Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeSmall
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2024-07-03 12:21:18
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 149.31 | 292.09 | 292.09 |
Net Site Energy | 149.31 | 292.09 | 292.09 |
Total Source Energy | 434.49 | 850.02 | 850.02 |
Net Source Energy | 434.49 | 850.02 | 850.02 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.16 |
Net Conditioned Building Area | 511.16 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 18.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 36.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 6.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.31 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 130.89 | 18.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 18.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 9.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 36.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 10.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 48.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 6.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.16 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.16 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 18.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 9.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 36.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 10.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 48.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 6.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.31 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 90.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 71.44 | 36.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
Other | 94.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 256.07 | 36.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 90.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 71.44 | 36.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
Other | 94.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 256.07 | 36.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 130.890 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 130.890 | 100.00 |
Total On-Site and Utility Electric Sources | 130.890 | 100.00 |
Total Electricity End Uses | 130.890 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 58.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 58.31 | 100.00 |
Total Water End Uses | 58.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 5.00 |
Time Setpoint Not Met During Occupied Cooling | 3.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1364.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |ZoneHeatingSummaryMonthly
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |ZoneElectricSummaryMonthly
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |SpaceGainsMonthly
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |PeakSpaceGainsMonthly
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |ComfortReportSimple55Monthly
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |OccupantComfortDataSummaryMonthly
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |DXReportMonthly
| PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL | PSZ-AC:5 COOLING COIL |WindowReportMonthly
| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |WindowEnergyReportMonthly
| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |WindowZoneSummaryMonthly
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |WindowEnergyZoneSummaryMonthly
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |CoilReportMonthly
| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL | PSZ-AC:5 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |MechanicalVentilationLoadsMonthly
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 281.51 | 84.45 | 56.30 | 84.45 | 56.30 |
Above Ground Wall Area [m2] | 281.51 | 84.45 | 56.30 | 84.45 | 56.30 |
Window Opening Area [m2] | 59.65 | 16.72 | 11.15 | 20.63 | 11.15 |
Gross Window-Wall Ratio [%] | 21.19 | 19.80 | 19.80 | 24.43 | 19.80 |
Above Ground Window-Wall Ratio [%] | 21.19 | 19.80 | 19.80 | 24.43 | 19.80 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 281.51 | 84.45 | 56.30 | 84.45 | 56.30 |
Above Ground Wall Area [m2] | 281.51 | 84.45 | 56.30 | 84.45 | 56.30 |
Window Opening Area [m2] | 59.65 | 16.72 | 11.15 | 20.63 | 11.15 |
Gross Window-Wall Ratio [%] | 21.19 | 19.80 | 19.80 | 24.43 | 19.80 |
Above Ground Window-Wall Ratio [%] | 21.19 | 19.80 | 19.80 | 24.43 | 19.80 |
Total | |
Gross Roof Area [m2] | 598.76 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_ZN | 149.66 | Yes | Yes | 456.46 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3958 | 18.58 | 6.7800 |
PERIMETER_ZN_1 | 113.45 | Yes | Yes | 346.02 | 1.00 | 84.45 | 0.00 | 20.63 | 20.63 | 9.3958 | 18.58 | 6.7800 |
PERIMETER_ZN_2 | 67.30 | Yes | Yes | 205.26 | 1.00 | 56.30 | 0.00 | 11.15 | 11.15 | 9.3958 | 18.58 | 6.7800 |
PERIMETER_ZN_3 | 113.45 | Yes | Yes | 346.02 | 1.00 | 84.45 | 0.00 | 16.72 | 16.72 | 9.3958 | 18.58 | 6.7800 |
PERIMETER_ZN_4 | 67.30 | Yes | Yes | 205.26 | 1.00 | 56.30 | 0.00 | 11.15 | 11.15 | 9.3958 | 18.58 | 6.7800 |
ATTIC | 567.98 | No | No | 720.19 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.16 | 1559.03 | 281.51 | 0.00 | 59.65 | 59.65 | 9.3958 | 18.58 | 6.7800 | |||
Conditioned Total | 511.16 | 1559.03 | 281.51 | 0.00 | 59.65 | 59.65 | 9.3958 | 18.58 | 6.7800 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 567.98 | 720.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_ZN | 149.66 | Yes | Yes | 1.00 | CORE_ZN | GENERAL | CORE_ZN | 9.3958 | 18.58 | 6.7800 | |
PERIMETER_ZN_1 | 113.45 | Yes | Yes | 1.00 | PERIMETER_ZN_1 | GENERAL | PERIMETER_ZN_1 | 9.3958 | 18.58 | 6.7800 | |
PERIMETER_ZN_2 | 67.30 | Yes | Yes | 1.00 | PERIMETER_ZN_2 | GENERAL | PERIMETER_ZN_2 | 9.3958 | 18.58 | 6.7800 | |
PERIMETER_ZN_3 | 113.45 | Yes | Yes | 1.00 | PERIMETER_ZN_3 | GENERAL | PERIMETER_ZN_3 | 9.3958 | 18.58 | 6.7800 | |
PERIMETER_ZN_4 | 67.30 | Yes | Yes | 1.00 | PERIMETER_ZN_4 | GENERAL | PERIMETER_ZN_4 | 9.3958 | 18.58 | 6.7800 | |
ATTIC | 567.98 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.16 | 9.3958 | 9.29 | 6.7800 | |||||||
Conditioned Total | 511.16 | 9.3958 | 9.29 | 6.7800 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 567.98 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.16 | 511.16 | 0.00 | 567.98 | 9.3958 | 18.58 | 6.7800 |
Total | 511.16 | 511.16 | 0.00 | 567.98 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | 02-JAN-06:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 43327.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5097.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3060.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3325.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1731.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 545.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 13758.99 | 43327.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 43327.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5097.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3060.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 3325.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 1731.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 545.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 19.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 114.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 152.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 414.53 | 19.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 39.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 56.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 223.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 126.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 43.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 810.96 | 39.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 39.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 56.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 223.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 126.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 43.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 810.96 | 39.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
CORE_ZN DIRECT AIR | 0.311392 |
PERIMETER_ZN_1 DIRECT AIR | 0.427507 |
PERIMETER_ZN_2 DIRECT AIR | 0.250649 |
PERIMETER_ZN_3 DIRECT AIR | 0.259182 |
PERIMETER_ZN_4 DIRECT AIR | 0.296665 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 0.311392 | 0.311392 | 0.311392 | 0.311392 | 0.311392 | 0.311392 | 1.00 | 1.00 | 0.311392 |
PSZ-AC:2 | 0.427507 | 0.427507 | 0.427507 | 0.427507 | 0.427507 | 0.427507 | 1.00 | 1.00 | 0.427507 |
PSZ-AC:3 | 0.250649 | 0.250649 | 0.250649 | 0.250649 | 0.250649 | 0.250649 | 1.00 | 1.00 | 0.250649 |
PSZ-AC:4 | 0.259182 | 0.259182 | 0.259182 | 0.259182 | 0.259182 | 0.259182 | 1.00 | 1.000000 | 0.259182 |
PSZ-AC:5 | 0.296665 | 0.296665 | 0.296665 | 0.296665 | 0.296665 | 0.296665 | 1.00 | 1.00 | 0.296665 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 0.311392 | 0.064622 |
PSZ-AC:2_OA_CONTROLLER | 0.427507 | 0.048988 |
PSZ-AC:3_OA_CONTROLLER | 0.250649 | 0.029060 |
PSZ-AC:4_OA_CONTROLLER | 0.259182 | 0.048988 |
PSZ-AC:5_OA_CONTROLLER | 0.296665 | 0.029060 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 0.311392 | 0.311392 | 0.311392 | 0.311392 | 5256.96 | 8966.89 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 0.427507 | 0.427507 | 0.427507 | 0.427507 | 7076.76 | 11111.35 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 0.250649 | 0.250649 | 0.250649 | 0.250649 | 4149.14 | 6524.87 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.259182 | 0.259182 | 0.259182 | 0.259182 | 4335.52 | 7318.69 | 40.00 | 1.00 |
PSZ-AC:5_UNITARY_PACKAGE_DX | 0.296665 | 0.296665 | 0.296665 | 0.296665 | 4910.86 | 7561.68 | 40.00 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
PSZ-AC:1 FAN | 0.311392 |
PSZ-AC:2 FAN | 0.427507 |
PSZ-AC:3 FAN | 0.250649 |
PSZ-AC:4 FAN | 0.259182 |
PSZ-AC:5 FAN | 0.296665 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
PSZ-AC:1 COOLING COIL | 0.311392 | 5256.96 | 0.800500 |
PSZ-AC:2 COOLING COIL | 0.427507 | 7076.76 | 0.800655 |
PSZ-AC:3 COOLING COIL | 0.250649 | 4149.14 | 0.800655 |
PSZ-AC:4 COOLING COIL | 0.259182 | 4335.52 | 0.800828 |
PSZ-AC:5 COOLING COIL | 0.296665 | 4910.86 | 0.800655 |
Design Size Nominal Capacity [W] | |
PSZ-AC:1 HEATING COIL | 8966.89 |
PSZ-AC:2 HEATING COIL | 11111.35 |
PSZ-AC:3 HEATING COIL | 6524.87 |
PSZ-AC:4 HEATING COIL | 7318.69 |
PSZ-AC:5 HEATING COIL | 7561.68 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000004 | 0.000486 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000004 | 0.000000 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
PERIMETER_ZN_1_WALL_SOUTH | ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | |
PERIMETER_ZN_2_WALL_EAST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH | |
PERIMETER_ZN_3_WALL_NORTH | ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH | |
PERIMETER_ZN_4_WALL_WEST | ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH | |
Possible Shadow Receivers | |
PERIMETER_ZN_1_WALL_SOUTH | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | |
PERIMETER_ZN_2_WALL_EAST | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | |
PERIMETER_ZN_3_WALL_NORTH | PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | |
PERIMETER_ZN_4_WALL_WEST | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeSmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 6 | 71 | 23 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_ZN | 0.0 | 0.00 | 0.00 | 0.00 | 13.85 | 9.23 | 1.53 | 1 | 1 | 1 | 5.00 | 22.69 | 5.00 | 13.46 | 0.00 | 3.05 | 3.05 | 456.46 | TARP | TARP | 149.66 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | PERIMETER_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 13.85 | 2.21 | 1.53 | 1 | 1 | 1 | 0.00 | 27.69 | 0.00 | 5.00 | 0.00 | 3.05 | 3.05 | 346.02 | TARP | TARP | 113.45 | 84.45 | 63.82 | 20.63 | 6 | 7 | 0 | Yes |
3 | PERIMETER_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 25.64 | 9.23 | 1.53 | 1 | 1 | 1 | 22.69 | 27.69 | 0.00 | 18.46 | 0.00 | 3.05 | 3.05 | 205.27 | TARP | TARP | 67.30 | 56.30 | 45.15 | 11.15 | 6 | 4 | 0 | Yes |
4 | PERIMETER_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 13.85 | 16.25 | 1.53 | 1 | 1 | 1 | 0.00 | 27.69 | 13.46 | 18.46 | 0.00 | 3.05 | 3.05 | 346.02 | TARP | TARP | 113.45 | 84.45 | 63.83 | 16.72 | 6 | 8 | 0 | Yes |
5 | PERIMETER_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.05 | 9.23 | 1.53 | 1 | 1 | 1 | 0.00 | 5.00 | 0.00 | 18.46 | 0.00 | 3.05 | 3.05 | 205.27 | TARP | TARP | 67.30 | 56.30 | 45.15 | 11.15 | 6 | 4 | 0 | Yes |
6 | ATTIC | 0.0 | 0.00 | 0.00 | 0.00 | 13.85 | 9.23 | 3.70 | 1 | 1 | 1 | -0.60 | 28.29 | -0.60 | 19.06 | 3.05 | 6.33 | 1.64 | 720.19 | TARP | TARP | 567.98 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_ZN | 149.66 | 8.1 | 18.581 | 5.382E-002 | 9.396 | 6.780 | 0.000 | 0.000 | 0.000 | 0.000 | 16.176 | No |
2 | PERIMETER_ZN_1 | 113.45 | 6.1 | 18.581 | 5.382E-002 | 9.396 | 6.780 | 0.000 | 0.000 | 0.000 | 0.000 | 16.176 | No |
3 | PERIMETER_ZN_2 | 67.30 | 3.6 | 18.581 | 5.382E-002 | 9.396 | 6.780 | 0.000 | 0.000 | 0.000 | 0.000 | 16.176 | No |
4 | PERIMETER_ZN_3 | 113.45 | 6.1 | 18.581 | 5.382E-002 | 9.396 | 6.780 | 0.000 | 0.000 | 0.000 | 0.000 | 16.176 | No |
5 | PERIMETER_ZN_4 | 67.30 | 3.6 | 18.581 | 5.382E-002 | 9.396 | 6.780 | 0.000 | 0.000 | 0.000 | 0.000 | 16.176 | No |
6 | ATTIC | 567.98 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | CORE_ZN | BLDG_OCC_SCH_WO_SB | CORE_ZN | 149.66 | 8.1 | 8.1 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 |
2 | PERIMETER_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_ZN_1 | 113.45 | 6.1 | 6.1 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 |
3 | PERIMETER_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_ZN_2 | 67.30 | 3.6 | 3.6 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 4 |
4 | PERIMETER_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_ZN_3 | 113.45 | 6.1 | 6.1 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 |
5 | PERIMETER_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_ZN_4 | 67.30 | 3.6 | 3.6 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 4 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_ZN_LIGHTS | LTG_SCH_OFFICE | CORE_ZN | 149.66 | 8.1 | 1406.157 | 9.396 | 174.581 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1406.157 |
2 | PERIMETER_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_ZN_1 | 113.45 | 6.1 | 1065.958 | 9.396 | 174.581 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1065.958 |
3 | PERIMETER_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_ZN_2 | 67.30 | 3.6 | 632.340 | 9.396 | 174.581 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 632.340 |
4 | PERIMETER_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_ZN_3 | 113.45 | 6.1 | 1065.958 | 9.396 | 174.581 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1065.958 |
5 | PERIMETER_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_ZN_4 | 67.30 | 3.6 | 632.340 | 9.396 | 174.581 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 632.340 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_ZN_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_ZN | 149.66 | 8.1 | 1014.677 | 6.780 | 125.977 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1014.677 |
2 | PERIMETER_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_ZN_1 | 113.45 | 6.1 | 769.191 | 6.780 | 125.977 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 769.191 |
3 | PERIMETER_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_ZN_2 | 67.30 | 3.6 | 456.294 | 6.780 | 125.977 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 456.294 |
4 | PERIMETER_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_ZN_3 | 113.45 | 6.1 | 769.191 | 6.780 | 125.977 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 769.191 |
5 | PERIMETER_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_ZN_4 | 67.30 | 3.6 | 456.294 | 6.780 | 125.977 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 456.294 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_ZN_1 | 7 | 0 |
2 | PERIMETER_ZN_2 | 4 | 0 |
3 | PERIMETER_ZN_3 | 6 | 0 |
4 | PERIMETER_ZN_4 | 4 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_ZN_1 | 0 | |
2 | PERIMETER_ZN_2 | 0 | |
3 | PERIMETER_ZN_3 | 0 | |
4 | PERIMETER_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.1514 | 11722.8 | 1.001 | 0.9234 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_ZN_1_INFILTRATION | INFIL_QUARTER_ON_SCH | PERIMETER_ZN_1 | 113.45 | 6.1 | 2.165E-002 | 1.908E-004 | 2.563E-004 | 0.225 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_ZN_1 | 113.45 | 6.1 | 7.646E-002 | 6.739E-004 | 9.053E-004 | 0.795 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | PERIMETER_ZN_2_INFILTRATION | INFIL_QUARTER_ON_SCH | PERIMETER_ZN_2 | 67.30 | 3.6 | 1.443E-002 | 2.144E-004 | 2.563E-004 | 0.253 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_ZN_3_INFILTRATION | INFIL_QUARTER_ON_SCH | PERIMETER_ZN_3 | 113.45 | 6.1 | 2.165E-002 | 1.908E-004 | 2.450E-004 | 0.225 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_ZN_4_INFILTRATION | INFIL_QUARTER_ON_SCH | PERIMETER_ZN_4 | 67.30 | 3.6 | 1.443E-002 | 2.144E-004 | 2.563E-004 | 0.253 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 567.98 | 0.0 | 0.200 | 3.523E-004 | 3.052E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_ZN | Mixing/Well-Stirred |
2 | PERIMETER_ZN_1 | Mixing/Well-Stirred |
3 | PERIMETER_ZN_2 | Mixing/Well-Stirred |
4 | PERIMETER_ZN_3 | Mixing/Well-Stirred |
5 | PERIMETER_ZN_4 | Mixing/Well-Stirred |
6 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone CORE_ZN | 1.2000 |
3 | Zone PERIMETER_ZN_1 | 1.2000 |
4 | Zone PERIMETER_ZN_2 | 1.2000 |
5 | Zone PERIMETER_ZN_3 | 1.2000 |
6 | Zone PERIMETER_ZN_4 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone CORE_ZN | 1.2000 |
3 | Zone PERIMETER_ZN_1 | 1.2000 |
4 | Zone PERIMETER_ZN_2 | 1.2000 |
5 | Zone PERIMETER_ZN_3 | 1.2000 |
6 | Zone PERIMETER_ZN_4 | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_DAYLREFPT1 | 2.1604E-003 |
2 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_DAYLREFPT2 | 2.3949E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_DAYLREFPT1 | 2.4394E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_DAYLREFPT2 | 2.6586E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_DAYLREFPT1 | 1.2704E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_DAYLREFPT2 | 1.4378E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_DAYLREFPT1 | 6.1769E-004 |
8 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_DAYLREFPT2 | 6.9004E-004 |
9 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_DAYLREFPT1 | 1.2077E-002 |
10 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_DAYLREFPT2 | 1.2533E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_DAYLREFPT1 | 1.2409E-002 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_DAYLREFPT2 | 1.3857E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_DAYLREFPT1 | 1.0660E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_DAYLREFPT2 | 7.4604E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_DAYLREFPT1 | 5.2685E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_DAYLREFPT2 | 2.8551E-003 |
17 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_DAYLREFPT1 | 1.0592E-002 |
18 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_DAYLREFPT2 | 1.2036E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_DAYLREFPT1 | 1.0947E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_DAYLREFPT2 | 1.3379E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_DAYLREFPT1 | 9.0407E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_DAYLREFPT2 | 6.9707E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_DAYLREFPT1 | 4.3739E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_DAYLREFPT2 | 2.6377E-003 |
25 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_DAYLREFPT1 | 2.1529E-003 |
26 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_DAYLREFPT2 | 2.3799E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_DAYLREFPT1 | 2.4336E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_DAYLREFPT2 | 2.6483E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_DAYLREFPT1 | 1.2638E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_DAYLREFPT2 | 1.4214E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_DAYLREFPT1 | 6.1268E-004 |
32 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_DAYLREFPT2 | 6.7888E-004 |
33 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_DAYLREFPT1 | 2.0702E-003 |
34 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_DAYLREFPT2 | 2.0940E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_DAYLREFPT1 | 2.3601E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_DAYLREFPT2 | 2.3815E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_DAYLREFPT1 | 1.1983E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_DAYLREFPT2 | 1.2146E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_DAYLREFPT1 | 5.7821E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_DAYLREFPT2 | 5.8578E-004 |
41 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_DAYLREFPT1 | 2.0641E-003 |
42 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_DAYLREFPT2 | 2.0687E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_DAYLREFPT1 | 2.3549E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_DAYLREFPT2 | 2.3589E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_DAYLREFPT1 | 1.1941E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_DAYLREFPT2 | 1.1971E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_DAYLREFPT1 | 5.7597E-004 |
48 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_DAYLREFPT2 | 5.7743E-004 |
49 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_1_DAYLREFPT1 | 3.2171E-003 |
50 | Clear Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_1_DAYLREFPT2 | 3.8786E-003 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_1_DAYLREFPT1 | 3.5655E-003 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_1_DAYLREFPT2 | 4.2428E-003 |
53 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_1_DAYLREFPT1 | 1.9803E-003 |
54 | Intermediate Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_1_DAYLREFPT2 | 2.3594E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_1_DAYLREFPT1 | 9.7824E-004 |
56 | Overcast Sky | 12/21 | PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_1 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_1_DAYLREFPT2 | 1.0987E-003 |
57 | Clear Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_DAYLREFPT1 | 1.4473E-003 |
58 | Clear Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_DAYLREFPT2 | 1.6230E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_DAYLREFPT1 | 1.3444E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_DAYLREFPT2 | 1.4748E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_DAYLREFPT1 | 1.2059E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_DAYLREFPT2 | 1.2658E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_DAYLREFPT1 | 9.6923E-004 |
64 | Overcast Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_DAYLREFPT2 | 1.0358E-003 |
65 | Clear Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_DAYLREFPT1 | 5.9906E-003 |
66 | Clear Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_DAYLREFPT2 | 4.5998E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_DAYLREFPT1 | 4.8243E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_DAYLREFPT2 | 3.8256E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_DAYLREFPT1 | 4.1770E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_DAYLREFPT2 | 3.3265E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_DAYLREFPT1 | 4.7355E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_DAYLREFPT2 | 3.0307E-003 |
73 | Clear Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_DAYLREFPT1 | 1.5264E-002 |
74 | Clear Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_DAYLREFPT2 | 7.2483E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_DAYLREFPT1 | 1.6227E-002 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_DAYLREFPT2 | 7.0135E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_DAYLREFPT1 | 1.2005E-002 |
78 | Intermediate Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_DAYLREFPT2 | 6.1214E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_DAYLREFPT1 | 5.6490E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_DAYLREFPT2 | 3.2549E-003 |
81 | Clear Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_2_DAYLREFPT1 | 1.8345E-003 |
82 | Clear Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_2_DAYLREFPT2 | 2.2968E-003 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_2_DAYLREFPT1 | 1.8521E-003 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_2_DAYLREFPT2 | 2.3489E-003 |
85 | Intermediate Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_2_DAYLREFPT1 | 1.3300E-003 |
86 | Intermediate Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_2_DAYLREFPT2 | 1.5591E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_2_DAYLREFPT1 | 9.7407E-004 |
88 | Overcast Sky | 12/21 | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_2_DAYLREFPT2 | 1.0469E-003 |
89 | Clear Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_DAYLREFPT1 | 7.5450E-004 |
90 | Clear Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_DAYLREFPT2 | 8.9729E-004 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_DAYLREFPT1 | 6.0570E-004 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_DAYLREFPT2 | 7.1777E-004 |
93 | Intermediate Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_DAYLREFPT1 | 4.9451E-004 |
94 | Intermediate Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_DAYLREFPT2 | 5.6925E-004 |
95 | Overcast Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_DAYLREFPT1 | 6.1140E-004 |
96 | Overcast Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_DAYLREFPT2 | 6.7467E-004 |
97 | Clear Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_DAYLREFPT1 | 4.6938E-003 |
98 | Clear Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_DAYLREFPT2 | 4.0420E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_DAYLREFPT1 | 3.7020E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_DAYLREFPT2 | 3.0854E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_DAYLREFPT1 | 3.5433E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_DAYLREFPT2 | 2.1021E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_DAYLREFPT1 | 3.9914E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_DAYLREFPT2 | 2.5353E-003 |
105 | Clear Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_DAYLREFPT1 | 6.5543E-003 |
106 | Clear Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_DAYLREFPT2 | 4.7846E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_DAYLREFPT1 | 5.1025E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_DAYLREFPT2 | 3.6165E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_DAYLREFPT1 | 4.7221E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_DAYLREFPT2 | 2.3348E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_DAYLREFPT1 | 5.7858E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_DAYLREFPT2 | 2.9695E-003 |
113 | Clear Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_DAYLREFPT1 | 7.7284E-004 |
114 | Clear Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_DAYLREFPT2 | 9.4518E-004 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_DAYLREFPT1 | 6.2006E-004 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_DAYLREFPT2 | 7.5378E-004 |
117 | Intermediate Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_DAYLREFPT1 | 5.0557E-004 |
118 | Intermediate Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_DAYLREFPT2 | 5.8959E-004 |
119 | Overcast Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_DAYLREFPT1 | 6.2147E-004 |
120 | Overcast Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_DAYLREFPT2 | 6.9704E-004 |
121 | Clear Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_DAYLREFPT1 | 6.9053E-004 |
122 | Clear Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_DAYLREFPT2 | 7.1167E-004 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_DAYLREFPT1 | 5.5317E-004 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_DAYLREFPT2 | 5.7009E-004 |
125 | Intermediate Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_DAYLREFPT1 | 4.4972E-004 |
126 | Intermediate Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_DAYLREFPT2 | 4.6127E-004 |
127 | Overcast Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_DAYLREFPT1 | 5.7947E-004 |
128 | Overcast Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_DAYLREFPT2 | 5.8788E-004 |
129 | Clear Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_3_DAYLREFPT1 | 6.8444E-004 |
130 | Clear Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_3_DAYLREFPT2 | 6.8866E-004 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_3_DAYLREFPT1 | 5.4816E-004 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_3_DAYLREFPT2 | 5.5158E-004 |
133 | Intermediate Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_3_DAYLREFPT1 | 4.4588E-004 |
134 | Intermediate Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_3_DAYLREFPT2 | 4.4826E-004 |
135 | Overcast Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_3_DAYLREFPT1 | 5.7693E-004 |
136 | Overcast Sky | 12/21 | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_3_DAYLREFPT2 | 5.7851E-004 |
137 | Clear Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_DAYLREFPT1 | 1.7513E-003 |
138 | Clear Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_DAYLREFPT2 | 2.1560E-003 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_DAYLREFPT1 | 1.7406E-003 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_DAYLREFPT2 | 2.1638E-003 |
141 | Intermediate Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_DAYLREFPT1 | 1.2979E-003 |
142 | Intermediate Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_DAYLREFPT2 | 1.5158E-003 |
143 | Overcast Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_DAYLREFPT1 | 9.7565E-004 |
144 | Overcast Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_DAYLREFPT2 | 1.0480E-003 |
145 | Clear Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_DAYLREFPT1 | 1.3807E-002 |
146 | Clear Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_DAYLREFPT2 | 6.6925E-003 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_DAYLREFPT1 | 1.4370E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_DAYLREFPT2 | 6.3622E-003 |
149 | Intermediate Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_DAYLREFPT1 | 1.1493E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_DAYLREFPT2 | 5.8143E-003 |
151 | Overcast Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_DAYLREFPT1 | 5.6265E-003 |
152 | Overcast Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_DAYLREFPT2 | 3.2130E-003 |
153 | Clear Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_DAYLREFPT1 | 6.0202E-003 |
154 | Clear Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_DAYLREFPT2 | 4.5514E-003 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_DAYLREFPT1 | 4.8041E-003 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_DAYLREFPT2 | 3.7452E-003 |
157 | Intermediate Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_DAYLREFPT1 | 4.0783E-003 |
158 | Intermediate Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_DAYLREFPT2 | 3.1961E-003 |
159 | Overcast Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_DAYLREFPT1 | 4.7319E-003 |
160 | Overcast Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_DAYLREFPT2 | 2.9957E-003 |
161 | Clear Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | PERIMETER_ZN_4_DAYLREFPT1 | 1.4023E-003 |
162 | Clear Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | PERIMETER_ZN_4_DAYLREFPT2 | 1.5799E-003 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | PERIMETER_ZN_4_DAYLREFPT1 | 1.2833E-003 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | PERIMETER_ZN_4_DAYLREFPT2 | 1.4147E-003 |
165 | Intermediate Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | PERIMETER_ZN_4_DAYLREFPT1 | 1.1736E-003 |
166 | Intermediate Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | PERIMETER_ZN_4_DAYLREFPT2 | 1.2316E-003 |
167 | Overcast Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | PERIMETER_ZN_4_DAYLREFPT1 | 9.7064E-004 |
168 | Overcast Sky | 12/21 | PERIMETER_ZN_4_DAYLCTRL | PERIMETER_ZN_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | PERIMETER_ZN_4_DAYLREFPT2 | 1.0368E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_ZN | Cooling | 3486.20464 | 4183.44557 | 0.25949 | 0.31139 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 28.77600 | 8.82049E-003 | 149.65740 | 8.05449 | 6.46221E-002 | 0.00000 |
2 | CORE_ZN | Heating | 783.11518 | 939.73822 | 3.42507E-002 | 6.46221E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 149.65740 | 8.05449 | 6.46221E-002 | 0.00000 |
3 | PERIMETER_ZN_1 | Cooling | 4786.00246 | 5743.20296 | 0.35626 | 0.42751 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40000 | 8.82150E-003 | 113.45000 | 6.10582 | 4.89877E-002 | 0.00000 |
4 | PERIMETER_ZN_1 | Heating | 2352.41970 | 2822.90363 | 0.10288 | 0.12346 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 113.45000 | 6.10582 | 4.89877E-002 | 0.00000 |
5 | PERIMETER_ZN_2 | Cooling | 2806.22815 | 3367.47378 | 0.20887 | 0.25065 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 25.15333 | 8.81472E-003 | 67.30000 | 3.62205 | 2.90601E-002 | 0.00000 |
6 | PERIMETER_ZN_2 | Heating | 1481.10462 | 1777.32554 | 6.47763E-002 | 7.77316E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 67.30000 | 3.62205 | 2.90601E-002 | 0.00000 |
7 | PERIMETER_ZN_3 | Cooling | 2901.68432 | 3482.02118 | 0.21599 | 0.25918 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 28.88000 | 8.82066E-003 | 113.45000 | 6.10582 | 4.89877E-002 | 0.00000 |
8 | PERIMETER_ZN_3 | Heating | 2367.27813 | 2840.73375 | 0.10353 | 0.12424 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 113.45000 | 6.10582 | 4.89877E-002 | 0.00000 |
9 | PERIMETER_ZN_4 | Cooling | 3321.39980 | 3985.67976 | 0.24722 | 0.29666 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90400 | 8.81750E-003 | 67.30000 | 3.62205 | 2.90601E-002 | 0.00000 |
10 | PERIMETER_ZN_4 | Heating | 1473.80657 | 1768.56788 | 6.44571E-002 | 7.73486E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 67.30000 | 3.62205 | 2.90601E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 4495.41 | 0.31139 | 0.31139 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 3406.87 | 6.46221E-002 | 6.46221E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 5976.41 | 0.42751 | 0.42751 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 4260.63 | 0.12346 | 0.12346 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 3359.20 | 0.25065 | 0.25065 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 2628.71 | 7.77316E-002 | 7.77316E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 3719.78 | 0.25918 | 0.25918 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 4278.20 | 0.12424 | 0.12424 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
9 | PSZ-AC:5 | Cooling | Sensible | 4028.53 | 0.29666 | 0.29666 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC:5 | Heating | Sensible | 2620.08 | 7.73486E-002 | 7.73486E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CORE_ZN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.31139 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | PERIMETER_ZN_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.42751 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | PERIMETER_ZN_2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.25065 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | PERIMETER_ZN_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.25918 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | PERIMETER_ZN_4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.29666 |
6 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.31139 |
7 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.31139 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.31139 |
9 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.31139 |
10 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.31139 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.31139 |
12 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
13 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.42751 |
15 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.42751 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.42751 |
17 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.42751 |
18 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.42751 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.42751 |
20 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
21 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.25065 |
23 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.25065 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.25065 |
25 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.25065 |
26 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.25065 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 0.25065 |
28 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
29 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
30 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.25918 |
31 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.25918 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.25918 |
33 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.25918 |
34 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.25918 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.25918 |
36 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
37 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
38 | AirLoopHVAC | PSZ-AC:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.29666 |
39 | AirLoopHVAC | PSZ-AC:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.29666 |
40 | AirLoopHVAC | PSZ-AC:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.29666 |
41 | AirLoopHVAC | PSZ-AC:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.29666 |
42 | AirLoopHVAC | PSZ-AC:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.29666 |
43 | AirLoopHVAC | PSZ-AC:5 | Adjusted Main Design Air Flow Rate [m3/s] | 0.29666 |
44 | AirLoopHVAC | PSZ-AC:5 | User Heating Air Flow Ratio [] | 1.00000 |
45 | AirLoopHVAC | PSZ-AC:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
46 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 0.31139 |
47 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 0.42751 |
48 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 0.25065 |
49 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.25918 |
50 | AirLoopHVAC | PSZ-AC:5 | Design Supply Air Flow Rate [m3/s] | 0.29666 |
51 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.31139 |
52 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 6.46221E-002 |
53 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.31139 |
54 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.31139 |
55 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.31139 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.31139 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5256.95832 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8966.89499 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
61 | Fan:OnOff | PSZ-AC:1 FAN | Design Size Maximum Flow Rate [m3/s] | 0.31139 |
62 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.31139 |
63 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5256.95832 |
64 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80050 |
65 | Coil:Heating:Fuel | PSZ-AC:1 HEATING COIL | Design Size Nominal Capacity [W] | 8966.89499 |
66 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.42751 |
67 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 4.89877E-002 |
68 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.42751 |
69 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.42751 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.42751 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.42751 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7076.76158 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11111.35306 |
74 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
75 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
76 | Fan:OnOff | PSZ-AC:2 FAN | Design Size Maximum Flow Rate [m3/s] | 0.42751 |
77 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.42751 |
78 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7076.76158 |
79 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
80 | Coil:Heating:Fuel | PSZ-AC:2 HEATING COIL | Design Size Nominal Capacity [W] | 11111.35306 |
81 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.25065 |
82 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.90601E-002 |
83 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.25065 |
84 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.25065 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.25065 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.25065 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4149.13812 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6524.86671 |
89 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
90 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
91 | Fan:OnOff | PSZ-AC:3 FAN | Design Size Maximum Flow Rate [m3/s] | 0.25065 |
92 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:3 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.25065 |
93 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:3 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4149.13812 |
94 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:3 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
95 | Coil:Heating:Fuel | PSZ-AC:3 HEATING COIL | Design Size Nominal Capacity [W] | 6524.86671 |
96 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.25918 |
97 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 4.89877E-002 |
98 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.25918 |
99 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.25918 |
100 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.25918 |
101 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.25918 |
102 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4335.51532 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7318.69217 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
106 | Fan:OnOff | PSZ-AC:4 FAN | Design Size Maximum Flow Rate [m3/s] | 0.25918 |
107 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:4 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.25918 |
108 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:4 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4335.51532 |
109 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:4 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80083 |
110 | Coil:Heating:Fuel | PSZ-AC:4 HEATING COIL | Design Size Nominal Capacity [W] | 7318.69217 |
111 | Controller:OutdoorAir | PSZ-AC:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.29666 |
112 | Controller:OutdoorAir | PSZ-AC:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.90601E-002 |
113 | AirLoopHVAC:UnitarySystem | PSZ-AC:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.29666 |
114 | AirLoopHVAC:UnitarySystem | PSZ-AC:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.29666 |
115 | AirLoopHVAC:UnitarySystem | PSZ-AC:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.29666 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.29666 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC:5_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4910.85812 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7561.68169 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
121 | Fan:OnOff | PSZ-AC:5 FAN | Design Size Maximum Flow Rate [m3/s] | 0.29666 |
122 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:5 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.29666 |
123 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:5 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4910.85812 |
124 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:5 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
125 | Coil:Heating:Fuel | PSZ-AC:5 HEATING COIL | Design Size Nominal Capacity [W] | 7561.68169 |
126 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.04800E-006 |
127 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.85760E-004 |
128 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.04800E-006 |
129 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 1.72991E-008 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:1 COOLING COIL | 5012.9 | 3.10 | 10.59 | 11.08 | 10.48 | 10.44 |
2 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:2 COOLING COIL | 6741.7 | 3.09 | 10.55 | 11.04 | 10.44 | 10.38 |
3 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:3 COOLING COIL | 3952.7 | 3.09 | 10.55 | 11.04 | 10.44 | 10.38 |
4 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:4 COOLING COIL | 4132.4 | 3.10 | 10.57 | 11.06 | 10.46 | 10.41 |
5 | Coil:Cooling:DX:SingleSpeed | PSZ-AC:5 COOLING COIL | 4678.4 | 3.09 | 10.55 | 11.04 | 10.44 | 10.38 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_ZN | RunPeriod: RUNPERIOD 1 | 1.9310603027E-003 | 1.4673456464E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | PERIMETER_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2056415729 | 0.1865907765 | Pass | Pass | 0.7947076739 | 1.7861138215 | Pass | Pass |
3 | PERIMETER_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2209334160 | 0.1968969682 | Pass | Pass | 0.5634167523 | 1.3460378150 | Pass | Pass |
4 | PERIMETER_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2068640444 | 0.1868312412 | Pass | Pass | 0.8113188316 | 1.7979046590 | Pass | Pass |
5 | PERIMETER_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2226492448 | 0.1985420301 | Pass | Pass | 0.5571657354 | 1.3271759404 | Pass | Pass |
6 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.1125135177 | 0.1125308315 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 778.30 | 28.95 | 0.00 | 38.46 | 51.58 | 897.30 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 84.45 | 63.82 | 180.00 | 90.00 | S |
PERIMETER_ZN_1_FLOOR | PERIMETER_ZN_1_FLOOR_FFACTOR | 1.00 | 0.219 | 0.227 | 113.45 | 113.45 | 135.00 | 180.00 | |
PERIMETER_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 56.30 | 45.15 | 90.00 | 90.00 | E |
PERIMETER_ZN_2_FLOOR | PERIMETER_ZN_2_FLOOR_FFACTOR | 1.00 | 0.246 | 0.257 | 67.30 | 67.30 | 270.00 | 180.00 | |
PERIMETER_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 84.45 | 63.83 | 0.00 | 90.00 | N |
PERIMETER_ZN_3_FLOOR | PERIMETER_ZN_3_FLOOR_FFACTOR | 1.00 | 0.219 | 0.227 | 113.45 | 113.45 | 180.00 | 180.00 | |
PERIMETER_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 56.30 | 45.15 | 270.00 | 90.00 | W |
PERIMETER_ZN_4_FLOOR | PERIMETER_ZN_4_FLOOR_FFACTOR | 1.00 | 0.246 | 0.257 | 67.30 | 67.30 | 90.00 | 180.00 | |
ATTIC_SOFFIT_WEST | EXT_SOFFIT_FLOOR | 0.30 | 3.082 | 7.547 | 11.44 | 11.44 | 270.00 | 180.00 | |
ATTIC_SOFFIT_SOUTH | EXT_SOFFIT_FLOOR | 0.30 | 3.082 | 7.547 | 16.97 | 16.97 | 225.00 | 180.00 | |
ATTIC_SOFFIT_EAST | EXT_SOFFIT_FLOOR | 0.30 | 3.082 | 7.547 | 11.44 | 11.44 | 45.00 | 180.00 | |
ATTIC_SOFFIT_NORTH | EXT_SOFFIT_FLOOR | 0.30 | 3.082 | 7.547 | 16.97 | 16.97 | 315.00 | 180.00 | |
ATTIC_ROOF_NORTH | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 197.51 | 197.51 | 0.00 | 18.45 | |
ATTIC_ROOF_WEST | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 101.87 | 101.87 | 270.00 | 18.45 | |
ATTIC_ROOF_EAST | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 101.87 | 101.87 | 90.00 | 18.45 | |
ATTIC_ROOF_SOUTH | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 197.51 | 197.51 | 180.00 | 18.45 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_ZN_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 53.95 | 53.95 | 180.00 | 90.00 | S |
CORE_ZN_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 25.80 | 25.80 | 90.00 | 90.00 | E |
CORE_ZN_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 53.95 | 53.95 | 0.00 | 90.00 | N |
CORE_ZN_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 25.80 | 25.80 | 270.00 | 90.00 | W |
CORE_ZN_FLOOR | CORE_ZN_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 149.66 | 149.66 | 270.00 | 180.00 | |
CORE_ZN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 149.66 | 149.66 | 270.00 | 0.00 | |
PERIMETER_ZN_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 21.57 | 21.57 | 315.00 | 90.00 | N |
PERIMETER_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 21.57 | 21.57 | 45.00 | 90.00 | E |
PERIMETER_ZN_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 53.95 | 53.95 | 0.00 | 90.00 | N |
PERIMETER_ZN_1_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 113.45 | 113.45 | 45.00 | 0.00 | |
PERIMETER_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 21.57 | 21.57 | 315.00 | 90.00 | N |
PERIMETER_ZN_2_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 21.57 | 21.57 | 225.00 | 90.00 | W |
PERIMETER_ZN_2_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 25.80 | 25.80 | 270.00 | 90.00 | W |
PERIMETER_ZN_2_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 67.30 | 67.30 | 270.00 | 0.00 | |
PERIMETER_ZN_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 53.95 | 53.95 | 180.00 | 90.00 | S |
PERIMETER_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 21.57 | 21.57 | 225.00 | 90.00 | W |
PERIMETER_ZN_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 21.57 | 21.57 | 135.00 | 90.00 | S |
PERIMETER_ZN_3_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 113.45 | 113.45 | 180.00 | 0.00 | |
PERIMETER_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 21.57 | 21.57 | 135.00 | 90.00 | S |
PERIMETER_ZN_4_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 21.57 | 21.57 | 45.00 | 90.00 | E |
PERIMETER_ZN_4_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 25.80 | 25.80 | 90.00 | 90.00 | E |
PERIMETER_ZN_4_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 67.30 | 67.30 | 90.00 | 0.00 | |
ATTIC_FLOOR_PERIMETER_SOUTH | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 113.45 | 113.45 | 180.00 | 180.00 | |
ATTIC_FLOOR_PERIMETER_WEST | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 67.30 | 67.30 | 315.00 | 180.00 | |
ATTIC_FLOOR_PERIMETER_EAST | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 67.30 | 67.30 | 135.00 | 180.00 | |
ATTIC_FLOOR_CORE | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 149.66 | 149.66 | 270.00 | 180.00 | |
ATTIC_FLOOR_PERIMETER_NORTH | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 113.45 | 113.45 | 315.00 | 180.00 | |
CORE_ZN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 299.31 | 0.00 | 90.00 | N | ||
PERIMETER_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 226.90 | 0.00 | 90.00 | N | ||
PERIMETER_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.60 | 0.00 | 90.00 | N | ||
PERIMETER_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 226.90 | 0.00 | 90.00 | N | ||
PERIMETER_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.60 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_ZN_1_WALL_SOUTH_DOOR | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 3.91 | 0.00 | 0.00 | 3.91 | 3.91 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | WINDOW_U_0.38_SHGC_EAST_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | WINDOW_U_0.38_SHGC_EAST_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | WINDOW_U_0.38_SHGC_EAST_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | WINDOW_U_0.38_SHGC_EAST_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | WINDOW_U_0.38_SHGC_WEST_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | WINDOW_U_0.38_SHGC_WEST_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | WINDOW_U_0.38_SHGC_WEST_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | WINDOW_U_0.38_SHGC_WEST_0.36 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.159 | 0.361 | 0.397 | No | PERIMETER_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 59.65 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
North Total or Average | 16.72 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
Non-North Total or Average | 42.93 | 2.159 | 0.361 | 0.397 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_ZN_3_WALL_NORTH |
PERIMETER_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_ZN_3_WALL_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.54 | 0.28 | 1.00 | 1.00 | 1.00 |
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.54 | 0.28 | 1.00 | 1.00 | 1.00 |
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.54 | 0.28 | 1.00 | 1.00 | 1.00 |
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.54 | 0.28 | 1.00 | 1.00 | 1.00 |
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | 1.00 | 1.00 | 1.00 | 0.00 | 0.54 | 0.28 | 1.00 | 1.00 | 1.00 |
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | 1.00 | 1.00 | 1.00 | 0.02 | 0.54 | 0.28 | 1.00 | 1.00 | 1.00 |
PERIMETER_ZN_1_WALL_SOUTH_DOOR | 1.00 | 1.00 | 1.00 | 0.18 | 0.81 | 0.62 | 1.00 | 1.00 | 1.00 |
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | 1.00 | 0.04 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.73 | 0.00 |
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.86 | 0.00 | 0.00 | 1.00 |
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.86 | 0.00 | 0.00 | 1.00 |
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.86 | 0.00 | 0.00 | 1.00 |
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.86 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_ZN_LIGHTS | CORE_ZN | CORE_ZN | GENERAL | 9.3958 | 149.66 | 1406.16 | LightsWired | LTG_SCH_OFFICE | 55.32 | 168.00 | 43.88 | 0.0000 | Y | 11.58 |
PERIMETER_ZN_1_LIGHTS | PERIMETER_ZN_1 | PERIMETER_ZN_1 | GENERAL | 9.3958 | 113.45 | 1065.96 | LightsWired | LTG_SCH_OFFICE | 55.32 | 168.00 | 36.83 | 0.0000 | Y | 7.37 |
PERIMETER_ZN_2_LIGHTS | PERIMETER_ZN_2 | PERIMETER_ZN_2 | GENERAL | 9.3958 | 67.30 | 632.34 | LightsWired | LTG_SCH_OFFICE | 55.32 | 168.00 | 38.33 | 0.0000 | Y | 4.55 |
PERIMETER_ZN_3_LIGHTS | PERIMETER_ZN_3 | PERIMETER_ZN_3 | GENERAL | 9.3958 | 113.45 | 1065.96 | LightsWired | LTG_SCH_OFFICE | 55.32 | 168.00 | 40.00 | 0.0000 | Y | 8.00 |
PERIMETER_ZN_4_LIGHTS | PERIMETER_ZN_4 | PERIMETER_ZN_4 | GENERAL | 9.3958 | 67.30 | 632.34 | LightsWired | LTG_SCH_OFFICE | 55.32 | 168.00 | 38.39 | 0.0000 | Y | 4.56 |
Interior Lighting Total | 9.3958 | 511.16 | 4802.75 | 36.06 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_ZN_1_DAYLREFPT1 | PERIMETER_ZN_1 | PERIMETER_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.24 | 1065.96 | 255.72 |
PERIMETER_ZN_1_DAYLREFPT2 | PERIMETER_ZN_1 | PERIMETER_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.03 | 1065.96 | 32.19 |
PERIMETER_ZN_2_DAYLREFPT1 | PERIMETER_ZN_2 | PERIMETER_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.24 | 632.34 | 151.70 |
PERIMETER_ZN_2_DAYLREFPT2 | PERIMETER_ZN_2 | PERIMETER_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.03 | 632.34 | 19.10 |
PERIMETER_ZN_3_DAYLREFPT1 | PERIMETER_ZN_3 | PERIMETER_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.24 | 1065.96 | 255.72 |
PERIMETER_ZN_3_DAYLREFPT2 | PERIMETER_ZN_3 | PERIMETER_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.03 | 1065.96 | 32.19 |
PERIMETER_ZN_4_DAYLREFPT1 | PERIMETER_ZN_4 | PERIMETER_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.24 | 632.34 | 151.70 |
PERIMETER_ZN_4_DAYLREFPT2 | PERIMETER_ZN_4 | PERIMETER_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.03 | 632.34 | 19.10 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 87.95 | AstronomicalClock | - | 42.59 | 42.59 | 0.70 | |
EXTERIOR_LIGHTS_B | 200.47 | AstronomicalClock | - | 83.55 | 63.07 | 2.37 | |
EXTERIOR_LIGHTS_C | 773.25 | AstronomicalClock | - | 83.55 | 47.80 | 6.94 | |
Exterior Lighting Total | 1061.67 | 10.01 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5256.96 | 4208.19 | 1048.76 | 0.80 | 3.82 | |||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7076.76 | 5666.05 | 1410.72 | 0.80 | 3.82 | |||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4149.14 | 3322.03 | 827.11 | 0.80 | 3.82 | |||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4335.52 | 3472.00 | 863.51 | 0.80 | 3.82 | |||
PSZ-AC:5 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4910.86 | 3931.90 | 978.95 | 0.80 | 3.82 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1 COOLING COIL | 5012.9 | 3.10 | 10.59 | 11.08 | 10.48 | 10.44 | |
PSZ-AC:2 COOLING COIL | 6741.7 | 3.09 | 10.55 | 11.04 | 10.44 | 10.38 | |
PSZ-AC:3 COOLING COIL | 3952.7 | 3.09 | 10.55 | 11.04 | 10.44 | 10.38 | |
PSZ-AC:4 COOLING COIL | 4132.4 | 3.10 | 10.57 | 11.06 | 10.46 | 10.41 | |
PSZ-AC:5 COOLING COIL | 4678.4 | 3.09 | 10.55 | 11.04 | 10.44 | 10.38 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PSZ-AC:5 COOLING COIL | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | 8966.89 | 0.80 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | 11111.35 | 0.80 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | 6524.87 | 0.80 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | 7318.69 | 0.80 | |
PSZ-AC:5 HEATING COIL | Coil:Heating:Fuel | 7561.68 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC:1 FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 348.79 | 1120.11 | 1.00 | 1.87 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 |
PSZ-AC:2 FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 478.85 | 1120.11 | 1.00 | 1.68 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 |
PSZ-AC:3 FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 280.75 | 1120.11 | 1.00 | 2.04 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 |
PSZ-AC:4 FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 290.31 | 1120.11 | 1.00 | 2.01 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 |
PSZ-AC:5 FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 332.30 | 1120.11 | 1.00 | 1.90 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000004 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_ZN | 3486.20 | 4183.45 | 27.95 | 0.259 | 0.311 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 23.89 | 23.89 | 0.00901 | 28.78 | 0.00882 | 0.065 | 0.00 |
PERIMETER_ZN_1 | 4786.00 | 5743.20 | 50.62 | 0.356 | 0.428 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 23.89 | 23.89 | 0.00878 | 29.40 | 0.00882 | 0.049 | 0.00 |
PERIMETER_ZN_2 | 2806.23 | 3367.47 | 50.04 | 0.209 | 0.251 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 23.89 | 23.89 | 0.00879 | 25.15 | 0.00881 | 0.029 | 0.00 |
PERIMETER_ZN_3 | 2901.68 | 3482.02 | 30.69 | 0.216 | 0.259 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 23.89 | 23.89 | 0.00897 | 28.88 | 0.00882 | 0.049 | 0.00 |
PERIMETER_ZN_4 | 3321.40 | 3985.68 | 59.22 | 0.247 | 0.297 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 23.89 | 23.89 | 0.00874 | 26.90 | 0.00882 | 0.029 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_ZN | 783.12 | 939.74 | 6.28 | 0.034 | 0.065 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00800 | -4.20 | 0.00269 | 0.065 | 0.00 |
PERIMETER_ZN_1 | 2352.42 | 2822.90 | 24.88 | 0.103 | 0.123 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00773 | -4.20 | 0.00269 | 0.049 | 0.00 |
PERIMETER_ZN_2 | 1481.10 | 1777.33 | 26.41 | 0.065 | 0.078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00772 | -4.20 | 0.00269 | 0.029 | 0.00 |
PERIMETER_ZN_3 | 2367.28 | 2840.73 | 25.04 | 0.104 | 0.124 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00773 | -4.20 | 0.00269 | 0.049 | 0.00 |
PERIMETER_ZN_4 | 1473.81 | 1768.57 | 26.28 | 0.064 | 0.077 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00772 | -4.20 | 0.00269 | 0.029 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 0.31 | 0.31 | 0.06 | 0.06 | 0.3114 | 0.3114 | 0.3114 | 1.0000 | 1.0000 |
PSZ-AC:2 | 0.43 | 0.43 | 0.12 | 0.12 | 0.4275 | 0.4275 | 0.4275 | 1.0000 | 1.0000 |
PSZ-AC:3 | 0.25 | 0.25 | 0.08 | 0.08 | 0.2506 | 0.2506 | 0.2506 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.26 | 0.26 | 0.12 | 0.12 | 0.2592 | 0.2592 | 0.2592 | 1.0000 | 1.0000 |
PSZ-AC:5 | 0.30 | 0.30 | 0.08 | 0.08 | 0.2967 | 0.2967 | 0.2967 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | PSZ-AC:1 | 5256.958 | 4208.195 | 0.311392 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 5208.17 | 4814.06 | 0.311392 | 25.83 | 17.27 | 0.00897353 | 12.80 | 11.97 | 0.00850000 | 28.78 | 0.00882049 | 18.14 | 20.7526 | 23.89 | 0.00901621 | 48.1228 | 3473.41 | 0.00 | 5256.06 | 4172.75 |
PSZ-AC:1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | PSZ-AC:1 | 8966.895 | 8966.895 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8966.89 | 8966.89 | 0.311392 | 15.86 | 11.63 | 0.00689810 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.7526 | 21.11 | 0.00800000 | 50.6363 | 782.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | PSZ-AC:2 | 7076.762 | 5666.046 | 0.427507 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 6938.90 | 6601.32 | 0.427507 | 25.44 | 16.99 | 0.00878804 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 11.4589 | 23.89 | 0.00878371 | 46.9000 | 4786.00 | 0.00 | 7075.55 | 5617.55 |
PSZ-AC:2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | PSZ-AC:2 | 11111.353 | 11111.353 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 11111.35 | 11111.35 | 0.427507 | 18.21 | 12.84 | 0.00715484 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 11.4589 | 21.11 | 0.00773264 | 48.9663 | 2352.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | PSZ-AC:3 | 4149.138 | 3322.029 | 0.250649 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 4144.33 | 3933.95 | 0.250649 | 24.96 | 16.82 | 0.00879095 | 12.80 | 11.97 | 0.00850000 | 25.15 | 0.00881472 | 16.91 | 11.5939 | 23.89 | 0.00878826 | 46.9220 | 2804.94 | 0.00 | 4148.43 | 3293.60 |
PSZ-AC:3 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | PSZ-AC:3 | 6524.867 | 6524.867 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6524.87 | 6524.87 | 0.250649 | 18.18 | 12.81 | 0.00713486 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 11.5939 | 21.11 | 0.00771774 | 48.8733 | 1481.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | PSZ-AC:4 | 4335.515 | 3472.004 | 0.259182 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 4287.42 | 3984.34 | 0.259182 | 25.76 | 17.22 | 0.00893786 | 12.80 | 11.97 | 0.00850000 | 28.88 | 0.00882066 | 18.17 | 18.9009 | 23.89 | 0.00896693 | 47.8635 | 2892.15 | 0.00 | 4334.77 | 3442.51 |
PSZ-AC:4 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | PSZ-AC:4 | 7318.692 | 7318.692 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7318.69 | 7318.69 | 0.259182 | 16.33 | 11.70 | 0.00678089 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 18.9009 | 21.11 | 0.00773423 | 48.9763 | 2367.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC:5 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | PSZ-AC:5 | 4910.858 | 3931.904 | 0.296665 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 4867.91 | 4656.13 | 0.296665 | 25.11 | 16.84 | 0.00875014 | 12.80 | 11.97 | 0.00850000 | 26.90 | 0.00881750 | 17.51 | 9.7956 | 23.89 | 0.00874283 | 46.6829 | 3321.40 | 0.00 | 4910.02 | 3898.25 |
PSZ-AC:5 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | PSZ-AC:5 | 7561.682 | 7561.682 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7561.68 | 7561.68 | 0.296665 | 18.63 | 13.07 | 0.00722408 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 9.7956 | 21.11 | 0.00771641 | 48.8650 | 1473.81 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | CORE_ZN | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5256.958 | 4208.195 | 0.311392 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5214 | 1004.8586 | 1.1870 | PSZ-AC:1 FAN | Fan:OnOff | 0.311392 | 0.36961967 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | Sensible | 5208.17 | 4814.06 | 0.9907 | 0.36961967 | 0.311392 | 25.83 | 17.27 | 0.00897353 | 48825.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 348.793 | 4859.37 | 28.78 | 0.00882049 | 18.14 | 0.06462207 | 20.7526 | 23.89 | 0.00901361 | 23.89 | 0.00901621 | 48.1228 | 3473.41 | 0.00 | 5256.06 | 4172.75 | 0.35502248 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.18 | 14.47 | 0.00998828 | 40517.5 | |
PSZ-AC:1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | PSZ-AC:1 | CORE_ZN | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8966.895 | 8966.895 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:1 FAN | Fan:OnOff | 0.311392 | 0.36961967 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8966.89 | 8966.89 | 1.0000 | 0.36961967 | 0.311392 | 15.86 | 11.63 | 0.00689810 | 33389.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8966.89 | -4.20 | 0.00269032 | -4.20 | 0.06462207 | 20.7526 | 21.11 | 0.00800000 | 21.11 | 0.00800000 | 50.6363 | 782.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | PERIMETER_ZN_1 | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7076.762 | 5666.046 | 0.427507 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1765 | 1004.8586 | 1.1870 | PSZ-AC:2 FAN | Fan:OnOff | 0.427507 | 0.50744707 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | Sensible | 6938.90 | 6601.32 | 0.9805 | 0.50744707 | 0.427507 | 25.44 | 16.99 | 0.00878804 | 47961.7 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 478.854 | 6460.04 | 29.40 | 0.00882150 | 18.34 | 0.04898771 | 11.4589 | 23.89 | 0.00878371 | 23.89 | 0.00878371 | 46.9000 | 4786.00 | 0.00 | 7075.55 | 5617.55 | 0.48740674 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001183 | 40805.7 | |
PSZ-AC:2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | PSZ-AC:2 | PERIMETER_ZN_1 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11111.353 | 11111.353 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:2 FAN | Fan:OnOff | 0.427507 | 0.50744707 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 11111.35 | 11111.35 | 1.0000 | 0.50744707 | 0.427507 | 18.21 | 12.84 | 0.00715484 | 36433.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11111.35 | -4.20 | 0.00269032 | -4.20 | 0.04898771 | 11.4589 | 21.11 | 0.00773264 | 21.11 | 0.00773264 | 48.9663 | 2352.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | PERIMETER_ZN_2 | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4149.138 | 3322.029 | 0.250649 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1819 | 1004.8586 | 1.1870 | PSZ-AC:3 FAN | Fan:OnOff | 0.250649 | 0.29751857 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | Sensible | 4144.33 | 3933.95 | 0.9988 | 0.29751857 | 0.250649 | 24.96 | 16.82 | 0.00879095 | 47474.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 280.754 | 3863.57 | 25.15 | 0.00881472 | 16.91 | 0.02906014 | 11.5939 | 23.89 | 0.00878783 | 23.89 | 0.00878826 | 46.9220 | 2804.94 | 0.00 | 4148.43 | 3293.60 | 0.28576883 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001183 | 40805.7 | |
PSZ-AC:3 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | PSZ-AC:3 | PERIMETER_ZN_2 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6524.867 | 6524.867 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:3 FAN | Fan:OnOff | 0.250649 | 0.29751857 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6524.87 | 6524.87 | 1.0000 | 0.29751857 | 0.250649 | 18.18 | 12.81 | 0.00713486 | 36348.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6524.87 | -4.20 | 0.00269032 | -4.20 | 0.02906014 | 11.5939 | 21.11 | 0.00771774 | 21.11 | 0.00771774 | 48.8733 | 1481.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | PERIMETER_ZN_3 | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4335.515 | 3472.004 | 0.259182 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4550 | 1004.8586 | 1.1870 | PSZ-AC:4 FAN | Fan:OnOff | 0.259182 | 0.30764711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | Sensible | 4287.42 | 3984.34 | 0.9889 | 0.30764711 | 0.259182 | 25.76 | 17.22 | 0.00893786 | 48662.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 290.312 | 3997.11 | 28.88 | 0.00882066 | 18.17 | 0.04898771 | 18.9009 | 23.89 | 0.00896517 | 23.89 | 0.00896693 | 47.8635 | 2892.15 | 0.00 | 4334.77 | 3442.51 | 0.29549737 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.28 | 14.52 | 0.01000077 | 40653.0 | |
PSZ-AC:4 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | PSZ-AC:4 | PERIMETER_ZN_3 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7318.692 | 7318.692 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:4 FAN | Fan:OnOff | 0.259182 | 0.30764711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7318.69 | 7318.69 | 1.0000 | 0.30764711 | 0.259182 | 16.33 | 11.70 | 0.00678089 | 33569.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7318.69 | -4.20 | 0.00269032 | -4.20 | 0.04898771 | 18.9009 | 21.11 | 0.00773423 | 21.11 | 0.00773423 | 48.9763 | 2367.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:5 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | PSZ-AC:5 | PERIMETER_ZN_4 | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4910.858 | 3931.904 | 0.296665 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1061 | 1004.8586 | 1.1870 | PSZ-AC:5 FAN | Fan:OnOff | 0.296665 | 0.35213855 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | Sensible | 4867.91 | 4656.13 | 0.9913 | 0.35213855 | 0.296665 | 25.11 | 16.84 | 0.00875014 | 47522.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 332.297 | 4535.61 | 26.90 | 0.00881750 | 17.51 | 0.02906014 | 9.7956 | 23.89 | 0.00874283 | 23.89 | 0.00874283 | 46.6829 | 3321.40 | 0.00 | 4910.02 | 3898.25 | 0.33823174 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001183 | 40805.7 | |
PSZ-AC:5 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | PSZ-AC:5 | PERIMETER_ZN_4 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7561.682 | 7561.682 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:5 FAN | Fan:OnOff | 0.296665 | 0.35213855 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7561.68 | 7561.68 | 1.0000 | 0.35213855 | 0.296665 | 18.63 | 13.07 | 0.00722408 | 37037.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7561.68 | -4.20 | 0.00269032 | -4.20 | 0.02906014 | 9.7956 | 21.11 | 0.00771641 | 21.11 | 0.00771641 | 48.8650 | 1473.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_ZN | 1106.00 | 2338.00 | 119.50 |
PERIMETER_ZN_1 | 1473.00 | 3010.33 | 827.50 |
PERIMETER_ZN_2 | 1445.00 | 2580.17 | 1011.00 |
PERIMETER_ZN_3 | 1564.83 | 3378.50 | 1269.33 |
PERIMETER_ZN_4 | 1717.00 | 3112.50 | 1159.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 2378.17 | 3451.00 | 1364.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_ZN | 0.67 | 3.00 | 0.67 | 3.00 |
PERIMETER_ZN_1 | 1.83 | 0.00 | 1.33 | 0.00 |
PERIMETER_ZN_2 | 4.00 | 0.00 | 2.33 | 0.00 |
PERIMETER_ZN_3 | 7.67 | 0.00 | 5.00 | 0.00 |
PERIMETER_ZN_4 | 3.83 | 0.00 | 1.50 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 9.67 | 3.00 | 5.00 | 3.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_ZN | 4.75 | 8.05 | 456.46 | 0.367 | 0.000 | 0.000 | 0.000 |
PERIMETER_ZN_1 | 3.60 | 6.11 | 346.02 | 0.366 | 0.232 | 0.000 | 0.000 |
PERIMETER_ZN_2 | 1.93 | 3.62 | 205.26 | 0.333 | 0.028 | 0.000 | 0.000 |
PERIMETER_ZN_3 | 3.60 | 6.11 | 346.02 | 0.365 | 0.023 | 0.000 | 0.000 |
PERIMETER_ZN_4 | 2.13 | 3.62 | 205.26 | 0.366 | 0.026 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_ZN | 4.75 | 8.05 | 456.46 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_ZN_1 | 3.60 | 6.11 | 346.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_ZN_2 | 1.93 | 3.62 | 205.26 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_ZN_3 | 3.60 | 6.11 | 346.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_ZN_4 | 2.13 | 3.62 | 205.26 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_ZN | PSZ-AC:1 | 4.75 | 8.05 | 456.46 | 149.66 | 0.0646 | 0.065 |
PERIMETER_ZN_1 | PSZ-AC:2 | 3.60 | 6.11 | 346.02 | 113.45 | 0.0490 | 0.049 |
PERIMETER_ZN_2 | PSZ-AC:3 | 1.93 | 3.62 | 205.26 | 67.30 | 0.0291 | 0.029 |
PERIMETER_ZN_3 | PSZ-AC:4 | 3.60 | 6.11 | 346.02 | 113.45 | 0.0490 | 0.049 |
PERIMETER_ZN_4 | PSZ-AC:5 | 2.13 | 3.62 | 205.26 | 67.30 | 0.0291 | 0.029 |
Total Facility | 16.00 | 27.51 | 1559.03 | 511.16 | 0.2207 | 0.221 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_ZN | 703501.65 | 0.00 | 703501.65 | 0.00 | 703501.65 | 2037921.45 | 5736.00 | 3024.00 | 0.00 | 0.00 |
PERIMETER_ZN_1 | 533299.81 | 0.00 | 533299.81 | 400110.91 | 933410.71 | 1544876.42 | 5736.00 | 3024.00 | 0.00 | 0.00 |
PERIMETER_ZN_2 | 316360.31 | 0.00 | 316360.31 | 63438.46 | 379798.76 | 916440.58 | 5736.00 | 3024.00 | 0.00 | 756.00 |
PERIMETER_ZN_3 | 533299.81 | 0.00 | 533299.81 | 95157.68 | 628457.49 | 1544876.42 | 5736.00 | 3024.00 | 0.00 | 0.00 |
PERIMETER_ZN_4 | 316360.31 | 0.00 | 316360.31 | 63438.46 | 379798.76 | 916440.58 | 5736.00 | 3024.00 | 0.00 | 0.00 |
Total Facility | 2402821.88 | 0.00 | 2402821.88 | 622145.51 | 3024967.39 | 6960555.45 | 5736.00 | 3024.00 | 0.00 | 756.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_ZN | 0.0456 | 0.0000 | 0.0456 | 0.0000 | 0.0456 | 0.0646 | 1260.00 | 3024.00 | 0.00 |
PERIMETER_ZN_1 | 0.0346 | 0.0000 | 0.0346 | 0.0219 | 0.0565 | 0.0490 | 1260.00 | 3024.00 | 0.00 |
PERIMETER_ZN_2 | 0.0187 | 0.0000 | 0.0187 | 0.0016 | 0.0203 | 0.0291 | 1260.00 | 2268.00 | 0.00 |
PERIMETER_ZN_3 | 0.0346 | 0.0000 | 0.0346 | 0.0022 | 0.0367 | 0.0490 | 1260.00 | 3024.00 | 0.00 |
PERIMETER_ZN_4 | 0.0205 | 0.0000 | 0.0205 | 0.0014 | 0.0220 | 0.0291 | 1260.00 | 3024.00 | 0.00 |
Total Facility | 0.1540 | 0.0000 | 0.1540 | 0.0271 | 0.1811 | 0.2207 | 1260.00 | 3024.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC:1 | 991196.63 | 0.00 | 991196.63 | 2037921.45 | 5736.00 | 0.00 | 3024.00 | 0.00 |
PSZ-AC:2 | 751391.23 | 0.00 | 751391.23 | 1544876.42 | 5736.00 | 0.00 | 3024.00 | 0.00 |
PSZ-AC:3 | 445734.94 | 0.00 | 445734.94 | 916440.58 | 5736.00 | 0.00 | 3024.00 | 756.00 |
PSZ-AC:4 | 751391.23 | 0.00 | 751391.23 | 1544876.42 | 5736.00 | 0.00 | 3024.00 | 0.00 |
PSZ-AC:5 | 445734.94 | 0.00 | 445734.94 | 916440.58 | 5736.00 | 0.00 | 3024.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC:1 | 0.0643 | 0.0000 | 0.0643 | 0.0646 | 1260.00 | 0.00 | 3024.00 |
PSZ-AC:2 | 0.0487 | 0.0000 | 0.0487 | 0.0490 | 1260.00 | 0.00 | 3024.00 |
PSZ-AC:3 | 0.0263 | 0.0000 | 0.0263 | 0.0291 | 1260.00 | 0.00 | 2268.00 |
PSZ-AC:4 | 0.0487 | 0.0000 | 0.0487 | 0.0490 | 1260.00 | 0.00 | 3024.00 |
PSZ-AC:5 | 0.0289 | 0.0000 | 0.0289 | 0.0291 | 1260.00 | 0.00 | 3024.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC:1 | 0.00 | 3024.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:2 | 0.00 | 3024.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:3 | 0.00 | 3024.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:4 | 0.00 | 3024.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:5 | 0.00 | 3024.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC:1 | 0.0000 | 0.0910 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:2 | 0.0000 | 0.0690 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:3 | 0.0000 | 0.0409 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:4 | 0.0000 | 0.0690 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:5 | 0.0000 | 0.0409 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Surfaces by ClassTotal | Outdoors | |
Wall | 20 | 4 |
Floor | 14 | 8 |
Roof | 9 | 4 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 21 | 21 |
Door | 2 | 2 |
Glass Door | 1 | 1 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 5 |
Conditioned Zones | 5 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 541 |
Defaulted Fields | 372 |
Fields with Defaults | 1327 |
Autosized Fields | 100 |
Autosizable Fields | 122 |
Autocalculated Fields | 90 |
Autocalculatable Fields | 156 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 130.89 | 677.68 | 01-JAN-11:30 | 13758.99 | 10-AUG-16:00 |
Electricity:Building | 84.36 | 677.68 | 01-JAN-00:10 | 6744.96 | 02-JAN-08:10 |
Electricity:Zone:CORE_ZN | 25.72 | 198.41 | 01-JAN-00:10 | 1974.80 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 84.36 | 677.68 | 01-JAN-00:10 | 6744.96 | 02-JAN-08:10 |
InteriorLights:Electricity | 36.06 | 110.04 | 01-JAN-00:10 | 3419.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_ZN | 11.58 | 32.22 | 01-JAN-00:10 | 1001.21 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 36.06 | 110.04 | 01-JAN-00:10 | 3419.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 36.06 | 110.04 | 01-JAN-00:10 | 3419.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN | 11.58 | 32.22 | 01-JAN-00:10 | 1001.21 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 36.06 | 110.04 | 01-JAN-00:10 | 3419.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_ZN_1 | 18.09 | 150.41 | 01-JAN-00:10 | 1497.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 | 7.37 | 24.42 | 01-JAN-00:10 | 758.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 | 7.37 | 24.42 | 01-JAN-00:10 | 758.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_ZN_2 | 10.91 | 89.23 | 01-JAN-00:10 | 888.06 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 | 4.55 | 14.49 | 01-JAN-00:10 | 450.24 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 | 4.55 | 14.49 | 01-JAN-00:10 | 450.24 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_ZN_3 | 18.72 | 150.41 | 01-JAN-00:10 | 1497.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 | 8.00 | 24.42 | 01-JAN-00:10 | 758.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 | 8.00 | 24.42 | 01-JAN-00:10 | 758.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_ZN_4 | 10.92 | 89.23 | 01-JAN-00:10 | 888.06 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 | 4.56 | 14.49 | 01-JAN-00:10 | 450.24 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 | 4.56 | 14.49 | 01-JAN-00:10 | 450.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 48.30 | 567.64 | 01-JAN-00:10 | 3325.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_ZN | 14.14 | 166.20 | 01-JAN-00:10 | 973.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 48.30 | 567.64 | 01-JAN-00:10 | 3325.31 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 48.30 | 567.64 | 01-JAN-00:10 | 3325.31 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN | 14.14 | 166.20 | 01-JAN-00:10 | 973.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 48.30 | 567.64 | 01-JAN-00:10 | 3325.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 | 10.72 | 125.99 | 01-JAN-00:10 | 738.04 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 | 10.72 | 125.99 | 01-JAN-00:10 | 738.04 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 | 6.36 | 74.74 | 01-JAN-00:10 | 437.82 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 | 6.36 | 74.74 | 01-JAN-00:10 | 437.82 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 | 10.72 | 125.99 | 01-JAN-00:10 | 738.04 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 | 10.72 | 125.99 | 01-JAN-00:10 | 738.04 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 | 6.36 | 74.74 | 01-JAN-00:10 | 437.82 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 | 6.36 | 74.74 | 01-JAN-00:10 | 437.82 | 02-JAN-08:10 |
ElectricityPurchased:Facility | 130.89 | 677.68 | 07-JAN-10:00 | 13758.99 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 130.89 | 677.68 | 07-JAN-10:00 | 13758.99 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 130.89 | 677.68 | 07-JAN-10:00 | 13758.99 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 130.89 | 677.68 | 07-JAN-10:00 | 13758.99 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 130.89 | 677.68 | 07-JAN-10:00 | 13758.99 | 10-AUG-16:00 |
ElectricityNet:Plant | 130.89 | 677.68 | 07-JAN-10:00 | 13758.99 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 130.89 | 677.68 | 07-JAN-10:00 | 13758.99 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 130.89 | 677.68 | 07-JAN-10:00 | 13758.99 | 10-AUG-16:00 |
Electricity:HVAC | 29.57 | 0.00 | 01-JAN-11:30 | 6828.18 | 10-AUG-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 9.14 | 0.00 | 01-JAN-00:10 | 5097.17 | 10-AUG-16:00 |
General:Cooling:Electricity | 9.14 | 0.00 | 01-JAN-00:10 | 5097.17 | 10-AUG-16:00 |
Fans:Electricity | 20.43 | 0.00 | 01-JAN-11:30 | 1731.01 | 04-JAN-06:10 |
General:Fans:Electricity | 20.43 | 0.00 | 01-JAN-11:30 | 1731.01 | 04-JAN-06:10 |
ExteriorLights:Electricity | 10.01 | 0.00 | 01-JAN-08:10 | 1061.67 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 10.01 | 0.00 | 01-JAN-08:10 | 1061.67 | 01-JAN-06:10 |
Electricity:Plant | 6.95 | 0.00 | 01-JAN-00:10 | 897.70 | 13-FEB-12:30 |
WaterSystems:Electricity | 6.95 | 0.00 | 01-JAN-00:10 | 897.70 | 13-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 6.95 | 0.00 | 01-JAN-00:10 | 897.70 | 13-FEB-12:30 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-07:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 18.42 | 0.00 | 01-JAN-11:30 | 43327.81 | 02-JAN-06:20 |
NaturalGas:HVAC | 18.42 | 0.00 | 01-JAN-11:30 | 43327.81 | 02-JAN-06:20 |
Heating:NaturalGas | 18.42 | 0.00 | 01-JAN-11:30 | 43327.81 | 02-JAN-06:20 |
General:Heating:NaturalGas | 18.42 | 0.00 | 01-JAN-11:30 | 43327.81 | 02-JAN-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 58.31 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 58.31 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 58.31 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 29.16 | 0.00 | 01-JAN-00:10 | 0.00 | 10-MAR-12:40 |
MainsWater:Facility | 58.31 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 58.31 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 58.31 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 29.16 | 0.00 | 01-JAN-00:10 | 0.00 | 10-MAR-12:40 |
WaterUse:WaterSystems:Water | 29.16 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-12:10 |
WaterUse:WaterSystems:MainsWater | 29.16 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 105.52 | 0.00 | 01-JAN-11:30 | 70699.50 | 02-JAN-06:20 |
EnergyTransfer:Building | 52.03 | 0.00 | 01-JAN-11:30 | 36037.25 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_ZN | 16.00 | 0.00 | 01-JAN-00:10 | 8717.58 | 02-JAN-06:20 |
Heating:EnergyTransfer | 11.52 | 0.00 | 01-JAN-11:30 | 36037.25 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_ZN | 0.60 | 0.00 | 01-JAN-00:10 | 8717.58 | 02-JAN-06:20 |
General:Heating:EnergyTransfer | 11.52 | 0.00 | 01-JAN-11:30 | 36037.25 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_ZN | 0.60 | 0.00 | 01-JAN-00:10 | 8717.58 | 02-JAN-06:20 |
Cooling:EnergyTransfer | 40.50 | 0.00 | 01-JAN-00:10 | 15400.63 | 14-AUG-15:30 |
Cooling:EnergyTransfer:Zone:CORE_ZN | 15.40 | 0.00 | 01-JAN-00:10 | 4167.29 | 14-AUG-05:10 |
General:Cooling:EnergyTransfer | 40.50 | 0.00 | 01-JAN-00:10 | 15400.63 | 14-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_ZN | 15.40 | 0.00 | 01-JAN-00:10 | 4167.29 | 14-AUG-05:10 |
EnergyTransfer:Zone:PERIMETER_ZN_1 | 12.61 | 0.00 | 01-JAN-00:40 | 8900.33 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 | 3.49 | 0.00 | 01-JAN-00:40 | 8900.33 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 | 3.49 | 0.00 | 01-JAN-00:40 | 8900.33 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 | 9.12 | 0.00 | 01-JAN-00:10 | 5237.56 | 11-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 | 9.12 | 0.00 | 01-JAN-00:10 | 5237.56 | 11-SEP-14:00 |
EnergyTransfer:Zone:PERIMETER_ZN_2 | 7.00 | 0.00 | 01-JAN-00:40 | 5437.97 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 | 2.06 | 0.00 | 01-JAN-00:40 | 5437.97 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 | 2.06 | 0.00 | 01-JAN-00:40 | 5437.97 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 | 4.94 | 0.00 | 01-JAN-00:10 | 2885.12 | 24-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 | 4.94 | 0.00 | 01-JAN-00:10 | 2885.12 | 24-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_ZN_3 | 9.64 | 0.00 | 01-JAN-00:10 | 7545.31 | 17-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 | 3.39 | 0.00 | 01-JAN-00:10 | 7545.31 | 17-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 | 3.39 | 0.00 | 01-JAN-00:10 | 7545.31 | 17-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 | 6.25 | 0.00 | 01-JAN-00:10 | 2723.11 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 | 6.25 | 0.00 | 01-JAN-00:10 | 2723.11 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_ZN_4 | 6.77 | 0.00 | 01-JAN-00:40 | 5440.74 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 | 1.98 | 0.00 | 01-JAN-00:40 | 5440.74 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 | 1.98 | 0.00 | 01-JAN-00:40 | 5440.74 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 | 4.79 | 0.00 | 01-JAN-00:10 | 2894.94 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 | 4.79 | 0.00 | 01-JAN-00:10 | 2894.94 | 14-AUG-16:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 110.28 | 02-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 110.28 | 02-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 110.28 | 02-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 110.28 | 02-JAN-07:10 |
EnergyTransfer:HVAC | 53.50 | 0.00 | 01-JAN-11:30 | 34662.25 | 02-JAN-06:20 |
HeatingCoils:EnergyTransfer | 14.73 | 0.00 | 01-JAN-11:30 | 34662.25 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 38.76 | 0.00 | 01-JAN-00:10 | 19838.67 | 10-AUG-15:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 110.28 | 02-JAN-07:10 |
WaterSystems:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 110.28 | 02-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 110.28 | 02-JAN-07:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_ZN | 0.000 | 0.000 | 0.601 | -15.397 | 0.000 | 0.000 | 5.188 | 11.582 | 14.140 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -16.114 |
PERIMETER_ZN_1 | 0.000 | 0.000 | 3.488 | -9.122 | 0.000 | 0.000 | 4.008 | 7.370 | 10.719 | 16.296 | 0.000 | 0.045 | 0.000 | 0.000 | -9.213 | 0.000 | -5.238 | -18.354 |
PERIMETER_ZN_2 | 0.000 | 0.000 | 2.061 | -4.942 | 0.000 | 0.000 | 1.758 | 4.549 | 6.359 | 6.344 | 0.000 | 0.002 | 0.000 | 0.000 | -4.756 | 0.000 | -0.836 | -10.539 |
PERIMETER_ZN_3 | 0.000 | 0.000 | 3.393 | -6.252 | 0.000 | 0.000 | 4.084 | 8.004 | 10.719 | 3.441 | 0.000 | 0.003 | 0.000 | 0.000 | -7.270 | 0.000 | -1.225 | -14.897 |
PERIMETER_ZN_4 | 0.000 | 0.000 | 1.981 | -4.792 | 0.000 | 0.000 | 2.392 | 4.556 | 6.359 | 6.882 | 0.000 | 0.001 | 0.000 | 0.000 | -4.962 | 0.000 | -0.853 | -11.564 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.240 | 21.957 | 0.000 | 0.000 | 0.000 | -31.197 | -0.000 |
Total Facility | 0.000 | 0.000 | 11.523 | -40.504 | 0.000 | 0.000 | 17.430 | 36.062 | 48.296 | 32.964 | 0.000 | 9.291 | 21.957 | 0.000 | -26.200 | 0.000 | -39.349 | -71.468 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_ZN | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 | -4687.91 | 0.00 | 0.00 | 55.46 | 32.22 | 486.79 | 0.00 | 0.00 | 0.00 | 4113.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_1 | 11-SEP-05:01 | 0.00 | 0.00 | 0.00 | -6382.11 | 0.00 | 0.00 | 39.12 | 24.42 | 369.02 | 0.00 | 0.00 | 0.00 | 6737.65 | 0.00 | -581.19 | 0.00 | -206.93 | 0.00 |
PERIMETER_ZN_2 | 24-JUL-05:01 | 0.00 | 0.00 | 0.00 | -3743.28 | 0.00 | 0.00 | 23.65 | 14.49 | 218.91 | 677.04 | 0.00 | 0.00 | 2813.11 | 0.00 | -0.00 | 0.00 | -3.91 | 0.00 |
PERIMETER_ZN_3 | 24-JUL-05:01 | 0.00 | 0.00 | 0.00 | -3965.39 | 0.00 | 0.00 | 42.65 | 24.42 | 369.02 | 314.89 | 0.00 | 0.00 | 3219.91 | 0.00 | -0.00 | 0.00 | -5.51 | 0.00 |
PERIMETER_ZN_4 | 24-JUL-05:01 | 0.00 | 0.00 | 0.00 | -4406.95 | 0.00 | 0.00 | 22.68 | 14.49 | 218.91 | 0.00 | 0.00 | 0.00 | 4332.03 | 0.00 | -177.11 | 0.00 | -4.04 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-05:01 | 0.00 | 0.00 | 0.00 | -22850.25 | 0.00 | 0.00 | 180.33 | 110.04 | 1662.65 | 991.93 | 0.00 | 543.82 | 19962.62 | 0.00 | -471.26 | 0.00 | -129.88 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_ZN | 02-JAN-06:11 | 0.00 | 0.00 | 9287.06 | 0.00 | 0.00 | 0.00 | 72.84 | 255.86 | 486.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10102.56 |
PERIMETER_ZN_1 | 17-JAN-06:11 | 0.00 | 0.00 | 11481.52 | 0.00 | 0.00 | 0.00 | 55.22 | 193.96 | 369.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -602.80 | 0.00 | -308.03 | -11188.89 |
PERIMETER_ZN_2 | 17-JAN-06:11 | 0.00 | 0.00 | 6757.08 | 0.00 | 0.00 | 0.00 | 32.75 | 115.06 | 218.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -322.75 | 0.00 | -42.04 | -6759.02 |
PERIMETER_ZN_3 | 17-JAN-06:11 | 0.00 | 0.00 | 7602.82 | 0.00 | 0.00 | 0.00 | 55.22 | 193.96 | 369.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -474.75 | 0.00 | -59.78 | -7686.49 |
PERIMETER_ZN_4 | 17-JAN-06:11 | 0.00 | 0.00 | 7796.51 | 0.00 | 0.00 | 0.00 | 32.75 | 115.06 | 218.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -316.65 | 0.00 | -42.74 | -7803.84 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-JAN-06:11 | 0.00 | 0.00 | 42895.43 | 0.00 | 0.00 | 0.00 | 248.79 | 873.91 | 1662.65 | 0.00 | 0.00 | 328.70 | 0.00 | 0.00 | -1198.15 | 0.00 | -591.94 | -44219.38 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 0.3114 | 0.0000 | 8.0545 | 1.0000 | Calculated from schedules | 0.0646 | 0.3114 | 0.2075 | 1.0000 | Not calculated | 0.0646 | 0.2075 | ||
PSZ-AC:2 | 0.4275 | 0.0000 | 6.1058 | 1.0000 | Calculated from schedules | 0.0490 | 0.4275 | 0.1146 | 1.0000 | Not calculated | 0.0490 | 0.1146 | ||
PSZ-AC:3 | 0.2506 | 0.0000 | 3.6221 | 1.0000 | Calculated from schedules | 0.0291 | 0.2506 | 0.1159 | 1.0000 | Not calculated | 0.0291 | 0.1159 | ||
PSZ-AC:4 | 0.2592 | 0.0000 | 6.1058 | 1.0000 | Calculated from schedules | 0.0490 | 0.2592 | 0.1890 | 1.0000 | Not calculated | 0.0490 | 0.1890 | ||
PSZ-AC:5 | 0.2967 | 0.0000 | 3.6221 | 1.0000 | Calculated from schedules | 0.0291 | 0.2967 | 0.0980 | 1.0000 | Not calculated | 0.0291 | 0.0980 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 0.3114 | 0.0000 | 8.0545 | 1.0000 | Calculated from schedules | 0.0646 | 0.3114 | 1.0000 | 1.0000 | Not calculated | 0.0646 | 0.2075 | ||
PSZ-AC:2 | 0.4275 | 0.0000 | 6.1058 | 1.0000 | Calculated from schedules | 0.0490 | 0.4275 | 1.0000 | 1.0000 | Not calculated | 0.0490 | 0.1146 | ||
PSZ-AC:3 | 0.2506 | 0.0000 | 3.6221 | 1.0000 | Calculated from schedules | 0.0291 | 0.2506 | 1.0000 | 1.0000 | Not calculated | 0.0291 | 0.1159 | ||
PSZ-AC:4 | 0.2592 | 0.0000 | 6.1058 | 1.0000 | Calculated from schedules | 0.0490 | 0.2592 | 1.0000 | 1.0000 | Not calculated | 0.0490 | 0.1890 | ||
PSZ-AC:5 | 0.2967 | 0.0000 | 3.6221 | 1.0000 | Calculated from schedules | 0.0291 | 0.2967 | 1.0000 | 1.0000 | Not calculated | 0.0291 | 0.0980 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_ZN | PSZ-AC:1 | 0.000000 | 8.0545 | 0.000432 | 149.66 | 0.0646 | 1.0000 | 0.0646 | 1.000 | 0.0646 |
PERIMETER_ZN_1 | PSZ-AC:2 | 0.000000 | 6.1058 | 0.000432 | 113.45 | 0.0490 | 1.0000 | 0.0490 | 1.000 | 0.0490 |
PERIMETER_ZN_2 | PSZ-AC:3 | 0.000000 | 3.6221 | 0.000432 | 67.30 | 0.0291 | 1.0000 | 0.0291 | 1.000 | 0.0291 |
PERIMETER_ZN_3 | PSZ-AC:4 | 0.000000 | 6.1058 | 0.000432 | 113.45 | 0.0490 | 1.0000 | 0.0490 | 1.000 | 0.0490 |
PERIMETER_ZN_4 | PSZ-AC:5 | 0.000000 | 3.6221 | 0.000432 | 67.30 | 0.0291 | 1.0000 | 0.0291 | 1.000 | 0.0291 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 8.05 | 0.000432 | 149.6574 | 0.0646 | 0.0646 | 0.0646 |
PSZ-AC:2 | 0.000000 | 6.11 | 0.000432 | 113.4500 | 0.0490 | 0.0490 | 0.0490 |
PSZ-AC:3 | 0.000000 | 3.62 | 0.000432 | 67.3000 | 0.0291 | 0.0291 | 0.0291 |
PSZ-AC:4 | 0.000000 | 6.11 | 0.000432 | 113.4500 | 0.0490 | 0.0490 | 0.0490 |
PSZ-AC:5 | 0.000000 | 3.62 | 0.000432 | 67.3000 | 0.0291 | 0.0291 | 0.0291 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_ZN | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3114 | 0.3114 | 0.3114 | No | 0.0646 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_ZN_1 | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4275 | 0.4275 | 0.4275 | No | 0.0490 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_ZN_2 | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2506 | 0.2506 | 0.2506 | No | 0.0291 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_ZN_3 | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2592 | 0.2592 | 0.2592 | No | 0.0490 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_ZN_4 | PSZ-AC:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2967 | 0.2967 | 0.2967 | No | 0.0291 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 0.3114 | 0.3114 | 0.3114 | 0.3114 | 0.0646 | 1.0000 |
PSZ-AC:2 | 0.4275 | 0.4275 | 0.4275 | 0.4275 | 0.0490 | 1.0000 |
PSZ-AC:3 | 0.2506 | 0.2506 | 0.2506 | 0.2506 | 0.0291 | 1.0000 |
PSZ-AC:4 | 0.2592 | 0.2592 | 0.2592 | 0.2592 | 0.0490 | 1.0000 |
PSZ-AC:5 | 0.2967 | 0.2967 | 0.2967 | 0.2967 | 0.0291 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_ZN | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3114 | 0.3114 | 0.3114 | No | 0.0646 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_ZN_1 | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4275 | 0.4275 | 0.4275 | No | 0.0490 | 0.3968 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_ZN_2 | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2506 | 0.2506 | 0.2506 | No | 0.0291 | 0.3739 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_ZN_3 | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2592 | 0.2592 | 0.2592 | No | 0.0490 | 0.3943 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_ZN_4 | PSZ-AC:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2967 | 0.2967 | 0.2967 | No | 0.0291 | 0.3757 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 0.3114 | 0.3114 | 0.3114 | 0.3114 | 0.0646 | 1.0000 |
PSZ-AC:2 | 0.4275 | 0.4275 | 0.4275 | 0.4275 | 0.0490 | 1.0000 |
PSZ-AC:3 | 0.2506 | 0.2506 | 0.2506 | 0.2506 | 0.0291 | 1.0000 |
PSZ-AC:4 | 0.2592 | 0.2592 | 0.2592 | 0.2592 | 0.0490 | 1.0000 |
PSZ-AC:5 | 0.2967 | 0.2967 | 0.2967 | 0.2967 | 0.0291 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 511.16 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_ZN | 149.66 | 149.66 | 0.00 | 82.16 |
PERIMETER_ZN_1 | 113.45 | 113.45 | 0.00 | 82.16 |
PERIMETER_ZN_2 | 67.30 | 67.30 | 0.00 | 67.66 |
PERIMETER_ZN_3 | 113.45 | 113.45 | 0.00 | 82.16 |
PERIMETER_ZN_4 | 67.30 | 67.30 | 0.00 | 82.16 |
ATTIC | 567.98 | 0.00 | 567.98 | 0.00 |
Totals | 511.16 | 511.16 | 0.00 |
Data | |
Number of hours heating loads not met | 5.00 |
Number of hours cooling loads not met | 3.00 |
Number of hours not met | 8.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 18.42 | 43327.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 9.14 | 5097.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 36.06 | 3419.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 10.01 | 1061.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 48.30 | 3325.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 20.43 | 1731.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 6.95 | 897.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 48.30 | 130.89 |
Natural Gas | 0.00 | 18.42 |
Additional | 0.00 | 0.00 |
Total | 48.30 | 149.31 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 70.55 |
Space Heating | 0.00 |
Space Cooling | 17.88 |
Fans (All) | 39.97 |
Service Water Heating | 13.60 |
Receptacle Equipment | 94.48 |
Miscellaneous (All) | 256.07 |
Subtotal | 256.07 |
Natural Gas [MJ/m2] | |
Space Heating | 36.03 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 36.03 |
Subtotal | 36.03 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 24.15 |
Space Heating | 12.33 |
Space Cooling | 6.12 |
Fans (All) | 13.68 |
Service Water Heating | 4.66 |
Receptacle Equipment | 32.35 |
Miscellaneous | 6.71 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2885. | 8760. |
BLDG_EQUIP_SCH | 3948. | 8760. |
BLDG_OCC_SCH | 2512. | 4420. |
BLDG_OCC_SCH_W_SB | 1854. | 3640. |
BLDG_OCC_SCH_WO_SB | 2533. | 4420. |
BINARY OCCUPANCY | 4420. | 4420. |
INFIL_QUARTER_ON_SCH | 5991. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
BLDG_SWH_SCH | 2064. | 3900. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6200. | 8760. |
ALWAYS_OFF | 0. | 0. |
HVACOPERATIONSCHD_W_SB | 2600. | 2600. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 3120. | 3120. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | CORE_ZN DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_OPTIMUM | CORE_ZN DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_ZN | 8738.50 | 21.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_1 | 8649.67 | 110.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_2 | 8696.00 | 64.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_4 | 8565.83 | 194.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 7442.83 | 520.67 | 402.67 | 390.33 | 3.50 |
Min | 7442.83 | 0.50 | 0.00 | 0.00 | 0.00 |
Max | 8759.50 | 520.67 | 402.67 | 390.33 | 3.50 |
Average | 8475.39 | 151.86 | 67.11 | 65.06 | 0.58 |
Sum | 50852.33 | 911.17 | 402.67 | 390.33 | 3.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_ZN | 17892.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_1 | 13356.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_2 | 4788.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_3 | 13356.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_4 | 6804.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 17892.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 9366.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 56196.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_ZN | 7972.83 | 787.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_1 | 8634.50 | 125.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_2 | 8701.50 | 58.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_3 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_4 | 8572.83 | 187.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 7524.00 | 727.67 | 249.00 | 176.00 | 83.33 |
Min | 7524.00 | 3.50 | 0.00 | 0.00 | 0.00 |
Max | 8756.50 | 787.17 | 249.00 | 176.00 | 83.33 |
Average | 8360.36 | 314.92 | 41.50 | 29.33 | 13.89 |
Sum | 50162.17 | 1889.50 | 249.00 | 176.00 | 83.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_ZN | 17892.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_1 | 13356.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_2 | 4788.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_3 | 13356.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_4 | 6804.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 17892.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 9366.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 56196.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:18
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_ZN | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 35040.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_ZN | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_ZN_1 | 0.00 | 0.00 | 13356.00 | 0.00 |
PERIMETER_ZN_2 | 0.00 | 0.00 | 4788.00 | 0.00 |
PERIMETER_ZN_3 | 0.00 | 0.00 | 13356.00 | 0.00 |
PERIMETER_ZN_4 | 0.00 | 0.00 | 6804.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 13356.00 | 0.00 |
Average | 0.00 | 0.00 | 6384.00 | 0.00 |
Sum | 0.00 | 0.00 | 38304.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: CORE_ZN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.533677E+09 | 1338.57 | 06-JAN-11:00 | -0.6 | -0.6 | 0.234063E+09 | 373.04 | 11-JAN-16:19 | 13.67 | 10.10 |
February | 0.539178E+09 | 1362.48 | 09-FEB-08:70 | -0.6 | -1.1 | 0.223795E+09 | 402.33 | 28-FEB-16:10 | 13.98 | 10.63 |
March | 0.755324E+09 | 1321.41 | 01-MAR-07:13 | 0.33 | -1.4 | 0.302623E+09 | 402.34 | 17-MAR-15:09 | 12.80 | 8.51 |
April | 0.880878E+09 | 3976.47 | 28-APR-05:03 | 11.10 | 9.92 | 0.274933E+09 | 402.36 | 28-APR-14:20 | 18.13 | 12.83 |
May | 0.153410E+10 | 4604.22 | 15-MAY-05:03 | 10.28 | 8.68 | 0.311333E+09 | 402.36 | 08-MAY-15:20 | 10.28 | 8.68 |
June | 0.193498E+10 | 4687.95 | 12-JUN-05:02 | 14.40 | 13.42 | 0.312492E+09 | 402.36 | 12-JUN-10:30 | 17.25 | 14.57 |
July | 0.213533E+10 | 4480.60 | 19-JUL-05:02 | 11.57 | 9.58 | 0.284807E+09 | 402.36 | 11-JUL-07:40 | 11.57 | 9.58 |
August | 0.258343E+10 | 4451.69 | 14-AUG-05:01 | 15.37 | 13.48 | 0.327672E+09 | 402.36 | 02-AUG-08:50 | 15.37 | 13.48 |
September | 0.181658E+10 | 4501.63 | 11-SEP-05:01 | 12.12 | 10.60 | 0.284058E+09 | 402.36 | 01-SEP-10:50 | 12.12 | 10.60 |
October | 0.121595E+10 | 4686.16 | 05-OCT-05:03 | 8.30 | 5.23 | 0.295116E+09 | 402.35 | 25-OCT-13:20 | 13.50 | 10.37 |
November | 0.843396E+09 | 1577.41 | 08-NOV-16:10 | 9.90 | 8.67 | 0.269908E+09 | 402.35 | 08-NOV-14:39 | 9.90 | 8.67 |
December | 0.624220E+09 | 1316.73 | 06-DEC-16:57 | 1.10 | 0.98 | 0.232166E+09 | 375.16 | 05-DEC-15:09 | 1.10 | 0.98 |
Annual Sum or Average | 0.153970E+11 | 0.335297E+10 | ||||||||
Minimum of Months | 0.533677E+09 | 1316.73 | -0.6 | -1.4 | 0.223795E+09 | 373.04 | 1.10 | 0.98 | ||
Maximum of Months | 0.258343E+10 | 4687.95 | 15.37 | 13.48 | 0.327672E+09 | 402.36 | 18.13 | 14.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_ZN_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 90021759.98 | 771.00 | 06-JAN-11:27 | 0.00 | -0.0 | 0.171897E+09 | 297.73 | 20-JAN-14:30 | 6.95 | 4.83 |
February | 0.169375E+09 | 1424.58 | 27-FEB-15:10 | 19.90 | 12.22 | 0.165988E+09 | 305.00 | 28-FEB-14:50 | 13.98 | 10.93 |
March | 0.347924E+09 | 2021.73 | 02-MAR-14:30 | 13.30 | 8.35 | 0.213561E+09 | 305.00 | 10-MAR-14:39 | 16.30 | 11.68 |
April | 0.471287E+09 | 3398.96 | 27-APR-14:20 | 26.47 | 16.98 | 0.196268E+09 | 305.01 | 28-APR-14:20 | 18.13 | 12.83 |
May | 0.683430E+09 | 2753.92 | 15-MAY-14:00 | 23.30 | 13.50 | 0.229410E+09 | 305.01 | 05-MAY-15:00 | 23.30 | 13.50 |
June | 0.951679E+09 | 2877.09 | 29-JUN-05:02 | 12.80 | 11.44 | 0.234192E+09 | 305.01 | 29-JUN-15:39 | 17.60 | 13.26 |
July | 0.142444E+10 | 6347.44 | 24-JUL-05:01 | 15.87 | 13.15 | 0.215186E+09 | 305.02 | 14-JUL-13:39 | 15.87 | 13.15 |
August | 0.213277E+10 | 6276.01 | 14-AUG-05:01 | 15.37 | 13.48 | 0.248104E+09 | 305.02 | 04-AUG-13:50 | 15.37 | 13.48 |
September | 0.154246E+10 | 6382.09 | 11-SEP-05:01 | 12.12 | 10.60 | 0.214081E+09 | 305.02 | 22-SEP-13:20 | 21.67 | 16.70 |
October | 0.881597E+09 | 4786.92 | 04-OCT-13:50 | 21.02 | 11.37 | 0.216997E+09 | 305.00 | 06-OCT-15:09 | 17.30 | 12.22 |
November | 0.262043E+09 | 1400.24 | 02-NOV-13:30 | 14.40 | 11.48 | 0.191708E+09 | 305.01 | 02-NOV-13:39 | 14.40 | 11.44 |
December | 0.164486E+09 | 1331.79 | 05-DEC-13:20 | 10.60 | 6.25 | 0.169236E+09 | 304.99 | 05-DEC-16:10 | 6.10 | 4.53 |
Annual Sum or Average | 0.912152E+10 | 0.246663E+10 | ||||||||
Minimum of Months | 90021759.98 | 771.00 | 0.00 | -0.0 | 0.165988E+09 | 297.73 | 6.10 | 4.53 | ||
Maximum of Months | 0.213277E+10 | 6382.09 | 26.47 | 16.98 | 0.248104E+09 | 305.02 | 23.30 | 16.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_ZN_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11325118.91 | 332.89 | 06-JAN-16:30 | 2.50 | 2.03 | 73118371.04 | 149.45 | 11-JAN-16:19 | 13.67 | 10.10 |
February | 38598427.22 | 340.96 | 09-FEB-09:58 | 3.30 | 1.91 | 67771808.28 | 169.97 | 27-FEB-16:00 | 18.90 | 12.17 |
March | 0.105595E+09 | 412.04 | 02-MAR-08:07 | 2.15 | 1.10 | 87838937.34 | 178.02 | 14-MAR-15:00 | 17.20 | 10.94 |
April | 0.220150E+09 | 1411.88 | 27-APR-10:02 | 19.27 | 13.13 | 84796763.07 | 180.93 | 28-APR-14:39 | 17.97 | 12.77 |
May | 0.439929E+09 | 1663.22 | 15-MAY-08:52 | 17.20 | 11.71 | 0.100109E+09 | 180.94 | 05-MAY-15:00 | 17.20 | 11.71 |
June | 0.786441E+09 | 2010.96 | 28-JUN-08:52 | 18.90 | 13.39 | 0.102492E+09 | 180.94 | 12-JUN-12:39 | 18.90 | 13.39 |
July | 0.968333E+09 | 3743.27 | 24-JUL-05:01 | 15.87 | 13.15 | 93801121.47 | 180.94 | 26-JUL-15:00 | 22.80 | 17.11 |
August | 0.126610E+10 | 3646.77 | 14-AUG-05:01 | 15.37 | 13.48 | 0.108008E+09 | 180.94 | 16-AUG-14:50 | 19.55 | 15.96 |
September | 0.683234E+09 | 3682.20 | 11-SEP-05:01 | 12.12 | 10.60 | 92994206.06 | 180.94 | 13-SEP-12:00 | 21.10 | 16.89 |
October | 0.280548E+09 | 1314.53 | 04-OCT-10:02 | 17.48 | 10.97 | 92383396.45 | 180.93 | 06-OCT-12:00 | 16.70 | 12.03 |
November | 0.101646E+09 | 342.66 | 22-NOV-09:57 | 3.30 | 3.04 | 80387882.82 | 180.93 | 02-NOV-14:30 | 3.30 | 3.04 |
December | 40024707.23 | 372.59 | 06-DEC-09:00 | 0.90 | 0.78 | 69935993.22 | 148.18 | 05-DEC-13:00 | 0.90 | 0.78 |
Annual Sum or Average | 0.494193E+10 | 0.105364E+10 | ||||||||
Minimum of Months | 11325118.91 | 332.89 | 0.90 | 0.78 | 67771808.28 | 148.18 | 0.90 | 0.78 | ||
Maximum of Months | 0.126610E+10 | 3743.27 | 19.27 | 13.48 | 0.108008E+09 | 180.94 | 22.80 | 17.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_ZN_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32726480.55 | 687.18 | 05-JAN-16:53 | 3.90 | 3.16 | 0.168731E+09 | 246.21 | 11-JAN-16:10 | 14.03 | 10.30 |
February | 63340351.93 | 719.69 | 16-FEB-15:35 | 2.80 | 1.89 | 0.154888E+09 | 272.67 | 28-FEB-16:00 | 14.40 | 10.82 |
March | 0.224234E+09 | 642.79 | 29-MAR-13:51 | 5.60 | 4.80 | 0.194008E+09 | 293.12 | 10-MAR-15:30 | 5.60 | 4.80 |
April | 0.273361E+09 | 1284.21 | 27-APR-15:53 | 27.20 | 16.90 | 0.184127E+09 | 305.00 | 27-APR-14:39 | 27.20 | 16.90 |
May | 0.569306E+09 | 1588.36 | 05-MAY-15:30 | 24.70 | 17.20 | 0.228101E+09 | 305.01 | 05-MAY-15:00 | 25.00 | 17.36 |
June | 0.920042E+09 | 2083.27 | 28-JUN-15:53 | 26.10 | 16.29 | 0.234826E+09 | 305.01 | 23-JUN-10:50 | 26.10 | 16.29 |
July | 0.118563E+10 | 3965.37 | 24-JUL-05:01 | 15.87 | 13.15 | 0.215211E+09 | 305.01 | 14-JUL-13:30 | 15.87 | 13.15 |
August | 0.146706E+10 | 3739.14 | 09-AUG-05:02 | 14.97 | 12.17 | 0.247550E+09 | 305.01 | 16-AUG-15:50 | 18.98 | 15.94 |
September | 0.792482E+09 | 2533.84 | 01-SEP-05:02 | 15.50 | 13.57 | 0.212839E+09 | 305.01 | 13-SEP-13:30 | 21.95 | 17.16 |
October | 0.407901E+09 | 1269.99 | 04-OCT-15:57 | 21.10 | 11.40 | 0.207009E+09 | 305.00 | 06-OCT-13:20 | 16.87 | 12.01 |
November | 0.242121E+09 | 676.75 | 10-NOV-08:10 | 5.18 | 4.64 | 0.182545E+09 | 303.47 | 03-NOV-15:00 | 5.18 | 4.64 |
December | 73467979.46 | 612.05 | 21-DEC-11:23 | 5.10 | 3.68 | 0.160926E+09 | 241.67 | 29-DEC-16:10 | 10.40 | 8.63 |
Annual Sum or Average | 0.625167E+10 | 0.239076E+10 | ||||||||
Minimum of Months | 32726480.55 | 612.05 | 2.80 | 1.89 | 0.154888E+09 | 241.67 | 5.18 | 4.64 | ||
Maximum of Months | 0.146706E+10 | 3965.37 | 27.20 | 17.20 | 0.247550E+09 | 305.01 | 27.20 | 17.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_ZN_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19869412.74 | 296.63 | 06-JAN-16:03 | 3.03 | 2.40 | 0.100524E+09 | 153.60 | 11-JAN-16:10 | 14.03 | 10.30 |
February | 30188452.22 | 272.12 | 09-FEB-16:43 | 5.10 | 2.79 | 94124919.87 | 180.92 | 27-FEB-16:49 | 18.98 | 12.21 |
March | 85968509.70 | 653.66 | 02-MAR-16:35 | 12.97 | 8.50 | 0.120784E+09 | 180.96 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.177377E+09 | 1801.61 | 27-APR-15:55 | 27.20 | 16.90 | 0.114545E+09 | 180.94 | 28-APR-14:39 | 17.97 | 12.77 |
May | 0.458742E+09 | 2171.00 | 15-MAY-15:57 | 23.90 | 12.85 | 0.138058E+09 | 180.94 | 08-MAY-15:30 | 23.90 | 12.85 |
June | 0.706575E+09 | 3891.73 | 23-JUN-05:02 | 13.80 | 11.92 | 0.140367E+09 | 180.94 | 23-JUN-10:00 | 15.00 | 12.45 |
July | 0.995060E+09 | 4406.93 | 24-JUL-05:01 | 15.87 | 13.15 | 0.128724E+09 | 180.94 | 11-JUL-15:00 | 15.87 | 13.15 |
August | 0.120247E+10 | 4316.78 | 09-AUG-05:02 | 14.97 | 12.17 | 0.147848E+09 | 180.94 | 30-AUG-14:30 | 24.00 | 16.72 |
September | 0.704519E+09 | 4347.14 | 11-SEP-05:01 | 12.12 | 10.60 | 0.127531E+09 | 180.94 | 13-SEP-14:20 | 22.97 | 17.25 |
October | 0.275761E+09 | 2022.90 | 04-OCT-15:57 | 21.10 | 11.40 | 0.127466E+09 | 180.93 | 06-OCT-13:20 | 16.87 | 12.01 |
November | 91433499.59 | 387.49 | 08-NOV-15:50 | 9.90 | 8.81 | 0.111716E+09 | 180.93 | 08-NOV-15:20 | 9.90 | 8.81 |
December | 44537556.82 | 374.65 | 06-DEC-17:00 | 1.10 | 0.98 | 96619809.13 | 160.05 | 01-DEC-15:00 | 1.10 | 0.98 |
Annual Sum or Average | 0.479250E+10 | 0.144831E+10 | ||||||||
Minimum of Months | 19869412.74 | 272.12 | 1.10 | 0.98 | 94124919.87 | 153.60 | 1.10 | 0.98 | ||
Maximum of Months | 0.120247E+10 | 4406.93 | 27.20 | 16.90 | 0.147848E+09 | 180.96 | 24.00 | 17.25 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.29 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.29 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.22 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.22 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.75 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.75 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.42 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.04 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.04 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.75 | 0.00 | 0.00 | 17.17 | 13.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_ZN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.277470E+09 | 9287.05 | 02-JAN-06:11 | 6.10 |
February | 93560295.34 | 9227.35 | 21-FEB-06:11 | 1.70 |
March | 28892800.50 | 9117.07 | 06-MAR-06:01 | 6.70 |
April | 22381917.99 | 459.60 | 27-APR-17:12 | 26.10 |
May | 4796370.27 | 435.82 | 15-MAY-05:07 | 10.28 |
June | 5744418.06 | 470.07 | 28-JUN-17:02 | 26.52 |
July | 10161880.20 | 618.59 | 24-JUL-17:12 | 28.50 |
August | 19240540.92 | 868.74 | 10-AUG-17:01 | 31.62 |
September | 3037470.63 | 427.07 | 29-SEP-05:07 | 11.52 |
October | 8585329.77 | 433.23 | 04-OCT-05:07 | 11.52 |
November | 27927517.00 | 9116.57 | 27-NOV-06:01 | 11.70 |
December | 98805505.81 | 9225.84 | 26-DEC-06:11 | -1.0 |
Annual Sum or Average | 0.600604E+09 | |||
Minimum of Months | 3037470.63 | 427.07 | -1.0 | |
Maximum of Months | 0.277470E+09 | 9287.05 | 31.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_ZN_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118917E+10 | 11481.50 | 17-JAN-06:11 | 1.30 |
February | 0.605045E+09 | 11420.80 | 21-FEB-06:11 | 1.70 |
March | 0.281946E+09 | 11164.54 | 06-MAR-06:01 | 6.70 |
April | 0.140873E+09 | 10997.27 | 18-APR-05:01 | 3.30 |
May | 48842736.25 | 2125.90 | 18-MAY-06:10 | 5.68 |
June | 32328523.41 | 556.29 | 29-JUN-05:04 | 12.80 |
July | 23025108.65 | 649.63 | 24-JUL-05:04 | 15.87 |
August | 28132918.33 | 760.74 | 10-AUG-17:23 | 31.25 |
September | 16623605.10 | 640.97 | 01-SEP-05:03 | 15.50 |
October | 44409015.49 | 1814.30 | 16-OCT-06:10 | 6.60 |
November | 0.307775E+09 | 11167.46 | 13-NOV-06:01 | 1.70 |
December | 0.769758E+09 | 11460.82 | 26-DEC-06:11 | -1.0 |
Annual Sum or Average | 0.348793E+10 | |||
Minimum of Months | 16623605.10 | 556.29 | -1.0 | |
Maximum of Months | 0.118917E+10 | 11481.50 | 31.25 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_ZN_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.738693E+09 | 6757.07 | 17-JAN-06:11 | 1.30 |
February | 0.421744E+09 | 6743.73 | 21-FEB-06:11 | 1.70 |
March | 0.153108E+09 | 6554.53 | 06-MAR-06:01 | 6.70 |
April | 49456239.39 | 6455.57 | 18-APR-05:01 | 3.30 |
May | 21567170.65 | 1057.79 | 30-MAY-05:05 | 10.60 |
June | 14554842.84 | 322.10 | 29-JUN-05:04 | 12.80 |
July | 12795432.95 | 380.27 | 24-JUL-17:12 | 28.50 |
August | 16792526.38 | 460.65 | 10-AUG-17:01 | 31.62 |
September | 14157677.39 | 367.52 | 14-SEP-05:04 | 12.62 |
October | 22577964.56 | 2787.11 | 30-OCT-05:03 | 7.20 |
November | 0.149567E+09 | 6556.92 | 13-NOV-06:01 | 1.70 |
December | 0.446124E+09 | 6744.98 | 26-DEC-06:11 | -1.0 |
Annual Sum or Average | 0.206114E+10 | |||
Minimum of Months | 12795432.95 | 322.10 | -1.0 | |
Maximum of Months | 0.738693E+09 | 6757.07 | 31.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_ZN_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116888E+10 | 7602.81 | 17-JAN-06:11 | 1.30 |
February | 0.751715E+09 | 7598.92 | 21-FEB-06:11 | 1.70 |
March | 0.294243E+09 | 7488.79 | 06-MAR-06:13 | 6.70 |
April | 0.101133E+09 | 7361.95 | 18-APR-05:01 | 3.30 |
May | 23910493.91 | 1193.61 | 30-MAY-05:05 | 10.60 |
June | 17314032.42 | 380.84 | 28-JUN-17:02 | 26.52 |
July | 12594313.60 | 489.14 | 24-JUL-17:12 | 28.50 |
August | 19492187.00 | 673.47 | 10-AUG-17:01 | 31.62 |
September | 16753700.03 | 329.74 | 14-SEP-05:04 | 12.62 |
October | 32048821.44 | 6992.86 | 30-OCT-05:03 | 7.20 |
November | 0.243032E+09 | 7451.45 | 27-NOV-06:13 | 11.70 |
December | 0.711407E+09 | 7595.15 | 26-DEC-06:11 | -1.0 |
Annual Sum or Average | 0.339252E+10 | |||
Minimum of Months | 12594313.60 | 329.74 | -1.0 | |
Maximum of Months | 0.116888E+10 | 7602.81 | 31.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_ZN_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.707898E+09 | 7796.50 | 17-JAN-06:11 | 1.30 |
February | 0.405303E+09 | 7776.62 | 21-FEB-06:11 | 1.70 |
March | 0.156353E+09 | 7552.45 | 06-MAR-06:01 | 6.70 |
April | 53314299.10 | 7418.61 | 18-APR-05:01 | 3.30 |
May | 21867937.59 | 336.63 | 25-MAY-05:35 | 8.53 |
June | 18183090.04 | 469.71 | 23-JUN-05:04 | 13.80 |
July | 10604344.74 | 472.03 | 21-JUL-05:04 | 13.40 |
August | 16332837.10 | 486.83 | 29-AUG-17:12 | 30.73 |
September | 11987838.76 | 462.58 | 14-SEP-05:04 | 12.62 |
October | 23528146.36 | 2487.06 | 30-OCT-05:03 | 7.20 |
November | 0.140482E+09 | 7554.43 | 13-NOV-06:01 | 1.70 |
December | 0.414732E+09 | 7777.29 | 26-DEC-06:11 | -1.0 |
Annual Sum or Average | 0.198059E+10 | |||
Minimum of Months | 10604344.74 | 336.63 | -1.0 | |
Maximum of Months | 0.707898E+09 | 7796.50 | 30.73 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: CORE_ZN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.966778E+09 | 1001.21 | 02-JAN-08:09 | 0.118664E+10 | 973.59 | 02-JAN-08:09 |
February | 0.874572E+09 | 1001.21 | 01-FEB-08:09 | 0.107295E+10 | 973.59 | 01-FEB-08:09 |
March | 0.105063E+10 | 1001.21 | 01-MAR-08:09 | 0.125726E+10 | 973.59 | 01-MAR-08:09 |
April | 0.922067E+09 | 1001.21 | 03-APR-07:10 | 0.113787E+10 | 973.59 | 03-APR-07:10 |
May | 0.100871E+10 | 1001.21 | 01-MAY-07:10 | 0.122195E+10 | 973.59 | 01-MAY-07:10 |
June | 0.100592E+10 | 1001.21 | 01-JUN-07:10 | 0.120670E+10 | 973.59 | 01-JUN-07:10 |
July | 0.924851E+09 | 1001.21 | 03-JUL-07:10 | 0.115223E+10 | 973.59 | 03-JUL-07:10 |
August | 0.105063E+10 | 1001.21 | 01-AUG-07:10 | 0.125726E+10 | 973.59 | 01-AUG-07:10 |
September | 0.922067E+09 | 1001.21 | 01-SEP-07:10 | 0.113608E+10 | 973.59 | 01-SEP-07:10 |
October | 0.966778E+09 | 1001.21 | 02-OCT-07:10 | 0.118754E+10 | 973.59 | 02-OCT-07:10 |
November | 0.963995E+09 | 1001.21 | 01-NOV-07:10 | 0.117228E+10 | 973.59 | 01-NOV-07:10 |
December | 0.924851E+09 | 1001.21 | 01-DEC-08:09 | 0.115133E+10 | 973.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.115819E+11 | 0.141401E+11 | ||||
Minimum of Months | 0.874572E+09 | 1001.21 | 0.107295E+10 | 973.59 | ||
Maximum of Months | 0.105063E+10 | 1001.21 | 0.125726E+10 | 973.59 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_ZN_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.658140E+09 | 758.98 | 02-JAN-08:09 | 0.899552E+09 | 738.04 | 02-JAN-08:09 |
February | 0.564928E+09 | 758.98 | 01-FEB-08:09 | 0.813362E+09 | 738.04 | 01-FEB-08:09 |
March | 0.661956E+09 | 758.98 | 03-MAR-08:09 | 0.953087E+09 | 738.04 | 01-MAR-08:09 |
April | 0.567813E+09 | 758.98 | 03-APR-07:10 | 0.862580E+09 | 738.04 | 03-APR-07:10 |
May | 0.615231E+09 | 698.29 | 01-MAY-07:10 | 0.926320E+09 | 738.04 | 01-MAY-07:10 |
June | 0.609145E+09 | 698.29 | 16-JUN-07:10 | 0.914754E+09 | 738.04 | 01-JUN-07:10 |
July | 0.567915E+09 | 758.98 | 12-JUL-07:10 | 0.873466E+09 | 738.04 | 03-JUL-07:10 |
August | 0.642395E+09 | 758.98 | 02-AUG-07:19 | 0.953087E+09 | 738.04 | 01-AUG-07:10 |
September | 0.574634E+09 | 758.98 | 05-SEP-07:10 | 0.861220E+09 | 738.04 | 01-SEP-07:10 |
October | 0.620208E+09 | 758.98 | 10-OCT-07:10 | 0.900233E+09 | 738.04 | 02-OCT-07:10 |
November | 0.651093E+09 | 758.98 | 01-NOV-07:10 | 0.888667E+09 | 738.04 | 01-NOV-07:10 |
December | 0.636604E+09 | 758.98 | 01-DEC-08:09 | 0.872785E+09 | 738.04 | 01-DEC-08:09 |
Annual Sum or Average | 0.737006E+10 | 0.107191E+11 | ||||
Minimum of Months | 0.564928E+09 | 698.29 | 0.813362E+09 | 738.04 | ||
Maximum of Months | 0.661956E+09 | 758.98 | 0.953087E+09 | 738.04 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_ZN_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.406541E+09 | 450.24 | 02-JAN-08:09 | 0.533626E+09 | 437.82 | 02-JAN-08:09 |
February | 0.353840E+09 | 450.24 | 01-FEB-08:09 | 0.482497E+09 | 437.82 | 01-FEB-08:09 |
March | 0.410738E+09 | 450.24 | 01-MAR-16:30 | 0.565383E+09 | 437.82 | 01-MAR-08:09 |
April | 0.348905E+09 | 450.24 | 03-APR-07:10 | 0.511694E+09 | 437.82 | 03-APR-07:10 |
May | 0.374778E+09 | 414.23 | 01-MAY-14:30 | 0.549505E+09 | 437.82 | 01-MAY-07:10 |
June | 0.374453E+09 | 414.23 | 08-JUN-15:20 | 0.542644E+09 | 437.82 | 01-JUN-07:10 |
July | 0.346505E+09 | 450.24 | 12-JUL-08:30 | 0.518151E+09 | 437.82 | 03-JUL-07:10 |
August | 0.396832E+09 | 450.24 | 02-AUG-07:30 | 0.565383E+09 | 437.82 | 01-AUG-07:10 |
September | 0.355941E+09 | 450.24 | 05-SEP-07:10 | 0.510887E+09 | 437.82 | 01-SEP-07:10 |
October | 0.387089E+09 | 450.24 | 03-OCT-15:39 | 0.534030E+09 | 437.82 | 02-OCT-07:10 |
November | 0.402183E+09 | 450.24 | 01-NOV-07:10 | 0.527169E+09 | 437.82 | 01-NOV-07:10 |
December | 0.391529E+09 | 450.24 | 01-DEC-08:09 | 0.517747E+09 | 437.82 | 01-DEC-08:09 |
Annual Sum or Average | 0.454933E+10 | 0.635872E+10 | ||||
Minimum of Months | 0.346505E+09 | 414.23 | 0.482497E+09 | 437.82 | ||
Maximum of Months | 0.410738E+09 | 450.24 | 0.565383E+09 | 437.82 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_ZN_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.714587E+09 | 758.98 | 02-JAN-08:09 | 0.899552E+09 | 738.04 | 02-JAN-08:09 |
February | 0.634109E+09 | 758.98 | 01-FEB-08:09 | 0.813362E+09 | 738.04 | 01-FEB-08:09 |
March | 0.732849E+09 | 758.98 | 01-MAR-16:49 | 0.953087E+09 | 738.04 | 01-MAR-08:09 |
April | 0.618023E+09 | 758.98 | 03-APR-07:10 | 0.862580E+09 | 738.04 | 03-APR-07:10 |
May | 0.642754E+09 | 698.29 | 01-MAY-07:10 | 0.926320E+09 | 738.04 | 01-MAY-07:10 |
June | 0.638976E+09 | 698.29 | 16-JUN-07:10 | 0.914754E+09 | 738.04 | 01-JUN-07:10 |
July | 0.596219E+09 | 758.98 | 12-JUL-07:10 | 0.873466E+09 | 738.04 | 03-JUL-07:10 |
August | 0.701970E+09 | 758.98 | 02-AUG-07:10 | 0.953087E+09 | 738.04 | 01-AUG-07:10 |
September | 0.633188E+09 | 758.98 | 01-SEP-07:10 | 0.861220E+09 | 738.04 | 01-SEP-07:10 |
October | 0.693056E+09 | 758.98 | 02-OCT-07:10 | 0.900233E+09 | 738.04 | 02-OCT-07:10 |
November | 0.709230E+09 | 758.98 | 01-NOV-07:10 | 0.888667E+09 | 738.04 | 01-NOV-07:10 |
December | 0.688934E+09 | 758.98 | 01-DEC-08:09 | 0.872785E+09 | 738.04 | 01-DEC-08:09 |
Annual Sum or Average | 0.800389E+10 | 0.107191E+11 | ||||
Minimum of Months | 0.596219E+09 | 698.29 | 0.813362E+09 | 738.04 | ||
Maximum of Months | 0.732849E+09 | 758.98 | 0.953087E+09 | 738.04 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_ZN_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.406194E+09 | 450.24 | 02-JAN-08:09 | 0.533626E+09 | 437.82 | 02-JAN-08:09 |
February | 0.353501E+09 | 450.24 | 01-FEB-08:09 | 0.482497E+09 | 437.82 | 01-FEB-08:09 |
March | 0.412641E+09 | 450.24 | 01-MAR-08:09 | 0.565383E+09 | 437.82 | 01-MAR-08:09 |
April | 0.351156E+09 | 450.24 | 03-APR-07:10 | 0.511694E+09 | 437.82 | 03-APR-07:10 |
May | 0.374542E+09 | 450.24 | 01-MAY-07:10 | 0.549505E+09 | 437.82 | 01-MAY-07:10 |
June | 0.374427E+09 | 450.24 | 16-JUN-07:10 | 0.542644E+09 | 437.82 | 01-JUN-07:10 |
July | 0.346605E+09 | 450.24 | 11-JUL-07:10 | 0.518151E+09 | 437.82 | 03-JUL-07:10 |
August | 0.398190E+09 | 450.24 | 02-AUG-07:10 | 0.565383E+09 | 437.82 | 01-AUG-07:10 |
September | 0.355956E+09 | 450.24 | 01-SEP-07:10 | 0.510887E+09 | 437.82 | 01-SEP-07:10 |
October | 0.387603E+09 | 450.24 | 02-OCT-07:10 | 0.534030E+09 | 437.82 | 02-OCT-07:10 |
November | 0.403505E+09 | 450.24 | 01-NOV-07:10 | 0.527169E+09 | 437.82 | 01-NOV-07:10 |
December | 0.392089E+09 | 450.24 | 01-DEC-08:09 | 0.517747E+09 | 437.82 | 01-DEC-08:09 |
Annual Sum or Average | 0.455641E+10 | 0.635872E+10 | ||||
Minimum of Months | 0.346605E+09 | 450.24 | 0.482497E+09 | 437.82 | ||
Maximum of Months | 0.412641E+09 | 450.24 | 0.565383E+09 | 437.82 |
Report: SpaceGainsMonthly
For: CORE_ZN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.711734E+09 | 0.966778E+09 | 0.118664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.643949E+09 | 0.874572E+09 | 0.107295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.779518E+09 | 0.105063E+10 | 0.125726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.677841E+09 | 0.922067E+09 | 0.113787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.745626E+09 | 0.100871E+10 | 0.122195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.745626E+09 | 0.100592E+10 | 0.120670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677841E+09 | 0.924851E+09 | 0.115223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.779518E+09 | 0.105063E+10 | 0.125726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.677841E+09 | 0.922067E+09 | 0.113608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.711734E+09 | 0.966778E+09 | 0.118754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.711734E+09 | 0.963995E+09 | 0.117228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.677841E+09 | 0.924851E+09 | 0.115133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.854080E+10 | 0.115819E+11 | 0.141401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.643949E+09 | 0.874572E+09 | 0.107295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.779518E+09 | 0.105063E+10 | 0.125726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_ZN_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.539540E+09 | 0.658140E+09 | 0.899552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637371E+09 |
February | 0.488155E+09 | 0.564928E+09 | 0.813362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548119E+09 |
March | 0.590925E+09 | 0.661956E+09 | 0.953087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572137E+09 |
April | 0.513848E+09 | 0.567813E+09 | 0.862580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1832351.08 | 0.449871E+09 |
May | 0.565233E+09 | 0.615231E+09 | 0.926320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 256157.67 | 0.401337E+09 |
June | 0.565233E+09 | 0.609145E+09 | 0.914754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1919427.60 | 0.316987E+09 |
July | 0.513848E+09 | 0.567915E+09 | 0.873466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10956026.34 | 0.219406E+09 |
August | 0.590925E+09 | 0.642395E+09 | 0.953087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29727958.18 | 0.210943E+09 |
September | 0.513848E+09 | 0.574634E+09 | 0.861220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 486096.72 | 0.275358E+09 |
October | 0.539540E+09 | 0.620208E+09 | 0.900233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458454E+09 |
November | 0.539540E+09 | 0.651093E+09 | 0.888667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550082E+09 |
December | 0.513848E+09 | 0.636604E+09 | 0.872785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598054E+09 |
Annual Sum or Average | 0.647448E+10 | 0.737006E+10 | 0.107191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45178017.60 | 0.523812E+10 |
Minimum of Months | 0.488155E+09 | 0.564928E+09 | 0.813362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210943E+09 |
Maximum of Months | 0.590925E+09 | 0.661956E+09 | 0.953087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29727958.18 | 0.637371E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_ZN_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.234287E+09 | 0.406541E+09 | 0.533626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94346297.62 |
February | 0.211974E+09 | 0.353840E+09 | 0.482497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83533216.04 |
March | 0.256600E+09 | 0.410738E+09 | 0.565383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83309396.27 |
April | 0.223130E+09 | 0.348905E+09 | 0.511694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 251582.31 | 80620866.89 |
May | 0.245443E+09 | 0.374778E+09 | 0.549505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6737.02 | 70043992.17 |
June | 0.245443E+09 | 0.374453E+09 | 0.542644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44693.34 | 59969488.73 |
July | 0.223130E+09 | 0.346505E+09 | 0.518151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 336409.15 | 49529927.89 |
August | 0.256600E+09 | 0.396832E+09 | 0.565383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 917250.41 | 43970452.85 |
September | 0.223130E+09 | 0.355941E+09 | 0.510887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6232.45 | 33502299.13 |
October | 0.234287E+09 | 0.387089E+09 | 0.534030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75546843.16 |
November | 0.234287E+09 | 0.402183E+09 | 0.527169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80286142.54 |
December | 0.223130E+09 | 0.391529E+09 | 0.517747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81610752.94 |
Annual Sum or Average | 0.281144E+10 | 0.454933E+10 | 0.635872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1562904.68 | 0.836270E+09 |
Minimum of Months | 0.211974E+09 | 0.346505E+09 | 0.482497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33502299.13 |
Maximum of Months | 0.256600E+09 | 0.410738E+09 | 0.565383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 917250.41 | 94346297.62 |
Report: SpaceGainsMonthly
For: PERIMETER_ZN_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.539540E+09 | 0.714587E+09 | 0.899552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141470E+09 |
February | 0.488155E+09 | 0.634109E+09 | 0.813362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123955E+09 |
March | 0.590925E+09 | 0.732849E+09 | 0.953087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121654E+09 |
April | 0.513848E+09 | 0.618023E+09 | 0.862580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 496027.28 | 0.115857E+09 |
May | 0.565233E+09 | 0.642754E+09 | 0.926320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10105.10 | 0.101724E+09 |
June | 0.565233E+09 | 0.638976E+09 | 0.914754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68032.84 | 86257314.11 |
July | 0.513848E+09 | 0.596219E+09 | 0.873466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 918460.60 | 72020826.66 |
August | 0.590925E+09 | 0.701970E+09 | 0.953087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1561358.59 | 62535047.21 |
September | 0.513848E+09 | 0.633188E+09 | 0.861220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9369.04 | 48096478.55 |
October | 0.539540E+09 | 0.693056E+09 | 0.900233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109674E+09 |
November | 0.539540E+09 | 0.709230E+09 | 0.888667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119412E+09 |
December | 0.513848E+09 | 0.688934E+09 | 0.872785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122019E+09 |
Annual Sum or Average | 0.647448E+10 | 0.800389E+10 | 0.107191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3063353.44 | 0.122467E+10 |
Minimum of Months | 0.488155E+09 | 0.596219E+09 | 0.813362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48096478.55 |
Maximum of Months | 0.590925E+09 | 0.732849E+09 | 0.953087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1561358.59 | 0.141470E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_ZN_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.320062E+09 | 0.406194E+09 | 0.533626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94711980.10 |
February | 0.289580E+09 | 0.353501E+09 | 0.482497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84034809.17 |
March | 0.350544E+09 | 0.412641E+09 | 0.565383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84485686.43 |
April | 0.304821E+09 | 0.351156E+09 | 0.511694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 176658.99 | 81238337.46 |
May | 0.335303E+09 | 0.374542E+09 | 0.549505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6734.66 | 72626792.94 |
June | 0.335303E+09 | 0.374427E+09 | 0.542644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43988.11 | 60988061.56 |
July | 0.304821E+09 | 0.346605E+09 | 0.518151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 314796.50 | 53958581.78 |
August | 0.350544E+09 | 0.398190E+09 | 0.565383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 836036.72 | 46404955.97 |
September | 0.304821E+09 | 0.355956E+09 | 0.510887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6212.17 | 34990941.35 |
October | 0.320062E+09 | 0.387603E+09 | 0.534030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76736238.97 |
November | 0.320062E+09 | 0.403505E+09 | 0.527169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81050694.02 |
December | 0.304821E+09 | 0.392089E+09 | 0.517747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82011007.67 |
Annual Sum or Average | 0.384075E+10 | 0.455641E+10 | 0.635872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1384427.15 | 0.853238E+09 |
Minimum of Months | 0.289580E+09 | 0.346605E+09 | 0.482497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34990941.35 |
Maximum of Months | 0.350544E+09 | 0.412641E+09 | 0.565383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 836036.72 | 94711980.10 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930884E+09 | 0.706517E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822748E+09 | 0.126346E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788218E+09 | 0.219327E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628983E+09 | 0.337537E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585621E+09 | 0.449831E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533316E+09 | 0.455246E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581002E+09 | 0.483712E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677387E+09 | 0.376121E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889480E+09 | 0.291400E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864997E+09 | 0.165881E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829700E+09 | 0.861984E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110740E+10 | 0.574238E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923973E+10 | 0.311967E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533316E+09 | 0.574238E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110740E+10 | 0.483712E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_ZN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 966.54 | 02-JAN-08:09 | 1001.21 | 02-JAN-08:09 | 973.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 966.54 | 01-FEB-08:09 | 1001.21 | 01-FEB-08:09 | 973.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 966.54 | 01-MAR-08:09 | 1001.21 | 01-MAR-08:09 | 973.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 966.54 | 03-APR-07:10 | 1001.21 | 03-APR-07:10 | 973.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 966.54 | 01-MAY-07:10 | 1001.21 | 01-MAY-07:10 | 973.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 966.54 | 01-JUN-07:10 | 1001.21 | 01-JUN-07:10 | 973.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 966.54 | 03-JUL-07:10 | 1001.21 | 03-JUL-07:10 | 973.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 966.54 | 01-AUG-07:10 | 1001.21 | 01-AUG-07:10 | 973.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 966.54 | 01-SEP-07:10 | 1001.21 | 01-SEP-07:10 | 973.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 966.54 | 02-OCT-07:10 | 1001.21 | 02-OCT-07:10 | 973.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 966.54 | 01-NOV-07:10 | 1001.21 | 01-NOV-07:10 | 973.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 966.54 | 01-DEC-08:09 | 1001.21 | 01-DEC-08:09 | 973.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 966.54 | 1001.21 | 973.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 966.54 | 1001.21 | 973.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_ZN_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 732.70 | 02-JAN-08:09 | 758.98 | 02-JAN-08:09 | 738.04 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2383.38 | 06-JAN-08:00 |
February | 732.70 | 01-FEB-08:09 | 758.98 | 01-FEB-08:09 | 738.04 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2213.43 | 09-FEB-08:00 |
March | 732.70 | 01-MAR-08:09 | 758.98 | 03-MAR-08:09 | 738.04 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2121.69 | 01-MAR-07:05 |
April | 732.70 | 03-APR-07:10 | 758.98 | 03-APR-07:10 | 738.04 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.55 | 27-APR-16:10 | 1854.45 | 19-APR-06:10 |
May | 732.70 | 01-MAY-07:10 | 698.29 | 01-MAY-07:10 | 738.04 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.61 | 05-MAY-16:10 | 1564.45 | 11-MAY-06:03 |
June | 732.70 | 01-JUN-07:10 | 698.29 | 16-JUN-07:10 | 738.04 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.79 | 28-JUN-17:00 | 1261.27 | 15-JUN-06:03 |
July | 732.70 | 03-JUL-07:10 | 758.98 | 12-JUL-07:10 | 738.04 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 444.81 | 31-JUL-16:05 | 1103.27 | 03-JUL-06:05 |
August | 732.70 | 01-AUG-07:10 | 758.98 | 02-AUG-07:19 | 738.04 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 697.70 | 10-AUG-17:00 | 1195.64 | 01-AUG-06:03 |
September | 732.70 | 01-SEP-07:10 | 758.98 | 05-SEP-07:10 | 738.04 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.21 | 14-SEP-17:00 | 1382.48 | 27-SEP-06:03 |
October | 732.70 | 02-OCT-07:10 | 758.98 | 10-OCT-07:10 | 738.04 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1614.90 | 13-OCT-06:03 |
November | 732.70 | 01-NOV-07:10 | 758.98 | 01-NOV-07:10 | 738.04 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2027.56 | 13-NOV-08:00 |
December | 732.70 | 01-DEC-08:09 | 758.98 | 01-DEC-08:09 | 738.04 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2290.76 | 26-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 732.70 | 698.29 | 738.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1103.27 | |||||
Maximum of Months | 732.70 | 758.98 | 738.04 | 0.00 | 0.00 | 0.00 | 0.00 | 697.70 | 2383.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_ZN_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 434.65 | 02-JAN-08:09 | 450.24 | 02-JAN-08:09 | 437.82 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 139.40 | 12-JAN-24:00 |
February | 434.65 | 01-FEB-08:09 | 450.24 | 01-FEB-08:09 | 437.82 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 128.18 | 16-FEB-04:00 |
March | 434.65 | 01-MAR-08:09 | 450.24 | 01-MAR-16:30 | 437.82 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 127.70 | 29-MAR-05:04 |
April | 434.65 | 03-APR-07:10 | 450.24 | 03-APR-07:10 | 437.82 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.86 | 01-APR-17:03 | 135.33 | 07-APR-24:00 |
May | 434.65 | 01-MAY-07:10 | 414.23 | 01-MAY-14:30 | 437.82 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 05-MAY-16:00 | 133.78 | 17-MAY-18:55 |
June | 434.65 | 01-JUN-07:10 | 414.23 | 08-JUN-15:20 | 437.82 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28-JUN-15:57 | 141.53 | 13-JUN-03:00 |
July | 434.65 | 03-JUL-07:10 | 450.24 | 12-JUL-08:30 | 437.82 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 24-JUL-18:10 | 68.26 | 02-JUL-04:00 |
August | 434.65 | 01-AUG-07:10 | 450.24 | 02-AUG-07:30 | 437.82 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 | 29-AUG-18:10 | 105.87 | 11-AUG-04:00 |
September | 434.65 | 01-SEP-07:10 | 450.24 | 05-SEP-07:10 | 437.82 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 14-SEP-17:00 | 64.26 | 18-SEP-23:20 |
October | 434.65 | 02-OCT-07:10 | 450.24 | 03-OCT-15:39 | 437.82 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 129.30 | 31-OCT-20:00 |
November | 434.65 | 01-NOV-07:10 | 450.24 | 01-NOV-07:10 | 437.82 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 149.81 | 29-NOV-21:00 |
December | 434.65 | 01-DEC-08:09 | 450.24 | 01-DEC-08:09 | 437.82 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 131.32 | 26-DEC-19:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 434.65 | 414.23 | 437.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.26 | |||||
Maximum of Months | 434.65 | 450.24 | 437.82 | 0.00 | 0.00 | 0.00 | 0.00 | 27.86 | 149.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_ZN_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 732.70 | 02-JAN-08:09 | 758.98 | 02-JAN-08:09 | 738.04 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 210.12 | 12-JAN-24:00 |
February | 732.70 | 01-FEB-08:09 | 758.98 | 01-FEB-08:09 | 738.04 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 193.75 | 16-FEB-04:00 |
March | 732.70 | 01-MAR-08:09 | 758.98 | 01-MAR-16:49 | 738.04 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 192.82 | 29-MAR-05:04 |
April | 732.70 | 03-APR-07:10 | 758.98 | 03-APR-07:10 | 738.04 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.32 | 01-APR-17:03 | 194.41 | 07-APR-24:00 |
May | 732.70 | 01-MAY-07:10 | 698.29 | 01-MAY-07:10 | 738.04 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 05-MAY-16:00 | 199.86 | 17-MAY-18:55 |
June | 732.70 | 01-JUN-07:10 | 698.29 | 16-JUN-07:10 | 738.04 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 | 28-JUN-15:57 | 207.88 | 13-JUN-03:00 |
July | 732.70 | 03-JUL-07:10 | 758.98 | 12-JUL-07:10 | 738.04 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.21 | 23-JUL-14:00 | 102.22 | 02-JUL-04:00 |
August | 732.70 | 01-AUG-07:10 | 758.98 | 02-AUG-07:10 | 738.04 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.15 | 29-AUG-18:10 | 155.24 | 11-AUG-04:00 |
September | 732.70 | 01-SEP-07:10 | 758.98 | 01-SEP-07:10 | 738.04 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 | 14-SEP-17:00 | 96.14 | 18-SEP-23:20 |
October | 732.70 | 02-OCT-07:10 | 758.98 | 02-OCT-07:10 | 738.04 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 192.39 | 31-OCT-20:00 |
November | 732.70 | 01-NOV-07:10 | 758.98 | 01-NOV-07:10 | 738.04 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 225.85 | 29-NOV-21:00 |
December | 732.70 | 01-DEC-08:09 | 758.98 | 01-DEC-08:09 | 738.04 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 197.18 | 26-DEC-19:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 732.70 | 698.29 | 738.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.14 | |||||
Maximum of Months | 732.70 | 758.98 | 738.04 | 0.00 | 0.00 | 0.00 | 0.00 | 49.32 | 225.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_ZN_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 434.65 | 02-JAN-08:09 | 450.24 | 02-JAN-08:09 | 437.82 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 139.86 | 12-JAN-24:00 |
February | 434.65 | 01-FEB-08:09 | 450.24 | 01-FEB-08:09 | 437.82 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 129.68 | 16-FEB-06:03 |
March | 434.65 | 01-MAR-08:09 | 450.24 | 01-MAR-08:09 | 437.82 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 128.69 | 29-MAR-05:04 |
April | 434.65 | 03-APR-07:10 | 450.24 | 03-APR-07:10 | 437.82 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 01-APR-17:03 | 131.03 | 07-APR-24:00 |
May | 434.65 | 01-MAY-07:10 | 450.24 | 01-MAY-07:10 | 437.82 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 05-MAY-16:00 | 135.76 | 17-MAY-18:55 |
June | 434.65 | 01-JUN-07:10 | 450.24 | 16-JUN-07:10 | 437.82 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28-JUN-15:57 | 137.89 | 13-JUN-03:00 |
July | 434.65 | 03-JUL-07:10 | 450.24 | 11-JUL-07:10 | 437.82 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 | 23-JUL-14:00 | 70.80 | 02-JUL-04:00 |
August | 434.65 | 01-AUG-07:10 | 450.24 | 02-AUG-07:10 | 437.82 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | 29-AUG-18:10 | 111.45 | 11-AUG-04:00 |
September | 434.65 | 01-SEP-07:10 | 450.24 | 01-SEP-07:10 | 437.82 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 14-SEP-17:00 | 66.55 | 30-SEP-06:00 |
October | 434.65 | 02-OCT-07:10 | 450.24 | 02-OCT-07:10 | 437.82 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 130.99 | 31-OCT-20:00 |
November | 434.65 | 01-NOV-07:10 | 450.24 | 01-NOV-07:10 | 437.82 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 149.95 | 29-NOV-21:00 |
December | 434.65 | 01-DEC-08:09 | 450.24 | 01-DEC-08:09 | 437.82 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 131.33 | 26-DEC-19:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 434.65 | 450.24 | 437.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.55 | |||||
Maximum of Months | 434.65 | 450.24 | 437.82 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 149.95 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1270.65 | 09-JAN-03:00 | 2729.67 | 20-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1584.56 | 27-FEB-03:55 | 3638.78 | 08-FEB-13:30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1442.80 | 01-MAR-21:00 | 5370.92 | 14-MAR-13:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1254.46 | 27-APR-05:45 | 6115.68 | 18-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1249.35 | 15-MAY-03:00 | 7256.35 | 31-MAY-13:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1229.38 | 10-JUN-02:00 | 6461.47 | 22-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1333.49 | 08-JUL-03:00 | 6568.63 | 13-JUL-13:30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1314.58 | 09-AUG-05:35 | 6008.86 | 06-AUG-12:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.03 | 10-SEP-05:00 | 5580.67 | 07-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1312.84 | 04-OCT-22:00 | 4069.53 | 11-OCT-12:20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1405.04 | 11-NOV-24:00 | 2943.49 | 04-NOV-13:20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1737.41 | 06-DEC-04:00 | 2242.30 | 06-DEC-12:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1229.38 | 2242.30 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1737.41 | 7256.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_ZN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1338.57 | 06-JAN-11:00 | 2899.62 | 3003.64 | 2920.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1362.48 | 09-FEB-08:70 | 966.54 | 1001.21 | 973.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1321.41 | 01-MAR-07:13 | 608.92 | 1401.67 | 1460.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3976.47 | 28-APR-05:03 | 425.28 | 128.87 | 1947.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4604.22 | 15-MAY-05:03 | 318.96 | 96.65 | 1460.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4687.95 | 12-JUN-05:02 | 531.60 | 161.09 | 2433.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4480.60 | 19-JUL-05:02 | 531.60 | 161.09 | 2433.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4451.69 | 14-AUG-05:01 | 850.55 | 257.74 | 3894.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4501.63 | 11-SEP-05:01 | 744.23 | 225.53 | 3407.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4686.16 | 05-OCT-05:03 | 425.28 | 128.87 | 1947.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1577.41 | 08-NOV-16:10 | 1933.08 | 2002.42 | 1947.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1316.73 | 06-DEC-16:57 | 2899.62 | 3003.64 | 2920.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1316.73 | 318.96 | 96.65 | 973.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4687.95 | 2899.62 | 3003.64 | 3894.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_ZN_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 771.00 | 06-JAN-11:27 | 2198.10 | 1661.95 | 2214.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.36 |
February | 1424.58 | 27-FEB-15:10 | 732.70 | 553.98 | 738.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.49 |
March | 2021.73 | 02-MAR-14:30 | 1465.40 | 1107.96 | 1476.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.70 |
April | 3398.96 | 27-APR-14:20 | 732.70 | 553.98 | 738.04 | 0.00 | 0.00 | 0.00 | 0.00 | 32.87 | 0.00 |
May | 2753.92 | 15-MAY-14:00 | 732.70 | 553.98 | 738.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 |
June | 2877.09 | 29-JUN-05:02 | 402.98 | 122.12 | 1845.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.86 |
July | 6347.44 | 24-JUL-05:01 | 564.18 | 170.96 | 2583.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.43 |
August | 6276.01 | 14-AUG-05:01 | 644.77 | 195.39 | 2952.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.05 |
September | 6382.09 | 11-SEP-05:01 | 564.18 | 170.96 | 2583.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.93 |
October | 4786.92 | 04-OCT-13:50 | 732.70 | 553.98 | 738.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.21 |
November | 1400.24 | 02-NOV-13:30 | 732.70 | 553.98 | 738.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.25 |
December | 1331.79 | 05-DEC-13:20 | 732.70 | 553.98 | 738.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 771.00 | 402.98 | 122.12 | 738.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6382.09 | 2198.10 | 1661.95 | 2952.17 | 0.00 | 0.00 | 0.00 | 0.00 | 32.87 | 292.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_ZN_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 332.89 | 06-JAN-16:30 | 1303.94 | 1350.72 | 1313.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 |
February | 340.96 | 09-FEB-09:58 | 1738.59 | 1314.52 | 1751.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 |
March | 412.04 | 02-MAR-08:07 | 1738.59 | 1314.52 | 1751.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 |
April | 1411.88 | 27-APR-10:02 | 1738.59 | 1314.52 | 1751.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 |
May | 1663.22 | 15-MAY-08:52 | 2173.23 | 1643.15 | 2189.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 |
June | 2010.96 | 28-JUN-08:52 | 2173.23 | 1643.15 | 2189.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
July | 3743.27 | 24-JUL-05:01 | 334.68 | 101.42 | 1532.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 |
August | 3646.77 | 14-AUG-05:01 | 382.49 | 115.91 | 1751.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 |
September | 3682.20 | 11-SEP-05:01 | 334.68 | 101.42 | 1532.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.40 |
October | 1314.53 | 04-OCT-10:02 | 1738.59 | 1314.52 | 1751.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 |
November | 342.66 | 22-NOV-09:57 | 1303.94 | 999.49 | 1313.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 |
December | 372.59 | 06-DEC-09:00 | 869.29 | 657.26 | 875.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 332.89 | 334.68 | 101.42 | 875.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 | |
Maximum of Months | 3743.27 | 2173.23 | 1643.15 | 2189.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_ZN_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 687.18 | 05-JAN-16:53 | 2930.79 | 3035.93 | 2952.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.59 |
February | 719.69 | 16-FEB-15:35 | 1465.40 | 1396.58 | 1476.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.31 |
March | 642.79 | 29-MAR-13:51 | 5861.59 | 5525.20 | 5904.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.97 |
April | 1284.21 | 27-APR-15:53 | 2930.79 | 2519.83 | 2952.17 | 0.00 | 0.00 | 0.00 | 0.00 | 4.62 | 0.00 |
May | 1588.36 | 05-MAY-15:30 | 1465.40 | 1123.24 | 1476.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 0.00 |
June | 2083.27 | 28-JUN-15:53 | 2198.10 | 1889.87 | 2214.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 | 0.00 |
July | 3965.37 | 24-JUL-05:01 | 564.18 | 170.96 | 2583.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 |
August | 3739.14 | 09-AUG-05:02 | 483.58 | 146.54 | 2214.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.73 |
September | 2533.84 | 01-SEP-05:02 | 483.58 | 146.54 | 2214.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.68 |
October | 1269.99 | 04-OCT-15:57 | 2198.10 | 2094.87 | 2214.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.02 |
November | 676.75 | 10-NOV-08:10 | 1465.40 | 1517.97 | 1476.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 |
December | 612.05 | 21-DEC-11:23 | 2198.10 | 2071.95 | 2214.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 612.05 | 483.58 | 146.54 | 1476.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3965.37 | 5861.59 | 5525.20 | 5904.34 | 0.00 | 0.00 | 0.00 | 0.00 | 4.62 | 63.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_ZN_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 296.63 | 06-JAN-16:03 | 1303.94 | 1229.11 | 1313.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 |
February | 272.12 | 09-FEB-16:43 | 1303.94 | 1201.91 | 1313.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 |
March | 653.66 | 02-MAR-16:35 | 1738.59 | 1314.52 | 1751.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 |
April | 1801.61 | 27-APR-15:55 | 1738.59 | 1314.52 | 1751.27 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 | 0.00 |
May | 2171.00 | 15-MAY-15:57 | 1303.94 | 985.89 | 1313.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 0.00 |
June | 3891.73 | 23-JUN-05:02 | 239.06 | 72.44 | 1094.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.75 |
July | 4406.93 | 24-JUL-05:01 | 334.68 | 101.42 | 1532.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 |
August | 4316.78 | 09-AUG-05:02 | 286.87 | 86.93 | 1313.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.74 |
September | 4347.14 | 11-SEP-05:01 | 334.68 | 101.42 | 1532.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 |
October | 2022.90 | 04-OCT-15:57 | 1303.94 | 985.89 | 1313.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.35 |
November | 387.49 | 08-NOV-15:50 | 869.29 | 819.40 | 875.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.19 |
December | 374.65 | 06-DEC-17:00 | 1303.94 | 1350.72 | 1313.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 272.12 | 239.06 | 72.44 | 875.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4406.93 | 1738.59 | 1350.72 | 1751.27 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 | 48.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.79 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.43 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.68 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.38 | 0.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.59 | 0.00 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 868.04 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.92 | 0.00 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 731.95 | 0.00 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.87 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1108.98 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.46 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 923.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1108.98 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.107493E+11 | 10197.17 | 23-JAN-16:49 | 0.677622E+10 | 43327.81 | 02-JAN-06:19 |
February | 0.951198E+10 | 9425.96 | 27-FEB-16:00 | 0.387133E+10 | 36469.23 | 21-FEB-06:19 |
March | 0.110021E+11 | 9635.81 | 02-MAR-16:00 | 0.138882E+10 | 18101.33 | 06-MAR-06:19 |
April | 0.984953E+10 | 11939.42 | 27-APR-15:09 | 0.464881E+09 | 9504.85 | 18-APR-06:10 |
May | 0.109447E+11 | 11496.99 | 05-MAY-14:30 | 21871725.40 | 1606.30 | 18-MAY-06:49 |
June | 0.113433E+11 | 12205.90 | 28-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.113308E+11 | 13512.56 | 31-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.131832E+11 | 13758.99 | 10-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.110718E+11 | 12626.40 | 14-SEP-15:09 | 122055.38 | 203.43 | 28-SEP-06:30 |
October | 0.108645E+11 | 11509.08 | 04-OCT-15:09 | 71193993.27 | 3835.63 | 30-OCT-05:10 |
November | 0.106078E+11 | 10541.52 | 06-NOV-16:49 | 0.151894E+10 | 17140.33 | 27-NOV-06:10 |
December | 0.104313E+11 | 10196.53 | 27-DEC-16:19 | 0.430241E+10 | 37841.34 | 26-DEC-06:19 |
Annual Sum or Average | 0.130890E+12 | 0.184158E+11 | ||||
Minimum of Months | 0.951198E+10 | 9425.96 | 0.00 | 0.00 | ||
Maximum of Months | 0.131832E+11 | 13758.99 | 0.677622E+10 | 43327.81 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.315224E+10 | 0.120973E+10 | 0.405300E+10 | 0.00 | 0.171237E+10 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621963E+09 | 0.00 |
February | 0.278095E+10 | 0.949992E+09 | 0.366466E+10 | 0.00 | 0.154202E+10 | 0.01 | 0.00 | 10888233.34 | 0.00 | 0.00 | 0.00 | 0.563472E+09 | 0.00 |
March | 0.326882E+10 | 0.861761E+09 | 0.429420E+10 | 0.00 | 0.186326E+10 | 0.00 | 0.00 | 54490626.47 | 0.00 | 0.00 | 0.00 | 0.659527E+09 | 0.00 |
April | 0.280796E+10 | 0.665175E+09 | 0.388642E+10 | 0.00 | 0.162023E+10 | 0.00 | 0.00 | 0.299252E+09 | 0.00 | 0.00 | 0.00 | 0.570492E+09 | 0.00 |
May | 0.301601E+10 | 0.568556E+09 | 0.417360E+10 | 0.00 | 0.178225E+10 | 0.00 | 0.00 | 0.805083E+09 | 0.00 | 0.00 | 0.00 | 0.599166E+09 | 0.00 |
June | 0.300292E+10 | 0.497288E+09 | 0.412149E+10 | 0.00 | 0.178225E+10 | 0.00 | 0.00 | 0.136411E+10 | 0.00 | 0.00 | 0.00 | 0.575232E+09 | 0.00 |
July | 0.278209E+10 | 0.535596E+09 | 0.393546E+10 | 0.00 | 0.162023E+10 | 0.00 | 0.00 | 0.193354E+10 | 0.00 | 0.00 | 0.00 | 0.523917E+09 | 0.00 |
August | 0.319002E+10 | 0.627856E+09 | 0.429420E+10 | 0.00 | 0.186326E+10 | 0.00 | 0.00 | 0.262599E+10 | 0.00 | 0.00 | 0.00 | 0.581915E+09 | 0.00 |
September | 0.284179E+10 | 0.753744E+09 | 0.388029E+10 | 0.00 | 0.162023E+10 | 0.00 | 0.00 | 0.145213E+10 | 0.00 | 0.00 | 0.00 | 0.523581E+09 | 0.00 |
October | 0.305473E+10 | 0.970854E+09 | 0.405607E+10 | 0.00 | 0.170124E+10 | 0.00 | 0.00 | 0.517296E+09 | 0.00 | 0.00 | 0.00 | 0.564323E+09 | 0.00 |
November | 0.313001E+10 | 0.111763E+10 | 0.400396E+10 | 0.00 | 0.170124E+10 | 0.00 | 0.00 | 72460475.21 | 0.00 | 0.00 | 0.00 | 0.582500E+09 | 0.00 |
December | 0.303401E+10 | 0.125623E+10 | 0.393240E+10 | 0.00 | 0.162111E+10 | 0.00 | 0.00 | 2717914.39 | 0.00 | 0.00 | 0.00 | 0.584788E+09 | 0.00 |
Annual Sum or Average | 0.360616E+11 | 0.100144E+11 | 0.482958E+11 | 0.00 | 0.204297E+11 | 0.03 | 0.00 | 0.913795E+10 | 0.00 | 0.00 | 0.00 | 0.695088E+10 | 0.00 |
Minimum of Months | 0.278095E+10 | 0.497288E+09 | 0.366466E+10 | 0.00 | 0.154202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523581E+09 | 0.00 |
Maximum of Months | 0.326882E+10 | 0.125623E+10 | 0.429420E+10 | 0.00 | 0.186326E+10 | 0.02 | 0.00 | 0.262599E+10 | 0.00 | 0.00 | 0.00 | 0.659527E+09 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.677622E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.387133E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.138882E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.464881E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 21871725.40 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 122055.38 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 71193993.27 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.151894E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.430241E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184158E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.677622E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3419.66 | 02-JAN-08:09 | 1061.67 | 01-JAN-06:10 | 3325.31 | 02-JAN-08:09 | 0.00 | 1731.01 | 04-JAN-06:10 | 0.00 | 02-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 3419.66 | 01-FEB-08:09 | 1061.67 | 01-FEB-06:10 | 3325.31 | 01-FEB-08:09 | 0.00 | 1731.01 | 09-FEB-06:10 | 0.00 | 01-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 3419.66 | 03-MAR-08:09 | 1061.67 | 01-MAR-06:10 | 3325.31 | 01-MAR-08:09 | 0.00 | 1731.01 | 13-MAR-05:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 3419.66 | 03-APR-07:10 | 1061.67 | 01-APR-05:10 | 3325.31 | 03-APR-07:10 | 0.00 | 1731.01 | 03-APR-05:19 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 3262.27 | 17-MAY-07:10 | 675.04 | 01-MAY-19:19 | 3325.31 | 01-MAY-07:10 | 0.00 | 1731.01 | 19-MAY-08:39 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 3257.73 | 16-JUN-07:10 | 675.04 | 01-JUN-19:00 | 3325.31 | 01-JUN-07:10 | 0.00 | 1731.01 | 26-JUN-09:39 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 |
July | 3419.66 | 12-JUL-08:30 | 675.04 | 01-JUL-20:10 | 3325.31 | 03-JUL-07:10 | 0.00 | 1731.01 | 12-JUL-13:30 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 |
August | 3419.66 | 02-AUG-07:30 | 1061.67 | 16-AUG-05:10 | 3325.31 | 01-AUG-07:10 | 0.00 | 1731.01 | 02-AUG-10:20 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 |
September | 3419.66 | 05-SEP-07:10 | 1061.67 | 01-SEP-05:10 | 3325.31 | 01-SEP-07:10 | 0.00 | 1731.01 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 3419.66 | 10-OCT-07:10 | 1061.67 | 01-OCT-05:10 | 3325.31 | 02-OCT-07:10 | 0.00 | 1731.01 | 02-OCT-05:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 3419.66 | 01-NOV-07:10 | 1061.67 | 01-NOV-05:10 | 3325.31 | 01-NOV-07:10 | 0.00 | 1731.01 | 24-NOV-06:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 3419.66 | 01-DEC-08:09 | 1061.67 | 01-DEC-06:10 | 3325.31 | 01-DEC-08:09 | 0.00 | 1731.01 | 05-DEC-06:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3257.73 | 675.04 | 3325.31 | 0.00 | 1731.01 | 0.00 | 0.00 | ||||||
Maximum of Months | 3419.66 | 1061.67 | 3325.31 | 0.00 | 1731.01 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 897.58 | 30-JAN-12:20 | 0.00 |
February | 454.77 | 27-FEB-15:39 | 0.00 | 0.00 | 0.00 | 897.70 | 13-FEB-12:30 | 0.00 |
March | 710.77 | 02-MAR-15:00 | 0.00 | 0.00 | 0.00 | 897.24 | 01-MAR-12:20 | 0.00 |
April | 3302.00 | 27-APR-15:09 | 0.00 | 0.00 | 0.00 | 895.72 | 03-APR-11:50 | 0.00 |
May | 2903.02 | 05-MAY-15:00 | 0.00 | 0.00 | 0.00 | 893.60 | 01-MAY-11:50 | 0.00 |
June | 3563.32 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 868.64 | 02-JUN-11:09 | 0.00 |
July | 4936.42 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 777.84 | 03-JUL-11:39 | 0.00 |
August | 5097.17 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | 777.10 | 31-AUG-11:00 | 0.00 |
September | 3996.88 | 14-SEP-15:30 | 0.00 | 0.00 | 0.00 | 778.20 | 29-SEP-11:00 | 0.00 |
October | 2808.31 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 891.61 | 30-OCT-11:30 | 0.00 |
November | 806.54 | 02-NOV-14:09 | 0.00 | 0.00 | 0.00 | 894.30 | 30-NOV-12:00 | 0.00 |
December | 242.62 | 05-DEC-13:20 | 0.00 | 0.00 | 0.00 | 896.27 | 27-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 777.10 | 0.00 | ||
Maximum of Months | 5097.17 | 0.00 | 0.00 | 0.00 | 897.70 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 10197.17 | 23-JAN-16:49 | 3419.66 | 3325.31 | 1061.67 | 0.00 | 1731.01 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9425.96 | 27-FEB-16:00 | 3371.48 | 3325.31 | 0.00 | 0.00 | 1731.01 | 0.00 | 0.00 | 338.81 | 0.00 |
March | 9635.81 | 02-MAR-16:00 | 3270.25 | 3325.31 | 0.00 | 0.00 | 1731.01 | 0.00 | 0.00 | 649.92 | 0.00 |
April | 11939.42 | 27-APR-15:09 | 2923.48 | 3325.31 | 0.00 | 0.00 | 1731.01 | 0.00 | 0.00 | 3302.00 | 0.00 |
May | 11496.99 | 05-MAY-14:30 | 3214.09 | 3325.31 | 0.00 | 0.00 | 1731.01 | 0.00 | 0.00 | 2789.33 | 0.00 |
June | 12205.90 | 28-JUN-15:00 | 2931.12 | 3325.31 | 0.00 | 0.00 | 1731.01 | 0.00 | 0.00 | 3563.32 | 0.00 |
July | 13512.56 | 31-JUL-15:00 | 3108.33 | 3325.31 | 0.00 | 0.00 | 1731.01 | 0.00 | 0.00 | 4802.52 | 0.00 |
August | 13758.99 | 10-AUG-15:00 | 3060.15 | 3325.31 | 0.00 | 0.00 | 1731.01 | 0.00 | 0.00 | 5097.17 | 0.00 |
September | 12626.40 | 14-SEP-15:09 | 2923.48 | 3325.31 | 0.00 | 0.00 | 1731.01 | 0.00 | 0.00 | 3991.79 | 0.00 |
October | 11509.08 | 04-OCT-15:09 | 2996.35 | 3325.31 | 0.00 | 0.00 | 1731.01 | 0.00 | 0.00 | 2801.04 | 0.00 |
November | 10541.52 | 06-NOV-16:49 | 3419.66 | 3325.31 | 1061.67 | 0.00 | 1731.01 | 0.00 | 0.00 | 378.15 | 0.00 |
December | 10196.53 | 27-DEC-16:19 | 3419.66 | 3325.31 | 1061.67 | 0.00 | 1731.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 9425.96 | 2923.48 | 3325.31 | 0.00 | 0.00 | 1731.01 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13758.99 | 3419.66 | 3325.31 | 1061.67 | 0.00 | 1731.01 | 0.00 | 0.00 | 5097.17 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 43327.81 | 02-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 36469.23 | 21-FEB-06:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 18101.33 | 06-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 9504.85 | 18-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 1606.30 | 18-MAY-06:49 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 203.43 | 28-SEP-06:30 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 3835.63 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 17140.33 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 37841.34 | 26-DEC-06:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 43327.81 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_ZN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.91 | 0.33 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
February | 0.17 | 20.44 | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.66 | 0.83 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.66 | 2.00 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.45 | 0.17 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Annual Sum or Average | 0.67 | 20.18 | 0.67 | 20.18 | 3.00 | 23.27 | 3.00 | 23.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.45 | 0.33 | 20.45 | 2.00 | 24.66 | 2.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_ZN_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 18.27 | 0.83 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
February | 0.17 | 20.12 | 0.17 | 20.12 | 0.00 | 20.12 | 0.00 | 20.12 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.13 | 0.33 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 |
Annual Sum or Average | 1.83 | 18.78 | 1.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.13 | 0.83 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_ZN_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 17.16 | 1.00 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
February | 0.83 | 19.23 | 0.67 | 19.70 | 0.00 | 19.70 | 0.00 | 19.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 19.25 | 0.67 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
Annual Sum or Average | 4.00 | 18.03 | 2.33 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.25 | 1.00 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_ZN_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 18.11 | 2.50 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
February | 2.00 | 17.44 | 1.00 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 |
March | 0.17 | 20.30 | 0.17 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.50 | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
December | 1.33 | 19.48 | 1.17 | 19.77 | 0.00 | 19.77 | 0.00 | 19.77 |
Annual Sum or Average | 7.67 | 18.27 | 5.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 20.50 | 2.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_ZN_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 16.83 | 0.83 | 17.71 | 0.00 | 17.71 | 0.00 | 17.71 |
February | 0.50 | 18.43 | 0.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 16.73 | 0.33 | 17.61 | 0.00 | 17.61 | 0.00 | 17.61 |
Annual Sum or Average | 3.83 | 17.01 | 1.50 | 17.91 | 0.00 | 17.91 | 0.00 | 17.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 18.43 | 0.83 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_ZN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 21.34 | 74.33 | 21.24 | 74.33 | 21.17 |
February | 323.00 | 21.85 | 25.67 | 21.77 | 25.67 | 21.71 |
March | 391.00 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
April | 290.17 | 23.45 | 13.33 | 23.52 | 0.00 | 23.52 |
May | 86.33 | 23.81 | 67.17 | 24.31 | 0.00 | 24.31 |
June | 14.17 | 23.88 | 145.33 | 24.83 | 0.00 | 24.83 |
July | 0.00 | 0.00 | 237.33 | 24.69 | 0.00 | 24.69 |
August | 0.00 | 0.00 | 332.83 | 24.58 | 0.00 | 24.58 |
September | 7.33 | 23.84 | 173.33 | 24.64 | 0.00 | 24.64 |
October | 196.33 | 23.71 | 17.17 | 23.82 | 0.00 | 23.82 |
November | 332.67 | 22.66 | 0.67 | 22.66 | 0.67 | 22.66 |
December | 340.00 | 21.69 | 18.83 | 21.65 | 18.83 | 21.61 |
Annual Sum or Average | 2338.00 | 22.50 | 1106.00 | 23.07 | 119.50 | 23.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.24 | 0.00 | 21.17 |
Maximum of Months | 391.00 | 23.88 | 332.83 | 24.83 | 74.33 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_ZN_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 20.82 | 280.33 | 20.73 | 280.33 | 20.70 |
February | 323.00 | 21.40 | 159.00 | 21.17 | 159.00 | 21.05 |
March | 388.17 | 22.08 | 59.67 | 21.93 | 59.67 | 21.81 |
April | 304.50 | 22.56 | 42.33 | 22.53 | 28.17 | 22.41 |
May | 294.33 | 23.34 | 14.50 | 23.42 | 0.00 | 23.42 |
June | 199.00 | 23.62 | 43.00 | 23.90 | 0.00 | 23.90 |
July | 59.50 | 23.70 | 157.83 | 24.52 | 0.00 | 24.52 |
August | 29.50 | 23.70 | 242.67 | 24.66 | 0.50 | 24.66 |
September | 104.33 | 23.57 | 140.00 | 24.24 | 0.00 | 24.24 |
October | 255.17 | 23.09 | 33.83 | 23.26 | 0.00 | 23.26 |
November | 355.83 | 21.87 | 90.50 | 21.64 | 90.50 | 21.48 |
December | 340.00 | 21.11 | 209.33 | 20.94 | 209.33 | 20.87 |
Annual Sum or Average | 3010.33 | 22.18 | 1473.00 | 22.29 | 827.50 | 22.04 |
Minimum of Months | 29.50 | 20.82 | 14.50 | 20.73 | 0.00 | 20.70 |
Maximum of Months | 388.17 | 23.70 | 280.33 | 24.66 | 280.33 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_ZN_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 294.00 | 20.53 | 278.33 | 20.51 | 278.33 | 20.51 |
February | 266.00 | 20.79 | 192.67 | 20.68 | 192.67 | 20.63 |
March | 322.00 | 21.49 | 120.83 | 21.30 | 120.83 | 21.19 |
April | 262.50 | 22.44 | 37.00 | 22.29 | 33.67 | 22.14 |
May | 253.50 | 23.40 | 8.17 | 23.45 | 0.00 | 23.45 |
June | 135.83 | 23.76 | 50.17 | 24.14 | 0.00 | 24.14 |
July | 39.33 | 23.89 | 120.33 | 24.72 | 0.00 | 24.72 |
August | 21.83 | 23.87 | 182.83 | 24.74 | 0.00 | 24.74 |
September | 132.50 | 23.71 | 69.17 | 24.05 | 0.00 | 24.05 |
October | 278.67 | 22.99 | 1.83 | 22.97 | 1.83 | 22.96 |
November | 294.00 | 21.51 | 134.83 | 21.24 | 134.83 | 21.10 |
December | 280.00 | 20.64 | 248.83 | 20.60 | 248.83 | 20.59 |
Annual Sum or Average | 2580.17 | 21.96 | 1445.00 | 21.93 | 1011.00 | 21.66 |
Minimum of Months | 21.83 | 20.53 | 1.83 | 20.51 | 0.00 | 20.51 |
Maximum of Months | 322.00 | 23.89 | 278.33 | 24.74 | 278.33 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_ZN_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 20.63 | 326.67 | 20.61 | 326.67 | 20.60 |
February | 323.00 | 20.80 | 241.67 | 20.71 | 241.67 | 20.68 |
March | 391.00 | 21.22 | 187.83 | 21.08 | 187.83 | 21.01 |
April | 336.50 | 22.06 | 58.33 | 21.88 | 58.33 | 21.75 |
May | 347.17 | 23.33 | 2.33 | 23.34 | 0.00 | 23.34 |
June | 232.83 | 23.74 | 26.33 | 23.90 | 0.00 | 23.90 |
July | 71.00 | 23.86 | 97.50 | 24.58 | 0.00 | 24.58 |
August | 45.17 | 23.84 | 141.00 | 24.61 | 0.00 | 24.61 |
September | 220.83 | 23.68 | 28.33 | 23.83 | 0.00 | 23.83 |
October | 357.00 | 22.77 | 2.67 | 22.76 | 2.67 | 22.74 |
November | 357.00 | 21.46 | 152.33 | 21.22 | 152.33 | 21.10 |
December | 340.00 | 20.70 | 299.83 | 20.67 | 299.83 | 20.66 |
Annual Sum or Average | 3378.50 | 21.98 | 1564.83 | 21.82 | 1269.33 | 21.58 |
Minimum of Months | 45.17 | 20.63 | 2.33 | 20.61 | 0.00 | 20.60 |
Maximum of Months | 391.00 | 23.86 | 326.67 | 24.61 | 326.67 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_ZN_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 20.67 | 317.83 | 20.63 | 317.83 | 20.62 |
February | 323.00 | 21.02 | 211.50 | 20.86 | 211.50 | 20.80 |
March | 391.00 | 21.72 | 121.33 | 21.53 | 121.33 | 21.41 |
April | 310.33 | 22.52 | 48.67 | 22.48 | 35.33 | 22.34 |
May | 278.17 | 23.56 | 39.00 | 23.79 | 0.00 | 23.79 |
June | 170.50 | 23.97 | 82.83 | 24.53 | 7.67 | 24.63 |
July | 72.50 | 25.49 | 169.50 | 25.52 | 28.67 | 25.77 |
August | 65.67 | 25.83 | 216.83 | 25.36 | 29.83 | 25.63 |
September | 128.50 | 23.81 | 97.00 | 24.40 | 0.67 | 24.41 |
October | 318.83 | 23.13 | 6.67 | 23.17 | 1.17 | 23.16 |
November | 357.00 | 21.72 | 136.50 | 21.44 | 136.50 | 21.28 |
December | 340.00 | 20.80 | 269.33 | 20.72 | 269.33 | 20.69 |
Annual Sum or Average | 3112.50 | 22.20 | 1717.00 | 22.26 | 1159.83 | 22.04 |
Minimum of Months | 65.67 | 20.67 | 6.67 | 20.63 | 0.00 | 20.62 |
Maximum of Months | 391.00 | 25.83 | 317.83 | 25.52 | 317.83 | 25.77 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_ZN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 357.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 323.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 391.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 374.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 374.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 391.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 357.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 357.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 4284.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 323.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 391.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_ZN_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 357.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 323.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 391.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 374.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 374.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 391.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 357.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 357.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 4284.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 323.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 391.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_ZN_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 294.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 266.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 322.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 280.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 308.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 308.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 280.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 322.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 280.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 294.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 294.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 280.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3528.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 266.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 322.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_ZN_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 357.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 323.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 391.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 374.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 374.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 391.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 357.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 357.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 4284.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 323.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 391.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_ZN_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 357.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 323.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 391.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 374.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 374.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 391.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 357.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 357.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 340.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 4284.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 323.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 391.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 4451820.05 | 1093119.23 | 4.50 | 3388177.90 | 1063642.16 | 0.00 | 0.11 | 28-FEB-16:55 | 0.00 | 01-FEB-00:10 | 500.71 | 28-FEB-16:55 | 380.79 | 28-FEB-17:00 | 119.99 | 28-FEB-16:55 | 122.32 | 28-FEB-16:55 | 0.00 | 01-FEB-00:10 |
March | 79028896.35 | 19230216.99 | 51.72 | 66390486.67 | 12638409.68 | 0.00 | 0.26 | 10-MAR-14:25 | 0.00 | 01-MAR-00:10 | 1225.93 | 10-MAR-14:15 | 945.47 | 10-MAR-15:17 | 294.51 | 10-MAR-14:15 | 292.38 | 10-MAR-14:15 | 0.00 | 01-MAR-00:10 |
April | 0.477673E+09 | 0.114238E+09 | 125.67 | 0.413101E+09 | 64571662.35 | 0.00 | 1.00 | 28-APR-05:03 | 0.00 | 01-APR-00:10 | 5510.10 | 28-APR-05:03 | 4516.54 | 28-APR-05:03 | 993.55 | 28-APR-05:03 | 1155.58 | 28-APR-05:03 | 0.00 | 01-APR-00:10 |
May | 0.141001E+10 | 0.331024E+09 | 245.77 | 0.118724E+10 | 0.222772E+09 | 0.00 | 1.00 | 04-MAY-05:03 | 0.00 | 01-MAY-00:10 | 5580.52 | 08-MAY-05:03 | 5249.12 | 15-MAY-05:03 | 1317.14 | 08-MAY-05:03 | 1165.17 | 08-MAY-05:03 | 0.00 | 01-MAY-00:10 |
June | 0.206563E+10 | 0.477097E+09 | 261.36 | 0.176200E+10 | 0.303623E+09 | 0.00 | 1.00 | 08-JUN-05:03 | 0.00 | 01-JUN-00:10 | 5603.55 | 13-JUN-05:03 | 5228.44 | 12-JUN-05:02 | 1451.88 | 13-JUN-05:05 | 1168.04 | 13-JUN-05:03 | 0.00 | 01-JUN-00:10 |
July | 0.257738E+10 | 0.588326E+09 | 239.75 | 0.215995E+10 | 0.417427E+09 | 0.00 | 1.00 | 03-JUL-05:03 | 0.00 | 01-JUL-00:10 | 5624.11 | 28-JUL-05:02 | 5008.85 | 19-JUL-05:02 | 1383.60 | 28-JUL-05:15 | 1199.26 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.329289E+10 | 0.755216E+09 | 275.92 | 0.271006E+10 | 0.582834E+09 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 5616.81 | 10-AUG-05:02 | 4913.00 | 14-AUG-05:01 | 1369.25 | 28-AUG-05:15 | 1183.33 | 10-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.201685E+10 | 0.462039E+09 | 237.24 | 0.163521E+10 | 0.381640E+09 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 5602.95 | 26-SEP-05:03 | 4981.18 | 11-SEP-05:01 | 1443.99 | 26-SEP-05:03 | 1167.97 | 26-SEP-05:03 | 0.00 | 01-SEP-00:10 |
October | 0.872509E+09 | 0.206595E+09 | 207.79 | 0.744466E+09 | 0.128043E+09 | 0.00 | 1.00 | 04-OCT-05:03 | 0.00 | 01-OCT-00:10 | 5461.49 | 06-OCT-05:03 | 5271.35 | 05-OCT-05:03 | 748.51 | 06-OCT-05:03 | 1148.26 | 06-OCT-05:03 | 0.00 | 01-OCT-00:10 |
November | 0.222964E+09 | 53688618.85 | 77.89 | 0.171324E+09 | 51640166.36 | 0.00 | 0.31 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 1489.86 | 03-NOV-16:00 | 1086.65 | 02-NOV-14:00 | 440.90 | 03-NOV-16:00 | 352.27 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.130194E+11 | 0.300855E+10 | 1727.60 | 0.108531E+11 | 0.216625E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.329289E+10 | 0.755216E+09 | 275.92 | 0.271006E+10 | 0.582834E+09 | 0.00 | 1.00 | 0.00 | 5624.11 | 5271.35 | 1451.88 | 1199.26 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 38943961.75 | 9457410.04 | 19.14 | 38344515.63 | 599446.12 | 0.00 | 0.27 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 1672.05 | 27-FEB-15:00 | 1672.05 | 27-FEB-15:00 | 55.36 | 28-FEB-14:40 | 399.14 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.134368E+09 | 32423772.45 | 46.49 | 0.133503E+09 | 865620.17 | 0.00 | 0.31 | 02-MAR-14:20 | 0.00 | 01-MAR-00:10 | 1875.90 | 02-MAR-14:25 | 1875.90 | 02-MAR-14:25 | 130.34 | 10-MAR-13:07 | 444.58 | 02-MAR-14:30 | 0.00 | 01-MAR-00:10 |
April | 0.378502E+09 | 91464248.28 | 82.01 | 0.364498E+09 | 14004034.21 | 0.00 | 0.65 | 27-APR-14:30 | 0.00 | 01-APR-00:10 | 4280.14 | 27-APR-14:30 | 4038.66 | 27-APR-14:30 | 440.10 | 28-APR-12:52 | 1048.08 | 27-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.675463E+09 | 0.162470E+09 | 155.83 | 0.629893E+09 | 45569296.72 | 0.00 | 0.50 | 04-MAY-14:00 | 0.00 | 01-MAY-00:10 | 3262.74 | 04-MAY-14:00 | 3197.02 | 15-MAY-14:00 | 374.93 | 05-MAY-12:53 | 781.46 | 04-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 0.109834E+10 | 0.263559E+09 | 208.24 | 0.102101E+10 | 77329850.89 | 0.00 | 0.58 | 29-JUN-05:02 | 0.00 | 01-JUN-00:10 | 3903.43 | 29-JUN-05:02 | 3578.60 | 29-JUN-05:02 | 382.56 | 12-JUN-14:50 | 884.85 | 29-JUN-05:02 | 0.00 | 01-JUN-00:10 |
July | 0.181264E+10 | 0.431953E+09 | 219.13 | 0.162865E+10 | 0.183996E+09 | 0.00 | 1.00 | 24-JUL-05:01 | 0.00 | 01-JUL-00:10 | 7312.76 | 31-JUL-05:02 | 7183.71 | 24-JUL-05:01 | 1079.85 | 26-JUL-05:02 | 1539.47 | 31-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.276094E+10 | 0.658876E+09 | 261.33 | 0.244378E+10 | 0.317162E+09 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 7379.17 | 25-AUG-05:02 | 7083.62 | 09-AUG-05:02 | 924.33 | 24-AUG-05:02 | 1549.92 | 25-AUG-05:02 | 0.00 | 01-AUG-00:10 |
September | 0.177535E+10 | 0.409705E+09 | 203.34 | 0.159464E+10 | 0.180716E+09 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 7324.51 | 15-SEP-05:02 | 7222.06 | 11-SEP-05:01 | 876.70 | 14-SEP-12:05 | 1541.38 | 15-SEP-05:02 | 0.00 | 01-SEP-00:10 |
October | 0.756652E+09 | 0.176959E+09 | 133.29 | 0.738462E+09 | 18189564.82 | 0.00 | 0.77 | 04-OCT-13:50 | 0.00 | 01-OCT-00:10 | 5094.81 | 04-OCT-13:50 | 5094.81 | 04-OCT-13:50 | 236.93 | 06-OCT-10:43 | 1122.06 | 04-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 61134930.74 | 14930971.89 | 34.17 | 56258991.78 | 4875938.95 | 0.00 | 0.23 | 02-NOV-13:30 | 0.00 | 01-NOV-00:10 | 1462.50 | 02-NOV-13:30 | 1316.57 | 02-NOV-13:30 | 145.92 | 02-NOV-13:30 | 351.03 | 02-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 11158439.86 | 2717914.39 | 5.86 | 11158439.86 | -0.0 | 0.00 | 0.17 | 05-DEC-13:20 | 0.00 | 01-DEC-00:10 | 1003.35 | 05-DEC-13:20 | 1003.35 | 05-DEC-13:20 | 0.00 | 06-DEC-14:45 | 242.62 | 05-DEC-13:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.950350E+10 | 0.225452E+10 | 1368.84 | 0.866019E+10 | 0.843308E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.276094E+10 | 0.658876E+09 | 261.33 | 0.244378E+10 | 0.317162E+09 | 0.00 | 1.00 | 0.00 | 7379.17 | 7222.06 | 1079.85 | 1549.92 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.152600E+09 | 37351939.56 | 79.06 | 0.147401E+09 | 5199457.70 | 0.00 | 0.45 | 27-APR-15:20 | 0.00 | 01-APR-00:10 | 1697.83 | 27-APR-15:20 | 1598.05 | 27-APR-15:03 | 145.28 | 28-APR-13:00 | 432.87 | 27-APR-15:20 | 0.00 | 01-APR-00:10 |
May | 0.419626E+09 | 0.101227E+09 | 183.57 | 0.396901E+09 | 22724636.24 | 0.00 | 0.47 | 15-MAY-10:10 | 0.00 | 01-MAY-00:10 | 1774.10 | 15-MAY-10:10 | 1747.58 | 15-MAY-10:06 | 175.54 | 05-MAY-16:00 | 410.18 | 15-MAY-10:10 | 0.00 | 01-MAY-00:10 |
June | 0.872038E+09 | 0.207625E+09 | 243.39 | 0.823438E+09 | 48600077.32 | 0.00 | 0.62 | 29-JUN-05:02 | 0.00 | 01-JUN-00:10 | 2430.94 | 29-JUN-05:02 | 2228.01 | 29-JUN-05:02 | 232.66 | 12-JUN-09:00 | 548.08 | 29-JUN-05:02 | 0.00 | 01-JUN-00:10 |
July | 0.118172E+10 | 0.280366E+09 | 236.00 | 0.108581E+10 | 95913570.47 | 0.00 | 1.00 | 24-JUL-05:01 | 0.00 | 01-JUL-00:10 | 4281.38 | 31-JUL-05:02 | 4226.89 | 24-JUL-05:01 | 493.55 | 26-JUL-05:02 | 901.60 | 31-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.160575E+10 | 0.383495E+09 | 272.47 | 0.144669E+10 | 0.159062E+09 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 4319.00 | 25-AUG-05:02 | 4099.10 | 14-AUG-05:01 | 558.63 | 24-AUG-05:02 | 907.59 | 25-AUG-05:02 | 0.00 | 01-AUG-00:10 |
September | 0.784849E+09 | 0.185290E+09 | 213.02 | 0.705299E+09 | 79549744.72 | 0.00 | 1.00 | 11-SEP-05:01 | 0.00 | 01-SEP-00:10 | 4244.20 | 12-SEP-05:02 | 4162.19 | 11-SEP-05:01 | 444.80 | 14-SEP-05:02 | 895.27 | 12-SEP-05:02 | 0.00 | 01-SEP-00:10 |
October | 0.194979E+09 | 46959997.32 | 104.18 | 0.190804E+09 | 4174761.46 | 0.00 | 0.38 | 04-OCT-10:02 | 0.00 | 01-OCT-00:10 | 1370.65 | 04-OCT-10:02 | 1370.65 | 04-OCT-10:02 | 93.18 | 06-OCT-09:00 | 321.79 | 04-OCT-10:10 | 0.00 | 01-OCT-00:10 |
November | 2857553.29 | 705047.90 | 5.49 | 2457136.62 | 400416.67 | 0.00 | 0.07 | 02-NOV-14:20 | 0.00 | 01-NOV-00:10 | 237.08 | 02-NOV-14:20 | 213.98 | 02-NOV-14:20 | 36.68 | 03-NOV-16:00 | 58.39 | 02-NOV-14:20 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.521442E+10 | 0.124302E+10 | 1337.18 | 0.479879E+10 | 0.415625E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.160575E+10 | 0.383495E+09 | 272.47 | 0.144669E+10 | 0.159062E+09 | 0.00 | 1.00 | 0.00 | 4319.00 | 4226.89 | 558.63 | 907.59 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 72286139.11 | 17891039.49 | 26.69 | 65668317.82 | 6617821.28 | 0.00 | 0.48 | 27-APR-15:55 | 0.00 | 01-APR-00:10 | 1928.18 | 27-APR-15:55 | 1769.68 | 27-APR-15:53 | 241.70 | 28-APR-13:04 | 487.15 | 27-APR-15:55 | 0.00 | 01-APR-00:10 |
May | 0.372544E+09 | 89637874.13 | 139.99 | 0.334544E+09 | 37999898.28 | 0.00 | 0.55 | 05-MAY-16:00 | 0.00 | 01-MAY-00:10 | 2231.00 | 05-MAY-16:00 | 1931.42 | 05-MAY-16:00 | 299.57 | 05-MAY-16:00 | 536.45 | 05-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.890938E+09 | 0.211436E+09 | 218.32 | 0.808123E+09 | 82814444.39 | 0.00 | 0.65 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 | 2646.02 | 28-JUN-16:00 | 2503.19 | 28-JUN-15:53 | 363.63 | 12-JUN-15:00 | 640.59 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.139126E+10 | 0.327068E+09 | 227.82 | 0.122483E+10 | 0.166435E+09 | 0.00 | 1.00 | 24-JUL-05:01 | 0.00 | 01-JUL-00:10 | 4481.83 | 26-JUL-05:02 | 4386.05 | 24-JUL-05:01 | 691.23 | 27-JUL-05:02 | 943.43 | 26-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.184239E+10 | 0.436790E+09 | 265.73 | 0.158748E+10 | 0.254908E+09 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 4511.04 | 25-AUG-05:02 | 4168.64 | 09-AUG-05:02 | 681.73 | 24-AUG-05:02 | 948.05 | 25-AUG-05:02 | 0.00 | 01-AUG-00:10 |
September | 0.794261E+09 | 0.187411E+09 | 187.29 | 0.671881E+09 | 0.122380E+09 | 0.00 | 0.79 | 14-SEP-05:02 | 0.00 | 01-SEP-00:10 | 3411.47 | 14-SEP-05:02 | 2931.32 | 14-SEP-05:02 | 480.15 | 14-SEP-05:02 | 745.07 | 14-SEP-05:02 | 0.00 | 01-SEP-00:10 |
October | 0.122628E+09 | 29503659.84 | 58.33 | 0.117519E+09 | 5109415.40 | 0.00 | 0.37 | 04-OCT-15:27 | 0.00 | 01-OCT-00:10 | 1406.50 | 04-OCT-15:27 | 1406.50 | 04-OCT-15:27 | 118.69 | 06-OCT-10:53 | 332.86 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.548630E+10 | 0.129974E+10 | 1124.17 | 0.481004E+10 | 0.676264E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.184239E+10 | 0.436790E+09 | 265.73 | 0.158748E+10 | 0.254908E+09 | 0.00 | 1.00 | 0.00 | 4511.04 | 4386.05 | 691.23 | 948.05 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:5 COOLING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 1368665.39 | 337704.06 | 1.96 | 1345889.05 | 22776.34 | 0.00 | 0.09 | 27-FEB-16:35 | 0.00 | 01-FEB-00:10 | 369.99 | 27-FEB-16:35 | 361.29 | 27-FEB-16:35 | 8.70 | 27-FEB-16:35 | 90.85 | 27-FEB-16:35 | 0.00 | 01-FEB-00:10 |
March | 11567851.10 | 2836637.03 | 11.53 | 11489250.68 | 78600.42 | 0.00 | 0.15 | 02-MAR-16:35 | 0.00 | 01-MAR-00:10 | 603.80 | 14-MAR-16:00 | 603.58 | 02-MAR-16:35 | 20.93 | 10-MAR-14:50 | 147.01 | 14-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.156033E+09 | 38306847.29 | 64.60 | 0.147425E+09 | 8607742.81 | 0.00 | 0.54 | 27-APR-15:53 | 0.00 | 01-APR-00:10 | 2410.87 | 27-APR-15:53 | 2249.43 | 27-APR-15:55 | 187.49 | 28-APR-13:45 | 606.25 | 27-APR-15:53 | 0.00 | 01-APR-00:10 |
May | 0.500152E+09 | 0.120725E+09 | 189.43 | 0.463106E+09 | 37045484.56 | 0.00 | 0.56 | 15-MAY-15:53 | 0.00 | 01-MAY-00:10 | 2502.68 | 15-MAY-15:57 | 2502.68 | 15-MAY-15:57 | 257.51 | 08-MAY-15:55 | 595.85 | 15-MAY-15:57 | 0.00 | 01-MAY-00:10 |
June | 0.851142E+09 | 0.204388E+09 | 237.02 | 0.789245E+09 | 61897161.45 | 0.00 | 0.97 | 23-JUN-05:02 | 0.00 | 01-JUN-00:10 | 4805.60 | 23-JUN-05:02 | 4569.73 | 23-JUN-05:02 | 305.16 | 29-JUN-05:02 | 1020.38 | 23-JUN-05:02 | 0.00 | 01-JUN-00:10 |
July | 0.127891E+10 | 0.305829E+09 | 237.30 | 0.115788E+10 | 0.121029E+09 | 0.00 | 1.00 | 20-JUL-05:02 | 0.00 | 01-JUL-00:10 | 5087.28 | 31-JUL-05:02 | 5026.03 | 24-JUL-05:01 | 627.61 | 27-JUL-05:02 | 1070.35 | 31-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.161646E+10 | 0.391609E+09 | 273.42 | 0.143438E+10 | 0.182079E+09 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 5124.10 | 25-AUG-05:02 | 4970.44 | 09-AUG-05:02 | 582.64 | 30-AUG-05:02 | 1076.07 | 25-AUG-05:02 | 0.00 | 01-AUG-00:10 |
September | 0.873262E+09 | 0.207686E+09 | 217.91 | 0.773025E+09 | 0.100237E+09 | 0.00 | 1.00 | 11-SEP-05:01 | 0.00 | 01-SEP-00:10 | 5048.43 | 13-SEP-05:02 | 4959.99 | 11-SEP-05:01 | 489.75 | 15-SEP-05:02 | 1063.95 | 13-SEP-05:02 | 0.00 | 01-SEP-00:10 |
October | 0.237879E+09 | 57278694.23 | 114.49 | 0.229005E+09 | 8873942.53 | 0.00 | 0.51 | 04-OCT-16:00 | 0.00 | 01-OCT-00:10 | 2256.92 | 04-OCT-15:57 | 2256.92 | 04-OCT-15:57 | 95.77 | 06-OCT-15:15 | 518.68 | 04-OCT-15:57 | 0.00 | 01-OCT-00:10 |
November | 12720764.56 | 3135836.56 | 21.00 | 10895264.76 | 1825499.80 | 0.00 | 0.09 | 02-NOV-14:30 | 0.00 | 01-NOV-00:10 | 396.52 | 02-NOV-14:30 | 339.93 | 02-NOV-14:25 | 69.37 | 03-NOV-16:00 | 97.19 | 02-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.553950E+10 | 0.133213E+10 | 1368.66 | 0.501780E+10 | 0.521696E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.161646E+10 | 0.391609E+09 | 273.42 | 0.143438E+10 | 0.182079E+09 | 0.00 | 1.00 | 0.00 | 5124.10 | 5026.03 | 627.61 | 1076.07 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.72 | 27.02 | 17.70 | 41.53 | 54.06 | 0.00 | 0.00 | 0.00 |
February | 68.88 | 43.32 | 25.57 | 72.81 | 49.19 | 0.00 | 0.00 | 0.00 |
March | 73.74 | 40.14 | 33.60 | 80.94 | 44.15 | 0.00 | 0.00 | 0.00 |
April | 71.48 | 30.11 | 41.37 | 81.09 | 37.20 | 0.00 | 0.00 | 0.00 |
May | 57.76 | 13.34 | 44.42 | 61.74 | 32.08 | 0.00 | 0.00 | 0.00 |
June | 49.72 | 8.06 | 41.67 | 51.74 | 25.80 | 0.00 | 0.00 | 0.00 |
July | 54.75 | 14.72 | 40.03 | 65.13 | 24.28 | 0.00 | 0.00 | 0.00 |
August | 65.95 | 28.18 | 37.78 | 85.31 | 24.49 | 0.00 | 0.00 | 0.00 |
September | 83.63 | 46.75 | 36.88 | 104.00 | 34.24 | 0.00 | 0.00 | 0.00 |
October | 77.04 | 48.27 | 28.77 | 88.26 | 43.50 | 0.00 | 0.00 | 0.00 |
November | 45.35 | 26.49 | 18.86 | 44.08 | 48.93 | 0.00 | 0.00 | 0.00 |
December | 47.74 | 31.30 | 16.44 | 48.40 | 56.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.66 | 29.72 | 31.95 | 68.70 | 39.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.72 | 8.06 | 16.44 | 41.53 | 24.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.63 | 48.27 | 44.42 | 104.00 | 56.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.72 | 27.02 | 17.70 | 41.53 | 54.06 | 0.00 | 0.00 | 0.00 |
February | 68.88 | 43.32 | 25.56 | 72.81 | 49.19 | 0.00 | 0.00 | 0.00 |
March | 73.74 | 40.14 | 33.60 | 80.94 | 44.15 | 0.00 | 0.00 | 0.00 |
April | 71.38 | 30.08 | 41.31 | 80.94 | 37.24 | 0.00 | 0.00 | 0.00 |
May | 57.68 | 13.31 | 44.37 | 61.58 | 32.08 | 0.00 | 0.00 | 0.00 |
June | 49.70 | 8.05 | 41.65 | 51.70 | 25.80 | 0.00 | 0.00 | 0.00 |
July | 54.70 | 14.69 | 40.01 | 65.01 | 24.28 | 0.00 | 0.00 | 0.00 |
August | 65.84 | 28.12 | 37.72 | 85.06 | 24.49 | 0.00 | 0.00 | 0.00 |
September | 83.57 | 46.73 | 36.84 | 103.92 | 34.26 | 0.00 | 0.00 | 0.00 |
October | 77.04 | 48.27 | 28.77 | 88.25 | 43.50 | 0.00 | 0.00 | 0.00 |
November | 45.35 | 26.49 | 18.86 | 44.08 | 48.93 | 0.00 | 0.00 | 0.00 |
December | 47.74 | 31.30 | 16.44 | 48.40 | 56.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.63 | 29.70 | 31.92 | 68.64 | 39.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.72 | 8.05 | 16.44 | 41.53 | 24.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.57 | 48.27 | 44.37 | 103.92 | 56.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.72 | 27.02 | 17.70 | 41.53 | 54.06 | 0.00 | 0.00 | 0.00 |
February | 68.88 | 43.32 | 25.56 | 72.81 | 49.19 | 0.00 | 0.00 | 0.00 |
March | 73.74 | 40.14 | 33.60 | 80.94 | 44.15 | 0.00 | 0.00 | 0.00 |
April | 71.38 | 30.08 | 41.30 | 80.94 | 37.24 | 0.00 | 0.00 | 0.00 |
May | 57.68 | 13.31 | 44.37 | 61.58 | 32.08 | 0.00 | 0.00 | 0.00 |
June | 49.70 | 8.05 | 41.65 | 51.70 | 25.80 | 0.00 | 0.00 | 0.00 |
July | 54.70 | 14.69 | 40.01 | 65.01 | 24.28 | 0.00 | 0.00 | 0.00 |
August | 65.84 | 28.12 | 37.72 | 85.06 | 24.49 | 0.00 | 0.00 | 0.00 |
September | 83.57 | 46.73 | 36.84 | 103.91 | 34.26 | 0.00 | 0.00 | 0.00 |
October | 77.04 | 48.27 | 28.77 | 88.25 | 43.50 | 0.00 | 0.00 | 0.00 |
November | 45.35 | 26.49 | 18.86 | 44.08 | 48.93 | 0.00 | 0.00 | 0.00 |
December | 47.74 | 31.30 | 16.44 | 48.40 | 56.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.63 | 29.70 | 31.92 | 68.64 | 39.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.72 | 8.05 | 16.44 | 41.53 | 24.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.57 | 48.27 | 44.37 | 103.91 | 56.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.72 | 27.02 | 17.70 | 41.53 | 54.06 | 0.00 | 0.00 | 0.00 |
February | 68.88 | 43.32 | 25.56 | 72.81 | 49.19 | 0.00 | 0.00 | 0.00 |
March | 73.74 | 40.14 | 33.60 | 80.94 | 44.15 | 0.00 | 0.00 | 0.00 |
April | 71.38 | 30.08 | 41.30 | 80.94 | 37.24 | 0.00 | 0.00 | 0.00 |
May | 57.68 | 13.31 | 44.37 | 61.58 | 32.08 | 0.00 | 0.00 | 0.00 |
June | 49.70 | 8.05 | 41.65 | 51.70 | 25.80 | 0.00 | 0.00 | 0.00 |
July | 54.70 | 14.69 | 40.01 | 65.01 | 24.28 | 0.00 | 0.00 | 0.00 |
August | 65.84 | 28.12 | 37.72 | 85.06 | 24.49 | 0.00 | 0.00 | 0.00 |
September | 83.57 | 46.73 | 36.84 | 103.91 | 34.26 | 0.00 | 0.00 | 0.00 |
October | 77.04 | 48.27 | 28.77 | 88.25 | 43.50 | 0.00 | 0.00 | 0.00 |
November | 45.35 | 26.49 | 18.86 | 44.08 | 48.93 | 0.00 | 0.00 | 0.00 |
December | 47.74 | 31.30 | 16.44 | 48.40 | 56.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.63 | 29.70 | 31.92 | 68.64 | 39.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.72 | 8.05 | 16.44 | 41.53 | 24.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.57 | 48.27 | 44.37 | 103.91 | 56.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.72 | 27.02 | 17.70 | 41.53 | 54.06 | 0.00 | 0.00 | 0.00 |
February | 68.88 | 43.32 | 25.56 | 72.81 | 49.19 | 0.00 | 0.00 | 0.00 |
March | 73.74 | 40.14 | 33.60 | 80.94 | 44.15 | 0.00 | 0.00 | 0.00 |
April | 71.38 | 30.08 | 41.31 | 80.94 | 37.24 | 0.00 | 0.00 | 0.00 |
May | 57.68 | 13.31 | 44.37 | 61.58 | 32.08 | 0.00 | 0.00 | 0.00 |
June | 49.70 | 8.05 | 41.65 | 51.70 | 25.80 | 0.00 | 0.00 | 0.00 |
July | 54.70 | 14.69 | 40.01 | 65.01 | 24.28 | 0.00 | 0.00 | 0.00 |
August | 65.84 | 28.12 | 37.72 | 85.06 | 24.49 | 0.00 | 0.00 | 0.00 |
September | 83.58 | 46.73 | 36.85 | 103.91 | 34.25 | 0.00 | 0.00 | 0.00 |
October | 77.04 | 48.27 | 28.77 | 88.25 | 43.50 | 0.00 | 0.00 | 0.00 |
November | 45.35 | 26.49 | 18.86 | 44.08 | 48.93 | 0.00 | 0.00 | 0.00 |
December | 47.74 | 31.30 | 16.44 | 48.40 | 56.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.63 | 29.70 | 31.92 | 68.64 | 39.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.72 | 8.05 | 16.44 | 41.53 | 24.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.58 | 48.27 | 44.37 | 103.91 | 56.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.72 | 27.02 | 17.70 | 41.53 | 54.06 | 0.00 | 0.00 | 0.00 |
February | 68.88 | 43.32 | 25.57 | 72.81 | 49.19 | 0.00 | 0.00 | 0.00 |
March | 73.74 | 40.14 | 33.60 | 80.94 | 44.15 | 0.00 | 0.00 | 0.00 |
April | 71.49 | 30.12 | 41.37 | 81.04 | 37.13 | 0.00 | 0.00 | 0.00 |
May | 57.74 | 13.33 | 44.41 | 61.70 | 32.07 | 0.00 | 0.00 | 0.00 |
June | 49.73 | 8.06 | 41.67 | 51.75 | 25.80 | 0.00 | 0.00 | 0.00 |
July | 54.74 | 14.71 | 40.03 | 65.10 | 24.28 | 0.00 | 0.00 | 0.00 |
August | 65.95 | 28.17 | 37.78 | 85.29 | 24.48 | 0.00 | 0.00 | 0.00 |
September | 83.62 | 46.75 | 36.87 | 103.95 | 34.20 | 0.00 | 0.00 | 0.00 |
October | 77.04 | 48.27 | 28.77 | 88.26 | 43.50 | 0.00 | 0.00 | 0.00 |
November | 45.35 | 26.49 | 18.86 | 44.08 | 48.93 | 0.00 | 0.00 | 0.00 |
December | 47.74 | 31.30 | 16.44 | 48.40 | 56.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.66 | 29.72 | 31.94 | 68.69 | 39.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.72 | 8.06 | 16.44 | 41.53 | 24.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.62 | 48.27 | 44.41 | 103.95 | 56.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_DOOR
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.20 | 37.86 | 25.34 | 58.78 | 75.16 | 0.00 | 0.00 | 0.00 |
February | 97.26 | 60.69 | 36.58 | 102.88 | 68.49 | 0.00 | 0.00 | 0.00 |
March | 104.38 | 56.24 | 48.13 | 114.55 | 61.36 | 0.00 | 0.00 | 0.00 |
April | 109.46 | 48.08 | 61.38 | 127.40 | 51.67 | 0.00 | 0.00 | 0.00 |
May | 93.42 | 26.04 | 67.38 | 105.98 | 44.61 | 0.00 | 0.00 | 0.00 |
June | 81.51 | 18.43 | 63.08 | 91.62 | 35.94 | 0.00 | 0.00 | 0.00 |
July | 90.54 | 30.25 | 60.29 | 113.57 | 33.91 | 0.00 | 0.00 | 0.00 |
August | 105.05 | 48.79 | 56.26 | 139.02 | 34.29 | 0.00 | 0.00 | 0.00 |
September | 119.84 | 66.77 | 53.07 | 149.31 | 47.82 | 0.00 | 0.00 | 0.00 |
October | 108.73 | 67.63 | 41.10 | 124.47 | 60.62 | 0.00 | 0.00 | 0.00 |
November | 64.14 | 37.11 | 27.03 | 62.39 | 68.04 | 0.00 | 0.00 | 0.00 |
December | 67.31 | 43.85 | 23.47 | 68.17 | 79.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.01 | 45.04 | 46.96 | 104.83 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.20 | 18.43 | 23.47 | 58.78 | 33.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.84 | 67.63 | 67.38 | 149.31 | 79.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.60 | 4.12 | 11.48 | 6.00 | 55.73 | 0.00 | 0.00 | 0.00 |
February | 28.76 | 10.51 | 18.25 | 20.01 | 48.27 | 0.00 | 0.00 | 0.00 |
March | 42.71 | 15.75 | 26.95 | 37.16 | 40.73 | 0.00 | 0.00 | 0.00 |
April | 66.12 | 27.83 | 38.29 | 68.88 | 33.13 | 0.00 | 0.00 | 0.00 |
May | 69.06 | 23.95 | 45.11 | 73.80 | 29.57 | 0.00 | 0.00 | 0.00 |
June | 83.19 | 36.06 | 47.13 | 94.69 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 77.47 | 34.35 | 43.12 | 91.75 | 21.68 | 0.00 | 0.00 | 0.00 |
August | 77.39 | 38.83 | 38.56 | 95.24 | 21.88 | 0.00 | 0.00 | 0.00 |
September | 57.55 | 26.87 | 30.68 | 62.78 | 31.02 | 0.00 | 0.00 | 0.00 |
October | 37.58 | 16.30 | 21.28 | 34.06 | 40.81 | 0.00 | 0.00 | 0.00 |
November | 18.24 | 5.35 | 12.90 | 9.68 | 48.67 | 0.00 | 0.00 | 0.00 |
December | 15.10 | 5.04 | 10.05 | 7.60 | 57.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.15 | 20.46 | 28.70 | 50.29 | 37.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.10 | 4.12 | 10.05 | 6.00 | 21.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.19 | 38.83 | 47.13 | 95.24 | 57.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.60 | 4.12 | 11.48 | 6.00 | 55.73 | 0.00 | 0.00 | 0.00 |
February | 28.76 | 10.51 | 18.25 | 20.01 | 48.27 | 0.00 | 0.00 | 0.00 |
March | 42.70 | 15.75 | 26.95 | 37.16 | 40.73 | 0.00 | 0.00 | 0.00 |
April | 66.12 | 27.83 | 38.29 | 68.88 | 33.13 | 0.00 | 0.00 | 0.00 |
May | 69.06 | 23.95 | 45.10 | 73.80 | 29.57 | 0.00 | 0.00 | 0.00 |
June | 83.18 | 36.06 | 47.13 | 94.68 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 77.47 | 34.35 | 43.12 | 91.75 | 21.68 | 0.00 | 0.00 | 0.00 |
August | 77.39 | 38.83 | 38.56 | 95.23 | 21.88 | 0.00 | 0.00 | 0.00 |
September | 57.55 | 26.87 | 30.68 | 62.78 | 31.02 | 0.00 | 0.00 | 0.00 |
October | 37.58 | 16.30 | 21.28 | 34.06 | 40.81 | 0.00 | 0.00 | 0.00 |
November | 18.24 | 5.35 | 12.90 | 9.68 | 48.67 | 0.00 | 0.00 | 0.00 |
December | 15.10 | 5.04 | 10.05 | 7.60 | 57.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.15 | 20.46 | 28.69 | 50.29 | 37.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.10 | 4.12 | 10.05 | 6.00 | 21.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.18 | 38.83 | 47.13 | 95.23 | 57.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.60 | 4.12 | 11.48 | 6.00 | 55.73 | 0.00 | 0.00 | 0.00 |
February | 28.76 | 10.51 | 18.25 | 20.01 | 48.27 | 0.00 | 0.00 | 0.00 |
March | 42.70 | 15.75 | 26.95 | 37.16 | 40.73 | 0.00 | 0.00 | 0.00 |
April | 66.12 | 27.83 | 38.29 | 68.88 | 33.13 | 0.00 | 0.00 | 0.00 |
May | 69.06 | 23.95 | 45.10 | 73.80 | 29.57 | 0.00 | 0.00 | 0.00 |
June | 83.18 | 36.06 | 47.13 | 94.68 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 77.47 | 34.35 | 43.12 | 91.75 | 21.68 | 0.00 | 0.00 | 0.00 |
August | 77.39 | 38.83 | 38.56 | 95.23 | 21.88 | 0.00 | 0.00 | 0.00 |
September | 57.55 | 26.87 | 30.68 | 62.78 | 31.02 | 0.00 | 0.00 | 0.00 |
October | 37.58 | 16.30 | 21.28 | 34.06 | 40.81 | 0.00 | 0.00 | 0.00 |
November | 18.24 | 5.35 | 12.90 | 9.68 | 48.67 | 0.00 | 0.00 | 0.00 |
December | 15.10 | 5.04 | 10.05 | 7.60 | 57.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.15 | 20.46 | 28.69 | 50.29 | 37.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.10 | 4.12 | 10.05 | 6.00 | 21.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.18 | 38.83 | 47.13 | 95.23 | 57.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.66 | 4.14 | 11.52 | 6.05 | 55.66 | 0.00 | 0.00 | 0.00 |
February | 28.83 | 10.54 | 18.29 | 20.10 | 48.25 | 0.00 | 0.00 | 0.00 |
March | 42.72 | 15.76 | 26.96 | 37.19 | 40.73 | 0.00 | 0.00 | 0.00 |
April | 66.12 | 27.83 | 38.29 | 68.88 | 33.13 | 0.00 | 0.00 | 0.00 |
May | 69.06 | 23.95 | 45.11 | 73.80 | 29.57 | 0.00 | 0.00 | 0.00 |
June | 83.19 | 36.06 | 47.13 | 94.69 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 77.47 | 34.35 | 43.12 | 91.75 | 21.68 | 0.00 | 0.00 | 0.00 |
August | 77.39 | 38.83 | 38.56 | 95.24 | 21.88 | 0.00 | 0.00 | 0.00 |
September | 57.56 | 26.88 | 30.68 | 62.79 | 31.02 | 0.00 | 0.00 | 0.00 |
October | 37.63 | 16.32 | 21.30 | 34.14 | 40.81 | 0.00 | 0.00 | 0.00 |
November | 18.30 | 5.37 | 12.93 | 9.76 | 48.65 | 0.00 | 0.00 | 0.00 |
December | 15.17 | 5.07 | 10.10 | 7.69 | 57.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.18 | 20.47 | 28.71 | 50.32 | 37.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.17 | 4.14 | 10.10 | 6.05 | 21.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.19 | 38.83 | 47.13 | 95.24 | 57.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.52 | 0.00 | 9.52 | 0.40 | 58.62 | 0.00 | 0.00 | 0.00 |
February | 14.93 | 0.00 | 14.93 | 3.60 | 51.04 | 0.00 | 0.00 | 0.00 |
March | 22.08 | 0.00 | 22.08 | 10.85 | 41.86 | 0.00 | 0.00 | 0.00 |
April | 31.47 | 0.12 | 31.35 | 23.01 | 33.38 | 0.00 | 0.00 | 0.00 |
May | 40.41 | 1.20 | 39.22 | 34.50 | 28.78 | 0.00 | 0.00 | 0.00 |
June | 42.68 | 2.78 | 39.90 | 39.17 | 22.87 | 0.00 | 0.00 | 0.00 |
July | 40.84 | 3.18 | 37.66 | 42.02 | 21.23 | 0.00 | 0.00 | 0.00 |
August | 33.03 | 0.90 | 32.13 | 34.60 | 21.26 | 0.00 | 0.00 | 0.00 |
September | 25.54 | 0.01 | 25.53 | 19.76 | 31.35 | 0.00 | 0.00 | 0.00 |
October | 17.37 | 0.00 | 17.37 | 7.87 | 41.35 | 0.00 | 0.00 | 0.00 |
November | 10.78 | 0.00 | 10.78 | 1.43 | 50.19 | 0.00 | 0.00 | 0.00 |
December | 8.13 | 0.00 | 8.13 | 0.27 | 59.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.78 | 0.69 | 24.09 | 18.21 | 38.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.13 | 0.00 | 8.13 | 0.27 | 21.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.68 | 3.18 | 39.90 | 42.02 | 59.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.52 | 0.00 | 9.52 | 0.40 | 58.62 | 0.00 | 0.00 | 0.00 |
February | 14.93 | 0.00 | 14.93 | 3.60 | 51.04 | 0.00 | 0.00 | 0.00 |
March | 22.08 | 0.00 | 22.08 | 10.85 | 41.86 | 0.00 | 0.00 | 0.00 |
April | 31.45 | 0.11 | 31.34 | 23.01 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 40.35 | 1.18 | 39.17 | 34.42 | 28.81 | 0.00 | 0.00 | 0.00 |
June | 42.58 | 2.74 | 39.84 | 38.97 | 22.88 | 0.00 | 0.00 | 0.00 |
July | 40.76 | 3.14 | 37.62 | 41.86 | 21.24 | 0.00 | 0.00 | 0.00 |
August | 32.96 | 0.88 | 32.08 | 34.52 | 21.31 | 0.00 | 0.00 | 0.00 |
September | 25.54 | 0.01 | 25.53 | 19.76 | 31.35 | 0.00 | 0.00 | 0.00 |
October | 17.37 | 0.00 | 17.37 | 7.87 | 41.35 | 0.00 | 0.00 | 0.00 |
November | 10.78 | 0.00 | 10.78 | 1.43 | 50.19 | 0.00 | 0.00 | 0.00 |
December | 8.13 | 0.00 | 8.13 | 0.27 | 59.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.75 | 0.68 | 24.08 | 18.17 | 38.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.13 | 0.00 | 8.13 | 0.27 | 21.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.58 | 3.14 | 39.84 | 41.86 | 59.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.52 | 0.00 | 9.52 | 0.40 | 58.62 | 0.00 | 0.00 | 0.00 |
February | 14.93 | 0.00 | 14.93 | 3.60 | 51.04 | 0.00 | 0.00 | 0.00 |
March | 22.08 | 0.00 | 22.08 | 10.85 | 41.86 | 0.00 | 0.00 | 0.00 |
April | 31.44 | 0.11 | 31.33 | 23.01 | 33.42 | 0.00 | 0.00 | 0.00 |
May | 40.35 | 1.18 | 39.17 | 34.42 | 28.81 | 0.00 | 0.00 | 0.00 |
June | 42.58 | 2.74 | 39.84 | 38.97 | 22.88 | 0.00 | 0.00 | 0.00 |
July | 40.76 | 3.14 | 37.62 | 41.86 | 21.24 | 0.00 | 0.00 | 0.00 |
August | 32.96 | 0.88 | 32.08 | 34.52 | 21.32 | 0.00 | 0.00 | 0.00 |
September | 25.53 | 0.01 | 25.53 | 19.76 | 31.35 | 0.00 | 0.00 | 0.00 |
October | 17.37 | 0.00 | 17.37 | 7.87 | 41.35 | 0.00 | 0.00 | 0.00 |
November | 10.78 | 0.00 | 10.78 | 1.43 | 50.19 | 0.00 | 0.00 | 0.00 |
December | 8.13 | 0.00 | 8.13 | 0.27 | 59.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.75 | 0.68 | 24.08 | 18.17 | 38.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.13 | 0.00 | 8.13 | 0.27 | 21.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.58 | 3.14 | 39.84 | 41.86 | 59.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.52 | 0.00 | 9.52 | 0.40 | 58.62 | 0.00 | 0.00 | 0.00 |
February | 14.93 | 0.00 | 14.93 | 3.60 | 51.04 | 0.00 | 0.00 | 0.00 |
March | 22.08 | 0.00 | 22.08 | 10.85 | 41.86 | 0.00 | 0.00 | 0.00 |
April | 31.44 | 0.11 | 31.33 | 23.01 | 33.42 | 0.00 | 0.00 | 0.00 |
May | 40.35 | 1.18 | 39.17 | 34.42 | 28.81 | 0.00 | 0.00 | 0.00 |
June | 42.58 | 2.74 | 39.84 | 38.97 | 22.88 | 0.00 | 0.00 | 0.00 |
July | 40.76 | 3.14 | 37.62 | 41.86 | 21.24 | 0.00 | 0.00 | 0.00 |
August | 32.96 | 0.88 | 32.08 | 34.52 | 21.32 | 0.00 | 0.00 | 0.00 |
September | 25.54 | 0.01 | 25.53 | 19.76 | 31.35 | 0.00 | 0.00 | 0.00 |
October | 17.37 | 0.00 | 17.37 | 7.87 | 41.35 | 0.00 | 0.00 | 0.00 |
November | 10.78 | 0.00 | 10.78 | 1.43 | 50.19 | 0.00 | 0.00 | 0.00 |
December | 8.13 | 0.00 | 8.13 | 0.27 | 59.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.75 | 0.68 | 24.08 | 18.17 | 38.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.13 | 0.00 | 8.13 | 0.27 | 21.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.58 | 3.14 | 39.84 | 41.86 | 59.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.52 | 0.00 | 9.52 | 0.40 | 58.62 | 0.00 | 0.00 | 0.00 |
February | 14.93 | 0.00 | 14.93 | 3.60 | 51.04 | 0.00 | 0.00 | 0.00 |
March | 22.08 | 0.00 | 22.08 | 10.85 | 41.86 | 0.00 | 0.00 | 0.00 |
April | 31.45 | 0.11 | 31.34 | 23.02 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 40.35 | 1.18 | 39.17 | 34.42 | 28.81 | 0.00 | 0.00 | 0.00 |
June | 42.58 | 2.74 | 39.84 | 38.97 | 22.88 | 0.00 | 0.00 | 0.00 |
July | 40.76 | 3.14 | 37.62 | 41.86 | 21.24 | 0.00 | 0.00 | 0.00 |
August | 32.96 | 0.88 | 32.08 | 34.52 | 21.32 | 0.00 | 0.00 | 0.00 |
September | 25.54 | 0.01 | 25.53 | 19.76 | 31.35 | 0.00 | 0.00 | 0.00 |
October | 17.37 | 0.00 | 17.37 | 7.87 | 41.35 | 0.00 | 0.00 | 0.00 |
November | 10.78 | 0.00 | 10.78 | 1.43 | 50.19 | 0.00 | 0.00 | 0.00 |
December | 8.13 | 0.00 | 8.13 | 0.27 | 59.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.75 | 0.68 | 24.08 | 18.17 | 38.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.13 | 0.00 | 8.13 | 0.27 | 21.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.58 | 3.14 | 39.84 | 41.86 | 59.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.52 | 0.00 | 9.52 | 0.40 | 58.62 | 0.00 | 0.00 | 0.00 |
February | 14.93 | 0.00 | 14.93 | 3.60 | 51.04 | 0.00 | 0.00 | 0.00 |
March | 22.08 | 0.00 | 22.08 | 10.85 | 41.86 | 0.00 | 0.00 | 0.00 |
April | 31.47 | 0.11 | 31.35 | 23.03 | 33.39 | 0.00 | 0.00 | 0.00 |
May | 40.45 | 1.21 | 39.23 | 34.59 | 28.81 | 0.00 | 0.00 | 0.00 |
June | 42.68 | 2.77 | 39.90 | 39.16 | 22.87 | 0.00 | 0.00 | 0.00 |
July | 40.87 | 3.19 | 37.68 | 42.10 | 21.24 | 0.00 | 0.00 | 0.00 |
August | 33.03 | 0.90 | 32.12 | 34.64 | 21.31 | 0.00 | 0.00 | 0.00 |
September | 25.54 | 0.01 | 25.53 | 19.76 | 31.35 | 0.00 | 0.00 | 0.00 |
October | 17.37 | 0.00 | 17.37 | 7.87 | 41.35 | 0.00 | 0.00 | 0.00 |
November | 10.78 | 0.00 | 10.78 | 1.43 | 50.19 | 0.00 | 0.00 | 0.00 |
December | 8.13 | 0.00 | 8.13 | 0.27 | 59.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.79 | 0.69 | 24.10 | 18.23 | 38.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.13 | 0.00 | 8.13 | 0.27 | 21.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.68 | 3.19 | 39.90 | 42.10 | 59.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.56 | 5.09 | 11.47 | 7.79 | 56.33 | 0.00 | 0.00 | 0.00 |
February | 29.77 | 11.50 | 18.27 | 22.48 | 49.42 | 0.00 | 0.00 | 0.00 |
March | 41.26 | 14.20 | 27.07 | 36.13 | 42.17 | 0.00 | 0.00 | 0.00 |
April | 62.43 | 24.03 | 38.40 | 64.82 | 35.06 | 0.00 | 0.00 | 0.00 |
May | 79.81 | 32.65 | 47.16 | 88.60 | 31.56 | 0.00 | 0.00 | 0.00 |
June | 76.57 | 29.52 | 47.05 | 86.11 | 25.54 | 0.00 | 0.00 | 0.00 |
July | 95.64 | 50.35 | 45.28 | 117.53 | 24.67 | 0.00 | 0.00 | 0.00 |
August | 79.74 | 40.91 | 38.83 | 99.74 | 24.41 | 0.00 | 0.00 | 0.00 |
September | 65.41 | 31.75 | 33.67 | 75.20 | 33.31 | 0.00 | 0.00 | 0.00 |
October | 37.27 | 15.50 | 21.77 | 34.45 | 42.44 | 0.00 | 0.00 | 0.00 |
November | 18.45 | 5.42 | 13.03 | 10.39 | 49.40 | 0.00 | 0.00 | 0.00 |
December | 15.67 | 5.57 | 10.10 | 9.26 | 58.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.68 | 22.29 | 29.39 | 54.59 | 39.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.67 | 5.09 | 10.10 | 7.79 | 24.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.64 | 50.35 | 47.16 | 117.53 | 58.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.49 | 5.07 | 11.42 | 7.73 | 56.39 | 0.00 | 0.00 | 0.00 |
February | 29.72 | 11.48 | 18.24 | 22.39 | 49.43 | 0.00 | 0.00 | 0.00 |
March | 41.24 | 14.19 | 27.06 | 36.10 | 42.17 | 0.00 | 0.00 | 0.00 |
April | 62.43 | 24.03 | 38.40 | 64.82 | 35.06 | 0.00 | 0.00 | 0.00 |
May | 79.81 | 32.65 | 47.16 | 88.60 | 31.56 | 0.00 | 0.00 | 0.00 |
June | 76.57 | 29.52 | 47.05 | 86.11 | 25.54 | 0.00 | 0.00 | 0.00 |
July | 95.64 | 50.35 | 45.28 | 117.52 | 24.67 | 0.00 | 0.00 | 0.00 |
August | 79.74 | 40.91 | 38.83 | 99.74 | 24.41 | 0.00 | 0.00 | 0.00 |
September | 65.41 | 31.75 | 33.66 | 75.19 | 33.31 | 0.00 | 0.00 | 0.00 |
October | 37.23 | 15.49 | 21.74 | 34.37 | 42.44 | 0.00 | 0.00 | 0.00 |
November | 18.39 | 5.40 | 12.99 | 10.31 | 49.42 | 0.00 | 0.00 | 0.00 |
December | 15.61 | 5.55 | 10.06 | 9.18 | 58.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.66 | 22.28 | 29.38 | 54.55 | 39.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.61 | 5.07 | 10.06 | 7.73 | 24.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.64 | 50.35 | 47.16 | 117.52 | 58.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.49 | 5.07 | 11.42 | 7.73 | 56.39 | 0.00 | 0.00 | 0.00 |
February | 29.72 | 11.48 | 18.24 | 22.39 | 49.43 | 0.00 | 0.00 | 0.00 |
March | 41.24 | 14.19 | 27.06 | 36.10 | 42.17 | 0.00 | 0.00 | 0.00 |
April | 62.43 | 24.03 | 38.40 | 64.82 | 35.06 | 0.00 | 0.00 | 0.00 |
May | 79.81 | 32.65 | 47.16 | 88.60 | 31.56 | 0.00 | 0.00 | 0.00 |
June | 76.57 | 29.52 | 47.05 | 86.11 | 25.54 | 0.00 | 0.00 | 0.00 |
July | 95.64 | 50.35 | 45.28 | 117.52 | 24.67 | 0.00 | 0.00 | 0.00 |
August | 79.74 | 40.91 | 38.83 | 99.74 | 24.41 | 0.00 | 0.00 | 0.00 |
September | 65.41 | 31.75 | 33.66 | 75.19 | 33.31 | 0.00 | 0.00 | 0.00 |
October | 37.23 | 15.49 | 21.74 | 34.37 | 42.44 | 0.00 | 0.00 | 0.00 |
November | 18.39 | 5.40 | 12.99 | 10.31 | 49.42 | 0.00 | 0.00 | 0.00 |
December | 15.61 | 5.55 | 10.06 | 9.18 | 58.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.66 | 22.28 | 29.38 | 54.55 | 39.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.61 | 5.07 | 10.06 | 7.73 | 24.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.64 | 50.35 | 47.16 | 117.52 | 58.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.49 | 5.07 | 11.42 | 7.73 | 56.39 | 0.00 | 0.00 | 0.00 |
February | 29.72 | 11.48 | 18.24 | 22.39 | 49.43 | 0.00 | 0.00 | 0.00 |
March | 41.24 | 14.19 | 27.06 | 36.10 | 42.17 | 0.00 | 0.00 | 0.00 |
April | 62.43 | 24.03 | 38.40 | 64.82 | 35.06 | 0.00 | 0.00 | 0.00 |
May | 79.81 | 32.65 | 47.16 | 88.60 | 31.56 | 0.00 | 0.00 | 0.00 |
June | 76.57 | 29.52 | 47.05 | 86.11 | 25.54 | 0.00 | 0.00 | 0.00 |
July | 95.64 | 50.35 | 45.28 | 117.53 | 24.67 | 0.00 | 0.00 | 0.00 |
August | 79.74 | 40.91 | 38.83 | 99.74 | 24.41 | 0.00 | 0.00 | 0.00 |
September | 65.41 | 31.75 | 33.66 | 75.19 | 33.31 | 0.00 | 0.00 | 0.00 |
October | 37.23 | 15.49 | 21.75 | 34.37 | 42.44 | 0.00 | 0.00 | 0.00 |
November | 18.40 | 5.40 | 13.00 | 10.31 | 49.42 | 0.00 | 0.00 | 0.00 |
December | 15.61 | 5.55 | 10.06 | 9.18 | 58.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.66 | 22.28 | 29.38 | 54.55 | 39.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.61 | 5.07 | 10.06 | 7.73 | 24.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.64 | 50.35 | 47.16 | 117.53 | 58.24 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119788E+09 | 72370997.34 | 47416673.17 | 0.111245E+09 | 0.144800E+09 |
February | 0.166642E+09 | 0.104793E+09 | 61849569.90 | 0.176142E+09 | 0.119006E+09 |
March | 0.197515E+09 | 0.107521E+09 | 89994539.33 | 0.216781E+09 | 0.118244E+09 |
April | 0.185276E+09 | 78053649.93 | 0.107222E+09 | 0.210180E+09 | 96429275.89 |
May | 0.154700E+09 | 35727770.54 | 0.118972E+09 | 0.165359E+09 | 85910523.77 |
June | 0.128879E+09 | 20880528.17 | 0.107999E+09 | 0.134117E+09 | 66882851.42 |
July | 0.146645E+09 | 39420510.69 | 0.107225E+09 | 0.174446E+09 | 65037101.57 |
August | 0.176653E+09 | 75472448.38 | 0.101180E+09 | 0.228481E+09 | 65587407.89 |
September | 0.216758E+09 | 0.121174E+09 | 95584256.83 | 0.269561E+09 | 88758798.45 |
October | 0.206357E+09 | 0.129291E+09 | 77066260.07 | 0.236385E+09 | 0.116508E+09 |
November | 0.117543E+09 | 68662429.69 | 48881038.34 | 0.114261E+09 | 0.126817E+09 |
December | 0.127864E+09 | 83828109.31 | 44035673.18 | 0.129633E+09 | 0.152280E+09 |
Annual Sum or Average | 0.194462E+10 | 0.937194E+09 | 0.100743E+10 | 0.216659E+10 | 0.124626E+10 |
Minimum of Months | 0.117543E+09 | 20880528.17 | 44035673.18 | 0.111245E+09 | 65037101.57 |
Maximum of Months | 0.216758E+09 | 0.129291E+09 | 0.118972E+09 | 0.269561E+09 | 0.152280E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119785E+09 | 72370997.34 | 47414368.75 | 0.111243E+09 | 0.144799E+09 |
February | 0.166639E+09 | 0.104793E+09 | 61846649.61 | 0.176139E+09 | 0.119005E+09 |
March | 0.197511E+09 | 0.107521E+09 | 89990013.70 | 0.216776E+09 | 0.118244E+09 |
April | 0.185030E+09 | 77966582.65 | 0.107063E+09 | 0.209807E+09 | 96521350.69 |
May | 0.154480E+09 | 35643507.91 | 0.118837E+09 | 0.164940E+09 | 85911690.64 |
June | 0.128819E+09 | 20862940.02 | 0.107956E+09 | 0.134007E+09 | 66882530.12 |
July | 0.146497E+09 | 39344404.45 | 0.107152E+09 | 0.174135E+09 | 65036536.07 |
August | 0.176338E+09 | 75312378.36 | 0.101025E+09 | 0.227824E+09 | 65586665.94 |
September | 0.216625E+09 | 0.121124E+09 | 95500311.12 | 0.269352E+09 | 88799447.86 |
October | 0.206354E+09 | 0.129291E+09 | 77062900.50 | 0.236382E+09 | 0.116508E+09 |
November | 0.117541E+09 | 68662429.69 | 48878535.93 | 0.114259E+09 | 0.126816E+09 |
December | 0.127862E+09 | 83828109.31 | 44033828.24 | 0.129632E+09 | 0.152280E+09 |
Annual Sum or Average | 0.194348E+10 | 0.936720E+09 | 0.100676E+10 | 0.216450E+10 | 0.124639E+10 |
Minimum of Months | 0.117541E+09 | 20862940.02 | 44033828.24 | 0.111243E+09 | 65036536.07 |
Maximum of Months | 0.216625E+09 | 0.129291E+09 | 0.118837E+09 | 0.269352E+09 | 0.152280E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119785E+09 | 72370997.34 | 47414368.75 | 0.111243E+09 | 0.144799E+09 |
February | 0.166639E+09 | 0.104793E+09 | 61846649.61 | 0.176139E+09 | 0.119005E+09 |
March | 0.197511E+09 | 0.107521E+09 | 89990013.70 | 0.216776E+09 | 0.118244E+09 |
April | 0.185025E+09 | 77966041.33 | 0.107059E+09 | 0.209804E+09 | 96525206.94 |
May | 0.154480E+09 | 35643507.91 | 0.118837E+09 | 0.164940E+09 | 85911690.64 |
June | 0.128819E+09 | 20862940.02 | 0.107956E+09 | 0.134007E+09 | 66882530.12 |
July | 0.146497E+09 | 39344404.45 | 0.107152E+09 | 0.174135E+09 | 65036536.07 |
August | 0.176337E+09 | 75312040.13 | 0.101025E+09 | 0.227822E+09 | 65586645.70 |
September | 0.216614E+09 | 0.121123E+09 | 95491036.92 | 0.269341E+09 | 88808216.24 |
October | 0.206354E+09 | 0.129291E+09 | 77062900.50 | 0.236382E+09 | 0.116508E+09 |
November | 0.117541E+09 | 68662429.69 | 48878535.93 | 0.114259E+09 | 0.126816E+09 |
December | 0.127862E+09 | 83828109.31 | 44033828.24 | 0.129632E+09 | 0.152280E+09 |
Annual Sum or Average | 0.194346E+10 | 0.936717E+09 | 0.100675E+10 | 0.216448E+10 | 0.124640E+10 |
Minimum of Months | 0.117541E+09 | 20862940.02 | 44033828.24 | 0.111243E+09 | 65036536.07 |
Maximum of Months | 0.216614E+09 | 0.129291E+09 | 0.118837E+09 | 0.269341E+09 | 0.152280E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119785E+09 | 72370997.34 | 47414368.75 | 0.111243E+09 | 0.144799E+09 |
February | 0.166639E+09 | 0.104793E+09 | 61846649.61 | 0.176139E+09 | 0.119005E+09 |
March | 0.197511E+09 | 0.107521E+09 | 89990013.70 | 0.216776E+09 | 0.118244E+09 |
April | 0.185025E+09 | 77966041.33 | 0.107059E+09 | 0.209804E+09 | 96525206.94 |
May | 0.154480E+09 | 35643507.91 | 0.118837E+09 | 0.164940E+09 | 85911690.64 |
June | 0.128819E+09 | 20862940.02 | 0.107956E+09 | 0.134007E+09 | 66882530.12 |
July | 0.146497E+09 | 39344404.45 | 0.107152E+09 | 0.174135E+09 | 65036536.07 |
August | 0.176337E+09 | 75312010.14 | 0.101025E+09 | 0.227822E+09 | 65586376.60 |
September | 0.216615E+09 | 0.121123E+09 | 95492026.70 | 0.269340E+09 | 88804931.31 |
October | 0.206354E+09 | 0.129291E+09 | 77062900.50 | 0.236382E+09 | 0.116508E+09 |
November | 0.117541E+09 | 68662429.69 | 48878535.93 | 0.114259E+09 | 0.126816E+09 |
December | 0.127862E+09 | 83828109.31 | 44033828.24 | 0.129632E+09 | 0.152280E+09 |
Annual Sum or Average | 0.194347E+10 | 0.936717E+09 | 0.100675E+10 | 0.216448E+10 | 0.124640E+10 |
Minimum of Months | 0.117541E+09 | 20862940.02 | 44033828.24 | 0.111243E+09 | 65036536.07 |
Maximum of Months | 0.216615E+09 | 0.129291E+09 | 0.118837E+09 | 0.269340E+09 | 0.152280E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119785E+09 | 72370997.34 | 47414368.75 | 0.111243E+09 | 0.144799E+09 |
February | 0.166639E+09 | 0.104793E+09 | 61846649.61 | 0.176139E+09 | 0.119005E+09 |
March | 0.197511E+09 | 0.107521E+09 | 89990013.70 | 0.216776E+09 | 0.118244E+09 |
April | 0.185029E+09 | 77966688.82 | 0.107063E+09 | 0.209804E+09 | 96517522.44 |
May | 0.154480E+09 | 35643507.91 | 0.118837E+09 | 0.164940E+09 | 85911690.64 |
June | 0.128819E+09 | 20862940.02 | 0.107956E+09 | 0.134007E+09 | 66882530.12 |
July | 0.146497E+09 | 39344404.45 | 0.107152E+09 | 0.174135E+09 | 65036536.07 |
August | 0.176338E+09 | 75312312.65 | 0.101025E+09 | 0.227822E+09 | 65585354.05 |
September | 0.216629E+09 | 0.121126E+09 | 95503174.60 | 0.269340E+09 | 88778970.98 |
October | 0.206354E+09 | 0.129291E+09 | 77062900.50 | 0.236382E+09 | 0.116508E+09 |
November | 0.117541E+09 | 68662429.69 | 48878535.93 | 0.114259E+09 | 0.126816E+09 |
December | 0.127862E+09 | 83828109.31 | 44033828.24 | 0.129632E+09 | 0.152280E+09 |
Annual Sum or Average | 0.194348E+10 | 0.936721E+09 | 0.100676E+10 | 0.216448E+10 | 0.124636E+10 |
Minimum of Months | 0.117541E+09 | 20862940.02 | 44033828.24 | 0.111243E+09 | 65036536.07 |
Maximum of Months | 0.216629E+09 | 0.129291E+09 | 0.118837E+09 | 0.269340E+09 | 0.152280E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119788E+09 | 72370997.34 | 47416673.05 | 0.111245E+09 | 0.144800E+09 |
February | 0.166642E+09 | 0.104793E+09 | 61849569.75 | 0.176142E+09 | 0.119006E+09 |
March | 0.197515E+09 | 0.107521E+09 | 89994539.10 | 0.216781E+09 | 0.118244E+09 |
April | 0.185300E+09 | 78074276.51 | 0.107226E+09 | 0.210057E+09 | 96244965.58 |
May | 0.154644E+09 | 35705161.36 | 0.118939E+09 | 0.165248E+09 | 85907152.10 |
June | 0.128888E+09 | 20885859.45 | 0.108002E+09 | 0.134136E+09 | 66882814.03 |
July | 0.146607E+09 | 39398055.58 | 0.107209E+09 | 0.174361E+09 | 65036429.99 |
August | 0.176651E+09 | 75462182.67 | 0.101189E+09 | 0.228451E+09 | 65572523.81 |
September | 0.216739E+09 | 0.121177E+09 | 95561664.36 | 0.269428E+09 | 88647459.55 |
October | 0.206357E+09 | 0.129291E+09 | 77066259.90 | 0.236385E+09 | 0.116508E+09 |
November | 0.117543E+09 | 68662429.69 | 48881038.21 | 0.114261E+09 | 0.126817E+09 |
December | 0.127864E+09 | 83828109.31 | 44035673.08 | 0.129633E+09 | 0.152280E+09 |
Annual Sum or Average | 0.194454E+10 | 0.937168E+09 | 0.100737E+10 | 0.216613E+10 | 0.124595E+10 |
Minimum of Months | 0.117543E+09 | 20885859.45 | 44035673.08 | 0.111245E+09 | 65036429.99 |
Maximum of Months | 0.216739E+09 | 0.129291E+09 | 0.118939E+09 | 0.269428E+09 | 0.152280E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_1_WALL_SOUTH_DOOR
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169270E+09 | 0.101393E+09 | 67877366.16 | 0.157425E+09 | 0.201311E+09 |
February | 0.235300E+09 | 0.146816E+09 | 88484491.94 | 0.248880E+09 | 0.165682E+09 |
March | 0.279561E+09 | 0.150638E+09 | 0.128923E+09 | 0.306799E+09 | 0.164357E+09 |
April | 0.283709E+09 | 0.124616E+09 | 0.159093E+09 | 0.330232E+09 | 0.133926E+09 |
May | 0.250209E+09 | 69743382.14 | 0.180466E+09 | 0.283870E+09 | 0.119475E+09 |
June | 0.211286E+09 | 47779390.64 | 0.163507E+09 | 0.237492E+09 | 93151777.08 |
July | 0.242501E+09 | 81023657.77 | 0.161477E+09 | 0.304174E+09 | 90834634.63 |
August | 0.281368E+09 | 0.130674E+09 | 0.150694E+09 | 0.372361E+09 | 91829197.15 |
September | 0.310623E+09 | 0.173058E+09 | 0.137565E+09 | 0.387020E+09 | 0.123940E+09 |
October | 0.291217E+09 | 0.181138E+09 | 0.110079E+09 | 0.333381E+09 | 0.162356E+09 |
November | 0.166250E+09 | 96196955.48 | 70053200.45 | 0.161723E+09 | 0.176357E+09 |
December | 0.180296E+09 | 0.117444E+09 | 62852223.96 | 0.182575E+09 | 0.211842E+09 |
Annual Sum or Average | 0.290159E+10 | 0.142052E+10 | 0.148107E+10 | 0.330593E+10 | 0.173506E+10 |
Minimum of Months | 0.166250E+09 | 47779390.64 | 62852223.96 | 0.157425E+09 | 90834634.63 |
Maximum of Months | 0.310623E+09 | 0.181138E+09 | 0.180466E+09 | 0.387020E+09 | 0.211842E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41776763.45 | 11038209.27 | 30738554.18 | 16076126.29 | 0.149259E+09 |
February | 69585133.53 | 25430454.28 | 44154679.25 | 48401995.57 | 0.116782E+09 |
March | 0.114382E+09 | 42187093.05 | 72194600.64 | 99527984.74 | 0.109104E+09 |
April | 0.171381E+09 | 72124814.25 | 99255845.82 | 0.178549E+09 | 85883945.03 |
May | 0.184969E+09 | 64157972.33 | 0.120811E+09 | 0.197667E+09 | 79189430.97 |
June | 0.215619E+09 | 93461979.33 | 0.122157E+09 | 0.245424E+09 | 62477127.70 |
July | 0.207496E+09 | 92009061.40 | 0.115487E+09 | 0.245751E+09 | 58070569.21 |
August | 0.207294E+09 | 0.104009E+09 | 0.103284E+09 | 0.255082E+09 | 58594239.75 |
September | 0.149179E+09 | 69657962.12 | 79521499.71 | 0.162723E+09 | 80396665.74 |
October | 0.100663E+09 | 43668239.27 | 56994454.26 | 91218444.75 | 0.109312E+09 |
November | 47290454.60 | 13856606.89 | 33433847.71 | 25087761.65 | 0.126161E+09 |
December | 40436360.13 | 13506560.44 | 26929799.69 | 20367632.82 | 0.153824E+09 |
Annual Sum or Average | 0.155007E+10 | 0.645108E+09 | 0.904962E+09 | 0.158588E+10 | 0.118905E+10 |
Minimum of Months | 40436360.13 | 11038209.27 | 26929799.69 | 16076126.29 | 58070569.21 |
Maximum of Months | 0.215619E+09 | 0.104009E+09 | 0.122157E+09 | 0.255082E+09 | 0.153824E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41774459.15 | 11038209.27 | 30736249.88 | 16075230.49 | 0.149259E+09 |
February | 69582213.39 | 25430454.28 | 44151759.11 | 48399575.26 | 0.116782E+09 |
March | 0.114377E+09 | 42187093.05 | 72190075.25 | 99523515.51 | 0.109104E+09 |
April | 0.171375E+09 | 72124814.25 | 99250366.61 | 0.178543E+09 | 85883448.14 |
May | 0.184962E+09 | 64157972.33 | 0.120804E+09 | 0.197659E+09 | 79188944.34 |
June | 0.215613E+09 | 93461979.33 | 0.122151E+09 | 0.245418E+09 | 62476596.45 |
July | 0.207491E+09 | 92009061.40 | 0.115481E+09 | 0.245745E+09 | 58069663.27 |
August | 0.207289E+09 | 0.104009E+09 | 0.103280E+09 | 0.255077E+09 | 58593179.66 |
September | 0.149175E+09 | 69657962.12 | 79517280.49 | 0.162719E+09 | 80395712.06 |
October | 0.100659E+09 | 43668239.27 | 56991094.86 | 91215331.26 | 0.109312E+09 |
November | 47287952.32 | 13856606.89 | 33431345.43 | 25086279.34 | 0.126162E+09 |
December | 40434515.29 | 13506560.44 | 26927954.85 | 20367046.82 | 0.153824E+09 |
Annual Sum or Average | 0.155002E+10 | 0.645108E+09 | 0.904912E+09 | 0.158583E+10 | 0.118905E+10 |
Minimum of Months | 40434515.29 | 11038209.27 | 26927954.85 | 16075230.49 | 58069663.27 |
Maximum of Months | 0.215613E+09 | 0.104009E+09 | 0.122151E+09 | 0.255077E+09 | 0.153824E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41774459.15 | 11038209.27 | 30736249.88 | 16075230.49 | 0.149259E+09 |
February | 69582213.39 | 25430454.28 | 44151759.11 | 48399575.26 | 0.116782E+09 |
March | 0.114377E+09 | 42187093.05 | 72190075.25 | 99523515.51 | 0.109104E+09 |
April | 0.171375E+09 | 72124814.25 | 99250366.61 | 0.178543E+09 | 85883448.14 |
May | 0.184962E+09 | 64157972.33 | 0.120804E+09 | 0.197659E+09 | 79188944.34 |
June | 0.215613E+09 | 93461979.33 | 0.122151E+09 | 0.245418E+09 | 62476596.45 |
July | 0.207491E+09 | 92009061.40 | 0.115481E+09 | 0.245745E+09 | 58069663.27 |
August | 0.207289E+09 | 0.104009E+09 | 0.103280E+09 | 0.255077E+09 | 58593179.66 |
September | 0.149175E+09 | 69657962.12 | 79517280.49 | 0.162719E+09 | 80395712.06 |
October | 0.100659E+09 | 43668239.27 | 56991094.86 | 91215331.26 | 0.109312E+09 |
November | 47287952.32 | 13856606.89 | 33431345.43 | 25086279.34 | 0.126162E+09 |
December | 40434515.29 | 13506560.44 | 26927954.85 | 20367046.82 | 0.153824E+09 |
Annual Sum or Average | 0.155002E+10 | 0.645108E+09 | 0.904912E+09 | 0.158583E+10 | 0.118905E+10 |
Minimum of Months | 40434515.29 | 11038209.27 | 26927954.85 | 16075230.49 | 58069663.27 |
Maximum of Months | 0.215613E+09 | 0.104009E+09 | 0.122151E+09 | 0.255077E+09 | 0.153824E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41939202.09 | 11096497.14 | 30842704.95 | 16214970.22 | 0.149087E+09 |
February | 69734082.89 | 25489069.80 | 44245013.10 | 48635437.99 | 0.116729E+09 |
March | 0.114422E+09 | 42206170.85 | 72215828.14 | 99609069.42 | 0.109104E+09 |
April | 0.171381E+09 | 72124814.25 | 99255846.11 | 0.178549E+09 | 85883945.05 |
May | 0.184969E+09 | 64157972.33 | 0.120811E+09 | 0.197667E+09 | 79189430.99 |
June | 0.215619E+09 | 93461979.33 | 0.122157E+09 | 0.245424E+09 | 62477127.73 |
July | 0.207496E+09 | 92009061.40 | 0.115487E+09 | 0.245751E+09 | 58070569.26 |
August | 0.207294E+09 | 0.104009E+09 | 0.103284E+09 | 0.255082E+09 | 58594239.80 |
September | 0.149191E+09 | 69661171.57 | 79529636.32 | 0.162743E+09 | 80396665.71 |
October | 0.100777E+09 | 43719439.86 | 57058056.96 | 91445007.78 | 0.109312E+09 |
November | 47434571.46 | 13910761.51 | 33523809.96 | 25301723.25 | 0.126098E+09 |
December | 40628240.67 | 13577259.17 | 27050981.50 | 20605657.46 | 0.153692E+09 |
Annual Sum or Average | 0.155088E+10 | 0.645424E+09 | 0.905461E+09 | 0.158703E+10 | 0.118863E+10 |
Minimum of Months | 40628240.67 | 11096497.14 | 27050981.50 | 16214970.22 | 58070569.26 |
Maximum of Months | 0.215619E+09 | 0.104009E+09 | 0.122157E+09 | 0.255082E+09 | 0.153692E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25495335.90 | 0.00 | 25495335.90 | 1068686.87 | 0.157010E+09 |
February | 36120934.40 | 0.00 | 36120934.40 | 8718651.70 | 0.123474E+09 |
March | 59136236.43 | 0.00 | 59136236.43 | 29068599.79 | 0.112120E+09 |
April | 81564127.84 | 298263.68 | 81265864.16 | 59651429.36 | 86508721.31 |
May | 0.108245E+09 | 3210726.61 | 0.105034E+09 | 92392410.94 | 77086425.60 |
June | 0.110628E+09 | 7209339.01 | 0.103419E+09 | 0.101531E+09 | 59279405.72 |
July | 0.109385E+09 | 8504000.17 | 0.100881E+09 | 0.112546E+09 | 56854662.81 |
August | 88468520.12 | 2422690.40 | 86045829.71 | 92674461.08 | 56953571.46 |
September | 66191832.27 | 20245.10 | 66171587.17 | 51223358.64 | 81251519.89 |
October | 46533401.82 | 0.00 | 46533401.82 | 21077579.44 | 0.110749E+09 |
November | 27953922.68 | 0.00 | 27953922.68 | 3699481.67 | 0.130100E+09 |
December | 21767100.38 | 0.00 | 21767100.38 | 714457.47 | 0.159956E+09 |
Annual Sum or Average | 0.781490E+09 | 21665264.97 | 0.759825E+09 | 0.574366E+09 | 0.121134E+10 |
Minimum of Months | 21767100.38 | 0.00 | 21767100.38 | 714457.47 | 56854662.81 |
Maximum of Months | 0.110628E+09 | 8504000.17 | 0.105034E+09 | 0.112546E+09 | 0.159956E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25493031.48 | 0.00 | 25493031.48 | 1068147.12 | 0.157011E+09 |
February | 36118014.11 | 0.00 | 36118014.11 | 8716616.31 | 0.123474E+09 |
March | 59131710.80 | 0.00 | 59131710.80 | 29064476.78 | 0.112120E+09 |
April | 81513940.73 | 291142.96 | 81222797.77 | 59645577.07 | 86586965.47 |
May | 0.108084E+09 | 3161443.64 | 0.104922E+09 | 92178184.82 | 77173277.23 |
June | 0.110362E+09 | 7099182.32 | 0.103263E+09 | 0.101021E+09 | 59292251.04 |
July | 0.109164E+09 | 8400708.26 | 0.100764E+09 | 0.112120E+09 | 56881538.87 |
August | 88285874.45 | 2355629.15 | 85930245.30 | 92448755.78 | 57089550.31 |
September | 66187337.41 | 20243.65 | 66167093.76 | 51218982.25 | 81251070.83 |
October | 46530042.25 | 0.00 | 46530042.25 | 21074695.15 | 0.110748E+09 |
November | 27951420.27 | 0.00 | 27951420.27 | 3698306.30 | 0.130101E+09 |
December | 21765255.44 | 0.00 | 21765255.44 | 714209.14 | 0.159957E+09 |
Annual Sum or Average | 0.780587E+09 | 21328349.98 | 0.759258E+09 | 0.572969E+09 | 0.121169E+10 |
Minimum of Months | 21765255.44 | 0.00 | 21765255.44 | 714209.14 | 56881538.87 |
Maximum of Months | 0.110362E+09 | 8400708.26 | 0.104922E+09 | 0.112120E+09 | 0.159957E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25493031.48 | 0.00 | 25493031.48 | 1068147.12 | 0.157011E+09 |
February | 36118014.11 | 0.00 | 36118014.11 | 8716616.31 | 0.123474E+09 |
March | 59131710.80 | 0.00 | 59131710.80 | 29064476.78 | 0.112120E+09 |
April | 81492066.12 | 288389.07 | 81203677.05 | 59645576.27 | 86624172.57 |
May | 0.108084E+09 | 3161443.64 | 0.104922E+09 | 92178184.82 | 77173277.23 |
June | 0.110362E+09 | 7099182.32 | 0.103263E+09 | 0.101021E+09 | 59292251.04 |
July | 0.109164E+09 | 8400671.21 | 0.100764E+09 | 0.112120E+09 | 56881635.69 |
August | 88284405.77 | 2355398.91 | 85929006.86 | 92448524.32 | 57091855.18 |
September | 66186623.18 | 20099.93 | 66166523.26 | 51218982.25 | 81252431.71 |
October | 46530042.25 | 0.00 | 46530042.25 | 21074695.15 | 0.110748E+09 |
November | 27951420.27 | 0.00 | 27951420.27 | 3698306.30 | 0.130101E+09 |
December | 21765255.44 | 0.00 | 21765255.44 | 714209.14 | 0.159957E+09 |
Annual Sum or Average | 0.780563E+09 | 21325185.07 | 0.759238E+09 | 0.572968E+09 | 0.121173E+10 |
Minimum of Months | 21765255.44 | 0.00 | 21765255.44 | 714209.14 | 56881635.69 |
Maximum of Months | 0.110362E+09 | 8400671.21 | 0.104922E+09 | 0.112120E+09 | 0.159957E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25493031.48 | 0.00 | 25493031.48 | 1068147.12 | 0.157011E+09 |
February | 36118014.11 | 0.00 | 36118014.11 | 8716616.31 | 0.123474E+09 |
March | 59131710.80 | 0.00 | 59131710.80 | 29064476.78 | 0.112120E+09 |
April | 81492220.85 | 288407.46 | 81203813.38 | 59645751.34 | 86624087.97 |
May | 0.108084E+09 | 3161443.64 | 0.104922E+09 | 92178184.82 | 77173277.23 |
June | 0.110362E+09 | 7099182.32 | 0.103263E+09 | 0.101021E+09 | 59292251.04 |
July | 0.109164E+09 | 8400671.21 | 0.100764E+09 | 0.112120E+09 | 56881635.69 |
August | 88284078.22 | 2355409.41 | 85928668.80 | 92449253.95 | 57093012.45 |
September | 66187425.76 | 19933.68 | 66167492.07 | 51218982.25 | 81251662.69 |
October | 46530042.25 | 0.00 | 46530042.25 | 21074695.15 | 0.110748E+09 |
November | 27951420.27 | 0.00 | 27951420.27 | 3698306.30 | 0.130101E+09 |
December | 21765255.44 | 0.00 | 21765255.44 | 714209.14 | 0.159957E+09 |
Annual Sum or Average | 0.780563E+09 | 21325047.72 | 0.759238E+09 | 0.572969E+09 | 0.121173E+10 |
Minimum of Months | 21765255.44 | 0.00 | 21765255.44 | 714209.14 | 56881635.69 |
Maximum of Months | 0.110362E+09 | 8400671.21 | 0.104922E+09 | 0.112120E+09 | 0.159957E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25493031.48 | 0.00 | 25493031.48 | 1068147.12 | 0.157011E+09 |
February | 36118014.11 | 0.00 | 36118014.11 | 8716616.31 | 0.123474E+09 |
March | 59131710.80 | 0.00 | 59131710.80 | 29064476.78 | 0.112120E+09 |
April | 81516650.73 | 291065.87 | 81225584.86 | 59663579.60 | 86601092.33 |
May | 0.108084E+09 | 3161443.64 | 0.104922E+09 | 92178184.82 | 77173277.23 |
June | 0.110362E+09 | 7099182.32 | 0.103263E+09 | 0.101021E+09 | 59292251.04 |
July | 0.109164E+09 | 8400759.42 | 0.100764E+09 | 0.112120E+09 | 56881635.69 |
August | 88285571.37 | 2355964.54 | 85929606.83 | 92452648.58 | 57093422.01 |
September | 66189205.30 | 20041.39 | 66169163.91 | 51218982.25 | 81248892.49 |
October | 46530042.25 | 0.00 | 46530042.25 | 21074695.15 | 0.110748E+09 |
November | 27951420.27 | 0.00 | 27951420.27 | 3698306.30 | 0.130101E+09 |
December | 21765255.44 | 0.00 | 21765255.44 | 714209.14 | 0.159957E+09 |
Annual Sum or Average | 0.780591E+09 | 21328457.18 | 0.759263E+09 | 0.572991E+09 | 0.121170E+10 |
Minimum of Months | 21765255.44 | 0.00 | 21765255.44 | 714209.14 | 56881635.69 |
Maximum of Months | 0.110362E+09 | 8400759.42 | 0.104922E+09 | 0.112120E+09 | 0.159957E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25495335.78 | 0.00 | 25495335.78 | 1068686.84 | 0.157010E+09 |
February | 36120934.24 | 0.00 | 36120934.24 | 8718651.60 | 0.123474E+09 |
March | 59136236.19 | 0.00 | 59136236.19 | 29068599.58 | 0.112120E+09 |
April | 81567152.83 | 297213.38 | 81269939.45 | 59704276.38 | 86559824.50 |
May | 0.108339E+09 | 3252690.79 | 0.105087E+09 | 92653788.14 | 77159903.95 |
June | 0.110616E+09 | 7192591.26 | 0.103423E+09 | 0.101500E+09 | 59291289.80 |
July | 0.109474E+09 | 8552600.66 | 0.100922E+09 | 0.112752E+09 | 56876210.12 |
August | 88462151.19 | 2422450.97 | 86039700.21 | 92788021.21 | 57083658.49 |
September | 66193215.54 | 20040.29 | 66173175.25 | 51223358.41 | 81250070.45 |
October | 46533401.65 | 0.00 | 46533401.65 | 21077579.29 | 0.110749E+09 |
November | 27953922.55 | 0.00 | 27953922.55 | 3699481.61 | 0.130100E+09 |
December | 21767100.29 | 0.00 | 21767100.29 | 714457.46 | 0.159956E+09 |
Annual Sum or Average | 0.781659E+09 | 21737587.35 | 0.759921E+09 | 0.574969E+09 | 0.121163E+10 |
Minimum of Months | 21767100.29 | 0.00 | 21767100.29 | 714457.46 | 56876210.12 |
Maximum of Months | 0.110616E+09 | 8552600.66 | 0.105087E+09 | 0.112752E+09 | 0.159956E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44348139.18 | 13636255.24 | 30711883.95 | 20873370.41 | 0.150871E+09 |
February | 72027062.57 | 27829525.18 | 44197537.39 | 54388269.87 | 0.119549E+09 |
March | 0.110514E+09 | 38020195.59 | 72493924.57 | 96782920.12 | 0.112939E+09 |
April | 0.161813E+09 | 62283665.44 | 99529219.37 | 0.168022E+09 | 90877437.47 |
May | 0.213757E+09 | 87440219.31 | 0.126317E+09 | 0.237318E+09 | 84523763.75 |
June | 0.198481E+09 | 76520589.89 | 0.121960E+09 | 0.223192E+09 | 66194653.09 |
July | 0.256161E+09 | 0.134870E+09 | 0.121291E+09 | 0.314784E+09 | 66066634.36 |
August | 0.213576E+09 | 0.109568E+09 | 0.104008E+09 | 0.267153E+09 | 65392566.25 |
September | 0.169555E+09 | 82294799.16 | 87260512.38 | 0.194918E+09 | 86350649.45 |
October | 99835222.26 | 41526742.05 | 58308480.21 | 92261212.45 | 0.113661E+09 |
November | 47812231.77 | 14040544.03 | 33771687.74 | 26932161.00 | 0.128037E+09 |
December | 41981638.42 | 14929467.12 | 27052171.30 | 24793695.35 | 0.155882E+09 |
Annual Sum or Average | 0.162986E+10 | 0.702960E+09 | 0.926901E+09 | 0.172142E+10 | 0.124035E+10 |
Minimum of Months | 41981638.42 | 13636255.24 | 27052171.30 | 20873370.41 | 65392566.25 |
Maximum of Months | 0.256161E+09 | 0.134870E+09 | 0.126317E+09 | 0.314784E+09 | 0.155882E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44174056.67 | 13577970.70 | 30596085.97 | 20704075.25 | 0.151027E+09 |
February | 71895250.92 | 27772431.73 | 44122819.19 | 54160333.17 | 0.119579E+09 |
March | 0.110465E+09 | 38000391.21 | 72464787.88 | 96692046.14 | 0.112939E+09 |
April | 0.161807E+09 | 62283665.44 | 99523740.16 | 0.168016E+09 | 90877099.40 |
May | 0.213750E+09 | 87440219.31 | 0.126310E+09 | 0.237310E+09 | 84523489.30 |
June | 0.198475E+09 | 76520589.89 | 0.121954E+09 | 0.223185E+09 | 66194262.94 |
July | 0.256156E+09 | 0.134870E+09 | 0.121286E+09 | 0.314779E+09 | 66066006.67 |
August | 0.213571E+09 | 0.109568E+09 | 0.104003E+09 | 0.267148E+09 | 65391633.77 |
September | 0.169537E+09 | 82288788.99 | 87248636.15 | 0.194887E+09 | 86349749.43 |
October | 99720527.86 | 41479788.30 | 58240739.56 | 92043522.09 | 0.113661E+09 |
November | 47679025.46 | 13998032.55 | 33680992.91 | 26734027.07 | 0.128086E+09 |
December | 41817099.95 | 14871076.61 | 26946023.33 | 24577168.97 | 0.155979E+09 |
Annual Sum or Average | 0.162905E+10 | 0.702671E+09 | 0.926377E+09 | 0.172024E+10 | 0.124067E+10 |
Minimum of Months | 41817099.95 | 13577970.70 | 26946023.33 | 20704075.25 | 65391633.77 |
Maximum of Months | 0.256156E+09 | 0.134870E+09 | 0.126310E+09 | 0.314779E+09 | 0.155979E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44174056.67 | 13577970.70 | 30596085.97 | 20704075.25 | 0.151027E+09 |
February | 71895250.92 | 27772431.73 | 44122819.19 | 54160333.17 | 0.119579E+09 |
March | 0.110465E+09 | 38000391.21 | 72464787.88 | 96692046.14 | 0.112939E+09 |
April | 0.161807E+09 | 62283665.44 | 99523740.16 | 0.168016E+09 | 90877099.40 |
May | 0.213750E+09 | 87440219.31 | 0.126310E+09 | 0.237310E+09 | 84523489.30 |
June | 0.198475E+09 | 76520589.89 | 0.121954E+09 | 0.223185E+09 | 66194262.94 |
July | 0.256156E+09 | 0.134870E+09 | 0.121286E+09 | 0.314779E+09 | 66066006.67 |
August | 0.213571E+09 | 0.109568E+09 | 0.104003E+09 | 0.267148E+09 | 65391633.77 |
September | 0.169537E+09 | 82288788.99 | 87248636.15 | 0.194887E+09 | 86349749.43 |
October | 99720527.86 | 41479788.30 | 58240739.56 | 92043522.09 | 0.113661E+09 |
November | 47679025.46 | 13998032.55 | 33680992.91 | 26734027.07 | 0.128086E+09 |
December | 41817099.95 | 14871076.61 | 26946023.33 | 24577168.97 | 0.155979E+09 |
Annual Sum or Average | 0.162905E+10 | 0.702671E+09 | 0.926377E+09 | 0.172024E+10 | 0.124067E+10 |
Minimum of Months | 41817099.95 | 13577970.70 | 26946023.33 | 20704075.25 | 65391633.77 |
Maximum of Months | 0.256156E+09 | 0.134870E+09 | 0.126310E+09 | 0.314779E+09 | 0.155979E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44176361.09 | 13577970.70 | 30598390.39 | 20704942.45 | 0.151027E+09 |
February | 71898171.21 | 27772431.73 | 44125739.48 | 54162585.66 | 0.119579E+09 |
March | 0.110470E+09 | 38000391.21 | 72469313.51 | 96696384.86 | 0.112939E+09 |
April | 0.161813E+09 | 62283665.44 | 99529219.66 | 0.168022E+09 | 90877437.49 |
May | 0.213757E+09 | 87440219.31 | 0.126317E+09 | 0.237318E+09 | 84523763.76 |
June | 0.198481E+09 | 76520589.89 | 0.121960E+09 | 0.223192E+09 | 66194653.11 |
July | 0.256161E+09 | 0.134870E+09 | 0.121291E+09 | 0.314784E+09 | 66066634.39 |
August | 0.213576E+09 | 0.109568E+09 | 0.104008E+09 | 0.267153E+09 | 65392566.30 |
September | 0.169542E+09 | 82288788.99 | 87252855.59 | 0.194891E+09 | 86350649.50 |
October | 99723887.43 | 41479788.30 | 58244099.13 | 92046492.07 | 0.113662E+09 |
November | 47681527.88 | 13998032.55 | 33683495.33 | 26735500.11 | 0.128086E+09 |
December | 41818944.89 | 14871076.61 | 26947868.27 | 24577618.23 | 0.155979E+09 |
Annual Sum or Average | 0.162910E+10 | 0.702671E+09 | 0.926427E+09 | 0.172028E+10 | 0.124068E+10 |
Minimum of Months | 41818944.89 | 13577970.70 | 26947868.27 | 20704942.45 | 65392566.30 |
Maximum of Months | 0.256161E+09 | 0.134870E+09 | 0.126317E+09 | 0.314784E+09 | 0.155979E+09 |
Report: WindowZoneSummaryMonthly
For: CORE_ZN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_ZN_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 307.97 | 399.53 | 331.54 | 199.98 | 131.56 | 0.00 | 0.00 |
February | 539.73 | 363.63 | 510.56 | 320.59 | 189.97 | 0.00 | 0.00 |
March | 600.15 | 326.24 | 546.83 | 297.10 | 249.73 | 0.00 | 0.00 |
April | 613.27 | 274.92 | 537.96 | 228.63 | 309.33 | 0.00 | 0.00 |
May | 475.73 | 237.05 | 439.62 | 105.94 | 333.68 | 0.00 | 0.00 |
June | 401.91 | 190.75 | 379.76 | 66.74 | 313.01 | 0.00 | 0.00 |
July | 503.85 | 179.60 | 418.81 | 118.44 | 300.37 | 0.00 | 0.00 |
August | 649.85 | 181.20 | 500.31 | 217.61 | 282.69 | 0.00 | 0.00 |
September | 772.90 | 253.28 | 621.37 | 347.19 | 274.19 | 0.00 | 0.00 |
October | 654.00 | 321.61 | 570.99 | 357.26 | 213.73 | 0.00 | 0.00 |
November | 326.88 | 361.59 | 336.23 | 196.05 | 140.17 | 0.00 | 0.00 |
December | 358.56 | 420.22 | 353.75 | 231.64 | 122.11 | 0.00 | 0.00 |
Annual Sum or Average | 516.75 | 292.13 | 461.84 | 223.29 | 238.55 | 0.00 | 0.00 |
Minimum of Months | 307.97 | 179.60 | 331.54 | 66.74 | 122.11 | 0.00 | 0.00 |
Maximum of Months | 772.90 | 420.22 | 621.37 | 357.26 | 333.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_ZN_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 24.05 | 222.84 | 62.45 | 16.51 | 45.94 | 0.00 | 0.00 |
February | 80.12 | 193.06 | 115.11 | 42.07 | 73.04 | 0.00 | 0.00 |
March | 148.66 | 162.94 | 170.83 | 63.01 | 107.82 | 0.00 | 0.00 |
April | 275.53 | 132.54 | 264.47 | 111.30 | 153.17 | 0.00 | 0.00 |
May | 295.20 | 118.26 | 276.23 | 95.82 | 180.42 | 0.00 | 0.00 |
June | 378.74 | 96.41 | 332.74 | 144.23 | 188.51 | 0.00 | 0.00 |
July | 367.01 | 86.72 | 309.88 | 137.41 | 172.47 | 0.00 | 0.00 |
August | 380.94 | 87.51 | 309.58 | 155.33 | 154.24 | 0.00 | 0.00 |
September | 251.12 | 124.07 | 230.22 | 107.50 | 122.72 | 0.00 | 0.00 |
October | 136.31 | 163.25 | 150.37 | 65.23 | 85.14 | 0.00 | 0.00 |
November | 38.79 | 194.66 | 73.03 | 21.40 | 51.63 | 0.00 | 0.00 |
December | 30.49 | 229.67 | 60.46 | 20.20 | 40.26 | 0.00 | 0.00 |
Annual Sum or Average | 201.18 | 150.80 | 196.63 | 81.84 | 114.80 | 0.00 | 0.00 |
Minimum of Months | 24.05 | 86.72 | 60.46 | 16.51 | 40.26 | 0.00 | 0.00 |
Maximum of Months | 380.94 | 229.67 | 332.74 | 155.33 | 188.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_ZN_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.39 | 351.73 | 57.11 | 0.00 | 57.11 | 0.00 | 0.00 |
February | 21.62 | 306.23 | 89.58 | 0.00 | 89.58 | 0.00 | 0.00 |
March | 65.11 | 251.17 | 132.47 | 0.00 | 132.47 | 0.00 | 0.00 |
April | 138.10 | 200.43 | 188.71 | 0.68 | 188.04 | 0.00 | 0.00 |
May | 206.74 | 172.83 | 242.28 | 7.13 | 235.14 | 0.00 | 0.00 |
June | 234.23 | 137.25 | 255.67 | 16.51 | 239.16 | 0.00 | 0.00 |
July | 251.56 | 127.41 | 244.74 | 18.91 | 225.83 | 0.00 | 0.00 |
August | 207.29 | 127.82 | 197.91 | 5.33 | 192.58 | 0.00 | 0.00 |
September | 118.57 | 188.08 | 153.22 | 0.05 | 153.17 | 0.00 | 0.00 |
October | 47.21 | 248.09 | 104.24 | 0.00 | 104.24 | 0.00 | 0.00 |
November | 8.56 | 301.16 | 64.70 | 0.00 | 64.70 | 0.00 | 0.00 |
December | 1.60 | 358.33 | 48.76 | 0.00 | 48.76 | 0.00 | 0.00 |
Annual Sum or Average | 109.12 | 230.52 | 148.57 | 4.08 | 144.49 | 0.00 | 0.00 |
Minimum of Months | 1.60 | 127.41 | 48.76 | 0.00 | 48.76 | 0.00 | 0.00 |
Maximum of Months | 251.56 | 358.33 | 255.67 | 18.91 | 239.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_ZN_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 30.97 | 225.48 | 66.04 | 20.30 | 45.74 | 0.00 | 0.00 |
February | 89.64 | 197.70 | 118.93 | 45.94 | 72.99 | 0.00 | 0.00 |
March | 144.44 | 168.67 | 164.99 | 56.76 | 108.23 | 0.00 | 0.00 |
April | 259.29 | 140.24 | 249.71 | 96.12 | 153.59 | 0.00 | 0.00 |
May | 354.41 | 126.23 | 319.23 | 130.59 | 188.64 | 0.00 | 0.00 |
June | 344.43 | 102.15 | 306.29 | 118.09 | 188.21 | 0.00 | 0.00 |
July | 470.10 | 98.67 | 382.55 | 201.42 | 181.14 | 0.00 | 0.00 |
August | 398.97 | 97.66 | 318.96 | 163.63 | 155.32 | 0.00 | 0.00 |
September | 300.76 | 133.26 | 261.64 | 126.99 | 134.65 | 0.00 | 0.00 |
October | 137.54 | 169.75 | 148.97 | 61.96 | 87.00 | 0.00 | 0.00 |
November | 41.33 | 197.64 | 73.63 | 21.62 | 52.01 | 0.00 | 0.00 |
December | 36.78 | 232.90 | 62.51 | 22.23 | 40.28 | 0.00 | 0.00 |
Annual Sum or Average | 218.23 | 157.35 | 206.65 | 89.14 | 117.52 | 0.00 | 0.00 |
Minimum of Months | 30.97 | 97.66 | 62.51 | 20.30 | 40.28 | 0.00 | 0.00 |
Maximum of Months | 470.10 | 232.90 | 382.55 | 201.42 | 188.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_ZN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_ZN_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.824877E+09 | 0.107010E+10 | 0.887987E+09 | 0.535619E+09 | 0.352368E+09 | 0.00 | 0.00 |
February | 0.130571E+10 | 0.879701E+09 | 0.123514E+10 | 0.775571E+09 | 0.459570E+09 | 0.00 | 0.00 |
March | 0.160745E+10 | 0.873800E+09 | 0.146463E+10 | 0.795763E+09 | 0.668872E+09 | 0.00 | 0.00 |
April | 0.158958E+10 | 0.712587E+09 | 0.139439E+10 | 0.592610E+09 | 0.801784E+09 | 0.00 | 0.00 |
May | 0.127420E+10 | 0.634905E+09 | 0.117748E+10 | 0.283750E+09 | 0.893725E+09 | 0.00 | 0.00 |
June | 0.104176E+10 | 0.494434E+09 | 0.984331E+09 | 0.172998E+09 | 0.811333E+09 | 0.00 | 0.00 |
July | 0.134951E+10 | 0.481042E+09 | 0.112174E+10 | 0.317220E+09 | 0.804520E+09 | 0.00 | 0.00 |
August | 0.174057E+10 | 0.485319E+09 | 0.134002E+10 | 0.582857E+09 | 0.757164E+09 | 0.00 | 0.00 |
September | 0.200335E+10 | 0.656507E+09 | 0.161060E+10 | 0.899904E+09 | 0.710697E+09 | 0.00 | 0.00 |
October | 0.175167E+10 | 0.861390E+09 | 0.152935E+10 | 0.956882E+09 | 0.572463E+09 | 0.00 | 0.00 |
November | 0.847262E+09 | 0.937238E+09 | 0.871501E+09 | 0.508172E+09 | 0.363329E+09 | 0.00 | 0.00 |
December | 0.960362E+09 | 0.112551E+10 | 0.947472E+09 | 0.620413E+09 | 0.327059E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.162963E+11 | 0.921253E+10 | 0.145646E+11 | 0.704176E+10 | 0.752289E+10 | 0.00 | 0.00 |
Minimum of Months | 0.824877E+09 | 0.481042E+09 | 0.871501E+09 | 0.172998E+09 | 0.327059E+09 | 0.00 | 0.00 |
Maximum of Months | 0.200335E+10 | 0.112551E+10 | 0.161060E+10 | 0.956882E+09 | 0.893725E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_ZN_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 64419901.01 | 0.596842E+09 | 0.167265E+09 | 44211124.96 | 0.123054E+09 | 0.00 | 0.00 |
February | 0.193823E+09 | 0.467060E+09 | 0.278484E+09 | 0.101780E+09 | 0.176703E+09 | 0.00 | 0.00 |
March | 0.398184E+09 | 0.436415E+09 | 0.457558E+09 | 0.168767E+09 | 0.288791E+09 | 0.00 | 0.00 |
April | 0.714184E+09 | 0.343535E+09 | 0.685512E+09 | 0.288499E+09 | 0.397012E+09 | 0.00 | 0.00 |
May | 0.790652E+09 | 0.316757E+09 | 0.739860E+09 | 0.256632E+09 | 0.483228E+09 | 0.00 | 0.00 |
June | 0.981684E+09 | 0.249907E+09 | 0.862465E+09 | 0.373848E+09 | 0.488617E+09 | 0.00 | 0.00 |
July | 0.982992E+09 | 0.232280E+09 | 0.829973E+09 | 0.368036E+09 | 0.461936E+09 | 0.00 | 0.00 |
August | 0.102032E+10 | 0.234375E+09 | 0.829166E+09 | 0.416038E+09 | 0.413128E+09 | 0.00 | 0.00 |
September | 0.650904E+09 | 0.321585E+09 | 0.596721E+09 | 0.278635E+09 | 0.318086E+09 | 0.00 | 0.00 |
October | 0.365094E+09 | 0.437247E+09 | 0.402759E+09 | 0.174724E+09 | 0.228035E+09 | 0.00 | 0.00 |
November | 0.100544E+09 | 0.504565E+09 | 0.189301E+09 | 55480582.17 | 0.133820E+09 | 0.00 | 0.00 |
December | 81677584.32 | 0.615135E+09 | 0.161934E+09 | 54096940.49 | 0.107837E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.634448E+10 | 0.475570E+10 | 0.620100E+10 | 0.258075E+10 | 0.362025E+10 | 0.00 | 0.00 |
Minimum of Months | 64419901.01 | 0.232280E+09 | 0.161934E+09 | 44211124.96 | 0.107837E+09 | 0.00 | 0.00 |
Maximum of Months | 0.102032E+10 | 0.615135E+09 | 0.862465E+09 | 0.416038E+09 | 0.488617E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_ZN_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 6409962.21 | 0.942065E+09 | 0.152963E+09 | 0.00 | 0.152963E+09 | 0.00 | 0.00 |
February | 52303768.52 | 0.740843E+09 | 0.216714E+09 | 0.00 | 0.216714E+09 | 0.00 | 0.00 |
March | 0.174395E+09 | 0.672723E+09 | 0.354799E+09 | 0.00 | 0.354799E+09 | 0.00 | 0.00 |
April | 0.357954E+09 | 0.519502E+09 | 0.489146E+09 | 1754482.43 | 0.487392E+09 | 0.00 | 0.00 |
May | 0.553728E+09 | 0.462908E+09 | 0.648919E+09 | 19109191.94 | 0.629809E+09 | 0.00 | 0.00 |
June | 0.607115E+09 | 0.355740E+09 | 0.662694E+09 | 42798659.54 | 0.619895E+09 | 0.00 | 0.00 |
July | 0.673766E+09 | 0.341245E+09 | 0.655517E+09 | 50659410.92 | 0.604857E+09 | 0.00 | 0.00 |
August | 0.555215E+09 | 0.342359E+09 | 0.530071E+09 | 14267543.40 | 0.515803E+09 | 0.00 | 0.00 |
September | 0.307323E+09 | 0.487506E+09 | 0.397136E+09 | 120604.04 | 0.397015E+09 | 0.00 | 0.00 |
October | 0.126454E+09 | 0.664491E+09 | 0.279187E+09 | 0.00 | 0.279187E+09 | 0.00 | 0.00 |
November | 22192188.50 | 0.780602E+09 | 0.167714E+09 | 0.00 | 0.167714E+09 | 0.00 | 0.00 |
December | 4285751.51 | 0.959739E+09 | 0.130595E+09 | 0.00 | 0.130595E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.344114E+10 | 0.726972E+10 | 0.468545E+10 | 0.128710E+09 | 0.455674E+10 | 0.00 | 0.00 |
Minimum of Months | 4285751.51 | 0.341245E+09 | 0.130595E+09 | 0.00 | 0.130595E+09 | 0.00 | 0.00 |
Maximum of Months | 0.673766E+09 | 0.959739E+09 | 0.662694E+09 | 50659410.92 | 0.629809E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_ZN_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 82958844.08 | 0.603924E+09 | 0.176873E+09 | 54370167.33 | 0.122502E+09 | 0.00 | 0.00 |
February | 0.216861E+09 | 0.478277E+09 | 0.287716E+09 | 0.111147E+09 | 0.176569E+09 | 0.00 | 0.00 |
March | 0.386863E+09 | 0.451755E+09 | 0.441914E+09 | 0.152021E+09 | 0.289893E+09 | 0.00 | 0.00 |
April | 0.672075E+09 | 0.363509E+09 | 0.647241E+09 | 0.249135E+09 | 0.398106E+09 | 0.00 | 0.00 |
May | 0.949255E+09 | 0.338095E+09 | 0.855015E+09 | 0.349761E+09 | 0.505254E+09 | 0.00 | 0.00 |
June | 0.892753E+09 | 0.264778E+09 | 0.793911E+09 | 0.306082E+09 | 0.487829E+09 | 0.00 | 0.00 |
July | 0.125913E+10 | 0.264265E+09 | 0.102463E+10 | 0.539480E+09 | 0.485155E+09 | 0.00 | 0.00 |
August | 0.106860E+10 | 0.261568E+09 | 0.854294E+09 | 0.438274E+09 | 0.416021E+09 | 0.00 | 0.00 |
September | 0.779582E+09 | 0.345401E+09 | 0.678172E+09 | 0.329161E+09 | 0.349011E+09 | 0.00 | 0.00 |
October | 0.368395E+09 | 0.454646E+09 | 0.399000E+09 | 0.165966E+09 | 0.233034E+09 | 0.00 | 0.00 |
November | 0.107115E+09 | 0.512275E+09 | 0.190852E+09 | 56034641.69 | 0.134817E+09 | 0.00 | 0.00 |
December | 98512371.83 | 0.623807E+09 | 0.167435E+09 | 59542696.96 | 0.107892E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.688210E+10 | 0.496230E+10 | 0.651706E+10 | 0.281097E+10 | 0.370608E+10 | 0.00 | 0.00 |
Minimum of Months | 82958844.08 | 0.261568E+09 | 0.167435E+09 | 54370167.33 | 0.107892E+09 | 0.00 | 0.00 |
Maximum of Months | 0.125913E+10 | 0.623807E+09 | 0.102463E+10 | 0.539480E+09 | 0.505254E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.621996E+09 | -493883531.0 | 0.00 | 0.00 | 744.00 | 0.00 | -128112279.8 | 60.05 | 0.00 | 0.00 |
February | 0.563485E+09 | -449915357.3 | 0.00 | 0.00 | 672.00 | 0.00 | -113569485.1 | 60.05 | 0.00 | 0.00 |
March | 0.659506E+09 | -538454772.4 | 0.00 | 0.00 | 744.00 | 0.00 | -121051705.7 | 60.05 | 0.00 | 0.00 |
April | 0.570471E+09 | -455724916.7 | 0.00 | 0.00 | 720.00 | 0.00 | -114746455.5 | 60.05 | 0.00 | 0.00 |
May | 0.599185E+09 | -483456854.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115728080.6 | 60.05 | 0.00 | 0.00 |
June | 0.575238E+09 | -464662162.5 | 0.00 | 0.00 | 720.00 | 0.00 | -110575410.8 | 60.05 | 0.00 | 0.00 |
July | 0.523931E+09 | -410957452.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112973073.2 | 60.05 | 0.00 | 0.00 |
August | 0.581860E+09 | -468898784.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112961581.5 | 60.05 | 0.00 | 0.00 |
September | 0.523625E+09 | -413389293.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110235774.1 | 60.05 | 0.00 | 0.00 |
October | 0.564285E+09 | -447475505.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116809504.8 | 60.05 | 0.00 | 0.00 |
November | 0.582544E+09 | -464840366.1 | 0.00 | 0.00 | 720.00 | 0.00 | -117703386.4 | 60.05 | 0.00 | 0.00 |
December | 0.584775E+09 | -458687491.9 | 0.00 | 0.00 | 744.00 | 0.00 | -126087051.1 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.695090E+10 | -0.555035E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140055E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.523625E+09 | -538454772.4 | 0.00 | 0.00 | 672.00 | 0.00 | -128112279.8 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.659506E+09 | -410957452.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110235774.1 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.82 | 0.73 | 03-JAN-09:50 | 449.67 | 21.17 | 68.00 | 112.00 | 787.09 | 28.04 | 180.33 | 99.83 |
February | 259.50 | 0.79 | 0.73 | 01-FEB-08:50 | 1073.04 | 25.08 | 122.67 | 176.67 | 1209.28 | 30.43 | 234.50 | 160.50 |
March | 247.00 | 0.78 | 0.73 | 01-MAR-07:40 | 1760.64 | 25.58 | 117.83 | 216.00 | 717.49 | 23.16 | 207.67 | 155.83 |
April | 379.50 | 0.80 | 0.73 | 01-APR-08:30 | 587.56 | 17.72 | 0.00 | 249.00 | 452.05 | 22.04 | 253.50 | 202.00 |
May | 427.83 | 0.80 | 0.73 | 01-MAY-09:20 | 516.34 | 17.55 | 1.00 | 260.67 | 386.62 | 21.82 | 272.17 | 197.50 |
June | 375.17 | 0.80 | 0.73 | 01-JUN-09:39 | 458.84 | 17.17 | 0.00 | 262.67 | 344.17 | 21.44 | 279.67 | 171.67 |
July | 471.00 | 0.83 | 0.73 | 01-JUL-11:50 | 407.88 | 15.92 | 0.00 | 234.33 | 310.39 | 20.16 | 207.83 | 184.00 |
August | 366.67 | 0.80 | 0.73 | 01-AUG-07:00 | 511.04 | 17.03 | 0.17 | 255.00 | 398.29 | 21.34 | 242.83 | 194.67 |
September | 301.17 | 0.78 | 0.73 | 01-SEP-11:50 | 823.99 | 19.06 | 11.83 | 229.67 | 568.58 | 22.88 | 238.67 | 190.67 |
October | 245.33 | 0.77 | 0.73 | 01-OCT-11:39 | 1628.21 | 25.10 | 106.67 | 207.83 | 769.97 | 23.35 | 191.83 | 171.33 |
November | 242.67 | 0.82 | 0.73 | 01-NOV-12:09 | 624.59 | 23.41 | 99.00 | 122.33 | 903.15 | 28.84 | 193.67 | 106.00 |
December | 160.33 | 0.80 | 0.73 | 01-DEC-09:00 | 607.94 | 20.54 | 35.83 | 95.67 | 1182.03 | 32.71 | 144.17 | 105.17 |
Annual Sum or Average | 3714.00 | 0.80 | 730.33 | 19.70 | 563.00 | 2421.83 | 593.80 | 23.75 | 2646.83 | 1939.17 | ||
Minimum of Months | 160.33 | 0.77 | 0.73 | 407.88 | 15.92 | 0.00 | 95.67 | 310.39 | 20.16 | 144.17 | 99.83 | |
Maximum of Months | 471.00 | 0.83 | 0.73 | 1760.64 | 25.58 | 122.67 | 262.67 | 1209.28 | 32.71 | 279.67 | 202.00 |
Report: DaylightingReportMonthly
For: PERIMETER_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.89 | 0.73 | 03-JAN-10:30 | 352.92 | 18.93 | 65.33 | 45.33 | 189.95 | 20.66 | 65.33 | 17.67 |
February | 259.50 | 0.86 | 0.73 | 01-FEB-09:09 | 572.79 | 17.91 | 45.33 | 89.67 | 378.43 | 22.97 | 117.67 | 50.17 |
March | 247.00 | 0.83 | 0.73 | 01-MAR-07:49 | 996.00 | 18.73 | 39.17 | 121.00 | 362.73 | 20.90 | 118.83 | 79.00 |
April | 379.50 | 0.83 | 0.73 | 01-APR-07:10 | 434.44 | 16.01 | 0.00 | 178.50 | 342.47 | 20.60 | 167.00 | 124.33 |
May | 427.83 | 0.82 | 0.73 | 01-MAY-09:09 | 428.95 | 16.16 | 0.00 | 205.50 | 338.84 | 20.84 | 206.17 | 143.33 |
June | 375.17 | 0.82 | 0.73 | 01-JUN-05:49 | 447.46 | 15.81 | 0.00 | 191.50 | 397.07 | 22.04 | 212.67 | 141.33 |
July | 471.00 | 0.85 | 0.73 | 01-JUL-12:20 | 366.56 | 14.56 | 0.00 | 174.83 | 312.17 | 20.99 | 184.00 | 125.33 |
August | 366.67 | 0.83 | 0.73 | 01-AUG-06:10 | 414.87 | 15.17 | 0.00 | 173.33 | 350.60 | 20.24 | 143.50 | 121.67 |
September | 301.17 | 0.83 | 0.73 | 02-SEP-06:49 | 471.49 | 16.55 | 7.00 | 131.00 | 353.92 | 21.21 | 131.17 | 82.33 |
October | 245.33 | 0.84 | 0.73 | 01-OCT-08:20 | 1327.59 | 20.00 | 62.83 | 106.00 | 487.06 | 22.48 | 112.33 | 71.00 |
November | 242.67 | 0.88 | 0.73 | 02-NOV-07:00 | 503.85 | 19.12 | 70.17 | 50.17 | 188.72 | 20.51 | 61.50 | 23.00 |
December | 160.33 | 0.87 | 0.73 | 01-DEC-10:30 | 512.07 | 21.22 | 56.83 | 44.50 | 171.71 | 18.99 | 30.67 | 13.00 |
Annual Sum or Average | 3714.00 | 0.84 | 536.26 | 16.98 | 346.67 | 1511.33 | 331.68 | 21.08 | 1550.83 | 992.17 | ||
Minimum of Months | 160.33 | 0.82 | 0.73 | 352.92 | 14.56 | 0.00 | 44.50 | 171.71 | 18.99 | 30.67 | 13.00 | |
Maximum of Months | 471.00 | 0.89 | 0.73 | 1327.59 | 21.22 | 70.17 | 205.50 | 487.06 | 22.97 | 212.67 | 143.33 |
Report: DaylightingReportMonthly
For: PERIMETER_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.96 | 0.91 | 06-JAN-11:20 | 122.23 | 12.23 | 0.00 | 0.00 | 85.00 | 15.99 | 0.00 | 0.00 |
February | 259.50 | 0.94 | 0.83 | 14-FEB-13:50 | 155.77 | 13.47 | 0.00 | 0.00 | 109.95 | 17.36 | 0.00 | 0.00 |
March | 247.00 | 0.90 | 0.74 | 15-MAR-14:20 | 213.59 | 15.04 | 0.00 | 5.67 | 152.49 | 19.00 | 10.33 | 0.00 |
April | 379.50 | 0.87 | 0.74 | 10-APR-15:30 | 251.29 | 15.88 | 0.00 | 15.17 | 175.50 | 19.70 | 44.33 | 0.00 |
May | 427.83 | 0.83 | 0.73 | 13-MAY-05:30 | 326.39 | 16.82 | 1.33 | 134.00 | 217.72 | 21.27 | 184.33 | 5.17 |
June | 375.17 | 0.82 | 0.73 | 04-JUN-08:20 | 332.52 | 18.25 | 25.17 | 128.33 | 246.74 | 22.35 | 209.00 | 14.83 |
July | 471.00 | 0.86 | 0.74 | 01-JUL-12:30 | 276.13 | 17.20 | 33.83 | 117.50 | 186.37 | 19.42 | 141.50 | 0.00 |
August | 366.67 | 0.87 | 0.74 | 01-AUG-07:49 | 264.56 | 15.79 | 0.00 | 35.83 | 173.15 | 19.64 | 42.33 | 0.00 |
September | 301.17 | 0.88 | 0.74 | 02-SEP-13:30 | 236.16 | 15.84 | 0.00 | 6.33 | 169.23 | 19.80 | 16.50 | 0.00 |
October | 245.33 | 0.92 | 0.74 | 02-OCT-09:30 | 172.94 | 13.94 | 0.00 | 0.17 | 126.28 | 17.95 | 0.83 | 0.00 |
November | 242.67 | 0.95 | 0.91 | 01-NOV-11:50 | 131.52 | 12.61 | 0.00 | 0.00 | 91.11 | 16.31 | 0.00 | 0.00 |
December | 160.33 | 0.96 | 0.91 | 01-DEC-10:20 | 115.88 | 12.05 | 0.00 | 0.00 | 85.01 | 16.18 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.88 | 235.09 | 15.42 | 60.33 | 443.00 | 163.62 | 19.18 | 649.17 | 20.00 | ||
Minimum of Months | 160.33 | 0.82 | 0.73 | 115.88 | 12.05 | 0.00 | 0.00 | 85.00 | 15.99 | 0.00 | 0.00 | |
Maximum of Months | 471.00 | 0.96 | 0.91 | 332.52 | 18.25 | 33.83 | 134.00 | 246.74 | 22.35 | 209.00 | 14.83 |
Report: DaylightingReportMonthly
For: PERIMETER_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.89 | 0.73 | 05-JAN-14:39 | 339.56 | 19.12 | 58.50 | 43.50 | 174.81 | 20.66 | 56.83 | 16.50 |
February | 259.50 | 0.86 | 0.73 | 01-FEB-13:30 | 583.77 | 18.28 | 45.17 | 82.83 | 350.94 | 22.92 | 112.83 | 50.67 |
March | 247.00 | 0.83 | 0.73 | 01-MAR-13:20 | 898.77 | 18.96 | 39.33 | 114.83 | 573.46 | 23.11 | 121.50 | 84.00 |
April | 379.50 | 0.83 | 0.73 | 01-APR-13:09 | 427.59 | 16.23 | 0.00 | 176.00 | 331.96 | 20.68 | 177.83 | 119.17 |
May | 427.83 | 0.82 | 0.73 | 01-MAY-11:00 | 462.04 | 16.44 | 0.33 | 219.00 | 372.71 | 21.01 | 224.00 | 152.50 |
June | 375.17 | 0.82 | 0.73 | 01-JUN-13:30 | 434.43 | 16.07 | 0.00 | 194.67 | 399.15 | 20.85 | 202.33 | 140.00 |
July | 471.00 | 0.84 | 0.73 | 01-JUL-12:20 | 414.93 | 14.75 | 0.00 | 202.83 | 352.12 | 19.53 | 170.83 | 161.00 |
August | 366.67 | 0.83 | 0.73 | 02-AUG-11:30 | 434.73 | 15.43 | 0.00 | 181.00 | 367.85 | 20.34 | 158.83 | 132.83 |
September | 301.17 | 0.82 | 0.73 | 01-SEP-12:20 | 665.18 | 17.26 | 8.67 | 155.33 | 458.70 | 21.78 | 160.83 | 117.83 |
October | 245.33 | 0.84 | 0.73 | 01-OCT-12:20 | 1243.31 | 20.56 | 66.83 | 113.00 | 462.46 | 23.18 | 128.83 | 75.33 |
November | 242.67 | 0.88 | 0.73 | 02-NOV-13:09 | 480.84 | 19.17 | 67.50 | 52.17 | 181.24 | 20.00 | 56.50 | 19.17 |
December | 160.33 | 0.88 | 0.73 | 01-DEC-13:20 | 539.36 | 20.14 | 47.50 | 41.17 | 169.00 | 18.83 | 34.67 | 13.17 |
Annual Sum or Average | 3714.00 | 0.84 | 549.41 | 17.21 | 333.83 | 1576.33 | 358.88 | 21.00 | 1605.83 | 1082.17 | ||
Minimum of Months | 160.33 | 0.82 | 0.73 | 339.56 | 14.75 | 0.00 | 41.17 | 169.00 | 18.83 | 34.67 | 13.17 | |
Maximum of Months | 471.00 | 0.89 | 0.73 | 1243.31 | 20.56 | 67.50 | 219.00 | 573.46 | 23.18 | 224.00 | 161.00 |
Report: CoilReportMonthly
For: PSZ-AC:1 HEATING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.508352E+09 | 8966.89 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.194107E+09 | 8966.89 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9865839.03 | 8966.89 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32736717.31 | 8966.89 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213936E+09 | 8966.89 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.958997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.508352E+09 | 8966.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 HEATING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145625E+10 | 11111.35 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.757248E+09 | 11111.35 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.304149E+09 | 11111.35 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140233E+09 | 11111.35 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15734301.60 | 2572.84 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 97644.30 | 162.74 | 28-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23614023.54 | 2160.34 | 16-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371307E+09 | 11111.35 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.961829E+09 | 11111.35 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.403046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145625E+10 | 11111.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 HEATING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.937713E+09 | 6524.87 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.540831E+09 | 6524.87 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176292E+09 | 6524.87 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44433402.22 | 6524.87 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 611857.00 | 957.75 | 30-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6096022.01 | 2759.20 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206477E+09 | 6524.87 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.603741E+09 | 6524.87 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.937713E+09 | 6524.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 HEATING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.166983E+10 | 7318.69 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111193E+10 | 7318.69 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.459801E+09 | 7318.69 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144875E+09 | 7318.69 | 10-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1151221.72 | 1032.46 | 30-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23583802.48 | 7091.85 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.434137E+09 | 7318.69 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114036E+10 | 7318.69 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.498566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.166983E+10 | 7318.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:5 HEATING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.848840E+09 | 7561.68 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492952E+09 | 7561.68 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160949E+09 | 7561.68 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42363947.43 | 7561.68 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3661346.59 | 2422.97 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170496E+09 | 7561.68 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.522062E+09 | 7561.68 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.848840E+09 | 7561.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 4451820.05 | 3388177.90 | 500.71 | 28-FEB-16:55 | 380.72 | 0.00 |
March | 0.00 | 0.00 | 79028896.35 | 66390486.67 | 1225.93 | 10-MAR-14:15 | 931.42 | 0.00 |
April | 0.00 | 0.00 | 0.477673E+09 | 0.413101E+09 | 5510.10 | 28-APR-05:03 | 4516.54 | 0.00 |
May | 0.00 | 0.00 | 0.141001E+10 | 0.118724E+10 | 5580.52 | 08-MAY-05:03 | 4263.38 | 0.00 |
June | 0.00 | 0.00 | 0.206563E+10 | 0.176200E+10 | 5603.55 | 13-JUN-05:03 | 4203.86 | 0.00 |
July | 0.00 | 0.00 | 0.257738E+10 | 0.215995E+10 | 5624.11 | 28-JUL-05:02 | 4418.98 | 0.00 |
August | 0.00 | 0.00 | 0.329289E+10 | 0.271006E+10 | 5616.81 | 10-AUG-05:02 | 4549.67 | 0.00 |
September | 0.00 | 0.00 | 0.201685E+10 | 0.163521E+10 | 5602.95 | 26-SEP-05:03 | 4158.95 | 0.00 |
October | 0.00 | 0.00 | 0.872509E+09 | 0.744466E+09 | 5461.49 | 06-OCT-05:03 | 4712.98 | 0.00 |
November | 0.00 | 0.00 | 0.222964E+09 | 0.171324E+09 | 1489.86 | 03-NOV-16:00 | 1048.96 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130194E+11 | 0.108531E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.329289E+10 | 0.271006E+10 | 5624.11 | 4712.98 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 38943961.75 | 38344515.63 | 1672.05 | 27-FEB-15:00 | 1672.05 | 0.00 |
March | 0.00 | 0.00 | 0.134368E+09 | 0.133503E+09 | 1875.90 | 02-MAR-14:25 | 1875.90 | 0.00 |
April | 0.00 | 0.00 | 0.378502E+09 | 0.364498E+09 | 4280.14 | 27-APR-14:30 | 4038.66 | 0.00 |
May | 0.00 | 0.00 | 0.675463E+09 | 0.629893E+09 | 3262.74 | 04-MAY-14:00 | 3061.32 | 0.00 |
June | 0.00 | 0.00 | 0.109834E+10 | 0.102101E+10 | 3903.43 | 29-JUN-05:02 | 3578.60 | 0.00 |
July | 0.00 | 0.00 | 0.181264E+10 | 0.162865E+10 | 7312.76 | 31-JUL-05:02 | 6814.83 | 0.00 |
August | 0.00 | 0.00 | 0.276094E+10 | 0.244378E+10 | 7379.17 | 25-AUG-05:02 | 6508.88 | 0.00 |
September | 0.00 | 0.00 | 0.177535E+10 | 0.159464E+10 | 7324.51 | 15-SEP-05:02 | 6612.42 | 0.00 |
October | 0.00 | 0.00 | 0.756652E+09 | 0.738462E+09 | 5094.81 | 04-OCT-13:50 | 5094.81 | 0.00 |
November | 0.00 | 0.00 | 61134930.74 | 56258991.78 | 1462.50 | 02-NOV-13:30 | 1316.57 | 0.00 |
December | 0.00 | 0.00 | 11158439.86 | 11158439.86 | 1003.35 | 05-DEC-13:20 | 1003.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.950350E+10 | 0.866019E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.276094E+10 | 0.244378E+10 | 7379.17 | 6814.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.152600E+09 | 0.147401E+09 | 1697.83 | 27-APR-15:20 | 1597.80 | 0.00 |
May | 0.00 | 0.00 | 0.419626E+09 | 0.396901E+09 | 1774.10 | 15-MAY-10:10 | 1747.41 | 0.00 |
June | 0.00 | 0.00 | 0.872038E+09 | 0.823438E+09 | 2430.94 | 29-JUN-05:02 | 2228.01 | 0.00 |
July | 0.00 | 0.00 | 0.118172E+10 | 0.108581E+10 | 4281.38 | 31-JUL-05:02 | 3936.74 | 0.00 |
August | 0.00 | 0.00 | 0.160575E+10 | 0.144669E+10 | 4319.00 | 25-AUG-05:02 | 3761.45 | 0.00 |
September | 0.00 | 0.00 | 0.784849E+09 | 0.705299E+09 | 4244.20 | 12-SEP-05:02 | 3879.30 | 0.00 |
October | 0.00 | 0.00 | 0.194979E+09 | 0.190804E+09 | 1370.65 | 04-OCT-10:02 | 1370.65 | 0.00 |
November | 0.00 | 0.00 | 2857553.29 | 2457136.62 | 237.08 | 02-NOV-14:20 | 213.98 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.521442E+10 | 0.479879E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.160575E+10 | 0.144669E+10 | 4319.00 | 3936.74 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 72286139.11 | 65668317.82 | 1928.18 | 27-APR-15:55 | 1769.66 | 0.00 |
May | 0.00 | 0.00 | 0.372544E+09 | 0.334544E+09 | 2231.00 | 05-MAY-16:00 | 1931.42 | 0.00 |
June | 0.00 | 0.00 | 0.890938E+09 | 0.808123E+09 | 2646.02 | 28-JUN-16:00 | 2503.09 | 0.00 |
July | 0.00 | 0.00 | 0.139126E+10 | 0.122483E+10 | 4481.83 | 26-JUL-05:02 | 3816.76 | 0.00 |
August | 0.00 | 0.00 | 0.184239E+10 | 0.158748E+10 | 4511.04 | 25-AUG-05:02 | 3844.97 | 0.00 |
September | 0.00 | 0.00 | 0.794261E+09 | 0.671881E+09 | 3411.47 | 14-SEP-05:02 | 2931.32 | 0.00 |
October | 0.00 | 0.00 | 0.122628E+09 | 0.117519E+09 | 1406.50 | 04-OCT-15:27 | 1406.50 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.548630E+10 | 0.481004E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.184239E+10 | 0.158748E+10 | 4511.04 | 3844.97 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:5 COOLING COIL
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1368665.39 | 1345889.05 | 369.99 | 27-FEB-16:35 | 361.29 | 0.00 |
March | 0.00 | 0.00 | 11567851.10 | 11489250.68 | 603.80 | 14-MAR-16:00 | 597.16 | 0.00 |
April | 0.00 | 0.00 | 0.156033E+09 | 0.147425E+09 | 2410.87 | 27-APR-15:53 | 2249.35 | 0.00 |
May | 0.00 | 0.00 | 0.500152E+09 | 0.463106E+09 | 2502.68 | 15-MAY-15:57 | 2502.68 | 0.00 |
June | 0.00 | 0.00 | 0.851142E+09 | 0.789245E+09 | 4805.60 | 23-JUN-05:02 | 4569.73 | 0.00 |
July | 0.00 | 0.00 | 0.127891E+10 | 0.115788E+10 | 5087.28 | 31-JUL-05:02 | 4786.13 | 0.00 |
August | 0.00 | 0.00 | 0.161646E+10 | 0.143438E+10 | 5124.10 | 25-AUG-05:02 | 4581.61 | 0.00 |
September | 0.00 | 0.00 | 0.873262E+09 | 0.773025E+09 | 5048.43 | 13-SEP-05:02 | 4597.40 | 0.00 |
October | 0.00 | 0.00 | 0.237879E+09 | 0.229005E+09 | 2256.92 | 04-OCT-15:57 | 2256.92 | 0.00 |
November | 0.00 | 0.00 | 12720764.56 | 10895264.76 | 396.52 | 02-NOV-14:30 | 339.93 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.553950E+10 | 0.501780E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.161646E+10 | 0.143438E+10 | 5124.10 | 4786.13 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 268.44 | 639.75 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 114.37 | 640.76 | 10-FEB-12:13 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 31.57 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 268.44 | 640.76 |
Report: FanReportMonthly
For: PSZ-AC:1 FAN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.342794E+09 | 0.34 | 348.79 | 02-JAN-06:01 | 0.93 |
February | 0.310147E+09 | 0.34 | 348.79 | 01-FEB-06:01 | 0.92 |
March | 0.375441E+09 | 0.37 | 348.79 | 01-MAR-06:02 | 0.92 |
April | 0.326470E+09 | 0.33 | 348.79 | 03-APR-05:03 | 0.92 |
May | 0.359117E+09 | 0.36 | 348.79 | 01-MAY-05:10 | 0.92 |
June | 0.359117E+09 | 0.37 | 348.79 | 01-JUN-05:05 | 0.92 |
July | 0.326470E+09 | 0.32 | 348.79 | 03-JUL-05:03 | 0.92 |
August | 0.375441E+09 | 0.37 | 348.79 | 01-AUG-05:02 | 0.92 |
September | 0.326470E+09 | 0.33 | 348.79 | 01-SEP-05:02 | 0.92 |
October | 0.342794E+09 | 0.34 | 348.79 | 02-OCT-05:05 | 0.92 |
November | 0.342794E+09 | 0.35 | 348.79 | 01-NOV-05:05 | 0.92 |
December | 0.326470E+09 | 0.32 | 348.79 | 01-DEC-06:01 | 0.92 |
Annual Sum or Average | 0.411352E+10 | 0.35 | |||
Minimum of Months | 0.310147E+09 | 0.32 | 348.79 | 0.92 | |
Maximum of Months | 0.375441E+09 | 0.37 | 348.79 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:2 FAN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.472937E+09 | 0.36 | 478.85 | 02-JAN-06:01 | 0.93 |
February | 0.425797E+09 | 0.34 | 478.85 | 01-FEB-06:01 | 0.93 |
March | 0.515439E+09 | 0.37 | 478.85 | 01-MAR-06:02 | 0.93 |
April | 0.448208E+09 | 0.34 | 478.85 | 03-APR-05:03 | 0.93 |
May | 0.493028E+09 | 0.36 | 478.85 | 01-MAY-05:10 | 0.93 |
June | 0.493028E+09 | 0.37 | 478.85 | 01-JUN-05:05 | 0.92 |
July | 0.448208E+09 | 0.32 | 478.85 | 03-JUL-05:03 | 0.93 |
August | 0.515439E+09 | 0.37 | 478.85 | 01-AUG-05:02 | 0.92 |
September | 0.448208E+09 | 0.33 | 478.85 | 01-SEP-05:02 | 0.92 |
October | 0.470618E+09 | 0.34 | 478.85 | 02-OCT-05:05 | 0.92 |
November | 0.470618E+09 | 0.35 | 478.85 | 01-NOV-05:05 | 0.93 |
December | 0.448208E+09 | 0.32 | 478.85 | 01-DEC-06:01 | 0.93 |
Annual Sum or Average | 0.564973E+10 | 0.35 | |||
Minimum of Months | 0.425797E+09 | 0.32 | 478.85 | 0.92 | |
Maximum of Months | 0.515439E+09 | 0.37 | 478.85 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:3 FAN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.278449E+09 | 0.38 | 280.75 | 02-JAN-06:01 | 0.93 |
February | 0.250206E+09 | 0.35 | 280.75 | 01-FEB-06:01 | 0.93 |
March | 0.302204E+09 | 0.37 | 280.75 | 01-MAR-06:02 | 0.93 |
April | 0.262786E+09 | 0.34 | 280.75 | 03-APR-05:03 | 0.93 |
May | 0.289065E+09 | 0.36 | 280.75 | 01-MAY-05:10 | 0.93 |
June | 0.289065E+09 | 0.37 | 280.75 | 01-JUN-05:05 | 0.92 |
July | 0.262786E+09 | 0.32 | 280.75 | 03-JUL-05:03 | 0.93 |
August | 0.302204E+09 | 0.37 | 280.75 | 01-AUG-05:02 | 0.92 |
September | 0.262786E+09 | 0.33 | 280.75 | 01-SEP-05:02 | 0.92 |
October | 0.275925E+09 | 0.34 | 280.75 | 02-OCT-05:05 | 0.92 |
November | 0.275925E+09 | 0.35 | 280.75 | 01-NOV-05:05 | 0.93 |
December | 0.263043E+09 | 0.33 | 280.75 | 01-DEC-06:01 | 0.93 |
Annual Sum or Average | 0.331444E+10 | 0.35 | |||
Minimum of Months | 0.250206E+09 | 0.32 | 280.75 | 0.92 | |
Maximum of Months | 0.302204E+09 | 0.38 | 280.75 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:4 FAN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.289023E+09 | 0.38 | 290.31 | 02-JAN-06:01 | 0.93 |
February | 0.259758E+09 | 0.36 | 290.31 | 01-FEB-06:01 | 0.93 |
March | 0.312492E+09 | 0.37 | 290.31 | 01-MAR-06:02 | 0.93 |
April | 0.271732E+09 | 0.34 | 290.31 | 03-APR-05:03 | 0.93 |
May | 0.298906E+09 | 0.36 | 290.31 | 01-MAY-05:10 | 0.93 |
June | 0.298906E+09 | 0.37 | 290.31 | 01-JUN-05:05 | 0.92 |
July | 0.271732E+09 | 0.32 | 290.31 | 03-JUL-05:03 | 0.93 |
August | 0.312492E+09 | 0.37 | 290.31 | 01-AUG-05:02 | 0.92 |
September | 0.271732E+09 | 0.33 | 290.31 | 01-SEP-05:02 | 0.92 |
October | 0.285319E+09 | 0.34 | 290.31 | 02-OCT-05:05 | 0.92 |
November | 0.285319E+09 | 0.35 | 290.31 | 01-NOV-05:05 | 0.93 |
December | 0.272092E+09 | 0.33 | 290.31 | 01-DEC-06:01 | 0.93 |
Annual Sum or Average | 0.342950E+10 | 0.35 | |||
Minimum of Months | 0.259758E+09 | 0.32 | 290.31 | 0.92 | |
Maximum of Months | 0.312492E+09 | 0.38 | 290.31 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:5 FAN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.329165E+09 | 0.38 | 332.30 | 02-JAN-06:01 | 0.93 |
February | 0.296110E+09 | 0.35 | 332.30 | 01-FEB-06:01 | 0.93 |
March | 0.357684E+09 | 0.37 | 332.30 | 01-MAR-06:02 | 0.93 |
April | 0.311030E+09 | 0.34 | 332.30 | 03-APR-05:03 | 0.93 |
May | 0.342133E+09 | 0.36 | 332.30 | 01-MAY-05:10 | 0.93 |
June | 0.342133E+09 | 0.37 | 332.30 | 01-JUN-05:05 | 0.92 |
July | 0.311030E+09 | 0.32 | 332.30 | 03-JUL-05:03 | 0.93 |
August | 0.357684E+09 | 0.37 | 332.30 | 01-AUG-05:02 | 0.92 |
September | 0.311030E+09 | 0.33 | 332.30 | 01-SEP-05:02 | 0.92 |
October | 0.326581E+09 | 0.34 | 332.30 | 02-OCT-05:05 | 0.92 |
November | 0.326581E+09 | 0.35 | 332.30 | 01-NOV-05:05 | 0.93 |
December | 0.311298E+09 | 0.33 | 332.30 | 01-DEC-06:01 | 0.93 |
Annual Sum or Average | 0.392246E+10 | 0.35 | |||
Minimum of Months | 0.296110E+09 | 0.32 | 332.30 | 0.92 | |
Maximum of Months | 0.357684E+09 | 0.38 | 332.30 | 0.93 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.02 | 0.01 | 0.00 | 02-JAN-07:10 | 0.00 | 0.00 | 31.44 | 0.00 |
February | 0.01 | 0.00 | 0.00 | 01-FEB-07:10 | 0.00 | 0.00 | 11.16 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 11.10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 11.10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 11.10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 11.10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 11.10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 11.10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 11.10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 11.10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 11.10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 11.10 | 0.00 |
Annual Sum or Average | 0.03 | 0.01 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 | 0.00 | |
Maximum of Months | 0.02 | 0.01 | 0.00 | 0.00 | 0.00 | 31.44 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48.89 | 48.89 | 268.44 | 639.75 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.16 | 11.16 | 114.37 | 640.76 | 10-FEB-12:13 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.10 | 11.10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.10 | 11.10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 11.10 | 11.10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.10 | 11.10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.10 | 11.10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.10 | 11.10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 11.10 | 11.10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.10 | 11.10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 11.10 | 11.10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 11.10 | 11.10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 31.57 | ||||||
Minimum of Months | 0.00 | 0.00 | 11.10 | 11.10 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 48.89 | 48.89 | 268.44 | 640.76 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_ZN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_ZN_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_ZN_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_ZN_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_ZN_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.342794E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.311240E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.394671E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.440708E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.690141E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.836214E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.914796E+09 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.113066E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.788509E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.549388E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.396482E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.326470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.712207E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.311240E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.113066E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.472937E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.435255E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.547862E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.539672E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.655498E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.756587E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.880160E+09 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.117432E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.857912E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.647577E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.485549E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.450925E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.790425E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.435255E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.117432E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.278449E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.250206E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.302204E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.300138E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.390292E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.496689E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.543152E+09 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.685699E+09 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.448077E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.322885E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.276630E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.263043E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.455746E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.250206E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.685699E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.289023E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.259758E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.312492E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.289623E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.388543E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.510341E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.598800E+09 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.749282E+09 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.459143E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.314823E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.285319E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.272092E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.472924E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.259758E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.749282E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:5
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.329165E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.296447E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.360521E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.349337E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.462858E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.546521E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.616859E+09 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.749293E+09 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.518715E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.383860E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.329717E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.311298E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.525459E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.296447E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.749293E+09 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.342794E+09 | 0.00 | 0.508352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310147E+09 | 4451820.05 | 0.194107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.375441E+09 | 79028896.35 | 9865839.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.326470E+09 | 0.477673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.359117E+09 | 0.141001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.359117E+09 | 0.206563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.326470E+09 | 0.257738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.375441E+09 | 0.329289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.326470E+09 | 0.201685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.342794E+09 | 0.872509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.342794E+09 | 0.222964E+09 | 32736717.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.326470E+09 | 0.00 | 0.213936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.411352E+10 | 0.130194E+11 | 0.958997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.310147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.375441E+09 | 0.329289E+10 | 0.508352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.472937E+09 | 0.00 | 0.145625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425797E+09 | 38943961.75 | 0.757248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.515439E+09 | 0.134368E+09 | 0.304149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.448208E+09 | 0.378502E+09 | 0.140233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.493028E+09 | 0.675463E+09 | 15734301.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.493028E+09 | 0.109834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.448208E+09 | 0.181264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.515439E+09 | 0.276094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.448208E+09 | 0.177535E+10 | 97644.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.470618E+09 | 0.756652E+09 | 23614023.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.470618E+09 | 61134930.74 | 0.371307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.448208E+09 | 11158439.86 | 0.961829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.564973E+10 | 0.950350E+10 | 0.403046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.425797E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.515439E+09 | 0.276094E+10 | 0.145625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.278449E+09 | 0.00 | 0.937713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.250206E+09 | 0.00 | 0.540831E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302204E+09 | 0.00 | 0.176292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262786E+09 | 0.152600E+09 | 44433402.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.289065E+09 | 0.419626E+09 | 611857.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.289065E+09 | 0.872038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.262786E+09 | 0.118172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.302204E+09 | 0.160575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262786E+09 | 0.784849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275925E+09 | 0.194979E+09 | 6096022.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275925E+09 | 2857553.29 | 0.206477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263043E+09 | 0.00 | 0.603741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331444E+10 | 0.521442E+10 | 0.251619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.250206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.302204E+09 | 0.160575E+10 | 0.937713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.289023E+09 | 0.00 | 0.166983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259758E+09 | 0.00 | 0.111193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.312492E+09 | 0.00 | 0.459801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.271732E+09 | 72286139.11 | 0.144875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.298906E+09 | 0.372544E+09 | 1151221.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.298906E+09 | 0.890938E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271732E+09 | 0.139126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.312492E+09 | 0.184239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.271732E+09 | 0.794261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285319E+09 | 0.122628E+09 | 23583802.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285319E+09 | 0.00 | 0.434137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272092E+09 | 0.00 | 0.114036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342950E+10 | 0.548630E+10 | 0.498566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.259758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.312492E+09 | 0.184239E+10 | 0.166983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:5
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.329165E+09 | 0.00 | 0.848840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.296110E+09 | 1368665.39 | 0.492952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357684E+09 | 11567851.10 | 0.160949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.311030E+09 | 0.156033E+09 | 42363947.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.342133E+09 | 0.500152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.342133E+09 | 0.851142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.311030E+09 | 0.127891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.357684E+09 | 0.161646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.311030E+09 | 0.873262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.326581E+09 | 0.237879E+09 | 3661346.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326581E+09 | 12720764.56 | 0.170496E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311298E+09 | 0.00 | 0.522062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.392246E+10 | 0.553950E+10 | 0.224132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.296110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.357684E+09 | 0.161646E+10 | 0.848840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.342794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310147E+09 | 0.00 | 0.00 | 0.00 | 1093119.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.375441E+09 | 0.00 | 0.00 | 0.00 | 19230216.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.326470E+09 | 0.00 | 0.00 | 0.00 | 0.114238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.359117E+09 | 0.00 | 0.00 | 0.00 | 0.331024E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.359117E+09 | 0.00 | 0.00 | 0.00 | 0.477097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.326470E+09 | 0.00 | 0.00 | 0.00 | 0.588326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.375441E+09 | 0.00 | 0.00 | 0.00 | 0.755216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.326470E+09 | 0.00 | 0.00 | 0.00 | 0.462039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.342794E+09 | 0.00 | 0.00 | 0.00 | 0.206595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.342794E+09 | 0.00 | 0.00 | 0.00 | 53688618.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.326470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.411352E+10 | 0.00 | 0.00 | 0.00 | 0.300855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.310147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.375441E+09 | 0.00 | 0.00 | 0.00 | 0.755216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.472937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425797E+09 | 0.00 | 0.00 | 0.00 | 9457410.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.515439E+09 | 0.00 | 0.00 | 0.00 | 32423772.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.448208E+09 | 0.00 | 0.00 | 0.00 | 91464248.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.493028E+09 | 0.00 | 0.00 | 0.00 | 0.162470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.493028E+09 | 0.00 | 0.00 | 0.00 | 0.263559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.448208E+09 | 0.00 | 0.00 | 0.00 | 0.431953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.515439E+09 | 0.00 | 0.00 | 0.00 | 0.658876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.448208E+09 | 0.00 | 0.00 | 0.00 | 0.409705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.470618E+09 | 0.00 | 0.00 | 0.00 | 0.176959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.470618E+09 | 0.00 | 0.00 | 0.00 | 14930971.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.448208E+09 | 0.00 | 0.00 | 0.00 | 2717914.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.564973E+10 | 0.00 | 0.00 | 0.00 | 0.225452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.425797E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.515439E+09 | 0.00 | 0.00 | 0.00 | 0.658876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.278449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.250206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262786E+09 | 0.00 | 0.00 | 0.00 | 37351939.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.289065E+09 | 0.00 | 0.00 | 0.00 | 0.101227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.289065E+09 | 0.00 | 0.00 | 0.00 | 0.207625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.262786E+09 | 0.00 | 0.00 | 0.00 | 0.280366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.302204E+09 | 0.00 | 0.00 | 0.00 | 0.383495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262786E+09 | 0.00 | 0.00 | 0.00 | 0.185290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275925E+09 | 0.00 | 0.00 | 0.00 | 46959997.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275925E+09 | 0.00 | 0.00 | 0.00 | 705047.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331444E+10 | 0.00 | 0.00 | 0.00 | 0.124302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.250206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.302204E+09 | 0.00 | 0.00 | 0.00 | 0.383495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.289023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.312492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.271732E+09 | 0.00 | 0.00 | 0.00 | 17891039.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.298906E+09 | 0.00 | 0.00 | 0.00 | 89637874.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.298906E+09 | 0.00 | 0.00 | 0.00 | 0.211436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271732E+09 | 0.00 | 0.00 | 0.00 | 0.327068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.312492E+09 | 0.00 | 0.00 | 0.00 | 0.436790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.271732E+09 | 0.00 | 0.00 | 0.00 | 0.187411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285319E+09 | 0.00 | 0.00 | 0.00 | 29503659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272092E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342950E+10 | 0.00 | 0.00 | 0.00 | 0.129974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.259758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.312492E+09 | 0.00 | 0.00 | 0.00 | 0.436790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:5
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.329165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.296110E+09 | 0.00 | 0.00 | 0.00 | 337704.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357684E+09 | 0.00 | 0.00 | 0.00 | 2836637.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.311030E+09 | 0.00 | 0.00 | 0.00 | 38306847.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.342133E+09 | 0.00 | 0.00 | 0.00 | 0.120725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.342133E+09 | 0.00 | 0.00 | 0.00 | 0.204388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.311030E+09 | 0.00 | 0.00 | 0.00 | 0.305829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.357684E+09 | 0.00 | 0.00 | 0.00 | 0.391609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.311030E+09 | 0.00 | 0.00 | 0.00 | 0.207686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.326581E+09 | 0.00 | 0.00 | 0.00 | 57278694.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326581E+09 | 0.00 | 0.00 | 0.00 | 3135836.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311298E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.392246E+10 | 0.00 | 0.00 | 0.00 | 0.133213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.296110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.357684E+09 | 0.00 | 0.00 | 0.00 | 0.391609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_ZN
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309697E+09 | 0.00 | 0.00 | 0.18 |
February | 0.130890E+10 | 0.00 | 0.00 | 27441.56 | 0.00 | 0.114107E+09 | 24660472.97 | 0.00 | 0.18 |
March | 0.127131E+10 | 0.00 | 0.00 | 619122.22 | 0.00 | 6811599.94 | 0.393919E+09 | 0.00 | 0.19 |
April | 0.605267E+09 | 21050.48 | 0.00 | 2540357.57 | 0.00 | 0.00 | 0.664467E+09 | 0.00 | 0.17 |
May | 0.154458E+09 | 0.00 | 0.00 | 6653991.90 | 0.00 | 0.00 | 0.947525E+09 | 0.00 | 0.18 |
June | 62682837.63 | 25265.59 | 0.00 | 7853978.19 | 6244.20 | 0.00 | 0.784011E+09 | 0.00 | 0.19 |
July | 29968823.83 | 17339925.43 | 0.00 | 8740150.87 | 1553421.94 | 0.00 | 0.424987E+09 | 0.00 | 0.17 |
August | 26648875.86 | 50254111.00 | 0.00 | 8141796.34 | 4071914.60 | 0.00 | 0.332284E+09 | 0.00 | 0.19 |
September | 53096799.08 | 212053.09 | 0.00 | 7033342.36 | 0.00 | 0.00 | 0.636438E+09 | 0.00 | 0.17 |
October | 0.275994E+09 | 0.00 | 0.00 | 3850040.89 | 0.00 | 0.00 | 0.100212E+10 | 0.00 | 0.18 |
November | 0.112194E+10 | 0.00 | 0.00 | 916451.03 | 0.00 | 12208370.90 | 0.418939E+09 | 0.00 | 0.18 |
December | 0.145659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133930E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.769998E+10 | 67852405.59 | 0.00 | 46376672.92 | 5631580.74 | 0.576754E+09 | 0.562935E+10 | 0.00 | 0.18 |
Minimum of Months | 26648875.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.145659E+10 | 50254111.00 | 0.00 | 8740150.87 | 4071914.60 | 0.309697E+09 | 0.100212E+10 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_ZN_1
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.304174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620153E+09 | 0.00 | 0.00 | 0.17 |
February | 0.379968E+09 | 0.00 | 0.00 | 187994.26 | 0.00 | 0.353517E+09 | 69391071.22 | 0.00 | 0.18 |
March | 0.579562E+09 | 0.00 | 0.00 | 584182.28 | 0.00 | 0.145294E+09 | 0.149078E+09 | 0.00 | 0.19 |
April | 0.397187E+09 | 2460198.94 | 0.00 | 1231905.73 | 69499.34 | 71440534.12 | 0.191519E+09 | 0.00 | 0.17 |
May | 0.268276E+09 | 1066603.17 | 0.00 | 2512231.75 | 36902.58 | 16224535.93 | 0.333412E+09 | 0.00 | 0.18 |
June | 0.135116E+09 | 799410.33 | 0.00 | 3580379.10 | 177025.45 | 0.00 | 0.353031E+09 | 0.00 | 0.19 |
July | 55158974.13 | 27434679.36 | 0.00 | 4792895.03 | 2411431.67 | 0.00 | 0.201810E+09 | 0.00 | 0.17 |
August | 40904560.95 | 79488523.97 | 0.00 | 4541966.36 | 5550569.60 | 0.00 | 0.168609E+09 | 0.00 | 0.19 |
September | 0.107725E+09 | 11259008.92 | 0.00 | 4814106.66 | 113154.48 | 0.00 | 0.296635E+09 | 0.00 | 0.17 |
October | 0.324833E+09 | 0.00 | 0.00 | 2925773.71 | 0.00 | 20095884.67 | 0.362500E+09 | 0.00 | 0.18 |
November | 0.528367E+09 | 0.00 | 0.00 | 255962.90 | 0.00 | 0.198535E+09 | 0.121705E+09 | 0.00 | 0.18 |
December | 0.410929E+09 | 0.00 | 0.00 | 78855.27 | 0.00 | 0.443850E+09 | 33895098.85 | 0.00 | 0.17 |
Annual Sum or Average | 0.353220E+10 | 0.122508E+09 | 0.00 | 25506253.05 | 8358583.11 | 0.186911E+10 | 0.228158E+10 | 0.00 | 0.18 |
Minimum of Months | 40904560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.579562E+09 | 79488523.97 | 0.00 | 4814106.66 | 5550569.60 | 0.620153E+09 | 0.362500E+09 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_ZN_2
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 65882567.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476803E+09 | 0.00 | 0.00 | 0.17 |
February | 0.164899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294855E+09 | 0.00 | 0.00 | 0.18 |
March | 0.397069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105465E+09 | 0.00 | 0.00 | 0.19 |
April | 0.258749E+09 | 1580678.53 | 0.00 | 646303.39 | 36827.66 | 26837644.87 | 0.108201E+09 | 0.00 | 0.17 |
May | 0.130565E+09 | 864421.18 | 0.00 | 1863223.94 | 87542.37 | 758664.03 | 0.238375E+09 | 0.00 | 0.18 |
June | 39269984.08 | 512566.26 | 0.00 | 3439257.61 | 94168.11 | 0.00 | 0.240950E+09 | 0.00 | 0.19 |
July | 12072853.14 | 20889120.90 | 0.00 | 3479754.72 | 1772237.86 | 0.00 | 0.128863E+09 | 0.00 | 0.17 |
August | 10751308.08 | 55946107.94 | 0.00 | 2993617.38 | 3691958.27 | 0.00 | 99504650.56 | 0.00 | 0.19 |
September | 46713013.45 | 6476843.59 | 0.00 | 2543178.60 | 75693.57 | 0.00 | 0.192849E+09 | 0.00 | 0.17 |
October | 0.250476E+09 | 0.00 | 0.00 | 873359.87 | 0.00 | 5751418.20 | 0.164552E+09 | 0.00 | 0.18 |
November | 0.333455E+09 | 0.00 | 0.00 | 12779.30 | 0.00 | 0.148956E+09 | 13989112.38 | 0.00 | 0.18 |
December | 0.155068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359898E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.186497E+10 | 86269738.40 | 0.00 | 15851474.80 | 5758427.85 | 0.141932E+10 | 0.118729E+10 | 0.00 | 0.18 |
Minimum of Months | 10751308.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.397069E+09 | 55946107.94 | 0.00 | 3479754.72 | 3691958.27 | 0.476803E+09 | 0.240950E+09 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_ZN_3
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.157955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803676E+09 | 0.00 | 0.00 | 0.17 |
February | 0.237943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574819E+09 | 0.00 | 0.00 | 0.18 |
March | 0.621002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248783E+09 | 0.00 | 0.00 | 0.19 |
April | 0.548631E+09 | 1086697.26 | 0.00 | 223660.02 | 22625.79 | 75562492.44 | 49018069.98 | 0.00 | 0.17 |
May | 0.315408E+09 | 634530.18 | 0.00 | 1673382.78 | 67548.47 | 190569.76 | 0.355536E+09 | 0.00 | 0.18 |
June | 0.108038E+09 | 375270.24 | 0.00 | 3492160.89 | 118220.37 | 0.00 | 0.419656E+09 | 0.00 | 0.19 |
July | 33010889.19 | 22668562.33 | 0.00 | 4400381.00 | 2675112.75 | 0.00 | 0.241537E+09 | 0.00 | 0.17 |
August | 26018811.90 | 62812734.94 | 0.00 | 3895382.81 | 5629198.85 | 0.00 | 0.199586E+09 | 0.00 | 0.19 |
September | 0.120959E+09 | 2701676.39 | 0.00 | 2621213.90 | 23669.98 | 0.00 | 0.336579E+09 | 0.00 | 0.17 |
October | 0.550460E+09 | 0.00 | 0.00 | 579932.42 | 0.00 | 12741608.52 | 0.179892E+09 | 0.00 | 0.18 |
November | 0.618515E+09 | 0.00 | 0.00 | 1588.71 | 0.00 | 0.252421E+09 | 5324978.94 | 0.00 | 0.18 |
December | 0.282733E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627777E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.362067E+10 | 90279471.34 | 0.00 | 16887702.51 | 8536376.21 | 0.259597E+10 | 0.178713E+10 | 0.00 | 0.18 |
Minimum of Months | 26018811.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.621002E+09 | 62812734.94 | 0.00 | 4400381.00 | 5629198.85 | 0.803676E+09 | 0.419656E+09 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_ZN_4
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453476E+09 | 0.00 | 0.00 | 0.17 |
February | 0.186133E+09 | 0.00 | 0.00 | 1404.59 | 0.00 | 0.298700E+09 | 1291835.46 | 0.00 | 0.18 |
March | 0.403180E+09 | 0.00 | 0.00 | 63137.16 | 0.00 | 0.110046E+09 | 20646884.94 | 0.00 | 0.19 |
April | 0.300830E+09 | 1181620.62 | 0.00 | 459643.88 | 31328.90 | 28920121.34 | 83681885.71 | 0.00 | 0.17 |
May | 0.134670E+09 | 673503.65 | 0.00 | 1784862.14 | 71680.44 | 0.00 | 0.260003E+09 | 0.00 | 0.18 |
June | 50977004.96 | 532201.29 | 0.00 | 2722205.25 | 64630.29 | 0.00 | 0.255186E+09 | 0.00 | 0.19 |
July | 13484447.75 | 17989120.12 | 0.00 | 3300408.47 | 1454046.92 | 0.00 | 0.138700E+09 | 0.00 | 0.17 |
August | 11116859.13 | 46022918.25 | 0.00 | 2742295.89 | 3067884.44 | 0.00 | 0.110202E+09 | 0.00 | 0.19 |
September | 45181316.66 | 4488817.97 | 0.00 | 2267752.94 | 123784.91 | 0.00 | 0.210426E+09 | 0.00 | 0.17 |
October | 0.251664E+09 | 0.00 | 0.00 | 871577.15 | 0.00 | 5135134.96 | 0.193756E+09 | 0.00 | 0.18 |
November | 0.349302E+09 | 0.00 | 0.00 | 51576.63 | 0.00 | 0.132007E+09 | 45172332.73 | 0.00 | 0.18 |
December | 0.195452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345033E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.205609E+10 | 70888181.90 | 0.00 | 14264864.09 | 4813355.90 | 0.137332E+10 | 0.131907E+10 | 0.00 | 0.18 |
Minimum of Months | 11116859.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.403180E+09 | 46022918.25 | 0.00 | 3300408.47 | 3067884.44 | 0.453476E+09 | 0.260003E+09 | 0.00 | 0.19 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:18
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.601908E+10 | 0.672256E+09 | 0.00 | 0.463904E+10 | 0.135486E+10 |
February | 0.239064E+11 | 0.127784E+10 | 0.00 | 0.400940E+10 | 0.829919E+09 |
March | 0.514029E+11 | 0.227315E+10 | 0.00 | 0.445343E+10 | 0.557220E+09 |
April | 0.896649E+11 | 0.346403E+10 | 0.00 | 0.340892E+10 | 0.162932E+10 |
May | 0.123474E+12 | 0.450862E+10 | 0.00 | 0.316639E+10 | 0.418725E+10 |
June | 0.126798E+12 | 0.453271E+10 | 0.00 | 0.246730E+10 | 0.714219E+10 |
July | 0.135393E+12 | 0.455541E+10 | 0.00 | 0.118812E+10 | 0.101755E+11 |
August | 0.103406E+12 | 0.328214E+10 | 0.00 | 0.731406E+09 | 0.137444E+11 |
September | 0.684394E+11 | 0.198967E+10 | 0.00 | 0.204041E+10 | 0.769673E+10 |
October | 0.373539E+11 | 0.145871E+10 | 0.00 | 0.360907E+10 | 0.271618E+10 |
November | 0.104405E+11 | 0.808461E+09 | 0.00 | 0.430208E+10 | 0.675926E+09 |
December | 0.200371E+10 | 0.124486E+09 | 0.00 | 0.444523E+10 | 0.874358E+09 |
Annual Sum or Average | 0.778302E+12 | 0.289475E+11 | 0.00 | 0.384608E+11 | 0.515838E+11 |
Minimum of Months | 0.200371E+10 | 0.124486E+09 | 0.00 | 0.731406E+09 | 0.557220E+09 |
Maximum of Months | 0.135393E+12 | 0.455541E+10 | 0.00 | 0.463904E+10 | 0.137444E+11 |