+10 | 6090.27 | 07-NOV-15:30 | 21.50 | 7.27 | 0.223002E+09 | 347.85 | 09-NOV-14:20 | 19.33 | 8.45 |
December | 0.518797E+09 | 3667.37 | 01-DEC-15:30 | 19.50 | 7.14 | 0.205248E+09 | 347.84 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.312141E+11 | 0.290276E+10 | ||||||||
Minimum of Months | 0.518797E+09 | 3667.37 | 13.50 | 5.07 | 0.200841E+09 | 347.83 | 8.00 | 3.00 | ||
Maximum of Months | 0.562684E+10 | 15880.09 | 31.92 | 12.68 | 0.287522E+09 | 347.88 | 31.92 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.534115E+09 | 1291.70 | 24-JAN-14:50 | 17.17 | 6.51 | 0.320263E+09 | 485.10 | 25-JAN-14:00 | 14.00 | 4.48 |
February | 0.413437E+09 | 1219.13 | 27-FEB-13:30 | 14.00 | 4.75 | 0.288935E+09 | 491.87 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.860718E+09 | 1705.13 | 14-MAR-15:00 | 23.00 | 7.59 | 0.369647E+09 | 549.48 | 16-MAR-13:20 | 16.00 | 5.23 |
April | 0.101080E+10 | 1562.95 | 20-APR-13:30 | 21.50 | 8.83 | 0.342193E+09 | 549.49 | 13-APR-13:20 | 21.50 | 8.83 |
May | 0.205318E+10 | 3715.46 | 17-MAY-13:30 | 29.00 | 11.78 | 0.420962E+09 | 549.50 | 18-MAY-09:20 | 20.67 | 11.73 |
June | 0.443450E+10 | 6805.32 | 26-JUN-06:03 | 19.77 | 12.60 | 0.435420E+09 | 549.75 | 13-JUN-13:20 | 19.77 | 12.60 |
July | 0.442791E+10 | 6916.32 | 17-JUL-06:03 | 22.50 | 11.12 | 0.404856E+09 | 549.65 | 25-JUL-13:20 | 28.67 | 16.33 |
August | 0.436420E+10 | 5214.81 | 21-AUG-13:50 | 29.00 | 14.47 | 0.454024E+09 | 549.50 | 21-AUG-09:20 | 29.00 | 14.47 |
September | 0.350462E+10 | 6422.38 | 11-SEP-06:03 | 19.00 | 9.04 | 0.400868E+09 | 549.54 | 05-SEP-09:09 | 19.00 | 9.04 |
October | 0.155144E+10 | 3310.60 | 11-OCT-14:00 | 27.00 | 9.73 | 0.380894E+09 | 549.49 | 03-OCT-13:20 | 27.00 | 9.73 |
November | 0.953127E+09 | 1999.84 | 09-NOV-13:30 | 20.00 | 8.78 | 0.343308E+09 | 549.49 | 09-NOV-10:20 | 20.00 | 8.78 |
December | 0.507626E+09 | 1349.40 | 23-DEC-17:02 | -16.2 | -16.6 | 0.308456E+09 | 504.92 | 04-DEC-14:00 | -16.2 | -16.6 |
Annual Sum or Average | 0.246157E+11 | 0.446983E+10 | ||||||||
Minimum of Months | 0.413437E+09 | 1219.13 | -16.2 | -16.6 | 0.288935E+09 | 485.10 | -16.2 | -16.6 | ||
Maximum of Months | 0.443450E+10 | 6916.32 | 29.00 | 14.47 | 0.454024E+09 | 549.75 | 29.00 | 16.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.619351E+09 | 1890.61 | 25-JAN-08:30 | 5.00 | 0.11 | 0.226313E+09 | 347.87 | 24-JAN-10:20 | 5.00 | 0.11 |
February | 0.663993E+09 | 3346.92 | 27-FEB-08:35 | 7.67 | 2.12 | 0.207878E+09 | 347.88 | 23-FEB-10:20 | 7.67 | 2.12 |
March | 0.138408E+10 | 4656.82 | 15-MAR-08:50 | 13.17 | 3.86 | 0.262406E+09 | 347.88 | 27-MAR-09:20 | 1.33 | -0.7 |
April | 0.145681E+10 | 4897.25 | 21-APR-08:50 | 11.83 | 5.97 | 0.237913E+09 | 347.88 | 13-APR-09:00 | 11.83 | 5.97 |
May | 0.263199E+10 | 7591.86 | 16-MAY-06:02 | 13.67 | 8.41 | 0.274160E+09 | 347.90 | 31-MAY-09:00 | 25.00 | 13.24 |
June | 0.528594E+10 | 8201.18 | 08-JUN-06:02 | 14.77 | 8.93 | 0.276621E+09 | 348.43 | 27-JUN-09:00 | 26.60 | 12.07 |
July | 0.496466E+10 | 10556.21 | 16-JUL-09:02 | 33.17 | 14.76 | 0.257406E+09 | 348.38 | 18-JUL-09:00 | 31.00 | 14.50 |
August | 0.553639E+10 | 10864.43 | 06-AUG-08:51 | 25.00 | 15.42 | 0.288420E+09 | 348.28 | 16-AUG-09:50 | 32.33 | 12.79 |
September | 0.432023E+10 | 11047.35 | 04-SEP-09:01 | 24.68 | 13.41 | 0.255633E+09 | 348.44 | 08-SEP-09:50 | 25.82 | 12.10 |
October | 0.198162E+10 | 6626.80 | 09-OCT-09:23 | 13.50 | 8.57 | 0.250481E+09 | 347.88 | 03-OCT-13:09 | 13.50 | 8.57 |
November | 0.104556E+10 | 3594.01 | 07-NOV-08:25 | 12.00 | 3.43 | 0.237460E+09 | 347.87 | 14-NOV-10:20 | 3.33 | 2.24 |
December | 0.520669E+09 | 1492.51 | 18-DEC-08:30 | -1.5 | -3.4 | 0.214508E+09 | 347.88 | 18-DEC-10:20 | 3.33 | -0.7 |
Annual Sum or Average | 0.304113E+11 | 0.298920E+10 | ||||||||
Minimum of Months | 0.520669E+09 | 1492.51 | -1.5 | -3.4 | 0.207878E+09 | 347.87 | 1.33 | -0.7 | ||
Maximum of Months | 0.553639E+10 | 11047.35 | 33.17 | 15.42 | 0.288420E+09 | 348.44 | 32.33 | 14.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247500E+10 | 11919.74 | 22-JAN-15:13 | 8.33 | 4.26 | 0.368140E+09 | 554.97 | 24-JAN-14:09 | 17.83 | 6.61 |
February | 0.197608E+10 | 12251.66 | 26-FEB-14:02 | 17.00 | 4.30 | 0.325890E+09 | 549.65 | 17-FEB-14:50 | 17.00 | 4.30 |
March | 0.239835E+10 | 12598.61 | 12-MAR-12:31 | 18.67 | 6.04 | 0.395589E+09 | 557.76 | 13-MAR-13:00 | 23.00 | 7.20 |
April | 0.143817E+10 | 5669.51 | 12-APR-13:30 | 21.00 | 7.78 | 0.346787E+09 | 549.51 | 13-APR-13:50 | 15.50 | 9.79 |
May | 0.234333E+10 | 6689.06 | 16-MAY-12:00 | 27.00 | 11.84 | 0.409783E+09 | 549.52 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.563399E+10 | 10899.97 | 26-JUN-12:00 | 36.10 | 15.16 | 0.433720E+09 | 613.06 | 26-JUN-12:09 | 36.18 | 15.20 |
July | 0.571958E+10 | 10850.27 | 17-JUL-12:00 | 36.00 | 14.76 | 0.403853E+09 | 611.93 | 17-JUL-12:09 | 36.00 | 14.76 |
August | 0.735649E+10 | 11755.22 | 06-AUG-12:52 | 31.00 | 15.61 | 0.454102E+09 | 625.49 | 16-AUG-12:09 | 35.17 | 12.78 |
September | 0.725775E+10 | 13109.85 | 04-SEP-13:41 | 29.40 | 13.31 | 0.401977E+09 | 620.02 | 28-SEP-12:09 | 30.08 | 11.35 |
October | 0.473233E+10 | 12838.81 | 09-OCT-13:22 | 22.00 | 8.88 | 0.384148E+09 | 622.42 | 10-OCT-13:39 | 24.67 | 8.45 |
November | 0.340334E+10 | 12826.31 | 19-NOV-12:42 | 9.17 | 4.04 | 0.373307E+09 | 590.59 | 07-NOV-14:09 | 9.17 | 4.04 |
December | 0.218929E+10 | 12713.90 | 17-DEC-15:02 | 17.25 | 5.54 | 0.339608E+09 | 549.71 | 15-DEC-14:00 | 17.25 | 5.54 |
Annual Sum or Average | 0.469237E+11 | 0.463690E+10 | ||||||||
Minimum of Months | 0.143817E+10 | 5669.51 | 8.33 | 4.04 | 0.325890E+09 | 549.51 | 9.17 | 4.04 | ||
Maximum of Months | 0.735649E+10 | 13109.85 | 36.10 | 15.61 | 0.454102E+09 | 625.49 | 36.18 | 15.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.703864E+09 | 3729.71 | 23-JAN-16:10 | 18.17 | 6.14 | 0.221229E+09 | 347.83 | 27-JAN-14:20 | 9.33 | 5.12 |
February | 0.664889E+09 | 3900.63 | 17-FEB-16:30 | 13.50 | 6.66 | 0.200963E+09 | 347.84 | 22-FEB-14:20 | 8.00 | 3.90 |
March | 0.126866E+10 | 11428.42 | 12-MAR-16:32 | 18.00 | 5.65 | 0.250017E+09 | 347.85 | 16-MAR-09:20 | 11.67 | 3.37 |
April | 0.121289E+10 | 7282.48 | 08-APR-17:05 | 15.67 | 5.07 | 0.228265E+09 | 347.85 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.224092E+10 | 5957.65 | 31-MAY-16:00 | 28.00 | 14.86 | 0.270235E+09 | 347.85 | 10-MAY-13:50 | 28.00 | 14.86 |
June | 0.467284E+10 | 11999.20 | 25-JUN-16:31 | 32.70 | 13.89 | 0.276250E+09 | 347.86 | 27-JUN-09:20 | 25.53 | 11.25 |
July | 0.408685E+10 | 11819.66 | 02-JUL-17:52 | 28.00 | 12.39 | 0.256816E+09 | 347.85 | 11-JUL-09:30 | 25.50 | 13.66 |
August | 0.461114E+10 | 12091.71 | 13-AUG-17:41 | 22.83 | 10.50 | 0.288183E+09 | 347.86 | 15-AUG-13:39 | 25.33 | 13.66 |
September | 0.380194E+10 | 12361.48 | 17-SEP-16:01 | 26.52 | 10.67 | 0.255130E+09 | 347.88 | 05-SEP-09:09 | 26.52 | 10.67 |
October | 0.207388E+10 | 10667.51 | 09-OCT-16:02 | 21.83 | 8.61 | 0.248047E+09 | 347.85 | 19-OCT-09:20 | 9.67 | 2.68 |
November | 0.111868E+10 | 5338.38 | 07-NOV-15:40 | 21.33 | 7.24 | 0.233143E+09 | 347.85 | 07-NOV-10:20 | 21.33 | 7.24 |
December | 0.594277E+09 | 3073.29 | 04-DEC-15:30 | 18.00 | 5.80 | 0.210232E+09 | 347.83 | 18-DEC-14:00 | 5.00 | 0.54 |
Annual Sum or Average | 0.270508E+11 | 0.293851E+10 | ||||||||
Minimum of Months | 0.594277E+09 | 3073.29 | 13.50 | 5.07 | 0.200963E+09 | 347.83 | 5.00 | 0.54 | ||
Maximum of Months | 0.467284E+10 | 12361.48 | 32.70 | 14.86 | 0.288183E+09 | 347.88 | 28.00 | 14.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.779906E+09 | 1444.56 | 20-JAN-15:10 | 19.67 | 6.93 | 0.335020E+09 | 535.01 | 20-JAN-16:30 | 15.00 | 6.47 |
February | 0.702102E+09 | 1504.44 | 27-FEB-15:30 | 13.50 | 4.54 | 0.303513E+09 | 547.66 | 27-FEB-14:00 | 13.50 | 4.54 |
March | 0.137307E+10 | 3516.75 | 14-MAR-14:30 | 23.00 | 7.59 | 0.395315E+09 | 549.49 | 16-MAR-09:20 | 11.67 | 3.37 |
April | 0.147590E+10 | 3363.01 | 20-APR-13:30 | 21.50 | 8.83 | 0.363562E+09 | 549.51 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.316962E+10 | 5212.75 | 17-MAY-13:30 | 29.00 | 11.78 | 0.429761E+09 | 549.50 | 18-MAY-09:09 | 20.33 | 11.73 |
June | 0.562794E+10 | 9384.68 | 25-JUN-19:02 | 28.75 | 13.30 | 0.436332E+09 | 550.56 | 14-JUN-13:20 | 28.75 | 13.30 |
July | 0.549281E+10 | 9328.13 | 16-JUL-14:12 | 35.33 | 14.43 | 0.405750E+09 | 550.54 | 24-JUL-13:20 | 32.00 | 16.99 |
August | 0.508736E+10 | 7177.45 | 21-AUG-06:03 | 19.75 | 12.40 | 0.454489E+09 | 550.45 | 18-AUG-13:20 | 19.75 | 12.40 |
September | 0.370845E+10 | 7310.98 | 11-SEP-06:03 | 19.00 | 9.04 | 0.400544E+09 | 549.54 | 05-SEP-09:09 | 19.00 | 9.04 |
October | 0.165147E+10 | 3951.77 | 10-OCT-15:20 | 25.00 | 8.38 | 0.380564E+09 | 549.49 | 06-OCT-09:20 | 25.00 | 8.38 |
November | 0.103788E+10 | 2609.21 | 09-NOV-13:30 | 20.00 | 8.78 | 0.347130E+09 | 549.49 | 08-NOV-10:20 | 20.00 | 8.78 |
December | 0.611877E+09 | 1357.46 | 23-DEC-17:02 | -16.2 | -16.6 | 0.313451E+09 | 540.60 | 04-DEC-14:00 | -16.2 | -16.6 |
Annual Sum or Average | 0.307184E+11 | 0.456543E+10 | ||||||||
Minimum of Months | 0.611877E+09 | 1357.46 | -16.2 | -16.6 | 0.303513E+09 | 535.01 | -16.2 | -16.6 | ||
Maximum of Months | 0.562794E+10 | 9384.68 | 35.33 | 14.43 | 0.454489E+09 | 550.56 | 32.00 | 16.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.695019E+09 | 4368.18 | 26-JAN-13:02 | 9.00 | 2.97 | 0.171590E+09 | 356.46 | 10-JAN-11:09 | 9.00 | 2.97 |
February | 0.862287E+09 | 5322.01 | 27-FEB-09:10 | 9.17 | 2.67 | 0.157888E+09 | 356.46 | 10-FEB-11:09 | 9.17 | 2.67 |
March | 0.185724E+10 | 9674.18 | 12-MAR-10:02 | 15.17 | 5.61 | 0.196570E+09 | 356.46 | 27-MAR-10:09 | 0.33 | -0.4 |
April | 0.189069E+10 | 9173.28 | 09-APR-08:32 | 10.67 | 4.92 | 0.178371E+09 | 356.47 | 13-APR-10:09 | 15.17 | 8.09 |
May | 0.338085E+10 | 10153.07 | 28-MAY-08:53 | 12.00 | 8.64 | 0.204033E+09 | 356.48 | 31-MAY-10:09 | 25.17 | 13.22 |
June | 0.581314E+10 | 13819.96 | 18-JUN-09:22 | 23.00 | 17.55 | 0.205229E+09 | 356.47 | 05-JUN-10:09 | 23.00 | 17.55 |
July | 0.545139E+10 | 14449.54 | 16-JUL-08:51 | 33.00 | 14.82 | 0.191614E+09 | 356.46 | 18-JUL-14:09 | 31.00 | 15.46 |
August | 0.563364E+10 | 13498.89 | 06-AUG-09:02 | 25.33 | 15.45 | 0.213680E+09 | 356.49 | 30-AUG-10:09 | 25.17 | 12.29 |
September | 0.409747E+10 | 14055.71 | 04-SEP-09:01 | 24.68 | 13.41 | 0.189216E+09 | 356.48 | 18-SEP-10:09 | 25.18 | 11.04 |
October | 0.188625E+10 | 10211.69 | 09-OCT-09:23 | 13.50 | 8.57 | 0.183044E+09 | 356.46 | 10-OCT-14:09 | 25.00 | 8.67 |
November | 0.961270E+09 | 4950.28 | 07-NOV-08:50 | 13.33 | 3.89 | 0.174099E+09 | 356.45 | 07-NOV-11:09 | 16.67 | 5.90 |
December | 0.471412E+09 | 2178.01 | 18-DEC-09:20 | 1.00 | -1.7 | 0.158936E+09 | 356.45 | 05-DEC-11:09 | 1.00 | -1.7 |
Annual Sum or Average | 0.330007E+11 | 0.222427E+10 | ||||||||
Minimum of Months | 0.471412E+09 | 2178.01 | 1.00 | -1.7 | 0.157888E+09 | 356.45 | 0.33 | -1.7 | ||
Maximum of Months | 0.581314E+10 | 14449.54 | 33.00 | 17.55 | 0.213680E+09 | 356.49 | 31.00 | 17.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.459100E+10 | 14099.25 | 22-JAN-11:13 | 4.67 | 2.46 | 0.391964E+09 | 589.45 | 20-JAN-14:09 | 4.67 | 2.46 |
February | 0.418813E+10 | 14438.22 | 26-FEB-13:02 | 17.83 | 4.74 | 0.354652E+09 | 557.74 | 17-FEB-14:09 | 17.83 | 4.74 |
March | 0.457806E+10 | 14252.04 | 12-MAR-12:42 | 18.83 | 6.01 | 0.422126E+09 | 580.94 | 15-MAR-13:20 | 20.33 | 5.93 |
April | 0.300967E+10 | 8886.81 | 12-APR-13:05 | 21.00 | 7.79 | 0.377459E+09 | 550.39 | 21-APR-13:50 | 15.17 | 5.71 |
May | 0.426821E+10 | 7631.77 | 16-MAY-13:10 | 27.17 | 12.14 | 0.430988E+09 | 549.52 | 10-MAY-13:50 | 27.17 | 12.14 |
June | 0.640975E+10 | 13388.36 | 25-JUN-16:21 | 32.70 | 13.84 | 0.436127E+09 | 550.95 | 30-JUN-13:20 | 34.97 | 13.87 |
July | 0.649886E+10 | 13790.23 | 23-JUL-11:22 | 31.00 | 16.01 | 0.405832E+09 | 550.77 | 31-JUL-13:20 | 26.67 | 17.30 |
August | 0.772516E+10 | 14431.41 | 27-AUG-12:22 | 25.00 | 15.13 | 0.455354E+09 | 573.34 | 31-AUG-13:09 | 30.00 | 11.91 |
September | 0.742930E+10 | 15616.09 | 04-SEP-11:41 | 28.12 | 13.34 | 0.403681E+09 | 621.60 | 28-SEP-13:20 | 30.50 | 11.31 |
October | 0.589188E+10 | 15160.63 | 15-OCT-13:32 | 13.67 | 3.81 | 0.395799E+09 | 615.59 | 10-OCT-13:09 | 13.67 | 3.81 |
November | 0.498795E+10 | 15923.47 | 05-NOV-12:11 | 20.33 | 5.94 | 0.393428E+09 | 599.02 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.363359E+10 | 15279.26 | 17-DEC-13:52 | 18.00 | 5.77 | 0.368008E+09 | 555.70 | 14-DEC-14:09 | 18.00 | 5.77 |
Annual Sum or Average | 0.632116E+11 | 0.483542E+10 | ||||||||
Minimum of Months | 0.300967E+10 | 7631.77 | 4.67 | 2.46 | 0.354652E+09 | 549.52 | 4.67 | 2.46 | ||
Maximum of Months | 0.772516E+10 | 15923.47 | 32.70 | 16.01 | 0.455354E+09 | 621.60 | 34.97 | 17.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.999219E+09 | 4876.40 | 20-JAN-15:40 | 18.67 | 7.30 | 0.226041E+09 | 347.84 | 26-JAN-14:20 | 9.00 | 2.97 |
February | 0.102702E+10 | 6508.60 | 26-FEB-15:43 | 17.83 | 5.06 | 0.205666E+09 | 347.84 | 28-FEB-14:30 | 4.50 | 2.83 |
March | 0.189788E+10 | 10697.08 | 12-MAR-16:02 | 18.00 | 5.74 | 0.256633E+09 | 347.85 | 16-MAR-09:20 | 11.67 | 3.37 |
April | 0.177100E+10 | 10299.40 | 08-APR-17:05 | 15.67 | 5.07 | 0.233952E+09 | 347.86 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.318308E+10 | 9473.05 | 28-MAY-15:02 | 20.00 | 10.02 | 0.272433E+09 | 347.86 | 10-MAY-13:50 | 20.00 | 10.02 |
June | 0.544333E+10 | 15838.39 | 25-JUN-16:21 | 32.70 | 13.84 | 0.276315E+09 | 347.86 | 27-JUN-09:20 | 25.53 | 11.25 |
July | 0.478975E+10 | 14459.31 | 02-JUL-16:32 | 28.00 | 12.40 | 0.256991E+09 | 347.92 | 17-JUL-09:20 | 32.00 | 14.13 |
August | 0.499726E+10 | 14440.41 | 13-AUG-17:31 | 22.67 | 10.36 | 0.288048E+09 | 347.86 | 15-AUG-13:39 | 25.33 | 13.66 |
September | 0.380986E+10 | 15282.53 | 17-SEP-16:01 | 26.52 | 10.67 | 0.254169E+09 | 347.88 | 05-SEP-09:09 | 26.52 | 10.67 |
October | 0.216956E+10 | 12041.31 | 09-OCT-16:02 | 21.83 | 8.61 | 0.243996E+09 | 347.85 | 06-OCT-09:20 | 21.83 | 8.61 |
November | 0.123484E+10 | 9138.37 | 05-NOV-14:52 | 21.00 | 6.77 | 0.230583E+09 | 347.85 | 09-NOV-14:20 | 19.33 | 8.45 |
December | 0.694608E+09 | 3707.80 | 14-DEC-15:30 | 14.50 | 4.64 | 0.210724E+09 | 347.84 | 11-DEC-14:30 | 14.50 | 4.64 |
Annual Sum or Average | 0.320174E+11 | 0.295555E+10 | ||||||||
Minimum of Months | 0.694608E+09 | 3707.80 | 14.50 | 4.64 | 0.205666E+09 | 347.84 | 4.50 | 2.83 | ||
Maximum of Months | 0.544333E+10 | 15838.39 | 32.70 | 13.84 | 0.288048E+09 | 347.92 | 32.00 | 14.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 1382208.84 | 4893.58 | 26-DEC-07:03 | 6.83 |
Annual Sum or Average | 1382208.84 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 1382208.84 | 4893.58 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217335E+10 | 12531.55 | 05-JAN-06:13 | -17.0 |
February | 0.235237E+10 | 13089.08 | 06-FEB-06:08 | -10.0 |
March | 0.154653E+10 | 10122.40 | 20-MAR-05:08 | 0.00 |
April | 0.103458E+10 | 11702.94 | 17-APR-05:07 | -8.0 |
May | 0.382722E+09 | 4205.90 | 01-MAY-06:03 | 6.33 |
June | 0.108349E+09 | 4106.57 | 26-JUN-05:12 | 17.53 |
July | 85945716.83 | 4431.63 | 04-JUL-07:03 | 16.17 |
August | 0.111656E+09 | 3820.20 | 13-AUG-07:53 | 15.00 |
September | 0.297859E+09 | 3499.55 | 05-SEP-05:12 | 14.20 |
October | 0.140237E+10 | 11283.52 | 30-OCT-05:06 | -10.0 |
November | 0.177679E+10 | 12526.68 | 30-NOV-06:13 | -12.0 |
December | 0.352083E+10 | 13908.56 | 23-DEC-06:08 | -22.1 |
Annual Sum or Average | 0.147933E+11 | |||
Minimum of Months | 85945716.83 | 3499.55 | -22.1 | |
Maximum of Months | 0.352083E+10 | 13908.56 | 17.53 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132937E+10 | 6821.62 | 15-JAN-13:13 | 3.33 |
February | 0.131983E+10 | 6383.94 | 06-FEB-07:19 | -9.3 |
March | 0.845389E+09 | 5794.59 | 12-MAR-10:02 | 15.17 |
April | 0.653197E+09 | 3511.98 | 03-APR-06:12 | -7.3 |
May | 0.136668E+09 | 3181.51 | 28-MAY-08:53 | 12.00 |
June | 25276108.48 | 4221.21 | 25-JUN-15:41 | 32.88 |
July | 34615207.63 | 3610.20 | 04-JUL-14:02 | 27.83 |
August | 21282513.42 | 3660.03 | 20-AUG-15:02 | 28.00 |
September | 57905443.06 | 5047.97 | 24-SEP-14:43 | 22.20 |
October | 0.505572E+09 | 6130.37 | 15-OCT-14:52 | 15.00 |
November | 0.107121E+10 | 7198.42 | 05-NOV-14:52 | 21.00 |
December | 0.159715E+10 | 7028.78 | 26-DEC-07:13 | 6.67 |
Annual Sum or Average | 0.759747E+10 | |||
Minimum of Months | 21282513.42 | 3181.51 | -9.3 | |
Maximum of Months | 0.159715E+10 | 7198.42 | 32.88 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.634460E+09 | 2937.91 | 22-JAN-15:13 | 8.33 |
February | 0.651309E+09 | 3059.13 | 26-FEB-13:23 | 17.50 |
March | 0.427561E+09 | 3329.60 | 12-MAR-16:32 | 18.00 |
April | 0.325967E+09 | 2085.97 | 26-APR-07:06 | 5.67 |
May | 51125632.60 | 1714.67 | 01-MAY-07:06 | 8.33 |
June | 14656445.68 | 1991.11 | 11-JUN-15:41 | 28.88 |
July | 19710585.01 | 2293.95 | 04-JUL-14:51 | 27.00 |
August | 16703462.10 | 2515.43 | 20-AUG-15:02 | 28.00 |
September | 29180810.32 | 3259.06 | 17-SEP-14:42 | 26.60 |
October | 0.244790E+09 | 3978.83 | 23-OCT-05:01 | -4.0 |
November | 0.469149E+09 | 3615.56 | 05-NOV-12:32 | 20.67 |
December | 0.823094E+09 | 3872.85 | 17-DEC-12:21 | 17.00 |
Annual Sum or Average | 0.370771E+10 | |||
Minimum of Months | 14656445.68 | 1714.67 | -4.0 | |
Maximum of Months | 0.823094E+09 | 3978.83 | 28.88 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15621522.79 | 10819.43 | 06-JAN-07:01 | -7.0 |
February | 0.109433E+09 | 12299.17 | 06-FEB-06:01 | -10.0 |
March | 19650871.29 | 11375.81 | 20-MAR-05:01 | 0.00 |
April | 5639133.26 | 10550.56 | 17-APR-06:01 | -7.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 2139162.80 | 10379.67 | 31-OCT-06:01 | -9.0 |
November | 4546773.16 | 10569.86 | 01-NOV-06:01 | -2.8 |
December | 0.134704E+09 | 12608.95 | 26-DEC-06:11 | 7.00 |
Annual Sum or Average | 0.291735E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.134704E+09 | 12608.95 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.560361E+09 | 19135.07 | 02-JAN-06:01 | -2.8 |
February | 0.891627E+09 | 21658.75 | 06-FEB-05:01 | -10.0 |
March | 0.317628E+09 | 20465.82 | 20-MAR-04:11 | 0.67 |
April | 0.256009E+09 | 19424.26 | 03-APR-05:01 | -8.0 |
May | 2433230.77 | 16076.33 | 01-MAY-06:03 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.222292E+09 | 19137.79 | 30-OCT-05:01 | -10.0 |
November | 0.299523E+09 | 18863.51 | 30-NOV-06:01 | -12.0 |
December | 0.126925E+10 | 21402.34 | 26-DEC-06:11 | 7.00 |
Annual Sum or Average | 0.381912E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.126925E+10 | 21658.75 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152736E+10 | 8295.33 | 06-JAN-05:11 | -7.7 |
February | 0.175352E+10 | 8524.55 | 13-FEB-05:01 | -11.0 |
March | 0.797485E+09 | 8322.11 | 20-MAR-04:11 | 0.67 |
April | 0.423471E+09 | 8294.67 | 17-APR-04:11 | -8.0 |
May | 18307047.50 | 6803.40 | 01-MAY-05:12 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 5242842.40 | 6380.56 | 22-SEP-06:02 | -1.4 |
October | 0.641143E+09 | 8284.87 | 30-OCT-04:01 | -10.0 |
November | 0.106783E+10 | 8185.32 | 30-NOV-05:01 | -12.8 |
December | 0.273531E+10 | 8914.97 | 24-DEC-06:42 | -19.7 |
Annual Sum or Average | 0.896966E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 0.273531E+10 | 8914.97 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.734827E+09 | 7252.10 | 06-JAN-05:11 | -7.7 |
February | 0.903689E+09 | 7487.09 | 13-FEB-05:01 | -11.0 |
March | 0.420159E+09 | 7274.19 | 20-MAR-04:11 | 0.67 |
April | 0.220657E+09 | 7220.58 | 17-APR-04:11 | -8.0 |
May | 4678865.20 | 5493.36 | 01-MAY-05:12 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 2017644.63 | 4990.01 | 22-SEP-06:02 | -1.4 |
October | 0.411049E+09 | 7227.08 | 30-OCT-04:01 | -10.0 |
November | 0.557764E+09 | 7096.72 | 30-NOV-05:01 | -12.8 |
December | 0.147526E+10 | 7928.51 | 24-DEC-06:42 | -19.7 |
Annual Sum or Average | 0.473011E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 0.147526E+10 | 7928.51 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.769788E+09 | 9719.60 | 05-JAN-05:01 | -17.0 |
February | 0.111605E+10 | 9879.19 | 13-FEB-05:01 | -11.0 |
March | 0.624064E+09 | 9789.53 | 20-MAR-04:11 | 0.67 |
April | 0.390774E+09 | 9753.28 | 17-APR-04:11 | -8.0 |
May | 20285732.14 | 7721.58 | 01-MAY-05:12 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 4267111.01 | 7139.89 | 22-SEP-06:02 | -1.4 |
October | 0.584335E+09 | 9702.42 | 30-OCT-04:01 | -10.0 |
November | 0.623740E+09 | 9575.86 | 30-NOV-05:01 | -12.8 |
December | 0.156505E+10 | 10460.00 | 24-DEC-06:42 | -19.7 |
Annual Sum or Average | 0.569835E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 0.156505E+10 | 10460.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.819324E+09 | 7687.77 | 05-JAN-05:01 | -17.0 |
February | 0.984831E+09 | 7933.94 | 13-FEB-05:01 | -11.0 |
March | 0.477290E+09 | 7732.56 | 20-MAR-04:11 | 0.67 |
April | 0.274616E+09 | 7710.43 | 17-APR-04:11 | -8.0 |
May | 13157420.93 | 5732.51 | 01-MAY-05:12 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 4125274.54 | 5161.61 | 22-SEP-06:02 | -1.4 |
October | 0.414027E+09 | 7674.37 | 30-OCT-04:01 | -10.0 |
November | 0.604058E+09 | 7520.78 | 30-NOV-05:01 | -12.8 |
December | 0.155652E+10 | 8431.85 | 24-DEC-06:42 | -19.7 |
Annual Sum or Average | 0.514795E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 0.155652E+10 | 8431.85 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.978478E+09 | 5747.75 | 05-JAN-05:01 | -17.0 |
February | 0.121622E+10 | 6212.59 | 06-FEB-05:01 | -10.0 |
March | 0.474410E+09 | 5673.59 | 20-MAR-05:01 | 0.00 |
April | 0.185197E+09 | 5656.76 | 03-APR-05:01 | -8.0 |
May | 3182306.24 | 4890.21 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.129498E+09 | 5384.39 | 31-OCT-05:01 | -8.2 |
November | 0.260653E+09 | 5573.31 | 30-NOV-06:01 | -12.0 |
December | 0.125712E+10 | 6108.26 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.450476E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.125712E+10 | 6212.59 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.327453E+09 | 4841.38 | 06-JAN-06:01 | -7.0 |
February | 0.526400E+09 | 5609.08 | 06-FEB-05:01 | -10.0 |
March | 0.200945E+09 | 4929.14 | 20-MAR-05:01 | 0.00 |
April | 81187181.02 | 4885.94 | 03-APR-05:01 | -8.0 |
May | 344308.04 | 1793.31 | 01-MAY-06:03 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 80589621.17 | 4576.81 | 31-OCT-05:01 | -8.2 |
November | 0.120466E+09 | 4804.32 | 30-NOV-06:01 | -12.0 |
December | 0.552810E+09 | 5433.05 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.189020E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.552810E+09 | 5609.08 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146277E+10 | 9161.78 | 05-JAN-07:10 | -17.0 |
February | 0.181697E+10 | 8912.08 | 06-FEB-07:50 | -8.3 |
March | 0.153786E+10 | 7958.97 | 29-MAR-06:10 | -7.7 |
April | 0.107699E+10 | 8247.31 | 03-APR-06:10 | -7.7 |
May | 0.381466E+09 | 7021.10 | 02-MAY-06:10 | 0.17 |
June | 7872162.53 | 5417.05 | 09-JUN-06:06 | 9.37 |
July | 1108090.47 | 2195.40 | 03-JUL-06:07 | 11.00 |
August | 530258.03 | 2716.13 | 23-AUG-06:08 | 12.50 |
September | 59218364.39 | 6585.80 | 22-SEP-06:10 | -1.4 |
October | 0.108354E+10 | 8279.32 | 31-OCT-06:10 | -9.0 |
November | 0.115592E+10 | 8369.68 | 30-NOV-07:10 | -11.3 |
December | 0.198319E+10 | 9494.19 | 22-DEC-07:10 | -20.0 |
Annual Sum or Average | 0.105674E+11 | |||
Minimum of Months | 530258.03 | 2195.40 | -20.0 | |
Maximum of Months | 0.198319E+10 | 9494.19 | 12.50 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.346452E+09 | 4998.67 | 05-JAN-06:01 | -17.0 |
February | 0.518436E+09 | 5835.92 | 06-FEB-05:01 | -10.0 |
March | 0.207734E+09 | 5099.86 | 20-MAR-05:01 | 0.00 |
April | 98928098.93 | 5054.58 | 17-APR-05:01 | -8.0 |
May | 1437561.32 | 3951.59 | 01-MAY-06:03 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 83433600.62 | 4714.79 | 31-OCT-05:01 | -8.2 |
November | 0.111149E+09 | 4884.49 | 30-NOV-06:01 | -12.0 |
December | 0.584688E+09 | 5595.64 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.195226E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.584688E+09 | 5835.92 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.596116E+09 | 6243.60 | 05-JAN-05:01 | -17.0 |
February | 0.766961E+09 | 6863.85 | 06-FEB-05:01 | -10.0 |
March | 0.221666E+09 | 6087.03 | 20-MAR-05:01 | 0.00 |
April | 0.130802E+09 | 6126.68 | 03-APR-05:01 | -8.0 |
May | 916847.58 | 3968.50 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.221226E+09 | 6092.86 | 30-OCT-05:01 | -10.0 |
November | 0.332006E+09 | 6166.34 | 30-NOV-05:01 | -12.8 |
December | 0.127067E+10 | 6840.11 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.354037E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.127067E+10 | 6863.85 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279532E+09 | 5617.30 | 05-JAN-05:01 | -17.0 |
February | 0.402387E+09 | 6411.06 | 06-FEB-05:01 | -10.0 |
March | 0.127176E+09 | 5352.59 | 20-MAR-05:01 | 0.00 |
April | 70760356.39 | 5475.92 | 03-APR-05:01 | -8.0 |
May | 188790.79 | 1258.61 | 01-MAY-06:03 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.155274E+09 | 5405.25 | 30-OCT-05:01 | -10.0 |
November | 0.187859E+09 | 5510.01 | 30-NOV-05:01 | -12.8 |
December | 0.660994E+09 | 6420.58 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.188417E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.660994E+09 | 6420.58 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250616E+09 | 7267.77 | 05-JAN-05:01 | -17.0 |
February | 0.486934E+09 | 8203.99 | 06-FEB-05:01 | -10.0 |
March | 0.174047E+09 | 7105.45 | 20-MAR-05:01 | 0.00 |
April | 0.124371E+09 | 7162.74 | 03-APR-05:01 | -8.0 |
May | 1143458.37 | 4967.45 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.203903E+09 | 7064.78 | 31-OCT-05:01 | -8.2 |
November | 0.180892E+09 | 7155.75 | 01-NOV-05:01 | -3.0 |
December | 0.645387E+09 | 7991.19 | 21-DEC-05:01 | -18.2 |
Annual Sum or Average | 0.206729E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.2 | |
Maximum of Months | 0.645387E+09 | 8203.99 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302430E+09 | 5707.80 | 05-JAN-05:01 | -17.0 |
February | 0.420090E+09 | 6596.66 | 06-FEB-05:01 | -10.0 |
March | 0.131240E+09 | 5455.47 | 20-MAR-05:01 | 0.00 |
April | 89320733.59 | 5579.98 | 03-APR-05:01 | -8.0 |
May | 710179.52 | 3193.41 | 01-MAY-06:03 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 389.53 | 3.90 | 22-SEP-06:02 | -1.4 |
October | 0.148870E+09 | 5504.23 | 30-OCT-05:01 | -10.0 |
November | 0.183570E+09 | 5575.48 | 01-NOV-05:01 | -3.0 |
December | 0.688572E+09 | 6517.43 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.196480E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.688572E+09 | 6596.66 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.159593E+11 | 11206.55 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.144673E+11 | 11206.55 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.165050E+11 | 11206.55 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.154860E+11 | 11206.55 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.162322E+11 | 11206.55 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.159146E+11 | 11206.55 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.158014E+11 | 11206.55 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.165050E+11 | 11206.55 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.154816E+11 | 11206.55 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.159615E+11 | 11206.55 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.155311E+11 | 11206.55 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.157992E+11 | 11206.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.189644E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.144673E+11 | 11206.55 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.165050E+11 | 11206.55 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.456004E+09 | 735.45 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.387341E+09 | 688.55 | 06-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.428798E+09 | 549.73 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370263E+09 | 479.82 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.387702E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.380730E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.359596E+09 | 350.81 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.407726E+09 | 386.61 | 28-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.374987E+09 | 390.43 | 21-SEP-15:00 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.414109E+09 | 627.00 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.445704E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.447060E+09 | 735.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.486002E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.359596E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.456004E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.285036E+09 | 465.60 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.243682E+09 | 435.99 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.271106E+09 | 333.12 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234971E+09 | 258.84 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.247059E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.242835E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.229292E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.259487E+09 | 247.43 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.237598E+09 | 250.26 | 21-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.260268E+09 | 390.31 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.280142E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.280219E+09 | 465.60 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.307170E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.229292E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.285036E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.433663E+09 | 735.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.377588E+09 | 687.48 | 06-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.425971E+09 | 543.64 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.371125E+09 | 475.87 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.389570E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.383397E+09 | 350.81 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.362049E+09 | 350.81 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.409382E+09 | 384.05 | 28-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.374235E+09 | 383.76 | 21-SEP-15:00 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.408013E+09 | 621.20 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.429276E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.430492E+09 | 735.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.479476E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.362049E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.433663E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.277749E+09 | 465.57 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.239825E+09 | 434.19 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269243E+09 | 352.29 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.233729E+09 | 314.25 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.245237E+09 | 222.08 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241087E+09 | 238.44 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227784E+09 | 236.19 | 28-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256999E+09 | 244.03 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.236548E+09 | 253.02 | 22-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.259324E+09 | 397.50 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.273694E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.274452E+09 | 465.57 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.303567E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227784E+09 | 222.08 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.277749E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.454448E+09 | 735.45 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.386020E+09 | 686.78 | 06-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.428156E+09 | 542.64 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.369949E+09 | 414.04 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.387444E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.380509E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.359326E+09 | 350.81 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.407831E+09 | 383.47 | 28-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.374533E+09 | 387.48 | 21-SEP-15:00 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.412998E+09 | 622.89 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.444405E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.445824E+09 | 735.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.485144E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.359326E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.454448E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.284377E+09 | 465.60 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.243146E+09 | 435.08 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.270658E+09 | 328.85 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234800E+09 | 257.55 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.246891E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.242687E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.229159E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.259270E+09 | 245.73 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.237345E+09 | 248.70 | 21-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.259856E+09 | 387.90 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.279381E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.279470E+09 | 465.60 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.306704E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.229159E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.284377E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.433297E+09 | 735.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.377082E+09 | 685.65 | 06-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.425664E+09 | 536.26 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.370781E+09 | 413.44 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.389264E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.383086E+09 | 350.81 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.361775E+09 | 350.81 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.409034E+09 | 380.76 | 28-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.373926E+09 | 380.42 | 21-SEP-15:00 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.407521E+09 | 616.79 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.428504E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.428961E+09 | 735.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.478889E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.361775E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.433297E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.277276E+09 | 465.57 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.239419E+09 | 433.21 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.268958E+09 | 348.83 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.233563E+09 | 309.64 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.245097E+09 | 222.08 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240981E+09 | 236.39 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227649E+09 | 222.08 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256855E+09 | 242.51 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.236330E+09 | 251.71 | 22-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.258846E+09 | 395.42 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.272403E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.274070E+09 | 465.57 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.303145E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227649E+09 | 222.08 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.277276E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.456003E+09 | 735.45 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.387340E+09 | 688.55 | 06-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.428797E+09 | 549.71 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370263E+09 | 479.80 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.387701E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.380730E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.359596E+09 | 350.81 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.407726E+09 | 386.60 | 28-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.374987E+09 | 390.42 | 21-SEP-15:00 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.414108E+09 | 626.99 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.445702E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.447060E+09 | 735.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.486001E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.359596E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.456003E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.285036E+09 | 465.60 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.243682E+09 | 435.98 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.271106E+09 | 333.11 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234971E+09 | 258.83 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.247059E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.242835E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.229292E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.259487E+09 | 247.42 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.237598E+09 | 250.26 | 21-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.260267E+09 | 390.30 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.280141E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.280218E+09 | 465.60 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.307169E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.229292E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.285036E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.433663E+09 | 735.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.377588E+09 | 687.48 | 06-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.425971E+09 | 543.62 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.371125E+09 | 475.85 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.389569E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.383397E+09 | 350.81 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.362048E+09 | 350.81 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.409381E+09 | 384.04 | 28-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.374235E+09 | 383.75 | 21-SEP-15:00 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.408012E+09 | 621.19 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.429275E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.430492E+09 | 735.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.479476E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.362048E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.433663E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.277748E+09 | 465.57 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.239824E+09 | 434.19 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269243E+09 | 352.28 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.233729E+09 | 314.23 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.245236E+09 | 222.08 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241087E+09 | 238.43 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227784E+09 | 236.19 | 28-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256999E+09 | 244.03 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.236548E+09 | 253.02 | 22-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.259323E+09 | 397.49 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.273693E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.274452E+09 | 465.57 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.303567E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227784E+09 | 222.08 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.277748E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.159593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.144673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.165050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.154860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.162322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.159146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.158014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.165050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.154816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.159615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.155311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.157992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.189644E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.144673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.165050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.456004E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245118E+09 |
February | 0.901968E+09 | 0.387341E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393373E+09 |
March | 0.107774E+10 | 0.428798E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427394E+09 |
April | 0.956342E+09 | 0.370263E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459233E+09 |
May | 0.103597E+10 | 0.387702E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 992557.98 | 0.246488E+09 |
June | 0.103308E+10 | 0.380730E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20796040.77 | 0.107100E+09 |
July | 0.959235E+09 | 0.359596E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26264454.81 | 0.106561E+09 |
August | 0.107774E+10 | 0.407726E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14220490.54 | 0.105411E+09 |
September | 0.956342E+09 | 0.374987E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7655400.54 | 0.154952E+09 |
October | 0.994195E+09 | 0.414109E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 139095.33 | 0.330055E+09 |
November | 0.984487E+09 | 0.445704E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281947E+09 |
December | 0.959235E+09 | 0.447060E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525817E+09 |
Annual Sum or Average | 0.119305E+11 | 0.486002E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70068039.96 | 0.338345E+10 |
Minimum of Months | 0.901968E+09 | 0.359596E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105411E+09 |
Maximum of Months | 0.107774E+10 | 0.456004E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26264454.81 | 0.525817E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.285036E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168254E+09 |
February | 0.571020E+09 | 0.243682E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268993E+09 |
March | 0.682301E+09 | 0.271106E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293025E+09 |
April | 0.605444E+09 | 0.234971E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313418E+09 |
May | 0.655854E+09 | 0.247059E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 661379.62 | 0.167733E+09 |
June | 0.654023E+09 | 0.242835E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13608446.18 | 72843653.18 |
July | 0.607275E+09 | 0.229292E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17101946.54 | 73741055.73 |
August | 0.682301E+09 | 0.259487E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9203105.03 | 72580707.46 |
September | 0.605444E+09 | 0.237598E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4735311.03 | 0.107481E+09 |
October | 0.629407E+09 | 0.260268E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92729.14 | 0.227191E+09 |
November | 0.623262E+09 | 0.280142E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192067E+09 |
December | 0.607275E+09 | 0.280219E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356549E+09 |
Annual Sum or Average | 0.755301E+10 | 0.307170E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45402917.54 | 0.231388E+10 |
Minimum of Months | 0.571020E+09 | 0.229292E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72580707.46 |
Maximum of Months | 0.682301E+09 | 0.285036E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17101946.54 | 0.356549E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.433663E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269060E+09 |
February | 0.901968E+09 | 0.377588E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417976E+09 |
March | 0.107774E+10 | 0.425971E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448718E+09 |
April | 0.956342E+09 | 0.371125E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469795E+09 |
May | 0.103597E+10 | 0.389570E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 991955.56 | 0.249872E+09 |
June | 0.103308E+10 | 0.383397E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20636862.18 | 0.106841E+09 |
July | 0.959235E+09 | 0.362049E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26015741.83 | 0.107135E+09 |
August | 0.107774E+10 | 0.409382E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13777764.37 | 0.109295E+09 |
September | 0.956342E+09 | 0.374235E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6815098.10 | 0.163818E+09 |
October | 0.994195E+09 | 0.408013E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112039.06 | 0.349589E+09 |
November | 0.984487E+09 | 0.429276E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302864E+09 |
December | 0.959235E+09 | 0.430492E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560255E+09 |
Annual Sum or Average | 0.119305E+11 | 0.479476E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68349461.10 | 0.355522E+10 |
Minimum of Months | 0.901968E+09 | 0.362049E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106841E+09 |
Maximum of Months | 0.107774E+10 | 0.433663E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26015741.83 | 0.560255E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.277749E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168750E+09 |
February | 0.570983E+09 | 0.239825E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269395E+09 |
March | 0.682256E+09 | 0.269243E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293100E+09 |
April | 0.605404E+09 | 0.233729E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311942E+09 |
May | 0.655811E+09 | 0.245237E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 661116.31 | 0.169583E+09 |
June | 0.653980E+09 | 0.241087E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13545139.07 | 74524870.70 |
July | 0.607235E+09 | 0.227784E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16929019.71 | 73552194.98 |
August | 0.682256E+09 | 0.256999E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9296712.69 | 74330801.97 |
September | 0.605404E+09 | 0.236548E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4658799.46 | 0.108511E+09 |
October | 0.629366E+09 | 0.259324E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92739.28 | 0.226087E+09 |
November | 0.623221E+09 | 0.273694E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192997E+09 |
December | 0.607235E+09 | 0.274452E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357360E+09 |
Annual Sum or Average | 0.755252E+10 | 0.303567E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45183526.51 | 0.232013E+10 |
Minimum of Months | 0.570983E+09 | 0.227784E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73552194.98 |
Maximum of Months | 0.682256E+09 | 0.277749E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16929019.71 | 0.357360E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.454448E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135378E+09 |
February | 0.901968E+09 | 0.386020E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213208E+09 |
March | 0.107774E+10 | 0.428156E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.87 | 0.231194E+09 |
April | 0.956342E+09 | 0.369949E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249203E+09 |
May | 0.103597E+10 | 0.387444E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 547181.14 | 0.128565E+09 |
June | 0.103308E+10 | 0.380509E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12080017.39 | 54902440.14 |
July | 0.959235E+09 | 0.359326E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15785888.20 | 54391375.54 |
August | 0.107774E+10 | 0.407831E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8141458.78 | 55520381.45 |
September | 0.956342E+09 | 0.374533E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4401832.18 | 85993593.37 |
October | 0.994195E+09 | 0.412998E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76838.95 | 0.187918E+09 |
November | 0.984487E+09 | 0.444405E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159440E+09 |
December | 0.959235E+09 | 0.445824E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 533.56 | 0.293298E+09 |
Annual Sum or Average | 0.119305E+11 | 0.485144E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41033790.07 | 0.184901E+10 |
Minimum of Months | 0.901968E+09 | 0.359326E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54391375.54 |
Maximum of Months | 0.107774E+10 | 0.454448E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15785888.20 | 0.293298E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.284377E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94419882.22 |
February | 0.571020E+09 | 0.243146E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148608E+09 |
March | 0.682301E+09 | 0.270658E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 | 0.162166E+09 |
April | 0.605444E+09 | 0.234800E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174846E+09 |
May | 0.655854E+09 | 0.246891E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 361305.76 | 90395090.20 |
June | 0.654023E+09 | 0.242687E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7476611.80 | 39339837.69 |
July | 0.607275E+09 | 0.229159E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9408064.88 | 39873524.28 |
August | 0.682301E+09 | 0.259270E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4972358.21 | 40453810.54 |
September | 0.605444E+09 | 0.237345E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2569302.38 | 61799493.45 |
October | 0.629407E+09 | 0.259856E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51223.95 | 0.131464E+09 |
November | 0.623262E+09 | 0.279381E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110306E+09 |
December | 0.607275E+09 | 0.279470E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201678E+09 |
Annual Sum or Average | 0.755301E+10 | 0.306704E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24838868.09 | 0.129535E+10 |
Minimum of Months | 0.571020E+09 | 0.229159E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39339837.69 |
Maximum of Months | 0.682301E+09 | 0.284377E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9408064.88 | 0.201678E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.433297E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425714E+10 |
February | 0.901968E+09 | 0.377082E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421212E+10 |
March | 0.107774E+10 | 0.425664E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367242E+10 |
April | 0.956342E+09 | 0.370781E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279482E+10 |
May | 0.103597E+10 | 0.389264E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53529573.73 | 0.179046E+10 |
June | 0.103308E+10 | 0.383086E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729628E+09 | 0.451033E+09 |
July | 0.959235E+09 | 0.361775E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589638E+09 | 0.426252E+09 |
August | 0.107774E+10 | 0.409034E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640061E+09 | 0.623498E+09 |
September | 0.956342E+09 | 0.373926E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271088E+09 | 0.976006E+09 |
October | 0.994195E+09 | 0.407521E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3821290.47 | 0.330704E+10 |
November | 0.984487E+09 | 0.428504E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407187E+10 |
December | 0.959235E+09 | 0.428961E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474774E+10 |
Annual Sum or Average | 0.119305E+11 | 0.478889E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228777E+10 | 0.313304E+11 |
Minimum of Months | 0.901968E+09 | 0.361775E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426252E+09 |
Maximum of Months | 0.107774E+10 | 0.433297E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729628E+09 | 0.474774E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.277276E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94744846.25 |
February | 0.570983E+09 | 0.239419E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148817E+09 |
March | 0.682256E+09 | 0.268958E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 | 0.161748E+09 |
April | 0.605404E+09 | 0.233563E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173685E+09 |
May | 0.655811E+09 | 0.245097E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 360038.67 | 91084051.18 |
June | 0.653980E+09 | 0.240981E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7469450.73 | 40522888.88 |
July | 0.607235E+09 | 0.227649E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9391489.57 | 39499235.87 |
August | 0.682256E+09 | 0.256855E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5082263.51 | 41437000.26 |
September | 0.605404E+09 | 0.236330E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2534422.29 | 62506201.33 |
October | 0.629366E+09 | 0.258846E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51229.05 | 0.131412E+09 |
November | 0.623221E+09 | 0.272403E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110880E+09 |
December | 0.607235E+09 | 0.274070E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202017E+09 |
Annual Sum or Average | 0.755252E+10 | 0.303145E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24888895.21 | 0.129835E+10 |
Minimum of Months | 0.570983E+09 | 0.227649E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39499235.87 |
Maximum of Months | 0.682256E+09 | 0.277276E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9391489.57 | 0.202017E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.456003E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217212E+09 |
February | 0.901968E+09 | 0.387340E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342361E+09 |
March | 0.107774E+10 | 0.428797E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374131E+09 |
April | 0.956342E+09 | 0.370263E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403836E+09 |
May | 0.103597E+10 | 0.387701E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 836922.26 | 0.212268E+09 |
June | 0.103308E+10 | 0.380730E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17647385.63 | 91367518.88 |
July | 0.959235E+09 | 0.359596E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22574123.62 | 90845581.20 |
August | 0.107774E+10 | 0.407726E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12108398.93 | 90380119.86 |
September | 0.956342E+09 | 0.374987E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6524771.16 | 0.135036E+09 |
October | 0.994195E+09 | 0.414108E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118020.71 | 0.291568E+09 |
November | 0.984487E+09 | 0.445702E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248412E+09 |
December | 0.959235E+09 | 0.447060E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457907E+09 |
Annual Sum or Average | 0.119305E+11 | 0.486001E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59809622.31 | 0.295532E+10 |
Minimum of Months | 0.901968E+09 | 0.359596E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90380119.86 |
Maximum of Months | 0.107774E+10 | 0.456003E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22574123.62 | 0.457907E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.285036E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149083E+09 |
February | 0.421807E+09 | 0.243682E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234076E+09 |
March | 0.502994E+09 | 0.271106E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255965E+09 |
April | 0.447140E+09 | 0.234971E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275179E+09 |
May | 0.484071E+09 | 0.247059E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 522585.44 | 0.144385E+09 |
June | 0.482240E+09 | 0.242835E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11264980.88 | 62223303.66 |
July | 0.448971E+09 | 0.229292E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14277610.36 | 62892092.31 |
August | 0.502994E+09 | 0.259487E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7545914.96 | 62309362.49 |
September | 0.447140E+09 | 0.237598E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3886184.70 | 93314476.91 |
October | 0.465148E+09 | 0.260267E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68686.42 | 0.199826E+09 |
November | 0.460569E+09 | 0.280141E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169292E+09 |
December | 0.448971E+09 | 0.280218E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311035E+09 |
Annual Sum or Average | 0.557719E+10 | 0.307169E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37565962.77 | 0.201958E+10 |
Minimum of Months | 0.421807E+09 | 0.229292E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62223303.66 |
Maximum of Months | 0.502994E+09 | 0.285036E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14277610.36 | 0.311035E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.433663E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236543E+09 |
February | 0.901968E+09 | 0.377588E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363427E+09 |
March | 0.107774E+10 | 0.425971E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391617E+09 |
April | 0.956342E+09 | 0.371125E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412681E+09 |
May | 0.103597E+10 | 0.389569E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 835749.54 | 0.215030E+09 |
June | 0.103308E+10 | 0.383397E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17388064.90 | 91256339.46 |
July | 0.959235E+09 | 0.362048E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22132598.06 | 91509490.27 |
August | 0.107774E+10 | 0.409381E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11574494.23 | 93808346.35 |
September | 0.956342E+09 | 0.374235E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5718481.45 | 0.142222E+09 |
October | 0.994195E+09 | 0.408012E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73448.33 | 0.306857E+09 |
November | 0.984487E+09 | 0.429275E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265243E+09 |
December | 0.959235E+09 | 0.430492E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488803E+09 |
Annual Sum or Average | 0.119305E+11 | 0.479476E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57722836.52 | 0.309900E+10 |
Minimum of Months | 0.901968E+09 | 0.362048E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91256339.46 |
Maximum of Months | 0.107774E+10 | 0.433663E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22132598.06 | 0.488803E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.277748E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149157E+09 |
February | 0.570983E+09 | 0.239824E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234263E+09 |
March | 0.682256E+09 | 0.269243E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256104E+09 |
April | 0.605404E+09 | 0.233729E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274093E+09 |
May | 0.655811E+09 | 0.245236E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 556845.97 | 0.145927E+09 |
June | 0.653980E+09 | 0.241087E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11396730.62 | 63716085.81 |
July | 0.607235E+09 | 0.227784E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14287779.88 | 62875833.18 |
August | 0.682256E+09 | 0.256999E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7836309.07 | 63787477.60 |
September | 0.605404E+09 | 0.236548E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3910238.88 | 94376851.03 |
October | 0.629366E+09 | 0.259323E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78683.51 | 0.199138E+09 |
November | 0.623221E+09 | 0.273693E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169694E+09 |
December | 0.607235E+09 | 0.274452E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311209E+09 |
Annual Sum or Average | 0.755252E+10 | 0.303567E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38066587.92 | 0.202434E+10 |
Minimum of Months | 0.570983E+09 | 0.227784E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62875833.18 |
Maximum of Months | 0.682256E+09 | 0.277748E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14287779.88 | 0.311209E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305411E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477361E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521918E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558394E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 785924.21 | 0.284727E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20700935.98 | 0.120660E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27788015.41 | 0.119686E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13227014.00 | 0.121605E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6820923.64 | 0.187294E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56475.19 | 0.409604E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349321E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642549E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69379288.43 | 0.409853E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119686E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27788015.41 | 0.642549E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378921E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597279E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654576E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700386E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1016573.33 | 0.363954E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26289800.06 | 0.156388E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35159662.08 | 0.155437E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17048064.23 | 0.156069E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9064745.23 | 0.236766E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83062.85 | 0.510119E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432763E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795947E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88661907.78 | 0.513860E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155437E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35159662.08 | 0.795947E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380308E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607404E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666138E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712342E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666334.49 | 0.382751E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22606495.86 | 0.160086E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28277244.13 | 0.160498E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14394425.92 | 0.160638E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6565473.50 | 0.238578E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25331.99 | 0.513512E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435665E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802058E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72535305.90 | 0.521998E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160086E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28277244.13 | 0.802058E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 11206.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 11206.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 11206.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 11206.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 11206.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 11206.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 11206.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 11206.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 11206.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 11206.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 11206.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 11206.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 11206.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 11206.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 471.38 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 688.55 | 06-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 603.85 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 549.73 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1285.25 | 19-MAR-07:07 |
April | 1306.65 | 03-APR-09:09 | 479.82 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 847.17 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.44 | 17-MAY-14:50 | 494.96 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.64 | 25-JUN-17:55 | 307.17 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.23 | 16-JUL-12:00 | 302.35 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 386.61 | 28-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.14 | 02-AUG-16:00 | 398.93 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 390.43 | 21-SEP-15:00 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.83 | 10-SEP-15:00 | 326.68 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 627.00 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 | 11-OCT-14:00 | 721.53 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 719.71 | 01-NOV-04:10 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1086.87 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.35 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 218.23 | 1285.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 315.12 | 13-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 435.99 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 408.42 | 23-FEB-24:00 |
March | 827.22 | 01-MAR-10:09 | 333.12 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 856.87 | 19-MAR-07:07 |
April | 827.22 | 03-APR-09:09 | 258.84 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 563.75 | 15-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 | 17-MAY-14:50 | 330.62 | 03-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.95 | 25-JUN-17:55 | 205.16 | 08-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.48 | 16-JUL-12:00 | 213.58 | 02-JUL-08:50 |
August | 827.22 | 01-AUG-09:09 | 247.43 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 02-AUG-16:00 | 272.76 | 27-AUG-18:00 |
September | 827.22 | 01-SEP-09:09 | 250.26 | 21-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.49 | 10-SEP-14:45 | 218.00 | 21-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 390.31 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 | 11-OCT-14:00 | 483.89 | 29-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 482.85 | 01-NOV-04:04 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 721.42 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.16 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 145.48 | 856.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 489.46 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 687.48 | 06-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 637.66 | 19-FEB-17:00 |
March | 1306.65 | 01-MAR-10:09 | 543.64 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1284.68 | 19-MAR-07:07 |
April | 1306.65 | 03-APR-09:09 | 475.87 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 851.41 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.44 | 17-MAY-14:50 | 500.42 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.56 | 25-JUN-17:55 | 306.25 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.22 | 16-JUL-12:00 | 303.11 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 384.05 | 28-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.14 | 02-AUG-16:00 | 429.01 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 383.76 | 21-SEP-15:00 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.62 | 10-SEP-15:00 | 329.12 | 21-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 621.20 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 | 11-OCT-14:00 | 738.65 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 719.72 | 01-NOV-04:10 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1104.54 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.11 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 218.22 | 1284.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 317.30 | 13-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 434.19 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 414.03 | 23-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 352.29 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 856.78 | 19-MAR-07:07 |
April | 827.17 | 03-APR-09:09 | 314.25 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 562.06 | 15-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 222.08 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 | 17-MAY-14:50 | 336.42 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 238.44 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.10 | 25-JUN-17:53 | 215.81 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 236.19 | 28-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.48 | 16-JUL-12:00 | 208.10 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 244.03 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 02-AUG-16:00 | 289.34 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 253.02 | 22-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.41 | 10-SEP-15:00 | 216.73 | 21-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 397.50 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 | 11-OCT-14:00 | 480.56 | 29-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 484.92 | 01-NOV-04:04 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 726.75 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.10 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 145.48 | 856.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 269.88 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 686.78 | 06-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 325.06 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 542.64 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 | 14-MAR-13:00 | 725.19 | 19-MAR-06:53 |
April | 1306.65 | 03-APR-09:09 | 414.04 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 482.19 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.20 | 17-MAY-14:50 | 272.31 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.97 | 25-JUN-18:00 | 163.50 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.49 | 16-JUL-12:00 | 157.75 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 383.47 | 28-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.71 | 06-AUG-12:00 | 194.19 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 387.48 | 21-SEP-15:00 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.72 | 10-SEP-15:00 | 189.88 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 622.89 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 11-OCT-14:00 | 430.28 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 408.96 | 01-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | 02-DEC-15:00 | 603.23 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.75 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 121.49 | 725.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 185.30 | 13-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 435.08 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 229.21 | 23-FEB-24:00 |
March | 827.22 | 01-MAR-10:09 | 328.85 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 483.23 | 19-MAR-06:53 |
April | 827.22 | 03-APR-09:09 | 257.55 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 327.87 | 15-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.80 | 17-MAY-14:50 | 186.50 | 03-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.39 | 25-JUN-18:00 | 114.28 | 08-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.78 | 16-JUL-12:00 | 112.26 | 03-JUL-03:00 |
August | 827.22 | 01-AUG-09:09 | 245.73 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.55 | 02-AUG-16:00 | 140.73 | 27-AUG-18:00 |
September | 827.22 | 01-SEP-09:09 | 248.70 | 21-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.40 | 10-SEP-14:34 | 128.09 | 22-SEP-02:00 |
October | 827.22 | 02-OCT-09:09 | 387.90 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.07 | 11-OCT-14:00 | 294.69 | 29-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 271.53 | 01-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 400.84 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.26 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 77.78 | 483.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 27147.75 | 05-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 685.65 | 06-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 21394.32 | 02-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 536.26 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 20628.97 | 02-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 413.44 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 19967.42 | 17-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2542.69 | 31-MAY-16:10 | 13796.48 | 02-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8997.44 | 26-JUN-16:03 | 8649.28 | 09-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6905.42 | 17-JUL-11:03 | 8280.27 | 03-JUL-06:01 |
August | 1306.65 | 01-AUG-09:09 | 380.76 | 28-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7847.12 | 16-AUG-16:03 | 7480.71 | 17-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 380.42 | 21-SEP-15:00 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4219.64 | 12-SEP-16:05 | 15934.73 | 21-SEP-16:01 |
October | 1306.65 | 02-OCT-09:09 | 616.79 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 662.74 | 10-OCT-17:00 | 21776.96 | 30-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 23417.69 | 29-NOV-17:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 31364.21 | 21-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7480.71 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8997.44 | 31364.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 186.33 | 13-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 433.21 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 229.65 | 23-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 348.83 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 482.07 | 19-MAR-06:53 |
April | 827.17 | 03-APR-09:09 | 309.64 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 322.76 | 15-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 222.08 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.80 | 17-MAY-14:50 | 190.60 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 236.39 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.82 | 25-JUN-17:53 | 119.71 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 222.08 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.20 | 16-JUL-12:00 | 116.18 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 242.51 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.54 | 02-AUG-16:00 | 153.57 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 251.71 | 22-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 | 10-SEP-15:00 | 126.97 | 22-SEP-02:00 |
October | 827.17 | 02-OCT-09:09 | 395.42 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.07 | 11-OCT-14:00 | 291.06 | 29-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 271.09 | 01-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 403.76 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.18 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 80.20 | 482.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 430.31 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 688.55 | 06-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 530.94 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 549.71 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1112.42 | 19-MAR-06:53 |
April | 1306.65 | 03-APR-09:09 | 479.80 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 758.34 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 17-MAY-14:50 | 440.60 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.98 | 25-JUN-17:43 | 262.23 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.16 | 16-JUL-12:00 | 257.69 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 386.60 | 28-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.45 | 02-AUG-16:00 | 326.55 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 390.42 | 21-SEP-15:00 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.56 | 10-SEP-15:00 | 289.42 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 626.99 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.47 | 11-OCT-14:00 | 655.06 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 613.36 | 01-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 935.32 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.69 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 182.16 | 1112.42 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 465.60 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 287.85 | 13-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 435.98 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 358.91 | 23-FEB-24:00 |
March | 805.43 | 01-MAR-08:09 | 333.11 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 738.28 | 19-MAR-06:53 |
April | 805.43 | 03-APR-07:10 | 258.83 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 507.58 | 16-APR-15:00 |
May | 805.43 | 01-MAY-07:10 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 17-MAY-14:50 | 294.06 | 03-MAY-03:00 |
June | 805.43 | 01-JUN-07:10 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.92 | 25-JUN-17:43 | 175.41 | 08-JUN-23:00 |
July | 805.43 | 03-JUL-07:10 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.44 | 16-JUL-12:00 | 173.92 | 02-JUL-08:30 |
August | 805.43 | 01-AUG-07:10 | 247.42 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 02-AUG-16:00 | 224.31 | 27-AUG-18:00 |
September | 805.43 | 01-SEP-07:10 | 250.26 | 21-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.55 | 10-SEP-14:34 | 192.84 | 22-SEP-02:00 |
October | 805.43 | 02-OCT-07:10 | 390.30 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.19 | 11-OCT-14:10 | 438.95 | 29-OCT-09:00 |
November | 805.43 | 01-NOV-07:10 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 406.51 | 01-NOV-04:00 |
December | 805.43 | 01-DEC-08:09 | 465.60 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 619.25 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.92 | |||||
Maximum of Months | 805.43 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 121.44 | 738.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 445.82 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 687.48 | 06-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 558.04 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 543.62 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1115.52 | 19-MAR-06:53 |
April | 1306.65 | 03-APR-09:09 | 475.85 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 762.02 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 17-MAY-14:50 | 444.72 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.84 | 25-JUN-17:43 | 261.57 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.16 | 16-JUL-12:00 | 258.57 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 384.04 | 28-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.45 | 02-AUG-16:00 | 353.45 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 383.75 | 21-SEP-15:00 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.33 | 10-SEP-14:34 | 290.70 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 621.19 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 | 11-OCT-14:00 | 668.58 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 615.20 | 01-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 949.37 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.57 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 182.16 | 1115.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 289.37 | 13-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 434.19 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 363.42 | 23-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 352.28 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 736.65 | 19-MAR-06:53 |
April | 827.17 | 03-APR-09:09 | 314.23 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 503.23 | 15-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 222.08 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 17-MAY-14:50 | 298.82 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 238.43 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.00 | 25-JUN-17:43 | 184.05 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 236.19 | 28-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.44 | 16-JUL-12:00 | 177.76 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 244.03 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.96 | 02-AUG-16:00 | 238.15 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 253.02 | 22-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.53 | 10-SEP-15:00 | 191.74 | 22-SEP-02:00 |
October | 827.17 | 02-OCT-09:09 | 397.49 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.32 | 11-OCT-14:00 | 436.08 | 29-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 406.21 | 01-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 624.07 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.76 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 121.44 | 736.65 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 620.40 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 745.24 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1596.45 | 19-MAR-06:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1072.09 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.18 | 17-MAY-14:40 | 616.08 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.44 | 25-JUN-18:00 | 346.36 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.23 | 16-JUL-12:00 | 342.15 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.34 | 06-AUG-12:00 | 413.55 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.84 | 10-SEP-15:00 | 403.46 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 | 11-OCT-14:00 | 929.42 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 888.76 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1282.72 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.15 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.23 | 1596.45 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 773.30 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 943.01 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1975.09 | 19-MAR-06:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1351.79 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.36 | 17-MAY-14:40 | 779.04 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.70 | 25-JUN-18:00 | 445.39 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.14 | 16-JUL-12:00 | 445.47 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.70 | 06-AUG-12:00 | 534.51 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.56 | 10-SEP-15:00 | 510.94 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 11-OCT-14:00 | 1141.09 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1080.44 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1620.77 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.39 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.14 | 1975.09 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 718.37 | 31-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 964.68 | 19-FEB-17:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1972.47 | 19-MAR-06:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1301.48 | 16-APR-15:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 | 17-MAY-13:00 | 735.68 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.15 | 25-JUN-17:40 | 448.72 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.79 | 16-JUL-12:00 | 446.80 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.73 | 02-AUG-16:00 | 636.41 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.03 | 10-SEP-14:30 | 493.71 | 21-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 | 11-OCT-14:00 | 1112.63 | 29-OCT-13:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1021.61 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1674.26 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.80 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.79 | 1972.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14256.25 | 26-JAN-16:40 | 6035.01 | 3488.70 | 11182.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14135.07 | 27-FEB-16:20 | 6035.01 | 3488.70 | 11182.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29792.09 | 15-MAR-06:02 | 7623.17 | 6977.40 | 44330.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18480.65 | 13-APR-06:03 | 5082.11 | 4651.60 | 29553.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30715.91 | 22-MAY-06:02 | 6352.64 | 5814.50 | 36941.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32512.76 | 19-JUN-05:12 | 2541.06 | 1550.53 | 21793.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33235.77 | 24-JUL-05:12 | 2541.06 | 1550.53 | 21793.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33477.59 | 28-AUG-05:12 | 2541.06 | 1550.53 | 21793.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34035.97 | 05-SEP-06:03 | 7623.17 | 6977.40 | 44330.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32563.93 | 12-OCT-05:03 | 2541.06 | 846.94 | 21793.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29599.12 | 09-NOV-07:01 | 8893.70 | 8140.30 | 51718.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12552.63 | 15-DEC-16:00 | 6035.01 | 3488.70 | 11172.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12552.63 | 2541.06 | 846.94 | 11172.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34035.97 | 8893.70 | 8140.30 | 51718.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2905.73 | 20-JAN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 |
February | 2968.12 | 18-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 |
March | 6802.14 | 14-MAR-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 |
April | 6127.91 | 21-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.20 |
May | 8437.17 | 31-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 | 0.00 |
June | 11359.40 | 26-JUN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.14 | 0.00 |
July | 9869.06 | 17-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.16 | 0.00 |
August | 11117.40 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.08 | 0.00 |
September | 8406.76 | 12-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 | 0.00 |
October | 6521.11 | 11-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
November | 4066.44 | 09-NOV-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 |
December | 1704.99 | 01-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1704.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11359.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.16 | 66.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2945.94 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.02 |
February | 2290.77 | 10-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.08 |
March | 2608.31 | 15-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 |
April | 2400.53 | 15-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.88 |
May | 2614.81 | 18-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 |
June | 5112.17 | 26-JUN-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 0.00 |
July | 5468.27 | 17-JUL-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.70 | 0.00 |
August | 4718.04 | 21-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 | 0.00 |
September | 4677.65 | 05-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 |
October | 3195.47 | 10-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 | 0.00 |
November | 2252.59 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.41 |
December | 3597.80 | 23-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 999.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5468.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.70 | 999.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2819.56 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.72 |
February | 2651.71 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.48 |
March | 2815.07 | 30-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.28 |
April | 2543.06 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.04 |
May | 2598.45 | 16-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 | 0.00 |
June | 5565.11 | 26-JUN-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 0.00 |
July | 5540.10 | 17-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.37 | 0.00 |
August | 4575.93 | 21-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.24 | 0.00 |
September | 5092.74 | 05-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.28 |
October | 3328.80 | 11-OCT-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 |
November | 2373.26 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.27 |
December | 3324.80 | 19-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2373.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5565.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.37 | 164.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9763.55 | 25-JAN-16:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9830.48 | 27-FEB-16:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13376.23 | 15-MAR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11990.62 | 21-APR-14:00 | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15675.05 | 22-MAY-06:02 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28309.88 | 27-JUN-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29515.46 | 03-JUL-06:03 | 8893.70 | 8140.30 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29182.55 | 28-AUG-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30101.54 | 05-SEP-06:03 | 7623.17 | 6977.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26423.85 | 10-OCT-06:01 | 10164.22 | 9303.20 | 24207.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11775.91 | 08-NOV-16:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8072.56 | 21-DEC-16:35 | 12070.02 | 6977.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8072.56 | 2541.06 | 1550.53 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30101.54 | 12070.02 | 9303.20 | 24207.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8696.96 | 20-JAN-16:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8950.56 | 27-FEB-16:10 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14476.43 | 15-MAR-15:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13546.70 | 21-APR-14:00 | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15477.08 | 31-MAY-15:40 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30247.80 | 26-JUN-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30889.00 | 24-JUL-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30567.06 | 21-AUG-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31047.42 | 05-SEP-05:12 | 3176.32 | 1938.17 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15318.41 | 10-OCT-14:50 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11110.04 | 07-NOV-16:10 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7426.30 | 23-DEC-17:02 | 1905.79 | 1162.74 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7426.30 | 1905.79 | 1162.74 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31047.42 | 6198.29 | 3488.70 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1441.67 | 20-JAN-14:40 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 |
February | 1341.49 | 27-FEB-13:10 | 2544.47 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.15 |
March | 3706.03 | 14-MAR-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 |
April | 3742.40 | 20-APR-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 |
May | 5533.16 | 17-MAY-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 | 0.00 |
June | 10856.75 | 25-JUN-17:11 | 0.00 | 136.41 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 114.40 | 0.00 |
July | 10944.45 | 16-JUL-14:22 | 334.80 | 97.43 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 180.62 | 0.00 |
August | 6561.98 | 20-AUG-15:42 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | 0.00 |
September | 6481.34 | 10-SEP-16:01 | 468.72 | 136.41 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 36.77 | 0.00 |
October | 4022.37 | 11-OCT-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 | 0.00 |
November | 2446.13 | 09-NOV-13:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 |
December | 1522.89 | 23-DEC-17:02 | 401.76 | 245.12 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1341.49 | 0.00 | 97.43 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10944.45 | 2544.47 | 701.62 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 180.62 | 97.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2812.43 | 20-JAN-09:40 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.91 |
February | 4216.25 | 27-FEB-09:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.53 |
March | 8832.13 | 12-MAR-09:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.81 |
April | 7274.19 | 21-APR-08:40 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.69 |
May | 8864.12 | 28-MAY-09:23 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.58 |
June | 11206.71 | 11-JUN-09:02 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.07 |
July | 13492.90 | 16-JUL-09:02 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 47.94 | 0.00 |
August | 13588.57 | 06-AUG-09:02 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.31 |
September | 11519.92 | 04-SEP-09:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.15 |
October | 8120.91 | 01-OCT-09:43 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.61 |
November | 3924.17 | 07-NOV-09:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.19 |
December | 1238.49 | 14-DEC-09:35 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1238.49 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13588.57 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 47.94 | 224.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15456.62 | 22-JAN-12:13 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.00 |
February | 15646.72 | 26-FEB-13:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.12 |
March | 16990.76 | 12-MAR-12:31 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.38 |
April | 9303.12 | 21-APR-13:05 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 |
May | 8127.07 | 16-MAY-13:10 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 12.91 | 0.00 |
June | 14327.74 | 25-JUN-14:32 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 35.96 | 0.00 |
July | 15371.41 | 30-JUL-13:13 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 0.00 |
August | 15086.45 | 20-AUG-13:42 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 15.59 | 0.00 |
September | 16177.09 | 04-SEP-13:12 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 0.00 |
October | 17373.83 | 01-OCT-13:41 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.32 |
November | 16142.64 | 05-NOV-11:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.09 |
December | 16507.99 | 03-DEC-13:02 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8127.07 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17373.83 | 2613.31 | 701.62 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 35.96 | 305.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4921.59 | 20-JAN-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.74 |
February | 5328.14 | 17-FEB-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 |
March | 15433.35 | 12-MAR-15:52 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.60 |
April | 11119.84 | 08-APR-17:05 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.87 |
May | 9855.85 | 28-MAY-14:53 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.17 |
June | 15880.09 | 11-JUN-16:21 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 | 0.00 |
July | 15812.42 | 02-JUL-16:51 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 |
August | 15477.88 | 13-AUG-16:32 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.78 |
September | 15669.69 | 10-SEP-16:01 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 18.77 | 0.00 |
October | 12058.97 | 09-OCT-16:02 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.82 |
November | 6090.27 | 07-NOV-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 |
December | 3667.37 | 01-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3667.37 | 169.55 | 49.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15880.09 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 18.77 | 122.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1291.70 | 24-JAN-14:50 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.60 |
February | 1219.13 | 27-FEB-13:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.07 |
March | 1705.13 | 14-MAR-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
April | 1562.95 | 20-APR-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 |
May | 3715.46 | 17-MAY-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 | 0.00 |
June | 6805.32 | 26-JUN-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 |
July | 6916.32 | 17-JUL-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
August | 5214.81 | 21-AUG-13:50 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.44 | 0.00 |
September | 6422.38 | 11-SEP-06:03 | 1071.35 | 647.39 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 |
October | 3310.60 | 11-OCT-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 0.00 |
November | 1999.84 | 09-NOV-13:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 |
December | 1349.40 | 23-DEC-17:02 | 401.76 | 245.12 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1219.13 | 401.76 | 245.12 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6916.32 | 1306.65 | 647.39 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 | 48.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1890.61 | 25-JAN-08:30 | 2416.29 | 666.27 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 |
February | 3346.92 | 27-FEB-08:35 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.68 |
March | 4656.82 | 15-MAR-08:50 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 |
April | 4897.25 | 21-APR-08:50 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 |
May | 7591.86 | 16-MAY-06:02 | 847.82 | 370.15 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 |
June | 8201.18 | 08-JUN-06:02 | 847.82 | 370.15 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 |
July | 10556.21 | 16-JUL-09:02 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 27.69 | 0.00 |
August | 10864.43 | 06-AUG-08:51 | 339.13 | 98.69 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 |
September | 11047.35 | 04-SEP-09:01 | 296.74 | 86.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.84 |
October | 6626.80 | 09-OCT-09:23 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.56 |
November | 3594.01 | 07-NOV-08:25 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.66 |
December | 1492.51 | 18-DEC-08:30 | 2416.29 | 666.27 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1492.51 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11047.35 | 2416.29 | 666.27 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 27.69 | 27.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11919.74 | 22-JAN-15:13 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.87 |
February | 12251.66 | 26-FEB-14:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.80 |
March | 12598.61 | 12-MAR-12:31 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.06 |
April | 5669.51 | 12-APR-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.08 |
May | 6689.06 | 16-MAY-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1991.42 | 0.00 |
June | 10899.97 | 26-JUN-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6810.64 | 0.00 |
July | 10850.27 | 17-JUL-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6788.33 | 0.00 |
August | 11755.22 | 06-AUG-12:52 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 0.00 |
September | 13109.85 | 04-SEP-13:41 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 0.00 |
October | 12838.81 | 09-OCT-13:22 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 |
November | 12826.31 | 19-NOV-12:42 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.30 |
December | 12713.90 | 17-DEC-15:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5669.51 | 267.84 | 77.95 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13109.85 | 1306.65 | 350.81 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 6810.64 | 273.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3729.71 | 23-JAN-16:10 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 |
February | 3900.63 | 17-FEB-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 |
March | 11428.42 | 12-MAR-16:32 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.54 |
April | 7282.48 | 08-APR-17:05 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.53 |
May | 5957.65 | 31-MAY-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 | 0.00 |
June | 11999.20 | 25-JUN-16:31 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 29.97 | 0.00 |
July | 11819.66 | 02-JUL-17:52 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 0.00 |
August | 12091.71 | 13-AUG-17:41 | 0.00 | 98.69 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 |
September | 12361.48 | 17-SEP-16:01 | 339.11 | 98.69 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 |
October | 10667.51 | 09-OCT-16:02 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 |
November | 5338.38 | 07-NOV-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 |
December | 3073.29 | 04-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3073.29 | 0.00 | 61.68 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12361.48 | 805.38 | 222.08 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 29.97 | 64.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1444.56 | 20-JAN-15:10 | 2544.47 | 756.25 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 |
February | 1504.44 | 27-FEB-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.99 |
March | 3516.75 | 14-MAR-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 |
April | 3363.01 | 20-APR-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 |
May | 5212.75 | 17-MAY-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 0.00 |
June | 9384.68 | 25-JUN-19:02 | 0.00 | 160.07 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 28.96 | 0.00 |
July | 9328.13 | 16-JUL-14:12 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 149.64 | 0.00 |
August | 7177.45 | 21-AUG-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 |
September | 7310.98 | 11-SEP-06:03 | 1071.35 | 660.21 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 |
October | 3951.77 | 10-OCT-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 0.00 |
November | 2609.21 | 09-NOV-13:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 |
December | 1357.46 | 23-DEC-17:02 | 401.76 | 245.12 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1357.46 | 0.00 | 116.92 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9384.68 | 2544.47 | 756.25 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 149.64 | 71.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4368.18 | 26-JAN-13:02 | 4832.57 | 1332.55 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 |
February | 5322.01 | 27-FEB-09:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.86 |
March | 9674.18 | 12-MAR-10:02 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.08 |
April | 9173.28 | 09-APR-08:32 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.11 |
May | 10153.07 | 28-MAY-08:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.89 |
June | 13819.96 | 18-JUN-09:22 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.39 |
July | 14449.54 | 16-JUL-08:51 | 339.13 | 98.69 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 32.21 | 0.00 |
August | 13498.89 | 06-AUG-09:02 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 |
September | 14055.71 | 04-SEP-09:01 | 296.74 | 86.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.43 |
October | 10211.69 | 09-OCT-09:23 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 |
November | 4950.28 | 07-NOV-08:50 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 |
December | 2178.01 | 18-DEC-09:20 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2178.01 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14449.54 | 4832.57 | 1332.55 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 32.21 | 343.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14099.25 | 22-JAN-11:13 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.33 |
February | 14438.22 | 26-FEB-13:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.82 |
March | 14252.04 | 12-MAR-12:42 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.39 |
April | 8886.81 | 12-APR-13:05 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.34 |
May | 7631.77 | 16-MAY-13:10 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 0.00 |
June | 13388.36 | 25-JUN-16:21 | 669.60 | 194.87 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 68.04 | 0.00 |
July | 13790.23 | 23-JUL-11:22 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 | 0.00 |
August | 14431.41 | 27-AUG-12:22 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.68 |
September | 15616.09 | 04-SEP-11:41 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.32 |
October | 15160.63 | 15-OCT-13:32 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.35 |
November | 15923.47 | 05-NOV-12:11 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 |
December | 15279.26 | 17-DEC-13:52 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7631.77 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15923.47 | 2613.31 | 701.62 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 68.04 | 311.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4876.40 | 20-JAN-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 |
February | 6508.60 | 26-FEB-15:43 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.47 |
March | 10697.08 | 12-MAR-16:02 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.44 |
April | 10299.40 | 08-APR-17:05 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.48 |
May | 9473.05 | 28-MAY-15:02 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.18 |
June | 15838.39 | 25-JUN-16:21 | 423.88 | 123.36 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 23.90 | 0.00 |
July | 14459.31 | 02-JUL-16:32 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 | 0.00 |
August | 14440.41 | 13-AUG-17:31 | 0.00 | 86.35 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 |
September | 15282.53 | 17-SEP-16:01 | 339.11 | 98.69 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.27 |
October | 12041.31 | 09-OCT-16:02 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.39 |
November | 9138.37 | 05-NOV-14:52 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 |
December | 3707.80 | 14-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3707.80 | 0.00 | 49.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15838.39 | 805.38 | 222.08 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 23.90 | 107.47 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.865709E+11 | 81003.88 | 24-JAN-16:10 | 0.516150E+11 | 201848.41 | 05-JAN-07:19 |
February | 0.780762E+11 | 73499.76 | 27-FEB-11:00 | 0.555089E+11 | 202252.09 | 06-FEB-07:19 |
March | 0.912819E+11 | 98197.77 | 13-MAR-15:00 | 0.350275E+11 | 157563.51 | 20-MAR-06:19 |
April | 0.830109E+11 | 83590.99 | 07-APR-15:30 | 0.210403E+11 | 171550.44 | 03-APR-06:10 |
May | 0.967321E+11 | 109338.56 | 31-MAY-15:20 | 0.247007E+10 | 73988.15 | 02-MAY-06:10 |
June | 0.129775E+12 | 158908.33 | 26-JUN-15:09 | 18716231.35 | 10773.04 | 09-JUN-06:19 |
July | 0.126716E+12 | 145855.33 | 17-JUL-10:50 | 4197523.69 | 1101.33 | 03-JUL-06:00 |
August | 0.131014E+12 | 142400.88 | 16-AUG-14:00 | 2888434.21 | 1929.18 | 23-AUG-06:10 |
September | 0.109537E+12 | 126325.62 | 12-SEP-15:39 | 0.109737E+10 | 69547.04 | 22-SEP-06:10 |
October | 0.910371E+11 | 106762.99 | 10-OCT-15:50 | 0.241477E+11 | 166012.17 | 30-OCT-06:10 |
November | 0.855519E+11 | 84408.98 | 07-NOV-15:50 | 0.384605E+11 | 176824.87 | 30-NOV-07:10 |
December | 0.850999E+11 | 74604.34 | 01-DEC-13:00 | 0.738152E+11 | 222058.41 | 23-DEC-07:19 |
Annual Sum or Average | 0.119440E+13 | 0.303208E+12 | ||||
Minimum of Months | 0.780762E+11 | 73499.76 | 2888434.21 | 1101.33 | ||
Maximum of Months | 0.131014E+12 | 158908.33 | 0.738152E+11 | 222058.41 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.760930E+10 | 17000.11 | 31-JAN-12:30 | 0.00 | 0.00 |
February | 0.961065E+10 | 20259.14 | 24-FEB-12:30 | 0.00 | 0.00 |
March | 0.129606E+11 | 25643.75 | 28-MAR-12:09 | 0.00 | 0.00 |
April | 0.136047E+11 | 26811.28 | 26-APR-12:30 | 0.00 | 0.00 |
May | 0.172350E+11 | 24641.49 | 27-MAY-11:30 | 0.00 | 0.00 |
June | 0.197774E+11 | 25870.85 | 16-JUN-11:00 | 0.00 | 0.00 |
July | 0.179169E+11 | 26223.18 | 01-JUL-11:50 | 0.00 | 0.00 |
August | 0.176447E+11 | 24029.60 | 04-AUG-11:50 | 0.00 | 0.00 |
September | 0.139015E+11 | 22118.82 | 05-SEP-11:00 | 0.00 | 0.00 |
October | 0.108111E+11 | 21224.89 | 01-OCT-11:30 | 0.00 | 0.00 |
November | 0.805312E+10 | 18174.43 | 01-NOV-11:30 | 0.00 | 0.00 |
December | 0.655144E+10 | 14083.28 | 22-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.155676E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.655144E+10 | 14083.28 | 0.00 | 0.00 | |
Maximum of Months | 0.197774E+11 | 26811.28 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.143157E+11 | 0.387111E+10 | 0.554480E+11 | 0.212633E+10 | 0.435605E+10 | 0.295316E+09 | 0.00 | 0.105417E+10 | 0.00 | 0.00 | 0.00 | 0.510416E+10 | 0.00 |
February | 0.127784E+11 | 0.311835E+10 | 0.502161E+11 | 0.192869E+10 | 0.420047E+10 | 0.320352E+09 | 0.00 | 0.822425E+09 | 0.00 | 0.00 | 0.00 | 0.469143E+10 | 0.00 |
March | 0.149200E+11 | 0.292505E+10 | 0.575730E+11 | 0.222301E+10 | 0.573909E+10 | 0.210958E+09 | 0.00 | 0.223298E+10 | 0.00 | 0.00 | 0.00 | 0.545792E+10 | 0.00 |
April | 0.132200E+11 | 0.235678E+10 | 0.536187E+11 | 0.206169E+10 | 0.482660E+10 | 0.127010E+09 | 0.00 | 0.205469E+10 | 0.00 | 0.00 | 0.00 | 0.474544E+10 | 0.00 |
May | 0.141567E+11 | 0.210763E+10 | 0.565105E+11 | 0.217418E+10 | 0.832176E+10 | 27615504.10 | 0.00 | 0.861743E+10 | 0.00 | 0.00 | 0.00 | 0.481630E+10 | 0.00 |
June | 0.140420E+11 | 0.190756E+10 | 0.554637E+11 | 0.214010E+10 | 0.176873E+11 | 12398642.03 | 0.00 | 0.340084E+11 | 0.00 | 0.00 | 0.00 | 0.451382E+10 | 0.00 |
July | 0.131763E+11 | 0.202103E+10 | 0.546543E+11 | 0.209501E+10 | 0.167402E+11 | 12289162.14 | 0.00 | 0.339237E+11 | 0.00 | 0.00 | 0.00 | 0.409306E+10 | 0.00 |
August | 0.147365E+11 | 0.227746E+10 | 0.575730E+11 | 0.222278E+10 | 0.171016E+11 | 12696297.78 | 0.00 | 0.326544E+11 | 0.00 | 0.00 | 0.00 | 0.443564E+10 | 0.00 |
September | 0.132596E+11 | 0.260525E+10 | 0.535964E+11 | 0.206057E+10 | 0.127593E+11 | 18450735.01 | 0.00 | 0.211572E+11 | 0.00 | 0.00 | 0.00 | 0.408062E+10 | 0.00 |
October | 0.139841E+11 | 0.323314E+10 | 0.554592E+11 | 0.212661E+10 | 0.663213E+10 | 0.145064E+09 | 0.00 | 0.504922E+10 | 0.00 | 0.00 | 0.00 | 0.440777E+10 | 0.00 |
November | 0.141265E+11 | 0.360566E+10 | 0.541547E+11 | 0.207545E+10 | 0.477821E+10 | 0.227413E+09 | 0.00 | 0.200059E+10 | 0.00 | 0.00 | 0.00 | 0.458330E+10 | 0.00 |
December | 0.139337E+11 | 0.400421E+10 | 0.546432E+11 | 0.209512E+10 | 0.445031E+10 | 0.391081E+09 | 0.00 | 0.788276E+09 | 0.00 | 0.00 | 0.00 | 0.479396E+10 | 0.00 |
Annual Sum or Average | 0.166649E+12 | 0.340332E+11 | 0.658911E+12 | 0.253296E+11 | 0.107593E+12 | 0.180064E+10 | 0.00 | 0.144363E+12 | 0.00 | 0.00 | 0.00 | 0.557234E+11 | 0.00 |
Minimum of Months | 0.127784E+11 | 0.190756E+10 | 0.502161E+11 | 0.192869E+10 | 0.420047E+10 | 12289162.14 | 0.00 | 0.788276E+09 | 0.00 | 0.00 | 0.00 | 0.408062E+10 | 0.00 |
Maximum of Months | 0.149200E+11 | 0.400421E+10 | 0.575730E+11 | 0.222301E+10 | 0.176873E+11 | 0.391081E+09 | 0.00 | 0.340084E+11 | 0.00 | 0.00 | 0.00 | 0.545792E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.516150E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.555089E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.350275E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.210403E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.247007E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 18716231.35 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4197523.69 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2888434.21 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.109737E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.241477E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.384605E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.738152E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.303208E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 2888434.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.738152E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17672.30 | 02-JAN-16:49 | 3824.74 | 01-JAN-06:10 | 38886.07 | 02-JAN-08:09 | 1410.29 | 02-JAN-13:09 | 8090.14 | 24-JAN-16:19 | 693.71 | 05-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 17199.23 | 06-FEB-16:00 | 3824.74 | 01-FEB-06:10 | 38886.07 | 01-FEB-08:09 | 1410.29 | 01-FEB-08:20 | 8640.83 | 27-FEB-15:39 | 698.09 | 06-FEB-07:40 | 0.00 | 01-FEB-00:10 |
March | 15780.20 | 21-MAR-07:10 | 3824.74 | 01-MAR-06:10 | 38886.07 | 01-MAR-08:09 | 1410.29 | 01-MAR-13:09 | 18579.74 | 15-MAR-15:00 | 637.53 | 20-MAR-06:40 | 0.00 | 01-MAR-00:10 |
April | 14918.27 | 03-APR-07:10 | 3824.74 | 01-APR-05:10 | 38886.07 | 03-APR-07:10 | 1410.29 | 11-APR-07:10 | 11818.18 | 21-APR-13:39 | 681.86 | 03-APR-06:30 | 0.00 | 01-APR-00:10 |
May | 13903.46 | 01-MAY-07:10 | 2323.70 | 01-MAY-18:49 | 38886.07 | 01-MAY-07:10 | 1410.29 | 03-MAY-07:10 | 18500.93 | 31-MAY-15:20 | 371.31 | 02-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 13950.50 | 16-JUN-07:10 | 2323.70 | 01-JUN-19:19 | 38886.07 | 01-JUN-07:10 | 1410.29 | 01-JUN-07:19 | 31217.19 | 26-JUN-10:50 | 103.33 | 09-JUN-06:19 | 0.00 | 01-JUN-00:10 |
July | 13931.69 | 28-JUL-07:10 | 2323.70 | 01-JUL-19:30 | 38886.07 | 03-JUL-07:10 | 1410.29 | 03-JUL-07:10 | 33125.84 | 24-JUL-15:20 | 15.72 | 03-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 14178.45 | 28-AUG-15:00 | 3824.74 | 10-AUG-05:10 | 38886.07 | 01-AUG-07:10 | 1410.29 | 01-AUG-07:19 | 28919.16 | 14-AUG-14:00 | 20.38 | 23-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 14197.81 | 21-SEP-15:00 | 3824.74 | 01-SEP-05:10 | 38886.07 | 01-SEP-07:10 | 1410.29 | 01-SEP-07:10 | 26770.53 | 05-SEP-15:39 | 360.61 | 22-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 16561.09 | 30-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 38886.07 | 02-OCT-07:10 | 1410.29 | 11-OCT-07:10 | 18383.94 | 11-OCT-15:00 | 658.90 | 31-OCT-06:30 | 0.00 | 01-OCT-00:10 |
November | 17672.30 | 06-NOV-16:49 | 3824.74 | 01-NOV-05:10 | 38886.07 | 01-NOV-07:10 | 1410.29 | 01-NOV-12:09 | 10591.10 | 08-NOV-15:20 | 671.28 | 30-NOV-07:19 | 0.00 | 01-NOV-00:10 |
December | 17672.30 | 01-DEC-16:30 | 3824.74 | 01-DEC-06:10 | 38886.07 | 01-DEC-08:09 | 1410.29 | 05-DEC-08:09 | 7263.65 | 26-DEC-07:10 | 732.49 | 23-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 13903.46 | 2323.70 | 38886.07 | 1410.29 | 7263.65 | 15.72 | 0.00 | |||||||
Maximum of Months | 17672.30 | 3824.74 | 38886.07 | 1410.29 | 33125.84 | 732.49 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 14144.00 | 24-JAN-15:09 | 0.00 | 0.00 | 0.00 | 6742.22 | 30-JAN-12:39 | 0.00 | 01-JAN-00:10 |
February | 9573.33 | 18-FEB-13:50 | 0.00 | 0.00 | 0.00 | 6802.95 | 13-FEB-12:50 | 0.00 | 01-FEB-00:10 |
March | 22207.29 | 13-MAR-15:50 | 0.00 | 0.00 | 0.00 | 6740.47 | 01-MAR-12:20 | 0.00 | 01-MAR-00:10 |
April | 14877.19 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 6679.71 | 03-APR-11:30 | 0.00 | 01-APR-00:10 |
May | 32044.18 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 | 6264.74 | 01-MAY-11:20 | 0.00 | 01-MAY-00:10 |
June | 69541.96 | 26-JUN-14:00 | 0.00 | 0.00 | 0.00 | 5842.26 | 01-JUN-11:00 | 0.00 | 01-JUN-00:10 |
July | 56757.10 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 5757.87 | 06-JUL-11:30 | 0.00 | 01-JUL-00:10 |
August | 58115.32 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 5408.77 | 31-AUG-11:20 | 0.00 | 01-AUG-00:10 |
September | 43630.39 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 | 5768.93 | 29-SEP-11:00 | 0.00 | 01-SEP-00:10 |
October | 32273.40 | 11-OCT-14:30 | 0.00 | 0.00 | 0.00 | 5952.59 | 30-OCT-11:00 | 0.00 | 01-OCT-00:10 |
November | 17284.57 | 07-NOV-15:09 | 0.00 | 0.00 | 0.00 | 6270.33 | 30-NOV-12:30 | 0.00 | 01-NOV-00:10 |
December | 12066.98 | 01-DEC-13:00 | 0.00 | 0.00 | 0.00 | 6686.75 | 29-DEC-12:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 9573.33 | 0.00 | 0.00 | 0.00 | 5408.77 | 0.00 | |||
Maximum of Months | 69541.96 | 0.00 | 0.00 | 0.00 | 6802.95 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 81003.88 | 24-JAN-16:10 | 14981.21 | 38861.85 | 0.00 | 1410.29 | 8061.17 | 6.85 | 0.00 | 12429.11 | 0.00 |
February | 73499.76 | 27-FEB-11:00 | 13903.46 | 38858.69 | 0.00 | 1410.29 | 5026.89 | 6.85 | 0.00 | 8523.81 | 0.00 |
March | 98197.77 | 13-MAR-15:00 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 16779.97 | 6.85 | 0.00 | 22190.79 | 0.00 |
April | 83590.99 | 07-APR-15:30 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 10644.34 | 6.85 | 0.00 | 13750.26 | 0.00 |
May | 109338.56 | 31-MAY-15:20 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 18500.93 | 6.85 | 0.00 | 32044.18 | 0.00 |
June | 158908.33 | 26-JUN-15:09 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 31085.50 | 6.85 | 0.00 | 69391.16 | 0.00 |
July | 145855.33 | 17-JUL-10:50 | 13903.46 | 38858.69 | 0.00 | 1410.29 | 31287.56 | 6.85 | 0.00 | 55786.48 | 0.00 |
August | 142400.88 | 16-AUG-14:00 | 13903.46 | 38852.37 | 0.00 | 1410.29 | 27348.77 | 6.85 | 0.00 | 57680.40 | 0.00 |
September | 126325.62 | 12-SEP-15:39 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 24452.00 | 6.85 | 0.00 | 43444.50 | 0.00 |
October | 106762.99 | 10-OCT-15:50 | 13903.46 | 38861.85 | 0.00 | 1410.29 | 18124.40 | 6.85 | 0.00 | 30059.03 | 0.00 |
November | 84408.98 | 07-NOV-15:50 | 14495.67 | 38852.37 | 0.00 | 1410.29 | 10417.67 | 6.85 | 0.00 | 15688.68 | 0.00 |
December | 74604.34 | 01-DEC-13:00 | 13903.46 | 36960.84 | 0.00 | 1410.29 | 4302.35 | 6.85 | 0.00 | 12066.98 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 73499.76 | 13903.46 | 36960.84 | 0.00 | 1410.29 | 4302.35 | 6.85 | 0.00 | 8523.81 | 0.00 | |
Maximum of Months | 158908.33 | 14981.21 | 38861.85 | 0.00 | 1410.29 | 31287.56 | 6.85 | 0.00 | 69391.16 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 201848.41 | 05-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 202252.09 | 06-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 157563.51 | 20-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 171550.44 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 73988.15 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 10773.04 | 09-JUN-06:19 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 1101.33 | 03-JUL-06:00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1929.18 | 23-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 69547.04 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 166012.17 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 176824.87 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 222058.41 | 23-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 1101.33 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 222058.41 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.42 | 0.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Annual Sum or Average | 0.17 | 20.42 | 0.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.42 | 0.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.67 | 19.34 | 1.50 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
March | 0.33 | 18.21 | 0.17 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
April | 0.33 | 19.39 | 0.33 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 19.45 | 2.00 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
Annual Sum or Average | 4.33 | 19.31 | 4.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.45 | 2.00 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 18.53 | 2.67 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
February | 12.50 | 17.10 | 6.00 | 17.65 | 0.00 | 17.65 | 0.00 | 17.65 |
March | 1.83 | 17.05 | 1.33 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
April | 1.83 | 18.35 | 1.17 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.47 | 2.50 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.52 | 5.50 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.29 | 0.83 | 27.29 |
October | 1.33 | 19.00 | 1.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
November | 2.17 | 18.37 | 1.17 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
December | 24.33 | 17.65 | 15.67 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
Annual Sum or Average | 47.83 | 17.65 | 29.00 | 18.16 | 11.83 | 19.41 | 9.33 | 20.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.33 | 19.00 | 15.67 | 19.33 | 6.67 | 27.52 | 5.50 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 18.03 | 0.83 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
February | 8.83 | 16.16 | 2.67 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
March | 1.67 | 15.80 | 1.00 | 15.75 | 0.67 | 18.16 | 0.67 | 19.76 |
April | 1.33 | 16.93 | 0.33 | 17.41 | 0.50 | 19.72 | 0.50 | 21.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.65 | 0.83 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.79 | 10.50 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 28.03 | 15.67 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.96 | 7.83 | 27.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.74 | 6.50 | 27.75 |
October | 0.33 | 16.67 | 0.00 | 16.67 | 1.83 | 25.90 | 1.83 | 26.66 |
November | 1.33 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 |
December | 15.33 | 16.79 | 6.50 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 |
Annual Sum or Average | 30.83 | 16.64 | 11.33 | 17.16 | 47.33 | 22.83 | 44.33 | 24.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 | 0.00 | 16.55 |
Maximum of Months | 15.33 | 18.03 | 6.50 | 18.61 | 17.00 | 28.03 | 15.67 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 18.74 | 1.00 | 19.24 | 1.67 | 22.63 | 1.67 | 24.08 |
February | 6.17 | 16.76 | 2.33 | 17.40 | 2.17 | 19.55 | 2.17 | 20.97 |
March | 1.00 | 15.99 | 0.67 | 15.99 | 2.17 | 22.81 | 2.17 | 24.71 |
April | 1.00 | 17.17 | 0.33 | 17.66 | 0.00 | 17.66 | 0.00 | 17.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.38 | 0.17 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.63 | 6.33 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.76 | 10.00 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.88 | 6.33 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.34 | 10.83 | 27.33 |
October | 0.50 | 17.63 | 0.17 | 18.05 | 10.00 | 26.59 | 10.00 | 26.87 |
November | 0.83 | 17.41 | 0.17 | 17.74 | 4.83 | 25.88 | 4.83 | 26.65 |
December | 12.33 | 17.52 | 7.00 | 18.13 | 2.50 | 19.27 | 2.50 | 20.17 |
Annual Sum or Average | 23.33 | 17.31 | 11.67 | 17.90 | 59.67 | 24.01 | 57.00 | 25.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.66 | 0.00 | 17.66 |
Maximum of Months | 12.33 | 18.74 | 7.00 | 19.24 | 11.50 | 27.88 | 10.83 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 17.15 | 0.17 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
February | 9.00 | 15.95 | 3.33 | 16.25 | 0.17 | 16.40 | 0.17 | 16.54 |
March | 2.00 | 15.49 | 1.17 | 15.52 | 1.67 | 19.82 | 1.00 | 21.24 |
April | 1.50 | 16.71 | 0.33 | 17.19 | 0.17 | 18.11 | 0.17 | 18.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.64 | 3.17 | 27.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.48 | 5.50 | 28.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.10 | 8.50 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.21 | 4.00 | 28.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.20 | 5.33 | 28.25 |
October | 0.33 | 16.69 | 0.00 | 16.69 | 2.83 | 26.95 | 2.67 | 27.52 |
November | 1.00 | 16.93 | 0.00 | 16.93 | 0.50 | 20.45 | 0.50 | 22.21 |
December | 17.67 | 17.19 | 9.17 | 17.88 | 0.00 | 17.88 | 0.00 | 17.88 |
Annual Sum or Average | 32.83 | 16.71 | 14.17 | 17.23 | 43.83 | 22.51 | 31.00 | 23.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.40 | 0.00 | 16.54 |
Maximum of Months | 17.67 | 17.19 | 9.17 | 17.88 | 12.00 | 28.48 | 8.50 | 28.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.90 | 0.33 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
February | 3.67 | 19.47 | 3.33 | 19.59 | 0.00 | 19.59 | 0.00 | 19.59 |
March | 0.17 | 19.41 | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.83 | 19.64 | 5.33 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
Annual Sum or Average | 10.00 | 19.58 | 9.17 | 19.69 | 0.00 | 19.69 | 0.00 | 19.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.83 | 19.90 | 5.33 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 18.82 | 0.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.52 | 5.50 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.67 | 13.17 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.75 | 5.83 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.57 | 5.83 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.44 | 2.17 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 19.52 | 1.83 | 19.82 | 0.00 | 19.82 | 0.00 | 19.82 |
Annual Sum or Average | 3.17 | 19.33 | 2.33 | 19.69 | 32.67 | 26.48 | 32.67 | 27.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.52 | 1.83 | 19.82 | 13.17 | 27.75 | 13.17 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.00 | 18.02 | 42.00 | 18.02 | 2.33 | 18.27 | 2.33 | 18.51 |
February | 45.50 | 17.95 | 45.17 | 17.96 | 2.00 | 18.17 | 2.00 | 18.37 |
March | 31.00 | 18.22 | 31.00 | 18.22 | 1.50 | 18.44 | 1.50 | 18.65 |
April | 26.83 | 18.68 | 26.83 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
May | 5.50 | 19.23 | 5.50 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 25.18 | 6.33 | 25.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 26.36 | 4.50 | 26.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 25.81 | 13.33 | 25.81 |
September | 1.67 | 19.19 | 1.67 | 19.19 | 17.50 | 25.26 | 16.50 | 25.74 |
October | 23.67 | 18.04 | 23.67 | 18.04 | 16.50 | 20.23 | 15.83 | 21.47 |
November | 30.83 | 18.07 | 30.83 | 18.07 | 7.50 | 19.00 | 7.50 | 19.74 |
December | 63.33 | 17.61 | 62.83 | 17.61 | 3.00 | 17.85 | 3.00 | 18.08 |
Annual Sum or Average | 270.33 | 18.04 | 269.50 | 18.04 | 74.50 | 19.05 | 72.83 | 19.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 0.00 | 18.08 |
Maximum of Months | 63.33 | 19.23 | 62.83 | 19.23 | 17.50 | 26.36 | 16.50 | 26.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 18.85 | 0.50 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.58 | 0.33 | 27.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.78 | 0.17 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.50 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.02 | 4.00 | 28.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.85 | 4.83 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.96 | 2.83 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.86 | 5.00 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.90 | 2.33 | 27.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.37 | 0.17 | 27.37 |
December | 3.83 | 19.75 | 3.33 | 19.94 | 0.00 | 19.94 | 0.00 | 19.94 |
Annual Sum or Average | 4.67 | 19.59 | 3.83 | 19.84 | 28.67 | 26.05 | 20.17 | 26.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 19.75 | 3.33 | 19.94 | 6.83 | 28.02 | 5.00 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.33 | 19.31 | 2.00 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 19.43 | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.36 | 1.00 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.45 | 2.67 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.39 | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
December | 6.67 | 19.51 | 6.00 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
Annual Sum or Average | 9.33 | 19.45 | 8.33 | 19.60 | 4.33 | 21.14 | 3.67 | 22.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.67 | 19.51 | 6.00 | 19.65 | 2.83 | 27.45 | 2.67 | 27.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 18.11 | 0.33 | 18.60 | 0.17 | 19.68 | 0.17 | 20.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.96 | 0.83 | 27.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.65 | 0.83 | 27.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.73 | 1.17 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.71 | 9.83 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.99 | 14.33 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.04 | 6.33 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.77 | 6.50 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.76 | 2.67 | 27.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.50 | 18.70 | 2.67 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Annual Sum or Average | 4.33 | 18.59 | 3.00 | 18.95 | 43.67 | 26.59 | 42.67 | 27.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 18.70 | 2.67 | 19.02 | 15.00 | 28.04 | 14.33 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.34 | 8.17 | 26.34 |
February | 1.00 | 19.34 | 0.83 | 19.58 | 2.83 | 24.71 | 2.83 | 25.96 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.30 | 4.67 | 26.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.33 | 27.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.50 | 4.83 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.60 | 9.00 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.78 | 5.83 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.05 | 12.50 | 27.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 26.73 | 14.33 | 26.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.47 | 11.83 | 26.47 |
December | 3.00 | 19.34 | 2.33 | 19.65 | 3.67 | 23.08 | 3.67 | 24.53 |
Annual Sum or Average | 4.00 | 19.34 | 3.17 | 19.63 | 79.00 | 26.40 | 78.17 | 26.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 23.08 | 0.17 | 24.53 |
Maximum of Months | 3.00 | 19.34 | 2.33 | 19.65 | 14.33 | 27.78 | 14.33 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 18.13 | 0.33 | 18.61 | 0.33 | 20.58 | 0.33 | 21.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.07 | 1.00 | 28.09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.70 | 0.33 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.58 | 2.83 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.35 | 4.83 | 28.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.01 | 7.33 | 27.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.18 | 3.33 | 28.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.12 | 5.17 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.14 | 2.83 | 28.16 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.56 | 0.50 | 27.56 |
December | 5.67 | 19.59 | 5.00 | 19.77 | 0.00 | 19.77 | 0.00 | 19.77 |
Annual Sum or Average | 6.50 | 19.41 | 5.33 | 19.66 | 39.00 | 26.13 | 28.50 | 26.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 19.59 | 5.00 | 19.77 | 10.00 | 28.35 | 7.33 | 28.41 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 467.00 | 23.56 | 0.00 | 23.56 | 0.00 | 23.56 |
February | 402.17 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
March | 465.50 | 23.77 | 1.67 | 23.78 | 0.00 | 23.78 |
April | 365.00 | 23.91 | 7.83 | 23.94 | 0.00 | 23.94 |
May | 129.50 | 24.00 | 124.00 | 24.57 | 0.00 | 24.57 |
June | 2.33 | 24.00 | 286.33 | 24.54 | 0.17 | 24.54 |
July | 28.00 | 24.41 | 333.33 | 24.54 | 23.17 | 24.53 |
August | 1.83 | 24.16 | 321.83 | 24.56 | 0.17 | 24.56 |
September | 41.33 | 24.01 | 155.33 | 24.80 | 0.00 | 24.80 |
October | 236.00 | 23.96 | 42.50 | 24.20 | 0.00 | 24.20 |
November | 348.00 | 23.89 | 4.00 | 23.91 | 0.00 | 23.91 |
December | 492.17 | 23.30 | 27.33 | 23.19 | 27.33 | 23.09 |
Annual Sum or Average | 2978.83 | 23.68 | 1304.17 | 23.97 | 50.83 | 23.96 |
Minimum of Months | 1.83 | 23.30 | 0.00 | 23.19 | 0.00 | 23.09 |
Maximum of Months | 492.17 | 24.41 | 333.33 | 24.80 | 27.33 | 24.80 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.00 | 22.61 | 48.17 | 22.46 | 48.17 | 22.34 |
February | 449.83 | 22.62 | 65.50 | 22.39 | 65.50 | 22.22 |
March | 490.83 | 23.04 | 5.67 | 23.01 | 5.67 | 22.99 |
April | 438.17 | 23.21 | 7.83 | 23.19 | 6.17 | 23.15 |
May | 195.33 | 23.81 | 52.67 | 24.00 | 0.00 | 24.00 |
June | 14.00 | 24.01 | 265.33 | 24.41 | 0.00 | 24.41 |
July | 39.00 | 24.23 | 302.67 | 24.44 | 27.33 | 24.43 |
August | 7.00 | 24.03 | 271.33 | 24.46 | 0.17 | 24.46 |
September | 119.83 | 23.94 | 109.17 | 24.39 | 0.00 | 24.39 |
October | 374.00 | 23.48 | 9.83 | 23.47 | 5.33 | 23.43 |
November | 463.17 | 23.09 | 7.50 | 23.06 | 7.50 | 23.02 |
December | 497.00 | 22.20 | 115.00 | 21.89 | 115.00 | 21.68 |
Annual Sum or Average | 3587.17 | 22.98 | 1260.67 | 23.18 | 280.83 | 23.06 |
Minimum of Months | 7.00 | 22.20 | 5.67 | 21.89 | 0.00 | 21.68 |
Maximum of Months | 499.00 | 24.23 | 302.67 | 24.46 | 115.00 | 24.46 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.75 | 145.67 | 21.43 | 145.67 | 21.23 |
February | 454.00 | 21.89 | 149.50 | 21.52 | 149.50 | 21.30 |
March | 504.83 | 22.47 | 79.67 | 22.16 | 79.67 | 21.93 |
April | 451.83 | 22.63 | 58.00 | 22.39 | 58.00 | 22.19 |
May | 255.17 | 23.60 | 35.83 | 23.70 | 0.83 | 23.69 |
June | 18.17 | 23.92 | 264.50 | 24.38 | 0.00 | 24.38 |
July | 32.33 | 24.18 | 309.00 | 24.42 | 27.17 | 24.41 |
August | 19.17 | 23.94 | 269.17 | 24.38 | 0.17 | 24.38 |
September | 162.67 | 23.73 | 88.67 | 24.08 | 0.00 | 24.08 |
October | 452.00 | 22.94 | 53.33 | 22.72 | 53.33 | 22.53 |
November | 486.67 | 22.27 | 69.83 | 22.08 | 69.83 | 21.94 |
December | 497.00 | 21.35 | 232.17 | 21.02 | 232.17 | 20.85 |
Annual Sum or Average | 3835.83 | 22.37 | 1755.33 | 22.45 | 816.33 | 22.21 |
Minimum of Months | 18.17 | 21.35 | 35.83 | 21.02 | 0.00 | 20.85 |
Maximum of Months | 504.83 | 24.18 | 309.00 | 24.42 | 232.17 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.66 | 307.83 | 20.40 | 307.83 | 20.28 |
February | 454.00 | 20.82 | 286.83 | 20.56 | 286.83 | 20.45 |
March | 512.83 | 21.62 | 194.33 | 21.20 | 194.33 | 20.95 |
April | 453.83 | 21.76 | 138.50 | 21.34 | 135.50 | 21.07 |
May | 259.00 | 23.11 | 90.17 | 23.37 | 10.50 | 23.29 |
June | 24.50 | 24.39 | 337.67 | 24.41 | 8.33 | 24.44 |
July | 51.67 | 24.62 | 369.67 | 24.53 | 42.50 | 24.55 |
August | 54.00 | 23.73 | 301.17 | 24.27 | 4.00 | 24.28 |
September | 193.67 | 23.26 | 103.17 | 23.73 | 4.33 | 23.69 |
October | 470.67 | 22.05 | 121.00 | 21.70 | 121.00 | 21.47 |
November | 486.83 | 21.21 | 236.17 | 20.93 | 236.17 | 20.79 |
December | 497.00 | 20.36 | 385.67 | 20.18 | 385.67 | 20.12 |
Annual Sum or Average | 3960.00 | 21.53 | 2872.17 | 21.69 | 1737.00 | 21.40 |
Minimum of Months | 24.50 | 20.36 | 90.17 | 20.18 | 4.00 | 20.12 |
Maximum of Months | 512.83 | 24.62 | 385.67 | 24.53 | 385.67 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.67 | 21.33 | 221.33 | 20.94 | 221.33 | 20.74 |
February | 426.50 | 21.47 | 187.00 | 21.02 | 184.83 | 20.77 |
March | 418.33 | 21.84 | 159.83 | 21.50 | 142.00 | 21.20 |
April | 362.17 | 21.82 | 144.00 | 21.58 | 106.67 | 21.27 |
May | 163.50 | 23.27 | 174.17 | 23.89 | 7.67 | 23.86 |
June | 39.50 | 26.44 | 415.67 | 24.66 | 36.33 | 24.81 |
July | 88.17 | 25.90 | 438.50 | 24.84 | 87.17 | 24.99 |
August | 48.83 | 25.42 | 396.17 | 24.54 | 27.83 | 24.68 |
September | 127.17 | 23.80 | 209.67 | 24.32 | 17.83 | 24.41 |
October | 373.17 | 22.16 | 146.33 | 22.09 | 102.83 | 21.82 |
November | 459.83 | 21.72 | 156.67 | 21.39 | 154.83 | 21.18 |
December | 497.00 | 20.94 | 291.17 | 20.56 | 291.17 | 20.38 |
Annual Sum or Average | 3500.83 | 21.95 | 2940.50 | 22.30 | 1380.50 | 22.04 |
Minimum of Months | 39.50 | 20.94 | 144.00 | 20.56 | 7.67 | 20.38 |
Maximum of Months | 497.00 | 26.44 | 438.50 | 24.84 | 291.17 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 351.50 | 21.57 | 227.17 | 21.64 | 152.17 | 21.37 |
February | 316.00 | 21.42 | 221.00 | 21.43 | 154.50 | 21.14 |
March | 368.00 | 21.74 | 192.67 | 21.61 | 143.17 | 21.34 |
April | 364.33 | 21.66 | 144.33 | 21.43 | 110.50 | 21.13 |
May | 224.00 | 23.03 | 133.00 | 23.52 | 9.33 | 23.45 |
June | 55.00 | 24.57 | 334.50 | 24.45 | 19.00 | 24.54 |
July | 86.33 | 24.90 | 373.17 | 24.61 | 59.50 | 24.71 |
August | 65.00 | 24.67 | 361.17 | 24.46 | 22.83 | 24.58 |
September | 148.33 | 23.94 | 233.83 | 24.34 | 29.33 | 24.49 |
October | 326.50 | 22.31 | 220.33 | 22.55 | 116.00 | 22.37 |
November | 327.17 | 21.93 | 215.00 | 22.15 | 123.67 | 21.92 |
December | 396.67 | 21.31 | 261.83 | 21.16 | 219.83 | 20.92 |
Annual Sum or Average | 3028.83 | 22.11 | 2918.00 | 22.58 | 1159.83 | 22.33 |
Minimum of Months | 55.00 | 21.31 | 133.00 | 21.16 | 9.33 | 20.92 |
Maximum of Months | 396.67 | 24.90 | 373.17 | 24.61 | 219.83 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 465.33 | 21.07 | 246.50 | 20.74 | 243.17 | 20.56 |
February | 404.17 | 21.12 | 233.83 | 20.84 | 220.33 | 20.65 |
March | 431.50 | 21.64 | 191.33 | 21.37 | 164.67 | 21.11 |
April | 378.83 | 21.64 | 147.83 | 21.41 | 115.50 | 21.12 |
May | 218.17 | 23.16 | 154.00 | 23.68 | 15.17 | 23.68 |
June | 58.17 | 25.09 | 366.17 | 24.56 | 28.33 | 24.69 |
July | 89.83 | 25.03 | 395.00 | 24.64 | 66.50 | 24.74 |
August | 62.50 | 24.57 | 364.50 | 24.46 | 22.17 | 24.55 |
September | 169.50 | 23.69 | 183.67 | 24.18 | 24.83 | 24.31 |
October | 396.50 | 22.08 | 163.17 | 22.03 | 115.33 | 21.81 |
November | 430.17 | 21.46 | 192.17 | 21.20 | 181.67 | 21.01 |
December | 479.33 | 20.75 | 325.67 | 20.44 | 324.50 | 20.31 |
Annual Sum or Average | 3584.00 | 21.80 | 2963.83 | 22.11 | 1522.17 | 21.85 |
Minimum of Months | 58.17 | 20.75 | 147.83 | 20.44 | 15.17 | 20.31 |
Maximum of Months | 479.33 | 25.09 | 395.00 | 24.64 | 324.50 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.78 | 297.17 | 20.60 | 297.17 | 20.52 |
February | 454.00 | 20.79 | 294.67 | 20.63 | 294.67 | 20.56 |
March | 514.00 | 21.40 | 209.83 | 21.11 | 209.83 | 20.95 |
April | 481.67 | 21.74 | 122.17 | 21.47 | 122.17 | 21.29 |
May | 367.00 | 23.22 | 27.67 | 23.23 | 8.17 | 23.18 |
June | 30.17 | 23.97 | 256.17 | 24.27 | 4.50 | 24.27 |
July | 43.50 | 24.06 | 312.33 | 24.36 | 36.00 | 24.33 |
August | 36.83 | 23.90 | 253.17 | 24.26 | 2.50 | 24.26 |
September | 178.83 | 23.66 | 102.83 | 24.06 | 0.00 | 24.06 |
October | 486.33 | 22.69 | 56.50 | 22.48 | 56.50 | 22.31 |
November | 489.00 | 21.67 | 124.83 | 21.48 | 124.83 | 21.35 |
December | 497.00 | 20.71 | 329.33 | 20.53 | 329.33 | 20.45 |
Annual Sum or Average | 4080.33 | 21.73 | 2386.67 | 21.82 | 1485.67 | 21.57 |
Minimum of Months | 30.17 | 20.71 | 27.67 | 20.53 | 0.00 | 20.45 |
Maximum of Months | 514.00 | 24.06 | 329.33 | 24.36 | 329.33 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.64 | 171.83 | 21.34 | 171.83 | 21.16 |
February | 432.33 | 21.67 | 178.33 | 21.29 | 176.00 | 21.06 |
March | 457.00 | 22.16 | 115.17 | 21.83 | 110.00 | 21.58 |
April | 400.33 | 22.31 | 87.00 | 22.13 | 69.67 | 21.90 |
May | 181.17 | 23.42 | 130.33 | 23.93 | 1.67 | 23.92 |
June | 13.33 | 26.29 | 415.00 | 24.55 | 13.17 | 24.61 |
July | 64.67 | 25.44 | 445.83 | 24.73 | 64.67 | 24.81 |
August | 23.17 | 26.37 | 422.33 | 24.58 | 20.33 | 24.67 |
September | 63.17 | 24.12 | 242.83 | 24.62 | 8.00 | 24.69 |
October | 323.00 | 22.79 | 90.50 | 22.93 | 43.00 | 22.75 |
November | 443.00 | 22.35 | 72.33 | 22.16 | 67.67 | 21.98 |
December | 497.00 | 21.45 | 237.83 | 21.09 | 237.83 | 20.91 |
Annual Sum or Average | 3400.17 | 22.23 | 2609.33 | 22.65 | 983.83 | 22.42 |
Minimum of Months | 13.33 | 21.45 | 72.33 | 21.09 | 1.67 | 20.91 |
Maximum of Months | 502.00 | 26.37 | 445.83 | 24.73 | 237.83 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 361.50 | 21.64 | 150.33 | 21.65 | 93.17 | 21.32 |
February | 335.83 | 21.23 | 179.67 | 21.12 | 132.83 | 20.78 |
March | 403.83 | 21.59 | 147.00 | 21.29 | 131.33 | 21.01 |
April | 427.00 | 21.68 | 105.33 | 21.41 | 98.50 | 21.18 |
May | 331.50 | 22.77 | 54.17 | 22.95 | 12.17 | 22.86 |
June | 62.67 | 23.26 | 260.17 | 24.19 | 6.50 | 24.18 |
July | 73.67 | 23.74 | 333.00 | 24.36 | 42.83 | 24.33 |
August | 48.17 | 23.75 | 372.67 | 24.41 | 15.50 | 24.45 |
September | 86.33 | 23.80 | 271.17 | 24.54 | 21.17 | 24.67 |
October | 265.83 | 22.30 | 185.67 | 22.83 | 70.67 | 22.68 |
November | 296.00 | 21.89 | 166.67 | 22.34 | 63.33 | 22.07 |
December | 391.33 | 21.18 | 187.67 | 20.93 | 158.17 | 20.60 |
Annual Sum or Average | 3083.67 | 21.92 | 2413.50 | 22.46 | 846.17 | 22.18 |
Minimum of Months | 48.17 | 21.18 | 54.17 | 20.93 | 6.50 | 20.60 |
Maximum of Months | 427.00 | 23.80 | 372.67 | 24.54 | 158.17 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.50 | 21.49 | 179.83 | 21.21 | 179.00 | 21.04 |
February | 430.83 | 21.51 | 188.67 | 21.17 | 187.00 | 20.98 |
March | 462.83 | 21.92 | 135.83 | 21.61 | 130.33 | 21.37 |
April | 423.83 | 22.15 | 87.67 | 21.93 | 78.17 | 21.71 |
May | 244.50 | 23.34 | 102.67 | 23.72 | 3.00 | 23.70 |
June | 30.00 | 25.53 | 370.00 | 24.56 | 19.83 | 24.64 |
July | 48.33 | 24.77 | 398.67 | 24.55 | 48.33 | 24.57 |
August | 20.50 | 25.42 | 397.50 | 24.52 | 13.50 | 24.57 |
September | 94.17 | 24.21 | 214.00 | 24.62 | 15.17 | 24.73 |
October | 349.00 | 22.86 | 92.33 | 22.91 | 46.83 | 22.75 |
November | 433.50 | 22.26 | 72.67 | 22.10 | 66.50 | 21.94 |
December | 490.33 | 21.32 | 240.17 | 20.99 | 239.50 | 20.82 |
Annual Sum or Average | 3512.33 | 22.14 | 2480.00 | 22.50 | 1027.17 | 22.27 |
Minimum of Months | 20.50 | 21.32 | 72.67 | 20.99 | 3.00 | 20.82 |
Maximum of Months | 490.33 | 25.53 | 398.67 | 24.62 | 239.50 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.16 | 219.50 | 20.88 | 219.50 | 20.74 |
February | 454.00 | 21.21 | 219.17 | 20.91 | 219.17 | 20.76 |
March | 510.50 | 21.97 | 122.83 | 21.62 | 122.83 | 21.39 |
April | 456.50 | 22.26 | 80.17 | 21.98 | 78.00 | 21.76 |
May | 234.00 | 23.45 | 77.17 | 23.70 | 2.50 | 23.68 |
June | 8.83 | 24.27 | 351.33 | 24.44 | 4.00 | 24.44 |
July | 36.00 | 24.45 | 381.33 | 24.52 | 35.83 | 24.51 |
August | 22.67 | 23.92 | 309.17 | 24.36 | 2.33 | 24.36 |
September | 167.17 | 23.58 | 111.83 | 24.07 | 0.00 | 24.07 |
October | 465.33 | 22.59 | 64.33 | 22.34 | 64.33 | 22.15 |
November | 486.17 | 21.72 | 130.33 | 21.49 | 130.33 | 21.35 |
December | 497.00 | 20.78 | 302.33 | 20.53 | 302.33 | 20.43 |
Annual Sum or Average | 3840.17 | 21.90 | 2369.50 | 22.12 | 1181.17 | 21.85 |
Minimum of Months | 8.83 | 20.78 | 64.33 | 20.53 | 0.00 | 20.43 |
Maximum of Months | 510.50 | 24.45 | 381.33 | 24.52 | 302.33 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.67 | 21.67 | 143.67 | 21.35 | 142.33 | 21.16 |
February | 350.00 | 21.63 | 146.83 | 21.27 | 138.50 | 21.01 |
March | 356.67 | 22.10 | 99.83 | 21.86 | 81.33 | 21.59 |
April | 311.33 | 22.24 | 93.00 | 22.13 | 60.33 | 21.89 |
May | 131.67 | 23.58 | 152.67 | 24.20 | 4.33 | 24.22 |
June | 30.33 | 26.62 | 348.17 | 24.78 | 29.83 | 24.92 |
July | 79.17 | 25.94 | 373.17 | 24.98 | 79.17 | 25.12 |
August | 34.67 | 25.95 | 331.00 | 24.70 | 25.67 | 24.83 |
September | 99.83 | 24.11 | 178.67 | 24.61 | 13.67 | 24.73 |
October | 312.50 | 22.58 | 106.83 | 22.66 | 63.00 | 22.45 |
November | 377.67 | 22.06 | 92.33 | 21.85 | 85.17 | 21.65 |
December | 418.67 | 21.22 | 225.17 | 20.84 | 225.17 | 20.66 |
Annual Sum or Average | 2917.17 | 22.25 | 2291.33 | 22.67 | 948.50 | 22.45 |
Minimum of Months | 30.33 | 21.22 | 92.33 | 20.84 | 4.33 | 20.66 |
Maximum of Months | 418.67 | 26.62 | 373.17 | 24.98 | 225.17 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 329.00 | 22.07 | 177.17 | 22.31 | 89.67 | 22.09 |
February | 299.17 | 21.84 | 193.50 | 21.94 | 117.00 | 21.65 |
March | 352.00 | 22.10 | 136.50 | 22.09 | 83.33 | 21.85 |
April | 359.33 | 22.24 | 94.33 | 22.10 | 65.50 | 21.86 |
May | 195.00 | 23.37 | 130.33 | 23.85 | 3.17 | 23.81 |
June | 25.33 | 25.12 | 348.50 | 24.49 | 12.83 | 24.55 |
July | 55.33 | 25.14 | 385.67 | 24.64 | 50.50 | 24.70 |
August | 35.00 | 25.47 | 383.67 | 24.53 | 20.17 | 24.63 |
September | 111.67 | 24.33 | 247.50 | 24.59 | 24.67 | 24.75 |
October | 301.00 | 22.83 | 199.67 | 23.14 | 83.33 | 23.04 |
November | 307.17 | 22.48 | 177.00 | 22.90 | 68.83 | 22.78 |
December | 384.50 | 21.82 | 217.17 | 21.72 | 169.33 | 21.48 |
Annual Sum or Average | 2754.50 | 22.48 | 2691.00 | 23.05 | 788.33 | 22.87 |
Minimum of Months | 25.33 | 21.82 | 94.33 | 21.72 | 3.17 | 21.48 |
Maximum of Months | 384.50 | 25.47 | 385.67 | 24.64 | 169.33 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 457.67 | 21.56 | 164.17 | 21.27 | 159.50 | 21.07 |
February | 397.17 | 21.51 | 180.83 | 21.23 | 166.83 | 21.01 |
March | 427.67 | 22.05 | 126.67 | 21.84 | 100.00 | 21.59 |
April | 376.33 | 22.22 | 99.17 | 22.08 | 68.00 | 21.84 |
May | 188.17 | 23.48 | 155.00 | 23.98 | 7.17 | 23.99 |
June | 36.17 | 25.83 | 382.17 | 24.61 | 26.17 | 24.72 |
July | 60.00 | 25.37 | 409.67 | 24.67 | 59.00 | 24.75 |
August | 31.33 | 25.35 | 383.67 | 24.53 | 18.83 | 24.61 |
September | 134.00 | 24.03 | 193.17 | 24.46 | 19.33 | 24.61 |
October | 377.50 | 22.62 | 121.00 | 22.63 | 70.67 | 22.45 |
November | 420.50 | 21.98 | 117.17 | 21.83 | 99.50 | 21.64 |
December | 474.50 | 21.15 | 259.50 | 20.83 | 256.50 | 20.66 |
Annual Sum or Average | 3381.00 | 22.16 | 2592.17 | 22.55 | 1051.50 | 22.33 |
Minimum of Months | 31.33 | 21.15 | 99.17 | 20.83 | 7.17 | 20.66 |
Maximum of Months | 474.50 | 25.83 | 409.67 | 24.67 | 256.50 | 24.75 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.63334 | 20.06051 | 0.05725 | 5.67161 |
February | 454.00000 | 23.59445 | 18.41382 | 0.03479 | 5.89510 |
March | 514.00000 | 23.87087 | 18.19311 | 0.11892 | 5.59140 |
April | 485.00000 | 24.05142 | 22.17686 | 0.18892 | 6.01621 |
May | 508.00000 | 24.36219 | 24.90064 | -0.5493 | 11.87864 |
June | 496.00000 | 24.33857 | 33.01503 | -0.4435 | 9.50795 |
July | 497.00000 | 24.39802 | 34.90039 | -0.4104 | 8.92295 |
August | 514.00000 | 24.36620 | 33.48741 | -0.4288 | 9.29319 |
September | 485.00000 | 24.39714 | 24.85427 | -0.4908 | 10.62505 |
October | 502.00000 | 24.25870 | 19.60013 | 0.25702 | 6.69559 |
November | 489.00000 | 24.05177 | 20.83752 | 0.18398 | 6.00450 |
December | 497.00000 | 23.31280 | 15.17482 | -0.0517 | 6.20962 |
Annual Sum or Average | 5943.00000 | 24.05630 | 23.85080 | -0.1297 | 7.70886 |
Minimum of Months | 454.00000 | 23.31280 | 15.17482 | -0.5493 | 5.59140 |
Maximum of Months | 514.00000 | 24.39802 | 34.90039 | 0.25702 | 11.87864 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.62124 | 21.82271 | -0.1710 | 6.94946 |
February | 454.00000 | 22.63299 | 19.92613 | -0.1835 | 7.43915 |
March | 514.00000 | 23.11012 | 19.63695 | -0.0557 | 6.29249 |
April | 485.00000 | 23.31417 | 23.49013 | 0.01904 | 6.02801 |
May | 508.00000 | 24.11557 | 25.82688 | -0.6378 | 14.09929 |
June | 496.00000 | 24.26585 | 33.65272 | -0.4763 | 10.05772 |
July | 497.00000 | 24.32153 | 35.49372 | -0.4444 | 9.45904 |
August | 514.00000 | 24.28373 | 34.10846 | -0.4689 | 9.93587 |
September | 485.00000 | 24.25800 | 25.42803 | -0.5553 | 12.01666 |
October | 502.00000 | 23.70359 | 20.78825 | 0.11380 | 6.20114 |
November | 489.00000 | 23.15164 | 22.70049 | -0.0290 | 5.94933 |
December | 497.00000 | 22.19883 | 16.45901 | -0.3106 | 8.94246 |
Annual Sum or Average | 5943.00000 | 23.50525 | 24.99082 | -0.2678 | 8.62828 |
Minimum of Months | 454.00000 | 22.19883 | 16.45901 | -0.6378 | 5.94933 |
Maximum of Months | 514.00000 | 24.32153 | 35.49372 | 0.11380 | 14.09929 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.74969 | 22.81089 | -0.3919 | 10.41380 |
February | 454.00000 | 21.88722 | 20.69544 | -0.3745 | 10.60418 |
March | 514.00000 | 22.49829 | 20.09323 | -0.2099 | 8.44309 |
April | 485.00000 | 22.72977 | 24.18778 | -0.1239 | 7.53324 |
May | 508.00000 | 23.90958 | 25.92126 | -0.7095 | 16.59168 |
June | 496.00000 | 24.24846 | 33.38771 | -0.4736 | 10.03880 |
July | 497.00000 | 24.32016 | 35.27655 | -0.4379 | 9.41635 |
August | 514.00000 | 24.24823 | 34.02937 | -0.4763 | 10.08186 |
September | 485.00000 | 24.11668 | 25.33343 | -0.6109 | 13.70796 |
October | 502.00000 | 23.06520 | 21.59934 | -0.0517 | 6.90826 |
November | 489.00000 | 22.27941 | 23.94648 | -0.2475 | 7.95294 |
December | 497.00000 | 21.35115 | 17.20122 | -0.5314 | 13.42120 |
Annual Sum or Average | 5943.00000 | 23.04370 | 25.41579 | -0.3870 | 10.42922 |
Minimum of Months | 454.00000 | 21.35115 | 17.20122 | -0.7095 | 6.90826 |
Maximum of Months | 514.00000 | 24.32016 | 35.27655 | -0.0517 | 16.59168 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.66236 | 25.03934 | -0.6759 | 17.35215 |
February | 454.00000 | 20.81701 | 22.72779 | -0.6542 | 16.94577 |
March | 514.00000 | 21.62517 | 21.83004 | -0.4282 | 12.52561 |
April | 485.00000 | 21.90333 | 25.63622 | -0.3158 | 11.03009 |
May | 508.00000 | 23.65528 | 26.95035 | -0.7735 | 19.88549 |
June | 496.00000 | 24.30198 | 33.35699 | -0.4043 | 9.25683 |
July | 497.00000 | 24.40540 | 35.33158 | -0.3600 | 8.81680 |
August | 514.00000 | 24.20106 | 34.69691 | -0.4586 | 10.23364 |
September | 485.00000 | 23.89559 | 26.27954 | -0.6705 | 16.91570 |
October | 502.00000 | 22.17955 | 23.88001 | -0.2690 | 9.59315 |
November | 489.00000 | 21.21746 | 26.27028 | -0.5189 | 12.80812 |
December | 497.00000 | 20.35512 | 18.50010 | -0.8077 | 21.49802 |
Annual Sum or Average | 5943.00000 | 22.44939 | 26.74513 | -0.5272 | 13.88099 |
Minimum of Months | 454.00000 | 20.35512 | 18.50010 | -0.8077 | 8.81680 |
Maximum of Months | 514.00000 | 24.40540 | 35.33158 | -0.2690 | 21.49802 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.35802 | 24.91175 | -0.4888 | 13.49733 |
February | 454.00000 | 21.63671 | 22.31919 | -0.4297 | 14.07964 |
March | 514.00000 | 22.29428 | 20.87927 | -0.2298 | 11.28291 |
April | 485.00000 | 22.41096 | 24.66837 | -0.1544 | 10.62351 |
May | 508.00000 | 23.97501 | 25.98436 | -0.5938 | 14.99604 |
June | 496.00000 | 24.42196 | 32.77445 | -0.2516 | 7.88357 |
July | 497.00000 | 24.56697 | 34.84772 | -0.2040 | 8.05580 |
August | 514.00000 | 24.34064 | 33.90711 | -0.2929 | 8.55615 |
September | 485.00000 | 24.18412 | 25.40114 | -0.4809 | 12.83336 |
October | 502.00000 | 22.76295 | 22.77764 | -0.1016 | 9.94221 |
November | 489.00000 | 21.86475 | 25.79310 | -0.3442 | 10.71695 |
December | 497.00000 | 20.93727 | 18.89871 | -0.6494 | 17.86803 |
Annual Sum or Average | 5943.00000 | 22.90776 | 26.13123 | -0.3512 | 11.67519 |
Minimum of Months | 454.00000 | 20.93727 | 18.89871 | -0.6494 | 7.88357 |
Maximum of Months | 514.00000 | 24.56697 | 34.84772 | -0.1016 | 17.86803 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.40313 | 21.31758 | -0.1783 | 11.91323 |
February | 454.00000 | 22.30079 | 19.47739 | -0.2154 | 13.55331 |
March | 514.00000 | 22.44695 | 19.52088 | -0.1687 | 11.68491 |
April | 485.00000 | 22.27548 | 24.20091 | -0.1924 | 10.93523 |
May | 508.00000 | 23.74573 | 26.33937 | -0.7086 | 18.63065 |
June | 496.00000 | 24.27666 | 33.28680 | -0.3879 | 9.50759 |
July | 497.00000 | 24.41478 | 35.16435 | -0.3243 | 8.94070 |
August | 514.00000 | 24.28402 | 34.08630 | -0.3518 | 9.25100 |
September | 485.00000 | 24.16511 | 25.02482 | -0.4639 | 13.37685 |
October | 502.00000 | 22.99597 | 21.20671 | 0.00708 | 11.23507 |
November | 489.00000 | 22.75620 | 22.45853 | -0.0709 | 11.01677 |
December | 497.00000 | 21.93287 | 16.08685 | -0.3527 | 14.79628 |
Annual Sum or Average | 5943.00000 | 23.17431 | 24.89706 | -0.2849 | 12.06305 |
Minimum of Months | 454.00000 | 21.93287 | 16.08685 | -0.7086 | 8.94070 |
Maximum of Months | 514.00000 | 24.41478 | 35.16435 | 0.00708 | 18.63065 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.29211 | 24.47405 | -0.5032 | 14.72543 |
February | 454.00000 | 21.46563 | 22.05028 | -0.4722 | 15.03529 |
March | 514.00000 | 22.05399 | 21.40492 | -0.2898 | 12.12590 |
April | 485.00000 | 22.17964 | 25.37074 | -0.2171 | 11.17286 |
May | 508.00000 | 23.79853 | 26.75109 | -0.6676 | 18.02202 |
June | 496.00000 | 24.33895 | 33.32176 | -0.3103 | 9.08626 |
July | 497.00000 | 24.43975 | 35.31284 | -0.2897 | 8.69272 |
August | 514.00000 | 24.28746 | 34.50630 | -0.3517 | 9.34571 |
September | 485.00000 | 24.06050 | 25.95998 | -0.5443 | 15.05060 |
October | 502.00000 | 22.55118 | 23.31954 | -0.1435 | 10.32045 |
November | 489.00000 | 21.79499 | 25.63073 | -0.3583 | 11.48353 |
December | 497.00000 | 20.87418 | 18.44605 | -0.6654 | 18.88703 |
Annual Sum or Average | 5943.00000 | 22.77322 | 26.41860 | -0.4006 | 12.81144 |
Minimum of Months | 454.00000 | 20.87418 | 18.44605 | -0.6676 | 8.69272 |
Maximum of Months | 514.00000 | 24.43975 | 35.31284 | -0.1435 | 18.88703 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.77830 | 24.99182 | -0.6429 | 15.03673 |
February | 454.00000 | 20.79147 | 22.73258 | -0.6633 | 15.75426 |
March | 514.00000 | 21.39951 | 22.46591 | -0.4890 | 11.78425 |
April | 485.00000 | 21.75450 | 26.91727 | -0.3571 | 9.44933 |
May | 508.00000 | 23.48151 | 28.26141 | -0.8751 | 22.78506 |
June | 496.00000 | 24.20171 | 33.89813 | -0.4879 | 10.26423 |
July | 497.00000 | 24.29372 | 35.72518 | -0.4426 | 9.51479 |
August | 514.00000 | 24.18689 | 34.75632 | -0.4940 | 10.43002 |
September | 485.00000 | 24.07185 | 26.33465 | -0.6151 | 14.13072 |
October | 502.00000 | 22.72983 | 23.66435 | -0.1204 | 7.03472 |
November | 489.00000 | 21.66727 | 25.87082 | -0.3858 | 9.41832 |
December | 497.00000 | 20.70808 | 18.49037 | -0.6958 | 16.91643 |
Annual Sum or Average | 5943.00000 | 22.51917 | 27.04890 | -0.5220 | 12.70310 |
Minimum of Months | 454.00000 | 20.70808 | 18.49037 | -0.8751 | 7.03472 |
Maximum of Months | 514.00000 | 24.29372 | 35.72518 | -0.1204 | 22.78506 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.64278 | 24.89566 | -0.4107 | 10.64819 |
February | 454.00000 | 21.79673 | 22.32541 | -0.3915 | 11.96531 |
March | 514.00000 | 22.40273 | 21.27163 | -0.2127 | 9.38999 |
April | 485.00000 | 22.65122 | 25.32918 | -0.1094 | 8.24107 |
May | 508.00000 | 24.00114 | 26.65802 | -0.6276 | 15.08050 |
June | 496.00000 | 24.42857 | 32.89286 | -0.2919 | 7.76097 |
July | 497.00000 | 24.57092 | 34.85588 | -0.2434 | 7.69066 |
August | 514.00000 | 24.41117 | 33.59442 | -0.2899 | 7.88677 |
September | 485.00000 | 24.38592 | 25.21260 | -0.4047 | 10.11589 |
October | 502.00000 | 23.39450 | 22.23719 | 0.07055 | 7.91860 |
November | 489.00000 | 22.52758 | 25.04525 | -0.1622 | 7.81137 |
December | 497.00000 | 21.44825 | 18.84102 | -0.4994 | 13.03306 |
Annual Sum or Average | 5943.00000 | 23.14933 | 26.13191 | -0.2975 | 9.78730 |
Minimum of Months | 454.00000 | 21.44825 | 18.84102 | -0.6276 | 7.69066 |
Maximum of Months | 514.00000 | 24.57092 | 34.85588 | 0.07055 | 15.08050 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.45946 | 19.90952 | -0.1183 | 10.49607 |
February | 454.00000 | 22.08541 | 18.25160 | -0.2286 | 12.89315 |
March | 514.00000 | 22.17866 | 18.76219 | -0.2163 | 10.72580 |
April | 485.00000 | 21.98968 | 24.08219 | -0.2503 | 9.39183 |
May | 508.00000 | 23.31085 | 26.95716 | -0.8763 | 23.88529 |
June | 496.00000 | 24.15957 | 33.20746 | -0.4775 | 10.72131 |
July | 497.00000 | 24.31355 | 35.26448 | -0.4023 | 9.53112 |
August | 514.00000 | 24.28849 | 33.45287 | -0.3733 | 9.20444 |
September | 485.00000 | 24.32021 | 24.48292 | -0.3956 | 11.08242 |
October | 502.00000 | 23.31576 | 20.04957 | 0.12819 | 10.71359 |
November | 489.00000 | 22.96051 | 20.82890 | 0.03583 | 10.23507 |
December | 497.00000 | 21.89318 | 14.50099 | -0.2944 | 13.76652 |
Annual Sum or Average | 5943.00000 | 23.11423 | 24.20027 | -0.2904 | 11.89808 |
Minimum of Months | 454.00000 | 21.89318 | 14.50099 | -0.8763 | 9.20444 |
Maximum of Months | 514.00000 | 24.32021 | 35.26448 | 0.12819 | 23.88529 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.58489 | 24.55888 | -0.4230 | 11.23664 |
February | 454.00000 | 21.64970 | 22.16430 | -0.4275 | 12.24297 |
March | 514.00000 | 22.16355 | 21.72036 | -0.2748 | 9.93233 |
April | 485.00000 | 22.41455 | 26.08948 | -0.1755 | 8.45750 |
May | 508.00000 | 23.86379 | 27.38131 | -0.6948 | 17.41312 |
June | 496.00000 | 24.36933 | 33.39490 | -0.3436 | 8.59989 |
July | 497.00000 | 24.44150 | 35.39136 | -0.3321 | 8.34980 |
August | 514.00000 | 24.37686 | 34.16312 | -0.3462 | 8.50812 |
September | 485.00000 | 24.34641 | 25.56821 | -0.4456 | 11.11164 |
October | 502.00000 | 23.31926 | 22.51555 | 0.05522 | 7.85380 |
November | 489.00000 | 22.49092 | 24.89051 | -0.1692 | 7.89575 |
December | 497.00000 | 21.36292 | 18.53341 | -0.5187 | 13.73370 |
Annual Sum or Average | 5943.00000 | 23.04300 | 26.40378 | -0.3413 | 10.44238 |
Minimum of Months | 454.00000 | 21.36292 | 18.53341 | -0.6948 | 7.85380 |
Maximum of Months | 514.00000 | 24.44150 | 35.39136 | 0.05522 | 17.41312 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.16138 | 24.59602 | -0.5272 | 12.78195 |
February | 454.00000 | 21.21067 | 22.20550 | -0.5323 | 13.40511 |
March | 514.00000 | 21.98690 | 21.40346 | -0.3218 | 9.84243 |
April | 485.00000 | 22.36278 | 25.15717 | -0.1963 | 8.24054 |
May | 508.00000 | 23.86948 | 26.71212 | -0.6993 | 16.71490 |
June | 496.00000 | 24.33606 | 33.47680 | -0.4015 | 8.96376 |
July | 497.00000 | 24.43359 | 35.38053 | -0.3588 | 8.48132 |
August | 514.00000 | 24.25603 | 34.60314 | -0.4456 | 9.66389 |
September | 485.00000 | 24.07456 | 26.20620 | -0.6062 | 14.24837 |
October | 502.00000 | 22.70490 | 23.29521 | -0.1262 | 7.48661 |
November | 489.00000 | 21.73028 | 25.60451 | -0.3687 | 9.50523 |
December | 497.00000 | 20.77617 | 18.32449 | -0.6710 | 16.78821 |
Annual Sum or Average | 5943.00000 | 22.75504 | 26.45256 | -0.4375 | 11.33069 |
Minimum of Months | 454.00000 | 20.77617 | 18.32449 | -0.6993 | 7.48661 |
Maximum of Months | 514.00000 | 24.43359 | 35.38053 | -0.1262 | 16.78821 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.74566 | 24.23384 | -0.3723 | 10.59089 |
February | 385.00000 | 21.88535 | 21.63723 | -0.3466 | 12.10848 |
March | 433.00000 | 22.49478 | 20.33306 | -0.1672 | 9.73418 |
April | 410.00000 | 22.70997 | 24.33298 | -0.0767 | 8.60324 |
May | 430.00000 | 24.15020 | 25.89266 | -0.5453 | 13.43381 |
June | 418.00000 | 24.53367 | 32.63266 | -0.2453 | 7.90769 |
July | 422.00000 | 24.69870 | 34.51703 | -0.1922 | 8.04239 |
August | 433.00000 | 24.46226 | 33.74523 | -0.2852 | 8.45393 |
September | 410.00000 | 24.35315 | 25.29189 | -0.4404 | 11.69128 |
October | 427.00000 | 23.12232 | 22.18860 | -0.0017 | 8.77580 |
November | 417.00000 | 22.28637 | 25.00323 | -0.2214 | 8.77185 |
December | 422.00000 | 21.25299 | 18.36930 | -0.5437 | 14.75108 |
Annual Sum or Average | 5034.00000 | 23.15007 | 25.71186 | -0.2862 | 10.22769 |
Minimum of Months | 385.00000 | 21.25299 | 18.36930 | -0.5453 | 7.90769 |
Maximum of Months | 433.00000 | 24.69870 | 34.51703 | -0.0017 | 14.75108 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.86839 | 20.74644 | -0.0386 | 9.95413 |
February | 454.00000 | 22.69676 | 18.78613 | -0.0960 | 11.43007 |
March | 514.00000 | 22.78380 | 18.99567 | -0.0694 | 9.75919 |
April | 485.00000 | 22.73551 | 23.61941 | -0.0743 | 8.32763 |
May | 508.00000 | 23.95137 | 26.09624 | -0.6373 | 15.55863 |
June | 496.00000 | 24.32974 | 33.35812 | -0.3803 | 9.00314 |
July | 497.00000 | 24.45774 | 35.16986 | -0.3195 | 8.45401 |
August | 514.00000 | 24.35085 | 33.95386 | -0.3366 | 8.61367 |
September | 485.00000 | 24.31767 | 25.01530 | -0.4081 | 11.29415 |
October | 502.00000 | 23.41920 | 20.73003 | 0.12841 | 10.05326 |
November | 489.00000 | 23.21444 | 21.72790 | 0.06550 | 9.80576 |
December | 497.00000 | 22.39493 | 15.62123 | -0.2114 | 11.92918 |
Annual Sum or Average | 5943.00000 | 23.46646 | 24.53721 | -0.1995 | 10.34629 |
Minimum of Months | 454.00000 | 22.39493 | 15.62123 | -0.6373 | 8.32763 |
Maximum of Months | 514.00000 | 24.45774 | 35.16986 | 0.12841 | 15.55863 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.78907 | 23.93167 | -0.3566 | 10.94107 |
February | 454.00000 | 21.86395 | 21.46398 | -0.3509 | 12.03001 |
March | 514.00000 | 22.41910 | 20.88825 | -0.1844 | 9.77960 |
April | 485.00000 | 22.65058 | 24.80562 | -0.0966 | 8.48694 |
May | 508.00000 | 24.00811 | 26.46409 | -0.5955 | 14.92125 |
June | 496.00000 | 24.38877 | 33.39193 | -0.3033 | 8.54875 |
July | 497.00000 | 24.48227 | 35.33238 | -0.2847 | 8.18786 |
August | 514.00000 | 24.35093 | 34.38435 | -0.3369 | 8.70460 |
September | 485.00000 | 24.23043 | 25.87127 | -0.4832 | 12.59208 |
October | 502.00000 | 23.04141 | 22.73169 | -0.0087 | 8.53035 |
November | 489.00000 | 22.30486 | 24.87253 | -0.2107 | 8.83087 |
December | 497.00000 | 21.30093 | 18.15323 | -0.5293 | 14.78639 |
Annual Sum or Average | 5943.00000 | 23.07967 | 26.06583 | -0.3117 | 10.51946 |
Minimum of Months | 454.00000 | 21.30093 | 18.15323 | -0.5955 | 8.18786 |
Maximum of Months | 514.00000 | 24.48227 | 35.33238 | -0.0087 | 14.92125 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.376923E+11 | 0.00 | 324.87 | 176805.46 | 05-JAN-07:11 | 0.00 | 35.93 | 46.66 | 0.17 | 0.00 | 0.05 | 0.61 | 05-JAN-07:11 |
February | 0.408280E+11 | 0.00 | 336.40 | 169001.83 | 06-FEB-07:06 | 0.00 | 35.25 | 46.69 | 0.22 | 0.00 | 0.06 | 0.58 | 06-FEB-07:06 |
March | 0.250731E+11 | 0.00 | 277.87 | 167678.80 | 02-MAR-07:01 | 0.00 | 35.07 | 44.31 | 0.10 | 0.00 | 0.03 | 0.58 | 02-MAR-07:01 |
April | 0.149788E+11 | 0.00 | 219.15 | 162015.00 | 25-APR-06:02 | 0.00 | 32.89 | 40.97 | 0.06 | 0.00 | 0.02 | 0.56 | 25-APR-06:02 |
May | 0.166959E+10 | 0.00 | 64.03 | 150009.26 | 01-MAY-06:03 | 0.00 | 38.44 | 40.42 | 0.01 | 0.00 | 0.00 | 0.52 | 01-MAY-06:03 |
June | 11817349.66 | 0.00 | 39.51 | 8416.93 | 09-JUN-06:06 | 0.00 | 42.96 | 43.90 | 0.00 | 0.00 | 0.00 | 0.03 | 09-JUN-06:06 |
July | 2652807.77 | 0.00 | 73.40 | 3065.67 | 03-JUL-06:07 | 0.00 | 40.51 | 42.47 | 0.00 | 0.00 | 0.00 | 0.01 | 03-JUL-06:07 |
August | 1824537.74 | 0.00 | 52.02 | 5607.21 | 23-AUG-06:08 | 0.00 | 39.56 | 40.99 | 0.00 | 0.00 | 0.00 | 0.02 | 23-AUG-06:08 |
September | 0.794604E+09 | 0.00 | 25.17 | 90871.14 | 22-SEP-06:02 | 0.00 | 35.82 | 36.72 | 0.00 | 0.00 | 0.00 | 0.31 | 22-SEP-06:02 |
October | 0.174466E+11 | 0.00 | 187.78 | 151744.01 | 31-OCT-06:12 | 0.00 | 30.69 | 37.05 | 0.08 | 0.00 | 0.02 | 0.52 | 31-OCT-06:12 |
November | 0.274384E+11 | 0.00 | 272.97 | 157734.11 | 30-NOV-07:12 | 0.00 | 32.64 | 42.13 | 0.13 | 0.00 | 0.04 | 0.55 | 30-NOV-07:12 |
December | 0.555574E+11 | 0.00 | 390.50 | 189304.25 | 23-DEC-07:07 | 0.00 | 36.29 | 48.10 | 0.27 | 0.00 | 0.07 | 0.65 | 23-DEC-07:07 |
Annual Sum or Average | 0.221495E+12 | 0.00 | 2263.67 | 0.00 | 36.35 | 42.52 | 0.09 | 0.00 | 0.02 | ||||
Minimum of Months | 1824537.74 | 0.00 | 25.17 | 3065.67 | 0.00 | 30.69 | 36.72 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.555574E+11 | 0.00 | 390.50 | 189304.25 | 0.00 | 42.96 | 48.10 | 0.27 | 0.00 | 0.07 | 0.65 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.132034E+10 | 0.300002E+09 | 39.56 | 0.131933E+10 | 1013269.92 | 0.00 | 0.84 | 24-JAN-15:10 | 0.00 | 01-JAN-00:10 | 23049.57 | 24-JAN-15:10 | 23049.57 | 24-JAN-15:10 | 233.98 | 27-JAN-17:01 | 4835.21 | 24-JAN-15:10 | 0.00 |
February | 0.690257E+09 | 0.165598E+09 | 37.22 | 0.685961E+09 | 4296581.66 | 0.00 | 0.70 | 27-FEB-12:00 | 0.00 | 01-FEB-00:10 | 18710.78 | 27-FEB-12:00 | 18710.78 | 27-FEB-12:00 | 818.27 | 23-FEB-12:02 | 4071.68 | 27-FEB-12:00 | 0.00 |
March | 0.305143E+10 | 0.676426E+09 | 95.70 | 0.301724E+10 | 34192058.05 | 0.00 | 1.00 | 13-MAR-13:30 | 0.00 | 01-MAR-00:10 | 34487.07 | 13-MAR-16:00 | 34487.07 | 13-MAR-16:00 | 1667.06 | 17-MAR-14:20 | 6895.37 | 13-MAR-16:00 | 0.00 |
April | 0.341357E+10 | 0.793260E+09 | 119.66 | 0.334049E+10 | 73075423.17 | 0.00 | 0.77 | 13-APR-12:50 | 0.00 | 01-APR-00:10 | 20744.77 | 13-APR-12:50 | 20744.77 | 13-APR-12:50 | 2535.20 | 28-APR-14:00 | 4436.60 | 13-APR-12:50 | 0.00 |
May | 0.122562E+11 | 0.269422E+10 | 229.61 | 0.119634E+11 | 0.292794E+09 | 0.00 | 1.00 | 04-MAY-14:30 | 0.00 | 01-MAY-00:10 | 43393.65 | 31-MAY-16:00 | 43393.65 | 31-MAY-16:00 | 2927.25 | 31-MAY-06:02 | 9666.88 | 17-MAY-13:30 | 0.00 |
June | 0.475904E+11 | 0.110345E+11 | 432.84 | 0.453964E+11 | 0.219394E+10 | 0.00 | 1.00 | 01-JUN-10:05 | 0.00 | 01-JUN-00:10 | 71521.44 | 26-JUN-15:20 | 71521.44 | 26-JUN-15:20 | 20698.80 | 21-JUN-06:03 | 22133.18 | 26-JUN-15:20 | 0.00 |
July | 0.484526E+11 | 0.110593E+11 | 436.63 | 0.447362E+11 | 0.371643E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 66734.51 | 17-JUL-10:50 | 66734.51 | 17-JUL-10:50 | 29756.38 | 31-JUL-15:40 | 18100.47 | 17-JUL-12:20 | 0.00 |
August | 0.481181E+11 | 0.109318E+11 | 431.94 | 0.457009E+11 | 0.241720E+10 | 0.00 | 1.00 | 01-AUG-12:05 | 0.00 | 01-AUG-00:10 | 65993.01 | 16-AUG-16:00 | 65993.01 | 16-AUG-16:00 | 30700.46 | 04-AUG-06:03 | 19069.25 | 16-AUG-16:00 | 0.00 |
September | 0.338258E+11 | 0.743161E+10 | 364.91 | 0.333469E+11 | 0.478880E+09 | 0.00 | 1.00 | 01-SEP-09:50 | 0.00 | 01-SEP-00:10 | 59476.94 | 12-SEP-16:00 | 59476.94 | 12-SEP-16:00 | 9028.11 | 01-SEP-14:00 | 14385.10 | 12-SEP-16:00 | 0.00 |
October | 0.932015E+10 | 0.201882E+10 | 178.00 | 0.924900E+10 | 71152415.00 | 0.00 | 1.00 | 10-OCT-09:50 | 0.00 | 01-OCT-00:10 | 50647.07 | 10-OCT-15:30 | 50647.07 | 10-OCT-15:30 | 1634.93 | 03-OCT-11:10 | 10602.34 | 11-OCT-14:20 | 0.00 |
November | 0.312670E+10 | 0.700798E+09 | 85.78 | 0.310783E+10 | 18870330.06 | 0.00 | 1.00 | 07-NOV-15:05 | 0.00 | 01-NOV-00:10 | 29022.88 | 07-NOV-15:10 | 29022.88 | 07-NOV-15:10 | 988.81 | 13-NOV-13:05 | 5804.59 | 07-NOV-15:10 | 0.00 |
December | 0.910872E+09 | 0.215174E+09 | 44.61 | 0.909704E+09 | 1167670.10 | 0.00 | 0.65 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 17121.55 | 01-DEC-14:00 | 17121.55 | 01-DEC-14:00 | 207.39 | 03-DEC-15:18 | 3777.54 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.212076E+12 | 0.480215E+11 | 2496.45 | 0.202773E+12 | 0.930301E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.690257E+09 | 0.165598E+09 | 37.22 | 0.685961E+09 | 1013269.92 | 0.00 | 0.65 | 0.00 | 17121.55 | 17121.55 | 207.39 | 3777.54 | 0.00 | ||||||
Maximum of Months | 0.484526E+11 | 0.110593E+11 | 436.63 | 0.457009E+11 | 0.371643E+10 | 0.00 | 1.00 | 0.00 | 71521.44 | 71521.44 | 30700.46 | 22133.18 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.180998E+10 | 0.413278E+09 | 54.39 | 0.179630E+10 | 13680849.15 | 0.00 | 0.83 | 24-JAN-15:05 | 0.00 | 01-JAN-00:10 | 22428.82 | 24-JAN-15:05 | 22428.82 | 24-JAN-15:05 | 1290.51 | 27-JAN-13:25 | 4718.04 | 24-JAN-15:05 | 0.00 |
February | 0.104475E+10 | 0.251632E+09 | 58.87 | 0.101878E+10 | 25962018.72 | 0.00 | 0.62 | 18-FEB-13:05 | 0.00 | 01-FEB-00:10 | 15795.98 | 18-FEB-13:05 | 15795.98 | 18-FEB-13:05 | 1121.85 | 23-FEB-12:00 | 3519.59 | 18-FEB-13:05 | 0.00 |
March | 0.344404E+10 | 0.755736E+09 | 92.98 | 0.344270E+10 | 1330978.43 | 0.00 | 1.00 | 13-MAR-13:10 | 0.00 | 01-MAR-00:10 | 37461.29 | 13-MAR-15:50 | 37461.29 | 13-MAR-15:50 | 247.83 | 17-MAR-08:30 | 7488.62 | 13-MAR-15:50 | 0.00 |
April | 0.269549E+10 | 0.620946E+09 | 95.62 | 0.265912E+10 | 36365672.71 | 0.00 | 0.88 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 24236.87 | 20-APR-13:00 | 24236.87 | 20-APR-13:00 | 2622.42 | 28-APR-14:00 | 5021.83 | 20-APR-13:00 | 0.00 |
May | 0.130174E+11 | 0.284558E+10 | 240.36 | 0.126811E+11 | 0.336328E+09 | 0.00 | 1.00 | 04-MAY-13:50 | 0.00 | 01-MAY-00:10 | 47038.36 | 16-MAY-14:05 | 47038.36 | 16-MAY-14:05 | 2775.79 | 31-MAY-07:35 | 10392.52 | 16-MAY-14:05 | 0.00 |
June | 0.470722E+11 | 0.109105E+11 | 436.39 | 0.449210E+11 | 0.215130E+10 | 0.00 | 1.00 | 01-JUN-09:00 | 0.00 | 01-JUN-00:10 | 70568.22 | 26-JUN-15:00 | 70568.22 | 26-JUN-15:00 | 15381.90 | 22-JUN-13:20 | 21976.13 | 26-JUN-15:00 | 0.00 |
July | 0.477707E+11 | 0.109183E+11 | 442.75 | 0.441445E+11 | 0.362626E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 67446.03 | 17-JUL-10:30 | 67446.03 | 17-JUL-10:30 | 30338.28 | 31-JUL-15:40 | 18869.81 | 17-JUL-12:02 | 0.00 |
August | 0.454463E+11 | 0.103619E+11 | 431.18 | 0.431690E+11 | 0.227730E+10 | 0.00 | 1.00 | 01-AUG-12:05 | 0.00 | 01-AUG-00:10 | 65528.70 | 16-AUG-15:00 | 65528.70 | 16-AUG-15:00 | 21559.06 | 28-AUG-06:02 | 18452.22 | 16-AUG-14:05 | 0.00 |
September | 0.304135E+11 | 0.672088E+10 | 358.27 | 0.299395E+11 | 0.474061E+09 | 0.00 | 1.00 | 01-SEP-10:00 | 0.00 | 01-SEP-00:10 | 58652.86 | 11-SEP-14:05 | 58652.86 | 11-SEP-14:05 | 8158.97 | 01-SEP-14:00 | 13930.86 | 12-SEP-15:40 | 0.00 |
October | 0.725180E+10 | 0.158278E+10 | 142.71 | 0.721421E+10 | 37592316.00 | 0.00 | 1.00 | 10-OCT-10:05 | 0.00 | 01-OCT-00:10 | 49021.63 | 11-OCT-14:05 | 49021.63 | 11-OCT-14:05 | 2159.41 | 03-OCT-11:05 | 10548.57 | 11-OCT-14:05 | 0.00 |
November | 0.291870E+10 | 0.661625E+09 | 84.48 | 0.288152E+10 | 37186367.96 | 0.00 | 1.00 | 07-NOV-15:05 | 0.00 | 01-NOV-00:10 | 29477.08 | 07-NOV-15:05 | 29477.08 | 07-NOV-15:05 | 1146.22 | 14-NOV-13:04 | 5895.16 | 07-NOV-15:05 | 0.00 |
December | 0.122136E+10 | 0.287937E+09 | 55.06 | 0.121769E+10 | 3669072.62 | 0.00 | 0.74 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 19475.82 | 01-DEC-14:00 | 19475.82 | 01-DEC-14:00 | 206.78 | 03-DEC-15:18 | 4201.46 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.204106E+12 | 0.463312E+11 | 2493.06 | 0.195085E+12 | 0.902103E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.104475E+10 | 0.251632E+09 | 54.39 | 0.101878E+10 | 1330978.43 | 0.00 | 0.62 | 0.00 | 15795.98 | 15795.98 | 206.78 | 3519.59 | 0.00 | ||||||
Maximum of Months | 0.477707E+11 | 0.109183E+11 | 442.75 | 0.449210E+11 | 0.362626E+10 | 0.00 | 1.00 | 0.00 | 70568.22 | 70568.22 | 30338.28 | 21976.13 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.147504E+10 | 0.340886E+09 | 46.29 | 0.145577E+10 | 19272062.53 | 0.00 | 0.71 | 24-JAN-14:40 | 0.00 | 01-JAN-00:10 | 21979.74 | 24-JAN-14:40 | 21979.74 | 24-JAN-14:40 | 1098.49 | 27-JAN-13:40 | 4769.25 | 24-JAN-14:40 | 0.00 |
February | 0.170501E+10 | 0.405196E+09 | 68.13 | 0.167802E+10 | 26989874.07 | 0.00 | 0.66 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 20049.48 | 27-FEB-15:10 | 20049.48 | 27-FEB-15:10 | 1022.89 | 23-FEB-13:02 | 4413.80 | 27-FEB-15:10 | 0.00 |
March | 0.360248E+10 | 0.800818E+09 | 92.49 | 0.359986E+10 | 2620868.98 | 0.00 | 1.00 | 13-MAR-13:40 | 0.00 | 01-MAR-00:10 | 39205.08 | 13-MAR-15:50 | 39205.08 | 13-MAR-15:50 | 408.27 | 30-MAR-16:25 | 7838.91 | 13-MAR-15:50 | 0.00 |
April | 0.276617E+10 | 0.640484E+09 | 91.25 | 0.271838E+10 | 47795390.84 | 0.00 | 0.83 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 26529.09 | 20-APR-13:00 | 26529.09 | 20-APR-13:00 | 2969.29 | 28-APR-14:00 | 5567.93 | 20-APR-13:00 | 0.00 |
May | 0.139620E+11 | 0.307763E+10 | 240.94 | 0.135015E+11 | 0.460479E+09 | 0.00 | 1.00 | 04-MAY-13:50 | 0.00 | 01-MAY-00:10 | 55037.66 | 31-MAY-15:20 | 55037.66 | 31-MAY-15:20 | 3252.90 | 31-MAY-08:00 | 12214.22 | 31-MAY-15:20 | 0.00 |
June | 0.516232E+11 | 0.120634E+11 | 437.91 | 0.492685E+11 | 0.235475E+10 | 0.00 | 1.00 | 01-JUN-10:30 | 0.00 | 01-JUN-00:10 | 81946.93 | 26-JUN-15:10 | 81946.93 | 26-JUN-15:10 | 16689.21 | 22-JUN-13:20 | 25520.20 | 26-JUN-15:00 | 0.00 |
July | 0.517784E+11 | 0.119461E+11 | 446.47 | 0.478875E+11 | 0.389087E+10 | 0.00 | 1.00 | 01-JUL-08:40 | 0.00 | 01-JUL-00:10 | 74737.57 | 17-JUL-14:00 | 74737.57 | 17-JUL-14:00 | 31357.14 | 31-JUL-15:40 | 20584.34 | 17-JUL-13:10 | 0.00 |
August | 0.493515E+11 | 0.113607E+11 | 431.60 | 0.469275E+11 | 0.242396E+10 | 0.00 | 1.00 | 02-AUG-09:50 | 0.00 | 01-AUG-00:10 | 77302.69 | 16-AUG-15:00 | 77302.69 | 16-AUG-15:00 | 16130.21 | 05-AUG-14:50 | 21653.68 | 16-AUG-15:00 | 0.00 |
September | 0.313422E+11 | 0.700466E+10 | 359.28 | 0.307051E+11 | 0.637034E+09 | 0.00 | 1.00 | 01-SEP-10:40 | 0.00 | 01-SEP-00:10 | 65530.25 | 12-SEP-15:40 | 65530.25 | 12-SEP-15:40 | 7883.45 | 01-SEP-14:00 | 15595.04 | 12-SEP-15:40 | 0.00 |
October | 0.651527E+10 | 0.144762E+10 | 130.53 | 0.645804E+10 | 57228694.91 | 0.00 | 1.00 | 10-OCT-11:00 | 0.00 | 01-OCT-00:10 | 53397.10 | 11-OCT-14:50 | 53397.10 | 11-OCT-14:50 | 2104.21 | 03-OCT-11:05 | 11347.00 | 11-OCT-14:30 | 0.00 |
November | 0.276326E+10 | 0.638169E+09 | 80.33 | 0.272002E+10 | 43239680.54 | 0.00 | 0.89 | 07-NOV-14:50 | 0.00 | 01-NOV-00:10 | 28834.60 | 07-NOV-14:50 | 28834.60 | 07-NOV-14:50 | 913.35 | 14-NOV-13:50 | 5953.04 | 07-NOV-14:50 | 0.00 |
December | 0.119100E+10 | 0.285165E+09 | 52.30 | 0.118527E+10 | 5738597.96 | 0.00 | 0.61 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 18328.20 | 01-DEC-14:00 | 18328.20 | 01-DEC-14:00 | 382.18 | 29-DEC-16:10 | 4087.99 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.218076E+12 | 0.500108E+11 | 2477.53 | 0.208106E+12 | 0.996997E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.119100E+10 | 0.285165E+09 | 46.29 | 0.118527E+10 | 2620868.98 | 0.00 | 0.61 | 0.00 | 18328.20 | 18328.20 | 382.18 | 4087.99 | 0.00 | ||||||
Maximum of Months | 0.517784E+11 | 0.120634E+11 | 446.47 | 0.492685E+11 | 0.389087E+10 | 0.00 | 1.00 | 0.00 | 81946.93 | 81946.93 | 31357.14 | 25520.20 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 384.46 | 0.00 | 384.46 | 79.82 | 1801.58 | 0.00 | 0.00 | 0.00 |
February | 483.22 | 0.00 | 483.22 | 96.12 | 1834.01 | 0.00 | 0.00 | 0.00 |
March | 657.51 | 0.00 | 657.51 | 306.02 | 1394.86 | 0.00 | 0.00 | 0.00 |
April | 825.73 | 4.58 | 821.15 | 461.26 | 1199.07 | 0.00 | 0.00 | 0.00 |
May | 1128.00 | 37.29 | 1090.72 | 1020.74 | 728.71 | 0.00 | 0.00 | 0.00 |
June | 1236.93 | 137.13 | 1099.80 | 1641.47 | 405.28 | 0.00 | 0.00 | 0.00 |
July | 1169.80 | 75.72 | 1094.08 | 1570.33 | 384.31 | 0.00 | 0.00 | 0.00 |
August | 931.07 | 22.03 | 909.05 | 1194.41 | 439.21 | 0.00 | 0.00 | 0.00 |
September | 782.10 | 0.18 | 781.92 | 884.62 | 676.56 | 0.00 | 0.00 | 0.00 |
October | 560.17 | 0.00 | 560.17 | 311.53 | 1384.12 | 0.00 | 0.00 | 0.00 |
November | 425.24 | 0.00 | 425.24 | 126.24 | 1638.93 | 0.00 | 0.00 | 0.00 |
December | 359.71 | 0.00 | 359.71 | 68.46 | 2021.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 746.69 | 23.13 | 723.56 | 649.83 | 1155.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 359.71 | 0.00 | 359.71 | 68.46 | 384.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1236.93 | 137.13 | 1099.80 | 1641.47 | 2021.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 802.58 | 491.85 | 310.74 | 724.45 | 1130.88 | 0.00 | 0.00 | 0.00 |
February | 1066.14 | 673.05 | 393.09 | 1008.89 | 1174.67 | 0.00 | 0.00 | 0.00 |
March | 1286.81 | 750.58 | 536.22 | 1309.86 | 898.32 | 0.00 | 0.00 | 0.00 |
April | 1319.69 | 642.84 | 676.85 | 1313.85 | 782.36 | 0.00 | 0.00 | 0.00 |
May | 1542.70 | 644.39 | 898.31 | 1746.46 | 492.91 | 0.00 | 0.00 | 0.00 |
June | 1882.25 | 988.13 | 894.12 | 2523.21 | 272.67 | 0.00 | 0.00 | 0.00 |
July | 1711.11 | 814.79 | 896.32 | 2313.07 | 258.53 | 0.00 | 0.00 | 0.00 |
August | 1725.89 | 950.56 | 775.33 | 2320.04 | 294.84 | 0.00 | 0.00 | 0.00 |
September | 1436.03 | 780.09 | 655.94 | 1830.63 | 435.59 | 0.00 | 0.00 | 0.00 |
October | 1039.97 | 569.84 | 470.13 | 1093.73 | 905.94 | 0.00 | 0.00 | 0.00 |
November | 809.48 | 457.04 | 352.44 | 767.12 | 1057.96 | 0.00 | 0.00 | 0.00 |
December | 700.80 | 403.71 | 297.09 | 604.90 | 1281.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1277.76 | 680.24 | 597.52 | 1465.15 | 746.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 700.80 | 403.71 | 297.09 | 604.90 | 258.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1882.25 | 988.13 | 898.31 | 2523.21 | 1281.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3684.63 | 3031.01 | 653.63 | 4234.02 | 1644.91 | 0.00 | 0.00 | 0.00 |
February | 3534.25 | 2817.72 | 716.52 | 4017.83 | 1717.94 | 0.00 | 0.00 | 0.00 |
March | 2605.72 | 1714.42 | 891.30 | 3000.44 | 1371.20 | 0.00 | 0.00 | 0.00 |
April | 1687.66 | 678.61 | 1009.04 | 1771.27 | 1235.64 | 0.00 | 0.00 | 0.00 |
May | 1546.55 | 283.47 | 1263.08 | 1763.30 | 798.98 | 0.00 | 0.00 | 0.00 |
June | 1425.87 | 260.61 | 1165.26 | 2050.91 | 443.77 | 0.00 | 0.00 | 0.00 |
July | 1484.30 | 265.80 | 1218.50 | 2139.88 | 411.93 | 0.00 | 0.00 | 0.00 |
August | 1889.81 | 790.01 | 1099.80 | 2742.05 | 463.68 | 0.00 | 0.00 | 0.00 |
September | 2431.43 | 1356.72 | 1074.70 | 3309.86 | 695.05 | 0.00 | 0.00 | 0.00 |
October | 2907.28 | 2062.78 | 844.50 | 3529.11 | 1375.55 | 0.00 | 0.00 | 0.00 |
November | 3542.11 | 2823.58 | 718.53 | 4154.24 | 1572.04 | 0.00 | 0.00 | 0.00 |
December | 3387.18 | 2741.54 | 645.64 | 3813.06 | 1837.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2504.77 | 1561.76 | 943.01 | 3038.26 | 1127.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1425.87 | 260.61 | 645.64 | 1763.30 | 411.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3684.63 | 3031.01 | 1263.08 | 4234.02 | 1837.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 853.77 | 540.99 | 312.77 | 822.64 | 1157.22 | 0.00 | 0.00 | 0.00 |
February | 1029.52 | 638.00 | 391.52 | 978.44 | 1187.99 | 0.00 | 0.00 | 0.00 |
March | 1205.51 | 665.11 | 540.40 | 1217.11 | 915.07 | 0.00 | 0.00 | 0.00 |
April | 1135.04 | 480.56 | 654.48 | 1094.46 | 801.71 | 0.00 | 0.00 | 0.00 |
May | 1387.31 | 489.08 | 898.23 | 1572.41 | 522.28 | 0.00 | 0.00 | 0.00 |
June | 1696.77 | 816.38 | 880.39 | 2304.99 | 305.42 | 0.00 | 0.00 | 0.00 |
July | 1382.46 | 506.37 | 876.09 | 1882.58 | 280.11 | 0.00 | 0.00 | 0.00 |
August | 1442.90 | 712.81 | 730.09 | 1938.83 | 312.05 | 0.00 | 0.00 | 0.00 |
September | 1279.42 | 613.57 | 665.85 | 1643.36 | 465.15 | 0.00 | 0.00 | 0.00 |
October | 1076.33 | 615.20 | 461.13 | 1169.16 | 921.52 | 0.00 | 0.00 | 0.00 |
November | 883.19 | 536.20 | 346.98 | 871.96 | 1069.95 | 0.00 | 0.00 | 0.00 |
December | 713.37 | 421.41 | 291.96 | 629.81 | 1285.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1174.16 | 585.60 | 588.56 | 1345.34 | 766.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 713.37 | 421.41 | 291.96 | 629.81 | 280.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1696.77 | 816.38 | 898.23 | 2304.99 | 1285.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.15 | 0.00 | 128.15 | 27.46 | 612.21 | 0.00 | 0.00 | 0.00 |
February | 161.07 | 0.00 | 161.07 | 35.52 | 615.62 | 0.00 | 0.00 | 0.00 |
March | 219.16 | 0.00 | 219.16 | 110.92 | 464.67 | 0.00 | 0.00 | 0.00 |
April | 275.23 | 1.53 | 273.70 | 163.52 | 403.20 | 0.00 | 0.00 | 0.00 |
May | 375.98 | 12.43 | 363.55 | 353.36 | 237.12 | 0.00 | 0.00 | 0.00 |
June | 412.29 | 45.71 | 366.58 | 557.97 | 131.42 | 0.00 | 0.00 | 0.00 |
July | 389.92 | 25.24 | 364.68 | 533.73 | 123.93 | 0.00 | 0.00 | 0.00 |
August | 310.34 | 7.34 | 303.00 | 403.86 | 146.23 | 0.00 | 0.00 | 0.00 |
September | 260.69 | 0.06 | 260.63 | 295.78 | 234.72 | 0.00 | 0.00 | 0.00 |
October | 186.72 | 0.00 | 186.72 | 101.86 | 488.54 | 0.00 | 0.00 | 0.00 |
November | 141.74 | 0.00 | 141.74 | 39.95 | 574.74 | 0.00 | 0.00 | 0.00 |
December | 119.90 | 0.00 | 119.90 | 22.12 | 699.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.89 | 7.71 | 241.18 | 221.54 | 393.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.90 | 0.00 | 119.90 | 22.12 | 123.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.29 | 45.71 | 366.58 | 557.97 | 699.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.15 | 0.00 | 128.15 | 27.46 | 612.24 | 0.00 | 0.00 | 0.00 |
February | 161.07 | 0.00 | 161.07 | 35.52 | 615.66 | 0.00 | 0.00 | 0.00 |
March | 219.17 | 0.00 | 219.17 | 110.93 | 464.70 | 0.00 | 0.00 | 0.00 |
April | 275.24 | 1.53 | 273.72 | 163.52 | 403.23 | 0.00 | 0.00 | 0.00 |
May | 376.00 | 12.43 | 363.57 | 353.37 | 237.13 | 0.00 | 0.00 | 0.00 |
June | 412.31 | 45.71 | 366.60 | 558.00 | 131.43 | 0.00 | 0.00 | 0.00 |
July | 389.93 | 25.24 | 364.69 | 533.75 | 123.94 | 0.00 | 0.00 | 0.00 |
August | 310.36 | 7.34 | 303.01 | 403.88 | 146.23 | 0.00 | 0.00 | 0.00 |
September | 260.70 | 0.06 | 260.64 | 295.79 | 234.73 | 0.00 | 0.00 | 0.00 |
October | 186.72 | 0.00 | 186.72 | 101.86 | 488.57 | 0.00 | 0.00 | 0.00 |
November | 141.75 | 0.00 | 141.75 | 39.95 | 574.77 | 0.00 | 0.00 | 0.00 |
December | 119.90 | 0.00 | 119.90 | 22.12 | 699.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.90 | 7.71 | 241.19 | 221.55 | 393.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.90 | 0.00 | 119.90 | 22.12 | 123.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.31 | 45.71 | 366.60 | 558.00 | 699.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.15 | 0.00 | 128.15 | 27.46 | 612.24 | 0.00 | 0.00 | 0.00 |
February | 161.07 | 0.00 | 161.07 | 35.52 | 615.66 | 0.00 | 0.00 | 0.00 |
March | 219.17 | 0.00 | 219.17 | 110.93 | 464.70 | 0.00 | 0.00 | 0.00 |
April | 275.24 | 1.53 | 273.72 | 163.52 | 403.23 | 0.00 | 0.00 | 0.00 |
May | 376.00 | 12.43 | 363.57 | 353.37 | 237.13 | 0.00 | 0.00 | 0.00 |
June | 412.31 | 45.71 | 366.60 | 558.00 | 131.43 | 0.00 | 0.00 | 0.00 |
July | 389.93 | 25.24 | 364.69 | 533.75 | 123.94 | 0.00 | 0.00 | 0.00 |
August | 310.36 | 7.34 | 303.01 | 403.88 | 146.23 | 0.00 | 0.00 | 0.00 |
September | 260.70 | 0.06 | 260.64 | 295.79 | 234.73 | 0.00 | 0.00 | 0.00 |
October | 186.72 | 0.00 | 186.72 | 101.86 | 488.57 | 0.00 | 0.00 | 0.00 |
November | 141.75 | 0.00 | 141.75 | 39.95 | 574.77 | 0.00 | 0.00 | 0.00 |
December | 119.90 | 0.00 | 119.90 | 22.12 | 699.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.90 | 7.71 | 241.19 | 221.55 | 393.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.90 | 0.00 | 119.90 | 22.12 | 123.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.31 | 45.71 | 366.60 | 558.00 | 699.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 772.04 | 473.13 | 298.91 | 696.65 | 1128.17 | 0.00 | 0.00 | 0.00 |
February | 1025.58 | 647.44 | 378.14 | 978.76 | 1159.03 | 0.00 | 0.00 | 0.00 |
March | 1237.84 | 722.02 | 515.82 | 1274.80 | 888.46 | 0.00 | 0.00 | 0.00 |
April | 1269.47 | 618.38 | 651.09 | 1278.21 | 784.35 | 0.00 | 0.00 | 0.00 |
May | 1484.00 | 619.87 | 864.13 | 1699.77 | 477.42 | 0.00 | 0.00 | 0.00 |
June | 1810.63 | 950.53 | 860.10 | 2444.61 | 266.58 | 0.00 | 0.00 | 0.00 |
July | 1646.00 | 783.78 | 862.22 | 2241.39 | 252.48 | 0.00 | 0.00 | 0.00 |
August | 1660.22 | 914.39 | 745.83 | 2241.45 | 297.51 | 0.00 | 0.00 | 0.00 |
September | 1381.39 | 750.41 | 630.98 | 1762.77 | 449.28 | 0.00 | 0.00 | 0.00 |
October | 1000.40 | 548.16 | 452.24 | 1049.57 | 941.00 | 0.00 | 0.00 | 0.00 |
November | 778.68 | 439.65 | 339.03 | 730.73 | 1088.76 | 0.00 | 0.00 | 0.00 |
December | 674.13 | 388.35 | 285.78 | 577.97 | 1294.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1229.14 | 654.35 | 574.79 | 1416.78 | 750.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 674.13 | 388.35 | 285.78 | 577.97 | 252.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1810.63 | 950.53 | 864.13 | 2444.61 | 1294.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.53 | 18.71 | 11.82 | 27.54 | 44.61 | 0.00 | 0.00 | 0.00 |
February | 40.55 | 25.60 | 14.95 | 38.70 | 45.83 | 0.00 | 0.00 | 0.00 |
March | 48.94 | 28.55 | 20.40 | 50.40 | 35.13 | 0.00 | 0.00 | 0.00 |
April | 50.19 | 24.45 | 25.74 | 50.54 | 31.01 | 0.00 | 0.00 | 0.00 |
May | 58.68 | 24.51 | 34.17 | 67.21 | 18.88 | 0.00 | 0.00 | 0.00 |
June | 71.59 | 37.58 | 34.01 | 96.66 | 10.54 | 0.00 | 0.00 | 0.00 |
July | 65.08 | 30.99 | 34.09 | 88.62 | 9.98 | 0.00 | 0.00 | 0.00 |
August | 65.64 | 36.15 | 29.49 | 88.63 | 11.76 | 0.00 | 0.00 | 0.00 |
September | 54.62 | 29.67 | 24.95 | 69.70 | 17.76 | 0.00 | 0.00 | 0.00 |
October | 39.55 | 21.67 | 17.88 | 41.50 | 37.21 | 0.00 | 0.00 | 0.00 |
November | 30.79 | 17.38 | 13.41 | 28.89 | 43.05 | 0.00 | 0.00 | 0.00 |
December | 26.65 | 15.35 | 11.30 | 22.85 | 51.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.60 | 25.87 | 22.73 | 56.02 | 29.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.65 | 15.35 | 11.30 | 22.85 | 9.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.59 | 37.58 | 34.17 | 96.66 | 51.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1228.19 | 1010.32 | 217.87 | 1415.71 | 587.54 | 0.00 | 0.00 | 0.00 |
February | 1178.06 | 939.22 | 238.84 | 1351.36 | 601.73 | 0.00 | 0.00 | 0.00 |
March | 868.56 | 571.46 | 297.10 | 1012.81 | 472.74 | 0.00 | 0.00 | 0.00 |
April | 562.54 | 226.20 | 336.34 | 602.90 | 423.57 | 0.00 | 0.00 | 0.00 |
May | 515.51 | 94.49 | 421.02 | 603.29 | 260.72 | 0.00 | 0.00 | 0.00 |
June | 475.29 | 86.87 | 388.42 | 694.48 | 145.31 | 0.00 | 0.00 | 0.00 |
July | 494.76 | 88.60 | 406.16 | 723.42 | 135.03 | 0.00 | 0.00 | 0.00 |
August | 629.93 | 263.33 | 366.60 | 920.51 | 160.20 | 0.00 | 0.00 | 0.00 |
September | 810.46 | 452.23 | 358.23 | 1106.28 | 250.60 | 0.00 | 0.00 | 0.00 |
October | 969.08 | 687.58 | 281.50 | 1178.17 | 499.32 | 0.00 | 0.00 | 0.00 |
November | 1180.68 | 941.17 | 239.51 | 1388.28 | 569.85 | 0.00 | 0.00 | 0.00 |
December | 1129.04 | 913.83 | 215.21 | 1276.76 | 654.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 834.91 | 520.58 | 314.33 | 1020.95 | 395.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 475.29 | 86.87 | 215.21 | 602.90 | 135.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1228.19 | 1010.32 | 421.02 | 1415.71 | 654.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1228.19 | 1010.32 | 217.87 | 1415.71 | 587.54 | 0.00 | 0.00 | 0.00 |
February | 1178.06 | 939.22 | 238.84 | 1351.36 | 601.73 | 0.00 | 0.00 | 0.00 |
March | 868.56 | 571.46 | 297.10 | 1012.81 | 472.74 | 0.00 | 0.00 | 0.00 |
April | 562.54 | 226.20 | 336.34 | 602.90 | 423.57 | 0.00 | 0.00 | 0.00 |
May | 515.51 | 94.49 | 421.02 | 603.29 | 260.72 | 0.00 | 0.00 | 0.00 |
June | 475.29 | 86.87 | 388.42 | 694.48 | 145.31 | 0.00 | 0.00 | 0.00 |
July | 494.76 | 88.60 | 406.16 | 723.42 | 135.03 | 0.00 | 0.00 | 0.00 |
August | 629.93 | 263.33 | 366.60 | 920.51 | 160.20 | 0.00 | 0.00 | 0.00 |
September | 810.46 | 452.23 | 358.23 | 1106.28 | 250.60 | 0.00 | 0.00 | 0.00 |
October | 969.08 | 687.58 | 281.50 | 1178.17 | 499.32 | 0.00 | 0.00 | 0.00 |
November | 1180.68 | 941.17 | 239.51 | 1388.28 | 569.85 | 0.00 | 0.00 | 0.00 |
December | 1129.04 | 913.83 | 215.21 | 1276.76 | 654.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 834.91 | 520.58 | 314.33 | 1020.95 | 395.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 475.29 | 86.87 | 215.21 | 602.90 | 135.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1228.19 | 1010.32 | 421.02 | 1415.71 | 654.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1228.11 | 1010.25 | 217.86 | 1415.62 | 587.50 | 0.00 | 0.00 | 0.00 |
February | 1177.99 | 939.16 | 238.82 | 1351.28 | 601.69 | 0.00 | 0.00 | 0.00 |
March | 868.50 | 571.42 | 297.08 | 1012.74 | 472.71 | 0.00 | 0.00 | 0.00 |
April | 562.51 | 226.19 | 336.32 | 602.86 | 423.54 | 0.00 | 0.00 | 0.00 |
May | 515.48 | 94.48 | 421.00 | 603.25 | 260.70 | 0.00 | 0.00 | 0.00 |
June | 475.26 | 86.86 | 388.39 | 694.44 | 145.30 | 0.00 | 0.00 | 0.00 |
July | 494.73 | 88.59 | 406.14 | 723.37 | 135.02 | 0.00 | 0.00 | 0.00 |
August | 629.89 | 263.32 | 366.57 | 920.45 | 160.19 | 0.00 | 0.00 | 0.00 |
September | 810.41 | 452.20 | 358.21 | 1106.21 | 250.58 | 0.00 | 0.00 | 0.00 |
October | 969.01 | 687.54 | 281.48 | 1178.09 | 499.29 | 0.00 | 0.00 | 0.00 |
November | 1180.61 | 941.11 | 239.49 | 1388.20 | 569.81 | 0.00 | 0.00 | 0.00 |
December | 1128.97 | 913.77 | 215.20 | 1276.68 | 653.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 834.86 | 520.54 | 314.31 | 1020.89 | 395.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 475.26 | 86.86 | 215.20 | 602.86 | 135.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1228.11 | 1010.25 | 421.00 | 1415.62 | 653.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 821.28 | 520.41 | 300.88 | 796.71 | 1158.88 | 0.00 | 0.00 | 0.00 |
February | 990.35 | 613.72 | 376.63 | 953.15 | 1177.30 | 0.00 | 0.00 | 0.00 |
March | 1159.64 | 639.80 | 519.84 | 1188.31 | 904.36 | 0.00 | 0.00 | 0.00 |
April | 1091.86 | 462.27 | 629.58 | 1068.15 | 801.19 | 0.00 | 0.00 | 0.00 |
May | 1334.53 | 470.47 | 864.06 | 1534.07 | 506.06 | 0.00 | 0.00 | 0.00 |
June | 1632.21 | 785.32 | 846.89 | 2234.41 | 300.10 | 0.00 | 0.00 | 0.00 |
July | 1329.86 | 487.10 | 842.76 | 1828.02 | 271.14 | 0.00 | 0.00 | 0.00 |
August | 1388.00 | 685.69 | 702.31 | 1875.25 | 312.80 | 0.00 | 0.00 | 0.00 |
September | 1230.74 | 590.22 | 640.52 | 1582.58 | 479.93 | 0.00 | 0.00 | 0.00 |
October | 1035.38 | 591.79 | 443.58 | 1120.48 | 960.22 | 0.00 | 0.00 | 0.00 |
November | 849.58 | 515.80 | 333.78 | 834.69 | 1104.78 | 0.00 | 0.00 | 0.00 |
December | 686.23 | 405.37 | 280.86 | 606.19 | 1302.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1129.49 | 563.32 | 566.17 | 1303.30 | 771.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.23 | 405.37 | 280.86 | 606.19 | 271.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1632.21 | 785.32 | 864.06 | 2234.41 | 1302.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.47 | 20.58 | 11.90 | 31.50 | 45.82 | 0.00 | 0.00 | 0.00 |
February | 39.16 | 24.27 | 14.89 | 37.69 | 46.55 | 0.00 | 0.00 | 0.00 |
March | 45.85 | 25.30 | 20.55 | 46.98 | 35.76 | 0.00 | 0.00 | 0.00 |
April | 43.17 | 18.28 | 24.89 | 42.23 | 31.68 | 0.00 | 0.00 | 0.00 |
May | 52.77 | 18.60 | 34.16 | 60.66 | 20.01 | 0.00 | 0.00 | 0.00 |
June | 64.54 | 31.05 | 33.49 | 88.35 | 11.87 | 0.00 | 0.00 | 0.00 |
July | 52.58 | 19.26 | 33.32 | 72.28 | 10.72 | 0.00 | 0.00 | 0.00 |
August | 54.88 | 27.11 | 27.77 | 74.15 | 12.37 | 0.00 | 0.00 | 0.00 |
September | 48.66 | 23.34 | 25.33 | 62.57 | 18.98 | 0.00 | 0.00 | 0.00 |
October | 40.94 | 23.40 | 17.54 | 44.30 | 37.97 | 0.00 | 0.00 | 0.00 |
November | 33.59 | 20.39 | 13.20 | 33.00 | 43.68 | 0.00 | 0.00 | 0.00 |
December | 27.13 | 16.03 | 11.10 | 23.97 | 51.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.66 | 22.27 | 22.39 | 51.53 | 30.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.13 | 16.03 | 11.10 | 23.97 | 10.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.54 | 31.05 | 34.16 | 88.35 | 51.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 384.46 | 0.00 | 384.46 | 70.53 | 1902.98 | 0.00 | 0.00 | 0.00 |
February | 483.22 | 0.00 | 483.22 | 88.36 | 1920.39 | 0.00 | 0.00 | 0.00 |
March | 657.51 | 0.00 | 657.51 | 296.87 | 1467.63 | 0.00 | 0.00 | 0.00 |
April | 825.73 | 4.58 | 821.15 | 451.31 | 1274.15 | 0.00 | 0.00 | 0.00 |
May | 1128.00 | 37.29 | 1090.72 | 1012.17 | 755.03 | 0.00 | 0.00 | 0.00 |
June | 1236.93 | 137.13 | 1099.80 | 1645.04 | 413.84 | 0.00 | 0.00 | 0.00 |
July | 1169.80 | 75.72 | 1094.08 | 1574.70 | 391.89 | 0.00 | 0.00 | 0.00 |
August | 931.07 | 22.03 | 909.05 | 1196.69 | 451.87 | 0.00 | 0.00 | 0.00 |
September | 782.10 | 0.18 | 781.92 | 881.03 | 705.09 | 0.00 | 0.00 | 0.00 |
October | 560.17 | 0.00 | 560.17 | 299.15 | 1465.27 | 0.00 | 0.00 | 0.00 |
November | 425.24 | 0.00 | 425.24 | 114.43 | 1734.80 | 0.00 | 0.00 | 0.00 |
December | 359.71 | 0.00 | 359.71 | 61.90 | 2117.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 746.69 | 23.13 | 723.56 | 644.11 | 1212.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 359.71 | 0.00 | 359.71 | 61.90 | 391.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1236.93 | 137.13 | 1099.80 | 1645.04 | 2117.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 802.58 | 491.85 | 310.74 | 708.82 | 1192.14 | 0.00 | 0.00 | 0.00 |
February | 1066.14 | 673.05 | 393.09 | 998.01 | 1227.40 | 0.00 | 0.00 | 0.00 |
March | 1286.81 | 750.58 | 536.22 | 1300.93 | 942.31 | 0.00 | 0.00 | 0.00 |
April | 1319.69 | 642.84 | 676.85 | 1304.94 | 829.22 | 0.00 | 0.00 | 0.00 |
May | 1542.70 | 644.39 | 898.31 | 1739.76 | 508.91 | 0.00 | 0.00 | 0.00 |
June | 1882.25 | 988.13 | 894.12 | 2523.64 | 278.53 | 0.00 | 0.00 | 0.00 |
July | 1711.11 | 814.79 | 896.32 | 2313.95 | 263.94 | 0.00 | 0.00 | 0.00 |
August | 1725.89 | 950.56 | 775.33 | 2319.50 | 303.24 | 0.00 | 0.00 | 0.00 |
September | 1436.03 | 780.09 | 655.94 | 1826.40 | 452.04 | 0.00 | 0.00 | 0.00 |
October | 1039.97 | 569.84 | 470.13 | 1084.48 | 954.95 | 0.00 | 0.00 | 0.00 |
November | 809.48 | 457.04 | 352.44 | 752.84 | 1117.25 | 0.00 | 0.00 | 0.00 |
December | 700.80 | 403.71 | 297.09 | 592.68 | 1340.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1277.76 | 680.24 | 597.52 | 1457.65 | 781.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 700.80 | 403.71 | 297.09 | 592.68 | 263.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1882.25 | 988.13 | 898.31 | 2523.64 | 1340.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3684.63 | 3031.01 | 653.63 | 4213.06 | 1728.38 | 0.00 | 0.00 | 0.00 |
February | 3534.25 | 2817.72 | 716.52 | 4005.31 | 1795.80 | 0.00 | 0.00 | 0.00 |
March | 2605.72 | 1714.42 | 891.30 | 2992.15 | 1439.46 | 0.00 | 0.00 | 0.00 |
April | 1687.66 | 678.61 | 1009.04 | 1762.92 | 1310.50 | 0.00 | 0.00 | 0.00 |
May | 1546.55 | 283.47 | 1263.08 | 1759.26 | 828.66 | 0.00 | 0.00 | 0.00 |
June | 1425.87 | 260.61 | 1165.26 | 2056.41 | 455.15 | 0.00 | 0.00 | 0.00 |
July | 1484.30 | 265.80 | 1218.50 | 2145.74 | 421.70 | 0.00 | 0.00 | 0.00 |
August | 1889.81 | 790.01 | 1099.80 | 2746.49 | 477.60 | 0.00 | 0.00 | 0.00 |
September | 2431.43 | 1356.72 | 1074.70 | 3309.54 | 722.29 | 0.00 | 0.00 | 0.00 |
October | 2907.28 | 2062.78 | 844.50 | 3519.15 | 1448.31 | 0.00 | 0.00 | 0.00 |
November | 3542.11 | 2823.58 | 718.53 | 4137.81 | 1654.31 | 0.00 | 0.00 | 0.00 |
December | 3387.18 | 2741.54 | 645.64 | 3795.52 | 1923.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2504.77 | 1561.76 | 943.01 | 3031.40 | 1180.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1425.87 | 260.61 | 645.64 | 1759.26 | 421.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3684.63 | 3031.01 | 1263.08 | 4213.06 | 1923.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 853.77 | 540.99 | 312.77 | 813.69 | 1220.93 | 0.00 | 0.00 | 0.00 |
February | 1029.52 | 638.00 | 391.52 | 972.45 | 1244.13 | 0.00 | 0.00 | 0.00 |
March | 1205.51 | 665.11 | 540.40 | 1211.84 | 962.97 | 0.00 | 0.00 | 0.00 |
April | 1135.04 | 480.56 | 654.48 | 1088.26 | 851.44 | 0.00 | 0.00 | 0.00 |
May | 1387.31 | 489.08 | 898.23 | 1569.77 | 542.00 | 0.00 | 0.00 | 0.00 |
June | 1696.77 | 816.38 | 880.39 | 2309.24 | 313.36 | 0.00 | 0.00 | 0.00 |
July | 1382.46 | 506.37 | 876.09 | 1886.73 | 286.82 | 0.00 | 0.00 | 0.00 |
August | 1442.90 | 712.81 | 730.09 | 1941.64 | 321.42 | 0.00 | 0.00 | 0.00 |
September | 1279.42 | 613.57 | 665.85 | 1642.20 | 484.12 | 0.00 | 0.00 | 0.00 |
October | 1076.33 | 615.20 | 461.13 | 1161.80 | 973.55 | 0.00 | 0.00 | 0.00 |
November | 883.19 | 536.20 | 346.98 | 862.67 | 1130.85 | 0.00 | 0.00 | 0.00 |
December | 713.37 | 421.41 | 291.96 | 622.87 | 1345.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1174.16 | 585.60 | 588.56 | 1341.80 | 804.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 713.37 | 421.41 | 291.96 | 622.87 | 286.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1696.77 | 816.38 | 898.23 | 2309.24 | 1345.86 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102974E+10 | 0.00 | 0.102974E+10 | 0.213781E+09 | 0.482535E+10 |
February | 0.116901E+10 | 0.00 | 0.116901E+10 | 0.232537E+09 | 0.443685E+10 |
March | 0.176107E+10 | 0.00 | 0.176107E+10 | 0.819642E+09 | 0.373599E+10 |
April | 0.214030E+10 | 11873484.46 | 0.212843E+10 | 0.119559E+10 | 0.310799E+10 |
May | 0.302124E+10 | 99870170.09 | 0.292137E+10 | 0.273395E+10 | 0.195179E+10 |
June | 0.320613E+10 | 0.355452E+09 | 0.285068E+10 | 0.425469E+10 | 0.105049E+10 |
July | 0.313320E+10 | 0.202818E+09 | 0.293038E+10 | 0.420598E+10 | 0.102935E+10 |
August | 0.249379E+10 | 58994652.25 | 0.243479E+10 | 0.319912E+10 | 0.117637E+10 |
September | 0.202721E+10 | 476155.58 | 0.202673E+10 | 0.229295E+10 | 0.175364E+10 |
October | 0.150037E+10 | 0.00 | 0.150037E+10 | 0.834394E+09 | 0.370721E+10 |
November | 0.110223E+10 | 0.00 | 0.110223E+10 | 0.327208E+09 | 0.424810E+10 |
December | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.183351E+09 | 0.541548E+10 |
Annual Sum or Average | 0.235478E+11 | 0.729484E+09 | 0.228183E+11 | 0.204932E+11 | 0.364386E+11 |
Minimum of Months | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.183351E+09 | 0.102935E+10 |
Maximum of Months | 0.320613E+10 | 0.355452E+09 | 0.293038E+10 | 0.425469E+10 | 0.541548E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214964E+10 | 0.131736E+10 | 0.832275E+09 | 0.194038E+10 | 0.302895E+10 |
February | 0.257921E+10 | 0.162825E+10 | 0.950966E+09 | 0.244070E+10 | 0.284176E+10 |
March | 0.344658E+10 | 0.201036E+10 | 0.143622E+10 | 0.350834E+10 | 0.240606E+10 |
April | 0.342063E+10 | 0.166625E+10 | 0.175438E+10 | 0.340549E+10 | 0.202789E+10 |
May | 0.413195E+10 | 0.172593E+10 | 0.240602E+10 | 0.467773E+10 | 0.132022E+10 |
June | 0.487878E+10 | 0.256123E+10 | 0.231755E+10 | 0.654016E+10 | 0.706756E+09 |
July | 0.458304E+10 | 0.218233E+10 | 0.240071E+10 | 0.619533E+10 | 0.692436E+09 |
August | 0.462263E+10 | 0.254598E+10 | 0.207665E+10 | 0.621399E+10 | 0.789689E+09 |
September | 0.372219E+10 | 0.202200E+10 | 0.170019E+10 | 0.474499E+10 | 0.112904E+10 |
October | 0.278546E+10 | 0.152627E+10 | 0.125919E+10 | 0.292945E+10 | 0.242647E+10 |
November | 0.209818E+10 | 0.118466E+10 | 0.913528E+09 | 0.198838E+10 | 0.274224E+10 |
December | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.162018E+10 | 0.343229E+10 |
Annual Sum or Average | 0.402953E+11 | 0.214519E+11 | 0.188434E+11 | 0.462051E+11 | 0.235438E+11 |
Minimum of Months | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.162018E+10 | 0.692436E+09 |
Maximum of Months | 0.487878E+10 | 0.256123E+10 | 0.240602E+10 | 0.654016E+10 | 0.343229E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.986892E+10 | 0.811825E+10 | 0.175067E+10 | 0.113404E+11 | 0.440572E+10 |
February | 0.855005E+10 | 0.681664E+10 | 0.173341E+10 | 0.971992E+10 | 0.415603E+10 |
March | 0.697916E+10 | 0.459189E+10 | 0.238727E+10 | 0.803637E+10 | 0.367262E+10 |
April | 0.437441E+10 | 0.175897E+10 | 0.261544E+10 | 0.459114E+10 | 0.320277E+10 |
May | 0.414228E+10 | 0.759251E+09 | 0.338303E+10 | 0.472283E+10 | 0.213998E+10 |
June | 0.369585E+10 | 0.675498E+09 | 0.302035E+10 | 0.531597E+10 | 0.115025E+10 |
July | 0.397554E+10 | 0.711908E+09 | 0.326363E+10 | 0.573145E+10 | 0.110331E+10 |
August | 0.506167E+10 | 0.211597E+10 | 0.294570E+10 | 0.734430E+10 | 0.124192E+10 |
September | 0.630226E+10 | 0.351663E+10 | 0.278563E+10 | 0.857916E+10 | 0.180158E+10 |
October | 0.778685E+10 | 0.552495E+10 | 0.226190E+10 | 0.945237E+10 | 0.368427E+10 |
November | 0.918115E+10 | 0.731871E+10 | 0.186244E+10 | 0.107678E+11 | 0.407473E+10 |
December | 0.907223E+10 | 0.734294E+10 | 0.172929E+10 | 0.102129E+11 | 0.492097E+10 |
Annual Sum or Average | 0.789904E+11 | 0.492516E+11 | 0.297388E+11 | 0.958146E+11 | 0.355542E+11 |
Minimum of Months | 0.369585E+10 | 0.675498E+09 | 0.172929E+10 | 0.459114E+10 | 0.110331E+10 |
Maximum of Months | 0.986892E+10 | 0.811825E+10 | 0.338303E+10 | 0.113404E+11 | 0.492097E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228674E+10 | 0.144900E+10 | 0.837735E+09 | 0.220335E+10 | 0.309949E+10 |
February | 0.249063E+10 | 0.154345E+10 | 0.947175E+09 | 0.236704E+10 | 0.287399E+10 |
March | 0.322883E+10 | 0.178142E+10 | 0.144741E+10 | 0.325991E+10 | 0.245092E+10 |
April | 0.294203E+10 | 0.124560E+10 | 0.169642E+10 | 0.283684E+10 | 0.207802E+10 |
May | 0.371577E+10 | 0.130995E+10 | 0.240582E+10 | 0.421153E+10 | 0.139886E+10 |
June | 0.439802E+10 | 0.211606E+10 | 0.228196E+10 | 0.597453E+10 | 0.791656E+09 |
July | 0.370279E+10 | 0.135626E+10 | 0.234652E+10 | 0.504231E+10 | 0.750240E+09 |
August | 0.386466E+10 | 0.190920E+10 | 0.195546E+10 | 0.519296E+10 | 0.835795E+09 |
September | 0.331625E+10 | 0.159036E+10 | 0.172589E+10 | 0.425960E+10 | 0.120566E+10 |
October | 0.288284E+10 | 0.164776E+10 | 0.123508E+10 | 0.313147E+10 | 0.246819E+10 |
November | 0.228922E+10 | 0.138984E+10 | 0.899379E+09 | 0.226011E+10 | 0.277330E+10 |
December | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.168690E+10 | 0.344181E+10 |
Annual Sum or Average | 0.370285E+11 | 0.184676E+11 | 0.185609E+11 | 0.424266E+11 | 0.241679E+11 |
Minimum of Months | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.168690E+10 | 0.750240E+09 |
Maximum of Months | 0.439802E+10 | 0.211606E+10 | 0.240582E+10 | 0.597453E+10 | 0.344181E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.343232E+09 | 0.00 | 0.343232E+09 | 73547455.63 | 0.163973E+10 |
February | 0.389652E+09 | 0.00 | 0.389652E+09 | 85923504.28 | 0.148932E+10 |
March | 0.586995E+09 | 0.00 | 0.586995E+09 | 0.297095E+09 | 0.124456E+10 |
April | 0.713401E+09 | 3957640.90 | 0.709443E+09 | 0.423842E+09 | 0.104509E+10 |
May | 0.100703E+10 | 33288481.68 | 0.973745E+09 | 0.946430E+09 | 0.635092E+09 |
June | 0.106866E+10 | 0.118478E+09 | 0.950182E+09 | 0.144626E+10 | 0.340636E+09 |
July | 0.104435E+10 | 67602645.39 | 0.976748E+09 | 0.142954E+10 | 0.331946E+09 |
August | 0.831224E+09 | 19663953.70 | 0.811560E+09 | 0.108170E+10 | 0.391652E+09 |
September | 0.675704E+09 | 158711.02 | 0.675546E+09 | 0.766659E+09 | 0.608387E+09 |
October | 0.500100E+09 | 0.00 | 0.500100E+09 | 0.272811E+09 | 0.130850E+10 |
November | 0.367392E+09 | 0.00 | 0.367392E+09 | 0.103548E+09 | 0.148971E+10 |
December | 0.321136E+09 | 0.00 | 0.321136E+09 | 59236271.27 | 0.187288E+10 |
Annual Sum or Average | 0.784888E+10 | 0.243150E+09 | 0.760573E+10 | 0.698659E+10 | 0.123975E+11 |
Minimum of Months | 0.321136E+09 | 0.00 | 0.321136E+09 | 59236271.27 | 0.331946E+09 |
Maximum of Months | 0.106866E+10 | 0.118478E+09 | 0.976748E+09 | 0.144626E+10 | 0.187288E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.343246E+09 | 0.00 | 0.343246E+09 | 73548358.88 | 0.163983E+10 |
February | 0.389669E+09 | 0.00 | 0.389669E+09 | 85925157.47 | 0.148941E+10 |
March | 0.587020E+09 | 0.00 | 0.587020E+09 | 0.297104E+09 | 0.124464E+10 |
April | 0.713429E+09 | 3957747.28 | 0.709472E+09 | 0.423854E+09 | 0.104516E+10 |
May | 0.100707E+10 | 33289376.48 | 0.973784E+09 | 0.946460E+09 | 0.635131E+09 |
June | 0.106870E+10 | 0.118481E+09 | 0.950222E+09 | 0.144632E+10 | 0.340654E+09 |
July | 0.104439E+10 | 67604462.56 | 0.976787E+09 | 0.142960E+10 | 0.331964E+09 |
August | 0.831259E+09 | 19664482.27 | 0.811595E+09 | 0.108174E+10 | 0.391674E+09 |
September | 0.675733E+09 | 158715.28 | 0.675574E+09 | 0.766692E+09 | 0.608422E+09 |
October | 0.500121E+09 | 0.00 | 0.500121E+09 | 0.272821E+09 | 0.130858E+10 |
November | 0.367408E+09 | 0.00 | 0.367408E+09 | 0.103550E+09 | 0.148981E+10 |
December | 0.321149E+09 | 0.00 | 0.321149E+09 | 59237566.50 | 0.187300E+10 |
Annual Sum or Average | 0.784920E+10 | 0.243156E+09 | 0.760605E+10 | 0.698686E+10 | 0.123983E+11 |
Minimum of Months | 0.321149E+09 | 0.00 | 0.321149E+09 | 59237566.50 | 0.331964E+09 |
Maximum of Months | 0.106870E+10 | 0.118481E+09 | 0.976787E+09 | 0.144632E+10 | 0.187300E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.343246E+09 | 0.00 | 0.343246E+09 | 73548358.88 | 0.163983E+10 |
February | 0.389669E+09 | 0.00 | 0.389669E+09 | 85925157.47 | 0.148941E+10 |
March | 0.587020E+09 | 0.00 | 0.587020E+09 | 0.297104E+09 | 0.124464E+10 |
April | 0.713429E+09 | 3957747.28 | 0.709472E+09 | 0.423854E+09 | 0.104516E+10 |
May | 0.100707E+10 | 33289376.48 | 0.973784E+09 | 0.946460E+09 | 0.635131E+09 |
June | 0.106870E+10 | 0.118481E+09 | 0.950222E+09 | 0.144632E+10 | 0.340654E+09 |
July | 0.104439E+10 | 67604462.56 | 0.976787E+09 | 0.142960E+10 | 0.331964E+09 |
August | 0.831259E+09 | 19664482.27 | 0.811595E+09 | 0.108174E+10 | 0.391674E+09 |
September | 0.675733E+09 | 158715.28 | 0.675574E+09 | 0.766692E+09 | 0.608422E+09 |
October | 0.500121E+09 | 0.00 | 0.500121E+09 | 0.272821E+09 | 0.130858E+10 |
November | 0.367408E+09 | 0.00 | 0.367408E+09 | 0.103550E+09 | 0.148981E+10 |
December | 0.321149E+09 | 0.00 | 0.321149E+09 | 59237566.50 | 0.187300E+10 |
Annual Sum or Average | 0.784920E+10 | 0.243156E+09 | 0.760605E+10 | 0.698686E+10 | 0.123983E+11 |
Minimum of Months | 0.321149E+09 | 0.00 | 0.321149E+09 | 59237566.50 | 0.331964E+09 |
Maximum of Months | 0.106870E+10 | 0.118481E+09 | 0.976787E+09 | 0.144632E+10 | 0.187300E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206784E+10 | 0.126723E+10 | 0.800611E+09 | 0.186591E+10 | 0.302168E+10 |
February | 0.248107E+10 | 0.156629E+10 | 0.914786E+09 | 0.236781E+10 | 0.280394E+10 |
March | 0.331543E+10 | 0.193386E+10 | 0.138158E+10 | 0.341442E+10 | 0.237964E+10 |
April | 0.329048E+10 | 0.160284E+10 | 0.168763E+10 | 0.331312E+10 | 0.203305E+10 |
May | 0.397473E+10 | 0.166025E+10 | 0.231448E+10 | 0.455267E+10 | 0.127871E+10 |
June | 0.469314E+10 | 0.246377E+10 | 0.222938E+10 | 0.633643E+10 | 0.690984E+09 |
July | 0.440866E+10 | 0.209929E+10 | 0.230937E+10 | 0.600334E+10 | 0.676238E+09 |
August | 0.444673E+10 | 0.244909E+10 | 0.199764E+10 | 0.600351E+10 | 0.796844E+09 |
September | 0.358056E+10 | 0.194505E+10 | 0.163550E+10 | 0.456909E+10 | 0.116453E+10 |
October | 0.267947E+10 | 0.146819E+10 | 0.121128E+10 | 0.281117E+10 | 0.252039E+10 |
November | 0.201835E+10 | 0.113957E+10 | 0.878772E+09 | 0.189405E+10 | 0.282208E+10 |
December | 0.180559E+10 | 0.104015E+10 | 0.765447E+09 | 0.154802E+10 | 0.346786E+10 |
Annual Sum or Average | 0.387621E+11 | 0.206356E+11 | 0.181265E+11 | 0.446796E+11 | 0.236559E+11 |
Minimum of Months | 0.180559E+10 | 0.104015E+10 | 0.765447E+09 | 0.154802E+10 | 0.676238E+09 |
Maximum of Months | 0.469314E+10 | 0.246377E+10 | 0.231448E+10 | 0.633643E+10 | 0.346786E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81760686.43 | 50105254.26 | 31655432.17 | 73776515.83 | 0.119475E+09 |
February | 98099357.20 | 61929538.73 | 36169818.47 | 93621134.46 | 0.110865E+09 |
March | 0.131089E+09 | 76462961.31 | 54626324.10 | 0.135003E+09 | 94088970.95 |
April | 0.130102E+09 | 63374965.96 | 66727507.05 | 0.130998E+09 | 80384869.84 |
May | 0.157157E+09 | 65644977.66 | 91512381.12 | 0.180008E+09 | 50559102.08 |
June | 0.185563E+09 | 97415121.80 | 88147574.49 | 0.250537E+09 | 27320871.72 |
July | 0.174314E+09 | 83003846.61 | 91310418.94 | 0.237367E+09 | 26737853.60 |
August | 0.175820E+09 | 96834891.99 | 78984946.19 | 0.237373E+09 | 31506504.70 |
September | 0.141572E+09 | 76905604.65 | 64666355.52 | 0.180658E+09 | 46044435.13 |
October | 0.105944E+09 | 58050904.71 | 47892977.97 | 0.111151E+09 | 99653826.57 |
November | 79803621.74 | 45057757.81 | 34745863.93 | 74888966.80 | 0.111582E+09 |
December | 71391537.52 | 41126470.69 | 30265066.83 | 61207416.05 | 0.137116E+09 |
Annual Sum or Average | 0.153262E+10 | 0.815912E+09 | 0.716705E+09 | 0.176659E+10 | 0.935335E+09 |
Minimum of Months | 71391537.52 | 41126470.69 | 30265066.83 | 61207416.05 | 26737853.60 |
Maximum of Months | 0.185563E+09 | 97415121.80 | 91512381.12 | 0.250537E+09 | 0.137116E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.328958E+10 | 0.270603E+10 | 0.583550E+09 | 0.379185E+10 | 0.157366E+10 |
February | 0.284996E+10 | 0.227217E+10 | 0.577798E+09 | 0.326921E+10 | 0.145571E+10 |
March | 0.232635E+10 | 0.153060E+10 | 0.795748E+09 | 0.271271E+10 | 0.126618E+10 |
April | 0.145812E+10 | 0.586310E+09 | 0.871805E+09 | 0.156271E+10 | 0.109789E+10 |
May | 0.138075E+10 | 0.253078E+09 | 0.112767E+10 | 0.161586E+10 | 0.698314E+09 |
June | 0.123194E+10 | 0.225161E+09 | 0.100678E+10 | 0.180010E+10 | 0.376649E+09 |
July | 0.132517E+10 | 0.237298E+09 | 0.108787E+10 | 0.193760E+10 | 0.361654E+09 |
August | 0.168720E+10 | 0.705309E+09 | 0.981894E+09 | 0.246550E+10 | 0.429083E+09 |
September | 0.210072E+10 | 0.117218E+10 | 0.928536E+09 | 0.286749E+10 | 0.649543E+09 |
October | 0.259557E+10 | 0.184161E+10 | 0.753960E+09 | 0.315560E+10 | 0.133738E+10 |
November | 0.306033E+10 | 0.243952E+10 | 0.620807E+09 | 0.359843E+10 | 0.147704E+10 |
December | 0.302402E+10 | 0.244760E+10 | 0.576423E+09 | 0.341967E+10 | 0.175175E+10 |
Annual Sum or Average | 0.263297E+11 | 0.164169E+11 | 0.991283E+10 | 0.321967E+11 | 0.124749E+11 |
Minimum of Months | 0.123194E+10 | 0.225161E+09 | 0.576423E+09 | 0.156271E+10 | 0.361654E+09 |
Maximum of Months | 0.328958E+10 | 0.270603E+10 | 0.112767E+10 | 0.379185E+10 | 0.175175E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.328958E+10 | 0.270603E+10 | 0.583550E+09 | 0.379185E+10 | 0.157366E+10 |
February | 0.284996E+10 | 0.227217E+10 | 0.577798E+09 | 0.326921E+10 | 0.145571E+10 |
March | 0.232635E+10 | 0.153060E+10 | 0.795748E+09 | 0.271271E+10 | 0.126618E+10 |
April | 0.145812E+10 | 0.586310E+09 | 0.871805E+09 | 0.156271E+10 | 0.109789E+10 |
May | 0.138075E+10 | 0.253078E+09 | 0.112767E+10 | 0.161586E+10 | 0.698314E+09 |
June | 0.123194E+10 | 0.225161E+09 | 0.100678E+10 | 0.180010E+10 | 0.376649E+09 |
July | 0.132517E+10 | 0.237298E+09 | 0.108787E+10 | 0.193760E+10 | 0.361654E+09 |
August | 0.168720E+10 | 0.705309E+09 | 0.981894E+09 | 0.246550E+10 | 0.429083E+09 |
September | 0.210072E+10 | 0.117218E+10 | 0.928536E+09 | 0.286749E+10 | 0.649543E+09 |
October | 0.259557E+10 | 0.184161E+10 | 0.753960E+09 | 0.315560E+10 | 0.133738E+10 |
November | 0.306033E+10 | 0.243952E+10 | 0.620807E+09 | 0.359843E+10 | 0.147704E+10 |
December | 0.302402E+10 | 0.244760E+10 | 0.576423E+09 | 0.341967E+10 | 0.175175E+10 |
Annual Sum or Average | 0.263297E+11 | 0.164169E+11 | 0.991283E+10 | 0.321967E+11 | 0.124749E+11 |
Minimum of Months | 0.123194E+10 | 0.225161E+09 | 0.576423E+09 | 0.156271E+10 | 0.361654E+09 |
Maximum of Months | 0.328958E+10 | 0.270603E+10 | 0.112767E+10 | 0.379185E+10 | 0.175175E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.328937E+10 | 0.270586E+10 | 0.583513E+09 | 0.379161E+10 | 0.157356E+10 |
February | 0.284978E+10 | 0.227202E+10 | 0.577762E+09 | 0.326901E+10 | 0.145562E+10 |
March | 0.232620E+10 | 0.153050E+10 | 0.795698E+09 | 0.271254E+10 | 0.126610E+10 |
April | 0.145802E+10 | 0.586273E+09 | 0.871750E+09 | 0.156262E+10 | 0.109782E+10 |
May | 0.138066E+10 | 0.253062E+09 | 0.112760E+10 | 0.161576E+10 | 0.698270E+09 |
June | 0.123186E+10 | 0.225147E+09 | 0.100672E+10 | 0.179998E+10 | 0.376625E+09 |
July | 0.132508E+10 | 0.237283E+09 | 0.108780E+10 | 0.193748E+10 | 0.361632E+09 |
August | 0.168710E+10 | 0.705264E+09 | 0.981832E+09 | 0.246534E+10 | 0.429056E+09 |
September | 0.210059E+10 | 0.117211E+10 | 0.928477E+09 | 0.286730E+10 | 0.649502E+09 |
October | 0.259541E+10 | 0.184149E+10 | 0.753912E+09 | 0.315540E+10 | 0.133730E+10 |
November | 0.306013E+10 | 0.243937E+10 | 0.620768E+09 | 0.359821E+10 | 0.147695E+10 |
December | 0.302383E+10 | 0.244744E+10 | 0.576387E+09 | 0.341945E+10 | 0.175164E+10 |
Annual Sum or Average | 0.263280E+11 | 0.164158E+11 | 0.991221E+10 | 0.321947E+11 | 0.124741E+11 |
Minimum of Months | 0.123186E+10 | 0.225147E+09 | 0.576387E+09 | 0.156262E+10 | 0.361632E+09 |
Maximum of Months | 0.328937E+10 | 0.270586E+10 | 0.112760E+10 | 0.379161E+10 | 0.175164E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219973E+10 | 0.139386E+10 | 0.805865E+09 | 0.213392E+10 | 0.310394E+10 |
February | 0.239586E+10 | 0.148472E+10 | 0.911142E+09 | 0.230585E+10 | 0.284814E+10 |
March | 0.310598E+10 | 0.171363E+10 | 0.139235E+10 | 0.318277E+10 | 0.242224E+10 |
April | 0.283009E+10 | 0.119821E+10 | 0.163188E+10 | 0.276864E+10 | 0.207669E+10 |
May | 0.357440E+10 | 0.126010E+10 | 0.231429E+10 | 0.410886E+10 | 0.135544E+10 |
June | 0.423068E+10 | 0.203554E+10 | 0.219515E+10 | 0.579160E+10 | 0.777866E+09 |
July | 0.356191E+10 | 0.130466E+10 | 0.225725E+10 | 0.489617E+10 | 0.726212E+09 |
August | 0.371762E+10 | 0.183655E+10 | 0.188107E+10 | 0.502267E+10 | 0.837797E+09 |
September | 0.319008E+10 | 0.152985E+10 | 0.166023E+10 | 0.410204E+10 | 0.124399E+10 |
October | 0.277316E+10 | 0.158506E+10 | 0.118810E+10 | 0.300111E+10 | 0.257186E+10 |
November | 0.220212E+10 | 0.133695E+10 | 0.865163E+09 | 0.216352E+10 | 0.286359E+10 |
December | 0.183800E+10 | 0.108575E+10 | 0.752247E+09 | 0.162361E+10 | 0.348737E+10 |
Annual Sum or Average | 0.356196E+11 | 0.177649E+11 | 0.178547E+11 | 0.411008E+11 | 0.243151E+11 |
Minimum of Months | 0.183800E+10 | 0.108575E+10 | 0.752247E+09 | 0.162361E+10 | 0.726212E+09 |
Maximum of Months | 0.423068E+10 | 0.203554E+10 | 0.231429E+10 | 0.579160E+10 | 0.348737E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86975063.61 | 55111960.46 | 31863103.15 | 84372988.21 | 0.122727E+09 |
February | 94730006.39 | 58704353.86 | 36025652.54 | 91170833.26 | 0.112613E+09 |
March | 0.122807E+09 | 67755274.10 | 55052016.37 | 0.125843E+09 | 95773236.45 |
April | 0.111899E+09 | 47375869.14 | 64522999.00 | 0.109469E+09 | 82110301.23 |
May | 0.141328E+09 | 49823187.03 | 91504875.63 | 0.162460E+09 | 53592961.49 |
June | 0.167277E+09 | 80483061.54 | 86793885.65 | 0.228994E+09 | 30756088.99 |
July | 0.140834E+09 | 51584726.00 | 89249486.79 | 0.193590E+09 | 28713761.67 |
August | 0.146991E+09 | 72615278.85 | 74375646.53 | 0.198591E+09 | 33125731.20 |
September | 0.126132E+09 | 60488701.33 | 65643764.97 | 0.162191E+09 | 49186123.17 |
October | 0.109648E+09 | 62671682.37 | 46976140.24 | 0.118661E+09 | 0.101689E+09 |
November | 87069489.53 | 52861796.30 | 34207693.24 | 85543378.68 | 0.113224E+09 |
December | 72672600.43 | 42929506.76 | 29743093.67 | 64195754.34 | 0.137887E+09 |
Annual Sum or Average | 0.140836E+10 | 0.702405E+09 | 0.705958E+09 | 0.162508E+10 | 0.961398E+09 |
Minimum of Months | 72672600.43 | 42929506.76 | 29743093.67 | 64195754.34 | 28713761.67 |
Maximum of Months | 0.167277E+09 | 80483061.54 | 91504875.63 | 0.228994E+09 | 0.137887E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102974E+10 | 0.00 | 0.102974E+10 | 0.188904E+09 | 0.509694E+10 |
February | 0.116901E+10 | 0.00 | 0.116901E+10 | 0.213763E+09 | 0.464580E+10 |
March | 0.176107E+10 | 0.00 | 0.176107E+10 | 0.795149E+09 | 0.393089E+10 |
April | 0.214030E+10 | 11873484.46 | 0.212843E+10 | 0.116978E+10 | 0.330260E+10 |
May | 0.302124E+10 | 99870170.09 | 0.292137E+10 | 0.271099E+10 | 0.202227E+10 |
June | 0.320613E+10 | 0.355452E+09 | 0.285068E+10 | 0.426394E+10 | 0.107266E+10 |
July | 0.313320E+10 | 0.202818E+09 | 0.293038E+10 | 0.421769E+10 | 0.104963E+10 |
August | 0.249379E+10 | 58994652.25 | 0.243479E+10 | 0.320522E+10 | 0.121028E+10 |
September | 0.202721E+10 | 476155.58 | 0.202673E+10 | 0.228364E+10 | 0.182759E+10 |
October | 0.150037E+10 | 0.00 | 0.150037E+10 | 0.801244E+09 | 0.392459E+10 |
November | 0.110223E+10 | 0.00 | 0.110223E+10 | 0.296610E+09 | 0.449661E+10 |
December | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.165799E+09 | 0.567041E+10 |
Annual Sum or Average | 0.235478E+11 | 0.729484E+09 | 0.228183E+11 | 0.203127E+11 | 0.382503E+11 |
Minimum of Months | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.165799E+09 | 0.104963E+10 |
Maximum of Months | 0.320613E+10 | 0.355452E+09 | 0.293038E+10 | 0.426394E+10 | 0.567041E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214964E+10 | 0.131736E+10 | 0.832275E+09 | 0.189850E+10 | 0.319303E+10 |
February | 0.257921E+10 | 0.162825E+10 | 0.950966E+09 | 0.241438E+10 | 0.296934E+10 |
March | 0.344658E+10 | 0.201036E+10 | 0.143622E+10 | 0.348441E+10 | 0.252388E+10 |
April | 0.342063E+10 | 0.166625E+10 | 0.175438E+10 | 0.338241E+10 | 0.214934E+10 |
May | 0.413195E+10 | 0.172593E+10 | 0.240602E+10 | 0.465979E+10 | 0.136306E+10 |
June | 0.487878E+10 | 0.256123E+10 | 0.231755E+10 | 0.654127E+10 | 0.721938E+09 |
July | 0.458304E+10 | 0.218233E+10 | 0.240071E+10 | 0.619767E+10 | 0.706925E+09 |
August | 0.462263E+10 | 0.254598E+10 | 0.207665E+10 | 0.621254E+10 | 0.812185E+09 |
September | 0.372219E+10 | 0.202200E+10 | 0.170019E+10 | 0.473403E+10 | 0.117170E+10 |
October | 0.278546E+10 | 0.152627E+10 | 0.125919E+10 | 0.290466E+10 | 0.255773E+10 |
November | 0.209818E+10 | 0.118466E+10 | 0.913528E+09 | 0.195137E+10 | 0.289591E+10 |
December | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.158743E+10 | 0.359036E+10 |
Annual Sum or Average | 0.402953E+11 | 0.214519E+11 | 0.188434E+11 | 0.459685E+11 | 0.246554E+11 |
Minimum of Months | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.158743E+10 | 0.706925E+09 |
Maximum of Months | 0.487878E+10 | 0.256123E+10 | 0.240602E+10 | 0.654127E+10 | 0.359036E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.986892E+10 | 0.811825E+10 | 0.175067E+10 | 0.112843E+11 | 0.462929E+10 |
February | 0.855005E+10 | 0.681664E+10 | 0.173341E+10 | 0.968964E+10 | 0.434439E+10 |
March | 0.697916E+10 | 0.459189E+10 | 0.238727E+10 | 0.801418E+10 | 0.385544E+10 |
April | 0.437441E+10 | 0.175897E+10 | 0.261544E+10 | 0.456950E+10 | 0.339682E+10 |
May | 0.414228E+10 | 0.759251E+09 | 0.338303E+10 | 0.471201E+10 | 0.221950E+10 |
June | 0.369585E+10 | 0.675498E+09 | 0.302035E+10 | 0.533022E+10 | 0.117974E+10 |
July | 0.397554E+10 | 0.711908E+09 | 0.326363E+10 | 0.574715E+10 | 0.112948E+10 |
August | 0.506167E+10 | 0.211597E+10 | 0.294570E+10 | 0.735621E+10 | 0.127919E+10 |
September | 0.630226E+10 | 0.351663E+10 | 0.278563E+10 | 0.857833E+10 | 0.187218E+10 |
October | 0.778685E+10 | 0.552495E+10 | 0.226190E+10 | 0.942570E+10 | 0.387914E+10 |
November | 0.918115E+10 | 0.731871E+10 | 0.186244E+10 | 0.107252E+11 | 0.428796E+10 |
December | 0.907223E+10 | 0.734294E+10 | 0.172929E+10 | 0.101659E+11 | 0.515128E+10 |
Annual Sum or Average | 0.789904E+11 | 0.492516E+11 | 0.297388E+11 | 0.955983E+11 | 0.372244E+11 |
Minimum of Months | 0.369585E+10 | 0.675498E+09 | 0.172929E+10 | 0.456950E+10 | 0.112948E+10 |
Maximum of Months | 0.986892E+10 | 0.811825E+10 | 0.338303E+10 | 0.112843E+11 | 0.515128E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228674E+10 | 0.144900E+10 | 0.837735E+09 | 0.217940E+10 | 0.327014E+10 |
February | 0.249063E+10 | 0.154345E+10 | 0.947175E+09 | 0.235255E+10 | 0.300981E+10 |
March | 0.322883E+10 | 0.178142E+10 | 0.144741E+10 | 0.324580E+10 | 0.257921E+10 |
April | 0.294203E+10 | 0.124560E+10 | 0.169642E+10 | 0.282076E+10 | 0.220694E+10 |
May | 0.371577E+10 | 0.130995E+10 | 0.240582E+10 | 0.420447E+10 | 0.145168E+10 |
June | 0.439802E+10 | 0.211606E+10 | 0.228196E+10 | 0.598556E+10 | 0.812224E+09 |
July | 0.370279E+10 | 0.135626E+10 | 0.234652E+10 | 0.505341E+10 | 0.768230E+09 |
August | 0.386466E+10 | 0.190920E+10 | 0.195546E+10 | 0.520049E+10 | 0.860883E+09 |
September | 0.331625E+10 | 0.159036E+10 | 0.172589E+10 | 0.425659E+10 | 0.125484E+10 |
October | 0.288284E+10 | 0.164776E+10 | 0.123508E+10 | 0.311176E+10 | 0.260754E+10 |
November | 0.228922E+10 | 0.138984E+10 | 0.899379E+09 | 0.223605E+10 | 0.293115E+10 |
December | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.166829E+10 | 0.360476E+10 |
Annual Sum or Average | 0.370285E+11 | 0.184676E+11 | 0.185609E+11 | 0.423151E+11 | 0.253574E+11 |
Minimum of Months | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.166829E+10 | 0.768230E+09 |
Maximum of Months | 0.439802E+10 | 0.211606E+10 | 0.240582E+10 | 0.598556E+10 | 0.360476E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 79.82 | 1801.58 | 384.46 | 0.00 | 384.46 | 0.00 | 0.00 |
February | 96.12 | 1834.01 | 483.22 | 0.00 | 483.22 | 0.00 | 0.00 |
March | 306.02 | 1394.86 | 657.51 | 0.00 | 657.51 | 0.00 | 0.00 |
April | 461.26 | 1199.07 | 825.73 | 4.58 | 821.15 | 0.00 | 0.00 |
May | 1020.74 | 728.71 | 1128.00 | 37.29 | 1090.72 | 0.00 | 0.00 |
June | 1641.47 | 405.28 | 1236.93 | 137.13 | 1099.80 | 0.00 | 0.00 |
July | 1570.33 | 384.31 | 1169.80 | 75.72 | 1094.08 | 0.00 | 0.00 |
August | 1194.41 | 439.21 | 931.07 | 22.03 | 909.05 | 0.00 | 0.00 |
September | 884.62 | 676.56 | 782.10 | 0.18 | 781.92 | 0.00 | 0.00 |
October | 311.53 | 1384.12 | 560.17 | 0.00 | 560.17 | 0.00 | 0.00 |
November | 126.24 | 1638.93 | 425.24 | 0.00 | 425.24 | 0.00 | 0.00 |
December | 68.46 | 2021.91 | 359.71 | 0.00 | 359.71 | 0.00 | 0.00 |
Annual Sum or Average | 649.83 | 1155.46 | 746.69 | 23.13 | 723.56 | 0.00 | 0.00 |
Minimum of Months | 68.46 | 384.31 | 359.71 | 0.00 | 359.71 | 0.00 | 0.00 |
Maximum of Months | 1641.47 | 2021.91 | 1236.93 | 137.13 | 1099.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 724.45 | 1130.88 | 802.58 | 491.85 | 310.74 | 0.00 | 0.00 |
February | 1008.89 | 1174.67 | 1066.14 | 673.05 | 393.09 | 0.00 | 0.00 |
March | 1309.86 | 898.32 | 1286.81 | 750.58 | 536.22 | 0.00 | 0.00 |
April | 1313.85 | 782.36 | 1319.69 | 642.84 | 676.85 | 0.00 | 0.00 |
May | 1746.46 | 492.91 | 1542.70 | 644.39 | 898.31 | 0.00 | 0.00 |
June | 2523.21 | 272.67 | 1882.25 | 988.13 | 894.12 | 0.00 | 0.00 |
July | 2313.07 | 258.53 | 1711.11 | 814.79 | 896.32 | 0.00 | 0.00 |
August | 2320.04 | 294.84 | 1725.89 | 950.56 | 775.33 | 0.00 | 0.00 |
September | 1830.63 | 435.59 | 1436.03 | 780.09 | 655.94 | 0.00 | 0.00 |
October | 1093.73 | 905.94 | 1039.97 | 569.84 | 470.13 | 0.00 | 0.00 |
November | 767.12 | 1057.96 | 809.48 | 457.04 | 352.44 | 0.00 | 0.00 |
December | 604.90 | 1281.47 | 700.80 | 403.71 | 297.09 | 0.00 | 0.00 |
Annual Sum or Average | 1465.15 | 746.57 | 1277.76 | 680.24 | 597.52 | 0.00 | 0.00 |
Minimum of Months | 604.90 | 258.53 | 700.80 | 403.71 | 297.09 | 0.00 | 0.00 |
Maximum of Months | 2523.21 | 1281.47 | 1882.25 | 988.13 | 898.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4234.02 | 1644.91 | 3684.63 | 3031.01 | 653.63 | 0.00 | 0.00 |
February | 4017.83 | 1717.94 | 3534.25 | 2817.72 | 716.52 | 0.00 | 0.00 |
March | 3000.44 | 1371.20 | 2605.72 | 1714.42 | 891.30 | 0.00 | 0.00 |
April | 1771.27 | 1235.64 | 1687.66 | 678.61 | 1009.04 | 0.00 | 0.00 |
May | 1763.30 | 798.98 | 1546.55 | 283.47 | 1263.08 | 0.00 | 0.00 |
June | 2050.91 | 443.77 | 1425.87 | 260.61 | 1165.26 | 0.00 | 0.00 |
July | 2139.88 | 411.93 | 1484.30 | 265.80 | 1218.50 | 0.00 | 0.00 |
August | 2742.05 | 463.68 | 1889.81 | 790.01 | 1099.80 | 0.00 | 0.00 |
September | 3309.86 | 695.05 | 2431.43 | 1356.72 | 1074.70 | 0.00 | 0.00 |
October | 3529.11 | 1375.55 | 2907.28 | 2062.78 | 844.50 | 0.00 | 0.00 |
November | 4154.24 | 1572.04 | 3542.11 | 2823.58 | 718.53 | 0.00 | 0.00 |
December | 3813.06 | 1837.28 | 3387.18 | 2741.54 | 645.64 | 0.00 | 0.00 |
Annual Sum or Average | 3038.26 | 1127.41 | 2504.77 | 1561.76 | 943.01 | 0.00 | 0.00 |
Minimum of Months | 1763.30 | 411.93 | 1425.87 | 260.61 | 645.64 | 0.00 | 0.00 |
Maximum of Months | 4234.02 | 1837.28 | 3684.63 | 3031.01 | 1263.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 822.64 | 1157.22 | 853.77 | 540.99 | 312.77 | 0.00 | 0.00 |
February | 978.44 | 1187.99 | 1029.52 | 638.00 | 391.52 | 0.00 | 0.00 |
March | 1217.11 | 915.07 | 1205.51 | 665.11 | 540.40 | 0.00 | 0.00 |
April | 1094.46 | 801.71 | 1135.04 | 480.56 | 654.48 | 0.00 | 0.00 |
May | 1572.41 | 522.28 | 1387.31 | 489.08 | 898.23 | 0.00 | 0.00 |
June | 2304.99 | 305.42 | 1696.77 | 816.38 | 880.39 | 0.00 | 0.00 |
July | 1882.58 | 280.11 | 1382.46 | 506.37 | 876.09 | 0.00 | 0.00 |
August | 1938.83 | 312.05 | 1442.90 | 712.81 | 730.09 | 0.00 | 0.00 |
September | 1643.36 | 465.15 | 1279.42 | 613.57 | 665.85 | 0.00 | 0.00 |
October | 1169.16 | 921.52 | 1076.33 | 615.20 | 461.13 | 0.00 | 0.00 |
November | 871.96 | 1069.95 | 883.19 | 536.20 | 346.98 | 0.00 | 0.00 |
December | 629.81 | 1285.02 | 713.37 | 421.41 | 291.96 | 0.00 | 0.00 |
Annual Sum or Average | 1345.34 | 766.36 | 1174.16 | 585.60 | 588.56 | 0.00 | 0.00 |
Minimum of Months | 629.81 | 280.11 | 713.37 | 421.41 | 291.96 | 0.00 | 0.00 |
Maximum of Months | 2304.99 | 1285.02 | 1696.77 | 816.38 | 898.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 82.38 | 1836.69 | 384.45 | 0.00 | 384.45 | 0.00 | 0.00 |
February | 106.55 | 1846.95 | 483.21 | 0.00 | 483.21 | 0.00 | 0.00 |
March | 332.77 | 1394.06 | 657.49 | 0.00 | 657.49 | 0.00 | 0.00 |
April | 490.57 | 1209.65 | 825.72 | 4.58 | 821.14 | 0.00 | 0.00 |
May | 1060.09 | 711.38 | 1127.98 | 37.29 | 1090.69 | 0.00 | 0.00 |
June | 1673.96 | 394.27 | 1236.91 | 137.13 | 1099.78 | 0.00 | 0.00 |
July | 1601.23 | 371.82 | 1169.78 | 75.72 | 1094.06 | 0.00 | 0.00 |
August | 1211.61 | 438.69 | 931.06 | 22.03 | 909.03 | 0.00 | 0.00 |
September | 887.36 | 704.18 | 782.09 | 0.18 | 781.90 | 0.00 | 0.00 |
October | 305.58 | 1465.67 | 560.16 | 0.00 | 560.16 | 0.00 | 0.00 |
November | 119.85 | 1724.28 | 425.23 | 0.00 | 425.23 | 0.00 | 0.00 |
December | 66.35 | 2097.85 | 359.71 | 0.00 | 359.71 | 0.00 | 0.00 |
Annual Sum or Average | 664.65 | 1179.42 | 746.68 | 23.13 | 723.55 | 0.00 | 0.00 |
Minimum of Months | 66.35 | 371.82 | 359.71 | 0.00 | 359.71 | 0.00 | 0.00 |
Maximum of Months | 1673.96 | 2097.85 | 1236.91 | 137.13 | 1099.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 724.20 | 1172.77 | 802.57 | 491.84 | 310.73 | 0.00 | 0.00 |
February | 1017.46 | 1204.86 | 1066.13 | 673.04 | 393.09 | 0.00 | 0.00 |
March | 1325.20 | 923.59 | 1286.78 | 750.57 | 536.22 | 0.00 | 0.00 |
April | 1328.75 | 815.37 | 1319.67 | 642.83 | 676.84 | 0.00 | 0.00 |
May | 1766.98 | 496.29 | 1542.67 | 644.38 | 898.29 | 0.00 | 0.00 |
June | 2541.27 | 277.12 | 1882.22 | 988.11 | 894.11 | 0.00 | 0.00 |
July | 2330.01 | 262.46 | 1711.08 | 814.77 | 896.31 | 0.00 | 0.00 |
August | 2330.08 | 309.27 | 1725.86 | 950.54 | 775.32 | 0.00 | 0.00 |
September | 1832.47 | 467.04 | 1436.01 | 780.08 | 655.93 | 0.00 | 0.00 |
October | 1091.07 | 978.21 | 1039.95 | 569.83 | 470.12 | 0.00 | 0.00 |
November | 759.62 | 1131.81 | 809.47 | 457.03 | 352.44 | 0.00 | 0.00 |
December | 600.82 | 1345.95 | 700.79 | 403.70 | 297.08 | 0.00 | 0.00 |
Annual Sum or Average | 1472.80 | 779.78 | 1277.74 | 680.22 | 597.51 | 0.00 | 0.00 |
Minimum of Months | 600.82 | 262.46 | 700.79 | 403.70 | 297.08 | 0.00 | 0.00 |
Maximum of Months | 2541.27 | 1345.95 | 1882.22 | 988.11 | 898.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4247.05 | 1762.57 | 3684.49 | 3030.88 | 653.60 | 0.00 | 0.00 |
February | 4054.00 | 1805.16 | 3534.11 | 2817.61 | 716.50 | 0.00 | 0.00 |
March | 3038.36 | 1418.19 | 2605.62 | 1714.34 | 891.28 | 0.00 | 0.00 |
April | 1808.66 | 1270.68 | 1687.60 | 678.59 | 1009.01 | 0.00 | 0.00 |
May | 1809.84 | 782.15 | 1546.50 | 283.46 | 1263.04 | 0.00 | 0.00 |
June | 2083.40 | 435.93 | 1425.83 | 260.60 | 1165.23 | 0.00 | 0.00 |
July | 2170.20 | 405.07 | 1484.25 | 265.79 | 1218.46 | 0.00 | 0.00 |
August | 2761.47 | 480.59 | 1889.75 | 789.98 | 1099.77 | 0.00 | 0.00 |
September | 3318.78 | 751.77 | 2431.34 | 1356.67 | 1074.67 | 0.00 | 0.00 |
October | 3534.42 | 1497.94 | 2907.16 | 2062.69 | 844.47 | 0.00 | 0.00 |
November | 4164.77 | 1709.50 | 3541.97 | 2823.46 | 718.51 | 0.00 | 0.00 |
December | 3830.20 | 1962.05 | 3387.05 | 2741.43 | 645.62 | 0.00 | 0.00 |
Annual Sum or Average | 3062.79 | 1186.70 | 2504.67 | 1561.69 | 942.98 | 0.00 | 0.00 |
Minimum of Months | 1808.66 | 405.07 | 1425.83 | 260.60 | 645.62 | 0.00 | 0.00 |
Maximum of Months | 4247.05 | 1962.05 | 3684.49 | 3030.88 | 1263.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 828.22 | 1204.70 | 853.76 | 540.99 | 312.77 | 0.00 | 0.00 |
February | 990.83 | 1223.85 | 1029.51 | 637.99 | 391.52 | 0.00 | 0.00 |
March | 1235.29 | 940.12 | 1205.49 | 665.09 | 540.40 | 0.00 | 0.00 |
April | 1110.38 | 832.87 | 1135.03 | 480.55 | 654.48 | 0.00 | 0.00 |
May | 1594.73 | 526.07 | 1387.29 | 489.07 | 898.22 | 0.00 | 0.00 |
June | 2322.76 | 311.97 | 1696.74 | 816.37 | 880.38 | 0.00 | 0.00 |
July | 1900.30 | 281.86 | 1382.45 | 506.36 | 876.08 | 0.00 | 0.00 |
August | 1949.40 | 325.17 | 1442.88 | 712.80 | 730.08 | 0.00 | 0.00 |
September | 1645.15 | 498.91 | 1279.40 | 613.56 | 665.85 | 0.00 | 0.00 |
October | 1164.79 | 998.19 | 1076.32 | 615.19 | 461.12 | 0.00 | 0.00 |
November | 867.69 | 1148.46 | 883.17 | 536.19 | 346.98 | 0.00 | 0.00 |
December | 630.15 | 1353.52 | 713.36 | 421.40 | 291.96 | 0.00 | 0.00 |
Annual Sum or Average | 1354.83 | 801.51 | 1174.15 | 585.59 | 588.56 | 0.00 | 0.00 |
Minimum of Months | 630.15 | 281.86 | 713.36 | 421.40 | 291.96 | 0.00 | 0.00 |
Maximum of Months | 2322.76 | 1353.52 | 1696.74 | 816.37 | 898.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 70.53 | 1902.98 | 384.46 | 0.00 | 384.46 | 0.00 | 0.00 |
February | 88.36 | 1920.39 | 483.22 | 0.00 | 483.22 | 0.00 | 0.00 |
March | 296.87 | 1467.63 | 657.51 | 0.00 | 657.51 | 0.00 | 0.00 |
April | 451.31 | 1274.15 | 825.73 | 4.58 | 821.15 | 0.00 | 0.00 |
May | 1012.17 | 755.03 | 1128.00 | 37.29 | 1090.72 | 0.00 | 0.00 |
June | 1645.04 | 413.84 | 1236.93 | 137.13 | 1099.80 | 0.00 | 0.00 |
July | 1574.70 | 391.89 | 1169.80 | 75.72 | 1094.08 | 0.00 | 0.00 |
August | 1196.69 | 451.87 | 931.07 | 22.03 | 909.05 | 0.00 | 0.00 |
September | 881.03 | 705.09 | 782.10 | 0.18 | 781.92 | 0.00 | 0.00 |
October | 299.15 | 1465.27 | 560.17 | 0.00 | 560.17 | 0.00 | 0.00 |
November | 114.43 | 1734.80 | 425.24 | 0.00 | 425.24 | 0.00 | 0.00 |
December | 61.90 | 2117.09 | 359.71 | 0.00 | 359.71 | 0.00 | 0.00 |
Annual Sum or Average | 644.11 | 1212.91 | 746.69 | 23.13 | 723.56 | 0.00 | 0.00 |
Minimum of Months | 61.90 | 391.89 | 359.71 | 0.00 | 359.71 | 0.00 | 0.00 |
Maximum of Months | 1645.04 | 2117.09 | 1236.93 | 137.13 | 1099.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 708.82 | 1192.14 | 802.58 | 491.85 | 310.74 | 0.00 | 0.00 |
February | 998.01 | 1227.40 | 1066.14 | 673.05 | 393.09 | 0.00 | 0.00 |
March | 1300.93 | 942.31 | 1286.81 | 750.58 | 536.22 | 0.00 | 0.00 |
April | 1304.94 | 829.22 | 1319.69 | 642.84 | 676.85 | 0.00 | 0.00 |
May | 1739.76 | 508.91 | 1542.70 | 644.39 | 898.31 | 0.00 | 0.00 |
June | 2523.64 | 278.53 | 1882.25 | 988.13 | 894.12 | 0.00 | 0.00 |
July | 2313.95 | 263.94 | 1711.11 | 814.79 | 896.32 | 0.00 | 0.00 |
August | 2319.50 | 303.24 | 1725.89 | 950.56 | 775.33 | 0.00 | 0.00 |
September | 1826.40 | 452.04 | 1436.03 | 780.09 | 655.94 | 0.00 | 0.00 |
October | 1084.48 | 954.95 | 1039.97 | 569.84 | 470.13 | 0.00 | 0.00 |
November | 752.84 | 1117.25 | 809.48 | 457.04 | 352.44 | 0.00 | 0.00 |
December | 592.68 | 1340.49 | 700.80 | 403.71 | 297.09 | 0.00 | 0.00 |
Annual Sum or Average | 1457.65 | 781.82 | 1277.76 | 680.24 | 597.52 | 0.00 | 0.00 |
Minimum of Months | 592.68 | 263.94 | 700.80 | 403.71 | 297.09 | 0.00 | 0.00 |
Maximum of Months | 2523.64 | 1340.49 | 1882.25 | 988.13 | 898.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4213.06 | 1728.38 | 3684.63 | 3031.01 | 653.63 | 0.00 | 0.00 |
February | 4005.31 | 1795.80 | 3534.25 | 2817.72 | 716.52 | 0.00 | 0.00 |
March | 2992.15 | 1439.46 | 2605.72 | 1714.42 | 891.30 | 0.00 | 0.00 |
April | 1762.92 | 1310.50 | 1687.66 | 678.61 | 1009.04 | 0.00 | 0.00 |
May | 1759.26 | 828.66 | 1546.55 | 283.47 | 1263.08 | 0.00 | 0.00 |
June | 2056.41 | 455.15 | 1425.87 | 260.61 | 1165.26 | 0.00 | 0.00 |
July | 2145.74 | 421.70 | 1484.30 | 265.80 | 1218.50 | 0.00 | 0.00 |
August | 2746.49 | 477.60 | 1889.81 | 790.01 | 1099.80 | 0.00 | 0.00 |
September | 3309.54 | 722.29 | 2431.43 | 1356.72 | 1074.70 | 0.00 | 0.00 |
October | 3519.15 | 1448.31 | 2907.28 | 2062.78 | 844.50 | 0.00 | 0.00 |
November | 4137.81 | 1654.31 | 3542.11 | 2823.58 | 718.53 | 0.00 | 0.00 |
December | 3795.52 | 1923.27 | 3387.18 | 2741.54 | 645.64 | 0.00 | 0.00 |
Annual Sum or Average | 3031.40 | 1180.38 | 2504.77 | 1561.76 | 943.01 | 0.00 | 0.00 |
Minimum of Months | 1759.26 | 421.70 | 1425.87 | 260.61 | 645.64 | 0.00 | 0.00 |
Maximum of Months | 4213.06 | 1923.27 | 3684.63 | 3031.01 | 1263.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 813.69 | 1220.93 | 853.77 | 540.99 | 312.77 | 0.00 | 0.00 |
February | 972.45 | 1244.13 | 1029.52 | 638.00 | 391.52 | 0.00 | 0.00 |
March | 1211.84 | 962.97 | 1205.51 | 665.11 | 540.40 | 0.00 | 0.00 |
April | 1088.26 | 851.44 | 1135.04 | 480.56 | 654.48 | 0.00 | 0.00 |
May | 1569.77 | 542.00 | 1387.31 | 489.08 | 898.23 | 0.00 | 0.00 |
June | 2309.24 | 313.36 | 1696.77 | 816.38 | 880.39 | 0.00 | 0.00 |
July | 1886.73 | 286.82 | 1382.46 | 506.37 | 876.09 | 0.00 | 0.00 |
August | 1941.64 | 321.42 | 1442.90 | 712.81 | 730.09 | 0.00 | 0.00 |
September | 1642.20 | 484.12 | 1279.42 | 613.57 | 665.85 | 0.00 | 0.00 |
October | 1161.80 | 973.55 | 1076.33 | 615.20 | 461.13 | 0.00 | 0.00 |
November | 862.67 | 1130.85 | 883.19 | 536.20 | 346.98 | 0.00 | 0.00 |
December | 622.87 | 1345.86 | 713.37 | 421.41 | 291.96 | 0.00 | 0.00 |
Annual Sum or Average | 1341.80 | 804.08 | 1174.16 | 585.60 | 588.56 | 0.00 | 0.00 |
Minimum of Months | 622.87 | 286.82 | 713.37 | 421.41 | 291.96 | 0.00 | 0.00 |
Maximum of Months | 2309.24 | 1345.86 | 1696.77 | 816.38 | 898.23 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.213781E+09 | 0.482535E+10 | 0.102974E+10 | 0.00 | 0.102974E+10 | 0.00 | 0.00 |
February | 0.232537E+09 | 0.443685E+10 | 0.116901E+10 | 0.00 | 0.116901E+10 | 0.00 | 0.00 |
March | 0.819642E+09 | 0.373599E+10 | 0.176107E+10 | 0.00 | 0.176107E+10 | 0.00 | 0.00 |
April | 0.119559E+10 | 0.310799E+10 | 0.214030E+10 | 11873484.46 | 0.212843E+10 | 0.00 | 0.00 |
May | 0.273395E+10 | 0.195179E+10 | 0.302124E+10 | 99870170.09 | 0.292137E+10 | 0.00 | 0.00 |
June | 0.425469E+10 | 0.105049E+10 | 0.320613E+10 | 0.355452E+09 | 0.285068E+10 | 0.00 | 0.00 |
July | 0.420598E+10 | 0.102935E+10 | 0.313320E+10 | 0.202818E+09 | 0.293038E+10 | 0.00 | 0.00 |
August | 0.319912E+10 | 0.117637E+10 | 0.249379E+10 | 58994652.25 | 0.243479E+10 | 0.00 | 0.00 |
September | 0.229295E+10 | 0.175364E+10 | 0.202721E+10 | 476155.58 | 0.202673E+10 | 0.00 | 0.00 |
October | 0.834394E+09 | 0.370721E+10 | 0.150037E+10 | 0.00 | 0.150037E+10 | 0.00 | 0.00 |
November | 0.327208E+09 | 0.424810E+10 | 0.110223E+10 | 0.00 | 0.110223E+10 | 0.00 | 0.00 |
December | 0.183351E+09 | 0.541548E+10 | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.204932E+11 | 0.364386E+11 | 0.235478E+11 | 0.729484E+09 | 0.228183E+11 | 0.00 | 0.00 |
Minimum of Months | 0.183351E+09 | 0.102935E+10 | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.00 | 0.00 |
Maximum of Months | 0.425469E+10 | 0.541548E+10 | 0.320613E+10 | 0.355452E+09 | 0.293038E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.194038E+10 | 0.302895E+10 | 0.214964E+10 | 0.131736E+10 | 0.832275E+09 | 0.00 | 0.00 |
February | 0.244070E+10 | 0.284176E+10 | 0.257921E+10 | 0.162825E+10 | 0.950966E+09 | 0.00 | 0.00 |
March | 0.350834E+10 | 0.240606E+10 | 0.344658E+10 | 0.201036E+10 | 0.143622E+10 | 0.00 | 0.00 |
April | 0.340549E+10 | 0.202789E+10 | 0.342063E+10 | 0.166625E+10 | 0.175438E+10 | 0.00 | 0.00 |
May | 0.467773E+10 | 0.132022E+10 | 0.413195E+10 | 0.172593E+10 | 0.240602E+10 | 0.00 | 0.00 |
June | 0.654016E+10 | 0.706756E+09 | 0.487878E+10 | 0.256123E+10 | 0.231755E+10 | 0.00 | 0.00 |
July | 0.619533E+10 | 0.692436E+09 | 0.458304E+10 | 0.218233E+10 | 0.240071E+10 | 0.00 | 0.00 |
August | 0.621399E+10 | 0.789689E+09 | 0.462263E+10 | 0.254598E+10 | 0.207665E+10 | 0.00 | 0.00 |
September | 0.474499E+10 | 0.112904E+10 | 0.372219E+10 | 0.202200E+10 | 0.170019E+10 | 0.00 | 0.00 |
October | 0.292945E+10 | 0.242647E+10 | 0.278546E+10 | 0.152627E+10 | 0.125919E+10 | 0.00 | 0.00 |
November | 0.198838E+10 | 0.274224E+10 | 0.209818E+10 | 0.118466E+10 | 0.913528E+09 | 0.00 | 0.00 |
December | 0.162018E+10 | 0.343229E+10 | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.462051E+11 | 0.235438E+11 | 0.402953E+11 | 0.214519E+11 | 0.188434E+11 | 0.00 | 0.00 |
Minimum of Months | 0.162018E+10 | 0.692436E+09 | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.00 | 0.00 |
Maximum of Months | 0.654016E+10 | 0.343229E+10 | 0.487878E+10 | 0.256123E+10 | 0.240602E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113404E+11 | 0.440572E+10 | 0.986892E+10 | 0.811825E+10 | 0.175067E+10 | 0.00 | 0.00 |
February | 0.971992E+10 | 0.415603E+10 | 0.855005E+10 | 0.681664E+10 | 0.173341E+10 | 0.00 | 0.00 |
March | 0.803637E+10 | 0.367262E+10 | 0.697916E+10 | 0.459189E+10 | 0.238727E+10 | 0.00 | 0.00 |
April | 0.459114E+10 | 0.320277E+10 | 0.437441E+10 | 0.175897E+10 | 0.261544E+10 | 0.00 | 0.00 |
May | 0.472283E+10 | 0.213998E+10 | 0.414228E+10 | 0.759251E+09 | 0.338303E+10 | 0.00 | 0.00 |
June | 0.531597E+10 | 0.115025E+10 | 0.369585E+10 | 0.675498E+09 | 0.302035E+10 | 0.00 | 0.00 |
July | 0.573145E+10 | 0.110331E+10 | 0.397554E+10 | 0.711908E+09 | 0.326363E+10 | 0.00 | 0.00 |
August | 0.734430E+10 | 0.124192E+10 | 0.506167E+10 | 0.211597E+10 | 0.294570E+10 | 0.00 | 0.00 |
September | 0.857916E+10 | 0.180158E+10 | 0.630226E+10 | 0.351663E+10 | 0.278563E+10 | 0.00 | 0.00 |
October | 0.945237E+10 | 0.368427E+10 | 0.778685E+10 | 0.552495E+10 | 0.226190E+10 | 0.00 | 0.00 |
November | 0.107678E+11 | 0.407473E+10 | 0.918115E+10 | 0.731871E+10 | 0.186244E+10 | 0.00 | 0.00 |
December | 0.102129E+11 | 0.492097E+10 | 0.907223E+10 | 0.734294E+10 | 0.172929E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.958146E+11 | 0.355542E+11 | 0.789904E+11 | 0.492516E+11 | 0.297388E+11 | 0.00 | 0.00 |
Minimum of Months | 0.459114E+10 | 0.110331E+10 | 0.369585E+10 | 0.675498E+09 | 0.172929E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113404E+11 | 0.492097E+10 | 0.986892E+10 | 0.811825E+10 | 0.338303E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.220335E+10 | 0.309949E+10 | 0.228674E+10 | 0.144900E+10 | 0.837735E+09 | 0.00 | 0.00 |
February | 0.236704E+10 | 0.287399E+10 | 0.249063E+10 | 0.154345E+10 | 0.947175E+09 | 0.00 | 0.00 |
March | 0.325991E+10 | 0.245092E+10 | 0.322883E+10 | 0.178142E+10 | 0.144741E+10 | 0.00 | 0.00 |
April | 0.283684E+10 | 0.207802E+10 | 0.294203E+10 | 0.124560E+10 | 0.169642E+10 | 0.00 | 0.00 |
May | 0.421153E+10 | 0.139886E+10 | 0.371577E+10 | 0.130995E+10 | 0.240582E+10 | 0.00 | 0.00 |
June | 0.597453E+10 | 0.791656E+09 | 0.439802E+10 | 0.211606E+10 | 0.228196E+10 | 0.00 | 0.00 |
July | 0.504231E+10 | 0.750240E+09 | 0.370279E+10 | 0.135626E+10 | 0.234652E+10 | 0.00 | 0.00 |
August | 0.519296E+10 | 0.835795E+09 | 0.386466E+10 | 0.190920E+10 | 0.195546E+10 | 0.00 | 0.00 |
September | 0.425960E+10 | 0.120566E+10 | 0.331625E+10 | 0.159036E+10 | 0.172589E+10 | 0.00 | 0.00 |
October | 0.313147E+10 | 0.246819E+10 | 0.288284E+10 | 0.164776E+10 | 0.123508E+10 | 0.00 | 0.00 |
November | 0.226011E+10 | 0.277330E+10 | 0.228922E+10 | 0.138984E+10 | 0.899379E+09 | 0.00 | 0.00 |
December | 0.168690E+10 | 0.344181E+10 | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.424266E+11 | 0.241679E+11 | 0.370285E+11 | 0.184676E+11 | 0.185609E+11 | 0.00 | 0.00 |
Minimum of Months | 0.168690E+10 | 0.750240E+09 | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.00 | 0.00 |
Maximum of Months | 0.597453E+10 | 0.344181E+10 | 0.439802E+10 | 0.211606E+10 | 0.240582E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.220644E+09 | 0.491940E+10 | 0.102972E+10 | 0.00 | 0.102972E+10 | 0.00 | 0.00 |
February | 0.257774E+09 | 0.446814E+10 | 0.116899E+10 | 0.00 | 0.116899E+10 | 0.00 | 0.00 |
March | 0.891304E+09 | 0.373384E+10 | 0.176103E+10 | 0.00 | 0.176103E+10 | 0.00 | 0.00 |
April | 0.127155E+10 | 0.313541E+10 | 0.214026E+10 | 11873135.46 | 0.212839E+10 | 0.00 | 0.00 |
May | 0.283935E+10 | 0.190535E+10 | 0.302118E+10 | 99867234.64 | 0.292131E+10 | 0.00 | 0.00 |
June | 0.433891E+10 | 0.102194E+10 | 0.320607E+10 | 0.355441E+09 | 0.285063E+10 | 0.00 | 0.00 |
July | 0.428874E+10 | 0.995873E+09 | 0.313313E+10 | 0.202812E+09 | 0.293032E+10 | 0.00 | 0.00 |
August | 0.324518E+10 | 0.117500E+10 | 0.249374E+10 | 58992918.24 | 0.243475E+10 | 0.00 | 0.00 |
September | 0.230004E+10 | 0.182523E+10 | 0.202717E+10 | 476141.58 | 0.202669E+10 | 0.00 | 0.00 |
October | 0.818453E+09 | 0.392566E+10 | 0.150034E+10 | 0.00 | 0.150034E+10 | 0.00 | 0.00 |
November | 0.310648E+09 | 0.446933E+10 | 0.110221E+10 | 0.00 | 0.110221E+10 | 0.00 | 0.00 |
December | 0.177711E+09 | 0.561888E+10 | 0.963435E+09 | 0.00 | 0.963435E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.209603E+11 | 0.371941E+11 | 0.235473E+11 | 0.729462E+09 | 0.228178E+11 | 0.00 | 0.00 |
Minimum of Months | 0.177711E+09 | 0.995873E+09 | 0.963435E+09 | 0.00 | 0.963435E+09 | 0.00 | 0.00 |
Maximum of Months | 0.433891E+10 | 0.561888E+10 | 0.320607E+10 | 0.355441E+09 | 0.293032E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193969E+10 | 0.314116E+10 | 0.214960E+10 | 0.131734E+10 | 0.832266E+09 | 0.00 | 0.00 |
February | 0.246143E+10 | 0.291480E+10 | 0.257917E+10 | 0.162822E+10 | 0.950956E+09 | 0.00 | 0.00 |
March | 0.354943E+10 | 0.247373E+10 | 0.344652E+10 | 0.201032E+10 | 0.143620E+10 | 0.00 | 0.00 |
April | 0.344412E+10 | 0.211343E+10 | 0.342058E+10 | 0.166622E+10 | 0.175436E+10 | 0.00 | 0.00 |
May | 0.473268E+10 | 0.132927E+10 | 0.413189E+10 | 0.172590E+10 | 0.240599E+10 | 0.00 | 0.00 |
June | 0.658697E+10 | 0.718305E+09 | 0.487871E+10 | 0.256118E+10 | 0.231752E+10 | 0.00 | 0.00 |
July | 0.624071E+10 | 0.702976E+09 | 0.458297E+10 | 0.218229E+10 | 0.240068E+10 | 0.00 | 0.00 |
August | 0.624089E+10 | 0.828351E+09 | 0.462255E+10 | 0.254593E+10 | 0.207663E+10 | 0.00 | 0.00 |
September | 0.474975E+10 | 0.121057E+10 | 0.372213E+10 | 0.202196E+10 | 0.170017E+10 | 0.00 | 0.00 |
October | 0.292232E+10 | 0.262004E+10 | 0.278542E+10 | 0.152624E+10 | 0.125917E+10 | 0.00 | 0.00 |
November | 0.196894E+10 | 0.293366E+10 | 0.209815E+10 | 0.118463E+10 | 0.913518E+09 | 0.00 | 0.00 |
December | 0.160923E+10 | 0.360498E+10 | 0.187698E+10 | 0.108127E+10 | 0.795712E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.464461E+11 | 0.245913E+11 | 0.402947E+11 | 0.214515E+11 | 0.188432E+11 | 0.00 | 0.00 |
Minimum of Months | 0.160923E+10 | 0.702976E+09 | 0.187698E+10 | 0.108127E+10 | 0.795712E+09 | 0.00 | 0.00 |
Maximum of Months | 0.658697E+10 | 0.360498E+10 | 0.487871E+10 | 0.256118E+10 | 0.240599E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113753E+11 | 0.472088E+10 | 0.986853E+10 | 0.811791E+10 | 0.175061E+10 | 0.00 | 0.00 |
February | 0.980743E+10 | 0.436703E+10 | 0.854971E+10 | 0.681636E+10 | 0.173336E+10 | 0.00 | 0.00 |
March | 0.813795E+10 | 0.379847E+10 | 0.697889E+10 | 0.459170E+10 | 0.238719E+10 | 0.00 | 0.00 |
April | 0.468804E+10 | 0.329360E+10 | 0.437425E+10 | 0.175889E+10 | 0.261536E+10 | 0.00 | 0.00 |
May | 0.484747E+10 | 0.209490E+10 | 0.414215E+10 | 0.759219E+09 | 0.338293E+10 | 0.00 | 0.00 |
June | 0.540018E+10 | 0.112992E+10 | 0.369574E+10 | 0.675470E+09 | 0.302027E+10 | 0.00 | 0.00 |
July | 0.581267E+10 | 0.108494E+10 | 0.397541E+10 | 0.711879E+09 | 0.326354E+10 | 0.00 | 0.00 |
August | 0.739633E+10 | 0.128722E+10 | 0.506150E+10 | 0.211588E+10 | 0.294562E+10 | 0.00 | 0.00 |
September | 0.860227E+10 | 0.194859E+10 | 0.630203E+10 | 0.351648E+10 | 0.278555E+10 | 0.00 | 0.00 |
October | 0.946660E+10 | 0.401207E+10 | 0.778655E+10 | 0.552472E+10 | 0.226183E+10 | 0.00 | 0.00 |
November | 0.107951E+11 | 0.443103E+10 | 0.918079E+10 | 0.731841E+10 | 0.186238E+10 | 0.00 | 0.00 |
December | 0.102588E+11 | 0.525515E+10 | 0.907187E+10 | 0.734263E+10 | 0.172923E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.965881E+11 | 0.374238E+11 | 0.789874E+11 | 0.492495E+11 | 0.297379E+11 | 0.00 | 0.00 |
Minimum of Months | 0.468804E+10 | 0.108494E+10 | 0.369574E+10 | 0.675470E+09 | 0.172923E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113753E+11 | 0.525515E+10 | 0.986853E+10 | 0.811791E+10 | 0.338293E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.221829E+10 | 0.322666E+10 | 0.228670E+10 | 0.144898E+10 | 0.837728E+09 | 0.00 | 0.00 |
February | 0.239702E+10 | 0.296075E+10 | 0.249059E+10 | 0.154343E+10 | 0.947167E+09 | 0.00 | 0.00 |
March | 0.330861E+10 | 0.251801E+10 | 0.322879E+10 | 0.178139E+10 | 0.144740E+10 | 0.00 | 0.00 |
April | 0.287811E+10 | 0.215880E+10 | 0.294199E+10 | 0.124558E+10 | 0.169640E+10 | 0.00 | 0.00 |
May | 0.427132E+10 | 0.140904E+10 | 0.371573E+10 | 0.130993E+10 | 0.240580E+10 | 0.00 | 0.00 |
June | 0.602059E+10 | 0.808622E+09 | 0.439796E+10 | 0.211602E+10 | 0.228194E+10 | 0.00 | 0.00 |
July | 0.508976E+10 | 0.754926E+09 | 0.370274E+10 | 0.135624E+10 | 0.234650E+10 | 0.00 | 0.00 |
August | 0.522126E+10 | 0.870923E+09 | 0.386461E+10 | 0.190916E+10 | 0.195545E+10 | 0.00 | 0.00 |
September | 0.426423E+10 | 0.129317E+10 | 0.331621E+10 | 0.159034E+10 | 0.172587E+10 | 0.00 | 0.00 |
October | 0.311977E+10 | 0.267355E+10 | 0.288280E+10 | 0.164773E+10 | 0.123507E+10 | 0.00 | 0.00 |
November | 0.224906E+10 | 0.297681E+10 | 0.228919E+10 | 0.138982E+10 | 0.899371E+09 | 0.00 | 0.00 |
December | 0.168780E+10 | 0.362526E+10 | 0.191067E+10 | 0.112868E+10 | 0.781990E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.427258E+11 | 0.252765E+11 | 0.370280E+11 | 0.184673E+11 | 0.185607E+11 | 0.00 | 0.00 |
Minimum of Months | 0.168780E+10 | 0.754926E+09 | 0.191067E+10 | 0.112868E+10 | 0.781990E+09 | 0.00 | 0.00 |
Maximum of Months | 0.602059E+10 | 0.362526E+10 | 0.439796E+10 | 0.211602E+10 | 0.240580E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.188904E+09 | 0.509694E+10 | 0.102974E+10 | 0.00 | 0.102974E+10 | 0.00 | 0.00 |
February | 0.213763E+09 | 0.464580E+10 | 0.116901E+10 | 0.00 | 0.116901E+10 | 0.00 | 0.00 |
March | 0.795149E+09 | 0.393089E+10 | 0.176107E+10 | 0.00 | 0.176107E+10 | 0.00 | 0.00 |
April | 0.116978E+10 | 0.330260E+10 | 0.214030E+10 | 11873484.46 | 0.212843E+10 | 0.00 | 0.00 |
May | 0.271099E+10 | 0.202227E+10 | 0.302124E+10 | 99870170.09 | 0.292137E+10 | 0.00 | 0.00 |
June | 0.426394E+10 | 0.107266E+10 | 0.320613E+10 | 0.355452E+09 | 0.285068E+10 | 0.00 | 0.00 |
July | 0.421769E+10 | 0.104963E+10 | 0.313320E+10 | 0.202818E+09 | 0.293038E+10 | 0.00 | 0.00 |
August | 0.320522E+10 | 0.121028E+10 | 0.249379E+10 | 58994652.25 | 0.243479E+10 | 0.00 | 0.00 |
September | 0.228364E+10 | 0.182759E+10 | 0.202721E+10 | 476155.58 | 0.202673E+10 | 0.00 | 0.00 |
October | 0.801244E+09 | 0.392459E+10 | 0.150037E+10 | 0.00 | 0.150037E+10 | 0.00 | 0.00 |
November | 0.296610E+09 | 0.449661E+10 | 0.110223E+10 | 0.00 | 0.110223E+10 | 0.00 | 0.00 |
December | 0.165799E+09 | 0.567041E+10 | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.203127E+11 | 0.382503E+11 | 0.235478E+11 | 0.729484E+09 | 0.228183E+11 | 0.00 | 0.00 |
Minimum of Months | 0.165799E+09 | 0.104963E+10 | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.00 | 0.00 |
Maximum of Months | 0.426394E+10 | 0.567041E+10 | 0.320613E+10 | 0.355452E+09 | 0.293038E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.189850E+10 | 0.319303E+10 | 0.214964E+10 | 0.131736E+10 | 0.832275E+09 | 0.00 | 0.00 |
February | 0.241438E+10 | 0.296934E+10 | 0.257921E+10 | 0.162825E+10 | 0.950966E+09 | 0.00 | 0.00 |
March | 0.348441E+10 | 0.252388E+10 | 0.344658E+10 | 0.201036E+10 | 0.143622E+10 | 0.00 | 0.00 |
April | 0.338241E+10 | 0.214934E+10 | 0.342063E+10 | 0.166625E+10 | 0.175438E+10 | 0.00 | 0.00 |
May | 0.465979E+10 | 0.136306E+10 | 0.413195E+10 | 0.172593E+10 | 0.240602E+10 | 0.00 | 0.00 |
June | 0.654127E+10 | 0.721938E+09 | 0.487878E+10 | 0.256123E+10 | 0.231755E+10 | 0.00 | 0.00 |
July | 0.619767E+10 | 0.706925E+09 | 0.458304E+10 | 0.218233E+10 | 0.240071E+10 | 0.00 | 0.00 |
August | 0.621254E+10 | 0.812185E+09 | 0.462263E+10 | 0.254598E+10 | 0.207665E+10 | 0.00 | 0.00 |
September | 0.473403E+10 | 0.117170E+10 | 0.372219E+10 | 0.202200E+10 | 0.170019E+10 | 0.00 | 0.00 |
October | 0.290466E+10 | 0.255773E+10 | 0.278546E+10 | 0.152627E+10 | 0.125919E+10 | 0.00 | 0.00 |
November | 0.195137E+10 | 0.289591E+10 | 0.209818E+10 | 0.118466E+10 | 0.913528E+09 | 0.00 | 0.00 |
December | 0.158743E+10 | 0.359036E+10 | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.459685E+11 | 0.246554E+11 | 0.402953E+11 | 0.214519E+11 | 0.188434E+11 | 0.00 | 0.00 |
Minimum of Months | 0.158743E+10 | 0.706925E+09 | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.00 | 0.00 |
Maximum of Months | 0.654127E+10 | 0.359036E+10 | 0.487878E+10 | 0.256123E+10 | 0.240602E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112843E+11 | 0.462929E+10 | 0.986892E+10 | 0.811825E+10 | 0.175067E+10 | 0.00 | 0.00 |
February | 0.968964E+10 | 0.434439E+10 | 0.855005E+10 | 0.681664E+10 | 0.173341E+10 | 0.00 | 0.00 |
March | 0.801418E+10 | 0.385544E+10 | 0.697916E+10 | 0.459189E+10 | 0.238727E+10 | 0.00 | 0.00 |
April | 0.456950E+10 | 0.339682E+10 | 0.437441E+10 | 0.175897E+10 | 0.261544E+10 | 0.00 | 0.00 |
May | 0.471201E+10 | 0.221950E+10 | 0.414228E+10 | 0.759251E+09 | 0.338303E+10 | 0.00 | 0.00 |
June | 0.533022E+10 | 0.117974E+10 | 0.369585E+10 | 0.675498E+09 | 0.302035E+10 | 0.00 | 0.00 |
July | 0.574715E+10 | 0.112948E+10 | 0.397554E+10 | 0.711908E+09 | 0.326363E+10 | 0.00 | 0.00 |
August | 0.735621E+10 | 0.127919E+10 | 0.506167E+10 | 0.211597E+10 | 0.294570E+10 | 0.00 | 0.00 |
September | 0.857833E+10 | 0.187218E+10 | 0.630226E+10 | 0.351663E+10 | 0.278563E+10 | 0.00 | 0.00 |
October | 0.942570E+10 | 0.387914E+10 | 0.778685E+10 | 0.552495E+10 | 0.226190E+10 | 0.00 | 0.00 |
November | 0.107252E+11 | 0.428796E+10 | 0.918115E+10 | 0.731871E+10 | 0.186244E+10 | 0.00 | 0.00 |
December | 0.101659E+11 | 0.515128E+10 | 0.907223E+10 | 0.734294E+10 | 0.172929E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.955983E+11 | 0.372244E+11 | 0.789904E+11 | 0.492516E+11 | 0.297388E+11 | 0.00 | 0.00 |
Minimum of Months | 0.456950E+10 | 0.112948E+10 | 0.369585E+10 | 0.675498E+09 | 0.172929E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112843E+11 | 0.515128E+10 | 0.986892E+10 | 0.811825E+10 | 0.338303E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.217940E+10 | 0.327014E+10 | 0.228674E+10 | 0.144900E+10 | 0.837735E+09 | 0.00 | 0.00 |
February | 0.235255E+10 | 0.300981E+10 | 0.249063E+10 | 0.154345E+10 | 0.947175E+09 | 0.00 | 0.00 |
March | 0.324580E+10 | 0.257921E+10 | 0.322883E+10 | 0.178142E+10 | 0.144741E+10 | 0.00 | 0.00 |
April | 0.282076E+10 | 0.220694E+10 | 0.294203E+10 | 0.124560E+10 | 0.169642E+10 | 0.00 | 0.00 |
May | 0.420447E+10 | 0.145168E+10 | 0.371577E+10 | 0.130995E+10 | 0.240582E+10 | 0.00 | 0.00 |
June | 0.598556E+10 | 0.812224E+09 | 0.439802E+10 | 0.211606E+10 | 0.228196E+10 | 0.00 | 0.00 |
July | 0.505341E+10 | 0.768230E+09 | 0.370279E+10 | 0.135626E+10 | 0.234652E+10 | 0.00 | 0.00 |
August | 0.520049E+10 | 0.860883E+09 | 0.386466E+10 | 0.190920E+10 | 0.195546E+10 | 0.00 | 0.00 |
September | 0.425659E+10 | 0.125484E+10 | 0.331625E+10 | 0.159036E+10 | 0.172589E+10 | 0.00 | 0.00 |
October | 0.311176E+10 | 0.260754E+10 | 0.288284E+10 | 0.164776E+10 | 0.123508E+10 | 0.00 | 0.00 |
November | 0.223605E+10 | 0.293115E+10 | 0.228922E+10 | 0.138984E+10 | 0.899379E+09 | 0.00 | 0.00 |
December | 0.166829E+10 | 0.360476E+10 | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.423151E+11 | 0.253574E+11 | 0.370285E+11 | 0.184676E+11 | 0.185609E+11 | 0.00 | 0.00 |
Minimum of Months | 0.166829E+10 | 0.768230E+09 | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.00 | 0.00 |
Maximum of Months | 0.598556E+10 | 0.360476E+10 | 0.439802E+10 | 0.211606E+10 | 0.240582E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.510429E+10 | -0.486322E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -241066396.4 | 60.05 | 0.00 | 0.00 |
February | 0.469137E+10 | -0.447350E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -217872728.8 | 60.05 | 0.00 | 0.00 |
March | 0.545799E+10 | -0.521901E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -238975849.0 | 60.05 | 0.00 | 0.00 |
April | 0.474543E+10 | -0.451551E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -229924135.2 | 60.05 | 0.00 | 0.00 |
May | 0.481621E+10 | -0.458213E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234075135.0 | 60.05 | 0.00 | 0.00 |
June | 0.451391E+10 | -0.428800E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225904580.0 | 60.05 | 0.00 | 0.00 |
July | 0.409295E+10 | -0.386026E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232686866.7 | 60.05 | 0.00 | 0.00 |
August | 0.443561E+10 | -0.420254E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233063313.1 | 60.05 | 0.00 | 0.00 |
September | 0.408075E+10 | -0.385535E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225400027.2 | 60.05 | 0.00 | 0.00 |
October | 0.440766E+10 | -0.417274E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234920823.6 | 60.05 | 0.00 | 0.00 |
November | 0.458331E+10 | -0.435358E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -229726342.3 | 60.05 | 0.00 | 0.00 |
December | 0.479400E+10 | -0.455072E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -243280470.9 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.557235E+11 | -0.529366E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.278690E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.408075E+10 | -0.521901E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -243280470.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.545799E+10 | -0.385535E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -217872728.8 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:49 | 10608.03 | 39.55 | 274.17 | 267.83 | 5719.64 | 35.01 | 235.50 | 259.67 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 14167.50 | 39.31 | 241.00 | 264.33 | 2392.44 | 24.90 | 117.50 | 243.67 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:00 | 2839.00 | 19.18 | 18.33 | 327.33 | 1624.12 | 21.08 | 131.00 | 293.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 2130.57 | 18.95 | 8.33 | 340.67 | 1246.71 | 21.17 | 163.00 | 303.33 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1901.51 | 19.05 | 0.83 | 393.00 | 1053.77 | 21.25 | 261.67 | 357.17 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:49 | 1543.19 | 18.56 | 0.00 | 392.33 | 927.84 | 20.84 | 187.17 | 352.50 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:10 | 1732.54 | 18.69 | 2.83 | 396.00 | 985.19 | 20.91 | 236.67 | 357.50 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 1864.30 | 18.43 | 4.67 | 371.33 | 1143.72 | 20.67 | 171.83 | 337.00 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 3030.28 | 20.24 | 39.50 | 333.00 | 1425.63 | 21.08 | 169.33 | 305.00 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:40 | 13789.60 | 36.66 | 239.83 | 300.50 | 2004.95 | 21.67 | 123.83 | 277.33 |
November | 257.67 | 0.49 | 0.48 | 01-NOV-08:39 | 12101.16 | 39.11 | 250.50 | 264.67 | 3682.56 | 29.94 | 180.00 | 243.17 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 9938.22 | 39.96 | 250.67 | 258.50 | 8039.11 | 40.64 | 248.33 | 248.00 |
Annual Sum or Average | 3902.00 | 0.50 | 5411.17 | 25.59 | 1330.67 | 3909.50 | 2235.50 | 24.13 | 2225.83 | 3577.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1543.19 | 18.43 | 0.00 | 258.50 | 927.84 | 20.67 | 117.50 | 243.17 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 14167.50 | 39.96 | 274.17 | 396.00 | 8039.11 | 40.64 | 261.67 | 357.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.53 | 0.48 | 01-JAN-07:49 | 2470.79 | 21.00 | 82.67 | 235.00 | 1495.14 | 23.48 | 97.00 | 205.83 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 3941.77 | 23.33 | 84.33 | 250.83 | 2348.44 | 23.86 | 73.00 | 206.17 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:49 | 3771.68 | 22.39 | 83.50 | 319.83 | 2112.10 | 23.24 | 77.33 | 281.17 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 4103.61 | 21.88 | 84.83 | 341.83 | 1828.33 | 22.74 | 58.67 | 303.33 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:40 | 3292.41 | 21.79 | 111.67 | 400.67 | 1795.85 | 23.03 | 88.00 | 367.50 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-04:00 | 3919.40 | 21.43 | 109.00 | 404.67 | 2258.66 | 23.52 | 92.17 | 376.17 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:10 | 3526.81 | 21.64 | 116.33 | 406.67 | 1909.60 | 22.72 | 87.83 | 374.83 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:40 | 4852.18 | 22.98 | 131.00 | 373.50 | 1938.65 | 22.15 | 70.00 | 340.00 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-05:49 | 3960.04 | 22.54 | 108.33 | 332.33 | 1557.02 | 21.78 | 67.17 | 308.83 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:19 | 3651.12 | 22.94 | 79.83 | 290.33 | 2053.80 | 23.69 | 68.00 | 250.00 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:39 | 2486.69 | 21.33 | 70.50 | 242.83 | 1298.53 | 21.79 | 81.00 | 201.67 |
December | 251.17 | 0.52 | 0.48 | 01-DEC-07:40 | 2621.82 | 23.62 | 91.83 | 233.00 | 1547.91 | 24.16 | 97.17 | 195.17 |
Annual Sum or Average | 3902.00 | 0.50 | 3612.72 | 22.18 | 1153.83 | 3831.50 | 1859.65 | 22.96 | 957.33 | 3410.67 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2470.79 | 21.00 | 70.50 | 233.00 | 1298.53 | 21.78 | 58.67 | 195.17 | |
Maximum of Months | 430.33 | 0.53 | 0.48 | 4852.18 | 23.62 | 131.00 | 406.67 | 2348.44 | 24.16 | 97.17 | 376.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.55 | 0.48 | 01-JAN-08:00 | 561.88 | 14.46 | 0.00 | 219.17 | 375.14 | 17.24 | 0.00 | 156.50 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 669.75 | 16.01 | 0.00 | 241.33 | 462.42 | 18.71 | 1.50 | 176.17 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:19 | 869.31 | 17.35 | 0.00 | 315.67 | 564.64 | 19.73 | 10.83 | 261.33 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1160.94 | 18.58 | 0.00 | 345.67 | 690.29 | 20.73 | 78.33 | 302.17 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:00 | 1410.42 | 19.27 | 4.50 | 408.67 | 785.99 | 21.47 | 204.00 | 381.00 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 1542.23 | 21.90 | 76.17 | 418.17 | 863.67 | 24.04 | 255.17 | 404.83 |
July | 430.33 | 0.49 | 0.48 | 01-JUL-05:30 | 1453.34 | 20.28 | 35.67 | 420.00 | 805.96 | 22.46 | 236.83 | 393.50 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1130.92 | 18.46 | 2.83 | 380.00 | 701.28 | 20.64 | 113.83 | 347.00 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 952.33 | 17.85 | 0.00 | 330.83 | 602.78 | 20.13 | 42.83 | 290.33 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:00 | 812.11 | 17.11 | 0.00 | 281.33 | 547.99 | 19.64 | 1.33 | 218.67 |
November | 257.67 | 0.53 | 0.48 | 01-NOV-08:50 | 630.78 | 15.48 | 0.00 | 229.50 | 429.70 | 18.22 | 0.33 | 168.67 |
December | 251.17 | 0.53 | 0.48 | 01-DEC-08:30 | 580.44 | 15.08 | 0.00 | 217.83 | 385.47 | 17.88 | 0.00 | 151.17 |
Annual Sum or Average | 3902.00 | 0.51 | 1047.62 | 18.05 | 119.17 | 3808.17 | 632.52 | 20.42 | 945.00 | 3251.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 561.88 | 14.46 | 0.00 | 217.83 | 375.14 | 17.24 | 0.00 | 151.17 | |
Maximum of Months | 430.33 | 0.55 | 0.48 | 1542.23 | 21.90 | 76.17 | 420.00 | 863.67 | 24.04 | 255.17 | 404.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.51 | 0.48 | 01-JAN-08:00 | 2956.45 | 24.16 | 108.67 | 252.17 | 1770.26 | 24.45 | 104.33 | 219.00 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 3024.31 | 21.70 | 68.50 | 255.83 | 1733.33 | 23.94 | 73.67 | 214.17 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-07:30 | 3562.68 | 22.98 | 99.33 | 328.50 | 2025.92 | 23.79 | 91.17 | 294.50 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 3330.95 | 21.52 | 85.33 | 347.50 | 1513.87 | 21.47 | 39.33 | 312.50 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:30 | 2880.74 | 18.33 | 53.17 | 398.50 | 1519.72 | 19.14 | 6.50 | 367.50 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:49 | 3421.95 | 15.28 | 1.83 | 403.33 | 1934.97 | 18.78 | 1.00 | 378.33 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-06:10 | 2885.83 | 17.92 | 54.83 | 405.33 | 1579.80 | 18.93 | 7.50 | 376.17 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:19 | 2994.80 | 17.88 | 53.67 | 380.67 | 1706.67 | 18.89 | 8.33 | 357.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:40 | 3332.56 | 22.34 | 109.83 | 334.50 | 1810.81 | 23.37 | 98.67 | 310.00 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:00 | 4290.26 | 23.95 | 93.83 | 295.83 | 1695.50 | 23.65 | 66.50 | 260.00 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:50 | 2991.04 | 24.46 | 96.50 | 252.67 | 1714.95 | 25.00 | 99.83 | 214.50 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-08:30 | 2355.03 | 22.36 | 80.67 | 240.67 | 1422.42 | 24.74 | 93.83 | 212.83 |
Annual Sum or Average | 3902.00 | 0.50 | 3161.00 | 20.54 | 906.17 | 3895.50 | 1704.14 | 21.70 | 690.67 | 3517.00 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2355.03 | 15.28 | 1.83 | 240.67 | 1422.42 | 18.78 | 1.00 | 212.83 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 4290.26 | 24.46 | 109.83 | 405.33 | 2025.92 | 25.00 | 104.33 | 378.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:49 | 10373.60 | 39.34 | 274.17 | 267.83 | 5523.90 | 33.85 | 205.33 | 259.00 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 13943.54 | 39.05 | 241.00 | 263.00 | 2197.93 | 22.23 | 69.67 | 240.83 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:00 | 2723.10 | 15.35 | 10.33 | 327.83 | 1497.05 | 18.54 | 19.00 | 289.67 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 2026.45 | 15.27 | 0.00 | 339.00 | 1171.96 | 18.80 | 16.83 | 298.67 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1823.21 | 15.36 | 0.00 | 391.50 | 1003.21 | 18.85 | 3.50 | 354.17 |
June | 421.50 | 0.51 | 0.48 | 01-JUN-05:49 | 1481.48 | 15.08 | 0.00 | 390.00 | 889.14 | 18.67 | 0.00 | 348.83 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:10 | 1662.14 | 15.06 | 0.00 | 394.17 | 940.20 | 18.57 | 4.33 | 354.67 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 1773.32 | 14.85 | 0.00 | 369.00 | 1078.52 | 18.41 | 20.00 | 333.83 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 2900.87 | 16.73 | 29.50 | 331.50 | 1326.52 | 18.58 | 15.33 | 302.33 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:40 | 13588.53 | 36.18 | 239.67 | 300.00 | 1839.24 | 18.86 | 21.67 | 273.67 |
November | 257.67 | 0.49 | 0.48 | 01-NOV-08:39 | 11850.67 | 38.57 | 248.50 | 262.83 | 3481.37 | 27.91 | 131.83 | 240.83 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 9577.86 | 37.58 | 233.50 | 254.33 | 7837.92 | 40.39 | 247.17 | 246.33 |
Annual Sum or Average | 3902.00 | 0.50 | 5266.78 | 22.92 | 1276.67 | 3891.00 | 2126.57 | 21.96 | 754.67 | 3542.83 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1481.48 | 14.85 | 0.00 | 254.33 | 889.14 | 18.41 | 0.00 | 240.83 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 13943.54 | 39.34 | 274.17 | 394.17 | 7837.92 | 40.39 | 247.17 | 354.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.53 | 0.48 | 01-JAN-07:49 | 2406.25 | 20.52 | 82.67 | 233.67 | 1442.05 | 23.27 | 94.00 | 203.33 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 3857.75 | 22.86 | 84.33 | 249.50 | 2277.68 | 23.66 | 70.67 | 204.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:49 | 3506.00 | 20.27 | 68.83 | 315.67 | 2031.95 | 23.04 | 72.00 | 279.17 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 3997.26 | 21.42 | 84.83 | 340.83 | 1745.70 | 22.55 | 54.50 | 298.17 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:40 | 3194.45 | 21.34 | 111.67 | 399.33 | 1723.71 | 22.84 | 86.17 | 364.67 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-04:00 | 3811.40 | 20.96 | 109.00 | 402.50 | 2149.97 | 22.57 | 79.83 | 373.50 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:10 | 3417.29 | 21.06 | 114.50 | 404.50 | 1832.86 | 22.56 | 86.67 | 372.17 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:40 | 4657.50 | 21.37 | 116.50 | 368.83 | 1849.40 | 21.98 | 69.83 | 337.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-05:49 | 3866.36 | 22.08 | 108.33 | 330.33 | 1479.41 | 21.59 | 61.00 | 307.00 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:19 | 3556.48 | 22.47 | 79.83 | 289.00 | 1974.79 | 23.48 | 63.50 | 244.50 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:39 | 2392.56 | 20.69 | 69.50 | 239.67 | 1238.95 | 21.57 | 76.83 | 200.33 |
December | 251.17 | 0.52 | 0.48 | 01-DEC-07:49 | 2406.15 | 21.34 | 78.00 | 228.33 | 1495.91 | 23.95 | 93.50 | 192.17 |
Annual Sum or Average | 3902.00 | 0.51 | 3485.78 | 21.33 | 1108.00 | 3802.17 | 1782.53 | 22.69 | 908.50 | 3377.00 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2392.56 | 20.27 | 68.83 | 228.33 | 1238.95 | 21.57 | 54.50 | 192.17 | |
Maximum of Months | 430.33 | 0.53 | 0.48 | 4657.50 | 22.86 | 116.50 | 404.50 | 2277.68 | 23.95 | 94.00 | 373.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.55 | 0.48 | 01-JAN-08:00 | 541.66 | 10.86 | 0.00 | 214.67 | 365.10 | 14.80 | 0.00 | 150.67 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 647.35 | 12.57 | 0.00 | 239.00 | 451.84 | 16.51 | 0.00 | 172.00 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-07:30 | 840.34 | 14.11 | 0.00 | 313.67 | 550.13 | 17.76 | 0.00 | 253.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1121.65 | 15.32 | 0.00 | 344.17 | 669.16 | 18.82 | 9.50 | 295.67 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:00 | 1361.02 | 15.67 | 0.00 | 406.67 | 758.51 | 19.31 | 20.50 | 377.00 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 1460.28 | 15.87 | 0.00 | 416.33 | 834.75 | 22.29 | 110.17 | 402.67 |
July | 430.33 | 0.49 | 0.48 | 01-JUL-05:30 | 1396.28 | 15.58 | 0.00 | 416.50 | 777.93 | 20.45 | 61.67 | 391.83 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1118.37 | 15.17 | 0.00 | 380.83 | 681.46 | 18.77 | 22.17 | 344.00 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:30 | 919.91 | 14.63 | 0.00 | 327.67 | 586.01 | 18.22 | 0.00 | 286.67 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:00 | 783.29 | 13.87 | 0.00 | 278.50 | 533.83 | 17.63 | 0.00 | 212.67 |
November | 257.67 | 0.53 | 0.48 | 01-NOV-08:50 | 607.60 | 11.97 | 0.00 | 225.83 | 418.32 | 15.90 | 0.00 | 164.83 |
December | 251.17 | 0.54 | 0.48 | 01-DEC-08:30 | 557.96 | 11.47 | 0.00 | 215.00 | 374.08 | 15.43 | 0.00 | 144.67 |
Annual Sum or Average | 3902.00 | 0.51 | 1010.06 | 14.22 | 0.00 | 3778.83 | 613.33 | 18.37 | 224.00 | 3195.67 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 541.66 | 10.86 | 0.00 | 214.67 | 365.10 | 14.80 | 0.00 | 144.67 | |
Maximum of Months | 430.33 | 0.55 | 0.48 | 1460.28 | 15.87 | 0.00 | 416.50 | 834.75 | 22.29 | 110.17 | 402.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-08:00 | 2891.23 | 23.80 | 108.67 | 250.00 | 1715.82 | 24.36 | 104.00 | 215.67 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 2937.24 | 21.28 | 68.50 | 254.17 | 1661.33 | 23.84 | 72.83 | 210.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:30 | 3476.67 | 22.57 | 99.33 | 326.67 | 1955.01 | 23.67 | 88.33 | 289.50 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 3244.53 | 21.08 | 85.33 | 344.83 | 1447.07 | 21.31 | 38.83 | 308.33 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:30 | 2792.87 | 17.83 | 53.17 | 397.00 | 1454.50 | 18.96 | 4.67 | 364.33 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:00 | 3322.49 | 14.75 | 1.83 | 401.17 | 1841.17 | 18.60 | 1.00 | 374.83 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-06:10 | 2800.80 | 17.42 | 54.83 | 403.83 | 1517.12 | 18.74 | 5.50 | 374.67 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:19 | 2908.59 | 17.39 | 53.67 | 379.67 | 1637.99 | 18.72 | 7.83 | 354.33 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:40 | 3251.92 | 21.91 | 109.83 | 332.17 | 1739.44 | 23.04 | 94.50 | 306.00 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:00 | 4193.72 | 23.45 | 92.83 | 294.00 | 1554.14 | 22.47 | 57.00 | 252.83 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:50 | 2755.46 | 21.58 | 77.17 | 248.83 | 1654.72 | 24.91 | 99.17 | 212.50 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-08:30 | 2289.34 | 21.97 | 80.67 | 239.67 | 1368.88 | 24.66 | 92.50 | 208.83 |
Annual Sum or Average | 3902.00 | 0.50 | 3066.01 | 19.92 | 885.83 | 3872.00 | 1630.95 | 21.47 | 666.17 | 3472.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2289.34 | 14.75 | 1.83 | 239.67 | 1368.88 | 18.60 | 1.00 | 208.83 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 4193.72 | 23.80 | 109.83 | 403.83 | 1955.01 | 24.91 | 104.00 | 374.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:49 | 10373.60 | 39.34 | 274.17 | 267.83 | 5523.82 | 33.85 | 205.33 | 259.00 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 13943.51 | 39.05 | 241.00 | 263.00 | 2197.85 | 22.23 | 69.67 | 240.83 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:00 | 2723.01 | 15.35 | 10.33 | 327.83 | 1496.97 | 18.54 | 19.00 | 289.67 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 2026.34 | 15.28 | 0.00 | 339.00 | 1171.87 | 18.80 | 16.83 | 298.67 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1823.10 | 15.36 | 0.00 | 391.50 | 1003.13 | 18.85 | 3.50 | 354.17 |
June | 421.50 | 0.51 | 0.48 | 01-JUN-05:49 | 1481.42 | 15.08 | 0.00 | 390.00 | 889.08 | 18.67 | 0.17 | 348.67 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:10 | 1662.05 | 15.06 | 0.00 | 394.17 | 940.13 | 18.57 | 4.33 | 354.67 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 1773.24 | 14.85 | 0.00 | 369.00 | 1078.45 | 18.41 | 20.00 | 333.67 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 2900.76 | 16.73 | 29.50 | 331.50 | 1326.43 | 18.58 | 15.33 | 302.33 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:40 | 13588.46 | 36.18 | 239.67 | 300.00 | 1839.15 | 18.86 | 21.67 | 273.67 |
November | 257.67 | 0.49 | 0.48 | 01-NOV-08:39 | 11850.67 | 38.57 | 248.50 | 262.83 | 3481.27 | 27.91 | 131.83 | 240.83 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 9577.89 | 37.58 | 233.50 | 254.33 | 7837.83 | 40.39 | 247.17 | 246.33 |
Annual Sum or Average | 3902.00 | 0.50 | 5266.71 | 22.92 | 1276.67 | 3891.00 | 2126.49 | 21.96 | 754.83 | 3542.50 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1481.42 | 14.85 | 0.00 | 254.33 | 889.08 | 18.41 | 0.17 | 240.83 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 13943.51 | 39.34 | 274.17 | 394.17 | 7837.83 | 40.39 | 247.17 | 354.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.53 | 0.48 | 01-JAN-07:49 | 2406.24 | 20.52 | 82.67 | 233.67 | 1442.02 | 23.27 | 94.00 | 203.33 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 3857.75 | 22.86 | 84.33 | 249.50 | 2277.64 | 23.66 | 70.83 | 204.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:49 | 3505.98 | 20.27 | 68.83 | 315.67 | 2031.89 | 23.04 | 72.00 | 279.17 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 3997.21 | 21.42 | 84.83 | 340.83 | 1745.63 | 22.56 | 54.50 | 298.17 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:40 | 3194.38 | 21.34 | 111.67 | 399.33 | 1723.62 | 22.84 | 86.33 | 364.67 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-04:00 | 3811.36 | 20.96 | 109.00 | 402.50 | 2149.89 | 22.57 | 79.83 | 373.50 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:10 | 3417.23 | 21.06 | 114.50 | 404.50 | 1832.78 | 22.56 | 86.67 | 372.17 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:40 | 4657.46 | 21.37 | 116.50 | 368.83 | 1849.33 | 21.98 | 69.83 | 337.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-05:49 | 3866.32 | 22.08 | 108.33 | 330.33 | 1479.35 | 21.59 | 61.00 | 307.00 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:19 | 3556.47 | 22.47 | 79.83 | 289.00 | 1974.74 | 23.48 | 63.50 | 244.50 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:39 | 2392.56 | 20.70 | 69.50 | 239.67 | 1238.91 | 21.57 | 76.83 | 200.33 |
December | 251.17 | 0.52 | 0.48 | 01-DEC-07:49 | 2406.14 | 21.35 | 78.00 | 228.33 | 1495.88 | 23.95 | 93.50 | 192.17 |
Annual Sum or Average | 3902.00 | 0.51 | 3485.75 | 21.34 | 1108.00 | 3802.17 | 1782.47 | 22.69 | 908.83 | 3377.00 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2392.56 | 20.27 | 68.83 | 228.33 | 1238.91 | 21.57 | 54.50 | 192.17 | |
Maximum of Months | 430.33 | 0.53 | 0.48 | 4657.46 | 22.86 | 116.50 | 404.50 | 2277.64 | 23.95 | 94.00 | 373.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.55 | 0.48 | 01-JAN-08:00 | 541.66 | 10.86 | 0.00 | 214.67 | 365.08 | 14.80 | 0.00 | 150.67 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 647.35 | 12.58 | 0.00 | 239.00 | 451.82 | 16.51 | 0.00 | 172.00 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-07:30 | 840.33 | 14.11 | 0.00 | 313.67 | 550.10 | 17.76 | 0.00 | 253.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1121.62 | 15.32 | 0.00 | 344.17 | 669.12 | 18.82 | 9.50 | 295.67 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:00 | 1360.97 | 15.67 | 0.00 | 406.67 | 758.46 | 19.31 | 20.50 | 377.00 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 1460.24 | 15.87 | 0.00 | 416.33 | 834.70 | 22.29 | 110.17 | 402.67 |
July | 430.33 | 0.49 | 0.48 | 01-JUL-05:30 | 1396.23 | 15.58 | 0.00 | 416.50 | 777.88 | 20.45 | 61.67 | 391.83 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1118.35 | 15.18 | 0.00 | 380.83 | 681.42 | 18.77 | 22.17 | 344.00 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:30 | 919.89 | 14.64 | 0.00 | 327.67 | 585.98 | 18.22 | 0.00 | 286.67 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:00 | 783.29 | 13.87 | 0.00 | 278.50 | 533.80 | 17.63 | 0.00 | 212.67 |
November | 257.67 | 0.53 | 0.48 | 01-NOV-08:50 | 607.60 | 11.97 | 0.00 | 225.83 | 418.30 | 15.90 | 0.00 | 164.83 |
December | 251.17 | 0.54 | 0.48 | 01-DEC-08:30 | 557.96 | 11.47 | 0.00 | 215.00 | 374.06 | 15.43 | 0.00 | 144.67 |
Annual Sum or Average | 3902.00 | 0.51 | 1010.04 | 14.22 | 0.00 | 3778.83 | 613.30 | 18.37 | 224.00 | 3195.67 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 541.66 | 10.86 | 0.00 | 214.67 | 365.08 | 14.80 | 0.00 | 144.67 | |
Maximum of Months | 430.33 | 0.55 | 0.48 | 1460.24 | 15.87 | 0.00 | 416.50 | 834.70 | 22.29 | 110.17 | 402.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-08:00 | 2891.22 | 23.80 | 108.67 | 250.00 | 1715.78 | 24.36 | 104.00 | 215.67 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 2937.24 | 21.28 | 68.50 | 254.17 | 1661.29 | 23.84 | 72.83 | 210.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:30 | 3476.65 | 22.57 | 99.33 | 326.67 | 1954.95 | 23.67 | 88.50 | 289.50 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 3244.47 | 21.08 | 85.33 | 344.83 | 1447.00 | 21.31 | 38.83 | 308.33 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:30 | 2792.78 | 17.84 | 53.17 | 397.00 | 1454.41 | 18.96 | 4.67 | 364.33 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:00 | 3322.44 | 14.75 | 1.83 | 401.17 | 1841.10 | 18.60 | 1.00 | 374.83 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-06:10 | 2800.73 | 17.43 | 54.83 | 403.83 | 1517.04 | 18.74 | 5.67 | 374.67 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:19 | 2908.56 | 17.40 | 53.67 | 379.67 | 1637.93 | 18.72 | 7.83 | 354.33 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:40 | 3251.88 | 21.92 | 109.83 | 332.17 | 1739.37 | 23.04 | 94.50 | 306.00 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:00 | 4193.72 | 23.46 | 92.83 | 294.00 | 1554.09 | 22.47 | 57.00 | 252.83 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:50 | 2755.46 | 21.58 | 77.17 | 248.83 | 1654.68 | 24.91 | 99.17 | 212.50 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-08:30 | 2289.33 | 21.97 | 80.67 | 239.67 | 1368.84 | 24.66 | 92.50 | 208.83 |
Annual Sum or Average | 3902.00 | 0.50 | 3065.97 | 19.92 | 885.83 | 3872.00 | 1630.89 | 21.47 | 666.50 | 3472.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2289.33 | 14.75 | 1.83 | 239.67 | 1368.84 | 18.60 | 1.00 | 208.83 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 4193.72 | 23.80 | 109.83 | 403.83 | 1954.95 | 24.91 | 104.00 | 374.83 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.774226E+10 | 19469.74 | 05-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.793182E+10 | 18479.80 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.520389E+10 | 17304.14 | 02-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.301326E+10 | 17935.97 | 17-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247669E+09 | 8487.19 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 256105.50 | 4.33 | 19-JUN-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 542731.27 | 4.34 | 31-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 344377.39 | 4.47 | 28-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158979E+09 | 9462.00 | 22-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.314461E+10 | 18200.34 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.587669E+10 | 18444.36 | 30-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.917305E+10 | 20382.93 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.424934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 256105.50 | 4.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.917305E+10 | 20382.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6122613.57 | 11456.46 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6122613.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6122613.57 | 11456.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.194412E+10 | 8619.99 | 05-JAN-18:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230210E+10 | 7961.41 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.201895E+10 | 7773.29 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142759E+10 | 7787.69 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.516435E+09 | 7802.03 | 11-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11023172.34 | 7697.88 | 09-JUN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2933855.55 | 2872.48 | 03-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1039773.45 | 3479.84 | 23-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81579981.32 | 7940.54 | 22-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139203E+10 | 7966.10 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148519E+10 | 8180.39 | 29-NOV-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281138E+10 | 8989.12 | 21-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1039773.45 | 2872.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.281138E+10 | 8989.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.582718E+09 | 6529.82 | 05-JAN-18:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.765998E+09 | 6057.00 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.349392E+09 | 5855.90 | 24-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136423E+09 | 5865.97 | 17-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 458370.19 | 2296.13 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146188E+09 | 5960.04 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.220339E+09 | 6041.59 | 30-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104560E+10 | 6749.48 | 21-DEC-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.324712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104560E+10 | 6749.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160597E+10 | 7090.26 | 05-JAN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182674E+10 | 6618.78 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.879723E+09 | 6494.18 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.355740E+09 | 6463.30 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10368279.34 | 6398.73 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247495E+09 | 6586.74 | 30-OCT-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.527712E+09 | 6680.59 | 30-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213225E+10 | 7335.56 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.758601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.213225E+10 | 7335.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.606435E+09 | 6690.16 | 05-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.778744E+09 | 6328.57 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388200E+09 | 6207.54 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167569E+09 | 6137.48 | 17-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4462627.96 | 6113.19 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148022E+09 | 6226.94 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209943E+09 | 6312.60 | 30-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109503E+10 | 7028.18 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.339841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109503E+10 | 7028.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.755396E+10 | 20200.30 | 05-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.769081E+10 | 19104.30 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.524672E+10 | 18097.16 | 02-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.326680E+10 | 18065.63 | 17-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.337355E+09 | 8634.59 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 283701.86 | 185.93 | 09-JUN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 514116.94 | 4.53 | 24-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 321295.22 | 4.37 | 28-AUG-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.235411E+09 | 8935.82 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.362327E+10 | 19273.91 | 30-OCT-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.612101E+10 | 19330.08 | 29-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.916560E+10 | 20897.43 | 21-DEC-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 283701.86 | 4.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.916560E+10 | 20897.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.146254E+09 | 16128.72 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359467E+09 | 16123.63 | 08-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85021690.07 | 16192.25 | 21-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30108687.25 | 16072.96 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28594995.82 | 16067.82 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38474107.93 | 16070.85 | 01-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.833527E+09 | 16169.66 | 27-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.833527E+09 | 16192.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.443569E+09 | 8937.98 | 05-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.715072E+09 | 8429.71 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.341691E+09 | 8342.36 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.200353E+09 | 8344.68 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4259810.55 | 6787.31 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.335074E+09 | 8510.78 | 30-OCT-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.314772E+09 | 8534.88 | 29-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107235E+10 | 9331.48 | 21-DEC-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107235E+10 | 9331.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.493465E+09 | 7285.42 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.592515E+09 | 6599.67 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227976E+09 | 6529.18 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113416E+09 | 6527.19 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 258027.85 | 1720.19 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.236690E+09 | 6663.54 | 30-OCT-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.315871E+09 | 6682.89 | 29-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119061E+10 | 7603.74 | 21-DEC-16:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119061E+10 | 7603.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105435E+10 | 7442.48 | 05-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118472E+10 | 7105.69 | 13-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.460295E+09 | 7010.37 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.225549E+09 | 6958.57 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3260575.23 | 5129.27 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360791E+09 | 7190.23 | 30-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.606348E+09 | 7221.73 | 30-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208933E+10 | 7944.84 | 21-DEC-17:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.598464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208933E+10 | 7944.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.521887E+09 | 7413.92 | 05-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.641276E+09 | 6783.31 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262142E+09 | 6781.91 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144249E+09 | 6714.08 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2657047.64 | 4303.67 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45881.74 | 458.82 | 22-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.237904E+09 | 6849.04 | 30-OCT-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.329070E+09 | 6869.03 | 29-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130821E+10 | 7649.73 | 21-DEC-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130821E+10 | 7649.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.797357E+10 | 19630.54 | 05-JAN-08:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.809389E+10 | 17665.52 | 02-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.558231E+10 | 18603.72 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.354317E+10 | 18016.87 | 15-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.434043E+09 | 11254.68 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1190430.63 | 1394.03 | 09-JUN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 458284.72 | 4.89 | 31-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 287986.10 | 4.68 | 24-AUG-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.294731E+09 | 13091.74 | 22-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.408706E+10 | 18426.21 | 31-OCT-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.655635E+10 | 18735.11 | 29-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.970258E+10 | 19941.58 | 20-DEC-08:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.462696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 287986.10 | 4.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.970258E+10 | 19941.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152454E+10 | 22832.35 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185328E+10 | 22728.16 | 15-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.771873E+09 | 22721.41 | 21-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.512012E+09 | 22733.51 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9553430.58 | 22602.20 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.629394E+09 | 22657.05 | 31-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.827210E+09 | 22736.39 | 21-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324690E+10 | 23493.49 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.937476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.324690E+10 | 23493.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116531E+10 | 10895.10 | 05-JAN-08:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148771E+10 | 9944.93 | 06-FEB-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.930551E+09 | 10370.51 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570499E+09 | 9962.29 | 24-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35775341.22 | 9946.97 | 03-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9712255.17 | 9929.73 | 22-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.838928E+09 | 10195.96 | 31-OCT-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.918530E+09 | 10375.29 | 29-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230205E+10 | 11075.22 | 20-DEC-08:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.825906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.230205E+10 | 11075.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112579E+10 | 8371.91 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120609E+10 | 7736.13 | 02-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.619411E+09 | 7426.71 | 22-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337267E+09 | 7438.23 | 15-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9162277.57 | 7416.87 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4864194.92 | 7415.31 | 22-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.591372E+09 | 7614.65 | 31-OCT-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.820617E+09 | 7749.44 | 29-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227121E+10 | 8747.87 | 21-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.698579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.227121E+10 | 8747.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.228097E+10 | 9459.24 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.238718E+10 | 8801.30 | 02-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120760E+10 | 8761.63 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.655748E+09 | 8422.01 | 25-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32472825.87 | 8406.72 | 03-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11551065.70 | 8392.75 | 22-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.934873E+09 | 8831.44 | 30-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160557E+10 | 8784.87 | 29-NOV-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.400073E+10 | 9752.71 | 21-DEC-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.400073E+10 | 9752.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124251E+10 | 8883.84 | 05-JAN-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134560E+10 | 7923.14 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.709833E+09 | 8269.16 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.407519E+09 | 7939.17 | 15-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23439649.16 | 7928.14 | 03-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8312514.93 | 7914.39 | 22-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.598598E+09 | 8128.49 | 31-OCT-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.897806E+09 | 8272.98 | 29-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252563E+10 | 9115.84 | 22-DEC-08:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.775924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.252563E+10 | 9115.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.132034E+10 | 0.131933E+10 | 23049.57 | 24-JAN-15:10 | 23049.57 | 0.00 |
February | 0.00 | 0.00 | 0.690257E+09 | 0.685961E+09 | 18710.78 | 27-FEB-12:00 | 18710.78 | 0.00 |
March | 0.00 | 0.00 | 0.305143E+10 | 0.301724E+10 | 34487.07 | 13-MAR-16:00 | 34487.07 | 0.00 |
April | 0.00 | 0.00 | 0.341357E+10 | 0.334049E+10 | 20744.77 | 13-APR-12:50 | 20744.77 | 0.00 |
May | 0.00 | 0.00 | 0.122562E+11 | 0.119634E+11 | 43393.65 | 31-MAY-16:00 | 43393.65 | 0.00 |
June | 0.00 | 0.00 | 0.475904E+11 | 0.453964E+11 | 71521.44 | 26-JUN-15:20 | 71521.44 | 0.00 |
July | 0.00 | 0.00 | 0.484526E+11 | 0.447362E+11 | 66734.51 | 17-JUL-10:50 | 66734.51 | 0.00 |
August | 0.00 | 0.00 | 0.481181E+11 | 0.457009E+11 | 65993.01 | 16-AUG-16:00 | 65993.01 | 0.00 |
September | 0.00 | 0.00 | 0.338258E+11 | 0.333469E+11 | 59476.94 | 12-SEP-16:00 | 59476.94 | 0.00 |
October | 0.00 | 0.00 | 0.932015E+10 | 0.924900E+10 | 50647.07 | 10-OCT-15:30 | 50647.07 | 0.00 |
November | 0.00 | 0.00 | 0.312670E+10 | 0.310783E+10 | 29022.88 | 07-NOV-15:10 | 29022.88 | 0.00 |
December | 0.00 | 0.00 | 0.910872E+09 | 0.909704E+09 | 17121.55 | 01-DEC-14:00 | 17121.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.212076E+12 | 0.202773E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.690257E+09 | 0.685961E+09 | 17121.55 | 17121.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.484526E+11 | 0.457009E+11 | 71521.44 | 71521.44 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.180998E+10 | 0.179630E+10 | 22428.82 | 24-JAN-15:05 | 22428.82 | 0.00 |
February | 0.00 | 0.00 | 0.104475E+10 | 0.101878E+10 | 15795.98 | 18-FEB-13:05 | 15795.98 | 0.00 |
March | 0.00 | 0.00 | 0.344404E+10 | 0.344270E+10 | 37461.29 | 13-MAR-15:50 | 37461.29 | 0.00 |
April | 0.00 | 0.00 | 0.269549E+10 | 0.265912E+10 | 24236.87 | 20-APR-13:00 | 24236.87 | 0.00 |
May | 0.00 | 0.00 | 0.130174E+11 | 0.126811E+11 | 47038.36 | 16-MAY-14:05 | 47038.36 | 0.00 |
June | 0.00 | 0.00 | 0.470722E+11 | 0.449210E+11 | 70568.22 | 26-JUN-15:00 | 70568.22 | 0.00 |
July | 0.00 | 0.00 | 0.477707E+11 | 0.441445E+11 | 67446.03 | 17-JUL-10:30 | 67446.03 | 0.00 |
August | 0.00 | 0.00 | 0.454463E+11 | 0.431690E+11 | 65528.70 | 16-AUG-15:00 | 65528.70 | 0.00 |
September | 0.00 | 0.00 | 0.304135E+11 | 0.299395E+11 | 58652.86 | 11-SEP-14:05 | 58652.86 | 0.00 |
October | 0.00 | 0.00 | 0.725180E+10 | 0.721421E+10 | 49021.63 | 11-OCT-14:05 | 49021.63 | 0.00 |
November | 0.00 | 0.00 | 0.291870E+10 | 0.288152E+10 | 29477.08 | 07-NOV-15:05 | 29477.08 | 0.00 |
December | 0.00 | 0.00 | 0.122136E+10 | 0.121769E+10 | 19475.82 | 01-DEC-14:00 | 19475.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.204106E+12 | 0.195085E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.104475E+10 | 0.101878E+10 | 15795.98 | 15795.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.477707E+11 | 0.449210E+11 | 70568.22 | 70568.22 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.147504E+10 | 0.145577E+10 | 21979.74 | 24-JAN-14:40 | 21979.74 | 0.00 |
February | 0.00 | 0.00 | 0.170501E+10 | 0.167802E+10 | 20049.48 | 27-FEB-15:10 | 20049.48 | 0.00 |
March | 0.00 | 0.00 | 0.360248E+10 | 0.359986E+10 | 39205.08 | 13-MAR-15:50 | 39205.08 | 0.00 |
April | 0.00 | 0.00 | 0.276617E+10 | 0.271838E+10 | 26529.09 | 20-APR-13:00 | 26529.09 | 0.00 |
May | 0.00 | 0.00 | 0.139620E+11 | 0.135015E+11 | 55037.66 | 31-MAY-15:20 | 55037.66 | 0.00 |
June | 0.00 | 0.00 | 0.516232E+11 | 0.492685E+11 | 81946.93 | 26-JUN-15:10 | 81946.93 | 0.00 |
July | 0.00 | 0.00 | 0.517784E+11 | 0.478875E+11 | 74737.57 | 17-JUL-14:00 | 74737.57 | 0.00 |
August | 0.00 | 0.00 | 0.493515E+11 | 0.469275E+11 | 77302.69 | 16-AUG-15:00 | 77302.69 | 0.00 |
September | 0.00 | 0.00 | 0.313422E+11 | 0.307051E+11 | 65530.25 | 12-SEP-15:40 | 65530.25 | 0.00 |
October | 0.00 | 0.00 | 0.651527E+10 | 0.645804E+10 | 53397.10 | 11-OCT-14:50 | 53397.10 | 0.00 |
November | 0.00 | 0.00 | 0.276326E+10 | 0.272002E+10 | 28834.60 | 07-NOV-14:50 | 28834.60 | 0.00 |
December | 0.00 | 0.00 | 0.119100E+10 | 0.118527E+10 | 18328.20 | 01-DEC-14:00 | 18328.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.218076E+12 | 0.208106E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.119100E+10 | 0.118527E+10 | 18328.20 | 18328.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.517784E+11 | 0.492685E+11 | 81946.93 | 81946.93 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 14072.71 | 176805.46 | 05-JAN-07:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16876.67 | 169001.83 | 06-FEB-07:06 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 9361.23 | 167678.80 | 02-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5778.86 | 162015.00 | 25-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 623.35 | 150009.26 | 01-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 4.56 | 8416.93 | 09-JUN-06:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.99 | 3065.67 | 03-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.68 | 5607.21 | 23-AUG-06:08 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 306.56 | 90871.14 | 22-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6513.83 | 151744.01 | 31-OCT-06:12 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10585.80 | 157734.11 | 30-NOV-07:12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 20742.76 | 189304.25 | 23-DEC-07:07 |
Annual Sum or Average | 0.00 | 7023.57 | ||||
Minimum of Months | 0.00 | 0.00 | 0.68 | 3065.67 | ||
Maximum of Months | 0.00 | 0.00 | 20742.76 | 189304.25 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1806.24 | 6633.45 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1839.63 | 6650.93 | 14-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1938.73 | 6625.00 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1732.73 | 6419.05 | 03-APR-11:16 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1701.34 | 6125.95 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1644.89 | 5759.56 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1432.33 | 5439.71 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1559.71 | 5288.00 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1478.36 | 5461.94 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1548.77 | 5791.07 | 31-OCT-11:12 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1670.26 | 6145.81 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1689.79 | 6442.66 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 1669.26 | ||||
Minimum of Months | 0.00 | 0.00 | 1432.33 | 5288.00 | ||
Maximum of Months | 0.00 | 0.00 | 1938.73 | 6650.93 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142795E+10 | 0.38 | 3375.10 | 24-JAN-16:20 | 1.06 |
February | 0.132496E+10 | 0.38 | 3291.16 | 27-FEB-15:40 | 1.05 |
March | 0.186639E+10 | 0.42 | 5792.14 | 15-MAR-16:00 | 1.47 |
April | 0.152228E+10 | 0.37 | 3217.82 | 12-APR-14:10 | 1.04 |
May | 0.268287E+10 | 0.44 | 5622.87 | 16-MAY-14:30 | 1.43 |
June | 0.597268E+10 | 0.69 | 11041.98 | 26-JUN-12:08 | 2.18 |
July | 0.570729E+10 | 0.65 | 11041.98 | 24-JUL-15:10 | 2.18 |
August | 0.599149E+10 | 0.67 | 10012.64 | 17-AUG-16:00 | 2.06 |
September | 0.481902E+10 | 0.61 | 11041.98 | 05-SEP-06:02 | 2.19 |
October | 0.254476E+10 | 0.44 | 6038.37 | 13-OCT-16:00 | 1.51 |
November | 0.170785E+10 | 0.39 | 4401.83 | 08-NOV-15:50 | 1.24 |
December | 0.138060E+10 | 0.37 | 2685.60 | 26-DEC-07:03 | 0.94 |
Annual Sum or Average | 0.369481E+11 | 0.48 | |||
Minimum of Months | 0.132496E+10 | 0.37 | 2685.60 | 0.94 | |
Maximum of Months | 0.599149E+10 | 0.69 | 11041.98 | 2.19 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141334E+10 | 0.39 | 2969.02 | 02-JAN-07:02 | 1.00 |
February | 0.134872E+10 | 0.39 | 3101.55 | 27-FEB-15:40 | 1.03 |
March | 0.191655E+10 | 0.44 | 6694.89 | 15-MAR-16:00 | 1.63 |
April | 0.161443E+10 | 0.40 | 4318.41 | 21-APR-13:40 | 1.24 |
May | 0.291543E+10 | 0.48 | 6787.11 | 16-MAY-14:05 | 1.63 |
June | 0.598164E+10 | 0.70 | 10973.07 | 26-JUN-10:10 | 2.19 |
July | 0.568168E+10 | 0.65 | 10973.07 | 17-JUL-05:12 | 2.21 |
August | 0.572714E+10 | 0.66 | 10973.07 | 07-AUG-10:10 | 2.19 |
September | 0.421461E+10 | 0.57 | 10973.07 | 05-SEP-06:02 | 2.21 |
October | 0.211258E+10 | 0.43 | 7325.29 | 10-OCT-16:00 | 1.72 |
November | 0.152301E+10 | 0.40 | 4362.25 | 07-NOV-16:00 | 1.25 |
December | 0.137656E+10 | 0.39 | 2969.02 | 27-DEC-07:02 | 1.00 |
Annual Sum or Average | 0.358257E+11 | 0.49 | |||
Minimum of Months | 0.134872E+10 | 0.39 | 2969.02 | 1.00 | |
Maximum of Months | 0.598164E+10 | 0.70 | 10973.07 | 2.21 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151476E+10 | 0.42 | 2880.33 | 04-JAN-07:01 | 0.90 |
February | 0.152679E+10 | 0.46 | 2880.33 | 06-FEB-07:01 | 0.90 |
March | 0.195615E+10 | 0.48 | 6450.71 | 15-MAR-15:50 | 1.44 |
April | 0.168990E+10 | 0.43 | 4592.71 | 21-APR-13:30 | 1.17 |
May | 0.272346E+10 | 0.47 | 6613.64 | 31-MAY-15:20 | 1.44 |
June | 0.573299E+10 | 0.64 | 11243.28 | 26-JUN-15:10 | 2.02 |
July | 0.535120E+10 | 0.60 | 11559.09 | 17-JUL-10:40 | 2.06 |
August | 0.538294E+10 | 0.61 | 11189.10 | 14-AUG-15:00 | 2.02 |
September | 0.372567E+10 | 0.53 | 9904.32 | 05-SEP-15:30 | 1.86 |
October | 0.197479E+10 | 0.44 | 6869.63 | 11-OCT-16:00 | 1.49 |
November | 0.154736E+10 | 0.43 | 3553.62 | 07-NOV-15:50 | 1.01 |
December | 0.169315E+10 | 0.48 | 2880.33 | 11-DEC-07:03 | 0.90 |
Annual Sum or Average | 0.348192E+11 | 0.50 | |||
Minimum of Months | 0.151476E+10 | 0.42 | 2880.33 | 0.90 | |
Maximum of Months | 0.573299E+10 | 0.64 | 11559.09 | 2.06 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.282936E+09 | 0.257189E+09 | 717.36 | 05-JAN-07:01 | 652.08 | 652.08 | 44.55 | 2.33 |
February | 0.309156E+09 | 0.281023E+09 | 695.47 | 06-FEB-08:14 | 632.18 | 632.18 | 43.84 | 2.25 |
March | 0.198282E+09 | 0.180238E+09 | 662.15 | 02-MAR-07:01 | 601.90 | 601.90 | 40.88 | 2.10 |
April | 0.115050E+09 | 0.104580E+09 | 691.16 | 03-APR-06:17 | 628.26 | 628.26 | 44.71 | 2.23 |
May | 15087797.04 | 13714807.51 | 594.46 | 01-MAY-06:03 | 540.36 | 540.36 | 36.31 | 1.52 |
June | 166865.06 | 151680.34 | 109.38 | 09-JUN-06:06 | 99.42 | 99.42 | 43.23 | 0.12 |
July | 32724.33 | 29746.41 | 39.96 | 03-JUL-06:07 | 36.32 | 36.32 | 42.50 | 0.04 |
August | 20625.68 | 18748.74 | 62.13 | 23-AUG-06:08 | 56.47 | 56.47 | 39.72 | 0.07 |
September | 6490227.29 | 5899616.61 | 484.93 | 22-SEP-06:02 | 440.81 | 440.81 | 33.54 | 0.82 |
October | 0.132684E+09 | 0.120610E+09 | 682.04 | 31-OCT-06:12 | 619.98 | 619.98 | 43.44 | 2.19 |
November | 0.215354E+09 | 0.195757E+09 | 690.09 | 29-NOV-07:01 | 627.29 | 627.29 | 44.52 | 2.23 |
December | 0.378825E+09 | 0.344352E+09 | 743.52 | 23-DEC-07:03 | 675.86 | 675.86 | 42.16 | 2.41 |
Annual Sum or Average | 0.165409E+10 | 0.150356E+10 | ||||||
Minimum of Months | 20625.68 | 18748.74 | 39.96 | 36.32 | 36.32 | 33.54 | 0.04 | |
Maximum of Months | 0.378825E+09 | 0.344352E+09 | 743.52 | 675.86 | 675.86 | 44.71 | 2.41 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.03 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.97 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:02 | 2.06 | 2.06 | 56.87 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.73 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:05 | 2.06 | 2.06 | 56.98 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.16 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 57.23 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.40 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.39 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.21 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:01 | 2.06 | 2.06 | 57.39 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 56.87 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.73 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.21 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 60.00 | 60.00 | 14072.71 | 176805.46 | 05-JAN-07:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 40.52 | 40.52 | 16876.67 | 169001.83 | 06-FEB-07:06 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 33.67 | 33.67 | 9361.23 | 167678.80 | 02-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 31.19 | 31.19 | 5778.86 | 162015.00 | 25-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.11 | 22.11 | 623.35 | 150009.26 | 01-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 43.69 | 43.69 | 4.56 | 8416.93 | 09-JUN-06:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 42.48 | 42.48 | 0.99 | 3065.67 | 03-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 39.71 | 39.71 | 0.68 | 5607.21 | 23-AUG-06:08 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 39.48 | 39.48 | 306.56 | 90871.14 | 22-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 33.61 | 33.61 | 6513.83 | 151744.01 | 31-OCT-06:12 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 45.33 | 45.33 | 10585.80 | 157734.11 | 30-NOV-07:12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 38.78 | 38.78 | 20742.76 | 189304.25 | 23-DEC-07:07 |
Annual Sum or Average | 0.00 | 7023.57 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.11 | 22.11 | 0.68 | 3065.67 | ||
Maximum of Months | 0.00 | 0.00 | 60.00 | 60.00 | 20742.76 | 189304.25 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.03 | 58.03 | 1806.24 | 6633.45 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.46 | 57.46 | 1839.63 | 6650.93 | 14-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.46 | 57.46 | 1938.73 | 6625.00 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.53 | 57.53 | 1732.73 | 6419.05 | 03-APR-11:16 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.13 | 58.13 | 1701.34 | 6125.95 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.80 | 57.80 | 1644.89 | 5759.56 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.91 | 57.91 | 1432.33 | 5439.71 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.99 | 57.99 | 1559.71 | 5288.00 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.99 | 57.99 | 1478.36 | 5461.94 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.05 | 57.05 | 1548.77 | 5791.07 | 31-OCT-11:12 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.79 | 57.79 | 1670.26 | 6145.81 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.65 | 57.65 | 1689.79 | 6442.66 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 1669.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.05 | 57.05 | 1432.33 | 5288.00 | ||
Maximum of Months | 0.00 | 0.00 | 58.13 | 58.13 | 1938.73 | 6650.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.124815E+11 | 0.00 | 0.00 | 0.172795E+10 | 0.00 | 0.00 |
February | 0.136054E+11 | 0.00 | 0.00 | 0.149055E+10 | 0.00 | 0.00 |
March | 0.884015E+10 | 0.00 | 0.00 | 0.254281E+10 | 0.00 | 0.00 |
April | 0.510058E+10 | 0.00 | 0.00 | 0.231554E+10 | 0.00 | 0.00 |
May | 0.779394E+09 | 0.00 | 0.00 | 0.537709E+10 | 0.00 | 0.00 |
June | 11279277.84 | 0.00 | 0.00 | 0.170071E+11 | 0.00 | 0.00 |
July | 3476586.82 | 0.00 | 0.00 | 0.167666E+11 | 0.00 | 0.00 |
August | 1384150.84 | 0.00 | 0.00 | 0.169232E+11 | 0.00 | 0.00 |
September | 0.240559E+09 | 0.00 | 0.00 | 0.122506E+11 | 0.00 | 0.00 |
October | 0.507834E+10 | 0.00 | 0.00 | 0.456358E+10 | 0.00 | 0.00 |
November | 0.831988E+10 | 0.00 | 0.00 | 0.240864E+10 | 0.00 | 0.00 |
December | 0.162634E+11 | 0.00 | 0.00 | 0.159577E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.707254E+11 | 0.00 | 0.00 | 0.849696E+11 | 0.00 | 0.00 |
Minimum of Months | 1384150.84 | 0.00 | 0.00 | 0.149055E+10 | 0.00 | 0.00 |
Maximum of Months | 0.162634E+11 | 0.00 | 0.00 | 0.170071E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.102135E+11 | 0.00 | 0.00 | 0.182662E+10 | 0.00 | 0.00 |
February | 0.111839E+11 | 0.00 | 0.00 | 0.160035E+10 | 0.00 | 0.00 |
March | 0.662384E+10 | 0.00 | 0.00 | 0.267229E+10 | 0.00 | 0.00 |
April | 0.398047E+10 | 0.00 | 0.00 | 0.223537E+10 | 0.00 | 0.00 |
May | 0.347791E+09 | 0.00 | 0.00 | 0.576101E+10 | 0.00 | 0.00 |
June | 283701.86 | 0.00 | 0.00 | 0.168922E+11 | 0.00 | 0.00 |
July | 514116.94 | 0.00 | 0.00 | 0.166000E+11 | 0.00 | 0.00 |
August | 321295.22 | 0.00 | 0.00 | 0.160891E+11 | 0.00 | 0.00 |
September | 0.235457E+09 | 0.00 | 0.00 | 0.109355E+11 | 0.00 | 0.00 |
October | 0.482232E+10 | 0.00 | 0.00 | 0.369536E+10 | 0.00 | 0.00 |
November | 0.772554E+10 | 0.00 | 0.00 | 0.218463E+10 | 0.00 | 0.00 |
December | 0.156596E+11 | 0.00 | 0.00 | 0.166449E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.607935E+11 | 0.00 | 0.00 | 0.821568E+11 | 0.00 | 0.00 |
Minimum of Months | 283701.86 | 0.00 | 0.00 | 0.160035E+10 | 0.00 | 0.00 |
Maximum of Months | 0.156596E+11 | 0.00 | 0.00 | 0.168922E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.153127E+11 | 0.00 | 0.00 | 0.185565E+10 | 0.00 | 0.00 |
February | 0.163738E+11 | 0.00 | 0.00 | 0.193199E+10 | 0.00 | 0.00 |
March | 0.982158E+10 | 0.00 | 0.00 | 0.275697E+10 | 0.00 | 0.00 |
April | 0.602622E+10 | 0.00 | 0.00 | 0.233038E+10 | 0.00 | 0.00 |
May | 0.544446E+09 | 0.00 | 0.00 | 0.580109E+10 | 0.00 | 0.00 |
June | 1190430.63 | 0.00 | 0.00 | 0.177964E+11 | 0.00 | 0.00 |
July | 458284.72 | 0.00 | 0.00 | 0.172973E+11 | 0.00 | 0.00 |
August | 287986.10 | 0.00 | 0.00 | 0.167436E+11 | 0.00 | 0.00 |
September | 0.329171E+09 | 0.00 | 0.00 | 0.107303E+11 | 0.00 | 0.00 |
October | 0.768022E+10 | 0.00 | 0.00 | 0.342240E+10 | 0.00 | 0.00 |
November | 0.116261E+11 | 0.00 | 0.00 | 0.218553E+10 | 0.00 | 0.00 |
December | 0.240491E+11 | 0.00 | 0.00 | 0.197832E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.917652E+11 | 0.00 | 0.00 | 0.848300E+11 | 0.00 | 0.00 |
Minimum of Months | 287986.10 | 0.00 | 0.00 | 0.185565E+10 | 0.00 | 0.00 |
Maximum of Months | 0.240491E+11 | 0.00 | 0.00 | 0.177964E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142795E+10 | 0.132034E+10 | 0.124815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132496E+10 | 0.690257E+09 | 0.136054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186639E+10 | 0.305143E+10 | 0.884015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152228E+10 | 0.341357E+10 | 0.510058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.268287E+10 | 0.122562E+11 | 0.779394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.597268E+10 | 0.475904E+11 | 11279277.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.570729E+10 | 0.484526E+11 | 3476586.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.599149E+10 | 0.481181E+11 | 1384150.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.481902E+10 | 0.338258E+11 | 0.240559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.254476E+10 | 0.932015E+10 | 0.507834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170785E+10 | 0.312670E+10 | 0.831988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138060E+10 | 0.910872E+09 | 0.162634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369481E+11 | 0.212076E+12 | 0.707254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132496E+10 | 0.690257E+09 | 1384150.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.599149E+10 | 0.484526E+11 | 0.162634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141334E+10 | 0.180998E+10 | 0.102135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134872E+10 | 0.104475E+10 | 0.111839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191655E+10 | 0.344404E+10 | 0.662384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161443E+10 | 0.269549E+10 | 0.398047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.291543E+10 | 0.130174E+11 | 0.347791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.598164E+10 | 0.470722E+11 | 283701.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.568168E+10 | 0.477707E+11 | 514116.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572714E+10 | 0.454463E+11 | 321295.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.421461E+10 | 0.304135E+11 | 0.235457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211258E+10 | 0.725180E+10 | 0.482232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152301E+10 | 0.291870E+10 | 0.772554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137656E+10 | 0.122136E+10 | 0.156596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.358257E+11 | 0.204106E+12 | 0.607935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134872E+10 | 0.104475E+10 | 283701.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.598164E+10 | 0.477707E+11 | 0.156596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151476E+10 | 0.147504E+10 | 0.153127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152679E+10 | 0.170501E+10 | 0.163738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195615E+10 | 0.360248E+10 | 0.982158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168990E+10 | 0.276617E+10 | 0.602622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.272346E+10 | 0.139620E+11 | 0.544446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.573299E+10 | 0.516232E+11 | 1190430.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.535120E+10 | 0.517784E+11 | 458284.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.538294E+10 | 0.493515E+11 | 287986.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.372567E+10 | 0.313422E+11 | 0.329171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197479E+10 | 0.651527E+10 | 0.768022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154736E+10 | 0.276326E+10 | 0.116261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169315E+10 | 0.119100E+10 | 0.240491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348192E+11 | 0.218076E+12 | 0.917652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151476E+10 | 0.119100E+10 | 287986.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.573299E+10 | 0.517784E+11 | 0.240491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142795E+10 | 0.124815E+11 | 0.00 | 0.00 | 0.300002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132496E+10 | 0.136054E+11 | 0.00 | 0.00 | 0.165598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186639E+10 | 0.884015E+10 | 0.00 | 0.00 | 0.676426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152228E+10 | 0.510058E+10 | 0.00 | 0.00 | 0.793260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.268287E+10 | 0.779394E+09 | 0.00 | 0.00 | 0.269422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.597268E+10 | 11279277.84 | 0.00 | 0.00 | 0.110345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.570729E+10 | 3476586.82 | 0.00 | 0.00 | 0.110593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.599149E+10 | 1384150.84 | 0.00 | 0.00 | 0.109318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.481902E+10 | 0.240559E+09 | 0.00 | 0.00 | 0.743161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.254476E+10 | 0.507834E+10 | 0.00 | 0.00 | 0.201882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170785E+10 | 0.831988E+10 | 0.00 | 0.00 | 0.700798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138060E+10 | 0.162634E+11 | 0.00 | 0.00 | 0.215174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369481E+11 | 0.707254E+11 | 0.00 | 0.00 | 0.480215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132496E+10 | 1384150.84 | 0.00 | 0.00 | 0.165598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.599149E+10 | 0.162634E+11 | 0.00 | 0.00 | 0.110593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141334E+10 | 0.102135E+11 | 0.00 | 0.00 | 0.413278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134872E+10 | 0.111839E+11 | 0.00 | 0.00 | 0.251632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191655E+10 | 0.662384E+10 | 0.00 | 0.00 | 0.755736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161443E+10 | 0.398047E+10 | 0.00 | 0.00 | 0.620946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.291543E+10 | 0.347791E+09 | 0.00 | 0.00 | 0.284558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.598164E+10 | 283701.86 | 0.00 | 0.00 | 0.109105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.568168E+10 | 514116.94 | 0.00 | 0.00 | 0.109183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572714E+10 | 321295.22 | 0.00 | 0.00 | 0.103619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.421461E+10 | 0.235457E+09 | 0.00 | 0.00 | 0.672088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211258E+10 | 0.482232E+10 | 0.00 | 0.00 | 0.158278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152301E+10 | 0.772554E+10 | 0.00 | 0.00 | 0.661625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137656E+10 | 0.156596E+11 | 0.00 | 0.00 | 0.287937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.358257E+11 | 0.607935E+11 | 0.00 | 0.00 | 0.463312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134872E+10 | 283701.86 | 0.00 | 0.00 | 0.251632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.598164E+10 | 0.156596E+11 | 0.00 | 0.00 | 0.109183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151476E+10 | 0.153127E+11 | 0.00 | 0.00 | 0.340886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152679E+10 | 0.163738E+11 | 0.00 | 0.00 | 0.405196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195615E+10 | 0.982158E+10 | 0.00 | 0.00 | 0.800818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168990E+10 | 0.602622E+10 | 0.00 | 0.00 | 0.640484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.272346E+10 | 0.544446E+09 | 0.00 | 0.00 | 0.307763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.573299E+10 | 1190430.63 | 0.00 | 0.00 | 0.120634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.535120E+10 | 458284.72 | 0.00 | 0.00 | 0.119461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.538294E+10 | 287986.10 | 0.00 | 0.00 | 0.113607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.372567E+10 | 0.329171E+09 | 0.00 | 0.00 | 0.700466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197479E+10 | 0.768022E+10 | 0.00 | 0.00 | 0.144762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154736E+10 | 0.116261E+11 | 0.00 | 0.00 | 0.638169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169315E+10 | 0.240491E+11 | 0.00 | 0.00 | 0.285165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348192E+11 | 0.917652E+11 | 0.00 | 0.00 | 0.500108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151476E+10 | 287986.10 | 0.00 | 0.00 | 0.285165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.573299E+10 | 0.240491E+11 | 0.00 | 0.00 | 0.120634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.591771E+10 | 0.00 | 0.00 | 15025700.49 | 0.00 | 0.00 | 0.916246E+10 | 0.00 | 0.37 |
February | 0.597765E+10 | 0.00 | 0.00 | 13690565.00 | 0.00 | 0.00 | 0.810138E+10 | 0.00 | 0.36 |
March | 0.349201E+10 | 0.00 | 0.00 | 21904545.80 | 0.00 | 0.00 | 0.127992E+11 | 0.00 | 0.54 |
April | 0.187661E+10 | 0.00 | 0.00 | 20440965.39 | 0.00 | 0.00 | 0.111550E+11 | 0.00 | 0.47 |
May | 0.523923E+09 | 2171116.29 | 0.00 | 33439551.54 | 986144.22 | 0.00 | 0.141332E+11 | 0.00 | 0.81 |
June | 0.265007E+09 | 0.440485E+09 | 0.00 | 25597177.64 | 64259084.20 | 0.00 | 0.473182E+10 | 0.00 | 0.70 |
July | 0.257450E+09 | 0.560491E+09 | 0.00 | 22618427.78 | 0.111145E+09 | 0.00 | 0.339178E+10 | 0.00 | 0.66 |
August | 0.343128E+09 | 0.425642E+09 | 0.00 | 32531857.01 | 36892749.56 | 0.00 | 0.627983E+10 | 0.00 | 0.74 |
September | 0.454575E+09 | 63344839.25 | 0.00 | 36163775.05 | 20115793.66 | 0.00 | 0.933524E+10 | 0.00 | 0.82 |
October | 0.176180E+10 | 0.00 | 0.00 | 31735636.57 | 0.00 | 0.00 | 0.146300E+11 | 0.00 | 0.58 |
November | 0.278536E+10 | 0.00 | 0.00 | 23129426.51 | 0.00 | 0.00 | 0.130922E+11 | 0.00 | 0.45 |
December | 0.715587E+10 | 0.00 | 0.00 | 11800663.78 | 0.00 | 2036995.08 | 0.804744E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.308111E+11 | 0.149213E+10 | 0.00 | 0.288078E+09 | 0.233399E+09 | 2036995.08 | 0.114859E+12 | 0.00 | 0.57 |
Minimum of Months | 0.257450E+09 | 0.00 | 0.00 | 11800663.78 | 0.00 | 0.00 | 0.339178E+10 | 0.00 | 0.35 |
Maximum of Months | 0.715587E+10 | 0.560491E+09 | 0.00 | 36163775.05 | 0.111145E+09 | 2036995.08 | 0.146300E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104594E+11 | 0.00 | 0.00 | 3455806.15 | 0.00 | 34789705.41 | 0.200513E+10 | 0.00 | 0.30 |
February | 0.922193E+10 | 0.00 | 0.00 | 3116540.57 | 0.00 | 0.361120E+09 | 0.213233E+10 | 0.00 | 0.30 |
March | 0.740445E+10 | 0.00 | 0.00 | 9645109.60 | 0.00 | 34072732.58 | 0.571279E+10 | 0.00 | 0.43 |
April | 0.594537E+10 | 0.00 | 0.00 | 8557120.73 | 0.00 | 13856363.95 | 0.516873E+10 | 0.00 | 0.41 |
May | 0.154508E+10 | 1369400.86 | 0.00 | 22287609.14 | 1328442.40 | 0.00 | 0.964820E+10 | 0.00 | 0.63 |
June | 0.466441E+09 | 0.329052E+09 | 0.00 | 20765626.41 | 57623106.22 | 0.00 | 0.357000E+10 | 0.00 | 0.57 |
July | 0.399456E+09 | 0.427352E+09 | 0.00 | 18448787.36 | 0.118635E+09 | 0.00 | 0.260953E+10 | 0.00 | 0.54 |
August | 0.565778E+09 | 0.322940E+09 | 0.00 | 25856112.08 | 28299888.40 | 0.00 | 0.467389E+10 | 0.00 | 0.60 |
September | 0.810224E+09 | 49194582.50 | 0.00 | 25536012.03 | 21072890.13 | 0.00 | 0.654447E+10 | 0.00 | 0.63 |
October | 0.486989E+10 | 0.00 | 0.00 | 14720677.84 | 0.00 | 2682586.43 | 0.765784E+10 | 0.00 | 0.44 |
November | 0.812116E+10 | 0.00 | 0.00 | 6443805.37 | 0.00 | 6822455.36 | 0.410072E+10 | 0.00 | 0.34 |
December | 0.110359E+11 | 0.00 | 0.00 | 1732962.00 | 0.00 | 0.383492E+09 | 0.164880E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.608451E+11 | 0.112991E+10 | 0.00 | 0.160566E+09 | 0.226959E+09 | 0.836836E+09 | 0.554724E+11 | 0.00 | 0.46 |
Minimum of Months | 0.399456E+09 | 0.00 | 0.00 | 1732962.00 | 0.00 | 0.00 | 0.164880E+10 | 0.00 | 0.30 |
Maximum of Months | 0.110359E+11 | 0.427352E+09 | 0.00 | 25856112.08 | 0.118635E+09 | 0.383492E+09 | 0.964820E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.942669E+10 | 0.00 | 0.00 | 1358345.71 | 0.00 | 0.107526E+10 | 0.108622E+10 | 0.00 | 0.29 |
February | 0.811078E+10 | 0.00 | 0.00 | 1531680.36 | 0.00 | 0.149405E+10 | 0.108967E+10 | 0.00 | 0.27 |
March | 0.759643E+10 | 0.00 | 0.00 | 6845222.68 | 0.00 | 0.480499E+09 | 0.435124E+10 | 0.00 | 0.41 |
April | 0.592269E+10 | 0.00 | 0.00 | 7138157.93 | 0.00 | 0.328178E+09 | 0.459341E+10 | 0.00 | 0.40 |
May | 0.226923E+10 | 194059.35 | 0.00 | 19645581.60 | 372493.68 | 2294658.18 | 0.866755E+10 | 0.00 | 0.63 |
June | 0.633248E+09 | 0.258989E+09 | 0.00 | 22357767.68 | 51921361.61 | 0.00 | 0.328947E+10 | 0.00 | 0.61 |
July | 0.460052E+09 | 0.337592E+09 | 0.00 | 19614417.05 | 0.117014E+09 | 0.00 | 0.232296E+10 | 0.00 | 0.56 |
August | 0.643832E+09 | 0.265487E+09 | 0.00 | 25676994.53 | 26825504.36 | 0.00 | 0.414533E+10 | 0.00 | 0.59 |
September | 0.131241E+10 | 35905048.98 | 0.00 | 22082332.86 | 13765669.60 | 0.00 | 0.515189E+10 | 0.00 | 0.60 |
October | 0.577090E+10 | 0.00 | 0.00 | 8597357.56 | 0.00 | 0.592511E+09 | 0.477058E+10 | 0.00 | 0.42 |
November | 0.848106E+10 | 0.00 | 0.00 | 3191438.44 | 0.00 | 0.541613E+09 | 0.206364E+10 | 0.00 | 0.32 |
December | 0.898964E+10 | 0.00 | 0.00 | 490410.39 | 0.00 | 0.225004E+10 | 0.598269E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.596170E+11 | 0.898167E+09 | 0.00 | 0.138530E+09 | 0.209899E+09 | 0.676445E+10 | 0.421302E+11 | 0.00 | 0.45 |
Minimum of Months | 0.460052E+09 | 0.00 | 0.00 | 490410.39 | 0.00 | 0.00 | 0.598269E+09 | 0.00 | 0.27 |
Maximum of Months | 0.942669E+10 | 0.337592E+09 | 0.00 | 25676994.53 | 0.117014E+09 | 0.225004E+10 | 0.866755E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103976E+10 | 0.00 | 0.00 | 19468.18 | 0.00 | 0.161964E+10 | 28916672.03 | 0.00 | 0.30 |
February | 0.101322E+10 | 0.00 | 0.00 | 22285.82 | 0.00 | 0.141949E+10 | 11417822.24 | 0.00 | 0.29 |
March | 0.127992E+10 | 0.00 | 0.00 | 862429.57 | 0.00 | 0.829161E+09 | 0.482276E+09 | 0.00 | 0.40 |
April | 0.125375E+10 | 0.00 | 0.00 | 1275092.02 | 0.00 | 0.384547E+09 | 0.715653E+09 | 0.00 | 0.43 |
May | 0.641517E+09 | 71869.20 | 0.00 | 5001238.48 | 78556.13 | 20174663.95 | 0.191470E+10 | 0.00 | 0.76 |
June | 0.122242E+09 | 99759116.42 | 0.00 | 7135527.06 | 9355926.96 | 0.00 | 0.924710E+09 | 0.00 | 0.86 |
July | 0.103017E+09 | 0.129280E+09 | 0.00 | 5995144.42 | 20471809.21 | 0.00 | 0.610852E+09 | 0.00 | 0.77 |
August | 0.175379E+09 | 91833374.00 | 0.00 | 6975792.93 | 5167485.18 | 0.00 | 0.964754E+09 | 0.00 | 0.73 |
September | 0.398341E+09 | 13930800.14 | 0.00 | 5218907.10 | 2890939.74 | 9949108.63 | 0.987861E+09 | 0.00 | 0.66 |
October | 0.118977E+10 | 0.00 | 0.00 | 1052119.80 | 0.00 | 0.650883E+09 | 0.483657E+09 | 0.00 | 0.41 |
November | 0.111924E+10 | 0.00 | 0.00 | 265091.47 | 0.00 | 0.115901E+10 | 0.147442E+09 | 0.00 | 0.32 |
December | 0.825275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244009E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.916142E+10 | 0.334875E+09 | 0.00 | 33823096.87 | 37964717.22 | 0.853295E+10 | 0.727223E+10 | 0.00 | 0.52 |
Minimum of Months | 0.103017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.127992E+10 | 0.129280E+09 | 0.00 | 7135527.06 | 20471809.21 | 0.244009E+10 | 0.191470E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.754753E+09 | 0.00 | 0.00 | 504692.37 | 0.00 | 0.800837E+09 | 0.264123E+09 | 0.00 | 0.33 |
February | 0.669187E+09 | 0.00 | 0.00 | 985144.23 | 0.00 | 0.629064E+09 | 0.508061E+09 | 0.00 | 0.36 |
March | 0.603770E+09 | 0.00 | 0.00 | 3166674.96 | 0.00 | 0.387374E+09 | 0.166614E+10 | 0.00 | 0.71 |
April | 0.594425E+09 | 0.00 | 0.00 | 3385926.54 | 0.00 | 0.174975E+09 | 0.180708E+10 | 0.00 | 0.78 |
May | 0.245183E+09 | 61456.02 | 0.00 | 6695479.30 | 49841.07 | 5897493.86 | 0.266236E+10 | 0.00 | 1.33 |
June | 35560664.72 | 81508457.55 | 0.00 | 9370267.09 | 3967228.20 | 0.00 | 0.147024E+10 | 0.00 | 1.62 |
July | 35128882.92 | 0.123068E+09 | 0.00 | 7968194.70 | 5646188.73 | 0.00 | 0.791042E+09 | 0.00 | 1.30 |
August | 64894340.13 | 78513300.72 | 0.00 | 9945923.32 | 3097475.64 | 0.00 | 0.171467E+10 | 0.00 | 1.52 |
September | 0.152838E+09 | 12676177.01 | 0.00 | 7597734.17 | 1705176.03 | 5514346.10 | 0.161279E+10 | 0.00 | 1.30 |
October | 0.544406E+09 | 0.00 | 0.00 | 2826367.90 | 0.00 | 0.403069E+09 | 0.127743E+10 | 0.00 | 0.67 |
November | 0.728179E+09 | 0.00 | 0.00 | 985899.95 | 0.00 | 0.577466E+09 | 0.454078E+09 | 0.00 | 0.40 |
December | 0.633448E+09 | 0.00 | 0.00 | 126758.94 | 0.00 | 0.144522E+10 | 96196823.97 | 0.00 | 0.34 |
Annual Sum or Average | 0.506177E+10 | 0.295827E+09 | 0.00 | 53559063.46 | 14465909.67 | 0.442942E+10 | 0.143242E+11 | 0.00 | 0.89 |
Minimum of Months | 35128882.92 | 0.00 | 0.00 | 126758.94 | 0.00 | 0.00 | 96196823.97 | 0.00 | 0.33 |
Maximum of Months | 0.754753E+09 | 0.123068E+09 | 0.00 | 9945923.32 | 5646188.73 | 0.144522E+10 | 0.266236E+10 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.888235E+09 | 0.00 | 0.00 | 8525655.53 | 0.00 | 0.743333E+09 | 0.407511E+10 | 0.00 | 0.78 |
February | 0.765130E+09 | 0.00 | 0.00 | 8716138.69 | 0.00 | 0.743114E+09 | 0.391643E+10 | 0.00 | 0.72 |
March | 0.841814E+09 | 0.00 | 0.00 | 8866824.39 | 0.00 | 0.592917E+09 | 0.434177E+10 | 0.00 | 1.04 |
April | 0.100591E+10 | 0.00 | 0.00 | 5004774.67 | 0.00 | 0.283545E+09 | 0.273163E+10 | 0.00 | 0.80 |
May | 0.538361E+09 | 87110.12 | 0.00 | 7533408.57 | 78445.44 | 21447127.90 | 0.293028E+10 | 0.00 | 1.03 |
June | 0.156885E+09 | 0.112662E+09 | 0.00 | 8202885.95 | 8425836.29 | 0.00 | 0.974834E+09 | 0.00 | 0.95 |
July | 0.109560E+09 | 0.182224E+09 | 0.00 | 7119734.63 | 11444171.95 | 0.00 | 0.671258E+09 | 0.00 | 0.87 |
August | 0.152336E+09 | 0.133762E+09 | 0.00 | 11551489.11 | 4971189.57 | 0.00 | 0.149000E+10 | 0.00 | 1.04 |
September | 0.277878E+09 | 26979271.47 | 0.00 | 13159888.28 | 2661073.94 | 8433366.94 | 0.235449E+10 | 0.00 | 1.30 |
October | 0.669745E+09 | 0.00 | 0.00 | 11694856.99 | 0.00 | 0.571619E+09 | 0.466693E+10 | 0.00 | 1.25 |
November | 0.847847E+09 | 0.00 | 0.00 | 9713788.59 | 0.00 | 0.584993E+09 | 0.406068E+10 | 0.00 | 0.88 |
December | 0.908047E+09 | 0.00 | 0.00 | 6504389.17 | 0.00 | 0.123958E+10 | 0.283856E+10 | 0.00 | 0.70 |
Annual Sum or Average | 0.716175E+10 | 0.455714E+09 | 0.00 | 0.106594E+09 | 27580717.18 | 0.478898E+10 | 0.350520E+11 | 0.00 | 0.95 |
Minimum of Months | 0.109560E+09 | 0.00 | 0.00 | 5004774.67 | 0.00 | 0.00 | 0.671258E+09 | 0.00 | 0.70 |
Maximum of Months | 0.100591E+10 | 0.182224E+09 | 0.00 | 13159888.28 | 11444171.95 | 0.123958E+10 | 0.466693E+10 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.659108E+09 | 0.00 | 0.00 | 878330.06 | 0.00 | 0.837337E+09 | 0.526523E+09 | 0.00 | 0.39 |
February | 0.597235E+09 | 0.00 | 0.00 | 1249393.82 | 0.00 | 0.747448E+09 | 0.658905E+09 | 0.00 | 0.39 |
March | 0.687746E+09 | 0.00 | 0.00 | 3079244.37 | 0.00 | 0.452477E+09 | 0.146981E+10 | 0.00 | 0.76 |
April | 0.658285E+09 | 0.00 | 0.00 | 2832449.11 | 0.00 | 0.223940E+09 | 0.151273E+10 | 0.00 | 0.76 |
May | 0.312804E+09 | 87070.44 | 0.00 | 5876164.21 | 49436.92 | 14404581.28 | 0.216063E+10 | 0.00 | 1.21 |
June | 86829554.66 | 0.119240E+09 | 0.00 | 7084433.15 | 2780076.01 | 0.00 | 0.704806E+09 | 0.00 | 1.16 |
July | 65720231.70 | 0.133599E+09 | 0.00 | 5095107.43 | 8245302.64 | 0.00 | 0.488064E+09 | 0.00 | 1.01 |
August | 96199147.46 | 0.102396E+09 | 0.00 | 7542849.82 | 2225105.20 | 0.00 | 0.818994E+09 | 0.00 | 1.03 |
September | 0.205866E+09 | 17172083.23 | 0.00 | 6337533.28 | 882752.13 | 6623029.96 | 0.111111E+10 | 0.00 | 1.05 |
October | 0.577211E+09 | 0.00 | 0.00 | 3299272.26 | 0.00 | 0.415619E+09 | 0.140157E+10 | 0.00 | 0.79 |
November | 0.667924E+09 | 0.00 | 0.00 | 1295051.72 | 0.00 | 0.609516E+09 | 0.637028E+09 | 0.00 | 0.45 |
December | 0.559566E+09 | 0.00 | 0.00 | 444450.28 | 0.00 | 0.171820E+10 | 0.266706E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.517449E+10 | 0.372495E+09 | 0.00 | 45014279.50 | 14182672.89 | 0.502556E+10 | 0.117569E+11 | 0.00 | 0.79 |
Minimum of Months | 65720231.70 | 0.00 | 0.00 | 444450.28 | 0.00 | 0.00 | 0.266706E+09 | 0.00 | 0.39 |
Maximum of Months | 0.687746E+09 | 0.133599E+09 | 0.00 | 7542849.82 | 8245302.64 | 0.171820E+10 | 0.216063E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158574E+10 | 0.00 | 0.00 | 0.30 |
February | 0.999418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158242E+10 | 0.00 | 0.00 | 0.30 |
March | 0.142520E+10 | 0.00 | 0.00 | 155275.31 | 0.00 | 0.951617E+09 | 90801141.24 | 0.00 | 0.35 |
April | 0.151348E+10 | 0.00 | 0.00 | 191890.88 | 0.00 | 0.320091E+09 | 0.127252E+09 | 0.00 | 0.32 |
May | 0.832900E+09 | 327059.58 | 0.00 | 2619145.18 | 217245.66 | 8501179.03 | 0.953760E+09 | 0.00 | 0.49 |
June | 0.137941E+09 | 0.111407E+09 | 0.00 | 4330115.91 | 13547470.80 | 0.00 | 0.651751E+09 | 0.00 | 0.61 |
July | 0.114793E+09 | 0.137136E+09 | 0.00 | 3787525.80 | 23432328.52 | 0.00 | 0.467055E+09 | 0.00 | 0.58 |
August | 0.161411E+09 | 0.100649E+09 | 0.00 | 5280638.56 | 7797082.27 | 0.00 | 0.841000E+09 | 0.00 | 0.61 |
September | 0.344192E+09 | 15688897.27 | 0.00 | 5019449.88 | 4240927.66 | 0.00 | 0.104245E+10 | 0.00 | 0.62 |
October | 0.132760E+10 | 0.00 | 0.00 | 1087581.81 | 0.00 | 0.320512E+09 | 0.465838E+09 | 0.00 | 0.35 |
November | 0.166414E+10 | 0.00 | 0.00 | 175406.77 | 0.00 | 0.615168E+09 | 99150579.83 | 0.00 | 0.30 |
December | 0.113374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198885E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.108377E+11 | 0.365209E+09 | 0.00 | 22647030.10 | 49235054.91 | 0.737290E+10 | 0.473905E+10 | 0.00 | 0.43 |
Minimum of Months | 0.114793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.166414E+10 | 0.137136E+09 | 0.00 | 5280638.56 | 23432328.52 | 0.198885E+10 | 0.104245E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.943501E+09 | 0.00 | 0.00 | 355852.24 | 0.00 | 0.659353E+09 | 0.189687E+09 | 0.00 | 0.31 |
February | 0.751889E+09 | 0.00 | 0.00 | 774056.69 | 0.00 | 0.656598E+09 | 0.407803E+09 | 0.00 | 0.34 |
March | 0.748479E+09 | 0.00 | 0.00 | 2240711.13 | 0.00 | 0.327180E+09 | 0.116875E+10 | 0.00 | 0.57 |
April | 0.698336E+09 | 0.00 | 0.00 | 2377608.25 | 0.00 | 0.119144E+09 | 0.106314E+10 | 0.00 | 0.54 |
May | 0.267275E+09 | 377302.59 | 0.00 | 4930299.28 | 131271.38 | 247041.20 | 0.190396E+10 | 0.00 | 0.98 |
June | 32219807.70 | 0.104132E+09 | 0.00 | 6748616.97 | 6689739.95 | 0.00 | 0.120096E+10 | 0.00 | 1.30 |
July | 29048310.26 | 0.138179E+09 | 0.00 | 5781305.02 | 10039005.03 | 0.00 | 0.715123E+09 | 0.00 | 1.07 |
August | 63855555.34 | 0.105777E+09 | 0.00 | 8366160.47 | 4269527.27 | 0.00 | 0.155712E+10 | 0.00 | 1.36 |
September | 0.127875E+09 | 16325328.33 | 0.00 | 7701351.57 | 2518685.10 | 0.00 | 0.175886E+10 | 0.00 | 1.30 |
October | 0.590670E+09 | 0.00 | 0.00 | 3440384.62 | 0.00 | 0.180073E+09 | 0.131866E+10 | 0.00 | 0.61 |
November | 0.996052E+09 | 0.00 | 0.00 | 1288892.56 | 0.00 | 0.221813E+09 | 0.545927E+09 | 0.00 | 0.39 |
December | 0.885909E+09 | 0.00 | 0.00 | 169685.11 | 0.00 | 0.105965E+10 | 0.129499E+09 | 0.00 | 0.32 |
Annual Sum or Average | 0.613511E+10 | 0.364791E+09 | 0.00 | 44174923.90 | 23648228.73 | 0.322406E+10 | 0.119595E+11 | 0.00 | 0.76 |
Minimum of Months | 29048310.26 | 0.00 | 0.00 | 169685.11 | 0.00 | 0.00 | 0.129499E+09 | 0.00 | 0.31 |
Maximum of Months | 0.996052E+09 | 0.138179E+09 | 0.00 | 8366160.47 | 10039005.03 | 0.105965E+10 | 0.190396E+10 | 0.00 | 1.36 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106646E+10 | 0.00 | 0.00 | 4201492.05 | 0.00 | 0.179132E+10 | 0.221927E+10 | 0.00 | 0.64 |
February | 0.944551E+09 | 0.00 | 0.00 | 3519380.41 | 0.00 | 0.195311E+10 | 0.184363E+10 | 0.00 | 0.61 |
March | 0.102330E+10 | 0.00 | 0.00 | 3856865.85 | 0.00 | 0.148066E+10 | 0.186698E+10 | 0.00 | 0.76 |
April | 0.114870E+10 | 0.00 | 0.00 | 1408358.16 | 0.00 | 0.101248E+10 | 0.665247E+09 | 0.00 | 0.49 |
May | 0.856959E+09 | 574131.88 | 0.00 | 2974666.62 | 208419.19 | 0.280853E+09 | 0.893237E+09 | 0.00 | 0.59 |
June | 0.228395E+09 | 0.154054E+09 | 0.00 | 4709339.75 | 13334583.91 | 7932172.47 | 0.511578E+09 | 0.00 | 0.67 |
July | 0.170882E+09 | 0.197886E+09 | 0.00 | 4128053.73 | 20564632.70 | 2544827.95 | 0.392662E+09 | 0.00 | 0.65 |
August | 0.242136E+09 | 0.185709E+09 | 0.00 | 8899492.97 | 4065652.49 | 552586.95 | 0.105102E+10 | 0.00 | 0.88 |
September | 0.321161E+09 | 34525847.53 | 0.00 | 11561906.42 | 3511553.87 | 58333648.38 | 0.199873E+10 | 0.00 | 1.21 |
October | 0.582949E+09 | 0.00 | 0.00 | 10014760.22 | 0.00 | 0.112151E+10 | 0.329320E+10 | 0.00 | 0.99 |
November | 0.929592E+09 | 0.00 | 0.00 | 6934555.83 | 0.00 | 0.134459E+10 | 0.281404E+10 | 0.00 | 0.79 |
December | 0.105920E+10 | 0.00 | 0.00 | 4134939.02 | 0.00 | 0.270026E+10 | 0.179066E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.857428E+10 | 0.572749E+09 | 0.00 | 66343811.02 | 41684842.15 | 0.117541E+11 | 0.193403E+11 | 0.00 | 0.75 |
Minimum of Months | 0.170882E+09 | 0.00 | 0.00 | 1408358.16 | 0.00 | 552586.95 | 0.392662E+09 | 0.00 | 0.49 |
Maximum of Months | 0.114870E+10 | 0.197886E+09 | 0.00 | 11561906.42 | 20564632.70 | 0.270026E+10 | 0.329320E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.971491E+09 | 0.00 | 0.00 | 481622.26 | 0.00 | 0.607166E+09 | 0.298948E+09 | 0.00 | 0.34 |
February | 0.780375E+09 | 0.00 | 0.00 | 635473.41 | 0.00 | 0.692967E+09 | 0.413998E+09 | 0.00 | 0.36 |
March | 0.831314E+09 | 0.00 | 0.00 | 1751054.77 | 0.00 | 0.415012E+09 | 0.845123E+09 | 0.00 | 0.58 |
April | 0.805438E+09 | 0.00 | 0.00 | 1555265.09 | 0.00 | 0.146838E+09 | 0.691009E+09 | 0.00 | 0.49 |
May | 0.342819E+09 | 549654.38 | 0.00 | 3820143.22 | 132151.50 | 5095294.00 | 0.136376E+10 | 0.00 | 0.82 |
June | 72134686.47 | 0.143003E+09 | 0.00 | 4469153.61 | 3854796.18 | 0.00 | 0.597454E+09 | 0.00 | 0.92 |
July | 63624407.28 | 0.147650E+09 | 0.00 | 3344035.02 | 10263649.97 | 0.00 | 0.440057E+09 | 0.00 | 0.81 |
August | 76382321.34 | 0.124804E+09 | 0.00 | 5887775.71 | 3491819.19 | 0.00 | 0.806729E+09 | 0.00 | 0.94 |
September | 0.154500E+09 | 19203049.10 | 0.00 | 6019000.97 | 1325992.24 | 0.00 | 0.122770E+10 | 0.00 | 1.05 |
October | 0.573995E+09 | 0.00 | 0.00 | 3453550.08 | 0.00 | 0.185478E+09 | 0.132435E+10 | 0.00 | 0.66 |
November | 0.100320E+10 | 0.00 | 0.00 | 1193480.30 | 0.00 | 0.231998E+09 | 0.586587E+09 | 0.00 | 0.42 |
December | 0.922067E+09 | 0.00 | 0.00 | 331839.61 | 0.00 | 0.106262E+10 | 0.204401E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.659734E+10 | 0.435209E+09 | 0.00 | 32942394.06 | 19068409.08 | 0.334717E+10 | 0.880012E+10 | 0.00 | 0.65 |
Minimum of Months | 63624407.28 | 0.00 | 0.00 | 331839.61 | 0.00 | 0.00 | 0.204401E+09 | 0.00 | 0.34 |
Maximum of Months | 0.100320E+10 | 0.147650E+09 | 0.00 | 6019000.97 | 10263649.97 | 0.106262E+10 | 0.136376E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147810E+10 | 0.00 | 0.00 | 37631.91 | 0.00 | 0.113131E+10 | 38056679.90 | 0.00 | 0.29 |
February | 0.132918E+10 | 0.00 | 0.00 | 34258.46 | 0.00 | 0.111479E+10 | 42584804.67 | 0.00 | 0.29 |
March | 0.162685E+10 | 0.00 | 0.00 | 965078.86 | 0.00 | 0.481666E+09 | 0.520921E+09 | 0.00 | 0.40 |
April | 0.140846E+10 | 0.00 | 0.00 | 1309086.51 | 0.00 | 0.200222E+09 | 0.690738E+09 | 0.00 | 0.42 |
May | 0.578369E+09 | 622432.94 | 0.00 | 5284056.21 | 280159.79 | 729261.22 | 0.197323E+10 | 0.00 | 0.75 |
June | 97995073.84 | 0.130385E+09 | 0.00 | 6302968.80 | 11581366.60 | 0.00 | 0.949416E+09 | 0.00 | 0.80 |
July | 93469484.48 | 0.169180E+09 | 0.00 | 5302472.77 | 24365580.57 | 0.00 | 0.654062E+09 | 0.00 | 0.74 |
August | 0.150834E+09 | 0.118984E+09 | 0.00 | 6788497.66 | 5968916.40 | 0.00 | 0.104052E+10 | 0.00 | 0.73 |
September | 0.346583E+09 | 20243922.01 | 0.00 | 5434370.94 | 4381688.12 | 0.00 | 0.112772E+10 | 0.00 | 0.67 |
October | 0.127325E+10 | 0.00 | 0.00 | 1427584.01 | 0.00 | 0.435022E+09 | 0.646830E+09 | 0.00 | 0.40 |
November | 0.158477E+10 | 0.00 | 0.00 | 391362.15 | 0.00 | 0.688202E+09 | 0.199101E+09 | 0.00 | 0.32 |
December | 0.121011E+10 | 0.00 | 0.00 | 9737.61 | 0.00 | 0.188387E+10 | 12940047.99 | 0.00 | 0.31 |
Annual Sum or Average | 0.111780E+11 | 0.439415E+09 | 0.00 | 33287105.89 | 46577711.48 | 0.593581E+10 | 0.789612E+10 | 0.00 | 0.51 |
Minimum of Months | 93469484.48 | 0.00 | 0.00 | 9737.61 | 0.00 | 0.00 | 12940047.99 | 0.00 | 0.29 |
Maximum of Months | 0.162685E+10 | 0.169180E+09 | 0.00 | 6788497.66 | 24365580.57 | 0.188387E+10 | 0.197323E+10 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.782344E+09 | 0.00 | 0.00 | 760177.34 | 0.00 | 0.529863E+09 | 0.352258E+09 | 0.00 | 0.29 |
February | 0.593260E+09 | 0.00 | 0.00 | 1506764.80 | 0.00 | 0.510749E+09 | 0.747649E+09 | 0.00 | 0.36 |
March | 0.675777E+09 | 0.00 | 0.00 | 3608994.99 | 0.00 | 0.197848E+09 | 0.175158E+10 | 0.00 | 0.69 |
April | 0.541103E+09 | 0.00 | 0.00 | 3621532.79 | 0.00 | 86684146.20 | 0.174950E+10 | 0.00 | 0.72 |
May | 0.205863E+09 | 489342.77 | 0.00 | 6668851.78 | 176856.16 | 165748.94 | 0.259657E+10 | 0.00 | 1.24 |
June | 29555994.08 | 0.100618E+09 | 0.00 | 8235273.42 | 5963700.20 | 0.00 | 0.145576E+10 | 0.00 | 1.48 |
July | 29082923.67 | 0.146668E+09 | 0.00 | 7067058.34 | 8655933.81 | 0.00 | 0.833225E+09 | 0.00 | 1.22 |
August | 64085808.58 | 0.100402E+09 | 0.00 | 9197907.69 | 2780148.63 | 0.00 | 0.172003E+10 | 0.00 | 1.45 |
September | 0.144264E+09 | 17781121.65 | 0.00 | 7485897.67 | 2610195.57 | 0.00 | 0.170281E+10 | 0.00 | 1.27 |
October | 0.535505E+09 | 0.00 | 0.00 | 3386213.62 | 0.00 | 0.251599E+09 | 0.135102E+10 | 0.00 | 0.62 |
November | 0.760592E+09 | 0.00 | 0.00 | 1378947.86 | 0.00 | 0.337781E+09 | 0.580213E+09 | 0.00 | 0.37 |
December | 0.669589E+09 | 0.00 | 0.00 | 313185.85 | 0.00 | 0.117836E+10 | 0.177740E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.503102E+10 | 0.365958E+09 | 0.00 | 53230806.15 | 20186834.36 | 0.309304E+10 | 0.150184E+11 | 0.00 | 0.84 |
Minimum of Months | 29082923.67 | 0.00 | 0.00 | 313185.85 | 0.00 | 0.00 | 0.177740E+09 | 0.00 | 0.29 |
Maximum of Months | 0.782344E+09 | 0.146668E+09 | 0.00 | 9197907.69 | 8655933.81 | 0.117836E+10 | 0.259657E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120295E+10 | 0.00 | 0.00 | 10412273.60 | 0.00 | 0.408502E+09 | 0.442581E+10 | 0.00 | 0.82 |
February | 0.893916E+09 | 0.00 | 0.00 | 10032925.72 | 0.00 | 0.568779E+09 | 0.457301E+10 | 0.00 | 0.83 |
March | 0.113143E+10 | 0.00 | 0.00 | 9481302.79 | 0.00 | 0.322906E+09 | 0.433431E+10 | 0.00 | 1.06 |
April | 0.108197E+10 | 0.00 | 0.00 | 5241689.63 | 0.00 | 0.164938E+09 | 0.255904E+10 | 0.00 | 0.79 |
May | 0.511192E+09 | 892505.83 | 0.00 | 7712657.10 | 280573.72 | 1193774.60 | 0.285588E+10 | 0.00 | 1.00 |
June | 0.136575E+09 | 0.148313E+09 | 0.00 | 6915598.16 | 11536281.37 | 0.00 | 0.921538E+09 | 0.00 | 0.87 |
July | 0.109363E+09 | 0.232837E+09 | 0.00 | 5951007.22 | 15043037.28 | 0.00 | 0.664528E+09 | 0.00 | 0.81 |
August | 0.136024E+09 | 0.189658E+09 | 0.00 | 10683693.06 | 3066927.54 | 0.00 | 0.147641E+10 | 0.00 | 1.02 |
September | 0.269030E+09 | 41630388.30 | 0.00 | 12447074.61 | 3844588.57 | 0.00 | 0.232199E+10 | 0.00 | 1.28 |
October | 0.723877E+09 | 0.00 | 0.00 | 13011223.42 | 0.00 | 0.408066E+09 | 0.459348E+10 | 0.00 | 1.20 |
November | 0.109339E+10 | 0.00 | 0.00 | 11949684.82 | 0.00 | 0.291419E+09 | 0.455097E+10 | 0.00 | 0.95 |
December | 0.117690E+10 | 0.00 | 0.00 | 8132914.61 | 0.00 | 0.825247E+09 | 0.336729E+10 | 0.00 | 0.75 |
Annual Sum or Average | 0.846662E+10 | 0.613330E+09 | 0.00 | 0.111972E+09 | 33771408.48 | 0.299105E+10 | 0.366443E+11 | 0.00 | 0.95 |
Minimum of Months | 0.109363E+09 | 0.00 | 0.00 | 5241689.63 | 0.00 | 0.00 | 0.664528E+09 | 0.00 | 0.75 |
Maximum of Months | 0.120295E+10 | 0.232837E+09 | 0.00 | 13011223.42 | 15043037.28 | 0.825247E+09 | 0.459348E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.934904E+09 | 0.00 | 0.00 | 1048732.87 | 0.00 | 0.526726E+09 | 0.564341E+09 | 0.00 | 0.39 |
February | 0.790477E+09 | 0.00 | 0.00 | 1410855.10 | 0.00 | 0.548620E+09 | 0.783830E+09 | 0.00 | 0.43 |
March | 0.869992E+09 | 0.00 | 0.00 | 3172042.00 | 0.00 | 0.264275E+09 | 0.144760E+10 | 0.00 | 0.77 |
April | 0.722380E+09 | 0.00 | 0.00 | 2884652.64 | 0.00 | 0.121325E+09 | 0.140763E+10 | 0.00 | 0.74 |
May | 0.290608E+09 | 848559.77 | 0.00 | 5943458.94 | 177445.79 | 799993.35 | 0.209226E+10 | 0.00 | 1.17 |
June | 75743077.87 | 0.162528E+09 | 0.00 | 5596547.13 | 3068632.18 | 0.00 | 0.668804E+09 | 0.00 | 1.06 |
July | 62937427.22 | 0.183629E+09 | 0.00 | 4101056.37 | 8679279.32 | 0.00 | 0.485427E+09 | 0.00 | 0.94 |
August | 86223445.08 | 0.139983E+09 | 0.00 | 6794542.87 | 2293529.81 | 0.00 | 0.827980E+09 | 0.00 | 1.01 |
September | 0.192866E+09 | 25596964.68 | 0.00 | 5948639.49 | 1191196.92 | 158906.56 | 0.113341E+10 | 0.00 | 1.05 |
October | 0.625605E+09 | 0.00 | 0.00 | 3697272.79 | 0.00 | 0.272704E+09 | 0.148352E+10 | 0.00 | 0.77 |
November | 0.927643E+09 | 0.00 | 0.00 | 1548189.32 | 0.00 | 0.346857E+09 | 0.715434E+09 | 0.00 | 0.47 |
December | 0.844396E+09 | 0.00 | 0.00 | 549587.78 | 0.00 | 0.130800E+10 | 0.309050E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.642378E+10 | 0.512585E+09 | 0.00 | 42695577.29 | 15410084.03 | 0.338946E+10 | 0.119193E+11 | 0.00 | 0.77 |
Minimum of Months | 62937427.22 | 0.00 | 0.00 | 549587.78 | 0.00 | 0.00 | 0.309050E+09 | 0.00 | 0.39 |
Maximum of Months | 0.934904E+09 | 0.183629E+09 | 0.00 | 6794542.87 | 8679279.32 | 0.130800E+10 | 0.209226E+10 | 0.00 | 1.17 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:56
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.240464E+12 | 0.788734E+10 | 0.00 | 0.172016E+12 | 0.195822E+11 |
February | 0.297546E+12 | 0.970243E+10 | 0.00 | 0.158606E+12 | 0.189433E+11 |
March | 0.362395E+12 | 0.963565E+10 | 0.00 | 0.182701E+12 | 0.222853E+11 |
April | 0.375647E+12 | 0.909790E+10 | 0.00 | 0.181804E+12 | 0.169914E+11 |
May | 0.441595E+12 | 0.500632E+10 | 0.00 | 0.198236E+12 | 0.486535E+11 |
June | 0.462432E+12 | 0.123623E+10 | 0.00 | 0.116821E+12 | 0.180301E+12 |
July | 0.432084E+12 | 0.878928E+09 | 0.00 | 0.914580E+11 | 0.181927E+12 |
August | 0.429961E+12 | 0.121588E+10 | 0.00 | 0.942188E+11 | 0.175571E+12 |
September | 0.326134E+12 | 0.285749E+10 | 0.00 | 0.152497E+12 | 0.117041E+12 |
October | 0.286237E+12 | 0.782798E+10 | 0.00 | 0.203142E+12 | 0.348375E+11 |
November | 0.253617E+12 | 0.817235E+10 | 0.00 | 0.185756E+12 | 0.218313E+11 |
December | 0.199026E+12 | 0.118890E+11 | 0.00 | 0.163976E+12 | 0.223693E+11 |
Annual Sum or Average | 0.410714E+13 | 0.754075E+11 | 0.00 | 0.190123E+13 | 0.860335E+12 |
Minimum of Months | 0.199026E+12 | 0.878928E+09 | 0.00 | 0.914580E+11 | 0.169914E+11 |
Maximum of Months | 0.462432E+12 | 0.118890E+11 | 0.00 | 0.203142E+12 | 0.181927E+12 |