Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2024-07-03 12:19:35
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1227.45 | 5282.91 | 5282.91 |
Net Site Energy | 1227.45 | 5282.91 | 5282.91 |
Total Source Energy | 2395.41 | 10309.82 | 10309.82 |
Net Source Energy | 2395.41 | 10309.82 | 10309.82 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 73.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 87.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 24.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 165.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 53.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 511.22 | 716.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 73.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 87.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 24.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 64.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 165.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 30.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 73.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 87.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 24.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 15.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 64.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 165.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 53.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 653.99 | 1028.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1374.50 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2200.26 | 3082.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 653.99 | 1028.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1374.50 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2200.26 | 3082.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 511.216 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 511.216 | 100.00 |
Total On-Site and Utility Electric Sources | 511.216 | 100.00 |
Total Electricity End Uses | 511.216 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 2.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4215.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 7.1446 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.9598 | 18.52 | 1071.0790 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.5522 | 2.48 | 593.9329 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.5522 | 2.48 | 593.9329 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.1446 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.9598 | 18.52 | 1071.0790 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 8.5522 | 1.24 | 593.9329 | |||||||
Conditioned Total | 232.34 | 8.5522 | 1.24 | 593.9329 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 8.5522 | 2.48 | 593.9329 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-JUL-11:09 | 02-MAR-04:10 | - | - | - | - | - | - | - | - | - | - | 15-OCT-12:50 |
Heating | 0.00 | 81105.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14522.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1065.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13174.05 | 4596.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3053.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 324.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2547.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 34363.64 | 86026.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 81105.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14522.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1065.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12146.55 | 4596.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3053.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 324.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1313.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1040.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 79.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 277.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 77.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 841.99 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 203.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 179.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 169.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1619.02 | 776.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 341.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1195.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 331.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 212.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 875.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 774.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 729.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6968.23 | 3341.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 341.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1195.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 331.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 212.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 875.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 774.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 729.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6968.23 | 3341.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.69 |
KITCHEN DIRECT AIR | 1.43 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.69 | 2.69 | 2.69 | 2.69 | 2.69 | 2.69 | 1.00 | 1.00 | 2.69 |
PSZ-AC_2:2 | 1.43 | 1.43 | 1.43 | 1.43 | 1.43 | 1.43 | 1.00 | 1.000000 | 1.43 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.69 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.43 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.69 | 2882.31 |
PSZ-AC_2:2_ADDAQ FAN | 1.43 | 1529.42 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.69 | 2.69 | 2.69 | 1.78 | 48812.25 | 64884.20 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.43 | 1.43 | 1.43 | 0.943338 | 35492.91 | 66224.76 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.69 | 1.35 | 1.80 | 48812.25 | 24406.12 | 0.800850 | 0.800850 |
PSZ-AC_2:2 COOLING COIL | 1.43 | 0.714650 | 0.952867 | 35492.91 | 17746.46 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 64884.20 |
PSZ-AC_2:2 HEATING COIL | 66224.76 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 7.145 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 123.932 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.960 | 279.726 | 791.353 | 0.000 | 0.000 | 0.000 | 1081.039 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 829.995 | 7.145 | 9.481 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 829.995 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1157.049 | 9.960 | 184.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1157.049 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 457.500 | 3.938 | 72.928 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 570.000 | 4.907 | 90.861 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.6929 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.33002231E-12 | 0.10712597E-14 | -0.10720425E-12 | 0.10137879E-15 |
34 | 6 | 0.29661659E-07 | 0.19687232E-09 | 0.67865745E-08 | -0.14052424E-12 |
35 | 5 | -0.19512200E-03 | 0.16741682E-05 | -0.10029371E-03 | 0.67057946E-08 |
36 | 4 | 0.29799499 | 0.81016957E-03 | 0.10178761 | -0.34398158E-04 |
37 | 3 | -7.3821031 | 0.24971312E-01 | -2.3732702 | 0.29576512E-01 |
38 | 2 | 41.252923 | 0.88368331E-01 | 15.405914 | -0.33759269 |
39 | 1 | -80.838295 | 0.39713828E-01 | -29.267905 | 1.0848528 |
40 | 0 | 46.824337 | 0.79570062E-03 | 16.288235 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.449_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 2.552 | 2.552 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.449_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 2.552 | 2.552 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.449_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 2.552 | 2.552 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.449_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 2.552 | 2.552 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.67979E-002 | 0.16139 | 0.61739 | 0.61739 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12139 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.67979E-002 | 0.16139 | 0.61739 | 0.61739 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12139 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.67979E-002 | 0.16139 | 0.61739 | 0.61739 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12139 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.67979E-002 | 0.16139 | 0.61739 | 0.61739 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12139 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 21.722 | 0.5184 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 2.382E-002 | 2.051E-004 | 2.563E-004 | 0.242 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 2.382E-002 | 2.051E-004 | 2.510E-004 | 0.242 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5764E-003 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1930E-002 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.4116E-003 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0389E-002 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.3167E-003 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.2515E-002 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0943E-003 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0886E-002 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.4974E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.4796E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 5.0779E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 5.0562E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.1534E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.1455E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.1787E-002 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.1787E-002 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.1701E-002 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.5501E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0115E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3790E-003 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2215E-002 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2905E-003 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0887E-002 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0943E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 26442.80477 | 31731.36573 | 2.24469 | 2.69363 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10000 | 6.87148E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 4140.31035 | 4968.37242 | 0.20200 | 0.41606 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -5.20000 | 2.80840E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16835.82190 | 20202.98628 | 1.19108 | 1.42930 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 36.93000 | 6.86961E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:30:00 | -5.20000 | 2.80840E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 37533.91 | 2.69363 | 2.69363 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 19734.85 | 0.41606 | 0.41606 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 32906.37 | 1.42930 | 1.42930 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 54137.03 | 1.14133 | 1.14133 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.69363 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.42930 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.69363 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.69363 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.69363 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.69363 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.69363 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.69363 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.42930 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.42930 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.42930 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.42930 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.42930 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.42930 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.69363 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.42930 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.69363 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.69363 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2882.30673 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.69363 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.69363 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.69363 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.77779 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.69363 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.34681 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.79575 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 48812.25000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24406.12500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80085 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80085 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 48812.25000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 64884.19931 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 64884.19931 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.42930 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.42930 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1529.41808 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.42930 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.42930 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.42930 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.94334 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.42930 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.71465 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.95287 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35492.91000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17746.45500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35492.91000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 66224.75834 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 66224.75834 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 46852.2 | 11.24 | 11.19 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 34477.0 | 11.85 | 11.80 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_EAST_0.25 | N/A | 2.552 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_SOUTH_0.25 | N/A | 2.552 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_WEST_0.25 | N/A | 2.552 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.4025605556E-002 | 0.2149109804 | Pass | Pass | 0.4930858459 | 2.5070086825 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2819267071 | 0.6892203102 | Pass | Pass | 7.7979831666E-002 | 0.3297943255 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4975600342 | 0.5148518002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 643.27 | 70.52 | 539.44 | 12.17 | 765.70 | 2031.11 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.449_SHGC_EAST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.552 | 0.251 | 0.276 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.449_SHGC_SOUTH_0.25 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.552 | 0.251 | 0.276 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.449_SHGC_WEST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.552 | 0.251 | 0.276 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.552 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.552 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.1446 | 116.17 | 830.00 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 43.70 | 0.0000 | Y | 6.81 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.9598 | 116.17 | 1157.05 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 80.60 | 0.0000 | Y | 17.51 |
Interior Lighting Total | 8.5522 | 232.34 | 1987.04 | 24.32 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 830.00 | 315.40 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 830.00 | 315.40 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 218.22 | AstronomicalClock | - | 48.77 | 48.77 | 2.00 | |
EXTERIOR_LIGHTS_B | 1154.09 | AstronomicalClock | - | 83.77 | 62.77 | 13.60 | |
Exterior Lighting Total | 1372.31 | 15.60 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 48812.25 | 39091.29 | 9720.96 | 0.80 | 3.81 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35492.91 | 24883.37 | 10609.54 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 46852.2 | 11.24 | 11.19 | ||||
PSZ-AC_2:2 COOLING COIL | 34477.0 | 11.85 | 11.80 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 64884.20 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 66224.76 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.69 | 2882.31 | 1070.05 | 1.00 | 1.28 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.43 | 1529.42 | 1070.05 | 1.00 | 1.37 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 21.72 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 26442.80 | 31731.37 | 273.14 | 2.245 | 2.694 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.88 | 0.00762 | 38.10 | 0.00687 | 0.416 | 0.00 |
KITCHEN | 16835.82 | 20202.99 | 173.91 | 1.191 | 1.429 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00865 | 36.93 | 0.00687 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 4140.31 | 4968.37 | 42.77 | 0.202 | 0.416 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 21.11 | 21.11 | 0.00786 | -5.20 | 0.00281 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:30:00 | 18.89 | 24.17 | 0.00151 | -5.20 | 0.00281 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.69 | 2.69 | 0.42 | 0.42 | 2.6936 | 2.6936 | 2.6936 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.43 | 1.43 | 1.14 | 1.14 | 1.4293 | 1.4293 | 1.4293 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 48812.250 | 39091.290 | 2.693630 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24406.12 | 22925.00 | 1.795753 | 26.08 | 14.81 | 0.00750125 | 11.79 | 8.91 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 23.1689 | 23.88 | 0.00761630 | 35.8576 | 26442.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 64884.199 | 64884.199 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 64884.20 | 64884.20 | 2.693626 | 17.05 | 11.14 | 0.00709556 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 15.4460 | 20.14 | 0.00787872 | 46.5885 | 2319.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 35492.910 | 24883.369 | 1.429300 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 17746.46 | 17390.45 | 0.952867 | 34.74 | 17.41 | 0.00722817 | 11.79 | 8.91 | 0.00700000 | 36.93 | 0.00686961 | 17.82 | 119.7789 | 26.10 | 0.00864930 | 35.6289 | 16835.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 66224.758 | 66224.758 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 66224.76 | 66224.76 | 1.429300 | -4.15 | -5.03 | 0.00253870 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 79.8526 | 24.43 | 0.00146978 | 6.7629 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 48812.250 | 39091.290 | 2.693630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.7845 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.693626 | 2.81303869 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 24406.12 | 22925.00 | 1.0000 | 1.87536219 | 1.795753 | 26.08 | 14.81 | 0.00750125 | 45328.4 | 11.79 | 8.91 | 0.00700000 | 29511.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24406.12 | 38.10 | 0.00687148 | 18.17 | 0.41605618 | 23.1689 | 23.88 | 0.00761630 | 23.88 | 0.00761630 | 35.8576 | 26442.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 64884.199 | 64884.199 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.693626 | 2.81303869 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 64884.20 | 64884.20 | 1.0000 | 2.81303869 | 2.693626 | 17.05 | 11.14 | 0.00709556 | 35098.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64884.20 | -5.20 | 0.00280840 | -5.20 | 0.41605618 | 15.4460 | 21.11 | 0.00787872 | 20.14 | 0.00787872 | 46.5885 | 2319.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35492.910 | 24883.369 | 1.429300 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2768 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.429300 | 1.49266287 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 17746.46 | 17390.45 | 1.0000 | 0.99510890 | 0.952867 | 34.74 | 17.41 | 0.00722817 | 53451.0 | 11.79 | 8.91 | 0.00700000 | 29510.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17746.46 | 36.93 | 0.00686961 | 17.82 | 1.14133354 | 119.7789 | 26.05 | 0.00864930 | 26.10 | 0.00864930 | 35.6289 | 16835.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 66224.758 | 66224.758 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.429300 | 1.49266287 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 66224.76 | 66224.76 | 1.0000 | 1.49266287 | 1.429300 | -4.15 | -5.03 | 0.00253870 | 2157.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66224.76 | -5.20 | 0.00280840 | -5.20 | 1.14133354 | 79.8526 | 0.00 | 0.00146978 | 24.43 | 0.00146978 | 6.7629 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.69 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.43 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3419.17 | 3715.50 | 818.33 |
KITCHEN | 5360.00 | 5699.83 | 4177.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5397.17 | 6939.83 | 4215.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 7.50 | 60.67 | 0.00 | 2.17 |
KITCHEN | 0.00 | 243.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 7.50 | 262.33 | 0.00 | 2.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 5.611 | 4.215 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.999 | 0.013 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.111 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.312 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 14538138.63 | 0.00 | 14538138.63 | 10610152.42 | 25148291.05 | 13120747.55 | 1406.48 | 5801.22 | 1552.30 | 337.35 |
KITCHEN | 26251600.74 | 0.00 | 26251600.74 | 53433.20 | 26305033.94 | 35993094.65 | 8490.91 | 256.20 | 12.89 | 745.38 |
Total Facility | 40789739.37 | 0.00 | 40789739.37 | 10663585.62 | 51453324.99 | 49113842.20 | 8494.63 | 5802.01 | 1558.55 | 834.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.5439 | 0.0000 | 0.5439 | 0.4093 | 0.9532 | 0.4161 | 0.00 | 5715.65 | 1471.35 |
KITCHEN | 0.9650 | 0.0000 | 0.9650 | 0.0012 | 0.9663 | 1.1413 | 6927.97 | 255.55 | 3.48 |
Total Facility | 1.5089 | 0.0000 | 1.5089 | 0.4105 | 1.9194 | 1.5574 | 6927.97 | 5715.85 | 1473.55 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 15855791.47 | 0.00 | 15855791.47 | 13120747.55 | 1405.26 | 0.12 | 7354.62 | 337.31 |
PSZ-AC_2:2 | 28630490.61 | 0.00 | 28630490.61 | 35993094.65 | 8039.94 | 145.06 | 575.00 | 745.38 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5932 | 0.0000 | 0.5932 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.0525 | 0.0000 | 1.0525 | 1.1413 | 6482.59 | 142.47 | 561.94 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1067.87 | 658.14 | 5798.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 371.05 | 1213.99 | 6347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.3574 | 0.8299 | 0.4538 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.0498 | 1.1009 | 1.0472 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 263 |
Fields with Defaults | 881 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 511.22 | 3798.97 | 02-MAR-01:20 | 34363.64 | 03-JUL-11:10 |
Electricity:Building | 298.12 | 2110.08 | 01-JAN-01:20 | 18433.35 | 02-JAN-11:10 |
Electricity:Zone:DINING | 77.14 | 295.02 | 01-JAN-01:20 | 4205.23 | 02-JAN-17:10 |
Electricity:SpaceType:GENERAL | 290.18 | 1973.80 | 01-JAN-01:20 | 15139.30 | 02-JAN-11:10 |
InteriorLights:Electricity | 24.32 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-17:10 |
InteriorLights:Electricity:Zone:DINING | 6.81 | 25.01 | 01-JAN-01:20 | 681.55 | 02-JAN-17:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 24.32 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity | 24.32 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 6.81 | 25.01 | 01-JAN-01:20 | 681.55 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 24.32 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-17:10 |
Electricity:Zone:KITCHEN | 220.98 | 1815.06 | 01-JAN-01:20 | 14339.52 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.51 | 25.01 | 01-JAN-01:20 | 901.93 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.51 | 25.01 | 01-JAN-01:20 | 901.93 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 195.53 | 1653.77 | 01-JAN-01:10 | 10143.54 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 53.49 | 849.95 | 01-MAR-23:30 | 4370.28 | 17-JUL-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 45.55 | 764.18 | 08-JAN-23:30 | 2552.25 | 22-SEP-04:10 |
LowTempRefrigeration:Refrigeration:Electricity | 15.25 | 0.00 | 01-JAN-11:10 | 1476.02 | 22-SEP-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 30.30 | 683.18 | 02-MAR-00:30 | 1076.23 | 04-APR-03:40 |
ElectricityPurchased:Facility | 511.22 | 3798.97 | 02-MAR-01:20 | 34363.64 | 03-JUL-11:10 |
ElectricityPurchased:Plant | 511.22 | 3798.97 | 02-MAR-01:20 | 34363.64 | 03-JUL-11:10 |
Cogeneration:ElectricityPurchased | 511.22 | 3798.97 | 02-MAR-01:20 | 34363.64 | 03-JUL-11:10 |
General:Cogeneration:ElectricityPurchased | 511.22 | 3798.97 | 02-MAR-01:20 | 34363.64 | 03-JUL-11:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 511.22 | 3798.97 | 02-MAR-01:20 | 34363.64 | 03-JUL-11:10 |
ElectricityNet:Plant | 511.22 | 3798.97 | 02-MAR-01:20 | 34363.64 | 03-JUL-11:10 |
Cogeneration:ElectricityNet | 511.22 | 3798.97 | 02-MAR-01:20 | 34363.64 | 03-JUL-11:10 |
General:Cogeneration:ElectricityNet | 511.22 | 3798.97 | 02-MAR-01:20 | 34363.64 | 03-JUL-11:10 |
Electricity:HVAC | 151.95 | 0.00 | 01-JAN-01:10 | 19695.37 | 02-JUN-17:10 |
Fans:Electricity | 64.26 | 0.00 | 01-JAN-01:10 | 3465.38 | 19-DEC-04:50 |
General:Fans:Electricity | 64.26 | 0.00 | 01-JAN-01:10 | 3465.38 | 19-DEC-04:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 87.69 | 0.00 | 01-JAN-00:10 | 16438.38 | 02-JUN-17:10 |
General:Cooling:Electricity | 87.69 | 0.00 | 01-JAN-00:10 | 16438.38 | 02-JUN-17:10 |
ExteriorLights:Electricity | 15.60 | 0.00 | 01-JAN-07:20 | 1372.31 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 15.60 | 0.00 | 01-JAN-07:20 | 1372.31 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-09:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-09:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 716.23 | 1838.65 | 14-JAN-01:40 | 86026.09 | 02-MAR-04:10 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 73.13 | 0.00 | 01-JAN-00:10 | 81105.25 | 03-FEB-04:10 |
Heating:NaturalGas | 73.13 | 0.00 | 01-JAN-00:10 | 81105.25 | 03-FEB-04:10 |
General:Heating:NaturalGas | 73.13 | 0.00 | 01-JAN-00:10 | 81105.25 | 03-FEB-04:10 |
NaturalGas:Plant | 165.94 | 0.00 | 09-JAN-05:00 | 22556.39 | 01-FEB-13:50 |
WaterSystems:NaturalGas | 165.94 | 0.00 | 09-JAN-05:00 | 22556.39 | 01-FEB-13:50 |
Water Heater:WaterSystems:NaturalGas | 165.94 | 0.00 | 09-JAN-05:00 | 22556.39 | 01-FEB-13:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-OCT-12:50 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-OCT-12:50 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-OCT-12:50 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-OCT-12:50 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-OCT-12:50 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-OCT-12:50 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-OCT-12:50 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-OCT-12:50 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1074.61 | 2416.76 | 19-DEC-01:10 | 105962.87 | 26-JUL-13:00 |
EnergyTransfer:Building | 479.51 | 1208.38 | 19-DEC-01:10 | 37715.15 | 03-JUL-11:10 |
EnergyTransfer:Zone:KITCHEN | 348.57 | 1208.38 | 19-DEC-01:10 | 24172.34 | 21-MAR-04:10 |
Refrigeration:EnergyTransfer | 145.72 | 2416.76 | 19-DEC-01:10 | 7834.84 | 04-APR-03:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.86 | 1208.38 | 19-DEC-01:10 | 3917.42 | 04-APR-03:40 |
General:Refrigeration:EnergyTransfer | 72.86 | 1208.38 | 19-DEC-01:10 | 3917.42 | 04-APR-03:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.86 | 1208.38 | 19-DEC-01:10 | 3917.42 | 04-APR-03:40 |
EnergyTransfer:Plant | 198.36 | 1208.38 | 19-DEC-01:10 | 20144.45 | 07-FEB-13:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.19 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 59.67 | 1059.55 | 02-MAR-00:30 | 2238.70 | 04-APR-03:40 |
EnergyTransfer:Zone:DINING | 130.94 | 0.00 | 01-JAN-01:10 | 20093.96 | 14-JUN-17:10 |
Heating:EnergyTransfer | 11.95 | 0.00 | 01-JAN-00:10 | 11364.96 | 28-JAN-07:10 |
Heating:EnergyTransfer:Zone:DINING | 11.95 | 0.00 | 01-JAN-00:10 | 11364.96 | 28-JAN-07:10 |
General:Heating:EnergyTransfer | 11.95 | 0.00 | 01-JAN-00:10 | 11364.96 | 28-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:DINING | 11.95 | 0.00 | 01-JAN-00:10 | 11364.96 | 28-JAN-07:10 |
Cooling:EnergyTransfer | 394.69 | 0.00 | 01-JAN-01:10 | 33905.80 | 03-JUL-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 118.99 | 0.00 | 01-JAN-01:10 | 20093.96 | 14-JUN-17:10 |
General:Cooling:EnergyTransfer | 394.69 | 0.00 | 01-JAN-01:10 | 33905.80 | 03-JUL-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 118.99 | 0.00 | 01-JAN-01:10 | 20093.96 | 14-JUN-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 1260.08 | 02-JUL-23:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 1260.08 | 02-JUL-23:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 275.70 | 0.00 | 01-JAN-01:10 | 20320.16 | 21-MAR-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 275.70 | 0.00 | 01-JAN-01:10 | 20320.16 | 21-MAR-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 125.50 | 0.00 | 01-JAN-00:10 | 17726.59 | 30-JAN-13:10 |
PlantLoopHeatingDemand:Plant | 125.50 | 0.00 | 01-JAN-00:10 | 17726.59 | 30-JAN-13:10 |
WaterSystems:PlantLoopHeatingDemand | 125.50 | 0.00 | 01-JAN-00:10 | 17726.59 | 30-JAN-13:10 |
General:WaterSystems:PlantLoopHeatingDemand | 125.50 | 0.00 | 01-JAN-00:10 | 17726.59 | 30-JAN-13:10 |
EnergyTransfer:HVAC | 396.74 | 0.00 | 01-JAN-00:10 | 65533.75 | 19-DEC-04:10 |
HeatingCoils:EnergyTransfer | 58.51 | 0.00 | 01-JAN-00:10 | 64884.20 | 03-FEB-04:40 |
CoolingCoils:EnergyTransfer | 338.23 | 0.00 | 01-JAN-00:10 | 63797.59 | 03-AUG-02:30 |
WaterSystems:EnergyTransfer | 125.50 | 0.00 | 01-JAN-00:10 | 17726.59 | 30-JAN-13:10 |
WaterUse:WaterSystems:EnergyTransfer | 125.50 | 0.00 | 01-JAN-00:10 | 17726.59 | 30-JAN-13:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 11.948 | -118.993 | 0.000 | 0.000 | 68.883 | 6.809 | 52.748 | 24.917 | 0.000 | 21.842 | 1.258 | 0.000 | -9.579 | 0.000 | -59.835 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.007 | -275.692 | 0.000 | 0.000 | 4.443 | 17.506 | 201.243 | 0.000 | 0.000 | 0.039 | 52.954 | 0.000 | 0.000 | 0.000 | -0.500 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.406 | 12.176 | 0.000 | 0.000 | 0.000 | -16.582 | -0.000 |
Total Facility | 0.000 | 0.000 | 11.955 | -394.685 | 0.000 | 0.000 | 73.326 | 24.315 | 253.992 | 24.917 | 0.000 | 26.287 | 66.388 | 0.000 | -9.579 | 0.000 | -76.916 | -0.000 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 31-OCT-02:61 | 0.00 | 0.00 | 0.00 | -37856.98 | 0.00 | 0.00 | 0.00 | 25.01 | 202.51 | 0.00 | 0.00 | 0.00 | 38375.67 | 0.00 | -700.08 | 0.00 | -46.12 | 0.00 |
KITCHEN | 17-MAR-04:01 | 0.00 | 0.00 | 0.00 | -56844.68 | 0.00 | 0.00 | 9.10 | 25.01 | 4931.35 | 0.00 | 0.00 | 0.00 | 51930.14 | 0.00 | -0.00 | 0.00 | -50.93 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-JUN-03:21 | 0.00 | 0.00 | 0.00 | -82602.64 | 0.00 | 0.00 | 0.00 | 50.02 | 3157.65 | 0.00 | 0.00 | 266.73 | 79712.67 | 0.00 | -541.23 | 0.00 | -43.20 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 15-APR-02:04 | 0.00 | 0.00 | 17204.42 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 202.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -450.48 | 0.00 | -2.39 | -16979.07 |
KITCHEN | 02-JUL-23:01 | 0.00 | 0.00 | 6612.93 | 0.00 | 0.00 | 0.00 | 18.55 | 150.32 | 2003.46 | 0.00 | 0.00 | 18.16 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8803.44 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-APR-02:04 | 0.00 | 0.00 | 17204.42 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 1879.56 | 0.00 | 0.00 | 425.56 | 0.00 | 0.00 | -450.48 | 0.00 | -39.68 | -19069.39 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.6936 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.6936 | 0.1545 | 1.0000 | Not calculated | 0.4161 | 0.1545 | ||
PSZ-AC_2:2 | 1.4293 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.4293 | 0.1058 | 1.0000 | Not calculated | 0.1513 | 0.1058 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.6936 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.6936 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.1545 | ||
PSZ-AC_2:2 | 1.4293 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.4293 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1058 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6936 | 2.6936 | 2.6936 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4293 | 1.4293 | 1.4293 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.6936 | 2.6936 | 2.6936 | 2.6936 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.4293 | 1.4293 | 1.4293 | 1.4293 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6936 | 2.6936 | 2.6936 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4293 | 1.4293 | 1.4293 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.6936 | 2.6936 | 2.6936 | 2.6936 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.4293 | 1.4293 | 1.4293 | 1.4293 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 2.17 |
Number of hours not met | 2.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 73.13 | 81105.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 87.69 | 16438.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 24.32 | 1583.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 15.60 | 1372.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 64.26 | 3465.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 165.94 | 22556.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.25 | 1476.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 30.30 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 319.36 | 511.22 |
Natural Gas | 477.16 | 716.23 |
Additional | 0.00 | 0.00 |
Total | 796.51 | 1227.45 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 104.65 |
Space Heating | 0.00 |
Space Cooling | 377.43 |
Fans (All) | 276.56 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1144.28 |
Miscellaneous (All) | 2200.26 |
Subtotal | 2200.26 |
Natural Gas [MJ/m2] | |
Space Heating | 314.76 |
Service Water Heating | 714.21 |
Miscellaneous (All) | 3082.64 |
Subtotal | 3082.64 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.98 |
Space Heating | 5.96 |
Space Cooling | 7.14 |
Fans (All) | 5.23 |
Service Water Heating | 13.52 |
Receptacle Equipment | 60.53 |
Miscellaneous | 5.63 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8640.00 | 120.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8044.83 | 705.50 | 9.67 | 0.00 | 0.00 |
ATTIC | 5759.00 | 798.00 | 708.67 | 1083.83 | 410.50 |
Min | 5759.00 | 120.00 | 0.00 | 0.00 | 0.00 |
Max | 8640.00 | 798.00 | 708.67 | 1083.83 | 410.50 |
Average | 7481.28 | 541.17 | 239.44 | 361.28 | 136.83 |
Sum | 22443.83 | 1623.50 | 718.33 | 1083.83 | 410.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254598.33 | 126.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254598.33 | 126.67 | 0.00 | 0.00 | 0.00 |
Average | 90285.44 | 42.22 | 0.00 | 0.00 | 0.00 |
Sum | 270856.33 | 126.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8375.17 | 384.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6750.83 | 2009.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 5984.50 | 1122.17 | 383.67 | 347.00 | 922.67 |
Min | 5984.50 | 384.83 | 0.00 | 0.00 | 0.00 |
Max | 8375.17 | 2009.17 | 383.67 | 347.00 | 922.67 |
Average | 7036.83 | 1172.06 | 127.89 | 115.67 | 307.56 |
Sum | 21110.50 | 3516.17 | 383.67 | 347.00 | 922.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 249637.50 | 5087.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 12661.67 | 3596.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 249637.50 | 5087.50 | 0.00 | 0.00 | 0.00 |
Average | 87433.06 | 2894.61 | 0.00 | 0.00 | 0.00 |
Sum | 262299.17 | 8683.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:35
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210372E+10 | 6947.17 | 28-JAN-00:01 | -0.2 | -4.1 | 0.453628E+10 | 4411.37 | 03-JAN-12:00 | -0.2 | -4.1 |
February | 0.270933E+10 | 6839.47 | 03-FEB-00:01 | 0.00 | -4.1 | 0.425770E+10 | 4413.14 | 06-FEB-12:00 | 21.70 | 9.11 |
March | 0.401074E+10 | 7764.68 | 22-MAR-13:00 | 25.00 | 9.26 | 0.493418E+10 | 4681.01 | 18-MAR-18:10 | 25.00 | 9.26 |
April | 0.912599E+10 | 33744.55 | 20-APR-02:61 | 19.32 | 9.02 | 0.508360E+10 | 4681.01 | 01-APR-18:10 | 19.32 | 9.02 |
May | 0.142299E+11 | 34276.92 | 21-MAY-02:41 | 18.27 | 7.60 | 0.541102E+10 | 4681.29 | 27-MAY-18:00 | 27.20 | 17.08 |
June | 0.185184E+11 | 34325.78 | 11-JUN-02:61 | 19.32 | 7.24 | 0.529193E+10 | 4681.69 | 03-JUN-18:40 | 19.32 | 7.24 |
July | 0.188370E+11 | 35750.51 | 03-JUL-02:61 | 29.32 | 16.92 | 0.541254E+10 | 4681.23 | 22-JUL-18:00 | 26.70 | 20.03 |
August | 0.179733E+11 | 33493.15 | 07-AUG-02:61 | 27.70 | 16.80 | 0.547206E+10 | 4681.18 | 05-AUG-18:30 | 27.70 | 16.80 |
September | 0.153040E+11 | 33140.78 | 19-SEP-02:61 | 16.42 | 10.54 | 0.523866E+10 | 4681.50 | 02-SEP-18:00 | 16.42 | 10.54 |
October | 0.100042E+11 | 37862.10 | 31-OCT-02:61 | 15.58 | 7.27 | 0.523244E+10 | 4681.37 | 28-OCT-18:00 | 15.58 | 7.27 |
November | 0.412314E+10 | 32314.07 | 10-NOV-03:01 | 17.88 | 10.94 | 0.464313E+10 | 4413.31 | 10-NOV-12:20 | 19.80 | 11.75 |
December | 0.205470E+10 | 8161.14 | 28-DEC-05:10 | -3.0 | -3.8 | 0.451245E+10 | 3930.26 | 01-DEC-12:00 | -3.0 | -3.8 |
Annual Sum or Average | 0.118995E+12 | 0.600260E+11 | ||||||||
Minimum of Months | 0.205470E+10 | 6839.47 | -3.0 | -4.1 | 0.425770E+10 | 3930.26 | -3.0 | -4.1 | ||
Maximum of Months | 0.188370E+11 | 37862.10 | 29.32 | 16.92 | 0.547206E+10 | 4681.69 | 27.70 | 20.03 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223384E+11 | 36510.08 | 03-JAN-04:21 | 1.65 | -0.4 | 0.773528E+10 | 5135.15 | 03-JAN-11:00 | 16.70 | 8.07 |
February | 0.195851E+11 | 55815.96 | 21-FEB-05:01 | 4.60 | -0.4 | 0.701517E+10 | 5135.94 | 07-FEB-11:00 | 4.60 | -0.4 |
March | 0.214597E+11 | 56802.24 | 17-MAR-04:01 | 5.32 | -0.8 | 0.779995E+10 | 5135.94 | 07-MAR-11:00 | 5.32 | -0.8 |
April | 0.214228E+11 | 54147.80 | 11-APR-04:01 | 5.50 | 0.79 | 0.758914E+10 | 5135.96 | 26-APR-10:00 | 21.70 | 12.40 |
May | 0.233306E+11 | 51378.44 | 08-MAY-02:11 | 14.27 | 4.88 | 0.785784E+10 | 5135.97 | 23-MAY-10:09 | 26.38 | 17.58 |
June | 0.236850E+11 | 48387.07 | 13-JUN-03:21 | 18.60 | 6.81 | 0.760967E+10 | 5135.97 | 28-JUN-10:39 | 22.93 | 17.85 |
July | 0.251903E+11 | 31856.76 | 16-JUL-02:61 | 26.02 | 15.79 | 0.785843E+10 | 5135.96 | 07-JUL-10:20 | 26.02 | 15.79 |
August | 0.252742E+11 | 38390.11 | 23-AUG-02:61 | 22.20 | 12.48 | 0.786362E+10 | 5135.95 | 30-AUG-10:20 | 25.37 | 16.57 |
September | 0.242810E+11 | 43118.80 | 25-SEP-02:11 | 11.50 | 9.39 | 0.760450E+10 | 5135.96 | 26-SEP-10:30 | 22.75 | 14.13 |
October | 0.238964E+11 | 49995.06 | 31-OCT-03:41 | 15.17 | 6.62 | 0.784280E+10 | 5135.98 | 16-OCT-10:00 | 15.17 | 6.62 |
November | 0.224908E+11 | 55123.41 | 07-NOV-05:01 | 4.32 | 0.23 | 0.753118E+10 | 5135.97 | 10-NOV-11:00 | 21.10 | 12.09 |
December | 0.227453E+11 | 51317.23 | 01-DEC-05:01 | 4.90 | 2.37 | 0.772569E+10 | 5124.79 | 11-DEC-11:00 | 14.40 | 7.20 |
Annual Sum or Average | 0.275699E+12 | 0.920333E+11 | ||||||||
Minimum of Months | 0.195851E+11 | 31856.76 | 1.65 | -0.8 | 0.701517E+10 | 5124.79 | 4.60 | -0.8 | ||
Maximum of Months | 0.252742E+11 | 56802.24 | 26.02 | 15.79 | 0.786362E+10 | 5135.98 | 26.38 | 17.85 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 6.70 | 3.92 | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 6.42 | 1.84 | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.84 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.32 | 2.40 | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 11.18 | 2.41 | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.41 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 20.40 | 8.41 | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.41 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 25.03 | 11.56 | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.56 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 | 17.07 | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.07 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 | 18.12 | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.12 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 22.63 | 17.18 | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 | 8.67 | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.67 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 | 5.64 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.64 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8.95 | 5.46 | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.46 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 6.42 | 1.84 | 0.00 | 0.00 | 6.42 | 1.84 | ||
Maximum of Months | 0.00 | 0.00 | 27.63 | 18.12 | 0.00 | 0.00 | 27.63 | 18.12 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297251E+10 | 11364.96 | 28-JAN-07:10 | -2.9 |
February | 0.197152E+10 | 12402.64 | 03-FEB-05:01 | -3.8 |
March | 0.121388E+10 | 12460.45 | 02-MAR-05:01 | -3.9 |
April | 0.122239E+09 | 17207.77 | 15-APR-02:04 | 20.40 |
May | 46234578.49 | 16171.56 | 15-MAY-03:24 | 22.75 |
June | 0.102504E+09 | 16829.69 | 01-JUN-03:24 | 21.60 |
July | 59631852.25 | 5633.42 | 24-JUL-03:24 | 22.80 |
August | 63896865.00 | 14005.19 | 23-AUG-02:43 | 22.20 |
September | 11152958.43 | 9244.92 | 29-SEP-02:43 | 20.28 |
October | 19594145.54 | 6077.76 | 31-OCT-02:02 | 15.58 |
November | 0.119621E+10 | 7580.90 | 26-NOV-21:00 | 3.30 |
December | 0.416832E+10 | 11338.37 | 28-DEC-05:06 | -3.0 |
Annual Sum or Average | 0.119477E+11 | |||
Minimum of Months | 11152958.43 | 5633.42 | -3.9 | |
Maximum of Months | 0.416832E+10 | 17207.77 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44716.95 | 745.28 | 05-JAN-05:04 | -2.1 |
February | 9979.64 | 166.33 | 02-FEB-05:04 | -2.4 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 11.18 |
May | 240575.98 | 1604.59 | 19-MAY-23:01 | 28.03 |
June | 3005722.49 | 5059.92 | 14-JUN-23:01 | 31.83 |
July | 2111354.99 | 6613.24 | 02-JUL-23:01 | 33.48 |
August | 1466426.20 | 3782.83 | 06-AUG-23:01 | 30.40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 22.63 |
October | 368496.67 | 3099.06 | 01-OCT-23:01 | 29.63 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 4506.32 | 75.11 | 31-DEC-05:04 | -2.8 |
Annual Sum or Average | 7251779.25 | |||
Minimum of Months | 0.00 | 0.00 | -2.8 | |
Maximum of Months | 3005722.49 | 6613.24 | 33.48 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.662546E+09 | 681.55 | 02-JAN-17:10 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.574404E+09 | 681.55 | 01-FEB-17:30 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.581118E+09 | 681.55 | 01-MAR-17:49 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.511204E+09 | 681.55 | 01-APR-18:19 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.517712E+09 | 681.55 | 01-MAY-18:30 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.487790E+09 | 681.55 | 01-JUN-19:10 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.493965E+09 | 681.55 | 01-JUL-19:19 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.540767E+09 | 681.55 | 01-AUG-18:19 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.532282E+09 | 681.55 | 01-SEP-18:30 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.601864E+09 | 681.55 | 02-OCT-17:40 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.627301E+09 | 681.55 | 01-NOV-17:19 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.678421E+09 | 681.55 | 01-DEC-16:49 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.680937E+10 | 0.703313E+11 | ||||
Minimum of Months | 0.487790E+09 | 681.55 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.678421E+09 | 681.55 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147870E+10 | 901.93 | 02-JAN-10:09 | 0.166069E+11 | 10143.54 | 01-JAN-11:09 |
February | 0.133950E+10 | 901.93 | 01-FEB-10:09 | 0.149998E+11 | 10143.54 | 01-FEB-11:09 |
March | 0.150425E+10 | 901.93 | 01-MAR-10:09 | 0.166070E+11 | 10143.54 | 01-MAR-11:09 |
April | 0.143688E+10 | 901.93 | 01-APR-16:10 | 0.160712E+11 | 10143.54 | 01-APR-10:09 |
May | 0.149147E+10 | 901.93 | 01-MAY-09:09 | 0.166070E+11 | 10143.54 | 01-MAY-10:09 |
June | 0.145377E+10 | 901.93 | 01-JUN-09:09 | 0.160713E+11 | 10143.54 | 01-JUN-10:09 |
July | 0.147476E+10 | 901.93 | 01-JUL-16:10 | 0.166069E+11 | 10143.54 | 01-JUL-10:09 |
August | 0.150425E+10 | 901.93 | 01-AUG-09:09 | 0.166070E+11 | 10143.54 | 01-AUG-10:09 |
September | 0.143724E+10 | 901.93 | 01-SEP-09:09 | 0.160712E+11 | 10143.54 | 01-SEP-10:09 |
October | 0.147852E+10 | 901.93 | 02-OCT-09:09 | 0.166069E+11 | 10143.54 | 01-OCT-10:09 |
November | 0.143180E+10 | 901.93 | 01-NOV-09:09 | 0.160712E+11 | 10143.54 | 01-NOV-10:09 |
December | 0.147494E+10 | 901.93 | 01-DEC-10:09 | 0.166069E+11 | 10143.54 | 01-DEC-11:09 |
Annual Sum or Average | 0.175061E+11 | 0.195533E+12 | ||||
Minimum of Months | 0.133950E+10 | 901.93 | 0.149998E+11 | 10143.54 | ||
Maximum of Months | 0.150425E+10 | 901.93 | 0.166070E+11 | 10143.54 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.662546E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115331E+11 |
February | 0.852256E+10 | 0.574404E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874364E+10 |
March | 0.954557E+10 | 0.581118E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8463756.68 | 0.772075E+10 |
April | 0.915225E+10 | 0.511204E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103655E+10 | 0.308065E+10 |
May | 0.947560E+10 | 0.517712E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287043E+10 | 0.100605E+10 |
June | 0.922788E+10 | 0.487790E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565607E+10 | 0.241023E+09 |
July | 0.939996E+10 | 0.493965E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509906E+10 | 0.166659E+09 |
August | 0.954557E+10 | 0.540767E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420351E+10 | 0.504388E+09 |
September | 0.915225E+10 | 0.532282E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244785E+10 | 0.108804E+10 |
October | 0.940563E+10 | 0.601864E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520373E+09 | 0.396373E+10 |
November | 0.909363E+10 | 0.627301E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4581.11 | 0.888391E+10 |
December | 0.939996E+10 | 0.678421E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129026E+11 |
Annual Sum or Average | 0.111326E+12 | 0.680937E+10 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218423E+11 | 0.598345E+11 |
Minimum of Months | 0.852256E+10 | 0.487790E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166659E+09 |
Maximum of Months | 0.954557E+10 | 0.678421E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565607E+10 | 0.129026E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.147870E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72118308.74 |
February | 0.610713E+09 | 0.133950E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68397524.31 |
March | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71473143.35 |
April | 0.655836E+09 | 0.143688E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 1901721.46 | 45847264.19 |
May | 0.679007E+09 | 0.149147E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6241772.53 | 29908325.27 |
June | 0.661256E+09 | 0.145377E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 12554152.61 | 13142041.45 |
July | 0.673587E+09 | 0.147476E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 8939529.79 | 10453826.19 |
August | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6921071.44 | 13235951.50 |
September | 0.655836E+09 | 0.143724E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2091379.47 | 12950864.65 |
October | 0.673993E+09 | 0.147852E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 584179.12 | 38809841.92 |
November | 0.651635E+09 | 0.143180E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59584157.57 |
December | 0.673587E+09 | 0.147494E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63965068.91 |
Annual Sum or Average | 0.797748E+10 | 0.175061E+11 | 0.146594E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 39233806.41 | 0.499886E+09 |
Minimum of Months | 0.610713E+09 | 0.133950E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10453826.19 |
Maximum of Months | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 12554152.61 | 72118308.74 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397052E+09 | 0.922629E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377189E+09 | 0.100456E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395091E+09 | 0.139912E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385941E+09 | 0.163089E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389839E+09 | 0.176821E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322542E+09 | 0.181230E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247982E+09 | 0.176161E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285483E+09 | 0.165533E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334406E+09 | 0.151490E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355842E+09 | 0.123173E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417237E+09 | 0.100530E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497076E+09 | 0.875472E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440568E+10 | 0.165821E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247982E+09 | 0.875472E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497076E+09 | 0.181230E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 681.55 | 02-JAN-17:10 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 15372.10 | 26-JAN-20:00 |
February | 9454.80 | 04-FEB-19:10 | 681.55 | 01-FEB-17:30 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 15038.08 | 01-FEB-21:00 |
March | 9454.80 | 04-MAR-19:10 | 681.55 | 01-MAR-17:49 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 761.77 | 22-MAR-13:00 | 16557.86 | 01-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 681.55 | 01-APR-18:19 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5330.24 | 19-APR-17:03 | 9535.33 | 10-APR-19:55 |
May | 9454.80 | 06-MAY-18:10 | 681.55 | 01-MAY-18:30 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7751.25 | 19-MAY-17:10 | 5782.60 | 06-MAY-06:03 |
June | 9454.80 | 03-JUN-18:10 | 681.55 | 01-JUN-19:10 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10886.52 | 02-JUN-17:03 | 2822.82 | 29-JUN-06:10 |
July | 9454.80 | 01-JUL-18:10 | 681.55 | 01-JUL-19:19 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10545.62 | 03-JUL-17:10 | 2583.42 | 05-JUL-06:05 |
August | 9454.80 | 05-AUG-18:10 | 681.55 | 01-AUG-18:19 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9276.73 | 07-AUG-17:03 | 4476.40 | 16-AUG-20:00 |
September | 9454.80 | 02-SEP-18:10 | 681.55 | 01-SEP-18:30 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6905.01 | 19-SEP-17:02 | 6707.24 | 30-SEP-06:10 |
October | 9454.80 | 07-OCT-18:10 | 681.55 | 02-OCT-17:40 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4813.24 | 04-OCT-17:02 | 7934.45 | 23-OCT-18:55 |
November | 9454.80 | 04-NOV-18:10 | 681.55 | 01-NOV-17:19 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.42 | 08-NOV-14:53 | 14039.84 | 27-NOV-20:00 |
December | 9454.80 | 02-DEC-19:10 | 681.55 | 01-DEC-16:49 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 16971.76 | 26-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 681.55 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2583.42 | |||||
Maximum of Months | 9454.80 | 681.55 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 10886.52 | 16971.76 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 901.93 | 02-JAN-10:09 | 7408.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 282.16 | 26-JAN-01:20 |
February | 677.52 | 04-FEB-19:10 | 901.93 | 01-FEB-10:09 | 7408.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 442.63 | 24-FEB-05:00 |
March | 677.52 | 04-MAR-19:10 | 901.93 | 01-MAR-10:09 | 7408.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 317.66 | 20-MAR-00:20 |
April | 677.52 | 01-APR-18:10 | 901.93 | 01-APR-16:10 | 7408.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 29.35 | 21-APR-14:53 | 389.20 | 11-APR-02:00 |
May | 677.52 | 06-MAY-18:10 | 901.93 | 01-MAY-09:09 | 7408.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 29.55 | 19-MAY-13:55 | 273.67 | 04-MAY-01:40 |
June | 677.52 | 03-JUN-18:10 | 901.93 | 01-JUN-09:09 | 7408.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 38.36 | 15-JUN-02:03 | 200.15 | 28-JUN-02:00 |
July | 677.52 | 01-JUL-18:10 | 901.93 | 01-JUL-16:10 | 7408.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 35.58 | 03-JUL-00:07 | 97.47 | 30-JUL-01:20 |
August | 677.52 | 05-AUG-18:10 | 901.93 | 01-AUG-09:09 | 7408.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 24.99 | 26-AUG-14:55 | 153.25 | 14-AUG-00:50 |
September | 677.52 | 02-SEP-18:10 | 901.93 | 01-SEP-09:09 | 7408.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 9.25 | 10-SEP-15:00 | 64.01 | 25-SEP-03:30 |
October | 677.52 | 07-OCT-18:10 | 901.93 | 02-OCT-09:09 | 7408.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 18.80 | 02-OCT-00:15 | 200.17 | 24-OCT-02:00 |
November | 677.52 | 04-NOV-18:10 | 901.93 | 01-NOV-09:09 | 7408.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 246.60 | 10-NOV-04:40 |
December | 677.52 | 02-DEC-19:10 | 901.93 | 01-DEC-10:09 | 7408.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 334.84 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 901.93 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 64.01 | ||||||
Maximum of Months | 677.52 | 901.93 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 38.36 | 442.63 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 611.76 | 07-JAN-03:00 | 1797.94 | 26-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.18 | 10-FEB-24:00 | 2187.66 | 09-FEB-12:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.89 | 31-MAR-04:55 | 2421.15 | 17-MAR-12:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.52 | 27-APR-05:40 | 2609.12 | 13-APR-13:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.08 | 21-MAY-01:55 | 2432.53 | 12-MAY-12:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 705.10 | 14-JUN-03:51 | 2513.33 | 29-JUN-12:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.83 | 01-JUL-05:40 | 2391.96 | 06-JUL-13:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.45 | 26-AUG-06:00 | 2374.93 | 03-AUG-12:30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.96 | 12-SEP-04:00 | 2454.34 | 05-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.36 | 30-OCT-22:00 | 2266.30 | 24-OCT-13:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 669.80 | 23-NOV-01:00 | 1999.24 | 07-NOV-12:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 967.26 | 20-DEC-03:53 | 1985.59 | 27-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.45 | 1797.94 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 967.26 | 2609.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6947.17 | 28-JAN-00:01 | 4202.13 | 1211.66 | 3252.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 |
February | 6839.47 | 03-FEB-00:01 | 4202.13 | 908.75 | 3252.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.31 |
March | 7764.68 | 22-MAR-13:00 | 7353.73 | 163.57 | 3388.15 | 0.00 | 0.00 | 0.00 | 0.00 | 761.77 | 0.00 |
April | 33744.55 | 20-APR-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 |
May | 34276.92 | 21-MAY-02:41 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 |
June | 34325.78 | 11-JUN-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35750.51 | 03-JUL-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.38 | 0.00 |
August | 33493.15 | 07-AUG-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.98 | 0.00 |
September | 33140.78 | 19-SEP-02:61 | 0.00 | 200.07 | 2160.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 |
October | 37862.10 | 31-OCT-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.12 |
November | 32314.07 | 10-NOV-03:01 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.01 |
December | 8161.14 | 28-DEC-05:10 | 5252.67 | 250.09 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6839.47 | 0.00 | 163.57 | 2160.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37862.10 | 7353.73 | 1211.66 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 761.77 | 79.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36510.08 | 03-JAN-04:21 | 0.00 | 175.06 | 14864.35 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 72.51 |
February | 55815.96 | 21-FEB-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 24.16 |
March | 56802.24 | 17-MAR-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 |
April | 54147.80 | 11-APR-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 62.45 |
May | 51378.44 | 08-MAY-02:11 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 48387.07 | 13-JUN-03:21 | 0.00 | 250.09 | 21234.78 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 |
July | 31856.76 | 16-JUL-02:61 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 19.18 |
August | 38390.11 | 23-AUG-02:61 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 29.70 |
September | 43118.80 | 25-SEP-02:11 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 41.11 |
October | 49995.06 | 31-OCT-03:41 | 0.00 | 250.09 | 21234.78 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 104.03 |
November | 55123.41 | 07-NOV-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 32.84 |
December | 51317.23 | 01-DEC-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 44.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 31856.76 | 0.00 | 175.06 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56802.24 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 104.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.61 | 0.00 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.06 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.55 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.33 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.86 | 0.00 |
June | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.65 | 0.00 |
July | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.20 | 0.00 |
August | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.81 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.57 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.56 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.64 | 0.00 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.20 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.360272E+11 | 21878.08 | 26-JAN-11:09 | 0.744308E+11 | 86026.01 | 28-JAN-04:49 |
February | 0.328386E+11 | 22432.54 | 07-FEB-11:20 | 0.639512E+11 | 86026.00 | 03-FEB-04:49 |
March | 0.367151E+11 | 23947.51 | 22-MAR-10:00 | 0.644284E+11 | 86026.09 | 02-MAR-04:10 |
April | 0.399292E+11 | 27890.20 | 19-APR-10:20 | 0.545324E+11 | 44840.76 | 11-APR-10:20 |
May | 0.463559E+11 | 31088.13 | 19-MAY-10:00 | 0.541120E+11 | 42244.32 | 01-MAY-12:39 |
June | 0.510300E+11 | 34178.66 | 02-JUN-17:10 | 0.514021E+11 | 40721.73 | 01-JUN-12:20 |
July | 0.554415E+11 | 34363.64 | 03-JUL-11:09 | 0.524902E+11 | 39481.90 | 01-JUL-12:30 |
August | 0.523226E+11 | 33784.85 | 03-AUG-11:09 | 0.525558E+11 | 39492.73 | 31-AUG-12:39 |
September | 0.472562E+11 | 32363.26 | 01-SEP-10:00 | 0.513972E+11 | 40744.89 | 30-SEP-12:30 |
October | 0.416925E+11 | 30903.15 | 05-OCT-10:00 | 0.544675E+11 | 42266.88 | 31-OCT-12:39 |
November | 0.354593E+11 | 24891.97 | 10-NOV-11:20 | 0.618178E+11 | 55841.64 | 27-NOV-11:09 |
December | 0.361477E+11 | 22050.46 | 26-DEC-11:09 | 0.806451E+11 | 86026.08 | 28-DEC-04:10 |
Annual Sum or Average | 0.511216E+12 | 0.716231E+12 | ||||
Minimum of Months | 0.328386E+11 | 21878.08 | 0.513972E+11 | 39481.90 | ||
Maximum of Months | 0.554415E+11 | 34363.64 | 0.806451E+11 | 86026.09 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.214124E+10 | 0.161124E+10 | 0.225803E+11 | 0.00 | 0.546036E+10 | 0.79 | 0.00 | 33131390.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191390E+10 | 0.135412E+10 | 0.203951E+11 | 0.00 | 0.489623E+10 | 0.72 | 0.00 | 0.393893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208537E+10 | 0.135517E+10 | 0.225804E+11 | 0.00 | 0.532566E+10 | 0.80 | 0.00 | 0.973238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194808E+10 | 0.116654E+10 | 0.218518E+11 | 0.00 | 0.510663E+10 | 0.77 | 0.00 | 0.540612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200919E+10 | 0.108098E+10 | 0.225803E+11 | 0.00 | 0.535620E+10 | 0.80 | 0.00 | 0.106237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194156E+10 | 0.983744E+09 | 0.218520E+11 | 0.00 | 0.542446E+10 | 0.77 | 0.00 | 0.162339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.196872E+10 | 0.104393E+10 | 0.225802E+11 | 0.00 | 0.575642E+10 | 0.79 | 0.00 | 0.192959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204502E+10 | 0.115014E+10 | 0.225804E+11 | 0.00 | 0.556902E+10 | 0.80 | 0.00 | 0.161923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196952E+10 | 0.124723E+10 | 0.218518E+11 | 0.00 | 0.529788E+10 | 0.77 | 0.00 | 0.122774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208038E+10 | 0.143998E+10 | 0.225803E+11 | 0.00 | 0.530607E+10 | 0.79 | 0.00 | 0.561398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205910E+10 | 0.151977E+10 | 0.218519E+11 | 0.00 | 0.516413E+10 | 0.77 | 0.00 | 0.634605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215336E+10 | 0.164253E+10 | 0.225802E+11 | 0.00 | 0.559340E+10 | 0.79 | 0.00 | 14428014.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243154E+11 | 0.155953E+11 | 0.265865E+12 | 0.00 | 0.642565E+11 | 9.37 | 0.00 | 0.876925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.191390E+10 | 0.983744E+09 | 0.203951E+11 | 0.00 | 0.489623E+10 | 0.72 | 0.00 | 14428014.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.215336E+10 | 0.164253E+10 | 0.225804E+11 | 0.00 | 0.575642E+10 | 0.80 | 0.00 | 0.192959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.176542E+11 | 0.00 | 0.162509E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.127070E+11 | 0.00 | 0.146403E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.823134E+10 | 0.00 | 0.156714E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.115942E+10 | 0.00 | 0.141545E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 71516031.58 | 0.00 | 0.135148E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 38650170.49 | 0.00 | 0.121450E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 5285592.64 | 0.00 | 0.119592E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 29951295.46 | 0.00 | 0.120001E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 41878962.39 | 0.00 | 0.121369E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.409526E+09 | 0.00 | 0.135322E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.835755E+10 | 0.00 | 0.142418E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.244256E+11 | 0.00 | 0.156938E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.731319E+11 | 0.00 | 0.165941E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 5285592.64 | 0.00 | 0.119592E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.244256E+11 | 0.00 | 0.162509E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1583.48 | 02-JAN-17:10 | 1372.31 | 01-JAN-06:10 | 14073.79 | 01-JAN-11:09 | 0.00 | 3041.16 | 28-JAN-07:10 | 0.00 | 09-JAN-09:39 | 0.00 | 01-JAN-00:10 |
February | 1583.48 | 01-FEB-17:30 | 1372.31 | 01-FEB-06:10 | 14073.79 | 01-FEB-11:09 | 0.00 | 3444.46 | 10-FEB-04:49 | 0.00 | 02-FEB-08:39 | 0.00 | 01-FEB-00:10 |
March | 1583.48 | 01-MAR-17:49 | 1372.31 | 01-MAR-06:10 | 14073.79 | 01-MAR-11:09 | 0.00 | 2936.12 | 02-MAR-07:10 | 0.00 | 02-MAR-09:20 | 0.00 | 01-MAR-00:10 |
April | 1583.48 | 01-APR-18:19 | 1372.31 | 01-APR-05:10 | 14073.79 | 01-APR-10:09 | 0.00 | 2616.77 | 12-APR-06:10 | 0.00 | 04-APR-08:20 | 0.00 | 01-APR-00:10 |
May | 1583.48 | 01-MAY-18:30 | 1372.31 | 01-MAY-05:10 | 14073.79 | 01-MAY-10:09 | 0.00 | 2664.85 | 19-MAY-13:00 | 0.00 | 02-MAY-16:40 | 0.00 | 01-MAY-00:10 |
June | 1583.48 | 01-JUN-19:10 | 1372.31 | 01-JUN-19:10 | 14073.79 | 01-JUN-10:09 | 0.00 | 3256.98 | 02-JUN-17:10 | 0.00 | 02-JUN-06:49 | 0.00 | 01-JUN-00:10 |
July | 1583.48 | 01-JUL-19:19 | 1372.31 | 01-JUL-19:19 | 14073.79 | 01-JUL-10:09 | 0.00 | 3166.00 | 03-JUL-17:10 | 0.00 | 03-JUL-15:30 | 0.00 | 01-JUL-00:10 |
August | 1583.48 | 01-AUG-18:19 | 1372.31 | 01-AUG-05:10 | 14073.79 | 01-AUG-10:09 | 0.00 | 3070.56 | 03-AUG-12:00 | 0.00 | 08-AUG-16:19 | 0.00 | 01-AUG-00:10 |
September | 1583.48 | 01-SEP-18:30 | 1372.31 | 01-SEP-05:10 | 14073.79 | 01-SEP-10:09 | 0.00 | 2835.19 | 01-SEP-10:00 | 0.00 | 15-SEP-07:00 | 0.00 | 01-SEP-00:10 |
October | 1583.48 | 02-OCT-17:40 | 1372.31 | 01-OCT-05:10 | 14073.79 | 01-OCT-10:09 | 0.00 | 2671.24 | 03-OCT-13:00 | 0.00 | 02-OCT-09:30 | 0.00 | 01-OCT-00:10 |
November | 1583.48 | 01-NOV-17:19 | 1372.31 | 01-NOV-05:10 | 14073.79 | 01-NOV-10:09 | 0.00 | 2801.50 | 28-NOV-07:10 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1583.48 | 01-DEC-16:49 | 1372.31 | 01-DEC-06:10 | 14073.79 | 01-DEC-11:09 | 0.00 | 3465.38 | 19-DEC-04:49 | 0.00 | 14-DEC-08:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1583.48 | 1372.31 | 14073.79 | 0.00 | 2616.77 | 0.00 | 0.00 | ||||||
Maximum of Months | 1583.48 | 1372.31 | 14073.79 | 0.00 | 3465.38 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 1348.60 | 03-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3694.66 | 20-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5308.79 | 22-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9750.39 | 21-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12005.48 | 19-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16438.38 | 02-JUN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15857.62 | 03-JUL-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14843.86 | 03-AUG-02:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12641.18 | 01-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11919.76 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5426.98 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 838.30 | 01-DEC-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 838.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16438.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 21878.08 | 26-JAN-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2618.59 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22432.54 | 07-FEB-11:20 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2268.33 | 0.00 | 0.00 | 720.13 | 0.00 |
March | 23947.51 | 22-MAR-10:00 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2268.33 | 0.00 | 0.00 | 4015.17 | 0.00 |
April | 27890.20 | 19-APR-10:20 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2268.33 | 0.00 | 0.00 | 6173.62 | 0.00 |
May | 31088.13 | 19-MAY-10:00 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2603.08 | 0.00 | 0.00 | 10795.15 | 0.00 |
June | 34178.66 | 02-JUN-17:10 | 1065.50 | 11824.43 | 0.00 | 0.00 | 3256.98 | 0.00 | 0.00 | 16438.38 | 0.00 |
July | 34363.64 | 03-JUL-11:09 | 1065.50 | 13174.05 | 0.00 | 0.00 | 3053.57 | 0.00 | 0.00 | 14522.79 | 0.00 |
August | 33784.85 | 03-AUG-11:09 | 1065.50 | 13174.05 | 0.00 | 0.00 | 3064.30 | 0.00 | 0.00 | 13922.87 | 0.00 |
September | 32363.26 | 01-SEP-10:00 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2835.19 | 0.00 | 0.00 | 11829.91 | 0.00 |
October | 30903.15 | 05-OCT-10:00 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2646.08 | 0.00 | 0.00 | 10565.68 | 0.00 |
November | 24891.97 | 10-NOV-11:20 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2268.33 | 0.00 | 0.00 | 3168.51 | 0.00 |
December | 22050.46 | 26-DEC-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2777.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 21878.08 | 1065.50 | 11824.43 | 0.00 | 0.00 | 2268.33 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34363.64 | 1065.50 | 14073.79 | 0.00 | 0.00 | 3256.98 | 0.00 | 0.00 | 16438.38 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 81105.25 | 28-JAN-04:49 | 0.00 | 22553.00 | 28-JAN-13:30 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 81105.25 | 03-FEB-03:20 | 0.00 | 22556.39 | 01-FEB-13:50 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 81105.25 | 02-MAR-03:09 | 0.00 | 21919.06 | 01-MAR-13:20 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 18976.22 | 12-APR-06:10 | 0.00 | 20948.14 | 01-APR-12:20 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 4136.66 | 02-MAY-06:19 | 0.00 | 19261.17 | 01-MAY-12:39 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 4458.01 | 07-JUN-03:30 | 0.00 | 17738.58 | 01-JUN-12:20 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 1265.03 | 24-JUL-03:30 | 0.00 | 16498.75 | 01-JUL-12:30 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 3543.16 | 23-AUG-02:00 | 0.00 | 16509.58 | 31-AUG-12:39 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 5281.74 | 30-SEP-06:10 | 0.00 | 17761.74 | 30-SEP-12:30 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 8900.33 | 25-OCT-06:10 | 0.00 | 19283.73 | 31-OCT-12:39 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 31503.32 | 28-NOV-07:10 | 0.00 | 21000.83 | 30-NOV-13:50 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 81105.25 | 19-DEC-03:09 | 0.00 | 21918.53 | 31-DEC-13:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 1265.03 | 0.00 | 16498.75 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 81105.25 | 0.00 | 22556.39 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
February | 2.33 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
March | 1.50 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.00 | 24.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.59 | 0.17 | 24.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 24.79 | 0.00 | 24.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 24.93 | 0.50 | 24.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 24.89 | 0.50 | 24.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 24.82 | 0.50 | 24.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 24.70 | 0.50 | 24.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.00 | 24.51 |
December | 3.17 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 7.50 | 20.32 | 0.00 | 20.32 | 60.67 | 24.31 | 2.17 | 24.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.26 | 0.00 | 20.26 |
Maximum of Months | 3.17 | 20.53 | 0.00 | 20.53 | 13.33 | 24.93 | 0.50 | 24.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.34 | 0.00 | 27.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.76 | 0.00 | 27.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.96 | 0.00 | 27.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 29.49 | 0.00 | 29.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 30.03 | 0.00 | 30.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 30.17 | 0.00 | 30.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 30.38 | 0.00 | 30.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 30.39 | 0.00 | 30.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 30.42 | 0.00 | 30.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 29.86 | 0.00 | 29.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.20 | 0.00 | 28.20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.37 | 0.00 | 27.37 |
Annual Sum or Average | 0.00 | 0.00 | 243.00 | 29.61 | 0.00 | 29.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.34 | 0.00 | 27.34 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 30.42 | 0.00 | 30.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 593.00 | 21.14 | 63.17 | 21.02 | 63.17 | 20.92 |
February | 497.67 | 21.45 | 48.00 | 21.33 | 48.00 | 21.23 |
March | 492.67 | 21.67 | 37.33 | 21.57 | 37.33 | 21.48 |
April | 245.17 | 22.34 | 113.67 | 22.82 | 1.67 | 22.80 |
May | 81.50 | 22.99 | 371.50 | 23.80 | 4.17 | 23.80 |
June | 30.17 | 24.08 | 517.67 | 24.05 | 19.33 | 24.06 |
July | 241.17 | 24.13 | 609.00 | 24.06 | 241.17 | 24.07 |
August | 125.50 | 24.14 | 607.50 | 24.03 | 125.50 | 24.05 |
September | 159.17 | 23.73 | 542.67 | 23.89 | 140.33 | 23.90 |
October | 205.17 | 22.15 | 373.17 | 23.26 | 42.67 | 23.29 |
November | 440.83 | 21.33 | 59.67 | 21.45 | 19.17 | 21.37 |
December | 603.50 | 21.14 | 75.83 | 21.00 | 75.83 | 20.89 |
Annual Sum or Average | 3715.50 | 21.88 | 3419.17 | 22.75 | 818.33 | 22.76 |
Minimum of Months | 30.17 | 21.14 | 37.33 | 21.00 | 1.67 | 20.89 |
Maximum of Months | 603.50 | 24.14 | 609.00 | 24.06 | 241.17 | 24.07 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 462.67 | 19.81 | 180.67 | 20.30 | 91.33 | 20.08 |
February | 338.00 | 20.44 | 258.00 | 21.79 | 90.67 | 21.69 |
March | 357.67 | 21.76 | 344.17 | 23.24 | 132.50 | 23.39 |
April | 400.50 | 25.28 | 502.17 | 25.57 | 341.50 | 25.71 |
May | 501.17 | 26.14 | 599.00 | 26.09 | 497.17 | 26.12 |
June | 571.00 | 26.26 | 592.00 | 26.25 | 571.00 | 26.25 |
July | 609.00 | 26.25 | 609.00 | 26.25 | 609.00 | 26.25 |
August | 612.00 | 26.22 | 612.00 | 26.22 | 612.00 | 26.22 |
September | 559.17 | 26.10 | 585.67 | 26.07 | 556.67 | 26.09 |
October | 455.00 | 25.78 | 563.83 | 25.66 | 430.67 | 25.78 |
November | 368.33 | 21.66 | 310.67 | 22.98 | 133.67 | 23.24 |
December | 465.33 | 19.50 | 202.83 | 19.97 | 111.17 | 19.73 |
Annual Sum or Average | 5699.83 | 24.12 | 5360.00 | 24.74 | 4177.33 | 24.97 |
Minimum of Months | 338.00 | 19.50 | 180.67 | 19.97 | 90.67 | 19.73 |
Maximum of Months | 612.00 | 26.26 | 612.00 | 26.25 | 612.00 | 26.25 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.21890 | 25.66402 | -0.3298 | 8.37621 |
February | 551.00000 | 21.68502 | 22.05165 | -0.2426 | 8.02014 |
March | 612.00000 | 22.10491 | 20.66964 | -0.1490 | 7.52668 |
April | 590.00000 | 23.25926 | 22.82131 | 0.18270 | 7.27947 |
May | 611.00000 | 23.82738 | 31.31304 | -0.4486 | 10.33722 |
June | 592.00000 | 24.02575 | 36.59351 | -0.3001 | 7.39379 |
July | 609.00000 | 24.02752 | 54.69277 | -0.1543 | 5.85932 |
August | 612.00000 | 24.01089 | 48.65051 | -0.1911 | 6.15123 |
September | 590.00000 | 23.86497 | 47.30099 | -0.2379 | 7.05533 |
October | 610.00000 | 23.26654 | 40.70188 | 0.36683 | 9.35173 |
November | 591.00000 | 21.96120 | 26.50007 | -0.0889 | 7.45394 |
December | 609.00000 | 21.16803 | 22.39680 | -0.3575 | 8.75436 |
Annual Sum or Average | 7187.00000 | 22.87403 | 33.37059 | -0.1625 | 7.80016 |
Minimum of Months | 551.00000 | 21.16803 | 20.66964 | -0.4486 | 5.85932 |
Maximum of Months | 612.00000 | 24.02752 | 54.69277 | 0.36683 | 10.33722 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.79438 | 32.23127 | -0.1530 | 10.51713 |
February | 551.00000 | 22.02066 | 27.78661 | 0.09305 | 12.52861 |
March | 612.00000 | 23.00068 | 25.77115 | 0.30717 | 14.51302 |
April | 590.00000 | 25.12882 | 25.78498 | 0.83206 | 23.36028 |
May | 611.00000 | 25.97610 | 32.02808 | 0.53041 | 12.75860 |
June | 592.00000 | 26.24408 | 35.56668 | 0.68172 | 15.42815 |
July | 609.00000 | 26.25071 | 49.92720 | 0.81869 | 19.59290 |
August | 612.00000 | 26.22316 | 45.17429 | 0.77409 | 18.11780 |
September | 590.00000 | 26.00495 | 44.45958 | 0.69696 | 16.65571 |
October | 610.00000 | 25.26551 | 39.97258 | 1.01229 | 29.11159 |
November | 591.00000 | 22.59995 | 31.07789 | 0.29134 | 14.83254 |
December | 609.00000 | 20.52905 | 29.44668 | -0.2222 | 11.02676 |
Annual Sum or Average | 7187.00000 | 24.17938 | 35.00042 | 0.47341 | 16.55749 |
Minimum of Months | 551.00000 | 20.52905 | 25.77115 | -0.2222 | 10.51713 |
Maximum of Months | 612.00000 | 26.25071 | 49.92720 | 1.01229 | 29.11159 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 619680.83 | 191481.72 | 0.83 | 619680.83 | -0.0 | 0.00 | 0.03 | 03-JAN-15:00 | 0.00 | 01-JAN-00:03 | 480.30 | 03-JAN-15:00 | 480.30 | 03-JAN-15:00 | 0.00 | 03-JAN-14:35 | 148.20 | 03-JAN-15:00 | 0.00 | 01-JAN-00:03 |
February | 0.355558E+09 | 0.105853E+09 | 36.75 | 0.355558E+09 | -0.0 | 0.00 | 0.29 | 06-FEB-14:00 | 0.00 | 01-FEB-00:03 | 5724.38 | 06-FEB-14:00 | 5724.38 | 06-FEB-14:00 | 0.00 | 21-FEB-14:47 | 1659.48 | 06-FEB-14:00 | 0.00 | 01-FEB-00:03 |
March | 0.102639E+10 | 0.300474E+09 | 82.07 | 0.102639E+10 | 0.00 | 0.00 | 0.45 | 22-MAR-13:00 | 0.00 | 01-MAR-00:03 | 9399.04 | 22-MAR-13:00 | 9399.04 | 22-MAR-13:00 | 0.00 | 14-MAR-17:10 | 2613.96 | 22-MAR-13:00 | 0.00 | 01-MAR-00:03 |
April | 0.852234E+10 | 0.236064E+10 | 292.85 | 0.846221E+10 | 60132360.22 | 0.00 | 1.00 | 02-APR-02:61 | 0.00 | 01-APR-00:01 | 48155.58 | 03-APR-02:61 | 48155.58 | 02-APR-02:61 | 3747.72 | 29-APR-02:41 | 11515.23 | 02-APR-02:61 | 0.00 | 01-APR-00:01 |
May | 0.176513E+11 | 0.480739E+10 | 463.98 | 0.169092E+11 | 0.742093E+09 | 0.00 | 1.00 | 01-MAY-02:62 | 0.00 | 01-MAY-00:01 | 48155.58 | 04-MAY-02:61 | 48155.58 | 15-MAY-02:12 | 17651.28 | 28-MAY-02:62 | 11515.23 | 04-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.266948E+11 | 0.733284E+10 | 544.29 | 0.251959E+11 | 0.149888E+10 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:02 | 48155.58 | 18-JUN-02:21 | 48155.58 | 16-JUN-02:58 | 23152.05 | 28-JUN-02:61 | 11515.23 | 01-JUN-02:61 | 0.00 | 01-JUN-00:02 |
July | 0.329203E+11 | 0.860651E+10 | 592.79 | 0.252448E+11 | 0.767552E+10 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:02 | 52626.46 | 17-JUL-02:61 | 48079.33 | 03-JUL-02:61 | 34280.81 | 21-JUL-02:41 | 11814.96 | 17-JUL-02:61 | 0.00 | 01-JUL-00:02 |
August | 0.271828E+11 | 0.721488E+10 | 545.41 | 0.227878E+11 | 0.439504E+10 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:02 | 51203.05 | 02-AUG-02:61 | 48155.58 | 23-AUG-02:61 | 24785.19 | 02-AUG-03:46 | 11717.98 | 02-AUG-02:61 | 0.00 | 01-AUG-00:02 |
September | 0.206761E+11 | 0.545264E+10 | 447.84 | 0.171200E+11 | 0.355611E+10 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 50855.22 | 22-SEP-02:61 | 46332.05 | 29-SEP-02:61 | 28369.64 | 22-SEP-03:21 | 11694.84 | 22-SEP-02:61 | 0.00 | 01-SEP-00:01 |
October | 0.814940E+10 | 0.221971E+10 | 265.85 | 0.703374E+10 | 0.111566E+10 | 0.00 | 1.00 | 02-OCT-02:61 | 0.00 | 01-OCT-00:01 | 49386.21 | 04-OCT-02:61 | 48155.58 | 31-OCT-02:61 | 24610.87 | 04-OCT-02:41 | 11597.67 | 04-OCT-02:61 | 0.00 | 01-OCT-00:01 |
November | 0.521791E+09 | 0.152159E+09 | 45.18 | 0.509988E+09 | 11803385.25 | 0.00 | 1.00 | 09-NOV-03:01 | 0.00 | 01-NOV-00:01 | 48155.58 | 10-NOV-03:01 | 43488.68 | 10-NOV-03:01 | 4666.90 | 10-NOV-03:01 | 11515.23 | 10-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.143701E+12 | 0.385533E+11 | 3317.85 | 0.124646E+12 | 0.190552E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.329203E+11 | 0.860651E+10 | 592.79 | 0.252448E+11 | 0.767552E+10 | 0.00 | 1.00 | 0.00 | 52626.46 | 48155.58 | 34280.81 | 11814.96 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.112633E+09 | 32939908.98 | 18.93 | 0.100917E+09 | 11715620.58 | 0.00 | 1.00 | 03-JAN-04:21 | 0.00 | 01-JAN-00:03 | 17487.63 | 03-JAN-04:21 | 14634.08 | 31-JAN-04:21 | 4548.38 | 13-JAN-04:21 | 4189.95 | 03-JAN-04:21 | 0.00 | 01-JAN-00:03 |
February | 0.100555E+10 | 0.288041E+09 | 86.11 | 0.984958E+09 | 20596498.38 | 0.00 | 1.00 | 07-FEB-03:01 | 0.00 | 01-FEB-00:03 | 35015.43 | 07-FEB-04:21 | 32393.56 | 07-FEB-05:01 | 8700.69 | 13-FEB-03:01 | 8382.98 | 07-FEB-04:21 | 0.00 | 01-FEB-00:03 |
March | 0.236531E+10 | 0.672765E+09 | 176.41 | 0.233398E+10 | 31332768.80 | 0.00 | 1.00 | 04-MAR-03:01 | 0.00 | 01-MAR-00:03 | 35015.43 | 07-MAR-05:01 | 34953.60 | 16-MAR-02:32 | 15043.08 | 11-MAR-04:22 | 8382.98 | 07-MAR-05:01 | 0.00 | 01-MAR-00:03 |
April | 0.115689E+11 | 0.304548E+10 | 382.20 | 0.112790E+11 | 0.289897E+09 | 0.00 | 1.00 | 01-APR-02:61 | 0.00 | 01-APR-00:01 | 35015.43 | 01-APR-02:61 | 35015.43 | 03-APR-02:22 | 13373.97 | 17-APR-02:11 | 8382.98 | 01-APR-02:61 | 0.00 | 01-APR-00:01 |
May | 0.227481E+11 | 0.581628E+10 | 532.57 | 0.213998E+11 | 0.134836E+10 | 0.00 | 1.00 | 01-MAY-02:11 | 0.00 | 01-MAY-00:01 | 35015.43 | 18-MAY-02:11 | 35015.43 | 01-MAY-02:51 | 17035.97 | 25-MAY-02:51 | 8382.98 | 01-MAY-02:11 | 0.00 | 01-MAY-00:01 |
June | 0.342166E+11 | 0.890109E+10 | 600.79 | 0.315965E+11 | 0.262015E+10 | 0.00 | 1.00 | 01-JUN-00:42 | 0.00 | 01-JUN-00:02 | 35015.43 | 25-JUN-02:34 | 35015.43 | 01-JUN-00:42 | 20018.29 | 28-JUN-02:61 | 8551.57 | 14-JUN-14:00 | 0.00 | 01-JUN-00:02 |
July | 0.438692E+11 | 0.106894E+11 | 638.40 | 0.322267E+11 | 0.116425E+11 | 0.00 | 1.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:02 | 37891.08 | 21-JUL-02:11 | 34637.03 | 03-JUL-01:22 | 26142.44 | 21-JUL-02:16 | 8617.28 | 03-JUL-01:22 | 0.00 | 01-JUL-00:02 |
August | 0.361144E+11 | 0.897738E+10 | 620.62 | 0.288370E+11 | 0.727732E+10 | 0.00 | 1.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:02 | 37205.83 | 02-AUG-03:46 | 34368.30 | 23-AUG-00:42 | 21842.98 | 02-AUG-03:46 | 8528.88 | 02-AUG-03:46 | 0.00 | 01-AUG-00:02 |
September | 0.276393E+11 | 0.682472E+10 | 525.36 | 0.212792E+11 | 0.636003E+10 | 0.00 | 1.00 | 01-SEP-00:42 | 0.00 | 01-SEP-00:01 | 37181.75 | 22-SEP-02:61 | 29695.07 | 29-SEP-00:42 | 23920.44 | 22-SEP-02:61 | 8527.27 | 22-SEP-02:61 | 0.00 | 01-SEP-00:01 |
October | 0.131221E+11 | 0.339428E+10 | 394.66 | 0.103583E+11 | 0.276384E+10 | 0.00 | 1.00 | 01-OCT-02:11 | 0.00 | 01-OCT-00:01 | 35202.57 | 04-OCT-02:11 | 35015.43 | 02-OCT-00:10 | 19789.57 | 06-OCT-02:61 | 8395.66 | 04-OCT-02:11 | 0.00 | 01-OCT-00:01 |
November | 0.171942E+10 | 0.482447E+09 | 124.02 | 0.153903E+10 | 0.180394E+09 | 0.00 | 1.00 | 01-NOV-02:61 | 0.00 | 01-NOV-00:01 | 35015.43 | 01-NOV-02:61 | 35011.94 | 24-NOV-05:01 | 17066.26 | 03-NOV-02:61 | 8382.98 | 01-NOV-02:61 | 0.00 | 01-NOV-00:01 |
December | 50280806.95 | 14428014.15 | 11.91 | 43595401.02 | 6685405.92 | 0.00 | 1.00 | 01-DEC-04:21 | 0.00 | 01-DEC-00:03 | 35015.43 | 01-DEC-05:01 | 26491.43 | 01-DEC-05:01 | 8524.00 | 01-DEC-05:01 | 8382.98 | 01-DEC-05:01 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.194532E+12 | 0.491393E+11 | 4111.98 | 0.161979E+12 | 0.325528E+11 | 0.00 | ||||||||||||||
Minimum of Months | 50280806.95 | 14428014.15 | 11.91 | 43595401.02 | 6685405.92 | 0.00 | 1.00 | 0.00 | 17487.63 | 14634.08 | 4548.38 | 4189.95 | 0.00 | |||||||
Maximum of Months | 0.438692E+11 | 0.106894E+11 | 638.40 | 0.322267E+11 | 0.116425E+11 | 0.00 | 1.00 | 0.00 | 37891.08 | 35015.43 | 26142.44 | 8617.28 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.16 | 41.86 | 35.31 | 77.31 | 142.97 | 0.00 | 0.00 | 0.00 |
February | 103.24 | 58.85 | 44.39 | 121.29 | 125.16 | 0.00 | 0.00 | 0.00 |
March | 127.47 | 70.23 | 57.24 | 164.50 | 104.23 | 0.00 | 0.00 | 0.00 |
April | 153.59 | 85.21 | 68.38 | 233.31 | 63.61 | 0.00 | 0.00 | 0.00 |
May | 158.50 | 86.14 | 72.36 | 269.13 | 39.42 | 0.00 | 0.00 | 0.00 |
June | 158.59 | 88.22 | 70.36 | 303.01 | 20.42 | 0.00 | 0.00 | 0.00 |
July | 142.22 | 74.35 | 67.87 | 273.24 | 16.87 | 0.00 | 0.00 | 0.00 |
August | 135.33 | 69.26 | 66.07 | 248.48 | 24.38 | 0.00 | 0.00 | 0.00 |
September | 134.07 | 76.50 | 57.57 | 228.54 | 46.55 | 0.00 | 0.00 | 0.00 |
October | 103.11 | 55.65 | 47.46 | 147.96 | 76.88 | 0.00 | 0.00 | 0.00 |
November | 92.43 | 53.81 | 38.62 | 104.78 | 124.38 | 0.00 | 0.00 | 0.00 |
December | 77.10 | 40.85 | 36.25 | 72.19 | 158.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.91 | 66.71 | 55.21 | 187.19 | 78.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.10 | 40.85 | 35.31 | 72.19 | 16.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.59 | 88.22 | 72.36 | 303.01 | 158.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 394.74 | 299.06 | 95.68 | 550.52 | 271.43 | 0.00 | 0.00 | 0.00 |
February | 366.17 | 258.14 | 108.02 | 519.81 | 242.86 | 0.00 | 0.00 | 0.00 |
March | 297.59 | 171.59 | 126.00 | 436.19 | 213.93 | 0.00 | 0.00 | 0.00 |
April | 201.76 | 75.28 | 126.48 | 330.72 | 137.50 | 0.00 | 0.00 | 0.00 |
May | 142.58 | 19.96 | 122.63 | 258.43 | 84.55 | 0.00 | 0.00 | 0.00 |
June | 123.01 | 7.81 | 115.21 | 275.43 | 43.09 | 0.00 | 0.00 | 0.00 |
July | 125.40 | 11.62 | 113.77 | 279.66 | 35.32 | 0.00 | 0.00 | 0.00 |
August | 159.85 | 42.31 | 117.54 | 331.52 | 51.50 | 0.00 | 0.00 | 0.00 |
September | 249.51 | 129.63 | 119.88 | 468.17 | 98.59 | 0.00 | 0.00 | 0.00 |
October | 339.00 | 229.19 | 109.81 | 546.65 | 152.59 | 0.00 | 0.00 | 0.00 |
November | 407.96 | 311.02 | 96.94 | 589.86 | 236.82 | 0.00 | 0.00 | 0.00 |
December | 404.30 | 303.49 | 100.82 | 551.29 | 296.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 267.09 | 154.34 | 112.75 | 427.57 | 154.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 123.01 | 7.81 | 95.68 | 258.43 | 35.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 407.96 | 311.02 | 126.48 | 589.86 | 296.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.28 | 45.78 | 35.51 | 90.20 | 148.77 | 0.00 | 0.00 | 0.00 |
February | 91.72 | 48.75 | 42.97 | 109.06 | 132.35 | 0.00 | 0.00 | 0.00 |
March | 124.99 | 66.99 | 58.00 | 165.35 | 110.09 | 0.00 | 0.00 | 0.00 |
April | 143.66 | 77.60 | 66.07 | 220.88 | 67.53 | 0.00 | 0.00 | 0.00 |
May | 154.74 | 82.79 | 71.95 | 265.30 | 41.79 | 0.00 | 0.00 | 0.00 |
June | 150.63 | 80.90 | 69.72 | 291.21 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 133.67 | 66.42 | 67.25 | 259.82 | 17.57 | 0.00 | 0.00 | 0.00 |
August | 129.45 | 65.97 | 63.48 | 239.99 | 25.57 | 0.00 | 0.00 | 0.00 |
September | 132.39 | 73.75 | 58.63 | 230.27 | 49.71 | 0.00 | 0.00 | 0.00 |
October | 113.96 | 66.51 | 47.45 | 171.20 | 78.82 | 0.00 | 0.00 | 0.00 |
November | 95.66 | 58.24 | 37.41 | 118.01 | 129.50 | 0.00 | 0.00 | 0.00 |
December | 77.08 | 41.87 | 35.21 | 80.46 | 165.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.20 | 64.68 | 54.53 | 187.14 | 82.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.08 | 41.87 | 35.21 | 80.46 | 17.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 154.74 | 82.79 | 71.95 | 291.21 | 165.11 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206677E+09 | 0.112115E+09 | 94562375.67 | 0.207076E+09 | 0.382924E+09 |
February | 0.249755E+09 | 0.142358E+09 | 0.107396E+09 | 0.293420E+09 | 0.302788E+09 |
March | 0.341404E+09 | 0.188103E+09 | 0.153302E+09 | 0.440600E+09 | 0.279178E+09 |
April | 0.398105E+09 | 0.220859E+09 | 0.177246E+09 | 0.604749E+09 | 0.164881E+09 |
May | 0.424517E+09 | 0.230709E+09 | 0.193808E+09 | 0.720844E+09 | 0.105578E+09 |
June | 0.411054E+09 | 0.228677E+09 | 0.182377E+09 | 0.785410E+09 | 52937427.91 |
July | 0.380913E+09 | 0.199135E+09 | 0.181779E+09 | 0.731855E+09 | 45181591.02 |
August | 0.362460E+09 | 0.185503E+09 | 0.176957E+09 | 0.665540E+09 | 65287867.16 |
September | 0.347515E+09 | 0.198283E+09 | 0.149233E+09 | 0.592367E+09 | 0.120668E+09 |
October | 0.276170E+09 | 0.149046E+09 | 0.127124E+09 | 0.396306E+09 | 0.205914E+09 |
November | 0.239576E+09 | 0.139473E+09 | 0.100103E+09 | 0.271583E+09 | 0.322388E+09 |
December | 0.206500E+09 | 0.109408E+09 | 97091653.26 | 0.193359E+09 | 0.425278E+09 |
Annual Sum or Average | 0.384465E+10 | 0.210367E+10 | 0.174098E+10 | 0.590311E+10 | 0.247301E+10 |
Minimum of Months | 0.206500E+09 | 0.109408E+09 | 94562375.67 | 0.193359E+09 | 45181591.02 |
Maximum of Months | 0.424517E+09 | 0.230709E+09 | 0.193808E+09 | 0.785410E+09 | 0.425278E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105727E+10 | 0.800993E+09 | 0.256279E+09 | 0.147451E+10 | 0.727010E+09 |
February | 0.885828E+09 | 0.624494E+09 | 0.261333E+09 | 0.125752E+10 | 0.587533E+09 |
March | 0.797053E+09 | 0.459578E+09 | 0.337475E+09 | 0.116828E+10 | 0.573001E+09 |
April | 0.522967E+09 | 0.195132E+09 | 0.327836E+09 | 0.857227E+09 | 0.356410E+09 |
May | 0.381895E+09 | 53452571.20 | 0.328443E+09 | 0.692181E+09 | 0.226447E+09 |
June | 0.318851E+09 | 20231099.24 | 0.298620E+09 | 0.713926E+09 | 0.111692E+09 |
July | 0.335868E+09 | 31135394.64 | 0.304733E+09 | 0.749047E+09 | 94609089.61 |
August | 0.428138E+09 | 0.113330E+09 | 0.314808E+09 | 0.887933E+09 | 0.137949E+09 |
September | 0.646718E+09 | 0.335992E+09 | 0.310726E+09 | 0.121351E+10 | 0.255539E+09 |
October | 0.907988E+09 | 0.613860E+09 | 0.294128E+09 | 0.146415E+10 | 0.408687E+09 |
November | 0.105743E+10 | 0.806162E+09 | 0.251271E+09 | 0.152891E+10 | 0.613843E+09 |
December | 0.108289E+10 | 0.812864E+09 | 0.270024E+09 | 0.147657E+10 | 0.794982E+09 |
Annual Sum or Average | 0.842290E+10 | 0.486722E+10 | 0.355567E+10 | 0.134838E+11 | 0.488770E+10 |
Minimum of Months | 0.318851E+09 | 20231099.24 | 0.251271E+09 | 0.692181E+09 | 94609089.61 |
Maximum of Months | 0.108289E+10 | 0.812864E+09 | 0.337475E+09 | 0.152891E+10 | 0.794982E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217711E+09 | 0.122609E+09 | 95102548.56 | 0.241593E+09 | 0.398459E+09 |
February | 0.221890E+09 | 0.117939E+09 | 0.103951E+09 | 0.263830E+09 | 0.320172E+09 |
March | 0.334770E+09 | 0.179425E+09 | 0.155345E+09 | 0.442886E+09 | 0.294858E+09 |
April | 0.372378E+09 | 0.201128E+09 | 0.171250E+09 | 0.572532E+09 | 0.175037E+09 |
May | 0.414456E+09 | 0.221752E+09 | 0.192704E+09 | 0.710583E+09 | 0.111931E+09 |
June | 0.390427E+09 | 0.209702E+09 | 0.180725E+09 | 0.754812E+09 | 56235340.23 |
July | 0.358025E+09 | 0.177910E+09 | 0.180116E+09 | 0.695899E+09 | 47064309.06 |
August | 0.346729E+09 | 0.176706E+09 | 0.170023E+09 | 0.642782E+09 | 68485136.28 |
September | 0.343146E+09 | 0.191167E+09 | 0.151979E+09 | 0.596871E+09 | 0.128846E+09 |
October | 0.305239E+09 | 0.178147E+09 | 0.127092E+09 | 0.458530E+09 | 0.211099E+09 |
November | 0.247939E+09 | 0.150968E+09 | 96970677.15 | 0.305891E+09 | 0.335668E+09 |
December | 0.206462E+09 | 0.112157E+09 | 94305573.05 | 0.215496E+09 | 0.442228E+09 |
Annual Sum or Average | 0.375917E+10 | 0.203961E+10 | 0.171956E+10 | 0.590171E+10 | 0.259008E+10 |
Minimum of Months | 0.206462E+09 | 0.112157E+09 | 94305573.05 | 0.215496E+09 | 47064309.06 |
Maximum of Months | 0.414456E+09 | 0.221752E+09 | 0.192704E+09 | 0.754812E+09 | 0.442228E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 699.09 | 544.23 | 553.19 | 386.69 | 166.50 | 0.00 | 0.00 |
February | 732.16 | 482.37 | 561.12 | 365.74 | 195.39 | 0.00 | 0.00 |
March | 747.17 | 409.38 | 550.04 | 308.81 | 241.23 | 0.00 | 0.00 |
April | 768.74 | 252.46 | 499.02 | 238.09 | 260.93 | 0.00 | 0.00 |
May | 785.65 | 158.54 | 455.82 | 188.89 | 266.93 | 0.00 | 0.00 |
June | 867.29 | 82.85 | 432.23 | 176.93 | 255.29 | 0.00 | 0.00 |
July | 810.53 | 67.57 | 401.29 | 152.40 | 248.89 | 0.00 | 0.00 |
August | 817.01 | 98.48 | 424.63 | 177.55 | 247.08 | 0.00 | 0.00 |
September | 919.30 | 187.17 | 515.96 | 279.88 | 236.09 | 0.00 | 0.00 |
October | 859.65 | 302.12 | 556.08 | 351.35 | 204.73 | 0.00 | 0.00 |
November | 795.83 | 473.88 | 596.04 | 423.07 | 172.97 | 0.00 | 0.00 |
December | 679.38 | 596.15 | 558.49 | 386.21 | 172.27 | 0.00 | 0.00 |
Annual Sum or Average | 790.10 | 303.75 | 508.20 | 285.72 | 222.48 | 0.00 | 0.00 |
Minimum of Months | 679.38 | 67.57 | 401.29 | 152.40 | 166.50 | 0.00 | 0.00 |
Maximum of Months | 919.30 | 596.15 | 596.04 | 423.07 | 266.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187245E+10 | 0.145766E+10 | 0.148166E+10 | 0.103572E+10 | 0.445943E+09 | 0.00 | 0.00 |
February | 0.177123E+10 | 0.116696E+10 | 0.135747E+10 | 0.884792E+09 | 0.472681E+09 | 0.00 | 0.00 |
March | 0.200122E+10 | 0.109649E+10 | 0.147323E+10 | 0.827105E+09 | 0.646122E+09 | 0.00 | 0.00 |
April | 0.199256E+10 | 0.654384E+09 | 0.129345E+10 | 0.617118E+09 | 0.676332E+09 | 0.00 | 0.00 |
May | 0.210429E+10 | 0.424639E+09 | 0.122087E+10 | 0.505914E+09 | 0.714954E+09 | 0.00 | 0.00 |
June | 0.224803E+10 | 0.214741E+09 | 0.112033E+10 | 0.458610E+09 | 0.661722E+09 | 0.00 | 0.00 |
July | 0.217092E+10 | 0.180977E+09 | 0.107481E+10 | 0.408180E+09 | 0.666627E+09 | 0.00 | 0.00 |
August | 0.218829E+10 | 0.263756E+09 | 0.113733E+10 | 0.475540E+09 | 0.661788E+09 | 0.00 | 0.00 |
September | 0.238283E+10 | 0.485137E+09 | 0.133738E+10 | 0.725441E+09 | 0.611938E+09 | 0.00 | 0.00 |
October | 0.230247E+10 | 0.809191E+09 | 0.148940E+10 | 0.941053E+09 | 0.548344E+09 | 0.00 | 0.00 |
November | 0.206279E+10 | 0.122830E+10 | 0.154495E+10 | 0.109660E+10 | 0.448344E+09 | 0.00 | 0.00 |
December | 0.181966E+10 | 0.159673E+10 | 0.149585E+10 | 0.103443E+10 | 0.461421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.249167E+11 | 0.957897E+10 | 0.160267E+11 | 0.901050E+10 | 0.701622E+10 | 0.00 | 0.00 |
Minimum of Months | 0.177123E+10 | 0.180977E+09 | 0.107481E+10 | 0.408180E+09 | 0.445943E+09 | 0.00 | 0.00 |
Maximum of Months | 0.238283E+10 | 0.159673E+10 | 0.154495E+10 | 0.109660E+10 | 0.714954E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.131315E+11 | -0.123522E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -779222051.2 | 60.05 | 0.00 | 0.00 |
February | 0.118299E+11 | -0.111463E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -683602645.3 | 60.05 | 0.00 | 0.00 |
March | 0.126631E+11 | -0.119247E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -738355521.0 | 60.05 | 0.00 | 0.00 |
April | 0.114375E+11 | -0.107617E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -675810845.5 | 60.05 | 0.00 | 0.00 |
May | 0.109204E+11 | -0.102373E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -683131197.3 | 60.05 | 0.00 | 0.00 |
June | 0.981369E+10 | -0.915704E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -656648899.5 | 60.05 | 0.00 | 0.00 |
July | 0.966360E+10 | -0.898622E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -677385261.4 | 60.05 | 0.00 | 0.00 |
August | 0.969658E+10 | -0.901855E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -678029028.1 | 60.05 | 0.00 | 0.00 |
September | 0.980698E+10 | -0.914738E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -659600290.1 | 60.05 | 0.00 | 0.00 |
October | 0.109347E+11 | -0.102398E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -694838591.8 | 60.05 | 0.00 | 0.00 |
November | 0.115079E+11 | -0.107868E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -721174570.0 | 60.05 | 0.00 | 0.00 |
December | 0.126812E+11 | -0.118968E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -784378980.1 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.134087E+12 | -0.125655E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.843218E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.966360E+10 | -0.123522E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -784378980.1 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.131315E+11 | -0.898622E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -656648899.5 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.27 | 0.24 | 01-JAN-07:00 | 1866.96 | 25.32 | 114.50 | 279.67 | 2367.42 | 26.40 | 130.83 | 276.67 |
February | 268.33 | 0.27 | 0.24 | 01-FEB-07:49 | 1512.09 | 22.84 | 87.00 | 270.17 | 1638.45 | 22.92 | 81.67 | 273.83 |
March | 351.83 | 0.27 | 0.24 | 01-MAR-06:00 | 1458.16 | 20.20 | 55.33 | 334.83 | 1317.71 | 17.89 | 4.67 | 332.50 |
April | 373.83 | 0.27 | 0.24 | 01-APR-06:19 | 1716.05 | 17.66 | 0.00 | 355.17 | 1499.09 | 17.65 | 0.00 | 362.33 |
May | 408.83 | 0.28 | 0.24 | 01-MAY-05:00 | 1103.79 | 17.35 | 0.00 | 381.33 | 1133.30 | 17.38 | 0.00 | 380.33 |
June | 398.00 | 0.27 | 0.24 | 01-JUN-05:00 | 1090.65 | 17.31 | 0.00 | 378.50 | 1115.22 | 17.32 | 0.00 | 373.17 |
July | 400.17 | 0.27 | 0.24 | 01-JUL-05:00 | 1029.15 | 17.33 | 0.00 | 391.33 | 1047.81 | 17.36 | 0.00 | 380.67 |
August | 377.83 | 0.27 | 0.24 | 01-AUG-05:49 | 1107.55 | 17.65 | 0.00 | 367.83 | 1499.41 | 17.61 | 0.00 | 362.83 |
September | 365.83 | 0.27 | 0.24 | 01-SEP-06:30 | 1354.46 | 17.84 | 5.67 | 337.67 | 1362.86 | 17.87 | 7.17 | 338.00 |
October | 318.83 | 0.27 | 0.24 | 01-OCT-06:00 | 1432.32 | 21.01 | 66.67 | 311.33 | 1417.72 | 20.83 | 59.33 | 315.33 |
November | 295.83 | 0.27 | 0.24 | 01-NOV-12:39 | 1822.93 | 23.76 | 110.00 | 284.83 | 1478.03 | 23.87 | 109.17 | 289.33 |
December | 289.50 | 0.27 | 0.24 | 01-DEC-07:10 | 3179.34 | 28.37 | 158.83 | 272.67 | 3177.96 | 29.36 | 167.33 | 276.50 |
Annual Sum or Average | 4125.67 | 0.27 | 1503.92 | 20.09 | 598.00 | 3965.33 | 1531.86 | 20.04 | 560.17 | 3961.50 | ||
Minimum of Months | 268.33 | 0.27 | 0.24 | 1029.15 | 17.31 | 0.00 | 270.17 | 1047.81 | 17.32 | 0.00 | 273.83 | |
Maximum of Months | 408.83 | 0.28 | 0.24 | 3179.34 | 28.37 | 158.83 | 391.33 | 3177.96 | 29.36 | 167.33 | 380.67 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105094E+11 | 64884.20 | 28-JAN-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.756293E+10 | 64884.20 | 03-FEB-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.520692E+10 | 64884.20 | 02-MAR-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.864135E+09 | 16868.01 | 15-APR-02:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57212825.26 | 15527.83 | 26-MAY-02:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30920136.39 | 16057.55 | 01-JUN-03:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4228474.11 | 5060.10 | 24-JUL-03:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23961036.36 | 12991.68 | 23-AUG-02:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33503169.91 | 9380.85 | 26-SEP-02:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.327621E+09 | 7584.61 | 31-OCT-02:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.535750E+10 | 27610.77 | 28-NOV-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139034E+11 | 64884.20 | 19-DEC-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4228474.11 | 5060.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139034E+11 | 64884.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.361396E+10 | 24653.79 | 05-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260266E+10 | 24363.91 | 02-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137815E+10 | 22753.48 | 02-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63402404.52 | 5043.74 | 12-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132853E+10 | 15089.93 | 28-NOV-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.563703E+10 | 25266.01 | 19-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.563703E+10 | 25266.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 619680.83 | 619680.83 | 480.30 | 03-JAN-15:00 | 480.30 | 0.00 |
February | 0.00 | 0.00 | 0.355558E+09 | 0.355558E+09 | 5724.38 | 06-FEB-14:00 | 5724.38 | 0.00 |
March | 0.00 | 0.00 | 0.102639E+10 | 0.102639E+10 | 9399.04 | 22-MAR-13:00 | 9399.04 | 0.00 |
April | 0.00 | 0.00 | 0.852234E+10 | 0.846221E+10 | 48155.58 | 03-APR-02:61 | 48155.58 | 0.00 |
May | 0.00 | 0.00 | 0.176513E+11 | 0.169092E+11 | 48155.58 | 04-MAY-02:61 | 41537.43 | 0.00 |
June | 0.00 | 0.00 | 0.266948E+11 | 0.251959E+11 | 48155.58 | 18-JUN-02:21 | 42019.23 | 0.00 |
July | 0.00 | 0.00 | 0.329203E+11 | 0.252448E+11 | 52626.46 | 17-JUL-02:61 | 18772.95 | 0.00 |
August | 0.00 | 0.00 | 0.271828E+11 | 0.227878E+11 | 51203.05 | 02-AUG-02:61 | 28564.59 | 0.00 |
September | 0.00 | 0.00 | 0.206761E+11 | 0.171200E+11 | 50855.22 | 22-SEP-02:61 | 24466.96 | 0.00 |
October | 0.00 | 0.00 | 0.814940E+10 | 0.703374E+10 | 49386.21 | 04-OCT-02:61 | 25739.56 | 0.00 |
November | 0.00 | 0.00 | 0.521791E+09 | 0.509988E+09 | 48155.58 | 10-NOV-03:01 | 43488.68 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143701E+12 | 0.124646E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.329203E+11 | 0.252448E+11 | 52626.46 | 48155.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.112633E+09 | 0.100917E+09 | 17487.63 | 03-JAN-04:21 | 12964.25 | 0.00 |
February | 0.00 | 0.00 | 0.100555E+10 | 0.984958E+09 | 35015.43 | 07-FEB-04:21 | 32178.68 | 0.00 |
March | 0.00 | 0.00 | 0.236531E+10 | 0.233398E+10 | 35015.43 | 07-MAR-05:01 | 31032.84 | 0.00 |
April | 0.00 | 0.00 | 0.115689E+11 | 0.112790E+11 | 35015.43 | 01-APR-02:61 | 33976.76 | 0.00 |
May | 0.00 | 0.00 | 0.227481E+11 | 0.213998E+11 | 35015.43 | 18-MAY-02:11 | 27905.16 | 0.00 |
June | 0.00 | 0.00 | 0.342166E+11 | 0.315965E+11 | 35015.43 | 25-JUN-02:34 | 21857.34 | 0.00 |
July | 0.00 | 0.00 | 0.438692E+11 | 0.322267E+11 | 37891.08 | 21-JUL-02:11 | 11748.64 | 0.00 |
August | 0.00 | 0.00 | 0.361144E+11 | 0.288370E+11 | 37205.83 | 02-AUG-03:46 | 15362.85 | 0.00 |
September | 0.00 | 0.00 | 0.276393E+11 | 0.212792E+11 | 37181.75 | 22-SEP-02:61 | 13261.31 | 0.00 |
October | 0.00 | 0.00 | 0.131221E+11 | 0.103583E+11 | 35202.57 | 04-OCT-02:11 | 15648.79 | 0.00 |
November | 0.00 | 0.00 | 0.171942E+10 | 0.153903E+10 | 35015.43 | 01-NOV-02:61 | 19060.94 | 0.00 |
December | 0.00 | 0.00 | 50280806.95 | 43595401.02 | 35015.43 | 01-DEC-05:01 | 26491.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.194532E+12 | 0.161979E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 50280806.95 | 43595401.02 | 17487.63 | 11748.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.438692E+11 | 0.322267E+11 | 37891.08 | 33976.76 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4593.23 | 17724.88 | 30-JAN-13:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 4588.84 | 17722.97 | 01-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 4433.33 | 17389.59 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4133.07 | 16446.74 | 01-APR-12:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 3803.44 | 15205.40 | 01-MAY-12:20 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 3514.48 | 13930.03 | 01-JUN-12:20 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 3337.19 | 13034.50 | 01-JUL-13:00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 3349.10 | 13044.80 | 31-AUG-13:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 3510.86 | 13947.73 | 30-SEP-12:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3804.45 | 15226.11 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4142.69 | 16464.76 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4423.09 | 17399.87 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 3965.97 | ||||
Minimum of Months | 0.00 | 0.00 | 3337.19 | 13034.50 | ||
Maximum of Months | 0.00 | 0.00 | 4593.23 | 17724.88 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117916E+10 | 0.27 | 503.64 | 01-JAN-00:03 | 0.31 |
February | 0.107773E+10 | 0.27 | 503.64 | 01-FEB-00:03 | 0.31 |
March | 0.120528E+10 | 0.27 | 503.64 | 01-MAR-00:03 | 0.31 |
April | 0.121602E+10 | 0.28 | 503.64 | 01-APR-02:61 | 0.31 |
May | 0.128597E+10 | 0.29 | 503.64 | 01-MAY-00:15 | 0.31 |
June | 0.124616E+10 | 0.29 | 503.64 | 01-JUN-00:07 | 0.31 |
July | 0.128825E+10 | 0.29 | 503.64 | 01-JUL-00:05 | 0.30 |
August | 0.128835E+10 | 0.29 | 503.64 | 01-AUG-00:05 | 0.30 |
September | 0.124441E+10 | 0.29 | 503.64 | 01-SEP-00:09 | 0.30 |
October | 0.126714E+10 | 0.28 | 503.64 | 01-OCT-00:19 | 0.30 |
November | 0.117017E+10 | 0.27 | 503.64 | 01-NOV-02:61 | 0.30 |
December | 0.117440E+10 | 0.27 | 503.64 | 01-DEC-00:03 | 0.30 |
Annual Sum or Average | 0.146430E+11 | 0.28 | |||
Minimum of Months | 0.107773E+10 | 0.27 | 503.64 | 0.30 | |
Maximum of Months | 0.128835E+10 | 0.29 | 503.64 | 0.31 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.285919E+10 | 0.56 | 2882.31 | 28-JAN-04:50 | 1.02 |
February | 0.253837E+10 | 0.55 | 2882.31 | 03-FEB-03:03 | 1.02 |
March | 0.271839E+10 | 0.53 | 2882.31 | 02-MAR-03:03 | 1.02 |
April | 0.252050E+10 | 0.53 | 1440.54 | 12-APR-06:10 | 0.71 |
May | 0.260113E+10 | 0.54 | 1861.61 | 31-MAY-02:61 | 0.82 |
June | 0.254251E+10 | 0.54 | 2602.81 | 15-JUN-02:61 | 0.97 |
July | 0.264525E+10 | 0.53 | 2882.31 | 03-JUL-02:61 | 1.01 |
August | 0.262612E+10 | 0.53 | 2882.31 | 02-AUG-02:61 | 1.00 |
September | 0.253846E+10 | 0.53 | 2882.31 | 22-SEP-02:61 | 1.00 |
October | 0.259903E+10 | 0.53 | 2449.81 | 02-OCT-02:61 | 0.94 |
November | 0.263508E+10 | 0.53 | 1536.07 | 28-NOV-07:05 | 0.73 |
December | 0.296952E+10 | 0.57 | 2882.31 | 19-DEC-03:05 | 1.02 |
Annual Sum or Average | 0.317935E+11 | 0.54 | |||
Minimum of Months | 0.252050E+10 | 0.53 | 1440.54 | 0.71 | |
Maximum of Months | 0.296952E+10 | 0.57 | 2882.31 | 1.02 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142201E+10 | 0.55 | 953.39 | 05-JAN-05:04 | 0.81 |
February | 0.128014E+10 | 0.55 | 1529.42 | 07-FEB-05:01 | 1.02 |
March | 0.140199E+10 | 0.55 | 1529.42 | 07-MAR-05:01 | 1.02 |
April | 0.137010E+10 | 0.56 | 1529.42 | 04-APR-02:11 | 1.02 |
May | 0.146910E+10 | 0.58 | 1529.42 | 01-MAY-02:11 | 1.01 |
June | 0.163579E+10 | 0.61 | 1529.42 | 01-JUN-02:61 | 1.01 |
July | 0.182292E+10 | 0.64 | 1529.42 | 01-JUL-02:61 | 1.00 |
August | 0.165454E+10 | 0.61 | 1529.42 | 01-AUG-02:61 | 1.00 |
September | 0.151501E+10 | 0.59 | 1529.42 | 01-SEP-02:61 | 1.00 |
October | 0.143989E+10 | 0.57 | 1529.42 | 01-OCT-02:11 | 1.01 |
November | 0.135888E+10 | 0.55 | 1529.42 | 01-NOV-02:61 | 1.01 |
December | 0.144948E+10 | 0.55 | 1529.42 | 01-DEC-05:01 | 1.02 |
Annual Sum or Average | 0.178199E+11 | 0.58 | |||
Minimum of Months | 0.128014E+10 | 0.55 | 953.39 | 0.81 | |
Maximum of Months | 0.182292E+10 | 0.64 | 1529.42 | 1.02 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 52.16 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 53.29 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 53.41 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 53.77 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 53.15 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 54.72 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:03 | 0.00 | 0.00 | 55.06 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 55.20 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 55.06 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 53.71 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 54.22 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 53.75 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 52.16 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 55.20 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 40.99 | 40.99 | 4593.23 | 17724.88 | 30-JAN-13:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 53.29 | 53.29 | 4588.84 | 17722.97 | 01-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 53.41 | 53.41 | 4433.33 | 17389.59 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 53.76 | 53.76 | 4133.07 | 16446.74 | 01-APR-12:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 43.35 | 43.35 | 3803.44 | 15205.40 | 01-MAY-12:20 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 54.71 | 54.71 | 3514.48 | 13930.03 | 01-JUN-12:20 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 55.06 | 55.06 | 3337.19 | 13034.50 | 01-JUL-13:00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 55.20 | 55.20 | 3349.10 | 13044.80 | 31-AUG-13:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 55.06 | 55.06 | 3510.86 | 13947.73 | 30-SEP-12:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 44.77 | 44.77 | 3804.45 | 15226.11 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 54.23 | 54.23 | 4142.69 | 16464.76 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 53.76 | 53.76 | 4423.09 | 17399.87 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 3965.97 | ||||||
Minimum of Months | 0.00 | 0.00 | 40.99 | 40.99 | 3337.19 | 13034.50 | ||
Maximum of Months | 0.00 | 0.00 | 55.20 | 55.20 | 4593.23 | 17724.88 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.285938E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.264422E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.301886E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.488114E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.740852E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.987535E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.112518E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.984100E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.799110E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.481874E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.278724E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.296952E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.703468E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.264422E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.112518E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.145495E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.156818E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.207475E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.441559E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.728538E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.105369E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.125123E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.106319E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.833973E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.483417E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.184133E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.146391E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.669591E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.145495E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.125123E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.285919E+10 | 619680.83 | 0.105094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253837E+10 | 0.355558E+09 | 0.756293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271839E+10 | 0.102639E+10 | 0.520692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252050E+10 | 0.851339E+10 | 0.864135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.260113E+10 | 0.175812E+11 | 57212825.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.254251E+10 | 0.265221E+11 | 30920136.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.264525E+10 | 0.326794E+11 | 4228474.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.262612E+10 | 0.269539E+11 | 23961036.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.253846E+10 | 0.205551E+11 | 33503169.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259903E+10 | 0.812299E+10 | 0.327621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.263508E+10 | 0.520809E+09 | 0.535750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296952E+10 | 0.00 | 0.139034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317935E+11 | 0.142831E+12 | 0.438818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.252050E+10 | 0.00 | 4228474.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.296952E+10 | 0.326794E+11 | 0.139034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142201E+10 | 0.112633E+09 | 0.361396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128014E+10 | 0.100174E+10 | 0.260266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140199E+10 | 0.235150E+10 | 0.137815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137010E+10 | 0.115205E+11 | 63402404.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146910E+10 | 0.225324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163579E+10 | 0.337137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182292E+10 | 0.431858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165454E+10 | 0.355101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151501E+10 | 0.273727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143989E+10 | 0.130394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135888E+10 | 0.170510E+10 | 0.132853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144948E+10 | 50280806.95 | 0.563703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178199E+11 | 0.192096E+12 | 0.146237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128014E+10 | 50280806.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182292E+10 | 0.431858E+11 | 0.563703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.285919E+10 | 0.00 | 0.00 | 0.00 | 191481.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253837E+10 | 0.00 | 0.00 | 0.00 | 0.105853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271839E+10 | 0.00 | 0.00 | 0.00 | 0.300474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252050E+10 | 0.00 | 0.00 | 0.00 | 0.236064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.260113E+10 | 0.00 | 0.00 | 0.00 | 0.480739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.254251E+10 | 0.00 | 0.00 | 0.00 | 0.733284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.264525E+10 | 0.00 | 0.00 | 0.00 | 0.860651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.262612E+10 | 0.00 | 0.00 | 0.00 | 0.721488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.253846E+10 | 0.00 | 0.00 | 0.00 | 0.545264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259903E+10 | 0.00 | 0.00 | 0.00 | 0.221971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.263508E+10 | 0.00 | 0.00 | 0.00 | 0.152159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317935E+11 | 0.00 | 0.00 | 0.00 | 0.385533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.252050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.296952E+10 | 0.00 | 0.00 | 0.00 | 0.860651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142201E+10 | 0.00 | 0.00 | 0.00 | 32939908.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128014E+10 | 0.00 | 0.00 | 0.00 | 0.288041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140199E+10 | 0.00 | 0.00 | 0.00 | 0.672765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137010E+10 | 0.00 | 0.00 | 0.00 | 0.304548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146910E+10 | 0.00 | 0.00 | 0.00 | 0.581628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163579E+10 | 0.00 | 0.00 | 0.00 | 0.890109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182292E+10 | 0.00 | 0.00 | 0.00 | 0.106894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165454E+10 | 0.00 | 0.00 | 0.00 | 0.897738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151501E+10 | 0.00 | 0.00 | 0.00 | 0.682472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143989E+10 | 0.00 | 0.00 | 0.00 | 0.339428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135888E+10 | 0.00 | 0.00 | 0.00 | 0.482447E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144948E+10 | 0.00 | 0.00 | 0.00 | 14428014.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178199E+11 | 0.00 | 0.00 | 0.00 | 0.491393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128014E+10 | 0.00 | 0.00 | 0.00 | 14428014.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182292E+10 | 0.00 | 0.00 | 0.00 | 0.106894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.590998E+10 | 0.00 | 0.00 | 754756.40 | 0.00 | 0.846040E+10 | 0.398902E+09 | 0.00 | 3.63 |
February | 0.493299E+10 | 0.00 | 0.00 | 5093916.33 | 0.00 | 0.612031E+10 | 0.166767E+10 | 0.00 | 4.25 |
March | 0.548221E+10 | 0.00 | 0.00 | 10586182.77 | 0.00 | 0.392261E+10 | 0.301119E+10 | 0.00 | 4.75 |
April | 0.293097E+10 | 0.251310E+09 | 0.00 | 27748078.84 | 25273.49 | 0.564967E+09 | 0.346963E+10 | 0.00 | 5.19 |
May | 0.949173E+09 | 0.129875E+10 | 423284.84 | 27186309.27 | 557452.79 | 4949965.33 | 0.285563E+10 | 134612.04 | 5.08 |
June | 85439807.42 | 0.352809E+10 | 2888442.08 | 13490680.57 | 15143541.70 | 558191.03 | 0.130145E+10 | 232853.02 | 4.70 |
July | 66485880.46 | 0.576655E+10 | 1302837.54 | 4984139.13 | 31063125.40 | 0.00 | 0.728984E+09 | 38277.46 | 4.95 |
August | 0.107506E+09 | 0.354279E+10 | 2147977.72 | 13300038.22 | 21204635.95 | 57330.37 | 0.186436E+10 | 207787.84 | 5.25 |
September | 0.653736E+09 | 0.206010E+10 | 809644.96 | 24077609.48 | 3047657.01 | 4180499.68 | 0.306774E+10 | 45630.59 | 5.46 |
October | 0.348619E+10 | 0.418795E+09 | 307873.24 | 28698582.95 | 597186.19 | 0.126244E+09 | 0.519619E+10 | 12669.48 | 5.81 |
November | 0.586014E+10 | 0.00 | 0.00 | 8679087.31 | 0.00 | 0.418028E+10 | 0.286802E+10 | 0.00 | 4.43 |
December | 0.559442E+10 | 0.00 | 0.00 | 277361.44 | 0.00 | 0.111603E+11 | 0.237546E+09 | 0.00 | 3.56 |
Annual Sum or Average | 0.360592E+11 | 0.168664E+11 | 7880060.37 | 0.164877E+09 | 71638872.52 | 0.345449E+11 | 0.266673E+11 | 671830.42 | 4.76 |
Minimum of Months | 66485880.46 | 0.00 | 0.00 | 277361.44 | 0.00 | 0.00 | 0.237546E+09 | 0.00 | 3.56 |
Maximum of Months | 0.590998E+10 | 0.576655E+10 | 2888442.08 | 28698582.95 | 31063125.40 | 0.111603E+11 | 0.519619E+10 | 232853.02 | 5.81 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.317711E+11 | 0.00 | 0.00 | 6461647.76 | 0.00 | 2151885.93 | 0.658902E+10 | 0.00 | 8.18 |
February | 0.222383E+11 | 0.00 | 0.00 | 20717581.21 | 0.00 | 0.00 | 0.107987E+11 | 0.00 | 8.22 |
March | 0.185842E+11 | 0.00 | 0.00 | 37301754.61 | 0.00 | 0.00 | 0.154359E+11 | 0.00 | 8.25 |
April | 0.640759E+10 | 2719947.36 | 0.00 | 80938776.57 | 0.00 | 0.00 | 0.168062E+11 | 0.00 | 8.45 |
May | 0.166709E+10 | 0.244387E+09 | 0.00 | 0.105966E+09 | 0.00 | 0.00 | 0.128812E+11 | 0.00 | 8.69 |
June | 0.237005E+09 | 0.367668E+10 | 0.00 | 82747936.59 | 2311120.19 | 0.00 | 0.549776E+10 | 0.00 | 9.14 |
July | 0.157728E+09 | 0.843852E+10 | 0.00 | 29808310.67 | 14545262.62 | 0.00 | 0.159631E+10 | 0.00 | 9.50 |
August | 0.287015E+09 | 0.341480E+10 | 0.00 | 75694794.82 | 6606860.79 | 0.00 | 0.506256E+10 | 0.00 | 9.15 |
September | 0.121739E+10 | 0.120742E+10 | 0.00 | 94098002.10 | 1202222.97 | 0.00 | 0.932648E+10 | 0.00 | 8.96 |
October | 0.477141E+10 | 0.236360E+09 | 0.00 | 86494764.91 | 331233.08 | 0.00 | 0.190736E+11 | 0.00 | 8.55 |
November | 0.195664E+11 | 0.00 | 0.00 | 32567431.18 | 0.00 | 0.00 | 0.150191E+11 | 0.00 | 8.21 |
December | 0.350188E+11 | 0.00 | 0.00 | 5165380.50 | 0.00 | 0.00 | 0.598848E+10 | 0.00 | 8.19 |
Annual Sum or Average | 0.141924E+12 | 0.172209E+11 | 0.00 | 0.657962E+09 | 24996699.65 | 2151885.93 | 0.124075E+12 | 0.00 | 8.63 |
Minimum of Months | 0.157728E+09 | 0.00 | 0.00 | 5165380.50 | 0.00 | 0.00 | 0.159631E+10 | 0.00 | 8.18 |
Maximum of Months | 0.350188E+11 | 0.843852E+10 | 0.00 | 0.105966E+09 | 14545262.62 | 2151885.93 | 0.190736E+11 | 0.00 | 9.50 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:35
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.344528E+11 | 0.144796E+11 | 0.829508E+11 | 0.123727E+09 | 0.236938E+11 |
February | 0.378551E+11 | 0.115441E+11 | 0.711045E+11 | 0.775016E+09 | 0.254196E+11 |
March | 0.589529E+11 | 0.111194E+11 | 0.729025E+11 | 0.143654E+10 | 0.318508E+11 |
April | 0.662188E+11 | 0.564921E+10 | 0.492547E+11 | 0.163495E+10 | 0.537967E+11 |
May | 0.727861E+11 | 0.174856E+10 | 0.298954E+11 | 0.133354E+10 | 0.816118E+11 |
June | 0.715215E+11 | -0.199686E+10 | 0.545403E+10 | 0.632421E+09 | 0.109335E+12 |
July | 0.684163E+11 | -0.433678E+10 | -0.108951E+11 | 0.262863E+09 | 0.129248E+12 |
August | 0.628436E+11 | -0.169375E+10 | 0.457019E+10 | 0.903207E+09 | 0.112069E+12 |
September | 0.566084E+11 | 0.578756E+09 | 0.200131E+11 | 0.128574E+10 | 0.918112E+11 |
October | 0.481922E+11 | 0.598867E+10 | 0.513181E+11 | 0.249229E+10 | 0.551018E+11 |
November | 0.363730E+11 | 0.117483E+11 | 0.749372E+11 | 0.127786E+10 | 0.269017E+11 |
December | 0.290507E+11 | 0.156940E+11 | 0.879371E+11 | 7953869.96 | 0.248617E+11 |
Annual Sum or Average | 0.643271E+12 | 0.705233E+11 | 0.539443E+12 | 0.121661E+11 | 0.765701E+12 |
Minimum of Months | 0.290507E+11 | -0.433678E+10 | -0.108951E+11 | 7953869.96 | 0.236938E+11 |
Maximum of Months | 0.727861E+11 | 0.156940E+11 | 0.879371E+11 | 0.249229E+10 | 0.129248E+12 |