Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2024-07-03 12:19:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1240.13 | 5337.48 | 5337.48 |
Net Site Energy | 1240.13 | 5337.48 | 5337.48 |
Total Source Energy | 2646.86 | 11392.03 | 11392.03 |
Net Source Energy | 2646.86 | 11392.03 | 11392.03 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 225.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 21.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 252.09 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 67.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 137.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 40.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 625.33 | 614.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 225.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 21.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 67.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 137.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 12.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 19.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 225.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 21.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 15.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 252.09 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 67.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 137.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 40.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1271.32 | 592.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1258.52 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2691.40 | 2646.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1271.32 | 592.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1258.52 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2691.40 | 2646.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 625.329 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 625.329 | 100.00 |
Total On-Site and Utility Electric Sources | 625.329 | 100.00 |
Total Electricity End Uses | 625.329 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1972.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6087.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 HP COOLING COIL | PSZ-AC_2:2 HP COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1_SUPPHEATCOIL | PSZ-AC_2:2_SUPPHEATCOIL | PSZ-AC_1:1 HP COOLING COIL | PSZ-AC_2:2 HP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 4.6627 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.9536 | 18.52 | 1067.3199 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 7.3082 | 2.48 | 592.0534 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 7.3082 | 2.48 | 592.0534 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 4.6627 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.9536 | 18.52 | 1067.3199 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 7.3082 | 1.24 | 592.0534 | |||||||
Conditioned Total | 232.34 | 7.3082 | 1.24 | 592.0534 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 7.3082 | 2.48 | 592.0534 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUN-17:10 | 16-JAN-13:20 | - | - | - | - | - | - | - | - | - | - | 12-MAY-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25202.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1008.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 11387.73 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4332.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19453.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1257.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 43188.34 | 42436.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 25202.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1008.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 10796.93 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4332.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 19453.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 426.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 8.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 715.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 69.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 798.38 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 212.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 149.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 127.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1980.42 | 666.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 35.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3077.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 299.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 212.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3436.21 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 913.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 642.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 549.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8523.68 | 2868.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 35.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3077.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 299.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 212.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3436.21 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 913.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 642.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 549.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8523.68 | 2868.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.40 |
KITCHEN DIRECT AIR | 1.14 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.40 | 2.40 | 2.40 | 2.40 | 2.40 | 2.40 | 1.00 | 1.00 | 2.40 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.40 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.14 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.40 | 2573.12 |
PSZ-AC_2:2_ADDAQ FAN | 1.14 | 1263.64 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | User-Specified Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.40 | 2.40 | 2.40 | 1.59 | 58471.47 | 37703.39 | 40.00 | 56273.71 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.753280 | 28342.03 | 18989.16 | 40.00 | 28342.03 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 HP COOLING COIL | 2.40 | 1.20 | 1.60 | 58471.47 | 29235.74 | 0.708290 | 0.708290 |
PSZ-AC_2:2 HP COOLING COIL | 1.14 | 0.570667 | 0.760887 | 28342.03 | 14171.01 | 0.701080 | 0.701080 |
Design Size Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | Design Size Speed 2 Gross Rated Heating Capacity [W] | Design Size Speed 1 Gross Rated Heating Capacity [W] | Design Size Resistive Defrost Heater Capacity | |
PSZ-AC_1:1 HEATING COIL | 2.40 | 1.20 | 56273.71 | 28136.86 | 0.000000 |
PSZ-AC_2:2 HEATING COIL | 1.14 | 0.570667 | 28341.94 | 14170.97 | 0.000000 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_SUPPHEATCOIL | 56273.71 |
PSZ-AC_2:2_SUPPHEATCOIL | 28342.03 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 4.663 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 121.450 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.954 | 275.967 | 791.353 | 0.000 | 0.000 | 0.000 | 1077.273 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 541.679 | 4.663 | 6.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 541.679 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1156.323 | 9.954 | 184.325 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1156.323 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 277.500 | 2.389 | 44.235 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 313.300 | 2.697 | 49.942 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.6929 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.33002231E-12 | 0.10712597E-14 | -0.10720425E-12 | 0.10137879E-15 |
34 | 6 | 0.29661659E-07 | 0.19687232E-09 | 0.67865745E-08 | -0.14052424E-12 |
35 | 5 | -0.19512200E-03 | 0.16741682E-05 | -0.10029371E-03 | 0.67057946E-08 |
36 | 4 | 0.29799499 | 0.81016957E-03 | 0.10178761 | -0.34398158E-04 |
37 | 3 | -7.3821031 | 0.24971312E-01 | -2.3732702 | 0.29576512E-01 |
38 | 2 | 41.252923 | 0.88368331E-01 | 15.405914 | -0.33759269 |
39 | 1 | -80.838295 | 0.39713828E-01 | -29.267905 | 1.0848528 |
40 | 0 | 46.824337 | 0.79570062E-03 | 16.288235 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.23 | 38 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 | ||
2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.23 | 39 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 | ||
3 | NONRESWINDOW_U_0.503_SHGC_EAST_0.23 | 40 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 | ||
4 | NONRESWINDOW_U_0.503_SHGC_WEST_0.23 | 41 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 21.722 | 0.5184 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 2.382E-002 | 2.051E-004 | 2.563E-004 | 0.242 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 2.382E-002 | 2.051E-004 | 2.510E-004 | 0.242 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5320E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1901E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.4027E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0695E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.2728E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.2194E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0078E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0016E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.4811E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.3846E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.8212E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.7076E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.6945E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.6355E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0845E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0846E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.8065E-003 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3087E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.2367E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1307E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.5142E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0397E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0017E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0078E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 31816.49763 | 31816.49763 | 2.40467 | 2.40467 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00000 | 9.15790E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 2245.47723 | 2245.47723 | 9.63321E-002 | 0.41606 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 6.30000 | 6.07234E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16097.02250 | 16097.02250 | 1.01315 | 1.14133 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 41.12700 | 9.15644E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | 00:10:00 | 6.30000 | 6.07234E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 40305.13 | 2.40467 | 2.40467 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 16537.72 | 0.41606 | 0.41606 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 39308.74 | 1.14133 | 1.14133 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 45366.59 | 1.14133 | 1.14133 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.40467 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14133 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.40467 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.40467 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.40467 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.40467 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.40467 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.40467 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14133 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14133 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14133 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14133 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14133 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14133 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.40467 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.14133 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.40467 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.40467 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2573.11571 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.40467 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.40467 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.40467 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.58709 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.40467 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.20234 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.60311 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 58471.47000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 29235.73500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70829 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70829 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 58471.47000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37703.38678 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 56273.71161 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 2.40467 |
42 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.20234 |
43 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 56273.71161 |
44 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 28136.85581 |
45 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
46 | Coil:Heating:Electric | PSZ-AC_1:1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 56273.71161 |
47 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14133 |
48 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
49 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14133 |
50 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1263.63741 |
51 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14133 |
52 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14133 |
53 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14133 |
54 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75328 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14133 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57067 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76089 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28342.03000 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14171.01500 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28342.03000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18989.16004 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 28342.02991 |
66 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
67 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.14133 |
68 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57067 |
69 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 28341.94189 |
70 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 14170.97095 |
71 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
72 | Coil:Heating:Electric | PSZ-AC_2:2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 28342.02991 |
73 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
74 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
75 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
76 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
77 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | 56759.2 | 11.45 | 11.40 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | 27530.8 | 11.67 | 11.61 |
Component Type | Component Name | High Temperature Heating (net) Rating Capacity {W} | Low Temperature Heating (net) Rating Capacity {W} | HSPF {Btu/W-h} | Region Number | |
1 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | 58201.5 | 32073.9 | 8.03 | 2 |
2 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | 29258.9 | 16099.9 | 8.11 | 2 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_EAST_0.23 | N/A | 2.860 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.23 | N/A | 2.860 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_WEST_0.23 | N/A | 2.860 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 6.5535643621E-002 | 0.2178548757 | Pass | Pass | 0.1943005132 | 0.6487844074 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2516969582 | 0.6170813212 | Pass | Pass | 5.4995005795E-002 | 0.3198735257 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4233151486 | 0.4115067039 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 516.81 | -73.4 | -35.9 | 9.10 | 0.154861E+11 | 0.154861E+11 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.503_SHGC_EAST_0.23 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.860 | 0.231 | 0.254 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.23 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.860 | 0.231 | 0.254 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.503_SHGC_WEST_0.23 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.860 | 0.231 | 0.254 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.860 | 0.231 | 0.254 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.860 | 0.231 | 0.254 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 4.6627 | 116.17 | 541.68 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 43.78 | 0.0000 | Y | 4.45 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.9536 | 116.17 | 1156.32 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 80.60 | 0.0000 | Y | 17.50 |
Interior Lighting Total | 7.3082 | 232.34 | 1698.00 | 21.95 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 541.68 | 205.84 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 541.68 | 205.84 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 218.22 | AstronomicalClock | - | 48.75 | 48.75 | 2.00 | |
EXTERIOR_LIGHTS_B | 1154.09 | AstronomicalClock | - | 83.75 | 62.75 | 13.59 | |
Exterior Lighting Total | 1372.31 | 15.59 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 58471.47 | 41414.76 | 17056.71 | 0.71 | 3.67 | |||
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28342.03 | 19870.03 | 8472.00 | 0.70 | 3.74 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 HP COOLING COIL | 56759.2 | 11.45 | 11.40 | ||||
PSZ-AC_2:2 HP COOLING COIL | 27530.8 | 11.67 | 11.61 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 58201.5 | 32073.9 | 8.03 | 2 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 29258.9 | 16099.9 | 8.11 | 2 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 56273.71 | 3.49 | |
PSZ-AC_1:1_SUPPHEATCOIL | Coil:Heating:Electric | 56273.71 | 1.00 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 28341.94 | 3.55 | |
PSZ-AC_2:2_SUPPHEATCOIL | Coil:Heating:Electric | 28342.03 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.40 | 2573.12 | 1070.05 | 1.00 | 1.29 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1263.64 | 1107.16 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 21.72 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 31816.50 | 31816.50 | 273.88 | 2.405 | 2.405 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 23.89 | 23.88 | 0.00811 | 42.00 | 0.00916 | 0.416 | 0.00 |
KITCHEN | 16097.02 | 16097.02 | 138.56 | 1.013 | 1.141 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 26.11 | 26.10 | 0.00873 | 41.13 | 0.00916 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 2245.48 | 2245.48 | 19.33 | 0.096 | 0.416 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00796 | 6.30 | 0.00607 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | 00:10:00 | 15.56 | 25.15 | 0.00182 | 6.30 | 0.00607 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.40 | 2.40 | 0.42 | 0.42 | 2.4047 | 2.4047 | 2.4047 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.1413 | 1.1413 | 1.1413 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 58471.470 | 41414.757 | 2.404670 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 29235.74 | 24918.86 | 1.603113 | 27.01 | 16.99 | 0.00828940 | 11.91 | 9.95 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 25.9530 | 23.88 | 0.00810769 | 42.8864 | 31816.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 56273.712 | 56273.712 | 2.404675 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 28136.86 | 28136.86 | 1.202337 | 18.55 | 13.34 | 0.00764988 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 34.6039 | 20.76 | 0.00797993 | 51.0372 | 1213.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_1:1 | 56273.712 | 56273.712 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 56273.71 | 56273.71 | 2.404675 | 18.55 | 13.34 | 0.00764988 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 17.3020 | 20.76 | 0.00797993 | 51.0372 | 1213.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28342.030 | 19870.030 | 1.141330 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14171.01 | 12189.99 | 0.760887 | 42.00 | 22.26 | 0.00915790 | 11.88 | 9.94 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 150.0005 | 26.09 | 0.00889795 | 41.1929 | 14594.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28342.030 | 28342.030 | 1.141334 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14170.97 | 14170.97 | 0.570667 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 200.0000 | 25.15 | 0.00181757 | 9.0003 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_2:2 | 28342.030 | 28342.030 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 28342.03 | 28342.03 | 1.141334 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 100.0000 | 25.15 | 0.00181757 | 9.0003 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 58471.470 | 41414.757 | 2.404670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2496 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.404675 | 2.82257232 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | Sensible | 29235.74 | 24918.86 | 1.0000 | 1.88171112 | 1.603113 | 27.01 | 16.99 | 0.00828940 | 48288.8 | 11.91 | 9.95 | 0.00700000 | 29625.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29235.74 | 42.00 | 0.00915790 | 22.26 | 0.41605618 | 25.9530 | 23.87 | 0.00810769 | 23.88 | 0.00810769 | 42.8864 | 31816.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 56273.712 | 56273.712 | 2.404675 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.404675 | 2.82257232 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 28136.86 | 28136.86 | 1.0000 | 1.41128616 | 1.202337 | 18.55 | 13.34 | 0.00764988 | 38033.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28136.86 | 6.30 | 0.00607234 | 6.30 | 0.41605618 | 34.6039 | 21.11 | 0.00797993 | 20.76 | 0.00797993 | 51.0372 | 1213.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56273.712 | 56273.712 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.404675 | 2.82257232 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 56273.71 | 56273.71 | 1.0000 | 2.82257232 | 2.404675 | 18.55 | 13.34 | 0.00764988 | 38033.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56273.71 | 6.30 | 0.00607234 | 6.30 | 0.41605618 | 17.3020 | 21.11 | 0.00797993 | 20.76 | 0.00797993 | 51.0372 | 1213.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28342.030 | 19870.030 | 1.141330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8641 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.141334 | 1.33968072 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14171.01 | 12189.99 | 1.0000 | 0.89311771 | 0.760887 | 42.00 | 22.26 | 0.00915790 | 65821.7 | 11.88 | 9.94 | 0.00700000 | 29595.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14171.01 | 42.00 | 0.00915790 | 22.26 | 1.14133354 | 150.0005 | 26.04 | 0.00889795 | 26.09 | 0.00889795 | 41.1929 | 14594.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 28342.030 | 28342.030 | 1.141334 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.141334 | 1.33968072 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14170.97 | 14170.97 | 1.0000 | 0.66984036 | 0.570667 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14170.97 | 6.30 | 0.00607234 | 6.30 | 1.14133354 | 200.0000 | 0.00 | 0.00181757 | 25.15 | 0.00181757 | 9.0003 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28342.030 | 28342.030 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.141334 | 1.33968072 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 28342.03 | 28342.03 | 1.0000 | 1.33968072 | 1.141334 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28342.03 | 6.30 | 0.00607234 | 6.30 | 1.14133354 | 100.0000 | 0.00 | 0.00181757 | 25.15 | 0.00181757 | 9.0003 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 5609.83 | 3692.00 | 2480.17 |
KITCHEN | 6778.00 | 6390.17 | 6079.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6785.50 | 7130.00 | 6087.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 120.83 | 0.00 | 2.67 |
KITCHEN | 0.00 | 2378.83 | 0.00 | 1970.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 2406.17 | 0.00 | 1972.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.361 | 4.102 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.663 | 0.005 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 3.981 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 7.266 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 11257172.17 | 0.00 | 11257172.17 | 10140925.33 | 21398097.50 | 13120747.55 | 1342.64 | 7411.74 | 5.62 | 479.64 |
KITCHEN | 25233014.90 | 0.00 | 25233014.90 | 18558.80 | 25251573.70 | 35993094.65 | 6330.14 | 2429.86 | 0.00 | 974.57 |
Total Facility | 36490187.06 | 0.00 | 36490187.06 | 10159484.13 | 46649671.19 | 49113842.20 | 6368.00 | 7451.58 | 5.62 | 1011.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4161 | 0.0000 | 0.4161 | 0.3917 | 0.8078 | 0.4161 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 0.9092 | 0.0000 | 0.9092 | 0.0005 | 0.9097 | 1.1413 | 4899.43 | 2287.57 | 0.00 |
Total Facility | 1.3253 | 0.0000 | 1.3253 | 0.3922 | 1.7175 | 1.5574 | 4899.43 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 15509765.04 | 0.00 | 15509765.04 | 13120747.55 | 1301.29 | 4.47 | 7454.24 | 479.64 |
PSZ-AC_2:2 | 34765337.09 | 0.00 | 34765337.09 | 35993094.65 | 5168.87 | 81.84 | 3509.29 | 974.57 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5733 | 0.0000 | 0.5733 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.2527 | 0.0000 | 1.2527 | 1.1413 | 3820.03 | 78.25 | 3288.72 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 246.21 | 0.00 | 7420.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 2206.74 | 0.00 | 1591.57 | 4363.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 0.5733 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 1.5730 | 0.0000 | 1.1040 | 1.1122 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 389 |
Defaulted Fields | 292 |
Fields with Defaults | 936 |
Autosized Fields | 49 |
Autosizable Fields | 119 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 625.33 | 3088.27 | 01-JAN-01:20 | 43188.34 | 22-JUN-17:10 |
Electricity:Building | 281.98 | 1673.38 | 01-JAN-01:20 | 17939.26 | 02-JAN-11:10 |
Electricity:Zone:DINING | 74.78 | 295.02 | 01-JAN-01:20 | 4037.01 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 274.04 | 1537.10 | 01-JAN-01:20 | 14645.21 | 02-JAN-11:10 |
InteriorLights:Electricity | 21.95 | 50.02 | 01-JAN-01:20 | 1346.16 | 02-JAN-17:40 |
InteriorLights:Electricity:Zone:DINING | 4.45 | 25.01 | 01-JAN-01:20 | 444.80 | 02-JAN-17:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 21.95 | 50.02 | 01-JAN-01:20 | 1346.16 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity | 21.95 | 50.02 | 01-JAN-01:20 | 1346.16 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 4.45 | 25.01 | 01-JAN-01:20 | 444.80 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 21.95 | 50.02 | 01-JAN-01:20 | 1346.16 | 02-JAN-17:40 |
Electricity:Zone:KITCHEN | 207.20 | 1378.36 | 01-JAN-01:20 | 13902.25 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.50 | 25.01 | 01-JAN-01:20 | 901.37 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.50 | 25.01 | 01-JAN-01:20 | 901.37 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 252.09 | 1487.08 | 01-JAN-01:10 | 13637.09 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 252.09 | 1487.08 | 01-JAN-01:10 | 13637.09 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 181.76 | 1217.07 | 01-JAN-01:10 | 9706.84 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 40.31 | 609.97 | 31-DEC-23:30 | 3931.14 | 17-APR-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 32.37 | 524.20 | 31-DEC-23:30 | 1668.68 | 18-JUL-04:10 |
LowTempRefrigeration:Refrigeration:Electricity | 12.80 | 0.00 | 01-JAN-11:10 | 1031.59 | 18-JUL-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 19.58 | 515.18 | 01-JAN-01:10 | 637.09 | 02-JAN-14:10 |
ElectricityPurchased:Facility | 625.33 | 3088.27 | 01-JAN-01:20 | 43188.34 | 22-JUN-17:10 |
ElectricityPurchased:Plant | 625.33 | 3088.27 | 01-JAN-01:20 | 43188.34 | 22-JUN-17:10 |
Cogeneration:ElectricityPurchased | 625.33 | 3088.27 | 01-JAN-01:20 | 43188.34 | 22-JUN-17:10 |
General:Cogeneration:ElectricityPurchased | 625.33 | 3088.27 | 01-JAN-01:20 | 43188.34 | 22-JUN-17:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 625.33 | 3088.27 | 01-JAN-01:20 | 43188.34 | 22-JUN-17:10 |
ElectricityNet:Plant | 625.33 | 3088.27 | 01-JAN-01:20 | 43188.34 | 22-JUN-17:10 |
Cogeneration:ElectricityNet | 625.33 | 3088.27 | 01-JAN-01:20 | 43188.34 | 22-JUN-17:10 |
General:Cogeneration:ElectricityNet | 625.33 | 3088.27 | 01-JAN-01:20 | 43188.34 | 22-JUN-17:10 |
Electricity:HVAC | 295.38 | 0.00 | 01-JAN-01:10 | 30210.81 | 10-JUN-18:10 |
Fans:Electricity | 67.02 | 0.00 | 01-JAN-01:10 | 4340.39 | 01-JUL-18:10 |
General:Fans:Electricity | 67.02 | 0.00 | 01-JAN-01:10 | 4340.39 | 01-JUL-18:10 |
Cooling:Electricity | 225.79 | 0.00 | 01-JAN-00:10 | 25926.33 | 10-JUN-18:10 |
General:Cooling:Electricity | 225.79 | 0.00 | 01-JAN-00:10 | 25926.33 | 10-JUN-18:10 |
Heating:Electricity | 2.58 | 0.00 | 01-JAN-00:10 | 4648.29 | 05-JAN-07:10 |
General:Heating:Electricity | 2.58 | 0.00 | 01-JAN-00:10 | 4648.29 | 05-JAN-07:10 |
ExteriorLights:Electricity | 15.59 | 0.00 | 01-JAN-07:20 | 1372.31 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 15.59 | 0.00 | 01-JAN-07:20 | 1372.31 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 05-MAR-08:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 05-MAR-08:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 614.80 | 1838.65 | 06-JAN-03:40 | 42436.32 | 16-JAN-13:20 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Plant | 137.64 | 0.00 | 04-JAN-03:00 | 19453.17 | 16-JAN-13:20 |
WaterSystems:NaturalGas | 137.64 | 0.00 | 04-JAN-03:00 | 19453.17 | 16-JAN-13:20 |
Water Heater:WaterSystems:NaturalGas | 137.64 | 0.00 | 04-JAN-03:00 | 19453.17 | 16-JAN-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-MAY-12:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-MAY-12:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-MAY-12:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-MAY-12:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-MAY-12:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-MAY-12:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-MAY-12:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-MAY-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1609.60 | 3017.04 | 01-JAN-01:10 | 129570.01 | 25-AUG-13:00 |
EnergyTransfer:Building | 537.91 | 1508.52 | 01-JAN-01:10 | 39885.72 | 12-JUN-11:10 |
EnergyTransfer:Zone:KITCHEN | 339.39 | 1508.52 | 01-JAN-01:10 | 18795.09 | 31-JAN-05:10 |
Refrigeration:EnergyTransfer | 160.68 | 2831.40 | 31-DEC-23:30 | 7834.84 | 14-APR-03:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 80.34 | 1415.70 | 31-DEC-23:30 | 3917.42 | 14-APR-03:30 |
General:Refrigeration:EnergyTransfer | 80.34 | 1415.70 | 31-DEC-23:30 | 3917.42 | 14-APR-03:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 80.34 | 1415.70 | 31-DEC-23:30 | 3917.42 | 14-APR-03:30 |
EnergyTransfer:Plant | 183.48 | 1415.70 | 31-DEC-23:30 | 17954.04 | 17-JAN-13:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.50 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 66.84 | 1349.98 | 01-JAN-01:10 | 2238.70 | 02-JAN-14:10 |
EnergyTransfer:Zone:DINING | 198.53 | 0.00 | 01-JAN-01:10 | 27030.70 | 07-JUN-17:10 |
Heating:EnergyTransfer | 1.96 | 0.00 | 01-JAN-00:10 | 5874.65 | 03-MAY-23:10 |
Heating:EnergyTransfer:Zone:DINING | 1.92 | 0.00 | 01-JAN-00:10 | 5573.23 | 31-DEC-07:10 |
General:Heating:EnergyTransfer | 1.96 | 0.00 | 01-JAN-00:10 | 5874.65 | 03-MAY-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 1.92 | 0.00 | 01-JAN-00:10 | 5573.23 | 31-DEC-07:10 |
Cooling:EnergyTransfer | 455.61 | 0.00 | 01-JAN-01:10 | 36624.16 | 10-JUN-18:10 |
Cooling:EnergyTransfer:Zone:DINING | 196.61 | 0.00 | 01-JAN-01:10 | 27030.70 | 07-JUN-17:10 |
General:Cooling:EnergyTransfer | 455.61 | 0.00 | 01-JAN-01:10 | 36624.16 | 10-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 196.61 | 0.00 | 01-JAN-01:10 | 27030.70 | 07-JUN-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.04 | 0.00 | 01-JAN-00:10 | 1479.45 | 03-MAY-23:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.04 | 0.00 | 01-JAN-00:10 | 1479.45 | 03-MAY-23:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 259.00 | 0.00 | 01-JAN-01:10 | 15000.62 | 31-JAN-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 259.00 | 0.00 | 01-JAN-01:10 | 15000.62 | 31-JAN-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 103.14 | 0.00 | 01-JAN-00:10 | 15400.23 | 17-JAN-13:30 |
PlantLoopHeatingDemand:Plant | 103.14 | 0.00 | 01-JAN-00:10 | 15400.23 | 17-JAN-13:30 |
WaterSystems:PlantLoopHeatingDemand | 103.14 | 0.00 | 01-JAN-00:10 | 15400.23 | 17-JAN-13:30 |
General:WaterSystems:PlantLoopHeatingDemand | 103.14 | 0.00 | 01-JAN-00:10 | 15400.23 | 17-JAN-13:30 |
EnergyTransfer:HVAC | 888.20 | 0.00 | 01-JAN-00:10 | 91129.88 | 01-JUL-19:00 |
CoolingCoils:EnergyTransfer | 880.19 | 0.00 | 01-JAN-00:10 | 91129.88 | 01-JUL-19:00 |
HeatingCoils:EnergyTransfer | 8.02 | 0.00 | 01-JAN-00:10 | 13873.47 | 05-JAN-07:10 |
WaterSystems:EnergyTransfer | 103.14 | 0.00 | 01-JAN-00:10 | 15400.23 | 17-JAN-13:30 |
WaterUse:WaterSystems:EnergyTransfer | 103.14 | 0.00 | 01-JAN-00:10 | 15400.23 | 17-JAN-13:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 1.916 | -196.608 | 0.000 | 0.000 | 66.349 | 4.451 | 52.748 | 23.659 | 0.000 | 57.255 | 20.385 | 0.000 | -5.522 | 0.000 | -24.634 | -0.001 |
KITCHEN | 0.000 | 0.000 | 0.043 | -258.999 | 0.000 | 0.000 | 3.748 | 17.495 | 187.472 | 0.000 | 0.000 | 0.053 | 50.257 | 0.000 | 0.000 | 0.000 | -0.070 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.607 | 9.895 | 0.000 | 0.000 | 0.000 | -15.502 | -0.000 |
Total Facility | 0.000 | 0.000 | 1.959 | -455.607 | 0.000 | 0.000 | 70.098 | 21.947 | 240.220 | 23.659 | 0.000 | 62.915 | 80.537 | 0.000 | -5.522 | 0.000 | -40.205 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-MAY-02:61 | 0.00 | 0.00 | 0.00 | -41352.41 | 0.00 | 0.00 | 0.00 | 25.01 | 202.51 | 39.66 | 0.00 | 15.61 | 41069.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 30-DEC-03:01 | 0.00 | 0.00 | 0.00 | -39057.49 | 0.00 | 0.00 | 0.00 | 25.01 | 1240.35 | 0.00 | 0.00 | 0.00 | 37859.73 | 0.00 | -0.00 | 0.00 | -67.60 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-APR-02:61 | 0.00 | 0.00 | 0.00 | -65995.00 | 0.00 | 0.00 | 0.00 | 50.02 | 1442.86 | 0.00 | 0.00 | 435.93 | 64104.02 | 0.00 | -37.82 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 20-DEC-06:04 | 0.00 | 0.00 | 6030.60 | 0.00 | 0.00 | 0.00 | 719.71 | 197.69 | 1321.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1018.82 | 0.00 | -2361.98 | -4888.57 |
KITCHEN | 03-MAY-23:01 | 0.00 | 0.00 | 8220.44 | 0.00 | 0.00 | 0.00 | 18.55 | 150.23 | 1566.76 | 0.00 | 0.00 | 17.15 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9973.13 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-MAY-23:01 | 0.00 | 0.00 | 13971.29 | 0.00 | 0.00 | 0.00 | 325.14 | 224.36 | 1871.70 | 512.40 | 0.00 | 417.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17322.11 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4047 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.4047 | 0.1730 | 1.0000 | Not calculated | 0.4161 | 0.1730 | ||
PSZ-AC_2:2 | 1.1413 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1413 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1325 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4047 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.4047 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.1730 | ||
PSZ-AC_2:2 | 1.1413 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1413 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1325 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4047 | 2.4047 | 2.4047 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1413 | 1.1413 | 1.1413 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4047 | 2.4047 | 2.4047 | 2.4047 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1413 | 1.1413 | 1.1413 | 1.1413 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4047 | 2.4047 | 2.4047 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1413 | 1.1413 | 1.1413 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4047 | 2.4047 | 2.4047 | 2.4047 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1413 | 1.1413 | 1.1413 | 1.1413 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1972.67 |
Number of hours not met | 1972.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 2.58 | 4648.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 225.79 | 25926.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 21.95 | 1346.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 15.59 | 1372.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 67.02 | 4340.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 137.64 | 19453.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 12.80 | 1031.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 19.58 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 292.41 | 625.33 |
Natural Gas | 477.16 | 614.80 |
Additional | 0.00 | 0.00 |
Total | 769.57 | 1240.13 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 94.46 |
Space Heating | 11.11 |
Space Cooling | 971.78 |
Fans (All) | 288.43 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1085.00 |
Miscellaneous (All) | 2691.40 |
Subtotal | 2691.40 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 592.40 |
Miscellaneous (All) | 2646.08 |
Subtotal | 2646.08 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.77 |
Space Heating | 0.21 |
Space Cooling | 18.21 |
Fans (All) | 5.40 |
Service Water Heating | 11.10 |
Receptacle Equipment | 58.80 |
Miscellaneous | 4.51 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8236.33 | 392.17 | 131.50 | 0.00 | 0.00 |
KITCHEN | 5401.67 | 2392.67 | 963.67 | 2.00 | 0.00 |
ATTIC | 4259.67 | 1055.67 | 1071.33 | 1132.50 | 1240.83 |
Min | 4259.67 | 392.17 | 131.50 | 0.00 | 0.00 |
Max | 8236.33 | 2392.67 | 1071.33 | 1132.50 | 1240.83 |
Average | 5965.89 | 1280.17 | 722.17 | 378.17 | 413.61 |
Sum | 17897.67 | 3840.50 | 2166.50 | 1134.50 | 1240.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254091.00 | 467.33 | 166.67 | 0.00 | 0.00 |
KITCHEN | 10705.83 | 3688.67 | 1858.00 | 5.50 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254091.00 | 3688.67 | 1858.00 | 5.50 | 0.00 |
Average | 88265.61 | 1385.33 | 674.89 | 1.83 | 0.00 |
Sum | 264796.83 | 4156.00 | 2024.67 | 5.50 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 5711.67 | 2949.17 | 99.17 | 0.00 | 0.00 |
KITCHEN | 2531.33 | 5775.00 | 453.67 | 0.00 | 0.00 |
ATTIC | 3481.50 | 2237.33 | 863.83 | 509.67 | 1667.67 |
Min | 2531.33 | 2237.33 | 99.17 | 0.00 | 0.00 |
Max | 5711.67 | 5775.00 | 863.83 | 509.67 | 1667.67 |
Average | 3908.17 | 3653.83 | 472.22 | 169.89 | 555.89 |
Sum | 11724.50 | 10961.50 | 1416.67 | 509.67 | 1667.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 175150.17 | 79476.83 | 98.00 | 0.00 | 0.00 |
KITCHEN | 4118.50 | 11183.67 | 955.83 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 175150.17 | 79476.83 | 955.83 | 0.00 | 0.00 |
Average | 59756.22 | 30220.17 | 351.28 | 0.00 | 0.00 |
Sum | 179268.67 | 90660.50 | 1053.83 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420254E+10 | 11186.33 | 15-JAN-03:01 | 15.85 | 13.69 | 0.486000E+10 | 4681.14 | 14-JAN-19:40 | 15.85 | 13.69 |
February | 0.638157E+10 | 14452.88 | 23-FEB-03:01 | 15.28 | 13.33 | 0.464910E+10 | 4681.01 | 25-FEB-19:19 | 19.33 | 16.87 |
March | 0.126369E+11 | 25100.41 | 12-MAR-02:61 | 22.18 | 17.57 | 0.542072E+10 | 4681.41 | 25-MAR-18:19 | 23.53 | 13.98 |
April | 0.202857E+11 | 40006.60 | 28-APR-02:61 | 29.83 | 17.14 | 0.526109E+10 | 4681.18 | 15-APR-18:10 | 29.83 | 17.14 |
May | 0.257544E+11 | 41356.27 | 06-MAY-02:61 | 31.75 | 18.39 | 0.544783E+10 | 4681.20 | 13-MAY-18:19 | 32.23 | 22.81 |
June | 0.258887E+11 | 35255.19 | 05-JUN-02:61 | 31.48 | 20.26 | 0.529769E+10 | 4681.33 | 03-JUN-18:00 | 31.48 | 20.26 |
July | 0.242789E+11 | 25261.83 | 01-JUL-02:61 | 31.37 | 24.28 | 0.541770E+10 | 4831.20 | 01-JUL-18:40 | 36.30 | 28.69 |
August | 0.228434E+11 | 25329.32 | 03-AUG-02:61 | 29.53 | 23.75 | 0.547654E+10 | 4681.18 | 19-AUG-18:10 | 26.02 | 25.39 |
September | 0.205335E+11 | 28050.31 | 29-SEP-02:61 | 25.03 | 20.73 | 0.526263E+10 | 4681.75 | 09-SEP-18:10 | 25.03 | 20.73 |
October | 0.175266E+11 | 34539.31 | 23-OCT-02:61 | 20.48 | 16.58 | 0.540614E+10 | 4681.81 | 14-OCT-18:49 | 20.48 | 16.58 |
November | 0.108249E+11 | 23535.97 | 10-NOV-03:01 | 17.72 | 15.45 | 0.511676E+10 | 4681.09 | 25-NOV-19:10 | 17.82 | 11.99 |
December | 0.545256E+10 | 12117.83 | 29-DEC-03:01 | 15.67 | 12.56 | 0.494363E+10 | 4591.11 | 16-DEC-19:10 | 15.67 | 12.56 |
Annual Sum or Average | 0.196610E+12 | 0.625598E+11 | ||||||||
Minimum of Months | 0.420254E+10 | 11186.33 | 15.28 | 12.56 | 0.464910E+10 | 4591.11 | 15.67 | 11.99 | ||
Maximum of Months | 0.258887E+11 | 41356.27 | 31.75 | 24.28 | 0.547654E+10 | 4831.20 | 36.30 | 28.69 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204869E+11 | 37959.46 | 13-JAN-03:01 | 10.25 | 8.98 | 0.781231E+10 | 5135.96 | 13-JAN-11:00 | 19.00 | 14.37 |
February | 0.183177E+11 | 36482.63 | 18-FEB-03:01 | 13.80 | 10.42 | 0.708047E+10 | 5135.97 | 09-FEB-11:00 | 13.80 | 10.42 |
March | 0.207268E+11 | 35740.43 | 01-MAR-03:01 | 13.38 | 10.98 | 0.786024E+10 | 5135.95 | 22-MAR-10:30 | 21.70 | 15.26 |
April | 0.212075E+11 | 31257.01 | 10-APR-02:61 | 19.25 | 13.67 | 0.760828E+10 | 5145.99 | 17-APR-10:00 | 34.50 | 22.99 |
May | 0.227991E+11 | 26419.25 | 28-MAY-02:61 | 28.28 | 17.05 | 0.788566E+10 | 5184.20 | 22-MAY-10:50 | 28.28 | 17.05 |
June | 0.222268E+11 | 21936.59 | 05-JUN-02:61 | 31.48 | 20.26 | 0.766517E+10 | 5217.13 | 28-JUN-10:00 | 32.50 | 28.26 |
July | 0.225914E+11 | 18083.08 | 11-JUL-02:61 | 26.50 | 23.05 | 0.793972E+10 | 5224.98 | 17-JUL-10:50 | 34.45 | 27.92 |
August | 0.227334E+11 | 17119.13 | 16-AUG-02:61 | 24.23 | 23.73 | 0.795073E+10 | 5237.87 | 25-AUG-10:50 | 32.72 | 28.77 |
September | 0.225721E+11 | 21230.47 | 29-SEP-02:61 | 25.03 | 20.73 | 0.764585E+10 | 5209.41 | 12-SEP-10:50 | 25.03 | 20.73 |
October | 0.232957E+11 | 29774.59 | 24-OCT-02:11 | 18.73 | 14.80 | 0.785817E+10 | 5148.27 | 04-OCT-10:50 | 18.73 | 14.80 |
November | 0.210833E+11 | 37439.25 | 27-NOV-03:01 | 11.55 | 9.68 | 0.759727E+10 | 5135.96 | 28-NOV-11:30 | 20.05 | 14.53 |
December | 0.209629E+11 | 39101.56 | 30-DEC-03:01 | 11.97 | 8.54 | 0.782374E+10 | 5135.97 | 08-DEC-11:00 | 11.97 | 8.54 |
Annual Sum or Average | 0.259004E+12 | 0.927276E+11 | ||||||||
Minimum of Months | 0.183177E+11 | 17119.13 | 10.25 | 8.54 | 0.708047E+10 | 5135.95 | 11.97 | 8.54 | ||
Maximum of Months | 0.232957E+11 | 39101.56 | 31.48 | 23.73 | 0.795073E+10 | 5237.87 | 34.50 | 28.77 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 7.83 | 7.49 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.73 | 7.85 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.85 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 |
April | 0.00 | 0.00 | 01-APR-00:02 | 23.70 | 16.77 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.77 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 | 18.24 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.24 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 | 22.58 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.58 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 | 24.65 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.65 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.32 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 28.43 | 25.91 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 26.58 | 21.85 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.85 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 | 15.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.668758E+09 | 5545.23 | 21-JAN-07:10 | 5.63 |
February | 0.110832E+09 | 3686.93 | 01-FEB-23:25 | 10.15 |
March | 881428.18 | 931.89 | 11-MAR-00:01 | 24.75 |
April | 84164173.46 | 4382.97 | 27-APR-23:01 | 32.73 |
May | 0.188920E+09 | 5750.70 | 03-MAY-23:01 | 35.95 |
June | 0.214370E+09 | 5612.72 | 05-JUN-23:01 | 35.62 |
July | 0.178001E+09 | 5360.24 | 02-JUL-23:01 | 35.28 |
August | 0.124575E+09 | 3854.28 | 08-AUG-23:01 | 32.07 |
September | 71022008.18 | 2959.22 | 17-SEP-23:01 | 30.23 |
October | 8197743.25 | 2978.09 | 22-OCT-23:01 | 29.42 |
November | 1832660.16 | 678.48 | 27-NOV-07:10 | 10.02 |
December | 0.263924E+09 | 6031.31 | 20-DEC-06:04 | 6.40 |
Annual Sum or Average | 0.191548E+10 | |||
Minimum of Months | 881428.18 | 678.48 | 5.63 | |
Maximum of Months | 0.668758E+09 | 6031.31 | 35.95 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 5204260.36 | 5545.96 | 27-APR-23:01 | 32.73 |
May | 15993089.17 | 8220.31 | 03-MAY-23:01 | 35.95 |
June | 14136649.31 | 7951.53 | 05-JUN-23:01 | 35.62 |
July | 4110865.87 | 5881.01 | 04-JUL-23:01 | 35.10 |
August | 2115133.51 | 3315.72 | 02-AUG-23:01 | 30.53 |
September | 1142688.57 | 1686.99 | 23-SEP-23:01 | 28.32 |
October | 387663.52 | 2775.41 | 22-OCT-23:01 | 29.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 43090350.31 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 15993089.17 | 8220.31 | 35.95 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:02 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.421201E+09 | 444.80 | 02-JAN-17:40 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.364234E+09 | 444.80 | 01-FEB-17:00 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.373458E+09 | 444.80 | 01-MAR-18:19 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.341454E+09 | 444.80 | 01-APR-18:40 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.339140E+09 | 444.80 | 01-MAY-18:00 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.329426E+09 | 444.80 | 01-JUN-19:10 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.341096E+09 | 444.80 | 01-JUL-19:19 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.363430E+09 | 444.80 | 01-AUG-18:00 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.358345E+09 | 444.80 | 01-SEP-18:49 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.392258E+09 | 444.80 | 02-OCT-17:00 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.402664E+09 | 444.80 | 01-NOV-17:40 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.424620E+09 | 444.80 | 01-DEC-17:19 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.445132E+10 | 0.703313E+11 | ||||
Minimum of Months | 0.329426E+09 | 444.80 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.424620E+09 | 444.80 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147778E+10 | 901.37 | 02-JAN-10:09 | 0.154373E+11 | 9706.84 | 01-JAN-11:09 |
February | 0.133867E+10 | 901.37 | 01-FEB-10:09 | 0.139433E+11 | 9706.84 | 01-FEB-11:09 |
March | 0.150331E+10 | 901.37 | 01-MAR-10:09 | 0.154374E+11 | 9706.84 | 01-MAR-11:09 |
April | 0.143598E+10 | 901.37 | 01-APR-16:10 | 0.149393E+11 | 9706.84 | 01-APR-10:09 |
May | 0.149055E+10 | 901.37 | 01-MAY-09:09 | 0.154373E+11 | 9706.84 | 01-MAY-10:09 |
June | 0.145287E+10 | 901.37 | 01-JUN-09:09 | 0.149394E+11 | 9706.84 | 01-JUN-10:09 |
July | 0.147384E+10 | 901.37 | 01-JUL-16:10 | 0.154372E+11 | 9706.84 | 01-JUL-10:09 |
August | 0.150331E+10 | 901.37 | 01-AUG-09:09 | 0.154374E+11 | 9706.84 | 01-AUG-10:09 |
September | 0.143634E+10 | 901.37 | 01-SEP-09:09 | 0.149393E+11 | 9706.84 | 01-SEP-10:09 |
October | 0.147760E+10 | 901.37 | 02-OCT-09:09 | 0.154373E+11 | 9706.84 | 01-OCT-10:09 |
November | 0.143091E+10 | 901.37 | 01-NOV-09:09 | 0.149393E+11 | 9706.84 | 01-NOV-10:09 |
December | 0.147402E+10 | 901.37 | 01-DEC-10:09 | 0.154372E+11 | 9706.84 | 01-DEC-11:09 |
Annual Sum or Average | 0.174952E+11 | 0.181762E+12 | ||||
Minimum of Months | 0.133867E+10 | 901.37 | 0.139433E+11 | 9706.84 | ||
Maximum of Months | 0.150331E+10 | 901.37 | 0.154374E+11 | 9706.84 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.421201E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791178E+10 |
February | 0.852256E+10 | 0.364234E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135198E+09 | 0.434182E+10 |
March | 0.954557E+10 | 0.373458E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199716E+10 | 0.159050E+10 |
April | 0.915225E+10 | 0.341454E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719854E+10 | 0.132065E+09 |
May | 0.947560E+10 | 0.339140E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108689E+11 | 1911121.52 |
June | 0.922788E+10 | 0.329426E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108134E+11 | 288177.87 |
July | 0.939996E+10 | 0.341096E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855882E+10 | 106484.63 |
August | 0.954557E+10 | 0.363430E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710821E+10 | 130032.76 |
September | 0.915225E+10 | 0.358345E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586691E+10 | 642643.48 |
October | 0.940563E+10 | 0.392258E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374133E+10 | 0.657266E+09 |
November | 0.909363E+10 | 0.402664E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960189E+09 | 0.300922E+10 |
December | 0.939996E+10 | 0.424620E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5847339.54 | 0.698780E+10 |
Annual Sum or Average | 0.111326E+12 | 0.445132E+10 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572545E+11 | 0.246335E+11 |
Minimum of Months | 0.852256E+10 | 0.329426E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106484.63 |
Maximum of Months | 0.954557E+10 | 0.424620E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108689E+11 | 0.791178E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.147778E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14595508.64 |
February | 0.610713E+09 | 0.133867E+10 | 0.101891E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 7836.78 | 16233451.76 |
March | 0.684021E+09 | 0.150331E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 1555923.52 | 12935556.73 |
April | 0.655836E+09 | 0.143598E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 8416477.97 | 1519179.62 |
May | 0.679007E+09 | 0.149055E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 15140236.93 | 1347325.92 |
June | 0.661256E+09 | 0.145287E+10 | 0.109170E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 9881027.85 | 701749.40 |
July | 0.673587E+09 | 0.147384E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 8127997.26 | 1244992.58 |
August | 0.684021E+09 | 0.150331E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 4103721.43 | 1258526.83 |
September | 0.655836E+09 | 0.143634E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 3556468.07 | 1299257.01 |
October | 0.673993E+09 | 0.147760E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2341740.80 | 1294955.75 |
November | 0.651635E+09 | 0.143091E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 316448.95 | 3910653.70 |
December | 0.673587E+09 | 0.147402E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13501072.18 |
Annual Sum or Average | 0.797748E+10 | 0.174952E+11 | 0.132823E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 53447879.56 | 69842230.11 |
Minimum of Months | 0.610713E+09 | 0.133867E+10 | 0.101891E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 701749.40 |
Maximum of Months | 0.684021E+09 | 0.150331E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 15140236.93 | 16233451.76 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575237E+09 | 0.965941E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436207E+09 | 0.105478E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465360E+09 | 0.147645E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520057E+09 | 0.167982E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451989E+09 | 0.170490E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421662E+09 | 0.162196E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267082E+09 | 0.129719E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259443E+09 | 0.123088E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377682E+09 | 0.107926E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586005E+09 | 0.132313E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621662E+09 | 0.109700E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624534E+09 | 0.970724E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560692E+10 | 0.155020E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259443E+09 | 0.965941E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624534E+09 | 0.170490E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 444.80 | 02-JAN-17:40 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10748.85 | 02-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 444.80 | 01-FEB-17:00 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2392.67 | 22-FEB-14:00 | 7901.88 | 04-FEB-07:10 |
March | 9454.80 | 04-MAR-19:10 | 444.80 | 01-MAR-18:19 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8962.66 | 28-MAR-17:02 | 4892.44 | 01-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 444.80 | 01-APR-18:40 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12414.09 | 28-APR-17:08 | 2414.82 | 11-APR-06:10 |
May | 9454.80 | 06-MAY-18:10 | 444.80 | 01-MAY-18:00 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15226.69 | 03-MAY-17:02 | 463.70 | 13-MAY-06:10 |
June | 9454.80 | 03-JUN-18:10 | 444.80 | 01-JUN-19:10 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16051.40 | 07-JUN-17:03 | 76.42 | 18-JUN-05:10 |
July | 9454.80 | 01-JUL-18:10 | 444.80 | 01-JUL-19:19 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12681.86 | 03-JUL-17:03 | 12.16 | 19-JUL-01:53 |
August | 9454.80 | 05-AUG-18:10 | 444.80 | 01-AUG-18:00 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10440.40 | 07-AUG-17:03 | 11.94 | 16-AUG-00:10 |
September | 9454.80 | 02-SEP-18:10 | 444.80 | 01-SEP-18:49 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10040.38 | 17-SEP-20:00 | 121.72 | 27-SEP-05:10 |
October | 9454.80 | 07-OCT-18:10 | 444.80 | 02-OCT-17:00 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9836.58 | 02-OCT-12:00 | 3775.38 | 29-OCT-06:10 |
November | 9454.80 | 04-NOV-18:10 | 444.80 | 01-NOV-17:40 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4630.94 | 09-NOV-13:00 | 6846.52 | 25-NOV-19:55 |
December | 9454.80 | 02-DEC-19:10 | 444.80 | 01-DEC-17:19 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 552.66 | 28-DEC-14:00 | 10298.28 | 30-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 444.80 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.94 | |||||
Maximum of Months | 9454.80 | 444.80 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 16051.40 | 10748.85 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 901.37 | 02-JAN-10:09 | 6972.03 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 63.50 | 15-JAN-02:50 |
February | 677.52 | 04-FEB-19:10 | 901.37 | 01-FEB-10:09 | 6972.03 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.55 | 22-FEB-14:55 | 86.56 | 26-FEB-02:00 |
March | 677.52 | 04-MAR-19:10 | 901.37 | 01-MAR-10:09 | 6972.03 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 11.74 | 27-MAR-15:00 | 248.40 | 25-MAR-00:20 |
April | 677.52 | 01-APR-18:10 | 901.37 | 01-APR-16:10 | 6972.03 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 30.99 | 15-APR-14:25 | 30.22 | 05-APR-00:10 |
May | 677.52 | 06-MAY-18:10 | 901.37 | 01-MAY-09:09 | 6972.03 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 48.67 | 04-MAY-00:08 | 40.45 | 15-MAY-02:00 |
June | 677.52 | 03-JUN-18:10 | 901.37 | 01-JUN-09:09 | 6972.03 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 28.42 | 06-JUN-14:55 | 47.59 | 18-JUN-00:40 |
July | 677.52 | 01-JUL-18:10 | 901.37 | 01-JUL-16:10 | 6972.03 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 34.08 | 03-JUL-03:30 | 29.44 | 19-JUL-02:00 |
August | 677.52 | 05-AUG-18:10 | 901.37 | 01-AUG-09:09 | 6972.03 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 22.40 | 31-AUG-02:10 | 28.98 | 16-AUG-00:40 |
September | 677.52 | 02-SEP-18:10 | 901.37 | 01-SEP-09:09 | 6972.03 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 12.87 | 28-SEP-14:20 | 24.33 | 09-SEP-00:40 |
October | 677.52 | 07-OCT-18:10 | 901.37 | 02-OCT-09:09 | 6972.03 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 15.71 | 03-OCT-14:53 | 45.62 | 12-OCT-02:10 |
November | 677.52 | 04-NOV-18:10 | 901.37 | 01-NOV-09:09 | 6972.03 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 3.48 | 13-NOV-14:00 | 52.75 | 28-NOV-04:30 |
December | 677.52 | 02-DEC-19:10 | 901.37 | 01-DEC-10:09 | 6972.03 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 111.26 | 29-DEC-04:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 901.37 | 6972.03 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | ||||||
Maximum of Months | 677.52 | 901.37 | 6972.03 | 7998.14 | 0.00 | 0.00 | 0.00 | 48.67 | 248.40 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.66 | 23-JAN-07:20 | 1927.66 | 31-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.21 | 19-FEB-23:00 | 2001.32 | 20-FEB-13:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.94 | 28-MAR-06:45 | 2292.61 | 31-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.47 | 22-APR-15:10 | 2500.47 | 29-APR-14:02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.12 | 22-MAY-14:00 | 2423.82 | 14-MAY-13:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 995.17 | 03-JUN-18:40 | 2569.47 | 08-JUN-13:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.66 | 04-JUL-05:40 | 2355.14 | 10-JUL-13:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.03 | 24-AUG-06:10 | 2034.04 | 05-AUG-13:30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.23 | 30-SEP-06:45 | 2026.70 | 26-SEP-13:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.02 | 02-OCT-06:35 | 2226.00 | 09-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.01 | 24-NOV-07:15 | 1954.28 | 23-NOV-12:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 735.11 | 03-DEC-07:23 | 1858.31 | 27-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.03 | 1858.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 995.17 | 2569.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11186.33 | 15-JAN-03:01 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 |
February | 14452.88 | 23-FEB-03:01 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25100.41 | 12-MAR-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 |
April | 40006.60 | 28-APR-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41356.27 | 06-MAY-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 | 0.00 |
June | 35255.19 | 05-JUN-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 0.00 |
July | 25261.83 | 01-JUL-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.57 | 0.00 |
August | 25329.32 | 03-AUG-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 | 0.00 |
September | 28050.31 | 29-SEP-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
October | 34539.31 | 23-OCT-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
November | 23535.97 | 10-NOV-03:01 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12117.83 | 29-DEC-03:01 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11186.33 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41356.27 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.57 | 41.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37959.46 | 13-JAN-03:01 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 |
February | 36482.63 | 18-FEB-03:01 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 58.91 |
March | 35740.43 | 01-MAR-03:01 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 |
April | 31257.01 | 10-APR-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
May | 26419.25 | 28-MAY-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 |
June | 21936.59 | 05-JUN-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.20 | 0.00 |
July | 18083.08 | 11-JUL-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 |
August | 17119.13 | 16-AUG-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 |
September | 21230.47 | 29-SEP-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
October | 29774.59 | 24-OCT-02:11 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 |
November | 37439.25 | 27-NOV-03:01 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39101.56 | 30-DEC-03:01 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 67.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 17119.13 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39101.56 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.20 | 67.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.83 | 0.00 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.67 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.96 | 0.00 |
April | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.56 | 0.00 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.81 | 0.00 |
June | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.46 | 0.00 |
July | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.21 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.09 | 0.00 |
September | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.43 | 0.00 |
October | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.51 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.87 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.81 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.354160E+11 | 23126.12 | 26-JAN-11:20 | 0.547480E+11 | 42436.32 | 16-JAN-13:20 |
February | 0.337192E+11 | 25826.02 | 22-FEB-11:20 | 0.491712E+11 | 42321.38 | 02-FEB-13:00 |
March | 0.429979E+11 | 30002.37 | 28-MAR-16:10 | 0.535982E+11 | 41593.50 | 01-MAR-13:39 |
April | 0.513819E+11 | 36567.97 | 27-APR-11:09 | 0.506505E+11 | 39864.39 | 02-APR-12:30 |
May | 0.639303E+11 | 40620.04 | 17-MAY-17:10 | 0.510843E+11 | 38209.54 | 01-MAY-12:00 |
June | 0.677142E+11 | 43188.34 | 22-JUN-17:10 | 0.484992E+11 | 36819.02 | 02-JUN-10:50 |
July | 0.714590E+11 | 42260.43 | 10-JUL-11:00 | 0.496815E+11 | 36118.76 | 01-JUL-10:39 |
August | 0.702419E+11 | 42104.27 | 25-AUG-11:00 | 0.499893E+11 | 36544.61 | 31-AUG-10:00 |
September | 0.631245E+11 | 39234.42 | 17-SEP-19:00 | 0.492267E+11 | 37872.04 | 30-SEP-12:39 |
October | 0.500834E+11 | 35514.07 | 04-OCT-11:00 | 0.521259E+11 | 39608.73 | 31-OCT-12:39 |
November | 0.393972E+11 | 29210.72 | 09-NOV-11:20 | 0.516770E+11 | 41354.49 | 30-NOV-13:00 |
December | 0.358632E+11 | 24454.94 | 18-DEC-11:20 | 0.543456E+11 | 42299.47 | 31-DEC-13:30 |
Annual Sum or Average | 0.625329E+12 | 0.614797E+12 | ||||
Minimum of Months | 0.337192E+11 | 23126.12 | 0.484992E+11 | 36118.76 | ||
Maximum of Months | 0.714590E+11 | 43188.34 | 0.547480E+11 | 42436.32 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.189898E+10 | 0.156513E+10 | 0.214106E+11 | 0.00 | 0.464608E+10 | 0.79 | 0.136615E+10 | 0.126975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170290E+10 | 0.133518E+10 | 0.193386E+11 | 0.00 | 0.421529E+10 | 0.72 | 0.366405E+09 | 0.375462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187677E+10 | 0.135105E+10 | 0.214107E+11 | 0.00 | 0.480619E+10 | 0.80 | 501334.30 | 0.101636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177744E+10 | 0.118300E+10 | 0.207199E+11 | 0.00 | 0.513131E+10 | 0.77 | 0.00 | 0.192722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182969E+10 | 0.111309E+10 | 0.214107E+11 | 0.00 | 0.620777E+10 | 0.80 | 0.00 | 0.299081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.178230E+10 | 0.101833E+10 | 0.207201E+11 | 0.00 | 0.671155E+10 | 0.77 | 0.00 | 0.340844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181494E+10 | 0.108427E+10 | 0.214105E+11 | 0.00 | 0.726268E+10 | 0.79 | 0.00 | 0.363528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.186674E+10 | 0.117237E+10 | 0.214107E+11 | 0.00 | 0.721886E+10 | 0.80 | 0.00 | 0.350291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179469E+10 | 0.125381E+10 | 0.207199E+11 | 0.00 | 0.642035E+10 | 0.77 | 0.00 | 0.295454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186985E+10 | 0.142515E+10 | 0.214106E+11 | 0.00 | 0.515816E+10 | 0.79 | 0.00 | 0.167575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183357E+10 | 0.148683E+10 | 0.207200E+11 | 0.00 | 0.458703E+10 | 0.77 | 47488173.56 | 0.743934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189864E+10 | 0.160383E+10 | 0.214105E+11 | 0.00 | 0.464996E+10 | 0.79 | 0.800569E+09 | 0.220965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219465E+11 | 0.155921E+11 | 0.252093E+12 | 0.00 | 0.670152E+11 | 9.37 | 0.258111E+10 | 0.225786E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.170290E+10 | 0.101833E+10 | 0.193386E+11 | 0.00 | 0.421529E+10 | 0.72 | 0.00 | 0.126975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189898E+10 | 0.160383E+10 | 0.214107E+11 | 0.00 | 0.726268E+10 | 0.80 | 0.136615E+10 | 0.363528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.142223E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.00 | 0.00 | 0.125673E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.130724E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.114321E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.105585E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.928070E+10 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.915577E+10 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.946353E+10 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.100083E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.116001E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.124585E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.138198E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.00 | 0.00 | 0.137639E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.00 | 0.00 | 0.915577E+10 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.142223E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1346.16 | 02-JAN-17:40 | 1372.31 | 01-JAN-06:10 | 13637.09 | 01-JAN-11:09 | 0.00 | 2114.15 | 17-JAN-05:10 | 0.00 | 01-JAN-07:10 | 4648.29 | 05-JAN-07:10 |
February | 1346.16 | 01-FEB-17:00 | 1372.31 | 01-FEB-06:10 | 13637.09 | 01-FEB-11:09 | 0.00 | 2122.58 | 10-FEB-05:10 | 0.00 | 01-FEB-06:10 | 3118.32 | 02-FEB-07:10 |
March | 1346.16 | 01-MAR-18:19 | 1372.31 | 01-MAR-06:10 | 13637.09 | 01-MAR-11:09 | 0.00 | 2575.14 | 28-MAR-14:09 | 0.00 | 05-MAR-08:39 | 207.36 | 01-MAR-07:10 |
April | 1346.16 | 01-APR-18:40 | 1372.31 | 01-APR-05:10 | 13637.09 | 01-APR-10:09 | 0.00 | 3328.08 | 26-APR-17:10 | 0.00 | 22-APR-14:09 | 0.00 | 01-APR-00:10 |
May | 1346.16 | 01-MAY-18:00 | 1372.31 | 01-MAY-05:10 | 13637.09 | 01-MAY-10:09 | 0.00 | 3892.88 | 17-MAY-17:10 | 0.00 | 03-MAY-07:40 | 0.00 | 01-MAY-00:10 |
June | 1346.16 | 01-JUN-19:10 | 1372.31 | 01-JUN-05:10 | 13637.09 | 01-JUN-10:09 | 0.00 | 4332.21 | 22-JUN-17:10 | 0.00 | 24-JUN-14:30 | 0.00 | 01-JUN-00:10 |
July | 1346.16 | 01-JUL-19:19 | 1372.31 | 01-JUL-05:10 | 13637.09 | 01-JUL-10:09 | 0.00 | 4340.39 | 01-JUL-18:10 | 0.00 | 22-JUL-10:39 | 0.00 | 01-JUL-00:10 |
August | 1346.16 | 01-AUG-18:00 | 1372.31 | 01-AUG-05:10 | 13637.09 | 01-AUG-10:09 | 0.00 | 4252.41 | 25-AUG-11:00 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 1346.16 | 01-SEP-18:49 | 1372.31 | 01-SEP-05:10 | 13637.09 | 01-SEP-10:09 | 0.00 | 3966.20 | 14-SEP-17:19 | 0.00 | 08-SEP-13:50 | 0.00 | 01-SEP-00:10 |
October | 1346.16 | 02-OCT-17:00 | 1372.31 | 01-OCT-05:10 | 13637.09 | 01-OCT-10:09 | 0.00 | 3208.33 | 04-OCT-11:00 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1346.16 | 01-NOV-17:40 | 1372.31 | 01-NOV-05:10 | 13637.09 | 01-NOV-10:09 | 0.00 | 2360.83 | 09-NOV-11:00 | 0.00 | 26-NOV-09:09 | 1646.29 | 27-NOV-07:10 |
December | 1346.16 | 01-DEC-17:19 | 1372.31 | 01-DEC-06:10 | 13637.09 | 01-DEC-11:09 | 0.00 | 2114.15 | 15-DEC-05:10 | 0.00 | 01-DEC-06:10 | 4435.52 | 31-DEC-07:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1346.16 | 1372.31 | 13637.09 | 0.00 | 2114.15 | 0.00 | 0.00 | ||||||
Maximum of Months | 1346.16 | 1372.31 | 13637.09 | 0.00 | 4340.39 | 0.00 | 4648.29 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 5292.40 | 12-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7865.03 | 22-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13339.72 | 28-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19312.74 | 26-APR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23104.84 | 17-MAY-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25926.33 | 10-JUN-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24284.55 | 01-JUL-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22843.76 | 25-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22167.26 | 17-SEP-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17362.62 | 04-OCT-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10628.23 | 09-NOV-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6399.34 | 28-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5292.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25926.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 23126.12 | 26-JAN-11:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 2038.34 | 0.00 | 0.00 | 2528.55 | 0.00 |
February | 25826.02 | 22-FEB-11:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 2038.34 | 0.00 | 0.00 | 5229.21 | 0.00 |
March | 30002.37 | 28-MAR-16:10 | 1008.12 | 12287.48 | 0.00 | 0.00 | 2505.78 | 0.00 | 0.00 | 13043.22 | 0.00 |
April | 36567.97 | 27-APR-11:09 | 1008.12 | 12737.35 | 0.00 | 0.00 | 3181.38 | 0.00 | 0.00 | 17926.47 | 0.00 |
May | 40620.04 | 17-MAY-17:10 | 1008.12 | 11387.73 | 0.00 | 0.00 | 3892.88 | 0.00 | 0.00 | 23104.84 | 0.00 |
June | 43188.34 | 22-JUN-17:10 | 1008.12 | 11387.73 | 0.00 | 0.00 | 4332.21 | 0.00 | 0.00 | 25202.71 | 0.00 |
July | 42260.43 | 10-JUL-11:00 | 1008.12 | 12737.35 | 0.00 | 0.00 | 4042.45 | 0.00 | 0.00 | 23230.43 | 0.00 |
August | 42104.27 | 25-AUG-11:00 | 1008.12 | 12737.35 | 0.00 | 0.00 | 4252.41 | 0.00 | 0.00 | 22843.76 | 0.00 |
September | 39234.42 | 17-SEP-19:00 | 897.44 | 9588.24 | 1372.31 | 0.00 | 3882.49 | 0.00 | 0.00 | 22167.26 | 0.00 |
October | 35514.07 | 04-OCT-11:00 | 1008.12 | 12737.35 | 0.00 | 0.00 | 3208.33 | 0.00 | 0.00 | 17362.62 | 0.00 |
November | 29210.72 | 09-NOV-11:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 2129.49 | 0.00 | 0.00 | 8504.88 | 0.00 |
December | 24454.94 | 18-DEC-11:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 2038.34 | 0.00 | 0.00 | 3856.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 23126.12 | 897.44 | 9588.24 | 0.00 | 0.00 | 2038.34 | 0.00 | 0.00 | 2528.55 | 0.00 | |
Maximum of Months | 43188.34 | 1008.12 | 13637.09 | 1372.31 | 0.00 | 4332.21 | 0.00 | 0.00 | 25202.71 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 19453.17 | 16-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 19338.23 | 02-FEB-13:00 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 18610.35 | 01-MAR-13:39 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 16881.24 | 02-APR-12:30 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 15226.39 | 01-MAY-12:00 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 13624.96 | 01-JUN-12:20 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 12629.79 | 01-JUL-12:39 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 13255.63 | 31-AUG-12:20 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 14888.89 | 30-SEP-12:39 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 16625.58 | 31-OCT-12:39 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 18371.34 | 30-NOV-13:00 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 19316.32 | 31-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 26660.45 | 0.00 | 0.00 | 0.00 | 12629.79 | 0.00 | ||
Maximum of Months | 26660.45 | 0.00 | 0.00 | 0.00 | 19453.17 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.00 | 24.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.62 | 0.50 | 24.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 24.82 | 0.50 | 24.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 25.16 | 0.00 | 25.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 25.35 | 0.00 | 25.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 25.47 | 0.00 | 25.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 25.43 | 0.00 | 25.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 25.28 | 0.00 | 25.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 24.88 | 1.67 | 24.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 24.58 | 0.00 | 24.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 120.83 | 25.14 | 2.67 | 25.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 25.47 | 1.67 | 25.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.68 | 0.00 | 27.68 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 28.19 | 0.00 | 28.19 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 29.25 | 0.00 | 29.25 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 | 28.63 | 23.17 | 28.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 240.67 | 28.26 | 207.00 | 28.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 408.67 | 28.63 | 364.00 | 28.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 611.67 | 28.73 | 535.00 | 28.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 575.33 | 28.96 | 505.33 | 28.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 376.00 | 28.16 | 334.17 | 28.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 29.93 | 1.33 | 29.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 29.17 | 0.00 | 29.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.88 | 0.00 | 27.88 |
Annual Sum or Average | 0.00 | 0.00 | 2378.83 | 28.64 | 1970.00 | 28.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.68 | 0.00 | 27.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 611.67 | 29.93 | 535.00 | 29.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 426.83 | 21.37 | 80.67 | 21.70 | 6.00 | 21.66 |
February | 235.33 | 21.58 | 246.50 | 22.74 | 3.00 | 22.75 |
March | 80.00 | 22.48 | 491.17 | 23.71 | 6.33 | 23.72 |
April | 23.67 | 25.78 | 571.83 | 24.11 | 23.67 | 24.17 |
May | 200.50 | 24.50 | 611.00 | 24.20 | 200.50 | 24.26 |
June | 381.83 | 24.26 | 592.00 | 24.18 | 381.83 | 24.21 |
July | 583.17 | 24.14 | 609.00 | 24.13 | 583.17 | 24.13 |
August | 612.00 | 24.09 | 612.00 | 24.09 | 612.00 | 24.09 |
September | 532.17 | 24.08 | 590.00 | 24.07 | 532.17 | 24.07 |
October | 124.50 | 24.12 | 599.83 | 23.99 | 122.33 | 24.01 |
November | 132.83 | 22.02 | 417.83 | 23.41 | 5.50 | 23.41 |
December | 359.17 | 21.38 | 188.00 | 22.20 | 3.67 | 22.18 |
Annual Sum or Average | 3692.00 | 23.30 | 5609.83 | 23.73 | 2480.17 | 23.82 |
Minimum of Months | 23.67 | 21.37 | 80.67 | 21.70 | 3.00 | 21.66 |
Maximum of Months | 612.00 | 25.78 | 612.00 | 24.20 | 612.00 | 24.26 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 411.00 | 23.72 | 425.00 | 24.44 | 254.00 | 24.79 |
February | 389.83 | 25.40 | 484.83 | 25.42 | 341.50 | 25.60 |
March | 527.67 | 26.12 | 612.00 | 26.01 | 527.67 | 26.05 |
April | 587.50 | 26.30 | 590.00 | 26.30 | 587.50 | 26.30 |
May | 611.00 | 26.97 | 611.00 | 26.97 | 611.00 | 26.97 |
June | 592.00 | 27.82 | 592.00 | 27.82 | 592.00 | 27.82 |
July | 609.00 | 28.60 | 609.00 | 28.60 | 609.00 | 28.60 |
August | 612.00 | 28.67 | 612.00 | 28.67 | 612.00 | 28.67 |
September | 590.00 | 27.39 | 590.00 | 27.39 | 590.00 | 27.39 |
October | 605.83 | 26.16 | 610.00 | 26.16 | 605.83 | 26.16 |
November | 460.67 | 26.02 | 577.67 | 25.84 | 455.17 | 25.91 |
December | 393.67 | 24.69 | 464.50 | 25.00 | 294.17 | 25.25 |
Annual Sum or Average | 6390.17 | 26.68 | 6778.00 | 26.69 | 6079.83 | 26.79 |
Minimum of Months | 389.83 | 23.72 | 425.00 | 24.44 | 254.00 | 24.79 |
Maximum of Months | 612.00 | 28.67 | 612.00 | 28.67 | 612.00 | 28.67 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.08613 | 45.84194 | 0.03832 | 6.90400 |
February | 551.00000 | 22.84354 | 48.03839 | 0.25197 | 8.08622 |
March | 612.00000 | 23.70123 | 47.42816 | 0.48460 | 10.50174 |
April | 590.00000 | 24.03341 | 46.12818 | 0.59898 | 12.83913 |
May | 611.00000 | 24.10383 | 56.17859 | -0.0834 | 6.03658 |
June | 592.00000 | 24.13322 | 64.20597 | 0.00482 | 6.21370 |
July | 609.00000 | 24.12508 | 73.69822 | 0.07533 | 6.27903 |
August | 612.00000 | 24.09484 | 76.23693 | 0.08318 | 6.10052 |
September | 590.00000 | 24.06085 | 72.66412 | 0.02939 | 5.71527 |
October | 610.00000 | 23.94058 | 55.20591 | 0.66428 | 14.48474 |
November | 591.00000 | 23.38221 | 48.40328 | 0.44433 | 10.16684 |
December | 609.00000 | 22.35333 | 44.99743 | 0.12574 | 7.32351 |
Annual Sum or Average | 7187.00000 | 23.57429 | 56.64476 | 0.22577 | 8.38594 |
Minimum of Months | 551.00000 | 22.08613 | 44.99743 | -0.0834 | 5.71527 |
Maximum of Months | 612.00000 | 24.13322 | 76.23693 | 0.66428 | 14.48474 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.71859 | 47.63372 | 0.64704 | 20.20954 |
February | 551.00000 | 24.92107 | 47.64559 | 0.94395 | 27.21656 |
March | 612.00000 | 25.91782 | 47.15963 | 1.20201 | 35.92984 |
April | 590.00000 | 26.30183 | 47.13511 | 1.32441 | 41.71192 |
May | 611.00000 | 26.96719 | 55.68124 | 1.11014 | 32.74069 |
June | 592.00000 | 27.81695 | 62.02082 | 1.47071 | 49.73365 |
July | 609.00000 | 28.60055 | 67.74445 | 1.79551 | 65.11286 |
August | 612.00000 | 28.66744 | 67.68975 | 1.82323 | 65.77799 |
September | 590.00000 | 27.38668 | 65.49286 | 1.35368 | 44.11230 |
October | 610.00000 | 26.15623 | 53.26380 | 1.36008 | 43.52245 |
November | 591.00000 | 25.60693 | 47.78740 | 1.15088 | 34.11951 |
December | 609.00000 | 24.31397 | 45.68310 | 0.79631 | 22.99035 |
Annual Sum or Average | 7187.00000 | 26.37272 | 54.62583 | 1.24997 | 40.35351 |
Minimum of Months | 551.00000 | 23.71859 | 45.68310 | 0.64704 | 20.20954 |
Maximum of Months | 612.00000 | 28.66744 | 67.74445 | 1.82323 | 65.77799 |
Report: DXReportMonthly
For: PSZ-AC_1:1 HP COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.139551E+10 | 0.431285E+09 | 130.86 | 0.118516E+10 | 0.210356E+09 | 0.00 | 0.50 | 15-JAN-03:01 | 0.00 | 01-JAN-00:03 | 12673.49 | 15-JAN-03:01 | 7926.91 | 15-JAN-03:01 | 4746.58 | 15-JAN-03:01 | 3612.97 | 15-JAN-03:01 | 0.00 |
February | 0.549190E+10 | 0.164026E+10 | 264.31 | 0.449976E+10 | 0.992138E+09 | 0.00 | 0.66 | 23-FEB-03:01 | 0.00 | 01-FEB-00:05 | 17279.13 | 23-FEB-03:01 | 13326.00 | 22-FEB-12:55 | 6373.82 | 26-FEB-03:01 | 4727.42 | 23-FEB-03:01 | 0.00 |
March | 0.180235E+11 | 0.512993E+10 | 507.92 | 0.143324E+11 | 0.369107E+10 | 0.00 | 1.00 | 10-MAR-03:01 | 0.00 | 01-MAR-00:10 | 43000.85 | 12-MAR-02:61 | 29205.21 | 12-MAR-02:61 | 16862.72 | 13-MAR-02:61 | 10389.27 | 12-MAR-02:61 | 0.00 |
April | 0.348996E+11 | 0.998036E+10 | 603.63 | 0.288848E+11 | 0.601478E+10 | 0.00 | 1.00 | 01-APR-18:02 | 0.00 | 01-APR-00:02 | 63448.67 | 27-APR-02:61 | 51892.48 | 28-APR-02:61 | 27488.54 | 26-APR-02:61 | 14727.24 | 27-APR-02:61 | 0.00 |
May | 0.543711E+11 | 0.154433E+11 | 633.63 | 0.391963E+11 | 0.151748E+11 | 0.00 | 1.00 | 01-MAY-02:61 | 0.00 | 01-MAY-00:03 | 64091.70 | 23-MAY-02:61 | 54985.21 | 06-MAY-02:61 | 43765.07 | 23-MAY-02:61 | 15840.59 | 04-MAY-02:61 | 0.00 |
June | 0.648317E+11 | 0.178260E+11 | 620.52 | 0.400016E+11 | 0.248301E+11 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:03 | 64091.70 | 25-JUN-02:61 | 47372.82 | 05-JUN-02:61 | 43207.35 | 28-JUN-02:61 | 17464.03 | 10-JUN-18:10 | 0.00 |
July | 0.746358E+11 | 0.189203E+11 | 638.21 | 0.367207E+11 | 0.379151E+11 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:02 | 64091.70 | 11-JUL-02:61 | 35003.02 | 01-JUL-02:61 | 43704.78 | 19-JUL-02:61 | 16453.29 | 01-JUL-18:03 | 0.00 |
August | 0.731745E+11 | 0.180502E+11 | 633.36 | 0.332161E+11 | 0.399585E+11 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 64091.70 | 04-AUG-02:02 | 34044.54 | 03-AUG-02:61 | 45345.59 | 30-AUG-02:61 | 15348.20 | 25-AUG-11:55 | 0.00 |
September | 0.580726E+11 | 0.144718E+11 | 612.01 | 0.287181E+11 | 0.293545E+11 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:02 | 64091.70 | 12-SEP-02:61 | 35509.99 | 29-SEP-02:61 | 42402.24 | 12-SEP-02:02 | 14775.60 | 01-SEP-02:61 | 0.00 |
October | 0.311155E+11 | 0.849083E+10 | 604.26 | 0.219514E+11 | 0.916406E+10 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:02 | 64091.70 | 01-OCT-02:61 | 41822.46 | 05-OCT-02:61 | 31405.42 | 04-OCT-02:61 | 14775.60 | 01-OCT-02:61 | 0.00 |
November | 0.126572E+11 | 0.362759E+10 | 396.72 | 0.101485E+11 | 0.250868E+10 | 0.00 | 1.00 | 01-NOV-02:61 | 0.00 | 01-NOV-00:01 | 38297.79 | 10-NOV-03:01 | 24709.69 | 10-NOV-03:01 | 13588.10 | 10-NOV-03:01 | 9307.52 | 10-NOV-03:01 | 0.00 |
December | 0.272779E+10 | 0.831712E+09 | 191.71 | 0.225146E+10 | 0.476336E+09 | 0.00 | 0.51 | 29-DEC-03:01 | 0.00 | 01-DEC-00:10 | 12962.81 | 29-DEC-03:01 | 9760.80 | 28-DEC-14:00 | 4251.26 | 29-DEC-03:01 | 3685.73 | 29-DEC-03:01 | 0.00 |
Annual Sum or Average | 0.431397E+12 | 0.114844E+12 | 5837.15 | 0.261106E+12 | 0.170290E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.139551E+10 | 0.431285E+09 | 130.86 | 0.118516E+10 | 0.210356E+09 | 0.00 | 0.50 | 0.00 | 12673.49 | 7926.91 | 4251.26 | 3612.97 | 0.00 | ||||||
Maximum of Months | 0.746358E+11 | 0.189203E+11 | 638.21 | 0.400016E+11 | 0.399585E+11 | 0.00 | 1.00 | 0.00 | 64091.70 | 54985.21 | 45345.59 | 17464.03 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 HP COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.294088E+10 | 0.838463E+09 | 237.35 | 0.222970E+10 | 0.711186E+09 | 0.00 | 1.00 | 06-JAN-05:01 | 0.00 | 01-JAN-00:03 | 27960.76 | 14-JAN-03:01 | 17329.41 | 12-JAN-03:01 | 15144.35 | 16-JAN-03:01 | 6818.00 | 12-JAN-03:01 | 0.00 |
February | 0.785221E+10 | 0.211436E+10 | 343.38 | 0.610307E+10 | 0.174914E+10 | 0.00 | 1.00 | 03-FEB-03:01 | 0.00 | 01-FEB-00:05 | 27960.76 | 20-FEB-03:01 | 18598.32 | 18-FEB-03:01 | 13947.47 | 16-FEB-03:11 | 6818.00 | 07-FEB-03:01 | 0.00 |
March | 0.197420E+11 | 0.503364E+10 | 557.85 | 0.161883E+11 | 0.355374E+10 | 0.00 | 1.00 | 01-MAR-03:01 | 0.00 | 01-MAR-00:10 | 29066.93 | 29-MAR-02:11 | 24305.93 | 28-MAR-14:10 | 15205.55 | 31-MAR-02:11 | 6893.22 | 29-MAR-02:11 | 0.00 |
April | 0.358725E+11 | 0.929187E+10 | 655.58 | 0.322202E+11 | 0.365226E+10 | 0.00 | 1.00 | 01-APR-02:11 | 0.00 | 01-APR-00:02 | 30806.96 | 20-APR-02:61 | 29594.36 | 16-APR-10:43 | 15646.61 | 23-APR-02:61 | 8541.19 | 27-APR-14:55 | 0.00 |
May | 0.558022E+11 | 0.144648E+11 | 704.03 | 0.450736E+11 | 0.107286E+11 | 0.00 | 1.00 | 01-MAY-02:61 | 0.00 | 01-MAY-00:03 | 31066.25 | 24-MAY-02:61 | 29584.34 | 03-MAY-19:23 | 20694.50 | 22-MAY-23:00 | 9208.46 | 03-MAY-14:55 | 0.00 |
June | 0.638099E+11 | 0.162584E+11 | 685.08 | 0.440418E+11 | 0.197681E+11 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:03 | 31066.25 | 24-JUN-07:50 | 29515.79 | 04-JUN-10:41 | 21738.41 | 24-JUN-14:00 | 9111.87 | 07-JUN-15:53 | 0.00 |
July | 0.721848E+11 | 0.174325E+11 | 709.98 | 0.367899E+11 | 0.353948E+11 | 0.00 | 1.00 | 01-JUL-00:06 | 0.00 | 01-JUL-00:02 | 31066.25 | 18-JUL-13:00 | 29015.52 | 04-JUL-20:25 | 22336.01 | 19-JUL-04:02 | 8372.34 | 02-JUL-15:53 | 0.00 |
August | 0.722187E+11 | 0.169789E+11 | 707.57 | 0.312037E+11 | 0.410150E+11 | 0.00 | 1.00 | 01-AUG-00:04 | 0.00 | 01-AUG-00:01 | 31066.25 | 12-AUG-07:10 | 22815.14 | 07-AUG-14:00 | 23600.29 | 12-AUG-07:55 | 7924.68 | 07-AUG-14:55 | 0.00 |
September | 0.646340E+11 | 0.150736E+11 | 673.38 | 0.305703E+11 | 0.340637E+11 | 0.00 | 1.00 | 01-SEP-00:05 | 0.00 | 01-SEP-00:02 | 31066.25 | 07-SEP-09:25 | 27572.03 | 29-SEP-13:00 | 22167.40 | 10-SEP-02:13 | 7951.91 | 17-SEP-20:00 | 0.00 |
October | 0.338848E+11 | 0.826670E+10 | 652.88 | 0.245969E+11 | 0.928785E+10 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:02 | 31066.25 | 04-OCT-02:61 | 28379.79 | 02-OCT-13:00 | 19285.35 | 12-OCT-03:32 | 7631.78 | 03-OCT-13:00 | 0.00 |
November | 0.148719E+11 | 0.381176E+10 | 469.69 | 0.118952E+11 | 0.297672E+10 | 0.00 | 1.00 | 01-NOV-02:61 | 0.00 | 01-NOV-00:01 | 27960.76 | 13-NOV-03:11 | 17451.48 | 09-NOV-12:05 | 14637.82 | 09-NOV-03:11 | 6818.00 | 01-NOV-02:61 | 0.00 |
December | 0.497641E+10 | 0.137794E+10 | 278.20 | 0.379238E+10 | 0.118403E+10 | 0.00 | 1.00 | 01-DEC-03:01 | 0.00 | 01-DEC-00:10 | 27960.76 | 06-DEC-03:01 | 19418.44 | 30-DEC-03:01 | 13916.39 | 28-DEC-03:01 | 6818.00 | 01-DEC-03:01 | 0.00 |
Annual Sum or Average | 0.448790E+12 | 0.110943E+12 | 6674.96 | 0.284705E+12 | 0.164085E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.294088E+10 | 0.838463E+09 | 237.35 | 0.222970E+10 | 0.711186E+09 | 0.00 | 1.00 | 0.00 | 27960.76 | 17329.41 | 13916.39 | 6818.00 | 0.00 | ||||||
Maximum of Months | 0.722187E+11 | 0.174325E+11 | 709.98 | 0.450736E+11 | 0.410150E+11 | 0.00 | 1.00 | 0.00 | 31066.25 | 29594.36 | 23600.29 | 9208.46 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.96 | 25.67 | 38.29 | 71.35 | 112.80 | 0.00 | 0.00 | 0.00 |
February | 77.70 | 32.08 | 45.62 | 109.63 | 88.32 | 0.00 | 0.00 | 0.00 |
March | 94.79 | 39.12 | 55.66 | 166.95 | 53.13 | 0.00 | 0.00 | 0.00 |
April | 112.77 | 52.58 | 60.19 | 252.00 | 18.51 | 0.00 | 0.00 | 0.00 |
May | 111.00 | 49.21 | 61.79 | 288.14 | 3.23 | 0.00 | 0.00 | 0.00 |
June | 90.34 | 29.97 | 60.36 | 258.08 | 2.62 | 0.00 | 0.00 | 0.00 |
July | 75.93 | 16.03 | 59.89 | 212.18 | 0.90 | 0.33 | 0.00 | 0.00 |
August | 68.41 | 11.91 | 56.51 | 177.23 | 2.69 | 0.00 | 0.00 | 0.00 |
September | 73.09 | 20.38 | 52.71 | 165.52 | 9.55 | 0.00 | 0.00 | 0.00 |
October | 79.95 | 32.30 | 47.66 | 158.84 | 44.14 | 0.00 | 0.00 | 0.00 |
November | 70.89 | 30.43 | 40.46 | 112.00 | 82.22 | 0.00 | 0.00 | 0.00 |
December | 61.81 | 24.49 | 37.32 | 74.08 | 112.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.70 | 30.30 | 51.40 | 170.71 | 43.99 | 0.33 | 0.00 | 0.00 |
Minimum of Months | 61.81 | 11.91 | 37.32 | 71.35 | 0.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.77 | 52.58 | 61.79 | 288.14 | 112.80 | 0.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.58 | 165.02 | 106.56 | 406.62 | 222.18 | 0.00 | 0.00 | 0.00 |
February | 258.23 | 143.43 | 114.80 | 420.91 | 178.62 | 0.00 | 0.00 | 0.00 |
March | 220.79 | 97.52 | 123.27 | 419.80 | 110.45 | 0.00 | 0.00 | 0.00 |
April | 155.09 | 43.77 | 111.32 | 399.19 | 38.57 | 0.00 | 0.00 | 0.00 |
May | 111.53 | 8.26 | 103.27 | 373.06 | 6.47 | 0.00 | 0.00 | 0.00 |
June | 102.02 | 1.74 | 100.28 | 363.72 | 5.26 | 0.00 | 0.00 | 0.00 |
July | 106.42 | 1.46 | 104.95 | 337.71 | 1.83 | 0.33 | 0.00 | 0.00 |
August | 112.88 | 6.03 | 106.86 | 313.73 | 5.42 | 0.00 | 0.00 | 0.00 |
September | 151.33 | 39.28 | 112.05 | 354.19 | 19.40 | 0.00 | 0.00 | 0.00 |
October | 260.35 | 145.38 | 114.97 | 523.65 | 90.11 | 0.00 | 0.00 | 0.00 |
November | 325.19 | 214.94 | 110.25 | 571.02 | 166.53 | 0.00 | 0.00 | 0.00 |
December | 290.22 | 181.86 | 108.36 | 450.55 | 219.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 196.78 | 87.07 | 109.72 | 410.98 | 88.29 | 0.33 | 0.00 | 0.00 |
Minimum of Months | 102.02 | 1.46 | 100.28 | 313.73 | 1.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 325.19 | 214.94 | 123.27 | 571.02 | 222.18 | 0.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.57 | 24.35 | 38.22 | 75.77 | 120.04 | 0.00 | 0.00 | 0.00 |
February | 71.55 | 26.37 | 45.18 | 103.27 | 93.47 | 0.00 | 0.00 | 0.00 |
March | 92.79 | 37.09 | 55.70 | 165.35 | 55.85 | 0.00 | 0.00 | 0.00 |
April | 112.78 | 52.89 | 59.89 | 252.37 | 18.92 | 0.00 | 0.00 | 0.00 |
May | 106.79 | 45.30 | 61.49 | 280.76 | 3.32 | 0.00 | 0.00 | 0.00 |
June | 100.31 | 38.96 | 61.34 | 277.37 | 2.60 | 0.00 | 0.00 | 0.00 |
July | 74.43 | 14.48 | 59.95 | 208.57 | 0.99 | 0.33 | 0.00 | 0.00 |
August | 68.36 | 12.15 | 56.21 | 177.40 | 2.72 | 0.00 | 0.00 | 0.00 |
September | 75.14 | 22.06 | 53.08 | 169.68 | 9.64 | 0.00 | 0.00 | 0.00 |
October | 78.21 | 31.14 | 47.07 | 157.49 | 45.80 | 0.00 | 0.00 | 0.00 |
November | 70.76 | 30.16 | 40.60 | 116.67 | 86.69 | 0.00 | 0.00 | 0.00 |
December | 60.55 | 23.09 | 37.46 | 75.46 | 116.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.17 | 29.80 | 51.37 | 171.89 | 46.17 | 0.33 | 0.00 | 0.00 |
Minimum of Months | 60.55 | 12.15 | 37.46 | 75.46 | 0.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.78 | 52.89 | 61.49 | 280.76 | 120.04 | 0.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171302E+09 | 68758244.32 | 0.102544E+09 | 0.191100E+09 | 0.302119E+09 |
February | 0.187971E+09 | 77603017.01 | 0.110368E+09 | 0.265221E+09 | 0.213658E+09 |
March | 0.253873E+09 | 0.104790E+09 | 0.149083E+09 | 0.447160E+09 | 0.142296E+09 |
April | 0.292300E+09 | 0.136285E+09 | 0.156015E+09 | 0.653178E+09 | 47969660.35 |
May | 0.297293E+09 | 0.131803E+09 | 0.165490E+09 | 0.771746E+09 | 8650447.33 |
June | 0.234153E+09 | 77691470.85 | 0.156461E+09 | 0.668936E+09 | 6802449.79 |
July | 0.203359E+09 | 42943938.22 | 0.160415E+09 | 0.568314E+09 | 2403889.35 |
August | 0.183235E+09 | 31887135.15 | 0.151348E+09 | 0.474703E+09 | 7201872.92 |
September | 0.189451E+09 | 52833016.04 | 0.136618E+09 | 0.429036E+09 | 24742075.48 |
October | 0.214145E+09 | 86500154.89 | 0.127645E+09 | 0.425437E+09 | 0.118230E+09 |
November | 0.183745E+09 | 78871726.17 | 0.104874E+09 | 0.290308E+09 | 0.213113E+09 |
December | 0.165559E+09 | 65595291.96 | 99963664.62 | 0.198423E+09 | 0.300070E+09 |
Annual Sum or Average | 0.257639E+10 | 0.955562E+09 | 0.162082E+10 | 0.538356E+10 | 0.138726E+10 |
Minimum of Months | 0.165559E+09 | 31887135.15 | 99963664.62 | 0.191100E+09 | 2403889.35 |
Maximum of Months | 0.297293E+09 | 0.136285E+09 | 0.165490E+09 | 0.771746E+09 | 0.302119E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.727392E+09 | 0.441982E+09 | 0.285410E+09 | 0.108908E+10 | 0.595074E+09 |
February | 0.624711E+09 | 0.346982E+09 | 0.277729E+09 | 0.101826E+10 | 0.432112E+09 |
March | 0.591373E+09 | 0.261204E+09 | 0.330169E+09 | 0.112439E+10 | 0.295830E+09 |
April | 0.401984E+09 | 0.113452E+09 | 0.288532E+09 | 0.103469E+10 | 99978453.29 |
May | 0.298716E+09 | 22112978.05 | 0.276603E+09 | 0.999199E+09 | 17338081.06 |
June | 0.264433E+09 | 4512464.01 | 0.259921E+09 | 0.942766E+09 | 13628124.11 |
July | 0.285023E+09 | 3920248.80 | 0.281103E+09 | 0.904536E+09 | 4908525.42 |
August | 0.302349E+09 | 16147681.32 | 0.286201E+09 | 0.840299E+09 | 14506955.88 |
September | 0.392248E+09 | 0.101809E+09 | 0.290440E+09 | 0.918065E+09 | 50292302.75 |
October | 0.697316E+09 | 0.389378E+09 | 0.307938E+09 | 0.140256E+10 | 0.241339E+09 |
November | 0.842888E+09 | 0.557131E+09 | 0.285757E+09 | 0.148007E+10 | 0.431658E+09 |
December | 0.777331E+09 | 0.487097E+09 | 0.290234E+09 | 0.120675E+10 | 0.587665E+09 |
Annual Sum or Average | 0.620576E+10 | 0.274573E+10 | 0.346004E+10 | 0.129607E+11 | 0.278433E+10 |
Minimum of Months | 0.264433E+09 | 3920248.80 | 0.259921E+09 | 0.840299E+09 | 4908525.42 |
Maximum of Months | 0.842888E+09 | 0.557131E+09 | 0.330169E+09 | 0.148007E+10 | 0.595074E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167592E+09 | 65220211.76 | 0.102372E+09 | 0.202953E+09 | 0.321511E+09 |
February | 0.173099E+09 | 63791643.98 | 0.109308E+09 | 0.249829E+09 | 0.226111E+09 |
March | 0.248516E+09 | 99340234.55 | 0.149175E+09 | 0.442886E+09 | 0.149580E+09 |
April | 0.292324E+09 | 0.137089E+09 | 0.155236E+09 | 0.654135E+09 | 49034182.18 |
May | 0.286030E+09 | 0.121328E+09 | 0.164702E+09 | 0.751983E+09 | 8898834.09 |
June | 0.259992E+09 | 0.100988E+09 | 0.159005E+09 | 0.718955E+09 | 6729054.08 |
July | 0.199359E+09 | 38775257.33 | 0.160583E+09 | 0.558634E+09 | 2653948.30 |
August | 0.183090E+09 | 32540604.47 | 0.150549E+09 | 0.475137E+09 | 7291700.74 |
September | 0.194772E+09 | 57179271.37 | 0.137592E+09 | 0.439804E+09 | 24985236.04 |
October | 0.209485E+09 | 83416332.71 | 0.126068E+09 | 0.421820E+09 | 0.122670E+09 |
November | 0.183400E+09 | 78163883.48 | 0.105236E+09 | 0.302418E+09 | 0.224701E+09 |
December | 0.162168E+09 | 61838181.87 | 0.100330E+09 | 0.202123E+09 | 0.311890E+09 |
Annual Sum or Average | 0.255983E+10 | 0.939670E+09 | 0.162016E+10 | 0.542068E+10 | 0.145606E+10 |
Minimum of Months | 0.162168E+09 | 32540604.47 | 0.100330E+09 | 0.202123E+09 | 2653948.30 |
Maximum of Months | 0.292324E+09 | 0.137089E+09 | 0.164702E+09 | 0.751983E+09 | 0.321511E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 541.60 | 442.88 | 398.11 | 215.04 | 183.07 | 0.00 | 0.00 |
February | 626.78 | 353.38 | 407.48 | 201.88 | 205.61 | 0.00 | 0.00 |
March | 747.39 | 214.71 | 408.36 | 173.74 | 234.63 | 0.00 | 0.00 |
April | 902.28 | 74.73 | 380.64 | 149.24 | 231.40 | 0.00 | 0.00 |
May | 941.89 | 12.96 | 329.32 | 102.76 | 226.55 | 0.00 | 0.00 |
June | 899.11 | 10.41 | 292.66 | 70.68 | 221.99 | 0.00 | 0.00 |
July | 758.46 | 3.72 | 256.77 | 31.97 | 224.80 | 0.00 | 0.00 |
August | 668.34 | 10.81 | 249.65 | 30.08 | 219.57 | 0.00 | 0.00 |
September | 689.23 | 38.42 | 299.56 | 81.72 | 217.84 | 0.00 | 0.00 |
October | 838.52 | 178.58 | 418.51 | 208.82 | 209.70 | 0.00 | 0.00 |
November | 795.82 | 331.57 | 466.83 | 275.53 | 191.31 | 0.00 | 0.00 |
December | 590.66 | 438.46 | 412.58 | 229.44 | 183.14 | 0.00 | 0.00 |
Annual Sum or Average | 750.24 | 175.11 | 359.65 | 147.16 | 212.49 | 0.00 | 0.00 |
Minimum of Months | 541.60 | 3.72 | 249.65 | 30.08 | 183.07 | 0.00 | 0.00 |
Maximum of Months | 941.89 | 442.88 | 466.83 | 275.53 | 234.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.145063E+10 | 0.118620E+10 | 0.106629E+10 | 0.575960E+09 | 0.490326E+09 | 0.00 | 0.00 |
February | 0.151632E+10 | 0.854886E+09 | 0.985781E+09 | 0.488376E+09 | 0.497405E+09 | 0.00 | 0.00 |
March | 0.200180E+10 | 0.575075E+09 | 0.109376E+10 | 0.465334E+09 | 0.628428E+09 | 0.00 | 0.00 |
April | 0.233872E+10 | 0.193697E+09 | 0.986607E+09 | 0.386825E+09 | 0.599782E+09 | 0.00 | 0.00 |
May | 0.252275E+10 | 34705032.51 | 0.882039E+09 | 0.275244E+09 | 0.606795E+09 | 0.00 | 0.00 |
June | 0.233049E+10 | 26991280.00 | 0.758579E+09 | 0.183192E+09 | 0.575387E+09 | 0.00 | 0.00 |
July | 0.203147E+10 | 9952973.56 | 0.687741E+09 | 85639444.35 | 0.602102E+09 | 0.00 | 0.00 |
August | 0.179008E+10 | 28946045.00 | 0.668674E+09 | 80575420.94 | 0.588099E+09 | 0.00 | 0.00 |
September | 0.178648E+10 | 99594275.80 | 0.776470E+09 | 0.211821E+09 | 0.564650E+09 | 0.00 | 0.00 |
October | 0.224588E+10 | 0.478307E+09 | 0.112095E+10 | 0.559294E+09 | 0.561651E+09 | 0.00 | 0.00 |
November | 0.206276E+10 | 0.859428E+09 | 0.121003E+10 | 0.714166E+09 | 0.495867E+09 | 0.00 | 0.00 |
December | 0.158204E+10 | 0.117437E+10 | 0.110506E+10 | 0.614530E+09 | 0.490528E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.236594E+11 | 0.552215E+10 | 0.113420E+11 | 0.464096E+10 | 0.670102E+10 | 0.00 | 0.00 |
Minimum of Months | 0.145063E+10 | 9952973.56 | 0.668674E+09 | 80575420.94 | 0.490326E+09 | 0.00 | 0.00 |
Maximum of Months | 0.252275E+10 | 0.118620E+10 | 0.121003E+10 | 0.714166E+09 | 0.628428E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.114922E+11 | -0.107664E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -725780732.6 | 60.05 | 0.00 | 0.00 |
February | 0.101549E+11 | -0.952004E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -634868121.9 | 60.05 | 0.00 | 0.00 |
March | 0.105630E+11 | -0.987943E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -683542636.1 | 60.05 | 0.00 | 0.00 |
April | 0.923767E+10 | -0.858335E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -654315452.3 | 60.05 | 0.00 | 0.00 |
May | 0.853173E+10 | -0.786717E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -664563437.8 | 60.05 | 0.00 | 0.00 |
June | 0.749905E+10 | -0.687056E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -628489176.1 | 60.05 | 0.00 | 0.00 |
July | 0.739832E+10 | -0.676317E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -635150677.8 | 60.05 | 0.00 | 0.00 |
August | 0.764684E+10 | -0.701292E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -633916517.5 | 60.05 | 0.00 | 0.00 |
September | 0.808713E+10 | -0.745148E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -635648507.2 | 60.05 | 0.00 | 0.00 |
October | 0.937344E+10 | -0.869487E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -678575201.6 | 60.05 | 0.00 | 0.00 |
November | 0.100670E+11 | -0.939985E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667134697.9 | 60.05 | 0.00 | 0.00 |
December | 0.111669E+11 | -0.104525E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -714411993.3 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.111218E+12 | -0.103262E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.795640E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.739832E+10 | -0.107664E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -725780732.6 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.114922E+11 | -0.676317E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -628489176.1 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.29 | 0.24 | 01-JAN-07:00 | 1325.88 | 23.21 | 108.17 | 285.67 | 1325.14 | 23.12 | 106.83 | 284.83 |
February | 303.83 | 0.27 | 0.24 | 01-FEB-07:49 | 1269.80 | 22.66 | 91.33 | 276.50 | 1291.18 | 22.57 | 93.33 | 272.83 |
March | 364.50 | 0.27 | 0.24 | 01-MAR-07:30 | 1453.60 | 20.43 | 57.83 | 338.67 | 1107.95 | 18.50 | 3.67 | 338.17 |
April | 379.83 | 0.29 | 0.24 | 01-APR-06:00 | 993.25 | 17.22 | 0.00 | 338.67 | 1077.48 | 17.23 | 0.00 | 339.00 |
May | 406.00 | 0.28 | 0.24 | 01-MAY-06:10 | 926.70 | 17.11 | 0.00 | 368.50 | 1153.10 | 17.08 | 0.00 | 364.33 |
June | 386.67 | 0.29 | 0.24 | 01-JUN-06:49 | 907.02 | 16.78 | 0.00 | 344.33 | 935.55 | 16.86 | 0.00 | 346.17 |
July | 379.83 | 0.27 | 0.24 | 01-JUL-06:19 | 819.19 | 17.29 | 0.00 | 343.17 | 858.98 | 17.31 | 0.00 | 345.33 |
August | 372.50 | 0.28 | 0.24 | 01-AUG-06:40 | 847.38 | 17.31 | 0.00 | 330.00 | 845.79 | 17.31 | 0.00 | 331.17 |
September | 344.33 | 0.28 | 0.24 | 01-SEP-06:00 | 1113.03 | 18.15 | 5.83 | 311.33 | 982.21 | 18.14 | 6.67 | 313.17 |
October | 347.33 | 0.29 | 0.24 | 01-OCT-06:49 | 1152.94 | 20.26 | 60.67 | 309.83 | 1138.72 | 20.19 | 60.67 | 308.33 |
November | 317.83 | 0.27 | 0.24 | 01-NOV-07:10 | 1253.58 | 23.40 | 110.17 | 287.33 | 1505.72 | 23.14 | 106.67 | 285.67 |
December | 315.50 | 0.28 | 0.24 | 01-DEC-07:30 | 1403.26 | 25.22 | 133.50 | 287.83 | 1475.83 | 23.28 | 96.83 | 283.83 |
Annual Sum or Average | 4237.50 | 0.28 | 1107.95 | 19.69 | 567.50 | 3821.83 | 1127.49 | 19.34 | 474.67 | 3812.83 | ||
Minimum of Months | 303.83 | 0.27 | 0.24 | 819.19 | 16.78 | 0.00 | 276.50 | 845.79 | 16.86 | 0.00 | 272.83 | |
Maximum of Months | 406.00 | 0.29 | 0.24 | 1453.60 | 25.22 | 133.50 | 368.50 | 1505.72 | 23.28 | 106.83 | 364.33 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.411167E+10 | 12187.60 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115210E+10 | 9569.57 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1639832.76 | 677.87 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150381E+09 | 5165.31 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.247298E+10 | 12953.68 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.788877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.411167E+10 | 12953.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106596E+09 | 4994.55 | 02-JAN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22620364.36 | 2955.56 | 21-DEC-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106596E+09 | 4994.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HP COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.139551E+10 | 0.118516E+10 | 12673.49 | 15-JAN-03:01 | 7926.91 | 0.00 |
February | 0.00 | 0.00 | 0.549190E+10 | 0.449976E+10 | 17279.13 | 23-FEB-03:01 | 11471.06 | 0.00 |
March | 0.00 | 0.00 | 0.180235E+11 | 0.143324E+11 | 43000.85 | 12-MAR-02:61 | 29205.21 | 0.00 |
April | 0.00 | 0.00 | 0.348996E+11 | 0.288848E+11 | 63448.67 | 27-APR-02:61 | 36391.39 | 0.00 |
May | 0.00 | 0.00 | 0.543711E+11 | 0.391963E+11 | 64091.70 | 23-MAY-02:61 | 20326.63 | 0.00 |
June | 0.00 | 0.00 | 0.648317E+11 | 0.400016E+11 | 64091.70 | 25-JUN-02:61 | 23137.65 | 0.00 |
July | 0.00 | 0.00 | 0.746358E+11 | 0.367207E+11 | 64091.70 | 11-JUL-02:61 | 31065.11 | 0.00 |
August | 0.00 | 0.00 | 0.731745E+11 | 0.332161E+11 | 64091.70 | 04-AUG-02:02 | 26358.00 | 0.00 |
September | 0.00 | 0.00 | 0.580726E+11 | 0.287181E+11 | 64091.70 | 12-SEP-02:61 | 21833.13 | 0.00 |
October | 0.00 | 0.00 | 0.311155E+11 | 0.219514E+11 | 64091.70 | 01-OCT-02:61 | 35272.39 | 0.00 |
November | 0.00 | 0.00 | 0.126572E+11 | 0.101485E+11 | 38297.79 | 10-NOV-03:01 | 24709.69 | 0.00 |
December | 0.00 | 0.00 | 0.272779E+10 | 0.225146E+10 | 12962.81 | 29-DEC-03:01 | 8711.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.431397E+12 | 0.261106E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.139551E+10 | 0.118516E+10 | 12673.49 | 7926.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.746358E+11 | 0.400016E+11 | 64091.70 | 36391.39 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HP COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.294088E+10 | 0.222970E+10 | 27960.76 | 14-JAN-03:01 | 16268.07 | 0.00 |
February | 0.00 | 0.00 | 0.785221E+10 | 0.610307E+10 | 27960.76 | 20-FEB-03:01 | 16353.31 | 0.00 |
March | 0.00 | 0.00 | 0.197420E+11 | 0.161883E+11 | 29066.93 | 29-MAR-02:11 | 15105.43 | 0.00 |
April | 0.00 | 0.00 | 0.358725E+11 | 0.322202E+11 | 30806.96 | 20-APR-02:61 | 19506.96 | 0.00 |
May | 0.00 | 0.00 | 0.558022E+11 | 0.450736E+11 | 31066.25 | 24-MAY-02:61 | 13110.64 | 0.00 |
June | 0.00 | 0.00 | 0.638099E+11 | 0.440418E+11 | 31066.25 | 24-JUN-07:50 | 9506.18 | 0.00 |
July | 0.00 | 0.00 | 0.721848E+11 | 0.367899E+11 | 31066.25 | 18-JUL-13:00 | 9324.25 | 0.00 |
August | 0.00 | 0.00 | 0.722187E+11 | 0.312037E+11 | 31066.25 | 12-AUG-07:10 | 7836.18 | 0.00 |
September | 0.00 | 0.00 | 0.646340E+11 | 0.305703E+11 | 31066.25 | 07-SEP-09:25 | 9497.79 | 0.00 |
October | 0.00 | 0.00 | 0.338848E+11 | 0.245969E+11 | 31066.25 | 04-OCT-02:61 | 14379.65 | 0.00 |
November | 0.00 | 0.00 | 0.148719E+11 | 0.118952E+11 | 27960.76 | 13-NOV-03:11 | 14970.22 | 0.00 |
December | 0.00 | 0.00 | 0.497641E+10 | 0.379238E+10 | 27960.76 | 06-DEC-03:01 | 15600.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.448790E+12 | 0.284705E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.294088E+10 | 0.222970E+10 | 27960.76 | 7836.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.722187E+11 | 0.450736E+11 | 31066.25 | 19506.96 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4000.92 | 15381.40 | 17-JAN-13:30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 3916.42 | 15289.07 | 01-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3669.96 | 14633.25 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:02 | 3293.63 | 13350.23 | 01-APR-12:17 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 2919.89 | 11879.55 | 01-MAY-12:30 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 2633.64 | 10529.92 | 01-JUN-12:37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 2508.33 | 9740.28 | 01-JUL-13:00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 2601.31 | 10365.62 | 31-AUG-13:00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 2857.58 | 11606.97 | 30-SEP-12:30 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 3228.54 | 13125.81 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3608.05 | 14433.29 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 3883.80 | 15252.59 | 31-DEC-13:20 |
Annual Sum or Average | 0.00 | 3256.55 | ||||
Minimum of Months | 0.00 | 0.00 | 2508.33 | 9740.28 | ||
Maximum of Months | 0.00 | 0.00 | 4000.92 | 15381.40 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:02 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.120873E+10 | 0.24 | 503.64 | 01-JAN-00:03 | 0.27 |
February | 0.110236E+10 | 0.24 | 503.64 | 01-FEB-00:05 | 0.27 |
March | 0.126116E+10 | 0.25 | 503.64 | 01-MAR-00:10 | 0.27 |
April | 0.124486E+10 | 0.26 | 503.64 | 01-APR-00:16 | 0.27 |
May | 0.128895E+10 | 0.26 | 503.64 | 01-MAY-00:08 | 0.27 |
June | 0.124767E+10 | 0.25 | 503.64 | 01-JUN-00:08 | 0.27 |
July | 0.128972E+10 | 0.25 | 503.64 | 01-JUL-00:06 | 0.27 |
August | 0.128985E+10 | 0.25 | 503.64 | 01-AUG-00:04 | 0.26 |
September | 0.124719E+10 | 0.25 | 503.64 | 01-SEP-00:05 | 0.26 |
October | 0.128656E+10 | 0.26 | 503.64 | 01-OCT-00:06 | 0.27 |
November | 0.120959E+10 | 0.25 | 503.64 | 01-NOV-00:40 | 0.27 |
December | 0.120993E+10 | 0.24 | 503.64 | 01-DEC-00:10 | 0.27 |
Annual Sum or Average | 0.148866E+11 | 0.25 | |||
Minimum of Months | 0.110236E+10 | 0.24 | 503.64 | 0.26 | |
Maximum of Months | 0.128985E+10 | 0.26 | 503.64 | 0.27 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.229757E+10 | 0.45 | 1029.25 | 01-JAN-05:27 | 0.54 |
February | 0.207643E+10 | 0.46 | 1029.25 | 03-FEB-15:40 | 0.54 |
March | 0.230626E+10 | 0.48 | 1700.83 | 12-MAR-02:61 | 0.73 |
April | 0.227820E+10 | 0.49 | 2573.12 | 15-APR-02:61 | 0.89 |
May | 0.259171E+10 | 0.51 | 2573.12 | 02-MAY-02:61 | 0.89 |
June | 0.280267E+10 | 0.54 | 2573.12 | 01-JUN-02:61 | 0.89 |
July | 0.298579E+10 | 0.54 | 2573.12 | 01-JUL-02:61 | 0.89 |
August | 0.295779E+10 | 0.54 | 2573.12 | 01-AUG-02:61 | 0.88 |
September | 0.252021E+10 | 0.51 | 2573.12 | 01-SEP-02:61 | 0.88 |
October | 0.233171E+10 | 0.49 | 2573.12 | 01-OCT-02:61 | 0.89 |
November | 0.222995E+10 | 0.48 | 1474.79 | 10-NOV-03:01 | 0.68 |
December | 0.229741E+10 | 0.45 | 1029.25 | 02-DEC-15:03 | 0.54 |
Annual Sum or Average | 0.296757E+11 | 0.49 | |||
Minimum of Months | 0.207643E+10 | 0.45 | 1029.25 | 0.54 | |
Maximum of Months | 0.298579E+10 | 0.54 | 2573.12 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113979E+10 | 0.50 | 1263.64 | 12-JAN-03:01 | 0.93 |
February | 0.103650E+10 | 0.50 | 1263.64 | 07-FEB-03:01 | 0.93 |
March | 0.123877E+10 | 0.54 | 1263.64 | 01-MAR-03:01 | 0.93 |
April | 0.160825E+10 | 0.63 | 1263.64 | 01-APR-02:11 | 0.93 |
May | 0.232711E+10 | 0.74 | 1263.64 | 01-MAY-02:61 | 0.92 |
June | 0.266121E+10 | 0.80 | 1263.64 | 01-JUN-02:61 | 0.92 |
July | 0.298717E+10 | 0.83 | 1263.64 | 01-JUL-02:61 | 0.92 |
August | 0.297122E+10 | 0.83 | 1263.64 | 01-AUG-00:04 | 0.91 |
September | 0.265295E+10 | 0.80 | 1263.64 | 01-SEP-02:61 | 0.91 |
October | 0.153989E+10 | 0.61 | 1263.64 | 01-OCT-02:61 | 0.92 |
November | 0.114749E+10 | 0.52 | 1263.64 | 01-NOV-02:61 | 0.93 |
December | 0.114261E+10 | 0.50 | 1263.64 | 01-DEC-03:01 | 0.93 |
Annual Sum or Average | 0.224530E+11 | 0.65 | |||
Minimum of Months | 0.103650E+10 | 0.50 | 1263.64 | 0.91 | |
Maximum of Months | 0.298717E+10 | 0.83 | 1263.64 | 0.93 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 53.13 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 54.21 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 54.46 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 54.95 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 54.66 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 56.02 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 56.32 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 56.35 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 56.07 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 54.77 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 55.02 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 54.52 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 53.13 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 56.35 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 43.33 | 43.33 | 4000.92 | 15381.40 | 17-JAN-13:30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 54.21 | 54.21 | 3916.42 | 15289.07 | 01-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 54.45 | 54.45 | 3669.96 | 14633.25 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:02 | 54.93 | 54.93 | 3293.63 | 13350.23 | 01-APR-12:17 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 46.98 | 46.98 | 2919.89 | 11879.55 | 01-MAY-12:30 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 56.01 | 56.01 | 2633.64 | 10529.92 | 01-JUN-12:37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 56.32 | 56.32 | 2508.33 | 9740.28 | 01-JUL-13:00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 56.35 | 56.35 | 2601.31 | 10365.62 | 31-AUG-13:00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 56.09 | 56.09 | 2857.58 | 11606.97 | 30-SEP-12:30 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 47.33 | 47.33 | 3228.54 | 13125.81 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 55.03 | 55.03 | 3608.05 | 14433.29 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 54.53 | 54.53 | 3883.80 | 15252.59 | 31-DEC-13:20 |
Annual Sum or Average | 0.00 | 3256.55 | ||||||
Minimum of Months | 0.00 | 0.00 | 43.33 | 43.33 | 2508.33 | 9740.28 | ||
Maximum of Months | 0.00 | 0.00 | 56.35 | 56.35 | 4000.92 | 15381.40 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.405871E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.408309E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.743669E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.122586E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.180350E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.206287E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.219061E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.210080E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.169920E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.108225E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.590502E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.392191E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.147056E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.392191E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.219061E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.201454E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.315086E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.627241E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.109001E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.167919E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.189196E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.204197E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.199501E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.177265E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.980659E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.495925E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.252834E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.133440E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.201454E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.204197E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.229757E+10 | 0.139551E+10 | 0.411167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207643E+10 | 0.549190E+10 | 0.115210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230626E+10 | 0.180235E+11 | 1639832.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.227820E+10 | 0.348996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.259171E+10 | 0.543711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.280267E+10 | 0.648317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.298579E+10 | 0.746358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.295779E+10 | 0.731745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252021E+10 | 0.580726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.233171E+10 | 0.311155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222995E+10 | 0.126572E+11 | 0.150381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229741E+10 | 0.272779E+10 | 0.247298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296757E+11 | 0.431397E+12 | 0.788877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.207643E+10 | 0.139551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.298579E+10 | 0.746358E+11 | 0.411167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.113979E+10 | 0.294088E+10 | 0.106596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103650E+10 | 0.785221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123877E+10 | 0.197420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160825E+10 | 0.358725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232711E+10 | 0.558022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.266121E+10 | 0.638099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.298717E+10 | 0.721848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.297122E+10 | 0.722187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.265295E+10 | 0.646340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153989E+10 | 0.338848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114749E+10 | 0.148719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114261E+10 | 0.497641E+10 | 22620364.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224530E+11 | 0.448790E+12 | 0.129216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103650E+10 | 0.294088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.298717E+10 | 0.722187E+11 | 0.106596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.229757E+10 | 0.00 | 0.00 | 0.132986E+10 | 0.431285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207643E+10 | 0.00 | 0.00 | 0.366405E+09 | 0.164026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230626E+10 | 0.00 | 0.00 | 501334.30 | 0.512993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.227820E+10 | 0.00 | 0.00 | 0.00 | 0.998036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.259171E+10 | 0.00 | 0.00 | 0.00 | 0.154433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.280267E+10 | 0.00 | 0.00 | 0.00 | 0.178260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.298579E+10 | 0.00 | 0.00 | 0.00 | 0.189203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.295779E+10 | 0.00 | 0.00 | 0.00 | 0.180502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252021E+10 | 0.00 | 0.00 | 0.00 | 0.144718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.233171E+10 | 0.00 | 0.00 | 0.00 | 0.849083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222995E+10 | 0.00 | 0.00 | 47488173.56 | 0.362759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229741E+10 | 0.00 | 0.00 | 0.792786E+09 | 0.831712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296757E+11 | 0.00 | 0.00 | 0.253704E+10 | 0.114844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.207643E+10 | 0.00 | 0.00 | 0.00 | 0.431285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.298579E+10 | 0.00 | 0.00 | 0.132986E+10 | 0.189203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.113979E+10 | 0.00 | 0.00 | 36287544.38 | 0.838463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103650E+10 | 0.00 | 0.00 | 0.00 | 0.211436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123877E+10 | 0.00 | 0.00 | 0.00 | 0.503364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160825E+10 | 0.00 | 0.00 | 0.00 | 0.929187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232711E+10 | 0.00 | 0.00 | 0.00 | 0.144648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.266121E+10 | 0.00 | 0.00 | 0.00 | 0.162584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.298717E+10 | 0.00 | 0.00 | 0.00 | 0.174325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.297122E+10 | 0.00 | 0.00 | 0.00 | 0.169789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.265295E+10 | 0.00 | 0.00 | 0.00 | 0.150736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153989E+10 | 0.00 | 0.00 | 0.00 | 0.826670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114749E+10 | 0.00 | 0.00 | 0.00 | 0.381176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114261E+10 | 0.00 | 0.00 | 7782438.13 | 0.137794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224530E+11 | 0.00 | 0.00 | 44069982.51 | 0.110943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103650E+10 | 0.00 | 0.00 | 0.00 | 0.838463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.298717E+10 | 0.00 | 0.00 | 36287544.38 | 0.174325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.634168E+10 | 0.00 | 0.00 | 7042732.47 | 0.00 | 0.294343E+10 | 0.181230E+10 | 0.00 | 3.57 |
February | 0.415723E+10 | 53445802.06 | 0.00 | 18072542.28 | 0.00 | 0.617750E+09 | 0.211681E+10 | 0.00 | 3.60 |
March | 0.141559E+10 | 0.183033E+10 | 0.00 | 21861873.41 | 1191059.52 | 0.00 | 0.183631E+10 | 0.00 | 3.65 |
April | 42957574.28 | 0.730778E+10 | 0.00 | 4482889.40 | 84424303.19 | 0.00 | 0.285673E+09 | 0.00 | 3.72 |
May | 2245635.74 | 0.161710E+11 | 0.00 | 482679.05 | 0.275717E+09 | 0.00 | 572023.20 | 0.00 | 3.83 |
June | 0.00 | 0.219555E+11 | 0.00 | 103864.85 | 0.472678E+09 | 0.00 | 493645.55 | 0.00 | 3.89 |
July | 0.00 | 0.273328E+11 | 0.00 | 89426.42 | 0.542593E+09 | 0.00 | 428296.59 | 0.00 | 3.93 |
August | 440765.38 | 0.260240E+11 | 0.00 | 266024.82 | 0.465461E+09 | 0.00 | 66363.87 | 0.00 | 3.92 |
September | 1044348.95 | 0.186775E+11 | 0.00 | 505136.42 | 0.307256E+09 | 0.00 | 242603.23 | 0.00 | 3.89 |
October | 0.304208E+09 | 0.533402E+10 | 0.00 | 8746972.89 | 18455171.01 | 0.00 | 0.843795E+09 | 0.00 | 3.71 |
November | 0.284613E+10 | 0.811441E+09 | 0.00 | 22140949.36 | 0.00 | 33906812.85 | 0.227915E+10 | 0.00 | 3.63 |
December | 0.636488E+10 | 0.00 | 0.00 | 12179916.06 | 0.00 | 0.144841E+10 | 0.217721E+10 | 0.00 | 3.57 |
Annual Sum or Average | 0.214764E+11 | 0.125498E+12 | 0.00 | 95975007.42 | 0.216778E+10 | 0.504349E+10 | 0.113531E+11 | 0.00 | 3.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 89426.42 | 0.00 | 0.00 | 66363.87 | 0.00 | 3.57 |
Maximum of Months | 0.636488E+10 | 0.273328E+11 | 0.00 | 22140949.36 | 0.542593E+09 | 0.294343E+10 | 0.227915E+10 | 0.00 | 3.93 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128366E+11 | 0.00 | 0.00 | 37880524.85 | 0.00 | 0.00 | 0.167671E+11 | 0.00 | 6.57 |
February | 0.642853E+10 | 0.00 | 0.00 | 54556424.48 | 0.00 | 0.00 | 0.148971E+11 | 0.00 | 6.66 |
March | 0.115364E+10 | 0.349384E+09 | 0.00 | 86563313.93 | 387872.90 | 0.00 | 0.125201E+11 | 0.00 | 6.94 |
April | 0.175379E+09 | 0.535903E+10 | 0.00 | 50503916.73 | 15595644.13 | 0.00 | 0.310582E+10 | 0.00 | 7.93 |
May | 10835190.36 | 0.197249E+11 | 0.00 | 4139676.77 | 49551011.55 | 0.00 | 85256835.26 | 0.00 | 9.50 |
June | 0.00 | 0.284659E+11 | 0.00 | 206730.73 | 50490834.16 | 0.00 | 8276405.43 | 0.00 | 10.55 |
July | 0.00 | 0.365584E+11 | 0.00 | 93076.02 | 40615212.41 | 0.00 | 4822819.46 | 0.00 | 11.19 |
August | 455481.55 | 0.365373E+11 | 0.00 | 258613.34 | 47025740.73 | 0.00 | 31015523.87 | 0.00 | 11.12 |
September | 4467127.37 | 0.298415E+11 | 0.00 | 807157.02 | 78767192.77 | 0.00 | 93635569.54 | 0.00 | 10.47 |
October | 0.478293E+09 | 0.342274E+10 | 0.00 | 64906126.35 | 9407897.83 | 0.00 | 0.471956E+10 | 0.00 | 7.66 |
November | 0.274060E+10 | 74132.82 | 0.00 | 89683070.63 | 0.00 | 0.00 | 0.153582E+11 | 0.00 | 6.79 |
December | 0.104134E+11 | 0.00 | 0.00 | 48351981.56 | 0.00 | 0.00 | 0.176352E+11 | 0.00 | 6.59 |
Annual Sum or Average | 0.342422E+11 | 0.160259E+12 | 0.00 | 0.437951E+09 | 0.291841E+09 | 0.00 | 0.852261E+11 | 0.00 | 8.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 93076.02 | 0.00 | 0.00 | 4822819.46 | 0.00 | 6.57 |
Maximum of Months | 0.128366E+11 | 0.365584E+11 | 0.00 | 89683070.63 | 78767192.77 | 0.00 | 0.176352E+11 | 0.00 | 11.19 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.290584E+11 | 0.104036E+11 | 0.788358E+11 | 0.328296E+10 | 0.121340E+19 |
February | 0.341325E+11 | 0.651737E+10 | 0.560308E+11 | 0.238385E+10 | 0.113820E+19 |
March | 0.489784E+11 | 0.142750E+10 | 0.341747E+11 | 0.121116E+10 | 0.132490E+19 |
April | 0.580964E+11 | -0.613089E+10 | -0.685098E+10 | 48794171.37 | 0.138650E+19 |
May | 0.628575E+11 | -0.142041E+11 | -0.456940E+11 | -458623753.3 | 0.145510E+19 |
June | 0.576013E+11 | -0.186387E+11 | -0.628410E+11 | -885069795.1 | 0.138890E+19 |
July | 0.466570E+11 | -0.223293E+11 | -0.777395E+11 | -0.104778E+10 | 0.125060E+19 |
August | 0.393945E+11 | -0.223075E+11 | -0.765693E+11 | -802908378.5 | 0.120410E+19 |
September | 0.414157E+11 | -0.166306E+11 | -0.610000E+11 | -480038227.0 | 0.117830E+19 |
October | 0.398567E+11 | -0.437390E+10 | 0.396786E+10 | 0.665724E+09 | 0.139030E+19 |
November | 0.326791E+11 | 0.355036E+10 | 0.477624E+11 | 0.176527E+10 | 0.132490E+19 |
December | 0.260835E+11 | 0.934944E+10 | 0.740482E+11 | 0.341922E+10 | 0.123080E+19 |
Annual Sum or Average | 0.516811E+12 | -0.733666E+11 | -0.358750E+11 | 0.910256E+10 | 0.154860E+20 |
Minimum of Months | 0.260835E+11 | -0.223293E+11 | -0.777395E+11 | -0.104778E+10 | 0.113820E+19 |
Maximum of Months | 0.628575E+11 | 0.104036E+11 | 0.788358E+11 | 0.341922E+10 | 0.145510E+19 |